Trane CVHH Installation, Operation And Maintenance Manual

CVHH Water-Cooled CenTraVac Chillers
With Tracer AdaptiView Control
Model: CVHH
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air­conditioning equipment can be hazardous and r equires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all pr ecautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
October 2014
X39641257001
SAFETY WARNING
CVHH-SVX001A-EN
Introduction
X39003892001A
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Y our personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/ stat e/national electrical codes.
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situatio n which, if not avoided, could result in death or serio us in jur y.
Indicates a potentially hazardous situatio n which, if not avoided, could result in minor or moderat e injury. It could also be used to alert against unsaf e practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlo rin e, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same po tential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs.
Important Responsible Refrigerant Pr actic es
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technician s who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirement s that must also be adhered to for r esponsible management of refrigerants. Know the applicable laws and follow them.
Note: Graphic labels (shown above) are used for CE
application only.
Important:
Before servicing, disconnect all power so urces an d
allow at least 30 minutes for capacitors to discharge.
All electrical enclosures—unit or remote—are IP2X.
© 2014 Trane All rights reserved CVHH-SVX001A-EN
Introduction
X39003892001A
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut res istant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/ SDS and OSHA/GHS (Global Harmonized System of Clas s ification and Labelling of C hemicals ) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a ris k of energiz ed elec trical c ontact, arc, or flash, tec hnicians MUST put on all PPE in ac c ordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PE RFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING W ITHOUT PROPER ELECTRICAL PPE AND ARC FL ASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
WARNING
Replace Manual in Cabinet After Use!
Failure to replace this Installation, Operation, and Maintenance manual in cabinet after use could prevent personnel fr o m access in g necessary safety information and could r esult in death or serious injury or equipment damage.
NOTICE:
Do Not Use Non-Compatible Parts or Materials!
Use of non-compatible parts or materials c ould result in equipment damage. Only genuine Trane® replacement components with identical Trane part numbers should be used in Trane CenTraVac chillers. Trane assumes no responsibility for damages resulting from the use of non-compatible parts or materials.
WARNING
Refrigerant May Be Under Positive P ressure!
Failure to recover refrigerant to relieve pressure or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in an explosion which could result in death or serious injury or equipment damage. System contains oil and refr igerant and may be under positive pressure. Recover refrigerant to relieve pressure bef ore opening the system. See unit nameplate for refrig er ant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
CVHH-SVX001A-EN 3
Note: Graphic labels (shown above) are used for CE
application only.
Copyright
This document and the information in it are the property of T rane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Introduction
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
CVHH-SVX001A-EN (10 Oct 2014)
First version of this literature
Factory Warranty Information
Compliance with the following is required to preserve the factory warranty:
All Unit Installations
Startup MU ST be performed by Trane, or an authorized agent of Trane, to VALIDATE this WARRANTY. Contractor must provide a two-week startup notification to T rane (or an agent of Trane specifically authorized to perform startup).
Additional Requirements for Units Requiring Disassembly
When a new fully assembled chiller is shipped and received from our Trane manufacturing location and, for any reason, it requires disassembly or partial disassembly—which could include but is not limited to the evaporator, condenser, control panel, compressor/motor, purge, factory-mounted starter or any other components origin ally attached to the fully assembled unit— compliance with the following is required to preserve the factory warranty:
Trane, or an agent of Trane specifically authorized to perform start-up and warranty of Trane perform or have direct on-site technical supervision of the disassembly and reassembly work.
The installing con tractor must notify Trane—or an agent of Trane spe cifically authorized to perform startup and warranty of Trane in advance of the scheduled disassembly work to coordinate the disassembly and reassembly work.
Start-up must be performed by Trane or an agent of Trane specifically authoriz ed to perform startup and warranty of Tran e
Trane, or an agent of Trane specifically authorized to perform start-up and warr anty of Trane provide qualified personnel and standard hand tools to perform the disassembly work at a location specified by the contractor. Trane, or an agent of Trane specifically authorized to per form star t-up and warranty of Trane products, will perform or have direct on-site supervision of the disassembly and reassembly work. The contractor shall provide the rigging equipment such as chain falls, gantries, cranes, forklifts, etc. necessary for the disassembly and reassembly work and the required qualified personnel to operate the necessary rigging equipment.
Important: Any devi ation from these r equirements
®
products.
must be agre ed upon prior to startup in a written agreement from Trane.
®
products—two weeks
®
products, will
®
products, will
4 CVHH-SVX001A-EN
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warnings, Cautions, and No tices . . . . . . . . 2
Important Environmental Concerns . . . . . 2
Important Responsible Refrigerant Pra ctices
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Unit and Compressor Nameplates . . . . . . . . 8
Unit Nameplate . . . . . . . . . . . . . . . . . . . . . . . 8
Compresso r Nameplate . . . . . . . . . . . . . . . . 9
Model Number Descriptions . . . . . . . . . . . . . 10
CVHH CenTraVac Chiller Description . . . . 10
CCHH Centrifugal Compressor Descri ption 10
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . 11
ASHRAE Standard 15 Compliance . . . . . . 11
Unit Shipment . . . . . . . . . . . . . . . . . . . . . . . 11
General Information . . . . . . . . . . . . . . . . . . 11
Installat ion Requirements and Contractor Re-
sponsibilities . . . . . . . . . . . . . . . . . . . . . . . . . 11
Storage Requirements . . . . . . . . . . . . . . . . 13
Unit Components . . . . . . . . . . . . . . . . . . . . . 14
Unit Clearances and Weights . . . . . . . . . . . . 15
Recommended Unit Clearances . . . . . . . . 15
General Weights . . . . . . . . . . . . . . . . . . . . . . 16
Installation: Mechanical . . . . . . . . . . . . . . . . . 17
Operating Environment . . . . . . . . . . . . . . . 17
Foundati on Requirements . . . . . . . . . . . . . 17
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Standard Chiller Lift . . . . . . . . . . . . . . . . . 17
Special Lift Requirements . . . . . . . . . . . . 18
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . 19
Isolatio n Pads . . . . . . . . . . . . . . . . . . . . . . . . 19
Spring Isolators . . . . . . . . . . . . . . . . . . . . . . 19
Leveling the Un it . . . . . . . . . . . . . . . . . . . . . 20
Installation: Water Piping . . . . . . . . . . . . . . . . 22
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Water Treatment . . . . . . . . . . . . . . . . . . . . . 22
Pressure Gauges . . . . . . . . . . . . . . . . . . . . . 22
Valves—Drains and Vents . . . . . . . . . . . . . 22
Strainers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Required Flow-Sensing Devices . . . . . . . . 22
Evaporator and Condenser Water Piping .25
Water Piping Connections . . . . . . . . . . . . . .26
Waterbo x Locations . . . . . . . . . . . . . . . . . . .26
Grooved Pipe Coupling . . . . . . . . . . . . . . . . .27
Flange-Connect ion Adapters . . . . . . . . . . . .27
Victaulic Gasket Instal lation . . . . . . . . . . . . .28
Bolt-Tig htening Sequen ce for Water Pipin g
Connections . . . . . . . . . . . . . . . . . . . . . . . . . .29
Flanges with 8 or 12 Bolts . . . . . . . . . . . . .29
Flanges with 16 or 20 Bolts . . . . . . . . . . . .29
Pressure Testin g Waterside Piping . . . . . . .29
Vent Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Refrigerant Vent Line . . . . . . . . . . . . . . . . . .30
General Requirements . . . . . . . . . . . . . . . .30
Purge Discharge . . . . . . . . . . . . . . . . . . . . .30
Vent Line Materials . . . . . . . . . . . . . . . . . .30
Vent Line Sizing . . . . . . . . . . . . . . . . . . . . .30
Vent Line In stallation . . . . . . . . . . . . . . . . . . .31
Trane Ruptu reGuard . . . . . . . . . . . . . . . . . . .34
General Information . . . . . . . . . . . . . . . . . .34
