1. Read this manual before installing or operating. Keep this instruction manual on hand
of the end user, and make use of this manual in maintenance and inspection.
2. All information contained in this manual will be changed without notice. Please
contact your Toshiba distributor to confirm the latest information.
NOTICE
E6581741
Introduction
Thank you for purchasing the “EtherNet/IP™ - Modbus® TCP option (IPE002Z)” for
TOSVERT VF-MB1/S15 inverter. Before using EtherNet/IP™ - Modbus
carefully read this function manual in order to completely and correctly utilize its excellent
performance.
This option needs the option adaptor to connect VF-S15 which type form is SBP009Z.
Please match here and buy it when SBP009Z is not at hand yet.
After reading this function manual, please keep it handy for future reference.
For details of its general handling, see an instruction manual attached with the option
unit.
- TOSVERT VF-MB1/S15 communication option Precautions Manual···········E6581739
- TOSVERT VF-MB1 Communication Function Instruction Manual················ E6581726
- TOSVERT VF-S15 Communication Function Instruction Manual················· E6581913
EtherNet/IP™ is a trademark of ControlNet International, Ltd.
Modbus
Handling in general
Prohibited
Do not connect or disconnect a network cable while the Inverter power is on.
It may lead to electric shocks or fire.
®
TCP module,
®
TCP is a registered trademark of AEG Schneider Automation International S.A.S.
Warning
Mandatory
Network control
Prohibited
Mandatory
Mandatory
See the instruction manual attached with the option unit for cautions the handling.
Otherwise, it may lead to electric shocks, fire, injuries or damage to product.
Warning
Do not send the value out of the valid range to objects and attributes.
Otherwise, the motor may suddenly start/stop and that may result in injuries.
Use an additional safety device with your system to prevent a serious accident due to the
network malfunctions. Usage without an additional safety device may cause an accident.
Caution
Set up “Communication error trip function (see below)” to stop the Inverter when the
option unit is deactivated by an unusual event such as tripping, an operating error,
power outage, failure, etc.
- Network Time-Out, Inverter operation at disconnection, Preset speed operation
selection
(Refer to " 3.2.3 Network error detection (c100 - c103, c523)" for details)
Deactivated the option module may cause an accident, if the “Communication error trip
function” is not properly set up.
Make sure that the operation signals are STOP before resetting Inverter’s fault. The
motor may suddenly start and that may result in injuries.
Notes on operation
Notes
When the control power is shut off by the instantaneous power failure, communication
will be unavailable for a while.
The Life of EEPROM is approximately 100,000 times. Avoid writing a command more
than 100,000 times to the same parameter of the Inverter and the option module.
2.3. Example of connection to an EtherNet/IP™ and Modbus® TCP .........................................................5
2.4. LED indicator........................................................................................................................................6
5.1.11. Instance 105: TOSHIBA specific output..................................................................................52
5.1.12. Instance 155: TOSHIBA specific input....................................................................................52
6. ABOUT EDS FILE ....................................................................................................................................54
7. INTEGRATION IN RSLOGIX™................................................................................................................54
7.1. Create a new project ..........................................................................................................................54
7.2. Add a EtherNet/IP scanner to the I/O configuration...........................................................................55
7.3. Configure the VF-MB1/S15 EtherNet/IP module ...............................................................................57
7.4. Download the program to the PLC.....................................................................................................59
7.5. Edit the I/O scan data.........................................................................................................................61
8. MODBUS TCP SERVER ..........................................................................................................................64
8.8. "43 (0x2B) Read Device identification" function ................................................................................69
8.9. Parameter data ..................................................................................................................................71
The EtherNet/IP™ - Modbus® TCP option (IPE002Z) allows the VF-MB1/S15 inverter to be connected
into the EtherNet/IP™ - Modbus
®
TCP network.
2. Names and functions
The drawing below shows names and functions of main parts.
2.1. Outline
MAC address Label
(Back side)
Release tab
Connector to the inverter
MS
LNK
(Port L)
LED indicator (See 2.4)
Shielded female RJ45
EtherNet/IP Connector
NS
LNK
Shielded female RJ45
EtherNet/IP Connector
(Port R)
- 4 -
E6581741
2.2. RJ45 connector pin layout
The EtherNet/IP™ - Modbus® TCP option is equipped with two shielded RJ45
connectors.
