5.1 Torque Limit, Current Limit, and Unstable Motor Operation
5.1.1 Overvoltage Trips39
27
28
30
30
30
32
32
38
39
39
5.1.2 Mains Phase Loss Trips40
5.1.3 Control Logic Problems40
5.1.4 Programming Problems40
5.1.5 Motor/Load Problems41
5.2 Internal Frequency Converter Problems
5.2.1 Overtemperature Faults41
5.2.2 Current Sensor Faults41
5.2.3 Signal and Power Wiring Considerations for Electromagnetic Compatibility41
5.2.4 Eects of EMI42
5.2.5 Sources of EMI42
5.2.6 EMI Propagation43
5.2.7 Preventive Measures44
6 Test Procedures
6.1 Non-repairable Units
6.2 Introduction
6.3 Static Test Procedures
6.3.2 Rectier Circuit Test48
41
45
45
47
47
6.3.3 Inverter Section Tests48
6.3.4 Intermediate Section Tests49
6.3.5 Location of UDC Terminals49
6.4 Dynamic Test Procedures
6.4.1 No Display Test (Display is Optional)52
202/2017 All rights reserved.BAS-SVM04B-EN
52
ContentsTR150 and TR170 Service Manual
6.4.2 Input Voltage Test
6.4.3 Basic Control Card Voltage Test53
6.4.4 Input Imbalance of Supply Voltage Test53
6.4.5 Input Waveform Test
6.4.6 Output Imbalance of Motor Supply Voltage Test54
6.4.7 Input Terminal Signal Tests55
6.5 Initial Start-up Or After Repair Drive Tests
7 H-Frame Size Disassembly and Assembly Instructions
7.1 Electrostatic Discharge (ESD)
7.2 General Disassembly Procedure
7.3 H6 Frame Size Disassembly and Assembly Instructions
7.3.1 Control Card and Control Card Mounting Plate57
7.3.2 Heat sink Fan Assembly58
7.3.3 DC Coil59
7.3.4 DC Link Card59
7.3.5 RFI Filter60
7.3.6 Power Card60
52
53
56
57
57
57
57
7.4 H7 Frame Size Disassembly and Assembly Instructions
7.4.1 Control Card and Control Card Mounting Plate61
7.4.2 Power Card61
7.4.3 Inrush Card62
7.4.4 RFI Filter62
7.4.5 Relay Transducer Card63
7.4.6 Rectier Modules63
7.4.7 IGBT63
7.4.8 Heat Sink Fan Assembly64
7.4.9 DC Coil65
7.4.10 Capacitor Bank65
7.5 H8 Frame Size Disassembly and Assembly Instructions
7.5.1 Control Card and Control Card Mounting Plate66
7.5.2 Power Card66
7.5.3 Inrush Card67
7.5.4 Rectier Modules67
7.5.5 RFI Filter68
61
66
7.5.6 Relay Transducer Card69
7.5.7 IGBT69
7.5.8 Heat Sink Fan Assembly70
7.5.9 DC Coil71
7.5.10 Capacitor Bank71
7.6 H10 Frame Size Disassembly and Assembly Instructions
BAS-SVM04B-EN02/2017 All rights reserved.3
72
Contents
7.6.1 Control Card and Control Card Mounting Plate
7.6.2 Power Card Cover72
7.6.3 Power Card73
7.6.4 Heat Sink and DC Coils
7.6.5 Heat Sink Fan Assembly74
8 I-Frame Size Disassembly and Assembly Procedures
8.1 General Disassembly Procedure
8.2 I6 Frame Size Disassembly and Assembly Instructions
8.2.1 Control Card and Control Card Mounting Plate75
8.2.2 Cable Mounting Plate76
8.2.3 Heat Sink Fan Assembly76
8.2.4 SMPS Card77
8.2.5 Bus Bar Unit77
8.2.6 Power Card78
8.2.7 DC Coil78
8.2.8 RFI Filter79
8.3 I7 Frame Size Disassembly and Assembly Instructions
72
73
75
75
75
79
8.3.1 Control Card and Control Card Mounting Plate79
8.3.2 Power Card80
8.3.3 Power Card Mounting Plate80
8.3.4 Inrush Card81
8.3.5 Bus Bar81
8.3.6 RFI Filter82
8.3.7 Relay Transducer Card82
8.3.8 Fan83
8.3.9 Terminal Plate83
8.3.10 DC Bus Bar Assembly84
8.3.11 Heat Sink Fan Assembly84
8.3.12 Capacitor Bank85
8.3.13 DC Coil85
8.3.14 IGBT86
8.3.15 Thyristor86
8.4 I8 Frame Size Disassembly and Assembly Procedure
8.4.1 Control Card and Control Card Mounting Plate86
86
8.4.2 Power Card87
8.4.3 Power Card Mounting Plate88
8.4.4 Inrush Card88
8.4.5 Bus Bar89
8.4.6 RFI Filter89
8.4.7 Relay Transducer Card90
402/2017 All rights reserved.BAS-SVM04B-EN
ContentsTR150 and TR170 Service Manual
8.4.8 Terminal Plate
8.4.9 DC Bus Bar Assembly91
8.4.10 Heat Sink Fan Assembly91
8.4.11 Capacitor Bank
8.4.12 DC Coil92
8.4.13 IGBT93
8.4.14 Thyristor
9 Block Diagrams
9.1 Block Diagrams, Frame Sizes H and 9
9.1.1 H6 Frame Size94
9.1.2 I6 Frame Size95
9.1.3 H7, H8, I7, I8 Frame Size96
9.1.4 H9 Frame Size97
9.1.5 H10 Frame Size98
Index
90
92
93
94
94
99
BAS-SVM04B-EN02/2017 All rights reserved.5
Introduction
1
1Introduction
1.1 Purpose
This manual provides the technical information and
instructions required, for a qualied technician approved
by Trane to identify faults and perform repairs and
maintenance on the frequency converter:
Data for the dierent enclosure sizes
•
Description of user interfaces and internal
•
processing
Troubleshooting and test instructions
•
Assembly and disassembly instructions
•
The manual applies to frequency converter models and
voltage ranges described in Table 1.2 to Table 1 . 4 .
