Trane HUV Installation and Maintenance Manual

Installation, Operation, and Maintenance
Horizontal Unit Ventilator
Models HUVC
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
January 2013 UV-SVN02C-EN
“C” and later Design Sequence 750 cfm—2000 cfm
SAFETY WARNING

Warnings, Cautions, and Notices

Warnings, Cautions, and Notices. Note that
warnings, cautions, and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNI NG
ATT EN TI ON : Warnings, Cautions, and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of arc or flash, technicians MUST put on all PPE in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow instructions could result in death or serious injury.
WARNI NG
Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non­approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.
© 2013 Trane All rights reserved UV-SVN02C-EN
WARNING
R-410A Refrigerant under Higher Pressure than R-22!
Some of the units described in this manual uses R-410A refrigerant which operates at higher pressures than R-22 refrigerant. Use ONLY R-410A rated service equipment or components with this unit. For specific handling concerns with R-410A, please contact your local Trane representative.
Failure to use R-410A rated service equipment or components could result in equipment or components exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
WARNING
Hazard of Explosion!
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage.
Warnings, Cautions, and Notices
Trademarks
ComfortLink, Rover, Tracer, Tracer Summit, Trane, and the Trane logo are trademarks or registered trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE); Echelon, LonTalk, and L trademarks of Echelon Corporation; Energizer is a registered trademark of Eveready Battery Company, Inc.; National Electrical Code, National Fire Protection Association, and NEC are registered trademarks of the National Fire Protection Association.
UV-SVN02C-EN 3
ONWORKS are registered
Table of Contents
Model Number Descriptions . . . . . . . . . . . . . . 6
General Information . . . . . . . . . . . . . . . . . . . . . 8
Unit Description . . . . . . . . . . . . . . . . . . . . . 8
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unit Ventilator Controls . . . . . . . . . . . . . . 10
ECM Application Notes . . . . . . . . . . . . . . . . . . 12
Dimensions and Weights . . . . . . . . . . . . . . . . 13
Unit Location and Clearances . . . . . . . . . 13
Receiving and Handling . . . . . . . . . . . . . . . . . 19
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . 20
Jobsite Inspection . . . . . . . . . . . . . . . . . . 20
Jobsite Storage . . . . . . . . . . . . . . . . . . . . 20
Installation—Mechanical . . . . . . . . . . . . . . . . 21
Location Considerations . . . . . . . . . . . . . . . 21
Unit Mounting . . . . . . . . . . . . . . . . . . . . . . . 21
Horizontal Recessed Mounting . . . . . . . . 21
Installation—Piping . . . . . . . . . . . . . . . . . . . . . 23
Trane Piping Packages (Option) . . . . . . . 23
Split System Units . . . . . . . . . . . . . . . . . . 23
Refrigerant Piping . . . . . . . . . . . . . . . . . . 23
Steam Piping . . . . . . . . . . . . . . . . . . . . . . 24
Modulating Water Valves (Option) . . . . . 24
Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Manual Opener . . . . . . . . . . . . . . . . . . . . . 26
Isolation Valves . . . . . . . . . . . . . . . . . . . . . . 26
Installation . . . . . . . . . . . . . . . . . . . . . . . . 26
Servicing/Removal of Valves . . . . . . . . . . 26
Heating Coils with Direct Expansion Cooling
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Installation—Sensors . . . . . . . . . . . . . . . . . . . 28
Control Options . . . . . . . . . . . . . . . . . . . . . . 28
Installing Wall-Mounted Wired Sensors . 29
Location Considerations . . . . . . . . . . . . . 30
Location Considerations for Wireless Zone
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Fan Mode Switch Installation . . . . . . . . . 30
Zone Sensor Installation . . . . . . . . . . . . . 30
Wireless Sensors . . . . . . . . . . . . . . . . . . . . . 31
Address Setting . . . . . . . . . . . . . . . . . . . . 31
Observing the Receiver for Readiness to As-
sociate . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Associating the Sensor to the Receiver . .32
Testing Signal Strength and Battery Status
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Configuring the Wireless Display Sensor
(Model WDS only) . . . . . . . . . . . . . . . . . . .34
Sensor Operations . . . . . . . . . . . . . . . . . . .36
Wireless Sensor Specifications . . . . . . . . . 39
Installation—Electrical . . . . . . . . . . . . . . . . . . .41
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Electrical Wiring . . . . . . . . . . . . . . . . . . . . .41
Electric Heat Units . . . . . . . . . . . . . . . . . . . 41
Heating Coils with Direct Expansion Cooling
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
ECM Overview and Setup . . . . . . . . . . . . . . . . 43
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
General Information . . . . . . . . . . . . . . . . . . .43
Trane BLDC Motor . . . . . . . . . . . . . . . . . . .43
ECM Engine Controller . . . . . . . . . . . . . . .43
Standard Adapter Board . . . . . . . . . . . . . .44
CSTI Adapter Board . . . . . . . . . . . . . . . . . .44
Installation and Initial Setup . . . . . . . . . . . .45
Installation and Initial Setup . . . . . . . . . . .45
Adjustment and Configuration of the Engine
Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
Status Display . . . . . . . . . . . . . . . . . . . . . . .48
Initial Setup and Configuration . . . . . . . . .53
Configuration . . . . . . . . . . . . . . . . . . . . . . . . .53
Configuring the ECM Engine Controller . .53
Configuring the ECM Engine Board . . . . .58
Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
Setting the Time Clock . . . . . . . . . . . . . . . .63
Wired Controllers—Communication Wiring 65
Wiring Installation (Tracer ZN520) . . . . . . .65
Device Addressing . . . . . . . . . . . . . . . . . . .65
Recommended Communication Wiring Prac-
tices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65
Wiring Installation (Tracer UC400) . . . . . . .65
Wiring Overview Outline . . . . . . . . . . . . . .66
4 UV-SVN02C-EN
General Instructions . . . . . . . . . . . . . . . . . 66
BACnet MS/TP Link . . . . . . . . . . . . . . . . . 66
Power Supply . . . . . . . . . . . . . . . . . . . . . . 67
Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Pre-Start-up Checklist . . . . . . . . . . . . . . . 69
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Tracer ZN520 Unit Startup . . . . . . . . . . . . 70
Tracer UC400 Unit Startup . . . . . . . . . . . 70
General Information . . . . . . . . . . . . . . . . . 70
Fan Mode Switch Operation . . . . . . . . . . 70
Tracer ZN520 Operation . . . . . . . . . . . . . 70
UC400 Controller Operation . . . . . . . . . . 71
Tracer ZN520 Sequence of Operation . . . 71
Cooling Operation (Tracer ZN520) . . . . . 72
Fan Mode Operation (Tracer ZN520) . . . 73
UC400 Sequence of Operation . . . . . . . . . 78
Power-up Sequence (UC400) . . . . . . . . . 78
Random Start (UC400) . . . . . . . . . . . . . . . 78
Occupancy Modes (UC400) . . . . . . . . . . . 78
Timed Override Control (UC400) . . . . . . 79
Zone Temperature Control (UC400) . . . . 79
Discharge Air Tempering (UC400) . . . . . 80
Heating or Cooling Mode (UC400) . . . . . 80
Entering Water Temperature Sampling Func-
tion (UC400) . . . . . . . . . . . . . . . . . . . . . . . 80
Fan Operation (UC400) . . . . . . . . . . . . . . 80
Exhaust Control (UC400) . . . . . . . . . . . . . 81
Valve Operation (UC400) . . . . . . . . . . . . . 81
Modulating Outdoor/Return Air Damper
(UC400) . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Two-position Control Of A Modulating Out-
door Air Damper (UC400) . . . . . . . . . . . . 83
Electric Heat Operation (UC400) . . . . . . . 83
Dehumidification Operation (UC400) . . . 83
Peer-to-peer Communication (UC400) . . 83
Unit Protection Strategies (UC400) . . . . . 83
Removal of the Drain Pan . . . . . . . . . . . . .85
Removal of the Fanboard and Coil Cleaning
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Lubrication: Fan Shaft . . . . . . . . . . . . . . . .86
Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
Modulating Valves (3-Wire Floating) . . . .87
Preventive Maintenance . . . . . . . . . . . . . . . .87
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Troubleshooting Checklist . . . . . . . . . . . . .88
Output Testing and Diagnostics (Tracer ZN520)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
Output Testing and Diagnostics (UC400) . .93
Output Testing (UC400) . . . . . . . . . . . . . . .93
Diagnostics (UC400) . . . . . . . . . . . . . . . . . 93
Troubleshooting (Wireless Controls) . . . . .94
Troubleshooting (Tracer ZN520) . . . . . . .100
Troubleshooting (UC400) . . . . . . . . . . . .101
Troubleshooting (ECM) . . . . . . . . . . . . . .103
General Information (ECM) . . . . . . . . . . .104
Troubleshooting Information (ECM) . . .104
Replacing ECM Components . . . . . . . . . . . .106
Circuit Modules Replacement Notes/Work In-
structions . . . . . . . . . . . . . . . . . . . . . . . . .107
Softsetting the IMC Address of an ECM En-
gine Module . . . . . . . . . . . . . . . . . . . . . . . 107
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . .109
Wallboxes . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
General Instructions . . . . . . . . . . . . . . . . .109
Installation in Masonry Walls . . . . . . . . .111
Installation in Curtain Walls . . . . . . . . . .111
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Service Access . . . . . . . . . . . . . . . . . . . . . 85
Periodic Maintenance . . . . . . . . . . . . . . . 85
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
UV-SVN02C-EN 5

