Notice that warnings and cautions
appear at appropriate intervals
throughout this manual. Warnings
are provided to alert installing
contractors to potential hazards that
could result in personal injury or
death, while cautions are designed to
alert personnel to conditions that
could result in equipment damage.
Your personal safety and the proper
operation of this machine depend
upon the strict observance of these
precautions.
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
WARNING – Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION – Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situation that may result in equipment or property-damage-only accidents.
Operation and maintenance
information for models CVHE, CVHF
and CVHG are covered in this
manual. This includes both 50 and 60
Hz. CVHE, CVHF and CVHG
centrifugal chillers equipped with the
Tracer CH530 Chiller Controller
system. Please note that information
pertains to all three chiller types
unless differences exist in which
case the sections are broken down
by Chiller type as applicable and
discussed separately.
By carefully reviewing this
information and following the
instructions given, the owner or
operator can successfully operate
and maintain a CVHE, CVHF or CVHG
unit.
If mechanical problems do occur,
however, contact a qualified service
organization to ensure proper
diagnosis and repair of the unit.
Note: The CH530 controller was first
applied to CVHE with Design
Sequence “3K”, and to CVHF with
Design Sequence “1W”.
Unit Nameplate
The unit nameplate is located on the
left side of the unit control panel.
The following information is
provided on the unit nameplate.
1. Serial Number
The unit serial number provides the
specific chiller identity. Always
provide this serial number when
calling for service or during parts
identification..
2. Service Model Number
The service model represents the unit
as built for service purposes . It
identifies the selections of variable
unit features required when ordering
replacements parts or requesting
service.
Note: Unit-mounted starters are
identified by a separate number
found on the starter.
The CVHE, CVHF and CVHG models
are defined and built using the
product definition and selection
(PDS) system. This system describes
the product offerings in terms of a
product coding block which is made
up of feature categories and feature
codes. An example of a typical
product code block is given on this
page. The coding block precisely
identifies all characteristics of a unit.
4. Identifies unit electrical
requirements
5. Correct operating charges and type
of refrigerant
6. Unit Test Pressures and Maximum
Operating Pressures
7. Identifies unit Installation and
Operation and Maintenance manuals
digit) Unit Type
A = Cooling Condenser
B = Heat Recovery Condenser
C = Auxiliary Condenser
D = Free Cooling Option
S = Special
L0 = (10
th
and 11th digit) Design
Sequence
th
0 = (12
digit) Hot Gas By-Pass
W = With HGB
0 = Without HGB
S = Special
th
A = (13
) Starter type
A = Star-Delta Unit Mounted
C = Star Delta – Remote Mounted
E = X-Line Full Volt – Remote
Mounted
F = Autotransformer – Remote
Mounted
G = Primary Reactor – Remote
Mounted
H = X-Line Full Volt – Unit Mounted
J = Autotransformer – Unit
Mounted
K = Primary Reactor – Unit
Mounted
L = Solid State – Unit Mounted
M = Solid State – Floor Mounted
N = Solid State – Wall Mounted
P = Adaptive Frequency Drive - Unit
Mounted
R = Customer Supplied
th
C = (14
digit) Control Enclosure
S = Special
C = Standard Control Enclosure
th
U = (15
digit) Compressor Motor
Power (kw)
275 = (16
th
, 17th, and 18th digit)
Compressor Imp Cutback
th
8 = (19
W = (20
digit) Evaporator Shell Size
th
digit) Evaporator Tube
Bundle
st
7 = (21
E = (22
8 = (23
T = (24
digit) Evaporator Tubes
nd
digit) Evaporator Waterbox
rd
digit) Condenser Shell Size
th
digit) Condenser Tube
Bundle
th
B = (25
C = (26
digit) Condenser Tubes
th
digit) Condenser
Waterboxes
th
0 = (27
digit) Heat Recovery
Condenser Shell Size
th
0 = (28
digit) Heat Recovery
Condenser Tube Bundle
th
0 = (29
digit) Heat Recovery
Condenser Tubes
th
0 = (30
digit) Heat Recovery
Condenser Waterboxes
st
0 = (31
digit) Auxiliary Condenser
Size and Waterboxes
nd
0 = (32
digit) Auxiliary Condenser
Tubes
rd
0 = (33
K = (34
digit) Orifice Size
th
digit) Orifice Size
th
0 = (35
1 = (36
digit) Unit Option
th
digit) Control: Enhanced
protection
G = (37
1 = (38
th
digit) Control: Generic BAS
th
digit) Control: Extended
operation
th
4 = (39
digit) Tracer communication
interface
th
C = (40
digit) Control: Condenser
refrigerant pressure
st
1 = (41
0 = (42
W = (43
digit) Control: Tracer IO
nd
digit) Special Options
nd
digit) Control: Water flow
control
th
1 = (44
digit) Control: Chilled water
reset
th
A = (45
digit) Control: Heat Recovery
temperature sensors
th
0 = (46
3 = (47
digit) Gas Powered Chiller
th
digit) Compressor Motor
Frame Size
th
B = (48
digit) Volute Discharge
Angle
th
1 = (49
digit) Control: Operating
status
W = (50
th
