Toshiba RAV-SM801AT-E, RAV-SM1401AT-E, RAV-SM561AT-E, RAV-SM1101AT-E SERVICE MANUAL

SERVICE MANUAL
SPLIT TYPE
<NEW DIGITAL INVERTER>
FILE NO. A05-001
OUTDOOR UNIT
RAV-SM561AT-E
RAV-SM801AT-E RAV-SM1101AT-E RAV-SM1401AT-E
INDOOR UNIT
This Service Manual describes contents of the new outdoor unit. For the indoor unit, ref er to the Service Manual with FILE NO. A03-003F.
R410A
PRINTED IN JAPAN, Apr.,2005 ToMo
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prev ent destruction of the oz one layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer.
CONTENTS
1. SPECIFICATIONS........................................................................................................... 3
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)............................................................. 5
3. REFRIGERATING CYCLE DIAGRAM ............................................................................ 8
4. WIRING DIAGRAM ....................................................................................................... 11
5. SPECIFICATIONS OF ELECTRICAL PARTS............................................................... 12
6. REFRIGERANT R410A................................................................................................. 13
6-1. Safety During Installation/Servicing................................................................................ 13
6-2. Refrigerant Piping Installation ....................................................................................... 13
6-3. Tools ...................................................................................................................................17
6-4. Recharging of Refrigerant ................................................................................................18
6-5. Brazing of Pipes ................................................................................................................19
7. CONTROL SPECIFICATIONS ...................................................................................... 21
7-1. Outdoor Controls ..............................................................................................................21
7-2. Outline of Main Controls...................................................................................................24
8. TROUBLESHOOTING .................................................................................................. 29
8-1. Summary of Troubleshooting ........................................................................................... 29
8-2. Check Code List ................................................................................................................31
8-3. Error Mode Judgment by LED Display of Outdoor Unit ................................................ 34
8-4. Contents of Error Display.................................................................................................35
8-5. Troubleshooting Procedure for Each Check Code.........................................................36
8-5. Other Function...................................................................................................................57
9. DETACHMENTS............................................................................................................ 58
10. EXPLODED VIEWS AND PARTS LIST ........................................................................ 73
– 2 –
RAV-SM561AT-E, RAV-SM801AT-E

1. SPECIFICATIONS

Model name
Appearance
Power supply
Type
Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Standard length
Max. total length (m) Pipe Over 20m
Outdoor lower (m)
Height difference
Outdoor higher (m)
Height (mm) Outer dimension Width (mm)
RAV-SM561AT-E RAV-SM801AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230 V (220 – 240 V) 50 Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
1.1 1.6 4 poles
R410A 1.0 R410A 1.7
Pulse motor valve
20 (without additional charge)
30
Add 20 g/m (Max. 200 g) Add 40 g/m (Max. 400 g)
30
30 550 780
Depth (mm) Total weight (kg) Heat exchanger
Fan Fan unit Standard air flow High (m³/h)
Motor (W)
Connecting pipe
Protection device
Sound level High (Mid./Low) (Note 2) (Cooling/Heating)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Gas side (mm)
Liquid side (mm)
(dBA)
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
38 42
2400 2700
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
Discharge temp. sensor
Over-current sensor
Compressor thermo.
46 / 48 48 / 50
290
Finned tube
Propeller fan
43
– 3 –
RAV-SM1101AT-E, RAV-SM1401AT-E
Model name
Appearance
Power supply
Type Compressor Motor (kW)
Pole Refrigerant charged (kg) Refrigerant control
Standard length
Max. total length (m) Pipe Over 20m
Outdoor lower (m)
Height difference
Outdoor higher (m)
Height (mm) Outer dimension Width (mm)
RAV-SM1101AT-E RAV-SM1401AT-E
Silky shade (Muncel 1Y8.5/0.5)
1 phase 230 V (220 – 240 V) 50 Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
2.5 3.0 4 poles
R410A 2.8
Pulse motor valve
30 (without additional charge)
50
Add 40 g/m (Max. 800 g)
30
30 795 780
Depth (mm) Total weight (kg) Heat exchanger
Fan Fan unit Standard air flow High (m³/h)
Motor (W)
Connecting pipe
Protection device
Sound level High (Mid./Low) (Note 2) (Cooling/Heating)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Gas side (mm)
Liquid side (mm)
Discharge temp. sensor
Over-current sensor
Compressor thermo.
(dBA)
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
320
77
Finned tube
Propeller fan
4500
100
Ø15.9 (5/8”)
Ø9.5 (3/8”)
53 / 54
– 4 –
RAV-SM561AT-E

