The new T r ane pack ag ed ter minal air conditioners (PTACs) and heat pumps are ideally suited for of fices, apar tments, hotels,
motels and institutional homes. K ey benefits whic h mak e the units a wise choice ar e:
T rane PTAC units and heat pumps are
among the most efficient in the industry,
with EERs of up to 11 .6 and COPs of up
to 3.3. The efficient design of the PSC
motor and airflow pattern help to reduce
the energy consumption of the fan.
Packaged terminal heat pumps tend to
be more efficient than electric heat only.
In fact, operating savings may result in a
payback of less than one year . During
heating operation, refrigerant in the heat
pump runs in the reverse direction of the
cooling operation. The outside air is
cooled, thereby giving up heat to the
refrigerant in the heat pump.
This heat is then pumped back inside,
resulting in up to three Btu’s of heat for
every Btu of energy consumed.
During cooling operation, heat is
removed from the building as the air is
cooled. This heat proceeds through the
compression cycle and is ultimately
rejected to the outside air.
Energy-saving options available with
PT AC units include:
Front Desk Contact P oint
Each unit has low voltage interface
capability with a field-supplied ON/OFF
switch. Turn off heating or cooling to
unoccupied rooms.
Fan Mode Switc h
Select continuous fan operation or cycle
the fan ON and OFF with the compressor
or heat operation. The switch is
concealed to help prevent tampering by
unauthorized personnel.
Temperature Limiter
This unit-mounted mechanical control
allows guests to adjust in-room
temperature settings within a preprogrammed range.
Reliability
These features help assure reliable
operation:
Freeze Pr ot ection
When the unit senses temperatures of
40°F or below, the unit activates the fan
motor and either the electric resistance
heater or the hydronic heater to help
prevent pipes or fixtures from freezing.
This also overrides front desk control of
the unit mounted or wall sensor.
Automatic Emer gency Heat
Each unit automatically switc hes over to
electric resistance heat if for any reason
the heat pump compressor system fails
or if the heating load is greater than the
unit capacity.
Random Restart
Avoid troublesome power surges that
can damage electrical circuits. Each unit
has a random restart circuit to prevent all
units from restarting at one time after
power disruption.
Compressor Restart Delay
Extend compressor life. The unit
automatically delays any restart at tempt
by three minutes to allow the refrigerant
pressures time to equalize.
Quiet Operation
State-of-the-art design and construction
provide a quiet environment for guests
to relax. Contributing to the quiet
operation of the unit are:
•An acoustically insulated bulkhead.
•Acoustical rubber -in-shear isolators
under the compressor.
•An isolated fan motor.
Operating sound levels are further
dampened when the unit is in the LO W
FAN mode of operation.
Comfort
Dehumidification and air filtration are
both factors affecting comfort. When the
air is dehumidified, occupants feel more
comfortable at higher temperatures.
T rane PTACs help maintain lower
humidity levels in rooms, without the
need for expensive add-on’s. Another
benefit is that dehumidification can help
extend the life of furniture, wall
coverings and fixtures.
When ventilation air is filtered, rooms
stay cleaner, longer. The hidden
ventilation air intake filters outside air to
reduce dust and pollen.
User -F r iendly Contr ols
Controls are easy to read, understand
and activate.
PTAC-PRC00 1 -EN4
Features and
Benefits
Remote Thermostat Control
Each unit is built to be operated from a
remote-mounted thermostat, if desired.
Even if it is started without a remote, a
built-in low voltage power source can
accommodate a large variety of
thermostat choices — manual, auto
changeover or programmable — at a
later date.
Remote T emperature Sensing
Occupants enjoy ultimate comfort with
consistent climate control. Attach an
optional, inexpensive remote thermistor
temperature sensing device and
temperatures are held more closely to
the chosen room set ting.
Attractive and Compact Design
The unit front has a sleek seven-inch
depth, one of the shallowest silhouettes
in the industry today. To inhibit
tampering, the front can be secured to
the chassis with hidden screws.
