Note 1 : The cooling capacities and electrical characteristics are measured under the conditions speciied by JIS B 8616 based
on the reference piping. The reference piping consists of 3 m piping connected with 0 meter height.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note: Rated conditionsCooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
– 11 –
Page 12
2. AIR DUCTING WORK
2-1. Static Pressure Characteristics of Each Model
Fig. 1 RAV-SM560BT-E
70% (570m³/h)110% (925m³/h)
Standard air volume : 840m³/h
12
11
Extra High tap
Extra High tap
10
9
8
High tap
High tap
7
6
Middole tap
5
Middle tap
4
External static pressure (mmAq)
3
Low tap
Low tap
2
1
0
5001000
600570
700800900 925
Air volume (m³/hr.)
12
70% (800m³/h)110% (1255m³/h)
11
10
9
8
7
6
5
4
External static pressure (mmAq)
3
2
1
Fig. 2 RAV-SM800BT-E
Standard air volume : 1140m³/h
Extra High tap
Extra High tap
High tap
High tap
Middole tap
Middle tap
Low tap
Low tap
0
7001300
800900100011001200 1255
Air volume (m³/hr.)
– 12 –
Page 13
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
3-1. Indoor Unit
4-Way Air Discharge Cassette Type
RAV-SM560UT-E/RAV-SM800UT-E
Surface
under ceiling
200
113
173
Refrigerant pipe
connecting port A
130
200
Check port
450)
(
Check port
450)
(
Cable draw-in port
45
Refrigerant pipe
connecting port B
Electric
parts box
860 to 910 Recommended external size
30
105
270
25070
950 Panel external dimension
790 Hanging bolt pitch
346.5
860 to 910 Recommended external size
Surface
under ceiling
Hanging bolt M10 or W3/8
Procured locally
130
210
360
Indoor unit
Standing
640 or less
Standing
850 or less
Drain up standing size
256
Surface
under ceiling
88
SM560
SM800
840 Unit external dimension
A
Ø6.4
Ø9.5
150
105
Ø12.7
Ø15.9
Knockout
97
35
Z view
for
humidifier
Ceiling
panel
(Sold
separately)
Surface
under ceiling
80
Ø162
B
415.0
105105
240
254.5
840 Hanging bolt
480
227
12097
Surface under ceiling
381.6
227
480
723 Hanging bolt pitch
950 Panel external dimension
35
64
57
57.5
25
188
Surface under ceiling
120
– 13 –
Page 14
Concealed Duct Type
RAV-SM560BT-E
2-Ø200
Discharge port flange
4-M10
Hanging bolt
(Procured locally)
For hanging bolt M10
(4-12 x 25 long hole)
Drain pipe connecting port
at drain up kit side
(For polyvinyl chloride pipe
(Inner dia. 32, Nominal dia. 25))
750 ± 7.5 Hanging bolt pitch
700 Dimension of main unit
150
160~6405
240
730
210
720
314.5
25
75
800 Dimension of main unit
565 Hanging bolt pitch
780 Ceiling opening size
170
12020
80
60
Drain up kit
(Sold separately)
70252280
457 to 637
Refrigerant pipe
connecting port
(Gas side Ø12.7)
25
305
90 120
Refrigerant pipe
connecting port
(Liquid side Ø6.4)
Drain pipe connecting port
at main unit side
(For polyvinyl chloride pipe
(Inner dia. 32, Nominal dia. 25))
2-Ø26 power supply remote
controller cord draw-out port
80
170
211
509
630
45
35
155 to 335
470 Ceiling opening size
300
13080
30
Panel
450
Ø125 knockout hole (Only rear side)
(For air suction)
6-Ø4 tapping screw lower hole Ø160
100
170
210
70
Suction port canvas
Suction panel
Plane view of main unit
30320
Check port A
450
NOTE 1 :
For maintenance of the equipment, be sure to install
a check port A at the position as shown below.
NOTE 2 :
Using the drain up kit sold separately, drain-up by 300 (mm)
from drain pipe draw-out port of the main unit is necessary.
The drain-up over 300mm or more is impossible.
– 14 –
150
(Pipe side)
Discharge side
Page 15
RAV-SM800BT-E
2-Ø200
Discharge port flange
4-M10
Hanging bolt
(Procured locally)
460~6405
For hanging bolt M10
(4-12 x 25 long hole)
Drain pipe connecting port
at drain up kit side
(For polyvinyl chloride pipe
(Inner dia. 32, Nominal dia. 25))
150
25
1050 Ceiling opening size
75
800 Dimension of main unit
565 Hanging bolt pitch
1050 ± 7.5 Hanging bolt pitch
1000 Dimension of main unit
290
1030
210
720
240
314.5
170
12020
Drain up kit
(Sold separately)
70252290
60
457 to 637
80
Refrigerant pipe
connecting port
(Gas side Ø12.7)
25
305
90 120
Refrigerant pipe
connecting port
(Liquid side Ø6.4)
Drain pipe connecting port
at main unit side
(For polyvinyl chloride pipe
(Inner dia. 32, Nominal dia. 25))
2-Ø26 power supply remote
controller cord draw-out port
80
170
211
45
13080
30
35
Panel
155 to 335
470 Ceiling opening size
450
509
630
300
Plane view of main unit
Ø125 knockout hole (Only rear side)
(For air suction)
100
Suction panel
6-Ø4 tapping screw lower hole Ø160
170
210
70
30320
Suction port canvas
Check port A
450
NOTE 1 :
For maintenance of the equipment, be sure to install
a check port A at the position as shown below.
NOTE 2 :
Using the drain up kit sold separately, drain-up by 300 (mm)
from drain pipe draw-out port of the main unit is necessary.
The drain-up over 300mm or more is impossible.
– 15 –
150
(Pipe side)
Discharge side
Page 16
High-Wall Type
RAV-SM560KRT-E/RAV-SM800KRT-E
298
998
Z
757
51
Pipe port from left
(Knockout hole)
Z views
Discharge port
110390
490
540
20
Pipe port from lower side
(Knockout hole)
998
763.5
450
48
10
Suction port
75 56
Drain hose
Refrigerant pipe connecting port B
Refrigerant pipe connecting port A
20
29
48
Pipe port from right
(Knockout hole)
50
41555555
758
50
SM560
SM800
A
Liquid Side
Ø6.4
Ø9.5
40
B
Gas Side
Ø12.7
Ø15.9
298
40
100100115115
Position of installation plate
55 or more
53 or more53 or more
Space required for service
– 16 –
Page 17
Under Ceiling/Console Type
RAV-SM560XT-E/RAV-SM800XT-E
Front panel
1093
208
633
Knock out system
Grille air inlet
Back body
For stud bolt
(Ø8 – Ø10)
For stud bolt (Ø6)
200 Min
330165
1093
1015
742
450
2020
Ø74
UNDER CEILING & CONSOLE INSTALLATION
– 17 –
Installation plate
Mount plate
M10 Suspention bolt
633
460
70 Min
Wireless remote control
Knock out system
160
5718
Page 18
3-2. Outdoor Unit
RAV-SM560AT-E
49.5
52121
25220
308
302
Ø6 hole pitch
For anchor bolt)
(Long hole pitch
147
Drain hole (Ø25)
83
A legs
150
11
30
76
153
B legs
Discharge guard
(49.3)
598
593
500 (Fan center dividing)
500 (Fan center dividing)
Protective net mounting hole
(2-Ø4 embossing)
Drain hole (2-Ø20 x 88 long hole)
600
115.3 125
30
21
780
115.3
Discharge guide mounting hole
(4-Ø4 embossing)
97
2927031
330
21
31
23
132
90.6
Charge port
216
31134
Valve cover
Earth
terminal
4370730
Protective net mounting hole
(4-Ø4 embossing)
Refrigerant pipe connecting port
(Ø12.7 flare at gas side)
600
52
36
R15
302
30811
Ø11 x 14 U-shape hole
Details of A legsDetails of B legs
2-Ø6 hole
Product
external line
Ø11 x 14 Ushape holes
308
302
11
Refrigerant pipe connecting port
(Ø6.4 flare at liquid side)
Space required for service
2-Ø11 x 14 U-shape holes
(For Ø8–Ø10 anchor bolt)
36
52
2-Ø6 hole
Product
external
line
R15
600
150
or more
365
500
or more
60
475
Suction port
150
or more
Discharge
port
600
300
or more
Discharge
port
(Minimum
distance up to wall)
2-Ø11 x 14 long hole
(For Ø8–Ø10 anchor bolt)
– 18 –
Page 19
RAV-SM800AT-E
Knockout
(For draining)
21
Suction
port
36517.517.5
4070
(Long hole pitch
for anchor bolt)
21
565101
Drain hole (Ø20 x 88 burring hole)
299019120
Suction
port
43
Knockout
(For draining)
6026
Discharge
port
300150
900
314
Drain hole (Ø25 burring hole)
Part B
40
39
Part A
95
43
Handles
(Both sides)
Refrigerant pipe connecting port
(Ø9.5 flare at liquid side)
Refrigerant pipe connecting port
(Ø15.9 flare at gas side)
2
47
Installation bolt hole
(Ø12 x 17 U-shape holes)
17.5
4040
Details of B part
Details of A part
17.5
Installation bolt hole
(Ø12 x 17 U-shape holes)
Discharge guide
mounting hole
(4-Ø4 embossing)
1
60 90
58
27
161
32028
400
264
6760
154
2760
300
Z
307
96
1
Knockout for lower piping
86 7
7
58
Z views
Space required for service
795
2
46
25
85
2
165
60 80
3045
1
2-Ø12 x 17 U-shape holes
(For Ø8–Ø10 anchor bolt)
150
or more
365
500
or more
Suction port
150
or more
Discharge
port
600
150
or more
Discharge
port
(Minimum
distance up to wall)
2-Ø12 x 17 long hole
(For Ø8–Ø10 anchor bolt)
– 19 –
Page 20
4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
Indoor Unit/Outdoor Unit
RAV-SM560UT-E, RAV-SM560BT-E, RAV-SM560KRT-E/RAV-SM560AT-E
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
– 20 –
(70%)
Page 21
Indoor Unit/Outdoor Unit
RAV-SM800UT-E, RAV-SM800BT-E, RAV-SM800KRT-E/RAV-SM800AT-E
Indoor unit
Air heat exchanger
TC sensor
Outer diameter of refrigerant pipe
Gas side ØALiquid side ØB
15.9mm9.5mm
TCJ
sensor
Accumulator
(1500cc)
TS sensor
TD sensor
Muffler
Ø25 × L160
Rotary compressor
(DA220A2F-20L)
Refrigerant pipe
at liquid side
Outer dia. ØB
Pd
Packed valve
Outer dia. ØB
Strainer
4-way valve
(STF-0213Z)
Ø25 × L210
Outdoor unit
TO sensor
TE
sensor
Heat exchangerØ8
1 row 30 stages
FP1.3 flat fin
Refrigerant pipe
at gas side
Outer dia. ØA
Packed valve
Outer dia. ØA
Modulating (PMV)
(SKV-18D26)
Capillary
Ø3ר2×
L530
Max
50m
Ps
Strainer
R410A 1.5 kg
Cooling
Heating
Pressure
(MPa)(kg/cm²G)
PdPsPdPs
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
4 poles are provided to this compressor.
