Toshiba RAS-M10YKV-E, RAS-M10YKCV-E, RAS-M18YAV-E, RAS-M18YACV-E SERVICE MANUAL

SERVICE MANUAL
AIR-CONDITIONER
FILE NO. A00-9906
SUPPLEMENT
SPLIT TYPE
RAS-M10YKV-E, RAS-M13YKV-E
RAS-M18YAV-E
R AS-M10YKCV-E, RAS-M13YKCV-E
RAS-M18YACV-E
/
R410A
PRINTED IN JAPAN, Nov.,1999 ToMo
CONTENTS
1. SPECIFICATIONS ...................................................................................... 3
2. REFRIGERANT R410A .............................................................................. 8
3. CONSTRUCTION VIEWS......................................................................... 16
4. WIRING DIA GRAM................................................................................... 18
5. SPECIFICATIONS OF ELECTRICAL PARTS.......................................... 21
6. REFRIGERANT CYCLE DIAGRAM......................................................... 22
7. CONTROL BLOCK DIA GRAM................................................................. 25
8. OPERATION DESCRIPTION ................................................................... 28
9. INSTALLATION PROCEDURE ................................................................ 41
10. HOW T O DIAGNOSE THE TROUBLE ...................................................... 49
11. HOW TO REPLACE THE MAIN PARTS ................................................... 69
12. EXPLODED VIEWS AND PARTS LIST.................................................... 80
– 2 –

1. SPECIFICATIONS

1-1. Specifications
RAS-M10YKV-E, RAS-M13YKV-E / RAS-M18YAV-E
Unit model Indoor Current limited
Cooling capacity (kW) Cooling capacity range (kW) Heating capacity (kW) Heating capacity range (kW) Power supply Electric Indoor Unit model characteristics
COP (Cooling/Heating) Operating noise Indoor Unit model
Indoor unit Unit model
Outdoor unit Unit model
Piping connection Type
Refrigerant Name of refrigerant Wiring connection Power supply Usable temperature range Indoor (Cooling/Heating) (°C) Accessory Indoor unit Installation plate
Outdoor
Running current (A) Power consumption (W) Power factor (%)
Outdoor Unit model
Operation mode Running current (A) Power consumption (W) Power factor (%) Starting current (A)
High (dB•A) Medium (dB•A) Low (dB•A)
Outdoor Unit model
10-1 indoor unit operating (dB•A) 13-1 indoor unit operating (dB•A) 2 indoor unit operating (dB•A)
Dimension Height (mm)
Width (mm)
Depth (mm) Net weight (kg) Fan motor output (W) Air flow rate (Cooling/Heating) (m3/h)
Dimension Height (mm)
Width (mm)
Depth (mm) Net weight (kg) Compressor Motor output (W)
Type
Model Fan motor output (W) Air flow rate (m3/h)
Indoor unit Unit model
Liquid side
Gas side Outdoor unit Unit model
A unit liquid side/gas side
B unit liquid side/gas side Maximum length (per unit) (m) Maximum length (total) (m) Maximum chargeless length (m) Maximum height difference (m)
Weight (kg)
Interconnection
Outdoor (Cooling/Heating) (°C)
Wireless remote control
Label
Remote control holder
Pan head wood screw
Purifying filter
Deodorizing filter
Batteries
Mounting screw
Installation manual Outdoor unit Installation manual
Owner's manual
RAS-M10YKV-E (Cooling / Heating) RAS-M13YKV-E (Cooling / Heating)
Twin rotar y type with DC-inverter variable speed control
• For performance when each indoor unit is combined with other unit, ref er to the separate table .
• The specifications may be subject to change without notice f or purpose of improv ement.
RAS-M10YKV-E, RAS-M13YKV-E
RAS-M18YAV-E
5,2
1,4 – 6,2
6,7
0,9 – 8,7
220 – 230 – 240V – 1Ph – 50 Hz
RAS-M10YKV-E RAS-M13YKV-E
0,15 0,15
30 30 87 87
RAS-M18YAV-E
Cooling Heating
7,90 / 7,57 / 7,28 8,55 / 8,17 / 7,81
1660 1790
95% 95%
9,86 / 9,43 / 9,04
3,02 / 3,62
36 / 39 39 / 40 33 / 35 35 / 35 30 / 30 30 / 30
RAS-M18YAV-E (Cooling / Heating)
42 / 45 46 / 49 46 / 49
RAS-M10YKV-E RAS-M13YKV-E
265 265 790 790 189 189
88
19 19
470 / 520 520 / 560
RAS-M18YAV-E
550 780 270
44
1100
DA130A1F-21F
40
2060
Flare connection
RAS-M10YKV-E RAS-M13YKV-E
Ø6,35 Ø6,35 Ø9,52 Ø9,52
RAS-M18YAV-E
Ø6,35 / Ø9,52 Ø6,35 / Ø9,52
20 30 30 10
R410A
1,15 3 Wires : includes earth 4 Wires : includes earth
21 – 32 / 0 – 28
21 – 43 / –5 – 21
1 1 2 1
2 (Ø3,1 x 16L)
1 1 2
6 (Ø4 x 25L)
1 1 1
– 3 –
RAS-M10YKCV-E, RAS-M13YKCV-E / RAS-M18YACV-E
Unit model Indoor Cooling capacity (kW)
Cooling capacity range (kW) Power supply Electric Indoor Unit model
characteristics
COP Operating noise Indoor Unit model
Indoor unit Unit model
Outdoor unit Unit model
Piping connection Type
