This installation and operation document includes information about the
™
Trac er
controller works in both the standalone mode and when connected to a Tracer
Summit
• Controller features
• Sequence of operation
• Inputs and outputs required for each feature
The controller is applied to air handling product configurations supporting
analog modulating valves, economizer damper, and face and bypass damper.
The controller also supports a constant volume or variable air volume supply
fan.
The configurable air handling unit controller is also available as the Tracer
AH.541 field-installed air handling unit controller (St. Paul, Minnesota). The
features and functions of the Tracer AH.541 are identical to those of the
Tracer AH.540 described in this manual.
AH.540 configurable air handling unit (AHU) controller. Version 1.0 of the
™
automation system. This document details:
CNT-SVX05A-EN1
Page 8
Supported Products
The configurable air handling unit controller is available installed, pre-wired,
and tested with the following Trane air handling equipment:
™
Packaged Climate Changer
LPC AHorizontal/Front Top
LPC BHorizontal/Top Front
LPC CVertical/Front Top
LPC DVertical/Top Front
LPC EVertical/Top Back
LPC FVertical/Back Top
Manufacturing Location: Macon, Georgia
Modular Climate Changer
The Tracer™ AH.540 controller availability on the Modular Climate Changer air
handler is limited to the features and functions provided by the controller.
See the Features section for more information.
Manufacturing Location: Lexington, Kentucky
T-Series Climate Changer
The Tracer AH.540 controller availability on the T-Series Climate Changer air
handlers is limited to the features and functions provided by the controller.
See the Features section for more information.
Manufacturing Location: Lexington, Kentucky
Air Handling Units
™
Air Handling Units
™
Air Handling Units
2CNT-SVX05A-EN
Page 9
Features
Ta b l e 1 — Tra c e r™ AH.540 features and contro l modes
Constant volume space
Fan controlOn/OffOn/OffVariable
Duct static pressure con-
trol
Hydronic coolingXXX
Hydronic heatingXXX
Steam heatXXX
Face and bypass heating XXX
Ventilation controlXXX
Economizer damperXXX
Warm-up functionsXXX
Mixed air temperature
control
Exhaust fan (on/off)XXX
temperature control
XXX
Constant volume
discharge air control
Variable air volume
control
X
Fan control options are:
• Constant volume with space temperature control
• Constant volume with discharge air temperature control
• Variable air volume with discharge air temperature control
Features available for any of the above fan control options include:
• Hydronic cooling valve
• Hydronic heating valve
• Steam heat valve
• Face and bypass damper (heating only)
• Economizer cooling
CNT-SVX05A-EN3
Page 10
Termination board
Analog Inputs
Power
Analog Outputs
Comm 5 Communication
Te rm ina ls
Binary Outputs
Duct Static Pressure Input
Binary Inputs
4CNT-SVX05A-EN
Page 11
Controller board
ID Label
Supply Fan
Status LED
Exhaust Fan
Status LED
RED Service LED
Service Push Button
Yellow Comm LED
Test Push Button
Green Status LED
CNT-SVX05A-EN5
Page 12
Physical specifications
Board dimensions
Termi n a t io n b oar d
Height: 3.5 inches (88.9 mm)
Width:8.0 inches (203.2 mm)
Depth:1.0 inch (25.4 mm)
Controller board
Height: 4.3 inches (109.2 mm)
Width:8.0 inches (203.2 mm)
Depth:2.0 inches (50.8 mm)
Operating environment
-40° to 70°C (-40° to 158°F)
5% to 95% relative humidity non-condensing
Storage environment
-40° to 85°C (-40° to 185°F)
5% to 95% relative humidity non-condensing
Agency Conformance
(See Appendix for use limitations)
UL
UL unlisted component
UL 873 Temperature Indicating and Regulating Equipment
CUL C22.2 No. 24-93 Temperature Indicating and Regulating Equipment
CE
Conducted EmissionsEN55022 Class A
EN55022 Class B
EN 61000-3-2
EN 61000-3-3
Radiated EmissionsEN55022 Class A
ImmunityEN 50082-2 Industrial
FCC
CFR 47, Part 15, Subpart A, Class A
CFR 47, Part 15, Subpart A, Class B
Power requirements
Low voltage class 2, non-safety device
18 to 32VAC (24VAC nominal)
Maximum VA = 13VA (control board)
50 or 60 HZ
6CNT-SVX05A-EN
Page 13
Physical specifications
Binary outputs
The binary outputs are normally-open, form A relays. The relays act as a switch,
either making or breaking the circuit between the load (device) and 24VAC. When
binary output 1 is energized, 24VAC is supplied to terminal TB21-1 (OUT),
energizing the supply fan start/stop relay.
Example:
24VAC
GND
Each binary output has a green status LED on the Tracer
The LED is off when the relay contacts are open. The LED is on when the relay
contacts are closed.
When the binary output relay is off (contact is open), a multimeter should
measure 0VAC across the output terminals. When the binary output relay is on
(contacts are closed), a multimeter should measure 24VAC across the output
terminals.
Termination board
TB21-1 (OUT)
TB21-2 (GND)
BO 1
Wiring external to the
Termination board
Supply Fan (start/stop)
Relay
AH.540 control board.
Table 2 — Binary outputs
DescriptionFunctionFactory
BO 1Supply fan
BO 2Exhaust fan
BO 3Not used
BO 4Not used
BO 5Not used
BO 6Not used
Note 1: Terminals BO 3, BO 4, BO 5, and BO 6 do not serve any function of the Tracer AH.540 controller and are not used.
start/stop
start/stop
(Note 1)
(Note 1)
(Note 1)
(Note 1)
Ter min al s
J21TB21-1
J22TB22-1
J23TB23-1
J24TB24-1
J25TB25-1
J26TB26-1
Field
Ter min al s
TB21-2
TB22-2
TB23-2
TB24-2
TB25-2
TB26-2
LabelTerminal
OUT
GND
OUT
GND
OUT
GND
OUT
GND
OUT
GND
OUT
GND
Function
24VAC
Ground
24VAC
Ground
Not usedNot used
Not usedNot used
Not usedNot used
Not usedNot used
Maximum
Output Rating
24VA
24VA
CNT-SVX05A-EN7
Page 14
Physical specifications
Analog outputs
The analog outputs are 0 to 10VDC.
Table 3 — Analog outputs
DescriptionFunctionFactory
AO 1Supply fan
AO 2Cool outputJ12TB12-1
AO 3Heat outputJ13TB13-1
AO 4Face and bypass
AO 5Outdoor air
AO 6 Not used—————
speed
damper
damper
terminals
J11TB11-1
J14TB14-1
J15TB15-1
Analog inputs
Table 4 — Analog inputs
Descriptio n FunctionSensor type
IN 1Space temp 10KΩ
IN 2Space setpoint 1K
IN 3Fan mode switch
IN 4Discharge air
IN 5Outdoor air temp 10K
IN 6Mixed air tempRTD
J43Duct static pres-
Note 1: Sensor type: Switched resistance fan auto = 2320Ω +/-5%, fan off = 4870Ω +/-5%.
Note 2: Sen sor type RTD averaging sensor, 1000Ω at 0°C, platinum 385 curve.
Note 3: See Appendix for analog input sensor curves, Table 65 on page 76 and Table 66 on page 77.
(Note 1)
temp
sure
(Note 3)
thermistor
potentiometer
Switched
resistance
10K
thermistor
thermistor
(Note 2)
Specialized
pressure
transducer
Field
terminals
TB11-2
TB12-2
TB13-2
TB14-2
TB15-2
Ω
Ω
Ω
LabelTerminal
OUT
GND
OUT
GND
OUT
GND
OUT
GND
OUT
GND
Factory
terminals
J31TB31-1
J32TB32-1
J33TB33-1
J34TB34-1
J35TB35-1
J36TB36-1
J43-1 GND
J43-2 Signal
J43-3 5VDC
Field
terminals
TB31-2INGND
TB32-2INGND
TB33-2INGND
TB34-2INGND
TB35-2INGND
TB36-2INGND
NADuct
function
0 to 10VDC
Ground
0 to 10VDC
Ground
0 to 10VDC
Ground
0 to 10VDC
Ground
0 to 10VDC
Ground
LabelRange
static
Maximum
output rating
20mA
20mA
20mA
20mA
20mA
-15° to 50°C
° to 122°F
5
10° to 29.4°C
50
° to 85°F
Off (4870
Auto (2320
-40° to 100°C
–40
-40° to 100°C
-40
-40
-40° to 212°F
0 to 1250 Pascals
0 to 5.02 in. water
Ω +/-5%)
° to 212°F
° to 212°F
° to 100°C
Ω +/-5%)
8CNT-SVX05A-EN
Page 15
Physical specifications
Binary inputs
Each binary input associates an input signal of 0VDC with closed contacts and
24VDC with open contacts. If the wired binary device has closed contacts, a
multimeter should measure less than 1.0VDC across the binary input terminals.
If the binary input has opened, a multimeter should measure greater than 20VDC
across the binary input terminals.
Table 5 — Binary inputs
Descriptio nFunctionFactory
IN 7Low temp detectJ37TB37-1
IN 8Run/stopJ38TB38-1
IN 9Occupancy or
IN 10Supply fan statusJ40TB40-1
IN 11Filter statusJ41TB41-1
IN 12Exhaust fan status J42TB42-1
generic
terminals
J39TB39-1
Field
terminals
TB37-2
TB38-2
TB39-2
TB40-2
TB41-2
TB42-2
LabelTerminal function
IN
GND
IN
GND
IN
GND
IN
GND
IN
GND
IN
GND
24VDC
Ground
24VDC
Ground
24VDC
Ground
24VDC
Ground
24VDC
Ground
24VDC
Ground
CNT-SVX05A-EN9
Page 16
Analog and binary outputs
The Tracer AH.540 is configured at the factory per unit configuration and order
information. The controller is applied to air handling product configurations
supporting analog modulating valves, economizer damper, and face and bypass
damper. The controller supports a constant volume or variable air volume supply
fan.
General description
The configuration of analog and binary outputs is largely based on the unit
configuration. Each of the five analog outputs and two binary outputs is assigned
a specific function:
Table 6 — Analog outputs
AO 1Supply fan speed (VAV units only)
AO 2Cooling valve output (water)
AO 3Heating valve output (water or steam)
AO 4Face and bypass damper output
AO 5Outdoor air damper output
AO 6Not used
Table 7 — Binary outputs
BO 1Supply fan start/stop output
BO 2Exhaust fan start/stop output
Output overrides
The Tracer AH.540 controller includes a manual output test function.
This function can be initiated by depressing the Test push button on the
controller. Use this feature to manually exercise the outputs in a defined
sequence. For more information about the manual output test function,
see the Troubleshooting section.
Figure 1
The Tracer AH.540 controller includes a water balancing function, which can
be controlled by Rover™ or another communicating device to selectively drive
open or closed the water valve outputs. For more information about the water
balancing function see the Sequence of operation section.
10CNT-SVX05A-EN
Page 17
Binary inputs
The default configuration for each binary input (including normally open/closed)
of the Tracer™ AH.540 is set at the factory. For field-installed AH.541 controllers,
the configuration of the binary inputs must be set with Trane Rover
software.
Configure any binary input not in use (an input to which no device is physically
connected) as Not Used.
The Tracer AH.540 controller has six available binary inputs. The binary inputs
are connected to the Tracer AH.540 terminal board on inputs IN 7 through IN 12.
Normally these inputs are factory-configured for the following functions.
Binary inputs
• IN 7: Low temperature detection (freezestat)
• IN 8: Run/stop
• IN 9: Occupancy or generic
• IN 10: Supply fan status
• IN 11: Filter status
• IN 12: Exhaust fan status
Configure IN 9 either as Occupancy or as a Generic binary input. When
configured as a generic binary input, IN 9 does not affect controller operation.
Table 8 — Table Binary input controller operation
Binary
input
IN 7Low temp detect
IN 8Run/stop
IN 9OccupancyNormally open UnoccupiedOccupied
IN 10Supply fan status
IN 11Filter statusNormally open DirtyClean
IN 12Exhaust fan statusNormally closed Exhaust fan
Note 1: During low temp detect, run/stop, and supply fan status diagnostics, the controller disables all normal unit
Note 2: The table below shows the controller’s response to low temp detect, run/stop, supply fan status, and exhaust
DescriptionConfigurationContact closedContact open
(Note 1)
(Note 1)
(Note 1)
operation of the fans, valves, and dampers.
fan status la tching diag nostics.
Normally closed NormalLatching diagnostic
Normally open Latching diagnostic
Normally open Normal Latching diagnostic
(Note 2)
diagnostic (Note 2)
(Note 2)
Normal
(Note 2)
Normal
™
service
CNT-SVX05A-EN11
Table 9 — Control response to binary input latching diagnostics
Binary
input
IN 7Low temp detectOffOpenFaceOpen
IN 8Run/stopOffClosedBypassClosedClosedOff
IN 10Supply fan status OffClosedBypassClosedClosedOff
IN 12Exhaust fan status Normal
Note 1: When steam is the source of heat, the heat output is cycled open and closed when the controller is shut down
Latching
diagnostic
on a Low Temp Detect latching diagnostic. See Steam valve cycling in the Sequence of operation section for further
details.
Supply
fan
Operation
Cool
output
Normal
Operation
Face and
bypass
damper
Normal
Operation
Heat
output
(Note 1)
Normal
Operation
Outdoor air
damper
ClosedOff
Normal
Operation
Exhaust
fan
Off
Page 18
Binary inputs
Low temperature detection
The low temperature detection device can be automatically or manually reset.
However, you must manually reset the Tracer
Temperature Detect diagnostic to clear the diagnostic and restart the unit.
Low temperature detection protects the coils of hydronic units. A low
temperature detection device (freezestat) connected to binary input IN 7 detects
the low temperature. The Tracer AH.540 controller can protect the coil using
one binary input. When the controller detects the low temperature detection
signal, the controller generates a diagnostic which disables the fan, opens all
unit water or steam valves, and closes the outdoor air damper (when present).
Note: Even if the low temperature detection device automatically resets when
the coil/heat exchanger temperature returns to a normal value, you must clear
the Low Temperature Detect diagnostic from the controller to restart the air
handling unit. See the Resetting Diagnostics section for instructions to clear
controller diagnostics.
Table 10 — Low temperature detection controller operation
DiagnosticFan
Low temperature
detection
Note 1: When steam is the source of heat, the heat valve is cycled open and closed when the controller is shut down on
a Low Temp Det ect latching diagnostic. Cycling the steam valve helps prevent excessive cabinet temperatures. See
Steam valve cycling in the Sequence of operation section for further det ails.
operation
OffOpenOpen
Cool
output
Heat output Face and
(Note 1)
™
AH.540 controller Low
bypass
FaceClosed
Outdoor air damper
operation
Run/stop
This hardwired binary input IN 8 can be used for a variety of functions to shut
down the unit. The Tracer AH.540 controller systematically shuts down unit
operation and reports a Unit Shutdown diagnostic upon detecting a stop input.
For example, a condensate overflow sensor or a smoke detector can be
connected to the run/stop input to shut down unit operation.
The run/stop input creates a latching Unit Shutdown diagnostic. The run/stop
input must first be returned to the run condition and the diagnostic must be
reset in the controller before the unit is allowed to run.
Table 11 — Run/stop IN 8 binary input configuration
ConfigurationContact c losedContact open
Not usedRunRun
Normally closedRunStop
Normally openStopRun
12CNT-SVX05A-EN
Page 19
Binary inputs
Occupancy
The Tracer AH.540 controller uses the occupancy binary input IN 9 for two
occupancy-related functions.
Standalone
For standalone controllers (any unit not receiving a communicated occupancy
request, typically from a building automation system), the occupancy binary
input determines the unit's occupancy based on the hardwired signal. Normally,
the signal is hardwired to a binary switch or clock.
When a hardwired occupancy signal on binary input IN 9 is open, the unit
switches to occupied mode if the occupancy input is configured as normally
open. When a hardwired occupancy signal is closed, the controller switches to
unoccupied mode (only if the occupied bypass timer = 0). See Occupied bypass
in the Sequence of operation section.
Communicated request
For controllers that receive a communicated occupancy request (typically from
a building automation system), the hardwired occupancy binary input, along
with the communicated occupancy request, place the controller in either
occupied, unoccupied, or occupied standby mode.
In occupied mode, the controller operates according to the occupied setpoints.
In occupied standby mode, the unit controller operates according to the
occupied standby setpoints. When the controller receives a communicated
unoccupied request, the controller operates according to the unoccupied
setpoints regardless of the state of the hardwired occupancy input (only if the
occupied bypass timer = 0).
When neither an occupancy device is wired to binary input IN 9 nor a
communicated input is used to select the occupancy mode, the controller
defaults to occupied mode because the occupancy binary input IN 9 typically
is configured as normally open and no occupancy device is connected.
CNT-SVX05A-EN13
Table 1 2 — Normally open hardwired input configuration
Binary input IN 9 can be configured as a generic binary input for a variety of
applications with Trane Tracer Summit
controller operation. Binary input IN 9 can be configured as Occupancy or
Generic. A generic binary input can be monitored only from Tracer Summit.
Supply fan status
The fan status binary input IN 10 indicates the presence of air flow through the
supply fan of an air handling unit. For Tracer
pressure switch detects fan status, with the high side of the differential being
supplied at the unit outlet and the low side supplied inside the unit. During fan
operation, differential pressure closes the normally open switch and confirms
that the fan is operating properly.