*
3.30.9 33.48.8
3.71.1 37.8 11.4
1.00.8 10.07.9
2.50.6 25.86.3
3.41.1 34.7 11.5
2.00.2 20.32.3
Pipe surface temperature (°C)
DischargeSuction
(TD)(TS)(TC)(TE)
8611944
90211854
19448
676422
85235516
89–1634–18
Indoor heat Outdoor heat
exchanger exchanger
Compressor
revolutions per
second (rps)
*
64
52
27
65
31
90
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor Outdoor
27/1935/–
32/2443/–
18/15.5–5/–
20/–7/6
30.–24/18
15/––20/
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
– 21 –
(70%)
Page 22
5-1. Indoor Unit
4-Way Air Discharge Cassette Type
RAV-SM560UT-E/RAV-SM800UT-E
5. WIRING DIAGRAM
LM1
LM2
FM
5 5
4 4
3 3
2 2
1 1
5 5
4 4
3 3
2 2
1 1
5 5
4 4
3 3
2 2
1 1
FS
CN34
(RED)
3 3
2 2
1 1
CN33
(WHI)
5 5
4 4
3 3
2 2
1 1
CN333
(WHI)
5 5
4 4
3 3
2 2
1 1
CN334
(WHI)
1 1
2 2
3 3
4 4
5 5
CN68
(BLU)
1 2
1 2
CN104
(YEL)
TA
1 2
1 2
CN102
(RED)
TCJ
12
12
CN101
(BLK)
TC
1 2 3
CN80
(GRN)
MCC-1402
Control P.C. Board for
Indoor Unit
Power
supply
circuit
Fuse
F302
T3.15A
250V~
Motor
drive
circuit
Motor
drive
circuit
RY
302
1 2331 2 3
1 2
RY
303
CN304
(GRY)
DP
Fuse
F301
250V~
T6.3A
CN67
(BLK)
RED
1 233
1 2
WHI BLK
DC20V
DC15V
DC12V
DC7V
5
445
RED
WHI
P301
BLK
(EXCT)
1 2
CN73
(RED)
1 2
CN66
(WHI)
Closed-end
connector
12
CN70
(WHI)
5
4
CN620
3
(BLU)
2
1
6
5
CN60
4
(WHI)
3
2
1
CN32
2
(WHI)
1
(FAN DRIVE)
6
5
4
CN61
(YEL)
3
2
1
5
4
CN50
3
(WHI)
2
1
3
CN309
2
(YEL)
1
BLK
3
3
2 2
BLK
1 1
CN41
(BLU)
BLK
WHI
2 2
1 1
CN001
(WHI)
Adapter for
Wireless Remote
Controller
BLK
B
A
WHI
2 2
1 1
CN1
(WHI)
Wired Renote
Controller
FM
TA
TC
TCJ
LM1,LM2
DP
FS
RY302
NOTE
: Fan motor
: Indoor temp. sensor
: Temp. sensor
: Temp. sensor
: Louver motor
: Drain pump motor
: Float switch
: Drain control relay
NL
Single phase
220 to 240V
50Hz
– 22 –
321
321
Serial
signal
Indoor unit
earth screw
Outdoor unit
earth screw
Color
Identification
BLACK
:
BLK
BLUE
:
BLU
RED
:
RED
GRAY
:
GRY
PINK
:
PNK
GREEN
:
GRN
WHITE
:
WHI
BROWN
:
BRW
ORANGE
:
ORN
YELLOW
:
YEL
Page 23
Concealed Duct Type
RAV-SM560BT-E/RAV-SM800BT-E
TA
TCJ
TC
FM
RC
FM
DP
1
1
1
2
RED
3
YEL
4
BLU
5
OPN
6
BLK
7
8
BRW
9
1
2
RED
3
YEL
4
BLU
5
OPN
6
BLK
7
8
BRW
9
(When selecting
high-static pressure)
2
2
3
3
4
4
5
5
6
6
7
7
8
9
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
9
1
2
3
4
5
6
7
1
2
3
4
5
6
7
FS
CN030
(RED)
LM
CN033
(GRN)
CN068
(BLU)
YEL
BLU
ORN
BLK
RED
CN083
(WHI)
3 3
2 2
1 1
3 3
2 2
1 1
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
1 2
1 2
CN104
(YEL)
3
2
1
UL
1
2
L
3
4
M
5
6
H
7
8
9
CN102
(RED)
RY001
RY002
RY007
RY
004
1
CN304
(GRY)
1 2
1 2
2 3
1 2
1 2
CN101
(BLK)
RY006
1 2 3
CN080
(GRN)
RY005
1 2 3
CN309
(YEL)
PNLEXCT
1 2
CN073
(RED)
Fuse
F001
T5A
250V~
1 2 3 4 5
1 2 3 4 5
RED
WHI
BLK
1 2
1 2
CN070
(WHI)
Power
supply
circuit
CN067
(BLK)
RED
WHI
CN060
(WHI)
CN032
(WHI)
CN061
(YEL)
CN066
6
5
4
OPTION
3
2
1
2
1
6
5
4
3
2
1
3 3
2 2
1 1
CN074
(WHI)
6
6
5 5
4 4
3 3
2 2
1 1
CN075
(WHI)
6
5
4
3
2
1
CN050
(WHI)
3 3
2 2
1 1
CN041
(BLU)
1 2
(WHI)
Closed-end
connector
FAN
DRIVE
B
A
TR
2
2
CN1
1
1
Remote
Controller
FM
RC
TR
LM
TA
TC, TCJ
RY001
RY002
RY005~007
DP
NOTE
: Fan motor
: Runing capacitor
: Transformer
: Louver motor
: Indoor temp. sensor
:
Indoor heat exchanger sensor
: Louver control relay
: Drain control relay
: Air volume control relay
: Drain pump motor
Indoor unit
earth screw
– 23 –
Outdoor unit
earth screw
321
321
NL
Color
Identification
BLACK
:
BLK
BLUE
:
BLU
RED
:
RED
GRAY
:
GRY
PINK
:
PNK
GREEN
:
GRN
WHITE
:
WHI
BROWN
:
BRW
ORANGE
:
ORN
YELLOW
:
YEL
Page 24
High-Wall Type
RAV-SM560KRT-E/RAV-SM800KRT-E
Remote Controller
(Option)
ORG
A
A
YEL
B
B
BLU
C
C
Central Centroller
Connection (Option)
1 1
X
2
Y2
CN01
RED
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
Infra-Red Receiver
9 9
10 10
CN25
SUB-CONTROL P.C. BOARD
CN
240
BLK
P02
P03
1 1
2 2
3
3
CN02
WHI
AI-NET
P.C. BOARD
MCC-1337
BLU
1
2
3
4
5
6
7
8
9
10
CN213
WHI
1
2
3
4
5
6
7
8
9
10
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
WHI
1
CN01
122
BLK
TR
CN12
1 1
2 2
1
1
1
1
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
10
10
11 11
12 12
13 13
14 14
15 15
16 16
CN02
WHI
2
2
2
2
CN63
WHI
CN64
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
CN31
WHI
6
6
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3344556
CN62
CN16
WHI
CN61
WHI
BLU
1
2
1
2
3344556
1
2
MCC-1370A
1
12233
Control P.C. Board for
Indoor Unit
F201
T3,15A
250V~
Indoor unit
GRN&YEL
RED
CN230
WHI
CN231
BLK
CN223
CN11
WHI
2 2
1 1
CN207
WHI
BLU
6 6
PNK
5 5
YEL
4 4
OPG
3 3
RED
2 2
BRN
1 1
BLU
6 6
YEL
5 5
WHI
4 4
BLK
3 3
2 2
RED
1 1
CN210
WHI
1
2
3
4
CN14
5
WHI
6
7
8
Outdoor unit
(1 Phase model)
F2
1
1
2
2
3
3
LM
FM
Earth
Screw
L
Power Supply
220/240 50Hz
N
Serial Signal
NOTE
: Fuse (PCB)
F
: Fan motor
FM
: Louver motor
LM
: Temperature sensor
TA
: Temperature sensor
TC
: Temperature sensor
TCJ
: Transformer
TR
: Outdoor
O/D
: Remote Contoller
R/C
2
2
BLK
TA
1
1
BLK
CN04
WHI
2
2
BLK
TC
D05
D02
D13
D11
1
1
BLK
CN05
WHI
Orange
Green
Orange
Green
2
2
BLK
TCJ
1
1
BLK
CN20
YEL
CN13
WHI
234
LED Detall
O/D Serial Signal Input
O/D Serial Signal Output
R/C Serial Signal Input
R/C Serial Signal Output
– 24 –
1
1
2
1
2
CN50
WHI
GRY
PNK
CN06
WHI
121
23456
CN21
WHI
Chack Code
04
08
09
0C
0d
0F
11
12
97
98
99
Diagnosis
Serial Signal Error
4-Way Valve Error
I/D Heart Exchange Error
TA Sensor Error
TC Sensor Error
TCJ Sensor Error
Indoor Fan Error
Indoor unit Error
LAN Comms Circuit Error
LAN Adress Setting
R/C Mis-Wiring
Page 25
RAV-SM560XT-E/RAV-SM800XT-E
SWITCH PCB
MCC-1428B
2
LOUVER
MOTOR
WHI
10
10
BLU
9
9
BLU
8
8
BLU
7
7
BLU
6
6
BLU
5
5
BLU
4
4
BLU
3
3
BLU
2
2
BLU
1
1
AND INDICATION PARTS
CN25
INFRARED RAYS RECEIVE
BRW
RED
ORN
YEL
PNK
BLU
10
9
8
7
6
5
4
3
2
1
CN13
1
2
3
4
5
CN07
CN101
CN100
10
9
8
7
6
5
4
3
2
1
1
2
3
4
5
66
R507
R09
R22
SG01
4
5
IC04
213
WHI
GRY
213
21
250VAC
GRY
3
DB01
FUSE
F01
T6.3A
FOR FLOAT SWITCH
(OPTION)
When you use float
switch you should cut J401
CN402
POWER
SUPPLY
CIRCUIT
C02
R01
C01
C15
R21
3
EXCHANGER
SENSOR
21
J401
DC12V
DC5V
CR502
RY501
MCC-1428A
R405
RY401
HEAT
(TCJ)
CN05
IC03
CR501
C501
CR401
21
21
CN03
21
2
121
2
121
CN01
R506
1
1
2
2
3
3
4
4
5
5
CN10
3
3
2
2
1
1
CN11
3
FOR DRAIN PUMP
2
1
CN401
BLK
BLK
BLK
BLK
WHI
RED
BLK
BRW
GRY
YEL
(OPTION)
1
1
2
2
3
3
4
4
5
5
66
3
3
2
2
1
1
THERMO
SENSOR
(TA)
HEAT
EXCHANGER
SENSOR
(TC)
WHI
RED
BLK
BLU
PUR
GRY
FAN-MOTOR
100”C
Check items
OPERATION
1
indicator
Terminal
2
block
Fuse
3
6.3A
DC 5V
4
DC 12V
5
BLK
P04
CN30
2
BLK
CN31
WHI
21
RED
INDOOR
TERMINAL
3
BLOCK
CN23
GRN&YEL
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS
Diagnosis result
Check to see if OPERATION indicator goes on and off when the main switch
or breaker is turned on.
Check the power supply voltage between 1 - 2 (Refer to the name plate.)
Chack the fluctuate voltage between 2 - 3 (DC15 to 60V)
Check to see if the fuse blows out. (Check the varistor. : R22, R21)
Check the voltage at the No.8 pin on CN13 connector of the infrared receiver.
(Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the brown lead of the louver motor.
(Check the transformer and the power supply circuit of the rated voltage.)
INDOOR
UNIT
OUTDOOR
UNIT
Identification
BRW
RED
GRY
PNK
ORN
GRN&YEL
GRN
PUR
Color
WHI
YEL
BLU
BLK
BROWN
:
RED
:
WHITE
:
YELLOW
:
BLUE
:
BLACK
:
GRAY
:
PINK
:
ORANGE
:
GREEN&
:
YELLOW
GREEN
:
PURPLE
:
– 25 –
Page 26
5-2. Outdoor Unit
RAV-SM560AT-E
Q200
BLU
P17 P18
P21
P22
P23
RED
WHI
BLK
4
2 1
2331
CM
COMPRESSOR
CN301
IGBT MODULE
BZBYBXEWBWEVBVEUBU
P.C. BOARD
(MCC-813)
5
5
GRY
4 3
PNK
2 1
YEL
3
3
BLK
2 1
2 1
WHI
RED
2 1
4 3
FM
FAN MOTOR
Q300
CN300
BRW
P19P20
P14
PUR
REACTOR
DB01
CONVERTER
MODULE
~
~
–
+
ELECTRONIC
STARTER
–
–
–
F04
FUSE
T3. 15A
250V~
P13
P12
2 1
2 1
+
+
+
P11
GEA
C12
C13
C14
2
REACTOR
P10
POWER
RELAY
3
P02
WHI
1
TO
INDOOR
UNIT
ORN
FUSE
T25A
250V~
2
2 1
2 1
P09
P08P07
CT
VARISTOR
F01
P03
P01
ORN
BLK
3
L
N
POWER
SUPPLY
220 to 240
50Hz
RELAY
THERMOSTAT
FOR
COMPRESSOR
CN500
2 1
2 1
CN600
CN601
CN602
CN603
CN701
P06
SURGE
ABSORBER
2
WHITE (S)
1
TE
11
22
TD
11
22
33
TO
11
22
TS
11
22
33
11
22
33
COIL FOR
11
22
33
44
55
66
BLK
YEL
RED
ORN
RED
GRY
4-WAY VALVE
PMV
PULSE
MODULATING
VALVE
BLACK (C)
RED (R)
BLK
CN703
TERMINAL OF COMPRESSOR
The sign in ( ) is displayed
in the terminalcover
Check
items
1
2
3
4
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS
Diagnosis result
TERMINAL BLOCK
There is no supply voltage
(AC220 to 240V) between L - N , 1 - 2
There is no voltage (DC15 to 25V) 2 - 3
FUSE
T25A 250V to fuse (F01) blown
T3.15A 250V to fuse (F04) blown
ELECTROLYTIC CAPACITOR VOLTAGE (C12, C13, C14)
DC320V not available between
+ – terminal of electrolytic capacitor
INVERTER OUTPUT (Inverter and compressor connector out of position)
(Please confirm within six minutes after instructing in the drive.)
Voltage between each line of inverter side
conector pins are not equal.
Power supply and connecting
cable check
Converter module (DB01) and
electrolytic capacitor (C12 to C14) check
IGBT module (Q200) check
Fan motor check
ELECTROLYTIC CAPACITOR VOLTAGE (C10, C11, C12, C13)
DC320V not available between
+ terminal of electrolytic capacitor
INVERTER OUTPUT (CN09, CN10, CN11)
(Please confirm within six minutes after instructing in the drive.)
Voltage between each line of inverterside
conector pins are not equal.
Connecting cable check
Converter module (DB01) and electrolytic
capacitor (C10 to C13) check IGBT
module (Q200) check, Fan motor check
SUB P.C. board check
4-Way Air Discharge Cassette Type
RAV-SM560UT-E/RAV-SM800UT-E
No.
1
Fan motor (for indoor)
2
Thermo. sensor (TA-sensor)
3
Heat exchanger sensor (TCJ-sensor)
4
Heat exchanger sensor (TC-sensor)
5
Float switch
6
Drain pump motor
Parts name
Concealed Duct Type
RAV-SM560BT-E/RAV-SM800BT-E
No.
1
Fan motor (RAV-SM800BT-E)
2
Fan motor (RAV-SM560BT-E)
3
Capacitor (RAV-SM800BT-E)
4
Capacitor (RAV-SM560BT-E)
5
Thermo. sensor (TA-sensor)
Parts name
Type
SWF-230-60-1
155 mm
Ø6 mm, 1200 mm
Ø6 mm, 1200 mm
FS-0218-106
ADP-1406
Type
STF-230-80-4C
STF-220-80-4C
EAG40M805UF1
CMPS400-4.0
818 mm
Specifications
Output (Rated) 60 W, 220–240 V
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
Specifications
Output (Rated) 80 W, 220–240 V, 4P
Output (Rated) 80 W, 220–240 V, 4P
400WV, 5µF
400WV, 4.0µF
10 kΩ at 25°C
6
Heat exchanger sensor (TC-sensor)
7
Heat exchanger sensor (TCJ-sensor)
High-Wall Type
RAV-SM560KRT-E/RAV-SM800KRT-E
No.
1
Fan motor (for indoor)
2
Grille motor
3
Thermo. sensor (TA-sensor)
4
Heat exchanger sensor (TC-sensor)
5
Heat exchanger sensor (TCJ-sensor)
Parts name
RAV-SM560XT-E/RAV-SM800XT-E
No.
1
Fan motor (for indoor)
2
Grille motor
Parts name
Ø6 mm, 1200 mm
Ø6 mm, 1200 mm
Type
ICF340-30-1
MP35EA12
268 mm
Ø6 mm, 400 mm
Ø6 mm, 400 mm
Type
AFP-220-50-4A
MP35EA
10 kΩ at 25°C
10 kΩ at 25°C
Specifications
Output (Rated) 30 W, 220–240 V
10 kΩ at 25°C
10 kΩ at 25°C
Specifications
Output (Rated) 50 W, 220–240 V
DC 12 V
3
Thermo. sensor (TA-sensor)
4
Heat exchanger sensor (TC-sensor)
5
Heat exchanger sensor (TCJ-sensor)
mm
Ø6 mm, mm
Ø6 mm, mm
– 28 –
10 kΩ at 25°C
10 kΩ at 25°C
Page 29
6-2. Outdoor Unit
RAV-SM560AT-E
No.
1
Fan motor
2
Compressor
3
Reactor
4
Outdoor temp. sensor (To-sensor)
5
Heat exchanger sensor (Te-sensor)
6
Suction temp. sensor (Ts-sensor)
7
Discharge temp. sensor (Td-sensor)
8
Fuse (Switching power (Protect))
9
Fuse (Inverter, input (Current protect)
10
4-way valve solenoid coil
11
Compressor thermo. (Protection)
RAV-SM800AT-E
No.
1
Fan motor
Parts name
Parts name
Type
ICF-140-43-1
DA130A1F-23F
CH-57
—
—
—
—
STF-0108G
US-622
Type
ICF-140-63-1
Specifications
Output (Rated) 40 W
3 phase, 4P, 1100 W
1=10 mH, 16A
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
T3.15 A, AC 250 V
25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C
Specifications
Output (Rated) 63 W, 220–240 V
2
Compressor
3
Reactor
4
Outdoor temp. sensor (To-sensor)
5
Heat exchanger sensor (Te-sensor)
6
Suction temp. sensor (Ts-sensor)
7
Discharge temp. sensor (Td-sensor)
8
Fuse (Switching power (Protect))
9
Fuse (Inverter, input (Current protect))
10
4-way valve solenoid coil
11
Compressor thermo. (Protection)
6-3. Accessory Separate Sold Parts
RBC-U21PG (W) E (Ceiling panel)
No.