When you use VF-MB1, the shielding is connected to the drive ground. When you use
VF-S15, the shielding is connected to the grounding terminal of option adapter.
Use an STP (shielded twisted pair) Ethernet cable.
The transmission speed is detected automatically by the unit (10 Mbps or 100 Mbps).
The card can operate in half duplex or full duplex mode, whether connected to a hub or a
switch and regardless of the transmission speed (10 Mbps or 100 Mbps).
Port L and Port R
8………………1
* Fix a cable so that a communication connector may be not taken the weight of wire.
Pin Signal
1 TD+
2 TD-
3 RD+
4 -
5 -
6 RD-
7 -
8 -
2.3. Example of connection to an EtherNet/IP™ and Modbus® TCP
Example of daisy chain topology and star topology
Daisy chain topology Star topology
PLC
Ethernet switch
- 5 -
E6581741
2.4. LED indicator
The LED shows the present
status of the network and module.
The behavior of LNK LED
Link Activity
Protocol Color and behavior Meaning
EtherNet/IP
&
Modbus TCP
The behavior of MS LED
Module Status
Protocol Color and behavior Meaning
EtherNet/IP
Modbus TCP
The behavior of NS LED
Network Status
Protocol Color and behavior Meaning
EtherNet/IP
Modbus TCP
OFF No link
Flashing Green/Red Power up testing
Green ON Link at 100Mbps
Yellow ON Link at 10Mbps
Green Blink Activity at 100Mbps
Yellow Blink Activity at 10Mbps
OFF No power is supplied to the device
Flashing Green/Red Power up testing
Green ON The option is operating correctly
Green flashing The option has not been configured
Red flashing The option has detected a recoverable minor fault
Red on The option has detected a non-recoverable major fault
OFF The option does not have an IP address or powered off
Flashing Green/Red Power up testing
Green ON The option is ready
Green flashing The option is not ready (waiting for cable connection or etc.)
Red flashing The option has detected a communication error (err8)
Red ON The option has detected a option module error (e-23)
OFF The option does not have IP address or powered off
Flashing Green/Red Power up testing
Green ON The option has at least one established connection
Green flashing The option does not have at least one established connection
Red flashing One or more of the connections in which this device is the target
has time out. This shall be left only if all time out connections are
re-established or if the device is reset
Red on Error: duplicate IP address
OFF The option does not have an IP address or powered off
Flashing Green/Red Power up testing
Green ON At least one port is connected and an IP address has been
obtained
Green flashing 3 times All ports are unplugged, but the card has an IP address
Green flashing 4 times Error: duplicate IP address
Green flashing 5 times The card is performing a BOOTP or DHCP sequence
MS
LNK
NS
LNK
- 6 -
E6581741
3. Parameters
3.1. Communication parameters
Set up the inverter parameters as follows. It is necessary to reset the inverter to update the parameter.
This option doesn't operate if these parameters are not correctly set.
Title
cmod 0003 Command mode selection
fmod 0004
f856 0856
f899 0899 Communication function reset
(*1): There selections are effective in only VF-S15.
(*2): The unit depends on the f519 setting.
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
Communi
cation No.
Communi
cation No.
Function Description
Frequency setting mode
selection 1
Number of motor pole pair for
communication
Function Description
0: Terminal board
1: Panel keypad (including remote keypad)
2: RS485 communication
3: CANopen communication
4: Communcation option
0: Setting dial 1 (save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2 (press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: 11: Pulse train input
12, 13: - (*1)
14: sr0 (*1)
1: 2 poles
2: 4 poles
3: 6 poles
4: 8 poles
5: 10 poles
6: 12 poles
7: 14 poles
8: 16 poles
0: 1: Reset (after execution: 0)
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
(*4): (V[R) does not work for this parameter.
Preset speed operation
selection
Communication time-out
condition selection
0: None
1 to 15: Preset speed
0: Disconnection detection
1: When communication mode enable (Both
cmod and fmod are set CANopen or
communication option) only
2: 1 + Driving operation
0
0
- 8 -
E6581741
Title
c500C500
c501C501
c502C502
c503 C503
c504C504
c505-
c508
c509-
c512
c513-
c516
c517-
c522
c523 C523 Time out
c524-
c527
c528-
c531
c532-
c535
Communi
cation No.
