Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
August 2020
PART-SVN234B-EN
Page 2
Introduction
Read this manual thoroughly before operating or
servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
CAUTIONs
NOTICE
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment. Trane advocates the responsible handling
of all refrigerants—including industry replacements for
CFCs and HCFCs such as saturated or unsaturated HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation whi
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
ch, if not avoided, could
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertaken
could result in death or serious injury. Technicians, in
order to protect themselves from potential electrical,
mechanical, and chemical hazards, MUST follow
precautions in this manual and on the tags, stickers,
and labels, as well as the instructions below:
•Before installing/servicing this unit, technicians
MUST put on all PP
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Safety Data Sheets
(SDS) and OSHA guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS
(Global Harmonized System of Classification and
Labeling of Chemicals) guidelines for information on
allowable personal exposure levels, proper
respiratory protection and handling instructions.
•If there is a risk of energized electrical contact, arc,
flash, technicians
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions below could result in
death or serious injury.
•All Trane personnel must follow the company’s
E
nvironmen
when performing work such as hot work, electrical,
fall protection, lockout/tagout, refrigerant handling,
etc. Where local regulations are more stringent than
these policies, those regulations supersede these
policies.
•Non-Trane personnel should always follow local
lations.
regu
tal, Health and Safety (EHS) policies
WARNING
R-410A Refrigerant under Higher Pressure
than R-22!
Failure to use proper equipment or components as
described below, could result in equipment failing and
possibly exploding, which could result in death, serious
injury, or equipment damage. The units described in
this manual use R-410A refrigerant which operates at
higher pressures than R-22. Use ONLY R-410A rated
service equipment or components with these units. For
specific handling concerns with R-410A, please contact
your local Ingersoll Rand representative.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
WARNING
Hazard of Explosion!
Failure to follow instructions below could result in
death or serious injury or equipment or property-only
damage. Use only dry nitrogen with a pressure
regulator for pressurizing unit. Do not use acetylene,
oxygen or compressed air or mixtures containing them
for pressure testing. Do not use mixtures of a hydrogen
containing refrigerant and air above atmospheric
pressure for pressure testing as they may become
flammable and could result in an explosion. Refrigerant,
when used as a trace gas should only be mixed with dry
nitrogen for pressurizing units.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on
the tags, stickers, and labels could result in death or
serious injury.
Technicians, in order to protect themselves from
p
otential electrical, mechanical, and chemical hazards,
MUST follow precautions in this manual and on the
tags, stickers, and labels, as well as the following
instructions: Unless specified otherwise, disconnect all
electrical power including remote disconnect and
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be
inadvertently energized. When necessary to work with
live electrical components, have a qualified licensed
electrician or other individual who has been trained in
handling live electrical components perform these
tasks.
WARNING
Hazardous Conditions!
Failure to follow these instructions could result in death
or serious injury or damage to the equipment. Observe
and follow the “Warning” and “Notices” labels on the
compressor.
NOTICE
Use Proper Charging and Crankcase
Heater Operation Procedures!
Failure to utilize proper charging and crankcase heater
procedure will result in compressor failure. Refer to unit
Installation, Operation, and Maintenance manual and
this manual for the proper procedures.
Copyright
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission. Trane reserves the right
to revise this publication at any time, and to make changes
PART-SVN234B-EN3
Page 4
Introduction
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
Updated for Trane Technologies.
4 PART-SVN234B-EN
Page 5
Table of Contents
Model Number Descriptions . . . . . . . . . . . . . . 6
The purpose of this document is to provide installation
and service information for Start to Finish™ R-410A
compressors.
This document is not meant to be provide a step-by-step
ocedure, but is intended to identify procedures or
pr
precautions that may be unique to a Start to Finish R-410A
compressor and should be taken into account to properly
and safely remove, install, and troubleshoot the
compressor.
Each installation has its unique set of circumstances
which
also must be taken into account by the service technician.
Table 1.Available Start to Finish™ compressors
Model NumberService Part Number
SFCOM0905754PSNADSFCOM090-5754AD
SFCOM0902304PSNAD
SFCOM0904604PSNADSFCOM090-4604AD
SFCOM1095754PSNADSFCOM109-5754AD
SFCOM1092304PSNADSFCOM109-2304AD
SFCOM1094604PSNADSFCOM109-4604AD
SFCOM1215754PSNADSFCOM121-5754AD
SFCOM1212304PSNADSFCOM121-2304AD
SFCOM1214604PSNADSFCOM121-4604AD
SFCOM1455754PSNADSFCOM145-5754AD
SFCOM1452304PSNADSFCOM145-2304AD
SFCOM1454604PSNAD
SFCOM1565754PSNADSFCOM156-5754AD
SFCOM1562304PSNAD
SFCOM1564604PSNADSFCOM156-4604AD
SFCOM1815754PSNADSFCOM181-5754AD
SFCOM1812304PSNADSFCOM181-2304AD
SFCOM1814604PSNAD
SFCOM1825754PSNANSFCOM182-5754AN
SFCOM1832304PSNAN
SFCOM1822304PSNANSFCOM182-2304AN
SFCOM1834604PSNANSFCOM183-4604AN
SFCOM1824604PSNANSFCOM182-4604AN
SFCOM2415754PSNANSFCOM241-5754AN
SFCOM2405754PSNANSFCOM240-5754AN
SFCOM2412304PSNANSFCOM241-2304AN
SFCOM2402304PSNANSFCOM240-2304AN
SFCOM2414604PSNANSFCOM241-4604AN
SFCOM2404604PSNANSFCOM240-4604AN
SFCOM3005754PSNANSFCOM300-5754AN
SFCOM3012304PSNANSFCOM301-2304AN
SFCOM3002304PSNANSFCOM300-2304AN
SFCOM3014604PSNANSFCOM301-4604AN
SFCOM3004604PSNAN
SFCOM3615754PSNANSFCOM361-5754AN
SFCOM3605754PSNANSFCOM360-5754AN
SFCOM090-2304AD
SFCOM145-4604AD
SFCOM156-2304AD
SFCOM181-4604AD
SFCOM183-2304AN
SFCOM300-4604AN
Table 1.Available Start to Finish™ compressors
Model NumberService Part Number
SFCOM3612304PSNAN
SFCOM3602304PSNANSFCOM360-2304AN
SFCOM3614604PSNANSFCOM361-4604AN
SFCOM3604604PSNANSFCOM360-4604AN
SFCOM361-2304AN
PART-SVN234B-EN7
Page 8
Dimensional Data
Figure 1.SFCOM090 compressors
APPLICATIONSFCOM090
REFRIGERANTR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)85.1
POWER INPUT (KW)8.67
EER (BTU/W-HR)9.82
Note: Fittings and connection part descriptions are
shown in
8 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 9
Figure 2.SFCOM109 and SFCOM121 compressors
Dimensional Data
APPLICATIONSFCOM109SFCOM121
REFRIGERANTR410AR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)101.0117.1
POWER INPUT (KW)10.1511.58
EER (BTU/W-HR)9.9510.11
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN9
Figure 13 and Figure 14, p. 19.
