Service Tests Group: ........................................ 88
v
Page 6
General
General
Literature Change History
CVHE-CLD-1 (February 1995)
Application of the Clear Language Display to the
UCP2 Centravac
CVHE-CLD-1A (February 2000)
Updated information and incorporated FastPak™
items.
About This Manual
This manual describes the application of the Clear
Language Display (CLD) to the UCP2 Centravac. It
describes its use as a machine-mounted human
interface.
A description of the UCP2 reports and message
displays are provided along with additional “Help
Notes” to clarify the display messages. In addition, a
Diagnostics section is also included.
LCD Display
The display on the Clear Language Display is a 2line by 40-character liquid crystal display (LCD).
Upper and lower case alphabetic characters can be
displayed, along with numeric and special
characters.
LED Alarm
In addition to the alpha-numeric LCD display, there's
a single discrete LED on the human interface. The
red LED flashes on-off whenever a latching
diagnostic is present and a manual reset is required
to restore full unit operation. The LED is also used to
indicate that a function or control has been set to
manual from within the Service Test Menu. If a
control has been set to manual, the LED is on and
non-flashing. A diagnostic supersedes a manual
operation. As a result, the unit could have a manual
mode set and be in a latching diagnostic. In this case
the LED would flash on-off. The LED is off otherwise.
Figure 1
Keypad Matrix
CUSTOM
REPORT
OPERATOR
SETTINGS
Previous+EnterAuto
CHILLER
REPORT
SERVICE
SETTINGS
REFRIGERANT
REPORTREPORT
SERVICE
TESTS
COMPRESSOR
DIAGNOSTICS
LCD Backlight
The LCD display has an LED backlight so it can be
read in low light conditions.
Next
-
CancelStop
Keypad
A sealed dirt-proof keypad is used on the unit mount
Clear Language Display. Metal dome switch
actuators respond when any key is pressed. See
Figure 1 .
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.
Information Manual1
Local Clear Language
The Local CLD “Clear Language Display” resides at
the Chiller providing display of chiller data and
access to operator/service controls, setpoints, and
chiller set-up information. All information is stored in
non-volatile memory in the Chiller module. The Local
CLD and the Chiller module work together to display
and store information requiring non-volatility.
Page 7
Control System
Control System
Unit Control Panel
Safety and operating controls are housed in the
UCP2 unit control panel, the starter panel, and the
purge control panel.
The UCP2 control is a modular design partitioned by
major function or group of functions. All modules (see
Figure 2 ) communicate with each other through the
Interprocessor Communication Circuit (IPC).
Figure 2
UCP2 Control Panel
I/O Module
Major components within each control group are
shown in the figure.
Unit-mounted temperature sensors, pressure
transducers, and functional switches provide analog
and binary inputs to the various modules.
The microcomputer-based modules are illustrated in
the figure. All wiring to the modules are to pluggable
terminal blocks.
Stepper Mod
Options Mod
Chiller Mod
Circuit Mod
2CVHE-CLD-1A
Page 8
Custom Report
Custom Report Group
Reports are added to the custom report group by
pressing the <+> key when the desired report is
being displayed from its normal report location.
Reports are removed from the custom report group
by pressing the <-> key when the desired custom
report is being displayed. The Custom report group
can contain a maximum of 20 reports. When adding
a report to the Custom Report, if the <+> key is
pressed when the Custom Report already contains
20 reports, a message, “Custom Report Is Full,
Report Not Added,” indicating that the Custom
Report is full, will be displayed for 2 seconds. If an
attempt is made to add a report to the Custom Report
that is already in the Custom Report, a message,
“Report Already In Custom Menu”, will be displayed
for 2 seconds.
Custom Report
The Custom Report sequence is as follows:
Report Heading
User Defined Custom Report
Press (Next)(Previous) To Continue
If no entries are selected for the Custom Report, see
Empty List Display.
Empty Display List
If no entries are selected for the Custom Report, the
second entry is:
No Items Are Selected For Custom Report:
See Operators Manual To Select Entries
The report then wraps around to the report heading
when <Next> is pressed.
If there are items selected for the Custom Report,
then the empty list display is not used. Instead, the
report heading and the selected items are displayed
sequentially as <Next> or <Previous> are pressed.
Information Manual3
Page 9
ASHRAE Guideline 3 Report
ASHRAE Guideline 3 Report
Press (Enter) For ASHRAE Guideline 3 Rpt
Press (Next)(Previous) To Continue
If <Enter> is pressed the ASHRAE Guideline 3
Report Menu is entered, shown at the end of the
Standard Report below. Otherwise, If <Next> is
pressed the Standard Report is entered. The
ASHRAE Guideline 3 Report Entry screen may be
added to Custom Report by pressing the <+> key.
Adding it to the Custom Report allows the user to
access the ASHRAE Guideline 3 Report from the
Custom Menu.
The following are the Standard Report screens, e.g.
not part of the ASHRAE Guideline 3 Report.
ASHRAE Guideline 3 Reports
ASHRAE Guideline 3 Report
Press (Next)(Previous) To Continue
Time Of Day/Refrigerant Type
Current Time/Date HH:MM xm Mon,XX XXXX
Refrigerant Type: [type]
Possible values for refrigerant type are: R11, R123,
R12, R134a, R22, R113, R114, R500, or R502.
Chiller Operating Mode
The chiller operating modes display comes up first in
the standard report:
[Operating mode line 1]
[Operating mode line 2]
Line 1 (and 2 if needed) indicates a current condition
of the unit as shown in the following table (Table 1) .
In some cases, an associated timer or system
parameter will be displayed that assures the
transition to an expected mode is in progress,
particularly during the unit start-up sequence.
4CVHE-CLD-1A
Page 10
Table 1
Operating Modes
ASHRAE Guideline 3 Report
Unit Operation
Stop
Auto
Operating Mode Display*
(First Line/Second Line)
Resetting
Local Stop: Cannot Be Overridden By
Any External Or Remote Device
Remote Display Stop: Chiller May Be
Set To Auto By Any Ext Or Rmt Device
Remote Run Inhibit
From External Source
Unit Operation
Run
Remote Run Inhibit
From Tracer
Heat Sink Temp Start InhibitUnit Is Running in Surge Condition
Diagnostic Shutdown StopUnit Is Running; Capacity Limited By
Diagnostic Shutdown AutoUnit Is Running; Capacity Limited By
Waiting For Evaporator Water Flow
Auto
Auto
Waiting For A Need To Cool
Waiting For Tracer Communications
To Establish Operating Status
Starting Is Inhibited By Staggered Start
Time Remaining: MIN:SEC
Starting Is Inhibited By Restart
Inhibit Timer: Time Remaining MIN:SEC
Auto
Operating Mode Display*
(First Line/Second Line)
Unit Is Running
Capacity Limited By Phase Unbalance
Unit Is Running
Capacity Limited By High Cond Press
Unit Is Running
Capacity Limited By Low Evap Temp
Unit is Running
Capacity Limited By Vane Open Travel
Stop
Unit Is Running
Minimum Capacity Due To Vane Closed
Travel Stop
Pulldown Rate Based Soft Loading
Current Based Soft Loading
Auto
Waiting For Condenser Water Flow
Establishing Evap Water Flow
Establishing Oil Pressure
Establishing Evap Water Flow
Prelubrication Time: MIN:SEC
Evap Water Is Flowing
Prelubrication Time: MIN:SEC
Evap Water Is Flowing
Performing IGV BPI Search & Calibration
Establishing Cond Water Flow
Establishing Oil Pressure
Establishing Cond Water Flow
Prelubrication Time: MIN:SEC
Cond Water Is Flowing
Prelubrication Time: MIN:SEC
Initialize
Start
Run
Information Manual5
Cond Water Is Flowing
Establishing Oil Pressure
Cond Water Is Flowing
Performing IGV BPI Search and
Calibration
Cond Water Is Flowing
PreStart Unload Time Remaining:
MIN:SEC
Starting CompressorUnit is Running; Base Loaded
Unit Is RunningUnit is Running; Base Loaded
Unit Is Running
Capacity Limited By High Current
Run
Establishing Evap Water Flow
Performing IGV BPI Search & Calibration
Unit is Running; Base Loaded
Unit is Running; Base Loaded
Capacity Limited By High Current
Unit is Running; Base Loaded
Capacity Limited By Phase Unbalance
Unit Is Running; Base Loaded
Capacity Limited By High Cond Press
Unit Is Running; Base Loaded
Capacity Limited By Low Evap Temp
At Vane Open Travel Stop
At Vane Closed Travel Stop
Unit is Running; Base Loaded
In Surge Condition
Page 11
ASHRAE Guideline 3 Report
Operating Mode Display*
Unit Operation
Run
Run-Unload
Run-Ice Build
* Displays are not in any sequence. Some displays will never appear, depending on options and situation
Active Chilled Water Setpoint/Chilled Water
Setpoint Source
Active Chilled Water Setpoint: xxx.x f/c
[settings source] CWS: xxx.x f/c
(First Line/Second Line)
Unit Is Running; Base Loaded
Current Based Soft Loading
Unit Is Running In Minimum CapacityUnit Is Building Ice
Unit Is Running In Minimum Capacity
Time Remaining: MIN:SEC
Unit Is Preparing To ShutdownIce Building Is Complete
Unit Is Building Ice
Capacity Limited By Vane Open Travel
Stop
Unit Is Building Ice
Unit Is Building Ice
Capacity Limited By High Current
Unit Is Building Ice
Capacity Limited By Phase Unbalance
Unit Operation
Run-Ice Build
Post-Lube
Stop
Active Current Limit Setpt/Current Limit Setpt
Source
Active Current Limit Setpoint: xxx %
[settings source] CLS: xxx %
Operating Mode Display*
(First Line/Second Line)
Capacity Limited By High Cond Press
Capacity Limited By Low Evap Temp
Surge Has Been Detected
Unit Is Running; Transitioning Ice Building
To Normal MIN:SEC
Time Remaining: MIN:SEC
Unit Is Building Ice
Unit Is Building Ice
Post Lubrication
Panic Stop
Starter Dry Run
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Ice Building.
Refrigerant Monitor
The following item will be displayed if the Analog Rfgt
Monitor is installed.
Refrigerant Monitor: xxx.x PPM
Press (Next)(Previous) To Continue
The following item will be displayed if the IPC Rfgt
Monitor option is installed.
Refrigerant Monitor: xxxx PPM R-YYYY
Press (Next)(Previous) To Continue
Where (Y) can equal 123, 11, 22, 134a, or 12.
Purge Pumpout Rate/Purge Max Pumpout Rate
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Pumpout Rate: xxx.x Min/24Hrs
Purge Max Pumpout Rate: xxx.x Min/24Hrs
6CVHE-CLD-1A
Page 12
ASHRAE Guideline 3 Report
Purge Total Pumpout Time/ Purge Total Run
Time
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Total Pumpout Time: xx,xxx.x Min
Purge Total Run Time: xx,xxx.x Hrs
Purge Operating Mode/Purge Status
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Operating Mode: [Mode]
Purge Status: [Status]
Possible values of [Mode] are: Auto, Stop, On, or
Adaptive.
Compressor Discharge Temperature shown only if
discharge temperature is installed.
Discharge Oil Pressure, Oil Tank Pressure
This screen is only displayed if the “Oil Pressure
Protection” setpoint is set to “Transducer” or “Xducer
& Switch.”
Discharge Oil Pressure: xxx.x psig
Oil Tank Pressure: xxx.x psig
Differential Oil Pressure, Oil Temperature
This screen is only displayed if the “Oil Pressure
Protection” setpoint is set to “Transducer” or “Xducer
& Switch.”
Differential Oil Pressure: xxx.x [units]
Oil Tank Temperature: xxx.x f/c
' Differential Oil Pressure: xxx.x [units]' is only
displayed if the “Oil Pressure Protection” setpoint is
set to “Transducer” or “Xducer & Switch.” If 'Switch' is
selected as the setpoint, then ' Differential Oil
Pressure Switch: [Status]' is displayed where
Status is open or closed.
For FastPak, Differential Oil Pressure: xxx.x [units],
this screen is only displayed if the “Oil Pressure
Protection Setpoint” is set to “Diff Xducer" If 'Switch'
is selected as the setpoint, then ' Differential Oil
Pressure Switch: [Status]' is displayed where
Status is open or closed.
The Possible value for [units] is “psid” or “kPa”
dependent upon whether English or SI units are
selected.
Bearing Temperatures #1 and #2
The following will be displayed only if the Bearing
Temp Sensors Option is Installed.
Saturated Evap Rfgt Temp: xxx.x f/c
Compressor Discharge Temp: xxx.x f/c
Bearing Temperature 1: xxx.x f/c
Bearing Temperature 2: xxx.x f/c
Compressor Starts and Running Time
The starts and hours counters are displayed as
follows:
Compressor Starts: xxxxx
Compressor Running Time: HRS:MIN:SEC
Information Manual7
Evaporator Entering and Leaving Water
Temperatures
The following will be displayed only if the low
pressure (< or = to 150 psig) Differential Water
Pressure Sensor Option is Installed.
Evap Entering Water Pressure:xx.x psid/kPa
Evap Leaving Water Pressure: xx.x psid/kPa
Evaporator Differential Water Pressure
The following will be displayed only if the Differential
Water Pressure Sensor Option is Installed.
Chiller Tons
The following will be displayed only if the Differential
Water Sensing Option is installed.
Approximate Chiller Capacity: xxxx Tons/KW
Press (Next)(Previous) To Continue
The possible values for units are “Tons” or “KW.”
Cond Entering and Leaving Water Temps
Dashes will be displayed for condenser entering or
leaving water temperature if the corresponding input
is open or shorted.
Cond Entering Water Temp: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Saturated Cond Temperature/Cond Refrigerant
Press
Saturated Cond Temp: xxx.x f/c
Cond Rfgt Pressure: xxx.x psig
Evap Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Evaporator Water Flow
The following is displayed only if the Differential
Water Sensing Option is installed.
Approx Evaporator Water Flow:xxx.x gpm/lpm
Press (Next)(Previous) To Continue
The possible values for units are “gpm” or “lpm.”
Chilled Water Flow Switch Status
The following will be displayed only if the Differential
Water Sensing Option is not installed. This screen
displays the status of the chilled water flow switch
status at the input to the UCM.
Chilled Water Flow Switch Status:
[y]
Condenser Approach Temp.
Condenser Approach Temp.: xx.x f/c
Press (Next)(Previous) To Continue
Condenser Entering/Leaving Water Pressure
The following will be displayed only if the low
pressure (< or = to 150 psig) Differential Water
Pressure Sensor Option is Installed.
Cond Entering Water Pressure:xx.x psid/kPa
Cond Leaving Water Pressure: xx.x psid/kPa
Condenser Differential Water Pressure
The following will be displayed only if the Differential
Water Pressure Sensor Option is Installed.
Cond Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Possible values for [y] are: Flow Switch is Open/No
Flow or Flow Switch is Closed/Flow.
8CVHE-CLD-1A
Page 14
Condenser Water Flow
The following will be displayed only if the Differential
Water Sensing Option is installed.
Approx Condenser Water Flow: xxx.x gpm/lpm
Press (Next)(Previous) To Continue
The possible values for units are “gpm” or “lpm.”
Condenser Water Flow Switch Status
The following screen is displayed only if the
Differential Water Pressure Sensor Option is not
Installed. This screen displays the status of the
condenser water flow switch status at the input to the
UCM.
Condenser Water Flow Switch Status:
[y]
ASHRAE Guideline 3 Report
Possible values for [y] are Flow Switch is Open/No
Flow or Flow Switch is Closed/Flow
Aux. Bundle or Heat Recovery Temps
The following will be displayed only if either the Heat
Recovery Option or Aux Condenser Option is
installed.
Aux/Heat Rcvy Ent Wtr Temp: xxx.x f/c
Aux/Heat Rcvy Lvg Wtr Temp: xxx.x f/c
Information Manual9
Page 15
Chiller Report
Chiller Report
The Chiller Report sequence is as follows:
Chiller Status, Water Temps & Setpts
Press (Next)(Previous) To Continue
Chiller Operating Mode
Friendly mode line 1
Friendly Mode (First Line/second Line)
Display is Blank
Resetting
Local Stop: Cannot Be Overridden By
Any External Or Remote Device
Remote Display Stop: Chiller May Be
Set To Auto By Any Ext Or Rmt Device
Remote Run Inhibit From Remote Computer
Remote Run Inhibit From External Source
Remote Run Inhibit From Tracer
Run Inhibit From DCM
Heat Sink Temperature Start Inhibit
Diagnostic Shutdown Stop
Diagnostic Shutdown Auto
Waiting For Evaporator Water Flow
Waiting For A Need To Cool
Waiting For A Need To Heat
Waiting For Tracer Communications
To Establish Operating Status
Starting Is Inhibited By Staggered Start
Time Remaining: MIN:SEC
Transitioning To Free Cooling
Waiting For Cond Water Flow
Opening Free Cooling Valves
Cond Water Is Flowing
Closing Free Cooling Valves
Unit Running; Last Mode Free Cooling Limit
Time Remaining To End Of Limit: MIN:SEC
Transitioning To Free Cooling
Waiting For IGV Positioning To Complete
Unit Is Free Cooling
Starting Is Inhibited By Restart
Inhibit Timer: Time Remaining MIN:SEC
Establishing Cond Water Flow
Establishing Oil Pressure
Establishing Cond Water Flow
PreLubrication Time: MIN:SEC
Cond Water Is Flowing
Establishing Oil Pressure
Unit Is Running
Friendly mode line 2
Friendly mode line 1 is indicative of a unit mode.
Friendly mode line 2 is usually a verbal continuation
of line 1 and can be viewed as a continuous
message along with line 1. In some cases Friendly
mode line 2 is the display of an associated timer or
system parameter.
[Friendly mode] will be one of the following:
Auto
Auto
Auto
Starting
10CVHE-CLD-1A
Page 16
Unit Is Running
Capacity Limited By High Current
Unit Is Running
Capacity Limited By Phase Unbalance
Unit Is Running
Capacity Limited By High Cond Press
Unit Is Running
Capacity Limited By Low Evap Temp
Unit Is Running; Capacity Limited By
Vane Open Travel Stop
Unit is Running; Minimum Capacity
Due To Vane Closed Travel Stop
Unit Is Running In Surge Condition
Unit Is Running; Capacity Limited By
Pulldown Rate Based Soft Loading
Unit Is Running; Capacity Limited By
Current Based Soft Loading
Unit Is Running; Hot Water Control
Unit Is Running; Hot Water Control
Capacity Limited By High Current
Unit Is Running; Hot Water Control
Capacity Limited By Phase Unbalance
Unit Is Running; Hot Water Control
Capacity Limited By High Cond Press
Unit Is Running; Hot Water Control
Capacity Limited By Low Evap Temp
Unit Is Running; Hot Water Control
At Vane Open Travel Stop
Unit is Running; Hot Water Control
At Vane Closed Travel Stop
Unit Is Running; Hot Water Control
In Surge Condition
Unit Is Running; Hot Water Control
Pulldown Rate Based Soft Loading
Unit Is Running; Hot Water Control
Current Based Soft Loading
Unit is Running; Base Loaded
Unit is Running; Base Loaded
Capacity Limited By High Current
Unit is Running; Base Loaded
Capacity Limited By Phase Unbalance
Unit Is Running; Base Loaded
Capacity Limited By High Cond Press
Unit Is Running; Base Loaded
Capacity Limited By Low Evap Temp
Unit Is Running; Base Loaded
At Vane Open Travel Stop
Unit is Running; Base Loaded
At Vane Closed Travel Stop
Unit Is Running; Base Loaded
In Surge Condition
Unit Is Running; Base Loaded
Pulldown Rate Based Soft Loading
Unit Is Running; Base Loaded
Current Based Soft Loading
Chiller Report
Unit Is Running In Hot Gas Bypass
Unit Is Running In Minimum Capacity
Time Remaining: HR:MIN:SEC
Unit Is Preparing To Shutdown
Information Manual11
Page 17
Chiller Report
Chiller Operating Mode
The chiller operating modes display comes up first in
the standard report:
[Operating mode line 1]
[Operating mode line 2]
Line 1 (and 2 if needed) indicates a current condition
of the unit as shown in the preceding table (Table 1) .
In some cases, an associated timer or system
parameter will be displayed that assures the
transition to an expected mode is in progress,
particularly during the unit start-up sequence.
