Toshiba MMY-MAP1004FT8Z-E, MMY-MAP1204FT8Z-E, MMY-MAP0804FT8-E, MMY-MAP1004FT8ZG-E, MMY-MAP1204FT8ZG-E User Manual

...
AIR CONDITIONER (MULTI TYPE)
Installation Manual
Outdoor Unit
Model name:
MMY-MAP0804FT8-E MMY-MAP1004FT8-E MMY-MAP1204FT8-E MMY-MAP1404FT8-E
MMY-MAP0804FT8Z-E MMY-MAP1004FT8Z-E MMY-MAP1204FT8Z-E MMY-MAP1404FT8Z-E
MMY-MAP0804FT8ZG-E MMY-MAP1004FT8ZG-E MMY-MAP1204FT8ZG-E
MMY-MAP1404FT8ZG-E
English
Original instruction
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 Precautions for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Accessory parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Installation of new refrigerant air conditioner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Selection of installation place. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Carrying in the outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Installation of the outdoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7 Refrigerant piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
8 Electric wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
9 Address setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
10 How to set up the cooling only indoor unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
–1–
11 Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
13 Machine card and logbook . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1-EN 2-EN
Thank you for purchasing this Toshiba air conditioner.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the Installation Manual supplied with the indoor unit. Moreover, as this installation manual includes the important articles concerning the “Machinery” Directive (Directive 2006/42/ EC), please read through the manual and make sure you understand it. After installation, give this Installation Manual, the Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them safe.
Prepare an exclusive power source for indoor units, independent to that for outdoor units. Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between indoor and outdoor units. Choose either of them considering the system capacity concerning piping. For installing branching pipes, refer to the installation manual of the Y-shaped branching unit or branching header (separately purchased). Outdoor connecting branching joints are required for connecting between outdoor units.
Generic Denomination: Air Conditioner
Work undertaken Protective gear worn
All types of work
Electrical-related work
Work done at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit Gloves to provide protectio n for electricians and from heat
Protective gloves ‘Safety’ working clothing
Gloves to provide protec tion for electricians and from h eat Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Warning indications on the air conditioner unit
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent Qualifications and knowledge which the agent must have
• The qualified installer is a pers on who installs, maintains, relocate s and removes the air conditione rs made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Car rier Corporation or, alternatively , he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowe d to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have
Qualified installer
Qualified service person
been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowe d to do the refrigerant hand ling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge re lated to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person is a person wh o installs, repairs, maintains, relocates and removes the air condition ers made by Toshiba Carrier Corporation . He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allo wed to do the electrical work involve d in installation, repair, relocation an d removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and pipi ng work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work de tailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
3-EN 4-EN
–2–
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
–3–
WARNING
1 Precautions for safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to do installationwork. If installation is carried out by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• If using separately sold products, make sure to use Toshiba specified products only. Using unspecified products may cause fire, electric shock, water leak or other failure.
• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
• Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
• When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work. Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
• When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
• When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work. Parts and other objects may fall from above, possibly injuring a person below.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable condition. If you find any part of the product broken, contact your dealer.
• Do not disassemble, modify, repair or move the product yourself. Doing so may cause fire, electric shock, injury or water leaks. Ask a qualified installer or qualified service person to do any repairs or to move the product.
Selection of installation location
• If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
• Do not install in a location where flammable gas may leaks are possible. If the gas should leak and accumulate around the unit, it may ignite and cause a fire.
• When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
• When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
• Places where the operation sound of the outdoor unit may cause a disturbance. (Especially at the boundary line with a neighbour, install the air conditioner while considering the noise.)
Installation
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
• The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury.
• Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result in the unit falling down, or other accidents.
• Be sure to fix the screws back which have been removed for installation or other purposes.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
• Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with fire, toxic gas may be produced.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
• When executing address setting, test run, or troubleshooting through the checking window on the electrical control box, put on insulated heat-proof gloves, insulated shoes and other clothing to provide protection from electric shock. Otherwise you may receive an electric shock.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
• Check that the product is properly earthed. (grounding work) Incomplete earthing may cause electric shock.
• Do not connect the earth wire to a gas pipe, water pipe, lightning conductor, or a telephone earth wire.
• After completing the repair or relocation work, check that the ground wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended may give rise to smoking and/or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
• Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow may occur on the terminal block and may result in fire.
• When carrying out electric connection, use the wire specified in the Installation Manual and connect and fix the wires securely to prevent them applying external force to the terminals. Improper connection or fixing may result in fire.
Test run
• Before operating the air conditioner after having completed the work, check that the electrical control box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
• When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
• After the work has finished, be sure to use an insulation tester set (500 V Megger) to check the resistance is 2 MΩ or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage. Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
5-EN 6-EN
Relocation
CAUTION
• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• When carrying out the pump-down work shut down the compr essor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.
• Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
New refrigerant air conditioner installation
This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
To disconnect the appliance from main power supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
7-EN 8-EN
–4–
–5–
2 Accessory parts
Part name
Owner’s Manual 1 1 1 1 (Be sure to hand it to the customers.)
Installation Manual 1 1 1 1 (Be sure to hand it to the customers.)
CD-ROM (Owner’s manual,
Installation manual)
F-GAS label 1 1 1 1
Attached pipe (Ø22.2 both forward and downward)
Attached pipe (Ø15.9 both forward and downward)
Attached pipe (Ø12.7 for draw-out forward)
Attached pipe (Ø12.7 for draw-out downward)
Attached pipe (Ø28.6 both forward and downward)
Attached pipe (Ø19.1 both forward and downward)
Attached pipe (Ø15.9 for draw-out forward)
Attached pipe (Ø15.9 for draw-out downward)
Attached pipe (Ø19.1 both forward and downward)
Attached pipe (Ø15.9 for draw-out forward)
Attached pipe (Ø15.9 for draw-out downward)
MAP080 MAP100 MAP120 MAP140
1111 –
11––
11––
11––
11––
––11
––1–
––1–
––1–
–––1
–––1
–––1
Q’ty
Shape Usage
For other languages that do not appear in this Installation Manual, Please refer to the enclosed CD-ROM.
Fill the items on the label after adding refrigerant.
Suction-side gas pipe Ø25.4 Ø22.2 pipe fitting
Discharge-side gas pipe Ø15.9 Ø19.1 pipe fitting
* Flare the connector on the outdoor unit for
installation
Liquid-side connection pipe * Flare the connector on the outdoor unit for
installation
Suction-side gas pipe Ø25.4 Ø28.6 pipe fitting
Discharge-side connection pipe * Flare the connector on the outdoor unit for
installation
Liquid-side gas pipe Ø15.9 Ø12.7 pipe fitting
* Flare the connector on the outdoor unit for
installation
Discharge-side gas pipe Ø19.1 Ø22.2 pipe fitting
* Flare the connector on the outdoor unit for
installation
Liquid-side connection pipe
* Flare the connector on the outdoor unit for
installation
3 Installation of new refrigerant air
conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times. As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting section of the installation tool differs to that of an air conditioner for the former refrigerant. Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.) : Former tool is available.
Gauge manifold
Charging hose Exclusive to R410A
Charging cylinder Charging refrigerant Unusable (Use the Refrigerant charging balance.)
Gas leak detector Checking gas leak Exclusive to R410A
Vacuum pump Vacuum drying
Vacuum pump with counterflow Vacuum drying R22 (Existing article)
Flare tool Flare processing of pipes Usable by adjusting size
Bender Bending processing of pipes R22 (Existing article)
Refrigerant recovery device Recovering refrigerant Exclusive to R410A
Torque wrench Tightening flare nut Exclusive to Ø12.7 mm and Ø15.9 mm
Pipe cutter Cutting pipes R22 (Existing article)
Refrigerant canister Charging refrigerant
Welding machine / Nitrogen gas cylinder
Refrigerant charging balance Charging refrigerant R22 (Existing article)
Used tools Usage Proper use of tools / parts
Vacuuming, charging refrigerant and operation check
Welding of pipes R22 (Existing article)
Exclusive to R410A
Usable if a counter-flow preventive adapter is attached
Exclusive to R410A Enter the refrigerate name for identification
9-EN 10-EN
4 Selection of installation place
NOTE
Air discharge
Air intake
Air intake
Air
intake
Air intake
Installation /
servicing
surface
Square hole for handling
Outdoor unit top view
10 mm or more
500 mm or
more
(Rear side)
10 mm or
more
500 mm or
more
(Front side)
20 mm or more
20 mm or more
Upon customer’s approval, install the air conditioner in a place which satisfies the following conditions:
• Place where it can be installed horizontally.
• Place which can reserve a sufficient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overflows.
Avoid the following places:
• Salty places (seaside area) or places with much gas sulfide (hot spring area) (If selecting such a place, special maintenance is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of the air conditioner, it may spontaneously combust and start a fire.
• Places where an organic solvent is used.
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to devices listed above may occur.)
• Places where discharged air from the outdoor unit blows against the windows of a neighbour's house.
• Places unable to bear the weight of the unit.
• Places with poor ventilation.
• Places where ambient temperature falls below -15°C for more than 72 hours running. The outdoor heat exchanger may be damaged by the frost.
The cooling performance may decline considerably when total operating capacity of cooling indoor units is less than 4HP while ambient temperature is below 0°C.
Installation space
Leave space necessary for running, installation and servicing.
Combination of outdoor units
Equivalent HP
8 HP MAP0804 MAP0804✽ ––
10 HP MAP1004 MAP1004✽ ––
12 HP MAP1204 MAP1204✽ ––
14 HP MAP1404 MAP1404✽ ––
16 HP AP1614 MAP0804✽ MAP0804✽
18 HP AP1814 MAP1004✽ MAP0804✽
20 HP AP2014 MAP1004✽ MAP1004✽
22 HP AP2214 MAP1204✽ MAP1004✽
24 HP AP2414 MAP1404✽ MAP1004✽
26 HP AP2614 MAP1404✽ MAP1204✽
28 HP AP2814 MAP1404✽ MAP1404✽
30 HP AP3014 MAP1004✽ MAP1004✽ MAP1004✽
32 HP AP3214 MAP1204✽ MAP1004✽ MAP1004✽
34 HP AP3414 MAP1404✽ MAP1004✽ MAP1004✽
36 HP AP3614 MAP1204✽ MAP1204✽ MAP1204✽
38 HP AP3814 MAP1404✽ MAP1204✽ MAP1204✽
40 HP AP4014 MAP1404✽ MAP1404✽ MAP1204✽
42 HP AP4214 MAP1404✽ MAP1404✽ MAP1404✽
Model name of
outdoor unit
MMY-
Unit 1Unit 2Unit 3
Combination of outdoor unit MMY-
• If there is an obstacle above the outdoor unit, leave a space of 2000 mm or more to the top end of the outdoor unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800 mm.