Refrigerant Name of refrigerant Wiring connection Power supply Usable temperature range Indoor (°C) Accessory Indoor unit Installation plate
Outdoor
Running current (A) Power consumption (W) Power factor (%)
Outdoor Unit model
Running current (A) Power consumption (W) Power factor (%) Starting current (A)
High (dB•A) Medium (dB•A) Low (dB•A)
Outdoor Unit model
10-1 indoor unit operating (dB•A) 13-1 indoor unit operating (dB•A) 2 indoor unit operating (dB•A)
Dimension Height (mm)
Width (mm)
Depth (mm) Net weight (kg) Fan motor output (W) Air flow rate (m3/h)
Dimension Height (mm)
Width (mm)
Depth (mm) Net weight (kg) Compressor Motor output (W)
Type
Model Fan motor output (W) Air flow rate (m3/h)
Indoor unit Unit model
Liquid side
Gas side Outdoor unit Unit model
A unit liquid side/gas side
B unit liquid side/gas side Maximum length (per unit) (m) Maximum length (total) (m) Maximum chargeless length (m) Maximum height difference (m)
Weight (kg)
Interconnection
Outdoor (°C)
Wireless remote control
Label
Remote control holder
Pan head wood screw
Purifying filter
Deodorizing filter
Batteries
Mounting screw
Installation manual Outdoor unit Installation manual
Owner's manual
RAS-M10YKCV-E, RAS-M13YKCV-E
RAS-M18YACV-E
5,2
1,4 – 6,2
220 – 230 – 240V – 1Ph – 50 Hz
RAS-M10YKCV-E RAS-M13YKCV-E
0,15 0,15
30 30 87 87
RAS-M18YACV-E
7,90 / 7,57 / 7,28
1660
95%
8,20 / 7,87 / 7,58
3,02
RAS-M10YKCV-E RAS-M13YKCV-E
36 39 33 35 30 30
RAS-M18YACV-E
42 46 46
RAS-M10YKCV-E RAS-M13YKCV-E
265 265 790 790 189 189
88
19 19
470 520
RAS-M18YACV-E
550 780 270
42
1100
Twin rotar y type with DC-inverter variable speed control
DA130A1F-21F
40
2060
Flare connection
RAS-M10YKCV-E RAS-M13YKCV-E
Ø6,35 Ø6,35 Ø9,52 Ø9,52
RAS-M18YACV-E
Ø6,35 / Ø9,52 Ø6,35 / Ø9,52
20 30 30 10
R410A
1,15 3 Wires : includes earth 4 Wires : includes earth
21 – 32 21 – 43
1 1 2 1
2 (Ø3,1 x 16L)
1 1 2
6 (Ø4 x 25L)
1 1 1
• For performance when each indoor unit is combined with other unit, ref er to the separate table .
• The specifications may be subject to change without notice f or purpose of improv ement.
– 4 –
1-2. Specifications of Performance When Each Indoor Unit is Combined with Other Unit
<Cooling>
Volts
V
220
230
240
Operation
status
1 unit
2 units
1 unit
2 units
1 unit
2 units
Operating Unit capacity Cooling Running Power Outdoor
indoor unit (kW) capacity current consumption
ABAB kW A W dB
10 2,7 2,7 4,13 770 42 13 3,7 3,7 6,58 1240 46 10 10 2,55 2,55 5,1 8,14 1700 46 13 10 3,01 2,19 5,2 8,20 1720 46 10 2,7 2,7 3,95 770 42 13 3,7 3,7 6,30 1240 46 10 10 2,55 2,55 5,1 7,78 1700 46 13 10 3,01 2,19 5,2 7,87 1720 46 10 2,7 2,7 3,79 770 42 13 3,7 3,7 6,03 1240 46 10 10 2,55 2,55 5,1 7,46 1700 46 13 10 3,01 2,19 5,2 7,58 1720 46
(1,1 to 3,2) (1,65 to 4,99) (255 to 930) (1,1 to 4,2) (1,65 to 7,25) (255 to 1430) (1,4 to 6,1) (1,68 to 10,29) (260 to 2150) (1,4 to 6,2) (1,68 to 10,38) (260 to 2170) (1,1 to 3,2) (1,59 to 4,78) (255 to 930) (1,1 to 4,2) (1,59 to 6,94) (255 to 1430) (1,4 to 6,1) (1,62 to 9,84) (260 to 2150) (1,4 to 6.2) (1,62 to 9,93) (260 to 2170) (1,1 to 3,2) (1,52 to 4,58) (255 to 930) (1,1 to 4,2) (1,52 to 6,65) (255 to 1430) (1,4 to 6,1) (1,55 to 9,43) (260 to 2150) (1,4 to 6,2) (1,55 to 9,52) (260 to 2170)
operating noise
<Heating>
Volts
Operation
V
220
230
240
status
1 unit
2 units
1 unit
2 units
1 unit
2 units
Operating Unit capacity Heating Running Power Outdoor
indoor unit (kW) capacity current consumption
ABAB kW A W dB
10 4,0 4,0 6,94 1450 45 13 5,0 5,0 9,86 2060 49 10 10 3,2 3,2 6,4 8,47 1770 49 13 10 3,72 2,98 6,7 8,85 1850 49 10 4,0 4,0 6,64 1450 45 13 5,0 5,0 9,43 2060 49 10 10 3,2 3,2 6,4 8,10 1770 49 13 10 3,72 2,98 6,7 8,47 1850 49 10 4,0 4,0 6,36 1450 45 13 5,0 5,0 9,04 2060 49 10 10 3,2 3,2 6,4 7,76 1770 49 13 10 3,72 2,98 6,7 8,11 1850 49
(0,7 to 5,2) (1,10 to 8,13) (170 to 1700) (0,7 to 6,5) (1,10 to 12,11) (170 to 2530) (0,9 to 8,3) (1,10 to 11,43) (170 to 2390) (0,9 to 8,7) (1,10 to 11,72) (170 to 2450) (0,7 to 5,2) (1,06 to 7,78) (170 to 1700) (0,7 to 6,5) (1,06 to 11,58) (170 to 2530) (0,9 to 8,3) (1,06 to 10,94) (170 to 2390) (0,9 to 8,7) (1,06 to 11,21) (170 to 2450) (0,7 to 5,2) (1,01 to 7,46) (170 to 1700) (0,7 to 6,5) (1,01 to 11,10) (170 to 2530) (0,9 to 8,3) (1,01 to 10,48) (170 to 2390) (0,9 to 8,7) (1,01 to 10,75) (170 to 2450)
operating noise
• The above specification values are those under the conditions Cooling indoor : DB/WB=27/19°C Cooling outdoor : DB=35°C
Heating indoor : DB=20°C Heating outdoor : DB/WB=7/6°C
– 5 –
1-2-1. Operation Characteristic Curve
<Cooling> <Heating>
10
9
8
7
6
5
