Trane Tracer TD7 User Manual

Page 1
4
0
User
G
e
s
Tracer™ TD7 with UC 80
uid
LC-SVU006A-E
Original instruction
Page 2
2
Copyrigh
t
A
p
g
f
s
f
e
ll rights reserved
This document and the information in it are the property of Trane and may not be used or re Trane reserves the ri to its content without obligation to noti
roduced in whole or in part, without the written permission of Trane.
ht to revise this publication at any time and to make changes
y any person of such revision or change.
Trademark
TD7, RTHD Trane, the Trane logo, and Tracer are trademarks of Trane. All trademarks
erenced in this document are the trademarks of their respective owners.
re
© 2014 Tran
RLC-SVU006A-E4
Page 3
Table of Contents
4
3
.
5
5
5
5
.
6
.
6
.
6
7
l
7
9
.
9
.
9
.
9
.
........................................................
1
....................................................................................................
..................................................................................................
2
RTU Protocol
Ove
...............................................................................................................................
3
...........................................................................................................
3
3Co
s
3
3
3
............................................................................................................................
S
...............................................................................................................
...............................................................................................
26
9
General Recommendations ................................................................................................... 4
Units with Nitrogen Charge Option .....................................................................................
Installer-Supplied Components.............................................................................................
Power Supply Wiring ..............................................................................................................
Control Power Supply ............................................................................................................
Motor Cable .................................................................................................................................................
Motor Rotation Check .................................................................................................................................
AC Mains Connection .................................................................................................................................
Interconnecting Wiring ...........................................................................................................
Chilled Water Pump Contro
Programmable Relays ............................................................................................................
Relay Assignments Using Tracer™ TU ..................................................................................
Low Voltage Wiring ................................................................................................................
Emergency Stop ..........................................................................................................................................
External Auto/Stop ......................................................................................................................................
Ice Building Option ...............................................................................................................
External Chilled Water Setpoint (ECWS) Option................................................................
External Demand Limit Setpoint (EDLS) Option ..............................................................
EDLS and ECWS Analog Input Signal Wiring Details:
Chilled Water Reset (CWR)
Communications Interface
LonTalk™ Interface (LCI-C) ........................................................................................................................ 12
BACnet Protocol ........................................................................................................................................12
BACnet Testing Laboratory (BTL) Certifi cation ......................................................................................... 12
dbus
................................................................................................................................12
rview
UC800 Specifi cations
Wiring and Port Descriptions ....................................................................................................................1
mmunication Interface
otary Switches ..........................................................................................................................................1
LED Description and Operation ................................................................................................................1
Tracer TD7 Operator Interface ..............................................................................................
Tr a cer™ TU
1
1
1
1
1
14
tarter Diagnostics
Main Processor Diagnostics ................................................................................................20
Communication Diagnostics
Operator Display Diagnostics and Messages ....................................................................2
RLC-SVU006A-E
Page 4
4
nstallation Electrical
s
g
N
:
Always refer to wiring diagrams shipped with
s
.
W
G
!
in d
W
G
(
g
discharged.
i
b
p
M
)
bef
.
e
D
3
)
W
G
!
B
C
d
p
disch
T
M
C
l
l
in p
.
D
3
)
O
:
l
.
Important:
To prevent control malfunctions, do not run
General Recommendation
As you review this manual, keep in mind that:
All fi eld-installed wiring must conform to European
uidelines and any applicable local codes. Be sure to satisfy proper equipment grounding requirements per European guidelines.
Compressor motor and unit electrical data (including
motor kW, voltage utilization range, rated load amps) is listed on the chiller nameplate.
All fi eld-installed wiring must be checked for proper
terminations, and for possible shorts or grounds.
ote
hiller or unit submittal for specifi c electrical chematic and connection information
ARNIN
Proper Field Wiring and Grounding Required
All fi eld wiring MUST be performed by qualifi ed personnel. Improperly installed and grounded fi eld wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for fi eld wiring installation and grounding as described in local electrical codes. Failure to follow code could result
eath or serious injury.
ARNIN
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run and AFD
Adaptive Frequency™ Drive) capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.
For variable frequency drives or other energy storin
components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have
ARNIN
Hazardous Voltage - Pressurized Burning Fluid
efore removing compressor terminal box cover for
servicing, or servicing power side of control panel,
LOSE COMPRESSOR DISCHARGE SERVICE VALVE
and disconnect all electric power including remote
isconnects. Discharge all motor start/run capacitors.
Follow lockout/tagout procedures to ensure the
ower cannot be inadvertently energized. Verify with
an appropriate voltmeter that all capacitors have
arged.
he compressor contains hot, pressurized refrigerant.
otor terminals act as a seal against this refrigerant.
are should be taken when servicing NOT to damage or
oosen motor terminals.
Do not operate compressor without termina
lace.
Failure to follow all electrical safety precautions could result in death or serious injury
For additional information regarding the safe discharge
f capacitors, see “Adaptive Frequency™ Drive (AF apacitor Discharge,” p. 28 and PROD-SVB06A-EN.
TICE
N
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could
t in equipment damage
resu
ow voltage wiring (<30 V) in conduit with
onductors carrying more than 30 volts.
box cover
DC bus capacitors retain hazardous voltages after
nput power has been disconnected. Follow proper
lockout/tagout procedures to ensure the power cannot
e inadvertently energized. After disconnecting input ower, wait fi ve (5) minutes for the DC capacitors to
discharge, then check the voltage with a voltmeter.
ake sure DC bus capacitors are discharged (0 VDC
ore touching any internal components
Failure to follow these instructions could result in death or serious injury.
For additional information regarding the safe discharg
f capacitors, see “Adaptive Frequency™ Drive (AF apacitor Discharge,” p. 28 and PROD-SVB06A-EN.
RLC-SVU006A-E4
Page 5
4
5
W
G
in d
Table 1. Capacitor Discharge Times
V
ge
r
g
t
]
3
20
3
40
n
A
EXV
s
h
g
.
g
W
G
!
p
y
r
.
A
a
w
A
(
s
s
w
.
d
N
U
U
r
.
a
g
g.
.
nstallation Electrical
In case of drive servicing only
ARNIN
DISCHARGE TIME!
Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any remote DClink power supplies, including battery backups, UPS and DC-link connections to other frequency converters. Wait for the capacitors to fully discharge before performing any service or repair work. The amount of wait time is listed in the Discharge Time table. Failure to wait the specifi ed time after power has been removed before doing service or repair could result
eath or serious injury.
olta
80-500 V 90-250 kW
we
15-800 kW
inimum waitin
ime [min
Units with Nitrogen Charge Optio
For units with nitrogen charge option (model number digit 15 = 2), the unit must NOT have shore power, or unit power applied until the unit has been charged.
pplying power will drive
inhibit suffi cient vac for unit charging.
valves closed, and will
Installer-Supplied Component
Customer wiring interface connections are shown in
e electrical schematics and connection diagrams that
t are shipped with the unit. The installer must provide the followin
Power supply wiring (in conduit) for all fi eld-wired
connections.
All control (interconnecting) wiring (in conduit) for
fi eld supplied devices
Fused-disconnect switches or circuit breakers.
components if not ordered with the unit:
Power Supply Wirin
ARNIN
Proper Field Wiring and Grounding Required
All fi eld wiring MUST be performed by qualifi ed
ersonnel. Improperly installed and grounded fi eld wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for
eld wiring installation and grounding as described in
our local electrical codes. Failure to follow code could
esult in death or serious injury
ll power supply wiring must be sized and selected
ccordingly by the project engineer in accordance
ith EN 60204.
ll wiring must comply with local codes. The installing
or electrical) contractor must provide and install the
ystem interconnecting wiring, as well as the power upply wiring. It must be properly sized and equipped
ith the appropriate fused disconnect switches
The type and installation location(s) of the fused
isconnects must comply with all applicable codes.
OTICE:
se Copper Conductors Only!
nit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
esult in equipment damage
Cut holes into the sides of the control panel for the
ppropriately-sized power wiring conduits. The wiring
s passed through these conduits and connected to the
terminal blocks, optional unit-mounted disconnects, or
ACR type breakers.
The hi through patch plate on the right side of the panel. The low voltage connections are made through knockouts
may be required for each 115 volt power supply to the
h voltage fi eld-provided connections are made
rovided on the left side of the panel. Additional grounds
nit. Green lugs are provided for 115V customer wirin
Control Power Supply
The unit is equipped with a control power transformer.
t is not necessary to provide additional control power
oltage to the unit. No other loads should be connected
to the control power transformer
ll units are factory-connected for appropriate labeled
oltages.
RLC-SVU006A-E
Page 6
nstallation Electrical
on
k
f
.
n
s
)
.
• T
Motor Cable
The motor must be connected to terminals U/T1/96, V/ T2/97, W/T3/98. Earth (ground) to terminal 99. All types of three-phase asynchronous standard motors can be used with a frequency converter unit. The factory setting is for clockwise rotation with the frequency converter output connected as follows:
Terminal no.
