Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury. When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
September 2010VAV-SVN04B-EN
Page 2
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provided to alert installing contractors
to potential hazards that could result in personal injury or death. Cautions are designed to alert
personnel to hazardous situations that could result in personal injury, while notices indicate a
situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance
of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage-only
accidents.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical
hazards.
•Before installing/servicing this unit, technicians MUST put on all Personal Protective
Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate
MSDS sheets and OSHA guidelines for proper PPE.
•When working with or around hazardous chemicals, ALWAYS refer to appropriate MSDS and
OSHA guidelines for information on allowable personal exposure levels, proper respiratory
protection and handling recommendations.
•If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE)
in accordance with NFPA70E or other country-specific requirements for arc/flash protection
PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and grounding as described in NEC and your local/
state electrical codes. Failure to follow codes could result in death or serious injury.
Note: At least one copy of this document ships with every order and is customer property. It must
be retained by the unit's maintenance personnel.
This booklet describes proper installation procedures for delivered air systems. By carefully
reviewing the information within this manual and following the instructions, the risk of improper
operation and/or component damage will be minimized. It is important that periodic maintenance
be performed to help assure trouble free operation. Should equipment failure occur, contact a
qualified service organization with qualified, experienced HVAC technicians to properly diagnose
and repair this equipment.
General
These instructions do not cover all variations in systems nor provide for every possible
contingency that may arise at a job site installation.
Inspection
Check carefully for any shipping damage. This must be reported to and claims made against the
transportation company immediately. Any missing parts should be reported to your supplier at
once and replaced with authorized parts only.
Cylinder: 18-gage galvanized–rolled and seam welded
Damper: Two 22-gage galvanized steel plates locked together with an elastomeric gasket
sandwiched between.
Actuator: Internal actuator w/synchronous motor and gear reduction is direct coupled to the
damper shaft. It has a drive time of 60 seconds.
• Electrical Rating:
• Power Supply—24 VAC (20 to 30 VAC) at 50/60 Hz
• Transformer Sizing—2.0 VA maximum at nominal voltage, Class 2
Table 1. Round bypass dampers
Size Diameter (in.)Length (in.)Shipping Weight
61717 lbs
81719 lbs
101720 lbs
121721 lbs
141723 lbs
161725 lbs
Table 2. Round zone dampers
Size Diameter (in.)Length (in.)Shipping Weight
Rectangular Bypass Damper
Sheet Metal Box: 22-gage galvanized steel
Length: 16"
Damper Frame: 18-gage galvanized steel
Damper Blades: 18-gage galvanized steel
Damper Shaft: 1/2" Diam.
Table 3. Rectangular bypass dampers
Size W" x H"No. of BladesShipping Weight
14 x 12316 lbs
16 x 16421 lbs
20 x 20429 lbs
30 x 20440 lbs
61719 lbs
81721 lbs
101722 lbs
121723 lbs
141725 lbs
161727 lbs
VAV-SVN04B-EN5
Page 6
General
Rectangular Zone Damper
Sheet Metal Box: 22-gage galvanized steel
Length: 16"
Damper Frame: 18-gage galvanized steel
Damper Blades: 18-gage galvanized steel
Crank Bearings: Glass filled Nylon
Damper Shaft: 1/2" Diam.
Table 4. Rectangular zone dampers
Size H" x W"No. of BladesShipping Weight
Actuator Specification
Actuator Design: 3 Wire 18 ga 24 VAC Floating Point Control, Non-spring return
Actuator Housing: Housing Type—NEMA 1, IP20
Shaft Rotation: All damper shafts rotate counter-clockwise to open
Electrical Rating:
• Power Supply—24 VAC (20 to 30 VAC) at 50/60 Hz
• Transformer Sizing—2.5 VA maximum at nominal voltage, Class 2
Manual Override: External release lever
Humidity: 90% RH maximum, non-condensing
Temperature Rating:
• Ambient – 35°–125°F (2°–52°C)
• Shipping and Storage: -20°–150°F (-29°–66°C)
Tor q ue :
• Running: 35 lb-in (4 N-m)
• Breakaway: 35 lb-in (4 N-m) minimum
• Stall: 40 lb-in (4.5 N-m) minimum
Running Time for 90° Rotation:
• 60 seconds at 60 Hz nominal
• 72 seconds at 50 Hz nominal
Weight: 1.5 lb (0.68 kg)
08 x 1228 lbs
08 x 14210 lbs
08 x 16212 lbs
10 x 16214 lbs
10 x 20216 lbs
14 x 18318 lbs
Install Bypass Dampers
Bypass damper(s) should be located before the first zone runs out from the supply air duct. VariTrac
dampers or supply duct branches should be installed downstream of bypass dampers. The
distance between bypass dampers and the communicating sensor/bypass control should be two
to three equivalent duct diameters (see Figure 1, p. 7).
