Low Outdoor Ambient Operation
Unit Mounting
Minimum Clearances
Trane XR Style Outdoor Models
Page 2
The purpose of this bulletin is to provide application criteria as related to the Trane XR style condensing
units and heat pump units.
This bulletin discusses:
I.T erms and definitions
II.Off season cooling operation
III.Compressor crankcase heat requirements for split heat pump systems.
IV .Unit mounting
V .Minimum operating clearances
VI.Clearance from vents
VII.Nameplate electrical data
POSITION ST A TEMENT :
Trane has always recommended installing T rane approved, matched indoor and outdoor systems.
The benefits of installing approved matched sytems are maximum efficiency , optimum performance, and
best overall system reliability
W arnings and Cautions may appear throughout this manual. Read these carefully .
WARNING – Indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION – Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to alert against unsafe
practices.
CAUTION – Indicates a situation that may result in equipment or property-damage-
only accidents.
ISSUED BY :
Product Application Engineering Department
Trane a company of Ingersoll Rand
T yler, T exas
Section I - T erms and Definitions:
Three phase products:
All 2.5 to 5 ton three phase split system cooling units and heat pumps are shipped from
the factory with compressor crankcase heat. Three phase compressor do not require
start capacitors or start relays.
Definitions and information:
CCHT - Compressor Crankcase Heater, sometimes called a compressor sump heater .
This device is designed to warm the compressor crankcase (or sump) in order to prevent
or deter refrigerant migration during the compressor off cycle. Compressor crankcase
heaters are required for low ambient cooling operation.
TXV - Thermostatic Exp ansion Valve. This is a type of refrigerant flow control device
designed to maintain constant superheat throughout the operating envelope. For low
ambient cooling applications, a non-bleed TXV is required.
Bleed TXV: This type of TXV will allow the refrigerant pressures between the high side
and low side to equalize through the valve during the off cycle.
Non Bleed TXV: This type of TXV will not allow the refrigerant pressures between the
high side and low side to equalize through the valve during the off cycle. When using this
type of valve on single phase units with reciprocating style compressors, compressor
start components are required. Check product data specifications for most current information.
Head pressure controller - A device that is field installed on a condensing unit or heat
pump designed to maintain system head pressure that will allow safe system operation
without indoor coil icing in colder outdoor ambients. The BAYLOAM*** will cycle the
condenser fan motor in order to achieve adequate operating head pressure. The control
is adjustable.
Evaporator Defrost Control - A device that is field installed on the system’s indoor coil
in order to prevent the system from running during the cooling cycle when the indoor coil
approaches or reaches a temperature in which frost will form on the coil surface. When
the indoor coil approaches a safe temperature for cooling operation, the control will close
and allow the outdoor unit to restart. This controller makes and breaks the control voltage to the condensing unit.
Quick Start Component - This component may be factory installed or offered as a field
installed accessory ( BAYKSKT***). A quick start kit consist of a capacitor with a high
microfarad rating and a potential relay. It is installed so that the start capacitor is wired in
parallel with the compressor’s run capacitor . Prior to st art-up the potential relay contacts
are closed, therefore placing the start capacitor in the compressor circuit, as the compressor motor reaches operating speed, electrical current flows through the potential
relay’s coil and the the relay contacts are opened, thus taking the start capacitor out of
the system until the next compressor start up.
