Trane Horizon OABE, Horizon Series, Horizon OABD, Horizon OAGD, Horizon OAGE Installation, Operation And Maintenance Manual

...
Installation, Operation, and Maintenance
Horizon™ Outdoor Air Unit
Indirect Gas-Fired/Electric Heat and Air Source Heat Pump Models: OABD, OABE, OAGD, OAGE
Important: Proper execution of the tasks outlined in this Installation, Operation, and Maintenance manual
require and assume the technician has been certified as a start up technician for the Horizon Outdoor Air unit. This includes working knowledge of the Tracer TU program.
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
AVERTISSEMENT DE SÉCURITÉ
November 2019
OAU-SVX02F-EN
Introduction
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handli ng of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires !
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
© 2019 Ingersoll Rand OAU-SVX02F-EN
Introduction
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
AVERTISSEMENT
Équipements de protection individuelle (EPI) obligatoires !
En cas d’équipement de protection individuelle inadapté au travail entrepris, les techniciens s’exposent à des risques de blessures graves voire mortelles. Afin de se prémunir d’éventuels risques électriques, mécaniques et chimiques, les techniciens DOIVENT respecter les consignes préconisées dans le présent manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes :
Avant d’installer/réparer cette unité, les techniciens doivent IMPÉRATIVEMENT porter tout l’équipement de protection individuelle (EPI) recommandé pour le travail entrepris (exemples : gants/manchons résistants aux coupures, gants en caoutchouc butyl, lunettes de protection, casque de chantier/antichoc, protection contre les chutes, EPI pour travaux électriques et vêtements de protection contre l es arcs électriques). Consulter SYSTÉMATIQUEMENT les fiches de données de sécurité et les directives de l’OSHA pour connaître la liste des EPI adaptés.
Lors d’une intervention avec ou à proximité de produits chimiques dangereux, consulter SYSTÉMATIQUEMENT les fiches de données de sécurité appropriées et les directives de l’OSHA/du SGH (système général harmonisé de classification et d’étiquetage des produits chimiques) afin d’obtenir des renseignements sur les niveaux admissibles d’exposition personnelle, la protection respiratoire adaptée et les recommandations de manipulation.
En cas de risque d’éclair, d’arc électrique ou de contact électrique avec un équipement électrique sous tension, et AVANT de réparer l’unité, les techniciens doivent IMPÉRATIVEMENT porter tout l’équipement de protection individuelle (EPI) conformément à l’OSHA, à la norme NFPA 70E ou à toute autre exigence propre au pays pour la protection contre les arcs électriques. NE JAMAIS COMMUTER, DÉBRANCHER ou EFFECTUER DE TEST DE TENSION SANS PORTER UN EPI POUR TRAVAUX ÉLECTRIQUES OU UN VÊTEMENT DE PROTECTION APPROPRIÉ CONTRE LES ARCS ÉLECTRIQUES. IL CONVIENT DE S’ASSURER QUE LES COMPTEURS ET ÉQUIPEMENTS ÉLECTRIQUES CORRESPONDENT À LA TENSION NOMINALE PRÉVUE.
OAU-SVX02F-EN 3
Introduction
WARNING
Refrigerant under High Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non­approved refrigerants, refrigerant substitutes, or refrigerant additives.
AVERTISSEMENT
Fluide frigorigène sous haute pression !
Tout manquement aux instructions indiquées ci­dessous peut provoquer une explosion pouvant causer des blessures graves voire mortelles ou des dommages matériels. Le système contient de l’huile et du fluide frigorigène sous haute pression. Avant d’ouvrir le circuit, récupérez le fluide frigorigène pour éliminer toute pression dans le circuit. Consultez la plaque constructeur de l’unité pour connaître le type de fluide frigorigène employé. Utilisez uniquement des fluides frigorigènes, substituts et additifs agréés.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow all proper safe refrigerant handling practices could result in death or serious injury. Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids.
AVERTISSEMENT
Risque d’explosion et gaz mortels !
Le non-respect de toutes les consignes de manipulation des fluides frigorigènes peut entraîner la mort ou des blessures graves.
N’effectuez en aucune circonstance des opérations de brasage ou de soudage sur des conduites de fluide frigorigène ou des composants de l’unité sous pression ou pouvant contenir du fluide frigorigène. Récupérez systématiquement le fluide frigorigène en respectant les directives de la loi américaine sur la propreté de l’air (Agence fédérale pour l’environnement) ou toute autre réglementation nationale ou locale en vigueur. Après la récupération du fluide frigorigène, utilisez de l’azote déshydraté pour ramener le système à la pression atmosphérique avant de l’ouvrir pour procéder aux réparations. Les mélanges de fluide frigorigène et d’air sous pression peuvent devenir combustibles en présence d’une source d’inflammation et provoquer une explosion. La chaleur excessive découlant de travaux de soudage ou de brasage associée à la présence de vapeurs de fluide frigorigène peut entraîner la formation de gaz hautement toxiques et d’acides extrêmement corrosifs.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Ingersoll Rand personnel must follow Ingersoll Rand Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. All policies can be found on the BOS
site. Where local regulations are more stringent than
these policies, those regulations supersede these policies.
Non-Ingersoll Rand personnel should always follow local regulations.
4 OAU-SVX02F-EN
Introduction
AVERTISSEMENT
Respecter les politiques EHS !
Lenon-respect des consignes suivantes peut être à l’origine de blessures graves,voire mortelles.
Tous les membres du personnel du groupe Ingersoll Rand sont tenus de respecter les règles établies par Ingersoll Rand en matière d’environnement, d’hygiène et de sécurité (EHS) lors d’une intervention, notamment en cas de travaux à chaud, de risque d’électrocution et de chute, deprocédures de verrouillage/mise hors service, de manipulation de fluide frigorigène, etc. Toutes les politiques sont disponibles sur le site BOS. Si les réglementations locales sont plus strictes que les règles imposées par le groupe, elles deviennent prioritaires.
Le personnel extérieur au groupe Ingersoll Rand est, quant à lui, systématiquement tenu d’observer les réglementations en vigueur à l’échelle locale.
WARNING
Hazard of Explosion and Deadly Gases!
Failure to follow instructions could result in death or serious injury.
If you smell gas:
1. Open windows.
2. Don’t touch electrical switches.
3. Extinguish any open flame.
4. Immediately call your gas supplier.
AVERTISSEMENT
Risque d’explosion et gaz mortels !
Le non-respect de toutes les consignes de sécurité ci­dessous peut entraîner la mort ou des blessures graves.
Si vous sentez une odeur de gaz:
1. Ouvrez les fenêtres.
2. Ne touches à aucun interrupteur.
3. Éteignez toute flamme nue.
4. Avertissez immédiatement votre fournisseur de gaz.
AVERTISSEMENT
Procédures d’entretien dangereuses !
Une installation, un réglage, une modification, une réparation ou un entretien incorrect peut entraîner des dommages matériels, des blessures ou la mort. Lisez attentivement les instructions d’installation, de fonctionnement et d’entretien avant de procéder à l’installation ou à l’entretien de cet équipement.
WARNING
Hazard of Explosion and Deadly Gases
Failure to follow instructions could result in death or serious injury.
The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous.
AVERTISSEMENT
Risque d’explosion et gaz mortels !
Le non-respect de toutes les consignes de sécurité ci­dessous peut entraîner la mort ou des blessures graves.
Il est dangereux d’utiliser ou d’entreposer de l’essence ou autres liquides ou vapeurs inflammables dans des récipients ouverts à proximité de cet appareil.
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Added French language translations of warnings.
Updated “Installation”, “Startup” and “Unit Weight and Rigging” chapters.
WARNING
Hazardous Service Procedures!
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
OAU-SVX02F-EN 5
Table of Contents
Model Number Descriptions . . . . . . . . . . . . . . 8
General Information . . . . . . . . . . . . . . . . . . . . 11
Overview of Manual . . . . . . . . . . . . . . . . . 11
Model Number Description . . . . . . . . . . . 11
Unit Nameplate . . . . . . . . . . . . . . . . . . . . 11
Compressor Nameplate . . . . . . . . . . . . . . 11
Unit Description . . . . . . . . . . . . . . . . . . . . 11
Indoor Fan Failure Input . . . . . . . . . . . . . 11
Low Pressure Control ReliaTel Control . 11
Refrigerant Circuits . . . . . . . . . . . . . . . . . 11
High Pressure Control ReliaTel Control . 11
Space Temperature / RH Sensor (Optional) 12
High Temperature Sensor . . . . . . . . . . . . 12
Outdoor Air Temperature and Relative Hu-
midity Sensor . . . . . . . . . . . . . . . . . . . . . . 12
Hot Gas Reheat . . . . . . . . . . . . . . . . . . . . . 12
100 Percent Outdoor Air Hood with Damper
and Filters . . . . . . . . . . . . . . . . . . . . . . . . . 12
Modulating Indirect Gas-Fired Burner . . 12
Through the Base Electrical with Disconnect
Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Through the Base Gas Piping . . . . . . . . . 12
Hinged Access Doors . . . . . . . . . . . . . . . . 12
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . 13
First Aid Measures . . . . . . . . . . . . . . . . . . 13
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Clearances . . . . . . . . . . . . . . . . . . . . 13
Unit Clearances, Curb Dimensions, and Dimen­sional Data
OAB Units . . . . . . . . . . . . . . . . . . . . . . . . . 14
Indirect-Fired OAG Units . . . . . . . . . . . . . 16
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Unit Weight and Rigging . . . . . . . . . . . . . . . . 19
Unit Weight . . . . . . . . . . . . . . . . . . . . . . . . 19
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . 22
General Unit Requirements . . . . . . . . . . . 22
OAB and OAG IF Heater Air Inlet Hood and
Flue Assembly Instructions . . . . . . . . . . . .23
Main Electrical Power Requirements . . . .25
Condensate Drain Configuration . . . . . . .25
Hot Water Control Valve Wiring . . . . . . . .25
Chilled Water Connection Size and Location 26
Filter Installation . . . . . . . . . . . . . . . . . . . . .26
Opening the Collapsed Exhaust Damper
Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Field Installed Power Wiring . . . . . . . . . . .28
Main Unit Power . . . . . . . . . . . . . . . . . . . . . .29
Standard Wiring . . . . . . . . . . . . . . . . . . . . .29
Voltage Imbalance . . . . . . . . . . . . . . . . . . .30
Electrical Phasing (Three-Phase Motors) .30
Compressor Crankcase Heaters . . . . . . . .31
Main Unit Display and ReliaTel Controls .31
Field-Installed Control Wiring . . . . . . . . . .31
Control Power Transformer . . . . . . . . . . .32
Controls Using 24 Vac . . . . . . . . . . . . . . . . 32
Controls Using DC Analog Input/Output (Standard Low Voltage Multiconductor Wire) 32
DC Conductors . . . . . . . . . . . . . . . . . . . . . . . .33
Factory-Provided Sensors . . . . . . . . . . . . . .33
Pre-Start Check List . . . . . . . . . . . . . . . . . . . . . .34
System Configuration and Pre-Start . . . . . . .35
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Indirect Gas-Fired Heating Startup . . . . . . .38
Startup Procedure . . . . . . . . . . . . . . . . . . .39
Safety Controls . . . . . . . . . . . . . . . . . . . . . .42
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Monthly Maintenance . . . . . . . . . . . . . . . . . .43
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Supply/Return Air Smoke Detector Mainte-
nance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Cooling Season . . . . . . . . . . . . . . . . . . . . .43
Heating Season . . . . . . . . . . . . . . . . . . . . .43
Condenser Coil Cleaning . . . . . . . . . . . . . .43
Final Process . . . . . . . . . . . . . . . . . . . . . . . . . .45
6 OAU-SVX02F-EN
Performance Data . . . . . . . . . . . . . . . . . . . . . . 47
Superheat and Refrigeration Circuit Data 51
Alarms and Troubleshooting . . . . . . . . . . . . 53
Microprocessor Control . . . . . . . . . . . . . . 53
System Alarms . . . . . . . . . . . . . . . . . . . . . 53
Sensor Failure Alarm Display . . . . . . . . . 53
RTRM Failure Modes . . . . . . . . . . . . . . . . 55
Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
OAU Filter Guide . . . . . . . . . . . . . . . . . . . . . 56
Field Installation of Factory-Provided Sensors
57
Horizon™ Dedicated Outdoor Air Unit Startup Form
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table of Contents
OAU-SVX02F-EN 7
Model Number Descriptions
Digit 1, 2 — Unit Type
OA = Outdoor Air
Digit 3 — Cabinet Size
B = 500 cfm–3000 cfm G = 1250 cfm–7500 cfm
Digit 4 — Major Design Sequence
D = Revision 1 E = Heat Pump
Digit 5, 6, 7 — Normal Gross Cooling Capacity (MBh)
000 = No Cooling 036 = 3 Tons High Efficiency 048 = 4 Tons High Efficiency 060 = 5 Tons High Efficiency 072 = 6 Tons High Efficiency 084 = 7 Tons High Efficiency 096 = 8 Tons High Efficiency 108 = 9 Tons High Efficiency 120 = 10 Tons High Efficiency 144 = 12 Tons High Efficiency 180 = 15 Tons High Efficiency 210 = 17 Tons High Efficiency 240 = 20 Tons High Efficiency 264 = 22 Tons High Efficiency 300 = 25 Tons High Efficiency 360 = 30 Tons High Efficiency
Digit 8 — Minor Design Sequence
A = Vertical Discharge/Vertical Return B = Vertical Discharge/Horizontal
Return
C = Horizontal Discharge/Vertical
Return
D = Horizontal Discharge/Horizontal
Return E = Vertical Discharge/No Return F = Horizontal Discharge/No Return
Digit 9 — Voltage Selection
3 = 208-230/60/3 4 = 460/60/3 5 = 575/60/3
Digit 10 — Reserved for Future Use
Digit 11 — Evaporator Type
0 = No Cooling C = DX 4-Row Interlaced D = DX 6-Row Interlaced F = Glycol/Chilled Water
Digit 12 — Hot Gas Reheat
0=No HGRH 1 = Fin and Tube Modulating 2 = Fin and Tube On/Off 3 = Microchannel Modulating 4 = Microchannel On/Off
Digit 13 — Compressor
0=No Compressors A = Scroll Compressors B = Digital Scroll (1 C = Digital Scroll (1 D = Variable Speed Scroll (1
E = Variable Speed Scroll (1
F = Scroll Compressors w/Sound
G = Digital Scroll (1
H = Digital Scroll (1
J = Variable Speed Scroll (1
K = Variable Speed Scroll (1
Circuit Only)
nd
Circuit)
2
Attenuation Package
w/Sound Attenuation Package
w/Sound Attenuation Package
Only) w/Sound Attenuation Package
nd
Circuit) w/Sound Attenuation
2 Package
st
Circuit Only)
st
and 2nd Circuit)
st
st
and
st
Circuit Only)
st
and 2nd Circuit)
st
Circuit
st
and
Digit 14 — Condenser
0 = No Condenser 1 = Air-Cooled Fin and Tube 2 = Air-Cooled Fin and Tube
3 = Water-Cooled DX Condenser
4 = Air-Cooled Fin and Tube
5 = Air-Cooled Microchannel 6 = Air-Cooled Microchannel
7 = Air-Cooled Microchannel
8 = Water-Cooled DX Condenser
w/Head Pressure On/Off Control
Copper/Steel
w/Head Pressure Variable Speed
w/Head Pressure On/Off Control
Variable Speed
Copper/Nickel
Digit 15 — Refrigerant Capacity Control
0 = No RCC Valve A = RCC Valve on 1 B = RCC Valve on 1 C = ERCC Valve on1 D = ERCC Valve on 1 E = HGBP Valve on 1 F = HGBP Valve on 1
nd
2
Circuit
st
Circuit
st
and 2nd Circuit
st
Circuit
st
and 2nd Circuit
st
Circuit
st
and
Digit 16 — Indoor Fan Motor (IFM)
0 = ECM w/Backward Curved
2 = Belt Drive 3 = Belt Drive w/VFD 4 = Special Motor Option
Plenum Fan
Digit 17 — Indoor Fan Wheel
A = 355 B = 450 X 2 C = 12/9 (Single Belt Drive) D = 12/9 BT (Dual Belt Drive)
Digit 18 — Indoor Fan Motor (hp)
ECM
