Trane CSRA025FAF0, CSRA040FAF0, CSRA060FAF0 Installation And Maintenance Manual

Page 1
Installation Operation Maintenance
25, 40 and 60 Ton Air-Cooled Cold Generators®
Models:
CSRA025FAF0, CSRA040FAF0, and CSRA060FAF0
© 2002 American Standard Inc. All Rights Reserved
CSRA-SVX02A-EN
Page 2
Table of Contents
General Information
Earnings and Cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Literature Change History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Overview of Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Nameplate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Evaporator Barrel Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Compressor Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Input Devices & System Functions. . . . . . . . . . . . . . . . . . . . . . . 9
Unit Component “Layout” and “Ship with” Locations . . . . . . . . 15
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installation
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Unit Dimensions & Weight Information. . . . . . . . . . . . . . . . . . . 16
Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Leveling the Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Shipping Fasteners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
General Unit Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Chilled Water Piping Requirements . . . . . . . . . . . . . . . . . . . . . 23
Main Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . 24
Chilled Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Final Water Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . 26
Freeze Protection from Ambient Conditions. . . . . . . . . . . . . . . 26
Electrical Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Electrical Cable Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Cam-lok Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Pig-tail Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Flexible Hose Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Dixon Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Hard Pipe Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Field Installed Power Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Circuit Breaker External Handle . . . . . . . . . . . . . . . . . . . . . . . . 38
Main Unit Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Power Wire Sizing and Protection Device Equations . . . . . . . . 41
Field Installed Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Controls using 24 VAC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Controls using DC Analog Input/Outputs . . . . . . . . . . . . . . . . . 44
Controls using DC Communication Links . . . . . . . . . . . . . . . . . 45
Ice Building Control Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
System Pre-Start Procedures
Voltage Imbalance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Electrical Phasing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
2 CSRA-SVX02A-EN
Page 3
Table of Contents
System Start-Up
Chilled Water Circulating Pump . . . . . . . . . . . . . . . . . . . . . . . . 59
Verifying Proper Fan Rotation . . . . . . . . . . . . . . . . . . . . . . . . . 63
Compressor Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Proper Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Compressor Crankcase Heaters . . . . . . . . . . . . . . . . . . . . . . . 72
Low Ambient Damper Adjustment . . . . . . . . . . . . . . . . . . . . . . 72
Final System Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Service & Maintenance
Compressor Operational Sounds . . . . . . . . . . . . . . . . . . . . . . . 75
Scroll Compressor Replacement . . . . . . . . . . . . . . . . . . . . . . . 75
Fuse Replacement Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Monthly Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Annual Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Final Process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
CSRA-SVX02A-EN 3
Page 4
General
NOTICE:
Information
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
-
WARNING
if not avoided, could result in death or serious injury.
CAUTION
not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
Indicates a potentially hazardous situation which,
-
Indicates a potentially hazardous situation which, if
CAUTION
property-damage-only accidents.
Indicates a situation that may result in equipment or
Literature History
CSRA-SVX02A-EN (May 2002)
Original issue of manual. Describes the Installation, Operation and Mainte­nance procedures for the unit.
Reference: CGAF-IOM-2 (Non-rental CGAF Chiller)
Overview of Manual
Note: One copy of this document ships inside the control panel of each unit
and is customer property. It must be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
4 CSRA-SVX02A-EN
Page 5
General Information
Important Note: Environmental scientists have found evidence that
refrigerant emissions contribute to depletion of ozone in the upper atmosphere and can increase global warming. Trane encourages every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC and HFC refrigerant to the atmosphere that can result from installation, operation, routine maintenance, or major service on this equipment. Only technicians with EPA certification should be allowed to handle CFC, HCFC or HFC refrigerants. Compliance or certification to other local or state codes may also be required when handling refrigerants. Always act in a responsible manner to conserve refrigerants.
Model Number Description
All Trane products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided in Figure 1a. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number, serial number, and DL number (if applicable) stamped on the unit nameplate.
Unit Nameplate
The ChillerSource unit nameplate is located on the panel adjacent to hinged chiller control panel door. It includes the model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent data. A Mylar and small metal chiller nameplate with the Model Number, Serial Number, and Unit Weight is located on the outside upper right corner of the control panel door. An additional nameplate is located on the inside of the control panel door. See Figure 1b.
When ordering replacement parts or requesting service, be sure to refer to the specific model number, serial number, and DL number (if applicable) stamped on the unit nameplate.
Evaporator Barrel Nameplate
The nameplate is located on the top of the evaporator barrel near the supply­end tube sheet. The word “Nameplate” is stenciled on the insulation. To view the nameplate, remove the tape over the area and spread the insulation. Re­tape the insulation after viewing.
Compressor Nameplate
The nameplate for the “Scroll” compressors are located on the compressor lower housing.
CSRA-SVX02A-EN 5
Page 6
General Information
Figure 1a — Model Number Description
6 CSRA-SVX02A-EN
Page 7
General Information
Figure 1b — Unit Nameplate
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation.
Each unit is equipped with manifolded scroll compressors. Each manifolded set of compressors is piped in parallel and utilizes a passive oil management system to maintain proper compressor oil level.
The condenser coils are aluminum fin, mechanically bonded to copper tubing. Copper-fin coils are optional. Louvered condenser grilles for coil protection are standard.
Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.
For “Ship with” items, refer to the Unit Component “Layout” and “Ship with” Locations illustration.
Low ambient dampers are provided for low ambient operation.
CSRA-SVX02A-EN 7
Page 8
General Information
The shell-and-tube type evaporator used in each air-cooled Cold Generator is manufactured in accordance with ASME standards. Each evaporator is fully insulated and equipped with a drain connection. The chilled solution temperature sensors are located on the solution outlet and the return solution end of the evaporator.
A liquid line solenoid valve, filter drier, sight glass, thermostatic expansion valve, and service valves (liquid and discharge) are provided on each circuit.
Standard controls for these units is a microelectronics control system that consists of a network of modules referred to as Unit Control Modules (UCM). The acronym UCM is used extensively throughout this document when referring to the control system network.
These modules through Proportional/Integral control algorithms perform specific unit functions that governs unit operation in response to chilled water temperature leaving the evaporator. The stages of capacity control for these units is achieved by starting and stopping the compressors.
They are mounted in the control panel and are factory wired to their respective internal components. They receive and interpret information from other unit modules, sensors, remote panels, and customer binary contacts to satisfy the applicable request for cooling. Refer to the following discussion for an explanation of each module function.
Human Interface Module (HI - Standard)
The Human Interface module enables the operator to adjust the operating parameters for the unit using it's 16 key keypad. The 2 line, 40 character LCD screen provides status information for the various unit functions as well as menus for the operator to set or modify the operating parameters.
Cold Generator Module (CGM - Standard)
The Cold Generator Module (CGM) responds to cooling requests by energizing the proper unit components based on information received from other unit modules, sensors, remote panels, and customer supplied binary inputs. It initiates unit operation based on that information.
Compressor Module (SCM & MCM - Size Specific)
The Compressor module, (Single Circuit & Multiple Circuit), upon receiving a request for mechanical cooling, energizes the appropriate compressors and condenser fans. It monitors the compressor operation through feedback information it receives from various protection devices.
Trane Communications Interface Module (TCI) (Used with Trane ICS™ Systems)
The Trane Communication Interface module allows external setpoints for most of the unit functions to be communicated to the unit's UCM network via a Trane ICS™ system or a Tracer Summit™ system. DIP Switch settings on the TCI module for these applications should be; Switches 1, 2, and 3 are “Off”.
8 CSRA-SVX02A-EN
Page 9
General Information
Generic Building Automation System Module (GBAS) (Used with Non-Trane Building Control System)
The Generic Building Automation System (GBAS) module allows a non­Trane building control system to communicate with the unit and accepts external setpoints in form of analog inputs 0 - 5 DCV and a binary Input for demand limit. Five (5) binary outputs are available on 0 - 5 DCV modules. Refer to the “Field Installed Control Wiring” section for the control wiring to the GBAS module and the various desired setpoints with the corresponding DC voltage inputs.
Current Sensing Module (CSM)
Current transformers located around two (2) of the main power leads for each compressor monitors the running current during compressor operation. The information is sent to the CGM and can be accessed through the “Compressor Status” submenu displayed at the Human Interface Module.
Input Devices & System Functions
The descriptions of the following basic Input Devices used within the UCM network are to acquaint the operator with their function as they interface with the various modules. Refer to the unit's electrical schematic for the specific module connections.
Lead/Lag (Standard)
When Lead-Lag is enabled, for each capacity add request, the CGM will begin sequencing the compressors “On” that have:
A. the least number of starts; or,
B. the least run time (if number of starts are equal)
At each capacity subtract request, the CGM will begin sequencing the compressors “Off” that have:
A. the most run time; or,
B. the least number of starts (if more than one compressor has the same run
time)
If a compressor is locked out for any reason when a capacity add request occurs, the next available compressor which meets the specified criteria will be started.
If a compressor can not be turned “Off” due to the minimum “On Time”, the next compressor which meets the specified criteria will be turned “Off”.
On dual circuit units, as the first two capacity add requests are initiated, one compressor on each circuit will start before any additional compressors on any circuit is started. When staging down from three compressor stages to two compressor stages, the CGM will turn the compressors “Off” on the circuit that has the most compressors operating.
CSRA-SVX02A-EN 9
Page 10
General Information
With Lead/Lag enabled, HGBP operation (if applicable) will be bypassed and the system will go directly into pump down when the last subtract command is initiated.
When the UCM is powered up (after a power loss), or any time the compressor's start time and run time are equal, the lead compressor for single circuit units (20 through 30 Tons), will be the first “On” and the lag compressor will be the first “Off”. For dual circuit units (40 through 60 Tons), the “On” sequence will be A-C-B-D and the “Off” sequence will be D-B-C-A.
Loss of Flow (Refrigerant) Control
Is accomplished using a binary input device (LPC) located on the suction lines near the scroll compressors.
The LP cutouts are designed to open if the suction pressure approaches 7 ± 4 psig. If the LP cutout opens after a compressor has started, all compressors operating on that circuit will be turned off immediately and will remain off for a minimum of three minutes.
The LPC contacts are designed to close when the suction pressure exceeds 22 ± 4 psig. If the LP control is open when a compressor is requested to start, none of the compressors on that circuit will be allowed to operate. They are locked out and a manual reset diagnostic is initiated.
If the LP cutout trips four consecutive times during the first three minutes of operation, the compressors on that circuit will be locked out and a manual reset diagnostic is initiated.
Saturated Condenser Temperature Sensors (Standard)
Are analog input devices mounted inside a temperature well located on a condenser tube bend. They monitor the saturated refrigerant temperature inside the condenser coil and are connected to the compressor module (SCM/MCM). As the saturated refrigerant temperature varies due to operating conditions, the condenser fans are cycled “On” or “Off” as required to maintain acceptable operating pressures.
Head Pressure Control (Standard)
Is accomplished using two saturated refrigerant temperature sensors. During a request for compressor operation, when the condensing temperature rises above the “lower limit” of the controlband, the Compressor Module (SCM/MCM) begins sequencing condenser fans “On”. If the operating fans can not bring the condensing temperature to within the controlband, more fans are turned “On”. As the saturated condensing temperature approaches the lower limit of the controlband, fans are sequenced “Off”. The minimum “On/Off” time for condenser fan staging is
5.2 seconds. If the system is operating at a given fan stage below 100% for 30 minutes and the saturated condensing temperature is above the “efficiency check point” setting, a fan stage will be added. If the saturated condensing temperature falls below the “efficiency check point” setting, the fan control will remain at the present operating stage. If a fan stage cycles
10 CSRA-SVX02A-EN
Page 11
General Information
four times within a 10 minute period, the control switches from controlling to the “lower limit” to a temperature equal to the “lower limit” minus the “temporary low limit suppression” setting. It will utilize this new “low limit” temperature for one hour to reduce condenser fan short cycling.
High Pressure Controls (Standard)
High Pressure controls are located on the discharge lines near the scroll compressors. They are designed to open when the discharge pressure approaches 405 ± 7 psig. The controls reset automatically when the discharge pressure decreases to approximately 300 ± 20 psig. However, the compressors on that circuit are locked out and a manual reset diagnostic is initiated.
Low Ambient Control
The low ambient modulating output on the compressor module is functional on all units with or without the low ambient option.
