Toshiba RAS-24S2AH-ES2, RAS-24SA-ES2, RAS-24SKHP-ES2, RAS-24SKP-ES2 DATA BOOK

SERVICE MANUAL
AIR CONDITIONER
RAS-24SKP-ES2 / RAS-24SA-ES2
RAS-24SKHP-ES2 / RAS-24S2AH-ES2
FILE NO. SVM-10049
SPLIT WALL TYPE
April, 2010
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit
3. WIRING DIAGRAM
3-1 RAS-24SKP-ES2 / RAS-24SA-ES2 3-2 RAS-24SKHP-ES2 / RAS-24S2AH-ES2
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-24SKP-ES2)
Outdoor Unit (RAS-24SA-ES2)
4-2 4-3
Indoor Unit (RASP-24SKHP-ES2) Outdoor Unit (RAS-24S2AH-ES2)
4-4
5. REFRIGERATION CYCLE DIAGRAM
RAS-24SKP-ES2 / RAS-24SA-ES2
5-1
RAS-24SKHP-ES2 / RAS-24S2AH-ES2
5-2
6. CONTROL BLOCK DIAGRAM
6-1 RAS-24SKP-ES / RAS-24SA-ES2
6-2 RAS-24SKHP-ES2 / RAS-24S2AH-ES2
7. OPERATION DESCRIPTION
7-1 Remote control 7-2 Outline of Air Conditioner Control
7-3 Description of Operation Circuit 7-4 Description of Safety and Reliability Prevention Function 7-5 One-Touch Operation 7-6 Hi POWER Operation 7-7 QUIET Operation 7-8 ECO Operation 7-9 COMFORT SLEEP Operation
7-10 FILTER Check lamp
7-11 Auto Restart Function
7-12 Self-Cleaning Operation
1
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 Test Operation
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code)
9-5 How To Diagnose Faulty Parts
Troubleshooting for Indoor unit
9-6 9-7 Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire) 9-8 Troubleshooting for P.C. Board 9-9 Troubleshooting for Remote Control
FILE NO. SVM-10049
HOW TO REPLACE THE MAIN PARTS
10.
10-1 Indoor Unit
Outdoor Unit
10-2
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy) 11-2 Indoor Unit 11-3
Outdoor Unit (RAS-24SA-ES2)
11-4
Outdoor Unit (RAS-24S2AH-ES2)
2

