Trane Stealth Air-Cooled Chiller Model RTAE Installation and Maintenance Manual

Stealth™ Air-Cooled Chiller Model RTAE
150 to 300 Nominal Tons
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air­conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the li terature and on the tags, stickers, and labels that are attached to the equipment.
October 2014
RTAE-SVX001B-EN

Warnings, Cautions and Notices

Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards thatcould result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these precautions.
Read this manual thoroughly beforeoperating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation thatcould result in equipment or property-damage only
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that
must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Refrigerant under High Pressure!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to recover refrigerant to relieve pressure or the use of non­approved refrigerants, refrigerant substitutes, or refrigerant additives could result in an explosion which could result in death or serious injury or equipment damage.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014 Trane All rights reserved RTAE-SVX001B-EN
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.

Factory Warranty Information

Compliance with the following is required to preserve the factory warranty:
All Unit Installations
Startup MUST be performed byTrane, or an authorized agent ofTrane, to VALIDATE this WARRANTY. Contractor must provide a two-week startup notification to Trane (or an agent of Trane specifically authorized to perform startup).
Warnings, Cautions and Notices

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in
part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any per son of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

RTAE-SVX001B-EN (29 Oct 2014)
Added transformer option.
Added harmonic filter option.
Added 150T and 165T single circuit units.
Added extreme low ambient option.
Added seismic isolation option.
Added CE/PED option.
Updated unit weights and isolator information.
Updated drive cooling fluid volumes.
Modified oil sump check procedure.
RTAE-SVX001A-EN (24 Sep 2013)
New release.
RTAE-SVX001B-EN 3
Table of Contents
Warnings, Cautions and Notices .......... 2
Factory Warranty Information ........... 3
Copyright ............................. 3
Trademarks ........................... 3
Revision History ....................... 3
Model Number Description ............... 6
Outdoor Unit Nameplate ............... 6
Compressor Nameplate ................ 6
Model Number Descriptions .............. 7
Unit Model Number .................... 7
Compressor Model Number ............ 8
Compressor Serial Number ............. 8
General Information ..................... 9
Unit Description ....................... 9
Accessory/Option Information ........... 9
General Data ........................... 10
Drive Cooling System ................. 11
Pre-Installation ......................... 12
Unit Inspection ..................... 12
Inspection ......................... 12
Storage ........................... 12
Installation Requirements .............. 13
Dimensions and Weights ................ 14
Weights ............................. 14
Unit Dimensions ...................... 14
Service Clearances .................... 14
Installation Mechanical .................. 15
Location Requirements ................ 15
Sound Considerations ............... 15
Foundation ........................ 15
Clearances ......................... 15
Center of Gravity ..................... 20
Isolation and Sound Emission .......... 20
Unit Isolation and Leveling ........... 20
Compressor Shipping Bolt Removal .... 23
Units with InvisiSound™ Ultimate Option
(Model Number Digit 12 = 3) .......... 23
Pressure Relief Valves ..................26
Evaporator Waterside Pressure Drop Curves
...............................27
Freeze Protection ......................29
Low Evaporator Refrigerant Cutout,
Glycol Requirements
...................30
Installation Electrical .....................31
General Recommendations .............31
Adaptive Frequency™ Drive (AFD3)
Capacitor Discharge ..................32
Units with Nitrogen Charge Option .....32
Installer-Supplied Components ..........32
Power Supply Wiring .................33
Control Power Supply ................34
Service Power Connection ............34
Heater Power Supply .................34
Interconnecting Wiring .................35
Chilled Water Pump Control ...........35
Programmable Relays ..................35
Relay Assignments Using Tracer™ TU ...36
Low Voltage Wiring ....................36
Emergency Stop .....................36
External Auto/Stop ...................36
External Circuit Lockout –
Circuit #1 and #2 .....................36
Ice Building Option ..................37
External Chilled Water Setpoint (ECWS)
Option .............................37
External Demand Limit Setpoint (EDLS)
Option .............................37
Chilled Water Reset (CWR) ............38
Transformer Power Rating ..............39
Communications Interface ..............39
LonTalk Interface (LCI-C) ..............39
BACnet Interface (BCI-C) ..............39
Modbus Remote Terminal Unit Interface .39
Operating Principals .....................40
Refrigeration Circuits ..................40
Refrigeration Cycle ....................40
Drainage ............................ 23
Refrigerant R-134a .....................40
Evaporator Piping Components ....... 25
4 RTAE-SVX001B-EN
Compressor and Lube Oil System ...... 40
Condenser and Fans .................. 40
Evaporator ........................... 41
Drive Cooling System ................. 41
Controls ............................... 42
UC800 Specifications .................. 42
Wiring and Port Descriptions ......... 42
Communication Interfaces ............ 43
Rotary Switches .................... 43
LED Description and Operation ........ 43
Tracer AdaptiView TD7 Display ......... 43
Operator Interface .................. 43
Main Display Area/Home Screen ...... 44
Viewing Chiller Operating Modes ..... 44
Alarms ........................... 46
Reports ........................... 47
Equipment Settings ................. 49
Display Settings .................... 51
Viewing the Settings Screen ......... 51
Cleaning the Display ................ 52
Security Settings ................... 52
Disabling/Enabling Security .......... 52
InvisiSound Ultimate - Noise Reduction
Mode ............................. 54
Tracer™ TU .......................... 55
Pre-Start ............................... 56
Start-Up and Shutdown ................. 57
Unit Start-Up ......................... 57
Temporary Shutdown And Restart ...... 57
Extended Shutdown Procedure ......... 57
Seasonal Unit Start-Up Procedure ...... 58
System Restart After Extended Shutdown 58
Sequence of Operation ................ 59
Software Operation Overview ......... 59
Timelines .......................... 59
Power Up Diagram .................. 60
Power Up to Starting ................ 61
Stopped to Starting ................. 62
Running (Lead Compressor/Circuit Start
and Run) .......................... 63
Running (Lag Compressor/Circuit
Start and Run) ......................63
Satisfied Setpoint ....................64
Normal Shutdown to Stopped or
Run Inhibit .........................65
Immediate Shutdown to Stopped or
Run Inhibit .........................65
Ice Making (Running to Ice Making to
Running) ...........................66
Ice Making (Auto to Ice Making to Ice
Making Complete) ...................67
Maintenance ............................68
Recommended Maintenance ............69
Weekly .............................69
Monthly ............................69
Annual .............................69
Refrigerant and Oil Charge Management .69
Lubrication System ....................69
Oil Sump Level Check ................69
Drive Cooling System ..................71
Service Intervals .....................71
Unit Diagnostics .....................71
pH Test ............................71
Pressure Relief Cap ..................71
Drive Cooling Expansion Tank .........71
Condenser Coils — Cleaning and Inspection
Coil Cleaning and Inspection Interval ....72
Cleaning Air Side of RTAE Coils ........72
Cleaning Coated Coils ................72
Coil Corrosion Protection Inspection ....72
............................72
Reinstallation of Compressor Shipping
Bolts
.................................72
Servicing Chiller Roof ................72
Diagnostics .............................73
AFD Diagnostics .......................73
Main Processor Diagnostics .............76
Communication Diagnostics ............85
Operator Display Diagnostics and Messages
............................88
Unit Wiring .............................89
Log and Check Sheet ....................90
RTAE-SVX001B-EN 5

Model Number Description

Nameplates
The Stealth™ outdoor unit nameplates are applied to the
exterior of the Control Panel. A compressor nameplate is located on each compressor. When the unit arrives, compare all nameplate data with ordering, submittal, and shipping information.

