11. HOW TO DIAGNOSE THE TROUBLE...................................................... 69
12. HOW TO REPLACE THE MAIN PARTS................................................... 94
13. EXPLODED VIEWS AND PARTS LIST ................................................. 111
– 1 –
FILE NO. SVM-13001
1. SAFETY PRECAUTIONS
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
Be sure to read this installation manual carefully before installing.
Recommend to the owner to perform maintenance periodically when using over long periods of time.
Be sure to follow the precautions provided here to avoid safety risks. The symbols and their meanings are shown below.
DANGER : It indicates that incorrect use of this unit can result in a high possibility of severe injury (*1) or death.
WARNING : It indicates that incorrect use of this unit may cause severe injury of death.
CAUTION : It indicates that incorrect use of this unit may cause personal injury (*2) or property damage (*3).
*1 : A severe injury refers to blindness, injury, burns (hot or cold), electrical shock, bone fracture, or
poisoning that leaves aftereffects and requires hospitalization or extended out-patient treatment.
*2 : Personal injury means a slight accident, burn, or electrical shock which does not require admission
or repeated hospital treatment.
*3 : Preperty damage means greater damage which affects assets or resources.
For general public use
Power supply cord of parts of appliance for outdoor use shall be at least polychloroprene sheathed flexible cord
(design H07RN-F) or cord designation 60245 IEC66 (1.5 mm2 or more). (Shall be installed in accordance with national
wiring regulations.)
CAUTION
New refrigerant air conditioner installation
•THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A), WHICH DOES NOT DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membranes, and oils because the
pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. As well as the adoption of this new refrigerant,
refrigerating machine oil has also been changed. Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerating machine oil does not enter the refrigeration cycle of a new-refrigerant air
conditioner. To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting port
connecting sections on the main unit are different from those for the conventional refrigerant, and different size tools
are also required. For connecting pipes, use new and clean piping materials with highpressure withstand
capabilities, designed for R410A only, and ensure that water or dust does not enter. Moreover, do not use any
existing piping as its pressure withstand may be insufficient and may contain impurities.
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• MEANS FOR DISCONNECTION FROM THE SUPPLY HAVING A CONTACT SEPERATION OF AT LEAST 3 mm
IN ALL POLES MUST BE INCORPORATED IN THE FIXED WIRING.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK, MAKE SURE ALL POWER
SWITCHES ARE OFF FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY,
ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL
AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATERS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO
THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS
PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES
BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK,
IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR
SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
• WHEN INSTALLING OR RE-INSTALLING THE AIR CONDITIONER, DO NOT INJECT AIR OR OTHER SUBSTANCES
BESIDES THE DESIGNATED REFRIGERANT "R410A" INTO THE REFRIGERATION CYCLE. IF AIR OR OTHER
SUBSTANCES ARE MIXED, AN ABNORMAL PRESSURE CAN OCCUR IN THE REFRIGERATING CYCLEL, AND
THIS CAN CAUSE AN INJURY DUE TO A PIPE RUPTURE.
–
– 2 –
FILE NO. SVM-13001
WARNING
• Installation work must be requested from the supplying retail dealership or professional vendors. Self-installation may
cause water leakage, electrical shock, or fire as a result of improper installation.
• Specified tools and pipe parts for model R410A are required, and installation work must be done in accordance with
the manual. HFC type refrigerant R410A has 1.6 times more pressure than that of conventional refrigerant (R22).
Use the specified pipe parts, and ensure correct installation, otherwise damage and/or injury may be caused. At the
same time, water leakage, electrical shock, and fire may occur.
• Be sure to install the unit in a place which can sufficiently bear its weight. If the load bearing of the unit is not enough,
or installation of the unit is improper, the unit may fall and result in injury.
• Electrical work must be performed by a qualified elecrical engineer in accordance with the code governing such
installation work, inernal wiring regulations, and the manual. A dedicated circuit and the rated voltage must be used.
Insufficient power supply or improper installation may cause electrical shock or fire.
• Use a cabtyre cable to connect wires in the indoor/outdoor units. Midway connection, stranded wire, and single-wire
connections are not allowed. Improper connection or fixing may cause a fire.