96, 97, 98, 99
uncti
ains U/T1, V/T2, W/T3
arth (ground)
Motor Rotation Chec
The direction of rotation can be changed by switching two phases in the motor cable or by changing the setting of 4-10 Motor Speed Direction.
erminal U/T1/96
connected to U-phase
Terminal V/T2/97
connected to V-phase
Terminal W/T3/98
connected to W-phase
A motor rotation check can be performed using1-28 Motor Rotation Check and the display
ollowing the steps shown in
AC Mains Connectio
Size wiring is based upon the input current of the
requency converter
Comply with local and national electrical codes for
cable size
onnect 3-phase AC input power wiring to terminals
L1, L2, and L3 (see Figure 1
Mains connection
otor connection
Earth (ground) the cable in accordance with the
instructions provided
All frequency converters may be used with an isolated
input source as well as with earth (ground) reference
ower lines. When supplied from an isolated mains
source (IT mains or fl oating delta) or TT/TN-S mains
ith a grounded leg (grounded delta), set 14-50 RFI Filter to OFF When off, the internal RFI fi lter capacitors between the chassis and the intermediate circuit are isolated to avoid damage to the intermediate circuit and to reduce earth (ground) capacity currents in accordance with IEC 61800-3.
RLC-SVU006A-E4
Page 7
4
g
A
Table 5. Pump Relay Operation
e
n
o
g
p
g
)
s
g
nstallation Electrical
Interconnecting Wirin
hilled Water Pump Control
NOTICE:
quipment Damage!
If the microprocessor calls for a pump to start and water does not fl ow, the evaporator may be damaged catastrophically. It is the responsibility of the installing contractor and/or the customer to ensure that a pump will always be running when called upon by the chiller controls.
An evaporator water pump output relay closes when the chiller is given a signal to go into the of operation from any source. The contact is opened to turn off the pump in the event of most machine level diagnostics to prevent the build up of pump heat.
The relay output is required to operate the Evaporator Water Pump (EWP) contactor. Contacts should be compatible with 115/240 VAC control circuit. Normally, the EWP relay follows the AUTO mode of the chiller.
henever the chiller has no diagnostics and is in the AUTO mode, regardless of where the auto command is coming from, the normally open relay is energized. When the chiller exits the AUTO mode, the relay is timed to open in an adjustable (using TU) 0 to 30 minutes. The non-AUTO modes in which the pump is stopped, include Reset, Stop, External Stop, Remote Display Stop,
topped by Tracer, Start Inhibited by Low Ambient Temp,
and Ice Building complete.
uto mode
f evaporator water fl ow is lost once it had been established, the EWP relay remains energized and a non-latching diagnostic is generated. If fl ow returns, the
iagnostic is cleared and the chiller returns to normal
operation.
n general, when there is either a non-latching or latchin
iagnostic, the EWP relay is turned off as though there
as a zero time delay. Exceptions whereby the relay
continues to be energized occur with:
ow Chilled Water Temp. diagnostic (non-latching)
unless also accompanied by an Evap Leaving Water
Temperature Sensor Diagnostic
r
oss of Evaporator Water Flow diagnostic (non-
latching) and the unit is in the AUTO mode, after
nitially having proven evaporator water fl ow.
rogrammable Relay
programmable relay concept provides for enunciation of certain events or states of the chiller, selected from a list of likely needs, while only using four physical output
elays, as shown in the fi eld wiring diagram. The four elays are provided (generally with a Quad Relay Output
LID) as part of the Programmable Relay Option. The
elay’s contacts are isolated Form C (SPDT), suitable
for use with 120 VAC circuits drawing up to 2.8 amps
nductive, 7.2 amps resistive, or 1/3 HP and for 240 VAC
circuits drawing up to 0.5 amp resistive.
The list of events/states that can be assi
rogrammable relays can be found in Table 6. The relay
ill be energized when the event/state occurs.
ned to the
Chiller Mod
t
ce Buildin
Tracer Override Close
to
ce Complete
iagnostics
When going from Stop to Auto, the EWP relay is energized immediately. If evaporator water fl ow is not established in 20 minutes (for normal transition) or 4 minutes, 15 seconds (for pump commanded ON due to an override safety), the UC800 de-energizes the EWP relay and generates a non-latching diagnostic. If fl ow returns (e.g. someone else is controlling the pump), the diagnostic is cleared, the EWP is re-energized, and normal control resumed.
elay Operatio
nstant close nstant close
Timed Open
nstant Open nstant Open
RLC-SVU006A-E
Page 8
nstallation Electrical
Table 6. Chiller events/status descriptions
e
n
g
t
m
g
g
g
)
g
y
y
vent/Stat
larm - Latchin
larm - Auto Rese
lar
arnin
Chiller Limit Mode This output is true whenever the chiller has been running in one of the Unloadin
ompressor Runnin
escriptio
This output is true whenever there is any active diagnostic that requires a manual reset to clear, that effects the Chiller, the Circuit, or any of the Compressors on a
ircuit. This classifi cation does not include informational diagnostics.
This output is true whenever there is any active diagnostic that could automatically
lear, that effects the Chiller, the Circuit, or any of the Compressors on a circuit. This classifi cation does not include informational diagnostics. If all of the auto resetting diagnostics were to clear, this output would return to a false condition.
This output is true whenever there is any diagnostic effecting any component, whether latching or automatically clearing. This classifi cation does not include informational diagnostics.
This output is true whenever there is any informational diagnostic effecting any
omponent, whether latching or automatically clearing.
types of limit modes (Condenser, Evaporator, Current Limit or Phase Imbalance
imit) continuously for the last 20 minutes. A given limit or overlapping of different limits must be in effect continuously for 20 minutes prior to the output becomin true. It will become false, if no Unload limits are present for 1 minute. The fi lter prevents short duration or transient repetitive limits from indicating. The chiller is considered to be in a limit mode for the purposes of front panel display and
nnunciation, only if it is fully inhibiting loading by virtue of being in either the
hold” or “forced unload” regions of the limit control, excluding the “limited loading region”. (In previous designs, the “limit load” region of the limit control was included in the criteria for the limit mode call out on the front panel and
nnunciation outputs
The output is true whenever any compressors are started or running on the
hiller and false when no compressors are either starting or running on the chiller.
This status may or may not refl ect the true status of the compressor in Service
umpdown if such a mode exists for a particular chiller.
Chiller Head Pressure Relief
equest Rela
This relay output is energized anytime the chiller is running in one of the following modes; Ice Making Mode or Condenser Pressure Limit Control Mode continuously for the duration specifi ed by the Chiller Head Relief Relay Filter Time. The Chiller
ead Relief Relay Filter Time is a service setpoint. The relay output is de-energized
nytime the chiller exits all above modes continuously for the duration specifi ed b
the same Chiller Head Relief Relay Filter Time.
RLC-SVU006A-E4
Page 9
4
)
.
Table 7. Default assignments
y
m
y
.
g
To prevent control malfunctions, do not run
p
.
p
nstallation Electrical
elay Assignments Using
Tracer™ TU
Tracer™ TU Service Tool is used to install the Programmable Relay Option package and assign any of the above list of events or status to each of the four relays provided with the option. (See “Tracer™ TU,” for more information on the Tracer TU service tool. The relays to be programmed are referred to by the relay’s terminal numbers on the LLID board 1A10
The default assignments for the four available relays of the Programmable Relay option are:
ela
elay 0Terminals J2-1,2,3: elay 1Terminals J2-4,5,6: elay 2Terminals J2 - 7,8,9: elay 3Terminals J2 -10,11,12: CMP Running Rela
If any of the Alarm/Status relays are used, provide electrical power, 115 VAC with fused-disconnect to the panel and wire through the appropriate relays (terminals on 1A10). Provide wiring (switched hot, neutral, and
round connections) to the remote annunciation devices. Do not use power from the chiller’s control panel transformer to power these remote devices. Refer to the fi eld diagrams which are shipped with the unit
ead press.
imit mode
lar
ow Voltage Wirin
The remote devices described below require low voltage
iring. All wiring to and from these remote input devices
to the Control Panel must be made with shielded, twisted
air conductors. Be sure to ground the shielding only at
the panel.
low voltage wiring (<30 V) in conduit with
onductors carrying more than 30 volts.
mergency Sto
C800 provides auxiliary control for a customer
pecifi ed/installed latching trip out. When this customer-
urnished remote contact 5K22 is provided, the chiller
ill run normally when the contact is closed. When the
contact opens, the unit will trip on a manually resettable
iagnostic. This condition requires manual reset at the
chiller switch on the front of the control panel
Connect low voltage leads to terminal strip locations 1A12. Refer to the fi eld diagrams that are shipped with the unit.
ilver or gold-plated contacts are recommended. These
customer-furnished contacts must be compatible with 24
DC, 12 mA resistive load.
xternal Auto/Sto
f the unit requires the external Auto/Stop function, the
nstaller must provide leads from the remote contacts 5K21 to the proper terminals of the LLID 1A12 on the control panel.
he chiller will run normally when the contacts are closed. When either contact opens, the compressor(s), if operating, will go to the RUN:UNLOAD operating mode
nd cycle off. Unit operation will be inhibited. Closure of the contacts will permit the unit to return to normal operation.
ield-supplied contacts for all low voltage connections must be compatible with dry circuit 24 VDC for a 12 mA resistive load. Refer to the fi eld diagrams that are
ipped with the unit.
RLC-SVU006A-E
Page 10
0
nstallation Electrical
n
b
I
g
When in the Ice Building mode, and the
O
:
g
C
p
n
.
S
4
5
9
.
n
These customer-supplied contact closures must be compatible with 24 VDC, 12 mA resistive load. Silver or gold plated contacts are recommended.
Ice Building Optio
UC800 provides auxiliary control for a customer specifi ed/installed correct with contact closure 5K20 for ice building if so confi gured and enabled. This output is known as the Ice Building Status Relay. The normally open contact will be closed when ice building is in progress and open when ice terminated either through reached or removal of the Ice Building command. This output is for use with the ice storage system equipment or controls (provided by others) to signal the system
es required as the chiller mode changes from
chan
ice building” to “ice complete”. When contact 5K12 is
rovided, the chiller will run normally when the contact
s open.