A = 1 kW 2 hp B = 2 kW 3 hp C = 3 kW 5 hp D = 4 kW 7.5 hp E = 10 hp F = 15 hp
Belt Drive
Digit 19 — Reserved for Future Use
Digit 20 — Heater Type (PRI/SEC)
0 = No Heat A = Indirect-Fired (IF) B = Direct-Fired (DF) C = Electric—4-Stage D = Electric—SCR Modulating E = Dual Fuel (PRI-IF/SEC-DF) F = Dual Fuel (PRI-ELEC/SEC-DF) G = Dual Fuel (PRI-IF/SEC-ELEC) H = Dual Fuel (PRI-ELEC/SEC-ELEC) J = Hot Water K = Steam L = No Primary Heat,
Secondary ELEC
M = Dual Fuel
(PRI-ELEC-STAGED/SEC-DF)
N = Dual Fuel
(PRI-ELEC-STAGED/SEC-ELEC) P = Dual Fuel (PRI-HW/SEC-DF) Q = Dual Fuel (PRI-HW/
SEC-ELEC-SCR) R = Dual Fuel (PRI-STEAM/SEC-DF) S = Dual Fuel (PRI-STEAM/SEC-
ELEC-SCR)
Digit 21 — Primary Fuel Type
0 = No Heat 1=Natural Gas 2 = Propane 3 = Electric—Open Coil 4 = Electric—Sheathed Coil 5 = Hot Water 6 = Steam
8 OAU-SVX02F-EN
Model Number Descriptions
Digit 22 — Heater Capacity— Primary Heat Source
IF ELEC HOT WATER
0 = No Heat No Heat No Heat A = 50 MBh 5 kW 1 Row/10 FPI B = 75 MBh 10 kW 1 Row/12 FPI C = 100 MBh 15 kW 1 Row/14 FPI D = 125 MBh 20 kW 2 Row/10 FPI E = 150 MBh 24 kW 2 Row/12 FPI F = 200 MBh 28 kW 2 Row/14 FPI G = 250 MBh 32 kW 3 Row/10 FPI H = 300 MBh 40 kW 3 Row/12 FPI J = 350 MBh 48 kW 3 Row/14 FPI K = 400 MBh 60 kW L = 500 MBh 68 kW M = 600 MBh 79 kW N = 99 kW O = 111 kW P = 119 kW X = Special Heater Option
Digit 23 — Heat Capacity— Secondary Heat Source
ELEC DF
0 = No Heat/No Secondary Heat A = 5 kW 6 in. Burner—
Up to 330 MBh
B = 10 kW 12 in. Burner—
Up to 400 MBh
C = 15 kW 12 in. Burner—
Up to 600 MBh
D = 20 kW 18 in. Burner—
Up to 400 MBh
E = 24 kW 18 in. Burner—
Up to 900 MBh F = 28 kW G = 32 kW H = 40 kW J = 48 kW
Digit 24 — Corrosive Environment Package
0 = No Corrosive Package 1 = S/S Interior, S/S Evap Coil Casing 2 = S/S Interior, Eco-Coated Coils 3 = S/S Interior,
Copper/Copper Evap Coil 4 = S/S Coil Casing 5 = S/S Interior 6 = Eco-Coated Coils 7 = S/S Coil Casing with
Eco-Coated Coils 8 = Copper/Copper Evap, HGRH
Coils 9 = Corrosion Resistant Package
Digit 25, 26 — Unit Controls
00 = Non DDC—Electromechanical AA = Trane—Discharge Air Control
AB = Trane—Space Control w/LON
AC = Trane—Discharge Air Control
AD = Trane—Space Control
AF = Trane—Discharge Air Control
AG = Trane—Space Control
AI = Trane—Discharge Air Control
AJ = Trane—Space Control
AK = Trane—Multi-Zone VAV Control
AL = Trane—Multi-Zone VAV Control
AM = Trane—Multi-Zone VAV Control
AN = Trane—Multi-Zone VAV Control
AO = Trane—Single-Zone VAV Control
AP = Trane—Single-Zone VAV Control
AQ = Trane—Single-Zone VAV Control
AR = Trane—Single-Zone VAV Control
XX = Special
w/LON Read-Write w/Display
Read-Write w/Display
®
w/BACnet
w/BACnet (No Display)
w/BACnet w/Display
w/BACnet w/Display
w/LON Read-Write (No Display)
w/LON Read-Write (No Display)
w/LON Read-Write w/Display
w/BACnet w/Display
w/LON Read-Write (No Display)
w/BACnet (No Display)
w/LON Read-Write w/Display
w/BACnet w/Display
w/LON Read-Write (No Display)
w/BACnet (No Display)
(No Display)
Digit 27 — Powered Exhaust Fan Motor (PFM) and Exhaust Dampers
0 = No Powered Exhaust 3 = Belt Drive 4 = Belt Drive w/VFD 5 = Special Motor Option 6 = ECM w/Backward Curved
7 = ECM w/Backward Curved
8 = ECM w/Backward Curved
9 = Barometric Relief Dampers
Plenum Fan
Plenum Fan and Barometric Relief Damper
Plenum Fan and Isolation Dampers w/End Switch
(No PFM)
Digit 28 — Powered Exhaust Fan Wheel
0 = No Powered Exhaust A = 355 B = 450 C = 450 X 2 D = 12/9 BT (single fan-belt drive) E = 12/9 BT (dual fan-belt drive)
Digit 29 — Powered Exhaust Fan Motor (hp)
ECM
0 = No Powered Exhaust A = 1 kW 2 hp B = 2 kW 3 hp C = 3 kW 5 hp D = 4 kW 7.5 hp E = 10 hp F = 15 hp
Belt Drive
DIGIT 30 — Reserved for Future Use
Digit 31 — ERV (Requires Powered Exhaust)
0=No ERV A = ERV—Composite Construction
w/Bypass
B = ERV—Composite Construction
with Frost Protection w/VFD
C = ERV—Aluminum Construction
w/Bypass
D = ERV—Aluminum Construction
with Frost Protection w/VFD
Digit 32 — ERV Size
0=No ERV 1 = 3014 2 = 3622 3 = 4136 4 = 4634 5 = 5856
Digit 33 — Damper Options
0 = 100% OA 2-Position Damper 1 = 100% OA 2-Position Damper
w/RA 2-Position Damper
2 = Modulating OA and RA Dampers
w/Economizer
Digit 34 — Filtration Options
A = No Filters B = MERV-8, 30% C = MERV-13, 80% D = MERV-14, 95% E = MERV-8 30%, MERV-13 80% F = MERV-8 30%, MERV-14 95% G = MERV-8, 30%, with UVC H = MERV-13, 80%, with UVC J = MERV-14, 95%, with UVC K = MERV-8 30%, MERV-13 80%,
and UVC
L = MERV-8 30%, MERV-14 95%,
and UVC
X = Special Filter Options
Digit 35 — Smoke Detector— Factory Installed
0 = No Smoke Detector 1 = Supply Smoke Detector 2 = Return Smoke Detector 3 = Supply and Return Smoke
Detectors
OAU-SVX02F-EN 9
Model Number Descriptions
Digit 36 — Electrical Options
0 = Terminal Block A = Non-Fused Disconnect B = Fused Disconnect Switch C = Non-Fused Disconnect
D = Fused Disconnect Switch
E = Dual Point Power F = Dual Point Power
G = 65 SCCR Electrical Rating
H = 65 SCCR Electrical Rating
J = 65 KAIC Electrical Rating
K = 65 KAIC Electrical Rating
L = 65 KAIC Non-Fused
M = 65 KAIC Fused
N = 65 SCCR Non-Fused
Digit 37 — Air Flow Monitoring
0 = No Airflow Monitoring 1 = Airflow Monitoring—IFM
2 = Airflow Monitoring—PE
3 = Airflow Monitoring—Outdoor Air
4 = Airflow Monitoring—IFM
5 = Airflow Monitoring—Outdoor Air
Digit 38 — Accessories
0=No Options A = Hailguards B = Hailguards and LED Service
D = Hailguards & LED Service Light
E = Hailguards & LED Service Light
Digit 39 — Altitude
0 = Sea Level to 1,000 feet 1 = 1,001 to 2,000 feet 2 = 2,001 to 3,000 feet 3 = 3,001 to 4,000 feet 4 = 4,001 to 5,000 feet 5 = 5,001 to 6,000 feet 6 = 6,001 to 7,000 feet 7 = Above 7,000 feet
w/Convenience Outlet
w/Convenience Outlet
w/Convenience Outlet
w/Non-Fused Disconnect
w/Fused Disconnect
w/Non-Fused Disconnect
w/Fused Disconnect
w/Convenience Outlet
w/Convenience Outlet
w/Convenience Outlet
Piezo Ring
Piezo Ring
with Display and IFM
w/Piezo Ring
Piezo Ring and PE Piezo Ring
Monitoring w/Display Supply Air
and Exhaust Air w/Piezo Rings
Light in Supply Fan Section
in Exhaust Fan Section
in Supply and Exhaust Fan
Section
10 OAU-SVX02F-EN
General Information
Overview of Manual
Note: One copy of this document ships inside the control
panel of each unit and is customer property. It must
be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC techn icians to properly diagnose and repair this equipment.
Model Number Description
All products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided (see Model Number chapter). Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate.
Unit Nameplate
A Mylar® unit nameplate is located on the unit’s corner support next to the control box. It includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data.
receive information from sensors and customer binary contacts to satisfy the applicable request for ventilation, cooling, dehumidification and heating.
Indoor Fan Failure Input
The Indoor Fan Failure Switch (IFFS) is connected to verify indoor fan operation.
When there is a call for the indoor fan to be energized, the differential pressure switch, connected to the Main Unit Display, must prove airflow within 60 seconds or the Main Unit Display will shut off all mechanical operations, lock the system out and send a diagnostic alarm to the Unit Display. The system will remain locked out until a reset is initiated through the MCM via the Alarm Reset Function on the Unit Display.
Low Pressure Control ReliaTel Control
This input incorporates the compressor low pressure control (CLP 1) for the refrigeration circuit and can be activated by opening a field supplied contact installed on the OAUTS.
If this circuit is open before the compressor is started, the ReliaTel™ control will not allow the affected compressor to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor is immediately turned “Off.” The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close.
If four consecutive open conditions occur during the first three minutes of operation, the compressor will be locked out, and a manual reset will be required to restart the compressor.
Refrigerant Circuits
Compressor Nameplate
The nameplate for the compressors are located on the side of the compressor.
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation.
The condenser coils are aluminum fin, mechanically bonded to copper tubing.
Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.
The Outdoor Air Unit Main Unit Display and ReliaTel™ Control Module (RTRM) are microelectronic control systems. The acronym RTRM is extensively throughout this document when referring to the control system network.
The Main Unit Display and the RTRM are mounted in the Main Control Panel. The Main Unit Display and RTRM
OAU-SVX02F-EN 11
For 3–5 ton units, one refrigerant circuit shall incorporate a standard 4- -row coil. For 6–9 ton units, one refrigerant circuit shall incorporate a 4 or 6 row coil. For 10–30 ton units, two refrigerant circuits shall incorporate a 4- or 6-row coil. All circuits shall have thermal expansion valves (TXVs), service pressure ports, and refrigerant line filter driers as standard. An area will be provided for replacement suction line driers. Each refrigerant circuit is equipped with a factory installed and preset refrigerant capacity control (RCC) to prevent evaporator coil temperatures below approximately 38°F (114 lb suction). The refrigerant capacity device is not installed when the unit is equipped with a digital scroll.
High Pressure Control ReliaTel Control
The compressor high pressure controls (CHP 1) are wired in series between the compressor outputs on RTRM1 (CHP 1) and the compressor contactor coils. If one of the high pressure control switches opens, the RTRM senses a lack of current while calling for cooling and locks the compressor out.
General Information
Space Temperature / RH Sensor (Optional)
Field installed, wall mounted temperature and humidity sensor (BAYSENS036A) to control space cooling, heating and dew point.
High Temperature Sensor
The Discharge Air Temperature Sensor (DTC) supplies a continuous signal to the MCM. Factory setting for Discharge Air Temperature (DTC) Discharge Air Temperature Setpoint (MDTS) is 90°F (adj 70–100°F), the unit will be shut down, and require a manual restart if Discharge Air Temperature exceeds MDTS for 10 minutes (adj 10–25 minutes). If DAT exceeds Discharge Air High Temperature Cutoff (DHCS) of 125°F for 10 minutes, the unit will shut down and require manual restart.
Outdoor Air Temperature and Relative Humidity Sensor
This factory installed combination outdoor air sensor located in the outdoor air hood is designed to sense both outdoor air temperature and relative humidity for use by the microprocessor controller to make required ventilation, cooling, dehumidification and heating decisions. Control Input (Occupied / Unoccupied)
Terminals are provided on the terminal strip labeled OAUTS for a field installed dry contact or switch closure to put the unit in the Occupied or Unoccupied modes.
Hot Gas Reheat
This option shall consist of a hot-gas reheat coil located on the leaving air side of the evaporator.
Through the Base Electrical with Disconnect Switch
An optional factory installed 3-pole, molded case disconnect switch with provisions for through the base electrical connections may be included. The disconnect switch, with integral overcurrent circuit breaker, will be installed in the unit in a water tight enclosure with access through a hinged door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized.
Through the Base Gas Piping
The unit will include provisions for installing through the base gas piping. The factory installed option will have all piping necessary including an external shutoff piping yoke with pre-assembled, manual gas shut-off valve, elbows, and union. The manual shut-off valve will include an 1/8 in. (3.17 mm) NPT pressure tap. This assembly will require minor field labor to install.
Hinged Access Doors
Hinged access doors with hold open brackets will be factory-installed.
Electric Heat
The unit may have four stage or fully modulating SCR controlled, electric heat. The primary heating section will include open coil heating elements, automatic and manual cut-outs, low voltage controls, air proving switch, maximum 48 amps per circuit and fusing for heaters over 48 amps.
100 Percent Outdoor Air Hood with Damper and Filters
Factory-installed and -integrated 100 percent outdoor air hood with damper controlled by a direct coupled actuator. The unit can be factory provided with an optional 100 percent return air damper controlled by a direct coupled actuator that is electrically interlocked with the outdoor air damper.
Modulating Indirect Gas-Fired Burner
The unit will have fully modulating, high turndown, indirect gas-fired heat. The heating section will include high turn-down burners and a stainless steel tubular heat exchanger. The heat exchanger will be constructed of type 439 stainless steel and be a tubular design capable of draining internal condensate. External flue to be constructed of type 430 stainless steel.
Units will be suitable for use with natural gas or Liquid Propane (LP) gas.
12 OAU-SVX02F-EN
General Information
Unit Inspection
WARNING
Fiberglass Wool!
Product may contain fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
AVERTISSEMENT
Laine de verre !
Le produit peut contenir de la laine de verre. Des interventions inappropriées sur l’isolation de ce produit pendant les opérations d’installation, d’entretien ou de réparation vous exposent à des particules aériennes de fibres de verre ou de fibres céramiques, responsables selon la législation américaine (état de Californie) de risques de cancers par inhalation. Les fibres de verre peuvent aussi provoquer des phénomènes d’irritation au niveau du système respiratoire, de la peau ou des yeux.
As soon as the unit arrives at the job site:
Verify that the nameplate data matches the data on
the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit
nameplate specifications.
Visually inspect the exterior of the unit, including the
roof, for signs of shipping damage.
Visually inspect the internal components for shipping
damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
If concealed damage is discovered, notify the carrier’s
terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the appropriate sales representative before
installing or repairing a damaged unit.
Wash clothes separately from other clothing: rinse washer thoroughly.
Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact
Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact
Wash affected areas gently with soap and warm water after handling.
Storage
Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if:
the unit is stored before it is installed; or,
the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for startup.
Note: Do not use the unit’s heater for temporary heat
without first completing the startup procedure detailed in “Startup,” p. 38.
The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.
Unit Clearances
“Unit Clearances, Curb Dimensions, and Dimensional Data,” p. 14 contains figures that illustrate the minimum
operating and service clearances for either a single or multiple unit installation. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust or recirculation of hot condenser air.
Avoid breathing fiberglass dust.
Use a NIOSH approved dust/mist respirator.
Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.
OAU-SVX02F-EN 13
Unit Clearances, Curb Dimensions, and Dimensional
7'-0"
6'-0"
END TO END
3'-0"
4'-0"
4'-0"
3'-0"


