Trane CVHE, CVHF, AFDH installation instructions

Installation Instructions
AFDH E-Frame Upgrade Adaptive Frequency Drive
For Tracer® AdaptiView™ Centrifugal Chiller Controllers
Direct Mount Transition Mount LiquiFlo Mou nt
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
May 2020
CVHE, CVHF, AFDH F0
SAFETY WARNING
AFDH-SVN004C-EN
Introduction
Read this manual thoroughly before operatingor servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation thatcould result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section 608) sets forth the requirements forhandling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYSreferto the appropriateSDSandOSHA/GHS (Global Harmonized System of Classification and Labeling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
© 2020 Trane AFDH-SVN004C-EN
Introduction
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
All Trane personnel must follow the company’s Environmental, Health and Safety (EHS) policies when performing work such as hot work, electrical, fall protection, lockout/tagout, refrigerant handling, etc. Where local regulations are more stringent than these policies, those regulations supersede these policies.
Non-Trane personnel should always follow local regulations.
WARNING
Refrigerant under Positive Pressure!
Failure to follow instructions below could result in an explosion which could result in death or serious injury or equipment damage. System contains oil and refrigerant and may be under positive pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
NOTICE
Stand-Mounted AFDH Supported by Equipment Room Floor!
Trane assumes no responsibility for equipment damage caused by the installation of an AFDH drive version that is specified as being incorrect for the application. A stand-mounted version of an AFDH drive is designed to be rigidly supported by the equipment room floor. Therefore, a stand-mounted AFDH drive is not recommended for use with a chiller that is equipped with spring-type vibration or seismic isolators. Trane recommends using a remote floor-mounted AFDH drive in this application.
Copyright
This document andthe information in itare the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise thispublication at anytime, and tomake changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Updated cover page figure.
Updated
Updated for HUB document numbers in General
Information chapter.
Updated mounting drawings in Pre-Installation
chapter.
Updated unit dimensional drawings in AFDH Drive
Package Specifications
Updated steps for Direct Mount Drive to Replace
Direct Mount Starter and mounting installation figures in Installation chapter.
Updated Trane default settings table in AFDH
Startup Procedure chapter.
Updated job specific settings and Trane default
settings tables in AFDH Startup Procedure.
Part number updated in table for Air filter in
Recommended Periodic Maintenance and Inspection chapter.
Model Number Descriptions chapter.
NOTICE
Incorrect Application! Adapting a Floor Stand Kit to an E-Frame AFDH!
The smallest model E-Frame drive weighs 1203 pounds. Any attempt to adapt the 50689890010 Floor Stand Kit to an E-Frame model AFDH drive will be considered an unsupported field modification to the drive unit design. Trane assumes no responsibility for the equipment damage caused by a stress or fatigue failure of the floor stand kit due to any use outside of its intended application.
AFDH-SVN004C-EN 3
Table of Contents
Model Number Descriptions .............. 5
Unit Model Number .................... 5
Nameplates ............................. 7
General Information ..................... 8
Other Literature Required Before Ordering or Installing an AFDH Upgrade
............. 8
Pre-Installation .......................... 9
Confirming the AFDH Package can be Properly
Installed .............................. 9
Installation Considerations for Unit-Mounted
AFDH Drives ........................ 9
Confirm Chiller Controller System Compatibil­ity with AFDH Drive
................... 12
Equipment Room Ambient Temperature and Environmental Considerations
......... 12
Chiller Upgrades ..................... 12
Electrical Cable Size Specifications for AFDH Drives
............................... 13
Requirements for Installation Technicians 14
Tools Required ....................... 14
Miscellaneous Field-Provided Material .. 14
Recommended Rigging and Lifting Proce-
dures for AFDH Drive Units ............ 15
Unit Lifting Points ................... 15
Alternative Lifting Method ............ 16
Center of Gravity Reference (FEA Method) 16
AFDH Drive Package Specifications ...... 18
Transition Mount Unit Dimensions ...... 19
LiquiFlo 1.0/1.5 Frame 4 Unit Dimensions 20
Drive Unit Weights and Heat Rejection .. 22
E-Frame Drive Unit Components ....... 23
Drive Unit Component Parts Housed within
the Custom Enclosure ............... 23
Additional Hardware Shipped with Tracer®
AdaptiView™ AFDH Packages ......... 32
Installation ............................. 34
Removal of Electrical Connections to the Ex­isting Starter
......................... 34
Mechanical Removal of Existing Unit-Mount­ed Starter
............................ 34
Mechanical Removal of Existing Unit-Mount-
ed LiquiFlo 1.0/1.5 Adaptive Frequency Drive
35
Mechanical Installation of a Unit-Mounted AFDH E-Frame
Transition Mount Drive to Replace Transition
Mount Starter .......................36
........................36
LiquiFlo Frame 3 Drive Replacement .....38
Direct Mount Drive to Replace Direct Mount Starter
...............................41
Linkage Bracket Installation for a Unit- Mount­ed Direct Mount E-Frame
Circuit Breaker Adjustment to Accommodate
Power Line Wiring ...................45
...............43
LiquiFlo 1.0/1.5 Frame 4 Replacement ....45
Electrical Installation (All AFDH Models) ..46
Install Shorting Buss Bars .............46
Input Power Wire Installation ..........47
Grounding AFDH Cabinet .............48
Output Wiring from the AFDH to the CTV Mo-
tor ................................48
Routing of Control Wiring to AFDH Cabinet .
49
Control Wiring Connections (Tracer® Adap­tiView™ Model AFDH Only)
.............49
Required Reprogramming of Tracer® Adap­tiView™ Controls.
Reprogramming Factory Installed Tracer® AdaptiView™ Controls (CTV Simplex Firm-
ware) ..............................50
.....................50
AFDH Startup Procedure .................51
Drive Settings .........................51
TR200 Drive Configuration ..............52
Troubleshooting .........................53
Startup Test Log .........................54
Recommended Periodic Maintenance and In­spection
................................55
Inspection Frequency ..................55
Visual Inspection—Power Removed ......55
Operational Inspection—Power Applied ..55
Air Filter ..............................55
Wiring Diagram Matrix ...................56
4 AFDH-SVN004C-EN
Model Number Descriptions
Unit Model Number
For service purposes, Trane®Model AFDH Air-Cooled drive upgrade packages are assigned a multiple character alphanumeric model number that preciselyidentifies each unit.
An explanation of the identification code that appears on the unit nameplate is shown below. Use of the service model number will enable the owner/operator, installing contractors, and service technicians to define theoperation, components, and options for any specific unit.
Refer to the model number printed on the nameplate when ordering replacement parts or requesting service.
Digits 1, 2, Adaptive Frequency Drive
AFD = Air Cool ed Ad apti ve Frequen cy Drive
Digit 4 — Development Sequence
H
Digits 5, 6, 7, 8 — Starter Size (Performance RLA rating)
Performance RLA = Performance RLA
Digit 9 — Chille r Vo ltage
D = 380V 60 Hz 3 Phase E = 440V 60 Hz 3 Phase F = 460V 60 Hz 3 Phase G = 480V 60 Hz 3 Phase H = 575V 60 Hz 3 Phase J = 600V 60 Hz 3 Phase R = 380V 50 Hz 3 Phase T = 400V 50 Hz 3 Phase U = 415V 50 Hz 3 Phase
Digits 10, 11— Design Sequence
** = Factory assigned
Digit 12 — N ew Sh ort Circuit Ra t ing
C = 35K Short Circuit A = 65K Short Circuit B = 100K Short Circuit
Digits 13, 14 — Maxim um RLA
1B = 190 Maximum RLA - 60 Hz
1C = 240 Maximum RLA - 60 Hz
0C = 302 Maximum RLA - 60 Hz
0D = 361 Maximum RLA - 60 Hz
0E = 443 Maximum RLA - 60 Hz
3 — Air Cooled
(460/480)
(460/480)
(460/480)
(460/480)
(460/480)
1A = 535 Maximum RLA - 60 Hz
(460/480)
0H = 590 Maximum RLA - 60 Hz
(460/480)
0J = 678 Maximum RLA - 60 Hz
(460/480)
0K = 730 Maximum RLA - 60 Hz
(460/480)
01 = 780 Maximum RLA - 60 Hz
(460/480)
02 = 890 Maximum RLA - 60 Hz
(460/480)
1D = 131 Maximum RLA - 60 Hz
(575/600)
1E = 155 Maximum RLA - 60 Hz
(575/600)
1F = 192 Maximum RLA - 60 Hz
(575/600)
0L = 242 Maximum RLA - 60 Hz
(575/600)
0M = 290 Maximum RLA - 60 Hz
(575/600)
0N = 344 Maximum RLA - 60 Hz
(575/600)
0P = 400 Maximum RLA - 60 Hz
(575/600)
0R = 450 Maximum RLA - 60 Hz
(575/600)
0T = 500 Maximum RLA - 60 Hz
(575/600)
0U = 570 Maximum RLA - 60 Hz
(575/600)
0V = 630 Maximum RLA - 60 Hz
(575/600)
03 = 729 Maximum RLA - 60 Hz
(575/600)
04 = 850 Maximum RLA - 60 Hz
(575/600)
1G = 212 Maximum RLA - 50 Hz
(380/400)
1H = 260 Maximum RLA - 50 Hz
(380/400)
0W = 315 Maximum RLA - 50 Hz
(380/400)
0X = 395 Maximum RLA - 50 Hz
(380/400)
0Y = 480 Maximum RLA - 50 Hz
(380/400)
0Z = 588 Maximum RLA - 50 Hz
(380/400)
05 = 658 Maximum RLA - 50 Hz
(380/400)
06 = 745 Maximum RLA - 50 Hz
(380/400)
07 = 800 Maximum RLA - 50 Hz
(380/400)
08 = 880 Maximum RLA - 50 Hz
(380/400)
09 = 990 Maximum RLA - 50 Hz
(380/400)
Digit 15 — Chille r Con t r ol Ty pe
