Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and r equires specific knowledge and training. Improperly installed, adjusted or altered equipment
by an unqualified person could result in death or serious injury. When working on the equipment, observe all pr ecautions in the literature and
on the tags, stickers, and labels that are attached to the equipment.
October 2014
X39641257001
SAFETY WARNING
CVHH-SVX001A-EN
Page 2
Introduction
X39003892001A
Read this manual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Y our personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/ stat e/national electrical codes.
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situatio n which, if not avoided, could
result in death or serio us in jur y.
Indicates a potentially hazardous
situatio n which, if not avoided, could
result in minor or moderat e injury. It
could also be used to alert against
unsaf e practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlo rin e, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same po tential impact to the
environment. Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
and HCFCs.
Important Responsible Refrigerant Pr actic es
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technician s who handle
refrigerants must be certified according to local rules. For
the USA, the Federal Clean Air Act (Section 608) sets forth
the requirements for handling, reclaiming, recovering and
recycling of certain refrigerants and the equipment that is
used in these service procedures. In addition, some states
or municipalities may have additional requirement s that
must also be adhered to for r esponsible management of
refrigerants. Know the applicable laws and follow them.
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut res istant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/ SDS and
OSHA/GHS (Global Harmonized System of
Clas s ification and Labelling of C hemicals ) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
•If there is a ris k of energiz ed elec trical c ontact, arc, or
flash, tec hnicians MUST put on all PPE in ac c ordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PE RFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING W ITHOUT PROPER ELECTRICAL PPE AND
ARC FL ASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or
serious injury.
WARNING
Replace Manual in Cabinet After Use!
Failure to replace this Installation, Operation, and
Maintenance manual in cabinet after use could prevent
personnel fr o m access in g necessary safety information
and could r esult in death or serious injury or equipment
damage.
NOTICE:
Do Not Use Non-Compatible Parts or
Materials!
Use of non-compatible parts or materials c ould result in
equipment damage. Only genuine Trane® replacement
components with identical Trane part numbers should
be used in Trane CenTraVac chillers. Trane assumes no
responsibility for damages resulting from the use of
non-compatible parts or materials.
WARNING
Refrigerant May Be Under Positive
P ressure!
Failure to recover refrigerant to relieve pressure or the
use of non-approved refrigerants, refrigerant
substitutes, or refrigerant additives could result in an
explosion which could result in death or serious injury
or equipment damage. System contains oil and
refr igerant and may be under positive pressure.
Recover refrigerant to relieve pressure bef ore opening
the system. See unit nameplate for refrig er ant type. Do
not use non-approved refrigerants, refrigerant
substitutes, or refrigerant additives.
CVHH-SVX001A-EN3
Note: Graphic labels (shown above) are used for CE
application only.
Copyright
This document and the information in it are the property of
T rane, and may not be used or reproduced in whole or in
part without written permission. Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Page 4
Introduction
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
CVHH-SVX001A-EN (10 Oct 2014)
•First version of this literature
Factory Warranty Information
Compliance with the following is required to preserve the
factory warranty:
All Unit Installations
Startup MU ST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY. Contractor
must provide a two-week startup notification to T rane (or
an agent of Trane specifically authorized to perform
startup).
Additional Requirements for Units Requiring
Disassembly
When a new fully assembled chiller is shipped and
received from our Trane manufacturing location and, for
any reason, it requires disassembly or partial
disassembly—which could include but is not limited to the
evaporator, condenser, control panel, compressor/motor,
purge, factory-mounted starter or any other components
origin ally attached to the fully assembled unit—
compliance with the following is required to preserve the
factory warranty:
•Trane, or an agent of Trane specifically authorized to
perform start-up and warranty of Trane
perform or have direct on-site technical supervision of
the disassembly and reassembly work.
•The installing con tractor must notify Trane—or an
agent of Trane spe cifically authorized to perform
startup and warranty of Trane
in advance of the scheduled disassembly work to
coordinate the disassembly and reassembly work.
•Start-up must be performed by Trane or an agent of
Trane specifically authoriz ed to perform startup and
warranty of Tran e
Trane, or an agent of Trane specifically authorized to
perform start-up and warr anty of Trane
provide qualified personnel and standard hand tools to
perform the disassembly work at a location specified by
the contractor. Trane, or an agent of Trane specifically
authorized to per form star t-up and warranty of Trane
products, will perform or have direct on-site supervision of
the disassembly and reassembly work. The contractor
shall provide the rigging equipment such as chain falls,
gantries, cranes, forklifts, etc. necessary for the
disassembly and reassembly work and the required
qualified personnel to operate the necessary rigging
equipment.
Important: Any devi ation from these r equirements
®
products.
must be agre ed upon prior to startup in a
written agreement from Trane.
Forms and Check Sheets . . . . . . . . . . . . . . . 102
Table of Contents
CVHH-SVX001A-EN7
Page 8
Unit and Compressor Nameplates
Unit Nameplate
The unit nameplate is located on the left side of the control
panel. A typical unit nameplate is illustrated in
and contains the following information:
•Unit model and size descriptor
•Unit electrical requirements
•Correct operating charge and refrigerant type
•Unit test pressures and maximum operating pressures
•Unit li terature
Serial Number. The unit serial number provides the
specific chiller identity. Always provide this serial number
when call ing for service or during parts identification.
Service Model Number. The service model represents
the unit as built for service purposes. It identifies the
selections of variable unit features requ ired when
ordering replacements parts or requesting service.
No te: Unit-mounted starters are identified by a separate
number found on the starter.
Product Description Block. The CenTraVac™ models
are defined and built using the Product Definition and
Selection (PDS) system. This system describes the product
offerings using a product coding block which is made up of
feature categories and codes that identifies all
characteristics of a unit.
Figure 1
Figure 1.Typical unit nameplate (CDHF shown; CVHH
is similar)
8 CVHH-SVX001A-EN
Page 9
Compressor Nameplate
TRANEMADE IN USAX39002458010B
MODEL NO.
SALES ORDERSERIAL NO.
The compressor assembly has a separate model number
which is required to identify internal and external
compressor parts. The model number begins with
“ CCHH” and the nameplate is located on the foot of the
volute.
Figure 2.Compressor nameplate
No te: The serial number space on the compressor
nameplate will be intentio nally left blank.
Unit and Compressor Nameplates
CVHH-SVX001A-EN9
Page 10
Model Number Descriptions
CVHH CenTraVac
Chiller Description
Digit 1, 2 — Simplex
CenTraVac™ Chiller
Digit 3 — Drive
Digit 4 — Development
Sequence
Digit 5, 6, 7 — Nominal Total
Compressor Tonnage
Digit 8 — Unit M otor Voltage
Digit 9 — Unit Type
Digit 10, 11 — Design Sequence
Digit 12 — M anufacturing
Communication Interface
Digit 32 — Special Options
Digit 33 — Water Flow Control
Digit 34 — Chilled Water Reset
Digit 35 — Control: Heat
Recovery/Auxiliary Temperature
Sensors
Digit 36 — Industrial Chiller
Package (INDP)
Digit 37 — Control Pow er
Transformer (CPTR)
Digit 38 — Thermal Dispersion
Water Flow Proving
Digit 39 — Compressor M otor
Frame Size
CCHH Centrifugal
Compressor
Description
The compressor assembly has a
separate model number which is
required to identify internal and
exter nal compressor parts. The
model number begins with “ CCHH”
and the nameplate is located on the
foot of the volute.
Digit 1, 2 — Unit Function
Digit 3 — Drive
Digit 4 — Development
Trane recommends that indoor CenTraVac unit
installations fully meet or exceed the guidelines of the
current version of ASHRAE Standard 15, in addition to any
applicable national, state, or local requirements. This
typically includes:
•A refrigerant monitor or detector that is capable of
monitoring and alarming within the acceptable
exposure level of the refrigerant, and that can actuate
mechanical ventilation.
•Audible and visual alarms, activated by the refrigerant
monitor, inside the equipment room and outside of
every entrance.
•The equipment room should be properly vented to the
outdoors, using mechanical ventilation t hat can be
activated by the refrigerant monitor.
•The purge discharge and the rupture disk must be
properly piped to the outdo ors.
•If required by local or other codes, a self-contained
breathing apparatus should be available in close
proximit y to the equip ment room.
For the USA, refer to the latest copy of ASHRAE
Standard 15 for specific guidelines. Trane assumes no
responsibility for any economic, health, or environmental
issues that may result from an equipment room’s design
or function.
Unit Shipment
Inspect u nit while it is still on the truck for an y shipping
damage. The chiller ships shrink-wrapped in a 0.254 mm
(0.010-in.) recyclable film prot ective covering. Do not
remove shrink-wrap for inspection! Inspect for damage to
the shrin k-wrap and determine if physical damage has
occurred.
Each chiller ships from the factory as a hermetically
assembled package; it is factory-assembled, -wired, and
-tested. All openings except for the waterbox vent and
drain holes are covered or plugged to prevent
contamination during shipment and h andling.
p. 14
shows an illustration of a typical unit and its
components. As soon as the unit arrives at the job site,
inspect it thoroughly for damage and material shortages.
In addition:
1 . V erify the hermetic integrity of the unit by checking the
chiller pressure for an indication of holding charge
pressure.
2. To prevent damaging moisture from entering the unit
and causing corrosion, each chiller is pressurized with
20.7 to 34.5 kPag (3 to 5 psig) of dry nitrogen before
shipment.
Figure 3,
Note: The holding charge should register approximately
34.5 kPag (5 psig) at 22.2°C (72°F). P lace a gauge on
the access valve provided (indicated by arrow and
circle in the preceding figure) on the refrigerant
pump discharge line to verify the holding charge.
This access valve is located on the front o f the oil
tank, which is at the right rear corner of the chiller.
If the charge has escaped, contact your local Trane
sales office for instructions.
3. The loose parts box and isolator pads ship on top of the
control panel box.
4. Check the oil sump sight glasses to verify that the sump
was factory-charged with 79.5 L (21 gallons) of oil. The
oil level should be vi sible to about halfway in the top
sight glass. If no oil level is visible, contact your local
Trane sales office.
General Information
Regulations regarding waste handling are constantly
changing. T o ensure that personnel are in compliance with
the latest federal, state and local regulations, contact your
local waste management office for the proper procedures
on handling, disposal, transporting and storage of oil, oil
filters, refrigerant filters, and filter dryer cores.
Installation Requirements and
Contractor Responsibilities
A list of the contractor responsibilities typically associated
with the unit installation process is provided.
CVHH-SVX001A-EN11
Page 12
Pre-Installation
WARNING
Combustible Material!
F ailur e to follo w this ins truc tion could r esult in death or
serious injury or equipment damage. Shrink-w rap is a
combustible material. Avoid open flames and hot
sparks.
Note: The chiller should remain within its protective
shrink-wrap covering during storage.
Type o f
Requirem ent
Found ation• Meet foundation requirem ents
Rigging• Safety chains
Disassembly/ Reassembly
(as required)
Isolatio n• Isolation pads or spring
Electrical• Circuit breakers or fusible
Water piping• Flow sensing devices
Relief• Rupture disk assembly
Insulation• Insulation (optional)• Insulation
Water Piping Connection
Components
Other M aterials• Material and equipment to perform leak testing
Trane S upplied
Trane I nstalled
• Trane will per form or have
direct on-site supervision of
the disassembly and
reassembly work (contact
your local Trane office for
pricing)
disconnects (op tional)
• Unit m ounted starter
(optional)
• PFCCs (optional)
• RuptureGuard™ (optional)
Flanged (optional)
• Welded on flange for
2068.4 kPag (300 psig)
waterboxes
Trane Supplied
Field I nstalled
isolators
• Jumper bars
• Temperature sensor
(optional outdoor air)
• Flow switches (m ay be
field supplied)
• Remote-mounted starter
(optional)
(may be field supplied)
Flanged ( optional)
• Victaulic
®
adapter for 1034 .2 kPag
(150 psig) waterboxes
to flang e
Field Supplied
Field I nstalled
• Clevis c onnectors
• Lifting beam
• Isolation pads or s pring isolators
• Circuit breakers or fusible disconnects (opti onal)
• Electrical connections to unit m ounted starter
(optional)
• Electrical connections to remote mo unted starter
(optional)
• Wiring sizes per submittal and NEC or local codes
• PFCCs (rem ote mounted star t er optional only)
• Terminal lugs
• Ground connection(s)
• Jumper bars
• BAS wiring (optional)
• IPC wiring (AFD and remote-m ounted starters only)
• Control voltage wiring (AFD and rem ote- mounted
starters only)
• Oil pum p i nter lock wiring (AFD and remote m ounted
starters only)
• High con denser pressure interlock wiring (AFD and
remote mounted starters only)
• Chilled water pump contactor and wiri ng including
interlock
• Condenser water pump contactor and wiring including
interlock
• Option relays and wiring
• Taps for flow sensing devices
• Ta ps for therm ometers and gauges
• Thermometers
• Strainers (as required)
• Water flow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain on waterbox valves (one each per pass)
• Pressure relief val ves ( for waterboxes as required)
• Vent line and flex ible conne ctor and vent line from
ruptu re disk to atmosphere
• Chiller feet insulation
Victaulic
• Victaulic coupling for 1034.2 kPag ( 150 psig) and
2068.4 kPag (300 psig) waterboxes
• Fasteners for flanged-type connections (optional)
• Dry nitrogen (55.2 kPag [ 8 psig] maximum per
machine as needed)
12 CVHH-SVX001A-EN
Page 13
Pre-Installation
Type o f
Requirem ent
“CenTraVac™ Installation
Completion Check Sheet
and Request for Trane
Service”
(CTV-ADF001-EN; refer to
“Forms and Check Sheets,”
p. 102
)
Chiller start-up
com missionin g
(a) Start- up m ust be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products. Contractor shall
provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the
scheduled start-up.
( a)
Trane S upplied
Trane I nstalled
• Trane, or an agent of Trane
specifically authori zed to
perform start-up of Trane
pro ducts
®
Trane Supplied
Field I nstalled
Field Supplied
Field I nstalled
• To be completed by installing contractor prior to
contacting Trane for start-up
Storage Requirements
NOTICE:
Ins ulation Damage!
Do not expose unit to direct sunlight as it could result
in damage to factory-installed insulation.
Less than 1 m onth1– 6 monthsGreater than 6 m onths
Location requirem ents:
• solid foundation
• vibration free
• dry
• temperature range -40°C to 70°C
(-40°F to 158°F)
• Do not rem ove any plastic coverings• Do not remove any plastic coverings• Do not remove any plastic coverings
• Do not cha rge the chiller with refrigerant
• If additional refrigerant is on site, follow
manufactures storage require m ents
• Verify dry nitrogen pressure using gauge
located on the evaporator shell reads
20.7 to 34.5 kPag ( 3 to 5 psig)
• Notify the l ocal Trane office if charge has
escaped
• Do not operate purge unit• Do not operate purge unit• Do not operate purge unit
Note: Chillers stored 5 years or longer should be inspected every 5 years by a qualified service organ izat ion for leaks.
(a) If protective plastic coverings need to be removed for access and/or service, contact your local Trane office.
Location requirements :
• solid foundation
• vibration free
• dry
• temperature range -40°C t o 70°C
(-40°F to 158°F)
• Do not cha rge the chiller with refrigerant
• If additiona l refrigerant is on site, follow
manufactures storage requirements
• Verify dry nitrogen pressure using gauge
located on the evaporator shell reads
20.7 to 34.5 kPag ( 3 to 5 psig)
• Notify the local Trane office if ch arge has
escaped
• Verify waterbox and tube bundles are
clean and dry
Location requ irements:
• solid foundation
• vibration free
• dry
• temperature range -40°C to 70°C
(-40°F to 158°F)
• Do not charge the chiller with refrigeran t
• If additiona l refr igerant is on site, follow
manufactures storage requirements
• Verify dry nitrogen pressure u sing gauge located
on the evaporator shell reads 20.7 to 34.5 kPag
(3 to 5 psig)
• Notify the local T rane office if charge has escaped
• Verify waterbo x and tube bundles are clean and
dry
• Conduct an oil analysis and verify no oil
breakdown
• Repeat yearly
• Replace oil if breakdown has occurred
• If no oil analysis pro gram has been followed,
replac e oil prior to start up
(a)
CVHH-SVX001A-EN13
Page 14
Pre-Installation
1
2
3
4
0
-
0
6
7
5
9
8
Unit Components
No te: The control p a nel side of the unit is always
designated as the front side of the unit.
Figure 3.Typical Simplex CVHH CenTraVac chiller
1.Suction Elbow
2. Comp ressor
3. Terminal Box
4. Control Panel
5. Condenser
6. Motor Housing
7.Economizer
8. Oil Tank Assembly
9. Purge
10. Evapo rat or
11. Display Panel
14 CVHH-SVX001A-EN
Page 15
Unit Clearances and Weights
Optional unit
mounted
starter
Condenser
Evaporator
Econom izer
Motor
B
A
E
Right hand tube pull shown,
apply tube pull clearance
dimension to left end for
left hand tube pull.
These dim ensions per
NEC Article 110
46 cm (18 in.)
C
D
92 cm (3 ft)
Recommended Unit Clearances
Adequate clearances around and above the chiller are
required to allow sufficient access for service and
maintenance operations. Specific unit clearan ce
requirements are indicated in the submittal package
provided for y our unit.
•Do NOT install piping or conduit above the compressor
motor assembly or behind the suction elbow of the
unit.
Figure 4.Clearance requirements
•Minimum vertical clearance above the unit is 92 cm
(3 feet).
•Use a housekeeping pad to provide bet ter service
clearances; refer to submittal for more infor mation.
Per NEC Article 110: Unit mounted starters from 0–600V
require a 107 cm (42 inch) clearance, 601–2500V require a
122 cm (48 inch) clearance, and 2501–9000V require a
152 cm (60 inch) clearance. Refer to NEC and local
electrical codes for starter and control panel clearance
requirements.
(a) All dimensions are approximate; refer to the unit submittal package for exact dimensions for your unit .
cmin.cmin.cmin.cmin.cmin.
General Weights
The unit weight information provided in
be used f or general information purposes only. Trane
does not recommend using this weight information for
considerations relative to chiller handling. The large
number of variances between chiller selections drives
vari ances in chiller weights that are not recognized in
this table. For specific we ights for your chiller, refer to
your submittal package.
The values in
the following:
• TECU 0.028-i n. (0.71 mm) tube wall.
• 1034.2 kPag (150 psig) non-mari ne waterboxes.
Table 2 representing chiller weights include
(a)
Tab le 2 should
• Chillers with starter weights i nclude the weight of
the h eaviest possible starter.
• Heaviest possible bundle and heaviest possible
motor combination for the application family
chiller.
The values in
Table 2 representing chiller weights do NOT
include the following options:
• INDP (Industrial Contr ol Panel) option—add 23 kg
(50 lb)
• CPTR (Control Panel Transformer) option—add
127 kg (280 lb)
• SMP (Supplemental Motor P rotection) option—add
230 kg (500 lb)
• Oper atin g weights in clude the largest possible
refrigerant charge.
•The stan dard chille r is designed for indoor use only
and as such has NEMA Type 1 or IP 20 enclosures.
•For chillers in unheated equipment rooms, contact
your local Trane service agency for methods to ensure
that the oil temperature is maintained suitable for
proper operation of the chiller.
T o ensure that electrical components operate properly, do
not locate the chiller in an area exposed to dust, dirt,
corrosive fumes, or excessive heat and humidity. The
ambient temperature range for chiller operation is 1.1°C to
40°C (34°F to 104°F).
NOTICE:
E quipment Failure!
Unit operating at ambient temperatures exceeding
40°C (104°F) could result in starter component damage
due to the panel’s inabili ty to dissipate heat adequately .
If any of these adverse operating conditions are
present, take necessary action to improve the
equipment room environment.
Foundation Requirements
Chiller mounting surface must be:
• rigid non-warping mounting pads or a concrete
foundation.
• able to support the chiller at its full operating weight
(including completed piping, and full operating
charges of refrigerant, oil and water.)
F or proper unit operation, the chiller must be level within
1.6 mm (1/16 in.) over its length and width when set into
place on the mounting surface.
approximate weights for various chiller sizes and options.
Note: For specific weigh t information, refer to the unit
submittal package.
Important: Tran e will not assume responsibility for
equipment problems resulting from an
improperly designed or constructed
fou ndation.
Table 2, p . 16 shows
Rigging
Lifting is the recommended method for moving chillers.
Suggested lifting arrangements for standard units are
described in
Note: The lifting beam used for Simplex units must be at
“ Standard Chiller Lift,” p. 17.
least 4.572 meters (15 feet) long.
WARNING
Heavy Objects!
Failure to properly lift unit could result in death or
serious injury, or equipment or property-only damage.
Do not use cables (chains or slings) except as s hown in
Figure 5, p. 18. Each of the cables (chains or slings)
used to lift the unit must be capable of supporting the
entire weight of the unit. Lifting cables (chains or
slings) m ay not be of the same length. Adjust as
necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit could result in death or
serious injury, or equipment or property-only damage.
•T es t lift unit approximately 61 c m (24 inches ) to verify
proper center of gravity lift point. T o a v oi d dropping
of unit, reposition lifting point if unit is not level.
•Do not lift chiller utilizing waterbox lifting lug.
Waterbox lifting lug is to be used only f o r removing
waterbox from chiller.
•Do not lift chiller utilizing elbow lifting tab. Elbow
lifting tab and approved clevis are used when
removing elbow from chiller.
NOTICE:
W iring Damage!
Damage to unit wiring could result in equipment
failure. Care must be t aken during rigging, assembly
and disassembly to avoid damaging unit wiring.
Standard Chiller Lift
1. Insert clevis connections at the points indicated in
Figure 5, p. 18. A 63.5 mm (2.5 in.) diameter lifting hole
is provided at each of these points.
2. Attach the lifting chains or cables.
3. Once the lifting cables are in place, attach a safety chain
or cable between the first-stage casing of the
compressor and the lifting beam.
Important: There should not be tension on this safety
cable; the cable is used only to prevent the
unit from rolling during th e lift.
4. Position isolator pads or spring isolators beneath the
chiller feet (refer to
instructions).
Note: Follow instructions provided by the spring
isolator man ufacturer, being careful to not
damage isolator adjustment bo lt.
“ Unit Isolation,” p. 19 for
CVHH-SVX001A-EN17
Page 18
Installation: Mechanical
Safety
chain or
cable
Jack slots
4.572 meters
(15 feet)
minimum
effective length
5. Once the isolators are in place, lower the chiller—
working from end to end—in small increments to
mai ntain stability.
6. When lift is complete, detach the clevis co nnection s
and safety chain.
Figure 5.Typical rigging arrangements for Simplex
units
Spec ial Lift Requirements
NOTICE:
Oil Loss!
F ailure to prevent oil migration out of the oil tank could
res ult in equipment failure or proper ty-only damage. To
prevent oil migration out of the oil tank during lifting
procedures, remove the oil from the oil tank if the unit
will be lifted at any angle greater than 15° from
horizontal end-to-end. If oil is allowed to run out of the
oil tank into other areas of the chiller, it will be
extremely difficult to return the oil to the oil tank even
during operation.
NOTICE:
Equipment Damage!
Moving the chiller using a fork lift could result in
equipment or property-only damage. Do not use a fork
lift to move the chiller!
NOTICE:
Compressor Alig nment!
Failure to preserve compressor alignment could result
in equipment or property-only damage. Lifting the
compressor/motor assembly from the shells without
factory-installed doweling in the compressor casting
flanges could result in misalignment of the compres sor
castings.
If the chiller cannot be moved using a standard chiller lift,
consider the following:
•When job site conditions require rigging of the chiller
at an angle greater than 45° from horizontal (end-toend), the unit may require removal of the compressor.
Contact Trane or an agent of Trane specifica lly
authorized to perform start-up and warranty of T rane
products reg arding the disassembly and reassembly
work. For more information, refer to
Information,” p. 4
Note: Disassembly and reassembly work includes
dowel-pinning the compressor and removing it
from the unit. Contact Trane or an agent of
Trane specifically authorized to perform startup and warranty of T rane
rigging instructions. Do NOT attempt to rotate
the chiller onto its side.
•When lifti ng the chiller is either i mpractical o r
undesirable, attach cables or chains to the jacking slots
shown in
across a smooth surface. Should the chiller be on a
shippin g skid, it is not necessary to remove the skid
from the chiller before moving it into place.
•If removal of the compressor or economizer assembly
is necessary to move the chiller to the operating
Figure 5, p. 18; th en push or pull the unit
.
“ Factory Warranty
®
products for specific
®
18 CVHH-SVX001A-EN
Page 19
Installation: Mechanical
228.6 mm
(9 in.)
457.2 mm
(18 in.)
9.525 mm
(3/ 8 in.)
Condenser
Evaporator
Length
2
5
1
4
6
3
Width
I solator Configuration 1
Origin:
Right front corner of
evap right front foot
Condenser
Evaporator
Length
2
5
1
4
6
3
Evap
Width
Width
I solator Configuration 2
location, contact T rane. F or more information, refer to
“ Factory Warranty Information,” p. 4.
Unit Isolation
T o minimize sound and vibration transmission through the
bui lding structure, and to ensure proper weigh t
distribution over the mount ing surface, always install
isolation pads or spring is olators under the chiller feet.
No te: Isolation pads (see
Figure 6) are provided with each
chiller unless spring isolators are specified on the
sales order.
Specific isolator loading da ta is provided in the unit
submittal package. If necessary, contact your local Trane
sales office for further information.
Important: When determining placement of isolation
pads or spring isolators, remember that the
control panel side of the unit is always
desig nated as the uni t front.
Isolation Pads
When the unit is ready for final placement, position
isolation pads (457.2-mm sides) end for end under the full
length of the chiller leg. The pads measure 228.6 mm x
457.2 mm (9 in. × 18 in.) and on some units there may be
small gaps between pads. Pads are provided to cover
entire foot.
Figure 6.Is olation pad and dimensions
Remember that the chiller must be level within 1.6 mm
(1/16 in.) over its length and width after it is lowered onto
the isolation pads. In addition, all piping connected to the
chiller must be properly isolated and supported so that it
does not place any stress on the unit.
Spring Isolators
Spring isolators should be considered whenever chiller
installation is planned for an upper story location. Base
isolator placement is shown in
Table 3.
CVHH-SVX001A-EN19
Figure 7; also refer to
Figure 7.Isolation spring placement by shell size,
evaporator and condenser lengt h
Table 3.Isolation spring placement, cm (in.)
