Toshiba RAV-SM802CT-E, RAV-SM563AT-E, RAV-SM562CT-E, RAV-SM562BT-E, RAV-SM1402CT-E User Manual 2

...
FILE NO. A06-010
Revised : Mar. 2007
SERVICE MANUAL/INTEGRATION
AIR-CONDITIONER
SPLIT TYPE
INDOOR UNIT
<DIGITAL INVER TER> RAV-SM563UT-E RAV-SM562BT-E RAV-SM562CT-E
<SUPER DIGITAL INVERTER> RAV-SP1102UT-E
OUTDOOR UNIT
<DIGITAL INVERTER> RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E RAV-SM1403AT-E
<SUPER DIGITAL INVERTER> RAV-SP562AT-E RAV-SP802AT-E RAV-SP1102AT-E RAV-SP1402AT-E
R410A
PRINTED IN JAPAN, Mar.,2007 ToMo
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer.
NOTE
A direct current motor is adopted for indoor fan motor in the Concealed Duct Standard Type air conditioner. Caused from its characteristics, a current limit works on the direct current motor. When replacing the high­performance filter or when opening the service board, be sure to stop the fan. If an above action is executed during the fan operation, the protective control works to stop the unit operation, and the check code “P12” may be issued. However it is not a trouble. When the desired operation has finished, be sure to reset the system to clear “P12” error code using the leak breaker of the indoor unit. Then push the operation stop button of the remote controller to return to the usual operation.
CONTENTS
SAFETY CAUTION ............................................................................................ 4
1. SPECIFICATIONS......................................................................................... 9
1-1. Indoor Unit........................................................................................................... 9
1-2. Outdoor Unit...................................................................................................... 17
1-3. Operation Characteristic Curve....................................................................... 19
2. AIR DUCTING WORK ................................................................................. 22
2-1. Static Pressure Characteristics of Each Model ............................................. 22
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)......................................... 24
3-1. Indoor Unit......................................................................................................... 24
3-2. Outdoor Unit...................................................................................................... 28
4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM ................................ 31
4-1. Indoor Unit/Outdoor Unit ................................................................................. 31
5. WIRING DIAGRAM ..................................................................................... 39
5-1. Indoor Unit......................................................................................................... 39
5-2. Outdoor Unit (Wiring Diagram)........................................................................ 42
6. SPECIFICATIONS OF ELECTRICAL PARTS............................................. 46
6-1. Indoor Unit......................................................................................................... 46
6-2. Outdoor Unit...................................................................................................... 48
6-3. Accessory Separate Soldparts ........................................................................ 50
– 2 –
7. REFRIGERANT R410A .............................................................................. 51
7-1. Safety During Installation/Servicing ............................................................... 51
7-2. Refrigerant Piping Installation....................................................................... 51
7-3. Tools .................................................................................................................. 55
7-4. Recharging of Refrigerant................................................................................ 55
7-5. Brazing of Pipes................................................................................................ 56
7-6. Instructions for Re-use Piping of R22 or R407C ............................................ 58
8. CONTROL BLOCK DIAGRAM ................................................................... 61
8-1. Indoor Control Cir cuit....................................................................................... 61
8-2. Control Specifications...................................................................................... 62
8-3. Indoor Print Circuit Board................................................................................ 70
9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS ............. 71
9-1. Indoor Control Cir cuit....................................................................................... 71
9-2. Outdoor Controls.............................................................................................. 71
10. TROUBLESHOOTING............................................................................... 80
10-1. Summary of Troubleshooting........................................................................... 80
10-2. Check Code List................................................................................................ 82
10-3. Error Mode Detected by LED on Outdoor P.C. Board .................................... 85
10-4. Troubleshooting Procedure f or Each Check Code......................................... 86
11. REPLACEMENT OF SERVICE INDOOR P.C. BOARD .......................... 102
12. SETUP AT LOCAL SITE AND OTHERS ................................................ 106
12-1. Indoor Unit....................................................................................................... 106
12-2. Setup at Local Site / Others ........................................................................... 113
12-3. How to set up central control address number............................................ 115
13. ADDRESS SETUP .................................................................................. 116
13-1. Address Setup ................................................................................................ 116
13-2. Address Setup & Group Control.................................................................... 117
13-3. Address Setup ................................................................................................ 118
14. DETACHMENTS..................................................................................... 120
14-1. Indoor Unit...................................................................................................... 120
14-2. Outdoor Unit.................................................................................................... 134
15. EXPLODED VIEWS AND PARTS LIST ................................................. 159
15-1. Indoor Unit....................................................................................................... 159
15-2. Outdoor Unit.................................................................................................... 173
15-3. Replacement of Main Parts (Sold Separately).............................................. 181
16. CORD HEATER INSTALLATION WORK ................................................ 183
16-1. Required parts for installation work (Recommendation) ............................ 183
16-2. Base Plate ....................................................................................................... 192
3
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage ( ) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit () at secondary circuit of the high­voltage transformer is applied.
Tur n off breaker.
Execute discharge
between terminals.
Prohibition
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an electric insulator.
: For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between high­voltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
– 4 –
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
If unspecified parts are used, a fire or electric shock may be caused. : For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead cables with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
∗∗
∗).
∗∗
Refrigerant
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refriger­ating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recover­ing device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
Assembly/Cabling
After repair work, surely assemble the disassembled parts, and connect and lead the removed cables as before. Perform the work so that the cabinet or panel does not catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or fire is caused at user’s side.
– 5 –
WARNING
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
After the work has finished, be sure to use an insulation tester set (500V mugger) to check the resistance is 2M metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
ΩΩ
or more between the charge section and the non-charge
ΩΩ
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The ear th wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on gloves (
If not putting on gloves, an injury may be caused with the parts, etc. () Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
∗∗
) during repair work.
