Trane Ice Bank Operation Manual

Installation and Operation Manual
Ice Bank® Energy Storage
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
August 2020
IB-SVX186B-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
CAUTIONs
NOTICE
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handli ng of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situatio result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
n which, if not avoided, could
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, flash, techni with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
all PPE required for the work being
refer to the appropriate SDS and OSHA/GHS
cians MUST put on all PPE in accordance
or
© 2020 Trane IB-SVX186B-EN
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Trane personnel must follow the company’s E
nvironm when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
Non-Trane personnel should always follow local regu
ental, Health and Safety (EHS) policies
lations.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Introduction
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Updated for Trane Technologies.
IB-SVX186B-EN 3
Introduction
This technical guide is written to provide a complete and comprehensive procedure for the installation of Ice Bank® Energy Storage tanks. It is not the intent of this guide to exclude sound and proven methods of installation by contractors who have, through experience, developed an efficient method of installation expertise.
All work must be performed in a
ccordance with LOCAL, STATE and NATIONAL codes. After reading this manual, if any questions arise, please call your local representative or CALMAC® Applications Engineering Department at (201) 797-1511 or e-mail info@calmac.com.
1. GENERAL
a. Module Description. Th
e storage module consists of a plastic tank full of water (ice in the charged state) in which a specially designed heat exchanger is immersed. The heat exchanger consists of a coiled mat of plastic tubes, which are spaced evenly throughout the entire volume of water. The unique spiral counterflow configuration allows ice to build up evenly throughout the tank without tank damage. An empty space is provided above the heat exchanger for expansion of water during freezing.
are
b. Model Types. The tank model num
bers appended with suffixes to specify different configurations. The complete model number can be found on the rating plate located on the tank cover adjacent to the connections.
c. Damage in Transit. Up
on receipt of the shipment of this equipment, inspect all tanks and packages for external damage. If external damage is noted, mark the
number of damaged items and the nature of the damage on the delivering carrier’s waybill and request the services of an inspector.
Since all materials are sold FOB factory, it is the responsibili
ty of the consignee to file claims with the delivering carrier for equipment received in damaged condition. Normally, claims for any and all damages should be filed with the freight company within five working days of the receipt of shipment.
2. SITE LAYOUT
oor Loading. When filled with water the tanks
a. Fl
are quite heavy. Consequently the structure supporting the tanks must be capable of bearing this weight. Refer to
Table 1 for the filled weight of each
tank model and required floor loading strength. The plastic bottom of the tank must be level (¼ inch /6 mm) over the tank diameter and supported over its entire area. For all “C” Model tanks (See Section
Step ii) the adjoining tanks must be on a
continuous level surface.
b. Partial Burial. Partiall
y burying the
tanks in the ground is permissible as long as one foot of the tank protrudes above ground level. The tanks must be installed on a concrete pad which is level and completely supports the bottom of the tank. (See Specifications for Partially Buried Ice Bank® tanks, #CS-3).
ll Burial. Tanks sitting on a concrete pad may be
c. Fu
pl aced i n a pit. A l ayer of sand th en woo d ch ips or top soi l may cover the tanks. (See the Installation Manual for Totally Buried Ice Bank Ice Storage Tanks, #IB-152 for more information).
