Trane Custom Climate Changer Air Handlers Installation and Maintenance Manual

Page 1
Installation Operation Maintenance
Custom Climate Changer™ Air Handlers
July 20 10
X-code - X39640745010
CAH-SVX01B-EN
Page 2
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provide to alert inst alling contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that may result in equipment or property-damage-only accidents.
Y our personal safety and the proper operation of this mac hine depend upon the strict observance of these precautions.
ATTENTION: Warnings, Cautions and Notices appear at appropriat e secti ons th roug hout
this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, could
result in minor or moderate injury . It could also be used to aler t against unsafe practices.
NOTICE: Indicates a situation that may result in equipment or property-damage only
accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth's naturally occurring stratospheric ozone layer when released to the atmosphere. In part icular , several of the identified chemicals that may af fect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containin g Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant pra ctices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the req uiremen ts for handli ng , reclaiming, recovering and recycling of certai n refrigerants and the equipment th at is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Refrigerant warning information!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or r efrigerant additives could r esult in death o r serious injury or equipment damage.
Page 3
Warnings, Cautions and Notices
WARNING
Hazard of Explosion!
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxyg en or compr essed air or mixtur es containing them f or pressu re t esting. Do not use mixtur es of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a tr ace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage.
Ultraviolet (UV) Germicidal Irradiation Lights
The United States Environmental Protection Agency (EP A) believes that molds and bacteria inside buildings have the potential to cause health problems in sensitive individuals. If specified, Trane provides ultraviolet lights (UV -C) as a factory-engineered and installed option in select commercial air handling products for the purpose of reducing microbiological growth (mold and bacteria) within the equipment. When factory provided, polymer materials that are susceptible to deterioration by the UV -C light will be substituted or shielded from direct exposure to the light. In addition, UV -C radiation can damage human tissue, namely eyes and skin. To reduce the potential for inadvertent exposure to the lights by operating and maintenance personnel, electrical interlocks that automatically disconnect pow er to the lights are pro vided at all unit en try points to equipment where lights are located.
WARNING
Equipment Damage From Ultraviolet (UV) Lights!
Trane does not recommend field-installation of ultr aviolet lig hts in its air handling equip ment for the intended pur pose of improving indoor air quality. High intensity C-band ultraviolet light is known to severely damage polymer (plastic) materials and poses a personal safety risk to anyone exposed to the light without proper personal protective equipment (could cause damage to e y es and skin ). Polymer materials commonly found in HVA C equipment that may be susceptible include insulation on el ectrical wiring, fan belts, thermal insulation, various fasteners and bushings. Degradation of these materi als can result in serious damage to the equipmen t.
Trane accepts no responsib ili ty for the performance or operation of our air handling equipment in which ultraviolet devices were installed outside of the Trane factory.
CAH-SVX01B-EN 3
Page 4
Table of Contents
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operating Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Factory-Mounted Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Pre-Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Receiving Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Resolving Shipping Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Storage Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Preparing the Unit Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Roof Curb Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Installation - Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Lifting and Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Lifting Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
TCP Model Assembly Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TCC Model Assembly Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Assembly Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
General Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Long-Term Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Outdoor Storage Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Suggested Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
TCP Standard Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
TCP Structural Roof Curb and I-Beam Dunnage . . . . . . . . . . . . . . . . . . . . 19
TCP Flat Concrete Pad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
TCP Roof Curbs for Large Units with Shipping Splits . . . . . . . . . . . . . . . 21
TCP Joining Sections Edge-to-Edge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
TCP Base Section Assembly with Flat Floor . . . . . . . . . . . . . . . . . . . . . . . 23
TCP Base Section Assembly with Turned-Up Floor . . . . . . . . . . . . . . . . . 24
TCP Wall Section Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
TCP Outdoor Roof Assembly - Single Span . . . . . . . . . . . . . . . . . . . . . . . 26
TCP Outdoor Roof Assembly - Multiple Span . . . . . . . . . . . . . . . . . . . . . . 27
TCP Indoor Roof Section Assembly (Typical) . . . . . . . . . . . . . . . . . . . . . . 28
TCP Indoor Roof Assembly - Multiple Span . . . . . . . . . . . . . . . . . . . . . . . 29
TCP Base-to-Interior Wall Section Assembly . . . . . . . . . . . . . . . . . . . . . . 30
TCP Stacked Unit Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
TCC Overhang Base on Common Roof Curb . . . . . . . . . . . . . . . . . . . . . . 32
TCC Flat Base to Steel Dunnage or Concrete Pad . . . . . . . . . . . . . . . . . . 32
TCC Joining Sections - Edge-to-Edge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
TCC Internal Shipping Split Frame Assembly (Typical) . . . . . . . . . . . . . . 36
TCC Wall Section Assembly (Typical) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Page 5
TCC Indoor Roof Section Assembly (Typical) . . . . . . . . . . . . . . . . . . . . . . 37
TCC Outdoor Roof Section Assembly (Typical) . . . . . . . . . . . . . . . . . . . . 38
TCC Stacking Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
TCC Energy Wheel and CDQ Wheel Assembly . . . . . . . . . . . . . . . . . . . . . 42
Pipe Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Duct Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Bottom Opening Duct Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Component Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Isolator Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Control Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Magnahelic Air Filter Gage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Outdoor Unit Weather Hood(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Coil Piping and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
General Coil Piping Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Drain Pan Trapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Steam Coil Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Water Coil Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Refrigerant Coil Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Liquid Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Suction Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Examples of Field-Installed Evaporator Piping . . . . . . . . . . . . . . . . . . . . . . . . 63
Single-Circuit Condensing Unit: Evaporator Coil with One Distributor . 63 Single-Circuit Condensing Unit: Evaporator Coil with Two Distributors 64 Single-Circuit Condensing Unit: Evaporator Coil with Four Distributors 65 Dual-Circuit Condensing Unit: Evaporator Coil with Two Distributors) . 66 Dual-Circuit Condensing Unit: Evaporator Coil with Four Distributors . 67 Dual-Circuit Condensing Unit: Evaporator Coil with Eight Distributors . 68
Installation - Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Quick Connects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Controls Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Connecting the Operator Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Setting Up the Operator Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Calibrating the Operator Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Adjusting Brightness and Contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
External Communications Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Pre-Startup Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
General Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Fan-Related Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
CAH-SVX01B-EN 5
Page 6
Coil-Related Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Motor-Related Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Unit Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Calculate Motor Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Tension the Fan Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Determine Fan Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Align Fan and Motor Sheaves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Check Multiple Belts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Traq™ Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Fan Inlet Airflow Measuring System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Transmitter Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Transmitter Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Constant Factor K . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
External Insulating Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Routine Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Throwaway Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Permanent Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Front Load Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Side Load Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Inspecting and Cleaning Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Fan Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Bearing Set Screw Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Motor Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Fan Motor Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Steam and Water Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Cleanable Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Refrigerant Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Coil Winterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Chilled Water Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Cleanable Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Moisture Purge Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Internal Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Multiple Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Ultraviolet (UV) Light Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Cleaning the Bulbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Replacing the Bulbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Disposal of Bulbs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Page 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
CAH-SVX01B-EN 7
Page 8
General Info rmation
Use this manual to install, startup, operate, and maintain the Custom Climate Changer™ air handler. Carefully review the procedures discussed in this manual to minimize installation and startup difficulties.
Each Trane air handler section is provided with a nameplate which identifies the type of section, customer tagging information, the section serial number, the section position, the service model number, and electrical data.
Note: This information is required when ordering parts or requesting service for a Trane air
handler.
Operating Environment
When considering the placement of the air handler, it is important to consider the operating environment. The acceptable ambient temperature range for unit operation is -40ºF to 140ºF (-40ºC to 60ºC).
For heating applications, a special motor may be required to withstand the higher temperatures. Motors with Class B insulation are acceptable for ambient temperatures up to 104º F, while motors with Class F insulation can withstand ambient temperatures to +140º F (60º C).
For the units furnished with gas furnaces, the heating demands require a special motor to withstand the higher temperatures. These motors are furnished with Class “H” insulation to withstand this rigorous duty.
Note: Units with UL approval have a maximum ambient temperature requirement of 104ºF. The
customer should provide adequate freeze protectio n for the coils. See “Coil Wint erization”
on page 93 for more information.
Unit Description
Custom Climate Changer™ air handlers are designed for a variety of controlled-air applications. The basic unit consists of a fan, heating and/or cooling coils, filters, and dampers. See the unit submittal drawings for detailed descriptions.
The fans are internally isolated. To insure fan stability, the unit ships with a minimum of four lock­down devices that prevent the fan from shifting during shipment and installation. These spacers must be removed prior to fan operation to ensure proper vibration isolation. Retain these spacers for use in adjusting fan isolators if required.
The units are available with factory mounted controls for climate and humidity control. Th ese can be use as stand-alone devices or operate with a complete controls system. End devices include factory-mounted star ters and variable speed drives.
Custom Climate Changer™ air handlers ship as complete assemblies or in sections. Some jobs ite assembly is required when the units ship in sections.
Page 9
Factory-Mounted Contr ols
Trane air handlers are available with a wide selection of factory-mounted controls, including controllers, motor starters, and variable frequency drives (VFD).
Most control components are mounted inside the unit. Depending on the system configuration, this may include damper actuators, dirty filter switches, averaging temperature sensors, and low limit switches. VFDs, starters, controllers, control transformers, static pressure transducers, DC power supplies, and customer interface relays will be in enclosures mounted on the inside of the unit.
Small items that cannot be factory-mounted, such as space temperature sensors, outside air temperature sensors, and humidity sensors, will ship inside the control enclosures, or packaged and shipped inside the fan or mixing box section. Larger items are shipped inside the fan section.
Note: All control valves ship directly to the “ship-to address” from the vendor unless another
address is given on the Trane sales order.
All factory-mounted control systems (controls that are factory-wired to a unit controller or terminal strip) ordered without starters or variable-frequency drives (VFDs) are provided with 120 to 24 Vac control transformers mounted and wired in the auxiliary control panel. The customer must provide 120 Vac 50/60 Hz control power. A dedicated 15-amp circuit is recommended.
Factory-mounted control systems ordered with factory-mounted starters or VFDs are supplied with line to 24 Vac control transformers. No additional power wiring is required.
General Information
Wiring
For a more in-depth understanding of controls, refer to the following manuals:
Tracer MP580/581 Programmable Controllers catalog, CNT-PRC002-EN
Tracer MP581 Programmable Controllers Hardware Installation, CNT-SVN01C-EN
Variable Frequency Drives TR200 Series, BAS-SLB026-EN Custom air handlers and/or field-installed accessories that must be stored for a period of time prior
to being installed must be protected from the elements. All controllers and electrical/electronic components should be stored in conditions of -20 to 120°F and 5- to 95-percent relative humidity non-condensing. Electrical components are not moisture-tolerant.
Note: The warranty will not cover damage to the unit or controls due to negligen ce during storage.
A controlled indoor environment is recommended for proper storage. For further storage considerations, refer to “Storage Recommendations” on page 11.
WARNING
Grounding Requir ed!
All field-installed wiring must be completed by qualified personnel. All field-installed wiring must comply with NEC and applicable local codes. Failure to follow these instructions could result in death or serious injuries.
On outdoor units, entrances are provided for field-installation of high and lo w voltage wiring through a pipe/nipple connection in the base of the unit. As a standard, there are no penetrations into the Custom air handler for any field-provided wiring or device. Before installation, consider overall unit serviceability and accessibility before mounting, running wires (power), making cabinet penetrations, or mounting any components to the cabinet.
Wiring to the unit must be provided by the installer and must comply with all national and local electrical codes. The fan motor nameplate includes a wiring diagram. If there are any questions concerning the wiring of the motor, be sure to write down the information from the motor nameplate and contact your local fan motor manufacturer representative for assistance.
CAH-SVX01B-EN 9
Page 10
Pre-Installation Requirements
Receiving Checklist
Based on customer requirements, Trane air handlers can ship as complete units or as individual sections to be field assembled.
Upon receipt of the air handler(s), a thorough inspection should be performed to note any shipping damage that may have occurred and that the shipment is complete. All factory shipping protection should be removed immediately to allow complete access for the inspection.
Note: The shipping protection provided by the factory is for transit protection only and should not
be used as a jobsite storage cover.
Note: Delivery cannot be refused. Trane is not responsible for shipping damage.
Check all access doors to confirm that the latches and hinges are not damaged.
Inspect the interior of each section for any internal damage.
Note: Concealed damage must be reported within 15 days of receipt.
Inspect the coils for damage to the fin surface and/or coil connections.
If the unit was ordered with factory-mounted contro ls, lo cate al l sensors.
Note: Items that cannot be factory-mounted should ship inside the control enclosures or should
be packaged inside the fan or mixing box section.
Check all control devices attached to the unit exterior and confirm that they are not damaged.
Manually rotate the fan wheel to ensure free movement of the shaft, bearings, and drive.
Inspect the fan housing for any foreign objects.
If the unit is shipped in sub-assemblies, locate the assembly hardware, which should be packaged and shipped inside the fan or mixing box section.
Inspect and test all piping for possible ship ping d amage. Nippl es may be i nstalled o n coi ls at the factory but should alwa ys be tightened and tested before any connections are made. Rough handling during shipping, in addition to other factors can cause pipe connections to become loose.
Note: T rane will not be responsible for any leak at the field connections. Coils have been factory
pressure tested before shipping.
Assembly Hardware
T rane air handlers ship with all necessary assembly hardware and gasket material. This hardware is packaged in either a clear plastic envelope or cardboard box and can be found inside the fan, mixing box, or access section. If there is not enough space inside the section, a crate or pallet will be loaded onto the bed of the truc k. Chec k the par ts list on the field assembly drawing against the contents of the crate. Do not proceed with unit assembly until verification that all materials are present. Sometimes it is necessary to use more than one section to ship hardware. Please check all sections thoroughly before contacting your local Trane sales engi neer to report missing hardware.
Page 11
Resolving Shipping Damage
Trane air handlers ship free-on-board (FOB), meaning that the unit belongs to the customer the moment the delivery truck leaves the factory. If damage has occur red to the unit during shipment, follow these instructions:
Note: Trane is no t r esponsible for shipping damage.
1 . Make specific notation, describing the damage, on the freight bill. T ake photos of the da maged
material if possible.
2. Report all claims of shipping damage to the delivering carrier immediately and coordinate carrier inspection if necessary.
Note: Do not attempt to repair the unit without consulting the delivering carrier.
3. Notify your Trane sales representative of the damage and arrange for repair.
Note: Do not attempt to repair the unit without consulting the Trane sales representative.
4. Keep the damaged material in the same location as it was received.
Note: It is the receiver's responsibility to provide reasonable evidence that concealed damage was
not incurred after delivery.
Storage Recommendations
Air handlers and/or field-installed accessories that must be stored for a period of time before installation must be protected from the elements. A controlled indoor environment is recommended for proper storage.
Note: The warranty does not cover damage to the unit or controls due to negligence during
storage.
Pre-Installation Requirements
NOTICE
Use Canvas Only!
All factory shipping protection should be removed. This wrapping is for transit protection only and should not be used for jobsite storage. Use only canvas tarps to cover air handlers. Plastic tarps can cause condensation to form in and on the equipment, which could result in corrosion damage or wet storage stains.
General Storage
The unit controller and all other electrical/electroni c components should be stored in conditions of
-20ºF to 120°F and 5 to 95 percent relative humidity, non-condensing. Electrical components are
not moisture-tolerant. Factory protective coverings should be removed prior to storage.
Long-Term Storage
For longer periods of storage, allow proper clearance around the unit to perform periodic inspection and maintenance of the equipment.
While the unit is in storage:
Every two weeks, rotate the fan and motor shaft 30 revolutions by hand. Chec k for free rotation.
Every six months, chec k fan shaft bearings and grease lines. Add grease using a manual grease
Check the motor lubrication; remove and clean grease plugs and check for the presence of
gun following the lubrications recommendations in “Fan Bearing Lubrication” on page 89.
moisture in the grease. If moisture is present, remove the motor and send it to an authorized repair shop for bearing inspection/replacement. If no moisture if present, refer to the motor manufacturer’s lubrication reco mm end ation for pro per lu bricatio n
CAH-SVX01B-EN 11
Page 12
Pre-Installation Requirements
Outdoor Storage Considerations
Outdoor storage is not recommended; however, when outdoor storage is necessary, several things must be done to prevent damage:
Note: Keep the equipment in the original shipping co ntainer for protection and ease of hand ling.
Select a well-drained area, preferably a concrete pad or blacktop surface.
Place the unit on a dry surface or raised off the ground to ensure adequate air circulation beneath the unit and to ensure no portion of the unit will contact standing water at any time.
Loosen the belt tension on the drive belts.
Cover the unit securely with a canvas tarp.
Do not stack units.
Do not pile other material on the unit.
Preparing the Unit Site
NOTICE Microbial Growth!
The roof curb or foundation must be level and the condensate drain at the proper height for proper coil drainage and condensate flow. Standing water and wet surfaces inside the equipment can become an amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials.
NOTICE Level Foundation!
A level foundation is critical to proper unit and door alignment, operation, and sealing. Failure to level and align sections properly can lead to structural damage.
Ensure the installation site can support the total weight of the unit. Refer to the unit submit tals for weights.
Allow sufficient space for adequate free air and necessary service access. Refer to submittals for specific minimums.
Allow room for supply and return piping, ductwork, electrical connections, and coil removal.
Ensure there is adequate height for condensate drain requirements. See “Drain Pan T rap ping”
on page 54.
Note: If unit is installed in a mechanical room on a pad, inadequate height may necessitate core-
drilling the floor to attain proper trap height. Insufficient height could inhibit condensate drainage and result in flooding the unit and/or equipment room.
