Trane Start to Finish R-410A Installation Manual

Page 1
Installation Guide
Start to Finish™ R-410A Scroll Compressors
Model Numbers:
SFCOM090***4PSNAD SFCOM181***4PSNAD SFCOM300***4PSNAN SFCOM109***4PSNAD SFCOM182***4PSNAN SFCOM301***4PSNAN SFCOM121***4PSNAD SFCOM183***4PSNAN SFCOM360***4PSNAN SFCOM145***4PSNAD SFCOM240***4PSNAN SFCOM361***4PSNAN SFCOM156***4PSNAD SFCOM241***4PSNAN
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
August 2020
PART-SVN234B-EN
Page 2
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTIONs
NOTICE
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants—including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation whi result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
ch, if not avoided, could
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PP undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, flash, technicians with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
refer to the appropriate SDS and OSHA/GHS
E required for the work being
MUST put on all PPE in accordance
or
© 2020 Trane PART-SVN234B-EN
Page 3
Introduction
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Trane personnel must follow the company’s E
nvironmen when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
Non-Trane personnel should always follow local lations.
regu
tal, Health and Safety (EHS) policies
WARNING
R-410A Refrigerant under Higher Pressure than R-22!
Failure to use proper equipment or components as described below, could result in equipment failing and possibly exploding, which could result in death, serious injury, or equipment damage. The units described in this manual use R-410A refrigerant which operates at higher pressures than R-22. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your local Ingersoll Rand representative.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
WARNING
Hazard of Explosion!
Failure to follow instructions below could result in death or serious injury or equipment or property-only damage. Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from p
otential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
WARNING
Hazardous Conditions!
Failure to follow these instructions could result in death or serious injury or damage to the equipment. Observe and follow the “Warning” and “Notices” labels on the compressor.
NOTICE
Use Proper Charging and Crankcase Heater Operation Procedures!
Failure to utilize proper charging and crankcase heater procedure will result in compressor failure. Refer to unit Installation, Operation, and Maintenance manual and this manual for the proper procedures.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes
PART-SVN234B-EN 3
Page 4
Introduction
to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Updated for Trane Technologies.
4 PART-SVN234B-EN
Page 5
Table of Contents
Model Number Descriptions . . . . . . . . . . . . . . 6
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . 8
General Information . . . . . . . . . . . . . . . . . . . . 17
POE Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Oil Handling . . . . . . . . . . . . . . . . . . . . . . . 17
Oil Level . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Operating Envelope . . . . . . . . . . . . . . . . . . . 17
Refrigerant Type . . . . . . . . . . . . . . . . . . . . 18
Transportation, Handling, and Storage . . 18
Pre-Installation Inspections . . . . . . . . . . . 19
Repair Recommendations . . . . . . . . . . . . . 20
Mechanical Failure . . . . . . . . . . . . . . . . . . 20
Electrical Failure . . . . . . . . . . . . . . . . . . . . . . 21
Two Types of Motor Failures . . . . . . . . . 21
Removal and Installation . . . . . . . . . . . . . . . . 22
Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Compressor Replacement—Tandem and Trio
Compressor Sets . . . . . . . . . . . . . . . . . . . 23
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Electrical Connections . . . . . . . . . . . . . . . . . 25
Leak Detection . . . . . . . . . . . . . . . . . . . . . . . 26
Vacuum Testing and Evacuation . . . . . . . . 27
Charging the System . . . . . . . . . . . . . . . . . . 28
Verification Before Start-Up . . . . . . . . . . . . 28
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . 31
182–361 Nominal Capacity Compressor Mo-
tor Protection Module Diagnosis . . . . . . 32
Log Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Replacement Scroll Compressors . . . . . . . 34
Log Sheet for Installers . . . . . . . . . . . . . . 34
Systems Check . . . . . . . . . . . . . . . . . . . . . 35
Operating Controls Check . . . . . . . . . . . . 35
Observations . . . . . . . . . . . . . . . . . . . . . . . 35
PART-SVN234B-EN 5
Page 6
Model Number Descriptions
Digit 1, 2 — Brand
SF = Start to Finish™
Digit 3, 4, 5 — Unit Type
COM= Scroll Compressor
Digit 6, 7, 8 — Nominal Capacity
090 = 85 MBtu/h 109 = 101 MBtu/h 121 = 117 MBtu/h 145 = 137 MBtu/h 156 = 158 MBtu/h 181 = 178 MBtu/h 182 = 176 MBtu/h, 115/230V Module 183 = 176 MBtu/h, 24V Module 240 = 237 MBtu/h, 115/230V Module 241 = 237 MBtu/h, 24V Module 300 = 298 MBtu/h, 115/230V Module 301 = 298 MBtu/h, 24V Module 360 = 359 MBtu/h, 115/230V Module 361 = 359 MBtu/h, 24V Module
Digit 9, 10, 11 — Electrical Code
230 = 200–230/60/3 460 = 460/60/3 575 = 575/60/3
Digit 12 — Refrigerant
2=R-22 4 = R-410A
Digit 13 — Lubricant
M= Mineral Oil P = Polyolester (POE) Oil
Digit 14 — Connection Type
R=Rotolock S = Stub Tube
Digit 15 — Motor Protection
E = External Protection N = Internal Protection
Digit 16 — Revision Level
A = Initial Release
Digit 17 — Bill of Material
D N
6 PART-SVN234B-EN
Page 7
Overview
The purpose of this document is to provide installation and service information for Start to Finish™ R-410A compressors.
This document is not meant to be provide a step-by-step
ocedure, but is intended to identify procedures or
pr precautions that may be unique to a Start to Finish R-410A compressor and should be taken into account to properly and safely remove, install, and troubleshoot the compressor.
Each installation has its unique set of circumstances
which
also must be taken into account by the service technician.