Outdoor Unit Nameplate

See Figure 1 for a typical unit nameplate.The outdoor unit nameplate provides the following information:
Unit model and size description.
Unit serial number.
Identifies unit electrical requirements.
Lists correct operating charges of R-134a and refrigerant
Lists unit test pressures.
Identifies installation, operation and maintenance and service
Lists drawing numbers for unit wiring diagrams.
Model Number Coding System
The model numbers for the unit and the compressor are
composed of numbers and letters that represent features of the equipment. Shown in the following table is a sample
oil (Trane OIL00311).
data literature.
of typical unit model number and the coding system for each.
Each position, or group of positions, in the model number is used to represent a feature. For example, in the first table, position 08 of the unit model number, Unit Voltage, contains the number“4”.A 4 in this position means that the unit voltage is 460/60/3.
Unit Model Number. An example of a typical unit
model number (M/N) is:
RTAE 200F UA01 AA1F N1X1 A1A0 0CB0 X02X AA03 000
Model number digits are selected and assigned in accordance with the definitions as listed in “Unit Model
Number,” p. 7.

Compressor Nameplate

The compressor nameplate provides the following
information:
Compressor model number. See “Compressor Model
Number,” p. 8.
Compressor serial number. See “Compressor Serial
Number,” p. 8.
Compressor electrical characteristics.
Utilization range.
Recommended refrigerant.
Figure 1. Typical unit nameplate
6 RTAE-SVX001B-EN

Model Number Descriptions

Unit Model Number

Digits 1,2 — Unit Model
RT = Rotary Chiller
Digits 3— Unit Type
A = Air-cooled
Digits 4 — Development Sequence
E = Development Sequence
Digits 5-7 — Nominal Capacity
149 = 150 NominalTons Single Circuit 164 = 165 NominalTons Single Circuit 150 = 150 NominalTons 165 = 165 NominalTons 180 = 180 NominalTons 200 = 200 Nominal Tons 225 = 225 Nominal Tons 250 = 250 Nominal Tons 275 = 275 Nominal Tons 300 = 300 Nominal Tons
Digit 8— Unit Voltage
A = 200/60/3 B = 230/60/3 C = 380/50/3 D = 380/60/3 E = 400/50/3 F = 460/60/3 G = 575/60/3 H = 400/60/3
Digit 9 — Manufacturing Location
U = Trane Commercial Systems,
Pueblo, CO USA
Digits 10, 11— Design Sequence
** = Factory assigned
Digit 12 — Unit Sound Package
1 = InvisiSound™ Standard Unit 2 = InvisiSound Superior
(Line Wraps, Reduced Fan Speed)
3 = InvisiSound Ultimate
(Compressor Sound Attenuation, Line Wraps, Reduced Fan Speed)
Digit 13 — Agency Listing
0 = No Agency Listing A = UL/CUL Listing C = CE European Safety Standard
Digit 14 — Pressure Vessel Code
A = ASME Pressure Vessel Code D = Australia PressureVessel Code C = CRN or Canada Equivalent
Pressure Vessel Code L = Chinese Pressure Vessel Code P = PED European Pressure Vessel
Code
Digit 15 — Factory Charge
1 = Refrigerant Charge HFC-134a 2 = Nitrogen Charge
Digit 16 — Evaporator
Application
F = Standard Cooling
(40 to 68°F/5.5 to 20°C)
G = LowTemp Process
(<40°F LeavingTemp)
C = Ice-making (20 to 68°F/-7 to 20°C)
w/ Hardwired Interface
Digit 17 — Evaporator Configuration
N = 2 Pass Evaporator P = 3 Pass Evaporator
Digit 18 — Evaporator Fluid
Type
1 = Water 2 = Calcium Chloride 3 = Ethylene Glycol 4 = Propylene Glycol 5 = Methanol
Digit 19 — Water Connection
X = Grooved Pipe F = Grooved Pipe + Flange
Digit 20 — Flow Switch
1 = Factory Installed - Other Fluid
(15 cm/s)
2 = Factory Installed - Water 2
(35 cm/s)
3 = Factory Installed - Water 3
(45 cm/s)
Digit 21 — Insulation
A = Factory Insulation - All Cold Parts
0.75”
B = Evaporator-Only Insulation -
High Humidity/Low EvapTemp
1.25”
Digit 22 — Unit Application
1 = Standard Ambient
(32 to 105°F/0 to 40.6°C)
2 = Low Ambient
(0 to 105°F/-17.7 to 40.6°C)
3 = Extreme Low Ambient
(-20 to 105°F/-28.9 to 40.6°C)
4 = High Ambient
(32 to 125°F/0 to 52°C)
5 = Wide Ambient
(0 to 125°F/-17.7 to 52°C)
Digit 23 — Condenser Fin Options
A = Aluminum Fins with Slits
D = CompleteCoat™ Epoxy Coated
Fins
Digits 24, 25 — Not Used
Digit 26 — Power Line Connection Type
A = Terminal Block C = Circuit Breaker D = Circuit Breaker w/ High Fault
Rated Control Panel
Digit 27 — Short Circuit Current Rating
A = Default A Short Circuit Rating B = High A Short Circuit Rating
Digit 28 — Transformer
0 = NoTransformer 1 = Factory Installed Transformer
Digit 29 — Line Voltage Harmonic Mitigation
X = Line Reactors (~30%TDD) 1 = Filter circuit (IEEE519 Compliant)
Digit 30 — Electrical
Accessories
0 = No Convenience Outlet C = 15A 115V convenience Outlet
(Type B)
Digit 31 — Remote Communication Options
0 = No Remote Digital
Communication
1 = LonTalk®Interface LCI-C
(Tracer™ Compatible)
2 = BACnet®MS/TP Interface
(Tracer compatible)
3 = ModBus™ Interface
Digit 32 — Hard Wire Communication
X = None
A = Hard Wired Bundle - All
B = Remote LeavingWaterTemp
Setpoint
C = Remote Leaving temp and
Demand Limit Setpoints D = Programmable Relay E = Programmable Relay and
Leaving Water and Demand Limit
Setpoint F = Percent Capacity G = Percent Capacity and Leaving
Water and Demand Limit Setpoint H = Percent Capacity and
Programmable Relay
Digit 33 — Not Used
RTAE-SVX001B-EN 7
Model Number Descriptions
Digit 34 — Structural Options
A = Standard Unit Structure B = Seismic to International Building
Code (IBC)
C = California Office of Statewide
Health Planning and Development (OSHPD) Certification
D = Wind Load for Florida Hurricane
175 MPH E = Seismic (IBC) and Wind Load F = OSHPD andWind Load
Digit 35 — Appearance Options
0 = No Appearance Options A = Architectural Louvered Panels
Digit 36 — Unit Isolation
0 = No Isolation 1 = Elastomeric Isolators 3 = Seismic Rated Isopads
Digit 37 — Not Used
0 = Not Used
Digit 38 — Not Used
0 = Not Used
Digit 39 — Special
0 = None S = Special

Compressor Model Number

Digits 1-4 — Compressor Type
CHHS= Positive displacement, helical
rotary (twin screw) hermetic compressor
Digit 5 — Frame Size
R = R Frame: 70 - 100 tons S = S Frame: 112 - 165 tons
Digit 6— Motor Length
B=145mm C=170mm E=165mm F=190mm
Digit 7 — Motor Winding
Characteristics
* = Factory assigned
Digit 8 — Volume Ratio
B = High Volume Ratio
Digit 9 — Refrigerant
1 = R-134a
Digits 10-11— Design Sequence
** = Factory assigned