Our unit’s new stylish design and neutral
color make it compatible with virtually
any room decor or arc hitectural design. It
blends into the room’s color scheme.
Special Paint Prot ection
The electrodeposition paint system on
the exterior panels assure the unit and
wall sleeve will withstand years of
moisture and atmospheric pollutants
without giving up its looks to rust and
corrosion.
Ease of Installation and Servicing
After the sleeve is in place, plug in or
directly hard-wire the unit and it is ready
to run. This unit has been designed to
replace most competitors’ units. In fact
this unit can fit into most existing
sleeves, making replacement of old or
inefficient units easy and economical.
And of course, the units may be installed
flush with the outside wall.
The main components are easily
serviced; the unit is easy to diagnose or
troubleshoot to spot potential problems.
When the filter needs to be cleaned or
replaced, the filt er access door tilts
forwar d for easy access. F or more
extensive service, the unit slides out of
the sleeve easily for full access t o all
working components.
5PTAC-PRC001-EN
Application
Considerations
Curtain Wall InstallationBlock and Brick Veneer InstallationFrame and Bric k Veneer Installation
Optional Leveling LegPanel Wall InstallationPanel Wall and Block V eneer Installation
On applications not requiring subbase or lev eling legs, unit may be flush mount ed t o floor.
Sleeve Installation Da ta
Framing for Wall CaseFraming With LintelAttaching W all Sleeve to Opening
1. 3¼” minimum with subbase.
2. On applications not requiring subbase or
leveling legs, unit may be flush mounted to floor.
1. Corrosion resistant, condensate pump, power vent units and all special units require extended ship cycles.
2. Only the following units are available from stock and can normally ship within 3 days after release.
3. Contact your local Trane representative for current stock availability and information on minimum quantity
requirements and shipping schedule for special production units.
Digit 8 — Main Pow er Supply
1 = 208-230/60/1
2 = 265/60/1
Digit 9 — Electric Heating Capacity**
0 = No Electric Heat – Air Conditioners Only
E = 2.5 kW
G = 3.5 kW (208-230V)
G = 3.7 kW (265V)
J = 5.0 kW*
Digit 10 — Design Sequence
Digit 1 1— Miscellaneous
A = Standard
B = Power Vent
C = Corrosion Resistant
D = Condensate Pump
H = Hydronic Chassis
F = Hydronic with Power Vent and Door
G = Hydronic with Power Door
J = Power Door
K = Condensate Pump with Power Vent
L = Condensate Pump with Power Door
*Sizes 09, 12 and 15 only.
**All heat pump units must have electric coils.
7PTAC-PRC001-EN
P erformance
Data
Table PD-1 — Cooling Performance — Air Conditioner with Electr ic Heat Models
Model TypeAir Conditioner
Model No.
Voltage
Capacity (Btu)
Amps3.02.82.33.83.73.05.05.04.36.96.95.9
Watts6006106107858058051 11011 101130152015451525
EER1 1.611.61 1.611.31 1.311.310.710.71 0.79.29.29.3
Unit without Electric Heater
Min. Circuit/Ampacity
cfm (cool, wet coil)
* 95 cfm with optional power vent kit. Actual vent cfm performance will vary due to application and installation conditions.
Table PD-2 — Cooling Performance —Heat Pump with Electric Heat Models
Model TypeHeat Pumps
Model No.
Voltage
Capacity(Btu)
Amps3.02.82.33.83.53.05.04.64.36.96.35.9
Watts6106156157858058051 1101 1201120148515051505
EER1 1.511.51 1.511.21 1.211.210.710.710.79.39.39.3
Unit without Electric Heater
Min Circuit/Ampacity
cfm (cool, wet coil)
*95 cfm with optional power vent kit. Actual vent cfm performance will vary due to application and installation conditions.