Confirm the roof curb or foundation of the mounting platform is level and large enough to accommodate the unit. Refer to the unit submittals for specific dimensions.
Provide adequate lighting for maintenance personnel to perform maintenance duties.
Provide permanent power outlets in close proximity to the unit for installation and maintenance.
Depending upon job requirements, the customer may n eed to provide 120 Vac p ower to the unit controller. Refer to submittals for more information. A dedicated 15-amp circuit is recommended.
Page 13
Wiring for units must be provided by the installer and must comply with all national and local electrical codes.
Rooftop curb mo un ted u ni ts m ust be sealed tightly to the curb. Use proper sealan ts and roof to curb sealing techniques to prevent water and air leakage.
Note: Preparation of the roof curb or pier mount and roof openings should be completed prior to
lifting the unit to the roof.
Roof Curb Installation Checklist
It is recommended that the curb be installed directly on the support members and fastened to the supports using tack welds or other equivalent methods. Properly supported decking should be installed inside the air handler section of the curb when this method is used. See Figure 1.
NOTICE
Roof Curb Structurally Sound
Check with curb manufacturer and job engineer to ensure the roof curb is structurally sufficient to support the weight of the unit. The curb should be checked to ensure it is level and square. Curb bowing, buckling, or sagging can lead to unit assembly and operation pr oblems up to complete failure.
Pre-Installation Requirements
Figure 1. Cross section of typical curb installation on new construction
CAH-SVX01B-EN 13
Page 14
Pre-Installation Requirements
1 . V erify that the roof structure can adequately support the combined weight of the unit and curb
assembly.
2. Ensure that the selected installation location provides sufficient service and operational clearances.
3. Remove any twist within the curb due to roof supports and square the curb.
4. Level the curb.
5. Secure the curb to the roof support members.
6. Install 2-inch thick boards or rigid insulation around the curb.
7. Install cant strips around the curb.
8. Bring field supplied roofing felt up to the top of the curb nailing strips. Nail felt into place.
9. Install field supplied flashing under the lip of the curb flanges and over the felt.
10. Apply sealant to the four corners. Caulk all joints between the curb and the roof. Attach the gasket material to the curb’ s top flanges (entire perimeter) and to the supply and return air duct opening panel flanges
Suggested Tools
T wo chain come-alongs. These have the pulling power to bring the shipping splits together, one on each side of the u nit. Cable come-alo ngs are not strong enough and n ormally will fai l. The chain versions work well.
Two long drift pins to keep holes aligned as the sections come together.
One half-inch or 3/4-inch electric impact gun. These are very effective to tighten the bolts at the base once it’s close enough together to get the bolts in.
Caulk guns.
Standard battery impact gun or bat tery drill for installation of screw in joint strips, hubcaps, and inlet or exhaust hoods.
Nut setters for battery impact gun - 3/8-inch and 5/16-inch.
Utility knives for cutting section-to-section gasket.
A couple of large pry bars.
Proper size soc kets and wrenches to remove lifting lugs when in p ositions. Multiple size sockets. Must have 15/16-inch and 1 1/16-inch sockets.
Page 15
Installation - Mechanical
Lifting and Rigging
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of suppor ting the enti r e w eight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit could result in death or serious injury. See details below.
WARNING
Heavy Objects!
Always place, assemble, and suspend sections/subassemblies one at a time. Do not lift units in windy conditions. Do not raise units o verhead with personnel below unit. F ailur e to f ollo w thes e instructions could result in death, serious injury, or equipmen t dam age.
WARNING
Installation - Mechanical
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
NOTICE Equipment Damage!
Do not use a fork lift on air handlers or subassemblies. Improper use of fork lifts on units may result in equipment damage. Trane is not responsible for equipment damage resulting from improper forklifting practices.
Preparation of the roof curb or pier mount and roof openings should be completed before liftin g unit to the roof. Per job requirements, air handlers will ship as a complete assembly or in sections. T rane recommends that the contractor use spreader bars and slings to rig units and sub-assemblies (sections).
CAH-SVX01B-EN 15
Page 16
Installation - Mechanical
Lifting Considerations
.
Figure 2. Recommended
attachment to lifting lugs.
Figure 3. Use proper lifting and rigging methods Make the loop of the sling parallel to
Before lifting the unit, estimate the approximate center of gravity for lifting safety. Because of the placement of internal components, the unit weight may be unevenly distributed, with more weight in the coil and fan areas. Refer to the unit submittals for section weights. Test the unit for proper balance and rigging before lifting.
Always assemble unit at the installation site. Never bolt sections together before rigging.
Always rig subassemblies or sections as they ship from the factory. See the unit submittal drawings for correct placement of sections.
Lift all sections individually using all lifting lugs provided. See Figure2. See specific instructions for handling the pipe cabinet (see “TCC Wall Section
Assembly (Typical)” on page 37) and inlet and exhaust hoods (see “Outdoor Unit Weather Hood(s)” on page 52).
the direction of airflow whenever possible.
Each of the cables used to lif t the unit must be capable of supporting the entire weight of the unit.
When hoisting the unit into position, use the proper rigging method, such as straps, slings, spreader bars, or lifting lugs for protection and safety. See Figure 3.
The air handler is not designed to be lifted, rigged or ceiling sus pend ed from the top of the unit.
Never lift units in windy conditions. Personnel should be positioned overhead and on the ground to guide the crane or helicopter operator in positioning the sections.
Never stack the pipe cabinet and inlet hoods on the unit as the unit is being lifted.
Do not attach the intake/exhaust hoods to the unit prior to lifting the unit. Doing so may damage the equipment. Attach the hoods to the unit only after all sections are in place.
Remove all wooden blocks before installing the unit to the roof curb.
Page 17
Unit Assembly
All Trane air handlers ar e identified by a multiple-character model number that identifies each section. It is located on the panel on the inside of the supply fan section access door. Be sure to refer to the information on the nameplate when ordering replacement parts or requesting servic e.
Note: If the unit is shipped as a complete assembly, go to “Coil Piping and Connections” on
Prior to unit assembly , refer to th e unit submit tal drawings and un it tagging for cor rect placement of sections. Failure to review the submittal drawings could result in performance or assembly problems. If there are any discrepancies, contact your local Trane sales representative before proceeding.
All shipping supports and crating on the face of the sections must be removed and discarded to permit proper fit-up and sealing of the surfaces.
Outdoor units may be mounted on the roof with a roof curb or pier mount. Indoor units may be mounted on housekeeping pads. Refer to submittals for unit dimensions and openings.
Note: For proper operation, the unit must be suppor ted aro und the entire unit base perime ter. If
Provide clearance around the unit to allow adequate free air and necessary service access. Also, allow room for supply and return piping, ductwork, electrical connections, and coil removal.
The building roof must be able to suppor t the entire weight of the unit, roof curb and accessories. See submittals for approximate unit weights.
Prepare the roof curb or pier mount and roof openings before lifting the unit to the roof.
Check that the gasketing or sealant on the roof curb is intact and provides an air tight seal with
Complete all ductwork, piping and electrical connections only after mounting the unit.
Installation - Mechanical
page 53.
the unit is shipped in sections, the entire section perimeter must be suppor ted, as well as at the base channels of the unit splits.
the unit base.
CAH-SVX01B-EN 17
Page 18
Installation - Mechanical
TCP Model Assembly Instructions
If the model number on the nameplate begins with TCP, use the assembly instructions below. The TCP base is constructed for specific installation requirements such as standard roof curbs, structural support curbs, steel I-beam dunnage support, and pier mounting.
NOTICE
Roof Curb Structurally Sound
Check with curb manufacturer and job engineer to ensure the roof curb is structurally sufficient to support the weight of the unit. The curb should be checked to ensure it is level and square. Curb bowing, buckling, or sagging can lead to unit assembly and operation pr oblems up to complete failure.
TCP Standard Roof Curb
Figure 4. Standard roof curb The TCP unit exterior base channel is
constructed to overhang the roof curb. Unit support is provide by a square tube channel locate inside of exterior base channel. See
Figure 4. The standard curb should be designed
to properly support the unit’s weight without bow and sized to fit within the perimeter base channel.
For large units shipped in sections, see additional requirements in “TCP R oof Curbs for
Large Units with Shipping Splits” on page 21.
Air handler
base structure
Roof curb
Insulation
Page 19
Installation - Mechanical
Air handler
basic structure
Structural
steel curb
Air handler base structure
Dunnage
TCP Structural Roof Curb and I-Beam Dunnage
The TCP base for structural roof curbs (see Figure 5) and I-beam dunnage (see Figure 6) are designed to sit directly onto unit support with no overhang. The structure should be designed to properly support unit weight without bow an d siz ed to the unit’s perimeter exterior base channel.
For large units shipped in sections, see additional requirements in “TCP Roof Curbs for Large Units
with Shipping Splits” on page 21.
Figure 5. Structural roof curb Figure 6. I-beam dunnage mount
CAH-SVX01B-EN 19
Page 20
Installation - Mechanical
Air handler
base structure
Concrete
pad
TCP Flat Concrete Pad
The TCP base for concrete is designed to sit flat on the concrete with full perimeter contact. Concrete pads should be perfectly level, flat, and sized to the minimum exterior base channel measurements. See Figure 7.
Figure 7. Flat concrete pad mo un t
Page 21
TCP Roof Curbs for Large Units with Shipping Splits
Larger units with shipping splits may require full-width intermedi ate support. With any raised type roof support such as curbs or dunnage, provisions must be made to carry the weight of the base cross members at the sectional splits. Since these unit bases are designed with lifting l ugs between the sections, temporary support must be pro v ided so additional sections can be set down with a 12-inch gap to allow for working room between sections and lug removal.The use of field-provided outriggers has proven to be a successful way to accomplish this, as shown in Figure 8.
.
Figure 8. Large units with shipping splits may require intermediate support. Field-supplied
outriggers may be a useful tool in making this field joint.
Installation - Mechanical
CAH-SVX01B-EN 21
Page 22
Installation - Mechanical
TCP Joining Sections Edge-to-Edge
Units must be installed level for proper drainage of conden sate from the drain pan. In addition, each section in a multi-section unit must be properly supported.
Note: Leveling each section, beginning with the first, is critical. Failure to level and align the
sections immediately creates greater misalignment or even structural damage afterward.
1. Remove all crating and wrapping from the surfaces to be joined.
2. Place one section of the air handler into the desired position. Verify section is installed level front to back and side to side. Verify section is square to support structure, this is critical to insure proper alignment for next adjoining sections.
3. Chec k squareness measuring the critical dimensions given. Use preselected method to anchor first piece in place. This is necessary so movement will not affect pulling next sections into alignment.
4. When th e unit i s positioned and squ areness is ensured with in 1/8-inch, remove all lifting lugs located along the split plane.
5. Af ter assuring positionin g is correct, anc hor in place either by welding unit base to the cu rb or by mechanical fasteners. The first section will be used to pull remaining sections up tight so it’ s critical that first section be secured.
6. Install 4-i nch x 1/4-inch neoprene gasket to all mating surfaces of the section, including an y internal walls. This gasket must be applied to the full perimeter of the section split on both sections to be joined.
7. Move the next mating section into alignment with the positioned section. Alignment o f sections must be completed before gasket surfaces meet. The two sections should be within 12 inches to reduce the amount of dragging required.
8. Remove lifting lugs on mating section as required.
Figure 9. Insert supplied bolts through each hole of
mating connecting plate.
9. Pulling sections together on a flat surface can be done by using chain come-alongs hooked onto the welded square tubes located on each si de of the shipping split. These square tubes are designed to fully support the stress of pulling sections together. Sections should be pulled together until mating gaskets make contact and factory-supplied bolts can be installed in connecting plate.
10. When sections are close enough to allow full threading of the factory-supplied nut onto the bolt, chain come-alongs can be removed. The use of an electric impact gun to tighten bolts in a sequential manner will allow the additional section to be pulled into the final position.
1 1 . Check overall u nit length to assure proper joint compression.
Note: Failure to compress the gasketing may result in air
leakage.
12. Once the sections are pulled together, install the assembly hardware as applicable for the walls, roof, and the base as demonstrated in the following assembly sections.
Page 23
TCP Base Section Assembly with Flat Floor
#14 SMS screw
Joining strip
3-in. x 1/8-in. gasket
4-in. x 1/4-in. gasket
Joining trim
Top floor
Add caulking before installing J strip
Trim gasket after strips are installed
Add caulking after trimming gasket
Note: Failure to completely compress the gasketing may result in air leakage.
1. Join the two units and secure with factory -pro vided 5/8-inch flat washers and 5/8-inch X 2-1/2­inch grade 9 bolts though each of the six holes. See Figure 10.
2. Caulk the overlapping flange along the length of each split to maintain a seal.
Note: Use a polyurethane or equivalent caulk.
3. Before installing the pre-cut 4- inch 1 8-gauge joining strips, pre-drill holes in the floor using the 4-inch strip as a guide with a 7/32-inch drill bit at 12-inch centers.
4. Af ter holes are pre-drilled, apply an ample bead of caulk to the joint then install 4-inch strip with #14 sheet metal screws uniformly straddling the split.
5. In cases of tread plate floor , some job specifications may call for the seam to be welded. In those cases make sure the sections are pulled together tightly then weld with appropriate method. The floor construction in those cases will be suc h that the heat from welding will not aff ect the insulation.
Figure 10. TCP base assembly with flat floor
Installation - Mechanical
CAH-SVX01B-EN 23
Page 24
Installation - Mechanical
Cap
Caulk
Floor
Cap
Caulk
Floor
Floor
Floor
Gasket
Gasket
TCP Base Section Assembly with Turned-Up Floor
1. See Figure 11. Apply 4-inch x ¼-inc h neoprene gasket to the full perimeter face of eac h shipping split section.
2. Join the two sections and secure with field-provided 5/8-inch flat washers and 5/8-inch x 2 ½­inch grade 9 bolts through each of the six holes.
3. Apply a heavy bead of caulk to the inside of the U-channel.
4. P ress U-channel down over upturned flanges with moderate pressure to ensure it is fully seated onto upturned flanges. The caulk w ill cur e and act as an adhe sive to hold U-channel in place, no fasteners are required.
Figure 11. Upturned floor assembly
Page 25
TCP Wall Section Assembly
Exterior Wall Assembly (Typical)
1. See Figure 12. Ensure shipping split sections are aligned and pulled together properly.
2. Apply a bead of caulk to full height of wall joint.
3. Apply 3-inch x 1/8-inch adhesive-backed foam gasket to inner joining strip.
4. Install inner joining strip using #14 x 1.5-inch gasketed tec screws.
5. Fit the pre-cut hub cap over the joining strip the vertical height of the wall flush with the roof and secure it to the wall with # 8 sheet metal screws. Fill the top and bottom openings with caulk as a moisture seal. Screw holes can be pre-drilled with a #29 bit.
Interior Wall and Roof Joint Assembly (Typical)
1. See Figure 12. Ensure shipping split sections are aligned and pulled together properly.
2. Pre-drill interior joining strip screw holes using #29 drill bit.
3. Apply a bead of caulk the full height of interior wall joint.
4. Install joining strips using #10 sheet metal screws.
Figure 12. Wall section assembly
Installation - Mechanical
#8 x 1-in. Phillips zip screw
2 3/4-in. wide joining strip
Add caulking before installing J strip
3-in. x 1/8-in. neoprene gasket is applied to metal joining strip. Apply gasket to metal strip before installation.
#8 x 1-in. Phillips zip screw
4-in. x 1/4-in. gasket
Wall split
Wall panel section split
2 3/4-in. wide joining strip
Trim cap
#10 x 1-in. self tapping screw
Add caulking after installing J strip
CAH-SVX01B-EN 25
Page 26
Installation - Mechanical
Add caulking before installing J cap
Joining cap
4-in. x 1/4-in. gasket
#10 x 1-in. self-tapping screw
Roof panel section split
2 3/4-in. wide joining strip
#8 x 1-in. Phillips zip screw
3-in. x 1/8-in. neoprene gasket is applied to metal joining strip. Apply gasket to metal strip before installation.
Roof split outdoor unit
TCP Outdoor Roof Assembly - Single Span
1. Ensure shipping split sections are aligned and pulled together properly . See Figure 13.
2. Add a bead of caulk al ong the length of the roof seams. Install the pre-cut J-cap over the seam and secure with #14 sheet metal screws on 12-inch centers.
Note: Use a polyurethane or equivalent caulk. It may be necessary to clamp the joint together or
pre-drill to prevent separation when drilling with screws.
3. Apply caulk to end of J-cap to seal thoroughly.
Figure 13. TCP outdoor roof assembly - single span
Page 27
TCP Outdoor Roof Assembly - Multiple Span
6-inch trim cap
#10 sheet metal screw
CaulkCap and
gasket
Standing seam
10 ga. galv
#14 sheet metal screw
on 10-inch centers
18 ga. galv
Zip screws
Follow instructions in Figure 13 for installation of J-Caps.
4. The multiple roof split requires and additional cap that covers the center T-shaped seam running parallel to air flow.
5. Install #14 self drilling screws on 10-inch centers on underside of center split as shown in
Figure 14.