Table 1. Available Start to Finish™ compressors
Model Number Service Part Number
SFCOM0905754PSNAD SFCOM090-5754AD
SFCOM0902304PSNAD
SFCOM0904604PSNAD SFCOM090-4604AD
SFCOM1095754PSNAD SFCOM109-5754AD
SFCOM1092304PSNAD SFCOM109-2304AD
SFCOM1094604PSNAD SFCOM109-4604AD
SFCOM1215754PSNAD SFCOM121-5754AD
SFCOM1212304PSNAD SFCOM121-2304AD
SFCOM1214604PSNAD SFCOM121-4604AD
SFCOM1455754PSNAD SFCOM145-5754AD
SFCOM1452304PSNAD SFCOM145-2304AD
SFCOM1454604PSNAD
SFCOM1565754PSNAD SFCOM156-5754AD
SFCOM1562304PSNAD
SFCOM1564604PSNAD SFCOM156-4604AD
SFCOM1815754PSNAD SFCOM181-5754AD
SFCOM1812304PSNAD SFCOM181-2304AD
SFCOM1814604PSNAD
SFCOM1825754PSNAN SFCOM182-5754AN
SFCOM1832304PSNAN
SFCOM1822304PSNAN SFCOM182-2304AN
SFCOM1834604PSNAN SFCOM183-4604AN
SFCOM1824604PSNAN SFCOM182-4604AN
SFCOM2415754PSNAN SFCOM241-5754AN
SFCOM2405754PSNAN SFCOM240-5754AN
SFCOM2412304PSNAN SFCOM241-2304AN
SFCOM2402304PSNAN SFCOM240-2304AN
SFCOM2414604PSNAN SFCOM241-4604AN
SFCOM2404604PSNAN SFCOM240-4604AN
SFCOM3005754PSNAN SFCOM300-5754AN
SFCOM3012304PSNAN SFCOM301-2304AN
SFCOM3002304PSNAN SFCOM300-2304AN
SFCOM3014604PSNAN SFCOM301-4604AN
SFCOM3004604PSNAN
SFCOM3615754PSNAN SFCOM361-5754AN
SFCOM3605754PSNAN SFCOM360-5754AN
SFCOM090-2304AD
SFCOM145-4604AD
SFCOM156-2304AD
SFCOM181-4604AD
SFCOM183-2304AN
SFCOM300-4604AN
Table 1. Available Start to Finish™ compressors
Model Number Service Part Number
SFCOM3612304PSNAN
SFCOM3602304PSNAN SFCOM360-2304AN
SFCOM3614604PSNAN SFCOM361-4604AN
SFCOM3604604PSNAN SFCOM360-4604AN
SFCOM361-2304AN
PART-SVN234B-EN 7
Page 8
Dimensional Data
Figure 1. SFCOM090 compressors
APPLICATION SFCOM090
REFRIGERANT R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 85.1 POWER INPUT (KW) 8.67 EER (BTU/W-HR) 9.82
Note: Fittings and connection part descriptions are
shown in
8 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 9
Figure 2. SFCOM109 and SFCOM121 compressors
Dimensional Data
APPLICATION SFCOM109 SFCOM121
REFRIGERANT R410A R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 101.0 117.1 POWER INPUT (KW) 10.15 11.58 EER (BTU/W-HR) 9.95 10.11
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN 9
Figure 13 and Figure 14, p. 19.
Page 10
Dimensional Data
Figure 3. SFCOM145 compressors
APPLICATION SFCOM145
REFRIGERANT R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 137.3 POWER INPUT (KW) 13.48 EER (BTU/W-HR) 10.18
Note: Fittings and connection part descriptions are
shown in
10 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 11
Figure 4. SFCOM156 compressors
APPLICATION SFCOM156
REFRIGERANT R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 158.2 POWER INPUT (KW) 15.33 EER (BTU/W-HR) 10.32
Dimensional Data
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN 11
Figure 13 and Figure 14, p. 19.
Page 12
Dimensional Data
Figure 5. SFCOM181 compressors
APPLICATION SFCOM181
REFRIGERANT R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 177.7 POWER INPUT (KW) 17.04 EER (BTU/W-HR) 10.43
Note: Fittings and connection part descriptions are
shown in
12 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 13
Figure 6. SFCOM182 and SFCOM183 compressors
Dimensional Data
APPLICATION SFCOM182 SFCOM183
REFRIGERANT R410A R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 176.2 176.2 POWER INPUT (KW) 17.36 17.36 EER (BTU/W-HR) 10.15 10.15
PROTECTION CONTROL MODULE
VAC 115/230 24
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN 13
Figure 13 and Figure 14, p. 19.
Page 14
Dimensional Data
Figure 7. SFCOM240 and SFCOM241 compressors
APPLICATION SFCOM240 SFCOM241
REFRIGERANT R410A R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 237.4 237.4 POWER INPUT (KW) 23.46 23.46 EER (BTU/W-HR) 10.12 10.12
PROTECTION CONTROL MODULE
VAC 115/230 24
Note: Fittings and connection part descriptions are
shown in
14 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 15
Figure 8. SFCOM300 and SFCOM301 compressors
Dimensional Data
APPLICATION SFCOM300 SFCOM301
REFRIGERANT R410A R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 298.2 298.2 POWER INPUT (KW) 29.75 29.75 EER (BTU/W-HR) 10.02 10.02
PROTECTION CONTROL MODULE
VAC 115/230 24
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN 15
Figure 13 and Figure 14, p. 19.
Page 16
Dimensional Data
Figure 9. SFCOM360 and SFCOM361 compressors
APPLICATION SFCOM360 SFCOM361
REFRIGERANT R410A R410A U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR) 358.9 358.9 POWER INPUT (KW) 36.10 36.10 EER (BTU/W-HR) 9.94 9.94
PROTECTION CONTROL MODULE
VAC 115/230 24
Note: Fittings and connection part descriptions are
shown in
16 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 17
General Information
Table 2. Torque values
Item Torque
Rotolock equalizer nut 1-3/4 and 2-1/4
Terminal screws #10-32 X 0.5 in
Terminal stud 2.75 ± 0.25 N·m; 30 ± 2 in·lb
Terminal stud nut
Ground screw 1.90 ± 0.25 N·m; 17 ± 2 in·lb
Terminal box cover 2.15 ± 0.25 N·m; 19 ± 2 in·lb
133 ± 10 N·m; 98 ± 7 ft·lb
2.75 ± 0.25 N·m; 25 ± 2 in·lb
3.4 ± 0.25 N·m; 30 ± 2 in·lb
Note: With Rotolock fittings, always use two wrenches:
one to back-up on the sleeve and one to tighten the nut. Proper torquing of the Rotolock nut is important to ensure a leak-free joint.
POE Oil
Table 3. Factory oil charge
Nominal Capacity Pints Liters Part Number
090 6.3 3.0 OIL00078, OIL00080
109–156 7.0 3.3
181 7.6 3.6 OIL00078, OIL00080
182–301 14.2 6.7 OIL00078, OIL00080
360–361 15.2 7.2 OIL00078, OIL00080
Notes:
1. OIL00078—1 quart container
2. OIL00080—1 gallon container
3. Oil amount and type is also pri
nted on the nameplate.
OIL00078, OIL00080
The oil should be visible through the oil sightglass both during operation and when the compressor(s) is off. Oil level slightly below the sightglass, but still visible is acceptable.
Single compressor. The oil level should be stable in the
sightglass.
Tandem and trio compressors. OperationThe oil
level will vary depending on the operating condition.