• Wiring between the indoor unit and outdoor units must be well shaped so that the cover can be firmly placed.
Improper cover installation may cause increased heat, fire, or electrical shock at the terminal area.
• Be sure to use only approved accessories or the specified parts. Failure to do so may cause the unit to fall, water
leakage, fire or electrical shock.
• After the installation work, ensure that there is no leakage of refrigerant gas. If the refrigerant gas leaks out of the
pipe into the room and is heated by fire or something else from a fan heater, stove or gas range, it causes generation
of poisonous gas.
• Make sure the equipment is properly earthed. Do not connect the earth wire to a gas pipe, water pipe, lightning
conductor, or telephone earth wire. Improper earth work may be the cause of electrical shock.
• Do not install the unit where flammable gas may leak. It there is any gas leakage or accumulation around the unit,
it can cause a fire.
• Do not select a location for installation where there may be excessive water or humidity, such as a bathroom.
Deterioration of insulation may cause elestrical shock or fire.
• Installation work must be performed following the instructions in this installation manual. Improper installation may
cause water leakage, electrical shock or fire. Check the following items before operating the unit.
- Be sure that the pipe connection is well placed and there are no leaks.
- Check that the service valve is open. If the service valve is closed, it may cause overpressure and result in
compressor damage. At the same time, if there is a leak in the connection part, it may cause air suction and
overpressure, resulting burst or injury.
• In pump down operations, ensure to perform the following procedures.
- Do not inject air into the refrigeration cycle.
- Be sure to close both service valves and stop the compressor before removing the refrigerant pipe. It removing
the refrigerant pipe while the compressor is operating with the service valves opened, it may cause to air absorbed
and abnormal high pressure inside the refrigeration cycle and resulting burst or injury.
• Do not modify the power cable, connect the cable midway, or use a multiple outlet extension cable. Doing so may
cause contact failure, insulation failure, or excess current, resulting in fire or electrical shock.
• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally
high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product
or an injury to your body.
• Be sure to comply with local regulations/codes when running the wire from the outdoor unit to the indoor unit,
(Size of wire and wiring method etc.).
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of
the air conditioner, it may spontaneously combust and start a fire.
• If you detect any damage, do not install the unit. Contact your supplying dealer immediately.
• Never modify this unit by removing any of the safety guards.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if
the unit falls.
– 3 –
FILE NO. SVM-13001
CAUTION
• Please read this installation manual carefbefore installing the unit. It contains further important instructions for proper
installation.
• Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet
basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise
level of the unit or where noise and discharged air might disturb neighbors.
• This appliance must be connected to the main power supply by means of a circuit breaker depending on the place
where the unit is installed. Failure to do so may cause electrical shock.
• Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit.
Ensure that drained water is discharged. Improper drainage can result in water leakage, causing water damage
to furniture.
• Tighten the flare nut with a torque wrench using the prescribed method. Do not apply excess torque. Otherwise, the
nut may crack after a long period of usage and it may cause the leakage of refrigerant.
• Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so may cause personal injury
when handling parts with sharp edges.
• Do not touch the air intake section or the aluminum fins of the outdoor unit. It may cause injury.
• Do not install the outdoor unit in a place which can be a nest for small animals. Small animals could enter and contact
internal electrical parts, causing a failure or fire.
• Request the user to keep the place around the unit tidy and clean.
• Make sure to conduct a trial operation after the installation work, and explain how to use and maintain the unit to the
customer in accordance with the manual. Ask the customer to keep the operation manual along with the
installation manual.