Figure 14. TCP outdoor roof assembly - multiple span
Installation - Mechanical
CAH-SVX01B-EN 27
6. Apply a bead of caulk to the seam the full length that roof cap will cover.
7. Apply 3-inch x 1/8-inch adhesive-backed neoprene gasket to underside of roof cap.
8. Install roof cap using #10 sheet metal screws in pre-punched holes.
9. Apply a bead of caulk over the butt joint where roof caps meet.
10. Install roof cap trim piece at joint of each roof cap using #10 sheet metal screws.
Page 28
Installation - Mechanical
18 ga. strip
18 ga. trim cap
No greater than 6 inch spacing on all fasteners
18 ga. trim cap
Gasket
#10 SMS
“Zip” screw
18 ga. strip
18 ga. trim cap
18 ga. strip
Interior of unit
TCP Indoor Roof Section Assembly (Typical)
1. Ensure shipping split sections are alig ned an d pu lled together properly.
2. Apply a bead of caulk to full height of wall joint.
3. Apply 3-inch x 1/8-inch adhesive-backed foam gasket to inner joining strip.
4. Install inner joining strip using #14 x 1.5-inch gasketed tec screws.
5. Fit the pre-cut hub cap over the joining strip the vertical height of the wall flush with the roof and secure it to the wall with #8 sheet metal screws.
6. Fill the top and bot tom openings with caulk as a moisture seal. S crew holes can be pre-drilled with a #29 bit.
7. Apply a bead of caulk over top corner of cap seam.
8. Using #10 sheet metal screws, attach corner seam trip cap as shown in Figure 15.
Figure 15. TCP indoor wall and roof assembly - trim cap
Page 29
TCP Indoor Roof Assembly - Multiple Span
6-inch trim cap
#10 sheet metal screw
CaulkCap and
gasket
Standing seam
10 ga. galv
#14 sheet metal screw
on 10-inch centers
18 ga. galv
Zip screws
1. Ensure shipping split sections are alig ned an d pu lled together properly.
2. Apply a bead of caulk to full height of wall joint.
3. Apply 3-inch x 1/8-inch adhesive-backed foam gasket to inner joining strip.
4. Install inner joining strip using #14 x 1.5-inch gasketed tec screws.
5. Fit the pre-cut hub cap over the joining strip the vertical height of the wall flush with the roof and secure it to the wall with #8 sheet metal screws.
6. Fill the top and bot tom openings with caulk as a moisture seal. S crew holes can be pre-drilled with a #29 bit.
7. Apply a bead of caulk over top corner of cap seam.
8. Using #10 sheet metal screws, attach corner seam trip cap as shown in Figure 16.
Figure 16. TCP indoor roof assembly - multiple span
Installation - Mechanical
CAH-SVX01B-EN 29
Page 30
Installation - Mechanical
Interior
wall
4-in. x 1/4-in. gasket
Secure 2-in. x 2-in. angle to wall with #14 SM screws at 12-in. centers
Caulk
Split
Split
Interior
wall
Caulk
Caulk
Split
Split
Base-to-Wall Assembly Complete
TCP Base-to-Interior Wall Section Assembly
Note: Failure to completely compress the gasketing may result in air leakage.
1 . Join the two units and secure with field provided 5/8-inc h flat washers and 5/8-inch X 2-1/2-inch
grade 9 bolts though each of the six holes.
2. Apply caulk th e leng th of t he base betwe en th e 2-inch X 2-inch angle on the one base section and the wall on the adjoining section. See Figure 17 below. Note: Use a polyurethane or equivalent caulk.
3. Secure the 2-inch X 2-inch angle to the adjoining wall with #14 sheet-metal crews on 12-inch centers along the length of the angle and wall.
Figure 17. TCP base-to-interior wall sections
Page 31
TCP Stacked Unit Assembly
Cap 18 ga. steel .050 if aluminum
Upper unit
Lower unit
Roof trim cap 14 ga. minimum .125 if aluminum
12-in. clip every 8 ft. and at all corners use grade 5 self-tapping screws 4-in. ctc
10 ga. steel .125 if aluminum
10 1/2
7 1/2
4 1/2
1 1/2
0
1. Install and assembl e al l lower sections as described in typical assembly.
2. Lift first piece of upper section into place assuring proper alignment with lower unit.
3. Install 1 0 gauge 12-inc h angl e clips as shown in Figure 18 and secure with grade 5 self-tapping screws placed 4-inches on center.
4. Lift next upper piece into place and secure shipping split with appropriate hardware then anchor to lower section as described above.
5. Continue until all sections are installed and anchored properly.
6. Install the 1 8-gauge cover trim cap using #10 self drilling screws. See Figure 18.
Figure 18. Stacked unit trim assembly
Installation - Mechanical
CAH-SVX01B-EN 31
Page 32
Installation - Mechanical
Air handler
base structure
Concrete
pad
TCC Model Assembly Instructions
NOTICE
Roof Curb Structurally Sound
Check with curb manufacturer and job engineer to ensure the roof curb is structurally sufficient to support the weight of the unit. The curb should be checked to ensure it is level and square. Curb bowing, buckling, or sagging can lead to unit assembly and operation pr oblems up to complete failure.
If your nameplate model number begins with TCC, use the assembly instructions below.
TCC Overhang Base on Common Roof Curb
1 . A base designed for use with a roof curb allows for 1/2- inch clearance around the full perimeter
of the curb.
2. The en d section must be installed first making sure it’s properly aligned with the remainder of the curb. Anchor this section securely so the base lugs can be used to pull the next section for base connections.
3. Install 3/1 6-inc h x 1.25-inch grey butyl tape to bottom rail of installed section allowing the tape to turn up each side w all approximately 8 inches. Remo ve paper backing from butyl tape. This will ensure the module-to-module joint is water tight along the bottom.
4. Lift next section onto roof curb using come-alongs to pull securely to first section. See “TCC
Joining Sections - Edge-to-Edge” on page 33 for assembly details.
TCC Flat Base to Steel Dunnage or Concrete Pad
Important: Units must be installed level for proper drainage of condensate from the drain pan
and for squareness of the sections during installation. In addition, eac h section in a multi-section unit must be properly supported.
1 . A base designed for concrete or steel dunnage has a flat channel base that allows the sections
to be installed level and square. Pad and dunn age should have unit perimeter marked clearly allowing a completely square installation. See Figure 19 and Figure 20.
2. Install first section and anchor with best method to hold securely.
3. Proceed with remaining sections per installation guidelines.
Figure 19. Steel base to concrete pad Figure 20. Flat base to steel dunnage
Air handler base structure
Dunnage
Page 33
TCC Joining Sections - Edge-to-Edge
Remove shipping blocks
NOTICE Microbial Growth!
The roof curb or foundation must be level and the condensate drain at the proper height for proper coil drainage and condensate flow. Standing water and wet surfaces inside the equipment can become an amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials.
NOTICE Level Foundation!
A level foundation is critical to proper unit and door alignment, operation, and sealing. Failure to level and align sections properly can lead to structural damage.
Important: Units must be installed level for proper drainage of condensate from the drain pan
and for squareness of the sections during installation. In addition, eac h section in a multi-section unit must be properly supported.
Note: Leveling each section, beginning with the first section, is critical. Failure to level and align
the sections immediately creates greater misalignment or even structural damage afterward.
1 . The end section must be installed first making sure it’s properly aligned with the remainder of
the curb. Anchor this section securely so the base lugs can be used to pull the next section for base connections.
2. For units with curb base, remove shipping blocks (see Figure 21).
Installation - Mechanical
Figure 21. Shipping block removal.
CAH-SVX01B-EN 33
Page 34
Installation - Mechanical
Butyl tape
Butyl tape
Butyl tape
Butyl tape
Insert hardware in each hole
3. Install 3/16-inc h x 1.25-inch ribbed grey butyl tape to bottom rail, each side wall, and top rail. Remove paper backing from butyl tape. This will ensure the module-to-module joint is water tight along the bottom. See Figure 22 and Figure 23.
Figure 22. Apply butyl tape to shipping splits
Figure 23. Butyl tape is applied to shipping splits
Page 35
Installation - Mechanical
Remove bottom hardware
Rod threaded 62-11x13.38, THD
Lockwasher .625
Nut 62-11
Figure 24. Remove lifting lug bolts 4. Lift next section into place sitting it as close to the
previous section as possible.
5. Remove lifting lug bolts. See Figure 24.
6. Using a come-along on eac h side in uniso n, pull second section securely to first section. Insert all 5/8-inch threaded rod through base lugs and tighten nuts to pull sections firmly together for final fit. See Figure 25 and
Figure 26 for assembly details.
Figure 25. Insert field provided threaded rods
CAH-SVX01B-EN 35
Figure 26. Insert threaded ro ds
Page 36
Installation - Mechanical
Washer .563 ID x 1.375 OD
Washer .563 ID x 1.375 OD
Bolt .500-13 x 3.500 Hex
Nut .500-13 Hex Mach
TCC Internal Shipping Split Frame Assembly (Typical)
1. Af ter exterio r ship pi ng sp li t has been seal ed, interior 2.5-inch x 2.5-inch angles can be bolted together using supplied hardware (see Figure 27, Figure 28, and Figure 29).
Figure 27. Join internal shipping split frame
Figure 28. Join internal shipping split frame- Graphic 1 Figure 29. Join internal shipping split frame- Graphic 2
Page 37
TCC Wall Section Assembly (Typical)
A
DETAIL A
Screw 10-16 x .750 self-driller
Screw 10-16 x .750 self-driller
Screw 10-16 x .750 self-driller
2 Screws .250-14 x 1.00 Hes WSH HD self-driller
Butyl tape
Seam cap
Seam cap
Butyl tape
Joint cap
1. Verify external unit squareness.
2. To complete the exterior joint, install a bead of caulk full height of side panel joint.
3. Over caulk, install 3/1 6-inc h x 1.25-inch ribbed grey butyl the full height of the side panel up to underside of roof overhang. Leave the paper backing on this tape, sealing the joint does not require this to be removed. The paper will be facing out towards seam cap.
4. Install side seam cap over butyl tape and secure with #10-16 x 0.750 self-drilling screw. The bottom two screws on this seam cap will be larger , ¼ x 20 self drillers with neoprene gasket (see
Figure 30).
TCC Indoor Roof Section Assembly (Typical)
1. Verify external unit squareness.
2. Apply the 1.25-inch x 0.33-inc h ribbed butyl tape to the exterior of the roofs covering the seam of the two adjoining sections (see method sheet).
3. Install seam cap o ver the bu tyl , uni formly straddlin g the spli ts. Secure with the provided number 10 sheet metal screws. See Figure 30.
Figure 30. Install seam cap over the butyl tape
Installation - Mechanical
CAH-SVX01B-EN 37
Page 38
Installation - Mechanical
TCC Outdoor Roof Section Assembly (Typical)
1 . Join two outdoor roof panels together at the seams at th e direction of airflow and secu re them
in place with 5/16-inch x 3/4-inch bolts and 5/16 loc k nuts. Cut the proper length of roof joint strip to cover the seam between two outdoor roof panels at the direction of airflow . (exclude single outdoor roof panel) (see Figure 31).
Figure 31. Join outdoor roof panels at the seams
2. Join outdoor roof panels together at the seams in the direction perpendicular to airflow and secure them in place with 5/16-inch x 3/4-inch bolts and 5/16 loc k nuts. Install the roof joint strip to cover the seam between two outdoor roof panels in the perpendicular to airflow direction of. Use 3/8-inch butyl tape to cover the seam between two outdoor roof panels overhang at the side the unit. Bend joint strip over roof panel and use two number 1 0 sheet metal screws (o ne in each roof panel) to secure joint strip. T rim the roof joint strip to insure that it does not protrud e more than 1/16-inch beyond outdoor roof overhang (see Figure 32 and Figure 33).
Page 39
Figure 32. Trim roof joint strip
Figure 33. Trim roof joint strip
Installation - Mechanical
CAH-SVX01B-EN 39
Page 40
Installation - Mechanical
Apply two layers of 1-inch x 2-inch gasketing around all openings in the lower unit roof.
Upper unit
Lower unit
Factory installed engagement plate
Apply .188-inch x 2-inch gasketing around lower unit perimeter
.250 - 14 x .75 leached self-driller screws in every hole, around upper unit base perimeter.
TCC Stacking Procedure
1 . After bot tom section of stac ked arrangement is in place, ensure top is clean and free of debris.
2. Apply two layers of 0.188-inch x 2-inch gasketing around perimeter of top section layout. See
Figure 34.
3. Apply two layers of 1-inch x 2-inch tape around perimeter of openings in lower unit roof. See
Figure 34 and Figure 35.
4. Lift upper section into place carefully aligning into proper position (see Figure 35).
5. Install 0.250-14 x 0.750 self drilling screws in each hole around upper unit base perimeter.
6. Install flashi ng at base of top section (see Figure 35 Detail A).
Figure 34. Upper base connection to lower unit gasket.
Page 41
Figure 35. Stacked assembly
Roof
lower unit
Screw
10-16 x .750 self-driller
Flashing
Wall
Base
Detail B
Detail A
Screw 10-16 x .750
Flashing
Base
PCAP
Detail A
Upper unit
.250-14 x .750 leached self-driller
screws in every hole, around
upper unit base perimeter.
Apply 2 layers of .188 x 2-in. gasket
around lower unit perimeter
Factory-installed
engagement plate
Lower unit
Detail B
Apply two layers of 1-in. x 2-in. gasket around all openings in the lower unit roof.
Installation - Mechanical
CAH-SVX01B-EN 41
Page 42
Installation - Mechanical
Section 5
Section 4
Section 4
Flashing
Screw
10-16 x .750
Section 1
Detail A
Detail A
Section 1
Section 2
Section 3
TCC Energy Wheel and CDQ Wheel Assembly
Units are shipped unstacked.
1. Set sections 1 – 5 of the unit in place in sequence order as shown in Figure 36 and secure as needed.
– Prior to setting section 2 and 3 apply 2-in. x 1-in. thic k gasket across full un it width along the
wheel’s upper-to-lower septum.
Figure 36. Energy wheel and CDQ wheel assembly
2. P rior to upper unit placement, install 0.188-in. x 2-in. gasketing on entire length of engagement plate and/or lower unit perimeter as needed. Engagement plates are used when the upper and lower unit dimensions are not matched. Refer to “TCC Stacking Procedure” on page 40.
3. Apply two layers of 1-in. tall x 2-in.wide gasketing around perimeter of roof opening in lower unit section prior to lifting upper unit. Refer to “TCC Stacking Procedure” on page 40.
Note: If gasketing is not installed first, leakage may occur between the upper and lower units and
will result in CFM loss.
4. Upper uni t with duct opening should be placed within 1 -inc h of lower duct opening in order to sufficiently compress gasket.
– Once unit is set in place verify the gasket seal between openings.
5. After installing all of the upper unit sections, Install all-thread rods (field-provided) fastening both upper and lower sections to the wheel section.
6. F asten the upper unit to the lower unit perimeter cap with ¼ -inch self-drilling screws through base rail.
Note: A drill extension will be required to ensure straight alignment.
Page 43
7. Units will have field installed flashing. Remove upper unit lif ting lugs, in order to install flashing
Butyl Tape
Hood
Butyl Tape
Pipe Cabinet
Roof Curb
Unit Base Rail
Mounting Channel
between the upper and lower unit. – Parts are number matched to the unit. Each piece of flashing will be identified with a unit
section number in which it applies.
– Top edge of flashing will be placed behind upper unit base rail flange and fastened to lower
unit perimeter cap. – Use #10 screws to install flashing. – For external/outdoor units caulk the corners and top edge of the flashing.
Pipe Cabinet Installation
1. Af ter air hand ler is complet ely ins t al led an d checked for accuracy of level and square, pipe cabinet install can begin.
2. Remove bolts holding the lifting lugs in place from the base of the air handler.
3. Check to ensure that the structure the pipe cabinet is to be installed on is square and level.
4. Install 3/16-inch x 1. 25-inch grey ribbed butyl tape to flanged side of pipe cabinet wall and remove paper backing from tape. See Figure 37.
Figure 37. Pipe cabinet installation
Installation - Mechanical
CAH-SVX01B-EN 43
Page 44
Installation - Mechanical
Pipe Cabinet
Unit
5. Lift cabinet into place aligning base tab with lifting lug brackets on air handler base.
6. Slide pipe cabinet tight up against mounting channels on side wall of air handler.
7. Install bolts through lifting lug gussets to anchor pipe cabinet base to the air handler. See
Figure 38. and Table 1.
Figure 38. Pipe cabinet detail
Table 1. Pipe cabinet hardware
Qty X-Code Code Description Description
4 X25017800000 BOLT; 0.625-11 X 1.750 5/8-1.75 in. Bolt 4 X28021500000 NUT; 0.62-11 5/8-11 Nut 4 X22020800000 LOCKWASHER; 0.625 ID 5/8-in. Lock Washer 8 X22050313010 WASHER; 0.656 ID X 1.312 OD Flat Washer
8. Check pipe cabinet side walls to ensure they are plumb.
9. Apply a bead of caulk along the corner between the pipe cabinet and air handler wall prior to installing connecting angle.
Page 45
Figure 39. Pipe cabinet
TOP VIEW
A
DETAIL A
DETAIL B
See Detail B
AHU
Pipe Cabinet
Ribbed Butyl tape
Screw 10-16 x .750 self-driller
Pipe cabinet outer roof
Slots provided to allow final adjustment of outer roof
AHU outdoor roof
“Picture frame” mounting chanels factory assembled to unit
Inside corner cap
Ribbed Butyl tape (see Note 1)
Roof and base parts removed for clarity
“Picture frame” mounting chanels factory assembled to unit
Ribbed Butyl tape
Ribbed Butyl tape
(see Note 1)
Inside corner cap
Pipe cabinet wall
Note:
1. Seam to be sealed with three-ribbed Butyl tape prior to attaching inside corner cap with screws (10-16 x .750 self-driller).
Installation - Mechanical
10. Install inside corner cap. See Figure 39 Detail A and B.
1 1 . Install 3/16-inch x 1 . 25-inch grey ribbed butyl tape to unit wall where pipe cabinet roof connects.