Current (A)
4
3
• Conditions Indoor : DB 27˚C/WB 19˚C
2
1
Outdoor : DB 35˚C Air flow : High Pipe length : 5m x 2 2 units operating 230V
0
10
0 20 30 40 50 60 70 80 90 100 0 20 40 60 80 100 120 140
12
10
8
6
Current (A)
4
2
0
• Conditions Indoor : DB 20˚C Outdoor : DB 7˚C/WB 6˚C Air flow : High Pipe length : 5m x 2 2 units operating 230V
Compressor speed (rps) Compressor speed (rps)
1-2-2. Cooling Capacity Variation Ratio According to Temperature
105115
• Conditions Indoor : DB27˚C
110
Outdoor : DB35˚C Indoor air flow : High Pipe length 5m×2
105
2 units operating
100
95
Capacity ratio (%)
90
85
0
100
95 90 85 80 75 70
Capacity ratio (%)
65 60 55 50
32 34
Current Limited Start
• Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length 5m×2 2 units operating
36 38 40 4233 35 37 39 41 4314 16 18 20 22 24
– 6 –
Outdoor temp. (˚C)Indoor air wet bulb temp. (˚C)
* Capacity ratio : 100% = 5,2 kW
1-3. Electrical Data
<Cooling>
Combination
of indoor unit
operation
AB
10 — 13 — 10 10 13 10
<Heating>
Combination
of indoor unit
operation
AB
10
System
Voltage range Power supply
Volts-
Hz
50 230–1 198 264
Hz
Ph.
Volts-
Ph.
Min. Max. MCA ICF
System
Voltage range Power supply
Min. Max. MCA ICF
MOCP
(Amps)
5,81 5,81 15 8,51 8,51 15 12,10 12,10 15 12,21 12,21 15
MOCP
(Amps)
9,56 9,56 15
Compressor Fan motor FLA
MSC RLA Indoor Outdoor
4,13 4,13 0,15 x 1=0,15 0,50 6,29 6,29 0,15 x 1=0,15 0,50 9,04 9,04 0,15 x 2=0,30 0,50 9,13 9,13 0,15 x 2=0,30 0,50
Compressor Fan motor FLA
MSC RLA Indoor Outdoor
7,13 7,13 0,15 x 1=0,15 0,50
13
50 230–1 198 264
10 10 13 10
14,31 14,31 15 13,47 13,47 15 13,81 13,81 15
NOTE :
Model of Indoor unit :
10 : RAS-M10YKV-E, RAS-M10YKCV-E
13 : RAS-M13YKV-E, RAS-M13YKCV-E MCA : Minimum Circuit Amps. ICF : Maximum Instantaneous Current Flow
(Equivalent to MCA in case of inv erter air conditioner) MOCP : Maximum Overcurrent Protection (Fuse only) MSC : Maximum Starting Current FLA : Full Load Amps. RLA : Rated Load Amps. RLA under conditions on the right.
10,93 10,93 0,15 x 1=0,15 0,50 10,14 10,14 0,15 x 2=0,30 0,50 10,41 10,41 0,15 x 2=0,30 0,50
<Cooling>
DB WB
Indoor temp. °C 27 19 Outdoor temp. °C 35
<Heating>
DB WB
Indoor temp. °C 20 — Outdoor temp. °C 7 6
– 7 –
2. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone lay er.
The working pressure of the new refrigerant R410A is 1,6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water , dust, and e xisting refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conf orming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
2-1. Safety During Installation/Servicing
As R410A’s pressure is about 1,6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive f or the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully . If the refrigerant gas comes into contact with fire,
a poisonous gas may occur .
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise , pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks , its concentration does not exceed the marginal lev el.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal le v el, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual. Improper installation may cause refrigeration
trouble, water leakage , electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s ma y result in water leakage , electric shock and fire, etc.
2-2. Refrigerant Piping Installation
2-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol­ored portion (especially on the interior surface). Otherwise, the expansion v alv e or capillary tube may become bloc ked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 2-2-1. Never use copper pipes thinner than 0,8 mm even when it is availab le on the market.
– 8 –
T a ble 2-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter Outer diameter (mm) R410A R22
1/4 6,35 0,80 0,80 3/8 9,52 0,80 0,80 1/2 12,70 0,80 0,80 5/8 15,88 1,00 1,00
(2) Joints
For copper pipes, flare joints or soc ket joints are used. Prior to use, be sure to remove all con­taminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in T ables 2-2-3 ~ 2-2­6 below.
Table 2-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 6,35 0,50 3/8 9,52 0,60 1/2 12,70 0,70
Reference outer diameter of Minimum joint thickness
copper pipe jointed (mm) (mm)
b) Socket Joints
Socket joints are such that the y are braz ed for connections, and used mainly f or thic k pipings whose diameter is larger than 20 mm. Thicknesses of sock et joints are as shown in T ab le 2-2-2.
5/8 15,88 0,80
2-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover .
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slo wly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all b urrs and clean the cut surface before installation.
– 9 –
c) Insertion of Flare Nut d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Table 2-2-3 Dimensions related to flare processing for R410A
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen­sion A” by using a gauge for size adjustment.
ØD
A
Fig. 2-2-1 Flare processing dimensions
Nominal
diameter
Outer
diameter
(mm)
1/4 6,35 0,8 3/8 9,52 0,8 1/2 12,70 0,8 5/8 15,88 1,0
T a ble 2-2-4 Dimensions related to flare processing for R22
Nominal
diameter
Outer
diameter
(mm)
1/4 6,35 0, 8 3/8 9,52 0, 8 1/2 12,70 0,8
Thickness
(mm)
Thickness
(mm)
A (mm)
Flare tool for
R410A clutch type
Conventional flare tool
Clutch type Wing nut type
0 to 0,5 1,0 to 1,5 1,5 to 2,0 0 to 0,5 1,0 to 1,5 1,5 to 2,0 0 to 0,5 1,0 to 1,5 2,0 to 2,5 0 to 0,5 1,0 to 1,5 2,0 to 2,5
A (mm)
Flare tool for
R22 clutch type
Conventional flare tool
Clutch type Wing nut type
0 to 0,5 0,5 to 1,0 1,0 to 1,5 0 to 0,5 0,5 to 1,0 1,0 to 1,5 0 to 0,5 0,5 to 1,0 1,5 to 2,0
5/8 15,88 1,0
Table 2-2-5 Flare and flare nut dimensions for R410A
Nominal Outer diameter Thickness
diameter (mm) (mm)
1/4 6,35 0, 8 3/8 9,52 0, 8 1/2 12,70 0,8 5/8 15,88 1,0
0 to 0,5 0,5 to 1,0 1,5 to 2,0
Dimension (mm)
Flare nut
width
ABCD
(mm)
9,1 9,2 6,5 13 17 13,2 13,5 9,7 20 22 16,6 16,0 12,9 23 26 19,7 19,0 16,0 25 29
– 10 –
Table 2-2-6 Flare and flare nut dimensions for R22
Nominal Outer diameter Thickness
diameter (mm) (mm)
1/4 6,35 0,8 3/8 9,52 0,8 1/2 12,70 0,8 5/8 15,88 1,0 3/4 19,05 1,0
46˚
~
45˚
B A
Dimension (mm)
Flare nut
width
ABCD
(mm)
9,0 9,2 6,5 13 17 13,0 13,5 9,7 20 22 16,2 16,0 12,9 20 24 19,4 19,0 16,0 23 27 23,3 24,0 19,2 34 36
D
C
43˚
~
45˚
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur .
T a ble 2-2-7 Tightening torque of flare for R410A [Reference values]
Nominal Outer diameter Tightening torque
diameter (mm) N•m (kgf•cm)
1/4 6,35 14 to 18 (140 to 180) 16 (160), 18 (180)
When it is strong, the flare nut may cra c k and may be made non-remov abl e. When choos­ing the tightening torque, comply with values designated by manufacturers . Table 2-2-7 shows reference values.
Note:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
3/8 9,52 33 to 42 (330 to 420) 42 (420) 1/2 12,70 50 to 62 (500 to 620) 55 (550) 5/8 15,88 63 to 77 (630 to 770) 65 (650)
– 11 –
2-3. Tools
2-3-1. Required Tools
The service port diameter of packed v alve of the outdoor unit in the air conditioner using R410A is changed to pre vent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12,7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge , clogging of capillary, etc. Accordingly, the tools to be used are classified into the f ollo wing three types.
(1) Tools exclusive f or R410A (Those which cannot be used f or conventional refrigerant (R22)) (2) Tools exclusive f or R410A, b ut can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for con v entional refrigerant (R22)
The table below shows the tools e xclusiv e for R410A and their interchangeability .
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A air conditioner
installation
No. Used tool
Flare tool
Copper pipe gauge for
adjusting projection
margin Torque wrench
(For Ø12,7)
Gauge manifold Charge hose
Vacuum pump adapter
Electronic balance for
refrigerant charging
Refrigerant cylinder Leakage detector Charging cylinder
(Note 1) When flaring is carried out for R410A using the conv entional flare tools , adjustment of projection
margin is necessary . For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
Usage
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut
Evacuating, refriger­ant charge, run check, etc.
Vacuum evacuating Refrigerant charge
Refrigerant charge Gas leakage check Refrigerant charge
Existence of Whether new equipment conventional for R410A equipment can
Yes
Yes
Yes
Yes
Yes Yes Yes
Yes
(Note 2)
be used
(Note 1)
*
(Note 1)
*
X X
X X
X X X
Conventional air
conditioner installation
Whether new equip­ment can be used with conventional refriger­ant
¡
(Note 1)
*
X X
¡ ¡
X
¡
X
General tools (Conventional tools can be used.)
In addition to the above e xclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (For Ø6,35) (3) Pipe cutter
Also prepare the following equipments f or other installation method and run check.
(1) Clamp meter (2) Thermometer
(4) Reamer (5) Pipe bender (6) Level vial (7) Screwdriver (+, –) (8) Spanner or Monkey wrench
(3) Insulation resistance tester (4) Electroscope
(9) Hole core drill (Ø65) (10) Hexagon wrench
(Opposite side 5mm)
(11) Tape measure (12) Metal saw
– 12 –
2-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor unit’s gas side.
When the compound gauge’s pointer has indicated –0,1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose of the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pump’s power switch. Then, evacuating the refrigerant in the cycle.
Never charge refrigerant e xceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 13 –
(OUTDOOR unit)
Opened
Closed
Service port
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the compo­sition of the charged refrigerant changes and the characteristics of the equipment varies.
