Toshiba RAV-SM802KRT-E User Manual

FILE NO.SVM-05053-1
SERVICE MANUAL
HI WALL TYPE (INDOOR UNIT)
RAV-SM562KRT-E
RAV-SM802KRT-E
R410A
Rev. Mar, 2006
CONTENTS
1. SPECIFICATIONS................................................................................................ 2
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM ......................................... 5
4. WIRING DIAGRAM .............................................................................................. 6
5. SPECIFICATIONS OF ELECTRICAL PARTS ..................................................... 7
6. REFRIGERANT R410A ....................................................................................... 8
7. INDOOR UNIT CONTROL ................................................................................. 16
8. TROUBLESHOOTING ....................................................................................... 27
9. HOW TO REPLACEMENT OF SERVICE INDOOR P.C. BOARD....................... 50
10. SETUP AT LOCAL SITE AND O THERS ........................................................... 54
11. ADDRESS SETUP ............................................................................................. 71
12. EXPLODED VIEWS AND PARTS LIST.............................................................. 76
NOTE :
This Service Manual describes explanation for the Under Ceiling type indoor unit. For the combined outdoor unit, refer to the following Service Manual.
Outdoor unit Model name SVM to be referred RAV-SMXX0AT-E A03-007 RAV-SPXXXAT-E A03-014
RAV-SMXX1AT-E A05-001
1
1-1. High-Wall Type (Indoor Unit)
1. SPECIFICATIONS
Model name
Standard capacity (Note 1) (kW)
Heating low temp. capacity (Note 1) (kW)
Energy consumption effect ratio (Cooling)
Power supply
Running current (A) Electrical characteristics
Appearance
Power consumption (kW)
(Low temp.) (kW)
Power factor (%)
Main unit
Ceiling Panel
(Sold separately)
Main unit Width (mm)
Model
Panel color
Height (mm)
RAV-SM562KRT-E RAV-SM802KRT-E
Cooling Heating Average Cooling Heating Average
5.1 5.6 6.7 8
(1.5 – 5.6) (1.5 – 6.3) (2.2 – 8.0) (2.2–9.0)
4.9 5.8
2.93 [D] 3.29 [C] 3.11 2.46 [E] 3.00 [D] 3.24
1 phase 230V (220 – 240V) 50Hz
8.33–7.63 8.138–7.46 13.15–12.05 12.91–11.84
1.74 1.7 2.72 2.67
1.95 2.21
95 95 94 94
Pure white
——
——
298
998
Outer dimension
Ceiling panel
(Sold separately)
Total weight
Heat exchanger
Soundproof/Heat-insulating material
Fan unit Standard air flow High (Mid./Low) (m³/h)
Air filter
Controller (Sold separately)
Connecting pipe
Main unit (kg)
Ceiling panel
Fan
Motor (W)
Gas side (mm)
Liquid side (mm)
Drain port (Nominal dia.)
Depth (mm)
Height (mm)
Width (mm)
Depth (mm)
221
——
——
——
12
——
Finned tubu
Inflammable polyethylene foam Foamed polyethylen
Turbo fan
840 1110
30
Attached main unit
Wired remote controller RBC-AMT21E
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
25 (Polyvinyl chloride tube)
Sound level High (Mid./Low) (Note 2) (dB•A)
45 41 36 45 41 36
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping. The reference piping consists of 3 m of main piping and 2 m of branch piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
2
Operation characteristic curve
<Cooling> <Heating>
14
12
RAV-SM802KRT-E
10
8
6
Current (A)
4
2
0
0201540 60 70 80 100
RAV-SM562KRT-E
• Conditions Indoor : DB27 C/WB19°C Outdoor : DB35°C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
16
14
12
10
8
Current (A)
6
4
2
0
15
020
