Trane SRV-SVX04C-EN Installation And Maintenance Manual

Page 1
Installation, Operation, and Maintenance
product image goes here, centered on page
Trane Rental Services
Desiccant Dehumidification Units
SAFETY WARNING
August 2022
SRV-SVX04C-EN
Page 2
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTIONs
NOTICE
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous si
tuation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
WAYS refer to the appropriate SDS and OSHA/GHS
AL (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized elec flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
trical contact, arc, or
©2022 Trane SRV-SVX04C-EN
Page 3
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Trane personnel must follow the company’s Env
ironmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Introduction
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Updated the General Information chapter.
Updated the Installation and Start-up Guidelines in the Unit Specifica
Updated the Installation Controls chapter.
tions chapter.
SRV-SVX04C-EN 3
Page 4
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . 5
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Specifications and Weights . . . . . . . . . . . . 6
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Start-up Guidelines . . . . . . . . . . . . . . . . . . . . . 7
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation - Controls . . . . . . . . . . . . . . . . . . . . . . 9
Customer Interface . . . . . . . . . . . . . . . . . . . . . 9
Auxiliary Dry Contacts - Operational System
States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Main Power Initialization Sequence . . . . . . . 9
Normal Start-up . . . . . . . . . . . . . . . . . . . . . . 9
Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Faults and Warnings . . . . . . . . . . . . . . . . . . . 10
Alarm Indication . . . . . . . . . . . . . . . . . . . . . 10
List of System and DH Warnings . . . . . . . . 11
Proportional Control Loops/ DH Interlocks . 11
Human Machine Interface Control
(Op73 Simatic Panel) . . . . . . . . . . . . . . . . . 12
Fan Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Shutdown and Maintenance . . . . . . . . . . . . . . . 15
Shut Down Guidelines . . . . . . . . . . . . . . . . . . 15
Maintenance Guidelines . . . . . . . . . . . . . . . . 15
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 16
4 SRV-SVX04C-EN
Page 5
General Information
Overview
This manual covers the desiccant dehumidification units (DHU) available to rent from Trane Rental Services for temporary dehumidification solutions. This includes DHU technical information, start-up information, and unit maintenance. Information contained in this manual is provided to ensure the safe installation and operation of the equipment and its surroundings.
Use this manual as a reference to determine unit size, power
irements, or lifting requirements. If additional information
requ is required, contact Trane Rental Services (TRS).
Prior to securing rental equipment, contact TRS for availability
ncluding ancillary items: electrical cable, flexible duct, etc.
i Equipment is available on a first-come, first-serve basis, but can be reserved with a signed rental agreement.
Trane Rental Services DHUs are highly efficient at providing
an, dehumidified air with minimal electrical power required.
cle The DHUs can be used in free blow or ducted applications. Each unit has a single horizontal supply air connection, single return air connection, and is equipped with a post-cooling coil to aid in reducing leaving air temperatures when required. When used in free blow applications, ducting on the front of the unit must be removed. Flexible duct is available upon request.
Table 1. RSDH5000 Desiccant dehumidification unit
Manufacturer - Munters™
Airflow
Post-cooling Coil Water Connection(s)
Supply Air Connection(s)
Return Air Connection(s)
Reactivation Air Connection(s)
Pre - Filter
Note: Unit can be provided with reducer to provide either 2.5 inch or 4 inch grooved water co nnection to allow connection to our flexible water hose accessories.
Orientation Horizontal
Nominal Airflow 4,750 cfm
Blower RPM 3500
Max Static Discharge Pressure 1.70 in. ESP
Type Flanged
Size 3 inches
Typ e Round
Quantity 1
Size 17.75 inches
Typ e Round
Quantity 1
Size 17.75 inches
None (Free Blow)
Type 30% efficient
Quantity and Dimensions
Inlet Delta P 0.21 in. wc
Final Delta P 0.42 in. wc
(2) 12 in. x 24 in. (2) 24 in. x 24 in.
SRV-SVX04C-EN 5
Page 6
Unit Specifications and Weights
Table 2. Unit specifications
Dehumidifier
Process Air Reservation Air
Desiccant Type
SiGel
Fans
Location
Supply
React
Post Cooling Coil
Typ e
Post Cool
SCFM
4750 102 1.82 2.12 1050 1.63 3.00 Electric 84
Size Rotation Motor HP RPM SCFM
15 CW 10 3500 4750 7.04 5.34 1.70 3
12-1/4-7 CW 3 3450 1050 4.50 3.00 1.50
SCFM Load MBH P (in.