12. Lift pipe cabinet roof into place and attach to unit wall with screws. See Figure 39.
CAH-SVX01B-EN 45
Page 46
Installation - Mechanical
Bottom supply/return airflow
Trane AHU
base (typical)
Field-supplied
rigid duct
Trane AHU
base (typical)
Field-supplied
rigid duct
Duct Connections
All duct connections to the units should be installed in accordance with the standards of the National Fire Protection Association (NFPA) for selecting and installing of air conditioning and ventilating systems other than residence type (NFPA 90A), and residence typ e warm air heating and air conditioning systems (NFPA 90B).
T o ensure the highest fan efficiency , duct turns and transitions must be made carefully, minimizing air friction losses and turbulence. Proper duct work installation by suc h organizations as SMACNA (Sheet Metal and Air Conditioning Contractors National Association, Inc.) should be adhered to.
Bottom Opening Duct Installation
1. Install gasket to duct flange to ensure air tight seal.
2. Install duct into place underneath framed opening in unit base per Figure 40. Refer to factory curb layout provided with unit submittals for duct size and location.
Figure 40. Field-supplied duct connection to AHU bottom supply/return air opening
Page 47
Installation - Mechanical
Unit wall
Unit floor
Supply opening in floor
Edge of supply opening
Unit base
Roof curb
Bottom of unit base elevation
Field­supplied duct
Gasket
Building roofing and structure may vary per job
0.5
Additional 1/2 inch of
duct length option
Not to scale.
Option A
Note: Bottom of unit base elevation is 1/2 inch lower than edge of duct opening in bottom of unit. During unit installation on roof curb, either raise field-provided duct or add additional gasket material to compensate for the 1/2 inch offset.
3. Bottom of unit base elevation is ½ inch lower than edge of duct opening in bottom of unit. During unit installation on roof curb, either raise field provided duct per Option A (see Figure 41) or add additional gasket material to compensate for the ½ inch offset per Option B (see
Figure 42).
Figure 41. Field-supplied duct connection option details -
Figure 42. Field-supplied duct connection option details -
Option A
Note: Bottom of unit base elevation is 1/2 inch lower than edge of duct opening in bottom of unit. During unit installation on roof curb, either raise field-provided duct or add additional gasket material to compensate for the 1/2 inch offset.
Component Installation Requirements
Option B
Unit wall
Unit
base
Gasket
Roof
curb
Building
roofing
and structure
may vary per job
Unit floor
Supply opening in floor
Additional 1/2 in. gasket
Option B
Additional 1/2 inch of gasket material
option. Not to scale.
0.5
Field-
supplied
duct
Edge of supply opening
Bottom of unit base elevation
WARNING
Hazardous Voltage with Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors befor e servicing . Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropr iate manufacturer’ s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before
CAH-SVX01B-EN 47
servicing could result in death or serious injury.
Each component in the Custom air handler may have installation requirements that could affect the unit’s pe rformance.
Note: For components included in the unit but not included in this manual, refe rence the
component manufacturers specific Installation, Maintenance, and Operation manual. Copies of these manuals are either included in the package with this unit IOM or are attached to the components mounted in the unit.
Page 48
Installation - Mechanical
Jam nut
Shipping
bolt
Fan
base
Shipping
tie-down
block (shim)
Adjusting nut
Fans
The fan and motor assembly are internally isolated. The fan and motor bases are bolted to a minimum of four spring isolators. The isolators are secured to the fan section support base. Shipping tie-down blocks are bolted to the isolators between the fan base and the isolator support frame.
To activate the isolation, remove the shipping tie-down blocks. Retain these blocks for use in adjusting isolators if necessary.
Isolator Adjustment
Note: Isolators are pre-adjusted and set at the factory. Follow this procedure only if necessary and
Figure 43. Isolator
as it applies to the isolators used in this unit. This procedure can and should be performed by one person to ensure that the proper sequence is followed.
Isolators are selected for distribution of equipment weight, but may not all compress the same. This procedure assumes the base surface is level. Isolators are not intended to be leveling devices.
1 Verify that the shipping bolts that hold the fan base in
a fixed position have been removed. See Figure 43.
2. R emove the jam nut on top of the isolator adjusting stud at the first isolator to be adjusted. Check that the shipping block is in place.
3. Turn the adjusting nut two or three turns only, counterclockwise on each isolator in a sequenced manner. The equipment weight will compress the spring inside the housing approximately 1/4 inch.
4. Check that the bushing on the isolator stud is centered in the isolator. Adjust to center by moving the stud in the fan base hole.
5. This procedure will raise the equipment load until the isolators are all off the shims (shipping tie-down blocks) approximately 1/32-inch (the thickness of a credit card), and the internal gap is approximately equal to the external gap.
Note: Do not adjust isolators once the fan base is off of the shipping tie down blocks.
6. Cont inue adjusting other isolators in sequence and repeat the same adjustment. Continue until all isolators are adjusted.
7. Replace the jam nut on each isolator adjusting bolt, tighten the nu t, and remo ve the shipp ing tie down block.
Page 49
Control Dampers
If the damper actuators are not factory mounted in stall damper actuators and connecting linkage. Check damper operation and linkage alignment.
Damper blades should be non-binding. Adjust damper frame as necessary to ensure free blade movement.
Magnahelic Air Filter Gage
Check zero adjustm ent of the gage. T urn both vent valves to the “Vent” position and adjust the gage pointer to zero by means of the external adjustment screw in the face of the gage. After zeroing, turn the vent valves to the “Line” position.
Air Filters
WARNING
Hazardous Voltage with Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors befor e servicing . Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropr iate manufacturer’ s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Installation - Mechanical
Front Load Filters
Most filters in custom units are installed in unitary sheet metal frames. Filters are secured with a metal clip. There are several different styles.
To install filters:
1. Disconnect power to the unit.
2. Open or remove the filter clip.
3. Remove the filter from the rack.
4. Install new filters with the directional arrows pointing in the direction of airflow.
5. Secure the filter using the appropriate clip for each filter.
Review Figure 44 through Figure 47 for an explanation of the methods for securing the different types of filters.
The filters are often installed in a pre/post filter configuration. Be sure to note the order of installation.
Note: Filters must have an airtight seal to prevent air bypass.
CAH-SVX01B-EN 49
Page 50
Installation - Mechanical
Figure 44. C-70 fastener holds 2-inch filter
Figure 46. Bag filter show with C-70 fastener Figure 47. C-80 spring fastener secures cartridge
Figure 45. C-86 fastener (shown) or C-77 fastener holds 4-
inch pleated filt ers
Side Load Filters
Most filters in custom units are installed in unitary sheet metal frames. If unit is provided with side access rack, do the following for installation:
2-inch or 4-inch flat filters
1. Disconnect the power to the unit.
2. Open the filter section access door and remove the filters and block-offs from their installed position.
3. Slide the filter into the rack.
4. Some side load racks will be provided with block-off plates.
5. Close and secure the door, making certain the door closes snug against the block- off (see
Figure 48).
Page 51
Figure 48. Filter block-off placement
Installation - Mechanical
Bag or Cartridge Filters
1. Disconnect power to the unit.
2. K eeping the bag filters folded, slide each filter into the filter rack, pushing them tightly against the unit. Pleats should be in the vertical position.
3. If using optional pre-filters, slide them into the appropriate filter rack.
4. If block-offs are provided with the unit, slide the block-offs into the filter track.
5. Close and secure the access door, making certain the door closes snug against the rack.
Note: The block-off is intended to make a seal when the access door is closed. It may require a few
adjustments to ensure a proper seal.
CAH-SVX01B-EN 51
Page 52
Installation - Mechanical
AHU outdoor roof
Butyl caulk tape
1.00 W x .125T.
Hood
Nut-Hex .31-18
Detail A
Screw self-driller 10-16 x .750
Butyl caulk tape
1.00 W x .125T.
Nut-Hex .31-18
Bolt .313-18 x .750 Hex
Bracket Support
Angle Hood Support (when required)
Bolt .313-18 x .750 Hex
Outdoor Unit Weather Hood(s)
1. Per the unit drawing determine mounting location of the unit weather hoods.
2. Using the factory provided screws mount the weather hoods to the unit.
3. On la rger units, weather hoods may be large enough to require angled down supports . In those cases, the angles are shipped attached to the hood but will need to be connected to the air handler by the installing contractor. See Figure 49.
Note: It is required that the hoods be sealed to the unit using field provided caulk or gasket.
Figure 49. Hood installation
Page 53
Coil Piping and Connections
General Coil Piping Recommendations
Proper installation, piping, and trappi ng is necessary to ensure satisfactory coil operation and to prevent operational damage:
Support all piping independently of the coils.
Provide swing joints or flexibl e fit ti ngs on all connections that are adjacent to heating coils to absorb thermal expansion and contraction strains.
If the coil was ordered with factory-mounted controls, install the control valves. The valves ship separately.
Note: The contractor is responsible for supplying the installation hardware.
For best results, use a short pipe nipple on the coil headers prior to making any welded flange or welded elbow type connections.
If extended drains and vents are required on water coils, they must be field-installed or ordered from the factory.
Pipe coils counterflow to airflow.
NOTICE Connection Leaks!
Use a backup wrench when attac h ing piping t o coils with copper headers to prevent damage to the coil header. Do not use brass connectors because they distort easily and could cause connection leaks.
When attac hing the piping to the coil header , make the connection only tight enough to prevent leaks. Maximum recommended torque is 200 foot-pounds.
NOTICE Over Tightening!
Do not use teflon-based products for any field connections because their high lubricity may allow connections to be over-tightened, resulting in damage to the coil header.
Use pipe sealer on all thread connections.
NOTICE Leakage!
Proper ly seal all penetrations in unit casing. Failure to seal penetrations from inner panel to outer panel may result in unconditioned air entering the unit, and water infiltrating the insulation, resulting in equipment damage.
After completing the piping connections, seal around pipe from inner panel to outer panel.
CAH-SVX01B-EN 53
Page 54
Coil Piping and Connections
Drain Pan Trapping
WARNING
No Step Surface!
Do not walk on the sheet metal dr ai n pan. Walking on the drain pan could cause the supporting metal to collapse. Failure of the drain pan could result in death or serious injury.
Threaded condensate drain connections are provided on only one side of the coil section. Pitch the connection lines horizontal or downward toward an open drain. Trane recommends installing a plug to facilitate cleaning of the trap.
Figure 50 illustrates the proper trapping, piping, and operation of the trap for negative pressure
sections. Use the formula under the figure to determine the correct minimum depth for the condensate trap.
Figure 51 illustrates the proper trapping, piping, and operation of the trap for positive pressure
sections.
Note: Positive pressure traps require a different design than negative pressure traps.
If a section has a drain pan for cleaning purposes only, it does not need a trap; however, a cap or shutoff valve should be installed on the drain con nection. Only sections handling condensate, such as a cooling coil section or moisture eliminator section, re qu ir e a tr ap.
NOTICE Wa ter Damage!
When more than one section has a drain pain, trap each section individually. Connecting all drains to a common line with only one trap can result in condensate retention and possible water damage to the air handler or adjoining space.
Page 55
Coil Piping and Connections
K
H
L
L = H + K + pipe diameter
where:
K = 1/2 inch (minimum) H = 1/2 inch plus the total unit
static pressure at worst case (loaded filters)
Figure 50. Drain pan trapping for section under negative pressure
L = H + J + pipe diameter where: H = 1 inch for each inch of negative pressure* plus 1 inch J = 1/2 H *Negative pressure = total unit static pressure at worst case (loaded filters) minus external pressure
L
Normal operation
Figure 51. Drain pan trapping for section under positive pressure
H
J
CAH-SVX01B-EN 55
Page 56
Coil Piping and Connections
Steam Coil Piping
Air handlers fitted with steam coils have labeled holes for pipi ng penetrations. Figure 52 and
Figure 53 illustrate typical steam coil piping configurations. See Table 2 for the codes of system
components in these figures. The coil condensate return line must be piped f ull size of the condensate trap connection, except
for a short nipple screwed directly into the coil header’ s condensate return tapping. Do not b ush or reduce the coil return tapping size.
Table 2. Code of system components for piping figures
Code System component
FT Float and thermostatic steam trap GV Gate valve OV Automatic two-position (ON-OFF) control valve VB Vacuum breaker ST Strainer AV Automatic or manual air vent MV Modulating control valve
Figure 52. Typical piping for Type N steam coils and
horizontal tubes for horizontal airflow
Figure 53. T y pical pipi ng for T yp e NS steam coils and
horizontal tubes for horizontal airflow
Page 57
Coil Piping and Connections
NOTICE
Breaker Cracking Pressure!
The 1/2-inch NPT, 15 degree swing check valve vacuum breaker is recommended because other vacuum breakers, such as spring-loaded ball-check breakers, have cracking pressures as high as
1.25 inches Hg (1 7 inc hes of wat er). Vacuum breakers with fitting sizes smaller than 1/2 inch NPT
are too small to relieve vacuum quick enough to ensure complete condensat e dr ainag e. Other types of swing check valv e v acuum br eak ers ar e acceptable if the fittings size is not smaller than 1/2-inch NPT and the cracking pressure is not larger than 0.25 inches Hg (3.4 inches of water). Failure to follow these instructions may result in equipment damage.
To prevent coil damage, complete the following recommendations:
Install a 1/2-inch NPT, 15 degree swing check valve vacuum breaker with cracking pressure of
0.25 inches Hg (3.4 inc hes water) or lower at the to p of the coil. This vacuum breaker should be installed as close to the coil as possible.
For coil types A, AA, N, NS, and NN, install the vacuum breaker in the unused condensate return tapping at the top of the coil.
Types T and ST coils require that the vacuum breaker be located as near as possible to the supply connection.
Vent the vacuum breaker line to atmosphere or connect it into the return main at the discharge side of the steam trap
Note: V acuu m breaker relief is mandatory when the coil is controlled by a modulating steam
supply or automatic two position (ON-OFF) steam supply valve. Vacuum breaker relief is also recommended when face-and-bypass control is used.
NOTICE
Coil Condensate!
Condensate must flow freely from the coil at all times to pr event coil damage from water hammer , unequal ther mal str esses, fr eeze-up and/or cor rosion. In all steam coil installations, th e condensate return connections must be at the low point of the coil. Failure to follow these instructions may result in equipment damage.
Proper steam trap installation is necessary for satisfactory coil performance and service life. For steam trap installation:
1. Install the steam trap discharge 12 inches below the condensate return connection. Twelve inches pro v ides sufficient hydrostatic head pressure to overcome trap losses and ensures complete condensate removal.
a. Use float and thermostatic traps with atmospheric pressure gravity condensate return, with
automatic controls, or where the possibility of low-pressure supply steam exists. (Float and thermostatic traps are recommended because of gravity drain and continuous discharge operation.)
b. Use bucket traps only when the supply steam is not modulated and is 25 psig or higher.
CAH-SVX01B-EN 57
Page 58
Coil Piping and Connections
AV
AV
AV
GV
MW
Water supply
main
Water
return main
Drain
Air flow
Pitch down
Note: T rane steam coils require a minimum of 2 psi of pressure to ensure even heat distribution.
2. Trap each coil separately to prevent holding up condensate in one or more of the coils.
3. Install strainers as close as possible to the inlet side of the trap.
4. If ins tal lin g coils in series airflow, control each coil bank independently with an automatic steam-control valve. Size the traps for each coil using the capacity of the first coil in direction of airflow.
5. Use a modulating valve that has linear flow c haracteristics to obtain gradual modulation of the coil steam supply.
Note: Do not modulate systems with overhead or pressurized returns unless the condensate is
drained by gravity into a receiver, vented to atmosphere, and returned to the condensate pump.
6. Pitch all supply and return steam piping down 1 inch for every 10 feet in the direction of the steam or condensate flow.
Note: Do not drain the steam mains or take-offs through the coils. Drain the mains ahead of the
coils through a steam trap to the return line.
7. Ensure overhead returns have 1 psig of pressure at the steam trap discharge for every 2 feet of elevation for continuous condensate removal.
Water Coil Piping
Figure 54, Figure 55, and Figure 56
illustrate typical water coil piping configurations.
Type WA, 5A, 5W, D, K, W, UW, TT, P,2, P4, and P8 water coils are self-venting only if the water velocity exceeds
1.5 feet per second (fps) in the coil tubes. T ype UU, WD, and 5D water coils are self-venting only if the water velocity exceeds 2.5 fps in the coil tubes. See the unit submittals for coil water velocity. If the water velocity is below these minimums, vent the coil by one of the following methods:
1. Install an air vent in the top pipe plug tapping of the return header.
2. When the return line rises above the top of the coil, vent from the top of the return header horizontally to the return piping.
Note: T, ST, and TT coils are designed
with larger than normal end tube sheet holes to allow for maximum expansion. Air leakage around tubes should be expected and handled by capping over coil ends or by sealing around tubes with a pliable sealant such as silicon.
