This installation and operation document includes information about the
™
Trac er
controller works in both the standalone mode and when connected to a Tracer
Summit
• Controller features
• Sequence of operation
• Inputs and outputs required for each feature
The controller is applied to air handling product configurations supporting
analog modulating valves, economizer damper, and face and bypass damper.
The controller also supports a constant volume or variable air volume supply
fan.
The configurable air handling unit controller is also available as the Tracer
AH.541 field-installed air handling unit controller (St. Paul, Minnesota). The
features and functions of the Tracer AH.541 are identical to those of the
Tracer AH.540 described in this manual.
AH.540 configurable air handling unit (AHU) controller. Version 1.0 of the
™
automation system. This document details:
CNT-SVX05A-EN1
Supported Products
The configurable air handling unit controller is available installed, pre-wired,
and tested with the following Trane air handling equipment:
™
Packaged Climate Changer
LPC AHorizontal/Front Top
LPC BHorizontal/Top Front
LPC CVertical/Front Top
LPC DVertical/Top Front
LPC EVertical/Top Back
LPC FVertical/Back Top
Manufacturing Location: Macon, Georgia
Modular Climate Changer
The Tracer™ AH.540 controller availability on the Modular Climate Changer air
handler is limited to the features and functions provided by the controller.
See the Features section for more information.
Manufacturing Location: Lexington, Kentucky
T-Series Climate Changer
The Tracer AH.540 controller availability on the T-Series Climate Changer air
handlers is limited to the features and functions provided by the controller.
See the Features section for more information.
Manufacturing Location: Lexington, Kentucky
Air Handling Units
™
Air Handling Units
™
Air Handling Units
2CNT-SVX05A-EN
Features
Ta b l e 1 — Tra c e r™ AH.540 features and contro l modes
Constant volume space
Fan controlOn/OffOn/OffVariable
Duct static pressure con-
trol
Hydronic coolingXXX
Hydronic heatingXXX
Steam heatXXX
Face and bypass heating XXX
Ventilation controlXXX
Economizer damperXXX
Warm-up functionsXXX
Mixed air temperature
control
Exhaust fan (on/off)XXX
temperature control
XXX
Constant volume
discharge air control
Variable air volume
control
X
Fan control options are:
• Constant volume with space temperature control
• Constant volume with discharge air temperature control
• Variable air volume with discharge air temperature control
Features available for any of the above fan control options include:
• Hydronic cooling valve
• Hydronic heating valve
• Steam heat valve
• Face and bypass damper (heating only)
• Economizer cooling
CNT-SVX05A-EN3
Termination board
Analog Inputs
Power
Analog Outputs
Comm 5 Communication
Te rm ina ls
Binary Outputs
Duct Static Pressure Input
Binary Inputs
4CNT-SVX05A-EN
Controller board
ID Label
Supply Fan
Status LED
Exhaust Fan
Status LED
RED Service LED
Service Push Button
Yellow Comm LED
Test Push Button
Green Status LED
CNT-SVX05A-EN5
Physical specifications
Board dimensions
Termi n a t io n b oar d
Height: 3.5 inches (88.9 mm)
Width:8.0 inches (203.2 mm)
Depth:1.0 inch (25.4 mm)
Controller board
Height: 4.3 inches (109.2 mm)
Width:8.0 inches (203.2 mm)
Depth:2.0 inches (50.8 mm)
Operating environment
-40° to 70°C (-40° to 158°F)
5% to 95% relative humidity non-condensing
Storage environment
-40° to 85°C (-40° to 185°F)
5% to 95% relative humidity non-condensing
Agency Conformance
(See Appendix for use limitations)
UL
UL unlisted component
UL 873 Temperature Indicating and Regulating Equipment
CUL C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
CE
Conducted EmissionsEN55022 Class A
EN55022 Class B
EN 61000-3-2
EN 61000-3-3
Radiated EmissionsEN55022 Class A
ImmunityEN 50082-2 Industrial
FCC
CFR 47, Part 15, Subpart A, Class A
CFR 47, Part 15, Subpart A, Class B
Power requirements
Low voltage class 2, non-safety device
18 to 32VAC (24VAC nominal)
Maximum VA = 13VA (control board)
50 or 60 HZ
6CNT-SVX05A-EN
Physical specifications
Binary outputs
The binary outputs are normally-open, form A relays. The relays act as a switch,
either making or breaking the circuit between the load (device) and 24VAC. When
binary output 1 is energized, 24VAC is supplied to terminal TB21-1 (OUT),
energizing the supply fan start/stop relay.
