For Factory Installation on Variable Air Volume
(VAV) Units
May 2010
VAV-SVX0 7 A-E N
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provide to alert installing contractors
to potential hazards that could result in personal injury or death. Cautions are designed to alert
personnel to hazardous situations that could result in personal injury, while notices indicate a
situation that may result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance
of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout
this literature. Read these carefully.
WAR NING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE: Indicates a situation that could result in equipment or property-damage only
accidents.
WARN ING
This equipment is to be serviced/installed by qualified personnel ONLY. Under NO
circumstances should an unqualified person service/install it. Servicing/installing this
equipment is a job requiring specific knowledge and MUST be left to a professional. It involves
working with hazardous components that are potentially life threatening if not handled
properly. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury.
WARN ING
Electrocution and Fire Hazards with Improperly Installed and Grounded
Field Wiring!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid
these hazards, you MUST follow requirements for field wiring installation and grounding as
described in NEC and your local/state electrical codes. All field wiring MUST be performed by
qualified personnel. Failure to follow these requirements could result in death or serious injury.
Overview of Manual
Note: One copy of this document ships inside the control panel of each unit and is customer
property. It must be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for delivered
air systems. By carefully reviewing the information within this manual and following the
instructions, the risk of improper operation and/or component damage will be minimized. It is
important that periodic maintenance be performed to help assure trouble free operation. Should
equipment failure occur, contact a qualified service organization with qualified, experienced HVAC
technicians to properly diagnose and repair this equipment.
This chapter contains information about the following:
•Tracer™ UC400 BACnet Unit Controller
•Shipping & Storage
•Specifications
•Tracer UC400 Controller Enhancements
•Tracer UC400 Controller Features
Tracer UC400 BACnet Unit Controller
The Tracer UC400 controller is a programmable general purpose BACnet, microprocessor-based,
Direct Digital Controller (DDC). When factory installed on Trane (Variable Air Volume) VAV terminal
units, it is factory downloaded with appropriate VAV programs and configuration settings. Trane
VAV units have been made with either pneumatic, analog electronic, or microprocessor controls
(DDC VAV). This manual discusses only terminal units with BACnet Tracer UC400 controller DDC/
VAV controls. Factory installed DDC/VAV controls are available with all single duct terminal units,
dual duct units, parallel fan-powered, and series fan-powered units. A single Tracer UC400
controller is needed for dual duct units, but programming is not provided from the factory.
The Tracer UC400 controller can be configured from the factory with three different application
programs: Space Temperature Control (STC), Ventilation Flow Control (VFC), and Flow Tracking
Control (FTC).
The Tracer UC400 controller programmed for STC modulates a VAV's damper blade based on a
zone temperature, measured airflow, and setpoints to continuously control conditioned air
delivery to the space. The volume of incoming air is monitored and the damper adjusts to provide
accurate control independent of the duct pressure. The damper modulates between operator
setpoints depending on space conditions. Additionally, fan and heat outputs may be energized
depending on the application.
The Tracer UC400 controller configured for VFC can be applied to a VAV terminal and used to
temper cold outdoor air (OA) that is brought into a building for ventilation purposes. The tempered
air is intended to supply an air-handling unit (AHU), which provides comfort control to the zones
it is serving. The VAV terminal supplies the correct amount of ventilation air, and when reheat is
added, tempers the ventilation air to reduce the load on the air handler by sensing the discharge
air temperature of the VAV unit and controlling its long-term average to the discharge air
temperature setpoint.
The Tracer UC400 controller can be configured for FTC and has two VAV units with Tracer UC400
controllers working together to provide flow tracking control. One Tracer UC400 controller is
configured from the factory with the Space temperature program and the other is downloaded with
the FTC program. The STC airflow output is bound to the flow tracking controller airflow setpoint
input. The flow tracking controller adds the configured airflow tracking offset (positive or negative)
to the airflow setpoint (communicated airflow setpoint) and controls the airflow to this setpoint.
The Tracer UC400 controller is BTL compliant with BACnet, an open standard building automation
protocol. It meets the Application Specific Controller (ASC) profile per ASHRAE 135-2004. This
allows the Tracer UC400 controller to integrate with other BACnet systems.
Available Inputs
Inputs include a twisted/shielded communication link, zone sensor, duct temperature sensors
(optional), Occupancy Sensor (optional), Discharge Air Temperature (DAT) and/or Supply Air
Temperature (SAT), CO
application, the spare inputs and outputs on the Tracer UC400 controller may be used for ancillary
control, which can be programmed using Tracer TU Tracer Graphical Programming 2 (TGP2).
Note: For more information on using spare points, see BAS-SVX20*-EN Tracer UC400
Programmable Controller Installation, Operation, and Maintenance.
VAV-SVX07A-EN5
sensor, and 24 VAC power. In addition to the points used for the VAV
2
General Information
Shipping & Storage
Each VAV order ships with service literature. When unpacking, make sure that the literature is not
lost or discarded with the packing material. Visually inspect the individual components for obvious
defects or damage. All components are thoroughly inspected before leaving the factory. Any
claims for damage incurred during shipment must be filed with the carrier.
If any component of the VAV system and/or field installed accessories must be stored for a period
of time prior to installation, they must be protected from the elements. The storage location
temperature should be between -40° to 150°F (-40° to 65.6°C) and the relative humidity should be
10% to 90%, non-condensing. The warranty will not cover damage to the VAV or controls due to
negligence during storage. A controlled indoor environment must be used for storage.
