(1,1 to 3,2)(1,65 to 4,99)(255 to 930)
(1,1 to 4,2)(1,65 to 7,25)(255 to 1430)
(1,4 to 6,1)(1,68 to 10,29)(260 to 2150)
(1,4 to 6,2)(1,68 to 10,38)(260 to 2170)
(1,1 to 3,2)(1,59 to 4,78)(255 to 930)
(1,1 to 4,2)(1,59 to 6,94)(255 to 1430)
(1,4 to 6,1)(1,62 to 9,84)(260 to 2150)
(1,4 to 6.2)(1,62 to 9,93)(260 to 2170)
(1,1 to 3,2)(1,52 to 4,58)(255 to 930)
(1,1 to 4,2)(1,52 to 6,65)(255 to 1430)
(1,4 to 6,1)(1,55 to 9,43)(260 to 2150)
(1,4 to 6,2)(1,55 to 9,52)(260 to 2170)
(0,7 to 5,2)(1,10 to 8,13)(170 to 1700)
(0,7 to 6,5)(1,10 to 12,11)(170 to 2530)
(0,9 to 8,3)(1,10 to 11,43)(170 to 2390)
(0,9 to 8,7)(1,10 to 11,72)(170 to 2450)
(0,7 to 5,2)(1,06 to 7,78)(170 to 1700)
(0,7 to 6,5)(1,06 to 11,58)(170 to 2530)
(0,9 to 8,3)(1,06 to 10,94)(170 to 2390)
(0,9 to 8,7)(1,06 to 11,21)(170 to 2450)
(0,7 to 5,2)(1,01 to 7,46)(170 to 1700)
(0,7 to 6,5)(1,01 to 11,10)(170 to 2530)
(0,9 to 8,3)(1,01 to 10,48)(170 to 2390)
(0,9 to 8,7)(1,01 to 10,75)(170 to 2450)
operating noise
• The above specification values are those under the conditions
Cooling indoor : DB/WB=27/19°CCooling outdoor : DB=35°C
Outdoor : DB 35˚C
Air flow : High
Pipe length : 5m x 2
2 units operating
230V
0
10
020 30405060 708090 100020406080100120140
12
10
8
6
Current (A)
4
2
0
• Conditions
Indoor : DB 20˚C
Outdoor : DB 7˚C/WB 6˚C
Air flow : High
Pipe length : 5m x 2
2 units operating
230V
Compressor speed (rps)Compressor speed (rps)
1-2-2. Cooling Capacity Variation Ratio According to Temperature
105115
• Conditions
Indoor : DB27˚C
110
Outdoor : DB35˚C
Indoor air flow : High
Pipe length 5m×2
105
2 units operating
100
95
Capacity ratio (%)
90
85
0
100
95
90
85
80
75
70
Capacity ratio (%)
65
60
55
50
3234
Current Limited Start
• Conditions
Indoor : DB27˚C/WB19˚C
Indoor air flow : High
Pipe length 5m×2
2 units operating
36384042333537394143141618202224
– 6 –
Outdoor temp. (˚C)Indoor air wet bulb temp. (˚C)
* Capacity ratio : 100% = 5,2 kW
1-3. Electrical Data
<Cooling>
Combination
of indoor unit
operation
AB
10—
13—
1010
1310
<Heating>
Combination
of indoor unit
operation
AB
10—
System
Voltage rangePower supply
Volts-
Hz
50230–1198264
Hz
Ph.
Volts-
Ph.
Min.Max.MCAICF
System
Voltage rangePower supply
Min.Max.MCAICF
MOCP
(Amps)
5,81 5,8115
8,51 8,5115
12,1012,1015
12,2112,2115
MOCP
(Amps)
9,56 9,5615
CompressorFan motor FLA
MSCRLAIndoorOutdoor
4,134,130,15 x 1=0,150,50
6,296,290,15 x 1=0,150,50
9,049,040,15 x 2=0,300,50
9,139,130,15 x 2=0,300,50
CompressorFan motor FLA
MSCRLAIndoorOutdoor
7,13 7,130,15 x 1=0,150,50
13—
50230–1198264
1010
1310
14,3114,3115
13,4713,4715
13,8113,8115
NOTE :
Model of Indoor unit :
10 : RAS-M10YKV-E, RAS-M10YKCV-E
13 : RAS-M13YKV-E, RAS-M13YKCV-E
MCA: Minimum Circuit Amps.
ICF: Maximum Instantaneous Current Flow
(Equivalent to MCA in case of inv erter air conditioner)
MOCP : Maximum Overcurrent Protection (Fuse only)
MSC: Maximum Starting Current
FLA: Full Load Amps.