55°F - 30°F55°F - 30°F 55°F - 30°F 55°F - 30°F 30°F - 20°F or 30°F - 0°F see lowest approved OD ambient
Air
Conditioner
Heat Pump
55 deg F. As
Manufactu red
Air
Conditioner
AY28X079 3
Heat Pump
AY28X0843
TXV-NBCCHT
BAYLOAM103
BAYLOAM107
Start Kit
Solenoid
Valve (AC)4
Windshield
Lowest App roved
Outdoor Ambient
Cooling Mode
13 SEERXXXXXBAYLOAM103XXXApproved to 0 d eg F
14 SEERXXXXXBAYLOAM103XXX
AC Approved to 20 deg F
HP Approved t o 10 deg F
15 SEERXXXXXBAYLOAM103XXX
AC Approved to 20 deg F
HP Approved t o 10 deg F
16 SEER 1 , 2XXXXXBAYLOAM107 1XXX
AC Approved to 20 deg F
HP Approved t o 10 deg F
17 SEERXXXXXBAYLOAM103XXX
AC Approved to 20 deg F
HP Approved t o 10 deg F
Notes:
1 DO NOT apply BAYLOAM to model t onnages wit h variable speed condenser fan motors
2 Models with VS co ndenser fan motors ar e approved to 30 deg F wit h EDC or air hand ler with EEV
3 AY28X*** EDC not required when indoor unit has EEV
4 Liquid line soleno id shall be used for isolation purposes. Also used if liquid line is 1/2" and located before t he evaporator coil if AC is ab ove ID coil
See SS-APG006-EN Refrigeration P iping A pplicatio n Guide
Trane outdoor units may be operated in the cooling mode to 55°F outdoor ambient as shipped
from the factory when applied with an indoor TXV. Where required, these units with
appropriate accessories may be applied to operate at outdoor temperatures below 55°F.
Unit requires a compressor crankcase heater and start accessory only if it is not factory installed.
Compressor Crankcase Heaters:
Reciprocating Compressor: BAYCCHT300
Large Scroll Compressor: BAYCCHT301RES
Small Scroll Compressor: BAYCCHT302RES
As noted in the above table, systems may be operated lower than 55°F by applying the
BAYLOAM103 or BAYLOAM107 and other accessories. The BAYLOAM*** controller cycles
the outdoor fan motor as needed to maintain liquid line temperature as set by the DIP switches
located on the control. There is no need to change the outdoor motor on approved products since
the controller does not vary the frequency to the motor. However the BAYLOAM*** CANNOT
be applied to those model tonnages with a variable speed condenser fan motor.
Page 5
Windshields:
If low ambient cooling operation is required, windshields are a must in order to block prevailing winds from
impacting system performance at low outdoor temperatures. Reference figure 1.
Figure 1 - Windshield Construction Information
SHIELD DESIGN FOR
HIGHLY DIRECTIONAL WINDS
SERVICE
ACCESS
AREA
SEE NOTES
UNIT
12" MIN.
PREVAILING
WIND DIRECTION
SOLID PANEL
UNIT
4" MINIMUM
24" MAXIMUM
SHIELD DESIGNED FOR
NON-DIRECTIONAL WINDS
SERVICE
ACCESS
AREA
SEE NOTES
REMOVEABLE PANEL
OR GATE
FOR SERVICE
2 1/2" MIN.
UNIT
12" MIN.
SHADOW BOX FENCE
33% MIN. FREE AREA
EACH SIDE
UNIT
NOTE:
National Electrical Code
requires minimum three
feet clearance from the
service panel. Some local
building departments will
allow a removeable panel
in front of the unit service
access area. Otherwise the
distance between the
windshield and the unit’s
service access is required
to be a minimum of three
feet. Reference page 16 of
this document for National
Electric Code information
.
2" MINIMUM
4" MAXIMUM
Low ambient cooling utilizing the frost control in GAM5A and T AM4 indoor units:
The T AM4 and T AM7 fan coil units utilize an electronic expansion valve (EEV). W ith this enhancement the
controls that monitor the EEV also allow us to take advantage of monitoring coil temperature.
How it works:
The on-board electr onic controls include a r elay that will open when the indoor coil begins to fr ost.
When this occurs, the contacts to the YO circuit will open and de-energize the outdoor unit, provided
figure 2 and 3 are followed. When the YO circuit opens the outdoor unit is taken off line; however,
the indoor blower continues to operate, thus clearing the indoor coil of frost build-up.
Low ambient cooling utilizing thermostatic control found in the A Y28X079 and A Y28X084.
How it works:
These controls ar e thermally contr olled contacts with a capillary style sensor. The capillary tube is
inserted into the coil fins in between the tube rows. When the sensor detects 25F, the contacts open.
