Trane Flex II 170, Flex II, Flex II 175, Flex II 180, Flex II 177, Flex II 160, Flex II 100, Flex II 115, Flex II 125, Flex II 135, Flex II 165, Flex II 155 Original Instructions Manual
A. Warranty is based on th e general terms and conditions of the manufactu r e r . The warranty is void if t he equipment
is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the
control system or the electrical wiring is modified. Damage due to m isu se , lack of maintenance or f ail u r e to comply
with the manufact urer’s instructions or re c omm e n dations is not cove r e d b y t h e warran ty obligation. If the user does
not conform to the ru l e s o f t his manu al, it may entail cance l l at io n of warranty and liabilities by the manufacturer.
B. Warranty is twelve (12) months as from the dat e of first start up at installat io n place or eighteen ( 18) mo n ths
after delivery at the project or other delivery location indicated by the customer. The date the unit is operated for
the first time mean s the date reported in the “1st start up form” contained into the “unit log book ” . This form should
be filled in and sen t, within 8 days from the start up, to Trane.
C. The warranty is valid if all the installat ion and start-up instructions have been adhered to (both those which may
have come from Trane an d those coming from current practice), if the “ 1st start up form” has been f il led in and sent
to the Trane after sal e s department.
D. The warranty is subject to any faults or defects being reported within eight days from their discovery. The
warranty will only be applied if and when the p u rc h aser suspends use of the equipment as soon as a defect has been
found.
E. The warrant y is v al id if the first running of the unit is carried out b y a T ran e authorized assistance center.
F. The warrant y is su bject to regular maintenan c e of the unit which is appropriately indicat e d in the “unit log book”
located inside the electrical panel.
G. Warranty automat ical l y e n ds in case of payment s n ot fulfilled, non-performance of the contract and even if the
units show tampering without TRANE written approvals.
1.2
RECEIVING THE UNIT
On receiving the unit, it is up to the customer to check that there is no obviou s damage or pie ces missing. If this is so,
an immediate complaint must be made to the carrier for damage or for not-delivery and the Receiving Card to be found
inside the unit electrical panel must be filled in. Photographic evidence must be provided for macroscopic damage. The
card must be sent to Trane with in 8 days of receiving the goods: if it is not se n t b ack or de lay ed, the complaint will not
be accepted.
1.3
FACTORY INSPECTION
Trane units are inspected into the factory, in appropriate areas, in accordance with internal procedures. Each performance
test carried out on t he unit is possible only if the same condit ions are reproduced and maintained ( charge consistency ,
constant temperature and evaporation - condensation and recovery capacity, quality and tolerance of the measuring
instruments etc. ) in the test rooms.
The inspection conditions are those indicated by the customer in the ordering phase: if not otherwise specified, reference
should be made to the nominal performance indicated in the technical bulletin in force at the date of the Confirmation of
the Order.
2 SAFETY REGULATIONS
2.1
ACCESS TO DANGEROUS AREA
The access to the u n it d an gerous areas is usually obstru c t ed through protection panels, which are rem ovable, by using a
tool. Axial fans are p ro tected with accident p r e vention grilles.
For all the units which al l ow access to the cooling piping without security gratings (optional) o r c l osin g panelling, the
following precaut ion s mu st be taken:
-mark the areas with c ontact risks.
-apply warning sign s.
The danger zone mu st be of a suitable size to avoid an y c on tact, even accidental c on tact.
Trane declines any r e sponsibility for damage to things and unauthoriz ed personnel in case of absence of clear and
static limiting systems of the risk areas and of the relevant warning an d danger signs.
2.2
GENERAL PRECAUTIONS
The operator must only intervene on the unit commands; he or she must not open any panels except for the one which
gives access to the c omm an d module.
The installer must only intervene on the connections between the plant and the machine; he or she must not open any
machine panels nor carry out any commands.
The following precautions should be made when approaching or working on the unit:
• Use appropriate protection (glove s, glasses etc.) when u sin g an open flame (welding) or c om p r e sse d air.
• If the unit is loc ated in a closed environm e n t, wear hearing protection.
• Before disconnecting, rem oving tubes, filt e rs, joints or other line parts in tercept the connect ion tubes, empty them
until the pressure reaches that of the atmosphere.
• Do not use your h an ds to check for possible pressure losses.
• Always use tools w h ic h ar e in good condition; make sure the instructions h av e b een fu lly understood before using them.
• Make sure that any tools, e le ctrical cables or other loose objects have been removed before closing the unit and
starting it up again.
2.3
PRECAUTIONS AGAINST RISKS DUE TO THE REFRIGERANT
Refer to Safety Data Sheet. Refrigerant shall be always recovered before ope n ing any part of refrigeratin g circuit.
2.4
PRECAUTIONS AGAINST RESIDUAL RISKS
Prevention from risk s d u e to the command system
• make sure the instructions for use have been understood before carrying out any work on the control panel.
• always keep t h e instruction manual close at hand when working on the control panel.
• start up the unit only after having certified that it is correctly connected to the plant.
• inform the technician promptly of any alarms which appear on the unit.
• do not reset t he al ar ms to manual restart wit h ou t having first identified the cause and removed it.
2.5
PREVENTION AGAINST RESIDUAL MECHANICAL RISKS
• install the un it in accordance with the provisions of the f o llowin g manual.
• carry out all the maintenance op e r at io n s provided for by this manual regularly.
• wear a protective helmet before entering inside the unit.
• before open in g a machine panel make sure that it is firmly conne c ted by means of a hinge.
• do not touch t he air condensation batter ie s without having first put on protective gloves.
• do not remove the protections to the moving parts while the unit is running.
• before rest arting the unit make sure that the moving part prot e c tions are in the correct position.
2.6
PREVENTION AGAINST RESIDUAL ELECTRICAL RISKS
• connect the unit to the mains in accordance with the provisions of this manual.
• carry out all maint e nance operations regularly.
• before opening the control panel disconnect the unit from the mains by means of the external knife switch.
• check that the unit has been earthen correctly before starting it up.
• control all the electrical connect ions and the connection cable s paying particular attention to the state of iso lation;
replace the cables which are clearly worn or damaged.
• carry out periodic checks of the w irin g inside the panel.
• do not use cabl e s with an inappropriate se c tion or flying connect ions not even for a limite d p e r iod or in an emergency.
2.7
PREVENTION AGAINST RESIDUAL RISKS OF A DIFFERENT NATURE
• the r e sidual risks due to pressur e ar e m ain ly coming from a failure of the safety devices. To prev e nt them it is
necessary to check and replace them when required
• carry out the plant connections to the unit by following the indications reported on the following manual and on the
panels of the unit itself.
• if a part is disassembled, make sure t h at it is correctly reassembl e d before restarting t h e unit.
• do not tou ch t h e discharg e l ine of the compressor, the compressor itself or any other tube or component which is
inside the machine without putting on protective gloves.
• keep a fire ex t inguisher which is able t o p u t ou t fires on electrical equip m e n t near the machine.
• on units install e d inside, connect the refrigerant circuit sh ut off valve to a network o f tube s which are able to lead
the possible spillag e of refrigerating fl u id outside.
• eliminate any f l u id l oss inside or outside th e unit.
• collect the d isc h ar ge liquid and clean up an y possible oil leakage.
• periodically clean the compressor casing of t h e accumu late d d irt deposits.
• do not keep inflammable liquids near the unit.
• do not dispose o f the refrigerant fluid and the lubricating oil in the environment.
• welding should only be carried out on empty tubes; do not approach the tubes containing refrigerant fluid with
flames or other sources of heat.
• do not bend or strike tubes containing pressurized fluids.
2.8
PRECAUTIONS TO BE OBSERVED DURING MAINTENANCE OPERATIONS
Only authorised technic ian s may carry out maintenanc e op erations. Before carr ying out any mainten an c e the
following must be performed:
• isolate the unit from the mains electric ity by using the extern al k n ife switch.
• place a notice on t h e external knife swit ch w h ic h say s “do not use - maintenance in progress”.
WARNING! DO NOT REMOVE THE HIGH PRESSURE SWITCHES HP IF THE UNIT IS NOT COMPLETELY
SERIOUS INJURY!
• make sure that any possible on-off commands are disabled.
• use appropriate safety equipmen t (helmet, isolating g l oves, protective glasse s, safety shoes etc.).
If measurements or con trols must be carried ou t which require the mach in e to be running the followin g observations
must be followed:
• operate with the electrical pan e l open for as short a time as is possible.
• close the ele c t r ic al panel as soon as the individual measurement or co n trol has been carried out.
• for un its which are located outside, do not carry out interventions in dangerou s atmospheric conditions such as rain,
snow, fog etc.
The following pr e c au tions should also be taken at al l times:
• never dispose of fluids contained in the refrigerant circuit in to the environment.
• when replacing the el e ctr on ic car d always use appropriate equipment (extractor, anti-static brace l e t, etc.).
• if a compressor, the evaporator, th e c on densation batteries or an y other heavy part is to be re placed, make sure that
the lifting equipment matches the weight to be lifted.
• if the unit has an indepe nden t compre ssor compartment, do not open the ventilator compartment without having
first isolated the mac h in e using the main switch on the side of the pan el and only after having plac e d a sign which says
“do not use - maintenance in progress”.
• if modifications must be carried o u t to the cooling, hydraulic or electrical circuit of the unit, or to its command
logic, contact Trane.
• if particularly co mplicated assembly o r disassembly operations are to be carried out c ontact Trane.
• always use orig inal spare parts bought directly from Trane or from official dealers of the companies reporte d in the
list of recommended spare parts.
• if the unit is t o be m oved after a year of being in the site or if it has to be dismantled contact Trane.
VERY IMPORTANT
No high pressure safety valve is installed on the unit.