2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)

Drain hole (Ø25)
Drain hole (2-Ø20 × 88 long hole)
A legs
60
600
108 125
30
54
90
2-Ø11-14 U-hole (For Ø8–Ø10 anchor bolts)
Connecting pipe port (Flare Ø12.7 at gas side)
69.5 147
320
306
hole pitch)
(Anchor bolt long
21
550
290
Ø6 hole pitch
B legs
449
483
30
20
483 257
108
Connecting pipe port (Flare Ø6.4 at liquid side)
8-Ø6 hole (For fixing outdoor unit)
2-Ø11 × 14 long hole (For Ø8–Ø10 anchor bolts)
157 79
25 31 143 22
54
137
93
21
145
8
32
52
35 6
Guard for air discharge
600
54
R15
38 11
2-Ø6 hole
Product
320
R5.5
Details of A legs Details of B legs
external line
320
38 54
Product external line
2-Ø6 hole
R15 R5.5
600
500
780
4-Ø4.5 embossing (Ø4 STS used) (For mounting air direction guide)
Space required for service
2-Ø11 × 14 U-shape holes (For Ø8–Ø10 anchor bolt)
Suction port
320
150 or more
500 or more
71
342
Charge port
Anchor bolt mounting dimension
600
Suction port
150
or more
Discharge port
300 or more
(Minimum distance up to wall)
2-Ø11 × 14 long hole (For Ø8–Ø10 anchor bolt)
Earth terminal
5
RAV-SM801AT-E
Drain hole (2-Ø20 × 88 long hole)
A legs
60
600
108 125
Drain hole (Ø25)
30
54
90
2-Ø11–14 U-hole (For Ø8–Ø10 anchor bolts)
Connecting pipe port (Flare Ø15.9 at gas side)
69.5 147
320
306
hole pitch)
(Anchor bolt long
21
550
290
Ø6 hole pitch
B legs
449
483
30
20
483 257
108
Connecting pipe port (Flare Ø9.5 at liquid side)
8-Ø6 hole (For fixing outdoor unit)
2-Ø11 × 14 long hole (For Ø8–Ø10 anchor bolts)
157 79
25 31 143 22
54
137
93
21
145
8
32
52
35 6
Guard for air discharge
600
54
R15
38 11
2-Ø6 hole
Product
320
R5.5
Details of A legs Details of B legs
external line
320
38 54
Product external line
2-Ø6 hole
R15 R5.5
600
500
780
4-Ø4.5 embossing (Ø4 STS used) (For mounting air direction guide)
Space required for service
2-Ø11 × 14 U-shape holes (For Ø8–Ø10 anchor bolt)
Suction port
320
150 or more
500 or more
71
342
Charge port
Anchor bolt mounting dimension
600
Suction port
150
or more
Discharge port
300 or more
(Minimum distance up to wall)
2-Ø11 × 14 long hole (For Ø8–Ø10 anchor bolt)
Earth terminal
6
RAV-SM1101AT-E, RAV-SM1401AT-E
Knockout (For draining)
21
Suction port
365 17.517.5
40 70
(Long hole pitch
for anchor bolt)
21
565 101
Drain hole (Ø20 × 88 Burring hole)
29 90 191 20
Suction port
43
Knockout (For draining)
6026
Discharge port
300150
900
314
Drain hole (Ø25 Burring hole)
Part B
40
39
Part A
43
95
Handles (Both sides)
Refrigerant pipe connecting port (Ø9.5 Flare at liquid side)
Refrigerant pipe connecting port (Ø15.9 Flare at gas side)
47
Installation bolt hole (Ø12 × 17 U-shape holes)
17.5 4040
Details of B part
Details of A part
17.5
Installation bolt hole (Ø12 × 17 U-shape holes)
2
Discharge guide mounting hole (4-Ø4 Embossing)
1
60 90
58
27
161
32028
400
6760
264
154
1
300
264
Z
307
2760
96
Knockout for lower piping
86 7
7 58
Z views
Space required for service
795
2
46
25
85
2
165
60 80
30 45
1
2-Ø12 × 17 U-shape holes (For Ø8–Ø10 Anchor bolt)
150 or more
365
500 or more
Suction port
150
or more
Discharge port
600
150 or more
Discharge port
(Minimum distance up to wall)
2-Ø12 × 17 long hole (For Ø8–Ø10 Anchor bolt)
7
RAV-SM561AT-E
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
12.7mm 6.4mm

