Trane J4PG4024A1060AA, J4PG4030A1060AA, J4PG4036A1090AA, J4PG4042A1090AA, J4PG4048A1090AA Installation Instructions Manual

...
INSTALLATION INSTRUCTIONS
PACKAGE GAS ELECTRIC UNITS
FEATURING R-410A
14 SEER SERIES - (2-5T
C
RECOGNIZE THIS SYMBOL
CONFORMS TO STD. 1995 CERTIFIED TO CSA STD. C22.2 NO. 236
CENTRAL FURNACE CONFORMS TO ANSI
STD Z21.47-2016,
CERTIFIED
STD 2.3-2016
AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
UL
TO CSA
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious injury death or property damage.
WARNING
— Do not store or use gasoline or other flammable
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance; do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
• Do not return to your home until authorized by the gas supplier or fire department.
— Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or death.
Refer to this manual, installation and service must be performed by a qualified installer, service agency or the gas supplier. In
the commonwealth of Massachusetts, installation must be performed by a licensed plumber or gas fitter for appropriate fuel.
vapors and liquids, or other combustible materials in the vicinity of this or any
NOTE: Do not use this furnace if any part has been under water
to use the furnace can result in fire or explosion. A qualified service agency should be contacted to inspect the furnace and to replace all gas controls, control system parts, electrical parts that have been wet or the furnace if deemed necessary.
. A flood-damaged furnace is extremely dangerous. Attempts
DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference by a serviceman.
Installation Start-upOperating and Service and Maintenance Instructions
CONTENTS PAGE
1.0 SAFETY...............................................................................................4
1.1 INSPECTION.................................................................................6
1.2 LIMITATIONS................................................................................6
2.0 INTRODUCTION...................................................................................7
3.0 INSTALLATION..................................................................................10
3.1 PRE-INSTALLATION CHECK-POINTS...........................................10
3.2 LOCATION CONSIDERATIONS.....................................................10
3.3 OUTSIDE INSTALLATION............................................................10
3.4 ATTACHING EXHAUST AND COMBUSTiON AIR INLET HOODS...10
3.5 COVER PANEL INSTAlLATiON / CONVERSION POCEDURE..........10
3.6 CLEARANCE................................................................................11
3.7 RIGGING AND HANDING ............................................................11
3.8 DUCTWORK................................................................................16
3.9 RETURN AIR...............................................................................16
3.10 FILTERS....................................................................................16
4.0 GAS SUPPLY, CONDENSATE DRAIN AND PIPING.............................16
4.1 GAS CONNECTION......................................................................16
4.2 LP CONVERSION.........................................................................17
4.3 ADJUSTING OR CHECKING FURNACE INPUT..............................18
4.4 CONDENSATE DRAIN..................................................................18
5.0 WIRING............................................................................................18
5.1 POWER SUPPLY.........................................................................18
5.2 HOOK-UP....................................................................................18
5.3 INTERNAL WIRING......................................................................19
5.4 THERMOSTAT.............................................................................19
6.0 FURNACE SECTION CONTROLS AND IGNITION SYSTEM..................19
6.1 NORMAL FURNACE OPERATING SEQUENCE...............................19
6.2 OPERATING INSTRUCTIONS.......................................................19
6.3 TO START THE FURNACE............................................................19
6.4 TO SHUT DOWN FURNACE.........................................................20
6.5 BURNERS...................................................................................20
6.6 MANUAL RESET OVERTEMPERATURE CONTROL.......................20
6.7 PRESSURE SWITCH....................................................................20
6.8 LIMIT CONTROL..........................................................................20
7.0 SYSTEM OPERATING INFORMATION.................................................20
7.1 ADVISE THE CUSTOMER..............................................................20
7.2 FURNACE SECTION MAINTENAECE..............................................20
7.3 LUBRICATION..............................................................................21
7.4 COOLING SECTION MAINTENANCE..............................................21
7.5 REPLACEMENT PARTS................................................................21
7.6 TROUBLESHOOTING....................................................................21
7.7 WIRING DIAGRAMS.....................................................................21
7.8 CHARGING...................................................................................21
7.9 BLOWER MOTOR SPEED TAPS.....................................................21
8.0 OPERATION.......................................................................................22
8.1 CONTROL SYSTEM OPERATION.................................................22
8.2 FAN DELAY ADJUSTMENT .........................................................22
9.0 PHYSICAL DATA................................................................................23
10.0 AIRFLOW PERFORMANCE...............................................................25
11.0 TROUBLE SHOOTING.......................................................................30
This document is customer property and is to remain with this unit. These instructions do not cover all the different variations of systems nor does it provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATION, STATE AND LOCAL CODES. If additional information is required please contact your local distributor.