digit) Industrial Chiller
Package (INDP)
0 = Without INDP
W = With INDP
st
1 = (51
digit) Control Power
Transformer (CPTR)
0 = Without CPTR
1 = With CPTR
S = Special
nd
B = (52
digit) Motor and Terminal
Board Configuration
A = Six Lead Low Voltage
B = Three Lead Medium
Voltage
C = Six Lead Medium
Voltage
S = Special
CVHE-SVU01E-EN
5
General
Information
Commonly Used Acronyms
For convenience, a number of
acronyms are used throughout this
manual. These acronyms are listed
alphabetically below, along with the
“translation” of each:
AFD = Adaptive Frequency Drive
ASME = American Society of
Mechanical Engineers
ASHRAE = American Society of
Heating, Refrigerating and Air
Conditioning Engineers
BAS = Building Automation System
CABS = Auxiliary Condenser TubeBundle S
CDBS = Condenser Bundle Size
CDSZ = Condenser Shell Size
CH530 = Tracer CH530 Controller
DV = DynaView
Display, also know as the Main
Processor (MP)
CWR = Chilled Water Reset
CWR’ = Chilled Water Reset Prime
DTFL = Design Delta-T at Full Load
(i.e., the difference between entering
and leaving chilled water
temperatures)
ELWT = Evaporator Leaving Water
Temperature
ENT = Entering Chilled Water
Temperature
FC = Free Cooling
GPM = Gallons-per-minute
™
Clear Language
HGBP = Hot Gas Bypass
HVAC = Heating, Ventilating, and Air
Conditioning
IE = Internally-Enhanced Tubes
IPC = Interprocessor Communication
LBU = La Crosse Business Unit
LCD = Liquid Crystal Display
LED = Light Emitting Diode
MAR = Machine Shutdown Auto
Restart (Non-Latching where chiller
will restart when condition corrects
itself.)
MMR = Machine Shutdown Manual
Restart (Latching where chiller must
be manually reset.)
Tracer CH530= Controls Platform
utilized on this Chiller
TOD = Temperature Outdoor
Control Optional Packages
OPST Operating Status Control
GBAS Generic Building Automation
Interface
EXOP Extended Operation
CDRP Condenser Pressure
Transducer
TRMM Tracer Communications
FRCL Free Cooling
HGBP Hot Gas Bypass
WPSR Water pressure sensing
EPRO Enhanced Protection
ACOS Auxillary Condenser sensors
CWR Chiller Water reset outdoor
6
CVHE-SVU01E-EN
General
Information
Overview
CVHE, CVHG, CVHF
Each CVHE, CVHG, or CVHF unit is
composed of 5 basic components.
— the evaporator,
— 3-stage compressor on CVHE,
CVHG or 2 stage compressor on
CVHF,
— 2-stage economizer on CVHE,
CVHG, or single economizer on
CVHF,
See Figure 1 for Typical CVHE and
CVHG, and Figure 2 for Typical CVHF
major components.
Figure 1. General CVHE and CVHG unit components
A heat-recovery or auxiliary
condenser can be factory-added to
the basic unit assembly to provide a
heat-recovery cycle.
— water-cooled condenser,
— related interconnecting piping.
CVHE-SVU01E-EN
7
General
Information
Figure 1. General CVHE and CVHG unit components - continued
8
CVHE-SVU01E-EN
General
Information
Figure 2. Illustrates the general component layout of a typical CVHF chiller
CVHE-SVU01E-EN
9
General
Information
Cooling Cycle
CVHE, CVHG, CVHF
When in the cooling mode, liquid
refrigerant is distributed along the
length of the evaporator and sprayed
through small holes in a distributor
(i.e., running the entire length of the
shell) to uniformly coat each
evaporator tube. Here, the liquid
refrigerant absorbs enough heat from
the system water circulating through
the evaporator tubes to vaporize.
The gaseous refrigerant is then
drawn through the eliminators
(which remove droplets of liquid
refrigerant from the gas) and firststage variable inlet guide vanes, and
into the first stage impeller.
Note: Inlet guide vanes are designed
to modulate the flow of gaseous
refrigerant to meet system capacity
requirements; they also prerotate the
gas, allowing it to enter the impeller
at an optimal angle that maximizes
efficiency at all load conditions.
CVHE, CVHG Compressor
Compressed gas from the first-stage
impeller flows through the fixed,
second-stage inlet vanes and into the
second-stage impeller.
Here, the refrigerant gas is again
compressed, and then discharged
through the third-stage variable guide
vanes and into the third stage
impeller.
Once the gas is compressed a third
time, it is discharged into the
condenser. Baffles within the
condenser shell distribute the
compressed refrigerant gas evenly
across the condenser tube bundle.
Cooling tower water circulated
through the condenser tubes absorbs
heat from the refrigerant, causing it to
condense. The liquid refrigerant then
passes through orifice plate ‘‘A’’ and
into the economizer.
The economizer reduces the energy
requirements of the refrigerant cycle
by eliminating the need to pass all
gaseous refrigerant through three
stages of compression. See Figure 3.
Notice that some of the liquid
refrigerant flashes to a gas because
of the pressure drop created by the
orifice plates, thus further cooling the
liquid refrigerant. This flash gas is
then drawn directly from the first
(Chamber A) and second (Chamber
B) stages of the economizer into the
third-and second-stage impellers of
the compressor, respectively.