Notes:
1. All 265 volt models must use Trane’s subbase or Trane’s hard-wire junction box kit.
2. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
3. Minimum voltage on 208/230 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
4. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included and
5. Minimum operating ambient = 45°F.
6. Certified in accordance with the Unitary Air-Conditioner Equipment certification program, which is based on ARI standard 310/380.
EER — Energy Efficiency Ratio per American Refrigeration Institute (ARI) Test Procedures.
COP — Coefficient of Performance per ARI Test Procedures.
1 & 5
3
6
2 & 4
High240245245240245245325315325315325325
Low205220220205220220250220250220250250
High260265265260265265345335345335345345
Low215230230215230230265235265235265265
1 & 5
3
6
2 & 4
High240245245240245245315325325315325325
Low205220220205220220220250250220250250
High260265265260265265335345345335345345
Low215230230215230230235265265235265265
factory installed on Trane chassis). Note: All heat pump units must have electric coils.
1. All 265 volt models must use Trane’s subbase or Trane’s hard-wire junction box kit.
2. Heating capacity and efficiency is based on unit operation without condensate pump. Unit automatically switches to electric heat at 25°F outdoor coil temperature.
*Based on ARI Rating Conditions of 70°F Entering Air Temp., 200°F Entering Water Temp and 180°F Leaving Water Temp.
Max Water Temperature 200°F Max. Water Pressure - 200 psig.
2-WayFan SpeedF an SpeedFan SpeedFan SpeedFan SpeedF an Speed
Heating Capacity (Btu) Hot Water
Table PD-9 — Heating Capacity — Steam
7,000 & 9,000 Btu Units12,000 Btu Units15,000 Btu Units
Voltage
208/2302.0/2.516,8008,500—2,140/2,65010.2/11.514.2156-15 P
208/2302.9/3.519,90012,000—3,040/3,65014.5/15.819.6206-20 P
208/2304.1/5.0**14,00017,100—4,240/5,15020.3/22.327.7306-30 P
2652.51——8,5002,6501 012.4157-20 P
2653.71——12,6003,85014.618.1207-20 P
2655.0**——17,1005,15019.524.2257-30 P
Notes:
1. Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
2. Minimum voltage on 208/230 volt models is 197 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 238.5 volts; maximum is 291.5 volts.
3. Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-style time delay fuses (included and
factory installed on Trane chassis).
4. Total watts for 7,000 and 9,000 Btu models; add 40 watts for size 12 and 70 watts for size 15.
**PTHC07, 09 and 12 are two-stage; PTHC15 is one-stage.
*** Note: All heat pumps must have electric coils.
Table EP-2 — Pow er Receptacle Configurations
Voltage208/230265
Unit Supplied Plug
HeaterNo. OfT otalT otalPower
Size (kW)StagesBtu 208Btu 230Btu 265Watts
4
AmpsAmpacity1Protection
3
Cord
Amps1 520302030
NEMA Rating6-15P6-20P6-30P7-20P7-30P
Receptacle
Amps2020302030
NEMA Rating6-20R6-20R6-30R7-20R7-30R
Notes:
1. All wiring, including receptacles, must be made in accordance with local electrical codes and regulations.
2. NEMA 6-15 and 6-20 plugs fit in NEMA 6-20 receptacles.
3. Receptacles shown for 208/230 applications are factory supplied with subbase, per local codes for wall mounted receptacles use or the corresponding NEMA receptacles.
4. Receptacles shown for 265 volt applications are factory supplied with subbase. Codes do not allow 265 volt units to mate with wall mounted receptacles. They may however be
hard-wired per Local Codes.
15PTA C-PRC001 -EN
Unit with Wall Sleeve and Subbase Accessory
Dimension and
Weights
T op View
Front View
Notes:
1. Allow a minimum of 31/4” clearance between cabinet and floor to permit installation of options subbase.
2. Allow minimum of 3” clearance between cabinet and side walls to permit front panel removal.
3. Drain tube can be mounted either right side, left side or bottom of sleeve. Bottom drain to be located by customer. Drain kit shipped separate.
