Toshiba RAV-SP1100AT-E SERVICE MANUAL

FILE NO. A03-003F
SERVICE MANUAL/INTEGRATION
SPLIT TYPE
OUTDOOR UNIT
<SUPER DIGITAL INVERTER>
RAV-SP560AT-E, RAV-SP800AT-E, RAV-SP1100AT-E, RAV-SP1400AT-E
RAV-SM560AT-E, RAV-SM800AT-E, RAV-SM1100AT-E, RAV-SM1400AT-E
INDOOR UNIT
<SUPER DIGITAL INVERTER>
RAV-SP1100UT-E
RAV-SM560UT-E, RAV -SM560BT-E, RAV -SM561BT-E, RAV-SM561CT-E,
RAV-SM800UT-E, RAV -SM800BT-E, RAV -SM801BT-E, RAV-SM801CT-E,
RAV-SM1100UT-E, RAV-SM1101CT-E, RAV-SM1101BT-E,
RAV-SM1400UT-E, RAV-SM1401CT-E, RAV-SM1401BT-E
R410A
PRINTED IN JAPAN, Jun.,2004 ToMo
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the con ventional refrigerant R22 in order to prevent destruction of the oz one layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to ha ve a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there f or the service person, and not for the customer.
Service Manual Table
FILE NO. for Owner’s Manual / Service Manual
Type
RAV- name
SM560 O/M
S/M
SM800 O/M
S/M
SM1100 O/M
S/M
SM1400 O/M
S/M
SP1100 O/M
S/M
Indoor unit
BT-E
UT-E
A02-013 A02-013 A03-006 A03-015 A02-014 A02-014 A03-007 A03-016
A02-013 A02-013 A03-006 A03-015 A02-014 A02-014 A03-007 A03-016
A03-002 A03-006 A03-015 A03-003 A03-007 A03-016
A03-002 A03-006 A03-015 A03-003 A03-007 A03-016
A03-013 — A03-014
AC motor DC motor
SM
0BT-E SM
SM
∗∗∗∗
∗∗
∗∗∗∗
∗∗∗∗∗∗
∗∗∗
∗∗∗∗∗∗
0BT-E SM
∗∗∗∗
∗∗
∗∗∗∗
∗∗∗∗∗∗
∗∗∗
∗∗∗∗∗∗
∗ ∗
1BT-E SM
1BT-E SM
O/M : OWNER’S MANUAL, INSTALLATION MANUAL S/M : SERVICE MANUAL
CT-E
∗∗∗∗
∗∗
∗∗∗∗
∗∗∗∗∗∗
∗∗∗
∗∗∗∗∗∗
1CT-E
1CT-E
Outdoor unit
AT-E SP
SP
AT-E
∗∗∗∗
∗∗
∗∗∗∗
SP
A02-013 A03-013 A02-014 A03-014
A02-013 A03-013 A02-014 A03-014
A03-002 A03-013 A03-003 A03-014
A03-002 A03-013 A03-003 A03-014
A03-013
AT-E
∗∗∗∗∗∗
∗∗∗
∗∗∗∗∗∗
A03-014
Concerning models for RAV -SM company ;
NO TICE
KRT-E, and RAV -SM
∗∗∗∗∗∗∗∗
∗∗∗∗
∗∗∗∗∗∗∗∗
Toshiba Carrier (Thailand) Co., Ltd. 144/9 Moo 5, BangKadi Indastrial park, Tivanon Road, Tambol BangKadi, Amphur Muang, Pathumthani 12000, Thailand
Tel : +66-2-501-1390 Fax : +66-2-501-1130
XT-E series, please contact the follo wing
∗∗∗∗∗∗∗∗
∗∗∗∗
∗∗∗∗∗∗∗∗
CONTENTS
1. SPECIFICATIONS ................................................................................................................................ 4
1-1. Indoor Unit ...........................................................................................................................................................4
1-2. Outdoor Unit...................................................................................................................................................... 10
1-3. Combination Specifications of Indoor Units with Outdoor Units ................................................................ 14
1-4. Operation Characteristic Cur ve ............................................................................................. ......................... 17
2. AIR DUCTING WORK ........................................................................................................................ 24
2-1. Static Pressure Characteristics of Each Model ............................................................................................. 24
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS) ............................................................................... 27
3-1. Indoor Unit ........................................................................................................................................................ 27
3-2. Outdoor Unit...................................................................................................................................................... 32
4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM....................................................................... 35
4-1. Indoor Unit/Outdoor Unit ................................................................................................................................. 35
5. WIR ING DI AGRAM............................................................................................................................. 43
5-1. Indoor Unit ........................................................................................................................................................ 43
5-2. Outdoor Unit...................................................................................................................................................... 47
6. SPECIFICATIONS OF ELECTRICAL PARTS ................................................................................... 50
6-1. Indoor Unit ........................................................................................................................................................ 50
6-2. Outdoor Unit...................................................................................................................................................... 52
6-3. Accessory Separate Soldparts ....................................................................................................................... 54
7. REFRIGERANT R410A ..................................................................................................................... 55
7-1. Safety During Installation/Servicing ............................................................................................................... 55
7-2. Refrigerant Piping Installation ...................................................................................................................... 55
7-3. Tools .................................................................................................................................................................. 59
7-4. Recharging of Refrigerant ............................................................................................................................... 60
7-5. Brazing of Pipes ............................................................................................................................................... 61
8. CONTROL BLOCK DIAGRAM .......................................................................................................... 63
8-1. Indoor Control Circuit ...................................................................................................................................... 63
8-2. Control Specifications ..................................................................................................................................... 65
8-3. Indoor Print Circuit Board................................................................................................................................ 65
9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS ................................................... 87
9-1. Microcomputer System Block Diagram.......................................................................................................... 87
9-2. Indoor Control Circuit ...................................................................................................................................... 95
9-3. Outdoor Controls .............................................................................................................................................. 98
10. TROUBLESHOOTING ..................................................................................................................... 117
10-1. Summary of Troubleshooting ........................................................................................................................ 117
10-2. Check Code List ............................................................................................................................................. 119