(1'72(1'















6833/<
5(7851
Data
WARNING
Combustible Materials!
Failure to maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials could cause a fire which could result in death or serious injury or property damage. Refer to unit nameplate and installation instructions for proper clearances.
AVERTISSEMENT
Matériaux combustibles !
Tout manquement à l’obligation de maintenir une distance appropriée entre l’échangeur de chaleur de l’unité, les surfaces de ventilation et les matériaux combustibles peut provoquer un incendie pouvant résulter en des blessures corporelles graves, voire mortelles, ou des dommages matériels. Reportez-vous à la plaque signalétique de l’unité et aux instructions d’installation pour connaître les distances appropriées.
OAB Units
Unit Clearances
Figure 1. Typical installation clearances for OAB unit
Figure 2. Typical installation clearances for OAB unit
with auxiliary cabinet
Note: Certain options require auxiliary cabinet. Refer to
project-specific unit submittals.
Curb Dimensions
Figure 3. Unit curb data for OAB 3–9 tons
14 OAU-SVX02F-EN
Unit Clearances, Curb Dimensions, and Dimensional Data















5(7851
6833/<







)52179,(:
(/(&75,&
',6&211(&7







5,*+76,'(9,(:




5$




6$






%277209,(:
7+528*+%$6(
(/(&75,&






5,*+76,'(9,(:

Figure 4. Unit curb data for OAB 3–9 tons with
auxiliary cabinet
Note: Certain options require auxiliary cabinet. Refer to
project-specific unit submittals.
Dimensional Data
Figure 5. Unit dimensional data for OAB 3–9 tons (in.)
Note: Sound attenuation package will add 17.76 in. to the
height of the condenser fan section. Refer to project-specific unit submittals.
OAU-SVX02F-EN 15
Unit Clearances, Curb Dimensions, and Dimensional Data







)52179,(:
(/(&75,&
',6&211(&7









5,*+76,'(9,(:




5$




6$






%277209,(:
7+528*+%$6(
(/(&75,&
72"
84"
36"
36"
48"
36"
Figure 6. Unit dimensional data for OAB 3–9 tons with
auxiliary cabinet (in.)
Indirect-Fired OAG Units
Unit Clearances
Figure 7. Typical installation clearances for indirect-
fired OAG unit
Note: Certain options require auxiliary cabinet. Refer to
project-specific unit submittals.
Note: Sound attenuation package will add 17.76 in. to the
height of the condenser fan section. Refer to project-specific unit submittals.
16 OAU-SVX02F-EN
Unit Clearances, Curb Dimensions, and Dimensional Data
72"
84"
36"
48"
36"
36"
S
U
P
P
L
Y
R
ET
U
R
N
4
13
3
55"
4
193"
3
"
" 23
4
3
53"
8
4
3
" 8
4
1
" 70
2
1
"
" 117
2
25
1 2
"
R
E
T
U
R
N
2
441"
84"
3
23
4
4
3
"
"
8
53"
3
8
1655"
1
" 70
2
1
"
" 117
2
3
55"
13
4
3
" 19
4
1
" 25
2
5
" 3
8
3
1 2
"
S
U
PPL
Y
17.250
35.798
ELECTRIC DISCONNECT
FRONT VIEW
77.524
67.060
74.000
74.417
3.226
NECT
RIGHT SIDE VIEW
121.000 32.573 6.084
6.914
13.039
159.656
22.463
BOTTOM VIEW
17.250
5.125
22.000
24.500
SUPPLY
4.000
19.955
RETURN
11.000
52.000
RETURN
11.000
4.000
54.000 SUPPLY
2.000 THROUGH
BASE ELECTRIC
Figure 8. Typical installation clearances for indirect-
fired OAG unit with auxiliary cabinet
Figure 10. Unit curb data for indirect-fired OAG with
auxiliary cabinet (in.)
Note: Certain options require auxiliary cabinet. Refer to
project-specific unit submittals.
Dimensional Data
Figure 11. Unit dimensional data for indirect-fired OAG
Note: Certain options require auxiliary cabinet. Refer to
project-specific unit submittals.
Curb Dimensions
Figure 9. Unit curb data for indirect-fired OAG (in.)
OAU-SVX02F-EN 17
Unit Clearances, Curb Dimensions, and Dimensional Data
17.250
35.798
ELECTRIC DISCONNECT
FRONT VIEW
77.524
67.060
74.000
74.417
3.226
6.914
13.039
6.084
17.250
2.000 THROUGH
BASE ELECTRIC
BOTTOM VIEW
5.125
22.000
24.500
SUPPLY
52.072
19.955
RETURN
11.000
52.000
RETURN
11.000
4.000
54.000 SUPPLY
RIGHT SIDE VIEW
121.000 48.072
32.585
3.039
40.595
207.740
169.072
Note: Sound attenuation package will add 10.79 in. to the
height of the condenser fan section. Refer to project-specific unit submittals.
Figure 12. Unit dimensional data for indirect-fired OAG
with auxiliary cabinet
Note: Certain options require auxiliary cabinet. Refer to
project-specific unit submittals.
Note: Sound attenuation package will add 10.79 in. to the
height of the condenser fan section. Refer to project-specific unit submittals.
18 OAU-SVX02F-EN
Unit Weight and Rigging
WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
WARNING
AVERTISSEMENT
Levage inapproprié de l’unité !
AVERTISSEMENT
Objets lourds !
Le non-respect des instructions ci-dessous ou un levage inapproprié de l’unité peut provoquer sa chute voire écraser l’opérateur/le technicien, ce qui peut occasionner des blessures graves voire mortelles, et éventuellement endommager l’équipement ou provoquer des dégâts matériels. Assurez-vous que l’équipement de levage utilisé est adapté au poids de l’unité à soulever. Chaque câble (chaîne ou élingue), crochet ou manille utilisé pour le levage de l’unité doit être assez robuste pour supporter le poids total de l’unité. Les câbles, chaînes ou élingues de levage ne doivent pas être de longueur identique. Procédez au réglage afin de soulever l’unité de manière équilibrée.
Table 1. Typical unit weight, center of gravity, and corner weights (percentage of total weight) - air cooled DX units
without powered exhaust or ERV
Le non-respect des instructions ci-dessous ou un levage inapproprié de l’unité peut provoquer sa chute voire écraser l’opérateur/le technicien, ce qui peut occasionner des blessures graves voire mortelles, et éventuellement endommager l’équipement ou provoquer des dégâts matériels. Faites un test de levage de l’unité d’environ 60 cm (24 po) afin de vérifier que le point de levage correspond au centre de gravité de l’appareil. Pour éviter une chute de celle-ci, ajustez son point de levage si elle n’est pas à l’horizontale.
Unit Weight
Weight (lb) Center-of-gravity (in.) Corner weight (% of total weight)
Model Number
OAB*036 1255 1736 46.1 24.1 28% 26% 27% 20% OAB*048 1255 1736 46.6 23.9 30% 24% 28% 18% OAB*060 1255 1736 45.9 23.9 29% 25% 28% 18% OAB*072 1255 1736 47.5 23.8 31% 24% 27% 18% OAB*084 1255 1736 46.5 24.0 29% 25% 28% 19% OAB*096 1255 1736 46.7 24.1 31% 22% 30% 17% OAB*108 1255 1736 46.2 24.0 27% 27% 25% 21% OAG*120 2437 4546 60.2 34.7 29% 24% 26% 21% OAG*144 2437 4546 59.5 34.9 26% 27% 24% 24% OAG*180 2437 4546 59.3 34.7 28% 26% 26% 21% OAG*210 2437 4546 60.7 35.5 26% 26% 24% 24% OAG*240 2437 4546 59.5 34.6 29% 24% 26% 20% OAG*264 2437 4546 59.9 34.4 26% 28% 23% 24% OAG*300 2437 4546 58.8 35.2 28% 24% 27% 20% OAG*360 2437 4546 58.9 34.2 28% 26% 25% 21%
OAU-SVX02F-EN 19
Min Max Length Width Corner A Corner B Corner C Corner D
Unit Weight and Rigging
Table 2. Typical unit weight, center of gravity, and corner weights (percentage of total weight) - air cooled DX units
with powered exhaust but without ERV
Weight (lb) Center-of-gravity (in.) Corner weight (% of total weight)
Model Number
OAB*036 1608 2352 68.8 24.8 36% 17% 34% 14% OAB*048 1608 2352 63.6 24.1 32% 22% 32% 14% OAB*060 1608 2352 65.5 24.3 29% 24% 29% 18% OAB*072 1608 2352 65.2 24.2 29% 25% 29% 18% OAB*084 1608 2352 63.0 24.0 22% 32% 23% 23% OAB*096 1608 2352 65.5 24.3 29% 24% 29% 18% OAB*108 1608 2352 66.9 24.6 29% 24% 28% 19% OAG*120 3199 4730 84.4 35.5 26% 26% 24% 24% OAG*144 3199 4730 83.6 35.3 24% 28% 23% 25% OAG*180 3199 4730 82.5 35.4 23% 29% 23% 25% OAG*210 3199 4730 84.0 35.0 24% 29% 21% 26% OAG*240 3199 4730 83.6 35.3 24% 28% 23% 25% OAG*264 3199 4730 83.6 35.3 24% 28% 23% 25% OAG*300 3199 4730 83.6 35.3 24% 28% 23% 25% OAG*360 3199 4730 83.6 35.3 24% 28% 23% 25%
Min Max Length Width Corner A Corner B Corner C Corner D
Corner Weight
Table 3. Typical unit weight, center of gravity, and corner weights (percentage of total weight) - air cooled DX units
with powered exhaust and ERV
Weight (lb) Center-of-gravity (in.) Corner weight (% of total weight)
Model Number
OAB*036 1740 2526 68.1 24.3 31% 22% 29% 18% OAB*048 1740 2526 68.9 24.0 31% 23% 27% 19% OAB*060 1740 2526 67.0 24.1 28% 25% 26% 20% OAB*072 1740 2526 67.0 24.4 25% 28% 24% 23% OAB*084 1740 2526 68.3 24.4 28% 26% 25% 22% OAB*096 1740 2526 67.3 24.2 30% 24% 28% 19% OAB*108 1740 2526 68.1 24.0 28% 26% 25% 21% OAG*120 3879 5972 89.4 35.3 28% 24% 23% 25% OAG*144 3879 5972 84.3 38.8 23% 24% 26% 26% OAG*180 3879 5972 88.1 35.1 25% 27% 21% 27% OAG*210 3879 5972 88.2 35.2 31% 22% 26% 21% OAG*240 3879 5972 87.4 35.2 29% 23% 25% 23% OAG*264 3879 5972 85.8 35.1 24% 28% 21% 26% OAG*300 3879 5972 87.0 36.0 27% 24% 24% 25% OAG*360 3879 5972 87.0 36.0 27% 24% 24% 25%
Min Max Length Width Corner A Corner B Corner C Corner D
20 OAU-SVX02F-EN
Unit Weight and Rigging
Intake hood
OAB and OAG Cabinets - top view
BA
CD
/(1*7+
:,'7+
635($'(5
%$56
6&5(:3,16+$&./(
/2&$7,216
4-point lift
Model: OAB
/(1*7+
:,'7+
635($'(5
%$56
6&5(:3,16+$&./(
/2&$7,216
6-point lift
Model: OAB
SPREADER
BARS
A
DETAIL A
SCALE 1 : 12
SCREW PIN SHACKLE
4 LOCATIONS
4-point lift
Model: OAG
A
SPREADER
BARS
SCALE 1 : 12
DETAIL A
SCREW PIN SHACKLE
4 LOCATIONS
6-point lift
Model: OAG
Figure 13. Cabinet corners
Rigging
Figure 14. Rigging and center-of-gravity data
Figure 14. Rigging and center-of-gravity data
Before proceeding, refer to tables in Unit Weight section for typical unit operating weights and Figure 14, p. 21 for rigging drawing.
1. Remove the shipping crate from around the unit.
2. Rig the unit as shown in Figure 14, p. 21. Attach adequate strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains, or slings except as shown.
3. Install a lifting bar, as shown in Figure 14, p. 21, to protect the unit and to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the unit should be 7 feet.
4. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments.
5. Lift the unit and position it into place. Remove fork pockets prior to setting on the curb.
OAU-SVX02F-EN 21
6. Downflow units; align the base rail of the unit with the curb rail while lowering the unit onto the curb. Make sure that the gasket on the curb is not damaged while positioning the unit.
Installation
48 in. (121.9 cm)
Minimum straight duct
distance before an elbow
for either gas heat
or electric heat
Airflow
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Procédures d’entretien dangereuses !
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles. Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
Ductwork
Elbows with turning vanes or splitters are recommended to minimize air noise due to turbulence and to reduce static pressure.
When attaching the ductwork to the unit, provide a water­tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork.
All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed.
Note: For sound consideration, cut holes in the roof deck
only for the ductwork penetrations. Do not cut out the roof deck within the entire curb perimeter. All
duct work must be installed and connected to top of roof curb before the unit is set on curb.
If a Curb Accessory Kit is not used:
1. Be sure to use flexible duct connections at the unit.
2. Gaskets must be installed around the curb perimeter flange and the supply and return air opening flanges.
Note: For units will electric heat in the primary heating
position, refer to figure below.
Figure 15.
Important: Bottom discharge units with open coil
electric heater in primary heat location require discharge duct with 90° elbow. This is a MANDATORY installation requirement.
Note: A minimum 48" of straight duct is required before
an elbow. This is a requirement for both vertical and horizontal discharge regardless of heat type.
General Unit Requirements
The checklist listed below is a summary of the steps required to successfully install a commercial unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does
not replace the detailed instructions called out in the applicable sections of this manual.
Check the unit for shipping damage and material
shortage. File a freight claim and notify appropriate sales representative if damage or shortage is discovered.
Verify that the unit nameplate model, options, and
voltage are correct.
Verify that the installation location of the unit will
provide the required clearance for proper operation.
22 OAU-SVX02F-EN
Installation
Control
panel
door
Heater
door
Assemble and install the roof curb (if applicable).
Refer to the latest edition of the curb installers guide that ships with each curb kit. Check curb for level installation; if not level, shim as required.
Convert unit to horizontal discharge and/or horizontal
return if necessary (Refer to “OAB and OAG IF Heater
Air Inlet Hood and Flue Assembly Instructions,” p. 23).
Rigging unit (refer to “Unit Weight and Rigging,”
p. 19).
Set the unit onto the curb; check for level.
Ensure unit-to-curb seal is tight and without buckles
or cracks.
Install and connect proper condensate drain line to
the evaporator condensate pan drain connection (see
Figure 24, p. 25).
Assemble indirect fired heater air inlet hood and flue
assembly (refer to “OAB and OAG IF Heater Air Inlet
Hood and Flue Assembly Instructions,” p. 23.)
OAB and OAG IF Heater Air Inlet Hood and Flue Assembly Instructions
Unit is shipped with the IF heater air inlet hood and flue cover stowed in the blower compartment.
Important: Assemble the inlet hood and flue cover to
the heater door before attempting any unit startup.
Figure 17. Wind screen
Figure 18. Heater air inlet hood
Figure 16. Flue cover
1. Open the blower compartment and remove the flue cover, wind screen, and heater air inlet hood.
2. Open the control panel door and remove the heater door shown in Figure 19.
Figure 19.
OAU-SVX02F-EN 23
Installation
3. Attach the flue cover to the heater door using the provided stainless steel screws as shown in Figure 20.
Figure 20.
4. Attach the heater air inlet hood to the heater door using quantity (6) of the provided painted head screws as shown in Figure 21.
Figure 22.
6. Install the heater door on the unit, as shown in
Figure 23, p. 24, ensuring that the heater flue extends
through the flue opening in the door.
Figure 23.
Figure 21.
5. Attach the wind screen to the inside of the heater door using quantity (6) of the provided painted head screws as shown in Figure 22.
24 OAU-SVX02F-EN
Installation
PANEL ENCLOSURE
D" NPT FEMALE CONNECTOR
CLEANOUT PLUG
Main Electrical Power Requirements
Verify that the power supply complies with the unit
nameplate specifications.
Inspect all control panel components; tighten any
loose connections.
Connect properly sized and protected power supply
wiring to a field-supplied/-installed disconnect switch and to the main power terminal block (HTB1) in the unit control panel.
Connect properly-sized earth ground.
Note: All field-installed wiring must comply with NEC
and applicable local codes.
Condensate Drain Configuration
OAU units are selected based on dehumidification capability. As such, condensate can form at a high rate. Therefore, the OAU drain pan and condensate line are sized and designed accordingly. However, an often­overlooked element of proper condensate drainage is proper P-Trap and drain line sizing and installation. An incorrectly-designed and -installed P-Trap can restrict condensate flow or cause water in the condensate drain pan to “spit” or “geyser” which may cause condensate overflow. Carefully install and trap the drain pan to ensure adequate condensate removal under all conditions.
An evaporator condensate drain connection is provided on the unit.
A condensate trap must be installed at the unit due to the drain connection being on the “negative pressure” side of the fan. Install the P-Trap using the guidelines in Figure 24.
Pitch drain lines connected to P-Trap at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow. Do not allow the horizontal run to sag causing a possible double-trap condition which could result in condensate backup due to “air lock”.
Figure 24. Condensate trap installation
D = Pipe diameter; see for correct pipe diameter H = Internal static pressure (in wg) +1 in. J = H x 0.5 L = H + J +D
Notes:
1. Pitch drain at least 1/2 in. per 10 ft horizontal run.
2. Condensate drain pan will not drain properly if P-trap is not primed
and of adequate height to allow for cabinet operating negative pressure.
Hot Water Control Valve Wiring
1. Mount the factory-provided water valve on the return line of the hot water coil.
2. Ensure the valve is set to normally open.
3. Run the 16 gauge black wire from TNS 2 to Input 1 of the actuator.
4. Run the 16 gauge red wire from TNS 2 to Input 2 of the actuator.
5. Run the 16 gauge yellow wire from AO1 from the UC600 to Input 3 of the actuator.
Note: The actuator valve will be open with a 0 percent
call for heat.
Figure 25. Hot water control valve wiring
OAU-SVX02F-EN 25
Installation
&
$
(
%
'
'(7$,/$
6&$/(
7RUH KH[KH VLGHV /LIWW VLGHS WRSXS $VV VHFXUH KRRG VFUHZV WKHSU VLGHS 5HS GDPS
Chilled Water Connection Size and Location
Figure 26. Outdoor air chilled water cooling pipe chase-
connections
Figure 27. OAB powered exhaust damper hood,
collapsed
Table 4. Chilled water pipe chase location (in.)
Unit A B C D E
OAB 61.25 12 10 3 3 OAG 79.75 12.5 10 3 4.125
Table 5. Chilled water connection size (MPT-in.)
Unit Size MPT-in.
OAB 3–9 tons 2 OAG 10–30 tons 2
Filter Installation
The filter rack is accessible through the evaporator coil compartment door. Filter type, size, and quantity are determined by selected filter option and unit size.
Note: Do not operate the unit without filters.
Opening the Collapsed Exhaust Damper
2. Lift the hood upward and rotate the side panels outward while holding the top up.
3. As shown in DETAIL B (see Figure 28) and marked by arrow (2), secure the side panels to the top of the hood using (8) hex head sheet metal screws, provided with the unit, through the pre-punched holes in the top and side panels (four screws per side).
4. Repeat these steps for the remaining damper hood.
Hood
OAB Cabinet
1. To release the damper hood, remove the hex head sheet metal screws (one per side) shown in DETAIL A (see Figure 27) and marked by arrow (1).
26 OAU-SVX02F-EN
Installation
'(7$,/%
6&$/(
WKH
WKH
JK
'(7$,/$
6&$/(
7RUHOH WKHKH[ VKRZQLQ /LIWWKH VLGHSDQ WRSXS $VVKR VHFXUHW KRRGXV VFUHZV WKHSUH VLGHSDQ 5HSHD
Figure 28. OAB powered exhaust damper hood, open
Figure 29. OAG powered exhaust damper hood,
collapsed
OAG Cabinet
1. To release damper hood, remove the hex head sheet metal screw shown in DETAIL A (see Figure 29) and marked by arrow (1).
2. Lift the hood upward and rotate the side panels outward while holding the top up.
3. As shown in DETAIL B (see Figure 30) and marked by arrow (2), secure the side panels to the top of the hood using (8) hex head sheet metal screws, provided with the unit, through the pre-punched holes in the top and side panels (four screws per side).
4. Repeat these steps for the remaining damper hood.
OAU-SVX02F-EN 27
Installation
'(7$,/%
6&$/(
WKH