Origin
to
to
Center
of
Middle
Pad
153.7
(60.5)
171.5
(67.5)
153.7
(60.5)
171.5
(67.5)
138.4
(54.5)
153.7
(60.5)
138.4
(54.5)
N/A
N/A
N/A
N/A
N/A
EVSZ CDSZ W idt h
200L200L
220L220L
200L20HL
220L22HL
160M 20HM
200L220L
160M 200M
100M 100M
100L100L
130M 130M
100M 10HM
130M 13HM
285.0
(112.2)
303.3
(119.4)
336.0
(132.3)
361.0
(142.5)
323.3
(127.3)
285.2
(112.3)
270.3
(106.4)
264.4
(104.1)
264.4
(104.1)
277.6
(109.3)
300.2
(118.2)
313.4
(123.4)
Evap
Width Length
170.2
457.2
(67)
(180)
188.0
457.2
(74)
(180)
170.2
457.2
(67)
(180)
188.0
457.2
(74)
(180)
154.9
406.4
(61)
(160)
170.2
457.2
(67)
(180)
154.9
406.4
(61)
(160)
406.4
N/A
(160)
457.2
N/A
(180)
406.4
N/A
(160)
406.4
N/A
(160)
406.4
N/A
(160)
I solator
Config
2
2
2
2
2
2
2
1
1
1
1
1
Origin
Center
of Rear
Pad
268.5
(105.7)
286.8
(112.9)
319.5
(125.8)
345.4
(136)
306.8
(120.8)
268.7
(105.8)
253.7
(99.9)
247.9
(97.6)
247.9
(97.6)
261.1
(102.8)
283.7
(111.7)
296.9
(116.9)
Spring isolators typically ship assembled and ready for
installat ion. To install and adjust the isolators properly,
follow the instructions given.
Page 20
Installation: Mechanical
Side View of UnitEnd View of Unit
Outside edge
of tube sheet
Center tube
sheet
support leg
Center of
isolator
spring
Note: The spring isolator must be cent ered
in relation to the tube sheet. Do not
align the isolator with the flat part of
the chiller foot since the tube sheet is
often off center
Note: The length of the
isolator should
be parallel to the
leg.
Note: Do not adjust the isolators until the chiller is piped
and charged with refrigerant and water.
1 . Position the spring isolators under the chiller as shown
in
Figure 7. Ensure that each isolator is centered in
relation to the tube sheet.
No te: Spring isolators shipped with the chiller may
not be identical. Compare the data provided in
the unit submittal package to determine proper
isolator placement.
2. Set the isolators on the sub-base; shim as necessary to
provide a flat, level surface at the same elevation for
the end supports.
Important: Support the full underside of the isolator
base plate; do NOT straddle gaps or small
shims.
3. If required, bolt the isolators to the floor through the
slots provided, or cement the pads.
Note: Fastening the isolators to the floor is not
necessary unless specified.
4. If the chiller must be fastened to the isolators, insert
capscrews through the chiller base and into holes
drilled and tapped in the upper housing o f each
isolator.
Important: Do NOT allow the screws to protrude below
the underside of the isolator upper housing,
or interfere with the adjusting bolts. An
alternative method of fasteni ng the chiller
to the isolators is to ceme nt the neoprene
pads.
5. Set the chiller on the isolat ors; refer to
Chiller Lift,” p. 17
. The we ight of the chiller will force
down the upper housing of each isolator, and could
cause it to rest on the isolator’s lower housing (refer to
Figure 8).
“ Standard
.
Figure 8.Chiller foot and isolator orientation
6. Check the clearance on each isolator. If this dimension
is less than 6.35 mm (1/4 in.) on an y iso lator , use a
wrench to turn the adjusting bolt one complete
revolution upward.
Note: When the load is applied to the isolators (
Step 5),
the top plate of each isola tor moves down to
compress the springs until either the springs
support the load or the top plate rests on the
botto m housing of the isolator. If the springs are
supporting the load, screwing down on the
adjusting bolt (
Step 7) will raise the chiller.
7. Turn the adjusting bolt on each of th e remaining
isolators to obtain the required minimum clearance of
6.35 mm (1/4 in.).
8. Once the minimum required clearance is obtained on
each of the isolators, level the chil ler by turning the
adjusting bolt on each of the isolators on the low side
of the unit. Work from one isol ator to the next.
Important: The chiller must be level to within 1.6mm (1/
16 in.) over its length and width, and the
clearance of each isolator must be at least
6.35 mm (1/4 in.).
Leveling the Unit
20 CVHH-SVX001A-EN
The chiller must be set level within 1.6 mm (1/16 in.).
1 . Measure and make a punch mark an equal distance up
from the bottom of each foot of the chiller.
Page 21
Installation: Mechanical
2
1
2. Suspend a clear plastic tube along the length of the
chiller as shown in the following figure.
3. Fill the tube with water u ntil the level aligns with the
punch mark at one end of the chiller.
4. Check the water level at the opposite mark. If the water
level does not align with the punch mark, use full
Figure 9.
Note: Use of a laser level is an acceptable alternative
method to level the unit.
Important: Immediately report any unit damage
incu rr ed during handling or installation at
the job site to the Trane sales office.
length shims to raise one end of the chiller until the
water level at each end of the tube aligns with the
punch mar ks at both ends of the chiller.
5. Once the unit is level across its length, repeat
through
Step 3 to level the unit across its width.
Step 1
CVHH-SVX001A-EN21
Page 22
Installation: Water Piping
Overview
The following water piping circuits must be installed and
connected to the chiller:
•Pipe the evaporato r in to the chilled water circuit.
•Pipe the condenser into the cooling tower water circuit.
•Optional: A heat-recovery condenser water circuit.
•Optional: An auxiliary condenser water circuit.
No te: Piping must be arranged and supported to avoid
stress on the equipment. It is strongly
recommended that the piping contractor does not
run pipe closer than 0.91 m (3 feet) minimum to the
equipment. This will allow for proper fit upon
arrival of the unit at the job site. Any adjustment
that is necessary can be made to the piping at that
time. Expenses that result from a failure to follow
this recommendation will not be pai d by Trane.
Piping suggestions for each of the water circuits listed
above are ou tli ned in
Piping,” p. 25
installation of field supplied piping compon ents (e.g.,
valves, flow switches, etc.) common to most chiller water
circuits are listed below.
. General recommendations for the
“ Evaporator and Condenser Water
Water Treatment
The use of untreated or improperly treated water in a
CenT raVac may result in inefficient operation and possible
tube damage.
Important: Trane strongly recommends using the
services of a qualified water treatment
specialist to determine necessary water
treatment. A lab el with a customer
disclaimer note is affixed to each unit.
NOTICE:
P roper Water Treatment!
Trane assumes no responsibility for equipment failures
which result from untreated or improper l y treated
water, or saline or brackish water. The use of untreated
or improperly treated water in a CenTraVac could result
in scaling, erosi on , corrosion, algae or slime. It is
recommended that the services of a qualified water
treatment specialist be engaged to determine what
water treatment, if any, is required.
Pressure Gauges
Valves—Drains and Vents
NOTICE:
W aterbox Damage!
Failure to follow instructions could res ul t in damage to
the waterbox. Do not over-tighten or use excessive
Tef lon® pipe tape when installing valves, drains, plugs
and vents on waterboxes.
1 . Install field-supplied air vents and drain valves on the
waterboxes. Eac h waterbox is provided with a National
Pipe Thread Female (NPTF ) vent and drain connection;
the openi ngs are 19.05 mm (3/4 i n.).
NOTICE:
Over-pressurization!
Failure to install pressure-relief valv es in the condenser
and evapora tor water circuits could result in waterbox
damage due to hydrostatic expansion.
2. If necessary for the application, install pressure-relief
valves at the drain connections on the evaporator and
condenser waterboxes. To do so, add a tee with the
relief valve attached to the drain valve. Fol low local
codes for determining if drai n connection is large
enough for relief devices.
T o determine whether or not pressure relief valves are
needed for a specific application, keep in mind that:
a. Vessels with close-coupled shutoff valves may
cause high potentially damaging hydrostatic
pressures as fluid temperature r ises.
b. Relief valves are required by American Society o f
Mechanical Engineers (A SME) codes when the
waterside is ASME. Follow ASME guidelines or
other applicable codes/local regulation to ensure
proper relief valve installation.
Strainers
NOTICE:
Tube Damage!
Failure to install strainers in all water piping entering
the chiller could result in tube plugging conditions that
damage unit components.
Locate pressure gauge taps in a straight length of pi pe.
Place each tap a minimum of one pipe diameter
downstream of any elbow, orifice, etc. F or example, for a
152.4 mm (6 in.) pipe, the tap would be at least 152.4 mm
(6 in.) from any elbow, orifice , etc.
22 CVHH-SVX001A-EN
Install a strainer in the entering side of each piping circuit
to av oid possible tube plugging in the chiller with debris.
Required Flow-Sensing Devices
The ifm efector® flow detection controller and sensor (see
“ Water Flow Detection Controller and Sensor—ifm
Page 23
Installation: Water Piping
Components:
A.E40174– 1/2" NPT adapter (for ow probe)
B. SF6200– Flow probe
C. SN0150– Flow control monitor
D.E70231– Combicon connectors (quantity 5)
E.E10965– Micro DC cable, 10m length, PUR jacket
F.F53003– Din rail, 40mm length
Output to
control cabinet
Jumper
N
L
AC
Jumper
monitoring
rated using
monitoring
rail (F) into control cabinet.
in combicon connectors (D) according to
4
3
2
1
If factory-provided,
located in control panel.
efector,” p. 23) are used to verify evap orat or and
condenser water flows.
If a customer-suppl ied flow sensing device is used to
ensure adequate chiller protection, refer to the wiring
diagrams that shipped with the unit for specific electrical
connections.
Be sure to follow the manufacturer’s recommendations for
device selection and installation.
Water Flow Detection Controller and Sensor—ifm
efector
Figure 10. Installation of ifm efec tor flow detection
controller and sensor
2. Insert the flo w probe through the 1/2-in. NPT adapter
as near the center of the pipe as p ossible (see item
labeled “ 2” in
Figure 10, p. 23). Finger-tighten the
1/2-in. NPT adapter; then, tighten with a wrench an
additional 1-1/4 turns.
Note: When installed, the tip of the ifm efector sensor
probe must be at least 2.54 cm (1 in.) away from
any pipe wall. Placing the tip of the probe at the
center of the pipe is preferred.
3. Install the Micro DC Cable by inserting it through the
wire openings on the back side of the control panel (see
item labeled “ 3” in
Figure 10, p. 23). Install the
supplied Micro DC C able (9 meters [25 feet] in length)
to the Flow Probe and hand-tighten the connector nut.
4. Plug the other end of the Micro DC C able into the Flow
Control Monitor with the Combicon connector (see
item labeled “ 4” in
Figure 10, p. 23). R efer to Figure 11
for cable wiring.
1. Mount the 1/2-in. NPT adapter in a horizonta l or
vertical section of pipe. The maximum distance from
the control panel must not exceed 8.99 meters (29.5 ft)
(see item labeled “ 1” in
five pipe diameters straight run of pipe upstream of the
sensor location, and three pipe diameters straight run
of pipe downstream of the sensor location.
No te: In the case of a horizontal pipe, mounting the
CVHH-SVX001A-EN23
Figure 10, p. 23). Allow at least
sensor in the side of the pipe is preferred. In the
case of a vertical pipe, mounting the sensor in
a place where the water flows upwards is
preferred.
Page 24
Installation: Water Piping
X39003892001A
7
NOTICE:
Do Not Apply Elec tric al Power to a Unit in
a Vacuum!
Failure to disconnect power to units with
inside-the-delta solid state starters during evacuation
or when the unit is in a deep vacuum could cause
compressor motor damage. Applying electrical power
to a motor in a vacuum could cause damage to the
motor. In addition, on units with inside-the-delta solid
state starters, all power to the unit must be
disconnected prior to evacuating the unit as line power
is directly applied to the motor terminals 4, 5, and 6.
flow setting cutout and adjusting counterclockwise (-)
increases the flow setting cutout.
Note: The “ Temp” potentiometer on the ifm efector
control module has no effect in Trane
application. It is not necessary to make
adjustments to the “ Temp” potentiometer.
8. Once the cutout setting is adjusted, the cutout setpoint
will be indicated with a yellow light on the Flow Control
Monitor LED bar graph display. When the water flows
are higher than the cutout, a green light will indicate
proper flow status. If the flows fall below the cutout
setpoint, a red light will indicat e low/no flow status.
Evaporator and condenser water circuits require proof
of flow switches.
•Failure to include the proof of flow devices and/or
jumping out these devices could cause the unit to
stop on a secondary level of protection.
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharg e.
•All electrical enclosures—unit or remote—are IP2X.
5. Apply power to the chiller control panel to verify the
Flow Control Monitor has power and the Low Volt
Broken Wire Re lay light is not lit .
6. Remove all air from the piping circuit prior to adjusting
the low water flow setpoint.
7. Reduce the water flow to the minimum allowable flow
and adjust the Flow setting on the Flow Control
Monitor (see item labeled “ 7” in
the “ Flow” potentiometer clockw ise (+) reduces the
Figure 11). Adjusting
•Frequent cycling on these higher level diagnostic
devices could c ause excessive thermal and pressure
cycling of unit components (O-rings, gaskets,
sensors, motors, controls, etc.) and/or freeze
damage, resulting in premature failure of the chiller.
Failure to provide flow switches or jumping-out of
switches could result in severe equipment damage.
Evaporator and condenser proof of flow switches are
required. These switches are u sed with control logic to
confirm flow prior to starting a unit and to stop a running
unit if flow is lost. For trouble shooting, a viewable
diagnostic is generated if a proof of flow switch does not
close when flow is required.
24 CVHH-SVX001A-EN
Page 25
Installation: Water Piping
44
445
5
3
3
7
2
21
9
6
2
2
8
Ou tlet
Inlet
1
2
3
45678
9
2
34
445
2
2
10
Outlet
Inlet
Evaporator and Condenser Water
Piping
Figure 12 and Figure 13, p. 25 illustrate the recommended
(typical) water piping arr angements for the evaporator
and condenser.
Figure 12. Typical evaporator water piping circuit
1.Balancing Valve
2. Gate (Iso lation) Valv e or Ball
Valve
3. Thermometer (if field supplied)
4. Waterbox Nozzle Connection
5. Drain, Vent, Anode
(a) Flow switch 4B4 may be installed in either the entering or leaving leg
of the chilled wat er circuit.
(b) It is recom mended to pipe the gauge between entering and leavin g
pipes. A shutoff valve on each side of the gauge allows the operator to
read either entering or leaving water pressure.
Figure 13. Typical c o nd en ser water piping circuits
1.Balancing Valve
2. Gate (Iso lation) Valv e or Ball
Valve
3. Thermometer (if field supplied)
4. Waterbox Nozzle Connection
5. Drain, Vent, Anode
Notes:
1 . Som e type of field-supplied temperature control device may be
required to regulate the temperat ure of the heat-recovery condenser
water circuit . For application recom mendations, refer to Heat Recovery Sem inar ( Part 2): "Systems/Equipm ent (AM- FND-8).
2 . Install a bypass valve system to avoid circulating water through the
auxiliary shell when the unit is shut down.
3 . On m ultiple pass condensers, entering condenser water must ent er at
the lowest nozzle.
(a) Flow switch 4B5 may be installed in either the entering or leaving leg
of the water circuit.
(b) It is recomm ended to pipe a single gauge bet ween entering and leaving
pipes.
CVHH-SVX001A-EN25
6. Strainer
7.Chilled Water Flow Switch
8. P ump
9. Pressure Gauge
6. Strainer
7.Condenser Water Flow
Switch (4B5)
8. 3-Way Valve (Optional)
9. Condenser Water Pump
10. Pressur e Gauge
(4B4)
Piping must be arranged and supported to avoid stress on
the equipment. It is strongly recommended that the piping
contractor does not run pipe closer than 0.91 meters
(3 feet) minimum to the equipment. This will allow for
proper fit upon arrival of the unit at t he jo b site. Any
adjustment that is necessary can be made to the piping at
that time. Expenses that result from a failure to follow this
recommendation will not be paid b y Trane.
Water piping connection sizes and components are
identified in
Table 4, p . 26 and Table 5, p. 27. Remember
that with many waterboxes the entering and leaving
evaporator water can be piped to either waterbox
connection when the tube bundles are split vertically.
However, large evaporator waterboxes, with entering and
leaving connections not at the same level, must be
connected with the entering water at the bottom and the
leaving water at the top.
Waterboxes with multip le pass arrangements uti lize a
baffle to separate the passes. These baffles are designed
for a maximum pressure of 137.9 kPad (20 psid). If larger
pressure drops are expected in the application, contact
(a)
(b)
your local Trane repr esentative to discuss special
waterbox options.
Impor tant: Water flows must be pi ped i n accordance
with nameplate designation.
Field-provided isolation valves for the evaporator and
condenser water lines should be installed upstream and
downstream of the heat exchangers, and be installed far
enough away from the chiller to also provide practical
service isol ation for flow sensing devices, field
thermometers, flexible connectors, and any removable
pipe spools.
Ensure that the evaporator water piping is clear, check it
after the chilled water pump is operated but before initial
chiller start-up. If any partial blockages exist, they can be
detected and removed to prevent possible tube damage
resulting from evaporator freeze-up or erosion.
For condenser and large evaporator connections, arrange
the water piping so that the water supply enters the shell
at the lower connection, and exits from the top connection.
Operation al problems may result if this piping is n ot
correct. Some shells may be piped as desired since both
connections are at the same level.
(a)
For applications th at include an “ infinite source” or
“ multiple-use”, cooling condenser water supply, install a
valved bypass “ leg” (optional) between the supply and
(b)
return pi pes. This valved bypass allows the operator to
short-cir cuit water flow through the cooling condenser
when the supply water temperature is too low.
Note: System refrig erant pressure differential must be
maintained ab ove 20.7 kPad (3 psid) at all times.
Fa ilure to do so could result in operating problems.
Page 26
Installation: Water Piping
Water Piping Connections
All standard units use grooved-pipe connections. These
are grooved-end NSP (Victaulic style) pipe connections.
Flanged connections are optional.
Piping joined using grooved type couplings, like all types
of piping systems, requires proper support to carry the
weight of pipes and equipmen t. The support methods
used must eliminate undue stresses on joints, piping and
other components; allow movement where required, and
provide for any other special requirements (i.e., drainage,
etc.).
Note: Plug-type sensor extension cables are available for
purchase from Trane P arts Service if needed. These
sensor extension cables may be necessary if the
waterboxes are changed or if the temperature
sensors are moved out into the unit pip ing for
better mixed temperature readings.
Do Not Exchange Positions of Heat
Recovery Waterboxes!
Failure to follow this instruction could prevent proper
unit operation. Contact CenTraVac Technical Service for
switching of heat recovery waterboxes.
If necessary, the non-marine-style waterboxes on each
shell whether evaporator o r condenser can be switched
end-fo r-end to obtain the desired piping arrangement.
If removal of waterboxes is necessary, refer to
Removal and Installation,” p. 98
.
If the waterboxes on any of the shells are exchanged endfor-end, be sure to reinstall them right side up to maintain
the correct baffle arrangements. Use a new gasket with
each waterbox cover.
“ Waterbox
Page 27
Installation: Water Piping
Water Box
Flange AdaptorTrane Provided
Flanged
Wat erbox
Flange Adaptor
Tra n e prov ided
Water Box
Style 77 Flexible
Customer Provided
Customer
Victaulic
Wat erbox
Style 77 Flexible
Customer provided
Customer
Three-pass waterboxes have lifting lugs on the top and
bottom. When reinstalling, ensure that the waterbox is
oriented the same way it as removed.
Grooved Pipe Coupling
A customer-supplied, standard flexible groo ved pipe
coupling (Victaulic Style 77 or equivalent) should be used
to complete the Victaulic connection for both 1034.2 kPag
or 150 psig and 2068.4 kPag or 300 psig waterboxes.
When a flexible coupling such as this is installed at the
waterbox connections, other flexible piping connectors
(i.e., braided-steel, elastomeric arch, etc.) are usually not
required to attenuate vibration and/or prevent stress on
the connections.
Table 5.Water piping connection components
Custom er Piping Connection
Unit Model
CVHH
CVHHVictaulic (All others)
Figure 15. Customer piping connection types
•Refer to the coupling manufacturer’s guidelines for
specific information concerning proper piping system
design and construction methods for grooved water
piping systems.
•Flexible coupling gaskets require proper lubrication
before installation to provide a good seal. Refer to the
coupling manufacturer’s guidelines for proper
lubricant type and application.
Flange-Connection Adapters
When flat-face flange connections are specified, flange-togroove adapters are provided (Victaulic Style 741 for
1034.2 kPag or 150 psig systems; Style 743 for 2068.4 kPag
or 300 psig systems). The adapters are shipped bolted to
one of the chi ller end-supports. A dapter descripti ons are
Unit Connection
TypeVictaulicFlanged
Flanged (Condenser
032–050 150 psig
[103 4.2 kPag] non-
marine only)
Customer
provided
Victaulic coupling
No adapter
required
Trane provided
Victaulic-to-
flang e adapter
given in
Table 6, p . 28 and Table 7, p. 28. The flange
adapters provide a direct, rigid connection of flanged
components to the grooved-pipe chiller waterbox
connections.
Figure 16. Typical shipping location for flange
In this case, the use of flexible type connecto rs (i.e.,
braided steel, elastomeric arch, etc.) are recommended to
attenuate vibration and prevent stress at the waterbox
connections. Flange adapter s are no t provided for CVHH
units with 2068.4 kPa or 300 psig waterboxes that hav e
356 mm (14 in.) and larger piping connections.
All flange-to-flange assembly bolts must be provided by
the installer. Bolt sizes and number required are given in
Table 6, p. 28 and Table 7, p. 28. The four draw-bolts
needed for the 355.6 mm (14 in.) and larger Style 741
(1034.2 kPag or 150 psig) adapters are provided. The
Style 741, 1034.2 kPag or 150 psig flange adapter requires
a smooth, hard surface for a good seal.
Connection to other type flange faces (i.e., raised, serrated,
rubber, etc.) will require the use of a flange washer
between the faces. Refer to the flange adapter
manufacturer’s guidelines for specific information.
The Style 743 (2068.4 kPa or 300 psig) flange adapters are
designed to mate with raised-face flanges. They can be
used with flat-faced flanges; however, only if t he raised
projections on the outside face of the adapter are
removed; see
Figure 17. The flange-adapter gasket must
be placed with the color-coded lip on the pipe and the other
lip facing the mating flange.
NOTICE:
Piping Connection Leaks!
Failure to provide effective seal could result in
equipment or property-only damage. To provide
effective s eal, gasket contact surfaces of adapter must
be free of gouges, undulations or deformities.
CVHH-SVX001A-EN27
Page 28
Installation: Water Piping
Remove to mate
to flat-faced
flanges
Figure 17.Modifying 300 psig or 21 bar flange adaptors
3. Align and bring two pipe ends together and slide
Victaulic Gasket Installation
gasket into position centered between the grooves on
each pipe. No portion of the gasket should extend into
1. Inspect supplied gasket to b e cert ain it is suited for
intended service (code identifies gasket grade). Apply
a thin coat of silicone lubricant to gasket tips and
outside of gasket.
2. Install gasket, placing gasket over pipe end and making
sure gasket lip does not overh ang pipe end. Refer to
Figure 18 f or gasket configuration.
the groove on either pipe.
4. Open fully and place hinged Victaulic flange around
the grooved pipe end with the circular key section
locating into the groove.
5. Insert a standard bolt through the mating holes of the
Victaulic flange to secure the flange firmly i n the
groove.
6. Tighten fasteners alternately and equally until housing
bolt pads are firmly together (metal to metal); refer to
“ Bolt-Tightening Sequence for Water Piping
Connections,” p. 29
. Do not excessivel y tighten
fasteners.
Note: Uneven tightening may cause gasket to pinch.
Table 6.Installation data for 150 psig flange adapters (Style 741)
Nominal Pipe Size
As sem bly Bolt
mmin.in.mmin.kglb
20083/ 4 x 3-1/2829811.757.516.6
250107/8 x 41236214.251124.2
300127/8 x 4124321721.246.8
350141 x 4-1/ 21247618.7528.162
400161 x 4-1/ 21654021.2535.879
450181-1/ 8 x 4-3/ 41657822.7537.382.3
500201-1/ 8 x 5-1/ 4206352546.9103.3
600241-1/ 4 x 5-3/ 42074929.564.4142
(a) Bolt size for conventional flange to flange connect ion. Longer bolts are required when flange washer m ust be used.
Size
( a )
Number of
Assem bly Bolts
Required
Bolt Pattern Diam eterWeight
Table 7.Installation data for 350 psig flange adapters (Style 743)
Nominal Pipe Size
mmin.in.mmin.kglb
219.183/ 4 x 4-3/ 4123301315.634.3
273.0101 x 5-1/ 41638715.2521.948.3
323.9121-1/ 8 x 5-3/ 41645117.7532. 070.5
(a) Bolt size for conventional flange to flange connect ion. Longer bolts are required when flange washer m ust be used.
Assem bly Bolt
Size
( a)
Number of
As sem bly Bolts
Required
Bolt Pattern Diam eterWeight
28 CVHH-SVX001A-EN
Page 29
Bolt-Tightening Sequence for
1
3
45
7
8
26
8 bolt flange
1
3
4
1011
9
5
7
8
12
26
12 bolt flange
1
1
5
5
9
9
20
22
3
3
4
4
66
7
7
8
8
10
10
19
18
17
16
16
15
15
14
14
13
13
12
12
11
11
16 bolt flan ge20 bolt flan ge
Water Piping Connections
This section describes a bolt-tightening sequence for
flanges with flat gaskets or O-rings. Remember that
improperly tightened flanges may leak.
No te: Before tightening any of the bolts, align the flanges.
Flanges with 8 or 12 Bolts
Tighten all bolts to a snug tightness, following the
numerical sequence for the appropriate bolt pattern as
shown below. Repeat this sequence to apply the final
torque to each bolt.
Installation: Water Piping
Flanges with 16 or 20 Bolts
Tighten only the first half of the total number of bolts to a
snug tightness, following the numerical sequence for the
appr opriate bolt pattern as shown below. Nex t,
sequentially tighten the remaining half of the bolts in
numerical order.
Pressure Testing Waterside Piping
NOTICE:
E quipment Damage!
Failure to follow these instructions could result in
equipment damage. Do not over pressurize the system
or exceed design pressure. Always perform as a hydro
pressure test with water present in piping and
waterboxes.
Waterside design pressure is either 1034.2 or 2068.4 kP ag
(150 or 300 psig); refer to unit nameplate or to submittal
documentation.