1
2
Motor-louver
Parts name
DA220A2F-20L
CH-47
—
—
—
—
DKV-M0ZS743B0
Type
MP24GA
3 phase, 4P, 1600 W
mH, A
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
T3.15 A, AC 250 V
25 A, AC 250 V
ON : 90 ± 5°C, OFF : 125 ± 4°C
Specifications
DC 12 V
TCB-DP11E (Drain up pump)
No.
1
2
Pump-drain
Parts name
Type
PJD-05230TF-1
– 29 –
Specifications
AC 220–240 V
Page 30
7. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
7-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc.
by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive for the refrigerant
R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the
refrigeration cycle. Otherwise, pressure in the
refrigeration cycle may become abnormally high
so that a rupture or personal injury may be
caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentration
does not exceed the marginal level.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal level, an
oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair’s may result in water leakage,
electric shock and fire, etc.
7-2. Refrigerant Piping Installation
7-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant must be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
As an air conditioner using R410A incurs
pressure higher than when using R22, it is
necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 7-2-1. Never use copper
pipes thinner than 0.8 mm even when it is
available on the market.
– 30 –
Page 31
Table 7-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4
3/8
1/2
5/8
(2) Joints
For copper pipes, flare joints or socket joints are
used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes
cannot be used for pipings whose outer
diameter exceeds 20 mm. In such a case,
socket joints can be used.
Sizes of flare pipe ends, flare joint ends and
flare nuts are as shown in Tables 7-2-3 to 72-6 below.
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410AR22
0.800.80
0.800.80
0.800.80
1.001.00
b) Socket Joints
Socket joints are such that they are brazed
for connections, and used mainly for thick
pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in
Table 7-2-2.
Table 7-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
7-2-2. Processing of Piping Materials
When performing the refrigerant piping installation,
care should be taken to ensure that water or dust
does not enter the pipe interior, that no other oil
other than lubricating oils used in the installed air
conditioner is used, and that refrigerant does not
leak. When using lubricating oils in the piping
processing, use such lubricating oils whose water
content has been removed. When stored, be sure to
seal the container with an airtight cap or any other
cover.
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe
so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs,
refrigerant leakage may occur. Carefully
remove all burrs and clean the cut surface
before installation.
– 31 –
Page 32
c) Insertion of Flare Nut
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perform the flare
processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Table 7-2-3 Dimensions related to flare processing for R410A
Flare processing dimensions differ according
to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
ØD
A
Fig. 7-2-1 Flare processing dimensions
Nominal
diameter
1/4
3/8
1/2
5/8
Nominal
diameter
1/4
3/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R410A clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Table 7-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
Thickness
(mm)
0.8
0.8
Flare tool for
R22 clutch type
0 to 0.5
0 to 0.5
A (mm)
Conventional flare tool
Clutch typeWing nut type
1.0 to 1.51.5 to 2.0
1.0 to 1.51.5 to 2.0
1.0 to 1.52.0 to 2.5
1.0 to 1.52.0 to 2.5
A (mm)
Conventional flare tool
Clutch typeWing nut type
0.5 to 1.01.0 to 1.5
0.5 to 1.01.0 to 1.5
1/2
5/8
Nominal
diameter
1/4
3/8
1/2
5/8
12.70
15.88
Table 7-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15,88
0.8
1.0
Thickness
(mm)
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0.5 to 1.01.5 to 2.0
0.5 to 1.01.5 to 2.0
Dimension (mm)
ABCD
9.1 9.2 6.513
13.213.5 9.720
16.616.012.923
19.719.016.025
– 32 –
Flare nut
width (mm)
17
22
26
29
Page 33
Table 7-2-6 Flare and flare nut dimensions for R22
NominalOuter diameterThickness
diameter(mm)(mm)
1/4 6.350.8
3/8 9.520.8
1/212.700.8
5/815.881.0
3/419.051.0
to 46
45
BA
Dimension (mm)
ABCD
9.0 9.2 6.513
13.013.5 9.720
16.216.012.920
19.419.016.023
23.324.019.234
D
C
43 to 45
Flare nut width
(mm)
17
22
24
27
36
Fig. 7-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening
torque for R410A is the same as that for
conventional R22. Incidentally, when the
torque is weak, the gas leakage may occur.
Table 7-2-7 Tightening torque of flare for R410A [Reference values]
NominalOuter diameterTightening torque
diameter(mm)N•m (kgf•cm)
When it is strong, the flare nut may crack and
may be made non-removable. When choosing
the tightening torque, comply with values
designated by manufacturers. Table 7-2-7
shows reference values.
NOTE:
When applying oil to the flare surface, be sure to use
oil designated by the manufacturer. If any other oil is
used, the lubricating oils may deteriorate and cause
the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/46.3514 to 18 (140 to 180)
3/8 9.5233 to 42 (330 to 420)
1/212.7050 to 62 (500 to 620)
5/815.8863 to 77 (630 to 770)
– 33 –
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
Page 34
7-3. Tools
7-3-1. Required Tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to
prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and
opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
(3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
Conventional air
conditioner installation
Whether new equipment
can be used with
conventional refrigerant
¡
(Note 1)
*
X
X
¡
¡
X
¡
X
No.Used tool
Flare tool
Copper pipe gauge for
adjusting projection
margin
Torque wrench
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for
refrigerant charging
Refrigerant cylinder
Leakage detector
Charging cylinder
Usage
Pipe flaring
Flaring by conventional
flare tool
Connection of flare nut
Evacuating, refrigerant
charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge
Gas leakage check
Refrigerant charge
air conditioner installation
Existence ofWhether convennew equipmenttional equipment
for R410Acan be used
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
Ye s
(Note 2)
R410A
(Note 1)
*
(Note 1)
*
X
X
X
X
X
X
X
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary
as the general tools.
(Opposite side 4mm)
(11) Tape measure
(12) Metal saw
Also prepare the following equipments for other installation method and run check.
(1) Clamp meter
(2) Thermometer
(3) Insulation resistance tester
(4) Electroscope
– 34 –
Page 35
7-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Connect the charge hose of the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
Never charge refrigerant exceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 7-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 35 –
(OUTDOOR unit)
Opened
Closed
Service port
Page 36
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ][ Cylinder without siphon ]
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Gauge manifold
OUTDOOR unit
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the
characteristics of the equipment varies.
7-5. Brazing of Pipes
7-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper. It is used to join iron,
copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
Fig. 7-4-2
7-5-2. Flux
(1) Reason why flux is necessary
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas
leakage. Therefore, use any other type of
brazing filler at a hot spring resort, etc., and
coat the surface with a paint.
When performing brazing again at time of
servicing, use the same type of brazing filler.
• By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler.
• In the brazing process, it prevents the metal
surface from being oxidized.
• By reducing the brazing filler's surface tension,
the brazing filler adheres better to the treated
metal.
– 36 –
Page 37
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen
gas
Rubber plug
(2) Characteristics required for flux
• Activated temperature of flux coincides with
the brazing temperature.
• Due to a wide effective temperature range, flux
is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric
acid.
It is effective in case where the brazing temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing
are this type.
It features an increased oxide film removing
capability due to the addition of compounds
such as potassium fluoride, potassium chloride
and sodium fluoride to the borax-boric acid
compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
7-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prevent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
Use a copper pipe to direct the piping mate-
rial, and attach a flow-meter to the cylinder.
Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open.
Adjust the flow rate of Nitrogen gas so that it
is lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/
cm²) by means of the reducing valve.
After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools
down to a certain extent (temperature at
which pipes are touchable with hands).
Remove the flux completely after brazing.
Copper - Copper
Copper - Iron
Piping
material
Iron - Iron
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain
chlorine.
When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange water).
Remove the flux after brazing.
Used brazing
filler
Phosphor copper
Silver
Silver
Used
flux
Do not use
Paste flux
Vapor flux
Fig. 7-5-1 Prevention of oxidation during brazing
– 37 –
Page 38
8. CONTROL BLOCK DIAGRAM
8-1. Indoor Control Circuit
Max. 8 units are connectable.*1
*1 Max. 7 units when network adapters
are attached
*2 Network adapters are attached to only
one unit.
*3 Weekly timer is not connectable to the
sub remote controller.
Central control
remote controller
(Option)
Indoor unit
#1
Network adapter (Option)
X
Y
Network adapter
P.C. board
(MCC-1401)
AI NET
communication
circuit
DC5V
Power circuit
Transformer
Remote
controller
communication
circuit
CPU
H8/3687
Switch setup
Louver
motor
Drain
pump
Indoor
fan
motor
Indoor control P.C. board (MCC-1402)
DC280V
Main (Sub) master remote controller
Display
LCD
CPU
Remote
controller
communication
circuit
Humidifier
relay output
Heater relay
output
control
circuit
Outside
output
Run
Warning
Ready
Thermo. ON
Cool
Heat
Fan
Function setup
Key switch
DC5V
Power circuit
Driver
Power
circuit
Display
LED
DC20V
DC12V
DC5V
CPU
TMP88CH
47FG
(TMP88PH
47FG)
Fan motor
Weekly timer
DC5V
Secondary
LCD
driver
CPU
battery
#2
AB
Same as
the left
*
123
Function setup
Key switch
#3
AB
Same as
the left
2
*
123
Display
LCD
CN2 CN1
3
*
Powe r
circuit
OptionOption
AB
Serial
send/
receive
circuit
EEPROM
TA sensor
TC sensor
TCJ sensor
Float input
Remote
controller
communication
circuit
CPU
H8/3039
AC
synchronous
signal input
circuit
2
123
123
Outdoor unit
Optional only for 4-way air
discharge cassette type models
– 38 –
communication
Powe r
circuit
DC5V
Buzzer
Receive circuit
Wireless remote controller kit
Sensor P.C. board (MCC-1418)
Remote
controller
circuit
CPU
Temporary
operation SW
Display LED
Function
setup SW
Outdoor
unit
Outdoor
unit
Page 39
8-2. Control Specifications
No.
1
When power
supply is reset
2
Operation mode
selection
Item
Outline of specifications
1) Distinction of outdoor units
When the power supply is reset, the outdoors are
distinguished, and control is exchanged according to
the distinguished result.
2) Setting of speed of the indoor fan/setting whether to
adjust air direction or not.
(Only 4-way models)
Based on EEPROM data, speed of the indoor fan or
setting whether to adjust air direction or not is selected.
1) Based on the operation mode selecting command
from the remote controller, the operation mode is
selected.
Remote controller
command
STOP
FAN
COOL
DRY
HEAT
AUTO
Ta
( C)
+1.5
Tsc
or Tsh
-1.5
COOL
Outline of control
Air conditioner stops.
Fan operation
Cooling operation
Dry operation
Heating operation
• COOL/HEAT operation mode
is automatically selected by Ta
and Ts for operation.
(COOL ON)
(COOL OFF)
HEAT
Remarks
Air speed/
Air direction adjustment
Ta : Room temperature
Ts : Setup temperature
Tsc : Setup temperature in
cooling operation
Tsh : Setup temperature
+ Room temperature
control temperature
compensation
1) Judge the selection of COOL/HEAT mode as shown
in the figure above.
When 10 minutes passed after thermostat had
been turned off, the heating operation (Thermo
OFF) is exchanged to cooling operation if Tsh
exceeds +1.5 or more.
(COOL OFF) and (COOL ON) in the figure indicate
an example.
When 10 minutes passed after thermostat had
been turned off, the cooling operation (Thermo
OFF) is exchanged to heating operation if Tsc
exceeds –1.5 or less.
2) For the automatic capacity control after judgment of
COOL/HEAT, refer to item 4.
3) For the temperature correction of room temperature
control in automatic heating operation, refer to item 3.
– 39 –
Page 40
No.
3
Item
Room
temperature
control
Outline of specifications
1) Adjustment range Remote controller setup temperature (°C)
COOL/
DRY
Wired type
Wireless type
: Only for 4-way air discharge cassette type
*
*
18 to 29
18 to 30
Heating
operation
18 to 29
16 to 30
Auto
operation
18 to 29
17 to 27
2) Using the item code 06, the setup temperature in
heating operation can be compensated.
Remarks
Shift of suction temperature in heating operation
Automatic
4
capacity control
(GA control)
5
selection
Setup data
Setup temp.
compensation
0246
+0°C+2°C+4°C+6°C
Setting at shipment
Setup data2
1) Based on the difference between Ta and Ts, the
operation frequency is instructed to the outdoor unit.
1) Operation with (HH), (H), (L), or [AUTO] mode is
performed by the command from the remote controller.
2) When the air speed mode [AUTO] is selected, the air
speed varies by the difference between Ta and Ts.
<COOL>
Ta ( C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
-0.5
HH
(HH)
H (HH)
H (HH)
L(H)
L(H)
L(H)
L(L)
A
B
C
D
E
F
G
HH > H > L > LLAir speed
• Controlling operation in case when thermo of remote
controller works is same as a case when thermo of
the body works.
• If the air speed has been changed once, it is not
changed for 3 minutes. However when the air volume
is exchanged, the air speed changes.
• When cooling operation has started, the air speed
selects a downward slope, that is, the high position.
• If the temperature is just on the difference boundary,
the air speed does not change.
• Mode in the parentheses indicates one in automatic
cooling operation.
– 40 –
Page 41
No.
5
Item
Air speed
selection
(Continued)
Outline of specifications
<HEAT>
Ta ( C)
L(L)
(-0.5)
(0)
(+0.5)
–1.0
Tsh
+1.0
L(H)
H(H)
H
E
D
(HH)
(+1.0)
(+1.5)
(+2.0)
+2.0
+3.0
+4.0
HH
(HH)
C
B
A
Value in the parentheses indicates one when thermostat of
the remote controller works.
Value without parentheses indicates one when thermostat
of the body works.
• If the air speed has been changed once, it is not
changed for 1 minute. However when the air speed is
exchanged, the air speed changes.
• When heating operation has started, the air speed
selects a upward slope, that is, the high position.
• If the temperature is just on the difference boundary, the
air speed does not change.
• Mode in the parentheses indicates one in automatic
heating operation.
• In Tc ≥ 60°C, the air speed increases by 1 step.
3) In heating operation, the mode changes to [UL] if
thermostat is turned off.
4) If Ta ≥ 25°C when heating operation has started and
when defrost operation has been cleared, it operates
with HIGH (H) mode or (HH) for 1 minute from when Tc
has entered in E zone of cool air discharge preventive
control (Item 6).
5) In automatic cooling/heating operation, the revolution
frequency of [HH] is set larger than that in the standard
cooling/heating operation. However the revolution
frequency is restricted in the automatic heating operation as shown in the following figure.
Tc: Indoor heat exchanger
sensor temperature
[PRE-HEAT] display
Tc
( C)
47
42
F5 F4
F5
– 41 –
Page 42
No.
6
Item
Cool air
discharge
preventive
control
Outline of specifications
1) In heating operation, the indoor fan is controlled based
on the detected temperature of Tc sensor or Tcj sensor.
As shown below, the
upper limit of the
revolution frequency
is determined.
Tc
Tcj
( C)
32
30
28
26
20
16
HH
UL
OFF
H
L
E zone
D zone
C zone
B zone
A zone
Remarks
In D or E zone, the priority
is given to setup of air
volume exchange.