Connection to External Vent Line and Drip
Leg . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Insulati on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Unit In sulation Requirements . . . . . . . . . . .39
Insulation Thickness Requirements . . . . . .39
Installation: Controls . . . . . . . . . . . . . . . . . . . . .41
UC800 Specifications . . . . . . . . . . . . . . . . . .41
Wiring and Port Descriptions . . . . . . . . . .41
Communication Interfaces . . . . . . . . . . . .42
Rotary Switches . . . . . . . . . . . . . . . . . . . . .42
LED Des cription and Operation . . . . . . . .42
Installing the Tracer AdaptiView Display . .44 Adjusting the Tracer AdaptiView Display Arm
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Electrical Requirements . . . . . . . . . . . . . . . . . .46
Installation Requ irements . . . . . . . . . . . . . .46
Electrical Requirements . . . . . . . . . . . . . . . .46
Trane-Supp lied Remote Starter Wiring . . .48
Customer-Supplied Remote Starter Wiring 49
CVHH-SVX001A-EN 5
Table of Contents
Current Transformer and Potential Transform-
er Wire Sizing . . . . . . . . . . . . . . . . . . . . . . . . 50
Power Supp ly Wiring . . . . . . . . . . . . . . . . . . . 51
Three-Phase Power . . . . . . . . . . . . . . . . . 51
Circuit Breakers and Fused Disconnect s . 52
CE for Control Power Transformer (CP TR ) Op-
tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
CE for Starter or Drive . . . . . . . . . . . . . . . 52
Contro l Power Transformer (CPTR) Option
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Power Factor Correction Capacitors (Optional)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Intercon necting Wiring . . . . . . . . . . . . . . . . 56
Starter t o Motor Wiring (Remote-Mount ed
Starters Only) . . . . . . . . . . . . . . . . . . . . . . . . 57
Ground Wire Terminal Lugs . . . . . . . . . . 57
Terminal Clamps . . . . . . . . . . . . . . . . . . . 58
Wire Terminal Lugs . . . . . . . . . . . . . . . . . 58
Bus Bars . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Starter t o Control Panel Wiring . . . . . . . . . 59
Medium Voltage Installation . . . . . . . . . . . . . 60
Medium Voltage Motor . . . . . . . . . . . . . . 60
Motor Terminal Box . . . . . . . . . . . . . . . . . 60
Motor Supply Wiring . . . . . . . . . . . . . . . . . . 61
System Control Circuit Wiring (Field Wiring)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Water Pump Int erlock Circuits and Flow
Switch Input . . . . . . . . . . . . . . . . . . . . . . . 64
Temperature Sensor Circuits . . . . . . . . . . . 65
Optional Control and Output Circuits . . . 66 Optional Tracer Communication Interface 66
Unit St art-up/Commissioning . . . . . . . . . . 66
Starter Module Configuration . . . . . . . . . . 66
Schematic Wiring Drawings . . . . . . . . . . . . 66
Operating Princip les . . . . . . . . . . . . . . . . . . . . 67
General Requirements . . . . . . . . . . . . . . . . 67
Cooling Cycle . . . . . . . . . . . . . . . . . . . . . . . . 67
Oil and Refrigerant Pump . . . . . . . . . . . . . . 68
Motor Cooling System . . . . . . . . . . . . . . . . 70
Tracer Adap tiView Display . . . . . . . . . . . . . 70
RuptureGuard . . . . . . . . . . . . . . . . . . . . . . . . 71
EarthWise Purge . . . . . . . . . . . . . . . . . . . . . . 71
How a Purge System Works . . . . . . . . . . .71
Start-up and Shut-down . . . . . . . . . . . . . . . . . .75
Chiller Sequence of Operation . . . . . . . . . .75
Software Operation Overview Diagram . .75 Start-up Se quence of Operation—Wye-Delta
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Power Up Diagram . . . . . . . . . . . . . . . . . . .78
Ice Machine Control . . . . . . . . . . . . . . . . . . .78
Free Cooling Cycle . . . . . . . . . . . . . . . . . . . . .80
Hot Water Control . . . . . . . . . . . . . . . . . . . . .80
Control Panel Devices and Unit-Mou nted De-
vices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81
Unit Control Panel . . . . . . . . . . . . . . . . . . .81
User-Defined Language Support . . . . . . .81
Unit St art-up and Shut-down Procedures .81
Daily Unit Start-up . . . . . . . . . . . . . . . . . . .82
Seasonal Unit Start-up . . . . . . . . . . . . . . .82
Daily Unit Shut-down . . . . . . . . . . . . . . . .82
EarthWise Purge Sequence of Operations 83
Purge Operating Modes . . . . . . . . . . . . . .83
Air Removal . . . . . . . . . . . . . . . . . . . . . . . .87
Pump-out Operating Sequence . . . . . . . .87
Carbon Tank and Regeneration Subsystem
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Recommended Maintenance . . . . . . . . . . . . .91
Record Keeping Forms . . . . . . . . . . . . . . .91
Normal Operation . . . . . . . . . . . . . . . . . . .92
Compresso r Oil Change . . . . . . . . . . . . . . . .93
Leak Checking Based on Purge Pump Out
Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
RuptureGu ard Maintenance . . . . . . . . . . . . .94
EarthWise Purge Maintenance . . . . . . . . . .94
Weekly Maintenance . . . . . . . . . . . . . . . . .94
Semi-Annual Maintenance . . . . . . . . . . . .95
Annual Maintenance . . . . . . . . . . . . . . . . .95
Inspecting t he Moisture Indicator . . . . . . .95
Maintaining the Moisture-Indicating Sight
Glass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
Removing Air After Servicing the Chiller .95 Recommended System Maintenance . . .96
6 CVHH-SVX001A-EN
Waterbox Removal and Installation . . . . . . 98
Discussion . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Reassembly . . . . . . . . . . . . . . . . . . . . . . . . 99
Torque Requirements . . . . . . . . . . . . . . . 99
Bolt-Tightening Sequence for Waterboxes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Evaporator Waterbox Covers . . . . . . . . 101
Condenser Waterbox Covers . . . . . . . . 101
Heat Recovery Condenser Waterbox Covers
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Forms and Check Sheets . . . . . . . . . . . . . . . 102
Table of Contents
CVHH-SVX001A-EN 7
Unit and Compressor Nameplates
Unit Nameplate
The unit nameplate is located on the left side of the control panel. A typical unit nameplate is illustrated in and contains the following information:
Unit model and size descriptor
Unit electrical requirements
Correct operating charge and refrigerant type
Unit test pressures and maximum operating pressures
Unit li terature
Serial Number. The unit serial number provides the
specific chiller identity. Always provide this serial number when call ing for service or during parts identification.
Service Model Number. The service model represents
the unit as built for service purposes. It identifies the selections of variable unit features requ ired when ordering replacements parts or requesting service.
No te: Unit-mounted starters are identified by a separate
number found on the starter.
Product Description Block. The CenTraVac™ models
are defined and built using the Product Definition and Selection (PDS) system. This system describes the product offerings using a product coding block which is made up of feature categories and codes that identifies all characteristics of a unit.
Figure 1
Figure 1. Typical unit nameplate (CDHF shown; CVHH
is similar)
8 CVHH-SVX001A-EN
Compressor Nameplate
TRANE MADE IN USA X39002458010B
MODEL NO.
SALES ORDERSERIAL NO.
The compressor assembly has a separate model number which is required to identify internal and external compressor parts. The model number begins with “ CCHH” and the nameplate is located on the foot of the volute.
Figure 2. Compressor nameplate
No te: The serial number space on the compressor
nameplate will be intentio nally left blank.
Unit and Compressor Nameplates
CVHH-SVX001A-EN 9
Model Number Descriptions
CVHH CenTraVac Chiller Description
Digit 1, 2 — Simplex CenTraVac™ Chiller
Digit 3 — Drive Digit 4 — Development
Sequence Digit 5, 6, 7 — Nominal Total
Compressor Tonnage Digit 8 — Unit M otor Voltage Digit 9 — Unit Type Digit 10, 11 — Design Sequence Digit 12 — M anufacturing
Location Digit 13 — Hot Gas Bypass
(HGB) Digit 14 — Starter Type Digit 15 — Control Enclosure Digit 16 — Evaporator Shell Size Digit 17 — Evaporator Tube
Bundle Digit 18 — Evaporator Tubes Digit 19 — Evaporator Waterbox Digit 20 — Condenser Shell Size Digit 21 — Condenser Tube
Bundle Digit 22 — Condenser Tubes Digit 23 — Condenser
Waterboxes Digit 24 — Auxiliary Condenser
Size and Waterboxes Digit 25 — Evapora tor Orifice
Size Digit 26 — Economizer Orifice
Size Digit 27 — Condenser Orifice
Size Digit 28 — Unit Option Digit 29 — Control: Enhanced
Protection Digit 30 — Control: Extended
Operation Digit 31 — Tracer™
Communication Interface Digit 32 — Special Options
Digit 33 — Water Flow Control Digit 34 — Chilled Water Reset Digit 35 — Control: Heat
Recovery/Auxiliary Temperature Sensors
Digit 36 — Industrial Chiller Package (INDP)
Digit 37 — Control Pow er Transformer (CPTR)
Digit 38 — Thermal Dispersion Water Flow Proving
Digit 39 — Compressor M otor Frame Size
CCHH Centrifugal Compressor Description
The compressor assembly has a separate model number which is required to identify internal and exter nal compressor parts. The model number begins with “ CCHH” and the nameplate is located on the foot of the volute.