CVHH-SVX001A-EN29
Page 30
Vent Piping
Refrigerant Vent Line
General Requirements
State and local codes, and ASHRAE Standard 15 contain
requirements for venting the relief device on the chiller to
the atmosphere outside of the building. These
requirements include, but are not limited to, permitted
mat erials, sizing, and pro per termination.
No te: The following information is a general outline of
vent-line installation requirements based on
ASHRAE Standard 15. Most codes contain similar
requirements but may vary in some significant
areas. The i nstaller must check state and local
codes and follow the specific requirements
applicable to the location.
Purge Discharge
To comply with ASHRAE Standard 15, the discharge
piping from purge units that remove noncondensible gas
from refrigerating systems must conform to the ASHRAE
Standard 15 requirements for relief piping. To h elp meet
this requirement, the purge discharge is factory-piped to
the relief device assembly.
Vent Line Materials
All materials in the relief device vent system must be
compatible with the refrigerant in use. Commonly used
and accepted p iping materials include steel and DWV
(drain/ waste/vent) copper. Consult local codes for
restrictions on materials. Consult with the manufacturers
of any field-provided components or materials for
acceptable material compatibility.
No te: PVC piping is acceptable for use as a v ent line
material with R-1233
the sections of plastic pipe may not be. When
considering a v ent system constructed of plastic
piping, such as PVC, ensure that both the pipe
material and the adhesive have been tested for
refrigerant compatibility. In addition, verify that the
local codes permit PVC for refrigerant vent lines;
even though ASHRAE Standard 15 doesn’t prohibit
its use, some local codes do.
The following materials for PVC pipe construction are
recommended for use with R-1233
Primer/Cleaner:
• Hercules—PVC Primer #60-465
• RECTORSEAL
Adhesives:
• Hercules—Clear PVC, Medium Body/Medium Set,
#60-020
• RECTORSEAL—PVC Cement, Gene™ 404L
®
PV C Cleaner—Sam™ CL-3L
(E), but the glue that joins
zd
(E):
zd
Vent Line Sizing
Vent line size must conform to lo cal codes and
requirements. In most cases, local codes are based on
ASHRAE Standard 15. ASHRAE Standard 15 provides
specific requirements for the discharge piping that allows
pressure-relief devices to safely vent refrigerant to the
atmosphere if over pressurization occurs. In part, the
standard mandates that:
•The minimum pipe size of the vent line must equal the
size of the discharge connection on the pressure-relief
device. A larger vent line size may be necessary,
depending on the length of the run.
•T wo or more relief devices can be piped together only if the vent line is sized to handle all devices that could
relieve at the same time.
•When two or more relief devices share a common vent
line, the shared line must equal or exceed the sum of
the outlet areas of all upstream relief devices,
depending on the resulting back pressure.
ASHRAE Standard 15 provides guidance for determining
the maximum vent line length. It also provides the
equation (shown in
properly size the vent line at the outlet of a pressure-relief
device or fusible plug.
The equation accounts for the relationship between pipe
diameter, equivalen t pipe len gth, and the pr essure
difference bet ween the vent line inlet and outlet to help
ensure that the vent line syst em provides sufficient flow
capacity.
Table 8, p. 35 provides additional information based on
ASHRAE Standard 15, including:
•Capacities of various vent line sizes and l engths.
However, this data applies only to conventional
pressure-relief valves and NOT to balanced relief
valves, rupture members (as used on Trane
centrifu gal chill ers), fusible plugs, or pilot-operated
valves.
•A simplified meth od to determine the appropriate
vent-line size, with
with the total C value, read across to a pipe curve and
down to find the maximum allowable length for that
size pipe.
To determine the total C value for a specific unit, add
the appropriate C values for the evaporator, standard
condenser, and economizer. If the unit is equipped with
any options (e.g., heat recovery, free cooling, or an
auxiliary condenser), add the applicable C value(s) for
those options to the total as well.
Note:
Table 8, p. 35 and Figure 23, p. 36 are applicable
only for non-manifolded vent-line runs connected
to a 344.7 kPa (50 psi) rupture disk relief device. The
pipe length provided by the table is in “equivalent
feet.” The vent-line length in equivalent feet is the
Figure 23, p. 36) and data necessary to
®
Figure 23, p. 36. Enter the figure
30 CVHH-SVX001A-EN
Page 31
Vent Piping
sum of the linear pipe length plus the equivalent
length of the fittings (e.g., elbows).
Vent Line Installation
Important: Before constructing the rupture disk vent
line, consult local codes for applicable
guidelines and constraints.
All CenTraVac centri fugal chillers are equipped with
rupture disks. If refrigerant pressure within the evaporator
exceeds 344.7 kPag (50 psig) the rupture disk breaks and
shell pressure is relieved as refrigerant escapes from the
chiller.
A cross-section of the rupture disk assembly appears in
Figure 19, p. 33 along with an illustration indicating the
location of the rupture disk on the suction elbow.
Several general recommendations for rupture disk vent
line installation are outlined below.
No te: If the rupture disk was removed for service or vent
line piping installation, the rupture disk must be
reinstalled (as shown in Figur e 19, p. 33). Refer to
the following procedure and contact CenTraVac
Technical Service when reinstal ling the rupture
disk.
•Ve rify that the rupture disk is positioned as shown in
the cross-section view that appears in
– Install t he two bottom bolt s though the pip e
flanges.
– Install the ruptu re disk with a gasket on each side
between the pipe flanges. Orient the disk with the
reference arrow facing the chiller side as shown in
Figure 19, p. 33.
– Install the two top bolts.
– Center the disk and gaskets to the flange bore.
– Hand tig hten all bolts assuring equal pressure.
– Use a torque wrench set to 196.6 N·m (145 ft·lb) with
a 24-mm socket.
– Tighten bolts in a star pattern, one half turn each, to
maintain even pressure on the disk.
– Final torque on all bolts should be 196.6 N·m
(145 ft·lb).
•When attaching the vent line to the chiller, do not apply
threading torque to the outside pipe of the rupture disk
assembly.
Figure 19, p. 33.
the rupture disk. (Stress can alter rupture pressure and
cause the disk to break premature ly.) The flexible
connector used to isolate the rupture disk from
excessive vent line vibration must be compatible with
the refrigerant in use. Use a flexible , steel co nnector
such as the stainless-steel type MFP, style HNE, flexible
pump connector (from Vibration Mounting and
Control, Inc.) or equivalent. Refer to
a recommended relief pipi ng arrangement.
Figure 20, p. 34 for
WARNING
Pressure-Relief Device Discharge Hazard!
An improper vent-line termination could result in death
or serious injury or equipment damage. When a
pressure-relief device operates, it could discharge a
large amount of fluid and/or vapor. Units MUST be
equipped with a vent-line termination that discharges
outdoors in an area that will not spray refrigerant on
anyone.
NOTICE:
Rupture Disk Damage!
Failure to follow instruction could result in damage to
the rupture disk assembly. Do not apply threading
torque to the outside pipe.
•P rovide support as needed for the vent line. Do not use
the rupt ure d isk assembly to support the vent line
piping.
•Use a flexible connection bet ween the vent-line and
the rupture disk assembly to avoid placing stress on
CVHH-SVX001A-EN31
Page 32
Vent Piping
X39003892001A
NOTICE:
P roper Refrigerant Vent Line Termination!
Failure to properly terminate a refrigerant vent line
could result in equipment damage. Improperly
terminating a refrigerant vent line could allow rain to
enter the line. Accumulated rainwater could cause the
relief device to malfunction; or, in the case of a rupture
disk, the rainwater pressure could cause the disk to
rupture, allowing water to enter the chiller.
NOTICE:
Equipment Damage!
Trane assumes no r es ponsibility for equipment damage
caused by insufficient drainage of the drip leg. All ventlines must be equipped with a drip leg of sufficient
volume to hold the expected accumulation of water
and or refrigerant. The drip leg must be drained
periodically to ensure that it does not overflow and
allow fluid to flow into the horizontal portion of the
vent-line.
•Consult local regulations and codes for any additional
relief line requir ements.
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
•Route t he vent-line piping so that it discharges
outdoors in an area that will not spray refrigerant on
anyone. Position the vent line discharge at least
4.572 meters (15 feet ) above grade level and at least
6.096 meters (20 feet) from any building opening.
P rovide a vent line termination that cannot be blocked
by debris or accumulate rainwater.
•Provide a drip leg on the vent-line (see
). Provide a standard 1/4-in. FL x 1/4-in. NPT,
p. 34
capped refrigerant service valve to facilitate liquid
removal.
32 CVHH-SVX001A-EN
Figure 20,
Page 33
Figure 19. Illustrates rupture disk location, cross section of rupture disk
Rupture disk
Suction connection
Gasket
Outside pipe
assembly
Cap
Bolt
Vent Piping
Note: Pipe connection is 3 in. NPT.
CVHH-SVX001A-EN33
Page 34
Vent Piping
Alternate
Purge discharge
vent line
Outside
wall
Support
this pipe
Flexible
steel
connection
Drip le g
(length as required
for easy access)
1/ 4 in. FL x 1/4 in. NPT
drain valve
Rupture disk
ass embly
Chiller
ChillerChiller
Flow
Flow
Flow
Flow
Flow
Disk in normal
operating position.
Chiller pressure is
below 50 psig.
The disk snaps
open through the
score line o f the
outlet ring and the
pressure is vent ed.
The ou tlet ring is
designed with a
hinge area to retain
the disk petal.
When chiller
pressure exceeds
the disk’s rated
burst pressure, the
disk begins to tear
open al ong the
scor e line of the
outlet ring.
Flow
Flow
Flow
Flow
Flow
Chiller
ChillerChiller
Figure 20. Arrangement for rupture disk relief piping
Trane RuptureGuard
General Information
The Trane RuptureGuard™ refrigerant containment
system replaces the rupture disk on new low pressure
chiller s utilizing R-1233
consists of a solid-metal, (non-fragmenting) reversebuckli ng rupture disk, an d automatically re-seati ng relief
valve. The relief valve and the rupture disk are rated at the
chiller’s maximum working pressure level. If the chiller’s
refrigerant pressure exceeds the rupture disk burst rating,
the disk bursts, releasing pressure to the relief valve. The
relief valve vents the pressure down to a safe level and
then re-seats, thus minimizing the amount of refrigerant
vented to the atmosphere.
operation of a reverse buckling rupture disk.
(E). The RuptureGuard system
zd
Figure 21 illustrates the
Figure 21. Reverse buckling rupture disk
To prevent water, refrigerant and/or other debris such as
rust from hindering the operation of the valve, a drip leg
should be i nstalled immediately after or downstream of
the RuptureGuard (see
Figure 22).
Connection to External Vent Line and Drip
Leg
NOTICE:
Equipment Damage!
Trane assumes no r esponsibility for equipment damage
caused by insuf fic ient drainage of dr i p leg. All vent lines
must be equipped with a drip leg of sufficient volume
to hold the expected accumulation of water and/or
refri gerant. The drip leg must be drained periodically to
assure that it does not overflow and allow fluid to flow
into the horizontal portion of the vent line.
With RuptureGuard installed horizontally, the drain plug
downstream of the valve relief plug and nearest to the
bottom of the valve body should be piped to the drip leg
in the vent line. This will allow the removal of any
condensate formed within the valve body.
Provisions, such as installing a set of fl anges (see
Figure 22) or other disconnect means, must be made in the
discharge vent piping. This will allow the piping
downstream of the valve to be easily removed for an
annual inspection, to replace t he rupture disk, or for any
other servicing need.
34 CVHH-SVX001A-EN
Page 35
Figure 22. External vent line and drip leg (not provided)
Purge
Exhaust
Flange
Drain Valve
Drain Line
Rupture
Disk
Inlet
Flange
Outlet Flange
Connect the discharge of the valve assembly to the vent
line conn ected to the outdoors.
1
No te: Make sure there are no crosses
, elbows, tees
or any other obstructions within the first
22.86 cm (9 in.) of valve discharge. Refer to
ASHRAE Standard 15, national, state, and local
codes for additional requirements on piping
rupture disk and relief valve vent lines.
Vent Piping
T able 8.“C” values us ed to determine rupture disk vent
Notes:
1 . Rupture disk diameter is 76.2 mm ( 3 in.).
2 . Use the total “ C” value in
pipe diam eter.
3 . If piping multiple rupture disks (multiple units) to a common vent
line, first determ ine the total “C” value for each unit, and then; add
all “C” values together and apply the result to
4 . The CVHH unit is a Simplex chiller and has (1) refrigerant circuit and
(1) relief device.
( EVSZ)
Figure 23, p. 36
Oil
Tank
Figure 23, p. 36.
1
A derate on the rated flow capacity for this configuration is published in RuptureGuard engineering bulletin, E/CTV-EB-10.
CVHH-SVX001A-EN35
Page 36
Vent Piping
Pipe Size ( I .D.)
friction factor
150 DN (6 NPS)
154 mm (6.06 in.)
f = 0.0149
100 DN (4 NPS)
102 mm (4.03 in.)
f = 0.0163
80 DN (3 NPS)
78 mm (3.07 in.)
f = 0.0173
125 DN (5 NPS)
128 mm (5.05 in.)
f = 0.0155
Pipe size as a Funct ion of “C” Value a nd Le ng t h of Run
10
1
0
100
100010
L = Pipe Length ( Equivalent Meters)
( Meters x 3 .2 81 = Feet)
“C” Value (kg/s)
ASHRAE Standard 15
L =
7.4381x10
-15d5
(P
2
0
- P
2
2
)-d * ln(P0 / P2)
fC
2
R
500f
Figure 23. Rupture disk vent pipe sizing (SI units); for use with
Table 8, p. 35
Note: This figure, provided as a reference, is based on ASHRAE Standard 15. Vent line size is typically dictated by state or local code which m ay be different
from ASHRAE Standard 15 requirements.
•L = equivalent length of discharge piping, meters
= rated capacity as stamped on the relief device in
•C
r
SCFM (conversion: kg/s = SCFM * 0.0764 / 132.28)
= C value from
C
r
T able 8, p. 35 (convert C in kg/s to lb/
min for IP; lb/min = (kg/s) / 132.28)
•f = Moody friction factor in fully turbulent flow
•d = inside diameter of pipe or tube, mm
•ln = natural log arithm
= absolute pressure at outlet of discharge piping,
•P
2
kPa (atmospheric pressure)
36 CVHH-SVX001A-EN
•P0 = allowed back pressure (absolute) at the outlet of
pressure relief device, kPa
= (0.15 P) + atmospheric pressure
P
0
Page 37
T able 9.“C” values us ed to determine rupture disk vent
Notes:
1 . Rupture disk diameter is 3 in. (76.2 m m).
2 . Use the total “ C” value in
pipe diam eter.
3 . If piping multiple rupture disks (multiple units) to a common vent
line, first determ ine the total “C” value for each unit, and then; add
all “C” values together and apply the result to Figure 24, p. 38.
4 . The CVHH unit is a Simplex chiller and has (1) refrigerant circuit and
(1) relief device.
( EVSZ)
Figur e 24, p. 38
Oil
Tank
Vent Piping
CVHH-SVX001A-EN37
Page 38
Vent Piping
Pipe Size ( I .D.)
friction factor
6 NPS (150 DN)
6.06 in. (154 m m)
f= 0.0149
4 NPS (100 DN)
4.03 in. (102 mm)
f= 0.0163
3 NPS (80 DN)
3.07 in. (78 mm)
f= 0.0173
5 NPS (125 DN)
5.05 in. (128 m m)
f= 0.0155
Pipe size as a Funct ion of “C” Value a nd Le ng t h of Run
1000
100
10
100
100010
L = Pipe Length ( Equivalent Feet)
( Feet x 0.3 05 = Meters)
“C” Value (lb/min)
ASHRAE Standard 15
L =
0.214d5 (P
2
0
- P
2
2
)-d * ln(P0 / P2)
fC
2
R
6f
Figure 24. Rupture disk vent pipe sizing (IP units); for use with
Table 9, p. 37
Note: This figure, provided as a reference, is based on ASHRAE Standard 15. Vent line size is typically dictated by state or local code which m ay be different
from ASHRAE Standard 15 requirements.
•L = equivalent length of discharge piping, feet
= rated capacity as stamped on the relief device in
•C
r
SCFM (conversion: lb/min = SCFM * 0.0764)
= C value in lb/min from
C
r
Table 9, p . 37
•f = Moody friction factor in fully turbulent flow
•d = inside diameter of pipe or tube, in.
•ln = natural log arithm
= absolute pressure at outlet of discharge piping, psi
•P
2
(atmospheric pressure)
38 CVHH-SVX001A-EN
•P0 = allowed back pressure (absolute) at the outlet of
pressure relief device, psi
= (0.15 P) + atmospheric pressure
P
0
Page 39
Insulation
Unit Insulation Requirements
F actory-installed insulation is available as an option for all
units. Factory installation does not include insulation of
the chiller feet; if required, insulation for chiller feet is
provided by others. In applications where the chiller is not
factory-insulated, install insulation over the areas outlined
and highlighted with dashed lines as shown in
p. 40
.
Insul ate all 6.35-mm (1/4-in.) eductor lines, one from the
suction cover and one from the evaporator to prevent
sweat ing .
The quantities of insulation required based on unit size
and insulation thickness are listed in Tab l e 10. Insulation
thickness is determined at normal design conditions which
are:
•standard comfort-cooling leavin g chilled water
temperature
•29.4°C (85°F) dry bulb ambient temperature
•75 percent relative humidity
Operation outside of normal design conditions as defined
above may require additional insulation; contact T rane for
further review.
Note: If the unit is not factory-insulated: install insulation
around the evaporator bulbwells and ensure that
the bulbwells and connections for the waterbox
drains and vents are still accessible after insulation
is applied. The sensor modules (LLIDs) and
interconnecting four wire cable (IPC bus) must be
raised up above the field-installed insulation.
Secure the IPC bus to the insulation top/outer
surface after insulatio n is completed.
Important: Do not insulate the motor housing, unit
wiring, or sensor modules.
Figure 25,
Insulation Thickness
Requirements
Factory applied insulation. All low-temperature
surfaces are covered with 19.05 mm (3/4 in.) Armaflex
or equal (thermal conductivity = 0.036 W/m2-K
[0.25 Btu/h-ft2]), including the evaporator, waterboxes,
suction elbow, economizer, and piping.
The insulation is Armaflex or equivalent closed cell
elastomeric insulati on to prevent the formation of
condensation in environments with a relative humidity up
to 75%. Chillers in high humidity areas or ice storage, low
leaving water temperature (less than 2.2°C [36°F] chilled
water temperature/glycol) units may require double
thickness to prevent formation of condensation.
NOTICE:
Insulation Damage!
To prevent damage to factory installed insulation:
•Do not allow the insulation to be exposed to
excessive sunlight. Store indoors or cover with
canvas to preven t exposure.
•Do not use thinners and solvents or other types of
paint. Use only water base latex.
Failure to follow these instructions could result in
insulation damage.
®
II
Table 10. CVHH evaporator insulation requirements
EVSZ
( Standard Unit)
100M61.4661
100L63.2680
130M63.5684
160M66.1711
200M68.6738
200L71.1765
220M71.5770
220L74.2799
Notes:
1 . Units are NOT insulated on the m otor or refrigerant drain lines.
2 . 19.05- mm (3/ 4- in.) sheet insulation is installed on t he evaporator,
Notes:
1 . Bulbwells, drain and vent connections m ust be accessible after insulating.
2 . Evaporators with pre ssure vessel nameplates must have insulation cut out
around the nam eplate . Do not glue insulation to t he nameplate.
3 . All units with evaporator marine waterboxes wrap waterbox shell insulation
with strapping and secure strapping with seal.
4 . Apply 50.8-mm (2-in.) wide black tape on overlap joints. Where possible
apply 7.6-c m (3-in.) wide strip of 9.7-mm (0.38-in.) thick insulat ion over
butt joint seam s.
5 . Insulate all economizer supports.
40 CVHH-SVX001A-EN
Page 41
Installation: Controls
LINK
++
+
24
VDC
+
MBUS
Front View
6
7
8
9
6
1
10
11
234 5
This section covers information pertaining to the UC800
controller hardware. For information about the Tracer
AdaptiView™ display, which is used to interface with the
internal chiller data and functions provided by the UC800,
refer to Tracer AdaptiView™ Display for Water-Cooled CenT raVac™ C hillers Operations Guide (CTV -SVU01D-E N,
or the most recent version).
UC800 Spec ifications
Power Supply
NOTICE:
Customer Wiring!
Failure to follow instructions below could result in
equipment or property-only damage. Only use flexible
conduit or metal-clad cable when wiring the control
panel and motor terminal box to ensure a vibration-free
installation.
The UC800 (1K1) receives 24 Vac (210 mA) power from the
1T3 power supply located in the chiller control panel.
Wiring and Port Descriptions
Figure 26 illustrates the UC800 controller ports, LEDs,
rotary switches, and wiring terminals. The numbered list
following
in the illustration.
Figure 26 corresponds to the numbered callouts
Figure 26. Wiring locations and connection ports
CVHH-SVX001A-EN41
Page 42
Installation: Controls
Bottom View
10
11
LINK
LINKMBUSIMC
TX
RX
ACT
SERVICE
Marquee LED
Figure 26. Wiring locations and connection ports
1 . Rotary Switches for setting BACnet® MAC address or MODBUS® ID.
2. LINK for BACnet MS/TP, or MODBUS Slave (two terminals, ±). Field
wired if used.
3. LINK for BACnet MS/TP, or MODBUS Slave (two terminals, ±). Field
wired if used.
4. Machine bus for existing machine LLIDs (IPC 3 T racer bus 19.200 baud).
IPC3 Bus: used for Comm4 using TCI or LonTalk
5. Power (210 mA at 24 Vdc) and ground terminations (same bus as
item 4). Factory wired.
6. Not used.
7.Marquee LED power and UC800 Status indicator (
8. Status LEDs for the BAS link, MBus link, and IMC link.
9. USB device type B connection for the service tool (Tracer TU).
10. The Ethernet connection can only be used with the Tracer AdaptiView
display.
11. USB Host (not used).
®
using LCI-C.
Tabl e 11, p . 42).
Communication Interfaces
There are four connections on the UC800 that support the
communication interfaces listed. R efer to
for the locations of each of these ports.
•BACnet MS/TP
•MODBUS Slave
•LonTalk using LCI-C (from the IPC3 bus)
•Comm 4 using TCI (from th e IPC3 bus)
Figure 26, p. 41
Rotary Switches
There are three rotary switches on the front of the UC800
controller. Use these switches to define a three-digit
address when the UC800 is installed in a BACnet or
MODBUS system (e.g., 107, 127, etc.).
Note: V alid addresses are 001 to 127 for BACnet and 001
to 247 f or MODBUS.
LED Description and Operation
There are 10 LEDs on t he front of the UC800.
shows the locations of each LED and
Table 11, p. 42
describes their behavior in specific instances.
42 CVHH-SVX001A-EN
Figure 27
Figure 27.LED locations
Table 11. LED behavior
LEDUC80 0 Status
Pow ered. If the Marquee LED is green solid, the
UC800 is powered and no problem s exist.
Low power or m alfunct ion. If the Marquee LED is
Marquee LED
LINK, MBUS,
IMC
Ethernet Li nk
Servic e
red solid, the UC800 is powered, but there are
problems present.
Alarm. The Marquee LED blinks Red when an alarm
exists.
The TX LED blinks green at the data transfer rate
w hen the UC800 tr ansfers data to other devices on
the link.
The Rx LED blinks yellow at the data transfer rate
when the UC800 receives data from other devices on
the link.
The LI NK LED is solid green if the Ethernet link is
connected and communicating.
The ACT LED blinks yellow at the data transfer rate
w hen data flow is active on the li nk.
The Service LED is solid green when pressed. For
qualified service technicians only. Do not use.
Important: Maintain at least 16 cm (6 in.) between low-
voltage (<30V) and high voltage circuits.
Failure to do so cou ld result in electrical
noise that could distort the signals carried
by the low-voltage wiring, including IPC.
Page 43
Installation: Controls
30 Volt Maximum30–120 Volt Maximum
Figure 28. Control panel: Tracer AdaptiView main unit assembly (showing low voltage and higher voltage areas for
proper routing of field wiring)
CVHH-SVX001A-EN43
Page 44
Installation: Controls
A
B
C
D
E
Installing the Tracer AdaptiView
Display
The Tracer AdaptiView display is boxed, shrink-wrapped,
and located behind the control panel during shipment. The
Tracer AdaptiView display must be installed at t he site.
Important: The Tracer AdaptiView display and display
arm are to be installed by Trane, or an agent
of Trane, for best results.
1 . Unwrap the control panel and display arm. Locate the
box containing the Tracer AdaptiView display behind
the control panel (labeled A).
2. After the box containing the display has been
removed, remove the shipping bra cket from the back
of the control panel (B).
CAUTION
Tension in Display Support Arm!
Failure to ensure that the support arm is in the full
upright position when removing the Tracer AdaptiView
display from the support arm could result in
unexpected movement of the spring-loaded support
arm which could result in personal injury.
Note: Review
Arm,” p. 45
adjustments may be required prior to attaching the
display to the support arm base.
6. Position the Tracer AdaptiView display, with the LCD
screen facing u p, on top of the disp lay support arm
base plate.
Note: Ensure the Trane logo is positioned so that it
“Adjusting the Tracer AdaptiView Display
prior to attaching the display as some
will be at the top when the Tracer AdaptiView
display is attached to the display support arm.
NOTICE:
Do Not Drop Display!
Failure to keep a firm grip on the Tracer AdaptiView
display as you position the display on top of the
support arm base place could result in equipment or
property-only damage.
3. R emove the Tracer AdaptiView display from the box.
Note: Screws are M4 (metric siz e 4), 6 to 8 mm long,
and are shipped with the display.
4. Plug the power cable (C) and the Ethernet cable (D) into
the bottom of the display.
Note: Both cables are already present and extend
from the end of the display arm.
7. Align the four holes in the display with the bolt hole s
in the display support arm base plate.
8. Attach the Tracer AdaptiView d isplay to the display
support arm base plate (E) using the M4 (metric size 4)
screws referenced in
Step 3.
5. Adjust the Tracer AdaptiView display support arm so
the base plate that attaches to the Tracer AdaptiView
display is horizontal.
44 CVHH-SVX001A-EN
Page 45
Adjusting the Tracer AdaptiView
4
3
2
1
Display Arm
The Tracer AdaptiView display arm may become too loose
or too tight and need adjustment. There are three joints on
the display arm that allow the Tracer AdaptiView display to
be positioned at a variety of heights and angles (refer to
items labeled 1, 2, and 3 in
To adjust the tension on the display arm:
•At each joint in the display arm, there is either a hex
bolt (1 and 2) or hex screw (3). Turn the hex bolt or
screw in the proper direction to increase or decrease
tension.
