Trane CVHE, CVHF, CVHG, CVRB, CVRC User guide

Page 1
Information Manual
Clear Language Display
Water-Cooled, Hermetic CenTraVac® Clear Language Display for UCP2 and FastPak™ Control Panels
Models CVHE, CVHF, CVHG, CVRB, CVRC 50 and 60 Hz
Cooling-Only and Heat Recovery, Direct-Drive CenTraVacs with UCP2 Control panels
X39470756-02
CVHE-CLD-1A
February 2000
Page 2
Contents
General .................................................................. 1
Literature Change History ................................... 1
About This Manual .............................................. 1
LCD Display ........................................................ 1
Keypad ................................................................ 1
LED Alarm ........................................................... 1
Local Clear Language ......................................... 1
Control System ..................................................... 2
Unit Control Panel ............................................... 2
Custom Report ...................................................... 3
Custom Report Group ......................................... 3
ASHRAE Guideline 3 Report ................................ 4
Chiller Report ...................................................... 10
Chiller Operating Mode ..................................... 10
Chiller Operating Mode ..................................... 12
Active Chilled Water Setpoint/Evap Leaving
Water Temp ..................................................... 12
Active Chilled Water Setpoint/Chilled Water Set-
point Source ..................................................... 12
Active Ice Termination Setpoint/Ice Termination
Setpoint Source ............................................... 12
Active Hot Wtr Setpoint/Hot Wtr
Setpoint Source ............................................... 12
Evaporator Entering and Leaving
Water Temperatures ........................................ 13
Cond Entering and Leaving Water Temps ........ 13
Active Current Limit Setpoint ............................. 13
Active Current Limit Setpoint/Current Limit
Setpoint Source ............................................... 13
Evaporator Water Flow/ Condenser Water Flow 13
Chiller Tons ....................................................... 13
Outdoor Temperature ........................................ 13
Aux. Bundle or Heat Recovery Temps .............. 13
Chilled Water Setpoint Source .......................... 13
Current Limit Setpoint Source ........................... 14
Hot Water Setpoint Source ................................ 14
Ice Termination Setpoint Source ....................... 14
Refrigerant Report ............................................. 15
Report Heading ................................................ 15
Evaporator and Condenser Refrigerant
Pressure .......................................................... 15
Saturated Evap Temperature/Evap Refrigerant
Pressure .......................................................... 15
Saturated Cond Temperature/Cond
Refrigerant Press ............................................ 15
Saturated Evap Temp. and Discharge Temp. .. 15
Purge Operating Mode/Purge Status ............... 15
Purge Alarm Message ...................................... 15
Purge Suction Temp/Purge Liquid Temp. ........ 16
Purge Pumpout Rate/Purge Max Pumpout Rate 16 Purge Total Pumpout Time/ Purge Total Run
Time ................................................................ 16
Purge Adaptive Cycle Time w/Chlr On/Time to
Purge Remaining ............................................ 16
Purge Adaptive Cycle Time w/Chlr Off/Time to
Purge Remaining ............................................ 16
Purge Service Log ............................................ 16
Pumpout Avg, Last 30 Days ............................. 16
Refrigerant Monitor ........................................... 17
Approach Temperature ..................................... 17
Compressor Report ........................................... 18
Report Heading ................................................ 18
Differential Oil Pressure, Oil Temperature ........ 18
Discharge Oil Pressure, Oil Tank Pressure ...... 18
AF Compressor Speed Command ................... 18
AF Boundary Pressure Coefficient/AF Press.
Coefficient ....................................................... 18
AF Re-Optimization Timer Time Remaining ..... 18
Inlet Guide Vane Position ................................. 18
Compressor Phase Currents % RLA ................ 19
Compressor Line Currents Amps ..................... 19
Compressor Line Voltages ............................... 19
Compressor Power Factor and Watts .............. 19
Compressor Winding Temperatures ................. 19
Compressor Starts and Running Time ............. 19
Bearing Temperatures #1 and #2 ..................... 19
Solid State Starter Heat Sink Temp. ................. 19
HGBP Time ...................................................... 19
Operator Settings ............................................... 20
Settings Group Keys ......................................... 20
Operator Settings Group Heading .................... 20
Set Contrast - Applies to
CCCLD Display Only. ...................................... 20
Information Manual ii
Page 3
Purge Operating Mode ..................................... 20
Time Of Day Setting ......................................... 21
Front Panel Chilled Water Setpoint .................. 21
Front Panel Hot Water Setpoint ........................ 22
Front Panel Current Limit Setpoint ................... 22
Print Report ....................................................... 22
Control Type ..................................................... 22
Free Cooling ..................................................... 22
Chilled Water Reset Type ................................. 22
Reset Ratio ....................................................... 23
Start Reset Setpoint .......................................... 23
Maximum Reset Setpoint .................................. 23
Ice Building Enable ........................................... 23
Front Panel Ice Termination Setpoint ............... 23
Ice Making To Normal Cooling Transition Timer 23
Chilled Water Setpoint Source .......................... 24
Current Limit Setpoint Source ........................... 24
Hot Water Setpoint Source ............................... 24
Ice Termination Setpoint Source ...................... 24
Outdoor Air Temperature Source ..................... 24
Setpoint Source Override ................................. 24
Service Settings (Non Password Protected Ser-
vice Settings Group) .......................................... 25
Service Setting Group Heading ........................ 25
Menu Settings Password .................................. 25
Keypad/Display Lockout ................................... 26
Language Setting .............................................. 27
Display Units ..................................................... 27
Decimal Places Displayed Setpoint .................. 27
Display Menu Headings Enable ........................ 27
Clear Custom Menu .......................................... 27
Differential to Start Setpoint .............................. 27
Differential to Stop Setpoint .............................. 27
Evap/Cond Pump Off Delay Time ..................... 28
Printer Setups ................................................... 28
Clear Restart Inhibit Timer ................................ 29
Field Start-up ...................................................... 30
Field Startup ..................................................... 30
Field Start-up Group Heading ........................... 30
Keypad/Display Lock Feature Enable ............... 30
Menu Settings Password Enable ...................... 30
ICS Address ...................................................... 31
Power Up Start Delay Time .............................. 31
Design Delta Temperature Setpoint ................. 31
Leaving Water Temperature Cutout Setpoint ... 31 Low Refrigerant Temperature Cutout Setpoint . 31
Condenser Limit Setpoint ................................. 31
Maximum Restart Inhibit (RI) Timer Setting ...... 31
Purge Control/Type ........................................... 32
Purge Service Log Reset .................................. 32
Purge Maximum Pumpout Rate ........................ 32
Purge Service Excessive Pumpout
Override Timer ................................................ 32
Purge Low Chiller Sat. Cond. Liquid Temp. Protec-
tion Enable ...................................................... 32
Purge Low Chiller Sat. Cond. Temp Setpoint ... 32
Surge Protection Enable ................................... 32
Under/Over Voltage Protection Enable ............. 32
Phase Reversal Protection Enable ................... 33
Phase Unbalance Limit Enable ......................... 33
Momentary Power Loss (MPL)
Protection Enable ............................................ 33
Enhanced Oil Temp. Protection ........................ 33
Oil Temp Setpoint ............................................. 33
Low Oil Temp Cutout ........................................ 34
Low Oil Temp Start Inhibit Differential .............. 34
High Discharge Temp Cutout ............................ 34
External Base Loading Enable .......................... 34
Soft Load Control Enable .................................. 34
Soft Load Starting Current Limit ........................ 34
Soft Load Current Limit Rate Of Change .......... 34
Soft Load Lvng Wtr Temp Rate of Change ....... 34
Hot Gas Bypass Enable .................................... 34
HGBP Timer Enable ......................................... 35
Maximum HGBP Time ...................................... 35
HGBP Mode, Vane Target ................................ 35
LWT Control Integral Gain (Ki) Setpt ................ 35
LWT Control Derivative Gain (Kd) Setpt ........... 35
IGV Maximum Travel Setpt ............................... 35
Guide Vane Closed Travel Stop ....................... 35
AF Adjustable Speed Control Algorithm Enable 36
AF Leaving Water Standard Deviation .............. 36
AF Pressure Coefficient Constant ..................... 36
AF Re-Optimization Factor ............................... 36
AF Re-Optimization Timer ................................ 36
AF Boundary Pressure Coefficient Y Intercept . 36 AF Boundary Pressure Coefficient Y
Intercept Max ................................................... 37
AF Pressure Error Deadband ........................... 37
AF Proportional Speed Gain ............................. 37
Minimum Capacity Timer Enable ...................... 37
Time Permitted at Minimum Capacity ............... 37
Evaporator Flow Coefficient .............................. 37
Evaporator Flow Equation Exponent ................ 37
Evaporator Fluid Coefficient .............................. 38
Condenser Flow Coefficient .............................. 38
Condenser Flow Equation Exponent ................ 38
Local Atmospheric Pressure ............................. 38
Refrigerant Pressure Analog Output Option ..... 38
Min Delta Pressure Calibration ......................... 38
Max Delta Pressure Calibration ........................ 38
IGV Stroke Time ............................................... 39
Low Differential Oil Pressure Cutout ................. 39
Check Oil Filter Diagnostic ................................ 39
Check Oil Filter Setpoint ................................... 39
Evap Leaving Water Temp Offset ..................... 39
Saturated Evap Rfgt Temp Offset ..................... 39
iii
Page 4
Water Pressure Calibration ............................... 39
Refrigerant Monitor Settings Group ................. 49
Machine Configuration ....................................... 40
Service Settings - Machine Configuration ......... 40
Machine Configuration Group Heading ............. 40
Unit Frequency .................................................. 40
Unit Type ........................................................... 40
Nominal Unit Tons ............................................ 40
Refrigerant Type ................................................ 40
Refrigerant Monitor Type ................................... 40
Starter Type ....................................................... 41
Startup Contactor Test - Y-D Starters Only ....... 41
Rated Load Amps .............................................. 41
Motor Heating Constant .................................... 41
Current Overload Setting #1 .............................. 41
Current Overload Setting #2 .............................. 41
Procedure For Selecting Current Overload Settings
for UCP2 .......................................................... 41
Maximum Acceleration Timer #1 ....................... 44
Maximum Acceleration Timer #2 ....................... 44
Hot Water Control Option .................................. 44
Heatsink Start Inhibit Temperature Setpoint
(FastPak) ......................................................... 44
External Chilled Water Setpoint Option ............. 45
External Current Limit Setpoint Option .............. 45
External Hot Water Setpoint Option .................. 45
Acceleration Time Out Action ............................ 45
Motor Over Temperature Protection .................. 45
Motor Winding RTD Type .................................. 45
High Pressure Cutout Setting ............................ 45
Line Voltage Sensing Option ............................. 45
Unit Line Voltage ............................................... 45
Auxiliary Condenser Option ............................... 46
Heat Recovery Option ....................................... 46
Hot Gas Bypass Option ..................................... 46
Free Cooling Option .......................................... 46
Condenser Pressure Sensor Option ................. 46
Bearing Temperature Sensors Option ............... 46
Discharge Temperature Sensor Option ............ 46
Ice Building Option ............................................ 46
Differential Water Press Sensing Option ........... 46
External Analog Input Type Selection,
4-20 ma/2-10 VDC ........................................... 47
Tracer Option .................................................... 47
TCI Option ......................................................... 47
Printer Option .................................................... 47
Duplex Control Module (DCM) Option ............... 47
IGV Output Type ............................................... 47
Oil Pressure Protection .................................... 47
Programmable Analog Output ........................... 47
Programmable Relay Outputs ........................... 48
Current Transducer Setpoint ............................. 48
Current Transducer at 100% RLA ..................... 48
Compressor Power Source ............................... 48
Refrigerant Monitor Settings Group Heading ... 49
Alarm Level 1 .................................................... 49
Alarm Level 2 .................................................... 49
Alarm Level 3 .................................................... 49
Refrigerant Audible Alarm ................................ 49
Trouble Audible Alarm ...................................... 49
Alarm 1 Latching Status ................................... 49
Alarm 2 Latching Status ................................... 49
Alarm 3 Latching Status ................................... 50
Channel Scanner .............................................. 50
Scanner Channel 1 ........................................... 50
Scanner Channel 2 ........................................... 50
Scanner Channel 3 ........................................... 50
Scanner Channel 4 ........................................... 50
Scanner Dwell Threshold ................................. 50
Auxiliary Input ................................................... 50
Auxiliary Input Alarm ......................................... 50
Analog Output Range ....................................... 50
Refrigerant Monitor Calibration ........................ 51
Refrigerant Monitor Settings Group Heading ... 51
Refrigerant Monitor Mode ................................. 51
Refrigerant Zero Calibration ............................. 51
Refrigerant Span Calibration ............................ 52
Service Tests Group .......................................... 54
Service Tools Group Password Request .......... 54
Service Tools Group Heading .......................... 55
Chilled Water Pump .......................................... 55
Chilled Water Flow Switch Status ..................... 55
Evaporator Differential Water Pressure ............ 55
Evaporator Entering/Leaving Water Pressure .. 55
Condenser Water Pump ................................... 55
Condenser Water Flow Switch Status .............. 55
Condenser Differential Water Pressure ............ 55
Condenser Entering/Leaving Water Pressure .. 55
Starter Dry Run ................................................. 56
Oil Pump Status ................................................ 56
Vane Control Status/Vane Position Commands 56
Vane Position ................................................... 56
HGBP Valve Control Status/Manual Open and
Close Commands ............................................ 56
HGBP Valve Manual Opening/Closing
Duty Cycle ....................................................... 57
Vane Control Status/Manual Load and Unload
Commands ...................................................... 57
Manual Loading/Unloading Duty Cycle ............ 57
AF Manual Speed Control - CVHE/F/G Only .... 57
AF Compressor Speed Command - CVHE/F/G
Only ................................................................. 57
AF Compressor Speed Command - CVHE/F/G
Only ................................................................. 58
Information Manual iv
Page 5
AF Boundary Pressure Coefficient/AF Pressure Co-
efficient - CVHE/F/G Only ............................... 58
AF Re-Optimization Timer Time Remaining- CVHE/
F/G Only .......................................................... 58
Module Software Revision Levels ..................... 58
Diagnostics Menu .............................................. 59
Diagnostics Group Heading .............................. 59
Menu Settings Password .................................. 59
Diagnostics and Annunciation .......................... 60
Clearing Diagnostics ......................................... 60
New Diagnostic Display .................................... 61
Diagnostics ....................................................... 62
FastPak™ “Settings Group” Menu Record ..... 81
Operator Settings Group: .................................. 81
FastPak™ “Settings Group” Menu Record ..... 82
Service Settings Group: Basic Setups .............. 82
FastPak™ “Settings Group” Menu Record ..... 83
Field Startup Group: ......................................... 83
FastPak™ “Settings Group” Menu Record ..... 85
Machine Configuration Group: .......................... 85
FastPak™ “Settings Group” Menu Record ..... 86
Machine Configuration Group: .......................... 86
FastPak™ “Settings Group” Menu Record ..... 87
Refrigerant Monitor Settings Group: ................. 87
FastPak™ “Settings Group” Menu Record ..... 88
Service Tests Group: ........................................ 88
v
Page 6
General
General
Literature Change History
CVHE-CLD-1 (February 1995)
Application of the Clear Language Display to the UCP2 Centravac
CVHE-CLD-1A (February 2000)
Updated information and incorporated FastPak™ items.
About This Manual
This manual describes the application of the Clear Language Display (CLD) to the UCP2 Centravac. It describes its use as a machine-mounted human interface.
A description of the UCP2 reports and message displays are provided along with additional “Help Notes” to clarify the display messages. In addition, a Diagnostics section is also included.
LCD Display
The display on the Clear Language Display is a 2­line by 40-character liquid crystal display (LCD). Upper and lower case alphabetic characters can be displayed, along with numeric and special characters.
LED Alarm
In addition to the alpha-numeric LCD display, there's a single discrete LED on the human interface. The red LED flashes on-off whenever a latching diagnostic is present and a manual reset is required to restore full unit operation. The LED is also used to indicate that a function or control has been set to manual from within the Service Test Menu. If a control has been set to manual, the LED is on and non-flashing. A diagnostic supersedes a manual operation. As a result, the unit could have a manual mode set and be in a latching diagnostic. In this case the LED would flash on-off. The LED is off otherwise.
Figure 1 Keypad Matrix
CUSTOM
REPORT
OPERATOR
SETTINGS
Previous + Enter Auto
CHILLER REPORT
SERVICE
SETTINGS
REFRIGERANT
REPORT REPORT
SERVICE
TESTS
COMPRESSOR
DIAGNOSTICS
LCD Backlight
The LCD display has an LED backlight so it can be read in low light conditions.
Next
-
Cancel Stop
Keypad
A sealed dirt-proof keypad is used on the unit mount Clear Language Display. Metal dome switch actuators respond when any key is pressed. See Figure 1 .
Important! FACTORY DEFAULT SETTINGS: Menu items that are programmable using the keypad may have a selectable choice that is listed as Factory Default. This Factory Default setting is the software default that is initially factory-programmed for a new module assembly and may NOT be the correct setting for a specific operating chiller. Always review all settings when any module is replaced to verify that the settings agree with the desired settings that were selected at initial startup or programmed at the factory.
Information Manual 1
Local Clear Language
The Local CLD “Clear Language Display” resides at the Chiller providing display of chiller data and access to operator/service controls, setpoints, and chiller set-up information. All information is stored in non-volatile memory in the Chiller module. The Local CLD and the Chiller module work together to display and store information requiring non-volatility.
Page 7
Control System
Control System
Unit Control Panel
Safety and operating controls are housed in the UCP2 unit control panel, the starter panel, and the purge control panel.
The UCP2 control is a modular design partitioned by major function or group of functions. All modules (see Figure 2 ) communicate with each other through the Interprocessor Communication Circuit (IPC).
Figure 2 UCP2 Control Panel
I/O Module
Major components within each control group are shown in the figure.
Unit-mounted temperature sensors, pressure transducers, and functional switches provide analog and binary inputs to the various modules.
The microcomputer-based modules are illustrated in the figure. All wiring to the modules are to pluggable terminal blocks.
Stepper Mod
Options Mod
Chiller Mod
Circuit Mod
2 CVHE-CLD-1A
Page 8
Custom Report
Custom Report Group
Reports are added to the custom report group by pressing the <+> key when the desired report is being displayed from its normal report location. Reports are removed from the custom report group by pressing the <-> key when the desired custom report is being displayed. The Custom report group can contain a maximum of 20 reports. When adding a report to the Custom Report, if the <+> key is pressed when the Custom Report already contains 20 reports, a message, “Custom Report Is Full, Report Not Added,” indicating that the Custom Report is full, will be displayed for 2 seconds. If an attempt is made to add a report to the Custom Report that is already in the Custom Report, a message, “Report Already In Custom Menu”, will be displayed for 2 seconds.
Custom Report
The Custom Report sequence is as follows:
Report Heading
User Defined Custom Report
Press (Next)(Previous) To Continue
If no entries are selected for the Custom Report, see Empty List Display.
Empty Display List
If no entries are selected for the Custom Report, the second entry is:
No Items Are Selected For Custom Report:
See Operators Manual To Select Entries
The report then wraps around to the report heading when <Next> is pressed.
If there are items selected for the Custom Report, then the empty list display is not used. Instead, the report heading and the selected items are displayed sequentially as <Next> or <Previous> are pressed.
Information Manual 3
Page 9
ASHRAE Guideline 3 Report
ASHRAE Guideline 3 Report
Press (Enter) For ASHRAE Guideline 3 Rpt
Press (Next)(Previous) To Continue
If <Enter> is pressed the ASHRAE Guideline 3 Report Menu is entered, shown at the end of the Standard Report below. Otherwise, If <Next> is pressed the Standard Report is entered. The ASHRAE Guideline 3 Report Entry screen may be added to Custom Report by pressing the <+> key. Adding it to the Custom Report allows the user to access the ASHRAE Guideline 3 Report from the Custom Menu.
The following are the Standard Report screens, e.g. not part of the ASHRAE Guideline 3 Report.
ASHRAE Guideline 3 Reports
ASHRAE Guideline 3 Report
Press (Next)(Previous) To Continue
Time Of Day/Refrigerant Type
Current Time/Date HH:MM xm Mon,XX XXXX
Refrigerant Type: [type]
Possible values for refrigerant type are: R11, R123, R12, R134a, R22, R113, R114, R500, or R502.
Chiller Operating Mode
The chiller operating modes display comes up first in the standard report:
[Operating mode line 1]
[Operating mode line 2]
Line 1 (and 2 if needed) indicates a current condition of the unit as shown in the following table (Table 1) . In some cases, an associated timer or system parameter will be displayed that assures the transition to an expected mode is in progress, particularly during the unit start-up sequence.
4 CVHE-CLD-1A
Page 10
Table 1 Operating Modes
ASHRAE Guideline 3 Report
Unit Operation
Stop
Auto
Operating Mode Display*
(First Line/Second Line)
Resetting
Local Stop: Cannot Be Overridden By
Any External Or Remote Device
Remote Display Stop: Chiller May Be
Set To Auto By Any Ext Or Rmt Device
Remote Run Inhibit
From External Source
Unit Operation
Run
Remote Run Inhibit
From Tracer
Heat Sink Temp Start Inhibit Unit Is Running in Surge Condition
Diagnostic Shutdown Stop Unit Is Running; Capacity Limited By
Diagnostic Shutdown Auto Unit Is Running; Capacity Limited By
Waiting For Evaporator Water Flow
Auto
Auto
Waiting For A Need To Cool
Waiting For Tracer Communications
To Establish Operating Status
Starting Is Inhibited By Staggered Start
Time Remaining: MIN:SEC
Starting Is Inhibited By Restart
Inhibit Timer: Time Remaining MIN:SEC
Auto
Operating Mode Display*
(First Line/Second Line)
Unit Is Running
Capacity Limited By Phase Unbalance
Unit Is Running
Capacity Limited By High Cond Press
Unit Is Running
Capacity Limited By Low Evap Temp
Unit is Running
Capacity Limited By Vane Open Travel
Stop
Unit Is Running
Minimum Capacity Due To Vane Closed
Travel Stop
Pulldown Rate Based Soft Loading
Current Based Soft Loading
Auto
Waiting For Condenser Water Flow
Establishing Evap Water Flow
Establishing Oil Pressure
Establishing Evap Water Flow
Prelubrication Time: MIN:SEC
Evap Water Is Flowing
Prelubrication Time: MIN:SEC
Evap Water Is Flowing
Performing IGV BPI Search & Calibration
Establishing Cond Water Flow
Establishing Oil Pressure
Establishing Cond Water Flow
Prelubrication Time: MIN:SEC
Cond Water Is Flowing
Prelubrication Time: MIN:SEC
Initialize
Start
Run
Information Manual 5
Cond Water Is Flowing
Establishing Oil Pressure
Cond Water Is Flowing
Performing IGV BPI Search and
Calibration
Cond Water Is Flowing
PreStart Unload Time Remaining:
MIN:SEC
Starting Compressor Unit is Running; Base Loaded
Unit Is Running Unit is Running; Base Loaded
Unit Is Running
Capacity Limited By High Current
Run
Establishing Evap Water Flow
Performing IGV BPI Search & Calibration
Unit is Running; Base Loaded
Unit is Running; Base Loaded
Capacity Limited By High Current
Unit is Running; Base Loaded
Capacity Limited By Phase Unbalance
Unit Is Running; Base Loaded
Capacity Limited By High Cond Press
Unit Is Running; Base Loaded
Capacity Limited By Low Evap Temp
At Vane Open Travel Stop
At Vane Closed Travel Stop
Unit is Running; Base Loaded
In Surge Condition
Page 11
ASHRAE Guideline 3 Report
Operating Mode Display*
Unit Operation
Run
Run-Unload
Run-Ice Build
* Displays are not in any sequence. Some displays will never appear, depending on options and situation
Active Chilled Water Setpoint/Chilled Water Setpoint Source
Active Chilled Water Setpoint: xxx.x f/c
[settings source] CWS: xxx.x f/c
(First Line/Second Line)
Unit Is Running; Base Loaded
Current Based Soft Loading
Unit Is Running In Minimum Capacity Unit Is Building Ice
Unit Is Running In Minimum Capacity
Time Remaining: MIN:SEC
Unit Is Preparing To Shutdown Ice Building Is Complete
Unit Is Building Ice
Capacity Limited By Vane Open Travel
Stop
Unit Is Building Ice
Unit Is Building Ice
Capacity Limited By High Current
Unit Is Building Ice
Capacity Limited By Phase Unbalance
Unit Operation
Run-Ice Build
Post-Lube
Stop
Active Current Limit Setpt/Current Limit Setpt Source
Active Current Limit Setpoint: xxx %
[settings source] CLS: xxx %
Operating Mode Display*
(First Line/Second Line)
Capacity Limited By High Cond Press
Capacity Limited By Low Evap Temp
Surge Has Been Detected
Unit Is Running; Transitioning Ice Building
To Normal MIN:SEC
Time Remaining: MIN:SEC
Unit Is Building Ice
Unit Is Building Ice
Post Lubrication
Panic Stop
Starter Dry Run
Settings source will be one of the following: Front Panel, Tracer, or External Source.