1. SPECIFICATIONS

MODEL RAS-24SKP-ES2
Cooling
ITEM
Capacity
kW
Phase
Power source
Hz Power consumption W Power factor % Running A Current Indoor/Outdoor Starting current A Moisture removal lit/h Noise Indoor (H/M+/M/L+/L) dB
Outdoor (220-240V) dB
Refrigerant Name of refrigerant
Rated amount kg Refrigerant control Interconnection Gas side size mm pipe Connection type
Liquid side size mm
Connection type
Maximum length m
(One way)
Maximum height m
difference
INDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Evaporator type Indoor fan type Airflow volume High fan
Medium fan
Low fan
3
m
3
m
3
m Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Condenser type Outdoor fan type Airflow volume
3
m Fan motor output W Compressor Model
Output W Safety device Louver type Usable outdoor temperature range °C
Note *1 Chargeless pipe
*2 Maximum pipe
V
/h /h /h
/h
220V
6.80
2030
98
0.3/9.1 0.3/8.6
56
Honeycomb woven filter with PP frame
4000
RAS--24SA-ES2
1
220 - 240
50
55
2.7
50/48/46/43/40
R410A
1.90
Capillary tube
12.7
Flare connection
6.35
Flare connection
RAS-24SKP-ES2
RAS-24SA-ES2
PA271X3CS-4MUL
Automatic louver
1
15*
2
25*
10
320
1050
228
13
Finned tube
Cross flow fan
1240
1000
850
30
890 900 320
59
Finned tube
Propeller fan
85
2000
Fuse , IOL
15 ~ 43
240V
6.85
2070
97
57
4200
3
MODEL RAS-24SKHP-ES2
RAS-24S2AH-ES2
ITEM Cooling Heating
Capacity
kW
220V
6.78
Phase
Power source
V
Hz Power consumption W Power factor %
2030
98 96 Running Indoor A 0.30 Current Outdoor A 9.40 9.10 8.95 8.90 Starting current A Moisture removal lit/h Noise Indoor (H/M+/M/L+/L) dB
Outdoor (220-240V) dB
56-57
Refrigerant Name of refrigerant
Rated amount kg Refrigerant control Interconnection Gas side size mm pipe Connection type
Liquid side size mm
Connection type
Maximum length m
(One way)
Maximum height m
difference
INDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Evaporator type Indoor fan type Airflow volume High fan
Medium fan
Low fan
3
m
/h
3
/h
m
3
m
/h
1240
1000
Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Height mm
Width mm
Depth mm Net weight kg Condenser type Outdoor fan type Airflow volume
3
m
/h
4000 4200 4000 Fan motor output W Compressor Model
Output W Safety device Louver type Usable outdoor temperature range °C
15 ~ 43 -10 ~ 24
Note *1 Chargeless pipe
*2 Maximum pipe
240V 220V
6.82 7.28
1
220 - 240
50
2100 1930
98
55
2.7
50/48/46/43/40
R410A
2.00
Capillary tube
12.7
Flare connection
6.35
Flare connection
1
15*
2
25*
10
RAS-24SKHP-ES2
320
1050
228
14
Finned tube
Cross flow fan
30
Honeycomb woven filter with PP frame
RAS-24S2AH-ES2
890 900 320
64
Finned tube
Propeller fan
85
PA271X3CS-4MUL
2000
Fuse , IOL
Automatic louver
240V
7.32
2050
96
57-58
1240
1000
850850
4200
4
Note : 1
Capacity is based on the following temperature conditions.
FILE NO. SVM-10049
Condition
Temperature
(DB) 27°C20°C
Indoor unit inlet air temperature
(WB) 19°C15°C
(DB) 35°C7°C
Outdoor unit inlet air temperature
(WB) 24°C6°C
Note : 2
Charge refrigerant according to the table below.
Refrige rant
*1 No need to charge
extra refrigerant
*2 Need to charge
extra refrigerant
JIS C9612
Cooling Heating
RAS-24SKP-ES2 / RAS-24SA-ES2
RAS-24SKHP-ES2 / RAS-24S2AH-ES2
15 m or less
Over 15 m up to 25 m (20 g/m)
5
2-1. Indoor Unit

2. CONSTRUCTION VIEWS

Grille Inlet
Front Panel
73.57
50
Knock out system
Heat exchanger
320
50
78 72
Air inlet
278 200 222 150
132
1050
Air outlet
200
Air filter
72 78
50
228
50
Knock out system
73.5
7
157
Drain hose (0.5m)
320
40
525
Hanger
Connecting pipe (0.39m)
12.70)
(Flare
85 23
Hanger
6
5
Hanger Hanger
262.5
786
235
215
Center line
Installation plate outline
Connecting pipe (0.49m)
235
215
262.5
Hanger
6.35)(Flare
For stud bold ( For stud bold (
6
5
10947 215.5 153.5
56
Wireless remote controller
63
Remote controller holder
6) 8~
10)
Outline of indoor unit
40
19
125
26
6
2-2. Outdoor Unit
FILE NO. SVM-10049
56.5
365
A Detail Drawing (Back leg)
600
R6
FAN-GUARD
890
365
Ø
547
Ø
A
113
25 Drain outlet
438
2- 12x17 Hole
Ø
525
365
12x17 Hole
Ø
B
HANDLE
B Detail Drawing (Front leg)
56.5
Z
PANEL-PIPING-BK
320
HANDLE
200 or more
320
150
Z View
600
Air inlet
150600
Service port
600 or more
365
400
Gas-side (Flare 12.70)
Liquid-side (Flare 6.35)
45
128
82
Ø
Ø
150 or more
Air outlet
1000 or more
Installation dimension
7
4x 17 Long holes
Ø