RAV-SM802KRT-E
RAV-SM562KRT-E
• Conditions Indoor : DB20°C Outdoor : DB7 C/WB6°C Air flow : High Pipe length : 7.5m 230V
40 60 80 90 100
Compressor speed (rps)
•Capacity variation ratioaccor ding to temperature <Cooling> <Heating>
105
100
95
90
120
110
100
90
80
85
70
80
60
75
70
Capacity ratio (%)
65
60
55
• Conditions Indoor : DB27 C/WB19°C Indoor air flow : High Pipe length : 7.5m
50
32 33 34 35 36 37 38 39 40 41 42 43
50
40
Capacity ratio (%)
30
20
10
0
-14-12-10-8-6-4-20246810
Outsoor temp. (°C)
• Conditions Indoor : DB20°C Indoor air flow : High Pipe length : 7.5m
Outsoor temp. (°C)
3
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
High-Wall Type RAV-SM562KRT-E/RAV-SM802KRT-E
75
7
51
Knock out system
Back body
Front panel
Grille inlet
298
Air inlet
Air outlet
998
75
56
220
Knock out system
50
50
75
8
Connection pipe (0.39 m)
(For SM802 : Flare ∅15.88) (For SM562 : Flare ∅12.7)
55 or more
Outline of indoor unit
298
Minimum distance
to ceiling
65
100
20
48
998
763.5
450
Installation Plate outline
Drain hose (0.54 m)
Connection pipe (0.49 m) (Flare ∅6.35)
20
10
100
57
Wireless remote control
(For stud bolt ∅6)
(For stud bolt 8 -10)
29
41
55
5555
6
40
5
160
18
48
4
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Hi Wall type
RAV-SM562KRT-E/SM802KRT-E
Outer diameter of refrig erant pipeModel
RAV-SM 562KRT-E 802KRT-E
Gas side ØA Liquid side ØB
12.7 mm 6.4 mm
15.9 mm
9.5 mm
Indoor unit
TCJ
sensor
Air heat exchanger
TC sensor
Refrigerant pipe at gas side Outer dia. ØA
Pd PsPacked valve
Packed valve Outer dia. ØA
Refrigerant pipe at liquid side Outer dia. ØB
Outer dia. ØB
Outdoor unit
NOTE :
The refrigerating cycle differs according to the combined outdoor units. For the cycle diagram, cycle pressure, etc., refer to the following Service Manual.
RAV-SMXXX0AT-E : A03-007 RAV-SPXXXXAT-E : A03-014
RAV-SMXXX1AT-E : A05-001
5
Cooling Heating
4-1. Hi Wall type (Indoor unit)
RAV-SM562KRT-E/SM802KRT-E
LOUVER MOTOR
BLK
F
S
CN22
F301 FUSE
T3.15A 250V〜
CN67 (BLK)
CN213(WHI)
9
6 7 8
BLUBLUBLUBLUBLUBLUBLUBLU
BLUBLUBLUBLUBLUBLUBLUBLU
6 7 8
BLUBLUBLUBLUBLUBLUBLUBLU
BLUBLUBLUBLUBLUBLUBLUBLU
10 10
9
WHI
BLUBLUBLUBLUBLUBLUBLU
BLU 9
10
9
10
CN80 (GRN)
1 2 3
CN82 (BLU)
2 3
BLUBLUBLUBLUBLUBLUBLUBLU
BLUBLUBLUBLUBLUBLUBLUBLU
BLUBLUBLUBLUBLUBLUBLUBLU
BLUBLUBLUBLUBLUBLUBLUBLU
2 3
INFRARED RAYS RECEIVE
AND INDICATION PARTS
(MCC−819)
PNL/EMG
4. WIRING DIAGRAM
TERMINAL
2 15 3
RED
BLK
CN61 (YEL)
3 4 1 53 4
3 4
BLOCK
U3
U4
BLU
BLU
112
CN40 (BLU)
POWER SUPPLY CIRCUIT
CN60 (WHI)
OPTION
FAN MOTOR
YEL
WHI
BRW
RED
ORN
BLU
YEL
PNK
BLU
3 2 1
CN210 (WHI)
5566
4 3
6 5
CN33 (WHI)
(MCC−1510)
ControlP.Cboard forindoorunit
CN81 (BLK)
4 5
4 51 2 3
HA
BUS
EMG
1 2
CN44 (BRW)
DC15V DC 0V
DC12V DC7V
CN50 (WHI)
CN41
2 1
(BLU)
CN100
(BRW)
3 1
CN101 (BLU)
CN103
(GRN)
CN102
(YEL)
CN104
(WHI)
3 2 1
212
1 2
1 2
BLK BLK
BLK BLK
BLK BLK
BLK BLK
TERMINAL BLOCK
B A
HEAT EXCHANGER SENSOR (TC)
HEAT EXCHANGER SENSOR (TCJ)
THERMO SENSOR (TA)
WHI
BLK
1
2
1
2
CN1(WHI)
WIERDREMOTE CONTROLLER
NOTE
: Fan motor
FM
: Indoor temp. sensor
TA
: Temp. sensor
TC
: Temp. sensor
TCJ
: Louver motor
LM
WHI BLK
RED
321
321
Serial
NL
signal
Single phase 220V, 50Hz
6
Indoor unit earth screw
Outdoor unit earth screw
Color
Identification
BLACK
:
BLK
BLUE
:
BLU
RED
:
RED
GRAY
:
GRY
PINK
:
PNK
GREEN
:
GRN
WHITE
:
WHI
BROWN
:
BRW
ORANGE
:
ORN
YELLOW
:
YEL
5. SPECIFICATIONS OF ELECTRICAL PARTS
5-1. Indoor Unit
High-Wall Type RAV-SM562KRT-E/RAV-SM802KRT-E
No.