1.0 SAFETY
When you see the symbols below on labels or in the manual, be alert
to the potential or immediate hazards of personal injury, property and/or product damage. It is the owner’s or installer’s responsibility to
comply with all safety instructions and information accompanying these symbols.
WARNING: This is a safety alert symbol indicating a potential
hazardous situation, which could result in personal injury,
property and/or product damage or death.
CAUTION: This is a safety alert symbol indicating a potential
hazardous situation, which could result in moderate personal
injury, and/or property and product damage.
WARNING
Proposition 65: This appliance contains fiberglass insulation. Respirable particles of fiberglass are known to the state of California to cause cancer. Exhaust gas from this appliance contains chemicals, including carbon monoxide, known to the state of california to cause birth defects of other reproductive harm.
WARNING
Never allow products of combustion or the flue products to enter the return air ductwork, or the circulating air supply. All return ductwork must be adequately sealed and secured to the furnace with sheet metal screws, and joints taped. All other duct joints must be secured with approved connections and sealed airtight. Failure to prevent products of combustion from being circulated
into the living space can create potentially hazardous conditions,
including Carbon Monoxide poisoning that could result in personal injury or death.
WARNING
These instructions are intended as an aid to qualified, licensed service personnel for proper installation, adjustment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
WARNING
The manufacturer’s warranty does not cover any damage or
defect to the gas/electric unit caused by the attachment or use of any components, accessories or devices (other than those
authorized by the manufacturer) into, onto or in conjunction with
the gas/electric unit. You should be aware that the use of
unauthorized components, accessories or devices may
adversely affect the operation of the gas/electric unit and may also endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such
unauthorized components, accessories or devices.
WARNING
Do not, under any circumstances, connect return ductwork to any other heat producing device such as a fireplace insert, stove, etc.
Unauthorized use of such devices may result in fire, Carbon
Monoxide poisoning, explosion, property damage, severe personal injury or death.
WARNING
This unit is designed certified for outdoor installation only. Installation inside any part of a structure can result in inadequate unit performance as well as property damage. Installation inside can also cause recirculation of flue products into the conditioned space resulting in personal injury or death.
WARNING
The spark ignitor and ignition lead from the ignition control are high voltage. Keep hands or tools away to prevent electrical shock. Shut off electrical power before servicing any of the controls. Failure to adhere to this warning can result in personal injury or death.
WARNING
Holes in the exhaust transition or heat exchanger can cause toxic fumes to enter the home. The exhaust transition or heat exchanger must be replaced if they have holes or cracks in them. Failure to do so can cause Carbon Monoxide poisoning resulting in personal injury or death.
WARNING
Do not attempt to manually light this furnace with a match or any open flame. Attempting to do so can cause fire or explosion resulting in property damage, personal injury or death.
WARNING
Should overheating occur or the gas supply fail to shut off. Shut off the Manual Gas valve to the appliance before shutting off the supply. Failure to do so can result in an explosion or fire causing property damage, severe personal injury or death.
WARNING
Disconnect all power to the unit before starting maintenance. Failure to do so can result in severe electrical shock or death. Regular maintenance will reduce the buildup of contaminants
and help to protect the unit’s finish.
WARNING
Turn off the main electrical power at the branch circuit disconnect closest to the unit before attempting any wiring. Failure to do so can cause electrical shock resulting in personal injury or death.
WARNING
DO NOT JUMPER THIS DEVICE! Do not reset the overtemperature control without taking corrective action to assure that an adequate supply of combustion air is maintained under all conditions of operation. Failure to do so can result in Carbon Monoxide poisoning or death. Replace this control only with the identical replacement part.
WARNING
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation resulting in fire ,electrical shock, property damage, personal injury or death.
installation & owner’s manual
4
WARNING
CAUTION
This unit is equipped at the factory for use on Natural Gas only. Conversion to LP Gas requires a special kit enclosed instructions with. DO NOT BURN ANY LIQUID FUEL OR SOLID FUEL IN THIS UNIT. Burning any unapproved fuel will result in damage to this unit heat exchanger, which could result in fire, Carbon Monoxide poisoning, explosion, personal injury, property damage or death.