Compressor Serial Number

Digits 1-2 — Year
YY = Last two digits of year of
manufacture
Digit 3— Week
WW= Week of build, from 00 to 52
Digit 5 — Day
1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday 7 = sunday
Digits 6-8 — Coded Time Stamp
TTT = Used to ensure uniqueness of
serial number
Digit 9 — Assembly Line
Assembly line compressor was built on.
Varies with facility
Digit 10— Build Location
A = Monterrey
8 RTAE-SVX001B-EN

General Information

Unit Description

The 150-300 ton Stealth™ units are helical-rotary type, air-
cooled liquid chillers designed for installation outdoors.
The compressor circuits are completely assembled,
hermetic packages that are factory-piped, wired, leak­tested, dehydrated, and tested for proper control operation before shipment.
Chilled water inlet and outlet openings are covered for shipment.The Stealth featuresTrane’s exclusive Adaptive Control ™ logic, which monitors the control variables that govern the operation of the chiller unit. Adaptive Control logic can adjust capacity variables to avoid chiller shutdown when necessary, and keep producing chilled water. All unit sizes are available with two independent refrigerant circuits. A single refrigeration circuit option is available for 150 and 165T units. Each compressor is controlled by a variable speed Adaptive Frequency™ Drive Generation 3 (AFD provided with filter, sight glass, electronic expansion valve, and charging valves.The shell-and-tube type evaporator is manufactured in accordance with ASME standards or other international codes. Each evaporator is fully insulated and is equipped with water drain and vent connection. As an option, a convenience outlet can be supplied.
Units are shipped with full oil charge and can be ordered with either a factory refrigerant charge, or optional nitrogen charge.
). Each refrigerant circuit is
3

Accessory/Option Information

Check all the accessories and loose parts which are shipped with the unit against the shipping list. Included in these items will be water vessel drain plugs, electrical diagrams, and service literature, which are placed inside the control panel for shipment.
If optional elastomeric isolators are ordered with unit (model number digit 36 = 1), they are shipped mounted on diagonal supports on the end of the unit opposite control panel. See Figure 3 and Figure 4.
If optional seismic isopads are selected (model number digit 36= 2), they will be shipped inside the unit control panel.
Figure 3. Elastomeric isolator shipping location
Figure 2. Typical Stealth RTAE
Elastomeric Isolator
Shipping Locations
(not all isolators shown ­quantity varies with unit configuration)
Figure 4. Elastomeric isolators attached for shipping
RTAE-SVX001B-EN 9

General Data

General Data
Table 1. General data table
Unit Size (tons) 150 165 180 200 225 250 275 300 150SC 165SC
Compressor Model CHHSR CHHSR CHHSR CHHSR CHHSS CHHSS CHHSS CHHSS CHHSS CHHSS
Quantity # 2 2 2 2 2 2 2 2 1 1
Evaporator
Water Storage (gal) 17.5 18.7 21.9 23.9 26.6 28.7 33.0 36.0 17.3 17.3
(L) 66.1 70.9 82.8 90.5 100.6 108.8 125.0 136.1 65.6 65.6
2 Pass arrangement
Minimum Flow (gpm) 171 187 202 228 261 288 318 354 169 169
(l/s) 10.8 11.8 12.7 14.4 16.5 18.2 20.1 22.3 10.7 10.7
Maximum Flow (gpm) 626 684 742 835 957 1055 1165 1299 620 620
(l/s) 39.5 43.1 46.8 52.7 60.4 66.5 73.5 81.9 39.1 39.1
3 Pass arrangement
Minimum Flow (gpm) 114 124 135 152 174 192 212 236 113 113
(l/s) 7.2 7.8 8.5 9.6 11.0 12.1 13.4 14.9 7.1 7.1
Maximum Flow (gpm) 417 456 495 557 638 703 777 866 414 414
(l/s) 26.3 28.8 31.2 35.1 40.2 44.3 49.0 54.6 26.1 26.1
Condenser
Qty of Coils 8 10 10 12 12 12 14 16 8 10
Coil Length (in) 78.74 78.74 78.74 78.74 78.74 78.74 78.74 78.74 78.74 78.74
(mm) 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000
Coil Height (in) 50 50 50 50 50 50 50 50 50 50
(mm) 1270 1270 1270 1270 1270 1270 1270 1270 1270 1270
Fins/Ft 192 192 192 192 192 192 192 192 192 192
Rows 3333333333
Condenser Fans
Quantity # 8 10 10 12 12 12 14 16 8 10
Diameter (in) 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5 37.5
(mm) 953 953 953 953 953 953 953 953 953 953
Total Airflow (cfm) 107,392 134,240 134,240 161,088 161,088 161,088 187,936 214,784 107,392 132,240
(m3/hr) 182,460 228,075 228,075 273,690 273,690 273,690 319,305 364,920 182,460 228,075
Tip Speed (ft/min) 8700 8700 8700 8700 8700 8700 8700 8700 8700 8700
(M/S) 44.2 44.2 44.2 44.2 44.2 44.2 44.2 44.2 44.2 44.2
Ambient Temperature Range
Standard Ambient °F (°C) 32 to 105 (0 to 40.6)
Low Ambient °F (°C) 0 to 105 (-17.7 to 40.6)
Extreme Low Ambient °F (°C) -20 to 105 (-28.9 to 40.6)
High Ambient °F (°C) 32 to 125 (0 to 52)
Wide Ambient °F (°C) 0 to 125 (-17.7 to 52)
General Unit
Refrigerant HFC-134a HFC-134a
Refrigerant Ckts # 2 1
Minimum Load % 20 18 17 15 20 18 16 15 30 27
Refrigerant Charge/ckt (lbs) 172 181 210 218 265 261 318 325 322 346
(kg) 78 82 95 99 120 118 144 148 146 157
Oil Trane OIL00311 (bulk)/OIL00315 (1 gal)/OIL00317 (5 gal)
Oil Charge/ckt (gal) 3.0 3.0 3.0 3.0 4.0 4.0 4.0 4.0 4.0 4.0
(L) 11.4 11.4 11.4 11.4 15.1 15.1 15.1 15.1 15.1 15.1
10 RTAE-SVX001B-EN

Drive Cooling System

Drive cooling fluid volumes are dependent on unit configuration.
Use Table 2 for units that meet the following criteria:
Model number digits 10, 11 = AA
Use Table 2 for units that meet the following criteria:
Model number digits 10, 11 = AB
AND Digits 28, 29 = 0X
Table 2. Drive cooling with load inductor
Unit Size (tons)
Standard Length Unit
150 165-200 225-250 275-300
gal l gal l gal l gal l
Fluid Type Trane Heat Transfer Fluid CHM01023 Fluid Volume
Ckt 1 1.74 6.58 1.83 6.92 2.00 7.58 2.09 7.92
Ckt2 1.93 7.30 2.27 8.59 2.44 9.24 2.58 9.78
Total 3.67 13.88 4.10 15.51 4.44 16.82 4.67 17.69
Use Table 2 for units that meet the following criteria:
Model number digits 10, 11 = AC
AND Digits 3-7 = 225, 250, 275 or 300
AND Digit 22=1or2
AND Digits 28, 29 = 0X
Use Table 3 for all other unit configurations.
General Data
Table 3. Drive cooling without load inductor
Unit Size (tons)
Standard Length Unit Extended Length Units
150S - 165S 150 165-250 275-300 150S - 165S 150 165-250 275-300
gal l gal l gal l gal l gal l gal l gal l gal l
Fluid Type Trane Heat Transfer Fluid CHM01023 Fluid Volume
Ckt 1 1.28 4.86 1.14 4.30 1.23 4.64 1.32 4.98 1.37 5.20 1.30 4.93 1.32 4.98 1.41 5.33
Ckt2 n/a n/a 1.32 5.01 1.67 6.31 1.81 6.84 n/a n/a 1.67 6.31 1.81 6.84 1.95 7.38
Total 1.28 4.86 2.46 9.31 2.89 10.95 3.12 11.83 1.37 5.20 2.97 11.23 3.12 11.83 3.36 12.71
(a) Units are extended length if either of the following are selected: Transformer (model number digit 28 = 1) Harmonic Filtration Option (model number digit 29 = 1)
Units without Harmonic Filtration Option or Transformer (digits 28, 29 = 0X) are standard length.
NOTICE:
Equipment Damage!
Use only Trane Heat Transfer Fluid P/N CHM01023. This fluid is a direct use concentration and is not to be diluted. Do not top off with water or any other fluid. Use of unapproved fluids, or dilution of approved fluid could result in catastrophic equipment damage.
Note: The use of incorrect compounds in the drive
cooling system may result in scaling, erosion, corrosion or freezing.TheTrane Company warranty specifically excludes liability for corrosion, erosion, freezing or deterioration of
Trane equipment.
Proper fluid level is important to the operation of the unit. See “Drive Cooling ExpansionTank,” p. 71 for fluid level
Non-Trane approved chemicals could react with system components and result in failure. Contact a qualified service technician and your localTrane Parts Center.
check instructions. The circuit capacities are shown in tables above.
If the level is below the recommended minimum levels, contact your localTrane office.
Note: Drive cooling fluid service life is 5 years. See“Drive
Cooling System,” p. 71.
(a)
RTAE-SVX001B-EN 11

