HSC940 genset controllers integrate digitization, intellectualization
and network technology which are used for gas genset automation and
monitor control system of single unit to achieve automatic start/stop,
data measure, alarm protection, three remote: remote control, remote
measuring and remote communication (SG485 module must be tted)
and speed regulation. The controller adopts large liquid crystal display
(LCD) and selectable Chinese, English, Spanish and Russian interface with
easy and reliable operation.
HSC940 genset controllers adopt microprocessor technology with
precision parameters measuring, xed value adjustment, time setting and
set adjusting etc. All parameters can be congured from front panel, or
by congurable port (USB to LINK, SG72 must be tted) to adjust via
PC. It can be widely used in all types of automatic genset control system
with compact structure, advanced circuits, simple connections and high
reliability.
032-5094-1A-EN
3
Page 4
Performance & Characteristics
HSC940, used for single automation systems; it regulates the speed simply by adjust the throttle opening via
the driving stepper motor; auto start/stop of the unit are performed with the help of remote signal.
Key characteristics
• 132×64 LCD with backlight, multilingual interface (including Chinese, English, Spanish and
Russian), pushbutton operation;
• Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems
with voltage 120/240V and frequency 50/60Hz;
• Collects and shows 3-phase voltage, current, power parameter and frequency of generator.
Generator
Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc)
Frequency Hz
• For generator, controller has over and under voltage, over and under frequency functions;
• Speed regulation function (via Driving Stepper Motor);
• Precision measure and display parameters about Engine,
Speed (SPD) r/min (unit)
Battery Voltage (VB) V (unit)
Charger Voltage (VD) V (unit)
Hour count (HC) can accumulate to max. 999999 hours.
Start times can accumulate to max. 999999 times.
• Protection: automatic start/stop of the genset, ATS(Auto Transfer Switch) control with perfect
failure indication and protection function;
• ETS (Energize to Stop), idle control, preheat control and raise speed/drop speed control; in
addition, they are all relay output.
• Parameter setting: parameters can be modied and cannot be lost even in case of power
outage; all parameters can be congured from front panel, or by congurable port (SG72 must
be tted) to adjust via PC.
Recovery Time<5s
Driving Stepper MotorMixed 2-phase; Drive current ≤1A
Case Dimension130mm x 112mm x 39mm
Panel Cutout110mm x 90mm
Working ConditionsTemperature: (-25~+70)°C; Humidity: (20~93)%RH
Storage ConditionTemperature:(-25~+70)°C
Protection LevelIP55 Gasket
Insulating IntensityApply AC2.2kV voltage between high voltage terminal and low
voltage terminal; The leakage current is not more than 3mA
within 1min.
032-5094-1A-EN
5
Page 6
4.1 KEY OPERATIONS
Operation
Stop/ Reset
StartStart genset in Manual/Test mode.
Manual Mode
Auto ModePressing this key will set the module into AUTO mode.
Set/Conrm
Up/Increase
Down/Decrease
4.2 INDICATOR LIGHTS
Stop running generator in Auto/Manual mode; Lamp test (press
at least 3 seconds); Reset alarm if alarm occurs; During stopping
process, press this button again to stop generator immediately.
Pressing this key will set the module into Manual mode. Pressing and (or ) simultaneously can adjust LCD contrast.
Pressing this key will view set menu; In parameter setting interface, press this key will shift cursor or conrm setting value.
Scrolls the screen up; Shift the cursor up or increase the set
value in parameter setting menu.
Scrolls the screen down; Shift the cursor down or decrease the
set value in parameter setting menu.
Alarm
Gens Normal
Indicator
Stop Indicator Close Gens
Stop
Manual Manual Auto Auto Start Set
Indicator Indicator
6
032-5094-1A-EN
Page 7
Operation
4.3 AUTO START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will illuminate to conrm the
operation.
Automatic Start Sequence:
1. When “Remote Start” is active, “Start Delay” timer is initiated;
2. “Start Delay” countdown will be displayed on LCD;
3. When start delay is over, preheat relay energizes (if congured), “preheat delay XX s”
information will be displayed on LCD;
4. After the above delay, the Fuel Relay is energized, and then one second later, the throttle of
the driving stepper motor will rotate as the pre-set angle and then the Start Relay is engaged.