Figure 54. Typical piping for type 5W one-row water coil
GV
Water supply
main
Water
TV
GV
GV
return main
Air flow
AV
Level
GV
AV
Drain
Figure 55. Typical piping for type 5A, 5W two-row, K, W 3- to 12-row, WD, D,
and DD water coils
Page 59
Figure 56. Typical piping for type W or WA 1-row water coil
AV
AV
TV
GV
GV
GV
GV
GV
Drain
Air flow
Water supply main
Water return main
18 Pitch down
Pitch down
AV
AV
AV
Water
supply main
Water
return main
GV
Drain
Air flow
GV
MV
Figure 57. Typical piping for stacked water coils
Coil Piping and Connections
CAH-SVX01B-EN 59
Page 60
Coil Piping and Connections
Discharge
line
Manual ball valve
Access
port
Filter
Access
port
Access
port
Filter drier with access port
Manual
angle valves
Check/relief
valve
Condensing unit
Condenser and
sbucooler coil
Compressors
Liquid line
Access
port
Manual
ball valve
Solenoid
valve
Moisture-
indicating
sight glass
Expansion
valves
Evaporator coil
Distriburtor
Manual ball valve
Suction lineFrostat™ control
Manual
ball valve
Kit with sensor - X13790452010 SEN-01212 Kit with switch - X13100429010 THT 02442
Refrigerant Coil Piping
Note: Refer to “Important En vironmental Concerns!” on page 2 for information on handling
refrigerants.
Use Figure 58 to determine the proper, relative sequence of the components in the refrigerant lines that connect the condensing unit to an evaporator coil. Refer to “Examples of Field-Installed
Evaporator Piping” on page 63 for more detailed schematics of evaporator piping.
Figure 58. Example of placement for split-system components
Liquid Lines
Line Sizing. Properly sizing the liquid line is critical to a successful split-system application. The selected tube diameter must provide at least 5°F [2.7°C] of subcooling at the expansion valve throughout the operating envelope. Increasing the size of the liquid line will not increase the available subcooling.
Routing. Instal l the liquid line with a slight slope in the direction of flow s o that it can be routed with the suction line. Minimize tube bends and reducers because these items tend to increase pressure drop and to reduce subcooling at the expansion valve. Liquid line receivers, other than those that are factory-installed, are not recommended.
Page 61
Coil Piping and Connections
Cut here for piping
Perforated plate (packed elbow)
Panel
Venturi type distributor
Coil
Insulation. The liquid line is generally warmer than the surrounding air, so it does not require insulation. In fact, heat loss from the liquid line improves system capacity because it provides additional subcooling.
Components. Liquid-line refrigerant components ne cessary for a successful job include a filter drier, access port, solenoid valve, moisture-indicating sight glass, expansion valve(s), and ball shutoff valves. Figure 58 illustrates the proper sequence for positioning them in the liquid line. Position the components as close to the evaporator as possible.
Filter drier. There is no substitute for cleanliness during system installation. The filter drier prevents residual contaminants, introduced during installation, from entering the expansion valve and solenoid valve.
Access port. The access port allows the unit to be charged with liquid refrigerant and is used to determine subcooling. This port is usually a Schraeder valve with a core.
Solenoid valve. In split systems, solenoid valves isolate the refrigerant from the evaporator during off cycles; under cer tain conditions, they may also trim the amount of active evaporator as compressors unload. Generally, the “trim” solenoid valve is unnecessary for variable-air­volume comfort-cooling applications, and is only required for constant-volume applications when dehumidification is a concern.
Moisture-indicating sight glass. Be sure to install one moisture-indicating sight glass in the main liquid line. The only value of the sight glass is its moisture indication ability. Use actual measurements of temperature and pressure—not the sight glass—to determine subcooling and whether the system is properly charged. The moisture indi cator/sight glass must be sized to match the size of the liquid line at the thermal expansion valve.
Thermal expansion valve. The expansion valve is the throttling device that meters the refrigerant into the evaporator coil. Metering too much refrigerant floods the compressor; metering too little elevates the compressor temperature. Choosing the correct size and type of expansion valve is critical to ensure it will correctly meter refrigerant into the evaporator coil throughout the entire operating envelope of the system. Correct refrigerant distribution into the
coil requires an expansion valve for each distributor.
Figure 59. Ty pe F refrigerant coil with packed elbow
The thermal expansion valve must be selected for proper size and capacity. The size of the expansion valve should cover the full range of loadings. Check that the valve will successfully operate at the lightest load condition. For improved modulation, choose expansion valves with balanced port construction and external equalization.
Cut the process tube and cap assembly from the liquid connection as shown in Figure 59 and install the expansion valve directly to the liquid connections.
CAH-SVX01B-EN 61
Page 62
Coil Piping and Connections
NOTICE Valve Damage!
Disassemble the thermal expansion valve before completing the brazing connections. If necessary, wrap the valve in a cool, wet cloth while brazing. Failure to protect the valve from high temperatures may result in damage to internal components.
Suction Lines
Line sizing. Proper suction-line sizing is required to guarantee the oil returns to the compressor throughout the system’s operating envelope. At the same time, the line must be sized so that the pressure drop does not excessively affect capacity or efficiency. To accomplish both objectives, it may be necessary to use two different line diameters: one for the horizontal run and for vertical drops, and another for the vertical lifts.
Routing. T o prevent residual or condensed refrigerant from “free-flowing” toward the compressor , install the suction line so it slopes slightly—that is, by ¼ inch to 1 inch per 10feet of run—toward the evaporator. When the application includes a suction riser, oil must be forced to travel the height of the riser. Riser traps and double risers are unnecessary in the suction line when the refrigerant coil is used with Trane condensing units.
Avoid putting refrigerant lines underground. Refrigerant condensation or installation debris inside the line, service access, and abrasion/corrosion can quickly impair reliability.
-Insulation. Any heat that transfers from the surrounding air to the cooler suction lines increases
the load on the condenser (reducing the system’s air-conditioning capacity) and promotes condensate formation (adversely affecting indoor air quality). After operating the system and testing all fittings and joints to verify the system is leak-free, insulate the suction lines all the way to inner side panel to prevent heat gain and unwanted condensation.
Components. Installing the suction line requires field installation of these components: a filter, access port, and a Frostat™ control when the refrigerant coil is used with Trane condensing units. Position them as close to the compressor as possible.
Note: Placement of the Frostat control is illustrated in Figure 58 on page 60.
Filter. The suction filter prevents contaminants, introduced during installation, from entering the compressor. For this reason, the suction filter should be the replaceable-core type, and a clean core should be installed after the system is cleaned up.
Access port. The access port is used to determine suction pressure. This port is usually a Schraeder valve with a core.
Frostat™ coil frost protection. The Frostat control is the preferred method for protecting evaporator coils from freezing when the refrigerant coil is used with Tr an e condensing units. It senses the suction-line temperature and temporarily disables mec hanical cooling if it detects frost conditions. The control is mec hanically attac hed to the outside of the refrigerant line, near the evaporator, and wired to the unit control panel.
Ball shutoff valve. Adding manual, ball-type shutoff valves upstream and downstream of the filter simplifies replacement of the filter core.
Page 63
Coil Piping and Connections
Examples of Field-Installed Evaporator Piping
Single-Circuit Condensing Unit: Evaporator Coil with One Distributor
Figure 60. Single-circuit evaporator coil with one distributor
1. Pitch the liquid line slightly—1 inch/10 feet [1 cm/3 m]—so that the refrigerant drains toward the evaporator. See Figure 60.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction header toward the suction riser—that is, 1 inch/ 10 feet [1 cm/3 m] in the direction of flow. Use the tube diameter that matches the suction­header connection.
4. For the vertical riser, use the tube diameter recommended by the condensing unit manufacturer. Ensure the top of the riser is higher than the evaporator coil.
5. Ar range the suction line so the refrigerant gas leaving the coil flows downward, past the lowest suction-header outlet, before turning upward.
6. Pitch the suction line slightly—1 inch/1 0feet [1 cm/3 m]—so the refrigerant drains toward the evaporator.
7. Insulate the suction line.
CAH-SVX01B-EN 63
Page 64
Suction line
7, 8
Liquid
line
Evaporator coil
with horizontal-split
(standard) circuiting
Evaporator coil with
intertwined circuiting
Liquid
line
‘Trim’
solenoid valve
‘Pump-down’
solenoid valve
Sight glass
1
Filter drier
Filter drier
Solenoid
valve
Thermal
expansion
valve (TXV)
9
2
2
1
9
7, 8
3
4
4
5
5
6
6
3
Distributor
Thermal
expansion
valve (TXV)
Sight glass
Distributor
S
S
S
Coil Piping and Connections
Single-Circuit Condensing Unit: Evaporator Coil with Two Distributors
Figure 61. Single-circuit evaporator coil with two distributors 1. Pitch the liquid line slightly—1 inch/10 feet
[1 cm/3 m]—so the refrigerant drains toward the evaporator. See Figure 61.
2. P rovide one expansion valve per distributor.
3. Slightly pitc h the outlet line from the suction header toward the suction riser—that is, 1 inch/10feet [1 cm/3 m] in the direction of flow. Use the tube diameter that matches the suction-header connection.
4. Arrange the suction line so the refrigerant gas leaving the coil flows downward, past the lowest suction-header outlet, before turning upward. Use a double-elbow configuration to isolate the thermal expansion valve bulb from other suction headers.
5. F or horizontal tubing, use the tube diameter recommended by the condensing unit manufacturer.
6. F or the ver tical riser, use the tube diameter recommended by the condensing unit manufacturer. Ensure the top of the riser is higher than the evaporator coil.
7 . Pitch the suction line slightly—1 inch/10feet
[1 cm/3 m]—so the refrigerant drains toward the evaporator.
8. Insul ate the suction lin e.
9. Only use a “trim” solenoid valve for constant-volume, humidity-sensitive applications. For all other applications, install a single solenoid valve (the “pumpdown” solenoid valve) between the liquid-line filter drier and the sight glass.
Page 65
Coil Piping and Connections
Single-Circuit Condensing Unit: Evaporator Coil with Four Distributors
Figure 62. Single-circuit evaporator coil with four distributors 1. Pitch the liquid line slightly—1 inch/10 feet
[1 cm/3 m]—so the refrigerant drains toward the evaporator. See Figure 62.
2. P rovide one expansion valve per distributor.
3. Slightly pitc h the outlet line from the suction header toward the suction riser—that is, 1 inch/10feet [1 cm/3 m ] in the direction of flow. Use the tube diameter that matches the suction-header connection.
4. Arrange the suction line so the refrigerant gas leaving the coil flows downward, past the lowest suction-header outlet, before turning upward. Use a double-elbow configuration to isolate the thermal expansion valve bulb from other suction headers.
5. F or horizontal tubing, use the tube diameter recommended by the condensing unit manufacturer.
6. F or the vertical riser, use the tube diameter recommended by the condensing unit manufacturer. Ensure the top of the riser is higher than the evaporator coil.
7 . Pitch the suction line slightly—1 inch/1 0 feet
[1 cm/3 m]—so the refrigerant drains toward the evaporator.
8. Insul ate the suction lin e.
9. Only use a “trim” solenoid valve for constant-volume, humidity-sensitive applications. For all other applications, install a single solenoid valve (the “pumpdown” solenoid valve) between the liquid-line filter drier and the sight glass.
CAH-SVX01B-EN 65
Page 66
Coil Piping and Connections
Dual-Circuit Condensing Unit: Evaporator Coil with Two Distributors)
Figure 63. Dual-circuit evaporator coil with two distributors
1. Pitch the liquid lines slightly—1 inch/10 feet [1 cm/3 m]—so the refrigerant drains toward the evaporator. See Figure63.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction header toward the suction riser—that is, 1 inch/ 10 feet [1 cm/3 m] in the direction of flow. Use the tube diameter that matches the suction­header connection.
4. The top of the Circuit 1 suction riser must be higher than the bottom evaporator coil. Use the tube diameter recommended by the condensing unit manufacturer for the riser.
5. Ar range the suction line so the refrigerant gas leaving the coil flows downward, past the lowest suction-header outlet, before turning upward.
6. The top of the Circuit 2 suction riser must be higher than the top evaporator coil. Use the tube diameter recommended by the condensing unit manufacturer for the riser.
7. Pitch the suction lines slightly—1 inch/1 0 feet [1 cm/3 m]—so the refrigerant drains toward the evaporator.
8. Insulate the suction lines.
Page 67
Coil Piping and Connections
Dual-Circuit Condensing Unit: Evaporator Coil with Four Distributors
Figure 64. Dual-circuit evaporator coil with four distributors 1 . Pitch the liquid line slightly—1 inch/10 feet
[1 cm/3 m]—so the refrigerant drains toward the evaporator. See Figure 64.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction header toward the suction riser—that is, 1 inch/10 feet [1 cm/3 m] in the direction of flow. Use the tube diameter that matches the suction-header connection.
4. Arrange the suction line so the refrigerant gas leaving the coil flows downward, past the lowest suction-header outlet, before turning upward. Use a double-elbow configuration to isolate the thermal expansion valve bulb from other suction headers.
5. F or horizontal tubing, use the tube diameter recommended by the condensing unit manufacturer.
6. F or the vertical riser , use the tube diameter recommended by the condensing unit manufacturer. Ensure the top of the riser is higher than the evaporator coil.
7. Pitch the suction line slightly—1 inch/ 10 feet [1 cm/3 m]—so the refrigerant drains toward the evaporator.
8. Insul ate the suction lin e.
9. The top of the Circuit 1 suction riser must be higher than the bottom evaporator coil. Use the tube diameter recommended by the condensing unit manufacturer for the riser.
10. The top of the Circuit 2 suction riser must be higher than the top evaporator coil. Use the tube diameter recommended by the condensing unit manufacturer for the riser.
CAH-SVX01B-EN 67
Page 68
Coil Piping and Connections
Dual-Circuit Condensing Unit: Evaporator Coil with Eight Distributors
Figure 65. Dual-circuit evaporator coil with eight distributors
1 . Pitch the liquid line slig htly—1 inch/1 0 feet
[1 cm/3 m]—so the refrigerant drains toward the evaporator. See Figure 65.
2. Provide one expansion valve per distributor.
3. Slightly pitch the outlet line from the suction header toward the suction riser—that is, 1 inch/10 feet [1 cm/3 m] in the direction of flow. Use the tube diameter that matches the suction-header connection.
4. A rrange the su ction line so the refrigeran t gas leaving the coil flows downward, past the lowest suction-header outlet, before turning upward. Use a double-elbow configuration to isolate the TXV bulb from other suction headers.
5. For horizontal tubing, use the tube diameter recommended by the condensing unit manufacturer.
6. F or the vertical riser, use the tube diameter recommended by the condensing unit manufacturer. Ensure the top of the riser is higher than the evaporator coil.
7. Pitch the suction line slightly—1 inch/ 10 feet [1 cm/3 m]—so the refrigerant drains toward the evaporator.
8. Insul ate the suction lin e.
9. The top of the Circuit 1 suction riser must be higher than the bottom evaporator coil. Use the tube diameter recommended by the condensing unit manufacturer for the riser.
10. The top of the Circuit 2 suction riser must be higher than the top evaporator coil. Use the tube diameter recommended by the condensing unit manufacturer for the riser.
11. Only use a “trim” solenoid valve for constant-volume, humidity-sensitive applications. For all other applications, install a single solenoid valve (the “pumpdown” solenoid valve) between the liquid-line filter drier and the sight glass.
Page 69
Installation - Electrical
WARNING
Hazardous Voltage w/ Capacitors!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the equipment cannot be inadvertently energiz ed. For variable frequency drives or other ener gy storing components provided by Trane or others, ref er to the appropriate manufacturer’s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have dischar ged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of capacitors, see
PROD-SVB06A-EN or PROD-SVB06A-FR
NOTICE Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Use of aluminum or other type of wiring may result in galvanic corrosion or overheating. F ailu re to use copper conductors may result in equipment damage.
If the unit does not include a factory-mounted star ter, wiring to the unit fan motor must be provided by the installer and must comply with all national and local electrical codes. The installer must also furnish a service disconnect switch in compliance with national and local electrical codes.
Fan motors require motor overload protective devices that are rated or selected in compliance with the National Electric Code (NEC) or Canadian Electric Code. Specific unit and motor connection diagrams are provided on the starter/VFD if Trane-provid ed, or refer to the motor nameplate.
If wiring directly to the motor, a flexible connection at the motor to permit fan belt adjustment should be provided. Fractional horsepower motors may be factory connected to a terminal box on the unit. If this construction is provided, the in staller should complete field wiring to this connection box. For a typical high voltage wiring schematic, see Figure 66.
CAH-SVX01B-EN 69
Page 70
Installation - Electrical
Figure 66. Typical high voltage wiring schematic
Page 71
Installation - Electrical
NOTICE Penetration Leaks!
Proper ly seal all penetrations in unit casing. Failure to seal penetrations from inner panel to outer panel may result in unconditioned air entering the unit, and water infiltrating the insulation, resulting in equipment damage.
Figure 67. Transformer plate
All units with starters or variable-frequency drives (VFDs) that have direct-digital controllers (DDCs) are provided with line voltage to 120 Vac power transformers (see Figure 67) with power 120 Vac to 24 Vac control transformers (see Figure 68). Figure 69 shows a typical VFD power box.
To provide field-wiring to units with DDC or low limit controls:
If VFD or starter is not factory-mounted, provide 120Vac power to a transformer in the valve jac k when a separate circuit is recommended (see Figure 68).
Install outside-air sensor and space sensor, if ordered.
For valve jack moun tin g an d wirin g detail, see Figure70.
Note: The valve jack is typically located at the air -leaving side of th e coil connection inside panel.
Figure 68. 120 to 24 Vac Control
Transformer
For coils with headers on both sides of the unit, the valve jack is located at the return connection for water coils and the supply connection for steam coils.
Figure 69. Variable-frequency drive
(VFD)
CAH-SVX01B-EN 71
Page 72
Installation - Electrical
Figure 70. Valve jack wiring details
Conduit assembly
Valve quick connect
Quick Connects
The actuators, factory-mounted or field-supplied, are separately wired and controlled by a direct­digital controller or other building logic. Figure 71 illustrates the typical quick connect scheme.
