Trane SmartGen HSC940 Owner's Manual

Page 1
Owner’s Manual
SmartGen® HSC940 Controller
March 2017 032-5094-1A-EN
Note: “Graphics in this document are for representation only.
Actual model may differ in appearance.”
Page 2
Table Of Contents
Key Operations / Indicator Lights . . . . . . . . . . . . . 6
Auto Start / Stop Operation . . . . . . . . . . . . . . 7
Manual Start / Stop Operation . . . . . . . . . . . . . . . 8
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Shutdown Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Wiring Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Scope & Denition of Congurable Parameters . . . . . . . . . . . . . 14
Contents & Scope of Parameters . . . . . . . . . . . . . . . . . . 14
Enable Denitions of Programmable Output Ports . . . . . . 19
Dened Contents of Congurable Input Ports . . . . . . . . . . 21
Conditions of Crank Disconnect Selection . . . . . . . . . . . 22
Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Typical Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Connection Between Controller and Genset . . . . . . . . . 25
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fixing Clips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Overall Dimension and Panel Cutout . . . . . . . . . . 27
GSM Short Message Alarm and Remote Control . . . . . . . . . . 28
GSM Short Message Alarm . . . . . . . . . . . . . . . 29
GSM Short Message Remote Control . . . . . . . . . . . . 29
Fault Finding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
2
032-5094-1A-EN
Page 3
Overview
HSC940 genset controllers integrate digitization, intellectualization and network technology which are used for gas genset automation and monitor control system of single unit to achieve automatic start/stop, data measure, alarm protection, three remote: remote control, remote
measuring and remote communication (SG485 module must be tted)
and speed regulation. The controller adopts large liquid crystal display
(LCD) and selectable Chinese, English, Spanish and Russian interface with easy and reliable operation.
HSC940 genset controllers adopt microprocessor technology with
precision parameters measuring, xed value adjustment, time setting and set adjusting etc. All parameters can be congured from front panel, or by congurable port (USB to LINK, SG72 must be tted) to adjust via PC. It can be widely used in all types of automatic genset control system
with compact structure, advanced circuits, simple connections and high
reliability.
032-5094-1A-EN
3
Page 4
Performance & Characteristics
HSC940, used for single automation systems; it regulates the speed simply by adjust the throttle opening via
the driving stepper motor; auto start/stop of the unit are performed with the help of remote signal.
Key characteristics
• 132×64 LCD with backlight, multilingual interface (including Chinese, English, Spanish and Russian), pushbutton operation;
• Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems with voltage 120/240V and frequency 50/60Hz;
• Collects and shows 3-phase voltage, current, power parameter and frequency of generator.
Generator
Line voltage (Uab, Ubc, and Uca) Phase voltage (Ua, Ub, and Uc)
Frequency Hz
• For generator, controller has over and under voltage, over and under frequency functions;
• Speed regulation function (via Driving Stepper Motor);
• Precision measure and display parameters about Engine, Speed (SPD) r/min (unit) Battery Voltage (VB) V (unit) Charger Voltage (VD) V (unit) Hour count (HC) can accumulate to max. 999999 hours.
Start times can accumulate to max. 999999 times.
• Protection: automatic start/stop of the genset, ATS(Auto Transfer Switch) control with perfect
failure indication and protection function;
• ETS (Energize to Stop), idle control, preheat control and raise speed/drop speed control; in
addition, they are all relay output.
• Parameter setting: parameters can be modied and cannot be lost even in case of power outage; all parameters can be congured from front panel, or by congurable port (SG72 must be tted) to adjust via PC.
• Multiple crank disconnect conditions (speed sensor, generator frequency) are optional;
• Widely power supply range DC(8~35)V, suitable to different start battery voltage environment;
• All parameters used digital adjustment, instead of conventional analog modulation with normal potentiometer, more reliability and stability;
• Modular design, self-extinguishing ABS plastic enclosure, pluggable connection terminals and embedded installation way; compact structure with easy mounting.
4
032-5094-1A-EN
Page 5
Specications
Items Contents
Operating Voltage DC8.0V to DC35.0V, Continuous Power Supply. Power Consumption Standby: ≤2W
Working: <8W (When driving stepper motor is regulating)
Alternator Input Range
3-Phase 4-Wire 2-Phase 3-Wire Single-Phase 2-Wire 3-Phase 3-Wire
Alternator Frequency 50Hz/60Hz Speed Sensor Voltage 1.0V to 24.0V (RMS)
Speed Sensor Frequency 10,000 Hz (max.) Start Relay Output 5A DC28V supply output Fuel Relay Output 5A DC28V supply output
Auxiliary Relay Output (1) 5A DC28V supply output Auxiliary Relay Output (2) 5A DC28V supply output Auxiliary Relay Output (3) 5A DC28V supply output Auxiliary Relay Output (4) 5A DC28V supply output Steady-state Speed Governing Rate <1.5% Steady-state Speed Fluctuation Rate <0.5%
Transient Speed Governing Rate Sudden Load-on <+10%
Recovery Time <5s Driving Stepper Motor Mixed 2-phase; Drive current ≤1A Case Dimension 130mm x 112mm x 39mm Panel Cutout 110mm x 90mm Working Conditions Temperature: (-25~+70)°C; Humidity: (20~93)%RH Storage Condition Temperature:(-25~+70)°C Protection Level IP55 Gasket Insulating Intensity Apply AC2.2kV voltage between high voltage terminal and low
Net Weight 0.26kg
AC15V - AC360V (ph-N) AC15V - AC360V (ph-N) AC15V - AC360V (ph-N) AC30V - AC620V (ph-ph)
Sudden Load-off >-15%
voltage terminal; The leakage current is not more than 3mA within 1min.