The unit fail safe is assured by cut-out of the electrical power sup p l y to the coils of the compressor contactors. T he cu t out action is carried ou t by the electrical cont ac t of the unit high pre ssu r e switch.
No Schrader valve is instal l e d in the port the unit h igh pressure switch is plugged into.
This implies that fol lo w in g instruction must be observed:
VOID OF REFRIG ERANT. FAILURE TO FOLLOW THIS INSTRUCTION COULD RESULT IN DEATH OR
2.9
MANUAL ALARM RESET
If there is an alarm the u n it must not be manually r e set before having located an d e l imin ated the cause of the f au l t.
Repeated manual r e se ts may cause unit damage an d the warranty to be annulled.
CHILLER MODE
kit -10°C
3 OPERATING LIMITS
3.1
STORAGE
The units can be st o red within the following environmental cond it io n s:
Min ambient temper ature : -10°C
Max ambient tempe r ature : 53°C
Max relative humidity : 95% not condensable
CAUTION: The storage in a very hig h h u midity space (condensation ) can damage electron ic components.
3.2
OPERATING LIMITS
Unit operation is perm itted within the lim its indicated in the d iag r am provided in 3.3.
CAUTION: The operation outside the limits specified may c au se the activation of t h e protections and disrupt
the operation of t h e un it and, in extreme cases, damage the unit.
In case of doubt, con tact Trane.
These operating lim it s apply to unit operating at full load.
3.3
OPERATING RANGE
OAT
= Outdoor Air Temperature [°C]
LWT
= Leaving Water Temperature [°C]
Low ambient kit down to -10°C:
• EC fans
Glycol
HEAT PUMP MODE
kit
-15°C
OAT
= Outdoor Air Temperature [°C]
LWT
= Leaving Water Temperature [°C]
Low ambient kit down to -15°C:
• Heater in control box
Pressure drop coefficient
Flow rate coefficient
1,02
1,033
1,05
1,072
1,095
1,124
ETHYLENE GLYCOL CORRECTION TABLE
% Ethylene glycol weight
Freezing temperature
Suggested security limit Cooling
capacity coefficient
Power input coefficient
Flow rate coefficient
In order to calculate performance with glycoled solutions multipl y main sizes by respect i ve co ef fici ent s.
°C -2 -3,9 -6,5 -8,9 -11,8 -15,6 -19 -23,4
°C 3 1 -1 -4 -6 -10 -14 -19
- 0,995 0,99 0,985 0,981 0,977 0,974 0,971 0,968
- 0,997 0,993 0,99 0,988 0,986 0,984 0,982 0,981
- 1,003 1,01 1,02 1,033 1,05 1,072 1,095 1,124
- 1,029 1,06 1,09 1,118 1,149 1,182 1,211 1,243
GLYCOL PERCENTAGE DEPENDING ON FREEZINGTEMPERATURE
% glycol according to the freezing temperature
Freezing temperature 0°C -5°C -10°C -15°C -20°C -25°C
% Ethylene glycol
5% 10% 15% 20% 25% 30% 35% 40%
5% 12% 20% 28% 35% 40%
In order to calculate performance with glycoled solutions multipl y main sizes by respect i ve co ef fici ent s.
IMPORTANT: Ove r sized water pump as on board un it pump is required for operation with glycol > 25%. If any doubt please contact
your local sales office.
IMPORTANT:
Correct lifting procedure
Figure 1
4 INSTALLATION
4.1
MOVING AND POSITIONING THE UNIT
The units have bee n d esigned to be lifted from above by means of eyebolts and h o les in the base members.
Use retractor bars t o keep the lifting wires or c h ain s away from the unit.
Lifting procedures provided with the unit have to be respected.
CAUTION
Do not use forklift trucks to lift the unit from below.
If equipment for lifting from above is not avail ab l e , using rollers may move the unit.
The surface on which the unit is placed must be flat and strong enough to withstand the weight of the unit while
running. In order to reduce the transmission of vibrations to the su p porting structures, f it sh oc k absorbers in every
fastening point. Rubber shock absorbers are recommended for units installed on the ground , spring shock absorber s f o r
units installed on roof s. Open spaces around th e unit must be provided for in order to allow for t h e passage of necessary
airflow and in order to allow normal maintenance to be carried out (as shown on general catalogues).
For example horizont al positioning of the u n it can l e ad to irreversible damage to the compressors.
Damage arising from incorrect transport will not be under warranty by the manufact ure r.
Immediately report an incorrect receipt of goods.
An arrow positioned up ward indicates the vertical position of the unit.
Make sure that dur in g transport the unit ALWAY S remains in the correct p osition!
minimum space requirements [mm]
Figure 2
4.2
MINIMUM SPACE REQUIREMENTS
Dimensional drawing sh al l be respected to avoid:
• Noise
• Incorrect heat exchange and ventilat ion
• Difficult mainten an ce or inaccessibility to components
It is fundamental to respect minimum distan c e s on all u n its, in order to en su re optimum ventilation for
the condenser coils. Limited installati on space could reduce th e normal air flow, thus signif ic an tly reducing
the unit performance and considerably increasing consumption of e le ct rical ene rg y .
CAUTION: in case two stand-alone units have to be inst all e d side by side, the distance of respect must
be doubled.
** As far as modular units are concerned no side space is required between any of the units and the
adjacent one. The minimum side space of 500 mm featured in Figure 2 is required only for the units
placed at the far sides of the modular system.
After the unit has re ach ed the final position, f ix the antivibration bolts.
4.3
PRECAUTIONS FOR DOMINANT WINDS
Avoid obstacles on suction and discharge sid es of the units. Respect the safety distances as sho w n on the units
dimensional drawings.
In case of presence of dominant winds in the installation area it is strict l y n e c e ssar y to avoid (for unit s with horizontal
flow fans) that such winds blow in front of the u n it (fans discharge side). In case of unit with vertical flow fans it is
strictly necessary to av o id installations w h e r e the dominant winds cou ld cause rejected hot air to co me back to the
condensing coils.
4.4
PRECAUTIONS AGAINST DIRECT SUNSHINE
Direct solar radiation c an raise the temperat u r e of condensation until it cau se s the unit shutdown or failure start-up of
the same by action of the high pressure switch.
4.5
PRECAUTIONS AGAINST THE PRESENCE OF FIREPLACES AND EXHAUST HOT AIR
Avoid installation of the machines downwind of chimneys, smokestacks and different e ffluent discharges.
4.6
PRECAUTIONS AGAINST THE PRESENCE OF FOLIAGE AND FOREIGN BODIES
Avoid installing the unit in the immediate v icin ity of plants that can p r e vent proper intake and discharge air.
4.7
CONTROL OF COMPRESSOR FASTENING
The compressors are fitted on shock absorber s. For fixing through spr in g anti-vibration moun ts, it is necessary to remove
blockages put to fast e n the compressors, as indicat e d on the label on compr e ssor s b o d y .
5 ACOUSTIC PROTECTION
When the sound level must be checked in particular, it is necessary to pay maximum WARNING in isolation from
the base of the unit properly applying the anti-vibration mounts (provided optionally). A lso, install flexible
joints on water connections.
6 ELECTRICAL POWER SUPPLY
The mains power supply characteristics have to match the unit’s absor p tion. The mains power su p ply tension must
correspond to the nominal value ± 10%, with a maximum difference between the phases of 2%.
All power supply w irin g must be sized and sele cted accordingly by the p roject engineer in accordance with standard IEC
60364. All wiring must comply with local code.
6.1
POWER CONNECTIONS
Protect the unit electric box power supply circuit with p rotection d evices (not included in the supplied
equipment). Connect the line terminals with a three-core cable of a section wh ich is ap propriate to the
machine absorption. The switch and the fu se s l ik e all the power connect ion s m u st co mp ly with the regulations
in force.
6.2
IMBALANCE BETWEEN THE SUPPLY TENSION PHASES
Do not run the electrical motors when the voltage unbalance between the phases is more than 2%.
Use the following formula to check:
% Imbalance = [(Vx – Vave) x 100/Vave]
Vave = (V1 + V2 + V3)/3
Vx = phase with greatest d i f ferenc e from Vave (without
regard to the sign)
IMPORTANT: If the mains voltage has an imbalance of above 2%, con t act the company, which distributes the electrical
energy. If the unit functions with a unit voltage imbalance between the phases of above 2% the warranty is invalid.
6.3
UNIT VOLTAGE PHASING
It is important that proper rotation of the compressors be establish ed before the unit is started. Proper mot or
rotation requires confirmation of the el e c t r ic al phase sequence of th e p ower supply. The motor is internally
connected for cloc k wise rotation with the in c om in g power supply phases A-B-C.
7 WATER CONNECTIONS
7.1
EVAPORATOR
The connection tubes have to be supported adequately in order that their weight does not damage the plant. The
following parts hav e to be installed on the w ater circuit of the evaporato r:
• Two pressure gaug e s o f adequate scale (in and out of the unit)
• Two shock-absorbing joints (in and out of the unit)
• One shut off valve (normal one in input)
• One setting valve (in output)
• Two thermomet e r s ( in and out)
• One circulation pump
• One safety valve on the water buffer
• One aut om at ic air vent valve
• One expansion tank
• An inlet filter placed as near as possible to the evaporator
• One flo w switch
The above-mention ed installation indications represent nece ssar y c on ditions for the warranty to be valid.
Trane is at your dispo sal t o e xamine any different requirements, which have to be approved before starting up the un it.
It is necessary that t he wat er flow rate to the un it is compat ible wit h the ev aporator on e. It is also n ecessar y that t he
water flow rate is ke pt un iform while th e un it is runnin g: it is sugg est ed t o use alw ays a pu mp syst em d edic ated to the
unit and independent from the remaining part of the plant.
