Trane IntelliPak I, IntelliPak II Programming Guide

Programming &
Troubleshooting
Guide
IntelliPak™ I and IntelliPak™ II
Commercial Single Zone Rooftop Air Conditioner or
Commercial Rooftop Air Handlers, with Variable Air Volume (VVDA/VVZT) Controls or Constant Air Volume (CVDA/CVZT) Controls
IntelliPak I models
IntelliPak II models
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air­conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
July 2014
S*HF*20-75 S*HL*20-75 S*HG*90-130 S*HK*90-130 W*HB, W*HE S*HJ090-162 W*HCA-C
SAFETY WARNING
RT-SVP07D-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014Trane All rights reserved RT-SVP07D-EN

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Minor running edits.
Addition of “Fault Detection and Diagnostics.,” p. 7
Addition of configuration screen details in
“CONFIGURATION Menu,” p. 98
Addition of testing and troubleshooting details in
“SERVICE MODE Menu (Local Human Interface only),” p. 107
Additional values added to Active Diagnostic - Auto Reset, see p. 118.
Introduction
RT-SVP07D-EN 3
Table of Contents
Introduction ............................................................ 2
Warnings, Cautions, and Notices .....................................2
Copyright ......................................................... 3
Commonly Used Acronyms ............................................. 5
Glossary of Terms ................................................. 6
Menu Keys ....................................................... 11
Data Manipulation Keys ........................................... 12
Unit Operation Keys ...................................................13
General Status Display ................................................. 13
STATUS Menu ........................................................ 26
SETUP Menu .......................................................... 54
Emergency Override Definitions (with LCI or BCI module installed) ...... 66
SETPOINT Menu ...................................................... 86
CONFIGURATION Menu ................................................ 98
SERVICE MODE Menu (Local Human Interface only) ..................... 107
DIAGNOSTICS Menu ................................................. 116
Diagnostics ..................................................... 122
Module Input / Output Descriptions ................................ 150
Index ................................................................ 154
4 RT-SVP07D-EN

Commonly Used Acronyms

For convenience, a number of acronyms and abbreviations are used throughout this manual.These acronyms are alphabetically listed and defined below.
Table 1. Acronyms
act = active, actuator IGV = inlet guide vanes
AH = air handler Indep = Independent
annunc = annunciate INFO = Information Only (Diagnostic)
AS = airside I/O = input/output
aux = auxiliary IOM = installation/operation/ maintenance manual
BAS = Building Automation System IPAK = IntelliPak I™, IntelliPak II™
®
BCI = BACnet
ccfm = cfm/100 (ex. 120.5 CCFM = 12050 CFM) IPCB = Interprocessor Communications Bridge (mod)
cfm = cubic-feet-per-minute iwc = inches water column
cfg = configured, configuration LCI = LonTalk
ckt = circuit LCI-I = LonTalk
cmd = command LH = left-hand
comp(s) = compressor, compressors lo = low
cond(s) = condenser, condensers LON = LonWorks
config = configured, configuration LRE = leaving recovery exhaust
ctrl = control max = maximum
CV = constant volume manif = manifolded
CVDA = Const. Volume airflow/Discharge Air temp ctrl MCM = Multiple Circuit Module
CVZT = Const. Volume airflow/Zone Temp ctrl MDM = Modulating Dehumidification Module
cw = clockwise min = minimum, minute
cww = counterclockwise misc = miscellaneous
cy = cycle mod = modulating, module
DCV = Demand Control Ventilation MPM = Multi-Purpose Module
dflt = default MWU = morning warm-up
diag = diagnostic NSB = Night Setback Panel
dmpr = damper num = number
DWU = daytime warm-up O/A, OA = outside air
DX = direct expansion (compressor control) occ = occupied
E/A, EA = exhaust air OVRD = override
ECEM = Exhaust Comparative Enthalpy Module PAR = partial system disable, auto reset
econ = economizer, economizing PMR = partial system disable, manual reset
ent = entering pos = position
evap = evaporator O/A, OA = outside air
F/A, FA = fresh air pot = potentiometer
FDD = Fault Detection and Diagnostics PPM = parts per million
funct = function press = pressure
GBAS = Generic Building Automation System (module) prop = proportional
HEAT = heat, heater, Heat (module) psig = pounds-per-square-inch gauge pressure
HGBP = hot gas bypass PWS = part-winding start
HGP = hot gas bypass R/A, RA = return air
hi = high refrig = refrigerant
HI = Human Interface (module) RHI = Remote Human Interface (module)
HO = History Only (Diagnostic) rpm = revolutions-per-minute
HVAC = heating, ventilation and air conditioning ICS = Integrated Comfort System
Communication Interface Module IPC = interprocessor communications
®
Communication Interface Module
®
Communication Interface for IPAK
®
(Echelon®, etc.)
RT-SVP07D-EN 5
Commonly Used Acronyms
Table 1. Acronyms (continued)
RHI = Remote Human Interface (module) UCM = unit control module
rpm = revolutions-per-minute unocc = unoccupied
RT = rooftop unit VAV = variable air volume
RTM = rooftop module VCM = Ventilation Control Module
S/A, SA = supply air vdc = volts dc
SAP = supply air pressure vent = ventilation
sat = saturated vfd = variable frequency drive
SCM = Single Circuit Module VOM = ventilation override module
SF = supply fan VSM = variable speed (compressor) module
src = source VSC = variable speed compressor
stg = stage VVDA = Variable Volume airflow/Discharge Air temp ctrl
stnd = standard VVZT = Variable Volume airflow/Zone Temp ctrl
stpt, stp = setpoint w/, w- = with
sw = switch w/o, wo- = without
sz = single-zone (unit airflow) w.c. = water column
TCI = Tracer Communications Interface (module) wu = warm-up
temp = temperature XL = across-the-line start
RH = right-hand, relative humidity
Notes:
1. Echelon, LON, LONWORKS, LonBuilder, NodeBuilder, LonManager, LonTalk, LonUsers, Neuron, 3120, 3150, the Echelon logo, and the LonUsers logo are trademarks of Echelon Corporation registered in the United States and other countries. LonLink, LonResponse, LonSupport, LonMaker, and LonPoint are trademarks of Echelon Corporation.
®
2. BACnet Inc. (ASHRAE.)
is a registered trademark of the American Society of Heating, Refrigeration and Air-conditioning Engineers

Glossary of Terms

Carefully review these definitions since they are used throughout this document and the Installation, Operation, Maintenance Guide (IOM). Knowledge of these terms is essential in gaining an understanding of how these units operate.
Active Setpoints. The setpoint which is currently being used by the specified control.
BACnet. An open, device networking communications protocol for controls.This protocol utilizes BACnet and ANSI/
ASHRAE control systems or subsystems together
Comparative Enthalpy. An economizer/cooling control strategy which compares return air enthalpy with outdoor
enthalpy. If the outdoor enthalpy is significantly less than return enthalpy the economizer will be utilized for cooling.
Compressor Protection Switch. (See Low Pressure Control). A pressure switch installed on the suction line that
prevents compressor operation below the switch’s setpoint. The purpose is to prevent no-flow scroll compressor operation.
Comm3/4. A Trane proprietary network communication protocol.
Comm5. Trane's implementation of LonTalk (an open network communication protocol).
Condenser Pressure. The saturated condenser pressure measured on each circuit's condenser section on Evaporative
Condenser units. Condenser pressure is converted to Saturated CondenserTemperature for display on the Human Interface.The data from these sensors is used in head pressure control.
Control Band. The range of temperatures, pressures or humidity which would normally be maintained by the various
control functions.
Control Point. The value of a setpoint that an algorithm is using at any given time.
®
Standard 135-2004 protocol which provides building owners the capability to connect various types of building
6 RT-SVP07D-EN
Commonly Used Acronyms
Deadband. A narrow band of sensor range equally spaced above and below the setpoint that defines a region where
the algorithm will be satisfied and the controlled output will be maintained without change.
Dehumidification Override High Zone Temp. The temperature in the critical zone on VAV units where
Dehumidification is disabled to prevent over-heating the space due to excess reheat.
Dehumidification Override Low Zone Temp. The temperature in the critical zone on VAV units where
Dehumidification is disabled to prevent sub-cooling the space due to insufficient reheat.
Demand Control Ventilation (DCV). An ASHRAE compliant ventilation scheme that varies the Outside Air Damper
minimum position or Fresh Air Flow (TRAQs) between minimum and maximum ventilation Setpoints based on CO2 level.
Dry Bulb. An outdoor temperature above which economizing will be disabled (unless comparative enthalpy is the
economizer control type being used.)
Economizer Zone Temp Setpoint Suppression. A parameter used for setting the active economizer cooling control
point to a value lower than the Zone Temp Cooling Setpoint to optimize economizer operation.
Emergency Stop. A binary input on the RTM, connected to a field-supplied switch, when set to OPEN causes a unit
shutdown with a manual reset diagnostic.
Energy RecoveryWheel. A wheel that rotates through the outdoor and exhaust air streams, transferring energy
between the two, to optimize unit efficiency.
Evap Diff. Evaporator Differential is a parameter indicating performance of a refrigeration system. It is calculated by
determining the difference between the entering and leaving temperatures of the evaporator. If this value rises too high it may indicate a problem with the system.
External Stop. A binary input on the RTM, connected to a field-supplied switch, when set to OPEN causes a unit stop
request.
Fault Detection and Diagnostics. A feature that determines whether the Outside Air damper actuator has failed to
control the damper properly, and annunciates specific diagnostics under such conditions.
Hot Gas Bypass. A feature to reduce a refrigeration circuit's cooling capacity by bypassing hot discharge line
refrigerant directly to the evaporator coil of the system to more effectively operate in low load conditions.
Humidification Control. During modes of continuous fan operation a relay is energized when the Humidity measured
in the controlled space drops below an adjustable Humidification Setpoint.The humidifier device is a user supplied device placed in the supply air stream.
IntelliPak™ I. Units covering the 20 through 130 ton capacity IntelliPak cabinet sizes, and containing the latest control
modules and software.
IntelliPak™ II. Units covering the 90 through 150 ton capacity IntelliPak II cabinet sizes, and containing the latest control
modules and software.
LonTalk®. An open, device networking communications protocol for controls.This protocol is defined in ANSI approved
typical EIA/CEA-709.1-A-1999.
Low Ambient Compressor Lockout. A function which prevents compressor operation at low outdoor ambient
temperatures.
Low Vi Compressor Operation. Enhancements to the compressor control will be implemented on units with Low Vi
compressors installed, which will insure optimized compressor operation at all times.
Night SetBack (NSB). Applies to the control of the rooftop unit during unoccupied periods. Also refers to the NSB
panel, a communicating wall sensor with night setback capability.
Rapid Restart. Certain unit applications require override of the normal unit startup sequence after a power outage.
Target cooling requirements are established within a specified time to meet extreme high return air temperatures.
RT-SVP07D-EN 7
Commonly Used Acronyms
Reference Enthalpy. An outdoor enthalpy value, set at the HI, above which economizing will be disabled.
Remote Human Interface. (See Interprocessor Communication Module). A human interface module designed
to be mounted remotely from the unit. There are some functional differences between a unit mounted and a remote mounted human interface module.
Reset Amount Maximum. An adjustable parameter on the HI where the maximum amount of reset allowed is defined.
Reset End Temperature. The temperature at which the maximum reset amount will occur.
Reset Start Temperature. The temperature at which reset will begin.
Return Fan Control. . Return Fan Control is a feature which allows units to operate at a higher external or duct system
static pressure, or to reduce the load (horsepower requirement) on the supply fan motor.The fan is placed in the return air path.
Return Fan Plenum Pressure. The area between the Exhaust and Return Dampers and the outlet of the Return Fan
defines the return plenum. The absolute static pressure measured in this area is the Return Fan Plenum Pressure.
Return Plenum Pressure High Limit. This control feature, available on all return fan options, shuts the supply fan and
return fan off if the pressure in the return plenum exceeds a non-adjustable setpoint of 3.5 iwc.
Space Pressure. The pressure in the building as measured by the space pressure transducer, referenced to outside
(atmospheric) pressure.
Single Zone Variable Air Volume. The active discharge air setpoint, used for cooling, heating and supply fan speed
control, is based on the zone temperature load conditions.
Supply Air Pressure High Limit. A pressure limit to prevent unit casing and/or ductwork over pressurization.
Statitrac™. A control method to maintain proper space pressurization.
Supply Air Pressure. The pressure in inches-water-column (IWC) of the supply duct plenum or outlet as measured by
the supply air pressure transducer, referenced to local outside (atmospheric) pressure.
Supply Air Tempering. An active heating mode where the supply air temperature has dropped below a preset value,
usually due to cold outside air being brought in to provide building ventilation.
Supply Air Temperature Control Point. The revised value of SATemp Setpoint after supply air temperature reset has
been applied.
Supply Air Temperature Reset. A function that shifts the SATemp Setpoint an amount based on the value of another
parameter—typically ZoneTemp or Outdoor AirTemp.The purpose of this function is to lower unit capacity to better meet load requirements.
Target Setpoints. An internally calculated control point which is typically derived from other setpoints in combination
with specific unit operating conditions.
Variable Speed Compressor. An inverter driven compressor that has the capability to provide continuous-
incremental cooling capacity control.

UCM Control System

Trane Large Commercial Rooftop Units are controlled by a microelectronic control system that consists of a network of
modules and are referred to as Unit Control Modules (UCM).
The unit size, type VVDA (VAV w/ IGV/VFD), SZxx (SZVAV), RRXX (Rapid Restart), CVDA (VAV w/o IGV/VFD), CVZT (CV),
VVZT (SZVAV), heating functions, peripheral devices, options, exhaust capabilities, etc. determine the number and type
of modules that a particular rooftop unit may employ.
The UCM receives analog or binary inputs, then processes this information and supplies outputs in the form of
modulating voltages, contact closures, etc. to control damper actuators, fan motors, compressors, valves, electric heating coils and other electrical devices in the unit to maintain set comfort levels.
8 RT-SVP07D-EN
Commonly Used Acronyms
The UCM provides some equipment protection functions both directly and indirectly, such as duct pressure limits and
compressor lockouts. Listed below are the various modules that may be employed in a UCM control system.
Rooftop Module (1U1 IntelliPak II / 1U48 IntelliPak I)
(standard on all units)The RTM is the central processor of the system. It continuously receives information from the other unit modules, sensors, the remote control panel, and customer supplied relays. It then interprets this information and responds to cooling, heating, and ventilation requests by directing the other modules in the system to energize the proper unit components. It also directly initiates supply and exhaust fan operations, and economizer operation.
Compressor Module (IU3 IntelliPak II / 1U49 IntelliPak I)
(compressor control, head pressure control, evaporative condensing)The SCM/MCM module upon receiving a request for mechanical cooling staging from the RTM, energizes the appropriate compressors. It provides protection of the refrigerant circuit through feedback information it receives from various protection devices. It provides the necessary sensor interface to provide both air-cooled and water-cooled condenser head-pressure control.
Heat Module (1U6 IntelliPak II / 1U50 IntelliPak I)
(staged heat, modulating heat, air-handler chill water valve control)The HEAT module, directs the unit’s heater to stage up, down, or modulate to bring the controlled temperature to within the applicable heating setpoint. Chill water valve control is handled by the modulating output and is coordinated with the heat control to insure proper cooling and heating operation.
Exhaust/Comparative Enthalpy Module (1U5 IntelliPak II / 1U52 IntelliPak I)
(Statitrac building pressure control, comparative enthalpy)The ECEM receives data from the return air humidity sensor, the return air temperature sensor, and the return air space pressure transducer to control the economizer,exhaust fan and the exhaust dampers to maintain set space pressure.
Ventilation Control Module (7U14 IntelliPak II / 3U218 IntelliPak I)
(TRAQ dampers, DCV, outdoor air preheat)The VCM receives data from two velocity pressure sensors associated with front and backTRAQ assemblies to measure fresh air flow entering the unit.These measurements are converted to CFM and added to give total fresh air flow. This value can be used for monitoring purposes, to maintain flow to a minimum fresh air flow Setpoint, or to maintain appropriate CO2 levels in the controlled space using its space CO2 sensor input and the DCV feature.WithoutTRAQ assemblies installed theVCM can use DCV and the CO2 sensor input to control OA Damper minimum position to maintain CO2 levels in the space. A preheat control relay output is also provided on this module to maintain tempered outdoor air during ventilation using the VCM AuxiliaryTemperature input.The preheat unit is user­supplied.
Multi Purpose Module (1U9 IntelliPak II / 1U105 IntelliPak I)
(return fan, energy recovery wheel, evaporative condensing)The MPM supports the function of return plenum pressure control by providing inputs for measuring return plenum pressure, calibrating that reading, and providing an output to control the return fan speed (if variable speed configured) in response to control algorithm requests. EnergyWheel control along with bypass damper control, and interface to the saturated condensing pressure sensors for evaporative condensing head-pressure control.
Modulating Dehumidification Module (1U15 IntelliPak II / 1U107 IntelliPak I)
(dehumidification hot gas reheat)The MDM supports specific control inputs and outputs for modulating dehumidification control including modulating reheat and cooling valve control as well as the reheat pumpout coil relay output.
Generic Building Automation System Module (1U10 GBAS(0-5VDC) / 1U11 GBAS(0-10VDC) IntelliPak II) or (1U51 – GBAS(0-5VDC)/(0-10VDC) IntelliPak I)
(interface to third party BAS controls)The GBAS modules allows a non-Trane building control system to communicate with the unit and accepts external Setpoints in form of analog inputs (0 - 5V or 0 - 10V depending on the module selected) and a binary Input for demand limit. Five (5) binary outputs are available on 0 - 5 V modules. One (1) binary output and four (4) analog outputs are available on the 0 - 10 V modules. Refer to the “Field Installed Control Wiring” section of the
RT-SVP07D-EN 9
Commonly Used Acronyms
Unit Installation, Operation, Maintenance Manual (IOM) for the control wiring to the GBAS module and the various desired Setpoints with the corresponding DC voltage inputs.
Ventilation Override Module (1U8 IntelliPak II / 1U53 IntelliPak I)
(special ventilation unit operation)The VOM module provides the necessary I/O interface to third party customer controls and allows specific override operation of the unit’s air handling functions such as space pressurization, exhaust, purge, unit off, etc.
Variable Speed Module (1U123 IntelliPak I)
(variable speed compressor operation) The VSM module provides the necessary I/O interface to control variable speed compressor drives.
Interprocessor Communications Bridge (1U12 IntelliPak II / 1U55 IntelliPak I)
(communications isolation for remote human interface, external IPC wiring)The IPCB module expands communications from the unit UCM network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for this application should be; Switches 1 and 2 “Off”, Switch 3 “On”.This module is used to isolate the unit communications bus from the outside wiring, and any potential wiring faults that may occur.
BACnet®Communication Interface Module (1U66 IntelliPak II / 1U104 IntelliPak I)
(used on units withTrane ICS or 3rd party Building Automation Systems)The BCI module expands communications from the unit UCM network to aTraneTracer Summit, or a 3rd party building automation system that utilizes BACnet, and allows external Setpoint and configuration adjustment and monitoring of status and diagnostics.
Lontalk®Communication Interface Module (1U7 IntelliPak II / 1U65 IntelliPak I)
(used on units withTrane ICS or 3rd party Building Automation Systems)The LCI module expands communications from the unit UCM network to aTraneTracer Summit, or a 3rd party building automation system that utilizes LonTalk, and allows external Setpoint and configuration adjustment and monitoring of status and diagnostics.
Human Interface Module (Local = 1U2, Remote = 9U13 IntelliPak II) (1U65 IntelliPak I)
(standard on all units) The LHI and RHI (Local and Remote Human Interface) share a similar keypad which is illustrated, see Figure 1. Human Interface Module" on page 11. This device enables the customer, building owner, or contractor, to communicate to the Rooftop unit the necessary parameters for unit operation such as cooling and heating Setpoints, demand limiting, ventilation override modes, etc
The local (unit mounted) Human Interface and the Remote Human Interface Panel functions are identical, except for
Service mode which is not available on the Remote Human Interface Panel.
The local HI Module is located in the unit’s main control panel. A small door located in the unit’s control panel door allows
access to the HI Module’s keypad and display window.
There is a 2 line by 40 character LCD screen which provides status information for the various unit functions as well as
menus used to set or modify the operating parameters.There is a 16 key keypad adjacent to the LCD screen, which allows the operator to scroll through the various menus and make adjustments to the setpoints, etc.
The LCD screen has a backlight that makes the information easier to read.The light will go out if no keys are pressed for
30 minutes. If it goes out, simply press the Status key.
The information displayed in the LCD window will be top-level status information unless the operator initiates other
displays.
At power-up, the Human Interface LCD will display one of four initial screens illustrated in the “General Status” section.
10 RT-SVP07D-EN
Figure 1. Human Interface Module
Commonly Used Acronyms

Menu Keys

The six main menu keys illustrated in Figure 2. Human Interface Keypad,(Status, Setpoints, Setup, Configuration,
Diagnostics, and Service Mode) are used to bring up the various interactive menus where the user inputs and accesses
unit operating data. Pressing these keys will display the initial screen for the menu designated by the key’s name. The following information describes the keys and their functions when viewing the various menus.
Note:
1. If no key is pressed for 30 minutes while the LCD is displaying a menu screen, it will revert back to the unit operating status screen.
Status Key
Pressing the Status key causes the LCD to display the operating status screen; i.e. “On”, “Unit Stop”, “External Stop”,
“Emergency Stop”,“Service Mode”. Pressing the Next key allows the operator to scroll through the screens which provide
information such as air and refrigerant temperatures, humidity levels, fan operation, compressor operation, heater operation, economizer positioning, exhaust operation, as well as heating, cooling, and compressor lockout setpoints. Pressing the Status key while viewing any of the data screens will cause the LCD to go back to the operating status screen.
RT-SVP07D-EN 11
Commonly Used Acronyms
Setpoints Key
Pressing the Setpoints key will cause the LCD screen to display the first of the setpoint screens where the operator will designate default temperature and pressure setpoints. While scrolling through the setpoint screens, pressing this key again will cause the LCD to display the first setpoint screen.
Diagnostics Key
Pressing the Diagnostics key at any time will allow the operator to view any active unit diagnostics, or 20 of the most recently logged unit diagnostics. The LCD screen will display one of the diagnostic screens (depending on which diagnostic, if any, is present). If no key is pressed for 30 minutes while the screen is displaying diagnostic information, it will revert back to the operating status display.
Configuration Key
Pressing the Configuration key will cause the LCD screen to display the first of the configuration screens where the operator will designate unit configuration data such as unit type, capacity, system control, etc.
This information was programmed at the factory. Pressing the configuration key at any level in the configuration menu
will display the first configuration screen.
Note:
1. This key should be used if the unit’s configuration data is lost or new options are added in the field, and to view current configuration.
2. The Stop key must be pressed prior to making any changes under the Configuration menu.
Setup Key
Pressing the Setup key will cause the LCD screen to display screens where the operator will designate various operating parameters such as temperature and pressure ranges, limits, percentages, setpoint source selections, and sensor input definitions for the control of the rooftop unit’s various operating modes. Pressing the Setup key at any level in the setup menu will display the first setup screen.
Service Mode Key
Pressing the Service Mode key causes the LCD to display the first of the service test mode screens showing various unit components which may be turned on or off for the particular test being performed. Once the status of these components is designated, the LCD will display screens that allow the operator to designate the TEST START time delay for each test.