3. REFRIGERATING CYCLE DIAGRAM

Indoor unit
TCJ
sensor
Air heat exchanger
TC sensor
TS sensor
TD sensor
Rotary compressor
(DA150A1F-20F)
2-step muffler
Ø19.05 × 200L
4-way valve
(STF-0108Z)
Muffler
Ø19 × L160
Refrigerant pipe at gas side Ø12.7 Packed valve
Packed valve Outer dia. ØA
TO sensor
Heat exchanger Ø8 ripple, 2 rows, 14 steps FP1.3, flat fin
Outdoor unit
TE sensor
Distributor
Refrigerant pipe at liquid side Ø6.4 Packed valve
Min.
5m Packed valve Outer dia. ØB
PMV (Pulse Motor Valve) (CAM-B30YGTF-1)
Strainer
Max. 30m
Cooling Heating
Pressure
(MPa) (kg/cm²G)
Pd P s Pd Ps
Standard
Cooling Overload
Low load Standard
Heating Over load
Low load
4 poles are provided to this compressor.
*
3.50 0.97 35.7 9.9
3.90 1.08 39.8 11.0
1.90 0.70 19.4 7.1
2.31 0.61 13.6 6.2
2.86 0.89 29.2 9.1
1.86 0.25 19.0 2.6
Discharge Suction
Pipe surface temperature (°C)
Indoor heat
exchanger exchanger
(TD) (TS) (TC) (TE)
85 14 12 48 93 26 17 54 48 7 5 30 87 5 40 1 86 17 47 11 69 –14 31 –15
Outdoor heat
Compressor
revolutions per
second (rps)
*
70 70 50 97 95 98
Indoor
fan
HIGH HIGH
LOW HIGH HIGH HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/– 32/24 43/–
18/15.5 –5/–
20/– 7/6 28/– 24/18 15/––10/
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
– 8 –
(70%)
RAV-SM801AT-E
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
15.9mm 9.5mm
Indoor unit
TCJ
sensor
Air heat exchanger
TC sensor
TS
sensor
Accumulator
(1000cc)
compressor
(DA150A1F-20F)
TD
sensor
Rotary
2-step muffler
Ø25 × 200L
4-way valve
(STF-0213Z)
Refrigerant pipe at gas side Ø15.9 Packed valve
Packed valve Outer dia. ØA
TO sensor
Heat exchanger Ø8 ripple, 2 rows, 20 steps FP1.3, flat fin
Outdoor unit
TE sensor
Distributor
Refrigerant pipe at liquid side Ø9.5 Packed valve
Min. 5m
Packed valve Outer dia. ØB
PMV (Pulse Motor Valve) (CAM-B30YGTF-1)
Strainer
Max. 50m
PsPd
Cooling Heating
Pressure
(MPa) (kg/cm²G)
Pd P s Pd Ps
Standard
Cooling Overload
Low load Standard
Heating Over load
Low load
4 poles are provided to this compressor.
*
3.28 0.86 33.4 8.8
3.59 1.00 33.6 10.2
1.85 0.83 18.9 8.5
2.53 0.62 25.8 6.3
3.42 1.07 34.9 10.9
1.99 0.23 20.3 2.3
Discharge Suction
Pipe surface temperature (°C)
Indoor heat
exchanger exchanger
(TD) (TS) (TC) (TE)
84 11 10 45 82 17 16 51 42 8 6 23 75 3 42 2 80 20 54 17 89 –19 34 –18
Outdoor heat
Compressor
revolutions per
second (rps)
*
83 76 35 95 50
120
Indoor
fan