1
Fan motor (for indoor)
2
Grille motor
3
Thermo. sensor (TA-sensor)
4
Heat exchanger sensor (TC-sensor)
5
Heat exchanger sensor (TCJ-sensor)
Parts name
Type
ICF340-30-X
MF-340-30-X
MP35EA12
268 mm Ø6 mm, 400 mm
Ø6 mm, 400 mm
Specifications
Output (Rated) 30 W, 220–240 V
10 kW at 25°C 10 kW at 25°C
7
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
6-1. Safety During Installation/Servicing
As R410A's pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual. Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repairÕs may result in water leakage, electric shock and fire, etc.
6-2. Refrigerant Piping Installation
6-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol­ored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 6-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
8
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4
3/8
1/2
5/8
(2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all con­taminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6­2-6 below.
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 6-2-2.
Table 6-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
9
c) Insertion of Flare Nut d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Table 6-2-3 Dimensions related to flare processing for R410A
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure "dimen­sion A" by using a gauge for size adjustment.
ØD
A
Fig. 6-2-1 Flare processing dimensions
Nominal
diameter
1/4
3/8
1/2
5/8
Nominal
diameter
1/4
3/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R410A clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Table 6-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
Thickness
(mm)
0.8
0.8
Flare tool for
R22 clutch type
0 to 0.5
0 to 0.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
1/2
5/8
Nominal
diameter
1/4
3/8
1/2
5/8
12.70
15.88
Table 6-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15,88
0.8
1.0
Thickness
(mm)
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
10
Flare nut
width (mm)
17
22
26
29
Table 6-2-6 Flare and flare nut dimensions for R22
Nominal Outer diameter Thickness
diameter (mm) (mm)
1/4 6.35 0.8
3/8 9.52 0.8
1/2 12.70 0.8
5/8 15.88 1.0
3/4 19.05 1.0
°
to 46
°
45
B A
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.4 19.0 16.0 23
23.3 24.0 19.2 34
D
C
43
°
to 45
°
Flare nut width
(mm)
17
22
24
27
36
Fig. 6-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
Table 6-2-7 Tightening torque of flare for R410A [Reference values]
Nominal Outer diameter Tightening torque
diameter (mm) N.m (kgf.cm)
1/4 6.35 14 to 18 (140 to 180)
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 6-2-7 shows reference values.
NOTE:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N.m (kgf.cm)
16 (160), 18 (180)
3/8 9.52 33 to 42 (330 to 420)
1/2 12.70 50 to 62 (500 to 620)
5/8 15.88 63 to 77 (630 to 770)
11
42 (420)
55 (550)
65 (650)
6-3. Tools
6-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No. Used tool
Flare tool
1
Copper pipe gauge for
adjusting projection
2
margin
3
Torque wrench
Gauge manifold
4
Charge hose
5
Vacuum pump adapter
6
Electronic balance for
7
refrigerant charging
Refrigerant cylinder
8
Leakage detector
9
Charging cylinder
10
Usage
Pipe flaring
Flaring by conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge Gas leakage check Refrigerant charge
air conditioner installation
Existence of Whether conven­new equipment tional equipment for R410A can be used
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s Ye s
(Note 2)
R410A
(Note 1)
*
(Note 1)
*
X
X X
X X
X X
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
(Note 1)
*
X
X
X
X
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (3) Pipe cutter
(4) Reamer (5) Pipe bender (6) Level vial (7) Screwdriver (+, - ) (8) Spanner or Monkey wrench
(9) Hole core drill (Ø65) (10) Hexagon wrench
(Opposite side 4mm) (11) Tape measure (12) Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (2) Thermometer
(3) Insulation resistance tester (4) Electroscope
12
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor unit's gas side.