∗∗
– 6 –
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is per­formed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil. For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the
former refrigerant in order to prev ent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.
3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refriger­ant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropri­ate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size , flare nut and others differ according to a refrigerant type. When us#ing a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe
without seam” and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installa­tion of the air conditioner. However clear impurities when using them.
– 7 –
4. Tools
1. Required T ools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary,
etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Flare tool
Copper pipe gauge for
adjusting projection margin Torque wrench
Gauge manifold
Charge hose
V acuum pump adapter
Electronic balance for
refrigerant charging Refrigerant cylinder
Leakage detector
Charging cylinder
Used tool
Usage
Pipe flaring Flaring by conventional
flare tool Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
V acuum evacuating
Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
air conditioner installation
R410A
Existence of Whether conven­new equipment tional equipment for R410A can be used
Yes *(Note 1)
Yes *(Note 1) Yes No
Yes No
Yes No
Yes Yes Yes No
Yes No
(Note 2) No
Conventional air
conditioner installation
Whether conventional equipment can be used
Yes
*(Note 1)
No
No
Yes
Yes
No
Yes
No
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projec-
tion margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which ser ve also for R22 are necessary as the general tools.
1) Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2) Torque wrench
3) Pipe cutter
4) Reamer
7) Screwdriver (+, –)
8) Spanner or Monkey wrench
9) Hole core drill
10) Hexagon wrench (Opposite side 4mm)
11) Tape measure
12) Metal saw
5) Pipe bender
6) Level vial
Also prepare the following equipments for other installation method and run check.
1) Clamp meter
2) Thermometer
3) IInsulation resistance tester
4) Electroscope
– 8 –
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Air Discharge Cassette Type
<Digital Inverter>
Revised : Mar. 2007
Model
Cooling capacity (kW) Heating capacity (kW) Po w er supply
Cooling
Electrical characteristics
Heating
Main unit
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min)
Air filter Controller (Sold separately)
Connecting pipe Liquid side (mm)
Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Po w er consumption (kW) Po w er factor (%) EER (W/W) Energy efficiency class * Energy rating ** Running current (A) Po w er consumption (kW) Po w er factor (%) COP (W/W) Energy efficiency class * Energy rating **
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
SM563UT-E SM803UT-E SM1103UT-E SM1403UT-E
SM563AT-E SM803AT-E SM1103AT-E SM1403AT-E
5.3 6.7 10.0 12.1
5.6 8.0 11.2 14.0 1 phase 230V (220 – 240V) 50Hz
7.89 – 7.24 10.11 – 9.26 14.42 – 13.21 7.67 – 16.19
1.65 2.09 3.11 3.77 95 94 98 97
3.21 3.21 3.22 3.21
AAAA
4.5 4.0 4.5 4.0
6.89 – 6.32 10.69 – 9.80 14.38 – 13.18 18.18 – 16.67
1.44 2.21 3.10 3.88 95 94 98 97
3.89 3.62 3.61 3.61
AAAA
6.0 4.5 5.0 4.0 Zinc hot dipping steel plate
RBC-U21PG (W)-E2
Moon-white (Muncel 2.5GY 9.0/0.5) 256 256 319 319 840 840 840 840 840 840 840 840
35 35 35 35 950 950 950 950 950 950 950 950
21 22 26 26
4.5 4.5 4.5 4.5 Finned tube
Turbo fan Turbo fan Turbo fan Turbo fan
17.5/13.9/12.1 20.0/15.7/13.6 28.0/22.0/18.0 34.0/25.0/20.0 60 60 90 90
TCB-LF1601UE2, UFM1601UE, UFH1601UE
RBC-AMT31E, AS21E2, TCB-SC642TLE2, AX21U(W)-E2
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
32/29/27 37/31/28 39/36/33 47/38/34 47/44/42 52/46/43 54/51/48 62/53/49
– 9 –
* : IEC standard, ** : AS standard
<Super Digital Inverter>
Revised : Mar. 2007
Model
Cooling capacity (kW) Heating capacity (kW) Po w er supply
Cooling
Electrical characteristics
Heating
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Po w er consumption (kW) Po w er factor (%) EER (W/W) Energy efficiency class * Energy rating ** Running current (A) Po w er consumption (kW) Po w er factor (%) COP (W/W) Energy efficiency class * Energy rating **
SM563UT-E SM803UT-E SP1102UT-E SM1403UT-E
SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E
5.3 7.1 10.0 12.5
5.6 8.0 11.2 14.0
1 phase 230V (220 – 240V) 50Hz