1.2 Product Overview
TR150 and TR170 frequency converters are designed for
the Heating, Ventilation, and Air-Conditioning (HVAC)
markets. They operate in variable torque mode, and
include features suited for fan and pump applications
within the HVAC market.
1.3 Safety
nected (linkage of DC intermediate circuit). There
may be high voltage on the DC-link even when
the LEDs are turned
potentially live parts of the frequency converter,
wait at least as stated in Table 1 . 1.
2.Before conducting repair or inspection,
disconnect mains.
3.
4.During operation and while programming
5.When operating on a PM motor, disconnect
Volt age [V]Power range [kW ]
on the LCP does not disconnect mains.
[O]
parameters, the motor may start without warning.
Press [Stop] when changing data.
motor cable.
3x2000.25–3.74
3x2005.5–1115
3x4000.37–7.54
3x40011–9015
3x6002.2–7.54
3x60011–9015
Before touching any
o.
Minimum waiting
time (minutes)
CAUTION
Frequency converters contain dangerous voltages when
connected to mains. Only qualied personnel should
carry out the service. See also chapter 2.1 Introduction.
CAUTION
For dynamic test procedures, main input power is
required and all devices and power supplies connected
to mains are energized at rated voltage. Take extreme
caution when conducting tests in a powered frequency
converter. Contact with powered components could
result in electrical shock and personal injury.
1.DO NOT touch electrical parts of the frequency
converter when connected to mains. Also make
sure that other voltage inputs have been discon-
Tab le 1.1 Dis c har ge Tim e
1.4 Electrostatic Discharge (ESD)
CAUTION
ELECTROSTATIC DISCHARGE
When performing service, use proper electrostatic
discharge (ESD) procedures to prevent damage to
sensitive components. Many electronic components
within the frequency converter are sensitive to static
electricity. The voltage of static electricity can reduce
lifetime,
sensitive electronic components.
•
•
performance, or completely destroy
aect
Do not touch components on the circuit boards.
Hold circuit boards by the edges or corners
only.
602/2017 All rights reserved.BAS-SVM04B-EN
IntroductionTR150 and TR170 Service Manual
1.4.1 Frame Size Denitions
ModelHP @200–240 V ACkW @200–240 V ACFrame SizeIP RatingRepairable Yes/No
PK250.330.25H1IP20No
PK370.50.37H1IP20No
PK751.00.75H1IP20No
P1K52.01.5TR150: H1
TR170: H2
P2K23.02.2H2IP20No
P3K75.03.7H3IP20No
P5K57.55.5H4IP20No
P7K510.07.5H4IP20No
P11K15.011.0H5IP20No
P15K20.015.0H6IP20Yes
P18K25.018.5H6IP20Yes
P22K30.022.0H7IP20Yes
P30K40.030.0H7IP20Yes
P37K50.037.0H8IP20Yes
P45K60.045.0H8IP20Yes
Table 1.2 TR150 and TR170 Frequency Converters 200–240 V AC
IP20No
11
BAS-SVM04B-EN02/2017 All rights reserved.7
Introduction
1
ModelHP @380–480 V ACkW @380–480 V ACFrame SizeIP RatingRepairable Yes/No
PK370.50.37H1IP20No
PK751.00.75H1IP20No
P1K52.01.5TR150:H1
TR170:H2
P2K23.02.2H2IP20No
P3K04.03.0H2IP20No
P4K05.04.0H2IP20No
P5K57.55.5H3IP20No
P7K510.07.5H3IP20No
P11K15.011.0H4IP20No
P15K20.015.0H4IP20No
P18K25.018.0H5IP20No
P22K30.022.0H5IP20No
P30K40.030.0H6IP20Yes
P37K50.037.0H6IP20Yes
P45K60.045.0H6IP20Yes
P55K70.055.0H7IP20Yes
P75K100.075.0H7IP20Yes
P90K125.090.0H8IP20Yes
PK751.00.75I2IP54No
P1K52.01.5I2IP54No
P2K23.02.2I2IP54No
P3K34.03.3I2IP54No
P4K05.04.0I2IP54No
P5K57.55.5I3IP54No
P7K510.07.5I3IP54No
P11K15.011.0I4IP54No
P15K20.015.0I4IP54No
P22K25.018.0I4IP54No
P11K15.011.0I5IP54No
P15K20.015.0I5IP54No
P22K25.018.0I5IP54No
P22K30.022.0I6IP54Yes
P30K40.030.0I6IP54Yes
P37K50.037.0I6IP54Yes
P45K60.045.0I7IP54Yes
P55K70.055.0I7IP54Yes
P75K100.075.0I8IP54Yes
P90K125.090.0I8IP54Yes
IP20No
Table 1.3 TR150 and TR170 Frequency Converters 380–480 V AC
802/2017 All rights reserved.BAS-SVM04B-EN
IntroductionTR150 and TR170 Service Manual
ModelHP @525–600 V ACkW @525–600 V ACFrame SizeIP RatingRepairable Yes/No
