Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury.When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
July 2014
SCXF-SVX01K-EN
Introduction
Read thismanual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situationthat could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
•If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or
serious injury.
System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for refrigerant
type. Do not use non-approved refrigerants, refrigerant
substitutes, or refrigerant additives. Failure to recover
refrigerant to relieve pressure or the use of nonapproved refrigerants, refrigerant substitutes, or
refrigerant additives could result in an explosion which
could result in death or serious injury or equipment
damage.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives or
other energy storing components provided by Trane or
others, refer to the appropriate manufacturer’s literature
for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect power
and discharge capacitors before servicing could result in
death or serious injury.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types
of conductors. Failure to use copper conductors could
result in equipment damage.
Introduction
Introduction
This manual covers installation, operation and
maintenance of 20-110 ton Signature Series Commercial
Self Contained products with R-410A refrigerant.
R-410A Compressors
•Use crank case heaters which must be energized 24
hours prior to compressor start.
•Contain POE oil which readily absorbs potentially
damaging
•Control box includes a phase monitor to detect phase
loss,
Refer to previous IOM versions for R-407C and R-22 units,
or contact your localTrane representative.
Refer to the appropriate IOM for air-cooled condenser
CXRC-SVX01 and programming Intellipak controls PKGSVP01.
moisture from air.
line voltage imbalance and reversal.
Copyright
This document and theinformation in it are the propertyof
Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
Trane.Trane 3-D, Intellipak, Integrated Comfort,Traq,
TOPSS, Frostat and theTrane logo are trademarks ofTrane
in the United States and other countries.
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
SCXF-SVX01K-EN (02 Jul 2014)
Update for fan wheel project.
Overview
Note: One copy of this document ships inside the control
panel of each unit and is customer property. It must
be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for air cooled systems. By
carefully reviewing the information within this manual
and following the instructions, the risk of improper
operation and/or component damage will be minimized. It
is important that periodic maintenance be performed to
help assure trouble free operation. A maintenance
schedule is provided at the end of this manual. Should
equipment failure occur, contact a qualified service
organizationwith qualified, experienced HVAC technicians
to properly diagnose and repair this equipment.
SCXF-SVX01K-EN3
SCXF-SVX01J-EN (23 Oct 2012)
Updated fan motor FLA data.
Table of Contents
Warnings, Cautions and Notices .......... 2
Introduction ........................... 3
Model Number Descriptions .............. 6
Self-Contained Ship-With Accessory Model
Number
.............................. 8
Remote Air-Cooled Condenser Model Number
Description
........................... 8
General Data ............................ 9
Signature Series Self-Contained Unit Components
................................. 9
Unit Nameplate .................... 10
General Data ......................... 11
Pre-Installation ......................... 17
Receiving ............................ 17
Contractor Installation Responsibilities .. 17
Unpackaging ......................... 18
Dimensions & Weights .................. 19
Airside Economizer ................... 26
Service Clearances .................... 27
Installation - Mechanical ................ 28
Unit Handling Procedure .............. 28
Installation Preparation ................ 29
Unit Vibration Isolator Option .......... 29
Duct Connections ..................... 30
Plenum .............................. 30
Airside Economizer Installation ......... 31
Water Piping ......................... 32
Condenser Connections .............. 32
Condensate Drain Connections ........ 32
General Waterside Recommendations . . 32
Water Piping Verification ............. 33
Hydronic Coil Installation .............. 33
Refrigerant System ................... 33
Interconnecting Piping ............... 34
Preliminary Refrigerant Charging ...... 35
Installation - Electrical ................... 37
Unit Wiring Diagrams ................. 37