No te: Each hex bolt or screw is labeled with loosen/
tighten or +/- indicators.
Figure 29. Joint locations on the display arm
Figure 29).
Installation: Controls
•Joint 3 has a 6 mm hex screw controlling the tension
on a gas spring, which allows the Tracer AdaptiView
display to tilt up and down.
•Joints 1 and 2 are covered by a plastic cap. Remove the
plastic cap to access the hex bolt. Adjust using a 13 mm
wrench as necessary.
•To adjust the swivel rotation tension of the Tracer
AdaptiView display, adjust the hex bolt located in the
support arm base plate, as described in
“ Installing the Tracer AdaptiView Display,” p. 44. This
adjustment must be done prior to attaching the Tracer
AdaptiView disp lay t o the support arm base. Use a
14 mm wrench to adjust the tension.
•T o adjust the left/right swivel of the entire display arm,
use a 13 m m wrench to adjust the bolt labeled 4 in
Figure 29.
Step 8 in
CVHH-SVX001A-EN45
Page 46
Electrical Requirements
X39003892001A
Installation Requirements
WARNING
P roper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MU ST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards , y ou MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/stat e/ national electrical codes.
As you review t his manual, along with the wiring
instruct ions presented in this sect ion, keep in mind that:
•All field-installed wiring must conform to National
Electric Code (NEC) guidelines, and any applicable
national, state, and local codes. For the USA, be sure to
satisfy proper equipment grounding requirements per
NEC.
•Compressor motor and unit electrical data (includin g
motor kW, voltage utilization range, rated load amps,
and locked rotor amps) is listed on the chiller
nameplate.
•All field-installed wiring must be checked for proper
terminations, and for possible shorts or grounds.
Note: Always re fer to the actual wiring diagrams that
shipped with the chiller or the unit submittal for
specific as-built electrical schematic and
connection information.
NOTICE:
St arter Component Damage!
Failure to remove debris from inside the starter panel
could result in an electrical short and could cause
serious starter component damage.
Do not modify or cut enclosure to provide electrical access.
Removable panels have been pro vid ed, and any
modification should be done away from the enclosure. If
the start er enclosure must be cut to provi de electrical
access, exercise care to prevent debris from falling inside
the enclosure. Refer to installation information shipped
with the starter or submitt al drawings.
Electrical Requirements
Before wiring begins, observe the foll owing electr ical
requirements:
•Follow all lockout-tagout procedures prior to
performing installation and/or service on the unit.
•Always wear appropriate personal prot ective
equipment.
No te: Graphic labels (shown above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
Unit-mounted starters are available as an option on most
units. While this option eliminates most field-installed
wiring requirements, the electrical contractor must still
complete the electrical connection for the following:
•power supply wiring to the starter,
•other unit control options present, and
•any field-supplied control devices.
46 CVHH-SVX001A-EN
•Wait the required time to allow the capacitor(s) to
discharge; this could be up to 30 minutes.
•Verify that all capacitors are discharged prior to service
using a properly rated volt meter.
•Use appropriate capacitor discharge tool when
necessary.
•Comply with the safety practices recommended in
PROD-SVB06*-EN.
Page 47
For AWG/MCM equivalents in mm2, refer to Table 12:
X39003892001A
Table 12. Wire sizing reference
AW G/ MCMm m2 equivalent
220.32
210.35
200. 5
180.75
171. 0
161. 5
142. 5
124
106
810
616
425
2 or 135
1/ 050
2/ 070
2/ 0 or 3/ 09 5
4/ 0 or 250120
300150
350 or 400185
450 or 500240
Note: AWG = American Wire Gauge
Electrical Requirements
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to follow proper handling guidelines could
result in death or serious injury. Always wear
appropriate personal pr otective equipment in
accordance with applicable regulations and/or
standards to guard against potential electrical shock
and flash hazards.
WARNING
Live Electrical Components!
Failure to follow all electrical safety prec autions when
exposed to live electrical components could result in
death or serious injury. During installation, testing,
servic ing and troubles hooting of this product, it may be
necessary to work with live electrical components.
Have a qualified licensed electrician or other individual
who has been properly trained in handling live
electrical components perform these tasks.
Important: Customers are responsible for al l fi eld
wirin g in compliance with local, national,
and/or international codes.
WARNING
Hazardous Volt age w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharg e all motor start/ run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. V er ify with an appropriate voltmeter that all
capacitors have discharged.
For additional inf ormation regarding the safe discharge of
capa citors, see PROD-SVB06*-EN
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
CVHH-SVX001A-EN47
Page 48
Electrical Requirements
Trane-Supplied Remote Starter Wiring
Table 13. Standard field power wiring requirements
Pow er Supply W iring
to Starter Panel
3-Phase Line VoltageL1, L2, L3, and GROUND
Start er t o Motor Pow er W iringStarterMot or
Remote Starte r to Chiller Motor Junction BoxT1 through T6T1 through T6
Pow er Supply W iring to Unit- Mounted
Cont rol Pow er Transform er
( CPTR Optional)
3-Phase Line Voltage
Grou ndCPTR panel GND
( b)
Starter t o Control Panel
12 0 Vac Control W iring
120 Vac Power Supply (from starter to control
panel)
High Pressure Cutout to Starter2X8-41X1-4
1F1 Circuit Breaker to Starter2X 8-31X1-2
Oil Pum p Interlock2X8-7, 2X8-81X1-10, 1X1-21
LV starter Oil/Refrigerant pump start2X8-241X1-21
MV starter Oil/ Refrigerant pump start2X 8-141X1-21
Oil/Refrigerant pump neutral2X8-251X1-16
Starter t o Oil/ Refrigerant Pump
Junction Box
Low Voltage 3-Phase Pum p Power2X8-21, 2X8-22, 2X8-234X4-1, 4X4-2, 4X4-3
Medium Voltage 1-Phase Pump Power2X8-12, 2X8-134X4-1, 4X4-4
Low Voltage Circuits
less than 30 Vac
Standard Circuits
Inter Processor Com munications (IPC)
Remote Mounted
Notes:
1 . All wiring to be in accordance with National Electrical Code and any local codes.
2 . Auxiliary equipm ent m ust be powered from other sources as the chiller control panel power supplies are si zed for the chiller loads only.
(a) Ground lug for a unit-mounted solid state starter or wye-delta starter is sized to accept 14 AWG solid to 8 AWG strand wire. For AWG/ MCM equivalents
in m m2, refer to
(b) Refer to submit tal and ship-with wiring schem atics for voltage requirem ents.
(c) Must be separated from 120 Vac and higher wiring.
(c)
Table 12, p. 47. If local codes require different lug size, it must be field-supplied and -installed.
Starter Panel
Terminals
(a)
Cont rol Pow er
Transformer Term inals
6Q1-1,3,5
Starter Panel
Terminals
2X8-1, 2X 8-2
2X8-G (Ground)
Starter Panel
Terminals
Starter Panel
Terminals
2K32-J3-3-4, or
2X1-12 to 13 if present (do not
gro und shield at starter)
Unit Control Panel
Terminat ions
1X1-1, 1X1-12
1X1-G (Ground)
Oil/ Refrigerant
Pum p Junction Box
Unit Control Panel
Terminat ions
1T2-J53-4
Shield ground at
1X1-G (GND) only.
2 wire with ground
Comm link
48 CVHH-SVX001A-EN
Page 49
Customer-Supplied Remote Starter Wiring
Table 14. Standard customer-supplied remote field wiring requirements
Pow er Supply W iring to Start er Panel
Starter by oth ers 3-Phase power wiring
Terminals
See starter by others
schem atic
Starter t o Motor Pow er W iringStarterMotor
Start er Panel
Remote Starter to Chiller Motor Junction
(a)
Box
T1 through T6T1 through T6
Cont rol Pow er
Pow er Supply W iring to Unit- Mounted
Cont rol Pow er Transform er ( CPTR)
3-Phase Line Voltage
Grou ndCPTR panel GND
( b)
Start er to Control Panel 1 20 Vac
Cont rol Wiring
Power from control panel 1F15X 12-31X1-2
Neutral from control panel5X 12-21X1-13
Ground from control panel5X12-G1X 1-G
Interlock r elay signal5X12-41 K23 J10-1
Start contactor signal5X12-51K23 J8-1
Oil Pum p Interlock5X 12-7, 5X12-81X1-10, 1X1-21
Run contactor signal5X12-101K23 J6-1
Transition com plete5X12-141K23 J12-2
Solid State Starter Fault
( c )
Low Voltage Circuit s less than 30 Vac
Standard Circuits
Current Transfor m ers (see
(Required)
Potential Transformers (Required)
Notes:
1 . All wiring to be in accordance with National Electrical Code and any local codes.
2 . Refer t o ship-with wiring schem atics; some terminals m ay vary based on unit.
(a) For AWG/ MCM equivalents in mm2, refer to
(b) Refer to submit tal and ship-with wiring schem atics for voltage requirem ents.
(c) Solid State Starter Fault input is used with low-and m edium-voltage, custom er-supplied solid state starters only.
(d) Must be separated from 120 Vac and higher wiring.
Notes:
1 . Wire length is for copper conductors only.
2 . The above length is maxim um round trip wire length. The maximum
distance the PT can be located from t he starter m odule is half of the
listed value.
(a) For AWG/MCM equivalents in m m2, refer to
and fuses/ breakers are sized based on National Electric Code NEC
[NFPA 70] and UL 1995.
Prim ary
MetersFeetMetersFeet
Max Wire Length
Secondary
Tab le 1 2 , p. 4 7. Wires, lugs,
50 CVHH-SVX001A-EN
Page 51
Power Supply Wiring
X39003892001A
WARNING
P roper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MU ST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards , y ou MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/stat e/ national electrical codes.
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
NOTICE:
St arter Component Damage!
Failure to remove debris from inside the starter panel
could result in an electrical short and could cause
serious starter component damage.
NOTICE:
U se Copper Conductors Only!
Failure to use copper conductors could result in
equipment damage as unit terminals are not designed
to accept other types of conductors.
•Do not modify or cut enclosure to provide electrical
access. Removable panels have been provided, and
any modification should be done away from the
enclosure. If the starter enclosure must be cut to
provid e electr ical access, ex ercise care to prevent
debris from falling inside the enclosure.
•Use copper conductors to connect the thr ee-phase
power supply to the remote- or unit-mounted starter
panel.
•Flexible con duit connection s are recommended t o
enhance serviceability and minimize vibration
transmission.
•Size the power supply wiring in accordance with NEC
and local guidelines, using the RLA value stamped on
the chiller nameplate and transformer load on L1 and
L2.
•Confirm that wire size is compatible with lug size stated
in unit submittal.
•Make sure that the incoming power wiring is properly
phased; each power supply conduit run to the starter
must carry the correct number of conductors to ensure
equal phase representation.
Note: Connect L1, L2, and L3 (shown below) per
starter diagram provided with chill er.
Three-Phase Power
R eview and follow the guidelines below to properly install
and connect the power supply wiring to the starter panel:
•Ve rif y that the star ter n ameplate ratings are
compatible with the power supply characteristics and
with the electrical data on the unit nameplate.
CVHH-SVX001A-EN51
Page 52
Power Supply Wiring
L3GL2 L1L3GL2 L1
L3 L2 L1 GL3 L2 L1 G L3 L2 L1 G
L2
L3GL2L1L3
G
L2L1
L3L1GL3L2L1GL3L2L1G
Unit-Mounted Starters
Remote-Mounted Starters
•When installing the power supply conduit, ensure that
the position of the conduit does not interfere with the
serviceability of any of the unit components, or with
structural members and equipment. Ensure that the
conduit is long enough to simplify any servicing that
may be necessary in the future (e.g., starter).
•Electrical wire torque specifi cations—follow starter
man ufacturer’s torque specifications.
Circuit Breakers and Fused
Disconnects
Any field supplied circuit break er or fused disconnect
installed in power supplied to the chiller must be sized in
compliance with NEC or local guidelines.
CE for Control Power Transformer (CPTR)
Opt ion
Important: For the CPTR (Control Power Transformer)
option, ch iller mounted/UPS power, the
customer needs to ensure that the supply is
NOT taken from public low vo ltage
supplies, and that a dedicated clean source
of private power supply is used for chiller
mounted CPTR option when a CE chiller is
selected. This also includes when CPTR
option is standard such as in customersupplied starters and remote-mounted
medium voltage AFDs.
All customer wiring, including power wiring to starters/
drives/CPTR Option/UPS shore power, needs to be
separated: 24–27 Vdc, 1 1 0–120 Vac, and 380–600 V ac eac h
need t o be in separate conduit runs.
For 110/120 V customer wiring, including main power
supply to CPTR option, it is required that the customer
provides some sort of surge protection ahead of it, and all
customer wiring needs to be run in flexible metal conduit
and grounded at both ends. Any ethernet cables being
used by customer to interface with the T rane chiller must
be shielded ethernet cabling.
The customer is required to provide an overcurrent device
upstream of the CPTR option in accordance with IEC
standards and/or any applicable local and national codes.
The customer is required to follow all local, national, and/
or IEC codes for installation.
Service personnel must use proper PPE for servicing and
should also use proper lockout/tagout procedures during
servicing. The customer should also disconnect the main
supply disconnecting device upstream of the starter or
drive first before performing any service on any part of the
chiller, including the CPT R option, related controls, and oil
pump motor circuits. In addition, service personnel should
first disconnect the supply disconnecting device upstream
of the CPTR option before performing any service on the
CPTR option or its related circuits. Lock the CPTR option
enclosure panel disconnect handle before servicing to
preven t accidental pulling of the disconnect handle.
CE for Starter or Drive
Important:
•All Trane-supplied remote starters and drives used in
conjunction with CVHH or CDHH T rane chillers will be
CE-complian t per EU directives and IEC standards to
which the CVHH and CDHH chi llers also comply. All
Trane-supplied remote starters and drives must be
used with CVHH or CDHH Trane chillers to ensure CE
compliance.
•For remot e starters and drives: Basic details ar e
provided on remot e starter/drive nameplate. Please
refer to the chiller unit nameplate located on the chiller
mounted control panel for details on wire sizing
(minimum current ampacity) and overcurrent
protection sizing upstream of the unit (maximum
over current protection).
•Always refer to as-built schematic wiring diagrams and
the chiller Installation, Operation, and Maintenance
manual located inside the chiller mounted control
panel (regardless of unit or remote-mounted starter or
drive) for details on wiring, safety, installati on, and
warnings.
•Refer to drive-speci fic Installation, Operation, and
Maintenance manuals for drive and option installation
specifics fo r un it- and remote-mounted adaptive
frequency drives.
52 CVHH-SVX001A-EN
Page 53
•Customers are responsible for all field wiring wi th
X39003892001A
respect to EMC and EMI interference. Customers are
responsible to mitigate the risks associated with EMC
and EMI interference that can occur as a result of
customer-provided field wiring as dictated by
international, national, and local codes. This also
implies that for remote-mounted starters and drives,
customers are responsible for th e enti re field wiring
into the starter/drive as well as between the starter/
drive and the chiller/compressor terminals with
respect to EMC and EMI int erference. It also implies
that customers are responsible for incoming po wer
wiring to both the starter/d rive and CPTR option
enclosure unit-mounted panel with respect to EMC
and EMI interference.
All customer wiring, including power wiring to starters/
drives/CPTR Option/UPS shore power, needs to be
separated: 24–27 Vdc, 1 1 0– 1 20 Vac, and 380–600 Vac each
need to be in separate conduit runs.
F or 1 10/120V customer wiring, including power supply to
CPTR op tion, it is required that the customer provides
some sort of surge protection and all customer wiring
needs to be run in flexible metal conduit and grounded at
both ends.
For remote starters interfaci ng with the Trane chiller, all
wiring needs to be run in flexible metal conduit and
grounded at both ends. Any ethernet cables being used by
customer to interface with the Trane chiller must be
shielded ethernet cabling.
The customer is required to provide an overcurrent
protective device upstream of all starters and drives in
accordance with IEC standards and/or any applicable local
and national codes.
Service personnel must use proper PPE for servicing and
should also use proper lockout/tagout procedures during
servicing: lock the starter disconnect handle before
servicing to prevent accidental pulling of disconnect
handle at the starter panel. In addition, service personnel
should first disco nnect the main supply disconnecting
device upstream of the starter or drive before performing
any service on any part of the chiller.
Power Supply Wiring
WARNING
Lockout/Tagout Before Removing TouchSafe Covers!
Failure to follow instructions regarding touch-safe
cov ers c ould r es ult in death or serious in jury. Touc h-s af e
covers inside panels are there for protection and may
be removed if necessary for service only and only after
disconnection of main power supply. Before removing
any touch-safe co v er, ensure that there is no line power
first. Removal of touch-safe covers would be at the
customer/ service personnel’s own risk. After any
servic e is completed, if the touch-safe covers have been
removed, the touch-safe covers need to be put back in
to ensure safety and protection.
CVHH-SVX001A-EN53
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
For CE units, the convenience outlet in the control panel
requires a suitable adaptor to meet the needs of customers
with different plug requirements.
Page 54
Power Supply Wiring
Control Power Transformer (CPTR) Option
The CPTR option provides a means to isolate the incoming
line voltage required for the chiller control circuits and the
oil/refrigerant pump from the compressor incoming line
voltage. The CPTR option provides a solution for
customers that cannot afford to lose communication with
the chiller or extended restart times due to lost incoming
power.
The CPTR option will be nefit:
•UPS customers
•Customers requiring fast restarts
•Customers who need controls sourced from a clean
dedicated source
•Customers with building automation /communication
systems who want to maintain chiller status reporting
during power loss
•Chillers with remote-mounted medium-voltage AFDs
or customer-supplied starters
NOTICE:
CPTR Option Enclos ure Panel Damage!
Failure to remove debris from inside the CPTR option
enclosure panel could result in an electrical short and
could cause serious component damage.
Service personnel are requir ed to ensure that the
incoming power supply voltage provided by the customer
to the CPTR option enclosure unit-mounted panel is as per
submittal and nameplate.
Power Factor Correction
Capacitors (Optional)
P ower factor correction capacitors (PFC Cs) are designed to
provide power factor correction for the compressor motor.
PF CC s are available as an option for unit-mounted starters
and remote mounted starters.
Notes:
•Verify PFCC voltage rat ing is greater than or equal to
the compressor vol tage r ating stamped on th e unit
nameplate.
•R efer to the wiring diagrams that shipped with the unit
for specific PFCC wiring information.
The stan dard unit-mounted CPTR option shall have an
enclosure with a disconnect and will require customersupplied power.
CVHH and CDHH chillers have a low-voltage CP TR option
and a medium-volta ge CPTR option.
The CPTR op tion involves a sin gle phase 4kVA
transformer(s) and the oil pump motor circuit to be located
together in an enclosure th at is unit-mounted. There is
3-phase line power between 380–600 Vac feeding this
enclosure. Wherever the 4kVA transformer is located, the
oil pump motor circuit will be located along with it.
With the CPTR option, the control power transformer(s)
and oil pump motor circuit are NOT inside of the starter.
For the low-vol tage CPTR option, the single phase 4kVA
transformer feeds the 120 V control power to all of the
controls. The three-phase line power feeds a motor starter
and overload oil pump motor circuit which feeds the
three-phase oil pump motor .
F or the medium-voltage CPTR option, there are two singlephase 4-kVA transformers: one of the 4 kVA transformers
feeds the 120 V control power to all of the controls. The
second transformer feeds a combination motor controller
oil pump motor circuit which then feeds a single-phase oil
pump motor.
Note: Refer to the unit nameplate for maximum
overcurrent protection and minimum current
ampacity values for connecting to the CPTR option
enclosure.
54 CVHH-SVX001A-EN
Page 55
NOTICE:
X39003892001A
Motor
Fuses
Enclosed
3-phase
capacitor
unit
Fuse d
disconnect
or suitable
breaker
Power
circuit
1
2
3
Current
tran sformer
Motor starter
contactor
Mo tor Damage!
Failure to wire PFCCs into the starter correctly could
cause misapplication of these capacitors and r esult in a
loss of m otor overload protection and subsequently
cause motor damage.
Power Supply Wiring
PFCCs must be wired one of two ways as
sho wn as explained in the following (Option 1
and Option 2).
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
CVHH-SVX001A-EN55
Page 56
Power Supply Wiring
X39003892001A
Motor
Fuses
Enclosed
3-phase
capacitor
unit
Fused
disconnect
or suitable
breaker
1
2
3
Current
transformer
Motor starter
contactor
Option 1—PFCCs installed downstream of
starter contactor, upstream of current
transformers.
WARNING
Hazardous Volt age w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharg e all motor start/ run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. V er ify with an appropriate voltmeter that all
capacitors have discharged.
For additional inf ormation regarding the safe discharge of
capa citors, see PROD-SVB06*-EN
the electrical distribution system. A leading power
factor—too much capacitance—may eventually develo p.
This overprotection causes poor voltage regulatio n (i.e.,
voltage is high when the circuit is unloaded, then drops as
loads are ad ded).
Option 2—PFCC wires routed through current
transformers.
Size motor overload protection t o account for capacitorsupplied current. Overloads are typi cally set to measure
the total current drawn by the motor. When PFCCs are
used, they become the source of part of that current. If the
current they provide is not registered by the overload
protectors, potentially damaging amperage can reach the
motor. The simplest way to ensure that the overloads
detect all current supplied to the motor is to position th e
PFCCs upstream of the current transformers as shown in
the preceding figure. If the capacitor connection points are
downstream of the current transformers, route the PFCC
leads through the cu rrent transformers as shown in the
following figure. This ensures that the overloads register
both line and capacitor-supplied current.
No te: Graphic labels (shown above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharg e.
•All electrical enclosures—unit or remote—are IP2X.
Simultaneously disconnect capacitors and load from line
power. If the capacitors are not switched offline when the
load is disconnected, they continue to add capacitance to
56 CVHH-SVX001A-EN
Interconnecting Wiring
T ypical equipment room conduit layouts with and without
unit-mounted starters are shown in
Figure 31.
Important: The interconnecting wiring between the
starter panel, compressor, and control
panel is factory-installed with unit-mounted
starters. However, when a remote-mounted
starter is used, the interconnecting wiring
must be field-installed.
Note: Refer to starter submittal drawing for location of
incoming wiring to the starter.
Figure 30 and
Page 57
Power Supply Wiring
2
3
1
1
2
3
4
6
7
5
Figur e 30. T ypic al equipment room layout for units with
unit-mounted starters
1.Line side power conduits
2. Unit-mounted starter
3. Unit control panel
Figur e 31. T ypic al equipment room layout for units with
remote-mounted starters
Figure 31. Typical equipment room layout for units with
remote-mounted starters
1.Line side power conduits
2. Remote-mounted starter
3. Unit control panel
4. IPC Circuit conduit less than 30V (and CT/PT wiring for starters by
others)
Note: Must enter the low voltage Class 2 portion of the unit control
5. Motor terminal box
6. 115 V Control conduit
7.Lead power wiring
panel (304.8 m [ 1000 feet ] max).
Note: Must enter the higher than 30 Vdc Class 1 port ion of the until
control panel.
Notes:
• Refer to the unit field connection diagram for approxim ate unit
control panel knock out locations.
• To prevent dam age to the unit control panel components, do not
route control conduit into the top of the box.
Starter to Motor Wiring (RemoteMounted Starters Only)
Ground Wire Terminal Lugs
Ground wire lugs are provided in the motor terminal box
and in the starter panel.
CVHH-SVX001A-EN57
Page 58
Power Supply Wiring
X39003892001A
2
1
3
4
5
Terminal Clamps
NOTICE:
Use Copper Conductors Only!
Failure to use copper conductors could result in
equipment damage as unit terminals are not designed
to accept other types of conductors.
Note: Wire size ranges for the starter line and load-
side lugs are listed on the starter submittal
drawings supplied by the starter manufacturer
or Trane. Carefully review t he sub mitted wire
lug sizes for compatibility with the conductor
sizes specified by the electrical engineer or
contractor.
•On 600 V and below, a terminal clamp with a
9.525-mm (3/8-in.) bolt is provid ed on each motor
terminal stud; use the factory-supplied Belleville
washers on the wire lug connections.
Figure 32
illustrates the junction between a motor terminal stud
and terminal lug.
Figure 32. Terminal stud, clamp, and lug assembly
(600 V and below)
No te: Graphic labels (shown above) are u sed for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
T erminal clamps are supplied with the motor terminals to
accommodate either bus bars or standard motor terminal
wire lugs. Terminal clamps provide additional surface area
to minimize the possibility of improp er electrical
connectio ns.
Wire Terminal Lugs
Wire terminal lugs must be field supp lied.
•Use field-provided, crimp-type wire terminal lugs
properly sized for the application.
1 . Belleville washer
2. Terminal lugs
3. Terminal clamp
4. Motor terminal stud
5. Terminal mounting bolt
•Torque for this assembly is 32.5 N·m (24 ft·lb).
•Install but do not connect the power leads between the
starter and compressor motor. (These connections will
be completed under supervision of a qualified Trane
service engineer after the pre-start in spection.)
NOTICE:
Component Damage!
F ailure to ensur e the power supply wiring and output to
motor wiring are connected to the proper terminals.
could cause catastrophic failure of the starter and/or
motor.
Bus Bars
Bus bars and extra nu ts are available as a Trane option.
Install the bus bars between the motor terminals when
using a starter that is:
•a low-voltage AFD
•across-the-line
•primary reactor/resistor
•auto transformer
•customer-supplied
58 CVHH-SVX001A-EN
Page 59
Connect T1 to T6, T2 to T4, and T3 to T5.
X39003892001A
No te: Bus bar s are not needed in medium-voltage or
high-voltage applications since only 3 terminals
are used in the motor and starter.
Starter to Control Panel Wiring
The unit submittal includes the field wiring connection
diagram and the starter-to-control-panel connection
diagram (showing the electrical connections required
between the remot e-mounted starter and the control
panel).
No te: Install separate conduit into the low voltage
(30 v olts) section of the control panel.
When sizing and installing the electrical conductors for
these circuits, follow the guidelines listed. Use 14 AWG for
120V control circuits unless otherwise specified. For AWG/
MCM equivalents in mm
Component Damage!
Remove all debris from inside the starter panel. Failu re
to do so could result in an electrical short and could
cause serious starter component damage.
2
, refer to
NOTICE:
Table 12, p. 47.
Power Supply Wiring
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards , y ou MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/ stat e/national electrical codes.