In A and B zones,
[PRE-HEAT] is displayed.
78Freeze preven-
tive control
(Low temperature release)
1) The cooling operation (including Dry operation) is
performed as follows based on the detected temperature of Tc sensor or Tcj sensor.
When [J] zone is detected for 6 minutes (Following
figure), the commanded frequency is decreased from
the real operation frequency. After then the commanded
frequency changes every 30 seconds while operation is
performed in [J] zone.
In [K] zone, time counting is interrupted and the operation is held.
When [I] zone is detected, the timer is cleared and the
operation returns to the normal operation.
If the commanded frequency becomes S0 because the
operation continues in [J] zone, the return temperature
A is raised from 5°C to 12°C until [I] zone is detected
and the indoor fan
operates with [M] mode.
( C)
5
I
2
J
In heating operation, the freeze-preventive control
works if 4-way valve is not exchanged and the condition
is satisfied. (However the temperature for J zone
dashing control is changed from 2°C to –5°C.)
Tcj : Indoor heat ex-
changer sensor
temperature
A
K
High-temp
release control
1) The heating operation is performed as follows based on
the detected temperature of Tc sensor or Tcj sensor.
• When [M] zone is detected, the commanded fre-
quency is decreased from the real operation frequency. After then the commanded frequency
changes every 30 seconds while operation is performed in [M] zone.
• In [N] zone, the commanded frequency is held.
• When [L] zone is detected, the commanded fre-
quency is returned to the original value by approx.
6Hz every 60 seconds.
Setup at
shipment
Control temp (°C)
AB
56 (54)52 (52)
Tcj
( C)Tc
A
B
L
M
N
NOTE :
When the operation has started or when Tc or Tcj became
lower than 30°C after start of the operation, temperature is
controlled between values in parentheses of A and B.
– 42 –
Same when thermostat is
turned off.
Page 43
No.
9
Drain pump control
(For the duct, when
the drain-up kit
(sold separately) is
mounted)
Item
Outline of specifications
1) In cooling operation (including Dry operation), the
drain pump is usually operated.
2) If the float switch operates while drain pump
operates, the compressor stops, the drain pump
continues the operation, and a check code is
output.
3) If the float switch operates while drain pump stops,
the compressor stops and the drain pump operates. If the float switch keeps operating for approx.
4 minutes, a check code is output.
Remarks
Check code [P10]
1011After-heat elimina-
tion
Flap control
(For 4-way air
discharge cassette
type only)
When heating operation stops, the indoor fan operates
with LOW mode for approx. 30 seconds.
1) Flap position setup
• When the flap position is changed, the position
moves necessarily to downward discharge
position once to return to the set position.
• The flap position can be set up in the following
operation range.
In cooling/dry operation In heating/fan operation
• In group twin/triple operation, the flap positions
can be set up collectively or individually.
2) Swing setup
• The swinging position can be moved in the
following operation range.
All modes
• In group twin/triple operation, the swinging
positions can be set up collectively or individually.
3) When the unit stops or when a warning is output,
the flap automatically moves downward.
4) While the heating operation is ready, the flap
automatically moves upward.
– 43 –
Warning :
A check code is displayed
on the remote controller,
and the indoor unit stops.
(Excluding [F08] and
[L31])
Page 44
No.
12
Frequency fixed
operation
(Test run)
Item
Outline of specifications
<In case of wired remote controller>
1. When pushing [CHECK] button for 4 seconds or more,
[TEST] is displayed on the display screen and the
mode enters in Test run mode.
2. Push [ON/OFF] button.
3. Using [MODE] button, change the mode from [COOL]
to [HEAT].
• Do not use other mode than [COOL]/[HEAT] mode.
• During test run operation, the temperature cannot be
adjusted.
• An error is detected as usual.
• A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the
operation. (Display in the display part is same as the
procedure in item 1).)
5. Push [CHECK] button to clear the test run mode.
([TEST] display in the display part disappears and the
status returns to the normal stop status.)
<In case of wireless remote controller>
(Option for 4-way air discharge cassette type only)
1. Turn off the power of the set.
Remove the adjuster with sensors from the ceiling
panel.
2. Turn Bit [1: TEST] of sensor P.C. board switch [S003]
from OFF to ON.
Attach the sensor P.C. board cover and mount the
adjuster with sensors to the ceiling panel.
Turn on the power of the set.
3. Push [ON/OFF] button of the wireless remote controller
and set the operation mode to [COOL] or [HEAT] using
[MODE] button.
(During test run operation, all the display lamps of
wireless remote controller sensors flash.)
• Do not use other mode than [COOL]/[HEAT] mode.
• An error is detected as usual.
• A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the
operation.
5. Turn off the power of the set.
Turn Bit [1: TEST] of sensor P.C. board switch [S003]
from ON to OFF.
Mount the adjuster with sensors to the ceiling panel.
Remarks
13 Filter sign display
(Except wireless
type)
1) The operation time of the indoor fan is calculated, the
filter reset signal is sent to the remote controller when
the specified time (2500H) has passed, and it is
displayed on LCD.
2) When the filter reset signal has been received from the
remote controller, time of the calculation timer is
cleared. In this case, the measurement time is reset if
the specified time has passed, and display on LCD
disappears.
– 44 –
[FILTER] goes on.
Page 45
No.
14
Central control
mode selection
15
Energy-save
control
(By connected
outdoor unit)
Item
Outline of specifications
1) Setting at the central controller side enables to select
the contents which can be operated on the remote
controller at indoor unit side.
2) RBC-AMT21
[Last push priority] :
The operation contents can be selected from both
remote controller and central controller of the indoor
unit side, and the operation is performed with the
contents selected at the last.
[Center] :
Start/Stop operation only can be handled on the
remote controller at indoor unit side.
[Operation Prohibited] :
It cannot be operated on the remote controller at
indoor unit side. (Stop status is held.)
1) Selecting [AUTO] mode enables an energy-saving to
be operated.
2) The setup temperature is shifted (corrected) in the
range not to lose the comfort ability according to input
values of various sensors.
3) Data (Input value room temp. Ta, Outside temp. To, Air
volume, Indoor heat exchanger sensor temp. Tc) for
20 minutes are taken the average to calculate
correction value of the setup temperature.
4) The setup temperature is shifted every 20 minutes,
and the shifted range is as follows.
In cooling time : +1.5 to –1.0K
In heating time : –1.5 to +1.0K
Remarks
(No display)
[CENTER] goes on.
[CENTER] goes on.
In a case of wireless type, the
display lamp does not change.
However, contents which can be
operated are same.
The status set in [CENTER]/
[Operation Prohibited] mode is
notified with the receiving sound
“Pi, Pi, Pi, Pi, Pi” (5 times).
16
Max. frequency
cut control
17
DC motor
(For 4-way air
discharge
cassette type
only)
1) This control is operated by selecting [AUTO] operation mode.
2) COOL operation mode: the frequency is controlled
according to
the following
figure if
To < 28°C.
Ta ( C)
+4
+3
Tsc
Normal control
Max. frequency is restricted
to approximately the rated
cooling frequency
3) HEAT operation mode: the frequency is controlled
according to
the right
figure if
To > 15°C.
Ta ( C)
Tsh
–3
–4
Normal control
Max. frequency is restricted
to approximately the rated
heating frequency
1) When the fan operation has started, positioning of the
stator and the rotor are performed.
(Moves slightly with tap sound)
2) The motor operates according to the command from
the indoor controller.
NOTES :
• When the fan rotates while the air conditioner stops
due to entering of outside air, etc, the air conditioner
may operated while the fan motor stops.
• When a fan locking is found, the air conditioner stops,
and an error is displayed.
Check code [P12]
– 45 –
Page 46
8-3. Indoor Print Circuit Board
4-Way Air Discharge Cassette Type
RAV-SM560UT-E/RAV-SM800UT-E
<MCC-1402>
– 46 –
DC fan return
Float SW
DC fan output
Microcomputer operation LED
EEPROM
Network adapter
power supply
Indoor/Outdoor
inter-unit cable
Drain pump output
Louver
Optional output
TA sensor
CHK
DISP
EXCT
TCJ sensor
TC sensor
Outside error input
Remote controller power LED
Remote controller inter-unit cable
Page 47
Concealed Duct Type
RAV-SM560BT-E/RAV-SM800BT-E
<MCC-1403>
– 47 –
Power transformer output
Louver
Drain pump
output
Indoor/Outdoor inter-unit cable
Power transformer input (AC11V,14V,20V)
Microcomputer operation LED
Remote controller
power LED
HA
Optional output
Network adapter
power supply
Fan output
EXCT
Float SW
TA sensor
TCJ sensor
Outside error input
TCsensor
Remote controller
inter-unit cable
CHK
DISP
Page 48
9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
9-1. Microcomputer System Block Diagram
9-1-1. Connection of Main Remote Controller
Main (Sub) master remote controller
Indoor unit
#1
Sensor display P.C. board
(MCC-819)
SensorsLED
Remote controller
No. setupTwin/
Triple setup
Sub P.C. board
(MCC-1370B)
Louver
motor
Indoor
fan
motor
Transformer
DC310~340V
Display
LCD
Display
LED
Power circuit
Optional
output
Comp.
Run
Error
Heat
Indoor fan
control circuit
DC15V
Power
circuit
Driver
DC
12V
DC
5V
synchronous
signal input
CPU
TMP47C
820F
AC
synchronous
signal input
circuit
ABC
ABC
Serial send/
receive circuit
CPU
TMP87CM
40AN
(TMP87PM
40AN)
AC
circuit
Communication P.C. board (Option)
123
123
EEPROM
Function setup
Key switch
Serial send/
receive circuit
Main P.C. board (MCC-1370A)
EEPROM
TA shift setup
Model selection
Function setup
TA sensor
TC sensor
TCJ sensor
Serial
send/
receive
circuit
Communication
LSI
MCC-1337
Pulse
trans
XY
The P.C. boards of the indoor unit are
classified into 4 boards according to the
function.
1. Main P.C. board (MCC-1370A)
Controller for power circuit, fan motor
driver, and whole unit
2. Sub P.C. board (MCC-1370B)
Setup of unit No. and concurrent twin
* The sub P.C. board is located near the
remote controller terminal block.
3. Sensor display P.C. board (MCC-819)
Wireless remote controller receive part,
LED display part
4. Communication P.C. board (MCC-1337)
Communication part with the central
control remote controller (Option)
Max. 16 units are connectable.
#2
Same as
BC
the left
123
#3
Same as
123
BC
the left
Outdoor unit
– 48 –
Outdoor
unit
Outdoor
unit
Page 49
9-1-2. Connection of Wireless Remote Controller
Indoor unit
#1
Infrared radiation
Sensors
LED
Sensor display
P.C. board
Remote controller
No. setupTwin/
Triple setup
Sub P.C. board(MCC-1370B)
Louver
motor
Indoor
fan
motor
Transformer
Optional
output
Comp.
Run
Error
Heat
Indoor fan
control circuit
DC15V
Power
circuit
Driver
DC
12V
DC
5V
synchronous
signal input
AC
circuit
Main P.C. board (MCC-1370A)
EEPROM
TA shift setup
Model selection
Function setup
CPU
TA sensor
TMP87CM
TC sensor
40AN
(TMP87PM
TCJ sensor
40AN)
Serial
send/
receive
circuit
DC310~340V
Outdoor unit
– 49 –
123
123
Communication
LSI
MCC-1337
Communication P.C. board (Option)
Pulse
trans
XY
Page 50
9-1-3. Control Specifications
No.
1
When power
supply is reset
2
Operation mode
selection
Item
Outline of specifications
1) Distinction of outdoor units
When the power supply is reset, the outdoors are
distinguished, and control is exchanged according to
the distinguished result.
2) Setting of the indoor fan speed
Based on EEPROM data, rspeed of the indoor fan is
selected.
1) Based on the operation mode selecting command
from the remote controller, the operation mode is
selected.
Remote controller
command
STOP
FAN
COOL
DRY
HEAT
AUTO
1) Judge the selection of COOL/HEAT mode as shown in the
figure below.
When the heating operation (Thermo OFF) is exchanged
to cooling operation if Tsh exceeds +3 or more.
(COOL OFF) and (COOL ON) in the figure indicate an
example.
When the cooling operation (Thermo OFF) is exchanged
to heating operation if Tsc exceeds -3 or less.
2) For the automatic capacity control after judgment of
COOL/HEAT, refer to item 4.
3) For the temperature correction of room temperature control
in automatic heating operation, refer to item 3.
Outline of control
Air conditioner stops.
Fan operation
Cooling operation
Dry operation
Heating operation
Ta
( C)
or Tsh
+3
Tsc
COOL
–3
(COOL OFF)
(COOL ON)
Heating
Remarks
Air speed
Ta : Room temperature
Ts : Setup temperature
Tsc : Setup temperature
in cooling operation
Tsh : Setup temperature
in heating operation
3
Room temperature control
1) Adjustment range Remote controller setup temperature (°C)
Standard type
Wireless type
Remote controller
setup temp
Setup temp (°C)
COOL/
DRY
18 to 29
17 to 30
▼5 ▼4 ▼3 ▼2 ▼1
1920212223
Heating
operation
18 to 29
17 to 30
Auto
operation
18 to 29
19 to 29
Standard24▲1 ▲2 ▲3 ▲4 ▲5
2) Differential 1K (=deg)
3) In heating operation, the setup temperature can be
corrected by using Dip switch (SW03) on the indoor
P.C. board.
SW03
Setup temp correction
1
2
ONONOFFOFF
ONOFFONOFF
+0°C+2°C+4°C+6°C
– 50 –
Max. setup temperature
Ts (Max) = 35°C
2526272829
Setup at shipment
SW03
12
ONOFF
Page 51
No.
4
Automatic
capacity control
Item
Outline of specifications
1) Based on the difference between Ta and Ts, the
operation frequency is instructed to the outdoor unit.
Remarks
(GA control)
NOTE :
In cooling operation :
When calculating the following conditions for 29 minutes,
the commanded frequency is assumed as the rated
cooling frequency.
Ta < 28°C
1
2
Indoor fan [High]
3
32°C < To ≤ 38°C or no To
4
Operation exceeding the rated cooling frequency
In heating operation: When calculating the following
conditions for 29 minutes, the commanded frequency is
assumed as the rated heating frequency.
Ta ≥ 19°C
1
2
Indoor fan [High]
3
5°C < To ≤ 10°C or no To
4
Operation exceeding the rated heating frequency
5
Tc ≥ 38°C
NOTE :
When air volume is set to [L], the maximum frequency is
restricted.
Tc : Temperature of indoor
heat exchanger
sensor
5
Air volume
control
1) Operation with [HIGH (H)], [MED (M)], [LOW (L)], or
[AUTO] mode is performed by the command from the
remote controller.
2) When the air volume mode [AUTO] is selected, the air
volume varies by the difference between Ta and Ts.
3) In heating operation, the mode changes to [Ultra
Low (UL)] or [STOP] if thermostat is turned off.
4) If Ta ≥ 25°C when heating operation has started and
when defrost operation has been cleared, it operates with MED mode or higher mode for 1 minute
from when Tc has entered in A zone of cool air
discharge preventive control (Item 6).