032-5094-1A-EN
5
Page 6
4.1 KEY OPERATIONS
Operation
Stop/ Reset
Start Start genset in Manual/Test mode.
Manual Mode
Auto Mode Pressing this key will set the module into AUTO mode.
Set/Conrm
Up/Increase
Down/Decrease
4.2 INDICATOR LIGHTS
Stop running generator in Auto/Manual mode; Lamp test (press
at least 3 seconds); Reset alarm if alarm occurs; During stopping process, press this button again to stop generator immediately.
Pressing this key will set the module into Manual mode. Press­ing and (or ) simultaneously can adjust LCD contrast.
Pressing this key will view set menu; In parameter setting inter­face, press this key will shift cursor or conrm setting value.
Scrolls the screen up; Shift the cursor up or increase the set value in parameter setting menu.
Scrolls the screen down; Shift the cursor down or decrease the set value in parameter setting menu.
Alarm
Gens Normal
Indicator
Stop Indicator Close Gens
Stop
Manual Manual Auto Auto Start Set Indicator Indicator
6
032-5094-1A-EN
Page 7
Operation
4.3 AUTO START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will illuminate to conrm the
operation.
Automatic Start Sequence:
1. When “Remote Start” is active, “Start Delay” timer is initiated;
2. “Start Delay” countdown will be displayed on LCD;
3. When start delay is over, preheat relay energizes (if congured), “preheat delay XX s” information will be displayed on LCD;
4. After the above delay, the Fuel Relay is energized, and then one second later, the throttle of the driving stepper motor will rotate as the pre-set angle and then the Start Relay is engaged. The engine is cranked for a pre-set time. If the engine fails to re during this cranking attempt then the fuel relay and start relay are disengaged for the pre-set rest period; “crank rest time” begins and wait for the next crank attempt.
5. Should this start sequence continue beyond the set number of attempts, the start sequence will be terminated, the fourth line of LCD display will be highlighted with black and Fail to Start fault will be displayed.
6. In case of successful crank attempt, the “Safety On” timer is activated and the throttle of
the driving stepper motor will govern the speed, allowing Low Oil Pressure, High Temperature,
Under speed, Charge Alternator Failure and auxiliary inputs (be congured) to stabilise without triggering the fault. As soon as this delay is over, “start idle” delay is initiated (if congured).
7. During “start idle” delay, under speed, under frequency, under voltage alarms are inhibited. When this delay is over, “warming up” delay is initiated (if congured).
8. After the “warming up” delay, if generator status is normal, its indicator will be illuminated. If generator voltage and frequency have reached on-load requirements, then the generator close relay will be energized; genset will take load; generator power indicator will illuminate and generator will enter into Normal Running status. If voltage or frequency is abnormal, the controller will initiate shutdown alarm (alarm information will be displayed on LCD).
Automatic Stop Sequence:
1. When the “Remote Start” signal is removed, the Stop Delay is initiated.
2. Once this “stop delay” has expired, the Generator Breaker will open and the “Cooling Delay” is
then initiated. Moreover, the generator indicator is extinguished.
3. During “Stop Idle” Delay (if congured), idle relay is energized.
4. “ETS Solenoid Hold” delay begins, ETS relay is energized while fuel relay is de-energized.
5. "Fail to Stop Delay" begins, complete stop is detected automatically.
6. When generator is stop completely, generator is placed into its standby mode. Otherwise, fail
to stop alarm is initiated and the corresponding alarm information is displayed on LCD.
032-5094-1A-EN
7
Page 8
Operation
4.4 MANUAL START/STOP OPERATION
1. MANUAL START: Manual mode is selected by pressing the button; a LED besides the button will illuminate to conrm the operation.
Then press button to start the genset; can detect crank disconnect condition and generator accelerates to high-speed running automatically.
With high temperature, low oil pressure, over speed and abnormal voltage during generator running, controller can protect genset to stop quickly. (please refer to No.3~8 of Automatic Start Sequence for detail procedures.) The controller will send Close Gen signal after the
genset is normal running.
