Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
WARNING
if not avoided, could result in death or serious injury.
CAUTION
not avoided, may result in minor or moderate injury. It may also be
used to alert against unsafe practices.
CAUTION
property-damage-only accidents.
-
Indicates a potentially hazardous situation which,
-
Indicates a potentially hazardous situation which, if
–
Indicates a situation that may result in equipment or
Literature History
CSRA-SVX01A-EN (April 2002)
Original issue of manual. Describes the Installation, Operation and Maintenance procedures for the unit.
Reference: The following manual is referenced throughout the manual and
provide useful information for installation, operation, and maintenance.
• CGA-IOM-4 (non-rental CGA chiller)
Installation Checklist
An Installation Checklist is provided at the end of the “Installation” section of
this manual. Use the checklist to verify that all necessary installation procedures have been completed. Do not use the checklist as a substitute for
reading the detailed information contained in the manual. Read the entire
manual before beginning installation procedures.
Unit Description
10 and 15 ton model CGA air-cooled Cold Generators are designed for outdoor installation with a vertical air discharge. Each refrigerant circuit is provided with an operating charge of refrigerant and refrigerant oil, a filter drier,
sight gas/moisture indicator and thermostatic expansion valve. All units are
dehydrated, leak tested, charged and tested for proper control operation
before shipment. Each unit is provided with an appropriately sized close
coupled hydronic pump mounted to a common base with the Cold Generator. Piping is provided to the inlet of the pump, pump to inlet of the Cold Generator, and the Cold Generator outlet. All necessary pressure gages, water
temperature gages, flow switches, and valves are mounted and ready for
operation.
4CSRA-SVX01A-EN
Page 5
General
Information
An access panel(s) provides access to the compressor section(s), and a
removable cover allows access to the control box. A unit circuit breaker
enclosure is also provided with 100 feet of power cord for single power supply hook up to customer provided disconnect box. A separate circuit breaker/
control panel enclosure is provided for the pump.
A bag containing the installation/operation/maintenance manual and the unit
wiring diagrams ships inside the unit control box. Be sure to read this literature before installing and operating the unit. Refer to Figures 2 and 3 for circuit breaker enclosure locations.
Unit Inspection
When the unit is delivered to the job site, verify that the correct unit has been
shipped by comparing the information on the unit nameplate with ordering,
submittal and shipping information. Refer to “Nameplates”.
Inspect the unit - inside and out - for damage. Rotate the condenser fan(s) to
ensure they turn freely. Report any apparent damage or material shortage to
the carrier and ChillerSource; make a “unit damage or shortage” notation on
the carrier’s delivery receipt. Specify the extent and type of damage found,
and notify ChillerSource. Do not proceed with installation of a damaged unit
without ChillerSource approval (800-755-5115).
Inspection Checklist
To protect against loss due to damage incurred in transit, complete the following checklist upon receipt of the unit:
[ ] Inspect individual pieces of the shipment before accepting the unit. Check
for obvious damage to the unit or packing material.
[ ] Check the unit for concealed damage before it is stored and as soon as
possible after delivery. Concealed damage must be reported within 15 days.
[ ] If concealed damage is discovered, stop unpacking the shipment. Do not
remove damaged material from the receiving location. Take photos of the
damage, if possible. The owner must provide reasonable evidence that the
damage did not occur after delivery.
[ ] Notify the carrier’s terminal of damage immediately by phone and by mail.
Request an immediate joint inspection of the damage by the carrier and the
consignee.
[ ] Notify the Trane sales representative and arrange for repair. Do not repair
the unit, however, until damage is inspected by the carrier’s representative.
CSRA-SVX01A-EN5
Page 6
General
Information
Nameplates
The nameplates on these machines provide valuable information pertaining
to the identification of the unit and its components. Be sure to provide all pertinent nameplate data when ordering parts or literature, and when making
other inquiries.
Unit Nameplates
The chiller unit nameplate is mounted on the end of the unit on the compressor access panel. This nameplate (shown in Figure 1b) specifies unit model
number, serial number, electrical characteristics, heat tape power requirements and refrigerant charge information.
Unit Model Number Description
All standard Trane products are identified by a multiple character model
number that precisely identifies a particular type of unit. An explanation of
the alphanumeric identification codes used for chiller units is provided on
this page. Its use will enable the owner/operator, installing contractors, and
service engineers to define the operation, components and options for any
specific unit. See Figure 1a.
6CSRA-SVX01A-EN
Page 7
General
Information
Figure 1a — Model Number Description
CSRA-SVX01A-EN7
Page 8
General
Information
Figure 1 b — Unit Nameplate
8CSRA-SVX01A-EN
Page 9
Installation
Complete the “Installation Checklist” during installation to verify completion
of all recommended procedures before unit start-up.
Unit Assembly Dimensions and Weights
The 10 and 15 ton assembly dimensions and weights are provided in Figure
2 and 3 and Table 1.
Handling
Each assembly is mounted on an assembly base with forklift tube slots easily accessible for wide and narrow forklift trucks with suitable capacity. At
either end of the base is attached a tow-bar when additional pulling and
pushing maneuvering is required. There is also an overhead lifting frame
attached to the assembly base for overhead lifting without the need for additional spreader bars.
Drainage
Locate the unit so that the entire assembly can be allowed to drain during
unit shutdown and repair.
Rigging
Use a forklift, crane or helicopter of suitable capacity to move the unit to its
mounting.
Table 1: Unit Weights
Model No.TonsShipping
Weight (lbs)
CSRA010FAF010 T38003820
CSRA015FAF015 T40304050
Operational
Weight (lbs)
WARNING
Heavy Objects!
Do not use cables (chains or slings) except as shown. Each of the
cables (chains or slings) used to lift the unit must be capable of
supporting the entire weight of the unit. Lifting cables (chains or
slings) may not be of the same length. Adjust as necessary for even
unit lift. Other lifting arrangements may cause equipment or propertyonly damage. Failure to properly lift unit may result in death or serious
injury. See details below.
Rig the unit using either belt or cable slings. Fasten the slings to the unit at
the four holes provided in the lifting frame. The point at which the slings meet
at the lifting hook must be at least 6 feet above the unit. Test-lift the unit to
ensure proper balance and rigging.
CSRA-SVX01A-EN9
Page 10
Installation
Figure 2 — 10 Ton Details
Note: Both the water inlet and outlet connections are 2 1/2” Victaulic
10CSRA-SVX01A-EN
Page 11
Installation
Figure 3 — 15 Ton Details
Note: Both the water inlet and outlet connections are 2 1/2” Victaulic
CSRA-SVX01A-EN11
Page 12
Installation
Location and Clearance Requirements
Select an installation site where air flow upward, unobstructed, through the
condenser coil and away from the fan discharge. Protect the unit’s condenser intakes from crosswinds exceeding 5 m.p.h. Position the unit above
the snowline, and above the path of any windblown debris. Refer to Figures
2 and 3 for clearances.
CAUTION
Compressor Damage!
Installation of unit under an overhang will cause obstruction of the
vertical air discharge, leading to pre-mature equipment failure.
If the unit is installed in a well or pit, the height of the pit walls must not
exceed the height of the unit; the normal condenser air clearances must be
doubled as well. In those applications as where multiple units are installed,
the minimum distance between each unit is 6 feet, (entire perimeter).
Unit Isolation
Mounting methods that will minimize sound and vibration problems are:
1. Mount the assembly on a level surface, preferably an isolated concrete
surface that completely supports the entire perimeter of the assembly
base.
2. An optional neoprene pad can be installed between the assembly base
and the mounting surface if assembly must be located in critical sound
and vibration locations.
Unit Water Piping
General Piping Recommendations
Thoroughly flush all water supply piping before making the final piping connections to the unit.
CAUTION
Pump Damage!
If using an acidic commercial flushing solution, construct a temporary
bypass around the pump and unit. Failure to do so may lead to
equipment damage.
12CSRA-SVX01A-EN
Page 13
Installation
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in an Air-Cooled Cold
Generator may result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment
specialist be engaged to determine what water treatment, if any, is
required. Trane assumes no responsibility for equipment failures
which result from untreated or improperly treated water, or saline or
brackish water.
Evaporator Water Piping
The unit’s water connection sizes and locations are shown in
Figure 13.
CAUTION
Component Damage!
Evaporator pressure should not exceed 150 psig (i.e., maximum
working pressure). Failure to do so may lead to equipment damage.
To prevent unit or pump damage, do NOT reverse system water piping connections to the unit or pump; water entering the evaporator is pre-piped to
the discharge of the pump. If the pump is not required, open bypass valve
and close inlet and discharge valves on pump. “Water Inlet” to the evaporator must enter on inlet connection to pump. Leaving water must exit the
evaporator through the designated “Water Outlet” connection.
Flexible Hose and Hard Pipe Installation
General
Use the procedure described below to ensure the proper installation of flexible hose provided as part of a ChillerSource rental. It is critical that this procedure is followed to minimize premature or catastrophic failure of this hose.