Data Manipulation Keys

The six data manipulation keys illustrated in Figure 2. Human Interface Keypad" on page 14, (Enter, Cancel, + (Plus), -
(Minus), Previous, and Next are used to modify the data within the screens (change values, move the cursor, confirm choices)
Enter Key
The Enter key will confirm the new values that were designated by pressing the + (Plus)or- (Minus) keys at all edit points.
When viewing status and diagnostics screens, it has no function.
Cancel Key
After changing data, at an editable screen, but before confirming it with the Enter key, pressing the Cancel key will return
the data to its previous value.This key shall also function to clear active diagnostics.
+ (Plus) Key
When viewing a setpoint screen, this key will increase the value of the displayed item per the units selected.When working
with a status menu, it will add the current status display to the CUSTOM MENU. When viewing setup, or service test screens, it will proceed forward though all the selections of that menu item, increase setpoints, toggle choices OFF to ON, DISABLED to ENABLED.
12 RT-SVP07D-EN

Unit Operation Keys

- (Minus) Key
When viewing a setpoint screen, this key will decrease the value of the displayed item per the units selected. When
working with a CUSTOM MENU, it will delete the current selected display. When viewing setup, or service test screens, it will proceed backwards though all the selections of that menu item, decrease setpoints, toggle choices ON to OFF, ENABLED to DISABLED.
Next Key
Pressing the Next key causes the LCD to scroll forward through the various displays for each menu. At displays with multiple edit points it moves the cursor forward from one edit point to another.
Previous Key
Pressing the Previous key causes the LCD to scroll backward through the various displays for each menu. At displays with multiple edit points, it moves the cursor backward from one edit point to another.
Unit Operation Keys
The four unit operation keys (Auto, Stop,Test Start, Custom) are used to control and monitor the unit in normal
operating mode, and also to initiate an active unit service test event.
Auto Key
Pressing the Auto key at any time will cause the display to go to the top level status display and, if the unit is shutdown, will cause the unit to begin operation in the appropriate mode no matter what level in the menu structure is currently being displayed. If the current display is an editable display, the Auto key will confirm the desired edit point similar to the Enter key.
Stop Key
Pressing the Stop key will cause the unit to transition to the stop state. If the current display is editable, pressing the Stop key will cancel the desired edit similar to the Cancel key. Prior to making any changes to the configuration menu screens, the Stop key must be pressed.
Test Start Key (Service Test Mode Start)
Pressing theTest Start key while viewing any screen in the Service Mode Menu will start the service test. Pressing this key while displaying any screen other than the Service Mode Menu will not start the service test, and has no other function.
Custom Key
Pressing the Custom key will change the display to the Custom Menu.This menu is simply a status menu that contains screens that the user monitors most frequently.The custom menu can only contain five status screens.To create the custom menu, press the Status key, followed by the Next key (this brings up the initial status screen). If you want to add this screen to the custom menu, press the + (Plus) key, if not, press the Next key again until a status screen appears that you would like to add to the custom menu. Pressing the + (Plus) key while viewing any of the various status screens will add that screen to the custom menu. Once the custom menu is programmed it can be accessed by pressing the Custom key.To remove a status screen from the custom menu, press the Custom key, then press the Next key until the status screen that you want to remove appears, then press the - (Minus) key.

General Status Display

Anytime the rooftop unit is powered up, or the Status,Auto,orStop keys are pressed, the unit mounted Human Interface
will display one of the following general status display screens.The operator will then be able to enter keystrokes which will allow him to navigate through a set of menus and submenus in order to provide/access various monitoring, setup,
RT-SVP07D-EN 13
General Status Display
and configuration information. The Human Interface will not display screens or parts of screens for which the unit is not configured.
Figure 2. Human Interface Keypad
14 RT-SVP07D-EN
General Status Display
Unit “Off” or “Stopped”
If at power up the unit is not running, the following display will appear on the Human Interface LCD screen. When this screen is being displayed, the only functional keys are the six menu keys (Status, Setpoints, Diagnostics, Setup, Configuration, and Service Mode), the Auto key, the Custom key, and the Stop key.
Stop by Network Supply Fan ON Initializing Diagnostics
Top Right Field:
Unit Off Unit Stopped External Stop Emergency Stop Stop by Network Unit Starting Service Mode Off
Bottom Left Field:
(blank) Shutdown Initializing Freeze Avoidance
Active
Supply Fan OFF Supply Fan ON
Bottom Right Field:
(blank) (Diagnostics)
Used With: Top Status Display
(Shown when unit is off or stopped)
Possible Values:
[see field descriptions at left]Top Left Field:
Unit “On”
If the unit has entered an operating state (running), the following display will appear on the Human Interface LCD screen.
When this screen is being displayed, the only functional keys are the six menu keys (Status, Setpoints, Diagnostics,
Setup, Configuration, and Service Mode), the Auto key, the Custom key, and the Stop key.
VVDA OA Flow 380.0 CCFM Supply Fan ON Occupied Cool 2 Diagnostics
Top Right Field:
Supply Fan ON Supply Fan OFF
CVZT VVDA CVDA
VVZT
Top Middle Field:
(blank) OA Flow 0 to 500 CCFM
Freeze Avoidance
Used With: Top Status Display
(Shown when unit is on)
Possible Values: [see field descriptions at left]Top Left Field:
Bottom Left Field:
(blank) Occupied Unoccupied MorningWU DaytimeWU Standby Shutdown Occupied TOV Initializing Tempering
Rapid Restart
RT-SVP07D-EN 15
Bottom Middle Field:
(blank) Heat 1 to 6 Cool 1 to 4 OA Dmpr 0 to 100 % Dehumid Purge Humidify
SA Fan 0 to 100%
Bottom Right Field:
(blank) Diagnostics
General Status Display
“Emergency Override” Active
If the unit has entered an Emergency Override mode of operation, one of the following displays will appear on the Human Interface LCD screen.
Ventilation Override Mode PRESSURIZE Diagnostics
Used With: LCI or BCI Options Top Left Field: Top Right Field: (blank) Bottom Left Field:
PRESSUREIZE DEPRESSURIZE PURGE SHUTDOWN FIRE
Bottom Right Field:
Diagnostics (Trouble Indicator) (blank)
“VOM” Active
If at power up the unit is running and has entered a Ventilation Override mode of operation, the following display will appear on the Human Interface LCD screen.
Ventilation Override Mode A Diagnostics
Used With: VOM Option Possible Values: Top Right Field: A, B, C, D, E, OFF Bottom Left Field:
(blank)
Bottom Right Field:
Diagnostics (Trouble Indicator) (blank)
“No Configuration” Condition
If at power up the unit has not been programmed with the necessary configuration data for normal unit operation, the following display will appear on the Human Interface LCD screen.When this screen is being displayed, the only functional keyistheConfiguration key.
Note: This screen will only appear when the RTM has been field replaced. Refer to the Configuration Menu section.
NO CONFIGURATION PRESENT
Used With: All Units
PRESS CONFIGURATION KEY
16 RT-SVP07D-EN
General Status Display
Factory Presets
The UCM controlled unit has many operating functions which are preset at the factory, but may be modified to meet the
unique requirements of each job. The following list in Table 2, identifies each of the unit’s adjustable functions and the value assigned to it. If these factory presets match the application’srequirements, simply press the Auto key at the Human Interface module to begin unit operation (after completing the Pre-Start and Start-Up procedures in the Installation, Operation, and Maintenance manual). If the application requires different settings, turn to the listed page beside the function, press the designated function menu key, then press and hold the Next or Previous key until its screen appears on the LCD. Once the proper screen appears, simply follow the programming instructions given below the applicable screen in this manual.
Note: Listed items availability is dependent on unit configuration.)
Table 2. Factory Presets List (Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
General Function
Unit Address (Comm3/Comm4only) 1
System Mode Auto ___________ Setup
Supply Fan Mode Auto ___________ Setup
Unit Start Delay 0 ___________ Setup
Single Zone VAV Econ Control Enabled ___________ Setup
Single Zone VAV Heat Control Disabled ___________ Setup
Daytime Warm-up Disabled ___________ Setup
Morning Warm-up Enabled ___________ Setup
Morning Warm-up type Cycling ___________ Setup
Supply Air Tempering Disabled ___________ Setup
Unoccupied Mechanical Cooling Enable ___________ Setup
Unoccupied Heating Enable ___________ Setup
Unoccupied Mechanical Cooling Enable ___________ Setup
Unoccupied Heating Enable ___________ Setup
Occupied Dehumidification Enable ___________ Setup
Unoccupied Dehumidification Enable ___________ Setup
Occupied Humidification Disable ___________ Setup
Unoccupied Humidification Disable ___________ Setup
Rapid Restart Economizer Control Disable ___________ Setup
VCM Preheat Output Disable ___________ Setup
Demand Limit Definition - Cooling None ___________ Setup
Demand Limit Definition - Heating None ___________ Setup
Compressor Lead/Lag Enable ___________ Setup
Evap Temperature Limit 35 F ___________ Setup
Coil Frost Cutout Temp 30 F ___________ Setup
Isolation Damper Interlock Disable ___________ Setup
___________ Setup
press...
Information Format
Display Text English ___________ Setup
Display Units English ___________ Setup
VAV Control
SA Temp Reset Cool None ___________ Setup
RT-SVP07D-EN 17
General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
Reset Cool Start Temp (Zone/OA) (72/90) ___________ Setup
Reset Cool End Temp (Zone/OA) (69/70) ___________ Setup
Reset Cool Max Amount 5 ___________ Setup
SA Temp Reset Heat None ___________ Setup
Reset Heat Start Temp (Zone/OA) (65/10) ___________ Setup
Reset Heat End Temp (Zone/OA) (68/60) ___________ Setup
Reset Heat Max Amount 10 ___________ Setup
VAV Box Stroke Time 6 Min ___________ Setup
Max Occ. IGV/VFD Command 100 % ___________ Setup
Economizer Control
Economizer Control Enable Type Drybulb ___________ Setup
Unoccupied Economizer Enable ___________ Setup
Head Pressure Control
Sump Drain Relay Control (on power loss) Drain ___________ Setup
Sump Purge Interval Time Disabled ___________ Setup
(a)
(a)
(a)
(120/60 sec.) ___________ Setup
(80/70 deg F) ___________ Setup
(90/80 deg F) ___________ Setup
Disabled ___________ Setup
Sump Purge Duration Time (IPak-I/IPak-II)
Sump Water Heater Setpoint 38 F ___________ Setup
Low Limit (Air-cooled/Water-cooled)
Upper Limit 120 deg F ___________ Setup
Temporary low limit suppression 20 deg F ___________ Setup
Efficiency check point 105 deg F ___________ Setup
Low amb. control point (Air-cooled/Water-cooled)
Alternate Refrigerant Type
(a)
press...
Sensor Source Selection
Daytime Warm-Up RTM Zone Temp ___________ Setup
Occupied Zone Control RTM Zone Temp ___________ Setup
Unoccupied Zone Control RTM Zone Temp ___________ Setup
Morning Warm-Up RTM Zone Temp ___________ Setup
Space Humidity Control RTM Space Humidity ___________ Setup
Dehumid OVRD Zone Temp RTM Zone Temp ___________ Setup
Zone Reset Function RTM Zone Temp ___________ Setup
Rapid Restart Function ECEM Return Temp ___________ Setup
Monitor RTM Zone Temp ___________ Setup
Outside Air Ventilation
Demand Control Ventilation Disable ___________ Setup
Active/Passive DCV Control Passive ___________ Setup
OA Flow Compensation Enabled ___________ Setup
OA Flow C02 Reset (IPak-INon-DCV) Disabled ___________ Setup
CO2 Start (IPak-I Non-DCV) 800 ___________ Setup
CO2 Max (IPak-I Non-DCV) 1000 ___________ Setup
18 RT-SVP07D-EN
General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
OA Flow Calibration Gain (Left) 1.0 ___________ Setup
OA Flow Calibration Offset (Left) 0 CFM ___________ Setup
OA Flow Calibration Gain (Right) 1.0 ___________ Setup
OA Flow Calibration Offset (Right) 0 CFM ___________ Setup
OA Normalization 100 CCFM ___________ Setup
OA Flow Calibration Data - Altitude: 0 Ft ___________ Setup
RTM Alarm Output Definition Any Active Diagnostic ___________ Setup
GBAS Input/Output Definitions
GBAS (0-5) Analog Input 1 Definitions Not Assigned ___________ Setup
GBAS (0-5) Analog Input 2 Definitions Not Assigned ___________ Setup
GBAS (0-5) Analog Input 3 Definitions Not Assigned ___________ Setup
GBAS (0-5) Analog Input 4 Definitions Not Assigned ___________ Setup
GBAS (0-5) Output 1 Definitions Not Assigned ___________ Setup
GBAS (0-5) Output 2 Definitions Not Assigned ___________ Setup
GBAS (0-5) Output 3 Definitions Not Assigned ___________ Setup
GBAS (0-5) Output 4 Definitions Not Assigned ___________ Setup
GBAS (0-5) Output 5 Definitions Not Assigned ___________ Setup
press...
GBAS (0-10) Analog Input 1 Definitions Not Assigned ___________ Setup
GBAS (0-10) Analog Input 2 Definitions Not Assigned ___________ Setup
GBAS (0-10) Analog Input 3 Definitions Not Assigned ___________ Setup
GBAS (0-10) Analog Input 4 Definitions Not Assigned ___________ Setup
GBAS (0-10) Output 1 Definitions Not Assigned ___________ Setup
GBAS (0-10) Output 2 Definitions Not Assigned ___________ Setup
GBAS (0-10) Output 3 Definitions Not Assigned ___________ Setup
GBAS (0-10) Output 4 Definitions Not Assigned ___________ Setup
GBAS (0-10) Output 5 Definitions Not Assigned ___________ Setup
Ventilation Override Definition See Definitions ___________ Setup
Temperature Input Offset for...
RTM Zone Temperature
RTM Aux Temperature
Outdoor Air Temperature
Heat Aux Temperature
Return Air Temperature
0 deg F ___________ Setup
0 deg F ___________ Setup
0 deg F ___________ Setup
0 deg F ___________ Setup
0 deg F ___________ Setup
Device Characteristics…
Outside Air Damper (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Direct ___________ Setup
30 sec ___________ Setup
10 VDC ___________ Setup
RT-SVP07D-EN 19
General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
Min Voltage
Supply Fan IGV/VFD (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Return Fan VFD (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Exhaust Damper/VFD (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
2 VDC ___________ Setup
Direct ___________ Setup
30/0 sec ___________ Setup
10 VDC ___________ Setup
2 VDC ___________ Setup
Direct ___________ Setup
60/0 sec ___________ Setup
10 VDC ___________ Setup
2 VDC ___________ Setup
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
0 VDC ___________ Setup
press...
Hydronic Heat (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Low Ambient Damper Ckt-1 (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Low Ambient Damper Ckt-2 (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Cond Fan VFD Ckt -1(if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
2 VDC ___________ Setup
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
2 VDC ___________ Setup
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
2 VDC ___________ Setup
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
0 VDC ___________ Setup
20 RT-SVP07D-EN
General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
Cond Fan VFD Ckt-2 (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
0 VDC ___________ Setup
press...
Modulating Gas Heat Actuator (if equipped)
Actuator Setup (Ipak-I/Ipak-II)
(a)
Max Stroke Time
Max Voltage
Min Voltage (Ipak-I/Ipac-II)
(a)
Outdoor Air Bypass Damper (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Exhaust Bypass Damper (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
Variable Speed Comp (if equipped)
Actuator Setup
Max Stroke Time
Max Voltage
Min Voltage
(Direct/Reverse) ___________ Setup
90 sec ___________ Setup
10 VDC ___________ Setup
(5 VDC/2 VDC) ___________ Setup
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
2 VDC ___________ Setup
Direct ___________ Setup
60 sec ___________ Setup
10 VDC ___________ Setup
2 VDC ___________ Setup
Direct ___________ Setup
30 sec ___________ Setup
10 VDC ___________ Setup
0 VDC ___________ Setup
Control Algorithm Tuning Parameters
(Partial)
(a)
VAV Cooling Control Gains
Proportional (w-VSC / wo-VSC)
Reset Time (w-VSC/wo-VSC)
(2.0%/F/3.3%/F) ___________ Setup
(100 Sec/50 Sec) ___________ Setup
Zone Control Occupied Heating Proportional Gain
IPak I Gas
IPak I Electric
IPak II Gas
IPak II Electric-90 kw
IPak II Electric -140 kw
IPak II Electric-265 kw
IPak II Electric-300 kw
30.0 deg F ___________ Setup
45.0 deg F ___________ Setup
30.0 deg F ___________ Setup
45.0 deg F ___________ Setup
60.0 deg F ___________ Setup
75.0 deg F ___________ Setup
75.0 deg F ___________ Setup
RT-SVP07D-EN 21
General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
CV Air Economizer Control Gains
Proportional
Reset Time
Rate Time
Bias
SZVAV Cooling Control Gains
Proportional
Reset Time
Rate Time
Bias
Zone Control Modulating Heat Gains
Proportional
Reset Time
Rate Time
Bias
SZVAV Heating Control Gains
Proportional
Reset Time
Rate Time
Bias
Rapid DX Interstage Timing
10.0 % F ___________ Setup
DISABLE ___________ Setup
0 Sec ___________ Setup
0 deg F ___________ Setup
6.0 % F ___________ Setup
1200 Sec ___________ Setup
0 Sec ___________ Setup
0 deg F ___________ Setup
10.0 % F ___________ Setup
DISABLE ___________ Setup
0 Sec ___________ Setup
0 deg F ___________ Setup
8.0% F ___________ Setup
1200 Sec ___________ Setup
0 Sec ___________ Setup
0 deg F ___________ Setup
30 Sec ___________ Setup
press...
Default Setpoints
Supply Air Cooling
Supply Air Heating
SA Cool Deadband 8.0 F ___________ Setpoints
SA Heat Deadband 4.0 F ___________ Setpoints
DWU Initiate 67 F ___________ Setpoints
DWU Terminate 71 F ___________ Setpoints
Occupied Zone Cooling 74 F ___________ Setpoints
Occupied Zone Heating 71 F ___________ Setpoints
Zone Derived Setpoint 4 F ___________ Setpoints
Unoccupied Zone Cooling 85 F ___________ Setpoints
Unoccupied Zone Heating 60 F ___________ Setpoints
Unoccupied Zone MWU 72 F ___________ Setpoints
Rapid Restart Critical Temp
Occ Dehumidification 60% ___________ Setpoints
Occ Dehumid Hysteresis Offset 5% ___________ Setpoints
Unocc Dehumidification 60% ___________ Setpoints
Unocc Dehumid Hysteresis Offset 5% ___________ Setpoints
Supply Air Reheat Setpoint 70 F ___________ Setpoints
Supply Air Reheat Deadband 4 F ___________ Setpoints
Maximum Reheat Valve Limit 85% ___________ Setpoints
Dehumid Ovrd High Zone Temp 75 F ___________ Setpoints
(VAV/SZVAV)
(VAV/SZVAV)
(a)
(a)
(a)
(55 F/50 F) ___________ Setpoints
(100 F/105 F) ___________ Setpoints
90 F ___________ Setpoints
22 RT-SVP07D-EN
General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
Dehumid Ovrd Low Zone Temp 68 F ___________ Setpoints
Cond Coil Purge Interval 90 Min ___________ Setpoints
Occ Humidification 30% ___________ Setpoints
Occ Humidification Hysteresis Offset 5% ___________ Setpoints
Unocc Humidification 30% ___________ Setpoints
Unocc Humidification Hysteresis Offset 5% ___________ Setpoints
Economizer Cooling Setpoint Suppression (CV) 3 F ___________ Setpoints
Reference Enthalpy 25 BTU/LB ___________ Setpoints
Economizer Drybulb Enable Stpt 75 F ___________ Setpoints
Supply Air Low Limit 50 F ___________ Setpoints
VCM Preheat Actuate Temp 35 F ___________ Setpoints
Design Min CO
DCV Min CO
Design Min OA Flow (DCV) 220 CCFM ___________ Setpoints
DCV Min OA Flow 67 CCFM ___________ Setpoints
DCV Min OA Flow Deadband 5 CCFM ___________ Setpoints
Min OA Flow w\ VCM Set per unit size ___________ Setpoints
Min OA Flow Deadband Set per unit size ___________ Setpoints
Design Min OA Damper Position (DCV) 15% ___________ Setpoints
DCV Min OA Damper Position 5% ___________ Setpoints
OA Damper Min Position (non-DCV) 15% ___________ Setpoints
OAD Min Position w/IGV/VFD at 0% 25% ___________ Setpoints
OAD Min Position w/IGV/VFD at 50% 20% ___________ Setpoints
OAD Min Position w/IGV/VFD at 100% 15% ___________ Setpoints
OAD Min Position (Default) 15% ___________ Setpoints
Supply Air Pressure 2.0 IWC ___________ Setpoints
Supply Air Pressure High Limit 4.0 IWC ___________ Setpoints
Supply Air Pressure Deadband 0.5 IWC ___________ Setpoints
Max Return Plenum Pressure 0.8 IWC ___________ Setpoints
Return Plenum Pressure Deadband 0.1 IWC ___________ Setpoints
Space Pressure - Setpoint 0.08 IWC ___________ Setpoints
Space Pressure - Deadband .04 IWC ___________ Setpoints
Space Pressure Low Limit -0.2 IWC ___________ Setpoints
Exhaust Enable Point 25% ___________ Setpoints
Exhaust Inhibit Point DISABLE ___________ Setpoints
Low Ambient Comp. Lockout (Standard Units) 50 F ___________ Setpoints
Low Ambient Comp. Lockout (Low Ambient Units) 0 F ___________ Setpoints
Standby Freeze Avoidance 0% ___________ Setpoints
Recovery Frost Avoidance Setpoint 27 F ___________ Setpoints
(DCV) 1000 PPM ___________ Setpoints
2
2
800 PPM ___________ Setpoints
press...
Setpoint Source Selection For...
Supply Air Temp Cooling Hi Default ___________ Setpoints
Supply Air Temp Heating Hi Default ___________ Setpoints
Occupied Zone Cooling Hi Default ___________ Setpoints
RT-SVP07D-EN 23
General Status Display
Table 2. Factory Presets List (continued)(Note: Listed Items availability is dependent on unit configuration.
To adjust
Adjustable Function Factory Preset Changed To
Occupied Zone Heating Hi Default ___________ Setpoints
Unoccupied Zone Cooling Hi Default ___________ Setpoints
Unoccupied Zone Heating Hi Default ___________ Setpoints
Morning Warm-Up Hi Default ___________ Setpoints
Economizer Dry Bulb Enable Hi Default ___________ Setpoints
Outside Damper Minimum Position Hi Default ___________ Setpoints
Occupied Dehumidification Hi Default ___________ Setpoints
Unoccupied Dehumidification Hi Default ___________ Setpoints
Supply Air Reheat Hi Default ___________ Setpoints
Occupied Humidity Hi Default ___________ Setpoints
Unoccupied Humidity Hi Default ___________ Setpoints
Minimum Outside Air Flow Rate Hi Default ___________ Setpoints
Supply Air Pressure Hi Default ___________ Setpoints
Space Pressure Hi Default ___________ Setpoints
(a) Field replacement of control modules requires proper human interface setup to insure unit performance
press...