– 4 –
/
/
FILE NO. SVM-13001
2. SPECIFICATIONS
Specification
Unit model Indoor RAS-10N3AV2-A
Cooling capacity (kW) 2.5
Cooling capacity range (kW) 1.1-3.1
Heating capacity (kW) 3.2
Heating capacity range (kW) 0.9-4.8
Power supply
Electric Indoor Operation mode Cooling Heating
characteristic Running current (A) 0.21-0.19 0.24-0.22
COP (Cooling / Heating)
Operating Indoor High (Cooling / Heating) (dB-A) 39/39
noise Medium (Cooling / Heating) (dB-A) 33/34
Indoor unit Unit model RAS-10N3KV2-A
Outdoor unit Unit model RAS-10N3AV2-A
Piping Type Flare connection
connection Indoor unit Liquid side (mm)
Refrigerant Name of refrigerant R410A
WiringPower supply
connectionInterconnection
Usable temperature range Indoor (Cooling / Heating)
Accessory Indoor unit Installation plate 1
* The specification may be subject to change without not i ce f or pur pose of i m pr ovement.
Outdoor RAS-10N3AV2-A
1Ph/50Hz/220-240V
Power consumption (W) 35 40
Outdoor Operation mode CoolingHeating
Outdoor (Cooling / Heating) (dB-A)
Dimension Height (mm) 275
Net weight (kg) 10
Fan motor output (W) 20
Air flow rate (Cooling / Heating)
Dimension Height (mm) 550
Net weicht (kg) 33
Compressor Motor output (W) 750
Fan motor output(W)
Air flow rate (Cooling / Heating)
Outdoor unit Liquid side (mm)
Maximum length (m) 20
Maximum charge-less length (m) 15
Maximum height difference (m) 10
Weight (kg) 0.80
Outdoor unit Drain nipple 1
Power factor (%) 76 76
Running current (A) 2.81-2.58 3.43-3.14
Power consumption (W) 563 710
Power factor (%) 91 94
Starting current (A) 3.67
Low (Cooling / Heating) (dB-A) 26/28
Width (mm) 790
Depth (mm) 225
3
min)
(m
Width (mm) 780
Depth (mm) 290
Type Single rotary type with DC-inverter variable speed conrol
Model DA89X1C-23FZ2
Indoor unit Unit model RAS-13N3KV2-A RAS-16N3KV2-A
DimentionHeight(mm)275275
Width(mm)790790
Depth (mm) 225 225
Net weight (kg) 10 10
Fan motor output(W)2030
Air flow rate (Cooling / Heating)
Outdoor unit Unit model RAS-13N3AV2-A RAS-16N3AV2-A
DimentionHeight(mm)550550
Width(mm)780780
Depth(mm)290290
Net weight (kg) 37 38
CompressorMotor output(W)7501100
Type
Model DA108X1C-23FZ DA131S1B-31FZ
Fan motor output(W)4343
Air flow rate (Cooling / Heating)
PipingTypeFlare conne ction
connection Indoor unit Liquid side (mm) ∅6.35∅6.35
Gas side (mm) ∅9.52∅12.7
Outdoor unit Liquid side (mm) ∅6.35∅6.35
Gas side (mm) ∅9.52∅12.7
Maximum length(m)2020
Maximun charge-less length(m)1515
Maximum height difference(m)1010
RefrigerantName of refrigerantR410AR410A
Weight(kg)1.051.10
WiringPower supply3 Wires: Includes earth (Outdoor)3 Wires: Includes earth (Outdoor)
connectionInterconnection4 Wires: Includes earth4 Wires: Includes earth
Usable temperature rangeIndoor(Cooling / Heating)
Outdoor(Cooling / Heating)
AccessoryIndoor unitInstallation plate11
Wireless remote controller11
batteries22
Remote controller holder11
TOSHIBA IAQ Filter (long type) 1 1
Mounting screw
Pan head wood screw
3
(m
/ min)
Single rotary type with DC-inverter
3
(m
/ min)
o
(
C)
o
(
C)
6 (∅ 4 x 25L)
2 (∅ 3.1 x 16L)
Plasma air purifier Installation manual 1
Owner's manual 1
Outdoor unitDrain nipple 1
Water proof rubber cap 2
3.4
2.0-4.1 0.8-5.0
4.2 5.3
1.8-5.6
96989798
5.24 7.02
10.4/10.4 11.4/12.3
Twin rotary type with DC-inverter
variable speed control
37.5/37.5 34.0/34.0
21-32/0-2821-32/0-28
-10-46/-15-24-10-46/-15-24
1
1
1
2
* The specification may be subject to change without not i ce f or pur pose of i m pr ovement.