The contacts close when the coil temperature reaches 60F. When wired as shown in figures 4 and 5,
the outdoor unit is de-energized when the EDC contact opens and re-energizes when the EDC
Typical wiring the frost control located in TAM4 or TAM7 fan coil unit
Figure 2
Cooling split system and T AM4 or T AM7 fan Coil Unit
GAM5 or TAM7 Air handling unit
Cooling
unit
Y
B
*NOTE:
Y2 and BK is present
on TAM7 units and not
present on GAM5 or
TAM4.
W3
W2
W1
BK (see note*)
G
Y2 (see note*)
YI (in)
YO (out
O
R
B
Figure 3
Heat pump split system and T AM4 or T AM7 fan coil unit
GAM5 or TAM7 Air handling unit
Thermostat
W
G
Y
R
B
Thermostat
W3
Brown X2
Heat pump
unit
W2
W1
BK (see note*)
X2
W
G
G
Y2 (see note*)
Y
O
R
B
Yellow
Orange
Red
Blue
YI (in)
YO (out
O
R
B
Warning! High voltage present in the outdoor unit and indoor unit. Assure high
voltage power is disconnected using lockout / tag-out procedures if applicable
prior to connecting low voltage wiring.
Typical wiring when using the evaporator defrost control (EDC):
Figure 4 -
Single Speed Cooling Split System and AY28X079 Evaporator Defrost Control
Air handling unit
Red (R)
EDC
Cooling
unit
Y
B
Y
Y Low
Green (G)
White (W1)
White (W2)
White (W3)
Blue (B)
Figure 5 -
Single Speed Heat Pump Split System and A Y28X084 Evaporator Defrost Contr ol
R
Y
Thermostat
G
W
B
Air handling unit
R
Y
Thermostat
O
G
W
X2
B
Heat pump
unit
Brown / X2
Red
Yellow
Orange
Blue
EDR-1
EDC
EDR
Red (R)
Y
Y Low
Orange
Green (G)
White (W1)
White (W2)
White (W3)
Blue (B)
Warning! High voltage present in the outdoor unit and indoor unit. Assure high
voltage power is disconnected using lockout / tag-out procedures if applicable
prior to connecting low voltage wiring.
Section III - Compressor Crankcase Heat Requirements for Split Heat Pumps:
Figure 6 -Climatic Zones for United States
Compressor crankcase heat is
required in Climatic Zones 1, 2,
and 3 for all heat pump
applcations. Refer to the unit
product data catalogue for
cranckase
heater selection.
Section IV - Unit Mounting:
This section describes appropriate methods for mounting and securing the unit.
However, if these units are to be
mounted in a region where high winds are an issue, a Trane BA YECMT*** extreme conditions mounting kit.may
be utilized. Otherwise, a local P .E. and restraining method approved by the authority having jurisdiction may be
required. In regions where seizmic restraint is a requirement, approval from a local P .E. (professional engineer)
may be required for the restraining method. (refer ence figures 7, 8, and 9 for possible mounting configuration
examples)
A. For mounting or securing the Trane condensing units and heat pumps please observe the following:
1. If the unit is to be supported from the edge, the supporting material must
extend two inches
minimum under the perimeter of the unit’s base.
2. The mounting hole locations are molded in the basepan, however, must be drilled through.
a) Hole locations are identified in figures 10 and 11.
3. W ashers should be placed in between the fastener head and the basepan.
4. Trane recommends supporting the center of the unit as shown in figures 9, 10, and 1 1.
5. Base size 3 and 4 pans have four mounting holes - see figures 10 and 11.
6. For hurricane or high wind applications, if using the BA YECMT*** kit, the bolt hardness and diameter
is specified in the BA YECMT*** installation guide.
a) Bolt length is determined by the authority having jursidiction and / or local P .E.
b) Mounting surface composition and weight shall be determined by the authority having jurisdiction and /
or local P .E.
c) For non-ground installations, refer to a local P .E.
d) A local P.E. may be required if the BA YECMT*** kit is used or not.
support must extend in 2” from the basepan perimeter
support center of unit
335 (13.19)
221 (8.69)
Drill
4 places
Figure 10 - Base 3
support must extend in 2” from the basepan perimeter
294 (11.56)
171 (6.74)
Drill
4 places
688 (27.08)
580 (22.85)
482 (18.99)
599 (23.58)
Measurements are provided
in MM and (Inches)
310 (12.20)
158 (6.24)
Drill
4 places
support center of unit
795 (31.28)
717 (28.24)
317 (12.48)
213 (8.39)
Drill
4 places
599 (23.28)
727 (28.64)
Figure 11 - Base 4
If supporting the base pan from the perimeter, the support must extend under the base pan at least 2”. Trane recommends
supporting the middle of the base pan with a cross member.