All remaining liquid refrigerant flows
through another orifice plate ‘‘C’’ to
the evaporator.
CVHF Compressor
Compressed gas from the first-stage
impeller is discharged through the
second-stage variable guide vanes
and into the second-stage impeller.
Here, the refrigerant gas is again
compressed, and then discharged
into the condenser.
Baffles within the condenser shell
distribute the compressed refrigerant
gas evenly across the condenser
tube bundle. Cooling tower water,
circulated through the condenser
tubes, absorbs heat from the
refrigerant, causing it to condense.
The liquid refrigerant then flows out
of the bottom of the condenser,
passing through an orifice plate and
into the economizer.
The economizer reduces the energy
requirements of the refrigerant cycle
by eliminating the need to pass all
gaseous refrigerant through both
stages of compression. See Figure 6.
Notice that some of the liquid
refrigerant flashes to a gas because
of the pressure drop created by the
orifice plate, thus further cooling the
liquid refrigerant. This flash gas is
then drawn directly from the
economizer into the second-stage
impellers of the compressor.
All remaining liquid refrigerant flows
out of the economizer, passes
through another orifice plate and into
the evaporator.
10
CVHE-SVU01E-EN
General
Information
Figure 3. CVHE, CVHG pressure enthalpy curve
Figure 4. CVHE, CVHG 2-stage economizer
CVHE-SVU01E-EN
11
Figure 5. CVHF pressure enthalpy curve
General
Information
Figure 6. CVHF single stage economizer
12
CVHE-SVU01E-EN
General
Information
Overview
Controls Operator Interface
Information is tailored to operators,
service technicians and owners
When operating a chiller, there is
specific information you need on a
day-to-day basis — setpoints, limits,
diagnostic information, and reports.
When servicing a chiller, you need
different information and a lot more
of it — historic and active
diagnostics, configuration settings,
and customizable control algorithms,
as well as operation settings.
By providing two different tools –
one for daily operation and one for
periodic service — everyone has
easy access to pertinent and
appropriate information.
DynaView™ Human Interface
— For the operator
Day-to-day operational information is
presented at the panel. Up to seven
lines of data (English or SI units) are
simultaneously displayed on the ¼
VGA touch-sensitive screen.
Logically organized groups of
information — chiller modes of
operation, active diagnostics,
settings and reports put information
conveniently at your fingertips. See
Operator Interface Section for details.
Figure 7. CVHE, CVHF, and CVHG sequence of operation overview
TechView
— For the service technician or
advanced operator
All chiller status, machine
configuration settings, customizable
limits, and up to 60 active or historic
diagnostics are displayed through
the service tool interface. Without
changing any hardware, we give you
access to the latest and greatest
version of Tracer CH530! A new level
of serviceability using the innovative
TechView
technician can interact with an
individual device or a group of
devices for advanced
troubleshooting. LED lights and their
respective TechView
visually confirm the viability of each
device. Any PC that meets the system
requirements may download the
service interface software and Tracer
CH530 updates. For more information
on TechView
Service company, or The Trane
Company’s website at
www.trane.com.
™
Chiller Service Tool
™
chiller service tool, a
™
indicators
™
visit your local Trane
CVHE-SVU01E-EN
13
General
Information
Figure 8. CVHE, CVHF, and CVHG sequence of operation: power up to starting
Figure 9. CVHE, CVHF, and CVHG sequence of operation: running
14
CVHE-SVU01E-EN
General
Information
Figure 10. CVHE, CVHF, and CVHG sequence of operation: satisfied setpoint
Figure 11. CVHE, CVHF and CVHG sequence of operation: normal shutdown to stopped and run inhibit
CVHE-SVU01E-EN
15
General
Information
Oil and Refrigeration Pump
Compressor Lubrication System -
A schematic diagram of the
compressor lubrication system is
illustrated in Figure 12.
Oil is pumped from the oil tank (by a
pump and motor located within the
tank) through an oil pressureregulating valve designed to maintain
a net oil pressure of 18 to 22 psid. It
is then filtered and sent to the oil
cooler located in the economizer and
on to the bearings. From the
bearings, the oil drains back to the
manifold under the motor and then
on to the oil tank.
CAUTION
Surface Temperatures!
MAY EXCEED 150°F. Use caution
while working on certain areas of
the unit, failure to do so may result
in minor or moderate injury.
To ensure proper lubrication and
prevent refrigerant from condensing
in the oil tank, a 750-watt heater is
immersed in the oil tank and is used
to warm the oil while the unit is off.
When the unit starts, the oil heater is
de-energized. This heater energizes
as needed to maintain 140° to 145° F
(60-63°C) when the chiller is not
running.
When the chiller is operating, the
temperature of the oil tank is typically
115° to 160°F (46-72°C). The oil return
lines from the thrust and journal
bearings, transport oil and some seal
leakage refrigerant. The oil return
lines are routed into a manifold
under the motor. Gas flow exits the
top of the manifold and is vented to
the Evaporator. A vent line solenoid
is not needed with the refrigerant
pump. Oil exits the bottom of the
manifold and returns to the tank.
Separation of the seal leakage gas in
the manifold keeps this gas out of the
tank.