C505-
C508
C509-
C512
C513-
C516
C517-
C522
C524-
C527
C528-
C531
C532-
C535
Protocol (*3)
Rate Setting (*3)
Actual Rate (L port)
Actual Rate (R port)
IP mode (*3)
IP address (*3)
Subnet Mask (*3)
IP Gate (*3)
MAC address (*5)
IP address actual
IP Mask actual
IP Gate actual
Function Description
This parameter is used to set the protocol of the option
card.
0: Modbus TCP (default)
1: EtherNet/IP
This field is used to set the transmission speed and the
transmission mode of the card.
0: Autodetect(default)
1: 10Mbps Full
2: 10Mbps Half
3: 100Mbps Full
4: 100Mbps Half
This field displays the baud rate and the transmission
mode currently used by the communication card.
(Display only)
0: unconnected
1: 10Mbps Full
2: 10Mbps Half
3: 100Mbps Full
4: 100Mbps Half
Use this parameter to select the IP address assignment
method.
0: Manual
1: BOOTP
2: DHCP
Refer to "
The IP address of the option module.
3.2.2 Assigning IP addresses" for the details.
These fields are effective settings at c504 = 0.
Refer to "3.2.2 Assigning IP addresses" for the details.
The subnet mask of the option module.
These fields are effective settings at c504 = 0.
Refer to "3.2.2 Assigning IP addresses" for the details.
The gateway IP address of the option module.
These fields are effective settings at c504 = 0.
Refer to "3.2.2 Assigning IP addresses" for the details.
The MAC address of the option module.
[C517 - C518 - C519 - C520 - C521 - C522]
The waiting time from the occurrence of the
Factory
setting
0
0
-
0
0.0.0.0
0.0.0.0
0.0.0.0
----
2
network error to detection can be adjusted.
* When you are using unconnected
communication of the EtherNet/IP protocol, time
out is not detected.
0.0: Disable
0.5 - 60 sec.
The current IP address of the option module.
Refer to "
The subnet mask actual of the option module.
Refer to "
The gateway IP address actual of the option module.
Refer to "
3.2.2 Assigning IP addresses" for the details.
3.2.2 Assigning IP addresses" for the details.
3.2.2 Assigning IP addresses" for the details.
-
-
-
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
(*5): .These values are displayed by decimal number format on panel of VFMB1/S15.
- 9 -
E6581741
EtherNet/IP parameters
Title
c536 C536 EtherNet Error
c554 C554 Web service (*3)
c555 C555 Drive Status
Communi
cation No.
Function Description
Modbus TCP parameters
Title
c600-
c603
c604 C604 IO Scan active (*3)
Communi
cation No.
C600-
C603
Function Description
IP Master (*3) The IP address for PLC(Master) of the Modbus TCP.
Monitor of the EtherNet error.
0: No error/clear error
1: Modbus TCP IO Scanning timeout
2: Network overload
3: Loss of Ethernet carrier
Enables web server.
0: Disable
1: Enable
Monitor the inverter status.
3: Gate Block
4: Run
23: Fault
Enables IO Scan function.
0: Non-active
1: Active
Factory
setting
-
1
-
Factory
setting
0.0.0.0
0
(*3): This parameter is effective by reset. Please reset (power supply reset or f899=1) after changing a set point.
Warning
Mandatory
action
Set up “Communication error trip function (c100 to c103 and c523)” to stop the
inverter when EtherNet/IP™ - Modbus® TCP communication is deactivated.
When the parameters are changed, please reset (power supply reset or f899=1) the
inverter for the changes to take effect.
- 10 -
E6581741
3.2. The details of the parameter setting
3.2.1. Device name (c081-c096)
This option module can set the "Device name" of 16 characters.
(Device name (c081-c096) is 1 character within one parameter.)
The device name is required if the option module uses DHCP to obtain its IP Address.
Please set the setting of the device name according to the following rules.
1. The parameter is displayed by the hexadecimal number.
2. One parameter shows an ASCII character.
3. The relation between the device name and the parameter is as follows.
(*The IP Master address.- Modbus TCP protocol only)
These parameters are effective settings at c504 = 0 (IP mode: Manual).
If the address has been given by a BOOTP or a DHCP server, these parameters are
invalidity.
• After dynamic addressing by a BOOTP or DHCP server, the new address value is
displayed in the parameters. (c524-c535)
They can be provided by:
*BOOTP server (correspondence between the MAC address and the IP addresses).
