Industrial Power Supplies
|
|
|
|
|
TIS Series |
|
75 - 600 Watt |
||
|
|
|
|
|
|
||||
|
|
|
|
||||||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Features
Switch mode power supplies for DIN-rail mounting
4 power ranges with 3, 6, 12 and 24 A output current (24 VDC models)
Selectable 115/ 230 VAC input Very low ripple and noise
EMI complies with EN50081-2 and EN50082-2
Conducted EMI to EN55011 class B
For system operation available with built-in functions:
RED: Redundancy module for N+1 systems with true current sharing.
SIG: Signal module with AC-Power- fail, DCOK Signal and external ON/OFF control
UDS: DC-UPS module for uninterruptable battery backed-up power systems.
Worldwide Safety Approvals
Easy snap-on mounting on DIN-rails or chassis mounting
2 Year Product Warranty
The switching power supplies of the TIS series have been particulary designed for applications in industrial process control systems and machine tools. Excellent specifications and high immunity against electrical disturbances guarantee reliable power for sensitive loads in rugged industrial environments. With help of optional function modules specific requirements for system applications can be met by a standard product. With the UDS module the power supplies can be extended to a perfect DC-UPS with automatic batterybackup. This function is very often required in applications where a time delayed shutdown of a system is necessary. To monitor and control the power supply a signal module can be installed. For parallel operation with active power sharing a redundancy option is available. This flexibility makes the TIS series power supplies a cost effective solution for many industrial applications.
Models
Ordercode |
Input Voltage |
Output Power |
Output Voltage |
Output Current |
|
(includes terminal plugs) |
|
max. |
nom. |
max. |
|
|
|
|
|
|
|
TIS 75-112 |
115 / 230 VAC |
|
12 VDC |
6.0 A |
|
TIS 75-124 |
75 W |
24 VDC |
3.0 A |
||
selectable |
|||||
TIS 75-148 |
|
48 VDC |
1.5 A |
||
|
|
||||
TIS 150-124 |
115 / 230 VAC |
150 W |
24 VDC |
6.0 A |
|
TIS 150-148 |
selectable |
48 VDC |
3.0 A |
||
|
|||||
TIS 300-124 |
115 / 230 VAC |
|
24 VDC |
12 A |
|
TIS 300-148 |
300 W |
48 VDC |
6.0 A |
||
selectable |
|||||
TIS 300-172 |
|
72 VDC |
4.2 A |
||
|
|
||||
TIS 500-124 |
230 VAC |
500 W |
24 VDC |
20 A |
|
TIS 600-124 |
|
|
24 VDC |
24 A |
|
TIS 600-128 |
115 / 230 VAC |
600 W |
28 VDC |
22 A |
|
TIS 600-148 |
selectable |
48 VDC |
12 A |
||
|
|||||
TIS 600-172 |
|
|
72 VDC |
8.5 A |
|
TIS 300-124 DCI |
300 - 800 VDC |
300 W |
24 VDC |
12 A |
|
|
|
|
|
|
http://www.tracopower.com |
Page 1 |
Industrial Power Supplies
TIS Series 75-600 Watt
Input Specifications
Input voltage range – TIS 75, TIS 150, TIS 300, TIS 600 |
93 – 132 VAC / 187 – 264 VAC |
||
– TIS 500 |
|
|
187 – 264 VAC |
– TIS 300 DCI |
