Please read this Installation Manual carefully before installing the Air to Water Heat Pump.
• This Manual describes the installation method of the hydro unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
Installation Manual
ADOPTION OF NEW REFRIGERANT
This Air to Water Heat Pump is a new type which adopts a new refrigerant HFC (R410A) instead of the
conventional refrigerant R22 in order to prevent destruction of the ozone layer.
HWS-802XWHM3-E8 kW Hydro Unit (3 kW 230 V ~ back up heater)
HWS-802XWHT6-E8 kW Hydro Unit (6 kW 400 V 3N ~ back up heater)
HWS-1402XWHM3-E11 & 14 kW Hydro Unit (3 kW 230 V ~ back up heater)
HWS-1402XWHT6-E11 & 14 kW Hydro Unit (6 kW 400 V 3N ~ back up heater)
HWS-1402XWHT9-E11 & 14 kW Hydro Unit (9 kW 400 V 3N ~ back up heater)
General Specifications
Outdoor unitHWS-802H-EHWS-1102H-EHWS-1402H-E
TypeInverter
FunctionHeating & Cooling
Capacity(kW)8.011.214.0
Heating
Cooling
Power supply230 V ~
RefrigerantR410A
DimensionHxWxD(mm)890 x 900 x 3201,340 x 900 x 320
Input(kW)1.962.403.15
COP4.084.664.45
Capacity(kW)6.010.011.0
Input(kW)2.133.524.08
EER2.822.842.69
Installation Manual
Hydro Unit
Back up heater capacity3 kW6 kW3 kW6 kW9 kW
for backup heater230 V ~400 V 3N ~230 V ~400 V 3N ~400 V 3N ~
Power supply
Leaving water
temperature
For use withHWS-802H-EHWS-1102H-E/HWS-1402H-E
DimensionHxWxD(mm)925 x 525 x 355
Hot water cylinder (option)
Water volumelitres150210300
Max water temperature(°C)75
Electric heater(kW)2.75 (230 V ~)
Height(mm)1,0901,4742,040
Diameter(mm)550
MaterialStainless steel
for hot water cylinder
heater(option)
Heating(°C)20 to 55
Cooling(°C)10 to 25
HWS-
802XWHM3-E
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-
802XWHT6-E
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-
1402XWHM3-E
230 V ~
HWS-
1402XWHT6-E
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
HWS-
1402XWHT9-E
EN
–3–
2-EN
Hydro Unit
Installation Manual
2ACCESSORY PARTS
NoParts name QuantityNoParts name Quantity
1Installation manual (this document)13Insulator for cooling1
2Owner’s manual 1
3PREPARATIONS FOR INSTALLATION
Parts required to connect this product (Common items)
CategoryPartSpecificationQuantity
Strainer (water filter)1 1/4" 30 to 40 meshes1
Water piping
Electrical system
Drain cock (for water charge)1
Isolating ball valves
Earth leakage breaker for main power
supply
Earth leakage breaker for backup heater30 mA1
(Option)
Earth leakage breaker for hot water cylinder
heater
1 1/4"
for service 1 1/4"
30 mA1
30 mA1
2
Options required for each function
Purpose
Heating––
Heating &Cooling
(all rooms)
Heating & Cooling
(partly heating only)
Hot water supply
2-zone control––
Interlocking with
boiler
Interlocking with
booster heater
In the Hydro UnitPurchased part
Part nameModel namePart namePrescribed specification
––Fan coil(s)
––
Hot water cylinder
150 L
210 L
300 L
Output control
board kit (1)
Output control
board kit (1)
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
TBC-PCIN3EBoiler
TBC-PCIN3EElectric heater
Radiator(s), Fan coil(s),
Under floor heating
Motorized 2-way valve (for
cooling)
Motorized 3-way valve
Earth leakage breaker
Motorized mixing valve
Circulator pumpOther power supply
Buffer tank
Refer to “Control parts
specifications” on page 23.
Refer to “Control parts
specifications” on page 23.
Refer to “Control parts
specifications” on page 23.
Other power supply
Signal 12 V input function is
required for boiler.
Other power supply.
Signal 230 V input function
is required for booster
heater
3-EN
–4–
Hydro Unit
Optional Parts
No.Part nameModel nameApplicationRemarks
External output
1
board
External input
2
board
Use specified products for the outdoor unit, Hydro Unit, and hot water cylinder.