3 = AdaptiView Controls Only
Digit 16 — Ag e ncy List i ng
1 = UL Listing (includes Canada and
California)
0 = No Listing
Digit 17 — AFD Typ e
C = NEMA 1 Upgrade Enclosure
Digit 18 — Mou n t ing Ty pe
C = Remote Mount A = Transition Mount L = LiquiFlo Mount P = Direct Mount 440E, 5000, 5800
Frame
T = Direct Mount 400 Frame
Digit 19 — AFD t o M otor Tr a n si t io n
0 = No Motor Transition A = 6" Sheetmetal Transition C = 12" Sheetmetal Transition B = 18" Sheetmetal Transition
Digit 20 — Fr a m e Size
D = D - Frame E = E - Frame
Digit 21 — Evaporator Shell Size
0 = For Transition, LiquiFlo, or
Remote 5 = 050S Short Evaporator Shell 6 = 050L Long Evaporator Shell 7 = 080S Short Evaporator Shell 8 = 080L Long Evaporator Shell A = 142E Extended Evaporator Shell B = 142M Medium Evaporator Shell C = 142L Long Evaporator Shell E = 210L Long Evaporator Shell
Digit 22 — Replacement Bracket for LF1.0/LF1.5
0 = No Bracket Needed 1 = Replacement Bracket Kit Needed
Digit 23
0
Digit 24 — Lug Sizes
0 = All Applicable Lugs N = Two Wire 3/0 - 250 KCmil B = Two Wire 400 - 500 KCmil C = Four Wire 4/0 - 400 KCmil D = Three Wire 4/0 - 400 KCmil E = Three Wire 500 - 750 KCmil F = Two Wire 2/0 - 250 KCmil G = One Wire 2/0 - 500 KCmil H = Three Wire 3/0 400 KCmil J = Two Wire 500 - 750 KCmil K = One Wire 200 - 500 KCmil L = Two Wire 3/0 - 350 KCmil M = Two Wire 2AWG - 500 KCmil P = Three Wire 4/0 - 500 KCmil Q = Four Wire 4/0 - 500 KCmil R = Four Wire 3/0 - 400 KCmil
Digit 25 — Jumper Bar Kit
0 = No Jumper Bars Required A = Bar Kit 1 (distance between holes
5.385 and dia. .812)
B = Bar Kit 2 (distance between holes
5.831 and dia. .812)
C = Bar Kit 3 (distance between holes
6.103 and dia. .812)
D = Bar Kit 4 (distance between holes
6.103 and dia. 1.187)
E = All Bars Included
Digits 26, 27 — Design Specials
00 = No Design Special
AFDH-SVN004C-EN 5
Model Number Descriptions
Digits 28, 29 — Harmonic Attenuation
00 = No Attenuation
Line Reactors
0A = Line /Load Reactor, 0.125mH, 320
Amps, NEMA1
0B = Line /Load Reactor, 0.105mH, 400
Amps, NEMA1
0C = Line /Load Reactor, 0.085mH, 500
Amps, NEMA1
0D = Line /Load Reactor, 0.065mH, 600
Amps, NEMA1
0E = Line /Load Reactor, 0.048mH, 750
Amps, NEMA1
0F = Line /Load Reactor, 0.042mH, 850
Amps, NEMA1
0G = Line /Load Reactor, 0.040mH, 900
Amps, NEMA1
0H = Line /Load Reactor, 0.0038mH,
1000 Amps, NEMA1
Advanced Filter
1A = Advanced Filter -208 Amp free
standing harmonic filter
1B = Advanced Filter -240 Amp free
standing harmonic filter
1C = Advanced Filter -320 Amp free
standing harmonic filter
1D = Advanced Filter -403 Amp free
standing harmonic filter
1E = Advanced Filter -482 Amp free
standing harmonic filter
1F = Advanced Filter -636 Amp free
standing harmonic filter
1G = Advanced Filter -786 Amp free
standing harmonic filter
1H = Advanced Filter -850 Amp free
standing harmonic filter
1J = Advanced Filter -1000 Amp free
standing harmonic filter
1K = Advanced Filter -1200 Amp free
standing harmonic filter
1L = Advanced Filter -208 Amp free
standing harmonic filter
1M = Advanced Filter -208 Amp free
standing harmonic filter
1N = Advanced Filter -208 Amp free
standing harmonic filter
1P = Advanced Filter -208 Amp free
standing harmonic filter
1Q = Advanced Filter -208 Amp free
standing harmonic filter
6 AFDH-SVN004C-EN
Nameplates
A nameplate is installed on each AFDH Air-Cooled Drive unit. Always provide the model number and serialnumber
Figure 1. Nameplate
that is printed on this nameplate when making warranty inquiries, ordering parts, or ordering literature for the unit.
AFDH-SVN004C-EN 7
General Information
This manual describes the procedures required to install NEMA 1 AFDH Air-Cooled Adaptive Frequency Drive package in place of existing direct mount starter, Transition mount starter, and LiquiFlo 1.0/1.5 drive on Trane CVHE, CVHF, CVHG model centrifugal chillers and retrofit LiquiFlo1.0/1.5 drives.This only applies to chillers with Tracer® AdaptiView™ controller.
E-Frame AFDH can be ordered in a unit-mounted configuration. Voltage options include 380/400V, 460/ 480V, and 575/600V.
The E-Frame units can be equipped with drive rating:
658 amps, 745 amps,800 amps, 880 amps,or 990 amps for 380V/400V.
590 amps, 678 amps,730 amps, 780 amps,or 890 amps for 460V/480V.
450 amps, 500 amps, 570 amps, 630 amps, 730 amps, or 850 amps for 575V/600V.
Note: Thefactory installed Tracer CH530 chiller controller
system will not support an AFDH Air-Cooled Adaptive Frequency drive. The controller system must be upgradedto Tracer® AdaptiView™before an AFDH
The AFDH series of upgrade air-cooled Adaptive Frequency installation on existing Trane chillers with CVHE, CVHF, or CVHG model centrifugal compressors. Trane makes no claim of suitability or performance regarding upgrade AFDH drives on older Trane centrifugal compressor models or on chillers made by other manufacturers. Although there may exist successful drive retrofits to these units, users are cautioned that Trane has not evaluated these installations. Accordingly, Trane cannot provide assurances regarding performance, reliability or suitability of upgrade AFDH installations to other than Trane model CVHE, CVHF, and CVHG compressors.
upgrade package can be installed.
drive packages are only intended for
HUB Document DOC-155220: MCT 10 Installation Instructions.docx (Danfoss VLT MotionControl Tools MCT 10 Set-up Software manual)
HUB Document DOC-179427: Creating a Project a Master File and Configuration for AFDH D & E Frame Drive.docx (AFDH D & E-Frame Drive Configuration Instructions Using MCT 10 Tool).
Other Literature Required Before Ordering or Installing an AFDH Upgrade
This manual must be used in conjunction with the following publications:
ECTV-PRB009*-EN, Engineering Bulletin, Chiller Upgrades Selection and Application Guideline for Aircooled Adaptive Frequency Drive Retrofit
BAS-SVP04*-EN, TR200 Programming Guide
CVRE-SVP01*-EN, Tracer® AdaptiView™ Panel Upgrade Programming Guide
CTV-SVP02*-EN, TracerTU Service Tool for Water-Cooled CenTraVac Chillers with Tracer® AdaptiView™ Controls Programming Guide
8 AFDH-SVN004C-EN
Pre-Installation
Confirming the AFDH Package can be Properly Installed
This chapter details potential interference fit problems, mechanical incompatibility situations, electrical code stipulations, and electrical conduit and wiring issues that can prevent the successful installationand/or operation of an AFDH upgrade drive package.
Installation Considerations for Unit­Mounted AFDH Drives
Important: Route Incoming Power Conduit to the Roof
of AFDH Cabinet! The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into the unit through the removable conduit connection cover located onthe left-hand rear corner of the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power conduit routed horizontally across the top of the starter, or connected to theside or to thebottom of the starter cabinet, an electrician will be required to reconfigure the conduit and wiring. Routing the incoming power conduit into the AFDH cabinet anywhere other than through the specified locationon the cabinet roof, will be considered an unsupported field modification to the cabinet design.
NOTICE
Route Incoming Power Conduit to the Roof of AFDH Cabinet!
Routing the incoming power conduit into the AFDH cabinet anywhere other than through the specified location on the cabinet roof, will be considered an unsupported field modification to the cabinet design. The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into the unit through the removable conduit connection cover located on the left-hand rear corner of the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power conduit routed horizontally across the top of the starter, or connected to the side or to the bottom of the starter cabinet, an electrician will be required to reconfigure the conduit and wiring.
Evaluate Space Available for Rigging/ Installing Unit-mounted AFDH
All models of the E-Frame AFDH unit-mounted upgrade drives are taller, wider, and deeper than the typical Wye Delta unit-mounted starter they are intended to replace. Accordingly any project should start with a careful evaluation on whether there is ample enough space to rig the AFDH into place and if any of the existing building piping and conduit will not interfere with its mounting.
AFDH-SVN004C-EN 9
Pre-Installation
Direct Mount. Transition Mount.
Figure 2. Comparison of direct-mounted AFDH to
typical unit-mounted starter
㼃㼅㻱㻌㻰㻱㻸㼀㻭㻌㻿㼀㻭㻾㼀㻱㻾
㻢㻜䇿㻌㼀㻌㼄㻌㻟㻤䇿㻌㼃㻌㼄㻌㻝㻠䇿㻌㻰
㼃㼅㻱㻌㻰㻱㻸㼀㻭㻌㻿㼀㻭㻾㼀㻱㻾㻌㼣㼕㼠㼔㻌㻼㻲㻯㻯㼟
㻢㻜䇿㻌㼀㻌㼄㻌㻠㻥䇿㻌㼃㻌㼄㻌㻝㻠䇿㻌㻰
㻰㻵㻾㻱㻯㼀㻌㻹㻻㼁㻺㼀㻵㻺㻳㻌㻭㻲㻰㻴
㻢㻜䇿㻌㼀㻌㼄㻌㻢㻢䇿㻌㼃㻌㼄㻌㻞㻟㻚㻞䇿㻌㻰
Figure 3. Open direct mount AFDH internal view
Figure 4. Comparison of transition-mounted AFDH to
typical unit-mounted starter
㼃㼅㻱㻌㻰㻱㻸㼀㻭㻌㻿㼀㻭㻾㼀㻱㻾
㻢㻜䇿㻌㼀㻌㼄㻌㻟㻤䇿㻌㼃㻌㼄㻌㻝㻠䇿㻌㻰
㼃㼅㻱㻌㻰㻱㻸㼀㻭㻌㻿㼀㻭㻾㼀㻱㻾㻌㼣㼕㼠㼔㻌㻼㻲㻯㻯㼟
㻢㻜䇿㻌㼀㻌㼄㻌㻠㻥䇿㻌㼃㻌㼄㻌㻝㻠䇿㻌㻰
㼀㻾㻭㻺㻿㻵㼀㻵㻻㻺㻭㻸㻌㻹㻻㼁㻺㼀㻵㻺㻳㻌㻭㻲㻰㻴
㻢㻤㻚㻢䇿㻌㼀㻌㼄㻌㻠㻤䇿㻌㼃㻌㼄㻌㻞㻟㻚㻞䇿㻌㻰
Figure 5. Open transition mount AFDH internal view
10 AFDH-SVN004C-EN
Pre-Installation
LiquidFlo.
Figure 6. Comparison of LiquiFlo AFDH to AFDB
LF MOUNTI NG AFDH
AFDB
9. 2" D EEPER THAN A FDB
AFDB STA RTER
68 .8" T X 6 4" W X 1 4" D
LF MOUNTI NG AFDH
68 .8" T X 6 4" W X 2 3.2 " D
Figure 7. Open LiquiFlo AFDH internal view
Important:
Verify
electrical disconnect switch installation height meets requirements of current NEC and/or local codes.Typical requirement is that switch can be no higher than 72 inchesabove the surface ofthe operator area floor or platform. Check the potential mounted height of the AFDH disconnect switch specially if the chiller has large shells or mounted on structural steel.