Active Chilled Water Setpoint/Evap
Leaving Water Temp
Active Chilled Water Setpoint:xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c
If the chiller is in the Ice Making or Ice Making
Complete state, the following display is substituted
for the above display:
Active Ice Termination Setpoint/Ice
Termination Setpoint Source
The following will be displayed only if the Ice Building
Option is installed.
Active Ice Termination Setpoint: xxx.x f/c
[settings source] ITS: xxx.x f/c
Settings source will be one of the following: Front
Panel or Tracer.
Active Hot Wtr Setpoint/Hot Wtr Setpoint
Source
The following will be displayed only if the Hot Water
Control Option is Installed.
Active Hot Water Setpoint: xxx.x f/c
[settings source] HWS: xxx.x f/c
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Active Ice Termination Setpoint: xxx.x f/c
Evap Entering Water Temp: xxx.x f/c
If the chiller is in the hot water control state, the
following display is substituted for the above display:
Active Hot Water Setpoint: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Active Chilled Water Setpoint/Chilled
Water Setpoint Source
Active Chilled Water Setpoint: xxx.x f/c
[settings source]CWS: xxx.x f/c
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Duplex Control.
12CVHE-CLD-1A
Page 18
Chiller Report
Evaporator Entering and Leaving Water
Temperatures
Evap Entering Water Temp: xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c
Cond Entering and Leaving Water Temps
Dashes will be displayed for condenser entering or
leaving water temperature if the corresponding input
is open or shorted.
Cond Entering Water Temp: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Active Current Limit Setpoint
Active Current Limit Setpoint: xxx %
Press (Next)(Previous) To Continue
Chiller Tons
The following will be displayed only if the Differential
Water Sensing Option is installed.
Approximate Chiller Capacity: xxxx Tons/KW
Press (Next)(Previous) To Continue
The possible values for units are “Tons” or “KW.”
Outdoor Temperature
If the outdoor air temperature input is open or
shorted and neither Outdoor Air Reset nor Low
Ambient Lockout is enabled, display “------” in place
of “xxx.x F.” Otherwise the temperature received
from the chiller module is displayed.
Outdoor Air Temperature: xxx.x f/c
Press (Next)(Previous) To Continue
Aux. Bundle or Heat Recovery Temps
Active Current Limit Setpoint/Current
Limit Setpoint Source
Active Current Limit Setpoint: xxx %
[settings source] CLS: xxx %
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Ice Building.
Evaporator Water Flow/ Condenser
Water Flow
The following will be displayed only if the Differential
Water Sensing Option is installed.
Approx Evaporator Water Flow:xxx.x gpm/lpm
Approx Condenser Water Flow: xxx.x gpm/lpm
The possible values for units are “gpm” or “lpm.”
The following will be displayed only if either the Heat
Recovery Option or Aux Condenser Option is
installed.
Aux/Heat Rcvy Ent Wtr Temp: xxx.x f/c
Aux/Heat Rcvy Lvg Wtr Temp: xxx.x f/c
Chilled Water Setpoint Source
Chld Wtr Setpt Source: [settings source]
Reset Condition: [reset condition]
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Reset condition will be one of the following: None,
Outdoor Temp, or Return Wtr Temp.
Information Manual13
Page 19
Chiller Report
Current Limit Setpoint Source
Cur Lim Setpt Source:[settings source]
Press (Next)(Previous) To Continue
Settings source will be one of the following: Front
Panel, Tracer, External Source, or Ice Building.
Hot Water Setpoint Source
The following will be displayed only if Hot Water
Control is Installed.
Hot Water Setpt Source: [settings source]
Press (Next)(Previous) To Continue
Settings source will be one of the following: Front
Panel, Tracer, or External Source.
Ice Termination Setpoint Source
The following will be displayed when/if remote
computer is installed.
Ice Termn Setpt Source: [settings source]
Press (Next)(Previous) To Continue
Settings source will be one of the following: Front
Panel or Tracer.
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Operating Mode: [Mode]
Purge Status: [Status]
Possible values of [Mode] are: Auto, Stop, On, or
Adaptive.
Possible values of [Status] are:
Idle(Condensing Unit is Off)
Running(Condensing Unit is On)
Pumpout(Temperature Initiated
Service Pumpout(Pumpout initiated by service
Running - Pumpout inhibited by
low temp.
Pumpout Maximum Rate
Disabled
pumpout)
switch)
(Pumpout inhibited by low
liquid temp)
(Max. pumpout rate alarm
disabled)
Saturated Cond Temperature/Cond
Refrigerant Press
Saturated Cond Temp: xxx.x f/c
Cond Rfgt Pressure: xxx.x psig
Purge Alarm Message
The following screen(s) is not displayed if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Alarm Msg: [Status]
[Help Message]
Saturated Evap Temp. and Discharge
Temp.
The Discharge Temp will be displayed only if the
Discharge Sensor Option is installed.
Saturated Evap Rfgt Temp: xxx.x f/c
Compressor Discharge Temp: xxx.x f/c
Information Manual15
Possible values for [Status] are: No Diagnostics
Present (the [Help Message] is: Press (Next)
(Previous) To Continue) or Diagnostic Alarm (the
[Help Message] is: Go to Diag. Menu for Description/
Reset).
Page 21
Refrigerant Report
Purge Suction Temp/Purge Liquid Temp.
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Suction Temp: xxx.x f/c
Purge Liquid Temp: xxx.x f/c
Purge Pumpout Rate/Purge Max
Pumpout Rate
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Pumpout Rate: xxx.x Min/24Hrs
Purge Max Pumpout Rate: xx.x Min/24Hrs
Purge Total Pumpout Time/ Purge Total
Run Time
Purge Adaptive Cycle Time w/Chlr Off/
Time to Purge Remaining
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Adapt Cycle T w/Chlr Off: xxx.x Hrs
Time To Purge Remaining: xxx.x Hrs
If the mode selected is not Adaptive, then the time in
the bottom line is dashed out.
Purge Service Log
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Service Log: Reset Log In Field Start_Up
Purge Pumpout Time: xxxxxxx.x Pumpout Min
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Total Pumpout Time: xx,xxx.x Min
Purge Total Run Time: xx,xxx.x Hrs
Purge Adaptive Cycle Time w/Chlr On/
Time to Purge Remaining
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Adapt Cycle T w/Chlr On: xxx.x Hrs
Time To Purge Remaining: xxx.x Hrs
If the mode selected is not Adaptive, then the time in
the bottom line is dashed out.
Service Log: Reset Log In Field Start_Up
Time Since Last Rst: xxxx Cal Days
Pumpout Avg, Last 30 Days
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
30 Day Purge Pumpout Avg: xxx.x Min
Chiller Average Run Time: xxx.x Hr/Day
30 Day Pumpout Avg,
Chiller Running: xxx.x Min
Last 5 Cycle Pumpout Avg,Interval From
Shtdn To 3 Hrs After Shtdn: xxx.x Min
30 Day Pumpout Avg, Interval From 3Hrs
After Shtdn To Next Start: xxx.x Min
16CVHE-CLD-1A
Page 22
Refrigerant Report
Refrigerant Monitor
The following item is displayed if the Analog
Refrigerant Monitor option is installed.
Refrigerant Monitor: xxx.x PPM
Press (Next)(Previous) To Continue
The following items are displayed if the IPC
Refrigerant Monitor option is installed.
The following screen is displayed if the refrigerant
monitor scanner is installed:
Refrigerant Monitor Mode: [Mode]
Scanner Channel X XXXX PPM [Rfgt Type]
The following screen is displayed if the channel
scanner is not installed:
Refrigerant Monitor Mode: [Mode]
The following is displayed if the IPC Refrigerant
Monitor Auxiliary input option is installed.
Rfgt Mon Auxiliary Input: XX.X mA
Press (Next) (Previous) To Continue
Approach Temperature
Evaporator Approach Temp: XXX.X F
Condenser Approach Temp: XXX.X F
XXXX PPM [Rfgt Type]
Possible values of Mode are: Warmup, Ready,
Monitor Check, Trouble.
If the PPM is out of range low or high “-Err” and
“++++” respectively are displayed. If the
concentration has not been determined, or the
refrigerant monitor is in “Monitor Check” mode, “-----”
is displayed.
The following is displayed if the channel scanner
option is installed.
Last Rfgt Conc Chan1 Chan2 Chan3 Chan4
PPM [Rfgt Type] XXXX XXXX XXXX XXXX
If the PPM is out of range low or high “-Err” and
“++++” respectively are displayed. If a channel is
inactive, “-----” is displayed.
Refrigerant Monitor Case Temp: XXX.X F
Refrigerant Monitor Bench Temp: XXX.X F
Information Manual17
Page 23
Compressor Report
Compressor Report
The Compressor Report Group sequence is as
follows.
Report Heading
Compressor Hours, Starts & Amps
Press (Next)(Previous) To Continue
Differential Oil Pressure, Oil Temperature
Differential Oil Pressure: xxx.x [units]
Oil Tank Temperature: xxx.x f/c
The possible value for [units] is “psid” or “kPa”
dependent upon whether English or SI units are
selected.
Discharge Oil Pressure, Oil Tank
Pressure
Discharge Oil Pressure: xxx.x psig
Oil Tank Pressure: xxx.x psig
AF Boundary Pressure Coefficient/AF
Press. Coefficient
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator and Adaptive
Speed Control Algorithm is Enabled.
AF Boundary Press Coefficient: x.xxx
AF Pressure Coefficient: x.xxx
Note: This is a Report only for Troubleshooting
purposes.
AF Re-Optimization Timer Time
Remaining
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator and Adaptive
Speed Control Algorithm is Enabled.
AF Re-Optimization Time Remaining:xx:xxHrs
Press (Next) (Previous) to Continue
Note: This is a Report only for Troubleshooting
purposes.
AF Compressor Speed Command
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator and Adaptive
Speed Control Algorithm is Enabled.
AF Compressor Speed Command: xx Hz
AF Compressor Speed Command: xxxx RPM
Range of values is 2520 to 3600 rpm in increments of
1 rpm. Factory default is 3600 rpm.
18CVHE-CLD-1A
Inlet Guide Vane Position
This screen does not appear if “Inlet Guide Vane
Output” is set to “Pulsed.”
Inlet Guide Vane Position xxx.x % Open
Inlet Guide Vane Position xx.x degrees
Page 24
Compressor Report
Compressor Phase Currents % RLA
Compressor Phase Currents - % RLA
A xxxx.x % B xxxx.x % C xxxx.x %
Compressor Line Currents Amps
Compressor Phase Currents - Amps
A xxxx amps B xxxx amps C xxxx amps
Compressor Line Voltages
Compressor Line Voltages
AB xxxx v BC xxxx v CA xxxx v
This data is displayed only if the line voltage sensing
option is installed. if not installed, no screen is
displayed.
Compressor Winding Temperatures
Compressor Winding Temperatures
W1 xxx f/c W2 xxx f/c W3 xxx f/c
Compressor Starts and Running Time
The starts and hours counters are displayed as
follows:
Compressor Starts: xxxxx
Compressor Running Time: HRS:MIN:SEC
Bearing Temperatures #1 and #2
The following will be displayed only if the Bearing
Temp Sensors Option is Installed.
Bearing Temperature 1: xxx.x f/c
Bearing Temperature 2: xxx.x f/c
Compressor Power Factor and Watts
The following is displayed only if the Line Voltage
Sensing Option is Installed AND the starter type is
Not “Adaptive Frequency” or AFD AND Compressor
Power Source is Utility AND External KW is Not
Installed.
Compressor Power Factor: xx %
Compressor KiloWatts: xxxx KW
Solid State Starter Heat Sink Temp.
The following will be displayed only if the Solid State
Starter is installed.
Solid State Starter Heat Sink: xxx.x f/c
Press (Next)(Previous) To Continue
HGBP Time
If HGBP is installed in the unit the following screen is
displayed:
HGBP Time: HRS:MIN:SEC
Press (Next)(Previous) To Continue
Information Manual19
Page 25
Operator Settings
Operator Settings
Settings Group Keys
The four settings Group Keys for CVHE/CVHF/
CVHG are as follows:
q Operator Settings - non-password protected
menu items that can be changed by the operator
q Service Settings - menu items that should only
be changed by a qualified service technician
q Service Tests - activate outputs of Chiller (e.g. oil
pump)
q Diagnostics - abnormal operating conditions,
informational warnings, automatic reset, and
manual reset types and other information.
Operator Settings Group Heading
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.
The Operator Settings Group sequence follows.
The possible values for status are “Locked” or
“Unlocked”. If the password status is locked, the
password message will be “Enter Password to
Unlock”. The user will then depress (-)(+)(-)(+)(-)(+)
followed by the <Enter> key. The password
keystrokes will be echoed to the screen as a visual
aide. The last six keystrokes represent the current
password, and up to twenty keystrokes can be
entered. An incorrect password, or the twenty-first
keystroke will result in the password message
“Invalid Password”.
If the password status is unlocked, the password
message will be “Press (Enter) to Lock”. Pressing
<Enter> locks the settings in ALL the menus. If the
password is entered to unlock the settings, this
unlocks the settings in ALL menus.
Whenever a password is in use the “Press (+)(-) to
change setting” message will be suppressed on
setpoint screens. Any attempt to change the setting
will result in the message “Setting is Locked”. The
password once entered will remain valid until
canceled.
Set Contrast - Applies to
CCCLD Display Only.
Set Contrast: Press (√) to Save
Press (+)(-) to Change Setting
Chilled Water & Current Limit Setpts
Press (Next)(Previous) To Continue
If the Menu Settings Password feature is Enabled in
the Service Setup Group following each setting
group heading the following is displayed:
Settings In This Menu Are [status]
[password message]
Likewise, if the Menu Settings Password is Disabled
in the Service Setup Group, the above screen will not
appear.
20CVHE-CLD-1A
Purge Operating Mode
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Operating Mode: [Mode]
Press (+)(-) to Change Setting
Possible values of [Mode] are: Stop, On, Auto
(Factory Default) and Adaptive.
Page 26
Time Of Day Setting
Operator Settings
Current Time/Date HH:MM xm Mon,XX XXXX
(Enter) to Change : (Next) to Continue
The top level "CurrentTime/Date" will be displayed
when this screen is first selected. Pressing the
<Next> or <Previous> key will go to the next or
previous screen as usual.
If the <Enter> key is selected, five separate screens
can be displayed with which the time may be set. The
“Current Time/Date” will be displayed on line one of
each of these screens. Each of these screens will
change one element of the current time/date. The
second line of each screen will indicate which
element of the current time/date is being changed.
If the first time changing screen is being displayed
and the <Previous> key is pressed, the top level
“Current Time/Date” screen will be displayed and the
<Enter> key will have to be selected to re-enter the
time changing screens. If the fifth time changing
screen is being displayed and the <Next> key is
pressed, the next screen will be displayed. If
<Previous> is selected at this point, the top level
“Current Time/Date” screen will be displayed and the
<Enter> key will have to be selected to re-enter the
time changing screens
To change an element of the current time/date,
select <Enter> from the top level “Current Time/Date”
screen to enter the time changing screens. Hit
<Next> or <Previous> to get to the proper screen.
Press the <+> <-> keys to change the element to it's
proper value and press the <Enter> key to store the
new time/date. A message “Updating Chiller Clock,
Please Wait” is displayed for two seconds after the
<Enter> key is pressed.
The five time changing screens are as follows:
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Month, Press(+)(-) & (Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Day, Press (+)(-) & (Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Year, Press (+)(-) & (Enter)
Front Panel Chilled Water Setpoint
Front Panel Chilled Wtr Setpt:xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 0 to 65°F (-17.8 to 18.3°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
44.0°F (6.7°C).
As shown above, the second line of a setting display
normally says:
“Press (+)(-) to Change Setting”
However, the following is displayed as the second
line of the display if an attempt is made to increment
the setpoint above the end of the setpoint range:
“Top of Range, Press (-) to Change”
The following is displayed as the second line of the
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Hour, Press (+)(-) & (Enter)
display if an attempt is made to decrement the
display below the end of the setpoint range:
“Bottom of Range, Press (+) to Change”
The following is displayed as the second line of the
display if a key other than <+>, <->, <Enter>, or
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Minute,Press (+)(-) &(Enter)
<Cancel> is pressed after <+> or <-> is pressed:
“Press (+)(-)(Enter)(Cancel) to Advance”
The exception to the above message is when the
<Stop> key is pressed. <Stop> is always active.
Information Manual21
Page 27
Operator Settings
Other messages are displayed on the second line of
the display for special cases as noted below in
association with the affected setpoint display.
When the Front Panel Chilled Water Setpoint is
within 1.7°F of the Leaving Water Temperature
Cutout Setpoint, the second line of this display will
read:
“Limited by Cutout Setpt, (+) to Change”
Front Panel Hot Water Setpoint
The Front Panel Hot Water Setpoint is only displayed
when the Hot water option is Installed.
Front Panel Hot Wtr Setpt: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 85 to 140°F (37.8 to 60.0°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
130°F (54.4°C).
Front Panel Current Limit Setpoint
Control Type
The following will be displayed only if the Hot Water
Control Option is Installed.
Control Type is: [control]
Press (+)(-) to Change Setting
Possible values of [control] are: Chilled Water
(Factory Default), Hot Water, and Ext. Hot/Chilled
Wtr Input.
Free Cooling
The free cooling enable screen is displayed only if
the free cooling option is installed.
Free Cooling: [Status]
Press (+)(-) to Change Setting
Possible values are: Disable (Factory Default) and
Enable.
Chilled Water Reset Type
Front Panel Current Limit Stpt: xxx %
Press (+)(-) to Change Setting
Range of values is 40 to 100% in increments of 1 %.
Factory Default is 100%.
Print Report
This screen is shown only when the Printer Option is
Installed.
Press (Enter) to Print Report
Press (Next)(Previous) To Continue
When <Enter> is pushed, a 2 second message
appears as shown below and then returns to the
above screen.
The Print Command is Being
Sent to the Printer
Chilled Water Reset Type: [type]
Press (+)(-) to Change Setting
The possible values for [type] are: Disable (Factory
Default), Return, Constant Return, and Outdoor Air.
If either Disable or Constant Return are selected, the
remaining chilled water reset displays are skipped by
the CLD. If either Return or Outdoor Air are selected,
the first word of the remaining chilled water reset
displays will be the type of reset.
Help Notes:
1 When CWR is enabled, the UCM will step to CWS
at a rate of 1°F every five minutes.
2 Constant Return is a short version of Return
CWR; it will reset the leaving chilled water
setpoint to provide a constant entering water
temperature. The reset ratio defaults to 100%,
start rest point to design delta T and max reset
setpoint to design.
3 Chilled water is reset based on either return water
temperature or outdoor air temperature.
4 This screen does not appear when the chiller is
22CVHE-CLD-1A
Page 28
Operator Settings
under Duplex Control and it is Compressor B.
Reset Ratio
This is the aggressive value. A higher number is a
quicker response.
[type] Reset Ratio: xxx %
Press (+)(-) to Change Setting
The values for Reset Ratio for each of the reset types
are:
Reset
Reset
Type
Return10 to
Outdoor80 to -80%1%1%10%
Ratio
Range
120%
Increment
(Eng.
units)
1%1%50%
Increment
(SI)
Default
Value
Start Reset Setpoint
This is the Delta T the unit is trying to maintain.
Press (+)(-) to Change Setting
The values for Maximum Reset for each of the reset
types are:
Maximum
Reset
Type
Return0 to 20°F
Outdoor0 to 20°F
Reset
Range
(0.1 to
11.1°C)
(0.1 to
11.1°C)
Increment
(Eng.
units)
1°F1°C5°F
1°F1°C5°F
Increment
(SI)
Default
Value
(2.8°C)
(2.8°C)
Ice Building Enable
The following will be displayed only if the ice building
option is installed.
Ice Building: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
[type] Start Reset Setpoint: xxx.x F
Press (+)(-) to Change Setting
The values for Start Reset for each of the reset types
are:
Start
Reset
Type
Return4 to 30°F
Outdoor50 to
Reset
Range
(2.2 to
16.7°C)
130°F (10
to 54.4°C)
Increment
(Eng.
units)
1°F1°C10°F
1°F1°C90°F
Increment
(SI)
Default
Value
(5.6°C)
(32.2°C)
Maximum Reset Setpoint
Controllable Maximum Reset value. Allows a reset
“Up” of this value. The chilled water is maintained
between the leaving chilled water setpoint and the
new reset value.
[type] Max Reset Setpoint: xxx.x F
Front Panel Ice Termination Setpoint
The following will be displayed only if ice building
option is installed.
Panel Ice Termination Setpoint:xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 20.0 to 32.0°F (-6.7 to 0.0°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
27.0°F (-2.8°C).