*DHCP server (correspondence between Device Name and the IP addresses).
The address is assigned according to the IP mode parameter.
c504: IP mode Comments
0 The option uses the address defined in c505-c516.
1 The option receives its address from a BOOTP server.
2 The option receives its address from a DHCP server.
*Device name contains (c081-c096) a valid name.
Note: The IP mode parameter may be modified according to the configuration control
attribute of the TCP/IP interface object (CIP standard).
err8 (Optional unit fault 1: 1BH): Network error stop
▼Related parameter
Title Function Setting range Description
The waiting time from when a network error occurs
can be adjusted. If a network error continues past
the time set in c100, it is recognized as a
communication error and the operation of the
inverter follows the setting of c101.
When normal communication returns during the
setting time, a communication error is not displayed
and operation is continued.
c100
c101
c102
c103
c523 Time out
Communication error
detection delay time
Inverter operation at the
communications loss action
Preset speed operation
selection
Communication time-out
condition selection
0.0-100.0 sec
0-5
1-15
0-2
0.0: Disable
0.5 - 60 sec.
*The case of Modbus
The time-out detection time provides by c523
parameter.
Disconnection detection time =
The operation of the inverter when the
communication fault occurs can be specified.
The operation frequency of the inverter when the
communication fault occurs can be specified. (Only
when c101 is set to 5)
Select the communication time-out condition.
The waiting time from the occurrence of the
network error to detection can be adjusted.
* When you are using unconnected communication
of the EtherNet/IP protocol, time-out is not
detected.
®
TCP protocol
TM
protocol
[μs] + c100
- 13 -
E6581741
3.2.4. Command data (c001-c006), Monitor data (c021-c026)
The outline is indicated about the setting item of parameter c001 – c006 and
c021 – c026 in Instance 102/152 and 105/155 of use. Please refer to a
communication functional description for details.
3.2.4.1. How to use Instance 102/152 and 105/155
Instance 102/152 and 105/155 choose a command or the monitor of the driving state by a menu of c001
- c006 and c021 - c026 and can perform the communication that is cyclic of EtherNet/IP™ and
Modbus
Example 1: Command transmitting by output Instance 102
VF-MB1/S15
"0xC400" is set to parameter fa06
Example 2: State monitoring by the input instance 152.
VF-MB1/S15
The value of a parameter fd03 (0x1234)
is outputted.
®
TCP (ID = 255).
If the command value “c400” set to parameter fa06, Choose parameter fa06 (a communication
option command) for command data (c001=1 (fa06)).
For example, please set C400 in FA06 when you want to send the command from an EtherNet/IP™
option and the availability of the frequency order and a driving order. (Please refer to ” 3.2.4.2”)
IPE002Z
Parameter Value
c001 1 (fa06)
c002 ...
c003 ...
... ...
EtherNet/IP Master
Output Instance 102
Byte Value
0 00
1 C4
2 ...
3 ...
... ...
When you want to monitor the output current, set “3 (fd03)” to parameter c021.
The value of the parameter
fd03 specified as 0 and 1 byte of the input instance 152 with the parameter
c021 is inputted.
IPE002Z
Parameter Value
c021 3 (fd03)
c022 ...
c023 ...
... ...
EtherNet/IP Master
Input Instance 152
Byte Value
0 34
1 12
2 ...
3 ...
... ...
- 14 -
E6581741
3.2.4.2. fa06 (Communication command1)
bit Function 0 1 Note
Preset speed
0
operation frequencies
1
Preset speed
1
operation frequencies
2
Preset speed
2
operation frequencies
3
Preset speed
3
operation frequencies
4
Motor selection (1 or 2)
4
(THR 2 selection)
5 PI D control Normal operationPI D off -
Acceleration/deceleration pattern selection
6
(1 or 2)
(AD2 selection)
7 DC braking OFF
8 Jog run OFF Jog run -
Forward/reverse run
9
selection
10 Run/stop Stop Run 11 Coast stop command Standby Cost stop 12 Emergency stop OFF Emergency stop Always enable, "E" trip
13 Fault reset OFF Reset No data is returned from the drive
Frequency priority
14
selection
Command priority
15
selection
(*1): When 14(sr0) is set to fmod, preset speed operation frequency 0 is selected in using VFS15,.