The engine is cranked for a pre-set time. If the engine fails to re during this cranking attempt
then the fuel relay and start relay are disengaged for the pre-set rest period; “crank rest time”
begins and wait for the next crank attempt.
5. Should this start sequence continue beyond the set number of attempts, the start sequence
will be terminated, the fourth line of LCD display will be highlighted with black and Fail to Start
fault will be displayed.
6. In case of successful crank attempt, the “Safety On” timer is activated and the throttle of
the driving stepper motor will govern the speed, allowing Low Oil Pressure, High Temperature,
Under speed, Charge Alternator Failure and auxiliary inputs (be congured) to stabilise without
triggering the fault. As soon as this delay is over, “start idle” delay is initiated (if congured).
7. During “start idle” delay, under speed, under frequency, under voltage alarms are inhibited.
When this delay is over, “warming up” delay is initiated (if congured).
8. After the “warming up” delay, if generator status is normal, its indicator will be illuminated.
If generator voltage and frequency have reached on-load requirements, then the generator
close relay will be energized; genset will take load; generator power indicator will illuminate
and generator will enter into Normal Running status. If voltage or frequency is abnormal, the
controller will initiate shutdown alarm (alarm information will be displayed on LCD).
Automatic Stop Sequence:
1. When the “Remote Start” signal is removed, the Stop Delay is initiated.
2. Once this “stop delay” has expired, the Generator Breaker will open and the “Cooling Delay” is
then initiated. Moreover, the generator indicator is extinguished.
3. During “Stop Idle” Delay (if congured), idle relay is energized.
4. “ETS Solenoid Hold” delay begins, ETS relay is energized while fuel relay is de-energized.
5. "Fail to Stop Delay" begins, complete stop is detected automatically.
6. When generator is stop completely, generator is placed into its standby mode. Otherwise, fail
to stop alarm is initiated and the corresponding alarm information is displayed on LCD.
032-5094-1A-EN
7
Page 8
Operation
4.4 MANUAL START/STOP OPERATION
1. MANUAL START: Manual mode is selected by pressing the button; a LED besides the
button will illuminate to conrm the operation.
Then press button to start the genset; can detect crank disconnect condition and
generator accelerates to high-speed running automatically.
With high temperature, low oil pressure, over speed and abnormal voltage during generator
running, controller can protect genset to stop quickly. (please refer to No.3~8 of Automatic
Start Sequence for detail procedures.) The controller will send Close Gen signal after the
genset is normal running.
2. MANUAL STOP: Press can stop the running generators. (please refer to No.2~6 of
Automatic Stop Sequence for detail procedures).
8
032-5094-1A-EN
Page 9
Protection
5.1 WARNINGS
Warnings are not shutdown alarms and do not affect the operation of the genset. Warning alarms does not
lead to shutdown and the alarm information will be displayed on the LCD. Warning alarms types are as follows:
No. Type Description
When the controller detects that there is High Temperature input and
1High Temperature Warn
2Low Oil Pressure
3Fail to Stop
4Charge Alt Fail
5Battery Under Voltage
6Battery Over Voltage
7Digital Input
8Loss of Speed Signal
9Low Coolant Level
10Low Fuel Level
the shutdown is prohibited, it will initiate a warning alarm and the alarm
information will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the
shutdown is prohibited, it will initiate a warning alarm and the alarm
information will be displayed on the LCD.
After the ETS delay/Fail to Stop delay has expired, if the genset stop
failure, it will initiate a warning alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the charger voltage has fallen below the
pre-set value, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the battery voltage has fallen below the
pre-set value, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the battery voltage has exceeded the
pre-set value, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the digit input port is set as warning and active, it will initiate a
warning alarm and the alarm information will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal
delay is set as 0, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that there is Low Coolant Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD.
When the controller detects that there is Low Fuel Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD.
032-5094-1A-EN
9
Page 10
Protection
5.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator.
Besides, the alarm information will be displayed on the LCD.
Shutdown alarms as following:
No.TypeDescription
When the controller detects that there is Emergency Stop input, it will ini-
1Emergency Stop
2High Temperature
3Low Oil Pressure
4Over Speed
5Under Speed
6Loss of Speed Signal
7Gen Over Volt.