CAUTION
Hose Damage!
Hose must never be pressurized over 150 psi. If higher pressures are
required, “hard” suction pipe must be utilized. Failure to do so may
lead to hose damage.
CAUTION
Hose Damage!
Hose must always be used in pressurized application. If a negative
pressure application is required, “hard” suction pipe must be utilized.
Failure to do so may lead to hose collapse and total system failure.
CSRA-SVX01A-EN13
Page 14
Installation
Flexible Hose Guidelines
WARNING
Hose Failure!
Failure to comply with installation instructions that follow may result in
death or serious injury or equipment damage.
• Do not support the hose ONLY by its couplings; support over half of
the hose's length by ground or other supporting surface otherwise
coupling clamps may fail.
• Do not run hose vertically more than 7 feet otherwise coupling
clamps may fail.
• Do not cut hose to “custom” fit pieces-this will affect the integrity of
the hose.
• Bleed all air from the system prior to pressurizing hose to avoid couplings separating from the hose.
• Install elbows for a smooth hose transition on all vertical hose installations, see Figure 4.
• Never pressurize hose above 150 psi.
Figure 4 — Correct Vertical Hose Installation
14CSRA-SVX01A-EN
Page 15
Installation
Dixon Coupling
• The Dixon coupling (See Figure 5), bolts are to be torqued prior to
charging the hose with water to 40 ft-lbs. DO NOT EXCEED 40 ft-lbs.
(The torque must be applied evenly between the bolts to ensure a
consistent gap on each side of the coupling. Some pinching of the
excess hose in the gap area is considered normal and will not create
a leak or premature failure.)
• Continually monitor and retighten, if necessary, on monthly inspection
intervals.
Figure 5 — Dixon Coupling
Horizontal Hose Installation
The following Figures illustrate the correct and incorrect methods for installing hose in a horizontal hookup application.
Figure 6 — Correct Horizontal Hose Installation
90° Elbow
In this configuration either a 45° or 90° elbow can be installed. This elbow
prevents stretching and crimping of the hose at the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle
to minimize the crimping of the hose at the ground or supporting surfaces.
CSRA-SVX01A-EN15
Page 16
Installation
Figure 7 — Incorrect Horizontal Hose Installation
In this configuration elbows are not installed. This causes the top of the hose
to be in tension, which stretches the hose out of the coupling; and the bottom of the hose to be in compression, which causes it to crimp. It also
causes the hose to crimp at the ground.
Vertical Hose Installation
The following figures illustrate the correct and incorrect methods for installing hose in a vertical hookup application.
Figure 8 — Correct Vertical Hose Installation
In this configuration, the hose is installed with an elevation less than 7 feet
off the ground. A 45° elbow is installed to reduce the stress in the hose coupling connection. This elbow also directs the hose to the ground at an appropriate angle to minimize the crimping of the hose at the ground or supporting
surface.
16CSRA-SVX01A-EN
Page 17
Installation
Figure 9 — Incorrect Vertical Hose Installation
Coupling
In this configuration the hose is installed without an elbow and with an elevation greater than 7 feet off the ground. This creates excessive stress at the
hose coupling connection, causing the hose to stretch and separate from the
coupling. It also causes the hose to crimp at the ground.
Couplings
Horizontal/Vertical Installation
The following figures illustrate the correct and incorrect methods for installing
hose in a horizontal and vertical combination application.
Figure 12 illustrates a correct horizontal hose installation where there is a
section of unsupported hose. The length of unsupported hose should be less
than 7 feet. Also, the hose must be adequately supported by having more
than half its total length on the ground.
18CSRA-SVX01A-EN
Page 19
Installation
Hard Pipe Guidelines
Certain installations may require the use of hard pipe (steel or PVC). Hard
pipe is typically recommended for (1) INDOOR INSTALLATIONS, (2) semipermanent installations (three months or more) and/or (3) installations with
space limitations.
When installing hard pipe:
• construct and install the piping according to local and national codes
• isolate and support the piping as required to prevent stress on the unit
and vibration to building piping
If there are any questions regarding how to install water piping, contact a
ChillerSource Technical Service Advisor in Charlotte, NC (800-755-5115).
Exceptions
The ChillerSource Technical Service Advisor in Charlotte, NC
(800-755-5115), must authorize any exceptions to the guidelines established
in this bulletin in writing.
Material Disposition
In the event the hose fails or leaks, call the ChillerSource Technical Service
Advisor in Charlotte, NC (800-755-5115); tag the hose “BAD” and place it
back in the shipping box.
CSRA-SVX01A-EN19
Page 20
Installation
Evaporator Drain
The 1/2 inch NPT drain plug is located in the leaving water tee near the bottom of the evaporator of the 15 ton (CSRA015FAF0). The 10 ton
(CSRA010FAF0) features a drain valve rather than a plug. See “Extended
Unit Shutdown/Winterization” on page 41 for draining instructions.
Note: If the system has been drained for shutdown, do not energize heat
tapes.
Figure 13 — 10 and 15 Ton Water Inlet/Outlet Connections
Note: The water inlet and outlet connections are both 2 1/2” Victaulic.
10 Ton
Important: When installing water pipes, be certain to route them away from
the compressor access panels to allow for compressor servicing or replacement.
20CSRA-SVX01A-EN
Page 21
Installation
Freeze Protection
General
Use the procedure described below to ensure that the chilled water system
is adequately protected from freeze-up in those applications where the unit
remains operational at subfreezing ambient temperatures.
1. Install chilled water piping heat tape along with a fused disconnect
switch, refer to the instructions outlined under “Heat Tape Installation”.
Ensure that all exposed piping is adequately protected.
Note: Heat tape is factory-installed on the unit evaporator. This heat tape
will protect the evaporator from freeze-up at ambient temperatures down to 20 ° F when used in conjunction with properly applied heat tape on the fieldinstalled water lines. Heat tape power draw is 84 watts on 10 ton units and
126 watts on 15 ton units.
2. Freeze-proof the chilled water system by adding a non- freezing, lowtemperature, heat-transfer fluid to the chilled water system. Provide protection against ice formation at 10° F below the lowest expected ambient
temperature.
Note: Use of an ethylene glycol-type antifreeze reduces unit cooling capacity; this condition must be accounted for during total system design. (Refer to
Figure 16, “Ethylene Glycol Adjustment Factor” on page 36).
Heat Tape Installation
Install heat tape on all water piping that may be exposed to freezing temperatures. Be sure to use heat tape that is recommended for low-temperature
applications; it should be rated at 110/120 volts, thermostatically-controlled,
and dissipate 6 to 7 watts per linear foot.
Heat tape selection should be based on the lowest expected ambient temperature-including any wind chill factor. For those tapes not automatically
(i.e., thermostatically) controlled, be sure to install an accessory thermostat.
Refer to Tables 2 and 3 for typical heat tape characteristics.
To install the heat tape properly, follow the instructions provided by the heat
tape manufacturer. If none are provided, use the recommendations outlined
below:
1. Wrap the heat tape around the pipe-or apply it straight along the pipe-as
necessary to provide the required protection. (See Tables 2 and 3).
2. Use friction tape to secure the heat tape to the water pipe.
3. Place the thermostat tightly against-and parallel to the water pipe. then
tape it into place at both ends. Be sure to install the thermostat on the
most exposed (i.e. coldest) portion of the pipe.
CSRA-SVX01A-EN21
Page 22
Installation
4 Wrap the pipe with weatherproof tape. On vertical pipe runs, start the
wrap at the bottom and work up as shown in Figure 14. Be sure to overlap the tape so that it will shed moisture.
Note: If additional protection is required, insulate the pipe with fiberglass
wrap before installing the outer wrap.
CAUTION
Electrical Failure!
Do not install fiberglass insulation under the outer wrap when using
non-thermostatically-controlled heat tape. Failure to do so may result
in unit damage.
If freezing is a potential problem, all exposed piping, pumps and other components must be similarly protected with heat tape and insulation.
Table 2: Heat Tape Selection Table for Proper Pipe Protection with Fiberglass and Outer Wrap
(Tape installed straight along pipe)*
Method of
Wrapping
3/8”1/2”3/4”1”1-1/4”1-1/2”2”3”4”6”
Tape
Required per
Foot of Pipe
Protection
Down to (°F)
* All values calculated at 0 MPH wind, metallic pipe. Fiberglass wrap should not be used with non-automatic models unless used in conjunction with properly installed thermostat.
Table 3: Heat Tape Selection Table for Proper Pipe Protection with Fiberglass and Outer Wrap
(Tape installed spiralled around pipe, 3 turns per foot)*
Method of
Wrapping
1’1’1’1’1’1’1’1’1’1’
-60-41-30-19-12-60+9+14+26
3/8”1/2”3/4”1”1-1/4”1-1/2”2”3”4”6”
Nominal Copper Pipe Size
Nominal Copper Pipe Size
Tape
Required per
Foot of Pipe
Protection
Down to (°F)
* All values calculated at 0 MPH wind, metallic pipe. Fiberglass wrap should not be used with non-automatic models unless used in conjunction with properly installed thermostat.