Before stalling unit s with temperature ar ou n d 0°C please evacuate the exchanger with compr e sse d air in order to avoid
breakings due to ic e .
If the unit is installed in order to replace another, the entire hydraulic system must be emptied and cleaned before
the new unit is installed. Regular tests and proper chemical treatment of water are recommended before starting
up the new unit.
In the event that glycol is added to the hydraulic system as anti-freeze protection, pay attention to the fact that
intake pressure will be lower, the unit’s performance will be lower and water pressure drops will be greater. All
unit-protection methods, such as anti-freeze, and low-pressure protection will need to be reset. Before insulating
water piping, check that there are no leaks.
CAUTION: Install a mechanical water filter at the water inlet of each heat exchange r. Fail u re to install the filt e r al lo w s
access of solid partic les and / or welding sl ag inside the heat exch an ger. We recommend the in stallation of a filter
having a filtering n et with holes not exceed in g 0.5 mm in diameter.
Trane cannot be held responsible for any damage to he at exchangers due to the lack of good quality water fil ters.
** In case the unit is a modular one the water filter and the flow switch are on board the unit so the installation of water filter and flow switch in the customer plant is not needed
Cold water heat production
Hot water heat production
150
155
157
160
165
170
180
190
1100
1110
1115
7.1.1
The machine needs a minimum water content according to the following values:
Calculation of total minimum water content and flow rates
FLEX II
V K Q min Q max V K Q min Q max
[m3] [m3/h] [m3/h] [m3] [m3/h] [m3/h]
- 202,5 5,3 14,1 200,4 6,0 16,1 0,48
- 199,1 5,8 15,6 197,0 6,7 17,9 0,54
- 196,4 6,1 16,4 194,2 7,0 18,8 0,56
- 195,6 6,5 17,3 193,3 7,5 20,0 0,60
- 84,8 7,0 18,7 84,2 7,9 21,1 0,63
- 84,1 7,3 19,6 83,5 8,3 22,2 0,67
- 81,9 8,2 21,8 81,3 9,2 24,5 0,74
- 80,2 9,3 24,8 79,5 10,5 28,0 0,84
- 43,0 10,6 28,2 42,7 11,7 31,3 0,94
- 42,5 11,5 30,6 42,2 12,7 33,9 1,02
- 41,8 12,3 32,8 41,5 14,1 37,6 1,13
LEGEND:
V
: minimum water content of the plant
Q min
Q max
: minimum water flow to the heat exchanger
: maximum water flow to the heat exchanger
∆Tmax chiller = 8 °C
∆Tmax heat pump = 8 °C
dpw = K·Q² / 1000 Q = 0,86 P/∆T
IMPORTANT: If pumps driven by inverters (either unit onboard pump or external pump) in every working condition the variation of
the water flow rate mu st be as low as possible. Vari ation must be less th an 10% o f the nominal flow rate per minu t e
7.2
WATER CIRCUIT REGULATION EQUIPMENT
Centrifugal motor pump block
Assures the discharge an d the prevalence n e c e ssar y to supply tube nest e v aporator, the tank and th e u tility.
Automatic filling unit
Assures the water p r e ssu r e in the plant is maintained at least 1.5 bar, automatically resetting it when necessary.
Safety valve
Takes care of openin g the plant in atmospher e if the pressure exceeds the value of 6 bar.
Expansion tank
Takes care of compen sating small water hammering and variations of volume for different temperatures.
Check valves
Take care of interc e pting the pump for possibl e m ain tenance.
W / m
7.3
WATER TREATMENT
Before putting the unit into operation, cl e an the hydraulic circuit. Dirt, scales, corros io n residue and other e xtraneous
material can accumulate inside the h eat exchanger and reduce it s h e at exchanging capacity. Pressure drops can
increase, as well, thus reducing water flow. Prope r water treatmen t t h ere f ore re d uce s the risk of corrosion, e rosion,
scaling, etc. T h e most appropriate water tr e atment must be determined locally with a specializ ed company, according
to the type of system an d t o the l oc al c h arac teristics of the pr oc e ss water.
Trane is not responsible for damage to or malf u n c tioning of equipment caused by failure to treat water or by improperly
treated water.
7.4
PRECAUTION AGAINST FROST RISK OF THE HYDRAULIC PIPES
It is necessary to insulate pipes in the plan t to avoid extreme heat loss an d to protect them from we at h er conditions.
The problem of water pipes freezing could appear in tw o different situation s:
1. Stand by, with mode on, but electrically conne c ted: in this case, the u n it has frost resistances, which protect the
water locally contained in th e exchangers and in t h e p ip es from ice formation. These resistances do not ensure the
protection against the frost in the outdoor connection pipes, to be prevented by frost protection systems. Trane suggest
to insert frost thermostatic resistances on every outdoor pipes. In the following table there are the indicative electric
powers per pipe linear meter
Table – Heating cable required power
dn inch
8
10
15
20
25
40
50
65
80
100
125
150
2. Electrically unconnected unit: in this case the frost resistances of the unit could not ensure the protection. It is
necessary to add the correct glycol quantity indicated in the chapter: “ethylene glycol correction table” (§3.3).
Please consult Trane service for % of glycol required.
5
1/4"
3/8" 5
1/2"
3/4" 10
1" 13
1" 1/2 30
2" 50
2" 1/2 80
3" 120
4" 200
5" 300
6" 450
5
7.4.1
In case of installation conditi o n s with a very low temperature:
Precaution for very low outdoor temperatures
1. If there is a storage on board the unit, insert elect ric resistances to be calculated by:
PrWatt = V x (10 – tmin) / 860
where: PrWatt is the resistance power (Watt) and tmin is the l ow er temperature (°C)
2. If there is no sto rage, maintain the water temperature higher than 10°C b y in serting thermostatic resistance
with power calculat ed as in case 1.
7.5
Two or more protect io n methods should be foresee n when designing the syst em as a whole:
1. Continuous water flow circulation inside piping and exchanger when ambient air temperature is holding
below 5 °C. This implies what follows:
2. Addition of an appropriate amount of glycol inside the water circuit.
3. Additional heat insulation and sufficient heating of exposed piping.
IMPORTANT: Trane can provide various optional kits (they are not included either in the Low ambient kit down
to -10°C in chiller mode or in the Low ambient kit down to -15°C in heat pump mode) for the protection of all
the components of the hydraulic circuit inside the unit (pumps, pipes and tank). Contact Trane for more
information.
4. Emptying and cleaning of the heat exchanger during the winter season.
It is the responsibil ity of the installer and/or of local maintenance personnel to ensure tw o or mo re of the described
antifreeze methods. Continuously verify, through routine checks, that appropriate anti-freeze protection is maintained.
Failure to follow the in structions above could result in damage to some of the unit’s components. Damage from freezing
is not covered by the warranty.
CAUTION: The unit water pipes are not protected against the risk of water freeze-up when the unit is not electrically
powered and when the power and control of the external water pumps is not managed by the un it con t roller. The
owner must provide appropriate solutions to prevent freezing.
ANTIFREEZE PROTECTION ON THE HEAT EXCHANGER
- if the water flow inside piping and exchanger of the unit is due to an external pump installed by the
customer, the on/off command of this pump must always be the one provided by the unit controller through
the relevant free potential contact in the electrical cabinet.
- as long as the ambient air temperature is holding below 5 °C the unit must always be electrically supplied.
Moreover the customer pump, if present, must always be electrically supplied alike and functioning
properly.
Relief Valve
Gauges
Water Charge
Check Valve
Water Tank
FIlter
2 Way Valve With ON/OFF Servo Control
7.6
HYDRAULIC VERSIONS
FLEX II units are av ail ab l e in six hydraulic versions characterized b y comple t e kits of all major hydraulic component s for
an easier installation, with reduced t ime , cost and space.