10-3. Error Mode Detected by LED on Outdoor P.C. Board.................................................................................. 122
10-4. Troubleshooting Procedure for Each Check Code...................................................................................... 125
11. REPLACEMENT OF SERVICE INDOOR P.C. BOARD .................................................................. 146
12. SETUP AT LOCAL SITE AND OTHERS ......................................................................................... 150
12-1. Indoor Unit ...................................................................................................................................................... 150
12-2. Network Adapter ............................................................................................................................................. 159
12-3. How to Set an Address Number .................................................................................................................... 161
12-4. Display and Operation of Main Remote Controller and Central Control Remote Controller .................. 163
13. ADDRESS SETUP ........................................................................................................................... 164
13-1. Address Setup ................................................................................................................................................ 164
13-2. Address Setup & Group Control ................................................................................................................... 165
13-3. Address Setup ................................................................................................................................................ 166
14. DETACHMENTS............................................................................................................................... 169
14-1. Indoor Unit ..................................................................................................................................................... 169
14-2. Outdoor Unit.................................................................................................................................................... 187
15. EXPLODED VIEWS AND PA RTS LIST ........................................................................................... 211
15-1. Indoor Unit ...................................................................................................................................................... 211
15-2. Outdoor Unit.................................................................................................................................................... 227
15-3. Replacement of Main Parts (Sold Separately) ............................................................................................. 237
16. CORD HEATER INSTALLATION WORK......................................................................................... 239
APPENDIX-1
1. SDI combination, Indoor / Outdoor .........................................................................................................................1
2. Service parts for 4-way Cassette Type ....................................................................................................................1
3. Specification for Concealed Duct Type ...................................................................................................................2
4. Service parts for Concealed Duct Type ..................................................................................................................2
5. Service parts for Under Ceiling Type ......................................................................................................................3
6. Service PCB Replacement .......................................................................................................................................4
7. Indoor unit & Remote controller ..............................................................................................................................5
8. Connecting cable for Remote controllers ..............................................................................................................5
– 3 –

1. SPECIFICATIONS

1-1. Indoor Unit
1-1-1. 4-Way Air Discharge Cassette Type
RAV-SM560UT-E, RAV-SM800UT-E (A02-014)
RAV-SM560/800UT-E
Model name
Standard capacity (Note 1) (kW)
Heating low temp. capacity (Note 1) (kW) Energy consumption effect ratio (Cooling)
Power supply Running current (A)
Electrical characteristics
Appearance
Outer dimension
Power consumption (kW) (Low temp.) (kW) Power factor (%) Main unit
Ceiling Panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
RAV-SM560UT-E RAV-SM800UT-E
Cooling Heating Average Cooling Heating Average
5.3 5.6 7.1 8.0
(1.5 – 5.6) (1.5 – 6.3) (2.2 – 8.0) (2.2–9.0)
4.9 7
3.01 [B] 3.90 [A] 3.46 3.03 [B] 3.45 [B] 3.24 1 phase 230V (220 – 240V) 50Hz
8.42–7.72 6.78–6.29 11.32–10.37 11.22–10.28
1.76 1.435 2.34 2.32
1.89 2.73
95 95 94 94
Zinc hot dipping steel plate
RBC-U21PG (W) E
Moon-white (Muncel 2.5GY 9.0/0.5)
256 840 840
53 950 950
Total weight
Heat exchanger Soundproof/Heat-insulating material
Fan unit Standard air flow High (Mid./Low) (m³/h)
Air filter Controller (Sold separately)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Main unit (kg) Ceiling panel
Fan
Motor (W)
Gas side (mm) Liquid side (mm) Drain port (Nominal dia.)
Inflammable polyethylene foam Foamed polyethylen
32 29 27 34 31 28
21 22
4.5
Finned tubu
Turbo fan
1050 1200
60
Attached ceiling panel
RBC-AMT21E
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
25 (Polyvinyl chloride tube)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 4 –
RAV-SM1100UT-E, RAV-SM1400UT-E (A03-003)
RAV-SM1100/1400UT-E
Model name
Standard capacity (Note 1) (kW)
Energy consumption effect ratio (Cooling)
Power supply
Electrical characteristics
Appearance
Outer dimension
Running current (A)
Power consumption (kW)
Power factor (%)
Main unit
Ceiling Panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Model
Panel color
Height (mm)
Depth (mm)
Height (mm)
Width (mm)
Depth (mm)
RAV-SM1100UT-E RAV-SM1400UT-E
Cooling Heating Average Cooling Heating Average
10.0 11.2 12.3 14.0
(2.2 – 11.2) (2.2 – 13.0) (3.0 – 13.2) (3.0 – 16.0)
2.84 3.22 3.03 3.01 3.50 3.26
1 phase 230V (220 – 240V) 50Hz
16.3–15.0 16.1–14.8 19.2–17.6 18.7–17.2
3.52 3.48 4.09 4.00
98 98 97 97
Zinc hot dipping steel plate
RBC-U21PG (W)-E
Moon-white (Muncel 2.5GY 9.0/0.5)
319
840
840
35
950
950
Total weight
Heat exchanger
Fan unit Standard air flow High (Mid./Low) (m³/h)
Air filter
Controller (Sold separately)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Main unit (kg)
Ceiling panel
Fan
Motor (W)
Gas side (mm)
Liquid side (mm)
Drain port (Nominal dia.)
1680 1980
Attached ceiling panel
25 (Polyvinyl chloride tube)
39 36 33 42 38 34
26
4.5
Finned tubu
Turbo fan
90
RBC-AMT21E
Ø15.9 (5/8”)
Ø9.5 (3/8”)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 5 –
RAV-SP1100UT-E (A03-014)
RAV-SP1100UT-E
Appearance
Outer dimension
Total weight
Heat exchanger
Model name
Main unit
Ceiling Panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel
Fan
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
RAV-SP1100UT-E
Zinc hot dipping steel plate
RBC-U21PG (W)-E
Moon-white (Muncel 2.5GY 9.0/0.5)
319 840 840
35 950 950
26
4.5
Finned tube
Turbo fan
Fan unit Standard air flow High (Mid./Low) (m³/h)
Motor (W) Air filter Controller (Sold separately)
Gas side (mm) Connecting pipe Liquid side (mm)
Drain port (Nominal dia.)