2-5. Brazing of Pipes
2-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper . It is used to join iron, copper or copper alloy, and is relatively expen­sive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
Fig. 2-4-2
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound water solution, which may cause a gas leak­age. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux
(1) Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flo w of brazing filler .
• In the brazing process, it prevents the metal surface from being o xidized.
• By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
– 14 –
(2) Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temper ature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harmless to the human body .
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the br azing temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used f or silv er br azing are this type. It features an increased oxide film remo ving capability due to the addition of compounds such as potassium fluoride, potassium chlo­ride and sodium fluoride to the borax-boric acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
2-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prev ent the o xide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow .
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder. Use a copper pipe to direct the piping
material, and attach a flow-meter to the cylinder.
Apply a seal onto the clearance between the
piping material and inserted copper pipe for Nitrogen in order to prevent bac kflo w of the Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open. Adjust the flow rate of Nitrogen gas so that it
is lower than 0,05 m3/Hr or 0,02 MPa (0,2kgf/ cm2) by means of the reducing valve .
After performing the steps above , keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
Remove the flux completely after brazing.
Piping
material
Copper - Copper
Copper - Iron
Iron - Iron
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains
within the pipe, the lubricating oil deterio­rates. Therefore, use a flux which does not contain chlorine.
When adding water to the flux, use water
which does not contain chlorine (e.g. distilled water or ion-exchange w ater).
Remove the flux after brazing.
Used brazing Used
filler flux
Phosphor copper Do not use
Silver Paste flux Silver Vapor flux
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Rubber plug
Fig. 2-5-1 Prevention of oxidation during brazing
– 15 –
Nitrogen gas

3. CONSTRUCTION VIEWS

,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,,
,,,,,,
,,,,,,
,,,,,,
,,,,,,
,,,,,,
,,,,,,
,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
3-1. Indoor Unit
RAS-M10YKV-E, RAS-M13YKV-E RAS-M10YKCV-E, RAS-M13YKCV-E
Air inlet
265
Air outlet
Air filter
790
Heat exchanger
50 94
47
189
47
Knock out system
50
10
External length reference
Hanger
26
46
265
178,5
37
3,5
790
Hanger
232 326 232
321
Connecting pipe (0,39m)
Hanger
Drain hose (0,54m)
Connecting pipe (0,49m) (Flare ø6,35)(Flare ø9,52)
65965,5
65,5 450 344 326
Minimum distance
2,5
to ceiling
66 or more
Minimum distance
17 20
to wall
20 20
120 or more 120 or more
37
Hanger
60,5
126269319
10,5
76
Hanger
Installation plate outline
Center line
790
Front panel
Back body
47
50
10
Knock out system
Hanger
For stud bolt (ø8~ø10)
For stud bolt (ø6)
Minimum distance to wall
40,5
Wireless remote control
55
136
16
– 16 –
3-2. Outdoor Unit
RAS-M18YAV-E RAS-M18YACV-E
310
A leg part
296
270
600
ø25 drain hole
115
76
90
ø11 × 17U-shape hole
50
(For ø8-ø10 anchor bolt)
Hanger
(ø6 hole pitch)
(Anchor bolt long hole pitch)
B leg part
ø4,5 embossing (ø4STS used) (For sunshade roof attaching)
14749,5
21
540
550
8
Fan guard
16
115,5
780 61
8-ø6 hole (For fixing outdoor unit)
ø11 × 17 long hole
(For ø8-ø10 anchor bolt)
Valve cover
Charging port
122,8
Earth terminal
157
332
59
21
Z
53 53 53
96,2
Connecting pipe port
(Pipe dia.ø6,35)
Connecting pipe port
(Pipe dia.ø9,52)
4 × ø11 × 17U-shape hole (For ø8-ø10 anchor bolt)
Intake
100 or
C
310
more
200 or more
Mounting dimensions of anchor bolt
600
50 or
more
D
Outlet
B
Intake
Outside line of product
4 × ø11 × 17 long hole (For ø8-ø10 anchor bolt)
Z
view
A
250 or more
(Minimum distance from wall)
Detailed A leg part
50 36
11
310
296
R5,5
11
310
296
36 50
Detailed B leg part
600
2-ø6 hole
2-ø6 hole
600
R15
Outside line of product
Outside line of product
R15
R5,5
– 17 –
4-1. Indoor Unit
RAS-M10YKV-E, RAS-M13YKV-E RAS-M10YKCV-E, RAS-M13YKCV-E
BLK P04
SG01 DSA
VARISTOR
T6,3A 250V
F01 FUSE
INDOOR
TERMINAL
BLOCK
3
2
BLK
1 2 3
WHI RED
CN30

4. WIRING DIAGRAM

LOUVER
MOTOR
R109
R116
J04
R21
IC04
L01
C15
MAIN P.C. BOARD
(MCC-772)
BLU
PNK
YEL
ORN
RED
6 5 4 3 2 1 6 5 4 3 2 1
CN07
R01
C01
C02
BRW
DB01
FAN MOTOR
DC MOTOR
4 3 2
5
4
3 211
5
CN10
TO1
C06
65
DC35V
DC12V
DC7V
DC0V
IC02
OUTDOOR
UNIT
Check items
OPERATION indicator
Terminal block
Fuse 6,3A
DC 5V
DC 12V
DC 35V
GRN & YEL
INDOOR
UNIT
CN23
CN13
1
2
3
4
BLU
BLU
BLU
BLU
1
2
3
1
1
INFRARED RAYS RECEIVE
AND INDICATION PARTS
4
2
3
4
5
BLU
5 5
6
BLU
6 6
4
7
PNK
7 7
8
BLK
8 8
9
WHI
9 9
Table 4-1-1 Simple check points for diagnosing faults
Diagnosis result
Check to see if the OPERATION indicator goes on and off when the main switch or breaker is turned on, or the power cord is plugged in the wall outlet. (Check the primary and secondary voltage of transformer.)