Example:
24VAC
GND
Each binary output has a green status LED on the Tracer
The LED is off when the relay contacts are open. The LED is on when the relay
contacts are closed.
When the binary output relay is off (contact is open), a multimeter should
measure 0VAC across the output terminals. When the binary output relay is on
(contacts are closed), a multimeter should measure 24VAC across the output
terminals.
Termination board
TB21-1 (OUT)
TB21-2 (GND)
BO 1
Wiring external to the
Termination board
Supply Fan (start/stop)
Relay
AH.540 control board.
Table 2 — Binary outputs
DescriptionFunctionFactory
BO 1Supply fan
BO 2Exhaust fan
BO 3Not used
BO 4Not used
BO 5Not used
BO 6Not used
Note 1: Terminals BO 3, BO 4, BO 5, and BO 6 do not serve any function of the Tracer AH.540 controller and are not used.
start/stop
start/stop
(Note 1)
(Note 1)
(Note 1)
(Note 1)
Ter min al s
J21TB21-1
J22TB22-1
J23TB23-1
J24TB24-1
J25TB25-1
J26TB26-1
Field
Ter min al s
TB21-2
TB22-2
TB23-2
TB24-2
TB25-2
TB26-2
LabelTerminal
OUT
GND
OUT
GND
OUT
GND
OUT
GND
OUT
GND
OUT
GND
Function
24VAC
Ground
24VAC
Ground
Not usedNot used
Not usedNot used
Not usedNot used
Not usedNot used
Maximum
Output Rating
24VA
24VA
CNT-SVX05A-EN7
Physical specifications
Analog outputs
The analog outputs are 0 to 10VDC.
Table 3 — Analog outputs
DescriptionFunctionFactory
AO 1Supply fan
AO 2Cool outputJ12TB12-1
AO 3Heat outputJ13TB13-1
AO 4Face and bypass
AO 5Outdoor air
AO 6 Not used—————
speed
damper
damper
terminals
J11TB11-1
J14TB14-1
J15TB15-1
Analog inputs
Table 4 — Analog inputs
Descriptio n FunctionSensor type
IN 1Space temp 10KΩ
IN 2Space setpoint 1K
IN 3Fan mode switch
IN 4Discharge air
IN 5Outdoor air temp 10K
IN 6Mixed air tempRTD
J43Duct static pres-
Note 1: Sensor type: Switched resistance fan auto = 2320Ω +/-5%, fan off = 4870Ω +/-5%.
Note 2: Sen sor type RTD averaging sensor, 1000Ω at 0°C, platinum 385 curve.
Note 3: See Appendix for analog input sensor curves, Table 65 on page 76 and Table 66 on page 77.
(Note 1)
temp
sure
(Note 3)
thermistor
potentiometer
Switched
resistance
10K
thermistor
thermistor
(Note 2)
Specialized
pressure
transducer
Field
terminals
TB11-2
TB12-2
TB13-2
TB14-2
TB15-2
Ω
Ω
Ω
LabelTerminal
OUT
GND
OUT
GND
OUT
GND
OUT
GND
OUT
GND
Factory
terminals
J31TB31-1
J32TB32-1
J33TB33-1
J34TB34-1
J35TB35-1
J36TB36-1
J43-1 GND
J43-2 Signal
J43-3 5VDC
Field
terminals
TB31-2INGND
TB32-2INGND
TB33-2INGND
TB34-2INGND
TB35-2INGND
TB36-2INGND
NADuct
function
0 to 10VDC
Ground
0 to 10VDC
Ground
0 to 10VDC
Ground
0 to 10VDC
Ground
0 to 10VDC
Ground
LabelRange
static
Maximum
output rating
20mA
20mA
20mA
20mA
20mA
-15° to 50°C
° to 122°F
5
10° to 29.4°C
50
° to 85°F
Off (4870
Auto (2320
-40° to 100°C
–40
-40° to 100°C
-40
-40
-40° to 212°F
0 to 1250 Pascals
0 to 5.02 in. water
Ω +/-5%)
° to 212°F
° to 212°F
° to 100°C
Ω +/-5%)
8CNT-SVX05A-EN
Physical specifications
Binary inputs
Each binary input associates an input signal of 0VDC with closed contacts and
24VDC with open contacts. If the wired binary device has closed contacts, a
multimeter should measure less than 1.0VDC across the binary input terminals.