Ice Making To Normal Cooling Transition
Timer
The following will be displayed only if the ice building
option is installed. This allows for a timed idle/stop
period for (X) minutes when coming out of ice before
going into the cooling mode (timed by Chiller).
Ice-To-Normal Cooling Timer: xx min
Press (+)(-) to Change Setting
Information Manual23
Page 29
Operator Settings
Range of values is 0 to 10 min. Factory Default is 5
min.
Chilled Water Setpoint Source
If the Tracer Option is installed, the word “Default”
will appear in front of the setpoint source.
[Default] Chilled Water Setpoint Source:
[source]
Possible values of [source] are: Front Panel (Factory
Default) and External Source (This choice shows up
only if the External Chilled Water Setpoint is Installed
at the Machine Configuration menu.).
Note: There is a Tracer installed screen in the
Machine configuration menu. If Tracer does not
choose to write a setpoint then the “default” setpoint
source is used, e.g. Front Panel.
Current Limit Setpoint Source
If the Tracer Option is installed, the word “Default”
will appear in front of the setpoint source.
Possible values of [source] are: Front Panel (Factory
Default) and External Source (This choice shows up
only if the External Hot Water Setpoint is Installed at
the Machine Configuration menu.)
Note: There is a Tracer installed screen in the
Machine configuration menu. If Tracer does not
choose to write a setpoint then the “default” setpoint
source is used, e.g. Front Panel.
Ice Termination Setpoint Source
The following will be displayed only if the Ice Building
Option is installed.
If the Tracer Option is installed, the word “Default”
will appear in front of the setpoint source.
[Default] Ice Termination Setpoint Source:
[source]
Possible values of [source] are: Front Panel (Factory
Default).
Note: There is a Tracer installed screen in the
Machine configuration menu. If Tracer does not
choose to write a setpoint then the “default” setpoint
source is used, e.g. Front Panel.
[Default] Current Limit Setpoint Source:
[source]
Possible values of [source] are: Front Panel (Factory
Default), and External Source. (This choice shows up
only if the External Current Limit Setpoint is Installed
at the Machine Configuration menu.)
Note: There is a Tracer installed screen in the
Machine configuration menu. If Tracer does not
choose to write a setpoint then the “default” setpoint
source is used, e.g. Front Panel.
Hot Water Setpoint Source
If the Tracer Option is installed, the word “Default”
will appear in front of the setpoint source.
[Default] Hot Water Setpoint Source:
[source]
Outdoor Air Temperature Source
If the Tracer is installed the Tracer Outdoor Air
Temp. is both used and displayed. If no Tracer is
installed the chiller module outdoor air temperature
sensor is used. If no sensor is installed, dashes are
displayed on the display of Outdoor Air Temperature.
Setpoint Source Override
Setpoint Source Override:
[source]
Possible values of [source] are: “None” (Factory
Default), “Use Front Panel Setpoints”, “Override
Tracer, and Use Default Setpoints” (Available only if
Tracer Option installed).
24CVHE-CLD-1A
Page 30
Service Settings (Non Password Protected Service Settings Group)
Service Settings (Non Password Protected Service Settings Group)
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.
The Service settings menu has three distinct
grouping of items within it. The first group is the nonpassword protected group that consists of all of the
settings, feature enables, setpoints etc., that are
benign; while they are unlikely to be changed often
by a user or operator, changes in them do not
seriously effect the standard protection or reliability
of the chiller.
The other two groupings are protected, each with a
separate password. These two groups are for
changing parameters and settings regarding field
commissioning and fundamental protection and
control of the chiller subsystems (Field Startup) or for
programming of the UCM as to how the specific
chiller was built in the Factory (Machine
Configuration). Once properly set, the items in these
protected menus should never be changed again
without specific knowledge of the effects of the
changes. In rare instances, certain field problems
may be corrected by making changes in these
protected menus but certain aspects of chiller
reliability may be compromised. The main reason
these are accessible at all, is for field commissioning
and to allow for the field programming of service
replacement UCMs.
Two additional password protected menus are
available in the Service Settings group if the IPC
Refrigerant Monitor is installed. The Refrigerant
Monitor Settings Group and the Refrigerant Monitor
Calibration Group are used to configure the IPC
Refrigerant Monitor.
Service Setting Group Heading
Service Settings: Basic Setups
Press (Next)(Previous) To Continue
Menu Settings Password
If the Menu Settings Password is Enabled in the
Service Setup Group, following each setting group
heading the following will be displayed:
Settings In This Menu Are [status]
[password message]
Likewise, if the Menu Settings Password is Disabled
in the Service Setup Group, the above screen will not
appear.
The possible values for status are “Locked” or
“Unlocked”. If the password status is locked, the
password message will be “Enter Password to
Unlock”. The user will then depress (-)(+)(-)(+)(-)(+)
followed by the <Enter> key. The password
keystrokes will be echoed to the screen as a visual
aide. The last six keystrokes represent the current
password, and up to twenty keystrokes can be
entered. An incorrect password, or the twenty-first
keystroke will result in the password message
“Invalid Password”.
If the password status is unlocked, the password
message will be “Press (Enter) to Lock”. Pressing
<Enter> will lock all of the setpoint menus. Likewise,
if the password status is locked and the correct
password is entered, all of the setpoint menus will be
unlocked.
Whenever a password is in use the “Press (+)(-) to
change setting” message will be suppressed on all
setpoint screens. Any attempt to change a setpoint
will result in the message “Setting is Locked” being
displayed for 1 second. The password once entered
will remain valid until canceled.
Information Manual25
Page 31
Service Settings (Non Password Protected Service Settings Group)
Service Settings Key
Menu Structure Under
Figure 3
Service Settings Group
The Service Settings Key
(+)(+)(-)(-)(+)(+)
(+)(-)(+)(-)(+)(-)
(-)(-)(+)(+)(-)(-)
(-)(+)(-)(-)(+)(+)
or
(+)(+)(-)(+)(-)(-)
Password Screen
Password Screen
Password Screen
Password Screen
Field Startup
Group
Machine Config. Group
Refrigerant Monitor
Settings Group
Refrigerant Monitor
Calibration Groups
Keypad/Display Lockout
Password will be required to Unlock
This display only appears if the keypad lockout
feature is enabled.
If the <Enter> key is pressed to lock the keypad, the
following message is displayed, and all further input
from the keypad is ignored, including the <Stop> key,
Press (Enter) to Lock Display & Keypad
26CVHE-CLD-1A
until the password is entered. The password consists
Page 32
Service Settings (Non Password Protected Service Settings Group)
of pressing the <Previous> and <Enter> keys at the
same time.
******DISPLAY AND KEYPAD ARE LOCKED******
********ENTER PASSWORD TO UNLOCK********
If the keypad is locked and the password is entered,
the display will go to the Chiller Operating Mode
display of the Chiller Report.
Language Setting
Language: xxxxxxxx
Press (+)(-) to Change Setting
Possible Language Selections for the CLD are:
English (Factory Default), Francais, Deutsche,
Espanol, Nippon (also known as Katakana (uses
Japanese Characters), Italian, Nederland, and
CODED. Possible Language Selections for the
CCCLD are: English (Factory Default), Traditional
Chinese, Simplified Chinese, Korean, Thai, and
Japanese.
Display Menu Headings Enable
Display Menu Headings: [d/e]
Press (+)(-) to Change Setting
The Factory Default value is Enabled. If disabled the
Menu Headings in each Menu or Group do not
appear.
Clear Custom Menu
Press (Enter) To
Clear The Custom Menu
When <Enter> is pushed a 2 second message
appears as shown below and then returns to above
screen.
Custom Menu Has Been Cleared
Differential to Start Setpoint
Display Units
Display Units: [Type]
Press (+)(-) to Change Setting
Possible values of [Type] are: English (Factory
Default) and SI.
Decimal Places Displayed Setpoint
Decimal Places Displayed: [Status]
Press (+)(-) to Change Setting
The choices for Status are: XXX.X (Factory Default)
and XXX.
Differential to Start Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 1 to 10°F (0.5 to 5.5°C) in
increments of 1 or 0.1°F or C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
5°F (2.8°C).
Differential to Stop Setpoint
Differential to Stop Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 1 to 10°F (0.5 to 5.5°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
5°F (2.8°C).
Information Manual27
Page 33
Service Settings (Non Password Protected Service Settings Group)
Evap/Cond Pump Off Delay Time
Evap Pump Off Delay: xxx Min
Press (+)(-) to Change Setting
Range of values is 0 to 30 minutes in increments of 1
Minute. Factory Default is 1 Minute.
If the current running mode is hot water control state
the following display is substituted for the above
display:
Cond Pump Off Delay: xxx Min
Press (+)(-) to Change Setting
Printer Setups
This screen is shown only when the Printer Option is
Installed.
The choices for Status are: Enable (Factory Default)
and Disable.
Number of Pre-Diag Reports: xx
Press (+)(-) to Change Setting
Range of values is 1 to 5 in increments of 1. Factory
Default is 5.
Diagnostic Report Interval: xx sec
Press (+)(-) to Change Setting
Range of values is 2 to 120 seconds in increments of
1 second. Factory Default is 5 seconds.
Printer, Baud Rate: [Status]
Press (+)(-) to Change Setting
The choices for Status are: 300, 1200, 2400, 4800,
9600 (Factory Default), and 19,200.
Printer Setups
(Enter) to Change : (Next) to Continue
If <Next> is pressed the following printer setup
screens are skipped. If <Enter> is pressed the
following screens are displayed to permit
modification of the printer setups.
Print on Time Interval: [Status]
Press (+)(-) to Change Setting
The choices for Status are: Enable (Factory Default)
and Disable.
Print Time Interval: xxx Hours
Press (+)(-) to Change Setting
Range of values is 1 to 24 Hours in increments of 1
Hour. Factory Default is 8 Hours.
Print on Diagnostic: [Status]
Press (+)(-) to Change Setting
Printer, Parity: [Status]
Press (+)(-) to Change Setting
The choices for Status are: None (Factory Default),
Odd, and Even.
Printer, Data Bits: [Status]
Press (+)(-) to Change Setting
The choices for Status are: 8 (Factory Default) and 7.
Printer, Stop Bits: [Status]
Press (+)(-) to Change Setting
The choices for Status are: 1 (Factory Default) and 2.
Printer Handshaking: [Status]
Press (+)(-) to Change Setting
The choices for Status are: XON/XOFF (Factory
Default), DTR, RTS, and None.
28CVHE-CLD-1A
Page 34
Clear Restart Inhibit Timer
Press (Enter) to
Clear the Restart Inhibit Timer
When <Enter> is pushed, a 2 second message
appears as shown below and then returns to above
screen.
Restart Inhibit Timer Has Been Cleared
Service Settings (Non Password Protected Service Settings Group)
Information Manual29
Page 35
Field Start-up
Field Start-up
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.
Field Startup
The Field Startup Group password is + + - - + +
<Enter>. The Field Startup Group contains items that
are primarily associated with Field Commissioning of
the chiller as well as the fundamental control and
protection of the chiller subsystems. If the field
startup password is entered, the display goes to the
menu defined below. If a key is not pressed every 10
minutes in this password protected menu, the display
returns to the Chiller Operating Mode display of the
Chiller Report, and the password must be entered
again to return to this menu.
Field Start-up Group Heading
in this condition, both the <Stop> and <Auto> keys
do not function.
Keypad/Display Lock Feature: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
When the keypad lock feature is Disabled, the
keypad lock display does not appear in the nonpassword protected area of the Service Settings
menu and the Keypad/Display cannot be locked.
When the keypad/display lock feature is Enabled, the
keypad lock display does appear in the Service
Settings menu so the keypad can be locked.
Menu Settings Password Enable
The Menu Settings Password permits the Settings in
each of the menus to be password protected. All
Report Menus and Setting Menus can still be viewed
at any time if this feature is either Enabled or
Disabled; the <Stop> and <Auto> keys also remain
active. If this feature is Enabled, then all Menu
Settings are password protected.
Menu Settings Password Feature: [d/e]
Field Start-up Group Settings
Press (Next)(Previous) To Continue
This header appears when the headers do not
appear in the Service Settings menu.
Keypad/Display Lock Feature Enable
This feature permits the entire Keypad and Display to
be locked out. A message appears on the screen to
describe this condition. No access is permitted to
either the Report screens or the Setting Screens
when this feature is both Enabled here and Locked at
the Service Settings Menu. It is important to note that
30CVHE-CLD-1A
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
When the feature is Disabled, the Menu Setting
Password display does not appear at the top of each
of the Settings Menus and the Menu Settings cannot
be password protected. When the Menu Setting
Password feature is Enabled, the Menu Settings
Password display appears just below each of the
Settings Menu Headers so the settings can be
changed if the proper password is entered.
Page 36
Field Start-up
ICS Address
ICS Address: xx
Press (+)(-) to Change Setting
Range of values is 1 to 127 in increments of 1.
Factory Default is 65.
Power Up Start Delay Time
Power Up Start Delay Time: xxx sec
Press (+)(-) to Change Setting
Range of values is 0 to 600 seconds in increments of
1. Factory Default is 0 sec.
Design Delta Temperature Setpoint
Design Delta Temp Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 4 to 30°F (2.2 to 16.7°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
10°F (5.5°C).
When this setpoint is adjusted below 35.3°F the
following is displayed on the second line:
“Warning: Adequate Antifreeze Required”.
Low Refrigerant Temperature Cutout
Setpoint
Low Rfgt Temp Cutout Setpt: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is -35 to 36°F (-37.2 to 2.2°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. The Factory
Default is 32.0°F (0.0°C).
Low Evaporator Water Flow Warning Setpoint
The following will be displayed only if the Differential
Water Sensing Option is installed.
Low Evap Flow Warning: xx.x gpm/ton
Press (+)(-) to Change Setting
Range of values is 0.0 to 4.0 gpm/ton (0.0 to 15.1
lpm/ton) in increments of 0.1. Factory Default is 1.2
gpm/ton (4.5 lpm/ton).
Leaving Water Temperature Cutout
Condenser Limit Setpoint
Setpoint
Condenser Limit Setpoint: xx % HPC
Lvg Wtr Temp Cutout Setpoint:xxx.x f/c
Press (+)(-) to Change Setting
Range of values is -10 to 36°F (-23.3 to 2.2°C) in
increments of 1 or 0.1 °F or °C depending on the
Service Setup Screen xxx or xxx.x. The Factory
Default is 36.0°F (2.2°C).
When this setpoint is within 1.7°F of the Front Panel
Chilled Water Setpoint, the Front Panel Chilled
Water Setpoint is increased along with this setpoint
to maintain the differential. A message will be
displayed for 2 seconds to indicate that the FPCW
setpoint has been increased.
Information Manual31
Press (+)(-) to Change Setting
Range of values is 80 to 120% in increments of 1%.
Factory Default is 93%.
Maximum Restart Inhibit (RI) Timer
Setting
Maximum RI Timer: xxx Minutes
Press (+)(-) to Change Setting
The Range of values is 30 to 60 Minutes in
increments of 1 Minute. Factory Default is 60
Minutes.
Page 37
Field Start-up
Purge Control/Type
Purge Control/Type: [Type]
Press (+)(-) to Change Setting
Possible values of [Type] are: Micro Purge (Factory
Default) and Stand-Alone Purge.
Purge Service Log Reset
The following screen(s) shall be suppressed if the
selected Purge Control/Type is “Stand-Alone Purge”.
Service Log: Press (Enter) to Reset
Purge Pumpout Time: xxxxxxxx.x Pumpout Min
Service Log: Press (Enter) to Reset
Time Since Last Reset: xxxxx Cal Days
Note: Resetting in either screen above will reset both
fields of data to Zero.
Purge Maximum Pumpout Rate
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Press (+)(-) to Change Setting
Range of values is 1 to 72 Hours in increments of 1
Hour. Factory Default is 0 Hours.
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Low Liquid Temp Inhibit:[d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
Purge Low Chiller Sat. Cond. Temp
Setpoint
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Prg Low Liquid Temp Inhibit Setpt xx.x f/c
Press (+)(-) to Change Setting
Range of values is 32 to 50°F(0.0 to 10.0°C) in
increments of 1 or 0.1°F or°C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
40°F (4.4°C).
Purge Max Pumpout Rate: xx Min/24 Hrs
Press (+)(-) to Change Setting
Range of values is 1 to 100 Minutes/24 Hrs in
increments of 1 Minute/24 Hrs. Factory Default is 20
Minutes/24 Hrs.
Purge Service Excessive Pumpout
Override Timer
The following screen(s) does not appear if the
selected Purge Control/Type is “Stand-Alone Purge.”
Purge Disable Pumpout Alarm for: xx Hrs
32CVHE-CLD-1A
Surge Protection Enable
Surge Protection: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable
(Factory Default). Surge protection is based on motor
current fluctuation.
Page 38
Field Start-up
Under/Over Voltage Protection Enable
This screen does not appear if the Line Voltage
Sensing Option is not installed or Compressor Power
Source is Engine/Generator.
Line voltage above + 10% of nominal. (Must hold = +
10 % of nominal. Must trip = + 15 % of nominal.
Reset differential = min. of 2% and max. of 4%. Time
to trip = minimum of 1 min. 10 sec. and maximum of
5 min. 20 seconds).
Under/Over Voltage Protection: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
Note: Under/Over Voltage Protection is activated
only if Under/Over Voltage Protection is enable and
Line Voltage Sensing Option is Installed.
Phase Reversal Protection Enable
This screen does not appear if the starter type is
“Adaptive Frequency” or “AFDB.”
Phase Reversal Protection: [d/e]
Press (+)(-) to Change Setting
Momentary Power Loss (MPL) Protection
Enable
This screen does not appear if the starter type is
“Adaptive Frequency” or “AFDB.” or Compressor
Power Source is Engine/Generator.
Momentary Power Loss Protection: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable
(Factory Default).
For MPL, on every power down, the reset inhibit
timer is reset to 30 seconds if the motor temperature
is <165°F and 15 minutes if the motor temperature is
> or = to 165°F.
Enhanced Oil Temp. Protection
This screen does not appear if the starter type is
“Adaptive Frequency” or “AFDB.
When enhanced oil protection is enabled, the oil
heater relay is energized at 140.5ºF (60.3ºC) and deenergized at 145.5ºF (63.1ºC). The low oil
temperature cutout “setpoint” is equal to the
saturated evaporator refrigerant temperature plus
30ºF (16.6ºC) or 100 ºF (37.8ºC) which ever is
larger.”
Possible values of [d/e] are: Disable and Enable
(Factory Default).
A phase reversal is detected on the incoming current.
On a compressor startup, the phase reversal logic
must detect and trip in 0.7 seconds.
Phase Unbalance Limit Enable
Phase Unbalance Limit: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable
(Factory Default).
The RLA of the motor is derated by resetting the
active current limit. The trip point is a 30% phase
unbalance for 90 seconds.
Information Manual33
Enhanced Oil Temp Protection: [option]
Press (+)(-) to Change Setting
Possible options are: Disable and Enable (Factory
Default).
Oil Temp Setpoint
This screen does not appear when Enhanced Oil
Temperature Protection is enabled.
Oil Temp SetPoint: xxx.x f/c
Press (+)(-) to Change Setting
The range of values is 100°F to 160°F (37.8 to
71.1°C) in increments of 1 or 0.1°F or °C, depending
Page 39
Field Start-up
on the Service Setup Screen xxx or xxx.x. Factory
Default is 143°F (61.9°C).
Low Oil Temp Cutout
This screen does not appear when Enhanced Oil
Temperature Protection is enabled.
Low Oil Temp Cutout: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 80 to 140°F (26.7 to 60.0°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
95°F (35.0°C).
Low Oil Temp Start Inhibit Differential
This screen only appears when Enhanced Oil
Temperature Protection is enabled.
External Base Loading Enable
External Base Loading: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
Soft Load Control Enable
Soft Load Control: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
Soft Load Starting Current Limit
Low Oil Temp Start Inhibit Diff: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 20 to 30°F (11.1 to 16.7°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
27.5°F (15.3°C).
High Discharge Temp Cutout
This screen is displayed only if the Discharge Sensor
Option is installed.
High Discharge Temp Cutout: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 170 to 220°F (76.6 to 104.4°C) in
increments of 1 or 0.1°F or °C depending on the
Service Setup Screen xxx or xxx.x. Factory Default is
200°F (93.3°C).
Soft Load Starting Current Limit: xx %
Press (+)(-) to Change Setting
Range of values is 40 to 100% in increments of 1%.
Factory Default is 100%.