Pre-Installation

Unit Inspection

When unit is delivered, verify it is the correct unit and is
properly equipped. Compare information on the unit nameplate with ordering and submittal information. Inspect all exterior components for visible damage.Report any apparent damage or material shortage to carrier and make a “unit damage” notation on carrier’s delivery receipt. Specify extent and type of damage found and notifyTrane Sales Office. Do not proceed with installation of a damaged unit without sales office approval.

Inspection

To protect against loss due to damage in transit, complete
the following steps upon receipt of unit.
Inspect the individual pieces of the shipment before
accepting the unit. Check for obvious damage to the unit or packing material.
Inspect the unit for concealed damage as soon as
possible after delivery and before it is stored. Concealed damage must be reported within 15 days.
If concealed damage is discovered, stop unpacking the
shipment. Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the carrier’s terminal of the damage
immediately, by phone and by mail. Request an immediate, joint inspection of the damage with the carrier and the consignee.
NotifyTrane sales representative and arrange for repair. Do not repair unituntil damage is inspectedby the carrier’s representative.

Storage

Extended storage of outdoor unit prior to installation requires these precautionary measures:
Store the outdoor unit in a secure area.
For units that have been charged with refrigerant, verify the following valves are closed on each circuit:
Suction service valve (butterfly valve)
Liquid line angle valve or EXV (EXV is driven closed
whenever circuit is powered)
Oil line shutoff valves to brazed plate heat
exchangers
Note: Units with factory refrigerant charge (model
number digit 15 = 1) are shipped with suction, liquid and oil line shutoff valves closed, isolating most of refrigerant charge in the evaporator. If unit goes directly into long term storage, it is recommended that these valve positions be confirmed.
For units with nitrogen charge option (model number digit 15 = 2), units are shipped with valves open. If unit goes directly into storage prior to refrigerant charge, confirm all service valves are open.
At least every three months (quarterly), check the pressure in the refrigerant circuits to verify that the refrigerant charge is intact. If it is not, contact a qualified service organization and the appropriate
Trane sales office.
12 RTAE-SVX001B-EN

Installation Requirements

A list of the contractor responsibilities typically associated with the unit installation process is provided in Table 4.
Table 4. Installation requirements
Pre-Installation
Type
Foundation • Meet foundation requirements
Rigging
Disassembly/Reassembly (as required)
Isolation
Electrical
Water piping • Flow switch
Insulation • Insulation • Insulation
Water Piping Connection Components • Grooved pipe
Other Materials
“Stealth™ RTAE Installation Completion Check Sheet and Request for Trane Service” (RLC-ADF002-EN, see “Log and Check Sheet,” p. 90)
Chiller Start-up Commissioning
(a) Trane, or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products, will perform or have direct on-site supervision of
the disassembly and reassembly work.
(b) Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane
provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the scheduled start-up.
(a)
(b)
Trane Installed
• Trane, or an agent of Trane specifically authorized to perform start-up of Trane products (contact your local Trane office for pricing)
• Circuit breakers (optional)
• Unit mounted starter
• R-134a refrigerant
• Dry nitrogen (optional)
• Trane, or an agent of Trane specifically authorized to perform start-up of Trane products
®
®
Trane Supplied
Trane Supplied Field Installed
• Elastomeric isolators (optional)
• Flange kit (optional)
Field Supplied Field Installed
• Safety chains
• Clevis connectors
• Lifting beam
• Spreader bar
• Elastomeric isolators (optional)
• Circuit breakers (optional)
• Electrical connections to unit mounted starter
• Wiring sizes per submittal and NEC
• Terminal lugs
• Ground connection(s)
• BAS wiring (optional)
• Control voltage wiring
• Chilled water pump contactor and wiring
• Option relays and wiring
• Taps for thermometers and gauges
• Thermometers
• Water flow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain
• Waterside pressure relief valves
• Water strainer
®
products. Contractor shall
RTAE-SVX001B-EN 13

Dimensions and Weights

Weights

Table 5. Weights
Standard Length Unit
Unit Size
(tons)
Shipping Operating Shipping Operating
lbs kg lbs kg lbs kg lbs kg
InvisiSound™ Standard or Superior
150S 9436 4280 9596 4353 11013 4995 11173 5068
165S 10451 4741 10611 4813 12011 5448 12171 5521
150 11333 5141 11479 5207 13492 6120 13638 6186
165 12377 5614 12533 5685 14532 6592 14688 6662
180 12698 5760 12880 5843 14853 6737 15035 6820
200 13808 6263 14007 6354 15991 7254 16213 7354
225 15244 6915 15466 7015 17427 7905 17649 8005
250 15622 7086 15861 7195 17805 8076 18044 8185
275 16820 7630 17095 7754 18975 8607 19250 8732
300 17965 8149 18265 8285 20121 9127 20421 9263
InvisiSound Ultimate
150S 10236 4643 10396 4716 11813 5358 11973 5431
165S 11251 5103 11411 5176 12811 5811 12971 5884
150 12133 5504 12279 5570 14292 6483 14438 6549
165 13177 5977 13333 6048 15332 6955 15488 7025
180 13498 6123 13680 6205 15653 7100 15835 7183
200 14608 6626 14807 6716 16791 7616 17013 7717
225 16044 7278 16266 7378 18227 8268 18449 8368
250 16422 7449 16661 7557 18605 8439 18844 8548
275 17620 7992 17895 8117 19775 8970 20050 9095
300 18765 8512 19065 8648 20921 9490 21221 9626
(a) Units are extended length if either of the following are selected: Transformer (model number digit 28 = 1) Harmonic Filtration Option (model number digit 29 = 1)
Units without Harmonic Filtration Option or Transformer (digits 28, 29 = 0X) are standard length. (b) Model number digit 12 = 1 or 2 (c) Model number digit 12 = 3
Extended Length Unit
(b)
(c)
(a)

Unit Dimensions

See unit submittals for specific unit dimensions and water connection locations.