4.4
0.9-6.3
variable speed control
6 (∅ 4 x 25L)
2 (∅ 3.1 x 16L)
– 6 –
Operation Characteristic Curve (RAS-10N3KV2-A)
<Cooling><Heating>
FILE NO. SVM-13001
10
9
8
7
6
5
4
Current (A)
3
2
1
RAS-10N3KV2-A
Conditions
Indoor : DB 27
Outdoor : DB 35
Air Flow : High
Pip Length : 5m
Voltage : 230V
o
0
01020 30 40 50 60 70 80 90 100 110 120
Compressor Speed (rps)
C/WB 19oC
o
C
9
8
7
RAS-10N3KV2-A
6
5
4
Current (A)
3
2
1
Conditions
Indoor : DB 20
Outdoor : DB 7
Air Flow : High
Pip Length : 5m
Voltage : 230V
o
C
o
C/WB 6oC
0
0 102030405060708090100110120
Compressor Speed (rps)
Capacity Variation Ratio According to Temperature (RAS-10N3KV2-A)
<Cooling>
105
100
95
90
85
80
75
Capacity ratio (%)
70
65
Capacity ratio:100%=
2.5kW(RAS-10N3KV2-A)
60
55
50
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Outdoor temp. (℃)
RAS-10N3KV2-A
Conditions
Indoor:DB27℃/WB19℃
Indoor air flow:High
Pipe length:5m
Voltage : 23
0V
<Heating>
120
100
80
60
40
Heating Capacity ratio (%)
20
0
-15-10-50510
RAS-10N3KV2-A
Condition
Indoor:DB20℃
Indoor air flow:High
Pipe length:5m
Voltage : 230V
Outdoor temp. (℃)
– 7 –
Operation Characteristic Curve (RAS-13,16N3KV2-A)
g
<Cooling> <Heating>
FILE NO. SVM-13001
9
8
7
RAS-16N3KV2-A
6
5
4
Current (A)
3
2
1
0
0 102030405060708090100110120
Compressor Speed (rps)
Conditions
Indoor : DB 27oC/WB 19oC
Outdoor : DB 35
Air Flow : High
Pipe Length : 5m
Voltage : 230V
RAS-13N3KV2-A
o
C
9
8
7
6
5
4
Current (A)
3
2
1
0
0 102030405060708090100110120
RAS-16N3KV2-A
Compressor Speed (rps)
RAS-13N3KV2-A
Conditions
Indoor : DB 20oC
Outdoor : DB 7
Air Flow : High
Pipe Length : 5m
Voltage : 230V
o
C/WB 6oC
Capacity Variation Ratio According to Temperature (RAS-13,16N3KV2-A)
<Cooling><
105
100
RAS-13N3KV2-A
95
90
85
80
75
Capacity ratio (%)
70
65
Capacity ratio :100%
60
3.4kW (RAS-13N3KV2-A)
4.4kW (RAS-16N3KV2-A)
55
50
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Outdoor temp. (oC)
RAS-16N3KV2-A
Conditions
Indoor : DB 27oC/WB 19oC
Outdoor : DB 35
Air Flow : High
Pipe Length : 5m
Voltage : 230V
o
C
Heatin
–7–
>
120
100
RAS-13N3KV2-A
80
60
Capacity ratio (%)
40
Conditions
Indoor : DB 20oC
20
Outdoor : DB 7
Air Flow : High
Pipe Length : 5m
Voltage : 230V
0
-15-10-50510
o
C/WB 6oC
Outdoor temp. (oC)
RAS-16N3KV2-A
Capacity ratio :100%
4.2kW (RAS-13N3KV2-A)
5.3kW (RAS-16N3KV2-A)
– 8 –
3. REFRIGERANT R410A
FILE NO. SVM-13001
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer .
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water , dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
1. Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure
in the refrigeration cycle becomes abnormally
high, and it may cause personal injury, etc. by a
rupture.
2. Confirm the used refrigerant name, and use tools
and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
3. If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
4. When installing or removing an air conditioner, do
not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so
that a rupture or personal injury may be caused.
