Product Catalog
Variable Refrigerant Flow (VRF)
Air Source Heat Pump and Heat Recovery
Outdoor Units 4TVH*/4TVR*
February 2015
VRF-PRC008B-EN
Page 2
Trane® VRF variable refrigerant systems are efficient, effective, reliable heating and cooling
solutions you can trust. When VRF is the right solution for your application, Trane® will help you ensure it's the best solution. VRF is well suited for historic buildings without existing ductwork, as well as schools and mid-rise office buildings with multiple interior spaces and diverse occupancy rates.
Trane® VRF systems are designed for exceptional energy efficiency, offering industry leading
performance up to 33 IEER and 32 SCHE.Trane® VRF utilizes inverter compressors (some model feature dual compressors) with vapor injection for improved performance and comfort.
Systems are available for both heat pump and simultaneous heating and cooling operation. Both feature individual zone control to provide individual occupant comfort.The simultaneous heating and cooling models offer the ability to heat and cool adjacent zones, intelligently exchanging energy between them through strategically located mode control units.
Indoor units are available in a wide variety of configurations and capacities, allowing architects the flexibility to satisfy almost any design requirement.
Trane® offers a complete line-up of controls to complete your VRF installation.These range from
easy to use individual zone controls, to centralized systems for building monitoring and control, as well as optional BACnet® connectivity for centralizedTrane® Tracer™ integration.
Best of all, yourTrane®VRF™ system is supported by theTrane® nationwide network of sales and service offices.
Copyright
This document and the information in it are the property ofTrane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
VRF-PRC008B-EN (17 February 2015)
AHRI-1230 ratings updated and now include larger capacity systems previously not covered.
Low ambient heating range expanded from -4°F to -13°F.
© 2015Trane All rights reserved VRF-PRC008B-EN
Page 3

Table of Contents

Introduction ......................................................2
Table of Contents ..................................................3
System Features ................................................ 4
Model Number Descriptions .........................................5
Products .........................................................6
Controls .........................................................7
Accessories .......................................................8
Product Specifications .............................................10
Outdoor Units ................................................. 10
Operation Limit - Outdoor Units .....................................30
Defrosting Correction Factor ..................................... 31
Electrical Wiring Diagrams - Outdoor Units ...........................32
Sound Levels - Outdoor Units ......................................38
NC Curves .................................................... 38
Sound Power .................................................. 40
NR Curves .................................................... 40
Cycle Diagrams ..................................................42
Parts of Outdoor Unit (HP) ....................................... 42
Parts of Outdoor Unit (HR) ....................................... 45
Dimensional Drawings ............................................48
Heat Pump/Heat Recovery ....................................... 48
VRF-PRC008B-EN 3
Page 4

System Features

Individual modules are available as standard heat pump or simultaneous heating and cooling (heat recovery) configuration; units can be combined as double or triple modules for larger capacity requirements.
3rd generation compressor technology features all inverter compressors for superior efficiency and reliability
Asymmetric scroll is designed to minimize frictional loss
Dual inverter compressors (available in many models) are designed to equally share load for higher reliability
Improved vapor injection system increases refrigerant flow rate up to 20% for superior heating performance
Intercooler uses a plate heat exchanger for improved heating and cooling efficiency
8,400 RPM (maximum speed) compressor assures quick start cooling and heating performance
Auto oil balancing eliminates the need for an oil balancing pipe
Compressor inverter drives are liquid cooled for improved reliability
Longer pipe lengths are the result of large oil storage capacity and low oil circulation rate
Total harmonic distortion is reduced through adaptive sine wave control
Refrigerant pump down and pump out facilitates maintenance and repair
Automatic refrigerant balancing between indoor units optimize refrigerant distribution for better comfort and performance
Optional quiet operation mode for reduced sound levels at night
Auto snow blowing function removes accumulated snow when conditions require it
Special hydrophilic heat exchanger coating minimizes frost build up on the outdoor coils and facilitates the defrost cycle.
Anti-corrosion finish provides added protection in harsh environments
Four and six port mode control units are light and compact. Distributed installation flexibility provides superior performance during simultaneous heating and cooling operation.
Trane® VRF systems feature self-diagnosis, including system monitoring and error code reporting
4 VRF-PRC008B-EN
Page 5

Model Number Descriptions

4TVR0096B300NB
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Digit 1 — Refrigerant
4 = R-410A
Digit 2 — Brand Name
T = Trane
Digit3—SystemType
V = Variable Refrigerant Flow
Digit4—FunctionalType Outdoor Unit
H = Heat Pump, DC Inverter (VRF) R = Heat Recovery (three pipe), DC
Inverter
Digit 5 — Special Application
0 = Standard
Digit 6,7,8 — Nominal Capacity
Important: Btuh x1,000
072 = 72,000 Btuh 096 = 96,000 Btuh 120 = 120,000 Btuh 144 = 144,000 Btuh
Digit 9 — Major Development Sequence
B = Second Development Sequence
Digit 10 — Electric Power Supply Characteristics
3 = 208–230/60/3 4 = 460/60/3
Digit 11 — Reserved for Future Use
0 = Not currently used
Digit 12 — Reserved for Future Use
0 = Not currently used
Digit 13 — Region of Sale
N = North America (UL or ETL)
Digit 14 — Minor Design Sequence
B = Second Design Sequence
System Combination Line-up
Single
Module
Double Module
Triple
Module
Tons 4TVH/R0072B 4TVH/R0096B 4TVH/R0120B 4TVH/R0144B
61
81 10 1 12 1 14 1 1 16 1 1 18 1 1 20 2 22 1 1 24 2 26 1 1 1 28 1 1 1 30 1 2 32 2 1 34 1 2 36 3
VRF-PRC008B-EN 5
Page 6

Products

Table 1. Application matrix
7.5
MBh
Type
Slim one
way
cassette
XXX
9.0
MBh
9.5
MBh
12
MBh
18
MBh
20
MBh
Capacity
24
MBh
30
MBh
36
MBh42MBh
48
MBh60MBh
76.8 MBh
96
MBh
Four way
cassette
Mini four
way
cassette
Slim duct
MSP duct
HSP duct
Ceiling
High Wall
Convertible
AHU
XXXXXXX
XXXX
X XXX XXX X
X XXX X
XXXX
XX
X XXXXX
XXXXXX
6 VRF-PRC008B-EN
Page 7

Controls

Table 2. Controls for VRF Products
Family Description Model Number
Zone Controllers
Centralized Control Systems
Integrated System Management
VRF Simple Wired Remote Control TVCTRLWR001T
VRF Duct Signal Receiver & Wire TVCTRLTRKA10N0
VRF Enterprise Management Software TVCTRLTSTP3P00
VRF Power Meter Interface Mod. TVCTRLTIMB16A0
Controls
VRF Wireless Remote Control TVCTRLTRDH00UT
VRF Wired Remote Control TVCTRLTWRWD01T
VRF Central On/Off Control TVCTRLTCMA202D
VRF Touch Screen Control TVCTRLTCMA300T
VRF Mode Select Switch TVCTRLTCMC2000
VRF System Controller TVCTRLTIMD00A0
Building Management System
Gateways
Interface Modules
Sensors
Commissioning and Utility Kits
VRF System Controller + BACnet TVCTRLTIMB17A0
VRF System Controller + LonTalk™ TVCTRLTIMB18A0
VRF External Contact Interface Module TVCTRLTIMB14A0
VRF Multi Function Control TVCTRLTC210N00
VRF MFC Enclosure TVCTRLTC210BOX
Required control box for 4TVM air
handling unit
VRF Ext. Room Temp Sensor TVCTRLTRWTA000
VRF Motion Sensor Mini 4Way MOTIONSEN4TVB
VRF Technician Utilities Tool TVCTRLTIMC0300
VRF Auto-Commissioning Tool TVCTRLTIMC1000
4TVCTRLAU001
VRF-PRC008B-EN 7
Page 8

Accessories

Accessories
Table 3. Accessories forVRF Products
Family Description Model Number
VRF Y-joint <51MBh 4YDK1509B0051A
VRF Y-joint 51-138MBh 4YDK2512B0138A VRF Y-joint 138-160MBh 4YDK2812B0160A VRF Y-joint 160-240MBh 4YDK2815B0240A VRF Y-joint 240-336MBh 4YDK3419B0336A VRF Y-joint 336-468MBh 4YDK4119B0468A
VRF Y-joint >468MBh 4YDK4422B0999A
Refrigeration Joints
Header Joints
EEV Kits (For Floor/Ceiling and Selected High
Wall Indoor Units
VRF Y-joint HR <80MBh 4YDK1500B0080A
VRF Y-joint HR 80-240MBh 4YDK2500B0240A
VRF Y-joint HR 240-468MBh 4YDK3100B0468A
VRF Y-joint HR >468MBh 4YDK3800B0999A
VRF T-joint >468MBh 4TDK3800B0999A VRF T-joint <468MBh 4TDK3819B0000A
VRF T-joint HR <468MBh 4TDK3100B0000A VRF T-joint HR >468MBh 4TDK4422B0999A
VRF Header Joint 4Units<160MBh 4HJK2512B0159A
VRF Header Joint 8Units 240MBh 4HJK3115B0241A
VRF Header Joint 8Units<160MBh 4HJK3819B0998A
VRF EEV Kit 1Unit 7-15.5MBh 4EEVEVA24SA000
VRF EEV Kit 1Unit 17-31MBh 4EEVEVA32SA000
VRF EEV 1x 7-15.5& 1x 17-31MBh 4EEVXDA24K132A
VRF EEV Kit 2Unit 7-15.5MBh 4EEVXDA24K200A
VRF EEV 2x 7-15.5& 1x 17-31MBh 4EEVXDA24K232A
VRF EEV Kit 2Unit 17-31MBh 4EEVXDA32K200A
VRF EEV 1x 7-15.5& 2x 17-31MBh 4EEVXDA32K224A
VRF EEV Kit 3Unit 7-15.5MBh 4EEVXDA24K300A
VRF EEV Kit 3Unit 17-31MBh 4EEVXDA32K300A
VRF AHU Kit 24-30MBh 4EEVAKA40K1025
AHU Kits
VRF AHU Kit 48-60MBh 4EEVAKA40K1050
VRF AHU Kit 72-90MBh 4EEVAKA64K1075 VRF AHU Kit 96-112MBh 4EEVAKA64K1100
8 VRF-PRC008B-EN
Page 9
Table 3. Accessories forVRF Products (continued)
Family Description Model Number
VRF Drain Pump High Wall and Floor/Ceiling CONDPUMPAHWB01
VRF Drain Pump Slim Duct CONDPUMPXVLB01
Condensate Pumps
VRF Drain Pump MSP 18/24MBh CONDPUMPXVMB01 VRF Drain Pump MSP 30/36MBh CONDPUMPXVMB02
VRF Drain Pump MSP48/ HSP3648MBh CONDPUMPXVDB01
VRF Drain Pump HSP 76.8/96MBh CONDPUMPXVHB01
Accessories
Mode Control Units (for Simultaneous
Heating and Cooling Applications)
Ball Valves
Cassette Panels
Pressure Differential Module (for high rise
applications)
Hail Guards
VRF MCU Kit up to 4 IDU 4MCUCUY4NCE000 VRF MCU Kit up to 6 IDU 4MCUCUY6NCE000
VRF MCU Kit 2 IDU 36 MBh + 4MCUCUY2NCE000
1/2" Ball Valve Flare BVALVE12FLARE1 1/4" Ball Valve Flare BVALVE14FLARE1 3/8" Ball Valve Flare BVALVE38FLARE1 5/8" Ball Valve Flare BVALVE58FLARE1
VRF Cass. Panel Sliding 1Way TVEPANPC1NUAET
VRF Cass. Panel Slim 1Way TVEPANPC1NUSET
VRF Cass. Panel 4Way TVEPANPC4NUSET
VRF Cass. Panel Mini 4Way TVEPANPC4SUSET
Pressure Diff Module 6/8/10 Ton MXD-A12K2A
Pressure Diff Module 12 Ton MXD-A38K2A
Hail Guard 4TVH/TVR0072B TVRGARD001A
Hail Guard 4TVH/TVR0096-0144B TVRGARD002A
Hail Guard 4TVH0036-0053B TVRGARD003A
VRF-PRC008B-EN 9
Page 10