Service Clearances

Figure 5. RTAE service clearances - top view
NO OBSTRUCTIONS ABOVE UNIT
Control
Panel
40”
(1016
mm)
See
note 1
85” (2160mm)
See note 2
36” (914.4mm)
24” (600.1mm)
14 RTAE-SVX001B-EN
NOTES:
1. A full 40” clearance is required in front of the control panel. Must be measured from front of panel, not end of unit base.
2. Clearance of 85” on the side of the unit is required for coil replacement. Preferred side for coil replacement is shown (left side of unit, as facing control panel), however either side is acceptable.

Installation Mechanical

Location Requirements

Sound Considerations

Refer toTrane Engineering Bulletin Chiller Sound Ratings and Installation Guide RLC-PRB035-EN for
sound consideration applications.
Locate the unit away from sound-sensitive areas.
Install the optional elastomeric isolators under the unit. See
Chilled water piping should not besupported by chiller frame.
Install rubber vibration isolators in all water piping.
Use flexible electrical conduit.
Seal all wall penetrations.
Note: Consult an acoustical engineer for critical

Foundation

Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the applicable operating weight (i.e., including completed piping, and full operating charges of refrigerant, oil and water). See Table 5, p. 14 for unit operating weights. Once in place, the unit must be level within 1/4”(6.4 mm) across the length and width of the unit.TheTrane Company is not responsible for equipment problems resulting from an improperly designed or constructed foundation.
“Isolation and Sound Emission,” p. 20.
applications.
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.
WARNING
Proper Lifting Configuration Required!
Use only lift locations designated with label shown in
Figure 6. Do NOT use locations marked with label
shown in Figure 7. Use unit lifting configurations as shown in Table 6 and Figure 8, p. 16 thru Figure 10,
p. 17. Other lifting arrangements could result in death,
serious injury or equipment damage.
Figure 6. Label - lift location

Clearances

Provide enough space around the unit to allow the installation and maintenance personnel unrestricted access to all service points. See submittal drawingsfor the unit dimensions, to provide sufficient clearance for the opening of control panel doors and unit service. See
Figure 5, p. 14 for minimum clearances. In all cases, local
codes which require additional clearances will take precedence over these recommendations.
For close spacing information, see RLC-PRB037-EN.
Rigging
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property-only damage.
X39003897001A
Figure 7. Label - do not lift
X39003894001A
Important:
Do not fork lift unit.
See unit nameplate and/or unit submittal for total
shipping weight.
See Table 6 and Figure 8 thru Figure 10 for unit lifting configuration.
See Table 7, p. 18 and Table 8, p. 19 for lift weights and dimensions at each lifting point locations.
See Table 9, p. 20 for center of gravity information.
RTAE-SVX001B-EN 15
Installation Mechanical
Table 6. Lifting configuration selection
Tons Unit Length
150S, 165S, 150 Standard and Extended
165, 180, 200, 225, 250 Standard
165, 180, 200, 225, 250 Extended
275 Standard
275 Extended
300 Standard and Extended
(a) Units are extended length if either of the following are selected: Transformer (model number digit 28 = 1) Harmonic Filtration Option (model number digit 29 = 1)
Units without Harmonic Filtration Option or Transformer (digits 28, 29 = 0X) are standard length.
Figure 8. 4-point lift configuration
96” (2438mm) Spreader Bar
(a)
Lift Configuration See
4-point Figure 8, p. 16
6-point Figure 9, p. 17
8-point Figure 10, p. 17
Control Panel
Lifting Location 1 (Lifting location 4 located on other side of unit)
Lifting Location 2 (Lifting location 3 located on other side of unit)
16 RTAE-SVX001B-EN
Figure 9. 6-point lift configuration
96” (2438mm) Spreader Bar
96”
(2438mm)
Spreader Bar
Installation Mechanical
Lifting Location 3 (Lifting location 4 located on other side of unit)
Lifting Location 2 (Lifting location 5 located on other side of unit)
Control Panel
Figure 10. 8-point lift configuration
96” (2438mm) Spreader Bar Qty 2
Control Panel
Lifting Location 1 (Lifting location 6 located on other side of unit)
Lifting Location 4 (Lifting location 5 located on other side of unit)
Lifting Location 3 (Lifting location 6 located on other side of unit)
Lifting Location 2 (Lifting location 5 located on other side of unit)
Lifting Location 1 (Lifting location 8 located on other side of unit)
RTAE-SVX001B-EN 17
Installation Mechanical
Table 7. Lift weights by location
Location
12345678
Tons lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
Standard Length Unit
150S 2540 1152 2451 1112 2164 981 2281 1034 - - - - - - - -
165S 2656 1205 2352 1067 2730 1238 2713 1230 - - - - - - - -
150 3426 1554 2638 1197 2234 1014 3035 1377 - - - - - - - -
165 3452 1566 2876 1304 2810 1275 3239 1469 - - - - - - - -
180 3528 1600 2941 1334 2896 1314 3333 1512 - - - - - - - -
200 3586 1627 3325 1508 3316 1504 3581 1624 - - - - - - - -
225 4003 1816 3551 1611 3617 1641 4073 1847 - - - - - - - -
250 4098 1859 3637 1650 3711 1683 4176 1894 - - - - - - - -
275 2484 1127 1943 881 3683 1671 3829 1737 2255 1023 2625 1191 - - - -
300 2061 935 2289 1038 2515 1141 1682 763 2729 1238 3008 1364 1737 788 1943 881
Extended Length Unit
150S 2698 1224 2597 1178 2837 1287 2881 1307 - - - - - - - -
165S 2988 1356 2841 1289 3135 1422 3047 1382 - - - - - - - -
150 3825 1735 3363 1525 2920 1324 3384 1535 - - - - - - - -
165 2653 1203 2629 1192 2570 1166 1959 889 2046 928 2675 1213 - - - -
180 2685 1218 2674 1213 2641 1198 1946 883 2100 953 2807 1273 - - - -
200 2919 1324 2640 1198 2797 1269 2846 1291 2274 1032 2514 1141 - - - -
225 3065 1391 2705 1227 3237 1468 3144 1426 2406 1091 2870 1302 - - - -
250 3117 1414 2749 1247 3322 1507 3229 1465 2458 1115 2930 1329 - - - -
275 2145 973 2668 1210 3279 1487 1513 686 2412 1094 2482 1126 1644 746 2831 1284
300 2056 933 2440 1107 3452 1566 2241 1017 3089 1401 2993 1358 1460 662 2389 1084
(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)
Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.
(a)
18 RTAE-SVX001B-EN
Installation Mechanical
Table 8. Lifting locations (from control panel end of frame)
Location
12345678
Tons in mm in mm in mm in mm in mm in mm in mm in mm
Standard Length Unit
150S 45.5 1156 45.5 1156 153.9 3909 153.9 3909 --------
165S 23.5 596 23.5 596 189.7 4818 189.7 4818 --------
150 39.6 1006 39.6 1006 171.4 4353 171.4 4353 --------
165 60.4 1534 60.4 1534 224.6 5705 224.6 5705 --------
180 60.4 1534 60.4 1534 224.6 5705 224.6 5705 --------
200 53.3 1355 53.3 1355 258.7 6570 258.7 6570 --------
225 53.3 1355 53.3 1355 258.7 6570 258.7 6570 --------
250 53.3 1355 53.3 1355 258.7 6570 258.7 6570 --------
275 75.8 1926 75.8 1926 190.7 4845 190.7 4845 311.9 7922 311.9 7922 - - - -
300 47.6 1210 47.6 1210 171.3 4350 171.3 4350 242.8 6168 242.8 6168 365.1 9274 365.1 9274
Extended Length Unit
150S 23.5 596 23.5 596 207.1 5261 207.1 5261 --------
165S 23.5 596 23.5 596 242.9 6170 242.9 6170 --------
150 44.7 1136 44.7 1136 224.6 5705 224.6 5705 --------
165 61.1 1552 61.1 1552 171.3 4350 171.3 4350 277.8 7057 277.8 7057 - - - -
180 61.1 1552 61.1 1552 171.3 4350 171.3 4350 277.8 7057 277.8 7057 - - - -
200 47.6 1210 47.6 1210 190.7 4845 190.7 4845 311.9 7922 311.9 7922 - - - -
225 47.6 1210 47.6 1210 190.7 4845 190.7 4845 311.9 7922 311.9 7922 - - - -
250 47.6 1210 47.6 1210 190.7 4845 190.7 4845 311.9 7922 311.9 7922 - - - -
275 75.8 1926 75.8 1926 182.0 4623 182.0 4623 258.5 6565 258.5 6565 365.1 9274 365.1 9274
300 47.6 1210 47.6 1210 168.5 4280 168.5 4280 296.1 7520 296.1 7520 418.3 10626 418.3 10626
(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)
Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.
(a)
RTAE-SVX001B-EN 19
Installation Mechanical