Supply Power Wiring ................. 37
Selection Procedures .................. 38
Static Pressure Transducer Installation (VAV
units only)
Standard with All IntelliPak Units .......40
............................39
Zone Sensor Options for IntelliPak™ Control
Units
.................................40
CV and VAV Unit Zone Sensor Options . .41
Integrated Comfort™ Systems Sensors for CV
and VAV Applications
B = STD plenum w/ factory-cut holes
C = Low plenum w/ factory-cut holes
E = Std plenum w/ field-cut holes
F = Low plenum w/ field-cut holes
H = STD plenum double wall w/ field-cut
holes
J = Low plenum double wall w/ field-cut
holes
K = Extended height plenum w/factorycut holes, ship separate
L = STD plenum w/factory-cut holes,
ship separate
M =Low plenum w/factory-cut holes,
ship separate
N = Extended height plenum w/field-cut
holes, ship separate
P = STD plenum w/field-cut holes, ship
separate
R = Low plenum w/field-cut holes, ship
separate
T = Extended height double-wall plenum
w/ field-cut holes, ship separate
U = STD double-wall plenum w/field-cut
holes, ship separate
V = Low double-wall plenum w/field-cut
holes, ship separate
W =STD double-wall (perf) plenum
w/field-cut holes (90-110 ton only)
X = Low double-wall (perf) plenum
w/field-cut holes (90-110 ton only)
Y = Extended height double-wall (perf)
plenum w/field-cut holes, ship
separate (90-110 ton only)
0 = None
Digit 14 - MotorType
2 = ODP motor
3 = TEFC motor
Digit 15, 16 - Motor HP
05 = 5 hp
07 = 7.5 hp
10 = 10 h p
15 = 15 hp
20 = 20 hp
25 = 25 hp
30 = 30 hp
40 = 40 hp
50 = 50 hp (400V, 460V, 575V only)
60 = 60 hp (90-110 ton only)
A = Steam coil
B = Hot water coil
C = Electric heat, 1 stage
D = Electric Heat (2 Stage)
F = Hydronic heat ctrl interface
G = Elec. heat ctrl interface, 1 stage
H = Elec. heat ctrl interface, 2-stage
(90-110 ton only)
J = Elec. heat ctrl interface, 3 stage
(90-110 ton only)
K = Steam coil ship separate, LH
L = Hot water coil ship separate, LH
1 = Timeclock
2 = Interface For remote HI (IPCB)
3 = Dirty filter switch
4 = 1 and 2
5 = 1 and 3
6 = 2 and 3
7 = 1, 2 and 3
0 = None
Digit 33 - Control Interface
Options
A = Generic BAS Module; 0-5 VDC
(GBAS)
B = Ventilation Override Module (VOM)
D = Remote Human Interface (RHI)
G = GBAS and VOM
H = GBAS and RHI
J = VOM and RHI
M =GBAS, VOM, and RHI
N = BACnet Communications Interface
(BCI)
P = BCI and GBAS
Q = BCI and VOM
R = BCI and RHI
T = BCI and GBAS and VOM
U = BCI and GBAS and RHI
V = BCI and VOM and RHI
W= BCI and GBAS and VOM and RHI
0 = None
1 = Lontalk Comm5 Interface (LCI)
2 = LCI and GBAS
3 = LCI and VOM
4 = LCI and RHI
5 = LCI and GBAS and VOM
6 = LCI and GBAS and RHI
7 = LCI and VOM and RHI
8 = LCI and GBAS and VOM and RHI
A = Non-coated aluminum
C = Protective coating aluminum
Digit 14 - Unit Isolators
0 = None
A = Spring isolators
B = Isopads
Digit 15 - Panels
0 = None
1 = Louvered panels
Digit 16 - Agency Listing
0 = None
U = With UL listing
8SCXF-SVX01K-EN
General Data
Signature Series Self-Contained
Unit Components
Commercial self contained units are complete HVAC
systems used infloor-by-floor applications. Units are easy
to install because they feature a single point power
connection, factory installed and tested controls, single
water point connection, factory installed options, and an
internally trapped drain connection.
See Figure 1, p. 9 and Figure 2, p. 10 for typical unit
components.
The hermetically sealed scroll compressor motors utilize
internal motor protection and time delays to prevent
excessive cycling.
Water-cooled units have 2-6 refrigerant circuits and ship
with a full refrigerant and oil charge. Each circuit includes
filter drier, pressure relief valve, sight glass/moisture
indicator, thermal expansion valve with sensing bulb and
and tube type with an internal subcooler. Condensers are
available as mechanically or chemically cleanable.
Air-cooled units have two circuits and ship with oil and a
dry nitrogen holding charge.Therefore, air-cooled units
require field piping refrigerant connections to an aircooled condensing unit and charging. Each circuit includes
filter drier (field installed), sight glass/moisture indicator,
thermal expansion valve with sensing bulb and external
equalizing line, discharge line schrader valve, suction line
schrader valve, high and low pressure cutout switches,
discharge line check valve and liquid line solenoid valve.
All units includeliquid line servicevalves for each circuitas
standard (suction and discharge service valves are
optional).
Evaporator fans are double width, double inlet and
forward curved with fixed pitch belt drive assembly.