Product Specifications

Outdoor Units

Table 4. 208-230V Heat Pump Single Modules
Power Supply
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
(a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. (If the height difference exceeds
164 ft., request engineering support from T rane). If the outdoor unit is installed below the below the indoor units, the allowa ble height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
Model Name 4TVH0072B300NB 4TVH0096B300NB 4TVH0120B300NB 4TVH0144B300NB
Nominal Tons System Type
Capacity
(Nominal)
Capacity
(Rated)
AHRI -1230
Efficiency
Ratings
MCA MOP SCCR Type (Qty.) Model Name
Output Oil Type
Initial Charge Type (Qty.) Output (Each) Airflow Rate External Static Pressure Liquid Pipe Gas Pipe High Pressure Gas Pipe (For HR)
Installation Limits
Number Of Connectable Indoor Units
Total Capacity Type Factory Charge Sound Pressure Sound Power Net Weight Shipping Weight Net Dimensions (WXHXD) Shipping Dimensions (WXHXD) Cooling Heating
Cooling
(a)
Heating Cooling High Temp
(b)
Heating Low T emp Heating EER IEER COP @ 47°F
(b)
COP @ 17°F SCHE
Max Length Max Height
(c)
(d)
Btuh Btuh Btuh
Btuh Btuh
-
-
-
-
­A 28 37.8 43 52.6 A35 50 50 70
kA - - - 5.0
- SSC SCROLL (1) SSC SCROLL (2) SSC SCROLL (2) SSC SCROLL (2)
- DS-GB052FBVASG DS-GB052FBVASG (2) DS-GB052FBVASG (2) DS-GB052FBVASG (2)
kW
each
- PVE PVE PVE PVE
fl. oz. 77.8 155.5 155.5 155.5
- Propeller (1) Propeller (2) Propeller (2) Propeller (2)
W 400 620 620 620
CFM 7,240 9,180 9,180 9,535
In. WG 0.31 0.31 0.31 0.31
Ø inch 3/8" Braze 3/8" Braze 1/2" Braze 1/2" Braze Ø inch 3/4" Braze 7/8" Braze 1 1/8" Braze 1 1/8" Braze Ø inch N/A N/A N/A N/A
ft. 656 (722) 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131) 361 (131)
-12 16 20 25
- 50 To 130% Of Total Outdoor Unit Capacity
- R-410A R-410A R-410A R-410A
lbs. 12.1 16.3 16.3 19.18 dB(A) 60.0 61.0 61.0 62.0 dB(A) 81 81 81 83
lbs. 425 624 624 657
lbs. 461 666 666 699
inches inches
°F 23 ~ 120 23 ~ 120 23 ~ 120 23 ~ 120 °F -13 ~ 75 -13 ~ 75 -13 ~ 75 -13 ~ 75
208-230/60/3 208-230/60/3 208-230/60/3 208-230/60/3
6.0 8.0 10.0 12.0
Ducted Non-ducted Ducted Non-ducted Ducted Non-ducted Ducted Non-ducted 72,000 72,000 96,000 96,000 120,000 120,000 144,000 144,000
81,000 81,000 108,000 108,000 135,000 135,000 162,000 162,000 69,000 69,000 92,000 92,000 114,000 114,000 138,000 138,000
77,000 77,000 103,000 103,000 129,000 129,000 154,000 154,000 51,000 51,000 67,000 67,000 84,000 84,000 100,000 100,000
11.50 12.90 11.60 13.80 11.10 12.50 10.80 11.20
22.50 33.00 23.00 31.00 21.80 26.70 21.10 24.50
3.46 4.15 3.60 4.23 3.43 3.97 3.54 3.64
2.49 2.75 2.47 2.90 2.45 2.62 2.23 2.40
--------
4.96 4.96 4.96 4.96
34.65 X 66.73 X 30.12 50.98 X 66.73 X 30,12 50.98 X 66.73 X 30,12 50.98 X 66.73 X 30.12
37.32 X 75.28 X 32.76 53.66 X 75.28 X 32.76 53.66 X 75.28 X 32.76 53.66 X 75.28 X 32.76
10 VRF-PRC008B-EN
Page 11
Product Specifications
Table 5. 208~230V Heat Pump Dual Modules I
Model Name 4TVH0168B300NB 4TVH0192B300NB 4TVH0216B300NB
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Nominal Tons 14.0 16.0 18.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A outdoor unit T-joint connection
(a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference; Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) ­Model Name ­Output kW each
Oil Type (Qty.) -
Output (Each) W Airflow Rate CFM External Static Pressure in. WG Liquid Pipe Ø inch Gas Pipe Ø inch High Pressure Gas Pipe (For HR) Ø inch
Installation Limits
Number Of Connectable Indoor Units ­Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A Factory Charge lbs. 28.4 28.4 31.3 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 425 + 624 425 + 624 425 + 657 Shipping Weight lbs. 461 + 666 461 + 666 461 + 699
Net Dimensions (WXHXD) inches Shipping Dimensions (WXHXD) inches
Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 168,000 168,000 192,000 192,000 216,000 216,000
(a)
Heating Btuh 189,000 189,000 216,000 216,000 243,000 243,000 Cooling Btuh 160,000 160,000 184,000 183,000 206,000 206,000 High Temp Heating Btuh 180,000 180,000 206,000 206,000 230,000 230,000
(b)
Low Temp Heating Btuh 118,000 118,000 134,000 134,000 150,000 150,000 EER - 11.40 12.10 10.90 11.40 10.60 10.80 IEER - 20.80 25.90 21.50 24.10 20.50 22.40 COP @ 47°F - 3.46 3.94 3.34 3.83 3.34 3.63
(b)
COP @ 17°F - 2.43 2.65 2.42 2.59 2.31 2.52 SCHE - - - - - - -
Type ­Initial Charge fl. oz.
Max Length Max Height
(c)
(d)
4TVH0072B300NB +
4TVH0096B300NB
Each individual outdoor unit requires a separate electrical connection.
SSC Scroll (3) SSC Scroll (3) SSC Scroll (3)
DS-GB052FBVASG x 3 DS-GB052FBVASG x 3 DS-GB052FBVASG x 3
4.96 x 3 4.96 x 3 4.96 x 3
Propeller (3) Propeller (3) Propeller (3)
400 + 620 x 2 400 + 620 x 2 400 + 620 x 2
7,240 + 9,180 7,240 + 9,180 7,240 + 9,535
5/8" Braze 5/8" Braze 5/8" Braze
1 1/8" Braze 1 1/8" Braze 1 1/8" Braze
ft. ft.
656 (722) 656 (722) 656 (722)
361 (131) 361 (131) 361 (131)
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
4TVH0072B300NB +
4TVH0120B300NB
Reference electrical data for each individual outdoor unit.
4TVH0072B300NB +
4TVH0144B300NB
PVE PVE PVE
233.3 233.3 233.3
0.31 0.31 0.31
N/A N/A N/A
29 33 37
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
VRF-PRC008B-EN 11
Page 12
Product Specifications
Table 6. 208~230V Heat Pump Dual Modules II
Model Name 4TVH0240B300NB 4TVH0264B300NB 4TVH0288B300NB
2x 4TVH0120B300NB
Power Supply
Nominal Tons System Type
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A outdoor unit T-joint connection (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) ­Model Name ­Output kW each
Oil Type (Qty.) -
Output (Each) W Airflow Rate CFM External Static Pressure in. WG Liquid Pipe Ø inch Gas Pipe Ø inch High Pressure Gas Pipe (For HR) Ø inch
Installation Limits
Number Of Connectable Indoor Units
Total Capacity ­Type ­Factory Charge lbs. Sound Pressure dB(A) Sound Power dB(A) Net Weight lbs. 624 x 2 624 + 657 657 x 2 Shipping Weight lbs. 699 x 2 665 + 699 699 x 2 Net Dimensions (WXHXD) inches (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 Shipping Dimensions (WXHXD) inches (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2 Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 240,000 240,000
(a)
Heating Btuh 270,000 270,000 Cooling Btuh 228,000 228,000 High T emp Heating Btuh 258,000 258,000
(b)
Low Temp Heating Btuh 168,000 168,000 EER - 10.60 11.10 IEER - 19.10 21.80 COP @ 47°F - 3.24 3.65
(b)
COP @ 17°F - 2.40 2.54 SCHE -
Type ­Initial Charge fl. oz.
Max Length Max Height
(c)
(d)
ft. ft.
-
208-230/60/3 208-230/60/3 208-230/60/3
20.0 22.0 24.0
Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
-----­28 37.8 43 35 50 50
---
SSC Scroll (1) SSC Scroll (2) SSC Scroll (2)
DS-GB052FBVASG DS-GB052FBVASG x 2 DS-GB052FBVASG x 2
4.96 x 4 4.96 x 4
PVE PVE
311.1 311.1
Propeller (4) Propeller (4)
620 x 4 620 x 4
9180 x 2 9,180 + 9,535
0.31 0.31
5/8" Braze 3/4" Braze
1 1/8" Braze 1 3/8" Braze
N/A N/A
656 (722) 656 (722)
361 (131) 361 (131)
41 45
50 to 130% of total outdoor unit cooling capacity
R410A R410A R410A
32.6 35.5 38.4
---
---
4TVH0120B300NB +
4TVH0144B300NB 2x 4TVH0144B300NB
264,000 264,000 288,000 288,000
297,000 297,000 324,000 324,000
252,000 252,000 276,000 276,000
282,000 282,000 308,000 308,000
184,000 184,000 200,000 200,000
10.10 10.50 10.00 9.50
18.60 21.50 18.60 21.00
3.25 3.45 3.25 3.26
2.26 2.41 2.12 2.29
4.96 x 4 PVE
311.1
Propeller (4)
620 x 4
9535 x 2
0.31
3/4" Braze
1 3/8" Braze
N/A
656 (722) 361 (131)
49
12 VRF-PRC008B-EN
Page 13
Product Specifications
Table 7. 208-230V Heat Pump Triple Modules I
Model Name 4TVH0312B300NB 4TVH0336B300NB 4TVH0360B300NB
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Nominal Tons 26.0 28.0 30.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires two 4TDK3819B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions (published ratings apply to systems 300,000 Btuh). (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft.. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (5) SSC Scroll (5) SSC Scroll (5) Model Name - DS-GB052FBVASG (5) DS-GB052FBVASG (5) DS-GB052FBVASG (5) Output kW each 4.96 x 5 4.96 x 5 4.96 x 5
Oil Type (Qty.) - Propeller (5) Propeller (5) Propeller (5)
Output (Each) W 400 + 620 x 4 400 + 620 x 4 400 + 620 x 4 Airflow Rate CFM 7,240 + 9,180 + 9,535 7,240 + 9,180 + 9,535 7,240 + (9,535 x2) External Static
Pressure Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 3/8" Braze 1 3/8" Braze 1 5/8" Braze High Pressure Gas
Pipe (For Hr) Installation Limits Number Of Connectable Indoor Units - 54 58 62
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 47.6 47.6 50.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 425 + 624 + 657 425 + 624 + 657 425 + (657 x2) Shipping Weight lbs. 461 + 666 + 699 461 + 666 + 699 461 + (699 x2)
Net Dimensions (WxHxD) inches Shipping Dimensions (WxHxD) inches
Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 312,000 312,000 336,000 336,000 360,000 360,000
(a)
Heating Btuh 351,000 351,000 378,000 378,000 405,000 405,000 Cooling Btuh 298,000 298,000 320,000 320,000 344,000 344,000 High T emp Heating Btuh 334,000 334,000 360,000 360,000 386,000 386,000
(b)
Low Temp Heating Btuh 218,000 218,000 234,000 234,000 250,000 250,000 EER - 10.30 10.50 10.00 10.20 9.80 9.80 IEER - 18.30 21.20 17.10 20.50 16.60 20.00 COP @ 47°F - 3.20 3.38 3.20 3.27 3.20 3.22
2
COP @ 17°F - 2.25 2.54 2.21 2.39 2.11 2.31 SCHE - - - - - - -
Type - PVE PVE PVE Initial Charge fl. oz. 388.9 388.9 388.9
in. WG 0.31 0.31 0.31
Ø inch N/A N/A N/A
Max Length Max Height
(c)
(d)
4TVH0072B300NB + 4TVH0096B300NB +
4TVH0144B300NB
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
4TVH0072B300NB + 4TVH0120B300NB +
4TVH0144B300NB
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
7.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
4TVH0072B300NB +
2x 4TVH0144B300NB