4. Unit provides 20 percent outside air.
5. Detachable cord ships attached to unit. Cord can be removed for direct attachment of building wiring or wiring from junction box kit.
6. For U.S. approval — 265 volt units and units with duct packages must have permanent wiring connection. Permanent wiring requirement can be met either by supplying
afull length subbase for concealed cord connection or by direct wiring with junction box kit.
7. Control door provided on standard unit for access to controls.
Right Side View
PTAC-PRC00 1 -EN16
Dimension and
Weights
Field Supplied Extension
17PTA C-PRC001 -EN
Hydronic Heat Kit
NOTE: W all sleeve must
extend exactly 3 inches
from finished interior
wall
Dimension and
Weights
Notes:
1. This kit completely encloses all plumbing and coils, but still allows easy access to controls.
2. The chassis can slide out for easy service without removing hydronic plumbing.
3. The kits feature left or right-hand piping.
4. Unit retains complete service access with kit installed.
PTAC-PRC00 1 -EN18
Dimension and
Weights
Duct Pack age
When two adjacent rooms need to be conditioned, a main duct kit and a duct extension kit are possible options. These kits transfer
air from one room to another, yet allow different air flows for the rooms (airflow distribution can be adjusted from
65/45 to 80/20.)
Front View
Duct T ermination Kit
The Duct Termination Kit
includes a grille and a
sleeve for fit ting duct or
duct extension through
the wall.
19PTA C-PRC001 -EN
Mec hanical
Specifications
Unit Chassis
Each unit will be slide-out design shipped
with room cabinet front installed. Unit
chassis will have the ability to be installed
with zero reversing clearance from
finished floor. An electrical power cord
will be included with chassis and
installed by the manufacturer to assure
proper NEMA 6 or 7 configuration and
UL approved length. Unit will be tested
for conformance to AS TME w ater
infiltration specification AS TME 331 -86
which assures no water infiltration when
tested at eight inches of rain per hour at
63 mph wind for 15 minutes.
Room Cabinet/Front P anel
The room cabinet/front panel will have
sloped discharge so that obstructions are
not placed on unit. The discharge
conditioned air can be directed into the
room at an angle of 15 to 40 degrees
from the vertical position. The discharge
grille will be a polycarbonate material to
resist bending, cracking, rusting and
corrosion. The front panel will be able to
be field secured to chassis to inhibit
tampering. Cabinet depth will be seveninch to minimize unit’s impact on room
space.
Filter
The filter will be accessible without
removing room front. Filter material will
be nylon mesh, permanent cleanable.
Condenser/Evaporat or F ans
One direct drive with a permanent split
capacitor two-speed motor. The
condenser fan will be propeller type and
the indoor evaporator fan will be a
centrifugal blower type.
Cooling Condensate Remov al
High humidity conditions may call for
condensate removal system. The
outdoor fan diffuses water directly on to
the outdoor condenser coil for rapid
evaporation and increased cooling
efficiency .
Compressor
The compressor will be hermetically
sealed, internally isolated, rotary-type
and permanently mounted on rubber
isolators. No removal or adjustment of
compressor hold down bolts will be
required during installation.
Coils
Coils will have rifled copper tubing
expanded into rippled-edge louvered
aluminum fins.
Heat Pumps
Heat pumps will include a changeover
thermostat that senses an outside coil
switch-over temperature of 25°F,
lock-open refrigerant valve during heat
pump operation, temperature-activated
defrost drain and automatic emergency
heat operation to override the heat
pump’s changeover thermostat and
bring on electric resistance heaters in the
event of a sealed system failure. Unit will
not operate compressor and electric
heaters simultaneously.
Outside Air Damper/V ent Control
The vent control will allow 65 to 70 cfm
of fresh air to be drawn into the room.
This fresh air can provide ventilation
when the blower is operating. T o obtain
access to the vent control, remove the
cabinet front. The vent control lever is on
the left side of the c hassis. The control
lever must be rotated to either open or
close the damper. Actual vent cfm
performance will vary due to application
and installation conditions.