(/(&75,&
',6&211(&7
6:,7&+
*$6,1/(7 037
&21'(16$7(
'5$,1
)37
7+528*+%$6(
(/(&75,&
OAB utility connections
GAS INLET 1-1/4" MPT
CONDENSATE
DRAIN
1/2" FPT
ELECTRIC
DISCONNECT
SWITCH
81.248
5.512
17.253
38.346
6.000
6.830
OAG utility connections
Figure 30. OAG powered exhaust damper hood, open
AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires !
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
An overall dimensional layout for the standard field installed wiring entrance into the unit is illustrated in . To ensure that the unit’s supply power wiring is properly sized and installed, refer to the following guidelines.
Figure 31. OAB and OAG utility connections
Field Installed Power Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
28 OAU-SVX02F-EN
Note: All field installed wiring must conform to NEC
guidelines as well as State and Local codes.
Verify that the power supply available is compatible with the unit’s nameplate ratings. The available supply power must be within 10 percent of the rated voltage stamped on the nameplate. Use only copper conductors to connect the power supply to the unit.
Main Unit Power
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.Verify that no power is present with a voltmeter.
AVERTISSEMENT
Risque d’électrocution !
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as unit terminals are not designed to accept other types of conductors.
Standard Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
Installation
AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires !
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate.
1. Location of the electrical service entrance is illustrated in. Complete the unit’s power wiring connections onto either; the main terminal block HTB1 inside the unit control panel, the factory mounted non-fused disconnect switch (UCD) or circuit breaker (UCB), or the electric heat non-fused disconnect switch. Refer to the customer connection diagram that shipped with the unit for specific termination points.
2. Provide proper grounding for the unit in accordance with local and national codes.
Use the following checklist in conjunction with the checklist in “General Unit Requirements,” p. 22 to ensure that the unit is properly installed and ready for operation.
Verify that the correct size and number of filters are in
place.
Inspect the interior of the unit for tools and debris and
install all panels in preparation for starting the unit.
Check all electrical connections for tightness and
“point of termination” accuracy.
Verify condenser airflow is unobstructed.
Verify that the condenser and indoor fans turn freely
without rubbing and are properly tightened on the shafts.
Check motor mounting bolts and inlet cone for
tightness. Free spin wheel by hand to check for proper alignment of motor, wheel, and inlet cone. Record motor nameplate amps at unit-rated voltage.
Check proper indoor fan wheel rotation. Wheel
housing will be marked to indicate direction of proper rotation.
With access doors closed and secured, operate
blower at 100 percent speed. Check amps to confirm operation within motor amp capacity.
OAU-SVX02F-EN 29
Installation
Voltage Imbalance
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Composants électriques sous tension !
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
Three phase electrical power to the unit must meet stringent requirements for the unit to operate properly. Measure each leg (phase-to-phase) of the power supply. Each reading must fall within the utilization range stamped on the unit nameplate. If any of the readings do not fall within the proper tolerances, notify the power company to correct this situation before operating the unit.
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2.0 percent. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:
% Voltage Imbalance = 100 X
AV (Average Voltage) =
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from the average voltage.
Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be:
221 + 230 + 227
3
= 226 Avg.
AV - VD
AV
Volt 1 + Volt 2 + Volt 3
where;
3
100 X
The 2.2 percent imbalance in this example exceeds the maximum allowable imbalance of 2.0 percent. This much imbalance between phases can equal as much as a 20 percent current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2.0 percent, notify the proper agencies to correct the voltage problem before operating this equipment.
226 - 221
226
= 2.2%
Electrical Phasing (Three-Phase Motors)
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Composants électriques sous tension !
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
The compressor motor(s) and the supply fan motor are internally connected for the proper rotation when the incoming power supply is phased as A to L1, B to L2, and C to L3.
Proper electrical supply phasing can be quickly determined and corrected before starting the unit by using an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following these steps:
Turn off the main source feeding power to the unit
field-supplied or factory-installed main disconnect device (switch or circuit breaker).
Close the unit disconnect device cover, leaving
disconnect switch in the off position, and turn main source power on.
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
30 OAU-SVX02F-EN
Installation
Observe the ABC and CBA phase indicator lights on
the face of the sequencer. The ABC indicator light will glow if the phase is ABC. If the CBA indicator light glows, turn main source power off and then open the unit main disconnect device cover and reverse any two power wires.
Restore the main source power and recheck the
phasing. If the phasing is correct, turn main source power off then open the unit main disconnect device cover, remove the phase sequence indicator, reinstall disconnect device cover and, leaving disconnect device in the off position, turn main power source to unit on.
Compressor Crankcase Heaters
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When it is necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Composants électriques sous tension !
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
To prevent injury or death from electrocution, it is the responsibility of the technician to recognize this hazard and use extreme care when performing service procedures with the electrical power energized.
Each compressor shall be equipped with a crankcase heater. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor starts. Oil foaming occurs when refrigerant condenses in the compressor and mixes with the oil. In lower ambient conditions, refrigerant migration to the compressor could increase.
When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.
Before initial start up, or if main power has been off for an extended period of time, compressor crankcase heater(s) should be operated for a minimum of 8 hours prior to compressor operation. With main power OFF, remove jumper between OAUTS terminals 9 and 10 (E-Stop). Turn main power to energize crankcase heater(s). At end of warm up period turn main power off, install 9-10 jumper, turn main power on, and resume normal operation.
Following crankcase heater warm-up, turn main power disconnect off, and install jumper on E-Stop terminals 9 and 10.
Turn Main disconnect “On”.
Main Unit Display and ReliaTel Controls
When first powered “On”, the controls perform self­diagnostic initialization to check that all internal controls are functional. The Status LED located on the Main Unit Display and the Liteport LED located on the RTRM module is turned “On” within one second of power-up if internal operation is okay.
Field-Installed Control Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
AVERTISSEMENT
Câblage sur site et mise à la terre corrects nécessaires !
Le non-respect de la réglementation peut entraîner des blessures graves, voire mortelles. Il est IMPÉRATIF de confier l’ensemble du câblage sur site à un électricien qualifié. Un câblage sur site mal installé ou mal mis à la terre constitue des risques D’INCENDIE et D’ÉLECTROCUTION. Pour éviter ces risques, il est IMPÉRATIF de respecter les obligations en matière de pose de câblage sur site et de mise à la terre tel que stipulé dans les règles du NEC et dans les réglementations électriques locales/nationales.
An overall layout of the various control options available with the required number of conductors for each control device is illustrated in Figure 32, p. 33.
Note: All field wiring must conform to NEC guidelines as
well as state and local codes.
OAU-SVX02F-EN 31
Installation
Control Power Transformer
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.Verify that no power is present with a voltmeter.
AVERTISSEMENT
Risque d’électrocution !
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
The 24-volt control power transformers are to be used only with the accessories called out in this manual. Transformers rated greater than 50 VA are equipped with internal circuit breakers. If a circuit breaker trips, turn “Off” all power to the unit before attempting to reset it.
The transformers are located in the control panel. The circuit breaker is located on the left side of the transformers and can be reset by pressing in on the black reset button.
Controls Using 24 Vac
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as unit terminals are not designed to accept other types of conductors.
Before installing any connecting wiring, refer to the below table for AC conductor sizing guidelines, and:
1. Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three (3) ohms/ conductor for the length of the run.
Note: Resistance in excess of 3 ohms per conductor
may cause component failure due to insufficient AC voltage supply.
3. Be sure to check all loads and conductors for grounds, shorts, and mis-wiring.
4. Do not run the AC low-voltage wiring in the same conduit with the high-voltage power wiring.
Table 6. 24 Vac conductors
Distance from Unit to Control Recommended Wire Size
000–460 feet
000–140 m
461–732 feet
104–223 m
18 gauge
0.75 mm 16 gauge
1 mm
2
2
Controls Using DC Analog Input/Output (Standard Low Voltage Multiconductor Wire)
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.Verify that no power is present with a voltmeter.
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.Verify that no power is present with a voltmeter.
AVERTISSEMENT
Risque d’électrocution !
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
32 OAU-SVX02F-EN
Risque d’électrocution !
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to the electrical access locations provided on the unit.
WARNING
AVERTISSEMENT
Installation
1. Below table lists the conductor sizing guidelines that must be followed when interconnecting the DC binary output devices and the system components utilizing a DC analog input\output signal to the unit.
Note: Resistance in excess of 2.5 ohms per conductor
can cause deviations in the accuracy of the controls.
2. Ensure that the wiring between controls and the unit’s termination point does not exceed 2.5 ohms/ conductor for the length of the run.
3. Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires.
Figure 32. OAUTS connection B
DC Conductors
Table 7. Zone sensor module wiring
Distance from Unit to Control Recommended Wire Size
000–150 feet
0–45.7 m
151–240 feet
46–73.1 m
241–385 feet
73.5–117.3 m 386–610 feet
117.7–185.9 m 611–970 feet
186.2–295.7 m
22 gauge
0.33 mm 20 gauge
0.50 mm 18 gauge
0.75 mm 16 gauge
1.3 mm
14 gauge
2.0 mm
2
2
2
2
2
Factory-Provided Sensors
installation in the return duct. Refer to Figure 42, p. 60 for installation instructions.
A discharge temperature sensor (VELSEN-0021) will be factory-provided for field installation in the supply duct. Refer to Figure 39, p. 57 for installation instructions.
If space control is selected, a combination space temperature/humidity sensor (BAYSENS036A) will be factory-provided for field installation in the space. Refer to
Figure 40, p. 58 for installation instructions.
If multi-zone VAV control is selected, a static pressure sensor (VELCON-0350) will be factory-provided for field installation in the supply duct or space. Refer to Figure 42,
p. 60 for installation instructions.
If modulating OA/RA dampers w/economizer and an exhaust fan are selected, a duct static pressure sensor (VELCON-0350) will be factory-provided for field
OAU-SVX02F-EN 33
Pre-Start Check List
Task Initial Date
1. Voltage is present and landed at equipment.
2. Gas piping is complete and landed at each component. Inlet gas pressure to be between 7 in. wg and 14 in. wg.
3. Field installed sensors installed. Refer to “Factory-Provided Sensors,” p. 33 for list of sensors that may be required.
4. Control wiring installed and landed.
5. Accessories installed.
6. Ductwork installed (all runs in place, final tie in complete).
7. Drain lines installed and properly terminated.
8. Startup appointment with Horizon certified Trane service technician set and confirmed.
Notes:
Check list must be completed and returned to Trane before startup is scheduled.
Startup must be performed by a Horizon-certified Trane technician with Tracer™ TU program.
Contractor to furnish access to equipment (ladder, lift, or roof access).
34 OAU-SVX02F-EN
System Configuration and Pre-Start
The following procedure must be completed prior to performing the startup procedure in “Startup,” p. 38. This section describes procedures to navigate the various displays on the Unit Display and configure the Outdoor Air Unit Main Unit Display system setpoints and operating parameters.
Important: This section is intended to provide
guidelines for navigation through the remote operator display screens. For additional control system information, refer to Integration Guide: Tracer™ UC600 Programmable Controller for Packaged Outdoor Air Unit (BAS-SVP18*-EN).
OAU-SVX02F-EN 35
System Configuration and Pre-Start
Table 8. Menu descriptions
Screen Menu Point List Min/Inactive Default Max/Active
Alarms
Reports (continued on next page)
Active Alarms List of all active alarms All Alarms List of all previous alarms Custom Graphics *NOT USED*
Program Control Discharge Air Control Space ControlSpace ControlY Heat Cool Mode Active Heat Cool N Occupancy Status Occupied|Unoccupied|Occupied Bypass|Occupied Standby|Unknown Y Compressor 1 Command Off On N Digital Scroll Command 0% 100% N Dehumidification Command Disabled Enabled N Discharge Air Temperature Local Analog Input Economizer Mode Disabled Enabled N Evap Leaving Temp Local Analog Input Heat Capacity 0% 100% N Heating Output Command 0% 100% N Heat 1 Command Off On N Heat 2 Command Off On N Inducer Command Off On N Gas Valve Status Binary Input HGRH Command 0% 100% N OA Damper End Switch Binary Input Outdoor Air Damper Command Closed Open N OAD Position Local Binary Input Outdoor Air Relative Humidity Local Analog Input Outdoor Air Temperature Local Analog Input
System Status
Space Dewpoint Active Analog Input Space Temperature Local Analog Input Supply Fan Start Stop Command Off Off N Filter Status Clean Dirty N System Lockout Normal Normal Lockout N UNOCC Cooling Mode Off On N UNOCC Dehumid Mode Off On N UNOCC Heating Mode Off On N ERV Command Disable Enable N ERV Leaving Air Temperature Local Analog Input PEVFD Command 0% 80% 100% Y Discharge Airflow Local Analog Input ERV Leaving Air Humidity Local Analog Input
BAS Point?
36 OAU-SVX02F-EN
System Configuration and Pre-Start
Table 8. Menu descriptions (continued)
Screen Menu Point List Min/Inactive Default Max/Active
DAT High Temp Cutout 100°F 125°F 150°F Y DAT Low Temp Cutout 35°F 35°F 50°F Y DAT Temp Cutout Time 10 min. 10 min. 25 min. Y Discharge Air Cooling Setpoint 55°F 55°F 75°F Y Discharge Air Heating Setpoint 65°F 85°F 90°F Y ERV Wheel Frost Cutout Setpoint 32°F 34°F 40°F Y EVAP Leaving Temp Setpoint 45°F 53°F 70°F Y IVFD Signal 50% 100% 100% Y Maximum Discharge Air Temperature 70°F 90°F 100°F Y Minimum Discharge Air Cooling Setpoint 40°F 50°F 65°F Y Minimum Discharge Air Heating Setpoint 50°F 55°F 60°F Y
System Setpoints
Reports (continued from previous page)
System Setup
