Rotating shafts and electrical equipment can
be hazardous. Therefore, it is strongly
recommended that all electrical work
conform to National Electrical Code (NEC)
and all local regulations. Installation, startup and maintenance should be performed
only by qualified personnel.
Motor control equipment and electronic controls are connected to
hazardous line voltages. When servicing drives and electronic
controls, there will be exposed components at or above line
potential. Extreme care should be taken to protect against shock.
Stand on an insulating pad and make it a habit to use only one
hand when checking components. Always work with another
person in case of an emergency. Disconnect power whenever
possible to check controls or to perform maintenance. Be sure
equipment is properly grounded. Wear safety glasses whenever
working on electric control or rotating equipment.
WARNING
!
Warnings Against Unintended Start
1.While the drive is connected to the AC line, the motor can be
brought to a stop by means of external switch closures, serial
bus commands or references. If personal safety
considerations make it necessary to ensure that no
unintended start occurs, these stops are not sufficient.
2.During programming of parameters, the motor may start. Be
certain that no one is in the area of the motor or driven
equipment when changing parameters.
3.A motor that has been stopped may start unexpectedly if
faults occur in the electronics of the drive, or if an overload, a
fault in the supply AC line or a fault in the motor connection or
other fault clears.
4.If the Local/Hand key is activated, the motor can only be
brought to a stop by means of the Stop/Off key or an
external safety interlock.
Electronic components of BACnet portal are
sensitive to electrostatic discharge (ESD).
ESD can reduce performance or destroy
sensitive electronic components. Follow
proper ESD procedures during installation
or servicing to prevent damage.
Touching electrical parts may be fatal, even after equipment has
been disconnected from AC line. To be sure that capacitors have
fully discharged, wait 14 minutes for 208 V and 460 V units and
30†minutes for 600 V units over 25 HP after power has been
removed before touching any internal component.
Power up .............................................................................................................................. 16
Troubleshooting drive communication .............................................................................. 16
Troubleshooting Ethernet communication ........................................................................ 16
Loss of signal recovery time ............................................................................................... 16
Appendix A: BACnet POINT MAPPING TABLES for BACnet PORTAL .............................. 17
Appendix B: BACnet Communications Site Survey.......................................................... 22
3
Page 4
Introduction
About this manual
The BACnet portal is a microprocessor based communication
server that provides seamless translation between BACnet and
Trane TR1 Series variable frequency drives. For TR1 Series
VFD applications into Tracer Summit, BACnet/Ethernet and
BACnet/IP are the supported connection types. The BACnet
portal provides a dedicated Ethernet port and two serial
communication ports which can be configured for two different
protocols. Baud rates are software selectable and default to 9600
baud rate. Up to ten drives can be connected to a single BACnet
portal.
The BACnet portal serves as a gateway to the Johnson Controls
Metasys
®
N2 protocol resident in the TR1 Series VFD. The
BACnet port operates with an internal BACnet server operating
protocol through standard CAT 5 Ethernet cabling. The serial port
(port 2) connection uses EIA-485, half duplex, 9600 baud,
shielded twisted-pair wiring. Data points from the N2 protocol are
mapped to Analog Value (AV) and Binary Value (BV) BACnet
objects.
Appendix A at the back of this manual contains the drive point
maps for BACnet.
The information in this manual is intended to provide
comprehensive information on installation and set up of the TR1
Series VFD for communication over a BACnet network.
It is assumed that the user has knowledge of the capabilities of the
BACnet network in addition to an understanding of the TR1 Series
VFD. For specific information on operation of the drive, refer to the
TR1 Series VFD Installation and Operation Manual, document
number TR1-SVX10A-EN.
Ordering information
See Appendix B.