Model Number Descriptions

Digit 1, 2, 3 — Unit Configuration
HUV = Horizontal Unit Ventilator
Digit 4 — Development Sequence
C = Third Generation
Digit 5, 6, 7 — Development Sequence
075 = 750 CFM 100 = 1000 CFM 125 = 1250 CFM 150 = 150 0 CFM 200 = 2000 CFM
Digit 8 — Unit Incoming Power Supply
1 = 120V/60/1 2 = 208V/60/1 3 = 208V/60/3 4 = 240V/60/1 5 = 240V/60/3 6 = 277V/60/1 8 = 480V/60/3-Phase 4-Wire Power
Supply
Digit 9 — Motor
0 = Free Discharge ECM 4 = Free Discharge ECM, Low
Acoustics
7 = Free Discharge ECM, Low FLA
Option
N = Free Discharge, Low Acoustics,
Low FLA A = High Static ECM E = High Static ECM, Low Acoustics H = High Static ECM, Low FLA
Option K = High Static ECM, Low Acoustics,
Low FLA
Digit 10, 11 — Design Sequence
** = Design Sequence
Digit 12, 13 — Coil Letter Designation
(Single Coil Options)
AA = 2 R, 12 FPI CW/HW Changeover AB = 2 R, 16 FPI CW/HW Changeover AC = 3 R, 12 FPI CW/HW Changeover AD = 4 R, 12 FPI CW/HW Changeover AE = 4 R, 16 FPI CW/HW Changeover H1 = 1 R, 12 FPI Heating Coil H2 = 1 R, 14 FPI Heating Coil H3 = 1 R, 16 FPI Heating Coil H4 = 2 R, 12 FPI Heating Coil H5 = 2 R, 14 FPI Heating Coil H6 = 2 R, 16 FPI Heating Coil K1 = 1 R Low Capacity Steam Coil K2 = 1 R High Capacity Steam Coil E4 = 4 Element Heating Only Coil E6 = 6 Element Heating Only Coil E8 = 8 Element Heating Only Coil G0 = 2 R, 12 FPI DX Coil
(Coupled Coil Options)
DA = 1 R, 12 FPI HW Coil with 2 R,
12 FPI CW Coil
DC = 1 R, 12 FPI HW Coil with 2 R,
14 FPI CW Coil
DD = 1 R, 12 FPI HW Coil with 3 R,
12 FPI CW Coil
DE = 1 R, 14 FPI HW Coil with 3 R,
14 FPI CW Coil DK = 1 R Steam with 3 R CW Coil X3 = 3 Element Elec Coil with
3 R CW Coil (2 R on Sz 125) X4 = 4 Element Elec Coil with
3 R CW Coil (2 R on Sz 125) X6 = 6 Element Elec Coil with
3 R CW Coil (2 R on Sz 125) GK = 1 R Steam Coil with 2 R DX Coil GA = 1 R Heating coil with 2 R DX Coil G3 = 3 Element Elec Heat Coil with
2 R DX Coil G4 = 4 Element Elec Heat Coil with
2 R DX Coil G6 = 6 Element Elec Heat Coil with
2 R DX Coil R1 = 3 R, 12 FPI CW Coil with 1 R,
12 FPI HW Coil R2 = 3 R, 14 FPI CW Coil with 1 R,
12 FPI HW Coil
Digit 14 — Coil Connections
A = Right Hand Supply B = Left Hand Supply C = Left Hand Cool/Right Hand Heat D = Right Hand Cool/Left Hand Heat
Digit 15 — Control Types
0 = Unit-Mounted Speed Switch Q = Tracer™ ZN520 R = Tracer ZN520 w/Low Temp T = Tracer ZN520 w/Time Clock U = Tracer ZN520 w/Low Temp &
Time Clock X = Tracer ZN520 ICS w/Fan Status Y = Tracer ZN520 ICS w/Low Temp &
Fan Status 8=CSTI 9 = CSTI w/Low Temp L = Tracer UC400 M = Tracer UC400 w/Time Clock
Digit 16 — Heating/Change Over Coil Control
0=None 1 = Face & Bypass Damper Actuator 2 = 2-Pipe Face & Bypass Damper
Control 3 = 4-Pipe Face & Bypass Damper
Control & Isolation Valve 4 = Single Stage Electric Heat
Control 5 = Dual Stage Electric Heat 7 = Face & Bypass Damper w/2-Pipe
Control & Isolation Valve 9 = 2-Way 1/2-in. 3.3 CV; 3-Wire Mod W = 2-Way 1/2-in. 1.9 CV; 3-Wire Mod G = 2-Way 3/4-in. 4.7 CV; 3-Wire Mod H = 2-Way 1-in. 6.6 CV; 3-Wire Mod Z = 3-Way 1/2-in. 1.9 CV; 3-Wire Mod Q = 3-Way 1/2-in. 3.8 CV; 3-Wire Mod R = 3-Way 3/4-in. 6.6 CV; 3-Wire Mod T = Steam: 3-Wire Mod 1/2-in. 1.9 CV U = Steam: 3-Wire Mod 1/2-in. 4.7 CV V = Steam: 3-Wire Mod 3/4-in. 8.6 CV
Digit 17 — Cooling Coil Control
0=None 1 = Single Stage DX Controls A = Field-Supplied Analog Valves W = 2-Way 1/2-in. 1.9 CV; 3-Wire Mod G = 2-Way 3/4-in. 4.7 CV; 3-Wire Mod H = 2-Way 1-in. 6.6 CV; 3-Wire Mod Z = 3-Way 1/2-in. 1.5 CV; 3-Wire Mod Q = 3-Way 1/2-in. 3.8 CV; 3-Wire Mod R = 3-Way 3/4-in. 6.6 CV; 3-Wire Mod
Digit 18 — Damper Configuration
0 = Field Installed Damper Actuator 1 = 100% Return Air/No Damper or
Actuator
(Modulating ASHRAE Cycle II)
F = RA/OA Damper and Actuator
(2–10 Vdc) A = RA/OA Damper and Actuator
(3-Point Modulating) E = RA/OA Damper and Actuator
with Exhaust (3-Point Mod)
(Two Position Control)
D = Damper w/Manual Quad Adjust
6 UV-SVN02C-EN
Model Number Descriptions
Digit 19 — Zone Sensor/Fan Speed Switch
0 = No Sensor - Unit Mounted Fan
Speed Switch
J = Wall Mt Zone Sensor (OALMH;
Setpoint Dial; On/Cancel)
K = Wall Mt Zone Sensor (OALMH;
Setpoint Dial)
L = UNIT Mt Zone Sensor (OALMH;
Setpoint Dial)
M = Wall Mount Display Sensor
w/Setpoint Adjust
P = Wall Mt Sensor (Setpoint dial;
On/Cancel) w/Unit-Mt Speed Switch
Q = Wall Mt Sensor (Setpoint Dial)
w/Unit Speed Switch
3 = Wireless Display Sensor
(H-L-A-O)
4 = Wireless Sensor - Ext Adjust
Digit 20 — Inlet Arrangement
A = FA Duct Top/RA Duct Lower Back B = FA Duct Top/RA Duct Bottom C = FA Duct Top/RA Bar Grille
Bottom D = FA Duct Top/RA Open Bottom E = 100% FA Duct Top F = FA Duct Upper Back/RA Duct
Lower Back G = FA Duct Upper Back/RA Duct
Bottom H = FA Duct Upper Back/RA Bar
Grille Bottom J = FA Duct Upper Back/RA Open
Bottom (no grille) K = 100% FA Duct Upper Back L = 100% RA Duct Lower Back M = 100% RA Duct Bottom N = 100% RA Bar Grille Bottom P = 100% RA Open Bottom (no grille)
Digit 21 — Discharge Arrangement
1 = Bar Grille Discharge 2 = Duct Collar Discharge 7-1/8 in.
from Top 3 = Duct Collar Discharge 3/4 in.
from Top 4 = Duct Collar Discharge 3-5/8 in.
from Top 5 = Front Double Deflection Grille
Discharge 6 = Front Double Deflection Opening
Only (no grille) 7 = Bottom w/Double Deflection
Grille
Digit 22 — Unit Access Panel
0 = Std. Horizontal Access Panel 1 = Safety Chain/Std. Access Panel 2 = Removable Access Panel 3 = Safety Chain/Removable
Access Panel
Digit 23 — Recessing Flange
0 = No Recessing Flange 1 = Standard Recessing Flange
Digit 24 — Piping Package
0 = No Factory Installed Piping
A = Package 1; Standard Package C = Package 2; Standard Package
D = Package 3; Standard Package
Package
w/Circuit Setter
w/Strainer and Circuit Setter
Digit 25 — Filter
1 = Throwaway Filter 2 = MERV 8 Filter 3 = MERV 13 Filter
Digit 26 — Color Selection
1 = Deluxe Beige Cabinet 2 = Cameo White Cabinet 3 = Soft Dove Cabinet 4 = Stone Gray Cabinet 5 = Driftwood Gray Cabinet
Digit 27 — Motor Disconnect
0 = No Disconnect A = Non-Fused Toggle B = Circuit Breaker
Digit 28 — Control Accessories
0=None A= C0 B = Wall Mounted Relative Humidity
2
Sensor
Sensor
UV-SVN02C-EN 7