Do not use commercially available products.
Use parts that conform to prescribed specifications for parts to be connected to the Hydro Unit.
If unspecified products or parts are used, a malfunction, failure or fire may be caused.
TCB-PCIN3E
TCB-PCMO3E
Boiler-linked output, Alarm output
Defrost signal output, compressor operation
signal output
Cooling/heating thermostat input
Forced-stop signal input
Installation Manual
Up to two boards
(according to applications)
Up to two boards
(according to applications)
4PRECAUTIONS FOR SAFETY
General Safety Precautions
Ensure that all Local, National and International regulations are satisfied.
• Read the “PRECAUTIONS FOR SAFETY” carefully before installation.
• The precautions described below include the important items regarding safety – Observe them without fail.
• After the installation work has been completed, perform a trial operation to check for any problems. Follow the
Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before unit maintenance.
• Ask the customer to keep the Installation Manual along with the Owner’s Manual.
Refrigerant Precautions
• If a refrigerant leak is suspected contact the dealer who supplied the system, in the case of a recharge of
refrigerant ask service personnel for details of the leak and confirmation of the repairs completed.
The refrigerant used in the system is harmless.
• Generally the refrigerant does not leak, however, if the refrigerant should leak into a room and a heater or stove
burner in the room is lit, toxic gas may be generated.
• Do not install the system in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks and stays around the unit a fire may occur.
• Install the refrigerant pipe securely during installation and before operation.
If the compressor is operated with no pipe work connected and valves open the compressor will suck air which
would result in over pressurization of the system which may result in bursting or injury.
Observe the same precautions for refrigerant recovery work (pump back procedure to outdoor unit) and do not
disconnect pipe work until refrigerant is recovered and valves closed.
EN
–5–
4-EN
Hydro Unit
Installation Manual
WARNING
Installation Precautions
• Ask an authorized dealer or qualified installation professional to install/maintain the Air to Water Heat Pump System.
Inappropriate installation may result in water leaks, electric shock or fire.
• Electrical work must be performed by a qualified electrician in accordance with the installation manual.
An inappropriate power supply capacity or installation may result in fire.
• When completing any electrical works to the system ensure that all Local, National and International regulations are
satisfied.
Inappropriate grounding may result in electric shock.
• Use the specified electrical cables, fixing securely at all terminations.
• Earth wire connections.
• Install an earth leakage breaker without fail.
Incomplete grounding can cause electric shock.
Do not ground wires to gas pipes, water pipes, lightning rods or telephone cable ground wires.
• This unit must be connected to the main power supply using a circuit breaker or switch with a contact separation of
at least 3 mm.
• Be sure to turn off all main power supply switches or the circuit breaker before starting any electrical work.
Ensure all power switches are off, failure to do so can cause electric shock.
Use an exclusive power circuit for the Air to Water Heat Pump system using the rated voltage.
• Ensure correct connection of interconnecting wire between Outdoor Unit and Hydro Unit.
Incorrect connection of the interconnecting cable may result in the damage of electrical parts.
• Ensure refrigeration system remains sealed to external gases and air.
Should air or other gases contaminate the refrigeration circuit, high system pressures could result in burst pipes and
injuries.
• Do not modify or bypass any of safety guards or switches in this system.
• After unpacking the outdoor unit, examine the unit carefully for any possible damage.
• Do not install in any place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
• Perform installation work properly in accordance with the installation manual.
Inappropriate installation may result in water leaks, electric shock or fire.
• Tighten all flare nuts with a torque wrench in the specified manner.
Excessive tightening of the flare nut may result in cracking of the pipe work or flare nut which may result in a
refrigerant leakage.
• Wear heavy duty gloves during installation work to avoid injury.
• Install the outdoor unit securely in a location where the base can sustain the weight adequately.
• In enclosed areas, if the refrigerant leaks during installation vacate and ventilate immediately.
• After installation is complete ensure and confirm that refrigerant does not leak.
If refrigerant leaks into a room and flows near a fire source noxious gas may be generated.
• Do not block any drain hoses. Hoses may come off and electric shocks may occur.
• Do not hit the manometer, because it is made of glass. It is breakable.
Notes on System Design
• The input water temperature to the Hydro Unit must be 55°C or less.