5
Page 5
Ethernet
Port
Port 2
Configuration
Jumpers
Port 2
Keypad/Display Port
DIP Switches
Power Switch
6"
1
/5"
485 - 4w
485 - 2w
2 wire 4 wire EIA-232
Net + Tx + Tx
Net -
n/c
n/c Rx - DCD/CTS
Signal Ground
Ethernet
10 baseT
BACnet
Assigned IP Address
EIA-232
EIA-485
VLTÆ BACLink
Tx - Rx
Rx + DTR/RTS
Power
OffOn
Single Class 2
Source Only
24 VAC, 60-80 Hz
7.2VA, 0.3A
Use Copper
Conductors Only
ô
Open Energy
Management Equipment
Ground
24 Vac
24 VAC
Portal Address Label
1
7
/
20
"
Port Connectors Label
N
O
1432
Keypad/Display
Port
Power
Run
Error
Port 1 Transmit
Port 1 Receive
Port 2 Transmit
Port 2 Receive
Link
Lan
IP Addr
Sw1
Port 1
Port 1
Connection
Port 2
Connection
Off/On
Default/Assigned
ARC156/Other
Address
+0 / +100
Access
Port
Format
Address
Format Button
10ës
1ës
Shield
Net -
Port 1
Net +
Addressing
Rotary Switches
Port 1
Access Port
1"
LED Indicators
Figure 1. BACnet Portal
Power switch. Two position on/off power switch.
Portal address label. Identifies factory-set or default portal
addresses used in BACnet.
Port connectors label. Identifies factory-settings for
communication ports 1 and 2. Default setting for port 1 is no
connection. Default setting for port 2 is EIA-485 2-wire to drive.
24 VAC connector. Input power for BACnet module.
Format button. Not used.
Address rotary switches. Rotary switches used to set BACnet
portal network addresses. Set addresses 01-99 with DIP switch 5
in the +0 position. Set addresses 100-199 with DIP switch 5 in the
+100 position.
Port 1. Preferred port for ARCnet connection. Selectable for
ARCnet or 2-wire EIA-485. Set DIP switch 4 (Port 1) to Other to
enable linking drives with EIA-485 wiring. Set DIP switch 4 (Port
1) to ARC156 for use as ARCnet connector. (See DIP switches.)
This port is not used for Tracer Summit connection.
5
Depth: 1
/8"
LED indicators. Status indicator lights for functions as labeled.
Access port. Utility port for factory programming, set up, and to
assign the IP address. The access port cannot be used as a
communication point or to download memory to the BACnet.
DIP switches. Two position switches used to enable selection of
IP address, module address, and network type. Sw1 and Sw2
are disabled in TR1 Series VFD communication applications.
Keypad/Display port. Access port for optional keypad.
Port 2. Preferred port for EIA-485 connection to the drives. The
terminal is jumper selectable for 2-wire/4-wire EIA-485 or EIA-
232. Default setting is EIA-485 (2-wire).
Port 2 configuration jumpers. Jumper placement determines
the configuration for EIA-485 (2-wire), EIA-485 (4-wire), or
EIA-232 communication for Port 2. Default is EIA-485 2-wire.
Ethernet port. Ethernet network connector supports 10baseT
network communication with BACnet.
6
Page 6
Installation requirements
Wiring and terminal tightening specifications
Mount the BACnet enclosure as required using the predrilled
mounting holes (see Figure 2). The unit weighs approximately
15.3 pounds (7 kg).
For BACnet portals ordered without an enclosure, mount the unit
in an enclosed panel using the mounting holes provided on the
BACnet portal backplate (refer back to Figure 1). Leave about 2
inches (5 centimeters) on each side for wiring access. In addition,
the BACnet portal requires 24 VAC input power.
WARNING
!
BACnet portal is a Class 2 device (less than
30VAC, 100VA maximum). Take appropriate
isolation measures when mounting BACnet
portal in control panels where non-Class 2
devices (for example, 120VAC) or wiring are
present.
Terminal tightening and wire specifications for the TR1 Series VFD
are defined in Table I.
Total wiring length to connect up to 10 TR1 Series VFDs from the
BACnet portal should not exceed 3,000 feet (900m) at 9600 baud
rate.