Specifications
AC wiring specifications
Wire
16 AWG (maximum) copper wire
Tr a n s f o r m e r
•UL Listed, Class 2 power transformer 19-30 VAC (24 VAC nominal)
•The transformer must be sized to provide adequate power to the Tracer UC400 controller (24
VA) and outputs (maximum 12 VA for each binary output)
Storage
•Temperature: -48°F to 203°F (-44°C to 95°C)
•Relative humidity: Between 5% to 95% (noncondensing)
Operating
•Temperature: -40°F to 158°F (-40°C to 70°C)
•Humidity: Between 5% to 95% (noncondensing)
•Power: 19-30 VAC (24 VAC nominal) 50-60 Hz 24 VA
•Mounting weight (controller): Mounting surface must support .80 lb. (364 kg)
•Environmental rating (enclosure): NEMA 1
•Altitude: 6,500 ft. maximum (1,981 m)
•Installation: Category 3
•Pollution Degree 2
Analog inputs AI1 to AI5
•AI1: Space temperature; thermistor: 10 kΩ@ 77°F (25°C)
Range: 32°F to 122°F (0°C to 50°C)
•AI2: Space setpoint; potentiometer: 1 k
From 50 to 90°F (10 to 32.2°C), */** (thumbwheel) functionality supported
•AI3: Spare
•AI4: Discharge air temperature: 10 k
From -40 to 212°F (-40 to 100°C)
•AI5: Supply air temperature: 10 k
From -40°F to 212°F (-40 to 100°C)
Ω
Ω@ 77°F (25°C)
Ω@ 77°F (25°C)
6 VAV-SVX07A-EN
General Information
Universal Inputs UI1 and UI2
•UI1: Spare, but recommended for Relative Humidity. Resistive/thermistor inputs, 0-10VDC
inputs, or 4-20 mA inputs. Current Mode Impedance: 200 ohm. Voltage Mode Impedance: 10
kohm min.
•UI2: Spare, but recommended for CO
. Resistive/thermistor inputs, 0-10VDC inputs, or 4-20 mA
2
inputs. Current Mode Impedance: 200 ohm. Voltage Mode Impedance: 10 kohm min.
Pressure Inputs P1 and P2
•P1: Supply air flow; pressure transducer: From 0 to 2 in. water column (0 to 498 Pa)
•P2: Spare, but recommended for dual duct secondary air flow
Binary input BI1 to BI3
•BI1: Occupancy
•BI2: Spare
•BI3: Spare
Binary outputs BO1 to BO9
Table 1.Binary outputs
Binary OutputsTypeOutput RatingPilot duty
BO1Fan10A up to 277 VAC10A at 30 VAC/VDC, 2A at 120 VAC, 8A at 250 VAC,
BO2Spare Relay10A up to 277 VAC10A at 30 VAC/VDC, 2A at 120 VAC, 8A at 250 VAC,
BO3Spare Relay10A up to 277 VAC10A at 30 VAC/VDC, 2A at 120 VAC, 8A at 250 VAC,
BO4Spare Relay10A up to 277 VAC10A at 30 VAC/VDC, 2A at 120 VAC, 8A at 250 VAC,
BO5Heat stage 3 TRIAC24-27 VAC, .5A Resistive VA
BO6Heat stage 2/Water Valve Close TRIAC 24-27 VAC, .5A Resistive VA
BO7Heat stage 1/Water Valve Open TRIAC 24-27 VAC, .5A Resistive VA
BO8Air Damper Close TRIAC24-27 VAC, .5A Resistive VA
BO9Air Damper Open TRIAC24-27 VAC, .5A Resistive VA
Analog outputs AO1 and AO2
•AO1: Spare. Voltage output is 0 to 10 VDC, 500 ohm min. impedance. Current output is 4 - 20
mA, 500 ohm max. impedance
Note: ECM fan for future production.
•AO2: Spare. Voltage output is 0 to 10 VDC, 500 ohm min. impedance. Current output is 4 - 20
mA, 500 ohm max. impedance
Note: For more information about wiring spare I/O, see the Tracer™ UC400 controller Installation
Sheet X39641064*-01.
Agency listings/compliance
UL - Open Energy Management Equipment, 834Y
UL94-5V Flammability
CE marked
FCC Part 15, Subpart B, Class B Limit
AS/NZS CISPR 22:2006
VCCI V-3/2008.04
VAV-SVX07A-EN7
General Information
ICES-003, Issue 4:2004
Table 2. Agency listings/compliance
StandardTest Level
EN 61326-1: 2006 Electrical equipment for measurement, control and
laboratory use - EMC requirements, part 1: General Requirements.
The Tracer™ UC400 controller is factory installed in the VAV control box.
Setting up the Tracer UC400 Controller on a BACnet Link
Tracer SC and BACnet Communications Link Wiring
Use 18 AWG shielded communication wire for BACnet MS/TP installations. Limit BACnet MS/TP
wiring links to 4,000 ft. There is a 60 device maximum per link (without a repeater). Two BACnet
links are available on the SC. Connect the BACnet link to the Tracer UC400 controller terminals
labeled Link. Incoming wires can be connected to the first two terminals, and the outgoing wires
can be connected to the second set of terminals, such that there is only one wire per termination.
Refer to Chapters 2 and 3 for further information about wire selection. See also wiring guide BASSVN03*-EN (Unit Controller Wiring for Tracer SC™System Controller) for required wire type,
topology, and active termination resistors for BACnet links.
Rotary Switches
There are three rotary switches on the front of the Tracer UC400 controller (see Figure 3, p. 16). Use
these switches to define a three-digit address when it is installed in a BACnet system (for example,
107, 120, and so on), whether with other Trane BACnet controls or controls from another vendor.