Check for power supply voltage between  – . (Refer to the name plate.) (Check the primary and secondary voltage of transformer.) Check for fluctuate voltage between  – . (DC 15 to 60V)
Check to determine if the fuse is open. (Check Varistor : R109, R21)
Check for voltage at the pink lead of the infrared rays receive parts. (Check the transformer and the rated voltage power supply circuit.)
Check for voltage at the  lead of louver motor. (Check the transformer and the rated voltage power supply circuit.)
Check for voltage at the CN10 connector side point. (Check the transformer and the rated voltage power supply circuit.)
CN25
CN03
21 21
BLK
BLK
THERMO SENSOR
(TA)
IC
IC01
CN01
BLK
IDENTIFICATION
GRN
&YEL
21 21
BLK
HEAT
EXCHANGER
SENSOR
(TC)
COLOR
BROWNBRW : REDRED : WHITEWHI : YELLOWYEL : BLUEBLU : BLACKBLK : GRAYGRY : PINKPNK : ORANGEORN : GREEN &
:
YELLOW
For detailed diagnostic procedure, refer to the ser vice data. DSA : Surge Absorber
– 18 –
4-2. Outdoor Unit
RAS-M18YAV-E
ORN P10
G E A
~
MODULE
CONVERTER
~
DB01
+
YEL
+ BU EU BV EV
BW EW
BX
IGBT MODULE
BY
BZ
Q200
BLU
P09
P19 P20
P18 P17
4 way valve
3
CN701
POWER RELAY
ELECTRONIC
STARTER
P.C. BOARD
MCC-758
REACTOR
1
11223
L01
POWER SUPPLY
220–230–240V~
FAN MOTOR
FM
PNK
YEL
RED
WHI
CN300
BLK
321 321
P06
SURGE
ABSORBER
VARISTOR
L03
GRY
221
P07P08
C14C12
CN301
RELAY
RY04
C15C13
CT
RELAY RY06
1234455 123
F03 FUSE 15A
F04 FUSE 3,15A
50/60Hz
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
L
WHI
BLKBLK
F01 FUSE 25A
To
INDOOR
UNIT
A
N 1 2 3 1 2 3
BRW
1
RED
2
CN704
ORN
3
YEL
4
1
CN501
313
P11
YEL
YEL
P12 P13
P14
REDP21 WHI
P22
BLKP23
REACTOR
11 22
REACTOR
PUR
1
1
2
2
3
3
To
INDOOR
UNIT
B
THERMOSTAT for COMPRESSOR
ORN
P04
RED
P05
WHI
P06
BRW
1
1
RED
2
2
CN15
ORN
3
3
YEL
4
4
BLK
GRY
CM
F01
FUSE 6,3A
P02 P01
PHOTO
COUPLER
SUB
P.C. BOARD
MCC-775
COMPRESSOR
CN01
WHI
CN08
WHI
CN02
WHI
CN03
WHI
CN04
BLK
CN05
YEL
CN14
CN13
1 1 2 2
1 1 2 2
1 1 2 2 3 3
1 1 2 2
1 1 2 2
1 1 2 2 3 3
6 6 5 5 4 4 3 3 2 2 1 1
6 6 5 5 4 4 3 3 2 2 1 1
GRY RED BLU ORN YEL WHI
GRY RED BLU ORN YEL WHI
BLK
YEL
TE
TD
TO
TS
TGa
P.M.V.
A UNIT
P.M.V.
B UNIT
– 19 –
COLOR IDENTIFICATION
BLK : BLACK BLU : BLUE
ORN : ORANGE
GRY : GRAY PNK : PINK SKB : SKY-BLUE
P.M.V. : PULSE MODULATING VALVE
WHI : WHITE
BRW : BROWN
RED : RED
YEL : YELLOW
PUR : PURPLE
RAS-M18YACV-E
ORN P10
G
E A ~
MODULE
CONVERTER
~
DB01
+
YEL
+ BU EU BV EV
BW EW
BX
IGBT MODULE
BY BZ
Q200
BLU
P.C. BOARD
P09
POWER RELAY
ELECTRONIC
P19 P20
P18 P17
REACTOR
CN701
MCC-758
STARTER
CN704
CN501
P11
P12 P13
P22
To
INDOOR
UNIT
A
BRW
1
RED
2
ORN
3
YEL
4
1
313
YEL YEL
P14
REDP21 WHI BLKP23
POWER
SUPPLY
220–230–240V~
FAN MOTOR
FM
1
123
L01
PNK
YEL
RED
WHI
GRY
221
P07P08
C14C12
CN301
C15C13
CT
RELAY RY06
1234455 123
F03 FUSE 15A
F04 FUSE 3,15A
CN300
BLK
321 321
P06
SURGE
ABSORBER
VARISTOR
L03
50/60Hz
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
L
N 1 2 3 1 2 3
BLKBLK
WHI
F01 FUSE 25A
REACTOR
11 22
REACTOR
PUR
1
1
2
2
3
3
To
INDOOR
UNIT
B
THERMOSTAT for COMPRESSOR
ORN
P04
RED
P05
WHI
P06
BRW
1
1
RED
2
2
CN15
ORN
3
3
YEL
4
4
BLK
GRY
FUSE 6,3A
P02 P01
F01
PHOTO
COUPLER
SUB
P.C. BOARD
MCC-775
COMPRESSOR
CM
CN08
WHI
CN02
WHI
CN03
WHI
CN04
BLK
CN05
YEL
CN14
CN13
1 1 2 2
1 1 2 2 3 3
1 1 2 2
1 1 2 2
1 1 2 2 3 3
6 6 5 5 4 4 3 3 2 2 1 1
6 6 5 5 4 4 3 3 2 2 1 1
GRY RED BLU ORN YEL WHI
GRY RED BLU ORN YEL WHI
BLK
YEL
TD
TO
TS
TGa
P.M.V.