Table I. Control Wiring and Torque
Specifications
Torque
Specification
4.5 in-lbs (0.5 Nm) 18 – 24 AWG
Control Wiring 24 VAC Input Wiring
2
(0.75mm
shielded twisted pair
2
– 0.2mm2)
22 AWG (0.3mm
)
11.00
[279.4]
12.22
[310.4]
0.31
∅
[7.9]
4 PLCS.
9.00
[228.6]
12.22
[310.4]
4.21
[107.0]
Figure 2. BACnet Enclosure Dimensions
NOTE: Dimensions in inches [mm].
7
Page 7
Electrical wiring
1. Power must be supplied to the 115 VAC outlet from an
external source (see Figure 3).
2. Plug transformer into 115 VAC outlet.
3. Connect transformer cable to 24 VAC connector on
BACnet board.
DIP switches 2 and 3 on the main control board of the TR1 Series
VFD (see Figure 4) are used to configure the drive for N2 serial
bus termination. The switch position shown is the factory setting.
See Table II for setting information. The DIP switch are located
directly above terminals 61, 68 and 69 on the board.
Figure 4. TR1 Series VFD DIP Switch
1. Connect signal wires to drive terminal 68 (P+) and terminal
69 (N-) on main control board of drive (see figure 5).
2. If shielded cabling is used, connect one end of shield to
terminal 61. This terminal is connected to ground via an
internal RC link.
For additional wiring guidelines, see the procedures for specific
network-type connections in this manual.
NOTE
It is highly recommended to use shielded
twisted-pair wires to reduce electrical noise
on drive communications. Ensure that
drive is grounded properly according to
instructions in the drive manual.
61
68
69
COM
EIA-485
EIA-485
Figure 5. Network Wiring
Table II. DIP Switch Settings
SWITCH
SETTING
Switch 1 Reserved/No function
Switches 2 & 3 Used for terminating an EIA-485 interface. When
the drive is the first, last, or only device on a
network, switches 2 and 3 must be ON.
When the drive is in any other location on the
network, switches 2 and 3 must be OFF.
Switch 4 Not applicable with BACnet.
N(-)
P(+)
9
Page 9
BACnet start up
Changing TR1 series VFD parameter data
1.Use the TR1 drive keypad to access the Extended Menu
key and the 500 Group (serial communication) parameters
(see Changing TR1 series VFD parameter data).
2.Set parameters 500, 501 and 502 as shown in Table III
below.
Other settings may be changed to meet application requirements.
The settings shown will serve as a good starting reference.
Parameters 503 through 508 are options that select control of the
drive through the digital and/or the BACnet serial port. If Digitalinput is selected, the command can only be carried out through
digital input. If Serial communication is selected, the command can
only be carried out through serial communication. If Logic and is
selected, the command must be by both serial communication and
a digital input. If Logic or is selected, the command can be made
by either digital or serial communication.
Parameter 560, Override release time, sets the interval between
receiving messages that determine communication on the network
is stopped.
Refer to the TR1 Series VFD Installation and Operation Manual
for details on changing parameters and programming the drive.
Use the TR1 keypad to access the Extended Menu key and the
500 Group (serial communication) parameters. Enter or change
parameter data or settings in accordance with the following
procedure.
1. Press [Extend Menu] key.
2. Use t and u keys to find parameter group to edit.
3. Use [+] and [-] keys to find parameter you chose to edit.
4. Press [Change Data] key.
5. Use [+] and [-] keys to select correct parameter setting.
6. Press [Cancel] key to disregard change, or press [OK] key
to accept change and enter new setting.
7. Press [Display Mode] key to return to normal drive display.
Table III. Serial Communication Startup Parameter Settings
Parameter Name Setting
500 Protocol METASYS N2
501 Address 01
502 Baud rate 9600 BAUD (fixed at 9600 for N2 protocol)
503 Coasting LOGIC OR
504 DC brake LOGIC OR
505 Start LOGIC OR
506 Reversing DIGITAL INPUT
507 Select setup LOGIC OR
508 Select speed LOGIC OR
560 Override release time OFF
The values in
bold
are
default values.