7.17 – 6.57 8.95 – 8.21 11.24 – 10.31 16.51 – 15.14
1.53 1.93 2.40 3.56 97 98 97 98
3.46 3.68 4.17 3.51
AAAA
————
5.62 – 5.15 9.42 – 8.63 12.28 – 11.25 16.60 – 15.22
1.20 2.03 2.62 3.58 97 98 97 98
4.67 3.94 4.27 3.91
AAAA
————
Main unit
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min)
Air filter Controller (Sold separately)
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Zinc hot dipping steel plate
RBC-U21PG (W)-E2
Moon-white (Muncel 2.5GY 9.0/0.5) 256 256 319 319 840 840 840 840 840 840 840 840
35 35 35 35 950 950 950 950 950 950 950 950
21 22 26 26
4.5 4.5 4.5 4.5 Finned tube
Turbo fan Turbo fan Turbo fan Turbo fan
17.5/13.9/12.1 20.0/15.7/13.6 28.0/22.0/18.0 33.0/25.0/20.0 60 60 90 90
TCB-LF1601UE2, UFM1601UE, UFH1601UE
RBC-AMT31E, AS21E2, TCB-SC642TLE2, AX21U (W)-E2
Gas side (mm)
Connecting pipe Liquid side (mm)
Drain port (mm) Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
– 10 –
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
32/29/27 37/31/28 39/36/33 42/38/34 47/44/42 52/46/43 54/51/48 57/53/49
* : IEC standard, ** : AS standard
1-1-2. Concealed Duct Type
<Digital Inverter>
Revised : Mar. 2007
Model
Cooling capacity (kW) Heating capacity (kW) Po w er supply
Cooling
Electrical characteristics
Heating
Main unit
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min)
Air filter TCB-
Controller (Sold separately)
Connecting pipe Liquid side (mm)
Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Po w er consumption (kW) Po w er factor (%) EER (W/W) Energy efficiency class * Energy rating ** Running current (A) Po w er consumption (kW) Po w er factor (%) COP (W/W) Energy efficiency class * Energy rating **
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E
SM563AT-E SM803AT-E SM1103AT-E SM1403AT-E
5.0 7.1 10.0 12.5
5.6 8.0 11.2 14.0
1 phase 230V (220 – 240V) 50Hz
8.52 – 7.81 12.23 – 11.21 16.50 – 15.10 20.70 – 19.00
1.78 2.53 3.56 4.42 95 94 98 97
2.81 2.81 2.81 2.83
CCCC
3.0 3.0 3.5 3.0
8.18 – 7.50 11.65 – 10.68 14.56 – 13.35 18.88 – 17.31
1.71 2.41 3.14 4.03 95 94 98 97
3.27 3.32 3.57 3.47
CCBB
3.0 3.5 5.0 4.0 Zinc hot dipping steel plate
— 320 320 320 320 700 1000 1350 1350 800 800 800 800
———— ———— ———— 30 39 54 54 ————
Finned tube
Centrifugal Centrifugal Centr ifugal Centrifugal
13.0/11.9/9.8 19.0/16.2/13.3 27.0/23.0/18.9 33.0/28.0/23.1 120 120 120 120
UFM11BFCE UFM21BFCE UFM21BE UFM31BE UFM41BE UFM61BE UFH51BFCE UFH61BFCE
UFM71BE UFH81BE
RBC-AMT31E, AS21E2, TCB-SC642TLE2, AX21E2
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
40/37/33 40/37/34 42/39/36 44/41/38 55/52/48 55/52/49 57/54/51 59/56/53
– 11 –
* : IEC standard, ** : AS standard
<Super Digital Inverter>
Model
Cooling capacity (kW) Heating capacity (kW) Po w er supply
Cooling
Electrical characteristics
Heating
Main unit
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min)
Air filter TCB-
Controller (Sold separately)
Connecting pipe Liquid side (mm)
Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Po w er consumption (kW) Po w er factor (%) EER (W/W) Energy efficiency class * Energy rating ** Running current (A) Po w er consumption (kW) Po w er factor (%) COP (W/W) Energy efficiency class * Energy rating **
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E
SP562AT-E SP802AT-E SP1102A T-E SP1402AT-E
5.0 7.1 10.0 12.5
5.6 8.0 11.2 14.0
1 phase 230V (220 – 240V) 50Hz
6.51 – 5.97 9.74 – 8.93 11.72 – 10.74 18.09 – 16.58
1.39 2.10 2.50 3.90 97 98 97 98
3.60 3.38 4.00 3.21
AAAA
————
7.26 – 6.66 9.74 – 8.93 11.72 – 10.74 16.70 – 15.31
1.55 2.10 2.50 3.60 97 98 97 98
3.61 3.81 4.48 3.89
AAAA
————
Zinc hot dipping steel plate
— 320 320 320 320 700 1000 1350 1350 800 800 800 800
———— ———— ———— 30 39 54 54 ————
Finned tube
Centrifugal Centrifugal Centrifugal Centrifugal
13.0/11.9/9.8 19.0/16.2/13.3 27.0/23.0/18.9 33.0/28.0/23.1 120 120 120 120
UFM11BFCE UFM21BFCE UFM21BE UFM31BE UFM 41BE UFM61BE UFH51BFCE UFH61BFCE
UFM71BE UFH 81BE
RBC-AMT31E, AS21E2, TCB-SC642TLE2, AX21E2
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
40/37/33 40/37/34 42/39/36 44/41/38 55/52/48 55/52/49 57/54/51 59/56/53
– 12 –
* : IEC standard, ** : AS standard
1-1-3. Under Ceiling Type
<Digital Inverter>
Revised : Mar. 2007
Model
Cooling capacity (kW) Heating capacity (kW) Po w er supply
Cooling
Electrical characteristics
Heating
Main unit
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min)
Air filter Controller (Sold separately)
Connecting pipe Liquid side (mm)
Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Po w er consumption (kW) Po w er factor (%) EER (W/W) Energy efficiency class * Energy rating ** Running current (A) Po w er consumption (kW) Po w er factor (%) COP (W/W) Energy efficiency class * Energy rating **
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E
SM563AT-E SM803AT-E SM1103AT-E SM1403AT-E
5.0 7.0 10.0 12.3
5.6 8.0 11.2 14.0
1 phase 230V (220 – 240V) 50Hz
8.71 – 7.98 12.23 – 11.21 16.20 – 14.90 21.18 – 19.40
1.82 2.53 3.51 4.52 95 94 98 97
2.75 2.77 2.85 2.72
DDCD
2.5 2.5 3.0 2.5
7.85 – 7.19 11.94 – 10.95 14.84 – 13.61 19.40 – 17.78
1.64 2.47 3.20 4.14 95 94 98 97
3.41 3.24 3.50 3.38
BCBC
4.0 4.0 5.0 3.5 Shine white
— 210 210 210 210 910 1180 1595 1595 680 680 680 680
———— ———— ———— 21 25 33 33 ————
Finned tube
Centrifugal Centrifugal Centr ifugal Centrifugal
13.0/11.2/10.0 18.5/16.7/14.6 27.5/24.0/21.2 30.0/26.0/23.1 60 60 120 120
Attached main unit
RBC-AMT31E, AS21E2, TCB-SC642TLE2, AX21E2
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
36/33/30 38/36/33 41/38/35 43/40/37 51/48/45 53/51/48 56/53/50 58/55/52
– 13 –
* : IEC standard, ** : AS standard
<Super Digital Inverter>
Revised : Mar. 2007
Model
Cooling capacity (kW) Heating capacity (kW) Po w er supply
Cooling
Electrical characteristics
Heating
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Po w er consumption (kW) Po w er factor (%) EER (W/W) Energy efficiency class * Energy rating ** Running current (A) Po w er consumption (kW) Po w er factor (%) COP (W/W) Energy efficiency class * Energy rating **
SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E
SP562AT-E SP802AT-E SP1102A T-E SP1402AT-E
5.0 7.1 10.0 12.5
5.6 8.0 11.2 14.0
1 phase 230V (220 – 240V) 50Hz
6.61 – 6.06 9.74 – 8.93 11.24 – 10.31 18.09 – 16.58
1.41 2.10 2.40 3.90 97 98 97 98
3.55 3.38 4.17 3.21
AAAA
————
7.03 – 6.44 10.20 – 9.35 11.72 – 10.74 17.39 – 15.94
1.50 2.20 2.50 3.75 97 98 97 98
3.73 3.64 4.48 3.73
AAAA
————
Main unit
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min)
Air filter Controller (Sold separately)
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Shine white
— 210 210 210 210 910 1180 1595 1595 680 680 680 680
———— ———— ———— 21 25 33 33 ————
Finned tube
Centrifugal Centrifugal Centrifugal Centrifugal
13.0/11.2/10.0 18.5/16.7/14.6 27.5/24.0/21.2 30.0/26.0/23.1 60 60 120 120
Attached main unit
RBC-AMT31E, AS21E2, TCB-SC642TLE2, AX21E2
Gas side (mm)
Connecting pipe Liquid side (mm)
Drain port (mm) Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
– 14 –
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
36/33/30 38/36/33 41/38/35 43/40/37 51/48/45 53/51/48 56/53/50 58/55/52
* : IEC standard, ** : AS standard
1-1-4. Twin Type
<Digital Inverter>
Revised : Mar. 2007
Type
Model
Cooling capacity (kW) Heating capacity (kW)
Pow er supply
Electrical characteristics
Fan unit
Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Pow er supply
Inter connecting pipes
Fan unit Standard air flow high (m³/min)
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) Sound power level Cooling/Heating (dB•A)
Indoor unit 1 RAV­Indoor unit 2 RAV­Outdoor unit RAV-
Indoor unit
Running current (A) Power consumption (kW)
Cooling Power factor (%)
EER (W/W) Energy efficiency class * Running current (A) Power consumption (kW)
Heating Power factor (%)
COP (W/W)
Energy efficiency class * Fan Standard
air flow Motor (W)
Outdoor unit
Standard length (m) Min. length (m) Max. total length (m) Over 30m
Height difference
Fan
Motor (W)
Gas side
Liquid side
H/M/L (m³/min)
Outdoor lower (m) Outdoor high (m)
Main (mm) Sub (mm) Main (mm) Sub (mm)
4-Way Air Cassette Concealed Duct Under Ceiling SM563UT-E SM803UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E SM563UT-E SM803UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E
SM1103AT-E SM1403AT-E SM1103AT-E SM1403AT-E SM1103AT-E SM1403AT-E
10.0 12.5 10.0 12.5 10.0 12.3
11.2 14.0 11.2 14.0 11.2 14.0
Indoor unit
1 phase 230V (220 – 240V) 50Hz
14.40–13.20 19.17–17.57 16.51–15.14 20.71–18.99 16.28–14.92 21.18–19.42
3.11 4.09 3.56 4.42 3.51 4.52 98 97 98 97 98 97
3.22 3.06 2.81 2.83 2.85 2.72
ABCCCD
14.40–13.20 18.74–17.18 14.56–13.35 18.88–17.31 14.84–13.61 19.40–7.78
3.10 4.00 3.14 4.03 3.20 4.14 98 97 98 97 98 97
3.61 3.50 3.57 3.47 3.50 3.38
ABBBBC
Turbo fan Turbo fan Centrifugal Centrifugal Centrifugal Centrifugal
17.5/ 20.0/ 13.0/ 19.0/ 13.0/ 18.5/
13.9/12.1 15.7/13.6 11.9/9.8 16.2/13.3 11.2/10.0 16.7/14.6 60 60 120 120 60 60
32/29/27 34/31/28 40/37/33 40/37/34 36/33/30 38/36/33 47/44/42 49/46/43 55/52/48 55/52/49 51/48/45 53/51/48
Outdoor unit
1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.)