4750 366 1.58 10 10 12 57 24.5
Moisture Removal
(lb/hr)
Fan Data Performance
Airside Values Coil Dimensions Fluidside Values
Table 3. Dimensions and weights
Length Width Height Weight
15 ft 2 in. 6 ft 2 in. 6 ft 5 in. 4175 lb
WheelP
(in. wc)
wc) Face ft
Unit P
(in. wc)
SCFM
2
Rows FPI Flow (gpm) P (ft)
WheelP
n. wc)
(i
TSP
(in. wc)
Unit P
(in. wc)
Sys Loss
(in. wc)
Energy Type Input kW
ESP
(in. wc)
T
Rigging
DHUs are equipped with fork pockets on two sides and lifting rings along the base of the unit.
WARNING
Heavy Objects!
Failure to follow instructions below could result in unit dropping which could result in death or serious injury, and equipment or property-only damage.
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
Figure 1. Desiccant dehumidification unit
6 SRV-SVX04C-EN
Page 7
Installation
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury.
Disconnect all electric power disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Verify that no power is present with a voltmeter.
1. Confirm unit is level.
2. Verify air inlet and outlet are clear of any debris or obstructions.
, including remote
Figure 2. Main unit disconnect
NOTICE
Proper Airflow!
Failure to follow the instructions below could result in equipment damage.
The reactivation air from the unit could be in excess of 180
°F. Do not position unit where reactivation outlet air could come into contact with sensitive materials and cause equipment and property damage.
3. Connect power cable from unit to the power source and confirm wires are pro securely to panel.
a. For ducted applications, install the supply and return air
ucts on the duct adapters (front of the unit). Ensure
d duct is straight.
b. For free blow applications, no duct installation is
quired.
re
perly phased, connected, and locked
Start-up Guidelines
1. Verify that the unit disconnect is in the OFF position on the unit.
2. Energize the source power to the DHU.
3. Switch the unit disconnect ON to supp
ly power to the unit.
4. Refer to “Installation - Controls,” p. 9 for unit operation.
5. Close all covers (local and remote panels) and secure.
SRV-SVX04C-EN 7
Page 8
Electrical Data
DHUs have connections to allow for use with TRS available 2/0 electrical cable. Below is a list of electrical data for these units. If additional information is needed, contact Trane Rental Services.
Table 4. Electrical data - RSDH5000
Fused Disconnect? Ye s
Unit Power 460V, 3-phase
Unit MCA 154.1 A
Unit MOP 175 A
Supply Motor FLA 11. 6 A
Reactivation Motor FLA 3.6 A
8 SRV-SVX04C-EN
Page 9
Installation - Controls
Customer Interface
Start the system in Auto mode using the AUTO/OFF/ MANUAL selector to interface with customer supplied
equipment.
Start the system in Auto mode by selecting the contact
through the ON/OFF selector switch between
closure TB06#61 and TB06#10.
MANUAL mode does not require the dry contact closure
to enable the system to start.
input
The selector switch has an integral to indicate the equipment has power.
light and will illuminate
Auxiliary Dry Contacts ­Operational System States
SYSTEM FAULT - Auxiliary dry contacts of CR02 are provided for customer interlocking and will close when the dehumidifier goes into any fault as described in the list of system and DH warnings. See
Warnings,” p. 11
SYSTEM contacts of MS03 are provided for customer interlocking and will close when the process blower is in operation.
SYSTEM W provided for customer interlocking and will close when the dehumidifier goes into a warning condition.
D/H RUN ­customer interlocking and will closed when the dehumidifier is in operation.
.
RUN (CONTROL RELAY) - Auxiliary dry
ARNING - Auxiliary dry contacts of CR03 are
Auxiliary dry contacts of MS02 are provided for
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
“List of System and DH
Start-up
Main Power Initialization Sequence
1. Energize the main power to the equipment by supplying correct voltage directly to the unit using the system main fused disconnect.
Note: The sel
2. High voltage is supplied to all motor starters and control transformer(s). supplied to the control circuits.
3. The HMI LCD (located on or in, visible through the door) mai System Screen. See
4. There is a 10 second delay in the eq power is activated by the selector switch.
Figure 3. HMI LCD
ector switch will illuminate indicating the
equipment is energized.