Settings source will be one of the following: Front Panel, Tracer, External Source, or Ice Building.
Refrigerant Monitor
The following item will be displayed if the Analog Rfgt Monitor is installed.
Refrigerant Monitor: xxx.x PPM
Press (Next)(Previous) To Continue
The following item will be displayed if the IPC Rfgt Monitor option is installed.
Refrigerant Monitor: xxxx PPM R-YYYY
Press (Next)(Previous) To Continue
Where (Y) can equal 123, 11, 22, 134a, or 12.
Purge Pumpout Rate/Purge Max Pumpout Rate
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Pumpout Rate: xxx.x Min/24Hrs
Purge Max Pumpout Rate: xxx.x Min/24Hrs
6 CVHE-CLD-1A
Page 12
ASHRAE Guideline 3 Report
Purge Total Pumpout Time/ Purge Total Run Time
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Total Pumpout Time: xx,xxx.x Min
Purge Total Run Time: xx,xxx.x Hrs
Purge Operating Mode/Purge Status
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Operating Mode: [Mode]
Purge Status: [Status]
Possible values of [Mode] are: Auto, Stop, On, or Adaptive.
Possible values of [Status] are:
Idle (Condensing Unit is Off)
Running (Condensing Unit is On)
Pumpout (Temperature initiated
Service Pumpout (Pumpout initiated by the
Running - Pumpout Inhibited By Low Temp.
Pumpout Maximum Rate Disabled
Pumpout)
service switch)
(Pumpout inhibited by low liquid temp)
(Max. Pumpout Rate alarm disabled)
Saturated Evap Temperature/Evap Refrigerant Pressure Compressor Discharge Temp
Compressor Discharge Temperature shown only if discharge temperature is installed.
Discharge Oil Pressure, Oil Tank Pressure
This screen is only displayed if the “Oil Pressure Protection” setpoint is set to “Transducer” or “Xducer & Switch.”
Discharge Oil Pressure: xxx.x psig
Oil Tank Pressure: xxx.x psig
Differential Oil Pressure, Oil Temperature
This screen is only displayed if the “Oil Pressure Protection” setpoint is set to “Transducer” or “Xducer & Switch.”
Differential Oil Pressure: xxx.x [units]
Oil Tank Temperature: xxx.x f/c
' Differential Oil Pressure: xxx.x [units]' is only displayed if the “Oil Pressure Protection” setpoint is set to “Transducer” or “Xducer & Switch.” If 'Switch' is selected as the setpoint, then ' Differential Oil Pressure Switch: [Status]' is displayed where Status is open or closed.
For FastPak, Differential Oil Pressure: xxx.x [units], this screen is only displayed if the “Oil Pressure Protection Setpoint” is set to “Diff Xducer" If 'Switch' is selected as the setpoint, then ' Differential Oil Pressure Switch: [Status]' is displayed where Status is open or closed.
The Possible value for [units] is “psid” or “kPa” dependent upon whether English or SI units are selected.
Bearing Temperatures #1 and #2
The following will be displayed only if the Bearing Temp Sensors Option is Installed.
Saturated Evap Rfgt Temp: xxx.x f/c
Compressor Discharge Temp: xxx.x f/c
Bearing Temperature 1: xxx.x f/c
Bearing Temperature 2: xxx.x f/c
Compressor Starts and Running Time
The starts and hours counters are displayed as follows:
Compressor Starts: xxxxx
Compressor Running Time: HRS:MIN:SEC
Information Manual 7
Evaporator Entering and Leaving Water Temperatures
Evap Entering Water Temp: xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c
Page 13
ASHRAE Guideline 3 Report
Saturated Evap Temperature/Evap Refrigerant Pressure
Saturated Evap Rfgt Temp: xxx.x f/c
Evap Rfgt Pressure: xxx.x psig
Evaporator Approach Temp.
Evaporator Approach Temp.: xx.x f/c
Press (Next)(Previous) To Continue
Evaporator Entering/Leaving Water Pressure
The following will be displayed only if the low pressure (< or = to 150 psig) Differential Water Pressure Sensor Option is Installed.
Evap Entering Water Pressure:xx.x psid/kPa
Evap Leaving Water Pressure: xx.x psid/kPa
Evaporator Differential Water Pressure
The following will be displayed only if the Differential Water Pressure Sensor Option is Installed.
Chiller Tons
The following will be displayed only if the Differential Water Sensing Option is installed.
Approximate Chiller Capacity: xxxx Tons/KW
Press (Next)(Previous) To Continue
The possible values for units are “Tons” or “KW.”
Cond Entering and Leaving Water Temps
Dashes will be displayed for condenser entering or leaving water temperature if the corresponding input is open or shorted.
Cond Entering Water Temp: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Saturated Cond Temperature/Cond Refrigerant Press
Saturated Cond Temp: xxx.x f/c
Cond Rfgt Pressure: xxx.x psig
Evap Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Evaporator Water Flow
The following is displayed only if the Differential Water Sensing Option is installed.
Approx Evaporator Water Flow:xxx.x gpm/lpm
Press (Next)(Previous) To Continue
The possible values for units are “gpm” or “lpm.”
Chilled Water Flow Switch Status
The following will be displayed only if the Differential Water Sensing Option is not installed. This screen displays the status of the chilled water flow switch status at the input to the UCM.
Chilled Water Flow Switch Status:
[y]
Condenser Approach Temp.
Condenser Approach Temp.: xx.x f/c
Press (Next)(Previous) To Continue
Condenser Entering/Leaving Water Pressure
The following will be displayed only if the low pressure (< or = to 150 psig) Differential Water Pressure Sensor Option is Installed.
Cond Entering Water Pressure:xx.x psid/kPa
Cond Leaving Water Pressure: xx.x psid/kPa
Condenser Differential Water Pressure
The following will be displayed only if the Differential Water Pressure Sensor Option is Installed.
Cond Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Possible values for [y] are: Flow Switch is Open/No Flow or Flow Switch is Closed/Flow.
8 CVHE-CLD-1A
Page 14
Condenser Water Flow
The following will be displayed only if the Differential Water Sensing Option is installed.
Approx Condenser Water Flow: xxx.x gpm/lpm
Press (Next)(Previous) To Continue
The possible values for units are “gpm” or “lpm.”
Condenser Water Flow Switch Status
The following screen is displayed only if the Differential Water Pressure Sensor Option is not Installed. This screen displays the status of the condenser water flow switch status at the input to the UCM.
Condenser Water Flow Switch Status:
[y]
ASHRAE Guideline 3 Report
Possible values for [y] are Flow Switch is Open/No Flow or Flow Switch is Closed/Flow
Aux. Bundle or Heat Recovery Temps
The following will be displayed only if either the Heat Recovery Option or Aux Condenser Option is installed.
Aux/Heat Rcvy Ent Wtr Temp: xxx.x f/c
Aux/Heat Rcvy Lvg Wtr Temp: xxx.x f/c
Information Manual 9
Page 15
Chiller Report
Chiller Report
The Chiller Report sequence is as follows:
Chiller Status, Water Temps & Setpts
Press (Next)(Previous) To Continue
Chiller Operating Mode
Friendly mode line 1
Friendly Mode (First Line/second Line)
Display is Blank
Resetting
Local Stop: Cannot Be Overridden By
Any External Or Remote Device
Remote Display Stop: Chiller May Be
Set To Auto By Any Ext Or Rmt Device
Remote Run Inhibit From Remote Computer
Remote Run Inhibit From External Source
Remote Run Inhibit From Tracer
Run Inhibit From DCM
Heat Sink Temperature Start Inhibit
Diagnostic Shutdown Stop Diagnostic Shutdown Auto
Waiting For Evaporator Water Flow
Waiting For A Need To Cool
Waiting For A Need To Heat
Waiting For Tracer Communications
To Establish Operating Status
Starting Is Inhibited By Staggered Start
Time Remaining: MIN:SEC
Transitioning To Free Cooling
Waiting For Cond Water Flow Opening Free Cooling Valves
Cond Water Is Flowing
Closing Free Cooling Valves
Unit Running; Last Mode Free Cooling Limit
Time Remaining To End Of Limit: MIN:SEC
Transitioning To Free Cooling
Waiting For IGV Positioning To Complete
Unit Is Free Cooling
Starting Is Inhibited By Restart
Inhibit Timer: Time Remaining MIN:SEC
Establishing Cond Water Flow
Establishing Oil Pressure
Establishing Cond Water Flow
PreLubrication Time: MIN:SEC
Cond Water Is Flowing
Establishing Oil Pressure
Unit Is Running
Friendly mode line 2
Friendly mode line 1 is indicative of a unit mode. Friendly mode line 2 is usually a verbal continuation of line 1 and can be viewed as a continuous message along with line 1. In some cases Friendly mode line 2 is the display of an associated timer or system parameter.
[Friendly mode] will be one of the following:
Auto
Auto
Auto
Starting
10 CVHE-CLD-1A
Page 16
Unit Is Running
Capacity Limited By High Current
Unit Is Running
Capacity Limited By Phase Unbalance
Unit Is Running
Capacity Limited By High Cond Press
Unit Is Running
Capacity Limited By Low Evap Temp
Unit Is Running; Capacity Limited By
Vane Open Travel Stop
Unit is Running; Minimum Capacity
Due To Vane Closed Travel Stop
Unit Is Running In Surge Condition
Unit Is Running; Capacity Limited By
Pulldown Rate Based Soft Loading
Unit Is Running; Capacity Limited By
Current Based Soft Loading Unit Is Running; Hot Water Control Unit Is Running; Hot Water Control
Capacity Limited By High Current
Unit Is Running; Hot Water Control
Capacity Limited By Phase Unbalance
Unit Is Running; Hot Water Control
Capacity Limited By High Cond Press
Unit Is Running; Hot Water Control
Capacity Limited By Low Evap Temp
Unit Is Running; Hot Water Control
At Vane Open Travel Stop
Unit is Running; Hot Water Control
At Vane Closed Travel Stop Unit Is Running; Hot Water Control
In Surge Condition
Unit Is Running; Hot Water Control
Pulldown Rate Based Soft Loading
Unit Is Running; Hot Water Control
Current Based Soft Loading
Unit is Running; Base Loaded Unit is Running; Base Loaded
Capacity Limited By High Current
Unit is Running; Base Loaded
Capacity Limited By Phase Unbalance
Unit Is Running; Base Loaded
Capacity Limited By High Cond Press
Unit Is Running; Base Loaded
Capacity Limited By Low Evap Temp
Unit Is Running; Base Loaded
At Vane Open Travel Stop
Unit is Running; Base Loaded
At Vane Closed Travel Stop
Unit Is Running; Base Loaded
In Surge Condition
Unit Is Running; Base Loaded
Pulldown Rate Based Soft Loading
Unit Is Running; Base Loaded
Current Based Soft Loading
Chiller Report
Unit Is Running In Hot Gas Bypass
Unit Is Running In Minimum Capacity
Time Remaining: HR:MIN:SEC
Unit Is Preparing To Shutdown
Information Manual 11
Page 17
Chiller Report
Chiller Operating Mode
The chiller operating modes display comes up first in the standard report:
[Operating mode line 1]
[Operating mode line 2]
Line 1 (and 2 if needed) indicates a current condition of the unit as shown in the preceding table (Table 1) . In some cases, an associated timer or system parameter will be displayed that assures the transition to an expected mode is in progress, particularly during the unit start-up sequence.
Active Chilled Water Setpoint/Evap Leaving Water Temp
Active Chilled Water Setpoint:xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c
If the chiller is in the Ice Making or Ice Making Complete state, the following display is substituted for the above display:
Active Ice Termination Setpoint/Ice Termination Setpoint Source
The following will be displayed only if the Ice Building Option is installed.
Active Ice Termination Setpoint: xxx.x f/c
[settings source] ITS: xxx.x f/c
Settings source will be one of the following: Front Panel or Tracer.
Active Hot Wtr Setpoint/Hot Wtr Setpoint Source
The following will be displayed only if the Hot Water Control Option is Installed.
Active Hot Water Setpoint: xxx.x f/c
[settings source] HWS: xxx.x f/c
Settings source will be one of the following: Front Panel, Tracer, or External Source.
Active Ice Termination Setpoint: xxx.x f/c
Evap Entering Water Temp: xxx.x f/c
If the chiller is in the hot water control state, the following display is substituted for the above display:
Active Hot Water Setpoint: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Active Chilled Water Setpoint/Chilled Water Setpoint Source
Active Chilled Water Setpoint: xxx.x f/c
[settings source]CWS: xxx.x f/c
Settings source will be one of the following: Front Panel, Tracer, External Source, or Duplex Control.
12 CVHE-CLD-1A
Page 18
Chiller Report
Evaporator Entering and Leaving Water Temperatures
Evap Entering Water Temp: xxx.x f/c
Evap Leaving Water Temp: xxx.x f/c
Cond Entering and Leaving Water Temps
Dashes will be displayed for condenser entering or leaving water temperature if the corresponding input is open or shorted.
Cond Entering Water Temp: xxx.x f/c
Cond Leaving Water Temp: xxx.x f/c
Active Current Limit Setpoint
Active Current Limit Setpoint: xxx %
Press (Next)(Previous) To Continue
Chiller Tons
The following will be displayed only if the Differential Water Sensing Option is installed.
Approximate Chiller Capacity: xxxx Tons/KW
Press (Next)(Previous) To Continue
The possible values for units are “Tons” or “KW.”
Outdoor Temperature
If the outdoor air temperature input is open or shorted and neither Outdoor Air Reset nor Low Ambient Lockout is enabled, display “------” in place of “xxx.x F.” Otherwise the temperature received from the chiller module is displayed.
Outdoor Air Temperature: xxx.x f/c
Press (Next)(Previous) To Continue
Aux. Bundle or Heat Recovery Temps
Active Current Limit Setpoint/Current Limit Setpoint Source
Active Current Limit Setpoint: xxx %
[settings source] CLS: xxx %
Settings source will be one of the following: Front Panel, Tracer, External Source, or Ice Building.
Evaporator Water Flow/ Condenser Water Flow
The following will be displayed only if the Differential Water Sensing Option is installed.
Approx Evaporator Water Flow:xxx.x gpm/lpm
Approx Condenser Water Flow: xxx.x gpm/lpm
The possible values for units are “gpm” or “lpm.”
The following will be displayed only if either the Heat Recovery Option or Aux Condenser Option is installed.
Aux/Heat Rcvy Ent Wtr Temp: xxx.x f/c
Aux/Heat Rcvy Lvg Wtr Temp: xxx.x f/c
Chilled Water Setpoint Source
Chld Wtr Setpt Source: [settings source]
Reset Condition: [reset condition]
Settings source will be one of the following: Front Panel, Tracer, or External Source.
Reset condition will be one of the following: None, Outdoor Temp, or Return Wtr Temp.
Information Manual 13
Page 19
Chiller Report
Current Limit Setpoint Source
Cur Lim Setpt Source:[settings source]
Press (Next)(Previous) To Continue
Settings source will be one of the following: Front Panel, Tracer, External Source, or Ice Building.
Hot Water Setpoint Source
The following will be displayed only if Hot Water Control is Installed.
Hot Water Setpt Source: [settings source]
Press (Next)(Previous) To Continue
Settings source will be one of the following: Front Panel, Tracer, or External Source.
Ice Termination Setpoint Source
The following will be displayed when/if remote computer is installed.
Ice Termn Setpt Source: [settings source]
Press (Next)(Previous) To Continue
Settings source will be one of the following: Front Panel or Tracer.
14 CVHE-CLD-1A
Page 20
Refrigerant Report
Refrigerant Report
Report Heading
Refrigerant Temp & Pressure Report
Press (Next)(Previous) To Continue
Evaporator and Condenser Refrigerant Pressure
Evap Rfgt Pressure: xxx.x psig
Cond Rfgt Pressure: xxx.x psig
Saturated Evap Temperature/Evap Refrigerant Pressure
Saturated Evap Temp: xxx.x f/c
Evap Rfgt Pressure: xxx.x psig
Purge Operating Mode/Purge Status
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Operating Mode: [Mode]
Purge Status: [Status]
Possible values of [Mode] are: Auto, Stop, On, or Adaptive.
Possible values of [Status] are:
Idle (Condensing Unit is Off)
Running (Condensing Unit is On)
Pumpout (Temperature Initiated
Service Pumpout (Pumpout initiated by service
Running - Pumpout inhibited by low temp.
Pumpout Maximum Rate Disabled
pumpout)
switch)
(Pumpout inhibited by low liquid temp)
(Max. pumpout rate alarm disabled)
Saturated Cond Temperature/Cond Refrigerant Press
Saturated Cond Temp: xxx.x f/c
Cond Rfgt Pressure: xxx.x psig
Purge Alarm Message
The following screen(s) is not displayed if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Alarm Msg: [Status]
[Help Message]
Saturated Evap Temp. and Discharge Temp.
The Discharge Temp will be displayed only if the Discharge Sensor Option is installed.
Saturated Evap Rfgt Temp: xxx.x f/c
Compressor Discharge Temp: xxx.x f/c
Information Manual 15
Possible values for [Status] are: No Diagnostics Present (the [Help Message] is: Press (Next) (Previous) To Continue) or Diagnostic Alarm (the [Help Message] is: Go to Diag. Menu for Description/ Reset).
Page 21
Refrigerant Report
Purge Suction Temp/Purge Liquid Temp.
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Suction Temp: xxx.x f/c
Purge Liquid Temp: xxx.x f/c
Purge Pumpout Rate/Purge Max Pumpout Rate
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Pumpout Rate: xxx.x Min/24Hrs
Purge Max Pumpout Rate: xx.x Min/24Hrs
Purge Total Pumpout Time/ Purge Total Run Time
Purge Adaptive Cycle Time w/Chlr Off/ Time to Purge Remaining
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Adapt Cycle T w/Chlr Off: xxx.x Hrs
Time To Purge Remaining: xxx.x Hrs
If the mode selected is not Adaptive, then the time in the bottom line is dashed out.
Purge Service Log
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Service Log: Reset Log In Field Start_Up
Purge Pumpout Time: xxxxxxx.x Pumpout Min
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Total Pumpout Time: xx,xxx.x Min
Purge Total Run Time: xx,xxx.x Hrs
Purge Adaptive Cycle Time w/Chlr On/ Time to Purge Remaining
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Adapt Cycle T w/Chlr On: xxx.x Hrs
Time To Purge Remaining: xxx.x Hrs
If the mode selected is not Adaptive, then the time in the bottom line is dashed out.
Service Log: Reset Log In Field Start_Up
Time Since Last Rst: xxxx Cal Days
Pumpout Avg, Last 30 Days
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
30 Day Purge Pumpout Avg: xxx.x Min
Chiller Average Run Time: xxx.x Hr/Day
30 Day Pumpout Avg,
Chiller Running: xxx.x Min
Last 5 Cycle Pumpout Avg,Interval From Shtdn To 3 Hrs After Shtdn: xxx.x Min
30 Day Pumpout Avg, Interval From 3Hrs After Shtdn To Next Start: xxx.x Min
16 CVHE-CLD-1A
Page 22
Refrigerant Report
Refrigerant Monitor
The following item is displayed if the Analog Refrigerant Monitor option is installed.
Refrigerant Monitor: xxx.x PPM
Press (Next)(Previous) To Continue
The following items are displayed if the IPC Refrigerant Monitor option is installed.
The following screen is displayed if the refrigerant monitor scanner is installed:
Refrigerant Monitor Mode: [Mode]
Scanner Channel X XXXX PPM [Rfgt Type]
The following screen is displayed if the channel scanner is not installed:
Refrigerant Monitor Mode: [Mode]
The following is displayed if the IPC Refrigerant Monitor Auxiliary input option is installed.
Rfgt Mon Auxiliary Input: XX.X mA
Press (Next) (Previous) To Continue
Approach Temperature
Evaporator Approach Temp: XXX.X F
Condenser Approach Temp: XXX.X F
XXXX PPM [Rfgt Type]
Possible values of Mode are: Warmup, Ready, Monitor Check, Trouble.
If the PPM is out of range low or high “-Err” and “++++” respectively are displayed. If the concentration has not been determined, or the refrigerant monitor is in “Monitor Check” mode, “-----” is displayed.
The following is displayed if the channel scanner option is installed.
Last Rfgt Conc Chan1 Chan2 Chan3 Chan4
PPM [Rfgt Type] XXXX XXXX XXXX XXXX
If the PPM is out of range low or high “-Err” and “++++” respectively are displayed. If a channel is inactive, “-----” is displayed.
Refrigerant Monitor Case Temp: XXX.X F
Refrigerant Monitor Bench Temp: XXX.X F
Information Manual 17
Page 23
Compressor Report
Compressor Report
The Compressor Report Group sequence is as follows.
Report Heading
Compressor Hours, Starts & Amps
Press (Next)(Previous) To Continue
Differential Oil Pressure, Oil Temperature
Differential Oil Pressure: xxx.x [units]
Oil Tank Temperature: xxx.x f/c
The possible value for [units] is “psid” or “kPa” dependent upon whether English or SI units are selected.
Discharge Oil Pressure, Oil Tank Pressure
Discharge Oil Pressure: xxx.x psig
Oil Tank Pressure: xxx.x psig
AF Boundary Pressure Coefficient/AF Press. Coefficient
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator and Adaptive Speed Control Algorithm is Enabled.
AF Boundary Press Coefficient: x.xxx
AF Pressure Coefficient: x.xxx
Note: This is a Report only for Troubleshooting purposes.
AF Re-Optimization Timer Time Remaining
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator and Adaptive Speed Control Algorithm is Enabled.
AF Re-Optimization Time Remaining:xx:xxHrs
Press (Next) (Previous) to Continue
Note: This is a Report only for Troubleshooting purposes.
AF Compressor Speed Command
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator and Adaptive Speed Control Algorithm is Enabled.
AF Compressor Speed Command: xx Hz
AF Compressor Speed Command: xxxx RPM
Range of values is 2520 to 3600 rpm in increments of 1 rpm. Factory default is 3600 rpm.
18 CVHE-CLD-1A
Inlet Guide Vane Position
This screen does not appear if “Inlet Guide Vane Output” is set to “Pulsed.”
Inlet Guide Vane Position xxx.x % Open
Inlet Guide Vane Position xx.x degrees
Page 24
Compressor Report
Compressor Phase Currents % RLA
Compressor Phase Currents - % RLA
A xxxx.x % B xxxx.x % C xxxx.x %
Compressor Line Currents Amps
Compressor Phase Currents - Amps
A xxxx amps B xxxx amps C xxxx amps
Compressor Line Voltages
Compressor Line Voltages
AB xxxx v BC xxxx v CA xxxx v
This data is displayed only if the line voltage sensing option is installed. if not installed, no screen is displayed.
Compressor Winding Temperatures
Compressor Winding Temperatures
W1 xxx f/c W2 xxx f/c W3 xxx f/c
Compressor Starts and Running Time
The starts and hours counters are displayed as follows:
Compressor Starts: xxxxx
Compressor Running Time: HRS:MIN:SEC
Bearing Temperatures #1 and #2
The following will be displayed only if the Bearing Temp Sensors Option is Installed.
Bearing Temperature 1: xxx.x f/c
Bearing Temperature 2: xxx.x f/c
Compressor Power Factor and Watts
The following is displayed only if the Line Voltage Sensing Option is Installed AND the starter type is Not “Adaptive Frequency” or AFD AND Compressor Power Source is Utility AND External KW is Not Installed.
Compressor Power Factor: xx %
Compressor KiloWatts: xxxx KW
Solid State Starter Heat Sink Temp.
The following will be displayed only if the Solid State Starter is installed.
Solid State Starter Heat Sink: xxx.x f/c
Press (Next)(Previous) To Continue
HGBP Time
If HGBP is installed in the unit the following screen is displayed:
HGBP Time: HRS:MIN:SEC
Press (Next)(Previous) To Continue
Information Manual 19
Page 25
Operator Settings
Operator Settings
Settings Group Keys
The four settings Group Keys for CVHE/CVHF/ CVHG are as follows:
q Operator Settings - non-password protected
menu items that can be changed by the operator
q Service Settings - menu items that should only
be changed by a qualified service technician
q Service Tests - activate outputs of Chiller (e.g. oil
pump)
q Diagnostics - abnormal operating conditions,
informational warnings, automatic reset, and manual reset types and other information.