Page 10
Dimensional Data
Figure 3.SFCOM145 compressors
APPLICATIONSFCOM145
REFRIGERANTR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)137.3
POWER INPUT (KW)13.48
EER (BTU/W-HR)10.18
Note: Fittings and connection part descriptions are
shown in
10 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 11
Figure 4.SFCOM156 compressors
APPLICATIONSFCOM156
REFRIGERANTR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)158.2
POWER INPUT (KW)15.33
EER (BTU/W-HR)10.32
Dimensional Data
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN11
Figure 13 and Figure 14, p. 19.
Page 12
Dimensional Data
Figure 5.SFCOM181 compressors
APPLICATIONSFCOM181
REFRIGERANTR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)177.7
POWER INPUT (KW)17.04
EER (BTU/W-HR)10.43
Note: Fittings and connection part descriptions are
shown in
12 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 13
Figure 6.SFCOM182 and SFCOM183 compressors
Dimensional Data
APPLICATIONSFCOM182SFCOM183
REFRIGERANTR410AR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)176.2176.2
POWER INPUT (KW)17.3617.36
EER (BTU/W-HR)10.1510.15
PROTECTION CONTROL MODULE
VAC115/23024
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN13
Figure 13 and Figure 14, p. 19.
Page 14
Dimensional Data
Figure 7.SFCOM240 and SFCOM241 compressors
APPLICATIONSFCOM240SFCOM241
REFRIGERANTR410AR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)237.4237.4
POWER INPUT (KW)23.4623.46
EER (BTU/W-HR)10.1210.12
PROTECTION CONTROL MODULE
VAC115/23024
Note: Fittings and connection part descriptions are
shown in
14 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 15
Figure 8.SFCOM300 and SFCOM301 compressors
Dimensional Data
APPLICATIONSFCOM300SFCOM301
REFRIGERANTR410AR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)298.2298.2
POWER INPUT (KW)29.7529.75
EER (BTU/W-HR)10.0210.02
PROTECTION CONTROL MODULE
VAC115/23024
Note: Fittings and connection part descriptions are
shown in
PART-SVN234B-EN15
Figure 13 and Figure 14, p. 19.
Page 16
Dimensional Data
Figure 9.SFCOM360 and SFCOM361 compressors
APPLICATIONSFCOM360SFCOM361
REFRIGERANTR410AR410A
U.L. RECOGNIZED USA & CANADA
RATED PERFORMANCE @45°/130°/20°/15°
CAPACITY (MBTU/HR)358.9358.9
POWER INPUT (KW)36.1036.10
EER (BTU/W-HR)9.949.94
PROTECTION CONTROL MODULE
VAC115/23024
Note: Fittings and connection part descriptions are
shown in
16 PART-SVN234B-EN
Figure 13 and Figure 14, p. 19.
Page 17
General Information
Table 2.Torque values
ItemTorque
Rotolock equalizer nut
1-3/4 and 2-1/4
Terminal screws #10-32 X 0.5 in
Terminal stud2.75 ± 0.25 N·m; 30 ± 2 in·lb
Terminal stud nut
Ground screw1.90 ± 0.25 N·m; 17 ± 2 in·lb
Terminal box cover2.15 ± 0.25 N·m; 19 ± 2 in·lb
133 ± 10 N·m; 98 ± 7 ft·lb
2.75 ± 0.25 N·m; 25 ± 2 in·lb
3.4 ± 0.25 N·m; 30 ± 2 in·lb
Note: With Rotolock fittings, always use two wrenches:
one to back-up on the sleeve and one to tighten the
nut. Proper torquing of the Rotolock nut is
important to ensure a leak-free joint.
POE Oil
Table 3.Factory oil charge
Nominal Capacity PintsLitersPart Number
0906.33.0OIL00078, OIL00080
109–1567.03.3
1817.63.6OIL00078, OIL00080
182–30114.26.7OIL00078, OIL00080
360–36115.27.2OIL00078, OIL00080
Notes:
1. OIL00078—1 quart container
2. OIL00080—1 gallon container
3. Oil amount and type is also pri
nted on the nameplate.
OIL00078, OIL00080
The oil should be visible through the oil sightglass both
during operation and when the compressor(s) is off. Oil
level slightly below the sightglass, but still visible is
acceptable.
Single compressor. The oil level should be stable in the
sightglass.
Tandem and trio compressors. •Operation—The oil
level will vary depending on the operating condition.
•Unloaded condition
—The running compressor will
have a higher oil level than the off compressor(s).
•Loaded condition
—Oil should be visible through all
of the compressor sight glasses. Some may have a
higher level than others, but this is not abnormal.
—After several minutes, the oil levels should be the
•Off
same in each compressor and should be visible in the
sightglass. This is the best method to determine if the
system has sufficient oil.
Units overcharged with oil will operate with degraded
erformance and co
p
uld lead to compressor damage.
Operating Envelope
The compressor must be operated within the published
operating envelope.
Oil Handling
POE oil is very hygroscopic, which means it absorbs
moisture very readily. Therefore, it is important to
properly handle the oil.
POE Oil handling guidelines
•Always use the smallest container size required for the
job requirements.
•Always leave the oil container tig
of use
.
•Do not reuse oil that has been opened.
htly sealed until time
Oil Level
Figure 10. Compressor oil label
PART-SVN234B-EN17
Page 18
R410A Operating Map - Superheat 20F
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
-30-20-10010203040506070
Evaporating temperature (°F)
Condensing temperature (°F)
R410A Operating Map - Superheat 20F
General Information
Figure 11. Operating envelope
Refrigerant Type
Start to Finish™ compressors are approved for use with
R-410A refrigerant only. Any use of hydrocarbon
refrigerants or air is strictly prohibited!
Heavy Objects!
Failure to follow instructions below or properly lift unit
could result in unit dropping and possibly crushing
Transportation, Handling, and
Storage
operator/technician which could result in death or
serious injury, and equipment or property-only damage.