When the compound gauge's pointer has indicated
- 0.1 Mpa (- 76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump's power switch.
Connect the charge hose of the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump's power switch. Then, evacuating the refrigerant in the cycle.
Never charge refrigerant exceeding the specified amount.
1.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
2.
Do not carry out additional charging.
3.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge's pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 6-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 13 –
(OUTDOOR unit)
Opened
Closed
Service port
Be sure to make setting so that liquid can be charged. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
6-5. Brazing of Pipes
6-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expen­sive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
Fig. 6-4-2
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
1.
with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2.
When performing brazing again at time of servicing, use the same type of brazing filler.
6-5-2. Flux
(1) Reason why flux is necessary
1.By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
2.In the brazing process, it prevents the metal surface from being oxidized.
3.By reducing the brazing filler's surface tension, the brazing filler adheres better to the treated metal.
14
(2) Characteristics required for flux
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
1.Activated temperature of flux coincides with the brazing temperature.
2.Due to a wide effective temperature range, flux is hard to carbonize.
3.It is easy to remove slag after brazing.
4.The corrosive action to the treated metal and brazing filler is minimum.
5.It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing tem­perature is higher than 800°C.
Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
6-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
1.
Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2.
Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
Apply a seal onto the clearance between the
3.
piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4.
When the Nitrogen gas is flowing, be sure to keep the piping end open.
5.
Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/ cm²) by means of the reducing valve.
6.
After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
Remove the flux completely after brazing.
7.
Copper - Copper
Copper - Iron
1.
2.
3.
4.
Piping
material
Iron - Iron
Used brazing
filler
Phosphor copper
Silver
Silver
Used
flux
Do not use
Paste flux
Vapor flux
Do not enter flux into the refrigeration cycle. When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
Remove the flux after brazing.
Fig. 6-5-1 Prevention of oxidation during brazing
15
7-1. Indoor Control Circuit
7. INDOOR UNIT CONTROL
Max. 8 units are connectable.*1
*1 When group and twin combination. main remote controller shal be connected follower indoor unit
*2 Weekly timer is not connectable to the sub remote controller.
Indoor unit
#1 Header unit
Indoor control P.C. board (MCC-1510)
Central control
remote controller
(Sold separatrly)
Reciver and Display P.C board
(MCC-819)
Reciver unit
Display LED
U3
U4
Main (Sub) master remote controller
(Wired)
Display
LCD
Display
LED
DC20V DC12V
DC5V
Buzzer
CPU
Remote
controller
communication
circuit
Central control
communication
circuit
Driver
Function setup
Key switch
CN2 CN1
DC5V
Power circuit
Sold separatrly Sold separatrly
AB
Remote
controller
communication
circuit
CPU
Driver
H8/3039
Weekly timer
Display
LCD
2
*
Powe r
circuit
EEPROM
TA sensor
TC sensor
TCJ sensor
LCD
driver
CPU
DC5V
Secondary
battery
Follower unit
AB
#2
Same as
the left
Function setup
Key switch
#3
AB
Same as
the left
Louver
motor
Indoor
fan
motor
DC280V
Power circuit
DC15V
Outdoor unit
Fan motor
control
circuit
123
3
12
Outside output
Run
Warning
Ready
Thermo. ON
Cool Heat
Fan
AC
synchronous
signal input
circuit
Serial send/
receive
circuit
HA
Wireless
remote
signal
Setting (A/B)
123
Outdoor
unit
123
Outdoor
unit
16
INDOOR UNIT CONTROL CIRCUIT (Continued)
7-2. Control Specifications
NO.
