HSC940 genset controllers integrate digitization, intellectualization
and network technology which are used for gas genset automation and
monitor control system of single unit to achieve automatic start/stop,
data measure, alarm protection, three remote: remote control, remote
measuring and remote communication (SG485 module must be tted)
and speed regulation. The controller adopts large liquid crystal display
(LCD) and selectable Chinese, English, Spanish and Russian interface with
easy and reliable operation.
HSC940 genset controllers adopt microprocessor technology with
precision parameters measuring, xed value adjustment, time setting and
set adjusting etc. All parameters can be congured from front panel, or
by congurable port (USB to LINK, SG72 must be tted) to adjust via
PC. It can be widely used in all types of automatic genset control system
with compact structure, advanced circuits, simple connections and high
reliability.
032-5094-1A-EN
3
Performance & Characteristics
HSC940, used for single automation systems; it regulates the speed simply by adjust the throttle opening via
the driving stepper motor; auto start/stop of the unit are performed with the help of remote signal.
Key characteristics
• 132×64 LCD with backlight, multilingual interface (including Chinese, English, Spanish and
Russian), pushbutton operation;
• Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire systems
with voltage 120/240V and frequency 50/60Hz;
• Collects and shows 3-phase voltage, current, power parameter and frequency of generator.
Generator
Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc)
Frequency Hz
• For generator, controller has over and under voltage, over and under frequency functions;
• Speed regulation function (via Driving Stepper Motor);
• Precision measure and display parameters about Engine,
Speed (SPD) r/min (unit)
Battery Voltage (VB) V (unit)
Charger Voltage (VD) V (unit)
Hour count (HC) can accumulate to max. 999999 hours.
Start times can accumulate to max. 999999 times.
• Protection: automatic start/stop of the genset, ATS(Auto Transfer Switch) control with perfect
failure indication and protection function;
• ETS (Energize to Stop), idle control, preheat control and raise speed/drop speed control; in
addition, they are all relay output.
• Parameter setting: parameters can be modied and cannot be lost even in case of power
outage; all parameters can be congured from front panel, or by congurable port (SG72 must
be tted) to adjust via PC.
Recovery Time<5s
Driving Stepper MotorMixed 2-phase; Drive current ≤1A
Case Dimension130mm x 112mm x 39mm
Panel Cutout110mm x 90mm
Working ConditionsTemperature: (-25~+70)°C; Humidity: (20~93)%RH
Storage ConditionTemperature:(-25~+70)°C
Protection LevelIP55 Gasket
Insulating IntensityApply AC2.2kV voltage between high voltage terminal and low
voltage terminal; The leakage current is not more than 3mA
within 1min.
032-5094-1A-EN
5
4.1 KEY OPERATIONS
Operation
Stop/ Reset
StartStart genset in Manual/Test mode.
Manual Mode
Auto ModePressing this key will set the module into AUTO mode.
Set/Conrm
Up/Increase
Down/Decrease
4.2 INDICATOR LIGHTS
Stop running generator in Auto/Manual mode; Lamp test (press
at least 3 seconds); Reset alarm if alarm occurs; During stopping
process, press this button again to stop generator immediately.
Pressing this key will set the module into Manual mode. Pressing and (or ) simultaneously can adjust LCD contrast.
Pressing this key will view set menu; In parameter setting interface, press this key will shift cursor or conrm setting value.
Scrolls the screen up; Shift the cursor up or increase the set
value in parameter setting menu.
Scrolls the screen down; Shift the cursor down or decrease the
set value in parameter setting menu.
Alarm
Gens Normal
Indicator
Stop Indicator Close Gens
Stop
Manual Manual Auto Auto Start Set
Indicator Indicator
6
032-5094-1A-EN
Operation
4.3 AUTO START/STOP OPERATION
Auto mode is selected by pressing the button; a LED besides the button will illuminate to conrm the
operation.
Automatic Start Sequence:
1. When “Remote Start” is active, “Start Delay” timer is initiated;
2. “Start Delay” countdown will be displayed on LCD;
3. When start delay is over, preheat relay energizes (if congured), “preheat delay XX s”
information will be displayed on LCD;
4. After the above delay, the Fuel Relay is energized, and then one second later, the throttle of
the driving stepper motor will rotate as the pre-set angle and then the Start Relay is engaged.
The engine is cranked for a pre-set time. If the engine fails to re during this cranking attempt
then the fuel relay and start relay are disengaged for the pre-set rest period; “crank rest time”
begins and wait for the next crank attempt.
5. Should this start sequence continue beyond the set number of attempts, the start sequence
will be terminated, the fourth line of LCD display will be highlighted with black and Fail to Start
fault will be displayed.
6. In case of successful crank attempt, the “Safety On” timer is activated and the throttle of
the driving stepper motor will govern the speed, allowing Low Oil Pressure, High Temperature,
Under speed, Charge Alternator Failure and auxiliary inputs (be congured) to stabilise without
triggering the fault. As soon as this delay is over, “start idle” delay is initiated (if congured).