RLA: Rated Load Amps. RLA under conditions on the right.
10,9310,930,15 x 1=0,150,50
10,1410,140,15 x 2=0,300,50
10,4110,410,15 x 2=0,300,50
<Cooling>
DBWB
Indoor temp.°C2719
Outdoor temp.°C35—
<Heating>
DBWB
Indoor temp.°C20—
Outdoor temp.°C 76
– 7 –
2. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone lay er.
The working pressure of the new refrigerant R410A
is 1,6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water , dust, and e xisting refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conf orming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
2-1. Safety During Installation/Servicing
As R410A’s pressure is about 1,6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc.
by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive f or the refrigerant
R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully .
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur .
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the
refrigeration cycle. Otherwise , pressure in the
refrigeration cycle may become abnormally high
so that a rupture or personal injury may be
caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks , its concentration
does not exceed the marginal lev el.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal le v el, an
oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage , electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair’s ma y result in water leakage ,
electric shock and fire, etc.
2-2. Refrigerant Piping Installation
2-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant must be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion v alv e or capillary tube
may become bloc ked with contaminants.
As an air conditioner using R410A incurs
pressure higher than when using R22, it is
necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 2-2-1. Never use copper
pipes thinner than 0,8 mm even when it is
availab le on the market.
– 8 –
T a ble 2-2-1 Thicknesses of annealed copper pipes
For copper pipes, flare joints or soc ket joints are
used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes
cannot be used for pipings whose outer
diameter exceeds 20 mm. In such a case,
socket joints can be used.
Sizes of flare pipe ends, flare joint ends and
flare nuts are as shown in T ables 2-2-3 ~ 2-26 below.
Socket joints are such that the y are braz ed
for connections, and used mainly f or thic k
pipings whose diameter is larger than 20 mm.
Thicknesses of sock et joints are as shown in
T ab le 2-2-2.
5/815,880,80
2-2-2. Processing of Piping Materials
When performing the refrigerant piping installation,
care should be taken to ensure that water or dust
does not enter the pipe interior, that no other oil
other than lubricating oils used in the installed air
conditioner is used, and that refrigerant does not
leak. When using lubricating oils in the piping
processing, use such lubricating oils whose water
content has been removed. When stored, be sure to
seal the container with an airtight cap or any other
cover .
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slo wly cut the pipe
so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs,
refrigerant leakage may occur. Carefully
remove all b urrs and clean the cut surface
before installation.
– 9 –
c) Insertion of Flare Nut
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perform the flare
processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Table 2-2-3 Dimensions related to flare processing for R410A
Flare processing dimensions differ according
to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
ØD
A
Fig. 2-2-1 Flare processing dimensions
Nominal
diameter
Outer
diameter
(mm)
1/4 6,350,8
3/8 9,520,8
1/212,700,8
5/815,881,0
T a ble 2-2-4 Dimensions related to flare processing for R22
Nominal
diameter
Outer
diameter
(mm)
1/4 6,350, 8
3/8 9,520, 8
1/212,700,8
Thickness
(mm)
Thickness
(mm)
A (mm)
Flare tool for
R410A clutch type
Conventional flare tool
Clutch typeWing nut type
0 to 0,51,0 to 1,51,5 to 2,0
0 to 0,51,0 to 1,51,5 to 2,0
0 to 0,51,0 to 1,52,0 to 2,5
0 to 0,51,0 to 1,52,0 to 2,5
A (mm)
Flare tool for
R22 clutch type
Conventional flare tool
Clutch typeWing nut type
0 to 0,50,5 to 1,01,0 to 1,5
0 to 0,50,5 to 1,01,0 to 1,5
0 to 0,50,5 to 1,01,5 to 2,0
5/815,881,0
Table 2-2-5 Flare and flare nut dimensions for R410A
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening
torque for R410A is the same as that for
conventional R22. Incidentally, when the
torque is weak, the gas leakage may occur .
T a ble 2-2-7 Tightening torque of flare for R410A [Reference values]
NominalOuter diameterTightening torque
diameter(mm)N•m (kgf•cm)
1/4 6,3514 to 18 (140 to 180)16 (160), 18 (180)
When it is strong, the flare nut may cra c k and
may be made non-remov abl e. When choosing the tightening torque, comply with values
designated by manufacturers . Table 2-2-7
shows reference values.
