Trane CFEA 04 C0M1, CFEA 06 C0M1, CFEA 08 C0M1, CFEA 10 C0M1, CFEA 12 C0M1 Owner's Manual

...
Page 1
Owner Manual
Chilled Water Fan Coil Convertible Type CFEA Series 50/60 Hz
UNT-SVU001-EN
50 Hz Models Cooling Only
60 Hz Models Cooling Only
Cooling/Heating
CFEA 04 CEM1 CFEA 06 CFM1 CFEA 08 CBM1 CFEA 10 CHM1 CFEA 12 CJM1 CFEA 14 CJM1 CFEA 16 CKM1 CFEA 20 CLM1
Cooling/Heating
CFEA 04 CEM2 CFEA 06 CFM2 CFEA 08 CBM2 CFEA 10 CHM2 CFEA 12 CJM2 CFEA 14 CJM2 CFEA 16 CKM2 CFEA 20 CLM2
AQUASTYLUS
August 1999
Page 2
2
UNT-SVU001-EN
General Information
General Information
Congratulations on your choice of a Trane chilled water fancoil system. These systems have been carefully designed and manufactured under strict Trane Worldwide Quality Standards to provide you with years of comfortable, convenient cooling or heating/cooling with a minimum of service.
This Owner Manual is given as a guide to start-up, operation and periodic maintenance by the user of CFEA chilled water fancoil system. It does not contain the full service procedures necessary for the continued success­ful operation of this equipment. The services of a qualified service techni­cian should be employed, through the maintenance contract with a reputable service company.
Read it completely before doing anything with your air conditioning system.
About this Manual
Cautions appear at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The Trane Company assumes no liability for the inappropriate usage of the unit.
© American Standard Inc. 1999
About the Unit
These CFEA units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to CFEA units are designed to operate in cooling mode only and in cooling or heating modes.
Trane CFEA series of chilled water fancoil systems offer three styles of installation: floor, low wall and under ceiling with both LCD wireless remote control or wired control. Trane CFEA series provide flexibility and savings. Note: For model CFEA14, CFEA16 and CFEA 20, there are only two styles of installation: under ceiling and low wall.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage of the unit on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the dealer at the same time.
The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the dealer.
Warning
Warnings are provided at appropriate places in this manual to indicate to installers, operators and service personnel of potentially hazardous situations which, if not avoided, COULD result in death or serious injury.
Caution
Cautions are provided at appropriate places in this manual to indicate to installers, operators, and service personnel of potentially hazardous situations which, if not avoided, MAY result in minor or moderate injury or malfunction of the unit.
Your personal safety and the proper operation of this unit require that you follow them carefully. The Trane Company assumes no liability for installations or servicing performed by unqualified personnel.
Warranty
Warranty is based on the general terms and conditions by country. The warranty is void if the equipment is modified or repaired without the written approval of The Trane Company, if the operating limits are exceeded or if the control system or the electrical wiring is modified.
Damage due to misusage, lack of maintenance or failure to comply with the manufacturer’s instructions, is not covered by the warranty obligation. If the user does not conform to the rules described in Owner Manual, it may entail cancellation of warranty and liabilities by The Trane Company.
Important
These instructions do not cover all variations in systems, nor do they provide for every possible contingency to be met. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your authorized Trane dealer.
Page 3
UNT-SVU001-EN
3
Contents
General Information 2 Control Operation 4 Wireless Remote Control 5 Wired Control 9 System Operation 12 Maintenance 13 Troubleshooting 14 Notes 15
Page 4
4
UNT-SVU001-EN
Infrared Remote Control Unit Display and One-touch Control Switch
Control Operation
Four lamps on the unit show operating status.
1. FAN Lamp
This lamp lights when the fan is operating.
2. COOLING Lamp
This lamp lights when the unit is in COOL or DRY mode of operation.
3. HEATING Lamp
This lamp lights when the unit is in HEAT mode of operation, or heater ON in the HEAT mode of AUTO mode (light does not function on units without electric heat)
4. TIMER Lamp
This lamp lights when the system is being controlled by the timer.
One Touch Control Switch (A)
This button is used for adjusting operation without remote control unit.