8Gen Under Volt.
9Fail To Start
10Gen Over Freq.
11Gen Under Freq.
tiate a shutdown alarm and the alarm information will be displayed on the
LCD.
When the controller detects that there is High Temperature input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD.
When the controller detects that the generator speed has exceeded the pre-
set value, it will initiate a shutdown alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the generator speed has fallen below the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal
delay is NOT set as 0, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects that the generator voltage has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the generator voltage has fallen below the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
If the engine does not re after the pre-set number of attempts, it will
initiate a shutdown alarm and the alarm information will be displayed on the
LCD.
When the controller detects that the generator frequency has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the generator frequency has fallen below
the pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
10
032-5094-1A-EN
Page 11
Protection
5.2 SHUTDOWN ALARM continued
When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator.
Besides, the alarm information will be displayed on the LCD.
Shutdown alarms as following:
No.TypeDescription
12No gens freqWhen the controller detects the generator frequency is 0, it will initiate a
shutdown alarm and the alarm information will be displayed on the LCD.
13Low Fuel LevelWhen the controller detects that the fuel level is lower than the set value or
there is Low Fuel Level input, it will initiate a shutdown alarm and the alarm
information will be displayed on the LCD.
14Low Coolant LevelWhen the controller detects that there is Low Coolant Level input, it will
initiate a shutdown alarm and the alarm information will be displayed on the
LCD.
032-5094-1A-EN
11
Page 12
Wiring Connections
HSC940 controller’s rear as following:
Description of terminal connection:
No.FunctionCable SizeRemarks
1B-2.5mm
2B+2.5mm
3EM. Stop1.5mm
4Fuel 1.0mm
5Crank1.0mm
6Aux. Output 11.0mm
7Aux. Output 21.0mm
8Aux. Output 31.0mm
9Aux. Output 41.0mm
2
2
Connected with negative of starter battery
Connected with positive of starter battery. Max. 20A fuse is
recommended.
2
2
2
Connected with B+ via emergency stop button
Fuel relay output; B+ is supplied by 3 terminal; rated 5A
Start relay output; B+ is supplied by 3 terminal; rated 5A;
Connected to starter coil.
2
2
2
2
B+ is supplied by 2 terminal; rated 5A
B+ is supplied by 2 terminal; rated 5A;
B+ is supplied by 2 terminal; rated 5A;
B+ is supplied by 2 terminal; rated 5A;
12
032-5094-1A-EN
Page 13
Wiring Connections
Continued:
No.FunctionCable SizeRemarks
10Aux. Input 11.0mm
11Aux. Input 21.0mm
12Aux. Input 31.0mm
13Aux. Input 41.0mm
14Aux. Input 51.0mm
15GNDThe common port of sensor; (B-) has already connected.
16CHARGER(D+)1.0mm
17MP21.0mm
18MP11.0mm
19S111.0mm
20S121.0mm
21S211.0mm
22S221.0mm
23RS232 RX0.5mm
25RS232 GND0.5mm
26Gens AC Voltage (U)1.0mm
27Gens AC Voltage (V)1.0mm
28Gens AC Voltage (W)1.0mm
29Gens AC Voltage (N)1.0mm
2
2
2
2
2
2
Ground connected is active (B-)
Ground connected is active (B-)
Ground connected is active (B-)
Ground connected is active (B-)
Ground connected is active (B-)
Connected with charger starter’s D+ (WL) terminals. Being
hang up If there is no this terminal.
2
(B-) has already connected. Connected with Speed sensor,
shielding line is recommended.
2
Connected with Speed sensor, shielding line is recommended.
2
2
2
2
Connect to stepper motor. S11 and S12 are belong to one
phase to the motor while S21 and S22 are belong to the
other phase.
Connected to GSM module.24RS232 TX0.5mm
2
Connected to U-phase of generator (2A fuse is recommended).
2
Connected to V-phase of generator (2A fuse is recommended).
2
Connected to W-phase of generator (2A fuse is recommended).
2
Connected to N-phase of generator (2A fuse is recommended).