A dual eductor system is used to
reclaim oil from the suction cover
and the evaporator, and deposit it
back into the oil tank. These eductors
use high pressure condenser gas to
draw the oil from the suction cover
and evaporator to the eductors and
then discharged into the oil tank. The
evaporator eductor line has a shut off
valve mounted by the evaporator and
ships closed. Open two turns if
necessary.
Liquid refrigerant is used to cool the
oil supply to both the thrust bearing
and journal bearings. On refrigerant
pump units the oil cooler is located
inside the economizer and uses
refrigerant passing from the
condenser to evaporator to cool the
oil. Oil leaves the oil cooler and
flows to both the thrust and journal
bearings.
Motor Cooling System
Compressor motors are cooled with
liquid refrigerant, see Figure 12.
The refrigerant pump is located on
the front of the oil tank (motor inside
the oil tank). The refrigerant pump
inlet is connected to the well at the
bottom of the condenser. The
connection is on the side where a
weir assures a preferential supply of
liquid. Refrigerant is delivered to the
motor via the pump. Motor
refrigerant drain lines are routed to
the condenser.
16
CVHE-SVU01E-EN
Figure 12. Oil refrigerant pump
General
Information
CVHE-SVU01E-EN
17
General
Information
Base Loading Control
Algorithm:
This feature allows an external
controller to directly modulate the
capacity of the chiller. It is typically
used in applications where virtually
infinite sources of evaporator load
and condenser capacity are available
and it is desirable to control the
loading of the chiller. Two examples
are industrial process applications
and cogeneration plants. Industrialprocess applications might use this
feature to impose a specific load on
the facility’s elecrical system.
Cogeneration plants might use this
feature to balance the system’s
heating, cooling and electrical
generation.
All chiller safeties and adaptive
control functions are in full effect
when Base Loading control is
enabled. If the chiller approaches full
current, the evaporator temperature
drops too low, or the condenser
pressure rises too high, Tracer CH530
Adaptive Control logic limits the
loading of the chiller to prevent the
chiller from shutting down on a
safety limit. These limits may prevent
the chiller from reaching the load
requested by the Base Loading
signal.
Base Loading Control is basically a
variation of the current limit
algorithm. During base loading, the
leaving water control algorithm
provides a load command every 5
seconds. The current limit routine
may limit the loading when the
current is below setpoint. When the
current is within the deadband of the
setpoint the current limit algorithm
holds against this loading command.
If the current exceeds the setpoint,
the current limit algorithm unloads.
The “Capacity Limited By High
Current” message normally
displayed while the current limit
routine is active is suppressed while
base loading.
Base loading can occur via Tracer,
External signal, or front panel.
Tracer Base Loading:
Current Setpoint Range:
(20 - 100) percent RLA
Requires Tracer and Optional Tracer
Communications Module (LLID)
The Tracer commands the chiller to
enter the base load mode by sending
the base load mode request. If the
chiller is not running, it will start
regardless of the differential to start
(either chilled water or hot water). If
the chiller is already running, it will
continue to run regardless of the
differential to stop (either chilled
water or hot water), using the base
load control algorithm. While the unit
is running in base loading, it will
report that status back to the Tracer
by setting “Base Load Status = true”
in the Tracer Status Byte. When the
Tracer removes the base load mode
request (sets the bit to 0). The unit
will continue to run, using the
normal chilled or hot water control
algorithm, and will turn off, only
when the differential to stop has been
satisfied.
External Base Loading:
Current Setpoint Range:
(20 - 100) percent RLA
The UCP accepts 2 inputs to work
with external base loading. The
binary input is at 1A18 Terminals J2-1
and J2-2 (Ground) which acts as a
switch closure input to enter the
base-loading mode. The second
input, an analog input, is at 1A17
terminals J2 – 1 and 3 (Ground)
which sets the external base loading
setpoint, and can be controlled by
either a 2-10Vdc or 4-20ma Signal. At
startup the input type is configured.
The graphs in Figure 13 show the
relationship between input and
percent RLA. While in base loading
the active current limit setpoint is set
to the Tracer or external base load
setpoint, providing that the base load
setpoint is not equal to 0 (or out of
range). If it is out of range, the front
panel current limit setpoint is used.
During base loading, all limits are
enforced with the exception of
current limit. The human interface
displays the message “Unit is
Running Base Loaded”. Hot Gas
Bypass is not run during base
loading. If base loading and ice
making are commanded
simultaneously, ice making takes
precedence.
An alternative and less radical
approach to Base Loading indirectly
controls chiller capacity. Artifically
load the chiller by setting the chilled
water setpoint lower than it is
capable of achieving. Then, modify
the chiller’s load by adjusting the
current limit setpoint. This method
provides greater safety and control
stability in the operation of the chiller
because it has the advantage of
leaving the chilled water temperature
control logic in effect. The chilled
water temperature control logic
responds quicker to dramatic system
changes, and can limit the chiller
loading prior to reaching an Adaptive
Control limit point.