Other
factors that affect the space required to successfully install a stand-mounted AFDH drive include the clearance distances specified by the local electrical codes. Typical code regulations require an average of 36 inches of clearance from the panel to nonconducting surface.
surfaces and 47 inchesto a conducting
Check and confirm that when installed, the drive clearances will conform to all local codes. Do not forget to account for cabinet door swing clearances.
Note: Refer
Specifications,”
to manual section
for the dimensions and weights of
“AFDH Drive Package
all models of AFDH drives.
AFDH-SVN004C-EN 11
Pre-Installation
Confirm Chiller Controller System Compatibility with AFDH Drive
NOTICE
Excessive Cable Lengths Between AFDH Drive and Compressor Motor!
Trane assumes no responsibility for equipment damage caused by use of improper cable lengths. The variable frequency drive industry recommends that the length of the electrical cables connecting a drive unit to a motor should be kept to less than 250 feet to protect the motor from reflected voltage waves that can cause the motor to fail. Cable lengths that exceed 250 feet between the drive and the motor create the potential for damage to occur to the motor windings and/or insulation.
Before starting the process of installing the AFDH, first confirm that the existing chiller controller system has the hardware and/or software componentsrequired to make it compatible with an AFDH upgrade.
The controller systems that can accept an AFDH upgrade is Tracer® AdaptiView™.
Note: UC800 controller must be equipped with a
Tracer® AdaptiView™ software version released in January 2019 or newer. Upload the correct Tracer® AdaptiView™ softwareversion as required.
Table 1. Environmental conditions
Con d it io n Sp ecif ica tion
Operat ing Temper at ur e (i nsi de NEMA 1 e ncl osure)
Am bi ent Tem perat ur e (out sid e NEMA 1 e ncl osure)
St orage Temper at ur e (Am bient ) - 40° F to 1 49 ° F ( -40 °C t o 6 5° C)
Humi dity 5% t o 95 % (non -conden sin g)
32 ° F t o 131° F ( 0° C t o 55 ° C)
32 ° F t o 104° F ( 0° C t o 40 ° C)
Chiller Upgrades
The chiller condenserloop setpoint should bereset to fully exploit the energy savings possible with a upgrade AFDH drive. It is recommended to use Trane Option Analyzer or a similar software to determine the optimum setpoint.
Important: Under
low condenser water conditions, use of an oil recovery system is recommended. These systems are found on all Trane chillers built since 1985.
®
Equipment Room Ambient Temperature and Environmental Considerations
An air-conditioned equipment room is not a prerequisite for the installation and operation of NEMA 1 AFDH upgrade drive package.
However, be advised that all models of the AFDH air­cooled drives are not suitable for installation into equipment rooms where the ambient temperature conditions are expected to exceed either 104°F for a continuous 24-hour period, or where the potential maximum ambient temperatures can exceed 113°F.
If the ambient temperatures exceed either of these conditions, the potential existstotrigger a drive shutdown from an over temperature fault—effectively disabling the chiller until the drive temperature drops to the factory set, non-adjustable, safe temperature level that will allow the drive to be restarted.
If the ambient temperature routinely exceeds either of these conditions, the overall service life of the drive may be compromised. Verify the drive location will meet the environmental conditions specified in the table below.
12 AFDH-SVN004C-EN
Electrical Cable Size Specifications for AFDH Drives
Table 2. Input/output power wire cable sizes AFDH E-Frame drives (380V/400V)
3 8 0 V / 4 0 0 V E- Fr a m e AFDH Max im um a m p s 6 5 8 7 4 5 80 0 8 8 0 9 90
I N COM I NG PO W ER T O DRI V E CI R CUI T BREAKER: N um be r of Cabl e Lug s per Ph ase an d Ran ge of W ir e S iz es St an da rd Lu gs W ill Acce pt
I N COM I NG PO W ER T O DRI V E CI R CUI T BREAKER: N um be r of Cab le Lu gs p er Ph ase and Ran ge of W ire Size s Op tion al Lu gs W ill Acce pt
PH AS E W I RE BETW EEN D RI V E AN D CB: N u m ber of W ire Cabl e Pe r P ha se an d Siz e of F ac tor y I nstal le d W ires
OU TP UT P OW ER TO CO MP RES SOR M OT OR: N u m be r of W i r e Cabl e Pe r P ha se an d Siz e of F ac tor y I nstal le d W ires
Four w ir e
lu gs
4/ 0– 50 0
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e
lu gs
3/ 0 - 40 0 K Cmi l
Thr ee
4/ 0 DLO
wi re s
Thr ee
4/ 0 DLO
wi re s
Four w ir e
lu gs
4/ 0– 50 0
KCm il
Thr ee wire
lu gs
50 0- 750
KCMI
Four w ir e
lu gs
3/ 0- 400
KCm il
Thr ee
4/ 0 DLO
wi re s
Thr ee
4/ 0 DLO
wi re s
Four w ir e
lu gs
4/ 0– 50 0
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e
lu gs
3/ 0- 400
KCm il
Thr ee
31 3 MCM D LO
wi re s
Thr ee
31 3 MCM D LO
wi re s
Pre-Installation
Four w ir e
lu gs
4/ 0– 50 0
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e
lu gs
3/ 0- 400
KCm il
Thr ee
31 3 M CM D LO
wi r es
Thr ee
31 3 M CM D LO
wi r es
Four w ir e
lu gs
4/ 0– 50 0
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e
lu gs
3/ 0- 400
KCm il
Four
4/ 0 DLO
wi re s
Four
4/ 0 DLO
wi re s
Table 3. Input/output power wire cable sizes AFDH E-Frame drives (460V/480V)
4 6 0 V / 4 8 0 V E- Fr a m e AFDH Max im um a m p s 5 9 0 6 7 8 7 30 7 8 0 8 90
I N COM I NG PO W ER T O DRI V E CI R CUI T BREAKER: N um be r of Cabl e Lug s per Ph ase an d Ran ge of W ir e S iz es St an da rd Lu gs W ill Acce pt
I N COM I NG PO W ER T O DRI V E CI R CUI T BREAKER: N um be r of Cab le Lu gs p er Ph ase and Ran ge of W ire Size s Op tion al Lu gs W ill Acce pt
PH AS E W I RE BETW EEN D RI V E AN D CB: N u m ber of W ire Cabl e Pe r P ha se an d Siz e of F ac tor y I nstal le d W ires
OU TP UT P OW ER TO CO MP RES SOR M OT OR: N u m be r of W i r e Cabl e Pe r P ha se an d Siz e of F ac tor y I nstal le d W ires
Four w ir e
lu gs
4/ 0- 500
KCm ilKCmi l
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e
lu gs
3/ 0- 4 00 KCm il
Tw o
31 3 MCM D LO
wi re s
Tw o
31 3 MCM D LO
wi re s
Four w ir e
lu gs
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e
lu gs
3/ 0- 400
KCm il
Thr ee
4/ 0 DLO
wi re s
Thr ee
4/ 0 DLO
wi re s
Four w ir e
lu gs
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e
lu gs
3/ 0- 400
KCm il
Thr ee
4/ 0 DLO
wi re s
Thr ee
4/ 0 DLO
wi re s
Four w ir e
lu gs
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Fou r wi re
lu gs
3/ 0- 400
KCm il
Thr ee
31 3 MCM DLO
wi res
Thr ee
31 3 MCM DLO
wi re s
Four w ir e
lu gs
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Fou r wi re
lu gs
3/ 0- 400
KCm il
Thr ee
31 3 MCM D LO
wi re s
Thr ee
31 3 MCM D LO
wi re s
AFDH-SVN004C-EN 13
Pre-Installation
Table 4. Input/output power wire cable sizes AFDH E-Frame drives (575V/600V)
5 7 5 V / 6 0 0 V E- Fr a m e AFDH Max im um a m p s 4 5 0 5 0 0 57 0 6 3 0 7 3 0 8 50
I NCOM I N G P OW ER TO D RI V E CI R CUI T BR EAK ER: N u m b e r o f Ca b le Lu gs p e r P ha s e a n d Ra ng e of W ire Siz es Sta nd ar d Lugs Will Acc ep t
I NCOM I N G P OW ER TO D RI V E CI R CUI T BR EAK ER: N u m b e r o f Ca b le Lu gs p e r P ha s e a n d Ra n ge of W ir e Si zes Op t io nal Lu gs W il l Acce pt
PH AS E W I RE BETW EEN D RI V E AN D CB: N um be r o f W ir e Cab le Pe r Ph a se a n d Siz e o f Fa ct or y I n st a ll ed W ir e s
OU TP UT P OW ER TO COMP RES SOR M OTO R: N um be r o f W ir e Cab le Pe r Ph a se a n d Siz e o f Fa ct or y I n st a ll ed W ir e s
Fou r w ire l ugs 4/ 0 -5 00 KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e lug s 3/ 0- 4 0 0 K Cm il
Tw o
4/ 0 DLO
wi re s
Tw o
4/ 0 DLO
wi re s
Four w ir e lug s
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Fou r wi re lu gs
3/ 0- 400
KCm il
Tw o
4/ 0 DLO
wi re s
Tw o
4/ 0 DLO
wi re s
Four w ir e lugs
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Fou r wi re lu gs
3/ 0- 400
KCm il
Tw o
31 3 MCM D LO
wi re s
Tw o
31 3 MCM D LO
wi re s
Four wire lugs
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four wire lugs
3/ 0- 400
KCm il
Thr ee
4/ 0 D LO w ire s
Thr ee
4/ 0 DLO
wi re s
Four w ir e lugs
4/ 0- 500
KCm il
Thr ee wire
lu gs
50 0- 750
KCm il
Four w ir e lugs
3/ 0- 400
KCm il
Thr ee
4/ 0 DLO
wi re s
Thr ee
4/ 0 DLO
wi re s
Four wire lugs
Th re e w ire
50 0- 750
Four wire lugs
31 3 MCM DLO
31 3 MCM DLO
4/ 0- 500
KCm il
lu gs
KCm il
3/ 0- 400
KCm il
Thr ee
wi res
Thr ee
wi res
Requirements for Installation Technicians
To properly install an AFDH upgrade Adaptive Frequency Drive package, the technician must have a good working knowledge of the centrifugal chiller controller system involved in the application. Training is highly Recommended before beginning this upgrade.
Tools Required
Normal tools are required to perform the work. An HVAC service technician with a well-stocked tool chest should already have the majority of the normal tools needed for this job.
In addition to the normally carried service tools and hardware, the following is a partial list of specific field supplied hardware and software components and special tools that will also be required to perform the drive upgrade:
The
Important: A spreader bar will be required if the drive
Torque wrench capable of 40-170 foot-pounds.
A
Note: Refer to BAS-SVP04*-EN (Programming Guide:
appropriate lifting device or devices (including all necessary rigginghardware) with the capacity to safely lift up to 1500 lb.
unit will be hoisted into position using a single lifting device that is capable of making only a single-point lift.
PC or laptop computer equipped with the correct software tools for the chiller controller involved in the application.
– Tracer TU service software version 10.2.174 or
newer.
TR200) for full program parameter details and descriptions, and the instructions necessary to
operate the Local Control Panel(LCP) and program the necessary drive parameters.