6 VAV-SVN04B-EN
Page 7
In systems with plenum return, bypass damper(s) should be ducted into the return air riser. Confirm
Voy ag er
Micro
Control
Heating and
Cooling Coils
Bypass
Damper
Return
Air
Duct
Ductwork
that sufficient relief or exhaust exists to prevent return plenum pressurization.
Important: The use of a relief fan or backdraft damper is strongly recommended in the return
Bypass Damper Wiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and grounding as described in NEC and your local/
state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
General
air system. This will prevent bypassed air from pressurizing the return air duct
system and spilling out of return grills into conditioned space, especially when the
unit is in economizer mode.
The interconnect cable is pre-wired to the bypass damper and may be lengthened if necessary.
Important: Mounting screws must be located towards the ends of the damper when hanging
straps are used to avoid interference with the rotating damper. A label attached to
the dampers indicates the acceptable areas for mounting screws.
NOTICE
Equipment Damage!
The bypass damper must be positioned to orient the drive shaft horizontally. Failure to do this
could result in drive train malfunction (see Figure 1, p. 7).
Important: It is important to note the airflow direction when installing dampers. A label for this
is present on each damper assembly.
Figure 1. Bypass damper installation
VAV-SVN04B-EN7
Page 8
Installation
Communications Wiring
n
Installing the Communicating Sensor/Bypass Control
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
The communicating sensor/bypass control is located between the supply fan and the bypass
damper in the least turbulent location possible. It is recommended that the distance between the
control and the nearest upstream transition be two to three equivalent duct diameters.
If the supply duct branches out at the riser, install the control in the largest supply duct.
A two-inch hole is required to insert the temperature and static pressure sensor. Use the supplied
gasket to seal off air leaks. Secure the sensor to the duct with a minimum of three sheet metal
screws.
Important: The sensor assembly should be installed on the side of the duct to keep the pressure
transducer in a vertical orientation. Do not install horizontally on the top or bottom
of a duct.
Note: Each of the three steps below may be found illustrated in Figure 2, p. 8. Each step has a
corresponding oval in the figure.
1. Plug the actuator connector from the BYPS damper onto the master damper UCM socket (ACT).
2. If two bypass dampers are used, connect the actuator plug of the second bypass damper to the
spare connector socket pigtailed on the first BYPS damper cable assembly.
3. If the cable assembly needs to be extended, cut and splice additional wire on the BYPS damper
end of the cable.
Figure 2. Installing the communicating sensor/bypass control
CLOSE
OPEN
HOT
ACTUATOR
Step 3
SPARE
CONNECTOR
J9
J11
J10
Address
Switch
TB2-1
TB2-2
TB2-3
IN
IN
Shielded T wisted Pair
TB2-4
OUT
J11
J7
JB
TB2-5
OUT
W–HOT
BK–OPEN
R–CLOSE
Step 1
ACT BIP
DDC/UCM
Control Board
YEL GRN
TB2-6
TB4-1
ZONE
TB2-1
TB3-1
GND
GND
8 VAV-SVN04B-EN
To NEC Class 2
24V T ransformer
Load 8 VA (without actuator)
24VAC
24V
TB1-1
J3
1
S
3-5
3-6
TB
TB
TB3-3
TB3-2
GND
SET A/CO2
Female plug end of bypass
sensor assembly cable
Male plug end located o
DDC/UCM control board
A
CT
WH
BK
R
DDC/UCM
Control Board
Step 2
Page 9
Connect the Communicating Sensor/Bypass Control Wiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and grounding as described in NEC and your local/
state electrical codes. Failure to follow code could result in death or serious injury.
The pre-wired interconnect cable plugs into the actuator connector inside the control box. The
cable is designed to connect in one orientation only. Refer to the VariTrac Changeover Bypass VAV
Literature (VAV-PRC003-EN) for information regarding system wiring.
Install the VariTrac Dampers
A sketch of basic damper installation is shown in Figure 4, p. 10. The damper may be connected
with hard duct or flex duct at either end.