UC800 will accept either an isolated contact closure (External Ice Building command) or a Remote Communicated input (Tracer) to initiate and command the Ice Building mode.
UC800 also provides a “Front Panel Ice Termination
etpoint”, settable through Tracer™ TU, and adjustable
from 20 to 31°F (-6.7 to -0.5°C) in at least 1°F (1°C)
ncrements.
vaporator entering water temperature drops
elow the ice termination setpoint, the chiller erminates the Ice Building mode and changes o the Ice Building Complete Mode.
uilding has been normally
ce Termination setpoint being
Connect leads from 5K12 to the proper terminals of 1A15. Refer to the fi eld diagrams which are shipped with
he unit.
Silver or gold-plated contacts are recommended. These customer furnished contacts must be com
4 VDC, 12 mA resistive load.
atible with
External Chilled Water Setpoint
ECWS) Optio
The UC800 provides inputs that accept either 4-20 mA or
-10 VDC signals to set the external chilled water setpoint (ECWS). This is not a reset function. The input defi nes the setpoint. This input is primarily used with generic BAS
building automation systems). The chilled water setpoint set via the Tracer TD7 or through digital communication with Tracer (Comm4). The arbitration of the various chilled water setpoint sources is described in the fl ow charts at the end of the section
The chilled water setpoint may be changed from a
emote location by sending either a 2-10 VDC or 4-20 mA
signal to the 1A14, terminals 5 and 6 LLID. 2-10 VDC and
-20 mA each correspond to a 10 to 65°F (-12 to 18°C)
external chilled water setpoint.
The following equations apply:
Voltage
As generated from external source VDC=0.1455*(ECWS) + 0.545
As processed by UC800 ECWS=6.875*(VDC) - 3.7
Current Signal
As generated from external source mA=0.2909(ECWS) + 1.090
As processed by UC800 ECWS=3.4375(mA) - 3.75
ignal
TICE
N
Equipment Damage!
Freeze inhibitor must be adequate for the leaving water temperature. Failure to do so will result in dama system components.
racer™ TU must also be used to enable or disable Ice
Machine Control. This setting does not prevent the Tracer
rom commanding Ice Building mode.
Upon contact closure, the U building mode, in which the unit runs fully loaded at all times. Ice building shall be terminated either by opening the contact or based on the entering evaporator water temperature. UC800 will not permit the ice building mode to be reentered until the unit has been switched out of ice building mode (open 5K12 contacts) and then switched back into ice building mode (close 5K12 contacts.)
In ice building, all limits (freeze avoidance, evaporator, condenser, current) will be ignored. All safeties will be enforced.
If, while in ice building mode, the unit gets down to the freeze stat setting (water or refrigerant), the unit will shut down on a manually resettable diagnostic, just as in normal operation.
800 will initiate an ice
e to
f the ECWS input develops an open or short, the LLID will report either a very high or very low value back to
he main processor. This will generate an informational
iagnostic and the unit will default to using the Front anel (TD7) Chilled Water Setpoint
Tracer TU Service Tool is used to set the input signal type from the factory default of 2-10 VDC to that of 4-20 mA.
racer TU is also used to install or remove the External Chilled Water Setpoint option as well as a means to enable and disable ECWS.
External Demand Limit Setpoint
EDLS) Optio
Similar to the above, the UC800 also provides for an optional External Demand Limit Setpoint that will accept either a 2-10 VDC (default) or a 4-20 mA signal. The
emand Limit Setting can also be set via the Tracer TD7 or through digital communication with Tracer (Comm4). The arbitration of the various sources of demand limit is
escribed in the fl ow charts at the end of this section. The
External Demand Limit Setpoint may be changed from a
emote location by hooking up the analog input signal to
he 1A14 LLID terminals 2 and 3. Refer to the following
paragraph on Analog Input Signal Wiring Details.
1
RLC-SVU006A-E4
Page 11
4
l
g
e
0
0
M
0
0
f
.
of
:
TU
For proper unit operation, BOTH the EDLS
C
S
)
.
.
.
(
))
S
)
S
e
S
S
ge
o
s
y
o
)
)
doo
o
)
)
nstallation Electrical
The following equations apply for EDLS:
enerated from
As external sourc
As processed by
C
Voltage Signa
VDC+0.133*(%)-6.
%=7.5*(VDC)+45.
Current Signal
mA=0.266*(%)-12.
%=3.75*(mA)+45.
If the EDLS input develops an open or short, the LLID will report either a very high or very low value back to the man processor. This will generate an informational diagnostic and the unit will de
ault to using the Front
Panel (Tracer TD7) Current Limit Setpoint
The Tracer™ TU Service Tool must be used to set the input signal type from the factory default of 2-10 VDC to
4-20 mA current. Tracer TU must be also be used
that to install or remove the External Demand Limit Setpoint Option for fi eld installation, or can be used to enable or disable the feature (if installed).
EDLS and ECWS Analog Input
ignal Wiring Details
Both the ECWS and EDLS can be connected and setup as either a 2-10 VDC (factory default), 4-20 mA, or resistance input (also a form of 4-2OmA) as indicated
elow. Depending on the type to be used, the Tracer
ervice Tool must be used to confi gure the LLID and the MP for the proper input type that is being used. This is accomplished by a setting change on the Custom Tab of the Confi guration View within Tracer TU.
nd ECWS settings MUST be the same 2-10 VDC or 4-20mA), even if only one nput is to be used.
he J2-3 and J2-6 terminal is chassis grounded and terminal J2- 1 and J2-4 can be used to source 12 VD The ECL
uses terminals J2-2 and J2-3. ECWS uses terminals J2-5 and J2-6. Both inputs are only compatible with high-side current sources.
.
Chilled Water Reset (CWR
C800 resets the chilled water temperature set point based on either return water temperature, or outdoor air temperature. Return Reset is standard, Outdoor Reset is optional.
The following shall be selectable:
ne of three Reset Types: None, Return Water
Temperature Reset, Outdoor Air Temperature Reset, or
onstant Return Water Temperature Reset.
Reset Ratio Set Points
For outdoor air temperature reset there shall be both
ositive and negative reset ratio’s
Start Reset Set Points
Maximum Reset Set Points.
The equations for each type of reset are as follows:
eturn
CWS’ = CWS + RATIO
nd CWS’ > or = CW
nd CWS’ - CWS < or = Maximum Reset
utdoor
CWS’ = CWS + RATIO * (START RESET - TOD
nd CWS’ > or = CW
nd CWS’ - CWS < or = Maximum Reset
wher
CWS’ is the new chilled water set point or the “reset CWS”
is the active chilled water set point before any reset
CW
as occurred, e.g. normally Front Panel, Tracer, or ECW
RESET RATIO is a user adjustable gain
TART RESET is a user adjustable reference
TOD is the outdoor temperature
TWE is entering evap. water temperature
is leaving evap. water temperature
MAXIMUM RESET is a user adjustable limit providing the maximum amount of reset. For all types of reset, CWS’ - CWS < or = Maximum Reset.
START RESET - (TWE - TWL
2-10 VDC, 4-20mA
Resister
I
I = 20/(R + 200)
RLC-SVU006A-E
J2-1 & 4 Dual J2-2 & 5 Analog J2-3 & 6 I/O LLID
J2-1 & 4 Dual J2-2 & 5 Analog J2-3 & 6 I/O LLID
J2-1 & 4 Dual J2-2 & 5 Analog J2-3 & 6 I/O LLID
an
eset
eturn
t
eset
e
ati
t
%
0 to
r
80%
tart
eset
to 30 F to 20 F
2.2 to
6.7 C t
F
10 to
54.4 C
ax
eset
0.0 to
1.1 C
to 20 F
0.0 to
1.1 C
ncrement
IP UnitsSI Unit
%
%
%
%
actor
efault
%
%
1
Page 12
2
nstallation Electrical
%
.
S
S
p
e
)
(
g
For more information see ACC-SVN100*-EN.
)
b
.
In addition to Return and Outdoor Reset, the MP provides a menu item for the operator to select a Constant Return Reset. Constant Return Reset will reset the leaving water temperature set point so as to provide a constant entering water temperature. The Constant
eturn Reset equation is the same as the Return Reset equation except on selection of Constant Return Reset, the MP will automatically set Ratio, Start Reset, and Maximum Reset to the following.
RATIO = 100
START RESET = Design Delta Temp
MAXIMUM RESET = Design Delta Temp.
The equation for Constant Return is then as follows:
CWS’ = CWS + 100% (Design Delta Temp. - (TWE - TWL)) and CW
and CWS’ - CWS < or = Maximum Reset
When any ty the Active CWS toward the desired CWS’ (based on the above equations and setup parameters) at a rate of 1 degree F every 5 minutes until the Active CWS equals the desired CWS’. This applies when the chiller is running.
When the chiller is not running, CWS is reset immediately (within one minute) for Return Reset and at a rate of 1 degree F every 5 minutes for Outdoor Reset. The chiller will start at the Differential to Start value above a fully reset CWS or CWS’ for both Return and Outdoor Reset.