−
Stand-alone version w ith single pump
−
Stand-alone version w ith single pump and tank
−
Stand-alone version w ith double pump and stand-by pump
−
Stand-alone version w ith double pump and stand-by pump and tank
−
Modular version with sin gle pump
−
Modular version with double pump and stan d -by pump
**
Units can be installed in modular configuration up to a maximum of 6 units by means of a dedicated hydraulic
connection kit
Figure 3
7.6.1 Hydraulic diagram for stand-alone FLEX II units with single pump
Water Differential Pressure Switch
Temperature Probe
Expansion Vessel
Safety Valve (6 bar)
Shut Off Valve
Pump
Water DIscharge
Remote connections by
the installer
Antivibration System
Flow S witch
Figure 4
Temperature Probe
Gauges
Water Charge
Check Valve
Water Tank
FIlter
2 Way Valve With ON/OFF Servo Control
Water Differential Pressure Switch
Temperature Probe
Expansion Vessel
Gauges
Pump
Water Charge
Check Valve
Water Tank
FIlter
2 Way Valve With ON/OFF Servo Control
7.6.2 Hydraulic diagram for stand-alone FLEX II units with single pump and tank
Relief Valve
Remote connections by
the installer
Safety Valve (6 bar)
Shut Off Valve
Water DIscharge
Antivibration System
Flow S witch
Figure 5
7.6.3 Hydraulic diagram for stand-alone FLEX II units with single pump + stand-by pump
Figure 6
Water Differential Pressure Switch
Relief Valve
Expansion Vessel
Safety Valve (6 bar)
Shut Off Valve
Pump
Water DIscharge
Antivibration System
Flow S witch
Remote connections by
the installer
Water Differential Pressure Switch
Relief Valve
Gauges
Safety Valve (6 bar)
Shut Off Valve
Pump
Water Charge
Check Valve
Water Tank
FIlter
2 Way Valve With ON/OFF Servo Control
Water Differential Pressure Switch
Relief Valve
Expansion Vessel
Gauges
Shut Off Valve
Water Charge
Check Valve
Water Tank
2 Way Valve With ON/OFF Servo Control
6” VICTAULIC MANIFOLD
6” VICTAULIC MANIFOLD
7.6.4 Hydraulic diagram for stand-alone FLEX II units with single pump + stand-by pump
and tank
Temperature Probe
Remote connections by
Expansion Vessel
Water DIscharge
the installer
Antivibration System
Flow S witch
Figure 7
7.6.5 Hydraulic diagram for modular FLEX II units with no on board unit pump
Temperature Probe
Safety Valve (6 bar)
Pump
Water DIscharge
Antivibration System
Flow S witch
FIlter
Figure 8
Water Differential Pressure Switch
Temperature Probe
Relief Valve
Expansion Vessel
Gauges
Safety Valve (6 bar)
Shut Off Valve
Pump
Water Charge
Check Valve
Water Tank
FIlter
2 Way Valve With ON/OFF Servo Control
FIlter
2 Way Valve With ON/OFF Servo Control
6” VICTAULIC MANIFOLD
6” VICTAULIC MANIFOLD
Water Differential Pressure Switch
Relief Valve
Gauges
Shut Off Valve
Pump
Water Charge
Check Valve
Water Tank
6” VICTAULIC MANIFOLD
6” VICTAULIC MANIFOLD
7.6.6 Hydraulic diagram for modular FLEX II units with single pump
Water DIscharge
Antivibration System
Flow S witch
Figure 9
7.6.7 Hydraulic diagram for modular FLEX II units with single pump + stand by pump
Temperature Probe
Expansion Vessel
Safety Valve (6 bar)
Water DIscharge
Antivibration System
Flow S witch
Figure 10
Primary Pump
Steel Mesh Strainer
CUSTOMER PLANT
WATER TANK
FANCOIL
AIR CONDITIONING WATER PUMP
7.7
7.7.1
CUSTOMER PLANT SKETCHES
Customer plant sketch with primary pump for a stand-alone unit with no on board pump
Secondary Pump
Temperature Probe
Flow S witch
Drainage
Vent Valve
Expansion Vessel
Filling Group
Check Valve
Safety Valve
Interception Valve
Figure 11
IMPORTANT: the flow switch and the water strainer in the customer plant are obligatory in order to keep the
warranty
Temperature Probe
AIR CONDITIONING WATER PUMP
WATER TANK
FANCOIL
CUSTOMER PLANT
7.7.2
Customer plant sketch without primary pump for a stand-alone unit with on board single pump or single
pump+ stand-by pump
Primary Pump
Secondary Pump
Flow S witch
Drainage
Vent Valve
Expansion Vessel
Filling Group
Steel Mesh Strainer
Check Valve
Safety Valve
Interception Valve
Figure 12
IMPORTANT: the flow switch and the water strainer in the customer plant are obligatory in order to keep the
warranty
WATER TANK
FANCOIL
AIR CONDITIONING WATER PUMP
WATER TANK
FANCOIL
Filling Group
Safety Valve
CUSTOMER PLANT
CUSTOMER PLANT
7.7.3
Customer plant sketch with primary pump for modular units with no on board pump
AIR CONDITIONING WATER PUMP
Primary Pump
Secondary Pump
Temperature Probe
Flow S witch
Drainage
Vent Valve
Expansion Vessel
Steel Mesh Strainer
Check Valve
Interception Valve
Figure 13
7.7.4
Customer plant sketch without primary pump for mod ul ar units with on board single pump or single
pump + stand by pump
Primary Pump
Secondary Pump
Temperature Probe
Flow S witch
Drainage
Vent Valve
Expansion Vessel
Filling Group
Steel Mesh Strainer
Check Valve
Safety Valve
Interception Valve
Figure 14
Mounting instructions
Dimensions (mm)
Paddle (model without “T” piece)
7.7.5 Flow switch installation
To ensure adequate water flow through the evaporator, it is essential to install a flow switch on the water circuit. The flow
switch must be installed on the inlet pipe of the water on which the pump is. The purpose of the flow switch is to stop the
unit in case of an interruption of the water flow while protecting the evaporator from freezing.
The flow switch can be mounted in any position far from elbows or bottlen eck s an d with the arrow in the direction of flow.
For installations on vertical piping is necessary to calibrate the device to compensate for the weight of the headstock. If
the unit is mounted to the bottom, WARNINGS on deposits that can form must be made. The appliance must be installed in
a straight pipe with no filters, valves, etc.
Have at least 5 times its diameter, both upstream and downstream.
Blade type flow switches are available as loose accessories and are suit able for harsh environments and for
pipes with diameters from 1 ” to 8”. Th e flow switch has a contact which must be wired, by the c ontract or, on
the jobsite. Check the unit wiring diagram for more information. See the instruction sheet inside the flow
switch box for information about positioning and settings.
PIPES TABLES
INDEX
INDEX
EVAPORATING/CONDENSING
COIL
DESUPERHEATER (IF PRESENT) FOR
PARTIAL RECOVERY
DISCHARGE TEMPERATURE
PROBE
SUCTION TEMPERATURE
PROBE
8 STANDARD REFRIGERANT SCHEMATIC
C COMPRESSOR
BCE
VE ELECTRONIC EXPANSION VALVE
EWR EVAPORATOR/CONDENSER
PA HP PRESSURE SWITCH
PB LP PRESSURE SWITCH
RC CARTER HEATER
AA LIQUID SEPARATOR
PS SERVICE VALVE
V FAN
VS SIGHT GLASS
Tsc
Tas
VIC CYCLE REVERING VALVE
D
Rliq LIQUID RECEIVER
VA SAFETY VALVE
FE FILTER DRIER
KA HP TRANSDUCER
KB LP TRANSDUCER
TW in INLET WATER TEMPERATURE PROBE
TW out OUTLET WATER TEMPERATURE PROBE
Tair EXTERNAL AIR TEMPERATURE PROBE
9 ELECTRICAL PANEL
All field-installed wiring must be in accordance with local regulation. Be sure to satisfy proper equipment groun d ing
requirements
The standardized values - Maximum Amps –Maximum kW atts are displayed o n u n it nameplate.
All field-installed wiring must be checked for p r oper terminations, and for p ossible shorts or ground s.
Ensure total prote ction against the possible penetration of water into the connection point.
All the cables and th e terminals are univocally numbered according t o the electrical scheme in order to avoid possible
misinterpretati on . The identification system of the cable s connected to the componen ts allow also an easy and intuitive
recognition of the componen t. Each component of the electrical panel is provid ed with an identific at io n plate according
to what is shown on the electrical scheme. All the connection to the ele ctrical panel are made f rom th e b ot t om and are
equipped with cover preventing from break. The electrical panel supply is 400V/3ph+n/50H z (TN-S system) and no
additional power sup ply is necessary. The e ntrance for the power cables is provided on the bot tom of the box where a
dismountable flang e su itable for the purpo se is provided. The electric al p ower supply without ne u tral 400V/3ph/50Hz is
available as option.
The control circuit is powered with 24 VAC. Each unit is provided w ith auxiliary transformer control circuit 230/24V. It
requires no additional power cable for the control equipment.
The unit has an antifreeze heater installed directly into the evaporator. The circuit al so h as an electric resistance
installed in the compressor in order to ke e p w arm the oil and thus avoid t h e t ransmigration of the ref r ig erant in its
interior. Obviou sly the operation of the e l e c trical resistors is ensured as long as the unit is power supplie d.
The unit is equipped with an alarm relay, w h ic h c h an ges state every time an al ar m oc c u rs in on e of the cooling circuits .
Connect the terminal s as per the wiring diagram on the unit - terminal “X ” - a visual or audible alarm or any external
supervision system .
BMS to monitor its operation is allowe d. See the wiring of the unit for wiring.
WARNING Hazardous Voltag e with Capacitor! Disconn e c t all electric powe r , including remote discon n e c ts and discharge
all motor start/run and capacitors before servicing. Follow prop e r lock out /t agou t p roced u re s to e nsure t h e power
cannot be inadvertently energized.
For variable frequency drives or other energy storing components, refer to the appropriate manufacturer’s literature for
allowable waiting p e r iod s f o r discharges capacitors. V erify with an appropriate voltmeter that all capacitors have
discharged below 60V .
After disconnectin g input power, wait f ive (5) minutes for units which are equipped with EC fans an d w ait twenty (20)
minutes for units which are equipped with variable frequency drive (0V DC) before touching any internal components.
Failure to follow the se instructions could re sult in death or serious inj u ry .
10 USER RESPONSABILITIES
It is important that the operator is properly trained and familiar with t h e equipment before w o rking on the unit. In
addition to reading this manual, the operator must study the manual ope r at io n of the microprocessor an d the wiring
diagram to understand the sequence of start- up, operation, shutdown sequen ces, and the criterion of ope ration of all
safety devices. D u ring the initial start-up of the unit an authorized t echnician is available to answer any questions an d
educate on the proper functioning. We recommend the operator to maintain a record of the op e r ating data for each
unit installed and al l main tenance activitie s an d periodic service. If the operator observes ab n o rmal o r u n usual
operating condition s, consult the author ized service technician.
11 START-UP PRELIMINARY PROCEDURES
11.1
Before starting the unit, even only momentarily, all the equipment connected to the chilled water, like the air h an dling
units, pumps, etc. have to be checked. The pump auxiliary contacts and the flow switch have to be connected to the
control panel as indicat ed in the electrical diagram. Before carrying o u t in terventions on the valve regulations, loosen
the relevant valve gland. Open the discharge valve of the compressor. Open the liquid shutoff valve placed on the liquid
line. Measure the su ction pressure. If it is low e r than 0.42 MPa jumper an d strain the solenoid valve on the liquid line.
