Toshiba RAS-M16SMUV-E, RAS-M10SMUV-E, RAS-M16SMUCV-E, RAS-M10SMUCV-E, RAS-M13SMUV-E User Manual

...
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
FILE NO. A06-015
INDOOR UNIT
Heat Pump Model Cooling Only Model
R410A
PRINTED IN JAPAN, Apr.,2007 ToMo
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refriger­ant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself.
The cleaning diagram for the air filter is there for the service person, and not for the customer.
CONTENTS
1. SAFETY PRECAUTIONS.............................................................................................................3
2. SPECIFICATIONS ........................................................................................................................ 5
2-1. Combined Outdoor Unit ..................................................................................................................................5
2-2. Indoor Unit ........................................................................................................................................................6
3. REFRIGERANT R410A................................................................................................................8
3-1. Safety During Installation/Servicing ..............................................................................................................8
3-2. Refrig erant Piping Installation .....................................................................................................................8
3-3. Tools ................................................................................................................................................................12
3-4. Recharging of Refrigerant ............................................................................................................................13
3-5. Brazing of Pipes .............................................................................................................................................14
4. CONSTRUCTION VIEWS...........................................................................................................16
4-1. Indoor Unit ......................................................................................................................................................16
5. REFRIGERA TING CYCLE DIAGRAM .......................................................................................17
5-1. Indoor Unit ......................................................................................................................................................17
6. WIRING DIAGRAM .................................................................................................................... 18
6-1. Indoor Unit ......................................................................................................................................................18
7. SPECIFICA TIONS OF ELECTRICAL PARTS ...........................................................................19
7-1. Indoor Unit ......................................................................................................................................................19
8. CONTROL BLOCK DIAGRAM ..................................................................................................20
8-1. Indoor Control Circuit ...................................................................................................................................20
9. OPERATION DESCRIPTION ..................................................................................................... 21
9-1. Outline of Air Conditioner Control...............................................................................................................21
9-2. Operation Description ...................................................................................................................................22
9-3. Intermittent Operation Control for Indoor Fans of the Indoor Unit
at Thermo-off Side in Heating Operation ....................................................................................................37
9-4. Remote Controller .........................................................................................................................................38
10. INSTALLATION MANUAL..........................................................................................................40
Accessory parts and Parts to be procured locally ....................................................................................40
1 PRECAUTIONS FOR SAFETY .......................................................................................................................41
2 SELECTION OF INSTALLATION PLACE ......................................................................................................43
3 INSTALLATION OF INDOOR UNIT ................................................................................................................45
4 DRAIN PIPING WORK ....................................................................................................................................49
5 REFRIGERANT PIPING AND EVACUATING .................................................................................................52
6 EVACUATING ..................................................................................................................................................53
7 ELECTRICAL WORK ......................................................................................................................................54
8 APPLICABLE CONTROLS.............................................................................................................................57
9 TEST OPERATION..........................................................................................................................................59
10 INSTALLATION / SERVICING TOOLS ...........................................................................................................59
11 MAINTENANCE ..............................................................................................................................................60
11. HOW TO DIAGNOSE THE TROUBLE ........................................................................................61
11-1. First Confirmation............................................................................................................................................61
11-2. Primary Judgment .........................................................................................................................................62
11-3. Judgment by Flashing LED of Indoor Unit (Switch Panel) .......................................................................62
11-4. Self-Diagnosis by Remote Controller (Check Code) .................................................................................63
11-5. Judgment of Trouble by Every Symptom ....................................................................................................66
11-6. How to Check Simply the Main Parts ..........................................................................................................70
11-7. P.C. Board Layout...........................................................................................................................................71
11-8. Service P.C. Board Selection Information ...................................................................................................72
12. DETACHMENTS.........................................................................................................................73
12-1. Indoor Unit ......................................................................................................................................................73
13. EXPLODED VIEWS AND PARTS LIST ..................................................................................... 81
13-1. Ceiling Panel ..................................................................................................................................................81
14-2. 4-way Air Discharge Cassette Type .............................................................................................................82
– 2 –
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be 1.5 mm ² (H07RN-F or 60245IEC66) polychloroprene sheathed flexible cord.
• Read this “SAFETY PRECAUTIONS” carefully before servicing.
• The precautions described below include the important items regarding safety. Observe them without f ail.
• After the servicing work, perform a trial operation to check for any problem.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during installation work, be sure that water , dust, former refrigerant, or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes , use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
A switch or circuit breaker that can disconnect all poles must be included in the fixed wiring. Be sure to use an approved circuit breaker or switch.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO INSTALL/ MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated. Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
• CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCOR­RECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
– 3 –
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT REGISTORS, FURNACE, STOVES, ETC.
• WHEN MO VING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VER Y CARE­FUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL BECOME ABNORMALLY HIGH AND IT MA Y RESULT IN THE PIPE BURSTING AND POSSIBLE PER­SONNEL INJURIES.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE WORK AND THE INSTALLATION W ORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may generate.
• The electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cables and connect the terminals securely to prevent external forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
• Exposure of unit to water or other moisture before installation may result in an electrical short. Do not store in a wet basement or expose to rain or water.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise or discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Perf orm the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously perf ormed for a long time under the condition that the outdoor temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate, resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner. For details, contact the dealer.
– 4 –