7.5 7.5 7.5 7.5 7.5 7.5
5.0 5.0 5.0 5.0 5.0 5.0 50 50 50 50 50 50
40g/m (31m to 50m) 30 30 30 30 30 30 30 30 30 30 30 30
Propeller fan
75 75 75 75 75 75
100 100 100 100 100 100
15.9 15.9 15.9 15.9 15.9 15.9
12.7 12.7 12.7 15.9 12.7 15.9
9.5 9.5 9.5 9.5 9.5 9.5
6.4 6.4 6.4 9.5 6.4 9.5 53/54 53/54 53/54 53/54 53/54 53/54 70/71 70/71 70/71 70/71 70/71 70/71
– 15 –
* : IEC standard
<Super Digital Inverter>
Revised : Mar. 2007
Type
Model
Cooling capacity (kW) Heating capacity (kW)
Indoor unit
Pow er supply
Electrical characteristics
Fan unit
Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Outdoor unit
Pow er supply
Inter connecting pipes
Fan unit Standard air flow high (m³/min)
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) Sound power level Cooling/Heating (dB•A)
Indoor unit 1 RAV­Indoor unit 2 RAV­Outdoor unit RAV-
Running current (A) Power consumption (kW)
Cooling Power factor (%)
EER (W/W) Energy efficiency class * Running current (A) Power consumption (kW)
Heating Power factor (%)
COP (W/W)
Energy efficiency class * Fan Standard
air flow Motor (W)
Standard length (m) Min. length (m) Max. total length (m) Over 30m
Height difference
Fan
Motor (W)
Gas side
Liquid side
H/M/L (m³/min)
Outdoor lower (m) Outdoor high (m)
Main (mm) Sub (mm) Main (mm) Sub (mm)
4-Way Air Cassette Concealed Duct Under Ceiling SM563UT-E SM803UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E SM563UT-E SM803UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E
SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E
10.0 12.5 10.0 12.5 10.0 12.3
11.2 14.0 11.2 14.0 11.2 14.0
Indoor unit
1 phase 230V (220 – 240V) 50Hz
11.24–10.31 16.51–15.14 11.72–10.74 18.09–16.58 11.24–10.31 18.09–16.58
2.40 3.56 2.50 3.90 2.40 3.90 97 98 97 98 97 98
4.17 3.51 4.00 3.21 4.17 3.21
AAAAAA
11.95–10.95 16.60–15.22 11.95–10.95 16.70–15.31 11.95–10.95 17.39–15.94
2.55 3.58 2.55 3.60 2.55 3.75 97 98 97 98 97 98
4.39 3.91 4.39 3.89 4.39 3.79
AAAAAA
Turbo fan Turbo fan Centrifugal Centrifugal Centrifugal Centrifugal
17.5/ 20.0/ 13.0/ 19.0/ 13.0/ 18.5/
13.9/12.1 15.7/13.6 11.9/9.8 16.2/13.3 11.2/10.0 16.7/14.6 60 60 120 120 60 60
32/29/27 34/31/28 40/37/33 40/37/34 36/33/30 38/36/33 47/44/42 49/46/43 55/52/48 55/52/49 51/48/45 53/51/48
Outdoor unit
1 phase 230V (220 – 240V) 50Hz (Po wer exclusive to outdoor is required.)
7.5 7.5 7.5 7.5 7.5 7.5
5.0 5.0 5.0 5.0 5.0 5.0 50 50 50 50 50 50
40g/m (31m to 50m) 30 30 30 30 30 30 30 30 30 30 30 30
Propeller fan
125 125 125 125 125 125
63 + 63 63 + 63 63 + 63 63 + 63 63 + 63 63 + 63
15.9 15.9 15.9 15.9 15.9 15.9
12.7 15.9 12.7 15.9 12.7 15.9
9.5 9.5 9.5 9.5 9.5 9.5
6.4 9.5 6.4 9.5 6.4 9.5 49/51 53/54 49/51 53/54 49/51 53/54 66/68 70/71 66/68 70/71 66/68 70/71
– 16 –
* : IEC standard
1-2. Outdoor Unit
<Digital Inverter>
Revised : Mar. 2007
Model name RAV-
Power supply
Type
Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Standard length (m)
Min. length (m)
Max. total length (m) Inter connecting pipe
Outer dimension Width (mm)
Additional refrigerant charge
under long piping connector
Height
difference
Height (mm)
Outdoor lower (m) Outdoor higher (m)
SM563AT-E SM803AT-E SM1103AT-E SM1403AT-E
1 phase 230V (220 – 240V)
50Hz (Power exclusive to outdoor is required.)
Hermetic compressor
1.1 1.6 2.5 3.0 4444
1.0 1.7 2.8 2.8
Pulse motor valve
7.5 7.5 7.5 7.5
5.0 5.0 5.0 5.0
30 30 50 50
20g/m 40g/m 40g/m 40g/m
(21m to 30m) (21m to 30m) (31m to 50m) (31m to 50m)
30 30 30 30
30 30 30 30 550 550 795 795 780 780 900 900
Depth (mm) Appearance Total weight (kg) Heat exchanger
Fan Fan unit Standard air flow (m³/h)
Motor (W)
Gas side (mm) Connecting pipe
Liquid side (mm) Sound pressure level Cooling/Heating (dB•A) Sound power leve l Cooling/Heating (dB•A) Outside air temperature, Cooling (°C) Outside air temperature, Heating (°C)
290 290 320 320
Silky shade (Muncel 1Y8.5/0.5)
38 44 77 77
Finned tube
Propeller fan 40 45 75 75 43 43 100 100
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 46/48 48/50 53/54 54/54 63/65 65/67 70/71 71/71
43 to –15 15 to –15
– 17 –
<Super Digital Inverter>
Model name RAV-
Power supply
Type
Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Standard length (m)
Min. length (m)
Max. total length (m) Inter connecting pipe
Outer dimension Width (mm)
Additional refrigerant charge
under long piping connector
Height
difference
Height (mm)
Outdoor lower (m) Outdoor higher (m)
SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E
1 phase 230V (220 – 240V)
50Hz (Power exclusive to outdoor is required.)