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
The compressor must be handled in the vertical position
(maximum 15-degree offset from vertical). Should the
compressor be handled in an upside down position, its
suitability for its use can not be guaranteed.
Improper Handling!
Improper handling of the compressor resulting from
being handled or transported in the upside position,
dropped or tipped over could result in internal damage
to the compressor and it is recommended that the
compressor not be put into service.
Damage to compressor or packag
to the shipper immediately.
Use a proper method of lifting the compressor, both lifting
ears must be used with a spread
18 PART-SVN234B-EN
NOTICE
ing should be
er bar.
reported
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift.
For approximate compressor weight, see
WARNING
Table 4, p. 19.
Page 19
General Information
Oil equalizer Rotolock
connection fitting
1/4 Schrader port
Oil drain valve
Sightglass
Oil equalizer Rotolock
connection fitting
1/4 Schrader port
Sightglass
Spreader bar use is recommended to better balance the
compressor.
Figure 12. Lifting compressor with spreader bar
lifting hooks with close clasps.
Use
Table 4.Compressor weight with full oil charge
Nominal CapacityWeight (lb)
090128
109–121
145148
156152
181155
182–183234
240–241238
300–301337
360–361362
142
Figure 13. Nominal capacity 182–361
Figure 14. Nominal capacity 090–181
The compressor and its packaging must not be exposed to
rain and/or corrosive, flammable atmosphere.
The compressor must not be stored in an environment
less than -31°F (-35°C) or to exceed +160°F (+71°C).
Pre-Installation Inspections
Check the following before using the compressor:
•Compressor for visible shipping damage.
•Compressor is the correct mo
del/part number.
•Compressor is the correct voltage.
•Compressor ship-with items:
– Restrictors for use with tandem and trio
compressors.
®
– Oil equalizer Teflon
gaskets.
WARNING
R-410A Refrigerant under Higher Pressure
than R-22!
Failure to use proper equipment or components as
described below, could result in equipment failing and
possibly exploding, which could result in death, serious
injury, or equipment damage. The units described in this
manual use R-410A refrigerant which operates at higher
pressures than R-22. Use ONLY R-410A rated service
equipment or components with these units. For specific
handling concerns with R-410A, please contact your local
Ingersoll Rand representative.
PART-SVN234B-EN19
Page 20
Oil equalizer Rotolock
connection fitting
Oil equalizer lines
TANDEM
TRIO
General Information
Suggested area to cut the
refrigerant lines so that
they can be reinstalled
Figure 15. Tandem and Trio
Other modification may cause oil return
issues and lead to compressor failure. Cut
the lines in a convenient place, remove the
compressor, and then unbraze the lines
from the compressor. On reinstallation,
reinstall lines to compressor and
reassemble the cut lines utilizing a slip
coupling. See
to cut the
Figure 16. Suggested areas to cut refrigerant lines
Figure 16 for suggested area
discharge and suction l
ine.
Repair Recommendations
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
Mechanical Failure
Replace only the failed compressor in a tandem or trio set.
Important: On tandem or
20 PART-SVN234B-EN
and discharge lines must NOT be modified,
except for the use of slip joint couplings.
trio assemblies, the suction
Minimize system and compressor open times to avoid
excessive moisture absorption by the POE oil. Maximum
suggested open time is 15 minutes.
Drain and replace oil in all the non-failed compressors.
Note: Fo
The 182–361 nominal capacity compressor has an
with a Schrader® valve that can be used to remove the oil
(see
Replace unit liquid line filter-drier. T
part of controlling moisture in R-410A POE oil systems.
Reuse the compressors mounting isolators or mounting
spacers that a
assembly.
Braze the compressor into
connections ar
silver, with paste flux to make the copper tube connections
to the compressor.
r 090–181 nomnial capacity compressors, this
requires removing
through the oil equalizer Rotolock fitting (see
Figure 14, p. 19). Use a dedicated device for
removing oi
device with clean oil prior to use.
Figure 13, p. 19).
re used with the existing compressor
e copper-plated steel. Use BAg-28, 40%
oil using a suction device
l. It is good practice to flush the suction
his is a very important
the system. Compressor
oil drain
Page 21
General Information
Nominal Capacity“X” Distance
090–181 10 inches
182–361 tandem 16 inches
182–361 trio 25 inches
X Minimum Distance
Proceed as described in the following sections:
•
“Leak Detection,” p. 26
•“Vacuum Testing and Evacuation,” p. 27
•“Charging the System,” p. 28
•“Verification Before Start-Up,” p. 28
Electrical Failure
Replace only the failed compressor in a tandem or trio set.
Drain and replace the oil in all the non-failed compressors.
Reuse the compressors mounting isolators or mounting
rs that are
space
assembly.
Braze compressor into the system. Compressor
connections are copper-plated steel. Use
silver, with paste flux to make the copper tube connections
to the compressor.
Important: On
Minimize system and compressor open times to avoid
excessive
suggested open time is 15 minutes.
Test the acid condition of the oil in the compressors using
acid
test kit. Use Part Numbers KIT06815, CHM00414,
an
and KIT06754.
Two Types of Motor Failures
Light. If oil test kit is negative and oil is only slightly
discolored, treat in the same manner as a mechanical
failure.
Severe. If oil test kit is positive with strong pungent odor
and dark oil, drain and replace oil in all of the non-failed
compressors.
Reuse the compressor mounting isolators or mounting
rs that are
space
assembly.
This type of failure requires changing both the suction and
iquid line
l
facilitate changing filter-driers, if required.
Install the suction filters no closer than the distance listed
in the table following
from the centerline
p. 20).
PART-SVN234B-EN21
used with the existing compressor
BAg-28, 40%
tandem or trio assemblies, the suction
and discharge lines must not be modified,
except for the use of slip joint couplings.
Other modification may cause oil return
issues and lead to compressor failure. Cut
the lines in a convenient place, remove the
compressor then unbraze the lines from the
compressor. On reinstallation, reinstall
lines to compressor and reassemble the cut
lines with a slip coupling. See
r suggested area to cut the discharge
fo
p. 20
and suction
moisture absorption by the POE oil. Maximum
used with the existing compressor
filter-driers. Use replaceable filter-drier cores to
line.
Figure 17. The distance is measured
of the suction inlet tee (see
Figure 16,
Figure 16,
Braze compressor into the system. Compressor
connection
silver, with paste flux to make the copper tube connections
to the compressor.
