Trane VariTrac VAV-SVN03A-EN, VariTrac X13650940010, VariTrac X13650942010 Installation Manual

Installation Manual
VariTrac
Central Control Panel
June 2002 VAV-SVN03A-EN
VariTrac Central Control Panel Installation Manual
Use of the software contained in this package is provided under a software license agreement. Unauthorized use of the software or related materials discussed in this manual can result in civil damages and criminal penalties. The terms of this license are included with the compact disk. Please read them thoroughly.
Trane has tested the system described in this manual. However, Trane does not guarantee that the system contains no errors.
Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change.
Trane may have patents or pending patent applications covering items in this publication. By providing this document, Trane does not imply giving license to these patents.
The following are trademarks or registered trademarks of Trane: Reliatel, Tracker, Trane, VariTrac, VariTrane, and Voyager.
VAV-SVN03A-EN
Printed in the U.S.A.
© 2002 American Standard Inc. All rights reserved.
Contents
About This Manual ............................................ 1
Contents .............................................................................................................. 1
Compliance Information .............................................................................. 1
Specifications ............................................................................................... 1
VariTrac Changeover Bypass System ......................................................... 1
Overview ................................................................................................ 1
Getting Started ...................................................................................... 1
Installing and Configuring the System ................................................ 1
Troubleshooting .................................................................................... 1
Delivered VAV System ................................................................................. 1
Overview ................................................................................................ 1
Getting Started ...................................................................................... 1
Installing and Configuring the System ................................................ 1
Naming Conventions ......................................................................................... 2
Cautionary Statements ...................................................................................... 2
Related Literature ............................................................................................... 2
FCC Information ............................................... 3
VariTrac and Delivered VAV Radio and Television Interference ........................ 3
VariTrac Changeover-Bypass System ................ 5
Overview ............................................................................................................. 5
Central Control Panel ................................................................................... 5
Unit Control Module (UCM) ........................................................................ 5
VariTrac Damper........................................................................................... 5
Communicating Sensor/Bypass Damper Control ...................................... 6
VariTrac Bypass Damper ....................................................................... 6
Communicating Sensor/Bypass Control .............................................. 6
Auxiliary Temperature Sensor ..................................................................... 6
Zone Temperature Sensors .......................................................................... 6
CO2 Sensor ................................................................................................... 7
Occupancy Sensor ....................................................................................... 7
Operator Display (optional) ......................................................................... 7
Service Model Number Description ........................................................... 7
Specifications ................................................... 9
VariTrac Central Control Panel ........................................................................... 9
Operator Display .............................................................................................. 10
VAV-SVN03A-EN i
UCM Damper .................................................................................................... 10
Communicating Sensor/Bypass Control Assembly ........................................ 11
Relay Board Binary Outputs ............................................................................. 11
Wire Specifications ........................................................................................... 11
Getting Started ............................................... 13
Unpack and Inspect the Components ............................................................. 13
Mount the Wiring Base ..................................................................................... 14
Mounting Requirements............................................................................ 14
Location................................................................................................ 14
Operating Environment....................................................................... 14
Clearances ............................................................................................ 14
Secure Termination Module Wall ............................................................... 15
Secure Termination Module to Conduit Box ............................................. 16
Install VariTrac CCP Relay Board ............................................................... 16
Wire AC Power .................................................................................................. 17
CCP Field Wiring ......................................................................................... 17
AC Power Wiring .................................................................................. 18
AC Power Checkout ............................................................................. 18
Binary Input Wiring .......................................................................................... 18
Priority Shutdown Input Wiring .......................................................... 18
Occupied/Unoccupied Input Wiring ................................................... 19
Output Wiring ................................................................................................... 19
Install the Bypass Dampers and Communicating
Sensor/Bypass Control Assembly ................................................................... 20
Install Bypass Dampers ............................................................................. 20
Bypass Damper Wiring .............................................................................. 21
Mount the Communicating Sensor/Bypass Control ................................ 21
Connect the Communicating Sensor/Bypass Control Wiring ................. 22
Install the VariTrac Dampers ............................................................................ 23
Connect UCM Wiring ................................................................................. 24
Set the UCM DIP Switches ........................................................................ 25
Slaved Dampers ............................................................................................... 26
Install the Zone Temperature Sensors ............................................................. 28
Location ...................................................................................................... 28
Mounting Standard and Digital Zone Temperature Sensors ................... 29
Wall Mount........................................................................................... 29
Junction Box Mount ............................................................................ 29
Zone Temperature Sensor Wiring .............................................................. 30
Communication Link Wiring ............................................................................ 32
Mount Main Module .................................................................................. 36
Install Operator Display (optional) ............................................................ 37
Connecting Modem Devices ..................................................................... 38
VAV-SVN03A-ENii
Connecting PC with VariTrac Software to CCP ......................................... 39
Installation Checklist...................................... 41
Shipment .................................................................................................... 41
Unit Location .............................................................................................. 41
AC Power Wiring ........................................................................................ 41
Communicating Sensor/Bypass Assembly .............................................. 41
Input Wiring ................................................................................................ 41
Output Wiring ............................................................................................. 41
VariTrac Dampers ....................................................................................... 42
Zone Temperature Sensors ........................................................................ 42
UCM Wiring ................................................................................................ 42
Communication Link Wiring ...................................................................... 42
System Start-Up and Checkout ...................... 43
Pre-power-Up Checkout ................................................................................... 43
Central Control Panel ................................................................................. 43
UCM ............................................................................................................ 43
Occupied Mode ................................................................................... 44
Unoccupied Mode ............................................................................... 44
Powering Down the System ...................................................................... 44
UCM LEDs .................................................................................................. 44
Green LED ............................................................................................ 45
Yellow LED ........................................................................................... 45
Tests and Troubleshooting .............................. 47
Displayed Failures ............................................................................................ 47
Static Sensor Calibration Failure............................................................... 47
Discharge Air Temperature Sensor Failure ............................................... 47
Communication Failure ............................................................................. 47
Zone Sensor Failure ................................................................................... 48
Zone Setpoint Failure ................................................................................ 48
Auxiliary Sensor Failure ............................................................................ 48
Static Pressure Sensor Troubleshooting ................................................... 48
Zone, Auxiliary and System Temperature Sensor Checkout ................... 48
UCM Local Heat Checkout ......................................................................... 50
Central Control Panel Input/Output Test .......................................................... 50
Binary Input Tests ....................................................................................... 50
Communicating Sensor/Bypass Control Test ........................................... 50
Supply Air Temperature Input Test ...................................................... 50
Static Pressure Sensor Input Test ....................................................... 51
Binary Output Test ............................................................................... 51
System Troubleshooting .................................................................................. 51
VAV-SVN03A-EN iii
Delivered VAV System .................................... 53
Overview ........................................................................................................... 53
What is Delivered VAV? ............................................................................. 53
What Delivered VAV is Not ........................................................................ 53
Central Control Panel ................................................................................. 55
Unit Control Module (UCM) ...................................................................... 55
VariTrane VAV Terminal Units .................................................................... 55
VariTrane VAV Terminal Unit Types ............................................................ 55
Single Duct ........................................................................................... 55
Parallel Fan-Powered ........................................................................... 55
Series Fan-Powered ............................................................................. 55
Auxiliary Temperature Sensor ............................................................. 56
Zone Temperature Sensors ................................................................. 56
CO
Sensor ........................................................................................... 56
2
Occupancy Sensor............................................................................... 56
Operator Display.................................................................................. 56
Getting Started ............................................... 57
Installing the Central Control Panel................................................................. 57
Install VariTrane VAV Terminal Units ................................................................ 57
Connect UCM Wiring ................................................................................. 57
Set UCM DIP Switches ............................................................................... 57
Installing Zone Temperature Sensors ....................................................... 57
Communications Link Wiring .................................................................... 57
Installation Checklist...................................... 63
Shipment .................................................................................................... 63
Unit Location .............................................................................................. 63
AC Power Wiring ........................................................................................ 63
Input Wiring ................................................................................................ 63
VariTrane Terminal Units ............................................................................ 63
Zone Temperature Sensors ........................................................................ 63
UCM Wiring ................................................................................................ 63
Communication Link Wiring ...................................................................... 64
Completing Central Control Panel Assembly ................................................. 64
Mount Main Module .................................................................................. 64
Install Operator Display ............................................................................. 64
Connecting Modem Devices ..................................................................... 64
VAV-SVN03A-ENiv
About This Manual
Contents
This manual describes the steps required to install and configure VariTrac Changeover Bypass Zoning and Delivered VAV Systems. Sections in this manual are highlighted below:
Compliance Information
Information about FCC approval and possible radio and telephone interfer­ence, and the CE compliance statement.
Specifications
Technical specifications for VariTrac Central Control Panel unit and system components.
VariTrac Changeover Bypass System
Overview
A brief description of a typical VariTrac changeover bypass system.
Getting Started
Pre-installation and setup information.
Installing and Configuring the System
Installation and configuration information, including an installation check­list.
VAV-SVN03A-EN 1
Troubleshooting
General troubleshooting guidelines for common problems.
Delivered VAV System
Overview
A brief description of a typical delivered VAV system.
Getting Started
Pre-installation and setup information.
Installing and Configuring the System
Installation and configuration information, including an installation check­list.
About This Manual
Naming Conventions
The following is a list of naming conventions used in this manual:
CCP: Refers to the system Central Control Panel
VariTrac: Refers to the CCP used in a pressure dependent bypass zoning
system
Delivered VAV: Refers to the CCP used with a Commercial Voyager VAV
rooftop unit and VariTrane pressure independent VAV boxes
VAV: Variable air volume
Cautionary Statements
The following cautionary statements signal procedures or conditions that require particular attention.
WARNING
Indicates a potentially hazardous situation, which, if not avoided, could result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation, which, if not avoided, may result in minor or moderate injury.
CAUTION
Indicates a situation in which property-damage-only accidents could occur. It is also used to alert against unsafe practices.
IMPORTANT
Alerts installer, servicer, or operator to potential actions that could cause the product or system to operate improperly, but will not likely result in potential for damage.