Variable frequency drives are optional. EISA efficiency
open drip proof (ODP) and totally enclosed fan cooled
(TEFC) motor options are available.
external equalizing line, discharge line schrader valve,
suction line schrader valve and high and low pressure
cutout switches.The water-cooled condensers are shell
Figure 1.IntelliPak™ commercial self-contained signature series unit components
Waterside economizer
(cleanable option shown)
Sight glasses with
ports for viewing
while unit is running
Unit mounted microprocessor
control with easy-to-read human
interface panel
Swing out VFD panel with
Tri-VFD for efficient VAV
operation
2-inch flat filter
box inside unit
casing
Internally trapped
drain for low cost
installation
Waterside valve
package option
to enhance system
efficiency
Two-bolt connection on
cleanable condenser for
quick, easy maintenance
Standard Controls
Standard controls supplied with the unit include the
human interface (HI) panel with unit control module
(UCM). All basic setup parameters are preset from the
factory.
SCXF-SVX01K-EN9
Human Interface Panel
The HI isunit mounted and accessible without openingthe
unit’s front panel. It allows easy setpoint adjustment using
the HI keypad. In addition,the HI displaysall unit operating
parameters and conditions in a clear language display,
Trane 3-D® Scroll Compressor
for reliability, efficiency and
quiet operation
General Data
which can be configured for either English, French, or
Spanish.
The optional remote human interface (RHI) will control up
to four self-contained units, each containing an
interprocessor communications bridge (IPCB). It has all
the same features as the unit-mounted HI except for the
service mode.
For more information on setpointdefaults and ranges and
unit programming, see the IntelliPak™ Self-ContainedProgramming Guide, PKG-SVP01*-EN. A copy ships with
each unit.
Figure 2.Right side view of unit
Optional Controls
Optional controls include a disconnect switch, dirty filter
switch, water flow switch (water-cooled only), supply air
temperature reset, or external setpoint inputs. Daytime
heating is available on units with electric, steam, or hot
water heat control options. Morningwarm-up operation is
available on all units.
The static pressure probe, zone night heat/morning warm-
up, supply air temperature reset sensor options ship
separate inside the unit control panel for field installation.
For more detailed information on the unit control options,
see the Owner’s section of this manual.
Unit Nameplate
The unit nameplate identifies the unit model number,
appropriate service literature, and wiring diagram
numbers. It is mounted on the left end of the unit control
panel.
Unit Control Module
The UCM provides “smart” unit control with safety
features and control relays for pumps, dampers, etc.The
Signature Series IntelliPak self-contained unit is controlled
by a microelectronic control system that consists of a
network of modules.These modules are referredto as unit
control modules (UCM). In thismanual, the acronym UCM
refers to the entire control system network.
These modules perform specific unit functions using
proportional/integral control algorithms.They are
mounted in the unit control panel and are factory wired to
their respective internal components. Each module
receives and interprets information from other unit
modules, sensors, remote panels, and customer binary
contacts to satisfy the applicable request; i.e.,
economizing, mechanical cooling, heating, ventilation.
See the Owner’s section of this manual for a detailed
description of each module’s function.
10SCXF-SVX01K-EN
General Data
General Data
Table 1.SCWF/SIWF Water-cooled self-contained, 20 to 42 tons
Rows4 or 624 or 634 or 66666
Sq. Ft.38.5749.0949.0949.0949.0949.0956.8156.8156.81
FPF144144144144144144144144144
Condenser Data
Min gpm w/o Econ648484102102112140168168
Min gpm w/ Econ648484102102112
Maximum gpm142186186226226248300350350
Evaporator Fan Data
Quantity111111111
Diameter (in.)25252527.527.527.527.527.527.5
Minimum hp7.57.57.5101010151515
Minimum kW(5.59)(7.46)(7.46)(7.46)(7.46)(7.46)(11.19)(11.19)(11.19)
Maximum hp304040505050606060
Maximum kW(22.37)(37.29)(37.29)(37.29)(37.29)(37.29)(44.74)(44.74)(44.74)
Min Design cfm119601425015080169001870020800175001750017500
Max Design cfm195502210024650276252980029800350003500035000
Note: This table depicts compressor location in unit, plan view from left
corner.