1680
90
Attached ceiling panel
RBC-AMT21E
Ø15.9 (5/8”)
Ø9.5 (3/8”)
25 (Polyvinyl chlor ide tube)
– 6 –
1-1-2. Concealed Duct Type
RAV-SM560BT-E, RAV-SM800BT-E (A02-014)
RAV-SM560/800BT-E
Model name
Standard capacity (Note 1) (kW)
Heating low temp. capacity (Note 1) (kW) Energy consumption effect ratio (Cooling)
Power supply
Running current (A) Electrical characteristics
Appearance
Power consumption (kW)
(Low temp.) (kW)
Power factor (%)
Main unit
Ceiling Panel
(Sold separately)
Main unit Width (mm)
Model Panel color Height (mm)
RAV-SM560BT-E RAV-SM800BT-E
Cooling Heating Average Cooling Heating Average
5 5.6 7.1 8
(1.5 – 5.6) (1.5 – 6.3) (2.2 – 8.0) (2.2–9.0)
4.6 6.2
2.60 [D] 3.27 [C] 2.94 2.73 [D] 3.21 [C] 2.97 1 phase 230V (220 – 240V) 50Hz
9.19–8.42 8.18–7.50 12.57–11.52 12.04–11.04
1.92 1.71 2.6 2.49
1.78 2.62
95 95 94 94
Zinc hot dipping steel plate
—— ——
320 700
Outer dimension
Ceiling panel (Sold separately)
Total weight
Heat exchanger Soundproof/Heat-insulating material
Fan unit Standard air flow High (Mid./Low) (m³/h)
Air filter Controller (Sold separately)
Connecting pipe
Main unit (kg) Ceiling panel
Fan
Motor (W)
Gas side (mm) Liquid side (mm) Drain port (Nominal dia.)
Depth (mm) Height (mm) Width (mm) Depth (mm)
800 (+7.5)
—— —— ——
39 53
——
Finned tubu
Inflammable polyethylene foam Foamed polyethylen
Turbo fan
840 1140
60 100
Attached main unit
RBC-AMT21E
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
25 (Polyvinyl chloride tube)
Sound level High (Mid./Low) (Note 2) (dB•A)
42 39 36 43 40 37
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 7 –
RAV-SM561BT-E, RAV-SM801BT-E (A03-007)
RAV-SM561/801BT-E
Model name
Standard capacity (Note 1) (kW)
Heating low temp. capacity (Note 1) (kW) Energy consumption effect ratio (Cooling)
Power supply Running current (A)
Electrical characteristics
Appearance
Outer dimension
Power consumption (kW) (Low temp.) (kW) Power factor (%) Main unit
Ceiling Panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
RAV-SM561BT-E RAV-SM801BT-E
Cooling Heating Average Cooling Heating Average
5.0 5.6 7.1 8.0
(1.5 – 5.6) (1.5 – 6.3) (2.2 – 8.0) (2.2 – 9.0)
4.6 6.2
2.81 [C] 3.27 [C] 3.04 2.81 [C] 3.32 [C] 3.07 1 phase 230V (220 – 240V) 50Hz
8.99–8.24 8.18–7.50 12.23–11.21 11.65–10.68
1.78 1.71 2.53 2.41
1.98 2.86
95 95 94 94
Zinc hot dipping steel plate
—— ——
320 320 700 1000 800 800
—— —— ——
Total weight
Heat exchanger Soundproof/Heat-insulating material
Fan unit Standard air flow High (Mid./Low) (m³/h)
Air filter Controller (Sold separately)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Main unit (kg) Ceiling panel
Fan
Motor (W)
Gas side (mm) Liquid side (mm) Drain port (Nominal dia.)
42 39 36 43 40 37
30 39
——
Finned tubu
Inflammable polyethylene foam
Multi-blade fan 840 1140 120 120
Attached main unit
RBC-AMT21E
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
25 (Polyvinyl chloride tube)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 8 –
RAV-SM1101BT-E, RAV-SM1401BT-E (A03-007)
RAV-SM1101/1401BT-E
Model name
Standard capacity (Note 1) (kW)
Heating low temp. capacity (Note 1) (kW) Energy consumption effect ratio (Cooling)
Power supply Running current (A)
Electrical characteristics
Appearance
Outer dimension
Power consumption (kW) (Low temp.) (kW) Power factor (%) Main unit
Ceiling Panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
RAV-SM1101BT-E RAV-SM1401BT-E
Cooling Heating Average Cooling Heating Average
10.0 11.2 12.5 14.0
(2.2 – 11.2) (2.2 – 12.5) (3.0 – 13.2) (3.0 – 16.0)
8.7 11.8
2.81 [C] 3.57 [B] 3.19 2.83 [C] 3.47 [B] 3.15 1 phase 230V (220 – 240V) 50Hz
16.5–15.1 14.6–13.4 20.7–19.0 18.9–17.3
3.56 3.14 4.42 4.03
3.50 4.18
98 98 97 97
Zinc hot dipping steel plate
—— ——
320
1340
800
—— —— ——
Total weight
Heat exchanger Soundproof/Heat-insulating material
Fan unit Standard air flow High (Mid./Low) (m³/h)
Air filter Controller (Sold separately)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Main unit (kg) Ceiling panel
Fan
Motor (W)
Gas side (mm) Liquid side (mm) Drain port (Nominal dia.)