Related Literature
VAV-SVX01B-EN: UCM 4.0 and Wireless VAV Communication
VAV-SLB006-EN: Zone Occupancy Sensor
VAV-SLB007-EN: Digital Display Zone Sensor
VAV-SLB008-EN: Zone and Duct CO2 Sensor
VAV-SVP01A-EN: VariTrac Operator’s Guide
VAV-SVN03A-EN2
FCC Information
VariTrac and Delivered VAV Radio and Television Interference
VariTrac and Delivered VAV generate, use, and can radiate radio frequency energy. If not installed and used in accordance with the instruction manual, interference to radio and television reception may occur. VariTrac and Delivered VAV are tested and comply with the limits for Class A computing devices in accordance with the specifications in Subpart J of Part 15 of FCC rules, to provide reasonable protection against such interference in a commercial installation.
There is no guarantee that interference will not occur in a particular installation. If interference does occur, consult a radio or television technician for suggestions to correct the problem. Also, the booklet
Identify and Resolve Radio-TV Interference Problems
U.S. Government Printing Office, Washington, DC 20402.
Order stock #004-000-00345-4.
is available from the
How to
VAV-SVN03A-EN 3
FCC Information
The manufacturer hereby declares that the product:
Conforms to the following standards or other normative documents:
'HFODUDWLRQRI&RQIRUPLW\
Manufacturer’s Name:
Manufacturer’s Address:
Product Name:
Product Number:
Product Option:
Electromagnetic Emission:
(by Council Directive 89/336/EEC)
Electromagnetic Immunity:
Trane 4833 White Bear Parkway Saint Paul, Minnesota 55110 USA
VariTrac CCP Controller X13650940010; X13650942010 Operator Display
EN 50081-1:1998 Radiated EN55022: 1998 Class B limit Conducted EN55022: 1998 Class B limit
EN61326-1:1997 +A1: 1998
EN61000-4-2 ±4 kV contact discharge ±8 kV air discharge EN61000-4-3 3 V/m
EN61000-4-4 ±1 kV
EN61000-4-5 ±1 kV
EN61000-4-6 3 V
EN61000-4-8 30 A/m
EN61000-4-11 1 cycle/100%
When and where issued
Electromagnetic Emission : 4/3/2001 Bounheng Saycocie Electromagnetic Immunity: 4/17/2001 Design/Compliance Engineer Saint Paul, Minnesota USA
Mark of Compliance European Contact
Societe Trane (Epinal, France) 1, rue des Ameriques, B.P. 6 F-88191 Golbey Cedex, France Phone: (33) 329.31.73.00 Fax: (33) 329.81.24.98
This document validates CE conformity of the VariTrac CCP controller.
VAV-SVN03A-EN4
VariTrac Changeover-Bypass System
Overview
VariTrac Changeover-bypass VAV is a comfort system solution designed for light commercial applications. As the name implies, these systems deliver a varying volume of air to multiple zones, each with its own thermostat, while still utilizing a unitary machine with a constant volume fan. Changeover­bypass VAV combines the comfort benefits of VAV with the cost effective­ness and simplicity of packaged unitary equipment.
Central Control Panel
The VariTrac Central Control Panel is the central source of communications and decision making between the individual zones and the air conditioning unit. Connections to the central control panel are:
24 Vac power
binary inputs for an occupied/unoccupied signal and external priority
shutdown signal (optional)
ICS communication bus to the Trane building automation system (op­tional)
UCM communication bus to the zone dampers and communicating sensor/bypass damper control and Trane Voyager™/Reliatel™ rooftop unit
binary outputs to heating, cooling, and fan of non-Voyager or Reliatel rooftop units
Unit Control Module (UCM)
A unit control module is mounted to each individual zone damper. Inputs and outputs consist of the twisted shielded pair communication link, zone temperature sensor, optional CO2 and occupancy sensors, 24 Vac power, damper motor control, and local heat outputs. Local heat may be duct or space mounted, and can be staged electric, pulse-width modulating electric, and modulating or staged two-position hot water.
VariTrac Damper
Each VariTrac damper consists of an integrated 24 Vac actuator and control box that encloses the UCM circuit board. The damper is designed to operate in static pressures up to 1.75 inches wg.
VariTrac dampers are referred to by their dimensions:
round damper sizes are 6, 8, 10, 12, 14, and 16 inches. The dampers con­sists of an 18 gage galvanized steel frame with a round damper blade assembly.
VAV-SVN03A-EN 5
VariTrac Changeover-Bypass System
rectangular damper sizes are 8 x 12, 8 x 14, 8 x 16, 10 x 16, 10 x 20, and
Communicating Sensor/Bypass Damper Control
The communicating sensor/bypass damper assembly is a bypass damper and communicating sensor/bypass control that resides on the same bus as the VariTrac dampers and Voyager/Reliatel rooftop unit.
VariTrac Bypass Damper
Bypass dampers are non-communicating VariTrac dampers which include an integrated actuator with a pre-wired interconnect cable that plugs into the communicating sensor/bypass control.
round bypass damper sizes are 6, 8, 10, and 12 inches. The damper con-
rectangular bypass damper sizes are 14 x 12, 16 x 16, 20 x 20, and 30 x 20
14 x 16 inches. The damper consists of a 16 gage galvanized steel frame and opposed blade damper assembly.
sists of an 18 gage galvanized steel frame with a round damper blade assembly. The round bypass damper operates in duct static pressures up to 1.75 inches wg.
inches. The damper consists of a 13 gage galvanized steel frame and opposed blade damper assembly. The rectangular bypass damper oper­ates in duct static pressures up to 2.00 inches wg.
Communicating Sensor/Bypass Control
The Communicating Sensor/Bypass Control is composed of an integrated UCM board, static pressure, and discharge air temperature sensors. It directly controls the bypass damper and communicates duct conditions to the central control panel.
The static pressure sensor measures duct static pressure and positions the bypass damper(s) to maintain the static pressure setpoint.
The discharge air temperature sensor allows the CCP to determine the heat/ cool action of each individual UCM and cycles the heating and cooling stages to maintain the discharge air temperature. Discharge air temperature setpoints are also edited through the operator display or PC software.
Auxiliary Temperature Sensor
The auxiliary temperature sensor allows the operator to monitor air temperature leaving a reheat device or measure duct temperature for automatic operation of a standalone UCM.
Zone Temperature Sensors
Five zone temperature sensor configurations are available:
sensor only
sensor with adjustable setpoint and communications jack
sensor with night setback override button, cancel button, and communica­tions jack
sensor with adjustable setpoint, night setback override button, cancel button, and communications jack
VAV-SVN03A-EN6
VA DA06 BYP 1
ProductType
Damper Size
VA = VariTrac Product Families D = Damper R = Rectangular Damper A = Development Sequence
DA06 = 6 Damper DA08 = 8 Damper DA10 = 10 Damper DA12 = 12” Damper DA14 = 14” Damper DA16 = 16” Damper RA0812 = 8 x 12 Zone Damper RA0814 = 8 x 14 Zone Damper RA0816 = 8 x 16 Zone Damper RA1016 = 10 x 16 Zone Damper RA1020 = 10 x 20 Zone Damper RA1418 = 14 x 18 Zone Damper RA1412 = 14 x 12 Bypass Damper RA1616 = 16 x 16 Bypass Damper RA2020 = 20 x 20 Bypass Damper RA3020 = 30 x 20 Bypass Damper
Inventory Number
Damper Control
BYPS = Bypass Control BYR = Rectangular Bypass Control CHGR = Changeover Control ELEC = 3 Stage, Primary Heat Disabled Control NCHW = 1 Stage, Primary Heat Enabled
CO2 Sensor
sensor with digital display, adjustable setpoint, night setpoint override button, cancel button, and communications jack
CO2 Sensor
A CO2 sensor may be connected to the UCM damper control to sense CO levels in the space. This signal is communicated to the CCP for demand ventilation calculation and control.
2
Occupancy Sensor
A normally open occupancy sensor contact may be connected to the UCM damper control binary input to indicate zone occupancy.
Operator Display (optional)
A 1/4 VGA monochrome LCD touch screen display is available for the CCP. This display provides setup, diagnostic, and seven-day scheduling functions to the system.
Service Model Number Description
Service model numbers determine product characteristics and are used when ordering replacement parts. Each digit signifies product characteris­tics. See Figure 1.
