Trane Symbio 800 Integration User guide

Page 1
Integration Guide
®®
Integration to IntelliPak
Rooftop Units (RTU)
With Symbio™ 800 Controls
®®
SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
April 2021
BBAASS--SSVVPP003399CC--EENN
Page 2
Introduction
WARNING
CAU
TION
NOTICE
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall//ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess..
©2021 Trane
BAS-SVP039C-EN
Page 3
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) RReeqquuiirreedd!!
FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd cchheemmiiccaall hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss,, aass wweellll aass tthhee iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,, ssaaffeettyy ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,, eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh ccllootthhiinngg)).. AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee SSaaffeettyy DDaattaa SShheeeettss ((SSDDSS)) aanndd OOSSHHAA gguuiiddeelliinneess ffoorr pprrooppeerr PPPPEE..
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee aapppprroopprriiaattee SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd LLaabbeelllliinngg ooff CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree lleevveellss,, pprrooppeerr rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg iinnssttrruuccttiioonnss..
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA 7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc rreeqquuiirreemmeennttss ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg tthhee uunniitt.. NNEEVVEERR PPEERRFFOORRMM AANNYY SSWWIITTCCHHIINNGG,, DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG WWIITTHHOOUUTT PPRROOPPEERR EELLEECCTTRRIICCAALL PPPPEE AANNDD AARRCC FFLLAASSHH CCLLOOTTHHIINNGG.. EENNSSUURREE EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD EEQQUUIIPPMMEENNTT AARREE PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD VVOOLLTTAAGGEE..
WWAARRNNIINNGG
FFoollllooww EEHHSS PPoolliicciieess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
Copyright
Trademarks
•• AAllll TTrraannee ppeerrssoonnnneell mmuusstt ffoollllooww tthhee ccoommppaannyy’’ss EEnnvviirroonnmmeennttaall,, HHeeaalltthh aanndd SSaaffeettyy ((EEHHSS)) ppoolliicciieess wwhheenn ppeerrffoorrmmiinngg wwoorrkk ssuucchh aass hhoott wwoorrkk,, eelleeccttrriiccaall,, ffaallll pprrootteeccttiioonn,, lloocckkoouutt//ttaaggoouutt,, rreeffrriiggeerraanntt hhaannddlliinngg,, eettcc.. WWhheerree llooccaall rreegguullaattiioonnss aarree mmoorree ssttrriinnggeenntt tthhaann tthheessee ppoolliicciieess,, tthhoossee rreegguullaattiioonnss ssuuppeerrsseeddee tthheessee ppoolliicciieess..
•• NNoonn--TTrraannee ppeerrssoonnnneell sshhoouulldd aallwwaayyss ffoollllooww llooccaall rreegguullaattiioonnss..
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
All trademarks referenced in this document are the trademarks of their respective owners.
BAS-SVP039C-EN
3
Page 4
Table of Contents
Overview . . . . . . .. . . .. . . .. . . . . . . . . . .. . . .. . . . . . . . . . . . . . . . . . .. . . . . . . .. . . .. . . . . . . . . 5
Purpose. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Symbio800700 Controller Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Units of Measure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Communication Setup and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Service Tool for Symbio800 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Connecting to the Symbio800 Web Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Protocol Configuration . . . . . . . . . . . . . . . . . . . . .. . . .. . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . 8
LonTalk Protocol Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Profile Definition and Network Variables. . . . . . . . . . . .. . . .. . . .. . . . . . .. . . .. . . .. . . 10
Arbitration . . . . . . . . . . . . .. . . . . . . . . . . . . . .. . . .. . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A–1
Symbio800 Controller Display . . . . .. . . .. . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B–1
4
BAS-SVP039C-EN
Page 5
Overview
Purpose
The purpose of this document is to provide instructions for integrating the Symbio800700 controller into Non-Trane building automation systems. This document is targeted to system integrators and controls contractors.
Symbio™ 800700 Controller Overview
The Symbio800700 controller has been installed, programmed, wired, commissioned, and tested in the factory prior to shipment. While some sensors and end devices are normally wired in the field, nearly all other wiring is factory-provided. Power for the controller is provided and connected from within the RTU control panel.
The RTUunit and associated controller can be applied as standalone or as part of a building automation system.
NNoottee:: For communicating applications to third-party control systems, network communication
wiring must be provided by others.
Communication Options
The Symbio 800 controller supports the following communication protocol options for integration to either Trane or non-Trane control systems:
BACnet TP
BACnet Air-Fi
BACnet IP
Ethernet
Wi-Fi
Modbus RTU
Modbus TCP
LonTalk
For information pertaining to the integration of the Symbio 800 controller using either Modbus or BACnet communication, refer to the integration guides specific to those applications.
Units of Measure
The communicated LonTalk data of the Symbio700 controller will be passed in the factory­configured units of measure, inch-pound (I-P) by default. The Symbio 700 mobile application allows the user to change and customize the Data Display Units Preferences.
The communicated data of the Symbio™ 800 controller will be passed in the factory-configured units of measure, either inch-pound (I-P) or the International System of Units (SI). The units of measure are selected as part of the unit order (the default selection is normally I-P). Should the units of measure need to be changed in the field, contact your local Trane representative.
The Symbio 800 controller provides a browser-based user interface for USB connection to the controller. One of the tools provided with that interface allows the user to change and customize the Data Display Units Preferences.
IImmppoorrttaanntt:: These adjustable settings are applied only to the units of measured displayed in the
Regardless of the communicated (system) units of measure, the user may change the displayed units of measure on their smart device. These user preference units of measure are independent of the communicated units.
BAS-SVP039C-EN
web interface, not the communicated interface.
5
Page 6
OOvveerrvviieeww
Communication Setup and Configuration
The Symbio800 controller can be factory ordered with a specific protocol configuration and rotary address setting. If communication options were not specified, the Symbio800 controller will be setup for BACnet TP communications at 76,800 bps with a rotary address setting of 000.
Figure 1. Symbio™™ 800 rotary address and service tool port
Service Tool for Symbio™ 800 Configuration
The service tool used to modify the Symbio800 controller is a standard web browser. The Symbio800 webpage is accessed by using a standard USB type A/B cable. Connect the USB cable between a laptop and the service tool port on the Symbio800 controller (shown in
).