Important: Maintain at least 16 cm (6 in.) between low-
voltage (<30V) and high voltage circuits.
F a ilure to do so could result in electrical
noise that may distort the signals carried by
the low voltage wiring, including the IPC
wiring.
To wire the starter to the control panel, follow the
gui delines below:
•If the starter enclosure must be cut to provide electrical
access, exercise care to prevent debris from falling
inside the enclosure. Do not cut AFD enclosure.
•Use only shielded, t wisted-pair wiring for the
Interprocessor Communication (IPC) circuit between
the starter and the con trol panel on remote mounted
starters.
No te: Recommended wire is Beldon Type 8760,
18 AWG for runs up t o 304.8 m (1000 f t). For
AWG/MCM equivalents in mm
Table 12, p . 47. The polarity of the IPC wiring is
critical for proper oper atio n.
•Separate low-voltage (less than 30V; refer to
p. 48
) wiring from the 115V wiring by running each in
its own conduit.
•When routing the IPC circuit out of the starter
enclosure, ensure that it is at least 16 cm (6 in.) from all
wires carrying a higher voltage.
CVHH-SVX001A-EN59
2
, refer to
Table 13,
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
•The IPC wiring shield should be grounded on one end
only at control panel end.The other end should be unterminated and taped back on the cable sheath to
prevent any con tact between shield and ground.
•Oil Pump Interlock: All starter s must p rovide an
interlo ck (normally open) contact with the chiller oil
pump connected to the control panel at terminals
1X1-10 and 1X1-21 (14 AWG; for AW G/MCM
equivalen ts in mm
purpose of this interlock is to maintain the oil pump
signal in the event that a starter failure, such as welded
contacts, keeps the chiller motor runnin g af ter the
controller interrupts the run signal.
2
, refer to
Table 12, p. 47.) The
Page 60
Medium Voltage Installation
X39003892001A
1219
633
949
A
889.1
457.2
673.6
B
737
203
670
C
WARNING
Hazardous Voltage!
Failure to disc on nect power before servicing could
result in deat h or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
F ol low proper lockout/ tagout procedures to ensure the
power can not be inadvertently energized.
autotransformer, or solid-state starting. Refer to the unit
nameplate for motor data including RLA, LRA, etc.
In all cases of non-Trane supplied starters, the Trane
Engineering Specification for UC800 Starter By Others
(available through your local Trane office) must be
followed in order to ensure proper function and protection
of the chiller. A disconnecting means and short-circui t
protection must be installed ahead of the starter, unless
they are included as part of the starter.
Note: Trane assumes no responsibility for the design,
documentation, construct ion, compatibility,
inst allation, start-up, or long term support of
starters provided by oth ers.
Motor Terminal Box
A large steel motor terminal bo x is provided to allow for
the field connection of the motor power supply wire to the
motor. There are three sizes available depending on
voltage and motor frame size.
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
All electrical circuits shall be treated as energized until all
lockout-tagout procedures are in place and the circuit has
been tested to verify that it is de-energized. The medium
voltage motor terminal box cover must not be removed if
power is present, or if there is a possibility that power may
be present. Working on energized medium voltage circuits
is not an approved practice for normal HVAC maintenance
or service.
Medium Volt age Motor
The motor is suitable for remote mounted across-the-line
(including circuit breaker starting), primary reactor,
60 CVHH-SVX001A-EN
Page 61
Medium Voltage Installation
X39003892001A
Box W eight ( kg)Volt Range
A256
B117.3
C58.5
Note: Lifting holes are 14.3 mm .
(a) Motor term inal box cover-only weight is 24.9 kg ( 55 lb).
(a)
6000–13.8kV
Fram e 6800, 6800L
2300–13.8kV
Fram e 440E, 5000, 5800, 580 L
380–600 Vac
Fram e 440E, 5000
Note: If the box is removed for installation purposes, the
motor terminals MUST be protected against
impact or stress damage. Field fabricati on of a
cover or guard is req uir ed.
•The motor terminal box is large enough to
accommodate the use of stress cones.
•If conduit is applied, a flexible connection of the
conduit to the box should be made to allow for unit
serviceability and for vibration isolation. The cable
should be supported or protected against abrasion and
wear on any edges or surfaces. Cable or conduit
openings can be cut at any location in the box sides,
top, or bottom for cable entry. Alway s ensur e that
debris does not remain in the box after cutting cable
entry holes.
Motor Supply Wiring
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards , y ou MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/ stat e/national electrical codes.
CVHH-SVX001A-EN61
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
Motor circuit wire sizing by the installer must be made in
accordance with the National Elect ric Code or any other
applicable codes
.
Three terminals are provided on the chiller for the
connection of power to the motor from the starter. Power
leads to motors must be in multiples of three, with equal
phase representation in all conduits or wire trays. To limit
the effects of corona o r ionization with cables carrying
more than 2000V, T rane requires that the power cable have
a metallic shield, unless the cable is speci fically listed or
Page 62
Medium Voltage Installation
approved for non-shielded use. If the cable is shielded, the
shielding must be grounded at one end (grou nding is
typically done at the starter or supply end).
Care must be taken while routing the inco mi ng cables to
ensure that cable loads or tensions are not applied to the
terminal or premature terminal failure could resu lt.
Motor Terminals
Field-provided, ring-type lugs, with no sharp edges or
corners, must be used by a qualified installer to co nnect
the power wiring to the motor terminals. Follow all
instructions provi ded with the fi eld-provided lugs to
ensure proper connections.
Important: The use of stress cones is hig hly
recommended to reduce and control
longitudinal and radial electrical stresses at
the cable ends.
P rior to assembly the terminal stud, nuts, and lug should
be inspected and cleaned to ensure they are not damaged
or contaminated. When attaching starter leads to 2.3–
6.6 kV motor terminals, the M14x2 brass jam nuts should
be tightened to a maximum torque of 32.5–40.7 N·m (24–
30 ft·lb). Always use a second wrench to backup the
assembly and prevent applying excessive torque to the
terminal shaft.
Note: 6.0kV and 6.6kV motors on 6800 or 6800L frames
(see compressor model number for motor frame)
use the same motor terminals as the 10kV–13.8kV
motors.
The motor terminal on a 10–13.8kV motor h as a copper
shaft that is threaded M14 x 2–6 G. Brass nuts are provided
on t he motor terminals to retain the lugs, and the final
connection shou ld be tightened to 32.5–40.7 N·m (24–
30 ft·lb).
chiller with the motor terminal box cover removed or with
any loose or missing cover bolts.
NOTICE:
Motor Terminal Damage!
Applying torque to the motor terminal when tightening
lugs could cause equipment or property-only damage.
Always use a second wrenc h to back-up the assembly
and prevent the application of torque t o the termin al
shaft.
Before beginning wiring and torquing , ensure proper
motor terminal care and do not apply any excess stress.
Ground Wire Terminal Lug
A ground wire lug is provided in the motor terminal box to
allow the field connection of an earth ground. The lug will
accept a field supplied ground wire of #8 to #2 AWG. For
AW G/MCM equivalents i n mm
After completing the field co nnect ion of wiring, i nspect
and clean the motor terminals and motor housing, and
remove any debris before reinstalling the motor terminal
box cover. The cover must be re-installed onto the motor
terminal box and all bolts instal led. Do not operate the
62 CVHH-SVX001A-EN
2
, refer to
Table 12, p. 47.
Page 63
System Control Circuit Wiring (Field Wiring)
Table 18. Unit control panel wiring 120 Vac
Standard Control Circuits: Uni t
Cont rol Panel Co ntrol Wiring
( 12 0 Vac)Unit Control TerminationsI nput or Output TypeContacts
Chilled Water Flow Proving I nput
Con denser Water Flow Proving Input
Chilled Water Pump Relay Output1K15-J2-4 to 6Binary OutputNormally Open
Condenser Water Pump Relay Output1K15-J2-1 to 3Binary OutputNormally Open
(a)
(b)
1X1-5 to 1K16-J3-2Binary InputNormally Open, closure
w ith flow
1X1-6 to 1K16-J2-2Binary InputNormally Open, closure
w ith flow
Optional Control Circuits
Note: Defaults are factory program med, alternates can be selected at start-up using the service tool.
( 12 0 Vac)
Alarm Relay MAR ( Non-Latching) Output1K19-J2-1 to 3Binary Ou tputNormally Open
Limit Warning Relay Output1K19-J2-4 to 6Binary OutputNormall y Open
Alarm Relay MMR ( Latching) Output1K19 -J2- 7 to 9Binary Outpu tNormally Open
Compressor Running Relay Output1K19-J2-10 to 12Binary OutputNormally Open
Maximum Capacity Relay Output1K20-J2-1 to 3Binary OutputNormally Open
Head Relief Request Relay Output1K20-J2-4 to 6Binary OutputNormally Open
Purge Alarm Relay Output1K20-J2-7 to 9Binary OutputNormally Open
Ice Making Relay Output1K15-J2-10 to 12Binary OutputNormally Open
Free Cooling Relay Output1K21-J2-4 to 6Binary OutputNormally Open
Standard Low Voltage Circuits
( less than 30 Vac)
External Auto Stop Input1K2-J2-1 to 2Binary I nputClosure required for
Emergency Stop Input1K2-J2- 3 to 4B inary InputClosure required for
( c)
U nit Control Panel
Terminations
I nput or Out put TypeContacts
normal operation
normal operation
Optional Low Voltage Circuits
External Base Loa ding Enable Input1K8-J2-1 to 2Binary I nputNorm ally Open
External Hot Water Control Enable I nput1K8-J2-3 to 4Binary InputNorm ally Open
Exte rnal Ice Machine Contr ol En able Input1K9-J2-1 to 2Binary InputNormally Open
External Free Cooling I nput Enable I nput1K10-J2-1 to 2Binary I nputNor m ally Open
% RLA Compressor Output1K5-J2-1 to 3Analog Output2–10 Vdc
External Condenser Pressure Output1K5-J2-4 to 6Analog Output2–10 Vdc
Evaporator/ Condenser Diff erential Pressure
Output
Condens er Head Pressure Control1K5-J2-4 to 6Analog Output2–10 Vdc
External Current Lim it Setpoint Input1K6-J2-2 to 3Anal og I nput2–10 Vdc, or 4–20 mA
External Chilled Water Setpoint Input1 K6-J2-5 to 6Analog Input2–10 Vdc, or 4–20 mA
External Base Loa ding Setpoint I nput1K7-J2-2 to 3Analog Input2–10 Vdc, or 4–20 mA
Generic Refrigerant Monitor input1K7-J2-5 to 6Anal og I nput2–10 Vdc, or 4–20 mA
Outdoor Air Temperature sensorIPC bus Connection and sensorComm unication an d sensor
Tracer Com m 4 Interface1K3-J2- 1(+ ) to 2(- )
BACnet or MODBUS1K1, 5(+ ) to 6(-)Commun ication to BA Cnet or
LonTalk Com m 5 interface
Note: All wiring to be in accordance with National Electrical Codes and any local codes
(a) If the Chilled Water Flow Proving I nput is a factory-installed ifm efector flow-sensing device, the secondary field device (recommended with 3.3°C [38°F]
and lower leaving chilled water temperatures) for proof of flow connects from 1X1-5 to 1K26- 4 (binary input; normally open, closure with flow). Remove
factory jum per when used.
(b) If the Condenser Water Flow Proving Input is a factory-installed ifm efector flow-sensing device, the secondary (optional) field device for proof of flow
connects from 1X1-6 to 1K27-4 (binary input; normally open, closure with flow). Remove factory j umper when used.
1K5-J2-4 to 6Analog Output2–10 Vdc
1K3-J2-3(+ ) to 4(-)
1K4-J2-1(+ ) to 2(-)
1K4-J2-3(+ ) to 4(-)
Left Panel
Communication to Tracer(as ordered, see sales
MODBUS
Communication to LonTalk
order)
(as ordered, see sales
order)
(as ordered, see sales
order)
CVHH-SVX001A-EN63
Page 64
System Cont rol Circuit Wiring (Field Wiring)
X39003892001A
(c) Standard low-voltage circuits (less than 30 Vac) must be separat ed from 120 Vac or higher wiring.
Water Pump Interlock Circuits and Flow
Switch Input
WARNING
Hazardous Voltage!
Failure to disc on nect power before servicing could
result in deat h or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
F ol low proper lockout/ tagout procedures to ensure the
power can not be inadvertently energized.
2. Connect circuit to 1K15-J2-6.
3. Use 1K15-J2-4 120 Vac output to allow the control
panel to control the evaporator water pump, or wire
the 5K1 contactor to operate remotely and
independently of the control panel.
Chilled water proof of flow
When this circuit is installed properly and the evaporator
pump is running and providing the required minimum
flow, this circuit will prove the evaporator water flow for
the chiller controls. Proof of evaporator water flow is
required before the start sequence will be allowed to
proceed and a loss of evaporator water flow during chiller
operatio n will result in a chiller shut-d own.
Re fer to as-built schematics on the inside of the control
panel for field wiring. This is a dry binary input; normallyopen, closure for flow. Apply no external power.
1. With factory-installed ifm efector flow-sensing
devices, a field-provided secondary flow-sensing
device is recommended with applications having 3.3° C
(38°F) and below leaving evaporator water
temperatures. When a secondary flow-sensing device
is used, remove the factory jumper and install its
contacts between 1X1-5 t o 1K26-4; this places the
secondary flow sensing device in series with the
ifm efector.
2. For field-provided primary proof o f fl ow devices,
connect the primary proof o f flow device between
terminals 1X1-5 to 1K16-J3-2. A secondary field device
is recommended with applications having 3.3°C (38°F )
and below leaving evaporator water temperatures,
and must be field-wired in series with the primary
proof o f flow device.
No te: Graphic labels (shown above) are u sed for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
Note: The circuits for the chilled water proof of flow and
the condenser water proof of flow do NOT require
external power. Re fer t o the wiring diagrams that
shipped with the chiller.
Chilled water pump
1 . Wire the evaporator water pump contactor (5K42) to a
separate 120 volt single phase power supply with
14 AWG, 600 volt copper wire. For AWG/MCM
equivalents in mm
64 CVHH-SVX001A-EN
2
, refer to
Table 12, p. 47.
Condenser water pump
1 . Wire the condenser water pump contactor (5K43) to a
separate 120-vo lt, single phase power supply with
14 AWG, 600-volt copper wire. For AWG/MCM
equivalen ts in mm
2. Connect circuit to control panel terminals 1K15-J2-3.
3. Use 1K15-J2-1 120 Vac output to allow the control
panel to control the condenser pump.
2
, refer to
Table 12, p. 47.
Condenser water proof of flow
When this circuit is installed properly and the condenser
pump is running and providing the required minimum
condenser water flow, this circuit will prove the condenser
water flow for the chiller controls. Proof of condenser
water flow is also required for the start sequence will be
allowed to proceed and a loss of condenser water flow
during chiller operation will result in a chiller shut-down.
Re fer to as-built schematics on the inside of the control
panel for field wiring. This is a dry binary input; normallyopen, closure for flow. Apply no external power.
Page 65
System Control Circuit Wiring (Field Wiring)
2
4
0
p
1
3
9
7
w
q
5
ty
er
ty
er
8
]a\
See Detail A
See Detail B
De tail A
De tail B
ty
er
=q
[
u
o
f
6
sd
-
i
1. With factory-installed ifm efector flow-sensing
devices, a secondary field-provided flow-sensing
device is optional. When a secondary flow-sensing
device is used, remove the factory jumper, and install
its contacts between 1X1-5 to 1K27-4; this p laces the
secondary flow sensing device in series wi th the
ifm efector.
2. For f ield -provided primary proof of flow devices,
connect the primary proof of flow device between
terminals 1X1-6 to 1K16-J2-2. The secondary field
provided flow sensing device is optional; however,
when it is present, it must be field-wired in series with
the primary pro of of flow device.
Figure 33. CVHH sensor locations
Temperature Sensor Circuits
All temperature sensors are factory installed except the
optional outdoor air temperatu re sensor (refer to
Figure 33, p. 65 for senso r lo cations). Thi s sensor is
required for the outdoor air temperature type of chilled
water reset. Use the following guidelines to locate and
mount the outdoor air t emperature sensor . Mount the
sensor probe where needed, however, mount the sensor
modul e in the control panel.
1 . Tracer AdaptiView display module
2 . Motor winding t emperature 1
3 . Motor winding t emperature 2
4 . Motor winding t emperature 3
5 . Oil pump discharge pressure transducer
6 . Oil t ank pressure transducer
7 . Evaporator water differential pressure transducer
8 . Condenser water differential pr essure transducer
9 . Compressor discharge refrigerant temp erature sensor
1 0.Evaporator saturated refrigerant temperature sensor
1 1.Condenser saturated refrigerant temperature sensor
1 2.Second condenser entering water temperature sensor ( used on HTRC)
1 3.Second condenser leaving wat er temperature sensor (used on HTRC)
1 4.Oil tank temperature sensor
1 5.Evaporator entering water temperature sensor
1 6.Evaporator leaving water temperature sensor
1 7.Condenser entering water temperature sensor
1 8.Condenser leaving water temperature sensor
1 9.Inboard bearing temperature sensor
2 0.Out board bearing temperat ure sensor
2 1.Oil cooling solenoid valve
2 2.Inlet guide vane first stage actuator
2 3.Inlet guide vane second stage actuat or
2 4.Out board bearing pad temperature sensor 1
2 5.Out board bearing pad temperature sensor 2
2 6.Out board bearing pad temperature sensor 3
2 7.Condenser high pressure cut out switch
2 8.Condenser refrigerant pressure transducer
2 9.Oil tank vent line valve
CVHH-SVX001A-EN65
Page 66
System Cont rol Circuit Wiring (Field Wiring)
CWR—Outdoor Option
The outdoor temperature sensor is similar to the unitmounted temperature sensors in that it consists of the
sensor probe and the module. A four-wire IPC bus is
connected to the module for 24 Vdc power and the
communications link. Trane recommends mounting the
sensor module within the control panel and the sensor two
wire leads be extended and routed to the outdoor
temperature sensor probe sensing location. This ensures
the four-wire IPC bus protection and provides access to the
module for configuration at start-up.
The sensor probe lead wire between the sensor probe and
the mod ule can be separated by cutting the t wo-wire
probe lead leaving equal lengths of wire on each d evice:
the sensor probe and the sensor module.
No te: This sens or and module are matched and must
remain t ogether or inaccuracy may occur.
These wires can then be spliced with two 14–18 AWG 600V
wires of sufficient length to reach the desired outdoor
location with a maximum length 304.8 meters (1000 feet).
For AWG/MCM equivalents in mm
. The module four-wire bus must be connected to the
p. 47
control panel four-wire bus using th e Trane-approved
connectors provided.
The sensor will be configured (given its identity and
become functional) at start-up when the Trane service
technician performs the start-up configuration. It will NOT
be operational until that time.
Note: If shielded cable is used to extend the sensor leads,
be sure to cover the shield wire with tape at the
junction box and ground it at the control panel. If
the added length is run in conduit, do not run them
in the same conduit with other circuits carrying 30
or more volts.
Important: Maintain at least 16 cm (6 in.) between low-
voltage (<30V) and high voltage circuits.
F a ilure to do so could result in electrical
noise that may distort the signals carried by
the low-voltage wiring, including the IPC.
2
, refer to
Table 12,
Unit Start-up/Commissioning
Important: Start-up must be performed by T rane or an
agent of Trane specifically authorized t o
perform start-up and warranty of Trane
products. Contractor shall provide Trane (or
an agent of T rane specifically authorized to
perform start-up) with notice of the
scheduled start-up at least two weeks prior
to t he scheduled start-up.
®
Starter Module Configuration
The starter module configuration settings will be checked
(and configured for Remote Starters) during start-up
commissioning.
Note: To configure starter modules, and perform other
starter checks, it is recommended th at the line
voltage t hree-phase power be turned off and
secured (locked out), and then that a separate
source control power (1 15 Vac) be utilized to power
up the control circuits.
Use the as-built starter schematic to ensure correct fuse
and terminals. Verify that the correct fuse is removed and
that the control circuit connections are correct; then apply
the 1 1 5 Vac separate source power to service the controls.
Schematic Wiring Drawings
Please refer to the submittals and drawings that shipped
with the unit. Additional wiring drawings for CenTraVac
chillers are available from your local Trane office.
Opt ional Control and Output Circuits
Install various optional wiring as required by the owner’s
specifications (see
Table 18, p. 63).
Optional Tracer Communication Interface
This control option allows the control panel to exchange
information—such as chiller status and operating set
points—with a Tracer system.
No te: The cir c uit mu st be r un in separate conduit to
prevent electrical noise interference.
Additi onal information about the Tracer Communication
interface option is published in the installation and
operation guide that ships with the Tracer.
66 CVHH-SVX001A-EN
Page 67
Operating Principles
condenser
high side economizer
evaporator
2
3
4
P
1
P
3
P
2
P
4
Pressure
compressor
(3rd stage)
low side economizer
compressor
(2
nd
stage)
com pressor
(1st stage)
5
6
7
8
1
General Requirements
Operation and maintenance information for CVHH chillers
are covered in this section. This includes both 50 and 60 Hz
centrifugal chillers equipped with the Tracer AdaptiView
UC800 control system. This information pertains to all
chiller types unless differences exist, in which case the
sections are listed by chiller type as app licable and
described separately. By carefully reviewing this
informatio n and following the instructions given, the
owner or operator can successfully operate and maintain
a CenTraVac unit. If mechanical problems d o occur,
however, contact a Trane service technician to ensure
proper di agnosis and repair of the unit.
Cooling Cycle
When in the cooling mode, liquid refrigerant is distributed
along the length of the evaporator and sprayed through
small holes in a distributor (i.e., running the entire length
of the shell) to uniformly coat each evaporator tube. Here,
the liquid refrigerant absorbs enough heat from the
system water circulating through the evaporator tubes to
vaporize. The gaseous refrigerant is then d rawn th rough
the eliminators (which remove droplets of liquid
refrigerant from the gas) and the first stage variable inlet
guide vanes, and into the f irst-stage impeller.
Figure 34. Pressure enthalpy curve, 3-st age
Figure 35. Refrigerant flow, 3-stage
CVHH 3-Stage Compressor
Compressed gas from the f irst-stage impeller flows
through the fixed, second-stage inlet vanes and into the
second-stage impeller. Here, the refrigerant gas is again
compressed, and then discharged through the third-stage
variable guide vanes and int o the third-stage impeller.
Once th e gas is compressed a third time, it is discharged
into the condenser. Baf fles within the condenser shell
distribute the compressed refrigerant gas evenly across
the condenser tube bundle. Cooling tower water circulated
throug h the condenser tubes absorbs heat fro m the
refrigerant, causing it to condense. The liquid refrigerant
then passes through an orifice plate and into the
economizer.
The economizer reduces the energy requirements of the
refrigerant cycle by eliminating the need to pass all
gaseous refrigerant through three stages of compression
(see
Figure 35, p. 67). Notice that some of the liqui d
refrigerant flashes to a gas because of the pressure drop
created by the orifice plates, thus further cooling the liquid
refrigerant. This flash gas is then drawn directly from the
first and second stages of the economizer int o the thirdand second-stage impellers of the compressor,
respectively. All remaini ng liquid refrigerant flows
through another orifice plate to the evaporator.
CVHH-SVX001A-EN67
CVHH 2-Stage Compressor
Compressed gas from the first-stage impeller is
discharged through the second -stage v ariable guide
vanes and into the second-stage impeller. Here , the
refrigerant gas is again compressed, and then discharged
into the condenser. Baffles within the condenser shell
distribute the compressed r efri gerant gas evenly across
the condenser tube bundle. Cooling tower water,
circulated through the condenser tubes, absorbs he at
from the refrigerant, causing it to condense. The liquid
refrigerant then flows out of the bottom of the condenser,
passing through an orifice plate and into the economizer.
The economizer reduces the energy requirements of the
refrigerant cycle by eliminating the need to pass all
gaseous refrigerant through both stages of compression
(see
Figure 37). Notice that some of the liquid refrigerant
flashes to a gas because of the pressure drop created by
the orifice plate, thus further cooling the liquid refrigerant.
This flash gas is then drawn directly from the economizer
into the second-stage impellers of the compressor. All
remaining liquid refrigerant flows out of the economizer,
passes through another orifice plate and into the
evaporator.
Page 68
Operating Principles
condense r
economizer
evaporator
2
3
4
P
1
P
2
P
3
Pressure
com pressor
(2nd stage)
com pressor
(1st stage)
1
5
6
Figure 36. Pressure enthalpy curve
Figure 37.Refrigerant flow, 2-stage
Oil and Refrigerant Pump
Compressor Lubrication System
A schematic diagram of the compressor lubrication
system is illustrated in
the oil tank (by a pump and motor located within the tank)
throug h an oil pressure regulating valve d esigned to
maintain a net oil pressure of 137.9 to 165.5 kPad (20 to
24 psid). It is then filtered and sent to the braze plate heat
exchanger oil cooler located above the oil tank and on to
the compressor motor bearings. From the bearings, the oil
drains back to the oil tank.
Figure 38, p. 69. Oil is pumped from
68 CVHH-SVX001A-EN
Page 69
Figure 38. Oil refrigerant pump
Compressor lubrication system
Motor cooling system
Oil reclaim s ystem
2
1
3
4
5
6
7
8
9
10
11
17
18
19
12
13
20
14
16
15
22
21
Operating Principles
1.Motor coolant return to condenser,
53.975 mm (2.125 in.) OD
2. Oil tank vent lin e , 53.975 mm (2.125 in.) OD13. Purge
3. Vent line actuated ball valve14. Compressor
4. Condenser15. Liquid refrigerant motor coolant supply,
5. High pressure condenser gas to drive oil reclaim
eductors, 9.525 mm (0.375 in.) OD
6. Oil return to tank17. Liquid refrigerant to evaporator
10. Liquid refrigerant to pump, 41.275 mm (1.625 in.) OD21. Oil tan k junction box enclo sure
11. Economizer22. Oil pump motor terminal box
nd
CVHH-SVX001A-EN69
eductor),
12. Oil supply to bearings, 22.225 mm (0.875 in.) OD
16. Liquid r efrigerant to economizer
20. Motor coolant filter
28.575 mm (1.125 in.) OD
6.35 mm (0.25 in.) OD
st
eductor),
Page 70
Operating Principles
X39003892001A
WARNING
Hot Surface!
Failure to use caution while wo rking on the oil system
could result in severe burns. Oil system temperat ure
could exceed 65.6°C (150°F).
WARNING
Hazardous Voltage in Oil Tank Junction
Box Enclosure and Oil Pump Motor
Terminal Box!