Soft Load Current Limit Rate Of Change
Soft Load Current Limit Rate:x.x %/min
Press (+)(-) to Change Setting
Range of values is 0.5 to 5%/Min in increments of 1
or 0.1%/Min depending on the Service Setup Screen
xxx or xxx.x. Factory Default is 5%/Min.
Soft Load Lvng Wtr Temp Rate of
Change
Soft Load Lvg Water Rate: x.x f/c/min
Press (+)(-) to Change Setting
Range of values is 0.5 to 5°F/Min (0.3 to 2.8°C/Min)
in increments of 1 or 0.1°F/Min depending on the
34CVHE-CLD-1A
Page 40
Field Start-up
Service Setup Screen xxx or xxx.x. Factory Default is
5°F/Min (2.8°C/MIn).
Hot Gas Bypass Enable
This screen does not appear when the hot gas
bypass option is not installed.
Hot Gas Bypass Control: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory
Default) and Enable.
HGBP Timer Enable
The following will be displayed only if HGBP is
installed.
HGBP Timer: [Status]
Press (+)(-) to Change Setting
Range of values is 0 to 30% in increments of 1%.
Factory Default is 10%. This setting drives the IGVs
to the target when HGBP is entered.
LWT Control Proportional Gain (Kp) Setpt
LWT Proportional Gain: xxx.x %/F
Factory Dflt is 10.0 %/F & 18.0 %/C
The range of valves is 0 to 100%/°F (0 to 180%/°C)
in increments of 0.1.
LWT Control Integral Gain (Ki) Setpt
LWT Integral Gain:x.xxx %/F
Factory Dflt is 0.110 %/F & 0.198 %/C
The range of valves is 0 to 1%/°F (0 to 1.8%/°C) in
increments of 0.001. The Factory Default is 0.110%/
°F (0.198%/°C).
The choices for Status are: Enable (Factory Default)
and Disable (Unlmtd Time).
Maximum HGBP Time
The following will be displayed only if HGBP is
Installed and the HGBP Timer is Enabled.
Maximum HGBP Time: xxx Min
Press (+)(-) to Change Setting
Range of values is 1 to 480 minutes in increments of
1 Minute. Factory Default is 30 Minutes.
HGBP Mode, Vane Target
This screen does not appear when the hot gas
bypass option is not installed.
Hot Gas Bypass Mode IGV Target:xx %
Press (+)(-) to Change Setting
LWT Control Derivative Gain (Kd) Setpt
LWT Derivative Gain: xx.x %/F
Factory Dflt is 00.0 %/F & 00.0 %/C
The range of valves is 0 to 10.0%/F (0 to 18.0%/C) in
increments of 0.1. The Factory Default is 00.0%/F
(00.0%/C).
IGV Maximum Travel Setpt
This screen is displayed only if “Inlet Guide Vane
Output” is “Stepper Motor.”
IGV Maximum Travel: xx,xxx Steps
Press (+)(-) to Change Setting
Range of values is 0 to 60,000 Steps in increments of
100 Steps. Factory Default is 50,000 Steps.
Note: this is also known as the 90 degree vane
setting. You must use the value determined at the
factory. Each unit is unique and must be individually
set. If the factory setting cannot be determined, it
Information Manual35
Page 41
Field Start-up
must be field-supplied by following the procedure in
Trane CVHF-CSB-2B.
Guide Vane Closed Travel Stop
This screen is displayed only if “Inlet Guide Vane
Output” is “Stepper Motor.”
Guide Vane Closed Travel Stop: xx.x %
Press (+)(-) to Change Setting
Range of values is 0 to 100% in increments of 1%.
Factory Default is 0%.
AF Adjustable Speed Control Algorithm
Enable
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Adaptive Speed Control Alg: d/e
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable
(Factory Default).
AF Leaving Water Standard Deviation
AF Pressure Coefficient Constant
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Pressure Coefficient Constant: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 2000 in increments of 1.
Factory Default is 800.
Note: The above value entered is 1.316 X 10^9 / (#
Stages X (Impeller Dia ^2)) all divided by 1000 for the
purpose of display and IPC data transmission (e.g.
the actual range is 0-2,000,000 in increments of
1000). In the chiller module it is multiplied by 1000
again so it is properly scaled.
AF Re-Optimization Factor
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Re-Optimization Factor: x.xx
Press (+)(-) to Change Setting
Range of values is 0.03 to 1.00 in increments of 0.01.
Factory Default is 0.30.
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Leaving Water Standard Deviation: x.x
Press (+)(-) to Change Setting
Range of values is 0.5 to 4.0 in increments of 0.1.
Factory Default is 1.0.
AF Re-Optimization Timer
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Re-Optimization Timer: xxx Hrs
Press (+)(-) to Change Setting
Range of values is 1 to 255 in increments of 1.
Factory Default is 24.
AF Boundary Pressure Coefficient Y
36CVHE-CLD-1A
Page 42
Field Start-up
Intercept
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Boundary PC Y-Intercept: x.xx
Press (+)(-) to Change Setting
Range of values is 0.01 to 2.00 in increments of 0.01.
Factory Default is 0.40. This setpoint is settable from
this screen but also changes as the Adjustable
Frequency Control Algorithm runs. It is similar to a
clock setting where you set it and then it runs from
there.
AF Boundary Pressure Coefficient Y
Intercept Max
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Boundary PC Y-Intercept Maximum: x.xx
Press (+)(-) to Change Setting
Range of values is 0.01 to 2.00 in increments of 0.01.
Factory Default is 2.00.
AF Pressure Error Deadband
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Pressure Error Deadband: x.xxx
Press (+)(-) to Change Setting
Range of values is 0.001 to 1.000 in increments of
0.001. Factory Default is 0.030.
AF Proportional Speed Gain
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Proportional Speed Gain: xxx
Press (+)(-) to Change Setting
Range of values is 1 to 100 in increments of 1.
Factory Default is 50.
Minimum Capacity Timer Enable
Min Capacity Timer: [Status]
Press (+)(-) to Change Setting
The choices for Status are: Enable (Factory Default)
and Disable (Unlmtd Time).
Information Manual37
Page 43
Field Start-up
Note: On Non-Adaptive Frequency chillers this Timer
times out when the chiller is at minimum IGV position
and the Leaving Water Temp is below the CWS. On
Adaptive Frequency chillers this Timer times out
when the chiller is at minimum IGV position or
minimum AF speed and LWT < CWS.
Time Permitted at Minimum Capacity
The following will be displayed only if the Minimum
Capacity Timer setpoint is Enabled.
Time Permitted at Min Cap: xxx Min
Press (+)(-) to Change Setting
Range of values is 1 to 480 minutes in increments of
1 Minute. Factory Default is 30 Minutes.
Evaporator Flow Coefficient
The following is displayed only if the Differential
Water Press Sensor Option is Installed.
Evap Flow Coefficient: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 3000 in increments of 5.
Factory Default is 1000.
Evaporator Fluid Coefficient
The following is displayed only if the Differential
Water Press Sensor Option is Installed.
Evap Fluid Coefficient: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 1000 in increments of 1.
Factory Default is 400.
Note: The desired range for the above is 0.0000 to
0.1000. To put in this kind of range into the CLD, the
fact that it does not start at zero represents a special
case. To minimize special cases it is preferred that a
multiplier of 10,000 be used in the computer that
generates the number.
Condenser Flow Coefficient
The following is displayed only if the Differential
Water Press Sensor Option is Installed.
Cond Flow Coefficient: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 2000 in increments of 5.
Factory Default is 500.
Condenser Flow Equation Exponent
Evaporator Flow Equation Exponent
The following is displayed only if the Differential
Water Press Sensor Option is Installed.
Evap Flow Equation Exponent: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 1000 in increments of 1.
Factory Default is 600.
Note: The desired range for the above is 0.5000 to
0.6000. To put in this kind of range into the CLD, the
fact that it does not start at zero represents a special
case. To minimize special cases it is preferred that a
multiplier of 10,000 and a offset of 5000 be used in
the computer that generates the number.
38CVHE-CLD-1A
The following is displayed only if the Differential
Water Press Sensor Option is Installed.
Cond Flow Equation Exponent: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 1000 in increments of 1.
Factory Default is 600.
Note: The desired range for the above is 0.5000 to
0.6000. To put in this kind of range into the CLD, the
fact that it does not start at zero represents a special
case. To minimize special cases it is preferred that a
multiplier of 10,000 and a offset of 5000 be used in
the computer that generates the number.
Page 44
Field Start-up
Local Atmospheric Pressure
Local Atmospheric Pressure: xx.x psia/kpa
Press (+)(-) to Change Setting
The range of settings is 10 to 16 psig in increments
of 1 or 0.1 psig or kPa depending on the Service
Setup Screen xxx or xxx.x. The Factory Default is
14.7 psig.
Refrigerant Pressure Analog Output
Option
Rfgt Pressure Output Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: % Cond (Factory
Default) and Delta.
Min Delta Pressure Calibration
The following is displayed only if the “Refrigerant
Pressure Analog Output Option” is set to “Delta”.
Note: 6.8948 kPa = 1 psi.
IGV Stroke Time
The following is displayed only if the “Inlet Guide
Vane Output” is set to “Pulsed”.
Inlet Guide Vane Stroke Time: XXX Sec
Press (+)(-) to Change Setting
The range of values is 15 to 100 seconds in
increments of 1 second. Default is 45 seconds.
Low Differential Oil Pressure Cutout
This screen is displayed only if the “Oil Pressure
Protection” is “Transducer”.
Low Diff Oil Press Cutout: XX psid/kpa
Press (+)(-) to Change Setting
The range of values is 9 to 35 psid in increments of 1
psid. Default is 12 psid.
Check Oil Filter Diagnostic
This screen is available only if differential oil pressure
transducer(s) are installed.
Min Delta Press Calib (2 VDC):XXXXPSID/kPa
Press (+)(-) to Change Setting
The range of values is 0-400 psid (0-2758 kPa) in
increments of 1 psid/kPa. Factory Default is 0 psid (0
kPa).
Note: 6.8948 kPa = 1 psi.
Max Delta Pressure Calibration
The following is displayed only if the “Refrigerant
Pressure Analog Output Option” is set to “Delta”.
Max Delta PressCalib (10 VDC):XXXXPSID/kPa
Press (+)(-) to Change Setting
The range of values is 1-400 psid (7-2758 kPa) in
increments of 1 psid/kPa. Factory Default is 30 psid
(207 kPa).
Check Oil Filter Diagnostic: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: Disable (Factory
Default) and Enable.
Check Oil Filter Setpoint
This screen is displayed only if differential oil
pressure transducer(s) are installed and check oil
filter diagnostic is enabled.
Check Oil Filter Setpt: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: 9 to 60 psid in 1 psid
increments. Factory Default is 15 psid.
Information Manual39
Page 45
Field Start-up
Evap Leaving Water Temp Offset
Evap Leaving Water Temp Offset:[setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: -2.0°F to 2.0°F in
0.1°F increments (-/+ 1.1°C in 0.1°C increments).
Factory Default is 0.0°F.
Saturated Evap Rfgt Temp Offset
Saturated Evap Rfgt Temp Offset: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: -2.0°F to 2.0°F in
0.1°F increments (-/+ 1.1°C in 0.1°C increments).
Factory Default is 0.0°F.
Water Pressure Calibration
The following menus is displayed only if the “Diff Wtr
Press Sensor” setpoint is set to “Installed, <= 150
psig.”
This non-zero value shall return to 0.0 psid (kPa)
when the water pressure calibration is completed.
Water Pressure Calibration: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: Auto (Factory
Default) and Manual
If the above menu is set to “Manual,” the following
two menus are displayed.
Measured Evap Diff Wtr Press: X.X PSID/kPa
Press (+)(-) to Change Setting
Possible values is 0 to 25 psid (0 to 172.4 kPa) in 0.1
psid (kPa) increments. Factory Default is 0.0 psid
(kPa).
Measured Cond Diff Wtr Press: X.X PSID/kPa
Press (+)(-) to Change Setting
Possible values is 0 to 25 psid (0 to 172.4 kPa) in 0.1
psid (kPa) increments. Factory Default is 0.0 psid
(kPa).
The value displayed in the preceding two menus
shall normally be 0.0 psid (kPa). When a manual
calibration of the evaporator or condenser water
pressure is desired, the measured differential
pressure shall be entered in the appropriate menu.
40CVHE-CLD-1A
Page 46
Machine Configuration
Machine Configuration
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.
Service Settings - Machine Configuration
The Machine Configuration password is + - + - + <Enter>. If the machine configuration password is
entered, the display goes to the menu defined below.
If a key is not pressed every 10 minutes in this
password protected menu, the display returns to the
Chiller Operating Mode display of the Chiller Report,
and the password must be entered again to return to
this menu.
Machine Configuration Group Heading
Unit Type
Unit Type: [type]
Press (+)(-) to Change Setting
Unit type will default to one of three chiller types. The
default unit type will limit the selections to chillers of
that type.
When the Factory Default is CVHE, possible values
of unit type are: CVHE, CVGF, FastPak watercooled, FastPak air cooled, CVHG, CVHF, CVHB,
CVGE, and CVGG.
Nominal Unit Tons
Nominal Unit Tons: [tons]
Press (+)(-) to Change Setting
Possible values of [tons] are “100” through “1800" in
10 ton increments. Factory Default is 500 tons.
Machine Configuration Group Settings
Press (Next)(Previous) To Continue
This header appears when the headers do not
appear in the Service Settings menu.
Unit Frequency
Unit Frequency: [Freq]
Press (+)(-) to Change Setting
Possible values of Frequency are: 60 Hz (Factory
Default) and 50 Hz.
Refrigerant Type
Refrigerant Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: R11, R123 (Factory
Default), R12, R134a, Water, R22, and R113.
Refrigerant Monitor Type
Refrigerant Monitor Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: None (Factory Default),
Analog interface, and IPC Interface.
Information Manual41
Page 47
Machine Configuration
Starter Type
Starter Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: Undefined, Adaptive
Frequency (AFDA), Y Delta (Factory Default), X Line,
Solid State (C515 Series), Auto Transformer, and
Primary Reactor, AFDB, Solid State (SMCPP)
(Standalone for FastPak only).
Startup Contactor Test - Y-D Starters
Only
This screen shall be displayed only when the starter
type is Y-Delta.
Level 2 ContactorIntegrityTest: [d/e]
Press (+)(-) to Change Setting
Select the Motor Heating Constant using the
following table:
NTON
230-320190-27030 Min
360-500300-42035 Min
560-800470-66040 Min
890-1280740-104045 Min
Motor Heating
Constant60 Hz50 Hz
Current Overload Setting #1
Current Overload Setting #1: xxxxxxxx
Press (+)(-) to Change Setting
The range of values is Decimal 00 through 31.
Factory Default is 00. Factory set per nameplate.
Possible values of [d/e] are: Disable (Factory
Default) and Enable. This test checks for welded
contactors before every start.
Rated Load Amps
Rated Load Amps: xxxx Amps
Press (+)(-) to Change Setting
The range of values is 0-2500 in 1 amp increments.
Factory Default is 500 Amps.
Motor Heating Constant
Motor Heating Constant Setpt: xxx Min
Press (+)(-) to Change Setting
The range of values XXX is 0 to 100 Minutes in 1
Minute increments. Factory Default is 25 Minutes.
Current Overload Setting #2
Current Overload Setting #2: xxxxxxxx
Press (+)(-) to Change Setting
The range of values is Decimal 224 through 255.
Factory Default is 255. For security purposes the
second setting is the 8-bit one's complement of the
first setting above. The current overload settings
establish the running current protection.
Procedure For Selecting Current
Overload Settings for UCP2
1 Determine the Rated Load Amps (RLA) from the
Unit Nameplate.
2 Refer to Table 2 or Table 3 as follows:
Select Table 2 if any of the following conditions are
met:
q the unit has a unit mounted starter with an RLA
less than 936 Amps.
q The unit has a 24" wide control panel; no unit
mounted starter, and RLA less the 936 Amps.
42CVHE-CLD-1A
Page 48
Machine Configuration
q The starter has a single CT/phase wired directly
to the starter module.
Select Table 3 if any of the following conditions are
met:
q The unit has an RLA over 935 Amps.
q The unit has a 38" wide “Starter By Others”
control panel.
q The starter has two CTs/phase wired to the starter
module (greater than 600 volts).
3 Using Table 2 or Table 3 (determined from Step
2), determine the CT Meter Scale Rating based
on the RLA from Step 1.
4 Calculate the CT factor using one of the following
two equations:
If Table 2 was used: CT Factor = (Motor RLA/CT
Meter Scale Rating) x 100
If Table 3 was used: CT Factor = (Motor RLA/CT
Meter Scale Rating) x 139
5 Refer to Table 4 . Determine Current Overload
Settings #1 and #2 based on the CT Factor
calculated in Step 4.
Table 2
CT Factor = (Motor RLA/CT Motor RLA/CT Meter Scale Rating)
X 100
Motor RLACT Part No.Ext
34-50A
51-67A1075A
68-100A01100A
101-134A02150A
135-184A03200A
185-267A04275A
268-334A05400A
335-467A06500A
468-667A07700A
668-935A081000A
x13580253
CT Meter Scale
Rating
0950A
Verify Current Overload Setting #1.
Verify Current Overload Setting #2.
Information Manual43
Page 49
Machine Configuration
Table 3
CT Factor = (Motor RLA/CT Meter Scale Rating) X 139
Line CT Part
No.Ext
X13580272-0150:5X1 to X238.0 – 11.916.7
X13580271-01100:548.0 – 72.0100
X13580048150:572.0 – 86.3150
X13580047-011800:5X1 to X2864.0 – 1007.91800
Line CT
Ratio
-0275:5218.0 – 23.937.5
-0150:5
-0275:536.0 – 47.975
180:5X1 to X386.4 – 95.9180
200:5X1 to X496.0 – 119.9200
-02250:5X1 to X2120.0 – 143.9250
300:5X1 to X3144.0 – 167.9300
350:5X1 to X4168.0 – 191.9350
-03400:5X1 to X2192.0 – 239.9 400
500:5X1 to X3240.0 – 287.9500
600:5X1 to X4288.0 – 335.9600
-04700:5X1 to X2336.0 – 383.9700
800:5X1 to X3384.0 – 479.9800
1000:5X1 to X4480.0 – 575.91000
-051200:5X1 to X2576.0 – 719.91200
1500:5X1 to X3720.0 – 863.91500
2100:5X1 to X31008.0 – 1199.92100
2500:5X1 to X41200.0 – 18002500
-021000:5X1 to X2480.0 – 575.91000
1200:5X1 to X3576.0 – 719.91200
1500:5X2 to X4720.0 – 863.91500
CT Ter.
Conn
No. of Prim.
TurnsRLA Ranges
212.0 – 17.925.0
24.0 – 35.950
1
Meter
Scale
44CVHE-CLD-1A
Page 50
Table 4
CT Factor, Current Overload Settings #1 and #2
Machine Configuration
Current
CT
Factor
660025577112448822233
670125478122438923232
680225379142419024231
690325280152409125230
700425181162399225230
710624982172389326229
720624883182379427228
730724884192369528227
740824785202359628227
750924686212349729226
761024587222339830225
Overload
Setting #1
Current
Overload
Setting #2
CT
Factor
Current
Overload
Setting #1
Maximum Acceleration Timer #1
Current
Overload
Setting #2
CT
Factor
9930225
The range of values is 191 to 249 Sec. Factory
Current
Overload
Setting #1
Default is 228 Seconds. For security purposes the
second setting is the 8-bit one's complement of the
Maximum Accel Timer Setpt #1: xx Sec
Press (+)(-) to Change Setting
Timer #1 setting above. Both the Maximum Accel.
Timers and the Overload Settings are not adjustable
from either the Remote CLD or Tracer or any other
Remote/External Device.
The range of values is 6 to 64 seconds. Factory
default is 27 seconds.
Current
Overload
Setting #2
Starter Type
UndefinedContact Factory
Variable Speed20
Y-Delta27 (Factory Default)
X-Line6
Sold State20
Auto-transformer16
Primary Reactor11
Recommended Max. Accel.
Timer #1 Setting
Maximum Acceleration Timer #2
The maximum acceleration timers establish the
starting overcurrent protection.
Maximum Accel Timer Setpt #2: xx Sec
Press (+)(-) to Change Setting
Hot Water Control Option
This screen does not appear if compressor power
source is “Engine/Generator.”