2. SPECIFICATIONS

2-1. Combined Outdoor Unit
The outdoor units, which can be combined with 4-way Air Discharge Cassette indoor unit are as described below:
2-1-1. Cooling and Heating Type
Outdoor
unit type
2-room Multi
outdoor unit
3-room Multi
outdoor unit
4-room Multi
outdoor unit
Combined outdoor unit
model name
RAS-M14GAV-E
RAS-M18GAV-E RAS-3M18SAV-E RAS-3M26GAV-E RAS-4M23SAV-E
RAS-4M27GAV-E
2-1-2. Cooling only type
Outdoor
unit type
2-room Multi
outdoor unit
3-room Multi
outdoor unit
4-room Multi
outdoor unit
Combined outdoor unit
model name
RAS-M14GACV-E
RAS-M18GACV-E RAS-3M18SACV-E RAS-3M23GACV-E RAS-4M23SACV-E
RAS-4M27GACV-E
Capacity rank of 4-way Air Discharge Cassette
16 class 13 class 10 class
×××
¡¡¡
¡¡¡
¡¡¡
¡¡¡
¡¡¡
: Combination available, ×: Combination unavailable
¡
Capacity rank of 4-way Air Discharge Cassette
16 class 13 class 10 class
×××
¡¡¡
¡¡¡
×××
¡¡¡
¡¡¡
Conditions
of combination
Combination unavailable
None None None None
Restrict the max. pipe length 70m to 50m
Conditions
of combination
Combination unavailable
None None
Combination unavailable
None
Restrict the max. pipe length 70m to 50m
: Combination available, ×: Combination unavailable
¡
This Service Manual describes about 4-way Air Discharge Cassette indoor units, RAS-M10SMUV-E, RAS-M13SMUV-E, RAS-M16SMUV-E, RAS-M10SMUCV-E, RAS-M13SMUCV-E and RAS-M16SMUCV-E only.
For the outdoor unit, refer to the Service Manual attached to the combined outdoor unit.
Outdoor unit
RAS-M18GAV-E RAS-M18GACV-E RAS-3M18SAV-E RAS-3M18SACV-E RAS-4M23SAV-E RAS-4M23SACV-E
RAS-3M26GAV-E, RAS-4M27GAV-E RAS-4M27GACV-E
File No. A05-009-1 A06-013 A06-014 A05-011
– 5 –
2-2. Indoor Unit
2-2-1. Heat Pump Model
Model
Power supply
Cooling mode
Heating mode
Fan unit
Outer Depth (mm) dimension Height (mm)
Appearance
Total weight
Piping connection
Installable ceiling height of indoor unit
Usable temperature range
Accessory
Indoor unit Panel
Voltage (V)
Electrical characteristics
Sound pressure level
Air flow Medium (m³/min.)
Electrical characteristics
Sound pressure level
Air flow Medium (m³/min.)
Fan Motor output (W)
Indoor unit Width (mm)
Panel Width (mm)
Indoor unit Panel Indoor unit (kg) Panel (kg)
Indoor unit
Panel
Running current (A) Power consumption (W) Power factor (%) High (dB) Medium+ (dB) Medium (dB) Low+ (dB) Low (dB) High (m³/min.) Medium+ (m³/min.)
Low+ (m³/min.) Low (m³/min.) Voltage (V) Running current (A) Power consumption (W) Power factor (%) High (dB) Medium+ (dB) Medium (dB) Low+ (dB) Low (dB) High (m³/min.) Medium+ (m³/min.)
Low+ (m³/min.) Low (m³/min.)
Height (mm)
Depth (mm)
Type Liquid side (mm) Gas side (mm) Drain port Minimun (m) Maximum (m) Cooling (°C) Heating (°C) Wireless remote controller Batteries Remote controller holder Mounting screw Owner’s manual Installation manual Installation manual Mounting screw
RAS-M10SMUV-E RAS-M13SMUV-E RAS-M16SMUV-E
RB-B11MC (W) E
1 phase, 50Hz 220 to 240 V, 60Hz 220 V
220/230/240 220/230/240 220/230/240
0.21/0.20/0.19 0.21/0.20/0.19 0.21/0.20/0.19 23 23 23 50 50 50 37 38 40 35 36 38 33 34 37 32 32 34 30 30 31
9.8 10.3 11.0
9.1 9.6 10.3
8.4 8.8 9.5
7.7 8.1 8.4
7.2 7.2 7.5
220/230/240 220/230/240 220/230/240
0.21/0.20/0.19 0.21/0.20/0.19 0.21/0.20/0.19 23 23 23 50 50 50 37 38 40 35 36 38 33 34 37 32 32 34 30 30 31
9.8 10.3 11.0
9.1 9.6 10.3
8.4 8.8 9.5
7.7 8.1 8.4
7.2 7.2 7.5 Turbo fan
60 268 575 575
27 700 700
Zinc hot diping steel plate
Moon-white (Muncel 2.5GY, 9.0/0.5)
15
3
Flare connection
Ø6.35
Ø9.52 Ø9.52 Ø12.7
VP25
2.5 2.5 2.5
2.7 2.7 3.5 21 to 32
0 to 29
1 (WH-H3UE)
2 1 1 1 1 1 4
– 6 –
2-2-2. Cooling Only Model
Model
Power supply
Cooling mode
Fan unit
Outer Depth (mm) dimension Height (mm)
Appearance
Total weight
Piping connection
Installable ceiling height of indoor unit
Usable temperature range Cooling (°C)
Accessory
Indoor unit Panel
Voltage (V)
Electrical characteristics
Sound pressure level
Air flow Medium (m³/min.)
Fan Motor output (W)
Indoor unit Width (mm)
Panel Width (mm)
Indoor unit Panel Indoor unit (kg) Panel (kg)
Indoor unit
Panel
Running current (A) Power consumption (W) Power factor (%) High (dB) Medium+ (dB) Medium (dB) Low+ (dB) Low (dB) High (m³/min.) Medium+ (m³/min.)
Low+ (m³/min.) Low (m³/min.)
Height (mm)
Depth (mm)
Type Liquid side (mm) Gas side (mm) Drain port Minimun (m) Maximum (m)
Wireless remote controller Batteries Remote controller holder Mounting screw Owner’s manual Installation manual Installation manual Mounting screw
RAS-M10SMUCV-E RAS-M13SMUCV-E RAS-M16SMUCV-E
RB-B11MC (W) E
1 phase, 50Hz 220 to 240 V, 60Hz 220 V
220/230/240 220/230/240 220/230/240
0.21/0.20/0.19 0.21/0.20/0.19 0.21/0.20/0.19 23 23 23 50 50 50 37 38 40 35 36 38 33 34 37 32 32 34 30 30 31
9.8 10.3 11.0
9.1 9.6 10.3
8.4 8.8 9.5
7.7 8.1 8.4
7.2 7.2 7.5 Turbo fan
60 268 575 575
27 700 700
Zinc hot diping steel plate
Moon-white (Muncel 2.5GY, 9.0/0.5)
15
3
Flare connection
Ø6.35
Ø9.52 Ø9.52 Ø12.7
VP25
2.5 2.5 2.5
2.7 2.7 3.5 21 to 32
1 (WC-H2UE)
2 1 1 1 1 1 4
– 7 –
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refriger­ating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the follow­ing precautions into consideration.
1. Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service por t differs from that of R22.
3. If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
4. When installing or removing an air conditioner, do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous.
If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used.
Copper pipes and joints suitable for the refrigerant must be chosen and installed.
Further more, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m.
Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pres­sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1.
Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 8 –
Table 3-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4 3/8 1/2 5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 3/8 1/2 5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
– 9 –
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Fig. 3-2-1 Flare processing dimensions
Flare tool for R410A
clutch type
ØD
A
A (mm)
Conventional flare tool
Clutch type Wing nut type
1/4 3/8 1/2 5/8
Nominal
diameter
1/4 3/8 1/2 5/8
6.35
9.52
12.70
15.88
0.8
0.8
0.8
1.0
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Table 3-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for R22
clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Nominal
diameter
1/4 3/8 1/2 5/8
Table 3-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
– 10 –
Flare nut width
(mm)
17 22 26 29
Table 3-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4 3/8 1/2 5/8 3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
45˚ to 46˚
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
B A
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.7 19.0 16.0 23
23.3 24.0 19.2 34
D
C
43˚ to 45˚
Flare nut width
(mm)
17 22 24 27 36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench.
The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer diameter
(mm)
Tightening torque
N•m (kgf•cm)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/4 3/8 1/2 5/8
6.35
9.52
12.70
15.88
14 to 18 (140 to 180) 33 to 42 (330 to 420) 50 to 62 (500 to 620) 63 to 77 (630 to 770)
– 11 –
16 (160), 18 (180)
42 (420) 55 (550) 65 (650)
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
air-water heat pump installation
No.
1
2
3
4 5 6
7 8
9
10
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
(Note 2) Charging cylinder for R410A is being currently developed.
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold Charge hose Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder Leakage detector Charging cylinder
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
Usage
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes Yes Yes
Yes
(Note 2)
R410A
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
× ×
× × ×
× ×
Conventional air-water
heat pump installation
Whether new equipment can be used with conventional refrigerant
¡
*(Note 1)
× ×
¡
¡
×
¡
×
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are neces­sary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11. Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
– 12 –
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor units gas side.
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
(For refrigerant charging, see the figure below.)
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(Water heat exchanger unit)
Opened
(Outdoor unit)
Refrigerant cylinder
(with siphon)
Check valve
Opened Open/close valve for charging
Electronic balance for refrigerant charging
Fig. 3-4-1 Configuration of refrigerant charging
Opened
Closed
Service port
– 13 –
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
Electronic
balance
Siphon
Fig. 3-4-2
1. Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2. When performing brazing again at time of servicing, use the same type of brazing filler.
3-5-2. Flux
3. Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1. Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
• In the brazing process, it prevents the metal surface from being oxidized.
• By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
– 14 –
2. Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temperature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
4. Piping materials for brazing and used brazing filler/flux
3-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m3/Hr or 0.02 MPa (0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7) Remove the flux completely after brazing.
Piping material
Copper - Copper
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver Silver
Used flux
Do not use
Paste flux
Vapor flux
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains within the pipe, the lubricating oil deterio­rates. Therefore, use a flux which does not contain chlorine.
3. When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
4. Remove the flux after brazing.
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Rubber plug
Fig. 3-5-1
Prevention of oxidation during brazing
Nitrogen gas
– 15 –