Note: The most current CTV and CVR microprocessor
(MP) firmware files are included with the program files for the Tracer TU service software tools.
Type A to Type B USB cable to connect the computer
to a Tracer UC800 controller.
South
pole magnet screwdriver (TOL01343).
Miscellaneous Field-Provided Material
Some field provided material will be required to perform the drive upgrade. Apartial list of materialis provided here to help the technician to plan ahead and to avoid material shortages at the job site.
Self-adhesive
ties.
– Used to help “clean up” wiring runs during the
installation
Loctite
®
applications (Trane part number SEL00528).
– Used in applications where a pressure
transducer needs to be installed.
Direct Mount Drive install, have 3" X 3" Slotted
For
Shim Full Assortment Kit available.
– Used to shim between the enclosure and the
evaporator attached bracket.
cable tie mounting bases and cable
process.
554 thread sealant for refrigerant
14 AFDH-SVN004C-EN
Pre-Installation
Recommended Rigging and Lifting Procedures for AFDH Drive Units
WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury, and equipment or property-only damage. An AFDH cabinet assembly is top heavy. Test lift unit approximately 24 inches (61 cm) to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
Do not lift such that any angle is placed on the lifting tabs. They must only be lifted vertically.
Unit Lifting Points
Figure 8. Unit lifting points and center of gravity
1. Fact ory p rovided unit lift t ab s.
2. AFDH E- Fram e Un it f ro nt - to -rea r center of gr av it y.
Preferred Lifting Method
The preferred method for lifting an AFDH drive unit to
AFDH-SVN004C-EN 15
position it for installation, is to use an identical individual hoisting device at each lift point.
Pre-Installation
Figure 9. Preferred lifting method using two identical
individual hoists
Alternative Lifting Method
If it is only possible to use a single hoisting device to lift an AFDH drive unit to position it for installation, a spreader bar should be used to allow adjusting the rigging as necessary to balance the unit around its center-of-gravity to ensure full control of the unit during lifting.
Figure 10. Alternative lifting method using a single
hoist and spreader bar
Center of Gravity Reference (FEA Method)
Figure 11. Direct mount
24 .65
CENTER OF GRAVI TY
0
0
ORIGI NAL
29 .51
ORIGI NAL
CENTER OF GRAVI TY
0
CENTER OF GRAVI TY
Y
ORIGI NAL
X
Z
12 .24
ORIGI NAL 0 0 0
CENTER OF GRAVITY
XYZ
12 .24 24. 65 29. 51
16 AFDH-SVN004C-EN
Figure 12. Transition mount and LiquiFlo 1.0/1.5 frame 3
Pre-Installation
CENTER OF GRAVI TY
39 .5 7
0
ORI GINAL
0
27 .2 8
Figure 13. LiquiFlo 1.0/1.5 frame 4
ORI GINAL
CENTER OF GRAVI TY
0
10 .7 3
CENTER OF GRAVI TY
Y
ORI GINAL
X
Z
XYZ ORI GINAL 0 0 0 CENTER OF
GRAVI TY
10 .7 3 3 9. 57 27. 28
35 .83
0
ORIGI NAL
CENTER OF GRAVI TY
0
28 .53
ORIGI NAL
CENTER OF GRAVI TY
0
10 .38
Y
ORIGI NAL
X
Z
ORI GINAL 0 0 0 CENTER OF
GRAVI TY
CENTER OF GRAVI TY
XYZ
10 .38 3 5.8 3 28. 53
AFDH-SVN004C-EN 17
AFDH Drive Package Specifications
Direct Mount Unit Dimension
Figure 14. Top, front, and side view of E-Frame AFDH cabinet with dimensions - Direct mount drive
18 AFDH-SVN004C-EN
AFDH Drive Package Specifications
Transition Mount Unit Dimensions
Figure 15. Top, front, and side view of E-Frame AFDH cabinet with dimensions - Transition mount drive
AFDH-SVN004C-EN 19
AFDH Drive Package Specifications
LiquiFlo 1.0/1.5 Frame 4 Unit Dimensions
Figure 16. Top, front, and side view of LF 1/1.5 frame 4 E-Frame AFDH cabinet with dimensions - LiquiFlo drive
1. Z -bra cke t m ount in g stu ds ( each stu d = 3/ 8- 16 x 1. 75 i n. )
2. Two-piece a ccess do or co ver on t op of t he 9.3 in. x 1 4.9 in . in com ing po we r wi re cu to ut .
3. Elect ri cal di scon nect swit ch
20 AFDH-SVN004C-EN
AFDH Drive Package Specifications
Figure 17. Rear view of LF 1/1.5 frame 4 E-Frame AFDH cabinet with dimensions - LiquiFlo drive
58. 40
2
57. 62
1
1. Tor t er m inal access co ver. Size o f cut out i s 7 .2 i n. x 1 7. 6 in .
2. Cent er lin e of Z- br ack et m oun ti ng st uds
AFDH-SVN004C-EN 21
AFDH Drive Package Specifications
Drive Unit Weights and Heat Rejection
Table 5. AFDH E-Frame unit weights (380V/480V)
3 8 0 V / 4 8 0 V E- Fr a m e AF DH Max im um a m p s
Enclo su re Ty pe
Un it W eigh t ( lb )
Hea t Re jecti on ( Btu/ h )
Direct
6 5 8 7 4 5 8 0 0 8 8 0 9 9 0
Transit i
14 02 1 43 7. 5 15 16.2 14 02 143 7. 5 1516. 2 1402 1437.5 1 51 6. 2 1 45 2 14 87 .5 15 66 .2 14 52 1 48 7. 5 1 56 6. 2
24 30 6 28 08 4 3 06 32 32 98 4 3 85 39
on
LF Direct
Transit i
on
Table 6. AFDH E-Frame unit weights (460V/480V)
4 6 0 V / 4 8 0 V E- Fr a m e AF DH Max im um a m p s
Enclo su re Ty pe
Un it W eigh t ( lb )
Hea t Re jecti on ( Btu/ h )
Direct
5 9 0 6 7 8 7 3 0 78 0 89 0
Transit i
14 02 1437.5 1 516.2 14 02 1437.5 15 16 .2 1402 1437.5 1 51 6. 2 1 45 2 14 87 .5 15 66 .2 14 52 1 48 7.5 1 56 6. 2
20 83 5 2 43 23 27 85 6 27310 32 17 6
on
LF Direct
Transit i
on
Table 7. AFDH E-Frame unit weights (575V/600V)
5 7 5 V / 6 0 0 V E- Fr a m e AFDH M ax im um a m ps
Enclo su re Ty pe
Un it W eigh t ( lb )
Hea t Re jecti on ( Bt u / h)
5 7 5 V / 6 0 0 V E- Fr a m e AFDH M ax im um a m ps
Enclo su re Ty pe
Un it W eigh t ( lb )
Hea t Re jecti on ( Bt u / h)
Direct Transit ion LF Direct Transit ion LF Direct Transit ion LF
14 02 1437.5 151 6. 2 1402 1 43 7. 5 1 51 6. 2 14 02 1 43 7. 5 15 16 .2
Direct Transit ion LF Direct Transit ion LF Direct Transit ion LF
14 02 1437.5 151 6. 2 1452 14 87 .5 1566. 2 1 45 2 1 48 7. 5 1 56 6. 2
4 5 0 5 0 0 5 7 0
21 35 3 24 13 9 28 22 1
6 3 0 7 3 0 8 5 0
32 08 1 35 96 1 44 06 7
LF Direct
LF Direct
Transit i
on
Transit i
on
LF Direct
LF Direct
Transit i
on
Transit i
on
LF Direct
LF Direct
Transit i
on
Transit i
on
LF
LF
22 AFDH-SVN004C-EN
E-Frame Drive Unit Components
Drive Unit Component Parts Housed within the Custom Enclosure
Figure 18. Custom enclosure parts
AFDH Drive Package Specifications
E-Frame
AFDH-SVN004C-EN 23
D and E-Frame
AFDH Drive Package Specifications
Table 8. Custom enclosure parts: E-Frame 658 amps model drives (380V/400V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 3 80 V/ 4 00 V E- Fra m e 658 a m p s A FD H
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a n e X - Co de Pa r t
N u m b e r
Tr a ne Mn em oni c
N um be r
Su pp li er Pa rt
N um be r
Qu a nt ity
24 AFDH-SVN004C-EN
AFDH Drive Package Specifications
Table 10. Custom enclosure parts; E-Frame 800 amps model drives (380V/400V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 3 80 V/ 4 00 V E- Fr am e 8 0 0 am ps AFDH
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a n e X - Cod e Pa r t
N u m b e r
Tr a ne Mn em oni c
N um be r
Su pp li er Pa rt
N um be r
Qu a nt ity
AFDH-SVN004C-EN 25
AFDH Drive Package Specifications
Table 12. Custom enclosure parts: E-Frame 990 amps model drives (380V/400V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 3 80 V/ 4 00 V E- Fr am e 9 9 0 am ps AFDH
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a n e X - Co d e P a r t
N u m b e r
Tr a ne Mn em oni c
N um be r
Su pp li er Pa rt
N um be r
Qu a nt ity
26 AFDH-SVN004C-EN
AFDH Drive Package Specifications
Table 14. Custom enclosure parts; E-Frame 678 amps model drives (460V/480V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 4 60 V/ 4 80 V E- Fr am e 6 7 8 am ps AFDH
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a n e X - Co d e P a r t
N u m b e r
Tr a ne Mn em oni c
N um be r
Su pp li er Pa rt
N um be r
Qu a nt ity
AFDH-SVN004C-EN 27
AFDH Drive Package Specifications
Table 16. Custom enclosure parts; E-Frame 780 amps model drives (460V/480V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 4 60 V/ 4 80 V E- Fr am e 7 8 0 am ps AFDH
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a n e X - Co d e P a r t
N u m b e r
Tr a ne Mn em oni c
N um be r
Su pp li er Pa rt
N um be r
Qu a nt ity
28 AFDH-SVN004C-EN
AFDH Drive Package Specifications
Table 18. Custom enclosure parts; E-Frame 450 amps model drives (575V/600V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 5 75 V/ 6 00 V E- Fr am e 4 5 0 am ps AFDH
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a ne X- Code
Pa r t N um be r
Tr a ne Mn em oni c
N um be r
Su pp lie r Pa r t Nu m be r
Qu a nt ity
AFDH-SVN004C-EN 29
AFDH Drive Package Specifications
Table 20. Custom enclosure parts; E-Frame 570 amps model drives (575V/600V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 5 75 V/ 6 00 V E- Fr am e 5 7 0 am ps AFDH
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a n e X - Co d e Pa r t
N u m b e r
Tr a ne Mn em oni c
N um be r
Su pp li er Pa rt
N um be r
Qu a nt ity
30 AFDH-SVN004C-EN
AFDH Drive Package Specifications
Table 22. Custom enclosure parts; E-Frame 730 amps model drives (575V/600V)
Tr a ne Assem bly Pa r t N um be r s for all Op t io nal M ode l Ve rsion s of 5 75 V/ 6 00 V E- Fr am e 7 3 0 am ps AFDH
Figu re 1 8
Callo ut
Pa r t Descri pt ion
Tr a n e X - Co de Pa r t
N u m b er
Tr a ne Mn em oni c
N um be r
Su pp li er Pa rt
N um be r
Qu a nt ity
AFDH-SVN004C-EN 31
AFDH Drive Package Specifications
Additional Hardware Shipped with Tracer® AdaptiView™ AFDH Packages
Table 24. Tracer® AdaptiView™ miscellaneous hardware contents
Tr a ce r® Adap t iV ie w ™ Misce lla neo us H a rdw ar e Co m p on e nt Pa r ts Li st
Pa r t D escr ip t ion Qu a nti ty
Low pr essu re tr ans duce r; 0 –7 0 PSI A, I PC3 OUTPUT, 2 4 VDC, 0- 70 PSIA, 0 .2 5 - 1 8 NPTF 1 X13 79 03 620 90 T DR007 33
Bra nch in g cabl e; Male t o t wo Fem ale, 3 9. 37 inch es lon g 1 X19 05 16 22 02 0 CAB0 11 47
Ext en sion cabl e; Male t o Female, 3 9. 37 inch es lon g 1 X19 05 16 23 01 0 CAB0 11 49
Execut iv e Beige Pain t; 1 0 oz. ae ro sol can 1 X35 02 04 76 02 0 PAI 00 29 7
TR20 0 Prog ram mi ng Gu ide 1 BAS- SVP04 * -EN
UC80 0 to D rive Mod bus Cab le 1 50 71 23 90
Schem at ics 1 50 71 21 27
AFDH E-Fram e Upgr ade Ad apti ve Freque ncy D ri ve I nstallation m anual 1 AFDH- SVN0 04 * -EN
Tr a ne X- Code
Pa r t N um be r
Mne m onic
N um be r
Note: Shorting buss bars that could be required for a
upgrade AFDH drive installation are not included within the Tracer® AdaptiView™ miscellaneous
match the spacing and size of the compressor motor terminal lugs onthe specific chiller receiving the drive upgrade.
