Trane TR150, TR170 Service Manual

Page 1
TR150 and TR170 Service Manual
February 2017
BAS-SVM04B-EN
BAS-SVM04B-EN
Page 2
Contents TR150 and TR170 Service Manual
Contents
1 Introduction
1.1 Purpose
1.2 Product Overview
1.3 Safety
1.4 Electrostatic Discharge (ESD)
1.5 Tools Required
1.6 Electrical Installation in General
1.6.1 Electrical Installation in General 10
1.7 Exploded Views – H Frame Size
1.8 Exploded Views - I Frame Size
1.9 Ratings
1.9.1 Short Circuit and Overcurrent Trips 17
1.9.2 DC Voltage Levels 17
2 Frequency Converter Control
2.1 Introduction
2.2 Status Messages
2.3 Frequency Converter Inputs and Outputs
6
6
6
6
6
9
10
11
14
17
18
18
18
18
2.3.1 Input Signals 18
2.3.2 Output Signals 19
2.4 Service Functions
2.5 Control Terminals
2.6 Control Terminal Functions
2.7 Grounding Shielded Cables
3 Internal Frequency Converter Operation
3.1 General
3.2 Description of Operation
3.2.1 Control Logic Section 23
3.2.2 Logic to Power Interface 24
3.2.3 Power Section 24
3.3 Sequence of Operation
3.3.1 Rectier Section 24
3.3.2 Intermediate Section 24
3.3.3 Inverter Section 25
3.3.4 Fan Speed Control 25
19
19
20
22
23
23
23
24
4 Troubleshooting
4.1 Troubleshooting Tips
4.2 Exterior Fault Troubleshooting
BAS-SVM04B-EN 02/2017 All rights reserved. 1
27
27
27
Page 3
Contents
4.3 Fault Symptom Troubleshooting
4.4 Visual Inspection
4.5 Fault Symptoms
4.5.1 No Display
4.5.2 Intermittent Display 30
4.5.3 Display (Line 2) Flashing 30
4.5.4 WRONG or WRONG LCP Shown
4.5.5 Motor Will Not Run 30
4.5.6 Incorrect Motor Operation 31
4.6 Warnings and Alarms
4.6.1 Alarms 32
4.6.2 Warnings 32
4.6.3 Warning And Alarm Messages
4.7 After Repair Tests
5 Frequency Converter and Motor Applications
5.1 Torque Limit, Current Limit, and Unstable Motor Operation
5.1.1 Overvoltage Trips 39
27
28
30
30
30
32
32
38
39
39
5.1.2 Mains Phase Loss Trips 40
5.1.3 Control Logic Problems 40
5.1.4 Programming Problems 40
5.1.5 Motor/Load Problems 41
5.2 Internal Frequency Converter Problems
5.2.1 Overtemperature Faults 41
5.2.2 Current Sensor Faults 41
5.2.3 Signal and Power Wiring Considerations for Electromagnetic Compatibility 41
5.2.4 Eects of EMI 42
5.2.5 Sources of EMI 42
5.2.6 EMI Propagation 43
5.2.7 Preventive Measures 44
6 Test Procedures
6.1 Non-repairable Units
6.2 Introduction
6.3 Static Test Procedures
6.3.2 Rectier Circuit Test 48
41
45
45
47
47
6.3.3 Inverter Section Tests 48
6.3.4 Intermediate Section Tests 49
6.3.5 Location of UDC Terminals 49
6.4 Dynamic Test Procedures
6.4.1 No Display Test (Display is Optional) 52
2 02/2017 All rights reserved. BAS-SVM04B-EN
52
Page 4
Contents TR150 and TR170 Service Manual
6.4.2 Input Voltage Test
6.4.3 Basic Control Card Voltage Test 53
6.4.4 Input Imbalance of Supply Voltage Test 53
6.4.5 Input Waveform Test
6.4.6 Output Imbalance of Motor Supply Voltage Test 54
6.4.7 Input Terminal Signal Tests 55
6.5 Initial Start-up Or After Repair Drive Tests
7 H-Frame Size Disassembly and Assembly Instructions
7.1 Electrostatic Discharge (ESD)
7.2 General Disassembly Procedure
7.3 H6 Frame Size Disassembly and Assembly Instructions
7.3.1 Control Card and Control Card Mounting Plate 57
7.3.2 Heat sink Fan Assembly 58
7.3.3 DC Coil 59
7.3.4 DC Link Card 59
7.3.5 RFI Filter 60
7.3.6 Power Card 60
52
53
56
57
57
57
57
7.4 H7 Frame Size Disassembly and Assembly Instructions
7.4.1 Control Card and Control Card Mounting Plate 61
7.4.2 Power Card 61
7.4.3 Inrush Card 62
7.4.4 RFI Filter 62
7.4.5 Relay Transducer Card 63
7.4.6 Rectier Modules 63
7.4.7 IGBT 63
7.4.8 Heat Sink Fan Assembly 64
7.4.9 DC Coil 65
7.4.10 Capacitor Bank 65
7.5 H8 Frame Size Disassembly and Assembly Instructions
7.5.1 Control Card and Control Card Mounting Plate 66
7.5.2 Power Card 66
7.5.3 Inrush Card 67
7.5.4 Rectier Modules 67
7.5.5 RFI Filter 68
61
66
7.5.6 Relay Transducer Card 69
7.5.7 IGBT 69
7.5.8 Heat Sink Fan Assembly 70
7.5.9 DC Coil 71
7.5.10 Capacitor Bank 71
7.6 H10 Frame Size Disassembly and Assembly Instructions
BAS-SVM04B-EN 02/2017 All rights reserved. 3
72
Page 5
Contents
7.6.1 Control Card and Control Card Mounting Plate
7.6.2 Power Card Cover 72
7.6.3 Power Card 73
7.6.4 Heat Sink and DC Coils
7.6.5 Heat Sink Fan Assembly 74
8 I-Frame Size Disassembly and Assembly Procedures
8.1 General Disassembly Procedure
8.2 I6 Frame Size Disassembly and Assembly Instructions
8.2.1 Control Card and Control Card Mounting Plate 75
8.2.2 Cable Mounting Plate 76
8.2.3 Heat Sink Fan Assembly 76
8.2.4 SMPS Card 77
8.2.5 Bus Bar Unit 77
8.2.6 Power Card 78
8.2.7 DC Coil 78
8.2.8 RFI Filter 79
8.3 I7 Frame Size Disassembly and Assembly Instructions
72
73
75
75
75
79
8.3.1 Control Card and Control Card Mounting Plate 79
8.3.2 Power Card 80
8.3.3 Power Card Mounting Plate 80
8.3.4 Inrush Card 81
8.3.5 Bus Bar 81
8.3.6 RFI Filter 82
8.3.7 Relay Transducer Card 82
8.3.8 Fan 83
8.3.9 Terminal Plate 83
8.3.10 DC Bus Bar Assembly 84
8.3.11 Heat Sink Fan Assembly 84
8.3.12 Capacitor Bank 85
8.3.13 DC Coil 85
8.3.14 IGBT 86
8.3.15 Thyristor 86
8.4 I8 Frame Size Disassembly and Assembly Procedure
8.4.1 Control Card and Control Card Mounting Plate 86
86
8.4.2 Power Card 87
8.4.3 Power Card Mounting Plate 88
8.4.4 Inrush Card 88
8.4.5 Bus Bar 89
8.4.6 RFI Filter 89
8.4.7 Relay Transducer Card 90
4 02/2017 All rights reserved. BAS-SVM04B-EN
Page 6
Contents TR150 and TR170 Service Manual
8.4.8 Terminal Plate
8.4.9 DC Bus Bar Assembly 91
8.4.10 Heat Sink Fan Assembly 91
8.4.11 Capacitor Bank
8.4.12 DC Coil 92
8.4.13 IGBT 93
8.4.14 Thyristor
9 Block Diagrams
9.1 Block Diagrams, Frame Sizes H and 9
9.1.1 H6 Frame Size 94
9.1.2 I6 Frame Size 95
9.1.3 H7, H8, I7, I8 Frame Size 96
9.1.4 H9 Frame Size 97
9.1.5 H10 Frame Size 98
Index
90
92
93
94
94
99
BAS-SVM04B-EN 02/2017 All rights reserved. 5
Page 7
Introduction
1
1Introduction
1.1 Purpose
This manual provides the technical information and instructions required, for a qualied technician approved by Trane to identify faults and perform repairs and maintenance on the frequency converter:
Data for the dierent enclosure sizes
Description of user interfaces and internal
processing
Troubleshooting and test instructions
Assembly and disassembly instructions
The manual applies to frequency converter models and voltage ranges described in Table 1.2 to Table 1 . 4 .
1.2 Product Overview
TR150 and TR170 frequency converters are designed for the Heating, Ventilation, and Air-Conditioning (HVAC) markets. They operate in variable torque mode, and include features suited for fan and pump applications within the HVAC market.
1.3 Safety
nected (linkage of DC intermediate circuit). There may be high voltage on the DC-link even when the LEDs are turned potentially live parts of the frequency converter, wait at least as stated in Table 1 . 1.
2. Before conducting repair or inspection, disconnect mains.
3.
4. During operation and while programming
5. When operating on a PM motor, disconnect
Volt age [V] Power range [kW ]
on the LCP does not disconnect mains.
[O]
parameters, the motor may start without warning. Press [Stop] when changing data.
motor cable.
3x200 0.25–3.7 4
3x200 5.5–11 15
3x400 0.37–7.5 4
3x400 11–90 15
3x600 2.2–7.5 4
3x600 11–90 15
Before touching any
o.
Minimum waiting
time (minutes)
CAUTION
Frequency converters contain dangerous voltages when connected to mains. Only qualied personnel should carry out the service. See also chapter 2.1 Introduction.
CAUTION
For dynamic test procedures, main input power is required and all devices and power supplies connected to mains are energized at rated voltage. Take extreme caution when conducting tests in a powered frequency converter. Contact with powered components could result in electrical shock and personal injury.
1. DO NOT touch electrical parts of the frequency converter when connected to mains. Also make sure that other voltage inputs have been discon-
Tab le 1.1 Dis c har ge Tim e
1.4 Electrostatic Discharge (ESD)
CAUTION
ELECTROSTATIC DISCHARGE
When performing service, use proper electrostatic discharge (ESD) procedures to prevent damage to sensitive components. Many electronic components within the frequency converter are sensitive to static electricity. The voltage of static electricity can reduce lifetime, sensitive electronic components.
performance, or completely destroy
aect
Do not touch components on the circuit boards.
Hold circuit boards by the edges or corners only.
6 02/2017 All rights reserved. BAS-SVM04B-EN
Page 8
Introduction TR150 and TR170 Service Manual
1.4.1 Frame Size Denitions
Model HP @200–240 V AC kW @200–240 V AC Frame Size IP Rating Repairable Yes/No
PK25 0.33 0.25 H1 IP20 No
PK37 0.5 0.37 H1 IP20 No
PK75 1.0 0.75 H1 IP20 No
P1K5 2.0 1.5 TR150: H1
TR170: H2
P2K2 3.0 2.2 H2 IP20 No
P3K7 5.0 3.7 H3 IP20 No
P5K5 7.5 5.5 H4 IP20 No
P7K5 10.0 7.5 H4 IP20 No
P11K 15.0 11.0 H5 IP20 No
P15K 20.0 15.0 H6 IP20 Yes
P18K 25.0 18.5 H6 IP20 Yes
P22K 30.0 22.0 H7 IP20 Yes
P30K 40.0 30.0 H7 IP20 Yes
P37K 50.0 37.0 H8 IP20 Yes
P45K 60.0 45.0 H8 IP20 Yes
Table 1.2 TR150 and TR170 Frequency Converters 200–240 V AC
IP20 No
1 1
BAS-SVM04B-EN 02/2017 All rights reserved. 7
Page 9
Introduction
1
Model HP @380–480 V AC kW @380–480 V AC Frame Size IP Rating Repairable Yes/No
PK37 0.5 0.37 H1 IP20 No
PK75 1.0 0.75 H1 IP20 No
P1K5 2.0 1.5 TR150:H1
TR170:H2
P2K2 3.0 2.2 H2 IP20 No
P3K0 4.0 3.0 H2 IP20 No
P4K0 5.0 4.0 H2 IP20 No
P5K5 7.5 5.5 H3 IP20 No
P7K5 10.0 7.5 H3 IP20 No
P11K 15.0 11.0 H4 IP20 No
P15K 20.0 15.0 H4 IP20 No
P18K 25.0 18.0 H5 IP20 No
P22K 30.0 22.0 H5 IP20 No
P30K 40.0 30.0 H6 IP20 Yes
P37K 50.0 37.0 H6 IP20 Yes
P45K 60.0 45.0 H6 IP20 Yes
P55K 70.0 55.0 H7 IP20 Yes
P75K 100.0 75.0 H7 IP20 Yes
P90K 125.0 90.0 H8 IP20 Yes
PK75 1.0 0.75 I2 IP54 No
P1K5 2.0 1.5 I2 IP54 No
P2K2 3.0 2.2 I2 IP54 No
P3K3 4.0 3.3 I2 IP54 No
P4K0 5.0 4.0 I2 IP54 No
P5K5 7.5 5.5 I3 IP54 No
P7K5 10.0 7.5 I3 IP54 No
P11K 15.0 11.0 I4 IP54 No
P15K 20.0 15.0 I4 IP54 No
P22K 25.0 18.0 I4 IP54 No
P11K 15.0 11.0 I5 IP54 No
P15K 20.0 15.0 I5 IP54 No
P22K 25.0 18.0 I5 IP54 No
P22K 30.0 22.0 I6 IP54 Yes
P30K 40.0 30.0 I6 IP54 Yes
P37K 50.0 37.0 I6 IP54 Yes
P45K 60.0 45.0 I7 IP54 Yes
P55K 70.0 55.0 I7 IP54 Yes
P75K 100.0 75.0 I8 IP54 Yes
P90K 125.0 90.0 I8 IP54 Yes
IP20 No
Table 1.3 TR150 and TR170 Frequency Converters 380–480 V AC
8 02/2017 All rights reserved. BAS-SVM04B-EN
Page 10
Introduction TR150 and TR170 Service Manual
Model HP @525–600 V AC kW @525–600 V AC Frame Size IP Rating Repairable Yes/No
P2K2 3.0 2.2 H9 IP20 No
P3K0 4.0 3.0 H9 IP20 No
P5K5 7.5 5.5 H9 IP20 No
P7K5 10.0 7.5 H9 IP20 No
P11K 15.0 11.0 H10 IP20 Yes
P15K 20.0 15.0 H10 IP20 Yes
P22K 30.0 22.0 H6 IP20 Yes
P30K 40.0 30.0 H6 IP20 Yes
P45K 60.0 45.0 H7 IP20 Yes
P55K 70.0 55.0 H7 IP20 Yes
P75K 100.0 75.0 H8 IP20 Yes
P90K 125.0 90.0 H8 IP20 Yes
Table 1.4 Repairable Yes/No Frequency Converters 525–600 V AC
1.5 Tools Required
Quick Guide for TR150 and TR170.
ESD Protection Kit Wrist strap and Mat
Metric socket set 7–19 mm
Torque wrench 0.5 N · m to 19 N · m
Socket extensions 100–150 mm (4 in and 6 in)
Torx driver set T10-T50
Needle nose pliers
Magnetic sockets
Ratchet
Screwdrivers Standard and Philips
1 1
Table 1.5 Required Tools
Additional Tools Recommended for Testing
Digital voltmeter/ohmmeter (must be rated for
1000 V DC for 600 V units)
Analog voltmeter
Oscilloscope
Clamp-on style ammeter
BAS-SVM04B-EN 02/2017 All rights reserved. 9
Page 11
Introduction
1
1.6 Electrical Installation in General
1.6.1 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper conductors are required. 75 °C (167 °F) is recommended. For TR170 drives operating in ambients over 50 °C (122 °F), copper conductors rated 80 °C (176 °F) or higher are recommended.
Power [kW (hp)] Torque [N · m (in-lb)]
Enclosure
size
TR150
H1 IP20 0.25–1.5
H2 IP20 2.2 (3) 2.2–4.0 (3–5) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
H3 IP20 3.7 (5) 5.5–7.5 (7.5–10) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
H4 IP20 5.5–7.5 (7.5–10) 11–15 (15–20) 1.2 (11) 1.2 (11) 1.2 (11) 0.5 (4) 0.8 (7) 0.5 (4)
H5 IP20 11 (15) 18.5–22 (25–30) 1.2 (11) 1.2 (11) 1.2 (11) 0.5 (4) 0.8 (7) 0.5 (4)
H6 IP20 15–18.5 (20–25) 30–45 (40–60) 4.5 (40) 4.5 (40) 0.5 (4) 3 (27) 0.5 (4)
H7 IP20 22–30 (30–40) 55 (70) 10 (89) 10 (89) 0.5 (4) 3 (27) 0.5 (4)
H7 IP20 75 (100) 14 (124) 14 (124) 0.5 (4) 3 (27) 0.5 (4)
H8 IP20 37–45 (50–60) 90 (125)
TR170
H2 IP20 1.5 (2) 1.5 (2) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
IP class 3x200–240 V 3x380–480 V Mains Motor DC
connection
0.37–1.5 (0.5–2) 0.8 (7) 0.8 (7) 0.8 (7) 0.5 (4) 0.8 (7) 0.5 (4)
(0.33–2)
24 (212)
1)
24 (212)
1)
Control
terminals
0.5 (4) 3 (27) 0.5 (4)
Ground Relay
Table 1.6 Tightening Torques for Enclosure Sizes H1–H8, 3x200–240 V & 3x380–480 V
Power [kW (hp)] Torque [N · m (in-lb)]
Enclosure
size
TR150
H9 IP20 2.2–7.5 (3–10) 1.8 (16) 1.8 (16) Not
H10 IP20 11–15 (15–20) 1.8 (16) 1.8 (16) Not
H6 IP20 18.5–30 (25–40) 4.5 (40) 4.5 (40) 0.5 (4) 3 (27) 0.5 (4)
H7 IP20 37–55 (50–70) 10 (89) 10 (89) 0.5 (4) 3 (27) 0.5 (4)
H8 IP20 75–90 (100–125) 14 (124)/24
Table 1.7 Tightening Torques for Enclosure Sizes H6–H10, 3x525–600 V
1) Cable dimensions >95 mm
2) Cable dimensions ≤95 mm
IP class 3x525–600 V Mains Motor DC
connection
recommended
recommended
14 (124)/24
2)
(212)
2
2
(212)
2)
Control
terminals
0.5 (4) 3 (27) 0.6 (5)
0.5 (4) 3 (27) 0.6 (5)
0.5 (4) 3 (27) 0.5 (4)
Ground Relay
10 02/2017 All rights reserved. BAS-SVM04B-EN
Page 12
Introduction TR150 and TR170 Service Manual
1.7 Exploded Views – H Frame Size
NOTICE
Non-repairable units are not shown with exploded views.