4. CONSTRUCTION VIEWS

4-1. Indoor Unit
RAS-M10SMUV-E, RAS-M13SMUV-E, RAS-M16SMUV-E RAS-M10SMUCV-E, RAS-M13SMUCV-E, RAS-M16SMUCV-E
200
1000 or more
15 or more
1000 or more
Obustacle
1000 or more
15 or more
Space required for
installation and servicing
149
175
207
64
Bottom face of ceiling
145.5
93
Knockout for flesh air intake 100 diam.
70
105
595 to 660 Ceiling open dimension
142 64 368.5
29
700 Panel external dimension
595 to 660 Ceiling open dimension
525 Hanging bolt pitch
Check port
( 450)
Check port
(o 450)
200
Check port
( 450)
Drain-up standing-up size
Indoor unit
627.5
or less
Stand-up
Bottom face of ceiling
Stand-up
850 or less
Note)
As ABS is used for the drain discharge port of the main unit, the vinyl chlor paste cannot be used.
595 to 660 Ceiling open dimension
Use the flexible hose (Band fix) included in the package.
Wireless remote controller Heat Pump : WH-H3UE Cooling only : WC-H2UE
63
18
Bottom face of ceiling
Ceiling panel
70
125
Drain discharge port
Hanging bolt M10 or W3/8 local arrange
26.5 63
58
5
Remote contollerRemote contoller holder
268 27
220.5
145.5 134
200
162
105235 235
162 diam.
For branch duct knockout square hole 150 diam.
Bottom face of ceiling
575 Unit external dimension
Electric parts box
575 Unit external dimension
331.5
320.5
– 16 –
162
diam.
256
177
700 Panel external dimension
595 to 660 Ceiling open dimension
Refrigerant pipe (Liquid) 6.4 diam.
Refrigerant pipe (Gas)
12.7 diam. RAS-M16SMUV-E RAS-M16SMUCV-E
9.5 diam. RAS-M10SMUV-E, M13SMUV-E RAS-M10SMUCV-E, M13SMUCV-E
214 105
97.5 42 148
139.5
190.5
Wiring connection port
55
9310570
For branch ductt knockout square hole 150 diam.
120
21
142
158
5-1. Indoor Unit