Digit 1, 2 — Unit Function Digit 3 — Drive Digit 4 — Development
Sequence Digit 5, 6, 7 — Nomin al Total
Compressor Tonnage Digit 8 — Compressor M otor
Vol t age Digit 9 — Compressor M otor
Frame Size Digit 10, 11 — Design Sequence Digit 12 — Manufacturing
Location Digit 13, 14, 15, 16 —
Compressor M otor Power (kW) Digit 17, 18, 19, 20 — First Stage
Compressor Impeller (IMPI) Digit 21, 22, 23, 24 — Second
Stage Compressor Impeller (IM P2)
Digit 25, 26, 27, 28 — Third Stage Compressor Impeller (IM P3)
Digit 29 — Motor and Terminal Board Configuration
Digit 30 — Resistent Temperature Detector
10 CVHH-SVX001A-EN
Pre-Installation
ASHRAE Standard 15 Compliance
Trane recommends that indoor CenTraVac unit installations fully meet or exceed the guidelines of the current version of ASHRAE Standard 15, in addition to any applicable national, state, or local requirements. This typically includes:
A refrigerant monitor or detector that is capable of monitoring and alarming within the acceptable exposure level of the refrigerant, and that can actuate mechanical ventilation.
Audible and visual alarms, activated by the refrigerant monitor, inside the equipment room and outside of every entrance.
The equipment room should be properly vented to the outdoors, using mechanical ventilation t hat can be activated by the refrigerant monitor.
The purge discharge and the rupture disk must be properly piped to the outdo ors.
If required by local or other codes, a self-contained breathing apparatus should be available in close proximit y to the equip ment room.
For the USA, refer to the latest copy of ASHRAE Standard 15 for specific guidelines. Trane assumes no responsibility for any economic, health, or environmental issues that may result from an equipment room’s design or function.
Unit Shipment
Inspect u nit while it is still on the truck for an y shipping damage. The chiller ships shrink-wrapped in a 0.254 mm (0.010-in.) recyclable film prot ective covering. Do not remove shrink-wrap for inspection! Inspect for damage to the shrin k-wrap and determine if physical damage has occurred.
Each chiller ships from the factory as a hermetically assembled package; it is factory-assembled, -wired, and
-tested. All openings except for the waterbox vent and
drain holes are covered or plugged to prevent contamination during shipment and h andling.
p. 14
shows an illustration of a typical unit and its components. As soon as the unit arrives at the job site, inspect it thoroughly for damage and material shortages. In addition:
1 . V erify the hermetic integrity of the unit by checking the
chiller pressure for an indication of holding charge pressure.
2. To prevent damaging moisture from entering the unit
and causing corrosion, each chiller is pressurized with
20.7 to 34.5 kPag (3 to 5 psig) of dry nitrogen before shipment.
Figure 3,
Note: The holding charge should register approximately
34.5 kPag (5 psig) at 22.2°C (72°F). P lace a gauge on the access valve provided (indicated by arrow and circle in the preceding figure) on the refrigerant pump discharge line to verify the holding charge. This access valve is located on the front o f the oil tank, which is at the right rear corner of the chiller. If the charge has escaped, contact your local Trane sales office for instructions.
3. The loose parts box and isolator pads ship on top of the control panel box.
4. Check the oil sump sight glasses to verify that the sump was factory-charged with 79.5 L (21 gallons) of oil. The oil level should be vi sible to about halfway in the top sight glass. If no oil level is visible, contact your local Trane sales office.
General Information
Regulations regarding waste handling are constantly changing. T o ensure that personnel are in compliance with the latest federal, state and local regulations, contact your local waste management office for the proper procedures on handling, disposal, transporting and storage of oil, oil filters, refrigerant filters, and filter dryer cores.
Installation Requirements and Contractor Responsibilities
A list of the contractor responsibilities typically associated with the unit installation process is provided.
CVHH-SVX001A-EN 11
Pre-Installation
WARNING
Combustible Material!
F ailur e to follo w this ins truc tion could r esult in death or serious injury or equipment damage. Shrink-w rap is a combustible material. Avoid open flames and hot sparks.
Note: The chiller should remain within its protective
shrink-wrap covering during storage.
Type o f Requirem ent
Found ation • Meet foundation requirem ents Rigging • Safety chains
Disassembly/ Reassembly (as required)
Isolatio n • Isolation pads or spring
Electrical • Circuit breakers or fusible
Water piping • Flow sensing devices
Relief • Rupture disk assembly
Insulation • Insulation (optional) • Insulation
Water Piping Connection Components
Other M aterials • Material and equipment to perform leak testing
Trane S upplied Trane I nstalled
• Trane will per form or have direct on-site supervision of the disassembly and reassembly work (contact your local Trane office for pricing)
disconnects (op tional)
• Unit m ounted starter (optional)
• PFCCs (optional)
• RuptureGuard™ (optional)
Flanged (optional)
• Welded on flange for
2068.4 kPag (300 psig) waterboxes
Trane Supplied Field I nstalled
isolators
• Jumper bars
• Temperature sensor (optional outdoor air)
• Flow switches (m ay be field supplied)
• Remote-mounted starter (optional)
(may be field supplied)
Flanged ( optional)
• Victaulic
®
adapter for 1034 .2 kPag (150 psig) waterboxes
to flang e
Field Supplied Field I nstalled
• Clevis c onnectors
• Lifting beam
• Isolation pads or s pring isolators
• Circuit breakers or fusible disconnects (opti onal)
• Electrical connections to unit m ounted starter (optional)
• Electrical connections to remote mo unted starter (optional)
• Wiring sizes per submittal and NEC or local codes
• PFCCs (rem ote mounted star t er optional only)
• Terminal lugs
• Ground connection(s)
• Jumper bars
• BAS wiring (optional)
• IPC wiring (AFD and remote-m ounted starters only)
• Control voltage wiring (AFD and rem ote- mounted starters only)
• Oil pum p i nter lock wiring (AFD and remote m ounted starters only)
• High con denser pressure interlock wiring (AFD and remote mounted starters only)
• Chilled water pump contactor and wiri ng including interlock
• Condenser water pump contactor and wiring including interlock
• Option relays and wiring
• Taps for flow sensing devices
• Ta ps for therm ometers and gauges
• Thermometers
• Strainers (as required)
• Water flow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain on waterbox valves (one each per pass)
• Pressure relief val ves ( for waterboxes as required)
• Vent line and flex ible conne ctor and vent line from ruptu re disk to atmosphere
• Chiller feet insulation
Victaulic
• Victaulic coupling for 1034.2 kPag ( 150 psig) and
2068.4 kPag (300 psig) waterboxes
• Fasteners for flanged-type connections (optional)
• Dry nitrogen (55.2 kPag [ 8 psig] maximum per machine as needed)
12 CVHH-SVX001A-EN
Pre-Installation
Type o f Requirem ent
“CenTraVac™ Installation Completion Check Sheet and Request for Trane Service”
(CTV-ADF001-EN; refer to
“Forms and Check Sheets,” p. 102
)
Chiller start-up com missionin g
(a) Start- up m ust be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products. Contractor shall
provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the scheduled start-up.
( a)
Trane S upplied Trane I nstalled
• Trane, or an agent of Trane specifically authori zed to perform start-up of Trane pro ducts
®
Trane Supplied Field I nstalled
Field Supplied Field I nstalled
• To be completed by installing contractor prior to contacting Trane for start-up
Storage Requirements
NOTICE:
Ins ulation Damage!
Do not expose unit to direct sunlight as it could result in damage to factory-installed insulation.
Less than 1 m onth 1– 6 months Greater than 6 m onths
Location requirem ents:
• solid foundation
• vibration free
• dry
• temperature range -40°C to 70°C (-40°F to 158°F)
• Do not rem ove any plastic coverings • Do not remove any plastic coverings • Do not remove any plastic coverings
• Do not cha rge the chiller with refrigerant
• If additional refrigerant is on site, follow manufactures storage require m ents
• Verify dry nitrogen pressure using gauge located on the evaporator shell reads
20.7 to 34.5 kPag ( 3 to 5 psig)
• Notify the l ocal Trane office if charge has escaped
• Do not operate purge unit • Do not operate purge unit • Do not operate purge unit
Note: Chillers stored 5 years or longer should be inspected every 5 years by a qualified service organ izat ion for leaks.
(a) If protective plastic coverings need to be removed for access and/or service, contact your local Trane office.
Location requirements :
• solid foundation
• vibration free
• dry
• temperature range -40°C t o 70°C (-40°F to 158°F)
• Do not cha rge the chiller with refrigerant
• If additiona l refrigerant is on site, follow manufactures storage requirements
• Verify dry nitrogen pressure using gauge located on the evaporator shell reads
20.7 to 34.5 kPag ( 3 to 5 psig)
• Notify the local Trane office if ch arge has escaped
• Verify waterbox and tube bundles are clean and dry
Location requ irements:
• solid foundation
• vibration free
• dry
• temperature range -40°C to 70°C (-40°F to 158°F)
• Do not charge the chiller with refrigeran t
• If additiona l refr igerant is on site, follow manufactures storage requirements
• Verify dry nitrogen pressure u sing gauge located on the evaporator shell reads 20.7 to 34.5 kPag (3 to 5 psig)
• Notify the local T rane office if charge has escaped
• Verify waterbo x and tube bundles are clean and dry
• Conduct an oil analysis and verify no oil breakdown
• Repeat yearly
• Replace oil if breakdown has occurred
• If no oil analysis pro gram has been followed, replac e oil prior to start up
(a)
CVHH-SVX001A-EN 13
Pre-Installation
1
2
3
4
0
-
0
6
7
5
9
8
Unit Components
No te: The control p a nel side of the unit is always
designated as the front side of the unit.