3. WIRING DIAGRAM

3-1. RAS-24SKP-ES2 / RAS-24SA-ES2
FILE NO. SVM-10049
OUTDOOR TERMINAL BLOCK
POWER SUPPLY 220 240 V ~ 50 Hz
L
N
BLK
RED
BLK
RED
RED
MAGNETIC CONTACTOR
1
1
BLK BLK
SPARK KILLER
A2 A1
52C
1/L1 2/T1
6/T35/L3
2
2
RED
CAPACITOR
3
3
GRY
CHASSIS
RED
WHI PNK
COMPRESSOR
CAPACITOR
S
R
OUTDOOR
UNIT
BLK
C
WHI RED
FAN MOTOR
BLK
8
3-2. RAS-24SKHP-ES2 / RAS-24S2AH-ES2
FILE NO. SVM-10049
OUTDOOR TERMINAL BLOCK
POWER SUPPLY 220- 240 V ~ 50 Hz
L
BLK
RED
BLK
RED
WHI PNK
COMPRESSOR
2
1
3
GRN&YEL
2
5/L3
3
i
CHASSIS
A1
N
FERRITE CORE
RED
CONTACTOR
1/L1
1
MAGNETIC
52C
BLK
6/T3
A2
RED
WHI RED
FAN MOTOR
2/T1
CAPACITOR CAPACITOR
S
C
R
TRANSFORMER
OUTDOOR UNIT
BLK BLK
BLK
BLK
RED
RED
BLK
BLK
WHI
RED
GRY
BLU
YEL
BLU
BLU COIL FOR 4 WAY VALVE
MAIN P.C. BOARD (MCC-890)
1
1 2
CN06
3
3
1
1
CN05
3
3
SG01
1
1
F01
3
3
250VAC T6. 3A
5
5
CN01
7
7
9
9
1
CN11
313
11
33
CR11
CN02
CR12
CR13
TNR R74
CN03
1 1
RY07
RY05
3
TNR R73
RY06
CN07
CN08
DISCHARGE PIPE SENSOR (TD)
BLU
1
1 2 3
3
BLU
BLK
1
1 2 3
3
BLK
HEAT EXCHANGER SENSOR (TE)
9

4. SPECIFICATION OF ELECTRICAL PARTS

4-1. Indoor Unit (RAS-24SKP-ES2)
FILE NO. SVM-10049
No.
1 Fan motor (for indoor) MF-340-30-1RT DC 340V, 30W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Switching Transformer (T01) SWT-77 DC7V, 12 V 4 Microcontroller TMP87CM40ANG-6P68 5 Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-R06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C03) EKMH451VSN121MQ35S 120 µF, 450 V 9 Fuse (F01) BET6.3A 6.3 A, 250 V
10 Varistor (R09, R10) SR561K14DO 560 V
11 Resistor (R01) RF-5TK1R8
2 TLou
13
v
Relay : (RY03)
P5War1ts name
er motor MP24Z3T Output (Rated) 2 W, 16 poles, 4 phase,
ype
——— 10 k at 25°C
1.8 ,
DC 12 V
G5NB-1A-CA
Coil DC 12V, 16.7mA, Contact AC 250V, 3A
Specifications
4-2. Outdoor Unit (RAS-24SA-ES2)
No. Parts name Type Specifications
Output (Rated) 2000W, 2poles, 1 phase, 220-240V 50Hz
1 Compressor PA271X3CS-4MU2 Winding resistance (Ω  ) Red-Black White-Black
(at 20°C) 1.27 2.10 Output (Rated) 42W, 4poles, 1 phase, 220 − 240V, 50Hz
2 Fan motor (for outdoor) WLF-240-85A Winding resistance (Ω) Red-Black White-Black
(at 20° C) 70.5 120.1
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor)
5
Magnetic contactor
DS451355NPQB AC 450V, 3.0µ F
32332I5606J063 A
B
A35P 220-240V, 50Hz
C 450V, 60µ F
10
FILE NO. SVM-10049
4-3. Indoor Unit (RAS-24SKHP-ES2)
No. Parts name Type Specifications
1 Fan motor (for indoor) MF-340-30-1RT DC 340V, 30W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Switching Transformer (T01) SWT-77 DC 7V, 12V 4 Microcontroller TMP87CM40ANG-6P68 5 Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-R06270 27mH, 600mA 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C03) EKMH451VSN121MQ35S 120 µF, 450 V 9 Fuse (F01) BET6.3A 6.3 A, 250 V
10 Varistor (R09, R10) SR561K14DO 560 V
11 Resistor (R01) RF-5TK1R8 1.8, 5W 12 Louver motor MP24Z3T Output (Rated) 2 W, 16 poles, 4 phase,
——— 10 k at 25°C
DC 12 V
4-4. Outdoor Unit (RAS-24S2AH-ES2)
No. Parts name Type Specifications
Output (Rated) 2000W, 2poles, 1 phase, 220 − 240V, 50Hz
1 Compressor PA271X3CS-4MU2 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 1.27 2.10 Output (Rated) 42W, 4poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 70.5 120.1
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor) Solenoid coil
5
(for 4-way valve) 6 Thermo sensor TE / TD 10k at 25°C / 50k at 25°C 7 Magnetic contactor A35P 220 ~ 240V, 50Hz 8 Transformer TT-05 220 ~ 240V 9 Microcontroller TMP47C840N
10 Varistor (R73, R74) 15G471K 470V 11 Fuse (F01) TSCR T6.3A, 250V
DS451305NPQB AC 450V, 3.0µF
B32332I5606J063 AC 450V, 60µF
VHV (STF) AC 220 ~ 240V
11

