Trane SmartGen HSC940 Owner's Manual

Owner’s Manual
SmartGen® HSC940 Controller
March 2017 032-5094-1A-EN
Note: “Graphics in this document are for representation only.
Actual model may differ in appearance.”
Table Of Contents
Key Operations / Indicator Lights . . . . . . . . . . . . . 6
Auto Start / Stop Operation . . . . . . . . . . . . . . 7
Manual Start / Stop Operation . . . . . . . . . . . . . . . 8
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Shutdown Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Scope & Denition of Congurable Parameters . . . . . . . . . . . . . 14
Contents & Scope of Parameters . . . . . . . . . . . . . . . . . . 14
Enable Denitions of Programmable Output Ports . . . . . . 19
Dened Contents of Congurable Input Ports . . . . . . . . . . 21
Conditions of Crank Disconnect Selection . . . . . . . . . . . 22
Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Typical Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Connection Between Controller and Genset . . . . . . . . . 25
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fixing Clips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Overall Dimension and Panel Cutout . . . . . . . . . . 27
GSM Short Message Alarm and Remote Control . . . . . . . . . . 28
GSM Short Message Alarm . . . . . . . . . . . . . . . 29
GSM Short Message Remote Control . . . . . . . . . . . . 29
Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2
032-5094-1A-EN
Overview
HSC940 genset controllers integrate digitization, intellectualization and network technology which are used for gas genset automation and monitor control system of single unit to achieve automatic start/stop, data measure, alarm protection, three remote: remote control, remote
measuring and remote communication (SG485 module must be tted)
and speed regulation. The controller adopts large liquid crystal display
(LCD) and selectable Chinese, English, Spanish and Russian interface with easy and reliable operation.
HSC940 genset controllers adopt microprocessor technology with
precision parameters measuring, xed value adjustment, time setting and set adjusting etc. All parameters can be congured from front panel, or by congurable port (USB to LINK, SG72 must be tted) to adjust via PC. It can be widely used in all types of automatic genset control system
with compact structure, advanced circuits, simple connections and high
reliability.
032-5094-1A-EN
3
Performance & Characteristics
HSC940, used for single automation systems; it regulates the speed simply by adjust the throttle opening via
the driving stepper motor; auto start/stop of the unit are performed with the help of remote signal.
Key characteristics
• 132×64 LCD with backlight, multilingual interface (including Chinese, English, Spanish and Russian), pushbutton operation;
• Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with voltage 120/240V and frequency 50/60Hz;
• Collects and shows 3-phase voltage, current, power parameter and frequency of generator.
Generator
Line voltage (Uab, Ubc, and Uca) Phase voltage (Ua, Ub, and Uc)
Frequency Hz
• For generator, controller has over and under voltage, over and under frequency functions;
• Speed regulation function (via Driving Stepper Motor);
• Precision measure and display parameters about Engine, Speed (SPD) r/min (unit) Battery Voltage (VB) V (unit) Charger Voltage (VD) V (unit) Hour count (HC) can accumulate to max. 999999 hours.
Start times can accumulate to max. 999999 times.
• Protection: automatic start/stop of the genset, ATS(Auto Transfer Switch) control with perfect
failure indication and protection function;
• ETS (Energize to Stop), idle control, preheat control and raise speed/drop speed control; in
addition, they are all relay output.
• Parameter setting: parameters can be modied and cannot be lost even in case of power outage; all parameters can be congured from front panel, or by congurable port (SG72 must be tted) to adjust via PC.
• Multiple crank disconnect conditions (speed sensor, generator frequency) are optional;
• Widely power supply range DC(8~35)V, suitable to different start battery voltage environment;
• All parameters used digital adjustment, instead of conventional analog modulation with normal potentiometer, more reliability and stability;
• Modular design, self-extinguishing ABS plastic enclosure, pluggable connection terminals and embedded installation way; compact structure with easy mounting.