If the binary input has opened, a multimeter should measure greater than 20VDC
across the binary input terminals.
Table 5 — Binary inputs
Descriptio nFunctionFactory
IN 7Low temp detectJ37TB37-1
IN 8Run/stopJ38TB38-1
IN 9Occupancy or
IN 10Supply fan statusJ40TB40-1
IN 11Filter statusJ41TB41-1
IN 12Exhaust fan status J42TB42-1
generic
terminals
J39TB39-1
Field
terminals
TB37-2
TB38-2
TB39-2
TB40-2
TB41-2
TB42-2
LabelTerminal function
IN
GND
IN
GND
IN
GND
IN
GND
IN
GND
IN
GND
24VDC
Ground
24VDC
Ground
24VDC
Ground
24VDC
Ground
24VDC
Ground
24VDC
Ground
CNT-SVX05A-EN9
Analog and binary outputs
The Tracer AH.540 is configured at the factory per unit configuration and order
information. The controller is applied to air handling product configurations
supporting analog modulating valves, economizer damper, and face and bypass
damper. The controller supports a constant volume or variable air volume supply
fan.
General description
The configuration of analog and binary outputs is largely based on the unit
configuration. Each of the five analog outputs and two binary outputs is assigned
a specific function:
Table 6 — Analog outputs
AO 1Supply fan speed (VAV units only)
AO 2Cooling valve output (water)
AO 3Heating valve output (water or steam)
AO 4Face and bypass damper output
AO 5Outdoor air damper output
AO 6Not used
Table 7 — Binary outputs
BO 1Supply fan start/stop output
BO 2Exhaust fan start/stop output
Output overrides
The Tracer AH.540 controller includes a manual output test function.
This function can be initiated by depressing the Test push button on the
controller. Use this feature to manually exercise the outputs in a defined
sequence. For more information about the manual output test function,
see the Troubleshooting section.
Figure 1
The Tracer AH.540 controller includes a water balancing function, which can
be controlled by Rover™ or another communicating device to selectively drive
open or closed the water valve outputs. For more information about the water
balancing function see the Sequence of operation section.
10CNT-SVX05A-EN
Binary inputs
The default configuration for each binary input (including normally open/closed)
of the Tracer™ AH.540 is set at the factory. For field-installed AH.541 controllers,
the configuration of the binary inputs must be set with Trane Rover
software.
Configure any binary input not in use (an input to which no device is physically
connected) as Not Used.
The Tracer AH.540 controller has six available binary inputs. The binary inputs
are connected to the Tracer AH.540 terminal board on inputs IN 7 through IN 12.
Normally these inputs are factory-configured for the following functions.
Binary inputs
• IN 7: Low temperature detection (freezestat)
• IN 8: Run/stop
• IN 9: Occupancy or generic
• IN 10: Supply fan status
• IN 11: Filter status
• IN 12: Exhaust fan status
Configure IN 9 either as Occupancy or as a Generic binary input. When
configured as a generic binary input, IN 9 does not affect controller operation.
Table 8 — Table Binary input controller operation
Binary
input
IN 7Low temp detect
IN 8Run/stop
IN 9OccupancyNormally open UnoccupiedOccupied
IN 10Supply fan status
IN 11Filter statusNormally open DirtyClean
IN 12Exhaust fan statusNormally closed Exhaust fan
Note 1: During low temp detect, run/stop, and supply fan status diagnostics, the controller disables all normal unit
Note 2: The table below shows the controller’s response to low temp detect, run/stop, supply fan status, and exhaust
DescriptionConfigurationContact closedContact open
(Note 1)
(Note 1)
(Note 1)
operation of the fans, valves, and dampers.
fan status la tching diag nostics.
Normally closed NormalLatching diagnostic
Normally open Latching diagnostic
Normally open Normal Latching diagnostic
(Note 2)
diagnostic (Note 2)
(Note 2)
Normal
(Note 2)
Normal
™
service
CNT-SVX05A-EN11
Table 9 — Control response to binary input latching diagnostics
Binary
input
IN 7Low temp detectOffOpenFaceOpen
IN 8Run/stopOffClosedBypassClosedClosedOff
IN 10Supply fan status OffClosedBypassClosedClosedOff
IN 12Exhaust fan status Normal
Note 1: When steam is the source of heat, the heat output is cycled open and closed when the controller is shut down
Latching
diagnostic
on a Low Temp Detect latching diagnostic. See Steam valve cycling in the Sequence of operation section for further
details.