5. REFRIGERATING CYCLE DIAGRAM

Heating time Cooling time
Distributor
Indoor unit
(Strainer incorporated)
TC sensor
Refrigerant pipe at liquid side Outer diameter Ø6.4
RAS-M10SMUV-E, RAS-M10SMUCV-E RAS-M13SMUV-E, RAS-M13SMUCV-E RAS-M16SMUV-E, RAS-M16SMUCV-E
TCJ sensor
Air heat
exchanger
Refrigerant pipe at gas side Outer diameter A
To outdoor unitTo outdoor unit
Outer diameter A
Ø9.52 Ø9.52 Ø12.7
For the outdoor unit, refer to the Service Manual of the combined outdoor unit.
– 17 –

6. WIRING DIAGRAM

6-1. Indoor Unit
6-1-1. 4-way Air Discharge Cassette Type
5 5 4 4 3 3
LM2
2 2 1 1
5 5 4 4 3 3
LM1
2 2 1 1
Wireless unit
assembly
MCC-5053
FM
FS
5 5 4 4 3 3 2 2 1 1
CN202
(WHI)
1 1 2 2 3 3 4 4 5 5 6 6
CN34
(RED)
3 3 1 1
CN33 (WHI)
5 5 4 4 3 3 2 2 1 1
CN201
(BLU)
1 1 2 2 3 3 4 4 5 5 6 6
CN333
(WHI)
1 1 3 3 5 5
CN334
(WHI)
1 1
4 4 5 5
1 1 2 2
CN102
(RED)
TCJ
1 1 2 2
CN101
(BLK)
TC
TA
1 1 2 2
CN104
2
(YEL)
MCC-5056
Control P.C. Board for
Indoor Unit
DC20V DC15V DC12V DC 7 V
Power
supply circuit
Motor
drive circuit
+
~~
2 3
2 1
6 5 4 3 2 1
4 3 2 1
(HA)
CN64
(GRN)
CN60 (WHI)
CN08 (WHI)
Symbol
FM TA TC
TCJ
LM1, LM2
DP FS
Parts Name
Fan motor
Indoor temp. sensor
Temp. sensor Temp. sensor Louver motor
Drain pump motor
Float switch
RY700
1 3
CN68
1 3
(BLU)
DP
Color
Identification
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRN : GREEN
– 18 –
Fuse, F301
~
, T3.15A
250V
Indoor unit
earth screw
CN67 (BLK)
220 240V
1 3 1 355
WHIBLK BLKRED
1 2 3
1 2 3
~
220V ~, 60Hz
, 50Hz
P01
Outdoor unit
earth screw
7-1. Indoor Unit

7. SPECIFICATIONS OF ELECTRICAL PARTS

No.
1
Fan motor (for indoor)
2
Thermo. sensor (TA-sensor)
3
Heat exchanger sensor (TCJ-sensor)
4
Heat exchanger sensor (TC-sensor)
5
Float switch
6
Drain pump
Parts name
Type
SWF-230-60-1R
155 mm
Ø6 mm, 1500 mm
Ø6 mm, 1400 mm
FS-0218-103
ADP-1409
Specifications
Output (Rated) 60 W, 220–240 V
10 k at 25°C
10 k at 25°C
10 k at 25°C
– 19 –
8-1. Indoor Control Circuit