Figure 71. Typical quick connects with wiring identification
Page 73
Controls Interface
The portable operator display is used for temporary connection to and operation of T racer MP580/ 581 and AH540/541 controllers. With the portable operator display, you can monitor data, c han ge setpoints, monitor alarms, and override points. The portable operator display includes a 10 ft (3 m) cable with connector that is stored in the storage compartment of the carrying bag. The cable cannot be disconnected from the operator display . Keep this document w ith the portable operator display for access to calibration and cleaning instructions.
Note: The portable operator display is not used for timeclock scheduling. To provide schedu ling
you must use a Tracer Summit system.
Connecting the Operator Display
To connect the portable operator display:
1. Open the controller enclosure door.
2. Attach the operator-display cable to the operator-display connector on the controller circuit board. The operator display receives power from the controller and turns on automatically when it is connected to the controller.
Setting Up the Operator Display
NOTICE Equipment Damage!
To clean the operator display, use a cloth dampened with commercial liquid glass cleaner. Spraying water or cleansers directly on the screen may result in equipment damage.
This section shows how to calibrate the operator display touch screen and how to adjust the brightness and contrast. T o set up the operator display screens and security , see CN T-SVP01C-EN Programming Tracer MP580/581 Programmable Controller programming guide.
Calibrating the Operator Display
To calibrate the operator display:
1. On the home screen, press Setup. The Setup menu appears.
2. Page down to view the next screen.
3. Press Calibrate Touch Screen. A calibration screen appears.
NOTICE Equipment Damage!
Do not allow the operator display to come in contact with sharp objects. This may result in equipment damage.
4. Touch the target using a small, pliable, blunt object, suc h as a pencil eraser or your finger. Hold until the beeping stops. A second calibration screen appears.
5. Ag ain, touch the target with the object. Hold until the beeping stops. The Advanced S electio n screen appears.
6. Press Hom e. The home screen appears.
CAH-SVX01B-EN 73
Page 74
Controls Interface
Adjusting Brightness and Contrast
To adjust the brightness and contrast of the operator display:
1. On the home screen, press Setup. The Setup menu appears.
2. Page down to view the next screen.
3. P ress the Adjust Brightness and Contrast buttons. The Brightness and Contrast screen appears.
4. To increase the brightness, press the buttons along the top row, in sequence, from left to right. To decrease the brightness, press the buttons from right to left.
Note: Contrast adjustment is not available on all computer display models.
5. To increase the contrast, press the buttons along the bottom row, in sequence, from left to right. To decrease the contrast, press the buttons from right to left.
6. Press Hom e. The home screen appears.
External Communications Port
On units that have been selected with the external communications port, both the operator display and Rover service tool can be connected without shutting off the unit through the external communications port. Remove the cover plate on the port and plug into the RJ-11 port for the operator display or the RS 485 port for the Rover service tool. This enables continuous operation of the Air Handling unit without d isruption to the operating co nditions of the unit. When servicing of the unit is complete, replace the cover plate on the external port to eliminate the air leakage path.
Page 75
Start-Up
Once the air handler has been assembled and installed, attention must be directed to individual components for proper operation. Before operating the unit, complete the pre-startup checklist.
WARNING
Hazardous Voltage with Capacitors!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors befor e servicing . Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. For variable frequency drives or other energy storing components provided by Trane or others, refer to the appropr iate manufacturer’ s literature for allowable waiting periods for discharge of capacitors. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
Note: For additional information regarding the safe discharge of capacitors, see
PROD-SVB06A-EN.
Pre-Startup Checklist
General Checks
Ensure the unit has been installed level.
Ensure supply-air and return-air ducts have been connected.
Ensure damper operator motors and connecting linkage have been installed.
Verify damper operation and linkage alignment. Damper blade and linkage positioning may have changed due to shipping and hand lin g vi bratio n.
Check that air filters are in place and positioned properly.
Remove any debris from the unit interior.
Close and secure all unit access doors.
Note: UL-listed units require a removable latch on access doors. The door clip shipped with the
unit meets this requirement.
Inspect electrical connections to the unit and unit controllers. – Connections should be clean and secure. – Compare the actual wiring with the unit diagrams. – Reference the appropriate controller manual for more details about starting units with
factory-mounted controls.
Leave this manual with the unit.
Fan-Related Checks
If the unit is internally isolated, ensure that the fan isolator tie-down bolts have been removed.
Rotate all fan wheels manually to confirm they turn freely in the proper direction.
Check fan shaft bearings, fan wheel, and drive sheave set screws for proper torque settings. – Fan sheaves should be tight and aligned. – Bearing set screws should be torqued.
Inspect the inlet vane assembly for freedom of movement. If resistance is above the recommended torques, check the assembly for any binding or misalignment. Do not force the vanes.
Check fan drive belt tension.
Inspect fan motor and bearings for proper lubrication, if ne cessary.
CAH-SVX01B-EN 75
Page 76
Start-Up
Coil-Related Checks
NOTICE
Proper Water Treatment!
The use of untreated or improperly treated water in coils may re sult in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. Trane assumes no responsibility fo r equipment f ailu r es whic h result from untreated or impr oper ly tr eat ed w at er, or saline or brackish water.
Ensure coil and condensate drain piping connections are complete.
Check the piping and val ves for leaks.
If unit has a refrigerant coil, ensure that it has been charged and leak-tested according to the
Remove all foreign material from the drain pan and chec k the pan opening and condensate line
For steam coils, slowly turn the steam on full for at least 1 0 minutes before opening the fresh
– Open or close the valves to check operation. – The drain lines should be open.
instructions provided with the condenser equipment. Adjust the superheat setting.
for obstructions.
air intake on units with fresh air dampers.
Motor-Related Checks
Obtain an IOM from the motor manufacturer for the specific motor installed. The motor manufacturer’s recommendations take precedence for all matters related to the start-up and routine maintenance of the motor.
Check the motor lubrication for moisture and rust. – Remove and clean grease plugs to inspect. – If moisture is present, consult an authorized repair shop for bearing inspection/replacement.
– If no moisture is present, refer to the motor manufacturer’ s lubrication recommendations for
– The motor manufacturer may recommend lubricating the motor as part of their routine
Check motor winding. An acceptable winding resistance reading is from 6 meg-ohms to infinity . If reading is less than 5 mega-ohms, the wi nding should be dried out in an o ven or by a blower .
Inspect the entire motor for rust and corrosion.
Bump-start the unit and confirm the fan wheel rotates properly, as indicated by the rotation arrow located on the fan housing.
Note: Note: For motor warranty needs, contact you local Trane sales office.
This may require removal and tr ansport of motor.
proper lubrication.
startup instructions.
Page 77
Unit Operation
100A
2
AvgVoltage×
----------------------- -------------------------- -
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to measure the speed of rotating co mponents. Have a qualified or licensed service individual who has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions when exposed to rotating components could result in death or serious injury.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qu alified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electr ical components could result in death or serious injury.
Before complete startup, bump-start the unit and confirm the fan wheel rotates properly, as indicated by the rotation arrow located on the fan housing. After initial startup:
Calculate the motor voltage imbalance, notifying the power company to correct unacceptable
Periodically check the fan belt tension.
Start-Up
imbalances.
Calculate Motor Voltage Imbalance
After startup, measure the motor voltage and amperage on all phases to ensure proper operation. The readings should fall within the range given on the motor nameplate. The maximum allowable voltage imbalance is 2 percent.
V oltage imbalance is defined as 100 times the sum of the absolute deviation of the three voltages from the average, divided by twice the average voltage. For example, if the three measured voltages are 221, 230 and 227, the average voltage would be 226 volts. The percent of voltage imbalance is then calculated:
Voltage imbalance =
where: A = (226-221) + (230-226) + (227-226)
Voltage imbalance = 2.2% (not acceptable)
In the example, 2.2 percent imbalance is not acceptable and the power company should be notified to correct it.
CAH-SVX01B-EN 77
Page 78
Start-Up
V-BELT DRIVE KIT
1627373
MODULE 0400
PURCHASE ORD. NUMBER B24597-061 H5D073B A CUSTOMER’S KIT # H5D073B A-012-0400 MTR HP.= 10.0 FAN RPM = 1458 CD = 9.4 AT 3.00 TRN OPN TENSION INFO - 3.86 LB., 0.14 IN. DRIVE’S BELTS - B40 MOTOR SHEAVE - 2VP75X 1 3/8 MOTOR BUSHING - NONE REQUIRED FAN SHEAVE - 2B5V80 FAN BUSHING - B 1 7/16
Small O-Ring
Force Scale
Large O-Ring
Span Scale
Belt Span
Belt Span
64
Deflection =
Tension the Fan Belt
NOTICE Belt Tension!
Do not over-tension belts. Excessive belt tension will reduce fan and motor bearing life, accelerate belt wear and po ssi b ly cause shaft failure. Under tensioning belts is the primary cause of premature belt failure. Belts should not squeal at startup. Recheck belt tension after 8 hours, 24 hours, and 100 hours of operation and monthly thereafter.
Figure 72. Tension drive belt label
Proper belt tension is required to ensure maximum bearing and drive component life and is based on motor horsepower requirement. A label located on the bearing support on the dri ve side of the unit lists all drive parts, the proper belt tension, and deflection for that tension for the specific drive (Figure 72).
If the drive is changed from the original, proper belt tension can be estimated using Table 3.
The correct operation tension for a V-belt drive is the lowest tension at which the belts wil l not slip under the peak load conditions. It may be necessary, however, to increase the tension of some dri ves to reduce excessive belt flopping or to reduce excessive startup squealing.
Figure 73. Belt tensioner
Check the fan belt tension at least three times during the first days of operation because there is a rapid decrease in tension until the belt settles in. To measure belt tension, use a belt tensiometer (see Figure 73). Determine actual deflection by depressing one belt with the belt tensiometer and measuring the deflection relative to the other belts or to belt line (see Figure 74). Adjust the belt tension to the correct pounds force and tighten all set screws to the proper torque.
Figure 74. Belt tension measurement
Page 79
Table 3. Typical sheave diameter and deflection force
Cross
section
A, AX
B, BX
C, CX
D
3V, 3VX
5V, 5VX
8V
Smallest sheave
diameter range
(in.)
3.0–3.6
3.8–4.8
5.0–7.0
3.4–4.2
4.4–5.6
5.8–8.6
7.0–9.0
9.5–16.0
12.0–16.0
18.0–20.0
2.2–2.4
2.65–3.65
4.12–6.90
4.4–6.7
7.1–10.9
11.8–16.0
12.5–17.0
18.0–22.4
Speed (rpm)
range
1,000–2,500 3.7 5.5 4.1 6.4 2,501–4,000 2.8 4.2 3.4 5.0 1,000–2,500 4.5 6.8 5.0 7.4 2,501–4,000 3.8 5.7 4.3 6.4 1,000–2,500 5.4 8.0 5.7 9.4 2,501–4,000 4.7 7.0 5.1 7.6
860–2,500 n/a n/a 4.9 7.2
2,501–4,000 n/a n/a 4.2 6.2
860–2,500 5.3 7.9 7.1 10.5
2,501–4,000 4.5 6.7 7.1 9.1
860–2,500 6.3 9.4 8.5 12.6
2,501–4,000 6.0 8.9 7.3 10.9
500–1,740 11.5 17.0 14.7 21.8
1,741–3,000 9.4 13.8 11.9 17.5
500–1,740 14.1 21.0 15.9 23.5
1,741–3,000 12.5 18.5 14.6 21.6
200–850 24.9 37.0 n/a n/a
851–1,500 21.2 31.3 n/a n/a
200–850 30.4 45.2 n/a n/a
851–1,500 25.6 38.0 n/a n/a 1,000–2,500 n/a n/a 3.3 4.9 2,501–4,000 n/a n/a 2.9 4.3 1,000–2,500 3.6 5.1 4.2 6.2 2,501–4,000 3.0 4.4 3.8 5.6 1,000–2,500 4.9 7.3 5.3 7.9 2,501–4,000 4.4 6.6 4.9 7.3
500–1,749 n/a n/a 10.2 15.2 1,750–3,000 n/a n/a 8.8 13.2 3,001–4,000 n/a n/a 5.6 8.5
500–1,749 12.7 18.9 14.8 22.1 1,750–3,000 11.2 16.7 13.7 20.1
500–1,749 15.5 23.4 17.1 25.5 1,750–3,000 14.6 21.8 16.8 25.0
200–850 33.0 49.3 n/a n/a
851–1,500 26.8 39.9 n/a n/a
200–850 39.6 59.2 n/a n/a
851–1,500 35.3 52.7 n/a n/a
Start-Up
Belt Deflection Force (lbs)
Super gripbelts and
unnotched gripbands
Used belt New belt Used belt New belt
Gripnotch belts and
notched gripbands
Determine Fan Speed
Fan speed can be determined using a strobe-type tachometer, or revolution counter. Check unit vibration if the fan speed is c hanged more than five percent from the original designed
speed, or if parts such as shaf ts, fan wheels, bearings, or other drive components are replaced. Do not exceed the maximum fan speed.
Pay particular attention to any vibration, noise, or overheating of the motor and fan bearings; however, note that bearings may run warm during break in.
CAH-SVX01B-EN 79
Page 80
Start-Up
D
Fixed Sheave
C
B
A
Adjustable
Sheave
Straight
Edge
Lines must
be parallel
Center line
must coincide
Fixed
Sheave
Figure 75. Proper drive alignment
Align Fan and Mot or Sheaves
Align the fan and motor sheaves using a straightedge. The straightedge must be long enough to span the distance between the outside edges of the sheaves. When the sheaves are aligned, the straightedge will touch both sheaves at points A through D (see Figure 75) to confirm the shaft is parallel. For uneven width sheaves, place a string in the center groove of both sheaves and pull tight. Adjust the sheaves and tighten the sheave set screws to the proper torque given in Table 4.
Check Multiple Belts
Tighten the belts slightly and rotate the drive several times. On multiple belt drives, ensure the force of deflection is approximately the
same on each belt by pushing each belt in an equal distance at a point halfway from each sheave (see Figure 75). If this force is not the same for each belt, the motor and fan shaft are not parallel. Realign as required. After realignment, tighten the belts ag ain to the standard belt tensioning specifications. If the force is still not the same for all belts, the belts or sheaves are worn and must be replaced.
Table 4. Fan and drive compound torque settings (inches)
Screw Size Hex Key Square Head Hex Head Torque (in.-lb.) Torque (ft.-lb.)
1/4 1/8 3/8 7/16 66-90 5.5-7.5
5/16 5/32 1/2 1/2 126-164 10.5-13.7
3/8 3/16 9/16 9/16 228-300 19.0-25.0
7/15 7/32 5/8 5/8 348-450 29.0-37.5
1/2 1/4 3/4 3/4 504-650 42.0-54.2 5/8 5/16 15/16 15/16 1290-1390 107.0-116.0
#10 3/32 - - 28-40 2.3-3.3
Page 81
Traq™ Dampers
Ventilation Control Module
Velocity (2-10 Vdc)
GND
24 Vac
GND
1TB1-3
1TB1-4
1TB1-5
1TB1-6
volts 2()
8
------------------------------
volts 2()
8
------------------------------
Figure 76. Traq damper terminal connections
T raq dampers are low-leak dampers that modulate and measure airflow. Each Traq damper section is supplied with a factory-mounted ventilation control module (VCM) on the interior of the mixing box. The VCM has an input terminal for power and an output terminal for air velocity (see
Figure 76). A direct-digital controller controls the factory-mounted and wired actuators.
Start-Up
VCM (Transducer) Calibration. The VCM has an auto-zero function that recalibrates the
transducer once every minute. When troubleshooting, allow for the recalibration time before making any measurements.
Input Power. The only input the VCM needs is the 24 Vac power connected to terminals 1TB1–5
and 1TB1–6.
Output Velocity Signal. The 2 to 10 Vdc linear output signal from the VCM represents air
velocity. This voltage can be converted to represent airflow (cfm or L/s) using the formula below,
Table 5 and Table 6.
In Table 6 the cfm at 10Vdc is a calculated value based on area and peak velocity. In certain situations, it can be advantageous to raise the velocity of air through the remaining Traq dampers by closing off one or more dampers in the unit. The cfm at 10Vdc can be recalculated based on the proportion of remaining Traq dampers or by multiplying the remaining area of dampers by peak velocity.
Table 5. Altitude adjustment factors
Sea level = 1.0
Elevation (feet) k
1000 0.982 2000 0.964 3000 0.949 4000 0.930 5000 0.914 6000 0.897 7000 0.876 8000 0.860 9000 0.846
10,000 0.825
Airflow = k (cfm @ 10V) or Airflow = k (L/s @ 10V)
For example, if the VCM on a size 30 air handler at sea level (k=1) has a 10-volt signal, it would represent 17,335 cfm (8181 L/s) through the Traq damper. If the voltage were 6 volts, airflow through the Traq damper would be 8,668 cfm (4091 L/s).
CAH-SVX01B-EN 81
Page 82
Start-Up
Table 6. Back or Top Inlet Traq Dampers - Air-Mixing and Economizer Section - VCM v oltag e v ersus airflo w at sea level
Part Number
DMP01123 13 1 0.9213 2500 2303 1087 DMP01124 16 1 1.3956 2650 3698 1745 DMP01663 20 1 2.1806 2650 5779 2727 DMP01125 24 1 3.1400 2700 8478 4001 DMP01126 28 1 4.2739 2700 11540 5446
Traq Damper Size (inches) Quantity Total Area (ft2)
Peak Velocity
(fpm)
CFM @ 10VDC Peak Velocity L/S @ 10VDC
Fan Inlet Airflow Measuring System
Figure 77. Piezometer ring airflow
measurement
A fan inlet airflow measuring system with a piezometer ring is available on many centrifugal and plenum fans. Each system comes with a differential pressure transmitter . The piezometer rin g is connected to the LO por t of the transmit ter and the reference pressure point is connected to (or actually is) the HI port of the transmitter. See Figure 77.