Operator Settings Group Heading
Important! FACTORY DEFAULT SETTINGS: Menu items that are programmable using the keypad may have a selectable choice that is listed as Factory Default. This Factory Default setting is the software default that is initially factory-programmed for a new module assembly and may NOT be the correct setting for a specific operating chiller. Always review all settings when any module is replaced to verify that the settings agree with the desired settings that were selected at initial startup or programmed at the factory.
The Operator Settings Group sequence follows.
The possible values for status are “Locked” or “Unlocked”. If the password status is locked, the password message will be “Enter Password to Unlock”. The user will then depress (-)(+)(-)(+)(-)(+) followed by the <Enter> key. The password keystrokes will be echoed to the screen as a visual aide. The last six keystrokes represent the current password, and up to twenty keystrokes can be entered. An incorrect password, or the twenty-first keystroke will result in the password message “Invalid Password”.
If the password status is unlocked, the password message will be “Press (Enter) to Lock”. Pressing <Enter> locks the settings in ALL the menus. If the password is entered to unlock the settings, this unlocks the settings in ALL menus.
Whenever a password is in use the “Press (+)(-) to change setting” message will be suppressed on setpoint screens. Any attempt to change the setting will result in the message “Setting is Locked”. The password once entered will remain valid until canceled.
Set Contrast - Applies to CCCLD Display Only.
Set Contrast: Press () to Save
Press (+)(-) to Change Setting
Chilled Water & Current Limit Setpts
Press (Next)(Previous) To Continue
If the Menu Settings Password feature is Enabled in the Service Setup Group following each setting group heading the following is displayed:
Settings In This Menu Are [status]
[password message]
Likewise, if the Menu Settings Password is Disabled in the Service Setup Group, the above screen will not appear.
20 CVHE-CLD-1A
Purge Operating Mode
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Operating Mode: [Mode]
Press (+)(-) to Change Setting
Possible values of [Mode] are: Stop, On, Auto (Factory Default) and Adaptive.
Page 26
Time Of Day Setting
Operator Settings
Current Time/Date HH:MM xm Mon,XX XXXX
(Enter) to Change : (Next) to Continue
The top level "CurrentTime/Date" will be displayed when this screen is first selected. Pressing the <Next> or <Previous> key will go to the next or previous screen as usual.
If the <Enter> key is selected, five separate screens can be displayed with which the time may be set. The “Current Time/Date” will be displayed on line one of each of these screens. Each of these screens will change one element of the current time/date. The second line of each screen will indicate which element of the current time/date is being changed.
If the first time changing screen is being displayed and the <Previous> key is pressed, the top level “Current Time/Date” screen will be displayed and the <Enter> key will have to be selected to re-enter the time changing screens. If the fifth time changing screen is being displayed and the <Next> key is pressed, the next screen will be displayed. If <Previous> is selected at this point, the top level “Current Time/Date” screen will be displayed and the <Enter> key will have to be selected to re-enter the time changing screens
To change an element of the current time/date, select <Enter> from the top level “Current Time/Date” screen to enter the time changing screens. Hit <Next> or <Previous> to get to the proper screen. Press the <+> <-> keys to change the element to it's proper value and press the <Enter> key to store the new time/date. A message “Updating Chiller Clock, Please Wait” is displayed for two seconds after the <Enter> key is pressed.
The five time changing screens are as follows:
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Month, Press(+)(-) & (Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Day, Press (+)(-) & (Enter)
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Year, Press (+)(-) & (Enter)
Front Panel Chilled Water Setpoint
Front Panel Chilled Wtr Setpt:xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 0 to 65°F (-17.8 to 18.3°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is
44.0°F (6.7°C).
As shown above, the second line of a setting display normally says:
“Press (+)(-) to Change Setting”
However, the following is displayed as the second line of the display if an attempt is made to increment the setpoint above the end of the setpoint range:
“Top of Range, Press (-) to Change”
The following is displayed as the second line of the
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Hour, Press (+)(-) & (Enter)
display if an attempt is made to decrement the display below the end of the setpoint range:
“Bottom of Range, Press (+) to Change”
The following is displayed as the second line of the display if a key other than <+>, <->, <Enter>, or
Current Time/Date HH:MM xm Mon XX,XXXX
To Change Minute,Press (+)(-) &(Enter)
<Cancel> is pressed after <+> or <-> is pressed:
“Press (+)(-)(Enter)(Cancel) to Advance”
The exception to the above message is when the <Stop> key is pressed. <Stop> is always active.
Information Manual 21
Page 27
Operator Settings
Other messages are displayed on the second line of the display for special cases as noted below in association with the affected setpoint display.
When the Front Panel Chilled Water Setpoint is within 1.7°F of the Leaving Water Temperature Cutout Setpoint, the second line of this display will read:
“Limited by Cutout Setpt, (+) to Change”
Front Panel Hot Water Setpoint
The Front Panel Hot Water Setpoint is only displayed when the Hot water option is Installed.
Front Panel Hot Wtr Setpt: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 85 to 140°F (37.8 to 60.0°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is 130°F (54.4°C).
Front Panel Current Limit Setpoint
Control Type
The following will be displayed only if the Hot Water Control Option is Installed.
Control Type is: [control]
Press (+)(-) to Change Setting
Possible values of [control] are: Chilled Water (Factory Default), Hot Water, and Ext. Hot/Chilled Wtr Input.
Free Cooling
The free cooling enable screen is displayed only if the free cooling option is installed.
Free Cooling: [Status]
Press (+)(-) to Change Setting
Possible values are: Disable (Factory Default) and Enable.
Chilled Water Reset Type
Front Panel Current Limit Stpt: xxx %
Press (+)(-) to Change Setting
Range of values is 40 to 100% in increments of 1 %. Factory Default is 100%.
Print Report
This screen is shown only when the Printer Option is Installed.
Press (Enter) to Print Report
Press (Next)(Previous) To Continue
When <Enter> is pushed, a 2 second message appears as shown below and then returns to the above screen.
The Print Command is Being
Sent to the Printer
Chilled Water Reset Type: [type]
Press (+)(-) to Change Setting
The possible values for [type] are: Disable (Factory Default), Return, Constant Return, and Outdoor Air.
If either Disable or Constant Return are selected, the remaining chilled water reset displays are skipped by the CLD. If either Return or Outdoor Air are selected, the first word of the remaining chilled water reset displays will be the type of reset.
Help Notes:
1 When CWR is enabled, the UCM will step to CWS
at a rate of 1°F every five minutes.
2 Constant Return is a short version of Return
CWR; it will reset the leaving chilled water setpoint to provide a constant entering water temperature. The reset ratio defaults to 100%, start rest point to design delta T and max reset setpoint to design.
3 Chilled water is reset based on either return water
temperature or outdoor air temperature.
4 This screen does not appear when the chiller is
22 CVHE-CLD-1A
Page 28
Operator Settings
under Duplex Control and it is Compressor B.
Reset Ratio
This is the aggressive value. A higher number is a quicker response.
[type] Reset Ratio: xxx %
Press (+)(-) to Change Setting
The values for Reset Ratio for each of the reset types are:
Reset
Reset
Type
Return 10 to
Outdoor 80 to -80% 1% 1% 10%
Ratio
Range
120%
Increment
(Eng. units)
1% 1% 50%
Increment
(SI)
Default
Value
Start Reset Setpoint
This is the Delta T the unit is trying to maintain.
Press (+)(-) to Change Setting
The values for Maximum Reset for each of the reset types are:
Maximum
Reset
Type
Return 0 to 20°F
Outdoor 0 to 20°F
Reset
Range
(0.1 to
11.1°C)
(0.1 to
11.1°C)
Increment
(Eng.
units)
1°F 1°C 5°F
1°F 1°C 5°F
Increment
(SI)
Default
Value
(2.8°C)
(2.8°C)
Ice Building Enable
The following will be displayed only if the ice building option is installed.
Ice Building: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
[type] Start Reset Setpoint: xxx.x F
Press (+)(-) to Change Setting
The values for Start Reset for each of the reset types are:
Start
Reset
Type
Return 4 to 30°F
Outdoor 50 to
Reset
Range
(2.2 to
16.7°C)
130°F (10 to 54.4°C)
Increment
(Eng. units)
1°F 1°C 10°F
1°F 1°C 90°F
Increment
(SI)
Default
Value
(5.6°C)
(32.2°C)
Maximum Reset Setpoint
Controllable Maximum Reset value. Allows a reset “Up” of this value. The chilled water is maintained between the leaving chilled water setpoint and the new reset value.
[type] Max Reset Setpoint: xxx.x F
Front Panel Ice Termination Setpoint
The following will be displayed only if ice building option is installed.
Panel Ice Termination Setpoint:xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 20.0 to 32.0°F (-6.7 to 0.0°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is
27.0°F (-2.8°C).
Ice Making To Normal Cooling Transition Timer
The following will be displayed only if the ice building option is installed. This allows for a timed idle/stop period for (X) minutes when coming out of ice before going into the cooling mode (timed by Chiller).
Ice-To-Normal Cooling Timer: xx min
Press (+)(-) to Change Setting
Information Manual 23
Page 29
Operator Settings
Range of values is 0 to 10 min. Factory Default is 5 min.
Chilled Water Setpoint Source
If the Tracer Option is installed, the word “Default” will appear in front of the setpoint source.
[Default] Chilled Water Setpoint Source:
[source]
Possible values of [source] are: Front Panel (Factory Default) and External Source (This choice shows up only if the External Chilled Water Setpoint is Installed at the Machine Configuration menu.).
Note: There is a Tracer installed screen in the Machine configuration menu. If Tracer does not choose to write a setpoint then the “default” setpoint source is used, e.g. Front Panel.
Current Limit Setpoint Source
If the Tracer Option is installed, the word “Default” will appear in front of the setpoint source.
Possible values of [source] are: Front Panel (Factory Default) and External Source (This choice shows up only if the External Hot Water Setpoint is Installed at the Machine Configuration menu.)
Note: There is a Tracer installed screen in the Machine configuration menu. If Tracer does not choose to write a setpoint then the “default” setpoint source is used, e.g. Front Panel.
Ice Termination Setpoint Source
The following will be displayed only if the Ice Building Option is installed.
If the Tracer Option is installed, the word “Default” will appear in front of the setpoint source.
[Default] Ice Termination Setpoint Source:
[source]
Possible values of [source] are: Front Panel (Factory Default).
Note: There is a Tracer installed screen in the Machine configuration menu. If Tracer does not choose to write a setpoint then the “default” setpoint source is used, e.g. Front Panel.
[Default] Current Limit Setpoint Source:
[source]
Possible values of [source] are: Front Panel (Factory Default), and External Source. (This choice shows up only if the External Current Limit Setpoint is Installed at the Machine Configuration menu.)
Note: There is a Tracer installed screen in the Machine configuration menu. If Tracer does not choose to write a setpoint then the “default” setpoint source is used, e.g. Front Panel.
Hot Water Setpoint Source
If the Tracer Option is installed, the word “Default” will appear in front of the setpoint source.
[Default] Hot Water Setpoint Source:
[source]
Outdoor Air Temperature Source
If the Tracer is installed the Tracer Outdoor Air Temp. is both used and displayed. If no Tracer is installed the chiller module outdoor air temperature sensor is used. If no sensor is installed, dashes are displayed on the display of Outdoor Air Temperature.
Setpoint Source Override
Setpoint Source Override:
[source]
Possible values of [source] are: “None” (Factory Default), “Use Front Panel Setpoints”, “Override Tracer, and Use Default Setpoints” (Available only if Tracer Option installed).
24 CVHE-CLD-1A
Page 30
Service Settings (Non Password Protected Service Settings Group)
Service Settings (Non Password Protected Service Settings Group)
Important! FACTORY DEFAULT SETTINGS: Menu items that are programmable using the keypad may have a selectable choice that is listed as Factory Default. This Factory Default setting is the software default that is initially factory-programmed for a new module assembly and may NOT be the correct setting for a specific operating chiller. Always review all settings when any module is replaced to verify that the settings agree with the desired settings that were selected at initial startup or programmed at the factory.
The Service settings menu has three distinct grouping of items within it. The first group is the non­password protected group that consists of all of the settings, feature enables, setpoints etc., that are benign; while they are unlikely to be changed often by a user or operator, changes in them do not seriously effect the standard protection or reliability of the chiller.
The other two groupings are protected, each with a separate password. These two groups are for changing parameters and settings regarding field commissioning and fundamental protection and control of the chiller subsystems (Field Startup) or for programming of the UCM as to how the specific chiller was built in the Factory (Machine Configuration). Once properly set, the items in these protected menus should never be changed again without specific knowledge of the effects of the changes. In rare instances, certain field problems may be corrected by making changes in these protected menus but certain aspects of chiller reliability may be compromised. The main reason these are accessible at all, is for field commissioning and to allow for the field programming of service replacement UCMs.
Two additional password protected menus are available in the Service Settings group if the IPC Refrigerant Monitor is installed. The Refrigerant Monitor Settings Group and the Refrigerant Monitor Calibration Group are used to configure the IPC Refrigerant Monitor.
Service Setting Group Heading
Service Settings: Basic Setups
Press (Next)(Previous) To Continue
Menu Settings Password
If the Menu Settings Password is Enabled in the Service Setup Group, following each setting group heading the following will be displayed:
Settings In This Menu Are [status]
[password message]
Likewise, if the Menu Settings Password is Disabled in the Service Setup Group, the above screen will not appear.
The possible values for status are “Locked” or “Unlocked”. If the password status is locked, the password message will be “Enter Password to Unlock”. The user will then depress (-)(+)(-)(+)(-)(+) followed by the <Enter> key. The password keystrokes will be echoed to the screen as a visual aide. The last six keystrokes represent the current password, and up to twenty keystrokes can be entered. An incorrect password, or the twenty-first keystroke will result in the password message “Invalid Password”.
If the password status is unlocked, the password message will be “Press (Enter) to Lock”. Pressing <Enter> will lock all of the setpoint menus. Likewise, if the password status is locked and the correct password is entered, all of the setpoint menus will be unlocked.
Whenever a password is in use the “Press (+)(-) to change setting” message will be suppressed on all setpoint screens. Any attempt to change a setpoint will result in the message “Setting is Locked” being displayed for 1 second. The password once entered will remain valid until canceled.
Information Manual 25
Page 31
Service Settings (Non Password Protected Service Settings Group)
Service Settings Key
Menu Structure Under
Figure 3
Service Settings Group
The Service Settings Key
(+)(+)(-)(-)(+)(+)
(+)(-)(+)(-)(+)(-)
(-)(-)(+)(+)(-)(-)
(-)(+)(-)(-)(+)(+)
or
(+)(+)(-)(+)(-)(-)
Password Screen
Password Screen
Password Screen
Password Screen
Field Startup Group
Machine Config. Group
Refrigerant Monitor Settings Group
Refrigerant Monitor Calibration Groups
Keypad/Display Lockout
Password will be required to Unlock
This display only appears if the keypad lockout feature is enabled.
If the <Enter> key is pressed to lock the keypad, the following message is displayed, and all further input from the keypad is ignored, including the <Stop> key,
Press (Enter) to Lock Display & Keypad
26 CVHE-CLD-1A
until the password is entered. The password consists
Page 32
Service Settings (Non Password Protected Service Settings Group)
of pressing the <Previous> and <Enter> keys at the same time.
******DISPLAY AND KEYPAD ARE LOCKED******
********ENTER PASSWORD TO UNLOCK********
If the keypad is locked and the password is entered, the display will go to the Chiller Operating Mode display of the Chiller Report.
Language Setting
Language: xxxxxxxx
Press (+)(-) to Change Setting
Possible Language Selections for the CLD are: English (Factory Default), Francais, Deutsche, Espanol, Nippon (also known as Katakana (uses Japanese Characters), Italian, Nederland, and CODED. Possible Language Selections for the CCCLD are: English (Factory Default), Traditional Chinese, Simplified Chinese, Korean, Thai, and Japanese.
Display Menu Headings Enable
Display Menu Headings: [d/e]
Press (+)(-) to Change Setting
The Factory Default value is Enabled. If disabled the Menu Headings in each Menu or Group do not appear.
Clear Custom Menu
Press (Enter) To
Clear The Custom Menu
When <Enter> is pushed a 2 second message appears as shown below and then returns to above screen.
Custom Menu Has Been Cleared
Differential to Start Setpoint
Display Units
Display Units: [Type]
Press (+)(-) to Change Setting
Possible values of [Type] are: English (Factory Default) and SI.
Decimal Places Displayed Setpoint
Decimal Places Displayed: [Status]
Press (+)(-) to Change Setting
The choices for Status are: XXX.X (Factory Default) and XXX.
Differential to Start Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 1 to 10°F (0.5 to 5.5°C) in increments of 1 or 0.1°F or C depending on the Service Setup Screen xxx or xxx.x. Factory Default is 5°F (2.8°C).
Differential to Stop Setpoint
Differential to Stop Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 1 to 10°F (0.5 to 5.5°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is 5°F (2.8°C).
Information Manual 27
Page 33
Service Settings (Non Password Protected Service Settings Group)
Evap/Cond Pump Off Delay Time
Evap Pump Off Delay: xxx Min
Press (+)(-) to Change Setting
Range of values is 0 to 30 minutes in increments of 1 Minute. Factory Default is 1 Minute.
If the current running mode is hot water control state the following display is substituted for the above display:
Cond Pump Off Delay: xxx Min
Press (+)(-) to Change Setting
Printer Setups
This screen is shown only when the Printer Option is Installed.
The choices for Status are: Enable (Factory Default) and Disable.
Number of Pre-Diag Reports: xx
Press (+)(-) to Change Setting
Range of values is 1 to 5 in increments of 1. Factory Default is 5.
Diagnostic Report Interval: xx sec
Press (+)(-) to Change Setting
Range of values is 2 to 120 seconds in increments of 1 second. Factory Default is 5 seconds.
Printer, Baud Rate: [Status]
Press (+)(-) to Change Setting
The choices for Status are: 300, 1200, 2400, 4800, 9600 (Factory Default), and 19,200.
Printer Setups
(Enter) to Change : (Next) to Continue
If <Next> is pressed the following printer setup screens are skipped. If <Enter> is pressed the following screens are displayed to permit modification of the printer setups.
Print on Time Interval: [Status]
Press (+)(-) to Change Setting
The choices for Status are: Enable (Factory Default) and Disable.
Print Time Interval: xxx Hours
Press (+)(-) to Change Setting
Range of values is 1 to 24 Hours in increments of 1 Hour. Factory Default is 8 Hours.
Print on Diagnostic: [Status]
Press (+)(-) to Change Setting
Printer, Parity: [Status]
Press (+)(-) to Change Setting
The choices for Status are: None (Factory Default), Odd, and Even.
Printer, Data Bits: [Status]
Press (+)(-) to Change Setting
The choices for Status are: 8 (Factory Default) and 7.
Printer, Stop Bits: [Status]
Press (+)(-) to Change Setting
The choices for Status are: 1 (Factory Default) and 2.
Printer Handshaking: [Status]
Press (+)(-) to Change Setting
The choices for Status are: XON/XOFF (Factory Default), DTR, RTS, and None.
28 CVHE-CLD-1A
Page 34
Clear Restart Inhibit Timer
Press (Enter) to
Clear the Restart Inhibit Timer
When <Enter> is pushed, a 2 second message appears as shown below and then returns to above screen.
Restart Inhibit Timer Has Been Cleared
Service Settings (Non Password Protected Service Settings Group)
Information Manual 29
Page 35
Field Start-up
Field Start-up
Important! FACTORY DEFAULT SETTINGS: Menu items that are programmable using the keypad may have a selectable choice that is listed as Factory Default. This Factory Default setting is the software default that is initially factory-programmed for a new module assembly and may NOT be the correct setting for a specific operating chiller. Always review all settings when any module is replaced to verify that the settings agree with the desired settings that were selected at initial startup or programmed at the factory.
Field Startup
The Field Startup Group password is + + - - + + <Enter>. The Field Startup Group contains items that are primarily associated with Field Commissioning of the chiller as well as the fundamental control and protection of the chiller subsystems. If the field startup password is entered, the display goes to the menu defined below. If a key is not pressed every 10 minutes in this password protected menu, the display returns to the Chiller Operating Mode display of the Chiller Report, and the password must be entered again to return to this menu.
Field Start-up Group Heading
in this condition, both the <Stop> and <Auto> keys do not function.
Keypad/Display Lock Feature: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
When the keypad lock feature is Disabled, the keypad lock display does not appear in the non­password protected area of the Service Settings menu and the Keypad/Display cannot be locked. When the keypad/display lock feature is Enabled, the keypad lock display does appear in the Service Settings menu so the keypad can be locked.
Menu Settings Password Enable
The Menu Settings Password permits the Settings in each of the menus to be password protected. All Report Menus and Setting Menus can still be viewed at any time if this feature is either Enabled or Disabled; the <Stop> and <Auto> keys also remain active. If this feature is Enabled, then all Menu Settings are password protected.
Menu Settings Password Feature: [d/e]
Field Start-up Group Settings
Press (Next)(Previous) To Continue
This header appears when the headers do not appear in the Service Settings menu.
Keypad/Display Lock Feature Enable
This feature permits the entire Keypad and Display to be locked out. A message appears on the screen to describe this condition. No access is permitted to either the Report screens or the Setting Screens when this feature is both Enabled here and Locked at the Service Settings Menu. It is important to note that
30 CVHE-CLD-1A
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
When the feature is Disabled, the Menu Setting Password display does not appear at the top of each of the Settings Menus and the Menu Settings cannot be password protected. When the Menu Setting Password feature is Enabled, the Menu Settings Password display appears just below each of the Settings Menu Headers so the settings can be changed if the proper password is entered.
Page 36
Field Start-up
ICS Address
ICS Address: xx
Press (+)(-) to Change Setting
Range of values is 1 to 127 in increments of 1. Factory Default is 65.
Power Up Start Delay Time
Power Up Start Delay Time: xxx sec
Press (+)(-) to Change Setting
Range of values is 0 to 600 seconds in increments of
1. Factory Default is 0 sec.
Design Delta Temperature Setpoint
Design Delta Temp Setpoint: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 4 to 30°F (2.2 to 16.7°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is 10°F (5.5°C).
When this setpoint is adjusted below 35.3°F the following is displayed on the second line:
“Warning: Adequate Antifreeze Required”.
Low Refrigerant Temperature Cutout Setpoint
Low Rfgt Temp Cutout Setpt: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is -35 to 36°F (-37.2 to 2.2°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. The Factory Default is 32.0°F (0.0°C).
Low Evaporator Water Flow Warning Setpoint
The following will be displayed only if the Differential Water Sensing Option is installed.
Low Evap Flow Warning: xx.x gpm/ton
Press (+)(-) to Change Setting
Range of values is 0.0 to 4.0 gpm/ton (0.0 to 15.1 lpm/ton) in increments of 0.1. Factory Default is 1.2 gpm/ton (4.5 lpm/ton).
Leaving Water Temperature Cutout
Condenser Limit Setpoint
Setpoint
Condenser Limit Setpoint: xx % HPC
Lvg Wtr Temp Cutout Setpoint:xxx.x f/c
Press (+)(-) to Change Setting
Range of values is -10 to 36°F (-23.3 to 2.2°C) in increments of 1 or 0.1 °F or °C depending on the Service Setup Screen xxx or xxx.x. The Factory Default is 36.0°F (2.2°C).
When this setpoint is within 1.7°F of the Front Panel Chilled Water Setpoint, the Front Panel Chilled Water Setpoint is increased along with this setpoint to maintain the differential. A message will be displayed for 2 seconds to indicate that the FPCW setpoint has been increased.
Information Manual 31
Press (+)(-) to Change Setting
Range of values is 80 to 120% in increments of 1%. Factory Default is 93%.
Maximum Restart Inhibit (RI) Timer Setting
Maximum RI Timer: xxx Minutes
Press (+)(-) to Change Setting
The Range of values is 30 to 60 Minutes in increments of 1 Minute. Factory Default is 60 Minutes.
Page 37
Field Start-up
Purge Control/Type
Purge Control/Type: [Type]
Press (+)(-) to Change Setting
Possible values of [Type] are: Micro Purge (Factory Default) and Stand-Alone Purge.
Purge Service Log Reset
The following screen(s) shall be suppressed if the selected Purge Control/Type is “Stand-Alone Purge”.
Service Log: Press (Enter) to Reset
Purge Pumpout Time: xxxxxxxx.x Pumpout Min
Service Log: Press (Enter) to Reset
Time Since Last Reset: xxxxx Cal Days
Note: Resetting in either screen above will reset both fields of data to Zero.