5. REFRIGERATION CYCLE DIAGRAM

5-1. RAS-24SKP-ES2 / RAS-24SA-ES2
FILE NO. SVM-10049
Indoor unit
Cooling
0.39 m (Connecting pipe)
12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Compressor
P
Packed valve
(∅12.7 )
Gas container connection (Reinstall etc.)
PA271X3CS-4MUL
Heat exchanger
Cross flow fan
T
0.49 m (Connecting pipe)
6 .35
Packed valve
(∅6.35)
Capillary tube
450 s
2.0x
Heat exchanger
Refrigerant R410A 1.90 kg
Cooling
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak
Ambient temp.
50 Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.86 9.4 High 27/19 35/24
Cooling High temperature 1.03 14.3 High 32/23 43/26
Low temperature 0.65 1.9 Low 21/15 21/15
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
12
5-2. RAS-24SKHP-ES2 / RAS-24S2AH-ES2
FILE NO. SVM-10049
Indoor unit
Cooling
0.39 m (Connecting pipe)
Æ12.7
O.D.:12.7 mm O.D.:6.35 mm
Cooling
Heating
Heating
P
Packed valve
(Æ12.7)
Heating
4-way valve
Cooling
Discharge Muffler
25x160L
Compressor
Accumulator
PA271X3CS-4MUL
Heat exchanger
Cross flow fan
T1
Capillary tube Æ2.0 x 700
Packed valve
(Æ6.35)
Capillary tube
Æ2.0 x 450
l
0.49 m
(Connecting pipe)
Æ6.35
l
Heat exchanger
Refrigerant R410A 2.00 kg.
Cooling
Heating
Propeller fan Outdoor unit
Mark ( ) means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.64 44.7 High 20/15 7/6
Heating Overload*1 3.54 ~ 3.80 49.3 ~ 51.0 Low 27/- 24/18
Low temperature 2.28 30.3 High 20/
-
-10/-10
Standard 0.90 11.6 High 27/19 35/24
Cooling Overload 1.10 17.5 High 32/23 43/26
Low temperature 0.73 2.6 Low 21/15 21/15
Note
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
·
·
*1 During heating overload operation, a value for the high temperature limit control operation is included.
- 13 -

6. CONTROL BLOCK DIAGRAM

6.1 RAS-24SKP-ES2 / RAS-24SA-ES2
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions
Louver Control
FILE NO. SVM-10049
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
Remote
Control
From Outdoor Unit
240 V AC 50 Hz
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Outdoor unit
ON/OFF Signal
Relay Driver
Relay RY03
Outdoor Unit
Louver ON/OFF Signal
Louver Driver
Timer
Display
Filter Sign
Display
Fan Only
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
14
6.2 RAS-24SKHP-ES2 / RAS-24S2AH-ES2
Indoor Unit Control Panel
Heat Exchanger Sensor
Functions
Louver Control
FILE NO. SVM-10049
M.C.U.
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
Remote
Control
From Outdoor Unit
240 V AC 50 Hz
Clock Frequency Oscillator Circuit
Power Supply
Circuit
Noise Filter
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Filter Sign
Display
PRE DEF.
Sign Display
Hi Power
Sign Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
15