Hot Water Control Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Heatsink Start Inhibit Temperature
Setpoint (FastPak)
Heatsink Start Inhibit Temp: xxx.x f/c
Press <+> <-> To Change Setting
The range of values shall be 100.0 to 200.0 °F (37.8
to 93.3 °C) in increments of .1°F/°C. Default shall be
100 °F (93.3 °C).
Information Manual45
Page 51
Machine Configuration
External Chilled Water Setpoint Option
External Chilled Wtr Setpoint:[Status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
External Current Limit Setpoint Option
External Current Limit Setpt:[Status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
External Hot Water Setpoint Option
External Hot Water Setpoint: [Status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Acceleration Time Out Action
Motor Winding RTD Type
Motor Winding RTD Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: 75 Ohm at 75°F
(Factory Default) and 100 Ohm at 0°C
High Pressure Cutout Setting
High Pressure Cutout Setting:xxxx Psig/kPa
Press (+)(-) to Change Setting
The range of values shall be -5-500 psig (350-3447
kPa) in increments of 5 psig/kPa. Factory Default is
15 psig (103 kPa) from -5 to 5 psig in increments of
1.
Line Voltage Sensing Option
Line Voltage Sensing Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Unit Line Voltage
Acceleration Time Out Action: [action]
Press (+)(-) to Change Setting
Possible values for “action” include: Shutdown
(Factory Default) and Transition. Transition results in
an IFW diagnostic.
Motor Over Temperature Protection
Motor Temp Protection: [input]
Press <+> < - > to Change Setting
Possible value of [input] are: 3 Winding Sensors,
MTC Switch. Factory default is 3 Winding Sensors
46CVHE-CLD-1A
This screen will not appear if the Line Voltage
Sensing Option is not installed.
Unit Line Voltage: [volt]
Press (+)(-) to Change Setting
Possible values of [volt] are “180” through “6600” in 5
volt increments. Factory Default is 460 volts.
Page 52
Machine Configuration
Auxiliary Condenser Option
Auxiliary Condenser Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Heat Recovery Option
Heat Recovery Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Hot Gas Bypass Option
Condenser Pressure Sensor Option
Condenser Press Sensor Option:[status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Bearing Temperature Sensors Option
Bearing Temp Sensors Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Discharge Temperature Sensor Option
Hot Gas Bypass Option : [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Free Cooling Option
Inlet Guide Vane Output
Has been Set to Stepper Motor
Free Cooling Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Discharge Temp Sensor Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Ice Building Option
Ice Building Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Differential Water Press Sensing Option
Diff Wtr Press Sensor Opt: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed, <= 150 psig
(1035 kPa), Installed, > 150 psig (1035 kPa), and Not
Installed (Factory Default).
Information Manual47
Page 53
Machine Configuration
This option screen applies to both the Evap and
Cond differential water pressure sensors for both
systems less than or equal to 150 psig (Sensors at
the Chiller Module) and systems greater than 150
psig (Sensors at the Options Module).
External Analog Input Type Selection,
4-20 ma/2-10 VDC
External Setpoint Inputs: [type]
Press (+)(-) to Change Setting
Possible values for status are: 4-20ma (Factory
Default) and 2-10 VDC.
Tracer Option
Tracer Option:
[status]
Press (+)(-) to Change Setting
Duplex Control Module (DCM) Option
DCM Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
IGV Output Type
Inlet Guide Vane Output: [Y]
Press (+)(-) to Change Setting
Possible values for Y are: Stepper Motor (Factory
Default) and Pulsed.
If Inlet Guide Vane Output is set to Pulsed and the
Hot Gas Bypass Option is currently set to Installed,
the Hot Gas Bypass Option will be set to Not
Installed and the following will be displayed for 3 sec
to indicate the change.
Possible values for status are: Installed and Not
Installed (Factory Default).
TCI Option
TCI Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Printer Option
Printer Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not
Installed (Factory Default).
Hot Gas Bypass Option
Has Been Set to Not Installed
Oil Pressure Protection
Oil Pressure Protection:
[status]
Press (+)(-) to Change Setting
Possible values for [status] are: Transducer (Factory
Default), and Diff Switch, Xducer & Switch.
Programmable Analog Output
Program Analog Output: [Output]
Press <+> <-> To Change Setting
Possible values of [Output] are:
Not Used% Cond Pres
% RLARefrig Diff Pres
48CVHE-CLD-1A
Page 54
Machine Configuration
Current Transducer at 100% RLA =
Machine LRA
Factory Default is % RLA.
Programmable Relay Outputs
The following represents three menu items and is
repeated for [N] = 1, 2, or 3.
Program Relay [N]: [Relay]
Press <+> <-> To Change Setting
Possible values of [Relay] are:
Not UsedLimit Warning
Comp RunningIce Making
MMR AlarmHead Relief Request
MAR AlarmTracer Controlled
MMR + MAR AlarmMax Capacity
Factory Default for
Current Transducer at 100% RLA
The following will only be displayed if Current
Transducer is set to “Other”.
Current Xducer at 100% RLA: XX.X VDC
Press <+> <-> To Change Setting
Range of values is -10.0 to -5.0 VDC in increments of
0.1 VDC
Note: Calculate setpoint as follows:
--------------------------------------X10–()
CT Span
Compressor Power Source
Cprsr Power Source: [status]
Press (+)(-) to Change Setting
[N] = 1 is MMR + MAR Alarm.
[N] = 2 is Comp Running.
[N] = 3 is Not Used.
Current Transducer Setpoint
The following will only be displayed if starter type is
set to “Stand Alone - No Starter Module”.
Current Xducer: [Setting]
Press <+> <-> To Change Setting
Possible values for [Setting] are: Cutler Hammer;
Other Factory Default is “Cutler Hammer”
Note: Select “Cutler Hammer” if starter has an A-1
module, otherwise select “Other”.
Possible settings for [status] are: Utility (Factory
Default) and Engine/Generator.
Information Manual49
Page 55
Refrigerant Monitor Settings Group
Refrigerant Monitor Settings Group
The Refrigerant Monitor Settings password is - - + + -
- <Enter>. If the refrigerant monitor settings
password is entered, the display goes to the menu
defined below. If a key is not pressed every 10
minutes in this password protected menu, the display
returns to the Chiller Operating Mode display of the
Chiller Report, and the password must be entered
again to return to this menu.
Refrigerant Monitor Settings Group
Heading
Refrigerant Monitor Group Settings
Press (Next)(Previous) To Continue
Alarm Level 1
Alarm Level 1: XXXX PPM [Rfgt Type]
Press (+)(-) to Change Setting
Refrigerant Audible Alarm
Refrigerant Audible Alarm: [Setting]
Press (+)(-) to Change Setting
Possible values are: Disable, Alarm 1, Alarm 2,
Alarm 3.
Trouble Audible Alarm
Trouble Audible Alarm:
[Status]
Press (+)(-) to Change Setting
Possible values of status are: Disable, Enable.
Alarm 1 Latching Status
Range of values are 3 to Alarm Level 2 minus 1 in
increments of 1. The maximum value for R-123 is 30.
Alarm Level 2
Alarm Level 2: XXXX PPM [Rfgt Type]
Press (+)(-) to Change Setting
Range of values are Alarm Level 1 plus 1 to Alarm
Level 3 minus 1 in increments of 1.
Alarm Level 3
Alarm Level 3: XXXX PPM [Rfgt Type]
Press (+)(-) to Change Setting
Range of values are Alarm Level 2 plus 1 to 1000 in
increments of 1.
Alarm 1 Latching Status: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Latching, NonLatching.
Alarm 2 Latching Status
Alarm 2 Latching Status: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Latching, NonLatching.
50CVHE-CLD-1A
Page 56
Refrigerant Monitor Settings Group
Alarm 3 Latching Status
Alarm 3 Latching Status: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Latching, NonLatching.
Channel Scanner
This item shall be displayed only when the refrigerant
monitor mode is Warmup.
Channel Scanner: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Installed, Not Installed.
Scanner Channel 1
Scanner Channel 1: [Status]
Press (+)(-) to Change Setting
Scanner Channel 4
Scanner Channel 4: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Active, Inactive.
Scanner Dwell Threshold
Scanner Dwell Threshold: XX %
Press (+)(-) to Change Setting
The range of values for Scanner Dwell Threshold is
30 to 70 in increments of 1.
Auxiliary Input
Auxiliary Input: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Installed, Not Installed.
Possible values of status are: Active, Inactive.
Scanner Channel 2
Scanner Channel 2: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Active, Inactive.
Scanner Channel 3
Scanner Channel 3: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Active, Inactive.
Auxiliary Input Alarm
Auxiliary Input Alarm: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Enable, Disable.
Auxiliary Input Alarm Level: XX.X mA
Press (+)(-) to Change Setting
Range of values is 4.0 to 20.0 in increments of 0.1.
Auxiliary InputAlarm Direction:[Direction]
Press (+)(-) to Change Setting
Possible values of Direction are: Above, Below.
Auxiliary Input Audible Alarm:[Status]
Press (+)(-) to Change Setting
Possible values of Status are: Disable, Enable.
Information Manual51
Page 57
Refrigerant Monitor Settings Group
Analog Output Range
Analog Output Range: [Range] PPM
Press (+)(-) to Change Setting
52CVHE-CLD-1A
Page 58
Refrigerant Monitor Calibration
Refrigerant Monitor Calibration
The Refrigerant Monitor Calibration password is - + -
- + + <Enter> for the field calibration menu. If a
refrigerant monitor calibration password is entered,
the display goes to the menu items defined below. If
a key is not pressed every 20 minutes in this
password protected menu, the display returns to the
Chiller Operating Mode display of the Chiller Report,
and a refrigerant monitor calibration password must
be entered again to return to this menu.
Refrigerant Monitor Settings Group
Heading
This header is displayed if the field calibration
password was entered.
Rfgt Monitor Field Calibration Group
Press (Next)(Previous) To Continue
This header is displayed if the factory calibration
password was entered.
Refrigerant Zero Calibration
Refrigerant Zero Calibration
(Enter) to Start, (Next) to Continue
If <Next> is pressed the following refrigerant zero
calibration screens are skipped. If <Enter> is pressed
the following screens are displayed to permit
refrigerant zero calibration.
Starting The Calibration Procedure
Please Wait
If the refrigerant monitor is unable to calibrate, the
following item is displayed.
Unable to Calibrate
Otherwise, continue with the following screens.
Rfgt Monitor Factory Calibration Group
Press (Next)(Previous) To Continue
Refrigerant Monitor Mode
Refrigerant Monitor Mode: [Mode]
Scanner Channel X XXXX PPM [Rfgt Type]
This item is displayed if the Channel Scanner is not
installed.
Refrigerant Monitor Mode: [Mode]
XXXX PPM [Rfgt Type]
Connect Refrigerant Zero Gas
(Next) To Continue, (Cancel) To Exit
Open Gas Sample Valve
(Next) To Continue, (Cancel) To Exit
XXXX PPM [Rfgt Type]
(Enter) To Adjust Conc, (Cancel) to Exit
Locking The Reading
Please Wait
Information Manual53
Page 59
Refrigerant Monitor Calibration
If the refrigerant monitor is unable to calibrate, the
following item is displayed.
Unable to Calibrate
Otherwise, the following screens continue.
Refrigerant Zero Calibration XXXX
Press (Enter)(Cancel)(+)(-) To Continue
Starting The Calibration Procedure
Please Wait
This item is followed by one of the following two
items.
Successful Calibration
If the refrigerant monitor is unable to calibrate, the
following item is displayed.
Unable to Calibrate
Otherwise, the following screens continue.
Connect Refrigerant Span Gas
(Next) To Continue, (Cancel) To Exit
Open Gas Sample Valve
(Next) To Continue, (Cancel) To Exit
XXXX PPM [Rfgt Type]
(Enter) To Adjust Conc, (Cancel) to Exit
Calibration Failed
(Enter) To Retry, (Cancel) To Exit
If the <Enter> key is pressed, the display will return
to the second menu item above. If the <Cancel> key
is pressed, the display continues to the next display.
Refrigerant Span Calibration
Refrigerant Span Calibration
(Enter) to Start, (Next) to Continue
If <Next> is pressed the following refrigerant span
calibration screens are skipped. If <Enter> is pressed
the following screens are displayed to permit
refrigerant span calibration.
Starting The Calibration Procedure
Please Wait
Locking The Reading
Please Wait
If the refrigerant monitor is unable to calibrate, the
following item is displayed.
Unable to Calibrate
Otherwise, the following screens continue.
Refrigerant Span Calibration XXXX
Press (Enter)(Cancel)(+)(-) To Continue
Starting The Calibration Procedure
Please Wait
54CVHE-CLD-1A
Page 60
This item is followed by one of the following two
items.
Successful Calibration
Calibration Failed
(Enter) To Retry, (Cancel) To Exit
If the <Enter> key is pressed, the display returns to
the second menu item above. If the <Cancel> key is
pressed, the display continues to the next display.
Refrigerant Monitor Calibration
Information Manual55
Page 61
Service Tests Group
Service Tests Group
Important! FACTORY DEFAULT SETTINGS: Menu
items that are programmable using the keypad may
have a selectable choice that is listed as Factory
Default. This Factory Default setting is the software
default that is initially factory-programmed for a new
module assembly and may NOT be the correct
setting for a specific operating chiller. Always review
all settings when any module is replaced to verify
that the settings agree with the desired settings that
were selected at initial startup or programmed at the
factory.
Service Tools Group Password Request
Pswd Reqd to Access Service ToolsGroup
Please Enter Password
The Service Tools Password is + + - - + + <Enter>.
Successfully entering the password sends you to the
Service Tools Group Heading Screen as defined
below.
Pressing the <Next> and Increment keys
simultaneously while the Service Tools Group
Password Request screen is displayed will send you
to the CLD-Chiller IPC communications screen
shown below. This screen can be used as a
debugging tool when CLD-Chiller IPC
communications are suspect. The first line on the
comm screen indicates which Chiller packets the
CLD is checking. The second line on the comm
screen indicates how many times in a 15 second
interval the particular packet was received by the
CLD. If a packet is received more than 9 times in the
interval, a “+” is displayed. The counters are reset to
0 every 15 seconds. Hitting any key while on this
screen will cause an exit.
Packet#:2 3 4 5 6 7 8 9 10 11 12 14 15
Received:x x x x x x x x x x x x x
If any item in the Service Tools Group is in manual
override, the alarm LED will be on and non-flashing.
The following table contains the Service Tools
setpoints which affect the alarm light.To turn the
alarm light off (from an on and non-flashing state), all
the conditions applicable to the unit type must be
satisfied.
Unit Type:Function / Setpoint:Condition to Turn Off
manual Alarm LED:
ALL“Chilled Water Pump:”Auto
ALL except CVAE“Condenser Water Pump:”Auto
CTV“Oil Pump:”Auto
CTV with IGV Output set to
Stepper Motor.
CTV with HGBP installed:“HGBP Valve Control Is:”Auto
CTV with IGV Output set to
Pulsed.
CTV with AF starter:“AF Manual Speed Control:”Disable
56CVHE-CLD-1A
“Vane Control:” Auto
“IGV Control Is:”Auto
Page 62
Service Tests Group
Service Tools Group Heading
Service Tests & Overrides
Press (Next)(Previous) To Continue
This header appears when the headers do not
appear in the Service Settings menu.
Chilled Water Pump
Chilled Water Pump: [Status]
Press (+)(-) to Change Setting
Possible values for Status are: Auto (Factory Default)
and On.
Chilled Water Flow Switch Status
This screen displays the status of the chilled water
flow switch status at the input to the UCM.
Condenser Water Pump
Condenser Water Pump: [Status]
[y]
Possible values for Status are: Auto (Factory Default)
and On.
Possible values for [y] are: Press (+)(-) to Change
Setting.
Condenser Water Flow Switch Status
This screen displays the status of the condenser
water flow switch status at the input to the UCM.
Condenser Water Flow Switch Status:
[y]
Possible values for [y] are: Flow Switch is Open/No
Flow and Flow Switch is Closed/Flow.
Chilled Water Flow Switch Status:
[y]
Possible values for [y] are: Flow Switch is Open/No
Flow and Flow Switch is Closed/Flow.
Evaporator Differential Water Pressure
The following will be displayed only if the Differential
Water Pressure Sensor Option is Installed.
Evap Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Evaporator Entering/Leaving Water
Pressure
The following will be displayed only if the low
pressure (< or = to 150 psig) Differential Water
Pressure Sensor Option is Installed.
Condenser Differential Water Pressure
The following will be displayed only if the Differential
Water Pressure Sensor Option is Installed.
Cond Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Condenser Entering/Leaving Water
Pressure
The following will be displayed only if the low
pressure (< or = to 150 psig) Differential Water
Pressure Sensor Option is Installed.
Cond Entering Water Pressure:xx.x psid/kPa
Cond Leaving Water Pressure: xx.x psid/kPa
Evap Entering Water Pressure:xx.x psid/kPa
Evap Leaving Water Pressure: xx.x psid/kPa
Information Manual57
Page 63
Service Tests Group
Starter Dry Run
Use the following screen when [xx] = “Disabled”.
Starter Dry Run: [xx]
Press +/- to Change
Use the following screen when [xx] Not equal to
“Disabled”.
Starter Dry Run: [xx]
(+)(-) (Enter): Trans Compl Inp: [y]
Possible values of [xx] are: Disabled (Factory
Default), Shorting Relay On, Run Relay On, Start
Relay On, Transition Relay On, and Start and Run
Relays On.
Possible values of [y] are:
Closed This denotes that the Transition Complete
input is seeing a contact closure.
Open This denotes that the Transition Complete
input is seeing a contact open.
If the unit is not in the local Stop mode the following
is displayed.
Starter Dry Run: Disabled
Unit Must Be In Local Stop To Execute
Vane Control Status/Vane Position
Commands
The following screens will be displayed only when
the “Inlet Guide Vane Output” is set to “Stepper
Motor”.
Vane Control Is: [Status]
Press (+)(-) to Change Setting
The possible values of [status] are “Auto” or
“Manual”. Factory Default is “Auto”.
If the vane control status is “Auto” the following is
displayed:
Inlet Guide Vane Position: xxx.x %Open
[Limit mode]
If the vane control status is “Manual” the following is
displayed. When the Vane Control Status is
transitioned from “Auto” to “Manual”, the manual
target is initialized to the current vane position.
Vane Pos xxx.x % Target xxx.x % Open
LWT = xx.x [limit mode]
The possible values of limit mode are: “Current
Limit”, “Condenser Limit”, "Evap Limit”, and “(+) (-)
and <Enter>”.
Vane Position
Oil Pump Status
This screen is displayed only if “Oil Pressure
Protection” is set to “Transducer” or “Xducer &
Switch.”
Oil Pump: [Status]
Differential Oil Pressure: xx.x psid
Possible values for Status are: Auto (Factory Default)
and On.
Differential Oil Pressure is not a setpoint but a status
display.
58CVHE-CLD-1A
The following screen will be displayed only when the
“Inlet Guide Vane Output” is set to “Stepper Motor”.
Inlet Guide Vane Position: xxxxx steps
Inlet Guide Vane Position:xx.x degrees
HGBP Valve Control Status/Manual Open
and Close Commands
If HGBP is installed in the unit, the following screen is
displayed:
HGBP Valve Control Is: [Status]
LWT = xx.x f/c [Y]
Page 64
Service Tests Group
The possible values of [status] are “Auto”, “Hold”,
“Open”, or “Close”. Factory Default is “Auto”.
The possible values of Y are: “Current Limit”,
“Condenser Limit”, “Evap Limit”, and (+)-) and
<Enter>”. The latter is displayed when there are no
limits operating.
HGBP Valve Manual Opening/Closing
Duty Cycle
If HGBP is installed in the unit, the following screen is
displayed:
Manual Opening/Closing Duty Cycle: xx%
Press (+)(-) to Change Setting
Range of values is 0 to 50% in increments of 1%.
Factory Default is 30%.
Vane Control Status/Manual Load and
Unload Commands
Range of values is 0 to 50% in increments of 1%.
Factory Default is 30%.
Condenser Fan 3 [Status]
Fan 1 [x] Fan 2 [y] Fan 3 [z].......
Possible values for Status are: Auto (Factory Default)
and On
Fan 1, Fan 2, and Fan 3 are not setpoints but a
status display.
Possible values for x,y,z are Auto/On and On/Off.
Note: status display (2nd line) does not appear while
in free cooling mode.
AF Manual Speed Control - CVHE/F/G
Only
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
The following screen will be displayed only when the
“Inlet Guide Vane Output” is set to “Pulsed”.
IGV Control Is: [Status]
LWT = xx.x f/c [Y]
The possible values of [status] are “Auto”, “Hold”,
“Load”, or “Unload”. Factory Default is “Auto”.