Purge Maximum Pumpout Rate
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Press (+)(-) to Change Setting
Range of values is 1 to 72 Hours in increments of 1 Hour. Factory Default is 0 Hours.
Purge Low Chiller Sat. Cond. Liquid Temp. Protection Enable
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Low Liquid Temp Inhibit:[d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
Purge Low Chiller Sat. Cond. Temp Setpoint
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Prg Low Liquid Temp Inhibit Setpt xx.x f/c
Press (+)(-) to Change Setting
Range of values is 32 to 50°F(0.0 to 10.0°C) in increments of 1 or 0.1°F or°C depending on the Service Setup Screen xxx or xxx.x. Factory Default is 40°F (4.4°C).
Purge Max Pumpout Rate: xx Min/24 Hrs
Press (+)(-) to Change Setting
Range of values is 1 to 100 Minutes/24 Hrs in increments of 1 Minute/24 Hrs. Factory Default is 20 Minutes/24 Hrs.
Purge Service Excessive Pumpout Override Timer
The following screen(s) does not appear if the selected Purge Control/Type is “Stand-Alone Purge.”
Purge Disable Pumpout Alarm for: xx Hrs
32 CVHE-CLD-1A
Surge Protection Enable
Surge Protection: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable (Factory Default). Surge protection is based on motor current fluctuation.
Page 38
Field Start-up
Under/Over Voltage Protection Enable
This screen does not appear if the Line Voltage Sensing Option is not installed or Compressor Power Source is Engine/Generator.
Line voltage above + 10% of nominal. (Must hold = + 10 % of nominal. Must trip = + 15 % of nominal. Reset differential = min. of 2% and max. of 4%. Time to trip = minimum of 1 min. 10 sec. and maximum of 5 min. 20 seconds).
Under/Over Voltage Protection: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
Note: Under/Over Voltage Protection is activated only if Under/Over Voltage Protection is enable and Line Voltage Sensing Option is Installed.
Phase Reversal Protection Enable
This screen does not appear if the starter type is “Adaptive Frequency” or “AFDB.”
Phase Reversal Protection: [d/e]
Press (+)(-) to Change Setting
Momentary Power Loss (MPL) Protection Enable
This screen does not appear if the starter type is “Adaptive Frequency” or “AFDB.” or Compressor Power Source is Engine/Generator.
Momentary Power Loss Protection: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable (Factory Default).
For MPL, on every power down, the reset inhibit timer is reset to 30 seconds if the motor temperature is <165°F and 15 minutes if the motor temperature is > or = to 165°F.
Enhanced Oil Temp. Protection
This screen does not appear if the starter type is “Adaptive Frequency” or “AFDB.
When enhanced oil protection is enabled, the oil heater relay is energized at 140.5ºF (60.3ºC) and de­energized at 145.5ºF (63.1ºC). The low oil temperature cutout “setpoint” is equal to the saturated evaporator refrigerant temperature plus 30ºF (16.6ºC) or 100 ºF (37.8ºC) which ever is larger.”
Possible values of [d/e] are: Disable and Enable (Factory Default).
A phase reversal is detected on the incoming current. On a compressor startup, the phase reversal logic must detect and trip in 0.7 seconds.
Phase Unbalance Limit Enable
Phase Unbalance Limit: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable (Factory Default).
The RLA of the motor is derated by resetting the active current limit. The trip point is a 30% phase unbalance for 90 seconds.
Information Manual 33
Enhanced Oil Temp Protection: [option]
Press (+)(-) to Change Setting
Possible options are: Disable and Enable (Factory Default).
Oil Temp Setpoint
This screen does not appear when Enhanced Oil Temperature Protection is enabled.
Oil Temp SetPoint: xxx.x f/c
Press (+)(-) to Change Setting
The range of values is 100°F to 160°F (37.8 to
71.1°C) in increments of 1 or 0.1°F or °C, depending
Page 39
Field Start-up
on the Service Setup Screen xxx or xxx.x. Factory Default is 143°F (61.9°C).
Low Oil Temp Cutout
This screen does not appear when Enhanced Oil Temperature Protection is enabled.
Low Oil Temp Cutout: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 80 to 140°F (26.7 to 60.0°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is 95°F (35.0°C).
Low Oil Temp Start Inhibit Differential
This screen only appears when Enhanced Oil Temperature Protection is enabled.
External Base Loading Enable
External Base Loading: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
Soft Load Control Enable
Soft Load Control: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
Soft Load Starting Current Limit
Low Oil Temp Start Inhibit Diff: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 20 to 30°F (11.1 to 16.7°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is
27.5°F (15.3°C).
High Discharge Temp Cutout
This screen is displayed only if the Discharge Sensor Option is installed.
High Discharge Temp Cutout: xxx.x f/c
Press (+)(-) to Change Setting
Range of values is 170 to 220°F (76.6 to 104.4°C) in increments of 1 or 0.1°F or °C depending on the Service Setup Screen xxx or xxx.x. Factory Default is 200°F (93.3°C).
Soft Load Starting Current Limit: xx %
Press (+)(-) to Change Setting
Range of values is 40 to 100% in increments of 1%. Factory Default is 100%.
Soft Load Current Limit Rate Of Change
Soft Load Current Limit Rate:x.x %/min
Press (+)(-) to Change Setting
Range of values is 0.5 to 5%/Min in increments of 1 or 0.1%/Min depending on the Service Setup Screen xxx or xxx.x. Factory Default is 5%/Min.
Soft Load Lvng Wtr Temp Rate of Change
Soft Load Lvg Water Rate: x.x f/c/min
Press (+)(-) to Change Setting
Range of values is 0.5 to 5°F/Min (0.3 to 2.8°C/Min) in increments of 1 or 0.1°F/Min depending on the
34 CVHE-CLD-1A
Page 40
Field Start-up
Service Setup Screen xxx or xxx.x. Factory Default is 5°F/Min (2.8°C/MIn).
Hot Gas Bypass Enable
This screen does not appear when the hot gas bypass option is not installed.
Hot Gas Bypass Control: [d/e]
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable (Factory Default) and Enable.
HGBP Timer Enable
The following will be displayed only if HGBP is installed.
HGBP Timer: [Status]
Press (+)(-) to Change Setting
Range of values is 0 to 30% in increments of 1%. Factory Default is 10%. This setting drives the IGVs to the target when HGBP is entered.
LWT Control Proportional Gain (Kp) Setpt
LWT Proportional Gain: xxx.x %/F
Factory Dflt is 10.0 %/F & 18.0 %/C
The range of valves is 0 to 100%/°F (0 to 180%/°C) in increments of 0.1.
LWT Control Integral Gain (Ki) Setpt
LWT Integral Gain:x.xxx %/F
Factory Dflt is 0.110 %/F & 0.198 %/C
The range of valves is 0 to 1%/°F (0 to 1.8%/°C) in increments of 0.001. The Factory Default is 0.110%/
°F (0.198%/°C).
The choices for Status are: Enable (Factory Default) and Disable (Unlmtd Time).
Maximum HGBP Time
The following will be displayed only if HGBP is Installed and the HGBP Timer is Enabled.
Maximum HGBP Time: xxx Min
Press (+)(-) to Change Setting
Range of values is 1 to 480 minutes in increments of 1 Minute. Factory Default is 30 Minutes.
HGBP Mode, Vane Target
This screen does not appear when the hot gas bypass option is not installed.
Hot Gas Bypass Mode IGV Target:xx %
Press (+)(-) to Change Setting
LWT Control Derivative Gain (Kd) Setpt
LWT Derivative Gain: xx.x %/F
Factory Dflt is 00.0 %/F & 00.0 %/C
The range of valves is 0 to 10.0%/F (0 to 18.0%/C) in increments of 0.1. The Factory Default is 00.0%/F (00.0%/C).
IGV Maximum Travel Setpt
This screen is displayed only if “Inlet Guide Vane Output” is “Stepper Motor.”
IGV Maximum Travel: xx,xxx Steps
Press (+)(-) to Change Setting
Range of values is 0 to 60,000 Steps in increments of 100 Steps. Factory Default is 50,000 Steps.
Note: this is also known as the 90 degree vane setting. You must use the value determined at the factory. Each unit is unique and must be individually set. If the factory setting cannot be determined, it
Information Manual 35
Page 41
Field Start-up
must be field-supplied by following the procedure in Trane CVHF-CSB-2B.
Guide Vane Closed Travel Stop
This screen is displayed only if “Inlet Guide Vane Output” is “Stepper Motor.”
Guide Vane Closed Travel Stop: xx.x %
Press (+)(-) to Change Setting
Range of values is 0 to 100% in increments of 1%. Factory Default is 0%.
AF Adjustable Speed Control Algorithm Enable
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Adaptive Speed Control Alg: d/e
Press (+)(-) to Change Setting
Possible values of [d/e] are: Disable and Enable (Factory Default).
AF Leaving Water Standard Deviation
AF Pressure Coefficient Constant
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Pressure Coefficient Constant: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 2000 in increments of 1. Factory Default is 800.
Note: The above value entered is 1.316 X 10^9 / (# Stages X (Impeller Dia ^2)) all divided by 1000 for the purpose of display and IPC data transmission (e.g. the actual range is 0-2,000,000 in increments of
1000). In the chiller module it is multiplied by 1000 again so it is properly scaled.
AF Re-Optimization Factor
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Re-Optimization Factor: x.xx
Press (+)(-) to Change Setting
Range of values is 0.03 to 1.00 in increments of 0.01. Factory Default is 0.30.
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Leaving Water Standard Deviation: x.x
Press (+)(-) to Change Setting
Range of values is 0.5 to 4.0 in increments of 0.1. Factory Default is 1.0.
AF Re-Optimization Timer
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Re-Optimization Timer: xxx Hrs
Press (+)(-) to Change Setting
Range of values is 1 to 255 in increments of 1. Factory Default is 24.
AF Boundary Pressure Coefficient Y
36 CVHE-CLD-1A
Page 42
Field Start-up
Intercept
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Boundary PC Y-Intercept: x.xx
Press (+)(-) to Change Setting
Range of values is 0.01 to 2.00 in increments of 0.01. Factory Default is 0.40. This setpoint is settable from this screen but also changes as the Adjustable Frequency Control Algorithm runs. It is similar to a clock setting where you set it and then it runs from there.
AF Boundary Pressure Coefficient Y Intercept Max
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Boundary PC Y-Intercept Maximum: x.xx
Press (+)(-) to Change Setting
Range of values is 0.01 to 2.00 in increments of 0.01. Factory Default is 2.00.
AF Pressure Error Deadband
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Pressure Error Deadband: x.xxx
Press (+)(-) to Change Setting
Range of values is 0.001 to 1.000 in increments of
0.001. Factory Default is 0.030.
AF Proportional Speed Gain
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Proportional Speed Gain: xxx
Press (+)(-) to Change Setting
Range of values is 1 to 100 in increments of 1. Factory Default is 50.
Minimum Capacity Timer Enable
Min Capacity Timer: [Status]
Press (+)(-) to Change Setting
The choices for Status are: Enable (Factory Default) and Disable (Unlmtd Time).
Information Manual 37
Page 43
Field Start-up
Note: On Non-Adaptive Frequency chillers this Timer times out when the chiller is at minimum IGV position and the Leaving Water Temp is below the CWS. On Adaptive Frequency chillers this Timer times out when the chiller is at minimum IGV position or minimum AF speed and LWT < CWS.
Time Permitted at Minimum Capacity
The following will be displayed only if the Minimum Capacity Timer setpoint is Enabled.
Time Permitted at Min Cap: xxx Min
Press (+)(-) to Change Setting
Range of values is 1 to 480 minutes in increments of 1 Minute. Factory Default is 30 Minutes.
Evaporator Flow Coefficient
The following is displayed only if the Differential Water Press Sensor Option is Installed.
Evap Flow Coefficient: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 3000 in increments of 5. Factory Default is 1000.
Evaporator Fluid Coefficient
The following is displayed only if the Differential Water Press Sensor Option is Installed.
Evap Fluid Coefficient: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 1000 in increments of 1. Factory Default is 400.
Note: The desired range for the above is 0.0000 to
0.1000. To put in this kind of range into the CLD, the fact that it does not start at zero represents a special case. To minimize special cases it is preferred that a multiplier of 10,000 be used in the computer that generates the number.
Condenser Flow Coefficient
The following is displayed only if the Differential Water Press Sensor Option is Installed.
Cond Flow Coefficient: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 2000 in increments of 5. Factory Default is 500.
Condenser Flow Equation Exponent
Evaporator Flow Equation Exponent
The following is displayed only if the Differential Water Press Sensor Option is Installed.
Evap Flow Equation Exponent: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 1000 in increments of 1. Factory Default is 600.
Note: The desired range for the above is 0.5000 to
0.6000. To put in this kind of range into the CLD, the fact that it does not start at zero represents a special case. To minimize special cases it is preferred that a multiplier of 10,000 and a offset of 5000 be used in the computer that generates the number.
38 CVHE-CLD-1A
The following is displayed only if the Differential Water Press Sensor Option is Installed.
Cond Flow Equation Exponent: xxxx
Press (+)(-) to Change Setting
Range of values is 0 to 1000 in increments of 1. Factory Default is 600.
Note: The desired range for the above is 0.5000 to
0.6000. To put in this kind of range into the CLD, the fact that it does not start at zero represents a special case. To minimize special cases it is preferred that a multiplier of 10,000 and a offset of 5000 be used in the computer that generates the number.
Page 44
Field Start-up
Local Atmospheric Pressure
Local Atmospheric Pressure: xx.x psia/kpa
Press (+)(-) to Change Setting
The range of settings is 10 to 16 psig in increments of 1 or 0.1 psig or kPa depending on the Service Setup Screen xxx or xxx.x. The Factory Default is
14.7 psig.
Refrigerant Pressure Analog Output Option
Rfgt Pressure Output Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: % Cond (Factory Default) and Delta.
Min Delta Pressure Calibration
The following is displayed only if the “Refrigerant Pressure Analog Output Option” is set to “Delta”.
Note: 6.8948 kPa = 1 psi.
IGV Stroke Time
The following is displayed only if the “Inlet Guide Vane Output” is set to “Pulsed”.
Inlet Guide Vane Stroke Time: XXX Sec
Press (+)(-) to Change Setting
The range of values is 15 to 100 seconds in increments of 1 second. Default is 45 seconds.
Low Differential Oil Pressure Cutout
This screen is displayed only if the “Oil Pressure Protection” is “Transducer”.
Low Diff Oil Press Cutout: XX psid/kpa
Press (+)(-) to Change Setting
The range of values is 9 to 35 psid in increments of 1 psid. Default is 12 psid.
Check Oil Filter Diagnostic
This screen is available only if differential oil pressure transducer(s) are installed.
Min Delta Press Calib (2 VDC):XXXXPSID/kPa
Press (+)(-) to Change Setting
The range of values is 0-400 psid (0-2758 kPa) in increments of 1 psid/kPa. Factory Default is 0 psid (0 kPa).
Note: 6.8948 kPa = 1 psi.
Max Delta Pressure Calibration
The following is displayed only if the “Refrigerant Pressure Analog Output Option” is set to “Delta”.
Max Delta PressCalib (10 VDC):XXXXPSID/kPa
Press (+)(-) to Change Setting
The range of values is 1-400 psid (7-2758 kPa) in increments of 1 psid/kPa. Factory Default is 30 psid (207 kPa).
Check Oil Filter Diagnostic: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: Disable (Factory Default) and Enable.
Check Oil Filter Setpoint
This screen is displayed only if differential oil pressure transducer(s) are installed and check oil filter diagnostic is enabled.
Check Oil Filter Setpt: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: 9 to 60 psid in 1 psid increments. Factory Default is 15 psid.
Information Manual 39
Page 45
Field Start-up
Evap Leaving Water Temp Offset
Evap Leaving Water Temp Offset:[setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: -2.0°F to 2.0°F in
0.1°F increments (-/+ 1.1°C in 0.1°C increments). Factory Default is 0.0°F.
Saturated Evap Rfgt Temp Offset
Saturated Evap Rfgt Temp Offset: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: -2.0°F to 2.0°F in
0.1°F increments (-/+ 1.1°C in 0.1°C increments). Factory Default is 0.0°F.
Water Pressure Calibration
The following menus is displayed only if the “Diff Wtr Press Sensor” setpoint is set to “Installed, <= 150 psig.”
This non-zero value shall return to 0.0 psid (kPa) when the water pressure calibration is completed.
Water Pressure Calibration: [setting]
Press (+)(-) to Change Setting
Possible values of [setting] are: Auto (Factory Default) and Manual
If the above menu is set to “Manual,” the following two menus are displayed.
Measured Evap Diff Wtr Press: X.X PSID/kPa
Press (+)(-) to Change Setting
Possible values is 0 to 25 psid (0 to 172.4 kPa) in 0.1 psid (kPa) increments. Factory Default is 0.0 psid (kPa).
Measured Cond Diff Wtr Press: X.X PSID/kPa
Press (+)(-) to Change Setting
Possible values is 0 to 25 psid (0 to 172.4 kPa) in 0.1 psid (kPa) increments. Factory Default is 0.0 psid (kPa).
The value displayed in the preceding two menus shall normally be 0.0 psid (kPa). When a manual calibration of the evaporator or condenser water pressure is desired, the measured differential pressure shall be entered in the appropriate menu.
40 CVHE-CLD-1A
Page 46
Machine Configuration
Machine Configuration
Important! FACTORY DEFAULT SETTINGS: Menu items that are programmable using the keypad may have a selectable choice that is listed as Factory Default. This Factory Default setting is the software default that is initially factory-programmed for a new module assembly and may NOT be the correct setting for a specific operating chiller. Always review all settings when any module is replaced to verify that the settings agree with the desired settings that were selected at initial startup or programmed at the factory.
Service Settings - Machine Configuration
The Machine Configuration password is + - + - + ­<Enter>. If the machine configuration password is entered, the display goes to the menu defined below. If a key is not pressed every 10 minutes in this password protected menu, the display returns to the Chiller Operating Mode display of the Chiller Report, and the password must be entered again to return to this menu.
Machine Configuration Group Heading
Unit Type
Unit Type: [type]
Press (+)(-) to Change Setting
Unit type will default to one of three chiller types. The default unit type will limit the selections to chillers of that type.
When the Factory Default is CVHE, possible values of unit type are: CVHE, CVGF, FastPak water­cooled, FastPak air cooled, CVHG, CVHF, CVHB, CVGE, and CVGG.
Nominal Unit Tons
Nominal Unit Tons: [tons]
Press (+)(-) to Change Setting
Possible values of [tons] are “100” through “1800" in 10 ton increments. Factory Default is 500 tons.
Machine Configuration Group Settings
Press (Next)(Previous) To Continue
This header appears when the headers do not appear in the Service Settings menu.
Unit Frequency
Unit Frequency: [Freq]
Press (+)(-) to Change Setting
Possible values of Frequency are: 60 Hz (Factory Default) and 50 Hz.
Refrigerant Type
Refrigerant Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: R11, R123 (Factory Default), R12, R134a, Water, R22, and R113.
Refrigerant Monitor Type
Refrigerant Monitor Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: None (Factory Default), Analog interface, and IPC Interface.
Information Manual 41
Page 47
Machine Configuration
Starter Type
Starter Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: Undefined, Adaptive Frequency (AFDA), Y Delta (Factory Default), X Line, Solid State (C515 Series), Auto Transformer, and Primary Reactor, AFDB, Solid State (SMCPP) (Standalone for FastPak only).
Startup Contactor Test - Y-D Starters Only
This screen shall be displayed only when the starter type is Y-Delta.
Level 2 ContactorIntegrityTest: [d/e]
Press (+)(-) to Change Setting
Select the Motor Heating Constant using the following table:
NTON
230-320 190-270 30 Min
360-500 300-420 35 Min
560-800 470-660 40 Min
890-1280 740-1040 45 Min
Motor Heating
Constant60 Hz 50 Hz
Current Overload Setting #1
Current Overload Setting #1: xxxxxxxx
Press (+)(-) to Change Setting
The range of values is Decimal 00 through 31. Factory Default is 00. Factory set per nameplate.
Possible values of [d/e] are: Disable (Factory Default) and Enable. This test checks for welded contactors before every start.
Rated Load Amps
Rated Load Amps: xxxx Amps
Press (+)(-) to Change Setting
The range of values is 0-2500 in 1 amp increments. Factory Default is 500 Amps.
Motor Heating Constant
Motor Heating Constant Setpt: xxx Min
Press (+)(-) to Change Setting
The range of values XXX is 0 to 100 Minutes in 1 Minute increments. Factory Default is 25 Minutes.
Current Overload Setting #2
Current Overload Setting #2: xxxxxxxx
Press (+)(-) to Change Setting
The range of values is Decimal 224 through 255. Factory Default is 255. For security purposes the second setting is the 8-bit one's complement of the first setting above. The current overload settings establish the running current protection.
Procedure For Selecting Current Overload Settings for UCP2
1 Determine the Rated Load Amps (RLA) from the
Unit Nameplate.
2 Refer to Table 2 or Table 3 as follows:
Select Table 2 if any of the following conditions are met:
q the unit has a unit mounted starter with an RLA
less than 936 Amps.
q The unit has a 24" wide control panel; no unit
mounted starter, and RLA less the 936 Amps.
42 CVHE-CLD-1A
Page 48
Machine Configuration
q The starter has a single CT/phase wired directly
to the starter module.
Select Table 3 if any of the following conditions are met:
q The unit has an RLA over 935 Amps.
q The unit has a 38" wide “Starter By Others”
control panel.
q The starter has two CTs/phase wired to the starter
module (greater than 600 volts).
3 Using Table 2 or Table 3 (determined from Step
2), determine the CT Meter Scale Rating based on the RLA from Step 1.
4 Calculate the CT factor using one of the following
two equations:
If Table 2 was used: CT Factor = (Motor RLA/CT Meter Scale Rating) x 100
If Table 3 was used: CT Factor = (Motor RLA/CT Meter Scale Rating) x 139
5 Refer to Table 4 . Determine Current Overload
Settings #1 and #2 based on the CT Factor calculated in Step 4.
Table 2 CT Factor = (Motor RLA/CT Motor RLA/CT Meter Scale Rating) X 100
Motor RLA CT Part No. Ext
34-50A
51-67A 10 75A
68-100A 01 100A
101-134A 02 150A
135-184A 03 200A
185-267A 04 275A
268-334A 05 400A
335-467A 06 500A
468-667A 07 700A
668-935A 08 1000A
x13580253
CT Meter Scale
Rating
09 50A
Verify Current Overload Setting #1.
Verify Current Overload Setting #2.
Information Manual 43
Page 49
Machine Configuration
Table 3 CT Factor = (Motor RLA/CT Meter Scale Rating) X 139
Line CT Part
No. Ext
X13580272 -01 50:5 X1 to X2 3 8.0 – 11.9 16.7
X13580271 -01 100:5 48.0 – 72.0 100
X13580048 150:5 72.0 – 86.3 150
X13580047 -01 1800:5 X1 to X2 864.0 – 1007.9 1800
Line CT
Ratio
-02 75:5 2 18.0 – 23.9 37.5
-01 50:5
-02 75:5 36.0 – 47.9 75
180:5 X1 to X3 86.4 – 95.9 180
200:5 X1 to X4 96.0 – 119.9 200
-02 250:5 X1 to X2 120.0 – 143.9 250
300:5 X1 to X3 144.0 – 167.9 300
350:5 X1 to X4 168.0 – 191.9 350
-03 400:5 X1 to X2 192.0 – 239.9 400
500:5 X1 to X3 240.0 – 287.9 500
600:5 X1 to X4 288.0 – 335.9 600
-04 700:5 X1 to X2 336.0 – 383.9 700
800:5 X1 to X3 384.0 – 479.9 800
1000:5 X1 to X4 480.0 – 575.9 1000
-05 1200:5 X1 to X2 576.0 – 719.9 1200
1500:5 X1 to X3 720.0 – 863.9 1500
2100:5 X1 to X3 1008.0 – 1199.9 2100
2500:5 X1 to X4 1200.0 – 1800 2500
-02 1000:5 X1 to X2 480.0 – 575.9 1000
1200:5 X1 to X3 576.0 – 719.9 1200
1500:5 X2 to X4 720.0 – 863.9 1500
CT Ter.
Conn
No. of Prim.