Hermetic compressor
2.0 2.0 3.75 3.75 4444
1.5 2.1 2.95 2.95
Pulse motor valve
7.5 7.5 7.5 7.5
5.0 5.0 5.0 5.0
50 50 70 70
20g/m 40g/m 40g/m 40g/m
(21m to 50m) (31m to 50m) (31m to 70m) (31m to 70m)
30 30 30 30
30 30 30 30 795 795 1340 1340 900 900 900 900
Depth (mm) Appearance Total weight (kg) Heat exchanger
Fan Fan unit Standard air flow (m³/h)
Motor (W)
Gas side (mm) Connecting pipe
Liquid side (mm) Sound pressure level Cooling/Heating (dB•A) Sound power leve l Cooling/Heating (dB•A) Outside air temperature, Cooling (°C) Outside air temperature, Heating (°C)
320 320 320 320
Silky shade (Muncel 1Y8.5/0.5)
55 62 95 95
Finned tube
Propeller fan 57 57 125 125 63 63 63 + 63 63 + 63
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 46/47 47/49 49/51 53/54 63/64 64/66 66/68 70/71
43 to –15 15 to –15
– 18 –
1-3. Operation Characteristic Curve
• Operation characteristic curve <Digital Inverter>
RAV-SM563AT-E, RAV-SM803AT-E
<Cooling> <Heating>
Revised : Mar. 2007
14
12
10
8
6
Current (A)
4
2
0
0 20 40 60708090100
RAV-SM803AT-E
RAV-SM803AT-E
RAV-SM563AT-E
RAV-SM563AT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
16
14
RAV-SM803AT-E
12
10
8
RAV-SM803AT-E
Current (A)
6
4
2
0
0 20406080100120
RAV-SM563AT-E
RAV-SM563AT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
RAV-SM1103AT-E, RAV-SM1403A T-E
<Cooling> <Heating>
22 22
20
RAV-SM1103AT-E
RAV-SM1103AT-E
18
16
14
12
10
Current (A)
8
6
4
2
0
0204060
RAV-SM1403AT-E
RAV-SM1403AT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
20
18
RAV-SM1403AT-E
RAV-SM1403AT-E
16
14
12
10
Current (A)
8
6
4
2
0
0 204060
Compressor speed (rps)
RAV-SM1103AT-E
RAV-SM1103AT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
Compressor speed (rps)
– 19 –
• Operation characteristic curve <Super Digital Inverter>
RAV-SP562AT-E, RAV-SP802AT-E
<Cooling> <Heating>
14
12
RAV-SP802AT-E
RAV-SP802AT-E
10
8
6
Current (A)
4
2
0
0 20406050 70 80 100
RAV-SP562AT-ERAV-SP562AT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps) Compressor speed (rps)
16
14
RAV-SP802AT-E
12
10
8
RAV-SP802AT-E
RAV-SP562AT-E
RAV-SP562AT-E
Current (A)
6
4
2
0
0 204060 908070 100
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
RAV-SP1102AT-E, RAV-SP1402A T-E
<Cooling> <Heating>
22
20
18
16
14
12
10
RAV-SP1402AT-E
RAV-SP1402AT-E
Current (A)
8
RAV-SP1102AT-E
6
4
2
0
020406080
RAV-SP1102AT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
22
20
18
16
14
12
10
Current (A)
8
6
4
2
0
020406080
RAV-SP1402AT-E
RAV-SP1402AT-E
RAV-SP1102AT-E
RAV-SP1102AT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
Compressor speed (rps)
– 20 –
• Capacity variation ratio according to temperature
RAV-SM563AT-E, RAV-SM803AT-E, RAV -SM1103AT-E, RAV-SM1403AT-E RAV-SP562AT-E, RAV-SP802AT-E, RAV-SP1102AT-E, RAV-SP1402AT-E
<Cooling> <Heating>
Revised : Mar. 2007
105
100
95
90
85
80
75
70
Capacity ratio (%)
65
60
55
50
32 33 34 35 36 37 38 39
Outdoor temp. (˚C)
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
40
41 42 43
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
-14-12-10-8-6-4-20246810
Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outdoor temp. (˚C)
– 21 –
2. AIR DUCTING WORK
2-1. Static Pressure Characteristics of Each Model
RAV-SM562BT-E, RAV-SM802BT-E, RAV-SM1102BT-E, RAV -SM1402BT-E
Fig. 1 RAV-SM562BT-E (Round duct)
140
120
100
Usable lim
80
60
Static pressure (Pa)
40
Air volume limit (Min.)
20
0 500 700 780 900
Standard air volume 780m³/h
High static pressure 2H tap
it
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume m³/h
140
120
100
80
60
Static pressure (Pa)
40
Air volume limit (Max.)
20
Fig. 3 RAV-SM802BT-E (Round duct)
Standard air volume 1140m³/h
High static pressure 2H tap
Usable limit
Air volume limit (Min.)
0 800
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
1000
Air volume m³/h
Air volume limit (Max.)
12001140 1300
Fig. 2 RAV-SM562BT-E (Square duct)
140
120
108 100
80
60
Usable limit
Static pressure (Pa)
40
Air volume limit (Min.)
20
0 500 700 780 900
Standard air volume 780m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume m³/h
140
120
100
80
60
Static pressure (Pa)
40
Air volume limit (Max.)
20
Fig. 4 RAV-SM802BT-E (Square duct)
Standard air volume 1140m³/h
High static pressure 2H tap
Usable limit
Air volume limit (Min.)
0 800
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
1000
Air volume m³/h
Air volume limit (Max.)
12001140 1300
– 22 –
0
Fig. 5 RAV-SM1102BT-E (Round duct)
Fig. 7 RAV-SM1402BT-E (Round duct)
140
120
Standard air volume 1620m³/h
140
120
Standard air volume 1980m³/h
High static pressure 2H tap
High static pressure 2H tap
100
100
Usable limit
High static pressure 1H tap
80
60
Standard H tap
Static pressure (Pa)
40
Air volume limit (Min.)
20
0 1200
Low static pressure H tap
Standard L tap
1620
Air volume limit (Max.)
2000
80
60
Static pressure (Pa)
40
20
0 1200 1800
Air volume m³/h
Usable limit
Air volume limit (Min.)