P2K23.02.2H9IP20No
P3K04.03.0H9IP20No
P5K57.55.5H9IP20No
P7K510.07.5H9IP20No
P11K15.011.0H10IP20Yes
P15K20.015.0H10IP20Yes
P22K30.022.0H6IP20Yes
P30K40.030.0H6IP20Yes
P45K60.045.0H7IP20Yes
P55K70.055.0H7IP20Yes
P75K100.075.0H8IP20Yes
P90K125.090.0H8IP20Yes
Table 1.4 Repairable Yes/No Frequency Converters 525–600 V AC
1.5 Tools Required
Quick Guide for TR150 and TR170.
ESD Protection KitWrist strap and Mat
Metric socket set7–19 mm
Torque wrench0.5 N · m to 19 N · m
Socket extensions100–150 mm (4 in and 6 in)
Torx driver setT10-T50
Needle nose pliers
Magnetic sockets
Ratchet
ScrewdriversStandard and Philips
11
Table 1.5 Required Tools
Additional Tools Recommended for Testing
Digital voltmeter/ohmmeter (must be rated for
•
1000 V DC for 600 V units)
Analog voltmeter
•
Oscilloscope
•
Clamp-on style ammeter
•
BAS-SVM04B-EN02/2017 All rights reserved.9
Introduction
1
1.6 Electrical Installation in General
1.6.1 Electrical Installation in General
All cabling must comply with national and local regulations on cable cross-sections and ambient temperature. Copper
conductors are required. 75 °C (167 °F) is recommended. For TR170 drives operating in ambients over 50 °C (122 °F), copper
conductors rated 80 °C (176 °F) or higher are recommended.
8RFI lter18Relay/transducer card with mounting plate
9Power Card 19Cable entry
10Power card mounting plate
Illustration 1.6 Exploded View - I8 Frame Size
1602/2017 All rights reserved.BAS-SVM04B-EN
IntroductionTR150 and TR170 Service Manual
1.9 Ratings
1.9.1 Short Circuit and Overcurrent Trips
The frequency converter is protected against short circuits with current measurement in each of the 3 motor phases or in
the DC link. A short circuit between 2 output phases causes an overcurrent in the inverter. The inverter turns o the IGBTs
individually when the short-circuit current exceeds the permitted value (Alarm 16 Trip Lock).
This section describes the optional display interfaces
available for the frequency converter, the inputs and
outputs, and the control terminal functions.
The following optional interfaces are available:
Numerical Local Control Panel (LCP 21).
•
Graphical Local Control Panel (GLCP or LCP 102).
•
Use the selected interface to adapt parameter settings or
read status.
Commands given to the frequency converter are indicated
on the selected interface display. Fault logs are maintained
within the frequency converter, for fault history. The
frequency converter issues warnings and alarms for fault
conditions arising within or external to the frequency
converter itself. Usually, the fault condition is found outside
of the frequency converter.
2.2 Status Messages
Status messages appear in the bottom of the display. The
left part of the status line indicates the active operation
model of the frequency converter.
The center part of the status line indicates the references
site. The last part of the status line gives the operation
status, for example:
Running.
•
Stop.
•
Standby.
•
Other status messages may appear and are related to the
software version and frequency converter type.
2.3 Frequency Converter Inputs and
Outputs
The frequency converter operates by receiving control
input signals. The frequency converter can also output
status data or control auxiliary devices.
Control input is sent to the frequency converter in 3 ways:
Via the optional LCP connected by cable to the
•
frequency converter, operating in [Hand On]
mode. These inputs include start, stop, reset, and
speed reference.
Via serial communication from a eldbus,
•
connected to the frequency converter through
the RS485 serial port, or through a communication option card. The serial communication
protocol:
-Supplies commands and references to
the frequency converter.
-Programs the frequency converter.
-Reads status data from the frequency
converter.