Password Protected Screens

Some of the operating displays on the Human Interface LCD screens and require a password to change.The following screens display the various programming sections that require a password in order to view or to modify the preset operating parameters. The password for each screen is a different series of + (Plus)or- (Minus) key strokes in a predefined sequence. Shown below are the password protected screens, and the passwords for accessing them.
The following screens display the various programming sections that require a specific password to be entered by a
qualified operator in order to modify the operating parameters. The following screen will appear if the password is not entered within approximately 15 seconds.
Password Entry Time Limit Exceeded
Configuration is Password Protected Please Enter Password: __________
1. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.
2. Press the Enter key to confirm the password and enter the menu.
Ventilation Override Mode _______ Enter Password to Lock Definition:
24 RT-SVP07D-EN
1. Press the + or - keys in this sequence ( + - - + ) to lock each VOM Mode.
2. Press the Enter key to confirm the password and Lock the definitions.
Diagnostic Reset is Password Protected Please Enter Password: ____________
1. Press the + or - keys in this sequence ( - + + ) to access this restricted screen.
2. Press the Enter key to confirm the diagnostic reset.
Diagnostic Log is Password Protected Please Enter Password: __________
General Status Display
1. Press the + or - keys in this sequence ( - + + -) to access this restricted screen.
2. Press the Enter key to confirm clearing the diagnostic log.
Turning Parameters are Password Protected Please Enter Password: __________
1. Contact Clarksville Service for Password.

Navigating the Human Interface Screens

In the following sections the user will be presented with a number of screens and submenus that follow the selection of a main menu key entry (Status, Setpoints, Diagnostics, Setup, Configuration, Service Mode and Custom). When a submenu is presented, it may be accessed by pressing the Enter key or, skipped entirely by pressing the Next key. Upon entering a menu, or submenu, the user will navigate through the desired selections by pressing the Next and Previous keys.The most probable keystroke would be to press Next to cycle forward through the screens as shown in these sections, but pressing the Previous key may be desirable to review previous screens or to quickly navigate to the end of a menu.
Once the user has navigated to a desired selection, the + (Plus) and - (Minus) keys will be pressed to cycle through the selection range of the menu item.The range of each item selected is dependent upon the item and is listed for each screen in the following sections. For instance, if the user has selected a Configuration item typical choices displayed with each + (Plus)or- (Minus) keystroke may be Installed or Not Installed.IfaSetup menu were accessed a choice may be Enabled or Disabled.Temperature Setpoints will typically cycle through their range one degree at a time, and so on. Similar to pressing the Previous key above, pressing the - (Minus) key to decrement through the range may provide quick access to the desired value.
Once a change has been made to the desired menu item the user will press the Enter key to accept the change, or press the Cancel key to ignore the modification and return the displayed item to its original value.
RT-SVP07D-EN 25

