Trane Symbio CVRF Installation Instructions Manual

Page 1
Installation Instructions
Symbio™ Chiller Controller Retrofit Replacement Panel UCP2
Model Number:
Note: Distribution/use of this document is limited to the Trane sales and service organization in support of the Symbio™ control
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
August 2022
CVRF
SAFETY WARNING
CVRF-SVN005C-EN
Page 2
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTIONs
NOTICE
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this u MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
WAYS refer to the appropriate SDS and OSHA/GHS
AL (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized elec flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
nit, technicians
trical contact, arc, or
©2022 Trane CVRF-SVN005C-EN
Page 3
WARNING
Refrigerant May Be Under Positive Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains refrigerant and may be under positive pr
essure; system may also contain oil. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or non-approved refrigerant additives.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Trane personnel must follow the company’s
Env
ironmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
Non-Trane personnel should always follow local regulations.
Introduction
CTV-SVD005*-EN1, Diagnostics Manual - Diagnostic Descriptions, Troubleshooting Tables, and Control Component Overview for Water-Cooled CenTraVac™ Chillers with Tracer AdaptiView™ Control
BAS-SVU047*-EN1, Getting Started Guide: To ol
CVRF-SVP01*-EN, Programming Guide: Tracer
™ Panel Upgrade
Symbio
TU Service
Revision History
Minor updates to the document.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Other Required Manuals
This manual must be used with the following publications (or their most recent versions):
CVHE-SVX005*-EN1, Installation, Operation, and Mainten CenTraVac™ Chillers With Symbio™ Control
CTV-SVU004*-EN1, Operations Guide - Tracer® Adap Chillers with Symbio™
CTV-SVP004*-EN1, Tracer TU Service Tool for Water­Coo
ance - CVHE, CVHF, and CVHG Water-Cooled
tiView™Display for CenTraVac™Water-Cooled
led CenTraVac Chillers with Symbio™ Control
CVRF-SVN005C-EN 3
Page 4
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . 5
About This Manual . . . . . . . . . . . . . . . . . . . . . . 5
Application Guidelines . . . . . . . . . . . . . . . . . . . 5
Getting Started . . . . . . . . . . . . . . . . . . . . . . . . . 5
Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Symbio™ Panel Conversion Kit Contents . . . 6
Notes for Remote Starter and
AFD Installations . . . . . . . . . . . . . . . . . . . . . . . 8
Note for Open Transition Starters . . . . . . . . . . 8
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . 8
Field-Provided Material . . . . . . . . . . . . . . . . . . 8
Model Number Descriptions . . . . . . . . . . . . . . . 10
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control Panel Conversion . . . . . . . . . . . . . . . 12
Before You Begin . . . . . . . . . . . . . . . . . . . . . . 12
Removal of Existing Panel . . . . . . . . . . . . . . 13
Installation of New Control Panel . . . . . . . . . 13
Wiring Installation . . . . . . . . . . . . . . . . . . . . . . 13
Motor Temperature Devices . . . . . . . . . . . . . 14
Mount Display Arm and Display . . . . . . . . . . 14
Adjusting the Tracer® AdaptiView™
Display Arm . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Oil Pressure Transducer Installation . . . . . . 17
Sensor Installation and Wiring . . . . . . . . . . . 17
Mounting Sensors Externally . . . . . . . . . . . . 18
Temperature Sensor Cable
Mounting for Wells . . . . . . . . . . . . . . . . . . . . . 18
Option I/O Installation . . . . . . . . . . . . . . . . . . 18
Inlet Guide Vane Actuator Installation . . . . . 18
Running the IPC Bus . . . . . . . . . . . . . . . . . . . 19
Purge Control Installation . . . . . . . . . . . . . . . 21
PRGC Purifier Purge . . . . . . . . . . . . . . . . . 21
PRGD, PRGG and PRGF EarthWise Purge 21
LONTALK® Option Installation . . . . . . . . . . . 22
Communication Option Installation . . . . . . . . 22
Wi-Fi Installation . . . . . . . . . . . . . . . . . . . . . 22
Air-Fi Installation . . . . . . . . . . . . . . . . . . . . 23
LTE Modem Installation . . . . . . . . . . . . . . . 23
Communication Device Mounting . . . . . . . 24
Water Flow Measurement . . . . . . . . . . . . . . . .25
Standard Accuracy Option . . . . . . . . . . . . . .25
Mounting of Flow Measurement Assembly .25
High Accuracy, Customer Provided
Meter Option . . . . . . . . . . . . . . . . . . . . . . . .26
Heat Recovery/Aux COND Option . . . . . . . .27
Energy Meter Option Installation . . . . . . . . . .28
480 Volts and Lower Installations . . . . . . . .29
Oil Pump Control . . . . . . . . . . . . . . . . . . . . .31
120 Vac Components Matrix . . . . . . . . . . . .31
120 Vac Oil Pump Starter Capacitor and Starter
Relay (Left) . . . . . . . . . . . . . . . . . . . . . . . . . 31
Line Voltage Pump Installation . . . . . . . . . .31
120 Vac Non Refrigerant Pump Style
Oil Pump Installation . . . . . . . . . . . . . . . . . . 31
120 Vac Refrigerant Pump Style Oil
Pump Installation . . . . . . . . . . . . . . . . . . . . .32
Installation of Oil Pump
Motor Wiring and Terminals . . . . . . . . . . . . . .32
Starter Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Starter Control Planning . . . . . . . . . . . . . . . . .33
Starter Sub-Box Installation . . . . . . . . . . . . . .33
Starter Sub-Panel . . . . . . . . . . . . . . . . . . . . . .34
Starter Sub-Panel Installation . . . . . . . . . . . . . 37
AFD Sub-Panel . . . . . . . . . . . . . . . . . . . . . . . . 39
Control Power Transformer . . . . . . . . . . . . . . .40
Current Transformers, CTs . . . . . . . . . . . . . . .40
CT Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Potential Transformers, Optional PTs . . . . . .44
Starter Wiring . . . . . . . . . . . . . . . . . . . . . . . . . .44
Wiring Diagram Matrix . . . . . . . . . . . . . . . . . . . . .46
4 CVRF-SVN005C-EN
Page 5
General Information
MODEL NUMBER : CVRF21000AA1FFB1001001000C000100A1 SERIAL NUMBER : L22C01078 ORDER NUMBER : LARRYSP4 ORIG. SERIAL NUMBER; L22A00000
LITERATURE CVRF-SVN005*-EN CVHE-SVX005*-EN CTV-SVU004*-EN BAS-SVNU47*-EN CVRF-SVP001*-EN CTV-SVP004*-EN www.trane.com/Patent MADE IN USA
SYMBIO 800
UPGRADE CONTROL AND PANEL
FOR USE ON LIQUID CHILLERS
About This Manual
This manual is provided to support the factory-assembled CVRF complete control panel for former factory installed UCP2 control panels. It does not apply to model CVRA, CVRB, CVRC, CVRD, or CVRE retrofit controls. This work replaces the older control panel with the current Symbio™ Chiller Control system. The factory assembled portion is the control panel only. Some of the control items will be field-installed.
The step-by-step instructions outlined in this manual describe
e procedures required to successfully install Symbio™
th controls on CVHE, CVHF, or CVHG units with a UCP2-based control system.
Notice that the insta divided into the following general topic areas:
1. Control panel installation includes removal of existing control pa
llation instructions in this manual are
nel. It is followed by installation of new panel and
4. AFD planning for UCP2 starter module equipped AFDB, AFDC, AFDG and early AFDH AFDs.
5. Actuator mounting includes removal
of the old actuator and
installation instructions for the stepper IGV actuator.
6. Accessories and options installation includes information
n how to install and wire any optional LLIDs or
o components. LLIDs are individual control components that communicate with the main processor.
Note: Ne
w Symbio™ and older Trane® wiring diagrams are often referenced throughout this manual. Locate any drawings reflecting changes, upgrades, or BAS tie-ins that have been performed on the unit since original installation. A complete set of Symbio™ wiring diagrams are referenced in
p. 46
in this manual. You may find it helpful to obtain a
py of the machine or job specific drawings before
co
“Wiring Diagram Matrix,”
you attempt to perform the control system conversion.
mounting brackets, and wiring in the new control panel.
2. Sensor installation includes the
mounting of temperature
and pressure sensors and wiring instructions.
3. Starter Panel planning for wye-delta starter applications, as additional information for converting non-wye-
as well
Application Guidelines
This Symbio™ control package is specifically designed to upgrade the controls of CVHE, CVHF, and CHVG water cooled chillers with a UCP2 control panel electrical section.
delta starters.
Table 1. Retrofit panel types
Description Application
Single door pneumatic 1966 to 1976 Trane CenTraVac chillers with pneumatic controls and a single horizontal door control panel
Double door pneumatic 1976 to 1980 Trane CenTraVac chillers with pneumatic controls and a double horizontal door control panel
Classic 1980 to 1985 CVHE/CVHB CenTraVac chillers with
(b)
UCP1
(b) 1993 to 2001 CVHE/CVHF/CVHG CenTraVac chillers having factory installed Trane UCP2 digital controls
UCP2
(a) These are general guidelines. The dates are not exact. It is necessary to confirm exactly which control system your chiller has. (b) The UCP1 and UCP2 application is specific to those units originally shipped with those controls. It does NOT include retrofit UCP1, UCP2, and UCP2 FastPak™ controllers;
to upgrade chillers with retrofit UCP1, UCP2, and UCP2 FastPak™ controllers, please refer to the appropriate manual for the original unit controls.
1985 to 1993 CVHE/CVHB/CVHF CenTraVac chillers having factory installed Trane UCP1 digital controls
(a)
Trane electronic “Classic” type controls
Getting Started
Figure 1. Symbio™ nameplate example
To properly install a Tracer® AdaptiView™ retrofit, the technician must have a good knowledge of Symbio™ control systems. Training in Symbio™ controls is highly recommended before beginning this retrofit.
Nameplates
A Symbio™ nameplate is provided with the kit; the nameplate should be placed onto the panel after installation. Always provide the model number and serial number information from the nameplate when making inquiries, or ordering parts or literature for the Symbio™ retrofit system.
CVRF-SVN005C-EN 5
Page 6
General Information
Remove the existing chiller nameplate on the unit and relocate to the outside of the new control panel. Important information is contained on this existing nameplate that must be retained for future unit servicing. If nameplate cannot be removed and relocated, copy information from old nameplate onto new vinyl nameplate included in retrofit package.
installed, wired, bound, and tested, along with some device LLIDs shipped loose that require field installation and binding.