If two bypass dampers are installed, a pigtail socket is provided on the cable so the second damper
can be plugged into the UCM.
Important: Mounting screws must be located towards the ends of the damper when hanging
straps are used to avoid interference with the rotating damper. A label attached to
the dampers indicates the acceptable areas for mounting screws.
Important: It is important to note airflow direction when installing the damper. A label for this
is present on each damper assembly.
Installation
NOTICE
Equipment Damage!
The control box on each damper must be positioned to orient the drive shaft horizontally. Failure
to do this could result in drive train malfunction. (See Figure 3, p. 9.)
Figure 3. Proper damper mounting positions
VAV-SVN04B-EN9
Page 10
Installation
Attach unit to hard duct using
a minimum of four
sheet metal screws
Attach unit to hard duct using
a minimum of four
sheet metal screws
Attach flex duct to unit using
self-locking plast ic tie st rap.
A screw & washer can be used
to secure the tie-strap if required.
IMPORTANT:
Mounting screws must be
3" away from damper bend
to avoid interference with
rotating damper.
Hard or Flex
Duct
Hard or Flex
Duct
Hard or Flex
Duct
Hard or Fle
x
Duct
Figure 4. VariTrac damper installation
10 VAV-SVN04B-EN
Page 11
Connect UCM Wiring
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow
requirements for field wiring installation and grounding as described in NEC and your local/
state electrical codes. Failure to follow code could result in death or serious injury.
CAUTION
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other individual
who has been properly trained in handling live electrical components perform these tasks.
Failure to follow all electrical safety precautions when exposed to live electrical components
could result in minor to moderate injury.
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper
conductors could result in equipment damage.
Installation
NOTICE
Equipment Damage!
Connecting a shared UCM power supply with reversed polarity will cause damage to the UCM,
TCI, and central control panel.
NOTICE
Equipment Damage!
When powering multiple UCMs from one transformer, polarity must be maintained. Terminal
TB1-1 is designated positive (+) and Terminal TB1-2 is negative (–) to unit casing ground.
Important: UCM control box cover must be replaced after field wiring to prevent
1. Connect the power to terminals TB1-1 (24V) and TB1-2 (ground). 24 Vac is required to power the
2. The power consumption for an auto-changeover cooling-only UCM (model CHGR) is 10VA.
3. Local heat outputs are rated at 12VA maximum for each output. To determine the total UCM
DIP Switch Settings
Dip switch SW1 contains six switches for addressing the UCM. These switches allow a user to set
a unique communication address for each UCM. Each UCM on a given communication link must
have a unique address in order for the CCP to communicate to it. Refer to Table 5, p. 12 for UCM
4.1 DIP switch settings.
electromagnetic interference.
UCM control. 20 Vac to 28 Vac is acceptable. Use 18 to 20 AWG for power wiring.
power requirements, add the power consumption of local heat to the circuit board power.
¼" quick connect required for all field connections.
Zone sensor terminals 4 and 5 require shielded twisted pair wiring for
3.
communications jack equipped zone sensor option.
4.
No additional wiring required for night setback override (on/cancel).
The optional binary input connects between TB4-1 (BIP) and 24VAC (hot) from
5.
transformer. The binary input can be reconfigured as an occupancy input via the
communications interface.
As shipped, the AUX input is configured as an AUX input. The AUX input can be
6.
reconfigured as a CO2 sensor input via the communications interface.
7.
S terminal not to be used with VariTrane.
If unit mounted transformer is not provided, polarity from unit to unit must be
8.
maintained to prevent permanent damage to control board. If one leg of 24VAC
supply is grounded. then ground leg must be connected to TB1-2.
Shields of communications wiring should be tied together and insulated.
9.
Factory wiring
Field wiring
Optional or alternate wiring
TB1–2
TB3–2
TB1–1
TB3–3
A/CO2
24V
TB3–5
TB3–6
GND
J3
TB2-6
5 4 3 2 1
INSTALLED ZONE SENSOR
To 24V
Transformer
1
S
TB3-2
TB2-5
TB3-3
ZONE SENSOR
W/ COMM. JACK
REMOTE MTD.
3. 4.
OPTIONAL FIELD
TB3-1
TB3-1
TB3-2
2
1
ZONE SENSOR
REMOTE MTD.
4.
OPTIONAL FIELD
INSTALLED ZONE SENSOR
VAV-SVN04B-EN13
Page 14
Page 15
Page 16
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts.
For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.