Unloaded condition
The running compressor will
have a higher oil level than the off compressor(s).
Loaded condition
Oil should be visible through all
of the compressor sight glasses. Some may have a higher level than others, but this is not abnormal.
After several minutes, the oil levels should be the
Off same in each compressor and should be visible in the sightglass. This is the best method to determine if the system has sufficient oil.
Units overcharged with oil will operate with degraded
erformance and co
p
uld lead to compressor damage.
Operating Envelope
The compressor must be operated within the published operating envelope.
Oil Handling
POE oil is very hygroscopic, which means it absorbs moisture very readily. Therefore, it is important to properly handle the oil.
POE Oil handling guidelines
Always use the smallest container size required for the job requirements.
Always leave the oil container tig of use
.
Do not reuse oil that has been opened.
htly sealed until time
Oil Level
Figure 10. Compressor oil label
PART-SVN234B-EN 17
Page 18
R410A Operating Map - Superheat 20F
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
-30 -20 -10 0 10 20 30 40 50 60 70
Evaporating temperature (°F)
Condensing temperature (°F)
R410A Operating Map - Superheat 20F
General Information
Figure 11. Operating envelope
Refrigerant Type
Start to Finish™ compressors are approved for use with R-410A refrigerant only. Any use of hydrocarbon refrigerants or air is strictly prohibited!
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing
Transportation, Handling, and Storage
operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the
The compressor must be handled in the vertical position (maximum 15-degree offset from vertical). Should the compressor be handled in an upside down position, its suitability for its use can not be guaranteed.
Improper Handling!
Improper handling of the compressor resulting from being handled or transported in the upside position, dropped or tipped over could result in internal damage to the compressor and it is recommended that the compressor not be put into service.
Damage to compressor or packag to the shipper immediately.
Use a proper method of lifting the compressor, both lifting ears must be used with a spread
18 PART-SVN234B-EN
NOTICE
ing should be
er bar.
reported
cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
For approximate compressor weight, see
WARNING
Table 4, p. 19.
Page 19
General Information
Oil equalizer Rotolock connection fitting
1/4 Schrader port
Oil drain valve
Sightglass
Oil equalizer Rotolock connection fitting
1/4 Schrader port
Sightglass
Spreader bar use is recommended to better balance the compressor.
Figure 12. Lifting compressor with spreader bar
lifting hooks with close clasps.
Use
Table 4. Compressor weight with full oil charge
Nominal Capacity Weight (lb)
090 128
109–121
145 148
156 152
181 155
182–183 234
240–241 238
300–301 337
360–361 362
142
Figure 13. Nominal capacity 182–361
Figure 14. Nominal capacity 090–181
The compressor and its packaging must not be exposed to rain and/or corrosive, flammable atmosphere.
The compressor must not be stored in an environment less than -31°F (-35°C) or to exceed +160°F (+71°C).
Pre-Installation Inspections
Check the following before using the compressor:
Compressor for visible shipping damage.
Compressor is the correct mo
del/part number.
Compressor is the correct voltage.
Compressor ship-with items:
– Restrictors for use with tandem and trio
compressors.
®
– Oil equalizer Teflon
gaskets.
WARNING
R-410A Refrigerant under Higher Pressure than R-22!
Failure to use proper equipment or components as described below, could result in equipment failing and possibly exploding, which could result in death, serious injury, or equipment damage. The units described in this manual use R-410A refrigerant which operates at higher pressures than R-22. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your local Ingersoll Rand representative.
PART-SVN234B-EN 19
Page 20
Oil equalizer Rotolock connection fitting
Oil equalizer lines
TANDEM
TRIO
General Information
Suggested area to cut the refrigerant lines so that they can be reinstalled
Figure 15. Tandem and Trio
Other modification may cause oil return issues and lead to compressor failure. Cut the lines in a convenient place, remove the compressor, and then unbraze the lines from the compressor. On reinstallation, reinstall lines to compressor and reassemble the cut lines utilizing a slip coupling. See to cut the
Figure 16. Suggested areas to cut refrigerant lines
Figure 16 for suggested area
discharge and suction l
ine.
Repair Recommendations
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
Mechanical Failure
Replace only the failed compressor in a tandem or trio set.
Important: On tandem or
20 PART-SVN234B-EN
and discharge lines must NOT be modified, except for the use of slip joint couplings.
trio assemblies, the suction
Minimize system and compressor open times to avoid excessive moisture absorption by the POE oil. Maximum suggested open time is 15 minutes.
Drain and replace oil in all the non-failed compressors.
Note: Fo
The 182–361 nominal capacity compressor has an with a Schrader® valve that can be used to remove the oil (see
Replace unit liquid line filter-drier. T part of controlling moisture in R-410A POE oil systems.
Reuse the compressors mounting isolators or mounting spacers that a assembly.
Braze the compressor into connections ar silver, with paste flux to make the copper tube connections to the compressor.
r 090–181 nomnial capacity compressors, this requires removing through the oil equalizer Rotolock fitting (see
Figure 14, p. 19). Use a dedicated device for
removing oi device with clean oil prior to use.
Figure 13, p. 19).
re used with the existing compressor
e copper-plated steel. Use BAg-28, 40%
oil using a suction device
l. It is good practice to flush the suction
his is a very important
the system. Compressor
oil drain
Page 21
General Information
Nominal Capacity “X” Distance
090–181 10 inches
182–361 tandem 16 inches
182–361 trio 25 inches
X Minimum Distance
Proceed as described in the following sections:
“Leak Detection,” p. 26
“Vacuum Testing and Evacuation,” p. 27
“Charging the System,” p. 28
“Verification Before Start-Up,” p. 28
Electrical Failure
Replace only the failed compressor in a tandem or trio set.
Drain and replace the oil in all the non-failed compressors.
Reuse the compressors mounting isolators or mounting
rs that are
space assembly.
Braze compressor into the system. Compressor connections are copper-plated steel. Use silver, with paste flux to make the copper tube connections to the compressor.
Important: On
Minimize system and compressor open times to avoid excessive suggested open time is 15 minutes.
Test the acid condition of the oil in the compressors using
acid
test kit. Use Part Numbers KIT06815, CHM00414,
an and KIT06754.
Two Types of Motor Failures
Light. If oil test kit is negative and oil is only slightly
discolored, treat in the same manner as a mechanical failure.
Severe. If oil test kit is positive with strong pungent odor
and dark oil, drain and replace oil in all of the non-failed compressors.
Reuse the compressor mounting isolators or mounting
rs that are
space assembly.
This type of failure requires changing both the suction and
iquid line
l facilitate changing filter-driers, if required.