A Low Supply Fan Air Flow diagnostic is detected during the following two
conditions:
• The controller is commanding the fan On and the fan status switch is not in
the closed position
• The fan status switch does not close the binary input within the configurable
fan On delay time limit of the controller commanding the fan On
This is a latching diagnostic and discontinues unit operation until the diagnostic
is cleared from the controller. Additional details can be found in the
Troubleshooting section.
™
only. The binary input does not affect
™
AH.540 applications, a differential
Table 1 4 — Fan status binary input IN 10 configuration
Note 1: A Low Supply Fan Air Flow diagnostic is generated when the controller turns on the supply fan output, but the
supply fan status binary input indicates the supply fan is not running after the configurable fan delay time.
Filter status
The filter status switch connected to binary input IN 11 detects a dirty air filter
and indicates a need for maintenance. For Tracer AH.540 applications, a
differential pressure switch detects filter status, with the high side of the
differential being supplied at the filter inlet and the low side supplied at the filter
outlet. During fan operation, filter differential pressure increases as the filter
becomes increasingly dirty.
A normally open filter status switch closes when the differential pressure
reaches a set threshold. This is a non-latching, informational diagnostic and the
controller will continue normal unit operation.
Table 1 5 — Filter status configuration
IN 11 configurationContact closedContact open
Not usedCleanClean
Normally closedCleanDirty
Normally openDirtyClean
14CNT-SVX05A-EN
Page 21
Binary inputs
Exhaust fan status
The exhaust fan status binary input IN 12 indicates the presence of air flow
through an exhaust fan associated with the controlled air handling unit. For
Trac er ™ AH.540 applications, a differential pressure switch detects exhaust fan
status, with the high side of the differential being supplied at the outlet. During
exhaust fan operation, differential pressure closes the normally open switch and
confirms that the fan is operating properly.
A Low Exhaust Fan Air Flow diagnostic is detected during the following two
conditions:
• The controller is commanding the exhaust fan On and the status switch is not
in the closed position
• The fan status switch does not close the binary input within two minutes of the
controller commanding the exhaust fan On
This is a latching diagnostic but does not affect controller operation of the air
handling unit. Refer to the Troubleshooting section for additional details.
Table 1 6 — Exhaust fan status binary input IN 12 configuration
IN 12 configurationContact closedContact open
Not usedNormalNormal
Normally closedExhaust fan diagnostic (Note 1)Normal
Normally openNormalExhaust fan diagnostic (Note 1)
Note 1: A Low Exhaust Fan Air Flow diagnostic is generated when the controller turns on the exhaust fan output, but
the exhaust fan status binary input indicates the exhaust fan is not running after a two-minute delay time.
CNT-SVX05A-EN15
Page 22
Analog inputs
The analog inputs are connected to the Tracer AH.540 termination board on
inputs IN 1 through IN 6. A special connector (J43) on the termination board is
used for the duct static pressure input, analog input J43.
Analog inputs
• IN 1: Space temperature
• IN 2: Local setpoint
• IN 3: Fan mode input
• IN 4: Discharge air temperature
• IN 5: Outdoor air temperature
• IN 6: Mixed air temperature
• Terminal J43 Duct static pressure
A communicated variable input like setpoint, space temperature, or outdoor air
temperature has priority over a locally wired input to the controller. For example,
if the Tracer™ AH.540 controller has a wired outdoor air temperature sensor, and
Trac e r Su m m it
air temperature, the communicated value is used by the Tracer AH.540 controller.
Space temperature
The space temperature analog input IN 1 measures space temperature only. The
space temperature is measured with a 10kΩ thermistor included with Trane zone
sensors. The Tracer AH.540 controller receives the space temperature from either
a wired zone sensor or as a communicated value. A communicated value has
precedence over a locally wired sensor input. Therefore, the communicated
value, when present, is automatically used by the controller.
If the Tracer AH.540 controller is operating in constant volume space
temperature control mode and the space temperature fails or does not receive a
communicated value, the controller generates a Space Temperature Failure
diagnostic.
The space temperature input may also be used to generate timed override On/
Cancel requests to the controller. If a momentary short of the space
temperature signal occurs, the Tracer AH.540 interprets the signal as a timed
override On request.
The Tracer AH.540 uses the timed override On request (while the zone is
unoccupied) as a request to go to the occupied bypass mode (occupied
bypass). The occupied bypass mode lasts for the duration of the occupied
bypass time, typically 120 minutes. The occupied bypass time can be changed
using the Trane Rover
Press the Cancel button on the zone sensor to cancel the override request and
return the controller to unoccupied mode. This creates a momentary fixed
resistance (1.5kΩ), which sends a cancel request to the space temperature
input.
™
or another Comm5 controller sends it a communicated outdoor
™
service tool.
16CNT-SVX05A-EN
Page 23
Analog inputs
Local setpoint
The local setpoint input is a hardwired setpoint connected on analog input IN 2.
The local setpoint is a resistive input for use with Trane zone sensors. If neither
a hardwired nor communicated setpoint is present, the controller uses the stored
default configured heating and cooling setpoints:
• Occupied setpoints
• Occupied standby setpoints
• Unoccupied setpoints
Once a valid setpoint is established through the hardwired input IN 2 or through
communication, and when neither a local setpoint nor communicated setpoint
is present, the controller generates a setpoint Failure diagnostic.
™
Rover
monitor, configure, and test Tracer
the communication link.
When a setpoint Failure diagnostic occurs, the controller operates using the
default heating and cooling setpoints. These setpoints are factory-configured,
but you can change them using the Rover service tool.
The Tracer AH.540 controller uses the following steps to determine the space
temperature setpoint:
1. Check for a communicated setpoint. If present, validate this setpoint.
2. Check for a hardwired setpoint and validate the setpoint.
3. Use the default setpoints if neither the hardwired setpoint nor the
, Trane's service tool communication software package, allows you to
™
AH.540 unit controllers via a connection to
communicated setpoint is available.
Tracer AH.540
status
StandaloneN/ANot presentConfigured default
StandaloneN/APresent - local zone
CommunicatingCommunicated
CommunicatingCommunicated
Note 1: Communicated inputs to the Tracer AH.540 controller have precedence over locally wired inputs.
Communicated setpoint
input - nviSetpoint (No te 1)
setpoint input
setpoint input
Local, wired setpoint
input - IN 2
sensor thumb wheel
Not presentCommunicated setpoint
Present - local zone
sensor thumb wheel
Result
setpoints are used
Local setpoint input
Communicated setpoint
Fan mode switch
The fan mode analog input IN 3 responds to specific resistances corresponding
to a fan mode switch provided with certain Trane zone sensors. The fan mode
switch on a Trane zone sensor generates the fan mode signal.
The Tracer AH.540 controller detects the unique resistance corresponding to
each position of the fan mode switch. By measuring this resistance, the
controller determines the requested fan mode.
If the Tracer AH.540 controller does not receive a hardwired or communicated
request for fan mode, the unit recognizes the fan input as Auto.
Table 17 — Tracer AH.540 fan modes
Fan modesTr acer AH.540 operation
OffFan off (4870 ohms +/-1%)
AutoIn occupied mode, the fan runs. In unoccupied mode, the fan cycles Off
when no heating or cooling is required. (2320 ohms +/-5%)
CNT-SVX05A-EN17
Page 24
Analog inputs
Discharge air temperature
The Tracer™ AH.540 controller cannot operate if the controller does not sense a
valid discharge air temperature input. If the sensor returns to a valid input, the
controller automatically allows the unit to resume operation.
The Tracer AH.540 controller uses analog input 4 (IN 4) as the discharge air
temperature input with a 10kΩ thermistor only. This sensor is hardwired and
located downstream from all unit heating/cooling capacity at the unit discharge
area. The discharge air temperature is used as a control input to the controller
which is used for all control modes of operation: constant volume space
temperature control, constant volume discharge air temperature control, and
variable air volume control.
Any time the discharge air temperature signal is not present, the controller
generates a Discharge Temperature Failure diagnostic and performs a unit
shutdown. If the sensor returns to a valid input, the controller automatically
clears the diagnostic and allows the unit to resume operation.
Outdoor air temperature
Analog input IN 5 is used for outdoor air temperature (10kΩ thermistor only).
When a valid outdoor air temperature (either hardwired or communicated) and
an economizer outdoor air damper exist, the controller uses this value to
determine if economizing (free cooling) is feasible and (only if economizing is
enabled) if the controller should enter freeze avoidance when the supply
fan is off.
If the outdoor air temperature is below the economizer enable point (default
60°F, adjustable), then economizing is allowed. When the outdoor air
temperature is not present, then economizing is not allowed. If both the
hardwired and communicated outdoor air temperatures are present, the
controller uses the communicated value for control decisions.
When an outdoor air temperature is established (either hardwired or
communicated), the controller generates an Outdoor Air Temp Failure
diagnostic if the signal is no longer valid, and the unit disallows economizing. If
the sensor returns to a valid input, the controller automatically clears the
diagnostic and allows economizer operation.
Mixed air temperature
The Tracer AH.540 controller uses analog input IN 6 as the mixed air temperature
input with an averaging, 1000Ω (at 0°C, 32°F) RTD sensor only. The controller’s
mixed air temperature input is used for mixed air tempering and outdoor air
economizing operations.
The Tracer AH.540 controller disallows economizing if the controller does not
sense a valid mixed air temperature input. If the sensor returns to a valid input,
the controller automatically checks to see if economizer operation is possible.
If a valid mixed air temperature signal has been established by the RTD sensor,
but then the value is no longer present, the controller generates a Mixed Air Temperature Failure diagnostic and disallows economizer operation. When the
sensor returns to a valid input, the controller automatically clears the diagnostic
and checks to see if economizer operation is possible.
Duct static pressure
The duct static pressure input (terminal J43) interfaces with a specialized
pressure transducer only. When a valid duct static pressure value (either
hardwired or communicated) exists and a variable air volume supply fan is
present, the controller uses this value for duct static pressure control.
18CNT-SVX05A-EN
Page 25
Analog inputs
When a duct static pressure is established, the controller generates a Duct
Static Pressure diagnostic if the signal is no longer valid, and shuts down the
unit. When the sensor returns to a valid input, the controller automatically
clears the diagnostic and allows the unit to resume operation.
™
The Tracer
cannot operate without a valid duct static pressure input. When the sensor
returns to a valid input, the controller resumes unit operation. The controller is
not required to have a duct static pressure input for constant volume space
temperature or constant volume discharge air temperature control.
On/cancel buttons
Momentarily pressing the On button during unoccupied mode places the
controller in occupied bypass mode for 120 minutes. You can adjust the number
of minutes the Tracer AH.540 is placed in the occupied bypass mode using
Rover
override time expires or until you press the Cancel button.
If Tracer Summit
someone presses the On button on the zone sensor, the controller goes to
occupied bypass and communicates back to Tracer that its effective occupancy
mode is occupied bypass.
If the controller is in the unoccupied mode, regardless of the source (Tracer
Summit or hardwired occupancy binary input), pressing the On button causes
the controller to go into the occupied bypass mode for the duration of the
configured occupied bypass time.
AH.540 controller, when configured for variable air volume control,
™
service tool. The controller remains in occupied bypass mode until the
™
sends an unoccupied mode command to the controller and
CNT-SVX05A-EN19
Page 26
Zone sensor
The controller accepts the following zone sensor inputs:
• Space temperature measurement (10kΩ thermistor)
• Zone sensor setpoint adjustment (either internal or external on the zone
sensor module)
• Fan mode switch
• Timed override On request
• Timed override Cancel request
• Communication jack
• Service pin message request
Space temperature measurement
Trane zone sensors use a 10kΩ thermistor to measure the space temperature.
Typically, zone sensors are wall-mounted in the room and include a space
temperature thermistor. A valid space temperature input is required for the
controller to operate in constant volume space temperature control.
If both a hardwired and communicated space temperature value exist, the
controller ignores the hardwired space temperature input and uses the
communicated value.
Zone sensor setpoint adjustment
Zone sensors with an internal or external setpoint adjustment (1kΩ) provide
the Tracer
An internal setpoint adjustment is concealed under the zone sensor’s cover.
To access the adjustable setpoint wheel, remove the zone sensor cover. An
external setpoint (when present) is accessible from the zone sensor’s front cover.
There is only one hardwired setpoint input (IN 2) associated with the Tracer
AH.540 controller. When the hardwired setpoint adjustment is used to
determine the setpoints, all unit setpoints are calculated based on the
hardwired setpoint value, the configured/default setpoints, and the active mode
of the controller.
Example: Assume the controller is configured with the following default
setpoints:
™
AH.540 controller with a local setpoint (50° to 85°F, 10° to 29.4°C).
Absolute setpoint Offset = setpoint Input - Mean setpoint
From the default setpoints in this example, the mean of the occupied cooling
and heating setpoints is 72°F [(74+70) / 2]. The absolute setpoint offset is the
difference between the setpoint input and the mean setpoint. For this example,
assume a setpoint input of 73°F, resulting in an absolute setpoint offset of one
degree (73 –72=1).
The hardwired setpoint is used with the controller's occupancy mode
(occupied, occupied standby, or unoccupied), the heating or cooling mode,
the temperature deadband values, and the heating and cooling setpoints
(high and low limits) to determine the controller's active setpoint.
Page 27
Zone sensor
The controller adds the absolute setpoint offset to occupied and occupied
standby default setpoints to derive the effective setpoints as follows:
When a building automation system or other controller communicates a
setpoint to the controller, the controller ignores the hardwired setpoint input
and uses the communicated value. The exception is in the unoccupied mode,
when the controller always uses the stored default unoccupied setpoints; a
communicated setpoint shift can move the default unoccupied setpoints.
After the controller completes all setpoint calculations based on the requested
setpoint, the occupancy mode, the heating and cooling mode, and other
factors, the calculated setpoint is validated against the following setpoint limits:
• Heating setpoint high limit
• Heating setpoint low limit
• Cooling setpoint high limit
• Cooling setpoint low limit
These setpoint limits only apply to the occupied and occupied standby heating
and cooling setpoints. These setpoint limits do not apply to the unoccupied
heating and cooling setpoints stored in the controller’s configuration.
When the controller is in unoccupied mode, it uses the stored unoccupied
heating and cooling setpoints.
The unit can also be configured to enable or disable the local (hardwired)
setpoint. This parameter provides additional flexibility to allow you to apply
communicated, hardwired, or default setpoints without making physical
changes to the unit.
Similar to hardwired setpoints, the effective setpoint value for a communicated
setpoint is determined based on the stored default setpoints (which determines
the occupied and occupied standby temperature deadbands) and the
controller’s occupancy mode.
AH.540 controller determines the effective setpoint based on the
CNT-SVX05A-EN21
Page 28
Zone sensor
Fan mode switch
The zone sensor fan mode switch provides the controller with a fan request
signal (Off, Auto). If the fan control request is communicated to the controller,
the controller ignores the hardwired fan mode switch input and uses the
communicated value.
The zone sensor fan mode switch input can be enabled or disabled through
configuration using the Rover
disabled, the controller resorts to the Auto fan mode.
When the fan mode switch is placed in the Off position, the controller does not
control any unit capacity. The unit remains powered and all outputs are driven
Closed or Off.
Upon a loss of signal on the fan speed input, the controller reports a diagnostic
and reverts to using the Auto fan mode of operation.
On/cancel buttons
Some Trane zone sensor modules include timed override On and Cancel buttons.
Use the timed override On and Cancel buttons to place the controller in override
(occupied bypass mode) and to cancel the override request.
The controller always recognizes the timed override On button. If someone
presses the zone sensor's timed override On button, the controller initializes
the bypass timer to 120 minutes (adjustable).
If the controller is unoccupied when someone presses the On button for two
seconds, the controller immediately changes to occupied bypass mode and
remains in the mode until either the timer expires or someone presses the zone
sensor's timed override Cancel button. If the On button is pressed during
occupied bypass mode before the timer expires, the controller re-initializes the
bypass timer to 120 minutes.
If the controller is in any mode other than unoccupied when someone presses
the On button, the controller initializes the bypass time to 120 minutes. As time
expires, the bypass timer continues to decrement. During this time, if the
controller changes from its current mode to unoccupied (perhaps due to a
change based on the system's time of day schedule), the controller switches
to occupied bypass mode for the remainder of the bypass time or until
someone presses the zone sensor's timed override Cancel button.
Zone sensor communication jack
Use the RJ-11 communication jack (present on some zone sensor modules)
as the connection point from Rover service tool to the communication link, when
the communication jack is wired to the communication link at the controller.
By accessing the communication jack via Rover, you gain communication access
to any controller on the link.
Service pin message request
At any time, pressing the zone sensor On button for ten seconds,
then releasing it, causes the controller to transmit a service pin message.
The service pin message can be useful for installing the controller in a
communication network. See Trane Rover service tool literature for
more information.
™
service tool. If the zone sensor switch is
22CNT-SVX05A-EN
Page 29
Zone sensor
Zone sensor wiring connections
Table 18 — Typical Trane zone sensor wiring connections
with a fan mode switch
TB1Description
1Space temperature
2Common
3setpoint
4Fan mode
5Communications
6Communications
Table 19 — Typical Trane zone sensor wiring connections
without a fan mode switch
TB1Description
1Space temperature
2Common
3setpoint
5Communications
6Communications
CNT-SVX05A-EN23
Page 30
Communications
The Tracer™ AH.540 controller communicates via Trane's Comm5 protocol.