1, p. 6
Figure
Connecting to the Symbio™ 800 Web Interface
1. Connect a laptop to the Symbio800 controller using a USB cable.
2. On the laptop, open a web browser to
3. When the Symbio800 page displays, click LLoogg IInn.
Figure 2. Symbio™™ 800 log in screen
http://198.80.18.1/
6
BAS-SVP039C-EN
Page 7
OOvveerrvviieeww
NNoottee:: The Symbio
800 web interface can only be viewed using the USB connection. Ethernet port 1 and Ethernet port 2 will not allow access to the Symbio security requirements.
web server to meet IT
BAS-SVP039C-EN
7
Page 8
Protocol Configuration
To access the Symbio 800 Protocol Configuration page:
1. Connect to the Symbio 800 web interface.
2. On the left-hand navigation, click IInnssttaallllaattiioonn.
3. Click IIddeennttiiffiiccaattiioonn aanndd CCoommmmuunniiccaattiioonnss.
Figure 3. Identification and Communications
4. Click the PPrroottooccooll CCoonnffiigguurraattiioonn tab.
Figure 4. Protocol Configuration
5. View the existing Protocol Configuration settings.
NNoottee:: There are no LonTalk communication parameters to edit.
LonTalk Protocol Settings
The Symbio 800 controller supports LonTalk communications with the optional LonTalk module. The LonTalk module is din rail mounted and is connected to the Symbio 800 controller using USB.
NNoottee:: The Symbio 800 rotary addresses are not used with LonTalk communications.
8
BAS-SVP039C-EN
Page 9
PPrroottooccooll CCoonnffiigguurraattiioonn
Figure 5. LonTalk protocol configuration
1. Verify the LonTalk adapter connection status is CCoonnnneecctteedd. If the adapter connection status is another state, verify the LonTalk adapter is connected to a Symbio 800 USB port.
2. Verify the Link Status is OOnnlliinnee. If the Link Status is set to a different state, LonTalk network management software such as Trane’s Rover software is needed to set the Link status to Online.
3. The Service Pin button will send a service pin message to the LonTalk network. A service pin will broadcast the Neuron ID to the LonTalk network so a LonTalk network management tool can find a device and set its Domain, Subnet, Node address.
LonTalk communication wire is connected to the LonTalk adapter. LonTalk does not require wire polarity but it is recommended that wire polarity be observed. Refer to the LonTalk standard for detailed information on LonTalk wiring.
All LonTalk devices must have a unique DSN address and must have the same Domain value. The Symbio 800 LonTalk adapter ships on the zero-length domain so it can be easily discovered by LonTalk network managers and tools.
BAS-SVP039C-EN
9
Page 10
Profile Definition and Network Variables
The following tables are sorted as follows:
Tables are listed by unit/profile type and sorted by network variable number.
Tables are sorted by name and provide a complete list of names, types, values/ranges, and descriptions.
NNoottee:: Not all points are available to the user. The available data points are defined during
self-configuration and are dependent on the type of equipment.
Table 1. SCC Network Variable Inputs
NV# Name RecvHrtBt SNVT
37
38 nviAuxHeatEnable
39
40
41
42 nviCWFlow
43 nviDAClSP
44 nviDAHtSP
45 nviDAReheatSP
46 nviDehumEnable
47 nviEconEnable
48
49 nviHumEnable
50 nviOAMinPos
51 nviOccManCmd
52 nviOccSchedule
53 nviOccSensor
54 nviOutdoorRH
55
nviApplicMode
nviBldgStaticSP SNVT_press_p Building Static Pressure Setpoint
nviBldgStatPress
nviComprEnable
nviEmergOverride SNVT_hvac_emerg Emergency Override BAS
nviOutdoorTemp
SNVT_hvac_mode
SNVT_switch
SNVT_press_p Building Static Pressure
SNVT_switch
SNVT_switch
SNVT_temp_p Discharge Air Cooling Setpoint BAS
SNVT_temp_p Discharge Air Heating Setpoint BAS
SNVT_temp_p Discharge Air Reheat Setpoint BAS
UNVT_switch_binary Dehumidification System Enable BAS
UNVT_switch_multistate
UNVT_switch_binary
SNVT_lev_percent
SNVT_lev_percent Occupancy Request
SNVT_lev_percent Occupancy Request
SNVT_occupancy Occupancy Input BAS
SNVT_lev_percent Outdoor Air Relative Humidity BAS
SNVT_temp_p Outdoor Air Temperature BAS
Description
Heat Cool Mode Request
Heat Auxiliary Enable
Compressor Cooling Enable BAS
Condenser Water Flow BAS
Economizer Enable BAS
Humidification Enable BAS
Economizer Minimum Position
Setpoint
10
BAS-SVP039C-EN
Page 11
Table 1. SCC Network Variable Inputs (continued)
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
NV# Name RecvHrtBt SNVT
nviRTUConfig SNVT_state Rooftop Configuration
nviRTUConfig.0 (MSB) Bit 0
nviRTUConfig.1
nviRTUConfig.2
nviRTUConfig.3
nviRTUConfig.4
nviRTUConfig.5
nviRTUConfig.6
nviRTUConfig.7
nviRTUConfig.8
56
57
58
59
60
61
62
63
64
65
66 nviTraneVar2
nviRTUConfig.9
nviRTUConfig.10
nviRTUConfig.11
nviRTUConfig.12
nviRTUConfig.13
nviRTUConfig.14
nviRTUConfig.15 (LSB) Bit 15
nviRequest SNVT_obj_request Reset Diagnostic Request
nviSetpoint SNVT_temp_p Space Temperature Setpoint BAS
nviSetptOffset
nviSetptShift
nviSpaceCO2
nviSpaceDehumSP SNVT_lev_percent Space Dehumidification Setpoint BAS