Install the suction filters no closer than the distance listed in the table following from the centerline
p. 20).
PART-SVN234B-EN 21
used with the existing compressor
BAg-28, 40%
tandem or trio assemblies, the suction and discharge lines must not be modified, except for the use of slip joint couplings. Other modification may cause oil return issues and lead to compressor failure. Cut the lines in a convenient place, remove the compressor then unbraze the lines from the compressor. On reinstallation, reinstall lines to compressor and reassemble the cut lines with a slip coupling. See
r suggested area to cut the discharge
fo
p. 20
and suction
moisture absorption by the POE oil. Maximum
used with the existing compressor
filter-driers. Use replaceable filter-drier cores to
line.
Figure 17. The distance is measured
of the suction inlet tee (see
Figure 16,
Figure 16,
Braze compressor into the system. Compressor connection silver, with paste flux to make the copper tube connections to the compressor.
Proceed as described in the following sections:
“Leak Detection,” p. 26
“Vacuum Testing and Evacuation,” p. 27
“Charging the System,” p. 28
“Verification Before Start-Up,” p. 28
Figure 17. Minimum distance b
1. Use acid removal type filter-drier cores in both the suction filter and liquid line filter drier.
2. Change when the pressure drop exceeds 4 psig.
s are copper-plated steel. Use BAg-28, 40%
efore installation
suction line filter
182–361 nominal capacity models
Test oil after 24 hours of operation. Change filter-drier again if required. If oil is still acid, drain and replace oil in all the non-failed compressors.
After system is clean, test kit in su
ction clean up filter-drier and replace the liquid line drier
with standard filter drier cores.
dicates okay, remove the
090–181 nominal capacity models
Since these compressors do not have an oil drain valve, it is recommended that after 24 hours of operation, the filter­drier cores be replaced with acid removal filter-drier cores. Operate the system for another 24 hours before changing to remo filter-drier in the liquid line.
ve the suction filter-drier and install a standard
of
Page 22
Removal and Installation
WARNING
Removal
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non­approved refrigerants, refrigerant substitutes, or refrigerant additives.
Pressurized Burning Fluid!
Failure to follow these instructions could result in death or serious injury. Before opening a system, you must remove refrigerant from both the high and low sides of the system. If the pressure is not removed from both sides of the system, pressure could still exist in the system. If a torch is used to unbraze the tubing, the refrigerant and oil mixture could ignite.
WARNING
Contains Refrigerant! R-410A Refrigerant under Higher Pressure than R-22!
Failure to use proper equipment or components as described below, could result in equipment failing and possibly exploding, which could result in death, serious injury, or equipment damage. The units described in this manual use R-410A refrigerant which operates at higher pressures than R-22. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your local Ingersoll Rand representative.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
Only qualified personnel should install or repair refrigeration systems. If you are not qualified, seek the services of qualified personnel. The steps listed below are not meant to be an exact step-by-step procedure, but are intended to identify procedures or precautions that may be unique to a Start to Finish™ compressor and should be taken into account to properly and safely remove and install the compressor. Each installation has its unique set of circumstances which must be considered by the service technician to perform a safe and successful compressor replacement.
22 PART-SVN234B-EN
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge of
capacitors, see PROD-SVB06*-EN.
Prior to removing the compressor, open th disconnect and place a lock on the disconnect to prevent someone else from accidentally applying power to the unit while it is under repair.
Completely recover the refrigerant fr om the refrigerant
t being rep
circui atmosphere! Use Responsible Refrigerant Practices. If adding or removing refrigerant, the service technician must comply with all Federal, State, and local laws.
Before removing the electrical connections on the
mpressor u
co power on:
Compressor power terminals.
Compressor motor protection module.
After confirming the absen electrical connections.
– Mark the electrical wires so they can
– 090–181 nominal capacity com
Remove oil prior to compressor
– 182–361 Nomi
se a voltmeter to check for the absence of
on the same terminal on the replacement compressor to prevent improper phasing.
bl
ocks are marked: T1 is marked red, T2 is marked
blue, and T3 has no mark (see
–361 nominal capacity compressors have an
182 oil drain
WARNING
WARNING
e unit
aired. Do not release refrigerant to the
ce of power, r
removal:
nal Capacity Compressors
valve (see
Figure 13, p. 19) that allows
emove the
be placed back
pressor terminal
Figure 21, p. 26).
Page 23
Removal and Installation
oil to be drained out of the compressor. After the refrigerant has been recovered, pressurize the system with nitrogen to help remove oil from the compressor.
If the
– 090–181 Nominal Capacity Compressors
Note: F
Fo
If
Tip: Befor
compressor, apply flux to the joint. This will aid in the flow of the braze material and help keep the joint clean for rebrazing. After fluxing, heat the joint evenly to slightly higher temperature than the melting temperature of the filler material. At this point, the two parts of the assembly should be easily separated.
Refrigerant Connection Removal
– Single compressor—Cut the refrigerant lines in a
co slip couplings. Then, unbraze the line from the compressor and reuse it when the replacement is installed.
Whe
T
compressor is in a tandem or trio set, place a catch pa connection on the compressor to catch the oil from the oil equalizer tube or compressor when the oil equalizer tube is removed.
r 090–181 nominal capacity compressors, oil removal requires using a suction or pump device through the oil equalizer Rotolock fitting, see with clean oil prior to use.
the compressor is in a tandem set, place a catch pan unde connection fitting on the compressor to catch the oil from the compressor when the oil equalizer tube is removed. Refer to
p. 19
connection fitting.
e removing the existing tubing from the
nvenient
on the cap of the compressor with a spreader bar (see
he lifting device must be rated to handle the
weight compressor
n under the oil equalizer Rotolock
or excess oil removal, the Schrader valve in the lower part of can be used. If more oil or the complete oil charge needs to be removed, use the following procedure.
Figure 14, p. 19. Flush the suction device
r the oil equalizer Rotolock
for the location of the oil equalizer Rotolock
location that allows reassembly with
n removing the compressor use both hooks
Figure 12, p. 19).
the compressor shell
Figure 14,
as listed in
Table 4, p. 19.