Proceed as described in the following sections:
•
“Leak Detection,” p. 26
•“Vacuum Testing and Evacuation,” p. 27
•“Charging the System,” p. 28
•“Verification Before Start-Up,” p. 28
Figure 17. Minimum distance b
1. Use acid removal type filter-drier cores in both the
suction filter and liquid line filter drier.
2. Change when the pressure drop exceeds 4 psig.
s are copper-plated steel. Use BAg-28, 40%
efore installation
suction line filter
182–361 nominal capacity models
Test oil after 24 hours of operation. Change filter-drier
again if required. If oil is still acid, drain and replace oil in
all the non-failed compressors.
After system is clean, test kit in
su
ction clean up filter-drier and replace the liquid line drier
with standard filter drier cores.
dicates okay, remove the
090–181 nominal capacity models
Since these compressors do not have an oil drain valve, it
is recommended that after 24 hours of operation, the filterdrier cores be replaced with acid removal filter-drier cores.
Operate the system for another 24 hours before changing
to remo
filter-drier in the liquid line.
ve the suction filter-drier and install a standard
of
Page 22
Removal and Installation
WARNING
Removal
Refrigerant under High Pressure!
Failure to follow instructions below could result in an
explosion which could result in death or serious injury
or equipment damage. System contains oil and
refrigerant under high pressure. Recover refrigerant to
relieve pressure before opening the system. See unit
nameplate for refrigerant type. Do not use nonapproved refrigerants, refrigerant substitutes, or
refrigerant additives.
Pressurized Burning Fluid!
Failure to follow these instructions could result in death
or serious injury. Before opening a system, you must
remove refrigerant from both the high and low sides of
the system. If the pressure is not removed from both
sides of the system, pressure could still exist in the
system. If a torch is used to unbraze the tubing, the
refrigerant and oil mixture could ignite.
WARNING
Contains Refrigerant!
R-410A Refrigerant under Higher Pressure
than R-22!
Failure to use proper equipment or components as
described below, could result in equipment failing and
possibly exploding, which could result in death, serious
injury, or equipment damage. The units described in
this manual use R-410A refrigerant which operates at
higher pressures than R-22. Use ONLY R-410A rated
service equipment or components with these units. For
specific handling concerns with R-410A, please contact
your local Ingersoll Rand representative.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
Only qualified personnel should install or repair
refrigeration systems. If you are not qualified, seek the
services of qualified personnel. The steps listed below are
not meant to be an exact step-by-step procedure, but are
intended to identify procedures or precautions that may
be unique to a Start to Finish™ compressor and should be
taken into account to properly and safely remove and
install the compressor. Each installation has its unique set
of circumstances which must be considered by the service
technician to perform a safe and successful compressor
replacement.
22 PART-SVN234B-EN
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge
of
capacitors, see PROD-SVB06*-EN.
•Prior to removing the compressor, open th
disconnect and place a lock on the disconnect to
prevent someone else from accidentally applying
power to the unit while it is under repair.
•Completely recover the refrigerant fr om the refrigerant
t being rep
circui
atmosphere! Use Responsible Refrigerant Practices. If
adding or removing refrigerant, the service technician
must comply with all Federal, State, and local laws.
Before removing the electrical connections on the
mpressor u
co
power on:
•Compressor power terminals.
•Compressor motor protection module.
•After confirming the absen
electrical connections.
– Mark the electrical wires so they can
– 090–181 nominal capacity com
•Remove oil prior to compressor
– 182–361 Nomi
se a voltmeter to check for the absence of
on the same terminal on the replacement
compressor to prevent improper phasing.
bl
ocks are marked: T1 is marked red, T2 is marked
blue, and T3 has no mark (see
–361 nominal capacity compressors have an
• 182
oil drain
WARNING
WARNING
e unit
aired. Do not release refrigerant to the
ce of power, r
removal:
nal Capacity Compressors
valve (see
Figure 13, p. 19) that allows
emove the
be placed back
pressor terminal
Figure 21, p. 26).
Page 23
Removal and Installation
oil to be drained out of the compressor. After the
refrigerant has been recovered, pressurize the
system with nitrogen to help remove oil from the
compressor.
• If the
– 090–181 Nominal Capacity Compressors
Note: F
• Fo
• If
Tip:Befor
compressor, apply flux to the joint. This will aid in
the flow of the braze material and help keep the
joint clean for rebrazing. After fluxing, heat the joint
evenly to slightly higher temperature than the
melting temperature of the filler material. At this
point, the two parts of the assembly should be
easily separated.
•Refrigerant Connection Removal
– Single compressor—Cut the refrigerant lines in a
co
slip couplings. Then, unbraze the line from the
compressor and reuse it when the replacement is
installed.
• Whe
• T
compressor is in a tandem or trio set, place
a catch pa
connection on the compressor to catch the oil
from the oil equalizer tube or compressor when
the oil equalizer tube is removed.
r 090–181 nominal capacity compressors, oil
removal requires using a suction or pump
device through the oil equalizer Rotolock fitting,
see
with clean oil prior to use.
the compressor is in a tandem set, place a
catch pan unde
connection fitting on the compressor to catch
the oil from the compressor when the oil
equalizer tube is removed. Refer to
p. 19
connection fitting.
e removing the existing tubing from the
nvenient
on the cap of the compressor with a spreader bar
(see
he lifting device must be rated to handle the
weight compressor
n under the oil equalizer Rotolock
or excess oil removal, the Schrader valve
in the lower part of
can be used. If more oil or the complete oil
charge needs to be removed, use the
following procedure.
Figure 14, p. 19. Flush the suction device
r the oil equalizer Rotolock
for the location of the oil equalizer Rotolock
location that allows reassembly with
n removing the compressor use both hooks
Figure 12, p. 19).
the compressor shell
Figure 14,
as listed in
Table 4, p. 19.
There are special considerations that are unique to
replacing compressors in a tandem or trio set:
1. Only replace the failed compressor.
2. On tandem or trio assemblies, the
discharge lines must not be modified, except for the
use of slip-joint couplings. Other modifications may
cause oil return issues and lead to compressor failure.