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
1980
Air volume m³/h
Air volume limit (Max.)
2200 2400
Fig. 6 RAV-SM1102BT-E (Square duct)
140
120
Usable limit
100
80
60
Static pressure (Pa)
40
Air volume limit (Min.)
20
Low static pressure H tap
Standard air volume 1620m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Standard L tap
Air volume limit (Max.)
Fig. 8 RAV-SM1402BT-E (Square duct)
140
120
100
80
60
Usable limit
Static pressure (Pa)
40
Air volume limit (Min.)
20
Standard air volume 1980m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume limit (Max.)
0
1200
1620
Air volume m³/h
2000
– 23 –
0 1200 1800
Air volume hm³/h
1980
2200 240
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
3-1. Indoor Unit
3-1-1. 4-Way Air Discharge Cassette Type
RAV-SM563UT-E, RAV-SM803UT-E
Surface under ceiling
200
113
173
Refrigerant pipe connecting port A
130
200
Check port (¨450)
Check port (¨450)
Cable draw-in port
45
Refrigerant pipe connecting port B
Electric parts box
860 to 910 Recommended external size
30
105
270 105 25070
950 Panel external dimension
790 Hanging bolt pitch
346.5
860 to 910 Recommended external size
Surface under ceiling
130
210
Indoor unit
Hanging bolt M10 or W3/8 Procured locally
Standing 850 or less
Standing 640 or less
360
Drain up standing size
256
88
Surface under ceiling
SM563 SM803
840 Unit external dimension
A
Ø6.4 Ø9.5
150
105
Ø12.7 Ø15.9
Knockout
97
35
Z view
for humidifier
Ceiling panel (Sold separately)
Surface under ceiling
80
Ø162
B
415.0
105105
240
254.5
840 Hanging bolt
480
227
12097
Surface under ceiling
381.6 227
480
723 Hanging bolt pitch
950 Panel external dimension
35˚
Z
64
57
57.5
25
188
Surface under ceiling
120
– 24 –
RAV-SM1103UT-E, RAV-SM1403UT-E, RAV-SP1102UT-E
860 to 910 Recommended external size
200
Check port (¨450)
200
Check port (¨450)
Take-in port of pipes
45
30
SM1103 SM1403 SP1102
860 to 910 Recommended external size
Ceiling bottom surface
A
B
Ø9.5
Ø15.9
Ø9.5
Ø15.9
Ø9.5 319183Ø15.9
Standing 850 or less
Standing 640 or less
C
183 183
D
319 319
113
173
Refrigerant pipe connecting port A
Refrigerant pipe connecting port B
130
Ceiling bottom surface
Ø162
105
80
Electric parts box
415.0
240
105 105
840 Unit external dimension
105
105
270
250
70
860 to 910 Ceiling opening dimension
950 Panel external dimension
790 Hanging bolt pitch
Knockout square hole for divide duct For Ø150
346.5
130
210
Drain pipe connecting port
Hanging bolt M10 or Ø3/8 (To be procured locally)
381.6
480
723 Hanging bolt pitch
950 Panel external dimension
860 to 910 Ceiling opening dimension
35˚
360
Indoor unit
Drain up standing size
D
227
88
Surface under ceiling
Ceiling panel (sold separately)
Ø162
105
Ceiling bottom surface
Knockout square hole for divide duct for Ø150 (2 positions)
C97
254.5
840 Unit external dimension
480
227
– 25 –
57.5
188
Z
C
97
Z view
35
Ceiling bottom surface
64
57
25
Surface under ceiling
3-1-2. Concealed Duct Type
RAV-SM562BT-E, RAV-SM802BT-E, RAV-SM1102BT-E, RAV-SM1402BT-E
129
110
Knock-out hole Ø125 (Air take-in port)
6-Ø4 T apping screw undersized hole Ø160
• Dimension
Discharge port flange N-Ø200
60 to 260 9
Suction port canvas (Separate sold)
Refrigerant pipe connecting port (Gas side ØF)
Hanging bolt pitch B
Main unit dimension A
J = M x K H
C
Ceiling open size D
Panel external dimension E
Hanging bolt 4-M10 screw (Arranged locally)
44 49
Refrigerant pipe connecting port (Liquid side ØG)
Drain pipe connecting port for vinyl chloride pipe (Inner dia. 32, VP. 25)
75
Main unit dimension 800
Hanging bolt pitch 700
50
131
50
Ø26 Power supply, remote controller cable take-out port
638
498
393
41
196
243
Panel C.L
410
Ceiling open size
470
Panel external dimension 500
5941
174
Suction port flange (Separate sold)
Suction port panel (Separate sold)
320
ABCDEFGHJKMNO
RAV-SM562BT
RAV-SM802BT
RAV-SM1102BT RAV-SM1402BT
700 766 690 750 780 12.7 6.4 252 280 280 1 2 410
1000 1066 990 1050 1080 15.9 9.5 252 580 290 2 3 410
1350 1416 1340 1400 1430 15.9 9.5 252 930 310 3 4 410
NOTE 1 :
For maintenance of the equipment, be sure to install a check port A at the position as shown below.
NOTE 2 :
Using the drain up kit sold separately, drain-up by 300 (mm) from drain pipe draw-out port of the main unit is necessary. The drain-up over 300mm or more is impossible.