When the compressor module has staged up to it's highest stage (stage 2 or 3 depending on unit size), the modulating output will be at 100% (10 VDC). When the control is at stage 1, the output (0 to 10 VDC) will modulate based on the saturated condensing temperature.
When the low ambient damper option is installed, the dampers will modulate according to the output to control the saturated condensing temperature to within the programmable “condensing temperature low ambient control point”.
Status/Alarm Output (Standard)
Is an internal function within the CGM control module that provides;
A. diagnostic signals to the Human Interface Alarm LED.
B. control of the binary Alarm output. C. control of the binary outputs on the GBAS module to inform the customer
of the operational status and/or diagnostic conditions.
Compressor Circuit Breakers (Standard)
The Scroll Compressors are protected by circuit breakers which interrupt the power supply to the compressors if the current exceeds the breakers “must trip” value and opens a set of auxiliary contacts in the control circuit.
When the Compressor Module (SCM or MCM) detects the open auxiliary compressor contacts, it turns any operating compressor(s) on that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic.
CSRA-SVX02A-EN 11
Page 12
General Information
Compressor Motor Winding Thermostats (Standard)
A thermostat is embedded in the motor windings of each Scroll compressor. Each thermostat is designed to open if the motor windings exceeds approximately 221°F. The thermostat will reset automatically when the winding temperature decreases to approximately 181°F. Rapid cycling, loss of charge, abnormally high suction temperatures, or the compressor running backwards could cause the thermostat to open. During a request for compressor operation, if the Compressor Module detects a problem outside of it's normal parameters, it turns any operating compressor(s) on that circuit “Off”, locks out all compressor operation for that circuit, and initiates a manual reset diagnostic.
Low Ambient Compressor Lockout (Standard)
When low ambient compressor lockout is enabled, the compressors are not allowed to operate if the temperature of the outside air falls below the lockout setpoint. Compressor operation is enabled when the temperature rises 5°F above the lockout setpoint. The setpoints and enable/disable option is programmable at the Human Interface inside the unit control panel. The default setting is 30°F.
Note: The unit is wired so the CGM monitors incoming power for proper phase sequencing. Observe proper polarity of internal wiring during service procedures.
Short Cycle Protection (Standard)
If compressor operation is interrupted by a loss of power or by a manual reset diagnostic, a minimum of one minute must elapse before the affected compressor(s) will be allowed to restart for “Process” applications. A minimum of three minutes must elapse before the affected compressor(s) will be allowed to restart for “Comfort Cooling” applications.
Hot Start (Load Limit) Control (Standard)
Each time the system is started and the control of the CGM transitions from “Loop Stabilization” to either “Process” or “Comfort Cooling”, if the Leaving Solution Temperature (LST) is higher than the programmable Hot Start Load Limit Setpoint (HSLLS), the lag compressor on each circuit will be prevented from operating until the leaving solution temperature is lowered by 5°F below the HSLLS.
If the Hot Start Limit time interval elapses before the LST is 5°F below the HSLLS, the control will transition immediately into the Hot Operation mode.
Hot Operation mode is programmable to:
1. Do not limit capacity, initiate an informational diagnostic until the LST falls 5°F below the HSLLS.
2. Limit the capacity to 50 percent (one compressor per circuit), initiate an auto reset diagnostic until the LST falls 5°F below the HSLLS.
12 CSRA-SVX02A-EN
Page 13
General Information
3. Turn “Off” and lockout all of the compressors and initiate a manual reset diagnostic.
Loss-of-Flow (Solution) Protection (Standard)
The factory installed solution flow switch is wired to the CGM. If it opens for more than 6 continuous seconds when the pump is requested to be “On”, an auto reset diagnostic will be initiated. If no compressors are operating, they will be inhibited from starting. Any time the compressors are operating, they will be turned “Off”. Once flow has been reestablished, full unit operation will be allowed.
In addition, a low pressure cutout and the entering (EST) and leaving solution temperature (LST) sensors provide loss of flow protection for the unit.
When there is a cooling demand, the CGM compares the EST to the LST. If the EST is 2°F or more below the LST, the chiller is stopped and a manually reset diagnostic is initiated. This input has priority over all other commands received by the CGM.
Low Ambient Start (Standard)
Is accomplished by utilizing an additional low pressure cutout (LPC) that is ignored at start-up for varying periods of time, depending on the prevailing ambient temperature. The relationship between this variable time period and the ambient temperature is linear from a maximum of 5 minutes at 0°F to a minimum of 30 seconds at 65°F. The bypass time is initiated each time a compressor is started on a refrigerant circuit when no other compressor on that circuit is operating. No additional compressors will be allowed to operate within that circuit until the bypass time has expired.
Chiller Solution Pump Output Relay (Standard)
A Solution Pump binary output (Form C) relay is located on the CGM which may be used to control the chiller solution pump.
If the Chiller Solution Pump Mode, at the Human Interface Module, is set to “On”, the Solution Pump will run continuously.
If the Chiller Solution Pump Mode, at the Human Interface Module, is set to Auto, the Solution Pump will be turned “Off”:
1. when the unit is stopped (Unit Stop or External Auto/Stop)
2. during the unit's Power On Delay Time
3. when the primary control states are:
Ice Rebuild Delay Ice Building Complete
A Solution Pump “Off Delay” Time may be programmed to allow the Solution Pump to remain “On” after a shut down request has been received. The delay is adjustable between 0.5 minutes and 10 minutes after an “Off” state is initiated. The Solution Pump will always run for this delay time when
CSRA-SVX02A-EN 13
Page 14
General Information
turning off except during an Emergency Stop condition. If an Emergency Stop is initiated, the Solution Pump is immediately turned “Off” (relay de­energized).
Low Ambient Pump Control (Standard)
A Low Ambient Pump “On” Control function (LAPC) allows the pump to run continuously if the outside ambient temperature falls below a programmable Low Ambient Pump “On” Temperature (LAPT) Setpoint or if an outside ambient temperature input failure occurs. An Auto Reset Diagnostic will be issued and remain as long as the condition exists.
This function will be disabled when an Emergency Stop request is initiated.
During service test operation, if a low ambient condition exists when the operator attempts to turn the pump “Off”, a message will be displayed on the Human Interface Module advising that the pump cannot be turned off due to the low ambient condition.
Emergency Stop (Optional)
Is accomplished when a customer provided, field installed binary input device is connected to the CGM. The unit will immediately shut down when the contacts are opened. Emergency Stop is a top priority command that will override all other commands received by the UCM. A manual reset diagnostic will occur and an indication showing that the unit is shut down due to Emergency Stop will be displayed at the Human Interface Module.
External Auto/Stop (Optional)
The unit can be Stopped and Started by a remote customer provided field installed binary input device (such as a time clock) connected to the CGM. When the input is opened (Stop), the unit will stage the compressors and the solution pump “Off” in a normal manner and display “Off due to external stop” at the unit Human Interface. When the input is closed (Start), the unit will start and run normally.
The External Auto/Stop input operates in the same manner as the STOP/ AUTO keys on the unit mounted Human Interface or the Remote Human Interface (RHI). However, the Stop key at the unit mounted Human Interface has priority over both the remote External Auto/Stop and the Remote Human Interface Auto/Stop.
Note: If the STOP key is pressed at the unit mounted Human Interface, no remote AUTO (Start) key will start the unit until the AUTO key is pressed at the unit mounted Human Interface.
A start (AUTO) command is allowed only if no overriding diagnostics or higher priority function is present.
14 CSRA-SVX02A-EN
Page 15
Control Panel
Condenser Fans
Typical Lifting Holes (4)
Pump Circuit Breaker/Control Panel Enclosure
Tow Bar
General Information
Figure 2 — Unit Component “Layout” and “Ship with” Locations (60 Ton Unit Illustrated)
Forklift Tube Slots
Water Inlet
Unit Inspection
As soon as the unit arrives at the job site
[ ] Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
[ ] Verify that the power supply complies with the unit nameplate specifications.
[ ] Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
[ ] Check for material shortages. Refer to Figure 2, “Component Layout and Ship with Location”.
If the job site inspection of the unit reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the “bill of lading” before signing.
[ ] Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
Water Outlet
CSRA-SVX02A-EN 15
Page 16
Installation
WARNING
No Step Surface!
Do not w alk on the sheet metal drain pan. W alking on the drain pan could cause the supporting metal to collapse. Failure of the drain pan could result in death or serious injury.
Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating.
[ ] If concealed damage is discovered, notify the carrier's terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
[ ] Notify the appropriate Trane office before installing or repairing a damaged unit.
Unit Clearances
Figure 3 illustrates the minimum operating and service clearances for either a single, multiple, or pit application. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Providing less than the recommended clearances may result in condenser coil starvation or recirculation of hot condenser air.
Locate the unit as close to the applicable system support equipment as possible to minimize refrigerant piping lengths.
Unit Dimensions & Weight Information
• Overall unit dimensional data for each unit is illustrated in Figure 4.
• A Center-of-Gravity illustration and the dimensional data is shown in Figure 5.
• Table 1 lists the typical unit operating and point loading weights.
Foundation
If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at each support location or a slab foundation for support. Refer to Table 1 for the unit operating and point loading weights when constructing the footing foundation.
For rooftop applications, ensure the roof is strong enough to support the unit. Refer to Table 1 for the unit operating weights.
16 CSRA-SVX02A-EN
Page 17
Installation
Anchor the unit to the roof with hold-down bolts or isolators. Follow the instructions under “Unit Isolation” for proper isolator placement and installation.
Check with a roofing contractor for proper waterproofing procedures.
Figure 3 — Typical Installation Clearances for Single, Multiple or Pit Applications
CSRA-SVX02A-EN 17
Page 18
Installation
Figure 4a — C25 Ton Unit Dimensional Data & Recommended Clearances
18 CSRA-SVX02A-EN
Page 19
Installation
Figure 4b — C40 Ton Unit Dimensional Data & Recommended Clearances
CSRA-SVX02A-EN 19
Page 20
Installation
Figure 4c — C60 Ton Unit Dimensional Data & Recommended Clearances
20 CSRA-SVX02A-EN
Page 21
Installation
Table 1 — Typical Unit Weights and Point Loading Data
Unit Weights Model No. Tons Shipping Operational Dimensioned from Pump End
Weight (lbs) Weight (lbs) X CSRA010FAF0 10 3800 3820 57 CSRA015FAF0 15 4030 4050 74 CSRA025FAF0 25 6050 6150 83.0 CSRA040FAF0 40 8250 8370 79.0 CSRA060FAF0 60 9300 9615 96.0
Notes:
1. Mounting locations correlate with those shown in point loading illustration.
2. Operating weight includes refrigerant, oil, and water.
3. Shipping weight includes refrigerant and oil charges.
Figure 5 — Rigging and Center-of-Gravity Data
CSRA-SVX02A-EN 21
Page 22
Installation
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each of the cables (chains or slings) used to lift the unit must be capable of supporting the entire w eight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements may cause equipment or property-only damage. Failure to properly lift unit may result in death or serious injury. See details below.
Rigging
A Rigging illustration and Center-of-Gravity dimensional data table is shown in Figure 5 and Table 1. Refer to the typical unit operating weights table before proceeding.
1. Rig the condensing unit as shown in Figure 5. Attach adequate strength lifting slings to all four lifting brackets on the lifting frame. Do not use cables, chains, or slings except as shown.
2. Install spreader bars, as shown in Figure 5, to protect the unit and to facil­itate a uniform lift. The minimum distance between the lifting hook and the top of the unit should be 7 feet.
3. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging adjustments.
4. Lift the unit and position it into place.
Leveling the Unit
Use the unit base rail as a reference. Level the unit to within 1/4 inch over its entire length. Use shims when required.
Shipping Fasteners
Compressor Shipping Hardware
Figure 6 illustrates the location of each tie down bolt and rubber isolator bolt for the compressor assembly in each circuit. Refer to the illustration and the following discussion to locate and remove the fasteners.
Two Manifolded Compressors
Each manifolded compressor assembly is rigidly bolted to a mounting rail assembly. The rail assembly sets on four (4) rubber isolators. The assembly is held in place by two shipping braces that secure each compressor assembly rail to the unit's base rail. To remove the shipping hardware, follow the procedures below:
1. Remove the four anchor bolts (2 front and 2 rear), used to secure the shipping brace to the unit's base rail.
2. Remove the three self-tapping screws that secure each shipping brace to the compressor mounting rails.
3. Remove and discard the two 30-1/2” long shipping braces for each assembly.
4. Do not remove the shipping plate located on top of the compressors.
22 CSRA-SVX02A-EN
Page 23
Installation
5. Ensure that the compressor rail assembly is free to move on the rubber isolators.
Figure 6 — Removing C25 through C60 Scroll Compressor Shipping Hardware Installation
General Unit Requirements
The checklist listed below is a summary of the steps required to successfully install a commercial air cooled unit. This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instruction called out in the applicable sections of this manual.