HIGH HIGH
LOW HIGH
LOW HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/– 32/24 43/–
18/15.5 –5/–
20/– 7/6 28/– 24/18 15/––10/
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
– 9 –
(70%)
RAV-SM1101AT-E, RAV-SM1401AT-E
Outer diameter of refrigerant pipe
Gas side ØA Liquid side ØB
15.9mm 9.5mm
Strainer
Indoor unit
TCJ sensor
Air heat exchanger
SM801BT-E / SM800AT-E, SM800UT-E, SM800BT-E, SM800KRT-E
Distributor (Strainer incorporated)
TC sensor
Accumulator
(2500cc)
compressor
(DA420A3F – 21M)
RAV-SM1101AT-E
Cooling: Low pressure
TS sensor
TD sensor
4-way valve
(STF-0213Z)
Muffler
Ø25 × L210
Rotary
Ø25 × L180
Refrigerant pipe at gas side Ø15.9 Ball valve
Ball valve Outer dia. ØA
Outdoor unit
Strainer
TO sensor
TE sensor
Heat exchanger Outer side Ø8, 2 rows, 20 steps
FP1.3, flat fin Inner side Ø9.52, 1 row, 30 steps
FP1.5, flat fin
Refrigerant pipe at liquid side Ø9.5 Packed valve
Packed valve Outer dia. ØB
PMV (Pulse Motor Valve) (UKV-25D22)
Distributor
Min. 5m
Strainer
Max. 50m
Cooling Heating
Standard
Cooling Overload
Low load Standard
Heating Over load
Low load
Pressure
(MPa) (kg/cm²G)
Pd P s Pd Ps
3.44 0.92 35.1 9.4
3.73 1.18 38.1 12.0
1.49 0.70 15.2 7.1
2.80 0.61 28.6 6.2
3.43 1.08 35.0 11.0
2.20 0.25 22.4 2.6
Discharge Suction
Pipe surface temperature (°C)
Indoor heat Outdoor heat exchanger exchanger
(TD) (TS) (TC) (TE)
82 8 10 39 82 15 17 48 398322 80 0 46 1 82 14 55 13 76 –19 36 –16
revolutions per
Compressor second (rps)
*
47 42 30 48 24 55
Indoor
fan
HIGH HIGH
LOW HIGH
LOW HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/– 32/24 43/–
18/15.5 –5/–
20/– 7/6 30/– 24/18 15/––10/
RAV-SM1401AT-E
Pressure
(MPa) (kg/cm²G)
Pd P s Pd Ps
Standard
Cooling Overload
Low load Standard
Heating Over load
Low load
4 poles are provided to this compressor.
*
3.52 0.85 35.9 8.7
3.78 1.12 38.6 11.4
1.51 0.71 15.4 7.2
2.88 0.60 29.4 6.1
3.41 1.08 34.8 11.0
2.35 0.24 24.0 2.4
Discharge Suction
Pipe surface temperature (°C)
Indoor heat Outdoor heat exchanger exchanger
(TD) (TS) (TC) (TE)
878939 84 15 17 47 407323 85 1 47 1 81 14 54 13 80 –19 40 –16
revolutions per
Compressor second (rps)
*
54 45 30 61 24 73
Indoor
fan
HIGH HIGH
LOW HIGH
LOW HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/19 35/– 32/24 43/–
18/15.5 –5/–
20/– 7/6 30/– 24/18 15/––10/
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
(70%)
(70%)
– 10 –
RAV-SM561AT-E, RAV-SM801AT-E