5) In automatic cooling/heating operation, the revolution frequency of [HIGH (H)] is set larger than that in
the standard cooling/heating operation. However the
revolution frequency is restricted in the automatic
heating operation as shown in the following figure.
Tc
( C)
47
42
F5 F4
F4
6) (For wireless type only) The mode enters [AUTO] in
automatic cooling/heating operation.
7) The mode enters [LOW (L)] during Dry operation
“Stop” is a “cool air
discharge preventive
control” operation by Tc.
Tc: Indoor heat exchanger
sensor temp.
Display: [AUTO]
6
Cool air discharge
preventive control
1) In heating operation, the indoor fan is controlled
based on the detected temperature of Tc sensor.
As shown below, the upper limit of the revolution
frequency is determined.
Tc( C)
30
26
20
16
A zone : Setup air volume
A
B zone : Low air
C zone : OFF
BC
from remote
controller
– 52 –
Display in C zone
Display of main unit:
Defrost LED goes on.
When wired remote
controller is installed:
PRE-HEAT/DEFROST
goes on remote controller.
Page 53
No.
7
Freeze preventive
control
(Low temperature
release)
Item
Outline of specifications
1) The cooling operation (including Dry operation) is
performed as follows based on the detected temperature of Tc sensor or Tcj sensor.
When [J] zone is detected for T1 minutes (Following
figure), the commanded frequency is decreased
from the real operation frequency. After then the
commanded frequency changes every 30 seconds
while operation is performed in [J] zone.
T1
Normal
Twin
6 minutes
6 minutes
In [K] zone, time counting is interrupted and the
operation is held.
When [I] zone is detected, the timer is cleared and
the operation returns to the normal operation.
If the commanded frequency becomes S0 because
the operation continues in [J] zone, the return
temperature A is raised from 5°C to 12°C until [I]
zone is detected and the indoor fan operates with [L]
mode.
( C)
5
I
A
K
Remarks
Tcj : Indoor heat
exchanger sensor
temperature
8
High-temp release
control
2
J
In heating operation, the freeze-preventive control
works if 4-way valve is not exchanged and the
condition is satisfied.
1) The heating operation is performed as follows based
on the detected temperature of Tc sensor.
• When [M] zone is detected, the commanded
frequency is decreased from the real operation
frequency. After then the commanded frequency
changes every 30 seconds while operation is
performed in [M] zone.
• In [N] zone, the commanded frequency is held.
• When [L] zone is detected, the commanded
frequency is returned to the original value by
approx. 6Hz every 60 seconds.
Setup at shipment
Control temp (°C)
AB
56 (54)52 (52)
Tc ( C)
A
B
M
N
L
NOTE :
When the operation has started or when Tc became
lower than 30°C after start of the operation, temperature is controlled between values in parentheses of A
and B.
– 53 –
Same when thermostat is
turned off.
Page 54
No.
9
Louver control
1) Louver
Item
position
Outline of specifications
The louver angle is displayed
setting 0° as “Full close”.
Remarks
Full close
2) Air direction
adjustment
(Swing
operation)
1) In the initial operation after
0
power-ON, the position is
automatically controlled according to the operating
status (COOL/HEAT).
CoolingHeating
45 103
2) After then a louver position is stored in the microcomputer every time when position is operated on the
remote controller, and the louver operates at the position
stored in memory in the next operation and after.
* If the operation mode has been changed from COOL
to HEAT, from HEAT to COOL, or the power has
turned off, the stored louver position is cleared and
the status returns to one in item 1).
1) When pushing [LOUVER] button during operation, the
louver starts swinging.
2) When the louver has arrived at the desired position, push
[LOUVER] again. The louver stops at that position.
10
Frequency fixed
operation
(Test run)
1) In case of wired remote controller
1. When pushing [ON/OFF] button on the remote
controller continuously for 5 seconds, the mode
enters [TEST]. The indoor fan rotates with [HIGH]
and a frequency fixed operation starts.
2. During this operation, the buttons other than [ON/
OFF], [UP △] and [DOWN ▽] cannot be accepted.
However, items 7 and 8 are effective.
3. To stop the frequency fixed operation, use [ON/OFF]
button only.
2) In case of wireless remote controller (Without wired
remote controller)
1. When pushing [Temporary] button continuously for
10 seconds or more, “Pi” sound is heard and the
mode enters [TEST]. The indoor fan rotates with
[HIGH] and a frequency fixed operation of [COOL]
starts.
NOTES :
• Temporary button is provided to near the display part of
the main unit when opening the front panel.
• If [Temporary] button is not continuously pushed for 10
seconds, “Automatic heating/cooling operation” is
performed.
2. To stop the operation, push [Temporary] button again.
NOTE :
Operation on the wireless remote controller is not accepted.
[COOL]/[HEAT] flash.
Air volume: [AUTO]
Temperature
COOL: [L]
HEAT: [H]
Commanded frequency
Approximately [S7]
– 54 –
Page 55
No.
11
Filter sign display
Item
Outline of specifications
1) The operation time of the indoor fan is calculated, the filter
lamp (Orange) on the display part of the main unit goes on
when the specified time (240H) has passed. When a wired
remote controller is connected, the filter reset signal is sent to
the remote controller, and also it is displayed on LCD of the
wired remote controller.
2) When the filter reset signal has been received from the wired
remote controller after [FILTER] lamp has gone on or when
the filter check button (Temporary button) is pushed, time of
the calculation timer is cleared. In this case, the measurement
time is reset if the specified time has passed, and display on
LCD and the display on the main unit disappear.
Remarks
[FILTER] goes
on.
12
Central control
mode selection
Setup on central
control remote
controller
Last push priority
Center
Operation prohibited
NOTE : When a wired remote controller is connected, there is no display on the main unit.
Energy-save
13
control
(By connected
outdoor unit)
1) Setting at the central remote controller side enables to select the contents which
can be operated on the remote controller at indoor unit side.
2) Operation contents on the remote controller at indoor unit side
[Last push priority] :
The operation contents can be selected from both remote controller and the
central controller of the indoor unit side, and the operation is performed with the
contents selected at the last.
[Center] :
Start/Stop operation only can be handled on the remote controller at indoor unit
side.
[Operation Prohibited] :
It cannot be operated on the remote controller at indoor unit side.
(Stop status is held.)
3) Display on the display part of the main unit or wired remote controller
Display on wired remote
controller
(In case of RBC-AM1)
[Central control] goes off.
[Central control] goes on.
[Central control] flashes.
Display on wired
remote controller
(In case of RBC-AM1)
[Center] goes off.
[Center] goes on.
[Center] flashes.
Display on main unit
(Only in case of no wired remote
controller)
No display
1) Selecting [AUTO] mode enables an energy-saving to be operated.
2) The setup temperature is shifted (corrected) in the range not to lose the comfort
ability according to input values of various sensors.
3) Data (Input value room temp. Ta, Outside temp. To, Air volume, Indoor heat
exchanger sensor temp. Tc) for 20 minutes are taken the average to calculate
correction value of the setup temperature.
4) The setup temperature is shifted every 20 minutes, and the shifted range is as
follows.In cooling time : +1.5 to –1.0K
In heating time : –1.5 to +1.0K
14
Max. frequency
cut control
1) This control is operated by selecting
[AUTO] operation mode.
2) COOL operation mode: the frequency is controlled according to the
following figure if To < 28°C.
3) HEAT operation mode: the frequency
is controlled according to the right
figure if To > 15°C.
– 55 –
Ta ( C)
+4
+3
Tsc
Ta ( C)
Tsh
-3
-4
Normal control
Max. frequency is restricted
to approximately the rated
cooling frequency
Max. frequency is restricted
to approximately the rated
heating frequency
Normal control
Page 56
9-2. Indoor Control Circuit
9-2-1. Print Circuit Board
<Main P.C. board (MCC-1370A)>
<Sub P.C. board (MCC-1370B)>
– 56 –
Page 57
9-2-2. Outline of Main Controls
1. Pulse Modulating Valve (PMV) control
1) For PMV, SM560 is controlled with 45 to 500 pulses and SM800 with 50 to 500 pulses during operation,
respectively.
2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC
sensor.
3) In heating operation, PMV is controlled with the temperature difference between TS sensor and TE
sensor.
4) For the temperature difference in items 2) and 3), 1 to 5K is aimed as the target in both cooling and
heating operations.
5) When the cycle excessively rose in both cooling and heating operations, PMV is controlled by TD sensor.
The aimed value is usually 105°C for SM560 and 100°C for SM800 in both cooling and heating operations.
REQUIREMENT
A sensor trouble may cause a liquid back-flow or abnormal overheat resulting in excessive shortening of the
compressor life. In a case of trouble on the compressor, be sure to check there is no error in the resistance
value an the refrigerating cycle of each sensor after repair and then start the operation.
2. Discharge temperature release control
1) This function controls the operation frequency,
that is, lowers the operation frequency when
the discharge temperature has not lower or
the discharge temperature has rapidly risen
during PMV control. It subdivides the frequency control up to a unit of 0.6Hz to stabilize the cycle.
2) When the discharge temperature is detected
in an abnormal stop zone, the unit stops the
compressor and restarts after 2 minutes 30
seconds. The error counter is cleared when it
has continued the operation for 10 minutes.
If the abnormal stop zone has been detected
by 4 times without clearing of counter, an
error ‘P03’ is displayed.
* The cause is considered as excessively little
amount of refrigerant, defective PMV, or
clogging of cycle.
[°C]
TD [ C]
Error stop ("P03" display with 4 times of error counts)
a
Frequency down
b
c
Frequency holding
d
Frequency slow-up
(Up to command)
e
As command is
abcde
SM560
SM800
11711210810598
1111061009590
3. Current release control
The output frequency and the output voltage are
controlled by AC current value detected by T02
on the outdoor P.C. board so that input current of
the inverter does not exceed the specified value.
ON when operation mode is in cooling system
(COOL, DRY, COOL in AUTO cooling/heating)
ON when operation mode is in heating system
(HEAT, HEAT in AUTO cooling/heating)
ON during indoor fan ON
(Air purifier is used/Interlock cable)
(When continued for 1 minute)
Check code “L30” is output and forced operation stops.
Option error input is controlled. (Protective operation
for device attached to outside is displayed.)
CHK
Operation check
DISP display
mode
EXCT demand
CN71
CN72
CN73
2
0V
1
Check mode input
2
0V
1
Display mode input
2
0V
1
Demand input
2
0V
* Setting of option error input is performed from
remote controller. (DN=2A)
Used for operation check of indoor unit. (Communication with outdoor unit or remote controller is not
performed, but the specified operation such as indoor
fan “H” or drain pump ON is output.)
Display mode enables indoor unit and remote controller to communicate. (When power is turned on)
Forced thermo-OFF operation in indoor unit
– 58 –
Page 59
MCC-1398 (RAV-SM560AT-E)
<Viewed from parts of P.C board>
9-3. Outdoor Controls
9-3-1. Print Circuit Board
5V power supplyMCUGND
– 59 –
IGB module
12V power supply
PMV output
TD sensor
TS sensor
TE sensor
TO sensor
Case thermo
Outdoor fan rpm input
Outdoor fan output
4-way valve output
(Except cooling only models)
Converter module
Page 60
MCC-813 (RAV-SM800AT-E)
Pump down switch
– 60 –
4-way valve
output
12V power supply
PMV output
Case thermo
Contactor against
night low-noise
5V power supply
TD sensor
TO sensor
TE sensor
TS sensor
Communication
between CDB and IPDU
Existing pipe
corresponding switch
(SW 801)
GND
MCU
Outdoor fan output
Status display LED
Page 61
9-3-2. Outline of Main Controls
1. Outdoor fan control (Object: SM80)
Allocautions of fan tap revolutions [rpm]
W1W2W3W4W5W6W7W8W9WAWBWCWDWE
SM800
1) Cooling fan control
The outdoor fan is controlled by TE sensor.
Q
(Cooling: Temperature conditions after medium
term)
The cooling fan is controlled by every 1 tap of DC
fan control (14 taps).
At the activation time, although the maximum fan
R
tap in the following table are fixed for 60 seconds,
after then the fan may not rotate with high speed
for several minutes because the fan is controlled
by TE sensor value. It is not an abnormal status.
When the discharge temperature sensor is
S
abnormal or the sensor comes off the holder, the
fan does not rotate with high speed, but a protective device works.
When the outdoor fan does not rotate with high
T
speed, judge a fan error by comparing the control
data in the following table with TO and TE values.
250270290310340370400440480520560610700780
TE [ C]
MAX.
46
+30 rpm / 20 sec.
37
Hold zone
34
–30 rpm / 20 sec.
20
MIN.
Control for fan tap by outdoor temperature in normal operation
TO
MIN
MAX
2) Heating fan control
Q
R
S
T
TO < 5°C5 ≤ TO <10°C 10 ≤ TO < 15°C 15 ≤ TO < 20°C 20 ≤ TO < 25°C25°C ≤ TOTO error
W1W2W3W4W5WAW1
W6W8WAWCWEWEWE
This control function lowers fan tap according to
TE sensor value when outdoor temperature is
high.
When a status TE > 20°C is detected continuously for 5 minutes, the operation may stop. This
status does not output an error code and is
assumed as usual status of thermo-OFF. The fan
restarts after approx. 2 minutes 30 seconds and
this intermittent operation is not a trouble.
If the status in item R is frequently found, it is
considered that the filter of suction part of the
indoor unit is dirty. Clean the filter and restart the
operation.
This control function does not work for 30 minutes after activation, 1 minute after defrosting,
and during defrost operation.
TE [ C]
–60 rpm / 20 sec. STOP timer count
24
–60 rpm / 20 sec.
21
–30 rpm / 20 sec.
17
Hold zone
15
+30 rpm / 20 sec.
– 61 –
Page 62
2. Outdoor fan control (Object: SM560)
The outdoor fan is controlled by TO sensor and the revolutions frequency of the compressor (rps).
The outdoor fan is controlled by every 1 tap of DC fan control (8 taps). According to each operation mode,
the fan is operated by selecting an outdoor fan operation tap in the following table based upon the conditions
of TO sensor and the compressor operation (rps).
Allocations of fan tap revolutions
F1F2F3F4F5F6F7F8
960870870870750700540390
SM560
Tap
Revolutions per
minute (rpm)
In cooling operationIn heating operation
Frequency of the
compressor (rps)
TO ≥ 38°C
TO < 38°C
To 14To 1435 to MAX
F7F4F3
F7F5F4
Frequency of the
compressor (rps)
TO ≥ 5.5°C
TO < 5.5°C
To 14To 1435 to MAX
F7F6F4
F6F6F3
3. Coil heating control
1) This control function heats the compressor by turning on the stopped compressor instead of a case
heater. It purposes to prevent slackness of the refrigerant inside of the compressor.
2) As usual, turn on power of the compressor for the specified time before a test run after installation,
otherwise a trouble of the compressor may be caused. As same as a test run, it is recommended to turn
on power of the compressor beforehand when starting operation after power of the compressor has been
interrupted for a long time.
3) A judgment for electricity is performed by TD and TO sensors. If TO sensor is defective, a backup control
is automatically performed by TE sensor. For a case of defective TO sensor, judge it with the outdoor LED
display.