WARNING
Install this unit only in a location and position as specified in the location requirements and considerations section of these instructions. Provide adequate combustion and ventilation air to the unit space as specified in the venting section of these instructions.
WARNING
Do not use this unit during construction if air laden corrosive compounds are present such as chlorine and fluorine. Otherwise, provisions must be taken to provide clean, uncontaminated combustion and ventilation air to the unit, combustion and ventilation air contaminated with these compounds forms acids during combustion which corrodes the heat exchanger and component parts, some of these contaminates are found in, but not limited to, paneling, dry wall, adhesives, paints, stains, varnishes, sealers, and masonry cleaning materials.
R410A systems operate at higher pressures than R22 systems. Do not use R22 service equipment or components on R410A equipment.
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in dangerous operation, serious injury, death or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage.
• Before servicing, disconnect all electrical power to furnace.
• When servicing controls, label all wires prior to disconnecting.
Reconnect wires correctly.
• Verify proper operation after servicing.
Improper installation, adjustment, alteration, service, Maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product.
Refer to the individual instructions packaged with the kits or accessories when installing.
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK, AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in dangerous operation, serious injury, death or property damage. Improper installation,adjustment,alteration,service, maintenance or use could cause carbon monoxide poisoning explosionfireelectrical shock or other conditions which may cause personal injury or property damage. Consult a qualified service agencylocal gas supplier or your distributor or branch for information or assistance. The qualified service
agency must use only factory-authorized and listed kits or
accessories when modifying this product.
WARNING
Always install unit to operate within the unit’s intended
temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in ducting section of these instructions, see also unit rating plate.
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure. Application of this furnace should be outdoors with special
attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
CAUTION
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions include in literature and attached to the unit. Consult local building codes,the
current editions of the National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the National Standards of Canada CAN/CSA-BI49.1 and .2 Natural Gas and Propane Installation Codes, and Canadian Electrical Code CSA C22.1
Recognize safety information. This is the safety-alert symbol . When
you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which
could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced Installation, reliability, or operation.
● Use only with type of gas approved for this unit. Refer to the unit
rating plate.
● Install this unit only in a location and position as specified in the
"Installation" section of these instructions.
● Provide adequate combustion and ventilation air to the unit space
as specified in "Safety" section.
● Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of leaks to check all connections, as specified in the "Gas Supply, Condensate drain and Piping" section.
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing, safety glasses and gloves when handling parts and servicing furnaces.
● Always install unit to operate within the furnace's intended
temperature-rise range with a duct system which has an external static pressure within the allowable range, as specified in the "Safety" section. See also unit rating plate.
installation & owner’s manual
5
● When unit is installed so that supply ducts carry air circulated by the
furnace to areas outside the space containing the furnace, the return
air shall also be handled by duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace. See “Ductwork” and "Return Air" section.
● The unit may be used for construction heat provided that the
furnace installation and operation complies with the CAUTION and WARING instructions in this manual.
● The unit is design-certified for use with natural and propane gases (see unit rating plate) and for installation in outside only. The unit is
factory-shipped for use with natural gas. A listed accessory gas conversion kit is required to convert unit for use with propane gas. The LP conversion kit is included with the unit.
● The unit must be kept free and clear of insulating materials. Inspect
surrounding area to ensure insulation material is in safe distance when installing furnaces or adding insulation materials. Insulation materials may be combustible.
See Table 3-1 for required clearances to combustible construction.
● Before heating season begins, exam the unit to determine that:
a. All flue gas carrying areas external to the unit (i.e. chimney, vent
connector) are clear and free of obstructions.
b. The vent connector is in place, slopes upward and is physically sound
without holes or excessive corrosion.
c. The return-air duct connection(s) is physically sound, is sealed to the
furnace casing, and terminates outside the space containing the furnace.
d. The physical support of the unit is sound without sagging,
cracks, gaps, etc around the base so as to provide a seal
between the support and the base. e. There are no obvious sign of deterioration of the unit. f. The burner flames are in good adjustment (by comparison
with pictorial sketches of the main burner flame.
● Furnace operation needs air for combustion and ventilation.
Do not block or obstruct air openings on furnace or spacing around furnace required for supplying sufficient combustion air and ventilation.