This three-digit rotary switch setting is used as both the BACnet MAC address and the BACnet
Device ID.
Note: Valid addresses are 001 to 120.
Important: Each Tracer UC400 controller on the BACnet link must have a unique rotary switch
setting, otherwise communication problems will occur.
Tracer UC400 Controller Features
Controller Interface Flexibility
The Tracer UC400 controller allows VAV units to communicate on a BACnet MS/TP link. This
controller works in standalone mode, peer-to-peer with one or more other units, or when
connected to a Tracer SC or a 3rd party building automation system that supports BACnet.
8 VAV-SVX07A-EN
General Information
Flow Tracking
The Tracer™ UC400 controller is designed with the ability to be applied in flow tracking
applications. This allows the controller to be paired with one of its peers to mirror the flow of the
lead unit, with or without an offset (positive or negative static pressure as desired).
Ventilation Flow Control with Tempering
The Tracer UC400 controller is designed with the ability to be applied in ventilation flow control
applications. These applications pair a fresh air unit with ventilation boxes to provide fresh
(tempered) air to a zone. This feature also includes a freeze protection sequence to protect the hot
water reheat coil from low supply air temperatures.
Auto-commissioning Sequence
The TracerUC400 controller is designed with an auto-commissioning sequence. With a discharge
air temperature sensor, this feature exercises the air valve, fan, and heat in the box and records the
temperature before and after the action. This allows the installer to more easily verify the operation
of the unit and commission by exception. An auto-commissioning report can be generated with
Tracer TU service tool.
Automatic Calibration
The Tracer UC400 controller is designed to automatically calibrate the flow transducer each time
the unit transitions to unoccupied. This eliminates the need to initiate/schedule calibration for most
installations. The exception is 24/7 sites, in which case Tracer SC can be used to initiate/schedule
calibration.
Temporary Heat (Construction Mode)
Upon reset (and power-up) if the controller does not detect a valid space temperature the controller
will provide temporary heat by driving the air valve to the heating maximum position.
Note: Note that the unit will only provide heat if hot air is being provided by the air-handling
unit.
Local Versus Remote Reheat Flexibility
The controller can be configured to have local and/or remote heat. Plus, configuration flexibility is
offered that allows the installer to select whether local or remote heat has priority.
Spare Inputs and Outputs
The Tracer UC400 controller has spare I/O that are not used by the VAV applications. These spare
I/O can be programmed using the Tracer Graphical Programming editor (by means of the Tracer
TU service tool) to measure and/or control ancillary devices such exhaust fans, second air valve for
dual duct VAV or sensing relative humidity.
Removable Terminals
The Tracer UC400 controller connector s are two-part connectors that have 5.08 mm pin separation.
The headers are attached on the Tracer UC400 controller itself. The other portion of the connector
is either a screw terminal (for field wiring) or a terminal housing (for factory wiring). Spare screw
terminals come factory installed for field mounted wired zone sensors and common accessories.
Wireless Zone Sensors
The Tracer UC400 controller is compatible with the latest wireless zone sensors available from
Trane. Wireless zone sensors provide flexibility of sensor location and re-location as well as
reducing the cost of installation. Wireless zone sensor receivers are available as a factory installed
option.
VAV-SVX07A-EN9
General Information
Flash Download
The Tracer™ UC400 controller has been designed with flash memory. This allows the option of
upgrading the controller in the field (features, corrections to defects) without changing out the
controller.
Trane Controller Compatibility
The Tracer UC400 controller is a BACnet-compliant controller. As such, the controller is compatible
with the latest generation of Trane controls. This allows the Tracer UC400 controller to exist on the
same communication wire as the rest of our controllers and share data with them as required.
Drive Min and Max from Zone Sensor
When applied with a Trane zone sensor module that includes a thumbwheel setpoint or a LCD
display, the Tracer UC400 controller can easily be overridden to minimum and maximum flow. By
simply turning the thumbwheel to "*" or increasing the setpoint to maximum on display sensors
(end of range in one direction) the controller drives the air valve to the minimum cooling flow
setpoint. Similarly, turning the thumbwheel to the "**" or decreasing the setpoint to minimum on
display sensors (end of range in the other direction) the controller drives the air valve to the
maximum cooling flow setpoint.
Auto-commissioning Report (Tracer SC, Tracer TU)
Tracer SC and Tracer TU both include auto-commissioning reports that extracts and formats the
commissioning data for each VAV controller. This commissioning report is valuable both for the
installer and for the owner. The feature enables the system to be commissioned by exception -- a
benefit for the installer. The feature also can be used as validation -- valuable to the owner.
Simpler VAS
Tracer SC includes a new VAV Air System (VAS) specifically designed for both BACnet and LonTalk
VAV controllers. This new VAS was designed to be much simpler to understand and provides a
wizard to aid in first time setup of a VAS.
Static Pressure Optimization
As a part of the standard application, VAS calculates the duct static pressure setpoint based on the
VAV unit with a damper in the maximum flow position.
Ventilation Optimization
As a part of the standard application, the VAV system has the ability to calculate the ventilation
setpoint for the air-handling unit. In addition, the Tracer UC400 controllers have a ventilation ratio
limit feature that automatically increases airflow to maintain the required ventilation while
operating within system limits for outside air percent concentrations in the supply air stream.
