Trane CVGF-SVN02B-E4, CVGF400, CVGF1000, CVGF500, CVGF650 Installation Manual

...
Installation Manual
Gear-Driven Centrifugal Water­Cooled Liquid Chillers
CVGF-SVN02B-E4
X39640686020
CVGF-SVN02B-E4
© 2004 American Standard Inc. All rights reserved.
Warnings and Cautions
NOTICE: Warnings and Cautions appear at appropriate sections throughout this manual.
Read these carefully.
WARNING
- Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION - Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION - Indicates a situation that may result in equipment or property-damage-only
accidents.
CVGF-SVN02B-E4
3
Contents
Warnings and Cautions
General Information
Installation: Mechanical
Installation: Electrical
2
4
32
56
CVGF-SVN02B-E4
4
General Information
Conversion Chart
SI Multiply by METRIC psi 6.89 kPa psi .069 Bar psi .070 kg/cm²
degrees °F (F-32)×5/9 Degrees C
pound-ft 1.36 Nm pound-ft 0.138 kg-m pound-ft 0.0014 kN-m
gpm (US) 0.063 L/s gpm (US) 6.309 m³/sec gpm (US) 63.09 cm³/sec
in-H²O 0.249 kPa in-H²O 0.0361 psi in-H²O 0.0736 in-Hg
inches 25.4 mm inches 2.54 cm feet 0.305 meters feet² 0.093 meters²
Microns 0.001 mm Hg
Safety Control Settings Chart
Control Settings I-P Settings SI Oil pressure control Cut-in 12 psi, Cut-in 151 kPa,
Cut-out 9 psi Cut-out 124 kPa High pressure control Cut-out 195 psi Cut-out 1344 kPa High oil temperature Cut-out 165°F Cut-out 74°C Low oil temperature Cut-out 5°F below set point Cut-out 2.8°C below set point High motor temperature Cut-out 265°F ± 15°F Cut-out 130°C ± 8°C
Oil Chart
USA Europe Oil 0037 Oil 021E Oil 0049 Oil 0020E
MODEL: CVGF500 MODEL NO: CVGF0500RA0U33809405C1B5C1C23A1A201E3AA0 SERIAL NO: S.O. NO:
ELECTRICAL CHARACTERISTICS: RATED VOLTAGE: 380 VOLTS 50HZ 3PH NAMEPLATE NMKW: 338 kW VOLTAGE UTILIZATION RANGE: 345- 422 VAC MINIMUM CIRCUIT AMPACITY: 726 AMPS MAXIMUM FUSE: 1200 AMPS MAXIMUM CIRCUIT BREAKER 1200 AMPS MAXIMUM OVERLOAD TRIP: 617 AMPS
MAX MAX
VOLTS-AC HZ PH RLA LRAY LRAD COMPRESSOR MOTOR 380 50 3 577 1048 3286 OIL PUMP MOTOR 380 50 31.43 FLA OIL TANK HEATER 115 50 1000 WATTS TOTAL CONTROL CIRCUIT 115 50 1500 VA MAX
WHEN MOTOR CONTROLLER PROVIDED BY OTHERS TRANE ENGINEERING SPEC. S6516-0360 APPLIES
GENERAL CHARACTERISTICS: REFRIGERANT SYSTEM TO BE FIELD CHARGED ACTUALLY CHARGED WITH 340 KG OF R-134A WITH KG OF R-134A
MAXIMUM REFRIGERANT WORKING PRESSURE HI SIDE 15.2 BAR LOW SIDE 15.2 BAR
FACTORY TEST PRESSURE HI SIDE 16.7 BAR LOW SIDE 16.7 BAR FIELD LEAK TEST PRESSURE 82.50 BAR MAX.
TESTED AT BAR LEAK TEST AND CHARGING SPECIFICATION ARE SUPPLIED IN CONTROL PANEL (SERVICE LITERATURE MANUAL)
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 4686834 4689967 4715190 5056032
5058031 5434738 5563489 5836382 SERVICE LITERATURE INSTALLATION, OPERATION AND MAINTENANCE MANUAL: CVGF-SVN02A-EN AND CVGF-SVU02A-EN
“FOR INSTALLATION REQUIREMENTS, USE ELECTRICAL CHARACTERISTICS NOT PRODUCT DESCRIPTION”
PRODUCT DESCRIPTION:
MODL CVGF DSEQ A0 NTON 500 VOLT 380 HRTZ 50 CPKW 338 CPIM 940 EVSZ 500 EVBS C EVTB TE25 EFLD WATE EVWB NM15 EVWP 2 EVCO FLGE EVWA RERE CDSZ 500 CDBS C CDTB TE28 CFLD WATE CDWB NM15 CDCO FLGE CDWA RERE ORSZ 23 AGLT UL SPKGEXPS INSL YES OPTM YES WVUO YES TRMM TRMS LCLD CLDC LANG ENGL SRTY USTR SRRL 952 PNCO DISC TEST PTR3
Figure 1. Typical unit nameplate
CVGF-SVN02B-E4
Literature Change History
CVGF-SVX001-E4 (July 2000)
This manual describes the installation, operation, and maintenance of CVGF units.
CVGF-SVN02A-E4 (2002)
Replaces CVGF-SVX001-E4.
About this Manual
This manual describes proper installation of Model CVGF, 50 Hz and 60 Hz chillers with the Tracer CH530 Controls platform. See Figures 2 and 3 for an illustration of a CVGF Centrifugal Chiller with the Tracer CH530 Unit Control Panel.