4. WIRING DIAGRAM

Compressor
Reactor
YEL
YEL
BRW
YEL
RED WHI BLK
P25
P23
P21
P35
P34
P19
P18 P11
P08
P04 P05 P06
P24
P22
P20
Q404
Q200~205 IGBT
R221
P.C. Board (MCC-5009)
R220
R219
F03
C13L03
Fuse
T3.15A
AC250V
C12 C14
Power relay
DB02
CT
Relay
P32
CN701 P7
P33 P31 P30 BLK
PUR
Reactor
Surge absorber
Coil for 4-way valve
Varistor
L01
Varistor
F01 Fuse T25A, AC250V
To indoor unit
P10
Power supply 220-240V~, 50Hz
CN300
CN700
P02P03 WHIBLKORN
CN603
CN602
CN601
CN600
BLK WHI RED
Fan motor
Pulse motor valve
TS
(Suction pipe Temp. sensor)
TO
(Outdoor
Temp. sensor)
TD
(Discharge pipe
Temp. sensor)
TE
(Condensor pipe
Temp. sensor)
RAV-SM1101AT-E, RAV-SM1401AT-E
1 2
1 2
1 2
1 2
GRY
WHI
WHI
GRY
P09
P08
P12
F01 Fuse T25A, 250V~
CN01
RED
CN02
WHI
CN03
BLK
PNK
CN02
WHI
Power supply
BLK
1 1 3 3 5 5
PMV
RED
WHI
BLK
RED
321 NL
220V~240V~,50Hz
To indoor unit
ReactorReactor
P13
531
CN13
531
RED
BLK
531
CN01
RED
531
53 41 2 5663 41 2
Pulse motor valve
CN702
WHI
RED BLK
Power factor
control
1 2
CN05
1 2
ORN
1 2 1 2
CN301
WHI
Fan motor
WHI
CN04
~
+
~ ~
P29 RED
P24 BRW
P21 ORG
RY01
P.C. Board (MCC-1438)
PNK
RED
WHI
SUB P.C. Board (MCC-1531)
31 2 31 2
BLK
WHI
RED
YEL
FM
BLU
WHI
PNK
53 41 2 53 41 2
GRY
P28 BLK
53 41 2
CN06
53 41 2
RED
BLK
53 41 2
CN800
53 41 2
CN300
WHI
3 3 1 1
RED
1 1
YEL
113
CN03
WHI
Optional P.C.Board MCC-1522
53 41 2 53 41 2
53 41 2 53 41 2
3
CN04
3
BLU
3
CN804
BLU
WHI
ORN
49C
112
112
P19
2
TH
2
ORN
BLUYEL
P20
P17
CN600
BLK
TS TE TO
113
CN605
WHI
CN700 YEL
RED
3 3 1 1
RED
CN500
BLU
3
P18
20SF
112
CN604
WHI
2
CN09 RED
CN10 WHI
CN11 BLK
IGBT Module
TD
112
113
2
CN600
CN601
WHI
WHI
7 85 63 41 2
CN801
Coil for 4-way valve
WV U
CM
Compressor
3
11

5. SPECIFICATIONS OF ELECTRICAL PARTS

RAV-SM561AT-E, RAV-SM801AT-E
No.
1
Fan motor
2
Compressor
3
Reactor
4
Outdoor temp. sensor (To-sensor)
5
Heat exchanger sensor (Te-sensor)
6
Suction temp. sensor (Ts-sensor)
7
Discharge temp. sensor (Td-sensor)
8
Fuse (Switching power (Protect))
9
Fuse (Inverter, input (Current protect)
10
4-way valve solenoid coil
11
Compressor thermo. (Protection)
Parts name
RAV-SM1101AT-E, RAV-SM1401AT-E
No.
1
Fan motor
Parts name
Type
ICF-140-43-4
DA150A1F-20F
CH-57
— — — —
VHV-01AJ503C1
US-622
Type
ICF-280-100-1
Specifications
Output (Rated) 43 W 3 phase, 4P, 1100 W 10 mH, 16A 10 k at 25°C 10 k at 25°C 10 k at 25°C 50 k at 25°C T3.15 A, AC 250 V 25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C
Specifications
Output (Rated) 100 W
2
Compressor
3
Reactor
4
Outdoor temp. sensor (To-sensor)
5
Heat exchanger sensor (Te-sensor)
6
Suction temp. sensor (Ts-sensor)
7
Discharge temp. sensor (Td-sensor)
8
Fuse (Switching power (Protect))
9
Fuse (Inverter, input (Current protect))
10
4-way valve solenoid coil
11
Compressor thermo. (Protection)
DA420A3F-21M
CH-56-2Z-T
— — — —
VHV-01AJ503C1
US-622
3 phase, 4P, 3750 W 6 mH, 18.5 A 10 k at 25°C 10 k at 25°C 10 k at 25°C 50 k at 25°C T3.15 A, AC 250 V 25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C
– 12 –