There are special considerations that are unique to replacing compressors in a tandem or trio set:
1. Only replace the failed compressor.
2. On tandem or trio assemblies, the discharge lines must not be modified, except for the use of slip-joint couplings. Other modifications may cause oil return issues and lead to compressor failure. Cut the lines in a convenient place, remove the compressor, and then unbraze the lines from the compressor. On re-installation, reinstall lines to compressor and reassemble the cut lines using a slip coupling. Refer to to cut the
Tip: Before removing the existing tubing from the
3. Change oil in all compressors in the tandem or trio
mpressors whenever there is a failure.
co
a. 182–361 Nominal Capacity—Use the oil charging
b. 090–181 Nominal Capacity—Remove the oil
Important: So
discharge and suction line.
compressor, apply flux to the joint. This will aid in the flow of the braze material and help keep the joint clean for re-brazing. After fluxing, heat the joint evenly to slightly higher temperature than the melting temperature of the filler material. At this point, the two parts of the assembly should be easily separated.
lve on the compressor.
va
equalizer fitting and use a suction or pump device to remove the oil from the compressor through the oil equalizer tube opening. A suction type device should be used to remove oil from the compressor.
require a restrictor be placed in the suction inlet to balance the oil levels. Refer to unit Installation, Operation, and Maintenance manual for correct size and location of restrictor. The restrictors are packaged in a bag with a label with the part number and diameter required (see The internal diameter in millimeters is Ø31. The restrictor is also marked on the face with both the extension number, last three digits of the part number, and diameter. For the previous example, the restrictor would be marked 010-31. Without the proper restrictor installed, the compressor oil level balance will not be correct.
Figure 16, p. 20 for suggested area
me mult
part number is X17311028010 and the
iple compressor configurations
suction and
Figure 18, p. 24).
Compressor Replacement—Tandem and Trio Compressor Sets
Definitions:
Tandem—Two compressors on a sing circuit.
Trio—Three compressors on a single refriger circuit.
PART-SVN234B-EN 23
le refrigerant
ant
Incorrect Restrictor Size and Location!
Failure to install the correct size restrictor or in the correct position will lead to improper oil levels in the compressor. This could result in a compressor failure due to low oil level.
NOTICE
Page 24
Removal and Installation
4. It will be necessary to use an oil catch pan under the oil equalizer connection to catch the oil when the connection is loosened and removed.
Figure 18. Restrictor label
Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge of capacitors,
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
Only qualified personnel should install or repair refrigeration systems. If you are not qualified, seek the services of qualified personnel.
Pressure tests must be performed by qualified
rsonnel.
pe
T
he replacement compressor contains a nitrogen charge of 5 psig. Before opening the connections on the compresso Schrader fitting on the shell to slowly release the nitrogen charge in the compressor.
see PROD-SVB06*-EN.
WARNING
r, connect a 1/4-inch service hose to the
Remove the suction plug before the discharge plug to avoid oil spray while opening the compressor.
Keep exposure to the atmosphere at a minimum due to
E oil. Remove th
PO install the compressor. Plug other compressor on tandem or trio compressors.
fore removing the oil equalizer connection ca
Be
• place a can pan under the Rotolock fitting as the compressor oil level is above the Rotolock connection. Oil must be added to the compressors after installation.
a. Removal Instructions
Tip: Be
fore removing the existing tubing from the compressor, apply flux to the joint. This will aid in the flow of the braze material and help keep the joint clean for rebrazing. After fluxing, heat the joint evenly to slightly higher temperature than the melting temperature of the filler material. At this point, the two parts of the assembly should be easily separated.
b. Installation
c. Preparation:
i. For proper capillary action to occur, the tube and
e fitting must be free of oil, grease, burrs, and
th
oxide contamination. To remove the oil and
grease a commercial solvent or denatured
alcohol can be used. The surface may be
properly cleaned by brushing with a stainless
shell brush or by a stiff rubbing with emery clo th.
Wipe the joint clean to remove small foreign
particles such as emery dust, by wiping the
surface with a clean cloth. Once the surfaces are
clean, be careful not to touch them as oil from
the skin will contaminate the surfaces.
ii. Pre-fit the existing tubing into
check that it has full insertion into the
compressor fitting. For compressors that have a
suction restrictor located in the suction inlet,
ensure that the tube is inserted completely such
that the suction restrictor fits tightly against the
end of the compressor suction connection.
iii. Apply flux with a brush
compressor connecting tubing, taking care to
evenly apply the flux around the entire diameter.
Care must also be taken not to get the flux inside
of the tubing as this may result in contamination
of the refrigerant system.
iv. Reinsert the tube into the
connection. If the tubing does not stay fully
in ser ted , it mu st be rest rai ned t o prev ent it fro m
backing out of the compressor connection
during the brazing process.
d. Brazing Technique
i. If possible, use a double-side torch while
zing.
bra
e rubber plugs only when ready to
,
p
the compressor to
to the outside of the
compressor
24 PART-SVN234B-EN
Page 25
Removal and Installation
2
ii. Use 40% silver brazing alloy with flux.
iii. Start heating the tube first. Evenly heat th
location 1 (see red color. Wh good indicator of when the proper brazing temperature has been reached. Continue heating the tube until the flux passes the “bubbling” temperature range and becomes quiet, completely fluid, and transparent—it should have the appearance of clear water.
iv. Direct the flame from the tube to the fitting,
enly heating it until the flux that may be
ev remaining in the fitting is also completely fluid.
v. Sweep the torch between the
tube, locations 1 and 2 (see mo
st of the heat being applied to the heavier and slower-heating fitting until the tube and fitting reach and maintain a uniform heat in both parts.
Figure 19. Brazing locations 1 and 2
vi. Pull the flame slightly back and feed the brazing
aterial in between the fitting and the tube. If
m the joint has been properly heated, the braze material should flow around and into the joint.
Important: The he
filler; the heat from the torch flame should not be what melts the filler.
vii.Once the braze material has flowed around and
the joint, briefly move the torch
into fitting to ensure complete capillary action into the joint.
viii.Check the joint to visually ensure that the braze
material is
e. Post-Braze
Figure 19), until it reaches a dull
en using flux, this color is also a
fitting and the
Figure 19), with
ated base metal should melt the
completely around
the joint.
NOTICE
e tube,
around the
Installation, Operation, and Maintenance manual for proper size and location of the restrictor.
When brazing refrigerant connections, protect mpressor b
co damage.
When brazing, always use a nitrogen purge to prevent
the formation of copper oxide contamination that can damage the compressor.
The 182–361 nominal capacity compressor has
internal check valve. When pressurizing the system, it is important to never allow the low-side pressure to exceed the high-side pressure by more than 5 bar (72 psig). Such a pressure differential could result in compressor over a two-minute time period to allow sufficient time for the internal pressures in the compressor to equalize.
ody and terminal box from torch heat
an
damage. Also, slowly rai
se the pressure
Electrical Connections
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
NOTICE
Clean Flux From Joint!
Flux is corrosive and could lead to long-term problems and equipment damage if not properly removed. Quench the joint with water or a wet rag while the joint is still hot—but below 900°F—to shock off the flux. If not cleaned off, flux could hide leaks.