NR = Not Recommended
CSRA-SVX01A-EN23
NRNR1’ 6”1’ 8”1’ 10”2’ 1”2’ 4”2’ 11”3’ 11”5’ 0”
NRNR-60-55-51-50-45-41-37-35
Page 24
Installation
Amps
Qty.RLALRA
Amps
Circuit
Maximum
Fuse Size
Range
Allowable Voltage
Circuit
Minimum
Ampacity
Unit
Range
Voltage
Allowable
Electrical
Characteristics
Basic Unit CharacteristicsCompressor Motor
Unit
Electrical
HPFLA
.
Characteristics
Model
Number
CSRA015FAF0460/60/3414-50637.450213.579
Table 4: Electrical Data for 10 and 15 Ton Units
24CSRA-SVX01A-EN
CSRA010FAF0460/60/3414-5062935210.071
Table 4: Continued
Amps
112.7133.8115/60/3104-1262
Outdoor Fan MotorPump MotorShore Power
Qty.HPFLAQty
20.51.6133.8115/60/3104-1262.4
NEC 440-33.
Notes:
1. Minimum circuit ampacity is 125% of the largest compressor RLA (see Table 4) plus 100% of the second compressor RLA plus the sum of the condenser fan FLAs per
2. Maximum fuse size is 225% of the largest compressor RLA plus 100% of the second compressor plus the sum of the condenser fan FLAs, per NEC 440-22.
Page 25
Installation
Table 5: Minimum Starting Ambient Temperatures for CGA Units
Low Ambient Units
No HGBP
10 Ton0
15 Ton0
Notes:
1. Minimum starting ambients in degrees F, based on unit at minimum
step of unloading and 5 m.p.h. wind across condenser.
Table 6: Control Settings and Time Delays for CGA Units
Control
Description
High Pressure CutoutHPC01, HPC02400 ± 10 psig250 ± 15 psig
Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
All wiring must comply with National Electric Code (NEC) and state and local
requirements. Outside the United States, the national and/or local electrical
requirements of other countries shall apply. The installer must provide properly sized system interconnecting and power supply wiring with appropriate
fused disconnect switches. Type and locations of disconnects must comply
with all applicable codes.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors.
Failure to use copper conductors may result in equipment damage.
Figures 2 and 3 show the locations of the unit electrical access openings.
Table 4 provides minimum circuit ampacity, recommended fuse sizes, and
motor electrical data.
Shore Power Supply (115V)
The shore power male receptacle located above the unit circuit breaker
enclosure (refer to Figure 2 and 3) is provided for customer convenience to
supply power (refer to Table 4 for allowable voltage range) to compressor
crankcase heaters and factory supplied evaporator heat tape. The crankcase heaters should operate at least 8 hours before the compressors are
allowed to start.
Chiller Source Unit Power Supply
Refer to the unit wiring schematic pasted to the control panel cover of the
cold generator. The installer must provide a power supply of proper voltage.
Connect power cable provided on the unit to a properly sized fused disconnect switch required by local codes. Provide proper equipment grounds
where required.
Heat Tape for Unit Evaporator
The evaporator is insulated from ambient air, and protected from freezing by
thermostatically controlled heat tape(s). The evaporator heat tape circuit is
energized when shore power (115 V) is connected as well as when the supply power (460V) to the unit is connected. Whenever the thermostat senses
40° F +/- 6° F, it closes, energizing the heat tape(s).
26CSRA-SVX01A-EN
Page 27
Installation
Checklist
Complete this checklist as the unit is installed to verify that all recommended
procedures are accomplished before the unit is started. This checklist does
not replace the detailed instructions given in the “Installation” section of this
manual! Read the entire section carefully to become familiar with installation
procedures before installing the unit.
Receiving
[ ] Verify that unit nameplate data corresponds with ordering information.
[ ] Inspect unit for shipping damages and material shortages; report any
damages or shortages found to ChillerSource, 800-755-5115.
Unit Location and Mounting
[ ] Inspect unit installation location for adequate ventilation.
[ ] Provide drainage facilities for evaporator water.
[ ] Remove and discard any shipping materials (e.g., cartons, crates, etc.)
[ ] Inspect to determine that service access clearances are adequate.
[ ] Install optional isolation neoprene pad between base and mounting surface.
[ ] Level the unit.
Evaporator Piping
[ ] Flush and clean all chilled water piping.
CAUTION
Pump Damage!
If using an acidic commercial flushing solution, construct a temporary
bypass around the pump and unit. Failure to do so may lead to
equipment damage.
CSRA-SVX01A-EN27
Page 28
Installation
Checklist
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in an Air-Cooled Cold
Generator may result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment
specialist be engaged to determine what water treatment, if any, is
required. Trane assumes no responsibility for equipment failures
which result from untreated or improperly treated water, or saline or
brackish water.
[ ] Make water connections.
[ ] Vent chilled water system at high points in system piping.
[ ] Apply heat tape and insulation as necessary to protect all exposed field
installed piping from freeze-up.
Electrical Wiring
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
28CSRA-SVX01A-EN
Page 29
Pre-Start
Procedures
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors.
Failure to use copper conductors may result in equipment damage.
[ ] Connect unit power supply cord to fused disconnect switch.
[ ] Connect power supply wiring, along with a fused disconnect switch, to
auxiliary heat tape installed on system water piping.
Pre-Start Checklist
Once the unit is installed, complete each step in the checklist that follows,
check off each step as it is completed. When all are accomplished, the unit is
ready for operation.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in
this section of the manual could result in exposure to electrical,
mechanical or other potential safety hazards. Always refer to the safety
warnings provided throughout this manual concerning these
procedures. When possible, disconnect all electrical power including
remote disconnects before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized.
When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained
in handling live electrical components perform these tasks. Failure to
follow all of the recommended safety warnings provided, could result
in death or serious injury.
Refer to unit schematics to check the number of disconnects required to deenergize the unit.
When electrically troubleshooting the compressor make sure electrical
power is NOT applied.
[ ] Inspect all wiring connections; electrical connections should be clean and
tight.
CAUTION
Compressor Damage!
Check tightness of all connections in the compressor power circuit
(disconnects, terminal block, contactors, compressor junction box
terminals, etc.). Failure to do so may result in over-heating at
connections and under voltage conditions at the compressor motor.
CSRA-SVX01A-EN29
Page 30
Pre-Start
Procedures
[ ] Check power supply voltage to the unit at the circuit breaker; the voltage
reading obtained must be within the voltage utilization range shown in Table
4. Also, voltage imbalance must not exceed 2%. (Refer to “Unit Voltage and
Amperage Checks”)
[ ] Check the condenser fan assemblies; the fan blades should rotate freely
in the fan orifice, and be securely attached to the fan shaft.
[ ] Disconnect power supply to shore power. Remove control circuit Fuse
(FU) from the main unit control panel; then energize the compressor crankcase heaters by closing the unit's circuit breaker. The crankcase heaters
should operate at least 8 hours before the compressors are allowed to start.
Note: To prevent compressor operation during this 8-hour interval, control
circuit fuse (FU) must be removed from the unit control panel.
CAUTION
Compressor Damage!
Compressor crankcase heaters must be energized at least 8 hours
before unit start-up. Failure to do so may result in compressor
mechanical damage.
[ ] Fill the chilled water (evaporator) circuit, leaving the system air vents
open. Close vents after filling.
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in an Air-Cooled Cold
Generator may result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment
specialist be engaged to determine what water treatment, if any, is
required. Trane assumes no responsibility for equipment failures
which result from untreated or improperly treated water, or saline or
brackish water.
[ ] Turn handle to “On” position on pump starter enclosure. Check the pump
rotation.The pump should start water circulating through the chilled water
system, inspect all piping connections for leaks and make any necessary
repairs.
[ ] Adjust the water flow rate through the chilled water circuit, and check the
water pressure drop through the evaporator. Refer to “Water System”.
[ ] Open the unit circuit breaker; then reinstall control circuit Fuse (FU) in the
unit control panel (i.e., provided the compressor crankcase heaters have
been energized at least 8 hours), and re-close the circuit breaker. Adjust the
flow switch (installed on the evaporator outlet piping) to provide proper operation.
30CSRA-SVX01A-EN
Page 31
Pre-Start
Procedures
Note: With the water pump operating, throttle the water flow to approxi-
mately 50 percent of the full flow rate. Following the manufacturer's instructions, adjust the flow switch contacts to open at this point. Use an ohmmeter
to verify opening and closure of the switch contacts.
[ ] Stop the chilled water pump.
[ ] Open all circuit breakers.