Details see
form 3
NOTE: LINK interface is parameters congured interface that can be programmed by
PC using an SG72 adapter. If there is need to remote control the genset, please use the
SG485 module produced by our company.
032-5094-1A-EN
13
Page 14
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS
Form 1
NoItemsRangeDefaultDescription
1Start Delay(0-3600)s1
2Stop Delay(0-3600)s1
3Start Attempts(1-10)times3
4Preheat Delay(0-300)s0
5Choke Time(0-300)s0Power-on time of choke after crank succeeds.
6Cranking Time(3-60)s8Power-on time of starter
7Crank Rest Time(3-60)s10
8Safety On Delay(1-60)s10
9Start Idle Time(0-3600)s0Idle running time of genset when starting.
10Warming Up Time(0-3600)s10
11Cooling Time(3-3600)s10Radiating time before genset stop, after it unloads.12Stop Idle (0-3600)s0Idle running time when genset stop.
13ETS Solenoid Hold(0-120)s20
14Fail to Stop Delay(0-120)s0
15Close Time(0-10)s5.0
Time from remote start signal is active to start genset.
Time from remote start signal is deactivated to genset stop.
Maximum crank times of crank attempts. When reach
this number, controller will send start failure signal.
Power-on time of heater plug before starter is pow-
ered up.
The waiting time before second power up when en-
gine start fail.
Alarms for low oil pressure, high temperature, under
speed, under frequency/voltage, charge alt failure
are inactive.
Warming time between genset switch on and high
speed running.
Stop electromagnet’s power on time when genset is
stopping.
Time between ending of genset idle delay and
stopped when “ETS time” is set as 0; Time between
ending of ETS hold delay and stopped when “ETS
time” is not 0.
Pulse width of generator switch on. When it is 0,
means output constantly.
14
032-5094-1A-EN
Page 15
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
NoItemsRangeDefaultDescription
Tooth number of the engine, for judging of starter
16Flywheel Teeth(1-300) 118
17Gen Abnormal Delay(0-20.0)s10.0
Gen Over Voltage
18
(Shutdown)
Generator Under
19
Voltage
(Shutdown)
Under Speed (Shut-
20
down)
Over Speed (Shut-
21
down)
Under Frequency
22
(Shutdown)
Over Frequency
23
(Shutdown)
24Loss of Speed Signal(0-20.0)s5.0
(30-620)V264
(30-620)V88
(0-6000)
r/min
(0-6000)
r/min
(0-75.0)Hz45.0
(0-75.0)Hz68.0
1000
4200
crank disconnect conditions and inspecting of engine
speed. See the installation instructions.
The alarm delay of generator over voltage and under
voltage.
When generator voltage has exceed the set value
and the “Gen abnormal delay” has expired, Gen Over
Voltage shutdown alarm is active. When set the value
as 620V, the controller does not detect over voltage
signal.
When generator voltage has fallen below the set
value and the “Gen abnormal delay” has expired,
Gen Under Voltage shutdown alarm is active. When
set the value as 30V, the controller does not detect
under voltage signal.
When engine speed has fallen below the set value
for 10s, Under Speed shutdown alarm is active. It will
initiate a shutdown alarm signal.
When engine speed has exceed the set value for 2s,
Over Speed shutdown alarm is active. It will initiate a
shutdown alarm signal.
When generator frequency has fallen below the set
value but Not equal to 0 for 10s, Under Frequency
shutdown alarm is active. It will initiate a shutdown
alarm signal.
When generator frequency has exceeded the set val-
ue for 2s, Over Frequency shutdown alarm is active. It
will initiate a shutdown alarm signal.
If the set value is 0, only warning and not to shut-
down the generator.
032-5094-1A-EN
15
Page 16
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Form 1 continued
NoItemsRangeDefaultDescription
Charge Alt Failure
25
(Warning)
Battery Over
26
Voltage (Warning)
Battery Under Volt-
27
age (Warning)
28Auxiliary Output 1 (0-17)15Factory default: Choke Control
29Auxiliary Output 2 (0-17)2Factory default: Energized To Stop
30Auxiliary Output 3 (0-17)3Factory default: Idle Control
31Auxiliary Output 4 (0-17)5Factory default: Close Generator
32Auxiliary Input 1 (0-15)1Factory default: High Temperature Input
The rising speed rate during the process of genset
change idle running status into rated speed running
status.