7. During “start idle” delay, under speed, under frequency, under voltage alarms are inhibited.
When this delay is over, “warming up” delay is initiated (if congured).
8. After the “warming up” delay, if generator status is normal, its indicator will be illuminated.
If generator voltage and frequency have reached on-load requirements, then the generator
close relay will be energized; genset will take load; generator power indicator will illuminate
and generator will enter into Normal Running status. If voltage or frequency is abnormal, the
controller will initiate shutdown alarm (alarm information will be displayed on LCD).
Automatic Stop Sequence:
1. When the “Remote Start” signal is removed, the Stop Delay is initiated.
2. Once this “stop delay” has expired, the Generator Breaker will open and the “Cooling Delay” is
then initiated. Moreover, the generator indicator is extinguished.
3. During “Stop Idle” Delay (if congured), idle relay is energized.
4. “ETS Solenoid Hold” delay begins, ETS relay is energized while fuel relay is de-energized.
5. "Fail to Stop Delay" begins, complete stop is detected automatically.
6. When generator is stop completely, generator is placed into its standby mode. Otherwise, fail
to stop alarm is initiated and the corresponding alarm information is displayed on LCD.
032-5094-1A-EN
7
Operation
4.4 MANUAL START/STOP OPERATION
1. MANUAL START: Manual mode is selected by pressing the button; a LED besides the
button will illuminate to conrm the operation.
Then press button to start the genset; can detect crank disconnect condition and
generator accelerates to high-speed running automatically.
With high temperature, low oil pressure, over speed and abnormal voltage during generator
running, controller can protect genset to stop quickly. (please refer to No.3~8 of Automatic
Start Sequence for detail procedures.) The controller will send Close Gen signal after the
genset is normal running.
2. MANUAL STOP: Press can stop the running generators. (please refer to No.2~6 of
Automatic Stop Sequence for detail procedures).
8
032-5094-1A-EN
Protection
5.1 WARNINGS
Warnings are not shutdown alarms and do not affect the operation of the genset. Warning alarms does not
lead to shutdown and the alarm information will be displayed on the LCD. Warning alarms types are as follows:
No. Type Description
When the controller detects that there is High Temperature input and
1High Temperature Warn
2Low Oil Pressure
3Fail to Stop
4Charge Alt Fail
5Battery Under Voltage
6Battery Over Voltage
7Digital Input
8Loss of Speed Signal
9Low Coolant Level
10Low Fuel Level
the shutdown is prohibited, it will initiate a warning alarm and the alarm
information will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the
shutdown is prohibited, it will initiate a warning alarm and the alarm
information will be displayed on the LCD.
After the ETS delay/Fail to Stop delay has expired, if the genset stop
failure, it will initiate a warning alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the charger voltage has fallen below the
pre-set value, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the battery voltage has fallen below the
pre-set value, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the battery voltage has exceeded the
pre-set value, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the digit input port is set as warning and active, it will initiate a
warning alarm and the alarm information will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal
delay is set as 0, it will initiate a warning alarm and the alarm information
will be displayed on the LCD.
When the controller detects that there is Low Coolant Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD.
When the controller detects that there is Low Fuel Level input, it will
initiate a warning alarm and the alarm information will be displayed on
the LCD.
032-5094-1A-EN
9
Protection
5.2 SHUTDOWN ALARM
When controller detects shutdown alarm, it will send signal to open breaker and shuts down generator.
Besides, the alarm information will be displayed on the LCD.
Shutdown alarms as following:
No.TypeDescription
When the controller detects that there is Emergency Stop input, it will ini-
1Emergency Stop
2High Temperature
3Low Oil Pressure
4Over Speed
5Under Speed
6Loss of Speed Signal
7Gen Over Volt.
8Gen Under Volt.
9Fail To Start
10Gen Over Freq.
11Gen Under Freq.
tiate a shutdown alarm and the alarm information will be displayed on the
LCD.
When the controller detects that there is High Temperature input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD.
When the controller detects that there is Low Oil Pressure input and the
shutdown is allowed, it will initiate a shutdown alarm and the alarm infor-
mation will be displayed on the LCD.
When the controller detects that the generator speed has exceeded the pre-
set value, it will initiate a shutdown alarm and the alarm information will be
displayed on the LCD.
When the controller detects that the generator speed has fallen below the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
When the controller detects the speed is 0 and the Loss of Speed Signal
delay is NOT set as 0, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
When the controller detects that the generator voltage has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the generator voltage has fallen below the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
If the engine does not re after the pre-set number of attempts, it will
initiate a shutdown alarm and the alarm information will be displayed on the
LCD.
When the controller detects that the generator frequency has exceeded the
pre-set value, it will initiate a shutdown alarm and the alarm information
will be displayed on the LCD.
When the controller detects that the generator frequency has fallen below
the pre-set value, it will initiate a shutdown alarm and the alarm information will be displayed on the LCD.
10
032-5094-1A-EN