Figure 1: Service Model Number Description
VAV-SVN03A-EN 7
VariTrac Changeover-Bypass System
Figure 2: VariTrac Changeover Bypass System Configuration
VariTrac
Zone Damper
Voyager or
Reliatel TCI-3
Bypass Damper
(w/connecting cable assembly)
Zone
Sensor
Communications Link (2 cond, Level 4 comm wire)
24 Vac
Sensor wiring
Legend
Communicating
Sensor/Bypass
Control Assembly
24 Vac
Transformer
VariTrac Central
Control Panel
VAV-SVN03A-EN8
Specifications
VariTrac Central Control Panel
stnemeriuqeRrewoP
deriuqer
AV03,esahpelgnis,zH06,caV03-02
remrofsnart2ssalCmuminim
tnemnorivnEgnitarepO
tnemnorivnEegarotS
tenibaC
gnitnuoM
snoisnemiD
thgieW
gniriWkniLnoitacinummoC
tupnIyraniB
detar
.xobtiudnoc
.peed.ni
sdnuop5.1
.snoitacificepS
cdV41ot01
Am41ot01
evitaler%09ot01,F°221otF°23
gnisnednoc-non,ytidimuh
evitaler%59ot5,F°581otF°04-
gnisnednoc-non,ytidimuh
munelp,erusolcneniser1AMEN
roecafrusllawnoyltceridtnuoM
.ni4x.ni4dessecernotnuom
57.2xediw.ni52.01xhgih.ni57.8
ebtsumgniriwknilnoitacinummoC
riapdedleihsdetsiwtGWA224leveL
reppocdennitdednartshtiweriw
eriwlatotmumixaM.srotcudnoc
teemtsumeriW.teef0053sihtgnel
eeS.snoitacificepsenarT
eriWkniLnoitacinummoC
:)PCCcarTiraVybdedivorp(egatloV
:)PCCcarTiraVybdedivorp(tnerruC
ebyamstcatnocyrdylnO:etoN
.stupniyranibotdehcatta
VAV-SVN03A-EN 9
lavorppALU
pukcaByromeM
.devorppaLU
.yltnenamrep
silenaPlortnoClartneCcarTiraVehT
-rotarepolla,ssolrewopanopU carTiraVehtniderotsataddetide
deniatniamsilenaPlortnoClartneC
Specifications
Operator Display
stnemeriuqeRrewoP
tnemnorivnEgnitarepO
tnemnorivnEegarotS
tenibaC
gnitnuoM
snoisnemiD
thgieW
.PCCeht
F°221otF°23
gnisnednoc
F°581otF°04-
gnisnednoc
detar
.peed
sdnuop3
ybderewopsiyalpsidrotarepoehT
-non,ytidimuhevitaler%09ot01
-non,ytidimuhevitaler%59ot5
munelp,erusolcneniser1AMEN
PCCcarTiraVotnoyltceridsgulP
.ni5.1xediw.ni52.01xhgih.ni57.8
UCM Damper
stnemeriuqeRrewoP
tnemnorivnEegarotS
xoBlortnoC
01,esahpelgnis,zH06,caV03ot02
lanoitpofodaolsulp(muminiMAV
remrofsnart2ssalC)stuptuotaeh
deriuqer
F°021otF°23
tnemnorivnEgnitarepO
gnisnednoc
F°002otF°05-
gnisnednoc
detarmunelp
gniriWkniLnoitacinummoC
.snoitacificepS
-non,ytidimuhevitaler%09ot01
-non,ytidimuhevitaler%59ot5
,erusolcnelatem1AMEN
ebtsumgniriwknilnoitacinummoC
riapdedleihsdetsiwtGWA224leveL
reppocdennitdednartshtiweriw
eriwlatotmumixaM.srotcudnoc
teemtsumeriW.teef0053sihtgnel
:1elbaTeeS.snoitacificepsenarT
eriWkniLnoitacinummoC
VAV-SVN03A-EN10
Communicating Sensor/Bypass Control Assembly
Communicating Sensor/Bypass Control Assembly
51,esahpelgnis,zH06,caV03ot02
stnemeriuqeRrewoP
deriuqer
F°021otF°23
tnemnorivnEgnitarepO
gnisnednoc
F°002otF°05-
tnemnorivnEegarotS
gnisnednoc
remrofsnart2ssalCmuminimAV
-non,ytidimuhevitaler%09ot01
-non,ytidimuhevitaler%59ot5
xoBlortnoC
gniriWkniLnoitacinummoC
detarmunelp
.snoitacificepS
,erusolcnelatem1AMEN
ebtsumgniriwknilnoitacinummoC
riapdedleihsdetsiwtGWA224leveL
reppocdennitdednartshtiweriw
eriwlatotmumixaM.srotcudnoc
teemtsumeriW.teef0053sihtgnel
:1elbaTeeS.snoitacificepsenarT
eriWkniLnoitacinummoC
Relay Board Binary Outputs
Voltage provided: 24 Vac from air conditioning unit
Current: 10 VA maximum
Wire Specifications
Shielded Level 4 communication wire is now recommended for all commu­nication link wiring on the new VariTrac CCP. This is the same wire which is recommended for the Tracker Version 10 Comm5 communication link.
The term Level 4 is used to specify a particular performance of communi­cation wire and is normally associated with LonTalk™. Level 4 wire is differ­ent from Category IV (four) wire and Category V (five) wire. The specification information for Level 4 wire can be found in the “LonWorks™ FTT-10A Free Topology Transcei ver Users Guide” at www.echelon.com.
VAV-SVN03A-EN 11
Shielded Level 4 communication wire can be purchased from two qualified suppliers: Windy City Wire and Connect-Air.
Specifications
Table 1: Communication Link Wire Specifications
.rp1:dnoCforebmuN eulbthgil:roloCtekcaJ
noitacificepS
03/7:dnartS.dnoC
"900.0:hcni.kcihttekcaJ.moN
"671.0:hcniDOmoN
22:TFMrepthgieW
detaRPMCmunelP4leveL,dedleihS,srotcudnoCGWA22
"510.0:nillaw.kcihttekcaJ.moN
noitalusnI
remylopdedocrolocedargmuimerP
)munelp(yollaremyloplarutanedargmuimerP
tekcaJ
)munelp-non(CVPRSedargmuimerP
C°57+otC°0morfesurofelbatiuS
V003fognitardetsegguS
dleihS
gnigakcaP
noitacilppA
sleer
®
skroWnoLetaroprocni
ygolonhcet
gnidnuorgetatilicafoteriwniardreppocdennit
tahtsnoitacilppahtiwelbitapmoceraselbacllA
yrtsudnI
slavorppA
noitallatsni527ro/dna008elcitrACENniesurof
dednartsasulp,liofmunimuladetroppusretseylopllarevO
rosloops)m503(.tf0001snotractuo-yap;)m503(.tf0001
selbacCTLPro/dnaP2LC,PMC,MCepyTsaLUybdetsiL
4mmoC:etoN rofstimilknil
carTiraVwen
secived53,)niahcysiad(teef0053
PCC
VAV-SVN03A-EN12
Getting Started
Familiarize yourself with the system components and preview the installation procedures before installing and configuring the VariTrac system.
Installation and configuring procedures appear in suggested order of performance:
Unpack and inspect the components
Mount the wiring base
Wire AC power
Binary input wiring
Output wiring
Install communicating sensor/bypass damper control
Install bypass damper(s) and connect to communicating sensor/bypass
control assembly
Install VariTrac dampers
Connect UCM wiring
Set UCM DIP switches
Install slaved dampers (if used)
Install zone temperature sensors
Communication link wiring
Mount main module
Install operator display (optional)
Connecting modem devices
IMPORTANT
The CCP is designed to work with UCM III and IV VariTrac damper and VariTrane VAV controllers produced beginning January 1995. If any other dampers are used (especially on a retrofit job), please consult the factory to confirm VariTrac Central Control Panel compatibility prior to installa­tion.
Unpack and Inspect the Components
Inspect components for damage. Match each component to the packing list to ensure that nothing was lost during shipment. Make sure that the litera­ture is not lost or discarded with the packing material. Visually inspect the central control panel for damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred in shipping must be filed with the carrier.
VAV-SVN03A-EN 13
Getting Started
Mount the Wiring Base
Figure 3: Termination module conduit access and mounting holes
Conduit connector
Holes for mounting on a 2 in. x 4 in. conduit box horizontally (left and right)
Two holes for mounting on a wall (one on each side)
Conduit access (three places)
Termination board
Holes for mounting on a 2 in. x 4 in.
Holes for mounting on a 4 in. x 4 in. conduit box (four corners)
Jamb nut (attaches to conduit connector)
conduit box vertically (top and bottom)
Mounting Requirements
Location
The VariTrac Central Control Panel should be mounted at a convenient level and located where it will be easily accessible. If possible, locate the CCP near the controlled equipment to reduce wiring cost.
Operating Environment
The VariTrac Central Control Panel is designed for indoor use only. It should be located in a dust-free and corrosive-free environment, and within a range of 32° to 120°F, and 10 to 90 percent humidity (non-condensing).
Clearances
Mount the VariTrac Central Control Panel on any vertical flat surface. The CCP is approximately 8.75 inches high, 10.25 inches wide and 2.75 inches deep.
VAV-SVN03A-EN14
Secure Termination Module to Wall
The VariTrac Central Control Panel should be easily accessible for making wiring connections and for servicing. Provide two inches of clearance on the left and right sides, and sufficient clearance above the unit to make conduit connections. Sufficient space should be available in front of the unit to making wiring connections and perform maintenance.
Figure 4: Dimensions for VariTrac Central Control Panel Components
Top view
8.75 in. (22.38 cm)
10.25 in. (26.04 cm)
Front view
2.75 in. (6.99 cm)
Side view
VAV-SVN03A-EN 15
Bottom view
Secure Termination Module to Wall
1 Mark the location of the two mounting holes on the wall.
2 Set the termination module aside and drill mounting holes.
3 Secure the termination module to the wall with the supplied hardware
(#10 x 1 in. screw with plastic anchor).
Getting Started
Secure Termination Module to Conduit Box
1 Remove the screws from the conduit box.
2 Line up the conduit box screw holes on the termination module (Figure 3)
with the screw holes on the conduit box.
3 Install the screws.
NOTE: When mounting the termination module to a 4 in. x 4 in. conduit box, remove the plastic cover over the box for easier access. Do not attempt to break away excess plastic. Use a hack saw blade and carefully cut away the plastic.
Install VariTrac CCP Relay Board
1 Separate the main module and front panel from the termination module.
2 Remove the relay board from its packaging.
3 Orient the relay board so that its 20-pin socket connector faces left (see
Figure 5).
4 Slide the left edge of the board underneath the catches on the left side.
5 Rotate the board to the catches on the right side.
6 Snap the board into place by pressing on the terminal block or on the
right side of the board.
Figure 5: Installing Optional Relay Board
VAV-SVN03A-EN16
US O
U
/
3
0
3
5
ge
5
er
3
3
4
n
d
Wire AC Power
Wire AC Power
CCP Field Wiring
Field wiring to the VariTrac Central Control Panel includes:
AC power wiring
binary input wiring
communication link wiring
binary output wiring (requires optional relay board)
These procedures are detailed in the following sections. Refer to Figure 6 for wiring connections.
Figure 6: Field Wiring
Termination Board TB2
Line volta
Legen
mm
li
mm
Transformer
=
Figure note
=
Termination resistor
Twisted pair, shielded wire
=
per Trane specifications
=
Shield termination
=
Contact points
=
Earth ground
Shield ground
=
Vac
ED
T
W
RI
RI
H
UNOC
Comm4 UCMComm4 UCM
+
+
Comm4 link
-
-
Splice
Comm5 UCMTrack
AA
Comm5 link
BB
Splice
Figure Notes
1 All customer wiring must be in acordance with national, state, and local electrical codes.
2 Trane recommends a dedicated transformer for 24 Vac power.
3 Do not apply voltage to the priority shutdown and occupancy inputs.
4 Example of Comm5 communication link wiring. See product-specific literature for Comm5 wire connection details.
OCC
1
MM4
1
M
1
VAV-SVN03A-EN 17
Getting Started
AC Power Wiring
A dedicated 24 Vac, 30 VA Class 2 transformer is required to power the VariTrac Central Control Panel.
The VariTrac Central Control Panel requires 3-wire service with a nominal voltage of 24 Vac and a utilization range of 20 to 30 Vac. All wiring must comply with the National Electrical Code and local codes.
The 24 Vac line can enter the VariTrac Central Control Panel cabinet through the 4 in. x 4 in. knockout or through the knockouts in the top of the panel.