Bring the suction pressure to 0.45 MPa, then remove the jumper. Ch arg e all t h e water circuit progre ssively . S tarts up
the water pump of the evaporator with the calibration valve shut and then slowly open it.
Discharge the air from t h e high points of the water circuit and check the direction of the water f lo w . Carry out a setting
of the flow by using a measurer (if present or av ailable) or by means of a comb in ation of the readings of the
manometers and the thermometers. In the starting phase set the valve on the pressure d ifference read on the
manometers, carry out drainage of the tubes and then carry out fine setting on the temperature difference between the
water in and the water out. The regulation is set in the factory for water in to the evaporator at 12°C and water out at
7°C. With the general switch open, check that the electrical connections are tightly clamped. Check for any possible
refrigerant leaks. Check that the electrical data on the label correspond to those of th e mains sup p l y . Check that the
thermal charge availab l e is appropriate for starting.
11.2
Units are sent with the complete charge of ref rigerant and are at a sufficie n t pressure to check t h e se al after installing.
If system if not under pressure, remove remain in g refrigerant with recovery system. Charge the system with dry
nitrogen to find the leak(s). Repair the leak.
After having elimin ated the leakage, t h e sy stem has to be dehydrated w ith a vacuum pump up to at least 1mm Hg absolute pressure (1 Torr o 133.3 Pa). This is t h e min imum recommended value to dehydrate the plan t.
WARNING! Do not use the compressor to vacuum the system.
STARTING CHECK
REFRIGERANT SEALS CONTROL
11.3
Units are supplied w ith a complete charge of re frigerant. If bubbles c an be seen through the peep h ol e with the
compressor running with a full charge and ste adily, it means that the ref rigerant charge is insufficient
REFRIGERANT CHARGE CHECK
DATE
N.
UNIT
COMPLIANCE
THE HYDRAULIC
PLEASE NOTE THAT
AND THE WATER LOAD IS AVAILABLE
THE UNIT DISPLAYS DENTS OR DAMAGES ON THE
TRANSPORTATION OR POSITIONING.
IF ANY, SPECIFY BELOW:
WARNING:
RESULT IN THE CALL
THE UNIT HAS BEEN INSTALLED IN
DIMENSIONAL DRAWING AND TECHNICAL DOCUMENTATION PROVIDED.
THE UNIT IS INSTALLED NEXT TO THE: PHOTOVOLTAIC SYSTEM, ELECTRONIC TRANSMITTERS,
SIMILAR DEVICES.
THE UNIT IS POSITIONED ON
ANTI
THE UNIT DISPLAYS DEFECTS OR DAMAGES RESULTING FROM MODIFICATIONS OR CHANGES (UNIT
TAMPERING / UNAUTHORIZED MODIFICATIONS TO THE REFRIGERANT CIRCUIT OR THE HYDRAULIC CIRCUIT
OR THE ELECTRICAL PANEL OR CHANGES TO THE UNIT OPERATING PARAMETERS) MADE BY A THI
WITHOUT A WRITTEN AUTHORIZATION ISSUED BY
DIAGRAMS AND TECHNICAL DOCUMENTATION) IN CASE OF RELEVANT DIFFERENCE BETWEEN THE UNIT AND
TRANE
WARNING:
RESULT IN THE CALL
THE UNIT HAS BEEN INSTALLED VERY CLOSE TO
INSTALLATION ENVIRONMENT
WARNING:
RESULT IN THE CALL
SPOTTED PRESENCE OF MOLD, MUSHROOMS, BACTERIA, MICROBIAL OF ANY TYPE.
THE UNIT DISPLAYS DAMAGES CAUSED BY: FLOODS, LIGHTNING, FIRE, ANY ACCIDENT BEYOND
CON
12 CHECK LIST – MANDATORY OPERATION CONTROL BEFORE
START-UP
CUSTOMER:
SITE:
ADDRESS:
POSTCODE:
COUNTRY:
GENERAL
1
2
3
4
5
6
-VIBRATIONS DAMPERS HAVE BEEN INSTALLED BETWEEN THE UNIT AND THE FLOOR.
CIRCUIT IS COMPLETE AND READY TO BE USED AND THE THERMAL LOAD IS AVAILABLE.
THE FIRST START-UP SHALL NOT BE CARRIED OUT U NL ESS THE PLANT IS READY
.
EXTERNAL CASING OCCURRED DURING THE
PLEASE BE AWARE THAT RELEVANT DAMAGES CAUSED BY THE QUOTED CIRCUMSTANCES MAY
-OFF OF THE WARRANTY.
ACCORDANCE WITH THE MINIMUM DISTANCE PROVIDED IN THE
ANTENNAS OR
A PERFECTLY FLAT (NOT INCLINED) SURFACE.
YES
NO
TRANE. THE UNIT SHALL BE CONFORM TO TRANE WIRING
7
8
9
10
STANDARD CONFIGURATION PLEASE CONTACT TRANE.
PLEASE BE AWARE THAT RELEVANT DAMAGES CAUSED BY THE QUOTED CIRCUMSTANCES MAY
-OFF OF THE WARRANTY.
A MARINE ENVIRONMENT OR AN AGGRESSIVE
(HIGHLY CORROSIVE CHEMICAL AGENT).
PLEASE BE AWARE THAT RELEVANT DAMAGES CAUSED BY THE QUOTED CIRCUMSTANCES MAY
-OFF OF THE WARRANTY.
TROL.
RD PERSON
TRANE
COMPLIANCE
THE UNIT IS ELECTRICALLY POWERED AND ALL THE RELEVANT ELECTRICAL WIRES ARE PROPERLY
ELECTRICAL SUPPLY HAS BEEN INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS PROVIDED IN THE NAME
PLATE AND IN THE TECHNICAL DOCUMENTATION. (ELECTRICAL POWER SUPPLY: 230V/400V +/
MAXIMUM “%” OF PHASE IMBALANCE: +/
VOLTAGE VALUE ( BETWEEN PHASES AND BETWEEN PHASE AND NEUTRAL)
PHASES ARE CONNECTED IN THE PROPER SEQUENCE.
ELECTRICAL CABLES SIZE ARE CONFORM TO FLA MAX
BOTH EXTERNAL AND INTERNAL
THE COMPRESSOR CRANCKCASE HEATERS HAVE BEEN POWERED AND HEATED AT LEAST 8 HOURS BEFORE THE
START
AN ELECTRONIC SUPERVISOR (OR ANY ADDITIONAL CONTROLLER) HAS BEEN
THE CONNECTION WIRES ARE
REMOTE CONTROL DEVICES OR INTERFACES ARE CONNECTED TO THE ELECTRICAL PANEL IN CONFORMITY
WITH
ELECTRONIC DEVICES ARE INTACT AND DON’T DISPLAY ANY
AN EXTERNAL
WIRING
THE ELECTRICAL ABSORP
COMPLIANCE
ALL CONNECTIONS ON THE REFRIGERANT
THE ELECTRONIC LEAKAGE DETECTOR OR THE PRESSURE GAUGE LEVEL INSTALLED ON THE REFRIGERANT
CIRCUIT HAVE DETECTED ANY LEAKAGE.
IF ANY, SPECIFY BELOW:
THE COMPRESSOR OIL INDICATOR LIGHT POINTS THE MAXIMUM LEVEL.
THE FILTER INDICATOR LIG
WARNING:
PLEASE CONTACT
ELECTRIC AND ELECTRONIC
11
12
13
14
15
16
17
18
19
ELECTRICAL WIRES ARE WELL TIGHTENED.
-UP
SHIELDED.
TRANE WIRING DIAGRAMS
- 2% ) . IT IS RECOMMENDABLE TO CHECK BY USING A TESTER THE
YES
CONNECTED.
- 10% -
VALUE.
INSTALLED.
NO
20
21
22
WATER PUMP IS ELECTRICALLY CONNECTED TO THE ELECTRICAL PANEL IN ACCORDANCE WITH THE
DIAGRAMS PROVIDED BY TRANE
TION AND THE WATER PUMP OVERHEATING ARE STANDARD.
REFRIGERANT CIRCUIT
23
24
25
HT ON THE LIQUID LINE IS GREEN.
26
THE YELLOW INDICATOR LIGHT INDICATES PRESENCE OF MOISTURE IN THE CIRCUIT. IN THIS CASE
TRANE.
DAMAGE.
CIRCUITS ARE WELL TIGHTENED.
YES
NO
THE FILTER IS INSTALLED ON
FROM THE UNIT.
PLEASE NOTE THAT THE FILTER INSTALLATION IS
RELATING THE FILTER PLEASE REFER TO THE TECHNICAL DOCUMENTA
WATER CIRCUIT
27
THE FLOW SWITCH HAS BEEN INSTALLED AND ELECTRICALLY CONNECTED. PLEASE NOTE THAT FLOW SWITCH
28
INSTALLATION IS MANDATORY.
THE VALVES ON THE WATER PLANT MUST BE OPENED. PLEASE BE AWARE THAT IF THE MACHINE IS POWERED
29
(OR IN STAND-BY MODE) PUMPS WILL START IF THE WATER TEMPERATURE IS EQUAL OR BELOW 4°C. CLOSING
THE VALVES MAY THEREFORE CAUSE SEVERE DAMAGES.
DRAINAGE VALVES ARE INSTALLED. THE DRAINAGE VALVES ARE INSTALLED ON THE LOWEST POINT. THE
30
UTILIZATION OF AUTOMATIC DRAINAGE VALVES IS RECOMMENDED.
AUTOMATIC OR MANUAL PURGE VALVES ARE INSTALLED.