2. MANUAL STOP: Press can stop the running generators. (please refer to No.2~6 of Automatic Stop Sequence for detail procedures).
8
032-5094-1A-EN
Page 9
Protection
5.1 WARNINGS
Warnings are not shutdown alarms and do not affect the operation of the genset. Warning alarms does not
lead to shutdown and the alarm information will be displayed on the LCD. Warning alarms types are as follows:
No. Type Description
When the controller detects that there is High Temperature input and
1 High Temperature Warn
2 Low Oil Pressure
3 Fail to Stop
4 Charge Alt Fail
5 Battery Under Voltage
6 Battery Over Voltage
7 Digital Input
8 Loss of Speed Signal
9 Low Coolant Level
10 Low Fuel Level
the shutdown is prohibited, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the
shutdown is prohibited, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
After the ETS delay/Fail to Stop delay has expired, if the genset stop
failure, it will initiate a warning alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the charger voltage has fallen below the pre-set value, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the controller detects that the battery voltage has fallen below the pre-set value, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the controller detects that the battery voltage has exceeded the pre-set value, it will initiate a warning alarm and the alarm information will be displayed on the LCD.
When the digit input port is set as warning and active, it will initiate a
warning alarm and the alarm information will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal delay is set as 0, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that there is Low Coolant Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD. When the controller detects that there is Low Fuel Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD.
032-5094-1A-EN
9
Page 10
Protection
5.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator. Besides, the alarm information will be displayed on the LCD.
Shutdown alarms as following:
No. Type Description
When the controller detects that there is Emergency Stop input, it will ini-
1 Emergency Stop
2 High Temperature
3 Low Oil Pressure
4 Over Speed
5 Under Speed
6 Loss of Speed Signal
7 Gen Over Volt.
8 Gen Under Volt.
9 Fail To Start
10 Gen Over Freq.
11 Gen Under Freq.
tiate a shutdown alarm and the alarm information will be displayed on the
LCD. When the controller detects that there is High Temperature input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD. When the controller detects that the generator speed has exceeded the pre-
set value, it will initiate a shutdown alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the generator speed has fallen below the pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal
delay is NOT set as 0, it will initiate a shutdown alarm and the alarm infor­mation will be displayed on the LCD.
When the controller detects that the generator voltage has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects that the generator voltage has fallen below the pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
If the engine does not re after the pre-set number of attempts, it will initiate a shutdown alarm and the alarm information will be displayed on the
LCD. When the controller detects that the generator frequency has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects that the generator frequency has fallen below the pre-set value, it will initiate a shutdown alarm and the alarm informa­tion will be displayed on the LCD.
10
032-5094-1A-EN
Page 11
Protection
5.2 SHUTDOWN ALARM continued
When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator. Besides, the alarm information will be displayed on the LCD.
Shutdown alarms as following:
No. Type Description
12 No gens freq When the controller detects the generator frequency is 0, it will initiate a
shutdown alarm and the alarm information will be displayed on the LCD.
13 Low Fuel Level When the controller detects that the fuel level is lower than the set value or
there is Low Fuel Level input, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
14 Low Coolant Level When the controller detects that there is Low Coolant Level input, it will
initiate a shutdown alarm and the alarm information will be displayed on the
LCD.
032-5094-1A-EN
11
Page 12
Wiring Connections
HSC940 controller’s rear as following:
Description of terminal connection:
No. Function Cable Size Remarks
1 B- 2.5mm
2 B+ 2.5mm
3 EM. Stop 1.5mm 4 Fuel 1.0mm
5 Crank 1.0mm
6 Aux. Output 1 1.0mm 7 Aux. Output 2 1.0mm
8 Aux. Output 3 1.0mm 9 Aux. Output 4 1.0mm
2
2
Connected with negative of starter battery Connected with positive of starter battery. Max. 20A fuse is
recommended.
2
2
2
Connected with B+ via emergency stop button Fuel relay output; B+ is supplied by 3 terminal; rated 5A Start relay output; B+ is supplied by 3 terminal; rated 5A;
Connected to starter coil.
2
2
2
2
B+ is supplied by 2 terminal; rated 5A B+ is supplied by 2 terminal; rated 5A; B+ is supplied by 2 terminal; rated 5A; B+ is supplied by 2 terminal; rated 5A;
12
032-5094-1A-EN
Page 13
Wiring Connections
Continued:
No. Function Cable Size Remarks
10 Aux. Input 1 1.0mm
11 Aux. Input 2 1.0mm
12 Aux. Input 3 1.0mm 13 Aux. Input 4 1.0mm 14 Aux. Input 5 1.0mm 15 GND The common port of sensor; (B-) has already connected.