Filtered Outdoor Air Intake
The outdoor air intake will be filtered
with a talc-filled polypropylene filter that
will reduce dust from coming into the
room.
Paint System Cor r osion Pr otection
All units are built with hot-dipped
galvanized steel. Metal parts are then run
through a six-stage zinc phosphate
cleaner/pretreatment, painted with a
cathodic electroplating of an epoxy resin
paint and baked for 20 minutes at 350°F.
All exterior parts that are exposed to
sunlight get an additional coating of
polyester and are baked for 20 minutes
at 350°F for additional protection from
the fading effects of ultraviolet rays. This
paint process makes the unit highly
resistant to normal rust, corrosion and
fading. It is the best paint process in the
industry today.
Corrosion-Resistant Chassis (Standar d
Option)
The condenser coil is painted using
cathodic electrocoat. The bottom ¼ of the
compressor is coated with a water borne
resin. The outdoor side of interior parts
are top coated, in addition, the base pan
is cathodic electrocoated.
PTAC-PRC00 1 -EN20
Mec hanical
Specifications
Unit Controls
The unit controls will be full solid-state
and accessible from the top. The
standard unit mounted controls will
include two rotary (switch) knobs
controlling unit operational and
temperature mode. The unit operational
switch includes:
• Off position.
• Fan only — unit operates on low fan
speed.
• Low cool — unit operates on low fan
speed to circulate air for cooling.
• High cool — unit operates on high fan
speed to circulate air for cooling.
• Low heat — unit operates on low fan
speed to circulate air for heating.
• High heat — unit operates on high fan
speed to circulate air for heating.
Temperature Switc h
The temperature switch is controlled by
turning the knob clockwise for a cooler
room temperature; turning it
counterclockwise will provide a w armer
room temperature. Adjusting the
thermostat to the mid setting (vertical)
will set the room temperature at
approximately 75°F.
Remote Control Operation
To operate units with remote
thermostats, the Standard/Remote unit
mounted switch must be set to the
remote position. When in the remote
position, the unit will only respond to the
wall-mounted thermostat inputs. Unit
will operate on low or high fan.
Remote Thermostat/Sensor T erminals
These terminals provide control inputs
for a remote thermostat or sensor.
Front Desk Contr ol Terminals
These terminals provide control inputs
for a front desk switch.
Load Shedding Terminals
The LS/IN terminals will provide a
connection for a switch that can be
added to close the circuit and lockout the
compressor and electric heat when the
power company or energy management
system is trying to reduce its load for a
specific time.
On Board Diagnostics
An LED light will flash a code displaying
8 conditions: Control OK, 24 Vac Fuse
Blown, ICT (Indoor Coil T emperature)
Probe Failure, Mode Switc h F ailure,
Potentiometer Failure, Bad Thermostat
Input Failure, Bad Communications in
Slave Mode, and IAT (Indoor Air
Temperature) Failure. A spare 500 MA
fuse has been provided on the board.
Temperature Limiter
The temperature limiting feature can
reduce energy costs by controlling the
maximum temperature in heating and
the minimum temperature in cooling.
Room Freez e Prot ection
Freeze protection is built into all units
and will activate the electric resistance
heater (when it senses a temperature of
40°F room temperature) to maintain an
above freezing temperature at the
sensor.
Fan Cycle S witch
The fan cycle switch sets the operational
mode of the fan. In the ON position, the
fan will run continuously whenever the
unit is in the heat or cool position. In the
AUTO position, the fan will cycle on and
off with the compressor or electric heater
when the unit is in the cool or heat
mode.
Aut omatic Emerg ency Heat Staged
Thermostat
On every unit mounted control heat
pump, electric heat engages
automatically if the sealed system or
compressor fails.
Compressor Time Delay
The compressor will not try to restart
once running or until approximately
three minutes have elapsed after
shutdown.