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
VRF-PRC008B-EN 13
Page 14
Product Specifications
Table 8. 208-230V Heat Pump Triple Modules II
Model Name 4TVH0384B300NB 4TVH0408B300NB 4TVH0432B300NB
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Nominal Tons 32.0 34.0 36.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating T emp Range
Note: Requires two 4TDK3819B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions (published ratings apply to systems 300,000 Btuh). (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (6) SSC Scroll (6) SSC Scroll (6) Model Name - DS-GB052FBVASG (6) DS-GB052FBVASG (6) DS-GB052FBVASG (6) Output kW each 4.96 x 6 4.96 x 6 4.96 x 6
Oil Type (Qty.) - Propeller (6) Propeller (6) Propeller (6)
Output (Each) W 620 x 6 620 x 6 620 x 6 Airflow Rate CFM (9,180 x2) + 9535 9,180 + (2x 9,535) 9535 x 3 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 5/8" Braze 1 5/8" Braze 1 5/8" Braze High Pressure Gas Pipe (For Hr) Ø inch N/A N/A N/A
Installation Limits
Number Of Connectable Indoor Units
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 51.8 54.7 57.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. (624 x 2) + 657 624 + (657 x2) 657 x 3 Shipping Weight lbs. (666 x2) + 699 666 + (699 x2) 699 x 3 Net Dimensions (WxHxD) inches (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 Shipping Dimensions (WxHxD) inches (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3 Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 384,000 384,000 408,000 408,000 432,000 432,000
(a)
Heating Btuh 432,000 432,000 459,000 459,000 486,000 486,000 Cooling Btuh 366,000 366,000 390,000 390,000 415,000 415,000 High Temp Heating Btuh 410,000 410,000 435,000 435,000 460,000 460,000
(b)
Low Temp Heating Btuh 268,000 268,000 284,000 284,000 300,000 300,000 EER - 9.50 9.50 9.50 9.50 9.50 9.50 IEER - 16.50 19.50 16.40 19.10 16.30 19.10 COP @ 47°F - 3.20 3.20 3.20 3.20 3.20 3.20
(b)
COP @ 17°F - 2.05 2.10 2.05 2.05 2.05 2.05 SCHE - - - - - - -
Type - PVE PVE PVE Initial Charge fl. oz. 466.6 466.6 466.6
Max Length Max Height
(c)
(d)
2x 4TVH0120B300NB +
4TVH0144B300NB
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
-64 64 64
4TVH0120B300NB + 2x 4TVH0144B300NB 3x 4TVH0144B300NB
14 VRF-PRC008B-EN
Page 15
Product Specifications
Table 9. 208-230V Heat Recovery Single Modules
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
(a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
Model Name 4TVR0072B300NB 4TVR0096B300NB 4TVR0120B300NB 4TVR0144B300NB
Nominal Tons 6.0 8.0 10.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
(a)
(b)
(b)
(f)
Cooling Heating Cooling High Temp
Heating Low Temp
Heating EER IEER COP @ 47°F COP @ 17°F SCHE
Type Initial Charge
Max Length Max Height
Capacity
(Nominal)
Capacity
(Rated)
AHRI -1230
Efficiency
Ratings
MCA MOP SCCR Type (Qty.) Model Name Output
Oil Type (Qty.)
Output (Each) Airflow Rate External Static Pressure Liquid Pipe Gas Pipe High Pressure Gas Pipe (For
Hr) Installation
Limits Number Of Connectable
Indoor Units Total Capacity Type Factory Charge Sound Pressure Sound Power Net Weight Shipping Weight Net Dimensions (WxHxD) Shipping Dimensions
(WxHxD) Cooling Heating
kW each
fl. oz.
in. WG Ø inch Ø inch Ø inch
(c)
(d)
dB(A) dB(A)
inches inches
72,000 72,000 96,000 96,000 120,000 120,000 144,000 144,000
Btuh
81,000 81,000 108,000 108,000 135,000 135,000 162,000 162,000
Btuh
69,000 69,000 92,000 92,000 114,000 114,000 138,000 138,000
Btuh Btuh
77,000 77,000 103,000 103,000 129,000 129,000 154,000 154,000
Btuh
51,000 51,000 67,000 67,000 84,000 84,000 100,000 100,000
11.50 12.90 11.60 13.80 11.10 12.50 10.80 11.20
-
22.50 33.00 23.00 31.00 21.80 26.70 21.10 24.50
-
3.46 4.15 3.60 4.23 3.43 3.97 3.54 3.64
-
2.49 2.75 2.47 2.90 2.45 2.62 2.23 2.40
-
26.00 28.00 26.50 32.00 25.50 31.00 25.00 27.50
­A A
kA
-
-
-
-
W
CFM
ft. ft.
-
-
-
lbs.
lbs. lbs.
34.65 x 66.73 x 30.12 50.98 x 66.73 x 30,12 50.98 x 66.73 x 30,12 50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 53.66 x 75.28 x 32.76 53.66 x 75.28 x 32.76 53.66 x 75.28 x 32.76
°F °F
28 37.8 43 52.6 35 50 50 70
- - - 5.0
SSC Scroll (1) SSC Scroll (2) SSC Scroll (2)
DS-GB052FBVASG DS-GB052FBVASG x 2 DS-GB052FBVASG x 2 DS-GB052FBVASG x 2
4.96 4.96 x 2 4.96 x 2 4.96 x 2 PVE PVE PVE PVE
77.8 155.5 155.5 155.5
Propeller (1) Propeller (2) Propeller (2) Propeller (2)
400 620 620 620
7,240 9,180 9,180 9,535
0.31 0.31 0.31 0.31
3/8" Braze 3/8" Braze 1/2" Braze 1/2" Braze 3/4" Braze 7/8" Braze 1 1/8" Braze 1 1/8" Braze
5/8" Braze 3/4" Braze 7/8" Braze 7/8" Braze
656 (722) 656 (722) 656 (722) 656 (722) 361 (131) 361 (131) 361 (131) 361 (131)
12 16 20 25
50 to 130% of total outdoor unit capacity
R410A R410A R410A R410A
12.1 16.3 16.3 19.18
60.0 61.0 61.0 62.0
81 81 81 83 430 637 637 672 465 679 679 714
5 ~ 120 5 ~ 120 5 ~ 120 5 ~ 120
-13 ~ 75 -13 ~ 75 -13 ~ 75 -13 ~ 75
208-230/60/3
12.0
Ducted Non-Ducted
SSC Scroll (2)
VRF-PRC008B-EN 15
Page 16
Product Specifications
Table 10. 208-230V Heat Recovery Dual Modules I
Model Name 4TVR0168B300NB 4TVR0192B300NB 4TVR0216B300NB
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Nominal Tons 14.0 16.0 18.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (3) SSC Scroll (3) SSC Scroll (3) Model Name - DS-GB052FBVASG x 3 DS-GB052FBVASG x 3 DS-GB052FBVASG x 3 Output kW each 4.96 x 3 4.96 x 3 4.96 x 3
Oil Type (Qty.) - Propeller (3) Propeller (3) Propeller (3)
Output (Each) W 400 + 620 x 2 400 + 620 x 2 400 + 620 x 2 Airflow Rate CFM 7,240 + 9,180 7,240 + 9,180 7,240 + 9,535 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 5/8" Braze 5/8" Braze 5/8" Braze Gas Pipe Ø inch 1 1/8" Braze 1 1/8" Braze 1 1/8" Braze High Pressure Gas Pipe (For Hr) Ø inch 7/8" Braze 1 1/8" Braze 1 1/8" Braze
Installation Limits Number Of Connectable Indoor Units - 29 33 37
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 28.4 28.4 31.3 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 430 + 637 430 + 637 430 + 672 Shipping Weight lbs. 465 + 479 465 + 479 465 + 714
Net Dimensions (WxHxD) inches Shipping Dimensions (WxHxD) inches
(f)
Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh
(a)
Heating Btuh Cooling Btuh High Temp Heating Btuh
(b)
Low Temp Heating Btuh EER ­IEER ­COP @ 47°F -
(b)
COP @ 17°F ­SCHE -
Type - PVE PVE PVE Initial Charge fl. oz. 233.3 233.3 233.3
Max Length Max Height
(c)
(d)
4TVR0072B300NB +
4TVR0096B300NB
4TVR0072B300NB +
4TVR0120B300NB
4TVR0072B300NB +
4TVR0144B300NB
168,000 168,000 192,000 192,000 216,000 216,000 189,000 189,000 216,000 216,000 243,000 243,000 160,000 160,000 184,000 184,000 206,000 206,000 180,000 180,000 206,000 206,000 230,000 230,000 118,000 118,000 134,000 134,000 150,000 150,000
11.40 12.10 10.90 11.40 10.60 10.80
20.80 25.90 21.50 24.10 20.50 22.40
3.46 3.94 3.34 3.83 3.34 3.63
2.43 2.65 2.42 2.59 2.31 2.52
23.50 27.00 23.50 26.50 23.00 25.50
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
°F 5 ~ 120 5 ~ 120 5 ~ 120
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
16 VRF-PRC008B-EN
Page 17
Product Specifications
Table 11. 208~230V Heat Recovery Dual Modules II
Model Name 4TVR0240B300NB 4TVR0264B300NB 4TVR0288B300NB
2x 4TVR0120B300NB
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Nominal Tons 20.0 22.0 24.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (4) SSC Scroll (4) SSC Scroll (4) Model Name - DS-GB052FBVASG x 4 DS-GB052FBVASG x 4 DS-GB052FBVASG x 4 Output kW each 4.96 x 4 4.96 x 4 4.96 x 4
Oil Type (Qty.) - Propeller (4) Propeller (4) Propeller (4)
Output (Each) W 620 x 4 620 x 4 620 x 4 Airflow Rate CFM 9180 x 2 9,180 + 9,535 9535 x 2 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 5/8" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 1/8" Braze 1 3/8" Braze 1 3/8" Braze High Pressure Gas Pipe (For Hr) Ø inch 1 1/8" Braze 1 1/8" Braze 1 1/8" Braze
Installation Limits
Number Of Connectable Indoor Units - 41 45 49 Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R410A R410A Factory Charge lbs. 32.6 32.6 35.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 637 x 2 637 x 2 637 + 672 Shipping Weight lbs. 714 x 2 679 x 2 679 + 714 Net Dimensions (WxHxD) inches (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 Shipping Dimensions (WxHxD) inches (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2 Cooling Heating °F -4 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 240,000 240,000 264,000 264,000 288,000 288,000
(a)
Heating Btuh 270,000 270,000 297,000 297,000 324,000 324,000 Cooling Btuh 228,000 228,000 252,000 252,000 276,000 276,000 High Temp Heating Btuh 258,000 258,000 282,000 282,000 308,000 308,000
(b)
Low Temp Heating Btuh 168,000 168,000 184,000 184,000 200,000 200,000 EER - 10.60 11.10 10.10 10.50 10.00 9.50 IEER - 19.10 21.80 18.60 21.50 18.60 21.00 COP @ 47°F - 3.24 3.65 3.25 3.45 3.25 3.26
(b)
COP @ 17°F - 2.40 2.54 2.26 2.41 2.12 2.29 SCHE - 22.50 25.50 22.00 24.50 21.50 23.50
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
Type - PVE PVE PVE Initial Charge fl. oz. 311.1 311.1 311.1
(f)
Max Length Max Height
(c)
(d)
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
°F 23 ~ 120 5 ~ 120 5 ~ 120
4TVR0120B300NB +
4TVR0144B300NB 2x 4TVR0144B300NB
VRF-PRC008B-EN 17
Page 18
Product Specifications
Table 12. 208-230V Heat Recovery Triple Modules I
Model Name 4TVR0312B300NB 4TVR0336B300NB 4TVR0360B300NB
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Nominal Tons 26.0 28.0 30.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires two each 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a) Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions (published ratings apply to systems 300,000 Btuh). (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (5) SSC Scroll (5) SSC Scroll (5) Model Name - DS-GB052FBVASG x 5 DS-GB052FBVASG x 5 DS-GB052FBVASG x 5
Output
Oil Type (Qty.) - Propeller (5) Propeller (5) Propeller (5)
