Toshiba RAS-10NKVX-T, RAS-13NKVX-T, RAS-10GKV-E2, RAS-10GAV-E2, RAS-10NKV-A2 SERVICE MANUAL

...
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
RAS-10GKV-E2 / RAS-10GAV-E2 RAS-13GKV-E2 / RAS-13GAV-E2 RAS-16GKV-E2 / RAS-16GAV-E2
RAS-10NKV-A2 / RAS-10NAV-A2
FILE NO. SVM-06032
RAS-13NKV-A2 / RAS-13NAV-A2 RAS-16NKV-A2 / RAS-16NAV-A2 RAS-10NKVX-T / RAS-10NAVX-T RAS-13NKVX-T / RAS-13NAVX-T
June, 2006
1. SPECIFICATIONS
1-1 Specifications 1-2 Operation Characteristic Curve 1-3 Capacity Variation Ratio According to Temperature
2. REFRIGERANT R410A
2-1 Safety During Installation/Servicing 2-2 Refrigerant Piping Installation 2-3 Tools 2-4. Recharging of Refrigerant 2-5. Brazing of Pipes
3. CONSTRUCTION VIEWS
3-1 Indoor Unit 3-2 Outdoor Unit
4. WIRING DIAGRAM
4-1 Indoor Unit (For 10, 13 Series) 4-2 Indoor Unit (For 16 Series)
4-3 Outdoor Unit (For 10 Series) 4-3 Outdoor Unit (For 13,16 Series)
FILE NO. SVM-06032
5. SPECIFICATION OF ELECTRICAL PARTS
5-1 Indoor Unit (For 13NKV) 5-2 Indoor Unit (For 16NKV) 5-3 Outdoor Unit (For 10NAV)
5-4 Outdoor Unit (For 13NAV) 5-5 Outdoor Unit (For 16NAV)
6. REFRIGERANT CYCLE DIAGRAM
6-1 Refrigerant Cycle Diagram 6-2 Operation Data
7. CONTROL BLOCK DIAGRAM
7-1 Indoor Unit 7-2 Outdoor Unit (Inverter Assembly)
8. OPERATION DESCRIPTION
8-1 Outlined of Air Conditioner Control 8-2 Description of Operation Circuit 8-3 Temporary Operation 8-4 Auto Restart Function 8-5 Filter Check Lamp 8-6 Remote Control and its Functions
9. INSTALLATION PROCEDURE
9-1 Safety Cautions 9-2 Indoor Unit 9-3 Outdoor Unit
1
9. INSTALLATION PROCEDURE
9-1 Safety Cautions 9-2 Indoor Unit 9-3 Outdoor Unit
10. HOW TO DIAGNOSE THE TROUBLE
10-1 First Confirmation 10-2 Primary Judgment 10-3 Judgment by Flashing LED of Indoor Unit 10-4 Self-Diagnosis by Remote Control (Check Code) 10-5 Judgment of Trouble by Every Symptom 10-6 Check Code 1C (Miswiring in indoor/outdoor units) and 1E 10-7 How to Diagnose Trouble in Outdoor Unit 10-8 How to Check Simply the Main Parts 10-9 How to Simply Judge Whether Outdoor Fan Motor is Good or Bad
11. HOW TO REPLACE THE MAIN PARTS
11-1 Indoor Unit 11-2 Microcomputer 11-3 Outdoor Unit
FILE NO. SVM-06032
12. EXPLODED VIEWS AND PARTS LIST
12-1 Indoor Unit (E-Parts Assy) 12-2 Indoor Unit (For RAS-10,13,16GKV-E2 / NKV-E2) 12-3 Indoor Unit (For RAS-10,13NKVX-T) 12-4 Outdoor Unit (For 10 Series) 12-5 Outdoor Unit (For 13 Series) 12-6 Outdoor Unit (For 16 Series)
12-7 Outdoor Unit (E-Parts Assy) (For 10 Series) 12-8 Outdoor Unit (E-Parts Assy) (For 13 Series) 12-9 Outdoor Unit (E-Parts Assy) (For 16 Series)
2

1. SPECIFICATIONS

1-1. Specifications
RAS-10GKV-E2 / RAS-10GAV-E2, RAS-10NKV-A2 / RAS-10NAV-A2
FILE NO. SVM-06032
Unit model
Cooling capacity Cooling capacity range Heating capacity Heating capacity range
Power supply
Electric characteristics
COP (Cooling / Heating) Operation noise
Indoor unit Unit model
Outdoor unit Unit model
Piping connection Type
Refrigerant Name of refrigerant
Wiring connection Power supply
Usable temperature range Indoor (Cooling / Heating) (°C)
Indoor
Outdoor
Indoor
Outdoor (Cooling / Heating)
Dimension Height
Net weight Fan motor output Air flow rate (Cooling / Heating)
Dimension Height
Net weight Compressor Motor output
Fan motor output Air flow rate (Cooling / Heating)
Indoor unit Liquid side
Outdoor unit Liquid side
Maximum length (Per unit) Maximum chargeless length Maximum height difference
Weight
Operation mode Running current Power consumption Power factor Operation mode Running current Power consumption Power factor
High (Cooling / Heating) Medium (Cooling / Heating) Low (Cooling / Heating)
Width Depth
Width Depth
Type Model
Gas side
Gas side
Interconnection
Outdoor (Cooling / Heating) (°C)
(kW) (kW) (kW)
(kW)
(A) (W) (%)
(A) (W) (%)
(dB• A) (dB• A)
(dB• A) (dB• A)
(mm) (mm) (mm)
(kg) (W)
(m3/h)
(mm) (mm) (mm)
(kg) (W)
(W)
(m3/h)
(m) (m) (m)
(kg)
RAS-10GKV-E2 / RAS-10GAV-E2
RAS-10NKV-A2 / RAS-10NAV-A2
2.5
0.9 3.0
3.2
0.9 4.0
220240V1Ph50Hz
Cooling Heating
0.15 0.15 30 30 87 87
Single rotary type with DC-inverter variable speed control
Cooling Heating
3.33 3.69
730 810
95 95
3.29/3.81 38/39 34/35 27/29 46/47
RAS-10GKV-E2, RAS-10NKV-A2
275 790 218
10 20
540/610
RAS-10GAV-E2, RAS-10NAV-A2
530 660
240
30
750
DA89X1F-23FZ
20
1320/1320
Flare connection
6.359.52
6.359.52
10
10
8
R410A
0.64
3 Wires:includes earth (Outdoor)
4 Wires:includes earth
21 − 32 / Up to 27 °C
15 43 / 10 24
The specification may be subject to change without nitice for purpose of improvement.