’ > or = CW
e of CWR is enabled, the MP will step
Communications Interfac
LonTalk™ Interface (LCI-C
UC800 provides an optional LonTalk™ Communication Interface (LCI-C) between the chiller and a Building Automation System to provide “ compatible device and the Chiller. The inputs/outputs include both mandatory and optional network variables as established by the LonMark Functional Chiller Pro
040.
ateway” functionality between a LonTalk
BAS). An LCI-C LLID shall be used
le
BACnet Protocol
The Building Automation and Control Network (BACnet
nd ANSI/ASHRAE Standard 135-2004) protocol is a standard that allows building automation systems or components from different manufacturers to share
nformation and control functions. BACnet provides
building owners the capability to connect various
ypes of building control systems or subsystems ogether for a variety of reasons. In addition, multiple
vendors can use this protocol to share information for
onitoring and supervisory control between systems
nd devices in a multi-vendor interconnected system. The BACnet protocol identifi es standard objects (data points) called BACnet objects. Each object has a defi ned list of properties that provide information about that object. BACnet also defi nes a number of standard
lication services that are used to access data and
anipulate these objects and provides a client/server
communication between devices.
BACnet Testing Laboratory (BTL Certifi cation
All Tracer™ UC800 controllers are designed to support BACnet communication protocol. In
ddition,someparticular revisions of the UC800 fi rmware
ave been tested and have achieved BTL certifi cation by
n offi cial BACnet testing laboratory. For more details,
efer to the BTL website at www.bacnetassociation.org.
Modbus RTU Protocol
Modicon Communication Bus (Modbus) is an application layer-messaging protocol that, like BACnet, provides client/server communication between devices over
variety of networks. During communications on a Modbus RTU network, the protocol determines how each controller will know its device address, recognize
message addressed to its device, determine what
ction to take, and extract any data or other information contained in the message. Controllers communicate using a master/slave technique, where
evice (master) can initiate transactions (queries). Other
evices (slaves) respond by supplying the requested
ata to the master or by taking the action requested in
he query.
he master can address individual slaves or it can
nitiate a broadcast message to all slaves. In turn, the
slaves respond to queries that are addressed to them
ndividually or broadcasted. The Modbus RTU protocol
establishes the format for the master’s query by placing
nto it the device address, a function code defi ning the
equested action, any data to be sent, and an error-
checking fi eld
y, only one
1
RLC-SVU006A-E4
Page 13
4
Overvie
w
r
e
s
w
.
.
.
.
.
.
.
.
.
.
P
)
)
s
.
Valid addresses are 001 to 127 for BACnet and 001
.
THD units utilize the following control/interface
components:
racer™ UC800 Controlle
racer TD7 Operator Interfac
UC800 Specifi cations
This section covers information pertaining to the UC800 controller hardware.
Wiring and Port Description
Figure 3 illustrates the UC800 controller ports, LEDs, rotary switches, and wiring terminals. The numbered list
ollowing Figure 3 corresponds to the numbered callouts
in the illustration.
ntrols
ottom View
. Rotary Switches for setting BACnet® MAC address or MODBUS ID
. LINK for BACnet MS/TP, or MODBUS Slave (two terminals, ±). Field
wired if used
3. LINK for BACnet MS/TP, or MODBUS Slave (two terminals, ±). Field wired if used
4. Machine bus for existing machine LLIDs (IPC3 Tracer bus 19.200 baud). IPC3 Bus: used for Comm4 using TCI or LonTalk® using LCI-C
5. Power (210 mA at 24 Vdc) and ground terminations (same bus as
tem 4). Factory wired
. Not used
. Marquee LED power and UC800 Status indicator.
. Status LEDs for the BAS link, MBus link, and IMC link
9. USB device type B connection for the service tool (Tracer TU)
0. The Ethernet connection can only be used with the Tracer AdaptiView isplay
1. USB Host (not used)
RLC-SVU006A-E
ront Vie
Communication Interfaces
There are four connections on the UC800 that support the communication interfaces listed. Refer to Figure 3,
. 13 for the locations of each of these ports.
BACnet MS/T
MODBUS Slave
onTalk using LCI-C (from the IPC3 bus
Comm 4 using TCI (from the IPC3 bus
Rotary Switche
There are three rotary switches on the front of the UC800 controller. Use these switches to defi ne a three-digit
ddress when the UC800 is installed in a BACnet or
MODBUS system (e.g., 107, 127, etc.)
o 247 for MODBUS.
ED Description and Operation
There are 10 LEDs on the front of the UC800. Figure 4
hows the locations of each LED and Table 8, p. 14
escribes their behavior in specifi c instances
3
Page 14
4
ntrol
s
s
C
:
!
l
g
e
.
.
U
.
®
LED
)
on
e
C800 Statu
wered. If the Marquee LED is green solid,
the UC800 is powered and no problems exist.
arquee
BUS, IM
thernet
ink
ervice
NOTICE
ectrical Noise
Maintain at least 6 inches between low-voltage (<30V) and high voltage circuits. Failure to do so could result in
ectrical noise that could distort the signals carried by
e the low-volta
ow power or malfunction. If the Marquee
ED is red solid, the UC800 is powered, but
there are problems present.
larm. The Marquee LED blinks Red when an
larm exists.
The
LED blinks green at the data transfer
rate when the UC800 transfers data to other
evices on the link.
,
The
LED blinks yellow at the data transfer
rate when the UC800 receives data from
ther devices on the link.
The link is connected and communicating.
The transfer rate when data ow is active on the link.
The Service LED is solid green when pressed.
or qualifi ed service technicians only. Do not se.
e wiring, including IPC.
LED is solid green if the Ethernet
CT LED blinks yellow at the data
Tracer TD7 Operator Interfac
nformation is tailored to operators, service technicians,
nd owners
hen operating a chiller, there is specifi c information
you need on a day-to-day basis—setpoints, limits,
iagnostic information, and reports.
ay-to-day operational information is presented at the
isplay. Logically organized groups of information—
chiller modes of operation, active diagnostics, settings
nd reports put information conveniently at your
ngertips
Tr a cer™ T
The RTHD operator interface allows for daily operational
asks and setpoint changes. However, to adequately service chillers Tracer™ TU service tool is required. (Non-Trane personnel, contact your local Trane offi ce for software purchase information.) Tracer TU adds a level of sophistication that improves service technician effectiveness and minimizes chiller downtime. This
ortable PC-based service-tool software supports service nd maintenance tasks, and is required for software
upgrades, confi guration changes and major service
sks
Tracer TU serves as a common interface to all Trane chillers, and will customize itself based on the properties of the chiller with which it is communicating. Thus, the service technician learns only one service interface.
he panel bus is easy to troubleshoot using
verifi cation. Only the defective device is replaced. Tracer
can communicate with individual devices or groups
f devices.
All chiller status, machine con customizable limits, and up to 100 active or historic
iagnostics are displayed through the service-tool
software interface.
s and their respective Tracer TU indicators visually
confi rm the availability of each connected sensor, relay,
nd actuator.
racer TU is designed to run on a customer’s laptop, connected to the Tracer control panel with a USB cable. Your laptop must meet the following hardware and software requirements:
1 GB RAM (minimum
1024 x 768 screen resoluti
CD-ROM driv
Ethernet 10/100 LAN card
An available USB 2.0 port
Microsoft® Windows® XP Professional operation system with Service Pack 3 (SP3) or Windows 7 Enterprise or Professional operating system (32-bit or 64-bit)
Microsoft .NET Framework 4.0 or later
guration settings,
sensor
1
RLC-SVU006A-E4
Page 15
4
Note
:
Tracer TU is designed and validated for this
:
For more information, see TTU-SVN01A-EN
e
ote
ntrols
inimum laptop confi guration. Any variation
rom this confi guration may have different results.
herefore, support for Tracer TU is limited to only
hose laptops with the confi guration previously
pecifi ed.
racer TU Getting Started Guid
RLC-SVU006A-E
Page 16
6
Diagnostic
s
ff
f
p
.
.
:
p
.
.
Diagnostic Name and Source: Name of Diagnostic and its source. Note that this is the exact text used in the User Interface and/or Service Tool displays.
ects Target: Defi nes the “target” or what is affected
A
by the diagnostic. Usually either the entire Chiller, or a particular Circuit or Compressor is affected by the diagnostic (the same one as the source), but in special cases functions are modifi ed or disabled by the diagnostic. None implies that there is no direct affect to the chiller, sub components or functional operation.
Design Note:
certain targets on its Diagnostics pages although
o the functionality implied by this table is supported. Targets such as Evap Pump, Ice Mode, Chilled Water Reset, External Set “Chiller” even though they do not imply a chiller shutdown – only a compromise of the specifi c feature
Severity: Defi nes the severity of the above effect.
Immediate means immediate shutdown of the affected
ortion, Normal means normal or friendly shutdown of the affected portion, Special Action means a special action or mode of operation (limp along) is invoked, but without shutdown, and Info means an Informational Note or Warning is generated. Design Note: Tracer TU does not support display of “Special Action”, on its Diagnostics pages, so that if a diagnostic has a special action defi ned in the table below, it will be displayed only as “Informational Warning” as long as no circuit
r chiller shutdown results. If there is a shutdown and special action defi ned in the table, then the Tracer TU Diagnostics Page display will indicate the shutdown type only
racer™ TU does not support the display
oints etc. – are displayed as simply
Persistence: Defi nes whether or not the diagnostic and
ts effects are to be manually reset (Latched), or can be either manually or automatically reset when and if the condition returns to normal (Nonlatched).