Wiring
In the absence of a factory-provided control system, consult the transmitter manufacturer or the factory for wiring.
Note: Ensure that the transmitter has a separate power source.
Transmitter Sizing
The T rane specification requires that the flow meter option have a total accuracy of 5 percent. The total accuracy is a combination of:
how accurately the piezometer ring itself is in sensing airflow
how accurately the transmitter senses the differential pressure
how accurately the controller translates the signal from the transmitter to a diff er e ntial pressure.
Selecting the proper transmitter is critical in order to get accurate airflow measurements using the piezometer ring. How accurately the transmitter se nses the differential pressure is dependent on:
the pressure range selected
accuracy of the selected transmitter
Page 83
T rane air handlers use a 0-20 inch range transmitter as standard. T o sufficiently cover V AV turndown on the smallest fans with the above range, a transmitter with an accuracy of 0.25 percent (full scale) is used as standard. If a field-provided transmitter with a lower accuracy is selected, the range should be chosen closer to the actual, maximum pressure differential expect ed for the application.
The transmitter outputs a signal that represen ts the differentia l pressure which is used to calculate airflow. T o adequately calculate and display the airflow for the smaller fans, ensure that the analog input is programmed with enough decimal places to sufficiently represent the pressure differential being measured. For instance, Rover should be used to increase the number of decimal places being used (to a maximum of 4) on an MP-580/58 1 controller in lieu of the default zero.
Note that the adjustment of the “Zero” and “Span” controls on the transmitter itself are not required at time of installation. The transmitter is factory-calibrated to the range selected and cannot be significantly adjusted to “tighten” the range closer to the pressure being read for the given application. The adjustments are primarily provided to account for any drift that may occur over time.
Transmitter Calibr ation
The transmitter is factory -calibrated to a specific pressure range with a 0 -20 inc h w .g. range being used in most cases. To check calibration and to adjust if necessary, consult the transmitter manufacturer or the factory for specific procedures.
The transmitter outputs a linear , 4-20 mA signal representin g a differential pressure measurement. With this measurement, the airflow through the fan can be calculated using the following equation :
Start-Up
Constant Factor K
CFM = K * SQRT(DP) Where: CFM = Airflow (ft3/min.) assuming a standard air density of 0.075 lbm/ft3. K = A constant factor that’s unique for each fan. See next section for more information. DP = Differential pressure (inches w.g.) being measured by the transmitter.
Significant differences in elevation and/or temperature will af fect the density of air . F or air at a constant, non-standard density, a field-obtained K factor can be used. Alternatively, the following equation can be used to continuously correct the equation above:
ACFM = CFM * SQRT(0.075/ρ) Where: ACFM = Actual airflow (ft3/min) corrected for non-standard air density.
ρ = Density (lbm/ft
3
) of the air at the inlet to the fan.
Note: Alternative units, including SI, can be used in place of the IP units abo ve although the
K-factor must be converted appropriately.
The constant factor K is unique for eac h fan and is primarily a function of the area and the g eometry of the fan inlet. Pre-engineered factors are available from the factory for fan types where the airflow measurement system is available.
Field-obtained factors can provide maximum accuracy. To obtain the factor in the field, measure the differential pressure being output from the transmitter while measurin g the airflow through the system. Once these two values have been measured, simply solve for K using the following equation:
K = ACFM/SQRT(DP) Where: K = Field-provided constant factor. ACFM = Actual airflow (ft3/min) being measured at the air density being measured. DP = Differential pressure (inches w.g.) being measured by the transmitter.
CAH-SVX01B-EN 83
Page 84
External Insulating Requirements
NOTICE Microbial Growth!
Wet interior unit insulation can become an amplification site for micr obial gr o wth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth on the interior insulation, the insulation should be removed and replaced pr ior to operating the system.
The following areas should be specifically addressed, as applicable:
Supply and return water piping connections
Supply and return refrigerant piping connections
Condensate drain lines and connections
Outdoor-air-intake duct connections
Discharge duct connections
Special requirements for low-temperatur e-air systems
Page 85
Routine Maintenance
The following checklist is provided as an abbreviated guide to periodic maintenance. Detailed procedural information is given after this checklist.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safe ty warnings provided throughout this manual concerning these procedures. When possible, disconnect all electric al power including remote disconnect and discharge all energy storing devices suc h as capacitors before servicing. Follow proper loc kout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warn in gs provided, could result in death or serious injury.
WARNING
Rotating Components!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Secure drive sheaves to ensure rotor cannot freewheel. Failure to secure drive sheaves or disconnect power before servicing could result in death or serious injury.
Table 7. Routine maintenance checklist
Frequency Maintenance After 48 hours of operation Every week
Every month
Every three to six months
Every year
Belts have acquired their permanent set. Readjust but do not ov ertighten. See “Tension the Fan Belt” on page 78 for more information.
Observe unit weekly for any change in running condition and unusual noise.
• Clean or replace air filters if clogged or dirty; coat permanent filters with oil after cleaning; and, change bag filters when pressure drop is 1 in. wg. See “Air Filters” on page 86 for more information.
• Relubricate fan bearings if necessary. See “Fan Bearing Lubrication” on page 89 for more information.
• Check and adjust fan belt tension.
• Check fan bearing grease line connections. Lines should be tight to the bearings.
• Check bearing and motor bracket bolt torque and bearing setscrew torque.
• Align fan and motor sheaves. Tighten sheave set screws to the proper torque. See “Align Fan and Motor Sheaves” on
page 80 for more information.
• Inspect and clean drain pans. See the “Drain Pans” section on page 87 for more information.
• Tighten electrical connections.
• Ins pect coils for dirt build-up. See “Coils” on page 91 for more information.
• Inspect the unit casing for corrosion. If damage is found, clean and repaint the surface with a rust-resistant primer.
• Clean the fan wheels and fan shaft. See “Fans” on page 88 for more information.
• Inspect and clean drain pans.
• Che ck damper linkages, set screws, and blade adjustment. Clean, but do not lubricate, the nylon dampe r rod bushings.
• Clean damper operators.
• Inspect electrical components and insulation.
• Inspect wiring for damage.
• Rotate the fan wheel and check for obstructions in the fan housing. The wheel should not rub on th e fan housing . Adjust the center if necessary and tighten wheel set screws to the proper torque.
• Lubricate motor bearings in accordance with motor manufacturer’s recommendations (see the “Motor Bearing Lubrication” section on page 90 for more information). This may only need to be done every 2 to 3 years.
• Check condition of gasketing and insulation around unit, door and dampers.
• Examine flex connections for cracks or leaks. Repair or replace damaged material.
CAH-SVX01B-EN 85
Page 86
Routine Maintenance
Air Filters
WARNING
Rotating Components!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Secure drive sheaves to ensure rotor cannot freewheel. Failure to secure drive sheaves or disconnect power before servicing could result in death or serious injury.
Throwaway Filters
T o replace throwaway filters, install new filters with the directional arrows pointing in the direction of airflow.
Note: Bag and cartridge filters must have an air tight seal to prevent air bypass. If using other than
Permanent Filters
To clean permanent filters:
1. Disconnect all electrical power to the unit.
2. Wash the filter under a stream of water to remove dirt and lint.
3. Remove oil from the filter with a wash of mild alkali solution.
4. Rinse the filter in clean, hot w a ter and allow to dry.
5. Coat both sides of the filter by immersing or spraying it with Air Maze Filter Kote W or an
6. Allow to drain and dry for about 12 hours.
7. Reinstall the filter.
Note: It may be preferable to keep extra, clean filters to replace the dirty filters to minimize unit
Trane-supplied filters, apply foam gasketing to the vertical edges of the filter.
equivalent.
downtime for filter maintenance.
Front Load Filters
Most filters in custom units are installed in unitary sheet metal frames. Filters are secured with a metal clip. There are several different styles.
To install filters:
1. Disconnect power to the unit.
2. Open or remove the filter clip.
3. Remove the filter from the rack.
4. Install new filters with the directional arrows pointing in the direction of airflow.
5. Secure the filter using the appropriate clip for each filter. The filters are often installed in a pre/post filter configuration. Be sure to note the order of
installation.
Note: Filters must have an airtight seal to prevent air bypass.
Page 87
Side Load Filters
Routine Maintenance
Most filters in custom units are installed in unitary sheet metal frames. If unit is provided with side access rack, do the following for installation:
2-inch or 4-inch flat filters
1. Disconnect the power to the unit.
2. Open the filter section access door and remove the filters and block-offs from their installed position.
3. Slide the filter into the rack.
4. S ome side load racks will be provided with block- off plates. Install them into the rack last before closing the door.
5. Close and secure the door, making certain the door closes snug against the block-off.
Cartridge or Bag Filters
To replace cartridge or bag filters:
1. Disconnect all electrical power to the unit.
2. Remove the dirty filters and block-offs from their installed position.
3. Keeping the new bag filters folded, slide each filter into the filter rack, pushing them tightly against the unit.
Note: The pleats on bag filters should be in the vertical position.
4. If using the option al pr e-fi lters, replace them on the appropriate filter rack.
5. If fixed and adjustable bloc k-offs are provided with the unit, slide the fixed block-offs into the filter track before the adjustable block-off.
Note: The adjustable bloc k-off should always be installed last, next to the access door.
6. Close and secure the access door. If the door can be closed without compressing the filter, adjust the block-off by loosening its screws and position it to provide an airtight seal.
Drain Pans
WARNING
Hazardous Chemicals!
Cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper handling should include goggles or f ace shie ld, chemical r esistant glo ves , boots, apr on or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury.
WARNING
No Step Surface!
Do not walk on the sheet metal dr ai n pan. Walking on the drain pan could cause the supporting metal to collapse. Failure of the drain pan could result in death or serious injury.
The condensate drain pan and drain line must be checked to ensure the condensate drains as designed. This inspection should occur a minimum of every six months or more often as dictated by operating experience.
If evidence of standing water or condensate overflow exists, identify and remedy the cause immediately. Refer to “Troub leshooting” on page 98 for possible causes and solutions.
CAH-SVX01B-EN 87
Page 88
Routine Maintenance
To clean drain pans:
1. Disconnect all electrical power to the unit.
2. Wearing the appropriate per sonal protective equipment, remove any standing water.
3. Scrape solid matter off of the drain pan.
4. Vacuum the drain pan with a vacuum device that uses high-efficiency particulate arrestance
5. Thoroughly clean any contaminated area(s) with a mild bleach and water solution or an EPA-
6. Immediately rinse the affected surfaces thoroughly with fresh water and a fresh sponge to
7. Allow the unit to dry completely before putting it back into service.
8. Be careful any contaminated mater ia l does not contact other areas of the unit or building.
Fans
WARNING
Rotating Components!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensur e the equipm ent can n ot be inadv ertently energized. Secure drive sheaves to ensure rotor cannot freewheel. Failure to secure drive sheaves or disconnect power before servicing could result in death or serious injury.
(HEPA) filter s with a minimum efficiency of 99.97 percent at 0.3 micron particle size.
approved sanitizer specifically designed for HVAC use.
prevent potential corrosion of metal surfaces.
Properly dispose of all contaminated materials and cleaning solution.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the equipment can not be inadvertentl y e nergized. Failur e to disconnect power before servicing could result in death or serious injury.
Inspecting and Cleaning Fans
Fan sections of air handlers should be inspected every six months at a minimum or more frequently if operating experience dictates. If evidence of microbial growth (mold) is found, identify and remedy the cause immediately. Refer to “Troubleshooting” on page 98 for possible causes and solutions. To clean the fan section:
1. Disconnect all electrical power to the unit.
2. Wearing the appropriate personal protective equipment, remove any contamination.
3. Vacuum the section with a vacuum device that uses high-efficiency particulate arrestance (HEPA) filter s with a minimum efficiency of 99.97 percent at 0.3 micron particle size.
4. Thoroughly clean any contaminated area(s) with a mild bleach and water solution or an EPA­approved sanitizer specifically designed for HVAC use.
5. Immediately rinse the affected surfaces thoroughly with fresh water and a fresh sponge to prevent potential corrosion of metal surfaces.
6. Allow the unit to dry completely before putting it back into service.
7. Be careful any contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution.
Page 89
Fan Bearing Lubrication
Align set screws
Align set screws
NOTICE
Bearing Failure!
Do not mix greases with different bases within the bearing. Mixing grease within the bearing may result in premature bearing failure.
The grease used in electric motor bearings is usually not compatible with the grease used in fan bearings. Never mix the two grease types! See Table 8 for compatible greases and Table 9 for maximum grease capacity.
Note: Lubricate the bearing according to the motor manufacturer’s recommendations and use the
manufacturer-recommended grease.
Fan bearings without lubrication lines are sealed bearings. Re-lubrication is not required.
Fan bearings equipped with lubrication lines should be lubricated with a lithium-based grease that conforms to NLGI No. 2 for consistency.
Table 8. Compatible Greases Table 9. Fan bearing maximum grease capacity
Type Shaft size (inches) Capacity (fluid ounce)
Texaco Multi Fak 2 1/2 - 3/4 1/7 Shell Alvania 2 7/8 - 1 3/16 3/8 Mobil 532 1 1/4 - 1 1/2 5/8 Chevron Dura-Lith 2 1 11/16 - 1 15/16 7/8 Exxon Beacon 2 - 2 7/16 1 1/4 Keystone 84H 2 1/2 - 2 15/16 2
Routine Maintenance
Refer to Table 10 for minimum torque of motor mounting an d bearings bolts.
Figure 78. Bearing set screw alignment
Bearing Set Screw Alignment
Align bearing set screws as illustrated in Figure 78.
Table 10 provides bearing set screw torque
measurements.
CAH-SVX01B-EN 89
Page 90
Routine Maintenance
Table 10. Minimum hex head bolt torque in lb.-ft. (Grade 5 bolts)
Size (inches) Thread Designati on Minimum Torque
1/4-20 UNC 6 1/4-28 UNF 7
65/16-18 UNC 14
5/16-24 UNF 16
3/8-16 UNC 24
3/8-24 UNF 28 7/16-14 UNC 42 7/16-20 UNF 45
1/2-13 UNC 69
1/2-20 UNF 83 9/16-12 UNC 99 9/16-18 UNF 118
5/8-11 UNC 150
5/8-18 UNF 176
3/4-10 UNC 254
3/4-16 UNF 301
7/8-9 UNC 358
7/8-14 UNF 422
Note: Soft metric conversions are not acceptable for screw and hex sizes.
Motor Bearing Lubrication
1-8 UNC 500
1-14 UNF 602
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedure to ensure the power cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Obtain an IOM from the motor manufacturer for the specific motor installed. The motor manufacturer’s recommendations take precedence for all matters related to the start-up and routine maintenance of the motor.
Motor grease fittings have been removed from factory-installed motors in compliance with UL regulations. Motor bearings require periodic maintenance throughout their life. Many different styles of motors come as standard selections, so please obtain the motor IOM and use the manufacturer -recommended grease.
Fan Moto r Inspection
Inspect fan motors periodically for excessive vibration or temperature.
Page 91
Coils
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Pr o per handling should include goggles or f ace shie ld, chemical r esistant glo ves , boots, apr on or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury.
All coils should be kept clean to maintain maximum performance.
Steam and Water Coils
To clean steam and water coils:
1. Disconnect all electrical power to the unit.
2. Wearing the appropriate per s onal protective equipment, use a soft brush to remove loose debris from both sides of the coil.
3. Install a bloc k-off to prevent spray from going thro ugh the coil and into a dry section of the unit and/or system ductwork.
4. Mix a high-quality coil cleaning detergent with water according to the manufacturer’s instructions.
Note: If the detergent is strongly alkaline after mixing (PH 8.5 or higher), it must contain an
5. Place the mixed solution in a garden pump-up sprayer or high-pressure sprayer. If a high pressure sprayer is to be used:
a. Maintain minimu m nozzle spray angle of 15 degrees. b. Spray perpendicular to the coil face. c. Keep the nozzle at least 6 inches from the coil. d. Do not exceed 600 psi.
6. Spray the leaving air side of the coil first, then the entering air side.
7. Thoroughly rinse both sides of the coil and the drain pan with cool, clean water.
8. Repeat steps 6 and 7 as necessary.
9. Straighten any coil fins that may have been damaged during the cleaning process.
10. Confirm the drain line is open following the cleaning process.
11. Allow the unit to dry thoroughly before putting it back into service.
12. Replace all panels and parts and restore electrical power to the unit.
13. Be careful any contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials.
Routine Maintenance
inhibitor. F ollow the cleaning solution manufacturer’ s instructions reg arding the use of the product.
CAH-SVX01B-EN 91
Page 92
Routine Maintenance
Cleanable Cooling Coils
Cleanable cooling coils have removable headers for cleaning:
1. Remove the headers.
2. Use a small nylon or fiber brush to clean the tubes.
3. Flush the tubes with water.
4. Install a new ru bber sealing gasket and be sure it seats properly when the header is replaced.
Note: Apply washers under the bolt heads. Bolts should be evenly tightened to 50 foot-pounds of
torque, beginning in the center and working toward the outside.
Refrigerant Coils
WARNING
Hazardous Pressures!
Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150°F to avoid excessive pressure in the coil. Failure to follow these safety precautions could result in coil bursting, which could result in death or serious injury.