– 3 –
RAS-10NKVX-T / RAS-10NAVX-T
Unit model
FILE NO. SVM-06032
RAS-10NKVX-T / RAS-10NAVX-T
Cooling capacity Cooling capacity range Heating capacity Heating capacity range
Power supply
Electric characteristics
COP (Cooling / Heating) Operation noise
Indoor unit Unit model
Outdoor unit Unit model
Piping connection Type
Refrigerant Name of refrigerant
Wiring connection Power supply
Usable temperature range Indoor (Cooling / Heating) (°C)
Indoor
Outdoor
Indoor
Outdoor (Cooling / Heating)
Dimension Height
Net weight Fan motor output Air flow rate (Cooling / Heating)
Dimension Height
Net weight Compressor Motor output
Fan motor output Air flow rate (Cooling / Heating)
Indoor unit Liquid side
Outdoor unit Liquid side
Maximum length (Per unit) Maximum chargeless length Maximum height difference
Weight
Operation mode Running current Power consumption Power factor Operation mode Running current Power consumption Power factor
High (Cooling / Heating) Medium (Cooling / Heating) Low (Cooling / Heating)
Width Depth
Width Depth
Type Model
Gas side
Gas side
Interconnection
Outdoor (Cooling / Heating) (°C)
(kW) (kW) (kW)
(kW)
(A) (W) (%)
(A) (W) (%)
(dB• A) (dB• A)
(dB• A) (dB• A)
(mm) (mm) (mm)
(kg) (W)
(m3/h)
(mm) (mm) (mm)
(kg) (W)
(W)
(m3/h)
(m) (m) (m)
(kg)
2.5
0.9 3.0
3.2
0.9 4.0
2201Ph50Hz
Cooling Heating
0.15 0.15 30 30 91 91
Single rotary type with DC-inverter variable speed control
Cooling Heating
3.64 4.02
760 840
95 95
3.29/3.81 38/39 34/35 27/29 46/47
RAS-10NKVX-T
275 790 218
10 20
540/610
RAS-10NAVX-T
530 660
240
30
750
DA89X1F-23FZ
20
1320/1320
Flare connection
6.359.52
6.359.52
10
10
8
R410A
0.64
3 Wires:includes earth (Outdoor)
4 Wires:includes earth
21 − 32 / Up to 27 °C
15 43 / 10 24
The specification may be subject to change without nitice for purpose of improvement.
4
RAS-13GKV-E2 / RAS-13GAV-E2, RAS-13NKV-A2 / RAS-13NAV-A2
FILE NO. SVM-06032
Unit model
Cooling capacity Cooling capacity range Heating capacity Heating capacity range
Power supply
Electric characteristics
COP (Cooling / Heating) Operation noise Indoor
Indoor unit Unit model
Outdoor unit Unit model
Piping connection Type
Refrigerant Name of refrigerant
Wiring connection Power supply
Usable temperature range Indoor (Cooling / Heating) (°C)
Indoor
Outdoor
Outdoor (Cooling / Heating)
Dimension Height
Net weight Fan motor output Air flow rate (Cooling / Heating)
Dimension Height
Net weight Compressor Motor output
Fan motor output Air flow rate (Cooling / Heating)
Indoor unit Liquid side
Outdoor unit Liquid side
Maximum length (Per unit) Maximum chargeless length Maximum height difference
Weight
Operation mode Running current Power consumption Power factor Operation mode Running current Power consumption Power factor
High (Cooling / Heating) Medium (Cooling / Heating) Low (Cooling / Heating)
Width Depth
Width Depth
Type Model
Gas side
Gas side
Interconnection
Outdoor (Cooling / Heating) (°C)
(kW) (kW) (kW)
(kW)
(A) (W) (%)
(A) (W) (%)
(dB• A) (dB• A)
(dB• A) (dB• A)
(mm) (mm) (mm)
(kg) (W)
(m3/h)
(mm) (mm) (mm)
(kg) (W)
(W)
(m3/h)
(m) (m) (m)
(kg)
RAS-13GKV-E2 / RAS-13GAV-E2
RAS-13NKV-A2 / RAS-13NAV-A2
3.5
1.1− 4.0
4.2
1.1 5.8
220240V1Ph50Hz
Cooling Heating
0.15 0.15 30 30 87 87
Cooling Heating
4.70 4.97
1040 1100
96 96
3.27/3.72 39/39 33/34 26/28 48/50
RAS-13GKV-E2, RAS-13NKV-A2
275 790 218
10 20
590/620
RAS-13GAV-E2, RAS-13NAV-A2
550 780 270
36
750
Single rotary type with DC-inverter variable speed control
DA89X1F-23FZ
43
2410/2410
Flare connection
6.359.52
6.359.52
15
15
10
R410A
0.8
3 Wires:includes earth (Outdoor)
4 Wires:includes earth
21 − 32 / Up to 27 °C
15 43 / 10 24
The specification may be subject to change without notice for purpose of improvement.