Unit Voltage and Amperage Checks
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
Electrical power to the unit must meet stringent requirements for the unit to
operate properly. Total voltage supply and voltage imbalance between
phases should be within the following tolerances.
Voltage Supply — 3-Phase Units Only
Measure each leg of supply voltage at all line voltage on circuit breaker.
Readings must fall within the voltage utilization range shown on the unit
nameplate. If voltage on any leg does not fall within tolerance, notify the
power company to correct this situation before operating the unit. Inadequate voltage to the unit will cause control components to malfunction and
shorten the life of electrical components and compressor motors.
CSRA-SVX01A-EN31
Page 32
Pre-Start
100
XV
–
V1V2V3++
V1V2V3,,
LineVoltages
=
VDVAV
453470467
++
100X463453
–
Procedures
Voltage Imbalance
Excessive voltage imbalance between phases in a three-phase system will
cause motors to overheat and eventually fail. Maximum allowable imbalance
is 2 percent. Voltage imbalance is defined as follows:
% Voltage Imbalance =
where (Avg. Voltage)
Example: If the three voltages measured at the line voltage side of the cir-
cuit breaker are 453 volts, 470 volts, and 467 volts, the average () would
be:
V
= Line voltage that deviates farthest from
---------------------------------------
-------------------------------=
A
3
= 463 volts
AVD
V
A
A
3
The percentage of imbalance is then:
----------------------------------------
=2.2%
463
The 2.2 percent imbalance that exists in the example above exceeds maximum allowable imbalance by 2.0 percent.
This much imbalance between phases can equal as much as 20 percent
current imbalance with a resulting increase in winding temperature that will
decrease compressor motor life.
Table 7: Chiller Evaporator Data
UnitWater*
Volume
gal.gpmgpm
10 Ton1.41236
15 Ton1.51854
* Includes water tubing provided by the factory, on the cold generator only.
Feet of Water = psi x 2.307
32CSRA-SVX01A-EN
Minimum
Flow Rate
Maximum
Flow Rate
Page 33
Pre-Start
Procedures
Water System: Water Flow Rates
Establish a balanced water flow through the evaporator. Flow rates should
fall between the minimum and maximum values indicated in Table 7. Evaporator water flow rates below the minimum acceptable values will result in a
stratified flow; this reduces heat transfer and causes either loss of expansion
valve control or repeated nuisance low pressure cutouts. Conversely, excessively high flow rates may cause erosion of components in the evaporator.
Pressure Drop Measurement
Measure the water pressure drop through the evaporator by closing the shutoff ball valve on the ¼” pipe connected to the inlet piping entering the evaporator and opening the shut-off ball valve on the ¼” pipe connected to the outlet piping leaving the evaporator. The pressure gage mounted on the ¼” pipe
will indicate the pressure leaving the evaporator. Close the leaving shut-off
valve and open the entering shut-off valve on the ¼” pipe assembly to record
the entering pressure to the evaporator. Take the difference of the two pressures to obtain the water pressure drop. The pressure drop obtained should
approximate those indicated by the pressure drop chart in Figure 15.
Note: The pressure drop curves shown in Figure 15 are calculated at the
unit water inlet and outlets. Be sure to account for any piping or fittings that
may create an additional pressure drop between the unit and the pressure
gauge locations.
CSRA-SVX01A-EN33
Page 34
Pre-Start
Procedures
Figure 15 — 10 and 15 Ton Evaporator Water Pressure Drop (English)
34CSRA-SVX01A-EN
Page 35
Pre-Start
∆
PH
O∆P
=
Procedures
Table 8: Normal Operating Pressures (Approximate)
10 Ton15 Ton
Ambient (F)Suction
Pressure
(psig)
455812856139
605916358174
756020459214
856123460244
956226661276
1056330162310
1156433963347
Discharge
Pressure
(psig)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Ethylene Glycol Adjustment Factor
The addition of ethylene glycol to the chilled water system reduces unit
capacity. To determine pressure drop of a glycol solution, obtain the pressure
drop adjustment factor from the chart in Figure 16 and multiply times the
pressure drop of water without glycol, i.e.;
Glycol x Adj. Factor
2
Notes:
1. Based on steady state conditions with 54° F entering water temperature (EWT)
and 44° F leaving water temperature (LWT).
2. An increase of 5° F in LWT while keeping the 10° F temperature drop will result in
an increase of approximately 6 psi in discharge pressure when compared to the
54° F EWT, the 44° F LWT given in Table 8.
3. Pressure at low ambients will not match this table if a head pressure control is
installed and operating.
CSRA-SVX01A-EN35
Page 36
Pre-Start
Procedures
Figure 16 — Performance Adjustments and Solution Freezing Points
(Ethylene Glycol in Evaporator)
36CSRA-SVX01A-EN
Page 37
Operation
Start-up Procedure
To properly start the unit, execute each step of the checklist that follows in
the sequence indicated; check off each step as it is completed. Do not start
the unit until the “Pre-Start Procedures” are complete. (Refer to Figure 17 for
the unit operating controls locations.)
[ ] Disconnect shore power cord if connected.
[ ] Position pump starter panel handle to the “Off” position.
[ ] Open the unit circuit breaker; then remove control circuit fuse (FU) from
the unit control panel. (This will prevent the compressors from energizing
when the disconnect switch is closed.)
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in
this section of the manual could result in exposure to electrical,
mechanical or other potential safety hazards. Always refer to the safety
warnings provided throughout this manual concerning these
procedures. When possible, disconnect all electrical power including
remote disconnects before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized.
When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained
in handling live electrical components perform these tasks. Failure to
follow all of the recommended safety warnings provided, could result
in death or serious injury.
Refer to unit schematics to check the number of disconnects required to deenergize the unit.
[ ] Position pump starter panel handle to the “On” position. If Chiller Source
pump not being used, leave in “Off” position. Close the fused disconnect
switch for the evaporator chilled water pump being used. Start the pump.
[ ] Close the circuit breaker for the chiller unit.
Note: The unit’s compressor crankcase heaters will energize when the disconnect switch is closed; these crankcase heaters must operate at least 8
hours before the compressors are allowed to start. The shore power supply
also energizes the crankcase heaters prior to 460V supply. Disconnect shore
power prior to 460 V supply to unit.
CSRA-SVX01A-EN37
Page 38
Operation
CAUTION
Compressor Damage!
Compressor crankcase heaters must be energized at least 8 hours
before unit start-up. Failure to do so may result in compressor
mechanical damage.
[ ] After the compressor crankcase heaters have operated a minimum of 8
hours, open the unit circuit breaker, reinstall control circuit fuse (FU) in the
unit control panel, and re-close the circuit breaker.
[ ] The factory-installed evaporator heat tape (HTTB) should be energized
whenever there is water in the unit evaporator. Additional heat tape supplied
in the field requiring its own fused disconnect box should be closed at this
time.
[ ] Reset any control that requires a manual reset.
[ ] Set the water temperature thermostat (WTT) as described on page 46.
Checking Operating Conditions
Once the unit has operated for at least 30 minutes and the system has stabilized, complete the following checklist to ensure proper unit operation.
[ ] Re-check evaporator water flow and pressure drop. These readings
should be stable at proper levels. Refer to “Water System”. If pressure differential drops off, clean all evaporator water supply strainers.
[ ] Measure unit suction and discharge pressures by installing pressure
gauges on the discharge and suction line access ports. Refer to Table 8 for
approximate normal operating pressures.
Note: Many application variables exist which can effect operating pressures;
these include ambient dry bulb temperature. as well as the installation of
such options as head pressure controls or hot gas bypass. Since these variables can give misleading results, do not use operating pressures as the
sole check of system operation.
[ ] Check compressor amp draw.
[ ] Check electrical power supply.
[ ] Check the liquid line sight glasses/moisture indicators for the presence of
moisture.
Note: Bubbles in the liquid line may indicate either a low refrigerant charge,
or excessive pressure drop in the liquid line. Such a restriction can often be
identified by a noticeable difference in line temperature on either side of the
restricted area. (Frost often forms on the outside of the liquid line at the point
of restriction, as well.) Bubbles are not necessarily a symptom of improper
system operation.
38CSRA-SVX01A-EN
Page 39
Operation
Important: A clear sight glass does not necessarily mean that the system is
sufficiently charged; be sure to consider system superheat, subcooling, and
unit operating pressures and ambient temperatures.
Proper unit refrigeration charge -per circuit- is indicated on the unit nameplate and also under “Refrigerant Charge Information” on page 39 of this
manual.
[ ] Measure system superheat.
Normal system superheat is 12 to 15 degrees F for each circuit at ARI conditions (54° entering water, 44° leaving water, and 95° ambient temperature). If
the superheat measured for either circuit does not fall within this range, alter
the setting of the superheat adjustment on the thermal expansion valve to
obtain the desired reading. Allow 15 to 30 minutes between adjustments for
the expansion valve to stabilize at each new setting.