Figure 3 shows the 24 Vac conduit entry holes. Connect the 24 Vac power wires to TB2-1 and TB2-2 and the ground wire from the circuit breaker panel ground to TB2-3 as shown in Figure 6. Use copper conductor wire only.
AC Power Checkout
After the 24 Vac connections have been made at TB2, apply AC power by closing the circuit breaker for the Class 2 transformer.
Measure the voltages at TB2. The voltage between:
TB2-1 and TB2-2 should be 20 to 30 Vac.
TB2-1 and TB2-3 (ground) should be 20 to 30 Vac.
TB2-2 and TB2-3 (ground) should be 20 to 30 Vac.
IMPORTANT
The 24 Vac power supplies must not be used to power any devices other than the VariTrac Central Control Panel. This could result in malfunction of the VariTrac Central Control Panel due to electrical noise.
WARNING
To prevent death or injuries from electrical shock, disconnect external power to the VariTrac Central Control Panel before making power connec­tions.
WARNING
When measurements are made with power on, use care to prevent injuries or death from electrical shock.
Binary Input Wiring
Use 18-22 AWG twisted pair copper conductor wire for binary input wiring. Wire run should be limited to less than 1,000 feet to avoid electrical noise problems.
Refer to Figure 6 for proper connection of binary inputs.
Priority Shutdown Input Wiring
This input closes the connection between TB2-6 and TB2-7. The most likely source of this input is a building management system or fire control panel, but any other device allowing a dry contact connection may be used. When the connection is open, the VariTrac Central Control Panel operates normally. When the connection is closed, the CCP goes into priority shutdown.
VAV-SVN03A-EN18
Occupied/Unoccupied Input Wiring
Occupied/Unoccupied Input Wiring
This input closes the connection between TB2-8 and TB2-9. This is most likely from an external time clock, but any other device allowing a dry contact connection may be used. When the connection is open, the VariTrac Central Control Panel operates in the occupied mode. When the connection is closed, the CCP operates in the unoccupied mode.
CAUTION
Do not run binary input wires and AC power wires together in the same conduit or wire bundles.
CAUTION
Controlling the binary inputs on multiple VariTrac Central Control Panels from a single contact closure is not permitted.
Output Wiring
Use only copper conductors for output wiring. The recommended wire size is 16-22 AWG. Do not run output wires in the same conduit or wire bundle with any AC power wires other than VariTrac Central Control Panel 24 V power.
ac
Output wires should enter the cabinet through the conduit entry holes shown in Figure 3. Output wiring connections at the VariTrac Central Control Panel are shown in Figure 7.
The wire from the air conditioning unit to the CCP consists of one wire from each stage of heating, cooling, the supply fan, and the leg of the 24 Vac power source at the air conditioning unit. 24 Vac power single transformer systems terminate power at Rh and Rc (TB1-1 andTB1-2). Two transformer systems terminate the heating transformer at Rh (TB1-2) and the cooling transformer at Rc (TB1-1).
The remaining wires are terminated per the diagram in Figure 7.
Binary output relay contacts are rated at 24 Vac, 1 amp 24 VA pilot duty.
IMPORTANT
All output wiring must comply with applicable electrical codes. Metal conduit may be required by local codes.
IMPORTANT
Output wires run in the same conduit or wire bundle with any AC power wires other than VariTrac Central Control Panel 24 Vac power could cause the VariTrac Central Control Panel to malfunction due to electrical noise.
VAV-SVN03A-EN 19
Getting Started
Figure 7: Binary Output Wiring for Optional Relay Board
Termination Board TB1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
24 V*
Ht. Pump
W1 Y2 Y 1 G Rh Rc
AUX W2/O
*24 Vac from the rooftop unit. For single transformer systems, connect Rc to Rh. For two transformer systems, connect the cooling transformer to RC and the heating transformer to Rh.
NOT USED NC NO
FAN
COMP1
C1
COMP2
C2 Ht1
EM HT
Ht22H/2C
C/O24 V* FAN
Install the Bypass Dampers and Communicating Sensor/Bypass Control Assembly
Install Bypass Dampers
Bypass damper(s) should be located before the first zone runs out from the supply air duct. VariTrac dampers or supply duct branches should be installed downstream of bypass dampers. The distance between bypass dampers and the communicating sensor/bypass control should be two to three equivalent duct diameters.
In a ducted return system, bypass dampers will be ducted directly to the return air duct.
In systems with plenum return, bypass damper(s) should be ducted into the return air riser. Confirm that sufficient relief or exhaust exists to prevent return plenum pressurization. See Figure 8.
IMPORTANT
The use of a relief fan or backdraft damper is strongly recommended in the return air system. This will prevent bypassed air from pressurizing the return air duct system and spilling out of return grills into conditioned space, especially when the unit is in economizer mode.
VAV-SVN03A-EN20
Bypass Damper Wiring
Bypass Damper Wiring
The interconnect cable is pre-wired to the bypass damper and may be lengthened if necessary.
IMPORTANT
Mounting screws must be located towards the ends of the damper when hanging straps are used to avoid interference with the rotating damper. A label attached to the dampers indicates the acceptable areas for mounting screws.
IMPORTANT
The bypass damper must be positioned to orient the drive shaft horizon­tally. Failure to do this may result in drive train malfunction (see Figure
11).
IMPORTANT
It is important to note the airflow direction when installing dampers. A label for this is present on each damper assembly.
Mount the Communicating Sensor/Bypass Control
Figure 8: Mounting the Bypass Damper Communicating Sensor/Bypass
Control Assembly
Voy ag er Micro Control
Heating and Cooling Coils
3
1
Bypass Damper
Ductwork
1. Avoid high pressure turns and transitions
2. Use hard duct
3. Mount communicating Sensor/Bypass Controller 2-3 duct diameters upstream of bypass damper
2
Return Air Duct
VAV-SVN03A-EN 21
The communicating sensor/bypass control is located between the supply fan and the bypass damper in the least turbulent location possible. It is recommended that the distance between the control and the nearest up­stream transition be two to three equivalent duct diameters.
Getting Started
If the supply duct branches out at the riser, install the control in the largest supply duct.
A two-inch hole is required to insert the temperature and static pressure sensor. Use the supplied gasket to seal off air leaks. Secure the sensor to the duct with a minimum of three sheet metal screws.
IMPORTANT
The sensor assembly should be mounted on the side of the duct to keep the pressure transducer in a vertical orientation. Do not install horizontally on the top or bottom of a duct.
Connect the Communicating Sensor/Bypass Control Wiring
The pre-wired interconnect cable plugs into the actuator connector inside the control. The cable is designed to connect in one orientation only.
Refer to the diagram and connect as follows:
1 Plug the red actuator connector brom the BYPS damper onto the master
damper UCM socket (ACT) as shown in Figure 9.
2 If two bypass dampers are used, connect the second bypass damper’s
red actuator plus to the spare connector socket pigtailed on the first BYPS damper cable assembly.
3 If cable assembly needs to be extended, cut and splice additional wire on
the BYPS damper end of the cable.
Figure 9: Wiring the Communicating Sensor/Bypass Control
Close
Step 2
Address
Switch
Open
Hot
Actuator
Step 1
DDC/UCM
Control Board
To NEC Class 2
24V Transformer
Load 8 VA (without actuator)
Static
Pressure
Port
Pressure
Transducer
Female plug end of bypass sensor assembly cable
Male plug end located on DDC/UCM control board
Shielded Twisted Pair
Communications Wiring
Air Supply
Temp Sensor
DDC/UCM
Control Board
Step 1
VAV-SVN03A-EN22
Install the VariTrac Dampers
Install the VariTrac Dampers
A sketch of basic damper installation is shown in Figure 10. The damper may be connected with hard duct or flex duct at either end.
If two bypass dampers are installed, a pigtail socket is provided on the cable so the second damper can be plugged into the UCM.
IMPORTANT
Mounting screws must be located towards the ends of the damper when hanging straps are used to avoid interference with the rotating damper. A label attached to the dampers indicates the acceptable areas for mounting screws.
IMPORTANT
It is important to note airflow direction when installing the damper. A label for this is present on each damper assembly.
IMPORTANT
The control box on each damper must be positioned to orient the drive shaft horizontally. Failure to do this may result in drive train malfunction. (See Figure 11.)
Figure 10: VariTrac Damper Installation
VAV-SVN03A-EN 23
Getting Started
Figure 11: Proper Damper Mounting Positions
Connect UCM Wiring
Connect the power to terminals TB1-1 (24V) and TB1-2 (ground). 24 Vac is required to power the UCM control. 20 Vac to 28 Vac is acceptable. Use 18 to 20 AWG for power wiring.
The power consumption for an auto-changeover cooling-only UCM (model CHGR) is 10VA.
Local heat outputs are rated at 10VA maximum for each output. To determine the total UCM power requirements, add the power consumption of local heat to the circuit board power.
CAUTION
Use wires with copper conductors only. The use of aluminum or other types of wire may result in overheating and equipment damage.
CAUTION
Connecting a shared UCM power supply with reversed polarity will cause damage to the UCM, TCI, and central control panel.
CAUTION
When powering multiple UCMs from one transformer, polarity must be maintained. Terminal TB1-1 is designated positive (+) and Terminal TB1-2 is negative (–) to unit casing ground.
IMPORTANT
UCM control box cover must be replaced after field wiring to prevent electromagnetic interference.
VAV-SVN03A-EN24
Figure 12: UCM Wiring
Set the UCM DIP Switches
VAV-SVN03A-EN 25
Set the UCM DIP Switches
Each device connected to the VariTrac Central Control Panel must a unique address. No two devices (of the same type) can have the same address. Table 2 lists the address settings for UCM DIP switches connected to the VariTrac Central Control Panel.
IMPORTANT
The UCM located in the communicating sensor/bypass control must always be addressed as #33.