Supply
fan
Operation
Cool
output
Normal
Operation
Face and
bypass
damper
Normal
Operation
Heat
output
(Note 1)
Normal
Operation
Outdoor air
damper
ClosedOff
Normal
Operation
Exhaust
fan
Off
Binary inputs
Low temperature detection
The low temperature detection device can be automatically or manually reset.
However, you must manually reset the Tracer
Temperature Detect diagnostic to clear the diagnostic and restart the unit.
Low temperature detection protects the coils of hydronic units. A low
temperature detection device (freezestat) connected to binary input IN 7 detects
the low temperature. The Tracer AH.540 controller can protect the coil using
one binary input. When the controller detects the low temperature detection
signal, the controller generates a diagnostic which disables the fan, opens all
unit water or steam valves, and closes the outdoor air damper (when present).
Note: Even if the low temperature detection device automatically resets when
the coil/heat exchanger temperature returns to a normal value, you must clear
the Low Temperature Detect diagnostic from the controller to restart the air
handling unit. See the Resetting Diagnostics section for instructions to clear
controller diagnostics.
Table 10 — Low temperature detection controller operation
DiagnosticFan
Low temperature
detection
Note 1: When steam is the source of heat, the heat valve is cycled open and closed when the controller is shut down on
a Low Temp Det ect latching diagnostic. Cycling the steam valve helps prevent excessive cabinet temperatures. See
Steam valve cycling in the Sequence of operation section for further det ails.
operation
OffOpenOpen
Cool
output
Heat output Face and
(Note 1)
™
AH.540 controller Low
bypass
FaceClosed
Outdoor air damper
operation
Run/stop
This hardwired binary input IN 8 can be used for a variety of functions to shut
down the unit. The Tracer AH.540 controller systematically shuts down unit
operation and reports a Unit Shutdown diagnostic upon detecting a stop input.
For example, a condensate overflow sensor or a smoke detector can be
connected to the run/stop input to shut down unit operation.
The run/stop input creates a latching Unit Shutdown diagnostic. The run/stop
input must first be returned to the run condition and the diagnostic must be
reset in the controller before the unit is allowed to run.
Table 11 — Run/stop IN 8 binary input configuration
ConfigurationContact c losedContact open
Not usedRunRun
Normally closedRunStop
Normally openStopRun
12CNT-SVX05A-EN
Binary inputs
Occupancy
The Tracer AH.540 controller uses the occupancy binary input IN 9 for two
occupancy-related functions.
Standalone
For standalone controllers (any unit not receiving a communicated occupancy
request, typically from a building automation system), the occupancy binary
input determines the unit's occupancy based on the hardwired signal. Normally,
the signal is hardwired to a binary switch or clock.
When a hardwired occupancy signal on binary input IN 9 is open, the unit
switches to occupied mode if the occupancy input is configured as normally
open. When a hardwired occupancy signal is closed, the controller switches to
unoccupied mode (only if the occupied bypass timer = 0). See Occupied bypass
in the Sequence of operation section.
Communicated request
For controllers that receive a communicated occupancy request (typically from
a building automation system), the hardwired occupancy binary input, along
with the communicated occupancy request, place the controller in either
occupied, unoccupied, or occupied standby mode.
In occupied mode, the controller operates according to the occupied setpoints.
In occupied standby mode, the unit controller operates according to the
occupied standby setpoints. When the controller receives a communicated
unoccupied request, the controller operates according to the unoccupied
setpoints regardless of the state of the hardwired occupancy input (only if the
occupied bypass timer = 0).
When neither an occupancy device is wired to binary input IN 9 nor a
communicated input is used to select the occupancy mode, the controller
defaults to occupied mode because the occupancy binary input IN 9 typically
is configured as normally open and no occupancy device is connected.
CNT-SVX05A-EN13
Table 1 2 — Normally open hardwired input configuration
Binary input IN 9 can be configured as a generic binary input for a variety of
applications with Trane Tracer Summit
controller operation. Binary input IN 9 can be configured as Occupancy or
Generic. A generic binary input can be monitored only from Tracer Summit.
Supply fan status
The fan status binary input IN 10 indicates the presence of air flow through the
supply fan of an air handling unit. For Tracer
pressure switch detects fan status, with the high side of the differential being
supplied at the unit outlet and the low side supplied inside the unit. During fan
operation, differential pressure closes the normally open switch and confirms
that the fan is operating properly.