Typically, a communication link is applied between unit controllers and a
building automation system. Communication also is possible via Rover service
tool. Peer-to-peer communication across controllers is possible even when a
building automation system is not present.
You do not need to observe polarity for Comm5 communication links.
The controller provides six terminals for the Comm5 communication link
connections, as follows:
• Two terminals for communication to the board
• Two terminals for communication from the board to the next unit (daisy chain)
• Two terminals for a connection from the zone sensor back to the controller
Figure 2 — Communication wiring
24CNT-SVX05A-EN
The Comm5 communications protocol allows peer-to-peer communications
between controllers, which allows controllers to share information or data.
A communicated variable input such as setpoint, space temperature, or outdoor
air temperature has priority over a locally wired input to the controller.
For example: If the Tracer AH.540 controller has a wired outdoor air
temperature sensor and Tracer Summit or another Comm5 controller sends it a
communicated outdoor air temperature, the communicated value is used by
the Tracer AH.540 controller. If a communicated input value is lost, the Tracer
AH.540 controller reverts to using the locally wired sensor input.
Device addressing
Comm5 devices are given a unique address by the manufacturer. This address
is called a Neuron ID. Each Tracer AH.540 controller can be identified by its
unique Neuron ID, which is printed on a label on the controller’s logic board. The
Neuron ID is also displayed when communication is established using Tracer
Summit or Rover service tool. The Neuron ID format is 00-01-64-1C-2B-00.
Page 31
Communications
Wire characteristics
UCM communication-link wiring must be low capacitance, 18-gauge, shielded,
twisted pair with stranded, tinned-copper conductors. For daisy chain
configurations, limit the wire run length to 5,000 ft (1524 m). Trunk and branch
configurations are significantly shorter (see Figure 3). Comm5 wire length
limitations can be extended through the use of a link repeater.
Wire capacitance (measured in picofarads/foot [pF/ft] or picofarads/meter
[pF/m]) between conductors must be 23+/-2 pF/ft (72+/-6 pF/m).
Link configuration and termination
Communication-link wiring must use one of the following configurations:
• Daisy chain configuration (preferred), shown in Figure 3
• Trunk and branch configuration, shown in Figure 4
• Limit total wire length to 5,000 ft (1,524 m). (Comm5 wire length limitations
can be extended through the use of a link repeater)
• See the following section on Termination resistance placement for
Comm5 links
Page 32
Communications
Figure 4 — Trunk and branch configuration for communication link wiring
• Total wire length for all branches is limited to 1,600 ft (500 m). (Comm5 wire
length limitations can be extended through the use of a link repeater)
• The maximum number of branches is ten
• See the following section on Termination resistance placement for Comm5
links
Termination resistance placement for Comm5 links
To correctly install a Comm5 link, termination resistors are required. For daisy
chain configurations, the termination resistance (measured in ohms) must be
100 ohms at each end. For trunk and branch configurations, the termination
resistance must be 50 ohms (use two termination resistors in parallel).
For correct termination placement, follow the guidelines below:
• Terminate the daisy chain configuration with a resistor at the extreme end of
each wire
• Terminate a trunk and branch configuration with a resistor or resistors placed
at one point on the link. The termination resistance for trunk and branch
configuration can be achieved by using two terminating resistors in parallel.
While it is not necessary that the termination resistance be placed at the
controller, it may be the most convenient
• When terminating a trunk and branch configuration, it is best to terminate at
the point where the branching occurs or at a point very close to it
• If the link contains more than one type of wire, the link will probably have to
be manually tuned. Trane recommends that only one type of wire be used for
the Comm5 communication link
• A set of as-built drawings or a map of the communication wire layout should
be made during installation. Any sketch of the communication layout should
feature the terminating resistor placement
26CNT-SVX05A-EN
Page 33
Communications
Figure 5 — Daisy chain resistor placement
Recommended wiring practices
The following guidelines should be followed while installing communication
wire.
• Comm5 is not polarity sensitive. Trane recommends that the installer keep
polarity consistent throughout the site
• Only strip away 2" maximum of the outer conductor of shielded cable
• Make sure that the 24VAC power supplies are consistent in how they are
grounded. Avoid sharing 24VAC between Comm5 UCMs
• Avoid over-tightening cable ties and other forms of cable wraps.
A tight tie or wrap could damage the wires inside the cable
• Do not run Comm5 cable alongside or in the same conduit as 24VAC power
• In an open plenum, avoid lighting ballasts, especially those using 277VAC
• Do not use a trunk and branch configuration, if possible. Trunk and branch
configurations shorten the distance cable can be run
CNT-SVX05A-EN27
Page 34
Power
The Tracer™ AH.540 controller is powered by 24VAC. Three pairs of two terminals
are provided for 24VAC connection to the board.
TB1-124VACPower input from control box 24VAC transformer
TB1-2GND
TB1-324VAC Accessory 24VAC power to other devices
TB1-4 GND
TB1-524VACAccessory 24VAC power to other devices
TB1-6 GND
Figure 6 — Tracer AH.540 power requirement
Line Voltage
Transformer
(factory supplied)
24 VAC
Termination
Board
Chasis
Ground
AHU Controller
28CNT-SVX05A-EN
Page 35
Input/output summary
The controller includes the following input and
output points:
Power
24VAC NEC Class 2
Two binary outputs
Supply fan start/stop (BO 1)
Exhaust fan start/stop (BO 2)
Five analog outputs
Supply fan speed (AO 1)
Cool output (AO 2)
Heat output (AO 3)
Face and bypass damper (AO 4)
Outdoor air damper (AO 5)
Seven analog inputs
Space temperature (IN 1)
Local setpoint (IN 2)
Fan mode switch (IN 3)
Discharge air temperature (IN 4)
Outdoor air temperature (IN 5)
Mixed air temperature (IN 6)
Duct static pressure (J43)
Six binary inputs
Low temp detect (IN 7)
Run/stop (IN 8)
Occupancy or generic (IN 9)
Supply fan status (IN 10)
Filter status (IN 11)
Exhaust fan status (IN 12)
Timed override On and Cancel inputs
Comm5 communication
CNT-SVX05A-EN29
Page 36
Sequence of operation
The Tracer™ AH.540 is a configurable controller. All of the controller's sequences
of operation are predefined with no need for programming the controller.
Configurable parameters are provided to allow user adjustments to the
controller’s operation. For example, the minimum occupied outdoor air damper
position can be changed.
All configuration parameters are set to defaults predetermined through
extensive air handling unit testing in several different operating conditions.
The factory default settings are also based on the air handling unit
configuration and order information.
The Tracer AH.540 controller is configurable to operate in one of three air
handling modes of operation:
• Constant volume space temperature control
• Constant volume discharge air temperature control
• Variable air volume (VAV) control
The Tracer AH.540 controller requires both a space temperature and discharge
air temperature sensor to be present for constant volume space temperature control operation (also called cascade control). In this control
mode, the controller compares the space temperature to the space heat/cool
setpoint to generate a discharge air temperature setpoint. The controller
modulates its heating or cooling outputs to control the discharge air
temperature to the discharge air temperature setpoint. This calculated
discharge air temperature setpoint is the desired discharge air temperature
(supply air temperature) that the unit must deliver to maintain space
temperature at the space heating or cooling setpoint.
The space temperature can be hardwired to analog input 1 (IN 1) on the
termination board (10kΩ thermistor only) or can be communicated to the
controller via Comm5. Similarly, a setpoint can be provided with either a
hardwired setpoint adjustment to analog input 2 (IN 2) on the controller, with a
communicated value, or by using the stored default setpoints in the controller.
The discharge air temperature must be a hardwired analog input (IN 4) to the
termination board (10kΩ thermistor only).
The Tracer AH.540 controller can be configured to operate in a constant volume discharge air temperature control mode. The controller only
requires a discharge air sensor (10kΩ thermistor only) to operate in this mode.
Constant volume discharge air temperature control modulates the heating or
cooling outputs to maintain the discharge air temperature at the discharge air
temperature setpoint.
When the Tracer AH.540 controller is configured for variable air volume (VAV) control, the controller maintains a discharge air temperature according
to the cool/heat discharge air setpoint, and duct static pressure at the duct static
pressure setpoint. The controller maintains duct static pressure by modulating
the fan analog output (AO 1) which is wired to the fan’s variable frequency
drive.
The duct static pressure input can either be hardwired or communicated to
the controller via Comm5. If both a communicated value and a hardwired duct
static pressure value exists, the communicated value has precedence. Similarly,
the duct static pressure setpoint can either be configured (default) or
communicated. If a communicated value is present, the communicated value
has precedence.
30CNT-SVX05A-EN
Page 37
Sequence of operation
If a space temperature input is provided to the controller when configured as
constant volume discharge air control or variable air volume control, the
controller uses the space temperature to perform morning warm-up and
daytime warm-up functions. Morning or daytime warm-up functions allow the
controller to automatically change to heating if space temperature is less than
the heating setpoint. Morning or daytime warm-up functions can also be
initiated through a communicated request.
Other temperature inputs, such as mixed air temperature or outdoor air
temperature, aid the controller's ability to maintain comfort and protect the
air handling unit.
Economizer cooling requires a mixed air temperature sensor and outdoor air
temperature value to be present. If an outdoor temperature is not available, a
communicated request from Tracer Summit
Economizer cooling is possible when the air handling unit is equipped with a
mixing box. The mixed air sensor is used as a low temperature limit, to keep
mixed air temperatures above freezing.
Active heating and cooling setpoints are affected by the controller's occupancy
mode. Valid occupancy modes for the three different control modes are shown
in the following table.
Table 20 — Tracer™ AH.540 occupancy modes of operation
Constant volume space temperature controlOccupied (default)
Constant volume discharge air temperature
control
Variable air volume controlOccupied (default)
The controller's occupancy mode is determined by either a binary input to the
controller (IN 9) or via a communicated request (from a system-level controller
or another peer controller).
Power up sequence
When 24VAC power is initially applied to the controller, the following sequence
occurs:
• Green Status LED turns on
• All binary outputs are controlled to their de-energized state, and analog
outputs are set to the normally closed output voltage
• The controller reads the inputs to determine initial values
• Power-up control wait feature is applied.The controller waits 300 seconds to
allow ample time for the communicated control data to arrive. If after
300 seconds, the controller has not received any communicated control data,
the unit assumes standalone operation
• Normal operation begins
Manual output test can be initiated at any time in the power up sequence or
during normal operation. Refer to the Manual output test section.
™
can enable economizer cooling.
Unoccupied
Occupied standby
Occupied bypass
Occupied (default)
Unoccupied
Occupied bypass
Unoccupied
Occupied bypass
CNT-SVX05A-EN31
Page 38
Sequence of operation
Space temperature setpoint operation
The controller has three sets of possible heating and cooling setpoints:
• Occupied
• Occupied standby
• Unoccupied
In unoccupied mode, the controller always uses locally stored default
unoccupied heating and cooling setpoints. These setpoints are configured at the
factory prior to shipment. Use Rover™ service tool to modify these default
unoccupied setpoints.
Table 21 — Setpoint operation
MethodUsed in these situations:
Zone sensor (with an
adjustable, hardwired
setpoint)
Communicated sourceA setpoint is communicated to the controller, typically from a building
Stored default setpointsThe controller uses the locally stored default heating and cooling
A hardwired, adjustable setpoint is connected to the controller
on IN 2. Local setpoints are enabled in the unit configuration.
No communicated setpoint is present.
automation system or a peer controller. If both a hardwired setpoint and
a communicated setpoint exist, the controller uses the communicated
value. The configuration feature for enabling/disabling the local setpoint
does not affect the setpoint handling when communic ated setpoints are
used. The communicated setpoint always takes priority over the setpointhardwired setpoint, even when the local setpoint is enabled.
setpoints when neither a local hardwired setpoint nor communicated
setpoint is present. When a building automation system is present,
the controller uses the default setpoints when no setpoint is
communicated to the controller and no hardwired setpoint exists.
The controller uses stored default setpoints when only a local setpoint
exists, but the local setpoint is disabled in the configuration of the
controller. The controller always uses the stored default (unoccupied)
setpoints in unoccupied mode.
Space temperature setpoint selection
Internal and external setpoint adjustment
Zone sensors with an internal or external setpoint adjustment (1kΩ) provide the
™
Trac er
An internal setpoint adjustment is concealed under the zone sensor’s cover.
To access the adjustable setpoint wheel, remove the zone sensor cover. An
external setpoint (when present) is accessible from the zone sensor’s front cover.
When the hardwired setpoint adjustment is used to determine the setpoints,
all unit setpoints are calculated based on the hardwired setpoint value, the
configured setpoints, and the active mode of the controller.
Example: Assume the controller is configured with the following default
setpoints:
Absolute Setpoint Offset = Setpoint Input – Mean Setpoint
From the default setpoints in this example, the mean setpoint is the mean of the
occupied cooling and heating setpoints, which is 72°F [(74+70) / 2]. The absolute
setpoint offset is the difference between the setpoint input and the mean
setpoint.
32CNT-SVX05A-EN
AH.540 controller with a local setpoint (50° to 85°F or 10° to 29.4°C).
Page 39
Sequence of operation
The hardwired setpoint is used with the controller's occupancy mode
(occupied, occupied standby, or unoccupied), the heating or cooling mode,
the temperature deadband values, and the heating and cooling setpoints
(high and low limits) to determine the controller's active setpoint
Example continued
an absolute setpoint offset of 1°F (73–72=1). The controller adds the absolute
setpoint offset (1°F) to occupied and occupied standby default setpoints to
AH.540 controller determines the effective setpoint based on the
following sequence:
1. Hardwired setpoint input
2. Setpoint calibration
3. Thumbwheel enabled or disabled? (Use default setpoints if thumbwheel is
disabled)
4. Communicated or local setpoint available?
5. Communicated setpoint input (nvisetpoint)
6. Communicated setpoint offset (nviSetptOffset)
7. Communicated setpoint shift (nviSetptShift)
8. Setpoint high and low limits (configurable)
9. Occupancy mode
10. Heating or cooling mode
When a building automation system or other controller communicates a
setpoint to the controller, the controller ignores the hardwired setpoint input
and uses the communicated value. The exception is the unoccupied mode,
when the controller always uses the stored default unoccupied setpoints.
After the controller completes all setpoint calculations based on the requested
setpoint, the occupancy mode, the heating and cooling mode, and other
factors, the calculated setpoint is validated against the following setpoint limits:
• Heating setpoint high limit
• Heating setpoint low limit
• Cooling setpoint high limit
• Cooling setpoint low limit
These setpoint limits only apply to the occupied and occupied standby heating
and cooling setpoints. These setpoint limits do not apply to the unoccupied
heating and cooling setpoints stored in the controller’s configuration.
Unit configuration also exists to enable or disable the local (hardwired)
setpoint at the zone sensor module. This parameter provides additional
flexibility to allow you to apply communicated, hardwired, or default
setpoints without having to make physical wiring changes to the controller.
: Assume a thumbwheel setpoint input of 73°F, resulting in
CNT-SVX05A-EN33
Page 40
Sequence of operation
Occupied and unoccupied operation
The valid occupancy modes of the Tracer™ AH.540 controller are:
•Occupied—Normal operating mode for occupied spaces or daytime
operation.
•Unoccupied—Normal operating mode for unoccupied spaces or nighttime
operation.
•Occupied Standby—Constant volume mode used to reduce the heating and
cooling demands during the occupied hours when the space is vacant or
unoccupied. For example, the controller may use occupied standby mode for
a classroom while the students are out of the room.
•Occupied Bypass—Mode used for timed override conditions. For example,
if the controller is in unoccupied mode and someone presses the On button
on the zone sensor, the controller is placed in occupied bypass mode for 120
minutes (adjustable) or until someone presses the Cancel button on the zone
sensor.
The occupancy mode can be hardwired to the controller via the occupancy
binary input or communicated to the controller.
Occupied mode
The Tracer AH.540 controller operates according to the configured control
mode:
• Constant volume space temperature control
• Constant volume discharge air temperature control
• Variable air volume control
When the controller is configured for constant volume space temperature
control, the unit attempts to maintain the space temperature at the active
occupied heating or cooling space setpoint, based on the measured space
temperature, the discharge air temperature, the active setpoint, and the
proportional/integral control algorithm. The modulating control algorithm used
when occupied or in occupied standby is described in the following sections.
Additional information related to the handling of the controller setpoints can be
found in the previous Setpoint operation section.
The Tracer AH.540 controller, when configured for constant volume discharge
air temperature control, maintains the discharge air temperature at the
configured discharge air temperature heating or cooling setpoint. The default
occupied mode of the controller is cooling. In the occupied mode, the
controller’s communicated application mode input (nviAppicMode) and heat/
cool mode input (nviHeatCool) determine the controller’s heating and cooling
setpoint. Refer to the Appendix for heating and cooling control modes of
operation.
When the controller is configured for variable air volume control, the duct static
pressure is always maintained at the configured or communicated duct static
pressure setpoint. The air volume is controlled by the supply fan speed analog
output to the variable frequency drive (VFD).
Variable air volume control also maintains the discharge air temperature at the
discharge air heating or cooling setpoint. The discharge air temperature and
supply fan speed are both modulated to maintain the duct static pressure at the
duct static setpoint and the discharge air at the discharge air temperature
setpoint.
Economizing is possible during any of the configured control types if a mixed
air sensor and outdoor air temperature sensor exist.