• This press switch is for selecting the system mode of operation FAN COOL DRY (HEAT) (AUTO) OFF (HEAT and AUTO are available only in Cooling/ Heating Modes)
• Fan speed will operate in AUTO mode; temperature setpoint will be maintained at 24OC.
Note: This press switch is started
from COOL mode (If the system is off) and operated sequencely as above (If the system is on). The One-Touch Control mode is cancelled by the signal of the remote control unit.
1 2 3
A
4
Infrared Signal Receiver
Display Panel
Page 5
UNT-SVU001-EN
5
Infrared Remote Control Name and Function of Buttons
1. Infrared Signal Transmitter
Transmits the signal to indoor unit.
2. MODE Button
Press this button to select system operating modes. In cooling only system, a mode is selected in a sequence as FAN, COOL, DRY and back to FAN. In cooling and heating system, a mode is selected in a sequence as FAN, COOL, DRY, HEAT, AUTO and back to FAN.
3. SWEEP Button
Press this button to activate sweep motor to distribute air flow (not available in all models).
4. LOUVER Button
Press this button to adjust the direction of air flow.
5. POWER Button
Press this button to start operation. Press the button again to stop operation.
6. Temperature Setting Button
TEMP : Press this button to increase the set temperature. TEMP : Press this button to decrease the set temperature.
7. FAN Button
Press this button to select fan speed.
8. SLEEP Button
Press this button to control temperature while sleeping.
9. CLOCK Button
This button is used to set the clock.
10.STOP Button
Press this button to set the OFF timer.
11.START Button
Press this button to set the ON timer.
12.MIN Button
This button is used to set the minute.
13.HOUR Button
This button is used to set the hour.
14.SEND Button
This button is used to confirm the programming on the remote unit to the fan coil unit.
MODE
LOUVER
HOUR
SLEEP
TEMP
SWEEP
SEND
START
MIN
STOP
FAN COOL DRY HEAT
START STOP
HIGH
MED
LOW
AUTO
1
7 8
9 10 11 12 13
14
2
3
4
5
6
Battery: Two AAA batteries are used in this remote control unit
Wireless Remote Control
Page 6
6
UNT-SVU001-EN
Indicators on Infrared Remote Control
System Operating Selection
FAN Only System Operation
- Press POWER button (the display panel shows the previous settings).
- Press MODE button to select the system operating mode, FAN mode will be shown on the display.
- Press FAN button to select any fan speed. The FAN display will show LOW, MED, HIGH or AUTO according to fan speed level, low, medium, high and auto.
COOLING System Operation
- Press POWER button (the display panel shows the previous settings).
- Press MODE button to select the COOL operating mode, “COOL” mode will be shown on the display.
- Press either TEMP or TEMP button to set the desired room temperature. Temperature set range is 18OC to 30OC.
- Press FAN button to select any fan speed. The FAN display will show LOW, MED, HIGH or AUTO according to fan speed level, low, medium, high and auto.
1. Clock
Displays the current time.
2. Timer START
The time set for timer on operation is indicated.
3. Timer STOP
The time set for timer off operation is indicated.
4. Transmission Indicator
This transmission indicator lights when remote control transmits signals to the indoor unit.
5. SLEEP Mode
Displayed by pressing the SLEEP button. Press the SLEEP button again to disappear.
6. Temperature Setting
Displays the temperature setting (18OC to 30OC) When setting the operation mode to FAN only, no temperature setting is displayed.
7. Fan Speed
Displays the selected fan speed. Fan speed level, low (LOW), medium (MED), high (HIGH), auto (AUTO) will be indicated.
8. System Mode
Displays the current operation mode. In cooling only (FAN, COOL or DRY). In cooling and heating system (FAN, COOL, DRY or HEAT).
FAN COOL DRY HEAT
START STOP
HIGH
MED
LOW
AUTO
1
2 3 4 5
7
6
8
HEATING System Operation (Heating/Cooling Models)
- Press POWER button (the display panel shows the previous settings).
- Press MODE button to select the HEAT operating mode, “HEAT” mode will be shown on the display.
- Press either TEMP or TEMP button to set the desired room temperature. Temperature set range is 18OC to 30OC.