1.1 INSPECTION
As soon as unit is received, it should be inspected and noted for
possible shipping damage during transportation. It is shipper’s
responsibility to cover the cost of shipping damage. Manufacturer or distributor will not accept the claims from dealer for any transportation damage.
1.2 LIMITATIONS
Refer to Fig. 2-2, 2-3 for unit physical data and to Table 7-1 for electrical data. If components are to be added to a unit they must
meet local codes, they are to be installed at the dealer’s and /or the customer’s expense. Size of unit for proposed installation should be
based on heat loss / heat gain calculations made in accordance with
industry recognized procedures identified by the Air conditioning
contractors of America.
Note: Rating plate must be left visible for future reference.
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
A.
This appliance does not have a pilot. it is equipped with an ignition device which automatically lights the burner.
Do not try to light the burner by hand.
BEFORE OPERATING smell all around the appliance
B.
area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
SWITCH SHOWN IN THE “OFF” POSITION
neighbors’ phone. Follow the gas suppliers
Instructions.
• If you cannot reach your gas supplier, call the
fire department. Use only your hand to turn the gas control switch. Never use
C.
tools. If the switch will not turn by hand, don’t try to repair it;
call a qualified service technician. Force or attempted repair may result in a fire or explosion.
Do not use this appliance if any part has been under water.
D.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
5. Remove control access panel.
6. Wait five (5) minutes to clear out any gas. if you
then smell gas, STOP! Follow “B” in the safety
information above on this label. If you don’t smell
gas, go to the next step.
7. Push gas control switch to “ON”.
NOTE: Do not force.
8. Replace control access panel.
9.Turn on all electric power to the appliance.
10.Set thermostat to desired setting
11.If the appliance will not operate, follow instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
See Fig: Instruction of lighting/ shutdown operation. Should the gas supply fail to shut off or if overheating occurs, shut off the gas valve to the furnace before shutting of the electrical supply.
installation & owner’s manual
3. Remove control access panel.
4. Push gas control to “OFF”. Do not force.
5. Replace control access panel.
6
2. INTRODUCTION
A Package Gas Electric Unit is a fully self-contained, combination gas heating/electric cooling unit designed for outdoor installation. All unit
sizes have return and discharge openings for both horizontal and
downflow configurations, and are factory shipped with all downflow duct openings covered. Units may be installed either on a rooftop or on a cement slab. In gas heating mode, this unit is designed for a minimum continuous return-air temperature and a maximum continuous return-air temperature. Failure to follow these return-air temperature limits may affect reliability of heat exchangers, motors, and other components. This booklet contains the installation and operating instructions for your Package Gas Electric Unit. There are some precautions that should be taken to derive maximum satisfaction from it. Improper installation can result in unsatisfactory operation or dangerous conditions. Read this booklet and any instructions packaged with separate equipment required to make up the system prior to installation. Give this booklet to the owner and explain its provisions. The owner should retain this booklet for future reference.
Outdoor fan grille and compressor access
Outdoor coil protective grille
A Package Gas Electric Unit includes a hermetically-sealed refrigerating system consisting of a compressor, condenser coil,
evaporator coil with thermal expansion valve (TXV) or throttle valve, a
circulation air blower, a condenser fan, a heat exchanger assembly, gas burner and control assembly, combustion air motor and fan, and all necessary internal electrical wiring. The cooling system of these units is factory-evacuated, charged and performance tested. All units are factory charged with Refrigerant R410A.
Front
6-5/16″
6-5/8″
10″
High pressure detected valve
1/4’’ SAE
Low pressure detected valve
1/4’’ SAE
Condensate drain conn. 3/4” NPTI
(Trap required)
Electrical service access compartment panel
Combustion air inlet hood
2-3/8″
23″
44-5/8″
High voltage conn. 1-23/64” Dia.
Low voltage conn. 7/8” Dia.