1 1
1 Blind cover 10 Filter protection cover
2Front cover LCP 11RFIlter
3Cradle 12EMC shield
4 Control card 13 Bus bar unit
5 Control card mounting plate 14 Heat sink fan assembly
6 DC coils 15 Connector
7 Coil mounting plate 16 DC coil cover
8 Coil mounting plate 17 Capacitor bank metal cover
9 DC link card 18 Capacitor vibration support
Illustration 1.1 Exploded View - H6 Frame Size
BAS-SVM04B-EN 02/2017 All rights reserved. 11
Page 13
1
Introduction
1 Blind cover 13 Relay/transducer card mounting plate
2 LCP 14 DC coil cover plate
3Front cover 15Bus bar
4EMC shield 16Plastic cover
5 Cradle 17 Rectier modules
6 Control card 18 Heat sink fan assembly
7 Control card mounting plate 19 DC coils
8Power card 20Capacitors
9 Power card mounting plate 21 Base plate
10 RFI lter 22 Relay/transducer card
11 EMC shield 23 IGBT
12 Inrush card 24 Cable mounting plate
Illustration 1.2 Exploded View - H7 Frame Size
12 02/2017 All rights reserved. BAS-SVM04B-EN
Page 14
Introduction TR150 and TR170 Service Manual
1 1
1LCP 12SMPS card
2 Front cover 13 Cable mounting plate
3 Cradle, control card, and mounting plate 14 IGBT
4 EMC shield 15 Relay/transducer card mounting plate
5 Power card 16 Relay/transducer card
6 Power card mounting plate 17 Bus bar
7 Support bracket 18 Rectier modules
8 Plastic cover 19 Heat sink fan assembly
9 RFI lter 20 Capacitors
10 DC coil cover plate 21 Base cover
11 Bus bar unit 22 Connection terminals
Illustration 1.3 Exploded View - H8 Frame Size
BAS-SVM04B-EN 02/2017 All rights reserved. 13
Page 15
Introduction
1
1.8 Exploded Views - I Frame Size
1 Local Control Panel (LCP) 9 DC coil
2Front cover 10Heat sink
3 Cradle 11 Fan assembly
4 Control card 12 Cable mounting plate
5 Control card mounting plate 13 RFI lter
6 Fan 14 Connectors
7 Bus bar unit 15 EMC shield
8 Power card 16 Cable entry
Illustration 1.4 Exploded View - I6 Frame Size
14 02/2017 All rights reserved. BAS-SVM04B-EN
Page 16
Introduction TR150 and TR170 Service Manual
1 1
1 Local Control Panel (LCP) 14 DC coil
2 Front door 15 Thyristors
3 Cradle 16 Back plate
4 Control card 17 IGBT
5 Control card mounting plate 18 Capacitor
6 Terminal plates 19 Heat sink fan
7 Support bracket 20 Bus bar unit
8 RFI lter 21 Relay/transducer card
9 Inrush card 22 Relay card mounting plate
10 Terminal connectors 23 Power card
11 Cable mounting plate 24 Power card mounting plate
12 Bus bar 25 Cable entry
13 Bracket
Illustration 1.5 Exploded View - I7 Frame Size
BAS-SVM04B-EN 02/2017 All rights reserved. 15
Page 17
1
Introduction
1LCP 11DC coil
2 Front cover 12 Rectier modules
3Cradle 13IGBTs
4LCP gasket 14Capacitors
5 Control card 15 Heat sink fan assembly
6 Control card mounting plate 16 Fan
7 Support bracket 17 Cable mounting plate
8 RFI lter 18 Relay/transducer card with mounting plate
9 Power Card 19 Cable entry
10 Power card mounting plate
Illustration 1.6 Exploded View - I8 Frame Size
16 02/2017 All rights reserved. BAS-SVM04B-EN
Page 18
Introduction TR150 and TR170 Service Manual
1.9 Ratings
1.9.1 Short Circuit and Overcurrent Trips
The frequency converter is protected against short circuits with current measurement in each of the 3 motor phases or in the DC link. A short circuit between 2 output phases causes an overcurrent in the inverter. The inverter turns o the IGBTs individually when the short-circuit current exceeds the permitted value (Alarm 16 Trip Lock).
1.9.2 DC Voltage Levels
200–240 V AC 380–480 V AC 525–600 V AC
H1–H5 H6–H8 H1–H5
I2–I3–I4
Inrush circuit enabled
Inrush circuit disabled 202 184 314 372 532
Undervoltage 202 184 314 372 532
Undervoltage re-enable 202+15 184+16 314+30 372+24 532+20
Overvoltage 410 412 800 800 976
Overvoltage re-enable 410-15 412-16 800-30 800-24 976-20
IT Grid Turn on 410+25 412+25 800+35 800+35 976+35
Table 1.8 DC Voltage Levels
H6–H8
I6–I8
H6–H10
1 1
BAS-SVM04B-EN 02/2017 All rights reserved. 17
Page 19
Frequency Converter Control
2 Frequency Converter Control
2
2.1 Introduction
This section describes the optional display interfaces available for the frequency converter, the inputs and outputs, and the control terminal functions.
The following optional interfaces are available:
Numerical Local Control Panel (LCP 21).
Graphical Local Control Panel (GLCP or LCP 102).
Use the selected interface to adapt parameter settings or read status. Commands given to the frequency converter are indicated on the selected interface display. Fault logs are maintained within the frequency converter, for fault history. The frequency converter issues warnings and alarms for fault conditions arising within or external to the frequency converter itself. Usually, the fault condition is found outside of the frequency converter.
2.2 Status Messages
Status messages appear in the bottom of the display. The left part of the status line indicates the active operation model of the frequency converter.
The center part of the status line indicates the references site. The last part of the status line gives the operation status, for example:
Running.
Stop.
Standby.
Other status messages may appear and are related to the software version and frequency converter type.
2.3 Frequency Converter Inputs and Outputs
The frequency converter operates by receiving control input signals. The frequency converter can also output status data or control auxiliary devices.
Control input is sent to the frequency converter in 3 ways:
Via the optional LCP connected by cable to the
frequency converter, operating in [Hand On] mode. These inputs include start, stop, reset, and speed reference.
Via serial communication from a eldbus,
connected to the frequency converter through the RS485 serial port, or through a communi­cation option card. The serial communication protocol:
- Supplies commands and references to the frequency converter.
- Programs the frequency converter.
- Reads status data from the frequency
converter.
Via signal wiring connected to the frequency
converter control terminals. Improperly connected control wiring can result in the frequency converter failing to start or to respond to a remote input.
2.3.1 Input Signals
The frequency converter can receive 2 types of remote input signals: digital or analog. Digital inputs are wired to terminals 18, 19, 20 (common), 27, 29. Analog or digital inputs are wired to terminals 53 or 54 and 55 (common). A switch placed under the LCP sets the terminal functions. Some options include additional terminals.
Analog signals can be either voltage (0 V to +10 V DC) or current (0–20 mA or 4–20 mA). Analog signals can be varied like dialing a rheostat up and down. The frequency converter can be programmed to increase or decrease output in relation to the amount of current or voltage. For example, a sensor or external controller may supply a variable current or voltage. The frequency converter output, in turn, regulates the speed of the motor connected to the frequency converter in response to the analog signal.
Digital signals are a simple binary 0 or 1 acting as a switch. A 0-24 V DC signal controls the digital signals. A voltage signal lower than 5 V DC is a logic 0. A voltage higher than 10 V DC is a logic 1. 0 is open, 1 is close. Digital inputs to the frequency converter are switched commands such as start, stop, reverse, coast, reset. (Do not confuse these digital inputs with serial communication formats where digital bytes are grouped into communication words and protocols).
The RS485 serial communication connector is wired to terminals (+) 68 and (-) 69. Terminal 61 is a common terminal. It is used for terminating shields only when the control cable is run between frequency converters, and not between frequency converters and other devices.
Parameters for NPN and PNP.
These parameters cannot be changed while the motor is running.
conguring
the input and output using
18 02/2017 All rights reserved. BAS-SVM04B-EN
Page 20
Frequency Converter Control TR150 and TR170 Service Manual
2
2.3.2 Output Signals
The frequency converter also produces output signals that are carried either through the RS485 serial bus or terminal
42. Output terminal 42 operates in the same manner as the inputs. The terminal can be programmed for either a variable analog signal in mA or a digital signal (0 or 1) in 24 V DC. In addition, a pulse reference can be provided on terminals 27 and 29. Output analog signals generally indicate the frequency, current, torque, and so on, to an external controller or system. Digital outputs can be control signals used to open or close a damper, or send a start or stop command to auxiliary equipment.
Additional terminals are Form C relay outputs on terminals 01, 02, and 03, and terminals 04, 05, and 06.
Terminals 12 and 13 provide 24 V DC low voltage power, often used to supply power to the digital input terminals (18–33). Those terminals must be supplied with power from either terminal 12 or 13, or from a customer supplied external 24 V DC power source. Improperly connected control wiring is a common service issue for a motor not operating or the frequency converter not responding to a remote input.
Number of digital outputs 2
Ter mina l nu m ber
Voltage level at digital output 17 V
Maximum output current at digital
output
Maximum load at digital output
42, 45
20 mA
Ω
1 k
1)
See the Quick Guide for detailed information on accessing and showing parameters, and for descriptions and procedures for service information available in parameter group 6-** Analog In/Out.
2.5 Control Terminals
For proper function of the frequency converter functioning, the input control terminals must be:
Wired properly.
Powered.
Programmed correctly for the intended function.
Ensure that the input terminal is wired correctly:
1. Conrm that the control and power sources are wired to the terminal.
2. Check the signal in either of 2 ways:
Press [Display Mode], then select Digital
Input. The LCP shows the digital inputs which are correctly wired.
Use a voltmeter to check for voltage at
the control terminal.
Conrm that each control terminal is programmed for the correct function. Each terminal has specic functions and a numbered parameter associated with it. The setting selected in the parameter enables the function of the terminal.
See the Quick Guide for details on changing parameters and the functions available for each control terminal.
2
Table 2.1 Digital Output
1) Terminals 42 and 45 can also be programmed as analog output.
2.4 Service Functions
Service information for the frequency converter can be shown in display lines 1 and 2. 24 dierent items can be accessed. Included in the data are
Counters that tabulate hours run, and so on.
Fault logs that store frequency converter status
values present at the ten most recent events that stopped the frequency converter
Frequency converter nameplate data
Parameter 14-28 Production Settings and parameter 14-29 Service Code, are the relevant service
parameters.
Parameter settings are shown by pressing [Main Menu].
Press [
], [▼], [] and [◄] to scroll through parameters.
BAS-SVM04B-EN 02/2017 All rights reserved. 19
Page 21
2
Frequency Converter Control
2.6 Control Terminal Functions
Tab l e 2.2 describes the functions of the control terminals. Many of these terminals have multiple functions determined by parameter settings. See Illustration 2.1.
Ter m in al
number
01, 02, 03 Form C relay output on control card. Maximum 240
04, 05 Form A relay output on control card. 30 V AC, 42.5
12, 13 Voltage supply to digital inputs and external
16–33 Programmable digital inputs for controlling the
20 Common for digital inputs.
39 Common for analog and digital outputs.
42, 45 Analog and digital outputs for indicating values
50 10 V DC, 17 mA maximum analog supply voltage
53, 54
55 Common for analog inputs. This common is
60 Programmable 0–20 mA or 4–20 mA, analog
61 RS485 common.
68, 69 RS485 interface and serial communication.
Func tion
V AC, 2 A. Minimum 24 V DC, 10 mA, or 24 V AC,
100 mA. Can be used for indicating status and
warnings. Physically located on power card.
V DC. Can be used for indicating status and
warnings.
transducers. For the 24 V DC to be used for digital
inputs, switch 4 on the control card must be closed
(ON position). The maximum output current is 200
mA.
Ω
frequency converter. R=2 k
(open). Greater than 10 V=logic 1 (closed).
such as frequency, reference, current, and torque.
The analog signal is 0–20 mA, or 4–20 mA at a
Ω
maximum of 500
a minimum of 600
for potentiometer or thermistor.
0–10 V DC voltage input, R = 10 k
reference or feedback signals. A thermistor can be
connected here.
isolated from the common of all other power
supplies. If, for example, the frequency converter’s
24 V DC power supply is used to power an
external transducer, which provides an analog
input signal, terminal 55 must be wired to terminal
39.
current input, Resistance=approx. 200
reference or feedback signals.
. The digital signal is 24 V DC at
Ω
. Less than 5 V=logic 0
.
Ω
Used for
Ω
. Used for
Tab le 2.2 Term ina l Functi ons
20 02/2017 All rights reserved. BAS-SVM04B-EN
Page 22
Frequency Converter Control TR150 and TR170 Service Manual
2
2
Illustration 2.1 Control Terminal Electrical Overview
Control terminals must be programmed. Each terminal has specic functions and a numbered parameter associated with it. The setting selected in the parameter enables the function of the terminal. See the TR150 and TR170 Quick Guide for details.
BAS-SVM04B-EN 02/2017 All rights reserved. 21
Page 23
Frequency Converter Control
2
2.7 Grounding Shielded Cables
Connect the shielded control cables to the metal cabinet of the frequency converter with cable camps at both ends. Illustration 2.3 shows ground cabling for optimal results.
Correct grounding
To ensure the best possible electrical connection, t control cables and cables for serial communication with cable clamps at both ends.
Illustration 2.2 Correct Grounding
Incorrect grounding
Do not use twisted cable ends (pigtails) since they increase shield impedance at high frequencies.
Ground potential protection
When the ground potential between the frequency converter and the PLC or other interface device is dierent, electrical noise may occur that can disturb the entire system. Resolve the electrical noise by cable next to the control cable. Minimum cable cross-
2
section is 10 mm
(8 AWG).
tting
an equalizing
Serial communication control cables
Low-frequency noise currents between frequency converters can be eliminated by connecting 1 end of the shielded cable to frequency converter terminal 61. This terminal connects to ground through an internal RC link. To reduce the dierential mode interference between conductors, use twisted-pair cables.
Illustration 2.5 Serial Communication Control Cables
1
Minimum 10 mm
2 Equalizing cable
Illustration 2.3 Ground Potential Protection
2
(8 AWG)
50/60 Hz ground loops
When using long control cables, 50/60 Hz ground loops may occur that can disturb the entire system. Resolve the ground loops by connecting 1 end of the shield with a 100 nF capacitor and keeping the lead short.
Illustration 2.4 50/60 Hz Ground Loops
22 02/2017 All rights reserved. BAS-SVM04B-EN
Page 24
Internal Frequency Converte... TR150 and TR170 Service Manual
3
3 Internal Frequency Converter Operation
3.1 General
This chapter provides an operational overview of the main assemblies and circuitry in the frequency converter.
3.2 Description of Operation
3.2.1 Control Logic Section
The control card includes most of the logic section (see Illustration 3.2). The primary logic element of the control card is a microprocessor, which supervises and controls all functions of frequency converter operation. In addition, a separate PROM contains the parameters to provide the user with programmable options. These parameters are programmed to enable the frequency converter to meet specic application requirements. This data is stored in an EEPROM providing security during power-down and also allows the exibility to change the operational character­istics of the frequency converter.
undesired program changes. With the addition of a remote mounting kit, the LCP can be mounted in a remote location.
Control terminals, with programmable functions, are provided for input commands such as run, stop, forward, reverse and speed reference. Additional output terminals are provided to supply signals to run peripheral devices or for monitoring and reporting status.
The control card logic
Communicates via serial link with outside devices
such as personal computers or Programmable Logic Controllers (PLC).
Provides 2 voltage supplies for use from the
control terminals.
24 V DC is used for switching functions such as start, stop, and forward/reverse. The 24 V DC supply also supplies 200 mA of power, which can partly be used to power external encoders or other devices. A 10 V DC supply rated at 17 mA is also available for use with speed reference circuitry.
The analog and digital output signals are powered through an internal supply. The 3 power supplies are isolated from one another to eliminate ground loop conditions in the control input circuitry.
3
Illustration 3.1 Logic Section
Another part of the logic section is the removable LCP or display mounted on the front of the frequency converter. The LCP provides a user interface to the frequency converter.
All programmable parameter settings can be uploaded into the EEPROM of the LCP. This function helps in maintaining a back-up frequency converter prole and parameter set. Its download function can be used in programming other frequency converters or restoring a program to a repaired unit. The LCP is removable during operation to prevent
2 relays for monitoring the status of the frequency converter are located on the power card. These relays are programmable through parameter group 5-4* Relays. The relays are Form C. These relays have one normally open contact, and one normally closed contact on a single throw. The contacts of the relay are rated for a maximum load of 240 V AC at 2 Amps resistance.
The logic circuitry on the control card allows for adding:
Option modules for synchronizing control
Serial communications
Additional relays
Cascade pump controller
Custom operating software
BAS-SVM04B-EN 02/2017 All rights reserved. 23
Page 25
3
Internal Frequency Converte...
3.2.2 Logic to Power Interface
The logic to power interface isolates the high-voltage components of the power section from the low voltage signals of the logic section. The interface consists of two sections.
Power Card
Gate Driver
The control card handles much of the fault processing for output short circuit and ground fault conditions. The power card provides conditioning of these signals. Scaling of current feedback and voltage feedback is accomplished on the interface sections before processing by the control card.
Illustration 3.2 Typical Power Section
3.3 Sequence of Operation
3.3.1
Rectier
Section
The power card contains a Switch Mode Power Supply (SMPS). The SMPS provides the unit with 24 V DC, 16 V DC, 7 V DC, 6 V DC, and 3.3 V DC operating voltage. SMPS powers the logic and interface circuitry. SMPS is supplied by the DC bus voltage. A secondary SMPS provides power to the logic circuitry with main input disconnected. It can keep units with communication options live on a network when the frequency converter is not powered from the mains.
Circuitry for controlling speed of the cooling fans is also provided on the power card.
3.2.3 Power Section
The DC coil is a single unit 2 two coils wound on a common core. One coil resides in the positive side of the DC bus and the other in the negative. The coil aids in the reduction of mains harmonics.
The DC bus capacitors are arranged into a capacitor bank along with bleeder and balancing circuitry.
The inverter section is made up of six IGBTs, commonly referred to as switches. One switch is necessary for each half phase of the 3-phase power, for a total of 6. The 6 IGBTs are contained in 3 dual modules.
A Hall eect type current sensor is located on each phase of the output to measure motor current.
The rectier provides a path for current owing from the line to the DC-link circuitry. As a result, the DC-link capacitors charge.
The rectier section consists of 6 diodes.
Inrush current, which appears when connected to grid, is limited with a PTC. A relay short-circuits the PTC when the DC-link capacitors are fully charged.
As long as power is applied to the frequency converter, voltage is present in the DC link and the inverter circuit. Voltage is also fed to the switch mode power supply (SMPS) on the power card and is used for generating all other low voltage supplies.
3.3.2 Intermediate Section
From the rectier section, voltage passes to the intermediate section. The DC link is an LC lter circuit consisting of the DC-link inductor and the DC-link capacitor bank that smooths the rectied voltage.