Via signal wiring connected to the frequency
•
converter control terminals. Improperly connected
control wiring can result in the frequency
converter failing to start or to respond to a
remote input.
2.3.1 Input Signals
The frequency converter can receive 2 types of remote
input signals: digital or analog. Digital inputs are wired to
terminals 18, 19, 20 (common), 27, 29. Analog or digital
inputs are wired to terminals 53 or 54 and 55 (common). A
switch placed under the LCP sets the terminal functions.
Some options include additional terminals.
Analog signals can be either voltage (0 V to +10 V DC) or
current (0–20 mA or 4–20 mA). Analog signals can be
varied like dialing a rheostat up and down. The frequency
converter can be programmed to increase or decrease
output in relation to the amount of current or voltage. For
example, a sensor or external controller may supply a
variable current or voltage. The frequency converter
output, in turn, regulates the speed of the motor
connected to the frequency converter in response to the
analog signal.
Digital signals are a simple binary 0 or 1 acting as a switch.
A 0-24 V DC signal controls the digital signals. A voltage
signal lower than 5 V DC is a logic 0. A voltage higher than
10 V DC is a logic 1. 0 is open, 1 is close. Digital inputs to
the frequency converter are switched commands such as
start, stop, reverse, coast, reset. (Do not confuse these
digital inputs with serial communication formats where
digital bytes are grouped into communication words and
protocols).
The RS485 serial communication connector is wired to
terminals (+) 68 and (-) 69. Terminal 61 is a common
terminal. It is used for terminating shields only when the
control cable is run between frequency converters, and not
between frequency converters and other devices.
Parameters for
NPN and PNP.
These parameters cannot be changed while the motor is
running.
conguring
the input and output using
1802/2017 All rights reserved.BAS-SVM04B-EN
Frequency Converter ControlTR150 and TR170 Service Manual
2
2.3.2 Output Signals
The frequency converter also produces output signals that
are carried either through the RS485 serial bus or terminal
42. Output terminal 42 operates in the same manner as
the inputs. The terminal can be programmed for either a
variable analog signal in mA or a digital signal (0 or 1) in
24 V DC. In addition, a pulse reference can be provided on
terminals 27 and 29. Output analog signals generally
indicate the frequency, current, torque, and so on, to an
external controller or system. Digital outputs can be
control signals used to open or close a damper, or send a
start or stop command to auxiliary equipment.
Additional terminals are Form C relay outputs on terminals
01, 02, and 03, and terminals 04, 05, and 06.
Terminals 12 and 13 provide 24 V DC low voltage power,
often used to supply power to the digital input terminals
(18–33). Those terminals must be supplied with power
from either terminal 12 or 13, or from a customer supplied
external 24 V DC power source. Improperly connected
control wiring is a common service issue for a motor not
operating or the frequency converter not responding to a
remote input.
Number of digital outputs2
Ter mina l nu m ber
Voltage level at digital output17 V
Maximum output current at digital
output
Maximum load at digital output
42, 45
20 mA
Ω
1 k
1)
See the Quick Guide for detailed information on accessing
and showing parameters, and for descriptions and
procedures for service information available in parametergroup 6-** Analog In/Out.
2.5 Control Terminals
For proper function of the frequency converter functioning,
the input control terminals must be:
Wired properly.
•
Powered.
•
Programmed correctly for the intended function.
•
Ensure that the input terminal is wired correctly:
1.Conrm that the control and power sources are
wired to the terminal.
2.Check the signal in either of 2 ways:
Press [Display Mode], then select Digital
•
Input. The LCP shows the digital inputs
which are correctly wired.
Use a voltmeter to check for voltage at
•
the control terminal.
Conrm that each control terminal is programmed for the
correct function. Each terminal has specic functions and a
numbered parameter associated with it. The setting
selected in the parameter enables the function of the
terminal.
See the Quick Guide for details on changing parameters
and the functions available for each control terminal.
2
Table 2.1 Digital Output
1) Terminals 42 and 45 can also be programmed as analog output.
2.4 Service Functions
Service information for the frequency converter can be
shown in display lines 1 and 2. 24 dierent items can be
accessed. Included in the data are
Counters that tabulate hours run, and so on.
•
Fault logs that store frequency converter status
•
values present at the ten most recent events that
stopped the frequency converter
Frequency converter nameplate data
•
Parameter 14-28 Production Settings and
parameter 14-29 Service Code, are the relevant service
parameters.
Parameter settings are shown by pressing [Main Menu].
Press [
], [▼], [►] and [◄] to scroll through parameters.
▲
BAS-SVM04B-EN02/2017 All rights reserved.19
2
Frequency Converter Control
2.6 Control Terminal Functions
Tab l e 2.2 describes the functions of the control terminals.
Many of these terminals have multiple functions
determined by parameter settings. See Illustration 2.1.
Ter m in al
number
01, 02, 03Form C relay output on control card. Maximum 240
04, 05Form A relay output on control card. 30 V AC, 42.5
12, 13Voltage supply to digital inputs and external
16–33Programmable digital inputs for controlling the
20Common for digital inputs.
