Trane TR1 Series VFD BACnet Installation And Operation Manual

TR1 Series VFD Variable Frequency Drive
BACnet
Installation and Operation Manual
175R5564
TR1-SVX03A-ENDecember, 2003
DANGER
CAUTION
!
!
Rotating shafts and electrical equipment can be hazardous. Therefore, it is strongly recommended that all electrical work conform to National Electrical Code (NEC) and all local regulations. Installation, start­up and maintenance should be performed only by qualified personnel.
Motor control equipment and electronic controls are connected to hazardous line voltages. When servicing drives and electronic controls, there will be exposed components at or above line potential. Extreme care should be taken to protect against shock. Stand on an insulating pad and make it a habit to use only one hand when checking components. Always work with another person in case of an emergency. Disconnect power whenever possible to check controls or to perform maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on electric control or rotating equipment.
WARNING
!
Warnings Against Unintended Start
1. While the drive is connected to the AC line, the motor can be brought to a stop by means of external switch closures, serial bus commands or references. If personal safety considerations make it necessary to ensure that no unintended start occurs, these stops are not sufficient.
2. During programming of parameters, the motor may start. Be certain that no one is in the area of the motor or driven equipment when changing parameters.
3. A motor that has been stopped may start unexpectedly if faults occur in the electronics of the drive, or if an overload, a fault in the supply AC line or a fault in the motor connection or other fault clears.
4. If the Local/Hand key is activated, the motor can only be brought to a stop by means of the Stop/Off key or an external safety interlock.
Electronic components of BACnet portal are sensitive to electrostatic discharge (ESD). ESD can reduce performance or destroy sensitive electronic components. Follow proper ESD procedures during installation or servicing to prevent damage.
Touching electrical parts may be fatal, even after equipment has been disconnected from AC line. To be sure that capacitors have fully discharged, wait 14 minutes for 208 V and 460 V units and 30†minutes for 600 V units over 25 HP after power has been removed before touching any internal component.
Copyright © 2003 American Standard, Inc. All rights reserved.
DANGER
!
Table of Contents
Introduction ............................................................................................................................ 5
About this manual ................................................................................................................. 5
Ordering information ............................................................................................................. 5
Installation requirements ...................................................................................................... 7
Wiring and terminal tightening specifications .................................................................... 7
Electrical wiring ..................................................................................................................... 8
Network connection............................................................................................................... 9
Termination switch settings .................................................................................................. 9
Network wiring ....................................................................................................................... 9
BACnet start up .................................................................................................................... 10
Changing parameter data ................................................................................................... 10
Ethernet network connection.............................................................................................. 11
Wiring ................................................................................................................................... 11
Set IP address of portal ....................................................................................................... 12
Set configuration jumpers on portal .................................................................................. 12
ARCnet network connection ............................................................................................... 13
EIA-485 network connection ............................................................................................... 14
EIA-232 network connection ............................................................................................... 15
Power up .............................................................................................................................. 16
Troubleshooting drive communication .............................................................................. 16
Troubleshooting Ethernet communication ........................................................................ 16
Loss of signal recovery time ............................................................................................... 16
Appendix A: BACnet POINT MAPPING TABLES for BACnet PORTAL .............................. 17
Appendix B: BACnet Communications Site Survey.......................................................... 22
3
Introduction
About this manual
The BACnet portal is a microprocessor based communication server that provides seamless translation between BACnet and Trane TR1 Series variable frequency drives. For TR1 Series VFD applications into Tracer Summit, BACnet/Ethernet and BACnet/IP are the supported connection types. The BACnet portal provides a dedicated Ethernet port and two serial communication ports which can be configured for two different protocols. Baud rates are software selectable and default to 9600 baud rate. Up to ten drives can be connected to a single BACnet portal.
The BACnet portal serves as a gateway to the Johnson Controls Metasys
®
N2 protocol resident in the TR1 Series VFD. The BACnet port operates with an internal BACnet server operating protocol through standard CAT 5 Ethernet cabling. The serial port (port 2) connection uses EIA-485, half duplex, 9600 baud, shielded twisted-pair wiring. Data points from the N2 protocol are mapped to Analog Value (AV) and Binary Value (BV) BACnet objects.
Appendix A at the back of this manual contains the drive point maps for BACnet.
The information in this manual is intended to provide comprehensive information on installation and set up of the TR1 Series VFD for communication over a BACnet network.
It is assumed that the user has knowledge of the capabilities of the BACnet network in addition to an understanding of the TR1 Series VFD. For specific information on operation of the drive, refer to the TR1 Series VFD Installation and Operation Manual, document number TR1-SVX10A-EN.
Ordering information
See Appendix B.