nviSpaceHumSP SNVT_lev_percent Space Humidity Setpoint BAS
nviSpaceRH
nviSpaceTemp
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6 PreCool Enable Command
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
SNVT_temp_p Space Setpoint Offset BAS
SNVT_temp_setpt Space Setpoint Shift BAS
SNVT_ppm Space CO2 Concentration BAS
SNVT_lev_percent Space Relative Humidity BAS
SNVT_temp_p Space Temperature BAS
UNVT_c5c
Description
Reserved
Cooling Lockout
Heating Lockout
Demand Limit Request BAS
Energy Consumption Reset
Supply Fan Compensation
Morning Warmup Enable Command
Supply Air Tempering Request BAS
Daytime Warmup Enable Command
Timed Override Request (with Bit 11)
Timed Override Request
00 Idle
01 On
10 Cancel
11 Invalid
Reserved
Manufacturer-defined
Table 2. SCC Network Variable Outputs
NV# Name SendHrtBt SNVT
67
68
69
70
nvoAlarmMessage
nvoBldgStatPress
nvoCondCap
nvoCoolPrimary
BAS-SVP039C-EN
SNVT_str_asc
SNVT_press_p Space Static Pressure Active
SNVT_lev_percent Condenser Capacity
UNVT_switch_binary Cooling Capacity Status
Description
Diagnostic Last Message
11
Page 12
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 2. SCC Network Variable Outputs (continued)
NV# Name SendHrtBt SNVT
nvoCprsrsRunning
nvoCprsrsRunning.0 (MSB) Bit 0 Validity of bit 8
nvoCprsrsRunning.1
nvoCprsrsRunning.2
nvoCprsrsRunning.3
nvoCprsrsRunning.4
nvoCprsrsRunning.5
nvoCprsrsRunning.6
71
72 nvoCWFlow
73
74
75 nvoDAReheatSP
76 nvoDehumidifier
77
78
79
80
81
82 nvoERFrostAvoid
83
84
85 nvoERPreheat
86 nvoERStatus
87
88 nvoExhFanOnOff
89 nvoExhFanStatus
90
nvoCprsrsRunning.7
nvoCprsrsRunning.8
nvoCprsrsRunning.9
nvoCprsrsRunning.10
nvoCprsrsRunning.11
nvoCprsrsRunning.12
nvoCprsrsRunning.13
nvoCprsrsRunning.14
nvoCprsrsRunning.15 (LSB) Bit 15 Compressor 2D Status
nvoCWPump
nvoCWTemp
nvoDischAirTemp
nvoEffectOccup
nvoEffectSetpt
nvoEffSpaceHumSP
nvoEREABPDamper
nvoERLvgExhTemp
nvoEROABPDamper
nvoExhDamper
nvoFanSpeed
SNVT_state
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
SNVT_switch
SNVT_switch
SNVT_temp_p Condenser Water Temperature
SNVT_temp_p Discharge Air Reheat Setpoint Active
SNVT_switch
SNVT_temp_p Discharge Air Temperature
SNVT_occupancy Occupancy Status
SNVT_temp_p Space Temperature Setpoint Active
SNVT_lev_percent Space Humidity Active
SNVT_lev_percent
SNVT_switch
SNVT_temp_p
SNVT_lev_percent
SNVT_switch
SNVT_switch
SNVT_lev_percent Exhaust Damper Position
SNVT_switch
SNVT_switch
SNVT_switch
Description
Compressor Status
Validity of bit 9
Validity of bit 10
Validity of bit 11
Validity of bit 12
Validity of bit 13
Validity of bit 14
Validity of bit 15
Compressor 1A Status
Compressor 1B Status
Compressor 1C Status
Compressor 1D Status
Compressor 2A Status
Compressor 2B Status
Compressor 2C Status
Condenser Water Flow Status
Condenser Water Pump Status
Dehumidification Control Status
Energy Recovery Exhaust Air Bypass
Energy Recovery Outdoor Air Bypass
Damper Position
Energy Recovery Frost Avoidance
Energy Recovery Leaving Exhaust
Energy Recovery Preheat Status
Exhaust Fan Output Status
Exhaust Fan Speed Status
Status
Temperature Status
Damper Status
Energy Recovery Status
Fan Speed Status
12
BAS-SVP039C-EN
Page 13
Table 2. SCC Network Variable Outputs (continued)
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
NV# Name SendHrtBt SNVT
nvoFDD
nvoFDD.0
nvoFDD.1 Bit 1
nvoFDD.2 Bit 2
nvoFDD.3 Bit 3
nvoFDD.4 Bit 4
nvoFDD.5 Bit 5
nvoFDD.6 Bit 6
91
92 nvoHeatCool
93
94
95 nvoHumidifier
96
97
98
99
100
101 nvoOAFlow
102 nvoOutdoorRH
103
104
105 nvoRetFanOnOff
106 nvoRetFanPress
107 nvoRetFanStatus
nvoFDD.7 Bit 7
nvoFDD.8 Bit 8
nvoFDD.9 Bit 9 Reserved
nvoFDD.10 Bit 10 Reserved
nvoFDD.11 Bit 11 Reserved
nvoFDD.12 Bit 12 Reserved
nvoFDD.13 Bit 13 Reserved
nvoFDD.14 Bit 14 Reserved
nvoFDD.15
nvoHeatPrimary
nvoHeatSecondary
nvoLocalCWTemp
nvoLocalSpaceTmp
nvoMixedAirTemp
nvoOADamper
nvoOAEnthalpy
nvoOutdoorTemp
nvoRATemp
SNVT_state Fault Detection and Diagnostics
(MSB) Bit 0
(LSB) Bit 15
SNVT_hvac_mode
SNVT_lev_percent Heating Capacity Primary Status
SNVT_lev_percent Heating Capacity Secondary Status
SNVT_lev_percent Humidification Capacity Status
SNVT_temp_p Condenser Water Temperature Local
SNVT_temp_p Space Temperature Local
SNVT_temp_p Mixed Air Temperature Local
SNVT_lev_percent Outdoor Air Damper Position
SNVT_enthalpy Outdoor Air Enthalpy Active
FNVT_flow
SNVT_lev_percent Outdoor Air Humidity Active
SNVT_temp_p Outdoor Air Temperature Active
SNVT_temp_p Return Air Temperature
SNVT_switch
SNVT_press_p
SNVT_switch
Description
Diagnostic: Not Economizing When
Diagnostic: Economizing When
Diagnostic: Excessive Outdoor Air
Diagnostic: Mixed Air Temperature
Diagnostic: Outdoor Air Damper Not
Diagnostic: Outdoor Air Temperature
Diagnostic: Return Air Temperature
Diagnostic: Supply Air Temperature
Should Be
Should Not
Diagnostic: Mixed Air Low
Outdoor Air Flow Active
Return Fan Output Status
Return Fan Air Pressure
Return Fan Speed Status
Flow
Temperature Cycle
Sensor Failure
Modulating
Sensor Failure
Sensor Failure