39Common for analog and digital outputs.
42, 45Analog and digital outputs for indicating values
5010 V DC, 17 mA maximum analog supply voltage
53, 54
55Common for analog inputs. This common is
60Programmable 0–20 mA or 4–20 mA, analog
61RS485 common.
68, 69RS485 interface and serial communication.
Func tion
V AC, 2 A. Minimum 24 V DC, 10 mA, or 24 V AC,
100 mA. Can be used for indicating status and
warnings. Physically located on power card.
V DC. Can be used for indicating status and
warnings.
transducers. For the 24 V DC to be used for digital
inputs, switch 4 on the control card must be closed
(ON position). The maximum output current is 200
mA.
Ω
frequency converter. R=2 k
(open). Greater than 10 V=logic 1 (closed).
such as frequency, reference, current, and torque.
The analog signal is 0–20 mA, or 4–20 mA at a
Ω
maximum of 500
a minimum of 600
for potentiometer or thermistor.
0–10 V DC voltage input, R = 10 k
reference or feedback signals. A thermistor can be
connected here.
isolated from the common of all other power
supplies. If, for example, the frequency converter’s
24 V DC power supply is used to power an
external transducer, which provides an analog
input signal, terminal 55 must be wired to terminal
39.
current input, Resistance=approx. 200
reference or feedback signals.
. The digital signal is 24 V DC at
Ω
. Less than 5 V=logic 0
.
Ω
Used for
Ω
. Used for
Tab le 2.2 Term ina l Functi ons
2002/2017 All rights reserved.BAS-SVM04B-EN
Frequency Converter ControlTR150 and TR170 Service Manual
2
2
Illustration 2.1 Control Terminal Electrical Overview
Control terminals must be programmed. Each terminal has specic functions and a numbered parameter associated with it.
The setting selected in the parameter enables the function of the terminal. See the TR150 and TR170 Quick Guide for details.
BAS-SVM04B-EN02/2017 All rights reserved.21
Frequency Converter Control
2
2.7 Grounding Shielded Cables
Connect the shielded control cables to the metal cabinet
of the frequency converter with cable camps at both ends.
Illustration 2.3 shows ground cabling for optimal results.
Correct grounding
To ensure the best possible electrical connection, t
control cables and cables for serial communication with
cable clamps at both ends.
Illustration 2.2 Correct Grounding
Incorrect grounding
Do not use twisted cable ends (pigtails) since they increase
shield impedance at high frequencies.
Ground potential protection
When the ground potential between the frequency
converter and the PLC or other interface device is dierent,
electrical noise may occur that can disturb the entire
system. Resolve the electrical noise by
cable next to the control cable. Minimum cable cross-
2
section is 10 mm
(8 AWG).
tting
an equalizing
Serial communication control cables
Low-frequency noise currents between frequency
converters can be eliminated by connecting 1 end of the
shielded cable to frequency converter terminal 61. This
terminal connects to ground through an internal RC link.
To reduce the dierential mode interference between
conductors, use twisted-pair cables.
Illustration 2.5 Serial Communication Control Cables
1
Minimum 10 mm
2Equalizing cable
Illustration 2.3 Ground Potential Protection
2
(8 AWG)
50/60 Hz ground loops
When using long control cables, 50/60 Hz ground loops
may occur that can disturb the entire system. Resolve the
ground loops by connecting 1 end of the shield with a
100 nF capacitor and keeping the lead short.
Illustration 2.4 50/60 Hz Ground Loops
2202/2017 All rights reserved.BAS-SVM04B-EN
Internal Frequency Converte...TR150 and TR170 Service Manual
3
3 Internal Frequency Converter Operation
3.1 General
This chapter provides an operational overview of the main
assemblies and circuitry in the frequency converter.
3.2 Description of Operation
3.2.1 Control Logic Section
The control card includes most of the logic section (see
Illustration 3.2). The primary logic element of the control
card is a microprocessor, which supervises and controls all
functions of frequency converter operation. In addition, a
separate PROM contains the parameters to provide the
user with programmable options. These parameters are
programmed to enable the frequency converter to meet
specic application requirements. This data is stored in an
EEPROM providing security during power-down and also
allows the exibility to change the operational characteristics of the frequency converter.
undesired program changes. With the addition of a remote
mounting kit, the LCP can be mounted in a remote
location.
Control terminals, with programmable functions, are
provided for input commands such as run, stop, forward,
reverse and speed reference. Additional output terminals
are provided to supply signals to run peripheral devices or
for monitoring and reporting status.
The control card logic
Communicates via serial link with outside devices
•
such as personal computers or Programmable
Logic Controllers (PLC).
Provides 2 voltage supplies for use from the
•
control terminals.
24 V DC is used for switching functions such as start, stop,
and forward/reverse. The 24 V DC supply also supplies 200
mA of power, which can partly be used to power external
encoders or other devices. A 10 V DC supply rated at 17
mA is also available for use with speed reference circuitry.
The analog and digital output signals are powered through
an internal supply. The 3 power supplies are isolated from
one another to eliminate ground loop conditions in the
control input circuitry.