[ ] Measure system subcooling.
Normal subcooling for each circuit is 12 to 22 degrees F at ARI conditions
(54° entering water, 44° leaving water, and 95° ambient temperature). If subcooling for either circuit is not in this range, check superheat for circuit and
adjust, if required. If superheat is normal but subcooling is not, contact a
qualified service technician.
[ ] If operating pressure, sight glass, superheat and subcooling readings
indicate refrigerant shortage, find and repair leaks and, gas-charge refrigerant into each circuit. Refrigerant shortage is indicated if operating pressures
are low and subcooling is also low.
Refrigerant Charge Information
The 10 ton units have 9 lbs. 8 oz. of refrigerant per circuit, and the 15 ton
units have 12 lbs. 7 oz. of refrigerant per circuit.
CAUTION
Equipment Damage!
Do not add refrigerant to unit when suction and discharge pressures
are low and subcooling is normal. Failure to follow all instructions
could result in equipment damage.
Add refrigerant vapor with the unit running by charging through the access
port on the suction line until operating pressures are normal.
CSRA-SVX01A-EN39
Page 40
Operation
CAUTION
Compressor Damage!
Do not allow liquid refrigerant to enter the suction line. Liquid charge
at the liquid line only. Failure to follow all instructions could result in
equipment damage.
[ ] If operating pressures indicated an overcharge, slowly (to minimize oil
loss) recover refrigerant at the liquid line service valve.
Important: Do NOT release refrigerant to the atmosphere! Refer to latest
version of the general service bulletin MSCU-SB-1.
CAUTION
Freezing Temperatures!
Do not allow liquid refrigerant to contact skin. If it does, treat the injury
similar to frostbite. Slowly warm the affected area with lukewarm water
and seek immediate medical attention. Direct contact with liquid
refrigerant may cause minor or moderate injury.
[ ] Be sure that all remote sensing bulbs are properly installed in bulb wells
with heat transfer compound. Remote bulb capillary tubes must be secured
(i.e., protected from vibration and abrasion) and undamaged.
[ ] Inspect the unit. Remove any debris, tools and hardware. Secure all exterior panels, including control and compressor access panels. Replace and
tighten all retaining screws.
Temporary Unit Shutdown and Restart (Not Servicing)
To shut down the unit for a short time:
1. Open the unit circuit breaker; then remove Control Circuit Fuse (FU) from
the main unit control panel. Once Control Circuit Fuse (FU) is removed,
re-close the unit disconnect switch. This will ensure that the compressor
2. Stop operation of the chilled water pump. Turn handle on pump starter
panel to “OFF”.
To restart the unit after a temporary shutdown:
1. Restart the chilled water pump, by turning handle on pump starter panel
to “ON” position.
2. Open the unit circuit breaker; then reinstall Control Circuit Fuse (FU) in
the main control panel. Once fuse (FU) is installed, close the unit circuit
breaker.
40CSRA-SVX01A-EN
Page 41
Operation
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Open unit disconnect switch before installing control circuit fuse (FU) in control panel.
The unit will now operate normally provided that: (1) the water temperature
thermostat (WTT) is calling for cooling, and (2) all system operating interlocks and safety circuits are satisfied.
Extended Unit Shutdown/Winterization
If the system is taken out of operation for long periods of time for any reason
(e.g., seasonal shutdown), use this procedure to prepare the system for
shutdown:
1. Check the refrigerant piping for leaks, fixing any that exist.
2. Service the chilled water pump and any air handling equipment according
to the manufacturer’s recommendations.
3. Open both electrical circuit breakers for the unit and chilled water pump;
lock both in the open position.
CAUTION
Compressor Damage!
Lock both unit and chilled water pump circuit breakers in open position
to prevent compressor or pump damage due to accidental start-up
while system is in “shutdown” condition. Failure to do so may result in
equipment damage.
Winterization: Close all evaporator water supply valves and drain the evaporator and water pump by removing the drain plug and opening the vent on
the entering water line just outside the unit. Re-install the drain plug. Since
the evaporator does not drain completely, add one quart of ethylene glycol
antifreeze to the remaining water through the vent or evaporator drain hole,
to keep the water from freezing, or refer to Table 7 and fill the evaporator with
antifreeze. Protect system to 10° F below the expected ambient temperature
and energize the evaporator heat tape(s) by closing the heat tape fused disconnect switch provided by the installer.
CSRA-SVX01A-EN41
Page 42
Operation
CAUTION
Evaporator Damage!
To prevent freeze damage to evaporator internal components, protect
with adequate strength antifreeze, and be certain to energize
evaporator heat tapes. Failure to do so may result in equipment
damage.
Note: If system has been drained for shutdown do not energize heat
tapes(s).
System Restart After Extended Shutdown
Use this procedure to prepare the system for restart after an extended shutdown:
1. Remove winterization antifreeze as it can reduce system capacity.
2. Verify that both the unit and the chilled water pump circuit breakers are
open; then remove control circuit Fuse (FU) from the unit control panel.
3. Close the unit circuit breakers to energize the compressor crankcase
heaters.
Note: The unit's compressor crankcase heaters will energize when the circuit breaker is closed; these crankcase heaters must operate at least 8
hours before the compressors are allowed to start. Disconnect shore power
prior to closing unit circuit breaker.
CAUTION
Compressor Damage!
Compressor crankcase heaters must be energized at least 8 hours
before unit start-up. Failure to do so may result in compressor
mechanical damage.
4. Fill the chilled water (i.e., evaporator) circuit; evaporator storage capacities are indicated in Table 7 (see “Water System”). Be sure to vent the
system while filling it, and close the vent when system is full.
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in an Air-Cooled Cold
Generator may result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment
specialist be engaged to determine what water treatment, if any, is
required. Trane assumes no responsibility for equipment failures
which result from untreated or improperly treated water, or saline or
brackish water.
5. Close the chilled water circuit breaker, and start the chilled water pump
motor. With water circulating through the chilled water system, inspect all
piping connections for leaks and make any necessary repairs.
42CSRA-SVX01A-EN
Page 43
Operation
6. Adjust the water flow rate through the chilled water circuit, and check the
water pressure drop through the evaporator. Refer to “Water System”.
7. Adjust the flow switch (installed on the evaporator outlet piping) to provide proper operation.
Note: With the water pump operating, throttle the water flow to approximately 50 percent of the full flow rate. Following the manufacturer's instructions, adjust the flow switch contacts to open at this point. Use an ohmmeter
to check for contact opening and closure.
8. Stop the chilled water pump.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power
can not be inadvertently energized. Failure to disconnect power before
servicing could result in death or serious injury.
9. Open all circuit breakers; then reinstall control circuit fuse (FU) (removed
in Step 1) in the main unit control panel.
The unit is now ready for normal operation; refer to “Start- Up Procedure”.
Low Ambient Operation
Field Installed Head Pressure Control Accessory
ChillerSource units will operate in outdoor ambient temperatures down to
(50° F- 10 ton, 45° F -15 ton) w/o HGBP. This accessory will enable units to
operate down to 0° F w/o HGBP. (See Table 5).
Head pressure control for chiller units is regulated by means of a field
installed head pressure accessory which varies condenser fan speed in relation to discharge pressure.
When discharge pressure is 270 psig or higher, the condenser fan runs at full
speed. At pressures between 270 psig and 180 psig, the fan speed is
adjusted (increased or decreased) in direct relation to the pressure, with minimum fan speed (10% of rated motor RPM) occurring when the pressure
reaches 180 psig. At pressures below 180 psig, the fan will not run.
When discharge pressure rises to 180 psig, the fan will start and run at the
reduced speed. Fan speed will continue to increase as the pressure
increases until full speed is reached at 270 psig.
CSRA-SVX01A-EN43
Page 44
Operation
Freeze Protection
If the unit will remain operational at subfreezing ambient temperatures, follow the recommendations outlined below to ensure adequate protection for
the chilled water system.
1. Energize the factory installed chilled water piping heat tape by energizing
shore power supply. If additional heat tape was installed in the field, energize the fused disconnect switch supplied by the field. Verify that all
exposed piping is adequately protected.
2. “Freeze-proof the chilled water system by adding a nonfreezing, low-temperature heat transfer fluid to the chilled water. The solution used must
be strong enough to provide sufficient protection to prevent ice formation
at 10° F below the lowest expected ambient temperature.
Follow the manufacturer's recommendations for installation and testing procedures for any freeze-proofing fluid used. Refer to Table 7 for evaporator
liquid capacities.
Note: Use of an ethylene-glycol type fluid will reduce system capacity. This
factor must be considered during system design. (See Figure 7).
Electrical Control System
The controls used on CGA 10 and 15-ton units are classified either as
“safety” controls or “operational” controls. Brief descriptions of the specific
safety and operating controls used in the CGA control scheme are provided
in the following paragraphs.
Refer to the following control descriptions and to Table 6 for control settings,
and to Figure 17 for control locations.