[ ] Verify that the power supply complies with the unit nameplate specifications.
[ ] Check the unit for shipping damage and material shortage; file a freight claim and notify Trane office.
[ ] Verify that the installation location of the unit will provide the required clearance for proper operation.
Chilled Water Piping Requirements
[ ] Flushing the chilled solution piping system, if applicable.
CAUTION Evaporator Damage!
If using an acidic, commercial flushing solution, flush all chilled solution piping before making the final connection to the EVP chiller barrel. Failure to do so may result in evaporator damage.
[ ] Install heat tape and insulation, if necessary, to protect any exposed solution piping from external freezing conditions.
CSRA-SVX02A-EN 23
Page 24
Installation
Main Electrical Power Requirements
[ ] Verify the power supply meets the required power requirements of the system.
[ ] Install power wiring in accordance with all applicable codes.
[ ] Install and connect properly sized power supply wiring, with over current protection, to the main circuit breaker (ICB1).
[ ] Install and connect properly sized power supply wiring, with over current protection, to the proper termination point in the air handling unit (If applicable).
[ ] Install and connect properly sized power supply wiring, with over current protection, to the proper termination point for the chilled solution pump (when choosing not to use pump supplied with chiller).
[ ] Install proper grounding wires to an earth ground.
Chilled Water Piping
Evaporator water inlet and outlet types, sizes and locations are shown in Figure 4. Refer to the operating GPM parameters listed in Table 8a-c when determining flow and piping requirements.
Air Vents
A vent port is located on top of the chiller near the return end. Additional vents must be installed at high points in the piping system to facilitate air purging during the filling process.
Water Pressure Gauges
A water pressure gauge is installed near the inlet side of the chiller barrel with appropriate piping to measure the entering and leaving solution pressure.
CAUTION Evaporator Damage!
Do not exceed 150 psig evaporator pressure. Failure to do so may cause evaporator damage.
24 CSRA-SVX02A-EN
Page 25
Installation
Water Shutoff Valves
Shutoff valves are provided in the “Supply” and “Return” pipe near the chiller so the gauge(s), thermostats, sensors, strainer, etc., can be isolated during service.
Pipe Unions and Connectors
Pipe unions and Victaulic connectors are used to simplify disassembly for system service.
Thermometers
Temperature gauges are used in the lines to monitor the evaporator entering and leaving water temperatures.
Balancing Valves
A balancing cock (valve) is installed in the leaving water line. It will be used to establish a balanced flow.
Note: Both the entering and leaving water lines have shutoff valves installed to isolate the evaporator for service.
Strainer
A pipe strainer is installed in the water return line (inlet piping to chiller) to protect the components from entrapped debris.
Chiller Drain
The chiller drain is piped to the outside of the chiller casing with a ball shutoff valve to facilitate evaporator draining during service or shutdown procedures.
Chiller Flow Switch
A flow switch, illustrated in Figure 7, is installed to prevent or stop the compressor operation if the water flow drops off drastically. Refer to unit schematics for the flow switch electrical interlock connections.
Figure 7 — Optional Flow Switch Illustration
CSRA-SVX02A-EN 25
Page 26
Installation
Final Water Piping Connections
1. All water piping to the system should be flushed thoroughly before mak­ing the final connections.
CAUTION Pump Damage!
If using an acidic commercial flushing solution, construct a temporary bypass around the pump and unit. Failure to do so may lead to equipment damage.
2. Connect the water pipe to the EVP chiller.
3. Ensure the drain shutoff valve is closed.
4. While filling the chiller system with solution, vent the air from the system at the highest points.
CAUTION Proper Water Treatment!
The use of untreated or improperly treated w ater in an Air-Cooled Cold Generator may result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified w ater treatment specialist be engaged to determine w hat w ater treatment, if any, is required. Trane assumes no responsibility for equipment failures w hich result from untreated or improperly treated w ater, or saline or brackish w ater.
Evaporator Water Piping
The unit's water connection sizes and locations are shown in Figure 4.
CAUTION Component Damage!
Evaporator pressure should not exceed 1 50 psig (i.e., maximum working pressure). Failure to do so may lead to equipment damage.
CAUTION Pump Damage!
Do not reverse system w ater piping connections to the unit or pump. Failure to follow these instructions may result in pump or unit damage.
Water entering the evaporator is pre-piped to the discharge of the pump. If the pump is not required, open bypass valve and close inlet and discharge valves on pump. “Water Inlet” to the evaporator must enter on inlet connection to pump. Leaving water must exit the evaporator through the designated “Water Outlet” connection.
26 CSRA-SVX02A-EN
Page 27
Installation
Flexible Hose and Hard Pipe Installation
General
Use the procedure described below to ensure the proper installation of flexible hose provided as part of a ChillerSource rental. It is critical that this procedure is followed to minimize premature or catastrophic failure of this hose.
CAUTION Hose Damage!
Hose must never be pressurized over 1 5 0 psi. If higher pressures are required, “hard” suction pipe must be utilized. Failure to do so may lead to hose damage.
CAUTION Hose Damage!
Hose must alw ays be used in pressurized application. If a negative pressure application is required, “hard” suction pipe must be utilized. Failure to do so may lead to hose collapse and total system failure.
Flexible Hose Guidelines
WARNING
Hose Failure
Failure to comply w ith installation instructions that follow may result in death or serious injury or equipment damage.
• Do not support the hose ONLY by its couplings; support over half of the hose's length by ground or other supporting surface otherwise coupling clamps may fail.
• Do not run hose vertically more than 7 feet otherwise coupling clamps may fail.
• Do not cut hose to “custom” fit pieces-this will affect the integrity of the hose.
• Bleed all air from the system prior to pressurizing hose to avoid cou­plings separating from the hose.
• Install elbows for a smooth hose transition on all vertical hose installa­tions, see Figure 10 (Correct Vertical Hose Installation)
• Never pressurize hose above 150 psi.
CSRA-SVX02A-EN 27
Page 28
Installation
Dixon Coupling
• The Dixon coupling (See Figure 7), bolts are to be torqued prior to charging the hose with water to 40 ft-lbs. DO NOT EXCEED 40 ft-lbs. (The torque must be applied evenly between the bolts to ensure a consistent gap on each side of the coupling. Some pinching of the excess hose in the gap area is considered normal and will not create a leak or premature failure.)
• Continually monitor and retighten, if necessary, on monthly inspec­tion intervals.
Figure 7 — Dixon Coupling
The following figures illustrate the correct and incorrect methods for installing hose in a horizontal hookup application.
Figure 8 — Correct Horizontal Hose Installation
Correct horizontal hose installation shows a correct hose installation. In this configuration either a 45° or 90° elbow can be installed. This elbow prevents stretching and crimping of the hose at the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle to minimize the crimping of the hose at the ground or supporting surfaces.
28 CSRA-SVX02A-EN
Page 29
Installation
Figure 9 — (Incorrect Horizontal Hose Installation)
Incorrect horizontal hose installation shows an incorrect hose installation. Elbows are not installed. This causes the top of the hose to be in tension, which stretches the hose out of the coupling; and the bottom of the hose to be in compression, which causes it to crimp. It also causes the hose to crimp at the ground.
The following figures illustrate the correct and incorrect methods for installing hose in a vertical hookup application.
Figure 10— Correct Vertical Hose Installation
Correct vertical hose installation shows a correct vertical hose installation. In this configuration, the hose is installed with an elevation less than 7 feet off the ground. A 45° elbow is installed to reduce the stress in the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle to minimize the crimping of the hose at the ground or supporting surface.
CSRA-SVX02A-EN 29
Page 30
Installation
Figure 11 — Incorrect Vertical Hose Installation
Incorrect vertical hose installation shows an incorrect hose installation. In this configuration the hose is installed without an elbow and with an elevation greater than 7 feet off the ground. This creates excessive stress at the hose coupling connection, causing the hose to stretch and separate from the coupling. It also causes the hose to crimp at the ground.
The following figures illustrate the correct and incorrect methods for installing hose in a horizontal and vertical combination application.
Figure 12 — Correct Horizontal/Vertical Installation
Correct horizontal/vertical installation shows a correct horizontal/vertical hose installation. In this configuration, correct installation techniques followed are:
• the hose is installed with elbows at both connection ends
• the vertical run of hose is less than 7 feet
• the hose is adequately supported by more than half its total length on the ground
These items minimize the stretching and separation at the hose-coupling interface and also the crimping of the hose at the ground.
30 CSRA-SVX02A-EN
Page 31
Installation
Figure 13 — Incorrect Horizontal/Vertical Installation
Incorrect horizontal/vertical installation shows an incorrect horizontal/vertical hose installation. In this configuration, a number of improper installation techniques can be noted:
• elbows are not installed
• the hose is completely supported by the couplings
• the vertical run of hose is greater than 7 feet
• the hose is not adequately supported by the ground
Figure 14 — Correct Unsupported Horizontal Installation
Correct unsupported horizontal installation illustrates a correct horizontal hose installation where there is a section of unsupported hose. The length of unsupported hose should be less than 7 feet. Also, the hose must be adequately supported by having more than half its total length on the ground.
CSRA-SVX02A-EN 31
Page 32
Installation
Hard Pipe Guidelines
Certain installations may require the use of hard pipe (steel or PVC). Hard pipe is typically recommended for (1) INDOOR INSTALLATIONS, (2) semi­permanent installations (three months or more) and/or (3) installations with space limitations.
When installing hard pipe:
• construct and install the piping according to local and national codes
• isolate and support the piping as required to prevent stress on the unit and vibration to building piping
If there are any questions regarding how to install water piping, contact a ChillerSource Technical Service Advisor, Charlotte, NC (800-755-5115).
Material Disposition
In the event the hose fails or leaks, call the ChillerSource Technical Service Advisor in Charlotte, NC (800-755-5115); tag the hose “BAD” and place it back in the shipping box.
Exceptions
The ChillerSource Technical Service Advisor, Charlotte, NC, must authorize any exceptions to the guidelines established in this bulletin in writing.
Freeze Protection from Ambient Conditions
Use the procedure described below to ensure that the chilled water system is adequately protected from freeze-up in applications where the unit remains operational at subfreezing ambient temperatures and against ice formation at the lowest expected operating temperatures by adding a non­freezing, low-temperature, heat-transfer fluid to the chilled water.
For evaporator water capacities, refer to the “System Start-Up” section. For the use and testing of the antifreeze solution, follow the manufacturer's recommendations.
Note: Use of an ethylene glycol-type antifreeze reduces unit cooling capacity; this condition must be accounted for during total system design. Also, the low pressure control may need to be changed. Contact the local Trane ChillerSource representative.
For all 60 Hz units, heat tape is factory-installed on the unit evaporator and all internal water piping.
This heat tape will protect the evaporator and internal piping from freezing due to low ambient temperatures down to -20°F. Heat tape power draw for 60 Hz units is 210 Watts on 25-30 Ton units, and 420 Watts on 40 through 60 Ton units.
32 CSRA-SVX02A-EN
Page 33
Installation
Install an appropriately sized fused disconnect switch for field installed heat tape when applying it to all exposed piping. A shore power 115V plug is provided for factory installed heat tape. Be sure to use heat tape that is recommended for low-temperature applications, it should be thermostatic controlled and dissipate 7 watts per linear foot. A field installed thermostat must be installed if the heat tape does not include a thermostat.
To install the heat tape properly, follow the instructions provided by the heat tape manufacturer. If no instructions are provided, use the recommendations outlined below:
1. Wrap the heat tape around the pipe or apply it straight along the pipe, as necessary, to provide the required protection. Refer to Figure 15 and Tables 2A and 2B.
2. Use friction tape to secure the heat tape to the solution pipe.
3. Place the thermostat parallel to the water pipe and tape it tightly in place at both ends. Be sure to install the thermostat on the most exposed (i.e., coldest) portion of the pipe.
4. Wrap the pipe with an insulation material and cover it with a weatherproof tape (if additional protection is required). On vertical pipe runs, start the wrap at the bottom and work up as shown in Figure 15. Be sure to over­lap the tape so that it will shed moisture.