Plane view of main unit
(Pipe side)
Discharge side
Check port A
300
100
450
– 26 –
3-1-3. Under Ceiling Type
RAV-SM562CT-E, RAV-SM802CT-E, RAV-SM1102CT-E, RAV-SM1402CT-E
128
84
170320
(Hanging position)
Hanging bolt
50
Within
Upper pipe draw-out port (Knockout hole)
Power supply cable take-in port (Knockout)
Remote controller cable take- in port (Knockout hole)
53
Left drain size
B (Hanging position)
Refrigerant pipe (Gas side ØD)
Ceiling surface
Unit
Refrigerant pipe (Liquid side ØC)
A
216
110
70
75 97
76
50
130
680
Drain pipe connecting port
146
145
Pipe hole on wall (Ø100 hole)
210
167
105
347
262
135 84
Outside air take-in port (Duct sold separately)(Knockout hole Ø92)
Pipe draw-out port (Knockout hole)
Drain port VP20 (Inner dia. Ø26, hose attached)
114
41
200 (Liquid pipe)
216 (Gas pipe)
Remote controller cable take- in port
Power supply cable take-in port (Knockout hole)
Remote controller cable take- in port
90
32
(Knockout hole)
92
Drain left pipe draw-out port (Knockout hole)
32
171
Wireless sensor mounting section
250 or more250 or more
Model name A B C D 562CT 802CT 1102CT, 1402CT
910 1180 1595
855 1125 1540
Ø6.4 Ø12.7
Ø9.5 Ø15.9
500 or more
– 27 –
3-2. Outdoor Unit
RAV-SM563AT-E, RAV-SM803AT-E
Revised : Mar. 2007
Drain hole (2-Ø20 × 88 long hole)
69.5 147
320
306
Ø6 hole pitch
For anchor bolt)
(Long hole pitch
21
550
290
A legs
6
48335
30
B legs
44952
Drain hole (Ø25)
60
600
108 125
30
20
2-Ø11 × L14 long hole (For Ø8-Ø10 anchor bolts)
483 257
108
90
2-Ø11-14 U-shape hole
54
(For Ø8-Ø10 anchor bolts)
Connecting pipe port Gas flare side RAV-SM563AT-E: Ø12.7
( )
RAV-SM803AT-E: Ø15.9 Connecting pipe port
Liquid flare side RAV-SM563AT-E: Ø6.4
( )
RAV-SM803AT-E: Ø9.5
8-Ø6 hole (For fixing outdoor unit)
25 22
157 79
21
145
31 143
8
Space required for service
2-Ø11 × 14 U-shape holes (For Ø8–Ø10 anchor bolt)
32
Discharge guard
150 or more
320
500 or more
600
54 38
R15
3
320
Ø11 × 14 U-shape hole
Details of A legs Details of B legs
2-Ø6 hole
Product external line
150
or more
500
780
600
Suction port
Discharge port
Discharge guide mounting hole (4-Ø4.5 embossing)
Discharge port
Ø11 × 14 U-shape holes
320
300 or more
(Minimum distance up to wall)
2-Ø11 × 14 long hole (For Ø8–Ø10 anchor bolt)
2-Ø6 hole
38 54
Product external line
R15
600
3
71
93
137
Charge port
342
54
Earth
terminal
– 28 –
RAV-SM1103AT-E, RAV-SM1403AT-E / RAV-SP562AT-E, RAV-SP802AT-E
Knockout (For draining)
21
Suction port
365 17.517.5
40 70
(Long hole pitch
for anchor bolt)
21
565 101
Drain hole (Ø20 × 88 Burring hole)
29 90 191 20
Knockout (For draining)
6026
314
43
Suction port
Discharge port
300150 900
Drain hole (Ø25 Burring hole)
Part B
40
39
Part A
95
43
Handles (Both sides)
Refrigerant pipe connecting port Flare at liquid side Ø6.4: RAV-SP562AT-E
( )
Ø9.5: RAV-SP802AT-E Refrigerant pipe connecting port
Flare at gas side Ø12.7: RAV-SP562AT-E
( )
Ø15.9: RAV-SP802AT-E
47
Installation bolt hole (Ø12 × 17 U-shape holes)
17.5 4040
Details of B part
Details of A part
17.5
Installation bolt hole (Ø12 × 17 U-shape holes)
2
Discharge guide mounting hole (4-Ø4 Embossing)
1
60 90
58
27
161
32028
400
264
300
795
25
85
2
Z
2
46
165
60 80
30 45
1
307
2760
96
2-Ø12 × 17 U-shape holes (For Ø8–Ø10 Anchor bolt)
264
6760
154
1
Knockout for lower piping
Space required for service
150 or more
365
500 or more
Z views
Suction port
150
or more
Discharge port
600
86 7
7
58
150 or more
Discharge port
(Minimum distance up to wall)
2-Ø12 × 17 long hole (For Ø8–Ø10 Anchor bolt)
– 29 –
RAV-SP1102AT-E, RAV-SP1402A T-E
Knockout (Drain)
365 17.517.5
350 625
Discharge guide mounting port (8-Ø3 embossing)
70 21
Suction port
21 40
9029
Knockout (Drain)
26
150
56567 60 565
164 300
314
Drain hole (Ø20 x 88)
191 20
Suction port
Drain hole (Ø25)
43
60
Discharge port
600 900
B legs
A legs
40
43
40
108
Refrigerant pipe connecting port (Ø9.5 flare at liquid side)
Refrigerant pipe connecting port (Ø15.9 flare at gas side)
54
28
706
715
67
154
60 27
z
95
307 400
60
60 90
27
Mountig bolt hole (Ø12 x 17 long hole)
161
58
320
1340
89
25
Mountig bolt hole (Ø12 x 17 U-shape hole)
12
20
46
8060
165
32 45
40
Details of A legs Details of B legs
2-Ø12 x 17 U-shape holes (For Ø8–Ø10 anchor bolt)
150 or more
365
– 30 –
40
86 7
Z view
58 7
Space required for service
600
Suction port
150
or more
Discharge port
500 or more
Discharge port
2-Ø12 x 17 long hole (For Ø8–Ø10 anchor bolt)
150 or more
(Minimum distance up to wall)
Loading...
+ 165 hidden pages