Table 1. Weight, loading strength and ove
Tank
Model
Number
1045A 58 0 ( 265 ) 43 8 0 ( 198 6 ) 14 7 ( 718 ) 24 ( 6 1) Yes 40 ( 1 52) 13 ( 4 9) 16 ( 4 7 5 )
1082A 10 2 5 ( 465 ) 84 5 5 ( 383 5 ) 28 3 ( 1 382 ) 2 4 (61 ) Yes 78 ( 295 ) 26 ( 98) 16 ( 4 75)
1098A 12 2 5 ( 555 ) 10 , 1 00 ( 4 5 80 ) 234 ( 1 1 42) 2 4 ( 61) Ye s 90 ( 3 41) 30 ( 1 14) 16 ( 4 7 5)
1105A 12 7 5 ( 580 ) 10 , 7 60 ( 488 0 ) 36 0 ( 175 8 ) 36 ( 9 1 .5) Yes 99 ( 375 ) 3 3 ( 1 25) 16 ( 4 75)
1190A 19 5 0 ( 885 ) 16 , 7 65 ( 760 5 ) 38 8 ( 189 4 ) 36 ( 9 1 .5) Yes 14 8 ( 560 ) 5 0 ( 1 89) 16 ( 4 75)
1045C 620 ( 2 8 0) 450 5 ( 2 045 ) 15 1 ( 737 ) 24 ( 61) Ye s 47 ( 1 78) 1 6 ( 6 1) 16 ( 4 7 5)
1082C 10 6 5 ( 485 ) 85 8 0 ( 389 0 ) 28 6 ( 139 6 ) 2 4 ( 61) No 8 6 ( 3 26) 29 ( 1 10) 16 ( 4 75)
1098C 12 7 5 ( 580 ) 10 , 2 35 ( 464 5 ) 23 7 ( 115 7 ) 2 4 ( 61) No 99 ( 3 75) 33 ( 1 2 5) 16 ( 475 )
1105C 13 1 5 ( 595 ) 10 , 7 60 ( 488 0 ) 36 3 ( 177 2) 36 ( 9 1 .5) No 1 0 7 ( 405 ) 3 6 ( 1 36) 16 ( 4 75)
1190C 20 0 0 ( 910 ) 16 , 9 00 ( 766 5 ) 39 1 ( 190 9) 36 ( 9 1 .5) No 157 ( 594 ) 5 2 ( 197 ) 16 ( 475 )
1220C 262 5 ( 1 190 ) 23, 0 0 0 ( 10, 4 3 3) 53 1 ( 259 3) 36 ( 9 1 .5) No 21 0 ( 795 ) 7 0 ( 265 ) 16 ( 475 )
1320C 400 0 ( 1 814 ) 34, 0 0 0 ( 15, 4 2 0) 39 1 ( 1 909 ) 3 6 ( 9 1.5 ) No 31 5 ( 119 2 ) 105 ( 397 )
1500C 600 0 ( 2 721 ) 50, 6 0 0 ( 22, 9 5 0) 39 1 ( 190 9) 36 ( 9 1 .5) No 47 0 ( 1 179 ) 15 5 ( 587 ) 3x 1 6 ( 4x47 5 )
Shipping
Weight-
Lbs. (kg)
Filled Weight-
Lbs. (Kg)
d. Outdoors. Tanks are suitable for outdoor
installation. They must be set on a surface that meets the
rhead clearances
Floor
Loading-
Lbs./Sq..Ft.
(Kg/m2)
Pure Glycol
Overhead
Clearance-
inches
(cm)
Fork Lift
Slots
Required
Coolantgals.
(liters)
Added to
HX-
(Sec IV.D)
gals. (liters)
of the surface may cause the tanks to shift. It is normal for the tank covers to show minor distortions when exposed
Required
Biocideoz.
(ml)
2x 1 6 ( 2x47 5 )
specifications outlined in Section II. A. Settling or erosion
4 IB-SVX186B-EN
Introduction
to the sunlight. These minor distortions will not affect the operation of the tank.
e. Roo
fs. Tanks can be
installed on roofs however they may need to be spaced apart so that maximum structural loading is not exceeded. Follow the instructions of a structural engineer regarding the distribution of the tank floor loading.
f. Service Access. Refer to
Table 1 for the required
overhead clearances for each model tank. No service access is required aro
und the sides of the tank beyond
what is needed for proper headering.
3. TANK INSTALLATION
a. Insu
lation. All tank
models are insulated at the factory and are shipped with integral insulated bases installed.
b. Moving
the Tanks. The tanks are heavy even
when empty and two people, with help of a forklift or crane, are generally required to move them. All standard
rigging procedures and safety rules for lifting heavy objects should be followed at all times even if not detailed in this manual.
i. “A” M
odel Tanks. All have forklift slots
incorporated into their bases to facilitate moving the tanks. Forklifts must have forks or extensions at least 72 inches (1830 mm) in length. Forklift operators must take care not to ram the tanks with their forks when picking the tanks up. This type of handling could puncture or otherwise damage the tanks.
