Trane VariTrac Dampers Installation and Maintenance Manual

Page 1
Installation Guide
VariTrac™ Dampers
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
September 2010 VAV-SVN04B-EN
Page 2
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage-only
accidents.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to appropriate MSDS and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA70E or other country-specific requirements for arc/flash protection PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow codes could result in death or serious injury.
© 2010 Trane All rights reserved VAV-SVN04B-EN
Page 3
Warnings, Cautions and Notices
Overview of Manual
Note: At least one copy of this document ships with every order and is customer property. It must
be retained by the unit's maintenance personnel.
This booklet describes proper installation procedures for delivered air systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
General
These instructions do not cover all variations in systems nor provide for every possible contingency that may arise at a job site installation.
Inspection
Check carefully for any shipping damage. This must be reported to and claims made against the transportation company immediately. Any missing parts should be reported to your supplier at once and replaced with authorized parts only.
VAV-SVN04B-EN 3
Page 4
Table of Contents
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Damper Descriptions & Actuator Specifications . . . . . . . . . . . . . . . . . . . . . . . . 5
Install Bypass Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Bypass Damper Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installing the Communicating Sensor/Bypass Control . . . . . . . . . . . . . . . . . . . 8
Connect the Communicating Sensor/Bypass Control Wiring . . . . . . . . . . . . . 9
Install the VariTrac Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Connect UCM Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Round Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 1. Round bypass dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2. Round zone dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rectangular Bypass Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 3. Rectangular bypass dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rectangular Zone Damper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 4. Rectangular zone dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Actuator Specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Figure 1. Bypass damper installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 2. Installing the communicating sensor/bypass control . . . . . . . . . . . . . 8
Figure 3. Proper damper mounting positions. . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 4. VariTrac damper installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DIP Switch Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 5. DIP switch settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 5. Typical VariTrac Zone/Changeover Wiring Diagram. . . . . . . . . . . . . 13
4 VAV-SVN04B-EN
Page 5
General
Damper Descriptions & Actuator Specifications
Round Dampers
Cylinder: 18-gage galvanized–rolled and seam welded
Damper: Two 22-gage galvanized steel plates locked together with an elastomeric gasket
sandwiched between.
Actuator: Internal actuator w/synchronous motor and gear reduction is direct coupled to the damper shaft. It has a drive time of 60 seconds.
• Electrical Rating:
Power Supply—24 VAC (20 to 30 VAC) at 50/60 Hz
Transformer Sizing—2.0 VA maximum at nominal voltage, Class 2
Table 1. Round bypass dampers
Size Diameter (in.) Length (in.) Shipping Weight
6 17 17 lbs
8 17 19 lbs
10 17 20 lbs
12 17 21 lbs
14 17 23 lbs
16 17 25 lbs
Table 2. Round zone dampers
Size Diameter (in.) Length (in.) Shipping Weight
Rectangular Bypass Damper
Sheet Metal Box: 22-gage galvanized steel
Length: 16"
Damper Frame: 18-gage galvanized steel
Damper Blades: 18-gage galvanized steel
Damper Shaft: 1/2" Diam.
Table 3. Rectangular bypass dampers
Size W" x H" No. of Blades Shipping Weight
14 x 12 3 16 lbs
16 x 16 4 21 lbs
20 x 20 4 29 lbs
30 x 20 4 40 lbs
61719 lbs
81721 lbs
10 17 22 lbs
12 17 23 lbs
14 17 25 lbs
16 17 27 lbs
VAV-SVN04B-EN 5
Page 6
General
Rectangular Zone Damper
Sheet Metal Box: 22-gage galvanized steel
Length: 16"
Damper Frame: 18-gage galvanized steel
Damper Blades: 18-gage galvanized steel
Crank Bearings: Glass filled Nylon
Damper Shaft: 1/2" Diam.