Note: To prevent heat tape failure, frozen pipes, and other unit damage, do not install insulation under the weatherproof wrap if a non-thermostatic controlled heat tape is used.
CSRA-SVX02A-EN 33
Page 34
Installation
Figure 15 — Typical Insulated, Spiralled Heat Tape Installation
Table 2A — Non-Insulated, Non-Thermostatically Controlled Heat Tape with Outer Wrap
Application
Technique “Straight”
Heat Tape Req. per Linear
Ft. of Pipe
Protection Down to (°F) 11° 15° 20° 22°
“Spiralled”
Heat Tape Req. per Linear
Ft. of Pipe
Protection Down to (°F) -27° -23° -20° -17° -15°
Note: Spiralled applications are twisted around pipe 3 turns per linear foot of pipe.
2” 2-1/2” 3” 4” 5”
12” 12” 12” 12” 12”
28” 31” 35” 47” 54”
Pipe Size
34 CSRA-SVX02A-EN
Page 35
Installation
Table 2B — Insulated, Non-Thermostatically Controlled Heat Tape with Outer Wrap
Application
Technique “Straight”
Heat Tape Req. per Linear
Ft. of Pipe
Protection Down to (°F) -6° 12° 16°
“Spiralled”
Heat Tape Req. per Linear
Ft. of Pipe
Protection Down to (°F) -55° -50° -45° -40° -1°
Note: Spiralled applications are twisted around pipe 3 turns per linear foot of pipe.
2” 2-1/2” 3” 4” 5”
12” 12” 12” 12” 12”
26” 31” 35” 47” 54”
Pipe Size
Electrical Cable
Technical Data
Conductor Size: 2/0 AWG
Ampacity: 300 Amps per conductor*
Construction: Rope stranded copper conductor, colored-coded (blue, red,
green and black) connectors on each end. Insulation is composed of water, acid, ozone and chemical resistant thermoplastic rubber compound.
Temperature Rating (°F): -49 to 194
Weight (Lbs./100 Ft.): 64
Conductor Nominal OD (in.): 0.8200
Cable Rating: UL Rated at 2000 Volts, C(UL) 600 volts for continuous use.
*The values listed above are based upon ambient temperature @ 86 °F, where the individual conductor is not installed in raceways or buried (Reference NEC Code, Table 310-16, 1999 Edition).
CSRA-SVX02A-EN 35
Page 36
Installation
*Temperature Correction Factors
Ambient Temp °F
70 - 77 1.04
78 - 86 1.00
87 - 95 0.96
96 - 104 0.91
105 - 113 0.87
114 - 122 0.82
Electrical Cable Box
The electrical cable is contained in a lightweight plastic box, approximately four feet long and four feet wide. The contents are as follows: Four (4) 100' sections of 2/0 awg cable and eight (8) 15' pig-tails.
Figure 16 — Electrical Cable Box
Factor
Cam-lok Connectors
Each cable is supplied with a male cam-lok on one end and a female cam­lok on the other. The cam-lok connectors provide quick, easy one-twist connections. The picture to the right depicts a typical connection. *For non cam-lok connections four male pig-tails and four female pig-tails are provided in a standard electrical cable box (see Pig-Tail Connectors).
36 CSRA-SVX02A-EN
Page 37
Installation
Figure 17 — Cam-lok Connectors
Pig-Tail Connectors
Each cable box has four male pig-tails and four female pig-tails for non cam­lok connections. Each male pig-tail has a male cam-lok on one end and a barrel lug on the other. Each female pig-tail has a female cam-lok on one and a barrel lug. The barrel lug end allows for connection into a power distribution panel or non cam-lok equipment. The pig-tail can then be connected to the standard cam-lok cable, see schematic below.
Pig-Tail/Cam-Lok Connection Schematic
Lug
M F M F Lug
CSRA-SVX02A-EN 37
Page 38
Installation
Figure 18 — Pig-tail Connectors
Field Installed Power Wiring
An overall dimensional layout for the field installed wiring entrance into the unit is illustrated in Figure 4. To insure that the unit's supply power wiring is properly sized and installed, follow the guidelines outlined below.
Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes.
Verify that the power supply available is compatible with the unit's nameplate ratings. The available supply power must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the 3­phase power supply to the unit.
CAUTION Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Circuit Breaker External Handle (Factory Mounted Option)
Units are provided with an externally mounted circuit breaker handle. This allows the operator to disconnect power from the unit without having to open the control panel door. The handle locations and its three positions are shown below;
“ON” - Indicates that the circuit breaker is closed, allowing the main power supply to be applied at the unit.
“OFF” - Indicates that the circuit breaker is open, interrupting the main power supply to the unit controls.
“OPEN COVER/RESET” - Turning the handle to this position releases the handle from the circuit breaker, allowing the control panel door to be opened.
38 CSRA-SVX02A-EN
Page 39
Installation
WARNING
Hazardous Voltage!
Disconnect all electric pow er, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the pow er can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Once the door has been opened, it can be closed with the handle in any one of the three positions outlined above, provided it matches the circuit breaker position.
An overall layout of the field required power wiring is illustrated in Figure 19. These diagrams are representative of standard applications and are for general reference only. Always refer to the wiring diagram that shipped with the unit for specific electrical schematic and connection information.
Main Unit Power Wiring
Table 3 lists the field connection wire ranges for both the cam-type connector and lug-type connector in the main power supply box The unit electrical data is listed in Table 4. The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. Refer to the “Power Wire Sizing & Protection Device Equations”, for determining;
A. the appropriate electrical service wire size based on “Minimum Circuit Am-
pacity” (MCA),
B. the “Maximum Over current Protection” (MOP) device. C. the “Recommended Dual Element fuse size” (RDE).
1. A field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). Refer to the “Power Wire Sizing & Protection Device Equations” (DSS calcula­tion), for determining the correct size.
2. Complete the unit's power wiring connections onto either the factory sup­plied cam-type receptacle, or the factory mounted lug-type connector inside the power supply box. There are also 3/8” holes provided for field supplied wire terminals. Refer to the customer connection diagram that shipped with the unit for specific termination points.
3. Provide proper grounding for the unit in accordance with local and national codes
CSRA-SVX02A-EN 39
Page 40
Installation
Figure 19 — Typical Field Installed Power Wiring for Field Installed Pump
Refer to the Wiring Diagram Notes at the end of this Section
40 CSRA-SVX02A-EN
Page 41
Installation
Table 3 — Customer Connection Wire Range
Power Wire Sizing and Protection Device Equations
To correctly size the main power wiring for the unit, use the appropriate calculation(s) listed below. Read the load definitions that follow and use Calculation #1 for determining the MCA (Minimum Circuit Ampacity), MOP (Maximum Over current Protection), and RDE (Recommended Dual Element fuse size) for each unit. Use Calculation #2 to determine the DSS (Disconnect Switch Size) for each unit.
Load Definitions: LOAD 1 = CURRENT OF THE LARGEST MOTOR
(COMPRESSOR OR FAN MOTOR)
LOAD 2 = SUM OF THE CURRENTS OF ALL REMAINING MOTORS
LOAD 4 = CONTROL POWER TRANSFORMER = AND ANY OTHER LOAD RATED AT 1 AMP OR MORE
Calculation #1 (MCA, MOP, and RDE)
MCA = (1.25 x LOAD 1) + LOAD 2 + LOAD 4
MOP = (2.25 x LOAD 1) + LOAD 2 + LOAD 4
Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size as listed in NEC 240-6, select the next lower standard fuse rating.
Note: If selected MOP is less than the MCA, then select the lowest standard maximum fuse size which is equal to or larger than the MCA, provided the selected fuse size does not exceed 800 amps.
CSRA-SVX02A-EN 41
Page 42
Installation
CGAF25
CGAF40
CGAF60
561
23
,
4
RDE = (1.5 x LOAD 1) + LOAD 2 + LOAD 4
Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as listed in NEC 240 - 6 select the next higher standard fuse rating.
Note: If the selected RDE is greater than the selected MOP value, then select the RDE value to equal the MOP value.
Calculation #2 Disconnect Switch Sizing (DSS)
DSS = 1.15 X (LOAD 1 + LOAD 2 + LOAD 4)
Table 4 — Unit Electrical Data
Unit Size
Compressor Motor (Each)
Rated
Voltage
460/60/3 61 80 2 17.1/25.4 117/178 3 1.8 0.9 1 6.5 5
460/60/3 92 90 4 17.2 117 4 1.8 0.9 1 12.0 10
460/60/3 131 125 4 25.4 178 6 1.8 0.9 1 12.0 10
Min. Ckt.
Amp.
Max. Fuse
Size
Qty
RLA
LRA Qty FLA Kw Qty FLA HP
Cond. Fan Motors
(Each)
Pump
Notes:
1. Minimum Circuit Ampacity is 125% of the largest compressor RLA plus 100% of the other compressor RLA plus the sum of the condenser fan FLA plus any other load rated at 1 Amp or more.
2. Maximum Fuse Size is 225% of the largest RLA plus 100% of the other compressor RLA plus the sum of the condenser fan FLA plus any other load rated at 1 Amp or more.
3. Recommended Dual Element Fuse Size is 150% of the largest compressor RLA plus 100% of the other compressor RLA plus the sum of the condenser fan FLA plus any other load rated at 1 Amp or more.
4. RLA is rated in accordance with UL Standard 465. Local codes may take precedence.
5. All units are across-the-line starting. Compressors will never start simultaneously.
6. (60 Hz units) One field provided 115/60/1, 15 amp power supply is required to operate the evaporator heat tape. (50 Hz unit) One field provided 240/50/1, 5 amp power supply is required to operate the evaporator heat tape.
Field Installed Control Wiring
Before installing any connecting wiring, refer to Figure 4 for the electrical access locations provided on the unit. Install appropriately sized control wiring for the 115 volt electrical components as required by the application.
WARNING
Hazardous Voltage!
Disconnect all electric pow er, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the pow er can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
42 CSRA-SVX02A-EN
Page 43
Installation
Since the unit-mounted 115V control power transformer (1T1) and the 24V control power transformers (1T2, 1T3, 1T4) are provided on all units, it is not necessary to run a separate 115 volt control circuit power source to the unit.
A separate field provided 15 Amp maximum 115V 60 Hz power source is required when the unit is equipped with field supplied heat tape. Refer to the wiring diagrams that shipped with the unit for proper connections. The factory supplied evaporator heat tape already is conveniently wired and can be energized by connecting to the shore power receptacle on the unit.
Note: All field wiring must conform to NEC guidelines as well as state and local codes.
Controls using 24 VAC
Before installing any connecting wiring, refer to Figure 4 for the electrical access locations provided on the unit and Table 5 for AC conductor sizing guidelines, and;
A. Use copper conductors unless otherwise specified.
B. Ensure that the AC control wiring between the controls and the unit's ter-
mination point does not exceed three (3) ohms/conductor for the length of the run.
Note: Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient AC voltage supply.
C. Be sure to check all loads and conductors for grounds, shorts, and miswir-
ing.
D. Do not run the AC low voltage wiring in the same conduit with the high volt-
age power wiring.
Install appropriately sized 24 volt AC/DC control wiring for the electrical components as required by the application.
These components may include:
• Remote Running/Alarm Indicator
• External Auto/Stop
• Flow Control Interlock
Table 5 — AC Conductors
Distance from
Unit to Control
000 - 460 feet 18 gauge
461 - 732 feet 16 gauge
733 - 1000 feet 14 gauge
Recommended
Wire Size
CSRA-SVX02A-EN 43
Page 44
Installation
Remote Running/Alarm Indicator (Optional)
If the remote run indication and alarm contacts are used, a 24 VAC control circuit must be provided between the Remote Running/Alarm Indicator panel and the appropriate terminals located at the UCM. Maximum contact rating @ 24 VAC is 10 Amp in-rush and 3.2 Amp sealed. Refer to the “Field Wiring” diagrams illustrated in Figure 20A. Provide a proper remote panel ground connection.
External Auto/Stop (Optional)
If the unit utilizes an optional remote Auto/Stop function, the installer must provide control wiring from the remote pump relay contacts (5S67) to the appropriate terminals on 1TB4 terminal board.
When this set of contacts opens, the UCM reads it as a command to stop chiller operation and begin the pump down cycle (if enabled).
Circuit requirements are 2-wire, 24 VDC; w/maximum contact rating 12 mA. Refer to the field wiring diagram illustrated in Figure 20A for the termination points.