11-EN 12-EN
–6–
–7–
CAUTION
Front / Back
GOOD NO GOOD NO GOOD
Plaster
Rope
Plaster
Rectangular holes for lifting
Reinforcing plate
Prongs of the forklift
Rectangular
holes for handling
GOOD
NO GOOD
Side
Z
X
Z
X
Y
Y
(A)
(B)
Anchor bolt position
700
Anchor bolt position
920
Anchor bolt position
755
Anchor bolt position
755
5 Carrying in the outdoor unit
Handle the outdoor unit carefully, observing the following items.
• When using a forklift or other machinery for loading / unloading in transportation, insert the prongs of the forklift into the rectangular holes for handling as shown below.
• When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and tie the unit from 4 sides. (Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused to the outer surface of the outdoor unit.) (There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
Weight centre and weight
Weight centre of an outdoor unit
13-EN 14-EN
No. Model type X (mm) Y (mm) Z (mm) Weight (kg)
(A)
(B)
MAP080
MAP100
MAP120
MAP140
490 370 680 259
590 350 700 334
6 Installation of the outdoor unit
WARNING
CAUTION
REQUIREMENT
Snowfall-hood for air discharge (locally procured)
Snowfall-hood for air discharge (4 faces) (locally procured)
Stand (locally procured)
20
20 mm or more
20 mm or more
M12 anchor bolt 4 positions / unit
A A A
B
755
790
Continuous hole (15 x 20 long hole)
310 or more
310 or more
500 mm or more
NO GOOD GOOD
GOOD GOOD
NO GOOD NO GOODNO GOOD
Anchor bolt
Vibration-proof rubber
Install the vibration-proof rubber so that the bent part of the fixing leg is grounded.
The bent part of the fixing leg is not grounded.
Be sure to install the outdoor unit in a place able to bear its weight.
If strength is insufficient, the unit may fall down resulting in human injury.
Perform specified installation work to protect against strong wind and earthquakes.
If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
• Anchor bolt positions are as shown below:
• Drain water is discharged from the outdoor unit. (Especially while heating) Install the outdoor unit in a place with good drainage.
• For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or noise) are not generated.
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that snowfall
will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a flat
2. Mount a snowfall-hood onto the air intake and the air discharge.
• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air intake and the air
1. To install multiple outdoor units, arrange them with 20 mm or more spaces in between.
Fix each outdoor unit with M12 anchor bolts at 4 positions. 20 mm projection is appropriate for an anchor bolt.
surface.)
discharge.
Model type A B
MAP080, MAP100 700 990
MAP120, MAP140 920 1210
2. When drawing out the refrigerant pipe from the underside, set the height of the stand to 500 mm or
3. Do not use 4 stands on the corner to support the outdoor unit.
(Unit: mm)
more.
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it fits under the whole clamping leg.
15-EN 16-EN
–8–
–9–
Within ±15 degrees
(Horizontal line)
Within ±15 degrees
(Horizontal line)
(A arrow view)
At a level position
(B arrow view)
Do not connect a branch unit vertically.
Header unit A Follower unit B Follower unit C
Main pipe
To indoor unit
Liquid joint
Discharge gas joint
Good
Header unit A Follower unit B Follower unit C
To indoor unit Main pipe
No
Good
Liquid joint
Discharge gas joint
Header unit A Follower unit B Follower unit C
Main pipe
Suction gas joint
To indoor unit
Good
Header unit A Follower unit B Follower unit C
Main pipe
Suction gas joint
To indoor unit
No
Good
Suction gas joint
Header unit A Follower unit B
Main pipe
Suction gas joint
To indoor unit
A view
Suction gas joint
A
No
Good
Unit
Vertical line
Header unit AFollower unit BFollower unit
C
L-shaped
pipe
To gas-side branch unit
Suction gas joint
Good
Header unit A
Suction gas joint
No
Good
Header unit A
Suction gas joint
No
Good
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of capacity from the one with the largest capacity. (A (Header unit) B C)
1) Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1, 3 and
5)
2) Be sure to use a T-shaped branch joint (RBM-BT14FE / RBM-BT24FE: separately purchased) to connect each outdoor unit.
3) When attaching a Y-shaped branch unit for the outdoor unit connection piping kit, attach it level with the ground (Be sure not to exceed ±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
A
B
4) Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe flows directly into the header unit.)
Discharge gas / Liquid pipes
Figure 1 Figure 2
Suction gas pipes
<Suction gas joint reverse orientation installation>
Figure 3 Figure 4
<Suction gas joint upright orientation installation>
Figure 5
When drawing pipes downward
<Vertical installation> <Vertical installation>
Figure 5 Figure 6 Figure 7
17-EN 18-EN
7 Refrigerant piping
WARNING
Front panel
Piping / wiring panel
(Rear piping)
Drawing out downward
(Left piping)
(Right piping)
D
r
a
w
i
n
g
o
u
t
f
o
r
w
a
r
d
5
0
0
m
m
o
r
m
o
r
e
Hook
(Left piping)
(Right piping)
Wet cloth
Packed valve of liquid side
Ball valve of suction gas side
Packed valve of balance pipe
Ball valve of discharge gas side
Packed valve of liquid side
Ball valve of suction gas side
Packed valve of balance pipe
Ball valve of discharge gas side
REQUIREMENT
Outer dia. of
copper pipe
Tightening torque (N•m)
9.5 mm 34 to 42
12.7 mm 49 to 61
15.9 mm 63 to 77
19.1 mm 100 to 120
Ball valve of discharge gas side
Do not clamp the service port with a double spanner, doing so may damage the service port.
Do not apply refrigerating oil to the surface of the flare.
Discharge-
side gas pipe
Liquid pipe
L-shaped pipe
Balance pipe
Suction-side
gas pipe
Section
to be
cut
Attachment pipe
Pipe
Socket
PipePipePipe
Attachment
pipe
Attachment
pipe
Socket
Elbow
Suction-side gas pipe
Discharge-
side gas pipe
Liquid pipe
L-shaped pipe
Suction-side gas pipe
Suction-side
gas pipe
Section
to be
cut
Pipe
Socket
Pipe
Pipe
Attachment
pipe
Attachment pipe
Socket
Pipe
Attachment
pipe
Socket
Balance pipe
If the refrigerant gas leaks during installation, ventilate the room.
If the leaked refrigerant gas comes into contact with fire, noxious gas may be generated.
After installation, check that the refrigerant gas does not leak.
If the refrigerant gas leaks into the room and comes into contact with fire such as a fan heater, stove, or kitchen range, noxious gas may be generated.
Connection of refrigerant pipe
1. The refrigerant pipe connecting section is set in the outdoor unit. Remove the front panel and the piping / wiring panel. (M5: 9 pcs.)
• As shown in the illustration on the right, the hooks
are at the right and left sides of the front panel. Lift up and remove the front panel.
2. Pipes can be drawn out forward or downward from the outdoor unit.
3. When drawing out the pipe forward, draw it out to the outside via the piping / wiring panel, and leave a space of 500 mm or more from the main pipe connecting the outdoor unit with the indoor unit, considering service work or other work on the unit. (For replacing the compressor, 500 mm or more space is required.)
4. When drawing out the pipe downward, remove the knockouts on the base plate of the outdoor unit, draw the pipes out of the outdoor unit, and perform piping on the right / left or rear side. Downward length of the balance pipe should be 5 m or less.
5. Wrap a wet cloth around the valve of the pipe connector valve to keep it cool during brazing. (If it is not cooled enough, the heat may affect the packing in the valve and cause gas leaks)
• For a brazing work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant.
* Remove all flux after brazing.
• Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level of tightening cannot be obtained. Tighten the flare nut with the specified torque. (If it is hard to loosen or tighten the flare nut of the balance pipe or packed valve of the liquid side with a double spanner, loosen or tighten the flare nut while holding the valve mounting plate with a spanner.)
Pipe connection method of valve at the gas side (Example)
MMY- Draw-out forward Draw-out downward
MAP080 MAP100
Suction-side gas pipe
Discharge­side gas pipe
Liquid pipe
Cut the L-shaped pipe, then braze the supplied attachment pipe and socket procured locally.
Braze the supplied attachment pipe and elbow procured locally.
Braze the supplied attachment pipe and socket procured locally.
Suction-side gas pipe
Discharge­side gas pipe
Liquid pipe
Cut the L-shaped pipe, then braze the supplied attachment pipe and socket procured locally.
Braze the supplied attachment pipe and socket procured locally.
Braze the supplied attachment pipe and socket procured locally.
19-EN 20-EN
(MAP080, MAP100)(MAP120✽, MAP140✽)
–10–
–11–
Discharge-
side gas pipe
Liquid pipe
Suction-side gas pipe
Suction-side
gas pipe
Section to
be cut
L-shaped pipe
Pipe
Socket
Pipe
PipePipe
Attachment
pipe
Attachment
pipe
Elbow
Discharge-
side gas pipe
Liquid pipe
Suction-side gas pipe
Suction-side
gas pipe
Section to
be cut
L-shaped pipe
Pipe
Socket
Pipe
Pipe
Attachment
pipe
Attachment
pipe
Pipe
Socket
Discharge-
side gas pipe
Liquid pipe
Suction-side gas pipe
Suction-side
gas pipe
Section to
be cut
L-shaped pipe
Socket
Pipe
Attachment
pipe
Attachment
pipe
Elbow
Socket
Pipe
Pipe
Discharge-
side gas pipe
Liquid pipe
Suction-side gas pipe
Suction-side
gas pipe
Section to
be cut
L-shaped pipe
Socket
Pipe
Pipe
Attachment
pipe
Attachment
pipe
Pipe
Socket
Socket
B
+0
-0.4
A
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
MMY- Draw-out forward Draw-out downward
Suction-side gas pipe
Discharge­side gas pipe
Cut the L-shaped pipe, then braze the socket procured locally.
Braze the supplied attachment pipe and elbow procured locally.
Suction-side gas pipe
Discharge­side gas pipe
Cut the L-shaped pipe, then braze the socket procured locally.
Braze the supplied attachment pipe and socket procured locally.
Liquid pipe Braze the supplied attachment pipe. Liquid pipe Braze the supplied attachment pipe.
MAP120
Suction-side gas pipe
Discharge­side gas pipe
Liquid pipe
Cut the L-shaped pipe, then braze the socket procured locally.