General Information

Unit Description

Configuration. This classroom unit ventilator is
configured in a horizontal (ceiling mount) configuration. The units range from 750 cfm to 2000 cfm for the horizontal configuration.
Cabinet. The units are constructed of 14- and 16-gauge
zinc coated steel. All steel surfaces are cleaned, phosphatized, rinsed and dried before application of final finish paint. The paint is applied by an electrostatic powder spray system, minimum thickness of 1.5 mil which results in an appliance grade finish.
Front Panels. The front panels are retained by Allen
wrench operated locks which open with a 180-degree rotation.
The bottom panel is constructed of heavy gauge material.
End Pockets. Unit Ventilators are equipped with end
pockets to provide field installation of valves, piping, and controls. The units have a large pipe access opening in both end pockets and large knockouts for piping and electrical connections. All electrical connections are made in the left-hand end pocket, with exception of units equipped with the electric heating coil option.
Drain Pan. The drain pan is positively sloped in all planes
to assure proper drainage and help eliminate the risk of microbial growth. To help ensure indoor air quality, the drain pan is insulated on the bottom to help prevent condensate formation. The drain pan can be easily removed for cleaning purposes. The drain pan is drilled­out and pitched toward the cooling coil connection during assembly per model number selection.
are permanently lubricated. Motors are capable of starting at 50 percent of rated voltage and operating at 90 percent of rated voltage on all speed settings. Motors can operate up to 10 percent over voltage.
Filter. Standard units are equipped with a single 1-inch
thick filter (MERV 8) that is accessible without removal of the unit front panel. Filter options include throwaway, MERV 8 and MERV 13 options.
OA/RA Damper. Trane unit ventilators are equipped
with dual blade type mixing damper to ensure proper modulation and mixing of return and outdoor air designed in accordance to ARI 840. A splitter is placed between the damper blades to separate the fresh-air and return-air compartments to prevent draft blow-through.

Options

OA/RA Actuator (Option). The OA/RA actuator
provides true spring return operation for positive close-off of the OA/RA damper. The spring return system of the actuator closes the outside damper if power is lost to the building. When ordered with factory mounted controls, the actuator is 3-point floating. A 2 to 10 Vdc actuator is also available when other than Trane controls is required. See Ta b l e 1 , p . 8 for technical data of the OA/RA actuator.
Table 1. Technical data for OA/RA actuator
Fanboard. The fanboard assembly is acoustically
designed in a single, rigid assembly that includes the fans, fan housing, bearings, fan shaft and motor. The fan motor is mounted on the fanboard. The fanboard is made from 14-gauge galvanized steel to resist corrosion and increase strength.
Electrically Commutated Motor (ECM). All motors
are brushless DC (BLDC)/electronically commutated motors (ECM) factory-programmed and run-tested in assembled units. The motor controller is mounted in a control box with a built-in integrated user interface and LED tachometer. If adjustments are needed, motor parameters can be adjusted through momentary contact switches accessible without factory service personnel on the motor control board.
Motors will soft-ramp between speeds to lessen the acoustics due to sudden speed changes. Motors can be operated at three speeds or with a field-supplied variable speed controller. The motor will choose the highest speed if there are simultaneous/conflicting speed requests.
All motors have integral thermal overload protection with a maximum ambient operating temperature of 104°F and
8 UV-SVN02C-EN
Power Supply 24 Vac ±20% 50/60Hz
24 Vac ±10% Power Running: 2.5W Consumption Holding: 1W Transformer Sizing 5VA (class 2 power source) Overload Electronic throughout Protection 0- to 95-degree rotation Control Signal 2–10 Vdc 3 point floating w/ Trane controls Rotation Angle 95-degree max. Adjustable w/mechanical stop Torque 35-inch/lb Rotation Direction Spring return reversible w/CW/CCW mounting Position Indication Visual indicator, 0- to 95-degrees Noise Level Running: 30dB
General Information
Face and Bypass (Option). The face and bypass option
consist of an actuator, damper blade and 2-position water valve (option).
During bypass mode, the damper moves to prevent air from traveling through the coil. The damper blade is tightly sealed to eliminate heat pickup while in the full bypass mode.
A two-position isolation valve control (option) further enhances this system by closing off all water flow to the coil during full bypass operation. Two-pipe main steam systems utilize the face and bypass as part of the standard operation and may incorporate the optional isolation valve.
Face and Bypass Actuator (Option). The face and
bypass damper actuator incorporates a direct couple design for the horizontal configurations. The actuator is provided with electronic protection against overload. It does not contain, nor require a limit switch. When reaching the damper end position, the actuator automatically stops. The gears can be manually disengaged with a button on the actuator housing. See Tab l e 2 for technical data.
Table 2. Technical data for face and bypass actuator
The actuator on the valve is a 24V, 3-point floating type. See Ta b l e 3 , p . 9 for more technical data.
Table 3. Technical data for modulating water valves
Power Supply 24V - 50/60 Hz Power Consumption 4W Maximum Duty Cycle 15% Operating Ambient Temperature 0°C to 65°C
32°F to 150°F
Min./Max. Fluid Temperatures 1°C to 95°C
34°F to 203°F Operating Pressure Differential Max. - 4 bar (60 psi) Pressure Rating Static - 20 bar (300 psi)
Burst - 100 bar (1500 psi) Flow Characteristics Linear
Power Supply 24 Vac ±20% 50/60Hz
24 Vac ±10% Power Consumption 2W Transformer Sizing 3VA (class 2 power source) Manual Override External push button Control Signal 3-point floating w/Trane controls Rotation Angle 95-degree max. Adjustable w/mechanical stop Torque 35-inch/lb Rotation Direction Reversible with switch L/R Position Indication Clip-on indicator Noise Level Less than 35dB
Modulating Water Valves (Option). The modulating
control valve option provides optimum control of hot and chilled water flow in various heating and cooling applications. They are designed to provide sinusoidal valve actuator travel and operate silently, resisting water hammer.
Isolation Valves (Option). The isolation valves are two
position 24V, spring return type. They provide added control in heating and cooling applications when used in conjunction with the face and bypass damper.
On heating coils and two-pipe change-over applications, the valve is a normally open type to prevent the coil from freezing in case of power loss.
For cooling, the valve is normally closed and opens when there is a call for cooling. See Table 4, p. 10 for more technical data.
UV-SVN02C-EN 9
General Information
Table 4. Technical data for isolation water valves
Power Supply 24V - 50/60 Hz Power Consumption 5W Max. Fluid Temp. 200°F / 94°C Min. Fluid Temp. 34°F / 1°C Max. Operating Pressure 300 psi Max. Close-off Pressure 1/2 in.= 30 psi
3/4 = 20 psi 1 = 15 psi