3
Illustration 3.1 Logic Section
Another part of the logic section is the removable LCP or
display mounted on the front of the frequency converter.
The LCP provides a user interface to the frequency
converter.
All programmable parameter settings can be uploaded into
the EEPROM of the LCP. This function helps in maintaining
a back-up frequency converter prole and parameter set.
Its download function can be used in programming other
frequency converters or restoring a program to a repaired
unit. The LCP is removable during operation to prevent
2 relays for monitoring the status of the frequency
converter are located on the power card. These relays are
programmable through parameter group 5-4* Relays. The
relays are Form C. These relays have one normally open
contact, and one normally closed contact on a single
throw. The contacts of the relay are rated for a maximum
load of 240 V AC at 2 Amps resistance.
The logic circuitry on the control card allows for adding:
Option modules for synchronizing control
•
Serial communications
•
Additional relays
•
Cascade pump controller
•
Custom operating software
•
BAS-SVM04B-EN02/2017 All rights reserved.23
3
Internal Frequency Converte...
3.2.2 Logic to Power Interface
The logic to power interface isolates the high-voltage
components of the power section from the low voltage
signals of the logic section. The interface consists of two
sections.
Power Card
•
Gate Driver
•
The control card handles much of the fault processing for
output short circuit and ground fault conditions. The
power card provides conditioning of these signals. Scaling
of current feedback and voltage feedback is accomplished
on the interface sections before processing by the control
card.
Illustration 3.2 Typical Power Section
3.3 Sequence of Operation
3.3.1
Rectier
Section
The power card contains a Switch Mode Power Supply
(SMPS). The SMPS provides the unit with 24 V DC, 16 V DC,
7 V DC, 6 V DC, and 3.3 V DC operating voltage. SMPS
powers the logic and interface circuitry. SMPS is supplied
by the DC bus voltage. A secondary SMPS provides power
to the logic circuitry with main input disconnected. It can
keep units with communication options live on a network
when the frequency converter is not powered from the
mains.
Circuitry for controlling speed of the cooling fans is also
provided on the power card.
3.2.3 Power Section
The DC coil is a single unit 2 two coils wound on a
common core. One coil resides in the positive side of the
DC bus and the other in the negative. The coil aids in the
reduction of mains harmonics.
The DC bus capacitors are arranged into a capacitor bank
along with bleeder and balancing circuitry.
The inverter section is made up of six IGBTs, commonly
referred to as switches. One switch is necessary for each
half phase of the 3-phase power, for a total of 6. The 6
IGBTs are contained in 3 dual modules.
A Hall eect type current sensor is located on each phase
of the output to measure motor current.
The rectier provides a path for current owing from the
line to the DC-link circuitry. As a result, the DC-link
capacitors charge.
The rectier section consists of 6 diodes.
Inrush current, which appears when connected to grid, is
limited with a PTC. A relay short-circuits the PTC when the
DC-link capacitors are fully charged.
As long as power is applied to the frequency converter,
voltage is present in the DC link and the inverter circuit.
Voltage is also fed to the switch mode power supply
(SMPS) on the power card and is used for generating all
other low voltage supplies.
3.3.2 Intermediate Section
From the rectier section, voltage passes to the
intermediate section. The DC link is an LC lter circuit
consisting of the DC-link inductor and the DC-link
capacitor bank that smooths the rectied voltage.
The intermediate section consists of the following
components:
The DC-link inductor located in the positive side
•
of the DC link provides series impedance to
changing current. This impedance aids the
ltering process while reducing harmonic
distortion to the input AC current waveform
normally inherent in rectier circuits.
The DC-link capacitors are arranged into a
•
capacitor bank along with bleeder and balancing
circuitry.
High frequency (HF) lter lm capacitors. These
•
capacitors reduce the common mode noise
caused by switching into stray capacitors to
ground in cable and motor.
2402/2017 All rights reserved.BAS-SVM04B-EN
Internal Frequency Converte...TR150 and TR170 Service Manual
3
The voltage on a fully charged DC link is equal to the peak
voltage of the input AC line. Theoretically, this voltage can
be calculated by multiplying the AC line value by 1.414
(V AC x 1.414). However, since AC ripple voltage is present
on the DC link, the actual DC value is closer to
(V AC x 1.38) under unloaded conditions. The DC value can
drop to (V AC x 1.32) while running under load.
Example
For a frequency converter sitting idle while connected to a
nominal 460 V line, the DC-link voltage is approximately
635 V DC (460 x 1.38). As long as power is applied to the
frequency converter, this voltage is present in the DC link
and the inverter circuit. Voltage is also fed to the switch
mode power supply (SMPS) on the power card which is
used for generating all other low voltage supplies. The
SMPS is activated when the DC-link voltage reaches
approximately 250 V DC.
3.3.3 Inverter Section
The inverter section is made up of six IGBTs, commonly
referred to as switches. One switch is necessary for each
half phase of the 3-phase power, for a total of six. The six
IGBTs are contained in one power module shared with the
rectier. The inverter section receives gate signals from the
MOC.