Before commencing the Symbio™ control retrofit, be sure to compare the data on the panel nameplate and ordering and shipping information to the data in the following tables to verify that the proper Symbio™ components were shipped. The tables are split into those components that are factory installed and those that are shipped loose and need to be field installed.
Symbio™ Panel Conversion Kit Contents
If an inspection of the conversion package reveals damage or material shortages, be sure to file these claims with the carrier
immediately. Specify the extent of the damage or material Each Symbio™ panel conversion kit includes a pre-assembled control panel with a number of standard features and options
Table 2. LLID legend and identification
LLID Name Description Part Number
Tracer® Adaptiview™ color display MOD03183
LON
DAIO Dual analog input and output BRD04875
DBI Dual low voltage binary input BRD04873
DHVBI Dual high voltage binary input BRD04874
DRO Dual relay output BRD04878
HPRO High power relay output MOD01401
IGV Inlet guide vane stepper actuator ACT00680
(a)
®
LonTalk Communications interface for chillers
shortages and be sure to notify the appropriate Trane
representative. Do not install a damaged component or panel.
KIT18458, KIT; ECHELON MODULE FIELD INSTALL KIT
Power supply 27 Vac to 24 Vdc for bus power supply BRD02102
Pressure sensor Low pressure range, 0 to 50 psia TDR00733
Pressure sensor High pressure range, 0 to 475 psia TDR00734
Pressure transducer
QRO Quad relay output BRD04879
Starter module Trane control board, starter module BRD04877
Starter module power supply 110 Vac/24 Vdc power supply PWR00147
Starter module on sub plate without power supply or LV PTs
Starter module on sub plate without power supply with LV P Ts
Starter module on sub plate with power supply without LV P Ts
Starter module on sub plate with power supply and LV PTs
AFD starter nodule on sub plate without power supply or LV PTs
AFD starter nodule on sub plate with power supply without LV PTs
Temp sensor Low range temperature sensor SEN02133
Triac Dual triac output BRD04876
TWTI Triple winding temperature input MOD02462
Danfoss pressure transducer, 475 PSI 7/16-20 NUF
Starter sub-panel for unit mount medium voltage
starters
Starter sub-panel for remote mount medium voltage
starters
Starter sub-panel for unit mount low voltage starters 018504220100
Starter sub-panel for remote mount low voltage
starters
Assembly for unit mount UCP2 AFDB, AFDC, and non­communicating AFDH
Assembly for remote mount UCP2 AFDB, AFDC, and non-communicating AFDH
TDR00735
018504210100
018504330100
018504350100
018504340100
018504370100
Symbio™ controller MOD02979
6 CVRF-SVN005C-EN
Page 7
General Information
Table 2. LLID legend and identification
(a)
(continued)
LLID Name Description Part Number
WIFI WiFi Mobile App MOD03122
AIRFI Air-Fi BACnet via Zigbee
LTE LTE 4G modem MOD03184
(a) All part number information in this table is subject to change at any time. Contact the Tran e Parts Center for assistance with identification of all parts involved with the Symbio™
system.
018504240100 MOD02971
Table 3. Factory installed LLIDs
DBI DHVBI HPRO QRO TWTI
Panel type—factory UCP2 1 2 1 3 1 2 1 1
Power Supply Symbio™ 800 Color Display
Table 4. Field installed LLIDs for various options
PS
475
DBI DHVBI DBO HPRO QRO DAIO LON IGV
Panel type ­factory UCP2
Starter module 3-phase
Actuator ­stepper
Oil protection ­full, low pressure, or high pressure
Heat recovery / aux con
denser
Hot gas bypass 1 1
Cold water reset 1
Enhanced
ection
prot
Chilled/tower water flow display, standard accuracy with Trane provided sensor/meter
Chilled/tower wa
ter flow display, high accuracy
Heat recovery / aux con
denser water flow display, standard accuracy
Heat recovery / aux con
denser water flow display, high accuracy
Extended opera
tion
1 2
1
1
2 1 1
PSI
1 or 2
4
2
Tem p
Sensor
7 1
3 1
PS
0 to 50
or 475
PSI
2
Starter
Module
1
Color
Display WiFi AirFi LT E
CVRF-SVN005C-EN 7
Page 8
General Information
Table 4. Field installed LLIDs for various options (continued)
PS
475
Tem p
PSI
DBI DHVBI DBO HPRO QRO DAIO LON IGV
Free cooling 1 1
®
LONTALK
Generic BAS 2
WiFi Mobile App 1
Air-Fi BACnet via Zigbee
LTE 4G modem 1
Notes for Remote Starter and
1
Note: Some field provided material will be required to
AFD Installations
For applications having remote starters or AFDs, the remote starter/AFD backplate will be provided with a 24 Vdc power supply. When this power supply is used, connect the existing starter module communications twisted pair to the communications terminals of one of the power supplies at the control panel.
Type A to Type B USB cable
Computer having Tracer® TU version 13.0 or newer
Digital multi-meter, with phase detection capability
13-mm and 14-mm wrenches
6-mm Allen wrench
Sensor
perform the replacement. This is a partial list in addition to normal service tools and hardware.
PS
0 to 50
or 475
PSI
Starter
Module
Color
Display WiFi AirFi LTE
1
Do not connect 24 Vdc power between the panel power supplies and the starter backplate supply.
You can use CAB01163 to connect the starter module to the control panel if new communications cable is needed. This cable is not included in the standard package and can be ordered through Trane Parts Centers. It is a four conductor 150 foot cable that can be used for communication.
Note for Open Transition Starters
Field-Provided Material
Some field provided material will be required to perform the Symbio™ controls retrofit. A list of material is provided here to help the technician plan ahead and to avoid material shortages at the job site.
Wire, Red #16 AWG - Control wire will be required to make the connections between LLIDs and existing components.
Wire connectors (fork, ring, 1/4 and 3/16-inch female quick
For applications with open transition starters, the starter will have to be replaced with a closed transition style. Symbio™ controls will not function with an open transition starter.
connect), and crimping tool for these connectors. Wire markers will be required to identify field wiring. Wire nuts and splicers may be required if splicing wires in the control panel. Cable ties help to “clean up” wiring runs.
Tools Required
Common hand tools and hand-held power tools are required to perform the work. A trained service technician with a well­stocked tool chest should have all of the necessary tools to perform the job. The following list is a sampling of the tools that one could expect to find inside the technician’s tool chest:
Box-end wrenches in sizes from 5/16 to 1.5-inch.
3/8 and 1/2-inch drive socket sets
Electric drill with 1/2-inch. chuck
Drill index with bit sizes ranging from 3/32 to 1/2-inch.
Wire strippers and cutters
A standard selection of Phillips-head and flat-bladed screwdrivers in various sizes and lengths
The following special tools are also required to perform the controls retrofit:
A heat conductive adhesive will be required when mounting the bearing temperature sensors to the bearing oil return lines. Use “Loctite® 383 Output High Strength Adhesive”, or equal.
An epoxy will be required when mounting plastic sensor sleeves on the machine for externally mounted sensors. Trane recommends Loctite® Quickset Epoxy.
A can of Executive Beige spray paint (Trane part # PAI00061) or standard gray may be required for touch-up work.
Field provided fuses will be required when installing the optional potential transformers. Refer to
Table 5, p. 9 for
proper fuse sizing.
Field provided relays may be required in the starter (refer to
“Wiring Diagram Matrix,” p. 46).
A control power transformer may be required if the existing transformer in the starter panel does not have a minimum capacity of 3 kVA.
8 CVRF-SVN005C-EN
Page 9
General Information
“Loctite 565 Liquid Thread Sealant” (Trane part number SLT00042) for installing pressure transducers. This sealant type does not require the use of heat to break the seal if a transducer needs to be replaced in the future.
“Loctite 277 Thread Lock” (Trane part number SLT00037
ml tube) for the adapter fittings used to convert the flare connections previously required by the oil differential pressure switch (1S2) from the existing control system to allow installation of Symbio™ pressure transducers on the copper oil lines.
for a 10-ml tube, or Trane part number SLT00038 for a 50-
Table 5. Fusing added for 2F1, 2F2 and 2F3 (as needed) for optional PT transformers
Voltage (Vac) Fuse (A) Voltage (Vac) Fuse (A)
200 1 600 1
230 1 2400 1
380 1 4200 1
460 1 3300 1
575 1 6600 1
Replacing an existing UCP2 control system with one based on the Symbio™ control scheme requires a number of wiring and hardware changes. To ensure that the chiller control system retrofit procedure is performed properly, carefully review the instructions in this section, and, if necessary, contact a qualified service organization before beginning the work.
Important: R
ecord a detailed description of all electricalchanges made during the Symbio™ retrofit process. Be sure to add a copy of this report to the chiller record file for future reference.
CVRF-SVN005C-EN 9
Page 10
Model Number Descriptions
For service purposes, Symbio™ 800 Panel Upgrade Kits are assigned a multiple character alphanumeric model number that precisely identifies each unit. An explanation of the identification code that appears on the unit nameplate is shown below. Use of the servicer will enable the owner/operator, installing contractors and service technicians to define the operation, components and options for any specific unit. Refer to the control panel model number printed on the nameplate when ordering replacement parts or requesting service.