The intermediate section consists of the following components:
The DC-link inductor located in the positive side
of the DC link provides series impedance to changing current. This impedance aids the ltering process while reducing harmonic distortion to the input AC current waveform normally inherent in rectier circuits.
The DC-link capacitors are arranged into a
capacitor bank along with bleeder and balancing circuitry.
High frequency (HF) lter lm capacitors. These
capacitors reduce the common mode noise caused by switching into stray capacitors to ground in cable and motor.
24 02/2017 All rights reserved. BAS-SVM04B-EN
Page 26
Internal Frequency Converte... TR150 and TR170 Service Manual
3
The voltage on a fully charged DC link is equal to the peak voltage of the input AC line. Theoretically, this voltage can be calculated by multiplying the AC line value by 1.414 (V AC x 1.414). However, since AC ripple voltage is present on the DC link, the actual DC value is closer to (V AC x 1.38) under unloaded conditions. The DC value can drop to (V AC x 1.32) while running under load.
Example
For a frequency converter sitting idle while connected to a nominal 460 V line, the DC-link voltage is approximately 635 V DC (460 x 1.38). As long as power is applied to the frequency converter, this voltage is present in the DC link and the inverter circuit. Voltage is also fed to the switch mode power supply (SMPS) on the power card which is used for generating all other low voltage supplies. The SMPS is activated when the DC-link voltage reaches approximately 250 V DC.
3.3.3 Inverter Section
The inverter section is made up of six IGBTs, commonly referred to as switches. One switch is necessary for each half phase of the 3-phase power, for a total of six. The six IGBTs are contained in one power module shared with the rectier. The inverter section receives gate signals from the MOC.
Once a run command and speed reference are present, the IGBTs begin switching to create the output waveform, as shown in Illustration 3.3. Looking at the phase to phase voltage waveform with an oscilloscope, a train of pulses of dierent widths is shown. The amplitude of the pulses measures the DC-link voltage. To view the fundamental sinusoidal curve, set the oscilloscope to lter out high harmonic content.
When measuring current, the normal view will be a sinusoidal curve. The amplitude of the measured current depends on the loading form.
This waveform, as generated by the frequency converter, provides optimal performance and minimal losses in the motor.
Hall eect current sensors monitor the output current and feed it back to the control. The current signal is used for two purposes:
to compensate for dynamic motor operation.
to monitor overcurrent conditions, including
ground faults and phase-to-phase shorts.
During normal operation, the power card and control monitor various functions within the frequency converter. The current sensors provide current feedback information. The DC bus voltage and mains voltage are monitored and
the voltage delivered to the motor. A thermal sensor mounted inside the IGBT module provides heat sink temp feedback for the inverter.
Illustration 3.3 Output Voltage and Current Waveforms
3.3.4 Fan Speed Control
IP20
Enclosure H6 H7 H8
Voltage T2T2T2 T2T2T2
Power rating
[kW]
FAN s tar t
temperature
FAN maximum
speed
temperature
FAN s top
temperature
Table 3.1 Fan Speed Control, IP20, H6–H8, T2
IP20
Enclosure H6 H7 H8
Volt age T4 T4 T 4 T4 T4 T4
Power rating
[kW]
FAN s tar t
temperature
FAN maximum
speed
temperature
FAN s top
temperature
Table 3.2 Fan Speed Control, IP20, H6–H8, T4
IP54
Enclosure I6 I7 I8
Voltage T4T4T4T4T4T4T4
Power rating
[kW]
FAN s tar t
temperature
15 18.5 22 30 37 45
45 45 45 45 45 45
°
C
60 60 60 60 60 60
°
C
36 36 36 36 36 36
°
C
30 37 45 55 75 90
45 45 45 40 40 40
°
C
60 60 60 55 55 55
°
C
41 41 41 30 30 30
°
C
22 30 37 45 55 75 90
45 45 45 40 40 40 40
°
C
3
BAS-SVM04B-EN 02/2017 All rights reserved. 25
Page 27
3
Internal Frequency Converte...
IP54
Enclosure I6 I7 I8
FAN maximum
speed
temperature
FAN s top
temperature
Table 3.3 Fan Speed Control, IP54, I6–I8
IP20
Enclosure H9 H10 H6 H7 H8
Voltage T6T6T6T6T6T6T6T6T6T6T6T6
Power
rating
[kW]
FAN s tar t
tempera-
°
C
ture
FA N
maximum
speed
tempera-
°
C
ture
FAN s top
tempera-
°
C
ture
60 60 60 55 55 55 55
°
C
35 35 35 30 30 30 30
°
C
2.2 3.0 5.5 7.5 11 15 22 30 45 55 75 90
35 35 35 35 45 45 45 45 40 40 40 40
55 55 55 55 60 60 60 60 55 55 55 55
31 31 31 31 36 41 41 41 30 30 30 30
Table 3.4 Fan Speed Control, IP20, H9–H10, and H6–H8, T6
26 02/2017 All rights reserved. BAS-SVM04B-EN
Page 28
Troubleshooting TR150 and TR170 Service Manual
4
4 Troubleshooting
4.1 Troubleshooting Tips
Before repairing a frequency converter, read and understand the following instructions.
1. Note all warnings concerning voltages present in the frequency converter. Always verify the presence of AC input voltage and DC link voltage before working on the unit. Some points in the frequency converter are referenced to the negative DC link. They are at DC link potential even though it sometimes appears on diagrams to be a neutral reference.
CAUTION
Voltage can be present for as long as 20 minutes on frequency converters after removing power from the unit. See the label on the front of the frequency converter door for the specic discharge time.
2. Never apply power to a unit that is suspected of being faulty. Many faulty components within the frequency converter can damage other components when power is applied. Always perform the procedure for testing the unit after repair as described in chapter 4.7 After Repair Tes ts .
3. Never attempt to defeat any fault protection circuitry within the frequency converter, as this results in unnecessary component damage and can cause personal injury.
4. Always use factory approved replacement parts. The frequency converter is designed to operate within certain specications. Incorrect parts can
tolerances and result in further damage to
aect the unit.
5. Read the instruction manual. A thorough understanding of the unit is the best approach. If ever in doubt, consult the factory or authorised repair centre for assistance.
4.2 Exterior Fault Troubleshooting
There may be slight dierences in servicing a frequency converter that has been operational for extended time, compared to a new installation. In either case, use proper troubleshooting procedures.
CAUTION
RISK OF INJURY OR PROPERTY DAMAGE
Never assume that a motor is wired properly after a service of the frequency converter. Check for:
Loose connections.
Improper programming.
Added equipment.
Failure to perform these checks can result in personal injury, property damage, or less than optimal performance.
Take a systematic approach, beginning with a visual inspection of the system. See Tabl e 4.1 for items to examine.
4.3 Fault Symptom Troubleshooting
The troubleshooting procedures are divided into sections based on the
1. See the visual inspection check list in Tab l e 4.1.
2. The most common fault symptoms are described
dierent
Often, incorrect installation or wiring of the frequency converter causes the problem. The check list provides guidance through the items to inspect during servicing of the frequency converter.
in chapter 4.5 Fault Symptoms:
The frequency converter processor monitors inputs and outputs as well as internal frequency converter functions. An alarm or warning does not necessarily indicate a problem within the frequency converter itself.
For each incident, further description explains how to troubleshoot that particular symptom. When necessary, further referrals are made to other parts of the manual for more procedures.
When troubleshooting is complete, perform the list of tests provided in chapter 6.5 Initial Start-up Or After Repair Drive Tes ts .
occurring symptom.
Problems with motor operation.
A warning or alarm shown by the frequency converter.
4
BAS-SVM04B-EN 02/2017 All rights reserved. 27
Page 29
4
Troubleshooting
4.4 Visual Inspection
Visually inspect the conditions in Table 4 .1 as part of any initial troubleshooting procedure.
Inspect for Description
Auxiliary equipment
Cable routing
Control wiring
Frequency converter cooling Check operational status of all cooling fans:
Frequency converter display The display shows important items, such as:
Frequenc y converter interior
EMC considerations
Environmental conditions
GLCP
Grounding
Look if more auxiliary equipment, switches, disconnects, or input fuses/circuit breakers reside on the
input power side of frequency converter or output side to motor.
Examine operation and condition of these items as possible causes for operational faults.
Check function and installation of pressure sensors or encoders, and other equipment used for
feedback to the frequency converter.
Avoid routing motor wiring, AC line wiring, and signal wiring in parallel. If parallel routing is
unavoidable, maintain a separation of 150–200 mm (6–8 inches) between the cables or separate them
with a grounded conductive partition.
Avoid routing cables through free air.
Check for broken or damaged wires and connections.
Check the voltage source of the signals. Though not always necessary depending on the installation
conditions, the use of screened cable or a twisted pair is recommended.
Ensure that the screen is terminated correctly.
When voltage is applied to the frequency converter, the fan activates for a few seconds.
Check for blockage or constrained air passages.
Warn ings.
Alarms.
Frequency converter status.
Fault histor y.
Check that the frequency converter interior is free of :
- Dirt.
- Metal chips.
- Moisture.
- Corrosion.
Check for burnt or damaged power components, or carbon deposits that are the result of a
catastrophic component failure.
Check for cracks or breaks in the housings of power semiconductors, or pieces of broken component
housings, which are loose inside the unit.
Check for proper installation regarding electromagnetic capability.
Refer to the frequency converter operating instructions and this chapter for further details.
Under
Humidity levels must be less than 95% non-condensing.
Check for harmful airborne contaminates such as sulfur-based compounds.
If supplied, check that the GLCP is correctly installed, and that the display is lit when powered on.
The frequency converter requires a dedicated ground wire from its enclosure to the building ground.
It is also suggested to ground the motor to the frequency converter enclosure.
The use of conduit or mounting of the frequency converter to a metal surface is not considered to
be suitable grounding.
Check for good ground connections that are tight and free of oxidation.
conditions, these units can be operated within a maximum ambient of 50 °C (122 °F).
specic
28 02/2017 All rights reserved. BAS-SVM04B-EN
Page 30
Troubleshooting TR150 and TR170 Service Manual
4
Inspect for Description
Input power wiring Check for:
Loose connections.
Proper fusing.
Blown fuses.
Memory module
Motor
Output to motor wiring Check for:
PROFIBUS option
Programming Ensure that frequency converter parameter settings are correct according to:
Proper clearance The frequency converter requires top and bottom clearance adequate to ensure proper air ow for
Vibration
Check that the memory module is plugged in correctly.
Check nameplate ratings of the motor.
Ensure that motor ratings coincide with frequency converters.
Ensure that the frequency converter motor parameters (parameter 1-20 Motor Power to
parameter 1-25 Motor Nominal Speed) are set according to motor ratings.
Loose connections.
Switching components in output circuit.
Faulty contacts in switch gear.
Check that the option is mounted correctly on the control card.
Motor.
Application.
I/O conguration.
cooling in accordance with the frequency converter size. When the heat sink is exposed at the rear of
the frequency converter, mount the frequency converter on a
Check for exposure to an unusual amount of vibration.
When the frequency converter experiences a high level of vibration, ensure solid mounting or use
shock mounts.
solid surface.
at,
4
Table 4.1 Visual Inspection Check List
BAS-SVM04B-EN 02/2017 All rights reserved. 29
Page 31
Troubleshooting
4
4.5 Fault Symptoms
4.5.1 No Display
The LCP display provides 2 display indications. One with the backlit alphanumeric display. The other is 3 LED indicator lights near the bottom of the LCP.
Illustration 4.1 LED Indicator Lights
If the green power-on LED is illuminated, but the backlit display is dark, it indicates that the LCP is defective and must be replaced. Be certain, however, that the display is dark.
If the display continues to cut out, follow the procedure for chapter 4.5.1 No Display as though the display was not lit at all.
4.5.3 Display (Line 2) Flashing
When line 2 ashes, it indicates that an LCP stop command has been given by pressing converter cannot accept any further run command until the LCP stop is cleared. To clear the LCP stop, press [Auto On] or [Hand On].
[O/Reset].
The frequency
CAUTION
IMMEDIATE START
If the frequency converter is operated in local control, or remote control with a maintained run signal, the frequency converter starts immediately. Failure to be prepared for immediate start can cause personal injury.
Be prepared for immediate start.
4.5.4 WRONG or WRONG LCP Shown
The message WRONG or WRONG LCP appears due to a faulty LCP or the use of an incorrect LCP.
A single character or just a dot in the upper corner of the LCP indicates that communications may have failed with the control card. This situation typically appears when a eldbus communication option has been installed in the frequency converter and is either not connected properly or is malfunctioning.
If neither indication is available, then the source of the problem is elsewhere. Proceed to the next troubleshooting steps.
4.5.2 Intermittent Display
Cutting out or ashing of the entire display and power LED indicates that the supply (SMPS) is shutting down due to overload. Improper control wiring or a fault within the frequency converter itself can cause the overload.
The rst step is to rule out a problem in the control wiring. To do so, disconnect all control wiring by unscrewing or unplugging the control terminal blocks from the control card.
If the display stays lit, the problem is in the control wiring (external to the frequency converter). Check all control wiring for short circuits or incorrect connections.
Replace the LCP with a correct and functioning one.
NOTICE
Error 84 appears when the LCP cannot communicate with the frequency converter.
4.5.5 Motor Will Not Run
If this symptom is detected, verify that the unit is properly powered up (display is lit) and that there are no warning or alarm messages displayed. The most common cause of this problem is either incorrect control logic or an incorrectly programmed frequency converter. Such occurrences result in one or more of the following status messages being displayed.
LCP Stop
has been pressed. Line 2 of the display also
[O] when this situation occurs.
Press [Auto On] or [Hand On]. Refer to the Input Terminal Signal Test.
Standby
This message indicates that there is no start signal at terminal 18.
Ensure that a start command is present at terminal 18. Re fer t o the I nput Termina l Sign a l Test.
ashes
30 02/2017 All rights reserved. BAS-SVM04B-EN
Page 32
Troubleshooting TR150 and TR170 Service Manual
4
Unit ready
Terminal 27 is low (no signal).
Ensure that terminal 27 is logic “1”. Refer to the Input Terminal Signal Test.
Run OK, 0 Hz
This message indicates that a run command has been given to the frequency converter but the reference (speed command) is zero or missing.
Check control wiring to ensure that the proper reference signal is present at the input terminals. Also check that the unit is properly programmed to accept the signal provided. Refer to the Input Terminal Signal Test.
O 1 (2 or 3)
This message indicates that bit #1 (or #2, or #3) in the control word is logic “0”. This situation only occurs when the frequency converter is being controlled via the eldbus.
A correct control word must be transmitted to the frequency converter over the communication bus.
STOP
One of the digital input terminals 16, 17, 27, 29, 32, or 33 is programmed for “Stop Inverse” and the corresponding terminal is low (logic “0”).
Ensure that the above parameters are programmed correctly and that any digital input programmed for “Stop Inverse” is high (logic “1”).
Display Indication that the unit is functioning, but there is no output.
If the unit is equipped with external 24 V DC option, check that the main power is applied to the frequency converter.
NOTICE
In this case, the display alternately ashes Warning 8.
4.5.6 Incorrect Motor Operation
A fault can occur in the event of incorrect motor operation. The symptoms and causes may vary consid­erably. The following sections list many of the possible problems by symptom along with recommended procedures for determining their causes.
Wrong speed/unit does not respond to command
Possible cause: Incorrect reference (speed command).
Actions:
1. Ensure that the unit is programmed correctly according to the reference signal being used.
2. Ensure that all reference limits are set correctly.
3. Perform the test chapter 6.4.7 Input Terminal Signal Tests to check for faulty reference signals.
Motor speed unstable
Possible causes:
Incorrect parameter settings.
Faulty current feedback circuit.
Loss of motor (output) phase.
Actions:
1. Check settings of all motor parameters, including all motor compensation settings (slip compen­sation, load compensation, and so on).
2. For closed-loop operation, check PID settings.
3. Perform test as described in chapter 6.4.7 Input Ter mina l S igna l Tests to check for faulty reference signals.
4. Perform test as described in chapter 6.4.6 Output Imbalance of Motor Supply Voltage Test to check for loss of motor phase.
Motor runs rough
Possible cause:
Overmagnetisation (incorrect motor settings).
IGBT misring.
NOTICE
The motor may stall when loaded, or the frequency converter may trip occasionally on Alarm 13, Over Current.
Action:
1. Check the setting of all motor parameters, see
chapter 6.4.6 Output Imbalance of Motor Supply Voltage Test.
2. If output voltage is unbalanced, see
chapter 6.4.6 Output Imbalance of Motor Supply Voltage Test.
Motor draws high current but cannot start
Possible causes:
Open winding in motor.
Open connection to motor.
Actions:
1. Perform the test in chapter 6.4.6 Output Imbalance of Motor Supply Voltage Test to ensure that the frequency converter provides correct output (see Motor Runs Rough above).
2. Check motor for open windings. Check all motor wiring connections.
3. Run an AMA to check the motor for open windings and unbalanced resistance. Inspect all motor wiring connections.
4
BAS-SVM04B-EN 02/2017 All rights reserved. 31
Page 33
Troubleshooting
4
4.6 Warnings and Alarms
When the frequency converter fault circuitry detects a fault condition, or a pending fault, a warning, or alarm is issued. A ashing display on the LCP indicates an alarm or warning condition and the associated number code on line
2. Sometimes a warning precedes an alarm. Table 4 . 2 denes whether a warning precedes an alarm and whether the frequency converter suspends operations (trips).
4.6.1 Alarms
An alarm causes the frequency converter to trip (suspend operation). The frequency converter has 3 trip conditions which are displayed on line 1:
TRIP (AUTO RESTART)
The frequency converter is programmed to restart automatically after the fault is removed. The number of automatic reset attempts can be continuous or limited to a programmed number of attempts. If the selected number of automatic reset attempts is exceeded, the trip condition changes to TRIP (RESET).
TRIP (RESET)
Requires resetting of the frequency converter before operation after a fault is cleared. The frequency converter can be reset manually by pressing [Reset], a digital input, or a serial bus command. For TR150 and TR170 frequency converters, stop and reset are the same key. If [O/Reset] is used to reset the frequency converter, [Start] must be pressed to initiate a run command in either local or remote.
TRIPLOCK (DISC> MAINS)
Requires that the main AC input power to the frequency converter must be disconnected long enough for the display to go blank. The fault condition must be removed and power reapplied. Following power up, the fault indication changes to TRIP (RESET) and allow for manual, digital, or serial bus reset.
Line 2 displays alarm and the associated number while line 3
identies
the alarm in plain language.
NOTICE
When exchanging the unit which requires re mode activation, carefully check that the Fire Mode parameters
Parameter 24-00 FM Function
Parameter 24-05 FM Preset Reference
Parameter 24-09 FM Alarm Handling
are correctly transferred into the exchange unit.
4.6.2 Warnings
During a warning, the frequency converter remains operational, although the warning the condition exists. The frequency converter could, however, reduce the warning condition. For example, if the warning shown was warning 12, Torque Limit, the frequency converter would reduce speed to compensate for the overcurrent condition. Sometimes, if the condition is not corrected or worsens, an alarm condition is activated and the frequency converter stops output to the motor terminals. Line 1 identies the warning in plain language, and line 2
identies
the warning number.
ashes
for as long as
4.6.3 Warning And Alarm Messages
The LEDs on the front of the frequency converter and a code in the display signal a warning or an alarm.