Center of Gravity

Figure 11. Center of gravity
CG
X
SIDE VIEW
CG
Z
Y
END VIEW
(Non-Control Panel End)
Table 9. Centers of gravity
CGx CGy CGz
Tons
150S 96.6 2454 43.8 1112 40.4 1025
165S 110.0 2793 45.2 1149 42.8 1087
150 105.5 2679 43.9 1115 37.5 953
165 142.4 3617 43.9 1115 39.7 1008
180 142.8 3628 43.9 1115 39.4 1002
200 155.5 3951 43.9 1115 41.2 1047
225 156.1 3964 43.9 1115 39.8 1011
250 156.4 3973 43.9 1115 39.7 1008
275 194.1 4930 43.9 1115 41.1 1043
300 207.1 5260 43.9 1115 42.4 1076
150S 118.8 3017 44.1 1121 37.2 944
165S 136.4 3464 44.7 1137 39.4 1002
150 134.7 3421 43.9 1115 33.3 846
165 169.1 4295 43.9 1115 35.4 898
180 169.9 4314 43.9 1115 35.2 894
200 181.6 4613 43.9 1115 36.9 937
225 183.6 4665 43.9 1115 36.0 915
250 184.2 4680 43.9 1115 36.0 913
275 220.2 5594 43.9 1115 37.4 950
300 232.3 5900 43.9 1115 38.7 984
(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)
Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.
in mm in mm in mm
Standard Length Unit
Extended Length Unit
(a)

Isolation and Sound Emission

The most effective form of isolation is to locate the unit
away from any sound sensitive area. Structurally transmitted sound can be reduced by elastomeric vibration eliminators. Spring isolators are not recommended. Consult an acoustical engineer in critical sound applications.
For maximum isolation effect, isolate water lines and electrical conduit.Wall sleeves and rubber isolated piping hangers can be used to reduce the sound transmitted through water piping.To reduce the sound transmitted through electrical conduit, use flexible electrical conduit.
State and local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound power levels for Stealth chillers are available on request.

Unit Isolation and Leveling

For additional reduction of sound and vibration, install the optional elastomeric isolators.
Construct an isolated concrete pad for the unit or provide concrete footings at the unit mounting points. Mount the unit directly to the concrete pads or footings.
Level the unit using the base rail as a reference.The unit must be level within 1/4-in (6 mm) over the entire length and width. Use shims as necessary to level the unit.
Elastomeric Isolators (Optional for units without seismic rating)
Note: See unit submittal, or Table 11, p. 21 thru Table 13,
p. 23 for point weights, isolator location and
isolator selections.
1. Secure the isolators to the mounting surface using the mounting slots in the isolator base plate. Do not fully tighten the isolator mounting bolts at this time.
2. Align the mounting holes in the base of the unit with the threaded positioning pins on the top of the isolators.
3. Lower the unit onto the isolators and secure the isolator to the unit with a nut.
4. Level the unit carefully. Fully tighten the isolator mounting bolts.
20 RTAE-SVX001B-EN
Installation Mechanical
5.
Figure 12. Elastomeric isolator
5.0 in
0.50 in
Mounting molded in neoprene
3.0 in
0.56 in
1.60 ± .25 in
2.75 in
1/2 - 13NC - 2B
4.63 in
Elastomeric Isolation Pads for Seismic Option
Elastomeric pads ship inside the unit control panel.They are provided with an isolation washer and 3/4” free hole in the center of the plate.
Figure 13. Seismic isolation pad — installed
Table 10. Seismically rated elastomeric isolation pad
Dimension (in)
Model Max Load Length Width Height
B-36 2520 6 6 .625
Figure 14. Mounting point locations
2468 10
(a)
0.38 in
Max Load
(lbs) Color
2250 RED 0.50 RDP-4
3000 GREEN 0.50 RDP-4
Maximum
Deflection (in) Type
Control panel
13579
(a) Quantity of isolators varies with unit. Shorter units will not use locations
5 and 6. See submittal for actual number required for specific unit.
Table 11. Point weights
Location
12345678910
Tons lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
Standard Length
150S 1731 785 1664 755 1834 832 1773 804 1219 553 1375 624 --------
165S 1666 756 1559 707 1886 855 1870 848 1914 868 1716 778 --------
150 1452 659 1543 700 1326 602 1446 656 1464 664 1350 612 1490 676 1262 572 ----
165 1539 698 1341 608 1622 736 1553 704 1657 752 1607 729 1522 690 1536 697 ----
180 1536 697 1338 607 1676 760 1620 735 1709 775 1659 753 1579 716 1581 717 ----
200 1442 654 1764 800 1696 769 1810 821 1836 833 1694 768 1986 901 1580 717 ----
225 1430 649 1792 813 1999 907 2058 933 2111 958 1994 905 2139 970 1721 781 ----
250 1426 647 1803 818 2064 936 2144 973 2182 990 2055 932 2195 996 1753 795 ----
275 1624 737 1627 738 1802 817 1746 792 1795 814 1530 694 1653 750 1831 830 1577 715 1634 741
300 1634 741 1850 839 1871 849 1925 873 1898 861 1938 879 1887 856 1695 769 1752 795 1515 687
RTAE-SVX001B-EN 21
Installation Mechanical
Table 11. Point weights (continued)
Location
12345678910
Tons lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg lb kg
Extended Length Unit
150S 1553 704 1795 814 1974 895 1959 889 2088 947 1804 818 --------
165S 1344 610 1236 561 1537 697 1494 678 1686 765 1668 757 1636 742 1570 712 ----
150 1563 709 1621 735 1705 773 1875 850 1952 885 1575 714 1601 726 1601 726 ----
165 1776 806 1827 829 1956 887 1925 873 2058 933 1958 888 1517 688 1515 687 ----
180 1774 805 1822 827 1990 903 1975 896 2128 965 2030 921 1577 715 1557 706 ----
200 1706 774 1524 691 1662 754 1294 587 1938 879 1738 788 1267 575 1753 795 1457 661 1652 749
225 1857 842 1669 757 1844 836 1412 640 2156 978 1860 844 1378 625 1985 900 1501 681 1766 801
250 1852 840 1664 755 1885 855 1439 653 2219 1006 1936 878 1438 652 2046 928 1530 694 1795 814
275 1874 850 1860 844 1626 737 1700 771 2204 1000 2101 953 2017 915 2131 967 1820 826 1642 745
300 1946 883 1826 828 1854 841 1795 814 2143 972 2106 955 2408 1092 2338 1060 1808 820 1898 861
(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)
Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.
(a)
Table 12. Isolator locations
(a)
Location
12345678910
Tons in mm in mm in mm in mm in mm in mm in mm in mm in mm in mm
Standard Length
150S 23.6 600 27.6 700 102.4 2600 94.5 2400 187.0 4750 187.0 4750 --------
165S 15.7 400 23.0 585 98.4 2500 102.2 2595 196.9 5000 204.7 5200 --------
150 24.4 620 11.8 300 47.2 1200 82.7 2100 100.4 2550 153.5 3900 188.2 4780 188.2 4780 ----
165 17.7 450 23.0 585 98.6 2505 102.2 2595 155.5 3950 190.6 4840 242.1 6150 242.9 6170 ----
180 17.7 450 23.0 585 98.6 2505 102.2 2595 155.5 3950 190.6 4840 242.1 6150 242.9 6170 ----
200 23.6 600 23.6 600 102.4 2600 137.8 3500 155.5 3950 198.8 5050 255.9 6500 263.8 6700 ----
225 23.6 600 23.6 600 102.4 2600 137.8 3500 155.5 3950 198.8 5050 255.9 6500 263.8 6700 ----
250 23.6 600 23.6 600 102.4 2600 137.8 3500 155.5 3950 198.8 5050 255.9 6500 263.8 6700 ----
275 21.7 550 18.9 480 141.3 3590 125.2 3180 196.1 4980 236.2 6000 236.2 6000 259.8 6598 328.0 8330 324.4 8240
300 19.7 500 27.6 700 143.1 3634 143.1 3634 202.4 5142 235.6 5984 257.9 6551 296.6 7534 347.8 8834 339.5 8624
Extended Length Unit
150S 19.7 500 15.7 400 102.4 2600 133.9 3400 204.7 5200 208.7 5300 --------
165S 23.6 600 23.6 600 86.6 2200 78.7 2000 149.6 3800 157.5 4000 259.8 6600 259.8 6600 ----
150 25.0 635 23.6 600 84.6 2150 98.4 2500 147.6 3750 190.9 4850 240.2 6100 240.2 6100 ----
165 19.7 500 19.7 500 129.9 3300 129.9 3300 204.7 5200 234.3 5950 293.3 7450 299.2 7600 ----
180 19.7 500 19.7 500 129.9 3300 129.9 3300 204.7 5200 234.3 5950 293.3 7450 299.2 7600 ----
200 25.6 650 19.7 500 118.1 3000 98.4 2500 208.7 5300 196.9 5000 255.9 6500 255.9 6500 315.0 8000 315.0 8000
225 25.6 650 19.7 500 118.1 3000 98.4 2500 208.7 5300 196.9 5000 255.9 6500 255.9 6500 315.0 8000 315.0 8000
250 25.6 650 19.7 500 118.1 3000 98.4 2500 208.7 5300 196.9 5000 255.9 6500 255.9 6500 315.0 8000 315.0 8000
275 6.3 160 9.8 250 177.2 4500 139.8 3550 198.8 5050 242.1 6150 309.1 7850 313.0 7950 354.3 9000 370.1 9400
300 9.8 250 9.8 250 177.2 4500 139.8 3550 206.7 5250 242.1 6150 311.8 7920 313.4 7960 393.7 10000 393.7 10000
(a) Dimensions are referenced from end of frame on the control panel side. (b) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)
Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.
(b)
22 RTAE-SVX001B-EN
Installation Mechanical
Table 13. Isolator selections
Location
Tons 1 2 3 4 5 6 7 8 9 10
Standard Length Unit
150S Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 - - - -
165S Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 - - - -
150 Red 62 Red 62
165 Red 62 Red 62
180 Red 62 Red 62
200 Red 62 Red 62
225 Red 62 Red 62
250 Red 62 Red 62
275 Red 62 Red 62
300 Red 62 Red 62
150S Red 62 Red 62 Green 63 Green 63 Green 63 Red 62 - - - -
165S Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 Red 62 - -
150 Red 62 Red 62
165 Red 62 Red 62
180 Red 62 Red 62
200 Red 62 Red 62
225 Red 62 Red 62
250 Red 62 Red 62
275 Red 62 Red 62
300 Red 62 Red 62
(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)
Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
Extended Length Unit
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Red 62 Red 62 - -
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
Green 63 Green 63 Green 63 Green 63 Green 63 Green 63 Red 62 Red 62
(a)