34CNT-SVX05A-EN
Page 41
Sequence of operation
Unoccupied mode
When the controller is in the unoccupied mode, the controller attempts to
maintain the space temperature between the configured unoccupied heating and
cooling setpoints, based on the measured space temperature. Similar to other
configuration properties of the controller, the locally stored unoccupied
setpoints can be modified using Rover™ service tool.
Constant volume space temperature control
In unoccupied mode the supply fan is off whenever the space temperature is
between the unoccupied heating and cooling setpoints. If the space temperature
rises above the unoccupied cooling setpoint the Tracer™ AH.540 turns on the
supply fan and provides cooling at the discharge air temperature setpoint low
limit.
If the space temperature drops below the unoccupied heating setpoint the
controller turns on the supply fan and provides heating at the discharge air
temperature setpoint high limit. See Table 40 Discharge air setpoint limits for constant volume space temperature control in the Configuration section of this
manual.
Constant volume discharge air or variable air volume control
For unoccupied heating or cooling operation the controller must have a space
temperature input either hardwired or communicated from Tracer Summit™.
In unoccupied mode the supply fan is off whenever the space temperature is
between the unoccupied heating and cooling setpoints. If the space temperature
rises above the unoccupied cooling setpoint the Tracer AH.540 turns on the
supply fan and provides cooling at the discharge air cooling setpoint.
If the space temperature drops below the unoccupied heating setpoint the
controller turns on the supply fan and provides heating at the discharge air
heating setpoint. See Table 41 Discharge air temperature control setpoints and setpoint limits in the Configuration section of this manual.
If configured for variable air volume control, supply fan will control duct static
pressure at the duct static pressure setpoint.
Note that primary heating or cooling capacity is defined by unit type and
whether heating or cooling is enabled or disabled. For example, if the
economizer is enabled and possible, it will be the primary cooling capacity.
If hydronic heating is possible, it will be the primary heating capacity.
Occupied standby mode
In the occupied standby mode, the controller uses the occupied standby cooling
and heating setpoints. Because the occupied standby setpoints typically cover a
wider range than the occupied setpoints, the Tracer AH.540 controller reduces
the demand for heating and cooling the space. Also, the outdoor air economizer
damper uses the economizer standby minimum position to reduce the heating
and cooling demands.
Occupied standby is a mode in which the controller has received an occupied
request from Tracer Summit
input IN 9 signal. For example, an unoccupied conference room (as sensed by a
local occupancy sensor) in an occupied building (as commanded by Tracer
Summit) is in occupied standby mode. When the conference room becomes
occupied with people, the local occupancy sensor changes the controller mode
to occupied.
The controller can be placed into the occupied standby mode when a
communicated occupancy request is combined with the local (hardwired)
occupancy binary input signal. When the communicated occupancy request
is unoccupied, the occupancy binary input (if present) does not affect the
™
, but has also received a local unoccupied binary
CNT-SVX05A-EN35
Page 42
Sequence of operation
controller's occupancy. When the communicated occupancy request is
occupied, the controller uses the local occupancy binary input to switch
between the occupied and occupied standby modes.
During occupied standby mode, the controller's economizer damper position
goes to the economizer standby minimum position. The economizer standby
minimum position can be changed using Rover service tool.
When no occupancy request is communicated, the occupancy binary input
switches the controller’s operating mode between occupied and unoccupied.
When no communicated occupancy request exists, the unit cannot switch to
occupied standby mode.
Occupied bypass mode
The controller can be placed in occupied bypass mode by either communicating
an occupancy request of Bypass to the controller or by using the timed override
On button on the Trane zone sensor.
When the controller is in unoccupied mode, you can press the On button on the
zone sensor to place the controller into occupied bypass mode for the duration
of the bypass time (typically 120 minutes).
If the controller is in the occupied standby mode, you can press the On button
on the zone sensor to place the controller into occupied bypass mode for the
duration of the configured bypass time. Typically occupied and occupied
standby are controlled from the local binary occupancy input.
Occupancy sources
There are four ways to control the occupancy mode:
• Communicated request (usually provided by the building automation system
or peer device)
• By pressing the zone sensor's timed override On button (or Cancel button)
• Occupancy binary input
• Default operation of the controller (occupied mode)
A communicated request from a building automation system or another peer
controller can change the controller's occupancy. However, if communication is
lost, the controller reverts to the default operating mode (occupied) after 15
minutes (configurable, specified by the “receive heartbeat time”), if no local
hardwired occupancy signal exists.
Determining the occupancy mode
The occupancy of the controller is determined by evaluating the combination of
three potential communicating inputs, as well as the hardwired occupancy input
and the occupied bypass timer. Three different communicating inputs affect the
controller's occupancy mode:
• Occupancy—manual command
• Occupancy—schedule
• Occupancy—sensor
These inputs provide maximum flexibility, but the number of inputs you decide to
use varies with the application and the features available in your building
automation system.
Occupancy—manual command
Some communicating devices may request occupancy based on the information
communicated in the network variable nvoOccManCmd. Trane systems and zone
sensors do not communicate this information to the controller, but the Tracer
controller accepts this network variable as communicated input nviOccManCmd.
Occupancy—schedule
™
AH.540
36CNT-SVX05A-EN
Page 43
Sequence of operation
Building automation systems normally communicate an occupancy request using
the occupancy—schedule input. The Tracer AH.540 controller accepts
communicated occupancy schedule as a network variable input nviOccSchedule.
Occupancy—sensor
Some occupancy sensors may be equipped with the ability to communicate
an occupancy mode to the controller. In such devices, network variable input
nviOccSensor is used to communicate occupancy to the controller. Trane systems
and zone sensors do not currently send this variable. The hardwired occupancy
input of this controller is handled as if it is a communicated occupancy sensor input.
When both a hardwired input and a communicated input exist, the communicated
input is used.
Table 2 2 — Effect of occupancy commands on the controller
Invalid or not presentOccupiedOccupied (Note 3)Occupied
Note 1: Occupied bypass is initiated by either a communicated request or by pressing the local zone sensor On button.
The effective occupancy is occupied bypass.
Note 2: The occupancy sensor can be either a local input or a communicated input. If a valid value for the network input
is present, it has precedence over the local input.
Note 3: If the occupancy sensor communicated input is invalid or not present, and no local input exists, the controller's
mode is occupi ed.
Note 4: If the occupied bypass timer is not equal to zero, the effective occupancy will be occupied bypass.
On and Cancel buttons on the zone sensor
Some Trane zone sensor modules include timed override On and Cancel buttons. Use
the timed override On and Cancel buttons to place the controller in override (occupied
bypass mode) and to cancel the override request.
The controller always recognizes the timed override On button. If someone presses
the zone sensor's timed override On button, the controller initializes the bypass timer
to 120 minutes (adjustable).
If the controller is unoccupied when someone presses the On button, the controller
immediately changes to occupied bypass mode and remains in the mode until either
the timer expires or someone presses the zone sensor's timed override Cancel
button. If the On button is pressed during occupied bypass mode before the timer
expires, the controller initializes the bypass timer to 120 minutes.
If the controller is in any mode other than unoccupied when someone presses the On
button, the controller initializes the bypass time to 120 minutes. As time expires, the
bypass timer continues to decrement. During this time, if the controller changes from
its current mode to unoccupied (perhaps due to a change based on the system's time
of day schedule), the controller switches
to occupied bypass mode for the remainder of the bypass time or until someone
presses the zone sensor's timed override Cancel button.
Occupancy binary input
You can configure input 9 (IN 9) as an occupancy binary input. The Tracer™
AH.540 controller uses the occupancy binary input for two occupancy-related
functions. For standalone controllers (any unit not receiving a communicated
occupancy request, typically from a building automation system), the occupancy
binary input determines the occupancy of the unit based on the hardwired signal.
Normally, the signal is hardwired to a binary switch or time clock.
When a hardwired occupancy signal is open, the unit switches to occupied
mode (if the occupancy input is configured as normally open). When a
hardwired occupancy signal is closed, the controller switches to unoccupied
mode.
For controllers that receive a communicated occupancy request from a building
automation system, the hardwired occupancy binary input is used with a
communicated occupancy request to place the controller in either occupied
mode or occupied standby mode.
In occupied mode, the controller operates according to the occupied setpoints.
In occupied standby mode, the unit controller operates according to the
occupied standby setpoints. When the controller receives a communicated
unoccupied request, the controller operates according to the unoccupied
setpoints regardless of the hardwired occupancy input state.
If neither the hardwired binary input nor a communicated request is used to
select the occupancy mode, the controller defaults to occupied mode because
the occupancy binary input (if present) typically is configured as normally open
and no occupancy device is connected.
Constant volume space temperature control
The controller uses the space temperature and the measured discharge air
temperature to maintain the space temperature at the active space cooling
setpoint or the active space heating setpoint.
The controller's heat/cool mode is determined by either a communicated
request or by the controller itself, when the heat/cool mode is Auto. When the
heat/cool mode is Auto, the controller compares the active space setpoint and
the active space temperature and decides if the space needs heating or cooling.
The Tracer AH.540 controller must have a valid space temperature and discharge
air temperature input to operate constant volume space temperature control.
When the controller is configured for a constant volume supply fan and space
temperature control, the controller will not operate the unit if the space
temperature or discharge air temperature sensors are missing or have failed.
The controller's space temperature control algorithm uses two control loops:
a space temperature loop and a discharge air temperature loop. The space
temperature control loop compares the active heat/cool space setpoint and
the space temperature and calculates a discharge air temperature setpoint.
The calculated discharge air temperature setpoint range is bound by
configurable heating (maximum) and cooling (minimum) limits.
The discharge air temperature loop compares the discharge air temperature
to the calculated discharge air temperature setpoint (calculated by the space
temperature loop), and calculates a heat or cool capacity to respond to
discharge air temperature setpoint.
38CNT-SVX05A-EN
Page 45
Sequence of operation
The capacity calculation, as a result of the discharge air control loop, is used to
drive the air handling unit's actuators to maintain space temperature at the
space temperature setpoint.
Figure 7 — Space temperature control block diagram
Space temperature →
Space temperature setpoint→
Space temperature control gains
Discharge air temperature setpoint limits→
Discharge air temperature→Discharge air control loop
Discharge air control gains→
Space temperature control loop
→
↓
Discharge air temperature setpoint
↓
↓
Calculate heat/cool capacity
↓
Use capacity to drive actuators
Control gains
Figure 7 above illustrates the separate control for the space temperature control
loop and discharge air control loop. The gain parameter values that control the
different loops have been determined through extensive testing of different
types of heating or cooling capacities and at operating conditions of the air
handling unit.
Heating or cooling control mode operation
The heating or cooling control mode of the controller can be determined two
ways:
• Communicated request
• Automatically by the controller
Communicated request
A building automation system or peer controller may communicate the heating
or cooling mode to the controller via network variables nviHeatCool and/or
nviApplicMode. Heating mode commands the controller to heat only. Cooling
mode commands the controller to cool only. The Auto mode allows the
controller to automatically change from heating to cooling or cooling to heating.
Refer to the Appendix, Table 63 Constant volume space temperature control operation based on the effective heat/cool output.
CNT-SVX05A-EN39
Page 46
Sequence of operation
Table 2 3 — Constant volume unit operation allowed based on communicated
request
Note 2: The Tracer™ AH.540 controller does not support Emergency heat. Emergency heat will be treated as Auto.
Automatically by the controller
A communicated request of Auto or the controller's default operation (Auto) can
place the unit into heating or cooling mode. When the controller automatically
determines the heating or cooling mode while in Auto mode, the unit switches
to the desired mode based on the control algorithm.
If the Tracer AH.540 controller is operating space temperature control,
it uses the space temperature and space temperature setpoint to automatically
determine heat or cool mode of operation. When the controller first powers up
or after a reset, it makes an initial determination if the heat/cool mode should
be heat or cool. If the controller is configured as heating and cooling, the
controller determines the appropriate mode.
Example: If the initial space temperature is less than the occupied space heat
setpoint then the initial heat/cool mode is heating. The heat/cool mode for a
cool-only unit is always cool. The heat/cool mode for a heat-only unit is always
heat.
When the controller is allowed to automatically determine its space heating and
cooling mode, the unit changes from cool to heat or from heat to cool, when
the integrated error between the active space setpoint and the active space
temperature is 900° F • seconds or greater. The integrated error is calculated
once every ten seconds.
See Figure 8 below for an example of the controller changing from space
cooling (Unit Mode = cool) to space heating (Unit Mode = heat). In this example
the controller’s initial unit mode is cool because the space temperature is above
the cool setpoint, and the controller's cooling capacity is greater than 0%.
Following the curve from left to right, the space temperature falls below the cool
setpoint and the controller reacts by lessening its cooling capacity.
When the space temperature reaches 1, the controller's capacity is 0%.
The rate at which the controller reaches 0% capacity depends on the space
temperature rate of change.
Supply fanMechanical
EnabledEnabledDisabl edClosedDisabled
EnabledEnabledEnabledEnabledEnabled
heating
Mechanical
cooling
Outdoor air damperExhaust fan
Economizer enabled
Economizer enabled
Enabled
Disabled
40CNT-SVX05A-EN
Page 47
Sequence of operation
Figure 8 — Automatic heat/cool changeover logic example
1 This is the point at which the cooling capacity equals 0%, space
temperature is less than 0.5° F below the cooling setpoint, and the error
integrator starts to add up. Error integration does not begin until the
capacity is 0%. See the Error integration example below.
2 The space temperature must fall below the active space heat setpoint
before the controller can change to heating. Conversely, the space
temperature must rise above the active space heat +0.5° F setpoint before
the controller can change to cooling.
3 The controller switches to heat (from cool) after the error integrator exceeds
900° F • seconds.
4 The controller must be able to heat before it will switch to heat. A unit that
cannot heat will not switch to heat. A unit that cannot cool will not switch
to cool.
Error integration example: If the active space temperature is 66.5 °F, t he
current mode is cooling, and the space cooling setpoint is 70 °F. T h e e r r o r
calculation is 70 - 0.5 - 66.5 = 3° F. If the same error exists for 60 seconds, the
error integration term is
(3 °F x 60 seconds = 180 °F seconds). Therefore, after five minutes
(3 °F x 300 seconds = 900 °F seconds), the controller will switch from cooling
to heating mode.
Cooling operation
The heating and cooling space setpoint high and low limits are always applied
to the occupied and occupied standby setpoints.
™
During the cooling mode, the Tracer
the active space temperature at the active space cooling setpoint. Based on the
controller's occupancy mode, the active space cooling setpoint is one of the
following:
• Occupied cooling setpoint
• Occupied standby cooling setpoint
• Unoccupied cooling setpoint
AH.540 controller attempts to maintain
CNT-SVX05A-EN41
Page 48
Sequence of operation
The cooling outputs are controlled based on the unit configuration and the
required machine cooling capacity. At 0% machine cooling capacity, the cooling
valve is closed and the outdoor air damper is at its minimum position. As the
required machine cooling capacity increases, the cooling valve and/or the
outdoor air damper opens above their minimum positions.
The constant volume control algorithm calculates a desired discharge air
temperature to maintain the space cooling setpoint. Cool capacity is controlled
to achieve the desired discharge air setpoint. Heat capacity can also be used to
temper cold outdoor air conditions to maintain ventilation and the discharge air
setpoint.
The outdoor air damper is used for cooling whenever economizing is possible
and there is a need for cooling. If economizing is not possible, it will not be
used in cooling. If economizing is possible, it is always the first stage of cooling.
See the Outdoor air damper section for more information.
Heating operation
In the heating mode, the Tracer
space temperature at the active heating setpoint. Based on the controller's
occupancy mode, the active space heating setpoint is one of the following:
• Occupied heating setpoint
• Occupied standby heating setpoint
• Unoccupied heating setpoint
The outputs are controlled based on the unit configuration and the required
machine heating capacity. At 0% machine heating capacity, the heating capacity
is at its minimum position. As the required machine heating capacity increases,
the heating capacity is opened above its minimum position. At 100% machine
heating capacity, the heating capacity is open to its maximum position.
The economizer outdoor air damper is never used as a source of heating.
The economizer damper is only used for ventilation when the unit is heating.
For more information about outdoor air damper operation, see the Outdoor air damperoperation section.
Constant volume discharge air temperature control
Constant volume discharge air temperature control maintains a discharge air
temperature at a desired discharge air temperature setpoint regardless of the
entering air conditions of the air handling unit.
Figure 9 shows the steps the Tracer AH.540 controller takes to control discharge
air. First the controller determines if a communicated discharge air heating
setpoint and discharge air cooling setpoint are present. The communicated
setpoint has precedence over the configured (default) setpoint. If no
communicated value is present, the controller uses the configured discharge air
temperature setpoint.
Discharge air temperature setpoint minimum and maximum limits are placed
on the discharge air setpoint depending on the effective heat or cool mode.
If the effective heat/cool mode is cool, the maximum discharge air cooling
setpoint limit and minimum discharge air cooling setpoint limit the discharge
air cooling setpoint. See the Configuration section for more information about
discharge air heating and cooling setpoint limits.