hardware package kit. Use the buss bars that best
Figure 19. Buss bars specifications: Tracer® AdaptiView™ hardware packages
1. Ex am pl e o f s hor t ing b uss bar s cont ai ned i n ki t BAR0177
2. Ex am pl e o f s hor t ing b uss bar s cont ai ned i n ki t BAR0163
3. Ex am pl e o f s hor t ing b uss bar s cont ai ned i n ki t BAR00176
4. Ex am pl e o f s hor t ing b uss bar s cont ai ned i n ki t BAR00165
32 AFDH-SVN004C-EN
Motor panel transition covers for Transition Mount and LiquiFlo
It is possible to order a complete new motor panel transition cover assembly if one is needed, either as part of the drive package order or separately if necessary.
The transition cover assembly when properly installed, lead sections thatemerge from the accesscutout at the back of a unit-mounted or stand-mounted AFDH drive, and connect to the compressor motor terminal board.
Table 25. Part numbers for motor paneltransition covers
prevents direct access to the output motor
AFDH Drive Package Specifications
Pa r t D escr ip t ion
6- inch m oto r panel t ra nsi ti on cov er
asse mbly
12 - inch motor pa nel t ransi tion cover
asse mbly
18 - inch motor pa nel t ransi tion cover
asse mbly
Tr a ne Pa r t
N um be r
50 68 20 00 01 00 COV02 94 6
50 68 59 44 01 00 COV03 20 3
50 68 19 75 01 00 COV02 94 5
Mne m onic N um be r
AFDH-SVN004C-EN 33
Installation
Removal of Electrical Connections to the Existing Starter
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Forvariable frequency drivesor other energy storing components provided by Trane or others, refer tothe appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN.
1. Turn off the main power disconnect to the chiller and then follow the correct lockout/tagout safety procedures to ensure that main power to the machine cannot be inadvertently restored.
a. For additional safety, also open all starter and
control in the open position.
b. Depending upon the starter type, proceed to verify
that no electrical power exists at either the starter breaker, or starter disconnect switch, or starter terminal block, and other starter components before starting the process of wiring removal.
2. Note the orientation of thepower cable connections to the starter terminal block.
a. Identify and clearly label the L1, L2, L3, and Ground
wiring
3. Identify and clearly labelthe power wiring cablesat the compressor motor terminal lugs T1, T2, T3, T4,T5, and T6 and then disconnect them.
a. Also disconnect the cables from their connection
points cabinet area to prevent them from getting in the way during the rest of the starter removal process.
b. Keep the motor terminal lugs. They will be reused
later in the installation.
4. At the starter cabinet, identify and clearly label the control starter panel.
a. Also identify and record the termination point of
each wire at the terminal block and then disconnect them.
panel disconnect switches and secure them
starter breaker, or starter disconnect switch, or
cables before they are disconnected.
on the starter and remove them from the
and communication wiring running to the
b. Remove and save the conduit fittings from the line,
load,
and control power entrances and exits on the
starter cabinet.
c. Remove and save the conduit top plate for possible
reuse
later in the installation.
Mechanical Removal of Existing Unit-Mounted Starter
WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury, and equipment or property-only damage. An AFDH cabinet assembly is top heavy. Test lift unit approximately 24 inches (61 cm) to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
1. Depending upon model type, a unit-mounted starter can weigh up to 750 pounds.
a. Verify that the intended lifting device and rigging
has the capacity to safely handle the load before hooking up to the designated lifting points on the starter unit.
Note: On
2. Using safe lifting practices, slowly begin taking up the slack
a. Tension the rigging only to the point that is
necessary to take up enough of the weight of the starter panel to enable loosening the bolts connecting the panel.
some existing starters, lifting tabs are spot­welded to the enclosure.These welds can break if not lifted straight up. To ensure a safe lift, Trane recommends drilling a hole and bolting the tabs to the enclosure to ensure a safe lift.
in the rigging.
34 AFDH-SVN004C-EN
Installation
3. While steadying the starter panel to prevent it from tipping forward, carefully begin removing the retaining bolts that connect it to the lower motor panel transition cover (Z-Bracket). See Transition Mount and LiquiFlo only. For Direct Mount remove
Note: The existing Z-bracket and transition cover on
4. Remove the bolts securing the bottom of the starter to the
5. Carefully remove the starter panel from the chiller and set it down in a safe location.
Important:
Do
to the evaporator shell as they will be reused!
Do angle-iron clips that were used to attach the starter panel tabs to the evaporator bracket as they will all be reused!
motor flange bolts.
Transition and LF 1/1.5 installations will be reused and do not need to be removed unless greater access is required to the motor terminals during drive installation.
brackets on the evaporator.
not cut off thestarter panel brackets thatare welded
not discard any of the nuts, bolts, washers, or the
Figure 42 for the
Mechanical Removal of Existing Unit-Mounted LiquiFlo 1.0/1.5 Adaptive Frequency Drive
WARNING
Heavy Objects!
Only attach cables (chains or slings) to the designated lifting points. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit could result in death or serious injury.
device and rigging hasthecapacity to safely handle the load before hooking up to the designated lifting points on the LiquiFlo drive.
Note: On
4. Using safe lifting practices, slowly begin taking up the
5. While steadying the starter panel to prevent it from
Note: The existing Z-bracket and transition cover will be
6. Remove the bolts securing the bottom of the LiquiFlo
7. Carefully remove the starter panel from the chiller and
Important:
8. Remove the bottom panel bracket from the starter
some existing LiquiFlo drives, lifting tabs are spot-welded to the enclosure. These weld scan break if not lifted straight up. To ensure a safe lift, Trane recommends drilling a hole and bolting the tabs to the enclosure to ensure a safe lift.
slack
in the rigging.Tension the rigging only to the point that is necessary to take upenough of the weight of the starter panel to enable loosening the bolts connecting the panel to the Z-bracket on the motor flange.
tipping retaining bolts that connect it to the Z-bracket.
drive to the brackets on the evaporator.
set
Do
Do not discard any of the nuts, bolts,washers,or the
panel brackets as shown in below figure.
forward, carefully begin removing the
reused and do not need to be removed unless greater access is required to the motor terminals during drive installation.
it down in a safe location.
not cut off the starter panel brackets that are welded to the evaporator shell as they will be reused!
angle-iron clips that were used to attach the starter panel tabs to the evaporator bracket as they will all be reused!
WARNING
Improper Unit Lift!
Most unit-mounted starter designs tend to be top heavy. Test lift unit to an approximate height of no greater than 24 inches to verify proper center of gravity lift point. To avoid dropping the unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property only damage.
1. Isolate the LiquiFlo drive water-side with isolation valves.
2. Cut and cap the LiquiFlo drive water-side connections.
3. Depending upon model type, a LiquiFlo drive can
up to 970pounds. Verify that the intended lifting
weigh
AFDH-SVN004C-EN 35
Installation
Figure 20. Removing bottom panel bracket from starter
panel brackets
Mechanical Installation of a Unit­Mounted AFDH E-Frame
Transition Mount Drive to Replace Transition Mount Starter
WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit in a LEVEL position could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury, and equipment or property-only damage. An AFDH cabinet assembly is top heavy. Test lift unit approximately 24 inches (61 cm) to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
WARNING
Unit Lowering!
Do not drop the drive cabinet assembly onto the evaporator mounting brackets when setting it into position! Dropping the cabinet onto the brackets could result in damage to the drive cabinet, the brackets, and/ or the evaporator shell.
36 AFDH-SVN004C-EN
Installation
Figure 21. Removal of Z-bracket weldment nuts
1. Z -bra cke t
2. We ldm e nt n ut s (4 t ot al on b ra cket , o nly 2 sh ow n) dr ill ou t or g ri nd of f flu sh.
1. Inspect the Z-bracket on the chiller motor flange. If the Z-bracket is equipped with weldment nuts, these nuts must either be ground off or drilled out to allow the M8X25 bolts on the back of the new drive cabinet to slide into the bracket at these locations.
2. Prepare lifting equipment and rigging.
a. Depending upon the model type, a unit-mounted
AFDH
can weigh up to 1400 pounds. Confirm the weight of theAFDH unit to be installed. For E-Frame units refer to Table.
b. Verify that the intended lifting device and rigging
has the capacity to safely handle the load before hooking up to thetwofactory provided lifting points on top of the cabinet assembly.
c. Use the appropriate rigging techniques to ensure
that
the cabinet assembly will be balanced about its center of gravity during lifting. Refer to
“Recommended Rigging and LiftingProcedures for AFDH Drive Units,”
.