Output (Each) W 400 + 620 x 4 400 + 620 x 4 400 + 620 x 4 Airflow Rate CFM 7,240 + 9,180 + 9,535 7,240 + 9,180 + 9,535 7,240 + (9,535 x2) External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 3/8" Braze 1 3/8" Braze 1 5/8" Braze High Pressure Gas Pipe (For Hr) Ø inch 1 1/8" Braze 1 1/8" Braze 1 3/8" Braze
Installation Limits Number Of Connectable Indoor Units -
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 47.6 47.6 50.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 430 + 637 + 672 430 + 637 + 672 430 + (672 x 2) Shipping Weight lbs. 465 + 679 + 714 465 + 679 + 714 465 + (714 x 2)
Net Dimensions (WxHxD) inches
Shipping Dimensions (WxHxD) inches
(f)
Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 312,000 312,000 336,000 336,000 360,000 360,000
(a)
Heating Btuh 351,000 351,000 378,000 378,000 405,000 405,000 Cooling Btuh 298,000 298,000 320,000 320,000 344,000 344,000 High Temp Heating Btuh 334,000 334,000 360,000 360,000 386,000 386,000
(b)
Low Temp Heating Btuh 218,000 218,000 234,000 234,000 250,000 250,000 EER - 10.30 10.50 10.00 10.20 9.80 9.80 IEER - 18.30 21.20 17.10 20.50 16.60 20.00 COP @ 47°F - 3.20 3.38 3.20 3.27 3.20 3.22
(b)
COP @ 17°F - 2.25 2.54 2.21 2.39 2.11 2.31 SCHE - 20.50 23.50 20.50 23.10 20.00 22.40
Type - PVE PVE PVE Initial Charge fl. oz. 388.9 388.9 388.9
Max Length Max Height
(c)
(d)
4TVR0072B300NB + 4TVR0096B300NB +
4TVR0144B300NB
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
kW
each
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
4.96 x 5 4.96 x 5 4.96 x 5
4TVR0072B300NB + 4TVR0120B300NB +
4TVR0144B300NB
4TVR0072B300NB + 2x 4TVR0144B300NB
54 58 62
34.65 x 66.73 x 30.12
+(50.98 x 66.73 x 30.12)
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
°F 5 ~ 120 5 ~ 120 5 ~ 120
x2
34.65 x 66.73 x 30.12
+(50.98 x 66.73 x 30.12)
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
x2
34.65 x 66.73 x 30.12
+(50.98 x 66.73 x 30.12)
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
x2
18 VRF-PRC008B-EN
Page 19
Product Specifications
Table 13. 208-230V Heat Recovery Triple Modules II
Model Name 4TVR0384B300NB 4TVR0408B300NB 4TVR0432B300NB
Power Supply 208-230/60/3 208-230/60/3 208-230/60/3
Nominal Tons 32.0 34.0 36.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires two each 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b) Rated per AHRI-1230 Standard conditions (published ratings apply to systems (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (6) SSC Scroll (6) SSC Scroll (6) Model Name - DS-GB052FBVASG x 6 DS-GB052FBVASG x 6 DS-GB052FBVASG x 6 Output kW each 4.96 x 6 4.96 x 6 4.96 x 6
Oil Type (Qty.) - Propeller (6) Propeller (6) Propeller (6)
Output (Each) W 620 x 6 620 x 6 620 x 6 Airflow Rate CFM (9,180 x2) + 9535 9,180 + (2x 9,535) 9535 x 3 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 5/8" Braze 1 5/8" Braze 1 5/8" Braze High Pressure Gas Pipe (For Hr) Ø inch 1 3/8" Braze 1 3/8" Braze 1 3/8" Braze
Installation Limits Number Of Connectable Indoor Units -
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 51.8 54.7 57.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. (637 x 2) + 672 (637 x 2) + 672 672 x 2 Shipping Weight lbs. (679 x 2) + 714 (679 x2) + 714 714 x 2 Net Dimensions (WxHxD) inches (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 Shipping Dimensions (WxHxD) inches (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3
(f)
Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 384,000 384,000 408,000 408,000 432,000 432,000
(a)
Heating Btuh 432,000 432,000 459,000 459,000 486,000 486,000 Cooling Btuh 366,000 366,000 390,000 390,000 415,000 415,000 High T emp Heating Btuh 410,000 410,000 435,000 435,000 460,000 460,000
(b)
Low Temp Heating Btuh 268,000 268,000 284,000 284,000 300,000 300,000 EER - 9.50 9.50 9.50 9.50 9.50 9.50 IEER - 16.50 19.50 16.40 19.10 16.30 19.10 COP @ 47°F - 3.20 3.20 3.20 3.20 3.20 3.20
(b)
COP @ 17°F - 2.05 2.10 2.05 2.05 2.05 2.05 SCHE - 16.50 23.00 19.00 22.00 19.00 21.50
Type - PVE PVE PVE Initial Charge fl. oz. 466.6 466.6 466.6
Max Length Max Height
(c)
(d)
2x 4TVR0120B300NB
+ 4TVR0144B300NB
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
4TVR0120B300NB + 2x 4TVR0144B300NB 3x 4TVR0144B300NB
64 64 64
°F 5 ~ 120 5 ~ 120 5 ~ 120
< 300,000 Btuh).
VRF-PRC008B-EN 19
Page 20
Product Specifications
Table 14. 460V Heat Pump Single Modules
Power Supply 460/60/3 460/60/3 460/60/3 460/60/3
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
(a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
Model Name 4TVH0072B400NB 4TVH0096B400NB 4TVH0120B400NB 4TVH0144B400NB
Nominal Tons 6.0 8.0 10.0 12.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A 16.4 19 21.7 26.4 MOP A 20 25 30 40 SCCR kA ­Type (Qty.) - SSC Scroll (1) SSC Scroll (1) SSC Scroll (1) SSC Scroll (2) Model Name - DS-GB052FAVASG DS-GB066FAVASG DS-GB066FAVASG DS-GB052FAVASG Output kW 4.96 6.13 6.13 4.96 x 2
Oil Type (Qty.) - Propeller (1) Propeller (2) Propeller (2) Propeller (2)
Output (Each) W 400 620 620 620 Airflow Rate CFM 7,240 9,180 9,180 9,535 External Static Pressure in. WG 0.31 0.31 0.31 0.31 Liquid Pipe Ø inch 3/8" Braze 3/8" Braze 1/2" Braze 1/2" Braze Gas Pipe Ø inch 3/4" Braze 7/8" Braze 1 1/8" Braze 1 1/8" Braze High Pressure Gas Pipe (For
HR) Installation
Limits Number Of Connectable
Indoor Units Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A R-410A Factory Charge lbs. 12.1 16.3 16.3 19.18 Sound Pressure dB(A) 60.0 61.0 61.0 62.0 Sound Power dB(A) 81 81 81 83 Net Weight lbs. 437 540 540 672 Shipping Weight lbs. 472 582 582 714 Net Dimensions (WxHxD) inches 34.65 x 66.73 x 30.12 50.98 x 66.73 x 30,12 50.98 x 66.73 x 30,12 50.98 x 66.73 x 30.12 Shipping Dimensions
(WxHxD) Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 72,000 72,000 96,000 96,000 120,000 120,000 144,000 144,000 Heating Btuh 81,000 81,000 108,000 108,000 135,000 135,000 162,000 162,000
(a)
Cooling Btuh 69,000 69,000 92,000 92,000 114,000 114,000 138,000 138,000 High Temp
Heating
(b)
Low Temp Heating
EER - 11.50 12.90 11.50 13.90 11.10 12.40 10.80 11.20 IEER - 22.50 33.00 22.40 29.60 21.20 27.10 21.10 24.50 COP @ 47°F - 3.46 4.15 3.56 4.23 3.43 3.97 3.54 3.64
(b)
COP @ 17°F - 2.49 2.75 2.45 2.81 2.44 2.53 2.23 2.40 SCHE - - - - - - - - -
Type - PVE PVE PVE PVE Initial Charge fl. oz. 77.8 77.8 77.8 155.5
Max Length Max Height
Btuh 77,000 77,000 103,000 103,000 129,000 129,000 154,000 154,000 Btuh 51,000 51,000 67,000 67,000 84,000 84,000 100,000 100,000
---
Ø inch N/A N/A N/A N/A
(c)
(d)
ft. 656 (722) 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131) 361 (131)
-12 16 20 25
inches 37.32 x 75.28 x 32.76 53.66 x 75.28 x 32.76 53.66 x 75.28 x 32.76 53.66 x 75.28 x 32.76
20 VRF-PRC008B-EN
Page 21
Product Specifications
Table 15. 460V Heat Pump Dual Modules I
Model Name 4TVH0168B400NB 4TVH0192B400NB 4TVH0216B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Nominal Tons 14.0 16.0 18.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A outdoor unit T-joint connection (a) Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (2) SSC Scroll (2) SSC Scroll (2)
Model Name ­Output kW 4.96 + 6.13 4.96 + 6.13 4.96 x 3
Oil Type (Qty.) - Propeller (3) Propeller (3) Propeller (3)
Output (Each) W 400 + 620 x 2 400 + 620 x 2 400 + 620 x 2 Airflow Rate CFM 7,240 + 9,180 7,240 + 9,180 7,240 + 9,535 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 5/8" Braze 5/8" Braze 5/8" Braze Gas Pipe Ø inch 1 1/8" Braze 1 1/8" Braze 1 1/8" Braze High Pressure Gas Pipe (For HR) Ø inch N/A N/A N/A
Installation Limits
Number Of Connectable Indoor Units - 29 33 37 Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 28.4 28.4 31.3 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 436 + 540 436 + 540 436 + 672 Shipping Weight lbs. 472 + 582 472 + 582 472 + 714
Net Dimensions (WxHxD) inches Shipping Dimensions (WxHxD) inches
Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F
Cooling Btuh
(a)
Heating Btuh Cooling Btuh High Temp Heating Btuh
(b)
Low Temp Heating Btuh EER ­IEER ­COP @ 47°F -
(b)
COP @ 17°F ­SCHE - - - - - - -
Type - PVE PVE PVE Initial Charge fl. oz. 155.5 155.5 233.3
Max Length Max Height
(c)
(d)
4TVH0072B400NB +
4TVH0096B400NB
4TVH0072B400NB +
4TVH0120B400NB
4TVH0072B400NB +
4TVH0144B400NB
168,000 168,000 192,000 192,000 216,000 216,000 189,000 189,000 216,000 216,000 243,000 243,000 160,000 160,000 184,000 184,000 206,000 206,000 180,000 180,000 206,000 206,000 230,000 230,000 118,000 118,000 134,000 134,000 150,000 150,000
11.30 12.10 10.90 11.20 10.60 10.80
20.50 25.30 21.50 24.20 20.50 22.40
3.44 3.94 3.34 3.83 3.34 3.63
2.43 2.65 2.42 2.59 2.31 2.52
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
DS-GB052FAVASG +
DS-GB066FAVASG
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
DS-GB052FAVASG +
DS-GB066FAVASG
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
DS-GB052FAVASG x 2
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
'-13 ~ 75 '-13 ~ 75 '-13 ~ 75
VRF-PRC008B-EN 21
Page 22
Product Specifications
Table 16. 460V Heat Pump Dual Modules II
Model Name 4TVH0240B400NB 4TVH0264B400NB 4TVH0288B400NB
2x 4TVH0120B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Nominal Tons 20.0 22.0 24.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A outdoor unit T-joint connection
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (2) SSC Scroll (3) SSC Scroll (4)
Model Name - DS-GB066FAVASG x 2 Output kW 6.13 x 2 (4.96 x 2) + 6.13 4.96 x 4
Oil Type (Qty.) - Propeller (4) Propeller (4) Propeller (4)
Output (Each) W 620 x 4 620 x 4 620 x 4 Airflow Rate CFM 9180 x 2 9,180 + 9,535 9535 x 2 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 5/8" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 1/8" Braze 1 3/8" Braze 1 3/8" Braze High Pressure Gas Pipe (For HR) Ø inch N/A N/A N/A
Installation Limits