Figure 3. Typical Simplex CVHH CenTraVac chiller
1. Suction Elbow
2. Comp ressor
3. Terminal Box
4. Control Panel
5. Condenser
6. Motor Housing
7. Economizer
8. Oil Tank Assembly
9. Purge
10. Evapo rat or
11. Display Panel
14 CVHH-SVX001A-EN
Unit Clearances and Weights
Optional unit mounted starter
Condenser
Evaporator
Econom izer
Motor
B
A
E
Right hand tube pull shown, apply tube pull clearance dimension to left end for left hand tube pull.
These dim ensions per NEC Article 110
46 cm (18 in.)
C
D
92 cm (3 ft)
Recommended Unit Clearances
Adequate clearances around and above the chiller are required to allow sufficient access for service and maintenance operations. Specific unit clearan ce requirements are indicated in the submittal package provided for y our unit.
Do NOT install piping or conduit above the compressor motor assembly or behind the suction elbow of the unit.
Figure 4. Clearance requirements
Minimum vertical clearance above the unit is 92 cm (3 feet).
Use a housekeeping pad to provide bet ter service clearances; refer to submittal for more infor mation.
Per NEC Article 110: Unit mounted starters from 0–600V require a 107 cm (42 inch) clearance, 601–2500V require a 122 cm (48 inch) clearance, and 2501–9000V require a 152 cm (60 inch) clearance. Refer to NEC and local electrical codes for starter and control panel clearance requirements.
CVHH-SVX001A-EN 15
Unit Clearances and Weights
Table 1. Clearance requirements
ABCDE
Shell Combo
100M/ 100M 213 84 422 166 1057 416 30 12 310 122
100M/ 10HM 213 84 422 166 1057 416 79 31 300 118
100L/100L 213 84 422 186 1161 457 30 12 310 122
130M/ 130M 224 88 422 166 1067 420 74 29 277 109
130M/ 13HM 224 88 422 166 1067 420 79 31 312 123
160M/ 200M 244 96 422 166 1087 428 94 37 285 112
160M/ 20HM 244 96 422 166 1087 428 91 36 325 128
200L/200L 272 107 472 186 1217 479 86 34 282 111 200L/20HL 272 107 472 186 1217 479 94 37 333 131 200L/220L 272 107 472 186 1219 480 94 37 305 120 220L/220L 305 120 472 186 1252 493 97 38 300 118 220L/22HL 305 120 472 186 1250 492 107 42 363 143
(a) All dimensions are approximate; refer to the unit submittal package for exact dimensions for your unit .
cm in. cm in. cm in. cm in. cm in.
General Weights
The unit weight information provided in be used f or general information purposes only. Trane does not recommend using this weight information for considerations relative to chiller handling. The large number of variances between chiller selections drives vari ances in chiller weights that are not recognized in this table. For specific we ights for your chiller, refer to your submittal package.
The values in the following:
TECU 0.028-i n. (0.71 mm) tube wall.
1034.2 kPag (150 psig) non-mari ne waterboxes.
Table 2 representing chiller weights include
(a)
Tab le 2 should
Chillers with starter weights i nclude the weight of
the h eaviest possible starter.
Heaviest possible bundle and heaviest possible
motor combination for the application family chiller.
The values in
Table 2 representing chiller weights do NOT
include the following options:
INDP (Industrial Contr ol Panel) option—add 23 kg
(50 lb)
CPTR (Control Panel Transformer) option—add
127 kg (280 lb)
SMP (Supplemental Motor P rotection) option—add
230 kg (500 lb)
Oper atin g weights in clude the largest possible refrigerant charge.
Table 2. Unit weights
Weight w it hout Starters Weight w ith Start ers
Operat ing Shipping Operat ing Shipping
MODEL NTON Hz EVSZ CDSZ kg lb kg lb kg lb kg lb
CVHH 900–1200 60 100M 100M 19748 43538 17218 37959 20044 44190 17514 38611
900–1200 60 100L 100L 20562 45331 17802 39246 20858 45983 18097 39898 900–1200 60 100M 10HM 21946 48382 19226 42386 22241 49034 19522 43038 900–1200 60 130M 130M 22193 48927 19019 41929 22489 49579 19314 42581 900–1200 60 130M 13HM 24873 54836 21522 47447 25169 55488 21817 48099 900–1200 60 160M 200M 25523 56269 21503 47405 25819 56921 21798 48057 900–1200 60 160M 20HM 28516 62868 24353 53690 28812 63520 24649 54342 900–1200 60 200L 220L 28443 62707 23780 52425 28739 63359 24075 53077
900–1200 60 220L 220L 30193 66564 25080 55291 30489 67216 25375 55943 1700–1500 60 200L 200L 27480 60583 23188 51120 27776 61235 23483 51772 1700–1500 60 200L 20HL 30683 67644 26248 57867 30979 68296 26544 58519 1700–1500 60 220L 220L 30588 67434 25474 56161 30883 68086 25770 56813 1700–1500 60 220L 22HL 34497 76053 29234 64451 34793 76705 29530 65103
1550 50 200L 200L 28456 62735 24164 53272 28752 63387 24459 53924 1550 50 200L 20HL 31659 69796 27224 60019 31955 70448 27520 60671 1550 50 220L 220L 31564 69586 26450 58313 31859 70238 26746 58965 1550 50 220L 22HL 35473 78205 30211 66603 35769 78857 30506 67255
16 CVHH-SVX001A-EN
Installation: Mechanical
Operating Environment
Important:
The stan dard chille r is designed for indoor use only
and as such has NEMA Type 1 or IP 20 enclosures.
For chillers in unheated equipment rooms, contact your local Trane service agency for methods to ensure that the oil temperature is maintained suitable for proper operation of the chiller.
T o ensure that electrical components operate properly, do not locate the chiller in an area exposed to dust, dirt, corrosive fumes, or excessive heat and humidity. The ambient temperature range for chiller operation is 1.1°C to 40°C (34°F to 104°F).
NOTICE:
E quipment Failure!
Unit operating at ambient temperatures exceeding 40°C (104°F) could result in starter component damage due to the panel’s inabili ty to dissipate heat adequately . If any of these adverse operating conditions are present, take necessary action to improve the equipment room environment.
Foundation Requirements
Chiller mounting surface must be:
rigid non-warping mounting pads or a concrete
foundation.
able to support the chiller at its full operating weight
(including completed piping, and full operating charges of refrigerant, oil and water.)
F or proper unit operation, the chiller must be level within
1.6 mm (1/16 in.) over its length and width when set into
place on the mounting surface. approximate weights for various chiller sizes and options.
Note: For specific weigh t information, refer to the unit
submittal package.
Important: Tran e will not assume responsibility for
equipment problems resulting from an improperly designed or constructed fou ndation.
Table 2, p . 16 shows
Rigging
Lifting is the recommended method for moving chillers. Suggested lifting arrangements for standard units are described in
Note: The lifting beam used for Simplex units must be at
“ Standard Chiller Lift,” p. 17.
least 4.572 meters (15 feet) long.
WARNING
Heavy Objects!
Failure to properly lift unit could result in death or serious injury, or equipment or property-only damage. Do not use cables (chains or slings) except as s hown in
Figure 5, p. 18. Each of the cables (chains or slings)
used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) m ay not be of the same length. Adjust as necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit could result in death or serious injury, or equipment or property-only damage.
T es t lift unit approximately 61 c m (24 inches ) to verify proper center of gravity lift point. T o a v oi d dropping of unit, reposition lifting point if unit is not level.
Do not lift chiller utilizing waterbox lifting lug. Waterbox lifting lug is to be used only f o r removing waterbox from chiller.
Do not lift chiller utilizing elbow lifting tab. Elbow lifting tab and approved clevis are used when removing elbow from chiller.
NOTICE:
W iring Damage!
Damage to unit wiring could result in equipment failure. Care must be t aken during rigging, assembly and disassembly to avoid damaging unit wiring.
Standard Chiller Lift
1. Insert clevis connections at the points indicated in
Figure 5, p. 18. A 63.5 mm (2.5 in.) diameter lifting hole
is provided at each of these points.
2. Attach the lifting chains or cables.
3. Once the lifting cables are in place, attach a safety chain or cable between the first-stage casing of the compressor and the lifting beam.
Important: There should not be tension on this safety
cable; the cable is used only to prevent the unit from rolling during th e lift.
4. Position isolator pads or spring isolators beneath the chiller feet (refer to instructions).
Note: Follow instructions provided by the spring
isolator man ufacturer, being careful to not damage isolator adjustment bo lt.
“ Unit Isolation,” p. 19 for
CVHH-SVX001A-EN 17
Installation: Mechanical
Safety chain or cable
Jack slots
4.572 meters (15 feet) minimum effective length
5. Once the isolators are in place, lower the chiller— working from end to end—in small increments to mai ntain stability.