5. After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentration
does not exceed the marginal le vel.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal le vel, an
oxygen starvation accident may result.
7. Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage , electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair’s may result in water leakage,
electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant m ust be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants .
1. Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored
portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary
to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 3-2-1. Never use copper
pipes thinner than 0.8 mm even when it is
available on the market.
– 9 –
Table 3-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
FILE NO. SVM-13001
Nominal diameter
1/4
3/8
1/2
5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410AR22
0.800.80
0.800.80
0.800.80
1.001.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds
20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below .
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose
diameter is larger than 20 mm.
Thicknesses of sock et joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not
enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used,
and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils
whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any
other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage ma y occur.
Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
– 10 –
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perform the flare
processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Flare processing dimensions differ according
to the type of flare tool. When using a conventional flare tool, be sure to secure “dimen-
sion A” by using a gauge for size adjustment.
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Fig. 3-2-1 Flare pr ocessing dimensions
Flare tool for R410A
clutch type
FILE NO. SVM-13001
ØD
A
A (mm)
Conventional flare tool
Clutch type Wing nut type
1/4
3/8
1/2
5/8
Nominal
diameter
1/4
3/8
1/2
5/8
6.35
9.52
12.70
15.88
Table 3-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
0.8
0.8
0.8
1.0
Thickness
(mm)
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Flare tool for R22
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
1.0 to 1.51.5 to 2.0
1.0 to 1.51.5 to 2.0
1.0 to 1.52.0 to 2.5
1.0 to 1.52.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.01.0 to 1.5
0.5 to 1.01.0 to 1.5
0.5 to 1.01.5 to 2.0
0.5 to 1.01.5 to 2.0
Nominal
diameter
1/4
3/8
1/2
5/8
Table 3-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.19.26.513
13.213.59.720
16.616.012.923
19.719.016.025
– 11 –
Flare nut width
(mm)
17
22
26
29
Table 3-2-6 Flare and flare nut dimensions for R22
FILE NO. SVM-13001
Nominal
diameter
1/4
3/8
1/2
5/8
3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
45˚ to 46˚
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
BA
Dimension (mm)
ABCD
9.09.26.513
13.013.59.720
16.216.012.920
19.719.016.023
23.324.019.234
D
C
43˚ to 45˚
Flare nut width
(mm)
17
22
24
27
36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis.
c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten-
ing torque, comply with values designated by man ufacturers. Table 3-2-7 shows reference v alues.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer.
If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer diameter
(mm)
Tightening torque
N•m (kgf•cm)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/4
3/8
1/2
5/8
6.35
9.52
12.70
15.88
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
– 12 –
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
FILE NO. SVM-13001
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is
changed to prev ent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing
dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are
lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge ,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
air-water heat pump installation
No.
1
2
3
4
5
6
7
8
9
10
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
(Note 2) Charging cylinder for R410A is being currently developed.
Whether new equipment
can be used with
conventional refrigerant
¡
*(Note 1)
×
×
¡
¡
×
¡
×
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary
as the general tools.
1. Vacuum pump
Use vacuum pump by attaching
vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Le vel vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. He xagon wrench
(Opposite side 4mm)
11 . Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
– 13 –
FILE NO. SVM-13001
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps .
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
Connect the charge hose to the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
(For refrigerant charging, see the figure below.)
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
(Indoor unit)
Opened
(Outdoor unit)
Refrigerant cylinder
(with siphon)
Check valve
Opened
Open/close
valve for charging
Electronic balance for refrigerant charging
Fig. 3-4-1 Configuration of refrigerant charging
Opened
Closed
Service port
– 14 –
FILE NO. SVM-13001
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ][ Cylinder without siphon ]
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the
characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper. It is used to join iron, copper
or copper alloy, and is relatively e xpensive though
it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
Electronic
balance
Siphon
Fig. 3-4-2
1. Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas
leakage. Therefore, use any other type of
brazing filler at a hot spring resort, etc., and
coat the surface with a paint.