Unit Safety Controls:
Low Pressure Cutout (LPCO1, LPCO2)
These units are protected by low pressure cutouts that open and stop compressor operation if the operating pressure drops below 38.5 ± 1 psig. The
cutout automatically resets when the pressure reaches 44.5 ± 2 psig. The
LPCO is a Single Pole Double Throw (SPDT) device and if it opens at low
ambient start-up, it will energize Outdoor Fan (ODF) relay, stopping the outdoor fan(s) while the compressor remains energized through the Low Ambient Start Timer (LAST).
High Pressure Cutout (HPCO1, HPCO2)
These units have high pressure cutouts that open and stop compressor
operation If the discharge pressure reaches 400 ± 10 psig. The cutout automatically resets when pressure drops to 250 ± 15 psig.
44CSRA-SVX01A-EN
Page 45
Operation
Figure 17 — Typical Unit Control Panels
CSRA-SVX01A-EN45
Page 46
Operation
Reset Relays (RR1, RR2)
If the unit is shut down by the low pressure cutout (or high pressure cutout),
the reset relay locks out the compressor contactor (CC1, CC2). This prevents the system from recycling until the condition that caused the low (or
high) pressure cutout to trip is determined and corrected.
CAUTION
Unit Damage!
Do not reset the control circuit until the cause of the safety lockout is
Identified and corrected. Failure to do so may result in unit damage.
To reset RR1 and RR2, open and re-close the unit disconnect switch.
Low Temperature Cutout (LTC)
The L TC is designed to protect the evaporator from freeze damage in the
event of a water temperature thermostat (WTT) malfunction or restricted
water flow. The LTC's remote sensing bulb is in the evaporator, where it
monitors leaving water temperature. If, during normal unit operation, the
leaving chilled water temperature falls to the trip point, the LTC will open to
interrupt compressor operation. (Manual reset is required.)
Motor Overloads
These units have internal compressor and condenser fan motor overloads.
These overloads protect the motors from overcurrent and overheating conditions and automatically reset as soon as they cool sufficiently.
Unit Operational Controls:
Water Temperature Thermostat (WTT)
System operation for 10 and 15-ton CGA units is governed by a two-stage
water temperature thermostat (WTT). The remote sensing bulb of this device
is factory-installed in a bulb well located on the evaporator water inlet; here,
it monitors the temperature of the water returning to the evaporator. It has a
control range of 5° F per stage, a differential of 5.0° F between stages and a
set point range of -30 to + 100 degrees F.
For an explanation on determining the WTT's setpoint and a description of
the WTT in operation refer to page 48.
Low Ambient Start Timer (LAST1, LAST2)
When LAST1 or LAST2 energizes, the low pressure control is bypassed for
4 minutes, this allows time for suction pressure to build sufficiently for the
low pressure cutout contacts to close.
46CSRA-SVX01A-EN
Page 47
Operation
Note: A low ambient start timer checkout procedure is given on page 59 of
this manual.
Anti-Short Cycle Timers (ASCT1, ASCT2)
An anti-short cycle timer is provided in each compressor control circuit to
protect the compressors from starting too frequently. This can occur as a
result of poor thermostat control associated with light loads and water loops
that are too short. It can also occur because of sudden power outages of
short duration. Whenever the contacts of the water temperature thermostat
(WTI) open-or when there is a momentary power outage-the anti-short cycle
timer will lock out compressor operation for 3 minutes.
Delay Between Compressors (DBC)
The delay between compressors prevents both compressors from starting at
the same time by delaying compressor #2 for 30 seconds.
Unit Control System
Sequence of Operation
Refer to the unit wiring schematic pasted to the inside of the control panel
cover when reviewing the control sequence described below. Refer to this
legend for an explanation of the acronyms used in this sequence.
CWFIR- Chilled Water Flow Interlock Relay
LPCO -Low Pressure Cutout
HPCO -High Pressure Cutout
ASCT -Anti-short Cycle Timer
CC -Compressor Contactor
LTC -Low Temperature Cutout
DBC -Delay Between Compressors
WTT -Water Temperature Thermostat
RR -Reset Relay
CSRA-SVX01A-EN47
Page 48
Operation
10 Ton Operation
1. Disconnect shore power supply to unit if 115 V supply cord is attached to
shore power receptacle.
2. With unit circuit breaker closed, power is supplied to the crankcase heaters, factory supplied evaporator heat tape, and the 24 V control circuit.
3. In order to start the chilled water pump, position handle on pump starter
control panel to the “ON” position. Starting the chilled water pump and
establishing flow will close the flow switch (FS).
4. When the entering water temperature (EWT) rises 5° F above the WTT's
setpoint, its first stage switch closes, allowing power to pass through, the
flow switch, the L TC, the ASCT1, the RR1 contacts, the LPCO1, and the
HPCO1 to energize the CC1 coil. This starts compressor #1 and the outdoor fan.
15 Ton Operation
1. Disconnect shore power supply to unit if 115 V supply cord is attached to
shore power receptacle.
2. With unit circuit breaker closed, power is supplied to the crankcase heaters, factory supplied evaporator heat tape, and the 24 V control circuit.
3. In order to start the chilled water pump, position handle on pump starter
control panel to the “ON” position. Starting the chilled water pump and
establishing flow will close the flow switch (FS), allowing power to pass
through the LTC to energize the CWFIR.
4. When the entering water temperature (EWT) rises 5° above the WTT's
setpoint, its first stage switch closes, allowing power to pass through the
CWFIR contacts, the ASCT1, the RR1 contacts, the LPCO1, and the
HPCO1 to energize the CC1 coil. This starts compressor #1 and outdoor
fan #1.
5. If the EWT rises 10° F above the WTT's setpoint, its 2nd stage switch
closes, allowing power to pass through the CWFIR contacts, the DBC
switch, the ASCT2, the RR2 contacts, the LPCO2, and the HPCO2 to
energize the CC2 coil. This starts compressor #2 and outdoor fan #2.
Determining the setpoint for the Water Temperature Thermostat (WTT)
1. Find the difference between the chiller's entering water temperature
(EWT) and the leaving water temperature (LWT) while both compressors
are running.
DT = EWT - LWT
2. Decide what minimum leaving water temperature (LWT min.) is desired.
This is the minimum temperature that the leaving water reaches during
normal cycling of the WTT.
48CSRA-SVX01A-EN
Page 49
Operation
CAUTION
Chiller Damage!
The minimum leaving water temperature (LWTmin) is not to be lower
than 40° F. Failure to maintain this minimum temperature may result in
ice formation in the chiller leading to unit damage.
If the minimum leaving water temperature (LWTmin) is lower than 40° F, add
the appropriate amount of ethylene glycol and adjust safety control settings.
Leaving an appropriate safety band between LWT min. and the Low Temperature Cut Out setting is important.
3. The WTT set point is then determined by the following formula:
WTT setpoint = LWT min. + DT/2
Note: Actual leaving water temperature will dip lower than the value used in
the equation above due to lag in the thermostat's control.
4. The maximum entering water temperature is computed by:
EWT max = WTT setpoint + 10
Note: Computing EWT max is important. If the heat source is not warm
enough to allow the EWT to rise to EWT max, the second stage of cooling
may never activate.
ADDITIONAL INFORMATION
A. Average Chiller Leaving Water Temperature (LWTavg) During Two Stage
Thermostatic Control as the Load Varies
LWTavg = WTTsetpoint -DT/2 + 5
B. The Maximum Leaving Water Temperature During Normal Thermostatic
Cycling is computed by:
LWTmax = WTTsetpoint -DT/2 + 10
Example:
1. Entering Water Temperature is 55° F based on an actual reading. Leaving
Water Temperature is 45° F.
DT = EWT -LWT
DT = 55 -45
DT = 10° F
2. Desired Minimum Leaving Water Temperature is 40° F. This temperature
is minimum allowable leaving water temperature without requiring ethylene glycol and special controls settings.
3. New Thermostat Setting:
WTTsetpoint = LWTmin + DT/2
WTTsetpoint = 40 + 10/2
WTTsetpoint = 45° F
CSRA-SVX01A-EN49
Page 50
Operation
4. Maximum Entering Water Temperature:
EWTmax = WTTsetpoint + 10
EWTmax = 45 + 10
EWTmax = 55° F
1. At start up, If the entering water temperature (EWT} is less than 5° F
above the WTT setpoint, the unit will not run. When the EWT rises to 5° F
above the WTT setpoint, its first stage switch closes, energizing compressor #1.
2. If the EWT continues to rise and reaches 10° F above the WTT setpoint,
its second stage switch closes, energizing compressor #2.
3. When the cooling demand is met and the EWT drops to 5° F above the
WTT setpoint, its second stage switch opens, dropping out compressor
#2.
4. If the EWT continues to fall and reaches the WTT setpoint, its first stage
switch opens, dropping out compressor #1.