Unit Ventilator Controls

Options
Field-Installed Controls (Option). The unit comes
equipped with a fan speed switch, damper blade (only), and an optional low temperature detection.
Customer Supplied Terminal Interface (CSTI) (Option).
will incorporate a pre-wired, selected control components to a terminal strip for wiring a field-provided controller and temperature sensor.
Note: For controller operation malfunction of any non-
Tracer ZN520 Control Package (Option). The Tracer
ZN520 electronic digital controller is a factory installed, tested and commissioned LonTalk may be used in a stand-alone control scheme, or as part of a building automation system. The controller is pre-wired to Trane selected control components best suited for room comfort. For more information on the Tracer ZN520 unit controller operation and service issues, refer to CNT-SVX04A-EN (Installation, Operation, and Programming Guide: Tracer ZN520 Unit Controller), or the most recent version.
Units containing the end device control design
Trane, field installed controls, consult the literature or technical support of the controls manufacturer.
®
certified design. It
Figure 1. Tracer ZN520 unit controller
Tracer UC400 Control Package (Option). The Tracer
UC400 electronic digital controller is a factory installed, tested and commissioned BACnet Tracer UC400 operates as a single zone VAV controller and ramps fan speed based on space load. It may be used in a stand-alone control scheme, or as part of a building automation system. The controller is mounted, pre-wired, and pre-programmed to selected control components best suited for room comfort. For more information on the Tracer UC400 unit controller operation and service issues, refer to BAS-SVX48B-EN (Installation, Operation, and
10 UV-SVN02C-EN
®
certified design. The
Programming: Tracer UC400 Programmable Controller), or the most recent version.
Figure 2. Tracer UC400 unit controller
When Trane controls are ordered for an installation, the controls are shipped already installed and factory-tested to ensure proper operation at start-up.
Notes:
For more details on the ZN520 unit controller option or
operation and service/replacement issues, please refer to CNT-SVX04A-EN (Installation, Operation, and Programming Guide: Tracer ZN520 Unit Controller), or the most recent version.
For more details on the UC400 unit controller option or
operation and service/replacement issues, refer to BAS-SVX48B-EN (Installation, Operation, and Programming: Tracer UC400 Programmable Controller), or the most recent revision.
General Information
Automatic Controls
Regardless of type of controls, all systems provide a sequence of operation designed to provide rapid warm-up of the room and increase ventilation while offsetting overheating.
In addition, air conditioning installations will usually provide a means of system changeover from heating to cooling as well as provisions for drawing a pr e-determined amount of outside air into the room.
Unit Switch
The unit “On-Off” switch, provided by Trane, is typically housed in the control box mounted in the left hand end pocket immediately below the discharge grille.
When Tracer ZN520 or Tracer UC400 unit controllers are used, the unit switch is located on the switch module in the end pocket behind the front panel rather than below the grille.
UV-SVN02C-EN 11

ECM Application Notes

The new Trane BLDC system has some notable differences to traditional designs.
RPM Mode
The motors are programmed from the factory to run in rpm mode and will not change rpm based on external static pressure, except at the performance limits of the motor/controller. For ducted units, the units are shipped with the rpm set for 0.2 in. ESP for High, Medium, and Low speeds. The speeds can for high, medium, and low operation, but should not be changed for the electric heat actuation speeds.
Generally, the fans deliver less cfm for the same rpm, if the static is increased and the power will decrease. The fan will deliver more cfm for the same rpm, if the static is decreased and the fan power will increase. A unit with high static configuration should not be used to free-deliver air (i.e., with no ducting attached).
Field Power Wiring
Note: This product uses an electronic variable speed
motor control, which includes a line reactor to minimize power line harmonic currents. It is recommended that good wiring practices be followed to manage building electrical power system harmonic voltages and currents to avoid electrical system problems or other equipment interaction.
Performance Boundaries
While the speeds of the fan motors can be adjusted, never program a fan speed higher than 1700 rpm, or lower than 450 rpm. In many cases, units configured for high-static operation will not achieve the desired rpm if the ESP of the unit is too low, or the unit is allowed to “free-discharge.” The ECM engine contains settings that will limit the output power of the motor under these overload conditions. If the motors cannot achieve rpm close to the target for a specific period of time, the unit will disable electric heat and fan­status indicators.
perform the function of a two 3-pole contactors.
Figure 3. Sample arrangement: electric heat relay
Troubleshooting Other Unit Functions
In some cases, the normal or abnormal operation of the BLDC system may interact with other components in the system. Generally, verification of the engine and adapter boards’ wiring and configuration should be checked if there are unexplained abnormalities in other areas of the unit:
1. Valve operation
2. Electric Heat operation
3. Changeover sensor operation
4. Damper operation
5. Condensate overflow switch
A high degree of protection is provided on electric heat
nits. If electric heat fails to actuate, it may be because of
u one of the following events:
1. Fans are failing to meet target speed. If a second motor is not present, all settings for speeds for Motor 2 should be set to 0000.
2. Hot water may be available in the changeover coil.
3. The connection to analogue input 1 on the Tracer ZN controlle
4. Target speeds for motor a. The  parameter may be set incorrectly.
b. The
r may be reversed in polarity.
s may be set too high:
 parameter may be set incorrectly.
MCA/MFS and Power Draw
The Trane BLDC motors have variable output but are shipped at specific settings to deliver proper performance and reliability. The power draw indicated in the catalogue indicates the power consumed when applied properly (as shipped and with the nominal ESP applied). However, the nameplate of the unit indicates the maximum input draw of the motor, as the motor settings can be changed to draw more power.
Electric Heat Relays
For quiet operation, the new BLDC units employ power relays instead of definite purpose contactors for electric heat actuation. The coils of multiple relays are hooked in parallel to simulate a multi-pole contactor, as shown in
Figure 3. In Figure 3, two sets of three relays are used to
12 UV-SVN02C-EN

