Trane CONTH01AAUTOA Installer's Manual

24V
RC
BYPASS
ODTH
POWER
STEP 1: Unpack the Humidifier Control Carton
Make sure all components are present (see Figure A):
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT – This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
THIS INFORMATION IS FOR USE BY INDIVIDUALS HAVING ADEQUATE BACKGROUNDS OF ELECTRICAL AND MECHANICAL EXPERIENCE. ANY ATTEMPT TO REPAIR A CENTRAL AIR CONDITIONING PRODUCT OR ACCESSORY HUMIDIFIER OR HUMIDIFIER CONTROL MAY RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE. THE MANUFACTURER OR SELLER CANNOT BE RESPONSIBLE FOR THE INTERPRETATION OF THIS INFORMATION, NOR CAN IT ASSUME ANY LIABILITY IN CONNECTION WITH ITS USE.
These instructions do not cover all variations in systems or provide for every possible contingency. Should further information be desired or particular problems arise which are not covered sufficiently by this manual, contact your local distributor or the manufacturer as listed on the humidifier nameplate.
Use the “OFF” setting to turn the Humidifier Pad Change indicator OFF.
Use setting “A” for very hard water conditions in any location. Humidifier Pad Change indicator LED light will activate after 75 hours of solenoid valve operation.
Use setting “B” for winters in the South.
Humidifier Pad Change indicator LED light will activate after 300 hours of solenoid valve operation.
Use setting “C” for winters in the Midwest and Eastern United States. Humidifier Pad Change indicator LED light will activate after 600 hours of solenoid valve operation.
Figure B
BYPASS/POWER MODE SWITCH
HUMIDIFIER PAD INDICATOR SETTING
90-1010
Installer’s Guide
18-CH31D1-3
Automatic Humidifier Control
*CONTH01AAUTOA
*May be “A” or “T”
READ COMPLETE INSTALLATION INSTRUCTIONS AND TEMPLATE BEFORE STARTING.
WARNING:
HAZARDOUS VOLTAGE – DISCONNECT POWER BEFORE INSTALLING OR SERVICING
WARNING
CAUTION
A
D
HUMIDIFIER PAD CHANGE INDICATOR
Figure A
C
B
90-1009
STEP 2: Disassemble the Humidifier Control
Remove door from the Humidifier Control by pulling the bottom of the door straight out.
STEP 3: Check the Mode Switch
With the door removed, notice the switch labeled BYPASS and POWER (partially covered by the enclosure). Make sure the switch is correctly set for the type of humidifier being installed or damage to the Humidifier Control could result (see Figure B).
STEP 4: Check the Change Humidifier Pad Indicator Setting
This setting controls the indicator light interval, reminding you to change your Humidifier Pad. If your Control came with a humidifier, the Control is pre-set at position “C”. If the installation site has a 3-month or shorter heating season or very hard water, you may want to adjust the setting (see Figure B). The Control must be energized to reset the Humidifier Pad Indicator.
1. 120 volts may cause serious injury from electrical shock. Disconnect electrical power to the furnace before starting installation.
2. Sharp edges may cause serious injury from cuts. Use care when
cutting plenum openings and handling ductwork. Use personal protective equipment when installing or servicing HVAC equipment.
1. Do not set humidity higher than recommended. Property damage may
result.
2. Do not set humidity up to recommended levels if there is condensation
on the inside of windows of any unheated living space. Property damage may result.
3. Do not mount Humidifier Control on supply plenum or duct. The Control
will not withstand supply temperatures.
4. When installing Humidifier Control on downflow furnaces, ensure
blower continues to run after a heat call is satisfied to eliminate high temperatures from damaging the Humidifier Control.
5. Do not mount Humidifier Control downstream of the bypass outlet. The
Control will not operate correctly due to false humidity readings.
6. Set the Bypass/Power mode switch in the proper position, or damage
to the Humidifier Control could result (see Step 3).
THESE INSTALLATION INSTRUCTIONS ARE FOR THE AUTOMATIC HUMIDIFIER CONTROL ONLY!
For Humidifier installation, follow Humidifier Installation Instructions.
© 2008 Trane. All rights reserved. 18-CH31D1-3
DOOR
Note: The Control may installed in automatic or manual mode.
STEP 9: Route the Wire from Control to Sensor
Run a separate 18 ga. control wire to the outdoor temperature sensor. Sensor is not affected by lead length. In either case, do not run outdoor temperature sensor alongside wires carrying high voltage (120 VAC or higher). Secure the sensor bracket with a #8 galvanized screw.
STEP 10: Attach Sensor Wire to Humidifier Control
Strip wire 1/4 inch, and insert the wires from the Sensor into the terminals labeled “ODT” on the Humidifier Control. See Figure F for location of terminals.