Especially, be careful when there is an external heating source such as a boiler.
When hot water over 55°C returns, it may result in a failure of the unit or water leakage.
• The flow rate of the circulating water must meet the following range.
11 and 14 kW 18 L/minute or more
8 kW 13 L/minute or more
If the flow rate becomes less than the minimum, the protective device is activated to stop operation.
Ensure the flow rate with a bypass valve, etc. when you use a flow rate valve for the Hydro Unit.
• Do not drive water by power other than the pump built in the Hydro Unit.
• The backup heater operates supplementarily to exert a prescribed capacity when the heat pump cannot exert its
capacity at a low outside temperature.
• Install the Hydro Unit and water pipes in a place in which they do not freeze.
• Make the water circuit closed. Never use it as an open circuit.
• Circulating water must be 20 liters or more. If total water amount is not enough, the unit may not function fully
due to protective operation.
5-EN
–6–
Hydro Unit
Installation Manual
5EXAMPLE OF HYDRO UNIT INSTALLATION
Example of Installation for Cooling and Heating
When both cooling and heating are used, install a 2-way valve (for cooling) to the pipe to the room for heating only.
Example of 2-Zone Temperature Control and Hot Water Supply
Installation Manual
System
The following shows an example of the 2-zone temperature control.
A buffer tank and a water pump are required for the 2-zone temperature control.
▼ Fig. 5-02
Hi-Pressure
By-Pass
Valve
Temperature
Regulating
Valve
(Mechanical)
TRV
Temp.
Regulating
Valve
(Mechanical)
Strainer (40 mesh / 0.4 mm)
Drain Cock for water
Charge and Drain
TTW
Isolating
Valves
(Service)
Diverting
3-Way
Valve for
Sanitary
Hot
Water
Tank
M
TRV
Zone 1
Fan Coil Unit (Heating
or Cooling)
Motorized 2-Way Valve
is required if fan coil
M
units are in cooling
operation.
Mixing 3-Way
M
Valve for Under
Floor Heating
External Pump for
Under Floor Heating
7-EN
Indirect Sanitary Hot
Water Tank
–8–
TFI
Direct Buffer tank for
Under Floor Heating
Zone 2
Under-floor Heating
(2-Way Valve Control)
Hydro Unit
Installation Manual
6MAIN COMPONENTS OF HYDRO UNIT
Exploded view and description for Hydro Unit
▼ Fig. 6-01
1
2
3
4
5
6
7
8
9
10
11
1 : Expansion vessel
2 : Hi pressure switch (4.15 MPa)
3 : Temperature sensor (for Heat pump outlet -TWO)
4 : Pressure sensor
5 : Heat exchanger
6 : Flow switch (13.0 L/min 17.5 L/min)
7 : Temperature sensor (for refrigerant -TC)
8 : Temperature sensor (for water inlet -TWI)
9 : Drain nipple
10 : Water inlet connection
11 : Refrigerant liquid connection
12 : Air relief valve
13 : Pressure relief valve (0.3 MPa (3 bar))
14 : Thermal protector (auto)
15 : Temperature sensor (for water outlet THO)
16 : Thermal protector (Single operation)
17 : Water pump
18 : Backup heater (3 kW, 3 kW x 2, 3 kW x 3)
19 : Manometer
20 : Water outlet connection
21 : Refrigerant gas connection
12
13
14
15
16
17
18
19
20
21
EN
–9–
8-EN
Hydro Unit
E-Box layout
▼ Fig. 6-02
Installation Manual
P.C. board
MCC-1511
Trans
former
Relay P.C. board
MCC-1217
(Option)
Relay P.C. board
MCC-1217
(Option)
Relay P.C. board
MCC-1431
Relay
(RY06)
MG-SW (RY05)
Relay
(RY03)
Relay
(RY01)
Fuse
MG-SW (RY04)
MG-SW (RY02)
Relay P.C. board
MCC-1214
(Option)
9-EN
–10–
Hydro Unit
Installation Manual
7HYDRO UNIT INSTALLATION
WARNING
• To protect yourself from injury, always use PPE (Personal Protective Equipment), that is, wear gloves.
• Install the Hydro Unit by at least two persons.