2. When performing brazing again at time of
servicing, use the same type of brazing filler.
3-5-2. Flux
3. Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
1. Reason why flux is necessary
• By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler .
• In the brazing process, it prevents the metal
surface from being oxidized.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 15 –
2. Characteristics required for flux
• Activated temperature of flux coincides with the
brazing temperature.
• Due to a wide effective temperature range, flux
is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric
acid.
It is effective in case where the brazing temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing
are this type.
It features an increased o xide film removing
capability due to the addition of compounds
such as potassium fluoride, potassium chloride
and sodium fluoride to the borax-boric acid
compound.
4. Piping materials for brazing and used
brazing filler/flux
FILE NO. SVM-13001
3-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prev ent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to
keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it
is lower than 0.05 m3/Hr or 0.02 MPa
(0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, k eep the
Nitrogen gas flowing until the pipe cools down
to a certain extent (temperature at which
pipes are touchable with hands).
7) Remove the flux completely after brazing.
Piping material
Copper - Copper
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver
Silver
Used flux
Do not use
Paste flux
Vapor flux
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain
chlorine.
3. When adding water to the flux, use water
which does not contain chlorine (e.g. distilled
water or ion-exchange water).
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
NOTE :
• The maximum pipe length of this air conditioner is 15 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
– 24 –
7-2. Operation Data
<Cooling>
FILE NO. SVM-13001
TempeatureHeat exchanger
condition(°C)
IndoorOutdoorP (MPa)T1 (°C)T2 (°C)(rps)
27/19 35/-
Model nameStandardIndoorOutdoorCompressor
RAS-pressurefan modefan moderevolution
10N3KV2-A
13N3KV2-A
16N3KV2-A
0.9 to 1.1 12 to 14 37 to 39 High High 49
0.8 to 1.0 11 to 13 46 to 48 High High 59
0.8 to 1.0 11 to 13 40 to 42 High High 67
pipe temp.
<Heating>
TempeatureHeat exchanger
condition(°C)
IndoorOutdoorP (MPa)T1 (°C)T2 (°C)(rps)
20/-7/610N3KV2-A2.5 to 2.739 to 410 to 3HighHigh60
Model nameStandardIndoorOutdoorCompressor
RAS-pressurefan modefan moderevolution
13N3KV2-A 2.6 to 2.8 41 to 43 0 to 2 High High 66
16N3KV2-A 2.7 to 2.9 43 to 45 0 to 2 High High 67
pipe temp.
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
– 25 –
8-1. Indoor Unit
FILE NO. SVM-13001
8. CONTROL BLOCK DIAGRAM
Heat Exchanger Sensor (Tc)
Room Temperature Sensor (Ta)
Infrared Rays Signal Receiver
and Indication
Initializing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Converter
(D.C circuit)
Noise Filter
M.C.U.
Functions
• Cold draft preventing Function
• 3-minute Delay at Restart for Compressor
• Fan Motor Starting Control
• Processing
(Temperature Processing)
• Timer
• Serial Signal Communication
• Clean Function
Serial Signal Transmitter/Receiver
Indoor Unit Control Unit
Louver
Motor
Louver Motor
Drive Control
Indoor Fan
Motor Control
Indoor
Fan Motor
Power Supply
(From Outdoor Unit)
REMOTE CONTROLLER
Serial Signal Communication
(Operation Command and Information)
Remote Controller
Operation [ ]
Operation Mode Selection
AUTO, COOL, DRY, HEAT
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECO
Hi-POWER
Infrared Rays, 36.7kHz
COMFORT SLEEP
QUIET
– 26–
8-2. Outdoor Unit (Inverter Assembly)
detect
Current
circuit
Gate drive
detect
Current
FILE NO. SVM-13001
Compressor
Outdoor
Fan motor
Inverter
(DC → AC)
P.M.V. : Pulse Motor Valve
M.C.U. : Micro Control Unit
MICRO-COMPUTER BLOCK DIAGRAM
M.C.U
MCC5009 (P.C.B)OUTDOOR UNIT
• PWM synthesis function
• Input current release control
circuit
Indoor unit
send/receive
circuit
Gate drive
• IGBT over-current detect control
• Outdoor fan control
• High power factor correction control
• Inverter output frequency control
• A/D converter function
• P.M.V. control
• Discharge temp. control
• 4-way valve control
• Signal communication to indoor unit
4MHz
Clock
frequency
circuit
High Power
factor Correction
Converter
(AC → DC)
sensor
Input current
Filter
Noise
Inverter
(DC → AC)
Relay
circuit
of P.M.V.