|
|
300 – 800 VDC |
Input frequency |
47 – 63 Hz |
|
|
Input current at full load (typ.) |
115 VAC |
230 VAC |
|
– TIS 75 |
1.7 A |
|
0.9 A |
– TIS 150 |
3.0 A |
|
1.7 A |
– TIS 300 |
5.4 A |
|
3.3 A |
– TIS 500 |
|
|
5.5 A |
– TIS 600 |
10.5 A |
|
6.4 A |
Inrush current (< 2 ms) |
115 VAC |
230 VAC |
|
– TIS 75 |
< 16.5 A |
< 33 A |
|
– TIS 150 |
< 35 |
A |
< 70 A |
– TIS 300 |
< 35 |
A |
< 70 A |
– TIS 500 |
|
|
< 70 A |
– TIS 600 |
< 70 |
A |
< 80 A |
Output Specifications |
|
|
|
Output voltage adj. range – 12 VDC models |
12 – 14 VDC |
|
|
– 24 VDC models |
24 – 28 VDC |
|
|
– 28 VDC models |
28 – 32 VDC |
|
|
– 48 VDC models |
48 – 52 VDC (48 – 55 VDC on request)) |
||
– 72 VDC models |
60 – 76 VDC |
|
|
Regulation – Input variation |
± 0.2 % max. |
|
|
– Load variation (10 – 90%) – TIS 75, TIS 150 |
± 1.0 % max. |
|
|
– TIS 300, TIS 500, TIS 600 |
± 0.3 % max. |
|
|
|
(± 1.5 % in parallel operation) |
||
|
|
|
|
Ripple and Noise (20MHz Bandwidth) |
< 50 mV pk-pk |
|
|
Electronic short circuit protection |
current limitation at 110 % typ. |
||
|
(constant current, automatic restart) |
||
|
|
||
Overvoltage protection, triggerpoint at |
140 % typ. Vout nom. |
||
|
|
|
|
Hold-up time |
115 VAC |
230 VAC |
|
– TIS 75 ... TIS 300 |
min. 25 ms |
min. 30 ms |
|
– TIS 500 |
|
|
min. 40 ms |
– TIS 600 |
min. 15 ms |
min. 25 ms |
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com |
Page 2 |
Industrial Power Supplies
TIS Series 75-600 Watt
General Specifications
|
Temperature ranges |
– Operating (ambient temp.) |
– 25 °C…+70 °C max. |
|
|
|
– Derating above 50 °C |
2% /°C |
|
|
|
– Storage (non operating) |
– 25 °C…+ 85 °C |
|
|
Humidity (non condensing) |
95 % rel H max. |
|
|
|
Temperature coefficient |
0.02 % / °C |
|
|
|
|
|
|
|
|
Switching frequency |
|
80 kHz typ. (Pulswidth modulation) |
|
|
|
|
|
|
|
Efficiency |
– TIS 75 ... TIS 300 |
85 % typ. |
|
|
|
– TIS 500 |
90 % typ. |
|
|
|
– TIS 600 |
88 % typ. |
|
|
Isolation |
|
according to EN 60950, UL 1950, UL 508C |
|
|
Reliability, calculated MTBF (MIL-HDBK-217 E) – TIS 75 /150 |
450000 h @ +25°C/ 420000 h @ +25°C |
||
|
|
– TIS 300 /500 |
360000 h @ +25°C/ 340000 h @ +25°C |
|
|
|
– TIS 600 |
300000 h @ +25°C |
|
|
Safety standards |
|
IEC 60950, EN 60950 (SELV), |
|
|
|
|
UL/cUL 1950, UL 508C |
|
|
|
|
|
|
|
Safety approvals |
|
UL/cUL 1950 recognized, File E18138 |
|
|
|
|
UL/cUL 508C listed, File E210002 |
|
|
|
|
UL/cuL 1604 listed, File E213613 (Class I,Division |
|
|
|
|
2, Groups A, B, C and D hazardous locations) |
|
|
|
|
CB-Scheme |
|
|
|
|
||
|
Electromagnetic compatibility (EMC), Emissions |
EN 50081-1 / EN 50081-2 |
||
|
– Conducted RI suppression on input |
EN 55011 class B, EN 55022 class B, |
||
|
|
|
FCC part 15, level B |
|
|
– Radiated RI suppression |
EN 55011 class A, EN 55022 class A, |