Figure 22. Transition mounting
345
1
2
67
1. Panel m ou nt ing p lat e
2. Evap orator m oun tin g bracke t
3. Bolt
4. Lock washer
5. Wash er
6. Wash er
7. Nut
3. Using safe lifting practices, carefully liftthe cabinetand position it over the brackets on the evaporator.
4. Slowly lower the cabinet until the lower mounting bracket makes contact with the evaporator brackets but do not place the full weight of the cabinet onto the brackets at this time. Keep tension on the lift rigging to support the weight of the cabinet.
a. Adjust the position of the lower mounting bracket
as
necessary until the back of the cabinet is level and lined up against the Z-bracket, then attach the cabinet to the bracket using the kit hardware provided (screws for the motor terminal access). Shims may be necessary to level the lower mounting bracket. The front edgeof the evaporator brackets may need to be ground down to allow for more adjustment.
b. Secure the lower mounting bracket to the
evaporator
brackets with the bolts provided and previously used (if needed) to secure the old starter panel to them.
c. Ensure that all nuts are properly tightened at all
cabinet mounting points.
5. Confirm that the drive is firmly attached to all brackets is stable before slowly lowering the lifting device
and to slacken the rigging and remove it from the lifting points.
AFDH-SVN004C-EN 37
Installation
Figure 23. Position cabinet base over evaporator
brackets
Figure 24. Leveling the AFDH drive cabinet against the
Z-bracket
LiquiFlo Frame 3 Drive Replacement
WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. An AFDH cabinet assembly is top heavy. Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
WARNING
Unit Lowering!
Do not drop the drive cabinet assembly onto the evaporator mounting brackets when setting it into position! Dropping the cabinet onto the brackets could result in damage to the drive cabinet, the brackets, and/ or the evaporator shell.
1. The AFDH drive angle bracket has slotted holes to
allow for adjustment. Loosen the nuts to allow for adjustment. Make sure not to take the nuts completely out.
38 AFDH-SVN004C-EN
Installation
Figure 25. AFDH drive angle bracket adjustment Figure 26. Starter panel welded brackets markings to
trim
2. Mark to trim the starter panel brackets that are welded to the evaporator shell as they will interfere with the drive. Make sure to lineup the motor terminal access with the starter panel bracket and only trim the extra length. Refer to the below figures.
Figure 27. Starter panel brackets markings to trim extra
length
AFDH-SVN004C-EN 39
Installation
3. Use a saw-zaw to trim the starter panel brackets. Refer to the below figure.
Figure 28. Starter panel brackets during trimming
Figure 29. Starter panel brackets after trimming
of the new drive cabinet to slide into the bracket at these locations.
5. Prepare lifting equipment and rigging.
a. Depending upon the model type, a unit-mounted
AFDH
can weigh up to 1400 pounds. Confirm the weight of the AFDH drive. See
Table 7.
b. Verify that the intended lifting device and rigging
has the capacity to safely handle the load before hooking up to thetwofactory provided lifting points on top of the cabinet assembly.
c. Use the appropriate rigging techniques to ensure
that
the cabinet assembly will be balanced about its center of gravity during lifting. Refer to
“Recommended Rigging and LiftingProcedures for AFDH Drive Units,”
6. Implement safe lifting practices, carefully lift the cabinet the evaporator. Slowly lower the cabinet until the panel and angle bracket make contact with the evaporator brackets and rests on the brackets. The cabinet angle bracket is slotted if the AFDHneeds to be moved for adjustment. Do NOT place the full weight of the cabinet onto the brackets at this time.Keep tension on the lift rigging to support the weight of the cabinet.
7. Keep the upper part of the AFDH panel flush with the Z­bracket AFDH panel in position.
8. Verify that the Z-bracket is flush against the AFDH panel. See
9. Attach the Z-bracket at the top of the panel, make sure the AFDH panel is level.
10. Once the upper Z-bracket is secured, leave the lift rigging in place and attach a C-clamp to the cabinet angle bracket and starter panel brackets to hold the cabinet angle bracket in place. Refer to the below figure.
and position it over the mounting brackets on
face. Keep tensionon the lift riggingto hold the
Figure 24, p. 38.
.
Table 5, Table 6 and
4. Inspect the lower panel transition cover (Z-bracket) on the chiller motor flange. If the Z-bracket is equipped with weldment nuts, these nuts must either be ground off or drilled out to allow the M8X25 bolts on the back
40 AFDH-SVN004C-EN
Installation
Figure 30. Installing bolts on mounting brackets on the
evaporator and cabinet angle bracket
Direct Mount Drive to Replace Direct Mount Starter
WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. An AFDH cabinet assembly is top heavy. Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
11. Use a lubricateddrill bit (for M16bolt) and drill through the mounting brackets on the evaporator and cabinet angle bracket.
12. Bolt cabinet angle bracket to the evaporator support brackets with M16bolts, nuts, and washers (washer on top and bottom).
Figure 31. Cabinet angle bracket and evaporator
support bracket in position
AFDH-SVN004C-EN 41
Unit Lowering!
Do not drop the drive cabinet assembly onto the evaporator mounting brackets when setting it into position! Dropping the cabinet onto the brackets could result in damage to the drive cabinet, the brackets, and/ or the evaporator shell.
1. Prepare lifting equipment and rigging.
a. Depending upon the model type, a unit-mounted
can weigh up to 1400 pounds. Confirm the
AFDH weight of the AFDH drive. See
Table 7.
b. Verify that the intended lifting device and rigging
has
the capacity to safely handle the load before hooking up to thetwofactory provided lifting points on top of the cabinet assembly.
c. Use the appropriate rigging techniques to ensure
that
the cabinet assembly will be balanced about its center of gravity during lifting. Refer to
“Recommended Rigging and LiftingProcedures for AFDH Drive Units,”
2. Implement safe lifting practices, carefully lift the cabinet the evaporator.Slowly lower the cabinet untilthe AFDH panel flush and lineup with the motor terminal access bolt pattern.
and position it over the mounting brackets on
.
Table 5, Table 6 and
WARNING
Installation
3. Reuse the motor terminal access bolts and bolt the cabinet to the motor at the motor terminal. Do NOT place the full weight of the cabinet onto the brackets at this time. Keeptension on the liftrigging to support the weight of the cabinet.
4. The 400 frame motorrequiresan adapter plate tocover the excess gap at the AFDH drive motor terminal access opening.
1. 400 Mot or A dapt er
2. M12 Flat Wash er
3. M12 Hex Nut
4
2
4. Screw, M12 X 30MM Hex Cap
3
1
5. Make sure the cabinet is level and bolt the cabinet to the evaporator support brackets with the provided bolts, nuts, and washers.
6. Shim the space between the cabinet and the evaporator support brackets with 3”X 3”slotted shims. Place the shims slots around the bolts. Ease the tension on the lifting rigging, confirm the shims are snug, and then tighten the bolts to secure the cabinet on top of the evaporator support brackets.
42 AFDH-SVN004C-EN
Linkage Bracket Installation for a Unit- Mounted Direct Mount E-
Installation
WARNING
Unit Lowering!
Do not drop the drive cabinet assembly onto the evaporator mounting brackets when setting it into position! Dropping the cabinet onto the brackets could result in damage to the drive cabinet, the brackets, and/ or the evaporator shell.
1. Install drive on direct mount stand. Loosely attach bolts to motor flange. Tightly attach bolts to base. Leave lifting gantry connected to right side of AFD.
2. Install linkage bar to mounting handle with bolt, washers and nut, but do not fasten the bolts. Because linkage bar need to be adjusted to a proper direction when install into tube sheet.
Figure 32. Linkage subassembly installation
4
Frame
WARNING
Heavy Objects!
Failure to follow instructions below or properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift.
WARNING
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. An AFDH cabinet assembly is top heavy. Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level.
5
1. Mount in g Han dl e
2. Linkage bar
3. Bolt
4. Washer
5. Nut
3. Install linkage subassembly into tube sheet with bolt, spacers, plane washer and nut. Ensure bolt is tightened to 150 ft-lbs torque.
1
2
3
AFDH-SVN004C-EN 43
Installation
Figure 33. Install linkage subassembly into tube sheet
1
6
2
1. Linkage subassem bly
2. Tubesheet
3. Bolt
4. Spacers
5. Pla ne w ash er
6. Nut
4
3
5
4. Use gantry to lift right side of drive slightly over horizontal. Fixed linkage under the C channel from enclosure with bolts, washers and nuts, then tight the fasteners. At the same time, linkage bar will be set at a proper position then make sure all bolts including motor terminal bolts are tightened. Release tension from gantry and confirm that panel is setting correctly and not sagging.
44 AFDH-SVN004C-EN
Installation
Figure 34. Fixing linkage under the C channel
6
4
5
2
1
1. Link age su bassem bly
2. C chan nel
3. Nut
4. Washe rs
5. Bolt
6. Evapo rato r m oun ting bra cket
Circuit Breaker Adjustment to Accommodate Power Line Wiring
Adjust circuit breaker location to ease power line wiring installation. See picture below.
3
LiquiFlo 1.0/1.5 Frame 4 Replacement
Figure 35. LiquiFlo 1.0/1.5 frame 4 mounting
installation
1
34
AFDH-SVN004C-EN 45
5
2
1. Panel mou ntin g pl ate
2. Evapo rat or m oun ting br acket
3. Bolt
4. Washe r
5. Nut
Installation
Figure 36. Evaporator mounting bracket
3
1
2
1. Bracket
2. Suppor t
3. Str ip
Electrical Installation (All AFDH Models)
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Forvariable frequency drivesor other energy storing components provided by Trane or others, refer tothe appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN.
Install Shorting Buss Bars
Note: Shorting buss bars must be installed since the
AFDH is a three-lead device while the starter was a six-lead device. The wires must be connected (shorted) at both ends (at the AFDH and at the motor terminals) to ensure that there is no difference in potential between the two paired leads caused by different wire lengths. Some existing starters may have this done already.
1. Remove the motor terminal lug from all six terminals on
the compressor motor terminal board.
2. Install the three buss bars provided, one each between the following motor terminal pairs
a. T1 - T6
b. T2 - T4
c. T3 - T5
3. Reinstall all of the motor terminal lugs.
Figure 37. Buss bar installation on compressor motor
terminal board
WARNING
Conform to All Applicable National, State, and Local Electrical Codes!
Failure to follow all applicable codes could result in an arc flash event, electrocution, explosion, or fire, which could result in death or serious injury. Users MUST conform to all applicable national, state, and local electrical codes during the electrical installation and servicing of this product.
1. Co mpressor m ot or t er mina l board
2. Rem ove m ot or te rm inal l ugs ( fr om all 6 t erm inal s) .
3. I nst all shor t ing b uss bars across t he m oto r term inal p air s as shown .
Mot or t erm inal lugs r ein st all ed
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the equipment was not designed or qualified to accept other types of conductors.
46 AFDH-SVN004C-EN
Installation
Input Power Wire Installation
NOTICE
Route Incoming Power Conduit to the Roof of the AFDH Cabinet!
Routing the incoming power conduit into the AFDH cabinet anywhere other than through the specified location on the cabinet roof, will be considered an unsupported field modification to the cabinet design. The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into the unit through the removable conduit connection cover located on the left-hand rear corner of the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power conduit routed horizontally across the top of the starter, or connected to the side or to the bottom of the starter cabinet, an electrician will be required to reconfigure the conduit and wiring.
NOTICE
Keep Dirt, Debris, or Metal Filings From Entering the Drive Cabinet!
Failure to observe the appropriate precautions could result in damage to the electrical components when they are energized for the first time. Take all precautions necessary to prevent any dirt, debris, or metal filings from entering into the drive cabinet during the installation process.