31
AUTOMATIC OR MANUAL PURGE VALVES ARE INSTALLED ON THE HIGHEST POINT.
THE HYDRAULIC CIRCUIT HAS BEEN FILLED AND PURGED.
THE HEAT EXCHANGER INLET PIPES AT A MAXIMUM DISTANCE OF 2 METERS
MANDATORY. FOR FURTHER TECHNICAL INFORMATION
TIONS.
THE PLANT SHALL BE PURGED SEVERAL TIMES BEFORE STARTING UP THE UNIT. THE FILTER INSTALLED NEXT
TO THE HEAT EXCHANGER SHALL BE CLEANED SEVERAL TIMES BEFORE STARTING UP THE UNIT, UNTIL THE
32
CORRECT DELTA T IS ASSURED AND THE HYDRAULIC PRESSURE IS CONFORM TO THE PLANT AND TO THE
WATER PRESSURE DROPS.
FOR FURTHER TECHICAL INFORMATION, REFER TO DOCUMENTATION AND PROCEDURE FOR THE FIRST START
UP.
COMPLIANCE
YES
NO
HYDRAULIC CONNECTIONS TO THE UNIT ARE COMPLIANT WITH THE UNIT NAME PLATE AND DIMENSIONAL
33
DRAWINGS (HOT WATER INLET, HOT WATER OUTLET, COLD WATER INLET, COLD WATER OUTLET, ETC.).
RUBBER JOINTS ARE INSTALLED ON THE HYDRAULIC CONNECTIONS, IN ORDER TO MINIMIZE VIBRATIONS
34
BETWEEN THE UNIT AND WATER PIPES.
35
SHUTOFF VALVES ARE INSTALLED ON THE HYDRAULIC CIRCUIT.
THE EXPANSION TANK IS INSTALLED ON THE HYDRAULIC CIRCUIT. EXPANSION TANK CAPACITY CONCURS
36
WITH THE WATER PLANT CAPACITY.
TEMPERATURE PROBES AND PRESSURE GAUGES ARE INSTALLED ON THE HYDRAULIC CIRCUIT, BOTH INLET
37
AND OUTLET SIDE.
THE HYDRAULIC CIRCUIT IS FREE FROM OBSTRUCTION OR ANY KIND OF CONSTRAINT.
38
BUFFER TANKS ARE INSTALLED IN THE HYDRAULIC CIRCUIT. THE BUFFER TANKS INSTALLATION IS STRONGLY
RECOMMENDED IN ORDER TO WARRANTY THE OPTIMAL UNIT OPERATION.
39
SPECIFY BUFFER TANK CAPACITY:LT
THE PRESSURE RELIEF VALVE IS INSTALLED BETWEEN DELIVERY AND RETURN PIPES.
40
41
42
WARNING: IN ORDER TO AVOID WATER-HAMMER, THE RELIEF VALVE PRESSURE SHALL BE SET UP IN
ACCORDANCE WITH THE STANDARD OPERATING PRESSURE OF THE WATER CIRCUIT.
THE AUXILIARY HEATING SYSTEM IS INSTALLED IN THE WATER CIRCUIT IN ORDER TO AVOID THE START-UP
OF THE UNIT WITH WATER TEMPERATURE BELOW 18°C. BEFORE STARTING UP THE UNIT THE INLET WATER
TEMPERATURE MUST BE EQUAL OR HIGHER THAN 18°C.
WARNING: THE UNIT SHALL NEVER WORK (NOT EVEN FOR SHORT PERIODS) WITH AN INLET WATER
TEMPERATURE LOWER THAN 18°C.
ANTIFREEZE PROTECTIONS ARE INSTALLED IN THE WATER CIRCUIT (ELECTRICAL HEATERS ARE INSTALLED ON
WATER PIPES AND TANKS).
FOR FURTHER TECHNICAL INFORMATION PLEASE REFER TO TECHNICAL DOCUMENTATION PROVIDED. PLEASE
3°C.
DATE:
NOTE THAT ANTIFREEZE PROTECTIONS ARE MANDATORY FOR OUTDOOR AIR TEMPERATURE LOWER THAN
THE WATER CIRCUIT IS FILLED WITH ETHYLENE GLYCOL. ETHYLENE GLYCOL “%” SHALL CONFORM WITH
43
THE DATA PROVIDED IN THE TECHNICAL DOCUMENTATION.
ALL WATER PIPES ARE GROUND CONNECTED (IN ORDER TO AVOID ABNORMAL VOLTAGES THAT CAN CAUSE
44
DANGEROUS CORROSIONS).
45
THE EVAPORATOR WATER FLOW IS COMPLIANT TO THE TECHNICAL DOCUMENTATION PROVIDED BY TRANE.
THE WATER PUMPS ARE CORRECTLY SET UP IN ACCORDANCE WITH THE PLANT WATER FLOW, AVAILABLE HEAD
46
PRESSURE AND PRESSURE DROP.
THE PUMP IMPELLERS ARE MECHANICALLY UNBLOCKED AND UNCLOGGED (FREE FROM ANY KIND OF
47
CONSTRAINTS.)
AUTHORIZED SERVICE:
NAME AND SIGNATURE
CUSTOMER:
NAME AND SIGNATURE
Refrigerant charge in the liquid phase
Refrigerant circuit diagram connection to vacuum pump
High pressure
Low pressure
port
High pressure
gauge
Vacuum meter
Vacuum pump
Oil trap
Low
pressure
gauge
Liquid sight glass
HR port
LP port
HP gauge
Scale
LP gauge
12.1
12.1.1
REFRIGERANT CHARGE
Refrigerant replacement procedure with unit stopped and in vacuum (refrigerant charge in
the liquid phase)
Open the shut off v alve as far as possible so that it cl oses the service coupling. Connect the refrig e r an t cylinder to the
service coupling without tightening the coupling. Half close the liquid shut off val v e. If the circuit has been deh y d r ated
and is in vacuum, charge the liquid by turn in g the cylinder upside down. Weigh and charge the ap propriate quantity.
Open the valve completely. Start up the unit and leave it running at full charge for some minutes. Check that the
indicator is clear wit h n o bubbles. Make sure th at th e transparency condition without bubbles is d u e to the liquid and
not to the vapour. Correct functioning of the unit allows for overheating of 4 - 7° C and sub cooling of 4 - 8°C. Values of
overheating which are t o o h igh may be caused by a lack of refrigerant, where as h igh sub cooling values may me an an
excess of charge. A f te r in t ervention on the charg e , it is ap propriate to check that the unit runs within the declared
values: with unit steadily running on a full charge, measure the temperature of the suction line downstream of the
thermostatic valve bulb; read the balance pressure to the evaporat o r o n the low pressure manometer and the
corresponding saturation temperature.
Overheating is equal to the difference between the temperatures measured in this way. Then measure the temperature
of the liquid line coming out of the condenser and read the balance pressure to the condenser on the high -pressure
manometer and the corresponding saturation temperature. The sub cooling is the difference between these
temperatures.
Danger While refrigeran t is being added do not ex c lu de any control system and le t the water circulate in th e evaporator
to avoid the formation of ice.
port
Refrigerant charge in the vapour phase
Liquid sight glass
HR port
LP port
HP gauge
LP gauge
Scale
Gauge manifold
12.1.2
Caution: charge vapour only. Do not charge liqu id b e c au se it may damage the comp r e ssor .
Connect the refrigerant cylinder to the service valve without tightening the coupling. Drain the connection piping and
tighten the coupling. Charge the circuit until the indicator indicates l iquid without bubbles. Now the unit has the
required charge. Make sure not to overcharge the circuit. Charging more t han necessary leads to a h igher delivery
pressure, greater power consumption and p ossible damage to the com p r e ssor .
Refrigerant replacement procedure with unit running (refrigerant charge in the vapour phase)
The symptoms of a low refrigerant charge are:
Low evaporation pre ssu r e .
High value of supe rheating.
Low value of sub cooling.
In this case, add re frigerant R410A. The sy stem is provided with a charging port between th e e xp ansion valve and the
evaporator. Charge refrig e rant u nt il cond itions ret u rn t o work normal. R e memb e r t o rep lace the cap closing t he v alv e
at the end.
IMPORTANT!
If the unit has not been provided with integrated pump on board, do not turn off the external pump before 3 minutes
have elapsed after turning off the last compressor. The early shutdow n o f th e pump causes a water flow alarm failure.
13 START-UP
13.1
Before starting up the equipment it is ver y important to check that al l the operations described in t h e paragraph
“CHECK LIST – MANDATORY OPERATION CONTROL BEFORE START UP” have been carried out correctly.
Moreover check t ha t all the mechanical and electric equi p ment has been tightened perfectly. P art icular attent ion
should be paid t o the main components (compressor, exchangers, ventilators, electrical mot or s, and pump) if loos e
fastenings are found, t ighten t hem well before start ing up the machine.
The oil heaters hav e to be inserted at least 8 h ours before starting up. Ensure that the compressors’ carter is hot. O p en
the compressor valve and the cooling circuit one, which may have b e e n shut f or charg ing. C ont rol all t he machine ry
connected to the unit.
PRELIMINARY CONTROLS
13.2
All the compressors mounted on units are factor y c h ar g ed with oil whose chemic al characteristic of stability are very
good, so it is not nec e ssar y to change frequentl y the lubricant oil.
The scroll compressors are equipped wit h an oil sight glass from which you can cont rol t he le v e l. In tandem or trio
performances, pay particular attent ion to oil level. Not perfe c t l y l e veled sight glasses between compressors in parallel,
but falling in th e up per and lower limits, are con sidered normal.
Next to the lamp the re is a connection on every c om p r e ssor for draining the o il an d a conne c tion for refilling.