The gain is regulated during the genset is idle running.
The initial opening of the throttle after the genset is
started.
The regulated gain when the genset is running in
1
rated speed.
18
032-5094-1A-EN
Page 19
Scope & Denitions of Congurable Parameters
7.1 CONTENTS AND SCOPES OF PARAMETERS continued
Note 1. If “high temperature inhibit” is congured, or set auxiliary input as “inhibit hightemperature stop” and this input is active, when temperature is higher than the preset
value, or high temperature alarm input is active, controller will send warning signal only
and not stop the unit.
Note 2. If “low oil pressure inhibit” is congured, or set auxiliary input as “inhibit low oilpressure stop” and this input is active, when oil pressure is lower than the preset value,
or low oil pressure alarm input is active, controller will send warning signal only and not
stop the unit.
Note 3. If “3P3W” is selected, maximum shutdown threshold of “Gens Over Voltage” can
be set as 620V; when select others, maximum shutdown threshold can be set as 360V.
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS
Form 2
NoItemsDescription
0Not UsedOutput port is deactivated when “Not Used” is selected.
Include all shutdown alarms and warning alarms. When there is warning
1Common Alarm
2Energized to Stop
3Idle Control
4Preheat ControlClose before starting and open before power up;
5Close Generator When close time is 0, it’s continuous output.
6Reserved
7Open ATSWhen close time is 0, it’s disabled.
8Raise Speed
alarm only, it is not self-lock; when a shutdown alarm occurs, it is self-lock
until the alarm is reset.
Suitable for genset with electromagnet and will active after “stop idle
delay”. It is deactivated when the “ETS Solenoid delay” expires.
Used for engine which has idles. Close before starting and open in warm-
ing up delay; Close during stop idle delay and open when stop is completed.
Close when the generator enters into Warming Up delay (close time:
warming up delay) while open when Aux. Raise Speed input is active.
032-5094-1A-EN
19
Page 20
Scope & Denitions of Congurable Parameters
7.2 ENABLE DEFINITION OF PROGRAMMABLE OUTPUT PORTS continued
Form 2 continued
NoItemsDescription
Close when the generator enters into Stop Idle delay/ Energized to Stop
9Drop Speed
10Generator Run
11Fuel Pump Control
12High Speed Control
13In Auto ModeThe controller is in automatic mode.
14Fuel Relay OutputTo control fuel relay output.
15Choke Control
16Reserved
delay (close time: Stop Idle delay) while open when Aux. Drop Speed input
is active.
Action when genset is normal running while deactivated when engine
speed is lower than the “crank disconnect speed”.
Close when fuel level is lower than the “Fuel Pump On” value or when low
fuel level warning input is active; Open when fuel level is higher than the
“Fuel Pump Off” and low fuel level warning input is deactivated;
Close when the generator enters into Warming Up delay while open after
cooling delay.
Start to output in cranking period; in addition, during safety on running,
output for preset delay.
17Reserved
20
032-5094-1A-EN
Page 21
Scope & Denitions of Congurable Parameters
7.2 DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS (ALL ACTIVE WHEN
CONNECT TO GRAND (B-))
Form 3
NoItemsDescription
0Not Used
1High Temperature Input
2Low Oil Pressure Input
3Warn InputOnly warning and not shutdown if this input is active.
4Shutdown inputShutdown alarm will be immediately initiated if this input is active.
If these signals are active after safety on delay, shutdown alarm will be im-
mediately initiated.
When the genset is running normally and this signal is activated, if there is
a high temperature situation, the controller will rst cool down the gen-
erator and then stop it; if the signal is deactivated and a high temperature
situation occurs, the controller will shut down the gen-set without cooling
down.
When it is active, high temperature shutdown will be prohibited. Note 1
When it is active, low oil pressure shutdown will be prohibited. Note 2
In Auto mode, if this input is active, whether remote start signal activates
or not, the controller will not give a start command to the generator. If
generator is normal running, stop command won’t be executed. When this
input is deactivated, genset will automatically start or stop.