• Install the Hydro Unit in a place strong enough to withstand the following weights:
Hydro Unit weight with no water 60 kg (802) 65 kg (1402)
Hydro Unit weight with full water 80 kg (802) 85 kg (1402)
CAUTION
• The operating temperature range is 5 to 32°C (Heating) and 18 to 30°C (Cooling).
Do not install the unit in a place where water freezes.
• Do not install the Hydro Unit in a place where combustible gas may leak.
• Do not install the Hydro Unit in a place exposed to rain or water.
• Do not install the Hydro Unit near equipment which generates heat.
• Do not install the Hydro Unit to a movable object.
• Do not install the Hydro Unit in a place exposed to vibration.
Handling, Unpacking, and Checking the Hydro Unit
• The unit should be checked when it is delivered, and any damage reported immediately to the courier claims the
department.
Positioning
Refrigeration pipe
The length and height of the refrigeration pipe must be within the following values.
As long as the Hydro Unit is installed within these ranges, no additional refrigerant is required.
▼ Fig. 7-01
Outdoor unit
L
H
EN
H: Max. ±30 m (above or below)
L: Max. 30 m
Min. HWS-802H-E : 5 m
HWS-1102H-E : 3 m
HWS-1402H-E : 3 m
–11–
10-EN
Hydro Unit
Installation Manual
Water pipe
Design the water pipe length within the QH characteristics of the pump (Refe to “Fig. 7-16” and “Fig. 7-17” on page 19).
The height of the pipe must be 7 m or less.
▼ Fig. 7-02
H < 7 m
Service space
Secure a service space for the Hydro Unit.
• Do not install the Hydro Unit in a place where heat stagnates.
▼ Fig. 7-03
200 mm
100 mm
500 mm
350 mm
Mounting
Install M10 bolts at the positions shown below and secure them with nuts.
▼ Fig. 7-04
380 mm
500 mm
M10
11-EN
960 mm
–12–
Hydro Unit
Installation Manual
The Hydro Unit can be installed directly without using the fixing angles.
However, the back side of the Hydro Unit can be highly heated, therefore, the installing surface must be heat-
resistant.
▼ Fig. 7-05
Remove the M5a screws to
detach the fixing angles.
▼ Fig. 7-06▼ Fig. 7-07
380
860
Install the Hydro Unit so that its tilting angle falls within the range below.
▼ Fig. 7-08
± 1°
▼ Fig. 7-09
M10
M10
Secure the Hydro Unit with
plain washers and nuts.
± 1°
–13–
EN
12-EN
Hydro Unit
Refrigerant Piping
Installation Manual
WARNING
• THIS SYSTEM ADOPTS HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY THE OZONE LAYER.
• The characteristics of R410A refrigerant are: ease to absorb water, oxidizing membrane or oil, and its pressure is
approximately 1.6 times higher that of R22. Accompanied with the new refrigerant the oil has also been changed.
Therefore during installation work prevention of the invasion of water, dust, former refrigerant or oil is of a paramount
importance.
To prevent the charging of incorrect refrigerants into the system the service valve connection ports have also
increased in size.
• The use of R410A tools is required for correct installation of the system.
• The use of the correct pipe sizes and wall thicknesses of copper pipe work is required for the correct installation of
the system.
CAUTION
• Ensure all refrigerant pipes are protected from the invasion of dust and water.
• Ensure all pipe work connections are tightened to the required torque settings detailed in this section.
• Perform an air tight using Oxygen Free Nitrogen (OFN) only.
• Evacuate the air in the pipe work using a vacuum pump.
• Check for refrigerant gas leaks at all connections throughout the pipe work.
NOTE
The Air to Water Heat Pump system uses R410A refrigerant. It is important that copper pipes used for refrigerant
piping have the following wall thickness:
• 0.8 mm for Ø6.4 mm, Ø9.5 mm and Ø12.7 mm
• 1.0 mm for Ø15.9 mm
Refrigerant pipe sizes
Hydro Unit ModelGas Side (mm)Liquid Side (mm)
8 kW Hydro UnitØ 15.88Ø 9.52
11 & 14 kW Hydro UnitØ 15.88Ø 9.52
Flaring
• Cut the refrigerant pipes to the correct length using a pipe cutter. Remove any burrs that may be on the pipes as
these may cause refrigerant leaks or component failure in the refrigeration cycle.