The possible values of Y are: “Current Limit”,
“Condenser Limit”, “Evap Limit”, and “(+)(-) and
<Enter>”. The latter is displayed when there are no
limits operating.
Manual Loading/Unloading Duty Cycle
The following screen will be displayed only when the
“Inlet Guide Vane Output” is set to “Pulsed”.
Manual Loading/Unloading Duty Cycle: xx%
Press (+)(-) to Change Setting
AF Manual Speed Control: [d/e]
Press (+)(-) to Change Setting
The possible values of [d/e] are: Disable (Factory
Default) and Enable.
AF Compressor Speed Command CVHE/F/G Only
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB”, or the Compressor
Power Source is Engine/Generator, and AF Manual
Speed Control is Enabled.
AF Compressor Speed Command: xxxx RPM
Press (+)(-) to Change Setting
Range of values is 2520 to 3600 RPM for “Adaptive
Frequency” Starter Type (2280 to 3600 RPM for
“AFDB” Starter Type) in increments of 1 RPM.
Factory Default is 3600 RPM.
Information Manual59
Page 65
Service Tests Group
AF Compressor Speed Command CVHE/F/G Only
The following is displayed only if the Starter Type is
“Adaptive Frequency” or AFDB” or the Compressor
Power Source is Engine/Generator.
AF Compressor Speed Command: xx.x Hz
AF Compressor Speed Command:xxxx.x RPM
Note This is a Report only for Troubleshooting
purposes.
AF Boundary Pressure Coefficient/AF
Pressure Coefficient - CVHE/F/G Only
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Boundary Press Coefficient: x.xxx
AF Pressure Coefficient: x.xxx
Module Software Revision Levels
Press (Enter) To Display Software
Revision Levels Or (Next) To Continue
If <Enter> is selected the following screen can be
displayed 5 times with 5 different pairs of modules.
[Module 1:] [Revision Level]
[Module 2:] [Revision Level]
Module 1/2 will be one of the following: Chiller,
Circuit, Starter, Options, Stepper 1, Stepper 2, TCI,
Purge, LCLD, RCLD, I/O, Refrigerant Monitor,
Scorpio, DCM.
Revision Level will either be an integer representing
the software version number of the particular module
or occurrence of a diagnostic, the display will
automatically go to this menu and display certain
messages as explained in the next section
“Diagnostics Menu.”
Note This is a Report only for Troubleshooting
purposes.
AF Re-Optimization Timer Time
Remaining- CVHE/F/G Only
The following is displayed only if the Starter Type is
“Adaptive Frequency” or “AFDB” or the Compressor
Power Source is Engine/Generator.
AF Re-Optimization Time Remaining:x.xx Hrs
Press (+)(-) to Change Setting
Note This is a Report only for Troubleshooting
purposes.
60CVHE-CLD-1A
Page 66
Diagnostics Menu
Strike Diagnostic Key
Diagnostics Menu
The Diagnostics Group is where all diagnostics, both
historical and active are presented. The group also
contains the facility to clear active diagnostics,
historic diagnostics, and purge diagnostics as
individual groups. To clearly annunciate the
Diagnostic Occurs
(IFW,MAR,MMR)
occurrence of a diagnostic, the display will
automatically go to this menu and display certain
messages as explained below. The following
illustration gives an overview of how the diagnostic
key and screens below it work.
Header Screens
New Diagnostic Screen
Operating Mode Screen for the
last diagnostic
Set of Screens for the 1st Diag.
Set of Screens for the nth Diag.
Diagnostics Group Heading
Active & Historic Diagnostics
Press (Next)(Previous) To Continue
Menu Settings Password
If the Menu Settings Password is Enabled in the
Service Setup Group, following each setting group
heading the following will be displayed:
Settings In This Menu Are [status]
[password message]
Screen(s) to Clear Diagnostics
Likewise, if the Menu Settings Password is Disabled
in the Service Setup Group, the above screen will not
appear.
The possible values for status are “Locked” or
“Unlocked”. If the password status is locked, the
password message will be “Enter Password to
Unlock”. The user will then depress “-+-+-+” followed
by the <Enter> key. The password keystrokes will be
echoed to the screen as a visual aide. The last six
keystrokes represent the current password, and up
to twenty keystrokes can be entered. An incorrect
password, or the twenty-first keystroke will result in
the password message “Invalid Password”.
If the password status is unlocked, the password
message will be “Press (Enter) to Lock”. Any attempt
to change the setting will result in the message
“Setting is Locked”. The password, once entered, will
remain valid until canceled.
Information Manual61
Page 67
Diagnostics Menu
Diagnostics and Annunciation
If there are no diagnostics present, only the following
screen will be displayed under the Diagnostics Group
heading screen.
No Diagnostics Present
Press (Next) (Previous) To Continue
If there are any diagnostics present, the following 3
screens are displayed sequentially when the <Next>
key is pressed. The first screen is:
Diagnostic Report Follows
Press (Next) For More
The second screen is:
Press (Enter) To Display Operating Mode
At Time Of LastDiagnostic or(Next)For More
The third screen is the chiller operating mode display
that was present at the time that the most recent
diagnostic occurred.
If there are one or more diagnostics present, the
following displays will be inserted into the display
sequence. Diagnostics will be listed in order of
occurrence from newest to oldest. Diagnostics will be
displayed on 2 screens. The two screens will vary
slightly depending on whether the diagnostic is active
or historic.
The first active diagnostic screen will be:
MAR diagnostics)
The second active diagnostic display screen will
contain the diagnostic sequence number, a time and
date stamp, and a help message suggesting possible
service procedures. The second active diagnostic
display screen will be:
[sn] occurred at HH:MM xm Mon xx, 199x
[help message]
The time will be displayed as xx:xx am/pm.
The date will be displayed as month - date- year.
The month will use a standard 3-letter abbreviation.
The year will not be abbreviated.
Depressing the next key will advance the display to
the next diagnostic in the sequence.
The first historic diagnostic screen will be:
[sequence number] [Diagnostic]
Historic Only, Press (Next) For More
The definitions of diagnostic and sequence number
are the same as for the active diagnostic messages.
If <Next> is pressed the second historic diagnostic
screen is displayed. The second historic diagnostic
screen will be:
[sn] occurred at HH:MM xm Mon xx, 199x
Historic Only, Reset At End Of Diag Menu
Up to 20 diagnostics will be displayed.
[sequence number] [diagnostic]
(Next) [diagnostic type]
The sequence number will run from 1 through n (n <=
20) and number the diagnostics sequentially where
the most recent diagnostic is sequence number [01].
The possible replacements for “diagnostic type” are:
Clearing Diagnostics
At the end of the diagnostic menu, there will be 4
screens that allow the user to Clear/Reset the
different diagnostic groups.
If any active diagnostics are present, the following
screen will be displayed:
Warning Only - Reset Not Reqd (Applies to all
IFW diagnostics.)
Unit Shutdown - Reset Reqd (Applies to all MMR
diagnostics)
Press (Enter) To Clr Active Diagnostics
And Shutdown / Reset System
Unit Shutdown - Automatic Reset (Applies to all
62CVHE-CLD-1A
Page 68
Diagnostics Menu
If the <Enter> key is pressed, the following message
is displayed for 2 seconds:
Active Diagnostics Have Been Cleared
System Is Resetting
The display will be reset to the operating mode
screen of the chiller report after this message clears.
If any historic diagnostics are present, the following
screen will be displayed:
Press (Enter) To
Clear Historic Diagnostics
If the <Enter> key is pressed, the following message
is displayed for 4 seconds:
Historic Diagnostics Have Been Cleared
Diagnostic Report Is Being Reset
The display will be reset to the top of the Diagnostic
Menu after this message clears.
If any purge diagnostics are present, the following
screen will be displayed:
Note: Pressing <+> will silence the audible alarm.
The IPC refrigerant monitor will cause all the
refrigerant monitor alarms (diagnostics) to become
non-latching for approximately 7.5 seconds. This
allows any latching alarms to clear if the trip condition
has been removed. This clearing function differs from
the balance of UCP2 in that the balance of UCP2
diagnostics are cleared on reset and reestablished if
the trip condition is still present.
If the <+> key is pressed, the following message is
displayed for 4 seconds:
Silencing Rfgt Mon Audible Alarm
Clearing Nonactive Rfgt Alarms
New Diagnostic Display
When a new diagnostic is sensed by the system, the
display will reset to the diagnostic menu. A “onetime” screen will be displayed to inform the user that
a new diagnostic has been detected. This screen will
vary depending on the type of diagnostic detected.
The two major categories of diagnostics are those
which are informational only, and those which have
resulted in machine shutdown.
If the diagnostic is an MMR/MAR, the screen will be:
Press (Enter) To
Clear Purge Diagnostics
If the <Enter> key is pressed, the following message
*** A MACHINE SHUTDOWN HAS OCCURRED ***
Press (Next) For More
Otherwise, the screen will be:
is displayed for 4 seconds:
A New Warning Has Been Detected
Purge Diagnostics Have Been Cleared
Press (Next) For More
Diagnostic Report Is Being Reset
This screen will be inserted into the diagnostic menu
The display will be reset to the top of the Diagnostic
Menu after this message clears.
directly after the “Diagnostic Report Follows” screen.
Pressing <Next> will therefore take the user to the
“Press (Next) to display operating mode at time of
If any IPC refrigerant monitor diagnostics are
present, the following screen will be displayed:
last diagnostic” screen. If <Next>or <Previous> is
pressed, this screen will no longer be in the display
sequence.
Press (+) To
Silence Rfgt Mon Audible Alarm
Information Manual63
Page 69
Diagnostics Menu
Diagnostics
In the table following, a “Latching” diagnostic is a
condition which will cause the machine or a portion of
Diagnostic Types And Action
MMR = Machine Shutdown - Manual Reset
MAR = Machine Shutdown - Auto Reset
the machine as noted to shut down and will require a
manual reset to restore operation. A diagnostic that
is non-latching is reset automatically when the
IFW = Information Warning - May affect machine
operation; lowest level of diagnostic
condition causing the diagnostic goes away. A nonlatching diagnostic will shut down the machine or a
part of the machine if so indicated. If a diagnostic is
information only, no machine action is taken.
Unless otherwise stated, all active diagnostics will be
lost on loss of power.
Remotely Resettable Diagnostics:
Except for the following, all diagnostics can be reset
remotely from either the Remote Clear Language
Display, the Tracer, or the External Diagnostic Reset
input at the Options Module. The following
diagnostics shall only be resettable ONLY at the
Local Clear Language Display, e.g. with the operator
standing at the unit.
Table 5
Can Be
DIAGNOSTIC DESCRIPTION
Starter Contactor Interrupt FailureMMRNo
Low Evap Rfgt PressureMMRNo
Phase LossMMRNo
Phase ReversalMMRNo
High Bearing #1 TempMMRNoHigh Motor Temp Position #3MMRNo
High Bearing #2 TempMMRNoSevere Phase UnbalanceMMRNo
Current OverloadMMRNoStarter Fault Type IMMRNo
Cprsr did not Accelerate: ShutdownMMRNo
Starter did not TransitionMMRNoStarter Fault Type IIMMRNo
High Pressure Cutout TrippedMMRNoStarter Fault Type IIIMMRNo
Low Evap Rfgt Temp.MMRNoCprsr did not Accelerate FullyMMRNo
High Motor Temp Position #1MMRNoTransition Complete Input OpenedMMRNo
High Motor Temp Position #2MMRNoAt Speed Input OpenedMMRNo
Diag
Type
Remotely
ResetDIAGNOSTIC DESCRIPTION
Diag
Type
Can Be
Remotely
Reset
64CVHE-CLD-1A
Page 70
Table 6
Diagnostic Table
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Adapt Freq Drive Fault Relay
Open
Diag
Type
MMRStarterAll Start
Module
that
Called
Diag.
Diag.
Active
Modes
and Run
CAUSEHelp Message
The Adaptive Frequency Drive fault relay is
open.
Mode
At Speed Input ShortedMMRStarterPre-Starta. Using either a Solid State Starter or an
Adaptive Frequency Drive, the Up to Speed/At
Speed input was found to be shorted before the
compressor was started.
b. Applies only to Solid State Starters and
Adaptive Frequency Drives.
At Speed Input OpenedMMRStarterAll
Running
Modes
a. The At Speed input was found to be opened
with the compressor motor running after
successfully obtaining at speed condition.
b. Applies only to Solid State Starters.
Aux/Ht Rcvry Ent Water Temp
Sensor
Aux/Ht Rcvry Lvg Water Temp
Sensor
IFWOptionsAllOpen or shorted and Heat Recovery is installed
(at the CLD).
IFWOptionsAllOpen or shorted and Heat Recovery is installed
(at the CLD).
Bearing Temp Sensor #1MMRStepperAllOpen or Short, only if this option is enabled at
the Human Interface.
Bearing Temp Sensor #2MMRStepperAllOpen or Short, only if this option is enabled at
the Human Interface.
Check ClockIFWChillerAllOn loss of power the clock does not keep time, if
there is an extended power loss (greater than 15
seconds) this diag. is also generated to alert the
operator to check the clock.
Check Oil FilterIFWChillerAll
Running
Modes
a. The differential oil pressure fell below the
Check Oil Filter Setpoint for 1000 psid-seconds
and the Check Oil Filter Diagnostic setpoint is
enabled.
b. This diagnostic shall not be active for 15
minutes after the compressor is started.
c. This IFW diagnostic will automatically reset
when the differential oil pressure rise above the
Check Oil Filter Setpoint for 1000 psid-seconds
or the compressor is not running.
See Adaptive
Frequency Drive
Service Bulletin,
check for an
open wire.
Check End of
Limt/At Speed
Input
Check End of
Limt/At Speed
Input
Check Sensor,
Wiring, and
Connections
Check Sensor,
Wiring, and
Connections
Check Sensor,
Wiring And
Connections
Check Sensor,
Wiring And
Connections
Check Main
Power Supply,
Reset Clock
Information Manual65
Page 71
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Chilled Water Flow LostMARChillerChilled
Module
that
Called
Diag.
Diag.
Active
Modes
Water
Control:
(All Stop
modes)
All modes
except
CAUSEHelp Message
a. The chilled water flow switch input was open
for more than 6-10 contiguous seconds.
b. 6-10 seconds of contiguous flow shall clear
this diagnostic.
c. Even though the pump times out in the STOP
modes, this diagnostic shall not be called out in
the STOP modes.
STOP
(00) and
EXTERN
AL STOP
(100)
Hot
Water
Control:
Start and
All Run
Modes.
Chiller: Loss of Comm with
Purge
Chiller: Loss of Comm with
Starter
Chiller: Loss of Comm with
Options
IFWChillerAllThe chiller module lost communications with the
Purge module for 15 contiguous seconds.
MMRChillerAllThe chiller module lost communications with the
Starter module for 15 contiguous seconds.
IFWChillerAllThe chiller module lost communications with the
Options module for 15 contiguous seconds. This
IFW diagnostic is generated if Free Cooling is
Not Installed, otherwise this is an MMR diag.
under code 2F6
Chiller: Loss of Comm with
Circuit
Chiller: Loss of Comm with I/O
Mod
MMRChillerAllThe chiller module lost communications with the
Circuit module for 15 contiguous seconds.
IFWChillerAllThe chiller module lost communications with the
I/O module for 15 contiguous seconds; And
HGBP is installed (at the CLD).
Chiller: Loss of Comm with I/O
Mod
MMRChillerAllThe chiller module lost communications with the
I/O module for 15 contiguous seconds; And
Pulsed IGV is installed (at the CLD).
Chiller: Loss of Comm with DCM IFWChillerAllThe DCM was setup as “installed” at the CLD
and the chiller module lost communications with
the DCM module for 15 contiguous seconds
Chiller: Loss of Comm with
Stepper #1
Chiller: Loss of Comm with
Local CLD
MMRChillerAllThe chiller module lost communications with the
Stepper #1 module for 15 contiguous seconds.
IFW-ARChillerAllThe chiller module lost communications with the
LCLD module for 15 contiguous seconds.
Note: As implemented this is a
latching IFW diagnostic. That is,
once generated it cannot be regenerated until a manual reset
is done.
Chiller: Loss of Comm with
Options
MMRChillerAllThe chiller module lost communications with the
Options module for 15 contiguous seconds. This
MMR diagnostic is generated if Free Cooling is
Installed, otherwise this is an IFW diag. under
code 2AE
Check Pump,
Valves, Flow
Switch
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
66CVHE-CLD-1A
Page 72
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Chiller: Loss of Comm with
Rfgt Monitor
Diag
Type
IFW-ARChillerAllThe Chiller module lost communications with the
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
Refrigerant Monitor for 15 contiguous seconds.
Chiller: Loss of Comm with TCIIFWChillerAllThe Tracer was setup as “installed” at the CLD
and the chiller module lost communications with
the TCI (comm 3 or comm 4) module for 15
contiguous seconds
Chiller Mod Off-Brd 5V RangeIFWChillerAllAn improper Off Board 5v voltage was detected
at the Chiller Module. A 5vdc is used for offboard devices such as the pressure transducers.
The micro checks to see that the A/D value falls
within an acceptable range.
Chiller Mod Ref Voltage
Calibration
IFWChillerAllAn improper reference voltage was detected at
the Chiller Module. A 2.5 vdc reference is used
to calibrate the non-ratiometric analog I/O such
as 2-10vdc and 4-20ma inputs as well as PWM
Analog outputs. The micro checks to see that the
A/D value falls within an acceptable range.
This diagnostic has not been implemented
Chlr Sat Cond Temp Sensor
(Purge)
(As Sensed by the Purge
module in Retrofit applications)
Circuit: Loss of Comm with
Starter
Circuit: Loss of Comm with
Chiller
IFWPurgeAllOpen or Shorted Sensor
a. Applies to Retrofit applications of the Purge
Only. Does not apply to UCP2 applications.
b. IFW to the chiller, MMR to the Purge.
MMRCircuitAllThe circuit module lost communications with the
Starter module for 15 contiguous seconds.
MMRCircuitAllThe circuit module lost communications with the
Chiller module for 15 contiguous seconds.
On loss of communications, the circuit module
shall run the oil pump for the post lube time and
then turn the oil pump off. On loss of
communications, the circuit module shall
continue to control the oil heater.
Circuit Module 24 Vdc Ref
Missing
IFWCircuitAll24vdc reference missing and the Rfgt monitor is
installed.
Circuit Mod Off-Brd 5V RangeMMRCircuitAllAn improper Off Board 5v voltage was detected
at the Circuit Module. A 5vdc is used for offboard devices such as the pressure transducers.
The micro checks to see that the A/D value falls
within an acceptable range.
Circuit Mod Ref Voltage
Calibration
IFWCircuitAllAn improper reference voltage was detected at
the Circuit Module. A 2.5 vdc reference is used
to calibrate the non-ratiometric analog I/O such
as 2-10vdc and 4-20ma inputs as well as PWM
Analog outputs. The micro checks to see that the
A/D value falls within an acceptable range.
Cond Diff Water Press
Transducer
IFWOptionsAllInput Shorted or Open and the Diff. water
pressure sensing option, > 150 psig, is “installed”
at the CLD.
Cond Entering Wtr Temp
IFWChillerAllOpen or ShortCheck Sensor,
Sensor
Cond Leaving Wtr Temp Sensor See
Descripti
on
ChillerAllOpen or Short.
a. IFW on Chilled Water Control
b. MMR on Heat Pump (Hot Water) Control.
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check Chiller
Module Voltages
Check Chiller
Module Voltages
Purge Inop: See
Purge O & M
Manual
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check Rfgt
Monitor Wiring/
24 Vdc Supply.
Check Circuit
Module Voltages
See
Troubleshooting
Service Bulletin
Check Sensor,
Wiring, and
Connections
Wiring And
Connections
Check Sensor,
Wiring And
Connections
Information Manual67
Page 73
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Condenser Rfgt Pressure
Sensor
Diag
Type
MMRCircuitAllOpen or Short.
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
Must Hold on open AND short input is 2.0 Psia.
Design: Both opens and shorts result in the
Check Sensor,
Wiring And
Connections
pressure going to the low end of the scale.
Therefore a Must Hold on the high pressure end
is not required.
Condenser Rfgt Temp SensorMMRStepperAllOpen or ShortCheck Sensor,
Wiring And
Connections
Condenser Water Flow LostMARChillerChilled
Water
Control:
Start and
All Run
Modes.