Driver circuit
valve
4-way
P.M.V.
Power Supply
(From Outdoor Unit)
For INDOOR UNIT
Discharge
temp. sensor
Outdoor air
temp. sensor
Suction temp.
– 27–
sensor
Heat exchanger
temp.sensor
9. OPERATION DESCRIPTION
FILE NO. SVM-13001
9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air
conditioner, which uses AC or DC motor for the indoor
for motor and the outdoor fan motor. And the capacityproportional control compressor which can change the
motor speed in the range from 11 to 96 rps is
mounted. The DC motor drive circuit is mounted to the
indoor unit. The compressor and the inverter to control
fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the
indoor unit controller.
The indoor unit controller drives the indoor fan motor
based upon command sent from the remote controller,
and transfers the operation command to the outdoor
unit controller.
The outdoor unit controller receives operation command from the indoor unit side, and controls the
outdoor fan and the pulse Modulating valve. (P.M.V)
Besides, detecting revolution position of the compressor motor, the outdoor unit controller controls speed of
the compressor motor by controlling output voltage of
the inverter and switching timing of the supply power
(current transfer timing) so that motors drive according
to the operation command.
And then, the outdoor unit controller transfers reversely
the operating status information of the outdoor unit to
control the indoor unit controller.
As the compressor adopts four-pole brushless
DC motor, the frequency of the supply power
from inverter to compressor is two-times cycles
of the actual number of revolution.
1. Role of indoor unit controller
The indoor unit controller judges the operation
commands from the remote controller and assumes
the following functions.
• Judgment of suction air temperature of the indoor
heat exchanger by using the indoor temp. sensor.
(TA sensor)
• Judgment of the indoor heat exchanger temperature by using heat exchanger sensor (TC sensor)
(Prevent-freezing control, etc.)
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal (Serial
signal) to the outdoor unit
• Reception of information of operation status
(Serial signal including outside temp. data) to the
outdoor unit and judgment/display of error
• Air purifier operation control
2. Role of outdoor unit controller
Receiving the operation command signal (Serial
signal) from the indoor unit controller, the outdoor
unit performs its role.
• Compressor operation control
• Operation control of outdoor fan motor
• P.M.V. control
• 4-way valve control
Operations follow ed to judgment
of serial signal from indoor side.
• Detection of inverter input current and current
release operation
• Over-current detection and prevention operation
to IGBT module (Compressor stop function)
• Compressor and outdoor fan stop function when
serial signal is off (when the serial signal does not
reach the board assembly of outdoor control by
trouble of the signal system)
• Transferring of operation information (Serial
signal) from outdoor unit controller to indoor unit
controller
• Detection of outdoor temperature and operation
revolution control
• Defrost control in heating operation (Temp.
measurement by outdoor heat exchanger and
control for 4-way valve and outdoor fan)
3. Contents of operation command signal
(Serial signal) from indoor unit controller to
outdoor unit controller
The following three types of signals are sent from
the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined
by indoor temperature and set temperature
(Correction along with variation of room temperature and correction of indoor heat exchanger
temperature are added.)
• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger temperature), the outdoor unit controller monitors the
input current to the inverter, and performs the
followed operation within the range that current
does not exceed the allowable value.
4. Contents of operation command signal
(Serial signal) from outdoor unit controller
to indoor unit controller
The following signals are sent from the outdoor unit
controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transferring of these signals, the indoor unit
controller monitors the contents of signals, and
judges existence of trouble occurrence.
Contents of judgment are described below.
• Whether distinction of the current operation
status meets to the operation command signal
• Whether protective circuit operates
When no signal is received from the outdoor