4) Coil heating is controlled by TD and TE sensor.
5) For every model, the power is turned off when TD is 30°C or more.
Power-ON condition
TD < 30 C
* TD sensor is read in once per 15 minutes.
(In trouble of sensor)
TO [ C]TO [ C]
18
15
10
No power-ON
Continuous ON (L)
8
Continuous ON (M)
20
18
12
10
(Object: SM560)
TO [ C]
10
No power-ON
9
4
Continuous ON (L)
3
2
Continuous ON (M)
1
Continuous ON (H)
No power-ON
Continuous ON (L)
Continuous ON (M)
L
20W and equivalent
M
40W and equivalent
L
10W and equivalent
M
20W and equivalent
H
30W and equivalent
SM800
SM560
– 62 –
Page 63
NOTIFICATION
It is not an abnormal phenomenon that electro-noise may be heard while heating the coil.
4. Short intermittent operation preventive control
The compressor may not stop for preventing the compressor for 3 to 10 minutes after start of the
Q
operation even if Thermo-OFF signal has been received from the indoor. This phenomenon is not
abnormal. (Continuous operation time of the compressor differs according to the operating status.)
If the equipment is stopped from the remote controller, the operation does not continue.
R
5. High-voltage suppression TE control (Only for SM800)
This control suppresses that voltage becomes abnormally higher during cooling operation.
Q
Stop the compressor under condition of TE ≥ 67°C, and count 1 on the error count.
R
After 2 minutes 30 seconds passed, if TE < 67°C, the compressor restarts and the error count is
S
cleared when the operation continues for 10 minutes.
When TE ≥ 67°C is detected again within 10 minutes, 1 is added to the error count and restart is
T
repeated.
If the error counts 10 are recognized, it is determined as an error and restart is not performed. Error
U
code ‘P04’ is displayed.
After restarting the compressor, continue controlling by using 70% to 90% of the control value of the
V
current release control for minimum 30 minutes.
6. Over-current preventive control
This control function stops the compressor when over-current preventive circuit has detected an
Q
abnormal current.
The compressor restarts with error count 1 after 2 minutes 30 seconds.
R
If the error counts 4 are recognized, it is determined as an error and restart is not performed. Error
S
code ‘H01’, ‘H02’ or ‘P26’ is displayed.
7. Current release value shift control
1) Object: SM800
This control function prevents troubles of the electron parts such as G-Tr of inverter of compressor
Q
drive system and troubles of the compressor during cooling operation.
This control function corrects the current release control value ( 1) in item 3 of 9-2-2 by TO sensor
R
value.
The value to be corrected is based upon the following control diagram and correction value table.
S
TO [ C]
T+8
T+7
T+5
T+4
T+2
T+1
T
T- 1
2) Object: SM560
The current release value of a single-phase model is selected from the right table according to TO sensor value.
I1 x a%
I1 x b%
I1 x c%
I1 x d%
As I1
Corrected value
SM800
Current release value shift control
45 ≤ TO
40 ≤ TO < 45
Tabcd
39°C40°C60°C80°C85°C
TO
TO < 45
SM560
7.07
7.90
10.22
– 63 –
Page 64
8. Defrost control
In heating operation, defrost operation is performed when TE sensor temperature satisfies any
Q
condition in A zone to D zone.
The defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or
R
it also is finished when condition of 7°C ≤ TE < 12°C has continued for 1 minute. The defrost operation
is also finished when defrost operation has continued for 10 minutes even if TE sensor temperature
has become 7°C or lower.
After defrost operation has finished, the compressor and the outdoor fan start heating operation after
S
stopped for approx. 50 seconds.
Start of heating operation
TE [ºC]
01015cbad[min]
–5
A zone
A zone
–10
–13
B zone
B zone
–18
C zone
*
C zone
D zone
D zone
* The minimum TE value between 10 and 15 minutes after heating operation has started is stored in memory as TE0.
A zone
B zone
C zone
D zone
a
b
c
d
T
Defrost operation is performed in this zone when TE0-TE ≥ 3 continued for T seconds.
Defrost operation is performed in this zone when TE0-TE ≥ 3 continued for T seconds.
Defrost operation is performed when this zone continued for T seconds.
Defrost operation is performed when this zone continued for T seconds.
SM560
28
28
28
60
120
SM800
34
40
55
90
120
– 64 –
Page 65
10. TROUBLESHOOTING
10-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
1) Required tools/instruments
+ and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch
•
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
The following operations are normal.
Q
a) Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Does not thermostat turn off?
• Does not timer operate during fan operation?
• Is not outside high-temperature operation controlled in heating operation?
b) Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
c) Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
d) ON/OFF operation cannot be performed from remote controller.
• Is not the control operation performed from outside/remote side?
• Is not automatic address being set up?
(When the power is turned on at the first time or when indoor unit address setting is changed, the
operation cannot be performed for maximum approx. 5 minutes after power-ON.)
Did you return the cabling to the initial positions?
R
Are connecting cables of indoor unit and remote controller correct?
S
(2) Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble
NOTE :
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to
outer noise is considered except the items to be checked. If there is any noise source, change the cables
of the remote controller to shield cables.
→→
→ Confirmation of check code display
→→
→→
→ Check defective position and parts.
→→
– 65 –
Page 66
<Wireless remote controller type> (Only for 4-way air discharge cassette type models)
1. Before troubleshooting
1) Required tools/instruments
+ and – screwdrivers, spanners, radio cutting pliers, nippers, etc.
•
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
The following operations are normal.
Q
a) Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Does not thermostat turn off?
• Does not timer operate during fan operation?
• Is not outside high-temperature operation controlled in heating operation?
b) Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
3) Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
4) ON/OFF operation cannot be performed from remote controller.
• Is not forced operation performed?
• Is not the control operation performed from outside/remote side?
• Is not automatic address being set up?
Did you return the cabling to the initial positions?
Q
Are connecting cables between indoor unit and receiving unit correct?
R
2. Troubleshooting procedure
(When the power is turned on at the first time or when indoor unit address setting is changed, the operation
cannot be performed for maximum approx. 5 minutes after power-ON.)
When a trouble occurred, check the parts along with the following procedure.
Trouble
Confirmation of lamp display
→→
→
→→
(When 4-way air discharge cassette type wireless remote controller is connected)
Check defective
→→
→
→→
position and parts.
1) Outline of judgment
The primary judgment to check where a trouble occurred in indoor unit or outdoor unit is performed with
the following method.
Method to judge the erroneous position by flashing indication on the display part of indoor unit
(sensors of the receiving unit)
The indoor unit monitors operating status of the air conditioner, and the blocked contents of self-diagnosis
are displayed restricted to the following cases if a protective circuit works.
– 66 –
Page 67
10-2. Check Code List
Error mode detected by indoor unit
Wireless sensor
lamp display
Operation
– 67 –
Timer Ready
◎●●
●●◎
◎●●
◎●◎
◎●◎
◎●◎
◎●◎
◎○◎
●◎◎
●◎◎
●◎◎
◎●◎
◎●◎
◎◎●
◎◎●
◎◎●
◎◎●
◎●●
◎●●
Wired remote
controller
Check code
E03
E04
E08
L03
L07
L08
L09
L30
P01
P10
P12
P19
P31
F01
F02
F10
F29
E10
E18
Cause of operation
No communication from remote controller (including wireless)
and communication adapters
The serial signal is not output from outdoor unit to indoor unit.
• Miscabling of inter-unit cables
• Defective serial sensing circuit on outdoor P.C. board
• Defective serial receiving circuit on indoor P.C. board
Duplicated indoor unit addresses
Duplicated indoor master units
There is group line in individual indoor units.
Unsetting of indoor group address
Unset indoor capacity
Abnormal outside interlock input
Fan motor thermal protection
Float switch operation
• Disconnection, coming-off, defective float switch contactor
of float circuit
Indoor DC fan error
Error in 4-way valve system
• Indoor heat exchanger temperature lowered after start of
heating operation.
Own unit stops while warning is output to other indoor units.
Coming-off, disconnection or short of indoor heat exchanger
sensor (TCJ)
Coming-off, disconnection or short of indoor heat exchanger
sensor (TC)
Coming-off, disconnection or short of indoor heat exchanger
sensor (TA)
Indoor EEPROM error
• EEPROM access error
Communication error between indoor MCU
• Communication error between fan driving MCU and main
MCU
Regular communication error between master and sub indoor
units or between main and sub indoor units
Diagnostic function
Status of air
conditioner
Stop
(Automatic reset)
S top
(Automatic reset)
Stop
Stop
Stop
Stop
Stop
Stop
Stop
(Automatic reset)
Stop (Sub unit)
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(Automatic reset)
Condition
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Judgment and measures
1. Check cables of remote controller and communication adapters.
• Handy remote controller LCD display OFF (Disconnection)
• Central remote controller [97] check code
1. Outdoor unit does not completely operate.
• Inter-unit cable check, correction of miscabling, case thermo operation
2. In normal operation
P.C. board (Indoor receiving/Outdoor sending) check
1. Check whether there is modification of remote controller connection (Group/
Individual) or not after power has been turned on (finish of group configuration/
address check).
* If group configuration and address are not normal when the power has been turned
on, the mode automatically shifts to address setup mode. (Resetting of address)
1. Set the indoor capacity. (DN=I1)
1. Check outside devices.
2. Check indoor P.C. board.
1. Check thermal relay of fan motor.
2. Check indoor P.C. board.
1. Defect of drain pump
2. Clogging of drain pump
3. Check float switch.
4. Check indoor P.C. board.
1. Defective detection of position
2. Over-current protective circuit of indoor fan driving unit operates.
3. Lock of indoor fan
4. Check indoor P.C. board.
1. Check 4-way valve.
2. Check indoor heat exchanger (TC/TCJ) sensor.
3. Check indoor P.C. board.
1. Judge sub unit while master unit is in [E03], [L03], [L07], [L08].
2. Check indoor P.C. board.
1. Check indoor heat exchanger temperature sensor (TCJ).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temperature sensor (TC).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temperature sensor (TA).
1. Check there are multiple master units for 2 remote controllers
(including wireless).
: Master unit is one and others are sub units.
1. Check address setup of central control system network.
(Network adapter SW01)
2. Check network adapter P.C. board.
1. Check multiple network adapters.
2. Check inter-unit cable/miscabling of remote controller.
: Only one network adapter on remote controller communication line
1. Check communication line/miscabling. Check power of indoor unit.
2. Check communication. (XY terminals)
3. Check network adapter P.C. board.
4. Check central controller (such as central control remote controller, etc.).
Check the check code of corresponding unit by handy remote controller.
*2 Check code is not displayed by wired remote controller. (Usual operation of air conditioner is disabled.)
For wireless type models, E01 is notified by the display lamp.
*3 These errors are related to communication of remote controllers (A, B) and central system (AI-NET, X, Y), and [E01], [E02], [E03], [E09], or [E18] is displayed or no check code is displayed on the
remote controller according to the error contents.
Page 70
10-3. Error Mode Detected by LED on Outdoor P.C. Board
<SW800: LED display in bit 1, bit 2, bit 3 OFF>
• When multiple errors are detected, the latest error is displayed.
• When LED display is ○ (Go on), there is the main cause of trouble on the objective part of control at CDB
side and the unit stops.
• When LED display is ◎ (Flash), there is the main cause of trouble on the objective part of control at IPDU
side and the unit stops.
• When case thermostat operates, the communication is interrupted on the serial circuit. If continuing the case
thermostat operation, a serial communication error occurs because serial sending to the indoor unit is interrupted.
CDB side
IPDU side
No.
1
TE sensor error
2
TD sensor error
3
TS sensor error
4
TO sensor error
5
Discharge temp. error
6
DC outdoor fan error
Communication error
7
between IPDU
(Abnormal stop)
High-pressure release
8
operation
9
EEPROM error
Communication error
10
between IPDU
(No abnormal stop)
G-Tr short-circuit
11
protection
12
Detection circuit error
13
Current sensor error
14
Phase missing detection
15
Comp. lock error
16
Comp. breakdown
Item
Check code
Type AType B
F0618
F0419
F0618
F081B
P031E
P221A
L291C
21
P04
—
——
——
P2614
P2916
H0317
H0317
H021D
H011F
LED display
D800D801D802D803
(Red)(Yellow)(Yellow)(Yellow)
○●●●
○○●●
●●○●
●○●●
●○○●
○○○●
○●●○
●○●○
○○●○
●●○○
◎●●●
●◎●●
◎◎●●
●●●◎
●●◎●
◎●◎●
○ : Go on ● : Go off ◎ : Flash (5Hz)
<<Check code>>
The check codes are classified into Type A and Type B according to the used remote controller. Be sure to
check the remote controller which you use.
Type A :
Neutral 2-cores type wired remote controller such as RBC-AMT21E, RBC-AS21E, and wireless remote controller kit such as TCB-AX21U (W)-E
Type B :
Polarized 3-cores type wired remote controller such as RBC-SR1-PE, RBC-SR2-PE, and central control remote
controller such as RBC-CR64-PE
– 70 –
Page 71
10-4. Troubleshooting Procedure for Each Check Code
10-4-1. New Check Code/Present Check Code (Central Control Side)
[E01 error]/*[99 error]
: When central controller [99] is displayed, there are other causes of error.
*
Is inter-unit cable of A and B normal?
YES
Is there no disconnection
or contact error of connector on harness
from terminal block of indoor unit?
NO
NO
Is group control operation?
YES
Is power of all indoor units turned on?
YES
Is power supplied to remote controller?
AB terminal: Approx. DC18V
YES
Are two remote controllers
set without master unit?
NO
NO
YES
NO
NO
YES
Correct inter-unit cable of remote controller.
Correct connection of connector.
Check circuit cables.
Check power connection of indoor unit.
(Turn on power again.)
Check indoor P.C. board (MCC-1402).
Defect
Correct as a master unit/a sub unit
(Remote controller address connector)
Replace
[E09 error]/*[99 error]
: When central controller [99] is displayed, there are other causes of error.
*
Are two remote controllers
set without master unit?
NO
YES
Check remote controller P.C. board.
Defect
Correct as a master unit/a sub unit
(Remote controller address connector)
Check remote controller P.C. board.
Defect
Replace
Replace
– 71 –
Page 72
[E04 error]/[04 error]
Does outdoor unit operate?
YES
NO
Is setup of group address correct?
YES
Are 1, 2, 3 inter-unit cables normal?
YES
Are connections from connectors
of inter-terminal blocks (1, 2, 3)
of indoor/outdoor units normal?
YES
2 and 3 of inter-terminal blocks (1, 2, 3)
Does voltage between
of indoor unit vary?*
YES
As shown in the following figure,
*
perform measurement within
20 seconds after power ON.
: When central controller [99] is displayed, there are other causes of trouble.
*
E08 : Duplicated indoor unit numbers
L03 : Two or more master units in a group control
L07 : One or more group addresses of [Individual] in a group control
L08 : Unset indoor group address (99)
If the above is detected when power has been turned on, the mode automatically enters in automatic address setup mode. (Check code is not displayed.)
However, if the above is detected during automatic address setup mode, the check code may be displayed.