The control voltage (115V/1Ø/60Hz) is
n control enclosure is energized and will display
Figure 3.
uipment start-up once
Normal Start-up
Normal start-up occurs when the main selector switch (SS01) is placed in the MANUAL or AUTO position with a customer­supplied auxiliary interlock (dry-contact) closed between TB06#61 and TB06#I0.2.
Shutdown
A normal shutdown will occur if:
Selector switch (SS01) is maintained in the OFF position.
Selector switch (SS01) is maintained in AUTO position with a contact opening across TB06 # 61 and TB06 # I0.2.
A fault has occurred.
Normal shutdown sequence of operation:
1. The reactivation control proportional control loop and fault circuits are de-energized.
2. The process control loops are de system and DH warnings. See
Warnings,” p. 11
3. A purge timer in the (PLC1) is a delay time with a fixed, on
of three minutes. This allows the air to continue to cool
time the desiccant wheel. When the timer has completed its count cycle, the desiccant wheel drive motor (MTR1), the
.
-energized in the list of
“List of System and DH
SRV-SVX04C-EN 9
Page 10
Installation - Controls
reactivation blower motor (MTR2), and supply blower motor (MTR3-optional) are all de-energized.
NOTICE
Equipment Damage!
Failure to follow all instructions could result in equipment damage!
Do not shut down unit by de-energizing main power pr
ior to the completion of the purge cycle. Wait for PURGING to change to STANDBY or READY before de­energizing main power.
Faults and Warnings
Important: Press ESC or Help button twice quickly to exit
back to the system screen at any time during screen navigation.
Table 5. List of system and DH faults
Fault Description
If the desiccant drive motor starter/protect
The system will go into the shutdown (
acts close in sequence (
cont blower (optional) will purge.
The dehumidifier will be held in the Fault condit
FAULT - D/H WHEEL MOTOR STARTER PROTECTOR
TRIPPED
FAULT - REACTIVATION MOTOR STARTER PROTECTOR TRIPPED
FAULT - SUPPLY BLOWER MOTOR STARTER PROTECTOR TRIPPED/ VFD FAULT (optional)
To restart the dehumidifier:
1. Clear the alarm pressing the acknowledge ACK on the HMI.
2. Reset the overload, go to the ALA the PLC.
To restart the system:
1. Move the selector switch (SS01) to the OFF position.
2. Move the (SS01) back to the AUTO or MANUAL position.
If the reactivation blower motor starter/protector
The dehumidifier goes into t
operation:,” p. 9
The dehumidifier will be held in the Fault condition by (PLC1). To restart the dehumidifier:
1. Clear the alarm pressing the acknowledge ACK on t
2. Reset the overload, and go to the ALARM screen, and press the F4 RESET key, which resets the PLC.
To restart the system:
1. Move the selector switch (SS01) to the OF
2. Move the (SS01) back to the AUT
If the supply blower motor starter/protector (MSP3) trips or the customer-supplied variable frequency drive (VFD) goes into a Fault, the system is faulted.
The system goes into the shutdown sequence. See
, and “Auxiliary Dry Contacts - Operational System States,” p. 9.
p. 9
The dehumidifier will be held in the Fault condition by (PLC1). To restart the dehumidifier:
1. Clear the alarm pressing the acknowledge ACK on t
2. Reset the overload, and go to the ALARM scree resets the PLC.
To restart the system:
1. Move the selector switch (SS01) to the OFF position.
2. Move the (SS01) back to the AUTO or MANUAL position.
and “Auxiliary Dry Contacts - Operational System States,” p. 9.
Alarm Indication
Fault and warning indication include the HMI display and fault warning lights. The HMI will display the blinking triangle with exclamation point and the fault message on the Alarm screen.
Figure 4.
See
A fault results in the red light (L
Figure 4. HMI alarm indication
or (MSP1) trips, the system is faulted.
“Shutdown,” p. 9) sequence and the system auxiliary dry
“Auxiliary Dry Contacts - Operational System States,” p. 9), process
ion by (PLC1).
RM screen, and press the F4 RESET key, which resets
(MSP2) trips, the system is faulted.
he shutdown sequence. See
F position.
O or MANUAL position.
“Normal shutdown sequence of operation:,”
n, and press the F4 RESET key, which
T02) constantly illuminating.
“Normal shutdown sequence of
he HMI.
he HMI.