These chillers are equipped with microcomputer-based control systems. A careful review of this information along with the submittal package provided for the unit will assure that the chiller is correctly installed.
Unit Identification ­Nameplates
When the unit arrives, compare all nameplate data with order, submittal and shipping information. A typical unit nameplate is shown in Figure 1.
5
General Information
CVGF-SVN02B-E4
Unit Nameplates
The CVGF unit nameplate (Figure 2 shows the nameplate location) is applied to the exterior surface of the control panel. The starter nameplate is located inside the starter panel.
The unit nameplate provides the following information:
• Unit model
• Unit serial number
• Unit device number - identifies unit electrical requirements
- Lists correct operating charges of HFC-134a and lubrication oil
- Lists unit test pressures and maximum working pressures
The starter nameplate provides the following information:
• Panel model number
• Rated load amps
• Voltage
• Electrical characteristics ­starter type, wiring
• Options included
Unit Inspection
When the unit is delivered, verify that it is the correct unit and that it is properly equipped.
Inspect all exterior components for visible damage. Report any apparent damage or material shortage to the carrier and make a “unit damage” notation on the carrier’s delivery receipt. Specify the extent and type of damage found and notify the appropriate Trane Sales Office.
Do not proceed with installation of a damaged unit without sales office approval.
Inspection Checklist
To protect against loss due to damage incurred in transit, complete the pre-commissioning checklist, which can be obtained from your Trane representative.
• Inspect the individual pieces of the shipment before accepting the unit. Check for obvious damage to the unit or packing material.
• Inspect the unit for concealed damage as soon as possible after delivery and before it is stored. Concealed damage must be reported within 10 days after receipt.
• If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
• Notify the Trane sales representative and arrange for repair. Do not repair the unit, however, until damage is inspected by the transportation representative.
6
General Information
Loose Parts Inventory
The loose parts items ship in the motor junction box for units without a unit-mounted starter, or in the starter panel for units equipped with a unit-mounted starter. This includes the isolation pads, extra oil filter, and any optional factory-shipped items.
Unit Description
The CVGF units are single­compressor, gear-type, water­cooled liquid chillers designed for installation indoors. Each unit is a completely assembled, hermetic package that is factory­piped, wired, leak-tested, dehydrated, oil-charged, and tested for proper control operation before shipment. Note: high-voltage starters are not unit-mounted before shipment.
Figure 2 and Figure 3 show a typical CVGF unit and its components. Water inlet and outlet openings are covered before shipment. The oil tank is factory-charged with 15 gallons (56.8L) of Trane Oil 37 and a holding charge of 5 psig (34 kPa) of dry nitrogen at 70°F (21°C). (See the Operation Maintenance Manual for equivalent oil specification.)
CVGF-SVN02B-E4
7
General Information
CVGF-SVN02B-E4
8
General Information
Figure 2. Component location for typical CVGF unit
Relief valves
Unit nameplate
Control Panel CH530
Evaporator
Oil Pump
Two-stage compressor
Unit-mounted starter (optional)
Condenser
Motor
Unit nameplate
Relief valves
Oil cooler
Economizer
Figure 3. Component location for typical CVGF unit (back view)
H = (9th digit) Unit Voltage
D = 380V-60 Hz F = 460V-60 Hz H = 575V-60 Hz N = 4160V-60 Hz P = 3300V-60 Hz R = 380V-50 Hz T = 400V-50 Hz U = 415V-50 Hz V = 3300V-50 Hz X = 6600V-60 Hz Z = 6600V-50 Hz S = Special
A0 = (10th and 11th digit) Design Sequence
C = (12th digit) Control Enclosure
C = Standard Control Enclosure S = Special
316 = (13th, 14th, and 15th digit) Compressor Motor Power (kw)
221 = 221 CPKW 254 = 254 CPKW 285 = 285 CPKW 316 = 316 CPKW 357 = 357 CPKW 401 = 401 CPKW 240 = 240 CPKW 266 = 266 CPKW 301 = 301 CPKW 338 = 338 CPKW 374 = 374 CPKW 430 = 430 CPKW 444 = 444 CPKW 484 = 484 CPKW 511 = 511 CPKW 532 = 532 CPKW 574 = 574 CPKW 594 = 594 CPKW 641 = 641 CPKW 674 = 674 CPKW 719 = 719 CPKW 751 = 751 CPKW 808 = 808 CPKW SSS = Special
0900 = (16th, 17th, 18th, and 19th digit) Compressor Impeller Cutback
0880 CPIM 0890 CPIM 0900 CPIM 0910 CPIM 0920 CPIM 0930 CPIM 0940 CPIM 0950 CPIM 0960 CPIM 0970 CPIM 0980 CPIM 0990 CPIM 1000 through 1510 = Cutback is the same as the FCOD for impeller cutback SSSS = Special
5 = (20th digit) Evaporator Shell Size
1 = 1000 ton evaporator 5 = 500 ton evaporator 7 = 700 ton evaporator S = Special