18
CVHE-SVU01E-EN
General
Information
Figure 13. Base loading with external mA input and with external voltage input
CVHE-SVU01E-EN
19
General
Information
Ice Machine Control
The control panel provides a service
level “Enable or Disable” menu entry
for the Ice Building feature when the
Ice Building option is installed. Ice
Building can be entered 1) from the
“Front Panel”, 2) if hardware is
specified, will accept either an
isolated contact closure (1A19
Terminals J2-1 and J2-2 (Ground) ) 3),
a remote communicated input
(Tracer) to initiate the ice building
mode where the unit runs fully
loaded at all times. Ice building will
be terminated either by opening the
contact or based on entering
evaporator fluid temperature. UCP
will not permit the Ice Building mode
to be entered again until the unit is
switched to the Non-ice building
mode and back into the ice building
mode. It is not acceptable to reset the
chilled water setpoint low to achieve
a fully loaded compressor. When
entering ice-building the compressor
will be loaded at its maximum rate
and when leaving ice building the
compressor will be unloaded at its
maximum rate. While loading and
unloading the compressor, all surge
detection will be ignored. While in
the ice building mode, current limit
setpoints less than the maximum will
be ignored. Ice Building can be
terminated by one of the following
means:
1. Front Panel Disable, or
2. Opening the external Ice. Contacts/
Remote communicated input
(Tracer), or
3. Satisfying an evaporator entering
fluid temperature setpoint (Default
to 27°F).
4. Surging for 7 minutes at full open
IGV.
Figure 14. CVHE, CVHF and CVHG sequence of operation: ice making: running
to ice making
Figure 15. CVHE, CVHF and CVHG sequence of operation: ice making:
stopped to ice to ice building complete
20
CVHE-SVU01E-EN
General
Information
Free Cooling Cycle
Based on the principle that refrigerant
migrates to the coldest area in the
system, the free cooling option
adapts the basic chiller to function as
a simple heat exchanger. However, it
does not provide control of the
leaving chilled water temperature.
If condenser water is available at a
temperature lower than the required
leaving chilled water temperature, the
operator interface must remain in
“AUTO” and the operator starts the
free cooling cycle by enabling the
Free cooling mode in the
“DynaView
of the operator interface, or by means
of a Tracer request.
Several components must be factoryinstalled or field-installed to equip the
unit for free cooling operation:
— a refrigerant gas line, and
electrically-actuated shutoff valve,
between the evaporator and
condenser;
— a valve liquid return line, and
electrically-actuated shutoff valve,
between the condenser sump and
the evaporator;
— a liquid refrigerant storage vessel
(larger economizer); and,
— additional refrigerant.
™
Feature Settings” group
When the chiller is changed over to
the free cooling mode, the
compressor will shut down if
running, the shutoff valves in the
liquid and gas lines open; unit
control logic prevents the
compressor from energizing during
free cooling. Liquid refrigerant then
drains (by gravity) from the storage
tank into the evaporator and floods
the tube bundle. Since the
temperature and pressure of the
refrigerant in the evaporator are
higher than in the condenser (i.e.,
because of the difference in water
temperature), the refrigerant in the
evaporator vaporizes and travels to
the condenser. Cooling tower water
causes the refrigerant to condense,
and it flows (again, by gravity) back
to the evaporator.
This compulsory refrigerant cycle is
sustained as long as a temperature
differential exists between condenser
and evaporator water. The actual
cooling capacity provided by the free
cooling cycle is determined by the
difference between these
temperatures which, in turn,
determines the rate of refrigerant flow
between the evaporator and
condenser shells.
If the system load exceeds the
available free cooling capacity, the
operator must manually initiate
changeover to the mechanical
cooling mode by disabling the free
cooling mode of operation. The gas
and liquid line valves then close and
compressor operation begins. (See
Figure 8 beginning at “Auto” mode.)
Refrigerant gas is drawn out of the
evaporator by the compressor, where
CVHE-SVU01E-EN
21
General
Information
it is then compressed and
discharged to the condenser. Most of
the condensed refrigerant initially
follows the path of least resistance by
flowing into the storage tank. This
tank is vented to the economizer
sump through a small bleed line;
when the storage tank is full, liquid
refrigerant must flow through the
bleed line restriction. Because the
pressure drop through the bleed line
is greater than that of the orifice flow
control device, the liquid refrigerant
flows normally from the condenser
through the orifice system and into
the economizer.
Free Cooling FRCL
To enable Free Cooling Mode:
1. Free Cooling must first be installed
and commissioned.
2. Enable the Free Cooling mode in
the DynaView
3. Press “AUTO”, and if used, close
the external binary input switch
(connected to 1A20 J2- 1 to 2) while
the chiller is in “AUTO”.
Free Cooling cannot be entered if the
chiller is in “STOP”.
If the chiller is in “AUTO” and not
running, the condenser water pump
will start. After condenser water flow
is proven, Relay Module 1A11 will
energize operating the Free Cooling
Valves 4B12 and 4B13. The Free
Cooling Valves End Switches must
open within 3 minutes, or an MMR
diagnostic will be generated. Once
the Free Cooling Valves End
Switches open, the unit is in the Free
Cooling mode. If the chiller is in
“AUTO” and running powered
cooling, the chiller will do a friendly
shut down first, (Run: Unload, Post
Lube, and drive vanes closed). After
the vanes have been overdriven,
closed and condenser water proven,
the Free Cooling relays will be
™
Settings Menu
energized. To disable Free Cooling
and return to Powered Cooling, either
disable the Free Cooling Mode in the
DynaView
enable Free Cooling or “OPEN” the
external binary input switch to the
1A20 Module if it was used to enable
Free Cooling. Once Free Cooling is
disabled, the Free Cooling relays
Relay Module 1A11 will de-energize
allowing the Free Cooling valves to
close. The Free Cooling valves end
switches must close within 3
minutes or an MMR diagnostic is
generated. Once the end switches
close the chiller will return to
“AUTO” and powered cooling will
resume if there is a call for cooling
based on the differential to start.