6. REFRIGERANT R410A

This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
6-1. Safety During Installation/Servicing
As R410As pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusiv e for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusiv e for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or remo ving an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, chec k to
make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks , its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual. Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repairs may result in water leakage, electric shock and fire, etc.
6-2. Refrigerant Piping Installation
6-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol­ored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 6-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 13 –
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4 3/8 1/2 5/8
(2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all con­taminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6­2-6 below .
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly f or thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 6-2-2.
Table 6-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 3/8 1/2 5/8
Reference outer diameter of
copper pipe jointed (mm)
6-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all b urrs and clean the cut surface before installation.
– 14 –
c) Insertion of Flare Nut d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Table 6-2-3 Dimensions related to flare processing for R410A
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen- sion A by using a gauge for size adjustment.
ØD
A
Fig. 6-2-1 Flare processing dimensions
Nominal
diameter
1/4 3/8 1/2 5/8
Nominal
diameter
1/4 3/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R410A clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Table 6-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
Thickness
(mm)
0.8
0.8
Flare tool for
R22 clutch type
0 to 0.5 0 to 0.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5 1/2 5/8
Nominal
diameter
1/4 3/8 1/2 5/8
12.70
15.88
Table 6-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
0.8
1.0
Thickness
(mm)
0.8
0.8
0.8
1.0
0 to 0.5 0 to 0.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
– 15 –
Flare nut
width (mm)
17 22 26 29
Table 6-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4 3/8 1/2 5/8 3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
45˚to 46˚
B A
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.4 19.0 16.0 23
23.3 24.0 19.2 34
D
C
43˚to 45˚
Flare nut
width (mm)
17 22 24 27 36
Fig. 6-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
Table 6-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer diameter
(mm)
Tightening torque
NOTE:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
N•m (kgf•cm)
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 6-2-7 shows reference v alues.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/4 3/8 1/2 5/8
6.35
9.52
12.70
15.88
14 to 18 (140 to 180) 33 to 42 (330 to 420) 50 to 62 (500 to 620) 63 to 77 (630 to 770)
– 16 –
16 (160), 18 (180)
42 (420) 55 (550) 65 (650)
6-3. Tools
6-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
   
  
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench Gauge manifold Charge hose Vacuum pump adapter Electronic balance for
refrigerant charging Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut Evacuating, refrigerant
charge, run check, etc. Vacuum evacuating Refrigerant charge
Refrigerant charge Gas leakage check Refrigerant charge
air conditioner installation
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes Yes
Yes Yes
(Note 2)
R410A
Whether conven­tional equipment can be used
NO GOOD
NO GOOD
NO GOOD NO GOOD
NO GOOD NO GOOD NO GOOD
*(Note 1)
*(Note 1)
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
OK
*(Note 1)
NO GOOD
NO GOOD
OK OK
NO GOOD
OK
NO GOOD
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge , etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (3) Pipe cutter
(4) Reamer (5) Pipe bender (6) Level vial (7) Screwdriver (+, –) (8) Spanner or Monkey wrench
(9) Hole core drill (Ø65)
(10) Hexagon wrench
(Opposite side 4mm) (11) Tape measure (12) Metal saw
Also prepare the following equipments for other installation method and run check.
(1) Clamp meter (2) Thermometer
(3) Insulation resistance tester (4) Electroscope
– 17 –
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps .
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor units gas side.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose of the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
Nev er charge refrigerant exceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 6-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 18 –
(OUTDOOR unit)
Opened
Closed
Service port
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
Electronic
balance
Siphon
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas , the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
Fig. 6-4-2
6-5. Brazing of Pipes
6-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is gener ally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refriger ant pipes.
Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution,
which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
When performing brazing again at time of servicing, use the same type of brazing filler.
6-5-2. Flux
(1) Reason why flux is necessary
By removing the oxide film and an y foreign matter on the metal surface, it assists the flow of brazing filler.
In the brazing process, it prevents the metal surface from being oxidized.
By reducing the brazing filler's surface tension, the brazing filler adheres better to the treated metal.
19
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
(2) Characteristics required for flux
Activated temperature of flux coincides with the brazing temperature.
Due to a wide effective temperature range, flux is hard to carbonize.
It is easy to remove slag after brazing.
The corrosive action to the treated metal and
brazing filler is minimum.
It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid.
It is effective in case where the br azing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type.
It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
6-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder. Use a copper pipe to direct the piping mate-
rial, and attach a flow-meter to the cylinder. Apply a seal onto the clearance between the
piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open. Adjust the flow rate of Nitrogen gas so that it
is lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/ cm²) by means of the reducing valve.
After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
Remove the flux completely after brazing.
(4) Piping materials for brazing and used
brazing filler/flux
Copper - Copper
Copper - Iron
 