10 SRV-SVX04C-EN
Page 11
Table 5. List of system and DH faults (continued)
Fault Description
Limit switch (LS01) is wired normally closed and located inside the dehumidifier wheel compartment next to desiccant wheel. As the wheel turns, a cam fastened to the wheel housing opens this limit switch.
If limit switch (LS01) is not opened once every 600 seconds, a timer in (PLC1) times out the system is faulted.
The system goes into the shutdown sequence. See
and “Auxiliary Dry Contacts - Operational System States,” p. 9.
p. 9
FAULT - DEHUMIDIFIER WHEEL ROTATION
FAULT – REACTIVATION ELECTRIC HEATER
OVERTEMPERATURE
The dehumidifier will be held in the Fault condition by (PLC1). To restart the dehumidifier:
1. Clear the alarm pressing the acknowledge ACK on the HMI.
2. Reset the overload, and go to the ALARM screen, and press the F4 RESET key, which resets the PLC.
To restart the system:
1. Move the selector switch (SS01) to the OFF position.
2. Move the (SS01) back to the AUTO or MANUAL position.
Temperature switch (TS01) is in the reactivation electric heater and will detect extreme temperature level or heat buildup.
Temperature switch (TS01) is in the reactivation heated to duct and will detect extreme temperature level or heat buildup.
The system goes into the shutdown sequence. See
p. 9
and “Auxiliary Dry Contacts - Operational System States,” p. 9.
The dehumidifier will be held in the Fault condition by (PLC1). To restart the dehumidifier:
1. Clear the alarm pressing the acknowledge ACK on the HMI.
2. Reset the overload, and go to the ALARM screen, and press the F4 RESET key, which resets the PLC.
To restart the system:
1. Move the selector switch (SS01) to the OFF position.
2. Move the (SS01) back to the AUTO or MANUAL position.
Installation - Controls
“Normal shutdown sequence of operation:,”
“Normal shutdown sequence of operation:,”
List of System and DH Warnings
WARNING – REACTIVATION LOW TEMP
LOW TEMP (Reactivation Low Temperature Fault Set point). The adjustment range is 90.0 to 110.0. The parameter corresponds to the value of the set point in engineering units (Typical set point = 110°F).
Proportional Control Loops/ DH Interlocks
Reactivation Heat Energy Control
The reactivation electric heater solid state relays will accept a 0-10V modulating signal from the logic controller to control the reactivation inlet air temperature.
This is sensed by the reactivation air inlet temperature transmitter (TC01).
The reactivation inlet temperature set point will vary based on the reactivation outlet control PID loop to maintain maximum, required reactivation inlet temperatures over a wide range of DH load conditions.
When the reactivation outlet PID loop output is 0% the reactivation inlet set point will be 200°F.
When the reactivation outlet PID loop output is 100% the reactivation inlet set point will be 325°F.
SRV-SVX04C-EN 11
Page 12
Installation - Controls
Human Machine Interface Control (Op73 Simatic Panel)
Note: Other visual options are password protected for
FACTORY USE ONLY.
Table 6. Screen descriptions, navigation, and security
System Screen is the first screen that comes up when power is applied to the equipment (Figure 2). The System screen displays the equipment’s operational status along with separate indication for the Reactivation air stream. The System screen also acts as the navigation portal for all of the screens configured in the system. All navigation references in this section assume the operator starts on the System screen. At any time during navigation, the ESC button on the Simatic Panel may be pressed twice to return to the System screen.
“SYSTEM” displays the modes of operation of the process as listed below:
READY The system is ready to run and there are no f
RUNNING The system is running, and process control loops are running if enabled.
FAULTED The system has faulted.
PURGING The system is going through a shutdown seque
REACT Displays the modes of operation of the dehumidifier as listed below:
READY The DH is ready to run and there are no faults, and the interlocks are made.
RUNNING The DH is running, and process control loops are running if enabled.
FAULTED The DH has faulted.
PURGING The DH is going through a shutdown sequence and is purging.
STANDBY The system is running, and the DH stopped because the
aults and the interlocks are made.
nce and is purging.
re is no call for dehumidification (full bypass).
1. Reactivation Temperature
a. Pressing the Up Arrow once navigates to this screen
(
Figure 5).
b. The Reactivation Temperature screen displays the real
dication of the reactivation inlet and outlet
time in temperatures (degrees Fahrenheit).