6. When lift is complete, detach the clevis co nnection s and safety chain.
Figure 5. Typical rigging arrangements for Simplex
units
Spec ial Lift Requirements
NOTICE:
Oil Loss!
F ailure to prevent oil migration out of the oil tank could res ult in equipment failure or proper ty-only damage. To prevent oil migration out of the oil tank during lifting procedures, remove the oil from the oil tank if the unit will be lifted at any angle greater than 15° from horizontal end-to-end. If oil is allowed to run out of the oil tank into other areas of the chiller, it will be extremely difficult to return the oil to the oil tank even during operation.
NOTICE:
Equipment Damage!
Moving the chiller using a fork lift could result in equipment or property-only damage. Do not use a fork lift to move the chiller!
NOTICE:
Compressor Alig nment!
Failure to preserve compressor alignment could result in equipment or property-only damage. Lifting the compressor/motor assembly from the shells without factory-installed doweling in the compressor casting flanges could result in misalignment of the compres sor castings.
If the chiller cannot be moved using a standard chiller lift, consider the following:
When job site conditions require rigging of the chiller at an angle greater than 45° from horizontal (end-to­end), the unit may require removal of the compressor. Contact Trane or an agent of Trane specifica lly authorized to perform start-up and warranty of T rane products reg arding the disassembly and reassembly work. For more information, refer to
Information,” p. 4
Note: Disassembly and reassembly work includes
dowel-pinning the compressor and removing it from the unit. Contact Trane or an agent of Trane specifically authorized to perform start­up and warranty of T rane rigging instructions. Do NOT attempt to rotate the chiller onto its side.
When lifti ng the chiller is either i mpractical o r undesirable, attach cables or chains to the jacking slots shown in across a smooth surface. Should the chiller be on a shippin g skid, it is not necessary to remove the skid from the chiller before moving it into place.
If removal of the compressor or economizer assembly is necessary to move the chiller to the operating
Figure 5, p. 18; th en push or pull the unit
.
“ Factory Warranty
®
products for specific
®
18 CVHH-SVX001A-EN
Installation: Mechanical
228.6 mm (9 in.)
457.2 mm (18 in.)
9.525 mm (3/ 8 in.)
Condenser
Evaporator
Length
2
5
1
4
6
3
Width
I solator Configuration 1
Origin: Right front corner of evap right front foot
Condenser
Evaporator
Length
2
5
1
4
6
3
Evap Width
Width
I solator Configuration 2
location, contact T rane. F or more information, refer to
“ Factory Warranty Information,” p. 4.
Unit Isolation
T o minimize sound and vibration transmission through the bui lding structure, and to ensure proper weigh t distribution over the mount ing surface, always install isolation pads or spring is olators under the chiller feet.
No te: Isolation pads (see
Figure 6) are provided with each
chiller unless spring isolators are specified on the sales order.
Specific isolator loading da ta is provided in the unit submittal package. If necessary, contact your local Trane sales office for further information.
Important: When determining placement of isolation
pads or spring isolators, remember that the control panel side of the unit is always desig nated as the uni t front.
Isolation Pads
When the unit is ready for final placement, position isolation pads (457.2-mm sides) end for end under the full length of the chiller leg. The pads measure 228.6 mm x
457.2 mm (9 in. × 18 in.) and on some units there may be small gaps between pads. Pads are provided to cover entire foot.
Figure 6. Is olation pad and dimensions
Remember that the chiller must be level within 1.6 mm (1/16 in.) over its length and width after it is lowered onto the isolation pads. In addition, all piping connected to the chiller must be properly isolated and supported so that it does not place any stress on the unit.
Spring Isolators
Spring isolators should be considered whenever chiller
installation is planned for an upper story location. Base isolator placement is shown in
Table 3.
CVHH-SVX001A-EN 19
Figure 7; also refer to
Figure 7. Isolation spring placement by shell size,
evaporator and condenser lengt h
Table 3. Isolation spring placement, cm (in.)
Origin
to
to
Center
of
Middle
Pad
153.7
(60.5)
171.5
(67.5)
153.7
(60.5)
171.5
(67.5)
138.4
(54.5)
153.7
(60.5)
138.4
(54.5)
N/A
N/A
N/A
N/A
N/A
EVSZ CDSZ W idt h
200L 200L
220L 220L
200L 20HL
220L 22HL
160M 20HM
200L 220L
160M 200M
100M 100M
100L 100L
130M 130M
100M 10HM
130M 13HM
285.0
(112.2)
303.3
(119.4)
336.0
(132.3)
361.0
(142.5)
323.3
(127.3)
285.2
(112.3)
270.3
(106.4)
264.4
(104.1)
264.4
(104.1)
277.6
(109.3)
300.2
(118.2)
313.4
(123.4)
Evap
Width Length
170.2
457.2
(67)
(180)
188.0
457.2
(74)
(180)
170.2
457.2
(67)
(180)
188.0
457.2
(74)
(180)
154.9
406.4
(61)
(160)
170.2
457.2
(67)
(180)
154.9
406.4
(61)
(160)
406.4
N/A
(160)
457.2
N/A
(180)
406.4
N/A
(160)
406.4
N/A
(160)
406.4
N/A
(160)
I solator
Config
2
2
2
2
2
2
2
1
1
1
1
1
Origin
Center
of Rear
Pad
268.5
(105.7)
286.8
(112.9)
319.5
(125.8)
345.4 (136)
306.8
(120.8)
268.7
(105.8)
253.7
(99.9)
247.9
(97.6)
247.9
(97.6)
261.1
(102.8)
283.7
(111.7)
296.9
(116.9)
Spring isolators typically ship assembled and ready for installat ion. To install and adjust the isolators properly, follow the instructions given.
Installation: Mechanical
Side View of Unit End View of Unit
Outside edge of tube sheet
Center tube sheet support leg
Center of isolator spring
Note: The spring isolator must be cent ered
in relation to the tube sheet. Do not align the isolator with the flat part of the chiller foot since the tube sheet is often off center
Note: The length of the
isolator should be parallel to the leg.
Note: Do not adjust the isolators until the chiller is piped
and charged with refrigerant and water.
1 . Position the spring isolators under the chiller as shown
in
Figure 7. Ensure that each isolator is centered in
relation to the tube sheet.
No te: Spring isolators shipped with the chiller may
not be identical. Compare the data provided in the unit submittal package to determine proper isolator placement.
2. Set the isolators on the sub-base; shim as necessary to provide a flat, level surface at the same elevation for the end supports.
Important: Support the full underside of the isolator
base plate; do NOT straddle gaps or small shims.
3. If required, bolt the isolators to the floor through the slots provided, or cement the pads.
Note: Fastening the isolators to the floor is not
necessary unless specified.
4. If the chiller must be fastened to the isolators, insert capscrews through the chiller base and into holes drilled and tapped in the upper housing o f each isolator.
Important: Do NOT allow the screws to protrude below
the underside of the isolator upper housing, or interfere with the adjusting bolts. An alternative method of fasteni ng the chiller to the isolators is to ceme nt the neoprene pads.
5. Set the chiller on the isolat ors; refer to
Chiller Lift,” p. 17
. The we ight of the chiller will force down the upper housing of each isolator, and could cause it to rest on the isolator’s lower housing (refer to
Figure 8).
“ Standard
.
Figure 8. Chiller foot and isolator orientation
6. Check the clearance on each isolator. If this dimension is less than 6.35 mm (1/4 in.) on an y iso lator , use a wrench to turn the adjusting bolt one complete revolution upward.
Note: When the load is applied to the isolators (
Step 5),
the top plate of each isola tor moves down to compress the springs until either the springs support the load or the top plate rests on the botto m housing of the isolator. If the springs are supporting the load, screwing down on the adjusting bolt (
Step 7) will raise the chiller.
7. Turn the adjusting bolt on each of th e remaining isolators to obtain the required minimum clearance of
6.35 mm (1/4 in.).
8. Once the minimum required clearance is obtained on each of the isolators, level the chil ler by turning the adjusting bolt on each of the isolators on the low side of the unit. Work from one isol ator to the next.
Important: The chiller must be level to within 1.6mm (1/
16 in.) over its length and width, and the clearance of each isolator must be at least
6.35 mm (1/4 in.).
Leveling the Unit
20 CVHH-SVX001A-EN
The chiller must be set level within 1.6 mm (1/16 in.). 1 . Measure and make a punch mark an equal distance up
from the bottom of each foot of the chiller.
Installation: Mechanical
2
1
2. Suspend a clear plastic tube along the length of the chiller as shown in the following figure.
3. Fill the tube with water u ntil the level aligns with the punch mark at one end of the chiller.
4. Check the water level at the opposite mark. If the water level does not align with the punch mark, use full
Figure 9.
Note: Use of a laser level is an acceptable alternative
method to level the unit.
Important: Immediately report any unit damage
incu rr ed during handling or installation at the job site to the Trane sales office.
length shims to raise one end of the chiller until the water level at each end of the tube aligns with the punch mar ks at both ends of the chiller.