Turns RLA Ranges
2 12.0 – 17.9 25.0
24.0 – 35.9 50
1
Meter Scale
44 CVHE-CLD-1A
Page 50
Table 4 CT Factor, Current Overload Settings #1 and #2
Machine Configuration
Current
CT
Factor
66 00 255 77 11 244 88 22 233
67 01 254 78 12 243 89 23 232
68 02 253 79 14 241 90 24 231
69 03 252 80 15 240 91 25 230
70 04 251 81 16 239 92 25 230
71 06 249 82 17 238 93 26 229
72 06 248 83 18 237 94 27 228
73 07 248 84 19 236 95 28 227
74 08 247 85 20 235 96 28 227
75 09 246 86 21 234 97 29 226
76 10 245 87 22 233 98 30 225
Overload
Setting #1
Current
Overload
Setting #2
CT
Factor
Current
Overload
Setting #1
Maximum Acceleration Timer #1
Current
Overload
Setting #2
CT
Factor
99 30 225
The range of values is 191 to 249 Sec. Factory
Current
Overload
Setting #1
Default is 228 Seconds. For security purposes the second setting is the 8-bit one's complement of the
Maximum Accel Timer Setpt #1: xx Sec
Press (+)(-) to Change Setting
Timer #1 setting above. Both the Maximum Accel. Timers and the Overload Settings are not adjustable from either the Remote CLD or Tracer or any other Remote/External Device.
The range of values is 6 to 64 seconds. Factory default is 27 seconds.
Current
Overload
Setting #2
Starter Type
Undefined Contact Factory
Variable Speed 20
Y-Delta 27 (Factory Default)
X-Line 6
Sold State 20
Auto-transformer 16
Primary Reactor 11
Recommended Max. Accel.
Timer #1 Setting
Maximum Acceleration Timer #2
The maximum acceleration timers establish the starting overcurrent protection.
Maximum Accel Timer Setpt #2: xx Sec
Press (+)(-) to Change Setting
Hot Water Control Option
This screen does not appear if compressor power source is “Engine/Generator.”
Hot Water Control Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Heatsink Start Inhibit Temperature Setpoint (FastPak)
Heatsink Start Inhibit Temp: xxx.x f/c
Press <+> <-> To Change Setting
The range of values shall be 100.0 to 200.0 °F (37.8 to 93.3 °C) in increments of .1°F/°C. Default shall be 100 °F (93.3 °C).
Information Manual 45
Page 51
Machine Configuration
External Chilled Water Setpoint Option
External Chilled Wtr Setpoint:[Status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
External Current Limit Setpoint Option
External Current Limit Setpt:[Status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
External Hot Water Setpoint Option
External Hot Water Setpoint: [Status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Acceleration Time Out Action
Motor Winding RTD Type
Motor Winding RTD Type: [type]
Press (+)(-) to Change Setting
Possible values for type are: 75 Ohm at 75°F (Factory Default) and 100 Ohm at 0°C
High Pressure Cutout Setting
High Pressure Cutout Setting:xxxx Psig/kPa
Press (+)(-) to Change Setting
The range of values shall be -5-500 psig (350-3447 kPa) in increments of 5 psig/kPa. Factory Default is 15 psig (103 kPa) from -5 to 5 psig in increments of
1.
Line Voltage Sensing Option
Line Voltage Sensing Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Unit Line Voltage
Acceleration Time Out Action: [action]
Press (+)(-) to Change Setting
Possible values for “action” include: Shutdown (Factory Default) and Transition. Transition results in an IFW diagnostic.
Motor Over Temperature Protection
Motor Temp Protection: [input]
Press <+> < - > to Change Setting
Possible value of [input] are: 3 Winding Sensors, MTC Switch. Factory default is 3 Winding Sensors
46 CVHE-CLD-1A
This screen will not appear if the Line Voltage Sensing Option is not installed.
Unit Line Voltage: [volt]
Press (+)(-) to Change Setting
Possible values of [volt] are “180” through “6600” in 5 volt increments. Factory Default is 460 volts.
Page 52
Machine Configuration
Auxiliary Condenser Option
Auxiliary Condenser Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Heat Recovery Option
Heat Recovery Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Hot Gas Bypass Option
Condenser Pressure Sensor Option
Condenser Press Sensor Option:[status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Bearing Temperature Sensors Option
Bearing Temp Sensors Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Discharge Temperature Sensor Option
Hot Gas Bypass Option : [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Free Cooling Option
Inlet Guide Vane Output
Has been Set to Stepper Motor
Free Cooling Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Discharge Temp Sensor Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Ice Building Option
Ice Building Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Differential Water Press Sensing Option
Diff Wtr Press Sensor Opt: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed, <= 150 psig (1035 kPa), Installed, > 150 psig (1035 kPa), and Not Installed (Factory Default).
Information Manual 47
Page 53
Machine Configuration
This option screen applies to both the Evap and Cond differential water pressure sensors for both systems less than or equal to 150 psig (Sensors at the Chiller Module) and systems greater than 150 psig (Sensors at the Options Module).
External Analog Input Type Selection, 4-20 ma/2-10 VDC
External Setpoint Inputs: [type]
Press (+)(-) to Change Setting
Possible values for status are: 4-20ma (Factory Default) and 2-10 VDC.
Tracer Option
Tracer Option:
[status]
Press (+)(-) to Change Setting
Duplex Control Module (DCM) Option
DCM Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
IGV Output Type
Inlet Guide Vane Output: [Y]
Press (+)(-) to Change Setting
Possible values for Y are: Stepper Motor (Factory Default) and Pulsed.
If Inlet Guide Vane Output is set to Pulsed and the Hot Gas Bypass Option is currently set to Installed, the Hot Gas Bypass Option will be set to Not Installed and the following will be displayed for 3 sec to indicate the change.
Possible values for status are: Installed and Not Installed (Factory Default).
TCI Option
TCI Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Printer Option
Printer Option: [status]
Press (+)(-) to Change Setting
Possible values for status are: Installed and Not Installed (Factory Default).
Hot Gas Bypass Option
Has Been Set to Not Installed
Oil Pressure Protection
Oil Pressure Protection: [status]
Press (+)(-) to Change Setting
Possible values for [status] are: Transducer (Factory Default), and Diff Switch, Xducer & Switch.
Programmable Analog Output
Program Analog Output: [Output]
Press <+> <-> To Change Setting
Possible values of [Output] are:
Not Used % Cond Pres
% RLA Refrig Diff Pres
48 CVHE-CLD-1A
Page 54
Machine Configuration
Current Transducer at 100% RLA =
Machine LRA
Factory Default is % RLA.
Programmable Relay Outputs
The following represents three menu items and is repeated for [N] = 1, 2, or 3.
Program Relay [N]: [Relay]
Press <+> <-> To Change Setting
Possible values of [Relay] are:
Not Used Limit Warning
Comp Running Ice Making
MMR Alarm Head Relief Request
MAR Alarm Tracer Controlled
MMR + MAR Alarm Max Capacity
Factory Default for
Current Transducer at 100% RLA
The following will only be displayed if Current Transducer is set to “Other”.
Current Xducer at 100% RLA: XX.X VDC
Press <+> <-> To Change Setting
Range of values is -10.0 to -5.0 VDC in increments of
0.1 VDC
Note: Calculate setpoint as follows:
--------------------------------------X10–()
CT Span
Compressor Power Source
Cprsr Power Source: [status]
Press (+)(-) to Change Setting
[N] = 1 is MMR + MAR Alarm.
[N] = 2 is Comp Running.
[N] = 3 is Not Used.
Current Transducer Setpoint
The following will only be displayed if starter type is set to “Stand Alone - No Starter Module”.
Current Xducer: [Setting]
Press <+> <-> To Change Setting
Possible values for [Setting] are: Cutler Hammer; Other Factory Default is “Cutler Hammer”
Note: Select “Cutler Hammer” if starter has an A-1 module, otherwise select “Other”.
Possible settings for [status] are: Utility (Factory Default) and Engine/Generator.
Information Manual 49
Page 55
Refrigerant Monitor Settings Group
Refrigerant Monitor Settings Group
The Refrigerant Monitor Settings password is - - + + -
- <Enter>. If the refrigerant monitor settings password is entered, the display goes to the menu defined below. If a key is not pressed every 10 minutes in this password protected menu, the display returns to the Chiller Operating Mode display of the Chiller Report, and the password must be entered again to return to this menu.
Refrigerant Monitor Settings Group Heading
Refrigerant Monitor Group Settings
Press (Next)(Previous) To Continue
Alarm Level 1
Alarm Level 1: XXXX PPM [Rfgt Type]
Press (+)(-) to Change Setting
Refrigerant Audible Alarm
Refrigerant Audible Alarm: [Setting]
Press (+)(-) to Change Setting
Possible values are: Disable, Alarm 1, Alarm 2, Alarm 3.
Trouble Audible Alarm
Trouble Audible Alarm:
[Status]
Press (+)(-) to Change Setting
Possible values of status are: Disable, Enable.
Alarm 1 Latching Status
Range of values are 3 to Alarm Level 2 minus 1 in increments of 1. The maximum value for R-123 is 30.
Alarm Level 2
Alarm Level 2: XXXX PPM [Rfgt Type]
Press (+)(-) to Change Setting
Range of values are Alarm Level 1 plus 1 to Alarm Level 3 minus 1 in increments of 1.
Alarm Level 3
Alarm Level 3: XXXX PPM [Rfgt Type]
Press (+)(-) to Change Setting
Range of values are Alarm Level 2 plus 1 to 1000 in increments of 1.
Alarm 1 Latching Status: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Latching, Non­Latching.
Alarm 2 Latching Status
Alarm 2 Latching Status: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Latching, Non­Latching.
50 CVHE-CLD-1A
Page 56
Refrigerant Monitor Settings Group
Alarm 3 Latching Status
Alarm 3 Latching Status: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Latching, Non­Latching.
Channel Scanner
This item shall be displayed only when the refrigerant monitor mode is Warmup.
Channel Scanner: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Installed, Not Installed.
Scanner Channel 1
Scanner Channel 1: [Status]
Press (+)(-) to Change Setting
Scanner Channel 4
Scanner Channel 4: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Active, Inactive.
Scanner Dwell Threshold
Scanner Dwell Threshold: XX %
Press (+)(-) to Change Setting
The range of values for Scanner Dwell Threshold is 30 to 70 in increments of 1.
Auxiliary Input
Auxiliary Input: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Installed, Not Installed.
Possible values of status are: Active, Inactive.
Scanner Channel 2
Scanner Channel 2: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Active, Inactive.
Scanner Channel 3
Scanner Channel 3: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Active, Inactive.
Auxiliary Input Alarm
Auxiliary Input Alarm: [Status]
Press (+)(-) to Change Setting
Possible values of status are: Enable, Disable.
Auxiliary Input Alarm Level: XX.X mA
Press (+)(-) to Change Setting
Range of values is 4.0 to 20.0 in increments of 0.1.
Auxiliary InputAlarm Direction:[Direction]
Press (+)(-) to Change Setting
Possible values of Direction are: Above, Below.
Auxiliary Input Audible Alarm:[Status]
Press (+)(-) to Change Setting
Possible values of Status are: Disable, Enable.
Information Manual 51
Page 57
Refrigerant Monitor Settings Group
Analog Output Range
Analog Output Range: [Range] PPM
Press (+)(-) to Change Setting
52 CVHE-CLD-1A
Page 58
Refrigerant Monitor Calibration
Refrigerant Monitor Calibration
The Refrigerant Monitor Calibration password is - + -
- + + <Enter> for the field calibration menu. If a refrigerant monitor calibration password is entered, the display goes to the menu items defined below. If a key is not pressed every 20 minutes in this password protected menu, the display returns to the Chiller Operating Mode display of the Chiller Report, and a refrigerant monitor calibration password must be entered again to return to this menu.
Refrigerant Monitor Settings Group Heading
This header is displayed if the field calibration password was entered.
Rfgt Monitor Field Calibration Group
Press (Next)(Previous) To Continue
This header is displayed if the factory calibration password was entered.
Refrigerant Zero Calibration
Refrigerant Zero Calibration
(Enter) to Start, (Next) to Continue
If <Next> is pressed the following refrigerant zero calibration screens are skipped. If <Enter> is pressed the following screens are displayed to permit refrigerant zero calibration.
Starting The Calibration Procedure
Please Wait
If the refrigerant monitor is unable to calibrate, the following item is displayed.
Unable to Calibrate
Otherwise, continue with the following screens.
Rfgt Monitor Factory Calibration Group
Press (Next)(Previous) To Continue
Refrigerant Monitor Mode
Refrigerant Monitor Mode: [Mode]
Scanner Channel X XXXX PPM [Rfgt Type]
This item is displayed if the Channel Scanner is not installed.
Refrigerant Monitor Mode: [Mode]
XXXX PPM [Rfgt Type]
Connect Refrigerant Zero Gas
(Next) To Continue, (Cancel) To Exit
Open Gas Sample Valve
(Next) To Continue, (Cancel) To Exit
XXXX PPM [Rfgt Type]
(Enter) To Adjust Conc, (Cancel) to Exit
Locking The Reading
Please Wait
Information Manual 53
Page 59
Refrigerant Monitor Calibration
If the refrigerant monitor is unable to calibrate, the following item is displayed.
Unable to Calibrate
Otherwise, the following screens continue.
Refrigerant Zero Calibration XXXX
Press (Enter)(Cancel)(+)(-) To Continue
Starting The Calibration Procedure
Please Wait
This item is followed by one of the following two items.
Successful Calibration
If the refrigerant monitor is unable to calibrate, the following item is displayed.
Unable to Calibrate
Otherwise, the following screens continue.
Connect Refrigerant Span Gas
(Next) To Continue, (Cancel) To Exit
Open Gas Sample Valve
(Next) To Continue, (Cancel) To Exit
XXXX PPM [Rfgt Type]
(Enter) To Adjust Conc, (Cancel) to Exit
Calibration Failed
(Enter) To Retry, (Cancel) To Exit
If the <Enter> key is pressed, the display will return to the second menu item above. If the <Cancel> key is pressed, the display continues to the next display.
Refrigerant Span Calibration
Refrigerant Span Calibration
(Enter) to Start, (Next) to Continue
If <Next> is pressed the following refrigerant span calibration screens are skipped. If <Enter> is pressed the following screens are displayed to permit refrigerant span calibration.
Starting The Calibration Procedure
Please Wait
Locking The Reading
Please Wait
If the refrigerant monitor is unable to calibrate, the following item is displayed.
Unable to Calibrate
Otherwise, the following screens continue.
Refrigerant Span Calibration XXXX
Press (Enter)(Cancel)(+)(-) To Continue
Starting The Calibration Procedure
Please Wait
54 CVHE-CLD-1A
Page 60
This item is followed by one of the following two items.
Successful Calibration
Calibration Failed
(Enter) To Retry, (Cancel) To Exit
If the <Enter> key is pressed, the display returns to the second menu item above. If the <Cancel> key is pressed, the display continues to the next display.
Refrigerant Monitor Calibration
Information Manual 55
Page 61
Service Tests Group
Service Tests Group
Important! FACTORY DEFAULT SETTINGS: Menu items that are programmable using the keypad may have a selectable choice that is listed as Factory Default. This Factory Default setting is the software default that is initially factory-programmed for a new module assembly and may NOT be the correct setting for a specific operating chiller. Always review all settings when any module is replaced to verify that the settings agree with the desired settings that were selected at initial startup or programmed at the factory.
Service Tools Group Password Request
Pswd Reqd to Access Service ToolsGroup
Please Enter Password
The Service Tools Password is + + - - + + <Enter>. Successfully entering the password sends you to the Service Tools Group Heading Screen as defined below.
Pressing the <Next> and Increment keys simultaneously while the Service Tools Group
Password Request screen is displayed will send you to the CLD-Chiller IPC communications screen shown below. This screen can be used as a debugging tool when CLD-Chiller IPC communications are suspect. The first line on the comm screen indicates which Chiller packets the CLD is checking. The second line on the comm screen indicates how many times in a 15 second interval the particular packet was received by the CLD. If a packet is received more than 9 times in the interval, a “+” is displayed. The counters are reset to 0 every 15 seconds. Hitting any key while on this screen will cause an exit.
Packet#:2 3 4 5 6 7 8 9 10 11 12 14 15
Received:x x x x x x x x x x x x x
If any item in the Service Tools Group is in manual override, the alarm LED will be on and non-flashing. The following table contains the Service Tools setpoints which affect the alarm light.To turn the alarm light off (from an on and non-flashing state), all the conditions applicable to the unit type must be satisfied.
Unit Type: Function / Setpoint: Condition to Turn Off
manual Alarm LED:
ALL “Chilled Water Pump:” Auto
ALL except CVAE “Condenser Water Pump:” Auto
CTV “Oil Pump:” Auto
CTV with IGV Output set to Stepper Motor.
CTV with HGBP installed: “HGBP Valve Control Is:” Auto
CTV with IGV Output set to Pulsed.
CTV with AF starter: “AF Manual Speed Control:” Disable
56 CVHE-CLD-1A
“Vane Control:” Auto
“IGV Control Is:” Auto
Page 62
Service Tests Group
Service Tools Group Heading
Service Tests & Overrides
Press (Next)(Previous) To Continue
This header appears when the headers do not appear in the Service Settings menu.
Chilled Water Pump
Chilled Water Pump: [Status]
Press (+)(-) to Change Setting
Possible values for Status are: Auto (Factory Default) and On.
Chilled Water Flow Switch Status
This screen displays the status of the chilled water flow switch status at the input to the UCM.
Condenser Water Pump
Condenser Water Pump: [Status]
[y]
Possible values for Status are: Auto (Factory Default) and On.
Possible values for [y] are: Press (+)(-) to Change Setting.
Condenser Water Flow Switch Status
This screen displays the status of the condenser water flow switch status at the input to the UCM.
Condenser Water Flow Switch Status:
[y]
Possible values for [y] are: Flow Switch is Open/No Flow and Flow Switch is Closed/Flow.
Chilled Water Flow Switch Status:
[y]
Possible values for [y] are: Flow Switch is Open/No Flow and Flow Switch is Closed/Flow.
Evaporator Differential Water Pressure
The following will be displayed only if the Differential Water Pressure Sensor Option is Installed.
Evap Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Evaporator Entering/Leaving Water Pressure
The following will be displayed only if the low pressure (< or = to 150 psig) Differential Water Pressure Sensor Option is Installed.
Condenser Differential Water Pressure
The following will be displayed only if the Differential Water Pressure Sensor Option is Installed.
Cond Differential Wtr Press: xx.x psid/kPa
Press (Next)(Previous) To Continue
Condenser Entering/Leaving Water Pressure
The following will be displayed only if the low pressure (< or = to 150 psig) Differential Water Pressure Sensor Option is Installed.
Cond Entering Water Pressure:xx.x psid/kPa
Cond Leaving Water Pressure: xx.x psid/kPa
Evap Entering Water Pressure:xx.x psid/kPa
Evap Leaving Water Pressure: xx.x psid/kPa
Information Manual 57
Page 63
Service Tests Group
Starter Dry Run
Use the following screen when [xx] = “Disabled”.
Starter Dry Run: [xx]
Press +/- to Change
Use the following screen when [xx] Not equal to “Disabled”.
Starter Dry Run: [xx]
(+)(-) (Enter): Trans Compl Inp: [y]
Possible values of [xx] are: Disabled (Factory Default), Shorting Relay On, Run Relay On, Start Relay On, Transition Relay On, and Start and Run Relays On.
Possible values of [y] are:
Closed This denotes that the Transition Complete input is seeing a contact closure.
Open This denotes that the Transition Complete input is seeing a contact open.
If the unit is not in the local Stop mode the following is displayed.
Starter Dry Run: Disabled
Unit Must Be In Local Stop To Execute
Vane Control Status/Vane Position Commands
The following screens will be displayed only when the “Inlet Guide Vane Output” is set to “Stepper Motor”.
Vane Control Is: [Status]
Press (+)(-) to Change Setting
The possible values of [status] are “Auto” or “Manual”. Factory Default is “Auto”.
If the vane control status is “Auto” the following is displayed:
Inlet Guide Vane Position: xxx.x %Open
[Limit mode]
If the vane control status is “Manual” the following is displayed. When the Vane Control Status is transitioned from “Auto” to “Manual”, the manual target is initialized to the current vane position.
Vane Pos xxx.x % Target xxx.x % Open
LWT = xx.x [limit mode]
The possible values of limit mode are: “Current Limit”, “Condenser Limit”, "Evap Limit”, and “(+) (-) and <Enter>”.
Vane Position
Oil Pump Status
This screen is displayed only if “Oil Pressure Protection” is set to “Transducer” or “Xducer & Switch.”
Oil Pump: [Status]
Differential Oil Pressure: xx.x psid
Possible values for Status are: Auto (Factory Default) and On.
Differential Oil Pressure is not a setpoint but a status display.
58 CVHE-CLD-1A
The following screen will be displayed only when the “Inlet Guide Vane Output” is set to “Stepper Motor”.
Inlet Guide Vane Position: xxxxx steps
Inlet Guide Vane Position:xx.x degrees
HGBP Valve Control Status/Manual Open and Close Commands
If HGBP is installed in the unit, the following screen is displayed:
HGBP Valve Control Is: [Status]
LWT = xx.x f/c [Y]
Page 64
Service Tests Group
The possible values of [status] are “Auto”, “Hold”, “Open”, or “Close”. Factory Default is “Auto”.
The possible values of Y are: “Current Limit”, “Condenser Limit”, “Evap Limit”, and (+)-) and <Enter>”. The latter is displayed when there are no limits operating.
HGBP Valve Manual Opening/Closing Duty Cycle
If HGBP is installed in the unit, the following screen is displayed:
Manual Opening/Closing Duty Cycle: xx%
Press (+)(-) to Change Setting
Range of values is 0 to 50% in increments of 1%. Factory Default is 30%.
Vane Control Status/Manual Load and Unload Commands
Range of values is 0 to 50% in increments of 1%. Factory Default is 30%.
Condenser Fan 3 [Status]
Fan 1 [x] Fan 2 [y] Fan 3 [z].......
Possible values for Status are: Auto (Factory Default) and On
Fan 1, Fan 2, and Fan 3 are not setpoints but a status display.
Possible values for x,y,z are Auto/On and On/Off.
Note: status display (2nd line) does not appear while in free cooling mode.
AF Manual Speed Control - CVHE/F/G Only
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
The following screen will be displayed only when the “Inlet Guide Vane Output” is set to “Pulsed”.
IGV Control Is: [Status]
LWT = xx.x f/c [Y]
The possible values of [status] are “Auto”, “Hold”, “Load”, or “Unload”. Factory Default is “Auto”.
The possible values of Y are: “Current Limit”, “Condenser Limit”, “Evap Limit”, and “(+)(-) and <Enter>”. The latter is displayed when there are no limits operating.
Manual Loading/Unloading Duty Cycle
The following screen will be displayed only when the “Inlet Guide Vane Output” is set to “Pulsed”.
Manual Loading/Unloading Duty Cycle: xx%
Press (+)(-) to Change Setting
AF Manual Speed Control: [d/e]
Press (+)(-) to Change Setting
The possible values of [d/e] are: Disable (Factory Default) and Enable.
AF Compressor Speed Command ­CVHE/F/G Only
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB”, or the Compressor Power Source is Engine/Generator, and AF Manual Speed Control is Enabled.
AF Compressor Speed Command: xxxx RPM
Press (+)(-) to Change Setting
Range of values is 2520 to 3600 RPM for “Adaptive Frequency” Starter Type (2280 to 3600 RPM for “AFDB” Starter Type) in increments of 1 RPM. Factory Default is 3600 RPM.
Information Manual 59
Page 65
Service Tests Group
AF Compressor Speed Command ­CVHE/F/G Only
The following is displayed only if the Starter Type is “Adaptive Frequency” or AFDB” or the Compressor Power Source is Engine/Generator.
AF Compressor Speed Command: xx.x Hz
AF Compressor Speed Command:xxxx.x RPM
Note This is a Report only for Troubleshooting purposes.
AF Boundary Pressure Coefficient/AF Pressure Coefficient - CVHE/F/G Only
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Boundary Press Coefficient: x.xxx
AF Pressure Coefficient: x.xxx
Module Software Revision Levels
Press (Enter) To Display Software
Revision Levels Or (Next) To Continue
If <Enter> is selected the following screen can be displayed 5 times with 5 different pairs of modules.
[Module 1:] [Revision Level]
[Module 2:] [Revision Level]
Module 1/2 will be one of the following: Chiller, Circuit, Starter, Options, Stepper 1, Stepper 2, TCI, Purge, LCLD, RCLD, I/O, Refrigerant Monitor, Scorpio, DCM.
Revision Level will either be an integer representing the software version number of the particular module or occurrence of a diagnostic, the display will automatically go to this menu and display certain messages as explained in the next section “Diagnostics Menu.”
Note This is a Report only for Troubleshooting purposes.
AF Re-Optimization Timer Time Remaining- CVHE/F/G Only
The following is displayed only if the Starter Type is “Adaptive Frequency” or “AFDB” or the Compressor Power Source is Engine/Generator.