7. OPERATION DESCRIPTION

7-1. Remote control
7-1-1. Function of Push Putton
1
11
Infrared signal emitter
11
2
Start/Stop button
3
Mode select button (MODE)
4
Temperature button (TEMP)
5
Fan speed button (FAN)
6
Swing louver button (SWING)
7
Set louver button (FIX)
8
On timer button (ON) Off timer button (OFF)
9
18
10
Sleep timer button (SLEEP)
19
Timer setup button (SET)
11 12
20
Timer clear button (CLR)
Memory and Preset button (PRESET)
13 14
One Touch button (ONE-TOUCH)
15
High power button (Hi-POWER)
16
Economy button (ECO)
17
Quiet button (QUIET)
18
Comfort sleep button (COMFORT SLEEP)
19
Filter reset button (FILTER)
20
Clock Reset button (CLOCK)
21
Check button (CHK)
FILE NO. SVM-10049
1
13
14
2
17
6
7
8 10 21
19
PRESET
ONE-TOUCH
QUIET
SWING
TIMER
SLEEP
CHK
FAN
TEMP
MODE
COMFORT
SLEEP
FIX Hi-POWER ECO
ON
OFF
FILTER
CLOCK
5
4 3
18
15 16
CLR
SET
12
9
11
20
16
FILE NO. SVM-10049
7-1-2. Display of Remote Control
All indications, except for the clock time indicator, are displayed by pressing the button.
1. Transmission mark
This transmission mark remote controller transmits signals to the indoor unit.
indicates when the
2. Mode indicator
Indicates the current operation mode. (A : Auto, : Cool,
: Dry, : Heat, : Fan only)
3. Temperature indicator
Indicates the temperature setting. (17°C to 30°C)
4. FAN speed indicator
Indicates the selected fan speed. AUTO or five fan speed levels
LOW , LOW+ , MED , MED+ ,
( HIGH ) can be shown. Indicate Auto will be appear with Dry operation
( : Dry) only.
9
1
12
2
13
10
10
5. TIMER and clock time indicator
The time setting for timer operation or the clock time is indicated.
The current time is always indicated except during TIMER operation.
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts. Press the Hi-POWER button to start and press it
again to stop the operation.
7. (PRESET) indicator
Flashes for 3 seconds when the PRESET button is pressed during operation.
The button for more than 3 seconds while the mark is
blinks. Press another button to turn off the mark.
mark is shown when holding down the
8. ECO indicator
Indicates when the ECO is in activated. Press the ECO button to start and press it again
to stop operation.
9. A, B change indicator remote controller
When the remote controller switching function is set, “B” appears in the remote controller display. (When the remote controller setting is “A”, there is no indication at this position.)
10. Comfort sleep
Indicates when comfort sleep is activaled. Press comfort sleep button to selectter
11
6
3
8
7
4
5
11. Quiet
Indicates when quiet is activated. Press quiet button to start and press it again to stop operation.
12. One-Touch
Indicates when one touch comfort is activated. Press one-touch button to start the operation.
13. Swing
Indicates when louver is swing. Press swing button to start the swing operation and press it again to stop the swing operation.
17
7-2. Outline of Air Conditioner Control
y
A
y
P
P
A
This is a fixed capacity type air conditioner, which uses a DC motor for an indoor fan. The DC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit. The outdoor unit receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the
outdoor unit
Receiving of information of the operation status
and judging of the information or indication of error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation commands from the indoor controller and executes them.
Compressor operation
control
Operation control of
outdoor fan motor
Operations according to the commands
from the indoor unit
FILE NO. SVM-10049
Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown command
Defrost control in heating operation
(Temperature measurement by the Indoor heat exchanger, control the four-way valve and
outdoor fan motor control)
7-2-1.
(1)
(2) Swing
7-2-2. Indoor Fan Control
Table (7-2-1) Cooling
Louver contr
V
er
tical air flow louver
ol
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [SWING] button is pressed, it stops swinging.
The operation controls the fan speed at indoor unit side. The indoor fan (cross flow fan) is operated by the phase control induction motor. The fan rotates in 5 stages in MANUAL mode, and in 5 stages in AUTO mode, respectively. (Table 7-2-3)