™
AH.540 controller attempts to maintain the
42CNT-SVX05A-EN
Page 49
Sequence of operation
The effective discharge air temperature setpoint is determined from:
• communicated or configured discharge air setpoint value
• minimum and maximum heat/cool setpoint limits
• the effective heat/cool mode
Example
Table 2 4 — Configuration parameters
Discharge air cooling setpoint55°F
Maximum discharge air cooling setpoint68
Minimum discharge air cooling setpoint 53
Discharge air heating setpoint100
Maximum discharge air heating setpoint
(Note 1)
Minimum discharge air heating setpoint 86
Note 1: When the controller is appli ed to an air hand ling unit with a draw-through suppl y fan, the maxi mum dischar ge
air heating setpoint should be set to 104°F (default setpoint). This prevents the discharge air temperature from
exceeding the high temperature limit of the supply fan motor. Exceeding the motor's temperature limit can cause
premature failures.
Table 2 5 — Communicated values
Discharge air cooling setpoint input50
Discharge air heating setpoint input none
Effective heat cool mode Cool
:
°F
°F
°F
104
°F
°F
°F
Since the effective heat cool mode is Cool and the communicated value has
precedence over the local configuration value, the discharge air cooling
setpoint is 50 °F. The maximum and minimum discharge air cooling setpoint
limits are then applied to determine an effective discharge air temperature
setpoint of 53 °F, from Table 23.
In this example, if the effective heat cool mode is Heat, the effective discharge
air temperature setpoint would be 100°F.
The discharge air temperature control loop uses the effective discharge air
temperature setpoint, discharge air temperature (from the wired sensor), and
the configured control gains to calculate an output capacity for the end devices.
CNT-SVX05A-EN43
Page 50
Sequence of operation
Figure 9 — Discharge air temperature control flow diagram
Configured value:
discharge air heating setpoint
discharge air cooling setpoint
→ The communicated heat/cool setpoint value has
precedence over the configured discharge air
temperature heat/cool setpoint
Communicated value:
discharge air heating setpoint
discharge air cooling setpoint
Effective heat/cool mode→ Effective discharge air temperature setpoint
Discharge air temperature→ Discharge air temperature control loop
(wired sensor)
Discharge air control gains→ Calculate heat/cool capacity
→
Discharge air heating
setpoint
Discharge air
heat setpoint limits
Use capacity to drive actuators
↓↓
↓↓
Discharge air cooling
setpoint
Discharge air
cool setpoint limits
↓
↓
↓
Heating or cooling control mode operation
The heating or cooling control mode of the controller can be determined in
two ways:
• Communicated request
• Automatically by the controller
Communicated request
A building automation system or peer controller may communicate the heating
or cooling mode to the controller via network variable nviApplicMode. Heating
mode commands the controller to heat only. Cooling mode commands the
controller to cool only. The Auto mode allows the controller to automatically
change from heating to cooling or cooling to heating. See Appendix Table 63
Constant volume discharge air temperature control and variable air volume
operation based on the effective heat/cool output.
Automatically by the controller
A communicated request of Auto or the controller's default operation (Auto)
can place the unit into cooling mode. A zone temperature input is required for
constant volume discharge air control when auto heat/cool changeover is
desired. When the controller automatically determines the heating or cooling
mode using auto mode, the unit switches to the desired mode based on the
control algorithm and the relationship between zone temperature to the
configured daytime warm up start and stop setpoints. See daytime warm up in
configuration section of this manual.
When the controller first powers up or after a reset, it makes an initial
determination if the discharge air control mode should be heating or cooling.
The discharge demand for a cooling-only unit is always cooling. The discharge
demand for a heating only unit is always heating. A unit that can heat or cool
initially starts in cooling mode.
44CNT-SVX05A-EN
Page 51
Sequence of operation
Variable air volume control
The Tracer™ AH.540 controller that is operating with variable air volume control
uses both a discharge air temperature control routine and a duct static pressure
control routine. The unit’s discharge air temperature is controlled using the
discharge air temperature control sequence. The air handling unit's duct static
pressure is maintained by a duct static pressure control sequence.
Duct static pressure control
The supply fan variable frequency drive, in a variable air volume system, is
controlled to maintain the duct static pressure setpoint. When the fan is On, the
controller reads and compares the duct static pressure input to the duct static
pressure setpoint and adjusts the supply fan speed analog output signal (AO 1)
to the variable frequency drive.
The duct static pressure signal can be from a wired sensor or communicated via
a network variable. If the controller does not have a valid duct static pressure
from a wired sensor or communicated, the controller generates a Duct static press failure diagnostic and shuts down the unit. The controller does not
operate duct static pressure control without a valid duct static pressure input.
If the controller has both a hardwired and communicated duct static pressure
input, the communicated value is used for duct static pressure control. The
greater of the two values, hardwired or communicated, is used for duct static
pressure high limit shutdown.
The Tracer AH.540 controller has a configurable duct static pressure high limit
setpoint. If the duct static pressure exceeds the duct static pressure high limit
setpoint, the controller shuts down the unit and generates a Duct static pressure high limit diagnostic. This latching diagnostic must be cleared from
the controller before unit is allowed to operate.
Supply fan operation
The Tracer AH.540 controller determines fan operation based on the selected
control mode. If the Tracer AH.540 controller is configured for constant volume
space temperature control or constant volume discharge air control, the
controller turns the supply fan binary output (BO 1) on continuously during
occupied, occupied standby, and occupied bypass modes.
When a supply fan status binary input sensor is wired to the controller (IN 10) it
is used to verify fan operation before heating and cooling start. Upon
energizing the supply fan output (BO 1) the Tracer AH.540 controller waits a
configurable time period (fan status delay) to allow the fan time to reach a
desired air flow. Then the controller verifies fan operation (fan status).
A Low Supply Fan Air Flow diagnostic is detected when the controller is
commanding the fan On and the fan status switch is not in the closed position,
or if the fan status switch does not close the binary input within the configured
time limit after the controller commanding the fan On. This is a latching
diagnostic and discontinues unit operation until the diagnostic is cleared from
the controller.
CNT-SVX05A-EN45
Page 52
Sequence of operation
Certain diagnostic conditions can cause the controller to shut down the unit,
which affects fan operation. See the Diagnostics section for details.
If the controller is configured for variable air volume control, variable speed fan
operation is assumed by the controller. The supply fan analog output (AO 1)
and binary output (BO 1) are used to control a variable frequency drive.
Constant volume operation
The Tracer™ AH.540 controller turns on the supply fan continuously during
occupied, occupied standby, and occupied bypass modes of operation.
During unoccupied periods, the supply fan binary output (BO 1) controls the
supply fan off and on depending on heating or cooling requirements.
If the controller is wired to a Trane zone sensor, the user can change the supply
fan operation through the fan mode switch (when present). When the fan mode
switch is in the Off position, the controller shuts down the unit. If the fan mode
switch is moved to the Auto position, the controller operates the fan on and off
according to heat and cool demands and the active occupancy mode.
Variable air volume operation
For variable air volume supply fan operation, the Tracer AH.540 controller must
be configured for variable air volume control and have a duct static pressure and
discharge air temperature sensor available. The controller's supply fan binary
output (BO 1) controls the fan's run/stop input, and the controller's supply fan
analog output (AO 1) controls the supply fan speed.
The supply fan speed is controlled to maintain the air handling unit's duct static
pressure to the desired duct static pressure setpoint.
The Tracer AH.540 controller has a configurable duct static pressure high limit.
Fan operation is controlled to actively avoid exceeding this high pressure limit.
If the duct static pressure exceeds the duct static pressure high limit point, the
controller shuts down the unit and generates a Duct static press high limit
diagnostic. This latching diagnostic must be cleared from the controller before
unit operation is allowed.
Valve operation
The controller uses analog modulating (0-10VDC or 2-10VDC) valves for heating
or cooling operation. The controller supports one or two modulating valves for
hydronic heating, steam heat, and hydronic cooling operation. The Tracer
AH.540 controller supports both one- and two-valve unit configurations. See the
Configuration section for further details regarding heating and cooling
configurations.
A one-valve unit can be either cooling only or heating only. A two-valve unit
supports preheat (heating coil before the cooling coil) or reheat coil-valve
configurations (heating coil after the cooling coil).
If the cooling output is configured for cooling and the heating valve is
configured for preheat (or reheat), the controller always assumes hot water
(or steam) is available for the heating valve and cold water is available for the
cooling valve.
The Tracer AH.540 controller operates to either normally open or normally
closed valves. The normal state of the valve is the position of the valve when
power is not applied. When power is applied, the controller has full control of
the valve. For example, if the fan mode switch on the zone sensor is in the Off
position, the controller closes the valve, regardless if it is configured normally
open or normally closed.
46CNT-SVX05A-EN
Page 53
Sequence of operation
Steam valve cycling
During low temp detect or freeze avoidance diagnostic conditions, which causes
a unit shutdown, the controller opens all heating and cooling valves 100% to
prevent the coil from freezing. When steam heat is present, the controller cycles
the steam heat valve output on, then off over a period of five minutes
(configurable) to prevent excessive unit cabinet temperatures. The heat valve
output Open position is configurable 0 to 100%.
For example: If steam heat cycling is configured for 25% (default), the
controller opens the steam valve for 75 seconds (25% of 5 minutes) and
closes it for 225 seconds.
Caution! An air handling unit with greater than 15 psig of steam could create
excessive cabinet temperatures with the valve 100% open.
Face and bypass damper operation
The face and bypass damper modulates a percentage of air to the face of the heat
coil and around the coil (bypass) to maintain the supply air temperature setpoint.
The air passing through the hot water coil is mixed with the air bypassing the
coil to produce a desired discharge air temperature.
™
The Tracer
outdoor temperature heating modes of operation only. During low outdoor
temperatures, when the outdoor air temperature is lower than the face and
bypass heat modulation setpoint, the heating valve is fully opened and the
face and bypass damper is used for heating to prevent the coil from freezing.
During economizer cooling operation, when outdoor temperature is less than
the face and bypass heat modulation setpoint, the face and bypass damper
is full bypass.
The face and bypass heat modulation setpoint is the outdoor air temperature
(40°F default) at which the controller changes over to face and bypass heating
operation. The face and bypass heat modulation setpoint can be changed using
the Trane Rover™ service tool.
When the outdoor air temperature is greater than 3°F above the face and
bypass heating modulation setpoint, the hydronic heating valve is modulated
to maintain discharge air temperature. The face and bypass damper is
positioned for full face air flow. When the outdoor air temperature is less than
the face and bypass heating modulation setpoint, the controller fully opens the
heating valve and uses the heat face and bypass damper to modulate heating
capacity to maintain the desired discharge air temperature.
AH.540 controller supports face and bypass operation for low
CNT-SVX05A-EN47
Table 2 6 — Face and bypass damper operation based upon outdoor air
temperature
Outdoor air tem peratureHyd ronic heating valveFace and bypass damper
Outdoor air temperature is
greater than face and
bypassheat modulation
setpoint (Note 1)
Outdoor air temperature is less
than face and bypass heat modulation setpoint
Note 1: The outdoor air temperature must rise 3°F above the face and bypass heating enable point before face and
bypass heating operation is disabled.
Modulated to maintain
desired setpoint
100% openModulated to maintain desired
Full coil face
(operation disabled)
setpoint
(operation enabled)
During diagnostic and fan off conditions, when the controller shuts down unit
operation, the face and bypass damper is in the full bypass position. During
freeze avoidance operation or a Low Temp Detect diagnostic, the face and bypass
damper is driven to full face.
Page 54
Sequence of operation
Outdoor air damper operation
The controller operates the modulating outdoor air damper according to the
effective occupancy, outdoor air temperature (communicated or hardwired
sensor), space temperature, effective space temperature setpoint, discharge air
temperature, and discharge air temperature setpoint. Default minimum damper
positions are provided and can be changed using Trane's Rover service tool for
occupied and occupied standby ventilation.
The controller can also receive a communicated outdoor air damper minimum
position from Tracer Summit
Summit has priority over all configured minimum setpoints. When a
communicated minimum position is not present, the controller uses the
configured minimum setpoints.
Table 2 7 — Determining the economizer damper minimum position setpoint
During occupied modes, the damper remains at a minimum damper position,
whether a configured minimum position or communicated from Tracer
Summit.
Mixed air temperature control
The Tracer
™
AH.540 controller provides minimum ventilation requirements
according to the effective occupancy mode. Ventilation requirements are
maintained by mixed air control depending on available heating and cooling
sources, unit configuration, and mixed air control type (configurable). Low
mixed air temperatures can be a concern for units with hydronic heating and
cooling.
Mixed air control is used to maintain the mixed air temperature above the
mixed air low limit setpoint (configurable). See Table 27 below. If the air
handling unit does not have a mixing box section, then mixed air control is not
required.
Heat only, cool only, or cool reheat air handling configurations with a mixing
box can be configured for mixed air control. If cold outdoor air conditions exist,
depending on ventilation requirements, the mixed air temperature can create
freezing conditions. Mixed air control reduces the outdoor air damper below
the minimum position to maintain mixed air temperature above the mixed air
temperature low limit.
Air handling units with preheat can use mixed air preheat control to maintain
mixed air temperature before reducing ventilation. Cold entering air conditions
from the mixing box can be heated with the preheat capacity to maintain the
mixed air temperature above the mixed air temperature low limit. Mixed air preheat control attempts to use preheat until it has reached 100% capacity.
At 100% preheat capacity, if mixed air temperature is below the low limit
temperature, the mixed air preheat control then lowers the outdoor air damper
below the minimum position to maintain mixed air above the mixed air
temperature low limit.
™
. A communicated minimum position from Tracer
48CNT-SVX05A-EN
Page 55
Sequence of operation
If ventilation is not a concern, the Tracer™ AH.540 controller can be configured
for mixed air control when preheat capacity is available. Mixed air preheat control is the best choice for preheat air handling units with ventilation
requirements.
Table 2 8 — Mixed air temperature control
Air handling unit
configuration
No mixing box
present
Heat only unit
Cool only unit
Cool reheat unit
Preheat cool unitMixed air preheat
Economizer operation
Economizing is a mode in which outdoor air is used as a source of cooling
capacity before hydronic cooling. With a valid outdoor air temperature
(either hardwired or communicated) or a communicated Enable command from
Tracer Summit
damper as the highest priority source of free cooling.
Economizing is possible during the occupied, occupied standby, unoccupied,
and occupied bypass modes.
The controller initiates the economizer function if the outdoor air temperature is
cold enough to be used as free cooling capacity. If the outdoor air temperature
is less than the economizer enable setpoint (absolute dry bulb), the controller
modulates the outdoor air damper (between the active minimum damper
position and 100%) to control the amount of outdoor air cooling capacity. When
the outdoor air temperature rises 5°F above the economizer enable point, the
controller disables economizing and moves the outdoor air damper back to its
predetermined minimum position based on the current occupancy mode or
communicated minimum damper position.
Mixed air
control type
(configurable)
NoneNone
Mixed air controlReduce ventilation. Mixed air temperature is maintained
control
™
, the Tracer AH.540 controller uses the modulating economizer
Controller action
above the mixed air low limit setpoint (50
urable) by reducing the outdoor air ventilation below minimum position. The lower percent of outdoor air raises the
mixed air temperature.
Preheat before reducing ventilation. Preheat capacity is used
to maintain the mixed air temperature above the mixed air
temperature low limit setpoint (50
100% preheat capacity does not maintain the mixed air temperature above the mixed air temperature low limit, outdoor
air ventilation is reduced below minimum position.
°F default, config-
°F default, configurable). If
CNT-SVX05A-EN49
Page 56
Sequence of operation
Table 2 9 — Relationship between outdoor temperature sensors and damper
position
Outdoor air temperature Occupied or
No or invalid outdoor
air temperature
Failed outdoor air
sensor
Outdoor air temperature
less than the low ambient damper lockout setpoint (Note 1)
Outdoor air temperature
present and economizing feasible
Outdoor air temperature
present and economizing not feasible (Note 2)
Note 1: The low ambient damper lockout setpoint is a configurable temperature setpoint used to close the outdoor air
damper, regardless of occupancy, when extreme outdoor air temperatures are present.
Note 2: The Tracer™ AH.540 controller disables economizing if the mixed air temperature sensor is not present or is not
valid.
Occupied bypass
Open to occupied
minimum position
Open to occupied
minimum position
ClosedClosedClosed
Economizing, damper
controlled between
occupied minimum
position and 100%
Open to occupied
minimum position
Low ambient damper lockout
The controller closes the outdoor air damper during any heating, cooling,
or economizer mode of operation or occupancy when extreme outdoor air
temperatures exist. This condition disables outdoor air damper ventilation and
economizing functions, but low ambient damper lockout does not affect other
unit operations.
The outdoor air temperature must rise 5°C (9°F) above the low ambient damper
lockout setpoint before economizing and ventilation become possible again.
Exhaust fan operation
The exhaust fan/damper is coordinated with the unit supply fan and outdoor
damper operation. The exhaust output is energized only when the unit supply
fan is operating and the outdoor damper position is greater than or equal to the
configurable exhaust fan start setpoint. The exhaust fan output is disabled when
the outdoor air damper position drops 10% (configurable) below the exhaust fan
start setpoint. If the enable point is less than 10% (configurable), the unit turns
on at the start setpoint and off at zero.
The controller logic commands the exhaust fan to be energized/de-energized
based on the target position of the economizing damper. Because of device
stroke time, the state of the exhaust fan may change before the economizing
damper reaches its target position.
If the exhaust fan start setpoint is set at or lower than the outdoor air damper
minimum position, the exhaust fan will be on continuously when the outdoor
air damper is at minimum position.