Flow Control Interlock (6S1)
The flow switch is a binary output device and is wired within the interlock circuit if a chilled water flow interlock diagnostic is desired for the system. Before installing the control wiring, refer to Figure 4 for the electrical access into the control panel. Refer to the field connection diagram for the specific connection points.
Provide a proper ground for all control circuitry at the ground connection screws provided within the unit's control panel.
Controls using DC Analog Input/Outputs (Standard Low Voltage Multiconductor Wire)
Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to Figure 4 for the electrical access locations provided on the unit.
A. Table 6 lists the conductor sizing guidelines that must be followed when
interconnecting the DC Installation binary output devices and the system components utilizing a DC analog input\output signal to the unit.
Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls.
B. Ensure that the wiring between the binary and analog controls and the
unit's termination point does not exceed two and a half (2.5) ohms/conduc­tor for the length of the run.
C. Do not run the electrical wires transporting DC signals in or around conduit
housing high voltage wires.
44 CSRA-SVX02A-EN
Page 45
Installation
Table 6 — DC Conductors
Distance from
Unit to Control
000 - 499 feet 16 gauge
500 - 1000 feet 14 gauge
Recommended
Wire Size
Controls using DC Communication Links
Before installing any connecting wiring between the unit and components utilizing a DC communication link, refer to the connection diagram that shipped with the unit for the electrical access and connection locations provided on the unit.
A. Wiring for the components utilizing a DC communication link must be
shielded cable (Belden 8760 or equivalent). Ground the shield at one end only.
B. Table 6 lists the conductor sizing guidelines that must be followed when in-
terconnecting a communication link to the unit. C. Communication link must not exceed 5,000 feet maximum for each link. D. Communication link must not pass between buildings. E. Do not run the electrical wires transporting DC signals in or around conduit
housing AC voltage wires.
Table 7 — Maximum Communications Wiring Length
Maximum
Communication
Link Wiring Length
1,000 feet Up to 60 PF/FT
2,000 feet Up to 50 PF/FT
3,000 feet Up to 40 PF/FT
4,000 feet Up to 30 PF/FT
5,000 feet Up to 25 PF/FT
PF/FT = Picofarads/foot
CSRA-SVX02A-EN 45
Maximum
Capacitance
Between
Conductors
Page 46
Installation
ICS™ Communication Link
This option allows the unit control module (UCM) in the unit to exchange information (i.e., operating setpoints and AUTO/STOP commands) with a higher level control device, such as a Tracer. Twisted-pair conductors establish the bi-directional communications link between the unit's control module and Tracer.
1. Refer to the Tracer installation literature to determine proper communica­tion link termination connections at the Tracer unit. Multiple UCM's on the communication link can be connected in a “daisy chain” configuration.
2. Connect the shield of the communication link wiring to the designated shield terminal at the Tracer 100.
3. Connect the shielded, twisted pair leads from the Tracer to the proper ter­minals on the UCM. There is no polarity requirement for this connection.
4. At the UCM, the shield should be cut off and taped to prevent any contact between the shield and ground.
Note: On multiple unit installations, connect the shield between each “daisy­chained” UCM in the system to the shield of the twisted-pair leads going to the next unit in line. Tape the spliced connection to prevent any contact between the shield and ground. At the last UCM on the link, the shield should be cut off and taped.
Ice Building Control Option
The CGM provides auxiliary control for a customer specified/installed contact closure for ice making. When this field installed normally open contact (5K86) is provided, the chiller will run normally. Upon contact closure, the unit will operate fully loaded until the entering water temperature falls below the pre-programmed ice building setpoint. High quality silver or gold-plated contacts are recommended. The field supplied contacts must be compatible with 24 VDC, 12 mA resistive load.
Connect the 5K86 relay contacts to the proper terminals on 1TB4 as illustrated in Figure 20A. Refer to the latest version of CGAF-IOM-2 for more complete details.
Compressor Inhibit / KW Limit
The unit is equipped with a 0-5V GBAS and a TCI module, the customer provided/installed remote contact (5K89) initiates the demand limit function. When the contact is “Open”, the chiller will operate normally. When the contact closes, the unit will be limited to the programmed operating capacity (25%, 50%, 75%, or 100%). When the contact opens, normal chiller operation is restored.
High quality silver or gold-plated contacts are recommended. These customer-supplied contacts must be compatible with 24 VDC, 12 mA resistive load. Refer to the wire selection Table 6 for proper wire size and Figure 20B for proper termination points.
Connect the wiring from the field supplied normally open contacts between terminals 5 and 6 on 1TB16, if when 0 - 5 Volt BGAS is installed.
46 CSRA-SVX02A-EN
Page 47
Installation
Figure 20A — Typical Field Control Connections Diagram
CSRA-SVX02A-EN 47
Page 48
Installation
Figure 20B — Typical GBAS 0 - 5 Volt Connections Diagram
48 CSRA-SVX02A-EN
Page 49
Installation
Field Connection Diagram Notes for all System Control Options
CSRA-SVX02A-EN 49
Page 50
Installation
Use the checklist provided below in conjunction with the “General Unit Requirement Checklist“ to ensure that the unit is properly installed and ready for operation. Be sure to complete all of the procedures described in this section before starting the unit for the first time.
[ ] Turn the field supplied disconnect switch, located upstream of the unit, to the “Off” position.
WARNING
Hazardous Voltage!
Disconnect all electric pow er, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the pow er can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
[ ] Turn the “System” selection switch (at the Remote Panel) to the “Off” position and the “Fan” selection switch (if applicable) to the “Auto” or “Off” position.
[ ] Check all electrical connections for tightness and “point of termination” accuracy.
[ ] Verify that the condenser airflow will be unobstructed.
[ ] Check the condenser fan blades. Ensure they rotate freely within the fan orifices and are securely fastened to the fan motor shaft.
[ ] Verify that all compressor service valves, discharge service valves, and liquid line service valves are back seated on each circuit.
CAUTION Compressor Damage!
Compressor service valves must be fully opened before start-up (suction, discharge, liquid line, and oil line). Failure to fully open valves prior to start-up may cause compressor failure due to lack of refrigerant and/or oil flow .
[ ] Inspect the interior of the unit for tools and debris.
[ ] Fill the chilled water system.
[ ] Vent the chilled water system at the highest points in the system. Vent the air out of the chiller barrel by opening the vent, located on the top of the chiller barrel. Close the vent when the chiller barrel is full of water.
[ ] Once the system has been filled, inspect the entire chilled water piping system for leaks. Make any necessary repairs before proceeding.
50 CSRA-SVX02A-EN
Page 51
System Pre-Start Procedures
Note: To avoid possible equipment damage, do not use untreated or
improperly treated system water.
Voltage Imbalance
Excessive three phase voltage imbalance between phases will cause motors to overheat and eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage between phases 1, 2, and 3 and calculate the amount of imbalance as follows:
% Voltage Imbalance = where;
AV (Average Voltage) =
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from the average voltage.
Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts would be:
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This much imbalance between phases can equal as much as a 20% current imbalance with a resulting increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is over 2%, notify the proper agencies to correct the voltage problem before operating this equipment.
AVVD
100
----------------------
AV
Volt1 Volt2 Volt3++
--------------------------------------------------------
221230227++
--------------------------------------- 226Avg
100
3
3
226221
------------------------ 2.2= 226
=
·
Scroll Compressor Current Imbalance
Typically, current imbalance is associated with loss in motor efficiency, higher operating motor temperature, loss of performance and reliability.
With the designs of specialized motors such as those used in the Trane scroll compressor, operating temperature, efficiency, performance, and reliability has been taken into account in the total performance of the compressor.
Current imbalance in a scroll compressor can typically vary from 4 to 15 percent with balanced line voltage. This imbalance occurs because not all of the winding turns see the same amount of stator iron. The variance of iron within the motor is to accommodate design requirements for motor cooling and oil return.
CSRA-SVX02A-EN 51
Page 52
System Pre-Start Procedures
At low operating voltage and high operating load, the imbalance may be around 4 percent. At high operating voltage and low operating load, the imbalance may be as high as 15 percent.
If an imbalance situation is suspected within the compressor (current draw unequal between phases) and the line voltage imbalance does not exceed 2 percent;
1. Turn the field supplied disconnect switch, located upstream of the unit to the “Off” position.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
2. Disconnect the compressor leads at the compressor terminals.
3. Measure the resistance of the compressor windings at the compressor terminals.
The actual resistance measured across each winding is not as important as the amount of variation between the windings. The actual resistance measured may vary due to the accuracy of the meter, rounding off of the resistance readings, and the amount of resistance between the meter leads and the compressor terminals.
Since the amount of copper in each winding is very consistent, the variance between the windings should not exceed 7 percent.
Example: Typical 10 Ton, 460 volt, 60 Hz compressor has a winding resistance of 1.44 to 1.09 Ohms.
Electrical Phasing
Unlike traditional reciprocating compressors, scroll compressors are phase sensitive. Proper phasing of the electrical supply to the unit is critical for proper operation and reliability.
The compressor motor is internally connected for clockwise rotation with the incoming power supply phased as A, B, C.
Proper electrical supply phasing can be quickly determined and corrected before starting the unit by observing the red phase monitor light on the chiller control panel door and following the steps below
[ ] Turn the field supplied disconnect switch that provides power to the chiller circuit breaker t the “OFF” position.
52 CSRA-SVX02A-EN
Page 53
System Pre-Start Procedures
[ ] Open switch (1S70), 24V Transformer SW and close switch (1S1), 115V control circuit SW inside chiller control panel.
[ ] Close the disconnect switch or circuit protector switch that provides the supply power to the unit's chiller circuit breaker.
[ ] Turn chiller circuit breaker handle on main control panel door to the “ON” position.
[ ] Observe if “RED” light is illuminated on outside of chiller control panel. If red light is not illuminated, push red light to test if illumination occurs. If illumination occurs only when pushed, then phases are correct. If red light is illuminated, open the field disconnect switch or circuit breaker protection switch and reverse any two power wires.
High voltage is present at chiller circuit breaker 1CB1.
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to w ork w ith live electrical components. Have a qualified licensed electrician or other individual w ho has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions w hen exposed to live electrical components could result in death or serious injury.
CSRA-SVX02A-EN 53
Page 54
System Start-Up
Sequence of Operation
Chiller Control for Comfort Applications
The CGM controls the leaving solution temperature (LST) to within an adjustable setpoint using deadband control. The CGM monitors the LST sensor and determines how far away the temperature is from the leaving solution setpoint (LSS). The compressors are staged On/Off depending on where the LST is within the control deadband.
Deadband Calculation
The rate at which capacity stages are added or subtracted is determined by a control algorithm The CGM control deadband for comfort applications is a calculated value based upon the control response setpoint, the difference between LSS and LST, the number of capacity steps, the design delta temperature (DDT) of the system, and the number of capacity steps. The minimum comfort deadband is 1 degree F. The maximum comfort deadband above or below the LSS is 10°F for a two stage unit and 5°F for a 4 stage unit.
When the LST is inside the control deadband, the calculation is cleared and no response is initiated. When the LST is outside the deadband and the calculated control algorithm value equals 1, a capacity add command is initiated. Conversely, when the value of the control algorithm equals -1, a capacity subtract command is initiated. Once a capacity add or subtract command is given and a change in the compressor staging has been detected, the value of the control algorithm is reset to 0.
Chiller Freeze Protection
The CGM prevents evaporator fluid from freezing by utilizing two separate algorithms. One is the evaporator limit control algorithm which stages compressors “Off” if violated and the other is the evaporator freeze protection algorithm which activates auto/manual diagnostics if violated. The freeze protection function will always operate as long as the unit is in the Auto mode for both normal cooling applications and/or ice building modes. A manual reset diagnostic will occur if all compressors are shut off due to a freeze protection violation.
The evaporator limit control integrator (ELCI) algorithm calculates a value based upon the low leaving solution temperature cutout setpoint and the leaving solution temperature. When the value for ELCI drops below -1, the unit control will reduce the chiller capacity by staging down and/or inhibiting a compressor from operation. After each capacity subtract command from the capacity control algorithm is issued, ELCI is increased by 1 and retained. The ELCI is set to 0 any time the leaving solution temperature is greater than or equal to the low leaving solution temperature cutout (LLSC) + 3°F. Compressors will be prevented from operating until the leaving solution temperature (LST) is 4°F above the LLSC.
If Pumpdown is enabled and a subtract command is issued, the circuit will be allow to pumpdown.