SCXF-SVX01K-EN15
General Data
Table 9.Filter data, water-cooled units models SCWF &
SIWF
Unit Size20- 38T40-85T90-110T
Number - Size (In.)8 - 20x1812 - 25 x 2015 - 24 x 24
4 - 20 x 20 6 - 20 x 203 - 24 x 12
Units With Hot Water Or
Steam
Number - Size (In.)4 - 16x204 - 25 x 20
4 - 20 x 20 2 - 20 x 20
4 - 18 x 208 - 25 x 16
4 - 20 x 16
n/a
Table 10. Filter data, air-cooled units models SCRF &
SIRF
Unit size20- 35 tons40-60 tons
Number - Size (in.) 8 - 20x1812 - 25 x 20
4 - 20 x 20 6 - 20 x 20
Units With Hot Water Or Steam
Number - Size (in.) 4 - 16x204 - 25 x 20
4 - 20 x 20 2 - 20 x 20
4 - 18 x 208 - 25 x 16
4 - 20 x 16
Table 11.Self-Contained Heating Coil
Unit Size
Steam Coil
Coil TypeNSNSNSNS
Rows1111
No./Size (in.) (2) 24 x 58 (2) 30 x 81 (2) 24 x 58 (2) 30 x 81
No./Size (mm)
FPF42424242
Hot Water
Coil
Coil Type5W 5W 5W 5W
Rows 1 or 2
No./Size (in)(2) 24 x 58 (2) 30 x 81 (2) 24 x 58 (2) 30 x 81
No./Size (mm)
FPF80 or 10880 or 10880 or 10880 or 108
Notes:
1. Hot water and steam heating coils have Prima-Flo® fins without
turbulators.
2. For coil capacities, use TOPSS™ (Trane Official Product Selection
Program).
3. Full capacity coils consist of two coils stacked and piped in parallel.
20 - 38
(2) 609.6 x
1473.2
(2) 609.6 x
1473.2
SCWF
SCWF
42 - 80
(2) 762 x
2057.4
(2) 762 x
2057.4
SCRF
20 - 35
(2) 609.6 x1
473.2
(2) 609.6 x
1473.2
SCRF
40 - 60
(2) 762 x
2057.4
(2) 762 x
2057.4
Table 12. Waterside economizer coil physical data - SCXF
Unit Size Type Rows FPF
20, 22 & 25
20, 22 & 25
20, 22 & 25
20, 22 & 25
29 & 32
29 & 32
29 & 32
29 & 32
35 & 38
35 & 38
35 & 38
35 & 38
42 & 46
42 & 46
42 & 46
42 & 46
52, 58, 65, 72,
80, 85
52, 58, 65, 72,
80, 85
52, 58, 65, 72,
80, 85
52, 58, 65, 72,
80, 85
90, 100 & 110
Chemically
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Chemically
Cleanable
Mechanical
Cleanable
Mechanical
Cleanable
21084078.5
21084078.5
41084078.5
41084078.5
21085578.5
21085578.5
41085578.5
41085578.5
210857.578.5
210857.578.5
410857.578.5
410857.578.5
214455101
214470101
414455101
414470101
214470101
214470101
414470101
414470101
414470119.3
Height
(in)
Length
(in)
16SCXF-SVX01K-EN
Pre-Installation
Receiving
Receiving Checklist
Complete following checklist immediately after receiving
shipment to detect any shipping damage.
•Inspect individual cartons before accepting. Check for
rattles, bent carton corners, orother visible indications
of shipping damage.
•If a unit appears damaged, inspect it immediately
before
accepting the shipment. Make specific
notations concerning the damage on the freight bill.
Do not refuse delivery.
•Inspect the unit for concealed damage before it is
stored
and as soon as possible after delivery. Report
concealed damage tothe freight linewithin the allotted
time after delivery. Check with the carrier for their
allotted time to submit a claim.
•Do not move damaged material from the receiving
location.
reasonable evidence that concealed damage did not
occur after delivery.
•Do not continue unpacking the shipment if it appears
damaged.
crate.Take photos of damaged material if possible.
•Notify the carrier’s terminal of the damage
immediately
immediate joint inspection of the damage by the
carrier and consignee.
Notify yourTrane representative of the damage and
arrange
damage before making any repairs to the unit.
Ship-Separate Accessories
Field-installed sensors ship separately inside unit’s main
control panel. Extra filters, sheaves, and belts ship in unit’s
fan motor section. Condenser plugs, spring isolators, and
isopads ship in unit’s bottom left side.
It is the receiver’s responsibility to provide
Retain all internal packing, cartons, and
by phone and mail. Request an
for repair. Have the carrier inspect the
Contractor Installation
Responsibilities
Complete the following checklist before beginning final
unit installation.
•Verify the unit size and tagging with the unit
nameplate.