Dimensions and Weights

Unit Location and Clearances

Locate the unit in an indoor area. The ambient temperature surrounding the unit must not be less than 45°F. Do not locate the unit in areas subject to freezing.
Electrocution and Fire Hazards with Improperly Installed and Grounded Field Wiring!
NOTICE:
Equipment Damage!
Do not locate the unit in areas subject to freezing. Pipes could burst at lower temperature resulting in equipment damage.
Attention should be given to service clearance and technician safety. The unit should contain enough space for service personnel to perform maintenance or repair. Provide sufficient room to make water, and electrical connection(s).
Table 5. Weights and measurements: horizontal unit ventilators
Unit Size 075 100 125 150 200
Unit Length (in.) 70-1/4 82-1/4 94-1/4 106-1/4 106-1/4 Unit Height (in.) 16-5/8 16-5/8 16-5/8 16-5/8 17-5/8 Unit Width (Front Discharge) (in.) 35-5/8 35-5/8 35-5/8 35-5/8 43-1/8 Unit Width (Bottom Discharge) (in.) 48-3/4 48-3/4 48-3/4 48-3/4 57-1/4 Shipping Weight (lb) Filter Size (inches-actual) 41-1/2 x 15-1/4 x 1 53-1/2 x 15-1/4 x 1 65-1/2 x 15-1/4 x 1 77-1/2 x 15-1/4 x 1 77-1/2 x 15-1/4 x 1
(a) Working weight is approximately 10% less than shipping weight. Trane recommends 1/4-inch rods for hanging suspension
(a)
340* 375* 435* 500* 600*
Improperly installed and grounded field wiring poses FIRE & ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. All field wiring MUST be performed by qualified personnel.
Failure to follow these requirements could result in death or serious injury.
A 36-inch clearance at the unit front is sufficient for maintenance and service of the equipment.
WARNING
Table 6. Control methodology
Fan Speed
FSS 3 or infinite CSTI 3 or infinite Tracer ZN520 3 Tracer UC400 Infinite
(a)With a field-supplied 2–10 Vdc controller.
(a) (a)
Table 7. Control sequences
Fan Speeds
(b)
(a)
(b)
(a)
1 1 2 2
DX operation Electric heat operation Sidewall Exhaust ERSA
(a) Fan speed during sequence operation. (b)Unit Ventilator when operating with option.
UV-SVN02C-EN 13
Dimensions and Weights
3"
4"
4"
1 3/4"
10 1/8"
6 1/2"
10 1/2"
32 1/2"
35 5/8"
11"
14 1/2"
16 5/8"
7 1/8"
7 7/8"
B17 1/8"
12 1/8"
13 1/2" 13 1/2"
4 7/8"
2 3/8"
2"-DIA K.O. FOR PIPING
7/8"-DIA K.O.
FOR ELECTRICAL
17 1/8"
A
C
D
F.A. UPPER BACK
R.A. LOWER BACK
BACK VIEW SIDE VIEW
TOP VIEW
NOTE:
WHEN ELECTRIC HEAT IS PRESENT, ALL POWER CONNECTIONS ARE MADE IN THE RIGHT HAND END POCKET. ON ALL OTHER CONFIGURATIONS, POWER CONNECTIONS ARE MADE IN THE LEFT HAND END POCKET.
ISO VIEW
7/8" x 2" SLOTS FOR HANGING BRACKETS
RIGHT HAND END POCKET
LEFT HAND END POCKET
DISCHARGE
Figure 4. Horizontal unit ventilator with ducted front discharge dimensional data; sizes 075–150 (dimensions in
inches)
Size A B C D
75 70-1/4 36 46 43-1/4 100 82-1/4 48 58 55-1/4 125 94-1/4 60 70 67-1/4 150 106-1/4 72 82 79-1/4
14 UV-SVN02C-EN
Dimensions and Weights
4"
5"
5"
2 3/4"
10 1/8"
7 1/2"
11 1/2"
39 1/2"
26 1/2"
43 1/8"
13 1/2"
15 1/2"
17 5/8"
6 1/8"
9 7/8"
72"17 1/8"
12 1/8"
13 1/2" 13 1/2"
4 7/8"
2 3/8"
2"-DIA K.O. FOR PIPING
7/8"-DIA K.O.
FOR ELECTRICAL
17 1/8"
106 1/4"
82"
79 1/4"
F.A. UPPER BACK
R.A. LOWER BACK
BACK VIEW SIDE VIEW
TOP VIEW
ISO VIEW
7/8" x 2" SLOTS FOR HANGING BRACKETS
RIGHT HAND END POCKET
LEFT HAND END POCKET
DISCHARGE
NOTE:
WHEN ELECTRIC HEAT IS PRESENT, ALL POWER CONNECTIONS ARE MADE IN THE RIGHT HAND END POCKET. ON ALL OTHER CONFIGURATIONS, POWER CONNECTIONS ARE MADE IN THE LEFT HAND END POCKET.
72"
Figure 5. Horizontal unit ventilator with ducted front discharge dimensional data; size 200 (dimensions in inches)
UV-SVN02C-EN 15
Dimensions and Weights
3"
6 1/2"
10 1/2"
14 1/2"
B
R.A. LOWER BACK
17 1/8"
4 7/8"
2 3/8"
2"-DIA K.O. FOR PIPING
7/8"-DIA K.O.
FOR ELECTRICAL
17 1/8"
3/4"
7 1/4"
5 1/8"
4"
A
4"
16 5/8"
10 1/8"
32 3/4"
46"
48 3/4"
11"
12 1/8"
13 1/2" 13 1/2"
C
D
BACK VIEW SIDE VIEW
TOP VIEW
NOTE:
WHEN ELECTRIC HEAT IS PRESENT, ALL POWER CONNECTIONS ARE MADE IN THE RIGHT HAND END POCKET. ON ALL OTHER CONFIGURATIONS, POWER CONNECTIONS ARE MADE IN THE LEFT HAND END POCKET.
ISO VIEW
7/8" x 2" SLOTS FOR HANGING BRACKETS
RIGHT HAND END POCKET
LEFT HAND END POCKET
BOTTOM DISCHARGE
B
Figure 6. Horizontal unit ventilator with double deflection discharge dimensional data; sizes 075–150 (dimensions in
inches)
Size A B C D
75 70-1/4 36 46 43-1/4 100 82-1/4 48 58 55-1/4 125 94-1/4 60 70 67-1/4 150 106-1/4 72 82 79-1/4
16 UV-SVN02C-EN
Dimensions and Weights
4"
7 1/2"
11 1/2"
15 1/2"
72"
R.A. LOWER BACK
17 1/8"
4 7/8"
2 3/8"
2"-DIA K.O. FOR PIPING
7/8"-DIA K.O.
FOR ELECTRICAL
17 1/8"
3/4"
9 1/4"
5 1/8"
5"
106 1/4"
5"
17 5/8"
10 1/8"
26 1/2"
53 3/4"
57 1/4"
13 1/2"
12 1/8"
13 1/2" 13 1/2"
82"
79 1/4"
BACK VIEW SIDE VIEW
TOP VIEW
ISO VIEW
7/8" x 2" SLOTS FOR HANGING BRACKETS
RIGHT HAND END POCKET
LEFT HAND END POCKET
NOTE:
WHEN ELECTRIC HEAT IS PRESENT, ALL POWER CONNECTIONS ARE MADE IN THE RIGHT HAND END POCKET. ON ALL OTHER CONFIGURATIONS, POWER CONNECTIONS ARE MADE IN THE LEFT HAND END POCKET.
BOTTOM DISCHARGE
Figure 7. Horizontal unit ventilator with double deflection discharge dimensional data; size 200 (dimensions in
inches)
UV-SVN02C-EN 17
Dimensions and Weights
Figure 8. Supply/return air arrangements for the horizontal unit ventilator
DIGIT 20 = A
FA DUCT TOP w/RA DUCT LOWER BACK
DIGIT 20 = B
FA DUCT TOP w/RA DUCT BOTTOM
DIGIT 20 = C & D
(C) FA DUCT TOP w/RA BAR GRILLE BOTTOM
(D) FA DUCT TOP w/RA OPEN BOTTOM
DIGIT 20 = E
DIGIT 20 = F
FA DUCT UPPER BACK w/RA DUCT LOWER BACK
DIGIT 20 = G
FA DUCT UPPER BACK w/RA DUCT BOTTOM
DIGIT 20 = H & J
(H) FA DUCT UPPER BACK w/RA BAR GRILLE BOTTOM
(J) FA DUCT UPPER BACK w/RA OPEN BOTTOM (no grille)
DIGIT 20 = K
DIGIT 20 = L
100% RA DUCT LOWER BACK
DIGIT 20 = M
100% RA DUCT BOTTOM
DIGIT 20 = N & P
(N) 100% RA BAR GRILL BOTTOM
(P) 100% RA OPEN BOTTOM (no grille)
100% FA DUCT TOP
100% FA DUCT UPPER BACK
18 UV-SVN02C-EN