Digit 1, 2, 3
CVR CenTraVac® liquid chiller retrofit
Digit 4 — Development Sequence
F = Tracer Symbio™800 chiller controller
Digit 5 — Panel Type
A = Single door pneumatic controls B = Double door pneumatic controls C = Classic black controls G = Generic 1 = UCP–1 2 = UCP–2
Digit 6 — Solid State Oil Relay Control
1 = No solid state relay A = Solid state relay only B = Solid state relay W/ELM01116 C = Solid state relay W/ELM08119
Digit 7, 8 — Chiller RLA (CTs)
00 = None, uses existing signal 0J = <600 V, 33–50 A, 2" hole, CTs (3) 0K = <600 V, 18–27 A, 2" hole, CTs (3) 0A = <600 V, 67–100 A, 2" hole, CTs (3) 0B = <600 V, 100–150 A, 2" hole, CTs (3) 0C = <600 V, 134–200 A, 2" hole, CTs (3) 0D = <600 V, 184–275 A, 2" hole, CTs (3) 0E = <600 V, 267–400 A, 2.5" hole, CTs (3) 0F = <600 V, 334–500 A, 2.5" hole, CTs (3) 0G = <600 V, 467–700 A, 2.5" hole, CTs (3) 0H = <600 V, 667–1000 A, 2.5" hole, CTs (3) 0L = <600 V, 936–1400 A, 3.5" hole, CTs (3) 0M = <600 V, 1260–1800 A, 4" hole CTs (3) 0N = Turn down transformer 5 A to 100 mA (3) 0P = >600 V, 8–18 A, 1.25" hole, CTs (3) 0R = >600 V, 18–27 A, 1.25" hole, CTs (3)
0T = >600 V, 24–144 A, 4" hole, CTs (3) 0U = >600 V, 120–252 A, 4" hole, CTs (3) 0V = >600 V, 480–1080 A, 4" hole, CTs (3) 0W = >600 V, 864–1800 A, 4" hole, CTs (3)
Digit 9 — Chiller Voltage Monitoring (Potential Transformers)
0 = None A = 480 Vac or less B = Greater than 600 Vac C = 2300/2400 Vac D = 3300 Vac E = 4200 Vac F = 6600 Vac/50 Hz
Digit 10, 11 — Design Sequence
A0 = 1st Design sequence
Digit 12 — Actuator
1 = Stepper actuator 2 = Pulse actuator (generic only)
Digit 13 — Oil Protection
F = Full protection for low pressure
units
H = Full protection for high pressure
units (generic only)
P = Oil pressure status for low
pressure units (generic only)
Digit 14 — Motor Protection and HPC
F = Full motor protection with 15 psig HPC switch H = High pressure option with 195 psig HPC switch (generic only)
Digit 15 — Symbio™ 800 Monitor
A = Without Symbio™ 800 monitor B = With Symbio™ 800 monitor
Digit 16 — Starter Box
0 = None 1 = Starter enclosure
Digit 17 — Free Cooling
0 = No 1 = Yes
Digit 18 — Heat Recovery/Auxiliary Condenser
0 = No 1 = Yes
Digit 19 — Hot Gas Bypass
1 = No 2 = Compressor discharge temp
sensor with LLID, bulb well 3 = 3 in. HGBP valve with sensor, LLID, bulbwell, conduit 4 = 4 in. HGBP valve w/sensor, LLID,
bulbwell, conduit 5 = 5 in. HGBP valve w/sensor, LLID,
bulbwell, conduit
Digit 20 — Tracer Interface Control
0 = None 2 = With generic BAS 5 = LonTalk
®
Digit 21 — Cold Water Reset (CWR)
0 = No 1 = Yes
Digit 22 — Enhanced Protection
0= No 1 = -15 to 35 psig (0 to 50 psia) low
pressure transducer
2 = 15 to 335 psig (0 to 350 psia)
high pressure transducer (generic only)
Digit 23 — Extended Operation
0 = No 1 = Yes
Digit 24 — Chilled/Tower Water Flow Display
0 = No 1 = Water flow display standard
accuracy, dual pressure sensor
2 = Water flow display high
accuracy, customer flow meter
Digit 25 — Design Special
0 = Standard unit offering
Digit 26 — Purge Upgrade
A = No purge option C = Interface for UCP2 purge E = ECOWISE purge
Digit 27 — AirFi Operation
0 = No 1 = Yes
Digit 28 — WiFi Operation
0 = No 1 = Yes
Digit 29 — LTE Operation
0 = No 1 = Yes
Digit 30 — Panel Enclosure
1 = Standard enclosure, NEMA 1
type
2 = NEMA 4 enclosure
Digit 31 — NEMA 4 Communication Box
0 = Without box 1 = Small box 2 = Large box
Digit 32 — Energy Meter Operation
0 = No A = Energy meter, 480V and low
10 CVRF-SVN005C-EN
Page 11
Digit 33 — Starter Type
0 = No starter module 3 = Starter module current limit 3
phase A = Starter module with plate for low voltage unit starter B = Starter module with plate for low voltage remote starter C = Starter module with plate for
unit AFD D = Starter module with plate for
remote AFD E = Starter module with plate for medium voltage unit starter F = Starter module with plate for medium voltage remote starter
Digit 34 — Oil Pump Type
1 = 120 Vac standard type oil pump 2 = 120 Vac refrigerant type oil
pump 3 = Line voltage oil pump
Model Number Descriptions
CVRF-SVN005C-EN 11
Page 12
Installation
Field Installed Nameplate
Control Panel Conversion
The control panel conversion will consist of removing, marking, and retaining selected wires in the existing control panel. The existing control panel will be removed.
The new control panel will be installed. The existing wires will be terminated panel along with any new wires required.
Make a note of run hours and starts o counter. Symbio™ controller will allow you to enter this information into its program.
Remove the nameplate from the exi original nameplate is a stick-on label, it may be necessary to cut out the metal section. This nameplate needs to be moved and attached to the new control panel near the new control panel nameplate. The old nameplate contains original unit information that will be useful in service and parts issues in the future.
A blank vinyl nameplate is included. Transfer information from
e old nameplate to the new one and install on new panel.
th
Figure 2. Recommended nameplate location on new
on the terminal block or LLIDs in the control
n the hour meter and start
sting panel. If the chiller
nel
pa
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
Before You Begin
1. Identify all field modifications made to the existing chiller
control scheme; then label all field-installed wiring entering the control panel accordingly, if required. This may include things like the power supply for the purge and any BAS interface wiring.
2. Determine how each of the field-adapted control functions
just iden Symbio™ chiller control panel.
3. Capture all existing chiller control settings before powering
dow
4. Open all starter and control panel disconnect switches and
secure them in th
tified in
n chiller controls.
Step 1 will be assumed by the new
at position.
Note: T
5. Disconnect all field-installed wiri panel (i.e., identified in termina 1TB1-11 to -13.
6. Remove from the control panel terminal block all wiring that has been routed through conduit from the starter panel to the control panel. (Wires 3D, 4C and oil pump interlock between 1TB1-7 to -8 and 120 Vac power to control panel between 1TB1-1 to -2 are typical.)
o eliminate migration of refrigerant into the oil sump, temporarily connect a field supplied thermostat and an auxiliary 115 Vac power source to the oil heater. Refer to wire 42A on the IU2 module, terminal J20-I.
ng entering the control
Step 1) from the control panel
l strip. This is typically between 1TB1-10 to -12 and
12 CVRF-SVN005C-EN
Page 13
Installation
Stepper Module (1U3)
Circuit Module (1U2)
Chiller Module (1U1)
Option Module (1U5) (Optional) Digit 6
Figure 3. Typical UCP2 before retrofit
Removal of Existing Panel
Remove the existing UCP2 panel. The existing brackets on the chiller will be reused to mount the new control panel.
Installation of New Control Panel
Install the new control panel using existing hardware to mount it to the UCP2 brackets.
Wiring Installation
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified pe
rsonnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
Unless otherwise indicated, all 115 volt control circuits use, as a minimum, #16 AWG, 600 volt wire. Be sure to use existing conduit wherever possible and separate all 115V wiring from any low voltage circuits.
Most wiring will use the existing wires removed and marked
m the original panel and moved to the terminal block in the
fro new panel. Some wires may need to be connected directly on a LLID terminal.
Table 6, p. 13
details the “before and after” of wires from the the new panel. Also refer to the connection and schematic diagrams listed in
“Wiring Diagram Matrix,” p. 46 for additional
detail.
original panel to
For 50 Hz applications, the control power transformer (1T1) is supplied as a 60 Hz application. To convert from 60 Hz to 50 Hz, the following step must be performed: move wire 2H from H3 on 1T1 to H2.
If you have wired a temporary thermostat and 115 Vac power
urce to the oil heater leads, wait to connect these wires until
so the Tracer® AdaptiView™ retrofit is complete to avoid too much cooling of the oil.
The information in
t exited the old control panel is to be rewired in the new
tha
Table 6, p. 13 describes where the wiring
factory panel. Also refer to the connection and schematic diagrams listed in
“Wiring Diagram Matrix,” p. 46.
Table 6. Field wiring cross reference, UCP2 to new
panel
To
Existing
Wire #
P5A 1U1 J3-1 1A13 J2-1 External Auto/Stop
P5A 1U1 J3-2 1A13 J2-2 External Auto/Stop
P5B 1U1 J5-3 1A13 J2-3 Emergency stop
P5B 1U1 J5-4 1A13 J2-4 Emergency stop
Black 1U2 J3-1 1A26 J2-1
White 1U2 J3-3 1A26 J2-2
Green 1U2 J3-5 1A26 J2-3
Red 1U2 J3-6 1A26 J2-4
42A 1U2 J20-1 1X1-22 Oil Heater 4HR1
2N 1TB1-4 1X1-8 Oil Heater 4HR1 Neutral
2M 4B3-2 1X1-7
9B/19A 1U2 J22-1 1X1-16 to 4K8 oil pump relay
From
(in Existing Panel)
1U1 J14-1 1A5 J2-1
5K2 Neutral Open neutral
1U1 J12-1 1A5 J2-4 Evap water pump relay
5K1 Neutral Open neutral
1TB1-10 1X1-4 to 5K1, 5S2 flow switches
1TB1-11 1X1-4 to 5K2, 5S3 flow switches
1TB1-12 1X1-19
1TB1-13 1X1-20
Starter Panel Ground 1X1-G
2TB1-1 (1TB1-1) 1X1-1
2TB1-2 (1TB1-2) 1X1-6
(in New
Panel)
Description or
Comments
Motor winding temp sensor
Motor winding temp sensor
Motor winding temp sensor
Motor winding temp sensor
Condenser water pump
y 5K2 coil
rela
Condenser water pump relay 5K2 neutral
Evap water pump relay
tral
neu
Oil pump motor (4B3) neutral
from 5K1, 5S2 flow
s
switche
from 5K2, 5S3 flow
s
switche
Panel ground (from starter)
120 Vac power to control panel from starter 2TB1­1
120 Vac neutral to control pan
el from starter 2TB1-
2
CVRF-SVN005C-EN 13
Page 14
Installation
Table 6. Field wiring cross reference, UCP2 to new
panel (continued)
To
Existing
Wire #
41B 1U2 J16-1 1X1-21
2X 1TB1-4 1X1-7
From
(in Existing Panel)
2TB1-9 (1TB1-8) 1X1-14 Oil pump interlock
2TB1-8 (1TB1-7) 1X1-15 Oil pump interlock
(in New
Panel)
Description or
Comments
Vent line solenoid valve 4L1
Vent line solenoid valve 4L1 neutral
Motor Temperature Devices
The new Symbio™ panel comes with the motor winding temperature input LLID (IA26). This is used for motors that have RTD-type sensors embedded in the motor windings. If the motor does not have RTD-type sensors, motor temperature protection can be accomplished a temperature sensor which installed in the bulb well of the motor, and connect to the IPC bus.
Mount Display Arm and Display
1. Secure the arm to the control panel using the 5/16 - 18 x
1-inch hex bolts, 5/16-inch lock washers, and 5/16 - 18 hex nuts provided. There are pre-drilled holes on the left and right sides of the control panel; select the side that’s most suitable for your specific application.