Figure 38. Adjustable circuit breaker
Note: Adjustable circuit breaker to accommodate inlet
wires length.
Figure 39. Factory installed input disconnect circuit
breaker
Note: The L1, L2, and L3 input power leads for this unit
will be connected to a factory installed input disconnect circuit breaker inside of the drive cabinet.
1. To prevent metallic debris from falling into the drive, remove another location for marking and drilling the required wire routing holes for the input wire leads.
Notes:
These wire routing holes are the only entry points
In
a. Install the appropriate conduit hubs before
2. Route the input wire leads into thecabinet and connect them to circuit breaker terminals L1, L2, and L3.
a. The torque specification for these terminal
the access cover pieces and take them to
that should beused for bringing input power wiring into the drive cabinet.
some cases, the top plate with conduit hubsfrom the original starter may bereused andinstalledover the incoming wire access cut-out on the top of the cabinet, in place of the two-piece access covers.
reinstalling cabinet.
connections is 23 foot-pounds.
the access door pieces on top of the
1. I nput d isconnect ci rcu it b reaker
2. N am eplat e
3. I np ut po wer term ina ls. Term inal connections sh oul d be tor qued to 2 3 f oot · pounds
AFDH-SVN004C-EN 47
Installation
Grounding AFDH Cabinet
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
NOTICE
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the equipment was not designed or qualified to accept other types of conductors.
Run a suitable, unbroken, grounding conductor from the drive cabinet’s ground connection terminal to the motor’s ground terminal, and then on to earth ground.
Figure 40. Location of AFDH cabinet ground terminal
3. Attach the leads in pairs to the correct motor terminals (both
T1 leads to the T1 terminal, both T2 leads to the
T2 terminal, and both T3 leads to the T3 terminal).
a. Torque the 3/8-inch bolts at each terminal
connection to 44 foot-pounds.
Note: These power connections should be re-torqued to
44 foot-pounds after the first three to six months of operation and then on an annual basis thereafter.
4. Put the transition cover backin place and reseal itwhen finished.
Figure 41. Output wiring from AFDH to CTV motor
1. Out pu t m ot or leads co ming i n fr om t he right ha nd cabin et com p ar tm e nt ( d ri ve m od ul e) an d r out ed u p t o t h e mo t or t er m in al acce ss cut out
2. Mot or lead s ro ut ed th rou gh cabi net m ot or ter mi nal acc ess cu to ut
3. Tra nsiti on cover rem oved and Z br acke t b lanked ou t o f p hot o f or clarity
4. Fact ory i nst alled m otor leads ar e l on g enough to ex t end approxi m at ely 1 8- inch es out fr om the access cu t out
5. Att ach b ot h T1 m ot or leads t o com pre ssor m otor t ermi nal T1
6. Att ach b ot h T2 m ot or leads t o com pre ssor m otor t ermi nal T2
1. Cabin et g ro un d connect ion t er mina l
7. Att ach b ot h T3 m ot or leads t o com pre ssor m otor t ermi nal T3
Com pr essor m ot or t erm in al bo ard
Output Wiring from the AFDH to the CTV Motor
1. Remove the cover plate from the motor terminal access cutout on the back of the drive cabinet.
2. Feed the six motor leads through the back of the drive cabinet to the compressor motor terminal board.
48 AFDH-SVN004C-EN
Installation
Routing of Control Wiring to AFDH Cabinet
NOTICE
Route Incoming Power Conduit to the Roof of the AFDH Cabinet!
Routing the incoming power conduit into the AFDH cabinet anywhere other than through the specified location on the cabinet roof, will be considered an unsupported field modification to the cabinet design. The air-cooled AFDH drive is designed to have the incoming power conduit routed vertically into the unit through the removable conduit connection cover located on the left-hand rear corner of the cabinet roof. If the starter that is being replaced by the AFDH drive has the incoming power conduit routed horizontally across the top of the starter, or connected to the side or to the bottom of the starter cabinet, an electrician will be required to reconfigure the conduit and wiring.
Figure 42. Wiring connections to 2X1 terminal strip in AFDH
1
NOTICE
Keep Dirt, Debris, or Metal Filings From Entering the Drive Cabinet!
Failure to observe the appropriate precautions could result in damage to the electrical components when they are energized for the first time. Take all precautions necessary to prevent any dirt, debris, or metal filings from entering into the drive cabinet during the installation process.
Control Wiring Connections (Tracer® AdaptiView™ Model AFDH Only)
2
2X1
4
5
6
7
3
8
9
10
1A
2A
4B
9A
10A
3D
4C
34
5
67
8910
11
34
5
67
8910
11
205A
208A
209A
401B
402B
203A
203B
207A
207B
2X2
11
12
13
JUHHQ
EODFN
ZKLWH
12
3
12
3
410A
411A
412A
AFDH-SVN004C-EN 49
Installation
1. Fact ory i nst alled w ir in g
2. Field in st all ed wiri ng
3.
N ot e: Act ual wi re des ign ato rs ma y var y depe ndi ng up on th e sp ecif ic mo del/ v ers ion of chi lle r c ont ro l t hat t h e AFDH dr ive is bei ng lin ked w ith .
Please refer to th e o rig inal ch ille r cont ro l w iri ng dia gra ms and t he wir e d escr ipt ion s li sted in Fig ure Call out s 4 –11 if a n a ctu al wir e d esig nat or does n ot m at ch the one sh ow n in t hi s g raphi c.
4. 1 15VAC f eed t o chi lle r con trol p ane l
5. N eut ral fe ed to chil ler cont rol pa nel
6. N orma lly Closed term inal (2 ) on HPC (High Pre ssur e Cut out ) sw it ch ( 3S1 ) f or or igin al chiller with sta rt er modu le an d/ or no n- com m. D ri ve term ina l 4 is 1 15 VAC o nly.
Note: For ori gina l ch illers wit h a comm un icat ing dr ive , h igh pr essur e cutout w iring is 24V. For ori gina l ch illers wit h a st art er mod ule, high pressur e cu to ut
wi ri ng is 1 15V.
7. Fr om 1A7 J2-4 o il pu m p LLID
8. Fr om 1A7 J2-2 o il LLI D or cou ld co me f ro m t he 1X1 te rm inal b lock
9. a nd 1 0. No rm al close d term inal on HPC swi tch (3 S1) fo r or igi nal chil ler w it h co mm. Dri ve t er mina ls 9 and 1 0 ar e 2 4VDC only.
Note: For ori gin al ch iller s wi th a com muni cat in g d ri ve, high pr essu re cutout w ir ing is 24V.
11 . 12 . an d 13 . From UC80 0 I MC Modbu s lin k
Important: If the chiller does not already have a
condenser pressure transducer. Do not forget to install the condenser pressure
Required Reprogramming of Tracer® AdaptiView™ Controls.
transducer provided in the Tracer® AdaptiView™ Miscellaneous Hardware Package. The accurate pressure readings required by the chillercontrols to enable the most efficient operation of the chiller with the upgraded AFDH drive can only be effectively measured with a pressure transducer.
Reprogramming Factory Installed Tracer® AdaptiView™ Controls (CTV Simplex Firmware)
Important: Make sure your laptop is loaded with the
most current version of Tracer TU tool software so that you have the most up-to­date version of CTV MP firmware available to install into the UC800.
Note: CTV
MP firmware is always usedin factoryinstalled Tracer® AdaptiView™ control systems or in Tracer® AdaptiView™ display upgrades to factory installed CH530 control systems.
Table 26. UC800/Tracer® AdaptiView™ CTV parameter values with upgrade AFDH
Tr a cer TU Se rv ice S et poi nt s V ie w : Ad just ab le Fre qu en cy Dri ve S et poi nts
AF Con trol Aut o, Fixed Aut o Aut o
ReOpt imi zat io n Sensit iv it y 0– 10 0% 2 0 20
Tr a cer TU Fi eld St a rt up V ie w : Ad just ab le Fre qu en cy Dri ve
AFD Tem pe rat ure Limi t Set poin t 0 .0 - 36 0. 0 21 2. 0 21 2. 0
Max im um Frequ ency 3 0– 60 H z 60 60
Min im um Fre quency 30 –6 0 Hz 3 8 38
Sur ge Speed I ncr ease 0– 2 Hz 1 1
Tr a cer TU Co nf ig ura t io n Vi ew : Mai n R an ge De fau lt Se tti ng Re com m en ded Sett ing
Uni t Type ( MODL) CVHE, CVHF, CVHG, CVGF CVHE
Tr a cer TU Co nf ig ura t io n Vi ew : UC8 00
St arter Type Not App licable Uni t Mou nt Wye -D elt a TR200 Modbu s AFD
I m pel ler D iam ete r (CPI M) 50 - 34 5 27 5 Enter CPI M f ro m Un it Na m epl at e
Tr a cer TU Co nf ig ura t io n Vi ew : St art er Ra nge Def ault Se tti ng Re com m end ed S et ting
Uni t Lin e Volt age 18 0– 15 00 0V 46 0 Ent er f rom Unit Name pla te
Mot or NP Pow er 40 00 k W 400 Enter fr om Unit Nam epla te
Mot or Tem perat ure Pro te ction Type 75 Oh m @75 F, 100 Ohm @ 0 C 75 ohm 7 5 oh m
Ra nge Def ault Se tti ng Re com m end ed S et ting
Ra nge Def ault Se tti ng Re com m end ed S et ting
Ent er Chill er Model fr om Unit Name plat e
( Not e: on ly CVHE or CVHF a pply)
Ra nge Def ault Se tti ng Re com m end ed S et ting
50 AFDH-SVN004C-EN
AFDH Startup Procedure
Follow the procedure below when starting the water chiller and drive.
1. The CenTraVac™ chiller control starts, stops, and monitors all unit and AFDH run functions.
Complete all items on the commissioningchecklistand in the startup procedures for the CVHE and CVHF as defined in the operation maintenance manual or other applicable manual.
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Forvariable frequency drivesor other energy storing components provided by Trane or others, refer tothe appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged.
DC bus capacitors retain hazardous voltages after input power has been disconnected. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. after disconnecting input power, wait ten (10) minutes for the dc capacitors to discharge and then check the voltage with a voltmeter to ensure the dc bus capacitors are discharged before touching any internal components. Failure to observe this precaution could result in death or serious injury.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN.
2. Check the following on the drive:
a. Make sure input wire sizing to the drive is sized
correctly connected as noted in this manual.
b. Check the drive ground connection; check cabinet
wire routing and grounding.
3. Check all drive wiring and connections in the drive to make damage.
4. AFDH control checkout:
a. CHILLER Setpoints: As with any new chiller, first
check out all setpoints for the chiller.
b. AFD Setpoints: Check out all AFD setpoints (refer to
“Drive Settings,”).
c. AFD Configuration: Verify the correctness of the
“Sales Order” specific setpoints in the “Starter Configurations for AFDStarters.”Thesesettingsare specific to unit/motor combination in the drive. All of the remaining settings are factory-determined
based on unit nameplate voltage, and
sure they are tight and free of any shipping
default setpoints that are the same on all AFDH air­cooled drives.