Receiving and Handling

The unit ventilator is packaged in clear stretch wrap and protective cardboard.
Note: Before unwrapping, make a visual inspection of the
unit for any damage that may have occurred during shipping. All orders are shipped FOB (Freight on Board) from the factory, therefore any claims must be made with the delivering carrier.
Figure 9. Horizontal unit ventilator as shipped
Following visual inspection, carefully begin the following procedures:
1. Carefully remove the stretch wrap and the top cardboard cover.
2. Remove remaining cardboard blocking.
3. Remove the bottom access panel with a 7/32-in. Allen
h.
wrenc
4. Verify nameplate sales order number is correct.
5. Remove shipping bracket from the lower rear corners of the unit and shipping skid. Access to the screws holding unit to the skid is obtained inside the unit.
Figure 10. Shipping skid removal
6. Rotate fan wheels manually. Wheels should move freely and be in proper alignment. Visually inspect the fan area for obstructions or shipping damage.
7. Remove all applicable knock-outs for coil piping and electrical connections
Figure 7, p . 17).
UV-SVN02C-EN 19
(see Figure 5, p. 13 through

Pre-Installation

Jobsite Inspection

Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifications.
3. Visually inspect the exterior shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been completed. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.

Jobsite Storage

This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing.
1. Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect
from the elements.
them
of the unit, for signs of
NOTICE:
Microbial Growth!
Wet interior unit insulation can become an amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth on the interior insulation, the insulation should be removed and replaced prior to operating the system.
3. Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces.
4. Do not stack units.
20 UV-SVN02C-EN

Installation—Mechanical

Location Considerations

Selecting the appropriate location for installing a unit is very important. The following factors should be considered:
1. Ceiling hung design must be of sufficient structure to support the weight of the unit (see Ta bl e 8 for weight data). Figure 5, p. 13 through Figure 9, p. 17 show hanging rod location and placement.
Note: Isolator and suspension rods are to be provided
by the installer. For hanging suspension, Trane recommends 3/8-in. rods.
Ta b l e 8. Typical unit weights
Unit Size lb kg
075 340 154 100 375 170 120 435 197 150 500 227 200 600 272
(a) Weight at time of shipping. Subtract approximately 10% for actual
hanging weight.
2. Service access is gained through the access panels on the bottom of the unit. Sufficient space should be allowed for panel removal. If the hinged panel option is ordered, allow for a swing radius of 14-in.
3. Sufficient free area around both the discharge and wall
ox should be maintained to ensure proper
b ventilation. If any part of the discharge is blocked off, unit performance may be affected. If the wall box is too small on the inlet, water or debris could be pulled into the unit (see Ta bl e 9) for minimum wall box free area requirements).
Table 9. Wall box free area requirements
Unit Size Discharge (in2)Inlet (in
075 232 169 100 296 217 120 364 265 150 430 313 200 576 391
4. Use the shortest and most efficient ductwork possible when ducting the discharge and/or return air grille. Units ordered with a duct collar discharge arrangement are equipped with a 1-in. duct flange.
Note: Ductwork
for ducted units will be provided by
the installer.
5. If installing a split system, refe installation instructions provided with that unit for special location considerations.
(a)
r to the condenser
2
)
Note: M
easurements in Figure 5, p. 13 through
Figure 9, p. 17 do not include adjusted leveling
legs. Adjustment of Leveling legs should be done first. New measurements from the floor should be retaken before installation.

Unit Mounting

The horizontal unit ventilator may be attached directly to the ceiling or suspended from the ceiling by hangers. Hanger rods should be at least 3/8 in. diameter steel to support unit weight, as given in Table 8, p. 21.
WARNI NG
Heavy Objects!
Always lift unit with fork trucks or other special lifting device following the recommended procedures. Failure to properly lift the unit as instructed, could result in death or serious injury.
Install the hanging devices before hoisting the unit. A fork lift or other special lifting device is required to hoist the unit into mounting position.
Protect the unit finish by covering the lifting platform.
To hoist the unit into place, follow the instructions below:
1. Secure 2 x 4s to the lift forks. These two supports must be long enough and spaced properly on the forks to support the unit while it is being lifted and clear the duct flanges on the unit.
2. Tip the unit onto the supports and slide it toward the lift
til the unit weight balances.
un
3. Lift the unit. Once in position, temporarily secure the
nit to the hanger rods or mounting studs with nuts
u and washers.
4. Align the unit with the du alignment, tighten the mounting nuts securely.
5. Recheck the unit alignment and make sure the unit is
.
level
6. Replace all covers, panels and filters the unit.
Note: Un
it must be mounted level. Coils and drain pans inside unit are pitched properly for drainage before shipment.

Horizontal Recessed Mounting

The recessing flange assembly ships in a box separate from the unit. The assembly includes pre-cut flanges, corner transition pieces, mounting screws, filler pieces, and pressure sensitive gaskets. Refer to Figure 11 and
Figure 12, p. 22 for typical horizontal installation.
ct work. When in proper
before starting
UV-SVN02C-EN 21
Installation—Mechanical
Supply Air
G
Access Panel
Recessing Flange
Return Air Inlet Grille
Supply Air Grille
Access Panel
Recessing Flange
Return Air Inlet Grille
Intake Panel
Bottom Front Panel
Discharge Panel
End Cover
Figure 11. Recess flange installation around horizontal
unit ventilator access panel and inlet
rille
Figure 12. Recess flange installation around bottom
and front of horizontal unit
1. Measure and cut the pressure sensitive gaskets to the correct lengths and attach to the flanges.
2. Starting at a corner, attach the top flange with the mounting screws provided.
3. Press the corner transition pieces
onto the end of the flange and attach the adjoining flanges and filler pieces at the bottom of the unit. Work around the unit in this manner until all flanges and corners are installed.
4. Mounting holes are pre-drilled in assembled flanges as a template to drill all 7/32-in. mounting holes in the cabinet.
5. Attach the flange section to
the flanges. Use the
the unit cabinet with the
mounting screws provided.
6. Open and remove the front access panel.
7. Tighten the mounting fastener unit is level.
8. Open the unit access panel and remove the bottom front panel
(see Figure 13, p. 22).
, making sure that the
Figure 13. Horizontal unit ventilator with front panel
removed
9. Hoist the unit onto a forklift and mount in place as described in “Unit Mounting,” p. 21, ensuring the unit is secured and aligned in place, and that the mounting
are tightly fastened.
nuts
Note: Un
it must be mounted level. Coils and drain pans inside the unit are pitched internally for proper drainage.
10. Replace all covers, panels and filters before starting the it.
un
22 UV-SVN02C-EN

Installation—Piping

13-5/8"
3"
Horizontal Unit
Note: Before installation of piping package, the shipping
bracket holding the piping in place, must be removed.
Proper installation of piping is necessary to provide efficient coil operation and to prevent damage during operation. Follow standard piping practices and include all accessories as necessary.
Piping connection knockouts are shown in Figure 5, p. 13 through Figure 9, p. 17. Field connection types and sizes for units without piping packages are listed in Tab l e 10 ,
p. 23.
Table 10. Coil data for field piping
Coil Type Connection Location Field Connection Size
4-pipe chilled water / hot water
2-pipe changeover coil Left or right 7/8 in. OD Hot water only Left or right 7/8 in. OD Steam Left or right 1 in. MPT Chilled water / electric
heat Chilled water / steam Left or right 7/8 in. OD / 1 in. MPT DX Left 7/8 in. suction, 3/8 in. DX / hot water Left cooling / right
DX / steam Left cooling / right
DX / electric heat Left cooling / right
Left or right (opposite ends)
Left cooling 7/8 in. OD
heating
heating
heating
7/8 in. OD / 5/8 in. OD
7/8 in. suction, 3/8 in. / 5/8 in. OD
7/8 in. suction, 3/8 in. / 1 in. MPT
7/8 in. suction, 3/8 in. / NA

Trane Piping Packages (Option)

Trane Standard Piping Package includes a two- or three­way valve with bypass balance valve, ball valves, Pete’s plugs, and unions. A strainer and circuit balancing valve are optional.
All union connections should be tightened in the field. Units are shipped with union connections hand-tightened only in the factory.
Notes:
All connections made in the field should be sweat
connections.
Piping packages are not shipped insulated. Any
insulation should be provided in the field by the installing contractor.