5
RAS-13NKVX-T / RAS-13NAVX-T
Unit model
FILE NO. SVM-06032
RAS-13NKVX-T / RAS-13NAVX-T
Cooling capacity Cooling capacity range Heating capacity Heating capacity range
Power supply
Electric characteristics
COP (Cooling / Heating) Operation noise Indoor
Indoor unit Unit model
Outdoor unit Unit model
Piping connection Type
Refrigerant Name of refrigerant
Wiring connection Power supply
Usable temperature range Indoor (Cooling / Heating) (°C)
Indoor
Outdoor
Outdoor (Cooling / Heating)
Dimension Height
Net weight Fan motor output Air flow rate (Cooling / Heating)
Dimension Height
Net weight Compressor Motor output
Fan motor output Air flow rate (Cooling / Heating)
Indoor unit Liquid side
Outdoor unit Liquid side
Maximum length (Per unit) Maximum chargeless length Maximum height difference
Weight
Operation mode Running current Power consumption Power factor Operation mode Running current Power consumption Power factor
High (Cooling / Heating) Medium (Cooling / Heating) Low (Cooling / Heating)
Width Depth
Width Depth
Type Model
Gas side
Gas side
Interconnection
Outdoor (Cooling / Heating) (°C)
(kW) (kW) (kW)
(kW)
(A) (W) (%)
(A) (W) (%)
(dB• A) (dB• A)
(dB• A) (dB• A)
(mm) (mm) (mm)
(kg) (W)
(m3/h)
(mm) (mm) (mm)
(kg) (W)
(W)
(m3/h)
(m) (m) (m)
(kg)
3.5
1.1− 4.0
4.2
1.1 5.8
220V1Ph50Hz
Cooling Heating
0.15 0.15 30 30 91 91
Cooling Heating
4.85 5.13
1040 1100
97 97
3.27/3.72 39/39 33/34 26/28 48/50
RAS-13NKVX-T
275 790 218
10 20
590/620
RAS-13NAVX-T
550 780 270
36
750
Single rotary type with DC-inverter variable speed control
DA89X1F-23FZ
43
2410/2410
Flare connection
6.359.52
6.359.52
15
15
10
R410A
0.8
3 Wires:includes earth (Outdoor)
4 Wires:includes earth
21 − 32 / Up to 27 °C
15 43 / 10 24
The specification may be subject to change without notice for purpose of improvement.
6
RAS-16GKV-E2 / RAS-16GAV-E2, RAS-16NKV-A2 / RAS-16NAV-A2
FILE NO. SVM-06032
Unit model
Cooling capacity Cooling capacity range Heating capacity Heating capacity range
Power supply
Electric characteristics
COP (Cooling / Heating) Operation noise Indoor
Indoor unit Unit model
Outdoor unit Unit model
Piping connection Type
Refrigerant Name of refrigerant
Wiring connection Power supply
Usable temperature range Indoor (Cooling / Heating) (°C)
Indoor
Outdoor
Outdoor (Cooling / Heating)
Dimension Height
Net weight Fan motor output Air flow rate (Cooling / Heating)
Dimension Height
Net weight Compressor Motor output
Fan motor output Air flow rate (Cooling / Heating)
Indoor unit Liquid side
Outdoor unit Liquid side
Maximum length (Per unit) Maximum chargeless length Maximum height difference
Weight
Operation mode Running current Power consumption Power factor Operation mode Running current Power consumption Power factor
High (Cooling / Heating) Medium (Cooling / Heating) Low (Cooling / Heating)
Width Depth
Width Depth
Type Model
Gas side
Gas side
Interconnection
Outdoor (Cooling / Heating) (°C)
(kW) (kW) (kW)
(kW)
(A) (W) (%)
(A) (W) (%)
(dB• A) (dB• A)
(dB• A) (dB• A)
(mm) (mm) (mm)
(kg) (W)
(m3/h)
(mm) (mm) (mm)
(kg) (W)
(W)
(m3/h)
(m) (m) (m)
(kg)
RAS-16GKV-E2 / RAS-16GAV-E2
RAS-16NKV-A2 / RAS-16NAV-A2
4.62
1.2− 5.2
5.9
1.3 7.4
220− 240V Ph 50Hz
Cooling Heating
0.2 0.2 30 30 65 65
Cooling Heating
7.20 7.60
1590 1700
96 97
2.85/3.41 45/44 40/40 34/34 51/53
RAS-16GKV-E2, RAS-16NKV-A2
275 790 218
10 30
760/780
RAS-16GAV-E2, RAS-16NAV-A2
550 780 270
39
1100
Twin rotary type with DC-inverter variable speed control
DA130A1F-24F
43
2410/2410
Flare connection
6.3512.7
6.3512.7
15
15
10
R410A
0.95
3 Wires:includes earth (Outdoor)
4 Wires:includes earth
21 − 32 / Up to 27 °C
15 43 / 10 24
The specification may be subject to change without notice for purpose of improvement.