CO2-Based Demand Control Ventilation
As a part of the standard application, the VAV system has the ability to calculate the ventilation
setpoint for the air-handling unit based on the CO
•Occupancy sensor to switch between normal and reduced ventilation
•CO
sensor for demand-controlled ventilation
2
10 VAV-SVX07A-EN
General Information
Temperature Statistics
As a part of the standard application, both the VAS and Area applications calculate the minimum
space temperature (and source), maximum space temperature (and source), and the average space
temperature.
Tracer™ UC400 Controller Compatibility
The Tracer UC400 controller integrates with other BACnet systems and devices using BACnet MS/
TP. The Tracer UC400 controller provides standard BACnet objects (data points) that can be read
by and/or written to by other systems.
Note: See BACnet Integration Guide (BAS-SVP01*-EN) for more information on the Tracer UC400
controller interface to non-Trane systems.
Note: BACnet is the Building Automation and Control Network (BACnet and ANSI/ASHRAE
Does not support zone sensor air balance
sequence.
(a) By simply turning the thumbwheel to "*" or increasing the setpoint to maximum on display sensors (end of range in one direction) the controller
(b) Turning the thumbwheel to the "**" or decreasing the setpoint to minimum on display sensors (end of range in the other direction) the controller
sensor input is available.
2
(a)
(b)
drives the air valve to the minimum cooling flow setpoint.
drives the air valve to the maximum cooling flow setpoint.
No local CO
communicated value.
Single star (*) initiates cool minimum
airflow override.
Double star (**) initiates cool maximum
airflow override.
Does not support VariTrac central control
panel (CCP2 and CCP3).
Supports enhanced ventilation control
sequences.
Supports zone sensor air balance
sequence.
sensor input. Uses only a
2
(a)
(b)
Supports only Comm4 or Comm3 (VariTrac or
VariTrane).
Local CO
Single star (*) initiates maximum flow override
after pressing the ON button. Override is held
until you move the thumbwheel.
Double star (**) initiates unoccupied override
after pressing the ON button. Override is held
until you move the thumbwheel.
Does support VariTrac CCP2 and CCP3.
Does not support enhanced ventilation control
sequences.
Does not support auto-commissioning
sequence.
Does not support zone sensor air balance
sequence.
sensor input is available.
2
VAV-SVX07A-EN11
VAV Start Up/Check Out Procedure
This chapter contains information about the following:
•Tracer™ UC400 Controller Pre-Power Check-Out
•Tracer UC400 Controller Power Wiring
•Communication Wiring
•Space Temperature Control Wiring
• Zone Sensor Wiring
• Duct Temperature Sensor Wiring
• Binary Input Wiring
• Binary Output Wiring
•Zone Sensor Check-Out
•Ventilation Flow Control
•Flow Tracking Control
•Wireless Zone Sensor
Tracer UC400 Controller Pre-Power Check-Out
WARN ING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other individual
who has been properly trained in handling live electrical components perform these tasks.
Failure to follow all electrical safety precautions when exposed to live electrical components
could result in death or serious injury.
•Check the supply voltage at XFRM. Proper polarity must be maintained. The 24 VAC is the hot
side (+) and is the ground side (-) of the 24 VAC input. Refer to Figure 4, p. 18 for the Tracer
UC400 controller terminal locations. The Tracer UC400 controller cannot be powered from a
common 24 VAC transformer that is supplying power to a device containing a full-wave rectifier
bridge in its power supply. The acceptable voltage is 19 to 30 VAC (24 VAC nominal). However,
voltages at either extreme may result in increased system instability.
•Verify communications wiring has properly been terminated to link plus and negative at XFRM
24 VAC (+) and (-) terminals. Polarity must be maintained on the BACnet communications
link.
•Verify that the zone sensor connections are correct as detailed in the Tracer UC400 controller
wiring section.
•If heat has been added to the unit, verify that the proper output connections have been made
as detailed in the Tracer UC400 controller wiring section.
•Verify that the tubing is properly connected to the differential pressure transducer.
12 VAV-SVX07A-EN
Tracer UC400 Controller Power Wiring
Power Requirements
WARN ING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
WARN ING
Electrocution and Fire Hazards with Improperly Installed and Grounded
Field Wiring!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid
these hazards, you MUST follow requirements for field wiring installation and grounding as
described in the National Electrical Codes (NEC) and your local/state electrical codes. All field
wiring MUST be performed by qualified personnel. Failure to follow these requirements could
result in death or serious injury.
VAV Start Up/Check Out Procedure
NOTICE
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper
conductors could result in equipment damage.
Use at a minimum 16 AWG for power wiring and connect to terminal XFRM 24 VAC and . The 24
VAC is required to power the Tracer UC400 controller and has an acceptable voltage tolerance of
19 to 30 VAC. Refer to Figure 4, p. 18 and Figure 5, p. 19 for the Tracer UC400 controller terminal
locations. Replace the control box cover after field wiring to prevent any electromagnetic
interference.
Note: A dedicated 24 VAC, 75VA NEC class 2 transformer is recommended to power the Tracer
UC400 controller. When powering multiple controllers from one transformer, polarity must
be maintained. Terminal 24 VAC is designated positive (+) and terminal is negative (-) to
the unit casing ground.
The power consumption for cooling only Series F Models (VariTrac and VariTrane) is 28 VA. To
determine the total Tracer UC400 controller power requirement, add the power consumption per
stage to the circuit board power requirement. For example, a Series F unit containing magnetic
contactors with three stages of reheat would consume 54 VA.