Note: Th
Figure 5. Production display arm bracket
ere is a production display arm bracket BRK04345
provided that where applicable can be mounted to the
existing control panel mounting arms. When used, the holes on the unused side should be plugged.
Figure 4. Bolting display arm to the panel
2. Securely fasten the Tracer® AdaptiView™ display to the mounting plate on the end of the display arm with the hardware provided.
14 CVRF-SVN005C-EN
Page 15
Figure 6. Attaching the Tracer® AdaptiView™ display to arm
Installation
3. After the display is attached, recheck the arm tension. The arm tension should be set so that the display does not spring up or sag down out of the position it is moved to by the operator.
CAUTION
Tension in Display Support Arm!
Failure to follow instructions below could result in unexpected movement of the spring-loaded support arm which could result in minor to moderate injury. Ensure that the support arm position when removing the Tracer AdaptiView display from the support arm.
is in the full upright
CVRF-SVN005C-EN 15
Page 16
Installation
1
3
4
2
Adjusting the Tracer® AdaptiView™ Display Arm
The Tracer® AdaptiView™ display arm may be too loose or too tight and in need of adjustment. To adjust the tension on the display arm:
1. There are three joints on the display arm that allow the
racer® AdaptiView™ display to be positioned at a variety
T of heights and angles (refer to items labeled 1, 2, and 3 in
Figure 7. Joint locations on the display arm
2. Joint 3 has a 6 mm hex screw controlling the tension on a gas spring, which allows the Tracer® AdaptiView™ display to tilt up and down.
3. Joints 1 and 2 are covered by a plastic cap. Remove the plastic cap to access wrench as necessary.
4. To adjust the swivel of the T (the spin right and left similar to the steering wheel on a car), you need to adjust the hex bolt located inside the display arm back plate. This adjustment needs to be done BEFORE attaching the display. Use a 9/16-inch or 14 mm wrench.
5. Use a 13 mm wrench to adjust the bolt (item labeled 4 in
Figure 7, p. 16) that allows the entire display arm to swivel
the left and right.
to
the hex bolt. Adjust using a 13 mm
racer® AdaptiView™ display
Figure 7, p. 16). At each joint in the display arm there is
ither a hex bolt (1 and 2) or hex screw (3). Turn the hex
e bolt or screw in the proper direction to increase or decrease tension.
Note: Each hex bolt or screw is labeled with ‘loosen’/
‘tighten’, or '+'/'–' indicators.
16 CVRF-SVN005C-EN
Page 17
Oil Pressure Transducer Installation
Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
The two existing oil pressure transducers will be replaced with new
transducers.
1. Use Loctite 565 on pressure transducer so connection can be broke transducer is required. Note which line is oil pump discharge pressure and which is sump pressure. Quickly attach sensors to lines to avoid large quantities of air entering machine.
Adapter fittings are provided with the kit. The transducers can be moun and transducers mounted to minimize any potential stacking of liquid on top of the transducers.
2. Label pressure transducers using labels provided.
n without heat if future replacement of pressure
ted in any direction. Lines should be routed
Sensor Installation and Wiring
Existing UCP2 sensors cannot be used with a Symbio™ retrofit. It is recommended that existing bulb wells be used. Installing new wells would necessitate opening the chiller to atmosphere
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains refrigerant under high pressure. Re
cover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
If installing new bulb wells (optional), use safe refrigerant p
ractices to evacuate the chiller. Install and wire each of the
temperature sensors listed below.
When the sensor is installed in a bulb well, be sure to:
Add thermastic paste to each b sensor.
Ensure that the sensor “bottoms ou well.
It is recommended that sensors “1” through “3” be mounted in
lls. The rest may be installed externally. Connect all
we Symbio™ temperature sensors to the main IPC bus using the provided pluggable cables.
ulb well before inserting the
t” at the base of the bulb
NOTICE
Equipment Damage!
Failure to follow instruction below could result in equipment damage. Never route low-voltage leads with other conductors carrying 30 or more volts.
The Symbio™ component identification is in parenthesis following each sensor name:
1. Oil tank temperature senso
2. Evaporator leaving water te
3. Evaporator saturated refri (4R10)
4. Condenser entering and leaving sensors (4R8 and 4R9)
5. Evaporator entering water temperature sensor (4R6)
6. Condenser saturated refrigeran (4R11)
Locate sensor at the bottom of the condenser or on the
ndenser liquid line upstream of any orifices or float
co valves.
Note: If u
nit has an EarthWise™ purge, PRGD (CH530 controls), the sensor bound as Condenser Saturated Refrigerant Temperature Sensor (used as Purge Liquid Temperature) cannot be used and will need to be unbound. Install the temperature sensor sent with the Tracer® AdaptiView™ components as described above.
r (4R5)
mperature sensor (4R7)
gerant temperature sensor
water temperature
t temperature sensor
CVRF-SVN005C-EN 17
Page 18
Installation
7. Condenser discharge refrigerant temperature sensor 4R16 (optional). This sensor is only shipped if Hot gas bypass or Enhanced Protection packages were ordered and are to be installed.
8. Bearing temperature sensors: inboard-4R1, outboard-4R2 (optional). These sensors are only shipped if Enhanced Protection package was ordered and is to be installed.
Mounting Sensors Externally
1. Remove the paint and rust from the pipe or chiller surface; then use a wire wheel to expose bare metal.
2. Epoxy the supplied plastic sleeve to the pipe surface. Use
3. Install the sensor probe, with thermastic paste,
4. Wrap the sensor with Armaflex® insulation,
Figure 8. Epoxy application
®
Loctite
sleeve. Wire tie the sensor leads to the plastic sleeve tab.
Epoxy Quick Set, or equivalent,
Figure 8, p. 18.
into the
Figure 9, p. 18.
To install insert the threaded end screw this into the temperature well, be inserted through the hole in the strain relief.
Figure 10. Strain relief
Figure 10, p. 18. The temperature probe can
Option I/O Installation
Wire additional LLIDs as shown on schematics. Pay careful attention to which LLIDs require low voltage inputs and which are 115 Vac inputs.
Inlet Guide Vane Actuator Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Figure 9. Sensor mounting with Armaflex insulation
Temperature Sensor Cable Mounting for Wells
For a convenient way to mount Symbio™ temperature sensors into existing wells, order and strain relief CON00849 (10 per package).
18 CVRF-SVN005C-EN
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit b
reaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
Inlet guide vane (IGV) stepper actuator mounting and wiring follows:
Page 19
Installation
1. Installing Symbio™ stepper actuator.
a. Determine the inlet guide vane stroke by manually
closing and opening the vanes and accurately measuring the length of travel.
b. Record this value as it will be used when performing the
post conversion
2. Remove the existing IGV actuator and existing conduit and wire.
3. Install the new IGV actuator on the chiller.
a. Use the connecting hardware retained when the old
ctuator was removed.
a
b. Use the existing actuator mo
and mounting hardware to install the new electric actuator.
The motor can be rotated 180 degrees to accommodate
hardware. The actuator rod may be connected to
existing the mounting plate at the compressor housing or to the vane linkage.
checkout.
unting plate, piston yoke
NOTICE
Equipment Damage!
Failure to ensure that the 0 degree vane position corresponds with the actuator fully closed when mounting the actuator could result in severe damage to the machine.
Figure 11. Installed stepper IGV actuator
through your local Trane Parts Center. Refer to PART-SVB16*­EN for identification of individual cables.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
4. The IGV ships in a mid-position. powered up, it will drive closed. This may mean travel as much as 1 inch. Disconnect the IGV actuator from the IGV linkage until fully retracted.
The first time the IGV is
Running the IPC Bus
There are several ways to string the IPC communication bus on the chiller. The Symbio™ retrofit kit includes a general wire kit that has several different types of wires. An example of a wiring layout can be seen in
vary depending on the options. You may have extra cables,
will or may be short needed cables. Extra cables can be ordered
CVRF-SVN005C-EN 19
Figure 12, p. 20. Each application
Page 20
Installation
Control Panel
CAB01155 leads to female
CAB01149 short, male to female
CAB01146 short, male to 2 female
Transducer LLID
Figure 12. Sample of IPC cable routing
To connect the IPC bus to the control panel LLIDs, thread the bus into the control panel via a knockout or other entry. The CAB01155 connector has a female plug on one end and four stripped leads on the other end. Attach the four stripped leads to the power supply in the control panel.
Figure 13. Connecting the stripped leads to the power
supply
Notes:
R. Red wire for 24 Volts direct current
Bk. Black wire for ground
Bl. Blue
Gr
wire for IPC+ connection
. Gray wire for IPC- connection
Make sure all devices and LLIDs are connected together in some way. Use the correct cables so that you don’t have any open plugs when finished. Avoid placing wire ties directly over plug connectors. This may press on the locking mechanism and over time the plugs may release.
Table 7. Cables shipped for various options
Standard panel cables 5 5 5 10 9 1 2 2
Actuator-stepper 1
Oil protection—full, low pressure or high pressure
Heat recovery / aux
ndenser
co
Hot gas bypass—electric actuator
20 CVRF-SVN005C-EN
CAB01146
branch M
(a)
2F 500 mm
to
1 1
1 1 1
1 1
CAB01147 branch M to 2F 1000 mm
CAB01148
branch M to
3F 500 mm
CAB01149
extension M
to F 1000 mm
CAB01150
extension M
to F 2000 mm
CAB01152
extension M
to leads 1000
mm
CAB01154
extension M
to receptacle
1M
CAB01155
extension F to
leads 1000
mm
Page 21
Table 7. Cables shipped for various options (continued)
Installation
CAB01146
branch M
2F 500 mm
Hot gas bypass—pulse actuator
Cold water reset 1 8
Enhanced protection 1 2 1 3
Chilled/tower water flow
, standard
display accuracy
Heat recovery / aux co
ndenser water flow display, standard accuracy
(a) The letters M and F represent male and female connectors.
CAB01147
(a)
branch M to
to
2F 1000 mm
1 1
2
1
CAB01148
branch M to
3F 500 mm
Purge Control Installation
Important: Be sure to retain all existing purge safety
controls!
The purge power line connections for the power to the unit
ld be wired per the purge wiring diagram. In general the
shou 115 Vac power for the purge originates from the unit control panel. In the new control panel a circuit breaker 1Q2 is provided to power the purge. A neutral connection can be found on the 1X1 terminal strip.
CAB01149
extension M
to F 1000 mm
5. Remove IPC bus cable from power supply LLID. (Ensure rema
6. It is optional to remove and discard the wires (303A, 304A, and 318A) from control power transformer to this power supply LLID (3A5).