Failure to disconnect main power and/or auxiliary
control power before opening oil tank junction box
enclosure or any other junction box/terminal box/panel
on the CVHH and CDHH chiller can result in death or
serious injury. Apply lockout/tagout devices and follow
all company procedures for lockout/ tagout. Unit must
be tested to ensure a zero energy state and equipment
must be put in an electrically safe work condition prior
to maintenance. Hazardous voltage up to 600 Vac is
present in the oil tank junction box enclosure and oil
pump motor terminal box.
T o ensure proper lubrication and prevent refrigerant from
condensin g in the oil tank, two 750-watt heaters are in
wells in the oil tank and are used to heat the oil while the
unit is off. With the default settings, the oil heaters are deenergized when the unit starts. The heaters energize as
needed to maintain 53.3°C to 56.1°C (128°F to 133°F) when
the chiller is no t running.
When the chi ller is operating, the temperature of the oil
tank is typically 37.8°C to 60.0°C (100°F to 140°F). The oil
return lines are routed into a separation chamber in the oil
tank. Gas flow exits out the top of the oil tank and is vented
to the evaporator.
A dual eductor system, using high pressure condenser
gas, reclaims oil from the suction cover and the
evaporator. The suction cover eductor is discharged into
the evaporator, and the evaporator eductor is discharged
into the oil tank. The evaporator eductor line has a shut-off
valve mounted on the evaporator. Normally, t he valve
should be 3/4 to one turn open. Open up to two turns if
necessary.
Oil supply to both the thrust bearing and journal bearings
is cooled when the oil tank temperatur e reaches 60.0°C
(140°F ). The supply oil and li quid refrigerant are pumped
to a brazed plate heat exchanger. The unit controller
monitors oil tank temperature and opens a solenoid valve
to allow liquid refrigerant to flow into the heat exchanger.
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharg e.
•All electrical enclosures—unit or remote—are IP2X.
Motor Cooling System
Compressor motors are cooled with liquid refrigerant (see
Figure 38, p. 69). The refrigerant pump is located on the
front of the oil tank (motor inside the oil tank). The
refrigerant p ump inlet is connected to the well at the
bottom of the condenser. The well design ensures
preferential supply of liquid ref rigerant to the refrigerant
pump before refrigerant is supplied to the economizer.
R efrigerant is delivered to the motor via the pump. An inline filter is installed (replace the in-line filter only with
major service). Motor refrigerant drain lines are routed to
the condenser.
Tracer AdaptiView Display
Information is tailored to operators, service technicians,
and owners.
When operating a chiller, there is specific information you
need on a day-to-day basis—setpoints, limits, diagnostic
information, and report s.
Day-to-day operational information is presented at the
display. Logically organized groups of info rmation—
chiller modes of operation, active diagnostics, settings
and reports put information conveniently at your
fingertips. For more information, refer to Tracer
AdaptiView™ Display for Water-Cooled CenTraVac™
Chillers Operations Guide (CTV-SVU01D-EN, or the most
recent version).
70 CVHH-SVX001A-EN
Page 71
Operating Principles
RuptureGuard
The rupture disk monitors the pressure inside the chiller. If
the pressure exceeds the disk’s burst setting, the disk
ruptures allo wing the chi ller pressure to enter the valve
holder compartment upstream of the relief valve. If the
pressure is above the pressure setting of the relief valve,
the valve will open allowing only the amount of refrigerant
to escape to keep the pressure within safe operating limits.
The excess flow valve maintains the downstream side of
the rupture disk at atmospheric pressure to assure proper
operating conditions for the disk. When the disk bursts, the
rapid pressure increase causes the excess flow valve to
seal and the valve holder area becomes pressurized.
A disk rupture will be indicated by a pressure reading on
the gauge and the pressure switch contacts will close. The
pressure switch is an optional accessory and does not wire
to the control panel. The pressure switch can be connected
to a customer-supplied building automation system
(BAS).
EarthWise Purge
Centrifugal chillers that use low-pressure refrigerants,
such as R-1233zd(E), operate with areas of the chiller at less
than atmospheric pressure. Non-condensables in the air,
such as water and nitrogen vapor, may leak into these lowpressure areas and accumulate in the condenser. If these
non-condensables are not removed, the condenser loses
its ability to condense refrigerant efficiently, and the
pressure of the condenser increases. Increased condenser
pressure lowers the chillers efficiency and capacity.
A purge system is requ ired on low-pressure cent rifugal
chiller s. It is a device that is externally mounted on the
chiller. Its purpose is to remove non-condensable
materials that have leaked into the machine.
Note: F or convenience, the term “ air” is often used in this
document, although any other non-cond ensable
materials that may exist in the chiller are also
removed by the purge system.
coil, it condenses into a liquid, leaving a partial vacuum
behind. More refrigerant vapor from the chiller condenser
migrates to the purge tank to fill th e vacuum.
The liquid refrigerant that has condensed in the purge tank
returns to the chiller condenser through the liquid return
line. The return line includes a filter-drier and a moistureindicati ng sight glass.
The condensing unit is air-cooled, and is operable whether
the chiller is running or not. No additional cooling source
is required.
How a Purge System Works
From a functional standpoint, the purge system can be
divided into subsystems of components. This section
identifies and describes the function of these subsystems.
Refrigeration Circuit Subsystem
The purge evaporator of the refrigeration circuit is located
in the purge tank. The purge tank is connected to the chiller
condenser by supply and return lines through which chiller
refrigerant can freely flow.
The purge evaporator coil p resents a cold condensing
surface to the chiller refrigerant entering the purge tank.
When the purge refrigeration system is run ning,
refrigerant from the chiller condenser is attracted to the
cold surface of the purge evaporat or. When the gaseous
refrigerant contacts the surface of the purge evaporator
CVHH-SVX001A-EN71
Page 72
Operating Principles
1. Purge tank
2. Condensing unit (includ es compressor, condenser coil, and fan)
3. Pressure-relief device (fusible plug)
4. Pump-out solenoid valve
5. Automatic expansio n valve
6. Carbon tank
7. Carbon tank temperature sensor
8. Carbon tank heater
9. Exhaust solenoid valve
10. Pump-out compressor
11. Float switch
12. Compressor suction temperature sensor
13. Chiller refrigerant return line
14. Filter -drier canister
1
4
7
10
3
6
5
9
2
11
8
12
13
14
Figure 39. Components of a Trane EarthWise purge system (front view)
72 CVHH-SVX001A-EN
Page 73
Figure 40. Components of a Trane EarthWise purge system (back view)
1
1. Regeneration solenoid valve
2. Pressure-relief valve
3. Exhau st solenoi d valve
4. Pum p-out compressor
5. Carbon tank heater
6. Autom atic expansion valve
7. Pump-out solenoid valve
8. Pressure-relief device (fusible plug)
9. Carbon tank
10. Purge tank
11. Condensing unit
12. Chiller refrigerant supply line
9
5
3
4
7
10
11
6
8
2
1
12
Operating Principles
Purge Tank Subsystem
Any non-condensables that have accumulated from the
refrigerant vapor are left beh ind to collect in the purge
tank. As the quantity of non-condensables increases, the
heat transfer efficiency of the purge evaporator coil is
reduced, causing the purge compressor suction
temperature to decrease.
A float switch, mounted in the bott om of the purge tank,
indicates if there is ex cessive accumulation of liquid
refrigerant in the tank. A liquid level sensor, which resides
CVHH-SVX001A-EN73
in the purge control panel, monitors the status of the float
switch.
If th e normally closed float switch is open fo r more than
20 minutes, the purge controls will turn off the
refrigeration system and generate a non-latching
diagnostic—Purge Liqui d Level Too High Warning. If the
float switch has re-closed after 20 m inu tes, the purge
controls will restart the r efri gerat ion system.
If the float switch remains open for more than 20 minutes,
or if the float switch/liquid level restart cycle has occurred
Page 74
Operating Principles
more than four times in four hours, a latching diagnostic—
Purge Liquid Level Too High Continuously—will be
generated. The purge system will not restart until it is
reset.
If a Purge Liquid Level Too High Continuously diagnostic
occurs, check the purge lines for any type of restriction
(trapped liquid, closed valves, etc.) and ensure that the
filter-drier on the liqu id return line is in good condition.
A UL-required pressure-relief device (fusible plug), which
protects against over-pressuri zation of the purge tank, is
mounted on the purge tank. The plug material will fuse at
98.9°C (21 0° F ), which equates to approximately 910.1 kPag
(132 psig) for refrigerant R-1233
(E).
zd
Pump-out Subsystem
When the purge control subsystem detects the presence
of non-condensables in the purge tank, the pump-out
solenoid and exhaust sole noi d val ves op en, and the
pump-out compressor turns on. The valves and the
compressor cycl e on and off as needed to achieve an
efficient and fast removal of non-condensables.
A High Vacuum Pump option is available for applications
that require purge operation at low condensing
temperatures and pressures. This option provides a twostage pump-out compressor. The High Vacuum Pump
option allows the purge system to operate to saturation
temperatures as low as 1.1°C (34°F). Typical applications
that may requ ire t he High Vacuum Pump o ption include
free-cooling installations, series chiller inst allat ions, ice
systems having brine flowing through idle chillers, chillers
installed outdoors or in uncon ditioned spaces, or any
application that may cause very low condenser water
temperatures.
Carbon Tank and Regeneration Subsystem
The discharge from the pump-out compressor is piped
through the carbon tank. The special carbon in the tank
effectively scrubs and collects refrigerant molecules from
the non-condensable gas b efore the gas passes through
the exhaust solenoid valve to the chiller vent line.
A 175 W resistive heater is mounted inside the carbon tank
and is used to periodically “ regenerate” the carbon bed
and drive any collected refrigerant vapor back into the
chiller. A UL-required pressure-relief valve, rated at
1034.2 kPa (150 psi), is mounted on the line leaving the
carbon tank. The valve protects against overpressurizati on of the carbon tank.
A temperature sensor is installed through the top of the
carbon tank shell so that the contr ols can monitor the
carbon bed temperature. The temperature sensor controls
the regeneration cycle and protect against overheating. If
the limit temperature is reached, the system shuts down
and a Purge Carbon Regen Temperature Limit Exceeded
diagnostic is generated.
Sensors
The following sensors are used to enable control
communication between the Tracer UC800 controller and
the EarthWise purge system. The sensors use low-level
intelligence devices (LLIDs) to communicate with the
Tracer UC800 controller.
Compressor suction temperature sensor. This
sensor is mounted on the purge condensing unit suction
line. The controller uses the val ue of this temperature
sensor to decide whether or not to purge noncondensables from the purge tank. When the temperature
drops to a specified point, the controller activates the
pump-out cycle to remove the accumulated noncondensables from the purge tank. When enough noncondensables have been removed and the purge
compressor suction temperature increases in response,
the controller terminates the pump-out cycle.
Saturated condenser temperature sensor. This
sensor is mounted on the chiller. If the chiller is ru nning,
the controller uses the value of this temperature sensor to
adjust the purge pump-out initiate/terminate setpoints. It
may be used to prohibit pump-out, if system conditions
are too cool.
Saturated evaporator temperature sensor. This
sensor is mounted on the chiller. If the chiller is Off, the
controller uses the value of this temperature sensor to
adjust the purge pump-out initiate/terminate setpoints. It
may be used to prohibit pump-out, if system conditions
are too cool.
Carbon tank tem perature sensor. This sensor is
mounted in the carbon tank of the purge system. It
provides feedback to the carbon regeneration algorithm.
The sensor and the controller function much the same as
a thermostat to control the carbon tank heater.
Liquid level sensor. This sensor resides in the purge
control panel. It monitors the status of the normally closed
float switch, which is mounted in the bottom of the purge
tank. If an adequate amount of liquid fails to drain from the
purge tank, the float swi tch and sensor detect the
condition and prevent further p urge operation .
Condensing unit LLID. This LLID resides in the purge
control panel. It uses a high-capacity relay to control the
operatio n of the purge condensing unit.
Quad rela y LLID. This LLID resides in the purge control
panel. It has four relay outputs that are used to control the
pump-out compre ssor, the carbon tank heater, the
regeneration solenoid valve, and an alarm output.
Dual triac LLID. This LLID resides i n the purge control
panel. It has two triac-type outputs that are used to control
the pump-out solenoid valve and the exhaust sol enoid
valve. The purge system draws its control power from the
power supplies of the chiller control panel.
74 CVHH-SVX001A-EN
Page 75
Start-up and Shut-down
Stopping
Preparing to Shut Down
Shutting Down
Running
Running
Running - Limit
Stopped
Stopped
Run Inhibit
Starting
Auto
Waiting to Start
Starting Compressor
Start
Command
Diagnostic
Reset
Confirmed Start
Stop Command
Diagnostic
Confirmed Shutdown
Power
Up
Fast Restart or Satisfied Setpoint
Stop Command or Diagnostic
This section will provide basic information on chiller
operation for common events. With microelectronic
controls, ladder diagrams cannot show today’s complex
logic, as the control functions are much more involved
than older pneumatic or solid state controls.
Chiller Sequence of Operation
Adaptive control algorithms can also complicate the exact
sequence of operation. This section illustrates common
control sequences.
Software Operation Overview Diagram
Figure 41 is a diagram of the five possible software states.
This diagram can be thought of as a state chart, with the
Figure 41. Software operation overview
arrows, and arrow text, depicting the transitions between
states.
Des c r iptions
•The text in the circles are the internal software
designations for each state.
•The first line of text in the circles are the visible top
level operating modes that can be displayed on Tracer
AdaptiView.
•The shading of each software state circle corresponds
to the shading on the time lines that show the state that
the chiller is in.
CVHH-SVX001A-EN75
Page 76
Start-up and Shut-down
Power
Applied
to
Controls
Last Chiller Mode
Was Auto
Call for Cooling
AutoWaiting to Start
Waiting to Start
Starting
Compressor
UC800 Boot
Time
(30–50 sec)
Enforce Power
Up Start Delay
Timer (0–30 min)
Wait for Highest Motor Winding
Temp to Fall Below 73.9°C (165°F)
Wait for Oil Temp to Rise Above
Sat Evap + -1.1°C (30°F)
and 37.8°C (100°F)
Prelube (60 sec)
Begin Oil Vent Line
Valve low limit
venting
Overdrive IGV Closed
Energize Condenser
Water Pump Relay
Confirm Condenser Water Flow
Within 4 min 15 sec
(6 sec Filter)
Energize Oil Pump Relay
Confirm 82.7 kPad (12 psid)
Oil Pressure
Within 3 min
Check for High Vacuum
Lockout
Initialize Oil Vent Line Valve to Minimum Open Position
Energize Evaporator
Water Pump Relay
Confirm Evaporator Water
Flow Within 4 min 15 sec
(6 sec Filter)
Open Oil Vent Line Valve
Enforce Stop to Start Timer Using Values From
Real Time Clock (5–200 sec, 30 is Default)
There are five generic states that the software can be in:
•Power Up
•Stopped
•Starting
•Running
•Stopping
Descriptions
•The time line indicates the upper level operating mode,
as it would be viewed on Tracer AdaptiView.
•The shading color of th e cylinder indicates the
software state.
•T ext in parentheses indicates sub-mode text as viewed
on Tracer AdaptiView.
•Text above the time line cylinder is used to illustrate
inputs to the Main Processor. This may include User
input to the Tracer AdaptiView Touch screen, Control
inputs from sensors, or Control Inputs from a Generic
BAS.
•Boxes indicate Control actions such as Turning on
R e lays, or moving the Inlet Guide Vanes.
•Smaller cylinders indicate diagnostic checks, text
indicates time based functions, solid double arrows
indicate fixed timer s , and dashed doubl e arrows
indicate variable timers.
Start-up Sequence of Operation—
Wye-Delta
Logic Circuits within the various modules will determine
the starting, running, and stopping operation of the chiller.
When operation of the chiller is required the chiller mode
is set at “Auto. ” Using customer supplied power, the chilled
water pump relay is energized and chilled water flow must
be verified within 4 minutes and 15 seconds, at the same
time the oil vent line valve is opened. The main processors
logic decides to start the chiller based on the differential to
start setpoint. With the differential to start criteria met, the
module then energizes condenser water pump relay with
customer supplied power (see
Based on the R estart Inhibit function and the Differential to
Start setpoint, the oil and refrigerant pump is energized,
and the oil vent line valve is closed t o the minimum
position. The oil pressure must be at least 82.7 kPad
(12 psid) for 60 continuous seconds and condenser water
flow verif ied within 4 minutes and 15 seconds for the
compressor start sequence to be initiated. After the
compressor starts, the oil vent line valve begins to open;
it can take betwe e n 15 and 30 minut es to full y open
depending on the chiller running conditions.
The compressor motor starts in the “ Wye” configuration
and then, after the compressor motor has accelerated and
the maximum phase current has dropped below
85 perc ent of the chiller nameplate RLA for 1.5 seconds,
the st arter transitions to the “ Delta” confi gur ation.
Figure 42, p. 76).
Figure 42. Sequence of operation: power up to starting
76 CVHH-SVX001A-EN
Page 77
Start-up and Shut-down
Starter
Status is
“Running”
Limit Mode
Exit
Limit Mode
Chiller
Is
Running
Starting
Compressor
Chiller Is Running
Chiller Is Running—LimitChiller Is Running
Modulate IGV/AFD
for LWT control
Modulate IGV/AFD
for LWT control
Modulate IGV/AFD
for Limit control
Enforce All Running Mode Diagnostics
Note: If the Oil Tank Temperature rises above the Oil Cooler Control Setpoint whilte the
compressor is running, the Oil Cooler Solenoid Valve shall be energized to cool the unit.
Satisfied Setpoint
Preparing Shutdown
Shutting DownShutting Down
RunningAuto
Close IGV (0–50 sec)
Postlube 3 min
De-Energize Oil Pump
Command IGV Closed
De-Energize
Compressor
Open Oil Vent Line Valve
Confirm No Oil Pressure*
5 min after oil pump is de-energized
Confirm No Compressor Currents
Within 0–30 sec
Hold position of Oil Vent Line Valve
De-Energize Condenser
Water Pump Relay
Enforce All Running Mode Diagnostics
*Note: No oil pressure is less than 20.7 kPad (3 psid)
Now that the compressor motor is running in the “ Delta”
configuration, the inlet guide vanes will modulate,
opening and closing to the chiller load variation by
operation of the stepper vane motor actuator to satisfy
chilled water setpoint. The chiller continues to run in its
appropriate mode of operation: Normal, Sof tload, Limit
Mode, and so on (see
Figure 43). If the oil tank temperature
rises above the oil cooler setpoint while the compressor is
running, the oil cooler solenoid valve shall be energized to
cool the oil.
If the chilled water temperature drops below the chilled
water set point by an amount set as the “ differential to
stop” setpoint, a normal chiller stop sequence is initiated
as follows:
Figure 43. Sequence of operation: running
1. The inlet guide vanes are driven closed (up to
50 seconds).
2. After the inlet guide vanes are closed, the stop relay
and the condenser water pump relays open to turn off.
The oil and refrigerant pump motor will continue to run
for 3 minutes post-lube while the compressor coasts to
a stop. The oil vent line valve will then open. The chilled
water pump will continue to run while the main
processor module monitors leaving chilled wat er
temperature preparing for the next compressor motor
start based on the “ different ial to start” setpoint.
Figure 44, p. 77 illustrates this sequence.
Figure 44. Sequence of operation: satisfied setpoint
CVHH-SVX001A-EN77
Page 78
Start-up and Shut-down
Local Stop
Normal Latching Diagnostic
Normal Non-Latching Diagnostic
Tracer Stop
External Auto-Stop
IGV Closed
Preparing ShutdownShutting Down
Shutting Down
Running
Stopped
Run Inhibit
Stopped
or
Run Inhibit
Evap Pump
Off Delay
and Postlube
Complete
Close IGV (0–50 sec)
Postlube 3 min
Evap Pump Off Delay Time
(0–30 min)
Command IGV Closed
Enforce All Running Mode Diagnostics
De-Energize Condenser
Water Pump Relay
De-Energize
Compressor
Confirm No Compressor Currents
Within 8 sec
Hold position of Oil Vent Line Valve
Open Oil Vent Line Valve
De-Energize Oil Pump
Confirm No Oil Pressure*
5 min after oil pump
is de-energized
De-Energize Evaporator
Water Pump Relay
*Note: No oil pressure is less than 20.7 kPad (3 psid)
If the STOP key is pressed on the operator interface, the
chiller will follow the same stop sequence as above except
the chilled water pump relay will also open and stop the
chilled water pump after the chilled water pump delay
timer has timed out after compressor shut down (see
If th e “ Immediate Stop” is initiated, a panic stop occurs
which follows the same stop sequence as pressing the
STOP key once except the inlet guide vanes are not
sequence closed and the compr essor mot or is
immediately turned off.
Figure 45).
Figure 45. Sequence of operation: normal shut-down to stopped and run inhibit
P ower Up Diagram
Figure 42, p. 76 i llu strates Tracer Adap tiView dur ing a
power up of the main processor. This process takes from
30 to 50 seconds depending on the number of installed
Options. On all power ups, the software model always will
transition through the Stopped software state
indepe ndent of the last mode. If the last mode before
power down was Auto, the transition from Stopped to
Starting occurs, but it is not apparent to the user.
Ice Machine Control
The con trol panel prov ides a service level Enable or
Disable menu entry for the Ice Building feature when the
Ice Building option is installed. Ice Building can be entered
from Front Panel, or i f hardware is specified the co ntr ol
panel will accept ei ther an isolated contact closure 1K9
Terminals J2-1 and J2-2 (Ground)) or a remote
communicated input (BAS) to initiate the ice building
mode where the unit runs fully loaded at all times. Ice
entered again until the unit is switched to the non-ice
building mode and back into the ice building mode. It is not
acceptable to reset t he chilled water setpoint low to
achieve a fully load ed compressor. When entering ice
buildi ng, the compressor will be loaded at its maximum
rate and when leaving ice building the compressor will be
unloaded at its maximum rate. While load ing and
unloading the compressor, all surge detection will be
ignored. While in the ice building mode, current limit
setpoints less than the maximum will be ig nored. Ice
Building can be terminated by one of the following means:
•Front panel disable.
•Openin g the external Ice. Contacts/ Remote
communicated input (BAS).
•Satisfying an evaporator entering fluid temperature
setpoint (default i s -2.8°C [27°F]).
•Surging for 7 minutes at full open IGV.
building will be terminated either by opening the contact
or based on entering evaporator fluid temperature. The
control panel will not permit the Ice Building mode to be
78 CVHH-SVX001A-EN
Page 79
Figure 46. Sequence of operation: ice building: running to ice buildin g
Ice Making Command:
1. Front Panel
2. Tracer
3. External Input
Evap Leaving
Water Temp Rises
Above the Diff To
Stop
Ice Making
Command
Withdrawn
Running
Running
Running
(Ice Building)
Running (Ice to Normal
Transition)
Running
Ice to Normal Transition Timer
(0–10 min)
Head Relief Request Relay
Delay (1–60 min)
Head Relief Request Relay
Delay (1–60 min)
Open IGV at Max Rate/
Max AFD Frequency
Ignore Softloading and
Set CLS=100%
Energize Ice Building
Relay
Close IGV/Min AFD
Frequency
De-Energize Ice Building
Relay
Modulate IGV/AFD
for LWT control
De-Energize Head Relief
Request Relay
Energize Head Relief
Request Relay
Enforce All Limits and Running Mode Diagnostics
Ice Making Command:
1. Front Panel
2. Tracer
3. External Input
Evap Entering
Water Temp Falls
Below the Ice
Termination
Setpoint
Auto
Run Inhibit
(Ice Building
Complete)
Starting
Compressor
Running
(Ice Building)
Preparing to
Shut Down
Shutting
Down
Run
Inhibit
Open IGV at Max Rate/
Max AFD Frequency
Close IGV
(0–50 sec)
Postlube
(3 min)
Heat Relief Request Relay
Delay (1–60 min)
Ignore Evap Pump
Off Delay Time
for Ice Building
Close IGV/Min AFD
Frequency
De-Energize Oil Pump
Open Oil Vent Line Valve
Hold position of Oil Vent Line Valve
De-Energize
Condenser
Water Pump Relay
De-Energize Evaporator
Water Pump Relay
De-Energize
Compressor
Confirm No Compressor Currents
Within 8 sec
Ignore Softloading and
Set CLS=100%
Energize Ice Building
Relay
Begin Oil Vent Line
Valve low limit venting
Enforce All Limits and Running Mode Diagnostics
De-Energize Ice
Building Relay
De-Energize Heat
Relief Request Relay
Energize Head Relief
Request Relay
Start-up and Shut-down
Figure 47.Sequenc e of operation: ice building: s topped to ice to ice building complete
CVHH-SVX001A-EN79
Page 80
Start-up and Shut-down
Free Cooling Cycle
Based on the principle that refrigerant migrates to the
coldest area in the system, the free cooling option adapts
the basic chiller to function as a simple heat exchanger.
However, it does not provide control of the leaving chilled
water temperature.
If condenser water is available at a temperature lower than
the required leaving chilled water temperature, the
operator interface must remain in AUTO and the operator
starts the free cooling cycle by enabling the Free cooling
mode in the Tracer AdaptiView Feature Settings group of
the operator interface, or by means of a BAS request. The
following components must be factory-installed or fieldinstalled to equip the unit for free cooling operation:
•a refrigerant gas line, and electrically-actuated shutoff
valve, between the evaporator and condenser, and
•a valved liqui d return line, and electrically-actuated
shutoff valve, between the condenser sump and the
evaporator.
When the chiller is changed over to the free cooling mode,
the compressor will shut down if running, the shutoff
valves in the liquid and gas lines open; unit control logic
prevents the compressor from energ izing dur ing free
cooling. Since the temperature and pressure of the
refrigerant in the evaporator are higher than in the
condenser (i.e., because of the difference in water
temperature), the refr igerant in the evaporator vaporizes
and travels to the condenser, cooling tower water causes
the refrigerant to condense on the condenser tubes, and
flow (again, by gravity) back to the evaporator.
This compulsory refrigerant cycle is sustained as long as
a temperature differential exists b etween condenser and
evaporator water. The actual cooling capacity provided by
the free cooling cycle is determined by the difference
between these temperatures which, in turn, determines
the rate of refrigerant f low between the evaporator and
condenser shells.
If the system load exceeds the available free cooling
capacity, the operator must manually initiate changeover
to the mechanical cooling mode by disabling the free
cooling mode of operation. The gas and liquid line valves
then close and compressor operati on begins (see
Figure 42, p. 76, beginning at Auto mode). Refrigerant gas
is drawn out of the evaporator by the compressor, where
it is then compressed and discharged to the condenser.