A warning indicates a condition that may require attention or a trend that may eventually require attention. A warning remains active until the cause is no longer present. Under some circumstances, motor operation may continue.
A trip is the action when an alarm has appeared. The trip removes power to the motor. It can be reset after the condition has been cleared by pressing [Reset], or through a digital input (parameter group 5-1* Digital Inputs). The event that caused an alarm cannot damage the frequency converter or cause a dangerous condition. Alarms must be reset to restart operation once their cause has been rectied.
The reset can be done in 3 ways:
Press [Reset]
A digital reset input
Serial communication/optional eldbus reset
signal
NOTICE
After a manual reset pressing [Reset] on the LCP, press [Auto On] to restart the motor.
An (X) marked in Table 4 .2 means that action occurs. A warning precedes an alarm.
If a situation occurs that can damage the frequency converter or connected equipment, an alarm triggers a trip lock. Power is removed from the motor. A trip lock can only be reset after a cycling power has cleared the condition. Once the problem has been rectied, only the alarm continues ashing until the frequency converter is reset.
32 02/2017 All rights reserved. BAS-SVM04B-EN
Page 34
Troubleshooting TR150 and TR170 Service Manual
4
No. Description Warning Alarm Trip Lock Parameter Reference
2 Live zero error (X) (X) 6–01
3 No motor (X) 1–80
4 Mains phase loss (X) (X) (X) 14–12
7DC over voltage (X) (X)
8DC under voltage (X) (X)
9 Inverter overloaded (X) (X)
10 Motor ETR over temperature (X) (X) 1–90
11 Motor thermistor over
temperature
13 Over Current (X) (X) (X)
14 Ground fault (X) (X) (X)
16 Short Circuit (X) (X)
17 Control word timeout (X) 8–04
24 Fan Fault (On ly on 400 V
30-90 kW)
30 Motor phase U missing (X) (X) 4–58
31 Motor phase V missing (X) (X) 4–58
32 Motor phase W missing (X) (X) 4–58
38 Internal fault (X) (X)
44 Ground fault 2 (X) (X)
47 Control Voltage Fault (X) (X)
48 VDD1 Supply Low (X) (X)
50 AMA Calibration Failed (X)
nom
nom
and I
nom
51 AMA check U
52 AMA low I
53 AMA motor too big (X)
54 AMA motor too small (X)
55 AMA Parameter out of
range
56 AMA interrupted by user (X)
57 AMA timeout (X)
58 AMA internal fault (X) (X)
59 Current limit (X)
60 External Interlock (X)
66 Heat sink Temperature Low (X)
69 Pwr Card Temperature (X) (X) (X)
79 Illegal PS cong (X) (X)
80 Drive Initialised to Default
Valu e
84 LCP Error X
87 Auto DC Braking (X)
95 Broken Belt (X) (X)
201 Fire Mode (X)
202 Fire M Limits Exceeded (X)
250 New spare parts (X) (X)
251 New Type Code (X) (X)
(X) (X) 1–90
(X) 14–53
(X)
(X)
(X)
(X)
*
22–6
4
Table 4.2 Alarm/Warning Code List
(X) Dependent on parameter. A trip is the action when an alarm has appeared. The trip coasts the motor and can be reset by pressing [Reset] or make a reset by a digital input
*
(parameter group 5-1
BAS-SVM04B-EN 02/2017 All rights reserved. 33
Digital Inputs [1]). The original event
that caused an alarm cannot damage the frequency converter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which can damage the
Page 35
Troubleshooting
4
frequency converter or connected parts. A trip lock situation can only be reset by a power cycling.
Warn ing Yell ow
Alarm Flashing red
Tab le 4.3 LED Ind i cat ion
The alarm words, warning words and extended status words can be read out via serial bus or optional for diagnosis.
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this condition.
Troubleshooting
Check connections on all analog mains terminals.
- Control card terminals 53 and 54 for
signals, terminal 55 common.
- General Purpose I/O terminals 11 and 12 for signals, terminal 10 common.
- Analog I/O Option terminals 1, 3, and 5 for signals, terminals 2, 4, and 6 common.
Check that the frequency converter programming
and switch settings match the analog signal type.
Perform an input terminal signal test.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectier. Options are programmed in parameter 14-12 Function at Mains Imbalance.
Troubleshooting
Check the supply voltage and supply currents to
the frequency converter.
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the frequency converter trips after a time.
Troubleshooting
Extend the ramp time
Change the ramp type
Increase parameter 14-26 Trip Delay at Inverter
Fau lt
WARNING/ALARM 8, DC under voltage
If the DC-link voltage drops below the undervoltage limit, the frequency converter checks for 24 V DC back-up supply. If no 24 V DC back-up supply is connected, the frequency converter trips after a xed time delay. The time delay varies with unit size.
eldbus
Troubleshooting
Check that the supply voltage matches the
frequency converter voltage.
Perform an input voltage test.
Perform a soft-charge circuit test.
WARNING/ALARM 9, Inverter overload
The frequency converter has run with more than 100% overload for too long and is about to cut out. The counter for electronic thermal inverter protection issues a warning at 98% and trips at 100% with an alarm. The frequency converter cannot be reset until the counter is below 90%.
Troubleshooting
Compare the output current shown on the
keypad with the frequency converter rated current.
Compare the output current shown on the
keypad with the measured motor current.
Show the thermal frequency converter load on
the keypad and monitor the value. When running above the frequency converter continuous current rating, the counter increases. When running below the frequency converter continuous current rating, the counter decreases.
WARNING/ALARM 10, Motor overload temperature
According to the electronic thermal protection (ETR), the motor is too hot.
Select 1 of these options:
The frequency converter issues a warning or an
alarm when the counter is >90% if parameter 1-90 Motor Thermal Protection is set to warning options.
The frequency converter trips when the counter
reaches 100% if parameter 1-90 Motor Thermal Protection is set to trip options.
The fault occurs when the motor runs with more than 100% overload for too long.
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded.
Check that the motor current set in
parameter 1-24 Motor Current is correct.
Ensure that the motor data in parameters 1-20 to
1-25 is set correctly.
If an external fan is in use, check that it is
selected in parameter 1-91 Motor External Fan.
Running AMA in parameter 1-29 Automatic Motor
Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces thermal loading.
34 02/2017 All rights reserved. BAS-SVM04B-EN
Page 36
Troubleshooting TR150 and TR170 Service Manual
4
WARNING/ALARM 11, Motor thermistor over temp
Check whether the thermistor is disconnected. Select whether the frequency converter issues a warning or an alarm in parameter 1-90 Motor Thermal Protection.
WARNING
Live Electrical Components!
Troubleshooting
Check for motor overheating.
Check if the motor is mechanically overloaded.
When using terminal 53 or 54, check that the
thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 or 54 is set for voltage. Check that parameter 1-93 Thermistor Resource selects terminal 53 or 54.
When using terminal 18, 19, 31, 32, or 33 (digital
inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. Select the terminal to use in parameter 1-93 Thermistor Resource.
WARNING
Disconnect power before proceeding.
WARNING/ALARM 13, Over current
The inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts about 1.5 s, then the frequency converter trips and issues an alarm. Shock loading or fast acceleration with high inertia loads can cause this fault.
Troubleshooting:
Remove power and check if the motor shaft can be turned.
Check that the motor size matches the frequency converter.
Check parameters 1-20 to 1-25 for correct motor data.
ALARM 14, Earth (ground) fault
There is current from the output phase to ground, either in the cable between the frequency converter and the motor, or in the motor itself. The current transducers detect the ground fault by measuring current going out from the frequency converter and current going into the frequency converter from the motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the frequency converter must be the same as the current going into the frequency converter.
Troubleshooting
Remove power to the frequency converter and
repair the ground fault.
Check for ground faults in the motor by
measuring the resistance to ground of the motor cables and the motor with a megohmmeter.
Reset any potential individual
current transducers in the frequency converter. Perform the manual initialization or perform a complete AMA. This method is most relevant after changing the power card.
oset
in the 3
WARNING
Disconnect power before proceeding.
ALARM 16, Short circuit
There is short-circuiting in the motor or motor wiring.
Troubleshooting
Remove the power to the frequency converter
and repair the short circuit.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to use maintain the frequency converter can result in death or serious injury.
qualied
Disconnect power before proceeding.
personnel to install, start up, and
WARNING
Disconnect power before proceeding.
WARNING/ALARM 17, Control word timeout
There is no communication to the frequency converter. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to [0] O. If parameter 8-04 Control Word Timeout Function is set to [5] Stop and Trip, a warning appears. The frequency converter then ramps down until it trips, while giving an alarm. Parameter 8-03 Control Timeout Time could possibly be increased.
WARNING
Live Electrical Components!
Troubleshooting
Check connections on the serial communication
cable.
Increase parameter 8-03 Control Word Timeout
Time.
Check the operation of the communication
equipment.
4
BAS-SVM04B-EN 02/2017 All rights reserved. 35
Page 37
4
Troubleshooting
Verify a proper installation based on EMC
requirements.
WARNING 24, External fan fault
The fan warning function is a protective function that checks if the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ([0] Disabled).
For frequency converters with DC fans, a feedback sensor is mounted in the fan. If the fan is commanded to run and there is no feedback from the sensor, this alarm appears. For frequency converters with AC fans, the voltage to the fan is monitored.
Troubleshooting
Check for proper fan operation.
Cycle power to the frequency converter and
check that the fan operates
Check the sensors on the heat sink.
ALARM 30, Motor phase U missing
Motor phase U between the frequency converter and the motor is missing.
briey
at start-up.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to use maintain the frequency converter can result in death or serious injury.
qualied
Disconnect power before proceeding.
personnel to install, start up, and
WARNING
Disconnect power before proceeding.
Troubleshooting
Remove the power from the frequency converter
and check motor phase U.
ALARM 31, Motor phase V missing
Motor phase V between the frequency converter and the motor is missing.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to use qualied personnel to install, start up, and maintain the frequency converter can result in death or serious injury.
Disconnect power before proceeding.
WARNING
Disconnect power before proceeding.
Troubleshooting
Remove the power from the frequency converter
and check motor phase V.
ALARM 32, Motor phase W missing
Motor phase W between the frequency converter and the motor is missing.
WARNING
HIGH VOLTAGE
Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to use maintain the frequency converter can result in death or serious injury.
qualied
Disconnect power before proceeding.
personnel to install, start up, and
WARNING
Disconnect power before proceeding.
Troubleshooting
Remove the power from the frequency converter
and check motor phase W.
ALARM 38, Internal fault
When an internal fault occurs, a code number dened in Tab l e 4.4 is displayed.
Troubleshooting
Cycle power
Check that the option is properly installed
Check for loose or missing wiring
It may be necessary to contact your Trane supplier or service department. Note the code number for further troubleshooting directions.
No. Text
0 Serial port cannot be initialised. Contact your Trane
supplier or Trane Service Department.
256-258 Power EEPROM data is defective or too old.
Replace power card.
512-519 Internal fault. Contact your Trane supplier or Trane
Service Department.
783 Parameter value outside of min/max limits
1024-1284 Internal fault. Contact your Trane supplier or the
Trane Serv ice Department.
1379-2819 Internal fault. Contact your Trane supplier or Trane
Service Department.
1792 HW reset of DSP
1793 Motor derived parameters not transferred correctly
to DSP
36 02/2017 All rights reserved. BAS-SVM04B-EN
Page 38
Troubleshooting TR150 and TR170 Service Manual
4
No. Text
1794 Power data not transferred correctly at power up
to DSP
1795 The DSP has received too many unknown SPI
telegrams
1796 RAM copy error
2561 Replace control card
2820 LCP stack overow
2821 Serial port overow
2822 USB port overow
3072-5122 Parameter value is outside its limits
5376-6231 Internal fault. Contact your Tr ane suppl ier or Trane
Service Department.
Tab le 4.4 Int e rna l Fau l t Code s
ALARM 44, Earth fault II
There is a discharge from the output phases to earth, either in the cable between the frequency converter and the motor or in the motor itself.
Troubleshooting
Turn o the frequency converter and remove the earth fault.
Measure the resistance to ground of the motor leads and the motor with a megohmmeter to check for earth fault in the motor.
WARNING 47, 24 V supply low
The 24 Vdc is measured on the control card.
WARNING 48, 1.8 V supply low
The 1.8Vdc supply used on the control card is outside of the allowable limits. The supply is measured on the control card.
Troubleshooting
Check for a defective control card.
If an option card is present, check for
overvoltage.
nom
nom
and I
nom
ALARM 51, AMA check U
The settings for motor voltage, motor current, and motor power are wrong.
Troubleshooting
Check the settings in parameters 1-20 to 1-25.
ALARM 52, AMA low I
The motor current is too low.
Troubleshooting
Check the setting in parameter 1-24 Motor Current.
ALARM 53, AMA motor too big
The motor is too large for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The parameter values of the motor are outside of the acceptable range. AMA does not run.
ALARM 56, AMA interrupted by user
The AMA is manually interrupted.
ALARM 57, AMA internal fault
Try to restart the AMA. Repeated restarts can overheat the motor.
ALARM 58, AMA Internal fault
Contact a Trane supplier.
WARNING 59, Current limit
The current is higher than the value in
parameter 4-18 Current Limit. Ensure that motor data in parameters 1-20 to 1-25 is set correctly. Increase the current
limit if necessary. Ensure that the system can operate safely at a higher limit.
WARNING 60, External interlock
A digital input signal indicates a fault condition external to the frequency converter. An external interlock has commanded the frequency converter to trip.
Troubleshooting
Clear the external fault condition.
To resume normal operation, apply 24 Vdc to the
terminal programmed for external interlock.
Reset the frequency converter.
WARNING 66, Heatsink temperature low
This warning is based on the temperature sensor in the IGBT module.
Troubleshooting
The heatsink temperature measured as 0 °C could indicate that the temperature sensor is defective, thus causing the fan speed to increase to the maximum. If the sensor wire between the IGBT and the gate drive card is disconnected, this warning is produced. Also, check the IGBT thermal sensor.
ALARM 79, Illegal power section
The scaling card has an incorrect part number or is not installed. The MK102 connector on the power card could not be installed.
ALARM 80, Drive initialised to default value
Parameter settings are initialized to default settings after a manual reset. To clear the alarm, reset the unit.
ALARM 84, LCP error
ALARM 84 is generated by the LCP and indicates an error with the LCP.
ALARM 95, Broken belt
Torque is below the torque level set for no load, indicating a broken belt. Parameter 22-60 Broken Belt Function is set for alarm.
Troubleshooting
Troubleshoot the system and reset the frequency
converter after clearing the fault.
conguration
4
BAS-SVM04B-EN 02/2017 All rights reserved. 37
Page 39
Troubleshooting
4
WARNING 200, Fire mode
The frequency converter is operating in re mode. The warning clears when re mode is removed. Refer to the re mode data in the alarm log.
WARNING 202, Fire mode limits exceeded
While operating in re mode, 1 or more alarm conditions that would normally trip the unit have been ignored. Operating in this condition voids unit warranty. Cycle power to the unit to remove the warning. Refer to the re mode data in the alarm log.
WARNING 250, New spare part
The power card or switch mode power supply has been exchanged. The frequency converter type code must be restored in the EEPROM. Select the correct type code in parameter 14-23 Typecode Setting according to the label on the unit. Remember to select ‘Save to EEPROM’ to complete.
WARNING 251, New typecode
The frequency converter has a new type code.
4.7 After Repair Tests
Following any repair to a frequency converter or testing of a frequency converter suspected of being faulty, the following procedure must be followed. Following the procedure ensures that all circuitry in the frequency converter is functioning properly before putting the unit into operation.
1. Perform visual inspection procedures as described in Table 4.1.
2. Perform static test procedures to ensure that frequency converter is safe to start.
3. Disconnect motor cables from output terminals (U, V, W) of frequency converter.
4. Apply AC power to frequency converter.
5. Give the frequency converter a run command and slowly increase reference (speed command) to approximately 40 Hz.
6. Use an analog voltmeter or a DVM capable of measuring true RMS, measure phase-to-phase output voltage on all three phases: U to V, U to W, V to W. All voltages must be balanced within 8 V. If unbalanced voltage is measured, refer to chapter 6.4.2 Input Voltage Test.
7. Stop the frequency converter and remove input power. Allow 20 minutes for DC capacitors to fully discharge.
8. Reconnect motor cables to frequency converter output terminals (U, V, W).
9. Reapply power and restart frequency converter. Adjust motor speed to a nominal level.
10. Use a clamp-on style ammeter, measure output current on each output phase. All currents must be balanced.
38 02/2017 All rights reserved. BAS-SVM04B-EN
Page 40
Frequency Converter and Mot... TR150 and TR170 Service Manual
5
5 Frequency Converter and Motor Applications
5.1 Torque Limit, Current Limit, and Unstable Motor Operation
Excessive loading of the frequency converter can result in warning or tripping on torque limit, overcurrent, or inverter overload. Avoid this situation by sizing the frequency converter properly for the application. Ensure that intermittent load conditions cause anticipated operation in torque limit or an occasional trip. Pay attention to the following parameters when matching the frequency converter to the motor for optimum operation.
Parameters 1-20 to 1-25 for the connected motor.
These parameters set:
Motor power.
Voltage.
Frequency.
Current.
Nominal motor speed.
It is important to set these parameters accurately. Enter the motor data required as listed on the motor nameplate. The frequency converter relies on this information for accurate motor control in dynamic loading applications.
Parameter 1-29 Automatic Motor Adaption (AMA) activates the automatic motor adaptation (AMA) function. When AMA is performed, the frequency converter measures the electrical characteristics of the motor and sets various frequency converter parameters based on the ndings. This function sets the following parameter values:
Parameter 1-30 Stator Resistance (Rs)
Parameter 1-35 Main Reactance (Xh)
Parameter 1-37 d-axis Inductance (Ld)
If motor operation is unstable, perform AMA if this operation has not already been performed. AMA can only be performed on single-motor applications within the programming range of the frequency converter. Refer to the operating guide/quick guide for more information on this function.
congure
the frequency converter
NOTICE
Never adjust these parameters to random values even though it seems to improve operation. Such adjustments can result in unpredictable operation under changing conditions.
5.1.1 Overvoltage Trips
Overvoltage trip occurs when the DC-link voltage reaches its DC link alarm voltage high (see chapter 1.9.1 Short Circuit and Overcurrent Trips). Before tripping, the frequency converter shows a high-voltage warning. Mostly, fast deceleration ramps concerning load inertia causes an overvoltage condition. During deceleration of the load, inertia of the system acts to sustain the running speed. Once the motor frequency drops below the running speed, the load begins overhauling the motor. The motor then becomes a generator and starts returning energy to the frequency converter. This is called regenerative energy. Regeneration occurs when the speed of the load is greater than the commanded speed. The diodes in the IGBT modules rectify this return and raises the DC link. If the amount of returned energy is too high, the DC voltage increases, causing the frequency converter to trip.