Hot
a. The chilled water flow switch input was open
for more than 6-10 contiguous seconds.
b. 6-10 seconds of contiguous flow shall clear
this diagnostic.
c. Even though the pump times out in the STOP
modes, this diagnostic shall not be called out in
the STOP modes.
Check Pumps,
Valves, Flow
Switch
Water
Control:
(All Stop
modes)
Condenser Water Flow Overdue MARChillerEstab.
Cond
Water
Condenser water flow was not proven within
4.25 minutes of the condenser pump relay being
energized.
Check Pump,
Valves, Flow
Switch
Flow
Condenser Water Pressure
Sensor
Cprsr did not Accelerate:
Shutdown
IFWChillerAllOpen or Short and the Cond Water Pressure
Sensor is setup as installed at the Clear
Language Display.
MMRStarterStart
Mode
a. The compressor did not come up to speed in
the allotted time defined by the Maximum
Acceleration Timer.
Check Sensor,
Wiring, and
Connections
Check Main
Power Supply &
Wiring
b. The Human Interface setups defined
“Shutdown” as the action when the Maximum
Acceleration Timer was exceeded.
Cprsr did not Accelerate FullyMMRStarterStartinga. Using either a Solid State Starter or an
Adaptive Frequency. Drive the UCM did not
receive an Up to Speed or At Speed Signal
Check End of
Limt/At Speed
Input
within the Maximum Acceleration Timer Setting.
b. Applies only to Solid State Starters and
Adaptive Frequency. Drives.
Cprsr Did Not Accelerate:
Transition
(The Motor is put across the
line.)
IFWStarterStart
Mode
a. The compressor did not come up to speed in
the allotted time defined by the Maximum
Acceleration Timer.
b. The Human Interface setups defined
See
Troubleshooting
Service Bulletin
“Transition” as the action when the Maximum
Acceleration Timer was exceeded.
Current OverloadMMRStarterAll
Running
Motor current exceeded overload time vs. trip
characteristic.
Modes
Current Overload Setpts ErrorIFWStarterAlla. The redundant overload settings did not agree
for 30 contiguous seconds. (Continue to use the
Check Main
Power Supply &
Wiring
Review
Overload Set Up
previous value for the 30 second timeout.) When
this diagnostic occurs the affected Starter
Module shall use the minimum (00000 binary, 00
decimal) overload setting as a default until either
the UCM is reset or, if the redundant settings
agree again, the starter module can go back to
using the actual setting.
68CVHE-CLD-1A
Page 74
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
CWS/Leaving Wtr Temp. Cutout
Setpt Overlap
also overlap of CWS and Low
Refrigerant Temp Cutout.
Diag
Type
NoneNoneAllNo diagnostic, limit value to last legal value and
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
tell the operator about it on the second line of the
display.
NOTE: The above is not a diagnostic because
you don't want the display vectoring you to a
different display state when you are trying to set
either the chilled water setpoint or the leaving
water temp. cutout setpoint as it will in the case
of a diagnostic.
DCM: Loss of Comm with Chiller AIFWChillerAllThe DCM module lost communications with the
chiller A Chiller module for 15 contiguous
seconds
DCM: Loss of Comm with Chiller BIFWChillerAllThe DCM module lost communications with the
chiller B Chiller module for 15 contiguous
seconds
DCM: Loss of Comm with
Starter A
IFWChillerAllThe DCM module lost communications with the
chiller A Starter module for 15 contiguous
seconds
DCM: Loss of Comm with
Starter B
IFWChillerAllThe DCM module lost communications with the
chiller B Starter module for 15 contiguous
seconds
DCM: Loss of Comm with TCI A IFWChillerAllThe DCM module lost communications with the
chiller A TCI module for 15 contiguous seconds
DCM: Loss of Comm with
Stepper A
IFWChillerAllThe DCM module lost communications with the
chiller A Stepper module for 15 contiguous
seconds
Differential Oil Pressure
Overdue
MMRCircuitPre-LubeA differential oil pressure 0f 9 psid was not
established within 3 minutes of starting the Oil
Pump in the Pre-Lube Mode.
Design: Some hysteresis was introduced into
this diagnostic. 9 psid is the criteria to establish
pre-lube oil flow and 8 psid is used to define a
loss of oil flow on pre-lube.
Differential Oil Pressure Switch
(CVGD and CVAD units only)
MMRCircuitPre-LubeJust prior to starting the oil pump the Differential
Oil Pressure Switch is checked to be sure it's
contacts are open (not stuck or jumpered), if not
set this diagnostic.
Discharge Temp SensorMMRStepperAllOpen or Short, only if HGBP and the Discharge
Temp. Sensor is called out as “Installed” at the
Human Interface.
Emergency Stop InputMMRChillerAlla. EMERGENCY STOP input is open. An
external interlock has tripped. Time to trip from
input opening to unit stop shall be 0.1 to 1.0
seconds.
Evap Diff Water Press
Transducer
IFWOptionsAllInput Shorted or Open and the Diff. water
pressure sensing option, > 150 psig, is “installed”
at the CLD.
Evap Entering Wtr Temp Sensor IFWChillerAllOpen or Short
a. Normal operation, no effects on control.
b. Chilled Water Reset, Will just run at either
normal CWS or will run at maximum reset
permitted.
Evap Leaving Water Temp
MMRChillerAllOpen or ShortCheck Sensor,
Sensor
N/A
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
See
Troubleshooting
Service Bulletin
Check Oil
Pressure
Switch/Wiring.
Check Sensor
Wiring And
Connections
Check
Emergency Stop
Input Device
Check Sensor,
Wiring, and
Connections
Check Sensor,
Wiring And
Connections
Wiring And
Connections
Information Manual69
Page 75
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
Evap Rfgt Temp SensorMMRStepperAllOpen or ShortCheck Sensor,
Wiring And
Connections
Evap Water Pressure SensorIFWChillerAllOpen or Short and the Evap Water Pressure
Sensor is setup as installed at the Clear
Language Display.
Evaporator Water Flow Overdue MARChillerEstab.
Evap.
Water
Evaporator water flow was not proven within
4.25 minutes of the Evaporator pump relay being
energized.
Check Sensor,
Wiring, and
Connections
Check Pump,
Valves, Flow
Switch
Flow on
going
from
STOP to
AUTO.
Extended Compressor SurgeMMRStarterAll
Running
Modes
An extended Surge condition was detected and
the Surge protection feature was Enabled at the
Clear Lang. Display. An extended Surge
Check
Condenser
Water Temp.
condition is defined being in a “continuous”
10% minutes.
Check Main
Power Supply &
Wiring
Extended Power Loss
Note: This diagnostic and the
functions tied to it are handled
by the Check Clock diagnostic.
surge condition for 15 +
IFWStarterAllThe unit lost power for an extended period of
time. On CTV units if power is lost for an
extended period of time the oil pump is not run
on Power Up. If a power loss is determined to be
a Momentary Power Loss the Oil Pump is run on
the Power Up to Post Lube the bearings. The
deciding factor determining if a power loss is
Extended or Momentary is TBD.
External Base Load SetpointIFW-ARChillerAlla. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input
diagnostic, Terminate external base loading
function. This IFW diagnostic will automatically
reset if the input returns to the normal range.
External Chilled Water SetpointIFW-AROptionsAlla. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input
diagnostic, default CWS to next level of priority
(e.g. Front Panel SetPoint). This IFW diagnostic
will automatically reset if the input returns to the
normal range.
External Current Limit SetpointIFW-AROptionsAlla. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input
diagnostic, default CLS to next level of priority
(e.g. Front Panel SetPoint. This IFW diagnostic
will automatically reset if the input returns to the
normal range.
External Hot Water SetpointIFW-AROptionsAlla. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input
diagnostic, default HWS to next level of priority
(e.g. Front Panel SetPoint). This IFW diagnostic
will automatically reset if the input returns to the
normal range.
External Vane Position Setpoint MMRChillerAlla. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal at
Input
diagnostic.
70CVHE-CLD-1A
Page 76
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Free Cooling ValvesMMROptionsWhen
Module
that
Called
Diag.
Diag.
Active
Modes
exiting
Free
cooling
CAUSEHelp Message
a. The Free Cooling Valves were commanded to
close and did not close in the three minutes
allowed for closure. And FC is installed (at the
CLD) and commanded off.
b. The Free Cooling Valves were commanded to
open and did not open in the three minutes
allowed for closure. And FC is installed (at the
CLD) and commanded On.
Heat Sink Temp SensorIFWStarterAllOpen or Short and Solid State Starter installed.
Note: The Solid State Starter is expected to be
protected from overheating via a thermal cutout.
Since this sensor is not used to protect the
starter, the failure of the sensor is treated as an
IFW.
HGBP Valve Closure OverdueIFWa. The HGBP Valve was commanded to close
and did not close in the three minutes allowed for
closure
High Bearing #1 TempMMRStepperAll
starting
and
running
modes
a. The bearing temperature at sensor #1
exceeded 180 + or - 5 °F (82.2 °C) for 0.5 - 2
seconds (Note: BT, WT, and DT may be
“instantaneous trip” but consistent with the
analog input filtering function.), and
b. This function is enabled at the CLD.
High Bearing #2 TempMMRStepperAll
starting
and
running
modes
a. The bearing temperature at sensor #2
exceeded 180 + or - 5 °F (82.2 °C) for 0.5 - 2
seconds (Note: BT, WT, and DT may be
“instantaneous trip” but consistent with the
analog input filtering function.), and
b. This function is enabled at the Human
Interface.
High Cprsr Discharge Temp.MARStepperAlla. The discharge temp. exceeded the trip value;
200°F + or - 5°F for CVHE/F, CVG and CVA.
The Discharge Temp Cutout is adjustable at the
Human Interface. See also section
P4_CPRSR.Doc of this Functional Specification.
b. Time to trip from trip value exceeded shall be
0.5 to 2.0 seconds. (Note: BT, WT, and DT may
be “instantaneous trip” but consistent with the
analog input filtering function.)
d. The diag. shall reset automatically 50 °F
below the trip point.
High Motor Temp Position #1MMRCircuitAny Start
and Run
Mode
The Motor winding temp. at sensor #1 exceeded
265 °F + or - 15°F for 0.5 - 2 seconds. (Note: BT,
WT, and DT may be “instantaneous trip” but
consistent with the analog input filtering
function.)
High Motor Temp Position #2MMRCircuitAny Start
and Run
Mode
The Motor Winding Temp. at sensor #2
exceeded 265 °F + or - 15 °F for 0.5 - 2 seconds.
(Note: BT, WT, and DT may be “instantaneous
trip” but consistent with the analog input filtering
function.)
High Motor Temp Position #3MMRCircuitAny Start
and Run
Mode
The Motor Winding Temp. at sensor #3
exceeded 265° F + or - 15° F for 0.5 - 2 seconds.
(Note: BT, WT, and DT may be “instantaneous
trip” but consistent with the analog input filtering
function.)
Check Clsd EndSwitches,
Valves, Wiring
Check Sensor
Wiring And
Connections
Check Clsd EndSwitches,
Valves, Wiring
Check Oil
System
Check Oil
System
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
Information Manual71
Page 77
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
High Oil TempMMRCircuitAll
Module
that
Called
Diag.
Diag.
Active
Modes
starting
and
running
Modes
CAUSEHelp Message
UCP2 shall provide a fixed High Oil Temperature
Cutout of 180 °F (82.2°C). If the oil temperature
violates the cutout by 120 degree F seconds
(66.6 degree C seconds) an MMR diagnostic
shall be generated.
High Pressure Cutout TrippedMMRCircuitAllA high pressure cutout was detected. See the
trip points for the various products under the
HPC switch description of this specification.
High Restart Inhibit Timer
Warning
IFWStarterAllThe Restart Inhibit timer has reached a
maximum threshold for the host chiller. For CTV
chillers this is 45 minutes. This indicates
excessive chiller cycling, steps should be taken
to correct this.
High Vacuum LockoutMMRCircuitPre-StartThe Oil Tank Pressure transducer shall be used
to sense for very low pressures in all Nonrunning cprsr modes.
IGV BPI Not Found During
Search
IFWStepperAllThe Inlet Guide Vane Actuator Binary Position
Indicator was not found over the entire stroke of
the IGV during the BPI search.
IGV BPI Found Low During
Search
IFWStepperAllThe Inlet Guide Vane Actuator Binary Position
Indicator was found too low in the stroke of the
IGV during the BPI search.
IGV BPI ShortedIFWStepperPre-StartAt what is believed to be a closed position, the
IGV BPI was found to be shorted.
IGV Electrical Drive Circuit
Open
MMRStepperOn
Demand
and
Run the IGV Actuator electrical drive circuit test
both on demand from the human interface and
just before the chiller starts.
Pre-Start
Incorrect Chiller Software
Installed
MMRChillerAllThe incorrect Eprom was loaded into this
module. This diagnostic is detected when a
factory test computer sets the unit type to
something other than what the Eprom software
was intended for.
Incorrect Stepper Software
Installed
MMRStepperAllThe incorrect Eprom was loaded into this
module. This diagnostic is detected when a
factory test computer sets the unit type to
something other than what the Eprom software
was intended for.
Inlet Guide Vane Closure
Overdue
IFWI/OAll Non-
running
modes,
a. The inlet guide vanes were commanded to
close and did not close in the three minutes
allowed for closure.
Starting,
Pre-Stop
(IGV
manual
modes)
I/O Mod: Loss of Comm with
Chiller
IFWI/OAllThe I/O module lost communications with the
Chiller module for 15 contiguous seconds.
Invalid Starter SelectionMMRStarterAll Modes The Cld has been setup for an AFD starter type,
however the starter module is not AFD
compatible.
(Note: This feature is not supported by
hardware.) (Special Note not for Publishing; See
Starter Module Design Specification for
requirements to enable AFD operation.)
Check Oil
System
Check
Condenser
Water Temp.
Check for
Excessive
Chiller Cycling
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
Check Stepper
Module, Wiring,
& Motor
Check Sensor,
Wiring, and
Connections
See
Troubleshooting
Service Bulletin
(No message is
required.)
(No message is
required.)
Check Clsd End-
Switches,
Vanes, Wiring
Check IPC
Wiring/
Connections
Call Local Trane
Service Agency
72CVHE-CLD-1A
Page 78
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Low Chilled Water Temp: Unit
Off
Diag
Type
IFW-ARChillerUnit in
Module
that
Called
Diag.
Diag.
Active
Modes
Auto and
No Ckt's
(Unit in Auto but not Starting or
Running)
Energize
d (Any
Ckt(s)
Energize
d)
Low Chilled Water Temp: Unit
On
MARChillerAny
Ckt(s)
Energize
(Unit Starting or Running)
d
(No Ckt's
Energize
d)
Low Differential Oil PressureMMRCircuitAll
starting
and
running
Modes
Low Evap Rfgt Temp.MMRStepperStarter
Contactor
Energize
d or in
Free
Cooling
Low Evap.Water Flow
(To be implemented in CTV
Phase C release and ABS
Phase B release.)
IFW-ARChillerChiller
Auto and
All
Running
Modes
Low Oil TempMARCircuitAll Non-
running
Modes.
CAUSEHelp Message
a. The chilled water temp. fell below the cutout
setpoint while the compressor (or Solution
Pump) was not running for 30 degree F
Seconds. Automatic Reset of the IFW dig shall
occur 2 degrees F (1.1 °C) above the cutout
setpoint.
a. The chilled water temp. fell below the cutout
setpoint while the compressor (or Solution
Pump) was running for 30 degree F Seconds.
Automatic Reset of the MAR diag shall occur 2
degrees F (1.1 °C) above the cutout setpoint.
Pre-Lube Mode on CVHE/F Chillers:
a. See Diagnostic 1FF.
Start & Run Mode on CVHE/F Chillers:
a. If during these modes the Differential oil
pressure drops below 9 PSID for more than 90
Psid Seconds, an MMR diagnostic shall be
generated. The 90 Psid Seconds integral shall
be reset to zero when the differential pressure
rises above 9 psid.
Pre-Lube Mode on CVGD/CVAD Chillers:
a. See Diagnostic 1FF.
Start & Run Mode on CVGD/CVAD Chillers:
a. While Starting and Running, if the differential
oil pressure switch opens for more than 3-5
seconds, generate an MMR diagnostic.
a. The Saturated Evap Rfgt Temp dropped
below
the Low Rfgt Temp. Cutout Setpoint when the
circuit was running for 30 °F seconds.
a. The evap. water flow measurement option
was installed and the flow dropped to a setpoint
set at the CLD. This IFW shall be Auto Reset
and reset 0.1 gpm/ton above the adjustable trip
point or when the Evaporator pump is turned off.
b. There shall be a 2 minute delay in permitting
this diagnostic to be called out from the time the
evap pump has been turned on AND flow has
been established/confirmed via the flow switch
input.
c. This is not necessarily active in a Manual On
of the Evaporator pump. That is, if the chiller is in
the Stop mode and the Evap. Relay is manually
turned on, this diagnostic shall not be active.
(Manual On is not taken into account.)
The oil temperature dropped below it's
adjustable Low Oil Temp. Cutout.
(“Instantaneous trip” but consistent with the
analog input filtering function.) See Section
P4_CPRSR for further description of this
diagnostic. Automatic Reset of the MAR diag
shall occur 5 degrees F (2.8 °C) above the
cutout setpoint.
Check Flow,
Sensor, & Wiring
Check Flow,
Sensor, & Wiring
Check Oil
System
Check
Operation, Call
Service
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
Information Manual73
Page 79
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Max Acceleration Setpts
Error
Diag
Type
IFWStarterAlla. The redundant Maximum Acceleration
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
settings did not agree for 30 contiguous
seconds. (Continue to use the previous value for
the 30 second timeout.) When this diagnostic
occurs the affected Starter Module shall use 6
seconds as a default until either the UCM is
reset or, if the redundant settings agree again,
the starter module can go back to using the
actual setting.
Max Pumpout Rate Exceeded-
IFWPurgeAlla. IFW to the chiller, MAR to the Purge.Purge Inop: See
Svc (Prg)
Max Pumpout Rate Exceeded
IFWPurgeAlla. IFW to the chiller, MAR to the Purge.Purge Inop: See
(Prg)
Memory Error Type I: NOVRAM MMRChillerOn UCM
Power Up
or
following
a Type II
Memory
error
diag.
a. On UCM either power up or following a Type II
Memory Error a NOVRAM memory error was
detected. The UCM is operating on all
Engineering Factory defaults for all setup
parameters. Check all setup parameters and
continue to run chiller. Replace the Chiller
Module as soon as a replacement is available.
Note: It is expected that this diagnostic will be
detected on the very first power up of the Chiller
Module at the Manufacturer since the NOVRAM
will not contain valid data on first power up.
Memory Error Type IVIFWChillerAllA page timeout error was detected while trying to
write data into EEPROM. There will likely be a
recall of Engineering Factory defaults on the
next reset or power transition. Replace the
Chiller Module as soon as a replacement is
available.
Memory Error Type II: Shadow
RAM
IFWChillerAlla. A Shadow RAM memory error was detected.
The UCM is operating on all last valid values
(pulled from NOVRAM) for all setup parameters.
No setup parameter changes were pending to be
loaded into NOVRAM, a complete recovery of all
setup parameters was made and there is no
need to check unit setup parameters.
Compressor starts and hour were lost for not
more than the last 24 hours. This is expected to
be an isolated event and repair or replacement is
not required. If this diagnostic does occur
repeatedly, then replace the Chiller module.
Memory Error Type IIIIFWChillerAlla. A Shadow Ram memory error was detected.
The UCM is operating on all last valid values
(pulled from NOVRAM) for all setup parameters.
Setup parameter changes less than 24 hours old
pending to be loaded into NOVRAM were lost.
Check all setup parameters made in the last 24
hours. Compressor starts and hours were lost for
not more than the last 24 hours. This is expected
to be an isolated event and repair or
replacement is not required. If this diagnostic
does occur repeatedly, then replace the Chiller
module.
Review Max
Acceleration Set
Up
Purge O & M
Manual
Purge O & M
Manual
Call Service to
Check all
Settings
Call Service to
Check all
Settings
No Settings
Were Lost
Settings
Changed in The
Last 24 Hours
Lost
74CVHE-CLD-1A
Page 80
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Momentary Power LossMARStarterAll
Module
that
Called
Diag.
Diag.
Active
Modes
Running
Modes
CAUSEHelp Message
Determine
Cause Of Power
Interruption
(Start
Mode,
e.g.