B = (21st digit) Evaporator Tube Bundle
A = Small bundle B = Medium bundle C = Large bundle D = Extra large bundle S = Special
1 = (22nd digit) Evaporator Tubes
1 = .75 diameter .025 wall internally enhanced cu tube 2 = 1.00 diameter .025 wall internally enhanced cu tube S = Special
CVGF-SVN02B-E4
9
General Information
Model number digits are selected and assigned in accordance with the following definitions using the typical model number example shown below:
CVGF0500HA0C31609005B1B5B1 C2306G4A1E2CC0A0CL
C = (1st digit)
V = (2nd digit) Hermetic Centrifugal Compressor
G = (3rd digit) Gear Drive
F = (4th digit) Development sequence
0500 = (5th, 6th, 7th, and 8th digit) Nominal compressor tonnage
0400 = 400 tons 0500 = 500 tons 0650 = 650 tons 0800 = 800 tons 1000 = 1000 tons SSSS = Special
CVGF-SVN02B-E4
0 = (30th digit) Factory Installed Insulation
0 = None A = Factory installed insulation
1 = (31st digit) Control: Operating Status
0 = None 1 = Operating Status
G = (32nd digit) Control: Generic BAS
0 = None G = Generic BAS
4 = (33rd digit) Tracer Communication Interface
0 = None 4 = COMM 4 5 = COMM 5
A = (34th digit) Chilled Water Reset ­Outdoor Air Temperature Sensor
0 = None A = Chilled Water Reset – With Outdoor Air Temp Sensor
1 = (35th digit) Control: Extended Operation
0 = None 1 = Extended Operation
E = (36th digit) Language
E = English F = French G = German T = Italian P = Spanish S = Special
10
General Information
B = (23rd digit) Evaporator Waterbox
B = 150 PSI Non-Marine - 2 pass C = 150 PSI Non-Marine - 3 pass D = 150 PSI Marine - 2 pass E = 150 PSI Marine - 3 pass H = 300 PSI Marine - 2 pass J = 300 PSI Marine - 3 pass L = 300 PSI Non-Marine - 2 pass M = 300 PSI Non-Marine - 3 pass S = Special
5 = (24th digit) Condenser Shell Size
1 = 1000 ton condenser 5 = 500 ton condenser 7 = 700 ton condenser S = Special
B = (25th digit) Condenser Tube Bundle
A = Small bundle B = Medium bundle C = Large bundle D = Extra large bundle S = Special
1 = (26th digit) Condenser Tubes
1 = .75 diameter .028 wall internally enhanced cu tube 2 = 1.00 diameter .028 wall internally enhanced cu tube 3 = .75 diameter .035 wall 90/10 cu/ni tube 4 = .75 diameter .028 wall titanium tube S = Special
C = (27th digit) Condenser Waterbox
A = 150 PSI Marine - 2 pass C = 150 PSI Non-Marine - 2 pass E = 300 PSI Marine - 2 pass G = 300 PSI Non-Marine - 2 pass S = Special
23 = (28th and 29th digit) Orifice Series
13 Orifice series 14 Orifice series 15 Orifice series 16 Orifice series 17 Orifice series 18 Orifice series 19 Orifice series 20 Orifice series 22 Orifice series 23 Orifice series 25 Orifice series 27 Orifice series 28 Orifice series 30 Orifice series 31 Orifice series 33 Orifice series 35 Orifice series 38 Orifice series 40 Orifice series 42 Orifice series 44 Orifice series 47 Orifice series 49 Orifice series 51 Orifice series 56 Orifice series SS = Special
A = (41st digit) Starter Type
A = Star-Delta - unit mounted B = Solid State - unit mounted C = Star-Delta - remote mounted E = X-line full volt - remote mounted F = Autotransformer - remote mounted G = Primary reactor - remote mounted M= Solid State Floor Mounted N= Solid State Wall Mounted R = Customer supplied
0 = (42nd digit) Additional Pressure Vessel Compliance
0 = None N = Non-destructive Examination for China K = KHK Japanese pressure vessel code
C = (43rd digit) Control: Condenser Refrigerant Pressure
0 = None C = Condenser Refrigerant Pressure
L = (44th digit) Manufacturing Location
L = La Crosse, Wisconsin T = Tai Cang, China
C = (39th digit) Impeller Rim Diameter 2nd Stage
A = 9.5 Rim diameter B = 10.0 Rim diameter C = 10.6 Rim diameter D = 11.1 Rim diameter E = 11.6 Rim diameter F = 9.8 Rim diameter G = 10.4 Rim diameter H = 11.0 Rim diameter J = 11.7 Rim diameter K = 12.7 Rim diameter L = 13.5 Rim diameter M = 14.3 Rim diameter N = 15.1 Rim diameter S = Special
0 = (40th digit) Special Options
0 = None S = Special option
CVGF-SVN02B-E4
11
General Information
2 = (37th digit) Motor Frame Size
2 = 400 Frame 3 = 440E Frame 4 = 5000 Frame S = Special
C = (38th digit) Impeller Rim Diameter 1st Stage
A = 9.5 Rim diameter B = 10.0 Rim diameter C = 10.6 Rim diameter D = 11.1 Rim diameter E = 11.6 Rim diameter F = 9.8 Rim diameter G = 10.4 Rim diameter H = 11.0 Rim diameter J = 11.7 Rim diameter K = 12.7 Rim diameter L = 13.5 Rim diameter M = 14.3 Rim diameter N = 15.1 Rim diameter S = Special
CVGF-SVN02B-E4
12
General Information
Service Model Numbers – Solid State Motor Starter
An example of a typical Solid State “IT” starter model number is:
CVSR0035FAA01EA0E1
Model Number Digit Identification ­Model number digits are selected and assigned in accordance with the following definitions using the model number example shown above.