7
1-2.Operation Characteristic Curve
A
A
A
A
RAS-10GAV-E2, RAS-13GAV-E2 RAS-10NAV-A2, RAS-13NAV-A2
<Cooling> <Heating>
FILE NO. SVM-06032
6
5
RAS-10GAV-E2
4
RAS-10NAV-A2
RAS-13GAV-E2
RAS-13NAV-A2
3
Current (A)
2
1
Conditions Indoor : DB 27 Outdoor : DB 35
ir flow : High Pipe lenght : 5 m Voltage : 230V
o
C/WB 19oC
o
C
0
0 20406080100
6
5
4
3
Current (A)
RAS-10GAV-E2 RAS-10NAV-A2
2
1
0
020406080100
Compressor speed (rps)
RAS-10NAVX-T, RAS-13NAVX-T
<Cooling> <Heating>
RAS-13GAV-E2 RAS-13NAV-A2
Conditions Indoor : DB 20 Outdoor : DB 7
ir flow : High Pipe lenght : 5 m Voltage : 230V
Compressor speed (rps)
o
C
o
C/WB 6oC
6
5
4
RAS-10NAVX-T
RAS-13NAVX-T
3
Current (A)
2
1
Conditions Indoor : DB 27 Outdoor : DB 35
ir flow : High
Pipe lenght : 5 m
age : 220V
Volt
o
C/WB 19oC
o
C
0
0 20406080100
Compressor speed (rps)
6
RAS-13NAVX-T
5
4
3 Current (A)
RAS-10NAVX-T
2
Conditions Indoor : DB 20
1
Outdoor : DB 7
ir flow : High
Pipe lenght : 5 m
age : 220V
Volt
o
C
o
C/WB 6oC
0
020406080100
Compressor speed (rps)
8
RAS-16GAV-E2, RAS-16NAV-A2
A
A
<Cooling> <Heating>
FILE NO. SVM-06032
10
8
6
Current (A)
4
Conditions Indoor : DB 27
2
Outdoor : DB 35
ir flow : High Pipe lenght : 5 m Voltage : 230V
°C/WB 19°C
°C
0
0 20 40 60 80 100 120
Compressor speed (rps)
10
8
6
Current (A)
4
Conditions Indoor : DB 20
2
Outdoor : DB 7
ir flow : High Pipe lenght : 5 m Voltage : 230V
°C
°C/WB 6°C
0
0 20406080100120
Compressor speed (rps)
1-3.Capacity Variation Ratio According to Temperature
<Cooling> <Heating>
105 100
95 90 85 80 75 70
Capacity ratio (%)
65 60 55 50
32 34
Current Limited Start
Conditions Indoor : DB27°C/WB19°C Indoor air flow : High Pipe length 5m
36 38 40 4233 35 37 39 41 43
Outdoor temp. (°C)
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
−10−9−8−7−6−5−4−3−2−1012345678910
Conditions
Indoor : DB 20°C Indoor air flow : High Pipe length : 5m
Outdoor temp. (°C)
Capacity ratio : 100% = Nominal Capacity
*
9
2. REFRIGERANT R410A
FILE NO. SVM-06032
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is
1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
2-1.Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materials exclu­sive for R410A, it is necessary to carry out installation/ servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A. If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use tools
and materials exclusive for the refrigerant R410A. The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22
(3) If a refrigeration gas leakage occurs during instal-
lation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture of personal injury may be caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level. If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual. Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician. Improper repair’s may result in water leakage, electric shock and fire, etc.
2-2.Refrigerant Piping Installation
2-2-1. Piping materials and joints used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suit­able for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table 2-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
10
FILE NO. SVM-06032
Table 2-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter Outer diameter (mm) R410A R22
1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.70 0.80 0.80 5/8 15.88 1.00 1.00
(2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used. Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 2-2-3 to 2-2-6 below.
Table 2-2-2 Minimum thicknesses of socket joints
Nominal diameter
Reference outer diameter of Minimum joint thickness
1/4 6.35 0.50 3/8 9.52 0.60 1/2 12.70 0.70 5/8 15.88 0.80
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 2-2-2.
copper pipe jointed (mm) (mm)
2-2-2. Processing of piping materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
11
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
D
A
Fig. 2-2-1 Flare processing dimensions
FILE NO. SVM-06032
Table 2-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
1/4 6.35 0.8 0 to 0.5 1.0 to 1.5 1.5 to 2.0 3/8 9.52 0.8 0 to 0.5 1.0 to 1.5 1.5 to 2.0 1/2 12.70 0.8 0 to 0.5 1.0 to 1.5 2.0 to 2.5 5/8 15.88 1.0 0 to 0.5 1.0 to 1.5 2.0 to 2.5
Nominal
diameter
1/4 6.35 0.8 0 to 0.5 0.5 to 1.0 1.0 to 1.5 3/8 9.52 0.8 0 to 0.5 0.5 to 1.0 1.0 to 1.5 1/2 12.70 0.8 0 to 0.5 0.5 to 1.0 1.0 to 2.0
Outer
diameter
(mm)
Table 2-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
Thickness
(mm)
Thickness
(mm)
Flare tool for R410A
clutch type
Flare tool for R410A
clutch type
A (mm)
Conventional flare tool
Clutch type Wing nut type
A (mm)
Conventional flare tool
Clutch type Wing nut type
5/8 15.88 1.0 0 to 0.5 0.5 to 1.0 1.0 to 2.0
Table 2-2-5 Flare and flare nut dimensions for R410A
Nominal
diameter
1/4 6.35 0.8 9.1 9.2 6.5 13 17 3/8 9.52 0.8 13.2 13.5 9.7 20 22 1/2 12.70 0.8 16.6 16.0 12.9 23 26 5/8 15.88 1.0 19.7 19.0 16.0 25 29
Nominal
diameter
1/4 6.35 0.8 9.0 9.2 6.5 13 17
Outer
diameter
(mm)
Outer
diameter
(mm)
Thickness
(mm)
Table 2-2-6 Flare and flare nut dimensions for R22
Thickness
(mm)
ABCD
ABCD
Dimension (mm)
Dimension (mm)
Flare nut
width
(mm)
Flare nut
width
(mm)
3/8 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24 5/8 15.88 1.0 19.7 19.0 16.0 23 27 3/4 19.05 1.0 23.3 24.0 19.2 34 36
12
FILE NO. SVM-06032
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do
not have any scar or dust, etc.