Note: The manual control of the inlet
guide vanes is disabled while in the
Free Cooling Mode and the
compressor is prevented from
starting by the control logic.
Note: The relay at 1A11-J-2-4 to 6 is a
FC auxiliary relay and can be used as
required.
™
settings menu if used to
22
CVHE-SVU01E-EN
General
Information
Hot Gas Bypass
The hot gas bypass (HGBP) control
option is designed to minimize
machine cycling by allowing the
chiller to operate stably under
minimum load conditions. In these
situations, the inlet guide vanes are
“locked” at a preset minimum
position, and unit capacity is
governed by the HGBP valve actuator.
Control circuitry is designed to allow
both the inlet guide vanes and the
HGBP valve to close for unit
shutdown.
After a chiller starts and is running
the inlet guide vanes will pass
through the HGBP Cut-In-Vane
position as the chiller starts to load.
As the chiller catches the load and
starts to unload, the inlet guide vanes
will close to the HGBP Cut-In Vane
position. At this point the movement
of the inlet guide vanes is frozen and
further unloading of the chiller is
controlled by the opening of the
HGBP Valve 4M5 and module
modulates the HGBP valve at low
loads. When the control algorithm
determines the chiller to be shut
down, the inlet guide vanes will be
driven fully closed, and the HGBP
valve will be driven closed. After the
inlet guide vanes are fully closed the
chiller will shut down in the Friendly
mode. Chillers with HGBP have a
discharge temperature sensor (4R16)
monitoring the discharge gas
temperature from the compressor. If
this temperature exceeds 200°F, the
chiller will shut off on a MAR
diagnostic. The chiller will reset
automatically when this temperature
drops 50°F below the trip-point.
HGBP is enabled in the Features
menu settings Group of the DV
Menus by enabling the option. The
setting the HGBP Cut-In Vane
Position is setup at unit
commissioning via the service tool.
CVHE-SVU01E-EN
23
General
Information
Hot Water control
Occasionally CTV chillers are
selected to provide heating as a
primary mission. With hot water
temperature control, the chiller can
be used as a heating source or
cooling source. This feature provides
greater application flexibility. In this
case the operator selects a hot water
temperature and the chiller capacity
is modulated to maintain the hot
water setpoint. Heating is the primary
mission and cooling is a waste
product or is a secondary mission.
This type of operation requires an
endless source of evaporator load
(heat), such as well or lake water. The
chiller has only one condenser.
Note: Hot water temperature control
mode does not convert the chiller to
a heat pump. Heat pump refers to the
capability to change from a coolingdriven application to a heating-driven
application by changing the
refrigerant path on the chiller. This is
impractical for centrifugal chillers as
it would be much easier to switch
over the water side.
This is NOT heat recovery. Although
this feature could be used to recover
heat in some form, there is a second
heat exchanger on the condenser
side.
The DynaView
provides the hot water temperature
control mode as standard. The
leaving condenser water temperature
is controlled to a hot water setpoint
between 80 and 140°F (26.7 to 60°C)
The leaving evaporator water
temperature is left to drift to satisfy
the heating load of the condenser. In
this application the evaporator is
normally piped into a lake, well, or
other source of constant temperature
water for the purpose of extracting
heat.
In hot water temperature control
mode all the limit modes and
diagnostics operate as in normal
cooling with one exception; The
leaving condenser water temperature
sensor is an MMR diagnostic when
in hot water temperature control
mode. (It is an informational warning
in the normal cooling mode.)
In the hot water temperature control
mode the differential-to-start and
differential-to-stop setpoints are used
with respect to the hot water setpoint
instead of with the chilled water
setpoint.
UCP provides a separate entry at the
DV to set the hot water setpoint.
Tracer is also able to set the hot
water setpoint. In the hot water mode
the external chilled water setpoint is
the external hot water setpoint; that
is, a single analog input is shared at
the 1A16 –J2-1 to J2-3 (ground)
™
Main Processor
An external binary input to select
external hot water control mode is on
the EXOP OPTIONAL module 1A18
terminals J2-3 to J2-4 (ground). Tracer
also has a binary input to select
chilled water control or hot water
temperature control.
There is no additional leaving hot
water temperature cutout; the HPC
and condenser limit provide for high
temperature and pressure protection.
In hot water temperature control the
softloading pulldown rate limit
operates as a softloading pullup rate
limit. The setpoint for setting the
temperature rate limit is the same
setpoint for normal cooling as it is
for hot water temperature control.
The hot water temperature control
feature is not designed to run with
HGBP, AFD, free cooling, or ice
making.
The factory set PID tuning values for
the leaving water temperature control
are the same settings for both normal
cooling and hot water temperature
control.