There are a few ways to overcome this situation. One method is to reduce the deceleration rate so it takes longer for the frequency converter to decelerate. A rule of thumb is that the frequency converter can only decelerate the load slightly faster than it would take for the load to naturally coast to a stop. A second method is to allow the overvoltage control function (parameter 2-17 Over-voltage Control) to take care of the deceleration ramp. When enabled, the overvoltage control function regulates deceleration at a rate that maintains the DC-link voltage at an acceptable level. One caution with overvoltage control is that it does not make corrections to unrealistic ramp rates.
For example, the deceleration ramp has to be 100 s due to the inertia, and the ramp rate is set at 3 s. Overvoltage control initially engages, then disengages and allows the frequency converter to trip. This is purposely done so the unit's operation is not misinterpreted.
5
Set parameter 1-30 Stator Resistance (Rs) and parameter 1-35 Main Reactance (Xh) parameters for the
AMA function. Use factory default values, or values that are supplied by the motor manufacturer.
BAS-SVM04B-EN 02/2017 All rights reserved. 39
The frequency converter has an AC brake function, which increases magnetization current to increase loss in motor and reduce DC-link voltage. If the DC-link voltage exceeds a certain voltage, the overvoltage control changes the frequency.
Page 41
Frequency Converter and Mot...
5
5.1.2 Mains Phase Loss Trips
The frequency converter monitors phase loss by monitoring the amount of ripple voltage on the DC bus. Ripple voltage on the DC bus is a product of a phase loss and can cause overheating in the DC-bus capacitors and the DC coil. If the ripple voltage on the DC bus is unchecked, the lifetime of the capacitors is drastically reduced.
When the input voltage becomes unbalanced or a phase disappears completely, the ripple voltage increases. This increase causes the frequency converter to trip and issue alarm 4, Mains Phase Loss. In addition to missing phase voltage, a line disturbance or imbalance can cause an increased bus ripple.
Possible sources of disturbance
Line notching.
Defective transformers.
Other loads that can aect the form factor of the
AC waveform.
Mains imbalances which exceed 3% cause sucient DC­bus ripple to initiate a trip.
Other causes of increased ripple voltage on the DC bus are:
Output disturbance.
Missing or lower than normal output voltage on
1 phase.
Checks
When a mains imbalance trip occurs, check both the input and output voltage of the frequency converter. Severe imbalance of supply voltage or phase loss is detectable with a voltmeter. View line disturbances through an oscilloscope. Conduct tests for:
Input imbalance of supply voltage.
Input waveform.
Output imbalance of supply voltage.
See details in chapter 4 Troubleshooting.
The frequency converters are designed to accept various signals. First, determine which of these signals the frequency converter is receiving:
Digital inputs (18, 19, 27, and 29).
Analog outputs (42 and 45).
10 V output.
Analog inputs (53 and 54).
Serial communication bus (68 and 69).
The presence of a correct reading indicates that the microprocessor of the frequency converter has detected the wanted signal. See chapter 2.3 Frequency Converter Inputs and Outputs.
This data can also be read in parameter group 16-6* Inputs and Outputs.
If there is no correct indication, check if the signal is present at the input terminals of the frequency converter. Use a voltmeter or oscilloscope in accordance with chapter 6.4.7 Input Terminal Signal Tests.
If the signal is present at the terminal, the control
card is defective and must be replaced.
If the signal is not present, the problem is
external to the frequency converter. Therefore, check the circuitry providing the signal along with its associated wiring.
5.1.4 Programming Problems
Diculty with operation of the frequency converter can be a result of improper programming of the frequency converter parameters.
Three areas where programming errors can frequency converter and motor operation are:
Motor settings.
References and limits.
I/O
See chapter 2.3 Frequency Converter Inputs and Outputs.
conguration.
aect
5.1.3 Control Logic Problems
Set up the frequency converter correctly for the motor or
Problems with control logic can often be dicult to diagnose, since there is usually no associated fault indication. The typical complaint is that the frequency converter does not respond to a given command. To obtain an output, give the following 2 basic commands to the frequency converter:
Start command: To execute.
Reference or speed command: To identify the
speed of execution.
40 02/2017 All rights reserved. BAS-SVM04B-EN
motors connected to it. Parameters must have data from the motor nameplate entered into the frequency converter. These data enable the frequency converter processor to match the frequency converter to power characteristics of the motor. Inaccurate motor data can cause the motor to draw higher than normal amounts of current when performing a task. In such cases, setting the correct values to these parameters and performing the AMA function usually solves the problem.
Page 42
Frequency Converter and Mot... TR150 and TR170 Service Manual
5
Any references or limits set incorrectly result in less than acceptable frequency converter performance. For instance, if maximum reference is set too low, the motor is unable to reach full speed. Set these parameters according to the requirements of the particular installation. References are set in parameter group 3-0* Reference Limits.
Incorrectly set I/O conguration usually results in the frequency converter not responding to the function as commanded. Remember that for every control terminal input or output there are corresponding parameter settings. These settings determine how the frequency converter responds to an input signal or the type of signal present at that output. Utilizing an I/O function involves a 2-step process. Wire the wanted I/O terminal properly, and set the corresponding parameter accordingly. Control terminals are programmed in parameter group 5-0* Digital I/O Mode and parameter group 6-0* Analog I/O Mode.
5.1.5 Motor/Load Problems
Problems with the motor, motor wiring, or mechanical load on the motor can develop in several ways. The motor or motor wiring can develop a phase-to-phase or phase-to­ground short circuit resulting in an alarm indication. Check whether the problem is in the motor wiring or the motor itself.
A motor with unbalanced, or asymmetrical, impedances on all 3-phases can result in uneven or rough operation, or unbalanced output currents. For measurements, use a clamp-on style ammeter to determine whether the current is balanced on the 3 output phases. See chapter 6.4.6 Output Imbalance of Motor Supply Voltage Test.
5.2 Internal Frequency Converter Problems
5.2.1 Overtemperature Faults
If an overtemperature indication is shown, determine whether this condition actually exists within the frequency converter, or whether the thermal sensor is defective.
5.2.2 Current Sensor Faults
Sometimes an over-current alarm that cannot be reset, even with the motor cables disconnected, indicates when a current sensor fails. However, the frequency converter experiences frequent false ground fault trips. This is due to the DC oset failure mode of the sensors.
The simplest method of determining whether a current sensor is defective is to disconnect the motor from the frequency converter. Then observe the current in the frequency converter display. With the motor disconnected, the current should be zero. A frequency converter with a defective current sensor indicates some current ow. An indication of a fraction of 1 A is tolerable. However, that value should be considerably less than 1 A. If the display shows more than 1 A of current, there is a defective current sensor. All 3 current sensors in TR150 and TR170 units are mounted on one circuit board (either power card, SMPS card, or current transducer card). The repair procedure is to replace all 3 current sensors at the same time.
5.2.3 Signal and Power Wiring Considerations for Electromagnetic Compatibility
5
Usually, a current limit warning indicates an incorrect mechanical load. If possible, disconnect the motor from the load to determine if the load is incorrect.
Often, the indications of motor problems are similar to the problems of a defect in the frequency converter itself. To determine whether the problem is internal or external to the frequency converter, disconnect the motor from the frequency converter motor terminals. Perform the initial procedure with no motor connection on all 3-phases with an analog voltmeter, see chapter 6.4.6 Output Imbalance of Motor Supply Voltage Test. If the 3 voltage measurements are balanced, the frequency converter is functioning correctly. Hence, the problem is external to the frequency converter.
If the voltage measurements are not balanced, the frequency converter is malfunctioning. Typically, 1 or more output IGBTs are not functioning correctly. This problem can be a result of a defective IGBT or gate signal.
BAS-SVM04B-EN 02/2017 All rights reserved. 41
This section provides an overview of general signal and power wiring considerations when addressing the electro­magnetic compatibility (EMC) concerns for typical commercial and industrial equipment. Only certain high frequency phenomena (such as RF emissions, RF immunity) are discussed. Low-frequency phenomena (such as harmonics, mains voltage imbalance, notching) are not covered.
NOTICE
Special installations or compliance to the European CE EMC directives require strict adherence to relevant standards and are not discussed here.
Page 43
Frequency Converter and Mot...
5
5.2.4 Eects of EMI
While electromagnetic interference-related (EMI) distur­bances to the operation of the frequency converter are uncommon, the following detrimental EMI eects sometimes occur:
Motor speed
Serial communication transmission errors.
Frequency converter CPU exception faults.
Unexplained frequency converter trips.
A disturbance resulting from other nearby equipment is more common. Generally, other industrial control
uctuations.
equipment has a high level of EMI immunity. However, non-industrial, commercial, and consumer equipment is often susceptible to lower levels of EMI.
Detrimental eects to these systems include the following:
Pressure/ow/temperature signal transmitter
signal distortion or aberrant behavior.
Radio and TV interference.
Telephone interference.
Computer network data loss.
Digital control system faults.
5.2.5 Sources of EMI
Modern frequency converters (see Illustration 5.1) utilize fast-switching electronic devices to generate the modulated output voltage waveform necessary for accurate motor control. These devices rapidly switch the xed DC-link voltage creating a variable frequency, and variable voltage PWM waveform. This high rate of voltage change [dU/dt] is the primary source of the frequency converter generated EMI.
The high rate of voltage change caused by the IGBT switching creates high frequency EMI.
1RFIlter 6 PWM waveform
2Rectier 7 IGBT
3DC link 8 Filter reactor
4Inverter 9 Sine-wave
5Motor 10 AC line
Illustration 5.1 Frequency Converter Principle Diagram
42 02/2017 All rights reserved. BAS-SVM04B-EN
Page 44
Frequency Converter and Mot... TR150 and TR170 Service Manual
5
5.2.6 EMI Propagation
Frequency converter generated EMI is both conducted to the mains and radiated to nearby conductors. See Illustration 5.2.
1AC line
2 Frequency converter
3Motor cable
4Motor
1AC line
2 Frequency converter
3Motor cable
4Motor
5 Stray capacitance
6 Signal wiring
7 Signal wiring
8 Signal wiring
9Ground
Illustration 5.2 Ground Currents
5 Stray capacitance
6AC line, to BMS
7 Signal wiring
Illustration 5.3 Signal Conductor Currents
NOTICE
Unprotected or poorly routed signal conductors located close to or in parallel to motor and mains conductors are susceptible to EMI.
5
NOTICE
Stray capacitance between the motor conductors, equipment ground, and other nearby conductors results in induced high frequency currents.
High ground circuit impedance at high frequencies results in an instant voltage at points reputed to be at ground potential. This voltage can appear throughout a system as a common mode signal that can interfere with control signals.
Theoretically, these currents return to the DC-bus via the ground circuit and a high frequency (HF) bypass network within the frequency converter itself. However, imperfections in the frequency converter grounding or the equipment ground system can cause some of the currents to travel out to the power network.
Signal conductors are especially vulnerable when they run in parallel to the power conductors for any distance. EMI coupled into these conductors can aect either the frequency converter or the interconnected control device. See Illustration 5.3.
While these currents tend to travel back to the frequency converter, imperfections in the system cause some current to ow in undesirable paths. This ow exposes other locations to the EMI.
NOTICE
High frequency currents can be coupled into the mains supplying the frequency converter, when the mains conductors are located close to the motor cables.
BAS-SVM04B-EN 02/2017 All rights reserved. 43
Page 45
Frequency Converter and Mot...
5
5.2.7 Preventive Measures
EMI-related problems are more eectively alleviated during the design and installation phases rather than after the system is in service. Many of the listed steps can be implemented at a relatively low cost compared to the cost of identifying and
Grounding
Ground the frequency converter and motor solidly to the equipment frame. A good high-frequency connection is necessary to allow the high frequency currents to return to the frequency converter instead of traveling through the power network. The ground connection is has high impedance to high frequency currents. Therefore, it must be as short and direct as possible. Flat-braided cable has lower high frequency impedance than round cable. Mounting the frequency converter or motor onto a painted surface creates an eective ground connection. In addition, running a separate ground conductor directly between the frequency converter and the running motor is recommended.
Cable routing
Avoid parallel routing of:
Motor wiring.
Mains wiring.
Signal wiring.
If parallel routing is unavoidable, preferably maintain a separation of 200 mm (6–8 in) between the cables or separate them with a grounded conductive partition. Avoid routing cables through free air.
the problem later.
xing
ineective
if it
separately from the signal and mains wiring, no further consideration is needed. If the conductors are routed close to other susceptible conductors, or if the system is suspected to cause EMI problems, consider alternate motor wiring methods.
Installing shielded power cable is the most eective way to alleviate EMI problems. The cable shield forces the noise current to ow directly back to the frequency converter. Thus, the noise current cannot get back into the power network or take other undesirable high frequency paths. Unlike most signal wiring, the shielding on the motor cable must be terminated at both ends.
If a shielded motor cable is not available, then 3-phase conductors along with ground in a conduit provides some degree of protection. This technique is not as eective as shielded cable due to the unavoidable contact of the conduit with various points within the equipment.
Serial communications cable selection
There are various serial communication interfaces and protocols in the market. Each of these interfaces recommends 1 or more specic types of twisted pair, shielded twisted pair, or proprietary cables. Refer to the manufacturer’s documentation when selecting these cables. Similar recommendations apply to serial communi­cation cables as to other signal cables. Using twisted-pair cables and routing them away from power conductors is encouraged. While shielded cable provides extra EMI protection, the shield capacitance may reduce the maximum allowable cable length at high data rates.
Signal cable selection
Single conductor 600 V rated wires provide the least protection from EMI. Twisted pair and shielded twisted-pair cables are available which are designed to minimize the eects of EMI. While unshielded twisted-pair cables are often adequate, shielded twisted-pair cables provide another degree of protection. Terminate the signal cable shield in a manner that is appropriate for the connected equipment. Avoid terminating the shield through a pigtail connection as it increases the high frequency impedance and spoils the eectiveness of the shield.
A simple alternative is to twist the existing single conductors to provide a balanced capacitive and inductive coupling. This operation cancels dierential mode interference. While not as eective as true twisted-pair cable, it can be implemented in the eld using the materials at hand.
Motor cable selection
Motor conductors have the greatest inuence on the EMI characteristics of the system. These conductors must receive the highest attention whenever EMI is a problem. Single conductor wires provide the least protection from EMI emissions. Often, if these conductors are routed
44 02/2017 All rights reserved. BAS-SVM04B-EN
Page 46
Test Procedures TR150 and TR170 Service Manual
6
6 Test Procedures
6.1 Non-repairable Units
H1–H5 and I2–I4 are non-repairable units and should not be repaired. The information about Line/Motor/UDC+­terminals is useful to verify what went wrong with these frequency converters, for statistics and WIIS purposes, but also to avoid replacing a frequency converter that is not defective.
6
1Line
2Ground
3Motor
4Relays
Illustration 6.1 H1–H5 Frame
IP20 200–240 V, 0.25–11 kW and IP20 380–480 V, 0.37–22 kW
1 RS485
2 Line in
3Ground
4Wire clamps
5Motor
6UDC
7Relays
8I/O
Illustration 6.2 I2 Frame
IP54 380–480 V, 0.75–4.0 kW
BAS-SVM04B-EN 02/2017 All rights reserved. 45
Page 47
6
Test Procedures
1RS485
2Line in
3Ground
4Wire clamps
5 Motor
6UDC
7Relays
8I/O
Illustration 6.3 I3 Frame
IP54 380–480 V, 5.5–7.5 kW
1 RS485
2 Line in
3Ground
4Wire clamps
5Motor
6UDC
7Relays
8I/O
Illustration 6.4 I4 Frame
IP54 380–480 V, 0.75–4.0 kW
46 02/2017 All rights reserved. BAS-SVM04B-EN
Page 48
Test Procedures TR150 and TR170 Service Manual
6
Oscilloscope
6.2 Introduction
WARNING
Current meter
6.3 Static Test Procedures
DISCHARGE TIME!
Frequency converters contain DC-link capacitors that can remain charged even when the frequency converter is not powered. To avoid electrical hazards, disconnect AC mains, any permanent magnet type motors, and any remote DC-link power supplies, including battery back­ups, UPS, and DC-link connections to other frequency converters. Wait for the capacitors to fully discharge before performing any service or repair work. The amount of wait time is listed in the Tabl e 1.1. Failure to wait the specied time after power has been removed before doing service or repair could result in death or serious injury.
This section contains detailed procedures for testing frequency converters. Previous sections of this manual provide symptoms, alarms, and other conditions which require additional test procedures to diagnose the frequency converter further. The results of these tests indicate the appropriate repair actions. Again, because the frequency converter monitors input and output signals, motor conditions, AC, and DC power and other functions, the source of fault conditions may exist outside of the frequency converter. Testing described here isolates many of these conditions as well. Disassembly and Assembly Instructions describes detailed procedures for removing and replacing frequency converter components.
The purpose of performing static testing is to check for any short circuit of the power components.
For all tests, use a meter capable of testing diodes. Use a digital Volt-Ohm Meter (VOM) set on the diode scale or an analog ohmmeter set on Rx100 scale.
Before making any checks, disconnect all connections for:
Input.
Motor.
Brake resistor.
Ensure that the frequency converter is disconnected from power, before performing static tests.
WARNING
SHOCK HAZARD
Disconnection of the input cable while the frequency converter is powered could result in electrical shock causing death or personal injury.
Do not disconnect the input cable while the
frequency converter is powered.
6.3.1 Pre-test Precautions
6
Frequency converter testing is divided into Static Tests, and Dynamic Tests. Static tests are conducted without power
applied to the frequency converter. Most frequency converter problems can be diagnosed simply with these tests. Static tests are performed with little or no disassembly. The purpose of static testing is to check for shorted power components. Perform these tests on any unit suspected of containing faulty power components before applying power.
CAUTION
For dynamic test procedures, main input power is required. All devices and power supplies connected to mains are energized at rated voltage. Use extreme caution when conducting tests on a powered frequency converter. Contact with powered components could result in electrical shock and personal injury.
Dynamic tests are performed with power applied to the frequency converter. Dynamic testing traces signal circuitry to isolate faulty components.
Digital voltmeter/ohmmeter capable of reading
real RMS
Analog voltmeter
Consider the following safety precautions before performing static tests.
Prepare the work area according to the ESD
regulations.
Ground the ESD mat and wrist strap.
Ensure that the ground connection between
body, the ESD mat, and the frequency converter is always present while performing service.
Handle disassembled electronic parts with care.
Perform the static test before powering up the
fault unit.
Perform static test after completing the repair
and assembly of the frequency converter.
Connect the frequency converter to the mains
only after completion of static tests.
Complete all necessary precautions for system
start-up, before applying power to frequency converter.
BAS-SVM04B-EN 02/2017 All rights reserved. 47
Page 49
Test Procedures
6
6.3.2 Rectier Circuit Test
Pay close attention to the polarity of the meter leads to ensure the an incorrect reading appears.