10
Page 10
Ethernet network connection
Procedure
The Ethernet network connects directly to the BACnet Ethernet
portal (refer back to Figure 1). The connection is a 10baseT port.
Both Ethernet and Ethernet IP (BACnet IP) connect through this
connector.
To establish Ethernet communication with the BACnet portal and
TR1 drives, the following must be completed:
1. Wiring
2. Setting IP address of portal
3. For port 2 connection, setting port 2 configuration jumpers
Ethernet
Standard default
VLTÆ BACLink
1. Wiring
Wire Connections. Each BACnet portal can support up to 10
drives (see Figure 6).
The preferred portal-to-drive wiring is EIA-485 from port 2.
Connect portal Net+ to drive terminal 68 (+) and Net- to 69 (-).
Additional drives are connected pos-to-pos and neg-to-neg in
daisy chain fashion.
If required, port 1 can be factory-configured to connect the drives
through EIA-485.
ô
VLTÆ BACLink
ô
Optional factory setting
NOTE: EIA-485 (2-wire)
Net+ and Net- from Port 2
to drive input terminals
68 (+) and 69 (-)
EIA-485
EIA-485
Figure 6. Ethernet Network Connection
11
Page 11
NOTE
Steps 2 and 3 in the following connection
procedure may have already been factory-set
based upon customer ordering information.
Default IP address is 192.168.168.xxx.
Default subnet mask is 255.255.255.0.
Default gateway address is 0.0.0.0.
2. Set IP address of portal
C. Set BACnet portal address DIP switch. The BACnet
portal DIP switch 5 (refer back to Figure 7) must correspond to the
final portion of the IP address setting. Set the switch to +0 for
addresses 0to 99 or to +100 for addresses 100 to 199.
3. Set configuration jumpers on portal
See the port connector label attached to the BACnet portal for the
factory-configured port assignments (refer back to Figure 1).
A. Set IP address to default or assigned. The BACnet portal
has either an internal default Internet Protocol (IP) address or a
factory-set IP address assigned from customer input. See the label
attached to the portal for the IP address in either case (refer back
to Figure 1). An IP address must always be present for Ethernet
IP network communication. Set the IP address DIP switch (switch
3 in Figure 7) on the BACnet portal as either default or assigned.
(Switches 1 and 2 are disabled.)
Switch 1
Switch 2
IP Address
Port 1
Portal Address
1
Off/On
Off/ On
2
3
Default/ Assig ne d
ARC156/ Other
4
5
+0/ +100
Figure 7. BACnet Portal DIP Switches
B. Set BACnet portal default address. The default IP address
is 192.168.168.xxx. The xxx indicates the final portion of the IP
address which is set using the rotary switches on the BACnet
portal. The final portion of the address identifies the BACnet portal
with a unique address on the BACnet network. For example,
using the default address, Figure 8 shows the BACnet portal
address configured as 192.168.168.3. Set the user-assigned final
portion of the portal network address using the rotary switches.
Set port 2 configuration jumpers for communication type.
When using port 2 on the BACnet portal for communication with
the drives, set the port 2 configuration jumpers for EIA-485
(2-wire). Figure 9 illustrates the appropriate setting. EIA-485
(2-wire) is the factory default setting.
485-2w
485-4w
EIA-232
EIA-485
Figure 9. Port 2 Configuration Jumpers
When using port 1. Port 1 must be programmed for operation at
the factory based upon customer ordering data. When using
port1 on the BACnet portal for communication with the drives, set
the port 1 DIP switch (refer back to Figure 7) for ARC156 when
using an ARCnet interface to the drives or Other for EIA-485 or
additional options.