If the exhaust fan start setpoint is set higher than the outdoor air damper
minimum position (minimum ventilation) the exhaust fan will be off during
periods of minimum ventilation. During economizer cooling operation the
exhaust fan start setpoint can be selected to compensate for the increased
outdoor ventilation.
The exhaust fan status binary input is present to detect operation of a
belt-driven exhaust fan. An Exhaust Fan Air Flow diagnostic is detected when
the control starts the exhaust fan and the exhaust fan status binary input does
not indicate operation after two minutes. This is an exhaust fan latching
Outdoor air damper
Occupied standbyUnoccupied
Open to occupied
standby minimum
position
Open to occupied
standby minimum
position
Economizing, damper
controlled between
occupied standby minimum position and 100%
Open to occupied
standby minimum
position
Closed
Closed
Open and economizing
during unit operation,
otherwise closed
Closed
50CNT-SVX05A-EN
Page 57
Sequence of operation
diagnostic and discontinues exhaust operation until the diagnostic is reset.
All other control functions continue to operate normally.
Electric heat operation
The Tracer™ AH.540 controller does not support electric heat. Use of the
controller's heat output to control electric heat elements for heating purposes is
highly discouraged. Using the heat output to control electric heat could cause
dangerously high cabinet temperature conditions when the supply fan is off or
when low airflows exist.
Morning warm-up
The morning warm-up function initiates a special heating sequence to raise
space temperature to occupied conditions. This sequence is especially useful for
a building occupancy transition from unoccupied to occupied.
The Tracer AH.540 controller performs morning warm-up differently for
constant volume space temperature control than constant volume discharge air
control or variable air volume control.
Constant volume space temperature control
The controller keeps the outdoor air damper closed (when a mixing box is
present) anytime during a occupied, occupied bypass, or occupied standby
mode when the space temperature is 3ºF or more below the heating setpoint.
The damper remains closed indefinitely (no time limit) during morning warmup until the space temperature is within 2ºF of the effective heating setpoint.
The outdoor air damper normally is open to a minimum position during the
occupied mode when the controller turns on the supply fan. The damper
normally is closed during:
• warm-up/cooldown mode
• unoccupied mode
• certain diagnostic conditions
• low ambient damper lockout
• anytime the supply fan is off.
Morning warm-up can also be a communicated request from a Trane Tracer
Summit
receives a communicated morning warm-up request, heating mode is enabled
and the outdoor air damper closes. The controller remains in morning warm-up
until a different request is communicated.
Constant volume discharge air control or variable air volume control
In these modes, the Tracer AH.540 controller requires a space temperature input
(hardwired or communicated) and setpoint input (hardwired, communicated,
or default value) to initiate the morning warm-up sequence of operation.
On a transition from unoccupied to occupied (occupied bypass or occupied
standby) the controller compares the space temperature to the heating
setpoint. If the space temperature is 1.5° F below the heating setpoint, morning
warm-up is initiated. The outdoor air damper closes (or remains closed) and the
controller's heat/cool mode is heating.
The morning warm-up control sequence has no time limit upon a transition
from unoccupied to occupied, when the controller is configured for constant
volume discharge air control or variable air volume control modes.
Morning warm-up can also be a communicated request from a Trane Tracer
Summit
receives a communicated morning warm-up request, heating mode is enabled
and the outdoor air damper closes. The controller remains in morning warm-up
until a different request is communicated.
™
building automation system. When the Tracer AH.540 controller
™
building automation system. When the Tracer™ AH.540 controller
CNT-SVX05A-EN51
Page 58
Sequence of operation
Daytime warm-up
The daytime warm-up sequence is only available when the air handling unit has
heating capacity (hydronic or steam) and Tracer AH.540 is configured for:
• constant volume discharge air temperature control
• variable air volume control.
A communicated or wired space temperature is required for the Tracer AH.540
to initiate daytime warm-up.
Daytime warm-up forces the controller into heating when the space
temperature is below the effective heating setpoint by a temperature that is
more than the configured daytime warm-up enable differential. This initiated
sequence of operation coordinates the controller's heat/cool to heating, as well
as communicating the controller's application mode of operation to the duct
system for changeover.
Daytime warm-up start setpoint is a configurable temperature below the
effective space heating setpoint. When the space temperature drops below the
start setpoint the daytime warm-up function is initiated by the controller.
Daytime warm-up stop setpoint is a configurable temperature above the start
setpoint. When the space temperature rises above the stop setpoint, the warmup function is terminated by the controller.
Unlike morning warm-up, the outdoor air damper is at the configured minimum
position or at the communicated minimum damper position according to the
effective occupancy.
Cooldown
The controller configured for constant volume space temperature control closes
the outdoor air damper (when present) at every transition from unoccupied to
occupied mode when the space temperature is 3ºF or more above the cooling
setpoint.
The damper remains closed during cooldown until the space temperature is
within 2ºF of the effective cooling setpoint. The damper normally is closed
during:
• anytime the supply fan is off
• warm-up/cooldown mode
• unoccupied mode
• certain diagnostic conditions
• low ambient damper lockout.
Filter status
The controller’s filter status is based on the supply fan’s cumulative run hours.
The controller compares the fan run time against an adjustable fan run hours
limit (maintenance required setpoint time, stored in the controller) and
recommends unit maintenance as required. The Maintenance Required
diagnostic is informational only. Its state does not affect unit operation.
Use the Rover™ service tool to edit the Maintenance Required setpoint time.
When the setpoint limit is exceeded, the controller generates a Maintenance Required diagnostic. To disable the diagnostic feature, set the maintenance
required setpoint time to zero.
™
You can use Rover service tool or Tracer Summit
Required diagnostic. When the diagnostic is cleared, the controller resets the
fan run time to zero and resumes accumulating fan run hours.
Freeze avoidance
Freeze avoidance is used as low ambient temperature protection and is only
to clear the Maintenance
52CNT-SVX05A-EN
Page 59
Sequence of operation
initiated when the supply fan is off. The controller enters the freeze avoidance
mode when the outdoor air temperature is below the freeze avoidance setpoint
(configurable). The controller disables freeze avoidance when the outdoor air
temperature rises 3°F above the freeze avoidance setpoint. When the controller
is in freeze avoidance mode:
• all water valves are driven open to allow water to flow through the coil
• steam valves are cycled open and closed to prevent excessive cabinet
temperatures
• supply fan is off
• face and bypass damper (when present) is at full bypass
• freeze avoidance protects the air handling unit's hydronic heating and cooling
coils from freezing when cold outdoor air temperatures are present and the
supply fan is off.
Example: The Tracer AH.540 is not able to run the air handling unit because the
run/stop input is set to stop (supply fan is off). If the outdoor air temperature is
below the freeze avoidance setpoint, the Tracer AH.540 opens all water valves.
Tra ce r Su mm i t™ and Rover™ output overrides
The controller includes the capability to override both analog and binary outputs
(typically for test and commissioning) through Trane's Tracer Summit building
automation system or from Rover service tool. For more information on the
output overrides, refer to the product-specific literature for the building
automation system and the service tool.
The controller includes a Manual Output Test function which allows the user to
manually exercise the outputs in a predefined sequence. For more information,
refer to the Manual output test section.
Service override mode
The controller includes a Manual Output Test function which allows the user to
manually exercise the outputs in a predefined sequence from the Test push
button. The service override mode allows you to step through the Manual Output
Test remotely via Rover.
The Rover service tool communicates through the Comm5 link to place the
™
Trac er
can step the Tracer AH.540 controller through Manual Output Test sequence.
For more information, refer to the Manual output test section.
Emergency override
The Tracer AH.540 controller can be placed into emergency override via the
communication link. Emergency override allows a building automation system
such as Trane Tracer Summit to pressurize, depressurize, or purge the air from a
building space. It can also be used to shut down the controller’s operation of the
unit.
The emergency override command influences the controller's supply fan,
outdoor air damper, and exhaust fan to create the desired condition, as shown
in the following table.
AH.540 in service override mode. From the Rover computer screen you
Duct static pressure (when present) is always controlled when the supply fan is
running. Freeze avoidance in emergency override can force the heating and
cooling valves open.
Water valve override
To support water balancing, the controller includes a communication variable
(nviValveOverride) that allows a user to specify the desired state of all water
valves. The states supported are:
• Open all valves
• Close all valves
Water valve override remains active until the override is removed. The
controller resets itself if the variable is not refreshed within ten hours or any
other value except open or closed is written to it.
The Rover service tool or another communicating device is required to access
this feature.
54CNT-SVX05A-EN
Page 61
Calibration
With Rover™ service tool, you can calibrate two of the controller’s analog inputs:
space temperature, and setpoint. For each input, the calibration value is added
to the measured value to determine the effective value.
CNT-SVX05A-EN55
Page 62
Configuration
Configurable parameters
The Tracer™ AH.540 controller is factory configured and commissioned with
fixed sequences of operation. All of the controller's configuration parameters are
predefined and loaded based upon the air handling unit configuration. The Trane
Rover™ service tool provides access to these parameters to make adjustments
to the controller's operation.
The Tracer AH.540 contains configuration parameters for the air handling unit
type to select the type of control mode, cooling source, heating source, face and
bypass damper, and outdoor air damper. Refer to Table 30. The control mode
selects the desired unit operation: constant volume space temperature control,
constant volume discharge air temperature control, or variable air volume
control.
Table 31 — Tracer AH.540 unit type configuration parameters
Control modeTemperature control
• Constant volume
• Variable air volume
Table 32 — Heating and cooling source
Cooling sourceHeat type
None
Hydronic
Note 1: In a preheat unit configuration, the heating coil is located in the air stream before the cooling coil (when present).
In a reheat unit configuration, the heating coiling is located in the air stream after the cooling coil.
(Note 1)
• Preheat
• Reheat
• Space temperature
• Discharge air
Heat source Face and bypass
• Hot water
• Steam
damper
• None
• Face and
bypass damper
Outdoor air
damper
• None
• Outdoor air
damper
Table 33 — Analog outputs
Analog output
(Note 1)
AO 1Supply fan speed0 to 10VDC or
AO 2Cool output0 to 10VDC or
AO 3Heat output0 to 10VDC or
AO 4Face and bypass
AO 5Outdoor air damper 0 to 10VDC or
Note 1: Trane’s Rover service tool uses the unit type to determine and download the proper default analog output
configuration. For example, if you configure the controller's control mode to be constant volume space temperature
control, Rover will not allow AO 1 to be configured for a supply fan speed output. Analog output 1 (AO 1) is only used
when the controller is configured for variable air volume control.
Note 2: The normally open/closed configuration item refers to the inactive state of the end device, such as a cooling
valve. If the device is a normally open valve, the configuration for analog output 2 (AO 2) must be normally open.
Note 3: A normally face damper is positioned full coil face, and a normally bypass damper is full coil bypass when the
analog output is at oVDC.
FunctionOutput voltage
damper
range
2 to 10VDC
2 to 10VDC
2 to 10VDC
0 to 10VDC or
2 to 10VDC
2 to 10VDC
Valid range
(Note 2)
Normally slow or
Normally fast
Normally open or
Normally closed
Normally open or
Normally closed
Normally face or
Normally bypass
(Note 3)
Normally open or
Normally closed
Default value
0 to 10VDC
Normally open
2 to 10VDC
Normally closed
2 to 10VDC
Normally open
2 to 10VDC
Normally face
2 to 10VDC
Normally closed
56CNT-SVX05A-EN
Page 63
Configuration
Table 34 — Analog inputs
Analog inp ut
(Note 1)
IN 1Space temperature sensor +/-10.0°F (+/-5.7°C)
IN 2Hardwired setpoint+/-10.0
IN 3Fan mode switchNANA
IN 4Discharge air tempNANA
IN 5Outdoor air tempNANA
IN 6Mixed air tempNANA
Duct staticDuct static pressureNANA
Note 1: Trane’s Rover service tool uses the unit type to determine and download the proper default analog input
configuratio n.
Table 35 — Binary inputs
Binary input
(Note 1)
IN 7Low temp detect or
IN 8Run/stop or
IN 9Occupancy,
IN 10Supply fan status or
IN 11Filter status or
IN 12Exhaust fan status or
Note 1: Tr ane’s Rover service too l uses the un it type to determine and download th e proper def ault binar y input
configuratio n.
Note 2: When the supply fan is off, the state of the fan status device is its normal state. For example, if the fan status
switch (end device) is normally open when the fan is off, the controller should be configured for a normally open fan
status input.
Note 3: When the supply fan is off, the state of the filter status device is its normal state. For example, if the filter status
switch (end device) is normally closed when the fan is off, the controller should be configured for a normally closed
filter status input.
FunctionCalibration rangeDefault value
°F
(0.1
°F resolution)
°F (+/-5.7°C)
°F resolution)
(0.1
FunctionValid rangeDefault Configuration
Not used
Not used
generic or Not used
Not used
Not used
Not used
Normally open or
Normally closed
Normally open or
Normally closed
Normally open or
Normally closed
Normally open (Note 2) or
Normally closed (Note 2)
Normally open (Note 3) or
Normally closed (Note 3)
Normally open or
Normally closed
0
0
°F
Dependent on air handling
unit type
Run/stop
Normally open
Occupancy
Normally open
Sales order dependent
Sales order dependent
Sales order dependent
CNT-SVX05A-EN57
Table 36 — Outdoor air damper
ParameterValid rangeDefault value
Occupied outdoor damper minimum position0 to 100%15%
Occupied standby damper minimum position (Note 1) 0 to 100%0%
Economizer enable temperature (dry bulb)32°F to 122°F
Low ambient damper lock out temperature (Note 2)-40 to 32
(0°C to 50°C)
°F
(-40°C to 0°C)
60
°F (15.6°C)
-20°F (-28.9°C)
Outdoor air damper open time (Note 3)0 to 30 minutes5 minutes
Note 1: Occupied standby minimum damper position only applies to space temperature control operation.
Note 2: This is the outdoor air temperature below which the outdoor air damper will always be closed.
Note 3: Adjustable open time for the outdoor air damper to open from 0% to minimum position.
Table 37 — Exhaust fan or damper
ParameterValid rangeDefault value
Exhaust fan start setpoint (Note 1)0 to 100%26%
Exhaust fan stop differential (Note 1)0 to 100%10%
Note 1: The exhaust fan is energized when the outdoor air damper is equal to or greater than the exhaust fan start
setpoint. The exhaust fan is turned off when the outdoor air damper is less than the exhaust fan start setpoint minus
the exhaust fan stop differential.
Page 64
Configuration
Table 3 8 — Local zone sensor fan switch
ParameterValid rangeDefault
Local fan switch Enable or disableEnable
Table 3 9 — Space temperature setpoints
Default setpointValid range Default value
Occupied heating setpoint40 to 115°F (4.44 to 46.1°C)71°F (21.7°C)
Occupied cooling setpoint40 to 115
Occupied standby heating setpoint40 to 115
Occupied standby cooling setpoint40 to 115
Unoccupied heating setpoint40 to 115
Unoccupied cooling setpoint40 to 115
Heating setpoint low limit (Note 1)40 to 115
Cooling setpoint low limit (Note 1)40 to 115
Heating setpoint high limit (Note 1)40 to 115
Cooling setpoint high limit (Note 1)40 to 115
Thumbwheel setpointDisable or enableEnable
Note 1: The heating and cooling setpoint high and low limits only apply to the occupied and occupied standby setpoints
and are never applied to the unoccupied setpoints.
Table 4 0 — Discharge air setpoint limits for constant volume space
temperature control
LimitValid rangeDefault va lue
Disharge temperature setpoint high limit (Note 1)38 to 150°F
Disharge temperature setpoint low limit (Note 1)35 to 150
Note 1: When the Tracer AH.540 controller is configured for constant volume space temperature control (control mode),
the control algorithm is limited to calculating this high and low discharge air temperature setpoint.
°F (4.44 to 46.1°C)74°F (23.3°C)
°F (4.44 to 46.1°C)67°F (19.4°C)
°F (4.44 to 46.1°C)78°F (25.6°C)
°F (4.44 to 46.1°C)60°F (15.6°C)
°F (4.44 to 46.1°C)85°F (29.4°C)
°F (4.44 to 46.1°C)40°F (4.4°C)
°F (4.44 to 46.1°C)40°F (4.4°C)
°F (4.44 to 46.1°C)104°F (40°C)
°F (4.44 to 46.1°C)104°F (40°C)
104
(3.3 to 65.6
(1.7 to 65.6
°F
°C)
°C)
°F (40°C)
45
°F (7.2°C)
Table 4 1 — Discharge air temperature control setpoints and setpoint limits
SetpointValid rangeDefault value
Discharge air cooling setpoint32°F to 86°F
Discharge air heating setpoint50 to 158°F
Maximum discharge air cooling setpoint32°F to 86°F
Minimum discharge air cooling setpoint32°F to 86°F
Maximum discharge air heating setpoint32°F to 158°F
Minimum discharge air heating setpoint32°F to 158°F
(0°C to 30°C)
(10°C to 70°C)
(0°C to 30°C)
(0°C to 30°C)
(0°C to 70°C)
(0°C to 70°C)
55°F (12.8°C)
100
°F (37.8°C)
68
°F (20°C)
44.6
°F (7°C)
104
°F (40°C)
86
°F (30°C)
Table 4 2 — Daytime warm-up
ParameterValid rangeDefault va lue
Daytime warm-up start setpoint (Note 1)40 to 87.0°F
Daytime warm-up stop setpoint (Note 2)43 to 90
Note 1: When the space temperature is below the daytime warm-up start setpoint, the daytime warm-up sequence is
initiated.