16 CHARGER(D+) 1.0mm
17 MP2 1.0mm
18 MP1 1.0mm
19 S11 1.0mm
20 S12 1.0mm 21 S21 1.0mm 22 S22 1.0mm 23 RS232 RX 0.5mm
25 RS232 GND 0.5mm
26 Gens AC Voltage (U) 1.0mm
27 Gens AC Voltage (V) 1.0mm
28 Gens AC Voltage (W) 1.0mm
29 Gens AC Voltage (N) 1.0mm
2
2
2
2
2
2
Ground connected is active (B-)
Ground connected is active (B-)
Ground connected is active (B-) Ground connected is active (B-) Ground connected is active (B-)
Connected with charger starter’s D+ (WL) terminals. Being
hang up If there is no this terminal.
2
(B-) has already connected. Connected with Speed sensor,
shielding line is recommended.
2
Connected with Speed sensor, shielding line is recommend­ed.
2
2
2
2
Connect to stepper motor. S11 and S12 are belong to one phase to the motor while S21 and S22 are belong to the
other phase.
Connected to GSM module.24 RS232 TX 0.5mm
2
Connected to U-phase of generator (2A fuse is recommend­ed).
2
Connected to V-phase of generator (2A fuse is recommend­ed).
2
Connected to W-phase of generator (2A fuse is recommend­ed).
2
Connected to N-phase of generator (2A fuse is recommend­ed).
Details see
form 3
NOTE: LINK interface is parameters congured interface that can be programmed by PC using an SG72 adapter. If there is need to remote control the genset, please use the SG485 module produced by our company.
032-5094-1A-EN
13
Page 14
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS
Form 1
No Items Range Default Description
1 Start Delay (0-3600)s 1
2 Stop Delay (0-3600)s 1
3 Start Attempts (1-10)times 3
4 Preheat Delay (0-300)s 0
5 Choke Time (0-300)s 0 Power-on time of choke after crank succeeds.
6 Cranking Time (3-60)s 8 Power-on time of starter
7 Crank Rest Time (3-60)s 10
8 Safety On Delay (1-60)s 10
9 Start Idle Time (0-3600)s 0 Idle running time of genset when starting.
10 Warming Up Time (0-3600)s 10
11 Cooling Time (3-3600)s 10 Radiating time before genset stop, after it unloads. 12 Stop Idle (0-3600)s 0 Idle running time when genset stop.
13 ETS Solenoid Hold (0-120)s 20
14 Fail to Stop Delay (0-120)s 0
15 Close Time (0-10)s 5.0
Time from remote start signal is active to start gen­set.
Time from remote start signal is deactivated to gen­set stop.
Maximum crank times of crank attempts. When reach
this number, controller will send start failure signal. Power-on time of heater plug before starter is pow-
ered up.
The waiting time before second power up when en-
gine start fail. Alarms for low oil pressure, high temperature, under
speed, under frequency/voltage, charge alt failure are inactive.
Warming time between genset switch on and high
speed running.
Stop electromagnet’s power on time when genset is stopping.
Time between ending of genset idle delay and stopped when “ETS time” is set as 0; Time between
ending of ETS hold delay and stopped when “ETS time” is not 0.
Pulse width of generator switch on. When it is 0, means output constantly.
14
032-5094-1A-EN
Page 15
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
No Items Range Default Description
Tooth number of the engine, for judging of starter
16 Flywheel Teeth (1-300) 118
17 Gen Abnormal Delay (0-20.0)s 10.0
Gen Over Voltage
18
(Shutdown)
Generator Under
19
Voltage (Shutdown)
Under Speed (Shut-
20
down)
Over Speed (Shut-
21
down)
Under Frequency
22
(Shutdown)
Over Frequency
23
(Shutdown)
24 Loss of Speed Signal (0-20.0)s 5.0
(30-620)V 264
(30-620)V 88
(0-6000)
r/min
(0-6000)
r/min
(0-75.0)Hz 45.0
(0-75.0)Hz 68.0
1000
4200
crank disconnect conditions and inspecting of engine speed. See the installation instructions.
The alarm delay of generator over voltage and under voltage.
When generator voltage has exceed the set value
and the “Gen abnormal delay” has expired, Gen Over Voltage shutdown alarm is active. When set the value as 620V, the controller does not detect over voltage
signal.
When generator voltage has fallen below the set value and the “Gen abnormal delay” has expired, Gen Under Voltage shutdown alarm is active. When set the value as 30V, the controller does not detect
under voltage signal.
When engine speed has fallen below the set value for 10s, Under Speed shutdown alarm is active. It will
initiate a shutdown alarm signal.
When engine speed has exceed the set value for 2s,
Over Speed shutdown alarm is active. It will initiate a shutdown alarm signal.
When generator frequency has fallen below the set value but Not equal to 0 for 10s, Under Frequency
shutdown alarm is active. It will initiate a shutdown alarm signal.
When generator frequency has exceeded the set val-
ue for 2s, Over Frequency shutdown alarm is active. It
will initiate a shutdown alarm signal. If the set value is 0, only warning and not to shut-
down the generator.