Once a run command and speed reference are present, the
IGBTs begin switching to create the output waveform, as
shown in Illustration 3.3. Looking at the phase to phase
voltage waveform with an oscilloscope, a train of pulses of
dierent widths is shown. The amplitude of the pulses
measures the DC-link voltage. To view the fundamental
sinusoidal curve, set the oscilloscope to lter out high
harmonic content.
When measuring current, the normal view will be a
sinusoidal curve. The amplitude of the measured current
depends on the loading form.
This waveform, as generated by the frequency converter,
provides optimal performance and minimal losses in the
motor.
Hall eect current sensors monitor the output current and
feed it back to the control. The current signal is used for
two purposes:
to compensate for dynamic motor operation.
•
to monitor overcurrent conditions, including
•
ground faults and phase-to-phase shorts.
During normal operation, the power card and control
monitor various functions within the frequency converter.
The current sensors provide current feedback information.
The DC bus voltage and mains voltage are monitored and
the voltage delivered to the motor. A thermal sensor
mounted inside the IGBT module provides heat sink temp
feedback for the inverter.
Illustration 3.3 Output Voltage and Current Waveforms
3.3.4 Fan Speed Control
IP20
EnclosureH6H7H8
VoltageT2T2T2 T2T2T2
Power rating
[kW]
FAN s tar t
temperature
FAN maximum
speed
temperature
FAN s top
temperature
Table 3.1 Fan Speed Control, IP20, H6–H8, T2
IP20
EnclosureH6H7H8
Volt ageT4T4T 4T4T4T4
Power rating
[kW]
FAN s tar t
temperature
FAN maximum
speed
temperature
FAN s top
temperature
Table 3.2 Fan Speed Control, IP20, H6–H8, T4
IP54
EnclosureI6I7I8
VoltageT4T4T4T4T4T4T4
Power rating
[kW]
FAN s tar t
temperature
1518.522303745
454545454545
°
C
606060606060
°
C
363636363636
°
C
303745557590
454545404040
°
C
606060555555
°
C
414141303030
°
C
22303745557590
45454540404040
°
C
3
BAS-SVM04B-EN02/2017 All rights reserved.25
3
Internal Frequency Converte...
IP54
EnclosureI6I7I8
FAN maximum
speed
temperature
FAN s top
temperature
Table 3.3 Fan Speed Control, IP54, I6–I8
IP20
EnclosureH9H10H6H7H8
Voltage T6T6T6T6T6T6T6T6T6T6T6T6
Power
rating
[kW]
FAN s tar t
tempera-
°
C
ture
FA N
maximum
speed
tempera-
°
C
ture
FAN s top
tempera-
°
C
ture
60606055555555
°
C
35353530303030
°
C
2.2 3.0 5.5 7.5 11 15 22 30 45 55 75 90
35 35 35 35 45 45 45 45 40 40 40 40
55 55 55 55 60 60 60 60 55 55 55 55
31 31 31 31 36 41 41 41 30 30 30 30
Table 3.4 Fan Speed Control, IP20, H9–H10, and H6–H8, T6
2602/2017 All rights reserved.BAS-SVM04B-EN
TroubleshootingTR150 and TR170 Service Manual
4
4 Troubleshooting
4.1 Troubleshooting Tips
Before repairing a frequency converter, read and
understand the following instructions.
1.Note all warnings concerning voltages present in
the frequency converter. Always verify the
presence of AC input voltage and DC link voltage
before working on the unit. Some points in the
frequency converter are referenced to the
negative DC link. They are at DC link potential
even though it sometimes appears on diagrams
to be a neutral reference.
CAUTION
Voltage can be present for as long as 20 minutes on
frequency converters after removing power from the
unit. See the label on the front of the frequency
converter door for the specic discharge time.
2.Never apply power to a unit that is suspected of
being faulty. Many faulty components within the
frequency converter can damage other
components when power is applied. Always
perform the procedure for testing the unit after
repair as described in chapter 4.7 After RepairTes ts .
3.Never attempt to defeat any fault protection
circuitry within the frequency converter, as this
results in unnecessary component damage and
can cause personal injury.
4.Always use factory approved replacement parts.
The frequency converter is designed to operate
within certain specications. Incorrect parts can
tolerances and result in further damage to
aect
the unit.
5.Read the instruction manual. A thorough
understanding of the unit is the best approach. If
ever in doubt, consult the factory or authorised
repair centre for assistance.
4.2 Exterior Fault Troubleshooting
There may be slight dierences in servicing a frequency
converter that has been operational for extended time,
compared to a new installation. In either case, use proper
troubleshooting procedures.
CAUTION
RISK OF INJURY OR PROPERTY DAMAGE
Never assume that a motor is wired properly after a
service of the frequency converter. Check for:
Loose connections.
•
Improper programming.
•
Added equipment.
•
Failure to perform these checks can result in personal
injury, property damage, or less than optimal
performance.