- Press FAN button to select any fan speed. The FAN display will show LOW, MED, HIGH or AUTO according to fan speed level, low, medium, high and auto.
AUTO System Operation (Heating/Cooling Models)
- Press POWER button (the display panel shows the previous settings).
- Press MODE button to select the AUTO operating mode, “AUTO” mode will be shown on the display.
- Press either TEMP or TEMP button to set the desired room temperature. Temperature set range is 18OC to 30OC.
- Press FAN button to select any fan speed. The FAN display will show LOW, MED, HIGH or AUTO according to fan speed level, low, medium, high and auto.
- The system will automatically switch between cooling mode and heating mode to maintain desired temperature setting.
DRY System Operation
- Press POWER button (the display panel shows the previous settings).
- Press MODE button to select the DRY operating mode, “DRY” mode will be shown on the display.
- Press either TEMP or TEMP button to get the desired room temperature setting at the indication. Temperature set range is 18OC to 30OC.
- The system automatically cycle the compressor and fan (low speed) to remove moisture from the air without overcooling the room.
Page 7
UNT-SVU001-EN
7
Timer Operation
Once you select the timer operation, the settings are saved in the remote control. Thereafter, the air conditioner will start operating under the same conditions when you simply push the POWER button of the remote control.
Setting STOP Timer
You can set the STOP timer to stop the unit automatically at any desired time up to 24 hour ahead.
- Press POWER button to turn on the unit and the display panel show the previous condition.
- Press STOP button once. On the display panel, the last set time of the STOP timer will be blinking.
- Press HOUR or MIN buttons to change the time (pass this step, if no time change is required).
- Press SEND or STOP buttons to transmit the signal to the air conditioner. The set time will stop blinking.
- The unit will stop automatically at set time of OFF timer
- To cancel the STOP timer, press STOP button again.
Setting START Timer
You can set the START timer to start the unit automatically at any desired time up to 24 hour ahead.
- Press POWER button to turn on the unit, and the display panel shows the previous condition.
- Press START button once. On the display panel, the last set time of the START timer will be blinking.
- Press HOUR or MIN buttons to change the time (pass this step, if no time change is required).
- Press SEND or START buttons to transmit the signal to the air conditioner. The set time will stop blinking.
- The unit is now standby for starting automatically at set time of START timer.
- To cancel the START timer, press START button again.
Note: In case of power failure,
the START/STOP timer will be automatically cancelled as there is no electricity in the air-conditioner. (But the set time on the remote unit is still displayed due to the batteries). If any button or the remote unit is pressed when the electricity is back to normal, this feature will be re-activated.
Page 8
8
UNT-SVU001-EN
SLEEP Mode
This feature automatically adjusts the temperature setting to provide increased comfort and save energy (The SLEEP display on LCD will disappear after 1 hour).
COOLING Mode
- Press SLEEP button, one hour after pressing, the air conditioner will automatically raise the set temperature by 10C.
0 1 2 3 4 5 6 7 8 9 10 11 12
-
2
O
C
-
1
O
C
SET POINT
START
NORMAL SLEEP
HOUR
+
1
O
C
+
2
O
C
SLEEP (COOLING MODE)
By pressing SLEEP button, the unit will operate at SLEEP FUNCTION it will automatically return to normal operation when the air-conditioner is switched off and on again.
HEATING Mode
- Press SLEEP button, one hour after pressing, the air conditioner will automatically reduce the set temperature by 1OC. (The SLEEP display on LCD will disappear after 1 hour).
SWEEP Operation
The SWEEP function will operate in either cooling or heating mode to rapidly distribute conditioned air into the room.
- The supply air grille will be fully closed when the unit is off.
- When the unit is turned on, the grille will open to the fully open position.
- After the unit has been turned on, pressing the SWEEP button will sweep the supply air grille back and forth to rapidly distribute and cool (or heat) the room.
- If the unit is in SWEEP mode, pressing the sweep button will return the grille to the fully open position.
- Press the POWER button while the unit is in operation, will turn off the unit and the supply air grille will automatically close.
LOUVER Operation
The direction of the airflow can be controlled
- Press LOUVER button to adjust the angle of the blade to control the direction of the air flow.