Active Modes [Inactive Modes]
periods of operation that the diagnostic is active in
nd, as necessary, those modes or periods that it is
specifi cally “not active” in as an exception to the active
odes. The inactive modes are enclosed in brackets, [ ].
ote that the modes used in this column are internal and
not generally annunciated to any of the formal mode
isplays.
riteria: Quantitatively defi nes the criteria used in
generating the diagnostic and, if nonlatching, the criteria for auto reset. If more ex
o the Functional Specifi cation is used
eset Level: Defi nes the lowest level of manual
iagnostic reset command which can clear the iagnostic. The manual diagnostic reset levels in order of
priority are: Local or Remote. For example, a diagnostic
hat has a reset level of Remote, can be reset by either
remote diagnostic reset command or by a local iagnostic reset command.
elp Text: Provides for a brief description of what kind
of problems might cause this diagnostic to occur. Both control system component related problems as well as chiller application related problems are addressed (as can possibly be anticipated). These help messages will be updated with accumulated fi eld experience with the chillers
States the modes or
lanation is necessary a hot link
1
RLC-SVU006A-E4
Page 17
4
Starter Diagnostic
s
e
e
e
]
a
]
al
8
alha
s
al
0
al
al
ex
Cod
iagnostic Name
nd Sourc
hase Reversal
8
tarter Dry Run Testhiller
se Loss
omentary Power
ss
A
wer Loss
evere Current
Imbalance
ffects arget
hiller
hiller
hiller
hiller
hiller
Severityersistenc
mmediate
mmediate
mmediate
mmediate
mmediate
rm
tch
tch
tch
nlatch
nLatch
tch
ctive Modes
Inactive Modes
ompressor
nergized
to transition
ommand [All
Other Times
tarter Dry Run
e
tart Sequence
nd Run mode
ll compressor
running and topping modes all compressor
tarting and non-
running modes]
ll compressor
running modes
all compressor
tarting and non-
running modes]
ll Running Modes
Diagnostics
Criteri
phase reversal was detected on the incoming current. On a compressor startup the phase reversal logic must detect and trip in a maximum of 0.3 second from
ompressor start.
hile in the Starter Dry Run Mode either 50% Line Voltage was sensed at the Potential Transformers or 10 % RLA Current was
ensed at the Current Transformers.
No current was sensed on one or two
f the current transformer inputs while
running or starting (See Nonlatching Power
oss Diagnostic for all three phases lost
hile running). Must hold = 20% RLA. ust trip = 5% RLA. Time to trip shall be
longer than guaranteed reset on Starter
odule at a minimum, 3 seconds maximum.
ctual design trippoint is 10%. The actual design trip time is 2.64 seconds. b) If Phase reversal protection is enabled and current is not sensed on one or more current
former inputs. Logic will detect and trip in maximum of 0.3 second from compressor
rt.
omentary Power Loss option disabled: No
ffect.
omentary Power Loss option enabled: A
loss of power on three line cycles or more
as detected. Diagnostic is reset in 30
econds.
ee Momentary Power Loss Protection
ecifi cation for additional information.
The compressor had previously established
urrents while running and then all three phases of current were lost. Design: Less than 10% RLA, trip in 2.64 seconds. This diagnostic will preclude the Phase Loss
iagnostic and the Transition Complete Input Opened Diagnostic from being called out. To prevent this diagnostic from occurring
ith the intended disconnect of main ower, the minimum time to trip must be reater than the guaranteed reset time of
the Starter module. Note: This diagnostic prevents nuisance latching diagnostics due to a momentary power loss – It does not
rotect motor/compressor from uncontrolled ower reapplication. See Momentary Power oss Diagnostic for this protection. This
diagnostic will auto reset in 10 seconds from its occurrence, and is not active during the
tart mode before the transition complete
input is proven. This prevents the chiller from
ycling due to some internal starter problem, s the starter would latch out on either a
Starter Fault Type 3” or a “Starter Did Not Transition” latching diagnostic. However true power loss occurring during a start would result in a misdiagnosis and the chiller would not automatically recover.
30% current imbalance has been detected n one phase relative to the average of all phases for 90 continuous seconds.
eset evel
c
c
c
emote
emote
c
RLC-SVU006A-E
7
Page 18
8
Diagnostic
s
e
e
s
]
aes
y
l
s
al
g
g
al
al701
t
alSta
Tra
odu
odu
alF5
y
p
al
o
5
t
alD6
d
t
al
ex
Cod
iagnostic Name
nd Sourc
E9 Starter Fault Type Ihiller
ED Starter Fault Type IIhiller
F1Starter Fault Type III
Solid State Starter
89
Compressor Did Not
Compressor Did Not
FA
Compressor Did Not
ccelerate: Shutdown
Transition Complete
D
lt
FD Drive Faul
rter Did Not
nsition
ccelerate Full
ccel: Transition
nput Shorted
t Speed Input
Shorte
ffect arget
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
Severityersistence
mmediate
mmediate
mmediate
mmediate
mmediate
mmediate
mmediate
nf
mmediate
mmediate
mmediate
atch
tch
tch
tch
tch
tch
tch Start Mode
tch Start Mode
tch Start Mode
tch
tch
ctive Modes
Inactive Modes
Starting - Y Delta
Starters Onl
Starting All types
f starter
tartin
Adaptive
requency Starter
Type]
ll The Solid State Starter Fault Relay is open
ll The AFD Drive Fault Relay is open
n the fi rst check
fter transition.
re-Star
re-Star
Criteri
This is a specifi c starter test where 1M(1K1) is closed fi rst and a check is made to ensure that there are no currents detected by the CT's. If currents are detected when only 1M is closed fi rst at start, then one of the other
ontactors is shorted. . This is a specifi c starter test where the
Shorting Contactor (1K3) is individually
nergized and a check is made to ensure that
there are no currents detected by the CT's. If
urrent is detected when only S is energized t Start, then 1M is shorted. b. This test in a. bove applies to all forms of starters (Note:
t is understood that many starters do not
onnect to the Shorting Contactor.).
s part of the normal start sequence to
pply power to the compressor, the Shortin Contactor (1K3) and then the Main Contactor (1K1) were energized. 1.6 seconds later there were no currents detected by the CT's for the last 1.2 seconds on all three
hases. The test above applies to all forms
f starters.
The Starter M transition complete signal in the designated time from its command to transition. The must hold time from the Starter M transition command is 1 second. The Must trip time from the transition command is
seconds. Actual design is 2.5 seconds. This diagnostic is active only for Y-Delta, Auto­Transformer, Primary Reactor, and X-Line
tarters. The starter module did not receive an “U
to Speed” or “End of Ramp” signal from the SSS within 2.5 seconds after commanding a bypass, or after the maximum acceleration time had expired, whichever is longer. This diagnostic only applies to SSS/AFD.
The compressor did not come up to speed (get to <85%RLA) in the allotted time defi ned by the Maximum Acceleration Timer
nd a transition was forced (motor put across
the line) at that time. This applies to all
tarter types. Note: Since RTHD SSS has no
forced transition capability, this info warning
an be followed with a “Compressor did not ccelerate fully” diagnostic above and an
rted start.
The compressor did not come up to speed (get to <85%RLA) in the allotted time defi ned by the Maximum Acceleration Timer
nd and the start was aborted per the starter onguration selected.
The Transition Complete input is shorted before the compressor was started. This is
ctive for all electromechanical starters.
The “At Speed” input is shorted before the
ompressor was started. This is active for
lid state starters and AFD.
le did not receive a
le
et
evel
oca
c
c
c
c
c
c
emote
emote
c
c
1
RLC-SVU006A-E4
Page 19
4
ex
e
e
e
]
aes
s
al
8
en
al
oad
al
l
al
alnLa
l
alnLa
l
/
Cod
Transition Complete
D7
D
A
iagnostic Name
nd Sourc
nput Opened
t Speed Input
Opened
tor Current
verl
tarter Contactor nterrupt Failure
Over Voltage
nder Voltage
ffects arget
hiller
hiller
hiller
hiller
hiller
hiller
Severityersistenc
mmediate
mmediate
mmediate
mmediate nd Special
ction
rm
rm
tch
tch
tch Chiller Energized
tch
tch
tch
ctive Modes
Inactive Modes
ll Running Modes
fter transition
ompleted
ll Running Modes
fter At Speed
rov
tarter Contactor
not Energized
Starter Contactor
nergized]
l
l
Diagnostics
Criteri
The Transition Complete input is open
ith the compressor motor running after a
uccessful completion of transition. This is
ctive only for all electromechanical starter
The “At Speed” input was found to be
pened with the compressor motor running fter successfully obtaining an at speed and
bypassed condition. This is active for solid
tate starters and AFD
Compressor current exceeded overload time
s. trip characteristic. For A/C products Must trip = 140% RLA, Must hold=125%, nominal trip 132.5% in 30 seconds
etected compressor currents greater than
0% RLA on any or all phases when the
ompressor was commanded off. Detection
time shall be 5 seconds minimum and
seconds maximum. On detection and until the controller is manually reset: generate diagnostic, energize the appropriate alarm relay, continue to energize the Evap and Cond Pump Outputs, continue to command the affected compressor off, fully unload the
ffected compressor. For as long as current
ontinues, perform liquid level and oil return
as pump contro . Average of all monitored Line voltages
bove + 10% of nominal. [Must hold =
10% of nominal. Must trip = + 15% of
nominal. Reset differential = min. of 2%
nd max. of 4%. Time to trip = minimum f 1 min. and maximum of 5 min.)
esign: Nom. trip: 60 seconds at greater
than 112.5%, + or - 2.5%, Auto Reset at
9% or less.