A graphic representation of the above explanation is shown in Figure 18.
50CSRA-SVX01A-EN
Page 51
Operation
Figure 18 — WTT Switching Action
CSRA-SVX01A-EN51
Page 52
Pressure Gauge Connection
Schematics
Figure 19 — Unit Refrigeration Schematic for 10 Ton (CSRA010FAFO)
HPCOHigh Pressure Cut Out Switch
Notes: 1. Circuits through the condenser coil are not shown.
SymbolDefinition
LPCOLow Pressure Control Connection
TXVThermal Expansion Valve
52CSRA-SVX01A-EN
Page 53
Schematics
Figure 20 — Unit Refrigeration Schematic for 15 Ton (CSRA015FAFO)
Pressure Gauge Connection
HPCOHigh Pressure Cut Out Switch
Notes: 1. Circuits through the condenser coil are not shown.
SymbolDefinition
LPCOLow Pressure Control Connection
TXVThermal Expansion Valve
CSRA-SVX01A-EN53
Page 54
Maintenance
Periodic Maintenance
Perform all of the indicated maintenance procedures at the intervals scheduled. This will prolong the life of the unit and reduce the possibility of costly
equipment failure.
Note: Use an “Operator's Log” (such as the one at the back of this manual)
to record a weekly operating conditions history for the unit. This operating
log can be a valuable diagnostic tool for service personnel; by noticing
trends in operating conditions, the operator can often foresee and prevent
problem situations before they become serious.
If the unit does not perform properly during any of these maintenance
inspections, consult the “Trouble Analysis” section of this manual for possible causes and recommended repairs.
Weekly Maintenance
Once the unit has been operating for about 30 minutes and the system has
stabilized, check operating conditions and complete the checkout procedure
described below:
[ ] Check suction and discharge pressures. (Refer to “Checking Operating
Conditions”.
[ ] Check the liquid line sight glasses/moisture indicators. (Refer to “Checking Operating Conditions”).
[ ] If operating pressures and sight glass/moisture indicator conditions indicate a refrigerant shortage, measure system superheat and system subcooling. (Refer to “Checking Operating Conditions”).
[ ] If operating conditions indicate an overcharge, slowly (to minimize oil
loss) recover refrigerant at the liquid line service valve.
Important Note: Do Not release refrigerant to the atmosphere! Refer to general service bulletin MSCU-SB-1 (latest edition).
CAUTION
Freezing Temperatures!
Do not allow liquid refrigerant to contact skin. If it does, treat the injury
similar to frostbite. Slowly warm the affected area with lukewarm water
and seek immediate medical attention. Direct contact with liquid
refrigerant may cause minor or moderate injury.
[ ] Inspect the entire system for unusual conditions and inspect coils for dirt
and debris. If coils are dirty, clean them. (Refer to “Coil Cleaning”).
54CSRA-SVX01A-EN
Page 55
Maintenance
Note: Use an operating log (such as the one at the end of this manual) to
record a weekly operating conditions history for the unit. A complete operating log is a valuable diagnostic tool for service personnel.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in
this section of the manual could result in exposure to electrical,
mechanical or other potential safety hazards. Always refer to the safety
warnings provided throughout this manual concerning these
procedures. When possible, disconnect all electrical power including
remote disconnects before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized.
When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained
in handling live electrical components perform these tasks. Failure to
follow all of the recommended safety warnings provided, could result
in death or serious injury.
Refer to unit schematics to check the number of disconnects required to deenergize the unit.
Monthly Maintenance
[ ] Perform all weekly maintenance procedures.
[ ] Measure and record system superheat.
[ ] Measure and record system subcooling.
[ ] Open the unit circuit breaker; then manually rotate the outdoor fans to
ensure proper orifice clearance.
[ ] Inspect the fan mounting bolts for tightness.
[ ] Check fan set screws for tightness.
Annual Maintenance
[ ] Perform all weekly and monthly maintenance procedures.
[ ] Have a qualified service technician check the setting and function of each
control and inspect the condition of all contactors and replace as necessary.
[ ] If the chiller is not piped to drain facilities, make sure the drain is clear to
carry away system water.
[ ] Drain water from evaporator pump and associated piping systems.
Inspect all piping components for leakage. damage, etc. Clean out any inIine water strainers.
CSRA-SVX01A-EN55
Page 56
Maintenance
[ ] Clean and repaint any corroded surfaces.
[ ] Clean condenser coils. (Refer to “Coil Cleaning”).
[ ] Inspect the expansion valve sensing bulbs for cleanliness; clean if
required. These sensing bulbs must make good contact with the suction
lines, and must be properly insulated.
[ ] Determine whether or not lubrication of the outdoor fan motor bearings is
needed; lubricate bearings with a light-weight oil (e.g., SAE-20 non-detergent or equivalent), if necessary.
Note: CGA outdoor fan motor assemblies are permanently lubricated and
usually do not require additional oiling unless the unit is installed in a “dirty”
environment. Under such conditions, lubricate the fan motor bearings after
every 10,000 hours of operation. Do not over lubricate!
[ ] Clean condenser fans.
Maintenance Procedures
This section describes specific maintenance procedure(s) which must be
performed as a part of the normal maintenance program for this unit. Be certain that electrical power to the unit is disconnected before performing these
procedures.
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in
this section of the manual could result in exposure to electrical,
mechanical or other potential safety hazards. Always refer to the safety
warnings provided throughout this manual concerning these
procedures. When possible, disconnect all electrical power including
remote disconnects before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized.
When necessary to work with live electrical components, have a
qualified licensed electrician or other individual who has been trained
in handling live electrical components perform these tasks. Failure to
follow all of the recommended safety warnings provided, could result
in death or serious injury.
Refer to unit schematics to check the number of disconnects required to deenergize the unit.
Coil Cleaning
Clean the condenser refrigerant coil at least once each year (or more frequently if the unit is located in a “dirty” environment) to help maintain proper
unit operating efficiency. Specific instructions for cleaning refrigerant coils
are outlined below. Follow these instructions as closely as possible to avoid
potential damage to the coils.
56CSRA-SVX01A-EN
Page 57
Maintenance
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly alkaline. Handle
chemical carefully. Proper handling should include goggles or face
shield, chemical resistant gloves, boots, apron or suit as required. For
personal safety refer to the cleaning agent manufacturers Materials
Safety Data Sheet and follow all recommended safe handling practices.
Failure to follow all safety instructions could result in death or serious
injury.
To clean the refrigerant coil, a soft brush and sprayer (i.e., either a garden
pump-up type, or a high-pressure sprayer) must be used. In addition, a highquality detergent is required; suggested brands include “SPREX A.C.”,
“OAKITE 161”, “OAKITE 166”, and “COILOX”.
Note: If the detergent is strongly alkaline (i.e., has a pH value greater than
8.5) after mixing, an inhibitor must be added.
Cleaning Procedure:
1. Disconnect power to the unit.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Refer to unit schematics to check the number of disconnects required to deenergize the unit.
2. Remove enough panels and components from the unit to gain access to
the condenser coils.
3. Protect all electrical devices such as motors and controls from dust and
water.
4. Straighten coil fins with a fin rake, if necessary.
5. Use a soft brush to remove loose dirt and debris from both sides of the
coil.
6. Mix the detergent with water according to the manufacturer's instructions.
To improve the cleansing ability of the solution, heat it to a maximum of
150° F.
CSRA-SVX01A-EN57
Page 58
Maintenance
WARNING
Hazardous Pressures!
Coils contain refrigerant under pressure. When cleaning coils,
maintain coil cleaning solution temperature under 1500F to avoid
excessive pressure in the coil. Failure to follow these safety
precautions could result in coil bursting, which could result in death or
serious injury.
7. Place the cleaning solution in the sprayer. Be sure to follow these guidelines if a high-pressure sprayer is used: (1) minimum nozzle spray angle
is 15 degrees; (2) spray solution at 90 degrees to the coil face; (3) keep
sprayer nozzle at least six inches from the coil; and, (4) sprayer pressure
must not exceed 600 psi.
8. Spray the leaving air side of the coil first; then spray the entering air side
of the coil. Allow the detergent-and- water solution to stand on the coil for
5 minutes.
9. Rinse both sides of the coil with cool, clean water.
10.Inspect the condenser coil. If it still appears to be dirty, repeat Steps 7
and 8.
11.Remove protective covers installed in step 3.
12.Reinstall all unit components and panels; then restore electrical power to
the unit.
Cleaning the Evaporator
The chilled water system is a closed loop. It should not accumulate a large
amount of scale or sludge. Inlet strainer should be cleaned periodically. If the
chiller is fouled, first try to dislodge foreign material by back-flushing the system several times. If this does not work, take a water sample from the evaporator and analyze it. Determine treatment based on the findings.
CAUTION
Evaporator Damage!
Do not use an acidic type cleaning agent. Failure to follow these
instructions may result in damage to the internal evaporator
components.