Cut the lines in a convenient place, remove the
compressor, and then unbraze the lines from the
compressor. On re-installation, reinstall lines to
compressor and reassemble the cut lines using a slip
coupling. Refer to
to cut the
Tip:Before removing the existing tubing from the
3. Change oil in all compressors in the tandem or trio
mpressors whenever there is a failure.
co
a. 182–361 Nominal Capacity—Use the oil charging
b. 090–181 Nominal Capacity—Remove the oil
Important: So
discharge and suction line.
compressor, apply flux to the joint. This will aid in
the flow of the braze material and help keep the
joint clean for re-brazing. After fluxing, heat the
joint evenly to slightly higher temperature than the
melting temperature of the filler material. At this
point, the two parts of the assembly should be
easily separated.
lve on the compressor.
va
equalizer fitting and use a suction or pump device to
remove the oil from the compressor through the oil
equalizer tube opening. A suction type device
should be used to remove oil from the compressor.
require a restrictor be placed in the suction
inlet to balance the oil levels. Refer to unit
Installation, Operation, and Maintenance
manual for correct size and location of
restrictor. The restrictors are packaged in a
bag with a label with the part number and
diameter required (see
The
internal diameter in millimeters is Ø31. The
restrictor is also marked on the face with
both the extension number, last three digits
of the part number, and diameter. For the
previous example, the restrictor would be
marked 010-31. Without the proper
restrictor installed, the compressor oil level
balance will not be correct.
Figure 16, p. 20 for suggested area
me mult
part number is X17311028010 and the
iple compressor configurations
suction and
Figure 18, p. 24).
Compressor Replacement—Tandem and
Trio Compressor Sets
Definitions:
•Tandem—Two compressors on a sing
circuit.
•Trio—Three compressors on a single refriger
circuit.
PART-SVN234B-EN23
le refrigerant
ant
Incorrect Restrictor Size and Location!
Failure to install the correct size restrictor or in the
correct position will lead to improper oil levels in the
compressor. This could result in a compressor failure
due to low oil level.
NOTICE
Page 24
Removal and Installation
4. It will be necessary to use an oil catch pan under the oil
equalizer connection to catch the oil when the
connection is loosened and removed.
Figure 18. Restrictor label
Installation
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge
of capacitors,
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
•Only qualified personnel should install or repair
refrigeration systems. If you are not qualified, seek the
services of qualified personnel.
•Pressure tests must be performed by qualified
rsonnel.
pe
•T
he replacement compressor contains a nitrogen
charge of 5 psig. Before opening the connections on
the compresso
Schrader fitting on the shell to slowly release the
nitrogen charge in the compressor.
see PROD-SVB06*-EN.
WARNING
r, connect a 1/4-inch service hose to the
•Remove the suction plug before the discharge plug to
avoid oil spray while opening the compressor.
•Keep exposure to the atmosphere at a minimum due to
E oil. Remove th
PO
install the compressor. Plug other compressor on
tandem or trio compressors.
fore removing the oil equalizer connection ca
Be
•
place a can pan under the Rotolock fitting as the
compressor oil level is above the Rotolock connection.
Oil must be added to the compressors after
installation.
a. Removal Instructions
Tip:Be
fore removing the existing tubing from the
compressor, apply flux to the joint. This will aid in
the flow of the braze material and help keep the
joint clean for rebrazing. After fluxing, heat the joint
evenly to slightly higher temperature than the
melting temperature of the filler material. At this
point, the two parts of the assembly should be
easily separated.
b. Installation
c. Preparation:
i. For proper capillary action to occur, the tube and
e fitting must be free of oil, grease, burrs, and
th
oxide contamination. To remove the oil and
grease a commercial solvent or denatured
alcohol can be used. The surface may be
properly cleaned by brushing with a stainless
shell brush or by a stiff rubbing with emery clo th.
Wipe the joint clean to remove small foreign
particles such as emery dust, by wiping the
surface with a clean cloth. Once the surfaces are
clean, be careful not to touch them as oil from
the skin will contaminate the surfaces.
ii. Pre-fit the existing tubing into
check that it has full insertion into the
compressor fitting. For compressors that have a
suction restrictor located in the suction inlet,
ensure that the tube is inserted completely such
that the suction restrictor fits tightly against the
end of the compressor suction connection.
iii. Apply flux with a brush
compressor connecting tubing, taking care to
evenly apply the flux around the entire diameter.
Care must also be taken not to get the flux inside
of the tubing as this may result in contamination
of the refrigerant system.
iv. Reinsert the tube into the
connection. If the tubing does not stay fully
in ser ted , it mu st be rest rai ned t o prev ent it fro m
backing out of the compressor connection
during the brazing process.
d. Brazing Technique
i. If possible, use a double-side torch while
zing.
bra
e rubber plugs only when ready to
,
p
the compressor to
to the outside of the
compressor
24 PART-SVN234B-EN
Page 25
Removal and Installation
2
ii. Use 40% silver brazing alloy with flux.
iii. Start heating the tube first. Evenly heat th
location 1 (see
red color. Wh
good indicator of when the proper brazing
temperature has been reached. Continue
heating the tube until the flux passes the
“bubbling” temperature range and becomes
quiet, completely fluid, and transparent—it
should have the appearance of clear water.
iv. Direct the flame from the tube to the fitting,
enly heating it until the flux that may be
ev
remaining in the fitting is also completely fluid.
v. Sweep the torch between the
tube, locations 1 and 2 (see
mo
st of the heat being applied to the heavier and
slower-heating fitting until the tube and fitting
reach and maintain a uniform heat in both parts.
Figure 19. Brazing locations 1 and 2
vi. Pull the flame slightly back and feed the brazing
aterial in between the fitting and the tube. If
m
the joint has been properly heated, the braze
material should flow around and into the joint.
Important: The he
filler; the heat from the torch flame should
not be what melts the filler.
vii.Once the braze material has flowed around and
the joint, briefly move the torch
into
fitting to ensure complete capillary action into
the joint.
viii.Check the joint to visually ensure that the braze
material is
e. Post-Braze
Figure 19), until it reaches a dull
en using flux, this color is also a
fitting and the
Figure 19), with
ated base metal should melt the
completely around
the joint.
NOTICE
e tube,
around the
Installation, Operation, and Maintenance manual for
proper size and location of the restrictor.
•When brazing refrigerant connections, protect
mpressor b
co
damage.
•When brazing, always use a nitrogen purge to prevent
the formation of copper oxide contamination that can
damage the compressor.
•The 182–361 nominal capacity compressor has
internal check valve. When pressurizing the system, it
is important to never allow the low-side pressure to
exceed the high-side pressure by more than 5 bar
(72 psig). Such a pressure differential could result in
compressor
over a two-minute time period to allow sufficient time
for the internal pressures in the compressor to
equalize.
ody and terminal box from torch heat
an
damage. Also, slowly rai
se the pressure
Electrical Connections
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
NOTICE
Clean Flux From Joint!
Flux is corrosive and could lead to long-term problems
and equipment damage if not properly removed.
Quench the joint with water or a wet rag while the joint
is still hot—but below 900°F—to shock off the flux. If
not cleaned off, flux could hide leaks.