. Average of all monitored Line voltages below - 10% of nominal or the Under Overvoltage transformer(s) are not
onnected. [Must hold = - 10% of nominal.
ust trip = - 15% of nominal. Reset
ifferential = min. of 2% and max. of 4%. Time to trip = min. of 1 min. and max. of 5 min.) Design: Nom. trip: 60 seconds at less than 87.5%, + or - 2.8% at 200V or
or - 1.8% at 575V, Auto Reset at 90%
r greater.
et
evel
c
c
c
c
emote
emote
RLC-SVU006A-E
Page 20
Diagnostic
s
s
e
e
s
]
a
d
onLa
l
5
alnla
Temp
8
abo
d
)
al9C
)
al
)
]
al
E
3000
Main Processor Diagnostic
ex
Cod
iagnostic Nam
9
Unexpected Starter
B
9
9D
A
efrigerant Pressure
97
efrigerant Pressure
: Reset Has
ccurre
Shutdown
ow Evaporator
efrigerant
erature
w Oil Flow
ss of Oil at
ompressor
(Running)
ss of Oil at
ompressor
Stopped
w Differential
Differential
ffect arget
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
Severityersistence
nf
rm
mmediate
mmediate
mmediate
mmediate nd Special
ction
mmediate
mmediate
ctive Modes
Inactive Modes
tch
modes, Starting,
tch
tch
Chiller Energized
tch
tch
tch
tch Chiller Energized
tch Chiller Energized
l
ll Cprsr Running
unning and reparing to
Shutdown
ll Ckt Running
es
nd Delta P
Psi
tarter Contactor
nergized
ompressor Pre-
tart [all other
modes
Criteri
The main processor has successfully come
ut of a reset and built its application.
reset may have been due to a power up, installing new software or conguration. This diagnostic is immediately and automatically
leared and thus can only be seen in the
istoric Diagnostic List in TechView The Starter module status reported back that
it is stopped when it should be running and no Starter diagnostic exists. This diagnostic
ill be logged in the active buffer and then
leared. . The inferred Saturated Evap Refrigerant
Temperature (calculated from suction
ressure transducer(s)) dropped below the ow Refrigerant Temperature Cutout Setpoint
for 450°F-sec (10°F-sec max rate) while the
ircuit was running after the ignore period had expired. The integral is held at zero for the 1 minute ignore time following the circuit
tartup and the integral will be limited to never trip in less than 45 seconds, i.e. the
rror term shall be clamped to 10°F. The minimum LRTC setpoint is -5°F (18.7 Psia) the point at which oil separates from the refrigerant. b. During the timeout of the trip integral, the unload solenoid(s) of the running compressors on the circuit, shall be
nergized continuously and the load solenoid
hall be off. Normal load/unload operation
ill be resumed if the trip integral is reset by
return to temps above the cutout setpoint. The oil pressure was out of the acceptable
pressure range for 15 seconds, while the
elta Pressure was greater than 15 Psid.:
cceptable range is 0.50 or 0.60 > (PC-Po) /
ve
PC-PE) for the fi rst 2.5 minutes of operation,
nd 0.40 or 0.50 > (PC-Po) / (PC-PE thereafter. The higher ratios used if the
stem DP is less than 23 psid
n running modes , Oil Loss Level Sensor
detects lack of oil in the oil tank feeding the
ompressor (distinguishing a liquid fl ow from
vapor fl ow
il Loss Level Sensor detects a lack of oil in
the oil tank feeding the compressor for 90
econds after EXV preposition is completed.
ote: Compressor start is delayed while
aiting for oil to be detected.
The system differential pressure was either below 15 Psid for more than 164 Psid-sec,
r below 23.0 Psid for latter integral’s value is not cleared for any reason including diagnostic trip, manual reset, or power up reset (ie. Integral is saved nonvolatily on power down). The integral will decay while circuit is running at a max rate
f –10 PSID, and while stopped at a rate of
0.4 PSID. This same integral is associated ith the operating mode “Compressor Cool own”. Also see diagnostic below
The system differential pressure was below
7.7 Psid. The occurrence of this diagnostic ill saturate the above “Low Diff Rfgt Press”
ntegral and invoke the same “Compressor
Cool Down” op mode.
Psid-sec. The
eset
evel
emote
emote
c
c
c
emote
emote
20
RLC-SVU006A-E4
Page 21
4
e
e
e
]
aes
6
al
)
6
o
y
Temp
]
E
t
al
l
al
l
0
lt p
p
8
t
l
l
onLa
)
l
al
)
Diagnostics
ex
Cod
7D
583
584
iagnostic Nam
C
C
8
84
9
9
igh Differential
efrigerant Pressure
igh Refrigerant
Temperature Sensor
vaporator Liquid
AS Communication
ow Evaporator Liquid
igh Evaporator
ressure Rati
igh Cprsr
fgt Discharge
erature
ow Discharge
Superhea
ompressor
ischarge
evel Sensor
AS Failed
to Establish
mmunication
s
vel
iquid Leve
ffects arget
Severityersistenc
hiller
hiller
hiller
hiller
hiller
hiller
hiller Specia
hiller Specia
hiller
hiller
rm
mmediate
mmediate
rm
mmediate
rm
nf
rm
ctive Modes
Inactive Modes
tch Chiller Energized
Service Pumpdown
tch
tch
tch
tch
tch
tch
tch
Onl
ll [compressor
not running or
during compressor
run unload
ny Running Mode
l
l
ower-u
l
tarter Contactor
nergized
all Stop modes]
tarter Contactor
nergized
all Stop modes]
Criteri
. The system differential pressure was bove 160 Psid- trip immediately (normal
hutdown
The diff pressure was above 152 Psid - trip
in 1 hour The system pressure ratio exceeded 5.61 for
contiguous minute. This pressure ratio is fundamental limitation of the compressor.
The pressure ratio is defi ned as Pcond (abs)/
evap(abs).
The compressor discharge temperature
xceeded 190°F. This diagnostic will be
uppressed if it occurs during the compressor run-unload period or after the compressor has stopped, but a run unload will be terminated early as a result. Note: As part
f the Compressor High Temperature Limit
ode (aka Minimum Capacity Limit), the
ompressor shall be forced loaded as the ltered discharge temperature nears this trip-point.
hile Running Normally, the Discharge Superheat was less than 12 degrees F +- 1F for more than 6500 degree F seconds.
t startup the UCM shall ignore the Discharge
Superheat for 5 minutes.
Sensor or LLID
Sensor or LLID
The BAS was setup as “installed” and the
AS did not communicate with the MP within 5 minutes after power-up. Refer to Section n Setpoint Arbitration to determine how
etpoints and operating modes may be
ffected. Note: The original requirement for
this was 2 minutes, but was implemented at
minutes for RTAC.
The BAS was setup as “installed” at the MP
nd the Comm 3 llid lost communications
ith the BAS for 15 contiguous minutes
fter it had been established. Refer to
Section on Setpoint Arbitration to determine how setpoints and operating modes may be effected by the comm loss. The chiller follows the value of the Tracer Default Run Command which can be previously written by Tracer and stored nonvolatilely by the MP
either use local or shutdown).
The liquid level sensor is seen to be
t or near its low end of range for 80
ontiguous minutes while the compressor
is running. Design: 20% or less of bit count
orresponding to –21.2 mm or less liquid
level for 80 minutes The liquid level sensor is seen to be at or
near its high end of range for 80 contiguous minutes while the compressor is running. (The diagnostic timer will hold, but not clear
hen the circuit is off). Design: 80% or more
f bit count corresponding to +21.2 mm or
more liquid level for 80 minutes
et
evel
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
RLC-SVU006A-E
1
Page 22
2
Diagnostic
s
e
e
s
]
aes
t
o
l
t
onLa
l
02
t
onLa
l
t
d
l
p)
onLa
)
d
g
al
l
d
l
g
o
l
8
al
al
l
al
l
1
]
al
d
al
ex
Cod
7
9A
9B
5B
iagnostic Nam
xternal Chilled/Hot
7
xternal Current Limit
9
xternal Base Loading
4
vap Water Flow
A
(Entering Water
vaporator Entering
ater Temp Sensor
vaporator Leavin
ater Temp Sensor
Condenser Entering
ater Temp Sensor
Condenser Leavin
ater Temp Sensor
Condenser Rfgt
ressure Transducer
ressure Transducer
il Flow Protection
E
efrigerant Pressure
ater Setpoin
etpoin
output power
inpu
etpoin
Tem
vaporator Rfgt
il Pressure
Transducer
lt
ow Evaporator
ffect arget
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
Severityersistence
nf
nf
nf
nfo an Special
ction
nf
nfo an Special
ction
rm
nfo an Special
ction
nf
rm
rm
rm
mmediate
mmediate
onLatch
tch
tch
nLatch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
ctive Modes
Inactive Modes
l
l
l
l
ny Ckt(s)
nergized
No Ckt(s
nergized]
l
l
l
l
l
tarter Contactor
nergized [all Stop
modes
Chiller Prestart an
Chiller Energized
Criteri
. Function Not “Enabled”: no diagnostics. b.
Enabled”: Out-Of-Range Low or Hi or bad
LID, set diagnostic, default CWS to next level of priority (e.g. Front Panel SetPoint). This Info diagnostic will automatically reset if the input returns to the normal range.
. Not “Enabled”: no diagnostics. b.
Enabled”: Out-Of-Range Low or Hi or bad
LID, set diagnostic, default CLS to next level
f priority (e.g. Front Panel SetPoint. This
nfo diagnostic will automatically reset if the
input returns to the normal range. Out-Of-Range Low or Hi or bad LLID,
et diagnostic, This Info diagnostic will
utomatically reset if the input returns to the normal range.
. Not “Enabled”: no diagnostics. b.