Compressor Shipping Bolt Removal

Units with InvisiSound™ Ultimate Option (Model Number Digit 12 = 3)

For chillers built with InvisiSound Ultimate option, compressor shipping bolts must be removed to assure minimum noise during operation. Use a 24mm socket to remove the (3) M15 x 75mm shipping bolts for each compressor.They are located under compressor mounting feet. See Figure 15.
Important:
DO NOT DISCARD SHIPPING BOLTS. Store bolts in the
control panel for future use.
All shipping bolts MUST be reinstalled prior to compressor removal or unit move.
Figure 15. Compressor shipping bolt removal
Isolator
Compressor
Compressor
Mounting
Foot
Shipping Bolt

Drainage

NOTICE:
Equipment Damage!
Do not remove compressor or move unit without reattaching compressor shipping bolts. Failure to reinstall bolts could cause shifting of parts and result in equipment damage.
RTAE-SVX001B-EN 23
Locate the unit near a large capacity drain for water vessel drain-down during shutdown or repair. Evaporators are provided with drain connections. A vent on top of evaporator waterbox prevents vacuum byallowing airinto evaporator for complete drainage. All local and national codes apply.
Installation Mechanical
Evaporator Piping
RTAE units are available with 2 or 3 pass configurations. See Figure 16.
Figure 16. Evaporator pass configurations
Control Panel End
Control Panel End
Outlet Waterbox
2-Pass Evaporators
Top V i ew
(Condenser removed for clarity)
3-Pass Evaporators
Top V i ew
(Condenser removed for clarity)
Inlet Water Connection
Outlet Water Connection
Inlet Waterbox
Outlet
End View
(Non-control panel end)
(Non-control panel end)
Inlet
End View
Inlet Waterbox (Outlet waterbox opposite end)
NOTICE:
Evaporator water connections are grooved.
Thoroughly flush allwater piping tothe unitbefore making
Proper Water Treatment!
The use of untreated or improperly treated water could
result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water.
the final piping connections to the unit.
Components and layout will vary slightly, depending on the location of connections and the water source.
A vent is provided on the top of the evaporator at the chilled water inlet. Be sure to provide additional vents at high points in the piping to bleed air from the chilled water system. Install necessary pressure gauges to monitor the entering and leaving chilled water pressures.
Provide shutoff valves in lines to the gauges to isolate
NOTICE:
Evaporator Damage!
The chilled water connections to the evaporator are to
be “victaulic” type connections. Do not attempt to weld these connections, as the heat generated from welding can cause microscopic and macroscopic fractures on the cast iron waterboxes that can lead to premature failure of the waterbox. To prevent damage to chilled water components, do not allow evaporator pressure (maximum working pressure) to exceed 150
them from the system when they are not in use. Use rubber vibration eliminators to prevent vibration transmission through the water lines.
If desired, install thermometers in the lines to monitor entering and leaving water temperatures. Install a balancing valve in the leaving water line to control water flow balance. Install shutoff valves on both the entering and leaving water lines so that the evaporator can be isolated for service
psig (10.5 bar).
24 RTAE-SVX001B-EN
Installation Mechanical