||
|
|
|
FCC part 15, level A |
|
|
|
|
|
|
|
Electromagnetic compatibility (EMC), Immunity |
EN 50082-2 |
|
|
|
– Electrostatic discharge (ESD) |
IEC / EN 61000-4-2 |
4 kV / 8 kV |
|
|
– Radiated RF field immunity |
IEC / EN 61000-4-3 |
10 V / m |
|
|
– Electrical fast transient / burst immunity |
IEC / EN 61000-4-4 |
2 kV |
|
|
– Surge immunity |
|
IEC / EN 61000-4-5 |
2 kV / 4 kV |
|
– Immunity to conducted RF disturbances |
IEC / EN 61000-4-6 |
10 V |
|
|
– Power frequency field immunity |
IEC / EN 61000-4-8 |
30 A / m |
|
|
Safety class |
|
Degree of Protection 1 (IEC 536) |
|
|
Case protection |
|
IP 20 (IEC 529) |
|
|
Environment |
– Vibration |
IEC 60068-2-6,1 gn, 200 sweeps, each axis |
|
|
|
– Shock |
IEC 60068-2-27, 15 gn, 11 ms, each axis |
|
|
|
|
|
|
|
Enclosure material |
|
Aluminium (chassis) / stainless steel (cover) |
|
|
Mounting (snap-on with selflocking spring) |
for 35 mm DIN-rails as per EN 50022 |
||
|
Connection |
|
Plugable screw terminals (plugs included) |
|
|
|
|
(TIS 600: screw terminal blocks) |
|
|
|
|||
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated. |
||||
|
|
|
|
|
http://www.tracopower.com |
|
Page 3 |
Industrial Power Supplies
|
|
|
|
|
TIS Series |
75-600 Watt |
|
|
|
|
|
||
|
|
|
|
|
||
|
|
|
|
|
|
|
PowerOptionalSuppliesMountingwithSystemsRedundancyDimensionsFunctionmm (inches)
With this option a parallel operation of up to 5 units is possible. Decoupling diodes and current share lines allow to build true N +1 redundant systems with active current sharing for all units. This function also includes an alarm relay to signal a single unit failure.
This option is available for TIS 150 W, TIS 300 W and TIS 600 W models. Please note: A combination with other options is not possible.
Models
Ordercode |
Input Voltage |
Output Power |
Output Voltage |
Output Current |
|
(includes terminal plugs) |
|
max. |
nom. |
max. |
|
|
|
|
|
|
|
TIS 150-124 RED |
115 / 230 VAC |
150 W |
24 VDC |
6.0 A |
|
TIS 150-148 RED |
selectable |
18 VDC |
12 A |
||
|
|||||
TIS 300-124 RED |
115 / 230 VAC |
300 W |
24 VDC |
12 A |
|
TIS 300-148 RED |
selectable |
48 VDC |
6.0 A |
||
|
|||||
TIS 600-124 RED |
115 / 230 VAC |
600 W |
24 VDC |
24 A |
|
TIS 600-148 RED |
selectable |
48 VDC |
12 A |
||
|
|||||
|
|
|
|
|
115/230VAC
Con1
L Pin3
Con1
N Pin2
Con1
Pin1
AC
DC
|
|
Con2 - Pin3/4 |
+Vout |
|
|
|
Bus |
24/48VDC |
|
|
|
Indicator |
|
|
|
|
Con2 - Pin1/2 |
-Vout |
|
|
|
|
||
I-Sense |
V-Sense |
Con3 - Pin4 |
Current |
|
Share- |
||||
|
|
|
||
|
|
|
line |
|
|
|
Con3 - Pin3 |
Unit OK |
|
|
|
Con3 - Pin2 |
||
|
|
Common |
||
|
|
Con3 - Pin1 |
||
Regulator |
|
Unit OK |
||
|
|
|||
|
|
Unit |
|
|
|
|
OK |
|
Specifications
Raiting per relay contact |
60 VDC /0.36 A max. |
|
|
Specifications can be changed without notice
http://www.tracopower.com Page 4