Braze the supplied attachment pipe and elbow procured locally.
Braze the supplied attachment pipe and socket procured locally.
Suction-side gas pipe
Discharge­side gas pipe
Liquid pipe
Cut the L-shaped pipe, then braze the socket procured locally.
Braze the supplied attachment pipe and socket procured locally.
Braze the supplied attachment pipe and socket procured locally.
MAP140
Extruding margin of copper pipe with flare machining: B (Unit: mm)
Copper pipe outer
dia.
9.5
12.7
15.9
19.1
When using R410A
tool
0 to 0.5 1.0 to 1.5
When using
conventional tool
Extruding margin of copper pipe with flare tools: A (Unit: mm)
Copper pipe outer dia. A
9.5 13.2
12.7 16.6
15.9 19.7
19.1 24.0
• When using the conventional flare tool, to connect R410A pipes with flaring, make a margin approx. 0.5 mm longer than that of an R22 pipe so that the flare size matches the one specified. It is convenient to use a copper pipe gauge for size adjustment of the extruding margin.
• The flared supplied attachment pipe (Ø19.1) must be used to connect with discharge-side gas pipe (Ø19.1) of MAP120 and MAP140. Do not use half hard or hard materials instead of the supplied attachment pipe. The half hard or hard materials may be cracked and may cause leakage of refrigerant when it is flared.
• Use the flare nut provided with the product.
• After flaring the connection, be sure the flared part is not damaged, deformed, uneven, or flattened, and that there are no cutting chips on it.
Coupling size of brazed pipe
Connected section
External size Internal size
K
ØC
Standard outer dia.
of connected
copper pipe
6.35 6.35 (±0.03) 6.45 ( ) 7 6 0.06 or less 0.50
9.52 9.52 (±0.03) 9.62 ( ) 8 7 0.08 or less 0.60
12.70 12.70 (±0.03) 12.81 ( ) 9 8 0.10 or less 0.70
15.88 15.88 (±0.03) 16.00 ( ) 9 8 0.13 or less 0.80
19.05 19.05 (±0.03) 19.19 ( ) 11 10 0.15 or less 0.80
22.22 22.22 (±0.03) 22.36 ( ) 11 10 0.16 or less 0.82
28.58 28.58 (±0.04) 28.75 ( ) 13 12 0.20 or less 1.00
34.92 34.90 (±0.04) 35.11 ( ) 14 13 0.25 or less 1.20
38.10 38.10 (±0.05) 38.31 ( ) 15 14 0.27 or less 1.26
41.28 41.28 (±0.05) 41.50 ( ) 15 14 0.28 or less 1.35
External size Internal size
G
ØF
Connected section
Standard outer dia.
(Allowable difference)
Min. depth of
insertion
Oval value
CFKG
(Unit: mm)
Min. thickness
of coupling
21-EN 22-EN
Selection of pipe size
NOTE
Indoor unit
Discharge-side
gas pipe
Header unit A
Follower unit C
Follower unit B
(7) <Connecting multiple units (group operation)> When connecting multiple indoor units to one flow selector unit
Outdoor
unit
(1)(1)(1)
(9)
(8) Branching header
(4)
(3) Main piping
(5)
(7)
(2)
(9)
(4)
(1) Balance pipes Ø9.5
Suction-side
gas pipe
Liquid pipe
(7) Y-shaped branching joint
(10)
(5)
(4)
(10)
(5)
(4)
(4)*2
(6) (6)
Cooling only Cooling only
First branch
(10) Flow selector unit
(4)
(5)
(10)
(7)
(7)
(4)
(4)
(10)
(4)*2
(7)
(4)*2
(7)
(6) (6) (6)
Capacity code of indoor and outdoor units
Selection of pipe material
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)
Table 1
Indoor unit
capacity rank
007 0.8 HP 2.2
009 1 HP 2.8
012 1.25 HP 3.6
015 1.7 HP 4.5
018 2 HP 5.6
024 2.5 HP 7.1
027 3 HP 8
030 3.2 HP 9
036 4 HP 11.2
048 5 HP 14
056 6 HP 16
072 8 HP 22.4
096 10 HP 28
Equivalent to HP
Table 2
Outdoor unit
model name
MAP0804 8 HP 22.4 13
MAP1004 10 HP 28 16
MAP1204 12 HP 33.5 20
MAP1404 14 HP 40 23
AP1614 16 HP 45 27
AP1814 18 HP 50.4 30
AP2014 20 HP 56 33
AP2214 22 HP 61.5 37
AP2414 24 HP 68 40
AP2614 26 HP 73 43
AP2814 28 HP 78.5 47
AP3014 30 HP 85 48
AP3214 32 HP 90 48
AP3414 34 HP 96 48
AP3614 36 HP 101 48
AP3814 38 HP 106.5 48
AP4014 40 HP 112 48
AP4214 42 HP 118 48
Equivalent to HPEquivalent to
* For combination of the outdoor units, refer to “Combination of outdoor units”.
23-EN 24-EN
Capacity code
Capacity code
capacity
Equivalent to
capacity
No. of
indoor
units
–12–
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs based on the height difference between the indoor units.
• When the height difference between the indoor units is 15 m or less: Up to 70~135 % of the capacity code (Equivalent to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit
• When the height difference between the indoor units is over 15 m: Up to 70~105 % of the capacity code
–13–
Model
Balance pipe
side
Suction gas
side
Discharge
gas side
Liquid side
MAP080 Ø9.5 Ø22.2 Ø19.1 Ø12.7
MAP100 Ø9.5 Ø22.2 Ø19.1 Ø12.7
MAP120 Ø9.5 Ø28.6 Ø19.1 Ø12.7
MAP140 Ø9.5 Ø28.6 Ø22.2 Ø15.9
Total capacity codes of outdoor units at
the downstream side
Suction
gas side
Discharge
gas side
Liquid
side
Equivalent to
capacity
Equivalent to HP
45.0 to below 61.5 16 to below 22 Ø28.6 Ø22.2 Ø15.9
61.5 to below 73.0 22 to below 26 Ø34.9 Ø28.6 Ø19.1
73.0 or more 26 or more Ø34.9 Ø28.6 Ø19.1
Total capacity codes of all
outdoor units
Suction
gas
side
Discharge
gas side
Liquid
side
Equivalent to
capacity
Equivalent to
HP
22.4 to below 33.5 8 to below 12 Ø22.2 Ø19.1 Ø12.7
33.5 to below 38.4 12 to below 14 Ø28.6 Ø19.1 Ø12.7
38.4 to below 45.0 14 to below 16 Ø28.6 Ø22.2 Ø15.9
45.0 to below 61.5 16 to below 22 Ø28.6 Ø22.2 Ø19.1
61.5 to below 73.0 22 to below 26 Ø34.9 Ø28.6 Ø19.1
73.0 to below 101.0 26 to below 36 Ø34.9 Ø28.6 Ø22.2
101.0 or more 36 or more Ø41.3 Ø34.9 Ø22.2
Total capacity codes of indoor
units at the downstream side
Suction
gas
side
Discharge
gas side
Liquid
side
Equivalent to
capacity
Equivalent to
HP
Below 18 Below 6.4 Ø 15.9 Ø12.7 Ø9.5
18 to below 34 6.4 to below 12.2 Ø22.2 Ø19.1 Ø12.7
34 to below 45.5 12.2 to below 16.2 Ø28.6 Ø22.2 Ø15.9
45.5 to below 56.5 16.2 t o below 20.2 Ø28.6 Ø22.2 Ø19.1
56.5 to below 70.5 20.2 t o below 25.5 Ø34.9 Ø28.6 Ø19.1
70.5 to below 98.5 25.2 t o below 35.2 Ø34.9 Ø28.6 Ø22.2
98.5 or more 35.2 ore more Ø41.3 Ø34.9 Ø22.2
Capacity rank Equivalent to HP Gas side Liquid side
007 to 012 0.8 to 1.25 Ø9.5 Ø6.4
015 to 018 1.7 to 2.0 Ø12.7 Ø6.4
024 to 056 2.5 to 6.0 Ø15.9 Ø9.5
072 to 096 8.0 to 10.0 Ø22.2 Ø12.7
Capacity rank
Equivalent to
HP
Length of piping Gas side
Liquid
side
007 to 012 0.8 to 1.25
15 m or less real length Ø9.5 Ø6.4
Exceeds 15 m real length Ø12.7 Ø9.5
015 to 018 1.7 to 2.0
15 m or less real length Ø12.7 Ø6.4
Exceeds 15 m real length Ø15.9 Ø9.5
024 to 056 2.5 to 6.0 - Ø15.9 Ø9.5
072 to 096 8.0 to 10.0 - Ø2 2.2 Ø12.7
Total capacity code of indoor units Model name
Equivalent to capacity
Equivalent to HP For 3 piping For 2 piping
Below 18.0 Below 6.4 RBM-BY55FE RBM-BY55E
18.0 to below 40.0 6.4 to below 14.2 RBM-BY1 05FE RBM-BY105E
40.0 to below 70.5 14.2 to below 25.2 RBM-BY205 FE RBM -BY205E
70.5 or more 25.2 or more RBM-BY305FE RBM-BY305E
Total capacity code of indoor units Model name
Equivalent to
capacity
Equivalent to
HP
For 3 piping For 2 piping
For 4 branches
Below 40.0 Below 14.2 RBM-HY1043FE RBM-HY1043E
40.0 to below 70.5 14.2 to below 25.2 RBM-HY2043FE RBM-HY2043E
For 8 branches
Below 40.0 Below 14.2 RBM-HY1083FE RBM-HY1083E
40.0 to below 70.5 14.2 to below 25.2 RBM-HY2083FE RBM-HY2083E
Total capacity codes of outdoor units at the
downstream side
Model name
Equivalent to capacity Equivalent to HP
Below 73.0 Below 26.0 RBM-BT14FE
73.0 or more 26.0 or more RBM-BT24FE
Total capacity codes of connected indoor units
Model name
Equivalent to
capacity
Equivalent to HP
Max. No. of
connected indoor
unit
Below 11.2 Below 4.0 Below 5 RBM-Y1123FE
11.2 to below 18.0 4.0 to below 6.4 Below 8 RBM-Y1803FE
18.0 to 28.0 or less 6.4 to below 10.0 Below 8 RBM-Y2803FE
Selection of pipe size
No.