AF Re-Optimization Time Remaining:x.xx Hrs
Press (+)(-) to Change Setting
Note This is a Report only for Troubleshooting purposes.
60 CVHE-CLD-1A
Page 66
Diagnostics Menu
Strike Diagnostic Key
Diagnostics Menu
The Diagnostics Group is where all diagnostics, both historical and active are presented. The group also contains the facility to clear active diagnostics, historic diagnostics, and purge diagnostics as individual groups. To clearly annunciate the
Diagnostic Occurs
(IFW,MAR,MMR)
occurrence of a diagnostic, the display will automatically go to this menu and display certain messages as explained below. The following illustration gives an overview of how the diagnostic key and screens below it work.
Header Screens
New Diagnostic Screen
Operating Mode Screen for the last diagnostic
Set of Screens for the 1st Diag.
Set of Screens for the nth Diag.
Diagnostics Group Heading
Active & Historic Diagnostics
Press (Next)(Previous) To Continue
Menu Settings Password
If the Menu Settings Password is Enabled in the Service Setup Group, following each setting group heading the following will be displayed:
Settings In This Menu Are [status]
[password message]
Screen(s) to Clear Diagnostics
Likewise, if the Menu Settings Password is Disabled in the Service Setup Group, the above screen will not appear.
The possible values for status are “Locked” or “Unlocked”. If the password status is locked, the password message will be “Enter Password to Unlock”. The user will then depress “-+-+-+” followed by the <Enter> key. The password keystrokes will be echoed to the screen as a visual aide. The last six keystrokes represent the current password, and up to twenty keystrokes can be entered. An incorrect password, or the twenty-first keystroke will result in the password message “Invalid Password”.
If the password status is unlocked, the password message will be “Press (Enter) to Lock”. Any attempt to change the setting will result in the message “Setting is Locked”. The password, once entered, will remain valid until canceled.
Information Manual 61
Page 67
Diagnostics Menu
Diagnostics and Annunciation
If there are no diagnostics present, only the following screen will be displayed under the Diagnostics Group heading screen.
No Diagnostics Present
Press (Next) (Previous) To Continue
If there are any diagnostics present, the following 3 screens are displayed sequentially when the <Next> key is pressed. The first screen is:
Diagnostic Report Follows
Press (Next) For More
The second screen is:
Press (Enter) To Display Operating Mode
At Time Of LastDiagnostic or(Next)For More
The third screen is the chiller operating mode display that was present at the time that the most recent diagnostic occurred.
If there are one or more diagnostics present, the following displays will be inserted into the display sequence. Diagnostics will be listed in order of occurrence from newest to oldest. Diagnostics will be displayed on 2 screens. The two screens will vary slightly depending on whether the diagnostic is active or historic.
The first active diagnostic screen will be:
MAR diagnostics)
The second active diagnostic display screen will contain the diagnostic sequence number, a time and date stamp, and a help message suggesting possible service procedures. The second active diagnostic display screen will be:
[sn] occurred at HH:MM xm Mon xx, 199x
[help message]
The time will be displayed as xx:xx am/pm.
The date will be displayed as month - date- year.
The month will use a standard 3-letter abbreviation. The year will not be abbreviated.
Depressing the next key will advance the display to the next diagnostic in the sequence.
The first historic diagnostic screen will be:
[sequence number] [Diagnostic]
Historic Only, Press (Next) For More
The definitions of diagnostic and sequence number are the same as for the active diagnostic messages. If <Next> is pressed the second historic diagnostic screen is displayed. The second historic diagnostic screen will be:
[sn] occurred at HH:MM xm Mon xx, 199x
Historic Only, Reset At End Of Diag Menu
Up to 20 diagnostics will be displayed.
[sequence number] [diagnostic]
(Next) [diagnostic type]
The sequence number will run from 1 through n (n <=
20) and number the diagnostics sequentially where the most recent diagnostic is sequence number [01].
The possible replacements for “diagnostic type” are:
Clearing Diagnostics
At the end of the diagnostic menu, there will be 4 screens that allow the user to Clear/Reset the different diagnostic groups.
If any active diagnostics are present, the following screen will be displayed:
Warning Only - Reset Not Reqd (Applies to all IFW diagnostics.)
Unit Shutdown - Reset Reqd (Applies to all MMR diagnostics)
Press (Enter) To Clr Active Diagnostics
And Shutdown / Reset System
Unit Shutdown - Automatic Reset (Applies to all
62 CVHE-CLD-1A
Page 68
Diagnostics Menu
If the <Enter> key is pressed, the following message is displayed for 2 seconds:
Active Diagnostics Have Been Cleared
System Is Resetting
The display will be reset to the operating mode screen of the chiller report after this message clears.
If any historic diagnostics are present, the following screen will be displayed:
Press (Enter) To
Clear Historic Diagnostics
If the <Enter> key is pressed, the following message is displayed for 4 seconds:
Historic Diagnostics Have Been Cleared
Diagnostic Report Is Being Reset
The display will be reset to the top of the Diagnostic Menu after this message clears.
If any purge diagnostics are present, the following screen will be displayed:
Note: Pressing <+> will silence the audible alarm. The IPC refrigerant monitor will cause all the refrigerant monitor alarms (diagnostics) to become non-latching for approximately 7.5 seconds. This allows any latching alarms to clear if the trip condition has been removed. This clearing function differs from the balance of UCP2 in that the balance of UCP2 diagnostics are cleared on reset and reestablished if the trip condition is still present.
If the <+> key is pressed, the following message is displayed for 4 seconds:
Silencing Rfgt Mon Audible Alarm
Clearing Nonactive Rfgt Alarms
New Diagnostic Display
When a new diagnostic is sensed by the system, the display will reset to the diagnostic menu. A “one­time” screen will be displayed to inform the user that a new diagnostic has been detected. This screen will vary depending on the type of diagnostic detected. The two major categories of diagnostics are those which are informational only, and those which have resulted in machine shutdown.
If the diagnostic is an MMR/MAR, the screen will be:
Press (Enter) To
Clear Purge Diagnostics
If the <Enter> key is pressed, the following message
*** A MACHINE SHUTDOWN HAS OCCURRED ***
Press (Next) For More
Otherwise, the screen will be:
is displayed for 4 seconds:
A New Warning Has Been Detected
Purge Diagnostics Have Been Cleared
Press (Next) For More
Diagnostic Report Is Being Reset
This screen will be inserted into the diagnostic menu
The display will be reset to the top of the Diagnostic Menu after this message clears.
directly after the “Diagnostic Report Follows” screen. Pressing <Next> will therefore take the user to the “Press (Next) to display operating mode at time of
If any IPC refrigerant monitor diagnostics are present, the following screen will be displayed:
last diagnostic” screen. If <Next>or <Previous> is pressed, this screen will no longer be in the display sequence.
Press (+) To
Silence Rfgt Mon Audible Alarm
Information Manual 63
Page 69
Diagnostics Menu
Diagnostics
In the table following, a “Latching” diagnostic is a condition which will cause the machine or a portion of
Diagnostic Types And Action
MMR = Machine Shutdown - Manual Reset
MAR = Machine Shutdown - Auto Reset
the machine as noted to shut down and will require a manual reset to restore operation. A diagnostic that is non-latching is reset automatically when the
IFW = Information Warning - May affect machine operation; lowest level of diagnostic
condition causing the diagnostic goes away. A non­latching diagnostic will shut down the machine or a part of the machine if so indicated. If a diagnostic is information only, no machine action is taken.
Unless otherwise stated, all active diagnostics will be lost on loss of power.
Remotely Resettable Diagnostics:
Except for the following, all diagnostics can be reset remotely from either the Remote Clear Language Display, the Tracer, or the External Diagnostic Reset input at the Options Module. The following diagnostics shall only be resettable ONLY at the Local Clear Language Display, e.g. with the operator standing at the unit.
Table 5
Can Be
DIAGNOSTIC DESCRIPTION
Starter Contactor Interrupt Failure MMR No
Low Evap Rfgt Pressure MMR No
Phase Loss MMR No
Phase Reversal MMR No
High Bearing #1 Temp MMR No High Motor Temp Position #3 MMR No
High Bearing #2 Temp MMR No Severe Phase Unbalance MMR No
Current Overload MMR No Starter Fault Type I MMR No
Cprsr did not Accelerate: Shutdown MMR No
Starter did not Transition MMR No Starter Fault Type II MMR No
High Pressure Cutout Tripped MMR No Starter Fault Type III MMR No
Low Evap Rfgt Temp. MMR No Cprsr did not Accelerate Fully MMR No
Emergency Stop Input MMR No High Cprsr Discharge Temp. MMR No
Starter Dry Run Test MMR No Phase Seq Monitor: Phase Reversal MMR No
Solid State Starter Fault Rly Open MMR No Transition Complete Input Shorted MMR No
Adapt Freq Drive Fault Relay Open MMR No At Speed Input Shorted MMR No
High Motor Temp Position #1 MMR No Transition Complete Input Opened MMR No
High Motor Temp Position #2 MMR No At Speed Input Opened MMR No
Diag Type
Remotely
Reset DIAGNOSTIC DESCRIPTION
Diag
Type
Can Be
Remotely
Reset
64 CVHE-CLD-1A
Page 70
Table 6 Diagnostic Table
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Adapt Freq Drive Fault Relay Open
Diag Type
MMR Starter All Start
Module
that
Called
Diag.
Diag.
Active
Modes
and Run
CAUSE Help Message
The Adaptive Frequency Drive fault relay is open.
Mode
At Speed Input Shorted MMR Starter Pre-Start a. Using either a Solid State Starter or an
Adaptive Frequency Drive, the Up to Speed/At Speed input was found to be shorted before the compressor was started. b. Applies only to Solid State Starters and Adaptive Frequency Drives.
At Speed Input Opened MMR Starter All
Running Modes
a. The At Speed input was found to be opened with the compressor motor running after successfully obtaining at speed condition. b. Applies only to Solid State Starters.
Aux/Ht Rcvry Ent Water Temp Sensor
Aux/Ht Rcvry Lvg Water Temp Sensor
IFW Options All Open or shorted and Heat Recovery is installed
(at the CLD).
IFW Options All Open or shorted and Heat Recovery is installed
(at the CLD).
Bearing Temp Sensor #1 MMR Stepper All Open or Short, only if this option is enabled at
the Human Interface.
Bearing Temp Sensor #2 MMR Stepper All Open or Short, only if this option is enabled at
the Human Interface.
Check Clock IFW Chiller All On loss of power the clock does not keep time, if
there is an extended power loss (greater than 15 seconds) this diag. is also generated to alert the operator to check the clock.
Check Oil Filter IFW Chiller All
Running Modes
a. The differential oil pressure fell below the Check Oil Filter Setpoint for 1000 psid-seconds and the Check Oil Filter Diagnostic setpoint is enabled. b. This diagnostic shall not be active for 15 minutes after the compressor is started. c. This IFW diagnostic will automatically reset when the differential oil pressure rise above the Check Oil Filter Setpoint for 1000 psid-seconds or the compressor is not running.
See Adaptive Frequency Drive Service Bulletin, check for an open wire.
Check End of Limt/At Speed Input
Check End of Limt/At Speed Input
Check Sensor, Wiring, and Connections
Check Sensor, Wiring, and Connections
Check Sensor, Wiring And Connections
Check Sensor, Wiring And Connections
Check Main Power Supply, Reset Clock
Information Manual 65
Page 71
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Chilled Water Flow Lost MAR Chiller Chilled
Module
that
Called
Diag.
Diag.
Active
Modes
Water Control: (All Stop modes) All modes except
CAUSE Help Message
a. The chilled water flow switch input was open for more than 6-10 contiguous seconds. b. 6-10 seconds of contiguous flow shall clear this diagnostic. c. Even though the pump times out in the STOP modes, this diagnostic shall not be called out in
the STOP modes. STOP (00) and EXTERN AL STOP (100)
Hot Water Control: Start and All Run Modes.
Chiller: Loss of Comm with Purge
Chiller: Loss of Comm with Starter
Chiller: Loss of Comm with Options
IFW Chiller All The chiller module lost communications with the
Purge module for 15 contiguous seconds.
MMR Chiller All The chiller module lost communications with the
Starter module for 15 contiguous seconds.
IFW Chiller All The chiller module lost communications with the
Options module for 15 contiguous seconds. This
IFW diagnostic is generated if Free Cooling is
Not Installed, otherwise this is an MMR diag.
under code 2F6
Chiller: Loss of Comm with Circuit
Chiller: Loss of Comm with I/O Mod
MMR Chiller All The chiller module lost communications with the
Circuit module for 15 contiguous seconds.
IFW Chiller All The chiller module lost communications with the
I/O module for 15 contiguous seconds; And
HGBP is installed (at the CLD).
Chiller: Loss of Comm with I/O Mod
MMR Chiller All The chiller module lost communications with the
I/O module for 15 contiguous seconds; And
Pulsed IGV is installed (at the CLD).
Chiller: Loss of Comm with DCM IFW Chiller All The DCM was setup as “installed” at the CLD
and the chiller module lost communications with
the DCM module for 15 contiguous seconds
Chiller: Loss of Comm with Stepper #1
Chiller: Loss of Comm with Local CLD
MMR Chiller All The chiller module lost communications with the
Stepper #1 module for 15 contiguous seconds.
IFW-AR Chiller All The chiller module lost communications with the
LCLD module for 15 contiguous seconds.
Note: As implemented this is a latching IFW diagnostic. That is, once generated it cannot be re­generated until a manual reset is done.
Chiller: Loss of Comm with Options
MMR Chiller All The chiller module lost communications with the
Options module for 15 contiguous seconds. This
MMR diagnostic is generated if Free Cooling is
Installed, otherwise this is an IFW diag. under
code 2AE
Check Pump, Valves, Flow Switch
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
66 CVHE-CLD-1A
Page 72
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Chiller: Loss of Comm with Rfgt Monitor
Diag Type
IFW-AR Chiller All The Chiller module lost communications with the
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
Refrigerant Monitor for 15 contiguous seconds.
Chiller: Loss of Comm with TCI IFW Chiller All The Tracer was setup as “installed” at the CLD
and the chiller module lost communications with the TCI (comm 3 or comm 4) module for 15 contiguous seconds
Chiller Mod Off-Brd 5V Range IFW Chiller All An improper Off Board 5v voltage was detected
at the Chiller Module. A 5vdc is used for off­board devices such as the pressure transducers. The micro checks to see that the A/D value falls within an acceptable range.
Chiller Mod Ref Voltage Calibration
IFW Chiller All An improper reference voltage was detected at
the Chiller Module. A 2.5 vdc reference is used to calibrate the non-ratiometric analog I/O such as 2-10vdc and 4-20ma inputs as well as PWM Analog outputs. The micro checks to see that the A/D value falls within an acceptable range.
This diagnostic has not been implemented
Chlr Sat Cond Temp Sensor (Purge) (As Sensed by the Purge module in Retrofit applications)
Circuit: Loss of Comm with Starter
Circuit: Loss of Comm with Chiller
IFW Purge All Open or Shorted Sensor
a. Applies to Retrofit applications of the Purge Only. Does not apply to UCP2 applications. b. IFW to the chiller, MMR to the Purge.
MMR Circuit All The circuit module lost communications with the
Starter module for 15 contiguous seconds.
MMR Circuit All The circuit module lost communications with the
Chiller module for 15 contiguous seconds. On loss of communications, the circuit module shall run the oil pump for the post lube time and then turn the oil pump off. On loss of communications, the circuit module shall continue to control the oil heater.
Circuit Module 24 Vdc Ref Missing
IFW Circuit All 24vdc reference missing and the Rfgt monitor is
installed.
Circuit Mod Off-Brd 5V Range MMR Circuit All An improper Off Board 5v voltage was detected
at the Circuit Module. A 5vdc is used for off­board devices such as the pressure transducers. The micro checks to see that the A/D value falls within an acceptable range.
Circuit Mod Ref Voltage Calibration
IFW Circuit All An improper reference voltage was detected at
the Circuit Module. A 2.5 vdc reference is used to calibrate the non-ratiometric analog I/O such as 2-10vdc and 4-20ma inputs as well as PWM Analog outputs. The micro checks to see that the A/D value falls within an acceptable range.
Cond Diff Water Press Transducer
IFW Options All Input Shorted or Open and the Diff. water
pressure sensing option, > 150 psig, is “installed” at the CLD.
Cond Entering Wtr Temp
IFW Chiller All Open or Short Check Sensor,
Sensor
Cond Leaving Wtr Temp Sensor See
Descripti on
Chiller All Open or Short.
a. IFW on Chilled Water Control b. MMR on Heat Pump (Hot Water) Control.
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check Chiller Module Voltages
Check Chiller Module Voltages
Purge Inop: See Purge O & M Manual
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check Rfgt Monitor Wiring/ 24 Vdc Supply.
Check Circuit Module Voltages
See Troubleshooting Service Bulletin
Check Sensor, Wiring, and Connections
Wiring And Connections
Check Sensor, Wiring And Connections
Information Manual 67
Page 73
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Condenser Rfgt Pressure Sensor
Diag
Type
MMR Circuit All Open or Short.
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
Must Hold on open AND short input is 2.0 Psia.
Design: Both opens and shorts result in the
Check Sensor, Wiring And
Connections pressure going to the low end of the scale. Therefore a Must Hold on the high pressure end is not required.
Condenser Rfgt Temp Sensor MMR Stepper All Open or Short Check Sensor,
Wiring And
Connections
Condenser Water Flow Lost MAR Chiller Chilled
Water Control: Start and All Run Modes. Hot
a. The chilled water flow switch input was open for more than 6-10 contiguous seconds. b. 6-10 seconds of contiguous flow shall clear this diagnostic. c. Even though the pump times out in the STOP modes, this diagnostic shall not be called out in the STOP modes.
Check Pumps,
Valves, Flow
Switch
Water Control: (All Stop modes)
Condenser Water Flow Overdue MAR Chiller Estab.
Cond Water
Condenser water flow was not proven within
4.25 minutes of the condenser pump relay being energized.
Check Pump,
Valves, Flow
Switch
Flow
Condenser Water Pressure Sensor
Cprsr did not Accelerate: Shutdown
IFW Chiller All Open or Short and the Cond Water Pressure
Sensor is setup as installed at the Clear Language Display.
MMR Starter Start
Mode
a. The compressor did not come up to speed in the allotted time defined by the Maximum Acceleration Timer.
Check Sensor,
Wiring, and
Connections
Check Main
Power Supply &
Wiring b. The Human Interface setups defined “Shutdown” as the action when the Maximum Acceleration Timer was exceeded.
Cprsr did not Accelerate Fully MMR Starter Starting a. Using either a Solid State Starter or an
Adaptive Frequency. Drive the UCM did not receive an Up to Speed or At Speed Signal
Check End of
Limt/At Speed
Input within the Maximum Acceleration Timer Setting. b. Applies only to Solid State Starters and Adaptive Frequency. Drives.
Cprsr Did Not Accelerate: Transition (The Motor is put across the line.)
IFW Starter Start
Mode
a. The compressor did not come up to speed in the allotted time defined by the Maximum Acceleration Timer. b. The Human Interface setups defined
See
Troubleshooting
Service Bulletin
“Transition” as the action when the Maximum Acceleration Timer was exceeded.
Current Overload MMR Starter All
Running
Motor current exceeded overload time vs. trip characteristic.
Modes
Current Overload Setpts Error IFW Starter All a. The redundant overload settings did not agree
for 30 contiguous seconds. (Continue to use the
Check Main
Power Supply &
Wiring
Review
Overload Set Up previous value for the 30 second timeout.) When this diagnostic occurs the affected Starter Module shall use the minimum (00000 binary, 00 decimal) overload setting as a default until either the UCM is reset or, if the redundant settings agree again, the starter module can go back to using the actual setting.
68 CVHE-CLD-1A
Page 74
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
CWS/Leaving Wtr Temp. Cutout Setpt Overlap
also overlap of CWS and Low Refrigerant Temp Cutout.
Diag Type
None None All No diagnostic, limit value to last legal value and
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
tell the operator about it on the second line of the display. NOTE: The above is not a diagnostic because you don't want the display vectoring you to a different display state when you are trying to set either the chilled water setpoint or the leaving water temp. cutout setpoint as it will in the case of a diagnostic.
DCM: Loss of Comm with Chiller AIFW Chiller All The DCM module lost communications with the
chiller A Chiller module for 15 contiguous seconds
DCM: Loss of Comm with Chiller BIFW Chiller All The DCM module lost communications with the
chiller B Chiller module for 15 contiguous seconds
DCM: Loss of Comm with Starter A
IFW Chiller All The DCM module lost communications with the
chiller A Starter module for 15 contiguous seconds
DCM: Loss of Comm with Starter B
IFW Chiller All The DCM module lost communications with the
chiller B Starter module for 15 contiguous seconds
DCM: Loss of Comm with TCI A IFW Chiller All The DCM module lost communications with the
chiller A TCI module for 15 contiguous seconds
DCM: Loss of Comm with Stepper A
IFW Chiller All The DCM module lost communications with the
chiller A Stepper module for 15 contiguous seconds
Differential Oil Pressure Overdue
MMR Circuit Pre-Lube A differential oil pressure 0f 9 psid was not
established within 3 minutes of starting the Oil Pump in the Pre-Lube Mode. Design: Some hysteresis was introduced into this diagnostic. 9 psid is the criteria to establish pre-lube oil flow and 8 psid is used to define a loss of oil flow on pre-lube.
Differential Oil Pressure Switch (CVGD and CVAD units only)
MMR Circuit Pre-Lube Just prior to starting the oil pump the Differential
Oil Pressure Switch is checked to be sure it's contacts are open (not stuck or jumpered), if not set this diagnostic.
Discharge Temp Sensor MMR Stepper All Open or Short, only if HGBP and the Discharge
Temp. Sensor is called out as “Installed” at the Human Interface.
Emergency Stop Input MMR Chiller All a. EMERGENCY STOP input is open. An
external interlock has tripped. Time to trip from input opening to unit stop shall be 0.1 to 1.0 seconds.
Evap Diff Water Press Transducer
IFW Options All Input Shorted or Open and the Diff. water
pressure sensing option, > 150 psig, is “installed” at the CLD.
Evap Entering Wtr Temp Sensor IFW Chiller All Open or Short
a. Normal operation, no effects on control. b. Chilled Water Reset, Will just run at either normal CWS or will run at maximum reset permitted.
Evap Leaving Water Temp
MMR Chiller All Open or Short Check Sensor,
Sensor
N/A
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
See Troubleshooting Service Bulletin
Check Oil Pressure Switch/Wiring.
Check Sensor Wiring And Connections
Check Emergency Stop Input Device
Check Sensor, Wiring, and Connections
Check Sensor, Wiring And Connections
Wiring And Connections
Information Manual 69
Page 75
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
Evap Rfgt Temp Sensor MMR Stepper All Open or Short Check Sensor,
Wiring And
Connections
Evap Water Pressure Sensor IFW Chiller All Open or Short and the Evap Water Pressure
Sensor is setup as installed at the Clear Language Display.
Evaporator Water Flow Overdue MAR Chiller Estab.
Evap. Water
Evaporator water flow was not proven within
4.25 minutes of the Evaporator pump relay being energized.
Check Sensor,
Wiring, and
Connections
Check Pump,
Valves, Flow
Switch
Flow on going from STOP to AUTO.
Extended Compressor Surge MMR Starter All
Running Modes
An extended Surge condition was detected and the Surge protection feature was Enabled at the Clear Lang. Display. An extended Surge
Check
Condenser
Water Temp. condition is defined being in a “continuous”
10% minutes.
Check Main
Power Supply &
Wiring
Extended Power Loss
Note: This diagnostic and the functions tied to it are handled by the Check Clock diagnostic.
surge condition for 15 +
IFW Starter All The unit lost power for an extended period of
time. On CTV units if power is lost for an extended period of time the oil pump is not run on Power Up. If a power loss is determined to be a Momentary Power Loss the Oil Pump is run on the Power Up to Post Lube the bearings. The deciding factor determining if a power loss is Extended or Momentary is TBD.
External Base Load Setpoint IFW-AR Chiller All a. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input diagnostic, Terminate external base loading function. This IFW diagnostic will automatically reset if the input returns to the normal range.
External Chilled Water Setpoint IFW-AR Options All a. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input diagnostic, default CWS to next level of priority (e.g. Front Panel SetPoint). This IFW diagnostic will automatically reset if the input returns to the normal range.
External Current Limit Setpoint IFW-AR Options All a. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input diagnostic, default CLS to next level of priority (e.g. Front Panel SetPoint. This IFW diagnostic will automatically reset if the input returns to the normal range.