Note:
When applying oil to the flare surface, be sure to use
oil designated by the manufacturer. If any other oil is
used, the lubricating oils may deteriorate and cause
the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
3/8 9,5233 to 42 (330 to 420)42 (420)
1/212,7050 to 62 (500 to 620)55 (550)
5/815,8863 to 77 (630 to 770)65 (650)
– 11 –
2-3. Tools
2-3-1. Required Tools
The service port diameter of packed v alve of the outdoor unit in the air conditioner using R410A is changed to pre vent
mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side
dimension of flare nut (For Ø12,7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge ,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the f ollo wing three types.
(1) Tools exclusive f or R410A (Those which cannot be used f or conventional refrigerant (R22))
(2) Tools exclusive f or R410A, b ut can be also used for conventional refrigerant (R22)
(3) Tools commonly used for R410A and for con v entional refrigerant (R22)
The table below shows the tools e xclusiv e for R410A and their interchangeability .
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
When the compound gauge’s pointer has indicated
–0,1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Connect the charge hose of the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
Never charge refrigerant e xceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally
high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 13 –
(OUTDOOR unit)
Opened
Closed
Service port
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ][ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and
the characteristics of the equipment varies.
2-5. Brazing of Pipes
2-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper . It is used to join iron,
copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
Fig. 2-4-2
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas leakage. Therefore, use any other type of brazing
filler at a hot spring resort, etc., and coat the
surface with a paint.
When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux
(1) Reason why flux is necessary
• By removing the oxide film and any foreign
matter on the metal surface, it assists the flo w
of brazing filler .
• In the brazing process, it prevents the metal
surface from being o xidized.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 14 –
(2) Characteristics required for flux
• Activated temperature of flux coincides with
the brazing temperature.
• Due to a wide effective temper ature range,
flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is
harmless to the human body .
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric
acid.
It is effective in case where the br azing
temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used f or silv er br azing
are this type.
It features an increased oxide film remo ving
capability due to the addition of compounds
such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric
acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
2-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prev ent the o xide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow .
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
Use a copper pipe to direct the piping
material, and attach a flow-meter to the
cylinder.
Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent bac kflo w of the
Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open.
Adjust the flow rate of Nitrogen gas so that it
is lower than 0,05 m3/Hr or 0,02 MPa (0,2kgf/
cm2) by means of the reducing valve .
After performing the steps above , keep the
Nitrogen gas flowing until the pipe cools
down to a certain extent (temperature at
which pipes are touchable with hands).
Remove the flux completely after brazing.
Piping
material
Copper - Copper
Copper - Iron
Iron - Iron
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not
contain chlorine.
When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange w ater).
Table 4-1-1 Simple check points for diagnosing faults
Diagnosis result
Check to see if the OPERATION indicator goes on and off when the main
switch or breaker is turned on, or the power cord is plugged in the wall
outlet. (Check the primary and secondary voltage of transformer.)
Check for power supply voltage between – . (Refer to the name
plate.) (Check the primary and secondary voltage of transformer.)
Check for fluctuate voltage between – . (DC 15 to 60V)
Check to determine if the fuse is open.
(Check Varistor : R109, R21)
Check for voltage at the pink lead of the infrared rays receive parts.
(Check the transformer and the rated voltage power supply circuit.)
Check for voltage at the lead of louver motor.
(Check the transformer and the rated voltage power supply circuit.)
Check for voltage at the CN10 connector side point.
(Check the transformer and the rated voltage power supply circuit.)
Deoxidized copper pipe
Both A and B rooms
Outer dia. : 6,35mm
Thickness : 0,8mm
Sectional shape
of heat insulator
Muffler
Ø25 x 80
TGa
Muffler
Ø25 x 80
Muffler
Ø25 x 160
TD
Compressor
DA130A1F-21F
Outdoor heat
exchanger
Split capillary
Strainer
Ø1,5 x 200
Allowable height
difference : 10m
Strainer
Capillary
Ø2,2 x 200
Pulse modulating
valve at liquid side
(SEV15RC2)
Per 1 unit
Max. : 20m
Total : 30m
Allowable pipe length
Temp. measurement
T
2
Propeller fan
OUTDOOR UNIT
Ø1,5 x 200
TE
NOTE :
Refrigerant amount : 1,15kg
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
T able 6-1-1
Each length in one room
Total length in two rooms
Unnecessary to add refrigerant
A roomB room
(Standard) 10 m5 m5 mDo not add the refrigerant
(Maximum) 30 m20 (10) m10 (20) mDo not add the refrigerant
NOTE :
• The maximum pipe length of this air conditioner is 30 m. The additional charging of refrigerant is unnecessary because this air conditioner is designed with charge-less specification.