4
032-5094-1A-EN
Specications
Items Contents
Operating Voltage DC8.0V to DC35.0V, Continuous Power Supply. Power Consumption Standby: ≤2W
Working: <8W (When driving stepper motor is regulating)
Alternator Input Range
3-Phase 4-Wire 2-Phase 3-Wire Single-Phase 2-Wire 3-Phase 3-Wire
Alternator Frequency 50Hz/60Hz Speed Sensor Voltage 1.0V to 24.0V (RMS)
Speed Sensor Frequency 10,000 Hz (max.) Start Relay Output 5A DC28V supply output Fuel Relay Output 5A DC28V supply output
Auxiliary Relay Output (1) 5A DC28V supply output Auxiliary Relay Output (2) 5A DC28V supply output Auxiliary Relay Output (3) 5A DC28V supply output Auxiliary Relay Output (4) 5A DC28V supply output Steady-state Speed Governing Rate <1.5% Steady-state Speed Fluctuation Rate <0.5%
Transient Speed Governing Rate Sudden Load-on <+10%
Recovery Time <5s Driving Stepper Motor Mixed 2-phase; Drive current ≤1A Case Dimension 130mm x 112mm x 39mm Panel Cutout 110mm x 90mm Working Conditions Temperature: (-25~+70)°C; Humidity: (20~93)%RH Storage Condition Temperature:(-25~+70)°C Protection Level IP55 Gasket Insulating Intensity Apply AC2.2kV voltage between high voltage terminal and low
Net Weight 0.26kg
AC15V - AC360V (ph-N) AC15V - AC360V (ph-N) AC15V - AC360V (ph-N) AC30V - AC620V (ph-ph)
Sudden Load-off >-15%
voltage terminal; The leakage current is not more than 3mA within 1min.
032-5094-1A-EN
5
4.1 KEY OPERATIONS
Operation
Stop/ Reset
Start Start genset in Manual/Test mode.
Manual Mode
Auto Mode Pressing this key will set the module into AUTO mode.
Set/Conrm
Up/Increase
Down/Decrease
4.2 INDICATOR LIGHTS
Stop running generator in Auto/Manual mode; Lamp test (press
at least 3 seconds); Reset alarm if alarm occurs; During stopping process, press this button again to stop generator immediately.
Pressing this key will set the module into Manual mode. Press­ing and (or ) simultaneously can adjust LCD contrast.
Pressing this key will view set menu; In parameter setting inter­face, press this key will shift cursor or conrm setting value.
Scrolls the screen up; Shift the cursor up or increase the set value in parameter setting menu.
Scrolls the screen down; Shift the cursor down or decrease the set value in parameter setting menu.
Alarm
Gens Normal
Indicator
Stop Indicator Close Gens
Stop
Manual Manual Auto Auto Start Set Indicator Indicator
6
032-5094-1A-EN
Operation
4.3 AUTO START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will illuminate to conrm the
operation.
Automatic Start Sequence:
1. When “Remote Start” is active, “Start Delay” timer is initiated;
2. “Start Delay” countdown will be displayed on LCD;
3. When start delay is over, preheat relay energizes (if congured), “preheat delay XX s” information will be displayed on LCD;
4. After the above delay, the Fuel Relay is energized, and then one second later, the throttle of the driving stepper motor will rotate as the pre-set angle and then the Start Relay is engaged. The engine is cranked for a pre-set time. If the engine fails to re during this cranking attempt then the fuel relay and start relay are disengaged for the pre-set rest period; “crank rest time” begins and wait for the next crank attempt.
5. Should this start sequence continue beyond the set number of attempts, the start sequence will be terminated, the fourth line of LCD display will be highlighted with black and Fail to Start fault will be displayed.
6. In case of successful crank attempt, the “Safety On” timer is activated and the throttle of
the driving stepper motor will govern the speed, allowing Low Oil Pressure, High Temperature,
Under speed, Charge Alternator Failure and auxiliary inputs (be congured) to stabilise without triggering the fault. As soon as this delay is over, “start idle” delay is initiated (if congured).
7. During “start idle” delay, under speed, under frequency, under voltage alarms are inhibited. When this delay is over, “warming up” delay is initiated (if congured).