Table 4. VA for factory installed component
StyleVolt Amps
F - Style Actuator:4 VA
Air Valve Actuator C through E Style:12 VA
Fan Power Fan Outp ut:6 VA
Hot Water Proportional:4 VA
Hot Water 2 Position:6.5 VA
Electric Heater Magnetic Contactor:10 VA
Electric Heater Mercury Contactor:12 VA
Note: VariTrane cooling only Series D and E models consume 20 VA (12 VA for the actuator and 8 VA for the board). The heating
output ratings remain the same. Refer to Figure 4, p. 18 and Figure 5, p. 19 for the Tracer UC400 controller terminal
locations and for wiring of output devices.
VAV-SVX07A-EN13
VAV Start Up/Check Out Procedure
SERVICE
IM
C
LINK
RX
TX
BO29OB1OBBO8BO7BO6BO5BO3 BO4
Marquee LED
LED Description and Behavior
There are 15 LEDs on the front of the Tracer UC400 controller. Figure 1, p. 14 shows the locations
of each LED and describes the behavior of each.
Tracer UC400 Controller Module
Figure 1. LED locations
LED Description and Operation
There are 15 LEDs on the front of the Tracer UC400 controller. Figure 1, p. 14 shows the locations
of each LED and a description of its behavior in specific instances.
Marquee LED
•Shows solid green when the Tracer UC400 controller is powered and operating normally.
•Shows solid red when the Tracer UC400 controller is powered, but represents low power or
a malfunction.
•Blinks red when an alarm exists.
LINK
•The TX LED blinks green at the data transfer rate when the Tracer UC400 controller transfers
data to other devices on the link.
•The RX LED blinks yellow at the data transfer rate when the Tracer UC400 controller receives
data from other devices on the link.
IMC
•The TX LED blinks green at the data transfer rate when the Tracer UC400 controller transfer data
to other devices on the IMC bus.
•The RX LED blinks yellow at the data transfer rate when the Tracer UC400 controller receives
data from other devices on the IMC bus.
Service
Shows solid green when pressed.
BO1 to BO9
Shows solid green when corresponding binary output is on.
14 VAV-SVX07A-EN
Communication Wiring
BILINK IMC
+
VDC
AI
AIAIAI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
BILINK IMC
+
VDC
AI
AIAIAI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
BILINK IMC
+
VDC
AI
AIAIAI AI
P P
TX
RX
LINK IM
SERVI
SERVICE TOOL
IM
+
+
BACnet Terminator
BACnet Terminator
WARN ING
Electrocution and Fire Hazards with Improperly Installed and Grounded
Field Wiring!
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid
these hazards, you MUST follow requirements for field wiring installation and grounding as
described in NEC and your local/state electrical codes. All field wiring MUST be performed by
qualified personnel. Failure to follow these requirements could result in death or serious injury.
Communication Link Wiring Requirements
•Use 18 AWG Trane purple-shielded communication wire for BACnet installations.
•Link limit of 4,000 ft and 60 devices maximum (without a repeater).
•Use a Trane BACnet termination on each end of the link.
•Use daisy chain topology. See Figure 2, p. 15.
•Maintain polarity.
Recommended Wiring Practices
To ensure proper network communication, follow these recommended wiring and planning
guidelines when installing communication wire:
•All wiring must comply with the National Electrical Code (NEC) and local codes.
•Make sure that 24 VAC power supplies are consistent in how they are grounded. Avoid sharing
24 VAC between controllers.
•Avoid over tightening cable ties and other forms of cable wraps. This can damage the wires
inside the cable.
•Do not run communication cable alongside or in the same conduit as 24 VAC power. This
includes the conductors running from TRIAC-type inputs.
•In open plenums, avoid running wire near lighting ballasts, especially those using 277 VAC.
•Use same communication wire type, without terminators, for the zone sensor communication
stubs from the Tracer UC400 controller IMC terminals to the zone sensor communication
module.
Note: For more information see wiring guide BAS-SVN03*-EN, Unit Controller Wiring for Tracer
SC™ System Controller.
VAV Start Up/Check Out Procedure
Figure 2. BACnet link wiring in daisy chain configuration with Trane BACnet terminators and zone senor
communication stubs
VAV-SVX07A-EN15
VAV Start Up/Check Out Procedure
ADDRESS
0
1
2
3
4
5
6
7
8
9
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
x100
Example of before and
after setting addresses
Rotary Switches
There are three rotary switches on the font of the Tracer™ UC400 controller device that are used
to define a three-digit address when the Tracer TU service tool is installed on a BACnet
communications network. The three-digit address setting is used as both the BACnet MAC address
and the BACnet device ID.
Note: Valid MAC addresses are 001 to 120 for BACnet.
Figure 3. Setting rotary switches
16 VAV-SVX07A-EN
Important: Each Tracer UC400 controller device on the BACnet link must have a unique rotary
switch setting, otherwise, communication problems will occur.
Use a 1/8 inch
flathead screwdriver
0
1
9
2
8
3
7
4
6
5
to set rotary switches.
Space Temperature Control Wiring
Zone Sensor Hardwired Option
Depending on the zone sensor options used, a maximum of seven wires may be required to run
from the Tracer™ UC400 controller to the zone sensor. The zone sensor options are:
•Zone sensor (temperature only) - Part Number X1351152801.
•Zone sensor with timed override (TOV) on/cancel button - Part Number X1351153001.
•Zone sensor with adjustable setpoint thumbwheel - Part Number X1351152901.
•Zone sensor with adjustable setpoint thumbwheel, timed override (TOV) on/cancel button - Part
Number X1351152701.
•Zone sensor with digital display - Part Number X1379088601. (Display sensor has factory
mounted communication module.)