Number Of Connectable Indoor Units - 41 45 49 Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 32.6 35.5 38.4 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 540 x 2 540 + 672 672 x 2 Shipping Weight lbs. 582 x 2 582 + 714 714 x 2 Net Dimensions (WxHxD) inches (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 Shipping Dimensions (WxHxD) inches (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2 Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 240,000 240,000 264,000 264,000 288,000 288,000
(a)
Heating Btuh 270,000 270,000 297,000 297,000 324,000 324,000 Cooling Btuh 228,000 228,000 252,000 252,000 276,000 276,000 High Temp Heating Btuh 258,000 258,000 282,000 282,000 308,000 308,000
(b)
Low Temp Heating Btuh 168,000 168,000 184,000 184,000 200,000 200,000 EER - 10.60 10.70 10.10 10.10 10.00 9.90 IEER - 18.50 22.10 18.50 21.50 18.60 21.00 COP @ 47°F - 3.24 3.65 3.25 3.45 3.25 3.26
(b)
COP @ 17°F - 2.40 2.54 2.26 2.41 2.12 2.29 SCHE - - - - - - -
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
Type - PVE PVE PVE Initial Charge fl. oz. 155.5 233.3 311.1
Max Length Max Height
(c)
(d)
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
(a) Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB.
(b) Rated per AHRI-1230 Standard conditions.
(c) Actual length (equivalent length in parenthesis).
(d) If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft.
(e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
4TVH0120B400NB +
4TVH0144B400NB 2x 4TVH0144B400NB
DS-GB052FAVASG x 2
+ DS-GB066FAVASG
DS-GB052FAVASG x 4
22 VRF-PRC008B-EN
Page 23
Product Specifications
Table 17. 460V Heat Pump Triple Modules I
Model Name 4TVH0312B400NB 4TVH0336B400NB 4TVH0360B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires two 4TDK3819B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions (published ratings apply to systems < 300,000 Btuh). (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
Nominal Tons 26.0 28.0 30.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (4) SSC Scroll (4) SSC Scroll (5)
Model Name ­Output kW (4.96 x 3) + 6.13 (4.96 x 3) + 6.13 4.96 x 5
Oil Type (Qty.) - Propeller (5) Propeller (5) Propeller (5)
Output (Each) W 400 + 620 x 4 400 + 620 x 4 400 + 620 x 4 Airflow Rate CFM 7,240 + 9,180 + 9,535 7,240 + 9,180 + 9,535 7,240 + (9,535 x2) External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 3/8" Braze 1 3/8" Braze 1 5/8" Braze High Pressure Gas Pipe (For HR) Ø inch N/A N/A N/A Installation
Limits Number Of Connectable Indoor Units - 54 58 62 Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A Factory Charge lbs. 47.6 47.6 50.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 437 + 540 + 672 437 + 540 + 672 437 + (672 x2) Shipping Weight lbs. 472 + 582 + 714 472 + 582 + 714 472 + (714 x2)
Net Dimensions (WxHxD) inches Shipping Dimensions (WxHxD) inches
Cooling °F 23 ~ 120 23 ~ 120 23 ~ 120 Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 312,000 312,000 336,000 336,000 360,000 360,000
(a)
Heating Btuh 351,000 351,000 378,000 378,000 405,000 405,000 Cooling Btuh 298,000 298,000 320,000 320,000 344,000 344,000 High Temp Heating Btuh 334,000 334,000 360,000 360,000 386,000 386,000
(b)
Low Temp Heating Btuh 218,000 218,000 234,000 234,000 250,000 250,000 EER - 10.30 10.60 10.00 10.20 9.80 9.80 IEER - 18.10 20.90 17.00 20.50 16.60 20.00 COP @ 47°F - 3.20 3.38 3.20 3.27 3.20 3.22
(b)
COP @ 17°F - 2.25 2.51 2.21 2.39 2.11 2.31 SCHE - - - - - - -
Type - PVE PVE PVE Initial Charge fl. oz. 311.1 311.1 388.9
Max Length Max Height
(c)
(d)
4TVH0072B400NB + 4TVH0096B400NB +
4TVH0144B400NB
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
DS-GB052FAVASG x 3
+ DS-GB066FAVASG
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
4TVH0072B400NB + 4TVH0120B400NB +
4TVH0144B400NB
DS-GB052FAVASG x 3
+ DS-GB066FAVASG
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
4TVH0072B400NB + 2x 4TVH0144B400NB
DS-GB052FAVASG x 5
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
VRF-PRC008B-EN 23
Page 24
Product Specifications
Table 18. 460V Heat Pump Triple Modules II
Model Name 4TVH0384B400NB 4TVH0408B400NB 4TVH0432B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires two 4TDK3819B0000A outdoor unit T-joint connections. (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions (published ratings apply to systems (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions.
Nominal Tons 32.0 34.0 36.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (4) SSC Scroll (5) SSC Scroll (6)
Model Name ­Output kW (4.96 x 2) + (6.13 x 2) (4.96 x 4) + 6.13 4.96 x 6
Oil Type (Qty.) - Propeller (6) Propeller (6) Propeller (6)
Output (Each) W 620 x 6 620 x 6 620 x 6 Airflow Rate CFM (9,180 x2) + 9535 9,180 + (2x 9,535) 9535 x 3 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 5/8" Braze 1 5/8" Braze 1 5/8" Braze High Pressure Gas Pipe (For HR) Ø inch N/A N/A N/A Installation
Limits Number Of Connectable Indoor Units - 64 64 64 Total Capacity - 50 to 130% of total outdoor unit capacity Type - R410A R410A R410A Factory Charge lbs. 51.8 54.7 57.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. (540 x 2) + 672 540 + (672 x 2) 672 x 3 Shipping Weight lbs. (582 x 2) + 714 582 + (714 x 2) 714 x 3 Net Dimensions (WxHxD) inches (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 Shipping Dimensions (WxHxD) inches (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3 Cooling °F Heating °F
Cooling Btuh 384,000 384,000 408,000 408,000 432,000 432,000
(a)
Heating Btuh 432,000 432,000 459,000 459,000 486,000 486,000 Cooling Btuh 366,000 366,000 390,000 390,000 415,000 415,000 High Temp Heating Btuh 410,000 410,000 435,000 435,000 460,000 460,000
(b)
Low Temp Heating Btuh 268,000 268,000 284,000 284,000 300,000 300,000 EER - 9.50 9.50 9.50 9.50 9.50 9.50 IEER - 16.20 19.50 16.30 19.10 16.30 19.10 COP @ 47°F - 3.20 3.20 3.20 3.20 3.20 3.20
(b)
COP @ 17°F - 2.05 2.10 2.05 2.05 2.05 2.05 SCHE - - - - - - -
Type - PVE PVE PVE Initial Charge fl. oz. 311.1 388.9 466.6
Max Length Max Height
(c)
(d)
2x 4TVH0120B400NB +
4TVH0144B400NB
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
DS-GB052FAVASG x 2
+ DS-GB066FAVASG x 2
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
23 ~ 120 23 ~ 120 23 ~ 120
-13 ~ 75 -13 ~ 75 -13 ~ 75
< 300,000 Btuh).
4TVH0120B400NB +
2x 4TVH0144B400NB 3x 4TVH0144B400NB
DS-GB052FAVASG x 4
+ DS-GB066FAVASG
DS-GB052FAVASG x 6
24 VRF-PRC008B-EN
Page 25
Product Specifications
Table 19. 460V Heat Recovery Single Modules
Power Supply 460/60/3 460/60/3 460/60/3 460/60/3
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
(a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
Model Name 4TVR0072B400NB 4TVR0096B400NB 4TVR0120B400NB 4TVR0144B400NB
Nominal Tons 6.0 8.0 10.0 12.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A 16.4 19 21.7 26.4 MOP A 20 25 30 40 SCCR kA - - - ­Type (Qty.) - SSC Scroll (1) SSC Scroll (1) SSC Scroll (1) SSC Scroll (2) Model Name - DS-GB052FAVASG DS-GB066FAVASG DS-GB066FAVASG DS-GB052FAVASG Output kW 4.96 6.13 6.13 4.96 x 2
Oil Type (Qty.) - Propeller (1) Propeller (2) Propeller (2) Propeller (2)
Output (Each) W 400 620 620 620 Airflow Rate CFM 7,240 9,180 9,180 9,535 External Static Pressure in. WG 0.31 0.31 0.31 0.31 Liquid Pipe Ø inch 3/8" Braze 3/8" Braze 1/2" Braze 1/2" Braze Gas Pipe Ø inch 3/4" Braze 7/8" Braze 1 1/8" Braze 1 1/8" Braze High Pressure Gas Pipe (For
HR) Installation
Limits Number Of Connectable
Indoor Units Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A R-410A Factory Charge lbs. 12.1 16.3 16.3 19.18 Sound Pressure dB(A) 60.0 61.0 61.0 62.0 Sound Power dB(A) 81 81 81 83 Net Weight lbs. 445 553 553 692 Shipping Weight lbs. 481 595 595 734 Net Dimensions (WxHxD) inches 34.65 x 66.73 x 30.12 50.98 x 66.73 x 30,12 50.98 x 66.73 x 30,12 50.98 x 66.73 x 30.12 Shipping Dimensions (WxHxD) Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 72,000 72,000 96,000 96,000 120,000 120,000 144,000 144,000
(a)
Heating Btuh 81,000 81,000 108,000 108,000 135,000 135,000 162,000 162,000 Cooling Btuh 69,000 69,000 92,000 92,000 114,000 114,000 138,000 138,000 High Temp
Heating
(b)
Low Temp Heating
EER - 11.50 12.90 11.50 13.90 11.10 12.40 10.80 11.20 IEER - 22.50 33.00 22.40 29.60 21.20 27.10 21.10 24.50 COP @ 47°F - 3.46 4.15 3.56 4.23 3.43 3.97 3.54 3.64
(b)
COP @ 17°F - 2.49 2.75 2.45 2.81 2.44 2.53 2.23 2.40 SCHE - 26.00 28.00 26.50 31.50 25.50 30.00 25.00 27.50
Type - PVE PVE PVE PVE Initial Charge fl. oz. 77.8 77.8 77.8 155.5
Max Length Max Height
(f)
Btuh 77,000 77,000 103,000 103,000 129,000 129,000 154,000 154,000 Btuh 51,000 51,000 67,000 67,000 84,000 84,000 100,000 100,000
Ø inch 5/8" Braze 3/4" Braze 7/8" Braze 7/8" Braze
(c)
ft. 656 (722) 656 (722) 656 (722) 656 (722)
(d)
ft. 361 (131) 361 (131) 361 (131) 361 (131)
-12 16 20 25
inches 37.32 x 75.28 x 32.76 53.66 x 75.28 x 32.76 53.66 x 75.28 x 32.76 53.66 x 75.28 x 32.76
°F 5 ~ 120 5 ~ 120 5 ~ 120 5 ~ 120
VRF-PRC008B-EN 25
Page 26
Product Specifications
Table 20. 460V Heat Recovery Dual Modules I
Model Name 4TVR0168B400NB 4TVR0192B400NB 4TVR0216B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Nominal Tons 14.0 16.0 18.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (2) SSC Scroll (2) SSC Scroll (2)
Model Name ­Output kW 4.96 + 6.13 4.96 + 6.13 4.96 x 3
Oil Type (Qty.) - Propeller (3) Propeller (3) Propeller (3)
Output (Each) W 400 + 620 x 2 400 + 620 x 2 400 + 620 x 2 Airflow Rate CFM 7,240 + 9,180 7,240 + 9,180 7,240 + 9,535 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 5/8" Braze 5/8" Braze 5/8" Braze Gas Pipe Ø inch 1 1/8" Braze 1 1/8" Braze 1 1/8" Braze High Pressure Gas Pipe (For HR) Ø inch 7/8" Braze 1 1/8" Braze 1 1/8" Braze
Installation Limits Number Of Connectable Indoor Units - 29 33 37
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A Factory Charge lbs. 28.4 28.4 31.3 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 445 + 553 445 + 553 445 + 692 Shipping Weight lbs. 481 + 595 481 + 595 481 + 734