032-5094-1A-EN
15
Page 16
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
No Items Range Default Description
Charge Alt Failure
25
(Warning)
Battery Over
26
Voltage (Warning)
Battery Under Volt-
27
age (Warning)
28 Auxiliary Output 1 (0-17) 15 Factory default: Choke Control 29 Auxiliary Output 2 (0-17) 2 Factory default: Energized To Stop
30 Auxiliary Output 3 (0-17) 3 Factory default: Idle Control 31 Auxiliary Output 4 (0-17) 5 Factory default: Close Generator 32 Auxiliary Input 1 (0-15) 1 Factory default: High Temperature Input
Auxiliary Input 1
33
Active Auxiliary Input 1
34
Delay
35 Auxiliary Input 2 (0-15) 2 Factory default: Low Oil Pressure Input
Auxiliary Input 2
36
Active
Auxiliary Input 2
37
Delay
38 Auxiliary Input 3 (0-15) 10 Factory default: Remote Start
Auxiliary Input 3
39
Active Auxiliary Input 3
40
Delay
41 Auxiliary Input 4 (0-15) 11 Factory default: Fuel Level Warn
(0-30)V 6.0
(12-40)V 33.0
(4-30)V 8.0
(0-1) 0 Factory default: Close to active
(0-20.0)s 2.0
(0-1) 0 Factory default: Close to active
(0-20.0)s 2.0
(0-1) 0 Factory default: Close to active
(0-20.0)s 2.0
During generator is normal running, when alternator
D+(WL) voltage has fallen below the set value and
remains for 5s, It will initiate a shutdown alarm signal.
When battery voltage has exceeded the set value and remains for 20s, It will initiate a warning alarm signal.
Only warning and not to shutdown the generator.
When battery voltage has fallen below the set value and remains for 20s, It will initiate a warning alarm
signal. Only warning and not to shutdown the gener­ator.
16
032-5094-1A-EN
Page 17
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
No Items Range Default Description
Auxiliary Input 4
42
Active Auxiliary Input 4
43
Delay
44 Auxiliary Input 5 (0-15) 3 Factory default: Warn Input
Auxiliary Input 5
45
Active Auxiliary Input 5
46
Delay
47 Power On Mode (0-2) 0
48 Module Address (1-254) 1 Communication address of controller. 49 Passwords (0-9999) 1234
50 Crank Disconnect (0-2) 2
Disconnect Engine
51
Speed Disconnect Genera-
52
tor Freq
53 High Temp. Inhibit (0-1) 0
54 Low OP Inhibit (0-1) 0
55 Voltage Input (0-3) 0
56 Rated Speed
(0-1) 0 Factory default: Close to active
(0-20.0)s 2.0
(0-1) 0 Factory default: Close to active
(0-20.0)s 2.0
0: Stop Mode 1: Manual Mode
2: Auto Mode
There are 2 conditions of disconnecting starter with
engine: Generator Frequency and Speed Sensor. Each
condition can be used alone and simultaneously to
separating the start motor and genset as soon as
possible. See Table 4.
(0-3000)
r/min
(10.0-30.0)Hz 14.0
(0-6000)
r/min
360
1500 Offer standard to adjust rated speed.
When the engine speed has exceeded the set value,
starter will be disconnected.
When the generator frequency has exceeded the set
value, starter will be disconnected.
Factory default: High Temp. Shutdown. When high
temperature occurs, shutdown alarm is active. Note 1 Factory default: when low oil pressure occurs, shut-
down alarm is active. Note 2 0: 3P4W; 1: 2P3W
2: 1P2W; 3: 3P3W Note 3
032-5094-1A-EN
17
Page 18
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
No Items Range Default Description
57 Idle Speed
58 Idle Slope 0-6000 10
59 Idle Gain 1-1000 150
60 Crank Angle (0-90)° 45 The throttle opening before the genset is starting.
61 Crank Disc. Angle (0-90)° 35
62 Proportional Gain 1-3000 1100 63 Integral Gain 1-3000 20 64 Differential Gain 1-3000 1 65 Total Gain 1-1000 100
66 Window
67 Window Gain 1000-3000 1950 68 Position Gain 0-1000 0 69 Compensate Gain 0-100 0 70 Scheduled Enable (0-1) 0 Factory default: Disable 71 Scheduled Run Mode (0-1) 0 Factory default: Off Load 72 Schedule Period (0-2) 0 Factory default: 0 Monthly 73 Schedule Day (1-31) 1 74 Schedule Week (0-6) 0 Factory default: 0 Daily 75 Schedule Hour (0-23) 0 76 Schedule Minute (0-59) 0 77 Schedule Duration (0-9999) 0 78 GSM Set (0-1) 0 Factory default: Disable
(0-6000) r/
min
(1-1000)
r/min
900 Offer standard to adjust idle speed.
The rising speed rate during the process of genset change idle running status into rated speed running status.