Installing the Humidifier Control for Manual Operation
If it is not feasible to use the Outdoor Temperature Sensor, the Humidifier Control can be operated in Manual Mode.
1. Connect the Manual Mode Resistor Case wires to the terminals labeled “ODT” on the Humidifier Control.
2. Snap the Manual Mode Resistor Case into the slot provided so that Resistor Case sticks out from the bottom edge of the base.
3. Remove the control knob and apply the Manual Mode label to the cover, aligning the sticker and knob holes. Re-install the knob.
STEP 8: Alternate Location for Outdoor Temperature Sensor
The Sensor can also be mounted in the center of either:
• 2 inch PVC fresh air intake pipe for the furnace
OR
• 6 inch fresh air intake duct. Mount the sensor with a #8 galvanized screw.
In both cases, the Sensor must be no more than 3 feet from the outside wall. See Figure E.
If it is not feasible to use the Outdoor Temperature Sensor in any of the ways described, the Humidifier Control can be installed for Manual Operation. See box “Installing the Humidifier Control for Manual Operation” and Figure G for details.
STEP 11: Determine Power Source for Humidifier Control
Determine where you will get 24 VAC to power the Humidifier Control (see options below).
OPTION 1:
FURNACES WITH ACCESSORY TERMINALS.
If the accessory terminals provide:
• 24 VAC: Wire these directly to the “R” and “C” terminals on the Humidifier Control.
• 120 VAC: Wire to a 24 VAC transformer, which in turn connects to the “R” and “C” terminals on the Humidifier Control.
OPTION 2:
EXTERNAL 24 VAC TRANSFORMER: Wire into a power source other than the furnace blower circuit. The transformer can be powered off the 120 VAC line at the junction box before it enters the furnace. The 24 volt side of the transformer is connected to the “R” and “C” terminals on the Humidifier Control.
In either case, the voltage to the Humidifier Control must be between 22 VAC and 30 VAC. Run a separate 18 ga. wire from a 24-volt supply to the humidifier control.
NOTES:
• The Humidifier Control will operate properly with either a switched or continuous power source.
• Whether using ACCESSORY TERMINALS OR an EXTERNAL TRANSFORMER, the minimum VA required is; 2.0 VA for Power Humidifiers; or 10.0 VA for Bypass Humidifiers.
• When power is connected for the first time, the red and green LEDs will light momentarily.
STEP 12: Wiring
See Diagrams A-D for wiring options.
Figure G
STEP 6: Determine Location for Outdoor Temperature Sensor
The location of the Outdoor Temperature Sensor must meet these three requirements:
1. Must be mounted on North, East or West side of house out of direct sunlight
2. Must be at least
3 feet from all exhaust vents
3. Must be above expected snow line (See Figure D)
Incorrect humidity levels will result if these requirements are not met.
STEP 7: Locate Existing Access Hole to Outside
A convenient way to get the Sensor wire outside is to make use of unused wires running to the A/C condensing unit (if applicable). Other ways are to use existing holes for Cable TV lines, telephone lines, A/C lines, etc. Read all equipment instructions beforehand for possible conflicts and warnings.
90-1013
Figure F
90-1012
Figure E
90-999
STEP 5: Determine Location for Humidifier Control
and Mount It
Humidifier Control must be mounted in the Return Duct. For proper operation, the Humidifier Control must be at least 6 inches upstream of any of the following:
• Humidifier
• Humidifier Bypass Ductwork (if applicable)
• Fresh Air Intake Ductwork (if applicable) (see Figure C)
After location for Control is selected, use the perforated Humidifier Control template (attached to these instructions) to mark the duct opening and cut it. Use 4 sheet metal screws (not provided) to mount the Humidifier Control in the duct opening and
make sure Humidifier Control is sealed tightly to duct.
Figure C
90-1137
NORTH, EAST OR WEST SIDE OF HOME
OUTDOOR
TEMPERATURE
SENSOR
SENSOR
BRACKET
SENSOR
ABOVE EXPECTED
SNOW LINE
OUTDOOR
TEMPERATURE SENSOR
LEADS
Figure D
90-998
CAUTION
Do not mount control on supply air plenum or duct. Failure to follow this caution my cause property damage.
18-CH31D1-3
RETURN
DUCT
HUMIDIFIER
CONTROL
FRESH AIR
INTAKE
CONNECTION
6" MIN.
BYPASS
HUMIDIFIER
COIL
36" MAX.
OUTSIDE WALL
CENTER LINE
BYPASS
POWER
RC
ODTH
24V
BYPASS
POWER
R
C ODTH
24V
Loading...
+ 2 hidden pages