24
CVHE-SVU01E-EN
General
Information
Heat Recovery Cycle
‘‘Heat recovery’’ is designed to
salvage the heat that is normally
rejected to the atmosphere through
the cooling tower, and put it to
beneficial use. For example, a highrise office building may require
simultaneous heating and cooling
during the winter months. With the
addition of a heat recovery cycle, heat
removed from the building cooling
load can be transferred to areas of the
building that require heat. (Keep in
mind that the heat recovery cycle is
only possible if a cooling load exists
to act as a heat source.)
To provide a heat recovery cycle, a
heat-recovery condenser is added to
the unit; see Figure 2. Though
physically identical to the standard
cooling condenser, the heat-recovery
condenser is piped into a heat circuit
rather than to the cooling tower.
During the heat recovery cycle, the
unit operates just as it does in the
‘‘cooling only’’ mode except that the
cooling load heat is rejected to the
heating water circuit rather than to
the cooling tower water circuit. When
hot water is required, the heating
water circuit pumps energize. Water
circulated through the heat-recovery
(or auxiliary) condenser tube bundle
by the pumps absorbs cooling-load
from the compressed refrigerant gas
discharge by the compressor. The
heated water is then used to satisfy
heating requirements.
Auxiliary Condensers
Unlike the heat-recovery condenser
(which is designed to satisfy comfort
heating requirements), the auxiliary
condenser serves a preheat function
only, and is used in those
applications where hot water is
needed for use in kitchens,
lavatories, etc. While the operation of
the auxiliary condenser is physically
identical to that of the heat-recovery
condenser, it is comparatively
smaller in size, and its heating
capacity is not controlled.
Trane does not recommend
operating the auxiliary condenser
alone because of its small size.
CVHE-SVU01E-EN
25
Unit Control
Panel (UCP)
Control Panel Devices and Unit
Mounted Devices
Unit Control Panel (UCP)
Safety and operating controls are
housed in the unit control panel, the
starter panel and the purge control
panel. The UCP ‘s operator interface
and main processor is called the
DynaView
the UCP door. (See Operators
interface section for detailed
information)
Figure 16. Control panel and approximate dimensions
™
(DV) and is located on
The UCP houses several other
controls modules called panel
mounted LLID (Low Level Intelligent
Device), power supply, terminal
block, fuse, circuit breakers, and
transformer. The IPC (Interprocessor
communication) bus allows the
communications between LLID’s and
the main processor. Unit mounted
devices are called frame mounted
LLID’s and can be temperature
sensors or pressure transducers.
These and other functional switches
provide analog and binary inputs to
the control system.
26
CVHE-SVU01E-EN
Unit Control
Panel (UCP)
Tracer CH530 Chiller Controller
Revolutionary control of the chiller,
chilled water system, and your entire
building with unprecedented
accuracy, reliability, efficiency, and
support for maintenance using the
chiller’s PC-based service tool.
Chiller reliability is all about
producing chilled water and keeping
it flowing, even when facing
conditions that ordinarily would shut
down the chiller — conditions that
often happen when you need cooling
the most.
Tracer CH530’s Main Processor,
DynaView
chiller online whenever possible.
Smart sensors collect three rounds of
data per second, 55 times the data
collection speed of its predecessor.
Each device (a sensor) has its own
microprocessor that simultaneously
converts and accurately calibrates its
own readings from analog to digital.
Because all devices are
communicating digitally with the
DynaView
no need for the main processor to
convert each analog signal one at a
time. This distributed logic allows
the main processor to focus on
responding to changing conditions
— in the load, the machine, its
ancillary equipment, or its power
supply. Tracer CH530 constantly
receives information about key data
parameters, temperatures and
™
, is fast and keeps the
™
main processor, there is
current. Every five seconds then a
multiple objective algorithm
compares each parameter to its
programmed limit. The chiller’s
Adaptive Control
™
capabilities
maintain overall system performance
by keeping its peak efficiency.
Whenever the controller senses a
situation that might trigger a
protective shutdown, it focuses on
bringing the critical parameter back
into control. When the parameter is
no longer critical, the controller
switches its objective back to
controlling the chilled water
temperature, or to another more
critical parameter should it exist.
Variable water flow through the
evaporator
Chilled-water systems that vary water
flow through chiller evaporators have
caught the attention of engineers,
contractors, building owners, and
operators. Varying the water flow
reduces the energy consumed by
pumps, while requiring no extra
energy for the chiller. This strategy
can be a significant source of energy
savings, depending on the
application. With its faster and more
intelligent response to changing
conditions, Tracer CH530 reliably
accommodates variable evaporator
water flow and its effect on the
chilled water temperature. These
improvements keep chilled water
flowing at a temperature closer to its
setpoint.
User-defined language support
DynaView
™
is capable of displaying
English text or one of the two
alternate languages that are stored in
DynaView
™
at one time. Switching
languages is simply accomplished
from a settings menu.
Similarly, TechView
™
accommodates
a primary and a secondary language
from the same list of available
languages.
CVHE-SVU01E-EN
27
Operator
Interface
Figure 17. DynaView™ main processor
DynaView
tabs across the top which are
labeled “MAIN, REPORTS, and
SETTINGS”.
The Main screen provides an overall
high level chiller status so the
operator can quickly understand the
mode of operation of the chiller.
The Chiller Operating Mode will
present a top level indication of the
chiller mode (Auto, Running, Inhibit,
Run Inhibit, etc.) The “additional
info” icon will present a subscreen
that lists in further detail the
subsystem modes. (See Machine
Operating Modes.)