Override Summary List of active overrides - same as selecting Override button at top of screen All Point Report List of all points (AO/AI/BO/BI/MS/etc …) in the configuration file About Co ntroller Name listed is the version of the program installed in the UC600 Expansion Modules Provides status of expansion modules TGP2 Programs List of all TGP2 programs loaded on the UC600
Data Graphs *NOT USED*
Schedules - Refer to UC600 IOM for scheduling functions Display Preferences
Settings
Language Date and Time Clean Touchscreen
Maximum OA Damper Position 0% 100% 100% Y Minimum OA Damper Position 0% 100% 100% Y Occupied Space Cooling Setpoint 65°F 74°F 90°F Y Occupied Space Heating Setpoint 60°F 70°F 75°F Y Outdoor Air Cooling Setpoint (OACS) 70°F 75°F 85°F Y Outdoor Air Dewpoint Setpoint (OADS) 49°F 58°F 65°F Y Outdoor Air Heating Setpoint (OAHS) 40°F 70°F 70°F Y PEVFD Setpoint 0% 80% 100% Y Space Dewpoint Setpoint (SPDS) 50°F 59°F 68°F Y UNOCC Space Cooling Setpoint 60°F 80°F 90°F Y UNOCC Space Dewpoint Setpoint 49°F 65°F 68°F Y UNOCC Space Heating Setpoint 50°F 60°F 70°F Y Program Control Discharge Air Control Space ControlSpace ControlY Compressor Count 004N Heater Count 002N Split Manifold Burner Not Installed Installe d Installed N ERV Option Not Installed Installed Installed N Powered Exhaust Option Not Installed Installed Installed N Return Air Damper Option Not Installed Installed Installed N Space Temp/Humidity Sensor Installed Not Installed Installed Installed N Heat Type No Heat|Gas Heat|Electric Heat|Other N Alarm Reset Off Off On Y Supply Fan Failure Reset Off Off On Y
BAS Point?
OAU-SVX02F-EN 37
Startup
Indirect Gas-Fired Heating Startup
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
Do not attempt the following procedures until all electrical and gas connections to the unit have been completed and the outdoor air damper and evaporator fan operation have been verified and are operating correctly.
AVERTISSEMENT
Procédures d’entretien dangereuses !
Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
N’essayez pas de réaliser les procédures suivantes avant d’avoir effectué tous les raccordements en gaz et électricité sur l’unité, d’avoir inspecté le registre d’air extérieur et le ventilateur d’évaporateur et confirmé que leur fonctionnement est approprié.
Notes:
1. This furnace module does not have a pilot. It is equipped with a direct spark ignition device that automatically lights the gas burner. DO NOT try to light burners by hand.
WARNING
Hazard of Explosion!
Failure to follow proper safe leak test procedures could result in death or serious injury or equipment or property-only-damage. NEVER use an open flame to detect gas leaks. You MUST use a leak test solution for leak testing.
AVERTISSEMENT
Risque d’explosion !
Le non-respect des procédures d’essai d’étanchéité sûres recommandées pourrait provoquer des accidents graves, voire mortels, ou des dommages matériels. Ne vérifiez JAMAIS la présence de fuites de gaz avec une flamme nue. Vous devez IMPÉRATIVEMENT utiliser une solution de test d’étanchéité pour vérifier l’étanchéité.
2. BEFORE OPERATING, leak test all gas piping up to heater gas valve. Smell around the unit area for gas. If gas is smelled, do NOT attempt to place heater in operation until source of gas leak is identified and corrected.
38 OAU-SVX02F-EN
Startup
3. Use only hand force to operate the gas control lever to the “ON” position. NEVER use tools. If lever does not operate by hand, replace gas valve prior to staring the unit. Forcing or attempting to repair the gas valve may result in fire or explosion.
4. Do not attempt to operate unit, if there is indication that any part or control has been under water. Any control or component that has been under water must be replaced prior to trying to start the unit.
Tools Required
Voltage Meter (A)
Amp Meter
•Gas Manometer (2)
Temperature Probe
Small Refrigeration Screwdriver
5/16-in. Nut Driver
3/16-in. Allen Wrench
3/32-in. Allen Wrench
1/8-in. NPT barbed pressure taps (3)
1/2-in. Open End Wrench
Startup Procedure
1. Check Inlet Gas Pressure
Check to insure the gas pressure supplied to the unit is within the pressure requirement listed on the nameplate. DO NOT expose gas controls to pressures above 1/2 psi (14 in. wc). The gas supply line should be installed with an external manual shutoff and pressure tap.
2. Verify Indoor Fan Failure Switch Operation
Indoor Fan Failure Switch (IFFS) is located in the unit electrical control compartment above the heater. Indoor fan failure switch will fail if not proven within 30 seconds of call for indoor fan—ON.
All unit air filters must be clean before proceeding to properly complete this verification.
Important: If the unit air filters are not clean, unit
performance could be affected. Remove and clean or replace air filters as required prior to proceeding with the burner pressure testing.
In the event that the pressure switch fails to operate, check the pick-up tubes to be certain that the tubes are not obstructed and confirm that the tube connections to IFFS are tight and secure.
3. Confirm Gas Flow at Unit
WARNING
Hazardous Voltage and Gas!
Failure to turn off gas or disconnect power before servicing could result in an explosion or electrocution which could result in death or serious injury. Turn off the gas supply and disconnect all electric power, including remote disconnects, before servicing the unit. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
AVERTISSEMENT
Tension dangereuse et présence de gaz !
Le non-respect de l’obligation de couper le gaz ou l’alimentation électrique avant de procéder à une opération d’entretien peut entraîner une explosion ou une électrocution pouvant résulter en des blessures graves, voire mortelles. Avant toute intervention sur l’unité, couper l’approvisionnement en gaz et l’ensemble de l’alimentation électrique, y compris les disjoncteurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
Open door to unit vestibule housing the gas heater. Move gas control lever to “OFF” position. Remove 1/8-in. pressure taps (see Figure 34, p. 42) from both modulating and on-off sections of the split heater manifold. Install a barbed fitting in both 1/8-in. tapped holes for connection to individual gas manometers.
Note: There is a third 1/8-in. gas pressure tap located in
the pipe connecting the main valve/regulator and modulating valve. Maximum pressure into modulating valve is 5-in. The On-Off gas valve includes a regulator adjustment device that is located on the top of the valve. Use this device to regulate valve output to modulating valve as required.
Wait 5 minutes for any gas to clear. If you smell gas, see
Step 2 and correct leak. If you don’t smell gas or have
corrected any leaks, go to Step 4.
4. Burner Starting Sequence and Burner Ignition
Figure 34, p. 42 illustrates indirect gas-fired furnace
components.
5. Main Gas Supply
Turn manual gas cock “ON”.
6. Split Manifold High Fire and Burner Test
Open all manual gas valves. Turn power on at unit’s main disconnect switch. Open gas supply manual shut­off valve. Using unit display (or computer with Trane Tracer TU), proceed to System Status Display and Override all Compressor stages OFF, Disable
OAU-SVX02F-EN 39
Startup
Dehumidification, Disable Economizer Mode, Disable ERV. If two heaters are installed, test heating with split manifold first by overriding burner 2 OFF. Override heating Output Command to 100.0 percent if one heater is installed and to 49 percent if two heaters are installed. Override Heat Cool Mode Active to Heat. This will enable call for heat to split manifold heater. Depending on outdoor air temperature, at time of startup, heater high limit temperature may be exceeded causing limit switch to trip. Limit switch is auto-reset. Limit switch must be jumpered out of the circuit if OA temperature dictates.
With limit switch closed, the draft inducer will run on high speed for 10 seconds for proof of high and low airflow switch closure, then begin a 30-second pre­purge period. At the end of the pre-purge the direct spark will be energized and On-Off gas valve will open for a 5-second ignition trial. Following successful ignition, the inducer remains on high for 10-second flame stabilization, followed by 30-second warm up. Should the flame go out or the burner fail to light, an ignition retry will initiate following a 15-second inter­purge period.
Following successful ignition, manifold pressure should be 1.2 in. wc during the warm-up period. The manifold pressure will rise to 3.5 in. wc at 100 percent firing rate. Following these sequences to check low fire gas pressure for modulating section, reduce Heating Output Command to 0 percent. Inducer speed will reduce to low speed. Correct gas pressure for modulating manifold section of heater at 0 percent output signal or low fire will be 0.25 - 0.30 in. wc. For modulating sections, the outlet gas pressure from main/regulator valve into the modulating valve is 5-in. wc.
Main On-Off valves in 1/2-in. gas line require 3/32-in. Allen wrench to adjust outlet gas pressure. Valves in 3/4-in. gas line require flat blade screwdriver to adjust outlet gas pressure. Following these sequences, inducer speed will reduce to low speed and will now be speed-controlled by the heater controller based on gas input to burners.
With heating command at 100 percent and with a single split manifold heater installed, the On-Off section of the heater will require the modulating section to prove ON before the On-Off section will enable. Inducer speed high at all times the On-Off section is in ignition sequence or firing. On-Off section sequence includes a 1-second ignition pre-purge followed by 4-second ignition trial. Ignition or flame failure will be followed by 30-second inter-purge for two ignition retry then 5-minute lockout period if both retry attempts fail. Correct manifold gas pressure for On-Off heater section is 3.5 in. wc.
For units including an additional separate On-Off heater, set heat command output to 49 percent to run modulating heater startup. When complete with
modulating heater startup, increase heat output command to 100 percent to start up the second heater.
High Fire and Low Fire Adjustment
To adjust high fire or low fire setting, please refer to EXA STAR Modulating Valve document. This document will ship with all gas heat units.
Failure to Ignite
On the initial startup, or after unit has been off long
periods of time, the first ignition trial may be unsuccessful due to need to purge air from manifold at startup.
If ignition does not occur on the first trial, the gas
and spark are shut-off by the ignition control and
riod
the control enters an inter-purge pe 15 seconds, during which the draft inducer continues to run.
At the end of the inter-purge period, another trial for
ignition will be initiated.
Control will initiate up to three ignition trials on a
call for heat before lockout of control occurs.
Control can be brought out of lockout by cycling call
for heat at the Main Unit Display.
Prior to completing the startup, check the appearance of the main burner flame. Refer to Figure 33 for flame characteristics of properly adjusted natural gas systems.
of
40 OAU-SVX02F-EN
Startup
Burner flame at startup: 1.2 in. wc manifold pressure draft inducer—high speed
Burner flame at high fire: 3.5 in. wc manifold pressure draft inducer—high speed
Figure 33. Flame characteristics of properly-adjusted
natural gas systems
surrounding buildings or prevailing winds cause recirculation, a flue extension may be required to prevent recirculation. Contact manufacturer prior to making any flue adjustments.
Reduced air delivery can also be the result of
inducer fan blade slippage, dirt accumulation in the fan blade or low voltage to draft inducer motor. Inspect draft fan assembly and be sure fan blade is secure to motor shaft. Check line voltage to heater.
7. Flame Sensor Current Check
NOTICE
Meter Damage!
Measuring voltage with meter connect to a circuit could result in meter damage. Do NOT measure voltage with meter connected to a circuit.
Flame current is the current which passes through the flame from the sensor to ground. A flame signal of 0.5 to 1.0 microamp (A) is marginal. For dependable operation, a flame signal of greater than 1.0 A is required. To measure flame current, connect a meter capable of reading micro-amp current so the flame signal will be read thru the meter’s COM and A connections. The meter should read greater than
1.0 A.
Note: If the meter reads below “0” on scale, meter
leads are reversed; disconnect power and reconnect meter leads for proper polarity.
Main Burner Flame
The burner flame should be predominately blue in
color and well defined and centered at the tube entry as shown in Figure 33 above. Distorted flame or yellow tipping of natural gas flame, or a long yellow flame on propane, may be caused by lint and dirt accumulation inside burner or at burner ports, at air inlet between burner and manifold pipe, or debris in the main burner orifice. Soft brush or vacuum clean affected areas.
Poorly defined, substantially yellow flames, or
flames that appear lazy, indicate poor air supply to burners or excessive burner input. Verify gas supply type and manifold pressure with rating plate.
Poor air supply can be caused by obstructions or
blockage in heat exchanger tubes or vent discharge pipe. Inspect and clean as necessary to eliminate blockage. Vacuum any dirt or loose debris. Clean heat exchanger tubes with stiff brush. Poor flame characteristics can also be caused by flue gas recirculation into combustion air supply. If
OAU-SVX02F-EN 41
Startup
Inducer motor
Ignition Controllers
On/Off gas valve
On/Off gas valve
Manifold gas pressure tap
Manifold gas pressure tap
Air-proving switch
Condensate drain (TYP. 2)
Inducer blower
Modulating valve inlet pressure tap
Flame sensor
High limit switch
Rollout switch
Rollout switch
Modulating gas valve
Minimum/maximum inlet pressure = 7 IN. WC/14 IN. WC (1.7 KPA/3.5 KPA) for natural gas and 10 in. WC/14 in. WC
(2.5 KPA/3.5 KPA) for propane Minimum/maximum inlet pressure = 7 IN. WC/14 IN. WC (1.7 KPA/3.5 KPA) for natural gas and 10 in. WC/14 in. WC (2.5 KPA/3.5 KPA) for propane
Figure 34. OAB/OAG indirect gas-fired furnace components
Safety Controls
Air Pressure Switch. An air pressure switch is provided
as part of the control system to verify airflow through draft inducer by monitoring the difference in pressure between the draft inducer and the atmosphere. If sufficient negative pressure is not present, indicating lack of proper air movement through heat exchanger, the switch opens shutting off gas supply though the ignition control module. On units with two speed draft inducer operation, a dual air pressure switch is used, monitoring high and low speed pressures. The air pressure switches have fixed settings and are not adjustable.
Rollout Switch (Manual Reset). The furnace module
is equipped with manual reset rollout switch(es) in the event of burner flame rollout. The switch will open on temperature rise and shut-off gas supply through the ignition control module. Flame rollout can be caused by insufficient airflow for the burner firing rate (high gas pressure), blockage of the vent system or in the heat exchanger. The furnace module should not be placed back in operation until the cause of rollout condition is identified and corrected. The rollout switch can be reset by pressing the button on top of the switch.
High Limit Switch. The furnace module is equipped
with a fixed temperature high limit switch mounted on the vestibule panel that shuts off gas to the heater through the ignition control module in the event of reduced airflow over the heat exchanger tubes. Reduced airflow can be caused by indoor fan failure, dirty or blocked filters, or restriction of the air inlet or outlet to the unit. The high limit switch will automatically reset when the air temperature drops to approximately 30°F below the limit setpoint. Determine the cause of the reduced air flow and correct.
42 OAU-SVX02F-EN
Maintenance
Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the power is applied.
Monthly Maintenance
Before completing the following checks, turn the unit OFF and lock the main power disconnect switch open.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.Verify that no power is present with a voltmeter.