8. After the “warming up” delay, if generator status is normal, its indicator will be illuminated. If generator voltage and frequency have reached on-load requirements, then the generator close relay will be energized; genset will take load; generator power indicator will illuminate and generator will enter into Normal Running status. If voltage or frequency is abnormal, the controller will initiate shutdown alarm (alarm information will be displayed on LCD).
Automatic Stop Sequence:
1. When the “Remote Start” signal is removed, the Stop Delay is initiated.
2. Once this “stop delay” has expired, the Generator Breaker will open and the “Cooling Delay” is
then initiated. Moreover, the generator indicator is extinguished.
3. During “Stop Idle” Delay (if congured), idle relay is energized.
4. “ETS Solenoid Hold” delay begins, ETS relay is energized while fuel relay is de-energized.
5. "Fail to Stop Delay" begins, complete stop is detected automatically.
6. When generator is stop completely, generator is placed into its standby mode. Otherwise, fail
to stop alarm is initiated and the corresponding alarm information is displayed on LCD.
032-5094-1A-EN
7
Operation
4.4 MANUAL START/STOP OPERATION
1. MANUAL START: Manual mode is selected by pressing the button; a LED besides the button will illuminate to conrm the operation.
Then press button to start the genset; can detect crank disconnect condition and generator accelerates to high-speed running automatically.
With high temperature, low oil pressure, over speed and abnormal voltage during generator running, controller can protect genset to stop quickly. (please refer to No.3~8 of Automatic Start Sequence for detail procedures.) The controller will send Close Gen signal after the
genset is normal running.
2. MANUAL STOP: Press can stop the running generators. (please refer to No.2~6 of Automatic Stop Sequence for detail procedures).
8
032-5094-1A-EN
Protection
5.1 WARNINGS
Warnings are not shutdown alarms and do not affect the operation of the genset. Warning alarms does not
lead to shutdown and the alarm information will be displayed on the LCD. Warning alarms types are as follows:
No. Type Description
When the controller detects that there is High Temperature input and
1 High Temperature Warn
2 Low Oil Pressure
3 Fail to Stop
4 Charge Alt Fail
5 Battery Under Voltage
6 Battery Over Voltage
7 Digital Input
8 Loss of Speed Signal
9 Low Coolant Level
10 Low Fuel Level
the shutdown is prohibited, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the
shutdown is prohibited, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
After the ETS delay/Fail to Stop delay has expired, if the genset stop
failure, it will initiate a warning alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the charger voltage has fallen below the pre-set value, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the controller detects that the battery voltage has fallen below the pre-set value, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the controller detects that the battery voltage has exceeded the pre-set value, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the digit input port is set as warning and active, it will initiate a
warning alarm and the alarm information will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal delay is set as 0, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that there is Low Coolant Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD. When the controller detects that there is Low Fuel Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD.
032-5094-1A-EN
9
Protection
5.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator. Besides, the alarm information will be displayed on the LCD.
Shutdown alarms as following:
No. Type Description
When the controller detects that there is Emergency Stop input, it will ini-
1 Emergency Stop
2 High Temperature
3 Low Oil Pressure
4 Over Speed
5 Under Speed
6 Loss of Speed Signal
7 Gen Over Volt.
8 Gen Under Volt.
9 Fail To Start
10 Gen Over Freq.
11 Gen Under Freq.
tiate a shutdown alarm and the alarm information will be displayed on the
LCD. When the controller detects that there is High Temperature input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD. When the controller detects that the generator speed has exceeded the pre-
set value, it will initiate a shutdown alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the generator speed has fallen below the pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal
delay is NOT set as 0, it will initiate a shutdown alarm and the alarm infor­mation will be displayed on the LCD.
When the controller detects that the generator voltage has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects that the generator voltage has fallen below the pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
If the engine does not re after the pre-set number of attempts, it will initiate a shutdown alarm and the alarm information will be displayed on the
LCD. When the controller detects that the generator frequency has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects that the generator frequency has fallen below the pre-set value, it will initiate a shutdown alarm and the alarm informa­tion will be displayed on the LCD.
10
032-5094-1A-EN