Net Dimensions (WxHxD) inches Shipping Dimensions (WxHxD) inches
(f)
Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 168,000 168,000 192,000 192,000 216,000 216,000
(a)
Heating Btuh 189,000 189,000 216,000 216,000 243,000 243,000 Cooling Btuh 160,000 160,000 184,000 184,000 206,000 206,000 High Temp Heating
(b)
Low Temp Heating Btuh 118,000 118,000 134,000 134,000 150,000 150,000 EER - 11.30 12.10 10.90 11.20 10.60 10.80 IEER - 20.50 25.30 21.50 24.20 20.50 22.40 COP @ 47°F - 3.44 3.94 3.34 3.83 3.34 3.63
(b)
COP @ 17°F - 2.43 2.65 2.42 2.59 2.31 2.52 SCHE - 23.50 27.00 23.50 26.50 23.00 25.50
Type - PVE PVE PVE Initial Charge fl. oz. 155.5 155.5 233.3
Max Length Max Height
(c)
(d)
4TVR0072B400NB +
4TVR0096B400NB
Btuh 180,000 180,000 206,000 206,000 230,000 230,000
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
DS-GB052FAVASG +
DS-GB066FAVASG
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
°F 5 ~ 120 5 ~ 120 5 ~ 120
4TVR0072B400NB +
4TVR0120B400NB
DS-GB052FAVASG +
DS-GB066FAVASG
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
4TVR0072B400NB +
4TVR0144B400NB
DS-GB052FAVASG x 2
34.65 x 66.73 x 30.12 +
50.98 x 66.73 x 30.12
37.32 x 75.28 x 32.76 +
53.66 x 75.28 x 32.76
26 VRF-PRC008B-EN
Page 27
Product Specifications
Table 21. 460V Heat Recovery Dual Modules II
Model Name 4TVR0240B400NB 4TVR0264B400NB 4TVR0288B400NB
2x 4TVR0120B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Nominal Tons 20.0 22.0 24.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
(Rated)
AHRI -1230
Efficiency Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (2) SSC Scroll (3) SSC Scroll (4)
Model Name - DS-GB066FAVASG x 2 Output kW 6.13 x 2 (4.96 x 2) + 6.13 4.96 x 4
Oil Type (Qty.) - Propeller (4) Propeller (4) Propeller (4)
Output (Each) W 620 x 4 620 x 4 620 x 4 Airflow Rate CFM 9180 x 2 9,180 + 9,535 9535 x 2 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 5/8" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 1/8" Braze 1 3/8" Braze 1 3/8" Braze High Pressure Gas Pipe (For HR) Ø inch 1 1/8" Braze 1 1/8" Braze 1 1/8" Braze
Installation Limits Number Of Connectable Indoor Units - 41 45 49
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A Factory Charge lbs. 32.6 35.5 38.4 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 553 x 2 553 + 692 692 x 2 Shipping Weight lbs. 595 x 2 595 + 734 734 x 2 Net Dimensions (WxHxD) inches (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 (50.98 x 66.73 x 30.12) x 2 Shipping Dimensions (WxHxD) inches (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2 (53.66 x 75.28 x 32.76) x 2
(f)
Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh
(a)
Heating Btuh Cooling Btuh High Temp Heating
(b)
Low Temp Heating Btuh EER ­IEER ­COP @ 47°F -
(b)
COP @ 17°F ­SCHE -
Type - PVE PVE PVE Initial Charge fl. oz. 155.5 233.3 311.1
Max Length Max Height
(c)
(d)
Btuh
240,000 240,000 264,000 264,000 288,000 288,000 270,000 270,000 297,000 297,000 324,000 324,000 228,000 228,000 252,000 252,000 276,000 276,000 258,000 258,000 282,000 282,000 308,000 308,000 168,000 168,000 184,000 184,000 200,000 200,000
10.60 10.70 10.10 10.10 10.00 9.90
18.50 22.10 18.50 21.50 18.60 21.00
3.24 3.65 3.25 3.45 3.25 3.26
2.40 2.54 2.26 2.41 2.12 2.29
22.50 25.50 22.00 24.50 21.50 23.50
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
°F 5 ~ 120 5 ~ 120 5 ~ 120
4TVR0120B400NB +
4TVR0144B400NB 2x 4TVR0144B400NB
DS-GB052FAVASG x 2
+ DS-GB066FAVASG
DS-GB052FAVASG x 4
VRF-PRC008B-EN 27
Page 28
Product Specifications
Table 22. 460V Heat Recovery Triple Modules I
Model Name 4TVR0312B400NB 4TVR0336B400NB 4TVR0360B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating Temp Range
Note: Requires two each 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions (published ratings apply to systems < 300,000 Btuh). (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
Nominal Tons 26.0 28.0 30.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
(Rated)
AHRI -1230
Efficiency Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (4) SSC Scroll (4) SSC Scroll (5)
Model Name ­Output kW (4.96 x 3) + 6.13 (4.96 x 3) + 6.13 4.96 x 5
Oil Type (Qty.) - Propeller (5) Propeller (5) Propeller (5)
Output (Each) W 400 + 620 x 4 400 + 620 x 4 400 + 620 x 4 Airflow Rate CFM 7,240 + 9,180 + 9,535 7,240 + 9,180 + 9,535 7,240 + (9,535 x2) External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 3/8" Braze 1 3/8" Braze 1 5/8" Braze High Pressure Gas Pipe (For HR) Ø inch 1 1/8" Braze 1 1/8" Braze 1 3/8" Braze
Installation Limits Number Of Connectable Indoor Units - 54 58 62
Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A Factory Charge lbs. 47.6 47.6 50.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 445 + 553 + 692 445 + 553 + 692 445 + (692 x 2) Shipping Weight lbs. 481 + 595 + 734 481 + 595 + 734 481 + (734 x 2)
Net Dimensions (WxHxD) inches Shipping Dimensions (WxHxD) inches
(f)
Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 312,000 312,000 336,000 336,000 360,000 360,000
(a)
Heating Btuh 351,000 351,000 378,000 378,000 405,000 405,000 Cooling Btuh 298,000 298,000 320,000 320,000 344,000 344,000 High Temp Heating
(b)
Low Temp Heating Btuh 218,000 218,000 234,000 234,000 250,000 250,000 EER - 10.30 10.60 10.00 10.20 9.80 9.80 IEER - 18.10 20.90 17.00 20.50 16.60 20.00 COP @ 47°F - 3.20 3.38 3.20 3.27 3.20 3.22
(b)
COP @ 17°F - 2.25 2.51 2.21 2.39 2.11 2.31 SCHE - 20.50 23.50 20.50 23.10 20.00 22.40
Type - PVE PVE PVE Initial Charge fl. oz. 311.1 311.1 388.9
Max Length Max Height
(c)
(d)
4TVR0072B400NB + 4TVR0096B400NB +
4TVR0144B400NB
Btuh 334,000 334,000 360,000 360,000 386,000 386,000
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
DS-GB052FAVASG x 3
+ DS-GB066FAVASG
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
°F 5 ~ 120 5 ~ 120 5 ~ 120
4TVR0072B400NB + 4TVR0120B400NB +
4TVR0144B400NB
DS-GB052FAVASG x 3
+ DS-GB066FAVASG
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
4TVR0072B400NB + 2x 4TVR0144B400NB
DS-GB052FAVASG x 5
34.65 x 66.73 x 30.12 +
(50.98 x 66.73 x 30.12) x2
37.32 x 75.28 x 32.76 +
(53.66 x 75.28 x 32.76) x2
28 VRF-PRC008B-EN
Page 29
Product Specifications
Table 23. 460V Heat Recovery Triple Modules II
Model Name 4TVR0384B400NB 4TVR0408B400NB 4TVR0432B400NB
Power Supply 460/60/3 460/60/3 460/60/3
Nominal Tons 32.0 34.0 36.0 System Type Ducted Non-Ducted Ducted Non-Ducted Ducted Non-Ducted
Capacity
(Nominal)
Capacity
Performance
Power
Compressor
Fan
Piping Connections
Indoor Unit Connections
Refrigerant
(e)
Sound
External Dimensions
Operating T emp Range
Note: Requires two each 4TDK3819B0000A and 4TDK3100B0000A outdoor unit T-joint connections (a)Nominal capacity based on 25 ft. of equivalent refrigerant piping with 0 ft. level difference. Cooling: Indoor temperature 80°F DB, 67°F WB/Outdoor
temperature 95°F DB, 75°F WB. Heating: Indoor temperature 70°F DB, 60°F WB/Outdoor temperature 47°F DB, 43°F WB. (b)Rated per AHRI-1230 Standard conditions. (c) Actual length (equivalent length in parenthesis). (d)If the outdoor unit is installed above the indoor units, the allowable height difference to the furthest indoor unit is 361 ft. If the outdoor unit is installed
below the below the indoor units, the allowable height difference is 131 ft. (e) Sound pressure was acquired in a dead room. Actual noise level may be different depending on installation conditions. (f) Cooling operation between 23° F and 5° F requires mixed mode condition (at least 50% of the indoor units must be in heating mode).
(Rated)
AHRI -1230
Efficiency
Ratings
MCA A MOP A SCCR kA Type (Qty.) - SSC Scroll (4) SSC Scroll (5) SSC Scroll (6)
Model Name ­Output kW (4.96 x 2) + (6.13 x 2) (4.96 x 4) + 6.13 4.96 x 6
Oil Type (Qty.) - Propeller (6) Propeller (6) Propeller (6)
Output (Each) W 620 x 6 620 x 6 620 x 6 Airflow Rate CFM (9,180 x2) + 9535 9,180 + (2x 9,535) 9535 x 3 External Static Pressure in. WG 0.31 0.31 0.31 Liquid Pipe Ø inch 3/4" Braze 3/4" Braze 3/4" Braze Gas Pipe Ø inch 1 5/8" Braze 1 5/8" Braze 1 5/8" Braze High Pressure Gas Pipe (For HR) Ø inch 1 3/8" Braze 1 3/8" Braze 1 3/8" Braze
Installation Limits
Number Of Connectable Indoor Units - 64 64 64 Total Capacity - 50 to 130% of total outdoor unit capacity Type - R-410A R-410A R-410A Factory Charge lbs. 51.8 54.7 57.5 Sound Pressure dB(A) - - ­Sound Power dB(A) - - ­Net Weight lbs. 553 + (692 x 2) 553 + (692 x 2) 692 x 3 Shipping Weight lbs. 595 + (734 x 2) 595 + (734 x 2) 734 x 3 Net Dimensions (WxHxD) inches (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 (50.98 x 66.73 x 30.12) x 3 Shipping Dimensions (WxHxD) inches (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3 (53.66 x 75.28 x 32.76) x 3 Cooling Heating °F -13 ~ 75 -13 ~ 75 -13 ~ 75
Cooling Btuh 384,000 384,000 408,000 408,000 432,000 432,000
(a)
Heating Btuh 432,000 432,000 459,000 459,000 486,000 486,000 Cooling Btuh 366,000 366,000 390,000 390,000 415,000 415,000 High Temp Heating
(b)
Low Temp Heating Btuh 268,000 268,000 284,000 284,000 300,000 300,000 EER - 9.50 9.50 9.50 9.50 9.50 9.50 IEER - 16.20 19.50 16.30 19.10 16.30 19.10 COP @ 47°F - 3.20 3.20 3.20 3.20 3.20 3.20
(b)
COP @ 17°F - 2.05 2.10 2.05 2.05 2.05 2.05 SCHE - 19.50 23.00 19.00 22.00 19.00 21.50
Type - PVE PVE PVE Initial Charge fl. oz. 311.1 388.9 466.6
Max Length Max Height
(f)
(c)
(d)
2x 4TVR0120B400NB +
4TVR0144B400NB
Btuh 410,000 410,000 435,000 435,000 460,000 460,000
Each individual outdoor unit requires a separate electrical connection.
Reference electrical data for each individual outdoor unit.
DS-GB052FAVASG x 2
+ DS-GB066FAVASG x 2
ft. 656 (722) 656 (722) 656 (722) ft. 361 (131) 361 (131) 361 (131)
°F 5 ~ 120 5 ~ 120 5 ~ 120
4TVR0120B400NB + 2x 4TVR0144B400NB 3x 4TVR0144B400NB
DS-GB052FAVASG x 4
+ DS-GB066FAVASG
DS-GB052FAVASG x 6
VRF-PRC008B-EN 29
Page 30