•Tandem (two compressors) and trio c
(three compressors) with uneven compressor
combinations requires the use of restrictor(s) to
balance the oil level in the compressor. Refer to unit
PART-SVN234B-EN25
ombinations
Page 26
Removal and Installation
BROWN
BLUE
BLACK
L1
M2
L3
L2
M1S2S1NL
L1
L3
L2
A
C
B
L1L3L2
M2M1NL
POWER
SUPPLY
MODULE INPUT
VOLTAGE
CONTROL
CIRCUIT
PHASING TO BE CONNECTED AS SHOWN TO
PREVENT REVERSE ROTATION
Blue dot
indicating T2
(Phase B)
Red dot
indicating T1
(Phase A)
Unmarked
T3
(Phase C)
182–361 Nominal Capacity
Before removing wires, mark them so that they can be
•
put back on the same terminal when the new
compressor is installed.
•Ensure that the compressor model terminals are
installed on the correct terminals (see
•If the compressor is not wired properly, it wi
within five seconds.
•Proper torque for the terminal screws is 25 in·lb.
Note: Wh
•Before st
en equipped with terminal stud with a nut,
torque the nut to 30 ±
2 in·lb.
arting the compressor
phasing with a phase sequence meter similar to an
Ideal-Sperry Model 61-520.
•Ensure that the compressor model terminals are
installed on the correct terminals (see
•Proper torque for the terminal screws is 25 in·lb.
Note: When
equipped with terminal stud with a nut,
torque the nut to 30 ± 2 in·lb.
Figure 21).
NOTICE
Improper Power Phasing!
Operating the compressor with improper phasing could
090–181 Nominal Capacity
The terminal blocks are marked with red and blue dots for
phase identification. Compressor terminal T1 is red,
compressor terminal T2 is blue, and compressor terminal
T3 is unmarked. Depending on the unit type, several
methods of marking the wires may be used, colored wires,
wire color marks on the wire or wire numbers to indicated
the proper location of the wire on the compressor terminal
block.
If the wires are not marked, ensure that you mark them
rior to removing them so that they can be reinstalled in
p
the same position.
26 PART-SVN234B-EN
cause compressor failure. Check phasing before starting
compressor.
•
Before starting the compressor, check the electrical
phasing with a phase sequence meter similar to an
Ideal-Sperry Model 61-520.
Leak Detection
WARNING
Hazard of Explosion!
Failure to follow instructions below could result in
death or serious injury or equipment or property-only
damage. Use only dry nitrogen with a pressure
regulator for pressurizing unit. Do not use acetylene,
oxygen or compressed air or mixtures containing them
for pressure testing. Do not use mixtures of a hydrogen
containing refrigerant and air above atmospheric
pressure for pressure testing as they may become
flammable and could result in an explosion. Refrigerant,
when used as a trace gas should only be mixed with dry
nitrogen for pressurizing units.
Page 27
Removal and Installation
WARNING
Hazardous Pressures!
Failure to properly regulate pressure could result in a
violent explosion, which could result in death or serious
injury or equipment or property-only-damage. When
using dry nitrogen cylinders for pressurizing units for
leak testing, always provide a pressure regulator on the
cylinder to prevent excessively high unit pressures.
Never pressurize unit above the maximum
recommended unit test pressure as specified in
applicable unit literature. See maximum recommended
unit test pressure below.
Pressure Testing
•Use industry-standard and EPA-accepted techniques
for testing.
•Pressure tests must be performed by qualified
rsonnel.
pe
•U
se tools especially designed for
•Do not exceed the high-side and low-side pressures
listed on th
•If no test pressure value is listed on the nameplate of
the unit, a pressure
acceptable.
e unit nameplate.
of no more than 150 psig is
leak testing.
NOTICE
Overpressure Damage!
Failure to follow these instructions could result in
compressor damage. Do not pressurize the low side of
the compressor by more than 5 bar (72 psig) higher
than the high side of the compressor within less than
two minutes.
•The 182–361 nominal capacity compressor has an
in
ternal check valve. When pressurizing the system, it
is important to never allow the low side pressure to
exceed the high side pressure by more than 5 bar
(72 psig). Greater pressure differen
compressor damage. Also slowly raise the pressure
over a 2-minute time period to allow sufficient time for
internal pressures in the compressor to equalize.
•Pressure decay testing can be used to check for gross
leaks but
•After pressurizing the system use an R-410A leak
detection devi
will not be able to detect the l
ce to detect and locate leaks.
tial could result in
ocation of a leak.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge
of
capacitors, see PROD-SVB06*-EN.
NOTICE
Compressor Motor Damage!
Failure to follow instructions below could cause
compressor motor damage. Never use the compressor
as a vacuum pump. Never meg-ohm test or apply
power to the compressor while it is in a vacuum.
•Ensure that there is no voltage being applied to the
compressor terminals.
•Evacuate the unit to 500 microns.
•Hold vacuum for 30 minutes.
•Rapid pressure rise indicates a
the leak.
•Slow pressure rise indicates on
– A small leak, indicated by a continuous rise in
pressure.
– Moisture in the system, indicated by
pressure and leveling-out at a pressure equivalent
to the moisture level. If this occurs, break the
vacuum with dry nitrogen and repeat evacuation
process to 500 micron.
•Once system is leak-tight, connect compressor re
the vacuum procedure, break vacuum with dry
nitrogen and evacuate to 500 microns. The vacuum
should be able to be maintained for four hours. Isolate
the vacuum
reads the system pressure.
•Vacuum must be measured in the refrigeration system
and n
pump so that the vacuum gauge only
ot at the vacuum pump.
leak; locate and repair
e of two possibilities:
a slow rise in
peat
Vacuum Testing and Evacuation
•Use the procedure as described in the unit
Operation, and Maintenance
•If no other information is available, use the following
information.
PART-SVN234B-EN27
manual.
Installation,
Page 28
Removal and Installation
Charging the System
WARNING
Hazardous Pressures!
Failure to follow safety precautions below could result
in a sudden rise of pressure possibly resulting in a
violent explosion which could result in death or serious
injury. If a heat source is required to raise the tank
pressure during removal of refrigerant from cylinders,
use only warm water or heat blankets to raise the tank
temperature. Do not exceed a temperature of 150°F. Do
not, under any circumstances apply direct flame to any
portion of the cylinder.
Use R-410A refrigerant only! Follow the instructions in the
un
Installation, Operation, and Maintenance manual for
it
proper charging methods.