(1)
(2)
(3)
(4)
Title Use part Selection of pipe size Remarks
Outdoor unit
Outdoor unit connecting pipe
Between Outdoor unit connection piping *6
Main piping
Branching pipe *1, *2, *6
Outdoor unit connection piping kit
Outdoor unit connection piping kit
Outdoor unit connection piping kit
Outdoor unit connection piping kit of header unit
First branching section
Branching section
Branching section
Branching section
Flow Selector unit
Flow Selector unit
Branching section
Pipe size differs based on the total capacity codes of all outdoor units (See Table 2.)
Pipe size differs based on the total capacity code value of indoor units at the downstream side. (See Table 1 and 2.)
No.
Indoor unit
(6)
connecting pipe
Y-shaped branching joint
(7)
*3, *4
Branching header
(8)
*3, *4, *5
Outdoor unit connection piping
(9)
kit *6
Flow Selector unit
(10)
*7
Title Use part Selection of pipe size Remarks
Terminal branching section
Indoor unit
Branching section
Branching section
Branching section
*1: Use the same size as the main pipe if it is larger tha n the main pipe.
25-EN 26-EN
Indoor unit
(5)
connecting pipe
Flow Selector unit
Indoor unit
*2: Use a suction gas pipe and a liquid pipe for the two pipes branching downstream from the flow selector unit and the dedicated cooling circuit. *3: Select the branch pipe of the first branch according to the outdoor capacity code. *4: Select according to the outdoor unit capacity code if the total of the indoor capacity codes exceeds the outdoor unit capacity code. *5: It is possible to select up to a maximum capacity code total AP056 (6 hp) for the first cir cuit after the header branch .
When using a branch header for the first branch with an outdoor unit capacity code of 33.5 (12 hp equivalent) or more and 73.0 (26 hp equivalent) or less, use RBM-HY2043 FE (4 branches) and RBM-HY-2083FE (8 branches) regardless of the total value of the capacity codes of the downstream indoor units. And, a branch header cannot be used as the first branch if the performance rank is over 73.0 (26 hp
equivalent). *6: The downstream star ting point is the main pipe. *7: Only group operation with one remote controller (or two remote controllers) is possible if one flow selector unit is connected to multiple
indoor units.
Allowable length of refrigerant pipes and allowable height
Height difference between outdoor units H3 5 m
Height difference between indoor units: H2 40 m
LcLbLa
L8
LA
Outdoor unit connection piping kit
Outdoor unit connecting pipes
Main piping L1
Height difference between outdoor and indoor units: H1 50 m
First
branching
section
L3
L4
L5
L6
Indoor unit
f
The longest piping length: L 200 m
a
A
Header unit
C Follower unit
B
Follower unit
(c)
(b)(a)
Outdoor
unit
Branching pipe L2
Heating / cooling switching unit connecting pipe
Branching header
Y-shaped branching joint
g
b
h
c
kl
The longest piping length from the first branch: Li 65 m
Length equivalent to furthest pipe in heating / cooling
switching unit group: Ln 30 m
L7
Flow selector unit
Indoor unit
connecting pipe i
d
e
j
mn
(m) (n)
(o)
Height difference between indoor units
(In the same heating / cooling switching unit group)
H4 0.5 m
(When outdoor unit is higher)
(When outdoor unit is higher)
o
Farthest piping length between outdoor units LO 15 m
difference between units
System restriction
Outdoor unit combination Up to 3 units
Total capacity of outdoor units Up to 42 HP
Indoor unit connection Up to 48 units
Total capacity of indoor units (varies depending on the height difference between indoor units.)
H2 15 m 135 % of outdoor units’ capacity
15 m < H2 105 % of outdoor units’ capacity
Limit on connecting multiple indoor units to flow selector unit
Model name RBM-Y1123FE RBM-Y1803FE✽ RBM-Y2803FE✽
Total capacity codes of connected indoor units Below 11.2 11.2 to below 18.0 18.0 to 28.0 or less
Max. No. of connected indoor unit Below 5 Below 8 Below 8
Cautions for installation
• Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) B ≥ C
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit
and those to indoor units at a right angle as shown in figure 1 on “6. Installation of the outdoor unit”. Do not connect them as in figure 2 on “6. Installation of the outdoor unit”.
27-EN 28-EN
–14–
–15–
WARNING
NOTE
REQUIREMENT
VL
VH
Connected to indoor unit
Main
piping
Suction gas side valve fully closed
Low pressure gauge
High pressure gauge
Brazed
Header outdoor unit
Fully closed
Fully closed
Connected to other follower units
Balanced pipe side valve fully closed
Liquid side valve fully closed
Service port
Ø6.4 copper pipe
Ø6.4 copper pipe
Nitrogen gas
Reducing valve
Gauge manifold
To gauge manifold
Liquid-side service port
Packed valve of balance pipe side
Service port of
discharge gas side
Piping at
site
Ball valve of
suction gas side
Service port of
suction gas side
Piping at site
To outdoor unit
To outdoor unit
Liquid-side valve
Packed valve
details
To outdoor unit
Service port of balance pipe side
Fully closed
Discharge gas side valv e fully closed
Service port To gauge manifold
To outdoor unit
Ball valve of
discharge gas side
Piping at site
Piping at site
Allowable length and allowable height difference of refrigerant piping
Item
Total extension of pipe (liquid pipe, real length)
Farthest piping length L (*1, *3)
Max. equivalent length of Main piping
Pipe length
Height difference
<In case of connecting flow selec tor unit to multiple indoor units>
*1: Farthest outdoor unit from the first branch: (C), farthest indoor unit: (o) *2: Run wires to one indoor unit a nd flow selector unit linked with on e of those remote controllers if flow selector unit is connect ed to multiple
indoor units.
*3: Allowable values for length equivalent to furthest pipe are shown below and they vary according to performance rank of outdoor unit.
22.4 to 40.0: 185 m, 45.0 t o 78.5: 195 m, 85.0 to 118. 0: 200 m
*4: When system capacity is greater than 28 HP, height difference between indoor units is limited to 3 m. If the piping exceeds 3 m with a
capacity greater than 28 HP there may be a case of capacity shortage in cooling.
*5: Ensure that the header unit is installed below all connected follower outdoor unit(s).
Possible product failure may occur if header unit is installe d above any follower unit(s).
29-EN 30-EN
Farthest equivalent piping length from the first branch Li (*1)
Farthest equivalent piping le ngth between outdoor units L0 (*1)
Maximum equivalent piping length of pipes connected to outdoor units
Maximum real length of terminal branching section to indoor units
Maximum real length of between Flow Selector unit and indoor unit
Maximum equivalent length between branching sections 50 m L2, L3, L4, L8
Height between outdoor and indoor units H1
Height between indoor units H2
Height between outdoor units H3 (*5) 5 m
Maximum equivalent length in door units in group control by one Flow Selector unit Ln
Maximum real length between Flow Selector unit and indoor unit (*2)
Height difference between indoor units in group control by one Flow Selector unit H4
Less than 34 HP or less 300 m LA + La + Lb + Lc + L1 + L2 + L3 + L4 + L5 + L6
34 HP or more 500 m
Equivalent length 200 m
Real length 180 m
Equivalent length 100 m
Real length 85 m
Equivalent length 120 m
Real length 100 m
H2 > 3 m 50 m
H2 3 m 65 m
Upper outdoor
units
Lower outdoor
units
Upper outdoor
units
Lower outdoor
units (*4)
H2 > 3 m
H2 3 m
Allowable
value
+ L7 + L8 + a + b + c + d + e + f + g + h + i + j +
LA + Lc + L1 + L3 + L4 + L5 + L6 + L7 + o
15 m LA + Lc (LA + Lb)
10 m Lc (La, Lb)
30 m a + f, b + g, c + h, d + l, e + j, k, l
15 m f, g, h, l, j
50 m
30 m
40 m
15 m
30 m L5 + L6 + L7 + o
To run wires to indoor unit (m):
15 m
To run wires to indoor unit (n):
0.5 m
k + l + m + n + o
L3 + L4 + L5 + L6 + L7 + o
L6 + m ≤ 15 m, L5 + L6 + L7 + n ≤ 30 m, L5 + L6 + L7 + o 30 m
L5 + L6 + m 30 m, L6 + L7 + n 15 m, L5 + L6 + L7 + o 30 m
Pipes
L1
Airtightness test
After the refrigerant piping has been finished, execute an airtight test. For an airtight test, connect a nitrogen gas canister as shown in the figure below and apply pressure.
• Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the liquid side, discharge gas side, suction gas side and balance pipe side.
• An airtight test can only be performed at the service ports at the liquid side, gas side and balance pipe side on header unit.
• Close the valves fully at the gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side before applying pressure.
• For each refrigerant line, apply pressure gradually in steps at the liquid side, discharge gas side, suction gas side and balance pipe side.
Be sure to apply pressure at the discharge gas side, suction gas side, liquid side, and balance pipe side.
Never use oxygen, flammable gases, or noxious gases in an airtight test.
Able to detect a serious leakage
1. Apply pressure 0.3 MPa (3.0 kg/cm²G) for 5 minutes or more.
2. Apply pressure 1.5 MPa (15 kg/cm²G) for 5 minutes or more.
Available to detect slow leakage
3. Apply pressure 3.73 MPa (38 kg/cm²G) for approx. 24 hours.
• If there is no pressure decrease after 24 hours, the test is passed.
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the pressure will change by about 0.01 MPa (0.1 kg/cm²G) per 1 °C. Consider the pressure change when checking the test result.
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points. Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or other methods. After sealing, execute an airtight test again.
Vacuum drying
P
V
L
VH
Connected to indoor unit
Main pipe
Low pressure
gauge
High pressure gauge
Brazed
Fully closed
Fully closed
Connected to other follower units
Balanced pipe side valve fully closed
Service port
Vacuum pump
Gauge manifold
Service port
Header outdoor unit
Fully closed
To gauge manifold
Liquid-side service port
Liquid-side valve
Piping at
site
Packed valve of balance pipe side
Ball valve of
suction gas side
Service port of
suction gas side
Piping at site
To outdoor unit
To outdoor unit
Packed valve
details
To outdoor unit
Service port of balance pipe side
To gauge manifold
To outdoor unit
Piping at site
Suction gas side valve fully closed
Liquid side valve fully closed
Discharge gas side valve fully closed
Service port of
discharge gas side
Ball valve of
discharge gas side
Piping at site
NOTE
• Be sure to use a vacuum pump equipped with the counter-flow prevention function so that oil in the pump will not flow back into piping for air conditioners. (If oil in the vacuum pump enters in the air conditioner with R410A refrigerant, a problem may be caused in the refrigerating cycle.)
After finishing the airtight test and discharging nitrogen gas, connect the gauge manifold to the service ports of the liquid side , discharge gas side, suction gas side, and balance pipe side and connect a vacuum pump as shown in the figure below. Be sure to perform vacuuming for the liquid, discharge gas side, suction gas side, and balance pipe sides.