• Place the correct size flare nuts onto the pipes (use the flare nuts supplied with the Hydro Unit or use flare nuts
designed specifically for R410A refrigerant) and then flare the pipes using the correct flaring tool.
13-EN
–14–
Hydro Unit
Installation Manual
Tightening
• Connect the refrigerant pipes, from the outdoor unit, to the Hydro Unit as shown below.
Fig. 7-10
Gas line Ø 15.88
Liquid line Ø 9.52
• Align the flare connection on each pipe with the corresponding outlet connection on the Hydro Unit.
Tighten the flare nuts, using fingers, to secure the pipes in place.
• Tighten the flare nuts, using a torque wrench, to the tightening torques shown below:
Outer Ø of Copper Pipe (mm)Tightening Torque (N/m)
9.533 to 42
15.963 to 77
• To prevent damage, to the refrigerant pipes, use two spanners to tighten the flare nut connections to the required
torque.
Water Pipe
WARNING
• Install water pipes according to the regulations of respective countries.
• Install water pipes in a freeze-free place.
• Make sure that water pipes have sufficient pressure resistance.
The setting value of the pressure relief valve is 0.3 MPa.
CAUTION
• Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.
• The water to be used must meet the water quality standard specified in EN directive 98/83 EC.
EN
–15–
14-EN
Hydro Unit
Installation Manual
Water circuit
• Install a strainer with 30 to 40 meshes (procured locally) at the water inlet of the Hydro Unit.
• Install drain cocks (procured locally) for water charge and discharge at the lower part of the Hydro Unit.
• Make the piping route a closed circuit. (An open water circuit may cause a failure.)
▼ Fig. 7-11
Attention
To avoid water leak, exchange the seal
tapes to new one.
Attention
Water (used at test in factory before
shipping) may be found in the caps.
Hot water outlet
connection 1 1/4"
▼ Fig. 7-12
Water inlet connection
1 1/4"
Inlet
Isolating Ball Valve
Strainer (30 to 40
meshes)
Drain cock for
water charge
and discharge
15-EN
Local arrangement
–16–
Hydro Unit
tohyd
it
Installation Manual
Piping to hot water tank (option)
Water supplied to the hot water cylinder is branched by a motorized 3-way valve (procured locally).
For the specifications of the motorized 3-way valve, refer to “Control parts specifications” on page 23.
Connect the hot water cylinder to port A (open when energized) of the valve.
▼ Fig. 7-13
ro un
room heating or cooling
B
Open when de-energized
AB
to hot water cylinder
A
Open when energized
Piping to 2-zone operation
To perform 2-zone temperature control, circulate water by another pump (procured locally) through a motorized
mixing valve (procured locally) and a buffer tank (procured locally).
For the specifications of the motorized mixing valve, Refer to “Control parts specifications” on page 23.
▼ Fig. 7-14
Water pump
(Procured locally)
Zone 2
Motorized mixing valve
(Procured locally)
AB
A
Open when
energized
to hydro unit
B
Open when
de-energized
Buffer tank
(Procured locally)
Checking water volume and initial pressure of expansion vessel
The expansion vessel of the Hydro Unit has a capacity of 12 liters.
The initial pressure of the expansion vessel is 0.1 MPa (1 bar).
The pressure of the safety valve is 0.3 MPa (3 bar).
Verify whether the capacity of the expansion vessel is sufficient using the following expression. If the volume is
insufficient, add the capacity locally.
–17–
EN
16-EN
Hydro Unit
Installation Manual
Expression for expansion vessel selection
V:Necessary total tank capacity ( )
:Water expansion coefficient at average hot water temperature
Vs: Total water amount in the system
P1: System pressure at tank setting position (MPaabs.)
(Pipe inner pressure during pump operation before heating device operates = water supply pressure)
P2: Maximum pressure used during operation at tank setting position (MPaabs.)
(= safety valve setting pressure)
* The absolute pressure value (abs.) is obtained by adding the atmospheric pressure (0.1 MPa (1 bar)) to the
gauge pressure.