10's digit
0
9
8
7
6
1
2
3
4
5
8
7
Figure 8. Rotary Address Switches
12
1's digit
0
9
6
1
2
3
4
5
Page 12
ARCnet network connection
Procedure
EIA-485
NOTE: EIA-485 Net+
and Net- from Port 2
to drive input terminals
68 (+) and 69 (-)
ARCnet
VLT® BACLink
™
ARCnet
1. Switch BACnet portal power off.
2. Wire ARCnet network input cable to BACnet portal port1
(see Figure 10).
3. Set port 1 DIP switch to ARC156 (see Figure 11).
4. Plug EIA-485/232 configuration jumper to EIA-485 position
as shown in Figure 12.
5. Set portal device instance number using rotary address
switches (see Figure 13).
6. Set BACnet portal address DIP switch. BACnet portal DIP
switch 5 (refer back to Figure 1) must correspond to device
instance number setting. Set switch to +0 for addresses 0to
99 or to +100 for addresses 100 to 199.
7. Wire to drives from BACnet port 2 from Net (+) to drive
terminal 68 and Net (-) to drive terminal 69.
Switch 1
Switch 2
IP Address
Port 1
Portal Address
1
Off/ On
Off/ On
2
3
Default/ Assig ne d
ARC156/ Other
4
5
+0/ +100
NOTE: Terminate shield at only
one portal of a multiportal
network.
Shield
Por t 1
Net -
Net +
ARC156 Network
Figure 10. ARCnet Network Connection
Figure 11. BACnet Portal DIP Switches
EIA-232
EIA-485
Figure 12. Port 2 Configuration Jumper Settings
10's digit
0
9
8
7
6
1
2
3
4
5
1's digit
9
8
7
6
0
1
2
3
4
5
Figure 13. Rotary Address Switches
13
Page 13
EIA-485 network connection
Procedure
EIA-485
EIA-485
VLT® BACLink
1. Switch BACnet portal power off.
2. Wire EIA-485 network input cable to BACnet portal port1
(see Figure 14).
™
3. Set port 1 DIP switch to Other (see Figure 15).
4. Plug EIA-485/232 configuration jumper to EIA-485 position
EIA-485
as shown in Figure 16.
5. Plug EIA-485 configuration jumper to (2-wire) position as
shown in Figure 16.
7. Wire to drives from BACnet portal port 2 from Net (+) to
drive terminal 68 and Net (-) to drive terminal 69.
Switch 1
Switch 2
IP Address
Port 1
Portal Address
1
Off/On
Off/ On
2
3
Default/ Assig ne d
ARC156/ Other
4
5
+0/ +100
NOTE: EIA-485 (2-wire)
from Port 2 to drive input
terminals 68 (+) and 69 (-)
3. Set port 1 DIP switch to Other (see Figure 18).
4. Plug EIA-485/232 configuration jumper to EIA-232 position
EIA-485
as shown in Figure 19.
5. Wire to drives from BACnet portal port 2 from Net (+) to
drive terminal 68 and Net (-) to drive terminal 69.
Switch 1
Switch 2
IP Address
Port 1
Portal Address
1
Off/On
Off/ On
2
3
Default/ Assig ne d
ARC156/ Other
4
5
+0/ +100
Figure 17. EIA-232 Network Connection
Figure 18. BACnet Portal DIP Switches
EIA-232
EIA-485
Figure 19. Configuration Jumper Settings
15
Page 15
Power up
1. Turn BACnet portal power switch to OFF. This prevents
portal from power up before proper voltage is verified.
3. For TR1 VFD termination, DIP switches 2 and 3 should be
in the ON position. Termination DIP switches are located on
TR1 VFD power board directly above drive terminals
where connections to terminals 68 and 69 are made.
2. Ensure that power is applied to drives.
3. Plug connector from transformer to BACnet portal 24 VAC
power terminal.
4. Ensure that 24 VAC is present at BACnet portal power
input terminals.