C = (1st digit)
V = 2nd digit)
S = (3rd digit)
R = (4th digit) Development Sequence
R = Cutler Hammer Solid State “IT” starter for gear drive centrifugal chillers with CH530 controls 0035 = (5th, 6th, 7th, and 8th digit) Starter Size
Use Rated Load Amps (RLA) value
F = (9th digit) Unit Voltage
D = 380V-60Hz-3Ph F = 460V-60Hz-3Ph H = 575V-60Hz-3Ph R = 380V-50Hz-3Ph T = 400V-50Hz-3Ph U = 415V-50Hz-3Ph S = Special
A = (10th digit) Design Sequence
A = Original Design
A = (11th digit) Starter Type
B = Unit Mounted M = Remote Floor Mounted N = Remote Wall Mounted S = Special
0 = (12th digit) Connection Type
0 = Terminal Block 1 = Disconnect Switch - Non-Fused 2 = Circuit Breaker 3 = Circuit Breaker Current Limiting 4 = Circuit Breaker High Interrupt Cap 5 = Circuit Breaker Higher Interrupt Cap S = Special
1 = (13th digit) Agency Listing
1 = UL & cUL Listed (Standard on all units) 2 = CE
E = (14th Digit) Power Factor Correction Capacitor
0 = None D = 25 KVAR E = 30 KVAR F = 35 KVAR G = 40 KVAR H = 45 KVAR
J = 50 KVAR K = 60 KVAR L = 70 KVAR M = 75 KVAR N = 80 KVAR P = 90 KVAR R = 100 KVAR T = 120 KVAR U = 125 KVAR V = 150 KVAR S = Special
A = (15th Digit) Ground Fault Protection
0 = None A = Ground Fault Protection S = Special
0 = (16th digit) Special Options
0 = None S = Special Options ( See Sales Order)
E = (17th digit) Literature Language
E = English F = French G = German P = Spanish T = Italian S = Special
1 = (18th digit) Oil Pump Starter Circuit
1 = 1 HP Oil Pump Motor 2 = 1.5 HP Oil Pump
CVGF-SVN02B-E4
13
General Information
Service Model Numbers ­Wye-delta Motor Starter
An example of a typical chiller starter model number is:
CVSN0035FAA01EA0E1
Model Number Digit Identification ­Model number digits are selected and assigned in accordance with the following definitions using the model number example shown above.
C = (1st digit)
V = 2nd digit)
S = (3rd digit)
N = (4th digit) Development Sequence
N = Cutler-Hammer electrical­mechanical starter for gear drive centrifugal chillers with CH530 controls
0035 = (5th, 6th, 7th, and 8th digit) Starter Size
F = (9th digit) Unit Voltage
D = 380V-60Hz-3Ph F = 460V-60Hz-3Ph H = 575V-60Hz-3Ph R = 380V-50Hz-3Ph T = 400V-50Hz-3Ph U = 415V-50Hz-3Ph S = Special
A = (10th digit) Design Sequence
A = Original Design
A = (11th digit) Starter Type
A = Star-Delta - Unit Mounted C = Star-Delta - Remote Mounted S = Special
0 = (12th digit) Connection Type
0 = Terminal Block 1 = Disconnect Switch - Non-Fused 2 = Circuit Breaker 3 = Circuit Breaker Current Limiting 4 = Circuit Breaker High Interrupt Cap 5 = Circuit Breaker Higher Interrupt Cap S = Special
1 = (13th digit) Agency Listing
1 = UL & cUL Listed (Standard on all units) 2 = CE.
E = (14th Digit) Power Factor Correction Capacitor
0 = None D = 25 KVAR E = 30 KVAR F = 35 KVAR G = 40 KVAR H = 45 KVAR
J = 50 KVAR K = 60 KVAR L = 70 KVAR M = 75 KVAR N = 80 KVAR P = 90 KVAR R = 100 KVAR T = 120 KVAR U = 125 KVAR V = 150 KVAR S = Special
A = (15th Digit) Ground Fault Protection
0 = None A = Ground Fault Protection S = Special
0 = (16th digit) Special Options
0 = None S = Special Options (See Sales Order)
E = (17th digit) Literature Language
E = English F = French G = German P = Spanish T = Italian S = Special
1 = (18th digit) Oil Pump Starter Circuit
1 = 1 HP Oil Pump Motor 2 = 1.5 HP Oil Pump Motor
CVGF-SVN02B-E4
14
General Information
Installation Overview
For convenience, Table 1 summarizes responsibilities that are typically associated with the CVGF chiller installation process.
Table 1. Installation responsibility chart for CVGF units
Requirement Trane-supplied, Trane-supplied, Field-supplied,
Trane-installed Field-installed Field-installed
Rigging Safety chains
Clevis connectors
Isolation Isolation pads Spring isolators
Spring isolators
Electrical
Terminal lugs Ground connection(s) Jumper bars BAS wiring (optional) IPC wiring Control voltage wiring
Optional relays and wiring
Water piping Thermometers
Pressure Relief Relief valves
Insulation Insulation (optional) Insulation
Lifting beam equipment, skates, rollers, and other lifting operations
Circuit breakers or non-fused disconnects (optional)
Circuit breakers or fusible disconnects (optional)
Temperature sensor (optional outdoor air)
Remote-mounted starter (optional)
Chilled-water-pump contactor and wiring
Condenser-water-pump contactor and wiring
Flow switches (may be field-supplied)
Water flow pressure gauges
Isolation and balancing valves water piping
Pressure relief valves (for water boxes as
required)
Vent line and flexible connector
Unit-mounted starter (optional)
Vent and drain valves
CVGF-SVN02B-E4
15
Refer to the Mechanical and Electrical sections of this manual for detailed instructions.