b) Correctly align the processed flare surface with
the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
Table 2-2-7 Tightening torque of flare for R410A [Reference values]
Nominal Outer diameter Tightening torque
diameter (mm) N·m (kgf·m)
1/4 6.35 14 to 18 (140 to 180) 16 (160), 18 (180) 3/8 9.52 33 to 42 (330 to 420) 42 (420) 1/2 12.70 50 to 62 (500 to 620) 55 (550) 5/8 15.88 63 to 77 (630 to 770) 65 (650)
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manuf acturers. Table 2-2-7 shows reference values.
Note:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N·m (kgf·m)
13
FILE NO. SVM-06032
2-3. T ools
2-3-1. Required tools
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For 12.70 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A air conditioner Conventional air
installation conditioner installation
No. Used tool Usage Existence of Whether Whether new equipment
new equipment conventional can be used with for R410A equipment can conventional refrigerant
be used
1 Flare tool Pipe flaring Yes *(Note 1) 2 Copper pipe gauge Flaring by
for adjusting projection conventional flare Yes *(Note 1) *(Note 1) margin tool
3 Torque wrench Connection of
(For 12.70) flare nut
4 Gauge manifold 5 Charge hose
6 Vacuum pump adapter Vacuum evacuating Yes
Electronic balance for
7
refrigerant charging
8 Refrigerant cylinder Refrigerant charge Yes 9 Leakage detector Gas leakage check Yes ! Charging cylinder Refrigerant charge (Note 2)
Evacuating, refrigerant charge, Yes run check, etc.
Refrigerant charge Yes
Yes
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools. (1) Vacuum pump (4) Reamer (9) Hole core drill (∅65)
Use vacuum pump by (5) Pipe bender (10) Hexagon wrench
attaching vacuum pump adapter. (6) Level vial (Opposite side 5 mm) (2) Torque wrench (For 6.35) (7) Screwdriver (+, –) (11) Tape measure (3) Pipe cutter (8) Spanner of Monkey wrench (12) Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (3) Insulation resistance tester (2) Thermometer (4) Electroscope
– 14
FILE NO. SVM-06032
2-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
When the compound gauges pointer has indi­cated -0.1 Mpa (-76 cmHg), place the handle Low
Connect the charge hose to packed valve service port at the outdoor units gas side.
in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
Place the handle of the gauge manifold Low in
(For refrigerant charging, see the figure below.)
the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
1 Never charge refrigerant exceeding the specified amount. 2 If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode. 3 Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 15
(OUTDOOR unit)
Opened
Closed
Service port
FILE NO. SVM-06032
1 Be sure to make setting so that liquid can be charged. 2 When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[Cylinder with siphon] [Cylinder without siphon]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment varies.
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Siphon
Fig. 2-4-2
2-5. Brazing of Pipes
2-5-1. Materials for brazing (1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1 Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound water solution, which may cause a gas leakage . Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2 When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux (1) Reason why flux is necessary
By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
In the brazing process, it prevents the metal surface from being oxidized.
By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
– 16
FILE NO. SVM-06032
(2) Characteristics required for flux
Activated temperature of flux coincides with the brazing temperature.
Due to a wide effective temperature range, flux is hard to carbonize.
It is easy to remove slag after brazing.
The corrosive action to the treated metal and
brazing filler is minimum.
It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing temperature is higher than 800°C.
Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
2-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified. In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
1 Attach a reducing valve and a flow-meter to the
Nitrogen gas cylinder.
2 Use a copper pipe to direct the piping material,
and attach a flow-meter to the cylinder.
3 Apply a seal into the clearance between the
piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4 When the Nitrogen gas is flowing, be sure to
keep the piping end open.
5 Adjust the flow rate of Nitrogen gas so that it is
lower than 0.05 m3/Hr or 0.02 Mpa (0.2 kgf/ cm2) by means of the reducing valve.
6 After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7 Remove the flux completely after brazing.
(4) Piping materials for brazing and used brazing
filler/flux
Piping Used brazing Used
material filler flux
Copper - Copper Phosphor copper Do not use
Copper - Iron Silver Paste flux
Iron - Iron Silver Vapor flux
1 Do not enter flux into the refrigeration cycle. 2 When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
3 When adding water to the flux, use water which
does not contain chlorine (e.g. distilled water or ion-exchange water).