1
Control at power-on reset
Operation mode
2
switching
Item
Overview of specifications
(1) Identification of outdoor unit
Identifies outdoor unit at power-on reset, and switches control according to the identification result.
(2)
Setting of indoor unit fan speed and adjustment of air flow direction Switches indoor unit fan speed, setting of air flow direction adjustment, etc. based on EEPROM data.
(1) Switches operation mode according to mode select instruction
from remote controller.
R/C instructions
OFF
FAN
COOL
DRY HEAT AUTO
Turns OFF air conditioner “Fan only” operation Cooling operation Dehumidifying operation Heating operation
• Selects COOL or HEAT mode
Outline of control
automatically according to Ta, Ts, and To.
• The first operation is as follows according to Ta. (COOL thermo sensor continues OFF (FAN mode with set fan speed) within the range of Ts +α-1<Ta< Ts +α+1.)
COOL operation
FAN mode with set fan speed
Ta
( )
+1.0
Ts+
Remarks
The “PREPARING” lamp lights during initial setting (model recognition) after power-on reset. Fan speed, adjustment of air flow direction
Ta : Room temperature Ts : Set temperature To : Outside air temperature
Room temperature
3
control
-1.0
HEAT operation
α is corrected according to outside air temperature.
Outside air temp. Corrected value (α)
No To 0 K
>
To
24°C -1 K
=
>
24>To
18°C 0 K
=
To<18°C +1 K
Abnormal To 0 K
(2) Operation instruction permission mode
HEAT and AUTO modes are not available for COOL only models. When instruction is issued from wireless remote controller in the HEAT or AUTO mode, it is indicated by a reception sound “pi, pi” and by alternate blinking of “TIMER” and “PREPARING” lamps. To cancel this alternate blinking, issue an instruction of mode other than HEAT or AUTO.
(1) Adjustment range Remote controller set temperature (°C)
COOL/DRY HEAT AUTO
Wired type 18 - 29 18 - 29 18 - 29
Wireless type 17 - 30 17 - 30 17 - 30
* When use of remote controller sensor is set (with DN32), even
when sensor value is within the above range in HEAT or AUTO mode, the thermo sensor turns OFF when Ta sensor value exceeds 35 °C.
k=deg
17
NO.
Room temperature
3
control
Capacity auto
4
control
(GA control)
Item
Overview of specifications
(2) The set temperature for HEAT operation can be corrected by code
No. 06.
Set data 0246
Correction of set temp. +0°C +2°C +4°C +6°C
Factory setting
Set data 2
* When use of remote controller sensor is set (with DN32), no
correction is performed.
(1) Issues instruction of operating frequency to outdoor unit according
to the difference between Ta and Ts.
(2) COOL operation
Calculates room temp. difference between Ta and Ts as well as room temp. variation every 90 seconds to find correction value of specified operating frequency and to correct the current operating frequency. Ta(n)–Ts(n) : Room temp. difference n : Number of detection times Ta(n-1)–Ta(n) : Room temp. variation n–1 : Number of detection times
(90 seconds before)
(3) HEAT operation
Calculates room temp. difference between Ta and Ts as well as room temp. variation every 60 seconds to find correction value of specified operating frequency and to correct the current operating frequency. Ts(n)–Ts(n) : Room temp. difference n : Number of detection times Ta(n)–Ta(n_1) : Room temp. variation n–1 : Number of detection times
(60 seconds before)
(4) DRY operation
The frequency correction control is the same as that for COOL operation. However, the maximum frequency is limited to S6 or so.
Note) When LOW fan speed is set, the maximum frequency is
limited to SB or so.
Remarks
Heat intake temperature shift (When unit’s temperature sensor is used)
COOL/HEAT/
5
AUTO control
(1) Switching between COOL and HEAT is determined based on the
following control.
Ta
(˚C)
+1.5
Tsc
or
Tsh
COOL
(COOL ON)
(COOL OFF)
-1.5
After 10 minutes pass from thermo sensor OFF, operation mode changes from HEAT (thermo sensor OFF) to COOL if Ta exceeds Tsh +1.5.
( ) shows an example of
HEAT
COOL ON/OFF.