21PTA C-PRC001 -EN
Options
Options
Wall Sleeves
Wall sleeves shall be industry standard
size of 13¾”D x 42”W x 16
Extended Wall Sleeves
Extended wall sleeves shall be industry
standard size of 18”D x 42”W x 16
or 24” D x 42”W x 16
Drain Kit
Drain kit attaches to the bot tom of the
wall sleeve for directional controlled
internal or external disposal of
condensate and defrost water.
Outdoor Grilles
Outdoor grilles are available as
architectural extruded, anodized
aluminum and four standard colors.
Special colors are also available or
standard stamped aluminum.
Condenser Baffle Kit
The condenser baffle kit is required
when replacing an existing packaged
terminal unit and/or the original outdoor
grille is not made by Trane. These baffles
are required to deflect discharge air
away from the inlet, preventing
recirculation of hot condenser air.
Leveling Legs Kit
Attaches easily to the w all sleeve for
support and accurate unit leveling on
units without subbases. Adjustable from
5/8
” to 5 ¼”.
2
Subbases
Subbases are prewired to facilitate field
electrical connections and include a
NEMA 6 or 7 configuration electrical
receptacle. The subbases include two
leveling screws for sleeve support and
accurate unit leveling during installation.
Subbases include locations for field
installation of physical disconnect
switches, cartridge-style fuse holders
and circuit breakers. Side skirts will be
included with subbases.
1/16
”H.
1/16
”H.
1/16
”H
Pow er Disconnect S witch Kit
A power disconnect switch must be
installed in hard-wire junction or
subbase for use as a physical disconnect
where required by local codes.
Circuit Breaker Kit
A circuit breaker kit is installed in the
subbase to provide overcurrent
protection for proper 208/230 volt
amperage. Can also be used as a
physical disconnect where local codes
permit 208/230 volts.
Fuse Holder Kit
Fuses are included in 265 volt units. For
208/230 volts, these kits allow fusing in
15, 20 and 30 amps. Fuses are not
included. Fuse holders must be installed
in the unit or subbase.
Hard-Wire Junction Box Kit
Provides for easy electrical connection
when permanent wiring is required.
Hard-wire kit must be used on 265 volt
units if subbases are not used.
Duct T r ansition and Ext ended Kit
A main duct transition piece will attac h to
the discharge of the unit and a duct
extension will be attached to the
transition piece to carry up to 40 percent
of the conditioned air to the adjoining
room.
Pow ered Outside V ent
and Damper Kit
An optional power vent kit can be
installed to increase cfm to 95. The
power damper will automatically open
when the unit is operating and close
when not powered. Actual vent cfm
performance will vary due to application
and installation conditions.
Hydronic Heat Kit
The hydronic heat kit is a field-installed
package that can attac h to air
conditioners to provide central system
hot water or steam heat capability on top
of units. The kit includes left or right-hand
piping. The units retain complete service
access with kit installed.
Control V alves
24 volt water valves are available in
either two-way or three-way for 208/230
volt units and 265 volt units. 24 volt
steam valves are also available for
208/230 and 265 volt units.
Remote/Wall Ther mostats
Manual changeover thermostat
One-stage heat, One-stage cool and Off
Switch.
Automatic changeover thermostat with
T wo-stage Heat and One-stage Cool and
Off Switc h.
T wo-stage Heat (heat pump only) First
stage brings on electric coil when room
temperature is more than 3.8°F cooler
than thermostat setting; then electric
heat will turn off and heat pump cycles
on. Also one-stage Cool with Manual
Changeover.
T wo-stage Heat and One-stage Cool with
Manual Changeover and Programmable.
Remote T emperature Sensor
This temperature sensor overrides
standard unit mounted sensor to allow
temperature sensing on internal wall for
more accurate temperature control.
Condensate Remov al Pump —Heat
Pump Only
The internal condensate pump serves as
an effective means for disposing of
condensate generated during heat pump
operation by transferring it to the indoor
coil. The warm coil surface and the warm
room air help in evaporation of the
condensate while adding humidity to the
room. As with any equipment of this
type, the addition of this kit will decrease
the sensible heating capacity of the unit.