Split System Units

The following refrigerant piping and interconnecting wiring instructions apply to unit ventilators with direct expansion type cooling coils used in conjunction with air­cooled condensing units. Reference must also be made to the condensing unit installation and wiring manuals which are shipped with the condensing unit.
Note: A UL listing mark applied to a unit ventilator does
not apply to any associated refrigerant condensing unit.

Refrigerant Piping

A 3/4-in. OD condensate drain connection is provided on the chilled water supply end of the unit. Attach a flexible condensate drain hose over the drain pan connection and secure with a hose clamp.
Figure 14. Condensate drain pan location
Hazard of Explosion and Deadly Gases!
Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove
WARNING
refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
The drain pan on the horizontal unit is internally pitched. To field reverse, remove the screws and drain pan, rotate
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury.
the pan and reinstall.
After the condensate drain piping has been completed, check water flow to be sure the system properly carries and away all condensate accumulation.
A P-trap is recommended for installations that drain directly into a sewer system. A P-trap is not necessary for operation but will eliminate sewer gas odor.
Unit ventilators with direct expansion cooling are dehydrated and shipped with a dry air holding charge. Connections are “pinched off” at the factory.
To connect the condensing unit lines, cut off the stubouts and swage. The condensing unit lines can then be brought into the swage and brazed. Trane recommends the use of nitrogen purge when brazing refrigerant lines to prevent formation of oxides in the lines.
UV-SVN02C-EN 23
Installation—Piping
Vacuum Equalizer
H= 12" minimum
F&T Trap
See text for sizing
Gravity flow to
vented receiver
Coil
To Condensate
return
Temp. Regulating Valve
Install the refrigerant suction and liquid lines as described in the condensing unit installation instructions. The thermal expansion valve (TXV) is factory-installed on the Unit Ventilator.
Note: The R-410A direct expansion (DX) refrigerant coil
includes a factory-mounted adjustable thermal expansion valve (TXV) set to 90 psig superheat and an equalizing tube.
Piping should be run straight out through the back of the unit. Access piping knockouts are located in the rear panels of the unit, as shown in Figure 5, p. 13 through
Figure 9, p. 17.
Recommended refrigerant line connections for various unit combinations are given in Table 9, p. 21. Typical Superheat Charging Charts are shown in the Trane Service Facts found in the condensing unit section manual. Refrigerant charge weights can also be determined with your local Trane account manager using a valid Trane Selection Program.

Steam Piping

When air, water or another product is heated, the temperature or heat transfer rate can be regulated by a modulating steam pressure control valve. Since pressure and temperature do not vary at the same rate as load, the steam trap capacity, which is determined by the pressure differential between the trap inlet and outlet, may be adequate at full load, but not some lesser load.
There are detailed methods for determining condensate load under various operating conditions. However, in most cases this is not necessary if the coils are piped as shown in Figure 15. Follow the procedure documented in the ASHRAE Systems Handbook, Steam Systems.
actuator 45° counter-clockwise (see Figure 16). The two­way valves are bi-directional flow. The three-way valves can be mixing or diverting (see Figure 17).
Note: The actuator must be removed if soldering is being
conducted near the valve. High heat may cause damage to the actuator’s plastic body/ mechanisms.
On applications without factory-installed piping packages (option), it is important to remove the cartridge assembly from the valve body with the provided tool (see Figure 18,
p. 25).
Figure 16. Remove modulating valve actuator by
pressing in tab (inset) and turning actuator 45° clockwise
Figure 15. Steam piping

Modulating Water Valves (Option)

The actuator on the valve is a 24 V, three-point floating valve. The actuator can be easily removed from the valve body by pressing in on the locking tab and rotating the
24 UV-SVN02C-EN
Installation—Piping
Two-way valve
AB<->B
AB
B
AB<->A
A
AB
Three-way valve
Figure 17. Steam piping: two-way valve (top) and three-
way valve (bottom)
Closed
B
A
Open
A
B
Figure 18. Cartridge removal tool
Use the following steps to complete cartridge assembly removal:
1. Remove valve actuator.
2. Remove the cartridge assembly from the valve body
with the enclosed tool.
3. Solder the valve in accordance with normal soldering
practices.
4. Re-install the cartridge after soldering by tightening til it bottoms out. The top surface of the cartridge
un will be flush with the top edge of the body casting.
Note: D
5. Replace valve actuator and wire in accordance with
instructions
o not over-tighten. Maximum torque is 40
in·lb.
.
UV-SVN02C-EN 25

Plumbing

The valve may be plumbed in any angle but preferably not with the actuator below horizontal level of the body. Make sure there is enough room around the actuator for servicing or replacement.
For use in diverting applications, the valve is installed with the flow water entering through the bottom AB port and diverting through end ports A or B. In mixing applications the valve is installed with inlet to A or B and outlet through AB.
Mount directly to the tube or pipe. Do not grip the actuator while making or tightening plumbing connections. Either hold valve body by hand or attach an adjustable spanner (38 mm/1-1/2”) across the hexagonal or flat faces on the valve body (see Figure 19, p. 26).
Installation—Piping
Figure 19. Proper plumbing technique for modulating
valves

Manual Opener

The manual opener can be manipulated only when in the up position. The A port can be manually opened by firmly pushing the white manual lever down to the midway position and pushing the lever in. In this position, both A and B ports are open. This “manual open” position may be used for filling, venting and draining the system or opening the valve during power failure.
The valve can be closed by depressing the white lever lightly and then pulling the lever outward. The valve and actuator will return to the automatic position when power is restored.
Note: If the valve is powered open, it cannot be manually
closed, unless the actuator is removed.
Figure 20. Proper mounting for isolation valves

Servicing/Removal of Valves

The actuator can be removed from the valve body. Removing the actuator is recommended of soldering is being conducted near the valve.
To remove the actuator:
1. Place the manual operating lever in the Open position
(see Figure 21, p. 26).
Figure 21. Removing isolation valve actuator
Typical floating controller is an SPDT controller with a center-off position. On a change in temperature from the set point, the controller will close the NO or NC contacts, driving the valve to an intermediate position until a further change at the controller.
The valve is set between the limits of the controller to satisfy various load requirements. In the event of power failure, the valve will stay in the position it was in before loss of power. When power is restored, the valve will again respond to controller demand.