Note: The sweep and louver
operations are optional functions of MCX 512 - MCX 524. These opera­tions are not available in the models that have cooling capacity more than 24,000 Btu.
0 1 2 3 4 5 6 7 8 9 10 11 12
START
NORMAL SLEEP
HOUR
SLEEP (HEATING MODE)
By pressing SLEEP button, the unit will operate at SLEEP FUNCTION it will automatically return to normal operation when the air-conditioner is switched off and on again.
-
2
O
C
-
1
O
C
SET POINT
+
1
O
C
+
2
O
C
Page 9
UNT-SVU001-EN
9
LOW
N
FF
MEDIUM
FAN SPEED
MODE
TEMPERATURE
HIGH
FAN
22
20
24
16 30
COOL
COOL WARM
O
OFF
Press Press
ON
ON/OFF Button Switch
FAN SPEED Selector Switch
OFF
LOW
MEDIUM
HIGH
System MODE Selector Switch
Temperature Setting WheelSet Point Indicator
COOL
FAN
Cooling-Only Model
Control and their functions
To operate the unit, follow these steps:
- Set the temperature on the setting wheel.
- Select the FAN SPEED to high, medium or low.
- Select the FAN/COOL mode.
- Press the ON/OFF button to turn the unit ON.
- To turn the unit OFF, press the ON/OFF button again.
Wired Control
Page 10
10
UNT-SVU001-EN
Cooling-Heating Model
Control and their functions
To operate the unit, follow these steps: Cooling Mode
- Set the temperature on the setting wheel.
- Select the FAN SPEED to high, medium or low.
- Select the FAN/COOL mode.
- Press the ON/OFF button to turn the unit ON.
- To turn the unit OFF, press the ON/OFF button again.
Heating Mode
- Select HEAT mode from the selection switch.
- Adjust the set point temperature on the temperature setting wheel to the desired setting. The temperature set point may be changed while the unit is in operation.
- Select the FAN SPEED to high, medium or low.
- Press the ON/OFF button to turn the unit ON.
- To turn the unit OFF, press the ON/OFF button again.
LOW
N
FF
MEDIUM
FAN SPEED
MODE
TEMPERATURE
HIGH
22
20
24
16 30
COOL WARM
O
OFF
Press Press
ON
ON/OFF Button Switch
FAN SPEED Selector Switch
OFF
LOW
MEDIUM
HIGH
System MODE Selector Switch
Temperature Setting WheelSet Point Indicator
FAN
HEAT
COOL
COOL
FAN HEAT
Page 11
UNT-SVU001-EN
11
Adjust Air Flow Direction
- The supply air grille may be adjusted left, right, up or down manually.
- Adjust the air flow direction properly, otherwise, it may cause discomfort and make the room temperature uneven.
Up
Down
Right
Left
Adjust Air Flow Direction (with sweep option)
- The sweep motor will sweep the supply air grille upward and
downward.
- For left and right air flow, the supply air grille can be adjusted manually.
Page 12
12
UNT-SVU001-EN
Operating Precautions
This system must be installed properly by a qualified installer in accordance with installation instructions.
Anti-Recycle Timer
- The control system has a build-in 3 minute anti-recycle timer which helps to preserve the life of system components.
- Anti-Recycle Timer will operate as circumstances occur during operation of unit:
• Temperature setting wheel is
adjusted back and forth.
ON/OFF switch is turned ON
and OFF.
• Room temperature reaches the
set point.
• Power failure.
Power Failure Recovery
- Saves settings during a power failure and restarts automatically when power resumes.
Freeze Protection
The system is protected against low indoor coil temperatures. Under certain conditions, the “COOL/DRY” LED will blink indicating the protective function has been activated. There is no need to adjust the system.
Stop The Air Conditioner At Once If Any Of The Following Occurs:
- The power cord is too hot to be touched by hand.
- The insulation of the power cord is exposed at any point.
- The fuse is blown or circuit breaker trips frequently.
- The functions of the switches are inaccurate.
System Operation
Operating Air Conditioner Safety
- Do not insert a bar or similar object into the supply air grille. In particular, advise small children not to insert anything in the grille.
- Do not pour water directly on the air conditioner to clean it. If the air conditioner is operating as wet, grounding may occur, damaging the unit.