Tandem (two compressors) and trio c (three compressors) with uneven compressor combinations requires the use of restrictor(s) to balance the oil level in the compressor. Refer to unit
PART-SVN234B-EN 25
ombinations
Page 26
Removal and Installation
BROWN
BLUE
BLACK
L1
M2
L3
L2
M1S2S1NL
L1
L3
L2
A
C
B
L1 L3L2
M2M1NL POWER SUPPLY
MODULE INPUT
VOLTAGE
CONTROL
CIRCUIT
PHASING TO BE CONNECTED AS SHOWN TO PREVENT REVERSE ROTATION
Blue dot
indicating T2
(Phase B)
Red dot
indicating T1
(Phase A)
Unmarked
T3
(Phase C)
182–361 Nominal Capacity
Before removing wires, mark them so that they can be
• put back on the same terminal when the new compressor is installed.
Ensure that the compressor model terminals are installed on the correct terminals (see
If the compressor is not wired properly, it wi within five seconds.
Proper torque for the terminal screws is 25 in·lb.
Note: Wh
Before st
en equipped with terminal stud with a nut,
torque the nut to 30 ±
2 in·lb.
arting the compressor
phasing with a phase sequence meter similar to an Ideal-Sperry Model 61-520.
Figure 20. 182–361 nominal capacity wiring diagram
Figure 20).
, ch
eck the electrical
ll shut of
Figure 21. 090–181 nominal capacity wiring diagram
f
Ensure that the compressor model terminals are installed on the correct terminals (see
Proper torque for the terminal screws is 25 in·lb.
Note: When
equipped with terminal stud with a nut,
torque the nut to 30 ± 2 in·lb.
Figure 21).
NOTICE
Improper Power Phasing!
Operating the compressor with improper phasing could
090–181 Nominal Capacity
The terminal blocks are marked with red and blue dots for phase identification. Compressor terminal T1 is red, compressor terminal T2 is blue, and compressor terminal T3 is unmarked. Depending on the unit type, several methods of marking the wires may be used, colored wires, wire color marks on the wire or wire numbers to indicated the proper location of the wire on the compressor terminal block.
If the wires are not marked, ensure that you mark them
rior to removing them so that they can be reinstalled in
p the same position.
26 PART-SVN234B-EN
cause compressor failure. Check phasing before starting compressor.
Before starting the compressor, check the electrical phasing with a phase sequence meter similar to an Ideal-Sperry Model 61-520.
Leak Detection
WARNING
Hazard of Explosion!
Failure to follow instructions below could result in death or serious injury or equipment or property-only damage. Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units.
Page 27
Removal and Installation
WARNING
Hazardous Pressures!
Failure to properly regulate pressure could result in a violent explosion, which could result in death or serious injury or equipment or property-only-damage. When using dry nitrogen cylinders for pressurizing units for leak testing, always provide a pressure regulator on the cylinder to prevent excessively high unit pressures. Never pressurize unit above the maximum recommended unit test pressure as specified in applicable unit literature. See maximum recommended unit test pressure below.
Pressure Testing
Use industry-standard and EPA-accepted techniques for testing.
Pressure tests must be performed by qualified
rsonnel.
pe
U
se tools especially designed for
Do not exceed the high-side and low-side pressures listed on th
If no test pressure value is listed on the nameplate of the unit, a pressure acceptable.
e unit nameplate.
of no more than 150 psig is
leak testing.
NOTICE
Overpressure Damage!
Failure to follow these instructions could result in compressor damage. Do not pressurize the low side of the compressor by more than 5 bar (72 psig) higher than the high side of the compressor within less than two minutes.
The 182–361 nominal capacity compressor has an in
ternal check valve. When pressurizing the system, it is important to never allow the low side pressure to exceed the high side pressure by more than 5 bar (72 psig). Greater pressure differen compressor damage. Also slowly raise the pressure over a 2-minute time period to allow sufficient time for internal pressures in the compressor to equalize.
Pressure decay testing can be used to check for gross leaks but
After pressurizing the system use an R-410A leak detection devi
will not be able to detect the l
ce to detect and locate leaks.
tial could result in
ocation of a leak.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge of
capacitors, see PROD-SVB06*-EN.
NOTICE
Compressor Motor Damage!
Failure to follow instructions below could cause compressor motor damage. Never use the compressor as a vacuum pump. Never meg-ohm test or apply power to the compressor while it is in a vacuum.
Ensure that there is no voltage being applied to the compressor terminals.
Evacuate the unit to 500 microns.
Hold vacuum for 30 minutes.
Rapid pressure rise indicates a the leak.
Slow pressure rise indicates on
– A small leak, indicated by a continuous rise in
pressure.
– Moisture in the system, indicated by
pressure and leveling-out at a pressure equivalent to the moisture level. If this occurs, break the vacuum with dry nitrogen and repeat evacuation process to 500 micron.
Once system is leak-tight, connect compressor re the vacuum procedure, break vacuum with dry nitrogen and evacuate to 500 microns. The vacuum should be able to be maintained for four hours. Isolate the vacuum reads the system pressure.
Vacuum must be measured in the refrigeration system and n
pump so that the vacuum gauge only
ot at the vacuum pump.
leak; locate and repair
e of two possibilities:
a slow rise in
peat
Vacuum Testing and Evacuation
Use the procedure as described in the unit
Operation, and Maintenance
If no other information is available, use the following information.
PART-SVN234B-EN 27
manual.
Installation,
Page 28
Removal and Installation
Charging the System
WARNING
Hazardous Pressures!
Failure to follow safety precautions below could result in a sudden rise of pressure possibly resulting in a violent explosion which could result in death or serious injury. If a heat source is required to raise the tank pressure during removal of refrigerant from cylinders, use only warm water or heat blankets to raise the tank temperature. Do not exceed a temperature of 150°F. Do not, under any circumstances apply direct flame to any portion of the cylinder.
Use R-410A refrigerant only! Follow the instructions in the un
Installation, Operation, and Maintenance manual for
it
proper charging methods.
If there are no instructions available, use
Evacuate the unit as described in
Evacuation,” p. 27
Ensure that the oil level is at least 1/2-sight glass in the compressor
Do not use the compressor to pull refrigerant into the system.
Charge liquid refrigerant into unit—either into the condenser or liquid receiver, if so eq
uipped.
Charge as much of the unit refrigerant charge as possible before
Do not charge liquid refrigerant into the low side of the compressor without the compressor runn amounts of liquid may be metered through refrigerant gauges into the suction line while the compressor is operating.
If the unit is equipped with suction and discharge
ice valves, close them du
serv procedure.