0000: Preset speed operation OFF
(*1)
0001-1111: Setting of preset speed
operation frequencies (1-15)
Motor 1
(THR 1)
Acceleration/decel
eration pattern 1
(AD1)
Forward run Reverse run -
OFF Enabled
OFF Enabled
Motor 2
(THR 2)
Acceleration/dec
eleration pattern
2
(AD2)
Forced DC
braking
Preset speed operation is
disabled or preset speed
operation frequencies (1-15) are
set by specifying bits for preset
speed operation frequencies 1-4.
Select acceleration/deceleration
1-3 by combination of two bits..
AD1: acc, dec
AD2: f500, f501
AD3: f510, f511
OC stall 1: f601
OC stall 2: f185
- 16 -
E6581741
3.2.4.4. fa07 (frequency reference from internal option)
Frequency reference is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,
80 / 0.01 = 8000 = 0x1F40 (Hex.)
3.2.4.5. fa50 (Terminal output data from communication)
The output data on the terminal board can be directly controlled with the computer.
To use this function, select functions from 92 to 95 in advance for the output terminal selection
parameters f130, f131, f132. If bit 0 through bit1 of the data (fa50) is set with the computer,
the specified data (0 or 1) can be output to the selected output terminal.
Data composition of output data on the terminal board (FA50)
bit Output TB function name 0 1
0
1
2-15 (Reserved) - -
Specified data output 1
(Output terminal No.: 92, 93)
Specified data output 2
(Output terminal No.: 94, 95)
Note: Set 0 to reserved bit
Example of use: To control only the RY-RC terminal with the computer
To turn on the RY terminal, set the output terminal selection 1A parameter (f130) to 92
(Designated data output 1) and set 0001H to fa50.
BIT15 BIT0
FA50:
0 0 0 0 000000000001
OFF ON
OFF ON
0
0
0
1
3.2.4.6. fa51 (Analog output (FM) data from communication)
Use this function, set the FM terminal meter selection parameter (fmsl) to 18 (communication data
output).
This makes it possible to send out the data specified as FM analog output data (fa51) though the FM
analog output terminal. Data can be adjusted in a range of 0 to 1000 (resolution of 10 bit).
Please refer to "Meter setting and adjustment" Section of the inverter’s instruction manual.
- 17 -
E6581741
3.2.4.7. fd01 (Inverter operating status 1)
bit Function 0 1 Note
0 Failure FL No output
1 Failure Not tripped Tripped
2 Alarm No alarm Alarm issued 3 Under voltage (moff) Normal Under voltage -
Motor selection (1 or 2)
4
(THR 2 selection)
5 PID control off
Acceleration/deceleratio
6
n pattern selection (1 or
2)
7 DC braking OFF
8 Jog run OFF Jog run -
9 Forward / reverse run Forward run Reverse run 10 Run/stop Stop Run 11 Coast stop (ST = OFF) ST=ON ST=OFF -
12 Emergency stop
13 Standby ST=ON Start-up processStandby
14 Standby Start-up processStandby
15 (Reserved) Undefined -
Note: Don’t use the reserved bit for the judgment.
Motor 1 (THR1)Motor 2 (THR2)
PID control
permitted
Acceleration/dec
eleration pattern
1 (AD1)
No emergency
stop status
Under in
progress
PID control
prohibits
Acceleration/dec
eleration pattern
2 (AD2)
Forced DC
braking
Emergency
stop status
-
Trip status includes rtry and
the trip retention status are also
regarded as tripped statuses.
Standby: Initialization
completed, not failure stop
status, not alarm stop status
(moff, ll forced stop),
ST=ON, and RUN=ON
Standby: Initialization completed,
not failure stop status and not
alarm stop status (moff, ll
forced stop)
3.2.4.8. fd00 (Output frequency)
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
- fd22 (Feedback value of PID)............................................... Unit: 0.01Hz
The output current is read into 0.01% of units and by the hexadecimal number.
For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal
number) is read out.
Since the minimum unit is 0.01%,
0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)
Also about the following parameters, these are the same as this.
- fd05 (Output voltage (real time))............................................. Unit: 0.01% (V)
- fd04 (Voltage at DC bus (real time)) ....................................... Unit: 0.01% (V)
* When the motor information connected to the drive set to the parameter (f405 - f415), torque
monitor value "100%" is same as the rated torque of a motor in general.