To refill oil, there is a ¼” Schrader connection.
To refill oil, it is ne c e ssar y to discharge the ref rigerant in the unit, recovering it in adequate cylinders. Then vacuum
until you reach a pre ssu re of about 6 Pa to remove any trace of humidity from the circuit. Then load the unit with a
small amount of refrigerant and fill oil from the proper connection f or re f illing.
Add oil until the oil sight glass is flat within the upper and lower limits indicated by the correspon ding notches.
At this point refill the previously discharge d am ou n t of refrigerant as in the indications above. Restart the compre sso r.
Run for 20 minutes at full load and check the oil level. The units use POE oil.
STARTING UP
In case of burns for the electrical motor or fault of t he compressor, it is nece ssary to make a test to check the acidity of
the lubricant oil and, eventually, clean the circuit t o re d u ce the acidit y to correct values, mounting for instance an
antiacid filter and c h an ging the oil in the circuit.
13.3
In order to keep all the machine components in good condition and to optimise their use, during the warm up it is necessary
to bring the circuit to the right temperature before rele asing cooling or heating energ y to th e u tilities.
The following steps must be followed for this to be carried out:
*
start up the machine
*
wait for the water in temperature to reach the running temperature
*
start up the consumers
Follow the above mentioned procedure every time the plant is stopped long enough for the water temperature contai ned
in it to vary considerably.
WARM UP OF THE PLANT
13.4
All the compressors are factory charged with oil whose chemical char acteristic of stability are very good, so it is n ot
necessary to change frequently the lubricant oil.
The scroll compressors are equipped with an oil sight glass from which you can control t h e lev e l. In t and e m or trio
performances, pay particular attent ion to oil level. Not perfe c t l y l e veled sight glasses between compressors in parallel,
but falling in th e up per and lower limits, are con sidered normal.
CONTROL OF THE OIL CHARGE
13.5
1) With the switch closed, open the electrical panel and exclude compressor (refer to the wiring dia gram on the
unit). Close the panel, set switch to “ON” (to give power to the unit).
2) Wa
The oil temperature must be at least 5°C higher than the saturation temperature of the refrigerant inside the
compressor.
3) Place the unit in the “ON” and wait until the unit is indicated on the display-On.
4) Turn on the pumps (at max speed if with inverter).
5) Verify that the loss of load of the evaporator is equal to that of the project and correct if necessary. The
pressure drop on the evaporator must be read on the service valves instal led on the evaporator piping as a
standard. Do not measure the load losses in points where any valves and
6) Check for air in cleaning filters, and then drain the system.
7) Return the pump to the factory setting.
8) Turn off the power (into standby mode) and make sure the pumps stop after about 2 minutes.
Verify that the local temperature subcooling is set to the required value by pressing the Set button.
9) Turn the main switch to “OFF”. Open the cabinet. Reactivate the compressors. Close the cabinet. Turn the main
switch to “ON” (to give power to the unit).
10) Wait for the start of the microprocessor and control.
11) When the compressor is started, wait about 1 minute for the system begins to stabilize.
12) Check the pressure of evaporation and condensation of refrigerant.
13) Verify that, after a period of time necessary for the stabilization of the refrigerant circuit, the liquid indicator
placed on the inlet pipe to the expansion valve is completely filled (no bubbles), and that the moisture indicator
signs ‘Dry’. The passage of bubbles within the liquid indicator may indicate a low amount of refrigerant, or an
excessive pressure drop through the filter drier, or an expansion valve blocked at the maximum opening position
14) In addition to checking the sight glass, check the operating parameters of the circuit controlling:
a) - O
b) - Overheat ing compr esso r discharge
c) – Sub cooling of the liquid exiting the condenser coil
d) - Evaporation pressure
c) - Condensing pressure
15) Measure the values of pressure and temperature by means of the suitable instrumentation and make comparison
by reading the corresponding values directly on the display of the microprocessor on board
16) To temporarily turn off the unit put on standby the unit key or open the remote contact (terminals shown in the
wiring diagram provided with the unit) of the terminal X (by means of a remote switch installed by the customer)
or set time zones. The microprocessor will activate the shutdown procedure that will take a few seconds. The unit
water pump will be running on for two minutes after the unit has been switched off. Do not remove the main
power to not turn off the electrical resistances of the compressor and the evaporator.
START UP PROCEDURE
it for the start of the microprocessor and control. Make sure that the temperature of the oil is hot enough.
/
or filters are interposed.
verheat in g co m pr e ss o r
14 MAINTENANCE
Maintenance operations are fundamental in order to keep the units running properly, from a purely functional and an
energetic and environmental points of view.
Every unit comes with a logbook, in which the user to machine maintenance can keep all the required notes, in order to
keep a historical log of the unit.
A lack of notes in the logbook could be considere d proof of careless maintenance .
14.1
IMPORTANT!
Beyond the cadences of checks recommended in the following, in order to keep the unit at optimum levels of
performance and ef ficiency and prevent in c ip ie nt failures, we recom me n d periodic visits of in spection and control of
the unit by qualified personnel.
In particular, we recommend:
4 annual visits to units that operate about 36 5 days / year (quarterly)
2 visits per year for un its with seasonal operation about 180 days / year (one at the start of the se ason and another one
at mid-season)
1 annual visit for unit s w ith seasonal operation of about 90 days / year (st arting seasonal)
It’s important t h at during the initial start -up and periodically during operation routine che ck s are carried out. Among
them we must also ch e c k the suction and condensation as well as the sight glass located on the liq u id lin e.
Check through the microprocessor installed on the unit if the unit is wor k in g within normal paramete r s of superheating
GENERAL
and sub cooling. A r ou tine maintenance prog r am recommended is show n at the end of this chapter while a card
collection of operat in g data is at the end of t h is man ual. It is suggested to record on a weekly basis all th e operating
parameters of the u n it. The collection of the se data will be very useful to technicians, in case technical assistance is
requested
Compressor Maintenance IMPORTANT!
The analysis of vibrat ion is a great tool for chec king the mechanical condit io n s of the compressor.
It is recommended to check the value of the vibration immediately after starting and periodicall y o n an an n u al basis.
Compressor Electrical Connections
It is very important that all the compressors are wired correctly f or p rope r rot at ion. These compressors will not tolerate
reverse rotation. Verify correct rotation/ p h asing using a rotation meter.
If wired incorrectly the compressor will make excessive noise , will not pump and will draw about half the normal
current. It will also become very hot if allowed to run for an extended period.
NOTICE: Do not “bump” the compressor to check rotation as incorrect rotation could cause compressor motor
failure in as little as 4 to 5 seconds!
Improper rotation of the compressors is indicated by a compressor modul e trip, noisy operation, n o pressure difference
on manifold gauges and low amp d r aw .
Compressor Replac emen t
If the chiller suffers a failed compressor, use t hese steps for replace ment:
Each compressor has lifting eyes. Both lifting eyes must be used to lift the failed compressor.
After a mechanical failu r e of a compressor, it is n e c e ssar y to change the oil in t h e rem ain in g compressor and also
replace the liquid line filter drier. After an elect rical failure of a compre ssor, it w ill also be ne ce ssary to chang e t h e oil
in the remaining comp ressor, replace the filters driers and add a suct ion filter drier with clean -up cores.
Change filters and oil until the oil no longe r test acidic.
Make sure that a heater is correctly installed on the compressor. T h e heater helps prevent dry starts.
Note: Do not alter the refrigerant piping in any way as this can affect compressor lubrica tion.
Refrigerant System Open Time
Units use POE oil and t her e fore refrigerant syst e m open time must be kept to a minimu m . The following procedure is
recommended:
Leave a new compresso r sealed until it is read y to be installed in the unit. Maximum system open time is dependent
upon ambient conditions, but do not e xceed one hour open time.
Plug the open ref rigerant line to minimize moisture absorption. Always change the liquid line filter drier.
Do not leave POE oil containe rs op e n t o t h e atmosphere. Always keep them sealed.
14.2
The risks due to the pr e ssu r e insid e the circuit have bee n elimin ated or (when it is not possible) reduced b y
means of safety dev ic e s. It is important to check periodically the status of this device and to carry out the
components inspect ions and repositioning as follows.
14.3
Check the liquid receiver state at least one a year.
It is important to ch e c k that the surface does not get rusty and that neith e r co rr osion nor deformations are v isible.
In case the superf ic ial oxidation and the c or rosio n ar e n ot properly controlle d an d stopped in time, c au se a thickness
reduction with a con se q uent reduction of the receiver mechanical resistance.
Use antioxidant p ain t or products to protect.
SIGHT CHECK OF THE LIQUID RECEIVER
SAFETY DEVICES
Recommended
basis
Power supply and auxiliary power
voltage check
Refrigerant charge check through sight
glass
Compressors carter heaters operation
check
Fans and compressors contactors state
check
14.4
It is mandatory to clean regularly the coils for a proper unit operation. Pollution and oth e r residual material clearing
helps extend the life of the coils and the whole unit
STANDARD CONTROLS
Compressors oil level check monthly
Inlet temperature check (overheating) monthly
Water circuits filling check monthly
Fans and compressors motors electrical
input check
Tightening all electrical connections monthly
Coils cleanliness monthly
Compressors and liquid circuit solenoid
valve check
Operations description
monthly
monthly
monthly
monthly
semiannual
quarterly
Evaporator heater operation check quarterly
Motor and fan bearing noise check semiannual
Pressure vessels conditions check yearly
Temperature and pressure probes –
The unit comes factory-equipped with all the sensors listed bel ow. Periodically
check that their measurements are correct by means of samp le inst rume nt s (manometers, thermometers); correct
readings if necessary u sing the microprocessor keyboard. Well- c alibrated sensors ensure better efficiency for the unit
and a longer lifetim e .