Water chi
• pumps while charging the unit to prevent freezing the evaporator.
ller units
.
starting the compressor.
—Alw
ays operate the chilled water
these guid
“Vacuum Testing and
the high-side of the
ring the charging
elines:
ing. Small
NOTICE
Improper Crankcase Heater Operation! Exception to 8-hour Minimum Crankcase Heater Operation Time!
Failure to follow this instruction could result in a compressor failure. Apply power to the crankcase heater for a minimum of 8 hours prior to startup of the compressor!
If the compressor is a replace and has been charged in accordance with either the procedures in the unit IOM or
p. 28
in this manual, the compressor could be immediately started after charging the system. Th that the refrigerant has not had sufficient time to migrate to the compressor and cause potential damage upon startup. The system should set for no more 8 hours or overnight h
eater operation. If the time exceeds 8 hours or the unit sits overnight, the crankcase heater must be operational for a minimum of 8 hours prior to starting the compressor.
If liquid refrigerant was charg side during the charging procedure, damage could still occur.
with a refrigerant charge without crankcase
ment for a failed co
“Charging the System,”
e reason for this is
ed into the suction or low
mpressor
Verification Before Start-Up
Follow the instructions in the unit
and Maintenance
available, use these guidelines:
Before starting the unit, verify that all service valves open.
Energize the crankcase he before starting the compressor
28 PART-SVN234B-EN
manual. If there are no instructions
Installation, Operation,
ater a mi
nimum of 8 hours
are
Page 29
Startup
Follow the instructions in the unit Installation, Operation, and Maintenance
available, use these guidelines:
Equipment Damage!
Failure to follow guidelines below could result in equipment damage.
Never start the compressor without refrigerant in the system.
Never bypass the low pressure switch to start the unit.
Monitor oil level for 60 minutes to ensure that oil returns from the system.
Check system pressures and tempe the y are in line with unit design pressures. Refer to the unit
Installation, Operation, and Maintenance manual
for this information.
To top off the unit, charge liquid refrigerant may added
slowly thr
by done only when the compressor is operating.
Do not overcharge the unit.
Recommended system full load superheats—unless
ecified differently in the unit
sp
and Maintenance
•Measure the oil sump superheat. Oil sump superheat should be g calculated as follows:
Oil Sump Superheat = Oil Sump Temperature – Saturated Suction
Measure thermocouple on the bottom of the compressor,
eferably in the center, and insulate it. Calculate sump
pr superheat. If less than 20°F, recheck the expansion valve superheat and increase it. Low sump superheat is indicated by foaming compressor oil.
After fully charging the unit, recheck all pressure,
eratures, and electrical readings.
temp
Ensure that the compressor protection module and power supply wires are installed on the correct terminals (see
Proper torque for the terminal screws is 25 in·lb.
Note: Wh
manual. If there are no instructions
NOTICE
ratures to ensure
ottling it into the suction line. Th is must be
Installation, Operation,
manual—is 16°F–20°F.
reater than 20°F. Oil sump superheat is
Temperature
the oil sump temperature by placing a
Figure 20, p. 26 and Figure 21, p. 26).
en equipped with terminal stud with a nut,
torque the nut to 30 ± 2 in·lb.
PART-SVN234B-EN 29
Page 30
Maintenance
Check the unit Installation, Operation, and Maintenance manual for specific instructions.
Operating conditions must always remain within the operating ran
Operating pressures (suction and discharge pressure).
Operating temperatures (suction, discharge, and
quid).
li
Operating parameters (compressor superheat, subcooling amperage).
Check all of the following on a regular basis:
– System operating conditions.
– System refrigerant charge level.
– Oil levels and oil color.
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge of capacitors,
ge of the compressor. This includes:
, oil sump superheat, voltage, and
WARNING
see PROD-SVB06*-EN.
Check electrical season).
C
heck unit operating controls.
30 PART-SVN234B-EN
connections (prior to startup each
Page 31
Troubleshooting
Important: Check the unit Installation, Operation, and
Maintenance
information regarding diagnosis and causes.
manual for additional
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from p
otential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
Compressor will not start
Refer to the unit
Maintenance
and corrective action.
Verify:
– Compressor voltage is correct.
82–361 nominal capacity compressors
1
protection module is the correct voltage.
– All safety switches are closed.
– All the contacts on the contactor are pulled in.
90–181 nominal capacity compressors
0
internal motor overloads may be open. Disconnect power to the unit and disconnect the wires from the compressor terminals. With an ohm meter, check to ensure that there is resistance between T1-T2 and T3.
Compressor will not build up pressure
090–181 nominal capacity compressor is wired incorrectly
amps. Shut the compressor off immediately. Running in this condition for more than 5 seconds may damage the compressor.
–361 nominal capacity compressor is wired
182 incorrectly
Check to ensure that any bypass valves in the system are not open.
Four-way reversing valve may be stuck and not switched properl
Installation, Operation, and
manual for possible diagnostics codes
—Moto
—The
—It will be noisy and draw 1/2 the expected
.
y bypassing from the high side to the
r
low side of the system; this situation is indicated by an extremely warm suction inlet to the compressor.
60–361 nominal capacity compressors contain an
3 internal pressure relief that may have opened.
take two to three hours to reset. The oil sump will be very warm and the compressor will be trippe the motor protection module. This is caused by a very high 625–715 psid difference between the high side
w side of the system. This could occur with either
and lo a blocked high side or low side.
It may
d out on
Abnormal running noise
Compressor is running backwards—Immediately shut off the compressor and check wiring and proper phasing.
Excessive floodback—The superheat should be a minimum should be at least 20°F above the saturated suction temperature. Measure the sump temperature at the bottom center of the compressor. Chillers with electronic expansion valves may operate with lower superheats; check the unit
Maintenance
Compressor is full of liquid on st heater eith eight hours, or it is defective.
Mechanical damage to the compressor has occurred— Check compressor motor protection module or other unit electrical protection devices such as circuit breakers.
of 16°F at full load and oil sump temperature
Installation, Operation, and
manual for proper operating superheats.
artup—The crankcase
er was not energized for a minimum of
compressor amperage. It may also trip the
High-pressure control opens
Check the unit
Maintenance
and corrective action.
Also check for:
– Defective condenser fan motors or controls.
– Dirty air-cooled or wate
– Restricted air flow.
– Insufficient water flow.
– System overcharged with refrigerant. Check
superheat
– Non-condensables in the system.
Installation, Operation, and
manual for possible diagnostics codes
d condensers.
r-coole
and system subcooling.
Low-pressure control opens
Check the unit
Maintenance
and corrective action.
Also check for:
– Defective evaporator fan motors, belts, or controls.