If there are no instructions available, use
•Evacuate the unit as described in
Evacuation,” p. 27
•Ensure that the oil level is at least 1/2-sight glass in the
compressor
•Do not use the compressor to pull refrigerant into the
system.
•Charge liquid refrigerant into
unit—either into the condenser or liquid receiver, if so
eq
uipped.
•Charge as much of the unit refrigerant charge as
possible before
•Do not charge liquid refrigerant into the low side of the
compressor without the compressor runn
amounts of liquid may be metered through refrigerant
gauges into the suction line while the compressor is
operating.
•If the unit is equipped with suction and discharge
ice valves, close them du
serv
procedure.
Water chi
•
pumps while charging the unit to prevent freezing the
evaporator.
Failure to follow this instruction could result in a
compressor failure. Apply power to the crankcase
heater for a minimum of 8 hours prior to startup of the
compressor!
If the compressor is a replace
and has been charged in accordance with either the
procedures in the unit IOM or
p. 28
in this manual, the compressor could be immediately
started after charging the system. Th
that the refrigerant has not had sufficient time to migrate
to the compressor and cause potential damage upon
startup. The system should set for no more 8 hours or
overnight
h
eater operation. If the time exceeds 8 hours or the unit
sits overnight, the crankcase heater must be operational
for a minimum of 8 hours prior to starting the compressor.
If liquid refrigerant was charg
side during the charging procedure, damage could still
occur.
with a refrigerant charge without crankcase
ment for a failed co
“Charging the System,”
e reason for this is
ed into the suction or low
mpressor
Verification Before Start-Up
Follow the instructions in the unit
and Maintenance
available, use these guidelines:
•
Before starting the unit, verify that all service valves
open.
•Energize the crankcase he
before starting the compressor
28 PART-SVN234B-EN
manual. If there are no instructions
Installation, Operation,
ater a mi
nimum of 8 hours
are
Page 29
Startup
Follow the instructions in the unit Installation, Operation,
and Maintenance
available, use these guidelines:
Equipment Damage!
Failure to follow guidelines below could result in
equipment damage.
•Never start the compressor without refrigerant in the
system.
Never bypass the low pressure switch to start the unit.
•
•Monitor oil level for 60 minutes to ensure that oil
returns from the system.
•Check system pressures and tempe
the y are in line with unit design pressures. Refer to the
unit
Installation, Operation, and Maintenance manual
for this information.
•To top off the unit, charge liquid refrigerant may added
slowly thr
by
done only when the compressor is operating.
•Do not overcharge the unit.
•Recommended system full load superheats—unless
ecified differently in the unit
sp
and Maintenance
•Measure the oil sump superheat. Oil sump superheat
should be g
calculated as follows:
Oil Sump Superheat = Oil Sump Temperature –
Saturated Suction
•Measure
thermocouple on the bottom of the compressor,
eferably in the center, and insulate it. Calculate sump
pr
superheat. If less than 20°F, recheck the expansion
valve superheat and increase it. Low sump superheat
is indicated by foaming compressor oil.
•After fully charging the unit, recheck all pressure,
eratures, and electrical readings.
temp
•Ensure that the compressor protection module and
power supply wires are installed on the correct
terminals (see
•Proper torque for the terminal screws is 25 in·lb.
Note: Wh
manual. If there are no instructions
NOTICE
ratures to ensure
ottling it into the suction line. Th is must be
Installation, Operation,
manual—is 16°F–20°F.
reater than 20°F. Oil sump superheat is
Temperature
the oil sump temperature by placing a
Figure 20, p. 26 and Figure 21, p. 26).
en equipped with terminal stud with a nut,
torque the nut to 30 ± 2 in·lb.
PART-SVN234B-EN29
Page 30
Maintenance
Check the unit Installation, Operation, and Maintenance
manual for specific instructions.
Operating conditions must always remain within the
operating ran
•Operating pressures (suction and discharge pressure).
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. Verify with an appropriate
voltmeter that all capacitors have discharged.
For additional information regarding the safe discharge
of capacitors,
ge of the compressor. This includes:
, oil sump superheat, voltage, and
WARNING
see PROD-SVB06*-EN.
•Check electrical
season).
•C
heck unit operating controls.
30 PART-SVN234B-EN
connections (prior to startup each
Page 31
Troubleshooting
Important: Check the unit Installation, Operation, and
Maintenance
information regarding diagnosis and
causes.
manual for additional
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on
the tags, stickers, and labels could result in death or
serious injury.
Technicians, in order to protect themselves from
p
otential electrical, mechanical, and chemical hazards,
MUST follow precautions in this manual and on the
tags, stickers, and labels, as well as the following
instructions: Unless specified otherwise, disconnect all
electrical power including remote disconnect and
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be
inadvertently energized. When necessary to work with
live electrical components, have a qualified licensed
electrician or other individual who has been trained in
handling live electrical components perform these
tasks.
Compressor will not start
•Refer to the unit
Maintenance
and corrective action.
•Verify:
– Compressor voltage is correct.
82–361 nominal capacity compressors
1
–
protection module is the correct voltage.
– All safety switches are closed.
– All the contacts on the contactor are pulled in.
90–181 nominal capacity compressors
–
0
internal motor overloads may be open. Disconnect
power to the unit and disconnect the wires from the
compressor terminals. With an ohm meter, check to
ensure that there is resistance between T1-T2 and
T3.
Compressor will not build up pressure
•090–181 nominal capacity compressor is wired
incorrectly
amps. Shut the compressor off immediately. Running
in this condition for more than 5 seconds may damage
the compressor.
–361 nominal capacity compressor is wired
•
182
incorrectly
•Check to ensure that any bypass valves in the system
are not open.
•Four-way reversing valve may be stuck and not
switched properl
Installation, Operation, and
manual for possible diagnostics codes
—Moto
—The
—It will be noisy and draw 1/2 the expected
.
y bypassing from the high side to the
r
low side of the system; this situation is indicated by an
extremely warm suction inlet to the compressor.
60–361 nominal capacity compressors contain an
•
3
internal pressure relief that may have opened.
take two to three hours to reset. The oil sump will be
very warm and the compressor will be trippe
the motor protection module. This is caused by a very
high 625–715 psid difference between the high side
w side of the system. This could occur with either
and lo
a blocked high side or low side.
It may
d out on
Abnormal running noise
•Compressor is running backwards—Immediately shut
off the compressor and check wiring and proper
phasing.