DIP Switch Settings
Addresses 25-32 used for Delivered VAV only
UCM
Number
1
2
3
4
6
5
ON
ON
ON ON
ON
ON
ON ON
ON
ON ON ON ON
ON
ON ON
ON
ON ON
ON
ON ON ON ON
ON ON ON ON ON ON ON ON
ON
ON ON
ON
ON
ON ON
ON
ON
ON ON ON
ON
ON ON
ON
ON
ON
ON ON ON
ON ON ON ON ON ON ON
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON
ON ON ON ON ON ON ON
= Off
01 02 03 04 05 06 07 08 09 10
11 12 13 14 15 16 17 18 19 20 21 22 23 24
25 26 27 28 29 30 31
ON ON ON ON ON
32
ON ON ON ON
33
Communicating Sensor/Bypass Control only
Getting Started
Table 2: DIP Switch Settings for UCM Damper Addresses
Slaved Dampers
In some applications it may be desirable to control an additional damper from a single UCM. The slaved damper does not require a UCM circuit board. For this reason a model BYPS damper is paralleled directly to the
ON
Example of Address #5
VAV-SVN03A-EN26
Close Open
Hot
Actuator
Slaved Dampers
outputs of the UCM controlling the primary damper by using the BYPS damper cable assembly shipped with the BYPS damper.
Refer to diagram and connect as follows:
1 Disconnect the red actuator plug from the master damper UCM.
2 Plug the red actuator connector from the BYPS damper onto the master
damper UCM socket (ACT) as shown in Figure 13.
3 Reconnect the master damper actuator’s red connector to the spare
connector socket pigtailed on the BYPS damper cable assembly.
4 If cable assembly needs to be extended, cut and splice additional wire on
the BYPS damper end of the cable.
Figure 13: Wiring for Slaved Damper
To NEC Class 2
24V Transformer
Load 8 VA (without actuator)
Step 3
Address
Switch
Steps 1 & 2
DDC/UCM
Control Board
Female plug end of bypass sensor assembly cable
Male plug end located on DDC/UCM control board
DDC/UCM
Control Board
Steps 1 & 2
Shielded Twisted Pair
Communications Wiring
VAV-SVN03A-EN 27
Getting Started
Install the Zone Temperature Sensors
Five types of zone temperature sensors are available. The sensors are shown below in Figure 14:
• sensor with night setback override button, cancel button, and communica­tions jack
• sensor with adjustable setpoint, night setback override button, cancel button, and communications jack
• sensor with adjustable setpoint and communications jack
• sensor with night setback override button, cancel button, and communica­tions jack
• sensor only
• sensor with digital display, adjustable setpoint, night setpoint override button, cancel button, and communications jack.
Figure 14: Zone Sensor Options
Location
Proper temperature sensor location is crucial to occupant comfort. The sensor should be placed in the most critical area of the zone where there is free circulation of air. It should be mounted on a flat interior surface approximately 54 inches from the floor, or as specified by the project plans and specifications.
Avoid locating sensors in the following places:
• areas of direct sunlight
• areas blanketed by air from diffusers or subject to drafts
• surfaces with unconditioned areas behind them (such as an outside wall or the wall of a storeroom)
VAV-SVN03A-EN28
Mounting Standard and Digital Zone Temperature Sensors
• areas near heat sources like equipment (appliances, computers, copiers, etc.) or concealed pipes or chimneys
• dead spots behind doors, draperies, or in corners.
Mounting Standard and Digital Zone Temperature Sensors
Zone temperature sensors consist of two basic pieces: the base and cover. Externally adjustable versions have an external adjustment knob. To remove the sensor cover from the base:
1 Note the position of the adjustment knob (if present).
2 Use a small screwdriver to gently pry the adjustment knob from the
cover.
3 Before mounting a zone temperature sensor, remove zone sensor cover
by easing the tip of a small screwdriver between the base and the cover. Gently lift the top of the screwdriver up. Do not force.
Follow these steps to replace the zone temperature sensor cover and (if present) adjustment knob after mounting:
1 Align the cover with the sides of the base.
2 Press the cover toward the wall until it snaps into place.
3 Align the knob to the position noted prior to its removal.
4 Push the stem through the cover hole until the stem sits firmly in setpoint
potentiometer.
5 Turn the knob to assure that it rotates freely through the entire range of
temperature settings.
Wall Mount
With the cover removed, feed the control wires through the rectangular opening in the base. Follow these steps if mounting the sensor to a wall:
1 Assuring that the base is level, position the back of the base over the wire
entry in the wall.
2 Mark the centers of the two oblong mounting holes, then set aside the
base.
3 Drill a 3/16 in. diameter hole approximately 1 in. deep at the marked
locations.
4 Insert plastic anchors into the holes until they are firmly seated.
5 Feed the control wires through the base and fasten the base to the wall
with the supplied mounting screws.
VAV-SVN03A-EN 29
6 Connect the control wires to the proper terminals on the temperature
sensor (See Figure 15).
7 Replace the sensor cover.
Junction Box Mount
1 With the cover removed, feed the control wires through the rectangular
opening in the base.
Getting Started
2 Using two #6-32 screws, fasten the base to the junction box’s threaded
mounting holes.
3 Connect the control wires to the proper terminals on the temperature
sensor (See Figure 15).
4 Replace the sensor cover.
Zone Temperature Sensor Wiring
A zone temperature sensor designed specifically for UCM damper control must control each unit. Field wiring for the zone temperature sensors must meet local code. If local codes require enclosed conductors, the zone tem­perature sensor wires should be installed in conduit
Do not route zone temperature sensor wires in conduit with 24V or any other high power conducting wires.
Different numbers of conductors are required based on the zone temperature sensor used. The following table lists the options and number of wires required.
Table 3: Zone Sensor Options
forebmuN
noitpOrosneSenoZ
deriuqeR
1
seriW
ylnorosneS2
tniopteselbatsujdahtiwrosneS3
edirrevokcabtesthginhtiwrosneS
snottublecnacdna
2
dnatniopteselbatsujdahtiwrosneS
lecnacdnaedirrevokcabtesthgin
3
snottub
dnayalpsidDCLhtiwrosneS
thgindnatniopteselbatsujda
2
5
snottublecnacdnaedirrevokcabtes
1. Some sensors have a communication jack available as an option. If these jacks
are used, they must be wired to the UCM using a separate two-conductor, shielded cable that meets the specification for communication link wiring. Tape back the shield of the communication link (if used) at the zone temperature sensor and splice the other end into the adjoining communication link shield. The communication jacks do not need to be wired for the system to operate properly.
VAV-SVN03A-EN30
Zone Temperature Sensor Wiring
2. 3 wires are required for sensor connection. 2 wires are required for 24 Vac power
connection. For wire lengths less than 75 feet, an 18 gage, 5 conductor cable may be used. For wire lengths greater than 75 feet, use 18 gage, 2 conductor cable for the power wiring (TB1-TB1), and 18 gage, 3 conductor cable for signal wiring (TB2-TB3).
Figure 15: Zone Temperature Sensor Controller Wiring
VAV-SVN03A-EN 31
Getting Started
Communication Link Wiring
The VariTrac Central Control Panel communication link (TB2-10, 11, and 12) connects the CCP, UCM dampers, communicating sensor/bypass damper control assembly, and Voyager/Reliatel rooftop units. Field wiring for the communication link must meet the following requirements:
• All wiring must be in accordance with the National Electrical Code and local codes.
• Communication link wiring must be Level 4 22 AWG twisted, shielded pair wire (meets or exceeds Trane specifications. See wiring specifications sections in this manual for further information).
• The maximum total wire length is 3,500 feet for the communication link.
At the VariTrac Central Control Panel, the communication link wires must be connected to Terminals TB2-10 (+) and TB2-11 (−). Refer to Figure 17. This connection is polarity sensitive.
IMPORTANT
Connections between lengths of link wiring should be soldered and taped. Wire nuts are not acceptable.
CAUTION
Connecting the communication link with reversed polarity will lead to system malfunction and possible equipment damage.
The shield on the communication link wiring must be connected to TB2-12. The shield wire should be spliced with the shield from the next section of communication link wiring at every junction. Tape each splice to prevent any contact between the shield and ground. The shield should be cut and taped back at the end of the link.
Communication link wiring cannot pass between buildings.
IMPORTANT
Improper communication link shield connections will lead to system malfunction.
IMPORTANT
Improper communication link routing will lead to system malfunction.
Connect UCMs on the communication link in a daisy-chain configuration. With this configuration, it is easier to solve communication problems by isolating portions of the communication link. See Figure 16 for an example of a daisy-chain configuration.
VAV-SVN03A-EN32
Communication Link Wiring
Figure 16: Daisy Chain Configuration for Communication Link Wiring
VariTrac Central Control Panel
UCM Dampers
UCM Dampers
UCM Dampers
UCM Dampers
UCM Dampers
UCM Dampers
Each Voyager/Reliatel Rooftop requires a Trane communications interface (TCI) board for connection to the VariTrac Central Control Panel communication link.
Refer to the TCI installation manual for more information on connecting a rooftop to the communication link.
VAV-SVN03A-EN 33
Getting Started
Figure 17: UCM Communication Link Wiring
VariTrac
1
2
3
4
5
6
Termination Board TB2
Static
Pressure Port
VOUT
DDC / UCM
Control Board
Pressure
Transducer
Assembly Address #33
Switch
Address
Communicating Sensor / Bypass Control
+
7
8
9
10
Air Supply Temp Sensor
COM
M 4
COMM 5
-
11
12
e
Splic
15
13
14
2
DDC / UCM
Control Board
Zone UCM Address #1
Switch
Address
DDC / UCM
Control Board
Zone UCM Address #2
Switch
Address
2
Splice
1 2
3 through 24
To Zone Dampers
Note
The UCM order in this drawing is for demonstration purposes only.
Figure Notes
1 Shield must be cut back and taped at last unit controller.
2 A continuous shield is required. At each unit controller, splice shield
wire and tape back to prevent grounding.
Twisted pair, shielded wire
per Trane specifications
=
end
No specific order is required on the Comm link.
Figure note
Shield ground
=
=
Leg
VAV-SVN03A-EN34
Figure 18: Voyager Communication Link Wiring
VariTrac Communications
Interface (Comm4)
Comm Termination Details for Voyager RTU
Voyager Communication Link Wiring
Voyager (UPC)
Unit Control Panel
1
2
(TCI-V)
Figure Notes
1 All dip switches off.
2 Comm board to non-isolated
Comm3 or Comm4 option.
VAV-SVN03A-EN 35
Getting Started
VariTrac Communications
Comm Termination Details for Voyager RTU
Figure 19: Precedent Communication Link Wiring
Interface (Comm4)
Trane Communication
Interface-Precedent
1
2
(TCI-P)
Figure Notes
1 All dip switches off.
2 Comm board to non-isolated
Comm3 or Comm4 option.