54 CSRA-SVX02A-EN
Page 55
System Start-Up
Evaporator Freeze Protection Diagnostic
The evaporator freeze protection integrator (EFZ) will start integrating when the leaving solution temperature is less than the low leaving solution temperature cutout setpoint. Once EFZ integrates up to 30 Sec., the following diagnostics will occur:
1. If all compressors are off, an auto diagnostic will occur. All of the com­pressors will be prevented from operating until the LST is 4°F greater than the LLSC. Once the LST is 4°F above the LLSC, the unit will allow normal unit operation.
2. If any compressors are “On”, a manual diagnostic will occur. All of the compressors will be shutdown and locked out due to the violation of the evaporator freeze protection.
Sequence of Operation
Chiller Control for Process Applications
Process applications are characterized as having fast changes in load and these loads are not adequately controlled with the same scheme used for comfort applications. To provide better control of these dynamic loads, a Proportional + Integral “control to setpoint” (as opposed to “control to deadband”) control strategy is used. System reliability is inversely proportional to compressor cycle rates so reliability is the driving factor for determining maximum cycle rate which ultimately translates into cycle-to­cycle leaving solution temperature swings.
To provide stable capacity control, a 1 minute minimum time between compressor starts is required. The control will determine an estimate of instantaneous load based on error from setpoint for the leaving solution temperature and cycle the appropriate compressor stage to best match the calculated load.
Determining instantaneous error:
Error = Chiller Solution Temp - Chiller Solution Setpoint.
PI Control Calculation:
The CGM calculates the Load Value by applying PI calculations to the instantaneous error value. The Load Value consists of an integer part and a fractional part. The integer part represents which compressor stages are locked “On” and the fractional part represents the duty cycle required for the next higher compressor stage. For a 4 compressor unit, the Load Value will range from 0.0 to 4.0. For a 2 compressor unit, the Load Value will range from 0.0 to 2.0.
CSRA-SVX02A-EN 55
Page 56
System Start-Up
Duty Cycle Calculations calculate the duty cycle based on the calculated Load Value Fraction:
On Time Seconds = 3600 / 4 X Max Cycle Rate X (1-Load Value Fraction)
Off Time Seconds = 3600 / 4 X Max Cycle Rate X Load Value Fraction
Where Load Value Fraction = Fractional part of the calculated Load Value.
Sequence of Operation
Leaving Solution Reset (LSR)
Leaving Solution Reset (LSR) refers to the process of adjusting the Leaving Solution Setpoint (LSS) based on an external temperature.
When the optional Leaving Solution Reset (LSR) feature is used, the CGM will automatically adjust the LSS in response to a temperature change from one of three different temperature sensor:
1. Zone Temperature sensor
2. Outside Air Temperature sensor
3. Entering Solution Temperature sensor.
The reset temperature value (Start Temperature), to start resetting the Leaving Solution Setpoint (LSS) and the maximum amount of reset to be applied to the LSS is programmable through the Human Interface. The reset amount applied to the LSS is a linear calculation between the Start Temperature and the End Temperature. After the reset amount has been calculated, it is added to the Leaving Solution Setpoint to create the Leaving Solution Reset Setpoint. If the solution temperature is above the selected Start Temperature, the reset amount is zero. If the solution temperature is below the End Temp, the maximum amount of reset is applied. For reset type 'None', the amount of reset is zero. Refer to the appropriate reset type in Table 8 for reset schedules.
56 CSRA-SVX02A-EN
Page 57
System Start-Up
Table 8a — Chilled Solution Reset Schedule based on Zone Temperature
Reset Amount = Maximum LSS = ALSS + Maximum
Active Leaving
Solution Setpoint
Zone Reset Cooling
Factory
Preset = 5
Reset Amount = Zero (0) LSS = ALSS
Reset Amount = Maximum LSS = ALSS + Maximum
Factory
Preset = 5
Adjustable
Reset
3 - 16 F
End Temperature Range 66 - 81 Factory Preset = 75
Start Temperature Range 66 - 81 Factory Preset = 78
Zone
Temperature
Table 8b — Chilled Solution Reset Schedule based on Outside Air Temperature
Active Leaving
Solution Setpoint
Adjustable
Reset
3 - 16 F
Outside Air Reset Cooling
Reset Amount = Zero (0) LSS = ALSS
CSRA-SVX02A-EN 57
End Temperature Range 65 - 125 Factory Preset = 70
Start Temperature Range 65 - 125 Factory Preset = 90
OA
Temperature
Page 58
System Start-Up
Table 8c — Chilled Solution Reset Schedule based on Entering Solution Temperature
Reset Amount = Maximum LSS = ALSS + Maximum
Active Leaving
Solution Setpoint
Entering Solution Reset
Factory
Preset = 5
Reset Amount = Zero (0) LSS = ALSS
Adjustable
Reset
3 - 16 F
End Temperature Range 4 - 19 Factory Preset = 8
Start Temperature Range 4 - 19 Factory Preset = 10
EST - LST
Temperature
Sequence of Operation
Lead/Lag (Standard)
When Lead-Lag is enabled, for each capacity add request, the CGM will begin sequencing the compressors “On” that have:
A. the least number of starts; or,
B. the least run time (if number of starts are equal)
At each capacity subtract request, the CGM will begin sequencing the compressors “Off” that have:
A. the most run time; or,
B. the least number of starts (if more than one compressor has the same run
time)
If a compressor is locked out for any reason when a capacity add request occurs, the next available compressor which meets the specified criteria will be started.
If a compressor can not be turned “Off” due to the minimum “On Time”, the next compressor which meets the specified criteria will be turned “Off”.
On dual circuit units, as the first two capacity add requests are initiated, one compressor on each circuit will start before any additional compressors on any circuit is started. When staging down from three compressor stages to two compressor stages, the CGM will turn a compressor “Off” on the circuit that has the most compressors operating.
58 CSRA-SVX02A-EN
Page 59
System Start-Up
With Lead/Lag enabled, HGBP operation (if applicable) will be bypassed and the system will go directly into pumpdown when the last subtract command is initiated.
When the UCM is powered up (after a power loss), or any time the compressor's start time and run time are equal, the number one (Lead) designated compressor will be the first “On” and the number two (lag) designated compressor will be the first “Off” on single circuit units (20 - 30 Tons).
For dual circuit units (40 through 60 Tons), the “On” sequence will be A-C-B­D and the “Off” sequence will be D-B-C-A under the previously described conditions. Refer to Figure 23 for compressor locations.
Sequence of Operation
Condenser Fan Control
The CGM condenser fan control logic is dependent on the number of compressors operating per circuit and the saturated condensing temperature. Fan logic is not initiated until the low ambient start time has elapsed.
The condenser fan contactors, located in the unit control panel, initiate fan operation when energized. Refer to Figure 22 for the condenser fan locations and fan contactor designators. Dashed lines connecting pairs of fans indicate instances where one contactor controls both fans.
Sequence of Operation
Low Ambient Dampers
Low Ambient Dampers are used to extend the operation of these units from the standard operational temperatures to a minimum of 0°F without hot gas bypass or 10°F with hot gas bypass. (These values apply when wind speed across the condenser coil is less than 5 m.p.h.). If typical wind speeds are higher than 5 m.p.h., a wind screen around the unit may be required. By restricting the airflow across the condenser coils, saturated condensing temperatures can be maintained as the ambient temperatures change.
The low ambient damper actuator controls damper modulation for each refrigerant circuit in response to saturated condensing temperature.
Chilled Water Circulating Pump
Once the system has been filled, complete the following chilled water system start-up procedures.
1. Turn the 115 volt control circuit switch 1S1 and the 24 volt control circuit switch 1S70 located in the unit control panel to the “Off” position.
2. Turn the chiller circuit breaker (1CB1) and the pump circuit breaker on the pump starter panel, to the “On” position.
3. Close the field supplied main power disconnect switch or circuit protector switch that provides the supply power to the unit's circuit breaker (1CB1).
CSRA-SVX02A-EN 59
Page 60
System Start-Up
4. Turn the 24 volt control circuit switch 1S70 located in the unit control panel to the “On” position.
Note: To prevent the compressors from starting, leave the 115 volt control circuit switch “Off”.
5. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the CGAF-PTG manual for the SERVICE TEST screens and programming instructions.
6. Use Table 10 to program the solution pump for operation by scrolling through the displays.
7. Once the configuration for the pump is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to check rotating components. Have a qualified or licensed service individual w ho has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions w hen exposed to rotating components could result in death or serious injury.
Make sure all personnel are standing clear of the unit before proceeding. The programmed components will start when the TEST START time designated in the previous step has elapsed.
8. Press the TEST START key to start the test. Remember that the delay designated in Step 7 must elapse before the pump will begin to operate.
9. To balance the flow through the evaporator, adjust the flow rates between the minimum and maximum values given in Table 9. Flow rates above or below these values can cause equipment damage or improper unit oper­ation.
10.Check the flow device (if applicable) on the evaporator outlet piping to ensure it opens and closes properly.
11.Measure the evaporator water pressure drop at the system pressure gauge(s). Compare the readings to the pressure drop values given in Fig­ure 21.
Note: Evaporator pressure drop is an approximation and is to be used as a tool to estimate flow rate and as an aid to waterside system piping design. If an accurate measurement of flow is required, a flow meter must be installed in the system.
60 CSRA-SVX02A-EN
Page 61
45.00
40.00
35.00
30.00
25.00
System Start-Up
Table 9 — Evaporator Data for C25 through C60 Units
Unit Size Water Volume Minimum Flow Rate Maximum Flow Rate
gal liter gpm liter/s gpm liter/s
C60 37.8 143 72 4.5 216 13.6
Figure 21 — Evaporator Water Pressure Drop for CGAF-C20 through C60 Units (English)
C60 Ton
C25 Ton
C40 Ton
20.00
15.00
Pressure Drop (Feet of Water)
10.00
5.00
0.00 0 50 100 150 200 250
Flow Rate (GPM)
Note 1: Factor to convert “Feet of Water” to “Lbs. per Sq. Inch” (PSI): 2.3
Feet of Water = 1 PSI
CSRA-SVX02A-EN 61
Page 62
System Start-Up
COMPONENT
COMPONENT CONFIGURATION
BEING TESTED
Condenser
Compressor Stage
Low Ambient
Liquid Line
Solution
Fans1234
Damper Output
Solenoid Valve
Pump
* COMPRESSOR
20 thru 30 Ton
A
A-Off/B-On
K10-Off
K11-On
N/A
N/A0%OnOnB
A-On/B-Off
K10-On
K11-Off
N/A
N/A0%OnOn40 thru 60 Ton
1A
1A-Off/1B-On
K11-Off
K3-Off
K12-On
K4-Off
0%
Ckt #1 On
On
2A-Off/2B-Off
1B
1A-On/1B-Off
K11-On
K3-Off
K12-Off
K4-Off
0%
Ckt #1 On
On
2A-Off/2B-Off
2A
1A-Off/1B-Off
K11-Off
K3-Off
K12-Off
K4-On
0%
Ckt #2 On
On
2A-Off/2B-On
2B
1A-Off/1B-Off
K11-Off
K3-On
K12-Off
K4-Off
0%
Ckt #2 On
On
2A-On/2B-Off
25 Ton
A-2B1
A-On/B-Off
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
B-2B2/2B3
A-Off/B-On
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
40 Ton
1A-2B1
1A-On/1B-Off
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-Off/2B-Off
1B-2B2
1A-Off/1B-On
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-Off/2B-Off
2A-2B4
1A-Off/1B-Off
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-On/2B-Off
2B-2B5
1A-Off/1B-Off
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-Off/2B-On
50 & 60 Ton
1A-2B1
1A-On/1B-Off
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-Off/2B-Off
1B-2B2/2B3
1A-Off/1B-On
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-Off/2B-Off
2A-2B4
1A-Off/1B-Off
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-On/2B-Off
2B-2B5/2B6
1A-Off/1B-Off
Off
Off
Off
Off
100%
Ckt #1/2 Off
Off
2A-Off/2B-On
CGM Evap Solution
1A-Off/1B-Off
Off
Off
Off
Off0%Ckt #1/2 Off
On
* - Compressors for the 20 thru 60 Ton units can operate individually or together and in any order while in the SERVICE
TEST mode.
Note:
Do Not operate the compressors for extended periods of time without the condenser fans, High
Head Pressure will develop.