External Hot Water Setpoint IFW-AR Options All a. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal At
Input diagnostic, default HWS to next level of priority (e.g. Front Panel SetPoint). This IFW diagnostic will automatically reset if the input returns to the normal range.
External Vane Position Setpoint MMR Chiller All a. Not “Enabled”: no diagnostics.
b. “Enabled“: Out-Of-Range Low or Hi, set
Check Signal at
Input diagnostic.
70 CVHE-CLD-1A
Page 76
Diagnostics Menu
Diag Type
DIAGNOSTIC DESCRIPTION
Free Cooling Valves MMR Options When
Module
that
Called
Diag.
Diag.
Active
Modes
exiting Free cooling
CAUSE Help Message
a. The Free Cooling Valves were commanded to close and did not close in the three minutes allowed for closure. And FC is installed (at the CLD) and commanded off. b. The Free Cooling Valves were commanded to open and did not open in the three minutes allowed for closure. And FC is installed (at the CLD) and commanded On.
Heat Sink Temp Sensor IFW Starter All Open or Short and Solid State Starter installed.
Note: The Solid State Starter is expected to be protected from overheating via a thermal cutout. Since this sensor is not used to protect the starter, the failure of the sensor is treated as an IFW.
HGBP Valve Closure Overdue IFW a. The HGBP Valve was commanded to close
and did not close in the three minutes allowed for closure
High Bearing #1 Temp MMR Stepper All
starting and running modes
a. The bearing temperature at sensor #1 exceeded 180 + or - 5 °F (82.2 °C) for 0.5 - 2 seconds (Note: BT, WT, and DT may be “instantaneous trip” but consistent with the analog input filtering function.), and b. This function is enabled at the CLD.
High Bearing #2 Temp MMR Stepper All
starting and running modes
a. The bearing temperature at sensor #2 exceeded 180 + or - 5 °F (82.2 °C) for 0.5 - 2 seconds (Note: BT, WT, and DT may be “instantaneous trip” but consistent with the analog input filtering function.), and b. This function is enabled at the Human Interface.
High Cprsr Discharge Temp. MAR Stepper All a. The discharge temp. exceeded the trip value;
200°F + or - 5°F for CVHE/F, CVG and CVA. The Discharge Temp Cutout is adjustable at the Human Interface. See also section P4_CPRSR.Doc of this Functional Specification. b. Time to trip from trip value exceeded shall be
0.5 to 2.0 seconds. (Note: BT, WT, and DT may be “instantaneous trip” but consistent with the analog input filtering function.) d. The diag. shall reset automatically 50 °F below the trip point.
High Motor Temp Position #1 MMR Circuit Any Start
and Run Mode
The Motor winding temp. at sensor #1 exceeded 265 °F + or - 15°F for 0.5 - 2 seconds. (Note: BT, WT, and DT may be “instantaneous trip” but consistent with the analog input filtering function.)
High Motor Temp Position #2 MMR Circuit Any Start
and Run Mode
The Motor Winding Temp. at sensor #2 exceeded 265 °F + or - 15 °F for 0.5 - 2 seconds. (Note: BT, WT, and DT may be “instantaneous trip” but consistent with the analog input filtering function.)
High Motor Temp Position #3 MMR Circuit Any Start
and Run Mode
The Motor Winding Temp. at sensor #3 exceeded 265° F + or - 15° F for 0.5 - 2 seconds. (Note: BT, WT, and DT may be “instantaneous trip” but consistent with the analog input filtering function.)
Check Clsd End­Switches, Valves, Wiring
Check Sensor Wiring And Connections
Check Clsd End­Switches, Valves, Wiring
Check Oil System
Check Oil System
See Troubleshooting Service Bulletin
See Troubleshooting Service Bulletin
See Troubleshooting Service Bulletin
See Troubleshooting Service Bulletin
Information Manual 71
Page 77
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
High Oil Temp MMR Circuit All
Module
that
Called
Diag.
Diag.
Active
Modes
starting and running Modes
CAUSE Help Message
UCP2 shall provide a fixed High Oil Temperature Cutout of 180 °F (82.2°C). If the oil temperature violates the cutout by 120 degree F seconds (66.6 degree C seconds) an MMR diagnostic shall be generated.
High Pressure Cutout Tripped MMR Circuit All A high pressure cutout was detected. See the
trip points for the various products under the HPC switch description of this specification.
High Restart Inhibit Timer Warning
IFW Starter All The Restart Inhibit timer has reached a
maximum threshold for the host chiller. For CTV chillers this is 45 minutes. This indicates excessive chiller cycling, steps should be taken to correct this.
High Vacuum Lockout MMR Circuit Pre-Start The Oil Tank Pressure transducer shall be used
to sense for very low pressures in all Non­running cprsr modes.
IGV BPI Not Found During Search
IFW Stepper All The Inlet Guide Vane Actuator Binary Position
Indicator was not found over the entire stroke of the IGV during the BPI search.
IGV BPI Found Low During Search
IFW Stepper All The Inlet Guide Vane Actuator Binary Position
Indicator was found too low in the stroke of the IGV during the BPI search.
IGV BPI Shorted IFW Stepper Pre-Start At what is believed to be a closed position, the
IGV BPI was found to be shorted.
IGV Electrical Drive Circuit Open
MMR Stepper On
Demand and
Run the IGV Actuator electrical drive circuit test both on demand from the human interface and just before the chiller starts.
Pre-Start
Incorrect Chiller Software Installed
MMR Chiller All The incorrect Eprom was loaded into this
module. This diagnostic is detected when a factory test computer sets the unit type to something other than what the Eprom software was intended for.
Incorrect Stepper Software Installed
MMR Stepper All The incorrect Eprom was loaded into this
module. This diagnostic is detected when a factory test computer sets the unit type to something other than what the Eprom software was intended for.
Inlet Guide Vane Closure Overdue
IFW I/O All Non-
running modes,
a. The inlet guide vanes were commanded to close and did not close in the three minutes allowed for closure.
Starting, Pre-Stop (IGV manual modes)
I/O Mod: Loss of Comm with Chiller
IFW I/O All The I/O module lost communications with the
Chiller module for 15 contiguous seconds.
Invalid Starter Selection MMR Starter All Modes The Cld has been setup for an AFD starter type,
however the starter module is not AFD compatible. (Note: This feature is not supported by hardware.) (Special Note not for Publishing; See Starter Module Design Specification for requirements to enable AFD operation.)
Check Oil
System
Check
Condenser
Water Temp.
Check for
Excessive
Chiller Cycling
See
Troubleshooting
Service Bulletin
See
Troubleshooting
Service Bulletin
Check Stepper
Module, Wiring,
& Motor
Check Sensor,
Wiring, and
Connections
See
Troubleshooting
Service Bulletin
(No message is
required.)
(No message is
required.)
Check Clsd End-
Switches,
Vanes, Wiring
Check IPC
Wiring/
Connections
Call Local Trane
Service Agency
72 CVHE-CLD-1A
Page 78
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Low Chilled Water Temp: Unit Off
Diag Type
IFW-AR Chiller Unit in
Module
that
Called
Diag.
Diag.
Active
Modes
Auto and
No Ckt's (Unit in Auto but not Starting or Running)
Energize
d (Any
Ckt(s)
Energize
d)
Low Chilled Water Temp: Unit On
MAR Chiller Any
Ckt(s)
Energize (Unit Starting or Running)
d
(No Ckt's
Energize
d)
Low Differential Oil Pressure MMR Circuit All
starting
and
running
Modes
Low Evap Rfgt Temp. MMR Stepper Starter
Contactor
Energize
d or in
Free
Cooling
Low Evap.Water Flow (To be implemented in CTV Phase C release and ABS Phase B release.)
IFW-AR Chiller Chiller
Auto and
All
Running
Modes
Low Oil Temp MAR Circuit All Non-
running
Modes.
CAUSE Help Message
a. The chilled water temp. fell below the cutout setpoint while the compressor (or Solution Pump) was not running for 30 degree F Seconds. Automatic Reset of the IFW dig shall occur 2 degrees F (1.1 °C) above the cutout setpoint.
a. The chilled water temp. fell below the cutout setpoint while the compressor (or Solution Pump) was running for 30 degree F Seconds. Automatic Reset of the MAR diag shall occur 2 degrees F (1.1 °C) above the cutout setpoint.
Pre-Lube Mode on CVHE/F Chillers:
a. See Diagnostic 1FF.
Start & Run Mode on CVHE/F Chillers:
a. If during these modes the Differential oil pressure drops below 9 PSID for more than 90 Psid Seconds, an MMR diagnostic shall be generated. The 90 Psid Seconds integral shall be reset to zero when the differential pressure rises above 9 psid.
Pre-Lube Mode on CVGD/CVAD Chillers:
a. See Diagnostic 1FF.
Start & Run Mode on CVGD/CVAD Chillers:
a. While Starting and Running, if the differential oil pressure switch opens for more than 3-5 seconds, generate an MMR diagnostic.
a. The Saturated Evap Rfgt Temp dropped below the Low Rfgt Temp. Cutout Setpoint when the circuit was running for 30 °F seconds.
a. The evap. water flow measurement option was installed and the flow dropped to a setpoint set at the CLD. This IFW shall be Auto Reset and reset 0.1 gpm/ton above the adjustable trip point or when the Evaporator pump is turned off. b. There shall be a 2 minute delay in permitting this diagnostic to be called out from the time the evap pump has been turned on AND flow has been established/confirmed via the flow switch input. c. This is not necessarily active in a Manual On of the Evaporator pump. That is, if the chiller is in the Stop mode and the Evap. Relay is manually turned on, this diagnostic shall not be active. (Manual On is not taken into account.)
The oil temperature dropped below it's adjustable Low Oil Temp. Cutout. (“Instantaneous trip” but consistent with the analog input filtering function.) See Section P4_CPRSR for further description of this diagnostic. Automatic Reset of the MAR diag shall occur 5 degrees F (2.8 °C) above the cutout setpoint.
Check Flow, Sensor, & Wiring
Check Flow, Sensor, & Wiring
Check Oil System
Check Operation, Call Service
See Troubleshooting Service Bulletin
See Troubleshooting Service Bulletin
Information Manual 73
Page 79
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Max Acceleration Setpts Error
Diag
Type
IFW Starter All a. The redundant Maximum Acceleration
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
settings did not agree for 30 contiguous seconds. (Continue to use the previous value for the 30 second timeout.) When this diagnostic occurs the affected Starter Module shall use 6 seconds as a default until either the UCM is reset or, if the redundant settings agree again, the starter module can go back to using the actual setting.
Max Pumpout Rate Exceeded-
IFW Purge All a. IFW to the chiller, MAR to the Purge. Purge Inop: See
Svc (Prg)
Max Pumpout Rate Exceeded
IFW Purge All a. IFW to the chiller, MAR to the Purge. Purge Inop: See
(Prg)
Memory Error Type I: NOVRAM MMR Chiller On UCM
Power Up or following a Type II Memory error diag.
a. On UCM either power up or following a Type II Memory Error a NOVRAM memory error was detected. The UCM is operating on all Engineering Factory defaults for all setup parameters. Check all setup parameters and continue to run chiller. Replace the Chiller Module as soon as a replacement is available. Note: It is expected that this diagnostic will be detected on the very first power up of the Chiller Module at the Manufacturer since the NOVRAM will not contain valid data on first power up.
Memory Error Type IV IFW Chiller All A page timeout error was detected while trying to
write data into EEPROM. There will likely be a recall of Engineering Factory defaults on the next reset or power transition. Replace the Chiller Module as soon as a replacement is available.
Memory Error Type II: Shadow RAM
IFW Chiller All a. A Shadow RAM memory error was detected.
The UCM is operating on all last valid values (pulled from NOVRAM) for all setup parameters. No setup parameter changes were pending to be loaded into NOVRAM, a complete recovery of all setup parameters was made and there is no need to check unit setup parameters. Compressor starts and hour were lost for not more than the last 24 hours. This is expected to be an isolated event and repair or replacement is not required. If this diagnostic does occur repeatedly, then replace the Chiller module.
Memory Error Type III IFW Chiller All a. A Shadow Ram memory error was detected.
The UCM is operating on all last valid values (pulled from NOVRAM) for all setup parameters. Setup parameter changes less than 24 hours old pending to be loaded into NOVRAM were lost. Check all setup parameters made in the last 24 hours. Compressor starts and hours were lost for not more than the last 24 hours. This is expected to be an isolated event and repair or replacement is not required. If this diagnostic does occur repeatedly, then replace the Chiller module.
Review Max Acceleration Set Up
Purge O & M Manual
Purge O & M Manual
Call Service to Check all Settings
Call Service to Check all Settings
No Settings Were Lost
Settings Changed in The Last 24 Hours Lost
74 CVHE-CLD-1A
Page 80
Diagnostics Menu
Diag Type
DIAGNOSTIC DESCRIPTION
Momentary Power Loss MAR Starter All
Module
that
Called
Diag.
Diag.
Active
Modes
Running
Modes
CAUSE Help Message
Determine Cause Of Power
Interruption (Start Mode, e.g. Before Transition
Motor Temp Sensor #1 MMR Circuit All Open or Short Check Sensor,
Wiring And
Connections
Motor Temp Sensor #2 MMR Circuit All Open or Short Check Sensor,
Wiring And
Connections
Motor Temp Sensor #3 MMR Circuit All Open or Short Check Sensor,
Wiring And
Connections
MPL Detect Circuit Inoperative MMR Starter All A failure was detected in the Momentary Power
Loss detect circuit. If there are no zero cross interrupts on Vab for 637.5 msec (Prior to
See
Troubleshooting
Service Bulletin
Centravac Upgrade 4: approx. 3 half line cycles), the timer interrupt will trip and generate a diagnostic that indicates that our ability to detect MPL is gone. If Vab was truly gone the module would be powered down so if we can detect that Vab is gone then there must be a hardware failure on the board.
Oil Pressure Sensor Calibration MMR Circuit All Non-
running Modes
The recalibration of the Differential Oil Pressure sensors resulted in an error correction of greater than 3 PSID.
See
Troubleshooting
Service Bulletin and not for 5 minutes after running.
Oil Pump Discharge Pressure Sensor
MMR Circuit All Open or shorted input.
Must Hold on open AND short input is 2.0 Psia. Design: Both opens and shorts result in the
Check Sensor,
Wiring, and
Connections
pressure going to the low end of the scale. Therefore a Must Hold on the high pressure end is not required.
Oil Sump Pressure Sensor MMR Circuit All Open or shorted input.
Must Hold on open AND short input is 2.0 Psia. Design: Both opens and shorts result in the
Check Sensor,
Wiring, and
Connections
pressure going to the low end of the scale. Therefore a Must Hold on the high pressure end is not required.
Oil Temp Sensor MMR Circuit All Open or Short Check Sensor,
Wiring And
Connections
Options: Loss of Comm with Starter
IFW Options All The options module lost communications with
the Starter module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Options: Loss of Comm with Chiller
IFW Options All The options module lost communications with
the Chiller module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Information Manual 75
Page 81
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Options Module 24 Vdc Ref Missing
Options Module 24 Vdc Ref Missing
Diag
Type
IFW Options All 24Vdc reference missing and the differential
MMR Options All 24Vdc reference missing and the differential
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
water pressure transducers are installed.
water pressure transducers are installed and Adaptive Frequency Drive installed.
Options Mod Off-Brd 5V Range IFW Options All An improper Off Board 5v voltage was detected
at the Options Module. A 5vdc is used for off­board devices such as the External CWS and CLS, and pressure transducers. The micro checks to see that the A/D value falls within an acceptable range.
Options Mod Ref Voltage Calibration
IFW Options All An improper reference voltage was detected at
the Options Module. A 2.5 vdc reference is used to calibrate the non-ratiometric analog I/O such as 2-10vdc and 4-20ma inputs as well as PWM Analog outputs. The micro checks to see that the A/D value falls within an acceptable range.
Outdoor Air Temp Sensor
IFW Chiller All Open or Short
a. Use end of range value (whatever value the See Also 3d3 diag. (Either Outdoor Air Reset or Low Ambient Lockout Selected)
Outdoor Air Temp Sensor
None None All Open or Short
open or short gives).
b. Clear diag. when the resistance returns to
normal range.
a. Display end of range value. (dashes “-----”) See Also 3d3 diag. (Both Outdoor Air Rst and Low Ambient Lockout not selected.)
Outdoor Air Temp Sensor
MMR Chiller All Open or Short Check Sensor,
See also A1 and A2 diag.
Over Voltage MAR Starter Pre-Start
and Any Ckt(s) Energzd
a. Line voltage above + 10% of nominal. (Must
hold = + 10% of nominal. Must trip = + 15% of
nominal. Reset differential = min. of 2% and
max. of 4%. Time to trip = minimum of 1 min. 10
sec. and maximum of 5 min. 20 seconds)
Phase Loss MMR Starter Contactor
Energizd or all Start, and Run modes.
a. No current was sensed on one or more of the
current xformer inputs. (Must hold = 20% RLA.
Must trip = 5% RLA.) Time to trip shall be 1
second minimum, 3 seconds maximum. Actual
design trip point is 10%.
b. Phase rotation protection is enabled and
either the Phase A current signal or the Phase C
current is less than approximately 5% of the CT
rating. Time to trip is 0.7 seconds for CTV/ABS.
Phase Reversal MMR Starter Contactor
energized to transition
a. A phase reversal was detected on the
incoming current. On a compressor startup the
phase reversal logic must detect and trip in 0.7
seconds.
command
Phase Reversal Protection Lost MMR Starter Starter
Contactor energized to transition command
a. The phase reversal protection on the
compressor has become inoperative. The phase
rotation protection system failed to detect 2 in a
row of one of the four phase circuit states; Phase
reversal, Phase rotation OK, Phase A lost,
Phase B lost.
Check Press Xducer Wiring/ 24 Vdc Supply.
Check Press Xducer Wiring/ 24 Vdc Supply.
Check Options Module Voltages
See Troubleshooting Service Bulletin
Check Sensor, Wiring And Connections
N/A
Wiring And Connections
Check Main Power Supply & Wiring
Check Main Power Supply & Wiring
Check Main Power Supply & Wiring
Check Starter Module.
76 CVHE-CLD-1A
Page 82
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Purge Cprsr Suction Temp Sensor
Diag Type
IFW Purge All Open or Shorted Sensor
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
a. IFW to the chiller, MMR to the Purge.
Purge Liquid Level Too High IFW Purge All a. The Level Switch at the purge opened for 6 to
10 Seconds. Note: This was implemented as tripping in 2 A/D samples, which are 0.4 seconds apart. Prior to 2/ 2/95 only 1 A/D sample could trigger this diagnostic. b. IFW to the chiller, MMR to the Purge.
Purge: Loss of Comm with Chiller
IFW Purge All The purge module lost communications with the
chiller module for 15 contiguous seconds. a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with Starter
IFW Purge All The purge module lost communications with the
starter module for 15 contiguous seconds. a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with Stepper
IFW Purge All The purge module lost communications with the
stepper module for 15 contiguous seconds. a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with Options
IFW Purge All The purge module lost communications with the
chiller module for 15 contiguous seconds. a. IFW to the chiller, IFW to the Purge.
Purge: Loss of Comm w/ Retrofit CLD
IFW Purge All The purge module lost communications with the
retrofit Human Interface module for 15 contiguous seconds.
Purge: Loss of Comm with Stepper #1
IFW Purge All The purge module lost communications with the
chiller module for 15 contiguous seconds. a. IFW to the chiller, MAR to the Purge.
Purge: Loss of Comm with Stepper #2
IFW Purge All The purge module lost communications with the
chiller module for 15 contiguous seconds. a. IFW to the chiller, MAR to the Purge.
Purge Memory Error Type I: NOVRAM
This diag. should be seen in both UCP2 and retrofit applications only.
MMR Purge On Purge
Power Up or following a Type II Memory error diag.
a. On either Purge Module power up or following a Type II Memory Error, a NOVRAM memory error was detected. The Purge Module is operating on all Engineering Factory defaults for all setup parameters. Check all setup parameters and continue to run purge. Replace the Purge Module as soon as a replacement is available. Note: It is expected that this diagnostic will be detected on the very first power up of the Purge Module at the Manufacturer since the NOVRAM will not contain valid data on first power up.
Purge Memory Error Type II: Shadow RAM
IFW Purge All a. A Shadow RAM memory error was detected.
The Purge Module is operating on all last valid
values (pulled from NOVRAM) for all setup This diag. should be seen in retrofit applications only.
parameters. No setup parameter changes were
pending to be loaded into NOVRAM, a complete
recovery of all setup parameters was made and
there is no need to check unit setup parameters.
Purge pumpout times Compressor starts and
hour were lost for not more than the last 24
hours. This is expected to be an isolated event
and repair or replacement is not required. If this
diagnostic does occur repeatedly, then replace
the Purge module.
Purge Inop: See Purge O & M Manual
Purge Inop: See Purge O & M Manual
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Check IPC Wiring/ Connections
Purge Inop: See Purge O & M Manual
No Setting Were Lost
Information Manual 77
Page 83
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Purge Memory Error Type III
Diag
Type
IFW Purge All a. A Shadow Ram memory error was detected.
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
The Purge Module is operating on all last valid This diag. should be seen in retrofit applications only.
values (pulled from NOVRAM) for all setup
parameters. Setup parameter changes less than
24 hours old pending to be loaded into NOVRAM
were lost. Check all setup parameters made in
the last 24 hours. Purge pumpout times
Compressor starts and hours were lost for not
more than the last 24 hours. This is expected to
be an isolated event and repair or replacement is
not required. If this diagnostic does occur
repeatedly, then replace the Purge module.
Purge Memory Error Type IV IFW Purge All A page timeout error was detected while trying to
write data into EEP Factory. There will likely be a
recall of Engineering Factory defaults or a
corruption of pumpout data on the next power
transition. Replace the Purge Module as soon as
a replacement is available.
Purge Memory Error III
IFW Purge All a. A Shadow Ram memory error was detected.
Compressor starts and hours were lost for not This diag will be seen in UCP2 applications of the Purge Module. This diag will not be seen in retrofit applications of the Purge Module. See also diag 385-387.
more than the last 24 hours. This is expected to
be an isolated event and repair or replacement is
not required. If this diagnostic does occur
repeatedly, then replace the Purge module. This
is an IFW diagnostic to both the Purge and
Chiller.
Purge Misconfigured as Retrofit IFW Purge All The Purge module is configured as a Retrofit
application instead of an UCP2 application.
Chiller module remaps Purge Retrofit Only
diagnostics to this diagnostic. Check Purge input
J1 pins 5,6. Open = UCP2 application, Short =
Retrofit application
Purge Misconfigured as UCP2 IFW Purge All The Purge module is configured as an UCP2
application instead of a Retrofit application.
Check Purge input J1 pins 5,6. Open = UCP2
application, Short = Retrofit application
Refrigerant Monitor Sensor IFW-AR Circuit All Open or Shorted input and the Rfgt Monitor is
setup as installed at the Clear Language
Display.
Rfgt Monitor Memory Lost IFW Rfgt Mon All Refrigerant Monitor lost battery backed-up RAM.
a. IFW to the chiller, MMR/MAR to the
Refrigerant Monitor.
Rfgt Monitor IR Source IFW Rfgt Mon All Refrigerant Monitor infrared optical source
failure.
a. IFW to the chiller, MAR to the Refrigerant
Monitor.
Rfgt Monitor Chopper IFW Rfgt Mon All Refrigerant Monitor optical bench photo-
interrupter failure.
a. IFW to the chiller, MAR to the Refrigerant
Monitor.
Rfgt Monitor Temp Sensor IFW Rfgt Mon All Refrigerant Monitor bench temperature sensor
failure.
a. IFW to the chiller, MAR to the Refrigerant
Monitor.
Settings Changed in The Last 24 Hours Lost
See Purge O & M Manual
No Settings Lost
See Purge O & M Manual
See Purge O & M Manual
Check Sensor, Wiring, and Connections
See Refrigerant Monitor IOM Manual
Check IR Source Wiring And Connections
Check Chopper Wiring And Connections
Check Sensor, Wiring, Connections
78 CVHE-CLD-1A
Page 84
Diagnostics Menu
Diag Type
DIAGNOSTIC DESCRIPTION
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
Rfgt Monitor Bench Flow Loss IFW Rfgt Mon All Air flow loss to the Refrigerant Monitor optical
bench. a. IFW to the chiller, MMR/MAR to the Refrigerant Monitor.
Rfgt Monitor Scanner Flow Loss IFW Rfgt Mon All Air flow loss to the Refrigerant Monitor scanner.
a. IFW to the chiller, MMR/MAR to the Refrigerant Monitor.
Rfgt Monitor Out Of Temp Range
Rfgt Monitor Refrig Level Too Low
IFW Rfgt Mon All Out of temperature range for measuring
refrigerant concentration.