Note: refer to th e micro p r oc essor use and maintenance manual for a complete description of ap plications, setting an d
adjustments.
All sensors are preassembled and connected to the microprocessor. T h e descriptions of each se n sor are listed below:
Outgoing water temp erature sensor –
by the microprocessor
for antifreeze protection and
This sensor is locat ed on the evaporator out going water connect io n an d is u se d
to control the unit load according to the system thermal load
IMPORTANT
In case a temperature control based on ingoing water temperature is needed, contact Trane before trying to set it
autonomously
.
Ingoing wat e r temperatu re sensor –
This sensor is located on the evaporator ingoing water connect ion and is used for
monitoring the return water temperature.
External air temperat ur e se nso r –
display.
High pressure transdu cer –
This allows to monitor the delivery pressure and to control the ve nt ilators. Sh ould an
This sensor allows to mon itor the external air temperature on the microprocessor
increase in condensation pressure occur, the microprocessor will control the circuit load in orde r to allow it to function
even if choked. It contributes to complementing the oil control logic.
Low-pressure transducer –
This allows to monitor th e c ompressor suction pressur e al ong with low pressure al ar ms. It
contributes to complementing the oil control logic.
Compressors discharge temperature sensor –
This allows to monitor the refrigerant temperature on compressor
delivery. It contributes to prevent compressors breakages.
.
X
X
X
X
X
Check pressure safety accessories (PED)
8) TAN (Total Acid Number):
0.10:
No action
Repositioning filters antacid and occurs after 1000 hours
of operation. Continue to replace the filters until the
Changing the oil, oil filter and the filter drier, Refer to
14.5
ORDINARY MAINTENANCE
Activities list week Month (note 1) Year (note 2)
General:
Data collection operation (Note 3) X
Visually inspect the un it for any damage and / or loosene ss
Verifying the integrity of the thermal insulation
Clean and paint where needed
Water Analysis (6)
Electric:
Check the correct operation of the equipment on the unit
Check the wear of contactors - Replace if necessary
Check tightness of all electrical terminals - Tighten if necessary
Clean the inside of the electrical panel
Visual inspection of the components for signs of overheating
Check the operation of the compressor and the electric resistance
Measurement using a Megger insulation of the compressor motor
Refrigerant circuit:
Perform a test of refrigerant leaks (5)
Check through the sight glass coolant flow - Full Indicator X
Check the pressure drop of the filter drier
Check the pressure drop of the oil filter (Note 5)
Carry out the analysis of the vibrations of the compressor
Carry out the analysis of the acidity of the oil of the compres sor (7)
X
X
X
X
X
X
X
X
X
X
X
Condensing section:
Cleaning the condenser coils (Note 4)
Check that the fans are tightened
Notes:
1)
The monthly activities include all those weekly.
2)
The annual activity (or earlier in the season), include all activities weekly and monthly.
3)
The values of the unit should be recorded each day for a high level of observation.
4)
The coil cleaning may be required more frequently in areas with a high percentage of particles in the air.
5)
Periodicity shall b e also defined by local r e gulation (Fgas)
6)
Replace the oil filter when its pressure drop reaches 2.0 bar.
7)
Check for dissolved metals and corrosion inhibitor and in case of brine % of brine and freeze up point
From 0.10 to 0.19:
TAN not falls below 0.10.
> 0.19:
regular intervals.
X
X
COMPONENTS
QUANTITY
fuses
(all)
filter dryers
(all)
solenoid valves
(1 per type)
COMPONENTS
QUANTITY
COMPONENTS
QUANTITY
15 RECOMMENDED SPARE PARTS
There follows a list of the recommended parts for several years’ running. Trane is at your disposal to
recommend a personalised list of accessories according to the commissioned order, including the part
number of the equipment.
1 YEAR
2 YEAR
5 YEAR
electronic expansion
valves
pressure switches (1 per type)
gas gauges (1 per type)
contactors and relays (1 per type)
thermal protectors (1 per type)
carter electric heaters (1 per type)
4-way valve
check valve (1 per type)
safety valve (1 per type)
sight glass (1 per type)
fans and engines (1 per type)
(1 per type)
(1 per type)
fuses (all)
filter dryers (all)
solenoid valves (all)
electronic expansion
valves
pressure switches (all)
gas gauges (all)
contactors and relays (all)
thermal protectors
carter electric heaters (all)
check valve (1 per type)
4-way valve (1 per type)
safety valve (1 per type)
sight glass (1 per type)
fans and engines (1 per type)
electrical component s (all)
compressors (1 per type)
(all)
(all)
fuses (all)
filter dryers (all)
solenoid valves (all)
electronic expansion
valves
pressure switches (all)
gas gauges (all)
contactors and relays (all)
thermal protectors (all)
carter electric heaters (all)
check valve (all)
4-way valve (1 per type)
safety valve (1 per type)
sight glass (all)
fans and engines (all)
electrical component s (all)
compressors (all)
heat exchanger (1 per type)
(all)
x s
Lack of consent of the high or
low pressure
x s
x s
x s
x s
x s
x s
x s
16 TROUBLESHOOTING
Symptom Cooling
Who can take
corrective action
U = User
S = specialised
personnel
Probable cause Possible remedy
A The unit does
not start
B The
compressor
does not start
C The
compressor
starts up and
stops
repeatedly
x s
x s
x s
x s
x s
x u
Probe faulty serv ic e
Defective compressor See point B.
Compressor burnt or seized Replace the compressor.
Compressor contactor de energized
Power circuit open
Motor thermal protection open
Intervention of the minimum
Compressor contactor defective Check and replace if necessary.
Calibration values of the setpoint or differential
Lack of cool ant See point G
Check and replace if necessary.
See points D-E
Check the voltage across the coil of
the compressor contactor and the
continuity of the coil.
Investigate the cause of the
protection, and check if there are any
short circuits in the w iring
or in the windings of the motors of
pump, fan, compressor and
transformer
The compressor has opera te d in
critic al condition or there is a lack of
charge in the circuit: Make sure that
working conditions are within the
limits of operation. Loss of coolant:
see section G.
See point E.
Modify them as reported in the in the
tables.
x s
D The
compressor
does not start
because the
maximum
pressure switch
has tripped
x u
s
x
x s
Pressure switch out of order Check and replace.
Overcharge of refrigerant Download the excess ref riger a nt
Finned coil clogged, air flow
rate is too low
Fan not working See point F.
Water pump circulation blocked Unblock the pump.
Water circulation pump and
defective
Presence of non condensable
gases in the refrigerant circuit
Refrigerant filter clo gged Check and replace.
Remove dirt from the coil and
obstructions to the air flow
Check and replace if necessary.
Prime the circuit after it has been
downloaded and put under vacuum.
x s
Presence of moisture in the
refrigerant circuit
Check the voltage across the coil of
the coil.
Lack of output voltage from the
control fan speed
Check the contacts, replace if
necessary.
Check the condition of the fan and
of the unit.
x s
x s
x s
x s
Symptom Cooling
x s
u
E The
compressor
does not start
because the
minimum
pressure switch
has tripped
x u
x s
s
s
x s
x s
x s
Who can take
corrective action
U = User
S = specialised
personnel
Probable cause Possible remedy
Pressure switch out of order Check and replace.
Machine completely void of
refrigerant
Finned coil clogged, airflow rate
is too low
Water c irculation pump block ed
Water c irculation pump block ed
and defective
Presence of frost on the
evaporator coil
Evaporator fan not working See point F.
Refrigerant filter clogged Check and replace.
Expansion device that is not
working properly
See point G.
Remove dirt from the coil.
Unloc k the pum p
Check the pump and replace if
necessary
See point N.
Check and replace if necessary.
Replace the filter, dry and recharge
F The fans do
not start
G Lack of gas
H Frost in the
liquid line
downstream
from a filter
I The unit
works
continuously
without ever
stopping
x s
x s
x s
x s
x s
x u
x s
Fan contactor de-energized
Thermal protection inside the
fan
Fan motor faulty Check and replace.
Loose electrical connections Check and replace.
Loss in the refrigerant circuit
The filter is clogged
Lack of refrigerant gas See item G.
Incorrect tuning of the operating
thermostat
Excessive thermal load Reduce the thermal load
Compressor does not give the
thermal output
the contactor and the continuity of
the air temperature during operation
Check the cooling circuit using a leak
detector after pressurising the circuit
to approximately 4 bars.
Repair, evacuate and refill.
Replace the filter
Check and set.
Check, change or revise
L The unit
works regularly
but with an
insufficient
capacity
x s
x s
The liquid filter is clogged Replace.
Low refrigerant charge
See point G.
Expansion device that is not
working properly
Check the pump and replace if
necessary.
x s
x s
Symptom Cooling
Who can take
corrective action
U = User
S = specialised
personnel
Probable cause Possible remedy
x s
x s
M Frost in the
compressor
intake pipe
x s
x s
x s
N Abnormal
noise detected
in the system
O The unit does
not start
x s
Verify and replace.
Water c irculation pump block ed Unlock the pump.
Water c irculation pump defec tive
Low refrigerant charge See p oint G.
The liquid filter is clogged Replace.
Compressor noisy Check and replace if necessary.
The panel vibrate Fasten properly.
Phases of the supply network
reversed
Invert two phases.
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and
17 IMPROPER USES
The unit is projected and built up to grant the maximum safety in its proximity, as well as to resist to the aggressive
environmental conditions. The fans are protected by grilles.
Residual risks are indica ted with warning labels.
SAFETY SYMBOLS
sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfol i o of advanced controls and HVAC
systems, comprehensive building services, and parts.
For more information, visit www.Trane.eu.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without noti ce.