This kit is not intended for use in
seacoast or corrosive environments.
Note: Under extreme high humidity conditions, the
internal condensate pump may not be able to dispose of
all the condensate produced, and condensate would
then drip from the outside of the wall sleeve. If this
condensation is unacceptable, then a drain system
(including factory approved drain kit for the wall sleeve)
should be installed.
Control Cov er Key Loc k Kit
Allows the owner to lock the control
panel access to prevent unauthorized
operation.
PTAC-PRC00 1 -EN22
Options
Subbase Kit
The fully skirted subbase conceals wiring
while providing strong support. A plug-in
receptacle and field wiring access
expedites installation. Electrical
accessories such as fuse holders, circuit
breakers and disconnect switches meet
N.E.C. requirements.
Fuse Holder Kit
Cartridge-style fuses can be installed in
the fuse holder for use in the subbase or
chassis. It is available in 1 5, 20 and 30
amp and included on the 265 volt unit.
Condensate Drain Kit
This kit attaches to the w all sleeve base
pan for controlled internal or external
disposal of condensate and defrost
water .
Outdoor Grilles
Outdoor grilles are available in stamped
aluminum and an attractive extruded
aluminum architectural grille.
Security Ke y Locks
The installation of T rane’s security key
locks helps prevent tampering of the
controls used to set temperature,
heating and cooling functions. Locks are
available for all PT AC models.
Deflector Baffle Kit
The kit includes two air deflection baffles.
These deflectors direct the air in toward
the center and away from the inlet to
prevent recirculation of the hot
condenser air. This kit is
when the outdoor grille is provided by
T rane.
Hard-Wire Kit
This kit is used to permanently wire to
chassis when standard subbase and
power cord are not utilized.
Circuit Breaker Kit
The circuit breaker kit, available in 15, 20,
25 or 30 amp, can be used with T rane’s
subbases. It gives overcurrent protection
and its location allows turning unit on or
off without tools.
not
to be used
Pow er Disconnect Switc h
The power disconnect switch can be
used for 265 or 208/230 volt physical
disconnect where required by local
codes. The switch is rated at 30 amp
capacity. The switch is for use with
T rane’s standard subbases or hard
wire kit.
Pow er Vent and D amper Kit
Installation of the power vent can
increase the cfm to 70. The damper will
automatically close when unit is not
powered.
Pow er Door Kit
Door will power open to allow fresh air
when the unit fan is on and spring
closed when the unit fan is off.
Remote T emperature Sensor
This sensor allows for inexpensive
temperature sensing on an internal wall
for more accurate temperature control.
23PTA C-PRC001 -EN
Warranty
W ar ranty Info r mation
Standard War ranty
•Full First-Year W arranty
T rane will repair or replace, free of
charge including labor , an y part whic h
proves to be defective due to
workmanship or materials.
•Full Fiv e-Year Sealed System
Warranty
T rane will repair or replace, free of
charge including labor , the evaporator,
condenser, compressor or connecting
tubing which proves to be defective due
to workmanship or materials.
•Limited Second thr ough Fif th Year
Warranty
During the 2nd through 5th year, Trane
will provide, free of charge, functional
parts whic h prove to be defective due to
workmanship or materials. Components
covered are switc hes, solenoids, fan
motors, thermostats, circuit boards,
factory installed heaters, blower wheel,
fan propeller and capacitor.
This limited warranty does not include
diagnostic time, labor or any
transportation and reinstallation c harges
that may be required.
PTAC-PRC00 1 -EN24
The T rane Company
An American Standard Company
www.trane.com
For more information contact your local
distributor (dealer), local district office, or
e-mail us at comfort@trane.com
Literature Order Number
File Number
Supersedes
Stocking Location
Since The Trane Company has a policy of continuous product and product data improvement, it reserves the
right to change design and specifications without notice.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.