42 39 36 44 41 38
54 54
——
Finned tubu
Inflammable polyethylene foam
Multi-blade fan
1620 1980
120 120
Attached main unit
RBC-AMT21E
Ø15.9 (5/8”)
Ø9.5 (3/8”)
25 (Polyvinyl chloride tube)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 9 –
1-1-3. Under Ceiling Type
RAV-SM561CT-E, RAV-SM801CT-E (A03-016)
RAV-SM561/801CT-E
Model name
Standard capacity (Note 1) (kW)
Energy consumption effect ratio (Cooling)
Power supply
Electrical characteristics
Appearance Main unit
Outer dimension
Total weight Main unit (kg)
Running current (A)
Power consumption (kW)
Power factor (%)
Height (mm)
Main unit Width (mm)
Depth (mm)
RAV-SM561CT-E RAV-SM801CT-E
Cooling Heating Average Cooling Heating Average
5.0 5.6 7.0 8.0
(1.5 – 5.6) (1.5 – 6.3) (2.2 – 8.0) (2.2 – 9.0)
2.75 [D] 3.41 [B] 3.08 2.77 [D] 3.24 [C] 3.01
1 phase 230V (220 – 240V) 50Hz
8.71–7.98 7.85–7.19 12.23–11.21 11.94–10.95
1.82 1.64 2.53 2.47
95 95 94 94
Shine white
210 210
680 680
910 1180
20 25
Heat exchanger
Soundproof/Heat-insulating material
Fan
Fan unit Standard air flow High (Mid./Low) (m³/h)
Motor (W)
Air filter
Controller (Sold separately)
Gas side (mm)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Liquid side (mm)
Drain port (Nominal dia.)
Inflammable polyethylene foam
840 1140
60 60
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
36 33 30 38 36 33
Finned tubu
Multi-blade fan
Attached main unit
RBC-AMT21E
25 (Polyvinyl chloride tube)
Note 1 : The cooling and heating capacities and electrical characteristics are measured under the conditions specified by JIS B
8616 based on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 10 –
RAV-SM1101CT-E, RAV-SM1401CT-E (A03-016)
RAV-SM1101/1401CT-E
Model name
Standard capacity (Note 1) (kW)
Energy consumption effect ratio (Cooling)
Power supply
Electrical characteristics
Appearance Main unit
Outer dimension
Total weight Main unit (kg)
Running current (A)
Power consumption (kW)
Power factor (%)
Height (mm)
Main unit Width (mm)
Depth (mm)
RAV-SM1101CT-E RAV-SM1401CT-E
Cooling Heating Average Cooling Heating Average
10.0 11.2 12.3 14.0
(2.2 – 11.2) (2.2 – 12.5) (3.0 – 13.2) (3.0 – 16.0)
2.85 [C] 3.50 [B] 3.18 2.72 [D] 3.38 [C] 3.05
1 phase 230V (220 – 240V) 50Hz
16.2–14.9 14.84–13.61 21.18–19.40 19.40–17.78
3.51 3.20 4.52 4.14
98 98 97 97
Shine white
210
680
1595
42
Heat exchanger
Soundproof/Heat-insulating material
Fan
Fan unit Standard air flow High (Mid./Low) (m³/h)
Motor (W)
Air filter
Controller (Sold separately)
Gas side (mm)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Liquid side (mm)
Drain port (Nominal dia.)
Inflammable polyethylene foam
1620 1980
120 120
41 38 35 43 40 37
Finned tubu
Multi-blade fan
Attached main unit
RBC-AMT21E
Ø15.9 (5/8”)
Ø9.5 (3/8”)
25 (Polyvinyl chloride tube)
Note 1 : The cooling and heating capacities and electrical characteristics are measured under the conditions specified by JIS B
8616 based on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 11 –
1-2. Outdoor Unit
RAV-SM560AT-E, RAV-SM800AT-E (A02-14)
RAV-SM560/800AT-E
Model name Appearance
Power supply
Type
Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Standard length
Max. total length (m) Pipe Over 20m
Outdoor lower (m) Outdoor higher (m)
Outer dimension
Height difference
Height (mm)
Width (mm)
Depth (mm)
RAV-SM560AT-E RAV-SM800AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
1.1 1.6 4 poles
R410A 0.9 R410A 1.5
Pulse motor valve
20 (without additional charge)
30 50
Add 20g/m (Max. 200g) Add 40g/m (Max. 1200g)
15
30 595 795 780 780 270 270
Total weight (kg) Heat exchanger
Fan
Fan unit Standard air flow High (m³/h)
Motor (W)
Connecting pipe
Protection device
Sound level High (Mid./Low) (Note 2) (Cooling/Heating)
Gas side (mm) Liquid side (mm)
(dBA)
35 55
Finned tube
Propeller fan
2400 3400
43 63
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor
Compressor thermo.
46/48 45/50
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 12 –
RAV-SM1100AT-E, RAV-SM1400AT-E (A03-003)
RAV-SM1100/1400AT-E
Model name
Appearance
Power supply
Type
Compressor Motor (kW)
Pole
Refrigerant charged (kg)
Refrigerant control
Standard length
Max. total length (m)
Pipe Over 20m
Outdoor lower (m)
Outdoor higher (m)
Outer dimension
Height difference
Height (mm)
Width (mm)
Depth (mm)
RAV-SM1100AT-E RAV-SM1400AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
2.0 3.75
4 poles
R410A 2.1 R410A 2.3
Pulse motor valve
20 (without additional charge)
50
Add 40g/m (Max. 1200g)
15
30
1340
900
320
Total weight (kg)
Heat exchanger
Fan
Fan unit Standard air flow High (m³/h)
Motor (W)
Connecting pipe
Protection device
Sound level High (Mid./Low) (Note 2) (Cooling/Heating)
Gas side (mm)
Liquid side (mm)
(dBA)
75 85
Finned tube
2 propeller fans
6800 7500
63 + 43 63 + 63
Ø15.9 (5/8”)
Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor
Compressor thermo.