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount factory default does not include the refrigerant for pipes at the local site. For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional refrigerant.
Outdoor unit type MAP080 MAP100 MAP120 MAP140
Charging amount (kg) 11. 0
Additional refrigerant
charge amount at local site
Real length of liquid pipe
=
Additional refrigerant
charge amount per 1 m
×
liquid pipe (Table 1)
1.3
×
Corrective amount of
refrigerant depending on HP
+
of co-operating outdoor units
(Table 2)
Table 1
Liquid pipe dia. (mm) 6.4 9.5 12.7 15.9 19.1 22.2
Additional refrigerant amount / 1 m liquid pipe (kg/m)
0.025 0.055 0.105 0.160 0.25 0 0.35 0
• Use a vacuum pump with a high vacuuming degree [-100.7 kPa (5 Torr, -755 mmHg)] and large exhaust gas amount (40 L/minute or larger).
• Perform vacuuming for 2 or 3 hours, though the time differs depending on the pipe length. Check that all the valves at the liquid side, discharge gas side, suction gas side, and balance pipe side are fully closed.
• If the pressure does not reach 100.7 kPa or less even after vacuuming for over 2 hours, continue vacuuming for 1 hour or more. If the pressure does not reach -100.7 kPa after 3 hours of vacuuming, stop vacuuming and check for air leakage.
• If the pressure reaches -100.7 kPa or less after vacuuming for 2 hours or more, close the valves VL and VH on the gauge manifold fully and stop the vacuum pump. Leave it as it is for 1 hour to confirm that the vacuuming degree does not change. If the degree of vacuum loss is large, moisture may remain in the pipes. In that case, inject dry nitrogen gas and apply pressure to 0.05 MPa and perform vacuuming again.
• After finishing the above procedure of vacuuming, exchange the vacuum pump with a refrigerant canister and advance to the additional charging of refrigerant.
• To protect the world's environment, do not release chlorofluorocarbons into the atmosphere.
• Do not do an air purge including used refrigerant.
31-EN 32-EN
–16–
–17–
Using flathead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Service port
Flare nut
Valve unit
(1)
(2)
Fully closed
Fully opened
Slot
Position of screwdriver slot
* When opened fully, do not apply excessive torque
after the screwdriver hits the stopper; otherwise a
problem may be caused on the valve. (5 N•m or less)
Fully closed
Fully opened
Table 2
Equivalent
HP
8 HP MAP0804 MAP0804✽ –– 2
10 HP MAP1004 MAP1004✽ –– 3
12 HP MAP1204 MAP1204✽ –– 8
14 HP MAP1404 MAP1404✽ ––10
16 HP AP1614 MAP0804✽ MAP0804✽ –0
18 HP AP1814 MAP1004✽ MAP0804✽ –1.5
20 HP AP2014 MAP1004✽ MAP1004✽ –3.5
22 HP AP2214 MAP1204✽ MAP1004✽ –7.5
24 HP AP2414 MAP1404✽ MAP1004✽ –8.5
26 HP AP2614 MAP1404✽ MAP1204✽ –11
28 HP AP2814 MAP1404✽ MAP1404✽ –12
30 HP AP3014 MAP1004✽ MAP1004✽ MAP1004✽ 2.5
32 HP AP3214 MAP1204✽ MAP1004✽ MAP1004✽ 5
34 HP AP3414 MAP1404✽ MAP1004✽ MAP1004✽ 6
36 HP AP3614 MAP1204✽ MAP1204
38 HP AP3814 MAP1404✽ MAP1204✽ MAP1204✽ 9.5
40 HP AP4014 MAP1404✽ MAP1404✽ MAP1204✽ 11
42 HP AP4214 MAP1404✽ MAP1404✽ MAP1404✽ 12.5
Model name of
outdoor unit
MMY-
Combination of outdoor unit
MMY-
Unit 1 Unit 2 Unit 3
MAP1204 8
Corrective of
refrigerant
(kg)
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080 MAP100
Balance pipe
Liquid side
Discharge gas side
Ø9.5 packed valve
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Ø12.7 packed valve
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Ø19.1 ball valve
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Ø25.4 ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
MAP120 MAP140
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the valve shaft.
Suction gas side
After opening the valves fully, be sure to close the caps.
When you close the valve shaft, its cap and service port cap, see below chart.
Valve size
Ø9.5 packed valve 14 to 18 14 to 18 7 to 9
Ø12.7 packed valve 20 to 25 14 to 18 7 to 9
33-EN 34-EN
Ø15.9 packed valve 33 to 42 14 to 18 14 to 16
Ø19.1 ball valve 20 to 25 14 to 18
Ø25.4 ball valve 20 to 25 14 to 18
Valve shaft cap (N·m) Service port cap (N·m) Valve shaft (N·m)
Tightening torque
F-GAS label
CAUTION
R410A
kg
kg
kg
Pre-charged Refrigerant at Factory [kg], specified in the nameplate
Additional Charge on Installation Site [kg]
Piping / wiring panel
Drawing-out sideward
Close the opening with the pipe cover.
Drawing-out frontward
Drawing-out downward
Piping / wiring panel
Drawing-out sideward
Fill silicon or putty into the periphery of the pipes.
Drawing-out frontward
Drawing-out downward
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol
• Chemical Name of Gas R410A
• Global Warming Potential (GWP) of Gas 1975
1. Stick the enclosed refrigerant label adjacent to the charging and/or recovering location.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the included
transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained fluorinated greenhouse gas. Ensure that the fluorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained fluorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only qualified service personnel are allowed to access and service this product.
5. Any handling of the fluorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EC) Regulation No. 842/2006 on certain fluorinated greenhouse gases and any relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Heat insulation for pipe
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use heat insulator resistant up to 120 °C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been finished, cover the opening of the piping / wiring panel with the piping cover, or fill silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
When using the piping cover When not using the piping cover
Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm) Interval
Ø15.9 - Ø19.1 2 m
Ø22.2 - Ø41.3 3 m
35-EN 36-EN
–18–
–19–
WARNING
CAUTION
Power supply for outdoor units
NO GOOD
L1L2L3 N L1L2L3 N L1L2L3 N
Circuit breaker
(Earth leakage breaker)
Main switch (Fuse)
8 Electric wiring
The appliance shall be installed in accordance with national wiring regulations. Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Refer to H07RN-F or 60245 IEC 66 regarding specifications of the power supply wire.
• Do not connect 380 V - 415 V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise, the unit may break down.
• Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Follow the same structure for both the control wiring and refrigerate piping.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
• Refer to the installation manuals of indoor unit and flow selector unit for power wiring and communication wiring of indoor unit and flow selector unit.
Power supply specifications
Do not bridge the power between outdoor units through the equipped terminal blocks (L1, L2, L3, N).
Power wiring selection
Standard model
MOCP: Maximum Overcurrent Protection (Amps)
Equivalent HP
8 HP MAP0804
10 HP MAP1004 27.1 32
12 HP MAP1204 31.2 40
14 HP MAP1404 36.4 50
16 HP AP1614
18 HP AP1814 51.6 63
20 HP AP2014 54.2 63
22 HP AP2214 58.3 80
24 HP AP2414 63.5 80
26 HP AP2614 67.6 80
28 HP AP2814 72.8 100
30 HP AP3014
32 HP AP3214 85.4 100
34 HP AP3414 90.6 125
36 HP AP3614 93.6 125
38 HP AP3814 98.8 125
40 HP AP4014 104 125
42 HP AP4214 109 125
Model name of
outdoor unit
MMY-
Power Supply
Phase and
frequency
3 N~ 50 Hz 380-400-415 V 342 456
3 N~ 50 Hz 380-400-415 V 342 456
3 N~ 50 Hz 380-400-415 V 342 456
Nominal
Voltage
Voltage Range
Min Max
MCA: Minimum Circuit Amps
(V)
MCA
MOCP
(A)
24.5 32
49.0 63
81.3 100
(A)
37-EN 38-EN
Specifications for communication wiring
U1 U2 U3 U4 U5 U6 U1 U2 U3 U4 U5 U6
U1 U2 U3 U4
U1 U2 A B U1 U2 A B U1 U2 A B U1 U2 A B
AB AB AB
CN02
CN81
CN02
CN81
CN02
CN81
CN02
CN81
Central remote device (option)
Outdoor unit
Header unit
Outdoor unit Follower unit
Control wiring between outdoor units (Shield wire)
Central control wiring (Shield wire)
Control wiring between indoor and outdoor units (Shield wire)
Indoor unit Indoor unit Indoor unit Indoor unit
Remote controller
Remote controller
Remote controller
(Group control)
Control wiring between indoor units (Shield wire)
Flow selector unit Flow selector unit Flow selector unit Flow selector unit
U3 U4
U1 U2
U1U3U2
U4
U5 U6
U1 U2
A B
U3 U4
U1 U2
U5 U6
U1 U2
A B
U1 U2
A B
U1 U2
A B
U1 U2
A B
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
U3 U4
U1 U2
U5 U6
U1 U2
A B
U1 U2
A B
U1 U2
A B
U3 U4
U1 U2
U5 U6
L1
L5
L6
L7
L4
L2 L3
Header
unit
Header unit
Follower unit
Follower unit
Follower unit
Header unit
Follower unit
Super modular multi system
Central control
controller
Outdoor unit
Indoor unit
Table-1
Table-2
Table-1
Remote controller
Remote controller
Remote controller
Table-3
Design of communication wiring
Summary of communication wiring
Be sure to keep the rule of below tables about size and length of communication wiring.
Table-1 Communication wiring between indoor and outdoor units (L1, L2, L3), Central control wiring
(L4)
Wiring 2-core, non-polarity
Type Shield wire
Size / Length 1.25 mm
(*1): Total length of Communication wiring length for all refrigerant circuits (L1 + L2 + L3 + L4)
2
: Up to 1000 m / 2.0 mm2: Up to 2000 m (*1)
Table-2 Communication wiring between outdoor units (L5)
• Communication wiring and central control wiring use 2-core non-polarity wires.
39-EN 40-EN
Use 2-core shield wires to prevent noise trouble.
• Connecting the closed end terminal of shield wire. (Connected to all connecting sections in each unit)
• Use 2-core non-polarity wire for remote controller. (A, B terminals) Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
• Control wire and power line wire between Flow selector unit and indoor unit are the accessory parts of Flow selector unit. (Wire length : 6m) If the length between indoor unit and Flow selector unit exceeds 5m, connect by using the Connection cable kit sold separately (RBC-CBK15FE).