Operation Limit - Outdoor Units

Figure 1. Cooling
(a)Extend operational temperature range applies to heat recovery systems in mixed mode condition (at least
50% of the indoor units must be in heating mode).
(a)
140 122
120 104
86 68 50 32
23(HP)
(HR)
14
5
-4
-22 50 59 68 77 80 86
Outdoor temperature (°F DB)
Continuous
Operation Range
“Expand operational
temperature range” option
Indoor temperature (°F WB)
Figure 2. Heating
86 75
68
50
Warming
Operation
32
Range
14
Outdoor temperature (°F DB)
-13
-22 50 59 68 77 80 86
Up
Continuous
Operation Range
Indoor temperature (°F WB)
30 VRF-PRC008B-EN
Page 31

Defrosting Correction Factor

In heating operation, frost can be formed on heat exchanger according to outdoor temperature. (frost on heat exchangerresults in decreasing the performance.)Toremove frost on heat exchanger of outdoor unit, defrost operation is carried out periodically. During defrost operation, capacity of outdoor unit may decrease.The decrement is not considered to the individual capacity tables.
Operation Limit - Outdoor Units
Outdoor temperature
(°F, WB)
Capacity coefficient 0.98 0.97 0.95 0.93 0.88 0.85 0.86 0.91 1.00
Figure 3. Corrected Heating Capacity = Heating Capacity x Capacity coefficient
14.0 17.6 21.2 24.8 28.4 32.0 37.4 41.0 44.6
Capacity coefficient of outdoor unit on defrost operation
1.05
1.00
0.95
0.90
0.85
0.80
Capacity coefficient
0.98
0.97
0.95
0.93
0.88
0.85
0.91
0.86
0.75
14.0
17.6 21.2 24.8 28.4 32.0 37.4 41.0 44.6
Outdoor temperature(°F)
1.00
VRF-PRC008B-EN 31
Page 32

Electrical Wiring Diagrams - Outdoor Units

Figure 4. Heat Pump - 4TVH0072B300NB, 4TVH0072B400NB
Note 1: Resistance value at 25°C (77°F)
Note 5: Input voltage 460V: Does not apply Input voltage 208-230V: Apply
32 VRF-PRC008B-EN
Page 33
Figure 5. Heat Pump - 4TVH0096B400NB, 4TVH0120B400NB
Note 1: Resistance value at 25°C (77°F) Note 2: 1 Fan: Does not apply
2 Fan: Apply Note 5: Input voltage 460V: Does not apply
Input voltage 208-230V: Apply
ElectricalWiring Diagrams - Outdoor Units
VRF-PRC008B-EN 33
Page 34
ElectricalWiring Diagrams - Outdoor Units
Figure 6. Heat Pump - 4TVH0096B300NB, 4TVH0120B300NB, 4TVH0144B300NB, 4TVH0144B400NB
Note 1: Resistance value at 25°C (77°F) Note 2: 1 Fan: Does not apply
2 Fan: Apply Note 3: 1 Comp: Does not apply
2 Comp: Apply Note 5: Input voltage 460V: Does not apply
Input voltage 208-230V: Apply
34 VRF-PRC008B-EN
Page 35
Figure 7. Heat Recovery - 4TVR0072B300NB, 4TVR0072B400NB
Note 1: Resistance value at 25°C (77°F) Note 4: Heat Pump: Does not apply
Heat Recovery: Apply Note 5: Input voltage 460V: Does not apply
Input voltage 208-230V: Apply
ElectricalWiring Diagrams - Outdoor Units
VRF-PRC008B-EN 35
Page 36
ElectricalWiring Diagrams - Outdoor Units
Figure 8. Heat Recovery - 4TVR0096B400NB, 4TVR0120B400NB
Note 1: Resistance value at 25°C (77°F) Note 2: 1 Fan: Does not apply
2 Fan: Apply Note 4: Heat Pump: Does not apply
Heat Recovery: Apply
Note 5: Input voltage 460V: Does not apply Input voltage 208-230V: Apply
36 VRF-PRC008B-EN
Page 37
ElectricalWiring Diagrams - Outdoor Units
Figure 9. Heat Recovery - 4TVR0096B300NB, 4TVR0120B300NB, 4TVR0144B300NB, 4TVR0144B400NB
Note 1: Resistance value at 25°C (77°F) Note 2: 1 Fan: Does not apply
2 Fan: Apply Note 3: 1 Comp: Does not apply
2 Comp: Apply Note 4: Heat Pump: Does not apply
Heat Recovery: Apply Note 5: Input voltage 460V: Does not apply
Input voltage 208-230V: Apply
VRF-PRC008B-EN 37
Page 38

Sound Levels - Outdoor Units

Figure 10. Sound Pressure Level
1m
Microphone
1.5m
Front
Model Pressure
4TVH/R0072B3, 4TVH/R0072B4 60 4TVH/R0096B3, 4TVH/R0120B3 61 4TVH/R0096B4, 4TVH/R0120B4 61 4TVH/R0072B3, 4TVH/R0072B4 60
Unit: dB(A)

NC Curves

Notes:
Measuring place: Anechoic chamber (conversion value)
These operation values were obtained in an anechoic room. Sound pressure level will vary
depending on a range of factors such as the construction of the particular room where the equipment is installed.
Operation sound level may differ depending on operation and ambient conditions.
Figure 11. 4TVH/R0072B3, 4TVH/R0072B4
4TVH/R0072B3, 4TVH/R0072B4
75
65
55
45
35
Sound pressure level (dB)
25
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30
38 VRF-PRC008B-EN
Page 39
Figure 12. 4TVH/R0096B3, 4TVH/R0120B3
4TVH/R0096B3, 4TVH/R0120B3
75
Sound Levels - Outdoor Units
65
55
45
35
Sound pressure level (dB)
25
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
Figure 13. 4TVH/R0096B4, 4TVH/R0120B4
4TVH/R0096B4, 4TVH/R0120B4
75
65
55
45
35
Sound pressure level (dB)
25
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30
NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35 NC 30
Figure 14. 4TVH/R0144B3, 4TVH/R0144B4
4TVH/R011B3, 4TVH/R0144B4
75
65
55
45
35
Sound pressure level (dB)
25
63 125 250 500 1000 2000 4000 8000
Octave band center frequency (Hz)
VRF-PRC008B-EN 39
NC 65 NC 60 NC 55 NC 50 NC 45 NC 40 NC 35
NC 30
Page 40
Sound Levels - Outdoor Units

Sound Power

Notes:
dBA = A-weighted sound power level.
Reference power: 1pW
Measured according to ISO 3741.
4TVH/R0072B3, 4TVH/R0072B4 81 4TVH/R0096B3, 4TVH/R0120B3 81 4TVH/R0096B4, 4TVH/R0120B4 81 4TVH/R0144B3, 4TVH/R0144B4 83

NR Curves

Figure 15. 4TVH/R0072B3, 4TVH/R0072B4
Sound pressure level (dB)
Model Power
4TVH/R0072B3, 4TVH/R0072B4
110.0
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
10.0
0.0 125 250 500 1000 2000 4000 8000 dBA
Octave band center frequency (Hz)
Unit: dB(A)
Power (dB) NR 100 NR 95 NR 90 NR 85 NR 80 NR 75 NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 25 NR 20 NR 15 NR 10 NR 5 NC 0
Figure 16. 4TVH/R0096B3, 4TVH/R0120B3
4TVH/R0096B3, 4TVH/R0120B3
110.0
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
Sound pressure level (dB)
20.0
10.0
0.0 125 250 500 1000 2000 4000 8000 dBA
Octave band center frequency (Hz)
40 VRF-PRC008B-EN
Power (dB) NR 100 NR 95 NR 90 NR 85 NR 80 NR 75 NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 25 NR 20 NR 15 NR 10 NR 5 NC 0
Page 41
Figure 17. 4TVH/R0096B4, 4TVH/R0120B4
4TVH/R0096B4, 4TVH/R0120B4
110.0
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
Sound pressure level (dB)
20.0
10.0
0.0 125 250 500 1000 2000 4000 8000 dBA
Octave band center frequency (Hz)
Figure 18. 4TVH/R0144B3, 4TVH/R0144B4
4TVH/R0144B3, 4TVHR0144B4
110.0
100.0
90.0
80.0
70.0
60.0
50.0
40.0
30.0
Sound pressure level (dB)
20.0
10.0
0.0 125 250 500 1000 2000 4000 8000 dBA
Octave band center frequency (Hz)
Power (dB) NR 100 NR 95 NR 90 NR 85 NR 80 NR 75 NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 25 NR 20 NR 15 NR 10 NR 5 NC 0
Power (dB) NR 100 NR 95 NR 90 NR 85 NR 80 NR 75 NR 70 NR 65 NR 60 NR 55 NR 50 NR 45 NR 40 NR 35 NR 30 NR 25 NR 20 NR 15 NR 10 NR 5 NC 0
Sound Levels - Outdoor Units
VRF-PRC008B-EN 41
Page 42

Cycle Diagrams

Parts of Outdoor Unit (HP)