[L09 error]/[46 error]
Is capacity of indoor unit unset?
YES
NO
Set capacity data of indoor unit.
(Setup item code (DN) = 11)
Check central controller
(including network adapter).
Defect
Replace.
NO
NO
YES
Correct cable connection
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Correct central control network address.
Replace
[L30 error]/[B6 error]
Are outside devices of
connector CN80 connected?
YES
Do outside devices normally operate?
YES
Check operation cause.
[b7 error] (Central controller)
Is group operation performed?
YES
Is check code displayed on sub unit
of main or sub remote controller?
YES
NO
NO
NO
NO
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Replace
Check outside devices.
Defect
Replace
Replace
Check corresponding
indoor/outdoor units.
– 74 –
Page 75
[P10 error]/[Ob error]
Is connection of float switch connector
(Indoor control P.C. board CH34) normal?
YES
Does float switch operate?
YES
Does drain pump operate?
YES
Is power of drain pump turned on?
NO
NO
Is circuit cabling normal?
YES
NO
YES
NO
NO
Correct connection of connector.
Check and correct cabling/wiring.
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Replace
Replace
Check drain pipe, etc.
[F10 error] [0C error]
Is connection of TA sensor connector
(indoor P.C. board CN104) normal?
YES
Are characteristics of TA sensor
resistance value normal?
YES
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect
Replace
Replace drain pump.
Check cabling.
NO
NO
* Refer to Characteristics-1.
Correct connection of connector.
Replace TA sensor.
– 75 –
Page 76
[P12 error]/[11 error]
<Only for 4-way air discharge cassette type models (RAV-SM560UT-E/RAV-SM800UT-E)>
Turn off the power.
Are not there connections errors or
disconnection on connectors CN333 and CN334
of indoor unit P.C. board (MCC-1402)?
NO
Remove connectors CN333 and
CN334 of indoor unit P.C. board
(MCC-1402).
Does the fan rotate without trouble
when handling the fan with hands?
YES
Are resistance values between phases
at fan motor connector CN333 motor side of
indoor P.C. board (MCC-1402) correct? *1
YES
YES
Correct connection of connector.
NO
Replace indoor fan motor.
NO
Replace indoor fan motor.
1
*
• Are not coil windings between
between
5
(Black lead) and (Red lead) opened or shorted?
35
(White lead) and (Black lead), between
1
13
(Red lead) and (White lead),
For resistance, see the following values.
AIU-P401H/HR, P451, P501, P561, P631, P711, P801
Approx. 70 to 100
AIU-P1121H/HR, P1401, P1601 Approx. 35 to 50
• Is not earthed between cabinet and 1, 3, 5 10M or more
Is resistance value of fan motor connector
CN333 at motor side of indoor P.C. board
(MCC-1402) correct? *2
YES
Is signal output of indoor fan motor
position detection correct? *3
YES
Check indoor P.C. board
(MCC-1402).
Defect
Replace
NO
2
*
Check resistance of fan motor position detection circuit.
Is not coil winding between (Yellow lead) and (Pink lead)
opened or shorted?
1
Resistance: Approx. 5 to 20k
NO
3
*
Check fan motor position detection signal.
• Using a tester, measure the voltage between CN334 and of
Replace indoor fan motor.
4
Replace indoor fan motor.
15
indoor P.C. board (MCC-1402) under condition that CN333 and
CN334 are mounted and the power is turned on.
Rotate the fan slowly with hands,
and check the pin voltage
swings between 0 to 5V voltage.
• Between and : 5V
45
CN333
– 76 –
CN334
Page 77
[P22 error]/[1A error]
(RAV-SM800AT-E)
Are connections of CN301 and
CN300 of P.C. board correct?
YES
Does the fan rotate without trouble
when handling the fan with hands under condition
of removing CN301 and CN300 from P.C. board?
YES
The status that the resistance values
between leads below are 50 to 80
for 40W motor (ICF-140-40) and 25 to 55
for 60W motor (ICF-140-60-1) is normal.
Between (Red lead) and (White lead)
Between (White lead) and (Black lead)
Between (Black lead) and (Red lead)
of motor winding of connector (CN301)
5k to 20k
12
23
31
YES
The status that there is
(Yellow lead) and (Pink lead)
14
resistance values between
of motor position detection of
connector (CN300) is normal.
YES
Normal fan motor
(Control or CDB P.C. board)
NO
NO
NO
Defective fan motor
CN301
CN300
* Connector of RAV-SM560AT-E differs from
that of RAV-SM800AT-E.
CN300: Motor coil winding
CN301: Motor position detection
(Control P.C. board or CDB P.C. board)
NOTE :
However, GND circuit error inside of the motor is rarely detected even if the above check is carried out.
When the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.
Objective P.C. board
Fan motor winding
Motor position detection
Fan motor winding
Motor position detection
Single phase
RAV-SM560AT-E
Control P.C. board
CN300
CN301
Single phase
RAV-SM800AT-E
CDB P.C. board
CN301
CN300
– 77 –
Page 78
[P19 error]/[08 error]
Check and replace
electron expansion
valve.
* Refer to Characteristics-2.
Replace TC sensor.
Is operation of
4-way valve normal?
NO
NO
Is flow of refrigerant
by electron expansion
valve normal?
Are characteristics
of TC sensor resistance
value normal?
YES
YES
YES
NO
Is voltage applied
to 4-way valve coil terminal
in heating operation?
YES
Is circuit cable normal?
YES
Check CDB P.C. board.
YES
NO
Check 4-way valve
Defect
NO
Check and correct circuit.
NO
Replace
Check indoor P.C. board.
Defect
Replace
* For RAV-SM560AT-E, check control P.C. board.
Check CDB P.C. board.
Defect
Replace
• In cooling operation, if high pressure is abnormally raised, [P19 error]/[08 error] may be displayed. In this
case, remove cause of pressure up and then check again referring to the item [P04 error]/[21 error].
Check connections of A, B terminal blocks.
Correct communication line of remote controller.
Correct power cable.
Turn on the source power supply.
Clear the check code.
NO
Is the network address changed
form remote controller?
NO
Is there no noise source, etc.?
NO
Can central remote controller
control normally other indoor units?
Is handling of central remote controller reflected
on the operation status of indoor unit?
YES
Does network adapter P.C. board
LED (D01) go on?
YES
Can handy remote controller control
normally other indoor units?
NO
YES
YES
NO
(Same as others)
YES
Eliminate noise, etc.
Check central controller.
Defect Replace
NO
Check network adapter P.C. board and power transformer.
Defect Replace
– 85 –
Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect Replace
Page 86
[E03 error] (Master indoor unit)
[E03 error] is detected when the indoor unit cannot receive a signal sent from the main remote controller (and
central controller).
In this case, check the communication cables of the remote controllers A and B, the central control system X
and Y. As communication is disabled, [E03] is not displayed on the main remote controller and the central
controller. [E01] is displayed on the main remote controller and [97 error] on the central controller, respectively.
If [E03] occurs during an operation, the air conditioner stops.
[F29 error] / [12 error]
[F29 error] or [12 error] indicates detection of trouble which occurred on IC10 non-volatile memory (EEPROM)
on the indoor unit P.C. board during operation of the air conditioner. Replace the service P.C. board.
* If EEPROM has not been inserted when the power was turned on or if EEPROM data never be read/written,
the automatic address mode is repeated. In this time, the central controller displays [97 error].
(Power ON)
(Approx. 3 minutes)
[SET] is displayed on
main remote controller.
(Approx. 1 minute)
[SET] goes off.
(Repetition)
LED (D02) on
indoor unit P.C. board flashes
with 1Hz for approx. 10 seconds.
Reboot
(Reset)
[P31 error] (Sub indoor unit)
When the master unit of a group operation has detected [E03], [L03], [L07], or [L08] error, the sub unit of the
group operation detects [P31 error] and then it stops. There is no display of the check code or alarm history of
the main remote controller.
(In this model, the mode enters in automatic address set mode when the master unit has detected [E03], [L03],
[L07], or [L08] error.)
– 86 –
Page 87
10-4-2. Relational Graph of Temperature Sensor Resistance Value and Temperature
Resistance
(k
200
20
)
10
0
1020403050
Temperature [ C]Temperature [ C]
Caracteristics-3
TA sensor
Caracteristics-1
Resistance
(k
40
TC, TCJ sensor
30
Caracteristics-2
)
20
10
0
–
1010302040506070
0
TE, TO, TS sensor
20
Resistance
(k
(10 C or lower)
100
200
Resistance
(k
(50 C or lower)
100
Resistance
(k
)
0
100-10204030506070
)
(10 C or higher)
10
0
Temperature [ C]
TD sensor
Caracteristics-4
20
Resistance
(k
)
)
(50 C or higher)
10
0
50100
0
Temperature [ C]
– 87 –
Page 88
11. REPLACEMENT OF SERVICE INDOOR P.C. BOARD
[Requirement when replacing the service indoor P.C. board assembly]
In the non-volatile memory (Hereinafter said EEPROM, IC10) installed on the indoor P.C. board before replacement, the type and capacity code exclusive to the corresponding model have been stored at shipment from the
factory and the important setup data such as system/indoor/group address set in (AUTO/MANUAL) mode or
setting of high ceiling selection have been stored at installation time. Replace the service indoor P.C. board
assembly according to the following procedure.
After replacement, check the indoor unit address and also the cycle by a test run.
<REPLACEMENT PROCEDURE>
CASE 1
Before replacement, power of the indoor unit can be turned on and the setup data can be readout from
the wired remote controller.
Read EEPROM data *1 (ref. P89)
ò
Replace service P.C. board & power ON *2 (ref. P89)
ò
Write the read data to EEPROM *3 (ref. P90)
ò
Power reset (All indoor units in the group when group operation)
CASE 2
Before replacement the setup data can not be readout from the wired remote controller.
Replace service P.C. board & power ON *2 (ref. P89)
ò
Write the data such as high ceiling setup to EEPROM (According to the customers’ information) *3
ò
Power reset (All indoor units in the group when group operation)
– 88 –
Page 89
r1 Readout of the setup data from EEPROM
(Data in EEPROM contents, which have been changed at the local site, are read out together with data in
EEPROM set at shipment from the factory.)
1. Push
2. Every pushing
3. Using the set temperature
4. First change the item code (DN) from
5. Next change the item code (DN) using the set temperature
6. Repeat item 5. and make a note of the important set data as shown in the later table (Ex.).
7. After finishing making a note, push
SET
,
, and
(Corresponded with No. in Remote controller)
When group operation, the master indoor unit address is displayed at the first time. In this time, the item
code (DN)
indoor unit No. to be replaced.
data displayed in this time.
•
01 to 9F are provided in the item code (DN). On the way of operation, DN No. may come out.
(Approx. 1 minute is required to start handling of the remote controller.)
Minimum requirements for item code
10
buttons of the remote controller at the same time for 4 seconds or more.
is displayed. The fan of the selected indoor unit operates and the flap starts swinging if any.
button, the indoor unit address in the group are displayed successively.
buttons, the item code (DN) can be moved up and down one by one.
/
10
to 01. (Setting of filter sign lighting time) Make a note of the set
/
buttons. Also make a note of the set data.
button to return the status to usual stop status.
6
1
2
Specify the
3
DN
10
11
12
13
14
Contents
Type
Indoor unit capacity
Line address
Indoor address
Droup address
(1) Type and capacity of the indoor unit is necessary to set the revolutions
frequency of the fan.
(2) If Line/Indoor/Group addresses differ from those before replacement,
the mode enters in automatic address setup mode and a manual
resetting may be required.
r2 Replacement of service P.C. board
1. Replace the P.C. board with a service P.C. board.
In this time, setting of jumper line (cut) or setting of (short-circuit) connecting connectors on the former P.C.
board should be reflected on the service P.C. board.
2. According to the system configuration, turn on power of the indoor unit with any method in the following items.
a) In case of single (individual) operation
Turn on the power supply.
1) Wait for completion of automatic address setup mode (Required time: Approx. 5 minutes) and then
proceed to r3.
(Line address = 1, Indoor address = 1, Group address = 0 (Individual) are automatically set.)
SET
, and
2) Push
(
1
(Unit No.
b) In case of group operation
Turn on power of the indoor unit of which P.C. board has been replaced with the service P.C. board with
any method in the following items.
1) Turn on power of the replaced indoor unit only.
(However, the remote controller is also connected. Otherwise r3 operation cannot be performed.)
Same as 1) and 2) in item a).
2) Turn on power of the multiple indoor units including replaced indoor unit.
• Only 1 system for twin, triple, double twin
• For all units in the group
Wait for completion of automatic address setup mode (Required time: Approx. 5 minutes) and then
proceed to r3.
* The master unit of a group may change by setup of automatic address. The line address/indoor address of the
replaced indoor unit are automatically set to the vacant addresses except addresses belonging to other indoor
units which have not been replaced. It is recommended to make a note that the refrigerant line which includes
the corresponding indoor unit and that the corresponding indoor unit is master or sub in the group control.
,
operation), interrupt the automatic address setup mode, and then proceed to r3.
ALL
is displayed.)
buttons of the remote controller at the same time for 4 seconds or more
– 89 –
Page 90
r3 Writing of the setup contents to EEPROM
UNIT
SET
CL
UNIT No.
SET DATA
R.C. No.
4
6
1
3
52
(The contents of EEPROM installed on the service P.C. board have been set up at shipment from the factory.)
1. Push
2. Every pushing
3. Using the set temperature
4. First set a type and capacity of the indoor unit.
5. Next write the contents which have been set up at the local site such as the address setup in EEPROM.
6. Using the set temperature
7. The contents of the displayed setup data in this time should be agreed with the contents in the previous
8. Using the set temperature
9. Then repeat the procedure 7. and 8.
10. After completion of setup, push
01 to 9F are provided in the item code (DN).
*
On the way of operation, DN No. may come out.
When data has been changed by mistake and
button has been pushed, the data can be returned
to the data before change by pushing
the item code (DN) was not yet changed.
SET
,
, and
(Corresponded with No. in Remote controller )
In group operation control, the master indoor unit No. is displayed at the first time. (If the automatic address
setup mode is interrupted in item 2. - a) - 2) in the previous page, the unit No.
the item code (DN)
if any.
Specify the indoor unit No. of which P.C. board has been replaced with a service P.C. board.
(When the unit No.
(Setting the type and capacity writes the data at shipment from the factory in EEPROM.)
1) Set the item code (DN) to
2) Using the timer time
(For example, 4-way air discharge cassette type is 0001) Refer to the attached table.
SET
3) Push
4) Using the set temperature
5) Using the timer time
(For example, 0012 for class 80) Refer to the attached table.
6) Push
7) Push
(Approx. 1 minute is required to start handling of the remote controller.)
Repeat the above procedure 1. and 2.
(Setup of lighting time of filter sign)
memorandum in r1.
1) If data disagree, change the displayed setup data to that in the previous memorandum by the timer time
2) There is nothing to do when data agrees.
As same as the above, check the contents of the setup data and then change them to data contents in the
previous memorandum.
button. (OK when the display goes on.)
SET
button. (OK when the display goes on.)
button to return the status to usual stop status.
buttons, and then push
/
buttons of the remote controller at the same time for 4 seconds or more.