▼ Tank selection method
Water temperature and expansion coefficient
Hot water temperature (°C)Expansion rate
00.0002500.0121
40.0000550.0145
50.0000600.0171
100.0003650.0198
150.0008700.0229
200.0017750.0258
250.0029800.0292
300.0043850.0324
350.0050900.0961
400.0078950.0967
450.0100
Hot water temperature (°C)Expansion rate
▼ Fig. 7-15
18
16
14
12
10
8
6
4
2
Expansion vessel volume( )
0
050100150
Water volume ( )
*Hot water temperature 55ºC
250200300
Install an external expansion vessel when the capacity of the expansion vessel is insufficient.
Charge water until the pressure gauge shows 0.2 MPa (2 bar).
Hydraulic pressure may drop when the trial run begins. In that case, add water.
Air may enter if the charged hydraulic pressure is low.
Loosen the purge valve cap by two turns to release air.
Installation Manual
▼ Fig. 7-18
Loosen the air vent screw of the pump, pull out air in the pump, and tighten again.
Loosen the cap of the pressure relief valve to release air.
Water may come out of the pressure relief valve.
Release the air completely from the water circuit. Failure to do so may disable correct operation.
Loosen 2 turns for
proper venting
Water quality
The water used must satisfy EN directive 98/83 EC.
Piping insulation
It is recommended that insulation treatment be applied to all pipes. To perform optional cooling operation, apply
insulation treatment of 20 t or more to all pipes.
19-EN
–20–
Hydro Unit
Electrical Installation
Installation Manual
WARNING
• Ensure electrical circuits are isolated before commencing the electrical installation.
• The electrical installation must be completed by a qualified electrician.
• The electrical installation must comply to all Local, National and International electrical installation regulations.
• This product must be earthed in accordance with Local, National and International electrical installation regulations.
CAUTION
• The Hydro Unit must be connected to a dedicated power supply for the back up heater circuit.
• The electrical supply must be protected by a suitably sized over current protection device (fuse, MCB etc) and an
earth leakage protection device.
• The Hydro Unit must be connected to the mains power supply using a isolating switch which disconnects all poles
and has a contact separation of at least 3 mm.
• The cord clamps, attached to the Hydro Unit, must be used to secure the electrical cables.
• Wrong connection of electrical cables may result in electrical component failure or fire.
• Ensure the electrical cables are sized in accordance with the installation instructions.
Power line
▼ Fig. 7-19
Input power
230 V ~
50 Hz
Leakage
breaker
30 mA
Backup heater
230 V ~ (3 kW type)
Input power
230 V ~
50 Hz
Leakage
breaker 30 mA
N
L
TB02TB02
1
2
3
L
N
1
2
TB01
3
Backup heater
400 V 3N ~ (6.9 kW type)
Input power
400 V 3N ~
50 Hz
Leakage
breaker 30 mA
L3
L1
L2
TB03
L1
1
2
L
N
N
Leakage
breaker
30 mA
Hot water cylinder
1
2
EN
Input power for
cylinder heater
230 V ~ 50 Hz
Hydro unitOutdoor unit
–21–
20-EN
Hydro Unit
Control line
Installation Manual
▼ Fig. 7-20
Pump (local)
Max 12 m
230 V 100 mA
0.75 mm² or more
Booster heater
(local)
Max 12 m
230 V 1 A
0.75 mm² or more
2Way-Valve for
cooling stop
Max 12 m
230 V 1 A
0.75 mm² or more
3Way-Valve for hot
water cylinder
Alert output
(local)
Mixing-Valve
type 2 for 2
zone control
4
2
3
1
TB04
TB04
1
2
3
4
TB05
5
6
7
8
CN208
OPTIONOPTION
9
PJ20
2
1
4
3
Boiler operation
(local)
Mixing-Valve type
1 for 2 zone control
Max 12 m
230 V 100 mA
0.75 mm² or more
N
CW
CCW
4
2
3
1
TB06
CN209
PJ20
2
1
4
3
Defrost output
(local)
Max 5 m shield wire
0.75 mm² or more
A
B
C
D
Temp sensor
for 2 zone
control
Compressor
operation output
(local)
Temp sensor in hot
water cylinder
A
B
Max 5 m shield
wire 0.75 mm² or
more
Max 12 m
non voltage
0.75 mm² or more
▼ Fig. 7-21
TB03
TB01
51
52
WPM
TTW
Sensor
connection
55
53
TB 05
54
2WV
6B6A6D
6C
TF1
TB 06
565758
BH
Don't apply
220-240V
or
breakdown
will occur.