After 10 minutes pass from thermo sensor OFF, operation mode changes from COOL (thermo sensor OFF) to HEAT if Ta lowers below Tsc -1.5.
(2) The GA control after determination of operation mode follows the
description in No. 4.
(3) The room temperature control and temperature correction follow
the descriptions in No. 3 and No. 15.
Tsc : COOL set temp. Tshc : HEAT set temp. +
room temp. control/ correction
18
INDOOR UNIT CONTROL CIRCUIT (Continued)
NO.
6
Fan speed control
Item
Overview of specifications
(1) A fan speed HH (quick high), H (high), L (low) or AUTO is selected
according to the instruction from remote controller for FAN mode operation.
(2) Fan speed is switched according to the difference between Ta and
Ts in the AUTO mode.
[Cooling]
Ta (˚C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
-0.5
HH (HH)
H+(HH)
H(HH)
L+(H+)
L(H)
L(H)
L(L+)
A
B
C
D
E
F
G
• The fan speed control is the same for temperature setting by remote controller or the unit.
• Once fan speed is changed, it remains unchanged for 3 minutes unless different fan speed is selected by instruction.
• At the beginning of cooling, a falling gradient (higher fan speed) is selected.
• When the temperature difference between Ta and Ts is on a threshold line, fan speed does not change.
• ( ): Auto cooling
Remarks
HH>H+>H> L+>L>UL
Wireless type allows HH, H+, H, L+, L, and AUTO.
HH
H+
H
L+
L
[Heating]
Ta (˚C)
(-0.5)
(0)
(+0.5)
(+1.0)
(+1.5)
(+2.0)
-1.0
Tsh
+1.0
+2.0
+3.0
+4.0
L( L+)
L+(H)
H(H+)
H+ (HH)
HH (HH)
E
D
C
B
A
( ): Temperature setting by remote controller Other than ( ): Temperature setting by unit
• Once fan speed is changed, it remains unchanged for one minute unless different fan speed is selected by instruction.
• At the beginning of heating, a rising gradient (higher fan speed) is selected.
• When the temperature difference between Ta and Ts is on a threshold line, fan speed does not change.
• ( ): Auto heating
• Fan speed is switched to a higher level when Tc reaches 60 °C.
Tc : Indoor unit heat
exchange sensor temp.
19
NO.
6
Fan speed control
Item
COOL
HH H+
H
L+
L
UL
Overview of specifications
HEAT
HH
AP40-56
1220
AP63
1180
H+
H
1140 1120 1060
L+
L
1060
990 940
UL
500
1360 1300 1240 1200 1120 1120 1020
970 500
Remarks
AP71-80
1480 1340 1320 1300 1200 1200 1100 1040
500
7
Cool air prevention control
(3) When thermo sensor turns OFF during heating, the fan speed
mode becomes UL (weak).
(4) When Ta is 25 °C or above at the beginning of HEAT operation or
when canceling defrost mode, H or HH mode continues for one minute from the time when Tc enters zone E shown in the figure in No.7 below.
(5) The HH fan speed for auto cooling/heating is set to a speed higher
than that for normal cooling/heating. However, it varies depending on the temperature difference of Tc during auto heating.
Tc
(˚C)
47
HH+
42
HH
(1) Performs indoor unit fan control in the HEAT mode according to
the Tc (or Tcj) sensor detect temperature. The maximum speed is limited as shown below.
Tc Tcj
(˚C)
36
34
32
30
24
20
HH
H
L
UL
OFF
Shifts Tc control value by +6 °C during defrosting. However, zone B is regarded as zone C after 6 minutes pass from the startup of compressor.
Zone E
Zone D
Zone C Zone B
Zone A
“HEAT PREPARING” indication
Fan speed select setting by remote controller takes precedence in zones D and E. “HEAT PREPARING” is indicated in zones A and B.
20
INDOOR UNIT CONTROL CIRCUIT (Continued)
NO.
8
Freezing prevention control (low-temp. release)
9
High-temp. release control
Item
Overview of specifications
(1) Performs the following operation control in the COOL or DRY
mode according to the Tc (or Tcj) sensor detect temperature. When zone J in the figure below is detected for 6 minutes, the specified operating frequency is decreased from the actual operating frequency, and the specified operating frequency is changed every 30 seconds in zone J. Timer count stops and is maintained in zone K. Timer count is cleared to restore normal operation when zone I is detected. If the specified operating frequency becomes SO due to continuation of zone J, return temperature A is raised from 5 to 12 °C, and operation with L fan speed continues until zone I is detected.