53/54 53/54
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 13 –
RAV-SP560AT-E, RAV-SP800AT-E (A03-14)
RAV-SP560/800AT-E
Model name
Appearance
Power supply
Type
Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Standard length (m)
Max. total length (m) Pipe
Over
Outdoor lower (m)
Height difference
Outdoor higher (m)
RAV-SP560AT-E RAV-SP800AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
2.0
4 poles
R410A 1.5 R410A 2.1
Pulse motor valve
20 30
(without additional charge) (without additional charge)
50
Over 20m : Add 20g/m Over 30m : Add 40g/m
(Max. 600g) (Max. 800g)
15 30
Height (mm) Outer dimension Width (mm)
Depth (mm) Total weight (kg) Heat exchanger
Fan Fan unit Standard air flow High (m³/h)
Motor (W)
Gas side (mm) Connecting pipe
Liquid side (mm)
Protection device
Sound level (Note 2)
(Cooling/Heating) (dBA)
795 900 320
55 62
Finned tube
Propeller fan
3400
63
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor Compressor thermo.
46/47 47/49
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
on the reference piping 7.5m. the actual operating environment become larger than the indicated values due to the effects of external sound.
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 14 –
RAV-SP1100AT-E, RAV--SP1400AT-E (A03-14)
RAV-SP1100/1400AT-E
Model name
Appearance
Power supply
Type Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Standard length (m)
Max. total length (m) Pipe Over 30m
Outdoor lower (m)
Height difference
Outdoor higher (m)
RAV-SP1100AT-E RAV-SP1400AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
3.75
4 poles
R410A 2.95
Pulse motor valve
30 (without additional charge)
70
Add 40g/m (Max. 1600g)
15 30
Height (mm) Outer dimension Width (mm)
Depth (mm) Total weight (kg) Heat exchanger
Fan Fan unit Standard air flow High (m³/h)
Motor (W)
Gas side (mm) Connecting pipe
Liquid side (mm)
Protection device
Sound level (Note 2)
(Cooling/Heating) (dBA)
1340
900 320
95
Finned tube
2 Propeller fans
7500
63 + 63
Ø15.9 (5/8”)
Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor Compressor thermo.
49/51 53/54
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
on the reference piping 7.5m. the actual operating environment become larger than the indicated values due to the effects of external sound.
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 15 –
1-3. Combination Specifications of Indoor Units with Outdoor Units
4-way Air Discharge Cassette type
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SP1100UT-E, RAV-SM1400UT-E RAV-SP560AT-E, RAV-SP800AT-E, RAV-SP1100AT-E, RAV-SP1400AT-E
Indoor Unit Outdoor Unit
Standard capacity (Note 1) (kW)
Energy consumption effect ratio
Power supply
Electrical characteristics Power
Sound level High/Mid./Low Indoor unit (Note 2) (dB•A)
Running current (A)
consumption Power factor (%)
(kW)
Concealed Duct type
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E RAV-SP560AT-E, RAV-SP800AT-E, RAV-SP1100AT-E, RAV-SP1400AT-E
Indoor Unit Outdoor Unit
Standard capacity (Note 1) (kW)
Energy consumption effect ratio
Power supply
Electrical characteristics Power
Sound level High/Mid./Low Indoor unit (Note 2) (dB•A)
Running current (A)
consumption Power factor (%)
(kW)
RAV-SM560UT-E RAV-SM800UT-E RAV-SP1100UT-E RAV-SM1400UT-E
RAV-SP560AT-E RAV-SP800AT-E RAV-SP1100AT-E RAV-SP1400AT-E
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5.30 5.60 7.10 8.00 10.00 11.20 12.50 14.00
(2.20-5.60) (2.20-7.10) (2.20-8.00) (2.20-10.00) (3.00-12.00) (3.00-13.00) (3.00-14.00) (3.00-16.50)
3.46 4.67 3.68 3.94 4.17 4.27 3.51 3.91 1 phase 230V (220-240V) 50Hz
7.17-6.57 5.62-5.15 8.95-8.21 9.42-8.63 11.24-10.31 12.28-11.25 16.51-15.14 16.60-15.22
1.53 1.20 1.93 2.03 2.40 2.62 3.56 3.58
97 97 98 98 97 97 98 98
32/29/27 34/31/28 39/36/33 42/38/34
RAV-SM561BT-E RAV-SM801BT-E RAV-SM1101BT-E RAV-SM1401BT-E
RAV-SP560AT-E RAV-SP800AT-E RAV-SP1100AT-E RAV-SP1400AT-E
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5.00 5.60 7.10 8.00 10.00 11.20 12.50 14.00
(2.20-5.60) (2.20-7.00) (2.20-8.00) (2.20-10.00) (3.00-12.00) (3.00-13.00) (3.00-14.00) (3.00-16.50)
3.60 4.67 3.38 3.94 4.00 4.27 3.21 3.91 1 phase 230V (220-240V) 50Hz
6.51-5.97 7.26-6.66 9.74-8.93 9.74-8.93 11.72-10.74 11.72-10.74 18.09-16.58 16.70-15.31
1.39 1.55 2.10 2.10 2.50 2.50 3.90 3.60
97 97 98 98 97 97 98 98
40/37/33 40/37/34 42/39/36 44/41/38
All Models
Under Ceiling type
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E RAV-SP560AT-E, RAV-SP800AT-E, RAV-SP1100AT-E, RAV-SP1400AT-E
Indoor Unit Outdoor Unit
Standard capacity (Note 1) (kW)
Energy consumption effect ratio
Power supply
Electrical characteristics Power
Sound level High/Mid./Low Indoor unit (Note 2) (dB•A)
Running current (A)
consumption Power factor (%)