3.2.4.10. fe35, fe36, fe37 (Monitoring of the analog input VIA, VIB, VIC)
VIA terminal board monitor: "Communication Number fe35"
VIB terminal board monitor: "Communication Number fe36"
VIC terminal board monitor: "Communication Number fe37"
These monitors can also be used as A/D converters irrespective of the drive's control.
VIA / VIC terminal board monitor is capable of reading the data from external devices in a range of 0.01
to 100.00% (unsigned data: 0x0000 to 0x2710).
VIB terminal board monitor is capable of reading the data from external devices in a range of -100.00 to
100.00% (signed data: 0xD8F0 to 0x2710).
If analog input mode is selected with the frequency setting mode selection parameter, however, keep in
mind that any data entered via an analog terminal is regarded as a frequency command.
3.2.4.11. fe14 (Cumulative run time)
The operated cumulative time is read by the hexadecimal number.
For example, when cumulative operation time is 18 hours, 0x0012 (18 hours) is read.
0x0012 = 18 (Dec., hour)
3.2.4.12. fe40 (Analog output (FM))
The output value of FM terminal is read.
The value range is set to 0 to 10000 (0x0000 to 2710H) which is corresponded to 0.00% to 100.00%.
For example, when analog output is 50.00%, 0x1388 is read.
0x1388 = 50.00(Dec., %)
- 19 -
E6581741
3.2.4.13. fc91 (Alarm code)
Remarks
bit
0 Over-current alarmNormal Alarming c flicking
1 Inverter over load alarmNormal Alarming l flicking
2 Motor over load alarmNormal Alarming l flicking
3 Over heat alarmNormal Alarming h flicking
4 Over voltage alarmNormal Alarming p flicking
5 Main circuit undervoltage alarmNormal Alarming -
6 main device overheat alarmNormal Alarming l flicking
7 Under current alarmNormal Alarming -
8 Over-torque alarmNormal Alarming -
9 Braking resistor overload alarmNormal Alarming 10 Cumulative operation hours alarmNormal Alarming 11 Option communication alarmNormal Alarming 12 Serial communication alarmNormal Alarming 13 MOFFMS (MSrelay off or MOFF)Normal Alarming -
14 Stop after instantaneous power off-
15 Stop after LL continuance time-
Function 0 1
Dec., Under
(Code displayed on
the panel)
Refer to f302
stop
Dec., Under
Refer to f256
stop
value
value
3.2.4.14. fd06 (Input TB Status)
bit TB Name Function (Parameter) 0 1
0 F Input terminal function selection 1 (f111)
1 R Input terminal function selection 2 (f112)
2 RES Input terminal function selection 3 (f113)
3 S1 Input terminal function selection 4 (f114)
4 S2 Input terminal function selection 5 (f115)
5 S3 Input terminal function selection 6 (f116)
6 VIB*1 Input terminal function selection 7 (f117)
7 VIA*1 Input terminal function selection 8 (f118)
5 to 15 (Reserved) - Undefined
Note: Don't use the reserved bit for the judgment.
*1: VIA/ VIB are input terminal function when f109 is logic input.
*The input terminal function is selected by each parameter.
Example: Data set for FE06 when the F and RES terminals are ON = 0005H
BIT15 BIT0
FE06:
0 0 0 0 000000000101
0
0
0
5
OFF ON
- 20 -
E6581741
3.2.4.15. fd07 (Output TB Status)
bit TB Name Function (Parameter) 0 1
0 RY-RC Output terminal function selection 1A (f130)OFF ON
1 OUT Output TB Function select 2A (f131) OFF ON
2 FL Output TB Function select 3 (f132) OFF ON
3 - 15 (Reserved)- Undefined
Note: Don't use the reserved bit for the judgment.
Example: Data set for FE07 when the RY and FL terminals are ON = 0005H
BIT15 BIT0
FE07:
0 0 0 0 000000000101
0
0
0
5
- 21 -
4. Objects
E6581741
This section contains the object specifications for all EtherNet/IP objects currently
supported by the “IPE002Z”. Table 1 outlines those objects covered:
Class Code
Hex. Dec.