Hot Water Control
Occasionally CTV chillers are selected to provide heating
as a primary mission. With hot water temperature control,
the chiller can be used as a heating source or coo ling
source. This feature provides greater application
flexibilit y. In this case the operator selects a hot water
temperature and the chiller capacity is modulated to
maintain the hot water setpoint. Heating is the primary
mission and cooling is a waste product or is a secondary
mission. This type of operation requires an endless source
80 CVHH-SVX001A-EN
of evaporator load (heat), such as well or lake water. The
chiller has only one condenser.
Note: Hot water temperature control mode does not
convert the chiller to a heat pump. Heat pump
refers to the capability to change fro m a coolingdriven application to a heating-driven application
by changing the refrigerant path on the chiller. This
is impractical for centrifugal chillers as it would be
much easier to switch over the water sid e .
This is NOT heat recovery. Although this feature could be
used to recover heat in so m e for m , a heat r ecov ery unit h as
a second heat exchanger on the condenser side.
The Tracer AdaptiView Main Processor provides t he hot
water temperature control mode as standard. The leaving
condenser water temperature is controlled to a hot water
setpoint between 26.7 and 60.0°C (80°F and 140°F). The
leaving evaporator water temperature is left to drift to
satisfy the heating load of the condenser. In this
applicati on the evaporator is normally piped into a lake,
well, or other source of constant temperature water for the
purpose of extracting heat . In hot water temperature
control mode all the limit modes and diagnostics operate
as in normal cooling with one exception; the leaving
condenser water temperature sensor i s an MMR
diagnostic when in hot water temperature control mode.
(It is an informational warning in the normal cooling
mo de.)
In the hot water temperature control mode the differentialto-start and differential-to-stop setpoints are used with
respect to the hot water setpoint instead of with the chilled
water setp oint. The control panel provides a separate
entry at the Tracer AdaptiView to set the hot water
setpoint. Tracer AdaptiView is also able to set the hot water
setpoint. In the hot water mode the external chilled water
setpoint is the external hot water setpoint; that is, a single
analog input is shared at the 1K6-J2-5 to 6 (ground).
An external bi nary input to select external hot water
control mode is on the EXOP OPTIONA L module 1K8
terminals J2-3 to J2-4 (ground). Tracer AdaptiView also
has a binary input to select chilled water control or hot
water temperature control. There is no additional leaving
hot water temper ature cutout; the HPC and condenser
limit provide for high temperature and pressure
protection.
In hot water temperature control the softloading pulldown
rate limit operates as a softloading pullup rate limit. The
setpoint for setting the temperature rate limit is the same
setpoint for normal cooling as it is for hot water
temperature control. The hot water temperature co ntrol
feature is not designed to run with HGBP, AFD, free
cooling, or ice building.
The factory set PID tuning values for the leaving water
temperature control are the same settings for both normal
cooling and hot water temperature control.
Page 81
Control Panel Devices and Unit-
X39003892001A
Mounted Devices
Unit Control Panel
Safety and operating controls are housed in the unit
control panel, the star ter panel, and the purge control
panel. The control panel operator interface and main
processor is called Tracer AdaptiView and is located on an
adjustable arm connected to the base of the control panel.
F or more information about operating Tracer AdaptiView,
refer to Tracer AdaptiView™ Display for Water-Cooled CenT raVac™ C hillers Operations Guide (CTV -SVU01D-E N,
or the most recent version).
The control panel houses several other controls modules
called panel mounted LLID (Low Level Intelligent Device),
power supply, terminal block, fuse, circuit breakers, and
transformer. The IPC (Interprocessor communication) bus
allows the communications between LLIDs and the main
processor. Unit mounted devices are called frame
mounted LLIDs and can be temperature sen sors or
pressure transducers. These and other functional switches
provide anal og and binary inputs to the control system.
Start-up and Shut-down
WARNING
Toxic Hazards!
Do not allow the chiller to increase above 54.4°C (130°F )
in temperature while unit is off. Failure to prevent high
c hi ller temperature will cause the inside pressure to
rise:
•Do not run evaporator water pump longer than
30 minutes after the chiller is shut down.
•Ensure that the evaporator is isolated from the hot
water loop before changeover to heating mode.
The rupture disk is designed to relieve and discharge
the refrigerant from the unit if the pressure in the
evaporator exceeds 344.7 kPag (50 psig). A significant
release of refrige rant into a confined space due to a
rupture disk failure could displace available oxygen to
breathe and cause possible asphyxiation. Should a
rupture disk fail, evacuate the area immediately and
contact the appropriate rescue or response authority.
Failure to follow instructions could result in death or
serious injury.
User-Defined Language Support
T racer AdaptiView is capable of displaying English text or
any of twenty-four other languages. Switching languages
is simply accomplished from a language settings menu.
Unit Start-up and Shut-down
Procedures
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when
exposed to live electrical components could result in
death or serious injury. During installation, testing,
servic ing and troubleshooting of this produc t, it may be
necessary to work with live electrical components.
Have a qualified licensed electrician or other individual
who has been properly trained in handling live
electrical components perform these tasks .
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
CVHH-SVX001A-EN81
Page 82
Start-up and Shut-down
Daily Unit Start-up
1. Verify the chilled water pump and condenser water
pump starter are in ON or AUTO.
2. Verify the cooling tower is in ON or AUTO.
3. Check the oil tank oil level; the level must be visible in
or above the lower sight glass. Also, check the oil tank
temperature; normal oil tank temperature before startup is 53.3°C to 56.1°C (128°F to 133°F).
4. Check the chilled water setpoint and read just it, if
necessary, in the Chiller Settings menu.
5. If necessary, readjust the current limit setpoint in the
Chiller Setpoints menu.
6. Press AUTO.
The control panel also checks compressor motor winding
temperature, and a start is initiated after a minimum
restart inhibit time if the winding temperature is less than
129.4°C (265°F ). The chilled wa ter pump relay is energiz ed
and evaporator water fl ow is proven. Next, the control
panel checks the leaving evaporator wat er temperature
and compares it to the chilled water setpoint. If the
difference between these values is less than the start
differenti al setpoint, cooling is not needed.
If the control panel determines that the difference between
the evaporator leaving water temperature and chilled
water setpoin t exceeds the start differential setpoint, the
unit enters the initiate Start Mode and the refrigerant
pump and the condenser water pump are started. If flow is
not initially established within 4 minutes 15 seconds of the
condenser pump relay energization, an automatically
resetting diagnostic “ Condenser Water Flow Overd ue”
shall be generated which terminates the prestart mode
and de-energi zes the condenser water pump relay. This
diagnostic is automatically reset if flow is established at
any later time.
No te: This diagnostic does not automatically reset if
Tracer AdaptiView is in control of the condenser
pump through its condenser pump relay, since it is
commanded off at the time of the diagnostic. It may
reset and all ow normal chiller operation if the
pump was controlled from some external so urce.
If the compressor motor starts and accelerates
successfully, Running appears on the display. If the purge
is set to AUTO, the purge will start running and will run as
lon g as the chiller is running.
No te: If a manual reset diagnostic condition is detected
during start-up, unit operation will be locked out,
and a manual reset is required before the start-up
sequence can begin again. If the fault condition has
not cleared, the control panel will not permit
restart.
When the cooling requirement is satisfied, the cont rol
panel originates a Shuttin g do wn signal. The inlet g uide
vanes are driven closed for 50 seconds, the compressor
stops, and the unit enters a 3-minute post-lube period. The
82 CVHH-SVX001A-EN
evaporator pump may continue to run for the amount of
time set using Tracer AdaptiView.
Once the post-lube cycle is done, the unit returns to auto
mode.
Seas onal Unit Start-up
1. Close all drain valves, and reinstall the drain plugs in
the evaporator and condenser header s.
2. Service the auxiliary equipment according to the startup and mainten ance instructions provided by the
respective equipment manufacturers.
3. Fill and vent the cooling tower, if used, as well as the
condenser and piping. At this point, all air must be
removed from the system (including each pass). Then
close the vents in the condenser waterboxes.
4. Open all of the valves in the evaporator chilled water
circuit.
5. If the evaporator was previously drained, fill and vent
the evaporator and chilled water circuit. When all air is
removed from the system (including each pass), close
the vent valves in the evaporator waterb oxes.
6. Lubricate the external vane control linkage as needed.
7. Check the adjustment and operation of each safety and
operating control.
8. Close all disconnect switches.
9. Perform in structions listed in
.
p. 82
“ Daily Unit Start-up,”
Daily Unit Shut-down
Note: Also refer to
1. Press STOP.
2. After compressor and water pumps shut-down, the
operator may turn Pump Contactors to OFF or open
pump disconnects.
Seasonal Unit Shut-down
Important: Control power disconnect switch must
1 . Open all disconnect switches except the control power
disconnect switch.
2. Drain the condenser piping and cooling tower, if used.
Rinse with clean water.
3. Remove the drain and vent plugs from the condenser
headers to drain the condenser. Ai r dry bundle of
residual water.
4. Once the unit is secured f or the season, the
maintenance procedures described
T able 21, p. 93 should be performed by qualified Trane
service technicians.
Note: During extended shut-down periods, be sure to
operate the purge unit for a two-hour period every
Figure 45, p. 78.
remain closed to allow oil sump heater
operation. Failure to do this will allow
refrigerant to con dense in the oil pump.
T able 20, p. 92 and
Page 83
Start-up and Shut-down
two weeks. This will prevent the accumulation of
air and noncondensables in the machine. To start
the purge, change the purge mode to ON in the unit
control “ Settings Purge” menu. Remember to turn
the purge mode to “Adaptive” after the two-hour
run time.
EarthWise Purge Sequence of
Operations
A Tracer UC800 controller that is configured to control a
purge system uses the operational sequences described in
this section.
Purge Operating Modes
Purge oper ating mode options are as follows:
Stop. The purge condensing unit does not run in this
mode.
On. The purge condensing unit runs continuously in this
mode, regardless of the chillers operational status.
Auto. The purge condensing unit runs in this mode, if the
main compressor of the chiller is operating.
Adaptive. The purge condensing unit operation depends
on past purge activity.
Adaptive Mode Process—Chiller C o mpressor
On
Figure 48, p. 84, illustrates the process described in this
subsection.
When the chiller compressor starts, the purge refrigeration
circuit starts. The purge refrigeration circuit continues to
run until 60 consecutive minutes of running occur without
any pump-out of non-condensables. The Pumpout Time is
the greater of the following two values that the controller
has been tracking:
•The pump-out time wit h the chiller On, over the last
24 hours
•The average daily pump-out time with the chiller On,
over the last 7 days
Adaptive Mode
The objectives of operating the unit in the adaptive mode
are to:
•Enable purge system operation
•Enable the refrigeration circui t to eff ectively
accumulate non-condensables whether or not the
chiller is running
•P rovide information to an operator regarding whether
leakage is on the high-pressure or low-pressure side of
the chiller
•Decrease energy usage by running the purge
refrigeration circuit only when needed to remove noncondensables, rather than running it continu ously
The adaptive mode requires historical operating data so
that the controller can make optimal decisions regarding
how to run the purge refrigeration circuit in the future. On
initial start-up of a chiller that is in adap tive mode, the
purge refrigeration circuit runs continuously for 168 hours
(7 days). The chiller compressor may or may not be
running during this p e riod.
Following the initial data collection period, the adaptive
mode customizes the purge refrigeration circuit operation
during two distinct chiller operating conditions:
•Chiller compressor On
•Chiller compressor Off
CVHH-SVX001A-EN83
Page 84
Start-up and Shut-down
First chiller power-up.
Purge operates
continuously f or 168
hours to collect data.
Chiller On or Off.
Chiller and purge
start.
Purge runs.
Has purge
run 60
minutes
without any
pump-out?
The purge control reviews
the historical data and
determ ine the Pumpout
Time with the c hiller On
(Pumpout Time from last
24 hours daily average over
last 7 days, whichever is
greater.
Yes
No
T urn purge unit Off for
1 hour, then restart.
T urn purge unit Off for
2 hours, then restart.
T urn purge unit Off for
3 hours, then restart.
T urn purge unit Off for
4 hours, then restart.
Is Pumpout
Time greater
than 8
minutes?
Is Pump out
Time greater
than 5
minutes?
Is Pumpout
Time greater
than
3 minutes?
Is Pum pout
Time greater
than
1 minute?
Yes
Yes
Yes
Yes
No
No
No
No
Figure 48. Adaptive chiller ON flow chart
The purge then shuts down for a corresponding period of
time, as shown in the following table:
Pum pout Time w ith chiller On
( over the last 24 hours or daily average
over the last 7 days, w hichever is greater)
Pumpout Time ≤ 1 minute4 hours
1 minute < Pumpout Time ≤ 3 minutes3 hours
3 minutes < Pum pout Time ≤ 5 minutes2 hours
5 minute < Pumpout Time ≤ 8 minutes1 hour
Pumpout Time > 8 minutesNo Off cycle
Purge Off cycle
duration
During the purge refrigeration circuit Off cycle, the time
remaining is displayed as Time Until Next Purge Run in the
Log Sheet that you can view from the Tracer AdaptiView
display (refer to
If th e compresso r is turned Of f during the purge
refrigeration circuit Off cycle, the purge transfers to
Adaptive Mode Procedure—Chiller Compressor Off.
Figure 49, p. 86 illustrates this process.
“ Log Sheet,” p. 21).
84 CVHH-SVX001A-EN
Page 85
Start-up and Shut-down
Adaptive Mode Procedure—Chiller
Compressor Off
Refer t o Figure 49, p. 86 for an illustration of the process
described in this subsection.
If the chiller compressor is turned Off, the purge
refrigeration circuit Off cycle is determined by the purge
control. The purge Off-cycle duration is determined by the
pump-out time, which is the greater of the following two
values:
•Daily P umpout—24 Hours (the pump-out time over the
last 24 hours whether the chiller is On or Off)
•Average Daily Pumpout—7 Days (the pump-out time
with the chiller On over the last 7 days)
Note: These two v alues can be seen o n the Tracer
AdaptiView display.
The purge will be shut down for a corresponding period of
time, as shown in the following table:
The pump- out tim e w ith chiller On or Off
( over the last 24 hrs or daily average over
the last 7 days, w hichever is greater)
Pump-out time ≤ 1 minute3 days
1 minute < pump-out tim e ≤ 3 minutes2 days
3 minutes < pump-out time ≤ 5 minutes1 day
Pump-out time > 5 min ute s6 hours
Purge Off cycle
duration
Daily Pumpout Limit Disabled. appears if the purge
refrigeration circuit is On but the daily pump-out limit has
been disabled.
Regenerating. appears if the purge carbon system is in
its regener ation mode. Pump-out is not allowed in thi s
submode.
Alarm–Check Diagnostics. appears if a new diagnostic
occurs.
Purge Diag Shutdown. appears if the purge system
has shut down in response to a latching diagnostic.
Regen Disabled. appears if carbon regeneration is not
allowed.
During the purge refrigeration cir cuit Off cycle, t he time
remaining is displayed as the Time Until Next Purge Run
in the purge report of the T racer AdaptiView display.
If the controls determine it is necessary to run the purge
while the chiller compresso r is Off, the purge will be
started and run until 60 consecutive minutes have passed
without any pump-out of non-condensables.
If the chiller compressor starts before the purge Off cycle
has elapsed, the purge starts and transfers to Adaptive
Mode Procedure—Chiller Compressor On.
, illustr ates this process.
p. 84
Figure 48,
Submodes
You can view up to six purge submodes from the Purge
Settings screen. The available purge submodes are:
Refrigeration Circuit On. appears if the p urg e
condensing unit/compressor is operating.
Refrigeration Circuit Idle. appears if the purge
condensing unit/ compressor is no t operating.
Pumping Out. appears if the purge refrigeration circuit
is On and pump-ou t has been initiated by the purge unit
controls.
Exhaust Circuit Check. appears if a pump-out has been
initiated by an operator.
Pumpout Inhibited. app ears if the purge refrigeration
circuit is On but pump-out has been inhibited by a lo w
condenser saturation temperature.
CVHH-SVX001A-EN85
Page 86
Start-up and Shut-down
First chiller p ower-up.
Purge operates
continuously for 168
h ours to collect data.
Chiller On or Off.
Chiller O ff.Purge Off.
The purge control reviews the historical
pump-out data f or “chiller On” and
“chiller Off” and determines the Pumpout
Time (from the last 24 hrs, or the daily
average over the last 7 days, whichever
is greate r).
Turn purge Off.
Hold purge Off for
6 hours.
Hold purge Off for
1 day.
Hold purge Off for
2 days.
Hold purge Off for
3 days.
Is Pumpout
Time less than
5 minutes?
Is Pumpout
Time less than
3 minutes?
Is Pumpout
Time less than
1 minute?
Is purge run
60 minutes
without
purging?
Run purge.
Yes
Yes
Yes
Yes
No
No
No
No
Figure 49. Adaptive chiller OFF flow chart
The purge condensing-un it compressor suction
temperature varies with the amount of non-condensables
collected in the purge tank. If the amount of noncondensables collected in the purge tank limits the
available condensing surface in the tank, the condensingunit compressor suction temperature begins to fall.
The purge controller initiates a pump-out cycle when the
suction temperature reaches the pump-out initiate value
that is calculated within t he pu rge control. During the
pump-out cycle, the small pump-out compressor pulls any
non-condensables from the purge tank and discharges
them through the carbon tank. As the non-condensables
are removed from the purge tank, the condensing-unit
compressor suction temperature increases. The purge
controller monitors the compressor suction temperature
and cycles or stops the pump-out, depending on the
temperature that is present.
The 1/4 hp air-cooled condensing unit of the refrigeration
system operates effectively when it is in the operating
range shown in
Figure 50.
86 CVHH-SVX001A-EN
Page 87
Figure 50. EarthWise purge operating limits
Typical o peratio n
Operating envelope extrem es
Ambient tempe rature (ºF)
Chiller c ondenser saturation tem perature (º F)
020406080100120140150
120
100
80
60
40
20
0
Pump-out can be
inhibited in this
range according to
control settings.
Start-up and Shut-down
Air Remova l
If no air is in the purge tank, the refrigerant returning to the
purge condensing unit compressor suction has a high
superheat (heat added past the point of evaporation ),
because of the heat removed from the condensing chiller
refrigerant vapor in the purge tank. As air accumulates in
the purge tank, it displaces the chiller refrigerant vapor and
decreases the amount of coil surface that is exposed to the
vapor. Less heat is removed from the vapor, and the
available superheat at the purge condensing unit
compressor suction consequen tly falls. When the purge
refrigerant compressor suction temperature falls far
enough to reach the pump-out initiate value, the purge
control activat es the solenoids and the pump-out
compressor to remove the accumulated air.
As air is removed from the purge tank, the inside coil is
once again exposed to chiller refrigerant vapor. As more
chiller refrigerant vapor condenses on the coil, more heat
is removed from the vapor, and the purge refrigerant
compressor suction temperature rises. The purge control
cycles or stops the pump-out process in response to the
compressor suction temperature.
P ump-out Operating Sequence
As the purge control system detects the presence of noncondensables in the purge tank, it init iates a pump-out
cycle. The pump-out solenoid valve, the exhaust solenoid
valve, and the pump-out compressor cycle On and Off as
needed to remove the non-co ndensables.
Non-Condensable Pump-out Algorithm
The control ler uses the non-condensable pump-out
algorithm to determine when to initiate, contro l, and
CVHH-SVX001A-EN87
terminate a pump-out cycle to remove air from the purge
tank. The purge refri gerant compressor suction
temperature sensor serves as the feedback to this control
algorithm. The compressor suction temperature pumpout initiate and pump-out terminate values are calculated
by the purge control and are a function of the purge liquid
temperature.
The refrigerant used in the purge refrigeration circuit,
R-404A, is metered into the purge tank coil by a constantpressure regulating expansion valve. The valve
automatically controls the purge suction pressure at a
constant value of 351.6 kPaa (51 psia). Therefore,
refrigerant is metered into the coil as a two-phase
refrigerant mixture at a constant saturation temperature of
approximately -18.9°C (-2°F).
The cold coil creates a low vapor pressure near its outside
surface, which draws refrigerant from the chiller
condenser into the purge tank and to the coil surface.
When the refrigerant gets close enough to the coil surface,
it condenses into a liquid. Since liquid refrigerant requires
less volume than it does in a gaseous form, additional
refrigerant enters the purge tank to fill the void and, in turn,
condenses. This mechanism is known as a thermal siphon.
As the chiller refrigerant condenses, heat is transferred
into the purge coil through the latent heat of condensation.
The compressor suction temperature sensor monitors this
heat transfer.
Air and other gases carried with the chiller refrigerant
vapor do n ot condense on the coil. Instead, they
accumulate in the purge tank, effectively acting to insulate
and inhibit the flow of refrigerant to the cold coil surface.
The thermal siphon rate is reduced and, consequently, so
is the amount of heat transfer. A corresponding reduction
Page 88
Start-up and Shut-down
occurs in the temperature of the purge refrigerant exiting
the coil. The compressor suction temperature sensor
monitors this temperature.
When sufficient non-condensables have accumulated in
the purge tank to decrease the compressor sucti on
temperature below the pump-out in itiate value, a pumpout cycle begins. The cycle is terminated when the
compressor suction temperature sensor increases above
the pump-out terminate value. The cal culation s for the
pump-out values are:
Pump-out initiate:
• (°C) = Purg e liquid temperature (°C) – 10.0°C or -
17.8°C (whichever is higher)
• (°F) = Purge liqu id temperature (°F) – 50°F or 0°F
• (°F) = Purge liqu id temperature (°F) – 40°F or 5°F
(whichever is higher)
The purge liquid temperature value comes from the
chiller’s saturated condenser temperature sensor when
the chiller is running, or the chiller’s saturated evaporator
temperature sensor when the chiller is off.
Non-condensable Pump-out cycle
A non-condensable pump-ou t cycle may be initiated as
described below only if the following two conditions are
met:
•A carbon regeneration cycle is NOT in process, and
•The refrigerati on circuit is on.
If at any time, except as described above, the purge
refrigerant compressor suction temperature drops below
the pump-out initiate value, the fol lowing sequence is
initiated by the controls.
The controller starts the pump-out compressor and opens
the exhaust solenoid valve. After 5 seconds, the pump-out
solenoid valve opens and pulses at a rate of 20 seconds On
and 20 seconds Off. If, after two cycles, the purge
refrigerant compressor suction temperature has not
exceeded the pump-out terminate value, the pump-out
solenoid valve stays continu ously open. If the pump-out
compressor runs for more than 10 consecutive minutes,
the controller recalculates the pump-out initiate and
pump-out terminate values as described.
The purge controls continue to operate the pump-out
solenoid valve and calculate values as described above
until the purge refrigerant compressor suction
temperature rises above the pump-out terminate value. At
this point, the controller will close the pump-out solenoid
valve and turn off the pump-out compressor and exhaust
solenoid valve.
No te: For purge systems equipped with standard pump-
out compressors, operation at lo w chiller
condenser saturation temperatures may result in a
system vacuum greater than the pump-ou t
compressor can overcome. If the chiller
experiences low condensing temperatures, then
the Tracer UC800 controller can be programmed to
inhibit the operation of the purge pump-out
compresso r.
Carbon Tank and Regeneration Subsystem
The function of the carbon tank is to absorb refrigerant
molecules that may be entrained in the discharge of noncondensables. In order to maintain effectiveness, the
carbon tan k periodically regenerates.
Carbon Regeneration Algorithm
The controller uses the carbon regeneration algorithm to
determine when to initiate, control, and terminate a
carbon regeneration cycle. The carbon bed temperature
sensor serves as the feedback to this algorithm. In
addition , the controller uses a pump-out accumulati on
timer to indicate the remaining carbon capacity in the
carbon tank. The carbon capacity is the capacity of the
carbon to adsorb refrigerant while maintaining acceptable
levels of refrigerant emission through the chiller vent line.
A capacity of 100 percent means the carbon bed has the
capacity to adsorb refrigerant and maintain acceptable
emission levels. A capacity of 0 percent means the carbon
bed has inadequate capacity to adsorb refrigerant and still
maintain acceptable emission levels.
The main objectives of the carbon regeneration algorithm
are to:
•Minimize the amount of refrigerant contained in the
carbon by performing a periodic r egener ation.
•Regenerate to maintain low emissions levels.
•Minimize the regeneration time.
•Regenerate only when the chiller is at a minimum level
of purging activity.
•Allow regeneration to occur with the chiller On or Off.
Re generation is preferabl e when the chiller is On to
ensure low carbon tank pressure, but regeneration is
also acceptable when the chiller is Off.
The rema ining amount of absorption capacity within the
carbon tank is directly proportional to the number of purge
pump-out minutes that have accumulated, and is also a
function of the chiller refrigerant type. The purge carbon
tank on an R-1233
fully saturated after the purge has accumulated
350 minutes of pump-out time. Because the relationship
between pump-out capacity and pump-out min utes is
directly proportional, it can be described by the following
equation within the regeneration algorithm:
Remain ing carbon capacity% =
100 - (pump-out minutes since last regen/pump-out
minutes at 100% capacity)*100
(E)-equipped chiller is considered to be
zd
88 CVHH-SVX001A-EN
Page 89
Start-up and Shut-down
X39003892001A
For example, an R-1233zd(E)-equipped chiller that has
accumulated 80 minutes of purge pump-out time since the
last carbon tank regeneration would be estimated to have
84 percent carbon tank capacity remaining:
100 – (80/350)*100 = 84%
The purge controls may initiate a carbon tank regeneration
cycle when the remaining carbon tank capacity is
calculated to be less than 80 percent. However, the
continued stable operation of the chiller is always more
important than the regen eration of the carb on tank.
Therefore, the following rules apply:
1 . If the Daily Pump-out Limit is disabled, a regeneration
cycle may not be initiated, regardless of the value of
the remaining carbon capacity.
Also, if the Daily Pump-out Limit is disabled during a
regeneration cy cle, the regeneration cycle must be
terminated.
2. When the remaining carbon capacity is less than
80 percent, a regeneration cycle will be initiated at the
next opportunity when the chiller is running (after the
chiller has started and no pump-out minutes have
accumulated for the previous 60 minutes).
3. If there is no opportunity to purge as indicated by Rules
1 and 2 and the remaining carbon capacity is less than
50 percent, a regeneration cycle will be initiated at the
best opportunity when the chiller is shut down (and no
pump-out minutes have accumulated for the previous
60 minutes).
4. If there is no opportunity to regenerate as indicated by
R ules 1, 2, and 3, and the carbon capacity drops below
0 percent, then a regeneration cycle is initiated.