•Excessive floodback—The superheat should be a
minimum
should be at least 20°F above the saturated suction
temperature. Measure the sump temperature at the
bottom center of the compressor. Chillers with
electronic expansion valves may operate with lower
superheats; check the unit
Maintenance
•Compressor is full of liquid on st
heater eith
eight hours, or it is defective.
•Mechanical damage to the compressor has occurred—
Check
compressor motor protection module or other unit
electrical protection devices such as circuit breakers.
of 16°F at full load and oil sump temperature
Installation, Operation, and
manual for proper operating superheats.
artup—The crankcase
er was not energized for a minimum of
compressor amperage. It may also trip the
High-pressure control opens
•Check the unit
Maintenance
and corrective action.
•Also check for:
– Defective condenser fan motors or controls.
– Dirty air-cooled or wate
– Restricted air flow.
– Insufficient water flow.
– System overcharged with refrigerant. Check
superheat
– Non-condensables in the system.
Installation, Operation, and
manual for possible diagnostics codes
d condensers.
r-coole
and system subcooling.
Low-pressure control opens
•Check the unit
Maintenance
and corrective action.
•Also check for:
– Defective evaporator fan motors, belts, or controls.
– Defective TXV valve.
– Plugged liquid line filter.
Installation, Operation, and
manual for possible diagnostics codes
PART-SVN234B-EN31
Page 32
Troubleshooting
– Liquid line solenoid valve does not open (if so
equipped).
– Dirty evaporators, either air-to-air or water-to-air.
– Restricted airflow.
– Insufficient evaporator water flow.
– System undercharged with refrigerant. Check
em superheat and subcooling.
syst
Compressor short cycling
•Check the unit
Maintenance
and corrective action.
•Also check for:
– Defective unit controls—maximum 12 starts per
r.
hou
– Compressors cycling on safety controls.
– Unit oversized.
– Building load is light—this is likely to occur
building occupancy
Installation, Operation, and
manual for possible diagnostics codes
ior to
pr
.
Motor protector module resets
•Type: Manual
Fault modes:
– Phase sequence
– Phase loss
– Multiple motor temperature overload cycles.
Reset—Remove power from mo
•Type: Auto with five-minute
4500 ohms)
Fault modes:
– Over current
– Running phase loss
– Motor over temperature (manual reset required
fter 2-5 auto reset cycles)
a
Reset—Auto-reset
ors resistance drops below 2750 ohms. Although
sens
module will reset automatically the compressor(s)
may not because the protection module may be wired
in a safety lockout circuit.
occurs when motor temperature
dule for five sec
delay (sensors exceed
onds.
Incorrect phase sequence
Incorrect phase sequence protection—compressor will
run approximately five seconds and trip off, pending the
motor protection module is correctly wired into the
system safety circuit. If the motor is believed to be
incorrectly phased; change two of the three wires.
PTC Overheat (motor over temperature/over
current)
•Compressor motor drawing too much current.
•Defective compressor; look for dark oil in
sightglass.
•Low voltage (voltage outside the
nominal voltage); voltage utilization range is printed
on compressor nameplate.
•Unbalanced voltage—must not exceed 2% imbalance.
•Motor PTC thermistor resistance above 4500 ohms will
cause the motor protector to open. The motor
protector will reset at resistance below 2750 ohms. A
five-minute time delay is active after cool down until
the maximum number of auto reset cycles has been
reached. The module will then be locked out until it is
manually reset.
±
the
10% range from
NOTICE
Excessive Voltage on PTC Sensors!
Failure to follow these instructions could cause
thermistor failure, resulting in a compressor
replacement. Do not measure the motor PTC sensors
with a device rated at more than 3 Vdc.
•When measuring the PTC sensors, do not use a meter
with gr
eater than 3 Volt.
360–361 nominal capacity compressor
•
valve has opened.
•Phase loss.
•Defective contactor.
•Loose or poor electrical co
or contactor.
nnections at the compressor
internal relief
182–361 Nominal Capacity Compressor
Motor Protection Module Diagnosis
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on
the tags, stickers, and labels could result in death or
serious injury.
Technicians, in order to protect themselves from
p
otential electrical, mechanical, and chemical hazards,
MUST follow precautions in this manual and on the
tags, stickers, and labels, as well as the following
instructions: Unless specified otherwise, disconnect all
electrical power including remote disconnect and
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be
inadvertently energized. When necessary to work with
live electrical components, have a qualified licensed
electrician or other individual who has been trained in
handling live electrical components perform these
tasks.
If M1-M2 contacts are open, proceed as follows:
1. Check motor protection module for the correct input
oltage on terminals L and N. Voltage applied to
v
32 PART-SVN234B-EN
Page 33
module must match module input voltage as printed
on module nameplate.
2. Check wire connection tightness.
3. Try to reset the module (i
five seconds).
4. If, after reset, module M1-M2 closes, determine which
fault caused module to tri
5. If M1-M2 remains open, proceed as follows:
Disconnect PTC thermistors from S1and S2 terminals,
d measure the resistance of the PTC using a device
an
with a maximum output of 3 volts.
• Resistance = ∞.
Open PTC open; replace compressor.
• Resistance = 0 ohms
PTC shorted; replace compressor.
• Resistance >2750 ohm
Wait until the motor has cooled down and
nce is less than 2750 ohms; reconnect and
resista
try to reset motor protector. Diagnose problem that
caused motor over temperature.
• Resistance = 150 ohms < R< 1250 ohms
Normal resistance value for PTC ambient
emperature.
t
nterrupt power for
p.
Troubleshooting
Test the module within the terminal box
1. Disconnect L-N voltage supply.
2. Disconnect S1-S2 PTC circuit on the module.
3. Disconnect M1-M2 safety circ
4. Apply a resistance between 150 and 1250 ohms across
S1-S2. This simu
5. Reconnect L-N voltage supply. Ensure that the voltage
L-N has been disabled for at least 5 seconds. This
to
will reset the module.
6. Check M1-M2 with ohmmeter.
7. M1-M2 closed—Module okay.
8. M1-M2 open—Module defective.
lates a functional, cool motor.
uit control contacts.
PART-SVN234B-EN33
Page 34
Log Sheet
Replacement Scroll Compressors
Complete and retain a record in the job file for future
reference.
If System Includes Liquid Line Solenoid, Verify Proper Opening/Closing
Log Sheet
Operating Controls Check
Low Pressure Control
High Pressure Control
Contactor
Replaced
Checked
Verify Proper Cycling of Unit Via Temperature Controls
Observations
Service Technician: Date:
PART-SVN234B-EN35
Page 36
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy
efficient indoor environments for commercial and residential applications. For more information,
please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.