This section discusses installating a condensing unit / heat pump where spacing is limited. When installing
Trane outdoor units in a location where clearance to other units, walls, fences, etc. is limited, the concerns
listed below must be addressed:
1. System Operation - Adequate airflow must be provided to and away from the condensing unit / heat
pump in order to enable appropriate heat transfer. If this is accomplished, head pressure will remain
within an effective operating range.
2. System Servicability - Sufficient working space must be allowed for the HVAC service technician to
properly maintain the condensing unit / heat pump. Furthermore, space must be allowed for major
component change out in the event of a failure. W orking space is determined by the Local, State and
National Codes. (See National Electric Code T able 110.26 for explanation.)
3. Space Maintenance - Appropriate space must be allowed in order to for personnel to maintain the
ground area where the units are positioned to prohibit foliage growth around the unit(s) and debris
from collecting on the panels.
3. State, Local Codes, and National Codes shall prevail. Check with the local jurisdiction before
installation to assure compliance.
Many projects require consideration of minimum clearances between outdoor units and adjacent walls,
fences and other units. The obstruction in question is usually one of the following:
1. One or more walls of an adjacent building.
2. Fences or barriers provided to reduce sound transmission or visually screen the equipment.
3. Other outdoor units in a multi-unit installation.
4. A combination of the above.
5. Overhangs
The prime considerations involved in establishing minimum clearances are:
1. Adequate airflow to the outdoor coil with minimum recirculation.
2. Service access to the equipment.
3. Compliance with the National Electric Code and other applicable codes.
4. Design temperature - Design temperatures greater than 105F require additional consideration.
I.In order to ensure adequate airflow reaches the condensing unit, size free air passages at 300 Feet Per
Minute maximum velocity . See condensing unit airflow performance on page 18 of this document.
II. The importance of providing proper service access to equipment cannot be overemphasized. The
HVAC service technician’s job may be performed with greater ease and lower cost if adequate service
space is allowed.
III. Knowledge of the National Electric Code and other applicable codes for the job site location is a
necessity in order to satisfy local inspectors. These codes are in place for serviceability as well as safety .
IV . Be sure to read all provisions and footnotes contained in this document.
V. Where ASHRAE design temperatures exceed 105F , minimum operating clearances may increase.
1. Installation of a single condensing unit / heat pump with one side facing wall, fence, or other
obstruction with free air space on top. (See Figur e 12)
A) For locations where the ASHRAE design ambient temperature is below 1 10F:
1) 6.0 inches clearance on 1 side. Three feet minimum clearance required from other three
sides from any obstructions.
2) Service access side - 3 feet minimum clearance required. Consult Local, State, and National
Electric Codes for minimum service clearance.
B) For locations where the ASHRAE design ambient temperature exceeds 1 10F:
Do not restrict any one side less than 1.0 feet. Refer to the unit’s installation manual or the
following pages of this document for more information regarding unit clearances.
Figure 12
-3.0’min
min
-6.0”-
Service Panel
3.0’ min
5 feet minimum unrestricted top
clearance shall be provided.
min
3.0’-
2. Installation of a multiple condensing units / heat pump units with one side facing wall, fence,
or other obstruction with free air space on top. (See Figur e 13)
A) For locations where the ASHRAE design ambient temperature is below 1 10F:
1) 6.0 inches clearance on 1 side. Three feet minimum clearance required from other three
sides from any obstructions.
2) Service access side - 3 feet minimum clearance required. Consult Local, State, and National
Electric Codes for minimum service clearance.