8. CONTROL BLOCK DIAGRAM

Indoor unit
Ceiling panel
Sensor display
P.C. board
(MCC-5053))
Louver
motor
Drain
pump
Indoor control P.C. board
(MCC-5056)
DC5V
DC12V
Driver
Outside output
Warning Ready
Thermo. ON
Cool/Heat Fan
CPU
EEPROM
TA sensor
TC sensor
CPU
TCJ sensor
Float input
Run
Indoor
fan motor
DC280V
220–240V,
220V, ~ 60Hz
~
50Hz
Fan motor
Power circuit
123
123
Outdoor unit
control
circuit
AC
synchronous
signal input circuit
Serial
send/receive
circuit
– 20 –

9. OPERATION DESCRIPTION

9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses DC motor for the indoor fan motor and the outdoor fan motor.
The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote controller, and transfers the operation command to the outdoor unit controller.
The outdoor unit controller receives operation com­mand from the indoor unit side, and controls the outdoor fan and the pulse motor valve. (P.M.V)
Besides, detecting revolution position of the compres­sor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inverter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command.
And then, the outdoor unit controller transfers reversely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inver ter to compressor is two-times cycles of the actual number of revolution.
1. Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
• Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor. (TA sensor)
• Judgment of the indoor heat exchanger tempera­ture by using heat exchanger sensor (TC sensor) (Prevent-freezing control, etc.)
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal (Serial signal) to the outdoor unit
• Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
2. Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor unit controller, the outdoor unit performs its role.
• Compressor operation control
• Operation control of outdoor fan motor
• P.M.V. control
• 4-way valve control
Operations followed to judgment
of serial signal from indoor side.
• Detection of inverter input current and current release operation
• Over-current detection and prevention operation to IGBT module (Compressor stop function)
• Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system)
• Transferring of operation information (Serial signal) from outdoor unit controller to indoor unit controller
• Detection of outdoor temperature and operation revolution control
• Defrost control in heating operation (Temp. measurement by outdoor heat exchanger and control for 4-way valve and outdoor fan)
3. Contents of operation command signal (Serial signal) from indoor unit controller to outdoor unit controller
The following three types of signals are sent from the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined
by indoor temperature and set temperature (Correction along with variation of room tempera­ture and correction of indoor heat exchanger temperature are added.)
• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger tem­perature), the outdoor unit controller monitors the input current to the inverter, and performs the followed operation within the range that current does not exceed the allowable value.
4. Contents of operation command signal (Serial signal) from outdoor unit controller to indoor unit controller
The following signals are sent from the outdoor unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transferring of these signals, the indoor unit controller monitors the contents of signals, and judges existence of trouble occurrence.
Contents of judgment are described below.
• Whether distinction of the current operation status meets to the operation command signal
• Whether protective circuit operates When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
– 21 –
9-2. Operation Description
9-2. 1. Basic operation....................................................................................................................... 23
1. Operation control............................................................................................................... 23
2. Operating mode selection when performing 2-room operation ......................................... 24
3. Cooling/Heating operation................................................................................................. 24
4. AUTO operation ................................................................................................................. 25
5. DRY operation ................................................................................................................... 25
2. Indoor fan motor control.......................................................................................................... 26
<In cooling operation> ............................................................................................................ 26
<In heating operation> (Heat pump model)............................................................................ 27
3. Release protective control by temperature of indoor heat exchanger.................................... 28
4. Dain pump control .................................................................................................................. 29
5. Over flow check control .......................................................................................................... 29