5. Once the unit is level across its length, repeat through
Step 3 to level the unit across its width.
Step 1
CVHH-SVX001A-EN 21
Installation: Water Piping
Overview
The following water piping circuits must be installed and connected to the chiller:
Pipe the evaporato r in to the chilled water circuit.
Pipe the condenser into the cooling tower water circuit.
Optional: A heat-recovery condenser water circuit.
Optional: An auxiliary condenser water circuit.
No te: Piping must be arranged and supported to avoid
stress on the equipment. It is strongly recommended that the piping contractor does not run pipe closer than 0.91 m (3 feet) minimum to the equipment. This will allow for proper fit upon arrival of the unit at the job site. Any adjustment that is necessary can be made to the piping at that time. Expenses that result from a failure to follow this recommendation will not be pai d by Trane.
Piping suggestions for each of the water circuits listed above are ou tli ned in
Piping,” p. 25
installation of field supplied piping compon ents (e.g., valves, flow switches, etc.) common to most chiller water circuits are listed below.
. General recommendations for the
“ Evaporator and Condenser Water
Water Treatment
The use of untreated or improperly treated water in a CenT raVac may result in inefficient operation and possible tube damage.
Important: Trane strongly recommends using the
services of a qualified water treatment specialist to determine necessary water treatment. A lab el with a customer disclaimer note is affixed to each unit.
NOTICE:
P roper Water Treatment!
Trane assumes no responsibility for equipment failures which result from untreated or improper l y treated water, or saline or brackish water. The use of untreated or improperly treated water in a CenTraVac could result in scaling, erosi on , corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required.
Pressure Gauges
Valves—Drains and Vents
NOTICE:
W aterbox Damage!
Failure to follow instructions could res ul t in damage to the waterbox. Do not over-tighten or use excessive Tef lon® pipe tape when installing valves, drains, plugs and vents on waterboxes.
1 . Install field-supplied air vents and drain valves on the
waterboxes. Eac h waterbox is provided with a National Pipe Thread Female (NPTF ) vent and drain connection; the openi ngs are 19.05 mm (3/4 i n.).
NOTICE:
Over-pressurization!
Failure to install pressure-relief valv es in the condenser and evapora tor water circuits could result in waterbox damage due to hydrostatic expansion.
2. If necessary for the application, install pressure-relief valves at the drain connections on the evaporator and condenser waterboxes. To do so, add a tee with the relief valve attached to the drain valve. Fol low local codes for determining if drai n connection is large enough for relief devices.
T o determine whether or not pressure relief valves are needed for a specific application, keep in mind that:
a. Vessels with close-coupled shutoff valves may
cause high potentially damaging hydrostatic pressures as fluid temperature r ises.
b. Relief valves are required by American Society o f
Mechanical Engineers (A SME) codes when the waterside is ASME. Follow ASME guidelines or other applicable codes/local regulation to ensure proper relief valve installation.
Strainers
NOTICE:
Tube Damage!
Failure to install strainers in all water piping entering the chiller could result in tube plugging conditions that damage unit components.
Locate pressure gauge taps in a straight length of pi pe. Place each tap a minimum of one pipe diameter downstream of any elbow, orifice, etc. F or example, for a
152.4 mm (6 in.) pipe, the tap would be at least 152.4 mm (6 in.) from any elbow, orifice , etc.
22 CVHH-SVX001A-EN
Install a strainer in the entering side of each piping circuit to av oid possible tube plugging in the chiller with debris.
Required Flow-Sensing Devices
The ifm efector® flow detection controller and sensor (see
“ Water Flow Detection Controller and Sensor—ifm
Installation: Water Piping
Components:
A. E40174 – 1/2" NPT adapter (for ow probe)
B . SF6200 – Flow probe
C . SN0150 – Flow control monitor
D. E70231 – Combicon connectors (quantity 5)
E . E10965 – Micro DC cable, 10m length, PUR jacket
F. F53003 – Din rail, 40mm length
Output to
control cabinet
Jumper
N
L
AC
Jumper
monitoring
rated using
monitoring
rail (F) into control cabinet.
in combicon connectors (D) according to
4
3
2
1
If factory-provided, located in control panel.
efector,” p. 23) are used to verify evap orat or and
condenser water flows. If a customer-suppl ied flow sensing device is used to
ensure adequate chiller protection, refer to the wiring diagrams that shipped with the unit for specific electrical connections.
Be sure to follow the manufacturer’s recommendations for device selection and installation.
Water Flow Detection Controller and Sensor—ifm efector
Figure 10. Installation of ifm efec tor flow detection
controller and sensor
2. Insert the flo w probe through the 1/2-in. NPT adapter as near the center of the pipe as p ossible (see item labeled “ 2” in
Figure 10, p. 23). Finger-tighten the
1/2-in. NPT adapter; then, tighten with a wrench an additional 1-1/4 turns.
Note: When installed, the tip of the ifm efector sensor
probe must be at least 2.54 cm (1 in.) away from any pipe wall. Placing the tip of the probe at the center of the pipe is preferred.
3. Install the Micro DC Cable by inserting it through the wire openings on the back side of the control panel (see item labeled “ 3” in
Figure 10, p. 23). Install the
supplied Micro DC C able (9 meters [25 feet] in length) to the Flow Probe and hand-tighten the connector nut.
4. Plug the other end of the Micro DC C able into the Flow Control Monitor with the Combicon connector (see item labeled “ 4” in
Figure 10, p. 23). R efer to Figure 11
for cable wiring.
1. Mount the 1/2-in. NPT adapter in a horizonta l or vertical section of pipe. The maximum distance from the control panel must not exceed 8.99 meters (29.5 ft) (see item labeled “ 1” in five pipe diameters straight run of pipe upstream of the sensor location, and three pipe diameters straight run of pipe downstream of the sensor location.
No te: In the case of a horizontal pipe, mounting the
CVHH-SVX001A-EN 23
Figure 10, p. 23). Allow at least
sensor in the side of the pipe is preferred. In the case of a vertical pipe, mounting the sensor in a place where the water flows upwards is preferred.
Installation: Water Piping
X39003892001A
7
NOTICE:
Do Not Apply Elec tric al Power to a Unit in a Vacuum!
Failure to disconnect power to units with inside-the-delta solid state starters during evacuation or when the unit is in a deep vacuum could cause compressor motor damage. Applying electrical power to a motor in a vacuum could cause damage to the motor. In addition, on units with inside-the-delta solid state starters, all power to the unit must be disconnected prior to evacuating the unit as line power is directly applied to the motor terminals 4, 5, and 6.
flow setting cutout and adjusting counterclockwise (-) increases the flow setting cutout.
Note: The “ Temp” potentiometer on the ifm efector
control module has no effect in Trane application. It is not necessary to make adjustments to the “ Temp” potentiometer.
8. Once the cutout setting is adjusted, the cutout setpoint will be indicated with a yellow light on the Flow Control Monitor LED bar graph display. When the water flows are higher than the cutout, a green light will indicate proper flow status. If the flows fall below the cutout setpoint, a red light will indicat e low/no flow status.
Figure 11. ifm efector flow sensing device terminal
connection
NOTICE:
Proof of Flow Switch!
Evaporator and condenser water circuits require proof of flow switches.
Failure to include the proof of flow devices and/or jumping out these devices could cause the unit to stop on a secondary level of protection.
Note: Graphic lab els (sho wn above) are used for CE
application onl y .
Important:
Before servicing, disconnect all power sources and
allow at least 30 minutes for capacitors to discharg e.
All electrical enclosures—unit or remote—are IP2X.
5. Apply power to the chiller control panel to verify the Flow Control Monitor has power and the Low Volt Broken Wire Re lay light is not lit .
6. Remove all air from the piping circuit prior to adjusting the low water flow setpoint.
7. Reduce the water flow to the minimum allowable flow and adjust the Flow setting on the Flow Control Monitor (see item labeled “ 7” in the “ Flow” potentiometer clockw ise (+) reduces the
Figure 11). Adjusting
Frequent cycling on these higher level diagnostic devices could c ause excessive thermal and pressure cycling of unit components (O-rings, gaskets, sensors, motors, controls, etc.) and/or freeze damage, resulting in premature failure of the chiller.
Failure to provide flow switches or jumping-out of switches could result in severe equipment damage.
Evaporator and condenser proof of flow switches are required. These switches are u sed with control logic to confirm flow prior to starting a unit and to stop a running unit if flow is lost. For trouble shooting, a viewable diagnostic is generated if a proof of flow switch does not close when flow is required.
24 CVHH-SVX001A-EN
Installation: Water Piping
44
445
5
3
3
7
2
21
9
6
2
2
8
Ou tlet
Inlet
1
2
3
45678
9
2
34
445
2
2
10
Outlet
Inlet
Evaporator and Condenser Water Piping
Figure 12 and Figure 13, p. 25 illustrate the recommended
(typical) water piping arr angements for the evaporator and condenser.