to Outdoor unit
Outdoor unit
connection
3WV
1
11 12
59
2
TB 01
3
13
43
42
MIXV
TB 04
31 32
HOT WATER CYLINDER
TB 03
44
L
Input
power
230 V ~
41
Hot
water
cylinder
50 Hz
Hot water
cylinder power
supply
TB02
L3
N
L2L1
N
L
N
TB 02
Input
power
230 V ~
50 Hz
Backup heater
power supply
L3
L1 L2
N
Input
power
400 V 3N ~
50 Hz
21-EN
–22–
Hydro Unit
Installation Manual
Electrical supply/cable specifications
▼ Wiring specifications
DescriptionPOWER SUPPLY
14 kW230 V ~ 50 Hz22.8 A25 A2.5 mm² or more
Outdoor unit
power
8 kW230 V ~ 50 Hz20.8 A25 A2.5 mm² or more
Outdoor-Hydro––1.5 mm² or more, ,
3 kW230 V ~ 50 Hz13 A16 A1.5 mm² or more, (TB02)
Hydro inlet heater
power
Hydro cylinder heater power 230 V ~ 50 Hz12 A16 A1.5 mm² or more, (TB03)
Hydro - cylinder–12 A–1.5 mm² or more, (TB03)
6 kW400 V 3N ~ 50 Hz 13 A (13 A x 2P)16 A1.5 mm² or more
9 kW400 V 3N ~ 50 Hz 13 A (13 A x 3P)16 A1.5 mm² or more
Maximum
current
▼ Wiring specifications (control line)
DescriptionLine spec
3-way valve control2 line or 3 line 100 mA12 m0.75 mm² or more
Mixing valve control3 line 100 mA12 m0.75 mm² or more
2-zone thermo sensor 2 line 100 mA5 m0.75 mm² or more, (TB06)
Cylinder thermo sensor
Second remote controller2 line 50 mA50 m0.75 mm² or more, (TB07)
2+GND(shield
wire)
Maximum
current
100 mA5 m0.75 mm² or more, (TB06)
Installation fuse
rating
Maximum length
Power wire
Connection
destination
,11 kW230 V ~ 50 Hz22.8 A25 A2.5 mm² or more
, , ,
(TB02)
Connection
destination
, ,
(TB05)
, ,
or
, ,
(TB04)
▼ Control parts specifications
PowerMaximum currentType
Motorized 3-way valve
(for hot water)
Motorized 2-way valve
(for cooling)
Motorized mixing valve
type 1 (for 2-zone)
AC 230 V 100 mA
AC 230 V 100 mAspring return type (normally open )
AC 230 V 100 mA
Spring return type
Note: 3-wire SPST and SPDT type can be used by changing
DIP switch 13-1.
60 sec 90º. SPDT type
Note: SPST and 20 to 240 sec type can be used by changing
the function code.
▼ Output line specifications
DescriptionOutput
External pump No.1AC230V1 A–12 m
External boost heaterAC230V1 A–12 m
Boiler control
ALARM Output
Compressor operation
output
Non-voltage
contacts
Non-voltage
contacts
Non-voltage
contacts
Maximum
current
0.5 AAC230 V12 m
1 ADC24 V12 m
0.5 AAC230 V12 m
1 ADC24 V12 m
0.5 AAC230 V12 m
1 ADC24 V12 m
Max
voltage
Maximum
length
EN
Output as required when outdoor air
temperature is -20°C or less
Output as required when outdoor air
temperature is -10°C or less
–23–
22-EN
Hydro Unit
Installation Manual
DescriptionOutput
Defrost Output
Non-voltage
contacts
Maximum
current
0.5 AAC230 V12 m
1 ADC24 V12 m
Max
voltage
Maximum
length
▼ Input line specifications
DescriptionInputMaximum length
Emergency stop controlNon-voltage12 m
Cylinder thermostat inputNon-voltage12 m
Cooling thermostat inputNon-voltage12 m
Heating thermostat inputNon-voltage12 m
CAUTION
Earthing arrangements
The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations.
It is essential that the equipment is earthed to prevent the electric shock and damage to the equipment.
Electrical connection to hydro unit
• Remove the front cover and the electrical box cover from the Hydro Unit.
• The Hydro Unit power cable must be sized in accordance with refer to “Electrical supply/cable specifications”.