Piping
material
Iron - Iron
Do not enter flux into the refrigeration cycle. When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
Remove the flux after brazing.
Used
brazing filler
Phosphor copper
Silver
Silver
Used
flux
Do not use
Paste flux
Vapor flux
Fig. 6-5-1.
Circuit Configuration and Control Specifications
20
7-1. Outdoor Controls
7-1-1. Print Circuit Board
<Viewed from parts of P.C board>
RAV-SM561AT-E, RAV-SM801AT-E
<MCC-5009>
F01, 02, 25A fuse P.C. board earth lead
L-phase power supply lead (Black)
N-phase power supply lead (White)
Serial lead (Orange) Reactor lead connector
(White) CN701:
4-way valve connector
21
RY701: 4-way valve relay
(Black)
C12, 13, 14
C12, 13, 14
electrolytic capacitor
electrolytic capacitor
DB02: High power factor diode
Q404: High power factor circuit IGBT
F03: 3.15A fuse
F03: 3.15A fuse
DB01:
DB01:
Single-phase rectifier diode
Single-phase rectifier diode
7. CONTROL SPECIFICATIONS
CN300: Fan motor connector
CN602: Outdoor temperature (TO) sensor connector
CN806: Optional connector
CN600: Heat exchange temperature (TE) sensor connector
CN603: Suction temperature (TS) sensor connector
CN601: Discharge temperature (TD) sensor connector
CN700: PMV connector
CN500: Case thermo connector
CN605: Sub SW board connector
Fan drive circuit Q300 to Q305: FET (QTY: 6P)
12V12V
GNDGND
IC800: MCU
IC800: MCU
J800 to 803, 806 Model switch jumper line
5V5V
Comp. lead (Red) (White) (Black)
Comp. drive circuit Q200 to Q205: IGBT (QTY: 6P) IC200: Drive IG (QTY: 1P)
RAV-SM1101AT-E, RAV-SM1401AT-E
<IPDU : MCC-1438>
Reactor connector DC15V output
IGBT (Compressor drive device)
Compressor output
22
CN09, CN10, CN11
Rectifier
(To MCC-1531) CN05
Communication signal (To MCC-1531) CN06
AC output (To MCC-1531) CN13
TH sensor CN600
Earth ground CN03
DC320V output (To MCC-1531) CN04
Mains (Neutral) input CN02
Mains (Live) input CN01
Rectifier connectors P29 (Red), P28 (Black), P21 (Orange), P24 (Brown)
Reactor Connector Capacitor
<CDB : MCC-1531>
Refrigerant recovery Switch SW802
Dip switch
EEPROM-IC IC801
Serial signal (To terminal block) CN02
AC input (To MCC-1438) CN01
SW801 P.M.V. CN702
23
4-way valve CN700
Model selection jumpers (Available only service P.C. board) J800 to J803
Case thermo. switch CN500
Communication signal (To MCC-1438) CN800
TD sensor CN600
TO sensor CN601
TE sensor CN604
TS sensor CN605
Optional connector CN804
Fan motor revolution CN300
DC15V input (To MCC-1438) CN04
Fan motor output CN301
DC320V input (To MCC-1438) CN03
7-2. Outline of Main Controls
a b
c
d
e
TD [˚C]
Error stop ("P03" display with 4 times of error counts)
As command is
Frequency down
Frequency holding
Frequency slow-up (Up to command)
1. Pulse Modulating Valve (PMV) control
1) For PMV with 50 to 500 pulses during operation, respectively.
2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor.
3) In heating operation, PMV is controlled with the temperature difference betw een TS sensor and TE sensor.
4) For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and heating operations.
5) When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD sensor. The aimed value is usually 103°C for SM561, SM801 and 92°C for SM1101, SM1401 in both cooling and heating operations.
REQUIREMENT
A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance value an the refrigerating cycle of each sensor after repair and then start the operation.
2. Discharge temperature release control
1) This function controls the operation frequency, that is, lowers the operation frequency when the discharge temperature has not lower or the discharge temperature has rapidly risen during PMV control. It subdivides the frequency control up to a unit of 0.6 Hz to stabilize the cycle.
2) When the discharge temperature is detected in an abnormal stop zone, the unit stops the compressor and restarts after 2 minutes 30 seconds. The error counter is cleared when it has continued the operation for 10 minutes. If the abnormal stop zone has been detected by 4 times without clearing of counter, an error “P03” is displayed.
* The cause is considered as excessively little
amount of refrigerant, defective PMV, or clogging of cycle.
[°C]
abcde
SM561, SM801
SM1101, SM1401
117 107 103 100 93 111 106 100 95 90
3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by T02 on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
Objective model
11 value [A]
SM561
COOL H E AT
10.1 12.0
SM801
COOL H E AT
12.2 14.0
SM1101
COOL HEAT
18.9 19.7
– 24 –
Current [A]
I1
I1–0.5
SM1401
COOL HEAT
19.7 19.7
Frequency down
Hold
Hold
Normal operation
Loading...
+ 53 hidden pages