7. Disconnect the cable from the DynaView to the power su
8. Remove the tilt bracket from the purge base. DynaView can remain attached to the tilt bracket panel.
9. Connect the IPC bus from the control panel to the IPC bus
PRGC Purifier Purge
The PRGC Purifier™ purge uses UCP2-based
for the purge using an IPC bus cable.
Figure 14. CABO1151 or CABO1153
communications and does not communicate with Tracer® AdaptiView™ controls. To convert the purge to a standalone purge, order KIT02586 from a Trane Parts Center and install it, making sure to install a jumper between terminals J1-5 and J1­6 on the 3UI module when doing the conversion. A PRGC requires a compressor running signal connected to J26, 1 and 2 on 3U1 in the purge to operate in the auto or adaptive modes. Use the Compressor Running contact closure from the quad relay LLID - 1A8, connected to 115 Vac purge source.
CAB01150
extension M
to F 2000 mm
CAB01152
extension M
to leads 1000
mm
CAB01154
extension M
to receptacle
1M
ining LLIDs are still connected to IPC bus).
pply LLID.
CAB01155
extension F to
leads 1000
mm
PRGD, PRGG and PRGF EarthWise Purge
If a stand-alone EarthWise purge (CH530 control) exists on the chiller, it will need some hardware changes to work with the Symbio™ retrofit controls. If the purge is a new installation with the Symbio™, then skip to
1. The compressor running LLID (3A6) will not be needed, nect and remove.
discon
2. The condenser saturated refri
(purge liquid temperature) will not be needed, disconnect and remove.
3. The existing 120-27 Vac transformer and DC power supply
in the purg
e is undersized and should be removed. The purge control will be powered by the Symbio™ panel power supply.
4. Remove and save purge power supply LLID.
CVRF-SVN005C-EN 21
Step 9.
gerant temperature LLID
Page 22
Installation
1A22 SYMBIO800 UNIT CONTROLLER
ETHERNET
USB
LON
1K47
INTERFACE
TRACER
OPTIONAL
COMMUNICATIONS
LTE
4Y2
MODEM
OPTIONAL
1 2
1324
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
Figure 15. LON module
Figure 16. LON wiring, ref. 50712738
LONTALK® Option Installation
Symbio™ 800 system uses a U60 LON module through the USB connection instead of the LCI-C LLID.
1. Install the U60 LON module (KIT18458, KIT; ECHELON MODUL put it at left side of Symbio™ 800.
2. Connect U60 LON module to Symbio™ 800 by USB cable which any one of the four USB ports under the Symbio™ 800 controller.
3. Connect U60 LON module to the BAS system using shie
22 CVRF-SVN005C-EN
E FIELD INSTALL KIT) on the DIN rail on the door,
is provided with the module Connect this cable to
lded cable.
Communication Option Installation
Symbio™ 800 system supports up to 3 wireless interfaces at same time, these are:
Wi-Fi mobile APP for BAS interface
Air-Fi BACnet via Zigbee for component interface
LTE 4G modem interface for remote c
Wi-Fi Installation
Refer to BAS-SVN042*-EN for more information. Mounting and wiring of Wi-Fi module (MOD03122).
1. Drill a 1.36-inch holes on the top of polycarbonate box, curely fasten the Wi-Fi module by gasket and nut which
se provided by module.
2. Connect Wi-Fi module to Symbio™ 800 by USB cable
ich provide by module, plug USB MICRO-B side to
wh
ommunications.
Page 23
Installation
+24
G
-
+
IMC
RED
BLK
GRN
WHT
RED
BLK
BLU
GRY
VDC
+24
G
-
+
MACHINEBUS
VDC
P3
-
+
BACKNET
P1
-
+
-
+
MODBUS
P2
G
IMC
B
IMC
A
1A22 SYMBIO800 UNIT CONTROLLER
SERVICE
ETHERNET 12
USB
1324
TOOL
WI-FI
4Y1
ANTENNA
OPTIONAL
WHT
GRN
BLK
LTE
4Y2
MODEM
OPTIONAL
bottom of Wi-Fi module and USB-A side to any one of the four USB ports under the Symbio™ 800 controller.
Figure 17. Wi-Fi wiring, ref. 50712738
Air-Fi Installation
Refer to BAS-SVX040*-EN for more information. Mounting and wiring of Air-Fi module (0185-0424-0100).
1. Drill a 0.87-inch holes on the top of polycarbonate box, gn this hole with thread hole on the module, and securely
ali fasten the Air-Fi module by M4 screw.
2. Connect Air-Fi module to Symbio™ 800 by Modbus
cable.
3. Remove the cover of module, connect 4 wires cable into 4
wire conn side of cable into two 2 wire connectors and plug them into the Symbio™ 800 controller IMC terminal.
Figure 18. Connecting wiring harness
ector and plug in Air-Fi module, connect other
Figure 19. Wiring harness connection
Figure 20. Air-Fi wiring, ref. 50712738
RE
RED
BLU
BLK
IMC
A
1X3-1
1X3-2
1X3-3
BLK
WHT
WHT
GRN
G
+
+
-
-
P1
BACKNET
1A22 SYMBIO800 UNIT CONTROLLER
P2
MODBUS
USB
1324
-
+
-
MACHINEBUS
+
P3
BLK
GRY
RED
GRN
G
+24
-
VDC
ETHERNET 12
+
BLU
G
IMC
BLK
RED
IMC
B
+24
VDC
SERVICE
TOOL
OPTIONAL
4K48
AIR-FI
INTERFACE
LTE Modem Installation
Modem part is MOD03184, MODULE; CELLULARLE USB 2.9 METER CABLE. Refer to provided literature for setup and operation details.
1. Drill a 1.36-inch holes on the top of polycarbonate box, curely fasten the LTE modem by gasket and nut which
se provided by modem.
2. Connect LTE modem to Symbio™ 800 by USB cable which
provide by module, plug USB MICRO-B side to bottom of LTE modem and USB-A side to any one of the four USB ports under the Symbio™ 800 controller.
CVRF-SVN005C-EN 23
Page 24
Installation
1A22 SYMBIO800 UNIT CONTROLLER
ETHERNET
USB
1324
LON
1K47
INTERFACE
TRACER
OPTIONAL
COMMUNICATIONS
LTE
4Y2
MODEM
OPTIONAL
12
LTE AirFi WiFi
Figure 21. LTE modem wiring, ref. 50712738
Communication Device Mounting
There devices are intended to be mounted on polycarbonate boxes. There are two installation approaches:
1. Each device is mounted independently on a small box (0185-0426-0100).
Figure 23. Boxes
2. Multiple devices are mounted on a large box (0185-0427-
100).
0
All devices connect Symbio™ 800 by standard USB or
bus cable. For installation standard application need to
Mod field drill a 1.09-inch hole on side of box for a snap bushing. This bush can be replaced as field straight connector and conduit (3/4-inch size) as NEMA 4 applications.
The boxes have magnets for flexible attachment to the
™ panel.
Symbio
Figure 22. Device mounting
The single box is 7-inch Long x 5-inch Wide x 5-inch height
Figure 24. Box mounting
The triple box is 15.5-inch Long x 6-inch Wide x 4-inch height.
24 CVRF-SVN005C-EN
Page 25
Figure 25. Boxes
Pressure
transducer
Flow
sensor
Temperature
sensor
Installation
Water Flow Measurement
Standard Accuracy Option
Water flow is determined by measuring pressure drop across heat exchanger using water pressure transducer LLID’s. Standard flow measurement transducers can be ordered for condense, evaporator and auxiliary/heat recovery heat exchangers. The standard accuracy part is (0185-3475-0100), there are two transducer (0185-3475-0100) provided per heat exchanger. Field connect by male to 2 female 1000mm branch cable (CAB01147) which provided in package.
Figure 26. Standard accuracy option
Water Box Types
Figure 27. Fabricated Non-Marine - ¾ inch NPTI port
Figure 28. Fabricated Marine - ¾ inch NPTI port
Mounting of Flow Measurement Assembly
This guidance is for mounting transducers on a wide variety of water boxes including marine type, non-marine type, for both 150 and 300 PSI applications in both fabricated steel and cast­iron construction.
CVRF-SVN005C-EN 25
Page 26
Installation
IPC BUS
LINE 269
-
Pg
+
SIG
4BP4
-
Pg
+
SIG
4BP5
-
Pg
+
SIG
4BP6
-
Pg
+
SIG
4BP7
WATER PRESSURE
EVAP ENTERING
OPTIONAL
TRANSDUCER
WATER PRESSURE
EVAP LEAVING
OPTIONAL
TRANSDUCER
WATER PRESSURE
COND ENTERING
OPTIONAL
TRANSDUCER
WATER PRESSURE
COND LEAVING
OPTIONAL
TRANSDUCER
Figure 29. Cast – ½ inch NPTI port
Preparation of Wells
Install the provided well using bushings as needed.
Water Box Valve Mounting
Figure 30. Standard accuracy flow meter wiring, ref.
50712746
High Accuracy, Customer Provided Meter Option
The high accuracy customer provided meter option provides an analog input/output LLID to monitor a customer provided high accuracy meter 0-10 Vdc or 4 – 20 mA outputs. (Rosemont, etc.) This option allows monitoring of condenser, evaporator flow and auxiliary heat exchangers.
Install needed DAIO LLID(s) (BRD04873) in CVRF control
anel:
p
1. LLID (1A21) is needed for EVAP and COND water flow. nnect flow meter wires to 1A21-J2-1 and 1A21-J2-1 for
Co EVAP, 1A21-J2-4 and 1A21-J2-5 for COND.
2. LLID (1A28) is need for HR Aux/COND water flow. nnect flow meter wires 1A28-J2-1 and 1A28-J2-1 for HR
Co flow or Aux COND.
Mount transducers on the entering and leaving side water box locations with the strainer horizontal, the strainer clean out port pointing down and the transducer facing upwards and connect to unit control buss. After system is filled, loosen the transducer in its threaded fitting. Then crack the isolation valve until water starts dripping from threads. Close the valve and re-tighten the transducer, and then reopen the valve for use.