When using a crane to move an “A”
Model tank into position put two 30 foot (9 m) long, 3-inch (75 mm) wide “choker” straps — each 180º apart — around the midsection of the tanks. As the crane starts to lift, the straps will slide up about a foot (300 mm), tighten around the tank, grip and then hold the tank. The tank can then be maneuvered into position.
ii. “C” Model
Tanks. These tanks consist of one,
two or three individual modules which have main headers built into the cover. Models 1320C and 1500C tanks must be rigged into position with a crane and a special rigging bar available from CALMAC®. (A standard spreader bar can be used on the Model 1190C and 1220C). When moved, they must be lifted as a single unit. Each module is equipped with 2 hoist rings. Normally, one rigging bar is shipped with each job. Lifting hooks are provided and packaged separately.
Insert the provided clevis pins through the
ate holes in the rigging bar, capturing the hooks
ropri
app between the steel channels (
Table 2). Lock the clevis pins in place by
Figure 2, Figure 3 and
inserting a cotter pin. Lifting cables should be attached to the rigging bar as shown in
Figure 2 and Figure 3 in accordance with Table 2.
The rigging bar should be placed on top of the ice
k unit
tan
and the lifting hooks secured to the tank hoist
rings.
If either the Model 1320C or Model 1500C Ice Bank
units must b
e temporarily set down, prior to its final placement, it should be placed on a clean, flat and reasonably level surface.
Note: Keep
ing the tanks level an
d preventing them from swinging will assist in maintaining the required uniform spacing between tanks.
4. PLUMBING PROCEDURES
a. General.
There is no preferred inlet or outlet
header connection to the tank.
Flange manufacturers recommend that the 4 inch
ange bo
fl
lts with washers be torqued to no more than 60 ft. lbs (81.4 Nm) and standard tightening pattern be used to prevent leaks or damage to the flanges.
” Model Tanks. The co
i. “A
nnections on Model
‘A’ tanks are 2" flanges.
Note: The standard polyethylene heat exchanger is
limited to 90 Psi (620 kPa) internal pressure. (Special orders to 125 Psi/862 kPa.) If system pressures exceed these limits, a heat exchanger must be used to isolate the storage tanks from the higher pressure. A pressure relief valve must also be installed in the system to assure that pressure does not exceed 90 Psi (620 kPa) for standard heat exchangers and 125 Psi (862 kPa) for special order heat exchangers.
Table 2. Lifting p
Model Pin # for Tanks
13 2 0 1, 2 , 3,4 7, 9
15 0 0 1, 2 , 3,4, 5 , 6 8, 1 0
in destinations
Pin # for lifting
cable
ii. “C” Model Tanks. External pipes must be
located in such a way that the internal header pipes are not pulled from their normal, at rest position. Using flange bolts to pull tank flanges to system piping may cause internal damage.
Models 1320C and 1500C have 4 inch flange
nnections. Model 1190C tanks can be bolted directly to
co each other at the 4 inch flange connection. See and
Figure 4. However, do not connect more
Figure 3
than three Model 1190C tanks directly to each other without an intermediate flexible connection that will allow 3/4 inch to 1 inch (20 to 25mm) of axial motion.
ushing. All field constructed piping systems
b. Fl
shoul
d be flushed thoroughly, before filling with the coolant, to remove weld slag, flux, debris etc. from the piping. It is a good practice at this time to valve off all heat exchange devices that are not protected by a strainer so that small passages do not become plugged. The Ice Bank® tanks should also be valved o ff . I t i s a g oo d p ra ct ic e to carefully monitor the amount of water needed to initially fill the system for flushing. This may be useful for determining the volume of coolant required to fill the system. Remember to add the Ice Bank heat exchanger,
IB-SVX186B-EN 5
Introduction
and any other piping volumes that were isolated from the system in the total system volume. Once the system has
Figure 1. Clevis and Cotter pins
Figure 2. Model 1500C
been thoroughly cleaned, the system should be totally drained of water.
Figure 3. Model 1320C
6 IB-SVX186B-EN
Figure 4. Assembly options for “C” model tanks
Introduction
c. Hydrostatic Testing. Hydrostatic tests are
normally done on all piping systems. If a hydrostatic test is specified before coolant is put in the system, the tanks should not be part of this test and should be valved off. This is because if pure water is pumped into the heat exchanger it cannot be removed. After the successful completion of the test, drain the system and add premixed glycol to the system as described in Section IV.D.2.