0x01 1 Identity Object
0x02 2 Message Router Object
0x04 4 Assembly Object
0x06 6 Connection Manager Object
0x28 40 Motor Data Object
0x29 41 Control Supervisor Object
For definitions of all data types referred to in these object specifications, refer to the
ODVA EtherNet/IP™ Specifications. In general, however, the following are some of the
most prevalent types:
BOOL .......................... Boolean 0(False) or 1(TRUE)
SINT............................ Signed Short Integer -128 to 127
INT ..............................Integer -32768 to 32767
USINT .........................Unsigned Short Integer 0 to 255
UINT............................ Unsigned Integer 0 to 65535
UDINT .........................Unsigned Double Integer 0 to 2
STRING ......................character string (1 byte per character)
SHORT_STRING........ character string (1 byte per character, 1 byte length indicator)
BYTE........................... Bit string - 8-bits
WORD......................... Bit string - 16-bits
DWORD ......................Bit string - 32-bits
EPATH ........................ CIP path segments
Object Class Page
23
25
26
27
28
29
32
33
35
36
37
39
31
to 231-1
32
-1
- 22 -
E6581741
4.1. Identity Object (0x01)
Class code 0x01.
This object provides identification of and general information about the device.
Class Attributes
Instance Attribute ID Access Name Data type Details Value
1 Get Revision UINT Revision of this object 1
2 Get Max Instances UINT Maximum instance number of an
object currently created in this class
level of the device.
3 Get Number of Instances UINT Number of object instances currently
created at this class level of the
device.
4 Get
0
6 Get Max ID of class
7 Get Max ID of instance
Optional attribute list STRUCT
of
Number of attributes UNIT Number of attribute in the optional
Optional attributes ARRAY of
UNIT
UINT The attribute ID number of the last
attributes
UINT The attribute ID number of the last
attribute
List of optional instance attributes
utilized in an object class
implementation.
attribute list.
List of optional attribute numbers. -
class attribute of the class definition
implemented in the device.
instance attribute of the class
definition implemented in the device.
Class Service
Service Code Service Name Description of Service
0x01 Get_Attribute_All Read all attributes
0x0E Get_Attribute_Single Read one attribute
Instance Attributes
Instance Attribute ID Access Name Data type Details Value
1 Get Vendor ID UINT
2 Get Device type UINT AC/DC Drive profile 2
3 Get Product code UINT
4 Get
1
5 Get Status WORD See “Attribute 5 State Description”*
6 Get Serial number UDINT 4 last bytes of MAC Address 7 Get Product name SHOT_
Revision STRUCT
of
Major revision USINT Major revision of drive 1 (*1)
Minor revision USINT Minor revision of drive 8 (*1)
STRING
Identification of vendor by number
Identification No. of a drive
(case of VF-MB1) 32000
(case of VF-S15) 32001
Revision of the item the Identity
Object represents
Human readable identification
(case of VF-MB1 drive) 6,
(case of VF-S15 drive) 6,
*1: These values depend on firmware version and revision.
Instance Services
Service Code Service Name Description of Service
0x01 Get_Attribute_All Read all attributes
0x05 Reset Invokes the Reset for the device
0x0E Get_Attribute_Single Read one attribute
1
1
0
-
7
7
377
VF-MB1
VF-S15
- 23 -
E6581741
Attribute 5 State Descriptions
Adapted from document [CIP] “
THE CIP NETWORKS LIBRARY”
Bit Called Definition
TRUE indicates the device (or an object within the device) has an owner.
Within the Master/Slave paradigm the setting of this bit means that the
0 Owned
Predefined Master/Slave Connection Set has been allocated to a master.
Outside the Master/Slave paradigm the meaning of this bit is TBD.
Æ unsupporteed
1 - (System reserved)
TRUE indicates the application of the device has been configured to do
2 Configured.
something different than the “out–of–box” default. This shall not include
configuration of the communications.
3 - (System reserved)
0000 Self-Testing or unknown
0001 Firmware update in progress
0010 At least one faulted I/O connection
0011 No I/O connections established
Extended Device
4-7
Status
0100 Non-Volatile configuration bad
0101 Major Fault – either bit 10 or bit 11 is true (1)
0110 At least one I/O connection in run mode
0111 At least one I/O connection established, all in idle mode
1000-
Unused
1111
Minor Recoverable
8
Fault
Minor
9
Unrecoverable
Fault.
Major Recoverable
10
Fault.