Mount Main Module
After mounting and wiring the wiring base, attach the main module.
NOTE: It is not necessary to turn off 24 Vac power to the wiring base prior to mount­ing and removing the main module.
• Verify that all the wires on the wiring base are securely fastened in place.
• Carefully line up the alignment pins on the wiring base with the back of the main module (Figure 20).
Precedent (UCP)
Unit Control Panel
VAV-SVN03A-EN36
Figure 20: Mounting Main Module
Termination module
Main module
Alignment pin (four places)
Mounting Main Module
VAV-SVN03A-EN 37
IMPORTANT
Do not use excessive force when mounting the module. If the module does not snap easily into place, slightly reposition it on the alignment pins. Failure to comply may cause damage to the module.
Firmly push the main module onto the wiring base until it snaps into place.
If 24 Vac is applied, the main module will start. The LEDs on the main module will flash on and off after a few seconds
Install Operator Display (optional)
An operator display is available to provide monitoring and control of VariTrac systems and UCM zones from one central location. The display provides a ¼ VGA touch screen to allow the operator to interface with the system. Temperature and system failure diagnostics and Voyager and Precedent Rooftop unit alarms are indicated on the operator display screen and in PC software.
NOTE: It is not necessary to turn off 24 Vac power to the wiring base prior to mount­ing and removing the operator display.
After mounting the main module, attach the operator display.
• Tilt the top of the operator display about 30 degrees towards you.
Getting Started
• Align the three tabs on the bottom of the display with the slots in the bottom of the main module. (Figure 21).
• Starting with the center tab, insert the tabs into the slots.
Figure 21: Install operator display
IMPORTANT
Do not use excessive force when mounting the module. If the module does not snap easily into place, slightly reposition it on the alignment pins. Failure to comply may cause damage to the module.
Push the top of the display module toward the main module until it snaps into place.
If 24 Vac is applied, the operator will turn on and display data.
Connecting Modem Devices
Remote communications may be accomplished through a Trane building management system or with stand-alone modem attached to a single CCP via the RS-232 port.
A US Robotics Sportster™ fax/data external modem is recommended for CCP applications. Modems require hardware and software configurations for use with the CCP
Physical connection of the modem to the VariTrac Central Control Panel is shown in Figure 22.
VAV-SVN03A-EN38
Figure 22: Modular Adapters, Cable, and Connections for External Modems
Termination module bottom view
RJ-12 port (PC direct connection)
Connecting Modem Devices
RJ-12 port for PC direct connection (bottom side)
To modem serial port
RJ-12 cable
(PN: 35914260)
Connect RJ-12 to 25-pin male adapter
(PN: 35914269)
Connecting PC with VariTrac Software to CCP
The VariTrac PC Software provides a graphic user interface for VariTrac and Delivered VAV systems. Advanced status and set-up information are avail­able via a PC serial port connection.
Install the PC software on your PC following the instructions provided with the software CD.
Connect your PC to the Central Control Panel as shown in Figure 23. The connection is made using a PC serial port adapter and cable:
Adapter: DB9 female to RJ12 (PN: 3591 4262) Cable: RJ12 to RJ12 (PN: 3591 4260)
VAV-SVN03A-EN 39
Getting Started
Figure 23: Typical VariTrac Central Control Panel to PC serial port connec-
tions
Termination module bottom view
RJ-12 port (PC direct connection)
RJ-12 port for PC direct connection (bottom side)
Connect RJ-12 to 9-pin female adapter (PN: 35914262)
To PC serial port
RJ-12 cable (PN: 35914260)
VAV-SVN03A-EN40
Installation Checklist
Complete this checklist as the VariTrac Central Control Panel is installed to verify that all recommended procedures are performed. This checklist does not replace the detailed instructions provided in the manual. Read the entire manual carefully to become familiar with the installation procedures before installing the unit.
Shipment
o Inspect VariTrac Central Control Panel for shipping damage. File claim if
necessary.
o Inspect zone dampers and accessories for shipping damage. File claim if
necessary.
Unit Location
o Install VariTrac Central Control Panel in environment that meets tempera-
ture and humidity requirements.
o Securely mount VariTrac Central Control Panel on wall at an accessible
location with proper clearances.
AC Power Wiring
o Field installed AC power wiring complies with all applicable codes.
o 24 Vac line from dedicated Class 2 transformer connected to VariTrac
Central Control Panel at TB2.
o Voltage measured at TB2-1 to TB2-2 is 20 to 30 Vac.
o Assure that a reliable earth ground has been attached to TB2-3.
Communicating Sensor/Bypass Assembly
o Bypass damper(s) properly installed between supply/return ductwork per
instructions.
o Communicating Sensor/Bypass Control mounted and wired to the
bypass damper(s).
o Communication cable properly terminated at the Communicating Sensor/
Bypass Control and routed back to VariTrac Central Control Panel.
Input Wiring
o Field installed input wiring complies with all applicable codes.
o Optional time clock and priority shutdown inputs terminated at TB2-6
through TB2-9 per instructions.
VAV-SVN03A-EN 41
Output Wiring
o Field installed output wiring complies with all applicable codes. If used,
relay wiring is terminated at TB1-1 through 11 per instructions.
Installation Checklist
VariTrac Dampers
o UCM dampers mounted and secure according to recommendations.
Zone Temperature Sensors
o Sensors are properly mounted and wired per instructions and in the
correct space.
UCM Wiring
o UCM power is properly wired to TB1-1 and TB1-2.
NOTE: TB1-2 is COMMON (case ground) if grounded secondary transformers are being used. Confirm polarity from one UCM to the next if more than one UCM is being powered from a single transformer.
o Confirm voltage present between 20 Vac and 28 Vac.
o Ensure that the sensor is properly terminated.
o If optional local heat is being used, confirm wiring per appropriate
diagram.
Communication Link Wiring
o Field installed communications wiring complies with all applicable codes.
o VariTrac Central Control Panel communication link wiring to UCMs is
connected at TB2-10, TB2-11, and TB2-12 on the CCP.
o Communication link wiring is properly terminated at each zone damper
UCM on terminals TB2-1 through TB2-6. Ensure that polarity (+ -) has been maintained through the link.
o Communication link wire shields spliced at each device junction and
taped to prevent contact with earth ground.
VAV-SVN03A-EN42
System Start-Up and Checkout
Pre-power-Up Checkout
Central Control Panel
• Measure the supply voltage to the CCP TB2-1 and TB2-2. The supply voltage should be between 20 Vac and 30 Vac.
• Assure that a reliable ground is attached to TB2-3 on the CCP.
• Check the UCM communication link to assure that the wire designated (+) is connected to the TB2-10 and the wire designated (–) is terminated at the TB2-11. The shield must be connected to TB2-12.
WARNING
The following test should not be performed until all people and equipment are clear of the air conditioning unit.
If the air handling unit is controlled by the optional field installed relay board, check the operation of the supply fan and heating and cooling stages by jumping the appropriate terminals of the binary output terminal block TB1. This check assures that the wires are properly terminated at the CCP and that the air conditioning unit is operational.
UCM
• Verify that the damper is installed with the drive shaft horizontal. See the Installation and Wiring section of this manual for more details.
• Check to assure that all mounting screws are a minimum of three inches away from the center damper bead if hanging straps are used. This allows full rotation of the damper.
• Check the supply voltage at TB1-1 and TB1-2. Polarity is important. Notice that TB1-1 is designated 24V and TB1-2 is designated ground to unit casing ground. The acceptable voltage present is 20 Vac to 28 Vac.
CAUTION
Connecting a shared UCM power supply with reversed polarity will cause damage to the UCM, TCI, and Central Control Panel.
When powering multiple UCMs from one transformer, polarity must be maintained. Terminal TB1-1 is designated 24V and Terminal TB1-2 is GND to unit casing ground.
• Verify that communications wiring is terminated at TB2-1 (+) and TB2-2 (–). Polarity is important.
• Verify that zone sensor connections are correct as detailed in the Installa­tion and Wiring section of this manual.
VAV-SVN03A-EN 43
System Start-Up and Checkout
• Verify that the proper unit address is set on each UCM.
Occupied Mode
After the system is completely wired and installed it is ready for the initial power-up. Upon power-up the CCP and UCMs will initiate the sequence of events that follows.
IMPORTANT
For the CCP start-up sequence to begin, it is necessary for one UCM and a communicating sensor/bypass control on the loop to communicate with the CCP.
• The CCP prepares for static calibration.
• UCMs begin driving closed to perform their calibration reset.
• After calibration, the UCMs are driven to maximum position, and the bypass begins to close.
• The “zero flow” voltage reading is taken with the fan off.
• System fan is turned on for approximately 45 seconds.
• High flow static sensor voltage is taken and stored in the CCP.
• The bypass damper is then driven to 50 percent and released.
• The UCMs are released from their MAX flow position.
• UCMs are scanned and heating/cooling callers are established.
• Fan remains on if edited to occupied fan mode “on”.
• Fan energizes if occupied fan mode is edited to “auto” and sufficient requests are present.
• The control action of each UCM changes as appropriate.
• Heating or cooling is staged to maintain the discharge air temperature.
Unoccupied Mode
Each time the CCP enters the unoccupied mode, a static sensor self­calibration sequence takes place.
Powering Down the System
CCP power must be disconnected to avoid unnecessary zone tagging and personal injury during service.
UCM LEDs
Green and yellow LEDs on the circuit board help diagnose communication or circuit board problems. Conditions indicated by the LEDs are:
VAV-SVN03A-EN44
Green LED
UCM LEDs
NO
FFO
Yellow LED
NO
FFO
noitarepOlamroN
draobevitcefedro,rewopcaV42oN
GNIKNILB
draoBevitcefeD
ytiralopknilnoitacinummocdesreveR
ytivitcaknilnoitacinummocoN
draobevitcefedro
WOLS
KNILB
MCUtahtrofdednetnitonknilehtnonoitacinummoC
TSAF
KNILB
PCCehthtiwdetacinummocMCUehT
VAV-SVN03A-EN 45
System Start-Up and Checkout
VAV-SVN03A-EN46
Tests and Troubleshooting
Displayed Failures
Static Sensor Calibration Failure
If static sensor calibration fails, the CCP uses 0.50 inch wg as the static pressure setpoint.