Note: If
5. When ready, start the drive from the chiller display.
6. Document all information on the startup log.
the set values do not match, contact the local Trane Service agency first, or the Global Parts Technical Service Department. The correct values are listed on the unit nameplate shipped with each unit.
Drive Settings
Important: Any AFDH drive module menu parameter
numbers not listed in this manual are non­Trane specific program parameters. All non-Trane specific program parameter values have been set by the manufacturer before shipment, to provide optimum drive performance. Under no circumstances should any of the pre-set values in these menu parameters be changed unless specifically directed to do so by a factory engineer or a factory technical support person.
Note: Please
For additional information, refer to the programming manual manual includes a detailed section that discusses accessing the parameters in the drive.
This process is summarized briefly below:
1. To access the parameters, press the Main Menu key.
2. If required, enter the password (999).
3. To select a parameter group, use the up/down arrow keys the Enter key to access that group.
4. Use the up/down arrow keys to access the parameter number, and then press the OK key.
5. Use the up/down arrow keys to change the parameter, and
refer to the BAS-SVP04*-EN (
Guide: TR200
program parameter details and descriptions, and the instructions necessary to operate the Local Control Panel (LCP) and program the necessary drive parameters.
that is shipped with the drive. The programming
to highlight the parameter group, and then press
then press the OK key to change the setting.
), or the most recent version, for full
Programming
AFDH-SVN004C-EN 51
AFDH Startup Procedure
TR200 Drive Configuration
Note: Technician may elect to configure the drive by
using Danfoss VLT Motion Control tool MCT10. Follow the following steps:
1. If the TDU Drive Utility Program is installed on your laptop: You must first uninstall the TDU Drive Utility in order to install the MCT 10 software.
2. Install MCT 10 toll: HUB Document DOC-155220: MCT 10 Installation Instructions.docx (Danfoss VLT Motion Control Tools MCT 10 Set-up Software manual)
3. Configure the TR200 drive using MCT 10 tool: HUB Document DOC-179427: Creating a Project a Master File and Configuration for AFDH D & E-Frame Drive.docx (AFDH D & E-Frame Drive Configuration Instructions Using MCT 10 Tool).
To manually configuring the drive, you should ensure the drive
is at the default sittings by performing the following
procedures to reset the drive:
1. Disconnect power to the drive, and wait for the display to shut down.
2. While powering up the drive, press and hold the following
3. After 5 seconds, release the keys.
After the drive is reset, reprogram the items listed in the below
Table 27. Job specific settings
keys: Status, Main, and OK.
tables.
Table 28. Trane default settings (continued)
Gr ou p Par a m e ter D escr ip t io n Se tti ng
1 03 Tor que chara cteri stics Var iable t or que ( 1)
1 22 Mot or v olta ge Nam epl at e vol tage
1 23 Mot or f re qu ency 6 0 Hz
1 39 Mot or p ole s Poles (2)
3 02 Min im um Refe rence 30 Hz
3 03 Max im um Refere nce 6 0 Hz
3 15 Referen ce 1 Sou rce No Funct ion
3 16 Referen ce 2 Sou rce No Funct ion
3 41 Ram p 1 ram p u p tim e 1 0 sec
3 42 Ram p 2 ram p d ow n tim e 20 sec
4 12 Mot or speed l ow li m it 3 8 Hz
4 14 Mot or speed h ig h lim it 60 Hz
5 12 Ter m in al 27 Digit al Input No operat ion ( 0)
5 40. 1 Funct ion Rel ay Running
8 01 Contr ol Sit e Contr olwor d only (2 )
8 03 Contr ol Tim eout Tim e 1 5 sec
8 0 4 Con tr ol Ti m eou t Fun ct io n St op
8 30 Prot ocol Modb us RTU
8 31 Add re ss 3
8 32 Bau d Rate 38 40 0 Bau d
8 33 Parity / St op Bi ts No Parity, 1 St op Bit
836
14 21 Aut om at ic Rest ar t Tim e 1 0 sec
Max im um Response Del ay
10 0
Gr ou p Pa r am ete r Descripti on Va lue
1 20 Mo tor kW Set to name pla te NMKW
1 24 Mo tor Cur re nt Set t o nam epla te NMRA
1 25 Mo tor Nom inal sp eed Set t o nam eplat e TRPM
4 16 Tor que l im it m ode Set t o ma xi mum
4 18 Cu rr en t limi t Set t o m aximu m
Table 28. Trane default settings
Gr ou p Par a m e ter D escr ip t io n Se tti ng
0 20 Displa y lin e 1. 1 sm all
0 21 Displa y lin e 1. 2 sm all
0 22 Displa y lin e 1. 3 sm all
0 23 Displa y lin e 2 lar ge
0 24 Displa y lin e 3 lar ge Fr eq Hz (1613)
032
0 40 Han d on key Disabl ed ( 0)
0 41 Off k ey Disab led ( 0)
0 60 Main Menu p assw or d 9 99
061
Cust om Read out Max Valu e
Access t o m ain m enu w / o passw or d
DC lin k volt age ( 16 30 )
Mot or Cu rr en t ( 16 14 )
Heat sin k tem p ( 16 34 )
I np ut Pow er Kw ( 16 10 )
Nam epla te NMRA
LCP; Read on ly ( 1)
After all settings are made save a copy chiller service report for future use.Recommend that Trane Techsload to ComfortSite by chiller serial number.
52 AFDH-SVN004C-EN
Troubleshooting
The drive displays three types of faults:
Warning
A warning oralarm is signaledby the LEDson the front of the AFD by a code on the LCP.
A warning indicates a condition that may require attention or a trend that may eventually require attention, and will remain active until the cause is no longer present. Under some circumstances, motor operation may continue.
Trip
A trip is the action when an alarm has appeared. The trip removes power to the motor and, after the condition has been cleared, can be reset by pressing the Reset button. The event that caused an alarm cannot damage the AFD or cause a dangerous condition.
After its cause has been rectified, an alarm must be reset
to restart operation.
Trip Lock
A trip lock is an action when an alarm occurs that may
damage to the AFD or equipment. Power is
cause removed from the motor, and a trip lock can only be reset after the condition is cleared by cycling power.
Once the problem has been rectified, only the alarm continues flashing until the AFD is reset.
2. Collect chiller information.
a. Note the following chiller information:
Operating
or 75% load etc.)
Number of chiller starts, and hours of operation.
Time
<1 hour, >1 hour, etc.)
b. What was the chiller state at the time of the failure?
(Chiller starting? Running low load? Running full load? etc.)
c. Record the chiller’s sales order and serial numbers,
and
the drive’s serial and model numbers.
3. Troubleshooting
a. Measure and record the DC bus (via the Local
Control
b. Check ALL wiring (tightness, ribbon cables fully
seated, proper phasing, etc.)
c. Refer to the Danfoss manuals for further
troubleshooting information.
mode and any sub-mode (i.e., 100%
since last diagnosticshutdown (<1 minute,
Panel [LCP]).
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Forvariable frequency drivesor other energy storing components provided by Trane or others, refer tothe appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN.
1. Tracer® AdaptiView™ only: Collect alarm and
parameter information.
a. DO NOT cycle unit power or reset the controls.
Leave the AFD and the UC800 in their present states.
b. Record all UC800 active and historic alarms. Make
a
full chiller service report.
c. Document and check all applicable parameter
settings. This information can be verified off of the chiller nameplate, and by referring to this manual..
AFDH-SVN004C-EN 53
Startup Test Log
Water-Cooled CenTraVac Chiller with Tracer® AdaptiView™ Control and Adjustable Frequency Drive (AFD) Starter
Job Nam e AFD Se rial Num ber Job Locati on AFD Model Num be r Sales Order Numb er Shi p Dat e Chiller Ser ial Nu m ber St art Dat e Chiller Model Num ber
54 AFDH-SVN004C-EN
Recommended Periodic Maintenance and Inspection
Inspection Frequency
Perform inspections outlined below every 1 to 12 months, depending on operating environment.
Visual Inspection—Power Removed
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/ tagout procedures to ensure the power cannot be inadvertently energized. Forvariable frequency drivesor other energy storing components provided by Trane or others, refer tothe appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with a CAT III or IV voltmeter rated per NFPA 70E that all capacitors have discharged.
For additional information regarding the safe discharge of capacitors, see PROD-SVB06*-EN.
1. Ensure the door interlocks are present and working.
2. Verify the safety ground connections to the door are securely connected.
panels
3. Inspect power wire cables and devices to assure no
abrasion is occurring from vibrations against chassis of cabinets, or other edges.
4. Ensure the drive interior and exterior is clear of any
dust or debris. Fans, circuit boards, vents etc. must be clean. Only use a vacuum for cleaning. DO NOT use compressed air. Review actual operation environment against specs if any concern.
5. Inspect the interior of the drive for any signs of
moisture
6. Visually inspect alldrive components andwiring. Look
for capacitors, discolored reactors or inductors, broken pre-charge resistors, smoke or arc trails on MOVs and capacitors, etc.)
7. Closely inspect the motor terminal board for any signs
of
8. Check ALL cable/lug/terminal connections inside the
drive enclosure. Ensure all are clean and tight, and not rubbing against each other anywhere.
entry or leakage.
signs of heat or failure (look for swelled or leaking
leakage, arcing, etc.
Operational Inspection—Power Applied
WARNING
Live Electrical Components!
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks.
1. Verify the drive cabinet cooling fans are operating.
This should be done from outside the enclosure, by looking into the cabinet at door and cabinet vents, to avoid electrical hazards.
Note: The power module fan comes on with power.
Other fans cycle with drive operation.
2. Check historic fault codes using Local Control Panel (LCP) connected to the AFD.
3. Check configuration settings and confirm all proper settings are still present in the controls.
4. Review the diagnostic history.
5. Make Chiller Service report to document all setpoints.
6. Check the UC800 alarm histories for any indications of operational
To properly diagnose service issues for Adaptive Frequency drives for centrifugal chillers equipped with AFDH starters. AllUC800 chillers willbe equipped withthe LCP as standard on the drive power module. This is for service only and NEVER for machine operation.
problems.
Air Filter
Clean or replace filter every 1 to 12 months, depending on operating environment.
Filt er Descri pti on Pa rt Num be r
Direct Mount D rive Air Fil ter FLR08 81 4
Transit ion Mo un t Dr iv e Air Filt er FLR08814
Liq uiFlo 1 .0 / 1.5 D rive Air Filter FLR08814
AFDH-SVN004C-EN 55
Wiring Diagram Matrix
W iri ng Diag r am N um be r
50 71 21 27 Cen TraVac™ W ir ing D iag ram wit h Dan foss
Note: Wir ing d iag rams are ava ila ble via e-Libr ary.
Descripti on
Ada pt iv e Fr equen cy Dr iv e
56 AFDH-SVN004C-EN
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor environments for commercial and residential applications. For more information, please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.
AFDH-SVN004C-EN 11 May 2020
Supersedes AFDH-SVN004B-EN (Jan 2020)
©2020 Trane
Loading...