• Connect the Hydro Unit power cable to Terminal 02 as shown below.
Single Phase Units: Live conductor – Terminal L1
• Ensure the Hydro Unit power cable is secured using the cable clamp fitted in the electrical box.
• Ensure the Hydro Unit power cable connection terminals are tight.
23-EN
Outdoor unit to hydro unit electrical connection
Fig. 7-22
(Main circuit)
Input power
230 V~,
50 Hz
Earth
Earth
Leakage
breaker
• Ensure electrical circuits are isolated before commencing work.
• The Outdoor Unit to Hydro Unit interconnecting cable must be sized in accordance with refer to “Electrical supply/
cable specifications”.
• Connect the Outdoor Unit to Hydro Unit interconnecting cable as shown in the diagram above.
(Hydro/outdoor
connecting wires)
L
N
Outdoor unit
Earth
11
22
33
Earth
Hydro Unit: Terminal 01
Remote controller
Hydro unit
–24–
Hydro Unit
Installation Manual
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp fitted in the
electrical box.
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight.
Electrical connection for external booster heater
CAUTION
• The maximum current available from the booster heater output is 1 A. Do not connect the booster
pump directly to Terminal Block 05 on the Hydro Unit. A separate contactor, supplied locally, must
be used to supply the booster heater.
• The booster heater can be installed only for room heating and cannot be used for hot water supply.
• Install the booster heater downstream of the 3-way valve on the indoor unit side.
The booster heater is an external heater, supplied locally, used to assist the Hydro Unit during low ambient
conditions.
• The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor. (Supplied locally)
• The output from the Hydro Unit is only enabled when the outdoor air temperature is less than -20°C.
• Ensure the external booster heater is installed and set up in accordance with all Local, National and International
regulations.
• Connect the external booster heater to the Hydro Unit in accordance with the diagram shown below.
• Connect the coil, of the field supplied contactor, to terminals 5 & 6 on Terminal Block 05. The contactor will
energize in the event of low ambient conditions.
• A separate dedicated electrical supply must be used for the external booster heater. This must be connected
through the contacts on the field supplied contactor.
▼ Fig. 7-23
Booster Heater
123456789
Terminal Block 05
Electrical connection for external additional pumps
• The Hydro Unit has the facility to connect an additional circulating pump, if required, into the heating or cooling
system.
• There is an output available from the Hydro Unit. AC230 V 1 A (maximum) is available from each output. The
output for each additional pump is synchronized with the operation of the main circulating pump inside the Hydro
Unit.
• Connect the additional pumps as shown in the diagram below.
• Connect external pump 1 to terminals 1 & 2 on Terminal Block 05.
• Install external pumps so that their motive power does not affect the internal pump.
EN
▼ Fig. 7-24
Pump
01
123456789
–25–
Terminal Block 05
24-EN
Hydro Unit
3-way valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA
Valve Diameters: Port A, Port B: Ø 1 1/4"
Return Mechanism: 3 types of 3-way valve (diverter) can be used.
Set the 3-way valve in use with the DIP switch SW13-1 on the Hydro Unit board.
SW13-1
Type 12-wire spring return OFF
Type 23-wire SPSTOFF
Type 33-wire SPDTON
NOTE
Continuous operation of the valve motor at the fully open position is not recommended.
• The 3-way diverter valve is used to select either domestic hot water or space heating.
• Connect the 3-way diverter valve to terminals 7, 8 and 9 on Terminal Block 05.
• Connect the 3-way diverter valve in accordance with the diagram below:-
Installation Manual
▼ Fig. 7-25
▼ Fig. 7-26
Type 1: SPRING RETURNType 2: SPST
port “A” to Hot water
cylinder
port “AB” to
Hydro unit
port “A” open
Hydro Unit
TB 05
7
8
port “AB” to
Hydro unit
9
port “B” to Room heating
or cooling
▼ Fig. 7-27
Type 3: SPDT
port “A” to Hot water
port “AB” to
Hydro unit
cylinder
port “A”
close
open
Hydro Unit
TB 05
7
8
port “A” to Hot water
cylinder
port “B” to Room heating
or cooling
port “A”
close
open
Hydro Unit
TB 05
7
8
9
25-EN
9
port “B” to Room heating
or cooling
–26–
Loading...
+ 60 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.