6. After-heat elimination.............................................................................................................. 29
7. Louver control ......................................................................................................................... 30
1) Louver position .................................................................................................................. 30
2) Cold draft preventive control .............................................................................................. 30
8. ECO operation ........................................................................................................................ 31
9. Hi power operation.................................................................................................................. 31
10. Temporar y operation............................................................................................................... 31
11. Forced operation stop switch.................................................................................................. 32
12. Indoor fan ON output .............................................................................................................. 33
13. Select switch on remote controller.......................................................................................... 34
14. Auto restar t function ............................................................................................................... 35
15. High ceiling select switch........................................................................................................ 35
16. Setting temperature correction switch .................................................................................... 36
9-3. Intermittent Operation Control for Indoor Fans of the Indoor Unit
at Thermo-off Side in Heating Operation...............................................................37
9-4. Remote Controller...................................................................................................38
9-4-1. Parts Name of Remote Controller ....................................................................................... 38
9-4-2. Names and Functions of Indications on Remote Controller ............................................ 39
– 22 –
Item
Operation flow and applicable data, etc.
Description
1. Basic operation
1. Operation control
Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as shown in the below.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives the control status with a serial signal.
6) The outdoor controller controls the operation as shown in the left, and also controls the compres­sor, outdoor fan motor, 4-way valve and pulse motor valve.
Selection of
operation conditions
ON/OFF
Remote controller
Control contents of remote controller
ON/OFF
Operation select (COOL/HEAT/AUTO/DRY)
Temperature setup
Air direction
Swing
Air volume select (AUTO/LOW/LOW+/MED/MED+/HIGH)
ECO
ON timer setup
OFF timer setup
High power
Signal receiving
Indoor unit control
Operation command
Serial signal send/receive
Serial signal send/receive
Outdoor unit control
Indoor unit
Indoor unit control
Command signal generating function of indoor unit operation
Calculation function (temperature calculation)
Activation compensation function of indoor fan
Cold draft preventive function
Timer function
Indoor heat exchanger release control
Outdoor unit
Outdoor unit control
Frequency control of inverter output
Waveform composite function
Calculation function
(Temperature calculation)
AD conversion function
Quick heating function
Delay function of compressor reactivation
Current release function
GTr over-current preventive function
Defrost operation function
Inverter
Indoor fan motor
Louver motor
~
Compressor
Outdoor fan motor
4-way valve
Pulse motor valve
(P.M.V.)
– 23 –
Item
Operation flow and applicable data, etc.
Description
1. Basic operation
2. Operating mode selection when performing 2-room operation
1) The outdoor unit operating mode conforms to the instructions of the indoor unit that was pressed first.
2) When combined operation consisting of cooling (dry) and heating, fan and heating, or cleaning operation and heating is performed, operation conforms to the instructions of the indoor unit that was pressed first as shown in the following table.
3) The indoor fan stops for the indoor unit that was pressed last and which instr uctions are ignored.
4) When three or four indoor units are operated concurrently, the priority is also given to operating mode of the indoor unit which was pressed first as same as the case when two indoor units are operated concurrently.
No.
1
2
3
4
Indoor unit
Pressed first Pressed last Pressed first Pressed last Pressed first Pressed last Pressed first Pressed last
Set operating mode
Cooling (dry) Cooling (dry)
Heating Heating
Cooling (dry)
Heating Heating
Cooling (dry)
Actual indoor unit operation
Cooling (dry) Cooling (dry)
Heating Heating
Cooling (dry)
Fan stopped
Heating
Fan stopped
Actual outdoor unit operation
Cooling
Heating
Cooling
Heating
3. Cooling/Heating operation
The operations are performed in the following parts by controls according to cooling/heating conditions.