Before
Transition
Motor Temp Sensor #1MMRCircuitAllOpen or ShortCheck Sensor,
Wiring And
Connections
Motor Temp Sensor #2MMRCircuitAllOpen or ShortCheck Sensor,
Wiring And
Connections
Motor Temp Sensor #3MMRCircuitAllOpen or ShortCheck Sensor,
Wiring And
Connections
MPL Detect Circuit InoperativeMMRStarterAllA failure was detected in the Momentary Power
Loss detect circuit. If there are no zero cross
interrupts on Vab for 637.5 msec (Prior to
See
Troubleshooting
Service Bulletin
Centravac Upgrade 4: approx. 3 half line cycles),
the timer interrupt will trip and generate a
diagnostic that indicates that our ability to detect
MPL is gone. If Vab was truly gone the module
would be powered down so if we can detect that
Vab is gone then there must be a hardware
failure on the board.
The recalibration of the Differential Oil Pressure
sensors resulted in an error correction of greater
than 3 PSID.
See
Troubleshooting
Service Bulletin
and not
for 5
minutes
after
running.
Oil Pump Discharge Pressure
Sensor
MMRCircuitAllOpen or shorted input.
Must Hold on open AND short input is 2.0 Psia.
Design: Both opens and shorts result in the
Check Sensor,
Wiring, and
Connections
pressure going to the low end of the scale.
Therefore a Must Hold on the high pressure end
is not required.
Oil Sump Pressure SensorMMRCircuitAllOpen or shorted input.
Must Hold on open AND short input is 2.0 Psia.
Design: Both opens and shorts result in the
Check Sensor,
Wiring, and
Connections
pressure going to the low end of the scale.
Therefore a Must Hold on the high pressure end
is not required.
Oil Temp SensorMMRCircuitAllOpen or ShortCheck Sensor,
Wiring And
Connections
Options: Loss of Comm with
Starter
IFWOptionsAllThe options module lost communications with
the Starter module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Options: Loss of Comm with
Chiller
IFWOptionsAllThe options module lost communications with
the Chiller module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Information Manual75
Page 81
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Options Module 24 Vdc Ref
Missing
Options Module 24 Vdc Ref
Missing
Diag
Type
IFWOptionsAll24Vdc reference missing and the differential
MMROptionsAll24Vdc reference missing and the differential
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
water pressure transducers are installed.
water pressure transducers are installed and
Adaptive Frequency Drive installed.
Options Mod Off-Brd 5V RangeIFWOptionsAllAn improper Off Board 5v voltage was detected
at the Options Module. A 5vdc is used for offboard devices such as the External CWS and
CLS, and pressure transducers. The micro
checks to see that the A/D value falls within an
acceptable range.
Options Mod Ref Voltage
Calibration
IFWOptionsAllAn improper reference voltage was detected at
the Options Module. A 2.5 vdc reference is
used to calibrate the non-ratiometric analog I/O
such as 2-10vdc and 4-20ma inputs as well as
PWM Analog outputs. The micro checks to see
that the A/D value falls within an acceptable
range.
Outdoor Air Temp Sensor
IFWChillerAllOpen or Short
a. Use end of range value (whatever value the
See Also 3d3 diag.
(Either Outdoor Air Reset or
Low Ambient Lockout Selected)
Outdoor Air Temp Sensor
NoneNoneAllOpen or Short
open or short gives).
b. Clear diag. when the resistance returns to
normal range.
a. Display end of range value. (dashes “-----”)
See Also 3d3 diag.
(Both Outdoor Air Rst and Low
Ambient Lockout not selected.)
Outdoor Air Temp Sensor
MMRChillerAllOpen or ShortCheck Sensor,
See also A1 and A2 diag.
Over VoltageMARStarterPre-Start
and Any
Ckt(s)
Energzd
a. Line voltage above + 10% of nominal. (Must
hold = + 10% of nominal. Must trip = + 15% of
nominal. Reset differential = min. of 2% and
max. of 4%. Time to trip = minimum of 1 min. 10
sec. and maximum of 5 min. 20 seconds)
Phase LossMMRStarterContactor
Energizd
or all
Start, and
Run
modes.
a. No current was sensed on one or more of the
current xformer inputs. (Must hold = 20% RLA.
Must trip = 5% RLA.) Time to trip shall be 1
second minimum, 3 seconds maximum. Actual
design trip point is 10%.
b. Phase rotation protection is enabled and
either the Phase A current signal or the Phase C
current is less than approximately 5% of the CT
rating. Time to trip is 0.7 seconds for CTV/ABS.
Phase ReversalMMRStarterContactor
energized
to
transition
a. A phase reversal was detected on the
incoming current. On a compressor startup the
phase reversal logic must detect and trip in 0.7
seconds.
command
Phase Reversal Protection Lost MMRStarterStarter
Contactor
energized
to
transition
command
a. The phase reversal protection on the
compressor has become inoperative. The phase
rotation protection system failed to detect 2 in a
row of one of the four phase circuit states; Phase
reversal, Phase rotation OK, Phase A lost,
Phase B lost.
Check Press
Xducer Wiring/
24 Vdc Supply.
Check Press
Xducer Wiring/
24 Vdc Supply.
Check Options
Module Voltages
See
Troubleshooting
Service Bulletin
Check Sensor,
Wiring And
Connections
N/A
Wiring And
Connections
Check Main
Power Supply &
Wiring
Check Main
Power Supply &
Wiring
Check Main
Power Supply &
Wiring
Check Starter
Module.
76CVHE-CLD-1A
Page 82
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Purge Cprsr Suction Temp
Sensor
Diag
Type
IFWPurgeAllOpen or Shorted Sensor
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
a. IFW to the chiller, MMR to the Purge.
Purge Liquid Level Too HighIFWPurgeAlla. The Level Switch at the purge opened for 6 to
10 Seconds.
Note: This was implemented as tripping in 2 A/D
samples, which are 0.4 seconds apart. Prior to 2/
2/95 only 1 A/D sample could trigger this
diagnostic.
b. IFW to the chiller, MMR to the Purge.
Purge: Loss of Comm with
Chiller
IFWPurgeAllThe purge module lost communications with the
chiller module for 15 contiguous seconds.
a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with
Starter
IFWPurgeAllThe purge module lost communications with the
starter module for 15 contiguous seconds.
a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with
Stepper
IFWPurgeAllThe purge module lost communications with the
stepper module for 15 contiguous seconds.
a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with
Options
IFWPurgeAllThe purge module lost communications with the
chiller module for 15 contiguous seconds.
a. IFW to the chiller, IFW to the Purge.
Purge: Loss of Comm w/
Retrofit CLD
IFWPurgeAllThe purge module lost communications with the
retrofit Human Interface module for 15
contiguous seconds.
Purge: Loss of Comm with
Stepper #1
IFWPurgeAllThe purge module lost communications with the
chiller module for 15 contiguous seconds.
a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with
Stepper #2
IFWPurgeAllThe purge module lost communications with the
chiller module for 15 contiguous seconds.
a. IFW to the chiller, MAR to the Purge.
Purge Memory Error Type I:
NOVRAM
This diag. should be seen in
both UCP2 and retrofit
applications only.
MMRPurgeOn Purge
Power Up
or
following
a Type II
Memory
error
diag.
a. On either Purge Module power up or following
a Type II Memory Error, a NOVRAM memory
error was detected. The Purge Module is
operating on all Engineering Factory defaults for
all setup parameters. Check all setup
parameters and continue to run purge. Replace
the Purge Module as soon as a replacement is
available.
Note: It is expected that this diagnostic will be
detected on the very first power up of the Purge
Module at the Manufacturer since the NOVRAM
will not contain valid data on first power up.
Purge Memory Error Type II:
Shadow RAM
IFWPurgeAlla. A Shadow RAM memory error was detected.
The Purge Module is operating on all last valid
values (pulled from NOVRAM) for all setup
This diag. should be seen in
retrofit applications only.
parameters. No setup parameter changes were
pending to be loaded into NOVRAM, a complete
recovery of all setup parameters was made and
there is no need to check unit setup parameters.
Purge pumpout times Compressor starts and
hour were lost for not more than the last 24
hours. This is expected to be an isolated event
and repair or replacement is not required. If this
diagnostic does occur repeatedly, then replace
the Purge module.
Purge Inop: See
Purge O & M
Manual
Purge Inop: See
Purge O & M
Manual
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
Purge Inop: See
Purge O & M
Manual
No Setting Were
Lost
Information Manual77
Page 83
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Purge Memory Error Type III
Diag
Type
IFWPurgeAlla. A Shadow Ram memory error was detected.
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
The Purge Module is operating on all last valid
This diag. should be seen in
retrofit applications only.
values (pulled from NOVRAM) for all setup
parameters. Setup parameter changes less than
24 hours old pending to be loaded into NOVRAM
were lost. Check all setup parameters made in
the last 24 hours. Purge pumpout times
Compressor starts and hours were lost for not
more than the last 24 hours. This is expected to
be an isolated event and repair or replacement is
not required. If this diagnostic does occur
repeatedly, then replace the Purge module.
Purge Memory Error Type IVIFWPurgeAllA page timeout error was detected while trying to
write data into EEP Factory. There will likely be a
recall of Engineering Factory defaults or a
corruption of pumpout data on the next power
transition. Replace the Purge Module as soon as
a replacement is available.
Purge Memory Error III
IFWPurgeAlla. A Shadow Ram memory error was detected.
Compressor starts and hours were lost for not
This diag will be seen in UCP2
applications of the Purge
Module. This diag will not be
seen in retrofit applications of
the Purge Module. See also
diag 385-387.
more than the last 24 hours. This is expected to
be an isolated event and repair or replacement is
not required. If this diagnostic does occur
repeatedly, then replace the Purge module. This
is an IFW diagnostic to both the Purge and
Chiller.
Purge Misconfigured as Retrofit IFWPurgeAllThe Purge module is configured as a Retrofit
application instead of an UCP2 application.
Chiller module remaps Purge Retrofit Only
diagnostics to this diagnostic. Check Purge input
J1 pins 5,6. Open = UCP2 application, Short =
Retrofit application
Purge Misconfigured as UCP2IFWPurgeAllThe Purge module is configured as an UCP2
application instead of a Retrofit application.
Check Purge input J1 pins 5,6. Open = UCP2
application, Short = Retrofit application
Refrigerant Monitor SensorIFW-ARCircuitAllOpen or Shorted input and the Rfgt Monitor is
setup as installed at the Clear Language
Display.
Rfgt Monitor Memory LostIFWRfgt MonAllRefrigerant Monitor lost battery backed-up RAM.
a. IFW to the chiller, MMR/MAR to the
Refrigerant Monitor.
Rfgt Monitor IR SourceIFWRfgt Mon AllRefrigerant Monitor infrared optical source
(Normally Closed) is stuck in the “reset” state or
the switch/jumper is missing.
Rfgt Monitor Level 3 Rfgt
Refrigerant Alarm
IFWRfgt MonAllThe Refrigerant Monitor has read a refrigerant
concentration greater or equal to the level 3
setpoint.
Rfgt Monitor Auxiliary AlarmIFWRfgt MonAllThe Refrigerant Monitor auxiliary input signal
indicates an alarm condition.
Rfgt Monitor Level 2 Rfgt
Refrigerant Alarm
IFWRfgt MonAllThe Refrigerant Monitor has read a refrigerant
concentration greater or equal to the level 2
setpoint.
Rfgt Monitor Level 1 Rfgt
Refrigerant Alarm
IFWRfgt MonAllThe Refrigerant Monitor has read a refrigerant
concentration greater or equal to the level 1
setpoint.
Safety String Input Opened*** MMRScorpioAllSafety string input opened on the Scorpio
module
Severe Phase UnbalanceMMRStarterAll
Running
Modes
a. A 30% Phase Unbalance diagnostic has been
detected. Items to check are the Current
Transformer Part Numbers (they should all
match), The Current Transformer resistances,
line voltage phase balance, all power wiring
connections, the contactor pole faces, and the
motor. If all these are OK, replace the Starter
module.
Solid State Starter Fault Rly
Open
MMRStarterAll Start
and Run
The SSS fault relay is open.See Solid State
Mode
Soln Pump Winding Thermostat
Open
MMRCircuitAlla. The motor winding temperature thermostat
opened; nominally 230°F (110 °C).
b. The motor temp. thermostat or wiring is open.
c. Time to trip from input open to Solution Pump
shutdown shall be 0.5 to 2.0 seconds.
See Refrigerant
Monitor IOM
Manual
See Refrigerant
Monitor IOM
Manual
Check Bench
Heater, Wiring,
Connections
Recalibrate
Refrigerant
Monitor
See Refrigerant
Monitor IOM
Manual.
See Refrigerant
Monitor IOM
Manual
Check Signal At
Input
See Refrigerant
Monitor IOM
Manual.
N/A
N/A
N/A
N/A
N/A
Check Main
Power Supply &
Wiring
Starter Service
Bulletin, check
for an open wire.
Check Machine
Operation
Information Manual79
Page 85
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Starter Contactor Interrupt
Failure
Diag
Type
MMRStarterStarter
Module
that
Called
Diag.
Diag.
Active
Modes
Contact
not
Energize
d
(Starter
Contact
Energize
d)
CAUSEHelp Message
a. Welded Starter contactor.
b. Detected a welded compressor contactor
when the compressor was commanded off but
the current did not go to zero. Detection time
shall be 5 second minimum and 10 seconds
maximum for all Electromechanical and Solid
State Starters. Detection time for Adaptive
Frequency. Drives shall be 12 seconds minimum
and 20 seconds maximum. On detection,
generate the diagnostic, energize the
appropriate alarm relay, continue to command
the affected compressor off.
Starter did not TransitionMMRStarterOn the
first
check
after
transition.
a. The UCM did not receive a transition complete
signal in the designated time from the UCM
command to transition. The must hold time from
the UCM transition command is 1 second. The
Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds.
b. Item a. above is active only for Y-Delta, Auto-
Transformer, and Primary Reactor, and X-Line
Starters.
Starter Dry Run TestMMRStarterStarter
Dry Run
Mode
While in the Starter Dry Run Mode either 50%
Line Voltage was sensed at the Potential
Transformers or 10% RLA Current was sensed
at the Current Transformers.
Starter Fault Type IMMRStarterStartinga. This is a specific starter test where 1M(2k1) is
closed first and a check is made to ensure that
there are no currents detected by the CT's. If
currents are detected when only 1M is closed
first at start, then one of the other contactors is
shorted.
b. This test applies only to factory installed Y-
Delta Closed Transition Starters.
Starter Fault Type IIMMRStarterStartinga. This is a specific starter test where the
Shorting Contactor (S)(2K3) is individually
energized and a check is made to ensure that
there are no currents detected by the CTs. If
current is detected when only S is energized at
Start, then 1M is shorted.
b. This test in a. above applies to all forms of
starters (Note: It is understood that many
starters do not connect to the Shorting
Contactor.).
Starter Fault Type IIIMMRStarterStartinga. As part of the normal start sequence to apply
power to the compressor the Shorting Contactor
(S) and then the Main Contactor (1M) were
energized. 1.6 seconds later there were no
currents detected by the CT's for the last 1.2
Seconds on all three phases.
b. This test in a. above applies to all forms of
starters except Adaptive Frequency. Drives
(Note: It is understood that many starters do not
connect to the Shorting Contactor.).
c. For Adaptive Frequency Drives, TBD
Starter: Loss of Comm with
Circuit
MMRStarterAllThe starter module lost communications with the
Circuit module for 15 contiguous seconds.
Complete
Starter
Checkout
Required
Complete
Starter
Checkout
Required
Current or
Voltage
Detected
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
Check IPC
Wiring/
Connections
80CVHE-CLD-1A
Page 86
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Starter: Loss of Comm with
Chiller
Diag
Type
MMRStarterAllThe starter module lost communications with the
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSEHelp Message
Chiller module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Starter Mod Ref Voltage
Calibration
IFWStarterAllAn improper reference voltage was detected at
the Starter Module. A 2.5 vdc reference is used
to calibrate the non-ratiometric analog I/O such
See
Troubleshooting
Service Bulletin
as 2-10vdc and 4-20ma inputs as well as PWM
Analog outputs. The micro checks to see that the
A/D value falls within an acceptable range.
Stepper #1:Loss of Comm with
Starter
MMRStepperAllThe Stepper #1 module lost communications
with the Starter module for 15 contiguous
seconds.
Stepper #1:Loss of Comm with
Chiller
MMRStepperAllThe Stepper #1 module lost communications
with the Chiller module for 15 contiguous
seconds.
Surge Shutdown: Ice BuildingMARStarterAll Ice
Building
Modes
An extended Surge condition was detected while
in Ice Building Mode. This diagnostic shall clear
when the Ice Building command is withdrawn.
TCI: Loss of Comm with PurgeIFWTCIAllThe TCI module lost communications with the
Purge module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
See
Troubleshooting
Service Bulletin
Check IPC
Wiring/
Connections
TCI: Loss of Comm with StarterIFWTCIAllThe TCI module lost communications with the
Starter module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with Options IFWTCIAllThe TCI module lost communications with the
Options module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with CircuitIFWTCIAllThe TCI module lost communications with the
Circuit module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with ChillerIFWTCIAllThe TCI module lost communications with the
Chiller module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with
Stepper #1
IFWTCIAllThe TCI module lost communications with the
Stepper #1 module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Tracer Communications LostIFWTCIAllThe Tracer was setup as “installed” at the CLD
and the TCI lost communications with the Tracer
for 15 contiguous minutes after it had been
Check Tracer to
UCP Wiring/
Connections
established. Continue to run the chiller with the
last valid Tracer Setpoints/Mode.
Tracer failed to Establish Comm IFWTCIAt power-upThe Tracer was setup as “installed” at the CLD
and the Tracer did not communicate with the TCI
within 2 minutes after power-up.
Check Tracer
Wiring/
Connections/
Power
Tracer Outdoor Air Temp
Sensor Fail
IFWChillerAllCheck Sensor,
Wiring, and
Connections
Tracer Temperature SensorIFWOptionsAllInput Shorted.Check Sensor,
Wiring, and
Connections
Transition Complete Input
Shorted
MMRStarterPre-Starta. The Transition Complete input was found to
be shorted before the compressor was started.
b. This is active for all electromechanical
Check transition
complete
contact
starters.
Information Manual81
Page 87
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Transition Complete Input
Opened
Under VoltageMARStarterPre-Start
NOTE: For FastPak, the “module that called the diagnostic” is
Scorpio if Circuit or Stepper is listed
*** FastPak-only Diagnostic
MMRStarterAll
Module
that
Called
Diag.
Diag.
Active
Modes
Running
Modes
and Any
Ckt(s)
Energzd
CAUSEHelp Message
a. The Transition Complete input was found to
be opened with the compressor motor running
after a successful completion of transition.
b. This is active only for Y-Delta, AutoTransformer, and Primary Reactor Starters.
a. Line voltage below - 10% of nominal or the
Under/Overvoltage transformer is not connected.
(Must hold = - 10% of nominal. Must trip = - 15%
of nominal. Reset differential = min. of 2% and
max. of 4%. Time to trip = min. of 1 min. and
max. of 5 min.)
4Display Menu HeadingsEnable, DisableEnable
5Differential To Start Setpoint1 to 10°F, 0.5 to 5.5 °C5 °F, 2.8°C
6Differential To Stop Setpoint1 to 10°F, 0.5 to 55°C5 °F, 2.8°C
7Evap Pump Off Delay0 to 30 Minutes1 Minute
8Printer Setups
Print Time IntervalEnable, DisableEnable
Print on Time Interval1 to 24 hrs.8 hrs.
Print on DiagnosticEnable, DisableEnable
Number of Pre-Diag Reports1 to 55
Diagnostic Report Interval2 to 120 secondsS seconds
3ICS Address:1 to 12765
4Power Up Start Delay Time0 to 60° Seconds0 Seconds
5Design Delta Temp Setpoint:4 to 30°F, 2.2 to 16.7° C100° F, 5.5 °C
6Lvg Wtr Temp Cutout Setpoint: (When this
setpoint is within 1.7°F of the Front Panel
Chilled Water Setpoint, the Front Panel
Chilled Water Setpoint is increased along
with this setpoint to maintain the differential)
7Low Rfgt Temp Cutout Setpt: (When this
setpoint is within 6°F of the Front Panel
Chilled Water Setpoint, the Front Panel
Chilled Water Setpoint is increased along
with this setpoint to maintain the differential.)
8Condenser Limit Setpoint:80 to 120%93%
9Maximum RI Timer Setting30 to 60 Minutes60 Minutes
10Purge Control/Type:Micro Purge, Stand-Alone
11Purge Max Pumpout Rate:1 to 100 minutes/24 hrs20 Minutes /24