The zone dampers continue to control normally. Failed static sensor calibration may indicate that the position or location of the sensor is not correct. See mounting the communicating sensor/bypass control in this manual. The following conditions create a static sensor calibration failure:
• No UCMs are communicating
• No UCM can be driven to MAX due to group level overrides
• Zero static reading was not in the range of 0.15 to 0.45 Vdc
• High flow static reading is less than 0.10 Vdc greater than the zero static reading
• Fan does not run during the start-up calibration sequence
• Design static pressure value is too low
• Bypass damper(s) are operating incorrectly
Discharge Air Temperature Sensor Failure
If the discharge air temperature sensor fails, the CCP issues a priority shutdown command:
• All zone dampers drive to maximum
• Bypass damper drives to 50 percent
• Fan and all stages of heating and cooling are de-energized
This failure appears in diagnostics on the operator display and PC software
A shorted or open temperature sensor or failed communicating sensor/ bypass control is the cause.
Communication Failure
If communications fails (no UCMs communicating), the CCP:
• De-energizes the fan and all stages of heating and cooling
• Drives the bypass to 50 percent
Individual UCM communications failures are displayed in diagnostics on the operator display and PC software. Check all wiring connections and polarity. See the Communications Troubleshooting section in this manual for details.
VAV-SVN03A-EN 47
Tests and Troubleshooting
Zone Sensor Failure
If the zone sensor fails, the damper drives to minimum position, and its vote is excluded.
Zone Setpoint Failure
If a setpoint fails, the UCM automatically uses the edited occupied cooling and heating setpoints.
Auxiliary Sensor Failure
If the auxiliary sensor circuit opens, the temperature reading on the display screen reads and a diagnostic is be displayed on the operator display and PC software. If the auxiliary sensor is used on a stand alone UCM to establish the control action, the UCM remains in the current control action.
Static Pressure Sensor Troubleshooting
The static pressure sensor signal enables the CCP to recognize system static and adjust the bypass damper accordingly. If a problem exists with the sensor or its location, the bypass damper controls with default values. If a “failure” persists, perform the following:
1 On the communicating sensor/bypass control UCM, read the voltage
across J3-1 (green wire) and J3-3 (red wire). Voltage should be between
4.50 Vdc and 5.50 Vdc.
2 Read the transducer output voltage across J3-1 (green wire) and J3-2
(black wire). Voltage should be between 0.20 Vdc and 0.45 Vdc. Record the zero flow voltage.
3 Wait approximately 4 minutes after power-up for the system fan to start.
Read the transducer output voltage again across J3-1 (green wire) and J3-2 (black wire). The difference between this voltage and the zero flow voltage should be 0.10 Vdc minimum.
4 If a defective transducer is suspected, check the output voltage with a
low-pressure source and Magnahelic gauge. Record the zero flow volt­age. Connect a low-pressure source and Magnahelic gauge to the “hi” port of the transducer. Input 1 inch of pressure. The voltage should be approximately 0.750 Vdc greater than the zero flow voltage. The reading on the voltmeter will include the zero flow voltage.
CAUTION
Do not exceed 2 inches of input pressure to avoid damaging the tranducer.
Signal change must be 0.10 Vdc minimum or a “AHU air flow” “failed” message will be displayed
Zone, Auxiliary and System Temperature Sensor Checkout
If temperature is reported to the UCM or CCP seems wrong use the temperature-resistance table (Table 4) to verify the integrity of the adjustable setpoint potentiometer or the sensor. Measure resistance across the terminals the device is connected to. For details of terminal connections see the Installation and Wiring section of this manual.
VAV-SVN03A-EN48
Zone, Auxiliary and System Temperature Sensor Checkout
Table 4: Temperature Resistance Table
pmeT
03­02-
01-
0
01 02 03 04 05
55 65 75 85 95
06 16 26 36 46 56 66 76 86 96
07 17 27
37 47 57 67 77 87 97
leehwbmuhT
ecnatsiseR
-
-
-
-
-
-
-
-
-
297
277 357 337 417
496 576 656 636 716 795 875 855 935 915
005 184 164 244 224 304 383 463 443 523
rosneS
ecnatsiseR
000142 000071
000121 00088 00046 00074 00053 00062 00002
85961 14561 53161 14751 85351
26941 50641 75241 81931 88531 66231 25621 64321 74321 65021
17711 39411 22211 75901 89601 54401 79101
5999 8179 7849
VAV-SVN03A-EN 49
08
18 28 38 48 58
09
001 021 031 041 051 571 002
603 682 762 742 822 802
-
-
-
-
-
-
-
-
0629 8309
1288 8068 9938 5918
0037 0085 0083 0003 0052 0002 0031
738
Tests and Troubleshooting
UCM Local Heat Checkout
Turn the adjustable zone sensor to full heating, or adjust the temperature setpoints at the CCP.
IMPORTANT
Model DCEA local heat outputs are disabled in the heating control action. Model DCWA local heat outputs are enabled in the heating or cooling control action.
To check the local heat outputs:
• Disconnect any connections to Terminals J8, J9, J10, or J11.
• Place a 500 to 1000 ohm resistor between Terminals common (J8) and the terminals (J9, J10, or J11) tested. This simulates a load condition across the triacs within the circuit board.
• Measure the voltage between J8 (common) and the appropriate output (J9, J10, and J11). When the heat is off, the voltage will measure between 0 and 1.5 Vac. When heat is on, voltage should read 24 Vac.
Central Control Panel Input/Output Test
Binary Input Tests
With the system in the occupied mode:
• Jump the priority shutdown input (TB2-5 and TB2-6) with a wire. The system goes into priority shutdown.
• Remove the jumper on the priority shutdown input. Normal system operation is restored.
• Jump the uncc input with a wire (TB2-6 and TB2-7). The system goes into the unoccupied mode.
• Remove the jumper wire from the uncc input. The system will go into the occupied mode.
Communicating Sensor/Bypass Control Test
The following defines the procedure necessary to test the supply air temperature and static pressure sensor inputs to the communicating sensor/ bypass sensor control:
Supply Air Temperature Input Test
• Disconnect the supply air temperature sensor from communicating sensor/bypass control terminals TB3-6 and TB3-7.
• System goes into priority shutdown.
• Disconnect the static sensor from J3.
• System displays static pressure failure.
• Input a resistance value between 9.4K and 10.5K across terminals TB3-6 and TB3-7. System returns to normal operation.
VAV-SVN03A-EN50
Static Pressure Sensor Input Test
Static Pressure Sensor Input Test
In order to perform this test a voltage between 0.25 Vdc and 0.7 Vdc must be present at J3 pins 2 and 3. This voltage is from the pressure transducer in the communicating sensor/bypass control. If system pressure is insufficient to create at least .25 Vdc apply pressure to the transducer with an alternate pressure source.
CAUTION
Do not over pressurize the transducer. The maximum pressure signal should not exceed 2 inches H20.
When the voltage is between 0.25 Vdc and 0.7 Vdc the static pressure failure clears.
Binary Output Test
The relay board binary outputs may be manually controlled from either the operator display or the PC software.
Great care must be taken when manually controlling these relays. There are NO minimum on-off timers or safe guards in effect during test mode. See the CCP operator guide for complete description of the binary output test.
WARNING
This test can energize the fan and both stages of heating and cooling at the rooftop unit. Before starting this test make sure that all persons, tools, etc. are clear.
System Troubleshooting
Contact your Trane representative for problems that cannot be resolved using these guidelines.
VAV-SVN03A-EN 51
Tests and Troubleshooting
VAV-SVN03A-EN52
Delivered VAV System
Overview
What is Delivered VAV?
Delivered VAV is a small tonnage VAV system made up of three Trane prod­uct families. It is the combination of:
• Voyager Commercial 27 ½ to 50 ton VAV Packaged Rooftop Unit
• Up to 32 VariTrane VAV boxes with DDC Controls
• VariTrac Central Control Panel with Operator Display
Delivered VAV will only work with this combination of Trane products. It will not support any other types of equipment.
The Voyager Commercial 27 ½ to 50 ton rooftop unit must be a VAV model with factory installed inlet guide vanes or variable frequency drive, micro­processor controls, and Trane Communications Interface.
Delivered VAV will support up to 32 VariTrane VAV boxes with the DDC controls option. They may be single duct boxes or fan powered boxes, and may have a factory installed local heat option if desired.
The heart of the system is the VariTrac Central Control Panel with Operator Display. The CCP acts as the communications hub of the system. It is responsible for coordinating the actions of the VAV rooftop and the actions of the VAV boxes with each other to meet the comfort requirements of the zones.
As in any other application, the Voyager Commercial VAV unit runs the supply fan at full constant volume whenever it goes into the heating mode, with all the VAV boxes commanded to maximum flow. For this reason the unit heat is only used for the Morning Warm-up and Daytime Warm-up modes available on the Voyager Commercial unit. In both of these modes the VAV boxes are commanded to maximum flow. If individual zone heat­ing is required during normal daytime operation, a local heat source must be provided at the box.
What Delivered VAV is Not
Delivered VAV is not changeover-bypass VAV. It is a true pressure indepen­dent VAV system. The fact that we utilize the VariTrac Central Control Panel as the heart of the system does not make it a VariTrac system. There is no bypass damper in this system.
Additionally, Delivered VAV will only work with the combination of the Voyager Commercial VAV unit, VariTrane VAV boxes with DDC controls, and the VariTrac CCP with Operator Display. It will not support any other types of equipment.
VAV-SVN03A-EN 53
Delivered VAV System
Figure 24: Delivered VAV System Configuration
VAV
Terminal
Unit
Voyager
Commercial VAV Unit
(27 1/2 to 50 ton)
Zone
Sensor
Communications Link (2 cond, Level 4 comm wire)
24 Vac
Sensor wiring
Legend
24 Vac
Transformer
VariTrac
Central Control Panel
VAV-SVN03A-EN54
w/ Operator Display
Central Control Panel
Central Control Panel
The VariTrac Central Control Panel is the central source of communications and decision making between the individual zones and the air conditioning unit. Connections to the CCP are:
• 24 Vac power
• binary inputs for an occupied/unoccupied signal and external priority shutdown signal (optional)
• ICS communication bus to the building automation system (optional)
• UCM communication bus to the VAV boxes and Trane Voyager commercial 27 ½ - 50 ton VAV rooftop unit
Unit Control Module (UCM)
A unit control module is mounted to each individual VAV terminal unit. Inputs and outputs consist of the twisted shielded pair communication link, zone temperature sensor, optional CO2 and occupancy sensors, 24 Vac power, damper motor control, and local heat outputs. Local heat may be duct or space mounted, and can be staged electric, pulse-width modulating electric, and modulating or staged two-position hot water.