Isolation Valves

Installation

The valve can be mounted in any position on a vertical line. If the valve is mounted horizontally, the actuator must be even with or above the center line. Make sure there is enough room to remove actuator cover for servicing. Mount the valve on the tube or pipe.
Note: Make sure the flow through the valve is in the
direction indicated by the arrow stamped on the valve body.
2. Depress the locking button and lift actuator until it
separates from the valve body.
To install the actuator to the valve body:
1. Align the slot on the shaft of the valve with the valve
body notch on side of body (see Figure 22, p. 27).
26 UV-SVN02C-EN
Installation—Piping
Figure 22. Installing isolation valve actuator
2. Install body valve into pipe.
3. Wiring connections may be made either before or after tor installed on body.
actua
4. Place the manual operating leve
OPEN position.
5. Align actuator coupling to slot on the shaf
body and fit the head onto the valve body to ensure the shaft seats correctly (see Figure 22).
6. Press the actuator and valve body until it secures
together
Soldering procedures are as follows:
. Remove actuator as stated earlier.
1
2. Place valves on the pipe. Rotate valve stem so the shaf
slot points at the notch in the side of the body (90O to flow direction). This protects the plug inside the valve by removing it from the seat (see Figure 23).
.
r on the actuator in the
t of the valve

Heating Coils with Direct Expansion Cooling

Heating options for direct expansion cooling in the unit ventilator are hot water, steam or electric heat.
These coils facilitate direct expansion cooling with standard capacities. The supply and return connections are located in the right hand end pocket. Hot water field connections are made with a 5/8 in.\[15.9\] OD male sweated joint, while steam coils have a 1 in.\[25.4\] male pipe thread (MPT) connection (see Tab l e 10 , p . 2 3 ).
Electric heat coils provide a third way to supply heating to the direct expansion cooling. The coil utilizes three to six preheat elements which are factory-wired.
t
Figure 23. Preparation for soldering
3. Sweat the joints, keeping outer surface free from
solder.
Note: Do not use silver solder due to high
temperature requirements.
UV-SVN02C-EN 27

Installation—Sensors

X13790822-04 (wall) X13790855-01 (unit)
X13790492-01 (wall) X13790855-01 (unit)
X13790842-01 (wall) X13651467-02 (comm)
X13790843-01 (unit)
X13511527-01 (wall) X13790849-01 (unit) X13651467-02 (comm)
X13511529-01 (wall) X13790849-01 (unit) X13651467-02 (comm)

Control Options

Figure 24. Wireless temp sensor with display
(SP, OALH, COMM) Digit 19 = 3
Figure 25. Wireless temp sensor
(SP, OALMH, COMM) Digit 19 = 4
Figure 27. Unit mtd temp sensor
(SP, OALH, COMM) Digit 19 = L
Figure 28. Split mtd zone sensor, unit mtd fan speed
switch, and wall mtd setpoint dial with On/Cancel Digit 19 = P
Figure 29. Split mtd zone sensor,
unit mtd fan speed switch, and wall mtd setpoint dial
Figure 26. Wall mtd temp sensor
(SP, OCC/UNOCC, OA, LMH, COMM) Digit 19 = J
28 UV-SVN02C-EN
Digit 19 = Q
Installation—Sensors
X13790841-01 (wall) X13651467-02 (comm)
X13790886-04 (wall) X13651467-02 (comm)
1
2
3
4
5
6
7
8
9
0
-
=
Figure 30. Wall mtd temp sensor
(SP, OALMH, COMM) Digit 19 = K
Figure 31. Wall mtd display temp sensor
(SP, OCC/UNOCC, OALMH, COMM) Digit 19 = M
Figure 32. Wall-mounted wired and wireless zone
sensor dimensions

Installing Wall-Mounted Wired Sensors

Reference the wall-mounted zone sensor dimensions in
Figure 32, p. 29. Position the sensor on an inside wall three
to five feet above the floor and at least 18 inches from the nearest outside wall. Installing the sensor at a lower height may give the advantage of monitoring the temperature closer to the zone, but it also exposes the sensor to airflow obstructions. Ensure that air flows freely over the sensor.
1. 0.31 in
2. TYP R.07 in (R1.9)
3. TYP 0.24 in)
4. 2.9 in
5. 1.08 in
6. 0.12 in
7. 3.39 in
8. 4.68 in
9. 2.48 in
10. 0.6 3 i n
11. 1.45 in
12. 2.62 in
Sensor
When selecting a sensor location, avoid the following:
Areas of direct sunlight
Areas in the direct airstream of air diffusers
Exterior walls and other walls that have a differential between the two sides
Areas that are close to heat sources appliances, concealed pipes, chimneys, or other heat­generating equipment
Drafty areas
Dead spots behind doors, projection screens, or
s
corner
Walls that are subject to high vibration
Areas with high humidity
High traffic areas (to reduce acci tampering)
dental damage or
temperature
such as sunlight,
UV-SVN02C-EN 29
Installation—Sensors
Metal barriers between the receiver and the sensor (for example, plastered walls with metal lathe or metal roof decks)
Thick, solid concrete walls between the receiver and the sensor
Placing the sensor inside metal enclosures
Height Requirements
It is recommended that you mount the back plate a maximum distance of 54 inches above the floor. If a parallel approach by a person in a wheelchair is required, reduce the maximum height to 48 inches.
Note: Consult section 4.27.3 of the 2002 ADA (Americans
with Disability Act) guideline, and local building codes, for further details regarding wheelchair requirements.
Mounting Surfaces
Using the hardware provided, mount the back plate of the sensor to a flat surface such as sheetrock or plaster, or an electrical junction box. The sensor must be mounted plumb for accurate temperature control and to ensure proper air movement through the sensor.
If mounting onto sheetrock or plaster threaded anchors (pre-drilling holes is not usually necessary) and the two M3.5 x 20 mm mounting screws.
For mounting onto an electrical junction box, use the two 6-32 x 3/4 in. screws.
Before beginning installation, consider the location
nsiderations below. Also, refer to the unit wiring
co schematic for specific wiring details and point connections.
, use the plastic

Location Considerations

Avoid mounting the sensor in an area subject to the following conditions:
Dead spots, such as behind do not allow free air circulation.
Air drafts from stairwells, outside doors, or
sectioned hollow walls.
un
Radiant heat from the sun, fireplaces, appliances, etc.
Airflow from adjacent z
Unheated or uncooled spaces behind the controller,
ch as outside walls or unoccupied spaces.
su
Concealed pipes, air ducts, or chimneys in partition
aces behind the controller.
sp
ors or in corners that do
ones or other units.

Location Considerations for Wireless Zone Sensors

Placement of the sensor is critical to proper operation (the receiver is factory mounted on fan-coil units). For most installations, barriers limit proper radio signal strength more than distance. For best radio transmission range and
reliability, mount the receiver and sensor in line of sight. Where this is not possible, try to minimize the number of barriers between the pair of devices. In general, sheetrock walls and ceiling tiles offer little restriction to the transmission range for the sensor is as follows:
Open range: 2,500 ft (packet error rate = 2%)
Usable range: 200 ft
Typical range: 75 ft

Fan Mode Switch Installation

The fan mode switch ships loose inside the unit accessory bag. Follow the steps below to install the fan mode switch.
Items needed:
2 x 4 electrical junction box
1. Remove the brown wire if not using a field-supplied damper.
2. Remove the terminals, cut and strip wires as required
r installation.
fo
3. Level and position a 2 x 4 electrical
4. Follow the instructions given in “Wall-Mounted
Control Interconnection Wiring,” p. 41 and route the
wires as shown in the wiring diagram. R typical wiring diagram or to the unit specific diagram on the unit.
5. Position the fan mode switch over the junction box with the two screws supplied.
junction box.
efer to the

Zone Sensor Installation

Follow the procedure below to install the wired zone sensor module.
1. Note the position of the setpoint adjustment knob and gently pry the adjustment knob from the cover using the blade of a small screwdriver.
2. Insert the screwdriver blade behi of the module and carefully pry the cover away from the base.
3. To mount the sensor back plate:
a. Hold the back plate against the mounting surface
and ma
b. Secure the back plate against the mounting surface
using included hardware.
4. To install the zone sensor module to a standard
nction box:
ju
a. Level and install a 2 x 4-in.
supplied) vertically on the wall.
b. Pull the control wires through the cutout. Attach the
module to the wall using the screws provided.
5. Strip the insulation on the i
0.25-inch and connect to TB1 (for wired sensors).
6. Screw down the terminal blocks (for wired sensors).
7. To replace the cover:
rk the screw locations.
nd the cover at the top
junction box (installer
nterconnection wires back
30 UV-SVN02C-EN
Loading...
+ 82 hidden pages