Tc(˚C)
I5
2
J
A
K
If 4-way valve cannot be switched during heating and the following conditions become true, freezing prevention control is performed. (However, zone J entering control temperature is changed from 2 to -5 °C.) [Conditions] The following A or B becomes true after 5 minutes pass from operation start.
<
A Tcn B Tcn<Tc(n–1)–1 and Tcn
Tc(n–1)–5
=
<
Ta<5°C
=
(1) Performs the following operation control in the HEAT mode
according to the Tc (or Tcj) sensor detect temperature.
When zone M is detected, the specified operating frequency is decreased from the actual operating frequency, and the specified operating frequency is changed every 30 seconds in zone M.
• The specified operating frequency is maintained in zone N.
• When zone L is detected, the specified operating frequency is returned by approx. 6 Hz every 60 seconds.
Factory setting
Control temp. (°C)
AB
Tc Tcj
(˚C)
A
56 (54) 52 (52)
B
L
Remarks
Tcj : Indoor unit heat
exchange sensor temp.
Tcn :
Tc after 5 minutes from operation start
Tc (n-1):
Tc at operation start
This control is disabled for twin follower indoor units.
M
N
Note) At the beginning of operation or when Tc (or Tcj) lowers below
30 °C after operation start, values (54) and (52) in the table are used as control temperature.
10 Runs indoor unit fan in L (low) mode for about 30 seconds after HEAT
Residual heat removal
operation stops to remove residual heat.
21
Even when the thermo is set to OFF, the control is implemented in the same way.
NO.
11
Item
Flap control
Overview of specifications
(1) During the first operation after power on, flap position is controlled
automatically according to operation mode (COOL/HEAT).
Cooling Heating
Remarks
Louver angle: 0 °C (full close)
Full close
45°
103°
(2) When louver position is controlled by remote controller, the unit’s
microcomputer memorizes the position for use in the next operation.
* The memorized louver position is cleared when power is turned
off, and returns to the state of (1) above.
(3) Flap position setting
• Flap position can be set within the range below.
COOL/DRY HEAT/FAN
• Flap position can be set collectively or individually in the group twin or triple operation mode. (Wireless remote controller allows individual setting only.)
(4) Swing setting
• Flap moves within the range below.
All operation modes
• Flap swing range can be set collectively or individually in the group twin or triple operation mode. (Setting by wireless remote controller is disabled when the main remote controller is used.)
(5) When air conditioner operation stops, flap closes automatically. It
keeps its position in the event of an alarm. (6) Flap tilts upward automatically during preparation for heating. (7) In the twin or triple operation mode selected by wireless remote
controller, swing setting interlocks with the header indoor unit. If
this setting is transmitted from a follower indoor unit, operation
does not change with a reception sound “pi, pi, pi” if operation
mode differs between header unit and follower unit.
Alarm : A code number
(except F08 and L31) appears on the remote controller and the indoor unit stops.
22
INDOOR UNIT CONTROL CIRCUIT (Continued)
NO.
12
Item
HA control
Overview of specifications
(1) When connected to a remote control system (tele-control or
remote on/off interface), operation ON/OFF can be controlled by
the HA signal input. (2) Outputs operation ON/OFF status to the HA output terminal. (3) HA signal input/output specifications conform to the JEMA
standard.
Remarks
A connector (separately available) is required when using the HA terminal CH61 for remote ON/OFF control.
When group operation is in use, connect the connector to either header or follower indoor unit.
13
Filter sign indication (unavailable for wireless type)
(1) Transmits filter replacement signal to remote controller for
indication on the LCD when accumulated operation hours of
indoor unit fan exceeds the specified time (150 hours).
(2) Clears accumulation timer upon receiving the filter reset signal
from remote controller. At this time, when the specified time has
already passed, the accumulated time is reset and the filter sign
disappears from the LCD.
“FILTER” lamp ON
– 23 –
Loading...
+ 55 hidden pages