Evaporator Piping Components

operating safety. SeeThese components and their general locations are given below.
Piping components include all devices and controls used to provide proper water system operation and unit
Figure 17. Typical Stealth™ water piping
6
5
8
4
B
7
2
2
8
C
3
3
2
A
1
A
2
A
Table 14. Water piping components
Item Description Item Description
1 Bypass Valve Pi Pressure Gauge
2 Isolation Valve FT Water Flow Switch
3 Vibration Eliminator T1 Evap Water Inlet Temp Sensor
4 Evaporator - End View (2-pass) T2 Evap Water Outlet Temp Sensor
5 Evaporator Waterbox (2-pass)
6 Vent A Isolate unit for initial water loop cleaning
7 Strainer B Vent must be installed at the high point of the line
8 Drain C Drain must be installed at the low point of the line
NOTES
Entering Chilled Water Piping
Air vents (to bleed air from system).
Water pressure gauges with shutoff valves.
Vibration eliminators.
Shutoff (isolation) valves.Thermometers (if desired).
Clean-out tees.
Pipe strainer.
Leaving Chilled Water Piping
Air vents (to bleed air from system).
Water pressure gauges with shutoff valves.
Vibration eliminators.
Shutoff (isolation) valves.
Thermometers.
Drains
A 1/2” drain connection is located under outlet end of evaporator waterbox for drainage during unit servicing.A shutoff valve must be installed on drain line.
Pressure Gauges
Install field-supplied pressure components as shown in
Figure 17, p. 25. Locate pressure gauges or taps in a
straight run of pipe; avoid placement near elbows, etc. Be sure to install the gauges at the same elevation on each shell if the shells have opposite-end water connections.
To read manifolded pressure gauges, open one valve and
close the other (depending upon the reading desired).This eliminates errors resulting from differently calibrated gauges installed at unmatched elevations.
Clean-out tees.
Balancing valve.
RTAE-SVX001B-EN 25
Installation Mechanical

Pressure Relief Valves

NOTICE:
Evaporator Damage!
To prevent shell damage, install pressure relief valves in
the evaporator water system.
Install a water pressure relief valve in the evaporator inlet piping between the evaporator and the inlet shutoff valve, as shown in Figure 17, p. 25. Water vessels with close- coupled shutoff valves have a high potential for hydrostatic pressure buildup on a water temperature increase. Refer to applicable codes for relief valve installation guidelines.
Evaporator Flow Switch
NOTICE:
Equipment Damage!
Flow switch is on a 24V circuit. Do NOT apply 120V to the flow switch. Incorrect voltage application could cause damage to the flow switch.
The flow switch is factory-installed and programmed
based on the operating conditions submitted with the order.The leaving evaporator temperature, fluid type and fluid concentration affect the selected flow switch. If the operating conditions on the job site change, the flow switch may need to be replaced. Contact your localTrane Sales office for more information.
The sensor head includes 3 LEDs, two yellow and one
green.Wait 15 seconds after poweris applied to the sensor before evaluating LEDs for flow status. When wired correctly and flow is established, only the green LED should be lit. Following are the LED indicators:
Green ON, both yellow OFF — Flow
Green and outside yellow ON — No Flow
Center yellow ON continuously — Miswire
Factory installed jumper wire W11 must be removed if using auxiliary contacts and/or additional proof of flow. See schematics in RTAE-SVE01*-EN for more details.
Indexing Flow Switch
To properly index the flow switch, the following
requirements must be met:
The dot must be at a position no greater than 90° off Index.
The torque must be between 22 ft-lb minimum and 74 ft-lb maximum.
A minimum distance of 5x pipe diameter must be maintained between flow switch and any bends, valves, changes in cross sections, etc.
Figure 18. Proper flow switch indexing
Top V ie w
Flow
Index
The flow switch must have the dot in the shaded area to the left of this line for proper indexing (±90° off Index)
NOTICE:
Equipment Damage!
Incorrect wiring of auxiliary contacts could cause equipment damage.
If using auxiliary flow sensing, both yellow LEDs come on initially when flow is stopped.The center yellow LED will turn off after approximately 7 seconds.The LED indicators are otherwise the same as indicated above.
26 RTAE-SVX001B-EN

Evaporator Waterside Pressure Drop Curves

0
2.5
5
7.5
10
12.5
15
17.5
20
22.5
25
27.5
30
32.5
35
37.5
40
42.5
45
47.5
50
0 200 400 600 800 1000 1200 1400
Pressure Drop (ft. H2O)
Water Flow (GPM)
pp
300T
275T
250T
225T
200T
185T
165T
150T
150S, 165S
Figure 19. Evaporator waterside pressure drop curve — 2-pass
Installation Mechanical
RTAE-SVX001B-EN 27
Installation Mechanical
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
0 100 200 300 400 500 600 700 800 900 1000
Pressure Drop (ft. H2O)
Water Flow (GPM)
300T
275T
250T
225T
200T
185T
165T
150T
150S, 165S
Figure 20. Evaporator waterside pressure drop curve — 3-pass
28 RTAE-SVX001B-EN

Freeze Protection

One or more of the ambient freeze avoidance methods in
Table 15 must be used to protect the Stealth chiller from
ambient freeze damage.
Table 15. RTAC freeze avoidance methods
Protects to
Method
Water Pump Control AND Heaters
Freeze Inhibitor
Drain Water Circuit Below -20°F
ambient temperature Notes
Heaters alone will provide low ambient protection down to -20°F (-29°C), but will NOT protect the evaporator from freezing as a result of charge migration. Therefore, it is required that water pump control be used in conjunction with heaters.
• Heaters are factory-installed on the evaporator and water piping and will protect them from freezing
• Install heat tape on all water piping, pumps, and other components that may be damaged if exposed to freezing temperatures. Heat tape must be designed for low ambient temperature applications. Heat tape selection should be based on the lowest expected ambient temperature.
• Tracer™ UC800 controller can start the pump when freezing conditions are detected. For this option the pump must to be controlled by the Stealth unit and this function must be validated.
• Water circuit valves need to stay open at all times.
• Water pump control and heater combination will protect the evaporator down to any
Down to -20°F
Varies. See “Low
Evaporator Refrigerant Cutout, Glycol Requirements,” p. 30
ambient temperature provided power is available to the pump and the controller. This option will NOT protect the evaporator in the event of a power failure to the chiller unless backup power is supplied to the necessary components.
• When no chiller operation is possible and the pump is already off, UC800 pump control for freeze protection will command the pump to turn: ON if average of the evaporator entering water temperature, the evaporator leaving water temperature, and the evaporator refrigerant pool temperature is less than Low Evaporator Refrigerant Temperature Cutout (LERTC) + 4°F for a period of time. OFF again if the evaporator refrigerant pool temperature rises above the LERTC + 6°F for a period of time.
Note: Time period referenced for ON and Off conditions above is dependent on past running conditions and present temperatures measured.
ON if entering OR leaving water temperature< LWTC for 30°F-sec (17°C-sec) OFF again if water temperature > LWTC for 30 min
• Freeze protection can be accomplished by adding sufficient glycol to protect against freezing below the lowest ambient expected.
• Use of glycol type antifreeze reduces the cooling capacity of the unit and must be considered in the design of the system specifications.
• Shut off the power supply to the unit and to all heaters.
• Purge the water circuit.
• Blow out the evaporator to ensure no liquid is left in the evaporator.
Installation Mechanical
NOTICE:
Evaporator Damage!
If insufficient concentration or no glycol is used, the evaporator water flow must be controlled by the UC800
AND heaters must be used to avoid catastrophic
damage to the evaporator due to freezing. It is the responsibility of the installing contractor and/or the customer to ensure that a pump will start when called upon by the chiller controls. Refer to RLC-PRB012-EN. Even with water pump control, a power loss of as little as 15 minutes under freezing conditions can damage the evaporator. Only the proper addition of freeze inhibitor or complete drainage of the water circuit can ensure no evaporator damage in the event of a power failure.
RTAE-SVX001B-EN 29
Loading...
+ 67 hidden pages