Described next is the procedure to conduct the static test on the
identication
rectier.
of any faulty component, in case
NOTICE
In H6 units the +/-UDC terminals are not readily accessible. Find terminals K601 (+) and K611 (-) between the DC capacitors. In H7-H8 units the +/-UDC terminals are directly accessible on MK900 on the power card. In I7-I8 units the +/-UDC terminals are accessible on MK900 on the power card or on MK3 on the current sensor board. For further details, see chapter 6.3.5 Location of UDC Terminals before measuring).
Before starting tests, ensure that meter is set to diode scale.
Rectier test part I
1. Connect the positive (+) terminal of the multimeter lead to the positive (+) DC Bus.
2. Connect the negative (-) terminal of the multimeter lead to the input terminal L1, L2, L3 in turn. The multimeter indicates Innity.
Rectier test part II
3. Reverse the meter leads by connecting the negative (-) terminal of the multimeter lead to the positive (+) DC Bus.
4. Connect the positive (+) terminal of the multimeter lead to the input terminal L1, L2, L3 in turn. The multimeter indicates Diode drop.
Rectier test part III
5. Connect the positive (+) terminal of the multimeter lead to the negative (-) DC Bus.
6. Connect the negative (-) terminal of the multimeter lead to the input terminal L1, L2, L3 in turn. The multimeter indicates a diode drop.
Rectier test part IV
7. Reverse the meter leads by connecting the negative (-) terminal of the multimeter lead to the negative (-) DC Bus.
8. Connect the positive (+) terminal of the multimeter lead to the input terminal L1, L2, L3 in turn. The multimeter indicates Innity.
6.3.3 Inverter Section Tests
The inverter section is primarily made up of the IGBTs used for switching the DC bus voltage to create the output to the motor. The frequency converter also has clamping capacitors between +UDC and -UDC on the IGBT.
CAUTION
Disconnect motor cables when testing inverter section. With leads connected, a short circuit in one phase reads in all phases, making isolation
Before starting tests, ensure that meter is set to diode scale.
Inverter test part I
1. Connect the positive (+) meter lead to the positive (+) DC bus terminal.
2. Connect the negative (-) meter lead to terminals U, V, and W in sequence.
Each reading must show innity.
Inverter test part II
1. Reverse the meter leads by connecting the negative (-) meter lead to the positive (+) DC bus terminal.
2. Connect the positive (+) meter lead to U, V, and W in sequence. Each reading should show a diode drop.
Inverter test part III
1. Connect the positive (+) meter lead to the negative (-) DC bus terminal.
2. Connect the negative (-) meter lead to terminals U, V, and W in sequence. Each reading should show a diode drop.
Inverter test part IV
1. Reverse the meter leads by connecting the negative (-) meter lead to the negative (-) DC bus terminal.
2. Connect the positive (+) meter lead to U, V, and W in sequence.
Each reading should show innity.
dicult.
48 02/2017 All rights reserved. BAS-SVM04B-EN
Page 50
Test Procedures TR150 and TR170 Service Manual
6
6.3.4 Intermediate Section Tests
NOTICE
This test is applicable for H7, H8, I7, and I8 units only.
The intermediate section of the frequency converter is made up of the DC bus capacitors, the DC coils, and the balance circuit for the capacitors.
1. Test for short circuits with the ohmmeter set on Rx100 scale or, for a digital meter, select diode.
2. Measure across the positive (+) DC terminal and the negative (–) DC terminal. Observe the meter polarity.
3. The meter starts out with low ohms and then move towards capacitors.
4. Reverse meter leads.
5. The meter pegs at zero while the meter discharges the capacitors. The meter then begins moving slowly toward 2 diode drops as the meter charges the capacitors in the reverse direction. Although the test does not ensure that the capacitors are fully functional, it ensures that no short circuits exist in the DC link.
Incorrect reading
A short circuit could be caused by a short in the inrush circuit, rectier, or inverter section. Be sure that the tests for these circuits have already been performed successfully. A failure in one of these sections could be read in the intermediate section since they are all routed via the DC bus.
The only other likely cause would be a defective capacitor within the capacitor bank.
There is not an is fully assembled. If suspecting a failure within the capacitor bank, replace the entire bank. Replace the capacitor bank in accordance with the disassembly procedures.
eective
as the meter charges the
innity
test of the capacitor bank when it
6.3.5 Location of UDC Terminals
H6
Remove the IP20 front cover, then remove the capacitor vibration support. The terminals K601 (+UDC) and K611 (­UDC) are located between the 4 capacitors on the circuit board. Remove the metal cover to access these terminals.
6
Illustration 6.5 UDC Terminals Location on H6 Frequency
Converter
Illustration 6.6 Metal Cover over Terminals
BAS-SVM04B-EN 02/2017 All rights reserved. 49
Page 51
6
Test Procedures
Illustration 6.7 The UDC Terminals on the Circuit Board
Illustration 6.9 +/- UDC Terminals
H9
The UDC terminals are available on connectors at the bottom of the frequency converter. Static measurements can be done directly from here.
H7 and H8
Remove the IP20 front cover to access the terminals directly on the power card MK900.
Illustration 6.10 UDC Terminals Location on H9 Frequency
Converter
Illustration 6.8 Power Card
50 02/2017 All rights reserved. BAS-SVM04B-EN
Page 52
Test Procedures TR150 and TR170 Service Manual
6
H10
Remove the front terminal cover to access the connectors. The UDC terminals are located inside the frequency converter.
Illustration 6.13 +/- UDC Terminals on Current Sensor Board
Illustration 6.11 UDC Terminals Location on H10 Frequency
Converter
6
I7 and I8
Remove the IP54 front cover to access the +/- UDC terminals, either on the power card MK900 or on MK3 on the current sensor board.
Illustration 6.12 +/- UDC Terminals on Power Card
Illustration 6.14 +/- UDC Terminals on Current Sensor Board -
Close-up View
BAS-SVM04B-EN 02/2017 All rights reserved. 51
Page 53
Test Procedures
6
6.4 Dynamic Test Procedures
NOTICE
Test procedures in this section are numbered for reference only. Tests do not need to be performed in this order. Perform tests only as necessary.
WARNING
Never disconnect the input cabling to the frequency converter with power applied due to danger of severe injury or death.
CAUTION
Take all the necessary safety precautions for system start-up before applying power to the frequency converter.
Dynamic tests are conducted to check the IGBT. The tests can indicate if an IGBT is faulty. The fault is indicated by a voltage drop on the terminals UVW.
Preparation:
Disconnect the motor from the frequency
converter.
Ensure that the frequency converter is powered
up.
Program the frequency converter to approxi-
mately 50 Hz on start.
Set the multimeter to AC 1000 V.
Procedure for dynamic test on the IGBT.
1. Connect the positive terminal of the multimeter lead to the U connector, and connect the negative terminal to the V terminal.
2. Connect the positive terminal of the multimeter lead to the U connector, and connect the negative terminal to the W terminal.
3. Connect the positive terminal of the multimeter lead to the V connector, and connect the negative terminal to the W terminal.
The meter reading is 450 V ±25 V when performing the dynamic test at 400 V mains. With PM motors the reading may dier. Contact hotline for help.
6.4.1 No Display Test (Display is Optional)
A frequency converter with no display in the LCP can be the result of several causes. First, verify that there is no display. A single character in the display or a dot in the upper corner of the display indicates a communication error. Check that all option cards are properly installed. When this condition occurs, the green power-on LED is illuminated.
If the LCD display is dark and the green power-on LED is not lit, proceed with the following tests.
First test for proper input voltage.
6.4.2 Input Voltage Test
1. Apply power to frequency converter.
2. Use the DVM to measure the input mains voltage between the frequency converter input terminals in sequence: L1 to L2 L1 to L3 L2 to L3
For 380 V frequency converters, all measurements must be within the range of 342–550 V AC. Readings of less than 342 V AC indicate problems with the input mains voltage. For 525–600 V frequency converters, all measurements must be within the range of 446–600 V AC. Readings of less than 446 V AC indicate problems with the input mains voltage.
In addition to the actual voltage reading, the balance of the voltage between the phases is also important. The frequency converter can operate within long as the imbalance of supply voltage is not more than 3%.
calculates mains imbalance per an IEC
Imbalance=0.67 X (V
For example, if 3-phase readings were taken and the results were 500 V AC, 478.5 V AC, and 478.5 V AC; then 500 V AC is V resulting in an imbalance of 3%.
, 478.5 V AC is V
max
max–Vmin
specications
specication.
)/V
avg
, and 485.7 V AC is V
min
as
avg
,
The reading must be within ±1.5%.
52 02/2017 All rights reserved. BAS-SVM04B-EN
Although the frequency converter can operate at higher mains imbalances, the lifetime of components, such as DC bus capacitors, is shortened.
Page 54
Test Procedures TR150 and TR170 Service Manual
6
Incorrect reading
CAUTION
Open (blown) input fuses or tripped circuit breakers usually indicate a more serious problem. Before replacing fuses or resetting breakers, perform static tests.
An incorrect reading here requires further investigation of the main supply. Typical items to check would be:
Open (blown) input fuses or tripped circuit
breakers
Open disconnects or line side contactors
Problems with the power distribution system
If this test was successful, check for voltage to the control card.
6.4.3 Basic Control Card Voltage Test
1. Measure the control voltage at terminal 12 with reference to terminal 20. The meter must read 21–27 V DC.
An incorrect reading here could indicate that a fault in the customer connections loads down the supply. Disconnect control wiring and repeat the test. If this test is successful, then continue. Remember to check the customer connections. If still unsuccessful, replace the unit.
2. Measure the 10 V DC control voltage at terminal 50 with reference to terminal 55. The meter must read between 9.2 and 11.2 V DC.
An incorrect reading here could indicate that a fault in the customer connections loads down the supply. Disconnect control wiring and repeat the test. If this test is successful, then continue. Remember to check the customer connections. If still unsuccessful, replace the unit.
6.4.4 Input Imbalance of Supply Voltage Tes t
Theoretically, the current drawn on all 3 input phases must be equal. Some imbalance may be seen, however, due to variations in the phase-to-phase input voltage, and single­phase loads within the frequency converter.
Voltage imbalances automatically result in a corresponding current imbalance.
2. Apply power to the frequency converter and place it in run.
3. Using a clamp-on ammeter (analog preferred), read the current on each of 3 input lines at L1 (R), L2 (S), and L3 (T). Typically, the current should not vary from phase­to-phase by more than 5%. If a greater current variation exists, it indicates a possible problem with the mains supply to the frequency converter, or a problem within the frequency converter. One way to determine if the mains supply is at fault is to swap 2 of the incoming phases. This assumes that 2 phases read 1 current while the 3 deviates by more than 5%. If all 3-phases are dierent from one another, swap the phase with the highest current with the phase with the lowest current:
3a Remove power to the frequency
converter.
3b Swap the phase that appears to be
incorrect with 1 of the other 2 phases.
3c Reapply power to the frequency
converter and place it in run.
3d Repeat the current measurements.
If the imbalance of supply voltage moves with swapping the leads, the mains supply is suspect. Otherwise, it may indicate a problem with the gating of the rectiers.
rd
6.4.5 Input Waveform Test
Testing the current waveform on the input of the frequency converter can help troubleshooting mains phase loss conditions or suspected problems with the diode modules. Phase loss caused by the mains supply can be easily detected. In addition, the diode modules control the rectier section. If 1 of the diode modules become defective, the frequency converter provides a response which is the same as loss of 1 of the phases.
The following measurements require an oscilloscope with voltage and current probes.
6
A current measurement of each phase reveals the balanced condition of the line. To obtain an accurate reading, the frequency converter must run at its rated load, or at a load of not less than 40%.
1. Perform the input voltage test before checking the current, in accordance with procedure.
BAS-SVM04B-EN 02/2017 All rights reserved. 53
Under normal operating conditions, the waveform of a single-phase of input AC voltage to the frequency converter appears as in Illustration 6.15.
Page 55
6
Test Procedures
Illustration 6.15 Normal AC Input Voltage Waveform
The waveform shown in Illustration 6.16 shows the input current waveform for the same phase as shown in Illustration 6.15 while the frequency converter is running at 40% load. The 2 positive and 2 negative jumps are typical of any 6-diode bridge. It is the same for frequency converters with diode modules.
6.4.6 Output Imbalance of Motor Supply Voltage Test
Check the balance of the output voltage and current to measure the electrical functioning between the frequency converter and the motor. In testing the phase-to-phase output, both voltage and current are monitored. Conduct static tests on the inverter section of the frequency converter before this procedure.
If the voltage is balanced, but the current is not, it indicates that the motor is drawing an uneven load. This could be the result of a defective motor, a poor connection in the wiring between the frequency converter and the motor, or a defective motor overload.
If the output current and the voltage are unbalanced, it indicates that the frequency converter is not working properly. It could be the result of a defective power card or an improper connection of the output circuitry.
Illustration 6.16 AC Input Current Waveform with Diode Bridge
With a phase loss, the current waveform of the remaining phases would take on the appearance shown in Illustration 6.17.
Illustration 6.17 Input Current Waveform with Phase Loss
Always verify the condition of the input voltage waveform before drawing a conclusion. The current waveform follows the voltage waveform. If the voltage waveform is incorrect, proceed to investigate the reason for the AC supply problem. If the voltage waveform on all 3-phases is correct, but the current waveform is not, the input in the frequency converter is suspect. Perform the static soft-charge and module test.
tests, and also the dynamic diode
rectier
rectier
circuit
NOTICE
Use an analog voltmeter for monitoring output voltage. Digital voltmeters are sensitive to waveform and switching frequencies and commonly return erroneous readings.
Perform the initial test with the motor connected and running its load.
If suspect readings are recorded, then:
Stop the motor and wait until the motor has
stopped rotating.
Set the frequency converter to coast.
Disconnect the motor cables to isolate the
problem further.
Then:
1. Using a voltmeter, measure AC output voltage at frequency converter motor terminals U, V, and W. Measure phase-to-phase checking U to V, then U to W, and then V to W. All 3 readings must be within 8 V AC of each other. The actual value of the voltage depends on the speed at which the frequency converter is running. The V/Hz ratio is relatively linear (except in VT mode). For example, if the rated motor frequency is 60 Hz, the voltage should be approx­imately equal to the applied mains voltage. At 30 Hz, it is about half of the applied mains voltage for any other speed selected. The exact voltage reading is less important than balance between phases.
2. Stop the frequency converter and disconnect mains.
54 02/2017 All rights reserved. BAS-SVM04B-EN
Page 56
Test Procedures TR150 and TR170 Service Manual
6
3. Reconnect the motor to the frequency converter.
4. Connect mains to the frequency converter, and start the frequency converter.
5. Monitor current on the 3 output phases at the motor terminals U, V, and W, using the clamp-on ammeter. An analog device is preferred. To achieve an accurate reading, run the frequency converter above 40 Hz as this is normally the frequency limitation of such meters.
The output current must be balanced from phase-to-phase, and no phase must be more than 2–3% dierent from another. If these tests are successful, the frequency converter is operating normally.
6. If the imbalance is greater than described previously, disconnect the motor cables and repeat the voltage balance test.
7. Stop the motor and disconnect mains from the frequency converter.
Since the current follows the voltage, it is necessary to dierentiate between a load problem and a frequency converter problem. When a voltage imbalance in the output is detected with the motor disconnected, the inverter is faulty. Exchange the frequency converter.
6.4.7 Input Terminal Signal Tests
The presence of signals on either the digital or analog input terminals of the frequency converter can be veried on the frequency converter display. Digital or analog input status can be selected or read in parameters 16-60 to 16-64.
Digital inputs
With digital inputs shown, control terminals 18, 19, 27, and 29 are shown left to right, with a 1 indicating the presence of a signal.
If the desired signal is not present in the display, the problem is either in the external control wiring to the frequency converter or a faulty control card. To determine the fault location, use a voltmeter to test for voltage at the control terminals.
Verify that the control voltage power supply is correct as follows:
1. Use a voltmeter for measuring voltage at control card terminal 12 and 13 with respect to terminal
20. The meter should read 21-27 V DC.
If the 24 V supply voltage is not present, test the control card in chapter 6.2.1 Introduction.
If 24 V is present, proceed with checking the individual inputs as follows:
2. Connect the (-) negative meter lead to reference terminal 20.
3. Connect the (+) positive meter lead to the terminals in sequence.
The presence of a signal at the desired terminal must correspond to the digital input display readout. A reading of 24 V DC indicates the presence of a signal. A reading of 0 V DC indicates that no signal is present.
Analog inputs
The value of signals on analog input terminals 53 and 54 can also be shown. The voltage or current in mA, depending on the switch setting, is shown in line 2 of the display.
If the desired signal is not present in the display, the problem is either in the external control wiring to the frequency converter, or a faulty control card. To determine the fault location, use a voltmeter to test for a signal at the control terminals.
Verify that the reference voltage power supply is correct as follows.
1. Use a voltmeter for measuring the voltage at control card terminal 50 with respect to terminal
55. The meter must read between 9.2 and 11.2 V DC.
If the 10 V supply voltage is not present, conduct basic control card voltage test, see chapter 6.4.3 Basic Control Card Voltage Test.
If 10 V is present, proceed with checking the individual inputs as follows.
2. Connect the (-) negative meter lead to reference terminal 55.
3. Connect the (+) positive meter lead to desired terminal 53 or 54.
For analog input terminals 53 and 54, a DC voltage between 0 and +10 V DC must be read to match the analog signal sent to the frequency converter. Or a reading of 0.9 V DC to 4.8 V DC corresponds to a 4–20 mA signal.
NOTICE
A (-) minus sign preceding any reading above indicates a reversed polarity. In this case, reverse the wiring to the analog terminals.
6
BAS-SVM04B-EN 02/2017 All rights reserved. 55
Page 57
6
Test Procedures
6.5 Initial Start-up Or After Repair Drive Tests
Perform these tests under the following conditions:
Starting a frequency converter for the rst time.
Approaching a frequency converter that is
suspected of being faulty.
After repair of the frequency converter.
Following this procedure ensures that all circuitry in the frequency converter is functioning properly before putting it into operation.
1. Perform visual inspection procedures as described in Table 4.1.
2. Perform static test procedures to ensure that the frequency converter is safe to start.
3. Disconnect motor cables from output terminals (U, V, W) of the frequency converter.
4. Apply AC power to frequency converter.
5. Give the frequency converter a run command and slowly increase reference (speed command) to approximately 40 Hz.
6. Use an analog voltmeter or a DVM capable of measuring true RMS to measure phase-to-phase output voltage on all 3-phases: U to V, U to W, V to W. All voltages must be balanced within 8 V. If measuring unbalanced voltage, refer to
chapter 6.4.6 Output Imbalance of Motor Supply Voltage Test.
7. Stop the frequency converter and remove input power. Wait for the discharge time listed in Tab l e 1.1 to allow DC capacitors to discharge fully.