1) When setting the fan speed to L, L+,M, M+ or H on the remote controller, the operation is performed with the constant speed shown in Table 7-2-1 and Table 7-2-2
Table (7-2-2) Heating
Indication
L L+
M M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Indication L L+
M M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
2) When setting the fan speed to AUTO on the remote controller, revolution of the fan motor is controlled to the fan speed level show in Table 7-2-3 according to the setup temperature, room temperature,
Table 7-2-3 Indoor fan and air flow rate
OPERATION
MODE
RAS-24SKP-ES2
Model
OPERATION
MODE
RAS-24SKHP-ES2
Model
Cooling Fan only Dr
rpm
ir flow volume (m3/h)
Cooling Fan only Dr Heat
rpm
ir flow volume (m3/h)
UH
1340
1240
UH H M+ M L+ L L- UL SL
UH H M+ M L+ L L- UL SL
1340
1240
and heat exchanger temperature.
FAN TA
H M+ M L+ L L- UL SL H M+ M L+ L L-
M+ M L+ L L- UL SL
1220 1100 1025 950 850 700 600
1120 1000 930 850 750 600 500
FAN TA
H M+ M L+ L L-
M+ M L+ L L- UL SL
1220 1100 1100 950 950 950 850 700 600
1120 1000 1000 850 850 850 750 600 500
- 18 -
FILE NO. SVM-10049
7-3. Description of Operation Mode
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation can be effected thereafter simply by pressing [ ] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, (Heat pump model
only) outdoor fan and operation display lamp are controlled as shown in Fig. 7-3-2.
° C
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
OPERATION
(Room temp.) (Preset temp.)
Preset temp.
0.5
0
Fig. 7-3-2
display lamp
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) (Preset temp.)
Preset temp.
0
(Preset temp.: 24 °C)
NOTE 1 : *1 : Fan speed = (M + L) x 3/4 + L
*2 : Fan speed = (M + L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
2 : The Hi Power, ECO and COMFORT SLEEP
operation can not be set
(Linear approximation from M+ and L)
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
M+
*1
*2
*3
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
°C
(Room temp.) (Preset temp.)
Preset temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*2
*3
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 1/4 + L
(Linear approximation from M+ and L)
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
- 19 -
FILE NO. SVM-10049
7-3-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, (Heat pump model
only) outdoor fan and operation display lamp are controlled as shown in Fig. 7-3-4.
° C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
OPERATION
display lamp
(Room temp.) (Preset temp.)
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-3-4
7-3-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-3-6.
° C
Preset temp.
0
0.5
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
Fig. 7-3-6
display lamp
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-3-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L. *S.L. S.L.L. L. S.L. L.
*Super Low
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO, COMFORT SLEEP, QUIET and
Hi POWER operations can not be set.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-7. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
Preset temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) (Preset temp.)
L
*1 *2
+
M
H
*1 : Fan speed = (M + L) x 1/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L *3 : Fan speed = (M + L) x 3/4 + L
(Calculated with Linear approximation from M+ and L+)
Fig. 7-3-7
- 20 -
FILE NO. SVM-10049
y.
c
e
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-3-8
Fan speed AUTO Fan speed MANUAL
46Tc34 45 33
33 21 32 20
*A+0 *A+0
*A-8 *A-8
Fan speed MANUAL or AUTO in starting Fan speed AUTO in stability
* No limitation while fan speed MANUAL mode is in stabilit * A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
Normal AUTO
Line-approximate H and SL with Tc.
SL (W2)
Stop
L-H (Up to setting speed)
Line-approximate H and SL with Tc.
SL (W2)
Stop
[In starting and in stability]
In starting
FAN • Until 12 minutes
AUTO
FAN Room temp. < Set
Manual
passed after operation start
When 12 to 25 minutes
passed after operation start and room temp. is 3°C or lower than set temp.
temp.–4°C
In stability
When 12 to 25 minutes