A Low Supply Fan Air Flow diagnostic is detected during the following two
conditions:
• The controller is commanding the fan On and the fan status switch is not in
the closed position
• The fan status switch does not close the binary input within the configurable
fan On delay time limit of the controller commanding the fan On
This is a latching diagnostic and discontinues unit operation until the diagnostic
is cleared from the controller. Additional details can be found in the
Troubleshooting section.
™
only. The binary input does not affect
™
AH.540 applications, a differential
Table 1 4 — Fan status binary input IN 10 configuration
Note 1: A Low Supply Fan Air Flow diagnostic is generated when the controller turns on the supply fan output, but the
supply fan status binary input indicates the supply fan is not running after the configurable fan delay time.
Filter status
The filter status switch connected to binary input IN 11 detects a dirty air filter
and indicates a need for maintenance. For Tracer AH.540 applications, a
differential pressure switch detects filter status, with the high side of the
differential being supplied at the filter inlet and the low side supplied at the filter
outlet. During fan operation, filter differential pressure increases as the filter
becomes increasingly dirty.
A normally open filter status switch closes when the differential pressure
reaches a set threshold. This is a non-latching, informational diagnostic and the
controller will continue normal unit operation.
Table 1 5 — Filter status configuration
IN 11 configurationContact closedContact open
Not usedCleanClean
Normally closedCleanDirty
Normally openDirtyClean
14CNT-SVX05A-EN
Binary inputs
Exhaust fan status
The exhaust fan status binary input IN 12 indicates the presence of air flow
through an exhaust fan associated with the controlled air handling unit. For
Trac er ™ AH.540 applications, a differential pressure switch detects exhaust fan
status, with the high side of the differential being supplied at the outlet. During
exhaust fan operation, differential pressure closes the normally open switch and
confirms that the fan is operating properly.
A Low Exhaust Fan Air Flow diagnostic is detected during the following two
conditions:
• The controller is commanding the exhaust fan On and the status switch is not
in the closed position
• The fan status switch does not close the binary input within two minutes of the
controller commanding the exhaust fan On
This is a latching diagnostic but does not affect controller operation of the air
handling unit. Refer to the Troubleshooting section for additional details.
Table 1 6 — Exhaust fan status binary input IN 12 configuration
IN 12 configurationContact closedContact open
Not usedNormalNormal
Normally closedExhaust fan diagnostic (Note 1)Normal
Normally openNormalExhaust fan diagnostic (Note 1)
Note 1: A Low Exhaust Fan Air Flow diagnostic is generated when the controller turns on the exhaust fan output, but
the exhaust fan status binary input indicates the exhaust fan is not running after a two-minute delay time.
CNT-SVX05A-EN15
Analog inputs
The analog inputs are connected to the Tracer AH.540 termination board on
inputs IN 1 through IN 6. A special connector (J43) on the termination board is
used for the duct static pressure input, analog input J43.
Analog inputs
• IN 1: Space temperature
• IN 2: Local setpoint
• IN 3: Fan mode input
• IN 4: Discharge air temperature
• IN 5: Outdoor air temperature
• IN 6: Mixed air temperature
• Terminal J43 Duct static pressure
A communicated variable input like setpoint, space temperature, or outdoor air
temperature has priority over a locally wired input to the controller. For example,
if the Tracer™ AH.540 controller has a wired outdoor air temperature sensor, and
Trac e r Su m m it
air temperature, the communicated value is used by the Tracer AH.540 controller.
Space temperature
The space temperature analog input IN 1 measures space temperature only. The
space temperature is measured with a 10kΩ thermistor included with Trane zone
sensors. The Tracer AH.540 controller receives the space temperature from either
a wired zone sensor or as a communicated value. A communicated value has
precedence over a locally wired sensor input. Therefore, the communicated
value, when present, is automatically used by the controller.
If the Tracer AH.540 controller is operating in constant volume space
temperature control mode and the space temperature fails or does not receive a
communicated value, the controller generates a Space Temperature Failure
diagnostic.
The space temperature input may also be used to generate timed override On/
Cancel requests to the controller. If a momentary short of the space
temperature signal occurs, the Tracer AH.540 interprets the signal as a timed
override On request.