Sensor Failure
Reserved
Heat Cool Mode Status
BAS-SVP039C-EN
13
Page 14
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 2. SCC Network Variable Outputs (continued)
NV# Name SendHrtBt SNVT
SNVT_state Rooftop Status
(MSB) Bit 0 Unit Running State
(LSB) Bit 15
SNVT_temp_p Space Temperature Setpoint Local
SNVT_ppm Space CO2 Concentration Active
SNVT_enthalpy Return Air Enthalpy Active
SNVT_lev_percent Space Humidity Active
SNVT_temp_p Space Temperature Active
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
108
109
110
111
112
113
114
115
116
117
118
nvoRTUStatus
nvoRTUStatus.0
nvoRTUStatus.1 Bit 1
nvoRTUStatus.2 Bit 2
nvoRTUStatus.3 Bit 3
nvoRTUStatus.4 Bit 4
nvoRTUStatus.5 Bit 5 Timed Override Status
nvoRTUStatus.6 Bit 6 Precool Mode Status
nvoRTUStatus.7 Bit 7
nvoRTUStatus.8 Bit 8
nvoRTUStatus.9 Bit 9
nvoRTUStatus.10 Bit 10 Reserved
nvoRTUStatus.11 Bit 11
nvoRTUStatus.12 Bit 12
nvoRTUStatus.13 Bit 13
nvoRTUStatus.14 Bit 14
nvoRTUStatus.15
nvoSetpoint
nvoSpaceCO2
nvoSpaceEnthalpy
nvoSpaceRH
nvoSpaceTemp
nvoStartsRunTmA
nvoStartsRunTmB
nvoStartsRunTmC
nvoStartsRunTmD
nvoStartsRunTmE
Description
Emergency Stop
External Auto Stop Input Status
Condensate Overflow Input
Timed Override Status (with Bit 5)
00 Idle
01 On
10 Cancel
Morning Warmup Running
Supply Air Tempering Status
Daytime Warmup Running
Compressor Lockout Status
Coil Frost Protection Status, Circuit 1
Coil Frost Protection Status, Circuit 2
Rapid Restart Status
Reserved
Starts - Compressor 1A
Starts
Run Time
Starts - Compressor 1B
Starts
Run Time
Starts - Compressor 1C
Starts
Run Time
Starts - Compressor 2A
Starts
Run Time
Starts - Compressor 2B
Starts
Run Time
14
BAS-SVP039C-EN
Page 15
Table 2. SCC Network Variable Outputs (continued)
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
NV# Name SendHrtBt SNVT
nvoStartsRunTmF
119
120 nvoStatus
121
122
123
124
125
126
127
128
129 nvoAirFlowPctC1
130 nvoAirFlowPctC2
131 nvoTerminalLoad
132 nvoTraneVar9
133
134 nvoUnitPower
135
136
nvoSucRfgtPrsC1
nvoSucRfgtPrsC2
nvoSucRfgtTmpC1
nvoSucRfgtTmpC2
nvoDschRfgtPrsC1
nvoDschRfgtPrsC2
nvoDisSatRfgTmp1
nvoDisSatRfgTmp2
nvoUnitCurrent
nvoUnitCurrent (bytes 1-
nvoUnitCurrent (bytes 3-
nvoUnitCurrent (bytes 5-
nvoUnitCurrent (bytes 7-
nvoUnitCurrent (bytes 9-
nvoUnitCurrent (bytes 11-
nvoUnitStatus (byte 1)
nvoUnitStatus (bytes 2-3)
nvoUnitStatus (bytes 4-5)
nvoUnitStatus (bytes 6-7)
nvoUnitStatus (bytes 8-9)
nvoUnitStatus (bytes 10-
nvoUnitStatus (byte 12)
nvoUnitVoltage (bytes 1-2)
nvoUnitVoltage (bytes 3-4)
nvoUnitVoltage (bytes 5-6)
2)
4)
6)
8)
10)
12)
nvoUnitStatus
11)
nvoUnitVoltage
Invalid
Invalid
Invalid
.mode Mode Status
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
SNVT_obj_status Local Setpoint Control
SNVT_press_f
SNVT_press_f
SNVT_temp_p
SNVT_temp_p
SNVT_press_f
SNVT_press_f
SNVT_temp_p
SNVT_temp_p
SNVT_lev_percent Air Flow Percentage, Circuit 1
SNVT_lev_percent Air Flow Percentage, Circuit 2
SNVT_lev_percent Unit Energy Demand
UNVT_c5s
UNVT_3phase_current
SNVT_amp_ac Current L1, in Amps
SNVT_amp_ac Current L2, in Amps
SNVT_amp_ac Current L3, in Amps
SNVT_power_f Unit Power Consumption
SNVT_hvac_status
.heat_output_primary Heating Capacity Primary Status
.heat_output_secondary Heating Capacity Secondary Status
.cool_output Cooling Capacity Status
.econ_output
.fan_output Supply Fan Speed Status
.in_alarm
UNVT_3Phase_volt
SNVT_volt_ac
SNVT_volt_ac
SNVT_volt_ac
Description
Starts - Compressor 2C
Starts
Run Time
Suction Refrigerant Pressure, Circuit
Suction Refrigerant Pressure, Circuit
Suction Refrigerant Temperature,
Suction Refrigerant Temperature,
Discharge Refrigerant Pressure,
Discharge Refrigerant Pressure,
Discharge Refrigerant Temperature,
Discharge Refrigerant Temperature,
Manufacturer-defined
Unit Current Per Line
1
2
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Unit Status
Economizer Status
In Alarm
Unit Voltage
Voltage AB
Voltage BC
Voltage CA
BAS-SVP039C-EN
15
Page 16
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 3. SCC Configuration Parameters
NV# Name
0
1
2
3 nciCool
4 nciCRC
5 nciDAClSP
6 nciDAHtSP
7 nciDAReheatSP
8 nciDevBuildNum U16 Device Build Number
9
10
11 nciDevMinVer SCPTdevMinVer Software Minor Version
12
13 nciEconVent
14 nciERFrostAvodSP
15
16 nciExhRet
17
18
19 nciLocation
20 nciMinOAFlowSP
21 nciMinOutTm
22 nciOAEnthSP
23 nciOAMinPos
24 nciPreheat
25 nciRcvHrtBt
26
27 nciReheat
28 nciRetFanPressSP
29
30 nciSndHrtBt
31
32
33
nciBldgStaticSP SNVT_press_p Space Static Pressure Setpoint
nciBypassTime
nciCabinetStyle UCPT_cabinet_style Cabinet Style*
nciDeviceConfig UCPTdeviceConfig
nciDevMajVer SCPTdevMajVer Software Major Version
nciEconConfigTyp UCPT_econo_config_type
nciExhaustConfig UCPT_exhaust_cfg Exhaust Enable Position Setpoint*
nciFanOperation SCPTfanOperation Supply Fan Configuration Command
nciHvacType SNVT_hvac_type HVAC Unit Type Identifier
nciRefrigType UCPT_refrig_type Refrigeration Type Identifier*
nciSetpoints SNVT_temp_setpt Occupancy Temperature Setpoints