(kW)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Nor mally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
RAV-SM561CT-E RAV-SM801CT-E RAV-SM1101CT-E RAV-SM1401CT-E
RAV-SP560AT-E RAV-SP800AT-E RAV-SP1100AT-E RAV-SP1400AT-E
Cooling Heating Cooling Heating Cooling Heating Cooling Heating
5.00 5.60 7.10 8.00 10.00 11.20 12.50 14.00
(2.20-5.60) (2.20-7.00) (2.20-8.00) (2.20-10.00) (3.00-12.00) (3.00-13.00) (3.00-14.00) (3.00-16.50)
3.55 3.73 3.38 3.64 4.17 4.48 3.21 3.73 1 phase 230V (220-240V) 50Hz
6.61-6.06 7.03-6.44 9.74-8.93 10.20-9.35 11.24-10.31 11.72-10.74 18.09-16.58 17.39-15.94
1.41 1.50 2.10 2.20 2.40 2.50 3.90 3.75
97 97 98 98 97 97 98 98
36/33/30 38/36/33 41/38/35 43/40/37
– 16 –
1-4. Operation Characteristic Curve
SM560UT-E SM560BT-EE
SM560UT-E SM560BT-E
SM800UT-E SM800BT-E
SM800UT-E SM800BT-E
• Operation characteristic curve (A02-014)
RAV-SM560UT-E, RAV-SM560BT-E, RAV-SM800UT-E, RAV-SM800BT-E
<Cooling> <Heating>
RAV-SM560/800UT-E RAV-SM560/800BT-E
14
12
10
SM800UT-E
SM800UT-E
SM800BT-E
SM800BT-E
16
14
12
10
8
6
Current (A)
SM560UT-E
SM560UT-E
SM560BT-EE
SM560BT-E
8
SM560UT-E
SM560UT-E
SM560BT-E
6
SM560BT-E
Current (A)
4
4
2
0
020
2
0
15
020
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
40 60 70 80 100
Compressor speed (rps)
• Capacity variation ratio according to temperature (A02-014)
SM800UT-E
SM800UT-E
SM800BT-E
SM800BT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
15
40 60 80 90 100
Compressor speed (rps)
RAV-SM560UT-E, RAV-SM560BT-E, RAV-SM800UT-E, RAV-SM800BT-E
<Cooling> <Heating>
105 100
95 90 85 80 75 70
Capacity ratio (%)
65 60 55
• Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
50
32 33 34 35 36 37 38 39 40 41 42 43
120 110 100
90 80 70 60 50 40
Capacity ratio (%)
30 20 10
0
-14-12-10-8-6-4-20246810
Outsoor temp. (˚C)
• Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outsoor temp. (˚C)
– 17 –
• Operation characteristic curve (A03-007)
RAV-SM561BT-E, RAV-SM801BT-E
<Cooling> <Heating>
RAV-SM561/801/1101BT-E
14
12
RAV-SM801BT-E
10
8
6
Current (A)
4
2
0
15
020
RAV-SM561BT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 220V
40 60 70 80 100
Compressor speed (rps)
16
14
12
10
8
Current (A)
6
4
2
0
15
020
RAV-SM801BT-E
RAV-SM561BT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 220V
40 60 80 90 100
Compressor speed (rps)
RAV-SM1101BT-E
<Cooling> <Heating>
20
18
16
14
12
10
Current (A)
8
6
4
2
0
0 204060
RAV-SM1100UT-ERAV-SM1101BT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
20
18
16
14
12
10
Current (A)
8
6
4
2
0
0204060
RAV-SM1100UT-ERAV-SM1101BT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
Compressor speed (rps)
Compressor speed (rps)
18
• Operation characteristic curve (A03-003)
RAV-SM1100UT-E
<Cooling> <Heating>
RAV-SM1100/1400UT-E
20
18
16
SM1100UT-E
14
SM1100UT-E
12
10
Current (A)
8
6
4
2
0
0 204060
Compressor speed (rps)
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
20
18
16
SM1100UT-E
14
SM1100UT-E
12
10
Current (A)Current (A)
8
6
4
2
0
0 204060
Compressor speed (rps)
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
RAV-SM1400UT-E
<Cooling> <Heating>
22 20
18 16 14 12 10
SM1400UT-E
SM1400UT-E
22 20
18 16 14 12 10
Current (A)
8 6
Conditions
4 2 0
020406080
Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
8 6 4 2 0
020406080
SM1400UT-E
SM1400UT-E
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
Compressor speed (rps)
– 19 –
• Operation characteristic curve (A03-014)
RAV-SP560AT-E, RAV-SP800AT-E <Cooling> <Heating>
RAV-SP560/800AT-E RAV-SP1100/1400AT-E
14
12
10
RAV-SP560AT-E
RAV-SP560AT-E
8
6
Current (A)
4
2
0
15
020
RAV-SP800AT-E
RAV-SP800AT-E
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
40 60 70 80 100
Compressor speed (rps)
16
14
12
10
8
RAV-SP560AT-E
RAV-SP560AT-E
Current (A)
6
4
2
0
15
020
RAV-SP800AT-E
RAV-SP800AT-E
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
40 60 80 90 100
Compressor speed (rps)
RAV-SP1100AT-E, RAV-SP1400AT-E <Cooling> <Heating>
22 20
18 16 14
RAV-SP1100AT-E
RAV-SP1100AT-E
12 10
RAV-SP1400AT-E
RAV-SP1400AT-E
Current (A)
8 6 4 2 0
020406080
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
22 20
18 16 14 12 10
Current (A)
8 6 4 2 0
020406080
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
Compressor speed (rps)
– 20 –
• Capacity variation ratio according to temperature (A03-014)
RAV-SP560AT-E, RAV-SP800AT-E, RAV-SP1100AT-E, RAV-SP1400AT-E <Cooling> <Heating>
RAV-SP560/800AT-E RAV-SP1100/1400AT-E
105 100
95 90 85 80 75 70
Capacity ratio (%)
65 60 55
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
50
32 33 34 35 36 37 38 39 40 41 42 43
Outsoor temp. (˚C)
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10
Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outsoor temp. (˚C)
– 21 –