26 CVRF-SVN005C-EN
Page 27
Figure 31. High accuracy customer meter wiring, ref. 50712746
4
4
RED
J11
1
J1
1
OPTIONAL WATER FLOW METER
CUSTOMER PROVIDE 4-20MA INPUT
1A21 DUAL ANALOG I/O
OPTIONAL
INPUT 1
OUTPUT 121
GND
INPUT 2
OUTPUT 2
GND
4
3
J2
5
6
COND FLOW METER
5B2 CUSTOMER PROVIDE
4-20mA
FLOW
METER
OUTPUT
EVAP FLOW METER
5B1 CUSTOMER PROVIDE
SIGNAL
24VDC
1A2 J5-1
0V
4-20mA
FLOW
METER
24VDC
1A1 J5-1
0V
1A2 J5-2
1A1 J5-2
OUTPUT
SIGNAL
Installation
Heat Recovery/Aux COND Option
When heat recovery/Aux COND option is selected, a DHVBI LLID (BRD04874) is required as 1A29, wires matrix show as following:
Wire # AWG From To
14B 16 1A29-J3-2 1X1-21
2K 16 1A29-J3-1 1X2-10
CVRF-SVN005C-EN 27
Page 28
Installation
Figure 32. HR/Aux COND flow switch wiring, ref. 50712747
RED
REQUIRED OPTIONAL
1X1-3
5S11 5K3
P
d
1X2-G
1A29 DUAL HIGH VOLTAGE BINARY INPUT
4
4
OPTIONAL
HEAT RECOVERY
AUX CONDENSER
WATER FLOW SWITCH
1
1
RED
14B
2
J3
1
2
J2
1
J11
J1
Energy Meter Option Installation
The Trane energy meter provides instrument grade accuracy power, volts and amps monitoring of Symbio™ controls installations. It has 1% accuracy for measuring both real power and energy and reactive power and energy. All data measured by the meter is communicated via Modbus to Symbio™ control system. See BAS-SVN224*-EN for more information.
Figure 33. Energy meter
1X1-21
2K
1X2-10
HEAT RECOVERY AUX CONDENSER WATER FLOW SWITCH
The meter is connected to line voltage of up to 480 volts and should be mounted within the starter cabinet. It is provided with a mounting bracket that can either be mounted on DIN rail or directly to the starter cabinet wall using the provided bracket.
Figure 34. Mounting bracket
28 CVRF-SVN005C-EN
Page 29
Installation
+
Shielded Wire
120 terminators on the first/last devices of daisy
chain
The meter is connected to Modbus communications and is self-powered by the unit voltage potential inputs. Review meter literature for setup and operation details.
Modbus communications is by shielded 14 – 26 AWG cable from meter to Symbio™ module. Please install 120 OHM resistors at first and last modules on Modbus daisy chain.
Figure 35. Modbus communication
S
The communications wiring will be
terminated at the Modbus distribution terminal (1X3) beside Symbio™ 800 using the 3 poles connector which provide in energy meter kits.
Figure 36. Distribution terminal
Figure 37. Modbus wiring, ref. 50712738
OPTIONAL
ENERGY METER
LINE 52
OPTIONAL
4Y1
WI-FI
ANTENNA
OPTIONAL
RED
BLK
BLU
IMC
A
1A22 SYMBIO800 UNIT CON
1X3-2
1X3-3
+
-
P1
BACKNET
1X3-1
+
-
G
MODBUS
GRN
-
P2
WHT
480 Volts and Lower Installations
POTENTIAL INPUT – Install provided fused inputs to line voltage per schematic.
CURRENT INPUT – Install provided Rogowski CTs per
ematic.
sch
Figure 38. Rogowski CTs
BLK
+
CVRF-SVN005C-EN 29
Page 30
Installation
2T50
2T51
2T52
LINE 99
TO 1X3
WHT
BLK
WHT
BLK
WH
T
BLK
RED
BLK
BLU
YEL
ORG
BRN
WHT
2F54
2F52
2F53
0.5A
0.5A
0.5A
DETAIL A
ENERGY METER OPTION
NOT US
ED
WB22
X1 X2 X1 X2 X1 X2 +-G
MODBUS
VOLT INPUTS
L1 L2 L3 N
2F1 LINE SIDE
2F2 LINE SIDE
2F3 LINE SIDE
2P25
ENERGY METER
(E23)
CT INPUTS
L1 L2 L3
T
T
T
T
T
T
T
T
T
Figure 39. Energy meter wiring, 480V and low application, ref. 50712756
30 CVRF-SVN005C-EN
Page 31
Installation
OIL PUMP MOTOR
1X1-6
LINE 143
TO 1X2-8
12C
1X1-14
21C
2M
23B
24B
123
124
23A
24A
22A
(6-1/4 A)
(6-1/4 A)
LT
RT
1K8
2
3
2
1
1X1-15
1X1-16
1F9
1F8
LT RT
1C1
34
1K8
Oil Pump Control
The Symbio™ control panel allows control UCP2:
Line voltage oil pumps directly with th
e LLID relay output
120 Vac non refrigerant pump oil pumps using a standard
city relay and capacitor
capa
120 Vac refrigerant pump style oil pumps using a high
city relay and capacitor
capa
120 Vac Components Matrix
120 Vac
oil pump
Non-refrigerant pump RLY03888 CPT01766
Refrigerant pump RLY03555 CPT01767
Figure 41. Line voltage oil pump wiring, ref 50712732
Starter
relay
Starter
capacitor Fuses
FUS01510 (6 ¼ Amp)
FUS00938 (15 Amp)
120 Vac Oil Pump Starter Capacitor and Starter Relay (Left)
Figure 40. Oil pump starter capacitor and starter relay
Line Voltage Pump Installation
1. Remove start relay, start capacitor and related wiring from Symbio™ panel and discard. These items will not be used in this application.
2. Wire oil pump contactor coil between terminals 1X1-14 and 1X1-6 as per schematic.
12C
1X1-14
120 Vac Non Refrigerant Pump Style Oil Pump Installation
1. Remove start capacitor from oil pump motor junction box and discard. This item will not be used in this application.
Figure 42. Non-refrigerant oil pump wiring, ref. 50712737
TO 1X2-8 LINE 143
OIL PUMP MOTOR
1X1-6
2. Install new wire of same gauge as existing from control panel to oil pump.
3. Wire oil pump terminal box from terminals 1X1-15, 1X1-16 and 1X1-6 per schematic.
CVRF-SVN005C-EN 31
Page 32
Installation
120 Vac Refrigerant Pump Style Oil Pump Installation
1. Remove start capacitor from oil pump motor junction box and discard. This will not be used in this application.
2. Install new wire of same gauge as existing from control
el to oil pump.
pan
Figure 43. Refrigerant oil pu
mp wiring, ref. 50712738
Installation of Oil Pump Motor Wiring and Terminals
The CVRF installation will relocate the oil pump relay to the control panel. Follow the below steps for installation.
1. Disconnect conduit from terminal box and disconnect Seal-Tite® fitting from conduit.
2. Use fish tape to thread wire through conduit for the new
y location in the control panel.
rela
3. Remove starter relay star the Symbio™ panel and discard. Replace these items with the larger capacity relay, capacitor and fuse provided with the kit.
4. Wire oil pump terminal box from terminals 1X1-15, 1X1-16
nd 1X1-6 per schematic.
a
t capacitor and oil pump fuse from
5. Attach Term-Lok adapters (KIT07955 included with kit)) and wire per schematic.
3. Remove and discard existing relay from oil pump junction box.
4. Remove the backing to expose the adhesive on the insulator (GKT04571 included with kit), and then install the insulator over the Fusite pins.
32 CVRF-SVN005C-EN
Page 33
Starter Work
WARNING
Electrical Fault!
Failure to follow instructions below could result in death or serious injury from burns or electric shocks. Tracer® AdaptiView™ wye-delta starter timing is different from UCP2 wye-delta starter timing. Symbio™800 uses contactor auxiliary switches to prevent simultaneous closure of run and shorting contactors. Starter wiring changes MUST be made per drawings listed in pr
event an electric fault condition.
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified pe
rsonnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
Important: Symb
Starter Control Planning
Electrical Fault!
Failure to follow instructions below could result in severe injury and equipment damage. Tracer® Adaptiview™ requires the use of contactor auxiliary switches to prevent simultaneous closure of run and shorting contactors. Existing mechanical interlocks will wear out and fail if not used in combination with contactor auxiliary and result in the contactors exploding. Starter wiring documented in
Diagram Matrix,” p. 46
electrical fault condition.
The starter work required varies significantly from one application to the next. These instructions are somewhat generic. Detailed plans have to be worked out using these instructions as a guide along with your specific starter wiring and hardware information. Use the existing starter wiring and the Symbio™ ship with starter wiring diagrams for determining your exact wiring.
The 3-phase starter module can control the starter using one
methods:
of two
– Direct control of each starter contactor
“Wiring Diagram Matrix,” p. 46 to
WARNING
io™800 requires a closed transition starter. If the existing starter is an open transition style, it must be replaced.
WARNING
, MUST be made to
“Wiring
prevent an
– Pilot relay interface to the existing contactors
Both methods result in similar operation of the starter. When
module is wired for direct control all functions of the dry run
the test can be performed. The pilot relay method must be used when the contactor coils are voltages other than 115 Vac. If both direct control or pilot relay control can be used on your application, select the method that best suits your needs.
The wiring diagrams for direct control are referenced in
Diagram Matrix,” p. 46 p. 46
for pilot relay diagrams, sometimes referred to as
stomer supplied starter wiring. Pilot relays are field provided.
cu
Retain any special options and determin into the new method of control. Keep a detailed record of your revisions to help with future troubleshooting.
Starter panel conversion varies starter control voltage. For reference,
p. 46
lists the electrical schematics for typical Symbio™ wiring for wye-delta, across-the-line, primary reactor, auto transformer, and solid-state starters.
Important: T
The instructions that follow detail the rework of delta starter for direct control by Symbio™ and the starter module LLID.
While this conversion procedure specifically applies to wye-
elta starters, it can be adapted to successfully modify other
d types of starters for operation with a Symbio™ starter module.
. Also use “Wiring Diagram Matrix,”
e how they might fit
with existing starter type and
“Wiring Diagram Matrix,”
o ensure that the starter panel retrofit procedure is performed properly, carefully review the instructions in this section. Record a detailed description of all electrical changes made during the starter retrofit process. Be sure to add a copy of this report to the chiller record file for future reference.
“Wiring
a typical wye-
Starter Sub-Box Installation
The starter sub-box is intended for remote mount starter installations where due to their custom nature there isn’t room for mounting the sub-panel in the starter enclosure and/or such an installation inside the enclosure would be inconvenient or un-safe.
As the Symbio™ starter sub-panel provides a direct
lacement for a UCP2 starter module it is expected that the
rep sub-box will be rarely required, however a description of its installation is provided in case it is needed.
1. Installing the Starter Panel sub-box
2. Mounting of the optional starter sub-box:
a. Remove door from box. Door can be hinged on either
of cabinet.
side
b. Mount starter sub-box on starter panel as shown in
Figure 45, p. 35 using hardware provided. When
drilling holes in starter cabinet, take care to avoid getting metal shavings into starter cabinet.
CVRF-SVN005C-EN 33
Page 34
Starter Work
c. Drill 3/4-inch or 1-inch hole through panel and starter
cabinet, near top of cabinet, to accommodate wires from sub-box to starter. Add grommet to hole.