Main screen content can be viewed
by selecting the up or down arrow
icons. The Main screen is the default
screen and after an idle time of 30
minutes.
™
presents three menu
The DynaView™ (DV) Operator
Interface contains the “Main
Processor (MP)” and is mounted on
the unit control panel front door
where it communicates commands
to other modules, collecting data,
status and diagnostic information
from the other modules over the IPC
(Inter Processor Communications)
link. The Main Processor (MP)
software controls water flows by
starting pumps and sensing flow
inputs, establishes a need to heat or
cool, performs pre-lube, performing
post-lube, starts the compressor(s),
performs water temperature control,
establishes limits, and pre-positions
the inlet guide-vanes.
28
The MP contains non-volatile
memory both checking for valid set
points and retaining them on any
power loss. System data from
modules (LLID) can be viewed at the
DynaView
as evaporator and condenser water
temperatures, outdoor air
temperature, evaporator and
condenser water pump control,
status and alarm relays, external
auto-stop, emergency stop,
evaporator and condenser water
pressure drops and evaporator and
condenser water flow switches.
™
operator interface. Such
CVHE-SVU01E-EN
Operator
Interface
DynaView™ (DV) is the operator
interface of the Tracer CH530 control
system utilized on the CTV machine.
The DynaView
wide, 8” high and 1.6” deep. The
DynaView
4” wide by 3” high. Features of the
display include a touch screen and
long life LED backlight. This device is
capable of operating in 0 - 95 percent
relative humidity (non-condensing),
and is designed and tested with UV
considerations consistent with an
outdoor application in direct
sunlight. The enclosure includes a
weather tight connection means for
the RS232 service tool connection.
Touch screen key functions are
determined completely in the
software and change depending
upon the subject matter currently
being displayed. The user operates
the touch sensitive buttons by
touching the button of choice. The
selected button is darkened to
indicate it is the selected choice. The
advantage of touch sensitive buttons
is that the full range of possible
choices as well as the current choice
is always in view.
™
enclosure is 9.75"
™
display is approximately
Spin values (up or down) are a
graphical user interface model used
to allow a continuously variable
setpoint, such as leaving water
setpoint to be changed. The value
changes by touching the increment
or decrement arrows.
Action buttons are buttons that
appear temporarily and provide the
operator with a choice such as Enter
or Cancel. The operator indicates his
choice by touching the button of
choice. The system then takes the
appropriate action and the button
typically disappears.
DynaView
screens, each meant to serve a
unique purpose of the machine being
served. Tabs are shown row across
the top of the display. The user
selects a screen of information by
touching the appropriate tab. The
folder that is selected will be brought
to the front so it’s contents are
visable
™
consists of various
The main body of the screen is used
for description text, data, setpoints,
or keys (touch sensitive areas) The
double up arrows cause a page by
page scroll either up or down. The
single arrow causes a line by line
scroll to occur. At the end of the
screen, the appropriate scroll buttons
will disappear. Wrap around will not
occur.
The bottom of the screen is the
persistent area. It is present in all
screens and performs the following
functions. The left circular area is
used to reduce the contrast and
viewing angle of the display. The
right circular area is used to increase
the contrast and viewing angle of the
display. The contrast control will be
limited to avoid complete “light” or
complete “dark”, which would
potentially confuse an unfamiliar
user to thinking the display was
malfunctioning.
CVHE-SVU01E-EN
29
Operator
Interface
The Auto and Stop keys are used to
put the unit into the auto or stop
modes. Key selection is indicated by
being darkened (reverse video).
The Alarms button is to the right of
the Stop key. The Alarms button
appears only when alarm information
is present. The alarm blinks to draw
attention to the shutdown diagnostic
condition. Blinking is defined as
normal versus reverse video.
Pressing on the Alarms button takes
you to the corresponding screen.
Persistent keys, horizontal at the
bottom of the display, are those keys
that must be available for operation
regardless of the screen currently
being displayed. These keys are
critical for machine operation. The
Auto and Stop keys will be
presented as radio buttons within the
persistent key display area. The
selected key will be dark. The chiller
will stop when the Stop key is
touched, entering the stop sequence.
Pressing the “Immediate Stop”
button will cause the chiller to stop
right away.
The AUTO and STOP, take
precedence over the ENTER and
CANCEL keys. (While a setting is
being changed, AUTO and STOP
keys are recognized even if ENTER or
CANCEL has not been pressed.
Selecting the Auto key will enable the
chiller for active cooling ( if no
diagnostic is present.)
Chiller Stop Prevention/Inhibit
Feature
A new chiller “Stop prevention/
inhibit” feature allows a user to
prevent an inadvertent chiller stop
from the DynaView screen for those
chillers which are solely controlled
by the CH530.
How It Works
This new feature will be activated
after the service tech sets a variable
shut down timer in TechView to be
greater that 0 seconds and up to 20
seconds (i.e. 0 < Timer ± 20). Then,
when the user presses the ‘STOP’
button on the DynaView display and
initiates a chiller shutdown, a
window will now appear that
displays the “Unit Stop Information
Screen” as shown below.
TechView service tool is utilized to
enable this feature.
30
CVHE-SVU01E-EN
Loading...
+ 82 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.