Table 4. Rectangular zone dampers
Size H" x W" No. of Blades Shipping Weight
Actuator Specification
Actuator Design: 3 Wire 18 ga 24 VAC Floating Point Control, Non-spring return
Actuator Housing: Housing Type—NEMA 1, IP20
Shaft Rotation: All damper shafts rotate counter-clockwise to open
Electrical Rating:
Power Supply—24 VAC (20 to 30 VAC) at 50/60 Hz
Transformer Sizing—2.5 VA maximum at nominal voltage, Class 2
Manual Override: External release lever
Humidity: 90% RH maximum, non-condensing
Temperature Rating:
Ambient – 35°–125°F (2°–52°C)
Shipping and Storage: -20°–150°F (-29°–66°C)
Tor q ue :
Running: 35 lb-in (4 N-m)
Breakaway: 35 lb-in (4 N-m) minimum
Stall: 40 lb-in (4.5 N-m) minimum
Running Time for 90° Rotation:
60 seconds at 60 Hz nominal
72 seconds at 50 Hz nominal
Weight: 1.5 lb (0.68 kg)
08 x 12 2 8 lbs
08 x 14 2 10 lbs
08 x 16 2 12 lbs
10 x 16 2 14 lbs
10 x 20 2 16 lbs
14 x 18 3 18 lbs
Install Bypass Dampers
Bypass damper(s) should be located before the first zone runs out from the supply air duct. VariTrac dampers or supply duct branches should be installed downstream of bypass dampers. The distance between bypass dampers and the communicating sensor/bypass control should be two to three equivalent duct diameters (see Figure 1, p. 7).
6 VAV-SVN04B-EN
Page 7
In systems with plenum return, bypass damper(s) should be ducted into the return air riser. Confirm
Voy ag er Micro Control
Heating and Cooling Coils
Bypass Damper
Return Air Duct
Ductwork
that sufficient relief or exhaust exists to prevent return plenum pressurization.
Important: The use of a relief fan or backdraft damper is strongly recommended in the return
Bypass Damper Wiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
General
air system. This will prevent bypassed air from pressurizing the return air duct system and spilling out of return grills into conditioned space, especially when the unit is in economizer mode.
The interconnect cable is pre-wired to the bypass damper and may be lengthened if necessary.
Important: Mounting screws must be located towards the ends of the damper when hanging
straps are used to avoid interference with the rotating damper. A label attached to the dampers indicates the acceptable areas for mounting screws.
NOTICE
Equipment Damage!
The bypass damper must be positioned to orient the drive shaft horizontally. Failure to do this could result in drive train malfunction (see Figure 1, p. 7).
Important: It is important to note the airflow direction when installing dampers. A label for this
is present on each damper assembly.
Figure 1. Bypass damper installation
VAV-SVN04B-EN 7
Page 8
Installation
Communications Wiring
n
Installing the Communicating Sensor/Bypass Control
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
The communicating sensor/bypass control is located between the supply fan and the bypass damper in the least turbulent location possible. It is recommended that the distance between the control and the nearest upstream transition be two to three equivalent duct diameters.
If the supply duct branches out at the riser, install the control in the largest supply duct.
A two-inch hole is required to insert the temperature and static pressure sensor. Use the supplied gasket to seal off air leaks. Secure the sensor to the duct with a minimum of three sheet metal screws.
Important: The sensor assembly should be installed on the side of the duct to keep the pressure
transducer in a vertical orientation. Do not install horizontally on the top or bottom of a duct.
Note: Each of the three steps below may be found illustrated in Figure 2, p. 8. Each step has a
corresponding oval in the figure.
1. Plug the actuator connector from the BYPS damper onto the master damper UCM socket (ACT).
2. If two bypass dampers are used, connect the actuator plug of the second bypass damper to the spare connector socket pigtailed on the first BYPS damper cable assembly.
3. If the cable assembly needs to be extended, cut and splice additional wire on the BYPS damper end of the cable.
Figure 2. Installing the communicating sensor/bypass control
CLOSE
OPEN
HOT
ACTUATOR
Step 3
SPARE
CONNECTOR
J9
J11
J10
Address
Switch
TB2-1
TB2-2
TB2-3
IN
IN
Shielded T wisted Pair
TB2-4
OUT
J1 1
J7
JB
TB2-5
OUT
W–HOT
BK–OPEN
R–CLOSE
Step 1
ACT BIP
DDC/UCM
Control Board
YEL GRN
TB2-6
TB4-1
ZONE
TB2-1
TB3-1
GND
GND
8 VAV-SVN04B-EN
To NEC Class 2
24V T ransformer
Load 8 VA (without actuator)
24VAC
24V
TB1-1
J3
1
S
3-5
3-6
TB
TB
TB3-3
TB3-2
GND
SET A/CO2
Female plug end of bypass sensor assembly cable
Male plug end located o DDC/UCM control board
A
CT
WH
BK
R
DDC/UCM
Control Board
Step 2
Page 9
Connect the Communicating Sensor/Bypass Control Wiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow code could result in death or serious injury.