If the specifications call for a complete hydrostatic pressure exchangers, completely fill system with glycol/water solution and remove air. Then increase air pressure in the expansion tank up to the hydrostatic test pressure (maximum 150 Psi/1034 kPa). After 30 minutes close
off all valves on each tank and let sit for the prescribed period of time. Monitor system pressure as tank valves are sequentially opened.
tank are recommended to alert operators of a shortage of liquid in the system. Since these systems contain a valuable heat transfer solution, steps should be taken to prevent the loss of the liquid. The tank farm as a whole should be capable of isolation by valves. A twostep alarm, triggered by either low liquid level in the expansion tank or low pressure at the high point of the building, should be installed. The first level of alarm is to alert the operator of routine requirements for the system’s fluid. The second
IB-SVX186B-EN 7
test of the entire system, including tank heat
ressure switches in the expansion
Liquid level and/
or p
level would be for extremely low level/pressure indicating a major leak and should close automatic valves to isolate the tanks and other parts of the system
Make-up systems using city water are not recomm dilute the coolant. If an automatic coolant make-up
system is required, CALMAC® GMS liquid pressurization system, which adds premixed solution is recommended. Indoor installations should have floor drains in accordance with local codes.
position be initially filled with water to approximately 90% of final fill height, or about 6 tubes below the top HX tube. At this time the Biocide should be added to the water. See section IV.D.4. After the tank heat exchangers are filled with coolant, the water level would be brought to the final correct height, just covering the top heat exchanger (HX) tube, except for Model 1220, which is filled to the bottom of the top HX tube. Partially or fully buried tanks
should be filled with water as soon as practically possible to prevent tank flotation, should the burial pit accumulate with water.
ended because adding water alone will
d. Recommended Filling Sequence.
dd Water to Tank. After the tanks are in final
i. A
and plumbed, CALMAC® recommends that tanks
Introduction
C =
C
R S+VIB
VS
ii. Add Heat Transfer Fluid Solution to Heat
Exchanger. The system should be filled with a glycol/
water mixture with a freezing point of about 12ºF (-11ºC)— approximately three parts water to one part ethylene glycol. Refer to
Figure 5. Recesses in the header insulation facilitate the assembly of connecting hardware
Table 1 for amount of coolant required for
each tank model. Houghton Chemical Wintrex, Dow SR-1
equivalent are recommended; automotive anti-freeze is
or not recommended because it contains additives which reduce the life of internal surfaces.
If the tank heat exchangers have been filled with water, perhaps due to a hydrostatic test or system flush (Section IV.C.), an adjustment must be made to the concentration and/or quantity of coolant added to the Pure glycol can be added to the system to account for the water left in the tank heat exchangers. The required quantity can be found in Table 1, (Pure glycol added to water in HX, Gals. (liters). T would then be filled with coolant at the normal concentration. (e.g. Adding 50 gals./189 liters) of concentrated glycol to the 148 gals./560 liters of water in an 1190 HX would result in 198 gals./750 liters) of solution volume at 25.3% glycol concentration).
Alternatively, the concent added to the system can be increased. This procedure may be simpler when coolant is ordered premixed, in bulk. The needed concentration can be calculated approximately from the following:
C = Concentration of added coolant
= System volume, not including tank HX’s
V
s
CR = Final concentration needed by system
= Volume of tank HX’s
V
IB
(Required coolant, Gals. (liters) from
8 IB-SVX186B-EN
he remain
ration of all the coolant to be
remaining
ing system volume
system.
Table 1)
In all large systems there should be a minimum two inch (50 mm) fill connection on the suction side of the pump. The premixed glycol solution should be pumped into this connection. Before starting the filling pump, high points of the system should have the vents open.
Note: Un
When the coolant reaches the vent, ma vent and stop the fill pump. Care must be taken not to over pressurize the system (maximum 90 psi/620 kPa at the tank inlet for standard tanks and 125 psi/862 kPa for special order tanks).
inutes, pr
m flow. Most air will quickly move to the high points. With the system pump off, the vents can be opened and the fill pump can be started again. After repeating this a few times and when most of the air is eliminated, open the valves and run the system pump at full flow. At this point the system’s air eliminator should be able to remove the final amounts of air. When all of the air is out, run the fill pump until the system’s expansion tank is at the proper level and the system is at its proper working pressure (usually 5 psi 35 kPa at the high point of the building).
design pressure. Make sure the system pressure doesn’t drop. If it does, there is a leak in the system.