The Tracer AH.540 uses the timed override On request (while the zone is
unoccupied) as a request to go to the occupied bypass mode (occupied
bypass). The occupied bypass mode lasts for the duration of the occupied
bypass time, typically 120 minutes. The occupied bypass time can be changed
using the Trane Rover
Press the Cancel button on the zone sensor to cancel the override request and
return the controller to unoccupied mode. This creates a momentary fixed
resistance (1.5kΩ), which sends a cancel request to the space temperature
input.
™
or another Comm5 controller sends it a communicated outdoor
™
service tool.
16CNT-SVX05A-EN
Analog inputs
Local setpoint
The local setpoint input is a hardwired setpoint connected on analog input IN 2.
The local setpoint is a resistive input for use with Trane zone sensors. If neither
a hardwired nor communicated setpoint is present, the controller uses the stored
default configured heating and cooling setpoints:
• Occupied setpoints
• Occupied standby setpoints
• Unoccupied setpoints
Once a valid setpoint is established through the hardwired input IN 2 or through
communication, and when neither a local setpoint nor communicated setpoint
is present, the controller generates a setpoint Failure diagnostic.
™
Rover
monitor, configure, and test Tracer
the communication link.
When a setpoint Failure diagnostic occurs, the controller operates using the
default heating and cooling setpoints. These setpoints are factory-configured,
but you can change them using the Rover service tool.
The Tracer AH.540 controller uses the following steps to determine the space
temperature setpoint:
1. Check for a communicated setpoint. If present, validate this setpoint.
2. Check for a hardwired setpoint and validate the setpoint.
3. Use the default setpoints if neither the hardwired setpoint nor the
, Trane's service tool communication software package, allows you to
™
AH.540 unit controllers via a connection to
communicated setpoint is available.
Tracer AH.540
status
StandaloneN/ANot presentConfigured default
StandaloneN/APresent - local zone
CommunicatingCommunicated
CommunicatingCommunicated
Note 1: Communicated inputs to the Tracer AH.540 controller have precedence over locally wired inputs.
Communicated setpoint
input - nviSetpoint (No te 1)
setpoint input
setpoint input
Local, wired setpoint
input - IN 2
sensor thumb wheel
Not presentCommunicated setpoint
Present - local zone
sensor thumb wheel
Result
setpoints are used
Local setpoint input
Communicated setpoint
Fan mode switch
The fan mode analog input IN 3 responds to specific resistances corresponding
to a fan mode switch provided with certain Trane zone sensors. The fan mode
switch on a Trane zone sensor generates the fan mode signal.
The Tracer AH.540 controller detects the unique resistance corresponding to
each position of the fan mode switch. By measuring this resistance, the
controller determines the requested fan mode.
If the Tracer AH.540 controller does not receive a hardwired or communicated
request for fan mode, the unit recognizes the fan input as Auto.
Table 17 — Tracer AH.540 fan modes
Fan modesTr acer AH.540 operation
OffFan off (4870 ohms +/-1%)
AutoIn occupied mode, the fan runs. In unoccupied mode, the fan cycles Off
when no heating or cooling is required. (2320 ohms +/-5%)
CNT-SVX05A-EN17
Analog inputs
Discharge air temperature
The Tracer™ AH.540 controller cannot operate if the controller does not sense a
valid discharge air temperature input. If the sensor returns to a valid input, the
controller automatically allows the unit to resume operation.
The Tracer AH.540 controller uses analog input 4 (IN 4) as the discharge air
temperature input with a 10kΩ thermistor only. This sensor is hardwired and
located downstream from all unit heating/cooling capacity at the unit discharge
area. The discharge air temperature is used as a control input to the controller
which is used for all control modes of operation: constant volume space
temperature control, constant volume discharge air temperature control, and
variable air volume control.
Any time the discharge air temperature signal is not present, the controller
generates a Discharge Temperature Failure diagnostic and performs a unit
shutdown. If the sensor returns to a valid input, the controller automatically
clears the diagnostic and allows the unit to resume operation.
Outdoor air temperature
Analog input IN 5 is used for outdoor air temperature (10kΩ thermistor only).
When a valid outdoor air temperature (either hardwired or communicated) and
an economizer outdoor air damper exist, the controller uses this value to
determine if economizing (free cooling) is feasible and (only if economizing is
enabled) if the controller should enter freeze avoidance when the supply
fan is off.
If the outdoor air temperature is below the economizer enable point (default
60°F, adjustable), then economizing is allowed. When the outdoor air
temperature is not present, then economizing is not allowed. If both the
hardwired and communicated outdoor air temperatures are present, the
controller uses the communicated value for control decisions.