Figure 12. Typical evaporator water piping circuit
1. Balancing Valve
2. Gate (Iso lation) Valv e or Ball Valve
3. Thermometer (if field supplied)
4. Waterbox Nozzle Connection
5. Drain, Vent, Anode
(a) Flow switch 4B4 may be installed in either the entering or leaving leg
of the chilled wat er circuit.
(b) It is recom mended to pipe the gauge between entering and leavin g
pipes. A shutoff valve on each side of the gauge allows the operator to read either entering or leaving water pressure.
Figure 13. Typical c o nd en ser water piping circuits
1. Balancing Valve
2. Gate (Iso lation) Valv e or Ball Valve
3. Thermometer (if field supplied)
4. Waterbox Nozzle Connection
5. Drain, Vent, Anode
Notes: 1 . Som e type of field-supplied temperature control device may be
required to regulate the temperat ure of the heat-recovery condenser water circuit . For application recom mendations, refer to Heat Recovery Sem inar ( Part 2): "Systems/Equipm ent (AM- FND-8).
2 . Install a bypass valve system to avoid circulating water through the
auxiliary shell when the unit is shut down.
3 . On m ultiple pass condensers, entering condenser water must ent er at
the lowest nozzle.
(a) Flow switch 4B5 may be installed in either the entering or leaving leg
of the water circuit.
(b) It is recomm ended to pipe a single gauge bet ween entering and leaving
pipes.
CVHH-SVX001A-EN 25
6. Strainer
7. Chilled Water Flow Switch
8. P ump
9. Pressure Gauge
6. Strainer
7. Condenser Water Flow Switch (4B5)
8. 3-Way Valve (Optional)
9. Condenser Water Pump
10. Pressur e Gauge
(4B4)
Piping must be arranged and supported to avoid stress on the equipment. It is strongly recommended that the piping contractor does not run pipe closer than 0.91 meters (3 feet) minimum to the equipment. This will allow for proper fit upon arrival of the unit at t he jo b site. Any adjustment that is necessary can be made to the piping at that time. Expenses that result from a failure to follow this recommendation will not be paid b y Trane.
Water piping connection sizes and components are identified in
Table 4, p . 26 and Table 5, p. 27. Remember
that with many waterboxes the entering and leaving evaporator water can be piped to either waterbox connection when the tube bundles are split vertically. However, large evaporator waterboxes, with entering and leaving connections not at the same level, must be connected with the entering water at the bottom and the leaving water at the top.
Waterboxes with multip le pass arrangements uti lize a baffle to separate the passes. These baffles are designed for a maximum pressure of 137.9 kPad (20 psid). If larger pressure drops are expected in the application, contact
(a)
(b)
your local Trane repr esentative to discuss special waterbox options.
Impor tant: Water flows must be pi ped i n accordance
with nameplate designation.
Field-provided isolation valves for the evaporator and condenser water lines should be installed upstream and downstream of the heat exchangers, and be installed far enough away from the chiller to also provide practical service isol ation for flow sensing devices, field thermometers, flexible connectors, and any removable pipe spools.
Ensure that the evaporator water piping is clear, check it after the chilled water pump is operated but before initial chiller start-up. If any partial blockages exist, they can be detected and removed to prevent possible tube damage resulting from evaporator freeze-up or erosion.
For condenser and large evaporator connections, arrange the water piping so that the water supply enters the shell at the lower connection, and exits from the top connection. Operation al problems may result if this piping is n ot correct. Some shells may be piped as desired since both connections are at the same level.
(a)
For applications th at include an “ infinite source” or “ multiple-use”, cooling condenser water supply, install a valved bypass “ leg” (optional) between the supply and
(b)
return pi pes. This valved bypass allows the operator to short-cir cuit water flow through the cooling condenser when the supply water temperature is too low.
Note: System refrig erant pressure differential must be
maintained ab ove 20.7 kPad (3 psid) at all times. Fa ilure to do so could result in operating problems.
Installation: Water Piping
Water Piping Connections
All standard units use grooved-pipe connections. These are grooved-end NSP (Victaulic style) pipe connections. Flanged connections are optional.
Piping joined using grooved type couplings, like all types of piping systems, requires proper support to carry the weight of pipes and equipmen t. The support methods used must eliminate undue stresses on joints, piping and other components; allow movement where required, and provide for any other special requirements (i.e., drainage, etc.).
Note: Plug-type sensor extension cables are available for
purchase from Trane P arts Service if needed. These sensor extension cables may be necessary if the waterboxes are changed or if the temperature sensors are moved out into the unit pip ing for better mixed temperature readings.
Table 4. Water connection pipe sizes
Wat er
Passes
Evaporator Metri c Pipe Size ( m m )
1 Pass DN3 00 DN300 DN350 DN400 DN500 DN400 DN500 2 Pass DN250 DN250 DN300 DN350 DN350 — 3 Pass DN200 DN200 DN250 DN300 DN300
Condenser
1 Pass DN300 DN350 DN400 DN600 DN600 2 Pass DN250 DN300 DN350 DN350
Evaporator Nom inal Pipe Size ( in.)
1 Pass 12 12 14 16 20 16 20 2 Pass 10 10 12 14 14 — 3 Pass 8 8 10 12 12
Condenser
1 Pass 12 14 16 24 24 2 Pass 10 12 14 14
10 0 13 0 160 20 0 220 40 0 4 4 0
Shell Size
Figure 14. Typical grooved pipe connection
Waterbox L ocations
26 CVHH-SVX001A-EN
NOTICE:
Do Not Exchange Positions of Heat Recovery Waterboxes!
Failure to follow this instruction could prevent proper unit operation. Contact CenTraVac Technical Service for switching of heat recovery waterboxes.
If necessary, the non-marine-style waterboxes on each shell whether evaporator o r condenser can be switched end-fo r-end to obtain the desired piping arrangement.
If removal of waterboxes is necessary, refer to
Removal and Installation,” p. 98
.
If the waterboxes on any of the shells are exchanged end­for-end, be sure to reinstall them right side up to maintain the correct baffle arrangements. Use a new gasket with each waterbox cover.
“ Waterbox
Installation: Water Piping
Water Box
Flange Adaptor Trane Provided
Flanged
Wat erbox
Flange Adaptor Tra n e prov ided
Water Box
Style 77 Flexible
Customer Provided
Customer
Victaulic
Wat erbox
Style 77 Flexible
Customer provided
Customer
Three-pass waterboxes have lifting lugs on the top and bottom. When reinstalling, ensure that the waterbox is oriented the same way it as removed.
Grooved Pipe Coupling
A customer-supplied, standard flexible groo ved pipe coupling (Victaulic Style 77 or equivalent) should be used to complete the Victaulic connection for both 1034.2 kPag or 150 psig and 2068.4 kPag or 300 psig waterboxes.
When a flexible coupling such as this is installed at the waterbox connections, other flexible piping connectors (i.e., braided-steel, elastomeric arch, etc.) are usually not required to attenuate vibration and/or prevent stress on the connections.
Table 5. Water piping connection components
Custom er Piping Connection
Unit Model
CVHH
CVHH Victaulic (All others)
Figure 15. Customer piping connection types
Refer to the coupling manufacturer’s guidelines for specific information concerning proper piping system design and construction methods for grooved water piping systems.
Flexible coupling gaskets require proper lubrication before installation to provide a good seal. Refer to the coupling manufacturer’s guidelines for proper lubricant type and application.
Flange-Connection Adapters
When flat-face flange connections are specified, flange-to­groove adapters are provided (Victaulic Style 741 for
1034.2 kPag or 150 psig systems; Style 743 for 2068.4 kPag
or 300 psig systems). The adapters are shipped bolted to one of the chi ller end-supports. A dapter descripti ons are
Unit Connection
Type Victaulic Flanged
Flanged (Condenser
032–050 150 psig
[103 4.2 kPag] non-
marine only)
Customer
provided
Victaulic coupling
No adapter
required
Trane provided
Victaulic-to-
flang e adapter
given in
Table 6, p . 28 and Table 7, p. 28. The flange
adapters provide a direct, rigid connection of flanged components to the grooved-pipe chiller waterbox connections.
Figure 16. Typical shipping location for flange
In this case, the use of flexible type connecto rs (i.e., braided steel, elastomeric arch, etc.) are recommended to attenuate vibration and prevent stress at the waterbox connections. Flange adapter s are no t provided for CVHH units with 2068.4 kPa or 300 psig waterboxes that hav e 356 mm (14 in.) and larger piping connections.
All flange-to-flange assembly bolts must be provided by the installer. Bolt sizes and number required are given in
Table 6, p. 28 and Table 7, p. 28. The four draw-bolts
needed for the 355.6 mm (14 in.) and larger Style 741 (1034.2 kPag or 150 psig) adapters are provided. The Style 741, 1034.2 kPag or 150 psig flange adapter requires a smooth, hard surface for a good seal.
Connection to other type flange faces (i.e., raised, serrated, rubber, etc.) will require the use of a flange washer between the faces. Refer to the flange adapter manufacturer’s guidelines for specific information.