Enabled”: Out-Of-Range Low or Hi or bad
LID, set diagnostic, default BLS to next level
f priority (e.g. Front Panel SetPoint. This
nfo diagnostic will automatically reset if the
input returns to the normal range. The entering evaporator water temp fell
below the leaving evaporator water temp. by more than 2°F for 100°F-sec. For falling lm evaporators this diagnostic cannot reliably indicate loss of fl ow, but can warn
f improper fl ow direction through the
vaporator, misbound temperature sensors,
r other system problems
ad Sensor or LLID Normal operation unless
CHW Reset is enabled. If CHW Reset is
nabled and either Return or Constant Return Chilled Water Reset is selected, its effect will be removed but slew rates on the change will be limited per the Chilled Water Reset spec.
Sensor or LLID
ad Sensor or LLID. If chiller running, and
ondenser water regulating valve option installed, force valve to 100% fl ow.
Sensor or LLID
Sensor or LLID
Sensor or LLID
Sensor or LLID
The Oil Pressure Transducer for this Chiller is reading a pressure either above its Condenser Pressure by 15 Psia or more, or below its Evaporator Pressure 10 Psia or more for 30 seconds continuously.
The Evaporator Refrigerant Pressure dropped below 10 psia just prior to compressor
tart. The pressure fell below 10 psia while running but before the 3 minute ignore time had expired or fell below 16 Psia after the
minute ignore time had expired.
et
evel
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
c
c
2
RLC-SVU006A-E4
Page 23
4
e
e
e
]
aes
)
)
3
f
p
)
6
)
alnLa
p
t
p
alnLa
y
p)
t
s
8
l
Diagnostics
ex
Cod
C
iagnostic Nam
ow Evaporator Water
Temp (Unit Off
B
84
B
Temp: Unit Of
ow Evaporator Water
Temp (Unit On
vaporator Water
vaporator Water
Condenser Water
Condenser Water
efrigerant Pressure
ow Evaporator
low Overdue
low Los
low Overdue
low Los
igh Evaporator
ffects arget
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
Severityersistenc
nfo and Special
ction
nfo and Special
ction
mmediate nd Special
ction
rm
mmediate
rm
mmediate
mmediate nd Special
ction
nLatch
nLatch
nLatch
tch
nLatch
tch
nLatch
nLatch
ctive Modes
Inactive Modes
Unit in Stop Mode,
r in Auto Mode
nd No Ckt(s
nergized
Any Ckt
nergized]
Unit in Stop Mode,
r in Auto Mode
nd No Ckt's
nergizd
Any Ckt Energizd]
ny Ckt[s]
nergized
No Ckt(s)
nergizd]
stab. Evap. Water
low on going from
STOP to AUTO.
vap pump
mmanded “on”
xcept for
All Stop modes]
stab Cond Water
low
Start and All Run
e
l
Criteri
The leaving Evaporator water temp. fell below the leaving water temp cutout setting for 30 degree F seconds while the Chiller is in the Stop mode, or in Auto mode with no
ompressors running. Energize Evap Water pump Relay until diagnostic auto resets, then return to normal evap pump control.
utomatic reset occurs when the temp rises
°F (1.1°C) above the cutout setting for
minutes.
The evap sat temp fell below the water tem
utout setting while the respective evap liquid level was greater than –21.2 mm for
0 (or 150 begining with rev 08) degree F
econds while Chiller is in the Stop mode, or in Auto mode with no compressors running.
nergize Evap Water pump Relay until
diagnostic auto resets, then return to normal
vap pump control. Automatic reset occurs
hen either the evap temp rises 2°F (1.1°C
bove the cutout setting or the liquid level
falls below –21.2mm for 30 minutes The Evaporator water temp. fell below the
utout setpoint for 30 degree F Seconds
hile the compressor was running. Automatic
reset occurs when the temperature rises
°F (1.1°C) above the cutout setting for minutes. This diagnostic shall not de­nergize the Evaporator Water Pump Output.
vaporator water fl ow was not proven within 0 minutes of the Evaporator water pum
relay being energized. The Evap pump
mmand status will not be effected. This
diagnostic will auto-clear on proof of fl ow
6-10 seconds of continuous fl ow), or if
hiller is returned to Stop mode. The Evaporator water fl ow proof input was
pen for more than 6-10 contiguous seconds fter fl ow had been proven. The pum
mmand status will not be effected. Even though the pump may be commanded to run in the STOP modes (pump off delay time), this diagnostic shall not be called out in the STOP modes. This diagnostic will auto-clear
n proof of fl ow (6-10 seconds of continuous
ow), or if chiller is returned to Stop mode. Condenser water fl ow was not proven within
0 minutes of the condenser pump rela
being energized. The Cond Pump shall be
ommanded off. Diagnostic is reset with
return of fl ow (although only possible with
xternal control of pum
The condenser water fl ow proof input was
pen for more than 6 contiguous seconds
fter fl ow had been proven. This diagnostic is automatically cleared once the compressor is stopped by a fi xed time out of 7 sec. The Cond Pump shall be commanded off but the
vap pump command will not be effected. The evaporator refrigerant pressure has
risen above 190 psig (future use – add “for
ontinuous15 seconds”). The evaporator
ater pump relay will be de-energized to
top the pump regardless of why the pump
is running. The diagnostic will auto reset
nd the pump will return to normal control
hen the evaporator pressures falls below
85 psig. This diagnostic must shutdown the
hiller if it is running.
et
evel
emote
emote
emote
emote
emote
emote
emote
cal
RLC-SVU006A-E
3
Page 24
Diagnostic
s
e
e
s
]
a
6
d
al
l
al
altdoo
Temp
d
l
2
t
onLa
d
odu
1
o
l
al
odu
l
al
d
l
d
6
o
l
3
/
t
o
l
C
t
onLa
l
a
ool
onLa
odu
g
ex
Cod
iagnostic Nam
B
F
C9
E
A
8
igh Evaporator
ater Temperature
igh Pressure Cutout
mergency Stop
efrigerant Monitor
Starter M
emory Error Type
Starter M
Conguration
Starter Failed to Arm
CI-C Software
ismatch: Use BAS
r Air
erature Sensor
npu
le
le
emory Error
Type 2 -
P: Invali
Check Clock
tar
estart Inhibi
T
ffect arget
Severityersistence
ne
nfo an Special
mmediate
mmediate
nfo an Special
mmediate
mmediate
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller inf
ction
ction
nf
nf
nf
nf
nf
nLatch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
ctive Modes
Inactive Modes
Only effective if
ither
Evap Wtr Flow
Overdue,
Evap Wtr Flow oss, or 3)Low
vap Rfgt Temp,-
nit Off, diagnostic
is active.
l
l
ll –if installe
l
l
l
l
l
l
Criteri
The leaving water temperature exceeded the high evap water temp limit (TV service menu settable –default 105F) for 15
ontinuous seconds. The evaporator water pump relay will be de-energized to stop the pump but only if it is running due one of the diagnostics listed on the right. The diagnostic
ill auto reset and the pump will return to normal control when the temperature falls 5°F below the trip setting. The primary
urpose is to stop the evaporator water ump and its associated pump heat from ausing excessive waterside temperatures nd waterside pressures when the chiller is
not running but the evap pump is on due to
ither Evap Water Flow Overdue, Evaporator
ater Flow Loss , or Low Evap Temp – Unit
Off Diagnostics. This diagnostic will not
uto clear solely due to the clearing of the nabling diagnostic.
high pressure cutout was detected; C.O. on
rise @ 180 psig, reset @ 135 psig (+/-5 psi
n switching tolerance) Note: Pressure relief alve is 200 Psig +- 2% trip at 315 ± 5 psi.
ote: Other diagnostics that may occur as an xpected consequence of the HPC trip will be uppressed from annunciation. These include hase Loss, Power Loss, and Transition
Complete Input Open.
. EMERGENCY STOP input is open. An xternal interlock has tripped. Time to trip
from input opening to unit stop shall be 0.1 to 1.0 seconds.
ad Sensor or LLID. This diagnostic will only ccur if OA sensor is congured.OA Chilled
ater reset will be suspended if selected and
Tracer OA unavailable. Open or Shorted input and the Rfgt Monitor
is setup as installed Checksum on RAM copy of the Starter LLID
onguration failed. Conguration recalled
from EEPROM. Checksum on EEPROM copy of the Starter
LID conguration failed. Factor default
lues used.
P has an invalid conguration based on the
rrent software installe
The real time clock had detected loss of its
scillator at some time in the past. Check /
replace battery? This diagnostic can be
ffectively cleared only by writing a new alue to the chiller’s time clock using the
TechView or DynaView’s “set chiller time” functions.
Starter failed to arm or start within the
llotted time (2 minutes).
The Restart Inhibit was invoked on
ompressor. This indicates excessive chiller ycling which should be corrected.