• Locate and maintain the loose parts such as, isolators, bulb wells, temperature sensors, flow sensors or other factory­ordered field-installed options, as required. Loose parts are located in the starter panel if equipped with a unit-mounted starter. If not equipped with a unit-mounted starter, loose parts are shipped in the motor junction box.
• Install the unit on a foundation with flat support surfaces, level within 1/4" (6 mm) and of sufficient strength and mass to support the chiller operating weight. Place the manufacturer­supplied isolation-pad assemblies under the unit.
• Install the unit per the instructions outlined in the Mechanical Installation section.
• Complete all water piping and electrical connections.
Note: Field piping must be arranged and supported to avoid stress on the equipment. It is strongly recommended that the piping contractor provide at least 3 feet (914 mm) of clearance between the pre­installation piping and the planned location of the unit. This will allow for the proper fit upon arrival of the unit at the installation site. All necessary piping adjustments can be made at that time.
• Where specified, supply and install valves in the water piping, upstream and downstream of the evaporator and condenser water boxes, in order to isolate the shells for maintenance and to balance and trim the system.
• Supply and install flow switches or equivalent devices in both the chilled-water piping and the condenser-water piping. Interlock each switch with the proper pump starter, to ensure that the unit can only operate when water flow is established.
Note: reference graphs 1-16 in the Installation Mechanical section for proper water flow.
• Supply and install taps for thermometers and a pressure gauge manifold in the water piping, adjacent to the inlet and outlet connections of both the evaporator and the condenser.
• Supply and install drain valves on each water box.
• Supply and install vent cocks on each water box.
• Where specified, supply and install strainers ahead of all pumps and automatic modulating valves.
• Supply and install refrigerant pressure-relief piping from the pressure-relief valve to the atmosphere.
• If necessary, supply enough HFC-134a refrigerant (1 pound = .45 kg) and dry nitrogen (75 psig = 517 kPa maximum) for leak testing.
• Evacuate the unit to less than 500 microns (0.5 mm Hg) or according to local code.
• Charge with refrigerant 134a.
• Go over the pre-commissioning check sheet and ensure that all items have been completed.
• Start the unit under the supervision of a qualified service technician.
General Information
Table 2. General data: 400 and 500 ton units
Nominal Tonnage 400 400 400 400 500 500 500 500
1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75
Two Three Two Three Two Three Two Three
Refrigerant Type R134a R134a R134a R134a R134a R134a R134a R134a Refrigerant Charge - 650 650 650 650 750 750 750 750 pounds (kg) (295) (295) (295) (295) (295) (295) (295) (295) Oil Charge 15 15 15 15 15 15 15 15 (gallon (l)) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) Overall Dimensions - Feet-Inch (mm) Length 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16"
(4800) (4800) (4800) (4800) (4800) (4800) (4800) (4800)
Width 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64"
(1989) (1989) (1989) (1989) (1989) (1989) (1989) (1989)
Height 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2"
(2096) (2096) (2096) (2096) (2096) (2096) (2096) (2096)
2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8"
(791) (791) (791) (791) (791) (791) (791) (791)
8" 8" 8" 8" 8" 8" 8" 8"
(203) (203) (203) (203) (203) (203) (203) (203)
2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2"
(3060) (3060) (3060) (3060) (3060) (3060) (3060) (3060)
10" 10" 10" 10" 10" 10" 10" 10"
(254) (254) (254) (254) (254) (254) (254) (254)
Weight - pounds (kg)) except Waterboxes Compressor/Motor 6220 6220 6220 6220 6220 6220 6220 6220
(2821) (2821) (2821) (2821) (2821) (2821) (2821) (2821)
Evaporator 3948 3948 4228 4228 4193 4193 4568 4568
(1791) (1791) (1918) (1918) (1902) (1902) (2072) (2072)
Condenser 2857 2857 3472 3472 3152 3152 3877 3877
(1296) (1296) (1575) (1575) (1430) (1430) (1759) (1759)
Economizer 535 535 535 535 535 535 535 535