–20–
Wiring 2-core, non-polarity
Type Shield wire
2
Size / Length 1.25 mm
to 2.0 mm2 / Up to 100 m (L5)
Table-3 Remote controller wiring (L6, L7)
Wire 2-core, non-polarity
Size 0.5 mm
Length
2
to 2.0 mm2
• Up to 500 m (L6 + L7)
• Up 400 m in case of wireless remote controller in group control.
• Up to 200 m total length of communication wiring between indoor units (L6)
Group control through a remote controller
NOTE
AB AB AB AB AB AB
(A.B)
Remote controller
Indoor unit
No.1
No.2
No.3
No.4
No.7
No.8
Piping / wiring panel
Knockout for the power supply wire
Knockout for the power wire
Knockout for the
communication wire
Power supply terminal block
Cord clamps
Communication terminal block
Power supply wires
Earth screw
Cord clamp
Communication
wires
Electrical control box
L1 L2 L3 N
L1 L2 L3
N
10 mm or more
Earth wire
Power supply wire
Group control of multiple indoor units (8 units) through a single remote controller switch
Connection of power wires and communication wires
Remove knockouts on the piping / wiring panel on the front of the unit and the panel on the bottom to get the power and communication wires through the holes.
Be sure to separate the power wire and communication wires.
–21–
Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power supply wire to the power supply terminal block and the earth wire to the earth screw. After that, fix the power supply wire with the 2 cord clamps.
2. Be sure to use round-type crimping terminals for power connection. Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.
41-EN 42-EN
Screw size and tightening torque
U1 U2 U3 U4 U5 U6
U5, U6: Communication wiring between outdoor units
U
3, U4: Central control device
U
1, U2: Communication wiring between Indoor / Outdoor unit
TO
INDOOR
UNIT
TO
CENTRAL
CONTROL
LER
TO
OUTDOOR
UNIT
Ssc (*1)
Model Ssc (kVA)
MMY-MAP0804FT8(Z)(ZG)-E 1290
MMY-MAP1004FT8(Z)(ZG)-E 1560
MMY-MAP1204FT8(Z)(ZG)-E 1692
MMY-MAP1404FT8(Z)(ZG)-E 1942
Screw size
Power supply terminal M6 2.3 to 2.7
Earth screw M8 5.5 to 6.6
Tightening torque
(N•m)
Regulation of harmonic current
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1)
Communication wire connection
Get the communication wire through the cutout on the side of the electrical control box and connect it to the communication wire terminals, then fix it with the communication cable clamp.
Screw size and tightening torque
Screw size
Communication wire terminal M4 1.2 to 1.4
Tightening torque
(N•m)
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the interface point.
43-EN 44-EN
–22–
–23–
CAUTION
REQUIREMENT
Access door cover
Fixing screw for the access door cover
Cover of the electrical control box
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Central
remote
controller
Central
remote
controller
Remote
controller
Remote
controller
Remote
controller
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Central remote
controller
Remote
controller
Remote
controller
Remote
controller
REQUIREMENT
U. 1. L08 (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. flash)
U. 1. - - - (U. 1. light)
SW04
SW05 SW15
SW01
SW02 SW03
D600 D601 D602 D603
D604
3
2,4
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Remote
controller
(Group control)
9 Address setting
On this unit, it is required to set the addresses of the indoor units before starting air conditioning. Set the addresses following the steps below.
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7­segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a malfunction.
• It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Automatic addressing: setting addresses using SW15 on the interface P.C. board on the header outdoor unit Manual addressing:
• High voltage parts exist in the electrical control box. If you set addresses on an outdoor unit, operate the unit through the access door shown on the illustration on the right to avoid electric shock. Do not remove the cover of electrical control box.
* After finishing operations, close the access door cover
and fix it with the screw.
setting addresses on the wired remote controller. * When setting an address manually, the wired remote controller must temporarily be
paired with an indoor unit one-to-one. (when the system is organized for group operation and no Remote controller)
Address setting procedure 1
1 Turn on indoor units first, and then turn on outdoor units. 2 About one minute after turning the power on, confirm that the 7-segment display on the interface
P.C. board of the header outdoor unit indicates .
3 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
4 The 7-segment display indicates .
After the indication, starts flashing on the display. When the flashing stops and remain lit on the display, the setting is complete.
Interface P.C. board on the header outdoor unit
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group before setting addresses.
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case, the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to make one unit the header unit using wired remote controller.
Automatic address setting
No central control (single refrigerant line): go to Address setting procedure 1 Central control of 2 or more refrigerant lines: go to Address setting procedure 2
(Example)
Address setting procedure
System wiring diagram
45-EN 46-EN
When controlling a single refrigerant line
centrally
To procedure 1 To procedure 2
When controlling 2 or more refrigerant lines
centrally
(Example) Controlling 2 or more refrigerant lines as a group
System wiring diagram
Address setting procedure 2
NOTE
SW06 SW07 SW09 SW10
SW11 SW12 SW13 SW14
1234 1234 1234 1234
1234 1234 1234 1234
U1 U2 U3 U4 U5 U6
2
TO
INDOOR
UNIT
TO CENTRAL CONTROL
LER
TO
OUTDOOR
UNIT
U. 1. L08 (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. flash)
U. 1. - - - (U. 1. light)
1 Set a system address for each system using SW 13 and 14 on the interface P.C. board on the
header outdoor unit of each system. (Factory default: Address 1)
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a custom side.
Line (system) address
26 ✕✕
27
28 
“–”: not used for system address setting (Do not change their positions.)
12341234
2 Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on all the
SW13 SW14
header outdoor units that will be connected to the central control. (Factory default: disconnected)
Interface P.C. board on the header outdoor unit
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
(: switch ON, : switch OFF)
Line (system) address
1–✕✕✕✕✕
2– ✕✕✕
3–✕✕ ✕✕
4– ✕✕
5–✕✕✕
6–
7–✕✕
8– 
9–✕✕✕✕
10 ✕✕
11 ✕✕
12 
13 ✕✕✕
14 
15 ✕✕
16 
17 ✕✕✕✕
18 ✕✕✕
19 ✕✕
47-EN 48-EN
20 ✕✕
21 ✕✕
22 
23 
24 
25
12341234
SW13 SW14
✕✕✕
–24–
3 Turn on indoor units first, and then turn on outdoor units. 4 About 1 minute after turning the power on, confirm that the 7-segment display on the interface
P.C. board of the header outdoor unit indicates .
5 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
6 The 7-segment display indicates .
After the indication, starts flashing on the display. When the flashing stops and , remains lit on the display, the setting is complete.
7 Repeat steps 4 to 6 for other refrigerant lines. 8 After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
–25–
9
TO
INDOOR
UNIT
TO
CENTRAL
CONTROL
LER
TO
OUTDOOR
UNIT
SW15
SW04
12
SW13 SW14
SW01 SW02
SW03
D600 D601 D602 D603 D604
SW05
SW30
7-segment
display
Header unit interface P.C. board
* Header unit connected to the same
centralized management, except header unit with lowest circuit address number.
A
U1 U2
U3 U4 U3 U4 U3 U4 U3 U4 U3 U4
U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2
U1 U2 U1 U2 U1 U2 U1 U2 U1 U2
U5 U6
BAB ABAB AB
Central
control
controller
Relay
connector
Relay
connector
Relay
connector
Header unit
Header unit
Header unit
Follower unit
Follower unit
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Individual
Group
Indoor units (automatic setting)
9 Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the header outdoor
unit of each refrigerant line.
U1 U2 U3 U4 U5 U6
10
Set the central control address.
(For the setting of the central control address, refer to the installation manuals of the central control devices.)
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
Outdoor unit’s interface
P.C. board
SW13, 14 (Line (system) address)
Dip switch 2 of SW30 (Terminator of indoor / outdoor communication line and central control line)
Relay connector
Header unit Follower unit Header unit Follower unit Header unit Factory default
1
ON
Connect after
setting
addresses.
(No setting
required)
(No setting
required)
Open
2
Set to OFF
after setting
addresses.
Connect after
setting
addresses.
*The items in bold font must be set manually.
(No setting
required)
(No setting
required)
Open
3 1
Set to OFF
after setting
addresses.
Connect after
setting
addresses.
ON
Open
Line (system) address 1 1 2 2 3
49-EN 50-EN
Indoor unit address 1 2 1 2 1
Group address 0 0 1 2 0
CAUTION
Relay connector connection
Outdoor
unit
Outdoor
unit
Remote
controller
Indoor unit 1
Indoor unit 2
Indoor unit 3
Indoor unit 1
Indoor unit 2
Refrigerant line 1
Refrigerant line 2
SET DATA
CODE No.
NOTE
SET
}
SET
SETTING
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all the refrigerant lines. Otherwise, the addresses cannot be set correctly.
Manual address setting using the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Line (system) address 1 1 1 2 2
Indoor unit address 1 2 3 1 2
Group address
In the example above, disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting.
2, 5, 8
4, 7, 10
1
Header unit2Follower unit2Follower unit2Follower unit2Follower unit
UNIT No.
R.C. No.
CODE No.
ON / OFF
11
FILTER RESET
SET
TEMP.
DATA
SETTING
TIMER SET
TIME
SET CL
TEST
3, 6, 9
<Line (system) address>
2 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
3 Push the TIME / buttons repeatedly to
set a system address.
(Match the address with the address on the interface P.C. board of the header outdoor unit in the same refrigerant line.)
4 Push button.
(It is OK if the display turns on.)
<Indoor unit address>
5 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
6 Push the TIME / buttons repeatedly to
set an indoor unit address.
7 Push the button.
(It is OK if the display turns on.)
<Group address>
SET
8 Push the TEMP. / buttons
repeatedly to set the CODE No. to .
9 Push the TIME / buttons repeatedly to
set a group address. If the indoor unit is individual, set the address to ; header unit, ; follower unit, .
Individual : 0000 Header unit : 0001 Follower unit : 0002
10
Push the button.
(It is OK if the display turns on.)
11
Push the button.
The address setting is complete. ( flashes. You can control the unit after has disappeared.)
TEST
In case of group
}
control
SETTING
1. Do not use address numbers 29 or 30 when setting
system addresses using the remote controller. These 2 address numbers cannot be used on outdoor units and the CODE No. [E04] (Indoor / outdoor communication error) will appear if they are mistakenly used.
2. If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will control them centrally, set the header outdoor unit of each line as below.