4 Remove the flux after brazing.
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Rubber plug
Nitrogen gas
Fig. 2-5-1 Prevention of oxidation during brazing
17
3-1. Indoor Unit
Front panel
FILE NO. SVM-06032

3. CONSTRUCTION VIEWS

60
6
Knock out system
Air inlet
Air filter
Heat exchanger
790
275
Air outlet
64
120 80
590
Hanger
218
60
6
48
Knock out system
48
53
Drain hose (0.54m)
Hanger
45
Minimum distance to ceiling
275
170 or more
320
620
235 235
215 215
Minimum distance to ceiling
65 or more
Hanger
– 18
Connecting pipe (0.43m)
(Flare 6.35) Connecting pipe (0.33m) (For 10,13 series ; Flare 9.52
For 16 series ; Flare 12.7)
Hanger
For stud bolt (6)
Hanger
150150 160160
Installation plate outline
Center line
For stud bolt (8~10)
26
Minimum distance to ceiling
170 or more
32
9090
4519040
160
57 18
Wireless remote control
3-2. Outdoor Unit
RAS-10GAV-E2, RAS-10NAV-A2, RAS-10NAVX-T
A
A Detail Drawing (Back Leg)
6 Hole
273.5
265
50 36
660
R 15
R 5.5
59.5
273.5
Fan guard
25Drain outlet
97
2-11x14 hole (for 8-10 anchor bolt)
B
FILE NO. SVM-06032
B Detail Drawing (Front Leg)
265
273.5
6 Hole
11x14 Hole
36 50
R 15
660
Cover PV
242
530
420
500 97.5 660
Z View
56
(11)
126
48
Z
(12.5)273.5 (pitch)
297
Liquid side
(Flare 6.35) Gas side (Flare 9.52)
54
Service port
Installation dimension
45 or more
273.5
100 or more
Air outlet
500
Air inlet
100 or more
– 19
600 or more
4x11x14 Long holes (for 8-10 anchor bolt)
3-3. Outdoor Unit
RAS-13GAV-E2, RAS-13NAV-A2, RAS-13NAVX-T RAS-16GAV-E2, RAS-16NAV-A2
A
FILE NO. SVM-06032
A Detail drawing (Back Leg)
6 Hole
310
600 52 36
302
270
R15
R5.5
32.5
310
302
30 Drain outlet
436
550
265
FAN GUARD
115 125
2-11 x 14 Hole (For 8-10 anchor bolt)
600 780
90
102
6 Hole
11 x 14 Hole
B
62
B Detail drawing (Front Leg)
310
302
36 52
R15
310 330
COVER PV
Z
Electrical part cover
100 or more
310
100 or more
Z View
Installation dimension
600
Air inlet
Air outlet
600 or more
4 x 11 x 14 Long holes (For 8 10 anchorbolt)
600 or more
120
75
Liquid side (Flare 6.35) Gas side (Flare 9.52 : For
13k Series) (Flare ∅12.7 : For 16k Series)
54
Service port
20

4. WIRING DIAGRAM

4-1. Indoor Unit (For 10,13 Series)
COLOR INDICATION
:
BROWN
BRW
:
RED
RED
:
WHITE
WHI
:
YELLOW
YEL
:
BLUE
BLU
:
BLACK
BLK
:
GRAY
GRY
:
PINK
PNK
:
ORANGE
ORN
:
GREEN & YELLOW
GRN&YEL
:
GREEN
GRN
BLK BLK
HEAT EXCHANGER
SENSOR
(TC)
BLK
BLK
THERMO SENSOR
(TA)
CN25 (WH I)
BLU
1
1
BLU
2
2
BLU
3
3
BLU
4
4
BLU
5
5
BLU
6
6
BLU
7
7
BLU
8
8
BLU
9
9
RECEIVING AND
INFRARED RAYS
MCC-861
MCC-861
BLU
10
10
INDICATING PARTS
WHI
11
11
1
CN01 (BLU)
1
2
CN03 (WHI)
1
2
CN13 (WHI)
1
2
3
4
5
6
7
8
9
10
11
4
10
11
TERMINAL
1
2
1
2
1
2
3
4
5
6
7
8
9
BLOCK
2
FUSE
F01
T3.15A
250VAC
MAIN P.C. BOARD
WP-004
1
BLK WHI RED
CN24
CN23
3
CN08
1
2
HA
JEM-A
CN21
3
R04
4
LINE
FILTER
Fan Motor
Drive ci rcuit
CN11 CN10
1
2
3
2
3
1
YEL
GRY
BRW
1
2
4
3
4
1
3
2
150°C
INDOOR
UNIT
Power
supply circ uit
+12 VDC
+5 VDC
5
5
WHI
6
5
5
6
FILE NO. SVM-06032
OUTDOOR
UNIT
5
CN07
(WH I)
WHI
1
2
3
4
5
3
1
1
3
BLK
RED
AC FAN MOTOR
1
1
YEL
2
2
YEL
3
3
YEL
4
4
YEL
5
5
LOUVER MOTOR
6
1
2
3
4
5
Simple Check for Failure Diagnosis
Chec k I tem
Check to see if the OPERATION indicator goes on
OPERAT ION
1
INDICATOR
TERMINAL
2
3
4
5
6
(AC 220~24 0V)
and off when t he main switc h or brea ker is turned on. (Check the prima ry and secondary voltage of the transformer.)
Check the power suppl y voltage between and . (Refer to the name plate.) (Check the prima ry and secondary voltage of the transformer.)
BLOCK
Check the fluctuating voltage between and . (15~60VDC)
Check to see if the fuse blows out.
FUSE
(Check the R04 of the vari stor.)
3.15A
Check the voltage at the No.4 pin on CN13 connector of the infr ared receiver.
DC5V
(Check the transfor mer an d the power supply ci rcuit of the rated voltage.)
Check the voltage at the white lead of the louver motor.
DC12V
(Check the transfor mer an d the power supply ci rcuit of the rated voltage.)
Check the voltage at the No.1 pin on CN10 connecto r and CN24. (Check the F01)
Refer to the service data for the detailed failure diagnosis.