nciSpaceCO2Lim SNVT_ppm Space CO2 High Limit
nciSpaceCO2LowLm SNVT_ppm Space CO2 Low Limit*
nciSpaceHumSP SNVT_lev_percent Space Humidification Setpoint
SNVT/UNVT, SCPT/UCPT Description
SNVT_time_min
UCPT_cool_type Cool Type*
UCPT_crc
SNVT_temp_p Discharge Air Cooling Setpoint
SNVT_temp_p Discharge Air Heating Setpoint
SNVT_temp_p Discharge Air Reheat Setpoint
UCPT_OA_type Economizer Type Identifier*
UCPT_ERFrostAvoidSP
UCPT_ER_type Exhaust Or Return Fan Type*
SNVT_str_asc
SNVT_flow
SNVT_time_sec
SNVT_enthalpy
SNVT_lev_percent
UCPT_heat_type Preheat Type Identifier*
SNVT_time_sec
UCPT_heat_type Reheat Type Identifier*
SNVT_press_p Return Fan Air Pressure Setpoint
SNVT_time_sec
Occupied Bypass Time
Manufacturer-defined*
Manufacturer-defined*
Economizer Decision Method*
Energy Recovery Frost Avoidance
Temp Setpoint*
Location Label
Outdoor Air Minimum Flow Setpoint
Economizer Outdoor Air Enthalpy
Outdoor Air Damper Minimum
Occupied Cool Setpoint
Occupied Standby Cooling Setpoint
Unoccuiped Cooling Setpoint
Occupied Heating Setpoint
Occupied Standby Heating Setpoint
Unoccupied Heating Setpoint
BAS
Minimum Send Time
Enable Setpoint BAS
Position
Receive Heartbeat
Send Heartbeat Time
16
BAS-SVP039C-EN
Page 17
Table 3. SCC Configuration Parameters (continued)
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
NV# Name
34
35
36 nciOATSP
* Manufacturer defined
nciSupplyFan UCPT_fan_type Supply Fan Type Identifier*
nciUntryType UCPT_large_equip_type Unitary Type Identifier*
SNVT/UNVT, SCPT/UCPT Description
SNVT_temp_p
Table 4. DAC Network Variable Inputs
NV# Name Recv HrtBt SNVT
42
43
44
45 nviCWFlow
46 nviDAClSP
47 nviDADewPointSP
48 nviDAHtSP
49 nviDAReheatSP
50 nviDehumEnable
51 nviDuctStaticSP
52 nviDuctStatPress
53 nviEconEnable
54
55 nviHumEnable
56 nviMinOAFlowSP
57 nviOAMinPos
58 nviOccManCmd
59 nviOccSchedule
60 nviOutdoorRH
61
62 nviPriCoolEnable
63 nviPriHeatEnable
nviApplicMode
nviBldgStaticSP SNVT_press_p Space Static Pressure Setpoint BAS
nviBldgStatPress
nviEmergOverride SNVT_hvac_emerg Emergency Override BAS
nviOutdoorTemp
SNVT_hvac_mode
SNVT_press_p Space Static Pressure BAS
SNVT_switch
SNVT_temp_p Discharge Air Cooling Setpoint BAS
SNVT_temp_p Discharge Air Dewpoint Setpoint
SNVT_temp_p Discharge Air Heating Setpoint BAS
SNVT_temp_p Discharge Air Reheat Setpoint BAS
SNVT_switch
SNVT_press_p Duct Static Pressure Setpoint BAS
SNVT_press_p
SNVT_switch
SNVT_switch
SNVT_flow
SNVT_lev_percent
SNVT_occupancy Occupancy Input
SNVT_tod_event
SNVT_lev_percent Outdoor Air Humidity BAS
SNVT_temp_p Outdoor Air Temperature BAS
SNVT_switch
SNVT_switch
Model Information
Cooling Source Size
Heating Source Size
Number of Circuits
Number of Compressors, Circuit 1
Number of Compressors, Circuit 2
Economizer Outdoor Air Enable
Setpoint BAS
Description
Heat Cool Mode Request
Condenser Water Flow BAS
Dehumidification Enable Command
Duct Static Pressure BAS
Economizer Airside Enable BAS
Humidification Command
Outdoor Air Minimum Flow Setpoint
Economizer Minimum Position
Cooling Capacity Enable
Heat Primary Enable BAS
BAS
Setpoint BAS
Occupancy Request
BAS-SVP039C-EN
17
Page 18
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 4. DAC Network Variable Inputs (continued)
NV# Name Recv HrtBt SNVT
nviRTUConfig
nviRTUConfig.0 (MSB) Bit 0
nviRTUConfig.1
nviRTUConfig.2
nviRTUConfig.3
nviRTUConfig.4
nviRTUConfig.5
nviRTUConfig.6
nviRTUConfig.7
nviRTUConfig.8
64
65
66
67
68
69
70
71 nviTraneVar2
nviRTUConfig.9
nviRTUConfig.10
nviRTUConfig.11
nviRTUConfig.12
nviRTUConfig.13
nviRTUConfig.14
nviRTUConfig.15 (LSB) Bit 15
nviRequest SNVT_obj_request Reset Diagnostic Request
nviSpaceCO2
nviSpaceDehumSP SNVT_lev_percent Space Dehumidification Setpoint BAS
nviSpaceHumSP SNVT_lev_percent Space Humidification Setpoint BAS
nviSpaceRH
nviSpaceTemp
SNVT_state
Bit 10
Bit 11
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
SNVT_ppm Space CO2 Concentration BAS
SNVT_lev_percent Space Humidity BAS
SNVT_temp_p Space Temperature BAS
UNVT_c5c
Description
Rooftop Configuration
Reserved
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6 PreCool Enable Command
Bit 7
Bit 8
Bit 9
Morning Warmup Enable Command
Supply Air Tempering Request BAS
Daytime Warmup Enable Command
Timed Override Request (with Bit 11)
Cooling Lockout
Heating Lockout
Demand Limit Request BAS
Energy Consumption Reset
Supply Fan Compensation
Timed Override Request
00 Idle
01 On
10 Cancel
11 Invalid
Reserved
Manufacturer-defined
Table 5. DAC Network Variable Outputs
NV# Name Send HrtBt SNVT
72
73
74
75
76
18
nvoAlarmMessage SNVT_str_asc
nvoApplicMode
nvoBldgStatPress
nvoCondCap
nvoCoolPrimary
SNVT_hvac_mode
SNVT_press_p Space Static Pressure Active
SNVT_lev_percent Condenser Capacity
SNVT_lev_percent Cooling Capacity Status
Description
Diagnostic Last Message
Application Mode Output
BAS-SVP039C-EN
Page 19
Table 5. DAC Network Variable Outputs (continued)
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
NV# Name Send HrtBt SNVT
nvoCprsrsRunning