The gain is regulated during the genset is idle run­ning.
The initial opening of the throttle after the genset is started.
The regulated gain when the genset is running in
1
rated speed.
18
032-5094-1A-EN
Page 19
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Note 1. If “high temperature inhibit” is congured, or set auxiliary input as “inhibit high temperature stop” and this input is active, when temperature is higher than the preset value, or high temperature alarm input is active, controller will send warning signal only and not stop the unit.
Note 2. If “low oil pressure inhibit” is congured, or set auxiliary input as “inhibit low oil pressure stop” and this input is active, when oil pressure is lower than the preset value, or low oil pressure alarm input is active, controller will send warning signal only and not stop the unit.
Note 3. If “3P3W” is selected, maximum shutdown threshold of “Gens Over Voltage” can
be set as 620V; when select others, maximum shutdown threshold can be set as 360V.
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS
Form 2
No Items Description
0 Not Used Output port is deactivated when “Not Used” is selected.
Include all shutdown alarms and warning alarms. When there is warning
1 Common Alarm
2 Energized to Stop
3 Idle Control
4 Preheat Control Close before starting and open before power up; 5 Close Generator When close time is 0, it’s continuous output.
6 Reserved 7 Open ATS When close time is 0, it’s disabled.
8 Raise Speed
alarm only, it is not self-lock; when a shutdown alarm occurs, it is self-lock
until the alarm is reset.
Suitable for genset with electromagnet and will active after “stop idle
delay”. It is deactivated when the “ETS Solenoid delay” expires.
Used for engine which has idles. Close before starting and open in warm-
ing up delay; Close during stop idle delay and open when stop is complet­ed.
Close when the generator enters into Warming Up delay (close time: warming up delay) while open when Aux. Raise Speed input is active.
032-5094-1A-EN
19
Page 20
Scope & Denitions of Congurable Parameters
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS continued
Form 2 continued
No Items Description
Close when the generator enters into Stop Idle delay/ Energized to Stop
9 Drop Speed
10 Generator Run
11 Fuel Pump Control
12 High Speed Control
13 In Auto Mode The controller is in automatic mode. 14 Fuel Relay Output To control fuel relay output.
15 Choke Control
16 Reserved
delay (close time: Stop Idle delay) while open when Aux. Drop Speed input
is active. Action when genset is normal running while deactivated when engine
speed is lower than the “crank disconnect speed”. Close when fuel level is lower than the “Fuel Pump On” value or when low
fuel level warning input is active; Open when fuel level is higher than the “Fuel Pump Off” and low fuel level warning input is deactivated;
Close when the generator enters into Warming Up delay while open after
cooling delay.
Start to output in cranking period; in addition, during safety on running, output for preset delay.
17 Reserved
20
032-5094-1A-EN
Page 21
Scope & Denitions of Congurable Parameters
7.2 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL ACTIVE WHEN CONNECT TO GRAND (B-))
Form 3
No Items Description
0 Not Used 1 High Temperature Input 2 Low Oil Pressure Input 3 Warn Input Only warning and not shutdown if this input is active. 4 Shutdown input Shutdown alarm will be immediately initiated if this input is active.
5 WTH STOP by cool
6 Generator Closed input 7 Reserved
Inhibit High
8
Temperature Stop
Inhibit Low Oil
9
Pressure Stop 10 Remote Start 11 Fuel Level Warn 12 Coolant Level Warn 13 Fuel Level Shutdown
Coolant Level 14
Shutdown
15 Inhibit Start Auto
If these signals are active after safety on delay, shutdown alarm will be im-
mediately initiated.
When the genset is running normally and this signal is activated, if there is
a high temperature situation, the controller will rst cool down the gen-
erator and then stop it; if the signal is deactivated and a high temperature
situation occurs, the controller will shut down the gen-set without cooling
down.
When it is active, high temperature shutdown will be prohibited. Note 1
When it is active, low oil pressure shutdown will be prohibited. Note 2
In Auto mode, if this input is active, whether remote start signal activates or not, the controller will not give a start command to the generator. If
generator is normal running, stop command won’t be executed. When this
input is deactivated, genset will automatically start or stop.
032-5094-1A-EN
21
Page 22
Protection
7.4 CONDITIONS OF CRANK DISCONNECT SELECTION
Form 4
No. Setting Description
0 Gen frequency 1 Speed sensor
2 Speed sensor + Gen frequency
NOTES:
1. There are 2 conditions to make starter disconnected with engine, that is, speed sensor and generator frequency. They all can be used separately. We recommend that speed sensor should be using with generator frequency together, in order to make the starter motor is
separated with engine immediately and can check crank disconnect exactly.
2. Speed sensor is the magnetic equipment which be installed in starter for detecting ywheel
teeth.
3. When set as speed sensor, must ensure that the number of ywheel teeth is as same as setting, otherwise, “over speed shutdown” or “under speed shutdown” may be caused.