passed after opeartion start and room temp. is than (set ) between preset
When 25 minutes or
more passed after operation start
Room temp. Set
temp. –3.5°C
3°C
7-3-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-3-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-3-9.
°C
Cooling operation
0
Fan only operation
-1
Heating operation
(Room temp.) (Preset temp.)
Heat pump model Cooling model
Fig. 7-3-9
Fig. 7-3-8 Cold draft preventing control
(4) In order to prevent cold draft when compressor
during heating operation.Then louver will move to upper position and fan speed will reduce or OFF.
- 21 -
7-4. Drescription of Safety and Reliability Prevention Function
FILE NO. SVM-10049
7-4-1. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Heat exchanger temperature
(°C)
7
4
Compressor Outdoor fan
ON
Less than 4°C continues
for 5 minutes
OFF
Fig. 7-4-1
7-4-2 High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-2.
7-4-3. Defrost Operation *Heat pump model only
When the indoor unit is in heating operation, if the refrigerant evaporation temperature detected by the outdoor heat exchanger sensor is under the specified temperature, the outdoor unit starts the defrosting operation. At this time, the 4-way valve relay and the outdoor fan motor are turned off. The indoor fan motor is also turned off by the cold draft preventing control of the indoor microcomputer. Then, [PRE. DEF.] lamp on the indoor unit comes on. The defrosting operation stops and the 4-way valve relay, outdoor fan motor and the indoor fan motor are turned on automatically when the refrigerant evaporation increases to the specified temperature, or when the defrosting time is over 12 minutes.
7-4-3-1. Defrost starting condition
A-Zone : If -10°C > Teo
start when. Teo - Te
~ 30 min after operation.
B-Zone : If Te
-18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC
Teo ≥ -10°C defrost will start when
Teo - Te -3°C at least 20 sec or ~ 60 min after operation.
- 18°C, defrost will
2.5°C at teat 20 sec or
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Fig. 7-4-2
Heat exchanger temp.
(°C) 62
55 54
7-4-3-2. Defrost finish condition.
1) If Te 3°C at least 60 sec -->4 way value on.
2) If Te 8°C --> 4 way value on.
Timing
Operation time (4 Loops = Tt)
Td1
Td2
Td3 Td4
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100 Heating time rate : (Tt - Td) x Tt
Fig. 7-4-3
- 22 -
FILE NO. SVM-10049
7-5. One-Touch Operation
(Heatpump Model : RAS-24SKHP-ES2)
One touch comfort is the fully automated operation that is set according to the preferable condition in a region.
Fan Operation
AUTO
*AUTO/L
L
0
*AUTO/L : Fan operates depends on the setting temperature and room temperature.
During the One Touch Comfort mode if the indoor unit receives any signal with other operation mode, the unit will cancel the comfort mode and operates according to the signal received.
Operation description
When an indoor unit receives "One Touch Comfort Signal" from the remote controller, the indoor unit operates as following.
1) Air conditioner starts to operation when the signal is received, even if the air conditioner was OFF.
2) Operation mode is set according to room temperature, the same as AUTO mode.
3) Target temperature is 24ºC.
4) Louver position is set as stored position.
(Cooling Only Model : RAS-24SKP-ES2)
One touch comfort is the fully automated operation that is set according to the preferable condition in a region.
Fan Operation
Hi-POWER
12
Fig. 7-5-1
25
*AUTO/L
Time after operation starts (min)
0
*AUTO/L : Fan operates depends on the setting temperature and room temperature.
During the One Touch Comfort mode if the indoor unit receives any signal with other operation mode, the unit will cancel the comfort mode and operates according to the signal received.
Operation description.
When an indoor unit receives "One Touch Comfort Signal" from the remote controller, the indoor unit operates as following.
1) Air conditioner starts to operation when the signal is received, even if the air conditioner was OFF.
2) Operation mode is set Cooling mode.
3) Target temperature is 22ºC.
4) Louver position is set swing.
5) Fan is controlled as diagram.
12
Fig. 7-5-2
25
- 23 -
Time after operation starts (min)