The pre-wired interconnect cable plugs into the actuator connector inside the control box. The cable is designed to connect in one orientation only. Refer to the VariTrac Changeover Bypass VAV Literature (VAV-PRC003-EN) for information regarding system wiring.
Install the VariTrac Dampers
A sketch of basic damper installation is shown in Figure 4, p. 10. The damper may be connected with hard duct or flex duct at either end.
If two bypass dampers are installed, a pigtail socket is provided on the cable so the second damper can be plugged into the UCM.
Important: Mounting screws must be located towards the ends of the damper when hanging
straps are used to avoid interference with the rotating damper. A label attached to the dampers indicates the acceptable areas for mounting screws.
Important: It is important to note airflow direction when installing the damper. A label for this
is present on each damper assembly.
Installation
NOTICE
Equipment Damage!
The control box on each damper must be positioned to orient the drive shaft horizontally. Failure to do this could result in drive train malfunction. (See Figure 3, p. 9.)
Figure 3. Proper damper mounting positions
VAV-SVN04B-EN 9
Page 10
Installation
Attach unit to hard duct using a minimum of four sheet metal screws
Attach unit to hard duct using a minimum of four sheet metal screws
Attach flex duct to unit using self-locking plast ic tie st rap. A screw & washer can be used to secure the tie-strap if required.
IMPORTANT:
Mounting screws must be 3" away from damper bend to avoid interference with rotating damper.
Hard or Flex Duct
Hard or Flex Duct
Hard or Flex Duct
Hard or Fle
x
Duct
Figure 4. VariTrac damper installation
10 VAV-SVN04B-EN
Page 11
Connect UCM Wiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ state electrical codes. Failure to follow code could result in death or serious injury.
CAUTION
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in minor to moderate injury.
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Installation
NOTICE
Equipment Damage!
Connecting a shared UCM power supply with reversed polarity will cause damage to the UCM, TCI, and central control panel.
NOTICE
Equipment Damage!
When powering multiple UCMs from one transformer, polarity must be maintained. Terminal TB1-1 is designated positive (+) and Terminal TB1-2 is negative (–) to unit casing ground.
Important: UCM control box cover must be replaced after field wiring to prevent
1. Connect the power to terminals TB1-1 (24V) and TB1-2 (ground). 24 Vac is required to power the
2. The power consumption for an auto-changeover cooling-only UCM (model CHGR) is 10VA.
3. Local heat outputs are rated at 12VA maximum for each output. To determine the total UCM
DIP Switch Settings
Dip switch SW1 contains six switches for addressing the UCM. These switches allow a user to set a unique communication address for each UCM. Each UCM on a given communication link must have a unique address in order for the CCP to communicate to it. Refer to Table 5, p. 12 for UCM
4.1 DIP switch settings.
electromagnetic interference.
UCM control. 20 Vac to 28 Vac is acceptable. Use 18 to 20 AWG for power wiring.
power requirements, add the power consumption of local heat to the circuit board power.
VAV-SVN04B-EN 11
Page 12
Installation
Table 5. DIP switch settings
UCM Unit # Dip 1 Dip 2 Dip 3 Dip 4 Dip 5 Dip 6
1 OFF ON ON ON ON ON
2 ON OFF ON ON ON ON
3OFFOFFONONONON
4 ON ON OFF ON ON ON
5 OFF ON OFF ON ON ON
6ONOFFOFFONONON
7 OFF OFF OFF ON ON ON
8 ON ON ON OFF ON ON
9 OFF ON ON OFF ON ON
10 ON OFF ON OFF ON ON
11 OFF OFF ON OFF ON ON
12 ON ON OFF OFF ON ON
13 OFF ON OFF OFF ON ON
14 ON OFF OFF OFF ON ON
15 OFF OFF OFF OFF ON ON
16 ON ON ON ON OFF ON
17 OFF ON ON ON OFF ON
18 ON OFF ON ON OFF ON
19 OFF OFF ON ON OFF ON
20 ON ON OFF ON OFF ON
21 OFF ON OFF ON OFF ON
22 ON OFF OFF ON OFF ON
23 OFF OFF OFF ON OFF ON
24 ON ON ON OFF OFF ON
(a)
33
(a) Bypass damper must always be addressed at 33.