nvoCprsrsRunning.0
nvoCprsrsRunning.1
nvoCprsrsRunning.2
nvoCprsrsRunning.3
nvoCprsrsRunning.4
nvoCprsrsRunning.5
nvoCprsrsRunning.6
77
78 nvoCWFlow
79
80
81 nvoDAReheatSP
82 nvoDehumidifier
83
84 nvoDuctStatPress
85 nvoEconEnabled
86 nvoEffDADewPtSP
87
88 nvoEffDuctStatSP
89
90
91
92
93
94 nvoERPreheat
95 nvoERStatus
96
97 nvoExhFanOnOff
98 nvoExhFanStatus
nvoCprsrsRunning.7
nvoCprsrsRunning.8
nvoCprsrsRunning.9
nvoCprsrsRunning.10
nvoCprsrsRunning.11
nvoCprsrsRunning.12
nvoCprsrsRunning.13
nvoCprsrsRunning.14
nvoCprsrsRunning.15
nvoCWPump
nvoCWTemp
nvoDischAirTemp
nvoEffDATempSP
nvoEffectOccup
nvoEffSpaceHumSP
nvoEREABPDamper
nvoERLvgExhTemp
nvoEROABPDamper
nvoExhDamper
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Bit 8
Bit 9
Bit 10
Bit 11
Bit 12
Bit 13
Bit 14
SNVT_state
(MSB) Bit 0 Validity of bit 8
(LSB) Bit 15 Compressor 2D Status
SNVT_switch
SNVT_switch
SNVT_temp_p Condenser Water Temperature
SNVT_temp_p Discharge Air Reheat Setpoint Active
SNVT_switch
SNVT_temp_p Discharge Air Temperature
SNVT_press_p
SNVT_switch
SNVT_temp_p
SNVT_temp_p
SNVT_press_p Duct Static Pressure Setpoint Active
SNVT_occupancy Occupancy Status
SNVT_lev_percent Space Humidity Active
SNVT_lev_percent
SNVT_temp_p
SNVT_lev_percent
SNVT_switch
SNVT_switch
SNVT_lev_percent Exhaust Damper Position
SNVT_switch
SNVT_switch
Description
Compressor Status
Validity of bit 9
Validity of bit 10
Validity of bit 11
Validity of bit 12
Validity of bit 13
Validity of bit 14
Validity of bit 15
Compressor 1A Status
Compressor 1B Status
Compressor 1C Status
Compressor 1D Status
Compressor 2A Status
Compressor 2B Status
Compressor 2C Status
Condenser Water Flow Status
Condenser Water Pump Status
Dehumidification Control Status
Duct Static Pressure Active
Economizer Entering Water
Temperature Active
Discharge Air Dewpoint Temperature
Discharge Air Temperature Setpoint
Energy Recovery Exhaust Air Bypass
Energy Recovery Leaving Exhaust
Energy Recovery Outdoor Air Bypass
Setpoint Active
Active
Damper Position
Temperature Status
Damper Status
Energy Recovery Preheat Status
Energy Recovery Status
Exhaust Fan Output Status
Exhaust Fan Speed Status
BAS-SVP039C-EN
19
Page 20
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 5. DAC Network Variable Outputs (continued)
NV# Name Send HrtBt SNVT
nvoFDD
nvoFDD.0
nvoFDD.1 Bit 1
nvoFDD.2 Bit 2
nvoFDD.3 Bit 3
nvoFDD.4 Bit 4
nvoFDD.5 Bit 5
nvoFDD.6 Bit 6
99
100 nvoHeatCool
101
102
103 nvoHumidifier
104
105 nvoLocalDSPress
106 nvoLocalOARH
107
108
109
110
111
112 nvoOAFlow
113 nvoOutdoorRH
114
115
116 nvoRetFanOnOff
117 nvoRetFanPress
118 nvoRetFanStatus
nvoFDD.7 Bit 7
nvoFDD.8 Bit 8
nvoFDD.9 Bit 9 Reserved
nvoFDD.10 Bit 10 Reserved
nvoFDD.11 Bit 11 Reserved
nvoFDD.12 Bit 12 Reserved
nvoFDD.13 Bit 13 Reserved
nvoFDD.14 Bit 14 Reserved
nvoFDD.15
nvoHeatPrimary
nvoHeatSecondary
nvoLocalCWTemp
nvoLocalOATemp
nvoMATemp
nvoOADamper
nvoOADewpoint
nvoOAEnthalpy
nvoOutdoorTemp
nvoRATemp
SNVT_state Fault Detection and Diagnostics
(MSB) Bit 0
(LSB) Bit 15
SNVT_hvac_mode
SNVT_lev_percent Heating Capacity Primary Status
SNVT_lev_percent Heating Capacity Secondary Status
SNVT_lev_percent Humidification Capacity Status
SNVT_temp_p Condenser Water Temperature Local
SNVT_press_p
SNVT_lev_percent Outdoor Air Relative Humidity Local
SNVT_temp_p Outdoor Air Temperature Local
SNVT_temp_p Mixed Air Temperature Local
SNVT_lev_percent Outdoor Air Damper Position
SNVT_temp_p Outdoor Air Dewpoint
SNVT_enthalpy Outdoor Air Enthalpy Active
SNVT_flow
SNVT_lev_percent Outdoor Air Humidity Active
SNVT_temp_p Outdoor Air Temperature Active
SNVT_temp_p Return Air Temperature
SNVT_switch
SNVT_press_p
SNVT_switch
Description
Diagnostic: Not Economizing When
Diagnostic: Economizing When
Diagnostic: Excessive Outdoor Air
Diagnostic: Mixed Air Temperature
Diagnostic: Outdoor Air Damper Not
Diagnostic: Outdoor Air Temperature
Diagnostic: Return Air Temperature
Diagnostic: Supply Air Temperature
Should Be
Should Not
Diagnostic: Mixed Air Low
Duct Static Pressure Local
Outdoor Air Flow Active
Return Fan Output Status
Return Fan Air Pressure
Return Fan Speed Status
Flow
Temperature Cycle
Sensor Failure
Modulating
Sensor Failure
Sensor Failure
Sensor Failure
Reserved
Heat Cool Mode Status
20
BAS-SVP039C-EN
Page 21
Table 5. DAC Network Variable Outputs (continued)
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
NV# Name Send HrtBt SNVT
SNVT_state Rooftop Status
(MSB) Bit 0 Unit Running State
(LSB) Bit 15
SNVT_ppm Space CO2 Concentration Active
SNVT_enthalpy Return Air Enthalpy Active
SNVT_lev_percent Space Humidity Active
SNVT_temp_p Space Temperature Active
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
119
120
121
122
123
124
125
126
127
128
nvoRTUStatus
nvoRTUStatus.0
nvoRTUStatus.1 Bit 1
nvoRTUStatus.2 Bit 2
nvoRTUStatus.3 Bit 3
nvoRTUStatus.4 Bit 4
nvoRTUStatus.5 Bit 5 Timed Override Status
nvoRTUStatus.6 Bit 6 Precool Mode Status
nvoRTUStatus.7 Bit 7
nvoRTUStatus.8 Bit 8
nvoRTUStatus.9 Bit 9
nvoRTUStatus.10 Bit 10 Reserved