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal starts being transferred from the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of “2. Indoor fan motor control” and the louver according to the contents of “9. Louver control”, respectively.
3) The outdoor unit controls the outdoor fan motor, compressor, pulse motor valve and 4-way valve according to the operation signal sent from the indoor unit.
*1. The power coupler of 4-way valve is usually turned off, and it is turned on during defrost
operation. (Only in heating)
Operation ON
Indoor unit control
Setup of remote controller
Indoor fan motor control / Louver control
Sending of operation command signal
Compressor revolution control / Outdoor fan motor control / 4-way valve control
Outdoor unit control
[In cooling operation: OFF, In heating operation: ON] Pulse motor valve control
– 24 –
Item
Operation flow and applicable data, etc.
Description
1. Basic operation
4. AUTO operation
Selection of operation mode As shown in the following figure, the operation starts by selecting automatically the status of room temperature (Ta) when starting AUTO operation.
Ta
Cooling operation
Ts + 1
Monitoring (Fan)
Ts – 1
Heating operation (Heat pump model) Fan only operation (Cooling-only model)
*1.When reselecting the operation mode, the fan speed
is controlled by the previous operation mode.
1) Detects the room temperature (Ta) when the operation started.
2) Selects an operation mode from Ta in the left figure.
3) Fan operation continues until an operation mode is selected.
4) When AUTO operation has started within 2 hours after heating operation stopped and if the room temperature is 20°C or more, the fan operation is performed with ”Super Ultra LOW” mode for 3 minutes. Then, select an operation mode.
5) If the status of compressor-OFF continues for 15 minutes the room temperature after selecting an operation mode (COOL/HEAT), reselect an operation mode.
5. DRY operation
DRY operation is performed according to the difference between room temperature and the setup temperature as shown below.
In DRY operation, fan speed is controlled in order to prevent lower ing of the room temperature and to avoid air flow from blowing directly to persons.
[˚C]
+
Ta
1.0
L– (W6)
(W6+W3) / 2
+
0.5
Tsc
SL (W3)
Fan speed
1) Detects the room temperature (Ta) when the DRY operation started.
2) Starts operation under conditions in the left figure according to the temperature difference between the room tempera­ture and the setup temperature (Tsc). Setup temperature (Tsc) = Set temperature on remote controller (Ts) + (0.0 to 1.0)
3) When the room temperature is lower 1°C or less than the setup temperature, turn off the compressor.
– 25 –
Item
Operation flow and applicable data, etc.
Description
2. Indoor fan motor control
COOL ON
Fan speed setup
AUTO
Ta
[˚C]
+2.5
a
+2.0
b
+1.5
c
+1.0
d
+0.5
e
Tsc
<In cooling operation>
(This operation controls the fan speed at indoor unit side.) The indoor fan (Turbo fan) is operated by DC motor.
The fan rotates in 5 stages in MANUAL mode, and in 5 stages in AUTO mode, respectively. (Table 1)
MANUAL
(Fig. 1)
Indication Fan speed
W6
(L + M) / 2
W9
(M + H) / 2
WC
(Fig. 2)
L L+ M M+ H
Air volume AUTO
M+(WB)
*3 *4 *5
L(W6)
*3 :Fan speed = (M + –L) x 3/4 + L *4 :Fan speed = (M + –L) x 2/4 + L *5 :Fan speed = (M + –L) x 1/4 + L
(Linear approximation from M+ and L)
* Symbols
UH : Ultra High H : High M+ : Medium+ M : Medium L+ : Low+ L : Low L- : Low– UL : Ultra Low SUL : Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc. The described value indicates one under condition of inclining downward blowing.
1) When setting the fan speed to L, L+, M, M+ or H on the remote controller, the operation is performed with the constant speed shown in Fig. 1.
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level shown in Fig. 2 and Table 1 according to the setup tempera­ture, room temperature, and heat exchanger temperature.
Fan speed
level
WF WE WD WC WB WA W9 W8 W7 W6 W5 W4 W3 W2 W1
Fan speed
level
WF WE WD WC WB WA W9 W8 W7 W6 W5 W4 W3 W2 W1
COOL
FAN
ONLY
UH
H
M+
M
L+
L
L–
UL SL
(Table 1) Indoor fan air flow rate (Cool/Dry/Fan only)
DRY
L– UL
SL
RAS-M10SMUV-E
RAS-M10SMUCV-E
Fan speed Air flow rate
(rpm) (m
650 590 650 590 650 590 630 570 600 540 570 500 550 480 530 460 500 430 480 410 450 380 370 290 350 270 350 270 350 270
3
/h)
RAS-M13SMUV-E
RAS-M13SMUCV-E
Fan speed Air flow rate
(rpm) (m
680 620 680 620 680 620 630 570 600 540 590 530 550 480 530 460 500 430 480 410 450 380 370 290 350 270 350 270 350 270
(Table 2) Indoor fan air flow rate (Heat)
HEAT
UH
H
M+
M
L+
L
L–
UL
SL
RAS-M10SMUV-E
Fan speed Air flow rate
(rpm) (m
700 640 650 590 640 580 620 560 600 540 570 500 550 480 520 450 500 430 450 380 440 370 420 350 400 330 370 290 350 270
3
/h)
RAS-M13SMUV-E
Fan speed Air flow rate
(rpm) (m
730 670 680 620 640 580 620 560 600 540 590 530 560 490
530 460
500 430 450 380 440 370 420 350 400 330 370 290 350 270
RAS-M16SMUV-E
RAS-M16SMUCV-E
3
/h)
3
/h)
Fan speed Air flow rate
(rpm) (m
720 660 720 660 720 660 680 620 650 590 630 570 600 540 550 480 520 450 500 430 450 380 370 290 350 270 350 270 350 270
RAS-M16SMUV-E
Fan speed Air flow rate
(rpm) (m
750 690 720 660 690 630 670 610 650 590 630 570 600 540 550 480 520 450 470 400 450 380 420 350 400 330 370 290 350 270
3
/h)
3
/h)
– 26 –
Loading...
+ 60 hidden pages