– 17 –
22
Outdoor temp.
(˚C)
Cool mode
20
Fan only mode
Fan only mode (Cooling only model)
Heat mode (Heat pump model)
2˚C
1˚C
1 hour
2 hours
Operation suppression zone
Operation start
Set
temperature
Room
temperature
2˚C
1˚C
Set temperature
Operation
suppression zone
Room
temperature
Operation start
1 hour
2 hours
3) Defrost reset
Resetting operation from defrost to heating is
performed when any one of the following
conditions is satisfied.
a. Temperature of the outdoor heat ex-
changer rose to +8°C or higher.
b. A status that temperature of the outdoor
heat exchanger is +5°C or higher contin-
ued for 80 seconds.
c. Defrost operation continued for 10 minutes.
In resetting defrost operation, the compressor
stops for 50 seconds if defrost has started
under condition a. to d. in item 1, but the
compressor is reset to heating operation
keeping operated if defrost has started under
condition e. in item 1.
8-2-5. Auto Operation
(1) As shown in Fig. 8-2-6, the operation mode
(COOL, FAN ONLY, HEA T) is selected according
to the outside temperature when the operation
has started.
The operation in F an only mode continues until
an operation mode is selected.
If the room temperature is 20°C or higher when
“AUTO” operation started within 2 hours after
“HEAT” operation had stopped, select an oper a-
tion mode after Fan operation of ultr a low fan.
In AU TO operation, the set temperature of each
operation can be corrected by the remote controller in the range of 17 to 30°C.
Fig. 8-2-6
(2) After selecting the operation mode (COOL, FA N
ONLY, HEAT), select an operation mode again
when a status that the compressor was turned
off by the room temperature or outside air temperature continues for 15 minutes.
8-2-6. ECO Timer Operation
When you push the ECO button during cooling, Dry,
heating, or A operation, the air conditioner will start
the following operation.
The fan speed will be automatically controlled.
• Cooling operation / Dry operation
In the operation suppression zone, where capacity
is kept to the minimum, overcooling is prevented by
raising the temperature setting by 1°C after 1 hour
and by 2°C after 2 hours of operation.
The room temperature is thus regulated between
the operation suppression zone and the set temperature.
Fig. 8-2-7
• Heating operation
(Heat pump model only)
In the operation suppression zone, where capacity
is kept to the minimum, ov erheating is prevented by
lowering the temperature setting by 1°C after 1
hour and by 2°C after 2 hours of operation.
The room temperature is thus regulated between
the set temperature and the operation suppression
zone.
Fig. 8-2-8
8-2-7. High POWER Operation
When you push the Hi-POWER b utton during cooling, heating, or A operation, the air conditioner will
start the following operation. (A operation : Auto
change over)
• Cooling operation
Performs the cooling operation at 1°C lower than
the setting temperature.
When the room temperature is above the setting
temperature. In addition, fan speed is high*.
Once room temperature is within 1°C of the setting
temperature.
* Noise level raises in accordance with fan speed.
• Heating operation (Heat pump model only)
Performs the heating operation at 2°C higher than
the setting temperature.