STATUS Menu

The status menu is used to view various operating conditions such as temperatures, pressures and humidity levels. It is
also used to view unit component status such as fan, compressor, heater, and economizer operation, as well as setpoint status.
The screens shown in this section are for example only. Pressing the + (Plus) key while viewing any of the status display
screens will add that screen to the Custom menu. While viewing the Custom menu, a screen can be removed by pressing the – (Minus) key.
When a status screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general
operating status display. If this happens, press the Status key again to return to the status menu.The following are examples of status screens that may be viewed by pressing the Status key.
Note:
1. Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit.
2. The range for some selections depend upon a sensor connected to a control module. Normal ranges expected will be listed for each screen shown. If the sensor is operating outside its normal limits, or has failed, “+ERR” will appear if out of range high, and “-ERR” if it is out of range low.
Press the Status key to begin viewing the status screens.
TOP LEVEL STATUS SCREEN
VVDA OA Flow 350.0 CCFM Supply Fan ON Occupied Cool 4 Diagnostics
• Press Next/Previous keys to navigate.
GENERAL SYSTEM STATUS SUBMENU SCREENS
General System Status Submenu Press ENTER to View Data in this Submenu
• Press Next key to skip this Submenu.
Active Unit Control Source: LOCAL Active Cluster Member Role: STANDALONE
RTM Supply Fan Relay: OFF RTM Supply Airflow Proving: FLOW
Note: One of the three following screens will be shown based on supply air pressure options.
Used With: All Units
Used With: BAS Interface Installed Possible Values:
Source: LOCAL, BAS/NETWORK Role: STANDALONE, SLAVE, MASTER• Press Next/Previous keys to navigate.
Used With: All Units Possible Values:
Fan Relay: ON, OFF Airflow Proving: FLOW, NO FLOW• Press Next/Previous keys to navigate.
26 RT-SVP07D-EN
STATUS Menu
Supply Fan IGV/VFD Target: 30% Master’s Algorithm Command to All Units
OR
Supply Fan IGV/VFD Cmd Opening To 30 % Active Supply Air Pressure 2.0 IWC
“Limited To” when shown indicates an active override.
OR
Active Supply Air Pressure 2.0 IWC
• Press Next/Previous keys to navigate.
Note: One of the three following screens will be shown based on power exhaust options.
Exhaust Fan OFF
Used With: Clustered VVDA Units Possible Values: 0 to 100%
Used With: VVDA Units Possible Values:
Cmd: 0 to 100% Press: 0.0 to 7.9 IWC“Opening To” and ”Closing To” indicate direction.
Used With: CVDA/CVZT Units Possible Values: 0.0 to 7.9 IWC
Used With: Units w Power Exhaust w/o
Statitrac, w/o Return Fan
Possible Values: ON, OFF
OR
Exhaust Damper/VFD Target: 70 % Master’s Algorithm Command to All Units
OR
Exhaust Fan ON Space Pressure 0.00 IWC Exhaust Damper/VFD Opening To 32 %
“Opening To” and ”Closing To” indicates direction. “Limited To” when shown indicates an active override.
• Press Next/Previous keys to navigate.
Note: One of the four following screens will be shown based on heating type options.
Used With: Clustered, w/Statitrac, w/o Return Fan Units
Possible Values: 0 to 100%
Used With: Units w/Statitrac, w/o
Return Fan
Possible Values:
Fan: ON, OFF Pressure:
IPakI: -0.2 to 0.3 IWC IPakII: -0.67 to 0.67 IWC
Damper/VFD: 0 to 100%
RT-SVP07D-EN 27
STATUS Menu
Electric Heat: ENABLED Stage: 6 K11: ON K12: ON K1: ON
“ENABLED” indicates heat is available. “DISABLED” indicates heating is not allowed. “LIMITED” indicates heating is available at reduced capacity.
OR
Gas Heat: ENABLED Stage: 2 K11: ON K12: ON K1: ON
“ENABLED” indicates heat is available. “DISABLED” indicates heating is not allowed. “LIMITED” indicates heating is available at reduced capacity.
OR
Hydronic Heat: ENABLED Valve Position: Opening To: 100 %
“ENABLED” indicates heat is available. “DISABLED” indicates heating is not allowed. “LIMITED” indicates heating is available at reduced capacity. “Opening To” and ”Closing To” indicates direction.
Used With: Units w/Electric Heat Possible Values:
Electric Heat:
ENABLED, DISABLED By Setup, LIMITED By Demand Limit DISALBED By BAS/Network
Stage: 0,1,2,3,4,5,6 K*: ON, OFF
Used With: Units w/Staged Gas Heat Possible Values:
Gas Heat:
ENABLED, DISABLED By Setup, LIMITED By Demand Limit DISALBED By BAS/Network
Stage: 0,1,2 K*: ON, OFF
Used With: Units w/Hydronic Heat Possible Values:
Hydronic Heat:
ENABLED, DISABLED By Setup, LIMITED By Demand Limit DISABLED By Low Air Temp DISALBED By BAS/Network
Position: 0 to 100%
OR
Mod Gas Heat: ENABLED Valve Position: Opening To: 100 %
“ENABLED” indicates heat is available. “DISABLED” indicates heating is not allowed. “LIMITED” indicates heating is available at reduced capacity. “Opening To” and ”Closing To” indicates direction.
• Press Next/Previous keys to navigate.
28 RT-SVP07D-EN
Used With: Units w/Mod Gas Heat Possible Values:
Mod Gas Heat:
ENABLED, DISABLED By Setup, LIMITED By Demand Limit DISABLED By Low Air Temp DISALBED By BAS/Network
Position: 0 to 100%
STATUS Menu
Chilled Water: ENABLED Valve Position: Opening To 100 %
“ENABLED” indicates cooling is available. “DISABLED” indicates cooling is not allowed. “LIMITED” indicates cooling is available at reduced capacity. “Opening To” and ”Closing To” indicates direction.
• Press Next/Previous keys to navigate.
Dehumidification Status: DISABLED by Comfort Control Override is Active
Table 3. Dehumidification Lockout Sources
Value Displayed in Bottom Field Disable Conditions
Used With: Air Handler Units w/Chilled
Water
Possible Values:
Chilled Water:
ENABLED, DISABLED By Setup, LIMITED By Demand Limit DISABLED By Low Air Temp DISALBED By BAS/Network
Position: 0 to 100%
Used With: Units w/Dehumidification Top Line Possible Values: ENABLED,
DISABLED
Bottom line Possible Values:
When ENABLED is Shown:
(blank line)
When LOCKED is Shown:
[See “Table 3. Dehumidification
Lockout Sources” Below]
Disabled By Call for Cooling Demand Limit ........................ Compressors unavailable due to demand limit.
Disabled By Compressor Lockout Sources .......................... Required compressors are not available.
Disabled By Occ Dehumid Function Disable ....................... Occupied Dehumid. control is disabled.
Disabled By Dehumid Override Zone Temp High/Low .......... VVDA/CVDA critical zone temp is too high/low.
Disabled By OA Temperature Out Of Range ....................... Outdoor air temperature is out of range.
Disabled By Unocc Dehumid Function Disable..................... Unoccupied Dehumid. control is disabled.
Disabled By Comfort Control Override is Active................... Comfort cooling control has priority.
Disabled By Required Sensor Failure Condition ................... Sensor(s) for dehumid. control have failed.
Disabled By Sat Reheat Cond Temp Sensor Fail .................. Sensor for dehumid. control have failed.
Disabled By Reheat Head Pressure High Limit..................... Reheat circuit is experiencing high pressures.
Disabled By Condenser Coil Purge is Active ........................ Active purge mode temporary override.
Disabled By Comp Press Differential.................................. Excessive refrig. pressures across compressors.
• Press Next/Previous keys to navigate.
Humidification Status: ENABLED Humidification is Active
• Press Next/Previous keys to navigate.
Used With: Units w/Humidification Top Right Field: ENABLED, DISABLED Bottom Field:
The following shown when DISABLED:
by Occ Humidification Function Disable by Unocc Humid Function Disable
The following shown when ENABLED:
Humidification is Inactive Humidification is Active
RT-SVP07D-EN 29
STATUS Menu
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
COMPRESSOR STATUS SUBMENU SCREENS
Compressor Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Note: Combinations of the following screens will be shown based on unit cooling capacity option.
Compressor Relay K10 Locked Disabled By Compressor Protection (MORE)
Note: There will be 2 screens shown for this configuration, one screen for K10 and one for K11.
• Press Next/Previous keys to navigate.
OR
Compressor Relay K11 Locked Disabled By Compressor Protection (MORE)
Note: There will be 4 screens shown for this configuration, one for K11, one for K12*, one for K3, and one for K4*. See the following replacement screen for K12 when a variable speed compressor is installed on 40-70 ton units. K12 and K4 will show either Enabled or Activated by Compressor Protection when the compressor is ON.
Important:
*See the following replacement screen for K12 when a variable
speed compressor is installed on 40-70 ton units.
*K12 and K4 will show either Enabled, or Activated by Compressor Protection, when the compressor is ON.
Used With: Units w/DX Cooling
Used With: IPakI 20-30Ton DX Cooling Possible Values: Compressor Relay:
K10: 1 K11: 2
Top Right Field:
ON, OFF, LOCKED
Bottom Field:
When ON or OFF is Shown: ENABLED When LOCKED is Shown:
[See “Table 4. Compressor Lockout
Sources" on page 32”]
Used With: IPakI 40-130Ton DX Cooling Possible Values: Compressor Relay:
K11: 1 K12: 2 K3: 3 K4: 4
Top Right Field:
ON, OFF, LOCKED
Bottom Field:
When ON or OFF is Shown: ENABLED When LOCKED is Shown:
[See “Table 4. Compressor Lockout
Sources" on page 32”]
st
Compressor
nd
Compressor
st
Compressor
nd
Compressor
rd
Compressor
th
Compressor
• Press Next/Previous keys to navigate.
30 RT-SVP07D-EN
STATUS Menu
Capacity of Variable Speed Comp: 0% Disabled By Compressor Protection (MORE)
Notes:
This screen replaces K12 if a variable speed compressor is installed.
*Applied Design Capacity is the maximum cooling capacity of the
variable speed compressor for this unit’s tonnage design.
• Press Next/Previous keys to navigate.
OR
Ckt 1 Compr Relay K11: OFF Enabled
Notes:
There will be 2 screens shown for the configuration, one for K11and
one for K12.
*K12 will show either Enabled or Activated by Compressor Protection when the compressor is ON.
• Press Next/Previous keys to navigate.
Used With: IPakI 40-70 Ton DX Cooling
Configured w/Variable Speed Compressor
Possible Values: % of Applied Design Capacity*
Top Right Field: 0–100% Bottom Field:
During Normal control: [blank] When VSC is locked: [See “Table 4.
Compressor Lockout Sources" on page
32”]
Used With: IPakII DX Cooling Possible Values: Compressor Relay:
K11: 1 K12: 2
Top Right Field:
ON, OFF, LOCKED
Bottom Field:
When ON or OFF is Shown: ENABLED When LOCKED is Shown:
[See “Table 4. Compressor Lockout
Sources” Below]
st
Compressor
nd
Compressor
Ckt 2 Compr Relay K3: ON Enabled
There will be 2 screens shown for the configuration, one for K3 and one for K4.
K4 will show either Enabled or Activated by Compressor Protection when the compressor is ON.
Used With: IPakII DX Cooling Possible Values: Possible Values: Compressor Relay:
Top Right Field:
Bottom Field:
When ON or OFF is Shown: ENABLED When LOCKED is Shown:
rd
K3: 3 K4: 4
ON, OFF, LOCKED
[See “Table 4. Compressor Lockout
Sources” Below]
Compressor
th
Compressor
RT-SVP07D-EN 31
STATUS Menu
Table 4. Compressor Lockout Sources
Value Displayed in Bottom Field
Disabled By Compressor Protection................... Compressor proving input did not close.
Disabled By Contactor/Drive Failure.................. Compressor proving input stuck closed.
Disabled By Low Pressure Cutout ..................... Low pressure cutout input to MCM.
Disabled By Bad Cond Temp Sensor .................. Temp sensor is out of range.
Disabled By Demand Limit............................... From GBAS or BAS/Network.
Disabled By Frost Protection ............................ Leaving evap temp. < coil frost setpoint.
Disabled By BAS/Network Lockout .................... BAS demand or capacity limited.
Disabled By Minimum Off Time......................... 3 minutes.
Disabled By Low Ambient Lockout .................... Ambient temp. < Low Ambient Lockout Stpt.
Disabled By Ventilation Override....................... Source is VOM input A-E, or BAS/Network.
Disabled By LPC Delay .................................... 3 minutes.
Disabled By Water Flow Status......................... Evap. condenser water flow failure.
Disabled By Cond Coil Purge Request ................ Dehumidification coil purge mode.
Disabled By Sump Temp Sensor Fail.................. Evap. condenser sump water temperature.
Disabled By Low Refrig Charge......................... Evap. temp. difference exceeded for 10 min.
Disabled By Ckt ............................................. Evap Low Limit Entering evaporator temp. is excessively low.
Disabled by Reheat Ckt Evap Low Limit ............. Entering evaporator temp. is excessively low.
Disabled By Evap Temp Sensor Fail ................... Entering or leaving temp. sensor(s) failed.
Disabled by Comp Press Differential.................. Excessive refrig. pressures across compressors.
Disabled By Sump Min Level Sensor Fail ............ Evap. condenser min level switch failed.
Disabled By Sump Pump Failure ....................... Evap. condenser pump proving failed.
Disabled By Sump Min Level Control ................. Evap. condenser water level marginal.
Activated By Compressor Protection.................. Comps on for refrigerant management
Lockout Conditions
• Press Next/Previous keys to navigate.
Circuit 1 Evap Diff: 5.0°F Enter Evap: 48.5°F Leave Evap: 53.5°F
"Evap Diff:" and associated value not displayed if:
1. circuit is inactive, or
2. for first ten minutes of circuit operation, or
3. HGBP is installed
"Enter Evap:" and associated value not displayed if:
1. HGBP is installed
• Press Next/Previous keys to navigate.
Circuit 1 Saturated Condensing Temp: 100.0°F
• Press Next/Previous keys to navigate.
Used With: DX Cooling Possible Values:
Evap Diff: 0.0 to 200.0ºF Enter Evap: -40.0 to 200.0ºF Leave Evap: -40 to 200.0ºF
Used With: DX Cooling. Possible Values:
Temp: -40.0 to 200.0ºF
32 RT-SVP07D-EN
STATUS Menu
Circuit 2 Evap Diff: 12.0°F Enter Evap: 40.0°F Leave Evap: 52.0°F
"Evap Diff:" and associated value not displayed if:
1. circuit is inactive, or
2. for first ten minutes of circuit operation, or
3. HGBP is installed
"Enter Evap:" and associated value not displayed if:
1. HGBP is installed
• Press Next/Previous keys to navigate.
Circuit 2 Saturated Condensing Temp: 97.0°F
• Press the Next key to navigate forward.
Circuit 1 Cond Fan Staging K1: ON K2: ON Stage 4
“K2:” status not displayed, and maximum stage is 1, on water­cooled condenser units.
• Press Next/Previous keys to navigate.
Used With: DX Cooling > 40Ton Possible Values:
Evap Diff: 0.0 to 200.0ºF Enter Evap: -40.0 to 200.0ºF Leave Evap: -40 to 200.0ºF
Used With: DX Cooling > 40Ton Possible Values:
Temp: -40.0 to 200.0ºF
Used With: DX Cooling Possible Values:
K1: ON, OFF; K2: ON, OFF
Bottom Right Field:
OFF Stage 1 Stage 2 Stage 3 Stage 4
Circuit 2 Cond Fan Staging K5: ON K6: ON Stage 4
“K6:” status not displayed and maximum stage is 1 on water­cooled condenser units.
• Press Next/Previous keys to navigate.
Condenser Fan Speed: Circuit 1: 100% Circuit 2: 100%
“Circuit 2:” only shown for units
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 33
> 40Tons.
Used With: DX Cooling > 40Ton Possible Values:
K5: ON, OFF; K6: ON, OFF
Bottom Right Field:
OFF Stage 1 Stage 2 Stage 3 Stage 4
Used With: DX Cooling w/Low Ambient Option or Water-Cooled Condensers
Possible Values:
Circuit 1: 0 to 100% Circuit 2: 0 to 100%
STATUS Menu
Condenser Sump Water Temp: 73.1°F Condenser Sump Heater Relay: OFF
“Cond Sump Heater Relay” only shown if Sump Heater installed.
• Press Next/Previous keys to navigate.
Condenser Sump Pump Relay Command: ON Condenser Sump Pump Proving: FLOW
• Press Next/Previous keys to navigate.
Condenser Sump Fill Relay: OFF Condenser Sump Fill Valve: OPEN
• Press Next/Previous keys to navigate.
Condenser Sump Drain Relay: ON Condenser Sump Drain Valve: CLOSED
“Relay” and “Valve” states are configurable based on the need to hold water in the sump or drain it on power loss. See the IOM, and
Table 7: Sump Drain Valve States" on page 110 in Service Test
section for further information.
Used With: DX Cooling w/Water-Cooled Condensers
Possible Values:
Temp: 0.0 to 200.0ºF Relay: ON, OFF
Used With: DX Cooling w/Water-Cooled Condensers
Possible Values:
Relay: ON, OFF Proving: FLOW, NO FLOW
Used With: DX Cooling w/Water-Cooled Condensers
Possible Values:
Relay: ON, OFF Valve: CLOSED, OPEN
Used With: DX Cooling w/Water-Cooled Condensers
Possible Values:
Sump Drain Relay: ON, OFF Sump Drain Valve: CLOSED, OPEN
• Press Next/Previous keys to navigate.
Cond Sump Water Level Max Input: OPEN Cond Sump Water Level Min Input: CLOSED
• Press Next/Previous keys to navigate.
External Sump Drain Request: INACTIVE
• Press Next/Previous keys to navigate.
Reheat Coil Pumpout Relay: OFF Reheat Coil Pumpout Valve: CLOSED
• Press Next/Previous keys to navigate.
34 RT-SVP07D-EN
Used With: DX Cooling w/Water-Cooled Condensers
Possible Values:
Max Input: CLOSED, OPEN Min Input: CLOSED, OPEN
Used With: DX Cooling w/Water-Cooled Condensers
Possible Values: ACTIVE, INACTIVE
Used With: DX Cooling w/
Dehumidification
Possible Values:
Relay: ON, OFF Valve: CLOSED, OPEN
STATUS Menu
Dehumid Reheat Valve Position: 0% Dehumid Cooling Valve Position: 100%
• Press Next/Previous keys to navigate.
Active Outside Air Temperature 70.0°F Low Ambient Comp Lockout Temp: 50°F
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
ECONOMIZER STATUS SUBMENU SCREENS
Used With: DX Cooling w/ Dehumidification
Possible Values:
Reheat Valve: 0 to Max Reheat Valve Position Setpoint (see Setpoints Menu)
Cooling Valve: 10 to 100%
Used With: DX Cooling Possible Values:
Active Outside Air Temp: -40 to
200.0ºF Lockout Temp: -20 to 80ºF Default(s):
Standard: 50ºF Low-Amb. w/Hot Gas Bypass: 0ºF Low-Amb. w/o Hot Gas Bypass: 10ºF
Economizer Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Air Economizing: ENABLED Outside Air Damper Pos: Closing to 10%
Air Economizing: LIMITED By SA Low Limit Outside Air Damper Pos: 30%
“Opening to” and “Closing to” indicates direction. “LIMITED By SA Low Limit” indicates economizer sub-cooling
prevention is activated and the OA Damper is limited.
• Press Next/Previous keys to navigate.
Used With: Units w/Economizer
Used With: Units w/Economizer Possible Values:
Economizing: ENABLED/DISABLED Damper Pos: 0 to 100%or
RT-SVP07D-EN 35
STATUS Menu
Active Outside Air Enthalpy 29.5 BTU/LB ECEM Return Air Enthalpy 34.0 BTU/LB
Energy Recovery is installed.
• Press Next/Previous keys to navigate.
Active Outside Air Temperature 86.0°F ECEM Return Air Temperature 78.0°F
Energy Recovery is installed.
• Press Next/Previous keys to navigate.
Active Outside Air Humidity 30 %RH ECEM Return Air Humidity 62 %RH
Energy Recovery is installed.
• Press Next/Previous keys to navigate.
Used With: Units w/Economizer Possible Values:
OA Enthalpy: 10 to 35 BTU/LB RA Enthalpy: 10 to 35 BTU/LB"Return Air Enthalpy" is displayed if Comparative Enthalpy or
Used With: Units w/Economizer Possible Values:
OA Temp: -40 to 200°F RA Temp: -40 to 200°F"Return Air Temperature” is displayed if Comparative Enthalpy or
Used With: Units w/Economizer Possible Values:
OA Humidity: 10 to 90% RA Humidity: 10 to 90%“Return Air Humidity” is displayed if Comparative Enthalpy or
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
OUTSIDE AIR VENTILATION STATUS SUBMENU SCREENS
Outside Air Ventilation Status Submenu Press ENTER to View Data in this Submenu
• Press the Next key to skip this Submenu.
Demand Control Ventilation is ENABLED Space CO2 Level: 600 PPM
is ENABLED
• Press Next/Previous keys to navigate.
Note: One of the three following screens will be shown based on fresh air measurement and DCV options.
Used With: Units w/Fresh Air Options
Used With: All Units Possible Values:
DCV: ENABLED, DISABLED CO
Level: 50 to 2200 PPM"Space CO2 Level” is shown only if “Demand Control Ventilation”
2
36 RT-SVP07D-EN
STATUS Menu
DCV Min OA Flow Target: 250.0 CCFM Deadband: 5.0 CCFM OA Flow 234.3 CCFM
OR
Active Min OA Flow Setpoint: 140.3 CCFM Deadband: 6.8 CCFM OA Flow 143.5 CCFM
OR
Active Min OA Flow Setpoint: 140.3 CCFM CO2 Level 1100 PPM OA Damper Pos: 99 %
• Press Next/Previous keys to navigate.
Used With: Fresh Air Measurement
(VCM) w/DCV and Demand Control Ventilation ENABLED
Possible Values:
Target: 0 to 650 CCFM Deadband: 5.0 to 200 CCFM OA Flow: 0 to 650 CCFM
Used With: Fresh Air Measurement (VCM) w/DCV and Demand Control Ventilation DISABLED
Possible Values:
Setpoint: 0 to 650 CCFM Deadband: 5.0 to 200 CCFM OA Flow: 0 to 650 CCFM
Used With: Fresh Air Measurement (VCM) w/o DCV and CO2 Reset ENABLED
Possible Values:
Setpoint: 0 to 650 CCFM CO2 Level: 50 to 2000 PPM OA Damper Pos: 0 to 650 CCFM
Outside Air Flow Total: 335.4 CCFM Left: 167.2 CCFM Right: 168.2 CCFM
• Press Next/Previous keys to navigate.
Outside Air Damper Target: 27 % Outside Air Damper Position: 24 %
• Press Next/Previous keys to navigate.
VCM Preheater Output Control: OFF VCM Module Aux Temp Input: 47.2 °F
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
Used With: Fresh Air Measurement
(VCM) w/DCV
Possible Values: 0 to 650 CCFM
Used With: Units w/Fresh Air Options Possible Values: 0 to 100%
Used With: Fresh Air Measurement
(VCM) w/DCV or OA Damper Min Position (VCM) w/DCV and Preheat ENABLED
Possible Values:
Output Control: ON, OFF Aux Temp Input: -40.0 to 200.0ºF
RT-SVP07D-EN 37
STATUS Menu
RETURN FAN STATUS SUBMENU SCREENS
Return Fan Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Return Fan Relay: ON Return Airflow Proving: ON
• Press Next/Previous keys to navigate.
Return Fan VFD Command: 45 % Return Plenum Pressure: 0.8 IWC
• Press Next/Previous keys to navigate.
Return Plenum Pressure Target: 0.8 IWC Return Fan VFD Pos: Opening to 45 %
“Limited to” indicates an active override.
Used With: Units w/Return Fan Option
Used With: Units w/Return Fan Option Possible Values: ON, OFF
Used With: Units w/Return Fan Option Possible Values:
Command: 0 to 100% Pressure: -0.7 to 3.5 IWCTop line shown only if Return Fan VFD is installed.
Used With: Units w/Return Fan Option Possible Values:
Target: -0.5 IWC, or 0.1 to 2.5 IWC VFD Pos: 0 to 100%“Opening to” and ”Closing to” indicates direction.
• Press Next/Previous keys to navigate.
Max Return Plenum Pressure Stp: 1.2 IWC High Limit: 3.5 IWC Deadband: 0.2 IWC
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
SINGLE ZONE VAV STATUS SUBMENU SCREENS
Single Zone VAV Control Status Submenu Press ENTER to View Data in this Section
• Press Next/Previous keys to navigate.
Used With: Units w/Return Fan Option Possible Values:
Pressure Stp: 0.1 to 2.5 IWC Deadband: 0.1 to 1.0 IWC High Limit: 3.5 IWC (non-adjustable)
Used With: Units w/SZVAV(VVZT) Option
38 RT-SVP07D-EN
STATUS Menu
Active SA Target High Limit: 123.0 °F Active SA Max Target Setpoint: 100.0 °F
The Target High Limit is a calculated value which corresponds to the Maximum Fan Speed during heating (see SA Target Setpoint on following screen). The Max Target Setpoint reflects the SA Heating Setpoint value and corresponds to the Minimum Fan Speed during heating.
• Press Next/Previous keys to navigate.
Active SA Target Setpoint: 74.0 °F Active SA Temperature: 73.9 °F
The SA Target Setpoint is a calculated discharge setpoint based on zone temperature conditions. Heating and Cooling is staged to maintain SA Temperature to this setpoint. The range is clamped on the high end to Max Target Setpoint (see previous screen) and to the low end to Min Target Setpoint (see next screen).
Press Next/Previous keys to navigate.
Active SA Min Target Setpoint: 50.0 °F Active SA Target Low Limit: 38.4 °F
The Target Low Limit is a calculated value which corresponds to the Maximum Fan Speed during cooling (see SA Target Setpoint on previous screen). The Min Target Setpoint reflects the SA Cooling Setpoint value and corresponds to the Minimum Fan Speed during cooling.
Press Next/Previous keys to navigate.
Used With: Units w/SZVAV(VVZT) Option
Possible Values:
High Limit: (calculated) Max Target: Equal to SA Cooling
Setpoint
Fan speed modulation in heating occurs when the Target Setpoint modulates between the Max Setpoint and High Limit Setpoint.
Used With: Units w/SZVAV(VVZT) Option
Possible Values:
SA Target: Max Target – Min Target SA Temp: See SA Temp status.
Used With: Units w/SZVAV(VVZT) Option
Possible Values:
MinTarget: Equal to SA Heating Setpoint
Low Limit: (calculated)
Fan speed modulation in cooling occurs when the Target Setpoint modulates between the Min Setpoint and Low Limit Setpoint.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
ENERGY RECOVERY STATUS SUBMENU SCREENS
Energy Recovery Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
RT-SVP07D-EN 39
Used With: Units w/Energy Recovery Option
STATUS Menu
Energy Wheel Relay: ON Energy Wheel Proving: ON
• Press Next/Previous keys to navigate.
Outside Air Bypass Damper Pos: 0% Exhaust Air Bypass Damper Pos: 15%
• Press Next/Previous keys to navigate.
Energy Wheel Frost Avoidance: INACTIVE Leaving Recovery Exhaust Temp: 45.0°F
• Press Next/Previous keys to navigate.
MPM Preheat Relay: OFF
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
Used With: Units w/Energy Recovery Option
Possible Values: ON, OFF
Used With: Units w/Energy Recovery
Option
Possible Values: 0 to 100%
Used With: Units w/Energy Recovery
Option
Possible Values:
Frost Avoidance: ACTIVE, INACTIVE; Exhaust Temp: -40.0 to 200.0ºF
Used With: Units w/Energy Recovery Option w/Preheat
Possible Values: ON, OFF
• Press Next/Previous keys to navigate.
CONTROLLING SETPOINT STATUS SUBMENU SCREENS
Controlling SETPOINT Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Active Supply Air Cooling STP From HI (KEYPAD) SETPOINT MENU Is 55°F
Used With: All Units
Used With: VVDA or CVDA Units Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 40 to 90ºF• Press Next/Previous keys to navigate.
40 RT-SVP07D-EN
STATUS Menu
Active Supply Air Heating STP From HI (KEYPAD) SETPOINT MENU Is 100°F
• Press Next/Previous keys to navigate.
Active Daytime Warmup Setpoints Initiate: 67 °F Terminate: 71 °F
Active Occupied Zone Cooling STP From HI (KEYPAD) SETPOINT MENU is 71°F
Used With: VVDA or CVDA Units w/ Hydronic Heat, Modulating Gas Heat, or IpakII w/Electric Heat
Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 40 to 180ºF
Used With: Units w/DWU ENABLED Possible Values:
Initiate: 50 to 87ºF Terminate: 53 to 90ºF• Press Next/Previous keys to navigate.
Used With: CVZT Units w/DX Cooling Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 52 to 90ºF• Press Next/Previous keys to navigate.
Active Occupied Zone Heating STP From HI (KEYPAD) SETPOINT MENU is 71°F
• Press Next/Previous keys to navigate.
Active Unoccupied Zone Cooling STP From HI (KEYPAD) SETPOINT MENU is 85°F
RT-SVP07D-EN 41
Used With: CVZT w/Heat, VV/CVDA w/ DWU or MWU Installed
Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 50 to 88ºF
Used With: All Units Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 52 to 90ºF• Press Next/Previous keys to navigate.
STATUS Menu
Active Unoccupied Zone Heating STP From HI (KEYPAD) SETPOINT MENU is 60°F
Active Morning Warmup Setpoint From HI (KEYPAD) SETPOINT MENU is 72°F
Active Rapid Restart Critical Stpt From HI (KEYPAD) SETPOINT MENU is 90°F
• Press Next/Previous keys to navigate.
Used With: Units w/Heat Installed Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 50 to 88ºF• Press Next/Previous keys to navigate.
Used With: Units w/MWU ENABLED Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 52 to 90ºF• Press Next/Previous keys to navigate.
Used With: Units w/Rapid Restart Possible Values:
HI (KEYPAD) SETPOINT MENU
Range: 75 to 95ºF
Active Occ Dehumidification Setpt From HI (KEYPAD) SETPOINT MENU is 60%
Active Unocc Dehumidification Setpt From HI (KEYPAD) SETPOINT MENU is 60%
42 RT-SVP07D-EN
Used With: Units w/Dehumid. Option Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 40 to 65%• Press Next/Previous keys to navigate.
Used With: Units w/Dehumid. Option Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 40 to 65%• Press Next/Previous keys to navigate.
STATUS Menu
Active Supply Air Reheat Setpoint From HI (KEYPAD) SETPOINT MENU is 70.0°F
Active Occ Humidification Setpt From HI (KEYPAD) SETPOINT MENU is 40%
Active Unocc Humidification Setpt From HI (KEYPAD) SETPOINT MENU is 20%
Used With: Units w/Dehumid. Option Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 60 to 80F• Press Next/Previous keys to navigate.
Used With: Units w/Humid. Option Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 20 to 50%• Press Next/Previous keys to navigate.
Used With: Units w/Humid. Option Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 20 to 50%• Press Next/Previous keys to navigate.
Active Econ DB Enable Setpoint From HI (KEYPAD) SETPOINT MENU is 75°F
Active OA Damper Min Position STP From HI (KEYPAD) SETPOINT MENU is 25%
• Press Next/Previous keys to navigate.
Used With: Units w/Economizer Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 40 to 90ºF• Press Next/Previous keys to navigate.
Used With: Units w/0-25% Motorized Damper, or Economizer and OA CFM Compensation Function DISABLED or OA Damper Min Position Setpoint Source Selection is Not “HI (KEYPAD) SETPOINT”
Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK
Range: 0 to 100%
RT-SVP07D-EN 43
STATUS Menu
Active Min OA Flow Setpoint From HI (KEYPAD) SETPOINT MENU is 34.2 CCFM
• Press Next/Previous keys to navigate.
Active Design Min OA Flow Setpoint From HI (KEYPAD) SETPOINT MENU is 34.2 CCFM
• Press Next/Previous keys to navigate.
Used With: Units w/Fresh Air
Measurement (VCM) w/o DCV Option Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK SETPOINT
Range: 0 to Max Unit Airflow
[See “Table 7. Max Unit Airflows" on page 91” in the Setpoints Section Below]
Used With: Units w/Fresh Air Measurement (VCM) w/DCV Option
Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK SETPOINT
Range: 0 to Max Unit Airflow
[See “Table 7. Max Unit Airflows" on page 91” in the Setpoints Section]
Active Min OA Flow Target From VCM Module is 120.5 CCFM
• Press Next/Previous keys to navigate.
Active Supply Air Pressure STP From HI (KEYPAD) SETPOINT MENU is 2.0 IWC
Active Supply Air Pressure Setpoints High Limit: 4.0 IWC Deadband: 0.5 IWC
• Press Next/Previous keys to navigate.
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV Option Possible Values:
VCM Module BAS/NETWORK
Range: 0 to Max Unit Airflow
[See “Table 7. Max Unit Airflows" on page 91” in the Setpoints Section]
Used With: VVDA Units Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK SETPOINT
Range: 0.7 to 5.1 IWC• Press Next/Previous keys to navigate.
Used With: VVDA or Units w/Supply Air Pressure Sensor Present
Possible Values:
High Limit: 1.2 to 4.7 IWC Deadband: 0.1 to 2.0 IWC
44 RT-SVP07D-EN
STATUS Menu
Active Space Pressure Setpoint From HI (KEYPAD) SETPOINT MENU is 0.08 IWC
Active Space Pressure Deadband 0.1 IWC
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
CONTROLLING SENSOR STATUS SUBMENU SCREENS
Used With: Units w/Statitrac Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10 VDC MODULE BAS/NETWORK SETPOINT
Range: -0.2 to 0.30 IWC• Press Next/Previous keys to navigate.
Used With: Units w/Statitrac Possible Values: 0.02 to 0.20 IWC
Controlling Sensor Status Submenu
Used With: All Units
Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Active Supply Air Temp Sensv Input From BAS/NETWORK is 50.0°F
Active Daytime WU Temp Sensor Input From RTM ZONE TEMP INPUT is 82.0°F
• Press Next/Previous keys to navigate.
Used With: All Units Possible Values:
RTM Supply Air Temp Input BAS/Network• Press Next/Previous keys to navigate.
Used With: Units w/DWU ENABLED Possible Values:
RTM ZONE TEMP INPUT NSB PANEL TEMP SENSOR INPUT RTM AUX TEMP INPUT HEAT MODULE AUX TEMP INPUT ECEM RETURN AIR TEMP INPUT BAS/
NETWORK SENSOR
Range: -40 to 200ºF
RT-SVP07D-EN 45
STATUS Menu
Active Occ Zone Temp Sensor Input From RTM ZONE TEMP INPUT is 75.0°F
• Press Next/Previous keys to navigate.
Active Unocc Zone Temp Sensor Input From RTM ZONE TEMP INPUT is 75.0°F
• Press Next/Previous keys to navigate.
Active Morning WU Temp Sensor Input From RTM ZONE TEMP INPUT is 82.0°F
• Press Next/Previous keys to navigate.
Active Space Humidity Sensor Input From RTM SPACE HUMIDITY INPUT is 55%
• Press Next/Previous keys to navigate.
Used With: CV or SZVAV Units Possible Values: [See “Possible Values:” Above]
Used With: All Units Possible Values: [See “Possible Values:” Above]
Used With: Units w/MWU ENABLED Possible Values: [See “Possible Values:” Above]
Used With: Units w/Dehumid. or Humid.
Option
Possible Values:
RTM SPACE HUMIDITY INPUT ECEM RA HUMIDITY INPUT BAS/NETWORK
Range: 10 to 90%
Active Rapid Restart Sensor Input From ECEM RETURN AIR TEMP INPUT is 82.0°F
• Press Next/Previous keys to navigate.
Active Space CO2 Sensor Input From VCM SPACE CO2 INPUT is 600 PPM
• Press Next/Previous keys to navigate.
Active Dehumid OVRD Temp Input From RTM ZONE TEMP INPUT is 73.5°F
Used With: Units w/Rapid Restart. Possible Values: [See “Possible Values:” Above]
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV, or CO Reset ENABLED
Possible Values:
VCM SPACE CO BAS/NETWORK
Range: 50 to 2000 PPM
Used With: Units w/Dehumid. Option Possible Values:
RTM ZONE TEMP INPUT NSB PANEL TEMP SENSOR INPUT RTM AUX TEMP INPUT HEAT MODULE AUX TEMP INPUT ECEM RETURN AIR TEMP INPUT BAS/NETWORK SENSOR
Range: -40 to 200ºF• Press Next/Previous keys to navigate.
INPUT
2
2
46 RT-SVP07D-EN
STATUS Menu
Active Zone Reset Temp Sensor Input From RTM ZONE TEMP INPUT is 82.0°F
• Press Next/Previous keys to navigate.
Active OA Temperature Sensor Input From RTM OUTSIDE AIR TEMP INPUT is 86.0°F
• Press Next/Previous keys to navigate.
Active Outside Air Humidity Input From OA HUMIDITY SENSOR INPUT is 30 %
Active Supply Air Press Input From RTM SA PRESSURE INPUT is 2.1 IWC
• Press Next/Previous keys to navigate.
Used With: All Units with Reset Select
not selected as None.
Possible Values: [See “Possible Values:” Above]
Used With: All Units Possible Values:
RTM OUTSIDE AIR TEMP INPUT BAS/ NETWORK
Range: -40 to 200ºF
Used With: Units w/Economizer Option Possible Values:
OA HUMIDITY SENSOR INPUT BAS/NETWORK SENSOR
Range: 10 to 90%• Press Next/Previous keys to navigate.
Used With: VVDA or Units w/Supply Air Pressure Sensor Present
Possible Values:
RTM SA PRESSURE INPUT BAS/NETWORK
Range: 0 to 7.9 IWC
Active Space Pressure Input From ECEM SPACE PRESSURE INPUT is 0.08 IWC
Temp Sensor Input Being Monitored: RTM ZONE TEMP INPUT is 82.0°F
RT-SVP07D-EN 47
Used With: Units w/Statitrac Option Possible Values:
ECEM SPACE PRESSURE INPUT BAS/NETWORK
Range: -0.67 to 0.67 IWC• Press Next/Previous keys to navigate.
Used With: All Units Possible Values:
RTM ZONE TEMP INPUT NSB PANEL TEMP SENSOR INPUT RTM AUX TEMP INPUT HEAT MODULE AUX TEMP INPUT ECEM RETURN AIR TEMP INPUT BAS/NETWORK SENSOR
Range: -40 to 200ºF• Press Next/Previous keys to navigate.
STATUS Menu
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
TEMPERATURE INPUT STATUS SUBMENU SCREENS
Temperature Input Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Temp Measured By Sensor Connected To RTM SUPPLY AIR TEMP INPUT 50.0°F
• Press Next/Previous keys to navigate.
Temp Measured By Sensor Connected To RTM ZONE TEMP INPUT 82.0°F
• Press Next/Previous keys to navigate.
Temp Measured By Sensor Connected To NSB PANEL TEMP SENSOR INPUT 79.5°F
• Press Next/Previous keys to navigate.
Temp Measured By Sensor Connected To RTM AUX TEMP INPUT 62.0°F
Used With: All Units
Used With: All Units
Used With: All Units
Used With: Units w/NSB Panel Installed
Used With: All Units
• Press Next/Previous keys to navigate.
Temp Measured By Sensor Connected To
Used With: All Units
RTM OUTSIDE AIR TEMP INPUT 86.0°F
• Press Next/Previous keys to navigate.
Temp Measured By Sensor Connected To
Used With: Units w/Heat Installed
HEAT MODULE AUX TEMP INPUT 82.0°F
• Press Next/Previous keys to navigate.
48 RT-SVP07D-EN
STATUS Menu
Temp Measured By Sensor Connected To ECEM RETURN AIR TEMP INPUT 78.0°F
• Press Next/Previous keys to navigate.
Temp Measured By Sensor Connected To VCM MODULE AUX TEMP INPUT 50.0°F
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
LOCAL HARDWIRED INPUT STATUS SUBMENU SCREENS
Local Hardwired Input Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
Used With: Units w/Comparative
Enthalpy Installed
Used With: Units w/VCM Module Installed
Used With: All Units
IntelliPak II Config Input: CLOSED Dehumidification Config Input: OPEN
• Press Next/Previous keys to navigate.
RTM Supply Airflow Proving: FLOW RTM Exhaust Airflow Proving: FLOW
“RTM Exhaust…” shown for Power Exhaust w/o Return Fan. “RTM Return…” shown for Power Exhaust w/ Return Fan.
• Press Next/Previous keys to navigate.
RTM Remote Min Position Pot Input 0 %
Note: If potentiometer input is out of range (> 350 ohms) this screen will not appear.
• Press Next/Previous keys to navigate.
RTM Supply Air Pressure Input 2.1 IWC
• Press Next/Previous keys to navigate.
Used With: All Units Possible Values: OPEN/CLOSED
Used With: All Units Possible Values: Flow, No Flow
Bottom Left Field:
RTM Exhaust Airflow Proving RTM Return Airflow Proving
Used With: Units w/Outside Air Damper and Minimum Position Source is RTM.
Possible Values: 0 to 100%
Used With: VVDA or Units w/Supply Air
Pressure is present. Possible Values: 0 to 5.0 IWC
RT-SVP07D-EN 49
STATUS Menu
RTM Outside Air Humidity 55 % ECEM Return Air Humidity 46 %
“OA Humidity” shown only if comparative enthalpy installed. “RA Humidity” shown only if comparative enthalpy installed, or
non-IpakII units with humidification control.
• Press Next/Previous keys to navigate.
RTM Space Humidity 10 %
• Press Next/Previous keys to navigate.
ECEM Space Pressure Input 0.08 IWC
• Press Next/Previous keys to navigate.
VCM Outside Air Flow Input 350.0 CCFM
• Press Next/Previous keys to navigate.
Used With: Units w/Economizer Option Possible Values: 10 to 90%
Used With: Units w/Dehumid. or Humid.
Option
Possible Values: 10 to 90%
Used With: Units w/Statitrac Option Possible Values: -0.67 to 0.67 IWC
Used With: Units w/Fresh Air
Measurement (VCM) Possible Values: 0 to Max Unit Air Flow [See “Table 7. Max Unit Airflows" on page
91” in the Setpoints Section]
VCM CO2 Level Input 1512 PPM
• Press Next/Previous keys to navigate.
MPM Return Plenum Pressure Input 0.0 IWC
• Press Next/Previous keys to navigate.
Compr Diff Pressure Control is Installed
• Press Next/Previous keys to navigate.
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV, or C02 Reset is ENABLED
Possible Values: 50 to 2000 PPM
Screen shown only if unit with Return Fan installed
Possible Values: -0.7 to 3.5 IWC
Used With: Units with high compressor
pressure differential control. Installed or [screen not shown] Possible Values: Installed or [screen
not shown]
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
50 RT-SVP07D-EN
GBAS (5VDC) MODULE STATUS SUBMENU SCREENS
STATUS Menu
GBAS (5VDC) Module Status Submenu Press ENTER to View Data in This Submenu
• Press the Next key to skip this Submenu.
GBAS 0-5VDC Module Input 1 0.00 VDC Assigned: Not Assigned
Note: There will be 4 screens shown for this configuration. The first screen will be for Input 1 setpoint assignment. The next screens will be identical and will show setpoint assignments for Input 2, Input 3, and Input 4.
• Press Next/Previous keys to navigate.
Used With: Units w/GBAS (5VDC)
Installed
Used With: Units w/GBAS (5VDC) Installed
Possible Values: Input: 0.0 to 5 VDC Bottom Right Field:
Not Assigned OCC ZONE COOLING SETPOINT UNOCC ZONE COOLING SETPOINT OCC ZONE HEATING SETPOINT UNOCC ZONE HEATING SETPOINT SUPPLY AIR COOLING SETPOINT SUPPLY AIR HEATING SETPOINT SPACE PRESSURE SETPOINT SA PRESSURE SETPOINT MIN OA FLOW SETPOINT MWU SETPOINT ECON DRY BULB ENABLE SETPOINT MINIMUM POSITION SETPOINT OCC DEHUMIDIFICATION SETPOINT UNOCC DEHUMIDIFICATION
SETPOINT SUPPLY AIR REHEAT SETPOINT OCC HUMIDIFICATION SETPOINT UNOCC HUMIDIFICATION SETPOINT
GBAS (0-5VDC) Demand Limit Input Status OPEN
• Press Next/Previous keys to navigate. Possible Values: OPEN, CLOSED
GBAS 0-5VDC Module Relay Output Status Output 1 OFF
RT-SVP07D-EN 51
Used With: Units w/GBAS (5VDC) Installed
Used With: Units w/GBAS (5VDC) Installed
STATUS Menu
Note: There will be 5 screens shown for this configuration. The first
screen shows the relay status for Output 1 and indicates the associated Alarm Diagnostic has tripped. The next screens are identical and will show Output 2, Output 3, Output 4 and Output 5 relay status.
• Press Next/Previous keys to navigate.
GBAS(5VDC) Hardware Configuration The Value Returned From This Input: XXX
• Press Next/Previous keys to navigate.
Possible Values: ON, OFF
Note: Please review the “Diagnostics Troubleshooting Chart” in the “DIAGNOSTICS Menu” section to see the list of diagnostics associated with each module. (Refer to the “Diagnostics Displayed” column for the specified module.)
Used With: Units w/GBAS (5VDC) Installed
Possible Values: 0-255
End of Submenu (Next) to enter Status
• Press Next/Previous keys to navigate.
GBAS (10VDC) MODULE STATUS SUBMENU SCREENS
GBAS (10VDC) Module Status Submenu Press ENTER to View Data in This Submenu
Used With: Units w/GBAS (10VDC) Installed
• Press the Next key to skip this Submenu.
GBAS (10VDC) Analog Input 1 0.00 VDC Assigned: NOT ASSIGNED
Note: There will be 4 screens shown for this configuration. The first screen will be for Input 1 setpoint assignment. The next screens will be identical and will show setpoint assignments for Input 2, Input 3, and Input 4.
• Press Next/Previous keys to navigate.
GBAS (0-10VDC) Demand Limit Input Status Open
• Press Next/Previous keys to navigate.
Used With: Units w/GBAS (10VDC)
Installed
Possible Values:
Input: 0.0 to 10.0 VDC
Bottom Right Field:
[See GBAS(5VDC) Above for Assignments]
Used With: Units w/GBAS (10VDC) Installed
Possible Values: Open, Closed
52 RT-SVP07D-EN
STATUS Menu
GBAS (0-10VDC) Binary Output 1 OFF Assigned: OUTPUT IS NOT ASSIGNED
• Press Next/Previous keys to navigate.
GBAS (10VDC) Analog Output 1 0.00 VDC Assigned: NOT ASSIGNED
Note: There will be 5 screens shown for this configuration. The first screen will be for Output 1 parameter assignment. The next screens will be identical and will show parameter assignments for Output 2, Output 3, Output 4 and Input 5.
• Press Next/Previous keys to navigate.
Used With: Units w/GBAS (10VDC)
Installed
Possible Values: Output: ON, OFF Bottom Right Field:
OUTPUT IS NOT ASSIGNED INDICATE ANY COMP IS RUNNING INDICATE UNIT AT MAX CAPACITY INDICATE SELECTED DIAG ALARMS
[See “Alarm Listings” in RTM Alarm Outputs Below]
Used With: Units w/GBAS (10VDC) Installed
Possible Values:
Output: 0.0 to 10.0 VDC
Bottom Right Field:
NOT ASSIGNED OUTSIDE AIR TEMPERATURE ACTIVE ZONE TEMPERATURE ACTIVE SUPPLY AIR TEMPERATURE ACTIVE SUPPLY AIR PRESSURE ACTIVE SPACE PRESSURE ACTIVE SPACE RELATIVE HUMIDITY ACTIVE OA RELATIVE HUMIDITY ACTIVE SPACE CO ACTIVE COOLING CAPACITY ACTIVE HEATING CAPACITY ACTIVE OA DAMPER POSITION ACTIVE OUTDOOR AIRFLOW
LEVEL
2
End of Submenu (NEXT) to Enter STATUS
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 53