3. Mounting and pre-wiring of components on back panel.
a. Mount starter sub-panel on the back panel.
b. Label components using labels provided.
c. Attach starter module LLID to IPC bus.
Figure 44. Starter sub-panel with PTs, CTs and power
pply
su
Starter Sub-Panel
The Symbio™ starter module is provided on an assembled sub-panel that is a direct replacement for the UCP2 starter module mounted in conventional starters and AFD applications. The sub panel has three significant options:
– It has the option of a 24 Vdc power supply to be used
remote mount starters and drives.
on
– It has the option of pre-installe
transformers
– It comes in a starter and AFD configuration. The AFD
configuration includes the needed LLIDS for UCP2 AFD control.
Each subpanel It is also provided as standard with a mounting
racket that allows mounting of factory installed AFD LLIDs or
b field installed secondary current transformers or pilot relays when needed.
A description of the sub-panel’s types and uses is below:
d 600 V or less current
Table 8. Sub-panel types
Model # Digit 33 Application Part Number Description
Starter module with plate for
E
medium voltage unit starter
Starter module with plate for low
A
F
B
C
D
age unit starter
volt
Starter module with plate for
dium voltage remote starter
me
Starter module with plate for low voltage remote starter
Starter module with plate for unit AFD
Starter module with plate for re
mote AFD
0185-0421-0100
0185-0433-0100
0185-0422-0100
0185-0435-0100
0185-0434-0100
0185-0437-0100
Starter module on sub plate W/O power supplier, W/O PT
Starter module on sub plate W/O power supplier, W/ PT
Starter module on sub plate W/ power supplier, W/O PT
Starter module on sub plate W/ power supplier, W/ PT
AFD Starter module on sub plate W/O power supplier, W/O PT
AFD Starter module on sub plate W/ power supplier, W/O PT
Starter
Mount Type
Unit mount MV starter
Unit mount LV Starter
Remote mount
Remote mount
Unit mount
Remote mount
PTs
Configuration Selection FACT/FCOD
MV starter
LV Starter
AFD starter already has LV PTs
AFD starter already has LV PTs
STYP/STUN; TPOT=NONE
STYP/STUN; TPOT=CPTA,CPTB,CPTC, CPTD,CPTE,CPTF
STYP/STRE; TPOT=NONE
STYP/STRE; TPOT=CPTA,CPTB,CPTC, CPTD,CPTE,CPTF
STYP/AFUN; TPOT=NONE,CPTB,CPTC
,CPTD,CPTE,CPTF
STYP/AFRE; TPOT=NONE,CPTB,CPTC ,CPTD,CPTE,CPTF
34 CVRF-SVN005C-EN
Page 35
Starter Work
Figure 45. Mounting starter sub-box
Starter control and power wires are connected to the terminal block on the right side of the sub-panel. CTs and starter module communications and power wires are connected directly to starter module on the left side.
Figure 46. Starter sub-panel
Figure 47. Low voltage potential transformer
connections
IMPORTANT NOTE FOR WYE DELTA AND AUTO TRANSFORMER STARTER APPLICATIONS
Per the schematics, Wye Delta and Auto Transformer starter require normally closed contactor interlock signals for proper operation. In the case that the starters do not have available auxiliary contacts, pilot relays can be substituted per the schematic notes below. If space is available, the relay(s) can be mounted on the sub-panel bracket.
Medium voltage potential transformer outputs are directly wired to starter module current inputs L1, L2, and L3 per the schematic drawing. Low voltage L1, L2, and L3 potential signals are connected to the potential transformer white and black leads on the sub-panel in the order below.
Note: If repla
cing a UCP2 starter module, you can remove and discard the 27 VAC UCP2 starter module transformer as it is not required for the CH530 type starter module operation.
Figure 48. Pilot relay terminal locations
CVRF-SVN005C-EN 35
Page 36
Starter Work
Figure 49. Pilot relay switching configuration
Figure 50. Wye delta interlock and pilot relay wiring
36 CVRF-SVN005C-EN
Page 37
Figure 51. Autotransformer interlock and pilot relay wiring
Starter Work
Starter Sub-Panel Installation
Virtually all Symbio™ UCP2 panel upgrades will have the starter sub panel installed as a direct replacement of the existing UCP2 starter module.
The starter module LLID, and CTs and any turn-down
nsformers can be mounted on the sub- panel.
tra
The starter control conversion will provide a direct replacement
existing UCP2 starter module. For UCP2 installations it
of the is recommended that the existing CTs and PTs will be reused and mounted on the Symbio™ starter sub-panel.
Installation steps are as follows:
1. Remove existing UCP2 module keeping potential nsformers and secondary current transformers if
tra needed for reuse.
CVRF-SVN005C-EN 37
2. Install existing potential transformers on lower panel if required and secondary current transformers if needed on the bracket.
3. Power and communications.
a. For unit mount starters, use global connector to provide
wer and communications to starter module.
po
b. For remote mount starters
i. Starter module power will be supplied by sub-panel
ower supply.
p
ii. Use existing communications cable to connect
mbio™ communications bus to starter module.
Sy
4. Wire Starter control interface per schematic. Remove the
xisting UCP2 wires between terminal 2TB1-6 and UCP2
e starter module J10-3, J12-3, and J14-3. See UCP2 existing starter module schematic drawing below of existing UCP2 wires to be discarded.
Page 38
Starter Work
Figure 52. Existing UCP2 wires to be discarded
Figure 53. Starter sub panel customer connections 5071-0496
Notes:
Be sure to refer to the wiring diagrams listed in
Diagram Matrix,” p. 46
as you review the following
“Wiring
instructions. The wire numbers and component
designations indicated in these steps appear in these figures. Actual existing numbers may vary for your unit. Service literature that includes sample original unit wiring can be found in CVHE-M-7 or CVHE-IN-8.
38 CVRF-SVN005C-EN
Page 39
Starter Work
To simplify future chiller trouble analysis, Trane recommends removing all existing, non-essential components from the starter panel enclosure.
AFD Sub-Panel
The Symbio™ starter module is provided on an assembled sub-panel that is a direct replacement for a UCP2 starter module mounted on an AFD. The panel contains the analog output, binary input and timer required to run the AFD as a non­communicating Symbio™ drive.
Installation steps are as follows:
1. Remove existing UCP2 module keeping medium voltage
AFD potential transformers and CTs for reuse.
and
2. Install new sub-panel in place of existing UCP2 starter
e and existing potential transformers on the bracket.
modul
3. Wire AFD control interface per schematic.
Figure 54. AFD sub panel customer connections 5071-1536
4. Power and communications.
a. For unit mount AFDs
i. Wire per schematic
ii. Use global connector to provide power and
nications to starter module.
commu
b. For remote mount AFDs
i. Wire per schematic, starter module will be powered
b-panel power supply.
by su
ii. Use existing communications cable to connect
mbio™ communications bus to starter module.
Sy
5. Shunt trip output (Optional) ­shunt trip function is not documented by the Symbio™ AFD schematic. It is not used on UCP2 AFDH and is not required for a Symbio™ upgrade.
The UCP2 starter module
If keeping shunt trip control is desired, a Symbio™ programmable binary output can be setup to transition upon starter fault. Wire the output normally open contact with 115 Vac to the AFD circuit breaker in order to initiate shunt trip.
Notes:
Be sure to
Diagram Matrix,” p. 46 as you review the following
CVRF-SVN005C-EN 39
refer to the wiring diagrams listed in
“Wiring
instructions. The wire numbers and component designations indicated in these steps appear in these figures. Actual existing numbers may vary for your unit. Service literature that includes sample original unit wiring can be found in CVHE-M-7 or CVHE-IN-8.
Page 40
Starter Work
To simplify future chiller trouble analysis, Trane recommends removing all existing, non-essential components from the starter panel enclosure.
Control Power Transformer
If the existing starter does not have 115 Vac 3 kVA of additional control power, install a transformer (fieldsupplied) that will provide 115 Vac to the Symbio™ control panel. (As just described, transformer requirements are: line voltage primary/ 115 Vac secondary, minimum capacity 3 kVA.)
Current Transformers, CTs
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
Three new current transformers CTs (“donut” shape) are optio
nal to re-work the starter. If used, install these three new
CTs as shown on wiring diagram. Pay careful attention to the
Table 9. CT specifications for single transformer per phase
polarity dot and its orientation. The polarity dot should face incoming power, in other words, towards the disconnect.
Figure 55. Current transformer, single turn-down
DIM “B”
DIM “A”
Schematic
Polarity Dot
1/4 in. male quick connect 2 places
Wire the leads from the CT male quick connects to the starter
ule as shown on the wiring diagram. Use female insulated
mod quick connect terminals.
The application of Symbio™ chiller controls to a medium voltage chiller recommends specific use of the dual current transformer (CT) application, rather than a single CT which is a common option on low voltage applications (600 Vac or less). Refer to CVRD-SVN11*-EN for wiring of medium voltage CT applications.
The dual CT installation uses a primary CT
that reduces the amperage to less than 5 amps. A second CT is then used to reduce the current input to the starter module to a nominal 100 mA value. Use dual CT data tables in the startup and programming manual CVRE-SVP01A-EN, or the latest version.
It is recommended that you confirm the correct CT has been
rovided before starting installation. Before wiring the starter
p module and CT be sure to confirm incoming power phasing. If Phase A, B, and C are wired in the wrong order the controls will not allow the motor to start. Use the phase meter on the low voltage side of the potential transformer. Do NOT use the meter on the primary side where there is medium voltage because it probably exceeds the safe operating voltage range of most service meters.
Actual Motor
RLA (A) CT Part Number CT Ratio (A:A) CT Rating (A)
67-100 TRR02028 40:00.1 100 2 3.35 1 100
100-150 TRR00715 30:00.1 150 2 3.35 1 150
134-200 TRR02029 20:00.1 200 2 3.35 1 200
184-275 TRR02030 35:00.1 275 2 3.35 1 275
267-400 TRR02031 40:00.1 400 2.5 3.95 1 400
334-500 TRR01142 20:00.1 500 2.5 3.95 1 500
467-700 TRR01255 40:00.1 700 2.5 3.95 1 700
40 CVRF-SVN005C-EN
Diameter
(a)
(inches)
Primary
Tur ns
CT Meter
ScaleInside A Inside B
Page 41
Table 9. CT specifications for single transformer per phase (continued)
Starter Work
Actual Motor
RLA (A) CT Part Number CT Ratio (A:A) CT Rating (A)
667-1000 TRR01405 40:00.1 1000 2.5 3.95 1 1000
964-1400 TRR01597 20:00.1 1400 3.5 5.25 1 1400
1200-1800 TRR01580 00:00.1 1800 4 6.5 1 1800
(a) Refer to
Figure 55, p. 40 for location of diameter A and B.