IFW Rfgt Mon All The Refrigerant Monitor read less than or equal
to -5 ppm refrigerant concentration.
Rfgt Monitor Fault IFW Rfgt Mon All A undefined diagnostic detected by the
Refrigerant Monitor. a. IFW to the chiller, MMR to the Refrigerant Monitor.
Rfgt Monitor Calibration Error (This diagnostic is currently ignored by UCP2)
IFW Rfgt Mon All The Refrigerant Monitor calibration failed.
a. IFW to the chiller, IFWMMR to the Refrigerant Monitor.
Rfgt Monitor Aux Input Error IFW Rfgt Mon All The Refrigerant Monitor auxiliary input is outside
the 4-20 mA range.
Rfgt Monitor External Reset IFW Rfgt Mon All The Refrigerant Monitor external reset switch
(Normally Closed) is stuck in the “reset” state or the switch/jumper is missing.
Rfgt Monitor Level 3 Rfgt Refrigerant Alarm
IFW Rfgt Mon All The Refrigerant Monitor has read a refrigerant
concentration greater or equal to the level 3 setpoint.
Rfgt Monitor Auxiliary Alarm IFW Rfgt Mon All The Refrigerant Monitor auxiliary input signal
indicates an alarm condition.
Rfgt Monitor Level 2 Rfgt Refrigerant Alarm
IFW Rfgt Mon All The Refrigerant Monitor has read a refrigerant
concentration greater or equal to the level 2 setpoint.
Rfgt Monitor Level 1 Rfgt Refrigerant Alarm
IFW Rfgt Mon All The Refrigerant Monitor has read a refrigerant
concentration greater or equal to the level 1 setpoint.
Safety String Input Opened*** MMR Scorpio All Safety string input opened on the Scorpio
module
Severe Phase Unbalance MMR Starter All
Running Modes
a. A 30% Phase Unbalance diagnostic has been detected. Items to check are the Current Transformer Part Numbers (they should all match), The Current Transformer resistances, line voltage phase balance, all power wiring connections, the contactor pole faces, and the motor. If all these are OK, replace the Starter module.
Solid State Starter Fault Rly Open
MMR Starter All Start
and Run
The SSS fault relay is open. See Solid State
Mode
Soln Pump Winding Thermostat Open
MMR Circuit All a. The motor winding temperature thermostat
opened; nominally 230°F (110 °C). b. The motor temp. thermostat or wiring is open. c. Time to trip from input open to Solution Pump shutdown shall be 0.5 to 2.0 seconds.
See Refrigerant Monitor IOM Manual
See Refrigerant Monitor IOM Manual
Check Bench Heater, Wiring, Connections
Recalibrate Refrigerant Monitor
See Refrigerant Monitor IOM Manual.
See Refrigerant Monitor IOM Manual
Check Signal At Input
See Refrigerant Monitor IOM Manual.
N/A
N/A
N/A
N/A
N/A
Check Main Power Supply & Wiring
Starter Service Bulletin, check for an open wire.
Check Machine Operation
Information Manual 79
Page 85
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Starter Contactor Interrupt Failure
Diag
Type
MMR Starter Starter
Module
that
Called
Diag.
Diag.
Active
Modes
Contact not Energize d (Starter Contact Energize d)
CAUSE Help Message
a. Welded Starter contactor.
b. Detected a welded compressor contactor
when the compressor was commanded off but
the current did not go to zero. Detection time
shall be 5 second minimum and 10 seconds
maximum for all Electromechanical and Solid
State Starters. Detection time for Adaptive
Frequency. Drives shall be 12 seconds minimum
and 20 seconds maximum. On detection,
generate the diagnostic, energize the
appropriate alarm relay, continue to command
the affected compressor off.
Starter did not Transition MMR Starter On the
first check after transition.
a. The UCM did not receive a transition complete
signal in the designated time from the UCM
command to transition. The must hold time from
the UCM transition command is 1 second. The
Must trip time from the transition command is 6
seconds. Actual design is 2.5 seconds.
b. Item a. above is active only for Y-Delta, Auto-
Transformer, and Primary Reactor, and X-Line
Starters.
Starter Dry Run Test MMR Starter Starter
Dry Run Mode
While in the Starter Dry Run Mode either 50%
Line Voltage was sensed at the Potential
Transformers or 10% RLA Current was sensed
at the Current Transformers.
Starter Fault Type I MMR Starter Starting a. This is a specific starter test where 1M(2k1) is
closed first and a check is made to ensure that
there are no currents detected by the CT's. If
currents are detected when only 1M is closed
first at start, then one of the other contactors is
shorted.
b. This test applies only to factory installed Y-
Delta Closed Transition Starters.
Starter Fault Type II MMR Starter Starting a. This is a specific starter test where the
Shorting Contactor (S)(2K3) is individually
energized and a check is made to ensure that
there are no currents detected by the CTs. If
current is detected when only S is energized at
Start, then 1M is shorted.
b. This test in a. above applies to all forms of
starters (Note: It is understood that many
starters do not connect to the Shorting
Contactor.).
Starter Fault Type III MMR Starter Starting a. As part of the normal start sequence to apply
power to the compressor the Shorting Contactor
(S) and then the Main Contactor (1M) were
energized. 1.6 seconds later there were no
currents detected by the CT's for the last 1.2
Seconds on all three phases.
b. This test in a. above applies to all forms of
starters except Adaptive Frequency. Drives
(Note: It is understood that many starters do not
connect to the Shorting Contactor.).
c. For Adaptive Frequency Drives, TBD
Starter: Loss of Comm with Circuit
MMR Starter All The starter module lost communications with the
Circuit module for 15 contiguous seconds.
Complete Starter Checkout Required
Complete Starter Checkout Required
Current or Voltage Detected
See Troubleshooting Service Bulletin
See Troubleshooting Service Bulletin
See Troubleshooting Service Bulletin
Check IPC Wiring/ Connections
80 CVHE-CLD-1A
Page 86
Diagnostics Menu
DIAGNOSTIC DESCRIPTION
Starter: Loss of Comm with Chiller
Diag Type
MMR Starter All The starter module lost communications with the
Module
that
Called
Diag.
Diag.
Active
Modes
CAUSE Help Message
Chiller module for 15 contiguous seconds.
Check IPC Wiring/ Connections
Starter Mod Ref Voltage Calibration
IFW Starter All An improper reference voltage was detected at
the Starter Module. A 2.5 vdc reference is used to calibrate the non-ratiometric analog I/O such
See Troubleshooting
Service Bulletin as 2-10vdc and 4-20ma inputs as well as PWM Analog outputs. The micro checks to see that the A/D value falls within an acceptable range.
Stepper #1:Loss of Comm with Starter
MMR Stepper All The Stepper #1 module lost communications
with the Starter module for 15 contiguous seconds.
Stepper #1:Loss of Comm with Chiller
MMR Stepper All The Stepper #1 module lost communications
with the Chiller module for 15 contiguous seconds.
Surge Shutdown: Ice Building MAR Starter All Ice
Building Modes
An extended Surge condition was detected while in Ice Building Mode. This diagnostic shall clear when the Ice Building command is withdrawn.
TCI: Loss of Comm with Purge IFW TCI All The TCI module lost communications with the
Purge module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Check IPC
Wiring/
Connections
See
Troubleshooting
Service Bulletin
Check IPC
Wiring/
Connections
TCI: Loss of Comm with Starter IFW TCI All The TCI module lost communications with the
Starter module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with Options IFW TCI All The TCI module lost communications with the
Options module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with Circuit IFW TCI All The TCI module lost communications with the
Circuit module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with Chiller IFW TCI All The TCI module lost communications with the
Chiller module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
TCI: Loss of Comm with Stepper #1
IFW TCI All The TCI module lost communications with the
Stepper #1 module for 15 contiguous seconds.
Check IPC
Wiring/
Connections
Tracer Communications Lost IFW TCI All The Tracer was setup as “installed” at the CLD
and the TCI lost communications with the Tracer for 15 contiguous minutes after it had been
Check Tracer to
UCP Wiring/
Connections established. Continue to run the chiller with the last valid Tracer Setpoints/Mode.
Tracer failed to Establish Comm IFW TCI At power-upThe Tracer was setup as “installed” at the CLD
and the Tracer did not communicate with the TCI within 2 minutes after power-up.
Check Tracer
Wiring/
Connections/
Power
Tracer Outdoor Air Temp Sensor Fail
IFW Chiller All Check Sensor,
Wiring, and
Connections
Tracer Temperature Sensor IFW Options All Input Shorted. Check Sensor,
Wiring, and
Connections
Transition Complete Input Shorted
MMR Starter Pre-Start a. The Transition Complete input was found to
be shorted before the compressor was started. b. This is active for all electromechanical
Check transition
complete
contact starters.
Information Manual 81
Page 87
Diagnostics Menu
Diag
Type
DIAGNOSTIC DESCRIPTION
Transition Complete Input Opened
Under Voltage MAR Starter Pre-Start
NOTE: For FastPak, the “module that called the diagnostic” is
Scorpio if Circuit or Stepper is listed
*** FastPak-only Diagnostic
MMR Starter All
Module
that
Called
Diag.
Diag.
Active
Modes
Running Modes
and Any Ckt(s) Energzd
CAUSE Help Message
a. The Transition Complete input was found to be opened with the compressor motor running after a successful completion of transition. b. This is active only for Y-Delta, Auto­Transformer, and Primary Reactor Starters.
a. Line voltage below - 10% of nominal or the Under/Overvoltage transformer is not connected. (Must hold = - 10% of nominal. Must trip = - 15% of nominal. Reset differential = min. of 2% and max. of 4%. Time to trip = min. of 1 min. and max. of 5 min.)
Complete Starter Checkout Required
Check Main Power Supply & Wiring
82 CVHE-CLD-1A
Page 88
FastPak™ “Settings Group” Menu Record
Operator Settings Group:
Menu item Choices Default Design/Actual
1 Purge Operating Mode Stop, On, Auto, Adaptive Auto
2 Front Panel Chilled Wtr Setpt 0-65 Deg F, -17.8-18.3
3 Front Panel Current Limit Setpt 40 to 100% 100%
4 Chilled Water Reset Type Return, Constant Return,
5 Reset Ratio 10 to 120% 50% 6 Start Reset Setpoint 4 to 30°F, 2.2 to 16.7°C 10°F, 5.6 °C 7 Max Reset Setpoint 0 to 20°F, 0.0 to 11.1 °C 5°F, 2.8 °C
8 Ice Building
Panel Ice Termination Setpoint (Displayed if Ice Building Enabled)
9 20 to 32 °F, -6.7 to 0°C 27°F, -2.8°C
10 Ice to Normal Cooling Timer (Displayed only
if Ice Building Option” is installed)
11 Chilled Water Setpoint Source Front Panel, External
12 Current Limit Setpoint Source Front Panel, External
13 Ice Termination Setpoint Source (Displayed
only if “Ice Building Option” is installed)
14 Setpoint Source Override None, Use Front Panel
Deg C
Disable
Disable, Enable Disable
0 to 10 mm. 5 minutes
SourceFuture 1, Future 2
Source, Future 1, Future 2
Front Panel, Future 1, Future 2, Future 3
Setpoints, Override Tracer-Use Default Setpoints (available only if Tracer Option is installed)
44.0 °F, 6.7 C
Disable
Front Panel
Front Panel
Front Panel
None
Information Manual 81
Page 89
FastPak™ “Settings Group” Menu Record
Service Settings Group: Basic Setups
Menu Item Choices Default Design/Actual
1 Language English, Francais, Deutch,
Espanol, Nippon, Italiano, Nederland, Portuguese, Coded
2 Display Units English, SI XXX.X, XXX English
3 Decimal Places Displayed XXX.X
4 Display Menu Headings Enable, Disable Enable 5 Differential To Start Setpoint 1 to 10°F, 0.5 to 5.5 °C 5 °F, 2.8°C 6 Differential To Stop Setpoint 1 to 10°F, 0.5 to 55°C 5 °F, 2.8°C
7 Evap Pump Off Delay 0 to 30 Minutes 1 Minute
8 Printer Setups
Print Time Interval Enable, Disable Enable
Print on Time Interval 1 to 24 hrs. 8 hrs.
Print on Diagnostic Enable, Disable Enable
Number of Pre-Diag Reports 1 to 5 5
Diagnostic Report Interval 2 to 120 seconds S seconds
Printer, Baud Rate 300, 4800, 1200, 9600,
2400, 19,200
Printer, Parity None, Odd, Even None
Printer, Data Bits 8,7 8
Printer, Stop Bits 1,2
Printer, Handshaking XON/XOFF, DTR, RTS,
None
English
9600
XON/XOFF
82 CVHE-CLD-1A
Page 90
FastPak™ “Settings Group” Menu Record
Field Startup Group:
Menu item Choices Default Design/Actual
1 Keypad/Display Lock Feature Enable Disable, Enable Disable
2 Menu Settings Password Enable Disable, Enable Disable
3 ICS Address: 1 to 127 65 4 Power Up Start Delay Time 0 to 60° Seconds 0 Seconds 5 Design Delta Temp Setpoint: 4 to 30°F, 2.2 to 16.7° C 100° F, 5.5 °C
6 Lvg Wtr Temp Cutout Setpoint: (When this
setpoint is within 1.7°F of the Front Panel Chilled Water Setpoint, the Front Panel Chilled Water Setpoint is increased along with this setpoint to maintain the differential)
7 Low Rfgt Temp Cutout Setpt: (When this
setpoint is within 6°F of the Front Panel Chilled Water Setpoint, the Front Panel Chilled Water Setpoint is increased along with this setpoint to maintain the differential.)
8 Condenser Limit Setpoint: 80 to 120% 93%
9 Maximum RI Timer Setting 30 to 60 Minutes 60 Minutes
10 Purge Control/Type: Micro Purge, Stand-Alone
11 Purge Max Pumpout Rate: 1 to 100 minutes/24 hrs 20 Minutes /24
12 Purge Service Excessive Pumpout Override
Timer
13 Prg Low Liq Temp Inhibit Enable, Disable Disable
14 Prg Low Liq Temp Inhibit Setpt: (Does not
display unless above feature = Enable”)
15 Surge Protection: Disable, Enable Enable
16 Under/Over Voltage Protection: (Permits
“Enable only if Option Installed)
17 Phase Reversal Protection: Disable, Enable Enable
18 Phase Unbalance Protection: Disable, Enable Enable
19 Momentary Power Loss Protection: Disable, Enable Enable
20 Enhanced Oil Temp Protection Disable, Enable Enable 21 Oil Temp Setpoint: 100 to 160° F, 37.8 to
22 Low Oil Temp Cutout: 80 to 140 °F, 26.7 to 60°C 95 °F, 35°C 23 High Discharge Temp Cutout: 170 to 220°F, 76.6 to
24 Soft Load Control: Disable, Enable Disable
25 Soft Load Starting current Limit: 40 to 100% 100%
26 Soft Load Current Limit Rate: 0.5 to 5.0% /Minute 5.0% /Minute 27 Soft Load Lvg Water Rate: 0.5 to 5.0 °F/Minute
-10 to 360°F,
-23.2 to 2.2° C
-35 to 360°F,
-37.2 to 2.2°C
Purge
1 to 72 Hours 0 Hours
32 to 50 °F, 0.0 to 10 °C 40°F, 4.4°C
Disable, Enable Enable
71.1°C
104.4 °C
0.3 to 2.8 0C/Minute
36° F, 2.2° C
32°F, 0.0°C
Micro Purge
Hours
143.5°F,61.9°C
200°F, 93.3 °C
5.0°F/Minute
2.8°C/Minute
Information Manual 83
Page 91
28 Hot Gas Bypass Control Disable, Enable Enable
29 HGBP Timer Disable, Enable; Unlimited
Menu Item Choices Default Design/Actual
30 Maximum HGBP Time (Displayed only if
HGBP is installed and HGBP Timer is enabled)
31 HGBP Vane Position 0 to 30% 10%
32 LWT Proportional Gain Setpoint 0 to 100%/ “F 0 to 180%/
Time
1 to 480 minutes 30 minutes
°C
33 LWT Integral Gain Setpoint 0 to 1%/ °F 0 to 1.8%/°C 0.1 10%/ °F
34 LWT Derivative Gain Setpoint 0 to 10%/ °F
28 IGV MAXIMUM Travel Setpt: 0 to 60,000 Steps 50,000 Steps
29 Guide Vane Closed Travel Stop 0 to 100% 0%
30 AF Adjustable Speed Control Algorithm Disable, Enable Enable
31 AF Leaving Water Standard Deviation 0.5 to 4.0 1.0
32 AF Pressure Coefficient Constant 0 to 2000 800
33 AF Re-Optimization Factor 0.03 to 1.00 0.30
34 AF Re-Optimization Timer 1 to 255 24
35 AF Boundary PC Y-Intercept 0.01 to 2.00 0.40
36 AF Boundary PC Y-Intercept Maximum 0.01 to 2.00 2.00
37 AF Pressure Error Deadband 0.001 to 1.000 0.030
38 AF Proportional Speed Gain 1 to 100 50
39 Minimum Capacity Timer Disable, Enable; Unlimited
40 Time Permitted at Mm Cap 1 to 480 minutes 30 minutes
41 Local Atmospheric Pressure 10 to 16 psig
42 Mm Delta Press Calib (2 VDC) 0 to 400 psid
43 Max Delta Press Calib (10 VDC) 1 to 400 psid 7 to 2758
44 Inlet Guide Vane Stroke Time 15 to 100 seconds 45 seconds
45 Low Diff Oil Pressure Cutout 9 to 35 psid
46 Pre Lube Setpt 20 to 60 seconds 60 seconds
47 Post Lube Setpt 30 to 420 seconds 180 seconds
48 Check Oil Filter Diagnostic Disable, Enable Disable
49 Check Oil Filter Setpt Diag Disabled, 9 to 60
0 to 18%/ °C
Time
68.9tollO.3kPa
0 to 2758 kPa
kPa
62 to 241 kPa
psid, 62 to 414 kPa
Enable
10%/°F 18%/”C
0.198%/ °C
0.00%/°F
0.00%/ °C
Enable
14.7 psig
101.3kPa
0 psid 0 kPa
30 psid 207 kPa
12 psid 64 kPa
15 psid, 103 kPa
84 CVHE-CLD-1A
Page 92
FastPak™ “Settings Group” Menu Record
Machine Configuration Group:
Menu Item Choices Default Design/Actual
1 Unit Frequency 60 HZ, 50 HZ 60 HZ
2 Unit Type CVHE & CVHG, CVHF, CVHB,
3 Nominal Unit Tons 100 to 1800 Tons 300 Tons
4 Refrigerant Type R114, R500, R502 R123
5 Refrigerant Monitor Type None, PC None
6 Starter Type Undefined, Adaptive Frequency, Y-
7 Level 2 Contactor Integrity Test (Startup
Contactor Test-Y-D only)
8 Rated Load Amps 0 to 2,500 500
9 Motor Heating Constant 0 to 100 Minutes 25 Minutes
10 Current Overload Setting #1
(See Manual for Setup Procedure)
11 Current Overload Setting # 2 (See Manual
for Setup Procedure)
12 Maximum Accel Time Setpt# 1 (See
Manual for Recommend Setpt)
13 (255 Minus Timer Setpt #1 above) 191 to 249 Seconds 226 Seconds 14 Heatsink Start Inhibit Temperature Setpoint 100.0 to 200.0 °F (37.8 to 93.3 °C),
15 External Chilled Wtr Setpoint Installed, Not Installed Not Installed
16 External Current Limit Setpt Installed, Not Installed Not Installed
17 Acceleration Time Out Action Shutdown, Transition Shutdown
18 Motor Temp Protection 3 Winding Sensors, MTC Switch 3 Winding
19 Motor Winding RTD Type 100 Ohm/ 0°C, 75 Ohm/ 75°C 75 Ohm /75°C
20 High Pressure Cutout setting -5 to 500 PSIG 15 PSIG for
21 Line Voltage Sensing Option Installed, Not Installed Not Installed
22 Unit Line Voltage 180 to 6600 460
23 Hot Gas Bypass Option Installed, Not Installed Not Installed
24 Condenser Press. Sensor Option Installed, Not Installed Not installed
25 Bearing Temp Sensors Option Installed, Not Installed Not installed
26 Discharge Temp Sensor Option Installed, Not Installed Not installed
27 Ice Building Option Installed, Not Installed Not installed
28 External Analog Inputs 4-20 mA, 2-10 VDC 4-20 mA
29 Tracer Option Installed, Not Installed Not Installed
30 TCI Option Installed, Not Installed Not Installed
CVGE, CVAE, FastPak Water Cooled, FastPak Air Cooled
Delta, X-Line, Solid State, Auto, Transformer, Primary Reactor, AFDB, SMCDP, Stand Alone No Str Module
Disable, Enable (Not available on any FastPak models)
00 to 31 00
224 to 255 255
6 to 64 Seconds 27 Seconds
in increments of 0.1 °F/°C
CVHE
Y-Delta
Disable
100 °F (93.3°C)
Sensors
standard unit 25 PSIG for ASME unit
Information Manual 85
Page 93
FastPak™ “Settings Group” Menu Record
Machine Configuration Group:
Menu Item Choices Default Design/Actual
31 Printer Option Installed, Not Installed Not Installed
32 Duplex Control Module
(DCM) Option
33 IGV Output Type Stepper Motor, Pulsed Stepper Motor
34 Oil Pressure Protection Xducer; Diff Switch Xducer
35 Programmable Analog
Output
36 Program Relay [N] where [N]
= 1, 2 or 3
37 Current Transducer Cutler Hammer, Other Cutler Hammer
38 Current Transducer at 100%
RLA (Displayed only if Current Transducer is set to “Other’)
39 Outdoor Air Temp Sensor Installed, Not Installed Installed
Installed, Not Installed Not Installed
Not Used;% RLA;% Cond Press; Refrig Diff Press
Not Used; Comp Running; MMR Alarm; MAR Alarm; MMR + MAR Alarm; Limit Warning; Ice Making; Head Relief Request; Tracer Controlled; Max Capacity
-10.0 to -5.0 VDC in 0.1 VDC Increments
% RLA
1 = MMR + MAR Alarm 2 = Comp Running 3 = Not Used
86 CVHE-CLD-1A
Page 94
FastPak™ “Settings Group” Menu Record
Refrigerant Monitor Settings Group:
Menu item Choices Design/Actual
1 Alarm Level 1
2 Alarm Level 2
3 Alarm Level 3
4 Refrigerant Audible Alarm Disable, Alarm 1, Alarm 2
5 Trouble Audible Alarm Disable, Enable
6 Alarm 1 Latching Status Latching, Non-Latching
7 Alarm 2 Latching Status Latching, Non-Latching
8 Alarm 3 Latching Status Latching, Non-Latching
9 Channel Scanner (Displayed only when
refrigerant monitor mode is in “Warm-up”.)
10 Scanner Channel 1 Active, Inactive
11 Scanner Channel 2 Active, Inactive
12 Scanner Channel 3 Active, Inactive
13 Scanner Channel 4 Active, Inactive
14 Scanner Dwell Threshold 30 to 70
15 Auxiliary Input Installed, Not Installed
16 Auxiliary Input Alarm Disable, Enable
17 Auxiliary Input Alarm Level 4.0 to 20.0
18 Auxiliary Input Alarm Direction Above, Below
19 Auxiliary Input Audible Alarm Off, On
20 Analog Output Range 0 to 100, 0 to 1000
Alarm 3
Installed, Not Installed
Information Manual 87
Page 95
FastPak™ “Settings Group” Menu Record
Service Tests Group:
Menu item Choices Default Design/Actual
1 Chilled Water Pump Auto, On Auto
2 Condenser Water Pump Auto, On Auto
5 Starter Dry Run: (Starter Dry Run Contactor
Test - Y - D Only)
6 Oil Pump (Set to Differential Transducer) Auto, On Auto
7 Oil Pump (Set to Differential Switch) Auto, On Auto
Vane Control Status Vane Position Commands (Displayed when “Inlet Guide Vane Output” is set to “Stepper Motor”.)
8 Vane Control Status Vane Position
Commands (Displayed when “Inlet Guide Vane Output” is set to “Pulsed”.)
9 Manual Loading/Unloading Duty Cycle 0 to 50% 30%
10 HGBP Valve Control is Auto, Open, Close Auto
11 HGBP Valve Opening /Closing Duty Cycle
(Displayed when “Inlet Guide Vane Output” is set to “Pulsed”.)
(Not available on any FastPak models)
Manual, Auto Auto
Auto, Hold, Load, Unload Auto
0 to 50% 30%
Disabled
88 CVHE-CLD-1A
Loading...