The Style 743 (2068.4 kPa or 300 psig) flange adapters are designed to mate with raised-face flanges. They can be used with flat-faced flanges; however, only if t he raised projections on the outside face of the adapter are removed; see
Figure 17. The flange-adapter gasket must
be placed with the color-coded lip on the pipe and the other lip facing the mating flange.
NOTICE:
Piping Connection Leaks!
Failure to provide effective seal could result in equipment or property-only damage. To provide effective s eal, gasket contact surfaces of adapter must be free of gouges, undulations or deformities.
CVHH-SVX001A-EN 27
Installation: Water Piping
Remove to mate to flat-faced flanges
Figure 17. Modifying 300 psig or 21 bar flange adaptors
Figure 18. Typical Victaulic flange gasket configuration
for flat-faced flange application
3. Align and bring two pipe ends together and slide
Victaulic Gasket Installation
gasket into position centered between the grooves on each pipe. No portion of the gasket should extend into
1. Inspect supplied gasket to b e cert ain it is suited for intended service (code identifies gasket grade). Apply a thin coat of silicone lubricant to gasket tips and outside of gasket.
2. Install gasket, placing gasket over pipe end and making sure gasket lip does not overh ang pipe end. Refer to
Figure 18 f or gasket configuration.
the groove on either pipe.
4. Open fully and place hinged Victaulic flange around the grooved pipe end with the circular key section locating into the groove.
5. Insert a standard bolt through the mating holes of the Victaulic flange to secure the flange firmly i n the groove.
6. Tighten fasteners alternately and equally until housing bolt pads are firmly together (metal to metal); refer to
“ Bolt-Tightening Sequence for Water Piping Connections,” p. 29
. Do not excessivel y tighten
fasteners.
Note: Uneven tightening may cause gasket to pinch.
Table 6. Installation data for 150 psig flange adapters (Style 741)
Nominal Pipe Size
As sem bly Bolt
mm in. in. mm in. kg lb
200 8 3/ 4 x 3-1/2 8 298 11.75 7.5 16.6 250 10 7/8 x 4 12 362 14.25 11 24.2 300 12 7/8 x 4 12 432 17 21.2 46.8 350 14 1 x 4-1/ 2 12 476 18.75 28.1 62 400 16 1 x 4-1/ 2 16 540 21.25 35.8 79 450 18 1-1/ 8 x 4-3/ 4 16 578 22.75 37.3 82.3 500 20 1-1/ 8 x 5-1/ 4 20 635 25 46.9 103.3 600 24 1-1/ 4 x 5-3/ 4 20 749 29.5 64.4 142
(a) Bolt size for conventional flange to flange connect ion. Longer bolts are required when flange washer m ust be used.
Size
( a )
Number of
Assem bly Bolts
Required
Bolt Pattern Diam eter Weight
Table 7. Installation data for 350 psig flange adapters (Style 743)
Nominal Pipe Size
mm in. in. mm in. kg lb
219.1 8 3/ 4 x 4-3/ 4 12 330 13 15.6 34.3
273.0 10 1 x 5-1/ 4 16 387 15.25 21.9 48.3
323.9 12 1-1/ 8 x 5-3/ 4 16 451 17.75 32. 0 70.5
(a) Bolt size for conventional flange to flange connect ion. Longer bolts are required when flange washer m ust be used.
Assem bly Bolt
Size
( a)
Number of
As sem bly Bolts
Required
Bolt Pattern Diam eter Weight
28 CVHH-SVX001A-EN
Bolt-Tightening Sequence for
1
3
45
7
8
26
8 bolt flange
1
3
4
10 11
9
5
7
8
12
26
12 bolt flange
1
1
5
5
9
9
20
22
3
3
4
4
66
7
7
8
8
10
10
19
18
17
16
16
15
15
14
14
13
13
12
12
11
11
16 bolt flan ge 20 bolt flan ge
Water Piping Connections
This section describes a bolt-tightening sequence for flanges with flat gaskets or O-rings. Remember that improperly tightened flanges may leak.
No te: Before tightening any of the bolts, align the flanges.
Flanges with 8 or 12 Bolts
Tighten all bolts to a snug tightness, following the numerical sequence for the appropriate bolt pattern as shown below. Repeat this sequence to apply the final torque to each bolt.
Installation: Water Piping
Flanges with 16 or 20 Bolts
Tighten only the first half of the total number of bolts to a snug tightness, following the numerical sequence for the appr opriate bolt pattern as shown below. Nex t, sequentially tighten the remaining half of the bolts in numerical order.
Pressure Testing Waterside Piping
NOTICE:
E quipment Damage!
Failure to follow these instructions could result in equipment damage. Do not over pressurize the system or exceed design pressure. Always perform as a hydro
pressure test with water present in piping and waterboxes.
Waterside design pressure is either 1034.2 or 2068.4 kP ag (150 or 300 psig); refer to unit nameplate or to submittal documentation.
CVHH-SVX001A-EN 29
Vent Piping
Refrigerant Vent Line
General Requirements
State and local codes, and ASHRAE Standard 15 contain requirements for venting the relief device on the chiller to the atmosphere outside of the building. These requirements include, but are not limited to, permitted mat erials, sizing, and pro per termination.
No te: The following information is a general outline of
vent-line installation requirements based on ASHRAE Standard 15. Most codes contain similar requirements but may vary in some significant areas. The i nstaller must check state and local codes and follow the specific requirements applicable to the location.
Purge Discharge
To comply with ASHRAE Standard 15, the discharge piping from purge units that remove noncondensible gas from refrigerating systems must conform to the ASHRAE Standard 15 requirements for relief piping. To h elp meet this requirement, the purge discharge is factory-piped to the relief device assembly.
Vent Line Materials
All materials in the relief device vent system must be compatible with the refrigerant in use. Commonly used and accepted p iping materials include steel and DWV (drain/ waste/vent) copper. Consult local codes for restrictions on materials. Consult with the manufacturers of any field-provided components or materials for acceptable material compatibility.
No te: PVC piping is acceptable for use as a v ent line
material with R-1233 the sections of plastic pipe may not be. When considering a v ent system constructed of plastic piping, such as PVC, ensure that both the pipe material and the adhesive have been tested for refrigerant compatibility. In addition, verify that the local codes permit PVC for refrigerant vent lines; even though ASHRAE Standard 15 doesn’t prohibit its use, some local codes do.
The following materials for PVC pipe construction are recommended for use with R-1233
Primer/Cleaner:
Hercules—PVC Primer #60-465
RECTORSEAL
Adhesives:
Hercules—Clear PVC, Medium Body/Medium Set, #60-020
RECTORSEAL—PVC Cement, Gene™ 404L
®
PV C Cleaner—Sam™ CL-3L
(E), but the glue that joins
zd
(E):
zd
Vent Line Sizing
Vent line size must conform to lo cal codes and requirements. In most cases, local codes are based on ASHRAE Standard 15. ASHRAE Standard 15 provides specific requirements for the discharge piping that allows pressure-relief devices to safely vent refrigerant to the atmosphere if over pressurization occurs. In part, the standard mandates that:
The minimum pipe size of the vent line must equal the size of the discharge connection on the pressure-relief device. A larger vent line size may be necessary, depending on the length of the run.
T wo or more relief devices can be piped together only if the vent line is sized to handle all devices that could relieve at the same time.
When two or more relief devices share a common vent line, the shared line must equal or exceed the sum of the outlet areas of all upstream relief devices, depending on the resulting back pressure.
ASHRAE Standard 15 provides guidance for determining the maximum vent line length. It also provides the equation (shown in properly size the vent line at the outlet of a pressure-relief device or fusible plug.
The equation accounts for the relationship between pipe diameter, equivalen t pipe len gth, and the pr essure difference bet ween the vent line inlet and outlet to help ensure that the vent line syst em provides sufficient flow capacity.
Table 8, p. 35 provides additional information based on
ASHRAE Standard 15, including:
Capacities of various vent line sizes and l engths. However, this data applies only to conventional pressure-relief valves and NOT to balanced relief valves, rupture members (as used on Trane centrifu gal chill ers), fusible plugs, or pilot-operated valves.
A simplified meth od to determine the appropriate vent-line size, with with the total C value, read across to a pipe curve and down to find the maximum allowable length for that size pipe.
To determine the total C value for a specific unit, add the appropriate C values for the evaporator, standard condenser, and economizer. If the unit is equipped with any options (e.g., heat recovery, free cooling, or an auxiliary condenser), add the applicable C value(s) for those options to the total as well.
Note:
Table 8, p. 35 and Figure 23, p. 36 are applicable
only for non-manifolded vent-line runs connected to a 344.7 kPa (50 psi) rupture disk relief device. The pipe length provided by the table is in “equivalent feet.” The vent-line length in equivalent feet is the
Figure 23, p. 36) and data necessary to
®
Figure 23, p. 36. Enter the figure
30 CVHH-SVX001A-EN
Loading...
+ 81 hidden pages