• Operation characteristic curve (A03-016)
RAV-SM561CT-E
RAV-SM561CT-E
RAV-SM561CT-E, RAV-SM801CT-E
<Cooling> <Heating>
RAV-SM561/801/1101CT-E
14
12
RAV-SM801CT-E
RAV-SM801CT-E
10
8
6
Current (A)
4
2
0
15
020
RAV-SM561CT-E
RAV-SM561CT-E
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 220V
40 60 70 80 100
Compressor speed (rps)
16
14
12
10
8
Current (A)
6
4
2
0
15
020
RAV-SM801CT-E
RAV-SM801CT-E
RAV-SM561CT-E
RAV-SM561CT-E
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 220V
40 60 80 90 100
Compressor speed (rps)
RAV-SM1101CT-E
<Cooling> <Heating>
20
18
16
RAV-SM1101CT-E
14
12
10
Current (A)
8
6
4
2
0
0 204060
RAV-SM1101CT-E
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
20
18
16
14
12
10
Current (A)
8
6
4
2
0
0204060
RAV-SM1101CT-E
RAV-SM1101CT-E
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
Compressor speed (rps)
Compressor speed (rps)
– 22 –
• Operation characteristic curve (A03-016)
RAV-SM1401CT-E
<Cooling> <Heating>
22
22
RAV-SM1401CT-E
20 18
RAV-SM1401CT-E RAV-SM1401CT-E
16
RAV-SM1401CT-E RAV-SM1401CT-E
14 12 10
Current (A)
8 6
Conditions
4 2 0
020406080
Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
20 18 16
14 12 10
Current (A)
8 6
Conditions
4 2 0
020406080
Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
• Capacity variation ratio according to temperature (A03-016)
RAV-SM1401CT-E
<Cooling> <Heating>
105 100
95 90
120 110 100
90 80
85
70
80
60
75 70
Capacity ratio (%)
65 60 55
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
50
32 33 34 35 36 37 38 39 40 41 42 43
50
Capacity ratio (%)
40 30 20 10
0
-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10
Outsoor temp. (˚C)
Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outsoor temp. (˚C)
– 23 –

2. AIR DUCTING WORK

2-1. Static Pressure Characteristics of Each Model
RAV-SM560BT-E, RAV-SM800BT-E (A02-014)
Fig. 1 RAV-SM560BT-E
RAV-SM560/800BT-E
12 11
10
9 8 7 6 5 4
External static pressure (mmAq)
3 2 1
0
500 1000
70% (570m³/h) 110% (925m³/h)
600570
Standard air volume : 840m³/h
Extra High tap
Extra High tap
High tap
High tap
Middole tap
Middle tap
Low tap
Low tap
700 800 900 925
Air volume (m³/hr.)
12
11 10
9 8 7 6 5 4
External static pressure (mmAq)
3 2 1
70% (800m³/h) 110% (1255m³/h)
Fig. 2 RAV-SM800BT-E
Standard air volume : 1140m³/h
Extra High tap
Extra High tap
High tap
High tap
Middole tap
Middle tap
Low tap
Low tap
0
700 1300
800 900 1000 1100 1200 1255
Air volume (m³/hr.)
– 24 –
RAV-SM561/801/1101/1401BT-E
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E (A03-007)
Fig. 1 RAV-SM561BT-E (Round duct)
140
120
100
Usable limit
80
60
Static pressure (Pa)
40
Air volume limit (Min.)
20
Standard air volume 780m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
140
120
100
Static pressure (Pa)
Air volume limit (Max.)
Fig. 3 RAV-SM801BT-E (Round duct)
Standard air volume 1140m³/h
High static pressure 2H tap
Usable limit
80
60
40
20
Air volume limit (Min.)
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume limit (Max.)
0 500 700 780 900
Air volume m³/h
Fig. 2 RAV-SM561BT-E (Square duct)
140
120
108 100
80
60
Usable limit
Static pressure (Pa)
40
Air volume limit (Min.)
20
Standard air volume 780m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Static pressure (Pa)
Air volume limit (Max.)
0 800
1000
Air volume m³/h
Fig. 4 RAV-SM801BT-E (Square duct)
140
120
100
Usable limit
80
60
40
Air volume limit (Min.)
20
Standard air volume 1140m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
12001140 1300
Air volume limit (Max.)
0 500 700 780 900
Air volume m³/h
– 25 –
0 800
1000
Air volume m³/h
12001140 1300
0
RAV-SM1101/1401BT-E
Fig. 5 RAV-SM1101BT-E (Round duct)
140
120
100
Usable limit
80
60
Static pressure (Pa)
40
Low static pressure H tap
Air volume limit (Min.)
20
Standard air volume 1620m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Standard L tap
Air volume limit (Max.)
Fig. 7 RAV-SM1401BT-E (Round duct)
140
120
100
Usable limit
80
60
Static pressure (Pa)
40
Air volume limit (Min.)
20
Standard air volume 1980m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume limit (Max.)
0 1200
1620
Air volume m³/h
Fig. 6 RAV-SM1101BT-E (Square duct)
140
120
Usable limit
100
80
60
Static pressure (Pa)
Low static pressure H tap
Standard air volume 1620m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
2000
0
1200 1800
1980
Air volume m³/h
Fig. 8 RAV-SM1401BT-E (Square duct)
140
120
100
80
60
Usable limit
Static pressure (Pa)
Standard air volume 1980m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
2200 2400
40
Air volume limit (Min.)
20
0
1200
Standard L tap
1620
Air volume m³/h
Air volume limit (Max.)
2000
– 26 –
40
Air volume limit (Min.)
20
0
1200 1800
Air volume hm³/h
Standard L tap
1980
Air volume limit (Max.)