20-7/16″
6-5/8″
3-3/4″
6-3/4″
1-3/4″
41-7/16″
2-3/8″
Flue exhaust hood
10-5/16″
57-15/32″
Blower/Evaporator access panel
Gas supply entrance
Fig. 2-1 Unit Dimensions
installation & owner’s manual
7
15″ 7-5/8″ 3-5/8″
Bottom supply air opening Bottom return air opening
15″
4-3/16″
15″
53-29/32″1-3/4″
57-15/32″
1-5/8″1-15/16″
Bottom View
1-7/8″40-7/8″
Back View
Heat exchanger
installation & owner’s manual
8
Side supply air opening
44-5/8″
Side return air opening
Fig. 2-2 Dimensions Back and Bottom
4-7/8″ 14-1/2″
14-1/2″14-1/2″ 8-5/32″
3-7/8″
Highly efficient enhanced microchannel outdoor coil
Compressor
Axial flow fan
Condenser fan motor
Highly efficient enhanced aluminum/copper tube and aluminum fin indoor coil
Decorative protective coil guard
Heavy gauge removable base rails
Blower motor with slide-out blower assembly
Electrical control box
Combustion air motor and fan
Gas valve
Copper nozzle
Gas burner
Gas tube
Fig. 2-3 Component Location
installation & owner’s manual
9
3.0 INSTALLATION
Install the unit in accordance with The American National Standard Z223.1-latest edition booklet entitled “National Fuel Gas Code”, and the requirements or codes of the local utility or other authority having jurisdiction. Unit should be installed in accordance with national and local safety
codes, including but not limit to ANSI/NFPS No. 70 or Canadian
Electrical Code Part 1, C22.1, local plumbing and wastewater codes and any other applicable codes. Additional helpful publications available from the “National Fire Protection Association” are: NFPA-90A - installation of Air Conditioning and Ventilating Systems 1985 or latest edition. NFPA-90B - Warm Air Heating and Air Conditioning Systems 1984.
3.1 PRE-INSTALLATION CHECK-POINTS
Before installation, carefully check the following:
1. For rooftop installation, be sure the structure has enough strength to support the weight of unit.
2. Clearances and provision for servicing.
3. Power supply and wiring.
4. Gas supply and piping.
5. Air duct connections and sizing.
6. Drain facilities and connections.
7. Location for minimum noise and vibration.
Typical outdoor installation in shown in Figure 3-2:
1. Select a location where external water drainage cannot collect around unit.
2. Locate unit where operating sounds will not disturb owner or neighbors.
3. The location of the unit should allow proper access for inspection and servicing.
4. Locate unit so roof runoff water does not pour directly on the unit. Provide gutter or other shielding at roof level. Do not locate unit in an area where excessive snow drifting may occur or accumulate.
5. Provide a concrete slab extending 3″ beyond all four sides of the
unit. The slab should be sufficiently high enough above grade to prevent surface water from entering the unit. The slab should be isolated from the foundation wall.
6. Pitch the slab approximately 1/2″ so that the unit will be pitched
toward the drain. See Figure 3-3.
7. It is essential that the unit be elevated above the base pad to allow
for defrost water runoff, condensate drainage, and possible
refreezing or condensate. Route condensation off the base pad to
an area that will not become slippery and result in personal injury.
Important: Do not interfere with opening in bottom of unit.
8. Where snowfall is anticipated, the height of the unit above the ground level must be considered. Mount unit high enough to be above average area snowfall to prevent snow from blocking the outdoor coil, to allow condensate runoff, and to allow combustion air to enter the combustion air inlet.
3.2 LOCATION CONSIDERATIONS
The metal parts of the unit may be subject to rust or deterioration in adverse environmental conditions. This oxidation could shorten the
equipment’s useful life. Salt spray, fog or mist in seacoast areas,
sulphur or chlorine from lawn watering systems, and various chemical contaminants from industries such as paper mills and petroleum refineries are especially corrosive.
If the unit is to be installed in an area where contaminants are likely to be a problem, give special attention to the equipment location and exposure:
1. Avoid having lawn sprinkler heads spray directly on the unit cabinet.
2. In coastal areas locate the unit on the side of the building away from the waterfront.
WARNING
Disconnect all power to the unit before starting maintenance. Failure to do so can cause electrical shock resulting in personal injury or death.
3. Shielding by a fence or shrubs may give some protection.
4. Elevate the unit off its slab or base enough to allow air circulation and avoid holding water against the base pan.
5. Frequent washing of the cabinet, fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit.
6. Regular cleaning and waxing of the cabinet with a good automobile polish will provide some protection.
7. Use a good liquid cleaner several times a year to remove matter
that will not wash off with water.
Several different types of protective coatings are offered in some areas. These coatings may provide some benefit, but the effectiveness of such coating materials cannot be verified by the equipment manufacturer. The best protection is frequent cleaning, maintenance and minimal exposure to contaminants.
3.3 OUTSIDE INSTALLATION
WARNING
This unit is designed certified for outdoor installation only. Installation inside any part of a structure can result in inadequate unit performance as well as property damage. Installation inside can also cause recirculation of flue products into the conditioned space resulting in personal injury or death.