nvoRTUStatus.11 Bit 11
nvoRTUStatus.12 Bit 12
nvoRTUStatus.13 Bit 13
nvoRTUStatus.14 Bit 14
nvoRTUStatus.15
nvoSpaceCO2
nvoSpaceEnthalpy
nvoSpaceRH
nvoSpaceTemp
nvoStartsRunTmA
nvoStartsRunTmB
nvoStartsRunTmC
nvoStartsRunTmD
nvoStartsRunTmE
Description
Emergency Stop
External Auto Stop Input Status
Condensate Overflow Input
Timed Override Status (with Bit 5)
00 Idle
01 On
10 Cancel
Morning Warmup Running
Supply Air Tempering Status
Daytime Warmup Running
Compressor Lockout Status
Coil Frost Protection Status, Circuit 1
Coil Frost Protection Status, Circuit 2
Rapid Restart Status
Reserved
Starts - Compressor 1A
Starts
Run Time
Starts - Compressor 1B
Starts
Run Time
Starts - Compressor 1C
Starts
Run Time
Starts - Compressor 2A
Starts
Run Time
Starts - Compressor 2B
Starts
Run Time
BAS-SVP039C-EN
21
Page 22
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 5. DAC Network Variable Outputs (continued)
NV# Name Send HrtBt SNVT
nvoStartsRunTmF
129
130 nvoStatus
131
132
133
134
135
136
137
138
139 nvoAirFlowPctC1
140 nvoAirFlowPctC2
141
142
143 nvoTraneVar9
144
145 nvoUnitPower
146
147
nvoSucRfgtPrsC1
nvoSucRfgtPrsC2
nvoSucRfgtTmpC1
nvoSucRfgtTmpC2
nvoDschRfgtPrsC1
nvoDschRfgtPrsC2
nvoDisSatRfgTmp1
nvoDisSatRfgTmp2
nvoSupFanOnOff
nvoSupFanStatus
nvoUnitCurrent
nvoUnitCurrent (bytes 1-
nvoUnitCurrent (bytes 3-
nvoUnitCurrent (bytes 5-
nvoUnitCurrent (bytes 7-
nvoUnitCurrent (bytes 9-
nvoUnitCurrent (bytes 11-
nvoUnitStatus (byte 1)
nvoUnitStatus (bytes 2-3)
nvoUnitStatus (bytes 4-5)
nvoUnitStatus (bytes 6-7)
nvoUnitStatus (bytes 8-9)
nvoUnitStatus (bytes 10-
nvoUnitStatus (byte 12)
nvoUnitVoltage (bytes 1-2)
nvoUnitVoltage (bytes 3-4)
nvoUnitVoltage (bytes 5-6)
2)
4)
6)
8)
10)
12)
nvoUnitStatus
11)
nvoUnitVoltage
Invalid
Invalid
Invalid
.mode Mode Status
UNVT_starts_runtime
SNVT_count_f
SNVT_time_f
SNVT_obj_status Local Setpoint Control
SNVT_press_f
SNVT_press_f
SNVT_temp_p
SNVT_temp_p
SNVT_press_f
SNVT_press_f
SNVT_temp_p
SNVT_temp_p
SNVT_lev_percent Air Flow Percentage, Circuit 1
SNVT_lev_percent Air Flow Percentage, Circuit 2
SNVT_switch
SNVT_switch
UNVT_c5s
UNVT_3phase_current
SNVT_amp_ac Current L1, in Amps
SNVT_amp_ac Current L2, in Amps
SNVT_amp_ac Current L3, in Amps
SNVT_power_f Unit Power Consumption
SNVT_hvac_status
.heat_output_primary Heating Capacity Primary Status
.heat_output_secondary Heating Capacity Secondary Status
.cool_output Cooling Capacity Status
.econ_output
.fan_output Supply Fan Speed Status
.in_alarm
UNVT_3Phase_volt
SNVT_volt_ac
SNVT_volt_ac
SNVT_volt_ac
Description
Starts - Compressor 2C
Starts
Run Time
Suction Refrigerant Pressure, Circuit
Suction Refrigerant Pressure, Circuit
Suction Refrigerant Temperature,
Suction Refrigerant Temperature,
Discharge Refrigerant Pressure,
Discharge Refrigerant Pressure,
Discharge Refrigerant Temperature,
Discharge Refrigerant Temperature,
Supply Fan Output Status
Supply Fan Speed Status
Manufacturer-defined
Unit Current Per Line
1
2
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Circuit 1
Circuit 2
Unit Status
Economizer Status
In Alarm
Unit Voltage
Voltage AB
Voltage BC
Voltage CA
22
BAS-SVP039C-EN
Page 23
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 6. DAC Network Configuration Parameters
0
1
2
3 nciCool
4 nciCoolResetEn
5 nciCRC
6 nciDAClSP
7
8 nciDAHtSP
9 nciDAReheatSP
10
11 nciDevBuildNum U16 Device Build Number
12
13
14 nciDevMinVer SCPTdevMinVer Software Minor Version
15 nciDuctStatSP
16
17 nciEconVent
18 nciERFrostAvodSP
19 nciExhRet
20 nciExhStartPos
21 nciHeatResetEn
22
23 nciLocation
24 nciMinOAFlowSP
25 nciMinOutTm
26 nciOAEnthSP
27 nciOAMinPos
28 nciOATSP
29 nciPreheat
30 nciRcvHrtBt
31 nciReheat
32 nciRetFanPressSP
33
34
35 nciSndHrtBt
nciBldgStaticSP SNVT_press_p Space Static Pressure Setpoint
nciBypassTime
nciCabinetStyle UCPT_cabinet_style Cabinet Style*
nciDADewpointSP SNVT_temp_p Discharge Air Dewpoint Setpoint
nciDaytime SNVT_temp_p Daytime Warmup Initiation Setpoint
nciDeviceConfig UCPTdeviceConfig
nciDevMajVer SCPTdevMajVer Software Major Version
nciEconConfigTyp UCPT_econo_config_type
nciHvacType SNVT_hvac_type HVAC Unit Type Identifier
nciRefrigType UCPT_refrig_type Refrigeration Type Identifier*
nciSetpoints SNVT_temp_setpt Occupancy Temperature Setpoints
SNVT_time_min Occupied Bypass Time
UCPT_cool_type Cool Type*
SNVT_switch
UCPT_crc
SNVT_temp_p Discharge Air Cooling Setpoint
SNVT_temp_p Discharge Air Heating Setpoint
SNVT_temp_p Discharge Air Reheat Setpoint
SNVT_press_p Duct Static Pressure Setpoint
UCPT_OA_type Economizer Type Identifier*
UCPT_ERFrostAvoidSP
UCPT_ER_type Exhaust Or Return Fan Type*
SNVT_lev_percent Exhaust Enable Position Setpoint
SNVT_switch
SNVT_str_asc
SNVT_flow
SNVT_time_sec
SNVT_enthalpy
SNVT_lev_percent
SNVT_temp_p
UCPT_heat_type Preheat Type Identifier*
SNVT_time_sec
UCPT_heat_type Reheat Type Identifier*
SNVT_press_p Return Fan Air Pressure Setpoint
SNVT_time_sec
Cooling Reset Type Status
Manufacturer-defined*
Manufacturer-defined*