•Make certain the floor or foundation is level, solid, and
ficient to support the unit and accessory weights.
suf
Level or repair the floor before positioning the unit if
necessary.
•Allow minimum recommended clearances for routine
maintenance
unit for shaft removal and servicing. Refer to unit
submittals for dimensions. See also “Service
Clearances,” p. 27.
•Allow three fan diameters above the unit for the
disc
harge ductwork. Return air enters the rear of the
unit and conditionedsupply air dischargesthrough the
top.
•Electrical connection knockouts are on the top, left side
of
the unit.
•Allow adequate space for piping access and panel
val. Condenser water piping, refrigerant piping,
remo
and condensate drain connectionsare on the lower left
end panel.
Note: Unit
using vibration isolators. The unit height may
increase up to 5 7/8” with spring type isolators.
•Electrical supply power must meet specific balance
and
voltage requirements as described in section
“Installation - Electrical,” p. 37.
•Water-cooled unitsonly:The installer is responsible for
pro
viding a condenser main, standby water pump,
cooling tower, pressure gauges, strainers, and all
components for waterside piping. See “Water Piping,”
p. 32 for general waterside recommendations.
•Air
-cooled units only:The installer is responsible for
providing and installing the remote air-cooled
condenser and refrigerant piping, including filter
driers.
and service. Allow space at end of the
height and connection locations will change if
SCXF-SVX01K-EN17
Pre-Installation
Unpackaging
Commercial self-contained units ship assembled with
protective coverings over thecoil and discharge openings.
Figure 3, p. 18 illustrates a typical shipping package.
Figure 3. Typical unit shipping package
Shipping Cover
Unit Protective Covers
Remove shipping protection coverings from human
interface panel (HI) at control panel, filter box (or air inlet
opening), discharge air opening, and optional variable
frequency drive (VFD).
Supply Fan Isolators
Remove the shipping channels and mounting bolts from
beneath the fan. See Figure 4, p. 18. Open both fan
compartment access doors to access the channels. There
Figure 4. Fan assembly shipping spacer locations
are four mounting points for 20-38 ton units and six
mounting points for 40-80 ton units.
Note: For 20-38 ton units, do not remove the fan
assembly shipping blocks and tie down bolts if the
fan speed is 750 rpm or less.
While keeping the fan mounting frame level, turn the fan
isolator height adjusting bolts until the fan housing Pgasket compresses 1/4” against the roof transition piece.
See Figure 4, p. 18.
Isolator Height
SCWF 40-80 &
SCRF 60 Only
Adjusting Bolt
SCWF 40-80 &
SCRF 60 Only
18SCXF-SVX01K-EN
Dimensions & Weights
Table 13. Unit Weights - SCWF/SCRF/SIWF/SIRF - lb (kg)
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in unit dropping and
possibly crushing operator/technician which could
result in death or serious injury and possible
equipment or property-only damage.
1. Use spreader bars to avoid unit damage.
2. Spreader bar must be a minimum of 11 feet for 20-85
ton units and 12 feet for 90-110 tons. Chains must not
bear on top of unit.
3. Do not use hooks to lift unit. Do not hook into open
channels
detail inFigure 3, p. 18 and Figure 17, p. 28.
4. Lift using overhead crane only. Adjust rigging for unit
center of
5. Unit center of gravity will fall within center of gravity
block
6. See unit nameplate for unit weights.
7. Do not stack units.
to lift unit. Loop chain through lifting lug. See
gravity.
at various locations depending on unit options.
Table 23. Gravity Block Dimensions 20-80 tons, in.
Unit SizeABC
20-35253238
42-80333450
Figure 17.Detail of how to loop chain through lifting
lug on self-contained
Figure 18. Gravity block location and dimensions for 20-80 ton units
28SCXF-SVX01K-EN
Figure 19. Gravity block location and dimensions for 90-110 ton units
Installation - Mechanical
Installation Preparation
Before installing the unit, perform the following
procedures to ensure proper unit operation.
1. Position the unit and skidassembly inits final location.
2. Test lift the unit to determine exact unit balance and
stability before hoisting it to the installation location.
See “Unit Handling Procedure,” p. 28 for proper
rigging procedures and cautions.
3. Remove the skids from under the unit. See Figure 3,
p. 18. Refer to the “Skid Removal” section. If you find
internal damage, file a claim immediately to the
deli
vering carrier.
4. Remove the protective shipping covers from the unit.
5. Verify isolators are properly tightened for operation.
e “Unit Vibration Isolator Option,” p. 29.