- Adjust the air flow, so it does not blow directly on room occupants.
- Do not use flammable sprays near the air conditioner because of danger of fire.
- Do not use a steel or copper wire in place of fuses.
- Do not inspect or service the air conditioner while it is operating. Turn off the power supply before doing any inspection or service work.
- The power cord should be kept away from furniture with sharp corners. It may cause fire or electric shock.
- When the air conditioner will not used for a long time, be sure to turn OFF the power supply.
If you have any questions or problems with your air conditioning system, please consult your nearest Trane dealer.
Page 13
UNT-SVU001-EN
13
Note: Once the air filter is washed,
dry it completely before returning it to its original position. After cleaning, be sure to return it to its original position.
Cautions
- Do not wash the air filter in water that is over 400C or it may shrink.
- Do not expose the air filter to fire.
- Do not expose the air filter to direct sunlight for a long time.
- Clean the air filter more frequently when the air is very dirty.
Maintenance
Regular Maintenance
Be sure to disconnect the power before inspection or maintenance of air conditioner.
1. Cleaning the air filter
Air flow is reduced and cooling efficiency impaired if the filter is clogged. Be sure to clean the filter every two weeks during the cooling season.
1.1 How to remove the air filters
- Remove each return air grille by pushing down and pulling forward
- Remove each air filter frame from the return air grille
1.2 How to clean the air filter
Wash away dust from the air filter with clean water or vacuum it with an electric vacuum cleaner.
Pull
Pull
Pull Upward
2. Cleaning the front panel
Do not pour water directly on the front panel to clean it. Dust or wipe it lightly with a soft cloth. If it is very dirty, use a soft cloth soaked in water or neutral detergent.
Cautions
- Do not use water over 500C to clean the front panel or it may become discolored.
- Do not use benzine, gasoline, thinner, polishing compound, machine oil, etc. when cleaning the front panel, or paint may peel off, or it may become deformed or damaged.
3. Maintenance before prolonged idle period
- Operate the fan for about half a day to dry the inside of the unit.
- Stop the air conditioner and disconnect the power by turning off the safety breaker.
- Clean the air filter and return it to its original position.
- Place the protective cover over the condensing unit.
- Outdoor unit internal components must be cleaned periodically.
Page 14
14
UNT-SVU001-EN
Troubleshooting
Before calling for service, please check the following.
The air conditioner does not operate at all:
- Check if the control ON/OFF switch is “OFF”. Turn the switch to ON.
- Check whether the fuse has been blown or circuit breaker thrown. Set the ON/OFF Control Switch to OFF, and turn on the circuit breaker or replace to a new fuse.
- Check whether the power supply is interrupted. Wait until the power is resupplied and then operate the air conditioner.
Cooling is insufficient:
- Check whether the air filter is clogged. Clean it.
- Check whether the thermostat setting is too high. Set the thermostat to lower temperature.
- Check whether windows or doors are opened. If opened, close it.
- Check whether there are sources of heat in the room, cooling is less effective.
- Check whether the return air inlet or the supply air outlet on the indoor unit and outdoor unit are blocked. If they are blocked, remove obstacles to make air passage clear.
- Check whether the fan speed is set at low. Set the fan switch from “LOW” to “MED” or “HIGH”
Heating is insufficient:
- Check to see if the air filters are clogged with dust or debris. Clean the air filters.
- Check to see if the thermostat setting is too low. Set the thermostat a higher temperature.
- Check to see if windows or doors are open. If they are open, close.
- Check to see if the return air inlet or the supply air outlet on the indoor unit are blocked. If they are blocked, remove obstacles to permit air passage properly.
- Check to see if the fan speed is set at low setting. Set the fan switch from “LOW” to “MED” or “HIGH”
Page 15
UNT-SVU001-EN
15
Notes
Page 16
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specifications without notice.
Trane Thailand 7 th Floor, Ploenchit Center Building 2 Sukhumvit Road, Klongtoey Bangkok 10110
http://www.trane.com An American Standard Company
Literature Order Number UNT-SVU001-EN Supersedes CFEA-OWN-1 0196 Stocking Location Bangkok, Thailand
Loading...