Diagnosis Result
1
2
2
3
21
4-2. Indoor Unit (For 16 Series)
COLOR INDICATION
:
BROWN
BRW
:
RED
RED
:
WHITE
WHI
:
YELL OW
YEL
:
BLUE
BLU
:
BLACK
BLK
:
GRAY
GRY
:
PINK
PNK
:
ORANGE
ORN
:
GREEN & YE LLOW
GRN&YEL
:
GREEN
GRN
BLK BLK
HEAT EXCHANGER
SENSOR
(TC)
THERMO SENSOR
(TA)
RECEIVING AND
INFRARED RAYS
INDICATING PARTS
MCC-861
MCC-861
CN25
(WHI)
1
2
3
4
5
6
7
8
9
10
11
BLK
BLK
BLU
1
BLU
2
BLU
3
BLU
4
BLU
5
BLU
6
BLU
7
BLU
8
BLU
9
BLU
10
WHI
11
1
CN01 (BLU)
1
2
CN03 (WHI)
1
2
CN13
(WHI)
1
2
3
4
5
6
7
8
9
10
11
4
1
2
1
2
1
2
3
4
5
6
7
8
9
10
11
TERMINAL
BLOCK
T3.15A
MAIN P.C. BOARD
MCC-867or MCC-5014
FUSE
F01
250VAC
2
BLK
CN24
1
WHI
CN23
3
2
1
3
RED
R04
CN08
3
2
HA
JEM-A
CN21
FILTER
4
LINE
R05
DB01
~
-+ ~
C03
DC5V DC12V
+
INDOOR
UNIT
FILE NO. SVM-06032
OUTDOOR
UNIT
CN10
6
(WHI)
1
3
4
5
6
CN07 (WHI)
1
2
CIRCUIT
3
4
POWER SUPPLY
5
FAN MOTOR
RED
1
BLK
3
4
5
6
WHI YEL BLU
DC MOTOR
5
WHI
1
1
2
3
4
5
1
YEL
2
2
YEL
3
3
YEL
4
4
YEL
5
5
LOUVER MOTOR
Simple Check for Failure Diagnosis
Check Item
OPERATION
1
INDICATOR
TERMINAL
2
BLOCK
3
4
5
6
(DC310 340V)
DC12V
DC325V
~
Check to see if the OPERATION indicator goes on and off when the main switch or breaker is turned on. (Check the primary and secondary voltage of the transformer.)
Check the power supply voltage between 1 and (Refer to the name plate.) (Check the primary and secondary voltage of the transformer.) Check the fluctuating voltage between and . (15
60VDC)
~
Check to see if the fuse blows out.
FUSE
(Check the R04 of the varistor.)
3.15A
Check the voltage at the No.4 pin on CN13 connector of the infrared receiver.
DC5V
(Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the white lead of the louver motor. (Check the transformer and the power supply circuit of the rated voltage.)
Check the voltage at the No.1 pin on CN10 connector. (Check the DB01, R05 and C03.)
Refer to the service data for the detailed failure diagnosis.
Diagnosis Result
2
2
.
3
22
FILE NO. SVM-06032
RAS-10GAV-E2, RAS-10NAV-A2,
RAS-10NAVX-T
4-3. Outdoor Unit
23
FILE NO. SVM-06032
RRAS-13GAV-E2, RAS-13NAV-A2, RAS-13NAVX-T
RAS-16GAV-E2, RAS-16NAV-A2
4-4. Outdoor Unit
24
FILE NO. SVM-06032

5. SPECIFICATION OF ELECTRICAL PARTS

5-1. Indoor Unit (For 13NKV)
No. Parts name Type Specifications
1 Fan motor (for indoor) SKF-220-20-4A-1 AC Motor with 150°C thermo fuse 2 Thermo. sensor (TA-sensor) ——— 10 k at 25°C 3 AC-AC transformer (T01) TT-10 187 - 276V, 6VA 4 Microcomputer 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) SS11V-06270 27 µH, AC 0.64A 7 Diode (DB01) KBP06M 1.5A, 420V 8 Capacitor (C50) 9 Fuse (F01) BET 3.15A, 250VAC T3.15A, 250 V
10 Regulator IC (IC08) NJM7812 12VDC, 1.5A max 11 Regulator IC (IC11) NJM7805 5VDC, 1.5A max 12 Varistor (R21, R109) TND15G561K 560V
µPD780024AGK
——— 10 k at 25°C
ELXV350ELL222ML35S 220µ F, 35V
13 Louver motor DC 12V
24BYJ48
5-2. Incoor Unit (For 16NKV)
No. Parts name Type Specifications
1 Fan motor (for indoor) ICF-340-30-2 DC 340 V, 30 W 2 Thermo. sensor (TA-sensor) ——— 10 k at 25°C 3 DC-DC transformer (T01) SWT-70 DC 390 V, Secondary DC 15 V, 12 V, 7 V 4 Microcomputer µPD780024AGK 5 Heat exchanger sensor
(TC-sensor) 6 Line filter (L01) SS11V-06270 27mH, AC 0.6A 7 Diode (DB01) D3SBA60 4A, 600 V 8 Capacitor (C03) KMH450VSSN120M25C 120µF, 450 V 9 Fuse (F01) FCU250V, 3.15A T3.15A, 250 V
10 Power supply IC (IC01) STR-L472 11 Regulator IC (IC01) NJM78M15FA 15DC, 1.5A max
12 Varistor (R21, R109) TND15G561K 560 V
——— 10 k at 25°C
13 Resistor (R01) RF-5TK4R7 4.7 , 5 W 14 Louver motor 24BYJ48 DC 12V
25
FILE NO. SVM-06032
5-3. Outdoor Unit (RAS-10GAV-E2, RAS-10NAV-A2, RAS-10NAVX-T)
No. Parts name Model name Rating
1 SC coil L01 ADR2516-0R6TB 0.6mH, 15A
(Noise filter) L03 ADR2510-020T4B 10A, 2mH
3 Reactor CH-51-Z-T L=19mH, 10A
4 Outside fan motor 5
Fan control relay
Outside air temp.
6
sensor (TO sensor) Heat exchanger temp.
7
sensor (TE sensor) Dischenge temp.