Note 2: When the space temperature is above the daytime warm-up stop setpoint, the daytime warm-up sequence is
terminated.
(4.4 to 30.6
(6.1 to 32.2
°C)
°F
°C)
62
°F (16.7°C)
°F (21.7°C)
71
58CNT-SVX05A-EN
Page 65
Configuration
Table 4 3 — Duct static pressure
ParameterValid rangeDefault va lue
Duct static pressure high limit (Note 1)0 to 5 inches WC
Duct static pressure setpoint0 to 5 inches WC
Maximum duct static pressure setpoint0 to 5 inches WC
Minimum duct static pressure setpoint0 to 5 inches WC
Note 1: This is the pressure at which the controller shuts down the unit to prevent duct damage.
(0 to 1250 Pa)
(0 to 1250 Pa)
(0 to 1250 Pa)
(0 to 1250 Pa)
Table 4 4 — Mixed air temperature control low limit
ParameterValid rangeDefa ult value
Mixed air low limit setpoint (Note 1)-4°F to 104°F
Mixed air control sequence (Note 2)• None
Note 1: If the mixed air temperature reaches this low limit setpoint, the controller uses the configured mixed air control
sequence to maintain mixed air temperature above the configured mixed air low limit setpoint.
Note 2: The Tracer™AH.540 controller can be configured three different ways to control mixed air temperature above
the mixed air low limit temperature. If none is selected, the controller does not attempt to prevent low mixed air
temperature conditions. Low temperature detect provides unit freeze protection from a binary input freezestat (IN 7).
Mixed air control reduces the outdoor air damper minimum position to maintain mixed air temperature. The mixed air
preheat control sequence first attempts to use preheat (if available) to maintain mixed air temperature above the low
limit temperature. If preheat capacity cannot maintain the air handling unit's mixed air temperature above the
configured mixed air low limit temperature, the controller lowers the outdoor air damper below its minimum
ventilation position.
(-20°C to 40°C)
• Mixed air control
• Mixed air preheat control
4 inches WC
(1000 Pa)
1.5 inches WC
(375 Pa)
3 inches WC
(750 Pa)
0.5 inches WC
(125 Pa)
50°F (10°C)
Dependent on air
handler unit type
Table 4 5 — Supply fan status ignore time
ParameterValid rangeDefault value
Supply fan status ignore time (Note 1)0.0 to 6,553 seconds30 seconds
Note 1: This configuration property defines the maximum period of time the supply fan status binary input is ignored
after the control has started the supply fan.
Table 4 6 — Face and bypass heat modulation
ParameterValid rangeDefault value
Face and bypass heat modulation setpoint
(Note 1)
Note 1: This parameter is only used when a face and bypass damper is present. When the outdoor air temperature is
below this outdoor air temperature setpoint, the face and bypass damper is used to modulate the hydronic heat
capacity. When the outdoor air temperature rises to 3°F (1.67°C) above this setpoint, the heat valve is used to modulate
the hydronic heat capacity.
14 to 122°F
(-10 to 50°C)
40°F (4.4°C)
Table 4 7 — Freeze avoidance
ParameterValid range
Freeze avoidance setpoint (Note 1)32 to 122°F
Note 1: This setpoint defines the outdoor air temperature below which the controller starts the freeze avoidance
sequence.
Note 2: A freeze avoidance setpoint value outside the valid range disables the freeze avoidance function.
(Note 2)
(0 to 50°C)
Default value
35°F (1.67°C)
CNT-SVX05A-EN59
Page 66
Configuration
Table 4 8 — Steam valve cycling
ParameterValid rangeDefault value
Time period0 to 10 minutes5 minutes
Duty cycle (Note 1)0 to 100%25%
Valve open position (Note 2)0 to 100%25%
Note 1: Duty cycle is the percentage of the time period the steam valve is open.
Note 2: The steam valve open position can be set to a partially open position to prevent excessive steam coil
temperatures.
Table 4 9 — Tim ers
ParameterValid rangeDefault value
Power up control wait0 to 1,000 seconds300 seconds
Maintenance required time setpoint
(based on fan run hours)
Occupancy bypass timer (Note 1)
Space temperature control
Occupancy bypass timer (Note 1)
Discharge air control
Note 1: The occupied bypass time is used for timed override applications when a building automation system is not
present or when the building automation system does not send the occupied (override) request. The timed override
timer is maintained in the unit controller. When the timed override is applicable, the controller reports Occupied Bypass
as its effective occupancy mode.
Table 5 0 — Diagnostic alarm level
ParameterValid range Default value
Diagnostic alarm level (Note 1)• Service required
Note 1: Duct Static Pressure Failure, Duct Static Pressure High Limit, Space Temperature Failure, Discharge Air
Temperature Failure, Unit Shutdown, Low Temperature Detect, and Low Supply Fan Air Flow diagnostics can all be
configured as service required or critical alarm diagnostics. The diagnostics cannot be individually configured.
0 to 10,000 hours600 hours
0 to 240 minutes
(1 minute resolution)
0 to 24 minutes
(1 minute resolution)
• Critical alarm
120 minutes
0 minutes
Service required
Location identifier
The Tracer™ AH.540 includes unit configuration for a location identifier. The
maximum length of the location identifier is 30 characters. You can use Rover™
service tool to download this identifier and easily identify the unit based on its
physical location.
60CNT-SVX05A-EN
Page 67
Application information
Standalone
Occupied/unoccupied
You can configure the controller's binary input (IN 9) as an occupancy input to
switch between occupied and unoccupied modes of operation. When IN 9 is
configured as a normally open occupancy input, the standalone controller
switches to occupied mode when IN 9 contacts are open.
Timed override
The range for the timed override bypass time is 0 to 240 minutes (configurable).
The default value for the bypass time is 120 minutes.
The controller’s space temperature analog input generates timed override On
and Cancel requests in the following manner. The controller interprets a
momentary short of the space temperature analog input as a timed override On
request. The controller always accepts this timed override On request and
resets the bypass time. The controller only changes to occupied bypass if the
controller is in either the unoccupied or occupied standby mode. The controller
stays in the occupied bypass mode for the occupied bypass time or until
someone presses the zone sensor’s Cancel button.
The controller interprets a momentary fixed resistance of 1.5KΩ on the space
temperature analog input as a timed override Cancel request. The controller
always accepts the Cancel request and sets the bypass time to zero. The
controller only acts on a Cancel request during occupied bypass.
Morning warm-up and daytime warm-up
If the Tracer
temperature control or variable air volume control, a space temperature sensor
can be wired to the controller to provide the morning warm-up and daytime
warm-up sequence of operation. The space temperature and setpoint inputs are
used by the controller to determine if heating or cooling air should be supplied
to the space.
In heating, the controller creates a supply air temperature according to the
configured discharge air heating setpoint or communicated discharge air
heating setpoint input. In cooling, the controller maintains a supply air
temperature according to the configured discharge air cooling setpoint or
communicated discharge air cooling setpoint input. If a valid communicated
discharge air setpoint exists, the controller uses the communicated value.
Configuration
Use Rover™ service tool to modify any of the controller’s configuration
parameters. Refer to the literature supplied with the Rover service tool for more
information.
Setpoint operation
Standalone unit controllers can use two different stipend sources, the local
hardwired thumbwheel setpoint input or the default setpoints (nciSetpoints).
Use the thumbwheel setpoint input to provide the controller with a single
setpoint from which all other heating and cooling setpoints are derived.
™
AH.540 controller is configured for constant volume discharge air
CNT-SVX05A-EN61
Page 68
Application information
Standalone peer-to-peer
Trac er™ AH.540 controllers allow peer-to-peer (also referred to as master/slave)
data communication. Data such as space temperature, setpoint, and occupancy
can be shared from a master control to a peer control with or without the
presence of Tracer Summit
Figure 10 — Simple data sharing application
Master
Controller
Comm5 Link
Occupied/unoccupied
The controller’s occupancy generic binary input can be an occupancy input.
As an occupancy input, the standalone controller uses the binary input to switch
between occupied and unoccupied.
The master controller (the unit controller with the hardwired occupancy input)
in peer-to-peer communication can send its occupancy mode to one or more
slave controllers (so they all track each other's occupancy mode). For these
applications, you must use Rover™service tool to set up the controller.
Refer to the Rover service tool product literature for more information.
Timed override
Peer-to-peer timed override requires at least two controllers. The first controller,
commonly referred to as the master, passes occupancy information to other
controllers, commonly referred to as slaves.
The master controller’s space temperature analog input generates timed
override On and Cancel requests in the following manner. The master controller
interprets a momentary short (0.4 to 5 seconds) on the space temperature input
as a timed override On request. During unoccupied mode, the On request
places the master controller in occupied bypass mode until the occupied timer
expires or until someone presses the zone sensor Cancel button. When the
master controller’s occupancy mode is communicated to one or more slave
controllers, the slave controllers echo the master’s occupancy mode, including
both On and Cancel requests.
The controller interprets a momentary fixed resistance (0.4 to 25 seconds) of
1.5KΩ by the space temperature input as a timed override Cancel request.
During occupied bypass mode, the controller uses a Cancel request to return
the controller to unoccupied mode.
™
.
Zone
Sensor
Controller
SlaveSlave
Controller
62CNT-SVX05A-EN
Page 69
Application information
Setpoint operation
Controllers sharing information peer-to-peer, also referred to as master/slave,
can share a variety of data, including the heating/cooling setpoint
(communicated from a master to a slave).
Each controller derives its effective setpoint and default setpoints (including
deadbands between setpoints) from the setpoint input (hardwired or
communicated). To make sure the peer-to-peer setpoint application results
in identical setpoints for each communicating controller, each controller must
have exactly the same default setpoints.
The standalone master controller derives its setpoint from either the local
hardwired setpoint input (if present) or from its default setpoints. Peer-to-peer
applications often require the use of one hardwired setpoint to be shared
across two or more controllers. You can achieve this by wiring the adjustable
setpoint (typically included as a part of the Trane zone sensor module) to one
controller—defined as the master. Next, use Rover™ to set up the master and
one or more slaves to share that setpoint. For this application, each
communicating controller uses the same setpoint.
CNT-SVX05A-EN63
Page 70
Troubleshooting
Red Service LED
Table 51 — Red Service LED activity
Red LED ActivityDescription
LED is off continuously after power
is applied to the controller.
LED is on continuously, even when
power is first applied to the controller.
LED flashes approximately once
every second.
Test push button
The Test push button is located on the top right board edge of the Tracer
Normal operation.
Someone is pressing the Service push button or
the controller has failed.
Uninstall (normal controller mode). Use Rover™ service tool
to restore the unit to normal operation. Refer to the Rover
product literature for more information.
™
AH.540
controller. It is used to initiate and advance the controller through the manual
output test sequence. The manual output test sequence can be useful to verify
unit operation and wiring. See Manual output test in this manual for details.
Service push button
The Service push button is located on the top right board edge of the Tracer
AH.540 controller. It can be used to install the controller in a communication
network. Refer to the Rover service tool product literature for more information.
Warning! If the Service push button is held down for more than 15 seconds,
the controller will uninstall itself from the ICS communication network. This
mode is indicated by the red Service LED flashing once every second. Refer to
the previous section on Red Service LED for more information. Use the Rover
service tool to restore the unit to normal operation. Refer to the Rover product
literature for more information.
64CNT-SVX05A-EN
Page 71
Troubleshooting
Green Status LED
The green Status LED is normally used to indicate whether or not the controller
is powered On (24VAC).
Table 52 — Green Status LED activity
Green LED activityDescription
LED is on continuously.Power on (normal operation).
LED blinks (one blink).The controller is in manual output test mode. No diagnostic present.
LED blinks (two blinks).The controller is in manual output test mode.
LED blinks (1/4 second on,
1/4 second off for ten seconds).
LED off.Power is off.
Note 1: During manual output test, certain diagnostics make the status LED light in a two-blink pattern. Refer to the
diagnostics table for a list of two-blink diagnostics. If a two-blink pattern remains after an attempt to clear diagnostics,
the diagnostic condition is still present and may affect the manual output test. The diagnostic must then be cleared
using another m ethod. Refer to the section on Resetting diagnostics.
Note 2: The Wink feature allows you to identify a controller. By sending a request from Rover service tool, you can
request the controller to wink (blink on and off as a notification that the controller received the signal). The green LED
blinks (1/4 second on, 1/4 second off for ten seconds) during Wink mode.
Yellow Comm LED
The yellow Comm LED blinks at the rate the controller receives communication.
The yellow LED does not blink when the controller is transmitting
communication data.
One or more diagnostics is present (Note 1).
Wink mode
Controller failure.
Test button is pressed.
(Note 2).
Table 53 — Yellow Comm LED activity
Yellow LED activityDescription
LED off continuously. The controller is not detecting any communication
LED blinks or flickers.The controller detects communication (normal for communicating
LED on continuously.Abnormal condition or extremely high traffic on the link.
(normal for standalone applications).
applications, including data sharing).
Manual output test
The manual output test sequence (Table 53) verifies output and end device
operation. The manual output test can be conducted to verify output wiring
and actuator operation without using the Rover™service tool.
Many service calls are initiated due to unit diagnostics, so the test sequence
attempts to clear unit diagnostics and restore normal unit operation prior to
testing the outputs. If the diagnostics remain after an attempt to clear
diagnostics, the status LED lights in a two-blink pattern, indicating the
diagnostic condition is still present and may affect the manual output test.
See the Diagnostics section for information on which diagnostics cause a twoblink pattern.
Manual output test can also be useful for air balancing or water balancing.
As shown in Table 53, Step 4 of the manual output test opens the cool valve and
Step 5 opens the heat valve for water balancing. Step 4 can also be used for air
balancing. This step opens the cool valve, opens the outdoor air damper to the
minimum occupied position, and controls the duct static pressure at the duct
static pressure setpoint.
Manual output test can be terminated by advancing completely through the test
sequence. The controller will time out if the unit remains in a single step for ten
hours.
CNT-SVX05A-EN65
Page 72
Troubleshooting
Manual output test can be overridden by the following sequences:
• Power up sequence
• Manufacturing test
• Emergency override
Test sequence
The procedure for testing is:
• Press and hold the Test push button for at least two seconds. The green Status
LED turns off, confirming the Test button has been pressed. The Test push
button is located on the right top board edge of the Tracer
• Release the Test button to start the manual output test mode. The manual
output test is then in Step 1. The green Status LED blinks in one of two
patterns. If the Status LED blinks once, no diagnostics are present. If the
Status LED blinks twice, diagnostics are present
• Press the Test button (no more than once per second) to advance through
the test sequence
The manual output test can also be controlled over the communications
network using Rover. When conducting the manual output test via the
communications network, the sequence must start with Step 1 (Off), as shown
in Table 53. However, subsequent steps may be conducted in any order.
Table 54 — Manual output test sequence
Step (Note 1)Supply fan Cool
1: Off (Note 2)Off, 0%CloseCloseBypassCloseOff
2: Supply fan on,
slowest speed (Note 3)
Face and bypass full
face
3: Supply fan on, duct
static pressure control
4: Cool output open
Outdoor air damper
open to occupied
minimum position
5: Heat output open
Face and bypass
full face
Outdoor air damper
open to occupied
minimum position
6: Exhaust fan on
Outdoor air damper
full open
Face and bypass
full bypass
7: Exit (Note 4)
Note 1: The following diagnostics cause the Tracer AH.540 to exit manual output test:
• Duct Static Pressure High Limit
• Low Supply Fan Air Flow
• Low Temp Dete ct
• Unit Shutdown
Note 2: Upon entering manual output test mode, all outputs are turned off or closed. The Status LED blinks in a one-
blink pattern in the manual output test, or the Status LED blinks in a two-blink pattern if in the manual output test and
a diagnostic is present.
Note 3: At the beginning of Step 2, the controller attempts to reset all present diagnostics. If the controller is
unsuccessful clearing all diagnostics, the controller exits manual output test.
Note 4: After the last step, the test sequence performs an exit. This initiates a reset and attempts to return the controller
to normal operation.
Note 5: If the controller is configured to operate in variable air volume control, the controller runs duct static pressure
(DSP) control during Steps 3-6.
Note 6: If an exhaust fan status diagnostic occurs, the controller turns off the exhaust fan on this step.
On, 0%CloseCloseFaceCloseOff
On, DSP
(Note 5)
On, DSP
(Note 5)
On, DSP
(Note 5)
On, DSP
(Note 5)
output
CloseCloseFaceCloseOff
OpenCloseFaceOccupied
CloseOpenFaceOccupied
CloseCloseBypassOpenOn
Heat output Face and
bypass
damper
™
AH.540 controller
Outdoor air
damper
minimum
position
minimum
position
Exhaust fan
Off
Off
(Note 6)
66CNT-SVX05A-EN
Page 73
Troubleshooting
Minimum timers
The controller automatically exits the manual test mode after ten hours and
reverts back to normal operation. The outputs are not subject to minimum times
during the test sequence. However, the test sequence only permits one step per
second, which enforces a minimum output time.
Required inputs for unit operation
The following locally wired sensor or communicated inputs are required for each
listed control function. If any one of the sensors does not exist, the controller
operates the control function.