Economizer Decision Method*
Energy Recovery Frost Avoidance
Temp Setpoint*
Heating Reset Type Status
Location Label
Outdoor Air Minimum Flow Setpoint
Minimum Send Time
Economizer Outdoor Air Enthalpy
Enable Setpoint
Outdoor Air Damper Minimum
Economizer Enable Minimum Outdoor
Occupied Standby Cooling Setpoint
Unoccuiped Cooling Setpoint
Occupied Heating Setpoint
Occupied Standby Heating Setpoint
Unoccupied Heating Setpoint
Position
Air Temperature Setpoint
Receive Heartbeat
Occupied Cool Setpoint
Send Heartbeat Time
BAS-SVP039C-EN
23
Page 24
PPrrooffiillee DDeeffiinniittiioonn aanndd NNeettwwoorrkk VVaarriiaabblleess
Table 6. DAC Network Configuration Parameters (continued)
36
37
38
39
40
41
*Manufacturer defined
nciSpaceCO2Lim SNVT_ppm Space CO2 High Limit
nciSpaceCO2LowLm SNVT_ppm Space CO2 Low Limit*
nciSpaceDehumSP SNVT_lev_percent Space Dehumidification Setpoint
nciSpaceHumSP SNVT_lev_percent Space Humidification Setpoint
nciSupplyFan UCPT_fan_type Supply Fan Type Identifier*
nciUntryType UCPT_large_equip_type Unitary Type Identifier*
Number of Compressors, Circuit 1
Number of Compressors, Circuit 2
Model Information
Cooling Source Size
Heating Source Size
Number of Circuits
24
BAS-SVP039C-EN
Page 25
Appendix A. Arbitration
The Symbio800 controller includes arbitration logic for several points. For each read/write point designated as “BAS”, an associated “Arbitration” point determines the behavior of that communicated data compared to the local hardwired (or wireless) sensor and a default value.
As shown in including Building Management Systems (BMS), local, and default. Each potential source is defined at a pre-determined, fixed priority. When the arbitration method is selected as full/auto, the BMS value is used instead of the local or default values.
The point designator with the arbitrator suffix includes the full priority array, allowing the user to see the value associated with all potential sources considered in the logic. The active point reflects the result of the arbitration logic.
Because the arbitrated points are normally associated with sensors, the default value is invalid, meaning the value must be provided either by the BMS or the local sensor.
Figure 6. Arbitration method - full/auto
Figure 6, p. A–1, the arbitrator considers all possible sources of the provided data,
BAS-SVP039C-EN
When the Arbitration Method is selected as local, the BMS value is ignored and local value is used instead. Though the arbitration logic still considers all inputs, any values sent by the BMS are effectively ignored.
Figure 7. Arbitration method - local
A–1
Page 26
Appendix B. Symbio™ 800 Controller Display
Figure 8. Symbio™™ 800 controller display and LEDs
77––SSeeggmmeenntt ssttaattuuss ddiissppllaayy
Table 7. Codes for 7–segment display segment
Code Description
U0. Waiting for USB drives to mount
U2. Checking signature on the .scfw file
U3.
U4.
U5. Beginning update
U12.
U51.
U54. Updating FPGA image
U55. Updating U-boot image
U57.
Checking software maintenance plan
Reformatting main filesystem (clearing database)
Searching for .scfw files on USB drive(s)
Updating main firmware
Updating recovery partition
B–1
NNoottee:: A code starting with an “F” indicates a failure, and requires Trane Service to resolve the
issue.
PP11 LLiinnkk —— BBAACCnneett TTPP oorr MMooddbbuuss RRTTUU
RS-485 daisy chain
Used for connection to a primary controller
BAS-SVP039C-EN
Page 27
Server
Server Serve
r
SSyymmbbiioo™ 880000 CCoonnttrroolllleerr DDiissppllaayy
Figure 9. P2 Modbus device (factory installed Modbus server devices)
NNoottee:: The P2 link is intended for factory devices only and should not have any other devices
added this link.
Figure 10. P3 machine bus (global bus — internal communication bus)
NNoottee:: The P3 link is intended for factory devices only and should not have any other devices
added this link.
BAS-SVP039C-EN
B–2
Page 28
SSyymmbbiioo™ 880000 CCoonnttrroolllleerr DDiissppllaayy
Figure 11. IMC link terminations for optional Air-Fi and expansion module (XM30)
B–3
For more information on Expansion Module wiring reference BAS-SVX46* – Expansion Module Installation Operation and Maintenance Manual.
Figure 12. (4) USB connectors
BAS-SVP039C-EN
Page 29
Touch Screen
Display
SSyymmbbiioo™ 880000 CCoonnttrroolllleerr DDiissppllaayy
The controller automatically detects devices on any of the ports (not port specific). The controller ships with all ports enabled, but they can be disabled via the Web interface.
NNoottee:: The USB ports are not to be used for any devices that are not Trane approved, such as
cellular phones.
Figure 13. Ethernet port 2
BAS-SVP039C-EN
NNoottee:: Ethernet Port 2 is for use with the Touch Screen display only. Communication to other
devices is not supported.
B–4
Page 30
NNootteess
30
BAS-SVP039C-EN
Page 31
NNootteess
BAS-SVP039C-EN
31
Page 32
Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
BAS-SVP039C-EN 22 Apr 2021
Supersedes BAS-SVP039B-EN (May 2020)
©2021 Trane
Loading...