032-5094-1A-EN
21
Page 22
Protection
7.4 CONDITIONS OF CRANK DISCONNECT SELECTION
Form 4
No.Setting Description
0Gen frequency
1Speed sensor
2Speed sensor + Gen frequency
NOTES:
1. There are 2 conditions to make starter disconnected with engine, that is, speed sensor and
generator frequency. They all can be used separately. We recommend that speed sensor
should be using with generator frequency together, in order to make the starter motor is
separated with engine immediately and can check crank disconnect exactly.
2. Speed sensor is the magnetic equipment which be installed in starter for detecting ywheel
teeth.
3. When set as speed sensor, must ensure that the number of ywheel teeth is as same as
setting, otherwise, “over speed shutdown” or “under speed shutdown” may be caused.
4. If genset without speed sensor, please don’t select corresponding items, otherwise, “start fail”
or “loss speed signal” maybe caused.
5. If not select generator frequency in crank disconnect setting, controller will not collect and
display the relative power quantity (can be used in water pump set); if not select speed sensor
in crank disconnect setting, the rotating speed displayed in controller is calculated by
generator signal.
22
032-5094-1A-EN
Page 23
Parameter Settings
Start the controller, then press to enter into the parameters setting menu, see g 1 below:
1. Set Parameters
2. Information
Fig. 1
Parameters Setting
When entering password interface, input correct password (default: 1234) can set all of the parameter items in
Form 1. If there is need to set more parameters (e.g. Voltage Calibration), please contact the factory.
CAUTION: Please change the controller parameters when generator is in standby mode only
(e. g. Crank disconnect conditions selection, auxiliary input, auxiliary output, various delay),
otherwise, shutdown and other abnormal conditions may happen.
CAUTION: Over voltage set value must be higher than under voltage set value, otherwise
over voltage and under voltage condition may occur simultaneously.
CAUTION: Over speed set value must be higher than under speed set value, otherwise over
speed and under speed condition may occur simultaneously.
CAUTION: Please set the generator frequency value as low as possible when cranking, in
order to make the starter be separated quickly as soon as possible.
CAUTION: Auxiliary input 1~5 could not be set as same items; otherwise, there are abnormal
functions. However, the auxiliary output 1~4 can be set as same items.
CAUTION: If need to shut down after cooling, please set any digital input as “WTH STOP by
cool”, then connect this input port to ground soundly.
Information
LCD will display software version, issue date of the controller.
Note: In this interface, pressing will display the auxiliary inputs and outputs status.
Language
Chinese, English, Spanish and Russian interface can be selected.
Time and Date
The time and date information can be set in this interface.
Pressing the key at any time will quit the setting and return to the previous settings menu.
3. Language
4. Time and Date
032-5094-1A-EN
23
Page 24
Commissioning
Please make the under procedures checking before commissioning,
1. Ensure all the connections are correct and wires diameter is suitable.
2. Ensure that the controller DC power has fuse, controller‘s positive and negative connected to
start battery are correct.
3. Take proper action to prevent engine to crank disconnect (e. g. Remove the connection wire
of fuel valve). If checking is OK, make the start battery power on; choose manual mode and
controller will executive routine.
4. Set controller under manual mode, press “start” button, genset will start. After the setting
times as setting, controller will send signal of Start Fail; then press “stop” to reset controller.
5. Recover the action of stop engine start (e. g. Connect wire of fuel valve), press start button
again, genset will start. If everything goes well, genset will normal run after idle running (if idle
run be set). During this time, please watch for engine’s running situations and AC generator’s
voltage and frequency. If abnormal, stop genset running and check all wires connection
according to this manual.
6. Select the AUTO mode from controller’s panel, connect remote start signal. genset will be
started automatically and into normal running, then controller send signal to close generator.
7. Cut-off remote start signal, the genset will be stopped automatically and the Open Generator
signal will be send out. If not like this, please check ATS’ wires connection of control part
according to this manual.
8. If there is any other question, please contact Smartgen’s service.
24
032-5094-1A-EN
Page 25
Typical Application
Typical Application Diagram
CAUTION! Expand relay with high capacity in start and fuel output is recommend.