5. Turn BACnet portal power switch to ON. Power, Run and
Error LEDs turn on. Run and Error LEDs then begin
blinking. Error LED turns off.
Troubleshooting drive communication
For use in the event of trouble communicating with the drives. Test
conditions for BACnet portal communications:
1. Test only one drive connected to portal at a time.
2. Portal power OFF.
Table IV. Troubleshooting Drive Communication
SYMPTOM CAUSE SOLUTION
Transmit LED ON steady
and receive LED OFF.
Transmit LED blinks slowly 3
times, then pauses and
repeats 3 blinks.
Reversed polarity to drive or short in
EIA-485 cable.
•
Drive not ON.
•
Drive not set for N2 protocol in
parameter 500.
•
Drive serial bus address not
correct in parameter 501.
•
Network cable not connected.
•
For TR1 VFD: termination
switches on drive in wrong
position.
Table V. Troubleshooting Ethernet Communication
SYMPTOM CAUSE SOLUTION
Link LED is OFF.
Lan LED is OFF.
Unable to see
BACnet objects.
•
Network speed set to
100kbps.
•
BACnet board not
connected to network.
•
Portal address not set
for network or not
recognized.
•
Bad network
connection.
•
Wrong device instance.
4. Drive power ON.
5. Apply power to BACnet portal and wait 20-25 seconds.
(See TableIV for test results.)
Troubleshooting Ethernet communication
With the BACnet portal connected to BACnet network through the
Ethernet connector, apply power to BACnet portal and switch
portal ON. See Table V for test results.
Loss of signal recovery time
When serial communication is lost to the drive, recovery time to
reestablish communication with the network can take up to
5minutes.
Reverse wires to drive terminals 68
(+) and 69 (-) or remove short.
•
Apply power to drive.
•
Set parameter 500 for N2
protocol.
•
Set drive address in
parameter 501.
•
Connect network cable to
unit.
•
Set termination switches 2
and 3 to ON position.
•
Set network speed for 10kbps.
•
Connect board to network.
•
Ping portal to test communications. To
ping portal, go to a DOS prompt on any
network computer. Type “ping” and the
portal address (displayed on the IP
address label on the unit) and press
enter. If communicating, you will get a
reply. If not communicating, you will get
no response indication.
•
Verify LED is lit at hub.
•
Use procedure outlined in BASPRB002-EN to perform Who-Is, I-Am on
BACnet.
16
Page 16
Appendix A
BACnet POINT MAPPING TABLES
for BACnet PORTAL
Binary Values to Drive
The following Binary Values are writeable for the BACnet client (Tracer Summit).
BACnet
REFERENCE NUMBER
coast_# Motor will coast freely to a stop.
Drive will not run in any mode
when coast is active.
start_# Provides a start command when
active. Motor will ramp to stop
when stop is active.
reset_# Allows resetting drive after a fault
that does not require cycling
power. Reset occurs at transition
from OFF to ON.
jog_# Used to start and run drive at a
frequency set in parameter 209.
relay_1_# Enables/disables high voltage
Form C relay when parameter 323
is set to
[29].
relay_2_# Enables/disables low voltage
Form A relay when parameter 323
is set to
[29].
reverse_# Changes motor direction of
rotation when parameter 506 is set
to a value other than
NOTE: # symbol represents drive ID number.
DESCRIPTION
Control Word Bit 11/12
Control Word Bit 11/12
Digital Input
RANGE
0=Coast stop
coast
0=Stop
0=Off
1=On
0=Off
1=On
0=Off
1=On
0=Off
1=On
0=Off
1=On
.
1=No
1=Start
The values in
bold
are
default values.
17
Page 17
Analog Values to Drive
The following Analog Values are writeable for the BACnet client (Tracer Summit).
BACnet
REFERENCE NAME
bus_ref_# Drive speed command
(open loop) or setpoint
(closed loop) via the
serial bus.
bus_feedback_# Drive feedback value
via the serial bus.
bus_feedback_2_# Second drive feedback
value via the serial bus.