When an outdoor air temperature is established (either hardwired or
communicated), the controller generates an Outdoor Air Temp Failure
diagnostic if the signal is no longer valid, and the unit disallows economizing. If
the sensor returns to a valid input, the controller automatically clears the
diagnostic and allows economizer operation.
Mixed air temperature
The Tracer AH.540 controller uses analog input IN 6 as the mixed air temperature
input with an averaging, 1000Ω (at 0°C, 32°F) RTD sensor only. The controller’s
mixed air temperature input is used for mixed air tempering and outdoor air
economizing operations.
The Tracer AH.540 controller disallows economizing if the controller does not
sense a valid mixed air temperature input. If the sensor returns to a valid input,
the controller automatically checks to see if economizer operation is possible.
If a valid mixed air temperature signal has been established by the RTD sensor,
but then the value is no longer present, the controller generates a Mixed Air Temperature Failure diagnostic and disallows economizer operation. When the
sensor returns to a valid input, the controller automatically clears the diagnostic
and checks to see if economizer operation is possible.
Duct static pressure
The duct static pressure input (terminal J43) interfaces with a specialized
pressure transducer only. When a valid duct static pressure value (either
hardwired or communicated) exists and a variable air volume supply fan is
present, the controller uses this value for duct static pressure control.
18CNT-SVX05A-EN
Analog inputs
When a duct static pressure is established, the controller generates a Duct
Static Pressure diagnostic if the signal is no longer valid, and shuts down the
unit. When the sensor returns to a valid input, the controller automatically
clears the diagnostic and allows the unit to resume operation.
™
The Tracer
cannot operate without a valid duct static pressure input. When the sensor
returns to a valid input, the controller resumes unit operation. The controller is
not required to have a duct static pressure input for constant volume space
temperature or constant volume discharge air temperature control.
On/cancel buttons
Momentarily pressing the On button during unoccupied mode places the
controller in occupied bypass mode for 120 minutes. You can adjust the number
of minutes the Tracer AH.540 is placed in the occupied bypass mode using
Rover
override time expires or until you press the Cancel button.
If Tracer Summit
someone presses the On button on the zone sensor, the controller goes to
occupied bypass and communicates back to Tracer that its effective occupancy
mode is occupied bypass.
If the controller is in the unoccupied mode, regardless of the source (Tracer
Summit or hardwired occupancy binary input), pressing the On button causes
the controller to go into the occupied bypass mode for the duration of the
configured occupied bypass time.
AH.540 controller, when configured for variable air volume control,
™
service tool. The controller remains in occupied bypass mode until the
™
sends an unoccupied mode command to the controller and
CNT-SVX05A-EN19
Zone sensor
The controller accepts the following zone sensor inputs:
• Space temperature measurement (10kΩ thermistor)
• Zone sensor setpoint adjustment (either internal or external on the zone
sensor module)
• Fan mode switch
• Timed override On request
• Timed override Cancel request
• Communication jack
• Service pin message request
Space temperature measurement
Trane zone sensors use a 10kΩ thermistor to measure the space temperature.
Typically, zone sensors are wall-mounted in the room and include a space
temperature thermistor. A valid space temperature input is required for the
controller to operate in constant volume space temperature control.
If both a hardwired and communicated space temperature value exist, the
controller ignores the hardwired space temperature input and uses the
communicated value.
Zone sensor setpoint adjustment
Zone sensors with an internal or external setpoint adjustment (1kΩ) provide
the Tracer
An internal setpoint adjustment is concealed under the zone sensor’s cover.
To access the adjustable setpoint wheel, remove the zone sensor cover. An
external setpoint (when present) is accessible from the zone sensor’s front cover.
There is only one hardwired setpoint input (IN 2) associated with the Tracer
AH.540 controller. When the hardwired setpoint adjustment is used to
determine the setpoints, all unit setpoints are calculated based on the
hardwired setpoint value, the configured/default setpoints, and the active mode
of the controller.
Example: Assume the controller is configured with the following default
setpoints:
™
AH.540 controller with a local setpoint (50° to 85°F, 10° to 29.4°C).
Absolute setpoint Offset = setpoint Input - Mean setpoint
From the default setpoints in this example, the mean of the occupied cooling
and heating setpoints is 72°F [(74+70) / 2]. The absolute setpoint offset is the
difference between the setpoint input and the mean setpoint. For this example,
assume a setpoint input of 73°F, resulting in an absolute setpoint offset of one
degree (73 –72=1).