SETUP Menu

After the unit is installed, the control modules must be programmed with certain setup information in order to operate
and function properly.The data necessary for unit operation will vary depending on certain factors such as unit size, type, and installed options.
The setup menu is used to input initial operating information such as control parameters, setpoint source selection, sensor
source selections, ventilation override definitions, functions enable/disable, text display (Language), units displayed (English or SI), unit diagnostic assignments, and system tuning parameters. When a setup screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the appropriate power-up display. If this happens, press the Setup key again to return to the setup menu.
Information that pertains to when the screens are shown, the possible values that may be designated, and the factory presets for these values is located to the right of each programmable screen.
Note:
1. Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit.
2. If a screen is not visible on the Unit Human Interface Module, refer to the “Used With” information listed to the right of each screen in this book.
Modifying Selections: Starting with the first setup screen program the necessary information by using the
appropriate keys to navigate (Next and Previous) and make changes (+ and -) to the selections. Once the selection has been changed to the desired value, the user has the following options to either Cancel or Accept the pending change:
To Cancel, press the Cancel key to remove the change, the display will revert to the original value.
To Accept, press the Enter key to confirm the new choice.
Press the Setup key to begin viewing or modifying the setup screens.
TOP LEVEL SETUP SCREEN
Display Text in: ENGLISH LANGUAGE Display Units Using: ENGLISH NOTATION
• Press Next/Previous keys to navigate.
GENERAL UNIT FUNCTIONS SETUP SUBMENU SCREENS
General Unit Functions Setup Submenu Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
Used With: All Units Factory Presets:
Text Language: ENGLISH Units Notation: ENGLISH
Possible Values:
Language: ENGLISH, FRENCH, SPANISH
Notation: ENGLISH, SI
Used With: All Units
54 RT-SVP07D-EN
SETUP Menu
If Remote Panel Mode Input Not Present: System Mode: AUTO Supply Fan Mode: AUTO
• Press Next/Previous keys to navigate.
Reduce Multi-Unit Startup Power Demand After Power-Up, Delay Unit Start 0 Sec
• Press Next/Previous keys to navigate.
Single Zone VAV Econ Control: ENABLED Single Zone VAV Heat Control: DISABLED
• Press Next/Previous keys to navigate.
Used With:
System Mode: All Units Supply Fan Mode: CV SZVAV
Factory Presets:
System: AUTO Supply Fan: AUTO
Possible Values:
System: OFF, AUTO Supply Fan: ON, AUTO
Used With: All units. Factory Presets: 0 Sec Possible Values: 0 to 255 Sec
Used With: SZVAV Units Factory Presets:
Econ: ENABLED Heat: DISABLED
Possible Values:
ENABLED, DISABLED
Daytime Warmup Function: ENABLED
• Press Next/Previous keys to navigate.
Morning Warmup Function: ENABLED Morning Warmup Type: FULL CAPACITY
• Press Next/Previous keys to navigate.
Supply Air Tempering Function: ENABLED Warm Up Outside Air Used For Ventilation
• Press Next/Previous keys to navigate.
Used With: VV/CVDA Units w/Heat
Installed
Factory Presets: ENABLED Possible Values: ENABLED, DISABLED
Used With: Units w/Heat Installed Factory Presets:
Function: ENABLED Type: CYCLING CAPACITY
Possible Values:
Function: ENABLED, DISABLED Type: FULL CAPACITY, CYCLING CAP.
Used With: VV/CVDA Units w/ Modulating Heat (w/Electric Heat if IPakII), or CVZT Units w/Staged Heat Installed.
Factory Preset: ENABLED Possible Values: ENABLED, DISABLED
RT-SVP07D-EN 55
SETUP Menu
Unocc Mech Cooling Function: ENABLED Unocc Heating Function: ENABLED
“Unocc Heating Function” only shown if unit has heat installed.
• Press Next/Previous keys to navigate.
Occupied Dehumid Function: ENABLED Unoccupied Dehumid Function: ENABLED
• Press Next/Previous keys to navigate.
Occ Humidification Function: DISABLED Unocc Humidification Function: DISABLED
• Press Next/Previous keys to navigate.
Rapid Restart Economizer Ctrl: DISABLED Compressors Used for Cooling Control:
• Press Next/Previous keys to navigate.
Used With: Units w/DX Cooling, or Air
Handler w/Chilled Water, and w/Heat Installed
Factory Presets: ENABLED Possible Values: ENABLED, DISABLED
Used With: Units w/Dehumidification Possible Values: ENABLED, DISABLED
Used With: Units w/Humidification Factory Presets: DISABLED Possible Values: ENABLED, DISABLED
Used With: Rapid Restart Units Factory Presets: DISABLED Possible Values: ENABLED, DISABLED
VCM Preheater Output Control: ENABLED Activate If Preheat Temp Below Setpoint
• Press Next/Previous keys to navigate.
Demand Limit Definition: Cooling: None Heating: None
“Heating” only shown if unit has heat installed.
A selection of “None” indicates the unit will not limit the cooling or heating capacity of the unit. A selection of “25%” indicates that 1 of the 4 compressors will be inhibited from operation.
• Press Next/Previous keys to navigate.
Used With: Units w/Fresh Air Measurement (VCM) Option
Factory Preset: DISABLED Possible Values: ENABLED, DISABLED
Used With: Units w/DX Cooling and/or
Heat, and GBAS(5VDC), GBAS(10VDC) or BAS/Network Installed
Factory Presets: None Possible Values:
Cooling: None, 25*, 50, 75*, 100% Heating: None, 50% or 100%
*allowed only w/DX Cooling
> 40Ton
56 RT-SVP07D-EN
SETUP Menu
Evap Temperature Limit. Shut Off Circuit if (Leaving - Entering) Exceeds: 35ºF
Note: On units with Dehumidification installed a non-adjustable Evap Temperature Limit of 40ºF is used for the Reheat Circuit only.
• Press Next/Previous keys to navigate.
Coil Frost Cutout Temperature. Shut off Compressors If Evap Temp Is Below: 30ºF
• Press Next/Previous keys to navigate.
Isolation Damper Interlock: ENABLED SA Proving Must Open Before Fan Start
If ENABLED, “SA Proving Must Open Before Fan Start” is shown. If DISABLED, the bottom line is blank.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
Used With: All Units Factory Preset: 35ºF Possible Values: 25 to 40ºF
Used With: Units w/DX Cooling Factory Preset: 30ºF Possible Values: 25 to 35ºF
Used With: All Units Factory Preset: DISABLED Possible Values: DISABLED, ENABLED
• Press Next/Previous keys to navigate.
VAV CONTROL FUNCTIONS SUBMENU SCREENS
VAV Control Functions Submenu Press ENTER to Review or Adjust
Press the Next key to skip this Submenu.
Supply Air Temp Reset type: Cooling: NONE Heating: NONE
“Heating” only shown if unit has heat installed.
• Press Next/Previous keys to navigate.
Used With: All Units
Used With: VV/CVDA Units w/Cooling
and Heat Installed
Factory Preset: NONE Possible Values: NONE, ZONE, OA
RT-SVP07D-EN 57
SETUP Menu
Supply Air Temp Zone Reset For Cooling: Start Temp: 72ºF End Temp: 69ºF
• Press Next/Previous keys to navigate.
Supply Air Temp OA Reset For Cooling: Start Temp: 90ºF End Temp: 70ºF
• Press Next/Previous keys to navigate.
Supply Air Temp Zone Reset For Cooling: Maximum Amount of Reset Applied: 5ºF
• Press Next/Previous keys to navigate.
Used With: Units w/SA Cooling Reset
Type Set to “ZONE”
Factory Presets:
Start Temp: 72ºF End Temp: 69ºF
Possible Values:
Start Temp: 51 to 90ºF End Temp: 50 to 89ºF
Used With: Units w/SA Cooling Reset Type Set to “OA”
Factory Presets:
Start Temp: 90ºF End Temp: 70ºF
Possible Values:
Start Temp: 1 to 95ºF End Temp: 0 to 94ºF
Used With: Units w/SA Cooling Reset Type Set to “ZONE”
Factory Presets: 5ºF Possible Values: 0 to 20ºF
Supply Air Temp OA Reset For Cooling: Maximum Amount of Reset Applied: 5ºF
• Press Next/Previous keys to navigate.
Supply Air Temp Zone Reset For Heating: Start Temp: 65ºF End Temp: 68ºF
• Press Next/Previous keys to navigate.
Supply Air Temp OA Reset For Heating: Start Temp: 10ºF End Temp: 60ºF
• Press Next/Previous keys to navigate.
Used With: Units w/SA Cooling Reset
Type Set to “OA”
Factory Presets: 5ºF Possible Values: 0 to 20ºF
Used With: Units w/SA Heating Reset
Type Set to “ZONE”
Factory Presets:
Start Temp: 65ºF End Temp: 68ºF
Possible Values:
Start Temp: 50 to 89ºF End Temp: 51 to 90ºF
Used With: Units w/SA Heating Reset Type Set to “OA”
Factory Presets:
Start Temp: 10ºF End Temp: 60ºF
Possible Values:
Start Temp: 0 to 94ºF End Temp: 1 to 95ºF
58 RT-SVP07D-EN
SETUP Menu
Supply Air Temp Zone Reset For Heating: Maximum Amount of Reset Applied: 10ºF
• Press Next/Previous keys to navigate.
Supply Air Temp OA Reset For Heating: Maximum Amount of Reset Applied: 10ºF
• Press Next/Previous keys to navigate.
VAV Box Max Stroke Time: 6 Min
• Press Next/Previous keys to navigate.
Max Occupied IGV/VFD Command: 100%
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
Used With: Units w/SA Heating Reset
Type Set to “ZONE”
Factory Presets: 10ºF Possible Values: 10 to 90ºF
Used With: Units w/SA Heating Reset
Type Set to “OA”
Factory Presets: 10ºF Possible Values: 10 to 90ºF
Used With: VVDA Units Factory Presets: 6 Min Possible Values: 0 to 10 Min
Used With: VVDA Factory Presets: 100% Possible Values: 0 to 100%
RT-SVP07D-EN 59
SETUP Menu
ECONOMIZER CONTROL FUNCTIONS SUBMENU SCREENS
Economizer Control Functions Submenu Press ENTER to Review or Adjust
• Press Next/Previous keys to navigate.
Economizer Ctrl Enable Type: REFERENCE When Comparative Enthalpy Not Available
• Press Next/Previous keys to navigate.
Unocc Air Economizer Function: ENABLED
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
HEAD PRESSURE CTRL SETUP SUBMENU SCREENS
Head Pressure Ctrl Setup Submenu Press ENTER to Review or Adjust
Used With: Units w/Economizer Option
Used With: Units w/Economizer Option Factory Presets: REFERENCE Possible Values: REFERENCE,
DRYBULB
Used With: Units w/Economizer Option Factory Presets: ENABLED Possible Values: ENABLED, DISABLED
Used With: Units w/DX Cooling
• Press the Next key to skip this Submenu.
Sump Drain Valve Relay Control is: DRAIN During Unit Power Loss Conditions
• Press Next/Previous keys to navigate.
Sump Water Purge Timers Interval: 3 Hrs. Duration 60 Sec
“Sump Purge Duration Timer” only shown if Interval Timer is not set to DISABLED.
• Press Next/Previous keys to navigate.
60 RT-SVP07D-EN
Used With: Units w/Water-Cooled Condensers Installed
Factory Preset: DRAIN Possible Values: HOLD, DRAIN
Used With: Units w/Water-Cooled
Condensers Installed Factory Preset:
Interval Timer: 3 Hrs Duration Timer: 30 Sec
Possible Values:
Interval Timer: 1 to 12 Hrs, DISABLED Duration Timer: 5 to 255 Sec
SETUP Menu
Sump Water Heater Setpoint: 38°F Low Sump Temp Activates Heater Output
• Press Next/Previous keys to navigate.
Cond Temp Control Band Lower Limit: 80°F Upper Limit: 120°F
• Press Next/Previous keys to navigate.
Cond Temp Control Band Temporary Low Limit Suppression: 10°F
• Press Next/Previous keys to navigate.
Cond Temp Efficiency Check Point: 105°F
• Press Next/Previous keys to navigate.
Used With: Units w/Water-Cooled
Condensers and Sump Heat Installed
Factory Preset: 38ºF Possible Values: 38 to 43ºF
Used With: Units w/DX Cooling Factory Presets:
Upper Limit: 120ºF Lower Limit: 80ºF
Possible Values:
Upper Limit: 110 to 130ºF Lower Limit: 70 to 90ºF
Used With: Units w/DX Cooling Factory Presets: 10ºF Possible Values: 0 to 20ºF
Used With: Units w/DX Cooling Factory Presets: 105ºF Possible Values: 95 to 115ºF
Cond Temp Low Ambient Control Point: 90°F
Low Ambient Dampers control condensing temperature to this value.
• Press Next/Previous keys to navigate.
Alternate Unit Refrigerant Type: ENABLED
Units w/R22 should have this set to ENABLED
• Press Next/Previous keys to navigate.
Used With: Units w/DX Cooling w/Low Ambient Option
Factory Presets: 90ºF Possible Values: 80 to 100ºF
Used With: Units w/DX Cooling Factory Presets: DISABLED Possible Values: ENABLED/DISABLED
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 61
SETUP Menu
SENSOR SOURCE SELECTIONS SUBMENU SCREENS
Sensor Source Selections Submenu Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
For Daytime Warmup Temp Crtl, Use sensor Connected to: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
For Unoccupied Zone Temp Ctrl, Use Sensor Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
Used With: All Units.
Used With: Units w/DWU ENABLED Factory Preset: RTM ZONE TEMP INPUT Possible Values:
RTM ZONE TEMP INPUT NSB PANEL TEMP SENSOR INPUT RTM AUX TEMP INPUT HEAT MODULE AUX TEMP INPUT ECEM RETURN AIR TEMP INPUT
Used With: All CV or SZVAV Unit, or VAV w/DWU Installed
Factory Preset: RTM ZONE TEMP INPUT Possible Values: [See “DWU Source Selection” Above]
For Unoccupied Zone Temp Ctrl, Use Sensor Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
For Morning Warmup Temp Ctrl, Use Sensor Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
For Space Humidity Control, Use Sensor Connected To: RTM SPACE HUMIDITY INPUT
• Press Next/Previous keys to navigate.
Used With: All Units Factory Preset: RTM ZONE TEMP INPUT Possible Values: [See “DWU Source Selection” Above]
Used With: Units w/MWU ENABLED Factory Preset: RTM ZONE TEMP INPUT Possible Values: [See “DWU Source Selection” Above]
Used With: Units w/Dehumidification or
Humidification Options
Factory Preset:
RTM SPACE HUMID INPUT
Possible Values:
RTM SPACE HUMIDITY INPUT ECEM RA HUMIDITY INPUT
62 RT-SVP07D-EN
SETUP Menu
For Dehumid OVRD Zone Temp, Use Sensor Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
For Zone Reset Function, Use Sensor Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
For Rapid Restart Function, Use Sensor Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
Monitor Specific Temp Input, Use Sensor Connected To: RTM ZONE TEMP INPUT
• Press Next/Previous keys to navigate.
Used With: Units w/Dehumid. Option Factory Preset: RTM ZONE TEMP INPUT Possible Values: [See “DWU Source Selection” Above]
Used With: All Units Factory Preset: RTM ZONE TEMP INPUT Possible Values: [See “DWU Source Selection” Above]
Used With: Units w/Rapid Restart Factory Preset: RTM ZONE TEMP INPUT Possible Values: [See “DWU Source Selection” Above]
Used With: All Units Factory Preset: RTM ZONE TEMP INPUT Possible Values: [See “DWU Source Selection” Above]
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
OUTSIDE AIR VENTILATION SETUP SUBMENU SCREENS
Outside Air Ventilation Setup Submenu
Used With: Units w/Fresh Air Option
Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
Demand Controlled Ventilation: ENABLED DCV Setpoint Modified By Space CO2 Level
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 63
Used With: Units w/ Fresh Air Measurement (VCM) w/DCV or OA Damper Min Position w/DCV Installed
Factory Preset: DISABLED Possible Values: ENABLED, DISABLED Bottom Field:
If ENABLED: “DCV Setpoint Modified
By Space CO
If DISABLED: (blank)
Level”
2
SETUP Menu
DCV Active Supply Fan Control: ENABLED Allow Supply Fan to Energize for DCV
• Press Next/Previous keys to navigate.
OA Flow Compensation Function: DISABLED Use fixed OA Damper Minimum Position
• Press Next/Previous keys to navigate.
OA Flow CO2 Reset Function: ENABLED
2
CO
Start: 800 PPM CO2 Max: 1000 PPM
Note: Bottom line will not be shown if function is DISABLED.
• Press Next/Previous keys to navigate.
Used With: CVZT or VVZT Units w/DCV
set to ENABLED.
Factory Preset: DISABLED Possible Values: DISABLED, ENABLED, Bottom Field:
If ENABLED: “Allow Supply Fan to Energize for DCV”
If DISABLED: (blank)
Used With: VVDA or VVZT Units w/ Economizer
Factory Preset: DISABLED Possible Values: ENABLED, DISABLED Bottom Field:
If ENABLED: “OA Damper Min Pos
Depends on IGV/VFD Pos”
If DISABLED: “Use Fixed OA Damper
Minimum Position”
Used With: IPak-I Units w/Fresh Air Measurement (VCM) w/o DCV Option
Factory Preset:
Function: DISABLED Start: 800, Max: 1000
Possible Values:
Function: ENABLED, DISABLED Start: 50 to 1900 Max: 150 to 2000
OA Flow Calibration Data (Left) Gain 1.0 Offset 0 CCFM
“Left” refers to the flow station on the left side of the unit when looking into the unit’s airstream.
• Press Next/Previous keys to navigate.
OA Flow Calibration Data (Right) Gain 1.0 Offset 0 CCFM
“Right” refers to the flow station on the right side of the unit when looking into the unit’s airstream.
• Press Next/Previous keys to navigate.
64 RT-SVP07D-EN
Used With: Units w/Fresh Air Measurement (VCM) w/DCV Option
Factory Preset: Gain 1.0, Offset 0 CCFM Possible Values:
Gain: 0.5 to 1.5 Offset: -25 to 25 CCFM
Used With: Units w/Fresh Air Measurement (VCM) w/DCV Option
Factory Preset: Gain 1.0, Offset 0 CCFM Possible Values:
Gain: 0.5 to 1.5 Offset: -25 to 25 CCFM
SETUP Menu
Maximum OA Flow at Design Conditions OA Normalization: 350 CCFM
• Press Next/Previous keys to navigate.
OA Flow Calibration Data Altitude: 0 Ft.
This correction factor is used to adjust airflow calculations due to density of air at different altitudes.
Table 5. Flow Calibration - Altitude Correction Factor C.F.
Feet Meters C.F. Feet Meters C.F.
0 0 1.00 5500 1650 0.91
500 150 0.99 6000 1800 0.90
1000 300 0.98 6500 2000 0.89
1500 450 0.97 7000 2150 0.88
2000 600 0.97 7500 2300 0.87
2500 750 0.96 8000 2450 0.86
3000 900 0.95 8500 2600 0.85
3500 1050 0.94 9000 2750 0.85
4000 1200 0.93 9500 2900 0.84
4500 1350 0.92 10000 3050 0.83
5000 1500 0.91
Used With: Units w/Return Fan and Fresh Air Measurement (VCM) w/DCV, Units w/Energy Recovery Wheel Option
Factory Preset: 1 CCFM Possible Values: 0 to Max Unit Airflow
[See “Max Unit Airflows” in Setpoints Section Below]
Used With: Units w/Return Fan and Fresh Air Measurement (VCM)
Factory Preset: 0 Ft (0 m) Possible Values:
[See “Table 5. Flow Calibration - Altitude
Correction Factor C.F.” for assignments
below.]
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 65
SETUP Menu