•Communications module - Part Number X1365146702. (for one box of 12)
Zone Sensor Wireless Option
Wireless zone sensors are available individually or on sensor/receiver sets. A receiver is used to
receive the signal from the wireless zone sensor and can be factory installed. See BAS-SVX04*-EN
for additional details on setup of the wireless zone sensors.
Note: Currently, wireless sensors do not provide a communication module option. It is
recommended that at least one wired sensor with communications module be installed
within the network of controllers, for service tool connection.
•Wireless zone sensor (temperature only)
– Sensor/Receiver Set - Part Number X1379082301.
– Sensor only - Part Number X13790821.
•Wireless zone sensor with adjustable setpoint thumbwheel (°F), timed override (TOV) on/cancel
button
– Sensor/Receiver Set - Part Number X13790496.
– Sensor only - Part Number X13790492.
•Wireless zone sensor with adjustable setpoint thumbwheel (°C), timed override (TOV) on/cancel
button
– Sensor/Receiver Set - Part Number X13790498.
– Sensor only - Part Number X13790494.
•Wireless zone sensor with digital display
– Sensor/Receiver Set - Part Number X1379082401.
– Sensor only - Part Number X1379082201.
•Wireless receiver only - Part Number X13790854.
VAV Start Up/Check Out Procedure
VAV-SVX07A-EN17
VAV Start Up/Check Out Procedure
Figure 4. Tracer UC400 controller wiring connection diagram: single duct unit
18 VAV-SVX07A-EN
VAV Start Up/Check Out Procedure
Figure 5. Tracer UC400 controller wiring connection diagram: fan powered unit
VAV-SVX07A-EN19
VAV Start Up/Check Out Procedure
Zone Sensor Wiring
Location and Mounting
A zone sensor in each control zone should be located in the most critical area of the zone. Sensors
should not be mounted in direct sunlight or in the area's supply air stream. Subdivision of the zone
may be necessary for adequate control and comfort. Avoid mounting zone sensors in areas subject
to the following:
•Drafts or "dead spots" behind doors or corners.
•Hot or cold air ducts.
•Radiant heat from the sun or appliances.
•Concealed pipes or chimneys.
•Unheated or uncooled surfaces behind the sensor such as outside walls.
•Air flows from adjacent zones or other units.
Wiring
Each unit must be controlled by a zone sensor that utilizes a standard 10K ohm at 77°F thermister
for temperature outputs. Field wiring for the zone sensors must meet the following requirements:
•18 to 22 AWG stranded, tinned-copper, shielded, twisted-pair wire is recommended.
•Maximum wire length 300 ft. (100 m).
•Refer to Figure 4, p. 18 and Figure 5, p. 19 and the sensor instructions for terminal connections.
•All wiring must be in accordance with the National Electrical Code and local codes.
•If local codes require enclosed conductors, the zone sensor wires should be installed in conduit.
Note: Do not route zone sensor wires in conduit with 24 VAC or other high power conducting
wires.
Zone Sensor Communication Stubs
The wire that runs from a zone sensor to a unit controller is commonly referred to as a
communication stub. Figure 2, p. 15 shows an example of communication stubs on a BACnet link.
The stub is not the BACnet link; it is a wire that goes from the Tracer™ UC400 controller IMC
terminal link down to the zone sensor. At least one zone sensor per area or controller network
should include the optional communications module. Installing additional sensors with the
communications module will provide added convenience for the service technician.
There is no limitation on the number of stubs that can be wired from the Tracer UC400 controller.
Polarity must be maintained and the length limit is 600 ft (182 m).
The wire for the communication stub must be the same as that used for BACnet communication
link wiring: low-capacitance, 18-gauge, shielded, twisted pair with stranded, tinned copper
conductors.
Duct Temperature Sensor Wiring
The Tracer UC400 controller has separate analog inputs for discharge air sensors and supply air
sensor. The typical mounting position of the supply air sensor is upstream of the VAV unit and
connected into the UC400 controller (Figure 6, p. 21) at AI5 and . However, the discharge air
temperature sensor may be downstream of the VAV unit, at the discharge, and connected into the
Tracer UC400 controller at AI4 and . Refer to Controller Diagrams Figure 4, p. 18 and Figure 5,
p. 19 for the Tracer UC400 controller terminal locations.
20 VAV-SVX07A-EN
Figure 6. Duct temperature sensors: upstream/downstream
Binary Input Wiring
Each Tracer™ UC400 controller provides three binary inputs. On the Tracer UC400 controller
factory-installed controller, one of the binary inputs is configured in the factory for occupancy. The
binary inputs can be configured with the Tracer TU service tool for occupancy or other use. The
input associates 0 VAC with open contacts and 24 VAC with closed contacts. It is activated by a dry
contact switch closure.
•Must be 18 to 22 AWG.
•Maximum wire length 1,000 ft. (300 m).
•Refer to Figure 4, p. 18 and Figure 5, p. 19 and the sensor instructions for terminal connections.
VAV Start Up/Check Out Procedure
Occupancy Binary Input
The occupancy binary input can be configured as NO or NC. Occupied is the normal state. It is also
the initial state at power-up and after a reset. Unoccupied is the other state. If the binary input is
configured as generic, the default occupancy mode is occupied.
Binary Output Wiring
Binary outputs that are required for unit operation are factory wired and commissioned. The Tracer
UC400 controller does have three extra binary outputs (BO2-BO4) available for other use. To
program the three extra outputs on the Tracer UC400 controller, see BAS-SVX20*-EN Tracer UC400
Programmable Controller Installation, Operation, and Maintenance.