8. Reconnect motor cables to frequency converter output terminals (U, V, W).
9. Reapply power and restart the frequency converter. Adjust motor speed to a nominal level.
10. Set load to 50%.
11. Using a clamp-on ammeter, measure output current on each output phase. All currents must be balanced.
12. The correct measurement is 50% rated current.
56 02/2017 All rights reserved. BAS-SVM04B-EN
Page 58
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7 H-Frame Size Disassembly and Assembly Instructions
7.1 Electrostatic Discharge (ESD)
CAUTION
Frequency converters contain dangerous voltages when connected to the main voltage. Never perform any disassembly when power is applied. Remove power to the frequency converter, and wait until the frequency converter capacitors fully discharge. Only a competent technician must carry out the service. Many electronic components within the frequency converter are sensitive to static electricity. Voltages so low that they cannot be felt, seen, or heard can reduce the life, aect performance, or completely destroy sensitive electronic components.
CAUTION
Use correct ESD procedures to prevent damage to sensitive components when servicing the frequency converter.
NOTICE
Frame size is used throughout this manual where ever procedures or components dier between frequency converters based upon the unit's physical size. Refer to chapter 1.4.1 Frame Size Denitions to determine frame size.
7.3 H6 Frame Size Disassembly and Assembly Instructions
7.3.1 Control Card and Control Card
Mounting Plate
1. Remove the LCP and the protection foil underneath it.
2. Remove the 3 screws (T10) from the control card.
3. Remove the control card.
4. Remove the 4 bolts on the bottom of the frame underneath the cable connector.
5. Remove the screws (T10) in the control card mounting plate.
6. Press barbs on ribbon cable and remove it.
7. Remove screws (T20) in cover plate.
8. Remove the control card mounting plate.
Reinstall in the reverse order.
7
7.2 General Disassembly Procedure
This procedure explains how to remove the outer parts of the frequency converter that are common for H frame sizes. When this procedure is completed, the inside components are accessible.
1. Remove the plastic cover beneath the LCP with a at-edged screwdriver.
2. Loosen and remove 4 screws (T20) on the front cover.
3. Remove the front cover.
BAS-SVM04B-EN 02/2017 All rights reserved. 57
Page 59
7
H-Frame Size Disassembly a...
7.3.2 Heat sink Fan Assembly
1. Unplug the fan cable
2. Remove 4 screws on fan cover plate.
3. Remove the fan.
Reinstall in the reverse order.
1LCP
2Cradle
3 Control card
4 Control card mounting plate
Illustration 7.1 Control Card and Control Card Mounting Plate
1Fan cover plate
2Screws
3Fan assembly
Illustration 7.2 Heat Sink Fan Assembly
58 02/2017 All rights reserved. BAS-SVM04B-EN
Page 60
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.3.3 DC Coil
1. Remove the 4 screws on the DC coil cover to access the DC coils.
2. Remove the 4 screws to loosen the cables from the DC Link card.
3. Remove the 6 screws on the DC coils (3 screws on each coil).
4. Remove the coils.
Reinstall in the reverse order.
7.3.4 DC Link Card
1. Remove the 6 screws on coil mounting plate.
2. Remove the coil mounting plate.
3. Loosen the 4 screws from the DC Link card.
4. Press one of the barbs to loosen the link card.
5. Unplug the 10-pin ribbon cable and the cable.
6. Remove the DC Link card.
Reinstall in the reverse order. Join the mounting snaps.
lter
7
1 DC coil cover
2DC coils
Illustration 7.3 DC Coil
BAS-SVM04B-EN 02/2017 All rights reserved. 59
1Coil mounting plate
2 Capacitor bank metal cover
3DC link card
Illustration 7.4 DC Link Card
Page 61
H-Frame Size Disassembly a...
7
7.3.5 RFI Filter
1. Remove the protection cover.
2. Remove the 6 distance bushes.
3. Remove the 2 screws on the frame side.
4. Remove the 3 screws from U V W cables.
5. Press the barbs on the side of the
6. Remove the RFI
Reinstall in the reverse order.
lter.
7.3.6 Power Card
1. Remove the 3 screws on the U V W cable connector.
2. Remove the connector.
3. Remove the 3 small screws (T10) from the power card.
lter.
NOTICE
If it is dicult to get out the screws, use a magnet.
4. Remove the 6 remaining screws (T20).
5. Lift the power card and slide it out of the frame.
Reinstall in the reverse order.
NOTICE
If it is dicult to remove the power card, it is helpful to press the frame sides outwards while pressing the barbs on the side of the power card.
1RFIlter
2EMC shield
Illustration 7.5 RFI Filter
60 02/2017 All rights reserved. BAS-SVM04B-EN
1Power card
2Power card mounting plate
Illustration 7.6 Power Card
Page 62
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.4 H7 Frame Size Disassembly and Assembly Instructions
7.4.1 Control Card and Control Card
Mounting Plate
1. Remove the LCP by pressing the barbs on the side.
2. Remove the foil.
3. Remove the 3 screws (T10).
4. Gently, lift o the control card.
5. Press the barb on the LCP ribbon cable and pull it out of the control card mounting plate.
6. Remove the mounting plate.
Reinstall in the reverse order.
7.4.2 Power Card
1. Remove the LCP ribbon cable from the power card.
2. Unplug all other cables from the power card, including the 3 gate cables at the bottom of the card.
3. Remove the 3 screws (T20) from the mounting plate.
4. Remove the power card by pushing in the 6 retaining clips.
NOTICE
Use a screwdriver if the retaining clips are hard to reach.
5. Slide the power card out and remove it.
Reinstall in the reverse order.
7
1Power card
1LCP
2Cradle
3 Control card
4 Control card mounting plate
Illustration 7.7 Control Card and Control Card Mounting Plate
BAS-SVM04B-EN 02/2017 All rights reserved. 61
Illustration 7.8 Power Card
Page 63
H-Frame Size Disassembly a...
7
7.4.3 Inrush Card
1. Remove the 2 screws (T20) from the lter shield.
2. Remove the shield.
3. Remove the 4 screws (T20) from the power card mounting plate.
4. Remove the power card mounting plate.
5. Unplug all cables from the inrush card.
6. Remove the 6 screws (T20) from the inrush card.
7. Remove the inrush card.
Reinstall in the reverse order.
7.4.4 RFI Filter
1. Remove the red/black cables from the lter cable.
2. Remove the protective foil.
3. Remove the 3 key.
4. Remove the 2 screws (T20) from the EMC shield.
5. Remove the EMC shield.
6. Remove the 8 screws (T20) on the lter cable cover.
7. Loosen the left cable connector using a hex 5 key
8. Remove the entire
Reinstall in the reverse order.
cables screws using a hex 8
lter
assembly.
lter
1EMC shield
2 Power card mounting plate
3Inrush card
Illustration 7.9 Inrush Card
1RFIlter
2Screws
3EMC shield
Illustration 7.10 RFI Filter
62 02/2017 All rights reserved. BAS-SVM04B-EN
Page 64
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.4.5 Relay Transducer Card
1. Unplug cables on the relay transducer card.
2. Loosen the right cable connector using a hex 5 key.
3. Open the plastic clamp to remove the cables from the connector.
4. Remove the 2 screws (T20) from the holding bracket.
5. Remove the holding bracket.
6. Remove the 3 cable screws (T20).
7. Remove the 3 screws on relay card (T20).
8. Remove the relay card by pushing in the retaining clips on the standos. Use a screwdriver if necessary.
9. Remove the mounting plate.
Reinstall in the reverse order.
7.4.6 Rectier Modules
1. Loosen and remove the 2 cables (T20).
2. Remove the 6 screws (T20) from the shield.
3. Remove metal shield and plastic cover.
4. Remove the 2 screws (T20) from each of the modules.
rectier
5. Remove the 3 rectier modules.
7.4.7 IGBT
1. Remove the 4 screws (T20) from the cable
connector plate.
2. Remove the cable connector plate.
3. Loosen the coil cables ( T20).
4. Unplug the cables.
5. Remove the 2 screws from each of the 2
capacitors
6. Remove the capacitors.
7. Remove the 4 screws (T20) from the bus bar.
8. Remove the cables from the IGBTs.
9. Remove the 2 screws (T20) from each IGBT.
10. Remove the IGBTs.
7
1 Relay transducer card
2 Relay card mounting plate
Illustration 7.11 Relay or Transducer Card
CAUTION
The IGBTs and the heat sink have thermal paste on them. Be careful not to touch the paste directly as it is poisonous.
11. Remove the thermal paste from the IGBT.
12. Clean the heat sink.
Reinstall in the reverse order. Join the mounting snaps.
BAS-SVM04B-EN 02/2017 All rights reserved. 63
Page 65
7
H-Frame Size Disassembly a...
7.4.8 Heat Sink Fan Assembly
1. Remove the 4 screws (T20) from the fan cover
plate.
2. Press the fan cover plate outwards using a
screwdriver.
3. Remove the fans and the fan cover plate.
Reinstall in the reverse order.
1Cable mounting plate
2IGBT
3Bus bar
4Capacitor
Illustration 7.12 IGBT
1Fan cover
2 Fan assembly
Illustration 7.13 Heat Sink Fan Assembly
64 02/2017 All rights reserved. BAS-SVM04B-EN
Page 66
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.4.9 DC Coil
1. Remove the 4 screws (T20) from the DC coil cover plate.
2. Remove the 4 screws (T20) from the heat sink.
3. Remove the heat sink.
4. Remove 4 screws (T20) from each of the 2 DC Coils.
5. Remove the coils.
Reinstall in the reverse order.
7.4.10 Capacitor Bank
1. Remove the foil.
2. Remove the 6 screws on the base plate.
3. Remove the base plate.
4. Remove the 4 screws (T20) from the capacitor mounting plate.
5. Remove the mounting plate.
6. Turn the capacitor bank upside-down.
7. Remove the hex nut with a hex 19 key.
8. Remove the capacitor.
Reinstall in the reverse order.
7
1 DC coil cover plate
2Heat sink
3DC coil
Illustration 7.14 DC Coil
1Foil
2 Base plate
3 Capacitor bank
Illustration 7.15 Capacitor Bank
BAS-SVM04B-EN 02/2017 All rights reserved. 65
Page 67
H-Frame Size Disassembly a...
7
7.5 H8 Frame Size Disassembly and Assembly Instructions
7.5.1 Control Card and Control Card
Mounting Plate
1. Remove the LCP by pressing the barbs on the side.
2. Remove the foil.
3. Remove the 3 screws (T10).
4. Gently, lift o the control card.
5. Press the barb on the LCP ribbon cable and pull it out of the control card mounting plate.
6. Remove the mounting plate.
Reinstall in the reverse order.
7.5.2 Power Card
1. Remove 2 screws ( T20) from the EMC shield.
2. Remove cables from EMC shield.
3. Remove the EMC shield.
4. Remove the LCP ribbon cable from the power card.
5. Unplug all other cables from the power card.
6. Remove the 3 screws (T20) from the mounting plate.
7. Remove the power card by pushing in the 6 retaining clips.
NOTICE
Use a screwdriver if the retaining clips are hard to reach.
8. Slide the power card out and remove it.
Reinstall in the reverse order.
1LCP
2Cradle
3 Control card
4 Control card mounting plate
Illustration 7.16 Control Card and Control Card Mounting Plate
66 02/2017 All rights reserved. BAS-SVM04B-EN
1Power card
Illustration 7.17 Power Card
Page 68
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.5.3 Inrush Card
1. Remove the 4 screws (T20) from the power card mounting plate.
2. Remove the power card mounting plate.
3. Unplug all cables from the inrush card.
4. Remove the 6 screws (T20) from the inrush card.
5. Remove the inrush card.
Reinstall in the reverse order.
7.5.4 Rectier Modules
CAUTION
Wear protective gloves when cleaning up the thermal paste as it is poisonous.
1. Remove cables and foil.
2. Remove coil cords (T20).
3. Remove 6 screws (T25).
4. Remove screws in coil cables (T20).
5. Remove the 6 screws (T25) from the bar.
6. Remove the bar.
7. Loosen and remove the 3 cables using a hex 10 key.
8. Remove the plastic cover.
9. Remove the 2 screws (T20) on each of the rectier modules
10. Remove the thermal paste paper.
11. Clean up any excessive thermal paste.
Reinstall in the reverse order. Join the mounting snaps.
7
1EMC shield
2 Power card mounting plate
3Inrush card
Illustration 7.18 Inrush Card
BAS-SVM04B-EN 02/2017 All rights reserved. 67
Page 69
7
H-Frame Size Disassembly a...
7.5.5 RFI Filter
1. Remove the 3 screws (T20) from the small EMC shield.
2. Remove the EMC shield.
3. Loosen left cable connector using a hex 8 key.
4. Remove the 4 screws (T20) from the
5. Remove the entire lter assembly.
Reinstall in the reverse order.
lter.
1Foil
2Bus bar
3Plastic cover
4 Rectier modules
Illustration 7.19 Rectier Modules
1RFIlter
2Screws
3EMC shield
Illustration 7.20 RFI Filter
68 02/2017 All rights reserved. BAS-SVM04B-EN
Page 70
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.5.6 Relay Transducer Card
1. Remove the 4 screws (T20) on the plate.
2. Carefully remove cables before removing the plate.
3. Loosen the cables in the right cable connector using a hex 8 key.
4. Pull out the cables.
5. Remove the 3 screws (T30) on the relay card.
6. Remove the 2 10-pin ribbon cables.
7. Remove the 3 screws (T20) from the relay card.
8. Press the 3 retaining clips.
9. Remove the relay card.
10. Remove the relay card mounting plate.
Reinstall in the reverse order.
7.5.7 IGBT
CAUTION
Wear protective gloves when cleaning up the thermal paste as it is poisonous.
1. Remove the 2 screws from the cable retaining guide.
2. Remove the cable retaining guide.
3. Remove the 4 screws (T20) from the cable connector plate.
4. Remove the cable connector plate.
5. Remove the 2 cable screws (T20)
6. Remove the 2 screws (T30) in each of the 2 capacitors.
7. Remove the capacitors.
8. Remove the 2 screws (T30) from the bus bar.
9. Remove the 4 screws (T20) holding the capacitors.
10. Remove the bus bar.
11. Remove the gate cables from the IGBTs.
12. Remove the 4 screws from each IGBT.
13. Remove the thermal paper.
14. Remove the thermal paste from the IGBTs and the heat sink.
Reinstall in the reverse order. Join the mounting snaps.
7
1 Relay transducer card
2 Relay card mounting plate
Illustration 7.21 Relay Transducer Card
BAS-SVM04B-EN 02/2017 All rights reserved. 69
Page 71
7
H-Frame Size Disassembly a...
7.5.8 Heat Sink Fan Assembly
1. Remove the 4 screws (T20) from the fan cover plate.
2. Press the fan cover plate outwards using a screwdriver.
3. Remove the fans and the fan cover plate.
Reinstall in the reverse order.
1Cable mounting plate
2IGBT
3Bus bar
4Capacitor
Illustration 7.22 IGBT
1Fan cover
2 Fan assembly
Illustration 7.23 Heat Sink Fan Assembly
70 02/2017 All rights reserved. BAS-SVM04B-EN
Page 72
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.5.9 DC Coil
1. Remove the 4 screws (T20) from the DC coil cover plate.
2. Remove the 4 screws (T20) from the heat sink.
3. Remove the heat sink.
4. Remove 4 screws (T20) from each of the 2 DC Coils.
5. Remove the coils.
Reinstall in the reverse order.
7.5.10 Capacitor Bank
1. Remove the foil.
2. Remove the 4 screws from the base plate.
3. Remove the base plate.
4. Remove the 4 screws from the capacitor bank assembly.
5. Remove the assembly.
6. Turn the assembly upside-down.
7. Remove the 2 hex nuts with a hex 19 key.
8. Remove the 2 capacitors.
Reinstall in the reverse order.
7
1 DC coil cover plate
2Heat sink
3DC coil
Illustration 7.24 DC Coil
1Foil
2 Base plate
3 Capacitor bank
Illustration 7.25 Capacitor Bank
BAS-SVM04B-EN 02/2017 All rights reserved. 71
Page 73
H-Frame Size Disassembly a...
7
7.6 H10 Frame Size Disassembly and Assembly Instructions
7.6.1 Control Card and Control Card
Mounting Plate
1. Remove the LCP cradle. LCP cradle can be removed by hand.
2. Remove 3 screws (T10) securing the control card mounting plate to the control assembly support bracket.
3. Carefully lift out the control card.
Reinstall in the reverse order.
7.6.2 Power Card Cover
1. Press and loosen the 3 barbs at the bottom, and the 3 barbs at the top.
2. Remove the power card cover.
Reinstall in the reverse order. Join the mounting snaps.
1LCP
2 Control card mounting plate
3 Control card
Illustration 7.26 Control Card and Control Card Mounting Plate
1Power card cover
Illustration 7.27 Power Card Cover
72 02/2017 All rights reserved. BAS-SVM04B-EN
Page 74
H-Frame Size Disassembly a... TR150 and TR170 Service Manual
7
7.6.3 Power Card
1. Remove the 4 screws (T10) for the DC coil cables.
2. Remove the 5 screws (T10) for the heat sink.
3. Remove the 4 IGBT screws (T25).
4. Unplug fan cable connector.
CAUTION
The power card and the heat sink have thermal paste on them. Wear protective gloves as the paste is poisonous.
5. Lift out the power card.
6. Remove the capacitor bank gasket.
Reinstall in the reverse order.
7.6.4 Heat Sink and DC Coils
1. Remove the 7 mounting screws from top surface.
2. Press and loosen the 3 barbs at the bottom.
3. Unplug the DC coil cables.
4. Remove the heat sink.
5. Lift out the DC coils.
Reinstall in the reverse order.
7
1Power card
Illustration 7.28 Power Card
1Heat sink
Illustration 7.29 Heat Sink
1DC coil
Illustration 7.30 DC Coil
BAS-SVM04B-EN 02/2017 All rights reserved. 73
Page 75
7
H-Frame Size Disassembly a...
7.6.5 Heat Sink Fan Assembly
1. Remove 2 screws ( T10) on the DC coil mounting plate
2. Remove the plate.
3. Press and loosen the 2 barbs on the fan.
4. Remove the fan.
Reinstall in the reverse order.
1Heat sink fan
2Fan mounting plate
Illustration 7.31 Heat Sink Fan Assembly
74 02/2017 All rights reserved. BAS-SVM04B-EN
Page 76
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8 I-Frame Size Disassembly and Assembly Procedures
8.1 General Disassembly Procedure
This procedure explains how to remove the outer parts of the frequency converter that are common for all I-frame sizes. When this procedure is completed, the inside components are accessible.
1. Loosen and remove the 4 screws (T20) from the front cover.
2. Remove the front cover.
3. Remove the screw and sheet metal next to the EMC shield.
4. Loosen and remove the 4 screws (T20) from the cable entry.
5. Remove the cable entry.
8.2 I6 Frame Size Disassembly and Assembly Instructions
8.2.1 Control Card and Control Card
Mounting Plate
1. Remove LCP cradle.
2. Remove 3 screws ( T12) on the control board.
3. Remove the control board.
4. Remove 1 screw (T20) on the fan bracket.
5. Unplug the fan cable and remove the fan.
6. Remove 4 screws ( T20) on the control card mounting plate.
7. Unplug ribbon cable.
8. Remove control card mounting plate.
Reinstall in the reverse order.