like when filling with water, these vent locations must be manned at all times during the filling process so that the heat transfer fluid is not inadvertently spilled.
nually close
The system pump can now be turned on for a few
eferably at low speed or valved back to half
Keep circulating coolant through the system
the
at the
Introduction
Use a refractometer or equivalent to test the solution’s glycol concentration after the system has been filled and circulated for 24 hours. If the solution’s glycol concentration is less than 25% or above 12°F (-11.1°C), draw off a sufficient amount of mixture and add pure glycol to achieve a 25% concentration.
ish Adding More Water to Tank. At this
iii. Fin
time, after heat transfer fluid has been added to the heat exchanger, finish filling the tank with water to a height just covering the top heat exchanger (HX) tube, except for Model 1220, which is filled to the bottom of the top HX tube. For water level instructions in MIXAIR tanks, see Installation Manual for MIXAIR Ice Bank® tanks #IB- 158.)
iv. Add W
ater Treatment. Pour in the initial treatment of biocide into the tank water upon filling, into the inspection port. This will help to control
biological growth. CALMAC® recommends a 20% Tetrakis hydroxymethyl phosphonium sulfate solution such as Aquacar PS20. All tank models require 16 oz. of biocide solution per tank.
The CAS number is 555-66-30-8
Note: The cove
r must always be in place whenever the tank is in operation in order to prevent floating of the heat exchanger. You are now ready to freeze the tank(s)!
e. Insu
lation. All piping mu
st be insulated to prevent condensate dripping as well as exposure to sunlight (to prevent ultra-violet degradation). Since these liquid lines run cooler than most chilled water systems the thickness of the insulation may need to be slightly greater than normal to avoid condensation.
5. RECOMMENDED OPERAT
ING TEMPERATURES
The storage system will operate most efficiently if the chiller controls are set to terminate charging at the highest return temperature that will charge the tanks in the available hours. In most cases, with a 6ºF (-14.4°C) temperature difference across the chiller, the average leaving chilled coolant temperature will be approximately 25ºF (-3.9°C) with a 31ºF (-0.6°C) return. Most commonly,
if the chiller unit is set to turn off when the coolant temperature leaving the tank reaches 28ºF (-2.2°C) (See project engineers specification for exact temperature.) the tanks will be completely charged.
If the chiller is allowed to run at lower conditions than required the free water above the heat exchanger may freeze causing an “ice cap”. This ice cap will in turn cause a shortage of water during discharge, thereby impairing the discharge performance and wasting energy.
6. REPAIRS AND MAINTENANCE
Note: The cove
r must always be in plac
e whenever the tank contains ice in order to prevent floating of the heat exchanger.
a. Routine Maintenance.
i. Annually. The water
/ice level in the tanks
should be checked at least once a year. (Check Ice Bank®
Ice Storage Operation and Maintenance Manual #IB­SVX147*-EN for complete details). When the tanks are 100% frozen, usually first thing in the morning, there should be approximately 4 to 7 inches (10 to 15 cm) of water above the submerged insulation depending on the tank model. The water level should be within ½ inch (1.27 cm) of the bottom of the tank covers. Add water if this is not the case. (If the tanks are not fully frozen, adding water may cause the tanks to overflow when fully charged, which will not hurt the tanks however, it may cause flooding of the area).
At the end of the cooling season, you should fully charge the tanks and leave
them frozen until the start of your next
air-conditioning season.
d with
If the tank is equippe
an inventory meter sensor, altering the water level may require re-calibration of the meter. Refer to “Ice Inventory Meter Installation and Operation Manual”, #IB-153.
The coolant should be checked annually for proper
on and
corrosi
freeze protection. This service should be
available from the glycol manufacturer.
ii. Tank Water Tr
eatment. Generally, if tanks are
kept at least partially frozen year round, provide retreatment with biocide as needed. However, if tanks are not kept frozen year round, retreatment may be required more often and the tanks should be checked for slime or odor seasonally.
b. Warranty Repairs. Auth
orization for in-warranty field repairs must be obtained in writing from CALMAC® before any repairs are attempted.
Note: To find
out more about Ice Bank
®
energy storage
visit calmac.com or trane.com/energystorage
IB-SVX186B-EN 9
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
IB-SVX186B-EN 07 Aug 2020
Supersedes IB-SVX186A-EN (Jun 2019)
©2020 Trane
Loading...