• To connect only one indoor unit, use connecting pipe with length by 5m or more.
– 22 –
RAS-M10YKCV-E, RAS-M13YKCV-E
RAS-M18YACV-E
To B room
INDOOR UNIT
Indoor heat
exchanger
T1
Temp. measurement
To B room
P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Both A and B rooms
Outer dia. : 9,52mm
Thickness : 0,8mm
Muffler
Ø25 x 80
Accumulating tank
Ø51 x 200
(290cc)
TS
Muffler
Ø25 x 80
Outdoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Both A and B rooms
Outer dia. : 6,35mm
Thickness : 0,8mm
Sectional shape
of heat insulator
TGa
TD
Compressor
DA130A1F-21F
Split capillary
Ø1,5 x 200
Allowable height
difference : 10m
Strainer
Capillary
Ø2,2 x 200
Pulse modulating
valve at liquid side
(SEV15RC2)
Per 1 unit
Max. : 20m
Total : 30m
Allowable pipe length
Temp. measurement
T
2
Propeller fan
OUTDOOR UNIT
Ø1,5 x 200
TE
NOTE :
Refrigerant amount : 1,15kg
Gas leak check position
Refrigerant flow
T able 6-1-2
Each length in one room
Total length in two rooms
Unnecessary to add refrigerant
A roomB room
(Standard) 10 m5 m5 mDo not add the refrigerant
(Maximum) 30 m20 (10) m10 (20) mDo not add the refrigerant
NOTE :
• The maximum pipe length of this air conditioner is 30 m. The additional charging of refrigerant is unnecessary because this air conditioner is designed with charge-less specification.
– 23 –
6-2. Operation Data
<Cooling>
Temperature
condition (°C)
Indoor Outdoor
27/1935/–
<Heating>
Temperature
condition (°C)
Indoor Outdoor
20/–7/6
No. of
operating
units
1 unit
2 units
No. of
operating
units
1 unit
2 units
Operating combination
(Unit)
AB
M13YKCV -E
M13YKV -E
M10YKCV -E
M10YKV -E
M13YKCV -E M10YKCV -E
M13YKV -EM10YKV-E
M10YKCV -E M10YKCV -E
M10YKV -EM10YKV-E
Operating combination
(Unit)
AB
M13YKV-E3,5 to 3,7
M10YKV-E 3,3 to 3,5
M13YKV-E M10YKV-E 2,5 to 2,7
M10YKV-E M10YKV-E 2,5 to 2,7
Standard
pressure
P (MPa)
0,7 to 0,9
0,9 to 1,1
0,8 to 1,0
0,8 to 1,0
Standard
pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C)T2 (°C)
9 to 11 46 to 48HighHigh62
11 to 13 45 to 47HighMED.38
11 to 13 50 to 52HighHigh74
10 to 12 50 to 52HighHigh74
Heat exchanger
pipe temp.
T1 (°C)T2 (°C)
53 to 55 0 to 2HighHigh79
48 to 50 0 to 2HighMED.63
41 to 43–2 to 0HighHigh9 7
41 to 43–2 to 0HighHigh9 7
Indoor Outdoor Compressor
fanfanrevolution
modemode(rps)
Indoor Outdoor Compressor
fanfanrevolution
modemode(rps)
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat e xchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m x 2 units
– 24 –
7-1. Indoor Unit
Heat Exchanger Sensor
Temperature Sensor
Infrared Rays Signal Receiver
7. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U
Functions
• Louver Control
• 3-minute Delay at Restart for Compressor
Operation
Display
Timer
Display
Infrared
Initializing Circuit
Rays
Clock Frequency
Oscillator Circuit
Remote
Control
From Outdoor Unit
REMOTE CONTROL
RAS-M10YKV-E, RAS-M13YKV-E
(Heat pump model)
Power Supply
Circuit
Noise Filter
• Motor Revolution Control
• Processing
(Temperature Processing)
• Timer
• Serial Signal Communication
Louver ON/OFF Signal
Serial Signal Transmitter/Receiver
Serial Signal Communication
RAS-M10YKCV-E, RAS-M13YKCV-E
Infrared
Rays
Louver Driver
(Cooling only model)
ECONO.
Sign Display
FAN-ONLY
Sign Display
Indoor
Fan Motor
Louver
Motor
Infrared
Rays
Remote Control
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECONO.
Remote Control
Operation (START/STOP)
Operation Mode Selection