Se
6. Tighten compressor isolator mounting bolts.Torque to
8 ft. lbs. (+ 2 ft. Lbs.)
1
Unit Vibration Isolator Option
Important: Vibration isolation is not necessary for the
unit since the factory internally isolates the
fan and compressors, thus creating double
isolation.Trane strongly recommends that
you consult a vibration specialist when
considering double isolation.In general,
Trane does not recommend double-
isolation.
If job requirements dictate unit isolators, use a housedspring isolator with a locating pin. Factory-provided unit
isolators are type CP and indicate the spring number on
the outer housing.See Figure 20, p. 29. Set the spring-type
vibration isolators inposition before completing electrical,
piping, or duct connections.The 20-38 ton units require
four isolators per unit, and the 40-80 ton units require six
isolators per unit. Reference the isolator placement sheet
that ships with the isolators to indicate proper placement.
Unit Isolator Installation Procedure
Follow the procedure below to install isolators:
1. Position the isolators under the unit base referring to
the isolator placement sheet that ships with the unit
isolators. Lift one end of the unit at a time to position
the isolators. Fasten the isolators to the floor using
anchor bolts.
2. Level the unit by adjusting the isolator heights. Unit
weight
isolators to rest on the lower housing. Maintain
clearances between 1/4 and 1/2”.To increase the
clearance, lift the unit off the isolator and turn the
leveling bolt counterclockwise. Verify that the unit is
level and the housing clearances are correct.The
maximum allowable difference between isolator
heights is 1/4”. Shim as required under the isolators.
Note: The unit is equipped with a positively sloped drain
pan to help indoor air quality (IAQ) and does not
require one corner of the unit to be pitched.
CP-1) for unit isolation
SCXF-SVX01K-EN29
Installation - Mechanical
Duct Connections
Return air enters the rear of the unit and conditioned
supply air discharges through the top. Attach supply air
ductwork directly to the unit’s top panel, around the fan
discharge opening. A duct collar is not provided.
Note: Units equipped with flexible horizontal discharge
plenum option may include a duct collar when
holes are factory cut. If discharge openings are
field-cut, refer to the “Plenum Installation” section.
Install all airducts according to the National Fire Protection
Association standards for the “Installation of Air
Conditioning and Ventilation Systems other than
ResidenceType (NFPA 90A) and ResidenceType Warm Air
Heating and Air Conditioning Systems (NFPA 90B).
Make duct connections to the unit with a flexible material
such as heavy canvas. If a fire hazard exists,Trane
Figure 21. Duct connection recommendations
Discharge
Duct
3-inch
Flexible
Duct
3 Fan
Diameters
Return
Air
recommends using Flexweave 1000, type FW30 or
equivalent canvas. Use three inches for return duct and
three inches for discharge duct. Keep material loose to
absorb fan vibration.
Note: Compressors and fan assembly are internally
isolated. External isolation devices (spring
mounting isolators) are at discretion of a vibration
specialist consulted by building or HVAC system
designer.
•If using return ductwork to the unit, secure it with three
inches of flexible duct connector.
•Extend discharge duct upward without change in size
direction for at least three fan diameters.
or
•Use 3” flexible duct connection on discharge
ductwork.
Run the ductwork straight from the opening for a minimum of
three
fan diameters. See Figure 21, p. 30. Extend remaining
ductwork as far as possible without changing size or direction.
Do not make abrupt turns or transitions near the unit due to
increased noise and excessive static losses. Use elbows with
splitters or turning vanes to minimize static losses.
Poorly constructed turning vanes may cause airflow generated
noise. Align the fan outlet properly with the ductwork to
decrease noise levels in the duct and to increase fan
performance.To complete trunk ductwork to the VAV terminal
units, refer to the VAV box manuals for specific requirements.
Check total external static pressures against fan characteristics
to be sure the required airflow is available throughout the
ductwork.
To achieve maximum acoustical performance, minimize the
duct static pressure setpoint
Plenum
Figure 22. Correct plenum insulation placement
Before installing plenum, attach insulation strip that ships
with plenum. See Figure 22, p. 30 for proper insulation
location. Align plenum front with control panel side of
unit. Using strips and screws provided, secure plenum to
unit.Treat field-cut holes to prevent fiberglass from
entering the airstream.
Note: Plenum insulation must be applied properly to
prevent air bypass around the plenum. See
Figure 22, p. 30.
Dashed line indicates correct insulation placement.
30SCXF-SVX01K-EN
Plenum Bottom View
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.