NOTE: # symbol represents drive ID number.
DESCRIPTION
RANGE
0% to 100% N/A
0% to 100% 535
0% to 100%
PARA No.
536
Bus reference. When the drive is set for open loop operation in
parameter 100, the bus reference is the speed command to the
drive. In closed loop operation, bus reference is the drives
setpoint.
Bus feedback. This is the feedback signal provided to the drive
via the BACnet bus. The TR1 Series VFD can regulate two
feedback signals provided to the drive.
Range. Percentage of range between minimum reference
(parameter 204) and maximum reference (parameter 205).
Drive Settings
The following Analog Values are writeable for the BACnet client (Tracer Summit).
BACnet
REFERENCE NAME
reset_counter_# Resets kWh counter
active_setup_# Selects active setup 1 to 4 002
warn_feedback_low_# Warning low feedback -999,999.999 to FB
warn_feedback_high_# Warning high feedback FB low to
setpoint_1_# Set point 1 Min. FB to max. FB 418
setpoint_2_# Set point 2 Min. FB to max. FB 419
prop_gain_#
int_time_# PID integration time 0.01 to 9999.00 sec. 424
fb_filter_time_# Feedback filter time 0.01 to10.00 sec. 427
NOTE: # symbol represents drive ID number.
DESCRIPTION
PID proportional gain
RANGE
0=no reset
1=reset
high
999,999.999
0.00 to10.00 423
PARA NO.
618
227
228
The values in
18
bold
are
default values.
Appendix A
Page 18
Analog Values from Drive
The following Analog Values are readable for the BACnet client (Tracer Summit).
BACNet
Reference Name
reference_# % Reference in % between min and
feedback_# Par.
freq_# Hz Drive output frequency. 512
motor_curr_# Amp Current being supplied to motor. 514
power_# kW Power being supplied to motor. 515
motor_volt_# VAC Voltage being supplied to motor. 517
dc_bus_volt_# VDC DC bus voltage of drive. 518
therm_motor_load_# % Calculated thermal load on motor.
therm_inverter_load_# % Calculated thermal load on drive.
term_53_analog_# VDC Voltage value on analog input
term_54_analog_# VDC Voltage value on analog input
term_60_analog_# mA Current value on analog input
heatsink_temperature_#
operating_hours_# Hour Number of hours power applied to
run_hours_# Hour Number of hours drive applied
kwh_counter_# kWh Output power of drive in hours. 602
UNIT
415
C
°
DESCRIPTION
max reference. Speed reference in
open loop. Setpoint reference in
closed loop.
Feedback using the unit of measure
selected in parameter 415.
Trip point is 100%.
Trip point is 100%.
Terminal 53.
Terminal 54.
Terminal 60.
Drive heatsink temperature. 528
drive.
power to motor.
PARA NO.
509
511
519
520
522
523
524
600
601
NOTE: # symbol represents drive ID number.
Appendix A
19
Page 19
Binary Values from Drive
The following Binary Values are readable for the BACnet client (Tracer Summit).
Each BACnet portal can control and monitor any mix of TR1 Series VFDs up to a total of ten.
Use separate BACnet Communications Site Survey sheet for each portal.
NETWORK INFORMATION
BACnet can communicate over all of the following networks. Indicate the network that will be used.
*Ethernet IP*EthernetARCnet (156K twisted pair)
PTP over EIA-232 (RS-232)MSTP over EIA-485 (RS-485)
*Supported by Tracer Summit.
PORTAL CONFIGURATION
The following information is required to program the portal. Network number must be supplied in all cases.
Device Instance Number: ____________ Supply number for TR1 BACnet portal in all cases.
Ethernet IP
IP Network Number: ____________ Supply user's network number in all cases.
Use default IP address.
Default address range is: 192.168.168.001
Default Subnet Mask is: 255.255.255.0
Default Gateway Address is: 0.0.0.0