Ventilation Flow control
See Duct Temperature Sensor wiring described on Space Temperature Control Wiring.
Note: If heat is installed Discharge Air sensor must be located at the discharge of the VAV unit.
Flow Tracking Control
Two controllers are used on to separate VAV units for flow tracking. One is a space temperature
controller, and the other is a flow tracking controller. The flow tracking unit does have inputs or
output connected to the controller.
VAV-SVX07A-EN21
VAV Start Up/Check Out Procedure
2.90 in (7.35 cm)
1.08 in (2.75 cm)
4.78 in (12.14 cm)
2.62 in (6.65 cm)
Note: The dimensions are the
same for both the sensor
and the receiver.
Wireless Zone Sensor
The Trane Wireless Zone Sensor set includes a sensor and a receiver that work together to provide
the same functions as the equivalent Trane wired sensor, such as the standard 10k Ω
input (with the exception of the communication jack). No further software or hardware is necessary
for site evaluation, installation, or maintenance.
The sensor transmits the zone temperature, all zone temperature setpoint functions, timed override
Occupied (On) and timed override Unoccupied (Cancel) information to the receiver. The receiver
electrically reproduces the zone temperature resistance, all zone temperature setpoint function
resistances, and timed override On and timed override Cancel information as sent by the sensor.
Dimensional Diagrams
See Figure 7, p. 22 and Figure 8, p. 23 for dimensions of the Wireless Zone Sensor set.
Figure 7. Outside dimensions for sensor
temperature
22 VAV-SVX07A-EN
Figure 8. Mounting hole dimensions for sensor
3.27 in (8.30 cm)
2.36 in (6.00 cm)
VAV Start Up/Check Out Procedure
1.34 in (3.41 cm)
Note: The dimensions are the
same for both the sensor
and the receiver.
Setting the Address, Mounting, Wiring, and Associating the Receiver and Sensor
The following procedure list shows the recommended order for installation:
•Choosing a Location for Mounting the Sensor.
•Setting the Rotary Address Switches on the Receiver and on the Sensor.
•Replacing and Securing the Receiver Cover.
•Powering the Sensor and Associating the Sensor to the Receiver.
•Applying Power to the Receiver.
•Testing Signal and Battery Strength.
•Disassociation.
VAV-SVX07A-EN23
VAV Start Up/Check Out Procedure
Choosing a Location for Mounting the Sensor
Placement of the receiver and the sensor set is critical to proper operation. In most installations,
distance is not the limiting factor for proper radio signal quality. It is more greatly affected by walls,
barriers, and general clutter. For best radio transmission range and reliability, wherever possible,
mount the receiver and sensor in line of sight. Try to minimize the number of barriers between the
pair of devices. In general, sheetrock walls and ceiling tiles offer little restriction to the propagation
of the radio signal throughout the building; concrete or metal barriers offer the most restriction.
The transmission range for the sensor is as follows:
•Open range: 2,500 ft (762 m) (packet error rate = 2%)
•Usable range: 200 ft (61 m)
•Typical range: 75 ft (23 m)
Ambient considerations
Avoid locations that are outside the operating temperature and humidity range.
Location Considerations for the Sensor
When selecting a location for the sensor, consider both thermal and radio transmission
characteristics of the location.
Thermal considerations
•Avoid areas of direct sunlight.
•Avoid areas in the direct air stream of air diffusers.
•Avoid exterior walls and other walls that have a temperature differential between their two
sides.
•Avoid areas close to sources of heat such as sunlight, appliances, or other equipment.
•Avoid drafty areas.
•Avoid dead spots behind doors, projection screens, or corners.
Radio transmission considerations
•Avoid metal barriers between the sensor and receiver, such as plastered walls with metal lathe.
They will decrease radio signal quality.
•Avoid placing the sensor inside metal enclosures.
•Avoid radio transmissions through thick, solid concrete walls.
Setting the Rotary Address Switches on the Receiver and the Sensor
Note: To expedite the installation and association process, set the addresses before applying
power to the receiver.
The process of establishing communication between the receiver and sensor is referred to as
association. The receiver and the sensor must have their rotary switches set to the same address
in order to enable communication between the two devices (see Figure 9, p. 25). Important
limitations are as follows:
•Multiple pairs may be located in close proximity.
•It is not possible to associate more than one sensor to a receiver, nor is it possible to associate
more than one receiver to a sensor.
24 VAV-SVX07A-EN
VAV Start Up/Check Out Procedure
S
5
GND
R77
C35
S1
S2
C33
LED4
S4
S5
S3
LED1
LED2
LED3
LED5
C34
J1
COMM -
24VAC/DC
SETPOINT
HEATING SET
SIGNAL
POWER
ADDDRESS
FAN/SYSTEM
ZONE
COMM +
IN
S
TAL
L
WIRELESS
GND
!
B1 +
INSTALL
WIRELESS
S4
S3
S2
S1
ADDRESS
STATUS
BATTERY
LED5
SIGNAL
LED3
L
ED2
LED1
Pb
Pb-FREE
STATUS
LED4
T
A
S
S
Do not remove the
insulation strip yet.
Receiver
Sensor
Figure 9. Setting the rotary address switches on the receiver and the sensor
Setting the Receiver Address
1. Using a small screwdriver, set the three rotary address switches (locations S1, S2, S3) on the
receiver (Figure 9, p. 25) to an address between 001 and 999.
Note: Do not use 000 as an address for installation. If you set the receiver address to 000, it will:
– Return the receiver outputs to their factory defaults indefinitely (zone temperature and
setpoint outputs: 72.5°F [22.5°C]).