Take a systematic approach, beginning with a visual
inspection of the system. See Tabl e 4.1 for items to
examine.
4.3 Fault Symptom Troubleshooting
The troubleshooting procedures are divided into sections
based on the
1.See the visual inspection check list in Tab l e 4.1.
2.The most common fault symptoms are described
dierent
Often, incorrect installation or wiring of the
frequency converter causes the problem. The
check list provides guidance through the items to
inspect during servicing of the frequency
converter.
in chapter 4.5 Fault Symptoms:
•
•
The frequency converter processor monitors
inputs and outputs as well as internal frequency
converter functions. An alarm or warning does
not necessarily indicate a problem within the
frequency converter itself.
For each incident, further description explains how to
troubleshoot that particular symptom. When necessary,
further referrals are made to other parts of the manual for
more procedures.
When troubleshooting is complete, perform the list of tests
provided in chapter 6.5 Initial Start-up Or After Repair DriveTes ts .
occurring symptom.
Problems with motor operation.
A warning or alarm shown by the
frequency converter.
4
BAS-SVM04B-EN02/2017 All rights reserved.27
4
Troubleshooting
4.4 Visual Inspection
Visually inspect the conditions in Table 4 .1 as part of any initial troubleshooting procedure.
Inspect forDescription
Auxiliary equipment
Cable routing
Control wiring
Frequency converter coolingCheck operational status of all cooling fans:
Frequency converter displayThe display shows important items, such as:
Frequenc y converter interior
EMC considerations
Environmental conditions
GLCP
Grounding
Look if more auxiliary equipment, switches, disconnects, or input fuses/circuit breakers reside on the
•
input power side of frequency converter or output side to motor.
Examine operation and condition of these items as possible causes for operational faults.
•
Check function and installation of pressure sensors or encoders, and other equipment used for
•
feedback to the frequency converter.
Avoid routing motor wiring, AC line wiring, and signal wiring in parallel. If parallel routing is
•
unavoidable, maintain a separation of 150–200 mm (6–8 inches) between the cables or separate them
with a grounded conductive partition.
Avoid routing cables through free air.
•
Check for broken or damaged wires and connections.
•
Check the voltage source of the signals. Though not always necessary depending on the installation
•
conditions, the use of screened cable or a twisted pair is recommended.
Ensure that the screen is terminated correctly.
•
When voltage is applied to the frequency converter, the fan activates for a few seconds.
•
Check for blockage or constrained air passages.
•
Warn ings.
•
Alarms.
•
Frequency converter status.
•
Fault histor y.
•
Check that the frequency converter interior is free of :
•
-Dirt.
-Metal chips.
-Moisture.
-Corrosion.
Check for burnt or damaged power components, or carbon deposits that are the result of a
•
catastrophic component failure.
Check for cracks or breaks in the housings of power semiconductors, or pieces of broken component
•
housings, which are loose inside the unit.
Check for proper installation regarding electromagnetic capability.
•
Refer to the frequency converter operating instructions and this chapter for further details.
•
Under
•
Humidity levels must be less than 95% non-condensing.
•
Check for harmful airborne contaminates such as sulfur-based compounds.
•
If supplied, check that the GLCP is correctly installed, and that the display is lit when powered on.
•
The frequency converter requires a dedicated ground wire from its enclosure to the building ground.
•
It is also suggested to ground the motor to the frequency converter enclosure.
The use of conduit or mounting of the frequency converter to a metal surface is not considered to
•
be suitable grounding.
Check for good ground connections that are tight and free of oxidation.
•
conditions, these units can be operated within a maximum ambient of 50 °C (122 °F).
specic
2802/2017 All rights reserved.BAS-SVM04B-EN
TroubleshootingTR150 and TR170 Service Manual
4
Inspect forDescription
Input power wiringCheck for:
Loose connections.
•
Proper fusing.
•
Blown fuses.
•
Memory module
Motor
Output to motor wiringCheck for:
PROFIBUS option
ProgrammingEnsure that frequency converter parameter settings are correct according to:
Proper clearanceThe frequency converter requires top and bottom clearance adequate to ensure proper air ow for
Vibration
Check that the memory module is plugged in correctly.
•
Check nameplate ratings of the motor.
•
Ensure that motor ratings coincide with frequency converters.
•
Ensure that the frequency converter motor parameters (parameter 1-20 Motor Power to
•
parameter 1-25 Motor Nominal Speed) are set according to motor ratings.
Loose connections.
•
Switching components in output circuit.
•
Faulty contacts in switch gear.
•
Check that the option is mounted correctly on the control card.
•
Motor.
•
Application.
•
I/O conguration.
•
cooling in accordance with the frequency converter size. When the heat sink is exposed at the rear of
the frequency converter, mount the frequency converter on a
Check for exposure to an unusual amount of vibration.
•
When the frequency converter experiences a high level of vibration, ensure solid mounting or use
•
shock mounts.
solid surface.
at,
4
Table 4.1 Visual Inspection Check List
BAS-SVM04B-EN02/2017 All rights reserved.29
Loading...
+ 73 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.