3.4 ATTACHING EXHAUST AND COMBUSTiON AIR INLET HOODS
IMPOPTANT: Do not operate this unit without the exhaust and combustion air inlet hood property installed. These hoods are shipped in a carton in the return air compartment inside the unit and must be attached the unit is installed. See Fig. 2-1.
To attach exhaust and combustion air inlet hood:
1. Remove 3 screws securing filter access panel and remove filter
access panel. For location of filter access panel, see Fig.3-4.
2. Remove both exhaust and combustion air inlet hoods from their
carton, located inside the return air compartment.
3. Attach filter access panel.
4, Attach the combustion air inlet hood and the exhaust hood with 4
and 6 screws as shown in Fig. 2-1. Screws are in parts bag shipped in the burner compartment.
5. Vent the unit using the flue exhaust hood, as supplied from the
factory, without alteration addition. The only exception is with factory approved additions. Consult your local unity or other authority having jurisdiction for accepted venting techniques.
3.5 COVER PANEL INSTAlLATION /
CONVERSION POCEDURE
All unit sizes have return and discharge openings for both horizontal
and downflow configurations, and are factory shipped with all downflow duct openings covered, HORIZONTAL is factory shipped.
HORIZONTAL TO DOWNFLOW
1. Remove screws and covers from the supply and return bottom
section.
2. Install gasket (supplied with parts bag) around perimeter of cover
on the insulate side.
3. Secure covers to the side of the unit using existing screws and
those supplied in the parts bag. See Fig. 3-4.
4. Seal duct covers with silicone caulk.
DOWNFLOW TO HORIZONTAL
1. Remove screws and covers from the supply and return bottom
section.
2. Install gasket (factory shipped) around perimeter of cover on the
insulate side.
3. Secure covers to the bottom of the unit using existing screws and
those supplied in the parts bag. See Fig. 3-5.
WARNING
This unit must not be installed directly on wood flooring, Class A, Class B or Class C roof covering materials, or any other combustion structure except as specified in Fig.3-1. Failure to adhere to this warning can cause a fire or explosion resulting in property damage, personal injury or death.
installation & owner’s manual
10
Back View
Nominal 4×4 timber
(Sides only)
Sideflow supply plenum connection
Sideflow return plenum connection
3-1/2″ MIN
1″ MIN
Supply plenum
(Downflow)
Return plenum
(Downflow)
Fig. 3-1 Exception to non-combustible flooring requirement
Both ends must be open for downflow or sideflow ductwork to provide ventilation
Combustible structure
3.6 CLEARANCE
All units require certain clearance for proper operation and service. Refer to Table 3-1 for the minimum clearances required for construction, servicing and proper unit operation.
Table 3-1: Unit Clearance
3
Distance (in.)
24
4
12
0
Direction
1
Top
Front
Rear
Distance (in.)
60
48
2
18
Direction
Right
Left
Bottom
Duct clearance: 1 inch clearance for all sides of air supply duct.
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. The minimum clearance without economizer/fresh air damper. For distance with Economizer/fresh air damper, please refer to the
relevant Install requirement.
3. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
4. If Economizer/fresh air damper is used, a 24″ minimum clearance
is required on left side of unit.
NOTE
For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply air duct.
3.7 RIGGING AND HANDING
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreader bars, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.
CAUTION
Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.
CAUTION
All panels must be secured in place when the unit is lifted. The condenser coils should be protected from rigging cable damage with plywood or other suitable material.
installation & owner’s manual
11
Condensate drain into roof drain if required by local codes
Service access panels Do not block access
Condensate drain into roof drain if required by local codes
Service access panels Do not block access
Supply plenum
Branch circuit disconnect
Union
Gas shut-off valve
Condensate drain into roof drain if required by local codes
Gas shut-off valve
Supply plenum
Trap
Service access panels Do not block access
Branch circuit disconnect
Power supply conduit
Union
Branch circuit disconnect
Branch circuit disconnect
Union
Trap
Gas shut-off valve
Gas supply
Supply duct at
closet ceiling
Filter grill
Slab floor
installation & owner’s manual
12
Power supply conduit
Fig. 3-2 Typical Installations
Union
Trap
Gas supply Service access panels Do not block access
Gas shut-off valve
Loading...
+ 25 hidden pages