(243) (243) (243) (243) (243) (243) (243) (243)
Starter Panel 500 500 500 500 500 500 500 500
(227) (227) (227) (227) (227) (227) (227) (227)
Control Panel 70 70 70 70 70 70 70 70
(318) (318) (318) (318) (318) (318) (318) (318) 2127 2127 2127 2127 2127 2127 2127 2127
(965) (965) (965) (965) (965) (965) (965) (965)
17867 17867 17867 17867 17867 17867 17867 17867 (8104) (8104) (8104) (8104) (8104) (8104) (8104) (8104)
21460 21460 21460 21460 22564 22564 22564 22564 (9734) (9734) (9734) (9734) (10235) (10235) (10235) (10235)
Operational Data
447 298 407 271 550 367 511 340 (28) (20) (25.6) (17) (34) (23) (32) (21)
1638 1092 1493 995 2018 1346 1873 124895 (103) (69) (94) (63) (127) (85) (118) (79)
499 499 487 487 606 606 586 586 (31) (31) (31) (31) (38) (38) (37) (37)
1831 1831 1786 1786 2221 2221 2148 2148 (115) (115) (113) (113) (140) (140) (135) (135)
CVGF-SVN02B-E4
16
General Information
Evaporator Water Pass
Evaporator Water Connection (NPS)
Condenser Nominal Connector Size (NPS)
Miscellaneous Item
Minimum Evaporator Flow in gpm (l/sec)
Maximum Evaporator Flow in gpm (l/sec)
Minimum Condenser Flow in gpm (l/sec)
Maximum Condenser Flow in gpm (l/sec)
Tube Outside Diameter (inch)
Evaporator Inside Diameter
Condenser Inside Diameter
Shipping Weight
Operating Weight
CVGF-SVN02B-E4
17
General Information
T
able 2. General data: 400 and 500 ton units (continued)
Nominal Tonnage 400 400 400 400 500 500 500 500
1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75
Two Three Two Three Two Three Two Three
Water Volume - 150 pound Waterboxes
101.7 101.49 95.7 95.4 117.2 116.9 111.2 110.9 (385) (384) (361) (361) (444) (443) (421) (420)
112 112 110.4 110.4 127.8 127.8 125.0 125.0
(424) (424) (418) (418) (484) (484) (473) (473)
Evaporator 2-pass Weight
Supply - pound 304 304 304 304 304 304 304 304
(kg) (138) (138) (138) (138) (138) (138) (138) (138)
Return - pound 337 337 337 337 337 337 337 337
(kg) (153) (153) (153) (153) (153) (153) (153) (153)
Evaporator 3-pass Weight
Supply - pound 314 314 314 314 314 314 314 314
(kg) (142) (142) (142) (142) (142) (142) (142) (142)
Return - pound 332 332 332 332 332 332 332 332
(kg) (151) (151) (151) (151) (151) (151) (151) (151)
Condenser 2-pass Weight
Supply - pound 304 304 304 304 304 304 304 304
(kg) (138) (138) (138) (138) (138) (138) (138) (138)
Return - pound 341 341 341 341 341 341 341 341
(kg) (155) (155) (155) (155) (155) (155) (155) (155)
300 pound Waterboxes
101.9 101.6 95.9 95.6 117.4 117.0 111.4 111.1 (386) (385) (363) (362) (444) (443) (422) (421)
112.3 112.3 110.6 110.6 128.0 128.0 125.3 125.3 (425) (425) (419) (419) (485) (485) (474) (474)
Evaporator 2-pass Weight
Supply - pound 427 427 427 427 427 427 427 427
(kg) (194) (194) (194) (194) (194) (194) (194) (194)
Return - pound 446 446 446 446 446 446 446 446
(kg) (202) (202) (202) (202) (202) (202) (202) (202)
Evaporator 3-pass Weight
Supply - pound 448 448 448 448 448 448 448 448
(kg) (203) (203) (203) (203) (203) (203) (203) (203)
Return - pound 448 448 448 448 448 448 448 448
(kg) (203) (203) (203) (203) (203) (203) (203) (203)
Condenser 2-pass Weight
Supply - pound 421 421 421 421 421 421 421 421
(kg) (191) (191) (191) (191) (191) (191) (191) (191)
Return - pound 436 436 436 436 436 436 436 436
(kg) (198) (198) (198) (198) (198) (198) (198) (198)
Evaporator Water Storage gallon (l)
Condenser Water Storage gallon (l)
Evaporator Water Storage gallon (l)
Condenser Water Storage gallon (l)
Evaporator Water Pass
Tube Outside Diameter (inch)
CVGF-SVN02B-E4
18
General Information
Table 3. General data: 650 ton units
Nominal Tonnage 650
1.0 0.75
Two Three Two Three
Refrigerant Type R134a R134a R134a R134a Refrigerant Charge - 975 975 975 975 pounds (kg) (442.3) (442.3) (442.3) (442.3) Oil Charge 15 15 15 15 gallon (l) (56.8) (56.8) (56.8) (56.8) Overall Dimensions - Feet-Inch (mm) Length 16' 16' 16' 16'
4877 4877 4877 4877
Width 6' - 9 3/4 6' - 9 3/4 6' - 9 3/4 6' - 9 3/4
(2076) (2076) (2076) (2076)
Height 7' - 5 11/32" 7' - 5 11/32" 7' - 5 11/32" 7' - 5 11/32"
(2270) (2270) (2270) (2270)
3' - 1/4" 3' - 1/4" 3' - 1/4" 3' - 1/4"
(921) (921) (921) (921)
10" 8" 10" 8"
(254) (203) (254) (203)
2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2"
(648) (648) (648) (648)
12" 12" 12" 12"
(300) (300) (300) (300)