B) For locations where the ASHRAE design ambient temperature exceeds 1 10F:
Do not restrict any one side less than 1.0 feet. Refer to the unit’s installation manual or the
following pages of this document for more information regarding unit clearances.
5 feet minimum
unrestricted top
clearance shall
be provided.
Service Panel
Page 12
3. Installation of a single unit in a corner with free air space on top. (See Figur e 14)
A) For locations where the design ambient temperature is below 105F:
1) 1.0 feet clearance on 2 sides - If foliage is to be placed by the unit other side, then allow 1.0
Feet minimum clearance from the unit
2) Service access side - 3 feet minimum clearance required. Consult Local, State, and National
Electric Codes for minimum service clearance.
B) For locations where the design ambient temperature exceeds 105F:
1) 1.5 feet clearance on 2 walls. - If foliage is to be placed by the unit other side, then allow 1.0
Feet minimum clearance from the unit.
2) Service access side - 3 feet minimum clearance required.
C) If unit is located in such a way that service panel is facing the wall
1) NEC requires 3 feet minimum clearance between the unit and the wall
a) This space may be increased to 3 1/2 feet. Consult the National Electric Code for more
information regarding minimum clearances for working spaces.
Figure 14
min
-1.0’-
Service
Panel
5 feet minimum unrestricted top
-1.0’min
min
-1.0’-
3.0’ min
clearance shall be provided.
4. Installation of two or more units where two adjacent walls form a corner . (See Figur e 15)
A) For locations where the design ambient temperature is below 105F:
1) Note the unit base size and obtain the minimum clearance values from the table below .
B) For locations where the design ambient temperature exceeds 105F:
1) 2.0 feet clearance from both walls.
2) 3.0 feet clearance in between units, unless service panels face each other . (if service panels
face each other, this clearance may be increased to 4 feet per NEC)
C) If unit’s are located with the service panels facing the wall
1) NEC requires minimum 3 feet between the unit and the wall
a) This space may be increased to 3 1/2 feet. Consult the most current edition of the National
Electric Code for more information regarding minimum clearances for working spaces.
2B indicates to multiply the B dimension
from Table 3 by 2.
5 feet minimum unrestricted top
clearance shall be provided.
Page 13
5. Units surrounded on all four sides: (See Figure 16, 17, 18, 19 and 20)
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
6
A. If installed unit(s) is / are surrounded by 2 walls and a solid fence, fence height on two sides shall be
no higher than the height of the unit. In this application knockouts or louvers shall be provided on two
sides minimum with free area to provide maximum 300 FPM velocity . Cutting a portion of the lower
fence on two sides to accomplish 300 FPM maximum velocity is acceptable provided debris, dirt, and
grass is prohibited from accumulating or growing to obstruct the opening. Refer to page 19 of this
document for outdoor unit airflow . Please refer to table below for minimum clearances.
Figure 16Figure 17
A
5 feet minimum top clearance
A
Service
Clearance*
A
shall be provided.
A
Figure 18
A
A
2B
* If removable panels are used and acceptable to local inspection agency, the clearance to the removable
panel may be reduced to (1.5 X the A dimension from Table 3)
A
2B
Service Clearance*
AA
2B
A
A
A
Service
Clearance*
These clearances apply in
geographical
locations in
which the
ASHRAE design
outdoor dry bulb
= 105F or less.
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Figure 19
Unit
location
SIngle Unit - Solid Fence
Solid Fence: If fence height is taller than unit(s), provide
openings in fence that will provide maximum 300 FPM air
velocity. These openings shall be located at the lower portion
of the fence. If acceptable, the fence may be raised to
provide open bottom clearance of fence height above the unit.
6. Installation of multiple units on a pad / rooftop where the top clearance is open. (See Figure 21)
A) Refer to minimum clearance table in the lower corner of this page for clearances
B) National Electric Code requires 3 feet minimum (4 feet if certain conditions are present) clearance between service access panel and adjacent unit.
If service access panel faces the wall, the
required space between the the wall and the unit shall be minimum 3 feet. (May require as much as
3 1/2 feet)
C) W alls shall not be higher than top of units.