8
1LCP and cradle
2 Control card and mounting plate
3 Support bracket
4Terminal plates
5EMC shield
Illustration 8.1 Control Card and Control Card Mounting Plate
BAS-SVM04B-EN 02/2017 All rights reserved. 75
Page 77
I-Frame Size Disassembly an...
8
8.2.2 Cable Mounting Plate
1. Remove the ribbon cable.
2. Remove 1 screw (T20) from shield metal.
3. Use a connection terminals.
4. Use a hex 4 key to loosen the screws in the cable connector.
5. Pull out the cables.
6. Slide the connector to the side and remove it.
7. Remove 2 screws (T20) from the mounting plate.
Reinstall in the reverse order.
screwdriver to release the retainers and
at
8.2.3 Heat Sink Fan Assembly
1. Unplug cable from power card.
2. Remove 2 screws ( T20) from the fan mounting plate.
3. Push the cable downwards. Use a screwdriver to press the gasket down through the entry.
4. Pull out fan assembly.
Reinstall in the reverse order.
1EMC shield
2Cable mounting plate
Illustration 8.2 Cable Mounting Plate
1Fan cover
2 Fan assembly
Illustration 8.3 Heat Sink Fan Assembly
76 02/2017 All rights reserved. BAS-SVM04B-EN
Page 78
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.2.4 SMPS Card
1. Remove the 3 black plastic covers.
2. Unplug and remove the fan.
3. Unplug all other cables.
4. Remove the 2 screws (T20) at MK101.
5. Remove the 3 screws (T20) at K103A, K104A, and K105A.
6. Remove the 4 screws (T20) and from the SMPS card.
7. Lift o the SMPS card.
Reinstall in the reverse order.
8.2.5 Bus Bar Unit
1. Remove the 2 screws from the snubber capacitor on the bus bar unit.
2. Remove the snubber capacitor.
3. Use a Hex 8 key to remove 2 screws from the bus bar unit.
4. Remove the 6 small screws (T10).
5. Remove the remaining 9 screws (T20).
6. Unplug cables.
7. Lift out the bus bar unit.
Reinstall in the reverse order.
8
1SMPS card
Illustration 8.4 SMPS Card
1Fan
2Bus bar unit
Illustration 8.5 Bus Bar Unit
BAS-SVM04B-EN 02/2017 All rights reserved. 77
Page 79
I-Frame Size Disassembly an...
8
8.2.6 Power Card
1. Remove 7 screws (T20)
2. Remove 5 screws ( T10) on the Power Card.
3. Lift out the power card.
Reinstall in the reverse order.
1Power card
Illustration 8.6 Power Card
8.2.7 DC Coil
1. Remove 4 screws ( T20) from the coil.
2. Lift the coil.
Reinstall in the reverse order.
1DC coil
Illustration 8.7 DC Coil
78 02/2017 All rights reserved. BAS-SVM04B-EN
Page 80
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.2.8 RFI Filter
1. Remove 2 screws (T20) from the lter.
2. Lift out the lter.
Reinstall in the reverse order.
1RFIlter
Illustration 8.8 RFI Filter
8.3 I7 Frame Size Disassembly and Assembly Instructions
8.3.1 Control Card and Control Card
Mounting Plate
1. Remove 2 screws (T20) from the 2 cover plates.
2. Remove the LCP cradle.
3. Remove 3 screws (T10) from the control card.
4. Remove the control card.
5. Remove 2 screws (T20) from the bracket next to the control card mounting plate.
6. Remove 4 screws ( T20) to remove the control card mounting plate.
7. Unplug the LCP ribbon cable.
8. Remove the control card mounting plate.
Reinstall in the reverse order.
8
1LCP and cradle
2 Control card and mounting plate
3EMC shield
4Terminal plates
5EMC shield
Illustration 8.9 Control Card Mounting Plate
BAS-SVM04B-EN 02/2017 All rights reserved. 79
Page 81
I-Frame Size Disassembly an...
8
8.3.2 Power Card
1. Unplug and remove the LCP ribbon cable.
2. Unplug all other cables from the power card.
3. Remove 3 screws ( T20) on the power card.
4. Remove the power card.
Reinstall in the reverse order.
8.3.3 Power Card Mounting Plate
1. Remove 4 screws (T20) from the power card mounting plate.
2. Remove the power card mounting plate with the fan attached.
Reinstall in the reverse order.
1 Power card mounting plate
1Power card
Illustration 8.10 Power Card
Illustration 8.11 Power Card Mounting Plate
80 02/2017 All rights reserved. BAS-SVM04B-EN
Page 82
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.3.4 Inrush Card
1. Unplug all cables.
2. Remove 6 screws (T20) from the inrush card.
3. Remove the inrush card.
Reinstall in the reverse order.
1Inrush card
Illustration 8.12 Inrush Card
8.3.5 Bus Bar
1. Unplug and remove the red/black cable.
2. Remove the black plastic cover.
3. Remove 8 screws (T20) from the support bracket.
4. Remove the bus bar assembly.
Reinstall in the reverse order.
8
1Bus bar
Illustration 8.13 Bus Bar
BAS-SVM04B-EN 02/2017 All rights reserved. 81
Page 83
I-Frame Size Disassembly an...
8
8.3.6 RFI Filter
1. Unplug the 3 lter cables from the thyristors using a hex 8 key.
2. Loosen the 3 cables from the cable connector using a hex 5 key.
3. Remove 3 screws (T20) from the support bracket.
4. Remove support bracket.
5. Remove 4 screws (T20) from the RFI lter.
6. Remove the entire assembly.
Reinstall in the reverse order.
8.3.7 Relay Transducer Card
1. Remove the 3 clamps on each side of the 2 cable connectors.
2. Remove the cable connector with no cables attached.
3. Remove 3 screws (T20) from the support bracket.
4. Loosen the 3 cables from the relay transducer card.
5. Remove the cable connector with cables and retaining guide attached.
6. Unplug all other cables from the relay transducer card.
7. Remove the 3 screws (T20)
8. Remove the relay transducer card.
Reinstall in the reverse order.
1RFIlter
Illustration 8.14 RFI Filter
1 Relay transducer card
Illustration 8.15 Relay Transducer Card
82 02/2017 All rights reserved. BAS-SVM04B-EN
Page 84
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.3.8 Fan
1. Remove 2 screws ( T20) on the fan bracket.
2. Remove 2 screws (T20) from the fan.
3. Remove the fan.
Reinstall in the reverse order.
1Fan
8.3.9 Terminal Plate
1. Remove the black plastic cover.
2. Remove 4 screws (T20) on the cover plate.
3. Remove the terminal plate.
Reinstall in the reverse order.
8
1Terminal plate
Illustration 8.16 Fan
Illustration 8.17 Terminal Plate
BAS-SVM04B-EN 02/2017 All rights reserved. 83
Page 85
I-Frame Size Disassembly an...
8
8.3.10 DC Bus Bar Assembly
1. Remove 2 screws (T20) from the 2 snubbers.
2. Remove the snubbers.
3. Loosen and remove cables from bus bar assembly and DC coil.
4. Remove 6 screws (T20) from the bus bar assembly.
5. Remove the bus bar assembly.
Reinstall in the reverse order.
8.3.11 Heat Sink Fan Assembly
1. Remove gate cables from IGBTs.
2. Remove 2 screws (T20) from the heat sink fan assembly.
3. Push the fan cable down through the gasket.
4. Carefully press the gasket down with a screwdriver.
5. Remove the fan assembly.
Reinstall in the reverse order.
1 DC bus bar assembly
Illustration 8.18 DC Bus Bar Assembly
1 Fan cover plate
2 Fan assembly
Illustration 8.19 Heat Sink Fan Assembly
84 02/2017 All rights reserved. BAS-SVM04B-EN
Page 86
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.3.12 Capacitor Bank
1. Remove 4 screws (T20) from each of the capacitors.
2. Remove the capacitors.
Reinstall in the reverse order.
1Capacitors
8.3.13 DC Coil
1. Remove 5 screws ( T20) on the potted coil.
2. Remove the DC coil.
Reinstall in the reverse order.
8
1Bus bar
2DC coil
Illustration 8.20 Capacitors
Illustration 8.21 DC Coil
BAS-SVM04B-EN 02/2017 All rights reserved. 85
Page 87
I-Frame Size Disassembly an...
8
8.3.14 IGBT
1. Remove 2 screws (T20) from each of the 3 IGBTs.
CAUTION
The IGBTs and the heat sink have thermal paste on them. Wear protective gloves as the paste is poisonous.
2. Remove all IGBTs.
Reinstall in the reverse order.
8.3.15 Thyristor
1. Remove 2 screws ( T20) from each of the 3 thyristors.
CAUTION
The thyristors and the heat sink have thermal paste on them. Wear protective gloves as the paste is poisonous.
2. Remove the thyristors.
Reinstall in the reverse order.
1IGBT
Illustration 8.22 IGBT
1Thyristor
Illustration 8.23 Thyristor
8.4 I8 Frame Size Disassembly and Assembly Procedure
8.4.1 Control Card and Control Card
Mounting Plate
1. Remove 2 screws (T20) from the 2 cover plates.
2. Remove the LCP cradle.
3. Remove 3 screws (T10) from the control card.
4. Remove the control card.
5. Remove 2 screws (T20) from the bracket next to the control card mounting plate.
6. Remove 4 screws ( T20) to remove the control card mounting plate.
7. Unplug the LCP ribbon cable.
8. Remove the control card mounting plate.
Reinstall in the reverse order.
86 02/2017 All rights reserved. BAS-SVM04B-EN
Page 88
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.4.2 Power Card
1. Unplug and remove the LCP ribbon cable.
2. Unplug all other cables from the power card.
3. Remove 3 screws (T20) on the power card.
4. Remove the power card.
Reinstall in the reverse order.
1 LCP and cradle
2 Control card and mounting plate
3EMC shield
4 Terminal plates
5EMC shield
Illustration 8.24 Control Card Mounting Plate
8
1Power card
Illustration 8.25 Power Card
BAS-SVM04B-EN 02/2017 All rights reserved. 87
Page 89
I-Frame Size Disassembly an...
8
8.4.3 Power Card Mounting Plate
1. Remove 4 screws (T20) from the power card mounting plate.
2. Remove the power card mounting plate with the fan attached.
Reinstall in the reverse order.
1Power card mounting plate
8.4.4 Inrush Card
1. Unplug all cables.
2. Remove 6 screws ( T20) from the inrush card.
3. Remove the inrush card.
Reinstall in the reverse order.
1Inrush card
Illustration 8.26 Power Card Mounting Plate
Illustration 8.27 Inrush Card
88 02/2017 All rights reserved. BAS-SVM04B-EN
Page 90
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.4.5 Bus Bar
1. Unplug and remove the red/black cable.
2. Remove the black plastic cover.
3. Remove 6 screws (T20) and 2 screws (T30) from the support bracket.
4. Remove the bus bar assembly.
Reinstall in the reverse order.
8.4.6 RFI Filter
1. Unplug the 3 lter cables from the thyristors using a hex 8 key.
2. Loosen the 3 cables from the cable connector using a hex 5 key.
3. Remove 3 screws (T20) from the support bracket.
4. Remove support bracket.
5. Remove 4 screws ( T20) from the RFI lter.
6. Remove the entire assembly.
Reinstall in the reverse order.
8
1Bus bar
Illustration 8.28 Bus Bar
1RFIlter
Tab le 8.1
Illustration 8.29 RFI Filter
BAS-SVM04B-EN 02/2017 All rights reserved. 89
Page 91
I-Frame Size Disassembly an...
8
8.4.7 Relay Transducer Card
1. Remove 2 screws (T20) from each of the 2 cable connectors.
2. Remove the cable connector.
3. Remove 3 screws (T20) from the support bracket.
4. Loosen the 3 cables ( T30) from the relay transducer card.
5. Unplug all other cables from the relay transducer card.
6. Remove the 3 screws (T20).
7. Remove the relay transducer card.
Reinstall in the reverse order.
8.4.8 Terminal Plate
1. Remove 4 screws (T20) on the cover plate.
2. Remove the complete terminal plate including cable connector.
Reinstall in the reverse order.
1Terminal plate
1 Relay transducer card
Illustration 8.30 Relay Transducer Card
Illustration 8.31 Terminal Plate
90 02/2017 All rights reserved. BAS-SVM04B-EN
Page 92
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.4.9 DC Bus Bar Assembly
1. Remove 2 screws (T30) from each of the 2 snubbers.
2. Remove the snubbers.
3. Loosen and remove the 2 cables from bus bar assembly and DC coil.
4. Remove 2 screws (T30).
5. Remove 8 screws (T20) on top of the bus bar assembly.
6. Remove the bus bar assembly.
Reinstall in the reverse order.
8.4.10 Heat Sink Fan Assembly
1. Remove 4 screws (T20) from the heat sink fan assembly.
2. Push the cables down through the gaskets.
3. Carefully press the gaskets down with a screwdriver.
4. Remove the fan assembly.
Reinstall in the reverse order.
8
1 Bus bar assembly
Illustration 8.32 DC Bus Bar Assembly
1Fan cover plate
2Heat sink fan
Illustration 8.33 Heat Sink Fan Assembly
BAS-SVM04B-EN 02/2017 All rights reserved. 91
Page 93
I-Frame Size Disassembly an...
8
8.4.11 Capacitor Bank
1. Remove 4 screws (T20) from each of the capacitors.
2. Remove the capacitors.
Reinstall in the reverse order.
Illustration 8.34 Capacitors
8.4.12 DC Coil
1. Remove 5 screws ( T20) on the potted coil.
2. Remove the DC coil.
Reinstall in the reverse order.
1Bus bar
2DC coil
1Capacitors
Illustration 8.35 DC Coil
92 02/2017 All rights reserved. BAS-SVM04B-EN
Page 94
I-Frame Size Disassembly an... TR150 and TR170 Service Manual
8
8.4.13 IGBT
1. Remove 4 screws (T20) from each of the 3 IGBTs.
CAUTION
The UGBTs and the heat sink have thermal paste on them. Wear protective gloves as the paste is poisonous.
2. Remove all IGBTs.
Reinstall in the reverse order.
8.4.14 Thyristor
1. Remove 2 screws ( T20) from each of the 3 thyristors.
CAUTION
The thyristors and the heat sink have thermal paste on them. Wear protective gloves as the paste is poisonous.
2. Remove the thyristors.
Reinstall in the reverse order.
8
1IGBT
Illustration 8.36 IGBT
1Thyristor
Illustration 8.37 Thyristor
BAS-SVM04B-EN 02/2017 All rights reserved. 93
Page 95
Block Diagrams
9Block Diagrams
9.1 Block Diagrams, Frame Sizes H and 9
9.1.1 H6 Frame Size
9
Illustration 9.1 H6 Frame Size
94 02/2017 All rights reserved. BAS-SVM04B-EN
Page 96
Block Diagrams TR150 and TR170 Service Manual
9
9.1.2 I6 Frame Size
Illustration 9.2 I6 Frame Size
9
BAS-SVM04B-EN 02/2017 All rights reserved. 95
Page 97
Block Diagrams
9.1.3 H7, H8, I7, I8 Frame Size
9
Illustration 9.3 H7, H8, I7, I8 Frame Size
96 02/2017 All rights reserved. BAS-SVM04B-EN
Page 98
Block Diagrams TR150 and TR170 Service Manual
9
9.1.4 H9 Frame Size
Illustration 9.4 H9 Frame Size
9
BAS-SVM04B-EN 02/2017 All rights reserved. 97
Page 99
Block Diagrams
9.1.5 H10 Frame Size
9
Illustration 9.5 H10 Frame Size
98 02/2017 All rights reserved. BAS-SVM04B-EN
Page 100
Index TR150 and TR170 Service Manual
Index
A
AMA...................................................................................... 31, 33, 39, 40
AMA
Warning............................................................................................... 37
Analog
Signal.................................................................................................... 34
Analog output....................................................................................... 19
Analog signal........................................................................... 19, 20, 55
Analog signals........................................................................................ 18
C
Cable cross-section.............................................................................. 22
Capacitor..................... 12, 13, 15, 16, 24, 25, 38, 40, 48, 49, 57, 63
Capacitor bank............................................................................... 24, 49
Check list.................................................................................................. 28
Circuitry............................................ 23, 24, 27, 32, 38, 40, 47, 54, 56
Conguration......................................................................................... 40
Control
card................................................................................................ 25, 40
logic...................................................................................................... 40
terminal........................................................................................ 30, 41
wiring................................................................................................... 30
Control cable
Long control cable........................................................................... 22
Serial communication control cable......................................... 22
Control card....................................................................... 20, 23, 53, 55
Control card
Control card....................................................................................... 30
Control card voltage....................................................................... 53
Live zero error.................................................................................... 34
Control terminal.......................................... 18, 19, 20, 21, 23, 34, 55
Control wiring................................................................... 18, 19, 31, 55
Current
rating.................................................................................................... 34
waveform..................................................................................... 24, 53
Output current.................................................................................. 34
Current waveform................................................................................ 25
D
DC bus capacitor................................................................................... 52
DC capacitor........................................................................................... 56
DC coil.................................................................... 14, 15, 16, 24, 40, 49
DC-link capacitor.................................................................................. 24
DC-link inductor.................................................................................... 24
Deceleration rate.................................................................................. 39
Diagnostic............................................................................................... 27
Digital input..................................................................................... 18, 20
Digital output........................................................................... 19, 20, 23
Diode............................................................... 24, 39, 47, 48, 49, 53, 54
Display
Flashing (line 2)................................................................................. 30
Intermittent........................................................................................ 30
No display........................................................................................... 30
Wrong................................................................................................... 30
Display line.............................................................................................. 19
E
Electrical installation........................................................................... 10
EMC......................................................................... 28, 36, 41, 62, 66, 68
EMI
Propagation....................................................................................... 43
Source.................................................................................................. 42
F
Fau lt
symptom...................................................................................... 27, 30
Fieldbus............................................................................................. 18, 30
Fire mode................................................................................................. 38
Form A...................................................................................................... 20
Form C relay..................................................................................... 19, 20
G
Gate signal................................................................................ 25, 41, 53
Gating circuit.......................................................................................... 25
Ground cabling..................................................................................... 22
H
Heat sink........................................................ 11, 12, 13, 76, 84, 91, 93
Heatsink.................................................. 25, 58, 63, 65, 69, 71, 73, 74
I
IGBT...................................... 12, 13, 16, 24, 25, 31, 39, 41, 42, 48, 52
Impedance......................................................................... 24, 41, 43, 44
Input
Analog.................................................................................................. 34
Digital................................................................................................... 35
Input cabling.......................................................................................... 52
Input signal........................................................................ 18, 20, 37, 41
Input signals........................................................................................... 18
Intermediate section........................................................................... 24
L
LCP....................................... 15, 16, 18, 19, 23, 30, 32, 57, 61, 66, 75
LED................................................................................... 6, 30, 32, 34, 52
M
Main assemblies...................................................................................... 6
BAS-SVM04B-EN 02/2017 All rights reserved. 99
Loading...