Weight - pounds (kg)) except Waterboxes Compressor/Motor 6800 6800 6800 6800
(3084) (3084) (3084) (3084)
Evaporator 5461 5834 5461 5834
(2477) (2643) (2477) (2643)
Condenser 3937 4763 3937 4763
(1786) (2161) (1786) (2161)
Economizer 799 799 799 799
(362) (362) (362) (362)
Starter Panel 542 542 542 542
(246) (246) (246) (246)
Control Panel 70 70 70 70
(318) (318) (318) (318) 2745 2745 2745 2745
(1245) (1245) (1245) (1245) 24140 24140 24140 24140
(10950) (10950) (10950) (10950)
28344 28344 28344 28344
(12857) (12857) (12857) (12857)
Operational Data
625 417 566 378
(39) (26) (36) (24)
2501 1529 1493 995 (158) (97) (94) (63)
682 682 668 668 (43) (43) (42) (42)
2501 2501 2450 2450 (158) (258) (155) (155)
Evaporator Water Pass
Evaporator Water Connection (NPS)
Condenser Nominal Connector Size (NPS)
Miscellaneous Item
Minimum Evaporator Flow in gpm (l/sec)
Maximum Evaporator Flow in gpm (l/sec)
Minimum Condenser Flow in
gpm (l/sec) Maximum Condenser Flow in gpm (l/sec)
Tube Outside
Diameter (inch)
Evaporator Inside
Diameter
Condenser
Inside Diameter
Shipping Weight
Operating Weight
CVGF-SVN02B-E4
19
General Information
Table 3. General data: 650 ton units (continued)
Nominal Tonnage 650
1.0 0.75
Two Three Two Three
Water Volume - 150 pound Waterboxes
163.2 158.2 154.1 149.1 (618) (599) (583) (564)
185.1 185.1 188.5 188.5 (701) (701) (714) (714)
Evaporator 2-pass Weight
Supply - pound 304 304 304 304
(kg) (138) (138) (138) (138)
Return - pound 337 337 337 337
(kg) (153) (153) (153) (153)
Evaporator 3-pass Weight
Supply - pound 314 314 314 314
(kg) (142) (142) (142) (142)
Return - pound 332 332 332 332
(kg) (151) (151) (151) (151)
Condenser 2-pass Weight
Supply - pound 304 304 304 304
(kg) (138) (138) (138) (138)
Return - pound 341 341 341 341
(kg) (155) (155) (155) (155)
300 pound Waterboxes
163.2 158.2 154.1 149.1 (618) (599) (583) (564)
185.1 185.1 189.4 189.4 (701) (701) (717) (717)
Evaporator 2-pass Weight
Supply - pound 427 427 427 427
(kg) (194) (194) (194) (194)
Return - pound 446 446 446 446
(kg) (202) (202) (202) (202)
Evaporator 3-pass Weight
Supply - pound 448 448 448 448
(kg) (203) (203) (203) (203)
Return - pound 448 448 448 448
(kg) (203) (203) (203) (203)
Condenser 2-pass Weight
Supply - pound 421 421 421 421
(kg) (191) (191) (191) (191)
Return - pound 436 436 436 436
(kg) (198) (198) (198) (198)
Evaporator Water Storage gallon (l)
Condenser Water Storage gallon (l)
Evaporator Water Storage (gallon (l))
Condenser Water Storage gallon (l)
Evaporator Water Pass
Tube Outside Diameter (inch)
CVGF-SVN02B-E4
20
General Information
Table 4. General data: 700 ton family
Nominal Tonnage 560 560 560 560 630 630 630 630
1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75
Two Three Two Three Two Three Two Three
875 875 875 875 925 925 925 925
(397) (397) (397) (397) 420) (420) (420) (420)
15 15 15 15 15 15 15 15
(56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) Overall Dimensions - Feet-Inch (mm) Length 16'11" 16'11" 16'11" 16'11" 16'11" 16'11" 16'11" 16'11"
(5153) (5153) (5153) (5153) (5153) (5153) (5153) (5153)
Width 6'10" 6'10" 6'10" 6'10" 6'10" 6'10" 6'10" 6'10"
(2075) (2075) (2075) (2075) (2075) (2075) (2075) (2075)
Height 7'5" 7'5" 7'5" 7'5" 7'5" 7'5" 7'5" 7'5"
(2269) (2269) (2269) (2269) (2269) (2269) (2269) (2269)
36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4"
(921) (921) (921) (921) (921) (921) (921) (921)
10" 8" 10" 8" 10" 8" 10" 8"
(254) (203) (254) (203) (254) (203) (254) (203)
29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2"
(749) (749) (749) (749) (749) (749) (749) (749)
12" 12" 12" 12" 12" 12" 12" 12"
(304) (304) (304) (304) (304) (304) (304) (304)
Weight- pound (kg) 150 Lb. Waterboxes
6440 6440 6440 6440 6440 6440 6440 6440
(2921) (2921) (2921) (2921) (2921) (2921) (2921) (2921)
5949 5949 6283 6283 5940 5940 6480 6480
(2698) (2698) (2850) (2850) (2694) (2694) (2939) (2939)
4651 4651 5515 5515 4875 4875 5824 5824
(2110) (2110) (2502) (2502) (2211) (2211) (2642) (2642)
904 904 904 904 904 904 904 904
(410) (410) (410) (410) (410) (410) (410) (410)
542 542 542 542 542 542 542 542
(246) (246) (246) (246) (246) (246) (246) (246)
70 70 70 70 70 70 70 70
(318) (318) (318) (318) (318) (318)) (318) (318) 1216 1216 1216 1216 1216 1216 1216 1216