– Remove all association knowledge.
– Make the receiver unable to associate with a sensor.
• Read the switches from left to right in the order in which they are numbered (S1, S2, S3).
• Zero is at the nine o'clock position.
2. Make a notation of the address and location of the receiver.
Setting the Sensor Address
1. Using a small screwdriver, set the three rotary address switches (locations S1, S2, S3) on the
2. Make a notation of the address and location where this sensor is to be mounted.
Note: Do not use 000 as an address for installation. If you set the address to 000, it will:
VAV-SVX07A-EN25
•Read the switches from left to right in the order in which they are numbered (S1, S2, S3).
•Zero is at the 9 o'clock position.
sensor (Figure 9, p. 25) to the same address used for the receiver it is to be associated with.
– Remove all association knowledge.
– Revert to a low-power hibernation mode.
– Send a disassociation request to the receiver. If the sensor and receiver are associated and
communicating at the time the sensor is set to 000 and the Test button is pressed, the
receiver will also become unassociated and will be available for re-association.
VAV Start Up/Check Out Procedure
3. Make a notation of the address and location of the sensor.
Factory Wiring of the Receiver to the VAV Unit Controller
The required power for the receiver is 24 VAC or 24 Vdc and is less than 1 VA. The receiver is
designed to be powered by the Tracer™ UC400 controller. Please see Figure 4, p. 18 and Figure 5,
p. 19 for wiring details.
Note: A dedicated transformer is not necessary or advised.
Note: The receiver is factory mounted and field wiring is not necessary. See Troubleshooting
section for wiring details.
Replacing and Securing the Receiver Cover
1. To replace the receiver cover on the base plate, hook the cover over the top of the base plate.
Apply light pressure to the bottom of the cover until it snaps in place.
2. If necessary to keep the cover securely attached, install the security screw into the bottom of
the receiver (Figure 10, p. 26).
Figure 10. Snap receiver cover on base plate and attach security screw
Security screw
26 VAV-SVX07A-EN
Applying Power to the Receiver
RECEIVER
LED3
LED3 will begin
to blink after
10 seconds
Restore power to the unit controller. Observe LED5 on the receiver (Figure 11, p. 27). It will light and
stay constantly On when 24 V power is normal.
Figure 11. LED5 stays on after applying power to the receiver
VAV Start Up/Check Out Procedure
LED5 stays constantly On
Receiver Indicates Readiness to Associate
After initial power up, the receiver conducts a channel scan for 10 seconds. During this time, the
receiver selects from 16 available channels the clearest channel on which to operate. LED1, LED2,
and LED3 flash rapidly in succession while the channel scan is in progress.
Note: Do not attempt association until the channel scan is finished. After the channel scan is
finished, LED3 will begin blinking (one-blink pattern) to show that the receiver is ready to
be associated with a sensor. LED3 will stop blinking when association has been established
(Figure 12, p. 27).
Figure 12. LED3 blinks when the receiver is ready to be associated with a sensor
VAV-SVX07A-EN27
VAV Start Up/Check Out Procedure
INSTALL
Powering the Sensor and Associating the Sensor to the Receiver
1. Verify that the sensor is set to the same address as the receiver it is to be associated with.
2. Remove the insulation barrier, which is a plastic strip located between the two batteries
(Figure 13, p. 28). Association will automatically occur between the sensor and the receiver. If
the first association attempt is unsuccessful, the sensor will automatically reattempt
association with the receiver every 10 minutes.
Note: A disassociated sensor will transmit an association request every 10 minutes. An associated
sensor that has lost communication with the receiver will transmit an association request
every 50 minutes.
Note: LED3 on the receiver stops blinking to indicate that association has been established.
Figure 13. Removing the insulation barrier on the sensor
SENSOR
LED1
LED2
LED3
LED5
SIGNAL
LED5
BATTERY
STATUS
S1
ADDRESS
S2
J1
Pb
Pb-FREE
B1 +
S3
STATUS
S4
WIRELESS
I
B2 -
LED4
+
–
+
–
S5
28 VAV-SVX07A-EN
Testing Signal and Battery Strength
LED1
LED2
LED3
LED5
srosnes SDW ledoMsrosnes SZW dna STW ledoM
Tes t bu tt on
Push firmly,
then release
Push firmly,
then release
Tes t bu tt on
The following recommended test indicates signal and battery strength. It verifies that the
association process was successful and that the batteries have adequate charge. (For more
information on LEDs, see "Troubleshooting" chapter.)
1. Firmly press and release the Test button (S5) on the bottom of the sensor (Figure 14, p. 29).
2. View LED1, LED2, and LED3 to determine the strength of the signal. View LED5 to determine
the strength of the battery.
Note: The LEDs will turn Off after 5 seconds to conserve battery strength.
3. Record the results in your commissioning statement.
Figure 14. Wireless sensors
VAV Start Up/Check Out Procedure
Disassociation
The receiver removes all stored association information, conducts a channel scan, and restarts
itself, if any of the following are true:
•The receiver address is changed from its current setting (001-999).
•The receiver receives a disassociation notification from its associated sensor.
•The receiver does not receive a communication from its associated sensor within 35 minutes.
Configuring the Wireless Sensor (Model Digital Display WDS only)
The configuration of the sensor determines which system features can be accessed and changes
can be made by the tenant (for example, changes to cooling/heating mode, setpoint, or fan speed.
VAV-SVX07A-EN29
Verify system and associated unit features before configuring the sensor.
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.