• Set a system address for the header outdoor unit
of each line with SW13 and 14 of their interface P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address. (For unifying the termination of the wiring for the central control of indoor and outdoor units)
• Connect the relay connectors between the [U1,
U2] and [U3, U4] terminals on the header outdoor unit of each refrigerate line.
• After finishing all the settings above, set the
address of the central control devices. (For the setting of the central control address, refer to the installation manuals of the central control devices.)
1
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1 Push and hold the , , and buttons at the same time for more than 4 seconds.
51-EN 52-EN
LCD starts flashing.
SET
CL
TEST
–26–
–27–
Starts running
Stop
VENT
TEST
SWING/FIX
SET
CL
TEST
Finish
SET
CL
TEST
Confirming the indoor unit
addresses and the position of an indoor unit using the remote controller
Confirming the numbers and positions of indoor units
To see the indoor unit address of an indoor unit which you know the position of
When the unit is individual (the indoor unit is
paired with a wired remote controller one-to­one), or it is a group-controlled one.
CODE No.
UNIT No.
FILTER RESET
TEMP.
TEST
TIMER SET
TIME
SET CL
ON / OFF
1
2
(Execute it while the units are running.)
1 Push the button if the units stop. 2 Push the button (left side of the
button).
A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows the system address and indoor unit address of the unit. When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other connected units appears each time you push the button (left side of the button).
ON / OFF
To find an indoor unit’s position from its address
When checking unit numbers controlled as a
group
UNIT No.
R.C. No.
CODE No.
ON / OFF
1
2
DATA
SET
SETTING
TEMP.
TIMER SET
3
FILTER RESET
TIME
SET CL
TEST
1
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated.
1 Push and hold the and buttons at
the same time for more than 4 seconds.
appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the group are activated.
2 Push the button (left side of the
button). Each time you push the button, the indoor unit numbers are indicated one after another.
• The first-indicated unit number is the address of the header unit.
• Only the fan and louvers of the indicated indoor unit are activated.
3 Push the button to finish the procedure.
All the indoor units in the group stop.
TEST
To check all the indoor unit addresses using
an arbitrary wired remote controller. (When communication wirings of 2 or more refrigerant lines are interconnected for central control)
UNIT No.
R.C. No.
CODE No.
ON / OFF
4
1
6
FILTER RESET
DATA
SET
SETTING
TEMP.
TIMER SET
TIME
TEST
SET CL
2
3
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line. When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated.
1 Push and hold the TIME and buttons
at the same time for more than 4 seconds. At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display. (Select an outdoor unit.)
2 Push the (left side of the button) and
3 Push the button to confirm the system
4 Push the button (left side of the
buttons repeatedly to select a system
address.
address selection.
• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its fan and louvers are activated.
button). Each time you push the button, the indoor unit numbers of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
5
TEST
• To select another system address
5 Push the CL button to return to step 2.
• After returning to step 2, select another system
address and check the indoor unit addresses of the line.
6 Push the button to finish the procedure.
Changing the indoor unit
address using a remote controller
To change an indoor unit address using a wired remote controller.
The method to change the address of an
individual indoor unit (the indoor unit is paired with a wired remote controller one-to-one), or an indoor unit in a group. (The method is available when the addresses have already been set automatically.)
UNIT No.
R.C. No.
CODE No.
ON / OFF
4
3 5
FILTER RESET
DATA
SET
SETTING
TEMP.
TIMER SET
TIME
SET CL
TEST
8
1
(Execute it while the units are stopped.)
1 Push and hold the , , and buttons at
the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)
2 Push the button (left side of the
button) repeatedly to select an indoor unit number to change if 2 or more units are controlled in a group. (The fan and louvers
2, 6, 7
of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
53-EN 54-EN
3 Push the TEMP. / buttons
repeatedly to select for CODE No.
4 Push the TIME / buttons repeatedly to
NOTE
SET
TEST
3
1
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
2
Cancels the line selection
CL
TEST
4 8
5, 7
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
6
Press to finish setting.
Finish
SET
change the value indicated in the SET DATA section to that you want.
5 Push the button. 6 Push the button (left side of the
button) repeatedly to select another indoor UNIT No. to change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the button (left side of the
button) to check the changed addresses.
8 If the addresses have been changed
correctly, push the button to finish the procedure.
To change all the indoor unit addresses using
an arbitrary wired remote controller. (The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check / change mode and change
the addresses.
If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line following
2.
step
(Execute it while the units are stopped.)
1 Push and hold the TIME and buttons
at the same time for more than 4 seconds. At first, the line 1 and CODE No.
4 Push the TIME / buttons repeatedly to
change the value of the indoor unit address in SET DATA. Change the value in SET DATA to that of a new address.
5 Push the button to confirm the new
SET
address on SET DATA.
6 Push the button (left side of the
button) repeatedly to select another address to change. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the button.
(All the segments on the LCD display light up.)
8 Push the button to finish the procedure.
TEST
Resetting the address
(Resetting to the factory default (address undecided))
Method 1
Clearing each address separately using a wired remote controller. Set the system address, indoor unit address and group address to “0099” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.
1 Turn off the refrigerant line to reset to the
factory default and set the header outdoor unit of the line as below.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals. (Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface P.C. board of the header outdoor unit if the switch is OFF. (Leave it as it is if it has already been set to ON.)
(Address Change) are indicated on the LCD display.
2 Push (left side of the button) and
SWING/FIX
buttons repeatedly to select a system
address.
3 Push the button.
• The address of one of the indoor units
55-EN 56-EN
SET
connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated. At first, the current indoor unit address is displayed in (No system address is indicated.)
SET DATA.
–28–
–29–
NOTE
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2
U1U3U2
U4
U5 U6
U1 U2
A B
Central control controller
Header unit
Follower unit
Follower unit
Remote controller
Remote controller
Remote controller
Remote controller
Indoor units to have their addresses initialized
Header unit
Header unit
Remote controller
FS unit
Control wiring between indoor unit and FS unit (Within 15 m)
Group control
Piping
Indoor unit
Piping
FS unit
Piping
FS unit
Control wiring between indoor unit and FS unit
Remote controller
Group control
Indoor unit
NG
FS unit
Piping
Control wiring between indoor unit and FS unit
Remote controller
Indoor unit
NG
5 4
2
3
1
.
VENT
TEST
2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the
addresses. About one minute after turning on the power, confirm that the 7-segment display on the header outdoor unit indicates “U.1. - - -” and operate the interface P.C. board on the header outdoor unit of the refrigerant line as follows.
SW01 SW02 SW03 SW04 Clearable addresses
212
222
Confirm that the 7-segment display indicates “A.d.buS” and turn SW04 ON for more than five seconds.
Confirm that the 7-segment display indicates “A.d.nEt” and turn SW04 O N for more than five seconds.
System / indoor unit / group address
Central control address
3 Confirm that the 7-segment display indicates “A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
4 After a time “U.1.L08” appears on the 7-segment display if the address clearing has been
completed successfully. If the 7-segment display indicates “A.d. n.G.”, the outdoor unit may still connected with other refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
Setting when connecting
multiple indoor units to a FS (Flow Selector) unit
Cautions to connection of indoor unit
• When connecting the multiple indoor units to a single
FS unit, it is necessary to set up the CODE No.. Be sure to set up the CODE No. after setup of address.
• When connecting the multiple indoor units to a single
FS unit, only group control is available. For the indoor unit, a remote controller cannot be individually connected.
• FS unit must be connected to one of the multiple
indoor units which is under group control of a remote controller. The distance between FS unit and the indoor unit must be within 15 m.
Incorrect example of connection
How to set up CODE No.
1 Push + buttons simultaneously
for 4 seconds or more.
is displayed in the UNIT No. window.
• In this time, the fans of all the indoor units in the group control start the fan operation.
2 Using the set temperature buttons /
, select the CODE No. “ ”.
3 Change SET DATA to “ ” by the timer
buttons / .
4 Push button. 5 Push button. Then the setup finished.
SET
TEST
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
5 Set the addresses again after finishing the clearance.
57-EN 58-EN
10How to set up the cooling only indoor unit
CAUTION
No.
1
3
5 2
4
6
SETTING
DATA
SET
SET
CL
TEST
TEST
CODE No.
UNIT No.
SETTING
R.C. No.
SETTING
DATA
SET
Select an indoor unit of which setting is to be changed.
SET
CL
TEST
TEST
When setting the specific indoor unit to Cooling Only unit without connecting to the flow selector unit, setup to the indoor unit to become the Cooling Only unit is necessary. Perform setup in the following procedure.
Setup to the indoor unit is performed by handling the wired remote controller. Even if a wired remote controller is not used, attach a wired remote controller for setup. Change the setup with the wired remote controller before using the air conditioner with a wireless remote controller. Change the setup during stop of the operation. (Be sure to stop operation of the air conditioner.)
1 When pushing + + buttons
TEST
simultaneously for 4 seconds or more, after a while, the display part flashes as shown in the figure.
Check that the displayed CODE No. is [10].
• If the CODE No. indicates one other than [10], push button to erase the display, and then retry the operation from the first step. (After pushing button, the operation of remote controller cannot be accepted after a while.)
2 In a group control, the firstly displayed
indoor unit No. becomes the header unit.
Every pushing button (left side of the button), the indoor unit No. in the group control is displayed successively.
DATA
SET
SETTING
SETTING
UNIT No.
R.C. No.
In this time, the position of the indoor unit of which setup is to be changed can be confirmed because the fan and louver of the selected indoor unit work.
CODE No.
3 Use and buttons of the set
temperature to specify the CODE No. [0F].
4 Use and buttons of the timer time to
select the setup data [0001].
SET DATA 0000 0001
Cooling Only
setup
Heat pump Cooling Only
5 Push button. In this time, if the display
changes from flashing to lighting, the setup completes.
• To change the setup of an indoor unit other than the selected one, start operation from Procedure
• In a group control, setup change of all the indoor units in a group is necessary. To change the setup of the set other than the selected one, start again operation from Procedure
Cooling Only and Heat pump cannot exist in the same group.
2.
2.
6 When the setup finished, push button.
(The setup is determined.)
TEST
Pushing button deletes the display and returns to normal stop status. (For some time after button has been pushed, the operation of the remote controller cannot be accepted.)
• Pushing button clears the set up contents which have been already set.
(* The display changes according to the indoor unit model.)
59-EN 60-EN
In this case, retry from Procedure 2.
–30–
–31–
CAUTION
CAUTION
NOTE
1, 5
3
2, 4
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
TEST
TEST
ON / OFF
MODE
TEST
ON / OFF
TEST
NOTE
[A]
[U1]
[B]
[ ]
7-segment display
[B]
[ ]
[A]
[ ]
7-segment display
Address display of the corresponding indoor unit
[B]
[ ]
[A]
[ ]

7-segment display
Address display of the corresponding indoor unit
[FF] is displayed for 5 seconds.