CT Work
Diameter
The existing CTs can be reused for UCP2. applications with a single CT or two CTs per phase. The output
(a)
(inches)
Primary
Tur ns
This is true for
of both CT applications is in the 100 mA range that the
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
Symbio™ starter module requires.
When reusing CTs it may be necessary to confirm all the
olarity of existing wiring is correct per these instructions.
p
In some cases starters shipped with ammeters. can remain if they have their own CTs.
When using existing CTs having a nominal chiller current to 5
mp ratio (i.e., 200:5), it is necessary to install or have ordered
a secondary CTs. In this case, two CTs are used per phase to either achieve the necessary turn-down or for metering convenience. The first stage consists of either the X13580271010 (TRR01287), X13580272010 (TRR01288), X13580048010 (TRR00448) and X13580048020 (TRR00449) (each of these CTs have a 5 amp secondary). The second stage consists of small CT transformers that reduce the nominal 3.6 amp signal to the 100 mA value used by the starter
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is
module. The existing 5 amp CTs cannot be used if they do not match the required ratio in
Table 9, p. 40.
The part number on the secondary CT is X13580266-01, Trane
art number TRR00975, three required per starter.
p
cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
Table 10. CT specifications for two transformers per phase
CT Meter
ScaleInside A Inside B
The meters
Actual Motor
RLA (A)
8.0-12.0 TRR01288 TRR00975 50:05:00 50 1.25 3 12
12.0-18.0 TRR01288 TRR00975 50:05:00 50 1.25 2 18
18.0-27.0 TRR01289 TRR00975 75:05:00 75 1.25 2 27
24.0-36.0 TRR01288 TRR00975 50:05:00 50 1.25 1 36
36.0-54.0 TRR01289 TRR00975 75:05:00 75 1.25 1 54
48.0-72.0 TRR01287 TRR00975 100:05:00 100 1.75 1 72
24.0-36.0 TRR00448 TRR00975 150:05:00 150 2.5 3 36
28.8-43.2 TRR00448 TRR00975 180:05:00 180 2.5 3 43.2
36.0-54.0 TRR00448 TRR00975 150:05:00 150 2.5 2 54
43.2-64.8 TRR00448 TRR00975 180:05:00 180 2.5 2 64.8
48.0-72.0 TRR00448 TRR00975 200:05:00 200 2.5 2 72
60.0-90.0 TRR00449 TRR00975 250:05:00 250 2.5 2 90
CVRF-SVN005C-EN 41
Primary CT
Number
Second CT
Number CT Ratio (A:A) CT Rating (A)
Inside Dia.
(inches) Primary Turns CT Meter Scale
Page 42
Starter Work
Front View / Primary
RED BRN
Front View / Secondary
BLK WHT
Bottom View
BLKWHT
RED BRN
Primary Leads
Secondary Leads
Schematic
RED
BROWN
BLACK
WHITE
Primary
Secondary
Table 10. CT specifications for two transformers per phase (continued)
Actual Motor
RLA (A)
72.0-108.0 TRR00448 TRR00975 150:05:00 150 2.5 1 108
86.4-129.6 TRR00448 TRR00975 180:05:00 180 2.5 1 129.6
96.0-144.0 TRR00448 TRR00975 200:05:00 200 2.5 1 144
120-180 TRR00449 TRR00975 250:05:00 250 2.5 1 180
144-216 TRR00449 TRR00975 300:05:00 300 2.5 1 216
168-252 TRR00449 TRR00975 350:05:00 350 2.5 1 252
192-288 TRR00450 TRR00975 400:05:00 400 2.5 1 288
240-360 TRR00450 TRR00975 500:05:00 500 2.5 1 360
288-432 TRR00450 TRR00975 600:05:00 600 2.5 1 432
336-504 TRR00451 TRR00975 700:05:00 700 2.5 1 504
384-576 TRR00451 TRR00975 800:05:00 800 2.5 1 576
480-720 TRR00451 TRR00975 1000:05:00 1000 2.5 1 720
480-720 TRR00655 TRR00975 1000:05:00 1000 4 1 720
576-864 TRR00499 TRR00975 1200:05:00 1200 2.5 1 864
576-864 TRR00655 TRR00975 1200:05:00 1200 4 1 864
720-1080
720-1080 TRR00655 TRR00975 1500:05:00 1500 4 1 1080
864-1296 TRR00453 TRR00975 1800:5, X1-X2 1800 4 1 126
1008-1512 TRR00453 TRR00975 2100:5, X1-X3 2100 4 1 1512
1200-1800 TRR00453 TRR00975 2500:5, X1-X4 2500 4 1 1800
Primary CT
Number
TRR00499 TRR00975 1500:05:00 1500 2.5 1 1080
Second CT
Number CT Ratio (A:A) CT Rating (A)
Inside Dia.
(inches) Primary Turns CT Meter Scale
The secondary CT used in the two transformer per phase is shown in
Figure 56, p. 42. For a typical wiring diagram used for
wiring low voltage applications using dual CTs, two transformers per phase, see
Figure 57, p. 43.
Figure 56. Secondary CT used with 5 amp primary CT, X13580266-01, TRR00975
42 CVRF-SVN005C-EN
Page 43
Figure 57. Dual CT wiring example
Starter Work
CVRF-SVN005C-EN 43
Page 44
Starter Work
Schematic
Secondary Leads, 0.187 in. terminals
Top View
Primary Leads, 0.250 in. terminals
Polarity Dots
Secondary
Primary
Polarity Dots
Potential Transformers, Optional PTs
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
Figure 58. Potential transformer, X13590079-01, TRR00713
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
Install the optional potential transformers (PTs). The potential transformers are used to measure line voltage. The wiring must have the correct polarity for them to work correctly.
For applications greater than 600 Vac, a large medium voltage
is used to step from line voltage to 115 Vac and a second
PT PT steps the voltage to less than 30 Vac. The large PT is a three phase type except for the 6600 Vac where three single phase PTs are used. Refer to CVRD-SVN11*-EN, for detailed wiring instructions.
For applications less than 600 Vac a single PT per phase like
at shown in
th to a voltage less than 30 Vac for input into the starter module. The black leads are connected to the line from phases A-B, B­C and C-A. The green ground wire is connected to chassis ground. Field provided wires connect the Starter module to the terminals on the PTs.
The part number on the less than 600 volt PT is X13590079-
Trane part number TRR00713, three required per starter.
01,
Note: Fu
44 CVRF-SVN005C-EN
Figure 58, p. 44 is used to step the signal down
ses (2F1, 2F2 and 2F3) must be installed with the
optional potential transformers (see
“Wiring Diagram
Matrix,” p. 46 for a list of the appropriate wiring diagram
examples). Use
Ta bl e 5, p. 9 to size the fuses.
Starter Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
Page 45
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
WARNING
PPE for Arc/Flash Required!
Failure to wear appropriate PPE could result in death or serious injury. On this unit, if the handle shield is cracked the circuit breaker could arc/flash when reset. To avoid being injured, technicians MUST put on all necessary Personal Protective Equipment (PPE), in accordance with NFPA70E for arc/flash protection, PRIOR to entering the starter panel cabinet.
NOTICE
Module Damage!
Failure to follow the following instruction could result in equipment damage. Do NOT connect the secondaries of the line-to-120 Vac potential transformer to the starter module!
Starter Work
Table 11. Starter wiring (continued)
Wi r e # F r om Te r mina l To Te rmin a l
507 2U1 J8-2 2K11 coil +
510 2U1 J8-1 2A1 J8-1
512 2U1 J10-3 2A1 J6-3
516 2U1 J10-1 2K3 AUX NC
518 2U1 J12-3 2A1 J4-3
521 2U1 J12-1 2K4 AUX NC
523 2U1 J14-3 2A1 J2-3
524 2U1 J14-1 2A1 J2-1
Additional wires
Wire # From Terminal To Te r min a l
508 2K11 coil - 2TB1-2
506 2K11 NO 2K1 AUX NO
505 2A1 J10-1 2K11 NO
514 2A1 J6-1 2K11 NO
515 2K11 NO 2K3 AUX NC
519 2A1 J4-1 2K4 AUX NC
IPC cable connected to either J1 or J3 1-4.
Remove
2T4 and all wires connected to it.
Comm Link wires connected to 2U1 J1-1,2.
Table 11. Starter wiring
Wire # From Terminal To Ter m inal
236A 2U1 J3-3 2A1 J5-1
237A 2U1 J3-4 2A1 J5-2
238A 2U1 J3-5 2A1 J5-3
239A 2U1 J3-6 2A1 J5-4
240A 2U1 J3-7 2A1 J5-5
241A 2U1 J3-8 2A1 J5-6
101A 2U1 J5-1 2A1 J7-1
102A 2U1 J5-2 2A1 J7-2
103A 2U1 J5-3 2A1 J7-3
104A 2U1 J5-4 2A1 J7-4
105A 2U1 J5-5 2A1 J7-5
106A 2U1 J5-6 2A1 J7-6
503 2U1 J4-2 2A1 J12-2
504 2U1 J4-1 2A1 J12-1
4B 2U1 J6-3 2A1 J10-3
CVRF-SVN005C-EN 45
Page 46
Wiring Diagram Matrix
Table 12. Wiring diagrams matrix
TYPE NUMBER
CONTROL
Unit Controls 50712738
Unit and Option 50712745
Option 50712746
Option 50712747
Legend 50712748
Field Connection Dia 50712755
Comm Panel Dia 50712779
STARTERS
Wye-Delta TS 50710492
X-Line TS 50710493
Primary Reactor TS 50710494
Auto X-Former TS 50710495
Solid State TS 50710528
Wye-Delta CS 50710523
X-Line CS 50710524
Primary Reactor CS 50710525
Auto X-Former CS 50710527
Starter Subpanel VFD 50711536
Energy Meter Option, 480V and Low 50712756
Energy Meter Option, 575 and 600V 50712757
Energy Meter Option, MV With Single
Energy Meter Option, MV With Double
Note: Wiring diagrams, including those for chillers equipped with drives, are
age PT
St
St
age PT
available via e-Library. Also refer to the drive Installation, Operation, and Maintenance manual for the appropriate diagrams. If the existing chiller has an AFDB or AFDC drive, contact Trane Global Parts Technical Service for specific instructions.
50712758
50712759
46 CVRF-SVN005C-EN
Page 47
Notes
CVRF-SVN005C-EN 47
Page 48
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
CVRF-SVN005C-EN 05 Aug 2022
Supersedes CVRF-SVN005B-EN (May 2022)
©2022 Trane
Loading...