AVERTISSEMENT
Risque d’électrocution !
Le non-respect de cette consigne peut entraîner des blessures graves, voire mortelles. Avant toute intervention, coupez l’alimentation électrique, y compris aux sectionneurs à distance. Suivez scrupuleusement les procédures de verrouillage/mise hors service préconisées pour empêcher tout rétablissement accidentel de l’alimentation électrique.
Filters
Inspect the return air filters. Clean or replace them if necessary. Refer to the unit Service Facts for filter information.
Supply/Return Air Smoke Detector Maintenance
Airflow through the unit is affected by the amount of dirt and debris accumulated on the indoor coil and filters.
To insure that airflow through the unit is adequate for proper sampling by the return air smoke detector, complete adherence to the maintenance procedures, including recommended intervals between filter changes, and coil cleaning is required.
Periodic checks and maintenance procedures must be performed on the smoke detector to insure that it will function properly.
For detailed instructions concerning these checks and procedures, refer to the appropriate section(s) of the smoke detector Installation and Maintenance Instructions provided with the literature package for this unit.
Cooling Season
Check the unit’s drain pans and condensate piping to ensure that there are no blockages.
Inspect the evaporator and condenser coils for dirt, bent fins, etc. If the coils appear dirty, clean them according to the instructions described in “Condenser
Coil Cleaning,” p. 43.
Manually rotate the condenser fan(s) to ensure free movement and check motor bearings for wear. Verify that all of the fan mounting hardware is tight.
Inspect the F/A-R/A damper hinges and pins to ensure that all moving parts are securely mounted. Keep the blades clean as necessary.
Verify that all damper linkages move freely; lubricate with white grease, if necessary.
Check supply fan motor bearings; repair or replace the motor as necessary.
Check the fan shaft bearings for wear. Replace the bearings as necessary.
Verify that all wire terminal connections are tight.
Remove any corrosion present on the exterior surfaces of the unit and repaint these areas.
Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping connections, etc.).
Make sure that all retaining screws are reinstalled in the unit access panels once these checks are complete.
With the unit running, check and record the: ambient temperature; compressor suction and discharge pressures; superheat; Record this data on an “operator’s maintenance log” like the one shown in
Table 9, p. 46. If the operating pressures indicate a
refrigerant shortage, measure the system superheat.
Note: Do NOT release refrigerant to the atmosphere! If
adding or removing refrigerant is required, the service technician must comply with all federal, state and local laws.
Heating Season
Inspect the unit’s air filters. If necessary, clean or replace them.
Check supply fan motor bearings; repair or replace the motor as necessary.
Inspect both the main unit control panel and heat section control box for loose electrical components and terminal connections, as well as damaged wire insulation. Make any necessary repairs.
Verify that the electric heat system operates properly.
Condenser Coil Cleaning
Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by minimizing: compressor head pressure and amperage draw; evaporator water carryover; fan brake horsepower, due to increase static pressure losses; airflow reduction.
OAU-SVX02F-EN 43
Maintenance
At least once each year, or more often if the unit is located in a “dirty” environment, clean the condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
Microchannel (MCHE) Coils
NOTICE
Coil Damage!
Failure to follow instructions below could result in coil damage. DO NOT use any detergents with microchannel condenser coils. Use pressurized water or air ONLY, with pressure no greater than 600psi.
For additional information regarding the proper microchannel coil cleaning procedure, refer to service bulletin RT-SVB83*-EN.
Due to the soft material and thin walls of the MCHE coils, the traditional field maintenance method recommended for Round Tube Plate Fin (RTPF) coils does not apply to microchannel coils.
Moreover, chemical cleaners are a risk factor to MCHE due to the material of the coil. The manufacturer does not recommend the use of chemical cleaners to clean microchannel coils. Using chemical cleaners could lead to warranty claims being further evaluated for validity and failure analysis.
The recommended cleaning method for microchannel condenser coils is pressurized water or air with a non­pinpoint nozzle and an ECU of at least 180 with pressure no greater than 600 psi. To minimize the risk of coil damage, approach the cleaning of the coil with the pressure washer aimed perpendicular to the face of the coil during cleaning. Optimum clearance between the sprayer nozzle and the microchannel coil is 1 in.–3 in.
Round Tube Plate Fin (RTPF) Coils
To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-up type or a high-pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX A.C.”, “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline (pH value exceeds 8.5), add an inhibitor.
WARNING
Hazardous Chemicals!
Failure to follow all safety instructions below could result in death or serious injury. Coil cleaning agents can be either acidic or highly alkaline and can burn severely if contact with skin occurs. Handle chemical carefully and avoid contact with skin. ALWAYS wear Personal Protective Equipment (PPE) including goggles or face shield, chemical resistant gloves, boots, apron or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices.
AVERTISSEMENT
Produits chimiques dangereux !
Le non-respect de toutes les consignes de sécurité indiquées ci-après pourrait entraîner des blessures graves voire mortelles. Les agents de nettoyage pour serpentin peuvent être soit acides, soit fortement alcalins et peuvent entraîner des brûlures graves au contact de la peau. Manipulez les produits chimiques avec prudence et évitez tout contact avec la peau. Portez TOUJOURS un équipement de protection individuel (EPI), y compris des lunettes ou un masque facial, des gants résistant aux produits chimiques, des bottes, un tablier ou une combinaison conformément aux exigences. Pour la sécurité personnelle, voir les fiches de données de sécurité du fabricant pour l’agent de nettoyage et suivre toutes les pratiques de manipulation préconisées.
1. Remove enough panels from the unit to gain access to the coil.
2. Protect all electrical devices such as motors and controllers from any over spray.
3. Straighten any bent coil fins with a fin comb.
WARNING
Hazardous Pressures!
Failure to follow safety precautions below could result in coil bursting, which could result in death or serious injury. Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil.
44 OAU-SVX02F-EN
AVERTISSEMENT
Pressions dangereuses !
Tout manquement aux consignes de sécurité préconisées ci-dessous risquerait d’entraîner un éclatement du serpentin susceptible de provoquer des blessures graves voire mortelles. Les serpentins contiennent du fluide frigorigène sous pression. Lors du nettoyage des serpentins, maintenez la température de l’agent de nettoyage pour serpentin à moins de 65,5 °C (150 °F) pour éviter toute pression excessive dans le serpentin.
4. Mix the detergent with water according to the manufacturer’s instructions. If desired, heat the solution BUT DO NOT EXCEED 150ºF maximum to improve its cleansing capability.
5. Pour the cleaning solution into the sprayer. If a high­pressure sprayer is used:
a. do not allow sprayer pressure to exceed 600 psi.
b. the minimum nozzle spray angle is 15°.
c. maintain a minimum clearance of 6 in. between the
sprayer nozzle and the coil.
d. spray the solution perpendicular (at 90°) to the coil
face.
6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes.
7. Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be dirty, repeat Step 6 and Step 7.
9. Reinstall all of the components and panels removed in
Step 1 and any protective covers installed in Step 2.
Note: For units equipped with hail guards follow
reinstallation procedure listed below.
Maintenance
_____________________________________________________
_____________________________________________________
_____________________________________________________
_____________________________________________________
— connection(s)
_____________________________________________________
_____________________________________________________
_____________________________________________________
Final Process
For future reference, you may find it helpful to record the unit data requested below in the blanks provided.
(1) Complete Unit Model Number:
_____________________________________________________
_____________________________________________________
_____________________________________________________
(2) Unit Serial Number:
_____________________________________________________
_____________________________________________________
_____________________________________________________
(3) Wiring Diagram Numbers (from unit control panel)
— schematic(s)
_____________________________________________________
OAU-SVX02F-EN 45
Maintenance
Table 9. Sample maintenance log
Refrigerant Circuit #1 Refrigerant Circuit #2
Suct.
Press.
Date
Current
Ambient
Temp F/C
Compr.
Oil Level
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
Psig/kPa
Disch.
Press
Psig/kPa
Liquid
Press
Psig/kPa
Super-
heat F/C
Sub-cool
F/C
Compr.
Oil Level
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
Suct.
Press.
Psig/kPa
Disch.
Press
Psig/kPa
Liquid
Press
Psig/kPa
Super-
heat F/C
Sub-cool
F/C
46 OAU-SVX02F-EN
Performance Data
Table 10. OABD general data—cooling 3–5 tons high efficiency
3 Tons 4 Tons 5 Tons
OABD036A OABD048A OABD060A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 41,462 (12.15) 55,709 (16.33) 66,870 (19.60) Nominal cfm (m
Compressor
Number 1 1 1 Type Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2 2 2 FPI 14 14 14
Indoor Coil
Type Propeller Propeller Propeller Tube Size—OD, in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 4 4 4 FPI 12 12 12 Refrigerant Control TXV TXV TXV Drain Connection Size, in. (mm) 3/4 (20) 3/4 (20) 3/4 (20)
Outdoor Fan
Type Propeller Propeller Propeller Number Used 1 1 1 Diameter, in. (mm) 27 27 27 Drive Type Direct Direct Direct No. Speeds 1 1 1 CFM (m Number Motors 1 1 1 Motor HP (kW), per motor 1.0 (0.75) 1.0 (0.75) 1.0 (0.75) Motor RPM 1140 1140 1140
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Number Used 1 1 1 Diameter Varies Varies Varies Drive Type Direct Drive Direct Drive Direct Drive Number Motors 1 1 1 Motor HP (kW), Standard–Oversized 2.68–4.0 (2–3) 2.68–4.0 (2–3) 2.68–4.0 (2–3) Motor RPM Varies Varies Varies
Filters
Type Furnished Varies Varies Varies Evap Size, in. (Qty) 20 x 24 x 2 (2) 20 x 24 x 2 (2) 20 x 24 x 2 (2) Type Furnished MERV-8 MERV-8 MERV-8 ERV Size, in. (Qty) 20 x 24 x 2 (4) 20 x 24 x 2 (4) 20 x 24 x 2 (4)
Refrigerant Charge, lb of R-410A
3
/h) 500–2000 (850–3398) 500–2000 (850–3398) 500–2000 (850–3398)
2
(m2) 11 (1.02) 11 (1.02) 11 (1.02)
2
(m2) 4.17 (0.39) 4.17 (0.39) 4.17 (0.39)
3
/h) 7,000 (11,893) 7,000 (11,893) 7,000 (11,893)
See Nameplate See Nameplate See Nameplate
OAU-SVX02F-EN 47
Performance Data
Table 11. OABD general data—cooling 6–9 tons high efficiency
6 Tons 7 Tons 8 Tons 9 Tons
OABD072A OABD084A OABD096A OABD108A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 78,600 (23.04) 88,768 (26.02) 99,099 (29.04) 108,214 (31.71) Nominal cfm (m
Compressor
Number 1111 Type Scroll Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2222 FPI 14141414
Indoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 46 46 46 46 FPI 12121212 Refrigerant Control TXV TXV TXV TXV Drain Connection Size, in. (mm) 3/4 (20) 3/4 (20) 3/4 (20) 3/4 (20)
Outdoor Fan
Type Propeller Propeller Propeller Propeller Number Used 1111 Diameter, in. (mm) 27 27 27 27 Drive Type Direct Direct Direct Direct No. Speeds 1111 CFM (m Number Motors 1111 Motor HP (kW), per motor 1.0 (0.75) 1.0 (0.75) 1.0 (0.75) 1.0 (0.75) Motor RPM 1140 1140 1140 1140
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Backward Curved Number Used 1111 Diameter Varies Varies Varies Varies Drive Type Direct Drive Direct Drive Direct Drive Direct Drive Number Motors 1111 Motor HP (kW), Standard–Oversized 2.68–4.0 (2–3) 2.68–4.0 (2–3) 2.68–4.0 (2–3) 2.68–4.0 (2–3) Motor RPM Varies Varies Varies Varies
Filters
Type Furnished Varies Varies Varies Varies Evap Size, in. (Qty) 20 x 24 x 2 (2) 20 x 24 x 2 (2) 20 x 24 x 2 (2) 20 x 24 x 2 (2) Type Furnished MERV-8 MERV-8 MERV-8 MERV-8 ERV Size, in. (Qty) 20 x 24 x 2 (4) 20 x 24 x 2 (4) 20 x 24 x 2 (4) 20 x 24 x 2 (4)
Refrigerant Charge, lb of R-410A
3
/h) 625–3000 (1061–5097) 625–3000 (1061–5097) 625–3000 (1061–5097) 625–3000 (1061–5097)
2
(m2) 11 (1.02) 11 (1.02) 11 (1.02) 11 (1.02)
2
(m2) 6.56 (167) 5.69 (145) 6.56 (167) 5.69 (145) 6.56 (167) 5.69 (145) 6.56 (167) 5.69 (145)
3
/h) 7,000 (11,893) 7,000 (11,893) 7,000 (11,893) 7,000 (11,893)
See Nameplate See Nameplate See Nameplate See Nameplate
48 OAU-SVX02F-EN
Performance Data
Table 12. OAGD general data—cooling 10–17 tons high efficiency
10 Tons 12 Tons 15 Tons 17 Tons
OAGD120A OAGD144A OAGD180A OAGD210A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 150,692 (44.16) 165,990 (48.65) 206,544 (60.53) 230,212 (67.47)
CFM
Nominal cfm (m3/h) 1250–2500 (2124–4248) 1500–3000 (2549–5097) 1875–3750 (3186–6371) 2125–4250 (3610–7221)
Compressor
Number 2222 Type Scroll Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2222 FPI 14141414
Indoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 46 46 46 46 FPI 12121212 Refrigerant Control TXV TXV TXV TXV Drain Connection Size, in. (mm) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1)
Outdoor Fan
Type Propeller Propeller Propeller Propeller Number Used 2223 Diameter, in. (mm) 27 (685.8) 27 (685.8) 27 (685.8) 27 (685.8) Drive Type Direct Direct Direct Direct No. Speeds 1111 CFM (m Number Motors 2223 Motor HP (kW), per motor 1 (0.75) 1 (0.75) 1 (0.75) 1 (0.75) Motor RPM 1,140 1,140 1,140 1,140
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Backward Curved Number Used 1–2 1–2 1–2 1–2 Diameter Varies Varies Varies Varies Drive Type Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Number Motors 1–2 1–2 1–2 1–2 Motor HP (kW), Standard–Oversized 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) Motor RPM, Standard–Oversized Varies Varies Varies Varies
Filters
Type Furnished Refer to “OAU Filter Number Size Recommended
Refrigerant Charge, lb of R-410A
2
(m2) 25 (2.32) 25 (2.32) 25 (2.32) 25 (2.32)
2
(m2) 10.0 (0.93) 10.0 (0.93) 10.0 (0.93) 12.0 (1.11)
3
/h) 14,000 (23,786) 14,000 (23,786) 14,000 (23,786) 21,000 (35,679)
Guide” in “Appendix,”
p. 56
See Nameplate See Nameplate See Nameplate See Nameplate
Refer to “OAU Filter
Guide” in “Appendix,”
p. 56
Refer to “OAU Filter
Guide” in “Appendix,”
p. 56
Refer to “OAU Filter
Guide” in “Appendix,”
p. 56
OAU-SVX02F-EN 49
Performance Data
Table 13. OAGD general data—cooling 20–30 tons high efficiency
20 Tons 22 Tons 25 Tons 30 Tons
OAGD240A OAGD264A OAGD300A OAGD360A
Cooling Performance
Gross Cooling Capacity, Btu (kW) 286,302 (83.91) 319,026 (93.50) 368,012 (107.85) 395,596 (115.94)
CFM
Nominal cfm (m3/h)
2500–5000
(4248–8495)
Compressor
Number 2222 Type Scroll Scroll Scroll Scroll
Outdoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) 3/8 (9.5) Face Area, ft Rows 2222 FPI 14141414
2
(m2) 37 (3.44) 37 (3.44) 37 (3.44) 37 (3.44)
Indoor Coil
Type High Performance High Performance High Performance High Performance Tube Size—OD, in. (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) Face Area, ft Rows 46 46 46 46 FPI 12121212 Refrigerant Control TXV TXV TXV TXV Drain Connection Size, in. (mm) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1) 3/4 (19.1)
2
(m2) 12.0 (1.11) 12.0 (1.11) 15.0 (1.39) 15.0 (1.39)
Outdoor Fan
Type Propeller Propeller Propeller Propeller Number Used 3333 Diameter, in. (mm) 27 (685.8) 27 (685.8) 27 (685.8) 27 (685.8) Drive Type Direct Direct Direct Direct No. Speeds 1111