D) National, State, and Local Codes must be observed.
E) If design outdoor dry bulb exceeds 105F (40.6C) add 1.0 Ft. to all dimensions.
Figure 21
A
min**
A
min**
A
min**
2B
min
Service Access *
min
-3.0’-
Service Access *Service Access *Service Access *
2B
min
3.0’
min
Service Access *
Service Access *
Service Access *
A
min**
min
-3.0’-
3.0’
min
2B
min
Service Access *
2B
min
Service Access *
A
min**
min
-3.0’-
3.0’
min
The measurement 2B indicates to
multiply the dimension B from
table 3 by 2 in order to determine
the appropriate minimum distance between units.
A
min**
A
min**
* Units may be rotated in order that service access sides face each other
provided that 3 feet minimum clearance is maintained between the units. In
order to comply with NEC, this may increase to 4 feet minimum clearance.
** If wall or fence is to be constructed around the entire perimeter of the
mechanical yard, Maintain minimum 1.5 feet clearance from the units. The
fence height shall not exceed that of the unit. It is recommended to install
louvers in the fence to allow no greater than 300 feet per minute velocity.
Consult table 6 for unit airflow. Place louvers in the lower section of the
fence by each unit in order to provide air access to each unit located by the
fence. The lower portion of the fence may also be cut in order to equal the
calculated free area.
7. Installation of multiple units on raised rooftop rail where the top clearance and side clearance
is open. (See Figure 22)
A) Area between outdoor units shall be open in order than air may be drawn from top, bottom
and sides.
B) Decorative walls shall be at minumum 10 feet away from the outdoor units.
C) Decorative walls shall not extend above the unit tops.
A) National Electric Code requires 3 feet minimum (4 feet if certain conditions are present)
clearance between service access panel and adjacent unit.
D) National, State, and Local Codes shall be observed.
E) If design outdoor dry bulb exceeds 95F (35.0C) add 1.0 Ft. to all dimensions.
Photo for illustration purposes - area between units open for air to draw from top, bottom, and sides.
2
2
2
2
2
2
2
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
2
2
2
2
2
2
Service Access *
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Service Access *
2
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
2
2
2
2
2
min
-3.0’-
Figure 22
36.0”
min
36.0”
min
2
2
2
2
2
2
2
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
2
2
2
2
2
Service Access *
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Service Access *
2
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
23456789
2
2
23456789
2
2
2
2
2
2
2
2
2
2
min
-3.0’-
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2345678
2
2
2345678
2
2
2
2345678
2
2
2345678
2
2
2345678
2
6.0”
2
2
2345678
2
min
2
2345678
2
2
2345678
2
2
2345678
2
2
2
2
2
2
2
2
2
Service Access *
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Service Access *
2
2
2
2
23456789
2
2
23456789
2
2
23456789
2
2
2
23456789
2
6.0”
2
23456789
2
2
min
23456789
2
2
2
23456789
2
2
23456789
2
2
2
2
2
2
2
2
2
2
min
-3.0’-
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Page 16
Electrical Code Information
Compliance with Local, State, and National Codes is a must on every HVAC Installation. This page
discusses the criteria regarding minimum working spaces as defined in the 2007 National Electric Code.
The main concern is the safety of the HV AC service / maintenance person. Minimum working clearances
are specified in the National Electric Code (NEC) Article 1 10.26
For electrical equipment that from ground to power the voltage is 600 volts or less:
The National Electric Code specifically states that service area around electrical equipment shall provide
sufficient access, and shall be properly maintained in order to permit safe operation and maintenance of the
equipment. Figure 22 includes T able 110.26 from the National Electrical Code as well as Condition 1, 2,
and 3 beside table 110.26. Conditions 1, 2, and 3 describe the minimum clearance for proper service and
access to electrical equipment.
Trane residential and light commercial condensing units ranging from 1 to 6 ton require access to the side
service panel as indicated on the previous pages as well those listed in Condition 1, 2, or 3 to gain access
to the electrical controls.