Emergency Override Definitions (with LCI or BCI module installed)

When an LCI or BCI module is installed, the user can initiate one of five (5) Emergency Override sequences that have the
following predefined unit operation via LonTalk or BACnet Communication:
PRESSURIZE
Supply Fan – On
Inlet Vanes - Open (if equipped)
Return Fan VFD – Min
Return Fan / Exhaust Damper - Off / Closed (if equipped)
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
DEPRESSURIZE
Supply Fan – Off
Inlet Vanes - Closed (if equipped)
Return Fan VFD – Max
Return Fan / Exhaust Damper - On / Open (if equipped)
OA Dampers – Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
PURGE
Supply Fan – On
Inlet Vanes - Open (if equipped)
Return Fan / Exhaust Damper - On / Open (if equipped)
Return Fan VFD – Max
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
SHUTDOWN
Supply Fan – Off
Inlet Vanes - Closed (if equipped)
Return Fan / Exhaust Damper - Off / Closed (if equipped)
Return Fan VFD – Min
OA Dampers – Closed
66 RT-SVP07D-EN
SETUP Menu
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied/Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)
FIRE
Supply Fan – Off
Inlet Vanes - Closed (if equipped)
Return Fan / Exhaust Damper - Off / Closed (if equipped)
Return Fan VFD – Min
OA Dampers – Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output - De-energized
VO Relay - Energized (with VOM module installed)
VCM Preheater State - Off (with VCM installed)

Ventilation Override Mode Definitions (with VOM installed)

Each of the five VOM modes have factory presets, that when initiated by a VOM contact closure, will accomplish five predefined operations (listed below). Any of the five sequences may be user-redefined by changing the factory presets at the unit mounted Human Interface or through Tracer.
Ventilation Override Mode A - (Unit Off)
Supply Fan – Off
Inlet Vanes / VFD - Closed / 0%
Return Fan VFD – Min
Return Fan / Exhaust Damper – Off / Closed (if equipped)
OA Dampers – Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Deenergized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode B - (Pressurize)
Supply Fan – On
Inlet Vanes / VFD - Open / 100%
Return Fan VFD – Min
Return Fan / Exhaust Damper - Off / Closed (if equipped)
OA Dampers – Open
Heat - All heat stages Off (staged gas & elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
RT-SVP07D-EN 67
SETUP Menu
Ventilation Override Mode C - (Exhaust)
Supply Fan – Off
Inlet Vanes - Closed (if equipped)
Return Fan / Exhaust Damper – On / Open (if equipped)
Return Fan VFD – Max
OA Dampers – Closed
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Deenergized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode D - (Purge)
Supply Fan – On
Inlet Vanes / VFD - Open / 100%
Return Fan VFD – Max
Return Fan / Exhaust Damper - On / Open (if equipped)
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.); Hydronic heat & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
Ventilation Override Mode E - (Purge with Duct Pressure Control)
Supply Fan – On
Return Fan VFD – Max
Inlet Vanes / VFD - Open/100% (Ctrl’d by SA Press control function, SA Press High Limit is disabled)
Return Fan / Exhaust Damper - On / Open (if equipped)
OA Dampers – Open
Heat - All heat stages Off (staged gas and elec.) Hydronic & Mod Gas Heat output at 0%.
Occupied / Unoccupied output – Energized
VO Relay – Energized
VCM Preheater State - Off (with VCM installed)
Note:
1. The five VOM modes A, B, C, D, E will have the factory defaults set to the above defined values.
2. ”OFF” - will appear in the Ventilation Override screen after all VOM binary inputs have been reset (opened).
68 RT-SVP07D-EN
VENTILATION OVERRIDE MENU SCREENS
Ventilation Override Definitions Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
SETUP Menu
Used With: Units w/VOM Installed
Ventilation Override Definition Mode A Supply Fan ON
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A Supply Fan IGV/VFD MIN
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A Exhaust Fan/Dampers ON/OPEN
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A Return Fan/Exhaust Dampers OFF/CLOSED
• Press the Next key to navigate forward.
Ventilation Override Definition Mode A Exhaust Fan ON
• Press Next/Previous keys to navigate.
Used With: Units w/VOM Installed Possible Values: ON, OFF
Used With: Units w/VOM Installed Possible Values: IN CONTROL, MIN, MAX
Used With: Units w/VOM and Power
Exhaust w/Statitrac
Possible Values: ON/OPEN, OFF/CLOSED
Used With: Units w/VOM and Return Fan Possible Values: OFF/CLOSED, ON/OPEN
Used With: Units w/VOM and Power
Exhaust w/o Statitrac Installed Possible Values: ON, OFF
Ventilation Override Definition Mode A Return Fan VFD Command Min
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A Outside Air Dampers OPEN
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A VAV Box Relay DEENERGIZED
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 69
Used With: Units w/VOM and Return Fan with Statitrac Installed
Possible Values: Return Fan VFD Command: MIN, MAX
Used With: Units w/VOM and Economizer Option
Possible Values: OPEN, CLOSED
Used With: Units w/VOM Installed Possible Values: ENERGIZED,
DEENERGIZED
SETUP Menu
Ventilation Override Definition Mode A Heat OFF
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A VCM Preheater State IN CONTROL
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A Ventilation Override Relay ENERGIZED
• Press Next/Previous keys to navigate.
Ventilation Override Definition Mode A Enter Password to Lock Definition:
Note: After locking a MODE (by entering the password), the displays for that MODE becomes "Reporting" only and the definition cannot be changed unless the Ventilation Override Module is replaced. If the password was entered, pressing the NEXT key will scroll through the previous screens to confirm the selected choices for each mode as follows:
Used With: Units w/VOM and Heat Installed
Possible Values: OFF, IN CONTROL
Used With: Units w/ and OA Preheater
Function Enabled
Possible Values: OFF, IN CONTROL
Used With: Units w/VOM Installed Possible Values: ENERGIZED,
DEENERGIZED
Used With: Units w/VOM Installed and Mode Not Locked
• Press Next/Previous keys to navigate.
Ventilation Override Mode A Is Locked Supply Fan ON
Note: This is “Reporting Only” display. After all of the “VOM A” entries have been viewed or modified, the following screen will be displayed:
• Press Next/Previous keys to navigate.
Ventilation Override Mode B Supply Fan OFF
Note: Follow the preceding steps, used in programming Mode "A", to program VOM Mode “B", "C", "D", and "E" if modifications are needed.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
Used With: Units w/VOM Mode Locked Factory Presets: See Definitions Above Possible Values: N/A
Used With: All Units Factory Presets: See Definitions Above Possible Values: ON, OFF
70 RT-SVP07D-EN
GBAS 0-5VDC MODULE I/O ASSIGNMENTS SCREENS
GBAS (5VDC) Module I/O Assignments Press ENTER to Review or Adjust
Press the Next key to skip this Submenu.
SETUP Menu
Used With: Units w/GBAS(5VDC) Installed
GBAS (5VDC) Analog Input 1 Assignment NOT ASSIGNED
Note: There are 3 additional screens associated with Input Assignments; “Analog Input 2”, “Analog Input 3”, and “Analog Input 4”. Press the Next key to proceed through the remaining assignments.
• Press Next/Previous keys to navigate.
GBAS (5VDC) Output 1 Alarm Assignments Press ENTER to Review or Adjust
Press the Next key to skip this Submenu.
Note: There are 4 additional screens associated with Alarm Output Assignments: “Alarm Output 2”, “Alarm Output 3”, “Alarm Output 4”, and “Alarm Output 5”. The process of assigning diagnostics to those outputs is identical to what is described here for “Alarm Output 1”.
If Enter was pressed, proceed to the following 3 screens.
Used With: Units w/GBAS(5VDC)
Installed.
Factory Presets: NOT ASSIGNED Possible Values:
NOT ASSIGNED OCC ZONE COOLING SETPOINT UNOCC ZONE COOLING SETPOINT OCC ZONE HEATING SETPOINT UNOCC ZONE HEATING SETPOINT SPACE STATIC PRESSURE SETPOINT SA STATIC PRESSURE SETPOINT MIN OA FLOW SETPOINT MORNING WARMUP SETPOINT ECON DRY BULB ENABLE SETPOINT MINIMUM POSITION SETPOINT OCC DEHUMID SETPOINT UNOCC DEHUMID SETPOINT SUPPLY AIR REHEAT SETPOINT OCC HUMIDIFICATION SETPOINT UNOCC HUMIDIFICATION SETPOINT
Used With: Units w/GBAS(5VDC) Installed Factory Presets:
Output 1 = Dirty Filters Output 2 = Compressor Trip Compressor Trip - Ckt 1 Compressor Trip - Ckt 2 Low Pressure Control Open Low Pressure Control Open - Ckt 1 Low Pressure Control Open - Ckt 2 Comp Contactor/Drive Fail Comp Contactor/Drive Fail - Ckt 1 Comp Contactor/Drive Fail - Ckt 2 Output 3 = Heat Fail Output 4 = Supply Fan Failure Output 5 = Any Active Diagnostic
Possible Values: Refer to the list of diagnostics that can be assigned to each of the five (5) output definitions in the "DIAGNOSTICS Menu" section.
RT-SVP07D-EN 71
SETUP Menu
Assign Diagnostic to Alarm Output 1? Any Active Diagnostic (Yes)
Note: If “Yes” is selected at this screen, any active diagnostic will activate this output. A selection of “No” will allow the user to choose, from the following menus, which diagnostics activate the Alarm Output.
If No was entered, proceed to the following 2 screens.
Assignment Submenu – RTM Alarms Press ENTER To Review Or Adjust
Pressing the Next key will allow the user to skip this submenu.
Pressing the Enter key will allow the user to select any of the diagnostics associated with the RTM module to activate the associated Alarm Output.
Note: The user will be presented with similar Assignment Submenus for the following alarm sources: “SCM/MCM Alarms”, “HEAT Alarms”, “ECEM Alarms”, “VOM Alarms”, “VCM Alarms”, “GBAS Alarms”, “MDM Alarms”, “MPM Alarms” and “BAS/Network Alarms”.
If Enter was pressed, proceed to the following screen.
Used With: All Units w/GBAS(5VDC)
Installed
Possible Values: Yes, No
Used With: Units w/GBAS(5VDC) Installed
and Any Active Diagnostic Set to “No”
Note: Please review the “Diagnostics Troubleshooting Chart” in the “DIAGNOSTICS Menu” section to see the list of diagnostics associated with each module. (Refer to the “Diagnostics Displayed” column for the specified module.)
Assign Diagnostic to Alarm Output 1? RTM Zone Temp Sensor Failure (Yes)
Selecting “Yes” for each of the diagnostics displayed will activate the associated Alarm Output when that diagnostic is activated.
Note: The list of diagnostics displayed here will be dependent upon the module assignments selected. See the “Diagnostics Table” in the diagnostics menu section for the complete list displayed for each module.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter GBAS
• Press Next/Previous keys to navigate.
GBAS 0-10VDC MODULE I/O ASSIGNMENTS SCREENS
GBAS (10VDC) Module I/O Assignments Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
Used With: Units w/GBAS(5VDC)
Used With: Units w/GBAS(10VDC)
Installed
72 RT-SVP07D-EN
SETUP Menu
GBAS (10VDC) Analog Input 1 Assignment NOT ASSIGNED
Note: There are 3 additional screens associated with Input Assignments; “Analog Input 2”, “Analog Input 3”, and “Analog Input 4”. Press the Next key to proceed through the remaining assignments.
• Press Next/Previous keys to navigate.
The following screen will display if "Indicate selected diag alarms" is assigned.
GBAS (10VDC) Binary Alarm Assignments Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
If Enter was pressed, proceed to the following 3 screens.
Assign Diagnostic To Alarm Output Any Active Diagnostic (Yes)
Note: If “Yes” is selected at this screen, any active diagnostic will activate this output. A selection of “No” will allow the user to choose, from the following menus, which diagnostics activate the Alarm Output.
Used With: Units w/GBAS(10VDC) Installed
Factory Presets: NOT ASSIGNED Possible Values:
[See “Possible Values” in GBAS(5VDC) Above]
Used With: Units w/GBAS(10VDC) Installed
Used With: Units w/GBAS(10VDC) Installed
Factory Presets: Yes Possible Values: Yes, No
If No was entered, proceed to the following 2 screens.
Assignment Submenu – RTM Alarms Press ENTER To Review Or Adjust
Pressing the Next key will allow the user to skip this submenu.
Pressing the Enter key will allow the user to select any of the diagnostics associated with the RTM module to activate the associated Alarm Output.
Note: The user will be presented with similar Assignment Submenus for the following alarm sources: “SCM/MCM Alarms”, “HEAT Alarms”, “ECEM Alarms”, “VOM Alarms”, “VCM Alarms”, “GBAS Alarms”, “MDM Alarms”, “MPM Alarms” and “BAS/Network Alarms”.
If Enter was pressed, proceed to the following screen.
Used With: Units w/GBAS(10VDC)
Installed and Any Active Diagnostic Set to “No”
Note: Please review the “Diagnostics Troubleshooting Chart” in the “DIAGNOSTICS Menu” section to see the list of diagnostics associated with each module. (Refer to the “Diagnostics Displayed” column for the specified module.)
RT-SVP07D-EN 73
SETUP Menu
Assign Diagnostic to Alarm Output 1?
Used With: Units w/GBAS(10VDC)
RTM Zone Temp Sensor Failure (Yes)
Selecting “Yes” for each of the diagnostics displayed will activate the associated Alarm Output when that diagnostic is activated.
Note: The list of diagnostics displayed here will be dependent upon the module assignments selected. See the “Diagnostics Table” in the diagnostics menu section for the complete list displayed for each module.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter GBAS
• Press Next/Previous keys to navigate.
GBAS (0-10 VDC) Analog Output 1 Assignment NOT ASSIGNED
Note: There are 3 additional screens associated with Output Assignments; “Analog Output 2”, “Analog Output 3”, and “Analog Output 4”. Press the Next key to proceed through the remaining assignments.
• Press Next/Previous keys to navigate.
Used With: Units w/GBAS(10VDC)
Installed
Factory Presets: NOT ASSIGNED Possible Values:
NOT ASSIGNED ACTIVE COOLING CAPACITY ACTIVE HEATING CAPACITY OUTSIDE AIR TEMPERATURE ACTIVE ZONE TEMPERATURE ACTIVE SUPPLY AIR TEMPERATURE ACTIVE SUPPLY AIR PRESSURE ACTIVE SPACE PRESSURE ACTIVE SPACE RELATIVE HUMIDITY ACTIVE OUTDOOR AIR HUMIDITY ACTIVE SPACE CO ACTIVE OA DAMPER POSITION ACTIVE OUTDOOR AIR FLOW
LEVEL
2
End of Submenu (NEXT) to enter SETUP
• Press Next/Previous keys to navigate.
74 RT-SVP07D-EN
RTM ALARM OUTPUT DIAGNOSTIC ASSIGNMENTS SCREENS
RTM Alarm Output Setup Submenu
Used With: All Units
Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
If Enter was pressed, proceed to the following 3 screens.
SETUP Menu
Assign Diagnostic to Alarm Output? Any Active Diagnostic (Yes)
Note: If “Yes” is selected at this screen, any active diagnostic will activate this output. A selection of “No” will allow the user to choose, from the following menus, which diagnostics activate the Alarm Output.
If No was entered, proceed to the following 2 screens.
Assignment Submenu - RTM Alarms Press ENTER to Review or Adjust
Pressing the Next key will allow the user to skip this submenu.
Pressing the Enter key will allow the user to select any of the diagnostics associated with the RTM module to activate the associated Alarm Output.
Note: The user will be presented with similar Assignment Submenus for the following alarm sources: “SCM/MCM Alarms”, “HEAT Alarms”, “ECEM Alarms”, “VOM Alarms”, “VCM Alarms”, “GBAS Alarms”, “MDM Alarms”, “MPM Alarms” and “BAS/Network Alarms”.
If Enter was pressed, proceed to the following screen.
Used With: All Units Possible Values: Yes, No
Used With: All Units and Any Active
Diagnostic Set to “No”
Note: Please review the “Diagnostics Troubleshooting Chart” in the “DIAGNOSTICS Menu” section to see the list of diagnostics associated with each module. (Refer to the “Diagnostics Displayed” column for the specified module.)
Assign Diagnostic to Alarm Output? RTM Zone Temp Sensor Failure (Yes)
Selecting “Yes” for each of the diagnostics displayed will activate the associated Alarm Output when that diagnostic is activated.
Note: The list of diagnostics displayed here will be dependent upon the Assignment Submenu selected. See the “Diagnostics Troubleshooting Table” in the diagnostics menu section for the list of diagnostics displayed for each module.
• Press Next/Previous keys to navigate.
Used With: All Units and the ENTER Key
Was Pressed At The Prior Screen
End of Submenu (NEXT) to Enter SETUP
• Press the Next key to navigate forward.
RT-SVP07D-EN 75
SETUP Menu