5. Note that if at any time during the regeneration cycle,
the chiller is running and shuts down or if the chiller is
off and starts up, then the regeneration cycle is
continued.
Carbon Tank Regeneration Sequence
WARNING
Hazardous Voltage
Failure to disconnect power before servicing could
result in death or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
Fo llow proper lockout/ tagout proced ur es to ens ur e the
power can not be inadvertently energized.
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
If th e purge controller determines that carbon tank
regeneration is desired and is allowed, the purge controls:
1. Disable the purge refrigeration circuit and the p umpout solen oid valve.
2. Open the regeneration solenoid valve and turn on the
carbon tank heater.
3. Mo nitor t he carb on temperature until it reaches the
regeneration temperature value of 1 15.6°C (240°F ), and
control wi thin a ±5.6°C (±10°F) dead band for
15 minutes (this step shou ld take approximately
3hours).
CVHH-SVX001A-EN89
Page 90
Start-up and Shut-down
0 2468
Time (Hours)
If the carbon tank temperature exceeds 120 percent of the
regeneration temperature setpoint, the controller issues a
latching diagnostic, Purge Carbo n Regeneration
Temperature Limit Exceeded. The purpose of this
diagnostic is to identify a failed heater relay or
temperature sensor. It disables the purge and opens the
exhaust solenoid valve.
If the carbon tank temperature does not increase more
than 13.3°C (56°F) in the fi rst two hours, the controller
generates a non-latching diagnostic, Carbon Regeneration
T emperature T oo Low. The purpose of this diagnostic is to
identify a failed heater or temperature sensor. It prevents
automatic regeneration from occurring, but a service
technician can ini tiate a manual regen eration for testing
purposes. All other purge algorithms continue to function.
If the carbon tank temperature does not reach the
minimum regeneration temperature setpoint within 4
hours, the controller generates a non-latching diagnostic,
Purge Carbon Regen Temperature Not Satisfied. The
purpose of this diagnostic is to identify a failing insulation
system.
The complete regeneration cycle can take as long as seven
hours to accomplish, but an average chiller does not have
to regenerate very often. A typical regeneration cycle is
depicted in
Figure 51. Typical carbon regeneration cycle
Figure 51.
Time Until Next Purge Run. Displayed if the purge is
in Adaptive mode and is idle. It indicates the amount of
time left on the adaptive cycle timer.
Daily Pumpout—24 Hours. Indicates the daily
pumpout time for the last 24 hours (a moving 24-hour
window). It indicates how the hermetic integrity of the
chiller compares to historic pump-out times for the same
chiller. It also allows a check against factory-recommended
values.
Average Daily Pumpout—7 Days. Indicates the
average daily pump-out time for the last 168 hours (a
moving 168-h our window). Enables a comparison of
present pump-out times to past averages, and can be
another indication o f the hermetic integrity of the chiller.
Daily Pumpout Limit/ Alarm. Indicates the limit value
that an operator has set in the Settings menu. When the
daily pumpout rate exceeds this value, purge operation
stops and a diagnostic is generated.
Chiller On—7 Days. Indicates the percentage of time
during the past 7 days (floating 168-hour window) that the
chiller was operating. Y ou can use it to help determine if a
leak is present on the high side or the low side of the chiller.
Pumpout Chiller On—7 Days. Indicates the
percentage o f the total purge pump-out time during the
past 7 days that occurred while the chiller was operating.
Y ou can use it to help determine if a leak is present on the
high side or the low side of the chiller.
Purge Status Points
The status points appear on the purge component screen
of the Tracer AdaptiView display. The purge component
screen is accessible from the purge to uch target on the
home screen of th e display.
Pumpout Chiller Off—7 Days. Indicates the
percentage o f the total purge pump-out time during the
past 7 days that occurred when the chiller was not
operatin g. You can use it to help determine if a leak is
present on the hi gh side or the low side of the chiller.
Pumpout—Life. Indicates the total purge pump-out
time that has accumulated over the life of the purge.
Purge Rfgt Cprsr Suction Temp. Indicates the purge
refrigerant compressor suction temperature. It is useful
for diagnosing purge system problems.
Purge Liquid Temp. Indicates the temperature sensed
by the controller and used to inhibit purge operation. The
purge liquid temperature sensor, when the chiller is
operating, is the chiller saturated condenser temperature
sensor ; when the chiller is Off, it is the chiller saturated
evaporator temperature sensor. If t his t emperature is
below the Pumpout Inhibit Temperature that is defined in
the Settings menu, pump out is not allowed. This value is
used to prevent inefficient operation of the purge under
certain conditions.
Carbon Tank Tem p. Indicates the carbon bed
temperature and is useful for monitoring regeneration and
for diagnosing regener ation system problems.
90 CVHH-SVX001A-EN
Page 91
Recommended Maintenance
X39003892001A
WARNING
Hazardous Volt age w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharg e all motor start/ run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. V er ify with an appropriate voltmeter that all
capacitors have discharged.
For additional inf ormation regarding the safe discharge of
capa citors, see PROD-SVB06*-EN
NOTICE:
Check Purge Run-Time for Unit Hermetic
Integrity!
If frequent purging is required, failure to monitor purge
pumpout rate, identify and correct source of air or
water leak as soon as possible could shorten chiller life
expectancy, due to moisture contamination caused by
leakage.
NOTICE:
Do Not Use Non-Compatible Parts or
Materials!
Use of non-compatible parts or materials c ould result in
equipment damage. Only genuine Trane
components with identical Trane part numbers should
be used in Trane CenTraVac chillers. Trane assumes no
responsibility for damages resulting from the use of
non-compatible parts or materials.
This section describes th e basic chiller preventive
maintenance procedures, and recommends the intervals
at which these procedures should be performed. Use of a
periodic maintenance program is important to ensure the
best possib le performance and efficiency from a
CenTraVac chiller.
®
replacement
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Important:
•Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
Record Keeping Forms
An important aspect of the chiller maintenance program is
the regular compl etion of recor ds. Refer to
Check Sheets,” p. 102
forms. When filled out accurately by the machine operator,
the completed logs can be reviewed to identify any
developing trends in the chiller’s operating conditions. For
example, if the machine operator notices a gradual
increase in condensing pressure during a month’s time, he
can systematically check, then correct the possible cause
of this condition.
for copies of the recommended
“ Forms and
CVHH-SVX001A-EN91
Page 92
Recommended Maintenance
Normal Operation
Table 19. Normal operation
Opera ting CharacteristicNorma l R eading
Approximate Evaporator Pressure55.2 to 91.0 kPaa (8 to 13.2 psia) / -46.2 to -10.3 kPag (-6.7 to -1.5 psig)
Approxim ate Condenser Pressure
Oil S ump Tem perature Unit not running 43.3°C to 57.2 °C (110°F to 135°F)
Oil S ump Tempe rature Unit running43. 3°C to 71.1°C ( 110°F to 16 0°F)
Oil S um p Differential Oil Pressure
(a) Condenser pressure is dependent on condenser water tem perature, and should equal the saturation pressure of R-1233zd(E) at a temperature above
that of leaving condenser water at full load.
(b) Oil tank pressure: -48.3 to -27.6 kPag (-7 to -4 psig). Discharge oil pressure: 89.6 to 137.9 kPag (13 to 20 psig).
Table 20. Recommended maintenance
DailyEve r y 3 monthsEvery 6 m onthsAnnua lly
Check the chiller’s evaporator and
condenser pressures, oil tank
pressure, differential oil pressure
and discharge oil pressure.
Compare the readings with the
values provided in
Check the oil level in the chiller oil
sump using the two sight glasses
provided in the oil sump head.
When t he unit is operating, the oil
level should be visible in the lower
sight glass.
Complete logs on a daily basis.
Tab le 1 9, p. 92 .
(a)
166.9 to 259.9 kPaa (24.2 to 37.7 psia) / 65.5 to 158.6 kPag (9.5 to 23 psig) (standard condenser)
(b)
137.9 to 165.5 kPad (2 0 to 24 psid)
Clean all water st rainers in the
water piping system .
Lubricate the vane control linkage
bearings, ball joints, and pivot
points.
Lubricate vane operator tang
O-rings.
Operate the tang operators
manually and check for any
abnormalities.
Drain content s of the rupture disk
and purge discharge ventline dripleg into an evacuated waste
container. Do this more often if the
purge is operated excessively.
Apply oil to any exposed m etal
parts t o prevent rust.
( a) , ( b)
Sh ut d ow n t h e ch iller on ce ea ch y ear t o check t he
item s listed on the
(refer t o “Forms and Check Sheets,” p. 102).
Perform the annual ma intenance procedures
referred to in
p. 94.
Use an ic e w at er b at h t o v er ify t h e accu ra cy of t h e
evaporator refrigerant temperature sensor
(4BT11). I f the sensor is exposed to t emperature
extremes outside its normal operati ng range
(-17.8°C to 32.2°C [ 0°F to 90°F]) , check its
accuracy at six-month intervals.
Inspect the condenser tubes for fouling; clean if
necessary.
Inspect and clean the ifm efector
sensors.
Submit a sam ple of t he compressor oil to a Tranequalified laboratory for comprehensive analysis.
“CVHH Annual Inspection List”
“EarthWise Purge Maintenance,”
®
flow detection
92 CVHH-SVX001A-EN
Page 93
Recommended Maintenance
Table 20. Recommended maintenance (continued)
Measure the compressor motor winding resistance
to ground; a qualified service technician should
conduct this check to ensure that the findings are
properly interpreted. Contact a qualified service
organizat ion to leak-test the chiller; this
procedure is especially important if the system
requires frequent pur ging.
(a) Every three years, use a nondestructive tube test to inspect the condenser and evaporator tubes. It may be desirable to perform tube tests on these
com ponents at m ore frequent intervals, depending upon chiller application. This is especially true of critical process equipment.
(b) Contact a qualified service organization to determine when to conduct a complete examination of the unit to discern the condition of the com pressor
and internal components. Check t he following: chronic air leaks (which can cause acidic condit ions in the compressor oil and result in premature bearing
wear) and evaporator or condenser water tube leaks (water mixed with the com pressor oil can result in bearing pitting, corrosion, or excessive wear).
Table 21. Recommended m aintenance of option al features
FeatureEv e r y 3 monthsEver y 6 monthsAnn ually
Waterbox Coatings Inspect waterbox coat ings within the
Waterbox AnodesInspect waterbox anodes within the first
GantriesLubricate the gantries annually. Use ConocoPhillips
Hing es
first 1–3 m onths to determine a required
maintenance schedule for your job site.
Refer to
“Waterbox and Tubesheet
Protective Coatings,” p. 97 for more
information.
1–3 months to determine a required
maintenance schedule for your job site.
Refer to
“Sacrificial Anodes,” p. 97 for
more information.
MegaPlex
Purpose (blue in color), or equivalent.
Lubricate the hinges annually. Use ConocoPhillips
MegaPlex® XD3 (gray in color), LPS® MultiPlex MultiPurpose (blue in color), or equivalent.
®
XD3 (gray in color), LPS® MultiPlex Multi-
Compressor Oil Change
After the first six months of accumulated operation, or
after 1,000 hours operation—whichever comes first—it is
recommended to change the oil filter. It is recommended
to subscribe to the Trane annual oil analysis program
rather than automatically change the oil as part of
scheduled maintenance . Change the oil only if indicated
by the oil analysis. Use of an oil analysis program will
reduce the chiller’s overall lifetime waste oil generation
and minimize refrigerant emissions. The analysis
determines system moisture content, acid level, and wear
metal content; it can be used as a diagnostic tool. Due to
the new refrigerant and oil combination, the oil analy sis
should be performed by the Trane Chemical Laboratory.
In conjunction with other diagnostics performed by a
qualified service technician, oil analyses can provide
valuable information on the performance of the chiller to
help minimize operating and maintenance costs and
maximize its operating life. An access valve is installed in
the oil supply line, befor e the oil filter, for obtaining oil
samples.
Notes:
•Use only Trane OIL00022. A full oil change is 79.5 L
(21 gallons).
Leak Checking Based on Purge
Pump Out Time
Figure 52 has been developed to aid in determining when
to do a leak check of a chiller based on the purge pump out
time and unit siz e. This figure depicts normal purge pumpout times, small leaks and large leaks based on the chiller
tonnage.
If the purge pump-out time is in the small leak region, then
a leak check should be performed and all leaks repaired at
the earliest convenience. If the purge pump-out time is in
the large leak region, a thorough leak check of the unit
should be performed immediately to find and fix the leaks.
CVHH-SVX001A-EN93
Page 94
Recommended Maintenance
Chiller tons (per circuit)
Purge minutes/day
large leak
small leaks
t ypical operation
X39003892001A
Figure 52. Purge operation under typical and leak
conditions
RuptureGuard Maintenance
It is recommende d th at the RuptureGuard be visually
inspected and the relief valve pressure tested annually.
The test can be performed with the valve in place and the
refrigerant in the chiller.
The vent li ne drip leg must be periodically checked fo r
accumulation of water or refrigerant. Drain any
accumulation that may be present into an evacuated,
properly labeled vessel and dispose of in accordance with
local, state and federal codes.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could
result in death or serious injury. Disconnect all electric
power, including remote disconnects before servicing.
Fo llow proper lockout/ tagout proced ur es to ens ur e the
power can not be inadvertently energized.
EarthWise Purge Maintenance
Maintenance requirements for an EarthWise purge system
with Tracer AdaptiView control are described in this
section. To ensure efficient and reliable purge operation,
perform all inspections and procedures at the prescribed
intervals. Keep records of inspection results to establi sh
proper service intervals. Document changes that occur in
purge activity that could provide information about chiller
performance.
WARNING
Contain Refrigerant!
Failure to follow proper procedures or the use of nonapproved refrigerants, refrigerant substitute s, or
refrigerant additives could result in death or serious
injury or equipment damage. System contains oil and
refr igerant under high pressure. Recover refrigerant to
relieve pressure bef ore opening the sys tem. See unit
nameplate for refrigerant type. Do not use nonapproved refrigerants, refrigerant substitute s, or
refrigerant additives.
Note: Graphic labels (shown above) are used for CE
application only.
Important:
•Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
•All electrical enclosures—unit or remote—are IP2X.
CAUTION
Hot Surfaces!
Failure to follow instructions below could result in
minor to severe burns. Surface temperatures may
exceed 148.9°C (300°F) on condensing unit and carbon
tank. Wear protective gear and allow surfaces to cool
before servicing these parts or any part located in their
vicinity.
Weekly Maintenance
P erform the following maintenance procedure on a weekly
basis:
94 CVHH-SVX001A-EN
Page 95
Recommended Maintenance
1. With the purge unit operating, check the purge tank
condensing activity by observing the liquid refrigerant
flow in the moisture-indicating sight glass located in
the liquid drain line immediately after the fi lter drier
canister. A lack of visible refrigerant flow in the sight
glass indicates one of the following:
• A pump-out cycle is necessary
• A problem exists with the purge heat transfer circuit
(such as the condensing unit, expansion device, or
purge evaporator coil)
• A problem exists in the purge control subsystem
• Refrigerant vapor from the chiller condenser is
blocked or restricted
2. Check the moisture-indicator sight glass. Replace the
filter-drier core if moisture is indicated.
No te: The need for frequent changes of the filter drier
could be an indication of significant chiller air or
tube leaks.
Semi-Annual Maintenance
P erform the following maintenance procedure on a semiannual basis:
1. Inspect the air-cooled condenser coil and clean as
needed. Clean the coil from the fan side u sing
compressed air or coil cleaner. A dirty coil will reduce
purge efficiency and capacity.
2. Inspect the purge tank and carbon tank insulation for
any damage or degradation. Make any needed repairs
to the insulation.
Annual Maintenance
Perform the following main tenance procedure on an
annual basis:
1. Perform the semi-annual maintenance procedures.
2. Open the purge control panel and check all internal
components for such problems as corrosion, terminal
tightness, or signs of overheating.
3. Change the filter-dri er assembly.
Ins pecting the Moisture Indicator
Monitor the quality of the liquid refrigerant in the chiller by
periodi cally inspecting the moisture indicator. The
ind icato r will show “ wet” whenever the chiller moisture
exceeds the levels shown in
indicator becomes more sensitive as the temperature
decreases. (The moisture i ndicator normally operates at
equipment room ambient temperatures.)
A “ wet” indication for more t han 72 hours typically
indicates that the filter-drier is saturated and should be
replaced. In some cases in which a substantial amount of
moisture has accumulated, such as when the chil ler has
been serviced, several filter-drier assembly changes may
be required before a satisfactory moisture level is
Table 22. Notice that the
achieved. A reoccurring or persistent “ wet” indication is a
sign of possible chiller air or water infiltration.
Inspect the moisture indicator only under the following
conditions:
•The chiller is operating.
•The purge unit is operating and has been allowed
sufficient time to properly remove system moisture
(allow a minimum of 72 hours after replacing filterdrier).
T able 22. Refriger ant moisture content as determined by
Note: Refrigerant moisture content given in parts per million (ppm).
23 .9 °C
( 75 °F)
37 .8 °C
( 10 0°F)
51 .7 °C
( 12 5°F)
Maintaining the Moisture-Indicating Sight
Glas s
In normal operating cond itions, the moisture-ind icating
sight glass should not require maintenance beyond
keeping the sight glass clean. However, the sig ht glass
should be replaced after any major repair to the unit has
taken place, or if it is on a unit in which severe moistu re
contamination is known to have occurred.
Be aware that it is normal for the sight glass to indicate the
presence of moisture for a period of least 72 hours after it
is installed and after it has been exposed to atmosphere.
Allow a minimum of 72 hours after sight glass installation
or filter-drier service before using the sight glass to
determine the system moisture content.
Removing Air After Servicing the Chiller
Air that leaks into a chiller during servicing needs to be
removed so that the chiller can operate normally. The
purge pump-out system, which performs this funct ion,
may operate for a long time to remove the air before
cycling off for the first time. This is due to the large amount
of non-condensables and the relatively small amount of
refrigerant b eing drawn into th e pur ge tank.
Important: Do not bypass or remove the pump-out
restrictor of the EarthW ise Purge syst em.
Doing so could reduce the efficiency of the
purge system. The purge system has a
faster air exhaust rate than previous purge
systems, which makes bypassing or
removing the restrictor unnecessary.
The Daily Pumpout Limit determines how long the purge
pump-out compressor can operate continuously without
generating a Purge Daily Pumpout Exceeded diagnostic,
which will shut off the purge system. Y ou can disable the
CVHH-SVX001A-EN95
Page 96
Recommended Maintenance
X39003892001A
Daily Pumpout Limit to allow the purge to pump out for an
extended p eriod of time.
Once the level of non-condensables present in the chiller
falls to a point in which an increasing amount of refrigerant
enters the purge tank, the pump-out compressor begins to
cycle on and off. As the refrigerant in the system becomes
less contaminated with non-condensables, purge pumpout is activated less frequently.
Note: If large amounts of non-condensables are present
in the chiller, the air removal rate can be enhanced
by o perating the chiller at part-load conditions.
Leak Testing
WARNING
Hazard of Explosion!
Failure to follow recommended safe leak test
procedures could result in death or serious injury or
equipment or property-only-damage. Never use an
open flame to detect gas leaks. Explosive conditions
may occur. Use a leak test solution or other approved
methods for le a k testing.
WARNING
Hazardous Pressures!
Failure to follow these safety precautions could result
in a sudden rise of pressure possibly resulting in a
violent explosion whic h could result in death or serious
injury. If a heat source is required to raise the tank
pressure during removal of refrigerant from cylinders,
use only warm water or heat blankets to raise the tank
temperature. Do not exceed a temperature of 150°F. Do
not, under any circumstances apply direct flame to any
portion of the cylinder.
Important: If leak testing is required , contact a Trane
service agency.
Recommended System Maintenance
NOTICE:
P roper Water Treatment!
The use of untreated or improperly treated water in a
CenTraVac could result in sc aling, erosion, corrosion,
algae or slime. It is recommended that the services of a
qualified water treatment specialist be engaged to
determine what water treatment, if any, is required.
Trane assumes no responsibility for equipment failures
which result from untreated or improperly treated
water, or saline or brackish water.
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Condenser
Condenser tube fouling is indicated when the approach
temperature (the difference between the condensing
refrigerant temperature and the leaving condenser water
temperature) is higher than predicted.
If the annual condenser tube inspection indicates that the
tubes are fouled, two cleaning methods, mechanical and
chemical, can be used to rid the tubes of contaminants.
Use the mechanical cleaning method to remove sludge
and loose material from smooth-bore tubes.
To clean other types of tubes including internallyenhanced types, consult a qu alified service organization
for recommendations.
96 CVHH-SVX001A-EN
Page 97
Recommended Maintenance
pipe
connections
circulator
pump
cleaning
solution
shutoff
valves
Figure 53. Typical chemical cleaning setup
Evaporator
Since the evaporator is typically part of a closed circuit, it
may not accumulate appreciable amounts of scale or
sludge. Normally, cleaning every three years is sufficient.
However, periodic inspection and cleaning is
recommended on open evaporator systems, such as air
washers.
Waterbox and Tubesheet Protective Coatings
Trane recommends that coated waterboxes/tubesheets—
regardless of the type of protective coating included—be
taken out of service within the first one to three months of
operation for inspection. Any voids or defects identified
upon inspection must be repaired. If the water quality is
known to be highly supportive of corrosion (i.e., sea water,
etc.), inspect the coating system at one month; if the water
quality is known to be relatively benign (i.e., normal
treated and clean condenser water), inspect the coating
1. Follow all instructions in “ Waterbox Removal and
Installa tion,” p. 98
2. Work a round nylon or brass bristled brush (attached to
a rod) in and out of each of the condenser water tubes
to loosen the sludge.
3. Thoroughly flush the condenser water tubes with clean
water.
Scale deposits are best removed by chemical means.
Be sure to consult any qualified chemical house in the
area (one familiar with the local water supply’s
chemical mineral content) for a recommended
cleani ng solution suitable for the job.
No te: A standard condenser water circuit is
composed solely of copper, cast iron, and steel.
to remove water box covers.
NOTICE:
Unit Corrosion Damage!
Failure to follow proper proced ures when using
corrosive chemicals to cl ean water side of unit could
result in corrosion damage to the unit and tubes. It is
recommended that the services of a qualified ch emical
cleaning firm be used. Proper personal protective
equipment as recommended by the chemical
manufacturer should be used. Refer to the chemicals
MSDS sheet for proper safety procedures.
Important: All of the materials used in the external
circulation system, the quantity of the
solution, the duration of the cleaning
period, and any required safety precautions
should be approved by the company
furnishing the materials or performing the
cleaning. Rememb er, however, that
whenever the chemical tube cl eaning
method is used, it must be followed up with
mechanical tube cleaning, flushing and
inspection.
CVHH-SVX001A-EN97
system within three months. Only when initial inspections
show no problems are present should subseq uent
maintenance intervals be increased.
Sacrificial Anodes
The replacement schedule for the optional zinc or
magnesium anodes can vary greatly with the
aggressiveness of the water that is in the system. Some
sites could require anode replacement every two to three
months while other sites may require anode replacement
every two to three years. Tran e recommends that anode
inspection for wear sometime within the first several
months of the anodes being placed into service. If the
observed loss of anode material is small, then the interval
between subsequent inspections can be lengthened.
Replace the anode and/or shorten the inspection interval if
the anode has lost 50 percent or more of its original mass.
If anode depletion occurs very quickly, consult a water
treatment specialist to determin e if the anode material
selected is correct for the application.
NOTICE:
Equipment Damage!
Failure to follow instructions could res ul t in equipment
damage. Do NOT use Teflon-based tape or paste on
anode; a s mall amount of liquid sealant (Loc tite®242 or
equivalent) may be applied to prevent leakage when
installing an anode, but do not apply so much sealant
that it prevents the necessary electrical connection
between the anode and the waterbox.
As needed after draining the waterbox, use a 63.5 mm (2-1/
2 in.) wrench to remove/insta ll Trane-supplied waterbox
anodes.
Page 98
Waterbox Removal and Installation
LIFTING
LOCATION
LIFTING
LOCATION
Lifting
location
Lifting
location
LIFTING
LOCATION
LIFTING
LOCATION
Lifting
location
Lifting
location
Important: Only qualified technicians should perform
the installation and servicing of this
equipment.
Discussion
This section will discuss recommended lifting. Proper
lifting technique will vary based on mechanical room
layout.
•It is the responsibility of the person(s) performing the
work to be properly trained in the safe practice of
rigging , lifting, securing, and fastening of the
waterbox.
•It is the responsibility of the person(s) providing and
using the rigging and lifting devices to inspect these
devices to ensure they are free from defect and are
rated to meet or exceed the published weight of the
waterbox.
•Always use rigging and lifting devices in accordance
with the applicable instru ctions for such device.
Procedure
WARNING
Heavy Objects!
Failure to properly lift waterbox c ould result in death or
serious injury. Each of the individual cables (chains or
slings) used to lift the waterbox must be capable of
supporting the entire weight of the water box. The
cables (chains or slings) must be rated for overhead
lifting applicati ons with an acceptable working load
limit. Refer to
Table 24, p. 99 for waterbox weights.
5. Disconnect water pipes, if connected.
6. Remove waterbox bolts.
7. Lift the waterbox away from the shell.
Figure 54. Waterbox lifting—condenser and evaporator
lifting points
Review mechanical room limitations and determine the
safest meth od or methods of rigging and lifting th e
waterboxes.
1. Determine the type and siz e of chiller being serviced.
Refer t o Trane nameplate locate d on chiller control
panel.
Important: This literature contains rigging and lifting
information only for T rane CTV chillers built
in La Crosse. For Trane CTV chiller s built
outside the United States, refer to literature
provided b y the applicable manufacturing
location.
2. The rated lifting capacity of the lifting shackle must
meet or exceed the published weight of the waterbox.
Verif y the waterbox weight from the latest published
literature.
3. Ensure that the lift connection device has the correct
size for the waterbox lifting hole.
4. Properly connect the shackle to the
waterbox.Fig ure 54, p. 98
98 CVHH-SVX001A-EN
WARNING
Overhead Hazard!
Failure to follow instructions could result in death or
serious injuries. Never stand below or in close
proximity to heavy objects while they are suspended
from, or being lifted by, a lift ing device in case the
object drops.
8. Stor e waterbox in a safe and secure locatio n and
position.
Note: Do not leave waterbox suspended from lifting
device.
Page 99
Waterbox Removal and Installation
Reassembly
Once service is co mplete, the wat erbox sh ould be
reinstalled on the shell following all previous procedures
in reverse. Use new O-rings or gaskets on all join ts after
thorou ghly cleaning each joint.