A UNIT
P.M.V.
B UNIT
– 20 –
COLOR IDENTIFICATION
BLK : BLACK
BLU : BLUE
ORN : ORANGE
GRY : GRAY PNK : PINK
SKB : SKY-BLUE
P.M.V. : PULSE MODULATING VALVE
WHI : WHITE
BRW : BROWN
RED : RED
YEL : YELLOW
PUR : PURPLE

5. SPECIFICATIONS OF ELECTRICAL PARTS

5-1. Indoor Unit
RAS-M10YKV-E, RAS-M13YKV-E / RAS-M10YKCV-E, RAS-M13YKCV-E
No. Parts name Type Specifications
1 Fan motor (for indoor) TICF-35-19-4 DC35V, 19W 2 Thermo. sensor (TA-sensor) ( – ) 10k at 25°C 3 DC-DC transformer (T01) SWT-34 or SWT-46 DC390V, Secondary DC35V, 12V, 7V
4 Microcomputer
Heat exchanger temp. sensor
5
(TC-sensor) 6 Line filter (L01) UF-253Y0R7 25mH, AC0,7A 7 Diode (DB01) RBV-406 or D3SBA60 4A, 600V 8 Capacitor (C02) KMH450VNSN100M25B 100µF, 450V 9 Fuse (F01) TSCR6,3A T6,3A, 250V
10 Power supply IC (IC01) MA2830-FJ 4A, 600V 11 Varistor (R21, R109) 15G561K 560V 12 Resistor (R01) ERF-5TK5R6 5,6, 5W 13 Louver motor MP35EA7 Output (Rated) 2W, 10poles, 1phase DC12V
5-2. Outdoor Unit
RAS-M18YAV-E / RAS-M18YACV-E
No. Parts name Model name Rating
1 SC coil (Noise filter)
2 DC-DC transformer SWT-43 Secondary side 3 Reactor CH38Z-K L=10mH, 16A x 2
4 Reactor CH43Z-K L=10mH, 1A 5 Outside fan motor ICF-140-40-7 DC140V, 40W
6 Fan control relay AJQ1341
Suction temp. sensor
7
(TS sensor)
Discharge temp. sensor
8
(TD sensor)
Outside air temp. sensor
9
(TO sensor)
Temp. sensor at A room
10
gas side (TGa sensor) RAS-M18YAV-E .............62k (20°C)
11 Terminal block (9P) ——— 20A, AC250V 12 Terminal block (3P) ——— 20A, AC250V
13 Fuse
14 Electrolytic capacitor 15 Transistor module 6MBI25GS-060-01 25A, 600V
16 Compressor DA130A1F-21F 3-phases 4-poles 1100W 17 Compressor thermo. PW-2AL OFF: 125 ± 4°C, ON: 90 ± 5°C 18 Converter module MP7002 Diode: 25A, 600V, IGBT: 40A, 600V
Heat exchanger temp. sensor
19
(TE-sensor) (H/P only)
L03 SC-15-S06J 15A, 0,6mH L01 SC-20-01J 20A, 150µH
TMP87PM40AF or
TMP87CM40AF
( – ) 10k at 25°C
Primary side DC280V 7,5V x 1, 13V x 1, 26,5V x 3, 16V x 1, 15V x 1
Coil DC12V Contact AC125V, 3A
(Inverter attached) 10k (25°C) (Inverter attached) 62k (20°C) (Inverter attached) 10k (25°C) (Inverter attached)
For protection of
switching power source
For protection of transistor
module breakage
For protection of
inverter input overcurrent
LLQ2G501KHUATF
400LISN500K35F
(Inverter attached) 10k at 25°C
RAS-M18YACV-E .......... 10k (25°C)
3,15A, AC250V 15A, AC250V 25A, AC250V 500µF, DC400V X 4 pieces
– 21 –

6. REFRIGERANT CYCLE DIAGRAM

6-1. Refrigerant Cycle Diagram
RAS-M10YKV-E, RAS-M13YKV-E RAS-M18YAV-E
To B room
INDOOR UNIT
Indoor heat
exchanger
T1 Temp. measurement
To B room
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe Both A and B rooms
Outer dia. : 9,52mm Thickness : 0,8mm
Muffler Ø25 x 80
4 way valve (VHV-0213)
Accumulating tank Ø51 x 200 (290cc)
TS
Cross flow fan
Deoxidized copper pipe Both A and B rooms Outer dia. : 6,35mm Thickness : 0,8mm
Sectional shape of heat insulator
Muffler Ø25 x 80
TGa
Muffler Ø25 x 80
Muffler Ø25 x 160
TD
Compressor DA130A1F-21F
Outdoor heat
exchanger
Split capillary
Strainer
Ø1,5 x 200
Allowable height
difference : 10m
Strainer Capillary
Ø2,2 x 200
Pulse modulating valve at liquid side (SEV15RC2)
Per 1 unit Max. : 20m Total : 30m
Allowable pipe length
Temp. measurement
T
2
Propeller fan
OUTDOOR UNIT
Ø1,5 x 200
TE
NOTE :
Refrigerant amount : 1,15kg
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
T able 6-1-1
Each length in one room
Total length in two rooms
Unnecessary to add refrigerant
A room B room
(Standard) 10 m 5 m 5 m Do not add the refrigerant
(Maximum) 30 m 20 (10) m 10 (20) m Do not add the refrigerant
NOTE :
• The maximum pipe length of this air conditioner is 30 m. The additional charging of refrigerant is unneces­sary because this air conditioner is designed with charge-less specification.