** - Condenser fan outputs can operate individually or together and in any order while in the SERVICE TEST mode.
Table 10 — Service Test Guide for Component Operation
62 CSRA-SVX02A-EN
Page 63
System Start-Up
Verifying Proper Fan Rotation
1. Close the main power disconnect switch or circuit protector switch that provides the supply power to the unit's circuit breaker (1CB1).
2. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the CGAF-PTG manual for the SERVICE TEST screens and programming instructions.
3. Use Table 10 to program the condenser fans for operation by scrolling through the displays. All of the condenser fans can be programmed to be “On”, if desired. Verify proper fan rotation for VFD's with bypass.
Refer to Figure 22 for the condenser fan locations and the Human Inter­face designator.
4. Once the configuration for the Fans is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to des­ignate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to check rotating components. Have a qualified or licensed service individual w ho has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions w hen exposed to rotating components could result in death or serious injury.
Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the designated TEST is initiated.
5. Press the TEST START key to start the test. Remember that the delay designated in Step 4 must elapse before the fans will begin to operate.
6. Check the supply fan and the exhaust fans (if equipped) for proper rota­tion. The direction of rotation is indicated by an arrow on the fan hous­ings. Check the condenser fans for clockwise rotation when viewed from the top.
If all of the fans are rotating backwards;
A. Press the STOP key at the Human Interface Module in the unit control pan-
el to stop the fan operation.
B. Open the field supplied disconnect switch upstream of the unit. Lock the
disconnect switch in the open position while working at the unit.
CSRA-SVX02A-EN 63
Page 64
System Start-Up
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
C. Interchange any two of the field connected main power wires at the unit cir-
cuit breaker (1CB1).
Note: Interchanging “Load” side power wires at the fan contactors will only affect the individual fan rotation. Ensure that the voltage phase sequence at the main terminal block 1TB1 or the factory mounted disconnect switch 1S14 is ABC as outlined in the “Electrical Phasing” section.
If some of the fans are rotating backwards;
A. Press the STOP key at the Human Interface Module in the unit control pan-
el to stop the fan operation.
B. Open the field supplied disconnect switch upstream of the unit. Lock the
disconnect switch in the open position while working at the unit.
C. Interchange any two of the fan motor leads at the contactor for each fan
that is rotating backwards
64 CSRA-SVX02A-EN
Page 65
System Start-Up
Figure 22 — Condenser Fan Locations
CSRA-SVX02A-EN 65
Page 66
System Start-Up
Compressor Start-Up
1. Ensure that the main power disconnect switch and the control power cir­cuit breaker for the “System Solution Pump” is “On”.
2. Before closing the main power disconnect switch for the unit, ensure that the compressor discharge service valve and the liquid line service valve for each circuit is back seated.
CAUTION
Compressor Damage!
Compressor service valves must be fully opened before start-up (suction, discharge, liquid line, and oil line). Failure to fully open valves prior to start-up may cause compressor failure due to lack of refrigerant and/or oil flow .
3. Remove the protective plastic coverings that shipped over the compres­sors.
4. Check the compressor oil levels. The oil level in each manifolded set of compressor sight glasses should be equally 1/2 to 3/4 full when they are “Off”.
5. Check the condenser coils. They should be clean and the fins should be straight. Straighten any bent coil fins with an appropriate sized fin comb.
6. Turn the main power disconnect switch or circuit protector switch that provides the supply power to the unit’s terminal block 1TB1 or the unit mounted disconnect switch 1S14 to the “On” position.
7. Turn the 24 volt control circuit switch 1S70 to the “On” position.
8. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the CGAF-PTG for the SERVICE TEST screens and programming instructions.
9. Use Table 10 to program the following system components for operation by scrolling through the displays;
20 through 30 Ton
Compressor 1A (On) Compressor 1A (On)
Compressor 1B (Off) Compressor 1B (Off)
Condenser Fans (On) Compressor 2A (Off)
Solution Pump (On) Compressor 2B (Off)
66 CSRA-SVX02A-EN
40 through 60 Ton
Condenser Fans (On)
Solution Pump (On)
Page 67
System Start-Up
10.Attach a set of service gauges onto the suction and discharge gauge ports for each circuit. Refer to Figure 23 for the various compressor loca­tions.
11.Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to check rotating components. Have a qualified or licensed service individual w ho has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions w hen exposed to rotating components could result in death or serious injury.
Make sure all personnel are standing clear of the unit before proceeding. The programmed components will start when the TEST START time designated in the previous step has elapsed.
12.Turn the 115 volt control circuit switch 1S1 “On”.
13.Press the TEST START key to start the test. Remember that the delay designated in step 11 must elapse before the system will begin to oper­ate.
14.Once each compressor or compressor pair has started, verify that the rotation is correct. If a scroll compressor is rotating backwards, it will not pump and a loud rattling sound can be observed. Check the electrical phasing at the load side of the compressor contactor.
If the phasing is correct, before condemning the compressor, interchange any two leads to check the internal motor phasing. Refer to the illustration in Figure 24 for the compressor terminal identification. If the compressor runs backward for an extended period (15 to 30 minutes), the motor wind­ings can over heat and cause the motor winding thermostats to open. This will cause a “compressor trip” diagnostic and stop the compressor.
15.Verify that the oil level in each compressor is correct. The oil level may be down to the bottom of the sightglass but should never be above the sight­glass.
16.Press the STOP key at the Human Interface Module in the unit control panel to stop the compressor operation.
17.Repeat steps 8 through 16 for each compressor stage and the appropri­ate condenser fans.
CSRA-SVX02A-EN 67
Page 68
System Start-Up
Verifying Proper Refrigerant Charge
1. Attach a set of service gauges onto the suction line and liquid line gauge ports for each circuit. Refer to Figure 23 for the various compressor loca­tions.
2. Open the Human Interface access door, located in the unit control panel, and press the SERVICE MODE key to display the first service screen. Refer to the latest edition of the CGAF-PTG for the SERVICE TEST screens and programming instructions.
3. Use Table 10 to program the following system components for the num­ber 1 refrigeration circuit by scrolling through the displays;
Chilled Solution Pump (On)
All Compressors for each circuit (On)
Condenser Fans for each circuit (On)
Hot Gas Bypass (Disabled, if applicable)
Low Ambient Dampers (100%, if applicable)
4. Once the configuration for the components is complete, press the NEXT key until the LCD displays the “Start test in __Sec.” screen. Press the + key to designate the delay before the test is to start. This service test will begin after the TEST START key is pressed and the delay designated in this step has elapsed. Press the ENTER key to confirm this choice.
WARNING
Rotating Components!
During installation, testing, servicing and troubleshooting of this product it may be necessary to check rotating components. Have a qualified or licensed service individual w ho has been properly trained in handling exposed rotating components, perform these tasks. Failure to follow all safety precautions w hen exposed to rotating components could result in death or serious injury.
Make sure all personnel are standing clear of the unit before proceeding. The programmed components will start when the TEST START time designated in the previous step has elapsed.
5. Press the TEST START key to start the test. Remember that the delay designated in step 4 must elapse before the system will begin to operate.
6. After all of the compressors and condenser fans for the number 1 circuit have been operating for approximately 30 minutes, observe the operat­ing refrigerant pressures and measure the system superheat and sub­cooling.
The outdoor ambient temperature must be between 65°F and 105°F. When the temperatures are outside of these ranges, refer to Table 10 for the recommended refrigerant capacities.
68 CSRA-SVX02A-EN
Page 69
System Start-Up
Environmental scientists have found evidence that refrigerant emissions contribute to depletion of ozone in the upper atmosphere and can increase global warming. Trane encourages every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC and HFC refrigerant to the atmosphere that can result from installation, operation, routine maintenance, or major service on this equipment. Only technicians with EPA certification should be allowed to handle CFC, HCFC or HFC refrigerants. Compliance or certification to other local or state codes may also be required when handling refrigerants. Always act in a responsible manner to conserve refrigerants.
Refer to general service bulletin MSCU-SB-1 (latest edition).
Subcooling
With the unit operating at “Full Circuit Capacity”, acceptable subcooling ranges between 14°F to 22°F.
Measuring Subcooling
A. At the liquid line service valve, measure the liquid line pressure. Using a
Refrigerant 22 pressure / temperature chart, convert the pressure reading into the corresponding saturated temperature.
B. Measure the actual liquid line temperature as close to the liquid line service
valve as possible. To ensure an accurate reading, clean the line thoroughly where the temperature sensor will be attached. After securing the sensor to the line, insulate the sensor and line to isolate it from the ambient air.
Note: Glass thermometers do not have sufficient contact area to give an accurate reading.
C. Determine the system subcooling by subtracting the actual liquid line tem-
perature (measured in b) from the saturated liquid temperature (converted in a).
Superheat
The reliability and performance of the refrigeration system is heavily dependent upon proper expansion valve adjustment. Therefore, the importance of maintaining the proper superheat cannot be over emphasized. Accurate measurements of superheat will provide the following information.
A. How well the expansion valve is controlling the refrigerant flow.
B. The efficiency of the evaporator. C. The amount of protection the compressor is receiving against flooding or
overheating.
The recommended range for superheat is 10 to 16 degrees at the evaporator.
Systems operating with less than 10 degrees of superheat:
A. Could cause serious compressor damage due to refrigerant floodback.
B. Removes working surface from the evaporator normally used for heat
transfer.
CSRA-SVX02A-EN 69
Page 70
System Start-Up
Systems operating with superheat in excess of 16 degrees:
A. Could cause excessive compressor cycling on internal winding thermostat
which leads to compressor motor failure.
B. Lowers the efficiency of the evaporator by reducing the heat transfer ca-
pability.
Measuring Superheat
A. Measure the suction pressure at the suction line gauge access port locat-
ed near the compressor.
B. Using a Refrigerant / Temperature chart, convert the pressure reading to
a corresponding saturated vapor temperature.
C. Measured the suction line temperature as close to the expansion valve
bulb, as possible.
D. Subtract the saturated vapor temperature obtained in Step B from the ac-
tual suction line temperature obtained in step c. The difference between the two temperatures is known as “superheat”.
Note: When adjusting superheat, recheck the system subcooling before shutting the system “Off”.
7. Once the checks and adjustments for the operating circuit has been com­pleted, check and record the:
ambient temperature; compressor oil level (each circuit); compressor suction and discharge pressures (each circuit); superheat and subcooling (each circuit);
Record this data on an “Operator's Maintenance Log” shown in Table 12.
8. Press the STOP key at the Human Interface Module in the unit control panel to stop the system operation.
9. Repeat Steps 1 through 8 for the number 2 refrigeration circuit.
10.After shutting the system off, check the compressor's oil's appearance. Discoloration of the oil indicates that an abnormal condition has occurred. If the oil is dark and smells burnt, it has overheated because of: compres­sor is operating at extremely high condensing temperatures; high super­heat; a compressor mechanical failure; or, occurrence of a motor burnout.
If the oil is black and contains metal flakes, a mechanical failure has occurred. This symptom is often accompanied by a high compressor amperage draw.
If a motor burnout is suspected, use an acid test kit to check the condition of the oil. Test results will indicate an acid level exceeding 0.05 mg KOH/g if a burnout occurred.
70 CSRA-SVX02A-EN
Page 71
System Start-Up
Compressor Oil
The scroll compressor uses Trane OIL-42 without substitution appropriate oil charge for a 9 and 10 Ton scroll compressor is 8.5 pints. For a 14 and 15 Ton scroll compressor, use 13.8 pints.
Table 11 — Recommended Refrigerant Capacities
Unit Size Refrigerant
Charge*
C25 54.0
C40 38.0
C60 67.0
* The listed refrigerant charge is for pounds per circuit.
Figure 23 — Typical Compressor Locations
. The
CSRA-SVX02A-EN 71
Page 72
System Start-Up
Figure 24 — Typical Compressor Terminal Block
Compressor Crankcase Heaters
Each compressor is equipped with a crankcase heater and is controlled by a 600 volt auxiliary switch on the compressor contactor. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor starts.
When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.
When power has been “Off” for an extended period, allow the crankcase heater to operate a minimum of 8 hours before starting the unit. Compressor crankcase heaters can be energized by supplying 115V power to the shore power plug (9J1) installed near the chiller control panel.
Low Ambient Damper Adjustment (Factory or Field Installed)
A damper is factory installed over the lead condenser fan for each refrigeration circuit. Refer to the appropriate unit illustrated in Figure 22 for the damper locations.