VariTrane VAV Terminal Units
The function of the VariTrane terminal unit in a VAV control zone is to vary the volumetric airflow rate to the zone. VariTrane units are supplied with microprocessor-based DDC controls. Factory-installed controls are required with all types of terminal units.
VariTrane VAV Terminal Unit Types
Single Duct
Single duct terminal units control the volumetric flow of supply air to the space to maintain the zone temperature at setpoint. These units are gener­ally applied in cooling-only VAV zones that require no heat during occupied hours. If local zone heat is necessary, it can be provided either remotely (for example, perimeter heat) or by terminal reheat (either electric or hot water coils).
Parallel Fan-Powered
Parallel fan-powered units are commonly used in VAV zones that require some degree of heat during occupied hours when the primary supply air is cool. The terminal unit fan is in parallel with the central unit fan; no primary air from the central fan passes through the terminal unit fan. The terminal unit fan draws air from the space return plenum.
Series Fan-Powered
VAV-SVN03A-EN 55
Series fan-powered terminal units are used commonly in VAV zones that not only require heat during occupied hours, but also desire constant air vol­ume delivery. The terminal unit fan is in series with the central fan. Primary air from the central fan always passes through the terminal unit fan.
Delivered VAV System
The local series fan within the terminal unit operates whenever the unit is in the occupied mode. The volume of air delivered to the VAV zone is constant, but the temperature of the delivered air varies. As the zone requires less cooling, the primary air damper closes. As the primary air damper closes, the air mixture supplied to the zone contains less cool air and more warm plenum air. Remote heat or terminal reheat can provide additional local heating.
Auxiliary Temperature Sensor
The auxiliary temperature sensor allows the operator to monitor air tem­perature leaving a reheat device or measure duct temperature for automatic operation of a standalone UCM.
Zone Temperature Sensors
Five zone temperature sensor configurations are available:
• sensor only
• sensor with adjustable setpoint and communications jack
• sensor with night setback override button, cancel button, and communica­tions jack
• sensor with adjustable setpoint, night setback override button, cancel button, and communications jack
• sensor with digital display, adjustable setpoint, night setpoint override button, cancel button, and communications jack
CO
Sensor
2
A CO2 sensor may be connected to the UCM damper control to sense CO
2
levels in the space. This signal is communicated to the CCP for demand ventilation calculation and control.
Occupancy Sensor
A normally open occupancy sensor contact may be connected to the UCM damper control binary input to indicate zone occupancy.
Operator Display
A ¼ VGA monochrome LCD touch screen display is installed on the CCP. This display provides setup, diagnostic, and seven-day scheduling functions to the system.
VAV-SVN03A-EN56
Getting Started
Familiarize yourself with the system components and preview the installa­tion procedures before installing and configuring the Delivered VAV system.
Installation and configuring procedures appear in suggested order of performance:
Installing the Central Control Panel
Refer to the following installation procedures for the CCP in this manual
• Unpacking and inspecting the components
• Wiring AC power
• Binary input wiring
NOTE: Ignore the sections referring to Installation of the CCP Relay Board and Binary Output Wiring. Those sections do not apply to this system.
Install VariTrane VAV Terminal Units
Refer to the appropriate installation instructions shipped with the VariTrane air terminal devices for proper installation.
Connect UCM Wiring
Refer to Connect UCM Wiring in this manual, and the appropriate installa­tion instructions shipped with the VariTrane air terminal devices.
Set UCM DIP Switches
Refer to Set UCM DIP Switches and Table 2 in this manual, and the appropri­ate installation instructions shipped with the VariTrane air terminal devices.
Installing Zone Temperature Sensors
Refer to Installing Zone Temperature Sensors in this manual.
Communications Link Wiring
The VariTrac Central Control Panel communication link (TB2-10, 11, and 12) connects the CCP, VAV UCMs, and Voyager VAV rooftop unit. Field wiring for the communication link must meet the following requirements:
• All wiring must be in accordance with the National Electrical Code and local codes.
• Communication link wiring must be Level 4 22 AWG twisted, shielded pair wire (meets or exceeds Trane specifications. See wiring specifications sections in this manual for further information).
• The maximum total wire length is 3,500 feet for the communication link.
VAV-SVN03A-EN 57
Getting Started
At the VariTrac Central Control Panel, the communication link wires must be connected to Terminals TB2-10 (+) and TB2-11 (−). Refer to Figure 26. This connection is polarity sensitive.
IMPORTANT
Connections between lengths of link wiring should be soldered and taped. Wire nuts are not acceptable.
CAUTION
Connecting the communication link with reversed polarity will lead to system malfunction and possible equipment damage.
The shield on the communication link wiring must be connected to TB2-12. The shield wire should be spliced with the shield from the next section of communication link wiring at every junction. Tape each splice to prevent any contact between the shield and ground. The shield should be cut and taped back at the end of the link.
Communication link wiring cannot pass between buildings.
IMPORTANT
Improper communication link shield connections will lead to system malfunction.
IMPORTANT
Improper communication link routing will lead to system malfunction.
Connect UCMs on the communication link in a daisy-chain configuration. With this configuration, it is easier to solve communication problems by isolating portions of the communication link. See Figure 25 for an example of a daisy-chain configuration.
VAV-SVN03A-EN58
Daisy Chain Configuration for Communication Link Wiring
Figure 25: Daisy Chain Configuration for Communication Link Wiring
VariTrac Central Control Panel
with Operator Display
VAV Terminal Unit
VAV Terminal Unit
VAV Terminal Unit
VAV Terminal Unit
VAV Terminal Unit
VAV Terminal Unit
Each Voyager VAV Rooftop requires a Trane communications interface (TCI) board for connection to the VariTrac Central Control Panel communication link.
Refer to the TCI installation manual for more information on connecting a rooftop to the communication link.
VAV-SVN03A-EN 59
Getting Started
Figure 26: UCM Communication Link Wiring
VariTrac
1
2
3
Termination Board TB2
VAV UCM Address #1
Address
4
DDC / UCM
Control Board
Switch
COM
M 4
-
+
5
6
7
8
9
11
10
12
COMM 5
15
13
14
e
2
Splic
DDC / UCM
Control Board
VAV UCM Address #2
Switch
Address
DDC / UCM
Control Board
VAV UCM Address #3
Switch
Address
2
Splice
1 2
4 through 32
To VAV Terminal Units
Note
The UCM order in this drawing is for demonstration purposes only.
Figure Notes
1 Shield must be cut back and taped at last unit controller.
2 A continuous shield is required. At each unit controller, splice shield
wire and tape back to prevent grounding.
Twisted pair, shielded wire
per Trane specifications
=
end
No specific order is required on the Comm link.
Figure note
Shield ground
=
=
Leg
VAV-SVN03A-EN60
Figure 27: Voyager Communication Link Wiring
VariTrac Communications
Interface (Comm4)
Comm Termination Details for Voyager RTU
Voyager Communication Link Wiring
Voyager (UPC)
Unit Control Panel
1
2
(TCI-V)
Figure Notes
1 All dip switches off.
2 Comm board to non-isolated
Comm3 or Comm4 option.
VAV-SVN03A-EN 61
Getting Started
VAV-SVN03A-EN62
Installation Checklist
Complete this checklist as the VariTrac Central Control Panel is installed to verify that all recommended procedures are performed. This checklist does not replace the detailed instructions provided in the manual. Read the entire manual carefully to become familiar with the installation procedures before installing the unit.
Shipment
o Inspect VariTrac Central Control Panel for shipping damage. File claim if
necessary.
o Inspect VAV terminal units and accessories for shipping damage. File
claim if necessary.
Unit Location
o Install VariTrac Central Control Panel in environment that meets tempera-
ture and humidity requirements.
o Securely mount VariTrac Central Control Panel on wall at an accessible
location with proper clearances.
AC Power Wiring
o Field installed AC power wiring complies with all applicable codes.
o 24 Vac line from dedicated Class 2 transformer connected to VariTrac
Central Control Panel at TB2.
o Voltage measured at TB2-1 to TB2-2 is 20 to 30 Vac.
o Assure that a reliable earth ground has been attached to TB2-3.
Input Wiring
o Field installed input wiring complies with all applicable codes.
o Optional time clock and priority shutdown inputs terminated at TB2-6
through TB2-9 per instructions.
VariTrane Terminal Units
o Air terminal units mounted and secure according to recommendations.
Zone Temperature Sensors
o Sensors are properly mounted and wired per instructions and in the
correct space.
UCM Wiring
VAV-SVN03A-EN 63
o UCM power is properly wired to TB1-1 and TB1-2.
NOTE: TB1-2 is COMMON (case ground) if grounded secondary transformers are being used. Confirm polarity from one UCM to the next if more than one UCM is being powered from a single transformer.
Installation Checklist
o Confirm voltage present between 20 Vac and 28 Vac.
o Ensure that the sensor is properly terminated.
o If optional local heat is being used, confirm wiring per appropriate
diagram.
Communication Link Wiring
o Field installed communications wiring complies with all applicable codes.
o VariTrac Central Control Panel communication link wiring to VAV UCMs
and Voyager VAV rooftop unit is connected at TB2-10, TB2-11, and TB2-12 on the CCP.
o Communication link wiring is properly terminated at each zone damper
UCM on terminals TB2-1 through TB2-6. Ensure that polarity (+ -) has been maintained through the link.
o Communication link wire shields spliced at each device junction and
taped to prevent contact with earth ground.
Completing Central Control Panel Assembly
Mount Main Module
Refer to Mount Main Module instructions in this manual.
Install Operator Display
Refer to Install Operator Display instructions in this manual. The Operator Display is required for the Delivered VAV system to function.
Connecting Modem Devices
Refer to Connecting Modem Devices instructions in this manual.
VAV-SVN03A-EN64
Trane An American Standard Company www.trane.com
For more information contact your local district office or e-mail us at comfort@trane.com
Literature Order Number VAV-SVN03A-EN
File Number SV-AH-VAV-000-SVN03A-EN-0602
Supersedes VADA-IN-2
Stocking Location La Crosse
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.
Loading...