Water Treatment
CAUTION
Proper Water Treatment!
The use of untreated or improperly treated water in an Air-Cooled Cold
Generator may result in scaling, erosion, corrosion, algae or slime. It is
recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required.
Trane assumes no responsibility for equipment failures which result
from untreated or improperly treated water, or saline or brackish water.
58CSRA-SVX01A-EN
Page 59
Trouble Analysis
Low Ambient Start Timer (LAST) Checkout Procedure
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before
servicing. Follow proper lockout/tagout procedures to ensure the
power can not be inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
To determine whether or not a low ambient start timer is defective, follow
these steps.
1. Remove power from the CGA unit by opening the supply power circuit
breaker.
2. Disable both low pressure cutouts (LPCO1 and LPCO2) by disconnecting
the wires from their number 1 terminals. Tape the disconnected wires to
prevent shorting.
3. Restore power to the system, energize compressor number one and
check how long it runs before cutting out.
4. Remove power from the system and disable compressor number one.
Tape any wires removed to prevent shorting.
5. Restore power to the system, energize compressor number two and
check how long it runs before cutting out.
6. Remove power from the system and re-connect the wires removed from
the low pressure cutouts in step two. Re-connect the wires that disabled
compressor number one.
7. Restore power to the unit.
Conclusion: Compare the compressor run times verified in steps 3 and 5
with the rated duration of the low ambient start timers. (The rated duration
times are usually stamped on the timers or given in the unit literature). If the
compressor run times don't match the duration times of the low ambient start
timers, the timers are defective and must be replaced.
Preliminary Troubleshooting Inspection
If operational difficulties are encountered, be sure to perform these preliminary checks before referring to the troubleshooting charts:
[ ] Check the water temperature thermostat (WTT) to ensure that it is set
correctly, receiving control power, and “making/breaking” at the proper intervals.
CSRA-SVX01A-EN59
Page 60
Trouble Analysis
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components.
Have a qualified licensed electrician or other individual who has been
properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed
to live electrical components could result in death or serious injury.
[ ] Verify that the unit is receiving electrical supply power, and that the fuses
in the main control panel are intact.
[ ] Check the evaporator for proper water supply. Check the flow switch for
proper operation, and take pressure drop readings across the evaporator.
After completing the preliminary checks described above, be sure to inspect
the unit for other obvious causes of trouble such as an excessively dirty condenser coil, leaking water connections, broken or disconnected wires, etc. If
everything appears to be in order, but the unit still fails to operate properly,
refer to the appropriate troubleshooting chart and contact a qualified service
technician.
Troubleshooting Charts
The troubleshooting charts which follow are provided to serve as an aid for
identifying the cause of any system malfunctions that may occur. Within
each chart are three columns: (1) the Symptom column describes the
behavior the unit is exhibiting; (2) the Probable Cause column identifies the
most likely sources of the malfunction; and, (3) the Recommended Action
column describes the suggested action for correcting the problem.
Note: The troubleshooting charts which follow are provided solely as a guide
for determining the cause of mechanical failure or malfunction. When
mechanical problems do occur, Trane recommends that qualified service
personnel be contacted (ChillerSource, 800-755-5115) to help ensure proper
diagnosis and repair of the unit.
The following warning applies to many of the recommended actions suggested in the troubleshooting charts.
WARNING
Live Electrical Components!
During troubleshooting of this product, it may be necessary to work
with live electrical components. Have a qualified licensed electrician or
other individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
60CSRA-SVX01A-EN
Page 61
Troubleshooting
Symptom
A. Compressor neither starts nor hums
Probable CauseRecommended Action
1. No power to unit.Check for the following:
a. Disconnect switch open.
b. Fuse(s) blown.
2. No call for cooling.Check for the following:
a. Defective thermostat.
b. Broken or improper
control wiring.
c. Blown control power fuse.
3. Anti-short cycleWait at least 3 minutes
timer has notfor the anti-short cycle
times out.timer to time out.
4. Unit locked out byCheck for the following:
reset relay.
a. Excessive discharge
pressure; see “Discharge
Pressure Too High”
b. Defective high pressure
control.
c. Low Charge; Low pressure
switch open.
d. Defective reset relay
contact.
5. Compressor contactorCheck for the following:
will not close.
a. Defective compressor
contactor.
b. Improper wiring.
c. Reset relay open.
d. Low pressure control open.
e. Cooling relay not
energized. Defective relay;
check thermostat circuit.
See probable cause #2
above.
6. Compressor windingSee “Compressor Motor
stat open. Winding Stat Open”.
a. Check compressor amp
draw.
Symptom
B. Compressor hums, but will not start.
Probable CauseRecommended Action
1. Low voltage atCheck for the following:
compressor.
a. Single blown fuse.
b. Low line voltage.
c. Defective compressor
contactor.
d. Loose wiring
connections.
2. Defective compressor. Check for the following:
a. Open motor winding.
b. Excessive amp draw on
all phases.
3. Insufficient starting Check for the following:
voltage (Single-phase
units only)a. Defective start capacity.
b. Defective start relay.
Symptom
C. 2nd stage compressor fails to start.
Probable CauseRecommended Action
1. Time delay contactsReplace time delay relay.
fail to close.
2. No call for cooling.Check for the following:
a. Defective thermostat.
b. Broken or improper
control wiring.
3. Unit locked out bySee Symptom A, Probable
reset relay.Cause #4.
4. Compressor contactor See Symptom A, Probable
will not close.Cause #5.
(Continued on next page)
CSRA-SVX01A-EN61
Page 62
Troubleshooting
Symptom
D. Compressor short cycles.
Probable CauseRecommended Action
1. Intermittent ContactCheck for the following:
in control circuit.
a. Defective relay contacts.
b. Loose wiring
connections.
Symptom
E. Compressor runs continuously.
Probable CauseRecommended Action
1. Unit undersized forCheck for cause of
load (cannot maintainexcessive load.
water temperature).
2. Thermostat setpointReadjust thermostat.
too low.
3. Defective thermostatReplace thermostat.
or control wiring.Replace or repair control
wiring.
4. Welded contacts onRepair or replace
compressor contactor. contactor.
5. Leaky valves inReplace compressor.
compressor (indicated
by abnormally low
discharge and high
suction pressures).
6. Shortage of refrigerant Find and repair refrigerant
(indicated by reducedleak. Recharge system.
capacity, high super heat, low subcooling
and low suction
pressure).
Symptom
F. Compressor motor winding stat open.
Probable CauseRecommended Action
1. Excessive load onCheck for the following:
evaporator (indicated
by high supply watera. Excessive water flow.
temperature).b. High return water
temperature.
2. Lack of motor coolingCheck for the following:
indicated by excessive
superheat).a. Improper expansion
valve setting.
b. Faulty expansion valve.
c. Restriction in liquid
line.
3. Improper voltage atCheck for the following:
compressor.
a. Low or imbalanced line
voltage.
b. Loose power wiring.
c. Defective compressor
contactor.
4. Internal parts of Replace compressor.
compressor damaged.
Symptom
G. Compressor is noisy.
Probable CauseRecommended Action
1. Internal parts of Replace compressor.
compressor damaged
or broken (compressor
knocks).
2. Liquid flood-backCheck and adjust
(indicated by superheat.
abnormally cold suction
line and low superheat.
3. Liquid refrigerant in Check crankcase heater.
compressor at start-up
(indicated by
abnormally cold Check for refrigerant
compressor shell). overcharge.
Symptom
H. System short of capacity.
Probable CauseRecommended Action
1. Low refrigerant charge Add refrigerant.
(indicated by high
superheat and low sub cooling).
(Continued on next page)
62CSRA-SVX01A-EN
Page 63
Troubleshooting
2. Clogged filter drier Replace filter drier or
(indicated by tempera- filter drier core.
ture change in
refrigerant line thru
drier).
4. Expansion valve stuck Repair or replace
or obstructed (i.e.,expansion valve.
high superheat and
high water temperature).
5. Low evaporator water Check strainers. Adjust
flow. water flow.
6. Noncondensibles in Evacuate and recharge
system. system.
7. Leaky valves in Replace compressor.
compressor (i.e.,
operation at
abnormally high suction
and low discharge
pressures).
Symptom
I. Suction pressure too low.
Probable CauseRecommended Action
1. Shortage of refrigerant Find and repair leak;
(i.e., high superheat, recharge system.
low subcooling).
Symptom
J. Suction pressure too high.
Probable CauseRecommended Action
1. Excessive cooling load See Symptom E.
(i.e., high supply
water temperatures).
2. Expansion valve over- Adjust superheat setting;
feeding (i.e. super-heat verify that remote bulb is
too low, liquid flooding properly attached to
to compressor).suction line.
Trane has a policy of continuous product data and product improvement and reserves the right to change
design and specifications without notice. Only qualified technicians should perform the installation and servicing
of equipment referred to in this bulletin.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.