Figure 23
The table and figure below are excerpts from the National Electric Code:
Table 110.26(A)(1) Working Clearances
Nominal
Voltage to
Ground
0-150 900 mm (3 FT) 900 mm (3 FT) 900 mm (3FT)
151-600 900 mm (3FT) 1 M (3.5FT) 1.2 mm (4FT)
Note: Where the conditions are as follows
Condition 1 - Exposed live parts on one side and no live or grounded parts
on the other side of the working space, or exposed live parts on both sides
effectively guarded by suitable wood or other insulating materials. Insulated
wire or insulated busbars operating at not over 300 volts to ground shall not
be considered live parts
Condition 2 - Exposed live parts on one side and grounded parts on the
other side. Concrete, brick, or tile walls shall be considered as grounded.
Condition 3 - Exposed live parts on both sides of the work space (not
guarded as provided in Condition 1) with the operator between.
Section VI - Minimum Clearances From Vents: (See Figure 24)
This section deals specifically with installations in which a dryer vent, kitchen exhaust vent, or furnace vent is
located near the condensing unit / heat pump unit.
A. Condensing units and heat pumps shall be located not less than five feet from clothes dryer
vents.
1. Do not locate the condensing unit / heat pump unit directly below a clothes dryer vent.
B. Condensing units and heat pumps units shall be located not less than three from any kitchen
exhaust vent.
1. Do not locate the condensing directly under a kitchen exhaust vent.
C. Condensing units and heat pump unit shall be located not less than three feet vertically from
any natural gas appliance vent outlet or inlet in which the condensing unit / heat pump unit is
within a 10 feet diameter of the appliance vent termination.
Gutter or other acceptable means to prohibit direct
contact by roof run-off water may be utilized if
clearance is not available from building structure.
Figure 24
Kitchen Exhaust Vent
3’
5’
3’
Furnace
Vent
10’
Dryer Vent
5’
D. Code Compliance:
1. Local, State and National codes shall be adhered to for all installations.
E. Manufacturers Instructions:
1. Always consult the manufacturers instructional manuals. These manuals contain information specific to the device or appliance being installed.
F. V ents other than discussed in this document:
1. The intent of this document is not to discuss every possible venting device nor all types of
gasses, vapors, and spaces that are mechanically vented or naturally vented by draft. Please
consult local, state and national codes. In the absence of codes, or if the installer is unfamiliar
with local, state and national codes, a professional engineer or local building department
should be utilized as a resource.
Quantity of 4 units in a mechanical yard, surrounded by a fence. Units are 4TTR6042B1000A
Required:
Determine free air opening space required in fence.
Solution:
4420 CFM x 4 units = 17,680 CFM
17,680 CFM / 300 FPM = 58.93 (59) square feet of free air opening in the fence sections
surrounding the mechanical yard.
Page 19
VII.Nameplate Electrical Data
Figure 25
Figure for reference only
Voltage Range -Units are tested @ 10% below the lowest
rated voltage and 10% above the highest rated voltage.
Ph - 1 for single phase, 3 denotes three phase
Hz - Frequency
Minimum Circuit Ampacity - the lowest current in which
the branch circuit conductor shall be rated. Reference National Electrical Code, local electrician or local building authority for assistance with wire sizing. (reference NEC Article
440.35)
Minimum Fuse / Breaker (HACR) - if this marking is present
on the nameplate indicates the lowest rated overcurrent branch
circuit protection device allowed for the appliance. (reference
NEC Article 440.22)
Maximum Fuse / Breaker (HACR) - the largest rated
overcurrent branch circuit protection device allowed for the
appliance.
Please note that all installatons shall comply to the codes adopted by the
authority having jursidiction. Questions regarding adopted codes should
be directed to the local building department prior to installation. Articles from
the National Electric Code include but are not limited to:
Article 210 - Branch Circuits
Article 240 - Overcurrent Protection
Article 310 - Conductors for General Wiring
Article 422 - Appliances
Article 424 - Fixed Electric Space Heating Equipment
Article 430 - Motors, Motor Circuits, and Controllers
Article 440 - Air Conditioning and Refrigerating Equipment