The UCM has a factory default setpoint of 90°F. This setpoint can be adjusted using the Human Interface programming procedures.
Inspect the damper blades for proper alignment and operation. Dampers should be in the closed position during the “Off” cycle. If adjustment is required;
1. At the Human Interface, program the actuator for 0% on circuit #1 and/or circuit #2. (The output signal will go to 0.0 VDC.)
72 CSRA-SVX02A-EN
Page 73
System Start-Up
2. Loosen the damper shaft “Locking” set screws on the actuator.
3. Firmly hold the damper blades in the closed position.
4. Tighten the “Locking” set screws.
To check damper operation, program the actuator for 100% on circuit #1 and/or circuit #2. (The output signal will go to 10 VDC and the damper will drive to the full open position.
Final System Setup
After completing all of the checkout and start-up procedures outlined in the previous sections (i.e., operating the unit in each of its Modes through all available stages of cooling), perform these final checks before leaving the unit:
[ ] Close the disconnect switch or circuit protector switch that provides the supply power to the unit's circuit breaker (1CB1).
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
[ ] Turn the solution pump control circuit breaker handle to the “Off” position.
[ ] At the Human Interface Module, press the “SETUP” key. The LCD screen will display various preset “parameters of operation” based on the unit type, size, and the installed options. Compare the factory preset information to the specified application requirements. If adjustments are required, follow the step-by-step instructions provided in the appropriate CGAF-PTG manual
[ ] Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel.
[ ] Verify that the Remote panel “System” selection switch, “Fan” selection switch, and “Zone Temperature” settings for comfort systems are correct.
[ ] Inspect the unit for misplaced tools, hardware, and debris.
[ ] Turn the solution pump control circuit disconnect switch to the “On” position.
[ ] Press the “AUTO” key at the Human Interface Module to begin system operation. The system will start automatically once a request for solution cooling has been initiated.
[ ] Verify that all exterior panels including the control panel doors and condenser grilles are secured in place.
CSRA-SVX02A-EN 73
Page 74
System Start-Up
Refrigerant Circuit #1
Refrigerant Circuit #2
Current
Ambient
Compr.
Suct.
Disch.
Liquid
Super-
Sub-
Compr.
Suct.
Disch.
Liquid
Super-
Sub-
Temp.
Oil
Press.
Press.
Press.
heat
cool.
Oil
Press.
Press.
Press.
heat
cool.
Date
(F)
Level
(Psig)
(Psig)
(Psig)
(F)
(F)
Level
(Psig)
(Psig)
(Psig)
(F)
(F)
Note:
Check and record the data requested above each month during the cooling season with the unit running.
Table 12 — Sample Operator’s Maintenance Log
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
- ok - ok
- low - low
74 CSRA-SVX02A-EN
Page 75
Service & Maintenance
Compressor Operational Sounds
Because of the scroll compressor design, it emits a higher frequency tone (sound) than a reciprocating compressor. It is designed to accommodate liquids, both oil and refrigerant, without causing compressor damage. The following discussion describes some of the operational sounds that differentiate it from those typically associated with a reciprocating compressor. These sounds do not affect the operation or reliability of the compressor.
At Shutdown:
When a Scroll compressor shuts down, the gas within the scroll expands and causes momentary reverse rotation until the discharge check valve closes. This results in a “flutter” type sound.
At Low Ambient Start-Up:
When the compressor starts up under low ambient conditions, the initial flow rate of the compressor is low due to the low condensing pressure. This causes a low differential across the thermal expansion valve that limits its capacity. Under these conditions, it is not unusual to hear the compressor rattle until the suction pressure climbs and the flow rate increases.
Scroll Compressor Replacement
Table 13 lists the specific compressor electrical data and the circuit breaker operating ranges.
The compressor manifold system was purposely designed to provide proper oil return to each compressors. The refrigerant manifolded system must not be modified in any way.
Note: Altering the manifold piping may cause oil return problems and compressor failure.
Should a compressor replacement become necessary and a suction line filter drier is to be installed, install it a minimum of 18 inches upstream of the oil separator tee. Refer to the illustration in Figure 25.
Anytime a compressor is replaced, the oil for each compressor within the manifolded set must be replaced.
The scroll compressor uses Trane OIL-42 without substitution. The appropriate oil charge for a 9 and 10 Ton scroll compressor is 8.5 pints. For a 14 and 15 Ton scroll compressor, use 13.8 pints.
CSRA-SVX02A-EN 75
Page 76
Service & Maintenance
Important: Environmental scientists have found evidence that refrigerant
emissions contribute to depletion of ozone in the upper atmosphere and can increase global warming. Trane encourages every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC and HFC refrigerant to the atmosphere that can result from installation, operation, routine maintenance, or major service on this equipment. Only technicians with EPA certification should be allowed to handle CFC, HCFC or HFC refrigerants. Compliance or certification to other local or state codes may also be required when handling refrigerants. Always act in a responsible manner to conserve refrigerants.
Refer to general service bulletin MSCU-SB-1 (latest edition).
Figure 25 — Suction Line Filter/Drier Installation
76 CSRA-SVX02A-EN
Page 77
Service & Maintenance
Table 13 — Compressor Circuit Breaker Data
Unit Size Number of
Compressors
C25 1, 1 10, 15 460 17.1, 25.4 117, 178 20.8, 29.5 23.9, 33.9
C40 4 9 460 17.2 117 18.9 21.7
C60 4 15 460 25.4 178 30.7 35.3
Compressor
Capacities
Rated
Voltage
Compressor
RLA
Compressor
LRA
Must Hold
(Amps)
Must Trip
(Amps)
Fuse Replacement Data
Table 14 lists the replacement fuses for the control circuit, compressors, and condenser fans.
Table 14 — Fuse Replacement Data
Fuse Replacement Table
Condenser Fan Fuse
Time Delay
Control Power Fuse 1F7 Class K5 6.25 Amp
Compressor Protection Fuse 1F44 & 1F45 Type MTH 6 Amp
Transformer Protection Fuse 1F72 Thru 1F74 Type FLQ 15 Amp
Compressor Crankcase
Heater Time Delay Fuse
1F1 Thru 1F6 Class RK5 15A
9F1, 9F2 Class CC 7.5 Amp
Evaporator Heat Tape
9F4 Class CC 5 Amp
Time Delay Fuse
25T Shorepower Fuse
9F3 Class CC 7 Amp
Time Delay
40T Shorepower Fuse
9F3 Class CC 10 Amp
Time Delay
60T Shorepower Fuse
9F3 Class CC 12 Amp
Time delay
CSRA-SVX02A-EN 77
Page 78
Unit
Size
Number
of
Coils
Service & Maintenance
Monthly Maintenance
Before completing the following checks, turn all system control circuit switches to the “Off” position.
“Open” the main power disconnect switches for the Condensing Unit and all system support equipment. “lock” the disconnect switches in the “Off” position before removing any access panels.
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Table 15 — Condenser Coil Data
Coil Fin
Configuration
WARNING
Tube
Diameter
Coil
Rows
Fins
per
Foot
Coil Size
(Inches)
Subcooler
Size
(Inches)
Tube Type
C25 2 Slit Fin 0.375” 3 144 45 x 71
35 x 71
C40 2 Slit Fin 0.375” 3 144 56 x 70 9 x 70 Smooth
C60 2 Slit Fin 0.375” 4 144 57 x 96 9 x 96 Smooth
Coil Cleaning
Regular coil maintenance, including annual cleaning, enhances the unit's operating efficiency by minimizing:
• compressor head pressure and amperage draw; evaporator water carryover; fan brake horsepower, due to increase static pressure losses; airflow reduction.
At least once each year, or more often if the unit is located in a “dirty” environment, clean the evaporator and condenser coils using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-up type or a high-pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX A.C.”, “OAKITE 161", “OAKITE 166" and “COILOX”. If the detergent selected is strongly alkaline (ph value exceeds 8.5), add an inhibitor.
1. Remove enough panels from the unit to gain access to the coil.
14 x 71 Smooth
78 CSRA-SVX02A-EN
Page 79
Service & Maintenance
2. Protect all electrical devices such as motors and controllers from any over spray.
3. Straighten any bent coil fins with a fin comb.
4. Mix the detergent with water according to the manufacturer's instructions. If desired, heat the solution to 150°F maximum to improve its cleansing capability.
WARNING
Hazardous Pressures!
Coils contain refrigerant under pressure. When cleaning coils, maintain coil cleaning solution temperature under 150 0 F to avoid excessive pressure in the coil. Failure to follow these safety precautions could result in coil bursting, w hich could result in death or serious injury.
5. Pour the cleaning solution into the sprayer. If a high-pressure sprayer is used:
• do not allow sprayer pressure to exceed 600 psi.
• the minimum nozzle spray angle is 15 degrees.
• maintain a minimum clearance of 6" between the sprayer nozzle and the coil.
• spray the solution perpendicular (at 90 degrees) to the coil face.
6. Spray the leaving-airflow side of the coil first; then spray the opposite side of the coil. Allow the cleaning solution to stand on the coil for five minutes.
7. Rinse both sides of the coil with cool, clean water.
8. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7.
9. Reinstall all of the components and panels removed in Step 1 and any protective covers installed in Step 2.
10.Restore the unit to it's operational status and check system operation.
System operation
[ ] Close the main power disconnect switch for the unit and all system support equipment. Turn all system control circuit switches to the “On” position.
WARNING
Rotating Components!
Disconnect all electric pow er, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the pow er can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
CSRA-SVX02A-EN 79
Page 80
Service & Maintenance
Make sure all personnel are standing clear of the unit before proceeding. The system components will start when the power is applied.
[ ] With the unit running, check and record the:
• ambient temperature;
• compressor oil level (each circuit);
• compressor suction and discharge pressures (each circuit);
• superheat and Subcooling (each circuit);
Record this data on an “operator's maintenance log” similar to the one illustrated in the “Final Setup” section of this manual. If the operating pressures indicate a refrigerant shortage, measure the system Superheat and system Subcooling. For guidelines, refer to the “System Start-Up” section.
Environmental scientists have found evidence that refrigerant emissions contribute to depletion of ozone in the upper atmosphere and can increase global warming. Trane encourages every effort to eliminate, if possible, or vigorously reduce the emission of CFC, HCFC and HFC refrigerant to the atmosphere that can result from installation, operation, routine maintenance, or major service on this equipment. Only technicians with EPA certification should be allowed to handle CFC, HCFC or HFC refrigerants. Compliance or certification to other local or state codes may also be required when handling refrigerants. Always act in a responsible manner to conserve refrigerants.
Refer to general service bulletin MSCU-SB-1 (latest edition).
Annual Maintenance
[ ] Perform all weekly and monthly maintenance procedures.
[ ] Have a qualified service technician check the setting and function of each control and inspect the condition of and replace compressor and control contactors if needed.
[ ] If chiller is not piped to drain facilities, make sure drain is clear to carry away system water.
[ ] Drain water from evaporator and associated piping systems. Inspect all piping components for leakage, damage, etc. Clean out any in-line water strainers.
[ ] Clean and repaint any corroded surface.
[ ] Check low ambient dampers for proper operation.
[ ] Clean condenser coils. Refer to “Coil Cleaning”.
80 CSRA-SVX02A-EN
Page 81
Service & Maintenance
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
[ ] Inspect the expansion valve sensing bulbs for cleanliness. Clean if required. Sensing bulbs must make good contact with suction lines and be properly insulated.
[ ] Clean condenser fans. Check fan assemblies for proper orifice clearance and for motor shaft mis-alignment, abnormal end-play or vibration and noise.
WARNING
Rotating Components!
Disconnect all electric pow er, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the pow er can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
CSRA-SVX02A-EN 81
Page 82
Service & Maintenance
(2) Unit Serial Number:
(3) Unit “DL” Number (“design special” units only):
Final Process
For future reference, you may find it helpful to record the unit data requested below in the blanks provided.
(1) Complete Unit Model Number:
(4) Wiring Diagram Numbers (from unit control panel):
— schematic(s)
— connection(s)
CSRA-SVX02A-EN 82
Page 83
Trane An American Standard Company www.trane.com
Aftermarket Business Unit 3600 Pammel Creek Road La Crosse, WI 54601
Literature Order Number CSRA-SVX02A-EN
File Number SV-CAP-Chillersource-CSRA-SVX02A-EN-0502
Supersedes New
Stocking Location La Crosse
Trane has a policy of continuous product data and product improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this bulletin.
Loading...