Temperature Input Calibration Screens

The following five (5) Offset screens are used only if calibration of a sensor designated to perform the listed function is
necessary.
Example: If the temperature sensor for Morning Warm Up (MWU) is checked and a difference between the actual measured room temperature and the corresponding measured sensor value is found, by programming the amount of error into theTemperature Input Offset for Morning Warm Up (MWU) Heat —The sensor can be calibrated.
CALIBRATION AND OFFSET SUBMENU SCREENS
Calibration and Offset Submenu Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
Temperature Calibration Offset For RTM Zone Temperature Input 0.0°F
• Press Next/Previous keys to navigate.
Temperature Calibration Offset For RTM Aux Temperature Input 0.0°F
• Press Next/Previous keys to navigate.
Temperature Calibration Offset For RTM Outside Air Temperature Input 0.0°F
• Press Next/Previous keys to navigate.
Temperature Calibration Offset For Heat Module Aux Temp Input 0.0°F
• Press Next/Previous keys to navigate.
Used With: All Units
Used With: All Units Factory Presets: 0.0ºF Possible Values: -5.0 to 5.0ºF
Used With: All Units Factory Presets: 0.0ºF Possible Values: -5.0 to 5.0ºF
Used With: All Units Factory Presets: 0.0ºF Possible Values: -5.0 to 5.0ºF
Used With: Units w/Heat or Chilled
Water Installed
Factory Presets: 0.0ºF Possible Values: -5.0 to 5.0ºF
Temperature Calibration Offset For ECEM Return Air Temperature Input 0.0°F
• Press Next/Previous keys to navigate.
Used With: Units w/Comparative
Enthalpy Installed
Factory Presets: 0.0ºF Possible Values: -5.0 to 5.0ºF
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
76 RT-SVP07D-EN
DEVICE CHARACTERISTICS SETUP DEFINITIONS SCREENS
SETUP Menu
Device Characteristic Setup Definitions Press ENTER to review or Adjust
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper Max Stroke Time 30 Sec
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper Min Voltage 2.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup OA Damper Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Used With: All Units
Used With: Units w/OA Damper Factory Presets: 30 Sec Possible Values: 1 to 255 Sec
Used With: Units w/OA Damper Factory Presets: 2.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/OA Damper Factory Presets: 10.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/OA Damper Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING,
REVERSE ACTING
Actuator Setup Supply Fan IGV/VFD Max Stroke Time 30 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Supply Fan IGV/VFD Cmd Min Voltage 0.0 VDC
Note: If the unit is configured for a Supply Fan VFD, initial setting should be 0.0 VDC. If the unit is configured with IGV set this value to 2.0 VDC.
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 77
Used With: VVDC Units Factory Preset: 30 Sec Possible Values: 1 to 255 Sec
Used With: VVDC Units Factory Presets: 0 VDC Possible Values: 0 to 10.0 VDC
SETUP Menu
Actuator Setup Supply Fan IGV/VFD Cmd Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Supply Fan IGV/VFD Cmd Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Return Fan VFD Max Stroke Time 30 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Return Fan VFD Min Voltage 0.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Return Fan VFD Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Used With: VVDC Units Factory Presets: 10.0 VDC Possible Values: 0 to 10.0 VDC
Used With: VVDC Units Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING,
REVERSE ACTING
Used With: Units w/Return Fan Option Factory Presets: 30 Sec Possible Values: 1 to 255 Sec
Used With: Units w/Return Fan Option Factory Presets: 0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/Return Fan Option Factory Presets: 10.0 VDC Possible Values: 0 to 10.0 VDC
Actuator Setup Return Fan VFD Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Exhaust Damper/VFD Max Stroke Time 60 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Exhaust Damper/VFD Min Voltage 2.0 VDC
Note: If the unit is configured for a Exhaust Fan VFD, initial setting should be 0.0 VDC. If the unit is configured w/o VFD set this value to 2.0 VDC.
• Press Next/Previous keys to navigate.
78 RT-SVP07D-EN
Used With: Units w/Return Fan Option Factory Presets: Direct Acting Possible Values: Direct, Reverse
Used With: Units w/Power Exhaust Factory Presets: 60 Sec Possible Values: 1 to 255 Sec
Used With: Units w/Power Exhaust Factory Presets: 2.0 VDC Possible Values: 0 to 10.0 VDC
SETUP Menu
Actuator Setup Exhaust Damper/VFD Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Exhaust Damper/VFD Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Hydronic Max Stroke Time 60 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Hydronic Min Voltage 2.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Hydronic Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Used With: Units w/Power Exhaust Factory Presets: 10.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/Power Exhaust Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING,
REVERSE ACTING
Used With: Units w/Hydronic Heat and/ or Chilled Water Installed
Factory Presets: 60 Sec Possible Values: 1 to 255 Sec
Used With: Units w/Hydronic Heat and/
or Chilled Water Installed
Factory Presets: 2.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/Hydronic Heat and/
or Chilled Water Installed
Factory Presets: 0 VDC Possible Values: 0 to 10.0 VDC
Actuator Setup Hydronic Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown
Actuator Setup Num 1 Low Ambient Max Stroke Time 60 Sec
OR
Actuator Setup Cond Fan VFD Ckt 1 Max Stroke Time 60 Sec
Press the Next key to navigate forward.
RT-SVP07D-EN 79
Used With: Units w/Hydronic Heat and/ or Chilled Water Installed
Factory Presets: DIRECT ACTING Possible Values: DIRECT ACTING,
REVERSE ACTING
Used With: Units w/DX Cooling, w/Air­Cooled Condensers
Factory Presets: 60 Sec Possible Values: 1 to 255 Sec
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 60 Sec Possible Values: 1 to 255 Sec
SETUP Menu
Note: Only one of the following two screens will be shown based
on condenser type.
Actuator Setup Num 1 Low Ambient Min Voltage 2.0 VDC
OR
Actuator Setup Cond Fan VFD Ckt 1 Min Voltage 0.0 VDC
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown based on condenser type.
Actuator Setup Num 1 Low Ambient Max Voltage 10.0 VDC
OR
Actuator Setup Cond Fan VFD Ckt 1 Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 2.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 10.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 10.0 VDC Possible Values: 0 to 10.0 VDC
Note: Only one of the following two screens will be shown based on condenser type.
Actuator Setup Num 1 Low Ambient Direct/Reverse Act DIRECT ACTING
OR
Actuator Setup Cond Fan VFD Ckt 1 Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
80 RT-SVP07D-EN
Used With: Units w/DX Cooling, w/Air­Cooled Condensers
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse
Acting
Used With: Units w/DX Cooling, w/ Water-Cooled Condensers
Factory Preset: DIRECT Possible Values: DIRECT, REVERSE
Note: Only one of the following two screens will be shown based on condenser type.
SETUP Menu
Actuator Setup Num 2 Low Ambient Max Stroke Time 60 Sec
OR
Actuator Setup Cond Fan VFD Ckt 2 Max Stroke Time 60 Sec
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown based on condenser type.
Actuator Setup Num 2 Low Ambient Min Voltage 2.0 VDC
OR
Actuator Setup Cond Fan VFD Ckt 2 Min Voltage 0.0 VDC
• Press Next/Previous keys to navigate.
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 60 Sec Possible Values: 1 to 255 Sec
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 60 Sec Possible Values: 1 to 255 Sec
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: 2.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 0 VDC Possible Values: 0 to 10.0 VDC
Note: Only one of the following two screens will be shown based on condenser type.
Actuator Setup Num 2 Low Ambient Max Voltage 10.0 VDC
OR
Actuator Setup Cond Fan VFD Ckt 2 Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Note: Only one of the following two screens will be shown based on condenser type.
Actuator Setup Num 2 Low Ambient Direct/Reverse Act DIRECT ACTING
RT-SVP07D-EN 81
Used With: Units w/DX Cooling, w/Air­Cooled Condensers
Factory Presets: 10.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: 10.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/DX Cooling, w/Air-
Cooled Condensers
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse
Acting
SETUP Menu
OR
Actuator Setup Cond Fan VFD Ckt 2 Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Modulating Gas Heat Max Stroke Time 90 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Modulating Gas Heat Min Voltage 2.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Modulating Gas Heat Max Voltage 10 VDC
• Press Next/Previous keys to navigate.
Used With: Units w/DX Cooling, w/
Water-Cooled Condensers
Factory Preset: DIRECT Possible Values: DIRECT, REVERSE
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is installed
Factory Presets: 90 Sec Possible Values: 1 to 255 Sec
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is installed
Factory Presets: 2 VDC Possible Values: 0 to 10.0 VDC
Used With: All Rooftop Units and Air
Handlers when Modulating Gas is installed
Factory Presets: 10 VDC Possible Values: 0 to 10.0 VDC
Actuator Setup Modulating Gas Heat Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Exh Bypass Damper Max Stroke Time 60 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Exh Bypass Damper Min Voltage 2.0 VDC
• Press Next/Previous keys to navigate.
82 RT-SVP07D-EN
Used With: All Rooftop Units and Air Handlers Modulating Gas is installed
Factory Presets: Direct Acting Possible Values: Direct Acting, Reverse
Acting
Used With: All IntelliPak II units with Energy Recovery installed.
Factory Preset: 60 Sec Possible Values: 1 to 255 Sec
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 2.0 VDC Possible Values: 0 to 10.0 VDC
SETUP Menu
Actuator Setup Exh Bypass Damper Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Exh Bypass Damper Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Actuator Setup OA Bypass Damper Max Stroke Time 60 Sec
• Press Next/Previous keys to navigate.
Actuator Setup OA Bypass Damper Min Voltage 2.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup OA Bypass Damper Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 10.0 VDC Possible Values: 0 to 10.0 VDC
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: DIRECT Possible Values: DIRECT, REVERSE
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 60 Sec Possible Values: 1 to 255 Sec
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 2.0 VDC Possible Values: 0 to 10.0 VDC
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: 10.0 VDC Possible Values: 0 to 10.0 VDC
Actuator Setup OA Bypass Damper Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Actuator Setup Variable Speed Comp Max Stroke Time 30 Sec
• Press Next/Previous keys to navigate.
Actuator Setup Variable Speed Comp Min Voltage 0.0 VDC
• Press Next/Previous keys to navigate.
Actuator Setup Variable Speed Comp Max Voltage 10.0 VDC
• Press Next/Previous keys to navigate.
Used With: All IntelliPak II units with
Energy Recovery installed.
Factory Preset: DIRECT Possible Values: DIRECT, REVERSE
Used With: Units w/Variable Speed
Compressor Installed.
Factory Preset: 30 Sec Possible Values: 1 to 255 Sec
Used With: Units w/Variable Speed
Compressor Installed.
Factory Preset: 0.0 VDC Possible Values: 0 to 10.0 VDC
Used With: Units w/Variable Speed
Compressor Installed.
Factory Preset: 10.0 VDC Possible Values: 0 to 10.0 VDC
RT-SVP07D-EN 83
SETUP Menu
Actuator Setup Variable Speed Comp Direct/Reverse Act DIRECT ACTING
• Press Next/Previous keys to navigate.
Used With: Units w/Variable Speed
Compressor Installed.
Factory Preset: DIRECT ACTING Possible Values: DIRECT ACTING,
REVERSE ACTING
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
CONTROL ALGORITHM TUNING PARAMETERS SCREENS (Partial)
Control Algorithm Tuning Parameters Press ENTER to Review or Adjust
Note: Contact the Trane Company before making any adjustment to these settings.
• Press Next/Previous keys to navigate.
SZVAV Cooling Control Gains Proportional 6.0 %/F Reset Time 1200 Sec
Note: This screen must be changed on field replacement of the RTM Module.
• Press Next/Previous keys to navigate.
Used With: All IntelliPak units with
SZVAV Installed.
Factory Preset:
Prop: 6.0 Reset: 1200
Possible Values:
Prop: 0.2 - 50 Reset: 90 - 3600, DISABLED
SZVAV Heating Control Gains Proportional 8.0 %/F Reset Time 1200 Sec
Note: This screen must be changed on field replacement of the RTM Module.
• Press Next/Previous keys to navigate.
Zone Control Occupied Heating Gains Proportional 30.0 %/F Reset Time 1800 Sec
Note: This screen must be changed on field replacement of the RTM Module.
84 RT-SVP07D-EN
Used With: All IntelliPak units with SZVAV Installed.
Factory Preset:
Prop: 8.0 Reset: 1200
Possible Values:
Prop: 0.2 - 50 Reset: 90 - 3600, DISABLED
Used With: All IntelliPak units with Staged Heat Installed.
Range: 2.0 - 200 Possible Values:
[See “Table 6. Proportional Parameter -
Staged Heat" on page 85 for
assignments.]
Table 6. Proportional Parameter - Staged Heat
SETUP Menu
Staged Heat
Product
IPak I Gas 2 30.0
IPak I Electric 3 45.0
IPak II Gas 2 30.0
IPak II Electric 90 kw 3 45.0
IPak II Electric 140 kw 4 60.0
IPak II Electric 265 kw 5 75.0
IPak II Electric 300 kw 5 75.0
Type No of Stages
Proportional
Gain
• Press Next/Previous keys to navigate.
Rapid DX Interstage Timing: 30 Sec
Note: This screen must be changed on field replacement of the RTM Module.
• Press Next/Previous keys to navigate.
End of Submenu (NEXT) to Enter SETUP
• Press Next/Previous keys to navigate.
Used With: All IntelliPak units w/
Dehumidification or Rapid Restart.
Factory Presets: Range: 30 Possible Values: 15 - 50
RT-SVP07D-EN 85