4. If genset without speed sensor, please don’t select corresponding items, otherwise, “start fail”
or “loss speed signal” maybe caused.
5. If not select generator frequency in crank disconnect setting, controller will not collect and
display the relative power quantity (can be used in water pump set); if not select speed sensor in crank disconnect setting, the rotating speed displayed in controller is calculated by
generator signal.
22
032-5094-1A-EN
Page 23
Parameter Settings
Start the controller, then press to enter into the parameters setting menu, see g 1 below:
1. Set Parameters
2. Information
Fig. 1
Parameters Setting
When entering password interface, input correct password (default: 1234) can set all of the parameter items in Form 1. If there is need to set more parameters (e.g. Voltage Calibration), please contact the factory. CAUTION: Please change the controller parameters when generator is in standby mode only (e. g. Crank disconnect conditions selection, auxiliary input, auxiliary output, various delay), otherwise, shutdown and other abnormal conditions may happen.
CAUTION: Over voltage set value must be higher than under voltage set value, otherwise over voltage and under voltage condition may occur simultaneously. CAUTION: Over speed set value must be higher than under speed set value, otherwise over speed and under speed condition may occur simultaneously. CAUTION: Please set the generator frequency value as low as possible when cranking, in
order to make the starter be separated quickly as soon as possible. CAUTION: Auxiliary input 1~5 could not be set as same items; otherwise, there are abnormal functions. However, the auxiliary output 1~4 can be set as same items.
CAUTION: If need to shut down after cooling, please set any digital input as “WTH STOP by cool”, then connect this input port to ground soundly.
Information
LCD will display software version, issue date of the controller.
Note: In this interface, pressing will display the auxiliary inputs and outputs status. Language
Chinese, English, Spanish and Russian interface can be selected.
Time and Date
The time and date information can be set in this interface.
Pressing the key at any time will quit the setting and return to the previous settings menu.
3. Language
4. Time and Date
032-5094-1A-EN
23
Page 24
Commissioning
Please make the under procedures checking before commissioning,
1. Ensure all the connections are correct and wires diameter is suitable.
2. Ensure that the controller DC power has fuse, controller‘s positive and negative connected to start battery are correct.
3. Take proper action to prevent engine to crank disconnect (e. g. Remove the connection wire
of fuel valve). If checking is OK, make the start battery power on; choose manual mode and
controller will executive routine.
4. Set controller under manual mode, press “start” button, genset will start. After the setting
times as setting, controller will send signal of Start Fail; then press “stop” to reset controller.
5. Recover the action of stop engine start (e. g. Connect wire of fuel valve), press start button
again, genset will start. If everything goes well, genset will normal run after idle running (if idle
run be set). During this time, please watch for engine’s running situations and AC generator’s voltage and frequency. If abnormal, stop genset running and check all wires connection
according to this manual.
6. Select the AUTO mode from controller’s panel, connect remote start signal. genset will be
started automatically and into normal running, then controller send signal to close generator.
7. Cut-off remote start signal, the genset will be stopped automatically and the Open Generator signal will be send out. If not like this, please check ATS’ wires connection of control part
according to this manual.
8. If there is any other question, please contact Smartgen’s service.
24
032-5094-1A-EN
Page 25
Typical Application
Typical Application Diagram
CAUTION! Expand relay with high capacity in start and fuel output is recommend.
CAUTION! Expand relay must be used in generator closed outputs.
Connection Between Controller and Genset
032-5094-1A-EN
25
Page 26
Installation
12.1 FIXING CLIPS
Controller is panel built-in design; it is xed by clips when installed.
1. Withdraw the xing clip screw (turn anticlockwise) until it reaches proper position.
2. Pull the xing clip backwards (towards the back of the module) ensuring two clips are inside
their allotted slots.
3. Turn the xing clip screws clockwise until they are xed on the panel.
Note: Care should be taken not to over tighten the screws of xing clips.
26
032-5094-1A-EN
Page 27
Installation
12.2 OVERALL DIMENSION AND PANEL CUTOUT
1. Battery Voltage Input
HSC940 controller can suit for widely range of battery voltage DC(8~35)V. Negative of battery must be connected with the engine shell. The diameter of wire which from power supply to battery must be over
2.5mm2. If oating charge congured, please rstly connect output wires of charger to battery’s positive and negative directly, then, connect wires from battery’s positive and negative to controller’s positive and negative input ports in order to prevent charge disturbing the controller’s normal working.
2. Speed Sensor Input
Speed sensor is the magnetic equipment which be installed in starter and for detecting ywheel teeth. Its connection wires to controller should apply for 2 cores shielding line. The shielding layer should connect to No. 17 terminal in controller while another side is hanging in air. The else two signal wires are connected to No.17 and No.18 terminals in controller. The output voltage of speed sensor should be within AC(1~24)V (effective value) during the full speed. AC12V is recommended (in rated speed). When install the speed sensor, let the sensor is spun to contacting ywheel rst, then, port out 1/3 lap, and lock the nuts of sensor at last.