Major
11
Unrecoverable Fault
TRUE indicates the device detected a problem with itself, which is thought to
be recoverable. The problem does not cause the device to go into one of the
faulted states.
TRUE indicates the device detected a problem with itself, which is thought to
be unrecoverable. The problem does not cause the device to go into one of
the faulted states.
TRUE indicates the device detected a problem with itself, which caused the
device to go into the “Major Recoverable Fault” state.
TRUE indicates the device detected a problem with itself, which caused the
device to go into the “Major Unrecoverable Fault” state.
12-15 - (System reserved)
Note: Don’t use the “System reserved” bit and Bit0 for the judgement.
- 24 -
E6581741
4.2. Message Router Object (0x02)
Class code 0x02.
The Message Router Object provides a messaging connection point through which a Client may
address a service to any object class or instance residing in the physical device.
Class Attributes
Instance Attribute ID Access Name Data type Details Value
1 Get Revision UINT Revision of this object 1
2 Get Max Instances UINT Maximum instance number of an
object currently created in this class
level of the device.
3 Get Number of Instances UINT Number of object instances currently
created at this class level of the
device.
4 Get
0
6 Get Max ID of class
7 Get Max ID of instance
Optional attribute list STRUCT
of
Number of attributes UNIT Number of attribute in the optional
Optional attributes ARRAY of
UNIT
UINT The attribute ID number of the last
attributes
UINT The attribute ID number of the last
attribute
List of optional instance attributes
utilized in an object class
implementation.
attribute list.
List of optional attribute numbers. 3
class attribute of the class definition
implemented in the device.
instance attribute of the class
definition implemented in the device.
Class Service
Service Code Service Name Description of Service
0x0E Get_Attribute_Single Read one attribute
Instance Attribute
Instance Attribute ID Access Name Data type Details Value
2 Get Number Available UNIT
1
3 Get Number active UNIT Number of connections currently
Maximum number of connections
supported
used by system components
Instance Services
Service Code Service Name Description of Service
0x0E Get_Attribute_Single Read one attribute
1
1
2
2
7
3
16
0
- 25 -
E6581741
4.3. Assembly Object (0x04)
Class code 0x04.
The Assembly Object binds attributes of multiple objects, which allows data to or from each object to
be sent or received over a single connection. Assembly objects can be used to bind input data or
output data. The terms ”input” and ”output” are defined from the network’s point of view. An input will
produce data on the network and an output will consume data from the network
Class Attributes
Instance Attribute ID Access Name Data type Details Value
1 Get Revision UINT Revision of this object 2
2 Get Max Instances UINT Maximum instance number of an
object currently created in this class
level of the device.
3 Get Number of Instances UINT Number of object instances currently
0
6 Get Max ID of class
attributes
7 Get Max ID of instance
attribute
UINT The attribute ID number of the last
UINT The attribute ID number of the last
created at this class level of the
device.
class attribute of the class definition
implemented in the device.
instance attribute of the class
definition implemented in the device.
Class Service
Service Code Service Name Description of Service
0x0E Get_Attribute_Single Read one attribute
Instance Attribute
Instance Attribute ID Access Name Details
See below
3 Get/Set* Data Settable Only on Output Assembly.
See below
See below
4 Get Size Number of bytes in Attribute 3.
199
13
7
4
Output Assembly:
Instance Type Size Page
20 CIP basic speed control output 2 words (4 bytes) 45
21 CIP extended speed control output 2 words (4 bytes) 46
100 Native drive output 2 to 8 words (4 to 16 bytes) 47
101 Native drive output 4 words (8 bytes) 49
102 Native drive output 6 words (12 bytes) 51
105 TOSHIBA specific output 9 words (18 bytes) 52
Input Assembly:
Instance Type Size Page
70 CIP basic speed control input 2 words (4 bytes) 45
71 CIP extended speed control input 2 words (4 bytes) 46
150 Native drive input 2 to 8 words (4 to 16 bytes) 47
151 Native drive input 4 words (8 bytes) 49
152 Native drive input 6 words (12 bytes) 51
155 TOSHIBA specific output 9 words (18 bytes) 52
Instance Services
Service Code Service Name Description of Service
0x0E Get_Attribute_Single Read one attribute
0x10 Set_Attribute_Single Write one attribute
- 26 -
Loading...
+ 62 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.