• To connect only one indoor unit, use connecting pipe with length by 5m or more.
– 22 –
RAS-M10YKCV-E, RAS-M13YKCV-E RAS-M18YACV-E
To B room
INDOOR UNIT
Indoor heat
exchanger
T1
Temp. measurement
To B room
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe Both A and B rooms
Outer dia. : 9,52mm Thickness : 0,8mm
Muffler Ø25 x 80
Accumulating tank Ø51 x 200 (290cc)
TS
Muffler Ø25 x 80
Outdoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Both A and B rooms Outer dia. : 6,35mm Thickness : 0,8mm
Sectional shape of heat insulator
TGa
TD
Compressor DA130A1F-21F
Split capillary
Ø1,5 x 200
Allowable height
difference : 10m
Strainer
Capillary Ø2,2 x 200
Pulse modulating valve at liquid side (SEV15RC2)
Per 1 unit Max. : 20m Total : 30m
Allowable pipe length
Temp. measurement
T
2
Propeller fan
OUTDOOR UNIT
Ø1,5 x 200
TE
NOTE :
Refrigerant amount : 1,15kg
Gas leak check position Refrigerant flow
T able 6-1-2
Each length in one room
Total length in two rooms
Unnecessary to add refrigerant
A room B room
(Standard) 10 m 5 m 5 m Do not add the refrigerant
(Maximum) 30 m 20 (10) m 10 (20) m Do not add the refrigerant
NOTE :
• The maximum pipe length of this air conditioner is 30 m. The additional charging of refrigerant is unneces­sary because this air conditioner is designed with charge-less specification.
– 23 –
6-2. Operation Data
<Cooling>
Temperature
condition (°C)
Indoor Outdoor
27/19 35/–
<Heating>
Temperature
condition (°C)
Indoor Outdoor
20/– 7/6
No. of
operating
units
1 unit
2 units
No. of
operating
units
1 unit
2 units
Operating combination
(Unit)
AB
M13YKCV -E M13YKV -E
M10YKCV -E M10YKV -E
M13YKCV -E M10YKCV -E M13YKV -E M10YKV-E
M10YKCV -E M10YKCV -E M10YKV -E M10YKV-E
Operating combination
(Unit)
AB
M13YKV-E 3,5 to 3,7
M10YKV-E 3,3 to 3,5 M13YKV-E M10YKV-E 2,5 to 2,7 M10YKV-E M10YKV-E 2,5 to 2,7
Standard
pressure
P (MPa)
0,7 to 0,9
0,9 to 1,1
0,8 to 1,0
0,8 to 1,0
Standard
pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
9 to 11 46 to 48 High High 62
11 to 13 45 to 47 High MED. 38
11 to 13 50 to 52 High High 74
10 to 12 50 to 52 High High 74
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
53 to 55 0 to 2 High High 79 48 to 50 0 to 2 High MED. 63 41 to 43 –2 to 0 High High 9 7 41 to 43 –2 to 0 High High 9 7
Indoor Outdoor Compressor
fan fan revolution
mode mode (rps)
Indoor Outdoor Compressor
fan fan revolution
mode mode (rps)
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat e xchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m x 2 units
– 24 –
7-1. Indoor Unit
Heat Exchanger Sensor
Temperature Sensor
Infrared Rays Signal Receiver
7. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U
Functions
• Louver Control
• 3-minute Delay at Restart for Compressor
Operation
Display
Timer
Display
Infrared
Initializing Circuit
Rays
Clock Frequency
Oscillator Circuit
Remote
Control
From Outdoor Unit
REMOTE CONTROL
RAS-M10YKV-E, RAS-M13YKV-E
(Heat pump model)
Power Supply
Circuit
Noise Filter
• Motor Revolution Control
• Processing (Temperature Processing)
• Timer
• Serial Signal Communication
Louver ON/OFF Signal
Serial Signal Transmitter/Receiver
Serial Signal Communication
RAS-M10YKCV-E, RAS-M13YKCV-E
Infrared
Rays
Louver Driver
(Cooling only model)
ECONO.
Sign Display
FAN-ONLY
Sign Display
Indoor
Fan Motor
Louver
Motor
Infrared
Rays
Remote Control
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECONO.
Remote Control Operation (START/STOP) Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECONO.
– 25 –
7-2. Outdoor Unit (Inverter Assembly)
RAS-M18YAV-E
CONTROL BLOK DIAGRAM (Outdoor unit)
220–230–240 V ~ 50 Hz
MCC-775 (SUB P.C.B) MCC-758 (MAIN P.C.B)
– 26 –
Outdoor Heat­exchanger temp.sensor
Discharge temp. sensor
Suction temp. sensor
Gas side pipe temp. sensor
Outdoor air temp. sensor
A unit
send/receive
circuit
B unit
send/receive
circuit
M.C.U
• Inverter output frequency control
• A/D converter function
• P.M.V. control
• Discharge temp. control
• Error display
• Signal communication to MCU
Driver circuit of P.M.V.
A unit
P.M.V.
B unit
P.M.V.
Noise
filter
M.C.U
• PWM synthesis function
• Input current release control
• IGBT over-current detect control
• Outdoor fan control
• High power factor correction control
• Signal communication to MCU
High power factor
correction circuit
Converter
(AC DC)
Relay RY04
Input current
Sensor
Over current detect circuit
Rotor position
detect circuit
Rotor position
detect circuit
Over current
detect circuit
Gate drive
Over current
sensor
Over current
sensor
circuit
Gate drive
circuit
Inverter
AC)
(DC
Inverter
(DC AC)
Outdoor
fan motor
Compressor
P.M.V. : Pulse Modulating Valve PWM : Pulse Width Modulation IGBT : Insulated Gate Bipolar Transistor
4 way valve
Loading...
+ 58 hidden pages