[A]
[U1]
[B]
[ ]
7-segment display
11Test run
Before test run
Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN.
• Before turning on the power, confirm that the resistance between the terminal block of power supply and the earth is more than 1 MΩ using a 500 V megohmmeter. Do not run the unit if it is less than 1 MΩ.
• Turn on the power and turn on the case heater of the compressor. To save the compressor when it is activated, leave the power on for more than 12 hours.
Methods of test run
When executing a test run using a remote controller
Operate the system normally to check the running condition using the wired remote controller. Follow the instructions in the supplied owner’s manual when operating the unit. If you use a wireless remote controller for operations, follow the instructions in the installation manual supplied with the indoor unit. To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the indoor temperature, follow the procedure below. The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to normal running.
1 Push and hold the button for more than 4
seconds. TEST appears on the LCD display and the unit enters the trial mode. (TEST is indicated on the LCD display during the test run.)
2 Push the button. 3 Push the button to switch the running
mode to COOL or HEAT.
• Do not run the unit in any mode other than COOL or HEAT.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
When executing a test run using the interface P.C. board on the outdoor unit
You can execute a test run by operating switches on the interface P.C. board of the header outdoor unit. “Individual trial”, which tests each indoor unit separately, and “corrective trial”, which tests all the indoor units connected, are available.
<Individual test operation>
Starting operation
1 Set the running mode to “COOL” or “HEAT”
on the remote controller of the indoor unit to be tested. (The unit will run in the current mode unless you set the mode otherwise.)
2 Set the rotary switches on the interface P.C.
board of the header outdoor unit: SW01 to [16], SW02 and SW03 to the address of the indoor unit to be tested.
SW02 SW03 Indoor unit address
1 to 16 1 1 to 16 Set number of SW02
1 to 16 2 17 to 32 Set number of SW02 + 16
1 to 16 3 33 to 48 Set number of SW02 + 32
• The running mode follows the mode setting on the remote controller of the target indoor unit.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Finishing operation
1 Set the rotary switches on the interface P.C.
board of the header unit back: SW01 to [1], SW02 to [1] and SW03 to [1].
Do not use forcible running except for a test run as it overloads the unit.
4 Push the button to stop running
after finishing the trial run. The indication on the LCD display returns to the status of procedure 1.
3 Push and hold SW04 for more than 10
seconds.
5 Push the button to exit the trial mode.
(TEST disappears on the LCD display and
61-EN 62-EN
the status changes to normal stopped mode.)
<Corrective trial>
NOTE
[A] [C ] [H ]
[B] [ ] [ ]
[F ] [ ]
7-segment display
[A] [C ] [H ]
[B] [ - C ] [ - H ]
[F ] [ - F ]
7-segment display
[A]
[U1]
[B]
[ ]
7-segment display
SW04
SW01 SW02
SW03
D600 D601 D602 D603 D604
SW05 SW15
Push switch
7-segment
display [A]
Push switch
7-segment display [B]
Rotary switches
Interface PC board
Start operation
1 Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1]. When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1]. When in “FAN” mode: SW01=[2], SW02=[9], SW03=[1].
2 Push and hold SW04 for more than 2 seconds.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Stop operation
1 Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
63-EN 64-EN
–32–
12Troubleshooting
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by checking the 7-segment display on the interface P.C. board. Use the function for various checks. Set every dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting value
SW01 SW02 SW03
1 1 1 Outdoor unit check code
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary
code for one second alternately.
Indication LED
A
B Check code display*
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Auxiliary code
E06 Number of indoor units which received normally Decrease of number of indoor units
E07 Indoor / outdoor communication circuit error
E08 Duplicated indoor addresses Duplication of indoor addresses.
01: Communication between indoor and outdoor units
E12
02: Communication between outdoor units
E15 No indoor unit during automatic addressing
00: Capacity over
E16
01~: Number of connected units
00: Header is nothing
E19
02: 2 or more header units
01: Other line outdoor connected
E20
02: Other line indoor connected
E23 Sending error between outdoor units communication
E25 Duplicated follower outdoor address set up
E26 Number of outdoor units which received normally Decrease of connected outdoor units
E28 Detected outdoor unit number Follower outdoor unit error
E31 IPDU quantity information
E31 80 Communication error between MCU and sub MCU
F04 TD1 sensor error
F05 TD2 sensor error
01: TE1 sensor
F06
02: TE2 sensor
F07 TL sensor error
F08 TO sensor error
01: TS1 sensor
F12
02: TS2 sensor
(*1)
Automatic addressing start error
Capacity over / number of connected indoor units
Number of header outdoor unit error
Other lines connected during automatic addressing
IPDU communication error
TE1 sensor error TE2 sensor error
TS1 sensor error TS2 sensor error
D600
AB
Outdoor unit number
Check code nameIndication on 7-segment display on the outdoor unit
D601 D602 D603 D604
(U
1 to U3)
–33–
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
01: Compressor 1
F13
02: Compressor 2 03: Compressor 3
F15
F16
F22 TD3 sensor error
F23 Ps sensor error
F24 Pd sensor error
F31 Outdoor EEPROM error
01: Compressor 1
H01
02: Compressor 2 03: Compressor 3
01: Compressor 1
H02
02: Compressor 2 03: Compressor 3
01: Compressor 1
H03
02: Compressor 2 03: Compressor 3
H05 TD1 sensor miswiring
H06 Low pressure protective operation
H07 Detected outdoor unit number
01: TK1 sensor error 02: TK2 sensor error
H08
03: TK3 sensor error 04: TK4 sensor error 05: TK5 sensor error
H15 TD2 sensor miswiring
01: TK1 oil circuit error 02: TK2 oil circuit error
H16
03: TK3 oil circuit error 04: TK4 oil circuit error 05: TK5 oil circuit error
H25 TD3 sensor miswiring
L02 Mismatch of the indoor unit and outdoor unit model
L04 Outdoor system address duplication
L06 Number of prior indoor units Duplication of indoor units with priority
L08 Indoor unit group / address unset
L10 Outdoor unit capacity unset.
L17 Mismatch of the outdoor unit model
L18 Detected indoor unit address Flow selector unit error
L28 Outdoor connected quantity over
L29 IPDU number information
L30 Detected indoor unit address External interlock of indoor unit
L31 Other compressor errors
P03 Discharge temperature TD1 error
(*1)
TH (Heat sink) sensor error
Outdoor temp. sensor miswiring Outdoor pressure sensor miswiring (TE1, TL)
Outdoor temp. sensor miswiring Outdoor pressure sensor miswiring (Pd, Ps)
Compressor breaking down
Compressor error (Locked)
Current detection circuit error
Oil level down detection (Indicated only on the header outdoor unit)
Temperature sensor error for oil level
Oil level detector circuit error
IPDU quantity error
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
01: Compressor 1
P04
02: Compressor 2 03: Compressor 3
00: Phase missing / power failure detection
01: Compressor 1
P05
02: Compressor 2 03: Compressor 3
01: Compressor 1
P07
02: Compressor 2 03: Compressor 3
P10 Detected indoor unit address Indoor overflow error
P13 Outdoor unit flow back error detected
01: TS condition
P15
02: TD condition
P17 Discharge temperature TD2 error
P18 Discharge temperature TD3 error
P19 Detected outdoor unit number 4-way valve inverse error
P20 High-pressure protective operation
0 *: IGBT circuit 1 *: Position detection circuit error 3 *: Motor lock error 4 *: Motor current detected
P22
C *: TH sensor temperature error D *: TH sensor error E *: Inverter DC voltage error
(outdoor unit’s fan)
01: Compressor 1
P26
02: Compressor 2 03: Compressor 3
01: Compressor 1
P29
02: Compressor 2 03: Compressor 3
*1PDU number information
01:Compressor 1 02:Compressor 2 03:Compressors 1 and 2 04:Compressor 3 05:Compressors 1 and 3 06:Compressors 2 and 3 07:Compressors 1, 2 and 3 08:Fan 09:Compressor 1 and fan 0A:Compressor 2 and fan 0B:Compressors 1, 2 and fan 0C:Compressor 3 and fan 0D:Compressors 1, 3 and fan 0E:Compressors 2, 3 and fan 0F:Compressors 1, 2, 3, and fan
High-pressure SW system operation
Inverter DC voltage error (on compressor)
Heat sink overheat error
Gas leak detection
Outdoor fan IPDU error
(NOTE)
Ignore 0-F appearing in the position of “*”.
G-TR short protection error
Compressor position detecting circuit error
65-EN 66-EN
13Machine card and logbook
Machine card
After test run, fill the items on the machine card and paste the card on an accessible place on the product securely before delivery to the customer.
Describe the following items on the machine card:
name, address and telephone number of the installer, his service department, the service department of the party concerned or at any addresses and telephone numbers of fire department, police, hospitals and burn centres;
Logbook
Update the log periodically after maintenance as defined in EN378-4.
Describe the following items on the logbook:
1. details of the maintenance and repair works;
2. quantities, kind of (new, reused, recycled) refrigerant which have been charged on each occasion, the quantities of refrigerant which have been transferred from the system on each occasion (see also EN378-4);
3. if there is an analysis of a reused refrigerant, the results shall be kept in the logbook;
4. source of the reused refrigerant;
5. changes and replacements of components of the system;
6. result of all periodic routine tests;
7. significant periods of non-use.
67-EN 68-EN
–34–
Warnings on Refrigerant Leakage
e.g., charged amount (10 kg)
e.g., charged amount (15 kg)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
Important
Refrigerant piping
Indoor unit
Outdoor unit
Outdoor unit
Very small room
Refrigerant piping
Indoor unit
Mechanical ventilation device - Gas leak detector
Small room
Medium room
Large room
0
5
10
10 20 30
15
20
25
30
35
40
m
2
kg
Min. indoor floor area
Range above the density limit of 0.3 kg/m
3
(countermeasures needed)
Range below the density limit of
0.3 kg/m
3
(countermeasures not needed)
Total amount of refrigerant
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device.The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
Concentration limit (kg/m
The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m
NOTE 1
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
3
3
)
)
3
.
–35–
2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15 % or larger than the respective floor spaces at the top or bottom of the door).
3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
NOTE 3
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7 m high)
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg.
69-EN 70-EN
The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
NOTE 2
The standards for minimum room volume are as follows.
1) No partition (shaded portion)
EH99889397
Loading...