CAUTION! Expand relay must be used in generator closed outputs.
Connection Between Controller and Genset
032-5094-1A-EN
25
Page 26
Installation
12.1 FIXING CLIPS
Controller is panel built-in design; it is xed by clips when installed.
1. Withdraw the xing clip screw (turn anticlockwise) until it reaches proper position.
2. Pull the xing clip backwards (towards the back of the module) ensuring two clips are inside
their allotted slots.
3. Turn the xing clip screws clockwise until they are xed on the panel.
Note: Care should be taken not to over tighten the screws of xing clips.
26
032-5094-1A-EN
Page 27
Installation
12.2 OVERALL DIMENSION AND PANEL CUTOUT
1. Battery Voltage Input
HSC940 controller can suit for widely range of battery voltage DC(8~35)V. Negative of battery must be
connected with the engine shell. The diameter of wire which from power supply to battery must be over
2.5mm2. If oating charge congured, please rstly connect output wires of charger to battery’s positive and
negative directly, then, connect wires from battery’s positive and negative to controller’s positive and negative
input ports in order to prevent charge disturbing the controller’s normal working.
2. Speed Sensor Input
Speed sensor is the magnetic equipment which be installed in starter and for detecting ywheel teeth. Its
connection wires to controller should apply for 2 cores shielding line. The shielding layer should connect to No.
17 terminal in controller while another side is hanging in air. The else two signal wires are connected to No.17
and No.18 terminals in controller. The output voltage of speed sensor should be within AC(1~24)V (effective
value) during the full speed. AC12V is recommended (in rated speed). When install the speed sensor, let the
sensor is spun to contacting ywheel rst, then, port out 1/3 lap, and lock the nuts of sensor at last.
3. Output And Expansion Relay
All outputs of controller are relay contact output type. If need to expand the relays, please add freewheel
diode to both ends of expand relay’s coils (when coils of relay has DC current) or, add resistance-capacitance
return circuit (when coils of relay has AC current), in order to prevent disturbance to controller or others
equipment.
4. Withdraw Voltage Test
When controller had been installed in control panel, if need the high voltage test, please disconnect
controller’s all terminal connections, in order to prevent high voltage into controller and damage it.
032-5094-1A-EN
27
Page 28
GSM Short Message Alarm & Remote Control
13.1 GSM SHORT MESSAGE ALARM
When controller detects alarm, it will send short message to phone automatically.
13.2 GSM SHORT MESSAGE REMOTE CONTROL
Users send order message to GSM module, then controller will make actions according to this SMS order and
pass back corresponding operations information. Controllers only execute the orders by pre-set. Detail orders
as following:
No.SMS OrdersPass Back InformationDescription
When genset is shutdown
alarm
At rest status in stop
mode
At rest status in manual
mode
At rest status in auto
mode
Running status in stop
mode
Running status in manual
mode
Running status in auto
mode
Generator is shutdown
alarm or trip alarm
Cannot start in stop
mode
Cannot start in auto
mode
Status of genset
Start genset
1
2
3
SMS
GENSET
SMS
START
SMS STOP
MODE
GENSET ALARM
SYSTEM IN STOP MODE
GENSET AT REST
SYSTEM IN MANUAL MODE
GENSET AT REST
SYSTEM IN AUTO MODE
GENSET AT REST
SYSTEM IN STOP MODE
GENSET IS RUNNING
SYSTEM IN MANUAL MODE
GENSET IS RUNNING
SYSTEM IN AUTO MODE
GENSET AT RUNNING
GENSET ALARM
STOP MODE NOT START
SMS START OKStart in manual mode
AUTO MODE NOT START
SMS STOP OKSet as stop mode
28
032-5094-1A-EN
Page 29
GSM Short Message Alarm & Remote Control
13.2 GSM SHORT MESSAGE REMOTE CONTROL continued
Users send order message to GSM module, then controller will make actions according to this SMS order and
pass back corresponding operations information. Controllers only execute the orders by pre-set. Detail orders
All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of the
copyright holder.
Applications for the copyright holder’s written permission to reproduce any part of this publication should be
addressed to Smartgen Technology at the address above.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Smartgen Technology reserves the right to change the contents of this document without prior notice.