Table 5 5 — Required sensors
Control functionSensor(s) required to be
Variable air volume
control
Discharge air
temperature control
Space temperature
control
Economizer operationOutdoor air temperature
present - wired sensor or
communicated value
Duct static pressure
Discharge air temperature
Discharge air temperatureDiagnostic shutdown
Space temperature
Discharge air temperature
Mixed air temperature
Diagnostics
Three different types of diagnostics are generated by the Tracer™ AH.540
controller to help you troubleshoot abnormal unit operation.
Controller operation if
input is not pre sent
Diagnostic shutdown
Diagnostic shutdown
Diagnostic shutdown
Diagnostic shutdown
Economizer disabled
Economizer disabled
Table 5 6 — Diagnostic types
Critical alarmThe controller shuts down the unit to protect the air handling unit and avert
Service requiredThe controller disables certain sequences of operation only and attempts to
InformationalThis type of diagnostic does not affect controller operation.
possible damage, or the controller cannot operate until the diagnostic
condition is corrected.
maintain unit operation. For example, if the mixed air temperature sensor fails
or is not wired, the Tracer AH.540 controller disables (does not allow)
economizer operation.
Table 5 7 — Controller diagnostics
Diagnostic or Condition Control type
Low Temp Detect
(Notes 1, 6)
Duct Static Press
High Limit (Note 6)
Unit Shutdown
(Note 6)
Low Supply Fan Air Flow
(Note 6)
Dirty Filter
(informational)
configuration
CV Space temp control
CV Discharge air control
Variable air volume control
Variable air volume control OffValves Closed
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
Supply
fan
OffValves Open (hydronic)
OffValves Closed
OffValves Closed
Enabled Valves Enabled
Other outputs
(Enabled = Normal Operation)
Valves Cycled (steam)
Outdoor air damper Closed
Face and bypass damper Face
Exhaust fan Off
Outdoor air damper Closed
Face and bypass damper Bypass
Exhaust fan Off
Outdoor air damper Closed
Face and bypass damper Bypass
Exhaust fan Off
Outdoor air damper Closed
Face and bypass damper Bypass
Exhaust fan Off
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Enabled
CNT-SVX05A-EN67
Page 74
Troubleshooting
Table 56 – (continued) Controller diagnostics
Diagnostic or Condition Control type
Low Exhaust Fan Air Flow
(service required)
Discharge Air Temp Failure (Notes 2, 6)
Space Temperature Failure
(Notes 2, 6)
Space Temperature Failure
(service required)
(Notes 2, 5)
Outdoor Air Temp
Failure
(service required)
(Notes 2, 5)
Mixed Air Temp Failure
(service required)
(Note 2)
Maintenance Required
(informational)
Local Fan Switch Failure
(informational)
(Note 2)
Local Space setpoint Failure
(service required)
(Note 2)
Duct Static Press Failure
configuration
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp controlOffValves Closed
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
Invalid Unit Configuration
(service required)
(Note 6)
Normal
(informational)
Note 1: If the low temp detect device requires manual reset, reset the freezestat device first before resetting the
controller.
Note 2: When a local temperature, setpoint, or pressure sensor has failed after being valid, the controller generates a
diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid sensor
value is present (non-latching diagnostic).
Note 3: If the local outdoor air temperature sensor fails and a communicated value is not present, the outdoor air
damper is opened to mini mum positio n and econom izer oper ation is disabled.
Note 4: If the air handling unit's mixed air sensor fails or is not present, economizer operation is disabled and the
outdoor air damper is opened to minimum position.
Note 5: A space temperature failure diagnostic disables morning and daytime warm-up sequence of operation when
the controller is configured for constant volume discharge air control or variable air volume control.
Note 6: This diagnostic message can be configured as a service required or critical alarm.
CV Space temp control
CV Discharge air control
CV Space temp control
CV Discharge air control
Variable air volume control
CV Space temp control
CV Discharge air control
Variable air volume control
Supply
fan
Enabled Valves Enabled
OffValves Closed
Enabled Valves Enabled
Enabled Valves Enabled
Enabled Valves Enabled
Enabled Valves Enabled
Enabled Valves Enabled
Enabled Valves Enabled
Enabled Valves Enabled
OffValves Closed
Enabled Valves Enabled
Other outputs
(Enabled = Normal Operation)
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Off
Outdoor air damper Closed
Face and bypass damper Bypass
Exhaust fan Off
Outdoor air damper Closed
Face and bypass damper Bypass
Exhaust fan Off
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Enabled
Outdoor air damper Minimum position (Note 3)
Face and bypass damper Enabled
Exhaust fan Enabled
Outdoor air damper Minimum position (Note 4)
Face and bypass damper Enabled
Exhaust fan Enabled
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Enabled
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Enabled
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Enabled
Outdoor air damper Closed
Face and bypass damper Bypass
Exhaust fan Off
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Enabled
Outdoor air damper Closed
Face and bypass damper Bypass
Exhaust fan Off
Outdoor air damper Enabled
Face and bypass damper Enabled
Exhaust fan Enabled
68CNT-SVX05A-EN
Page 75
Troubleshooting
Translating multiple diagnostics
The controller senses and records each diagnostic independently of other
diagnostics. It is possible to have multiple diagnostics present simultaneously.
The diagnostics are reported in the order they occur. Each diagnostic has a
priority. When two diagnostic conditions exist, one diagnostic has priority over
the other.
Example: If a freezestat condition occurs (IN 7), the controller communicates
a Low Temp Detect diagnostic message, shuts down the air handling unit, and
opens all valves. If a stop input condition occurs (IN 8), the controller
communicates a Unit Shutdown diagnostic message but does not close the
valves. Since low temp detect is a higher priority diagnostic, a unit shutdown
diagnostic does not override the output conditions.
Priority of each diagnostic:
1. Low Temp Detect
2. Unit Shutdown
3. Low Supply Fan Air Flow
4. Low Exhaust Fan Air Flow
5. Space Temperature Failure ∗
6. Duct Static Press Failure ∗
7. Duct Static Press High Limit
8. Discharge Air Temp Failure ∗
9. Local Space setpoint Failure ∗
10. Local Fan Switch Failure ∗
11. Outdoor Air Temp Failure ∗
12. Mixed Air Temp Failure ∗
13. Dirty Filter ∗
14. Maintenance Required
15. Invalid Unit Configuration
∗ Non-latching diagnostics automatically reset when the input is
present and valid.
CNT-SVX05A-EN69
Page 76
Troubleshooting
Resetting diagnostics
A reset clears any latching diagnostics and allows the controller to try to run the
air handling unit normally. If the latching condition is still present, the controller
immediately shuts down the air handling unit. A reset will restart a unit that is
running normally. A reset is similar to cycling power to the unit.
There are many ways to reset unit diagnostics:
• Manual output test at the controller
• Cycling power to the controller
• Building automation system
• Rover™ service tool
• Any communicating device able to access the controller's diagnostic reset
input
• Zone sensor fan mode switch
Manual output test
You can use the Test button on the controller either during installation to verify
proper end device operation or during troubleshooting. When you press the Test
button, the controller exercises all outputs in a predefined sequence. The first
and last outputs of the sequence reset the controller diagnostics. Refer to the
Manual output test section.
Cycling power
When the controller's 24VAC power is turned off, then on, the unit cycles through
a power up sequence. By default, the controller attempts to reset all diagnostics
at power up. Diagnostics present at power up and those that occur after power
up are handled according to the defined unit diagnostics sequences (see the
previous Diagnostics table).
Building automation system
Some building automation systems can reset diagnostics in the controller.
For more complete information, refer to the product literature for the building
automation system.
Rover™ service tool
Rover service tool can reset diagnostics in the controller. For more complete
information, refer to the Rover product literature.
Diagnostic reset input
Any device that can communicate the network variable nviRequest (enumeration “clear_alarm") can reset diagnostics in the controller.
Zone sensor fan mode switch
When the zone sensor fan mode switch is changed from off to auto, the controller
attempts to reset all diagnostics. If the zone sensor fan mode switch has been
disabled by configuration, then the zone sensor fan mode switch is ignored and
it cannot be used to reset diagnostics.
70CNT-SVX05A-EN
Page 77
Troubleshooting
Questionable unit operation
Table 5 8 — Fan outputs do not energize
Probable causeExplan ation
Power up control wait When power up control wait is enabled (non-zero time), the controller
Unoccupied operation When the controller is in the unoccupied mode, the fan is cycled between
Fan mode offWhen a local fan mode switch (provided on the Trane zone sensor)
Requested mode offYou can communicate a desired operating mode (such as off, heat, and cool)
Diagnostic presentSpecific diagnostics affect fan operation. For more information,
No power to the
controller
Unit configurationThe controller must be properly configured based on the actual installed end
Manual output testThe controller includes a manual output test sequence you can use to verify
Unit wiringThe wiring between the controller outputs and the fan relays and contacts
remains off until one of two conditions occurs:
The controller exits power up control wait when it
receives communicated information.
The controller exits power up control wait when the power up
control wait time expires.
high speed and off with capacity to maintain zone temperature control.
determines the fan operation, the off position controls the unit off.
to the controller. When off is communicated to the controller, the unit controls
the fan off. There is no heating or cooling.
see the Diagnostics section.
If the controller does not have power, the unit fan does not operate.
For the controller to operate normally, it must have an input voltage of 24VAC.
When the green LED is off continuously, the controller does not have
sufficient power or has failed.
devices and application. When the unit configuration does not match the
actual end devices, the fan may not work correctly.
output operation and associated output wiring. However, based on the
current step in the test sequence, the unit fan may not be on.
Refer to the Manual output test section.
must be present and correct for normal fan operation.
Table 5 9 — Valves stay open
Probable causeExplan ation
Normal operationThe controller opens and closes the valves to meet the unit
Manual output testThe controller includes a manual output test sequence you can use to verify
Freeze avoidanceWhen the controller is in the unoccupied mode with no demand for capacity
Diagnostic presentSpecific diagnostics affect valve operation. For more information,
No power to the
controller
No power to the valves If the valve does not have power, a normally open valve remains open.
Unit configurationThe controller must be properly configured based on the actual installed end
Unit wiringThe wiring between the controller outputs and the valve(s) must be
capacity requirements.
output operation and associated output wiring. However, based on the
current step in the test sequence, the valve(s) may be open.
Refer to the Manual output test section.
(0%) and the outdoor air temperature is below the freeze avoidance setpoint,
the controller opens the water valves (100%) and the face and bypass damper
to prevent coil freezing.
see the Diagnostics section.
If the controller does not have power, a normally open valve remains open.
For the controller or valve to operate normally, it must have an input voltage
of 24VAC. When the green LED is off continuously, the controller does not
have sufficient power or has failed.
The valves are powered separately from the controller's output signal.
If the valves do not have 24VAC, the controller cannot operate the valves.
devices and application. When the unit configuration does not match the
actual end devices, the valves may not work correctly.
present and correct for normal valve operation.
CNT-SVX05A-EN71
Page 78
Troubleshooting
Table 6 0 — Valves stay closed
Probable causeExplan ation
Requested mode offYou can communicate a desired operating mode (such as off, heat, and cool)
Power up control wait When power up control wait is enabled (non-zero time), the controller
Manual output testThe controller includes a manual output test sequence you can use to verify
Fan mode offWhen a local fan mode switch (provided on the Trane zone sensor)
Diagnostic presentSpecific diagnostics affect valve operation. For more information,
No power to the
controller
No power to the valves If the valve does not have power, a normally open valve remains closed.
Unit configurationThe controller must be properly configured based on the actual installed end
Unit wiringThe wiring between the controller outputs and the valve(s) must be
to the controller. When off is communicated to the controller, the unit controls
the fan off. There is no heating or cooling (valves are closed).
remains off until one of two conditions occurs:
The controller exits power up control wait when it receives
communicated information.
The controller exits power up control wait when the power up
control wait time expires.
output operation and associated output wiring. However, based on the
current step in the test sequence, the valve(s) may not be open.
Refer to the Manual output test section.
determines the fan operation, the Off position controls the unit off and
closes the valves.
see the Diagnostics section.
If the controller does not have power, a normally open valve remains closed.
For the controller or valve to operate normally, it must have an input voltage
of 24VAC. When the green LED is off continuously, the controller does not
have sufficient power or has failed.
The valves are powered separately from the controller's output signal.
If the valves do not have 24VAC, the controller cannot operate the valves.
devices and application. When the unit configuration does not match the
actual end devices, the valves may not work correctly.
present and correct for normal valve operation.
Table 6 1 — Outdoor air damper stays open
Probable CauseExplanation
Normal operationThe controller opens and closes the outdoor air damper based on the control-
Manual output testThe controller includes a manual output test sequence you can use to verify
Unit configurationThe controller must be properly configured based on the actual installed end
Unit wiringThe wiring between the controller outputs and the outdoor air damper
ler's occupancy mode and fan operation. Normally, the outdoor air damper is
open during occupied, occupied standby, and occupied bypass mode when
the fan is running and closed during unoccupied mode unless the controller is
economizing. Refer to the Outdoor air damper section for more information.
output operation and associated output wiring. However, based on the
current step in the test sequence, the outdoor air damper may be open.
Refer to the Manual output test section.
devices and application. When the unit configuration does not match the
actual end devices, the outdoor air damper may not work correctly.
must be present and correct for normal outdoor air damper operation.
72CNT-SVX05A-EN
Page 79
Troubleshooting
Table 6 2 — Outdoor air damper stays closed
Probable causeExplan ation
Normal operationThe controller opens and closes the outdoor air damper based on the control-
Warm-up and cool
down
Unoccupied modeWhen the controller is in the unoccupied mode, the outdoor air damper
Low ambient damper
lock out
Requested mode offYou can communicate a desired operating mode (such as off, heat, and cool)
Power up control wait When power up control wait is enabled (non-zero time), the controller
Manual output testThe controller includes a manual output test sequence you can use to verify
Fan mode offWhen a zone sensor fan mode switch determines the fan operation,
No power to the
controller
Diagnostic presentSpecific diagnostics affect outdoor air operation. For more information,
Unit configurationThe controller must be properly configured based on the actual installed end
Unit wiringThe wiring between the controller outputs and the outdoor air damper
ler's occupancy mode and fan operation. Normally, the outdoor air damper is
open during occupied, occupied standby, and occupied bypass mode when
the fan is running and closed during unoccupied mode unless the controller is
economizing. Refer to the Outdoor air damper section for more information.
The controller includes both a morning warm-up and cool down sequence to
keep the outdoor air damper closed during the transition from unoccupied to
occupied. This sequence is an attempt to bring the space under control as
quickly as possible.
remains closed unless economizing is enabled.
When the outdoor air temperature is less than the low ambient damper
lockout setpoint (which can be changed with the Rover™ service tool),
the outdoor air damper is closed.
to the controller. When off is communicated to the controller, the unit controls
the fan off. There is no heating or cooling (valves are closed).
The outdoor air damper is closed.
remains off until one of two conditions occurs:
The controller exits power up control wait when it receives
communicated information.
The controller exits power up control wait when the power up
control wait time expires.
output operation and associated output wiring. However, based on the
current step in the test sequence, the outdoor air damper may not be open.
Refer to the Manual output test section.
the Off position controls the unit off and closes the outdoor air damper.
If the controller does not have power, the unit fan does not operate.
For the controller to operate normally, it must have an input voltage of 24VAC.
When the green status LED is off continuously, the controller does not
have sufficient power or has failed.
see the Diagnostics section in the manual.
devices and application. When the unit configuration does not match the
actual end devices, the outdoor air damper may not work correctly.
must be present and correct for normal damper operation.
CNT-SVX05A-EN73
Page 80
AppendixAppendix
Table 63 — Constant volume space temperature control operation based on the
effective heat/cool output
Applicatio n
mode input
(nviApplicMode)
AutoAutoDetermined by
Note 1: Heating capacity can be used to control the discharge air temperature to the discharge air setpoint.
Heat/cool mode input
(nviHeatCool)
HeatHeatFan Enabled
Morning warm-upMorning warm-upFan Enabled
CoolCoolFan Enabled
Night purgeNight purgeFan Enabled
Pre-coolPre-coolFan Enabled
OffOffFan Disabled
TestDetermined by
Emergency heatDetermined by
Fan onlyFan onlyFan Enabled
Effective heat
cool mode output
(nvoHeatCool)
controller
controller
controller
Unit Operation
Fan Enabled
Heating Enabled
Cooling Enabled
Damper Enabled
Note: This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when
the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
CFR 47, Part 15, Subpart A, Class B
Note: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and
on, the user is encouraged to try to correct the interference by one or more of
the following measures:
• Reorient or relocate the receiving antenna
• Increase the separation between the equipment and receiver
• Connect the equipment into an outlet on a circuit different from that to which
the receiver is connected
• Consult the dealer or an experienced radio/TV technician for help
CE radiated emissions
EN55022 Class A
Warning: This is a Class A product. In a domestic environment this product
may cause radio interference in which case the user may be required to take
adequate measures.
78CNT-SVX05A-EN
Page 85
Index
A
Active setpoint.....................................................................................................33
Address of Comm5 devices..............................................................................24
AH.540
Analog inputs................................................................................................8
Analog outputs .............................................................................................8
Zone temperature...............................................................................................16
CNT-SVX05A-EN87
Page 94
Page 95
Page 96
The Trane Company
An American Standard Company
www.trane.com
For more information contact
your local sales office or
e-mail us at comfort@trane.com
Literature Order Number CNT-SVX005A-EN
File NumberSV-UN-RT-SVX005-10-00
SupersedesNew
Stocking LocationLa Crosse
Since The Trane Company has a policy of continuous product and product data improvement,
it reserves the right to change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.