– Defective TXV valve.
– Plugged liquid line filter.
Installation, Operation, and
manual for possible diagnostics codes
PART-SVN234B-EN 31
Page 32
Troubleshooting
– Liquid line solenoid valve does not open (if so
equipped).
– Dirty evaporators, either air-to-air or water-to-air.
– Restricted airflow.
– Insufficient evaporator water flow.
– System undercharged with refrigerant. Check
em superheat and subcooling.
syst
Compressor short cycling
Check the unit
Maintenance
and corrective action.
Also check for:
– Defective unit controls—maximum 12 starts per
r.
hou
– Compressors cycling on safety controls.
– Unit oversized.
– Building load is light—this is likely to occur
building occupancy
Installation, Operation, and
manual for possible diagnostics codes
ior to
pr
.
Motor protector module resets
Type: Manual
Fault modes:
– Phase sequence
– Phase loss
– Multiple motor temperature overload cycles.
Reset—Remove power from mo
Type: Auto with five-minute 4500 ohms)
Fault modes:
– Over current
– Running phase loss
– Motor over temperature (manual reset required
fter 2-5 auto reset cycles)
a
Reset—Auto-reset
ors resistance drops below 2750 ohms. Although
sens module will reset automatically the compressor(s) may not because the protection module may be wired in a safety lockout circuit.
occurs when motor temperature
dule for five sec
delay (sensors exceed
onds.
Incorrect phase sequence
Incorrect phase sequence protection—compressor will run approximately five seconds and trip off, pending the motor protection module is correctly wired into the system safety circuit. If the motor is believed to be incorrectly phased; change two of the three wires.
PTC Overheat (motor over temperature/over current)
Compressor motor drawing too much current.
Defective compressor; look for dark oil in sightglass.
Low voltage (voltage outside the nominal voltage); voltage utilization range is printed on compressor nameplate.
Unbalanced voltage—must not exceed 2% imbalance.
Motor PTC thermistor resistance above 4500 ohms will cause the motor protector to open. The motor protector will reset at resistance below 2750 ohms. A five-minute time delay is active after cool down until the maximum number of auto reset cycles has been reached. The module will then be locked out until it is manually reset.
±
the
10% range from
NOTICE
Excessive Voltage on PTC Sensors!
Failure to follow these instructions could cause thermistor failure, resulting in a compressor replacement. Do not measure the motor PTC sensors with a device rated at more than 3 Vdc.
When measuring the PTC sensors, do not use a meter with gr
eater than 3 Volt.
360–361 nominal capacity compressor
• valve has opened.
Phase loss.
Defective contactor.
Loose or poor electrical co or contactor.
nnections at the compressor
internal relief
182–361 Nominal Capacity Compressor Motor Protection Module Diagnosis
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from p
otential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
If M1-M2 contacts are open, proceed as follows:
1. Check motor protection module for the correct input oltage on terminals L and N. Voltage applied to
v
32 PART-SVN234B-EN
Page 33
module must match module input voltage as printed on module nameplate.
2. Check wire connection tightness.
3. Try to reset the module (i five seconds).
4. If, after reset, module M1-M2 closes, determine which fault caused module to tri
5. If M1-M2 remains open, proceed as follows:
Disconnect PTC thermistors from S1and S2 terminals,
d measure the resistance of the PTC using a device
an with a maximum output of 3 volts.
Resistance = .
Open PTC open; replace compressor.
Resistance = 0 ohms
PTC shorted; replace compressor.
Resistance >2750 ohm
Wait until the motor has cooled down and
nce is less than 2750 ohms; reconnect and
resista try to reset motor protector. Diagnose problem that caused motor over temperature.
Resistance = 150 ohms < R< 1250 ohms
Normal resistance value for PTC ambient
emperature.
t
nterrupt power for
p.
Troubleshooting
Test the module within the terminal box
1. Disconnect L-N voltage supply.
2. Disconnect S1-S2 PTC circuit on the module.
3. Disconnect M1-M2 safety circ
4. Apply a resistance between 150 and 1250 ohms across S1-S2. This simu
5. Reconnect L-N voltage supply. Ensure that the voltage
L-N has been disabled for at least 5 seconds. This
to will reset the module.
6. Check M1-M2 with ohmmeter.
7. M1-M2 closed—Module okay.
8. M1-M2 open—Module defective.
lates a functional, cool motor.
uit control contacts.
PART-SVN234B-EN 33
Page 34
Log Sheet
Replacement Scroll Compressors
Complete and retain a record in the job file for future reference.
Log Sheet for Installers
Job Name:
Job Address:
Equipment Model Number:
Equipment Serial Number:
Compressor Model Number:
Compressor Serial Number:
Startup Date:
Table 5. System operating data
Refrigeration Data Circuit 1 Circuit 2 Circuit 3 Circuit 4
Suction Pressure/Saturation Temp
Suction Line Temperature
Suction Superheat (2-1)
Discharge Pressure
Discharge Line Temp
Liquid Line Pressure/Saturation Temp
Liquid Line Temp
Liquid Subcooling (6-7)
Table 6. Electrical data
Unit Voltage L1-L2 L2-L3 L1-L3
Table 7. Compressor Amperage
Compressor #1 #2 #3 #4 #5 #6 #7 #8
T1 amps
T2 amps
T3 amps
Compressor Model 8 Digit Number
Table 8. Oil sight glass (when available)
Compressor #1 #2 #3 #4 #5 #6 #7 #8
Level
Condition
M=Manifold/S=Single
Compressor Model 8 Digit Number
34 PART-SVN234B-EN
Page 35
Table 9. Condenser
Type Air Cooled Water Cooled
Entering Temperature
Leaving Temperature
Ambient Not Applicable
Number of Fans ON
Clean (Yes/No)
Not Applicable
Table 10. Evaporator
Type DX-Air DX-Water
Entering Temperature
Leaving Temperature
CFM/GPM
Clean (Yes/No)
Chiller pressure drop Not Applicable
Systems Check
Suction Line Filter Drier Installed
Pressure Drop After 1 Hour:
PSIG After 4 Hours:
Liquid Line Filter Changed
Oil Changed
Acid Check
If System Includes Liquid Line Solenoid, Verify Proper Opening/Closing
Log Sheet
Operating Controls Check
Low Pressure Control
High Pressure Control
Contactor
Replaced
Checked
Verify Proper Cycling of Unit Via Temperature Controls
Observations
Service Technician: Date:
PART-SVN234B-EN 35
Page 36
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
PART-SVN234B-EN 17 Aug 2020
Supersedes PART-SVN234A-EN (Jan 2017)
©2020 Trane
Loading...