ALL
is displayed.) In this time,
10
is displayed. The fan of the selected indoor unit operates and the flap starts swinging
button, the indoor unit numbers in the group control are displayed successively.
ALL
is displayed, this operation cannot be performed.)
/
buttons, the item code (DN) can be moved up and down one by one.
10
. (As it is)
buttons, set up a type.
/
4
1
2
5
buttons, set
/
buttons, set the capacity.
/
11
to the item code (DN).
6
/
buttons, set
SET
button. (OK when the display goes on.)
/
buttons, change the item code (DN).
01
to the item code (DN).
3
<REMOTE CONTROLLER>
button to return
the status to the usual stop status.
(Approx. 1 minute is required to start handling of
the remote controller.)
6
SET
button if
– 90 –
Page 91
Memorandum for setup contents (Item code table (Example))
DN
01
Filter sign lighting time
02
Dirty state of filter
03
Central control address
06
Heating suction temp shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
19
Flap type (Adjustment of air direction)
1E
Temp difference of automatic cooling/
heating selecting control points
28
Automatic reset of power failure
2A
Option
2b
Thermo output selection (T10 ‡B)
2E
Option
32
Sensor selection
5d
High ceiling selection
60
Timer set (Wired remote controller)
8b
Correction of high heat feeling
Item
Memo
At shipment
According to type
0000: Standard
0099: Unfixed
0002: +2°C (Floor type: 0)
0000: Shared for cooling/heating
According to model type
According to capacity type
0099: Unfixed
0099: Unfixed
0099: Unfixed
According to type
0003: 3 deg (Ts ± 1.5)
0000: None
0002:
0000: Thermo ON
0000:
0000: Body sensor
0000: Standard
0000: Available
0000: None
Type
Item code [10]
Setup data
0001*
0006
4-way air discharge cassette
Concealed duct
Type
* Initial setup value of EEPROM installed on the service P.C. board
Indoor unit capacity
Item code [11]
Setup data
0000*
0009
0012
Model
Invalid
56
80
* Initial setup value of EEPROM installed on the service P.C. board
Abbreviated name
RAV-SM560/800TU-E
RAV-SM560/800BT-E
– 91 –
Page 92
12. SETUP AT LOCAL SITE AND OTHERS
12-1. Indoor Unit
12-1-1. Test Run Setup on Remote Controller
<Wired remote controller>
1. When pushing
Then push
•“TEST” is displayed on LC display during operation of Test Run.
• During Test Run, temperature cannot be adjusted but air volume can be selected.
• In heating and cooling operation, a command to fix the Test Run frequency is output.
• Detection of error is performed as usual. However, do not use this function except case of Test Run be-
cause it applies load on the unit.
2. Use either heating or cooling operation mode for [TEST].
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after
operation has stopped.
3. After a Test Run has finished, push
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote
controller.)
<Wireless remote controller> (Option for 4-way air discharge cassette type)
1. Turn off power of the unit.
Remove the adjuster attached with sensors from the ceiling panel. For removing, refer to the Installation
manual attached to the ceiling panel. (Be careful to handle the adjuster because cables are connected to the
sensor.) Remove the sensor cover from the adjuster. (1 screw)
2. Change ON of Bit [1: TEST] of the sensor P.C. board switch [S003] to OFF.
Mount the sensor cover and mount the adjuster with sensor to the ceiling panel.
Turn on power of the unit.
3. Push
button. (All the display lamps of sensors on the wireless remote controller flash during Test Run.)
• Do not perform Test Run operation in other modes than [HEAT] / [COOL] mode.
• Detection of error is performed as usual.
4. After Test Run operation, push
5. Turn off power of the unit.
Return Bit [1] of the sensor P.C. board switch [S003] to the original position. (ON → OFF)
Mount the adjuster with sensors to the ceiling panel.
button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display.
button.
button again and check that [TEST] on LC display has gone off.
button on the wireless remote controller and select [COOL] or [HEAT] operation mode using
button to stop the operation.
Sensor cover
Adjust corner cap
S003
– 92 –
Bit 1 : OFF to ON
ON
Sensor P.C. board
2
3
4
1
Page 93
12-1-2. Setup to Select Function
<Procedure> Use this function while the indoor unit stops.
SET
,
1
Push
The unit No. displayed at the first time indicates the indoor unit address of the master unit in the group control.
In this time, fan and flap of the selected indoor unit operate.
2
Every pushing button, the indoor unit numbers in the group control are displayed successively.
In this time, fan and flap of the selected indoor unit only operate.
0000 : 0 degto0010 : 10 deg
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
0000 : None0001 : Reset
0000 : Indoor thermo ON0001 : Output of outdoor comp-ON
receiving
0000 : Body TA sensor0001 : Remote controller sensor
0000 : Standard filter
0001 : Oil guard, Super-long life, Optical regenerative deodorization
0003 : High performance (65%), High performance (90%),
High antibacterial performance (65%)
According to type
0003 : 3 deg
(Ts±1.5)
0000 : None
0002 : Default
0000: Thermo. ON
0000 : Default
0000 : Default
0000 : Default
0000 : Body sensor
0003 : Default
0000 : Standard
60
Timer set
(Wired remote
controller)
8b
Correction of high
heat feeling
0000 : Available (Operable)0001 : Unavailable (Operation prohibited)
0000 : None0001 : Correction
– 94 –
0000 : Available
0000 : None
Page 95
12-1-3. Cabling and Setting of Remote Controller Control
2-remote controller control (Controlled by two remote controllers)
One or multiple indoor units are controlled by two remote controllers.
(Max. 2 remote controllers are connectable.)
• 1 indoor unit is controlled by 2
remote controllers
Remote controller
switch (Master)
Sold separately
BA
Indoor unit
213
213
Outdoor u
Remote controller
switch (Sub)
Sold separately
Remote controller
cables (Procured locally)
Terminal block for
remote controller cables
nit
(Setup method)
One or multiple indoor units are controlled by two remote controllers.
(Max. 2 remote controllers are connectable.)
<Wired remote controller>
How to set wired remote controller to sub remote
Rear side of remote
controller P.C. board
controller
Insert the remote controller address connector
provided on the rear side of the remote controller
switch P.C. board into Sub in exchange for Master.
<Wireless remote controller>
How to set wireless remote controller to sub
remote controller
Change OFF of Bit [3: Remote controller Sub/
Master] of switch S003 to ON.
Sensor
cover
Adjust
corner cap
Remote controller
address connector
Sub
remote controller
S003
Bit 1 : OFF to ON
ON
Sensor P.C. board
Master remote
controller
1
2
3
4
[Operation]
1. The operation contents can be changed by Last-push-priority.
2. Use a timer on either Master remote controller or Sub remote controller.
– 95 –
Page 96
12-1-4. Monitor Function of Remote Controller Switch
UNIT
SET
CL
UNIT No.
SET DATA
R.C. No.
4
2
1 2 3 4
31
<Operation procedure>
Returned to usual display
n Call of sensor temperature display
<Contents>
Each sensor temperature of the remote controller, indoor
unit, and outdoor unit can become known by calling the
service monitor mode from the remote controller.
<Procedure>
1
Push
seconds or more to call the service monitor
mode.
The service monitor goes on, the master indoor unit
No. is displayed, and then temperature of the item
code
2
Push the temperature setup
to select the sensor No. (Item code) of the sensor
to be monitored.
The sensor numbers are described below:
+
buttons simultaneously for 4
00
is displayed.
/
buttons
Item code
00
Indoor
unit data
*1 Only master unit in group control
3
The temperature of indoor units and outdoor unit in a group control can be monitored by pushing
button to select the indoor unit to be monitored.
4
Pushing
01
02
03
04
button returns the display to usual display.
Room temp (under control) *1
Room temp (remote controller)
Indoor suction temp
Indoor coil temp (TCJ)
Indoor coil temp (TC)
Data name
Outdoor
unit data
Item code
60
61
62
63
64
65
Heat exchanger temp TE
Outside temp TO
Discharge temp TD
Suction temp TS
—
Heat sink temp THS
Data name
– 96 –
Page 97
n Calling of error history
UNIT
SET
CL
UNIT No.
SET DATA
R.C. No.
3
2
1
1 2 3
<Operation procedure>
Returned to usual display
<Contents>
The error contents in the past can be called.
<Procedure>
1
Push
seconds or more to call the service check mode.
Service Check goes on, the item code
displayed, and then the content of the latest alarm is
displayed. The number and error contents of the
indoor unit in which an error occurred are displayed.
2
In order to monitor another error history, push
the set temperature
change the error history No. (Item code).
Item code
NOTE : Four error histories are stored in memory.
+
buttons simultaneously for 4
/
buttons to
01
(Latest) → Item code
04
01
(Old)
is
3
Pushing
display.
button returns the display to usual
<Requirement>
Do not push
the indoor unit are deleted.
button, otherwise all the error histories of
(Group control operation)
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.
The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to
setting on the remote controller.
<System example>
OUT
IN
1-1
OUT
IN
Master
2-1
OUT
IN
3-1
OUT
IN
4-1
OUT
IN
7-1
Max. 8 units
(1) Display range on remote controller
The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the
master unit is reflected on the remote controller.
(2) Address setup
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic
address.
If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the
system is rebooted and the automatic address setting will be judged again.
1) Connect 3 In/Out cables surely.
2) Check line address/indoor address/group address of the unit one by one.
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the
unit No. is not duplicated with one of another unit.
Remote controller
– 97 –
Page 98
12-2. Network Adapter
Model name: TCB-PCNT20E
12-2-1. Function
A network adapter is an optional P.C. board to connect the indoor unit to AI net (Central control remote controller).
12-2-2. Microcomputer Block Diagram
Remote controller
Optional communication P.C. board
Indoor control
P.C. board
CN309
AC220240V
CN41
Power
transformer
Terminal
block
(A.B)
AC14V
CN02
CN01
Remote
controller
communication
circuit
5V
power
supply
5V
MCU
Network address
setup switch
12-2-3. Network Address Setup Switch (SW01)
No.
1
LSB
2
3
Central control address
4
5
6
MSB
7
Setup availability from
remote controller
8
Item
Setup contents
123456
×××× × × : No.1 unit×: Switch OFF
〇××× × × : No.2 unit〇: Switch OFF
:
〇〇〇〇 〇 × : No.63 unit
〇〇〇〇 〇 〇 : No.64 unit
Switch OFF : Setup available from remote controller
Switch ON : Setup unavailable from remote controller
Indoor unit
AI-NET
communication
circuit
EEPROM
CN03
Terminal
block
(X.Y)
Central control
remote controller
Network
Communication
units: Total 64 units
Communication
distance: 1km
12-2-4. LED Display Specification
LED No.
D01 (Red)
D02 (Red)
D03 (Red)
D04 (Red)
Communication status: Remote controller
Communication status: Center
Operation status of air conditioner
Air conditioner error
* For positions of LED, refer to P.C. board external view.
Function
During communication
During communication
Running
Error
– 98 –
Go on
Go off
No communication (including communication error)
No communication (including communication error)
Stop
Normal
Page 99
12-2-5. Communication Cable Specifications
Communication circuit
No.
1
Remote controller
communication side
Cable
Cable type
Neutral 2-cable type
CVV(JIS C3401) Controlling vinyl insulation vinyl seal cable
Communication cable specifications
VCTF (JIS C3306) Vinyl cab tire round type cord
VCT(JIS C3401) 600V vinyl cab tire cable
VVR(JIS C3401) Vinyl insulation seal cable round type
MVVS Cable with net shielding for instrumentation
(Up to 400m when there is wireless remote controller in group)
2
AI NET side
Cable
Cable type
Cable dia.
Cable length
Neutral 2-cable type
MVVS Cable with net shielding for instrumentation
1.25 mm² ≤ 500 m, 2.0 mm² ≤ 1 km
Total cable length : Up to 500m when using 1.25mm² cable,
Up to 1000m when using 2.0mm² cable
12-2-6. Cable Connection
<Network cable connection>
• Install a network adapter per 1 group of the group control (including single unit control). Also install a network
adapter to one of the indoor units in the group control.
Central
control
remote
controller
X Y
Network
adapter
Indoor unit
Indoor
control
P.C. board
A B
Remote
controller
Indoor
unit
Indoor
control
P.C. board
A B
Indoor
unit
Indoor
control
P.C. board
A B
Connectable indoor units per group: Up to 8 units
(1-remote controller system*)
* In case of 2-remote controllers system,
the connectable indoor units are up to 7 units.
Indoor
unit
Indoor
control
P.C. board
A B
X Y
Network
adapter
Indoor unit
Indoor
control
P.C. board
A B
Indoor
unit
Indoor
control
P.C. board
A B
– 99 –
Page 100
12-3. How to Set an Address Number
UNIT
SET
CL
UNIT No.
SET DATA
R.C. No.
3
1
5
2
4
When connecting indoor units to the central control remote controller by using a network adapter, it is required
to set up a network address No.
• The network address No. should be agreed with the line No. of the central control remote controller.
• When the unit was shipped from the factory, the network address has been set to 1.
The following two methods to set the network address are provided.
1. How to set from the remote controller at indoor unit side
* This method is effective only when of set switch SW01 on the network adapter P.C. board is turned off.
<Procedure> Set the network address while the unit stops.
1
Push
In the group control, the unit No
and then all the indoor units in the group control are
selected. In this time, fans of all the selected indoor
units are turned on. (Fig. 1)
(Keep status of
button.)
For the individual remote controller which is not
included in a group control, the line address and the
indoor unit address are displayed.
2
Specify the item code 03 using the temperature
setup
+
buttons for 4 seconds or more.
RLL is displayed,
RLL display without pushing
/
buttons.
Fig. 1
3
Using the timer time
setup data.
The setup data are shown in the right table (Table 1).
SET
4
Push
• To change the item to be set, return to
5
Push
The status returns to the usual stop status.
button. (OK if display goes on)
button.
/
buttons, select the
2
Table 1
Setup data
0001
.
0002
0003
:
0064
0099
Unset (Setup at shipment from factory)
Network address No.
1
2
3
:
64
2. How to set by the switch on the network adapter P.C. board
When the remote controller cannot be found or when you don’t want to change setting of the network address
No. from the remote controller, use the setup switch SW01 on the network adapter P.C. board (Network address
No. setup switch) to set the address No.
<Procedure>
(1) Turn off the power.
(2) Turn
side. Accordingly the address No. set on the remote
controller is invalidated. (See Fig. 2.)
(3) Set the network address No. with combination of ON
and OFF of
SW01. The relation between combination of ON/OFF
and address No. is described in Table 2. The right
figure (Fig. 3) shows an example of case that the
address No. is set to 16.
When the network address No. has been changed,
be sure to turn of power of the central control remote
controller again or to reset the remote controller using
the reset hole on the operation panel of the central
control remote controller.
of the address No. setup switch SW01 to ON
to of the address No. setup switch
– 100 –
Invalid address No. setup from
remote controller
No. setup switch
ON
ON side
OFF side
4
5 6 7
32
1
Address No. setup
Setup example of address No. 16
ON
4 5 6
321
(Numeral side)
SW01
Fig. 2
ON side
OFF side
(Numeral side)
7
Fig. 3
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.