SETPOINT Menu

The setpoint menu is used to designate default zone temperature setpoints, supply air and space pressure setpoints, and
low ambient compressor lockout setpoints.
These setpoints will be active (in use) for the “Setpoint Source Selection” designated as “DEFAULT” for these inputs.
When a setpoint screen is displayed for 30 minutes without a key being pressed, the LCD screen will revert to the general
operating status display. If this happens, press the Setpoint key again to return to the setpoint menu.
Note: Many of the screens displayed in this section are applicable only for the options that are installed in the unit and
may not be visible on your unit.
Modifying Selections: Starting with the first setpoint screen program the necessary information by using the
appropriate keys to navigate (Next and Previous) and make changes (+ and -) to the selections. Once the selection has been changed to the desired value, the user has the following options to either Cancel or Accept the pending change:
To Cancel, press the Cancel key to remove the change, the display will revert to the original value.
To Accept, press the Enter key to confirm the new choice.
Press the Setpoint key to begin viewing or modifying the unit setpoints.
TOP LEVEL SETPOINTS SCREEN
Default Supply Air Temp Setpoints Cooling: 55°F Heating: 100°F
Note: These values must be reset on field replacement of the RTM Module if the unit is configured for SZVAV (VVZT).
“Heating” setpoint only shown if units are configured with hydronic or modulating gas heat, or if IpakII w/electric heat.
• Press Next/Previous keys to navigate.
Supply Air Temperature Deadband Cooling: 8.0°F Heating: 4.0°F
“Heating” setpoint only shown if units are configured with hydronic or modulating gas heat, or if IpakII w/electric heat.
• Press Next/Previous keys to navigate.
Default Daytime Warmup Setpoints Initiate: 67°F Terminate: 71°F
• Press Next/Previous keys to navigate.
Used With: VV/CVDA or VVZT Units Factory Presets: Factory Presets:
Cooling: 55ºF (VVZT: 50°F) Heating: 100ºF (VVZT: 105°F)
Possible Values:
Cool: 40 to 90ºF Heat: 40 to 180ºF
Used With: VV/CVDA Units Factory Presets:
Cooling: 8ºF Heating: 4ºF
Possible Values:
Cool: 1 to 20ºF Heat: 2 to 10ºF
Used With: VV/CVDA Units w/DWU Enabled
Factory Presets:
Initiate: 67ºF Terminate: 71ºF
Possible Values:
DWU Initiate: 50 to 87ºF DWU Terminate: 53 to 90ºF
86 RT-SVP07D-EN
SETPOINT Menu
Default Occupied Zone Temp Setpoints Cool: 74°F Heat: 71°F
“Cool” setpoint shown for CVZT units. “Heat” setpoint shown for CVZT w/heat installed, or VV/CVDA units with DWU or MWU enabled.
• Press Next/Previous keys to navigate.
Derived Zone Setpoint Deadband: 2.0°F Used When Only One Setpoint is Available
• Press Next/Previous keys to navigate.
Default Unoccupied Zone Temp Setpoints Cool: 85°F Heat: 60°F Morn Warmup: 72°F
Note: Minimum difference of 2ºF maintained between Heating & Cooling Setpoints. Morning warmup cannot be lower than Heating Setpoints.
“Heat” and “Morn Warmup” shown for units w/heat installed. “Morn Warmup” shown if MWU is enabled.
Used With: CVZT or VVZT Units, or VV/ CVDA Units w/DWU or MWU Enabled
Factory Presets:
Cool: 74ºF Heat: 71ºF
Possible Values:
Heat: 50 to 90ºF
Used With: CVZT or VVZT Units w/Zone Sensor Supporting Only One Setpoint
Factory Preset: 4.0ºF Possible Values: 2.0 to 10.0ºF
Used With: All Units Factory Presets:
Cool: 85ºF Heat: 60ºF MWU: 72ºF
Possible Values:
Cool: 52 to 90ºF Heat: 50 to 88ºF MWU: 50 to 90ºF
• Press Next/Previous keys to navigate.
Dflt Rapid Restart Critical Temp: 90°F
Return temperature relative to this setpoint determines target DX stage during a Rapid Restart event.
• Press Next/Previous keys to navigate.
HUMIDITY CONTROL SETPOINT SUBMENU SCREENS
Humidity Control Setpoint Submenu Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
Dehumidify if Space Humidity Above Occ Dehumidification Setpoint: 60%
• Press Next/Previous keys to navigate.
Used With: All IntelliPak Units w/Rapid
Restart Installed
Factory Preset: 90ºF Possible Values: 75, 80, 85, 90, 95 ºF
Used With: Units w/Dehumidification or
Humidification Option
Used With: Units w/Dehumidification Option
Factory Preset: 60 % Possible Values: 40 to 65 %
RT-SVP07D-EN 87
SETPOINT Menu
Stop Dehumid if Space RH Below STP Minus Occ Dehumid Hysteresis Offset: 5%
• Press Next/Previous keys to navigate.
Dehumidify if Space Humidity Above Unocc Dehumidification Setpoint: 60%
• Press Next/Previous keys to navigate.
Stop Dehumid if Space RH Below STP Minus Unocc Dehumid Hysteresis Offset: 5%
• Press Next/Previous keys to navigate.
Default Supply Air Reheat Stpt: 70°F Supply Air Reheat Deadband: 4°F
• Press Next/Previous keys to navigate.
Used With: Units w/Dehumidification
Option
Factory Preset: 5 % Possible Values: 3 to 10 %
Used With: Units w/Dehumidification
Option and Unocc Dehumid. Enabled
Factory Preset: 60 % Possible Values: 40 to 65 %
Used With: Units w/Dehumidification
Option and Unocc Dehumid. Enabled
Factory Preset: 5 % Possible Values: 3 to 10 %
Used With: Units w/Dehumidification
Option Factory Preset:
Reheat Setpoint: 70ºF Reheat Deadband: 4ºF
Possible Values:
Reheat Setpoint: 60 to 80ºF Reheat Deadband: 2 to 10ºF
In Active Dehumidification Mode, Limit Maximum Reheat Valve Position To: 85%
• Press Next/Previous keys to navigate.
Dehumid Ovrd High Zone Temp Stpt: 75°F Dehumid Ovrd Low Zone Temp Stpt: 68°F
• Press Next/Previous keys to navigate.
Cond Coil Purge Interval Setpt: 90 Min
• Press Next/Previous keys to navigate.
88 RT-SVP07D-EN
Used With: Units w/Dehumidification Option
Factory Preset: 85 % Possible Values: 50 to 85 %
Used With: VV/CVDA Units w/
Dehumidification Option Factory Preset:
Ovrd High Temp: 75ºF Ovrd Low Temp: 68ºF
Possible Values:
Ovrd High Temp: 70 to 85ºF Ovrd Low Temp: 60 to 75ºF
Used With: Units w/Dehumidification Option
Factory Preset: 90 Minutes Possible Values: 60 to 120 Minutes
SETPOINT Menu
Humidify if Space Humidity Below Occ Humidification Setpoint: 30%
• Press Next/Previous keys to navigate.
Stop Humid if Space RH Above STP Plus Occ Humid Hysteresis Offset: 5%
• Press Next/Previous keys to navigate.
Humidify if Space Humidity Below Unocc Humidification SETPOINT: 30%
• Press Next/Previous keys to navigate.
Stop Humid if Space RH Above STP Plus Unocc Humid Hysteresis Offset: 5%
• Press Next/Previous keys to navigate.
Used With: Units w/Humidification
Option
Factory Preset: 30 % Possible Values: 20 to 50 %
Used With: Units w/Humidification
Option
Factory Preset: 5 % Possible Values: 3 to 10 %
Used With: Units w/Humidification
Option and Unocc. Humid. Enabled
Factory Preset: 30 % Possible Values: 20 to 50 %
Used With: Units w/Humidification
Option and Unocc. Humid. Enabled
Factory Preset: 5 % Possible Values: 3 to 10 %
End Of Submenu (NEXT) to Enter SETPOINT
• Press Next/Previous keys to navigate.
OUTSIDE AIR CONTROL SETPOINT SUBMENU SCREENS
Outside Air Control Setpoint Submenu Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
When Economizer Cooling, Reduce Zone Temperature Cooling Setpoint By: 1.5°F
• Press Next/Previous keys to navigate.
Used With: Units w/Fresh Air Option
Used With: CVZT Units w/Economizer
Option
Factory Preset: 1.5ºF Possible Values: 0.0 to 3.0ºF
RT-SVP07D-EN 89
SETPOINT Menu
Reference Enthalpy. Enable Air Econ When OA Enthalpy is Below: 25 BTU/LB
Note: This Setpoint is used when Comparative Enthalpy is not installed or is invalid due to return air humidity or temperature is out of range or failed.
• Press Next/Previous keys to navigate.
Default Econ Drybulb Enable Setpoint Enable Economizer Below: 75°F
Note: This setpoint is used when Comparative Enthalpy is not installed, or is invalid, and Drybulb is selected for alternate economizer enable/disable decision.
• Press Next/Previous keys to navigate.
Supply Air Low Limit–Modulate Economizer Toward Min Pos if SA Temp below: 50°F
• Press Next/Previous keys to navigate.
Used With: Units w/Economizer Factory Presets: 25 BTU/LB Possible Values: 19 to 28 BTU/LB
Used With: Units w/Economizer Factory Presets: 75ºF Possible Values: 50 to 140ºF
Used With: CVZT Units, or non-VVZT
Units Operating in Unoccupied Economizer Cooling Mode
Factory Presets: 50ºF Possible Values: 40 to 65ºF
VCM Preheat ON If VCM Aux Temp Below Ventilation Preheat Setpoint: 35°F
• Press Next/Previous keys to navigate.
Default Design Min CO2 Setpt: 1000 PPM Default DCV Min CO2 Setpoint: 400 PPM
• Press Next/Previous keys to navigate.
Note: The following 2 screens are only shown if DCV is enabled.
Used With: Units w/Fresh Air Measurement (VCM) w/DCV, or OA Damper Min Position w/DCV, and Preheat Enabled
Factory Presets: 35ºF Possible Values: 35 to 75ºF
Used With: Units w/Fresh Air
Measurement (VCM) w/DCV, or OA Damper Min Position w/DCV
Factory Presets:
Design Min CO DCV Min CO
Possible Values:
Design Min CO DCV Min CO
: 1000 PPM
2
: 400 PPM
2
: 150 to 2000 PPM
2
: 50-1900 PPM
2
90 RT-SVP07D-EN
SETPOINT Menu
Default Design Min OA Flow Stp: 350 CCFM Default DCV Min OA Flow Setpt: 150 CCFM
• Press Next/Previous keys to navigate.
Demand Controlled Ventilation Min OA Flow deadband: 5 CCFM
• Press Next/Previous keys to navigate.
OR
Note: The following screen is only shown if DCV is disabled.
Default Min OA Flow Setpoint: 40 CCFM Min OA Flow Deadband: 5.0 CCFM
Used With: Units w/Fresh Air Measurement (VCM) w/DCV
Factory Preset: 220 CCFM
Ovrd to 112 CCFM for 90 and 105 Ton Ovrd to 146 CCFM for 120 and 130 Ton
Possible Values:
Design Min OA Flow: 0 to 585 CCFM DCV Min OA Flow: 0 to 585 CCFM
Used With: Units w/Fresh Air Measurement (VCM) w/DCV
Factory Presets: 5 CCFM Possible Values: 5 to 20 CCFM
Used With: Units w/Fresh Air
Measurement (VCM) w/o DCV
Factory Presets:
Setpoint: 40 CCFM Deadband: 5 CCFM
Possible Values:
[See “Table 7. Max Unit Airflows” for assignments.]
Table 7. Max Unit Airflows
Max Airflow
Capacity
Product
IPak 20 to 25 0 to 14000 500 to 2000
IPak 30 0 to 17000 500 to 2000
IPak 40 0 to 22000 500 to 2000
IPak 50 to 55 0 to 28000 500 to 2000
IPak 60 to 75 0 to 33000 700 to 2000
IPak 90 to 130 0 to 46000 1000 to 2000
IPak II 90 to 105 0 to 45000 500 to 2000
IPak II 120 to 150 0 to 58500 500 to 2000
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 91
(Tons)
Range (CFM)
Deadband
Range (CFM)
SETPOINT Menu
Default Design Min OA Damper Pos: 15% Default DCV Min OA Damper Pos Stp: 10%
• Press Next/Previous keys to navigate.
Default OA Damper Min Position: 15% With IGV/VFD Command At Minimum (0%)
Note: OA Damper Min Pos…At Minimum (0%) must be > OA Damper Min Pos…At Maximum (100%) if VVDA, or at Medium (50%) if VVZT.
• Press Next/Previous keys to navigate.
Default OA Damper Min Position: 20% With IGV/VFD Command At Medium (50%)
Note: OA Damper Min Pos…At Minimum (50%) must be > OA Damper Min Pos…At Maximum (100%) and must be < OA Damper Min Pos...At Minimum (0%).
Used With: Units w/OA Damper, And OA Damper Min Pos w/DCV Option, and OA CFM Compensation Disabled.
Factory Presets:
Design Min OA Damper: 15 % DCV Min OA Damper: 10 %
Possible Values: 0 to 100 %
Used With: VVDA or VVZT Units w/OA
Damper, And OA CFM Compensation Enabled
Factory Presets:
VVDA: 15 % VVZT: 25 %
Possible Values: 0 to 100 %
Used With: VVZT Units w/OA Damper,
And OA CFM Compensation Enabled
Factory Presets: 20% Possible Values: 0 to 100 %
• Press Next/Previous keys to navigate.
Default OA Damper Min Position: 10% With IGV/VFD Command At Maximum (100%)
Note: OA Damper Min Pos…At Minimum (100%) must be < OA Damper Min Pos…At Maximum (100%) if VVDA, or At Medium (50%) if VVZT.
• Press Next/Previous keys to navigate.
OR
Default OA Damper Min Position: 15%
Note: If unit has TRAQ, this setpoint is only used in case of flow station failure.
• Press Next/Previous keys to navigate.
End Of Submenu (NEXT) To Enter SETPOINT
• Press Next/Previous keys to navigate.
Used With: VVDA or VVZT Units w/OA
Damper, And OA CFM Compensation Enabled
Factory Presets:
VVDA: 10 % VVZT: 5 %
Possible Values: 0 to 100 %
Used With: Units w/OA Damper Option,
DCV Disabled, OACFM Compensation Disabled
Factory Presets: 15 % Possible Values: 0 to 100 %
Used With: All units
92 RT-SVP07D-EN
SETPOINT Menu
Default Supply Air Pressure: 2.0 IWC High Limit: 4.0 IWC Deadband: 0.5 IWC
“Default Supply Air Pressure” and “Deadband” shown for VVDA. “High Limit” shown for all VVDA, VVZT and CVDA units if present.
Note: “Default Supply Air Pressure” will not adjust higher than: (High Limit – 0.1 – ½ Deadband).
• Press Next/Previous keys to navigate.
Max Return Plenum Pressure Stp: 0.8 IWC Deadband: 0.2 IWC
• Press Next/Previous keys to navigate.
Used With: VV/CVDA or VVZT Units Factory Presets:
Setpoint: 2.0 IWC High Limit: 4.0 IWC Deadband: 0.5 IWC
Possible Values: (IPak II)
Setpoint: 0.7 to 5.1 IWC High Limit: 1.2 to 5.7 IWC Deadband: 0.1 to 2.0 IWC
Possible Values: (IPak-I)
Setpoint: 0.7 to 4.3 IWC High Limit: 1.2 to 4.7 IWC Deadband: 0.1 to 2.0 IWCV
Used With: Units w/Return Fan VFD Installed (Statitrac)
Factory Presets:
Setpoint: 0.8 IWC Deadband: 0.2 IWC
Possible Values:
Setpoint: 0.1 to 2.5 IWC Deadband: 0.1 to 1.0 IWC
Default Space Pressure Setpoint:0.08 IWC Space Pressure Deadband: 0.10 IWC
OR
Default Space Pressure Setpt: 0.08 IWC Deadband: 0.10 IWC Low Limit: -0.02 IWC
• Press Next/Previous keys to navigate.
Used With: Units w/Statitrac Installed,
w/o Return Fan Option
Factory Presets:
Setpoint: 0.08 IWC Deadband: 0.04 IWC
Possible Values:
Setpoint: -0.2 to 0.3 IWC Deadband: 0.02 to 0.2 IWC
Used With: Units w/Statitrac Installed, w/Return Fan Option
Factory Presets:
Setpoint: 0.08 IWC Deadband: 0.04 IWC Low Limit: -0.05 IWC
Possible Values:
Setpoint: -0.2 to 0.3 IWC Deadband: 0.02 to 0.2 IWC Low Limit: -0.4 to 0.2 IWC
RT-SVP07D-EN 93
SETPOINT Menu
Exhaust Enable Point. Enable Exhaust Fan When Outside Air damper is Above: 25%
• Press Next/Previous keys to navigate.
Exhaust Disabled When OA Damper is Below Exhaust Inhibit Point: 15%
“Exhaust Disabled When OA Damper is Below” is shown when set to anything other than DISABLED. If set to DISABLED, “Exhaust Function Not Disabled By” is shown on top line.
• Press Next/Previous keys to navigate.
Low Ambient Comp Lockout Temp: 50°F Comp(s) OFF if OA Temp Below This Value
• Press Next/Previous keys to navigate.
For Standby Freeze Avoidance, Open the Hydronic Heat Valve(s) To: 0%
Note: When the supply fan is OFF, and the active outside air temperature drops below 45F, the hydronic valve output will be driven to the value specified here.
Used With: Units w/Power Exhaust Option
Factory Presets: 25 % Possible Values: 0 to 100 %
Used With: Units w/Power Exhaust, w/
Return Fan Option
Factory Presets: DISABLED Possible Values: 0 to 25 %, DISABLED
Used With: Units w/DX Cooling Factory Presets: 50ºF Possible Values: -20 to 80ºF
Used With: Units w/Hydronic Heat Factory Preset: Disabled Possible Values: Disabled, 1 to 100 %
• Press Next/Previous keys to navigate.
Frost Avoidance ON When LRE Temp Below Recovery Frost Avoidance Setpoint: 27°F
• Press Next/Previous keys to navigate.
Used With: Units w/Energy Recovery
Option
Factory Preset: 27ºF Possible Values: 0 to 60ºF
SETPOINT SOURCE SELECTIONS SUBMENU SCREENS
Setpoint Source Selections Submenu Press ENTER to Review or Adjust
Note: For GBAS selections to be shown, either the GBAS(5VDC) or GBAS(10VDC) module must be installed.
• Press the Next key to skip this Submenu.
94 RT-SVP07D-EN
Used With: All Units Factory Presets: For All Setpoint
Source Selections the Factory Presets will be:
HI (KEYPAD) SETPOINT MENU
SETPOINT Menu
For Supply Air Temp Cooling Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
For Supply Air Temp Heating Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
For Occ Zone Temp Cooling Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
Used With: VV/CVDA or VVZT Units Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS (5VDC) MODULE GBAS (10VDC) MODULE• Press Next/Previous keys to navigate.
Used With: VV/CVDA or VVZT Units w/ Hydronic or Modulating Gas Heat, or IpakII w/Electric Heat
Possible Values:
HI (KEYPAD) SETPOINT MENU NSB PANEL SETPOINT INPUT GBAS(5VDC) Module GBAS(10VDC) Module
Used With: CVZT Units or VVZT w/ Cooling
Possible Values:
HI (KEYPAD) SETPOINT MENU ZONE SENSOR SETPOINT INPUT NSB PANEL SETPOINT INPUT GBAS (5VDC) MODULE GBAS (10VDC) MODULE
For Occ Zone Temp Heating Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
For Unocc Zone Temp Cooling Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
For Unocc Zone Temp Heating Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 95
Used With: CVZT or VVZT Units w/Heat, And VV/CVDA Units w/Heat and DWU Enabled
Possible Values: [Same as “Possible Values” Above]
Used With: Units w/Cooling Possible Values: [Same as “Possible Values” Above]
Used With: Units w/Heat Installed Possible Values: [Same as “Possible Values” Above]
SETPOINT Menu
For Morning Warmup Temp Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
For Economizer Dry Bulb Enable, Use Setpoint From: HI(KEYPAD) SETPOINT Menu
For Default OA Damper Min Position, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
HUMIDITY CTRL STPT SOURCE SELECT SUBMENU SCREENS
Used With: Units w/Heat Installed Possible Values:
HI (KEYPAD) SETPOINT MENU NSB PANEL SETPOINT INPUT GBAS (5VDC) MODULE GBAS (10VDC) MODULE• Press Next/Previous keys to navigate.
Used With: Units w/Economizer Option Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS(5VDC) MODULE GBAS(10VDC) MODULE• Press Next/Previous keys to navigate.
Used With: Units w/Economizer Option Possible Values:
HI (KEYPAD) SETPOINT MENU REMOTE MIN POS POT INPUT GBAS(5VDC) MODULE GBAS(10VDC) MODULE• Press Next/Previous keys to navigate.
Humidity Ctrl Stpt Source Select Submenu Press ENTER to Review or Adjust
• Press the Next key to skip this Submenu.
For Occ Dehumidification Control, Use Setpoint From: HI(KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
For Unocc Dehumidification Control, Use Setpoint From: HI(KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
For Occ Humidification Control, Use Setpoint From: HI(KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
Used With: All Units
Used With: Units w/Dehumidification
Option
Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS(5VDC) MODULE GBAS(10VDC) MODULE
Used With: Units w/Dehumidification Option
Possible Values: [Same as “Possible Values” Above]
Used With: Units w/Humidification
Option
Possible Values: [Same as “Possible Values” Above]
96 RT-SVP07D-EN
SETPOINT Menu
For Unocc Humidification Control, Use Setpoint From: HI(KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
For Supply Air Reheat Control, Use Setpoint From: HI(KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
End Of Submenu (NEXT) To ENTER SRC SEL
• Press Next/Previous keys to navigate.
For Min Outside Air Flow Rate Ctrl, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
For Supply Air Pressure Control, Use Setpoint From: HI (KEYPAD)SETPOINT MENU
• Press Next/Previous keys to navigate.
Used With: Units w/Humidification
Option
Possible Values: [Same as “Possible Values” Above]
Used With: Units w/Dehumidification
Option
Possible Values: [Same as “Possible Values” Above]
Used With: All units.
Used With: Units w/Fresh Air
Measurement (VCM) Option
Possible Values:
HI (KEYPAD) SETPOINT MENU GBAS 0-5 VDC MODULE GBAS 0-10VDC Module
Used With: VVDA Units Possible Values: [Same as “Possible Values” Above]
For Space Pressure Control, Use Setpoint From: HI (KEYPAD) SETPOINT MENU
• Press Next/Previous keys to navigate.
Used With: Units w/Statitrac Option Possible Values: [Same as “Possible Values” Above]
End Of Submenu (NEXT) To Enter SETPOINT
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 97

CONFIGURATION Menu

The electronically controlled unit has many operating functions whose settings are preset at the factory.The following
configuration programming steps are provided for those cases where the modules have been replaced after the unit has been in operation and must be reconfigured.
Refer to the Model number stamped on the unit nameplate located on the control panel door while scrolling through the configuration screens. Certain digits of this alpha/numeric model number provide information that must be entered at the Human Interface (HI) in order for the UCM network to operate properly.
Notes:
1. Prior to making any changes to these Configuration Menus, the Stop key must be pressed on the Local Human Interface.
2. Many of the screens displayed in this section are applicable only for the options that are installed in the unit and may not be visible on your unit. All screens displayed with “CONFIG REQ’D” are required to be changed prior to unit operation.
3. Pay close attention to the notes throughout this section of the document. The notes describe additional essential messages and other intermediate screen information.
Modifying Selections: Starting with the first configuration screen program the necessary information by using the
appropriate keys to navigate (Next and Previous) and make changes (+ and -) to the selections. Once the selection has been changed to the desired value, the user has the following options to either Cancel or Accept the pending change:
•ToCancel, press the Cancel key to remove the change, the display will revert to the original value.
•ToAccept, press the Enter key to confirm the new choice.
Press the Configuration key to begin viewing or modifying the configuration screens.
TOP LEVEL CONFIGURATION SCREEN
Unit Product Family is: INTELLIPAK II Press (NEXT) or (PREVIOUS) to Continue
Note: “Product Family” is based on the absence (INTELLIPAK), or presence (INTELLIPAK II), of a configuration jumper in the wire harness of the RTM module.
• Press Next/Previous keys to navigate.
Configuration - Model Num Digit 1 Unit Type: ROOFTOP UNIT
1. For INTELLIPAK II products, if “Unit Type” is changed “Unit Capacity” below is set to CONFIG REQ’D.
2. If “Heating Type” below is Electric Heat, the “Electric Heat Capacity” below is also set to CONFIG. REQ’D.
• Press Next/Previous keys to navigate.
Used With: All Units Possible Values:
INTELLIPAK INTELLIPAK II
Note: This screen is not adjustable.
Used With: All Units Possible Values:
ROOFTOP UNIT AIR HANDLERNote:
98 RT-SVP07D-EN
CONFIGURATION Menu
Configuration - Model Num Digit 2 Heating Type: GAS
Configuration - Model Num Digit 5, 6, 7 Unit Capacity: 90
OR
Configuration - Model Num Digit 5, 6, 7 Unit Capacity CFM: 16100-45000
• Press Next/Previous keys to navigate.
Configuration - Model Num Digit 6 Cooling Type: NO COOLING
Used With: All Units. Possible Values:
ELECTRIC GAS HYDRONIC EXTERNAL HEAT NONE (COOLING ONLY)• Press Next/Previous keys to navigate.
Used With: All Units w/DX Cooling Possible Values:
Multiple Selections: 20 through 162 Tons
Used With: Air Handler Units w/o DX Cooling
Possible Values:
Multiple Selections: 4000 through 45000
Used With: Air Handler Units Possible Values:
NO COOLING DX COOLING CHILLED WATER• Press Next/Previous keys to navigate.
Configuration - Model Num Digit 9 Electric Heat Capacity: 90 KW
OR
Configuration - Model Num Digit 9 Gas Heat Type: STAGED
Configuration - Model Num Digit 17 or 11 Exhaust/Return: NONE
Note: “RET FAN…” (All Return Fan) selections are not permitted to be installed here if the “Energy Recovery” option below is set to INSTALLED.
• Press Next/Previous keys to navigate.
RT-SVP07D-EN 99
Used With: Units w/Electric Heat Option Possible Values:
30, 50, 70, 110, 130, 150, 170, 190 KW
Used With: Units w/Gas Heat Option Possible Values:
STAGED MODULATING• Press Next/Previous keys to navigate.
Used With: All Units Possible Values:
NONE EXH FAN_W/ STATITRAC EXH FAN_W/O STATITRAC RET FAN W/ STATITRAC RET FAN W/O STATITRAC
CONFIGURATION Menu
Configuration - Model Num Digit 17 or 20 Single Zone VAV VVZT: INSTALLED
Note: Single Zone VAV (VVZT) functionality can be inhibited by setting this parameter to NOT INSTALLED. If set to NOT INSTALLED the unit will perform CVZT control.
• The following screens will be shown if there is a GBAS(5VDC)
SZSVAV hardware configuration failure. Otherwise press Next/ Previous keys to navigate.
GBAS Configuration Hardware Has Failed Press Enter to Reset, CANCEL to Ignore
Note: This screen is shown if the unit was configured for SZVAV and the hardware configuration input on the GBAS(5VDC) has failed or has been changed.
• Press the ENTER key to accept, and review the following screen.
Check GBAS Config Hardware, Cycle Power RETURN HERE TO CONFIRM CONFIGURATION
Note: This screen instructs the user to:
1. Turn OFF the power to the unit.
2. Inspect the GBAS(5VDC) hardware configuration input.
3. Restore the power to the Unit.
4. Return to this configuration screen and verify entry.
Used With: Units with GBAS(5VDC) Hardware Configuration - SZVAV.
Possible Values:
INSTALLED NOT INSTALLED
• Press Next/Previous keys to navigate.
Configuration - Model Num Digit 20 or 17 System Control: ZONE TEMP CTRL (CV)
Note: Zone Temp Ctrl (CV) - (CVZT) Disch Temp Ctrl (VAV) - (VVDA) - (Indicates w/ IGV/VFD) Disch Temp Ctrl (CV) - (CVDA) - (Indicates w/o IGV/VFD)
• Press Next/Previous keys to navigate.
Configuration - Model Num Digit 21 or 16 Fresh Air Section: No Fresh Air
• Press Next/Previous keys to navigate.
100 RT-SVP07D-EN
Used With: All Units not configured w/ Single Zone VAV (VVZT).
Possible Values:
ZONE TEMP CTRL (CV) DISCH TEMP CTRL (VAV) DISCH TEMP CTRL (CV)
Used With: All Units Possible Values:
NO FRESH AIR 0-100% ECONOMIZER 0-25% MOTORIZED DAMPER
Loading...