Figure 5. Reactivation temperature
2. Date/Time
a. Press the Up Arrow twice navi
(
Figure 6).
gates to this screen
b. The Date/Time screen displays the current date and
This may be configured by the customer using the
time. correct username and password.
c. The display will change to the Username and Password
screen (
Figure 7), prompted by pressing F1.
Figure 6. Date and time
Figure 7. Username and password
3. Username and Password
The operator will be prompted by the password screen (
Figure 7) when secure parameters are accessed.
Important: C
ontact Rental Services Technical Support if a
password is required.
The ENTER
button will reverse highlight the character for
editing.
a. Use the arr
ow buttons as necessary to select the
desired characters.
b. Once the last character h
as been located, press ENTER, to proceed to the password window. Important! Do not press any arrow.
12 SRV-SVX04C-EN
Page 13
Installation - Controls
c. Press ENTER again to edit the password.
d. Once the last character has been located press
ENTER. Do not press any arrow.
e. OK wil
l display a dotted box. Press ENTER to accept, and the screen will return to make the selection without security restriction.
4. Run Time Meter
a. Press the Down Arrow once to navigate to this screen
Figure 8).
(
Figure 8. Runtime meter
Table 7. System loops
1. Press F2 (ALM) to navigate to this screen (
2. The Alarm screen displays the Faults and Warnings the system encountered during operation. The triangle with exclamation
Alarms
F4 Reset
F1 CLEAR History
point will indicate to the operator when an alarm condition exists.
3. Press the ACK button to clear the current alarm message without clearing the history.
Note: The Alarm Screen displays and records information on triggered alarms. Each time an alarm is triggered, it is added to the Alarm History
list
Figure 10, and the last alarm is displayed.
1. The operator must press the F4 button to reset a fault in the PLC. This will clear all system faults and enable the equipment to be restarted by cycling the selector switch.
2. The selector switch may also be used as the system reset by turning it to the OFF position and return it to the AUTO or MANUAL position.
3. Press the a
4. The system screen will display READY after a fault has been reset.
1. The alarm history (see alarms stored.
2. To clear the alarm history, press F1.
3. Enter the User
cknowledge button (ACK) to clear the message and alarm symbol indication.
Figure 10) can be viewed by pressing the Down Arrow first and both Up and Down Arrows to scroll the
name and Password to clear the history.
b. The Run Time Meter screen displays the amount of
time in hours the equipment has been operating. There is an indication for DH displaying the amount of time dehumidification has been requested and operating. These values, shown in hours, may vary dependent on the configuration of the equipment.
5. Control Group Selection 1*
a. Press F1 (PID
b. The OP73 Display may prompt the operator for
rname and Password (
Use
ed. See section 834 for information regarding
proce Username and Password. The Control Group Selection 1 screen displays the various system loops available on the equipment.
Figure 9).
) to navigate to this screen (
Figure 10). Enter this to
Figure 9).
Figure 9. Alarm
Figure 10. Alarm history list
SRV-SVX04C-EN 13
Page 14
Fan Curve
Figure 11. Fan curve
14 SRV-SVX04C-EN
Page 15
Shutdown and Maintenance
Shutdown Guidelines
Refer to “Shutdown,” p. 9 for unit shutdown procedure.
Maintenance Guidelines
The motor and blower bearings are permanently lubricated and require no maintenance. The desiccant wheel is belt driven. The drive belt should be examined periodically for wear and correct tension.
Each unit is provided with disposable filters that are installed in the return air section. The filter access panel must be removed to gain access to the filters. Check filters periodically to verify that they are clean.
SRV-SVX04C-EN 15
Page 16
Wiring Diagrams
Figure 12.
Figure 13.
16 SRV-SVX04C-EN
Page 17
Figure 14.
Wiring Diagrams
Figure 15.
SRV-SVX04C-EN 17
Page 18
Wiring Diagrams
Figure 16.
Figure 17.
18 SRV-SVX04C-EN
Page 19
Figure 18.
Wiring Diagrams
Figure 19.
SRV-SVX04C-EN 19
Page 20
Wiring Diagrams
Figure 20.
Figure 21.
20 SRV-SVX04C-EN
Page 21
Notes
SRV-SVX04C-EN 21
Page 22
Notes
22 SRV-SVX04C-EN
Page 23
Notes
SRV-SVX04C-EN 23
Page 24
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
SRV-SVX04C-EN 06 Aug 2022
Supersedes SRV-SVX04B-EN (Jul 2020)
©2022 Trane
Loading...