Figure 19. 4TVH0072B300NB, 4TVH0072B400NB
2)0
69B*
7B$
+36:
&9B'
7B&7
&+
+36
26
,19
9B:
7B'
V
9B(6
9B(%
V
7B&2
&9B(
7B(2
,30&
(
(B0
,&
7B(,
(
(B9
7B/
69B/
2+;
7B6
V
9B+*
9B$5
V
/36
$&
Classification Description Classification Description
INV Inverter Compressor V_HG Hot Gas Bypass Valve OFM Outdoor Fan Motor V_4W 4way Valve OHX Outdoor Heat Exchanger V_AR Accumulator Oil Return Valve
AC Accumulator CV_E EEV Bypass Check Valve OS Oil Separator CV_D Discharge Check Valve
IC Intercooler T_D Discharge Temperature Sensor
IPMC IPM Cooler T_S Suction Temperature Sensor
CH Crank Case Heater T_CO Condenser Out Temperature Sensor HPS High Pressure Sensor T_EI EVI In Temperature Sensor LPS Low Pressure Sensor T_EO EVI Out Temperature Sensor
HPSW High Pressure Switch T_L Liquid Tube Temperature Sensor
E_M Main EEV T_CT Compressor Top Temperature Sensor E_EV EVI EEV T_A Ambient Temperature Sensor V_ES EVI Solenoid Valve SV_G Gas Pipe Service Valve V_EB EVI Bypass Valve SV_L Liquid Pipe Service Valve
42 VRF-PRC008B-EN
Page 43
Figure 20. 4TVH0096B400NB, 4TVH0120B400NB
2)0
Cycle Diagrams
69B*
7B$
+36:
&9B'
7B&7
&+
+36
26
,19
9B:
7B'
V
9B(6
V
7B6
9B+*
9B$5
V
/36
2+;
7B&2
(
&9B(
9B(%
7B(2
V
$&
,30&
(B0
,&
7B(,
(
(B9
7B/
69B/
Classification Description Classification Description
INV Inverter Compressor V_HG Hot Gas Bypass Valve OFM Outdoor Fan Motor V_4W 4way Valve OHX Outdoor Heat Exchanger V_AR Accumulator Oil Return Valve
AC Accumulator CV_E EEV Bypass Check Valve OS Oil Separator CV_D Discharge Check Valve
IC Intercooler T_D Discharge Temperature Sensor
IPMC IPM Cooler T_S Suction Temperature Sensor
CH Crank Case Heater T_CO Condenser Out Temperature Sensor HPS High Pressure Sensor T_EI EVI In Temperature Sensor LPS Low Pressure Sensor T_EO EVI Out Temperature Sensor
HPSW High Pressure Switch T_L Liquid Tube Temperature Sensor
E_M Main EEV T_CT Compressor Top Temperature Sensor E_EV EVI EEV T_A Ambient Temperature Sensor V_ES EVI Solenoid Valve SV_G Gas Pipe Service Valve V_EB EVI Bypass Valve SV_L Liquid Pipe Service Valve
VRF-PRC008B-EN 43
Page 44
Cycle Diagrams
Figure 21. 4TVH0096B300NB, 4TVH0120B300NB, 4TVH0144B300NB, 4TVH0144B400NB
69B*
2)0 7B$
+36:
7B&7
&+
+36
26
,19
7B'
&9B'
9B:
+36:
7B&7
&+
V
9B(6
26
,19
7B'
&9B'
9B(%
V
7B&2
&9B(
7B(2
,30&
(
(B0
,&
7B(,
(
(B9
7B/
69B/
2+;
7B6
V
9B+*
V
9B(6
/36
9B$5
V
$&
Classification Description Classification Description
INV Inverter Compressor V_HG Hot Gas Bypass Valve OFM Outdoor Fan Motor V_4W 4way Valve OHX Outdoor Heat Exchanger V_AR Accumulator Oil Return Valve
AC Accumulator CV_E EEV Bypass Check Valve OS Oil Separator CV_D Discharge Check Valve
IC Intercooler T_D Discharge Temperature Sensor
IPMC IPM Cooler T_S Suction Temperature Sensor
CH Crank Case Heater T_CO Condenser Out Temperature Sensor HPS High Pressure Sensor T_EI EVI In Temperature Sensor LPS Low Pressure Sensor T_EO EVI Out Temperature Sensor
HPSW High Pressure Switch T_L Liquid Tube Temperature Sensor
E_M Main EEV T_CT Compressor Top Temperature Sensor E_EV EVI EEV T_A Ambient Temperature Sensor V_ES EVI Solenoid Valve SV_G Gas Pipe Service Valve V_EB EVI Bypass Valve SV_L Liquid Pipe Service Valve
44 VRF-PRC008B-EN
Page 45

Parts of Outdoor Unit (HR)

Figure 22. 4TVR0072B300NB, 4TVR0072B400NB
Cycle Diagrams
&9B+
+36:
+36
&9B'
7B&7
&+
26
,19
9B:
7B'
&9B0&
V
9B0&
V
9B(6
7B6
9B+*
V
9B$5
2)0
2+;
9B(%
7B6
/36
V
$&
7B&2
V
9B2(
&9B(
7B$
7B(2
,30&
V
(
(B0
7B(,
,&
7B/
(
(B(9
69B+*
V
9B+*
69B/*
69B/
Classification Description Classification Description
INV Inverter Compressor V_HG Hot Gas Bypass Valve OFM Outdoor Fan Motor V_4W 4way Valve OHX Outdoor Heat Exchanger V_AR Accumulator Oil Return Valve
AC Accumulator CV_E EEV Bypass Check Valve OS Oil Separator CV_D Discharge Check Valve
IC Intercooler T_D Discharge Temperature Sensor
IPMC IPM Cooler T_S Suction Temperature Sensor
CH Crank Case Heater T_CO Condenser Out Temperature Sensor HPS High Pressure Sensor T_EI EVI In Temperature Sensor LPS Low Pressure Sensor T_EO EVI Out Temperature Sensor
HPSW High Pressure Switch T_L Liquid Tube Temperature Sensor
E_M Main EEV T_CT Compressor Top Temperature Sensor E_EV EVI EEV T_A Ambient Temperature Sensor V_ES EVI Solenoid Valve SV_G Gas Pipe Service Valve V_EB EVI Bypass Valve SV_L Liquid Pipe Service Valve
VRF-PRC008B-EN 45
Page 46
Cycle Diagrams
Figure 23. 4TVR0096B400NB, 4TVR0120B400NB
&9B+
+36:
+36
&9B'
7B&7
&+
26
,19
9B:
7B'
&9B0&
V
9B0&
V
9B(6
7B6
9B+*
V
2+;
9B$5
V
/36
2)02)0
7B&2
9B(%
V
7B6
$&
9B2(
&9B(
7B$
7B(2
,30&
V
(
(B0
7B(,
,&
7B/
(
(B(9
69B+*
V
9B+*
69B/*
69B/
Classification Description Classification Description
INV Inverter Compressor V_HG Hot Gas Bypass Valve OFM Outdoor Fan Motor V_4W 4way Valve OHX Outdoor Heat Exchanger V_AR Accumulator Oil Return Valve
AC Accumulator CV_E EEV Bypass Check Valve OS Oil Separator CV_D Discharge Check Valve
IC Intercooler T_D Discharge Temperature Sensor
IPMC IPM Cooler T_S Suction Temperature Sensor
CH Crank Case Heater T_CO Condenser Out Temperature Sensor HPS High Pressure Sensor T_EI EVI In Temperature Sensor LPS Low Pressure Sensor T_EO EVI Out Temperature Sensor
HPSW High Pressure Switch T_L Liquid Tube Temperature Sensor
E_M Main EEV T_CT Compressor Top Temperature Sensor E_EV EVI EEV T_A Ambient Temperature Sensor V_ES EVI Solenoid Valve SV_G Gas Pipe Service Valve V_EB EVI Bypass Valve SV_L Liquid Pipe Service Valve
46 VRF-PRC008B-EN
Page 47
Cycle Diagrams
Figure 24. 4TVR0096B300NB, 4TVR0120B300NB, 4TVR0144B300NB, 4TVR0144B400NB
&9B'
+36:
7B&7
&+
&9B+
26
,19
+36
7B'
&9B'
+36:
7B&7
&+
V
9B(6
9B:
&9B0&
V
&9B0&
26
7B'
,19
2)02)0
2+;
7B6
V
9B+*
V
9B(6
/36
9B$5
7B&2
7B6
$&
V
7B$
9B2(
&9B(
,30& ,30&
9B(%
7B(2
V
V
(
(B0
7B(,
,&
(
7B/
69B+*
V
9B+*
69B/*
(B(9
69B/
Classification Description Classification Description
INV Inverter Compressor V_HG Hot Gas Bypass Valve OFM Outdoor Fan Motor V_4W 4way Valve OHX Outdoor Heat Exchanger V_AR Accumulator Oil Return Valve
AC Accumulator CV_E EEV Bypass Check Valve OS Oil Separator CV_D Discharge Check Valve
IC Intercooler T_D Discharge Temperature Sensor
IPMC IPM Cooler T_S Suction Temperature Sensor
CH Crank Case Heater T_CO Condenser Out Temperature Sensor HPS High Pressure Sensor T_EI EVI In Temperature Sensor LPS Low Pressure Sensor T_EO EVI Out Temperature Sensor
HPSW High Pressure Switch T_L Liquid Tube Temperature Sensor
E_M Main EEV T_CT Compressor Top Temperature Sensor E_EV EVI EEV T_A Ambient Temperature Sensor V_ES EVI Solenoid Valve SV_G Gas Pipe Service Valve V_EB EVI Bypass Valve SV_L Liquid Pipe Service Valve
VRF-PRC008B-EN 47
Page 48

Dimensional Drawings

Heat Pump/Heat Recovery

Figure 25. 4TVH/R0072B*****
6
2
1
616(24.25)
671(26.42)
5
(a)
880(34.65)
765(30.12)
36(1.42)
557(21.93)
492(19.37)
172(6.77)
6
5
107(4.21)
1695(66.73)
34
7
740(29.13)
761(29.96)
8
(a)Unit: mm (inch)
803(31.61)
No. Name Description No. Name Description
1 Gas Ref. Pipe - 5 Power Wiring Conduit 4(0.16") - Ø43.7(1.72") 2 Liquid Ref. Pipe - 6
3 Power Wiring Conduit 2(0.08") - Ø43.7(1.72") 7
Communication Wiring
4
Conduit
2(0.08") - Ø34.5(1.36") 8 Anchor Bolt Hole 4(0.16") - Ø12(0.47")
Communication Wiring
Conduit
Knock-out Hole for Ref .
Piping
8(0.31") - Ø22.0(0.87")
178 x 76(7" x 3")
48 VRF-PRC008B-EN
Page 49
Dimensional Drawings
Figure 26. 4TVH/R0096B*****, 4TVH/R120B*****, 4TVH/R0144B*****
1295(50.98)
765(30.12)
36(1.42)
6
1695(66.73)
2
1
616(24.25)
671(26.42)
5
241(9.49)
122(4.80)
7
51(2.01)
202(7.95)
43
1150(45.28)
575(22.64)
557(21.93)
(a)
6
5
492(19.37)
172(6.77)
107(4.21)
761(29.96)
8
1295(50.98)
803(31.61)
(a)Unit: mm (inch)
No. Name Description No. Name Description
1 Gas Ref. Pipe - 5 Power Wiring Conduit 4(0.16") - Ø43.7(1.72") 2 Liquid Ref. Pipe - 6
3 Power Wiring Conduit 2(0.08") - Ø43.7(1.72") 7
Communication Wiring
4
Conduit
2(0.08") - Ø34.5(1.36") 8 Anchor Bolt Hole 4(0.16") - Ø12(0.47")
Communication Wiring
Conduit
Knock-out Hole for Ref .
Piping
8(0.31") - Ø22.0(0.87")
178 x 76(7" x 3")
VRF-PRC008B-EN 49
Page 50
Page 51
Page 52
Variable Refrigerant Flow (VRF) Multi-Split AC and HP AHRI Standard 1230
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in
creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2015Trane All rights reserved
VRF-PRC008B-EN 17 Feb 2015
Supersedes VRF-PRC008-EN (31 July 2013)