3. Output And Expansion Relay
All outputs of controller are relay contact output type. If need to expand the relays, please add freewheel
diode to both ends of expand relay’s coils (when coils of relay has DC current) or, add resistance-capacitance return circuit (when coils of relay has AC current), in order to prevent disturbance to controller or others
equipment.
4. Withdraw Voltage Test
When controller had been installed in control panel, if need the high voltage test, please disconnect
controller’s all terminal connections, in order to prevent high voltage into controller and damage it.
032-5094-1A-EN
27
Page 28
GSM Short Message Alarm & Remote Control
13.1 GSM SHORT MESSAGE ALARM
When controller detects alarm, it will send short message to phone automatically.
13.2 GSM SHORT MESSAGE REMOTE CONTROL
Users send order message to GSM module, then controller will make actions according to this SMS order and pass back corresponding operations information. Controllers only execute the orders by pre-set. Detail orders
as following:
No. SMS Orders Pass Back Information Description
When genset is shutdown alarm
At rest status in stop mode
At rest status in manual mode
At rest status in auto mode
Running status in stop mode
Running status in manual mode
Running status in auto mode
Generator is shutdown alarm or trip alarm
Cannot start in stop mode
Cannot start in auto mode
Status of genset
Start genset
1
2
3
SMS
GENSET
SMS START
SMS STOP MODE
GENSET ALARM
SYSTEM IN STOP MODE GENSET AT REST
SYSTEM IN MANUAL MODE GENSET AT REST
SYSTEM IN AUTO MODE GENSET AT REST
SYSTEM IN STOP MODE GENSET IS RUNNING
SYSTEM IN MANUAL MODE GENSET IS RUNNING
SYSTEM IN AUTO MODE GENSET AT RUNNING
GENSET ALARM
STOP MODE NOT START
SMS START OK Start in manual mode
AUTO MODE NOT START
SMS STOP OK Set as stop mode
28
032-5094-1A-EN
Page 29
GSM Short Message Alarm & Remote Control
13.2 GSM SHORT MESSAGE REMOTE CONTROL continued
Users send order message to GSM module, then controller will make actions according to this SMS order and pass back corresponding operations information. Controllers only execute the orders by pre-set. Detail orders
as following:
No. SMS Orders Pass Back Information Description
SMS MANUAL
4
MODE
SMS AUTO
5
MODE
6 SMS DETAIL
SMS MANUAL MODE OK Set as manual mode
SMS AUTO MODE OK Set as auto mode
Pass back information
includes: Working Mode;
Generator Voltage; Generator Frequency; Bat­tery Voltage; Charger Volt-
age; Speed; Total Run Time; Genset Status; Alarm Status
Gets details information of genset.
NOTE: Its national and area codes must be added. e.g. China: 8613666666666
NOTE: When sending orders, users need to follow SMS orders in above form and all the letters must be capital.
032-5094-1A-EN
29
Page 30
Symptoms Possible Solutions
Controller no response with power.
Genset shutdown
Low oil pressure alarm after crank disconnect
High water temp. alarm after crank disconnect
Shutdown Alarm in running
Fail to start
Starter no response
Stepping Motor Reverse
GOV is out of control.
Fault Finding
Check starting batteries;
Check controller connection wirings; Check DC fuse.
Check the water/cylinder temperature is too high or not; Check the genset AC voltage; Check DC fuse.
Check the oil pressure sensor and its connections.
Check the temperature sensor and its connections.
Check related switch and its connections according to the informa­tion on LCD; Check auxiliary input ports.
Check fuel oil circuit and its connections;
Check starting batteries;
Check speed sensor and its connections; Refer to engine manual.
Check starter connections;
Check starting batteries. Cross connect the S11 and S12;
Cross connect the S21 and S22; Change conguration (motor reduce direction) via PC.
Check the speed sensor voltage is no less than 2V when cranking. Check the connections of S11, S12, S21, S22.
30
032-5094-1A-EN
Page 31
Smartgen — make your generator smart
Smartgen Technology Co., Ltd.
No.28 Jinsuo Road
Zhengzhou Henan Province P. R. China
Tel: 0086-371-67988888/67981888 0086-371-67991553/67992951 0086-371-67981000(overseas)
Fax: 0086-371-67992952
Web: http://www.smartgen.com.cn
http://www.smartgen.cn
Email: sales@smartgen.cn
All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the
copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Smartgen Technology reserves the right to change the contents of this document without prior notice.
Software Version
Date Version Note
2014-06-10 1.0 Original release
Chinese Trademark English Trademark
032-5094-1A-EN
31
Page 32
032-5094-1A-EN (9 Mar 2017)
We are committed to using environmentally conscious print practices. © 2017 Ingersoll Rand IR000000