To clean refrigerant coils:
1. Disconnect all electrical power to the unit.
2. Wearing the appropriate per s onal protective equipment, use a soft brush to remove loose debris from both sides of the coil.
3. Install a bloc k-off to prevent spray from going thro ugh the coil and into a dry section of the unit and/or system ductwork.
4. Mix a high-quality coil cleaning detergent with water according to the manufacturer’s instructions.
Note: If the detergent is strongly alkaline after mixing (PH 8.5 or higher), it must contain an
inhibitor. F ollow the cleaning solution manufacturer’ s instructions reg arding the use of the product.
5. Place the mixed solution in a garden pump-up sprayer or high-pressure sprayer. If a high pressure sprayer is to be used:
– Maintain minimum nozzle spray angle of 15 degrees. – Spray perpendicular to the coil face. – Keep the nozzle at least 6 inches from the coil. –Do not exceed 600 psi.
6. Spray the leaving air side of the coil first, then the entering air side.
7. Thoroughly rinse both sides of the coil and the drain pan with cool, clean water.
8. Repeat steps 6 and 7 as necessary.
9. Straighten any coil fins damaged during the cleaning process.
10. Confirm the drain line is open following the cleaning process.
11. Allow the unit to dry thoroughly before putting it back into service.
12. Replace all panels and parts and restore electrical power to the unit.
13. Be careful any contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution.
Page 93
Coil Winterization
NOTICE
Coil Freez e-up!
Properly drain and vent coils when not in use. Trane recommends glycol protection in all possible freezing applications. Use a glycol approved for use with commercial cooling and heating systems and copper tube coils. Failure to do so may result in equipment damage.
In general, most coil manufacturers recommend the same method to protect coils from subfreezing temperatures. Primarily , this consists of draining water from the coil before the heating season and thoroughly blowing the coil out with compressed air . T rane also recommends flush ing the coil with glycol if coils will be exposed to temperatures below 35 degrees. If coils are purchased from a manufacturer other than Trane, contact that coil manufacturer for recommendations specific to their product.
Install field-fitted drains and vents to permit winterization of coils not in use and to assist in evacuating air from the water system during startup. If draining is questionable because of dirt or scale deposits inside the coil, fill the coil with glycol before the heating season begins.
Note: On many units, there are multiple coils in the coil section. Be sure to winteriz e all coils in a
Chilled Water Coils
Routine Maintenance
given coil section.
Note: Use care in removing header plugs from coils. Over-tor qu in g may result in twisted tubes.
1. Remove the vent and drain plugs.
2. Blow the coil out as completely as possible with compressed air.
3. Fill and drain the coil several times with full strength glycol so that it mixe s thoroughly with the water retained in the coil.
4. Drain the coil out as completely as possible.
5. To ensure no water remains in the coil, do not replace the vent and drain plugs until the coils are put back into service.
Cleanable Coils
1. Remove all vent and drain plugs.
2. Allow the water to drain from the coil.
3. Remove the header covers.
4. If tubes are fouled, clean the tubes with a nylon or wire brush.
5. To ensure no water remains in the coil, do not replace the header covers until the coils are put back into service.
Note: When the coils are put back into service, use new gaskets. Trane recommends washers be
Moisture Purge Cycle
By it’s very nature, any HVAC unit with a cooling coil serves as a dehumidifier, reducing the surrounding air’ s ability to hold water vapor as its temperature falls. This normally doesn’t present a problem when the unit is running. However , when the fan s tops, water vapor condenses on the cold metal surfaces inside the air handler and remains there until the air warms sufficiently to re­evaporate it. This damp, dark environment—though temporary—can encourage the growth of mold, mildew, and other microbial contaminants.
used under the bolt heads and bolts be evenly tightened to 50 ft-lbs torque.
CAH-SVX01B-EN 93
Page 94
Routine Maintenance
Providing a moisture purge cycle 15 to 30 minutes after shutdown disperses the cold, humid air inside the air-handling system more evenly throughout the building. This four-step cycle:
Closes the outdoor air dampers.
Turns off the cooling coil.
Opens any variable-air-volume terminals connected to the air handler.
Operates the supply fan for 10to 15 minutes.
Air movement discourages water condensation and hastens re-evaporation of any condensate that does happen to form. This simple preventative measure effectively combats microbial growth and curbs moisture-related deterioration of air-handling components.
Internal Insulation
NOTICE
Microbial Growth!
Wet interior unit insulation can become an amplification site for micr obial gr o wth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth on the interior insulation, the insulation should be removed and replaced pr ior to operating the system.
The process of cooling and dehumidification p roduces condensate that must be continuously removed from the air-handling unit. The section of the unit from the entering air side of the cooling coil to the leaving edge of the drain pan is considered to be the “wet” section of the unit. Other potentially “wet” sections are immediately downstream of a humidifier and/or an outside air intake section.
Internal insulation in areas of the unit that are normally considered to be “dry” must also be periodically inspected to ensure the insulation is clean and dry. Wet insulation in an area that is normally considered to be “dry” can indicate an operational problem (refer to “Troubleshooting”
on page 98 for further information). The equipment should be inspected a minimum of every six
months or more frequently as operating experience dictates. Accumulated dirt and other organic matter exposed to water or extended periods of high relative
humidity (60 percent or higher) can support microbial growth, which must be removed to prevent the unit from becoming a contaminant source.
If evidence of contamination exists in either the wet or dry sections:
Determine and eliminate the cause.
Remove the contam in ation.
Sanitize the affected area.
See “Troubleshooting” on page 98 for assistance in identifying the cause.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Page 95
Routine Maintenance
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Pr o per handling should include goggles or f ace shie ld, chemical r esistant glo ves , boots, apr on or suit as required. For personal safety refer to the cleaning agent manufacturer’s Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to follow all safety instructions could result in death or serious injury.
Cleaning Non-Porous Insulating Surface
If microbial growth on a non-porous insulating surface (closed cell insulation or sheet metal surface) is observed:
1. Disconnect all electrical power to the unit.
2. Wearing the appropriate personal protective equipment, use a brush for sheet metal surfaces or a soft sponge on a foil face or closed cell foam surface to mechanical ly remove the microbi al growth.
Note: Be careful not to damage the non-porous surface of the insulation.
3. Install a bl ock-off to prevent spray from going into a dry section of the unit and/or system ductwork.
4. Thoroughly clean the contaminated area(s) with an EPA-approved sanitizer specifically designed for HVAC use.
5. Rinse the af fected surfaces thoroughly with fresh water and a fresh sponge to prevent potential corrosion of the drain pan and drain line
6. Repeat steps 4 and 5 as necessary.
7. Confirm the drain line is open following the cleaning process.
8. Allow the unit to dry thoroughly before putting it back into service.
9. Replace all pa nels and parts and restore electrical power to the unit.
10. Be careful any contaminated material does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution.
Cleaning Porous Insulating Surface
To clean a porous insulating surface (fiberglass insulation):
1. Disconnect all electrical power to the unit.
2. W earing the appropriate personal protective equipment, use a vacuum device with a HEP A filter (99.97 percent efficient at 0.3micron particles) to remove the accum ul ate d dirt and organic matter.
Note: Be careful not to tear the insulation surface or edges.
3. Confirm the drain lin e is open foll owi ng the cleanin g process.
4. Allow the unit to dry thoroughly before putting it back into service.
5. Replace all pa nels and parts and restore electrical power to the unit.
6. Be careful any contaminated mater ia l does not contact other areas of the unit or building. Properly dispose of all contaminated materials and cleaning solution.
CAH-SVX01B-EN 95
Page 96
Routine Maintenance
Controls
On units that have been selected with the external communications port, both the operator display and Rover service tool can be connected without shutting off the unit through the external communications port. Remove the cover plate on the port and plug into the RJ-11 port for the operator display or the RS 485 port for the Rover service tool. This enables continuous operation of the Air Handling unit without d isruption to the operating co nditions of the unit. When servicing of the unit is complete, replace the cover plate on the external port to eliminate the air leakage path.
Multiple Fans
When controlled in a bank of fans, these fan units must be controlled using a common control signal, such as the duct static control signal, to modulate the fan speed.
Ultraviolet (UV) Light Maintenance
WARNING
Hazardous Voltage and Exposure to Ultraviolet Radiation!
If UV lights are present in this unit, it contains components that emit high-intensity ultraviolet (UV-C) radiation which can be harmful to unprotected eyes and skin. Disconnect all electrical power, including remot e disconn ects before servicing. Follow prop er loc kout/tagout procedures to ensure the equipment cannot be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
The intensity of the ultraviolet energy emitted from the ultraviolet bulbs is dependent on the cleanliness and age of the bulb. The surface of the bulb should be kept as clean as possible for optimum intensity. Depending on the filtration level of the HV AC system and the general hygiene of the building, periodic cleaning may be necessary. Before attempting any maintenance procedures, always follow all warnings and cautions as detailed in this maintenance section.
Cleaning the Bulbs
Note: If bulbs are found to be broken, see the proper warning and cautions below regarding
1. Disconnect all electrical power to the unit and the ultraviolet bulbs.
2. Wearing soft cloth gloves and safety glasses, use two hands and firmly grasp the bulb at each
3. R otate the bulb 90 degrees in either direction and move bulb aw ay from the fixture and out of
4. Wipe down eac h bulb with a clean clot h and alcohol. A void touching the bulb with bare hands
5. Carefully return the bulb to the fixture and rotate it 90 degrees in either direction until it is firmly
6. Close and latch all unit panels and reenergize power to the lights.
broken bulbs and hazardous vapors.
end.
unit.
as skin oils can accelerate future glass soiling and degrade the bulb performance.
secured.
Page 97
Replacing the Bulbs
WARNING
Hazardous Vapors!
If large numbers of UV bulbs are broken, an appropriate respirator should be considered to prevent inhalation of mercury vapors. Failure to use a respirator could result in death or serious injury.
CAUTION
Broken Glass!
Bulbs are fragile and can be easi ly br oken. Always use gloves and eye protection when handling these bulbs. Failur e t o handle bulb s prop er ly ma y r esult in mino r to moderat e injury. Refer to the MSDS sheet from the bulb manufacturer for additional safety information.
Ultraviolet bulbs should be replaced annually if operated continuously or af ter 9,000 hours of use if operated intermittently. Replacement bulbs must be the specific size and wattage as originally supplied from the factory.
Note: Although the lights may continue to generate a characteristi c blue glow beyond 9,000
1. Disconnect power to the HVAC unit and the ultraviolet bulbs. SEE WARNING ABOVE.
2. Wearing soft cloth gloves and safety glasses, use two hands and firmly grasp the bulb at each
3. R otate the bulb 90 degrees in either direction and move bulb aw ay from the fixture and out of
4. Carefully install a new replacement bulb in the fixture and rotate it 90 degrees in either direction
5. If broken bulbs are found or if you are required to dispose of used bulbs, the proper warning
6. Always use cloth gloves and suitable eye protection when cleaning or replacing these bul bs.
Routine Maintenance
operating hours, the ultraviolet radiation emitted by the bulbs degrades over time and will no longer provide the intended benefit.
end.
unit.
until it is firmly secured.
and cautions must be followed.
Bulbs may break if dropped or handled improperly.
Disposal of Bulbs
UV bulbs, like fluorescent bulbs, contain mercury, which is a regulated hazardous waste. The disposal requirements for hazardous wastes are determined by local, state and federal guidelines. Check all regulations before disposing of bulbs to ensure you have met all requirements.
Refer to the MSDS sheet from the bulb manufacturer for additional disposal, handling and safety information.
After replacing bulbs, close and latch all unit panels and reenergize power to the lights.
CAH-SVX01B-EN 97
Page 98
Troubleshooting
This section is intended to be used as a diagnostic aid only. For detailed repair procedures, contact your local Trane service representative.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safe ty warnings provided throughout this manual concerning these procedures. When possible, disconnect all electric al power including remote disconnect and discharge all energy storing devices suc h as capacitors before servicing. Follow proper loc kout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury. including remote disconnects before servicing. Follow proper l ockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components perform these tasks. Failure to follow all of the recommended safety warn in gs provided, could result in death or serious injury.
Table 11. Air handler trou bleshooting recommendations
Symptom Probable Cause Recommended Action
Bearing is excessively hot
Motor fails to start
Motor stalls
Excessive vibration
Motor runs and then dies down
Motor does not come up to speed
Motor overheats
Excessive motor noise
Rapid motor bearing wear
Loose fan belt
First start after relubrication (Grease distribution) Allow machine to cool down and restart. Over-lubrication Clean surface of grease and purge. Over tensioned belts Adjust belt tension. No lubricant Apply lubricant. Check bearings for damage. Misaligned bearing Correct alignment. Check shaft level. Blown fuse or open circuit breaker Replace fuse or reset circuit breaker. Overload trip Check and reset overload. Improper wiring or connections Check wiring with diagram supplied on unit.
Improper current supply
Mechanical failure Open phase Check line for an open phase.
Overloaded motor Reduce load or replace with larger motor. Low line voltage Check across AC line. Correct voltage if possible.
Poor alignment
Shipping spacers not removed Over tensioned belts Adjust belt tension.
Misaligned drive Align drive. Partial loss of line voltage Starter shorts when motor warms up Replace starter.
Low voltage at motor terminals Check across AC line and correct voltage loss if possible. Line wiring to motor too small Replace with larger sized wiring. Overloaded motor Reduce load or replace with a larger motor. Motor fan is clogged with dirt preventing proper ventilation Remove fan cover, clean fan and replace cover. Motor mounting bolts loose Tighten motor mounting bolts. Rigid coupling connections Replace with flexible connections. Worn motor bearings Replace bearings and seals. Fan rubbing on fan cover Remove interference in motor fan housing. Excessive overhung load due to overtensioned drive Check belt tension and overhung load. Excessive overhung load due to a small diameter motor sheave Motor is poorly positioned Adjust belt tension. Worn or damaged belt Replace belt or belt set. Check sheave alignment. Worn sheaves Replace sheaves.
Compare actual supply power with motor nameplate recommendations. Contact power company for adjustments. Check that motor and drive rotate freely. Check bearing lubricant.
Align bearing set screws (see “Bearing Set Screw Alignment”
on page 89). Loosen and retighten bearing set screws.
Remove shipping spacers and/or bo lts (see “Fans” section o n
page 48).
Check for loose connections. Determine adequacy of main power supply.
Replace sheave with larger one.
Page 99
Table 11. Air handler trou bleshooting recommendations
Symptom Probable Cause Recommended Action
Short belt life
Bearing noise
Low water coil capacity
Low refrigerant coil capacity
Low steam coil capacity
Drain pan is overflowing
Standing water in drain pan
Wet interior insulation
Excess dirt in unit Microbial growth
(mold) inside air handler
Worn sheaves Replace sheaves. Misaligned belt Realign drive with MVP sheave set at mean pitch diameter. Grease or oil on belts Check for leaky bearings. Clean belts and sheaves. Belt slipping Improper belt tension. Adjust tension. Belts rubbing Remove obstruction or realign drive for clearance.
Poor alignment Failed bearing Replace bearing.
Inadequate lubrication Replace bearing. Incorrect airflow Check fan operating condition.
Incorrect water flow
Incorrect water temperature
Coil is piped incorrectly Dirty fin surface Clean the fin surface (see “Coils” section on page 91).
Incorrect glycol mixture Verify glycol mixture and adjust if necessary. Incorrect airflow Check fan operating condition.
Expansion valve is not operating properly or is sized incorrectly
Incorrect refrigerant charge Verify refrigerant charge and adjust if necessary. Condensing unit failure Verify condensing unit operation.
Coil is piped incorrectly Clogged refrigerant line filter Change filter core.
Failure of suction/liquid line components Verify component operation Dirty fin surface
Fin frosting
Incorrect airflow Check fan operating condition. Coil is piped incorrectly Incorrect steam pressure Verify steam pressure and adjust if necessary. Excessive steam superheat Failure of steam line/condensate return components Verify component operation
Boiler failure Verify boiler operation Dirty fin surface Clean the fin surface (see “Coils” section on page 91). Plugged Drain Line Clean drain line Unit not level Level unit Improper trap design Design trap per unit installation instructions Improper trap design Design trap per unit installation instructions Unit not level Level unit Plugged drain line Clean drain line Coil face velocity too high Reduce fan speed Improper trap design Design trap per unit installation instructions Drain pan leaks/overflows Repair leaks Condensation on surfaces Insulate surfaces Missing filters Replace filters Filter bypass Reduce filter bypass by ensuring all blockoffs are in place. Standing water in drain pan See “Standing water in drain pan” above
Moisture problems See “Wet interior insulation” above
Loosen bearing set screws and realign (see “Bearing Set
Screw Alignment” on page 89)
Inspect the water pumps an d valves for proper op eration and check the lines for obstructions. Adjust the chiller or boiler to provide the proper water temperature. Verify coil piping (see “Coil Piping and Connections” section
on page 53).
Check sensing bulb temperature. Verify valve operation. Verify proper valve size.
Verify coil piping (see “Coil Piping and Connections” section
on page 53).
Clean the fin surface (see “Coils” section on page 91). Do not use steam to clean refrigerant coils. Verify defrost cycle operation. Verify Frostat operation. Verify refrigerant charge.
Verify coil piping (see “Coil Piping and Connections” section
on page 53).
Check steam superheat. Steam superheat should not exceed 50ºF.
Troubleshooting
CAH-SVX01B-EN 99
Page 100
www.trane.com
For more information, contact your local Trane office or e-mail us at comfort@trane.com
Literature Order Number CAH-SVX01B-EN Date July 1, 2010 Supersedes CAH-SVX01A-EN (July 2005)
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this literature.
Loading...