(552) (552) (552) (552) (552) (552) (552) (552) 1867 1891 1867 1891 1867 1891 1867 1891
(847) (858) (847) (858) (847) (858) (847) (858)
298 298 298 298 298 298 298 298
(135) (135) (135) (135) (135) (135) (135) (135)
22,024 22,048 23,222 23,246 22,239 22,263 23,728 23,750
(9990) (10001) (10553) (10544) (10541) (10552) (10763) (10773)
2608 2575 2519 2486 2809 2776 2689 2656
(1183) (1168) (1143) (1128) (1274) (1259) (1220) (1205)
997 997 997 997 1047 1047 1047 1047
(452) (452) (452) (452) (475) (475) (475) (475)
25,629 25,620 26,738 26,729 26,095 26,086 27,464 27,453
(11625) (11621) (12128) (12124) (11836) (11832) (12457) (12452)
Evaporator Water Connection size (NPS)
Condenser Nominal Connector size (NPS)
Economizer weight
Starter panel weight
Control panel weight
I/C Piping and Supports
Waterboxes
Miscellaneous Item
Total Shipping Weight
Total Water Volume Refrigerant and Oil
Total Weight
Evaporator Water Pass
Evaporator Inside Diameter
Condenser Inside Diameter
Compressor weight
Evaporator weight
Condenser weight
Tube Outside Diameter (inch)
Refrigerant Charge
- pounds (kg) Oil charge -
gallons (l)
CVGF-SVN02B-E4
21
General Information
Table 4. General data: 700 ton family (continued)
Nominal Tonnage 560 560 560 560 630 630 630 630
1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75
Two Three Two Three Two Three Two Three
Operational Data
625 417 566 378 706 471 628 419
(39.4) (26.3) (35.7) (23.8) (44.5) (29.7) (39.6) (26.4)
2293 1529 2077 1385 2581 1726 2304 1536
(144.6) (96.4) (131) (87.4) (162.8) (108.9) (145.3) (96.9)
682 682 668 668 764 764 744 744 (43) (43) (42.1) (42.1) (48.2) (48.2) (47) (47)
2501 2501 2450 2450 2801 2801 2727 2727
(157.7) (157.7) (154.5) (154.5) (176.7) (176.7) (172) (172)
150 pound waterboxes
150.7 146.4 141.8 137.5 162.7 158.4 151 146.7
(570.4) (554.2) (537) (520.5) (616) (600) (572) (555.3)
162.8 162.8 161 161 174.9 174.9 172.2 172.2
(616.3) (616.3) (609.5) (609.5) (662.1) (662.1) (652) (652)
Evaporator 2-pass Weight
Supply - pound 492.7 492.7 492.7 492.7 492.7 492.7 492.7 492.7
(kg) (223.5) (223.5) (223.5) (223.5) (223.5) (223.5) (223.5) (223.5)
Return - pound 435.2 435.2 435.2 435.2 435.2 435.2 435.2 435.2
(kg) (197.4) (197.4) (197.4) (197.4) (197.4) (197.4) (197.4) (197.4)
Evaporator 3-pass Weight
Supply - pound 476.6 476.6 476.6 476.6 476.6 476.6 476.6 476.6
(kg) (216.2) (216.2) (216.2) (216.2) (216.2) (216.2) (216.2) (216.2)
Return - pound 478.9 478.9 478.9 478.9 478.9 478.9 478.9 478.9
(kg) (217.2) (217.2) (217.2) (217.2) (217.2) (217.2) (217.2) (217.2)
Condenser 2-pass Weight
Supply - pound 500.2 500.2 500.2 500.2 500.2 500.2 500.2 500.2
(kg) (226.9) (226.9) (226.9) (226.9) (226.9) (226.9) (226.9) (226.9)
Return - pound 437.6 437.6 437.6 437.6 437.6 437.6 437.6 437.6
(kg) (198.5) (198.5) (198.5) (198.5) (198.5) (198.5) (198.5) (198.5)
300 pound Waterboxes
151 146.6 142.1 137.7 163 158.6 151.3 146.9
(571.6) (554.9) (537.9) (521.3) (617) (600.4) (572.7) (556.1)
163.4 163.4 161.6 161.6 175.5 175.5 172.8 172.8
(618.5) (618.5) (611.7) (611.7) (664.3) (664.3) (654.1) (654.1)
Evaporator 2-pass Weight
Supply - pound 625.9 625.9 625.9 625.9 625.9 625.9 625.9 625.9
(kg) (283.9) (283.9) (283.9) (283.9) (283.9) (283.9) (283.9) (283.9)
Return - pound 590.5 590.5 590.5 590.5 590.5 590.5 590.5 590.5
(kg) (267.8) (267.8) (267.8) (267.8) (267.8) (267.8) (267.8) (267.8)
Evaporator 3-pass Weight
Supply - pound 624.9 624.9 624.9 624.9 624.9 624.9 624.9 624.9
(kg) (283.4) (283.4) (283.4) (283.4) (283.4) (283.4) (283.4) (283.4)
Return - pound 627.2 627.2 627.2 627.2 627.2 627.2 627.2 627.2
(kg) (284.5) (284.5) (284.5) (284.5) (284.5) (284.5) (284.5) (284.5)
Condenser 2-pass Weight
Supply - pound 625.1 625.1 625.1 625.1 625.1 625.1 625.1 625.1
(kg) (283.5) (283.5) (283.5) (283.5) (283.5) (283.5) (283.5) (283.5)
Return - pound 594.4 594.4 594.4 594.4 594.4 594.4 594.4 594.4
(kg) (269.6) (269.6) (269.6) (269.6) (269.6) (269.6) (269.6) (269.6)
Minimum Evaporator Flow GPM (l/s)
Maximum Evaporator Flow GPM (l/s)
Minimum Condenser Flow GPM (l/s)
Maximum Condenser Flow GPM (l/s)
Evaporator Water Storage gallons (l)
Condenser Water Storage gallons (l)
Evaporator Water Storagegallons (l)
Condenser Water Storage gallons (l)
Evaporator Water Pass
Tube Outside Diameter (inch)