The hardwired setpoint is used with the controller's occupancy mode
(occupied, occupied standby, or unoccupied), the heating or cooling mode,
the temperature deadband values, and the heating and cooling setpoints
(high and low limits) to determine the controller's active setpoint.
Zone sensor
The controller adds the absolute setpoint offset to occupied and occupied
standby default setpoints to derive the effective setpoints as follows:
When a building automation system or other controller communicates a
setpoint to the controller, the controller ignores the hardwired setpoint input
and uses the communicated value. The exception is in the unoccupied mode,
when the controller always uses the stored default unoccupied setpoints; a
communicated setpoint shift can move the default unoccupied setpoints.
After the controller completes all setpoint calculations based on the requested
setpoint, the occupancy mode, the heating and cooling mode, and other
factors, the calculated setpoint is validated against the following setpoint limits:
• Heating setpoint high limit
• Heating setpoint low limit
• Cooling setpoint high limit
• Cooling setpoint low limit
These setpoint limits only apply to the occupied and occupied standby heating
and cooling setpoints. These setpoint limits do not apply to the unoccupied
heating and cooling setpoints stored in the controller’s configuration.
When the controller is in unoccupied mode, it uses the stored unoccupied
heating and cooling setpoints.
The unit can also be configured to enable or disable the local (hardwired)
setpoint. This parameter provides additional flexibility to allow you to apply
communicated, hardwired, or default setpoints without making physical
changes to the unit.
Similar to hardwired setpoints, the effective setpoint value for a communicated
setpoint is determined based on the stored default setpoints (which determines
the occupied and occupied standby temperature deadbands) and the
controller’s occupancy mode.
AH.540 controller determines the effective setpoint based on the
CNT-SVX05A-EN21
Zone sensor
Fan mode switch
The zone sensor fan mode switch provides the controller with a fan request
signal (Off, Auto). If the fan control request is communicated to the controller,
the controller ignores the hardwired fan mode switch input and uses the
communicated value.
The zone sensor fan mode switch input can be enabled or disabled through
configuration using the Rover
disabled, the controller resorts to the Auto fan mode.
When the fan mode switch is placed in the Off position, the controller does not
control any unit capacity. The unit remains powered and all outputs are driven
Closed or Off.
Upon a loss of signal on the fan speed input, the controller reports a diagnostic
and reverts to using the Auto fan mode of operation.
On/cancel buttons
Some Trane zone sensor modules include timed override On and Cancel buttons.
Use the timed override On and Cancel buttons to place the controller in override
(occupied bypass mode) and to cancel the override request.
The controller always recognizes the timed override On button. If someone
presses the zone sensor's timed override On button, the controller initializes
the bypass timer to 120 minutes (adjustable).
If the controller is unoccupied when someone presses the On button for two
seconds, the controller immediately changes to occupied bypass mode and
remains in the mode until either the timer expires or someone presses the zone
sensor's timed override Cancel button. If the On button is pressed during
occupied bypass mode before the timer expires, the controller re-initializes the
bypass timer to 120 minutes.
If the controller is in any mode other than unoccupied when someone presses
the On button, the controller initializes the bypass time to 120 minutes. As time
expires, the bypass timer continues to decrement. During this time, if the
controller changes from its current mode to unoccupied (perhaps due to a
change based on the system's time of day schedule), the controller switches
to occupied bypass mode for the remainder of the bypass time or until
someone presses the zone sensor's timed override Cancel button.
Zone sensor communication jack
Use the RJ-11 communication jack (present on some zone sensor modules)
as the connection point from Rover service tool to the communication link, when
the communication jack is wired to the communication link at the controller.
By accessing the communication jack via Rover, you gain communication access
to any controller on the link.
Service pin message request
At any time, pressing the zone sensor On button for ten seconds,
then releasing it, causes the controller to transmit a service pin message.
The service pin message can be useful for installing the controller in a
communication network. See Trane Rover service tool literature for
more information.
™
service tool. If the zone sensor switch is
22CNT-SVX05A-EN
Zone sensor
Zone sensor wiring connections
Table 18 — Typical Trane zone sensor wiring connections
with a fan mode switch
TB1Description
1Space temperature
2Common
3setpoint
4Fan mode
5Communications
6Communications
Table 19 — Typical Trane zone sensor wiring connections
without a fan mode switch
TB1Description
1Space temperature
2Common
3setpoint
5Communications
6Communications
CNT-SVX05A-EN23
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.