The neuron software in the LCI-C m does not match the chiller type. Download the proper software into the LCI-C neuron. To do this, use the Rover service tool, or
LonTalk® tool capable of downloadin oftware to a Neuron 3150®.
le
eset
evel
c
c
c
emote
emote
c
c
emote
emote
emote
emote
emote
24
RLC-SVU006A-E4
Page 25
4
e
e
e
]
aes
05
s
l
a
al
Diagnostics
Cod
7
ex
iagnostic Nam
Software Error
mber: 1001 Call Trane Service
ffects arget
ll
func-
tion
Severityersistenc
mmediate
tch –
ower down
reset is reqd
ctive Modes
Inactive Modes
l
Criteri
high level software watchdog has
etected a condition in which there was
ontinuous 5 minute period of compressor
eration, with neither chilled water fl ow
nor a” contactor interrupt failure” diagnostic
ctive. The occurrence of this software error
message suggests an internal software state
hart misalignment has occurred. The events that led up to this failure, if known, should be recorded and transmitted to Trane Controls
ngineering – (SW rev 6 and higher)
et
evel
loc
RLC-SVU006A-E
Page 26
Diagnostic
s
s
e
e
]
a
1Co
oad
al
l
a
2Co
oad
al
a
p
al
l
a
al
l
a
1
d
g
l
d
y
g
al
l
d
2Co
doo
d
l
a
3
p
al
l
a
p
d
l
d
6
g
p
o
a
6
p
d
l
d
6
l
a
t
d
l
a
t
d
l
a
Communication Diagnostic
ex
Cod
iagnostic Nam
D
D
Comm Loss: External
mergency Stop
E
xternal Ice Building
uilding Status Rela
mm Loss: Out
E
E
B
B
B
E9
ir Temperature
omm Loss: Eva
eaving Water Temp
omm Loss: Eva
ntering Water Temp
Condenser Leavin
Condenser Entering
omm Loss: Cprsr
ischarge Rfgt Temp
Chilled/Hot Water
urrent Limit Setpoin
mm Loss: Slide
lve Unl
mm Loss: Slide
lve L
uto/Sto
mm Loss:
mm Loss:
Comman
mm Loss: Ice
mm Loss:
ater Tem
mm Loss:
ater Tem
mm Loss: Ext
etpoin
mm Loss: Ext
ffectsSeverityersistence
hiller
hiller
hiller
hiller
ild-
in
ild-
in
r
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
rm
rm
rm
rm
rmal
rm
nfo an Special
ction
rm
nfo an Special
ction
nf
nfo an Special
ction
mmediate
nfo an Special
ction
nfo an Special
ction
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
ctive Modes
Inactive Modes
l
l
l
l
l
l
l
l
l
l
l
l
Criteri
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
Continual loss of communication between the MP and the Functional ID has occurre for a 30 second period. Chiller shall revert to normal (non-ice building) mode regardless of last state.
Continual loss of communication between the MP and the Functional ID has occurre for a 30 second period. Chiller shall revert to normal (non-ice building) mode regardless of last state.
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Note that if this diagnostic
ccurs, Chiller shall remove any OA Chilled
ater Reset, if it was in effect and if Tracer OA was unavailable. Apply slew rates per Chilled Water Reset spec
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
Continual loss of communication between the MP and the Functional ID has occurre for a 30 second period. Chiller shall remove
ny Return or Constant Return Chilled Water
eset, if it was in effect. Apply slew rates per
Chilled Water Reset spec. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
Continual loss of communication between the MP and the Functional ID has occurre for a 30 second period. If chiller running,
nd condenser water regulating valve option
installed, force valve to 100% fl ow. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Chiller shall discontinue
use of the External Chilled Water Setpoint
ource and revert to the next higher priority
for setpoint arbitration Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Chiller shall discontinue use of the External Current limit setpoint and revert to the next higher priority for Current
imit setpoint arbitration
eset
evel
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
26
RLC-SVU006A-E4
Page 27
4
e
e
e
]
aes
al
l
l
6
l
0
al
l
2
al
l
al
l
6Co
l
al
l
6Co
al
l
6
t
al
l
6
al
l
8
y
l
6
y
o
l
6
t
o
l
6
t
o
l
6
t
l
6
l
8
l
al
0
l
al
Diagnostics
ex
Cod
5F
iagnostic Nam
Comm Loss: High
ressure Cutout
vaporator Water
B
Condenser Water
F
F
B
B
B
B
B
B
B
B
B
8
9
vaporator Rfgt
Condenser Rfgt
Comm Loss: Oil
mm Loss: Oil
eturn Gas Pump Fil
mm Loss: Oil
eturn Gas Pump
Comm Loss: Oil Loss
evel sensor Inpu
mm Loss: Master
vaporator Water
Condenser Water
Comm Loss: SSS/AFD
efrigerant Monitor
mm Loss: Ext Base
oading Setpoin
mm Loss: Ext Base oading Command
vaporator Rfgt
mm Loss: Starter
witch
mm Loss:
low Switch
mm Loss:
low Switch
mm Loss:
ressure
mm Loss:
ressure
ressure
rain
il Line SV
mm Loss:
ump Rela
mm Loss:
ump Rela
l
mm Loss:
npu
mm Loss:
iquid Leve
ffectsSeverityersistenc
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
rm
mmediate
mmediate
rm
rm
rm
rm
rm
rm
rm
nfo
nf
nf
nf
nfo and Special
ction
nfo and Special
ction
rm
mmediate
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
ctive Modes
Inactive Modes
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
Criteri
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period. The external base load setpoint input is removed from the arbitration to establish the Base
oadingSetpoint.
Continual loss of communication between the MP and the Functional ID has occurred for a 30 second period. The external base load input is removed from the arbitration to
nable Base Loading.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
Continual loss of communication between the
P and the Functional ID has occurred for a
0 second period.
et
evel
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
emote
c
RLC-SVU006A-E
7
Page 28
8
Diagnostic
s
e
e
]
aes
1
al
l
a
5
2
al
l
a
l
al
d
l
a
S
0
Op
ys
o
l
a
6
t
o
l
a
6Co
d
t
al
l
a
6Co
d
t
l
a
03
t
l
a
t
a
d
o
g
l
a
ex
Cod
7
704
iagnostic Nam
94
lectronic Expansion
9
lectronic Expansion
Starter Comm Loss:
D
Comm Loss: Local
9D
A
B
B
B
87
AS Interface
Comm Loss:
Status Programmable
Compressor % RLA
mm Loss: Con
fgt Pressure Outpu
mm Loss: Con
ead Press Cntrl
mm Loss: AFD
peed signal outpu
mm Loss: AFD
utput power inpu
Comm Loss: External
t Water Comman
omm Loss:
lve
mm Loss:
lve
in Processor
ela
mm Loss:
utpu
utpu
ffectsSeverityersistence
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
hiller
rm
rm
mmediate
nfo an Special
ction
nf
nf
rm
mmediate
mmediate
mmediate
nf
tch
tch
tch
tch
tch
tch
tch
tch
tch
tch
arnin
ctive Modes
Inactive Modes
l
l
l
l
l
l
l
l
l
l
Criteri
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Starter has had a loss of communication with
the MP for a 15 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Use the last values sent from BA
Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period. Continual loss of communication between the
P and the Functional ID has occurred for
0 second period.
et
evel
emote
emote
c
emote
emote
emote
emote
emote
emote
emote
emote
2
RLC-SVU006A-E4
Page 29
4
Operator Display Diagnostics and Message
s
Table 9. Operator display diagnostics and messages
ge
n
g
t
t
eset
g
d
U
Diagnostics
Operator Display Messa
Valid Conguration is Presen
Communication Lost with UC800
isplay Failed to Establish
mmunication
isplay is about to Restar
rror Resulted From Invalid Conguration – Record Condition and Call Trane Service
ssertion: ‘File Name’ ‘Line Number’
escriptio
//Troubleshootin
valid conguration is present in the MP’s nonvolatile memory. The conguration
is a set of variables and settings that defi ne the physical makeup of this
articular chiller. These include: number/airfl ow,/and type of fans, number/and
ize of compressors, special features, characteristics, and control options.
//Temporary display of this screen is part of the normal power up sequence.
thernet cable not connected between display and UC800.
C800 not powered. C800 has an invalid conguration – Download a valid conguration C800 is in Binding View. When exit Binding View, select ‘Restart’ on this
ssage.
thernet cable not connected between display and UC800.
C800 not powered. C800 just has the backup application running as received from the vendor.
ownload CTV application software. C800 has an invalid conguration – Download a valid conguration
The display is low on memory, and needs to re-start. Select Yes to restart. Selecting Yes will not affect the UC800 operation.. Only the Operator Display is r
.
This error message is displayed when the MP code fi nds itself in an illegal location. These assertion points are placed in code locations to aid the software team in identifying why the MP locked up as a result of vectoring to an invalid location.
hen this message occurs, copy down the fi le name and line number and have
this ready to give Trane service. This message remains on the screen for two minutes. After two minutes, the
atchdog times out and a ‘Watchdog Error’ message is displayed The watchdo
then resets the MP. The MP heads into a boot and conguration mode the same
s it does on a power up.
These error messages are on the AdaptiView screen and do not appear in Tracer TU nor in the diagnostic logs.
ile Not Foun Screen partially populated. Auto and
Stop button graphics display, no text.
creen Unresponsive
The Page Cannot be found
C800 Conguration is Invalid
RLC-SVU006A-E
date UC800 software with Tracer T
alid conguration is not present. Download a conguration.
Tracer TU is downloading software. Wait till download is complete.
ost likely this UC800 has only the backup application. Download the latest UC
00 software build.
This could also mean that the UC800 does not have a valid conguration.
ownload a conguration to it.
Cycle power to the OD and UC800.
C could be in binding view. If so, get it out of binding view by navigating to
nother screen in Tracer TU.
pdate the UC800 conguration with Tracer TU.
Page 30
otes
30
RLC-SVU006A-E4
Page 31
4
otes
RLC-SVU006A-E
1
Page 32
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader
f
d
4
y
.
in creating and sustaining safe, comfortable and energy effi cient environments, Trane offers a broad portfolio
advanced controls and HVAC systems, comprehensive building services and parts. For more information visit
o www.Trane.com
© 2014 Trane All rights reserve
LC-SVU006A-E4 April 201
New
We are committed to using environmentall conscious print practices that reduce waste
Loading...