8
sensor (TD sensor)
SWT-72
HF-240-20B-2R
G5NB-1A Coil DC12V Contact AC250V-1.5A
(Inverter attached) 10k(25°C)
(Inverter attached) 10k(25°C)
(Inverter attached) 62k(20°C)
20W
Primary side DC280V, Secondary2 DC-DC transformer
side 7.0 V x 1, 12 V x 1, 17V x 2
9
Terminal block (6P)
Fuse
10
11
Electrolytic capacitor LLQ2G761KHUBTF 760µF, DC 400 V x 3 pieces
12
IGBT GT20J321 20A, 600
13
Compressor DA89X1C-23FZ 3-phases 4-poles 750W Compressor thermo. PW-2AL OFF: 125 ± 4°C, ON: 90 ± 5°C
14 15
Rectifier
16 4-way valve coil 17 Running capacitor DS451155NPQB
(for fan motor)
For protection of switching power source 3.15A, AC250V
For protection of inverter input overcurrent 25A, AC250V
JX0-6B
D25XB60-4001 20A, 600V
AC 450V~, 1.5µF
20A, AC250V
AC220-240V
26
FILE NO. SVM-06032
5-4. Outdoor Unit (RAS-13GAV-E2, RAS-13NAV-A2, RAS-13NAVX-T)
No. Parts name Model name Rating
1 SC coil L01 ADR2516-0R6TB 15A, 0.6mH
(Noise filter) L03 ADR2510-020T4B 20A, 0.15mH
3 Reactor CH-57-Z-T L=10mH, 16A x 2
4 Outside fan motor 5
Fan control relay
(Inverter atached) 10 k (25°C)
(TS sensor)
6
Discharge temp. sensor (TD sensor)
SWT-72
ICF-140-43-4R
(Inverter attached) 62k(20°C)
DC140V, 43W
Primary side DC280V, Secondary2 DC-DC transformer
side 7.0 V x 1, 12 V x 1, 17V x 2
Outside air temp. sensor
7
(TO sensor)
8
Heat exchanger temp.
sensor (TE sensor)
Terminal block (6P)
9
Fuse
10
11
Electrolytic capacitor LLQ2G761KHUBTF 760µ F, DC 400V x 3 pieces
12
IGBT GT20J321 20A, 600V Compressor DA89X1C-23FZ 3-phases 4-poles 750W
13 14
Rectifier
15 Compressor thermo PW -2AL
4-Way Valve coil
16
JXO-6B 30A, 600VAC
For protection of switching power source
For protection of inverter input overcurrent
(Inverter attached) 10k(25°C)
(Inverter attached) 10k(25°C)
3.15A, AC250V 25A, AC250V
D25XB60-4001 20A, 600V
OFF : 125±4°C, on : 90±5°C
VHV-01AJ503C1
AC220-240V~
– 27 –
FILE NO. SVM-06032
5-5. Outdoor Unit (RAS-16GAV-E2, RAS-16NAV-A2)
No. Parts name Model name Rating
1 SC coil L01 ADR2516-0R6TB 15A, 0.6m H
(Noise filter) L03 ADR2520-R15TB 20A, 0.15mH
2 DC-DC transformer SWT-72
3 Reactor CH-57-Z-T L=10mH, 16A x 2 4 Outside fan motor ICF-140-43-4R DC140 V, 43 W
5 Suction temp. sensor
(TS sensor) Discharge temp. sensor
6
(TD sensor) Outside air temp. sensor
7
(TO sensor) Heat exchanger temp.
8
sensor (TE sensor)
9 Terminal block (6P)
10 Fuse
For protection of switching power source 3.15A, AC 250 V
For protection of inverter input overcurrent 25A, AC 250 V
(Inverter attached) 10 k (25°C)
(Inverter attached) 62 k (20°C)
(Inverter attached) 10 k (25°C)
(Inverter attached) 10 k (25°C)
JXO-6B
Primary side DC280V, Secondary side 7.0 V x 1, 12 V x 1, 17V x 2
30A, 600 VAC
11 Electrolytic capacitor LLQ2G761KHUBTF 760µF, DC 400 V x 3 pieces 12 IGBT GT20J321 20A, 600V
13 Compressor DA130A1F-24F 3-phases 4-poles 1100 14 Rectifier D25XB60-4001 20A, 600V
15 Compressor thermo PW-2AL OFF : 125±4 °C, ON : 90±5°C 16 4-Way valve coil VHV-01AJ503C1 AC 220 240V
W
28

6. REFRIGERANT CYCLE DIAGRAM

6-1. Refrigerant Cycle Diagram
RAS-10GKV-E2 / RAS-10GAV-E2 RAS-10NKV-A2 / RAS-10NAV-A2 RAS-10NKVX-T / RAS-10NAVX-T
P
Pressure measurement Gauge attaching port Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 9.52mm Thickness : 0.80mm
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm Thickness : 0.80mm
Sectional shape of heat insulator
T1
Temp. measurement
FILE NO. SVM-06032
Max. :10m
Allowable height
difference : 8m
Allowable pipe length
4-way valve
Muffler
TD
Compressor
DA89X1F-23FZ
TS
Outdoor heat
exchanger
TO
Split capillary
1.0x600
Temp. measurement
T2
Propeller fan
OUTDOOR UNIT
1.0x600
TE
Refrigerant amount : 0.64kg
NOTE: Gas leak check position
Refrigerant flow (Cooling) Refrigerant flow (Heating)
Note :
The maximum length of the pipe for this air conditioner is 10 m. The additional charging of refrigerant is unnecessary because this air conditioner is designed with charge-less specification.
29
Loading...
+ 85 hidden pages