3
CFM (m Number Motors 3333 Motor HP (kW), per motor 1 (0.75) 1 (0.75) 1 (0.75) 1 (0.75) Motor RPM 1,140 1,140 1,140 1,140
/h) 21,000 (35,679) 21,000 (35,679) 21,000 (35,679) 21,000 (35,679)
Indoor Fan
Type Backward Curved Backward Curved Backward Curved Backward Curved Number Used 1–2 1–2 1–2 1–2 Diameter Varies Varies Varies Varies Drive Type Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Direct or Belt Drive Number Motors 1–2 1–2 1–2 1–2 Motor HP (kW), Standard–Oversized 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) 2–12 (1.49–8.95) Motor RPM, Standard–Oversized Varies Varies Varies Varies
Filters
Type Furnished Refer to “OAU Filter Number Size Recommended
Refrigerant Charge, lb of R-410A
Guide” in “Appendix,”
p. 56
See Nameplate See Nameplate See Nameplate See Nameplate
2750–5500
(4672–9345)
Refer to “OAU Filter
Guide” in “Appendix,”
p. 56
3125–6250
(5309–10619)
Refer to “OAU Filter
Guide” in “Appendix,”
p. 56
3750–7500
(6371–12743)
Refer to “OAU Filter
Guide” in “Appendix,”
p. 56
50 OAU-SVX02F-EN
Performance Data
Superheat and Refrigeration Circuit Data
Figure 35. Refrigeration diagram: single compressor
without reheat
Figure 36. Refrigeration diagram: single compressor
with reheat
OAU-SVX02F-EN 51
Performance Data
Figure 37. Refrigeration diagram: dual compressor
without reheat
Figure 38. Refrigeration diagram: dual compressor with
reheat
52 OAU-SVX02F-EN
Alarms and Troubleshooting
Microprocessor Control
The Main Unit Display and RTRM have the ability to provide the service personnel with some unit diagnostics and system status information.
WARNING
Hazardous Service Procedures!
Failure to follow all precautions in this manual and on the tags, stickers, and labels could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the following instructions: Unless specified otherwise, disconnect all electrical power including remote disconnect and discharge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks.
AVERTISSEMENT
Procédures d’entretien dangereuses !
Le non-respect de toutes les précautions contenues dans ce manuel ainsi que sur les étiquettes et les autocollants peut entraîner des blessures graves voire mortelles.
Les techniciens, afin d’être protégés des éventuels risques électriques, mécaniques et chimiques, DOIVENT suivre les précautions contenues dans ce manuel, sur les étiquettes et les autocollants, ainsi que les instructions suivantes : Sauf indication contraire, coupez toute l’alimentation électrique y compris les disjoncteurs à distance et déchargez tous les dispositifs de stockage d’énergie comme les condensateurs avant l’entretien. Respectez les procédures de verrouillage et d’étiquetage appropriées pour éviter tout risque de remise sous tension accidentelle. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
1. Verify that the Liteport LED on the RTRM is burning continuously. If the LED is lit, go to Step 3.
2. If the LED is not lit, verify that 24 Vac is presence between J1-1 and J1-2. If 24 Vac is present, proceed to
Step 3. If 24 Vac is not present, check the unit main
power supply, check transformer (TNS1). Proceed to
Step 3 if necessary.
3. Utilizing “Method 1” in the RTRM “System Status Checkout Procedure”, check the following:
System status
Cooling status
If a System failure is indicated, proceed to Step 4. If no failures are indicated, proceed to Step 5.
4. If a System failure is indicated, recheck Step 1 and Step
2. If the LED is not lit in Step 1, and 24 Vac is present in Step 2, the RTRM has failed. Replace the RTRM.
5. If no failures are indicated, use one of the override options to start the unit. Following the Override procedure will allow you to check all of the operating modes, and all of the external controls (relays, contactors, etc.) for each respective mode.
6. Refer to the sequence of operations for each mode, to assist in verifying proper operation. Make the necessary repairs and proceed to Step 7.
7. If no abnormal operating conditions appear in the Override mode, release the override and turn the power “Off” at the main power disconnect switch.
System Alarms
The Main Unit Display has built in alarms to help the operator troubleshoot system failures. This section will describe these alarms and provide a guide to troubleshooting the all unit operating modes.
Comprehensive system alarms and diagnostics are accessed through the Alarms icon at the unit display discussed later in the section, or through Tracer TU programming on connected computer. Sensor failures may be viewed through the Alarms icon.
If an alarm is present, the main indicator light on the UC600 will blink red. If the optional unit display is installed, the Alarm icon on the display will register ALARM, illuminate red and flash.
Important: The space temperature sensor (SPTC) and
space relative humidity sensor (SPHC) will read failed if they are not connected; they will Alarm as “In Fault.”
Sensor Failure Alarm Display
Press the Alarm button on the Home display of the Unit Display to display system sensor status as described in
Table 14 and Table 15, p. 54.
OAU-SVX02F-EN 53
Alarms and Troubleshooting
Table 14. TOAU UC600 alarms
Point Diagnostic Possible Cause
VFD not operating Outdoor and/or Return Air Dampers not
Operating Properly
Indoor Fan
1
Failure
OAD Proving
3
Switch
Discharge Air
6
Temp Source Failure
8 Fire Shutdown BAS ONLY
Low Temp
10
Lockout
Space Temp
11
Source Failure
OA Temp Source
13
Failure
OA Humidity
14
Source Failure
High Temp
15
Lockout
17 System Lockout
Space RH Source
19
Failure
ERV Leaving Air
32
Condition Failure
Indoor Fan Motor Failure Indoor Fan Failure Switch IFFS (pressure)
Failure IFFS Tubing damaged or not properly
connected Refer to startup procedure No voltage at actuator Failed OAD power transformer No continuity thru end switch (check at UC) Note: If unit optional RA damper is
installed, send switch on OAD is always proven
BAS communication down Failed sensor or improper sensor
installation
Heat Overridden OFF Compressor(s) Overridden ON Setpoint Failures Incorrect DAT sensor malfunction Reference Table 15, p. 54 for heat failure
issues BAS communication down Failed sensor or improper sensor
installation BAS communication down Failed sensor or improper sensor
installation BAS communication down Failed sensor or improper sensor
installation Humidity Wiring is polarity sensitive Heat Overridden ON Low discharge air volume Dirty air filters High gas heater manifold pressure OA/RA damper position incorrect High temp limit not properly installed or
wired DAT sensor malfunction Check all Alarms External safety device failed open BAS communication down Failed sensor or improper sensor
installation Humidity Wiring is polarity sensitive Failed RH or temperature sensor Incorrectly installed or connect RH or T emp
sensor
Table 14. TOAU UC600 alarms (continued)
Point Diagnostic Possible Cause
Applies to 5:1 and 10:1 Gas Heaters Only T rips after heat command “ON” and no GV
status offer 1 minute Refer to unit “Service Facts” heat control
LED status legend
42 Heat Failure
No gas, low gas pressure or high gas pressure to unit
Unit Manual shutoffs closed Heater inducer failure Heat relay failure Loose or incorrect wiring
Table 15. TOAU UC600 troubleshooting
Trouble Possible Cause
No power supply to unit disconnect switch Power disconnect tripped Lockout alarm mode
Unit Not Running
No Heat
No Compressor
Wide Discharge Temp Swings
Space too Hot, Cold or Humid
IFM or PEX VFD OC Trip
EX VFD only run to Min HZ Setting
ERV Will Not Run
Emergency Stop condition exists Unit in Unoccupied mode Discharge air sensor failed or not installed and
connected to unit No gas supply to unit Unit manual gas valve(s) closed Heater high limit tripped Heat relay not energized Conditions do not warrant call for heat Heater control module malfunction Roll out switch trip Main gas on-off switch OFF Inducer fan failure Heater air proving switch not making or failed Compressor limit switch(es) open Compressor relay not energized or failed Conditions do not warrant call for cooling or
dehumidification Discharge air sensor position must be at least
4 ft.-0 in. away from unit outlet Min and Max gas heater manifold pressures not set
correctly Setpoints not adjusted properly Space sensors not correctly located or wired Malfunctioning space sensor Overcurrent alarm requires max Hz sett ing on VFD
be checked and set to not exceed motor nameplate amps
If supplied with RA pressure transducer and modulating damper setup is not installed or properly wired.
ERV leaving air temp below 34°F low temp cutout Interlocked with Exhaust fan if exhaust is not
running ERV will be OFF
54 OAU-SVX02F-EN
Alarms and Troubleshooting
Table 15. TOAU UC600 troubleshooting (continued)
Trouble Possible Cause
High fire gas manifold pressure too high Supply fan speed too low
Unit Trips Heater High Limit
Protonode Not Communicating
Dirty or clogged filters Restricted discharge air duct Temperature of air entering heater too high Defective high limit
Change Baud rate on UC600 to 38,400
RTRM Failure Modes
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
Cool Failure
Measure the voltage between terminals J6-8 and J6-6.
Cool Operating = approximately 32 Vdc
Cool Off = less than 1 Vdc, approximately 0.75 Vdc
Cooling Failure = voltage alternates between 32 Vdc and
0.75 Vdc
AVERTISSEMENT
Composants électriques sous tension !
Le non-respect de toutes les consignes de sécurité lors de la manipulation de composants électriques sous tension peut entraîner des blessures graves, voire mortelles. S’il est nécessaire de travailler avec des composants électriques sous tension, demandez à un électricien qualifié et agréé ou à une autre personne ayant la formation nécessaire pour manipuler des composants électriques sous tension d’exécuter ces tâches.
Following is the listing of RTRM failure indication causes.
System Failure
Check the voltage between RTRM terminals 6 and 9 on J6, it should read approximately 32 Vdc. If no voltage is present, a System failure has occurred. Refer to Step 4 in
“Microprocessor Control,” p. 53 for the recommended
troubleshooting procedure.
Cooling Failure
CLP1 has opened during the 3 minute minimum “on time” during four consecutive compressor starts, check CLP1 by testing voltage between the J1-8 and J3-2 terminals on the RTRM and ground. If 24 Vac is present, the CLP has not tripped. If no voltage is present, CLP has tripped.
System Failure
Measure the voltage between terminals J6-9 and J6-6.
Normal Operation = approximately 32 Vdc
System Failure = less than 1 Vdc, approximately 0.75 Vdc
OAU-SVX02F-EN 55
Appendix
OAU Filter Guide
Table 16. OAB units
Evaporator
Thickness MERV Qty Height Width
2 in. 8, 13 2 20 24 4in. 14 2 20 24
Auxiliary Module
Return Air
Thickness MERV Qty Height Width
2 in. 8 4 20 24
Outside Air
Thickness MERV Qty Height Width
2 in. 8 4 20 24
(a)No filters will be provided on the ou tside air path of the auxiliary module
if electric preheat is provided.
Table 17. OAG units
Evaporator
Thickness MERV Qty Height Width
2in. 8
2 in. 13
4in. 14
Auxiliary Module
Return Air
Thickness MERV Qty Height Width
2in. 8
Outside Air
Thickness MERV Qty Height Width
2in. 8
Inlet
Thickness Material Qty Height Width
2 in. Aluminum Mesh 6 16 24
(a)No filters will be provided on the ou tside air path of the auxiliary module
if electric preheat is provided.
(a)
216 20 416 25 216 20 416 25 216 20 416 25
216 20 416 25
(a)
216 20 416 25
56 OAU-SVX02F-EN
Field Installation of Factory­Provided Sensors
Figure 39. VELSEN-0021 installation instructions
Appendix
OAU-SVX02F-EN 57
Appendix
Figure 40. BAYSENS036A installation instructions
58 OAU-SVX02F-EN
Figure 41. MZVAV DSPS document
Appendix
OAU-SVX02F-EN 59
Appendix
Figure 42. VELCON-0350 installation instructions for modulating OA/RA dampers w/economizer and an exhaust fan
60 OAU-SVX02F-EN
Horizon™ Dedicated Outdoor Air Unit Startup Form
Date : __________________
Job Name
:_____________________________________________________________________
Address :_____________________________________________________________________
_____________________________________________________________________
Serial Number: ________________________________ Tag : __________________________
Start up contractor : _____________________________________________________________
Address :_____________________________________________________________________
_____________________________________________________________________
1 . Is there any visible shipping damage?
_____YES
_____NO
2. Is the unit level?
_____YES
_____NO
3. Are the unit clearances adequate for service and operation?
_____YES
_____NO
4. Do all access doors open freely and are the handles operational? _____YES _____NO
5 . Have all electrical connections been tested for tightness? _____YES _____NO
6 . Does the electrical service correspond to the unit nameplate? _____YES _____NO
7. On 208/230V units, has transformer tap been checked? _____YES _____NO
8. Have the damper assemblies been inspected? _____YES _____NO
9. Are the air filters installed with proper orientation? _____YES _____NO
10. Have condensate drain and p-trap been connected? _____YES _____NO
11. Have the crankcase heaters been on for 24 hrs. _____YES _____NO
Discharge temp Space Temp / Humidity
Supply Duct Pressure Transducer Return Duct / Space Pressure Transducer
Quantity
Orientatio
n Clean
#L1L2L3Amps
123
4
Factory supplied sensors installed
Filters
Location
Pre Startup Checklist
Size
Installing contractor should verify the following items.
Program Control
Non Heat Pump: Discharge Space Single Zone VAV Multi Zone VAV
Heat Pump: Discharge Space Single Zone VAV Multi Zone VAV
Compressors
Model
Serial
p
Appendix
OAU-SVX02F-EN 61
Appendix
Wheel Spins freely Check Rotation FLA:
Voltage
L1: L2: L3:
Amps: HP:
Ambient Dry Bulb Temperature_______°F Ambient Wet Bulb Temperature________°F
Water Cooled
No water leaks Water Flow :_______________ GPM
Water Inlet Temp :__________°F Water Outlet Temp: ___________°F
Air Cooled L1 L2 L3 Amps HP
Pressure Sat Temperature Line Temperature Subcooling Super Heat
Discharge
Suction
Liquid
Pressure Sat Temperature Line Temperature Subcooling Super Heat
Discharge
Suction
Liquid
Pressure Sat Temperature Line Temperature Subcooling Super Heat
Discharge
Suction
Liquid
Pressure Sat Temperature Line Temperature Subcooling Super Heat
Discharge
Suction
Liquid
Refrigeration System --Circuit 1
Supply Fan Assembly
Power Exhaust Fan Assembly
Energy Recover Wheel
Fan 2 - Alignment Name plate amps: Actual Amps: Rotation Hrtz:
Fan 2 - Alignment Name plate amps: Actual Amps: Rotation Hrtz:
Fan 2 - Alignment Name plate amps: Actual Amps: Rotation Hrtz:
Operation check
Two Position
Modulating
Refrigeration System --Circuit 2
HEATING -- Refrigeration System (Heat Pump Only) --Circuit 1
HEATING -- Refrigeration System (Heat Pump Only) --Circuit 2
Condenser Configuration
Ambient Temperature
Dampers
Damper set up
Fan 1
Fan 2
Fan 3
Fan 4
Fan 2 - Alignment Name plate amps: Actual Amps: Rotation Hrtz:
Horizon™ Dedicated Outdoor Air Unit Startup Form
62 OAU-SVX02F-EN
Horizon™ Dedicated Outdoor Air Unit Startup Form
1. Has the entire system been flushed and pressure checked?
2. Has the entire system been filled with fluid?
3. Has air been bled from the heat exchangers and piping?
4. Is the glycol the proper type and concentration (N/A if water)?
6. Has the water piping been insulated?
7. What is the freeze point of the glycol (N/A if water)?
Natural Gas Propane Purge Air from the lines
Low Fire High Fire
Heat 1
Heat 2
Heat 3
Amps L1: L2: L3:
Amps L1: L2: L3:
Electric Heat
Water / Glycol System
_____YES NO_____
_____YES NO_____
_____YES NO_____
_____YES NO_____
_____YES NO_____
_____YES NO_____
Gas Heat
Pre Heat:
Primary:
Appendix
OAU-SVX02F-EN 63
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient
ingersollrand.com
environments. Our people and our family of brands—including Club Car®, Ingersoll Rand®, Thermo King® and Trane®—work together to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress and enduring results.
Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
OAU-SVX02F-EN 30 Nov 2019
Supersedes OAU-SVX02E-EN (Dec 2018)
©2019 Ingersoll Rand
Loading...