OFF ON ON ON ON OFF
12 VAV-SVN04B-EN
Page 13
Figure 5. Typical VariTrac Zone/Changeover Wiring Diagram.
Installation
R (HOT)
O (COMMON)
GR (NC CONTACT)
5.
BK (RETURN)
Y
OPTIONAL FIELD INSTALLED
OCCUPANCY SENSOR
3RD STG.
TO J11
2ND STG.
TO J10
1ST STG.
TO J9 TO J8
OPTIONAL FIELD INSTALLED
ELECTRIC HEATER
TO J8
BK (CLOSE)
TO J9
R (OPEN)
TO J10
OPTIONAL FIELD INSTALLED
PROPORTIONAL WATER VALVE
TO J9 TO J8
OPTIONAL FIELD INSTALLED
ON-OFF WA TER VALVE
6.
SENSOR
OPTIONAL FIELD INSTALLED
(TB1-1) 24 VAC) (TB4-1) BIP (TB1-1) 24VAC (TB1-2) GND NOT CONNECTED
HEATER STAGE CONTACTOR(S)
24VAC, 12VA
MAX/COIL
HOT
W (HOT)
CO2
TB3-5
OPTIONAL FIELD INSTALLED
PROP.
WATER
VALVE 24VAC
12VA MAX
ON –OFF
WA TER V ALVE
24 VAC
12VA MAX
(TB1-1) 24V
24V
(TB3-6) GND
GND
(TB3-5) A/CO2
OUT
CO2 SENSOR
TB3-6
6.
AUX TEMP SENSOR
Damper
Actuator
8.
Wiring
BL–HOT
BK–OPEN
R–CLOSE
GND
9
J
J11
J10
ADDRESS
SWITCH
TB2–3
TB2–2
TB2–1
UT
IN
IN
O
SHIELDED
TWISTED PAIR
COMMUNICATIONS
WIRING
J7
TB2–4
OUT
J1
8
J
B2–5 T
9.
ACTUATOR
D.D.C.\U.C.M.
CONTROL BOARD
YEL
TB2–6
D.D.C. U.C.M
CONTROL BOX
1
GRN
BIP
TB4–1
TB3–1
ZONE GND SET
NOTE:
1.
2.
¼" quick connect required for all field connections.
Zone sensor terminals 4 and 5 require shielded twisted pair wiring for
3. communications jack equipped zone sensor option.
4.
No additional wiring required for night setback override (on/cancel). The optional binary input connects between TB4-1 (BIP) and 24VAC (hot) from
5.
transformer. The binary input can be reconfigured as an occupancy input via the communications interface.
As shipped, the AUX input is configured as an AUX input. The AUX input can be
6.
reconfigured as a CO2 sensor input via the communications interface.
7.
S terminal not to be used with VariTrane. If unit mounted transformer is not provided, polarity from unit to unit must be
8.
maintained to prevent permanent damage to control board. If one leg of 24VAC supply is grounded. then ground leg must be connected to TB1-2.
Shields of communications wiring should be tied together and insulated.
9.
Factory wiring
Field wiring
Optional or alternate wiring
TB1–2
TB3–2
TB1–1
TB3–3
A/CO2
24V
TB3–5
TB3–6
GND
J3
TB2-6
5 4 3 2 1
INSTALLED ZONE SENSOR
To 24V
Transformer
1
S
TB3-2
TB2-5
TB3-3
ZONE SENSOR W/ COMM. JACK
REMOTE MTD.
3. 4.
OPTIONAL FIELD
TB3-1
TB3-1
TB3-2
2
1
ZONE SENSOR
REMOTE MTD.
4.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
VAV-SVN04B-EN 13
Page 14
Page 15
Page 16
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2010 Trane All rights reserved
VAV-SVN04B-EN 10 Sep 2010
Supersedes VAV-SVN04A-EN May 2008
Produced with paper that uses fewer trees and
chemicals, less energy, and environmentally friendly
print practices that reduce waste.
Loading...