2200 240

3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)

3-1. Indoor Unit
3-1-1. 4-Way Air Discharge Cassette Type
RAV-SM560UT-E, RAV-SM800UT-E (A02-014)
RAV-SM560/800UT-E
Surface under ceiling
200
113
173
Refrigerant pipe connecting port A
130
200
Check port (
450)
Check port
450)
(
Cable draw-in port
45
Refrigerant pipe connecting port B
Electric parts box
860 to 910 Recommended external size
30
105
270 25070
950 Panel external dimension
790 Hanging bolt pitch
346.5
860 to 910 Recommended external size
Surface under ceiling
Hanging bolt M10 or W3/8 Procured locally
130
210
360
Indoor unit
Standing 640 or less
Standing 850 or less
Drain up standing size
256
Surface under ceiling
88
SM560 SM800
840 Unit external dimension
A
Ø6.4 Ø9.5
150
105
Ø12.7 Ø15.9
Knockout
97
35
Z view
for humidifier
Ceiling panel (Sold separately)
Surface under ceiling
80
Ø162
B
415.0
105105
240
254.5
840 Hanging bolt
480
227
12097
Surface under ceiling
381.6 227
480
723 Hanging bolt pitch
950 Panel external dimension
35
˚
64
57
57.5
25
188
Surface under ceiling
120
– 27 –
RAV-SM1100UT-E, RAV-SM1400UT-E (A03-003), RAV-SP1100UT-E (A03-014)
860 to 910 Recommended external size
200
Check port
450)
(
200
Check port ( 450)
Take-in port of pipes
45
30
Ceiling bottom surface
SM1100UT SM1400UT
860 to 910 Recommended external size
SP1100UT
RAV-SM1100/1400UT-E RAV-SP1100UT-E
C
120 183
D
256 319
A
B
Ø12.7
Ø15.9 Ø15.9
Ø12.7
Ø9.5 319183Ø15.9
Standing 850 or less
Standing 640 or less
113
173
Refrigerant pipe connecting port
A
Refrigerant pipe connecting port
B
130
Ceiling bottom surface
105
Electric parts box
Ø162
80
240
105 105
434.5
840 Unit external dimension
105
105
270
250
70
860 to 910 Ceiling opening dimension
950 Panel external dimension
790 Hanging bolt pitch
Knockout square hole for divide duct For Ø150
345.5
130
210
Drain pipe connecting port
Hanging bolt M10 or Ø3/8 (To be procured locally)
381.6
480
723 Hanging bolt pitch
950 Panel external dimension
˚
860 to 910 Ceiling opening dimension
35
360
Indoor unit
Drain up standing size
D
227
88
Surface under ceiling
Ceiling panel (sold separately)
Ø162
105
Ceiling bottom surface
Knockout square hole for divide duct for Ø150 (2 positions)
C97
254.5
840 Unit external dimension
480
227
– 28 –
57.5
188
C
97
64
57
25
35
Ceiling bottom surface
Z view
Surface under ceiling
3-1-2. Concealed Duct Type
RAV-SM560BT-E (A02-014)
RAV-SM560BT-E
2-Ø200 Discharge port flange
4-M10 Hanging bolt (Procured locally)
For hanging bolt M10 (4-12 x 25 long hole)
Drain pipe connecting port at drain up kit side (For polyvinyl chloride pipe (Inner dia. 32, Nominal dia. 25))
750 ± 7.5 Hanging bolt pitch 700 Dimension of main unit
150
160~6405
240
730
210
720
314.5
25
75
780 Ceiling opening size
800 Dimension of main unit
565 Hanging bolt pitch
170 12020
80
60
70252280
Drain up kit (Sold separately)
457 to 637
Refrigerant pipe connecting port (Gas side Ø12.7)
25
305
90 120
Refrigerant pipe connecting port (Liquid side Ø6.4)
Drain pipe connecting port at main unit side (For polyvinyl chloride pipe (Inner dia. 32, Nominal dia. 25))
2-Ø26 power supply remote controller cord draw-out port
80
170
211
45
130 80
30
35
Panel
155 to 335
470 Ceiling opening size
450
509 630
300
Plane view of main unit
Ø125 knockout hole (Only rear side) (For air suction)
100
6-Ø4 tapping screw lower hole Ø160
170
210
70
30 320
Suction port canvas
Suction panel
Check port A
450
NOTE 1 :
For maintenance of the equipment, be sure to install a check port A at the position as shown below.
NOTE 2 :
Using the drain up kit sold separately, drain-up by 300 (mm) from drain pipe draw-out port of the main unit is necessary. The drain-up over 300mm or more is impossible.
– 29 –
150
(Pipe side)
Discharge side
RAV-SM561/800/801/1101/1401BT-E
RAV-SM561BT-E, RAV-SM800BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E (A03-007)
129
110
Knock-out hole Ø125 (Air take-in port)
6-Ø4 T apping screw undersized hole Ø160
• Dimension
Discharge port flange N-Ø200
60 to 260 9
Suction port canvas (Separate sold)
Refrigerant pipe connecting port (Gas side ØF)
Hanging bolt pitch B
Main unit dimension A
J = M x K H
C
Ceiling open size D
Panel external dimension E
Hanging bolt 4-M10 screw (Arranged locally)
44 49
Refrigerant pipe connecting port (Liquid side ØG)
Drain pipe connecting port for vinyl chloride pipe (Inner dia. 32, VP. 25)
75
Main unit dimension 800
Hanging bolt pitch 700
50
131
50
Ø26 Power supply, remote controller cable take-out port
638
498
393
41
196
243
Panel C.L
410
Ceiling open size
470
Panel external dimension 500
5941
174
Suction port flange (Separate sold)
Suction port panel (Separate sold)
320
ABCDEFGHJKMNO
RAV-SM561BT
RAV-SM800BT
RAV-SM801BT
RAV-SM1101BT RAV-SM1401BT
700 766 690 750 780 12.7 6.4 252 280 280 1 2 410 1000 1050 1030 1030 1050 12.7 6.4 252 580 290 2 3 450 1000 1066 990 1050 1080 15.9 9.5 252 580 290 2 3 410
1350 1416 1340 1400 1430 15.9 9.5 252 930 310 2 4 410
NOTE 1 :
For maintenance of the equipment, be sure to install a check port A at the position as shown below.
NOTE 2 :
Using the drain up kit sold separately, drain-up by 300 (mm) from drain pipe draw-out port of the main unit is necessary. The drain-up over 300mm or more is impossible.
Plane view of main unit
(Pipe side)
Discharge side
Check port A
300
100
450
– 30 –