5
Ethernet
Port
Port 2 Configuration Jumpers
Port 2
Keypad/Display Port
DIP Switches
Power Switch
6"
1
/5"
485 - 4w
485 - 2w
2 wire 4 wire EIA-232
Net + Tx + Tx
Net -
n/c
n/c Rx - DCD/CTS
Signal Ground
Ethernet 10 baseT
BACnet
Assigned IP Address
EIA-232
EIA-485
VLTÆ BACLink
Tx - Rx
Rx + DTR/RTS
Power
Off On
Single Class 2
Source Only
24 VAC, 60-80 Hz
7.2VA, 0.3A Use Copper
Conductors Only
ô
Open Energy
Management Equipment
Ground
24 Vac
24 VAC
Portal Address Label
1
7
/
20
"
Port Connectors Label
N
O
1432
Keypad/Display
Port
Power Run Error
Port 1 Transmit Port 1 Receive Port 2 Transmit Port 2 Receive
Link Lan
IP Addr
Sw1
Port 1
Port 1
Connection
Port 2
Connection
Off/On
Default/Assigned ARC156/Other
Address +0 / +100
Access
Port
Format
Address
Format Button
10ës
1ës
Shield
Net -
Port 1
Net +
Addressing Rotary Switches
Port 1
Access Port
1"
LED Indicators
Figure 1. BACnet Portal
Power switch. Two position on/off power switch.
Portal address label. Identifies factory-set or default portal
addresses used in BACnet.
Port connectors label. Identifies factory-settings for communication ports 1 and 2. Default setting for port 1 is no connection. Default setting for port 2 is EIA-485 2-wire to drive.
24 VAC connector. Input power for BACnet module.
Format button. Not used.
Address rotary switches. Rotary switches used to set BACnet
portal network addresses. Set addresses 01-99 with DIP switch 5 in the +0 position. Set addresses 100-199 with DIP switch 5 in the +100 position.
Port 1. Preferred port for ARCnet connection. Selectable for ARCnet or 2-wire EIA-485. Set DIP switch 4 (Port 1) to Other to enable linking drives with EIA-485 wiring. Set DIP switch 4 (Port
1) to ARC156 for use as ARCnet connector. (See DIP switches.) This port is not used for Tracer Summit connection.
5
Depth: 1
/8"
LED indicators. Status indicator lights for functions as labeled.
Access port. Utility port for factory programming, set up, and to
assign the IP address. The access port cannot be used as a communication point or to download memory to the BACnet.
DIP switches. Two position switches used to enable selection of IP address, module address, and network type. Sw1 and Sw2 are disabled in TR1 Series VFD communication applications.
Keypad/Display port. Access port for optional keypad.
Port 2. Preferred port for EIA-485 connection to the drives. The
terminal is jumper selectable for 2-wire/4-wire EIA-485 or EIA-
232. Default setting is EIA-485 (2-wire).
Port 2 configuration jumpers. Jumper placement determines the configuration for EIA-485 (2-wire), EIA-485 (4-wire), or EIA-232 communication for Port 2. Default is EIA-485 2-wire.
Ethernet port. Ethernet network connector supports 10baseT network communication with BACnet.
6
Installation requirements
Wiring and terminal tightening specifications
Mount the BACnet enclosure as required using the predrilled mounting holes (see Figure 2). The unit weighs approximately
15.3 pounds (7 kg).
For BACnet portals ordered without an enclosure, mount the unit in an enclosed panel using the mounting holes provided on the BACnet portal backplate (refer back to Figure 1). Leave about 2 inches (5 centimeters) on each side for wiring access. In addition, the BACnet portal requires 24 VAC input power.
WARNING
!
BACnet portal is a Class 2 device (less than 30VAC, 100VA maximum). Take appropriate isolation measures when mounting BACnet portal in control panels where non-Class 2 devices (for example, 120VAC) or wiring are present.
Terminal tightening and wire specifications for the TR1 Series VFD are defined in Table I.
Total wiring length to connect up to 10 TR1 Series VFDs from the BACnet portal should not exceed 3,000 feet (900m) at 9600 baud rate.
Table I. Control Wiring and Torque
Specifications
Torque Specification
4.5 in-lbs (0.5 Nm) 18 – 24 AWG
Control Wiring 24 VAC Input Wiring
2
(0.75mm shielded twisted pair
2
– 0.2mm2)
22 AWG (0.3mm
)
11.00 [279.4]
12.22 [310.4]
0.31
[7.9]
4 PLCS.
9.00 [228.6]
12.22 [310.4]
4.21 [107.0]
Figure 2. BACnet Enclosure Dimensions
NOTE: Dimensions in inches [mm].
7
Electrical wiring
1. Power must be supplied to the 115 VAC outlet from an external source (see Figure 3).
2. Plug transformer into 115 VAC outlet.
3. Connect transformer cable to 24 VAC connector on BACnet board.
Figure 3. BACnet Portal Enclosure Electrical Components
8
Loading...
+ 15 hidden pages